SOCOMECPDU-MIB
Socomec Sicon Upssnmptranslate -m SOCOMECPDU-MIB -Tpsnmpwalk -v2c -c <community> -m SOCOMECPDU-MIB <host> 1.3.6.1.4.1.4555Imports
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
|---|---|
| SNMPv2-SMI | Bits, Integer32, IpAddress, MODULE-IDENTITY, MibIdentifier, OBJECT-IDENTITY, OBJECT-TYPE, TRAP-TYPE, TimeTicks, Unsigned32, enterprises, iso |
| SNMPv2-TC | DisplayString, PhysAddress, TEXTUAL-CONVENTION |
OID tree
| Name | OID | Type | Access | Status | Example | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Nsocomec | 1.3.6.1.4.1.4555 | ||||||||||||
| Nups | 1.3.6.1.4.1.4555.2 | ||||||||||||
| Npdu | 1.3.6.1.4.1.4555.2.30 | ||||||||||||
| NdpduIdent | 1.3.6.1.4.1.4555.2.30.1 | ||||||||||||
| SdpduIdentManufacturer | 1.3.6.1.4.1.4555.2.30.1.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The EnviroStation Vendor. | |||||||||||||
| SdpduIdentModel | 1.3.6.1.4.1.4555.2.30.1.2 | DisplayString (SIZE (0..32)) | RO | mandatory | NRT-OP-PDU1-28 | ||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The PDU Model designation. Example values from LibreNMS test devices
| |||||||||||||
| SdpduIdentSerialNumber | 1.3.6.1.4.1.4555.2.30.1.3 | DisplayString (SIZE (0..16)) | RO | mandatory | YD17190028 A | ||||||||
scalar · DisplayString (SIZE (0..16)) · read-only · mandatory The PDU serial number Example values from LibreNMS test devices
| |||||||||||||
| SdpduIdentPDUFirmwareVersion | 1.3.6.1.4.1.4555.2.30.1.4 | DisplayString (SIZE (0..16)) | RO | mandatory | 00 | ||||||||
scalar · DisplayString (SIZE (0..16)) · read-only · mandatory The PDU firmware version Example values from LibreNMS test devices
| |||||||||||||
| SdpduIdentAgentSoftwareVersion | 1.3.6.1.4.1.4555.2.30.1.5 | DisplayString (SIZE (0..16)) | RO | mandatory | 01.09.0f | ||||||||
scalar · DisplayString (SIZE (0..16)) · read-only · mandatory The PDU NMC software version Example values from LibreNMS test devices
| |||||||||||||
| SdpduIdentName | 1.3.6.1.4.1.4555.2.30.1.6 | DisplayString (SIZE (0..32)) | RW | mandatory | |||||||||
scalar · DisplayString (SIZE (0..32)) · read-write · mandatory A string identifying the PDU. This object should be set by the administrator. | |||||||||||||
| SdpduAttachedDevices | 1.3.6.1.4.1.4555.2.30.1.7 | DisplayString (SIZE (0..63)) | RW | mandatory | |||||||||
scalar · DisplayString (SIZE (0..63)) · read-write · mandatory A string identifying the devices attached to the output(s) of the PDU. This object should be set by the administrator. | |||||||||||||
| NdpduOutput | 1.3.6.1.4.1.4555.2.30.2 | ||||||||||||
| SdpduOutputFrequency | 1.3.6.1.4.1.4555.2.30.2.1 | INTEGER | RO | mandatory | 499 | ||||||||
scalar · INTEGER · read-only · mandatory The present output frequency in 1/10 Hz.
Example values from LibreNMS test devices
| |||||||||||||
| SdpduOutputVoltage1 | 1.3.6.1.4.1.4555.2.30.2.2 | INTEGER | RO | mandatory | 2273 | ||||||||
scalar · INTEGER · read-only · mandatory The Output line 1 voltage of the PDU system in 1/10 V.
Example values from LibreNMS test devices
| |||||||||||||
| SdpduOutputCurrent1 | 1.3.6.1.4.1.4555.2.30.2.3 | INTEGER | RO | mandatory | 0 | ||||||||
scalar · INTEGER · read-only · mandatory The Output line 1 current of the PDU system in 1/10 A.
Example values from LibreNMS test devices
| |||||||||||||
| SdpduOutputVoltage2 | 1.3.6.1.4.1.4555.2.30.2.4 | INTEGER | RO | mandatory | 2270 | ||||||||
scalar · INTEGER · read-only · mandatory The Output line 2 voltage of the PDU system in 1/10 V.
Example values from LibreNMS test devices
| |||||||||||||
| SdpduOutputCurrent2 | 1.3.6.1.4.1.4555.2.30.2.5 | INTEGER | RO | mandatory | 0 | ||||||||
scalar · INTEGER · read-only · mandatory The Output line 2 current of the PDU system in 1/10 A.
Example values from LibreNMS test devices
| |||||||||||||
| SdpduOutputVoltage3 | 1.3.6.1.4.1.4555.2.30.2.6 | INTEGER | RO | mandatory | 0 | ||||||||
scalar · INTEGER · read-only · mandatory The Output line 3 voltage of the PDU system in 1/10 V.
Example values from LibreNMS test devices
| |||||||||||||
| SdpduOutputCurrent3 | 1.3.6.1.4.1.4555.2.30.2.7 | INTEGER | RO | mandatory | 0 | ||||||||
scalar · INTEGER · read-only · mandatory The Output line 3 current of the PDU system in 1/10 A.
Example values from LibreNMS test devices
| |||||||||||||
| NdpduAlarm | 1.3.6.1.4.1.4555.2.30.3 | ||||||||||||
| SdpduAlarmDisconnect | 1.3.6.1.4.1.4555.2.30.3.1 | INTEGER | RO | mandatory | |||||||||
scalar · INTEGER · read-only · mandatory Does the PDU disconnect?
| |||||||||||||
| SdpduAlarmL1LoadMajor | 1.3.6.1.4.1.4555.2.30.3.2 | INTEGER | RO | mandatory | |||||||||
scalar · INTEGER · read-only · mandatory L1 load major alarm
| |||||||||||||
| SdpduAlarmL1LoadMinor | 1.3.6.1.4.1.4555.2.30.3.3 | INTEGER | RO | mandatory | |||||||||
scalar · INTEGER · read-only · mandatory L1 load minor alarm
| |||||||||||||
| SdpduAlarmL1OutVoltMajor | 1.3.6.1.4.1.4555.2.30.3.4 | INTEGER | RO | mandatory | |||||||||
scalar · INTEGER · read-only · mandatory L1 output votage major alarm
| |||||||||||||
| SdpduAlarmL1OutVoltMinor | 1.3.6.1.4.1.4555.2.30.3.5 | INTEGER | RO | mandatory | |||||||||
scalar · INTEGER · read-only · mandatory L1 output voltage minor alarm
| |||||||||||||
| SdpduAlarmL2LoadMajor | 1.3.6.1.4.1.4555.2.30.3.6 | INTEGER | RO | mandatory | |||||||||
scalar · INTEGER · read-only · mandatory L2 load major alarm
| |||||||||||||
| SdpduAlarmL2LoadMinor | 1.3.6.1.4.1.4555.2.30.3.7 | INTEGER | RO | mandatory | |||||||||
scalar · INTEGER · read-only · mandatory L2 load minor alarm
| |||||||||||||
| SdpduAlarmL2OutVoltMajor | 1.3.6.1.4.1.4555.2.30.3.8 | INTEGER | RO | mandatory | |||||||||
scalar · INTEGER · read-only · mandatory L2 output votage major alarm
| |||||||||||||
| SdpduAlarmL2OutVoltMinor | 1.3.6.1.4.1.4555.2.30.3.9 | INTEGER | RO | mandatory | |||||||||
scalar · INTEGER · read-only · mandatory L2 output voltage minor alarm
| |||||||||||||
| SdpduAlarmL3LoadMajor | 1.3.6.1.4.1.4555.2.30.3.10 | INTEGER | RO | mandatory | |||||||||
scalar · INTEGER · read-only · mandatory L3 load major alarm
| |||||||||||||
| SdpduAlarmL3LoadMinor | 1.3.6.1.4.1.4555.2.30.3.11 | INTEGER | RO | mandatory | |||||||||
scalar · INTEGER · read-only · mandatory L3 load minor alarm
| |||||||||||||
| SdpduAlarmL3OutVoltMajor | 1.3.6.1.4.1.4555.2.30.3.12 | INTEGER | RO | mandatory | |||||||||
scalar · INTEGER · read-only · mandatory L3 output votage major alarm
| |||||||||||||
| SdpduAlarmL3OutVoltMinor | 1.3.6.1.4.1.4555.2.30.3.13 | INTEGER | RO | mandatory | |||||||||
scalar · INTEGER · read-only · mandatory L3 output voltage minor alarm
| |||||||||||||
| SdpduAlarmL12LoadMajor | 1.3.6.1.4.1.4555.2.30.3.14 | INTEGER | RO | mandatory | |||||||||
scalar · INTEGER · read-only · mandatory L1, L2 load major alarm
| |||||||||||||
| SdpduAlarmL12LoadMinor | 1.3.6.1.4.1.4555.2.30.3.15 | INTEGER | RO | mandatory | |||||||||
scalar · INTEGER · read-only · mandatory L1, L2 load minor alarm
| |||||||||||||
| NdpduEnvironment | 1.3.6.1.4.1.4555.2.30.4 | ||||||||||||
| SdpduEnvTemperature | 1.3.6.1.4.1.4555.2.30.4.1 | INTEGER | RO | mandatory | |||||||||
scalar · INTEGER · read-only · mandatory The ambient environmental temperature.
| |||||||||||||
| SdpduEnvHumidity | 1.3.6.1.4.1.4555.2.30.4.2 | INTEGER | RO | mandatory | |||||||||
scalar · INTEGER · read-only · mandatory The environmental humidity.
| |||||||||||||
| SdpduEnvSetTemperatureWarnLimit | 1.3.6.1.4.1.4555.2.30.4.3 | INTEGER | RW | mandatory | |||||||||
scalar · INTEGER · read-write · mandatory Alarm dpduEnvOverWarnTemperature on when the environmental temperature over the value.
| |||||||||||||
| SdpduEnvSetTemperatureAlarmLimit | 1.3.6.1.4.1.4555.2.30.4.4 | INTEGER | RW | mandatory | |||||||||
scalar · INTEGER · read-write · mandatory Alarm dpduEnvOverAlarmTemperature on when the environmental temperature over the value.
| |||||||||||||
| SdpduEnvSetHumidityWarnLimit | 1.3.6.1.4.1.4555.2.30.4.5 | INTEGER | RW | mandatory | |||||||||
scalar · INTEGER · read-write · mandatory Alarm dpduEnvOverWarnHumidity on when the environmental humidity over the value.
| |||||||||||||
| SdpduEnvSetHumidityAlarmLimit | 1.3.6.1.4.1.4555.2.30.4.6 | INTEGER | RW | mandatory | |||||||||
scalar · INTEGER · read-write · mandatory Alarm dpduEnvOverAlarmHumidity on when the environmental humidity over the value.
| |||||||||||||
| SdpduEnvSetEnvRelay1 | 1.3.6.1.4.1.4555.2.30.4.7 | INTEGER | RW | mandatory | |||||||||
scalar · INTEGER · read-write · mandatory
| |||||||||||||
| SdpduEnvSetEnvRelay2 | 1.3.6.1.4.1.4555.2.30.4.8 | INTEGER | RW | mandatory | |||||||||
scalar · INTEGER · read-write · mandatory
| |||||||||||||
| SdpduEnvSetEnvRelay3 | 1.3.6.1.4.1.4555.2.30.4.9 | INTEGER | RW | mandatory | |||||||||
scalar · INTEGER · read-write · mandatory
| |||||||||||||
| SdpduEnvSetEnvRelay4 | 1.3.6.1.4.1.4555.2.30.4.10 | INTEGER | RW | mandatory | |||||||||
scalar · INTEGER · read-write · mandatory
| |||||||||||||
| SdpduWarnOverEnvTemperature | 1.3.6.1.4.1.4555.2.30.4.11 | INTEGER | RO | mandatory | |||||||||
scalar · INTEGER · read-only · mandatory Does the environment over warning temperature?
| |||||||||||||
| SdpduAlarmOverEnvTemperature | 1.3.6.1.4.1.4555.2.30.4.12 | INTEGER | RO | mandatory | |||||||||
scalar · INTEGER · read-only · mandatory Does the environment over alarm temperature?
| |||||||||||||
| SdpduWarnmOverEnvHumidity | 1.3.6.1.4.1.4555.2.30.4.13 | INTEGER | RO | mandatory | |||||||||
scalar · INTEGER · read-only · mandatory Does the environment over warn humidity?
| |||||||||||||
| SdpduAlarmOverEnvHumidity | 1.3.6.1.4.1.4555.2.30.4.14 | INTEGER | RO | mandatory | |||||||||
scalar · INTEGER · read-only · mandatory Does the environment over alarm humidity?
| |||||||||||||
| SdpduAlarmEnvRelay1 | 1.3.6.1.4.1.4555.2.30.4.15 | INTEGER | RO | mandatory | |||||||||
scalar · INTEGER · read-only · mandatory The alarm status of relay1.
| |||||||||||||
| SdpduAlarmEnvRelay2 | 1.3.6.1.4.1.4555.2.30.4.16 | INTEGER | RO | mandatory | |||||||||
scalar · INTEGER · read-only · mandatory The alarm status of relay2.
| |||||||||||||
| SdpduAlarmEnvRelay3 | 1.3.6.1.4.1.4555.2.30.4.17 | INTEGER | RO | mandatory | |||||||||
scalar · INTEGER · read-only · mandatory The alarm status of relay3.
| |||||||||||||
| SdpduAlarmEnvRelay4 | 1.3.6.1.4.1.4555.2.30.4.18 | INTEGER | RO | mandatory | |||||||||
scalar · INTEGER · read-only · mandatory The alarm status of relay4.
| |||||||||||||
| SdpduAlarmEnvDisconnect | 1.3.6.1.4.1.4555.2.30.4.19 | INTEGER | RO | mandatory | |||||||||
scalar · INTEGER · read-only · mandatory To indicate the communication status of EnviroProbe.
| |||||||||||||
| NdpduTraps | 1.3.6.1.4.1.4555.2.30.20 | ||||||||||||
| !dpduCommunicationLost | 1.3.6.1.4.1.4555.2.30.20.0.1 | ||||||||||||
notification Communication with the PDU failed. | |||||||||||||
| !dpduCommunicationEstablished | 1.3.6.1.4.1.4555.2.30.20.0.2 | ||||||||||||
notification Communication with the PDU reestablished. | |||||||||||||
| !dpduL1LoadMajorAlarm | 1.3.6.1.4.1.4555.2.30.20.0.3 | ||||||||||||
notification L1 load major alarm. | |||||||||||||
| !dpduL1LoadMajorAlarmRecover | 1.3.6.1.4.1.4555.2.30.20.0.4 | ||||||||||||
notification Recover from L1 load major alarm. | |||||||||||||
| !dpduL1LoadMinorAlarm | 1.3.6.1.4.1.4555.2.30.20.0.5 | ||||||||||||
notification L1 load minor alarm. | |||||||||||||
| !dpduL1LoadMinorAlarmRecover | 1.3.6.1.4.1.4555.2.30.20.0.6 | ||||||||||||
notification Recover from L1 load minor alarm. | |||||||||||||
| !dpduL1OutVoltMajorAlarm | 1.3.6.1.4.1.4555.2.30.20.0.7 | ||||||||||||
notification L1 output voltage major alarm. | |||||||||||||
| !dpduL1OutVoltMajorAlarmRecover | 1.3.6.1.4.1.4555.2.30.20.0.8 | ||||||||||||
notification Recover from L1 output voltage major alarm. | |||||||||||||
| !dpduL1OutVoltMinorAlarm | 1.3.6.1.4.1.4555.2.30.20.0.9 | ||||||||||||
notification L1 output voltage minor alarm. | |||||||||||||
| !dpduL1OutVoltMinorAlarmRecover | 1.3.6.1.4.1.4555.2.30.20.0.10 | ||||||||||||
notification Recover from L1 output voltage minor alarm. | |||||||||||||
| !dpduL2LoadMajorAlarm | 1.3.6.1.4.1.4555.2.30.20.0.11 | ||||||||||||
notification L2 load major alarm. | |||||||||||||
| !dpduL2LoadMajorAlarmRecover | 1.3.6.1.4.1.4555.2.30.20.0.12 | ||||||||||||
notification Recover from L2 load major alarm. | |||||||||||||
| !dpduL2LoadMinorAlarm | 1.3.6.1.4.1.4555.2.30.20.0.13 | ||||||||||||
notification L2 load minor alarm. | |||||||||||||
| !dpduL2LoadMinorAlarmRecover | 1.3.6.1.4.1.4555.2.30.20.0.14 | ||||||||||||
notification Recover from L2 load minor alarm. | |||||||||||||
| !dpduL2OutVoltMajorAlarm | 1.3.6.1.4.1.4555.2.30.20.0.15 | ||||||||||||
notification L2 output voltage major alarm. | |||||||||||||
| !dpduL2OutVoltMajorAlarmRecover | 1.3.6.1.4.1.4555.2.30.20.0.16 | ||||||||||||
notification Recover from L2 output voltage major alarm. | |||||||||||||
| !dpduL2OutVoltMinorAlarm | 1.3.6.1.4.1.4555.2.30.20.0.17 | ||||||||||||
notification L2 output voltage minor alarm. | |||||||||||||
| !dpduL2OutVoltMinorAlarmRecover | 1.3.6.1.4.1.4555.2.30.20.0.18 | ||||||||||||
notification Recover from L2 output voltage minor alarm. | |||||||||||||
| !dpduL3LoadMajorAlarm | 1.3.6.1.4.1.4555.2.30.20.0.19 | ||||||||||||
notification L3 load major alarm. | |||||||||||||
| !dpduL3LoadMajorAlarmRecover | 1.3.6.1.4.1.4555.2.30.20.0.20 | ||||||||||||
notification Recover from L3 load major alarm. | |||||||||||||
| !dpduL3LoadMinorAlarm | 1.3.6.1.4.1.4555.2.30.20.0.21 | ||||||||||||
notification L3 load minor alarm. | |||||||||||||
| !dpduL3LoadMinorAlarmRecover | 1.3.6.1.4.1.4555.2.30.20.0.22 | ||||||||||||
notification Recover from L3 load minor alarm. | |||||||||||||
| !dpduL3OutVoltMajorAlarm | 1.3.6.1.4.1.4555.2.30.20.0.23 | ||||||||||||
notification L3 output voltage major alarm. | |||||||||||||
| !dpduL3OutVoltMajorAlarmRecover | 1.3.6.1.4.1.4555.2.30.20.0.24 | ||||||||||||
notification Recover from L3 output voltage major alarm. | |||||||||||||
| !dpduL3OutVoltMinorAlarm | 1.3.6.1.4.1.4555.2.30.20.0.25 | ||||||||||||
notification L3 output voltage minor alarm. | |||||||||||||
| !dpduL3OutVoltMinorAlarmRecover | 1.3.6.1.4.1.4555.2.30.20.0.26 | ||||||||||||
notification Recover from L3 output voltage minor alarm. | |||||||||||||
| !dpduL12LoadMajorAlarm | 1.3.6.1.4.1.4555.2.30.20.0.27 | ||||||||||||
notification L1 L2 load major alarm. | |||||||||||||
| !dpduL12LoadMajorAlarmRecover | 1.3.6.1.4.1.4555.2.30.20.0.28 | ||||||||||||
notification Recover from L1 L2 load major alarm. | |||||||||||||
| !dpduL12LoadMinorAlarm | 1.3.6.1.4.1.4555.2.30.20.0.29 | ||||||||||||
notification L1 L2 load minor alarm. | |||||||||||||
| !dpduL12LoadMinorAlarmRecover | 1.3.6.1.4.1.4555.2.30.20.0.30 | ||||||||||||
notification Recover from L1 L2 load minor alarm. | |||||||||||||
| !dpduEnvCommunicationLost | 1.3.6.1.4.1.4555.2.30.20.0.31 | ||||||||||||
notification Communication with the environmental sensor failed. | |||||||||||||
| !dpduEnvCommunicationEstablished | 1.3.6.1.4.1.4555.2.30.20.0.32 | ||||||||||||
notification Communication with the environmental sensor reestablished. | |||||||||||||
| !dpduEnvOverWarnTemperature | 1.3.6.1.4.1.4555.2.30.20.0.33 | ||||||||||||
notification The environment over warning temperature. | |||||||||||||
| !dpduNoLongerEnvOverWarnTemperature | 1.3.6.1.4.1.4555.2.30.20.0.34 | ||||||||||||
notification The environment recovered from over warning temperature. | |||||||||||||
| !dpduEnvOverWarnHumidity | 1.3.6.1.4.1.4555.2.30.20.0.35 | ||||||||||||
notification The environment over warning humidity. | |||||||||||||
| !dpduNoLongerEnvOverWarnHumidity | 1.3.6.1.4.1.4555.2.30.20.0.36 | ||||||||||||
notification The environment recovered from over warning humidity. | |||||||||||||
| !dpduEnvOverAlarmTemperature | 1.3.6.1.4.1.4555.2.30.20.0.37 | ||||||||||||
notification The environment over alarm temperature. | |||||||||||||
| !dpduNoLongerEnvOverAlarmTemperature | 1.3.6.1.4.1.4555.2.30.20.0.38 | ||||||||||||
notification The environment recovered from over alarm temperature. | |||||||||||||
| !dpduEnvOverAlarmHumidity | 1.3.6.1.4.1.4555.2.30.20.0.39 | ||||||||||||
notification The environment over alarm humidity. | |||||||||||||
| !dpduNoLongerEnvOverAlarmHumidity | 1.3.6.1.4.1.4555.2.30.20.0.40 | ||||||||||||
notification The environment recovered from over alarm humidity. | |||||||||||||
| !dpduEnvRelay1Alarm | 1.3.6.1.4.1.4555.2.30.20.0.41 | ||||||||||||
notification The environment relay1 is not in normal state. | |||||||||||||
| !dpduEnvRelay1Normal | 1.3.6.1.4.1.4555.2.30.20.0.42 | ||||||||||||
notification The environment relay1 is in normal state. | |||||||||||||
| !dpduEnvRelay2Alarm | 1.3.6.1.4.1.4555.2.30.20.0.43 | ||||||||||||
notification The environment relay2 is not in normal state. | |||||||||||||
| !dpduEnvRelay2Normal | 1.3.6.1.4.1.4555.2.30.20.0.44 | ||||||||||||
notification The environment relay2 is in normal state. | |||||||||||||
| !dpduEnvRelay3Alarm | 1.3.6.1.4.1.4555.2.30.20.0.45 | ||||||||||||
notification The environment relay3 is not in normal state. | |||||||||||||
| !dpduEnvRelay3Normal | 1.3.6.1.4.1.4555.2.30.20.0.46 | ||||||||||||
notification The environment relay3 is in normal state. | |||||||||||||
| !dpduEnvRelay4Alarm | 1.3.6.1.4.1.4555.2.30.20.0.47 | ||||||||||||
notification The environment relay4 is not in normal state. | |||||||||||||
| !dpduEnvRelay4Normal | 1.3.6.1.4.1.4555.2.30.20.0.48 | ||||||||||||
notification The environment relay4 is in normal state. | |||||||||||||
Traps / Notifications
- dpduCommunicationEstablished
1.3.6.1.4.1.4555.2.30.20.0.2 - dpduCommunicationLost
1.3.6.1.4.1.4555.2.30.20.0.1 - dpduEnvCommunicationEstablished
1.3.6.1.4.1.4555.2.30.20.0.32 - dpduEnvCommunicationLost
1.3.6.1.4.1.4555.2.30.20.0.31 - dpduEnvOverAlarmHumidity
1.3.6.1.4.1.4555.2.30.20.0.39 - dpduEnvOverAlarmTemperature
1.3.6.1.4.1.4555.2.30.20.0.37 - dpduEnvOverWarnHumidity
1.3.6.1.4.1.4555.2.30.20.0.35 - dpduEnvOverWarnTemperature
1.3.6.1.4.1.4555.2.30.20.0.33 - dpduEnvRelay1Alarm
1.3.6.1.4.1.4555.2.30.20.0.41 - dpduEnvRelay1Normal
1.3.6.1.4.1.4555.2.30.20.0.42 - dpduEnvRelay2Alarm
1.3.6.1.4.1.4555.2.30.20.0.43 - dpduEnvRelay2Normal
1.3.6.1.4.1.4555.2.30.20.0.44 - dpduEnvRelay3Alarm
1.3.6.1.4.1.4555.2.30.20.0.45 - dpduEnvRelay3Normal
1.3.6.1.4.1.4555.2.30.20.0.46 - dpduEnvRelay4Alarm
1.3.6.1.4.1.4555.2.30.20.0.47 - dpduEnvRelay4Normal
1.3.6.1.4.1.4555.2.30.20.0.48 - dpduL12LoadMajorAlarm
1.3.6.1.4.1.4555.2.30.20.0.27 - dpduL12LoadMajorAlarmRecover
1.3.6.1.4.1.4555.2.30.20.0.28 - dpduL12LoadMinorAlarm
1.3.6.1.4.1.4555.2.30.20.0.29 - dpduL12LoadMinorAlarmRecover
1.3.6.1.4.1.4555.2.30.20.0.30 - dpduL1LoadMajorAlarm
1.3.6.1.4.1.4555.2.30.20.0.3 - dpduL1LoadMajorAlarmRecover
1.3.6.1.4.1.4555.2.30.20.0.4 - dpduL1LoadMinorAlarm
1.3.6.1.4.1.4555.2.30.20.0.5 - dpduL1LoadMinorAlarmRecover
1.3.6.1.4.1.4555.2.30.20.0.6 - dpduL1OutVoltMajorAlarm
1.3.6.1.4.1.4555.2.30.20.0.7 - dpduL1OutVoltMajorAlarmRecover
1.3.6.1.4.1.4555.2.30.20.0.8 - dpduL1OutVoltMinorAlarm
1.3.6.1.4.1.4555.2.30.20.0.9 - dpduL1OutVoltMinorAlarmRecover
1.3.6.1.4.1.4555.2.30.20.0.10 - dpduL2LoadMajorAlarm
1.3.6.1.4.1.4555.2.30.20.0.11 - dpduL2LoadMajorAlarmRecover
1.3.6.1.4.1.4555.2.30.20.0.12 - dpduL2LoadMinorAlarm
1.3.6.1.4.1.4555.2.30.20.0.13 - dpduL2LoadMinorAlarmRecover
1.3.6.1.4.1.4555.2.30.20.0.14 - dpduL2OutVoltMajorAlarm
1.3.6.1.4.1.4555.2.30.20.0.15 - dpduL2OutVoltMajorAlarmRecover
1.3.6.1.4.1.4555.2.30.20.0.16 - dpduL2OutVoltMinorAlarm
1.3.6.1.4.1.4555.2.30.20.0.17 - dpduL2OutVoltMinorAlarmRecover
1.3.6.1.4.1.4555.2.30.20.0.18 - dpduL3LoadMajorAlarm
1.3.6.1.4.1.4555.2.30.20.0.19 - dpduL3LoadMajorAlarmRecover
1.3.6.1.4.1.4555.2.30.20.0.20 - dpduL3LoadMinorAlarm
1.3.6.1.4.1.4555.2.30.20.0.21 - dpduL3LoadMinorAlarmRecover
1.3.6.1.4.1.4555.2.30.20.0.22 - dpduL3OutVoltMajorAlarm
1.3.6.1.4.1.4555.2.30.20.0.23 - dpduL3OutVoltMajorAlarmRecover
1.3.6.1.4.1.4555.2.30.20.0.24 - dpduL3OutVoltMinorAlarm
1.3.6.1.4.1.4555.2.30.20.0.25 - dpduL3OutVoltMinorAlarmRecover
1.3.6.1.4.1.4555.2.30.20.0.26 - dpduNoLongerEnvOverAlarmHumidity
1.3.6.1.4.1.4555.2.30.20.0.40 - dpduNoLongerEnvOverAlarmTemperature
1.3.6.1.4.1.4555.2.30.20.0.38 - dpduNoLongerEnvOverWarnHumidity
1.3.6.1.4.1.4555.2.30.20.0.36 - dpduNoLongerEnvOverWarnTemperature
1.3.6.1.4.1.4555.2.30.20.0.34