Sentry3-MIB
Server Technology Inc.This is the MIB module for the third generation of the Sentry product family. This includes the Sentry Remote Power Manager (RPM), Sentry Power Distribution Unit (PDU), Sentry Environmental Monitor (EM), Sentry Smart and Switched Cabinet Distribution Unit (CDU), and Sentry Switched -48 VDC.
snmptranslate -m Sentry3-MIB -Tpsnmpwalk -v2c -c <community> -m Sentry3-MIB <host> 1.3.6.1.4.1.1718.3Imports
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
|---|---|
| SNMPv2-SMI | Bits, Integer32, IpAddress, MODULE-IDENTITY, MibIdentifier, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, TimeTicks, Unsigned32, enterprises, iso |
| SNMPv2-TC | DisplayString, PhysAddress, TEXTUAL-CONVENTION |
OID tree
| Name | OID | Type | Access | Status | Example | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| NserverTech | 1.3.6.1.4.1.1718 | ||||||||||||||||||||
| Isentry3 | 1.3.6.1.4.1.1718.3 | ||||||||||||||||||||
identity This is the MIB module for the third generation of the Sentry product family. This includes the Sentry Remote Power Manager (RPM), Sentry Power Distribution Unit (PDU), Sentry Environmental Monitor (EM), Sentry Smart and Switched Cabinet Distribution Unit (CDU), and Sentry Switched -48 VDC. | |||||||||||||||||||||
| NsystemGroup | 1.3.6.1.4.1.1718.3.1 | ||||||||||||||||||||
| SsystemVersion | 1.3.6.1.4.1.1718.3.1.1 | DisplayString (SIZE (0..80)) | RO | Sentry Switched CDU Version 7.1a | |||||||||||||||||
scalar · DisplayString (SIZE (0..80)) · read-only · current The firmware version of the system. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SsystemNICSerialNumber | 1.3.6.1.4.1.1718.3.1.2 | DisplayString (SIZE (0..8)) | RO | 8025492 | |||||||||||||||||
scalar · DisplayString (SIZE (0..8)) · read-only · current The serial number of the network interface card in the system. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SsystemLocation | 1.3.6.1.4.1.1718.3.1.3 | DisplayString (SIZE (0..32)) | RW | | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-write · current The location of the system. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SsystemTowerCount | 1.3.6.1.4.1.1718.3.1.4 | INTEGER (0..4) | RO | 2 | |||||||||||||||||
scalar · INTEGER (0..4) · read-only · current The number of towers in the system. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SsystemEnvMonCount | 1.3.6.1.4.1.1718.3.1.5 | INTEGER (0..4) | RO | 1 | |||||||||||||||||
scalar · INTEGER (0..4) · read-only · current The number of environmental monitors in the system. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SsystemTotalPower | 1.3.6.1.4.1.1718.3.1.6 | INTEGER (-1..150000) | RO | 279 | |||||||||||||||||
scalar · INTEGER (-1..150000) · read-only · current The total power consumption of all of the input feeds in the system. A non-negative value indicates the total power consumption in Watts. A negative value indicates that the total power consumption was not available.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SsystemArea | 1.3.6.1.4.1.1718.3.1.7 | INTEGER (0..1000) | RW | 0 | |||||||||||||||||
scalar · INTEGER (0..1000) · read-write · current The area that the footprint of the system occupies. A non-zero non-negative value indicates the area in tenths of area units as selected by the systemAreaUnit object. A zero or negative value indicates that the area was not available.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SsystemWattsPerAreaUnit | 1.3.6.1.4.1.1718.3.1.8 | INTEGER (-1..1500000) | RO | -1 | |||||||||||||||||
scalar · INTEGER (-1..1500000) · read-only · current The system Watts per area unit. A non-negative value indicates the power consumption per area unit as selected by the systemAreaUnit object. A negative value indicates that the power consumption per area unit was not available.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SsystemAreaUnit | 1.3.6.1.4.1.1718.3.1.9 | INTEGER | RW | squareMeter(0) | |||||||||||||||||
scalar · INTEGER · read-write · current The unit of area for the systemArea and systemWattsPerAreaUnit objects. If the agent does not support this object, then the unit of area is a square foot.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SsystemPowerFactor | 1.3.6.1.4.1.1718.3.1.10 | INTEGER (50..100) | RW | 100 | |||||||||||||||||
scalar · INTEGER (50..100) · read-write · current The power factor used in power calculations performed by the system.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SsystemFeatures | 1.3.6.1.4.1.1718.3.1.11 | Bits | RO | 00 | |||||||||||||||||
scalar · Bits · read-only · current The key-activated features enabled in the system.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SsystemFeatureKey | 1.3.6.1.4.1.1718.3.1.12 | DisplayString (SIZE (0..19)) | RW | | |||||||||||||||||
scalar · DisplayString (SIZE (0..19)) · read-write · current A valid feature key written to this object will enable a feature in the system. A valid feature key is in the form xxxx-xxxx-xxxx-xxxx. A read of this object returns an empty string. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SsystemOutletSeqInterval | 1.3.6.1.4.1.1718.3.1.13 | INTEGER (0..15) | RW | ||||||||||||||||||
scalar · INTEGER (0..15) · read-write · current The power-on sequencing interval for all outlets.
| |||||||||||||||||||||
| SsystemOutletRebootDelay | 1.3.6.1.4.1.1718.3.1.14 | INTEGER (5..600) | RW | ||||||||||||||||||
scalar · INTEGER (5..600) · read-write · current The reboot delay for all outlets.
| |||||||||||||||||||||
| SsystemConfigModifiedCount | 1.3.6.1.4.1.1718.3.1.15 | INTEGER (0..2147483647) | RO | 19 | |||||||||||||||||
scalar · INTEGER (0..2147483647) · read-only · current The total number of times the system configuration has changed. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NsystemTables | 1.3.6.1.4.1.1718.3.2 | ||||||||||||||||||||
| TtowerTable | 1.3.6.1.4.1.1718.3.2.1 | NA | |||||||||||||||||||
table · not-accessible · current A table of towers. | |||||||||||||||||||||
| RtowerEntry | 1.3.6.1.4.1.1718.3.2.1.1 | NA | |||||||||||||||||||
| CtowerIndex | 1.3.6.1.4.1.1718.3.2.1.1.1 | INTEGER (0..4) | NA | ||||||||||||||||||
column · INTEGER (0..4) · not-accessible · current Index for the tower table. | |||||||||||||||||||||
| CtowerID | 1.3.6.1.4.1.1718.3.2.1.1.2 | DisplayString (SIZE (1)) | RO | A | |||||||||||||||||
column · DisplayString (SIZE (1)) · read-only · current The ID of the tower. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtowerName | 1.3.6.1.4.1.1718.3.2.1.1.3 | DisplayString (SIZE (0..24)) | RW | TowerA | |||||||||||||||||
column · DisplayString (SIZE (0..24)) · read-write · current The name of the tower. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtowerStatus | 1.3.6.1.4.1.1718.3.2.1.1.4 | INTEGER | RO | normal(0) | |||||||||||||||||
column · INTEGER · read-only · current The operational status of the tower.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtowerInfeedCount | 1.3.6.1.4.1.1718.3.2.1.1.5 | INTEGER (0..4) | RO | 4 | |||||||||||||||||
column · INTEGER (0..4) · read-only · current The number of input feeds on the tower. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtowerProductSN | 1.3.6.1.4.1.1718.3.2.1.1.6 | DisplayString (SIZE (0..16)) | RO | ADLH0001862 | |||||||||||||||||
column · DisplayString (SIZE (0..16)) · read-only · current The product serial number of the tower. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtowerModelNumber | 1.3.6.1.4.1.1718.3.2.1.1.7 | DisplayString (SIZE (0..24)) | RO | CW-24V2C458C1 | |||||||||||||||||
column · DisplayString (SIZE (0..24)) · read-only · current The model number of the tower. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtowerCapabilities | 1.3.6.1.4.1.1718.3.2.1.1.8 | Bits | RO | P | |||||||||||||||||
column · Bits · read-only · current The capabilities of the tower.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtowerVACapacity | 1.3.6.1.4.1.1718.3.2.1.1.9 | INTEGER (-1..50000) | RO | ||||||||||||||||||
column · INTEGER (-1..50000) · read-only · current The total apparent power capacity of the tower circuit. A non-negative value indicates the maximum total apparent power in Volt-Amps. A negative value indicates that the total apparent power capacity was not available.
| |||||||||||||||||||||
| CtowerVACapacityUsed | 1.3.6.1.4.1.1718.3.2.1.1.10 | INTEGER (-1..1500) | RO | ||||||||||||||||||
column · INTEGER (-1..1500) · read-only · current The used percentage of the tower circuit total apparent power capacity (towerApparentPower / towerVACapacity x 100). A non-negative value indicates the percentage of capacity used in tenths. A negative value indicates that the percentage of capacity used was not available.
| |||||||||||||||||||||
| CtowerActivePower | 1.3.6.1.4.1.1718.3.2.1.1.11 | INTEGER (-1..50000) | RO | ||||||||||||||||||
column · INTEGER (-1..50000) · read-only · current The total active power consumption of the tower circuit. A non-negative value indicates the total active power consumption in Watts. A negative value indicates that the total active power consumption was not available.
| |||||||||||||||||||||
| CtowerApparentPower | 1.3.6.1.4.1.1718.3.2.1.1.12 | INTEGER (-1..50000) | RO | ||||||||||||||||||
column · INTEGER (-1..50000) · read-only · current The total apparent power consumption of the tower circuit. A non-negative value indicates the total apparent power consumption in Volt-Amps. A negative value indicates that the total apparent power consumption was not available.
| |||||||||||||||||||||
| CtowerPowerFactor | 1.3.6.1.4.1.1718.3.2.1.1.13 | INTEGER (-1..100) | RO | ||||||||||||||||||
column · INTEGER (-1..100) · read-only · current The overall power factor of the tower circuit. A non- negative value indicates the overall power factor in hundredths. A negative value indicates that the overall power factor was not able to be measured.
| |||||||||||||||||||||
| CtowerEnergy | 1.3.6.1.4.1.1718.3.2.1.1.14 | INTEGER (-1..2147483647) | RO | ||||||||||||||||||
column · INTEGER (-1..2147483647) · read-only · current The total energy consumption of the tower circuit. A non- negative value indicates the total energy consumption in Kilowatt-Hours. A negative value indicates that the total energy consumption was not available.
| |||||||||||||||||||||
| CtowerLineFrequency | 1.3.6.1.4.1.1718.3.2.1.1.15 | INTEGER (-1..60) | RO | ||||||||||||||||||
column · INTEGER (-1..60) · read-only · current The frequency of the input feed line voltage. A non- negative value indicates the frequency in Hertz. A negative value indicates that the frequency was not available.
| |||||||||||||||||||||
| TinfeedTable | 1.3.6.1.4.1.1718.3.2.2 | NA | |||||||||||||||||||
table · not-accessible · current A table of input feeds. | |||||||||||||||||||||
| RinfeedEntry | 1.3.6.1.4.1.1718.3.2.2.1 | NA | |||||||||||||||||||
| CinfeedIndex | 1.3.6.1.4.1.1718.3.2.2.1.1 | INTEGER (0..4) | NA | ||||||||||||||||||
column · INTEGER (0..4) · not-accessible · current Index for the input feed table. | |||||||||||||||||||||
| CinfeedID | 1.3.6.1.4.1.1718.3.2.2.1.2 | DisplayString (SIZE (2)) | RO | AA | |||||||||||||||||
column · DisplayString (SIZE (2)) · read-only · current The ID of the input feed. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinfeedName | 1.3.6.1.4.1.1718.3.2.2.1.3 | DisplayString (SIZE (0..24)) | RW | TowerA_InfeedA | |||||||||||||||||
column · DisplayString (SIZE (0..24)) · read-write · current The name of the input feed. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinfeedCapabilities | 1.3.6.1.4.1.1718.3.2.2.1.4 | Bits | RO | c0:00 | |||||||||||||||||
column · Bits · read-only · current The capabilities of the input feed.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinfeedStatus | 1.3.6.1.4.1.1718.3.2.2.1.5 | INTEGER | RO | on(1) | |||||||||||||||||
column · INTEGER · read-only · current The status of the input feed line. If the infeedCapabilities 'onSense' bit is TRUE, then all of the states are supported and indicate the sensed state of the input feed. If the infeedCapabilities 'onSense' bit is FALSE, then only the 'on' and 'noComm' states are supported, and 'on' indicates a derived state, not a sensed state.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinfeedLoadStatus | 1.3.6.1.4.1.1718.3.2.2.1.6 | INTEGER | RO | normal(0) | |||||||||||||||||
column · INTEGER · read-only · current The status of the load measured on the input feed line. If the infeedCapabilities 'loadSense' bit is TRUE, then all of the states are supported. If the infeedCapabilities 'loadSense' bit is FALSE, then only the 'normal' and 'noComm' states are supported.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinfeedLoadValue | 1.3.6.1.4.1.1718.3.2.2.1.7 | INTEGER (-1..60000) | RO | 362 | |||||||||||||||||
column · INTEGER (-1..60000) · read-only · current The load measured on the input feed line. A non-negative value indicates the measured load in hundredths of Amps. A negative value indicates that a load value was not able to be measured.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinfeedLoadHighThresh | 1.3.6.1.4.1.1718.3.2.2.1.8 | INTEGER (0..600) | RW | 24 | |||||||||||||||||
column · INTEGER (0..600) · read-write · current The load high threshold value of the input feed line in Amps.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinfeedOutletCount | 1.3.6.1.4.1.1718.3.2.2.1.9 | INTEGER (0..64) | RO | 0 | |||||||||||||||||
column · INTEGER (0..64) · read-only · current The number of controlled and/or monitored outlets on the input feed. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinfeedCapacity | 1.3.6.1.4.1.1718.3.2.2.1.10 | INTEGER (-1..600) | RO | 30 | |||||||||||||||||
column · INTEGER (-1..600) · read-only · current The load capacity of the input feed line. A non-negative value indicates the maximum load in Amps. A negative value indicates that the capacity was not available.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinfeedVoltage | 1.3.6.1.4.1.1718.3.2.2.1.11 | INTEGER (-1..4800) | RO | 2093 | |||||||||||||||||
column · INTEGER (-1..4800) · read-only · current The line-to-line voltage of the input feed. A non-negative value indicates the voltage in tenths of Volts. A negative value indicates that the voltage was not available.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinfeedPower | 1.3.6.1.4.1.1718.3.2.2.1.12 | INTEGER (-1..25000) | RO | 147 | |||||||||||||||||
column · INTEGER (-1..25000) · read-only · current The active power consumption of the input feed phase. A non- negative value indicates the active power consumption in Watts. A negative value indicates that the active power consumption was not available.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinfeedApparentPower | 1.3.6.1.4.1.1718.3.2.2.1.13 | INTEGER (-1..25000) | RO | ||||||||||||||||||
column · INTEGER (-1..25000) · read-only · current The apparent power consumption of the input feed phase. A non-negative value indicates the apparent power consumption in Volt-Amps. A negative value indicates that the apparent power consumption was not available.
| |||||||||||||||||||||
| CinfeedPowerFactor | 1.3.6.1.4.1.1718.3.2.2.1.14 | INTEGER (-1..100) | RO | ||||||||||||||||||
column · INTEGER (-1..100) · read-only · current The power factor of the input feed phase. A non-negative value indicates the power factor in hundredths. A negative value indicates that the power factor was not able to be measured.
| |||||||||||||||||||||
| CinfeedCrestFactor | 1.3.6.1.4.1.1718.3.2.2.1.15 | INTEGER (-1..1000) | RO | ||||||||||||||||||
column · INTEGER (-1..1000) · read-only · current The crest factor for the load of the input feed phase. A non-negative value indicates the crest factor in tenths. A negative value indicates that the crest factor was not able to be measured.
| |||||||||||||||||||||
| CinfeedEnergy | 1.3.6.1.4.1.1718.3.2.2.1.16 | INTEGER (-1..2147483647) | RO | ||||||||||||||||||
column · INTEGER (-1..2147483647) · read-only · current The energy consumption of the input feed phase. A non- negative value indicates the energy consumption in tenths of Kilowatt-Hours. A negative value indicates that the energy consumption was not available.
| |||||||||||||||||||||
| CinfeedReactance | 1.3.6.1.4.1.1718.3.2.2.1.17 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current The characterization of the phase relation between the voltage and current of the input feed phase.
| |||||||||||||||||||||
| CinfeedPhaseVoltage | 1.3.6.1.4.1.1718.3.2.2.1.18 | INTEGER (-1..2640) | RO | ||||||||||||||||||
column · INTEGER (-1..2640) · read-only · current The voltage measured for the input feed phase. A non- negative value indicates the voltage in tenths of Volts. A negative value indicates that the voltage was not available.
| |||||||||||||||||||||
| CinfeedPhaseCurrent | 1.3.6.1.4.1.1718.3.2.2.1.19 | INTEGER (-1..25500) | RO | ||||||||||||||||||
column · INTEGER (-1..25500) · read-only · current The current measured for the input feed phase. A non- negative value indicates the measured load in hundredths of Amps. A negative value indicates that a load value was not able to be measured.
| |||||||||||||||||||||
| CinfeedCapacityUsed | 1.3.6.1.4.1.1718.3.2.2.1.20 | INTEGER (-1..1500) | RO | ||||||||||||||||||
column · INTEGER (-1..1500) · read-only · current The used percentage of the input feed line load capacity (infeedLoadValue / infeedCapacity x 100). A non-negative value indicates the percentage of capacity used in tenths. A negative value indicates that the percentage of capacity used was not available.
| |||||||||||||||||||||
| CinfeedLineID | 1.3.6.1.4.1.1718.3.2.2.1.21 | DisplayString (SIZE (0..4)) | RO | ||||||||||||||||||
column · DisplayString (SIZE (0..4)) · read-only · current The ID of the input feed line. | |||||||||||||||||||||
| CinfeedLineToLineID | 1.3.6.1.4.1.1718.3.2.2.1.22 | DisplayString (SIZE (0..7)) | RO | ||||||||||||||||||
column · DisplayString (SIZE (0..7)) · read-only · current The line-to-line ID of the input feed. | |||||||||||||||||||||
| CinfeedPhaseID | 1.3.6.1.4.1.1718.3.2.2.1.23 | DisplayString (SIZE (0..6)) | RO | ||||||||||||||||||
column · DisplayString (SIZE (0..6)) · read-only · current The ID of the input feed phase. | |||||||||||||||||||||
| CinfeedVACapacity | 1.3.6.1.4.1.1718.3.2.2.1.24 | INTEGER (-1..25000) | RO | ||||||||||||||||||
column · INTEGER (-1..25000) · read-only · current The apparent power capacity of the input feed circuit. A non-negative value indicates the maximum apparent power in Volt-Amps. A negative value indicates that the apparent power capacity was not available.
| |||||||||||||||||||||
| CinfeedVACapacityUsed | 1.3.6.1.4.1.1718.3.2.2.1.25 | INTEGER (-1..1500) | RO | ||||||||||||||||||
column · INTEGER (-1..1500) · read-only · current The used percentage of the input feed circuit apparent power capacity (infeedApparentPower / infeedVACapacity x 100). A non-negative value indicates the percentage of capacity used in tenths. A negative value indicates that the percentage of capacity used was not available.
| |||||||||||||||||||||
| ToutletTable | 1.3.6.1.4.1.1718.3.2.3 | NA | |||||||||||||||||||
table · not-accessible · current A table of outlets. | |||||||||||||||||||||
| RoutletEntry | 1.3.6.1.4.1.1718.3.2.3.1 | NA | |||||||||||||||||||
row · not-accessible · current Row definition for the outlet table.
| |||||||||||||||||||||
| CoutletIndex | 1.3.6.1.4.1.1718.3.2.3.1.1 | INTEGER (0..64) | NA | ||||||||||||||||||
column · INTEGER (0..64) · not-accessible · current Index for the outlet table. | |||||||||||||||||||||
| CoutletID | 1.3.6.1.4.1.1718.3.2.3.1.2 | DisplayString (SIZE (2..4)) | RO | AA1 | |||||||||||||||||
column · DisplayString (SIZE (2..4)) · read-only · current The ID of the outlet. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletName | 1.3.6.1.4.1.1718.3.2.3.1.3 | DisplayString (SIZE (0..24)) | RW | Outlet AA1 | |||||||||||||||||
column · DisplayString (SIZE (0..24)) · read-write · current The name of the outlet. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletCapabilities | 1.3.6.1.4.1.1718.3.2.3.1.4 | Bits | RO | ||||||||||||||||||
column · Bits · read-only · current The capabilities of the outlet.
| |||||||||||||||||||||
| CoutletStatus | 1.3.6.1.4.1.1718.3.2.3.1.5 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current The status of the outlet. If the outletCapabilities 'onSense' bit is TRUE, then the state indicates the sensed state of the outlet, not a derived state, and 'offError' and 'onError' are supported to indicate a mismatch between the control and sensed state. If the outletCapabilities 'fusedBranch' bit is TRUE, then the outlet is on a fused branch circuit that can detect the fuse state, and 'offFuse' and 'onFuse' are supported to indicate a fuse error.
| |||||||||||||||||||||
| CoutletLoadStatus | 1.3.6.1.4.1.1718.3.2.3.1.6 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current The status of the load measured on the outlet. If the outletCapabilities 'loadSense' bit is TRUE, then all of the states are supported. If the outletCapabilities 'loadSense' bit is FALSE, then only the 'normal' and 'noComm' states are supported.
| |||||||||||||||||||||
| CoutletLoadValue | 1.3.6.1.4.1.1718.3.2.3.1.7 | INTEGER (-1..25500) | RO | 0 | |||||||||||||||||
column · INTEGER (-1..25500) · read-only · current The load measured on the outlet. A non-negative value indicates the measured load in hundredths of Amps. A negative value indicates that a load value was not able to be measured.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletLoadLowThresh | 1.3.6.1.4.1.1718.3.2.3.1.8 | INTEGER (0..255) | RW | ||||||||||||||||||
column · INTEGER (0..255) · read-write · current The load low threshold value of the outlet in Amps.
| |||||||||||||||||||||
| CoutletLoadHighThresh | 1.3.6.1.4.1.1718.3.2.3.1.9 | INTEGER (0..255) | RW | 12 | |||||||||||||||||
column · INTEGER (0..255) · read-write · current The load high threshold value of the outlet in Amps.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletControlState | 1.3.6.1.4.1.1718.3.2.3.1.10 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current The control state of the outlet. The supported states are dependent upon the outletCapabilities 'powerControl' and 'shutdown' bits, as well as the supported features of the firmware version.
| |||||||||||||||||||||
| CoutletControlAction | 1.3.6.1.4.1.1718.3.2.3.1.11 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current An action to change the control state of the outlet. If the outletCapabilities 'powerControl' bit is TRUE, then the 'on', 'off', and 'reboot' actions can be used to change the control state of the outlet. If the outletCapabilities 'powerControl' bit is FALSE, then the actions have no effect.
| |||||||||||||||||||||
| CoutletCapacity | 1.3.6.1.4.1.1718.3.2.3.1.12 | INTEGER (-1..255) | RO | ||||||||||||||||||
column · INTEGER (-1..255) · read-only · current The load capacity of the outlet. A non-negative value indicates the maximum load in Amps. A negative value indicates that the capacity was not available.
| |||||||||||||||||||||
| CoutletVoltage | 1.3.6.1.4.1.1718.3.2.3.1.13 | INTEGER (-1..2640) | RO | ||||||||||||||||||
column · INTEGER (-1..2640) · read-only · current The voltage of the outlet. A non-negative value indicates the voltage in tenths of Volts. A negative value indicates that the voltage was not available.
| |||||||||||||||||||||
| CoutletPower | 1.3.6.1.4.1.1718.3.2.3.1.14 | INTEGER (-1..10000) | RO | ||||||||||||||||||
column · INTEGER (-1..10000) · read-only · current The active power consumption of the device plugged into the outlet. A non-negative value indicates the active power consumption in Watts. A negative value indicates that the active power consumption was not available.
| |||||||||||||||||||||
| CoutletApparentPower | 1.3.6.1.4.1.1718.3.2.3.1.15 | INTEGER (-1..10000) | RO | ||||||||||||||||||
column · INTEGER (-1..10000) · read-only · current The apparent power consumption of the device plugged into the outlet. A non-negative value indicates the apparent power consumption in Volt-Amps. A negative value indicates that the apparent power consumption was not available.
| |||||||||||||||||||||
| CoutletPowerFactor | 1.3.6.1.4.1.1718.3.2.3.1.16 | INTEGER (-1..100) | RO | ||||||||||||||||||
column · INTEGER (-1..100) · read-only · current The power factor of the device plugged into the outlet. A non-negative value indicates the power factor in hundredths. A negative value indicates that the power factor was not able to be measured.
| |||||||||||||||||||||
| CoutletCrestFactor | 1.3.6.1.4.1.1718.3.2.3.1.17 | INTEGER (-1..1000) | RO | ||||||||||||||||||
column · INTEGER (-1..1000) · read-only · current The crest factor for the load of the device plugged into the outlet. A non-negative value indicates the crest factor in tenths. A negative value indicates that the crest factor was not able to be measured.
| |||||||||||||||||||||
| CoutletEnergy | 1.3.6.1.4.1.1718.3.2.3.1.18 | INTEGER (-1..2147483647) | RO | ||||||||||||||||||
column · INTEGER (-1..2147483647) · read-only · current The energy consumption of the device plugged into the outlet. A non-negative value indicates the energy consumption in Watt-Hours. A negative value indicates that the energy consumption was not available.
| |||||||||||||||||||||
| CoutletWakeupState | 1.3.6.1.4.1.1718.3.2.3.1.19 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current The wakeup state of the outlet.
| |||||||||||||||||||||
| CoutletPostOnDelay | 1.3.6.1.4.1.1718.3.2.3.1.20 | INTEGER (0..900) | RW | ||||||||||||||||||
column · INTEGER (0..900) · read-write · current The post-on delay of the outlet.
| |||||||||||||||||||||
| TenvMonTable | 1.3.6.1.4.1.1718.3.2.4 | NA | |||||||||||||||||||
table · not-accessible · current A table of environmental monitors. | |||||||||||||||||||||
| RenvMonEntry | 1.3.6.1.4.1.1718.3.2.4.1 | NA | |||||||||||||||||||
| CenvMonIndex | 1.3.6.1.4.1.1718.3.2.4.1.1 | INTEGER (0..4) | NA | ||||||||||||||||||
column · INTEGER (0..4) · not-accessible · current Index for the environmental monitor table. | |||||||||||||||||||||
| CenvMonID | 1.3.6.1.4.1.1718.3.2.4.1.2 | DisplayString (SIZE (1)) | RO | A | |||||||||||||||||
column · DisplayString (SIZE (1)) · read-only · current The ID of the environmental monitor. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CenvMonName | 1.3.6.1.4.1.1718.3.2.4.1.3 | DisplayString (SIZE (0..24)) | RW | Environmental_Monitor_A | |||||||||||||||||
column · DisplayString (SIZE (0..24)) · read-write · current The name of the environmental monitor. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CenvMonStatus | 1.3.6.1.4.1.1718.3.2.4.1.4 | INTEGER | RO | normal(0) | |||||||||||||||||
column · INTEGER · read-only · current The operational status of the environmental monitor.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CenvMonWaterSensorName | 1.3.6.1.4.1.1718.3.2.4.1.5 | DisplayString (SIZE (0..24)) | RW | ||||||||||||||||||
column · DisplayString (SIZE (0..24)) · read-write · current The name of the water sensor. | |||||||||||||||||||||
| CenvMonWaterSensorStatus | 1.3.6.1.4.1.1718.3.2.4.1.6 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current The status of the water sensor.
| |||||||||||||||||||||
| CenvMonADCName | 1.3.6.1.4.1.1718.3.2.4.1.7 | DisplayString (SIZE (0..24)) | RW | ||||||||||||||||||
column · DisplayString (SIZE (0..24)) · read-write · current The name of the analog-to-digital converter. | |||||||||||||||||||||
| CenvMonADCStatus | 1.3.6.1.4.1.1718.3.2.4.1.8 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current The status of the analog-to-digital converter.
| |||||||||||||||||||||
| CenvMonADCCount | 1.3.6.1.4.1.1718.3.2.4.1.9 | INTEGER (-1..255) | RO | ||||||||||||||||||
column · INTEGER (-1..255) · read-only · current The 8-bit count value from the analog-to-digital converter. A non-negative value indicates the digital value retrieved from the ADC. A negative value indicates that a digital value was not able to be retrieved. | |||||||||||||||||||||
| CenvMonADCLowThresh | 1.3.6.1.4.1.1718.3.2.4.1.10 | INTEGER (0..255) | RW | ||||||||||||||||||
column · INTEGER (0..255) · read-write · current The 8-bit count low threshold value of the analog-to-digital converter. | |||||||||||||||||||||
| CenvMonADCHighThresh | 1.3.6.1.4.1.1718.3.2.4.1.11 | INTEGER (0..255) | RW | ||||||||||||||||||
column · INTEGER (0..255) · read-write · current The 8-bit count high threshold value of the analog-to-digital converter. | |||||||||||||||||||||
| CenvMonTempHumidSensorCount | 1.3.6.1.4.1.1718.3.2.4.1.12 | INTEGER (0..2) | RO | 2 | |||||||||||||||||
column · INTEGER (0..2) · read-only · current The number of temperature/humidity sensors on the environmental monitor. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CenvMonContactClosureCount | 1.3.6.1.4.1.1718.3.2.4.1.13 | INTEGER (0..4) | RO | 0 | |||||||||||||||||
column · INTEGER (0..4) · read-only · current The number of contact closures on the environmental monitor. Example values from LibreNMS test devices
| |||||||||||||||||||||
| TtempHumidSensorTable | 1.3.6.1.4.1.1718.3.2.5 | NA | |||||||||||||||||||
table · not-accessible · current A table of temperature/humidity sensors. | |||||||||||||||||||||
| RtempHumidSensorEntry | 1.3.6.1.4.1.1718.3.2.5.1 | NA | |||||||||||||||||||
row · not-accessible · current Row definition for the temperature/humidity sensor table. | |||||||||||||||||||||
| CtempHumidSensorIndex | 1.3.6.1.4.1.1718.3.2.5.1.1 | INTEGER (0..2) | NA | ||||||||||||||||||
column · INTEGER (0..2) · not-accessible · current Index for the temperature/humidity sensor table. | |||||||||||||||||||||
| CtempHumidSensorID | 1.3.6.1.4.1.1718.3.2.5.1.2 | DisplayString (SIZE (2)) | RO | A1 | |||||||||||||||||
| CtempHumidSensorName | 1.3.6.1.4.1.1718.3.2.5.1.3 | DisplayString (SIZE (0..24)) | RW | Temp_Humid_Sensor_A1 | |||||||||||||||||
| CtempHumidSensorStatus | 1.3.6.1.4.1.1718.3.2.5.1.4 | INTEGER | RO | found(0) | |||||||||||||||||
| CtempHumidSensorTempStatus | 1.3.6.1.4.1.1718.3.2.5.1.5 | INTEGER | RO | normal(0) | |||||||||||||||||
| CtempHumidSensorTempValue | 1.3.6.1.4.1.1718.3.2.5.1.6 | INTEGER (-1..2540) | RO | 680 | |||||||||||||||||
column · INTEGER (-1..2540) · read-only · current The temperature measured by the sensor. A non-negative value indicates the measured temperature in tenths of degrees, using the scale selected by tempHumidSensorTempScale. If the agent does not support the tempHumidSensorTempScale object, then the temperature scale used is Celsius. A negative value indicates that a temperature value was not able to be measured.
| |||||||||||||||||||||
| CtempHumidSensorTempLowThresh | 1.3.6.1.4.1.1718.3.2.5.1.7 | INTEGER (0..254) | RW | 41 | |||||||||||||||||
column · INTEGER (0..254) · read-write · current The temperature low threshold value of the sensor in degrees, using the scale selected by tempHumidSensorTempScale. If the agent does not support the tempHumidSensorTempScale object, then the temperature scale used is Celsius.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtempHumidSensorTempHighThresh | 1.3.6.1.4.1.1718.3.2.5.1.8 | INTEGER (0..254) | RW | 113 | |||||||||||||||||
column · INTEGER (0..254) · read-write · current The temperature high threshold value of the sensor in degrees, using the scale selected by tempHumidSensorTempScale. If the agent does not support the tempHumidSensorTempScale object, then the temperature scale used is Celsius.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtempHumidSensorHumidStatus | 1.3.6.1.4.1.1718.3.2.5.1.9 | INTEGER | RO | normal(0) | |||||||||||||||||
| CtempHumidSensorHumidValue | 1.3.6.1.4.1.1718.3.2.5.1.10 | INTEGER (-1..100) | RO | 52 | |||||||||||||||||
column · INTEGER (-1..100) · read-only · current The humidity measured by the sensor. A non-negative value indicates the measured humidity in percentage relative humidity. A negative value indicates that a humidity value was not able to be measured.
| |||||||||||||||||||||
| CtempHumidSensorHumidLowThresh | 1.3.6.1.4.1.1718.3.2.5.1.11 | INTEGER (0..100) | RW | 10 | |||||||||||||||||
column · INTEGER (0..100) · read-write · current The humidity low threshold value of the sensor in percentage relative humidity.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtempHumidSensorHumidHighThresh | 1.3.6.1.4.1.1718.3.2.5.1.12 | INTEGER (0..100) | RW | 90 | |||||||||||||||||
column · INTEGER (0..100) · read-write · current The humidity low threshold value of the sensor in percentage relative humidity.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtempHumidSensorTempScale | 1.3.6.1.4.1.1718.3.2.5.1.13 | INTEGER | RW | fahrenheit(1) | |||||||||||||||||
column · INTEGER · read-write · current The scale used for temperature values. This is a global setting for all temperature values in the system. If the agent does not support this object, then the temperature scale used is Celsius.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtempHumidSensorTempRecDelta | 1.3.6.1.4.1.1718.3.2.5.1.14 | INTEGER (0..54) | RW | 2 | |||||||||||||||||
column · INTEGER (0..54) · read-write · current The temperature recovery delta (hysteresis) value of the sensor in degrees, using the scale selected by tempHumidSensorTempScale.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtempHumidSensorHumidRecDelta | 1.3.6.1.4.1.1718.3.2.5.1.15 | INTEGER (0..20) | RW | 2 | |||||||||||||||||
column · INTEGER (0..20) · read-write · current The humidity recovery delta (hysteresis) value of the sensor in percentage relative humidity.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| TcontactClosureTable | 1.3.6.1.4.1.1718.3.2.6 | NA | |||||||||||||||||||
table · not-accessible · current A table of contact closures. | |||||||||||||||||||||
| RcontactClosureEntry | 1.3.6.1.4.1.1718.3.2.6.1 | NA | |||||||||||||||||||
row · not-accessible · current Row definition for the contact closure table. | |||||||||||||||||||||
| CcontactClosureIndex | 1.3.6.1.4.1.1718.3.2.6.1.1 | INTEGER (0..4) | NA | ||||||||||||||||||
column · INTEGER (0..4) · not-accessible · current Index for the contact closure table. | |||||||||||||||||||||
| CcontactClosureID | 1.3.6.1.4.1.1718.3.2.6.1.2 | DisplayString (SIZE (2)) | RO | ||||||||||||||||||
column · DisplayString (SIZE (2)) · read-only · current The ID of the contact closure. | |||||||||||||||||||||
| CcontactClosureName | 1.3.6.1.4.1.1718.3.2.6.1.3 | DisplayString (SIZE (0..24)) | RW | ||||||||||||||||||
column · DisplayString (SIZE (0..24)) · read-write · current The name of the contact closure. | |||||||||||||||||||||
| CcontactClosureStatus | 1.3.6.1.4.1.1718.3.2.6.1.4 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current The status of the contact closure.
| |||||||||||||||||||||
| TbranchTable | 1.3.6.1.4.1.1718.3.2.7 | NA | |||||||||||||||||||
table · not-accessible · current A table of branches. | |||||||||||||||||||||
| RbranchEntry | 1.3.6.1.4.1.1718.3.2.7.1 | NA | |||||||||||||||||||
row · not-accessible · current Row definition for the branch table.
| |||||||||||||||||||||
| CbranchIndex | 1.3.6.1.4.1.1718.3.2.7.1.1 | INTEGER (0..4) | NA | ||||||||||||||||||
column · INTEGER (0..4) · not-accessible · current Index for the branch table. | |||||||||||||||||||||
| CbranchID | 1.3.6.1.4.1.1718.3.2.7.1.2 | DisplayString (SIZE (3)) | RO | ||||||||||||||||||
column · DisplayString (SIZE (3)) · read-only · current The ID of the branch. | |||||||||||||||||||||
| CbranchName | 1.3.6.1.4.1.1718.3.2.7.1.3 | DisplayString (SIZE (0..24)) | RW | ||||||||||||||||||
column · DisplayString (SIZE (0..24)) · read-write · current The name of the branch. | |||||||||||||||||||||
| CbranchCapabilities | 1.3.6.1.4.1.1718.3.2.7.1.4 | Bits | RO | ||||||||||||||||||
column · Bits · read-only · current The capabilities of the branch.
| |||||||||||||||||||||
| CbranchStatus | 1.3.6.1.4.1.1718.3.2.7.1.5 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current The status of the branch.
| |||||||||||||||||||||
| CbranchLoadStatus | 1.3.6.1.4.1.1718.3.2.7.1.6 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current The status of the load measured on the branch.
| |||||||||||||||||||||
| CbranchLoadValue | 1.3.6.1.4.1.1718.3.2.7.1.7 | INTEGER (-1..4000) | RO | ||||||||||||||||||
column · INTEGER (-1..4000) · read-only · current The load measured on the branch. A non-negative value indicates the measured load in hundredths of Amps. A negative value indicates that a load value was not able to be measured.
| |||||||||||||||||||||
| CbranchLoadHighThresh | 1.3.6.1.4.1.1718.3.2.7.1.8 | INTEGER (0..40) | RW | ||||||||||||||||||
column · INTEGER (0..40) · read-write · current The load high threshold value of the branch in Amps.
| |||||||||||||||||||||
| CbranchCapacity | 1.3.6.1.4.1.1718.3.2.7.1.9 | INTEGER (-1..40) | RO | ||||||||||||||||||
column · INTEGER (-1..40) · read-only · current The load capacity of the branch. A non-negative value indicates the maximum load in Amps. A negative value indicates that the capacity was not available.
| |||||||||||||||||||||
| NeventInformationGroup | 1.3.6.1.4.1.1718.3.99 | ||||||||||||||||||||
| SeventStatusText | 1.3.6.1.4.1.1718.3.99.1 | DisplayString (SIZE (0..20)) | RO | | |||||||||||||||||
scalar · DisplayString (SIZE (0..20)) · read-only · current The text representation of the enumerated integer value of the status object included in a trap. The value of this object is set only when sent with a trap. A get of this object will return a NULL string. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SeventStatusCondition | 1.3.6.1.4.1.1718.3.99.2 | INTEGER | RO | nonError(0) | |||||||||||||||||
scalar · INTEGER · read-only · current The condition of the enumerated integer value of the status object included in a trap. The value of this object is set only when sent with a trap. A get of this object will return zero.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| Nsentry3Traps | 1.3.6.1.4.1.1718.3.100 | ||||||||||||||||||||
| Nevents | 1.3.6.1.4.1.1718.3.100.0 | ||||||||||||||||||||
| !towerStatusEvent | 1.3.6.1.4.1.1718.3.100.0.1 | ||||||||||||||||||||
notification · current Tower status event. If enabled, this trap is sent when the
towerStatus indicates an error state ('noComm', 'fanFail',
'overTemp', 'nvmFail', or 'outOfBalance'). This trap is
repeated periodically while the towerStatus remains in an
error state. If the towerStatus returns to a non-error
state ('normal'), this trap is sent once more with the
non-error towerStatus, and then stops being repeated.
While the towerStatus indicates a 'noComm' error state, all
status and load traps are suppressed for input feeds and
outlets on the tower. | |||||||||||||||||||||
| !infeedStatusEvent | 1.3.6.1.4.1.1718.3.100.0.2 | ||||||||||||||||||||
notification · current Input feed status event. If enabled, this trap is sent when
the infeedStatus indicates an error state ('offError',
'onError', 'noComm', 'offFuse', or 'onFuse'). This trap is
repeated periodically while the infeedStatus remains in an
error state. If the infeedStatus returns to a non-error
state ('off' or 'on'), this trap is sent once more with the
non-error infeedStatus, and then stops being repeated.
While the infeedStatus indicates an error state, load
traps are suppressed for the input feed, and, if the
infeedCapabilities 'failSafe' bit is FALSE, all status and
load traps are suppressed for outlets on the input feed. | |||||||||||||||||||||
| !infeedLoadEvent | 1.3.6.1.4.1.1718.3.100.0.3 | ||||||||||||||||||||
notification · current Input feed load event. If enabled, this trap is sent when
the infeedLoadStatus indicates an error state ('loadLow',
'loadHigh', 'overLoad', 'readError', or 'noComm'). This
trap is repeated periodically while the infeedLoadStatus
remains in an error state. If the infeedLoadStatus returns
to a non-error state ('normal' or 'notOn'), this trap is
sent once more with the non-error infeedLoadStatus, and then
stops being repeated. | |||||||||||||||||||||
| !outletStatusEvent | 1.3.6.1.4.1.1718.3.100.0.4 | ||||||||||||||||||||
notification · current Outlet status event. If enabled, this trap is sent when the
outletStatus indicates an error state ('offError', 'onError',
'noComm', 'offFuse', or 'onFuse'). This trap is repeated
periodically while the outletStatus remains in an error state.
If the outletStatus returns to a non-error state ('off' or
'on'), this trap is sent once more with the non-error
outletStatus, and then stops being repeated.
While the outletStatus indicates an error state, load traps
are suppressed for the outlet. | |||||||||||||||||||||
| !outletLoadEvent | 1.3.6.1.4.1.1718.3.100.0.5 | ||||||||||||||||||||
notification · current Outlet load event. If enabled, this trap is sent when the
outletLoadStatus indicates an error state ('loadLow',
'loadHigh', 'overLoad', 'readError', or 'noComm'). This
trap is repeated periodically while the outletLoadStatus
remains in an error state. If the outletLoadStatus returns
to a non-error state ('normal' or 'notOn'), this trap is
sent once more with the non-error outletLoadStatus, and then
stops being repeated. | |||||||||||||||||||||
| !outletChangeEvent | 1.3.6.1.4.1.1718.3.100.0.6 | ||||||||||||||||||||
notification · current Outlet on/off change event. If enabled, this trap is sent
when the outletStatus changes from any 'on' state ('on',
'onWait', 'onError', or 'onFuse') to any 'off' state ('off',
'offWait', 'offError', or 'offFuse'), and vice-versa. | |||||||||||||||||||||
| !envMonStatusEvent | 1.3.6.1.4.1.1718.3.100.0.7 | ||||||||||||||||||||
notification · current Environmental monitor status event. If enabled, this trap
is sent when the envMonStatus indicates an error state
('noComm'). This trap is repeated periodically while the
envMonStatus remains in an error state. If the envMonStatus
returns to a non-error state ('normal'), this trap is sent
once more with the non-error envMonStatus, and then stops
being repeated.
While the envMonStatus indicates an error state, all status
traps are suppressed for the water sensor, ADC, temperature/
humidity sensors, and contact closures on the environmental
monitor. | |||||||||||||||||||||
| !envMonWaterSensorEvent | 1.3.6.1.4.1.1718.3.100.0.8 | ||||||||||||||||||||
notification · current Environmental monitor water sensor event. If enabled, this
trap is sent when the envMonWaterSensorStatus indicates an
error state ('alarm'). This trap is repeated periodically
while the envMonWaterSensorStatus remains in an error state.
If the envMonWaterSensorStatus returns to a non-error state
('normal'), this trap is sent once more with the non-error
envMonWaterSensorStatus, and then stops being repeated. | |||||||||||||||||||||
| !envMonADCEvent | 1.3.6.1.4.1.1718.3.100.0.9 | ||||||||||||||||||||
notification · current Environmental monitor analog-to-digital converter event.
If enabled, this trap is sent when the envMonADCStatus
indicates an error state ('countLow' or 'countHigh'). This
trap is repeated periodically while the envMonADCStatus
remains in an error state. If the envMonADCStatus returns
to a non-error state ('normal'), this trap is sent once more
with the non-error envMonADCStatus, and then stops being
repeated. | |||||||||||||||||||||
| !tempHumidSensorStatusEvent | 1.3.6.1.4.1.1718.3.100.0.10 | ||||||||||||||||||||
notification · current Temperature/humidity sensor status event. If enabled, this
trap is sent when the tempHumidSensorStatus indicates an
error state ('lost'). This trap is repeated periodically
while the tempHumidSensorStatus remains in an error state.
If the tempHumidSensorStatus returns to a non-error state
('found'), this trap is sent once more with the non-error
tempHumidSensorStatus, and then stops being repeated.
While the tempHumidSensorStatus indicates an error state, all
temperature and humidity status traps are suppressed for the
temperature/humidity sensor. | |||||||||||||||||||||
| !tempHumidSensorTempEvent | 1.3.6.1.4.1.1718.3.100.0.11 | ||||||||||||||||||||
notification · current Temperature/humidity sensor temperature event. If enabled,
this trap is sent when the tempHumidSensorTempStatus
indicates an error state ('tempLow' or 'tempHigh').
This trap is repeated periodically while the
tempHumidSensorTempStatus remains in an error state. If
the tempHumidSensorTempStatus returns to a non-error state
('normal'), this trap is sent once more with the non-error
tempHumidSensorTempStatus, and then stops being repeated. | |||||||||||||||||||||
| !tempHumidSensorHumidEvent | 1.3.6.1.4.1.1718.3.100.0.12 | ||||||||||||||||||||
notification · current Temperature/humidity sensor humidity event. If enabled,
this trap is sent when the tempHumidSensorHumidStatus
indicates an error state ('humidLow' or 'humidHigh').
This trap is repeated periodically while the
tempHumidSensorHumidStatus remains in an error state. If
the tempHumidSensorHumidStatus returns to a non-error state
('normal'), this trap is sent once more with the non-error
tempHumidSensorHumidStatus, and then stops being repeated. | |||||||||||||||||||||
| !contactClosureEvent | 1.3.6.1.4.1.1718.3.100.0.13 | ||||||||||||||||||||
notification · current Contact closure event. If enabled, this trap is sent when
the contactClosureStatus indicates an error state ('alarm').
This trap is repeated periodically while the
contactClosureStatus remains in an error state. If the
contactClosureStatus returns to a non-error state ('normal'),
this trap is sent once more with the non-error
contactClosureStatus, and then stops being repeated. | |||||||||||||||||||||
| !branchStatusEvent | 1.3.6.1.4.1.1718.3.100.0.14 | ||||||||||||||||||||
notification · current Branch status event. If enabled, this trap is sent when
the branchStatus indicates an error state ('offError',
'onError', 'noComm', 'offFuse', or 'onFuse'). This trap
is repeated periodically while the branchStatus remains in
an error state. If the branchStatus returns to a non-error
state ('off' or 'on'), this trap is sent once more with the
non-error branchStatus, and then stops being repeated.
While the branchStatus indicates an error state, load traps
are suppressed for the branch. | |||||||||||||||||||||
| !branchLoadEvent | 1.3.6.1.4.1.1718.3.100.0.15 | ||||||||||||||||||||
notification · current Branch load event. If enabled, this trap is sent when
the branchLoadStatus indicates an error state ('loadLow',
'loadHigh', 'overLoad', 'readError', or 'noComm'). This
trap is repeated periodically while the branchLoadStatus
remains in an error state. If the branchLoadStatus returns
to a non-error state ('normal' or 'notOn'), this trap is
sent once more with the non-error branchLoadStatus, and then
stops being repeated. | |||||||||||||||||||||
Traps / Notifications
- branchLoadEvent
1.3.6.1.4.1.1718.3.100.0.15 - branchStatusEvent
1.3.6.1.4.1.1718.3.100.0.14 - contactClosureEvent
1.3.6.1.4.1.1718.3.100.0.13 - envMonADCEvent
1.3.6.1.4.1.1718.3.100.0.9 - envMonStatusEvent
1.3.6.1.4.1.1718.3.100.0.7 - envMonWaterSensorEvent
1.3.6.1.4.1.1718.3.100.0.8 - infeedLoadEvent
1.3.6.1.4.1.1718.3.100.0.3 - infeedStatusEvent
1.3.6.1.4.1.1718.3.100.0.2 - outletChangeEvent
1.3.6.1.4.1.1718.3.100.0.6 - outletLoadEvent
1.3.6.1.4.1.1718.3.100.0.5 - outletStatusEvent
1.3.6.1.4.1.1718.3.100.0.4 - tempHumidSensorHumidEvent
1.3.6.1.4.1.1718.3.100.0.12 - tempHumidSensorStatusEvent
1.3.6.1.4.1.1718.3.100.0.10 - tempHumidSensorTempEvent
1.3.6.1.4.1.1718.3.100.0.11 - towerStatusEvent
1.3.6.1.4.1.1718.3.100.0.1