SYNSO-UPSMIB
Synso Inc.snmptranslate -m SYNSO-UPSMIB -Tpsnmpwalk -v2c -c <community> -m SYNSO-UPSMIB <host> 1.3.6.1.4.1.9557Imports
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
|---|---|
| SNMPv2-SMI | Bits, Integer32, IpAddress, MODULE-IDENTITY, MibIdentifier, OBJECT-IDENTITY, OBJECT-TYPE, TimeTicks, Unsigned32, enterprises, iso |
| SNMPv2-TC | DisplayString, PhysAddress, TEXTUAL-CONVENTION |
OID tree
| Name | OID | Type | Access | Status |
|---|---|---|---|---|
| Nsynso | 1.3.6.1.4.1.9557 | |||
| NsynsoUpsSoftware | 1.3.6.1.4.1.9557.1 | |||
| NsyupsBasicSetting | 1.3.6.1.4.1.9557.1.1 | |||
| SsyupsPlatForm | 1.3.6.1.4.1.9557.1.1.1 | DisplayString (SIZE (0..31)) | RO | mandatory |
scalar · DisplayString (SIZE (0..31)) · read-only · mandatory The platform which the UPS software is running on. | ||||
| TsyupsFeatureTable | 1.3.6.1.4.1.9557.1.1.2 | NA | mandatory | |
table · not-accessible · mandatory A table containing the supported features. | ||||
| RsyupsFeatureEntry | 1.3.6.1.4.1.9557.1.1.2.1 | NA | mandatory | |
row · not-accessible · mandatory An entry representing the support information for a feature.
| ||||
| CsyupsFeature | 1.3.6.1.4.1.9557.1.1.2.1.1 | INTEGER | RO | mandatory |
column · INTEGER · read-only · mandatory The string representing a feature. | ||||
| CsyupsSupportInfo | 1.3.6.1.4.1.9557.1.1.2.1.2 | DisplayString | RO | mandatory |
column · DisplayString · read-only · mandatory The string containing the support information for a feature. | ||||
| SsyupsSystemStartTime | 1.3.6.1.4.1.9557.1.1.3 | INTEGER | RO | mandatory |
scalar · INTEGER · read-only · mandatory The time that the UPS software starts. It is the
number of seconds elapsed since 00:00:00,
January 1, 1970. | ||||
| SsyupsSignalType | 1.3.6.1.4.1.9557.1.1.4 | INTEGER | RW | mandatory |
scalar · INTEGER · read-write · mandatory The signaling method between the UPS and software.
When the basicSignal used, the UPS changes the voltage
level of some specific pins to notify the software of what
critical event occurs. Usually, the UPS will inform
software when a power failure or a low battery condition
occurs. On the other hand, the software can change the
voltage signal of a specific pin to ask the UPS to shut
down (turn off).
When the smartSignal used, the UPS asks like a standard
communication device (such as mouse or modem). That means
the UPS and software communicate with each other using a
pre-defined protocol. The protocol should include at
least the following commands:
- query the power status of the UPS
- query the power data of the UPS
- command the UPS to shut down
| ||||
| SsyupsBasicSignalDefinition | 1.3.6.1.4.1.9557.1.1.5 | INTEGER | RO | mandatory |
scalar · INTEGER · read-only · mandatory The signal definitions for the basic signaling UPS. The
value can be the following bit combinations:
SG_POWER_FAILURE_ENABLE 0x01
SG_BATTERY_LOW_ENABLE 0x02
SG_SHUTDOWN_ENABLE 0x04
SG_POWER_FAILURE_VOLTHIGH 0x10
SG_BATTERY_LOW_VOLTHIGH 0x20
SG_SHUTDOWN_VOLTHIGH 0x40
SG_POWER_FAILURE_ENABLE, SG_BATTERY_LOW_ENABLE, and
SG_SHUTDOWN_ENABLE indicate whether the signals for
a power failure , a low battery condition, and the UPS
shutdown are enabled. SG_POWER_FAILURE_VOLTHIGH,
SG_BATTERY_LOW_VOLTHIGH, and SG_SHUTDOWN_VOLTHIGH indicate
whether the voltage level for these signals are high or low. | ||||
| SsyupsUpsComPort | 1.3.6.1.4.1.9557.1.1.6 | DisplayString (SIZE (0..31)) | RW | mandatory |
scalar · DisplayString (SIZE (0..31)) · read-write · mandatory The serial port which the UPS software use to communicate with the UPS. The format varies from platform to platform. For DOS program, the format is 'portNo, portAddress, portIRQ' (e.g. '1, 0x2f8, 3' for COM2). For Windows program, it is 'portNo'. For NetWare program, it is 'portType, boardNo, portNo'. For UNIX, it is 'device name'. | ||||
| SsyupsModemComPort | 1.3.6.1.4.1.9557.1.1.7 | DisplayString (SIZE (0..31)) | RW | mandatory |
scalar · DisplayString (SIZE (0..31)) · read-write · mandatory The serial port which the UPS software use to dial out when some particular events occur. The format varies from platform to platform. For DOS program, the format is 'portNo, portAddress, portIRQ' (e.g. '1, 0x2f8, 3' for COM2). For Windows program, it is 'portNo'. For NetWare program, it is 'portType, boardNo, portNo'. For UNIX, it is 'device name'. | ||||
| NsyupsUpsExtension | 1.3.6.1.4.1.9557.1.2 | |||
| SsyupsUpsAlarm | 1.3.6.1.4.1.9557.1.2.1 | INTEGER | RO | mandatory |
scalar · INTEGER · read-only · mandatory It is used internally. Each bit indicates a critical event, such as input bad, on battery, communications lost, ...,etc. | ||||
| SsyupsSerialNo | 1.3.6.1.4.1.9557.1.2.2 | DisplayString (SIZE (0..63)) | RO | mandatory |
scalar · DisplayString (SIZE (0..63)) · read-only · mandatory The serial number of the UPS connected to the UPS software. | ||||
| SsyupsConfigBatteryVoltage | 1.3.6.1.4.1.9557.1.2.3 | INTEGER | RO | mandatory |
scalar · INTEGER · read-only · mandatory The nominal battery voltage. | ||||
| SsyupsBatteryReplaceDate | 1.3.6.1.4.1.9557.1.2.4 | INTEGER | RW | mandatory |
scalar · INTEGER · read-write · mandatory The last battery replacement date. It represents the number of days elapsed since January 1, 1901. | ||||
| SsyupsNoOutlet | 1.3.6.1.4.1.9557.1.2.5 | INTEGER | RO | mandatory |
scalar · INTEGER · read-only · mandatory The total number of controllable outlets. | ||||
| SsyupsOutletParamter | 1.3.6.1.4.1.9557.1.2.6 | DisplayString | RW | mandatory |
scalar · DisplayString · read-write · mandatory This object is not used any more. | ||||
| SsyupsShutdownDepend | 1.3.6.1.4.1.9557.1.2.7 | DisplayString (SIZE (0..255)) | RW | mandatory |
scalar · DisplayString (SIZE (0..255)) · read-write · mandatory A string containing those who should perform their shutdown procedure before the UPS turns off. The agent will inform each one in the list to begin their shutdown procedure before it turns off the power of the UPS. | ||||
| SsyupsEnableAutoSave | 1.3.6.1.4.1.9557.1.2.8 | INTEGER | RW | mandatory |
scalar · INTEGER · read-write · mandatory Setting it to 1, the agent will try to save all files opened by applications before shutting down the operation system. Setting it to 0 will disable the auto save feature. | ||||
| SsyupsShutdownOsDelay | 1.3.6.1.4.1.9557.1.2.9 | INTEGER | RW | mandatory |
scalar · INTEGER · read-write · mandatory The delay time before shutting down the operation system. When it is necessary to shut down the operation system, the agent will run the specified command file and try to save all files opened by applications before shutting down the OS. This delay time is used to do such things. | ||||
| SsyupsShutdownUpsDelay | 1.3.6.1.4.1.9557.1.2.10 | INTEGER | RW | mandatory |
scalar · INTEGER · read-write · mandatory The delay time before shutting down the UPS. Before shutting down the operation system, the agent will send a command to tell the UPS to shut down. This delay time is used to allow the agent to shut down the operation system safely. | ||||
| SsyupsSaveConfig | 1.3.6.1.4.1.9557.1.2.11 | INTEGER | RW | mandatory |
scalar · INTEGER · read-write · mandatory Used to inform the agnet to save the configurations. Its value indicates which group to be saved. For example, a 1 indicates group 1 (syupsBasicSetting) to be saved, a 6 1 indicates group 6 (syupsCoworker) to be saved. You have to use it to save configurations after changing settings, or the settings may be lost. | ||||
| SsyupsNoOutlets | 1.3.6.1.4.1.9557.1.2.12 | INTEGER | RO | mandatory |
scalar · INTEGER · read-only · mandatory The number of controllable outlets. | ||||
| TsyupsOutletTable | 1.3.6.1.4.1.9557.1.2.13 | NA | mandatory | |
table · not-accessible · mandatory A list of outlet table entries. The number of entries is given by the value of syupsNoOutlets. | ||||
| RsyupsOutletEntry | 1.3.6.1.4.1.9557.1.2.13.1 | NA | mandatory | |
row · not-accessible · mandatory An entry containing information applicable to a particular controllable outlet.
| ||||
| CsyupsOutletIndex | 1.3.6.1.4.1.9557.1.2.13.1.1 | INTEGER | NA | mandatory |
column · INTEGER · not-accessible · mandatory The outlet identifier. | ||||
| CsyupsOutletDescription | 1.3.6.1.4.1.9557.1.2.13.1.2 | DisplayString (SIZE (0..15)) | RW | mandatory |
column · DisplayString (SIZE (0..15)) · read-write · mandatory The outlet description. | ||||
| CsyupsOutletShutdownDelay | 1.3.6.1.4.1.9557.1.2.13.1.3 | INTEGER | RW | mandatory |
column · INTEGER · read-write · mandatory The delay time (in seconds) before turning off the outlet. Before turning off the outlet, the agent will send a shutdown command to anyone specified in the syupsOutletShutdownDepend, telling them to start their shutdown procedure. This delay time is used to allow those cmputers to be shut down safely. | ||||
| CsyupsOutletShutdownDepend | 1.3.6.1.4.1.9557.1.2.13.1.4 | DisplayString (SIZE (0..63)) | RW | mandatory |
column · DisplayString (SIZE (0..63)) · read-write · mandatory A string containing those who should perform their shutdown procedure before the outlet turns off. The agent will inform each one in the list to begin their shutdown procedure before it turns off the power of the outlet. | ||||
| SsyupsOutletOperator | 1.3.6.1.4.1.9557.1.2.14 | DisplayString | RW | mandatory |
scalar · DisplayString · read-write · mandatory The operator is used to control the outlets. There are two commands: 1. 'SWITCH: OutletNo, OnOff'. The OutletNo specify the outlet. The OnOff can be 0 (off) or 1 (on). For example, 'SWITCH: 2, 1' means turning on (1) the outlet #2. 'SWITCH: 4, 0' means turning off (0) the outlet #4. 2. 'SET: OutletNo, Desc, DelayTime, Depend'. The OutletNo specify the outlet. The Desc specifies the outlet description. The DelayTime specifies the shutdown delay time for the outlet. The Depend specifies the shutdown dependent list for the outlet. For example, 'SET: 3, My Printer, 20, 192.168.1.9' means setting the description of outlet #3 to 'My Printer', the shutdown delay time to 20 seconds and the Shutdown Dependent to '192.168.1.9'. | ||||
| NsyupsEventAction | 1.3.6.1.4.1.9557.1.3 | |||
| SsyupsNoEventActionEntries | 1.3.6.1.4.1.9557.1.3.1 | INTEGER | RO | mandatory |
scalar · INTEGER · read-only · mandatory The number of event-action items. This variable indicates the number of rows in the event-action table. | ||||
| TsyupsEventActionTable | 1.3.6.1.4.1.9557.1.3.2 | NA | mandatory | |
table · not-accessible · mandatory A list of event action entries. The number of entries is given by the value of syupsNoEventActionEntries. | ||||
| RsyupsEventActionEntry | 1.3.6.1.4.1.9557.1.3.2.1 | NA | mandatory | |
row · not-accessible · mandatory An entry containing information applicable to a particular event action.
| ||||
| CsyupsEventId | 1.3.6.1.4.1.9557.1.3.2.1.1 | INTEGER | RO | mandatory |
column · INTEGER · read-only · mandatory The event ID. | ||||
| CsyupsLogEnable | 1.3.6.1.4.1.9557.1.3.2.1.2 | INTEGER | RW | mandatory |
column · INTEGER · read-write · mandatory Whether to log the event in the log file when it occurs. A 1 indicates enable, a 0 indicates disable.
| ||||
| CsyupsNotifyEnable | 1.3.6.1.4.1.9557.1.3.2.1.3 | INTEGER | RW | mandatory |
column · INTEGER · read-write · mandatory Whether to notify users when the event occurs. A 1 indicates enable, a 0 indicates disable.
| ||||
| CsyupsNotifyDelay | 1.3.6.1.4.1.9557.1.3.2.1.4 | INTEGER | RW | mandatory |
column · INTEGER · read-write · mandatory How long the event must last before notifying users. | ||||
| CsyupsNotifyMessage | 1.3.6.1.4.1.9557.1.3.2.1.5 | DisplayString (SIZE (0..63)) | RW | mandatory |
column · DisplayString (SIZE (0..63)) · read-write · mandatory The message which will be sent when the event occurs. | ||||
| CsyupsNotifyPeriod | 1.3.6.1.4.1.9557.1.3.2.1.6 | INTEGER | RW | mandatory |
column · INTEGER · read-write · mandatory How often (in seconds) to send the message. The -1 means once. | ||||
| CsyupsNotifyUsers | 1.3.6.1.4.1.9557.1.3.2.1.7 | DisplayString (SIZE (0..255)) | RW | mandatory |
column · DisplayString (SIZE (0..255)) · read-write · mandatory Who will receive the message when the event occurs. | ||||
| CsyupsEmailEnable | 1.3.6.1.4.1.9557.1.3.2.1.8 | INTEGER | RW | mandatory |
column · INTEGER · read-write · mandatory Whether to email users when the event occurs. A 1 indicates enable, a 0 indicates disable.
| ||||
| CsyupsEmailDelay | 1.3.6.1.4.1.9557.1.3.2.1.9 | INTEGER | RW | mandatory |
column · INTEGER · read-write · mandatory How long the event must last before emailing users. | ||||
| CsyupsEmailMessage | 1.3.6.1.4.1.9557.1.3.2.1.10 | DisplayString (SIZE (0..63)) | RW | mandatory |
column · DisplayString (SIZE (0..63)) · read-write · mandatory The additional message which will be sent when the event occurs. | ||||
| CsyupsEmailUsers | 1.3.6.1.4.1.9557.1.3.2.1.11 | DisplayString (SIZE (0..255)) | RW | mandatory |
column · DisplayString (SIZE (0..255)) · read-write · mandatory Who will receive the mail when the event occurs. | ||||
| CsyupsPageEnable | 1.3.6.1.4.1.9557.1.3.2.1.12 | INTEGER | RW | mandatory |
column · INTEGER · read-write · mandatory Whether to page users when the event occurs. A 1 indicates enable, a 0 indicates disable.
| ||||
| CsyupsPageDelay | 1.3.6.1.4.1.9557.1.3.2.1.13 | INTEGER | RW | mandatory |
column · INTEGER · read-write · mandatory How long the event must last before paging users. | ||||
| CsyupsPageMessage | 1.3.6.1.4.1.9557.1.3.2.1.14 | DisplayString (SIZE (0..15)) | RW | mandatory |
column · DisplayString (SIZE (0..15)) · read-write · mandatory The message which will be sent when the event occurs. | ||||
| CsyupsPageUsers | 1.3.6.1.4.1.9557.1.3.2.1.15 | DisplayString (SIZE (0..255)) | RW | mandatory |
column · DisplayString (SIZE (0..255)) · read-write · mandatory Who will receive the code when the event occurs. | ||||
| CsyupsCommandEnable | 1.3.6.1.4.1.9557.1.3.2.1.16 | INTEGER | RW | mandatory |
column · INTEGER · read-write · mandatory Whether to execute the external command file when the event occurs. A 1 indicates enable, a 0 indicates disable.
| ||||
| CsyupsCommandDelay | 1.3.6.1.4.1.9557.1.3.2.1.17 | INTEGER | RW | mandatory |
column · INTEGER · read-write · mandatory How long the event must last before executing the external command file. | ||||
| CsyupsCommandFile | 1.3.6.1.4.1.9557.1.3.2.1.18 | DisplayString (SIZE (0..63)) | RW | mandatory |
column · DisplayString (SIZE (0..63)) · read-write · mandatory The external command file which will be executed when the event occurs. | ||||
| CsyupsShutdownEnable | 1.3.6.1.4.1.9557.1.3.2.1.19 | INTEGER | RW | mandatory |
column · INTEGER · read-write · mandatory Whether to shut down the system when the event occurs. A 1 indicates enable, a 0 indicates disable.
| ||||
| CsyupsShutdownDelay | 1.3.6.1.4.1.9557.1.3.2.1.20 | INTEGER | RW | mandatory |
column · INTEGER · read-write · mandatory How long the event must last before shutting down the system. | ||||
| NsyupsHistory | 1.3.6.1.4.1.9557.1.4 | |||
| SsyupsMaxEventFileLength | 1.3.6.1.4.1.9557.1.4.1 | INTEGER | RW | mandatory |
scalar · INTEGER · read-write · mandatory The maximum length (in bytes) of the event log file. UPS software will cut the first half of the file whenever the file exceeds this maximum length. | ||||
| SsyupsEventNumRecords | 1.3.6.1.4.1.9557.1.4.2 | INTEGER | RO | mandatory |
scalar · INTEGER · read-only · mandatory The total number of records in the event log file. | ||||
| TsyupsEventTable | 1.3.6.1.4.1.9557.1.4.3 | NA | mandatory | |
table · not-accessible · mandatory A list of event entries. Each entry represents a record in the event log file. | ||||
| RsyupsEventEntry | 1.3.6.1.4.1.9557.1.4.3.1 | NA | mandatory | |
row · not-accessible · mandatory An entry representing a record in the event log file.
| ||||
| CsyupsEventIndex | 1.3.6.1.4.1.9557.1.4.3.1.1 | INTEGER | RO | mandatory |
column · INTEGER · read-only · mandatory The record number of an event entry. | ||||
| CsyupsEventRecord | 1.3.6.1.4.1.9557.1.4.3.1.2 | DisplayString | RO | mandatory |
column · DisplayString · read-only · mandatory The string containing an event entry. | ||||
| SsyupsDataRecordInterval | 1.3.6.1.4.1.9557.1.4.4 | INTEGER | RW | mandatory |
scalar · INTEGER · read-write · mandatory The number of minutes to wait between each recording to the data log file. | ||||
| SsyupsMaxDataFileLength | 1.3.6.1.4.1.9557.1.4.5 | INTEGER | RW | mandatory |
scalar · INTEGER · read-write · mandatory The maximum length (in bytes) of the data log file. UPS software will cut the first half of the file whenever the file exceeds this maximum length. | ||||
| SsyupsDataNumRecords | 1.3.6.1.4.1.9557.1.4.6 | INTEGER | RO | mandatory |
scalar · INTEGER · read-only · mandatory The total number of records in the data log file. | ||||
| TsyupsDataTable | 1.3.6.1.4.1.9557.1.4.7 | NA | mandatory | |
table · not-accessible · mandatory A list of data entries. Each entry represents a record in the data log file. | ||||
| RsyupsDataEntry | 1.3.6.1.4.1.9557.1.4.7.1 | NA | mandatory | |
row · not-accessible · mandatory An entry representing a record in the data log file.
| ||||
| CsyupsDataIndex | 1.3.6.1.4.1.9557.1.4.7.1.1 | INTEGER | RO | mandatory |
column · INTEGER · read-only · mandatory The record number of a data entry. | ||||
| CsyupsDataRecord | 1.3.6.1.4.1.9557.1.4.7.1.2 | DisplayString | RO | mandatory |
column · DisplayString · read-only · mandatory The string containing a data entry. | ||||
| SsyupsHistoryOperator | 1.3.6.1.4.1.9557.1.4.8 | DisplayString | RW | mandatory |
scalar · DisplayString · read-write · mandatory The operator which is used to operate on the history file. The command format is 'Command, File, Range'. So far, Command can be PURGE, File can be EVENT or DATA, and Range can be ALL or 'mm/dd/year..mm/dd/year'. For example, 'PURGE, EVENT, ALL' tells the UPS software to purge all entries in the event log file. And 'PURGE, DATA, 03/20/1995..07/02/1995' tells the UPS software to purge the entries which are recorded form 03/20/1995 to 07/20/1995 from the event log file. | ||||
| SsyupsScopeSettings | 1.3.6.1.4.1.9557.1.4.9 | DisplayString | RW | mandatory |
scalar · DisplayString · read-write · mandatory The string contains the settings for UPS Scope Chart,
including Value Original Point, Value Unit, Time Unit,
Time Interval, and Display Items. The format for the
settings string is '%d, %d, %d, %d, %d'. Display Items can
be any one or any combination of the following items:
SCOPE_INPUT_VOLT 0x0001
SCOPE_OUTPUT_VOLT 0x0010
SCOPE_INPUT_FREQ 0x0100
SCOPE_OUTPUT_FREQ 0x1000 | ||||
| NsyupsSchedule | 1.3.6.1.4.1.9557.1.5 | |||
| SsyupsNoSchEntries | 1.3.6.1.4.1.9557.1.5.1 | INTEGER | RO | mandatory |
scalar · INTEGER · read-only · mandatory The total number of schedule entries. | ||||
| SsyupsSchOperator | 1.3.6.1.4.1.9557.1.5.2 | DisplayString | RW | mandatory |
scalar · DisplayString · read-write · mandatory The operator which is used to operate on the
schedule table. There are three commands:
1. 'ADD: action, mm/dd/yyyy, hh:mm:ss,
week_day, repeat' indicates to add a new entry
to the schedule list.
2. 'REPLACE: i, action, mm/dd/yyyy, hh:mm:ss,
week_day, repeat' indicates to replace the
i-th entry in the table with the new settings.
3. 'DELETE:n1, n2' indicates to delete the entries
ranging from number n1 to number n2 from the schedule
table.
'action' could be the following:
General System Test (1)
Quick Battery Test (2)
Deep Battery Test (3)
Turn On UPS (11)
Turn Off UPS (21)
Turn On Outlet (100+x)
Turn Off Outlet (200+x)
where x indicates the outlet number.
'mm/dd/year' and 'hh:mm:ss' specify the action's
starting time. 'repeat' indicates the frequency
of the action, it could be Once(1), Daily(2),
Weekly(3) and Monthly(4). 'week_day' indicating the
day of week is meaningful only when the repeat is
set to Weekly, and it could be Sun(0), Mon(1), ...,
and Sat(6).
For example, '1, 07/08/1994, 15:30:00, 0, 4'
indicates that the UPS will do a General System Test
at 3:30 PM every month from July 8, 1994.
'203, 06/20/1995, 07:00:00, 0, 1' indicates that the UPS
will turn off outlet #3 at 7 o'clock on June 20, 1995 and
do it only once. | ||||
| TsyupsSchTable | 1.3.6.1.4.1.9557.1.5.3 | NA | mandatory | |
table · not-accessible · mandatory A list of schedule entries. | ||||
| RsyupsSchEntry | 1.3.6.1.4.1.9557.1.5.3.1 | NA | mandatory | |
| CsyupsSchIndex | 1.3.6.1.4.1.9557.1.5.3.1.1 | INTEGER | RO | mandatory |
column · INTEGER · read-only · mandatory The entry number of a schedule setting. | ||||
| CsyupsSchStartDate | 1.3.6.1.4.1.9557.1.5.3.1.2 | DisplayString | RO | mandatory |
column · DisplayString · read-only · mandatory The starting date (mm/dd/yyyy) of the schedule entry. | ||||
| CsyupsSchStartTime | 1.3.6.1.4.1.9557.1.5.3.1.3 | DisplayString | RO | mandatory |
column · DisplayString · read-only · mandatory The starting time (hh:mm:ss) of the schedule entry. | ||||
| CsyupsSchWeekDay | 1.3.6.1.4.1.9557.1.5.3.1.4 | INTEGER | RO | mandatory |
column · INTEGER · read-only · mandatory The starting day of week for the schedule entry. It could be Sun(0), Mon(1), ..., and Sat(6). It is used when syupsSchRepeat is set to weekly.
| ||||
| CsyupsSchAction | 1.3.6.1.4.1.9557.1.5.3.1.5 | INTEGER | RO | mandatory |
column · INTEGER · read-only · mandatory The action of the schedule entry. It could be:
General System Test (1)
Quick Battery Test (2)
Deep Battery Test (3)
Turn On UPS (11)
Turn Off UPS (21)
Turn On Outlet (100+x)
Turn Off Outlet (200+x)
where x indicates the outlet number. | ||||
| CsyupsSchRepeat | 1.3.6.1.4.1.9557.1.5.3.1.6 | INTEGER | RO | mandatory |
column · INTEGER · read-only · mandatory It indicates the frequency of the action, it could be Once(1), Daily(2), Weekly(3) and Monthly(4).
| ||||
| NsyupsCoworker | 1.3.6.1.4.1.9557.1.6 | |||
| SsyupsNoAccessControl | 1.3.6.1.4.1.9557.1.6.1 | INTEGER | RO | mandatory |
scalar · INTEGER · read-only · mandatory The total number of access control entries. | ||||
| SsyupsAccessControlOperator | 1.3.6.1.4.1.9557.1.6.2 | DisplayString | RW | mandatory |
scalar · DisplayString · read-write · mandatory The operator which is used to operate on the
access control table. There are three commands:
1. 'ADD: community' indicates
to add a new entry to the access control list.
2. 'REPLACE: x, community'
indicates to replace the x-th entry in the table
with the new settings.
3. 'DELETE:n1, n2' indicates to delete the entries
from number n1 to number n2 from the access control
table. | ||||
| TsyupsAccessControlTable | 1.3.6.1.4.1.9557.1.6.3 | NA | mandatory | |
table · not-accessible · mandatory A list of access control entries. Only entries in this list can have access to the agent. | ||||
| RsyupsAccessControlEntry | 1.3.6.1.4.1.9557.1.6.3.1 | NA | mandatory | |
| CsyupsAccessControlIndex | 1.3.6.1.4.1.9557.1.6.3.1.1 | INTEGER | RO | mandatory |
column · INTEGER · read-only · mandatory The entry number of a access control setting. | ||||
| CsyupsAccessControlSetting | 1.3.6.1.4.1.9557.1.6.3.1.2 | DisplayString | RO | mandatory |
column · DisplayString · read-only · mandatory A string containing the community name. | ||||
| SsyupsNoTrapReceiver | 1.3.6.1.4.1.9557.1.6.4 | INTEGER | RO | mandatory |
scalar · INTEGER · read-only · mandatory The total number of trap receiver entries. | ||||
| SsyupsTrapReceiverOperator | 1.3.6.1.4.1.9557.1.6.5 | DisplayString | RW | mandatory |
scalar · DisplayString · read-write · mandatory The operator which is used to operate on the
trap receiver table. There are three commands:
1. 'ADD: ipAddress' indicates to add a new
entry to the trap receiver list.
2. 'REPLACE: x, ipAddress' indicates to replace
the x-th entry in the table with the new settings.
3. 'DELETE:n1, n2' indicates to delete the entries
from number n1 to number n2 from the trap receiver
table. | ||||
| TsyupsTrapReceiverTable | 1.3.6.1.4.1.9557.1.6.6 | NA | mandatory | |
table · not-accessible · mandatory A list of trap receiver entries. When an important event occurs, the agent will send traps to all the entries in the list. | ||||
| RsyupsTrapReceiverEntry | 1.3.6.1.4.1.9557.1.6.6.1 | NA | mandatory | |
| CsyupsTrapReceiverIndex | 1.3.6.1.4.1.9557.1.6.6.1.1 | INTEGER | RO | mandatory |
column · INTEGER · read-only · mandatory The entry number of a trap receiver setting. | ||||
| CsyupsTrapReceiverSetting | 1.3.6.1.4.1.9557.1.6.6.1.2 | DisplayString | RO | mandatory |
column · DisplayString · read-only · mandatory A string containing a trap receiver's IP address. | ||||
| NsyupsTraps | 1.3.6.1.4.1.9557.1.7 | |||
| !syupsTrapOverTemperature | 1.3.6.1.4.1.9557.1.7.1 | |||
notification · current The battery temperature is too high. This trap is persistent and is resent at one minute intervals until the UPS either turns off or the status is no longer present.
| ||||
| !syupsTrapOverCurrent | 1.3.6.1.4.1.9557.1.7.2 | |||
notification · current The current is too high. This trap is persistent and is resent at one minute intervals until the UPS either turns off or the status is no longer present.
| ||||
| !syupsTrapOverVoltage | 1.3.6.1.4.1.9557.1.7.3 | |||
notification · current The voltage is too high. This trap is persistent and is resent at one minute intervals until the UPS either turns off or the status is no longer present.
| ||||
| !syupsTrapUnderVoltage | 1.3.6.1.4.1.9557.1.7.4 | |||
notification · current The voltage is too low. This trap is persistent and is resent at one minute intervals until the UPS either turns off or the status is no longer present.
| ||||
| !syupsOffFrequency | 1.3.6.1.4.1.9557.1.7.5 | |||
notification · current The frequency is abnormal. This trap is persistent and is resent at one minute intervals until the UPS either turns off or the status is no longer present.
| ||||
| !syupsLowBattery | 1.3.6.1.4.1.9557.1.7.6 | |||
notification · current The battery is too low. This trap is persistent and is resent at one minute intervals until the UPS either turns off or the status is no longer present.
| ||||
| !syupsBadBattery | 1.3.6.1.4.1.9557.1.7.7 | |||
notification · current The battery is bad. This trap is persistent and is resent at one minute intervals until the UPS either turns off or the status is no longer present.
| ||||
Traps / Notifications
- syupsBadBattery
1.3.6.1.4.1.9557.1.7.7 - syupsLowBattery
1.3.6.1.4.1.9557.1.7.6 - syupsOffFrequency
1.3.6.1.4.1.9557.1.7.5 - syupsTrapOverCurrent
1.3.6.1.4.1.9557.1.7.2 - syupsTrapOverTemperature
1.3.6.1.4.1.9557.1.7.1 - syupsTrapOverVoltage
1.3.6.1.4.1.9557.1.7.3 - syupsTrapUnderVoltage
1.3.6.1.4.1.9557.1.7.4