Sentry4-MIB
Server Technology Inc.This is the MIB module for the fourth generation of the Sentry product family. This includes the PRO1 and PRO2 series of Smart and Switched Power Distribution Unit (PDU), Cabinet Distribution Unit (CDU), Universal Power Distribution Unit (UPDU), and Inline Meter products.
snmptranslate -m Sentry4-MIB -Tpsnmpwalk -v2c -c <community> -m Sentry4-MIB <host> 1.3.6.1.4.1.1718.4Imports
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP, OBJECT-GROUP |
|---|---|
| SNMPv2-SMI | Bits, Integer32, IpAddress, MODULE-IDENTITY, MibIdentifier, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, TimeTicks, Unsigned32, enterprises, iso |
| SNMPv2-TC | DisplayString, PhysAddress, TEXTUAL-CONVENTION |
OID tree
| Name | OID | Type | Access | Status | Example | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| NserverTech | 1.3.6.1.4.1.1718 | ||||||||||||||||||||
| Isentry4 | 1.3.6.1.4.1.1718.4 | ||||||||||||||||||||
identity This is the MIB module for the fourth generation of the Sentry product family. This includes the PRO1 and PRO2 series of Smart and Switched Power Distribution Unit (PDU), Cabinet Distribution Unit (CDU), Universal Power Distribution Unit (UPDU), and Inline Meter products. | |||||||||||||||||||||
| Nst4Objects | 1.3.6.1.4.1.1718.4.1 | ||||||||||||||||||||
| Nst4System | 1.3.6.1.4.1.1718.4.1.1 | ||||||||||||||||||||
| Nst4SystemConfig | 1.3.6.1.4.1.1718.4.1.1.1 | ||||||||||||||||||||
| Sst4SystemProductName | 1.3.6.1.4.1.1718.4.1.1.1.1 | DisplayString (SIZE (0..63)) | RO | Sentry Switched PDU | |||||||||||||||||
scalar · DisplayString (SIZE (0..63)) · read-only · current The product name. Example values from LibreNMS test devices
| |||||||||||||||||||||
| Sst4SystemLocation | 1.3.6.1.4.1.1718.4.1.1.1.2 | DisplayString (SIZE (0..80)) | RW | ||||||||||||||||||
scalar · DisplayString (SIZE (0..80)) · read-write · current The location of the system. | |||||||||||||||||||||
| Sst4SystemFirmwareVersion | 1.3.6.1.4.1.1718.4.1.1.1.3 | DisplayString (SIZE (0..63)) | RO | Version 8.0n | |||||||||||||||||
scalar · DisplayString (SIZE (0..63)) · read-only · current The firmware version. Example values from LibreNMS test devices
| |||||||||||||||||||||
| Sst4SystemFirmwareBuildInfo | 1.3.6.1.4.1.1718.4.1.1.1.4 | DisplayString (SIZE (0..63)) | RO | ||||||||||||||||||
scalar · DisplayString (SIZE (0..63)) · read-only · current The firmware build information. | |||||||||||||||||||||
| Sst4SystemNICSerialNumber | 1.3.6.1.4.1.1718.4.1.1.1.5 | DisplayString (SIZE (0..8)) | RO | ||||||||||||||||||
scalar · DisplayString (SIZE (0..8)) · read-only · current The serial number of the network interface card. | |||||||||||||||||||||
| Sst4SystemNICHardwareInfo | 1.3.6.1.4.1.1718.4.1.1.1.6 | DisplayString (SIZE (0..63)) | RO | ||||||||||||||||||
scalar · DisplayString (SIZE (0..63)) · read-only · current Hardware information about the network interface card. | |||||||||||||||||||||
| Sst4SystemProductSeries | 1.3.6.1.4.1.1718.4.1.1.1.7 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The product series.
| |||||||||||||||||||||
| Sst4SystemUptime | 1.3.6.1.4.1.1718.4.1.1.1.8 | DisplayString (SIZE (0..48)) | RO | ||||||||||||||||||
scalar · DisplayString (SIZE (0..48)) · read-only · current The time in days, hours, minutes, and seconds since the network management portion of the system was last re-initialized. | |||||||||||||||||||||
| Sst4SystemFeatures | 1.3.6.1.4.1.1718.4.1.1.1.10 | Bits | RO | ||||||||||||||||||
scalar · Bits · read-only · current The key-activated features enabled in the system.
| |||||||||||||||||||||
| Sst4SystemFeatureKey | 1.3.6.1.4.1.1718.4.1.1.1.11 | DisplayString (SIZE (0..19)) | RW | ||||||||||||||||||
scalar · DisplayString (SIZE (0..19)) · read-write · current A valid feature key written to this object will enable a feature in the system. A valid feature key is in the form xxxx-xxxx-xxxx-xxxx. A read of this object returns an empty string. | |||||||||||||||||||||
| Sst4SystemConfigModifiedCount | 1.3.6.1.4.1.1718.4.1.1.1.20 | Integer32 (0..2147483647) | RO | ||||||||||||||||||
scalar · Integer32 (0..2147483647) · read-only · current The total number of times the system configuration has changed. | |||||||||||||||||||||
| Sst4SystemUnitCount | 1.3.6.1.4.1.1718.4.1.1.1.21 | Integer32 (0..8) | RO | ||||||||||||||||||
scalar · Integer32 (0..8) · read-only · current The number of units in the system. | |||||||||||||||||||||
| Nst4Units | 1.3.6.1.4.1.1718.4.1.2 | ||||||||||||||||||||
| Nst4UnitCommonConfig | 1.3.6.1.4.1.1718.4.1.2.1 | ||||||||||||||||||||
| Tst4UnitConfigTable | 1.3.6.1.4.1.1718.4.1.2.2 | NA | |||||||||||||||||||
table · not-accessible · current Unit configuration table. | |||||||||||||||||||||
| Rst4UnitConfigEntry | 1.3.6.1.4.1.1718.4.1.2.2.1 | NA | |||||||||||||||||||
| Cst4UnitIndex | 1.3.6.1.4.1.1718.4.1.2.2.1.1 | Integer32 (1..6) | NA | ||||||||||||||||||
column · Integer32 (1..6) · not-accessible · current Unit index. A=1, B=2, C=3, D=4, E=5, F=6. | |||||||||||||||||||||
| Cst4UnitID | 1.3.6.1.4.1.1718.4.1.2.2.1.2 | DisplayString (SIZE (1)) | RO | ||||||||||||||||||
column · DisplayString (SIZE (1)) · read-only · current The internal ID of the unit. Format=A. | |||||||||||||||||||||
| Cst4UnitName | 1.3.6.1.4.1.1718.4.1.2.2.1.3 | DisplayString (SIZE (0..32)) | RW | ||||||||||||||||||
column · DisplayString (SIZE (0..32)) · read-write · current The name of the unit. | |||||||||||||||||||||
| Cst4UnitProductSN | 1.3.6.1.4.1.1718.4.1.2.2.1.4 | DisplayString (SIZE (0..32)) | RO | <private> | |||||||||||||||||
column · DisplayString (SIZE (0..32)) · read-only · current The product serial number of the unit. Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4UnitModel | 1.3.6.1.4.1.1718.4.1.2.2.1.5 | DisplayString (SIZE (0..32)) | RO | C2S42CE-YCMFAM00 | |||||||||||||||||
column · DisplayString (SIZE (0..32)) · read-only · current The model of the unit. Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4UnitAssetTag | 1.3.6.1.4.1.1718.4.1.2.2.1.6 | DisplayString (SIZE (0..32)) | RW | ||||||||||||||||||
column · DisplayString (SIZE (0..32)) · read-write · current The asset tag of the unit. | |||||||||||||||||||||
| Cst4UnitType | 1.3.6.1.4.1.1718.4.1.2.2.1.7 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current The type of the unit.
| |||||||||||||||||||||
| Cst4UnitCapabilities | 1.3.6.1.4.1.1718.4.1.2.2.1.8 | Bits | RO | ||||||||||||||||||
column · Bits · read-only · current The capabilities of the unit.
| |||||||||||||||||||||
| Cst4UnitProductMfrDate | 1.3.6.1.4.1.1718.4.1.2.2.1.9 | DisplayString (SIZE (0..10)) | RO | ||||||||||||||||||
column · DisplayString (SIZE (0..10)) · read-only · current The product manufacture date in YYYY-MM-DD (ISO 8601 format) of the unit. | |||||||||||||||||||||
| Cst4UnitDisplayOrientation | 1.3.6.1.4.1.1718.4.1.2.2.1.20 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current The orientation of all displays in the unit.
| |||||||||||||||||||||
| Cst4UnitOutletSequenceOrder | 1.3.6.1.4.1.1718.4.1.2.2.1.21 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current The sequencing order of all outlets in the unit.
| |||||||||||||||||||||
| Cst4UnitOutletDisplayOrder | 1.3.6.1.4.1.1718.4.1.2.2.1.22 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current The display order in the user interfaces of all outlets in the unit.
| |||||||||||||||||||||
| Cst4UnitInputCordCount | 1.3.6.1.4.1.1718.4.1.2.2.1.30 | Integer32 (0..4) | RO | ||||||||||||||||||
column · Integer32 (0..4) · read-only · current The number of power input cords into the unit. | |||||||||||||||||||||
| Cst4UnitTempSensorCount | 1.3.6.1.4.1.1718.4.1.2.2.1.31 | Integer32 (0..2) | RO | ||||||||||||||||||
column · Integer32 (0..2) · read-only · current The number of external temperature sensors supported by the unit. | |||||||||||||||||||||
| Cst4UnitHumidSensorCount | 1.3.6.1.4.1.1718.4.1.2.2.1.32 | Integer32 (0..2) | RO | ||||||||||||||||||
column · Integer32 (0..2) · read-only · current The number of external humidity sensors supported by the unit. | |||||||||||||||||||||
| Cst4UnitWaterSensorCount | 1.3.6.1.4.1.1718.4.1.2.2.1.33 | Integer32 (0..1) | RO | ||||||||||||||||||
column · Integer32 (0..1) · read-only · current The number of external water sensors supported by the unit. | |||||||||||||||||||||
| Cst4UnitCcSensorCount | 1.3.6.1.4.1.1718.4.1.2.2.1.34 | Integer32 (0..4) | RO | ||||||||||||||||||
column · Integer32 (0..4) · read-only · current The number of external contact closure sensors supported by the unit. | |||||||||||||||||||||
| Cst4UnitAdcSensorCount | 1.3.6.1.4.1.1718.4.1.2.2.1.35 | Integer32 (0..1) | RO | ||||||||||||||||||
column · Integer32 (0..1) · read-only · current The number of analog-to-digital converter sensors supported by the unit. | |||||||||||||||||||||
| Cst4UnitFanSensorCount | 1.3.6.1.4.1.1718.4.1.2.2.1.36 | Integer32 (0..4) | RO | ||||||||||||||||||
column · Integer32 (0..4) · read-only · current The number of fan sensors supported by the unit. | |||||||||||||||||||||
| Tst4UnitMonitorTable | 1.3.6.1.4.1.1718.4.1.2.3 | NA | |||||||||||||||||||
table · not-accessible · current Unit monitor table. | |||||||||||||||||||||
| Rst4UnitMonitorEntry | 1.3.6.1.4.1.1718.4.1.2.3.1 | NA | |||||||||||||||||||
| Cst4UnitStatus | 1.3.6.1.4.1.1718.4.1.2.3.1.1 | DeviceStatus | RO | 0 | |||||||||||||||||
column · DeviceStatus · read-only · current The status of the unit. Example values from LibreNMS test devices
| |||||||||||||||||||||
| Tst4UnitEventConfigTable | 1.3.6.1.4.1.1718.4.1.2.4 | NA | |||||||||||||||||||
table · not-accessible · current Unit event configuration table. | |||||||||||||||||||||
| Rst4UnitEventConfigEntry | 1.3.6.1.4.1.1718.4.1.2.4.1 | NA | |||||||||||||||||||
| Cst4UnitNotifications | 1.3.6.1.4.1.1718.4.1.2.4.1.1 | EventNotificationMethods | RW | ||||||||||||||||||
column · EventNotificationMethods · read-write · current The notification methods enabled for unit events. | |||||||||||||||||||||
| Nst4InputCords | 1.3.6.1.4.1.1718.4.1.3 | ||||||||||||||||||||
| Nst4InputCordCommonConfig | 1.3.6.1.4.1.1718.4.1.3.1 | ||||||||||||||||||||
| Sst4InputCordActivePowerHysteresis | 1.3.6.1.4.1.1718.4.1.3.1.1 | Integer32 (0..1000) | RW | ||||||||||||||||||
scalar · Integer32 (0..1000) · read-write · current The active power hysteresis of the input cord in Watts.
| |||||||||||||||||||||
| Sst4InputCordApparentPowerHysteresis | 1.3.6.1.4.1.1718.4.1.3.1.2 | Integer32 (0..1000) | RW | ||||||||||||||||||
scalar · Integer32 (0..1000) · read-write · current The apparent power hysteresis of the input cord in Volt-Amps.
| |||||||||||||||||||||
| Sst4InputCordPowerFactorHysteresis | 1.3.6.1.4.1.1718.4.1.3.1.3 | Integer32 (0..20) | RW | ||||||||||||||||||
scalar · Integer32 (0..20) · read-write · current The power factor hysteresis of the input cord in hundredths.
| |||||||||||||||||||||
| Sst4InputCordOutOfBalanceHysteresis | 1.3.6.1.4.1.1718.4.1.3.1.4 | Integer32 (0..10) | RW | ||||||||||||||||||
scalar · Integer32 (0..10) · read-write · current The 3 phase out-of-balance hysteresis of the input cord in percent.
| |||||||||||||||||||||
| Tst4InputCordConfigTable | 1.3.6.1.4.1.1718.4.1.3.2 | NA | |||||||||||||||||||
table · not-accessible · current Input cord configuration table. | |||||||||||||||||||||
| Rst4InputCordConfigEntry | 1.3.6.1.4.1.1718.4.1.3.2.1 | NA | |||||||||||||||||||
row · not-accessible · current Configuration objects for a particular input cord. | |||||||||||||||||||||
| Cst4InputCordIndex | 1.3.6.1.4.1.1718.4.1.3.2.1.1 | Integer32 (1..4) | NA | ||||||||||||||||||
column · Integer32 (1..4) · not-accessible · current Input cord index. A=1, B=2, C=3, D=4. | |||||||||||||||||||||
| Cst4InputCordID | 1.3.6.1.4.1.1718.4.1.3.2.1.2 | DisplayString (SIZE (2)) | RO | AA | |||||||||||||||||
| Cst4InputCordName | 1.3.6.1.4.1.1718.4.1.3.2.1.3 | DisplayString (SIZE (0..32)) | RW | Master_Cord_A | |||||||||||||||||
| Cst4InputCordInletType | 1.3.6.1.4.1.1718.4.1.3.2.1.6 | DisplayString (SIZE (0..32)) | RO | L15-30P | |||||||||||||||||
column · DisplayString (SIZE (0..32)) · read-only · current The type of plug on the input cord, or socket for the input cord. Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4InputCordNominalVoltage | 1.3.6.1.4.1.1718.4.1.3.2.1.7 | Integer32 (0..6000) | RW | 2080 | |||||||||||||||||
column · Integer32 (0..6000) · read-write · current The user-configured nominal voltage of the input cord in tenth Volts.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4InputCordNominalVoltageMin | 1.3.6.1.4.1.1718.4.1.3.2.1.8 | Integer32 (0..600) | RO | 200 | |||||||||||||||||
column · Integer32 (0..600) · read-only · current The factory-set minimum allowed for the user-configured nominal voltage of the input cord in Volts.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4InputCordNominalVoltageMax | 1.3.6.1.4.1.1718.4.1.3.2.1.9 | Integer32 (0..600) | RO | 240 | |||||||||||||||||
column · Integer32 (0..600) · read-only · current The factory-set maximum allowed for the user-configured nominal voltage of the input cord in Volts.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4InputCordCurrentCapacity | 1.3.6.1.4.1.1718.4.1.3.2.1.10 | Integer32 (0..600) | RW | 30 | |||||||||||||||||
column · Integer32 (0..600) · read-write · current The user-configured current capacity of the input cord in Amps.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4InputCordCurrentCapacityMax | 1.3.6.1.4.1.1718.4.1.3.2.1.11 | Integer32 (0..600) | RO | 30 | |||||||||||||||||
column · Integer32 (0..600) · read-only · current The factory-set maximum allowed for the user-configured current capacity of the input cord in Amps.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4InputCordPowerCapacity | 1.3.6.1.4.1.1718.4.1.3.2.1.12 | Integer32 (0..50000) | RO | 10807 | |||||||||||||||||
column · Integer32 (0..50000) · read-only · current The power capacity of the input cord in Volt-Amps. For DC products, this is identical to power capacity in Watts.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4InputCordNominalPowerFactor | 1.3.6.1.4.1.1718.4.1.3.2.1.13 | Integer32 (0..100) | RW | ||||||||||||||||||
column · Integer32 (0..100) · read-write · current The user-configured estimated nominal power factor of the input cord in hundredths.
| |||||||||||||||||||||
| Cst4InputCordLineCount | 1.3.6.1.4.1.1718.4.1.3.2.1.20 | Integer32 (0..4) | RO | 3 | |||||||||||||||||
column · Integer32 (0..4) · read-only · current The number of current-carrying lines in the input cord. Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4InputCordPhaseCount | 1.3.6.1.4.1.1718.4.1.3.2.1.21 | Integer32 (0..6) | RO | 3 | |||||||||||||||||
column · Integer32 (0..6) · read-only · current The number of active phases from the lines in the input cord. Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4InputCordOcpCount | 1.3.6.1.4.1.1718.4.1.3.2.1.22 | Integer32 (0..12) | RO | 3 | |||||||||||||||||
column · Integer32 (0..12) · read-only · current The number of over-current protectors downstream from the input cord. Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4InputCordBranchCount | 1.3.6.1.4.1.1718.4.1.3.2.1.23 | Integer32 (0..12) | RO | 3 | |||||||||||||||||
column · Integer32 (0..12) · read-only · current The number of branches downstream from the input cord. Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4InputCordOutletCount | 1.3.6.1.4.1.1718.4.1.3.2.1.24 | Integer32 (0..128) | RO | 36 | |||||||||||||||||
column · Integer32 (0..128) · read-only · current The number of outlets powered from the input cord. Example values from LibreNMS test devices
| |||||||||||||||||||||
| Tst4InputCordMonitorTable | 1.3.6.1.4.1.1718.4.1.3.3 | NA | |||||||||||||||||||
table · not-accessible · current Input cord monitor table. | |||||||||||||||||||||
| Rst4InputCordMonitorEntry | 1.3.6.1.4.1.1718.4.1.3.3.1 | NA | |||||||||||||||||||
row · not-accessible · current Objects to monitor for a particular input cord. | |||||||||||||||||||||
| Cst4InputCordState | 1.3.6.1.4.1.1718.4.1.3.3.1.1 | DeviceState | RO | 1 | |||||||||||||||||
column · DeviceState · read-only · current The on/off state of the input cord. Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4InputCordStatus | 1.3.6.1.4.1.1718.4.1.3.3.1.2 | DeviceStatus | RO | 0 | |||||||||||||||||
column · DeviceStatus · read-only · current The status of the input cord. Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4InputCordActivePower | 1.3.6.1.4.1.1718.4.1.3.3.1.3 | Integer32 (-1..50000) | RO | 1701 | |||||||||||||||||
column · Integer32 (-1..50000) · read-only · current The measured active power of the input cord in Watts.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4InputCordActivePowerStatus | 1.3.6.1.4.1.1718.4.1.3.3.1.4 | DeviceStatus | RO | 0 | |||||||||||||||||
column · DeviceStatus · read-only · current The status of the measured active power of the input cord. Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4InputCordApparentPower | 1.3.6.1.4.1.1718.4.1.3.3.1.5 | Integer32 (-1..50000) | RO | 1790 | |||||||||||||||||
column · Integer32 (-1..50000) · read-only · current The measured apparent power of the input cord in Volt-Amps.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4InputCordApparentPowerStatus | 1.3.6.1.4.1.1718.4.1.3.3.1.6 | DeviceStatus | RO | 0 | |||||||||||||||||
column · DeviceStatus · read-only · current The status of the measured apparent power of the input cord. Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4InputCordPowerUtilized | 1.3.6.1.4.1.1718.4.1.3.3.1.7 | Integer32 (-1..1200) | RO | 165 | |||||||||||||||||
column · Integer32 (-1..1200) · read-only · current The amount of the input cord power capacity used in tenth percent. For AC products, this is the ratio of the apparent power to the power capacity. For DC products, this is the ratio of the active power to the power capacity.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4InputCordPowerFactor | 1.3.6.1.4.1.1718.4.1.3.3.1.8 | Integer32 (-1..100) | RO | 95 | |||||||||||||||||
| Cst4InputCordPowerFactorStatus | 1.3.6.1.4.1.1718.4.1.3.3.1.9 | DeviceStatus | RO | 0 | |||||||||||||||||
column · DeviceStatus · read-only · current The status of the measured power factor of the input cord. Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4InputCordEnergy | 1.3.6.1.4.1.1718.4.1.3.3.1.10 | Integer32 (-1..2147483647) | RO | 8937 | |||||||||||||||||
column · Integer32 (-1..2147483647) · read-only · current The total energy consumption of loads through the input cord in tenth Kilowatt-Hours.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4InputCordFrequency | 1.3.6.1.4.1.1718.4.1.3.3.1.11 | Integer32 (-1..1000) | RO | 600 | |||||||||||||||||
column · Integer32 (-1..1000) · read-only · current The frequency of the input cord voltage in tenth Hertz.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4InputCordOutOfBalance | 1.3.6.1.4.1.1718.4.1.3.3.1.12 | Integer32 (-1..2000) | RO | 26 | |||||||||||||||||
| Cst4InputCordOutOfBalanceStatus | 1.3.6.1.4.1.1718.4.1.3.3.1.13 | DeviceStatus | RO | 0 | |||||||||||||||||
column · DeviceStatus · read-only · current The status of the current imbalance on the lines of the input cord. Example values from LibreNMS test devices
| |||||||||||||||||||||
| Tst4InputCordEventConfigTable | 1.3.6.1.4.1.1718.4.1.3.4 | NA | |||||||||||||||||||
table · not-accessible · current Input cord event configuration table. | |||||||||||||||||||||
| Rst4InputCordEventConfigEntry | 1.3.6.1.4.1.1718.4.1.3.4.1 | NA | |||||||||||||||||||
row · not-accessible · current Event configuration objects for a particular input cord. | |||||||||||||||||||||
| Cst4InputCordNotifications | 1.3.6.1.4.1.1718.4.1.3.4.1.1 | EventNotificationMethods | RW | C0 0 1 | |||||||||||||||||
column · EventNotificationMethods · read-write · current The notification methods enabled for input cord events. Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4InputCordActivePowerLowAlarm | 1.3.6.1.4.1.1718.4.1.3.4.1.2 | Integer32 (0..50000) | RW | 0 | |||||||||||||||||
column · Integer32 (0..50000) · read-write · current The active power low alarm threshold of the input cord in Watts.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4InputCordActivePowerLowWarning | 1.3.6.1.4.1.1718.4.1.3.4.1.3 | Integer32 (0..50000) | RW | 0 | |||||||||||||||||
column · Integer32 (0..50000) · read-write · current The active power low warning threshold of the input cord in Watts.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4InputCordActivePowerHighWarning | 1.3.6.1.4.1.1718.4.1.3.4.1.4 | Integer32 (0..50000) | RW | 7565 | |||||||||||||||||
column · Integer32 (0..50000) · read-write · current The active power high warning threshold of the input cord in Watts.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4InputCordActivePowerHighAlarm | 1.3.6.1.4.1.1718.4.1.3.4.1.5 | Integer32 (0..50000) | RW | 8646 | |||||||||||||||||
column · Integer32 (0..50000) · read-write · current The active power high alarm threshold of the input cord in Watts.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4InputCordApparentPowerLowAlarm | 1.3.6.1.4.1.1718.4.1.3.4.1.6 | Integer32 (0..50000) | RW | 0 | |||||||||||||||||
column · Integer32 (0..50000) · read-write · current The apparent power low alarm threshold of the input cord in Volt-Amps.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4InputCordApparentPowerLowWarning | 1.3.6.1.4.1.1718.4.1.3.4.1.7 | Integer32 (0..50000) | RW | 0 | |||||||||||||||||
column · Integer32 (0..50000) · read-write · current The apparent power low warning threshold of the input cord in Volt-Amps.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4InputCordApparentPowerHighWarning | 1.3.6.1.4.1.1718.4.1.3.4.1.8 | Integer32 (0..50000) | RW | 7565 | |||||||||||||||||
column · Integer32 (0..50000) · read-write · current The apparent power high warning threshold of the input cord in Volt-Amps.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4InputCordApparentPowerHighAlarm | 1.3.6.1.4.1.1718.4.1.3.4.1.9 | Integer32 (0..50000) | RW | 8646 | |||||||||||||||||
column · Integer32 (0..50000) · read-write · current The apparent power high alarm threshold of the input cord in Volt-Amps.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4InputCordPowerFactorLowAlarm | 1.3.6.1.4.1.1718.4.1.3.4.1.10 | Integer32 (0..100) | RW | 30 | |||||||||||||||||
column · Integer32 (0..100) · read-write · current The power factor low alarm threshold of the input cord in hundredths.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4InputCordPowerFactorLowWarning | 1.3.6.1.4.1.1718.4.1.3.4.1.11 | Integer32 (0..100) | RW | 40 | |||||||||||||||||
column · Integer32 (0..100) · read-write · current The power factor low warning threshold of the input cord in hundredths.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4InputCordOutOfBalanceHighWarning | 1.3.6.1.4.1.1718.4.1.3.4.1.12 | Integer32 (0..100) | RW | 15 | |||||||||||||||||
column · Integer32 (0..100) · read-write · current The 3 phase out-of-balance high warning threshold of the input cord in percent.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4InputCordOutOfBalanceHighAlarm | 1.3.6.1.4.1.1718.4.1.3.4.1.13 | Integer32 (0..100) | RW | 20 | |||||||||||||||||
column · Integer32 (0..100) · read-write · current The 3 phase out-of-balance high alarm threshold of the input cord in percent.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| Nst4Lines | 1.3.6.1.4.1.1718.4.1.4 | ||||||||||||||||||||
| Nst4LineCommonConfig | 1.3.6.1.4.1.1718.4.1.4.1 | ||||||||||||||||||||
| Sst4LineCurrentHysteresis | 1.3.6.1.4.1.1718.4.1.4.1.1 | Integer32 (0..100) | RW | ||||||||||||||||||
scalar · Integer32 (0..100) · read-write · current The current hysteresis of the line in tenth Amps.
| |||||||||||||||||||||
| Tst4LineConfigTable | 1.3.6.1.4.1.1718.4.1.4.2 | NA | |||||||||||||||||||
table · not-accessible · current Line configuration table. | |||||||||||||||||||||
| Rst4LineConfigEntry | 1.3.6.1.4.1.1718.4.1.4.2.1 | NA | |||||||||||||||||||
row · not-accessible · current Configuration objects for a particular line. | |||||||||||||||||||||
| Cst4LineIndex | 1.3.6.1.4.1.1718.4.1.4.2.1.1 | Integer32 (1..4) | NA | ||||||||||||||||||
column · Integer32 (1..4) · not-accessible · current Line index. L1=1, L2=2, L3=3, N=4. | |||||||||||||||||||||
| Cst4LineID | 1.3.6.1.4.1.1718.4.1.4.2.1.2 | DisplayString (SIZE (3)) | RO | ||||||||||||||||||
column · DisplayString (SIZE (3)) · read-only · current The internal ID of the line. Format=AAN. | |||||||||||||||||||||
| Cst4LineLabel | 1.3.6.1.4.1.1718.4.1.4.2.1.4 | DisplayString (SIZE (0..32)) | RO | AA:L1 | |||||||||||||||||
| Cst4LineCurrentCapacity | 1.3.6.1.4.1.1718.4.1.4.2.1.6 | Integer32 (0..600) | RO | ||||||||||||||||||
column · Integer32 (0..600) · read-only · current The current capacity of the line in Amps.
| |||||||||||||||||||||
| Tst4LineMonitorTable | 1.3.6.1.4.1.1718.4.1.4.3 | NA | |||||||||||||||||||
table · not-accessible · current Line monitor table. | |||||||||||||||||||||
| Rst4LineMonitorEntry | 1.3.6.1.4.1.1718.4.1.4.3.1 | NA | |||||||||||||||||||
row · not-accessible · current Objects to monitor for a particular line. | |||||||||||||||||||||
| Cst4LineState | 1.3.6.1.4.1.1718.4.1.4.3.1.1 | DeviceState | RO | 1 | |||||||||||||||||
column · DeviceState · read-only · current The on/off state of the line. Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4LineStatus | 1.3.6.1.4.1.1718.4.1.4.3.1.2 | DeviceStatus | RO | 0 | |||||||||||||||||
column · DeviceStatus · read-only · current The status of the line. Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4LineCurrent | 1.3.6.1.4.1.1718.4.1.4.3.1.3 | Integer32 (-1..60000) | RO | 560 | |||||||||||||||||
| Cst4LineCurrentStatus | 1.3.6.1.4.1.1718.4.1.4.3.1.4 | DeviceStatus | RO | ||||||||||||||||||
column · DeviceStatus · read-only · current The status of the measured current on the line. | |||||||||||||||||||||
| Cst4LineCurrentUtilized | 1.3.6.1.4.1.1718.4.1.4.3.1.5 | Integer32 (-1..1200) | RO | ||||||||||||||||||
column · Integer32 (-1..1200) · read-only · current The amount of the line current capacity used in tenth percent.
| |||||||||||||||||||||
| Tst4LineEventConfigTable | 1.3.6.1.4.1.1718.4.1.4.4 | NA | |||||||||||||||||||
table · not-accessible · current Line event configuration table. | |||||||||||||||||||||
| Rst4LineEventConfigEntry | 1.3.6.1.4.1.1718.4.1.4.4.1 | NA | |||||||||||||||||||
row · not-accessible · current Event configuration objects for a particular line. | |||||||||||||||||||||
| Cst4LineNotifications | 1.3.6.1.4.1.1718.4.1.4.4.1.1 | EventNotificationMethods | RW | ||||||||||||||||||
column · EventNotificationMethods · read-write · current The notification methods enabled for line events. | |||||||||||||||||||||
| Cst4LineCurrentLowAlarm | 1.3.6.1.4.1.1718.4.1.4.4.1.2 | Integer32 (0..6000) | RW | ||||||||||||||||||
column · Integer32 (0..6000) · read-write · current The current low alarm threshold of the line in tenth Amps.
| |||||||||||||||||||||
| Cst4LineCurrentLowWarning | 1.3.6.1.4.1.1718.4.1.4.4.1.3 | Integer32 (0..6000) | RW | ||||||||||||||||||
column · Integer32 (0..6000) · read-write · current The current low warning threshold of the line in tenth Amps.
| |||||||||||||||||||||
| Cst4LineCurrentHighWarning | 1.3.6.1.4.1.1718.4.1.4.4.1.4 | Integer32 (0..6000) | RW | ||||||||||||||||||
column · Integer32 (0..6000) · read-write · current The current high warning threshold of the line in tenth Amps.
| |||||||||||||||||||||
| Cst4LineCurrentHighAlarm | 1.3.6.1.4.1.1718.4.1.4.4.1.5 | Integer32 (0..6000) | RW | ||||||||||||||||||
column · Integer32 (0..6000) · read-write · current The current high alarm threshold of the line in tenth Amps.
| |||||||||||||||||||||
| Nst4Phases | 1.3.6.1.4.1.1718.4.1.5 | ||||||||||||||||||||
| Nst4PhaseCommonConfig | 1.3.6.1.4.1.1718.4.1.5.1 | ||||||||||||||||||||
| Sst4PhaseVoltageHysteresis | 1.3.6.1.4.1.1718.4.1.5.1.1 | Integer32 (0..200) | RW | ||||||||||||||||||
scalar · Integer32 (0..200) · read-write · current The voltage hysteresis of the phase in tenth Volts.
| |||||||||||||||||||||
| Sst4PhasePowerFactorHysteresis | 1.3.6.1.4.1.1718.4.1.5.1.2 | Integer32 (0..20) | RW | ||||||||||||||||||
scalar · Integer32 (0..20) · read-write · current The power factor hysteresis of the phase in hundredths.
| |||||||||||||||||||||
| Tst4PhaseConfigTable | 1.3.6.1.4.1.1718.4.1.5.2 | NA | |||||||||||||||||||
table · not-accessible · current Phase configuration table. | |||||||||||||||||||||
| Rst4PhaseConfigEntry | 1.3.6.1.4.1.1718.4.1.5.2.1 | NA | |||||||||||||||||||
row · not-accessible · current Configuration objects for a particular phase. | |||||||||||||||||||||
| Cst4PhaseIndex | 1.3.6.1.4.1.1718.4.1.5.2.1.1 | Integer32 (1..6) | NA | ||||||||||||||||||
column · Integer32 (1..6) · not-accessible · current Phase index. Three-phase AC Wye: L1-N=1, L2-N=2, L3-N=3; Three-phase AC Delta: L1-L2=1, L2-L3=2, L3-L1=3; Single Phase: L1-R=1; DC: L1-R=1; Three-phase AC Wye & Delta: L1-N=1, L2-N=2, L3-N=3, L1-L2=4, L2-L3=5; L3-L1=6. | |||||||||||||||||||||
| Cst4PhaseID | 1.3.6.1.4.1.1718.4.1.5.2.1.2 | DisplayString (SIZE (3)) | RO | ||||||||||||||||||
column · DisplayString (SIZE (3)) · read-only · current The internal ID of the phase. Format=AAN. | |||||||||||||||||||||
| Cst4PhaseLabel | 1.3.6.1.4.1.1718.4.1.5.2.1.4 | DisplayString (SIZE (0..32)) | RO | AA:L1-L2 | |||||||||||||||||
| Cst4PhaseNominalVoltage | 1.3.6.1.4.1.1718.4.1.5.2.1.6 | Integer32 (0..6000) | RO | ||||||||||||||||||
column · Integer32 (0..6000) · read-only · current The nominal voltage of the phase in tenth Volts.
| |||||||||||||||||||||
| Cst4PhaseBranchCount | 1.3.6.1.4.1.1718.4.1.5.2.1.20 | Integer32 (0..12) | RO | ||||||||||||||||||
column · Integer32 (0..12) · read-only · current The number of branches downstream from the phase. | |||||||||||||||||||||
| Cst4PhaseOutletCount | 1.3.6.1.4.1.1718.4.1.5.2.1.21 | Integer32 (0..128) | RO | ||||||||||||||||||
column · Integer32 (0..128) · read-only · current The number of outlets powered from the phase. | |||||||||||||||||||||
| Tst4PhaseMonitorTable | 1.3.6.1.4.1.1718.4.1.5.3 | NA | |||||||||||||||||||
table · not-accessible · current Phase monitor table. | |||||||||||||||||||||
| Rst4PhaseMonitorEntry | 1.3.6.1.4.1.1718.4.1.5.3.1 | NA | |||||||||||||||||||
row · not-accessible · current Objects to monitor for a particular phase. | |||||||||||||||||||||
| Cst4PhaseState | 1.3.6.1.4.1.1718.4.1.5.3.1.1 | DeviceState | RO | 1 | |||||||||||||||||
column · DeviceState · read-only · current The on/off state of the phase. Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4PhaseStatus | 1.3.6.1.4.1.1718.4.1.5.3.1.2 | DeviceStatus | RO | 0 | |||||||||||||||||
column · DeviceStatus · read-only · current The status of the phase. Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4PhaseVoltage | 1.3.6.1.4.1.1718.4.1.5.3.1.3 | Integer32 (-1..6000) | RO | 2079 | |||||||||||||||||
| Cst4PhaseVoltageStatus | 1.3.6.1.4.1.1718.4.1.5.3.1.4 | DeviceStatus | RO | 0 | |||||||||||||||||
column · DeviceStatus · read-only · current The status of the measured voltage on the phase. Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4PhaseVoltageDeviation | 1.3.6.1.4.1.1718.4.1.5.3.1.5 | Integer32 (-1000..1000) | RO | ||||||||||||||||||
column · Integer32 (-1000..1000) · read-only · current The deviation from the nominal voltage on the phase in tenth percent.
| |||||||||||||||||||||
| Cst4PhaseCurrent | 1.3.6.1.4.1.1718.4.1.5.3.1.6 | Integer32 (-1..30000) | RO | 209 | |||||||||||||||||
| Cst4PhaseCurrentCrestFactor | 1.3.6.1.4.1.1718.4.1.5.3.1.7 | Integer32 (-1..250) | RO | ||||||||||||||||||
column · Integer32 (-1..250) · read-only · current The measured crest factor of the current waveform on the phase in tenths.
| |||||||||||||||||||||
| Cst4PhaseActivePower | 1.3.6.1.4.1.1718.4.1.5.3.1.8 | Integer32 (-1..25000) | RO | 415 | |||||||||||||||||
| Cst4PhaseApparentPower | 1.3.6.1.4.1.1718.4.1.5.3.1.9 | Integer32 (-1..25000) | RO | ||||||||||||||||||
column · Integer32 (-1..25000) · read-only · current The measured apparent power on the phase in Volt-Amps.
| |||||||||||||||||||||
| Cst4PhasePowerFactor | 1.3.6.1.4.1.1718.4.1.5.3.1.10 | Integer32 (-1..100) | RO | ||||||||||||||||||
column · Integer32 (-1..100) · read-only · current The measured power factor on the phase in hundredths.
| |||||||||||||||||||||
| Cst4PhasePowerFactorStatus | 1.3.6.1.4.1.1718.4.1.5.3.1.11 | DeviceStatus | RO | 0 | |||||||||||||||||
column · DeviceStatus · read-only · current The status of the measured power factor on the phase. Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4PhaseReactance | 1.3.6.1.4.1.1718.4.1.5.3.1.12 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current The status of the measured reactance of the phase.
| |||||||||||||||||||||
| Cst4PhaseEnergy | 1.3.6.1.4.1.1718.4.1.5.3.1.13 | Integer32 (-1..2147483647) | RO | ||||||||||||||||||
column · Integer32 (-1..2147483647) · read-only · current The total energy consumption of loads through the phase in tenth Kilowatt-Hours.
| |||||||||||||||||||||
| Tst4PhaseEventConfigTable | 1.3.6.1.4.1.1718.4.1.5.4 | NA | |||||||||||||||||||
table · not-accessible · current Phase event configuration table. | |||||||||||||||||||||
| Rst4PhaseEventConfigEntry | 1.3.6.1.4.1.1718.4.1.5.4.1 | NA | |||||||||||||||||||
row · not-accessible · current Event configuration objects for a particular phase. | |||||||||||||||||||||
| Cst4PhaseNotifications | 1.3.6.1.4.1.1718.4.1.5.4.1.1 | EventNotificationMethods | RW | ||||||||||||||||||
column · EventNotificationMethods · read-write · current The notification methods enabled for phase events. | |||||||||||||||||||||
| Cst4PhaseVoltageLowAlarm | 1.3.6.1.4.1.1718.4.1.5.4.1.2 | Integer32 (0..6000) | RW | ||||||||||||||||||
column · Integer32 (0..6000) · read-write · current The current low alarm threshold of the phase in tenth Volts.
| |||||||||||||||||||||
| Cst4PhaseVoltageLowWarning | 1.3.6.1.4.1.1718.4.1.5.4.1.3 | Integer32 (0..6000) | RW | ||||||||||||||||||
column · Integer32 (0..6000) · read-write · current The current low warning threshold of the phase in tenth Volts.
| |||||||||||||||||||||
| Cst4PhaseVoltageHighWarning | 1.3.6.1.4.1.1718.4.1.5.4.1.4 | Integer32 (0..6000) | RW | ||||||||||||||||||
column · Integer32 (0..6000) · read-write · current The current high warning threshold of the phase in tenth Volts.
| |||||||||||||||||||||
| Cst4PhaseVoltageHighAlarm | 1.3.6.1.4.1.1718.4.1.5.4.1.5 | Integer32 (0..6000) | RW | ||||||||||||||||||
column · Integer32 (0..6000) · read-write · current The current high alarm threshold of the phase in tenth Volts.
| |||||||||||||||||||||
| Cst4PhasePowerFactorLowAlarm | 1.3.6.1.4.1.1718.4.1.5.4.1.6 | Integer32 (0..100) | RW | ||||||||||||||||||
column · Integer32 (0..100) · read-write · current The low power factor alarm threshold of the phase in hundredths.
| |||||||||||||||||||||
| Cst4PhasePowerFactorLowWarning | 1.3.6.1.4.1.1718.4.1.5.4.1.7 | Integer32 (0..100) | RW | ||||||||||||||||||
column · Integer32 (0..100) · read-write · current The low power factor warning threshold of the phase in hundredths.
| |||||||||||||||||||||
| Nst4OverCurrentProtectors | 1.3.6.1.4.1.1718.4.1.6 | ||||||||||||||||||||
| Nst4OcpCommonConfig | 1.3.6.1.4.1.1718.4.1.6.1 | ||||||||||||||||||||
| Tst4OcpConfigTable | 1.3.6.1.4.1.1718.4.1.6.2 | NA | |||||||||||||||||||
table · not-accessible · current Over-current protector configuration table. | |||||||||||||||||||||
| Rst4OcpConfigEntry | 1.3.6.1.4.1.1718.4.1.6.2.1 | NA | |||||||||||||||||||
row · not-accessible · current Configuration objects for a particular over-current protector. | |||||||||||||||||||||
| Cst4OcpIndex | 1.3.6.1.4.1.1718.4.1.6.2.1.1 | Integer32 (1..64) | NA | ||||||||||||||||||
column · Integer32 (1..64) · not-accessible · current Over-current protector index. | |||||||||||||||||||||
| Cst4OcpID | 1.3.6.1.4.1.1718.4.1.6.2.1.2 | DisplayString (SIZE (3..4)) | RO | ||||||||||||||||||
column · DisplayString (SIZE (3..4)) · read-only · current The internal ID of the over-current protector. Format=AAN[N]. | |||||||||||||||||||||
| Cst4OcpLabel | 1.3.6.1.4.1.1718.4.1.6.2.1.4 | DisplayString (SIZE (0..32)) | RO | AA:L1-L2-BR1 | |||||||||||||||||
column · DisplayString (SIZE (0..32)) · read-only · current The system label assigned to the over-current protector for identification. | |||||||||||||||||||||
| Cst4OcpType | 1.3.6.1.4.1.1718.4.1.6.2.1.6 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current The type of over-current protector.
| |||||||||||||||||||||
| Cst4OcpCurrentCapacity | 1.3.6.1.4.1.1718.4.1.6.2.1.7 | Integer32 (0..125) | RW | ||||||||||||||||||
column · Integer32 (0..125) · read-write · current The user-configured current capacity of the over-current protector in Amps.
| |||||||||||||||||||||
| Cst4OcpCurrentCapacityMax | 1.3.6.1.4.1.1718.4.1.6.2.1.8 | Integer32 (0..125) | RO | ||||||||||||||||||
column · Integer32 (0..125) · read-only · current The factory-set maximum allowed for the user-configured current capacity of the over-current protector in Amps.
| |||||||||||||||||||||
| Cst4OcpBranchCount | 1.3.6.1.4.1.1718.4.1.6.2.1.20 | Integer32 (0..12) | RO | ||||||||||||||||||
column · Integer32 (0..12) · read-only · current The number of branches downstream from the over-current protector. | |||||||||||||||||||||
| Cst4OcpOutletCount | 1.3.6.1.4.1.1718.4.1.6.2.1.21 | Integer32 (0..128) | RO | ||||||||||||||||||
column · Integer32 (0..128) · read-only · current The number of outlets powered from the over-current protector. | |||||||||||||||||||||
| Tst4OcpMonitorTable | 1.3.6.1.4.1.1718.4.1.6.3 | NA | |||||||||||||||||||
table · not-accessible · current Over-current protector monitor table. | |||||||||||||||||||||
| Rst4OcpMonitorEntry | 1.3.6.1.4.1.1718.4.1.6.3.1 | NA | |||||||||||||||||||
row · not-accessible · current Objects to monitor for a particular over-current protector. | |||||||||||||||||||||
| Cst4OcpStatus | 1.3.6.1.4.1.1718.4.1.6.3.1.1 | DeviceStatus | RO | 0 | |||||||||||||||||
column · DeviceStatus · read-only · current The status of the over-current protector. Example values from LibreNMS test devices
| |||||||||||||||||||||
| Tst4OcpEventConfigTable | 1.3.6.1.4.1.1718.4.1.6.4 | NA | |||||||||||||||||||
table · not-accessible · current Over-current protector event configuration table. | |||||||||||||||||||||
| Rst4OcpEventConfigEntry | 1.3.6.1.4.1.1718.4.1.6.4.1 | NA | |||||||||||||||||||
row · not-accessible · current Event configuration objects for a particular over-current protector. | |||||||||||||||||||||
| Cst4OcpNotifications | 1.3.6.1.4.1.1718.4.1.6.4.1.1 | EventNotificationMethods | RW | ||||||||||||||||||
column · EventNotificationMethods · read-write · current The notification methods enabled for over-current protector events. | |||||||||||||||||||||
| Nst4Branches | 1.3.6.1.4.1.1718.4.1.7 | ||||||||||||||||||||
| Nst4BranchCommonConfig | 1.3.6.1.4.1.1718.4.1.7.1 | ||||||||||||||||||||
| Sst4BranchCurrentHysteresis | 1.3.6.1.4.1.1718.4.1.7.1.1 | Integer32 (0..100) | RW | ||||||||||||||||||
scalar · Integer32 (0..100) · read-write · current The current hysteresis of the branch in tenth Amps.
| |||||||||||||||||||||
| Tst4BranchConfigTable | 1.3.6.1.4.1.1718.4.1.7.2 | NA | |||||||||||||||||||
table · not-accessible · current Branch configuration table. | |||||||||||||||||||||
| Rst4BranchConfigEntry | 1.3.6.1.4.1.1718.4.1.7.2.1 | NA | |||||||||||||||||||
row · not-accessible · current Configuration objects for a particular branch. | |||||||||||||||||||||
| Cst4BranchIndex | 1.3.6.1.4.1.1718.4.1.7.2.1.1 | Integer32 (1..64) | NA | ||||||||||||||||||
column · Integer32 (1..64) · not-accessible · current Branch index. | |||||||||||||||||||||
| Cst4BranchID | 1.3.6.1.4.1.1718.4.1.7.2.1.2 | DisplayString (SIZE (3..4)) | RO | ||||||||||||||||||
column · DisplayString (SIZE (3..4)) · read-only · current The internal ID of the branch. Format=AAN[N]. | |||||||||||||||||||||
| Cst4BranchLabel | 1.3.6.1.4.1.1718.4.1.7.2.1.4 | DisplayString (SIZE (0..32)) | RO | AA:L1-L2-BR1 | |||||||||||||||||
| Cst4BranchCurrentCapacity | 1.3.6.1.4.1.1718.4.1.7.2.1.6 | Integer32 (0..125) | RO | ||||||||||||||||||
column · Integer32 (0..125) · read-only · current The current capacity of the branch in Amps.
| |||||||||||||||||||||
| Cst4BranchPhaseID | 1.3.6.1.4.1.1718.4.1.7.2.1.20 | DisplayString (SIZE (3)) | RO | ||||||||||||||||||
column · DisplayString (SIZE (3)) · read-only · current The internal ID of the phase powering this branch. Format=AAN. | |||||||||||||||||||||
| Cst4BranchOcpID | 1.3.6.1.4.1.1718.4.1.7.2.1.21 | DisplayString (SIZE (3..4)) | RO | ||||||||||||||||||
column · DisplayString (SIZE (3..4)) · read-only · current The internal ID of the over-current protector powering this outlet. Format=AAN[N]. | |||||||||||||||||||||
| Cst4BranchOutletCount | 1.3.6.1.4.1.1718.4.1.7.2.1.30 | Integer32 (0..128) | RO | ||||||||||||||||||
column · Integer32 (0..128) · read-only · current The number of outlets powered from the branch. | |||||||||||||||||||||
| Tst4BranchMonitorTable | 1.3.6.1.4.1.1718.4.1.7.3 | NA | |||||||||||||||||||
table · not-accessible · current Branch monitor table. | |||||||||||||||||||||
| Rst4BranchMonitorEntry | 1.3.6.1.4.1.1718.4.1.7.3.1 | NA | |||||||||||||||||||
row · not-accessible · current Objects to monitor for a particular branch. | |||||||||||||||||||||
| Cst4BranchState | 1.3.6.1.4.1.1718.4.1.7.3.1.1 | DeviceState | RO | 1 | |||||||||||||||||
column · DeviceState · read-only · current The on/off state of the branch. Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4BranchStatus | 1.3.6.1.4.1.1718.4.1.7.3.1.2 | DeviceStatus | RO | 0 | |||||||||||||||||
column · DeviceStatus · read-only · current The status of the branch. Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4BranchCurrent | 1.3.6.1.4.1.1718.4.1.7.3.1.3 | Integer32 (-1..12500) | RO | ||||||||||||||||||
column · Integer32 (-1..12500) · read-only · current The measured current on the branch in hundredth Amps.
| |||||||||||||||||||||
| Cst4BranchCurrentStatus | 1.3.6.1.4.1.1718.4.1.7.3.1.4 | DeviceStatus | RO | 0 | |||||||||||||||||
column · DeviceStatus · read-only · current The status of the measured current on the branch. Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4BranchCurrentUtilized | 1.3.6.1.4.1.1718.4.1.7.3.1.5 | Integer32 (-1..1200) | RO | ||||||||||||||||||
column · Integer32 (-1..1200) · read-only · current The amount of the branch current capacity used in tenth percent.
| |||||||||||||||||||||
| Tst4BranchEventConfigTable | 1.3.6.1.4.1.1718.4.1.7.4 | NA | |||||||||||||||||||
table · not-accessible · current Branch event configuration table. | |||||||||||||||||||||
| Rst4BranchEventConfigEntry | 1.3.6.1.4.1.1718.4.1.7.4.1 | NA | |||||||||||||||||||
row · not-accessible · current Event configuration objects for a particular branch. | |||||||||||||||||||||
| Cst4BranchNotifications | 1.3.6.1.4.1.1718.4.1.7.4.1.1 | EventNotificationMethods | RW | ||||||||||||||||||
column · EventNotificationMethods · read-write · current The notification methods enabled for branch events. | |||||||||||||||||||||
| Cst4BranchCurrentLowAlarm | 1.3.6.1.4.1.1718.4.1.7.4.1.2 | Integer32 (0..1250) | RW | ||||||||||||||||||
column · Integer32 (0..1250) · read-write · current The current low alarm threshold of the branch in tenth Amps.
| |||||||||||||||||||||
| Cst4BranchCurrentLowWarning | 1.3.6.1.4.1.1718.4.1.7.4.1.3 | Integer32 (0..1250) | RW | ||||||||||||||||||
column · Integer32 (0..1250) · read-write · current The current low warning threshold of the branch in tenth Amps.
| |||||||||||||||||||||
| Cst4BranchCurrentHighWarning | 1.3.6.1.4.1.1718.4.1.7.4.1.4 | Integer32 (0..1250) | RW | ||||||||||||||||||
column · Integer32 (0..1250) · read-write · current The current high warning threshold of the branch in tenth Amps.
| |||||||||||||||||||||
| Cst4BranchCurrentHighAlarm | 1.3.6.1.4.1.1718.4.1.7.4.1.5 | Integer32 (0..1250) | RW | ||||||||||||||||||
column · Integer32 (0..1250) · read-write · current The current high alarm threshold of the branch in tenth Amps.
| |||||||||||||||||||||
| Nst4Outlets | 1.3.6.1.4.1.1718.4.1.8 | ||||||||||||||||||||
| Nst4OutletCommonConfig | 1.3.6.1.4.1.1718.4.1.8.1 | ||||||||||||||||||||
| Sst4OutletCurrentHysteresis | 1.3.6.1.4.1.1718.4.1.8.1.1 | Integer32 (0..100) | RW | ||||||||||||||||||
scalar · Integer32 (0..100) · read-write · current The current hysteresis of the outlet in tenth Amps.
| |||||||||||||||||||||
| Sst4OutletActivePowerHysteresis | 1.3.6.1.4.1.1718.4.1.8.1.2 | Integer32 (0..1000) | RW | ||||||||||||||||||
scalar · Integer32 (0..1000) · read-write · current The power hysteresis of the outlet in Watts.
| |||||||||||||||||||||
| Sst4OutletPowerFactorHysteresis | 1.3.6.1.4.1.1718.4.1.8.1.3 | Integer32 (0..20) | RW | ||||||||||||||||||
scalar · Integer32 (0..20) · read-write · current The power factor hysteresis of the outlet in hundredths.
| |||||||||||||||||||||
| Sst4OutletSequenceInterval | 1.3.6.1.4.1.1718.4.1.8.1.10 | Integer32 (0..15) | RW | ||||||||||||||||||
scalar · Integer32 (0..15) · read-write · current The power-on sequencing interval for all outlets in seconds.
| |||||||||||||||||||||
| Sst4OutletRebootDelay | 1.3.6.1.4.1.1718.4.1.8.1.11 | Integer32 (5..600) | RW | ||||||||||||||||||
scalar · Integer32 (5..600) · read-write · current The reboot delay for all outlets in seconds.
| |||||||||||||||||||||
| Sst4OutletStateChangeLogging | 1.3.6.1.4.1.1718.4.1.8.1.12 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current Enables or disables informational Outlet State Change event logging.
| |||||||||||||||||||||
| Tst4OutletConfigTable | 1.3.6.1.4.1.1718.4.1.8.2 | NA | |||||||||||||||||||
table · not-accessible · current Outlet configuration table. | |||||||||||||||||||||
| Rst4OutletConfigEntry | 1.3.6.1.4.1.1718.4.1.8.2.1 | NA | |||||||||||||||||||
row · not-accessible · current Configuration objects for a particular outlet. | |||||||||||||||||||||
| Cst4OutletIndex | 1.3.6.1.4.1.1718.4.1.8.2.1.1 | Integer32 (1..128) | NA | ||||||||||||||||||
column · Integer32 (1..128) · not-accessible · current Outlet index. | |||||||||||||||||||||
| Cst4OutletID | 1.3.6.1.4.1.1718.4.1.8.2.1.2 | DisplayString (SIZE (3..5)) | RO | ||||||||||||||||||
column · DisplayString (SIZE (3..5)) · read-only · current The internal ID of the outlet. Format=AAN[N[N]]. | |||||||||||||||||||||
| Cst4OutletName | 1.3.6.1.4.1.1718.4.1.8.2.1.3 | DisplayString (SIZE (0..32)) | RW | ||||||||||||||||||
column · DisplayString (SIZE (0..32)) · read-write · current The name of the outlet. | |||||||||||||||||||||
| Cst4OutletCapabilities | 1.3.6.1.4.1.1718.4.1.8.2.1.5 | Bits | RO | ||||||||||||||||||
column · Bits · read-only · current The capabilities of the outlet.
| |||||||||||||||||||||
| Cst4OutletSocketType | 1.3.6.1.4.1.1718.4.1.8.2.1.6 | DisplayString (SIZE (0..32)) | RO | ||||||||||||||||||
column · DisplayString (SIZE (0..32)) · read-only · current The socket type of the outlet. | |||||||||||||||||||||
| Cst4OutletCurrentCapacity | 1.3.6.1.4.1.1718.4.1.8.2.1.7 | Integer32 (0..125) | RO | ||||||||||||||||||
column · Integer32 (0..125) · read-only · current The current capacity of the outlet in Amps.
| |||||||||||||||||||||
| Cst4OutletPowerCapacity | 1.3.6.1.4.1.1718.4.1.8.2.1.8 | Integer32 (0..10000) | RO | ||||||||||||||||||
column · Integer32 (0..10000) · read-only · current The power capacity of the outlet in Volt-Amps. For DC products, this is identical to power capacity in Watts.
| |||||||||||||||||||||
| Cst4OutletSocketAdapter | 1.3.6.1.4.1.1718.4.1.8.2.1.9 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current The manually-selected or automatically-detected socket adapter of the outlet.
| |||||||||||||||||||||
| Cst4OutletWakeupState | 1.3.6.1.4.1.1718.4.1.8.2.1.20 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current The wakeup state of the outlet.
| |||||||||||||||||||||
| Cst4OutletPostOnDelay | 1.3.6.1.4.1.1718.4.1.8.2.1.21 | Integer32 (0..900) | RW | ||||||||||||||||||
column · Integer32 (0..900) · read-write · current The post-on delay of the outlet in seconds.
| |||||||||||||||||||||
| Cst4OutletPhaseID | 1.3.6.1.4.1.1718.4.1.8.2.1.30 | DisplayString (SIZE (3)) | RO | ||||||||||||||||||
column · DisplayString (SIZE (3)) · read-only · current The internal ID of the phase powering this outlet. Format=AAN. | |||||||||||||||||||||
| Cst4OutletOcpID | 1.3.6.1.4.1.1718.4.1.8.2.1.31 | DisplayString (SIZE (3..4)) | RO | ||||||||||||||||||
column · DisplayString (SIZE (3..4)) · read-only · current The internal ID of the over-current protector powering this outlet. Format=AAN[N]. | |||||||||||||||||||||
| Cst4OutletBranchID | 1.3.6.1.4.1.1718.4.1.8.2.1.32 | DisplayString (SIZE (3..4)) | RO | ||||||||||||||||||
column · DisplayString (SIZE (3..4)) · read-only · current The internal ID of the branch powering this outlet. Format=AAN[N]. | |||||||||||||||||||||
| Tst4OutletMonitorTable | 1.3.6.1.4.1.1718.4.1.8.3 | NA | |||||||||||||||||||
table · not-accessible · current Outlet monitor table. | |||||||||||||||||||||
| Rst4OutletMonitorEntry | 1.3.6.1.4.1.1718.4.1.8.3.1 | NA | |||||||||||||||||||
row · not-accessible · current Objects to monitor for a particular outlet. | |||||||||||||||||||||
| Cst4OutletState | 1.3.6.1.4.1.1718.4.1.8.3.1.1 | DeviceState | RO | ||||||||||||||||||
column · DeviceState · read-only · current The on/off state of the outlet. | |||||||||||||||||||||
| Cst4OutletStatus | 1.3.6.1.4.1.1718.4.1.8.3.1.2 | DeviceStatus | RO | ||||||||||||||||||
column · DeviceStatus · read-only · current The status of the outlet. | |||||||||||||||||||||
| Cst4OutletCurrent | 1.3.6.1.4.1.1718.4.1.8.3.1.3 | Integer32 (-1..12500) | RO | ||||||||||||||||||
column · Integer32 (-1..12500) · read-only · current The measured current on the outlet in hundredth Amps.
| |||||||||||||||||||||
| Cst4OutletCurrentStatus | 1.3.6.1.4.1.1718.4.1.8.3.1.4 | DeviceStatus | RO | ||||||||||||||||||
column · DeviceStatus · read-only · current The status of the measured current on the outlet. | |||||||||||||||||||||
| Cst4OutletCurrentUtilized | 1.3.6.1.4.1.1718.4.1.8.3.1.5 | Integer32 (-1..1200) | RO | ||||||||||||||||||
column · Integer32 (-1..1200) · read-only · current The amount of the outlet current capacity used in tenth percent.
| |||||||||||||||||||||
| Cst4OutletVoltage | 1.3.6.1.4.1.1718.4.1.8.3.1.6 | Integer32 (-1..6000) | RO | ||||||||||||||||||
column · Integer32 (-1..6000) · read-only · current The measured voltage of the outlet in tenth Volts.
| |||||||||||||||||||||
| Cst4OutletActivePower | 1.3.6.1.4.1.1718.4.1.8.3.1.7 | Integer32 (-1..10000) | RO | ||||||||||||||||||
column · Integer32 (-1..10000) · read-only · current The measured active power of the outlet in Watts.
| |||||||||||||||||||||
| Cst4OutletActivePowerStatus | 1.3.6.1.4.1.1718.4.1.8.3.1.8 | DeviceStatus | RO | ||||||||||||||||||
column · DeviceStatus · read-only · current The status of the measured active power of the outlet. | |||||||||||||||||||||
| Cst4OutletApparentPower | 1.3.6.1.4.1.1718.4.1.8.3.1.9 | Integer32 (-1..10000) | RO | ||||||||||||||||||
column · Integer32 (-1..10000) · read-only · current The measured apparent power of the outlet in Volt-Amps.
| |||||||||||||||||||||
| Cst4OutletPowerFactor | 1.3.6.1.4.1.1718.4.1.8.3.1.10 | Integer32 (-1..100) | RO | ||||||||||||||||||
column · Integer32 (-1..100) · read-only · current The measured power factor of the outlet in hundredths.
| |||||||||||||||||||||
| Cst4OutletPowerFactorStatus | 1.3.6.1.4.1.1718.4.1.8.3.1.11 | DeviceStatus | RO | ||||||||||||||||||
column · DeviceStatus · read-only · current The status of the measured power factor of the outlet. | |||||||||||||||||||||
| Cst4OutletCurrentCrestFactor | 1.3.6.1.4.1.1718.4.1.8.3.1.12 | Integer32 (-1..250) | RO | ||||||||||||||||||
column · Integer32 (-1..250) · read-only · current The measured crest factor of the outlet in tenths.
| |||||||||||||||||||||
| Cst4OutletReactance | 1.3.6.1.4.1.1718.4.1.8.3.1.13 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current The status of the measured reactance of the outlet.
| |||||||||||||||||||||
| Cst4OutletEnergy | 1.3.6.1.4.1.1718.4.1.8.3.1.14 | Integer32 (-1..2147483647) | RO | ||||||||||||||||||
column · Integer32 (-1..2147483647) · read-only · current The total energy consumption of the device plugged into the outlet in Watt-Hours.
| |||||||||||||||||||||
| Tst4OutletEventConfigTable | 1.3.6.1.4.1.1718.4.1.8.4 | NA | |||||||||||||||||||
table · not-accessible · current Outlet event configuration table. | |||||||||||||||||||||
| Rst4OutletEventConfigEntry | 1.3.6.1.4.1.1718.4.1.8.4.1 | NA | |||||||||||||||||||
row · not-accessible · current Event configuration objects for a particular outlet. | |||||||||||||||||||||
| Cst4OutletNotifications | 1.3.6.1.4.1.1718.4.1.8.4.1.1 | EventNotificationMethods | RW | ||||||||||||||||||
column · EventNotificationMethods · read-write · current The notification methods enabled for outlet events. | |||||||||||||||||||||
| Cst4OutletCurrentLowAlarm | 1.3.6.1.4.1.1718.4.1.8.4.1.2 | Integer32 (0..1250) | RW | ||||||||||||||||||
column · Integer32 (0..1250) · read-write · current The current low alarm threshold of the outlet in tenth Amps.
| |||||||||||||||||||||
| Cst4OutletCurrentLowWarning | 1.3.6.1.4.1.1718.4.1.8.4.1.3 | Integer32 (0..1250) | RW | ||||||||||||||||||
column · Integer32 (0..1250) · read-write · current The current low warning threshold of the outlet in tenth Amps.
| |||||||||||||||||||||
| Cst4OutletCurrentHighWarning | 1.3.6.1.4.1.1718.4.1.8.4.1.4 | Integer32 (0..1250) | RW | ||||||||||||||||||
column · Integer32 (0..1250) · read-write · current The current high warning threshold of the outlet in tenth Amps.
| |||||||||||||||||||||
| Cst4OutletCurrentHighAlarm | 1.3.6.1.4.1.1718.4.1.8.4.1.5 | Integer32 (0..1250) | RW | ||||||||||||||||||
column · Integer32 (0..1250) · read-write · current The current high alarm threshold of the outlet in tenth Amps.
| |||||||||||||||||||||
| Cst4OutletActivePowerLowAlarm | 1.3.6.1.4.1.1718.4.1.8.4.1.6 | Integer32 (0..10000) | RW | ||||||||||||||||||
column · Integer32 (0..10000) · read-write · current The active power low alarm threshold of the outlet in Watts.
| |||||||||||||||||||||
| Cst4OutletActivePowerLowWarning | 1.3.6.1.4.1.1718.4.1.8.4.1.7 | Integer32 (0..10000) | RW | ||||||||||||||||||
column · Integer32 (0..10000) · read-write · current The active power low warning threshold of the outlet in Watts.
| |||||||||||||||||||||
| Cst4OutletActivePowerHighWarning | 1.3.6.1.4.1.1718.4.1.8.4.1.8 | Integer32 (0..10000) | RW | ||||||||||||||||||
column · Integer32 (0..10000) · read-write · current The active power high warning threshold of the outlet in Watts.
| |||||||||||||||||||||
| Cst4OutletActivePowerHighAlarm | 1.3.6.1.4.1.1718.4.1.8.4.1.9 | Integer32 (0..10000) | RW | ||||||||||||||||||
column · Integer32 (0..10000) · read-write · current The active power high alarm threshold of the outlet in Watts.
| |||||||||||||||||||||
| Cst4OutletPowerFactorLowAlarm | 1.3.6.1.4.1.1718.4.1.8.4.1.10 | Integer32 (0..100) | RW | ||||||||||||||||||
column · Integer32 (0..100) · read-write · current The low power factor alarm threshold of the outlet in hundredths.
| |||||||||||||||||||||
| Cst4OutletPowerFactorLowWarning | 1.3.6.1.4.1.1718.4.1.8.4.1.11 | Integer32 (0..100) | RW | ||||||||||||||||||
column · Integer32 (0..100) · read-write · current The low power factor warning threshold of the outlet in hundredths.
| |||||||||||||||||||||
| Tst4OutletControlTable | 1.3.6.1.4.1.1718.4.1.8.5 | NA | |||||||||||||||||||
table · not-accessible · current Outlet control table. | |||||||||||||||||||||
| Rst4OutletControlEntry | 1.3.6.1.4.1.1718.4.1.8.5.1 | NA | |||||||||||||||||||
row · not-accessible · current Objects for control of a particular outlet. | |||||||||||||||||||||
| Cst4OutletControlState | 1.3.6.1.4.1.1718.4.1.8.5.1.1 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current The control state of the outlet.
| |||||||||||||||||||||
| Cst4OutletControlAction | 1.3.6.1.4.1.1718.4.1.8.5.1.2 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current An action to change the control state of the outlet, or to queue an action.
| |||||||||||||||||||||
| Nst4OutletCommonControl | 1.3.6.1.4.1.1718.4.1.8.6 | ||||||||||||||||||||
| Sst4OutletQueueControl | 1.3.6.1.4.1.1718.4.1.8.6.1 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current An action to clear or commit queued outlet control actions. A read of this object returns clear(0) if queue is empty, and commit(1) if the queue is not empty.
| |||||||||||||||||||||
| Nst4TemperatureSensors | 1.3.6.1.4.1.1718.4.1.9 | ||||||||||||||||||||
| Nst4TempSensorCommonConfig | 1.3.6.1.4.1.1718.4.1.9.1 | ||||||||||||||||||||
| Sst4TempSensorHysteresis | 1.3.6.1.4.1.1718.4.1.9.1.1 | Integer32 (0..54) | RW | ||||||||||||||||||
scalar · Integer32 (0..54) · read-write · current The temperature hysteresis of the sensor in degrees, using the scale selected by st4TempSensorScale.
| |||||||||||||||||||||
| Sst4TempSensorScale | 1.3.6.1.4.1.1718.4.1.9.1.10 | INTEGER | RW | celsius(0) | |||||||||||||||||
scalar · INTEGER · read-write · current The current scale used for all temperature values.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| Tst4TempSensorConfigTable | 1.3.6.1.4.1.1718.4.1.9.2 | NA | |||||||||||||||||||
table · not-accessible · current Temperature sensor configuration table. | |||||||||||||||||||||
| Rst4TempSensorConfigEntry | 1.3.6.1.4.1.1718.4.1.9.2.1 | NA | |||||||||||||||||||
row · not-accessible · current Configuration objects for a particular temperature sensor. | |||||||||||||||||||||
| Cst4TempSensorIndex | 1.3.6.1.4.1.1718.4.1.9.2.1.1 | Integer32 (0..2) | NA | ||||||||||||||||||
column · Integer32 (0..2) · not-accessible · current Temperature sensor index. | |||||||||||||||||||||
| Cst4TempSensorID | 1.3.6.1.4.1.1718.4.1.9.2.1.2 | DisplayString (SIZE (2)) | RO | A1 | |||||||||||||||||
| Cst4TempSensorName | 1.3.6.1.4.1.1718.4.1.9.2.1.3 | DisplayString (SIZE (0..32)) | RW | Temp_Sensor_A1 | |||||||||||||||||
| Cst4TempSensorValueMin | 1.3.6.1.4.1.1718.4.1.9.2.1.4 | Integer32 (-40..253) | RO | -40 | |||||||||||||||||
column · Integer32 (-40..253) · read-only · current The minimum temperature limit of the sensor in degrees, using the scale selected by st4TempSensorScale.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4TempSensorValueMax | 1.3.6.1.4.1.1718.4.1.9.2.1.5 | Integer32 (-40..253) | RO | 123 | |||||||||||||||||
column · Integer32 (-40..253) · read-only · current The maximum temperature limit of the sensor in degrees, using the scale selected by st4TempSensorScale.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| Tst4TempSensorMonitorTable | 1.3.6.1.4.1.1718.4.1.9.3 | NA | |||||||||||||||||||
table · not-accessible · current Temperature sensor monitor table. | |||||||||||||||||||||
| Rst4TempSensorMonitorEntry | 1.3.6.1.4.1.1718.4.1.9.3.1 | NA | |||||||||||||||||||
row · not-accessible · current Objects to monitor for a particular temperature sensor. | |||||||||||||||||||||
| Cst4TempSensorValue | 1.3.6.1.4.1.1718.4.1.9.3.1.1 | Integer32 (-410..2540) | RO | -410 | |||||||||||||||||
column · Integer32 (-410..2540) · read-only · current The measured temperature on the sensor in tenth degrees using the scale selected by st4TempSensorScale. -410 means the temperature reading is invalid.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4TempSensorStatus | 1.3.6.1.4.1.1718.4.1.9.3.1.2 | DeviceStatus | RO | 0 | |||||||||||||||||
| Tst4TempSensorEventConfigTable | 1.3.6.1.4.1.1718.4.1.9.4 | NA | |||||||||||||||||||
table · not-accessible · current Temperature sensor event configuration table. | |||||||||||||||||||||
| Rst4TempSensorEventConfigEntry | 1.3.6.1.4.1.1718.4.1.9.4.1 | NA | |||||||||||||||||||
row · not-accessible · current Event configuration objects for a particular temperature sensor. | |||||||||||||||||||||
| Cst4TempSensorNotifications | 1.3.6.1.4.1.1718.4.1.9.4.1.1 | EventNotificationMethods | RW | C0 0 1 | |||||||||||||||||
column · EventNotificationMethods · read-write · current The notification methods enabled for temperature sensor events. Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4TempSensorLowAlarm | 1.3.6.1.4.1.1718.4.1.9.4.1.2 | Integer32 (-40..253) | RW | 1 | |||||||||||||||||
column · Integer32 (-40..253) · read-write · current The low alarm threshold of the temperature sensor in degrees.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4TempSensorLowWarning | 1.3.6.1.4.1.1718.4.1.9.4.1.3 | Integer32 (-40..253) | RW | 5 | |||||||||||||||||
column · Integer32 (-40..253) · read-write · current The low warning threshold of the temperature sensor in degrees.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4TempSensorHighWarning | 1.3.6.1.4.1.1718.4.1.9.4.1.4 | Integer32 (-40..253) | RW | 45 | |||||||||||||||||
column · Integer32 (-40..253) · read-write · current The high warning threshold of the temperature sensor in degrees.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4TempSensorHighAlarm | 1.3.6.1.4.1.1718.4.1.9.4.1.5 | Integer32 (-40..253) | RW | 50 | |||||||||||||||||
column · Integer32 (-40..253) · read-write · current The high alarm threshold of the temperature sensor in degrees.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| Nst4HumiditySensors | 1.3.6.1.4.1.1718.4.1.10 | ||||||||||||||||||||
| Nst4HumidSensorCommonConfig | 1.3.6.1.4.1.1718.4.1.10.1 | ||||||||||||||||||||
| Sst4HumidSensorHysteresis | 1.3.6.1.4.1.1718.4.1.10.1.1 | Integer32 (0..20) | RW | ||||||||||||||||||
scalar · Integer32 (0..20) · read-write · current The humidity hysteresis of the sensor in percent relative humidity.
| |||||||||||||||||||||
| Tst4HumidSensorConfigTable | 1.3.6.1.4.1.1718.4.1.10.2 | NA | |||||||||||||||||||
table · not-accessible · current Humidity sensor configuration table. | |||||||||||||||||||||
| Rst4HumidSensorConfigEntry | 1.3.6.1.4.1.1718.4.1.10.2.1 | NA | |||||||||||||||||||
row · not-accessible · current Configuration objects for a particular humidity sensor. | |||||||||||||||||||||
| Cst4HumidSensorIndex | 1.3.6.1.4.1.1718.4.1.10.2.1.1 | Integer32 (0..2) | NA | ||||||||||||||||||
column · Integer32 (0..2) · not-accessible · current Humidity sensor index. | |||||||||||||||||||||
| Cst4HumidSensorID | 1.3.6.1.4.1.1718.4.1.10.2.1.2 | DisplayString (SIZE (2)) | RO | A1 | |||||||||||||||||
| Cst4HumidSensorName | 1.3.6.1.4.1.1718.4.1.10.2.1.3 | DisplayString (SIZE (0..32)) | RW | Humid_Sensor_A1 | |||||||||||||||||
| Tst4HumidSensorMonitorTable | 1.3.6.1.4.1.1718.4.1.10.3 | NA | |||||||||||||||||||
table · not-accessible · current Humidity sensor monitor table. | |||||||||||||||||||||
| Rst4HumidSensorMonitorEntry | 1.3.6.1.4.1.1718.4.1.10.3.1 | NA | |||||||||||||||||||
row · not-accessible · current Objects to monitor for a particular humidity sensor. | |||||||||||||||||||||
| Cst4HumidSensorValue | 1.3.6.1.4.1.1718.4.1.10.3.1.1 | Integer32 (-1..100) | RO | -1 | |||||||||||||||||
column · Integer32 (-1..100) · read-only · current The measured humidity on the sensor in percentage relative humidity.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4HumidSensorStatus | 1.3.6.1.4.1.1718.4.1.10.3.1.2 | DeviceStatus | RO | 7 | |||||||||||||||||
column · DeviceStatus · read-only · current The status of the humidity sensor. Example values from LibreNMS test devices
| |||||||||||||||||||||
| Tst4HumidSensorEventConfigTable | 1.3.6.1.4.1.1718.4.1.10.4 | NA | |||||||||||||||||||
table · not-accessible · current Humidity sensor event configuration table. | |||||||||||||||||||||
| Rst4HumidSensorEventConfigEntry | 1.3.6.1.4.1.1718.4.1.10.4.1 | NA | |||||||||||||||||||
row · not-accessible · current Event configuration objects for a particular humidity sensor. | |||||||||||||||||||||
| Cst4HumidSensorNotifications | 1.3.6.1.4.1.1718.4.1.10.4.1.1 | EventNotificationMethods | RW | C0 0 1 | |||||||||||||||||
column · EventNotificationMethods · read-write · current The notification methods enabled for humidity sensor events. Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4HumidSensorLowAlarm | 1.3.6.1.4.1.1718.4.1.10.4.1.2 | Integer32 (0..100) | RW | 5 | |||||||||||||||||
column · Integer32 (0..100) · read-write · current The low alarm threshold of the humidity sensor in percentage relative humidity.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4HumidSensorLowWarning | 1.3.6.1.4.1.1718.4.1.10.4.1.3 | Integer32 (0..100) | RW | 10 | |||||||||||||||||
column · Integer32 (0..100) · read-write · current The low warning threshold of the humidity sensor in percentage relative humidity.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4HumidSensorHighWarning | 1.3.6.1.4.1.1718.4.1.10.4.1.4 | Integer32 (0..100) | RW | 90 | |||||||||||||||||
column · Integer32 (0..100) · read-write · current The high warning threshold of the humidity sensor in percentage relative humidity.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cst4HumidSensorHighAlarm | 1.3.6.1.4.1.1718.4.1.10.4.1.5 | Integer32 (0..100) | RW | 95 | |||||||||||||||||
column · Integer32 (0..100) · read-write · current The high alarm threshold of the humidity sensor in percentage relative humidity.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| Nst4WaterSensors | 1.3.6.1.4.1.1718.4.1.11 | ||||||||||||||||||||
| Nst4WaterSensorCommonConfig | 1.3.6.1.4.1.1718.4.1.11.1 | ||||||||||||||||||||
| Tst4WaterSensorConfigTable | 1.3.6.1.4.1.1718.4.1.11.2 | NA | |||||||||||||||||||
table · not-accessible · current Water sensor configuration table. | |||||||||||||||||||||
| Rst4WaterSensorConfigEntry | 1.3.6.1.4.1.1718.4.1.11.2.1 | NA | |||||||||||||||||||
row · not-accessible · current Configuration objects for a particular water sensor. | |||||||||||||||||||||
| Cst4WaterSensorIndex | 1.3.6.1.4.1.1718.4.1.11.2.1.1 | Integer32 (0..1) | NA | ||||||||||||||||||
column · Integer32 (0..1) · not-accessible · current Water sensor index. | |||||||||||||||||||||
| Cst4WaterSensorID | 1.3.6.1.4.1.1718.4.1.11.2.1.2 | DisplayString (SIZE (2)) | RO | ||||||||||||||||||
column · DisplayString (SIZE (2)) · read-only · current The internal ID of the water sensor. Format=AN. | |||||||||||||||||||||
| Cst4WaterSensorName | 1.3.6.1.4.1.1718.4.1.11.2.1.3 | DisplayString (SIZE (0..32)) | RW | ||||||||||||||||||
column · DisplayString (SIZE (0..32)) · read-write · current The name of the water sensor. | |||||||||||||||||||||
| Tst4WaterSensorMonitorTable | 1.3.6.1.4.1.1718.4.1.11.3 | NA | |||||||||||||||||||
table · not-accessible · current Water sensor monitor table. | |||||||||||||||||||||
| Rst4WaterSensorMonitorEntry | 1.3.6.1.4.1.1718.4.1.11.3.1 | NA | |||||||||||||||||||
row · not-accessible · current Objects to monitor for a particular water sensor. | |||||||||||||||||||||
| Cst4WaterSensorStatus | 1.3.6.1.4.1.1718.4.1.11.3.1.1 | DeviceStatus | RO | ||||||||||||||||||
column · DeviceStatus · read-only · current The status of the water sensor. | |||||||||||||||||||||
| Tst4WaterSensorEventConfigTable | 1.3.6.1.4.1.1718.4.1.11.4 | NA | |||||||||||||||||||
table · not-accessible · current Water sensor event configuration table. | |||||||||||||||||||||
| Rst4WaterSensorEventConfigEntry | 1.3.6.1.4.1.1718.4.1.11.4.1 | NA | |||||||||||||||||||
row · not-accessible · current Event configuration objects for a particular water sensor. | |||||||||||||||||||||
| Cst4WaterSensorNotifications | 1.3.6.1.4.1.1718.4.1.11.4.1.1 | EventNotificationMethods | RW | ||||||||||||||||||
column · EventNotificationMethods · read-write · current The notification methods enabled for water sensor events. | |||||||||||||||||||||
| Nst4ContactClosureSensors | 1.3.6.1.4.1.1718.4.1.12 | ||||||||||||||||||||
| Nst4CcSensorCommonConfig | 1.3.6.1.4.1.1718.4.1.12.1 | ||||||||||||||||||||
| Tst4CcSensorConfigTable | 1.3.6.1.4.1.1718.4.1.12.2 | NA | |||||||||||||||||||
table · not-accessible · current Contact closure sensor configuration table. | |||||||||||||||||||||
| Rst4CcSensorConfigEntry | 1.3.6.1.4.1.1718.4.1.12.2.1 | NA | |||||||||||||||||||
row · not-accessible · current Configuration objects for a particular contact closure sensor.
| |||||||||||||||||||||
| Cst4CcSensorIndex | 1.3.6.1.4.1.1718.4.1.12.2.1.1 | Integer32 (0..4) | NA | ||||||||||||||||||
column · Integer32 (0..4) · not-accessible · current Contact closure sensor index. | |||||||||||||||||||||
| Cst4CcSensorID | 1.3.6.1.4.1.1718.4.1.12.2.1.2 | DisplayString (SIZE (2)) | RO | ||||||||||||||||||
column · DisplayString (SIZE (2)) · read-only · current The internal ID of the contact closure sensor. Format=AN. | |||||||||||||||||||||
| Cst4CcSensorName | 1.3.6.1.4.1.1718.4.1.12.2.1.3 | DisplayString (SIZE (0..32)) | RW | ||||||||||||||||||
column · DisplayString (SIZE (0..32)) · read-write · current The name of the contact closure sensor. | |||||||||||||||||||||
| Tst4CcSensorMonitorTable | 1.3.6.1.4.1.1718.4.1.12.3 | NA | |||||||||||||||||||
table · not-accessible · current Contact closure sensor monitor table. | |||||||||||||||||||||
| Rst4CcSensorMonitorEntry | 1.3.6.1.4.1.1718.4.1.12.3.1 | NA | |||||||||||||||||||
row · not-accessible · current Objects to monitor for a particular contact closure sensor.
| |||||||||||||||||||||
| Cst4CcSensorStatus | 1.3.6.1.4.1.1718.4.1.12.3.1.1 | DeviceStatus | RO | ||||||||||||||||||
column · DeviceStatus · read-only · current The status of the contact closure. | |||||||||||||||||||||
| Tst4CcSensorEventConfigTable | 1.3.6.1.4.1.1718.4.1.12.4 | NA | |||||||||||||||||||
table · not-accessible · current Contact closure sensor event configuration table. | |||||||||||||||||||||
| Rst4CcSensorEventConfigEntry | 1.3.6.1.4.1.1718.4.1.12.4.1 | NA | |||||||||||||||||||
row · not-accessible · current Event configuration objects for a particular contact closure sensor.
| |||||||||||||||||||||
| Cst4CcSensorNotifications | 1.3.6.1.4.1.1718.4.1.12.4.1.1 | EventNotificationMethods | RW | ||||||||||||||||||
column · EventNotificationMethods · read-write · current The notification methods enabled for contact closure sensor events. | |||||||||||||||||||||
| Nst4AnalogToDigitalConvSensors | 1.3.6.1.4.1.1718.4.1.13 | ||||||||||||||||||||
| Nst4AdcSensorCommonConfig | 1.3.6.1.4.1.1718.4.1.13.1 | ||||||||||||||||||||
| Sst4AdcSensorHysteresis | 1.3.6.1.4.1.1718.4.1.13.1.1 | Integer32 (0..20) | RW | ||||||||||||||||||
scalar · Integer32 (0..20) · read-write · current The 8-bit count hysteresis of the analog-to-digital converter sensor. | |||||||||||||||||||||
| Tst4AdcSensorConfigTable | 1.3.6.1.4.1.1718.4.1.13.2 | NA | |||||||||||||||||||
table · not-accessible · current Analog-to-digital converter sensor configuration table. | |||||||||||||||||||||
| Rst4AdcSensorConfigEntry | 1.3.6.1.4.1.1718.4.1.13.2.1 | NA | |||||||||||||||||||
row · not-accessible · current Configuration objects for a particular analog-to-digital converter sensor. | |||||||||||||||||||||
| Cst4AdcSensorIndex | 1.3.6.1.4.1.1718.4.1.13.2.1.1 | Integer32 (0..1) | NA | ||||||||||||||||||
column · Integer32 (0..1) · not-accessible · current Analog-to-digital converter sensor index. | |||||||||||||||||||||
| Cst4AdcSensorID | 1.3.6.1.4.1.1718.4.1.13.2.1.2 | DisplayString (SIZE (2)) | RO | ||||||||||||||||||
column · DisplayString (SIZE (2)) · read-only · current The internal ID of the analog-to-digital converter sensor. Format=AN. | |||||||||||||||||||||
| Cst4AdcSensorName | 1.3.6.1.4.1.1718.4.1.13.2.1.3 | DisplayString (SIZE (0..32)) | RW | ||||||||||||||||||
column · DisplayString (SIZE (0..32)) · read-write · current The name of the analog-to-digital converter sensor. | |||||||||||||||||||||
| Tst4AdcSensorMonitorTable | 1.3.6.1.4.1.1718.4.1.13.3 | NA | |||||||||||||||||||
table · not-accessible · current Analog-to-digital converter sensor monitor table. | |||||||||||||||||||||
| Rst4AdcSensorMonitorEntry | 1.3.6.1.4.1.1718.4.1.13.3.1 | NA | |||||||||||||||||||
row · not-accessible · current Objects to monitor for a particular analog-to-digital converter sensor. | |||||||||||||||||||||
| Cst4AdcSensorValue | 1.3.6.1.4.1.1718.4.1.13.3.1.1 | Integer32 (-1..255) | RO | ||||||||||||||||||
column · Integer32 (-1..255) · read-only · current The 8-bit value from the analog-to-digital converter sensor. | |||||||||||||||||||||
| Cst4AdcSensorStatus | 1.3.6.1.4.1.1718.4.1.13.3.1.2 | DeviceStatus | RO | ||||||||||||||||||
column · DeviceStatus · read-only · current The status of the analog-to-digital converter sensor. | |||||||||||||||||||||
| Tst4AdcSensorEventConfigTable | 1.3.6.1.4.1.1718.4.1.13.4 | NA | |||||||||||||||||||
table · not-accessible · current Analog-to-digital converter sensor event configuration table. | |||||||||||||||||||||
| Rst4AdcSensorEventConfigEntry | 1.3.6.1.4.1.1718.4.1.13.4.1 | NA | |||||||||||||||||||
row · not-accessible · current Event configuration objects for a particular analog-to-digital converter sensor. | |||||||||||||||||||||
| Cst4AdcSensorNotifications | 1.3.6.1.4.1.1718.4.1.13.4.1.1 | EventNotificationMethods | RW | ||||||||||||||||||
column · EventNotificationMethods · read-write · current The notification methods enabled for analog-to-digital converter sensor events. | |||||||||||||||||||||
| Cst4AdcSensorLowAlarm | 1.3.6.1.4.1.1718.4.1.13.4.1.2 | Integer32 (0..255) | RW | ||||||||||||||||||
column · Integer32 (0..255) · read-write · current The 8-bit value for the low alarm threshold of the analog-to-digital converter sensor. | |||||||||||||||||||||
| Cst4AdcSensorLowWarning | 1.3.6.1.4.1.1718.4.1.13.4.1.3 | Integer32 (0..255) | RW | ||||||||||||||||||
column · Integer32 (0..255) · read-write · current The 8-bit value for the low warning threshold of the analog-to-digital converter sensor. | |||||||||||||||||||||
| Cst4AdcSensorHighWarning | 1.3.6.1.4.1.1718.4.1.13.4.1.4 | Integer32 (0..255) | RW | ||||||||||||||||||
column · Integer32 (0..255) · read-write · current The 8-bit value for the high warning threshold of the analog-to-digital converter sensor. | |||||||||||||||||||||
| Cst4AdcSensorHighAlarm | 1.3.6.1.4.1.1718.4.1.13.4.1.5 | Integer32 (0..255) | RW | ||||||||||||||||||
column · Integer32 (0..255) · read-write · current The 8-bit value for the high alarm threshold of the analog-to-digital converter sensor. | |||||||||||||||||||||
| Nst4FanSensors | 1.3.6.1.4.1.1718.4.1.14 | ||||||||||||||||||||
| Nst4FanSensorCommonConfig | 1.3.6.1.4.1.1718.4.1.14.1 | ||||||||||||||||||||
| Sst4FanSensorHysteresis | 1.3.6.1.4.1.1718.4.1.14.1.1 | Integer32 (0..1200) | RW | ||||||||||||||||||
scalar · Integer32 (0..1200) · read-write · current The fan speed hysteresis of the sensor in rotations per minute.
| |||||||||||||||||||||
| Tst4FanSensorConfigTable | 1.3.6.1.4.1.1718.4.1.14.2 | NA | |||||||||||||||||||
table · not-accessible · current Fan sensor configuration table. | |||||||||||||||||||||
| Rst4FanSensorConfigEntry | 1.3.6.1.4.1.1718.4.1.14.2.1 | NA | |||||||||||||||||||
row · not-accessible · current Configuration objects for a particular fan sensor. | |||||||||||||||||||||
| Cst4FanSensorIndex | 1.3.6.1.4.1.1718.4.1.14.2.1.1 | Integer32 (0..4) | NA | ||||||||||||||||||
column · Integer32 (0..4) · not-accessible · current Fan sensor index. | |||||||||||||||||||||
| Cst4FanSensorID | 1.3.6.1.4.1.1718.4.1.14.2.1.2 | DisplayString (SIZE (2)) | RO | ||||||||||||||||||
column · DisplayString (SIZE (2)) · read-only · current The internal ID of the fan sensor. Format=AN. | |||||||||||||||||||||
| Cst4FanSensorName | 1.3.6.1.4.1.1718.4.1.14.2.1.3 | DisplayString (SIZE (0..32)) | RW | ||||||||||||||||||
column · DisplayString (SIZE (0..32)) · read-write · current The name of the fan sensor. | |||||||||||||||||||||
| Tst4FanSensorMonitorTable | 1.3.6.1.4.1.1718.4.1.14.3 | NA | |||||||||||||||||||
table · not-accessible · current Fan sensor monitor table. | |||||||||||||||||||||
| Rst4FanSensorMonitorEntry | 1.3.6.1.4.1.1718.4.1.14.3.1 | NA | |||||||||||||||||||
row · not-accessible · current Objects to monitor for a particular fan sensor. | |||||||||||||||||||||
| Cst4FanSensorValue | 1.3.6.1.4.1.1718.4.1.14.3.1.1 | Integer32 (-1..15300) | RO | ||||||||||||||||||
column · Integer32 (-1..15300) · read-only · current The measured fan speed of the sensor in rotations per minute.
| |||||||||||||||||||||
| Cst4FanSensorStatus | 1.3.6.1.4.1.1718.4.1.14.3.1.2 | DeviceStatus | RO | ||||||||||||||||||
column · DeviceStatus · read-only · current The status of the fan sensor. | |||||||||||||||||||||
| Tst4FanSensorEventConfigTable | 1.3.6.1.4.1.1718.4.1.14.4 | NA | |||||||||||||||||||
table · not-accessible · current Fan sensor event configuration table. | |||||||||||||||||||||
| Rst4FanSensorEventConfigEntry | 1.3.6.1.4.1.1718.4.1.14.4.1 | NA | |||||||||||||||||||
row · not-accessible · current Event configuration objects for a particular fan sensor. | |||||||||||||||||||||
| Cst4FanSensorNotifications | 1.3.6.1.4.1.1718.4.1.14.4.1.1 | EventNotificationMethods | RW | ||||||||||||||||||
column · EventNotificationMethods · read-write · current The notification methods enabled for fan sensor events. | |||||||||||||||||||||
| Cst4FanSensorLowAlarm | 1.3.6.1.4.1.1718.4.1.14.4.1.2 | Integer32 (0..15300) | RW | ||||||||||||||||||
column · Integer32 (0..15300) · read-write · current The low alarm threshold of the fan sensor in rotations per minute.
| |||||||||||||||||||||
| Cst4FanSensorLowWarning | 1.3.6.1.4.1.1718.4.1.14.4.1.3 | Integer32 (0..15300) | RW | ||||||||||||||||||
column · Integer32 (0..15300) · read-write · current The low warning threshold of the fan sensor in rotations per minute.
| |||||||||||||||||||||
| Cst4FanSensorHighWarning | 1.3.6.1.4.1.1718.4.1.14.4.1.4 | Integer32 (0..15300) | RW | ||||||||||||||||||
column · Integer32 (0..15300) · read-write · current The high warning threshold of the fan sensor in rotations per minute.
| |||||||||||||||||||||
| Cst4FanSensorHighAlarm | 1.3.6.1.4.1.1718.4.1.14.4.1.5 | Integer32 (0..15300) | RW | ||||||||||||||||||
column · Integer32 (0..15300) · read-write · current The high alarm threshold of the fan sensor in rotations per minute.
| |||||||||||||||||||||
| Nst4EventInformation | 1.3.6.1.4.1.1718.4.1.99 | ||||||||||||||||||||
| Sst4EventStatusText | 1.3.6.1.4.1.1718.4.1.99.1 | DisplayString (SIZE (0..20)) | RO | ||||||||||||||||||
scalar · DisplayString (SIZE (0..20)) · read-only · current The text representation of the enumerated integer value of the most-relevant status or state object included in a trap. The value of this object is set only when sent with a trap. A read of this object will return a NULL string. | |||||||||||||||||||||
| Sst4EventStatusCondition | 1.3.6.1.4.1.1718.4.1.99.2 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The condition of the enumerated integer value of the status object included in a trap. The value of this object is set only when sent with a trap. A read of this object will return zero.
| |||||||||||||||||||||
| Nst4Notifications | 1.3.6.1.4.1.1718.4.100 | ||||||||||||||||||||
| Nst4Events | 1.3.6.1.4.1.1718.4.100.0 | ||||||||||||||||||||
| !st4UnitStatusEvent | 1.3.6.1.4.1.1718.4.100.0.1 | ||||||||||||||||||||
notification · current Unit status event. | |||||||||||||||||||||
| !st4InputCordStatusEvent | 1.3.6.1.4.1.1718.4.100.0.2 | ||||||||||||||||||||
notification · current Input cord status event. | |||||||||||||||||||||
| !st4InputCordActivePowerEvent | 1.3.6.1.4.1.1718.4.100.0.3 | ||||||||||||||||||||
notification · current Input cord active power event. | |||||||||||||||||||||
| !st4InputCordApparentPowerEvent | 1.3.6.1.4.1.1718.4.100.0.4 | ||||||||||||||||||||
notification · current Input cord apparent power event. | |||||||||||||||||||||
| !st4InputCordPowerFactorEvent | 1.3.6.1.4.1.1718.4.100.0.5 | ||||||||||||||||||||
notification · current Input cord power factor event. | |||||||||||||||||||||
| !st4InputCordOutOfBalanceEvent | 1.3.6.1.4.1.1718.4.100.0.6 | ||||||||||||||||||||
notification · current Input cord out-of-balance event. | |||||||||||||||||||||
| !st4LineStatusEvent | 1.3.6.1.4.1.1718.4.100.0.7 | ||||||||||||||||||||
notification · current Line status event. | |||||||||||||||||||||
| !st4LineCurrentEvent | 1.3.6.1.4.1.1718.4.100.0.8 | ||||||||||||||||||||
notification · current Line current event. | |||||||||||||||||||||
| !st4PhaseStatusEvent | 1.3.6.1.4.1.1718.4.100.0.9 | ||||||||||||||||||||
notification · current Phase status event. | |||||||||||||||||||||
| !st4PhaseVoltageEvent | 1.3.6.1.4.1.1718.4.100.0.10 | ||||||||||||||||||||
notification · current Phase voltage event. | |||||||||||||||||||||
| !st4PhasePowerFactorEvent | 1.3.6.1.4.1.1718.4.100.0.11 | ||||||||||||||||||||
notification · current Phase voltage event. | |||||||||||||||||||||
| !st4OcpStatusEvent | 1.3.6.1.4.1.1718.4.100.0.12 | ||||||||||||||||||||
notification · current Over-current protector status event. | |||||||||||||||||||||
| !st4BranchStatusEvent | 1.3.6.1.4.1.1718.4.100.0.13 | ||||||||||||||||||||
notification · current Branch status event. | |||||||||||||||||||||
| !st4BranchCurrentEvent | 1.3.6.1.4.1.1718.4.100.0.14 | ||||||||||||||||||||
notification · current Branch current event. | |||||||||||||||||||||
| !st4OutletStatusEvent | 1.3.6.1.4.1.1718.4.100.0.15 | ||||||||||||||||||||
notification · current Outlet status event. | |||||||||||||||||||||
| !st4OutletStateChangeEvent | 1.3.6.1.4.1.1718.4.100.0.16 | ||||||||||||||||||||
notification · current Outlet state change event. | |||||||||||||||||||||
| !st4OutletCurrentEvent | 1.3.6.1.4.1.1718.4.100.0.17 | ||||||||||||||||||||
notification · current Outlet current event. | |||||||||||||||||||||
| !st4OutletActivePowerEvent | 1.3.6.1.4.1.1718.4.100.0.18 | ||||||||||||||||||||
notification · current Outlet active power event. | |||||||||||||||||||||
| !st4OutletPowerFactorEvent | 1.3.6.1.4.1.1718.4.100.0.19 | ||||||||||||||||||||
notification · current Outlet power factor event. | |||||||||||||||||||||
| !st4TempSensorEvent | 1.3.6.1.4.1.1718.4.100.0.20 | ||||||||||||||||||||
notification · current Temperature sensor event. | |||||||||||||||||||||
| !st4HumidSensorEvent | 1.3.6.1.4.1.1718.4.100.0.21 | ||||||||||||||||||||
notification · current Humidity sensor event. | |||||||||||||||||||||
| !st4WaterSensorStatusEvent | 1.3.6.1.4.1.1718.4.100.0.22 | ||||||||||||||||||||
notification · current Water sensor status event. | |||||||||||||||||||||
| !st4CcSensorStatusEvent | 1.3.6.1.4.1.1718.4.100.0.23 | ||||||||||||||||||||
notification · current Contact closure sensor status event. | |||||||||||||||||||||
| !st4AdcSensorEvent | 1.3.6.1.4.1.1718.4.100.0.24 | ||||||||||||||||||||
notification · current Analog-to-digital converter sensor event. | |||||||||||||||||||||
| !st4FanSensorEvent | 1.3.6.1.4.1.1718.4.100.0.25 | ||||||||||||||||||||
notification · current Fan sensor event. | |||||||||||||||||||||
| Nst4Conformance | 1.3.6.1.4.1.1718.4.200 | ||||||||||||||||||||
| Nst4Groups | 1.3.6.1.4.1.1718.4.200.1 | ||||||||||||||||||||
| Gst4SystemObjectsGroup | 1.3.6.1.4.1.1718.4.200.1.1 | ||||||||||||||||||||
group · current System objects group. | |||||||||||||||||||||
| Gst4UnitObjectsGroup | 1.3.6.1.4.1.1718.4.200.1.2 | ||||||||||||||||||||
group · current Unit objects group.
| |||||||||||||||||||||
| Gst4InputCordObjectsGroup | 1.3.6.1.4.1.1718.4.200.1.3 | ||||||||||||||||||||
group · current Input cord objects group.
| |||||||||||||||||||||
| Gst4LineObjectsGroup | 1.3.6.1.4.1.1718.4.200.1.4 | ||||||||||||||||||||
group · current Line objects group. | |||||||||||||||||||||
| Gst4PhaseObjectsGroup | 1.3.6.1.4.1.1718.4.200.1.5 | ||||||||||||||||||||
group · current Phase objects group.
| |||||||||||||||||||||
| Gst4OcpObjectsGroup | 1.3.6.1.4.1.1718.4.200.1.6 | ||||||||||||||||||||
group · current Over-current protector objects group. | |||||||||||||||||||||
| Gst4BranchObjectsGroup | 1.3.6.1.4.1.1718.4.200.1.7 | ||||||||||||||||||||
group · current Branch objects group.
| |||||||||||||||||||||
| Gst4OutletObjectsGroup | 1.3.6.1.4.1.1718.4.200.1.8 | ||||||||||||||||||||
group · current Outlet objects group.
| |||||||||||||||||||||
| Gst4TempSensorObjectsGroup | 1.3.6.1.4.1.1718.4.200.1.9 | ||||||||||||||||||||
group · current Temperature sensor objects group. | |||||||||||||||||||||
| Gst4HumidSensorObjectsGroup | 1.3.6.1.4.1.1718.4.200.1.10 | ||||||||||||||||||||
group · current Humidity sensor objects group. | |||||||||||||||||||||
| Gst4WaterSensorObjectsGroup | 1.3.6.1.4.1.1718.4.200.1.11 | ||||||||||||||||||||
group · current Water sensor objects group. | |||||||||||||||||||||
| Gst4CcSensorObjectsGroup | 1.3.6.1.4.1.1718.4.200.1.12 | ||||||||||||||||||||
group · current Contact closure sensor objects group. | |||||||||||||||||||||
| Gst4AdcSensorObjectsGroup | 1.3.6.1.4.1.1718.4.200.1.13 | ||||||||||||||||||||
group · current Analog-to-digital converter sensor objects group. | |||||||||||||||||||||
| Gst4FanSensorObjectsGroup | 1.3.6.1.4.1.1718.4.200.1.14 | ||||||||||||||||||||
group · current Fan sensor objects group. | |||||||||||||||||||||
| Gst4EventInfoObjectsGroup | 1.3.6.1.4.1.1718.4.200.1.99 | ||||||||||||||||||||
| Gst4EventNotificationsGroup | 1.3.6.1.4.1.1718.4.200.1.100 | ||||||||||||||||||||
group · current Event notifications group.
| |||||||||||||||||||||
| Nst4Compliances | 1.3.6.1.4.1.1718.4.200.2 | ||||||||||||||||||||
| Mst4ModuleCompliances | 1.3.6.1.4.1.1718.4.200.2.1 | ||||||||||||||||||||
compliance · current The requirements for conformance to the Sentry4-MIB.
| |||||||||||||||||||||
Textual conventions
DeviceStateINTEGERoff(2)on(1)unknown(0)On or off state of devices.
DeviceStatusINTEGERalarm(18)breakerTripped(12)conflict(23)disabled(1)fuseBlown(13)highAlarm(17)highWarning(16)lost(8)lowAlarm(14)lowWarning(15)noComm(10)normal(0)notFound(7)nvmFail(21)overLimit(20)profileError(22)purged(2)pwrError(11)readError(9)reading(5)settle(6)underLimit(19)Status returned by devices.
EventNotificationMethodsBitsemail(1)snmpTrap(0)Bits to enable event notification methods.
Traps / Notifications
- st4AdcSensorEvent
1.3.6.1.4.1.1718.4.100.0.24 - st4BranchCurrentEvent
1.3.6.1.4.1.1718.4.100.0.14 - st4BranchStatusEvent
1.3.6.1.4.1.1718.4.100.0.13 - st4CcSensorStatusEvent
1.3.6.1.4.1.1718.4.100.0.23 - st4FanSensorEvent
1.3.6.1.4.1.1718.4.100.0.25 - st4HumidSensorEvent
1.3.6.1.4.1.1718.4.100.0.21 - st4InputCordActivePowerEvent
1.3.6.1.4.1.1718.4.100.0.3 - st4InputCordApparentPowerEvent
1.3.6.1.4.1.1718.4.100.0.4 - st4InputCordOutOfBalanceEvent
1.3.6.1.4.1.1718.4.100.0.6 - st4InputCordPowerFactorEvent
1.3.6.1.4.1.1718.4.100.0.5 - st4InputCordStatusEvent
1.3.6.1.4.1.1718.4.100.0.2 - st4LineCurrentEvent
1.3.6.1.4.1.1718.4.100.0.8 - st4LineStatusEvent
1.3.6.1.4.1.1718.4.100.0.7 - st4OcpStatusEvent
1.3.6.1.4.1.1718.4.100.0.12 - st4OutletActivePowerEvent
1.3.6.1.4.1.1718.4.100.0.18 - st4OutletCurrentEvent
1.3.6.1.4.1.1718.4.100.0.17 - st4OutletPowerFactorEvent
1.3.6.1.4.1.1718.4.100.0.19 - st4OutletStateChangeEvent
1.3.6.1.4.1.1718.4.100.0.16 - st4OutletStatusEvent
1.3.6.1.4.1.1718.4.100.0.15 - st4PhasePowerFactorEvent
1.3.6.1.4.1.1718.4.100.0.11 - st4PhaseStatusEvent
1.3.6.1.4.1.1718.4.100.0.9 - st4PhaseVoltageEvent
1.3.6.1.4.1.1718.4.100.0.10 - st4TempSensorEvent
1.3.6.1.4.1.1718.4.100.0.20 - st4UnitStatusEvent
1.3.6.1.4.1.1718.4.100.0.1 - st4WaterSensorStatusEvent
1.3.6.1.4.1.1718.4.100.0.22
Groups and compliance
- st4AdcSensorObjectsGroup
- st4BranchObjectsGroup
- st4CcSensorObjectsGroup
- st4EventInfoObjectsGroup
- st4EventNotificationsGroup
- st4FanSensorObjectsGroup
- st4HumidSensorObjectsGroup
- st4InputCordObjectsGroup
- st4LineObjectsGroup
- st4ModuleCompliances
- st4OcpObjectsGroup
- st4OutletObjectsGroup
- st4PhaseObjectsGroup
- st4SystemObjectsGroup
- st4TempSensorObjectsGroup
- st4UnitObjectsGroup
- st4WaterSensorObjectsGroup