SCHLEIFENBAUER-DATABUS-MIB
Schleifenbauer Products BVThis MIB describes the SNMP functions of network enabled databus devices. Copyright (c) 2021 by Schleifenbauer Holding BV
snmptranslate -m SCHLEIFENBAUER-DATABUS-MIB -Tpsnmpwalk -v2c -c <community> -m SCHLEIFENBAUER-DATABUS-MIB <host> 1.3.6.1.4.1.31034.12.1Imports
| SCHLEIFENBAUER-SMI | schleifenbauerMgmt |
|---|---|
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP, OBJECT-GROUP |
| SNMPv2-SMI | Bits, Integer32, IpAddress, MODULE-IDENTITY, MibIdentifier, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, TimeTicks, Unsigned32, iso |
| SNMPv2-TC | DisplayString, PhysAddress, TEXTUAL-CONVENTION |
OID tree
| Name | OID | Type | Access | Status | Example | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| IschleifenbauerDatabusMIB | 1.3.6.1.4.1.31034.12.1 | ||||||||||||||||||||
identity This MIB describes the SNMP functions of network enabled databus devices. Copyright (c) 2021 by Schleifenbauer Holding BV | |||||||||||||||||||||
| NsdbMIBNotifications | 1.3.6.1.4.1.31034.12.1.0 | ||||||||||||||||||||
| !sdbDevSsDeviceStatusCodeChanged | 1.3.6.1.4.1.31034.12.1.0.1 | ||||||||||||||||||||
notification · current Device status code changed.
OBJECTS {
sdbDevSsDeviceStatusCode
} | |||||||||||||||||||||
| !sdbDevSsTemperatureAlertDetected | 1.3.6.1.4.1.31034.12.1.0.2 | ||||||||||||||||||||
notification · current Temperature alert detected.
Internal temperature alert:
OBJECTS {
sdbDevSsTemperatureAlert,
sdbDevMsIntTemperature,
sdbDevMsIntTemperaturePeak
}
External analog temperature alert:
OBJECTS {
sdbDevSsTemperatureAlert,
sdbDevMsExtTemperature,
sdbDevMsExtTemperaturePeak
}
External digital temperature alert:
OBJECTS {
sdbDevSsTemperatureAlert,
sdbDevSnsValue
} | |||||||||||||||||||||
| !sdbDevSsInputCurrentAlertDetected | 1.3.6.1.4.1.31034.12.1.0.3 | ||||||||||||||||||||
notification · current Input current alert detected.
OBJECTS {
sdbDevSsInputCurrentAlert,
sdbDevInActualCurrent
} | |||||||||||||||||||||
| !sdbDevSsOutletCurrentAlertDetected | 1.3.6.1.4.1.31034.12.1.0.4 | ||||||||||||||||||||
notification · current Outlet current alert detected.
OBJECTS {
sdbDevSsOutletCurrentAlert,
sdbDevOutMtActualCurrent
} | |||||||||||||||||||||
| !sdbDevSsInputVoltageAlertDetected | 1.3.6.1.4.1.31034.12.1.0.5 | ||||||||||||||||||||
notification · current Input voltage alert detected.
OBJECTS {
sdbDevSsInputVoltageAlert,
sdbDevInActualVoltage
} | |||||||||||||||||||||
| !sdbDevSsOutletCurrentDropAlertDetected | 1.3.6.1.4.1.31034.12.1.0.6 | ||||||||||||||||||||
notification · current Outlet current drop alert detected.
OBJECTS {
sdbDevSsOutletCurrentDropAlert,
sdbDevOutMtActualCurrent
} | |||||||||||||||||||||
| !sdbDevSsInputCurrentDropAlertDetected | 1.3.6.1.4.1.31034.12.1.0.7 | ||||||||||||||||||||
notification · current Input current drop alert detected.
OBJECTS {
sdbDevSsInputCurrentDropAlert,
sdbDevInActualCurrent
} | |||||||||||||||||||||
| !sdbDevSsSensorChangeAlertDetected | 1.3.6.1.4.1.31034.12.1.0.8 | ||||||||||||||||||||
notification · current Sensor channel change alert detected.
OBJECTS {
sdbDevSsSensorChangeAlert
} | |||||||||||||||||||||
| !sdbMgmtStsRingStateChanged | 1.3.6.1.4.1.31034.12.1.0.9 | ||||||||||||||||||||
notification · current Ring state changed.
Ring state changded to open:
OBJECTS {
sdbMgmtStsRingState,
sdbMgmtStsRingBreachIndex
}
Ring state changded to closed:
OBJECTS {
sdbMgmtStsRingState
} | |||||||||||||||||||||
| !sdbDevSsOutletVoltageDropAlertDetected | 1.3.6.1.4.1.31034.12.1.0.10 | ||||||||||||||||||||
notification · current Outlet voltage drop alert detected.
OBJECTS {
sdbDevSsOutletVoltageDropAlert,
sdbDevOutMtActualVoltage
} | |||||||||||||||||||||
| !sdbDevSsBranchCurrentAlertDetected | 1.3.6.1.4.1.31034.12.1.0.11 | ||||||||||||||||||||
notification · current Branch current alert detected.
OBJECTS {
sdbDevSsBranchCurrentAlert,
sdbDevBranchActualCurrent
} | |||||||||||||||||||||
| !sdbDevSsBranchVoltageAlertDetected | 1.3.6.1.4.1.31034.12.1.0.12 | ||||||||||||||||||||
notification · current Branch current alert detected.
OBJECTS {
sdbDevSsBranchVoltageAlert,
sdbDevBranchActualVoltage
} | |||||||||||||||||||||
| !sdbDevSsNeutralCurrentAlertDetected | 1.3.6.1.4.1.31034.12.1.0.13 | ||||||||||||||||||||
notification · current Input current alert detected.
OBJECTS {
sdbDevSsNeutralCurrentAlert,
sdbDevTotalsNeutralCurrent
} | |||||||||||||||||||||
| !sdbDevSsResidualCurrentAlertDetected | 1.3.6.1.4.1.31034.12.1.0.14 | ||||||||||||||||||||
notification · current Residual current alert detected.
OBJECTS {
sdbDevSsResidualCurrentAlert,
sdbDevMsResidualCurrent,
sdbDevMsResidualPeak
} | |||||||||||||||||||||
| !sdbDevSsHardwareAlertDetected | 1.3.6.1.4.1.31034.12.1.0.15 | ||||||||||||||||||||
notification · current Hardware alert detected.
OBJECTS {
sdbDevSsHardwareAlert
} | |||||||||||||||||||||
| NsdbMIBObjects | 1.3.6.1.4.1.31034.12.1.1 | ||||||||||||||||||||
| NsdbMgmt | 1.3.6.1.4.1.31034.12.1.1.1 | ||||||||||||||||||||
| NsdbMgmtStatus | 1.3.6.1.4.1.31034.12.1.1.1.1 | ||||||||||||||||||||
| SsdbMgmtStsDevices | 1.3.6.1.4.1.31034.12.1.1.1.1.1 | Integer32 (1..512) | RO | 1 | |||||||||||||||||
scalar · Integer32 (1..512) · read-only · current The number of devices on the databus. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SsdbMgmtStsAddressableDevices | 1.3.6.1.4.1.31034.12.1.1.1.1.2 | Integer32 (1..255) | RO | ||||||||||||||||||
scalar · Integer32 (1..255) · read-only · current The number of devices on the databus addressable by snmp. | |||||||||||||||||||||
| SsdbMgmtStsNewDevices | 1.3.6.1.4.1.31034.12.1.1.1.1.3 | Integer32 (1..255) | RO | 0 | |||||||||||||||||
scalar · Integer32 (1..255) · read-only · current The number of new devices on the databus. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SsdbMgmtStsDuplicateDevices | 1.3.6.1.4.1.31034.12.1.1.1.1.4 | Integer32 (1..255) | RO | 0 | |||||||||||||||||
scalar · Integer32 (1..255) · read-only · current The number of duplicate devices on the databus. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SsdbMgmtStsRingState | 1.3.6.1.4.1.31034.12.1.1.1.1.5 | INTEGER | RO | closed(1) | |||||||||||||||||
scalar · INTEGER · read-only · current If the device is in a bridge-like mode, this will indicate the actual state of the databus.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SsdbMgmtStsRingBreachIndex | 1.3.6.1.4.1.31034.12.1.1.1.1.6 | Integer32 (0..65535) | RO | ||||||||||||||||||
scalar · Integer32 (0..65535) · read-only · current Indicates the breach index if the current state of the data bus is open. If the data bus is closed this has no meaning. | |||||||||||||||||||||
| NsdbMgmtControl | 1.3.6.1.4.1.31034.12.1.1.1.2 | ||||||||||||||||||||
| SsdbMgmtCtrlScan | 1.3.6.1.4.1.31034.12.1.1.1.2.1 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current Perform a bus scan. To verify if scanning is completed the value of this object can be read. During the bus scan the value remains 1. When the bus scan completed the value will be 0.
| |||||||||||||||||||||
| SsdbMgmtCtrlRenumberAllFromN | 1.3.6.1.4.1.31034.12.1.1.1.2.2 | Integer32 (0..65535) | RW | ||||||||||||||||||
scalar · Integer32 (0..65535) · read-write · current Renumber all devices on the databus. If set to 0 all units will be set to 0. If set to another value, all units will be numbered in sequence starting from the value set. | |||||||||||||||||||||
| SsdbMgmtCtrlRenumberZeros | 1.3.6.1.4.1.31034.12.1.1.1.2.3 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current Renumber all devices on the databus having address 0. Renumbering will be done in sequence. The sequence starts with the highest address found on the databus.
| |||||||||||||||||||||
| TsdbMgmtCtrlDevicesTable | 1.3.6.1.4.1.31034.12.1.1.1.2.4 | NA | |||||||||||||||||||
table · not-accessible · current A table containing information of devices connected to the databus. The number of entries is given by the value of sdbMgmtStsDevices. | |||||||||||||||||||||
| RsdbMgmtCtrlDevicesEntry | 1.3.6.1.4.1.31034.12.1.1.1.2.4.1 | NA | |||||||||||||||||||
row · not-accessible · current Information entry containing objects of a particular databus device.
| |||||||||||||||||||||
| CsdbMgmtCtrlDevIndex | 1.3.6.1.4.1.31034.12.1.1.1.2.4.1.1 | Integer32 (1..255) | NA | ||||||||||||||||||
column · Integer32 (1..255) · not-accessible · current A unique value for each device. Its value ranges between 1 and the value of sdbMgmtStsDevices with a maximum of 255. The value for each device will remain constant until the next scan is performed. | |||||||||||||||||||||
| CsdbMgmtCtrlDevUnitAddress | 1.3.6.1.4.1.31034.12.1.1.1.2.4.1.2 | Integer32 (0..65535) | RW | 210 | |||||||||||||||||
column · Integer32 (0..65535) · read-write · current User defined address. This will be used for addressing the device on the databus. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CsdbMgmtCtrlDevHardwareAddress | 1.3.6.1.4.1.31034.12.1.1.1.2.4.1.3 | DisplayString (SIZE (17)) | RO | ||||||||||||||||||
column · DisplayString (SIZE (17)) · read-only · current Hardware serial number. This cannot be changed. It can be used as backup unit address. format as 3 unsigned ints separated by dashes: int - int - int | |||||||||||||||||||||
| CsdbMgmtCtrlDevIsNew | 1.3.6.1.4.1.31034.12.1.1.1.2.4.1.4 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current Indication if the device is new on the databus.
| |||||||||||||||||||||
| CsdbMgmtCtrlDevIsDuplicate | 1.3.6.1.4.1.31034.12.1.1.1.2.4.1.5 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current Indication if the device is conflicting with another device on the databus.
| |||||||||||||||||||||
| NsdbDevice | 1.3.6.1.4.1.31034.12.1.1.2 | ||||||||||||||||||||
| NsdbDevIdentification | 1.3.6.1.4.1.31034.12.1.1.2.1 | ||||||||||||||||||||
| TsdbDevIdTable | 1.3.6.1.4.1.31034.12.1.1.2.1.1 | NA | |||||||||||||||||||
table · not-accessible · current A table containing identification information of devices connected to the databus. The number of entries is given by the value of sdbMgmtStsAddressableDevices. | |||||||||||||||||||||
| RsdbDevIdEntry | 1.3.6.1.4.1.31034.12.1.1.2.1.1.1 | NA | |||||||||||||||||||
row · not-accessible · current Information entry containing information objects of a particular databus device.
| |||||||||||||||||||||
| CsdbDevIdSPDMVersion | 1.3.6.1.4.1.31034.12.1.1.2.1.1.1.1 | Integer32 (0..9999) | RO | ||||||||||||||||||
column · Integer32 (0..9999) · read-only · current Data model version. | |||||||||||||||||||||
| CsdbDevIdFirmwareVersion | 1.3.6.1.4.1.31034.12.1.1.2.1.1.1.2 | Integer32 (0..9999) | RO | 250 | |||||||||||||||||
column · Integer32 (0..9999) · read-only · current The firmware revision number. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CsdbDevIdBuildNumber | 1.3.6.1.4.1.31034.12.1.1.2.1.1.1.3 | DisplayString (SIZE (0..12)) | RO | 180821PL1736 | |||||||||||||||||
column · DisplayString (SIZE (0..12)) · read-only · current Date and time the firmware was built. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CsdbDevIdSalesOrderNumber | 1.3.6.1.4.1.31034.12.1.1.2.1.1.1.4 | DisplayString (SIZE (0..16)) | RO | 2017-35126 | |||||||||||||||||
column · DisplayString (SIZE (0..16)) · read-only · current SP sales order number. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CsdbDevIdProductId | 1.3.6.1.4.1.31034.12.1.1.2.1.1.1.5 | DisplayString (SIZE (0..16)) | RO | SSDCHIN1307-002 | |||||||||||||||||
column · DisplayString (SIZE (0..16)) · read-only · current SP product id. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CsdbDevIdSerialNumber | 1.3.6.1.4.1.31034.12.1.1.2.1.1.1.6 | DisplayString (SIZE (0..16)) | RO | SVNL00056319 | |||||||||||||||||
column · DisplayString (SIZE (0..16)) · read-only · current SP serial number. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CsdbDevIdHardwareAddress | 1.3.6.1.4.1.31034.12.1.1.2.1.1.1.7 | DisplayString (SIZE (17)) | RO | ||||||||||||||||||
column · DisplayString (SIZE (17)) · read-only · current Hardware serial number. This can not be changed. It can be used as backup unit address. Format as 3 unsigned ints separated by dashes (-) e.g. 12345-54321-00000 | |||||||||||||||||||||
| CsdbDevIdMacAddress | 1.3.6.1.4.1.31034.12.1.1.2.1.1.1.8 | DisplayString (SIZE (17)) | RO | ||||||||||||||||||
column · DisplayString (SIZE (17)) · read-only · current The MAC address. This can not be changed. It represents an 802 MAC address as if it were transmitted least significant bit first. Format as six groups of 2 hexadecimal digits separated by colons (:) e.g. D0:22:12:B0:00:00 | |||||||||||||||||||||
| CsdbDevIdUnitAddress | 1.3.6.1.4.1.31034.12.1.1.2.1.1.1.9 | Integer32 (0..65535) | RW | ||||||||||||||||||
column · Integer32 (0..65535) · read-write · current User defined address. This will be used for addressing the device on the databus. | |||||||||||||||||||||
| CsdbDevIdName | 1.3.6.1.4.1.31034.12.1.1.2.1.1.1.10 | DisplayString (SIZE (0..16)) | RW | schleiftest | |||||||||||||||||
column · DisplayString (SIZE (0..16)) · read-write · current User configurable device name or identifier. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CsdbDevIdLocation | 1.3.6.1.4.1.31034.12.1.1.2.1.1.1.11 | DisplayString (SIZE (0..16)) | RW | s22dak | |||||||||||||||||
column · DisplayString (SIZE (0..16)) · read-write · current User configurable device location identifier. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CsdbDevIdVanityTag | 1.3.6.1.4.1.31034.12.1.1.2.1.1.1.12 | DisplayString (SIZE (0..20)) | RW | Smartdc | |||||||||||||||||
column · DisplayString (SIZE (0..20)) · read-write · current Characters to be displayed as vanity text in display. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CsdbDevIdIndex | 1.3.6.1.4.1.31034.12.1.1.2.1.1.1.13 | Integer32 (1..65535) | NA | ||||||||||||||||||
column · Integer32 (1..65535) · not-accessible · current A unique value for each device. Its value represents the unit address of the device and is used to address individual devices in the tree. The value for each device will remain constant until the next scan is performed. | |||||||||||||||||||||
| CsdbDevIdDeviceType | 1.3.6.1.4.1.31034.12.1.1.2.1.1.1.14 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current A unique value for each device group. Its value represents the device type of the device. Refer to manual for more information.
| |||||||||||||||||||||
| CsdbDevIdLocateUnit | 1.3.6.1.4.1.31034.12.1.1.2.1.1.1.15 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current The LCD-backlight flashes in a heartbeat rhythm to locate the unit.
| |||||||||||||||||||||
| CsdbDevIdConfigType | 1.3.6.1.4.1.31034.12.1.1.2.1.1.1.16 | Integer32 (0..256) | RO | ||||||||||||||||||
column · Integer32 (0..256) · read-only · current Wiring configuration type used. | |||||||||||||||||||||
| NsdbDevConfiguration | 1.3.6.1.4.1.31034.12.1.1.2.2 | ||||||||||||||||||||
| TsdbDevCfTable | 1.3.6.1.4.1.31034.12.1.1.2.2.1 | NA | |||||||||||||||||||
table · not-accessible · current A table containing configuration information of devices connected to the databus. The number of entries is given by the value of sdbMgmtStsAddressableDevices. | |||||||||||||||||||||
| RsdbDevCfEntry | 1.3.6.1.4.1.31034.12.1.1.2.2.1.1 | NA | |||||||||||||||||||
row · not-accessible · current Configuration entry containing configuration objects of a particular databus device.
| |||||||||||||||||||||
| CsdbDevCfPhases | 1.3.6.1.4.1.31034.12.1.1.2.2.1.1.1 | Integer32 (0 | 1 | 3) | RO | ||||||||||||||||||
column · Integer32 (0 | 1 | 3) · read-only · current Number of phases for input metering. | |||||||||||||||||||||
| CsdbDevCfOutletsTotal | 1.3.6.1.4.1.31034.12.1.1.2.2.1.1.2 | Integer32 (0..54) | RO | 6 | |||||||||||||||||
column · Integer32 (0..54) · read-only · current Total number of outlets including hardwired without switch/metered modules. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CsdbDevCfOutletsSwitched | 1.3.6.1.4.1.31034.12.1.1.2.2.1.1.3 | Integer32 (0..54) | RO | ||||||||||||||||||
column · Integer32 (0..54) · read-only · current Number of switched outlets. If outlet numbering is non-contiguous its the highest outlet number. | |||||||||||||||||||||
| CsdbDevCfOutletsMetered | 1.3.6.1.4.1.31034.12.1.1.2.2.1.1.4 | Integer32 (0..54) | RO | ||||||||||||||||||
column · Integer32 (0..54) · read-only · current Number of metered outlets. If outlet numbering is non-contiguous its the highest outlet number. | |||||||||||||||||||||
| CsdbDevCfSensors | 1.3.6.1.4.1.31034.12.1.1.2.2.1.1.5 | Integer32 (0..16) | RO | 1 | |||||||||||||||||
column · Integer32 (0..16) · read-only · current The number sensors. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CsdbDevCfMaximumLoad | 1.3.6.1.4.1.31034.12.1.1.2.2.1.1.6 | Integer32 (16 | 32) | RO | 32 | |||||||||||||||||
column · Integer32 (16 | 32) · read-only · current Maximum rated load of device per phase
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CsdbDevCfBranches | 1.3.6.1.4.1.31034.12.1.1.2.2.1.1.7 | Integer32 (0..6) | RO | ||||||||||||||||||
column · Integer32 (0..6) · read-only · current Number of branches for input metering. | |||||||||||||||||||||
| CsdbDevCfNeutral | 1.3.6.1.4.1.31034.12.1.1.2.2.1.1.8 | Integer32 (0 | 1) | RO | ||||||||||||||||||
column · Integer32 (0 | 1) · read-only · current Nuetral current measurement. | |||||||||||||||||||||
| CsdbDevCfTempSensors | 1.3.6.1.4.1.31034.12.1.1.2.2.1.1.9 | Integer32 (0..16) | RO | ||||||||||||||||||
column · Integer32 (0..16) · read-only · current Number of temperature sensors present in the system. | |||||||||||||||||||||
| CsdbDevCfTotals | 1.3.6.1.4.1.31034.12.1.1.2.2.1.1.10 | Integer32 (0..16) | RO | ||||||||||||||||||
column · Integer32 (0..16) · read-only · current The number of totals rows for the configuration. | |||||||||||||||||||||
| NsdbDevSystemStatus | 1.3.6.1.4.1.31034.12.1.1.2.3 | ||||||||||||||||||||
| TsdbDevSsTable | 1.3.6.1.4.1.31034.12.1.1.2.3.1 | NA | |||||||||||||||||||
table · not-accessible · current A table containing system status information of devices connected to the databus. The number of entries is given by the value of sdbMgmtStsAddressableDevices. | |||||||||||||||||||||
| RsdbDevSsEntry | 1.3.6.1.4.1.31034.12.1.1.2.3.1.1 | NA | |||||||||||||||||||
row · not-accessible · current System status entry containing system status objects of a particular databus device.
| |||||||||||||||||||||
| CsdbDevSsDeviceStatusCode | 1.3.6.1.4.1.31034.12.1.1.2.3.1.1.1 | Integer32 (0..255) | RO | ||||||||||||||||||
column · Integer32 (0..255) · read-only · current Returns an internal status or error code. A value of 0 means OK. If not 0 it can be any of the following codes. Multiple status codes can be active at the same time. The value will be the sum of the active status codes. 1 = alert flagged 2 = settings(s) initialized 4 = power-on reset 8 = external reset 16 = watchdog timer caused reset 32 = brownout detected 64 = controller error 128 = slave module was reset | |||||||||||||||||||||
| CsdbDevSsTemperatureAlert | 1.3.6.1.4.1.31034.12.1.1.2.3.1.1.2 | Integer32 (0..2) | RO | ||||||||||||||||||
column · Integer32 (0..2) · read-only · current An alert has been raised due to temperature exceeding treshhold. 0 = no alert 1 = internal temperature sensor 2 = external temperature sensor | |||||||||||||||||||||
| CsdbDevSsInputCurrentAlert | 1.3.6.1.4.1.31034.12.1.1.2.3.1.1.3 | Integer32 (0..3) | RO | ||||||||||||||||||
column · Integer32 (0..3) · read-only · current An alert has been raised due to current exceeding treshhold. The value indicates the exceeding phase. 0 = no alert. | |||||||||||||||||||||
| CsdbDevSsOutletCurrentAlert | 1.3.6.1.4.1.31034.12.1.1.2.3.1.1.4 | Integer32 (0..54) | RO | ||||||||||||||||||
column · Integer32 (0..54) · read-only · current An alert has been raised due to current exceeding treshhold. The value indicates the exceeding outlet. 0 = no alert. | |||||||||||||||||||||
| CsdbDevSsInputVoltageAlert | 1.3.6.1.4.1.31034.12.1.1.2.3.1.1.5 | Integer32 (0..3) | RO | ||||||||||||||||||
column · Integer32 (0..3) · read-only · current An alert has been raised due to a voltage dip. The value indicates the dipped phase. 0 = no alert. | |||||||||||||||||||||
| CsdbDevSsOutletCurrentDropAlert | 1.3.6.1.4.1.31034.12.1.1.2.3.1.1.6 | Integer32 (0..54) | RO | ||||||||||||||||||
column · Integer32 (0..54) · read-only · current An alert has been raised due to the current of a metered outlet suddenly dropping to near zero, possibly indicating a blown fuse. The value indicates the dropped outlet. 0 = no alert. | |||||||||||||||||||||
| CsdbDevSsInputCurrentDropAlert | 1.3.6.1.4.1.31034.12.1.1.2.3.1.1.7 | Integer32 (0..3) | RO | ||||||||||||||||||
column · Integer32 (0..3) · read-only · current An alert has been raised due to the current of a metered input suddenly dropping to near zero, possibly indicating a blown fuse. The value indicates the dropped phase. 0 = no alert. | |||||||||||||||||||||
| CsdbDevSsSensorChangeAlert | 1.3.6.1.4.1.31034.12.1.1.2.3.1.1.8 | Integer32 (0..16) | RO | ||||||||||||||||||
column · Integer32 (0..16) · read-only · current An alert has been raised due to a change in the number of sensors. The value indicates the previous amount of sensors. | |||||||||||||||||||||
| CsdbDevSsOutletVoltageDropAlert | 1.3.6.1.4.1.31034.12.1.1.2.3.1.1.9 | Integer32 (0..54) | RO | ||||||||||||||||||
column · Integer32 (0..54) · read-only · current An alert has been raised due to voltage drop on this outlet. The value indicates the first failed outlet. | |||||||||||||||||||||
| CsdbDevSsBranchCurrentAlert | 1.3.6.1.4.1.31034.12.1.1.2.3.1.1.10 | Integer32 (0..18) | RO | ||||||||||||||||||
column · Integer32 (0..18) · read-only · current An alert has been raised due to current exceeding treshhold. The value indicates the exceeding branch. 0 = no alert. | |||||||||||||||||||||
| CsdbDevSsBranchVoltageAlert | 1.3.6.1.4.1.31034.12.1.1.2.3.1.1.11 | Integer32 (0..18) | RO | ||||||||||||||||||
column · Integer32 (0..18) · read-only · current An alert has been raised due to a voltage dip. The value indicates the dipped branch. 0 = no alert. | |||||||||||||||||||||
| CsdbDevSsNeutralCurrentAlert | 1.3.6.1.4.1.31034.12.1.1.2.3.1.1.12 | Integer32 (0..1) | RO | ||||||||||||||||||
column · Integer32 (0..1) · read-only · current An alert has been raised due to current exceeding treshhold. 0 = no alert 1 = current alert | |||||||||||||||||||||
| CsdbDevSsResidualCurrentAlert | 1.3.6.1.4.1.31034.12.1.1.2.3.1.1.13 | Integer32 (0..2) | RO | ||||||||||||||||||
column · Integer32 (0..2) · read-only · current A residual current alert has been raised.
0 = no alert
1 = current exceeding treshhold alert
2 = sensor error | |||||||||||||||||||||
| CsdbDevSsHardwareAlert | 1.3.6.1.4.1.31034.12.1.1.2.3.1.1.14 | Integer32 (0..9) | RO | ||||||||||||||||||
column · Integer32 (0..9) · read-only · current 0 = no alarm >0 = or slave number for alert | |||||||||||||||||||||
| NsdbDevReset | 1.3.6.1.4.1.31034.12.1.1.2.4 | ||||||||||||||||||||
| TsdbDevRsTable | 1.3.6.1.4.1.31034.12.1.1.2.4.1 | NA | |||||||||||||||||||
table · not-accessible · current A table providing reset capabilities to devices connected to the databus. The number of entries is given by the value of sdbMgmtStsAddressableDevices. | |||||||||||||||||||||
| RsdbDevRsEntry | 1.3.6.1.4.1.31034.12.1.1.2.4.1.1 | NA | |||||||||||||||||||
row · not-accessible · current Reset entry providing reset objects of a particular databus device.
| |||||||||||||||||||||
| CsdbDevRsReboot | 1.3.6.1.4.1.31034.12.1.1.2.4.1.1.1 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current Warm reboot/reset of device controller. NOTE: this will have NO effect on outlet status!
| |||||||||||||||||||||
| CsdbDevRsResetAlerts | 1.3.6.1.4.1.31034.12.1.1.2.4.1.1.2 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current Reset all alert signals and device status code.
| |||||||||||||||||||||
| CsdbDevRsZeroInputKWhSubtotal | 1.3.6.1.4.1.31034.12.1.1.2.4.1.1.3 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current Reset of all input kWh subtotal counters to zero.
| |||||||||||||||||||||
| CsdbDevRsZeroOutletKWhSubtotal | 1.3.6.1.4.1.31034.12.1.1.2.4.1.1.4 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current Reset of all outlet kWh subtotal counter to zero.
| |||||||||||||||||||||
| CsdbDevRsResetPeaksAndDips | 1.3.6.1.4.1.31034.12.1.1.2.4.1.1.5 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current Reset all peak and dip values to zero.
| |||||||||||||||||||||
| NsdbDevSettings | 1.3.6.1.4.1.31034.12.1.1.2.5 | ||||||||||||||||||||
| TsdbDevStTable | 1.3.6.1.4.1.31034.12.1.1.2.5.1 | NA | |||||||||||||||||||
table · not-accessible · current A table containing setting information of devices connected to the databus. The number of entries is given by the value of sdbMgmtStsAddressableDevices. | |||||||||||||||||||||
| RsdbDevStEntry | 1.3.6.1.4.1.31034.12.1.1.2.5.1.1 | NA | |||||||||||||||||||
row · not-accessible · current Setting entry containing settings objects of a particular databus device.
| |||||||||||||||||||||
| CsdbDevStAutoResetAlerts | 1.3.6.1.4.1.31034.12.1.1.2.5.1.1.2 | Integer32 (0..65535) | RW | ||||||||||||||||||
column · Integer32 (0..65535) · read-write · current Auto reset alerts configuration. If set to 0 the auto reset alerts feature is disabled. If set to a value greater then 0, the auto reset alerts feature is enabled and alerts will get cleared after the configured amount of seconds since the last alert condition have passed.
| |||||||||||||||||||||
| CsdbDevStExtendedNames | 1.3.6.1.4.1.31034.12.1.1.2.5.1.1.3 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current Use original or longer names for inputs, outlets and sensors.
| |||||||||||||||||||||
| CsdbDevStPeakDuration | 1.3.6.1.4.1.31034.12.1.1.2.5.1.1.4 | MilliSecond (0..65535) | RW | ||||||||||||||||||
column · MilliSecond (0..65535) · read-write · current Amount of ms a current peak should last before an alert is raised.
| |||||||||||||||||||||
| CsdbDevStFixedOutletDelay | 1.3.6.1.4.1.31034.12.1.1.2.5.1.1.5 | MilliSecond (100..65535) | RW | ||||||||||||||||||
column · MilliSecond (100..65535) · read-write · current Minimal delay between two successive relay switches in milliseconds. Minimal delay is 100 ms. Will always be respected!
| |||||||||||||||||||||
| CsdbDevStPowerSaverMode | 1.3.6.1.4.1.31034.12.1.1.2.5.1.1.6 | Second (0 | 10 | 60 | 120 | 240) | RW | ||||||||||||||||||
column · Second (0 | 10 | 60 | 120 | 240) · read-write · current Set backlight on time in seconds. 0 keeps display always on. Note that keeping the backlight on may decrease luminosity over time.
| |||||||||||||||||||||
| CsdbDevStOutletPowerUpMode | 1.3.6.1.4.1.31034.12.1.1.2.5.1.1.7 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current Behaviour of outlets on power-up.
| |||||||||||||||||||||
| CsdbDevStMaximumTemperature | 1.3.6.1.4.1.31034.12.1.1.2.5.1.1.8 | Integer32 (0..99) | RW | ||||||||||||||||||
column · Integer32 (0..99) · read-write · current Maximum temperature threshold An alert will be generated whenever the temperature is above this value. Zero means disabled.
| |||||||||||||||||||||
| CsdbDevStDisplayOrientation | 1.3.6.1.4.1.31034.12.1.1.2.5.1.1.9 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current Display orientation.
| |||||||||||||||||||||
| CsdbDevStLocalAlertReset | 1.3.6.1.4.1.31034.12.1.1.2.5.1.1.10 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current Allow alerts to be reset locally on device by pushing one of the buttons.
| |||||||||||||||||||||
| CsdbDevStCurrentDropDetection | 1.3.6.1.4.1.31034.12.1.1.2.5.1.1.11 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current Enables the current drop detection function.
| |||||||||||||||||||||
| CsdbDevStUsbMode | 1.3.6.1.4.1.31034.12.1.1.2.5.1.1.13 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current Allow the USB port to be used for specific tasks
| |||||||||||||||||||||
| CsdbDevStSensorChangeAlertMode | 1.3.6.1.4.1.31034.12.1.1.2.5.1.1.14 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current Enable sensoe change alerts
| |||||||||||||||||||||
| CsdbDevStOutletUnlockOverride | 1.3.6.1.4.1.31034.12.1.1.2.5.1.1.15 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current Overrides the timeout. If this is set to 1 then the timeout will be ignored, otherwise the timeout will be taken into account.
| |||||||||||||||||||||
| NsdbDevInput | 1.3.6.1.4.1.31034.12.1.1.2.6 | ||||||||||||||||||||
| TsdbDevInTable | 1.3.6.1.4.1.31034.12.1.1.2.6.1 | NA | |||||||||||||||||||
table · not-accessible · current A table containing information of inputs of devices connected to the databus. | |||||||||||||||||||||
| RsdbDevInEntry | 1.3.6.1.4.1.31034.12.1.1.2.6.1.1 | NA | |||||||||||||||||||
row · not-accessible · current Inputs entry containing objects of an input of a particular databus device. Note that this table has two indexes. sdbDevIdIndex to identify a particular device and sdbDevInIndex to identify a particular input of the device identified by sdbDevIdIndex.
| |||||||||||||||||||||
| CsdbDevInIndex | 1.3.6.1.4.1.31034.12.1.1.2.6.1.1.1 | Integer32 (1..54) | NA | ||||||||||||||||||
column · Integer32 (1..54) · not-accessible · current A unique value for each input. Its value ranges between 1 and the value of sdbDevCfPhases. | |||||||||||||||||||||
| CsdbDevInKWhTotal | 1.3.6.1.4.1.31034.12.1.1.2.6.1.1.2 | KiloWattHour | RO | 66 | |||||||||||||||||
column · KiloWattHour · read-only · current Total kWh value of an input. This value can not be reset.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CsdbDevInKWhSubtotal | 1.3.6.1.4.1.31034.12.1.1.2.6.1.1.3 | KiloWattHour | RO | ||||||||||||||||||
column · KiloWattHour · read-only · current Subtotal kWh value of an input. This value can be reset.
| |||||||||||||||||||||
| CsdbDevInPowerFactor | 1.3.6.1.4.1.31034.12.1.1.2.6.1.1.4 | CentiPercent | RO | 4594 | |||||||||||||||||
column · CentiPercent · read-only · current Power factor of input. The power factor of an AC power system is defined as the ratio of the real or active power to the apparent power and is a number between 0 and 1. This value is expressed as a percentage between 0% and 100%.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CsdbDevInActualCurrent | 1.3.6.1.4.1.31034.12.1.1.2.6.1.1.5 | CentiAmpere | RO | 32 | |||||||||||||||||
column · CentiAmpere · read-only · current Actual apparent, RMS current.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CsdbDevInPeakCurrent | 1.3.6.1.4.1.31034.12.1.1.2.6.1.1.6 | CentiAmpere | RO | ||||||||||||||||||
column · CentiAmpere · read-only · current Peak apparent, RMS current. Highest value since last reset of the alerts.
| |||||||||||||||||||||
| CsdbDevInActualVoltage | 1.3.6.1.4.1.31034.12.1.1.2.6.1.1.7 | CentiVolt | RO | 22900 | |||||||||||||||||
column · CentiVolt · read-only · current The actual voltage.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CsdbDevInMinVoltage | 1.3.6.1.4.1.31034.12.1.1.2.6.1.1.8 | CentiVolt | RO | ||||||||||||||||||
column · CentiVolt · read-only · current RMS voltage dip. Lowest value since reset of alerts.
| |||||||||||||||||||||
| CsdbDevInPowerVoltAmpere | 1.3.6.1.4.1.31034.12.1.1.2.6.1.1.9 | Integer32 (0..327680) | RO | 70 | |||||||||||||||||
column · Integer32 (0..327680) · read-only · current Calculated apparent power.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CsdbDevInPowerWatt | 1.3.6.1.4.1.31034.12.1.1.2.6.1.1.10 | Integer32 (0..327680) | RO | ||||||||||||||||||
column · Integer32 (0..327680) · read-only · current Calculated real power.
| |||||||||||||||||||||
| CsdbDevInMaxAmps | 1.3.6.1.4.1.31034.12.1.1.2.6.1.1.11 | CentiAmpere | RW | 2800 | |||||||||||||||||
column · CentiAmpere · read-write · current Maximum current per input phase. Should last at least sdbDevStPeakDuration ms before triggering an alert.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CsdbDevInCTRatio | 1.3.6.1.4.1.31034.12.1.1.2.6.1.1.12 | Integer32 (0..255) | RW | ||||||||||||||||||
column · Integer32 (0..255) · read-write · current The multiplier to use for the input CTs. | |||||||||||||||||||||
| CsdbDevInName | 1.3.6.1.4.1.31034.12.1.1.2.6.1.1.13 | DisplayString (SIZE (0..8)) | RW | t=master | |||||||||||||||||
column · DisplayString (SIZE (0..8)) · read-write · current User configurable naming of inputs or phases. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CsdbDevInZeroKWhSubtotal | 1.3.6.1.4.1.31034.12.1.1.2.6.1.1.14 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current Reset input kWh subtotal counter of a single input to zero.
| |||||||||||||||||||||
| NsdbDevOutlet | 1.3.6.1.4.1.31034.12.1.1.2.7 | ||||||||||||||||||||
| TsdbDevOutTable | 1.3.6.1.4.1.31034.12.1.1.2.7.1 | NA | |||||||||||||||||||
table · not-accessible · current A table containing information of outlets of devices connected to the databus. | |||||||||||||||||||||
| RsdbDevOutEntry | 1.3.6.1.4.1.31034.12.1.1.2.7.1.1 | NA | |||||||||||||||||||
row · not-accessible · current Outlets entry containing objects of an outlet of a particular databus device. Note that this table has two indexes. sdbDevIdIndex to identify a particular device and sdbDevOutIndex to identify a particular outlet of the device identified by sdbDevIdIndex.
| |||||||||||||||||||||
| CsdbDevOutIndex | 1.3.6.1.4.1.31034.12.1.1.2.7.1.1.1 | Integer32 (1..54) | NA | ||||||||||||||||||
column · Integer32 (1..54) · not-accessible · current A unique value for each outlet. Its value ranges between 1 and the value of sdbDevCfOutletsTotal. | |||||||||||||||||||||
| CsdbDevOutName | 1.3.6.1.4.1.31034.12.1.1.2.7.1.1.2 | DisplayString (SIZE (0..8)) | RW | blaat | |||||||||||||||||
column · DisplayString (SIZE (0..8)) · read-write · current User configurable naming of individual outlets. Example values from LibreNMS test devices
| |||||||||||||||||||||
| TsdbDevOutMtTable | 1.3.6.1.4.1.31034.12.1.1.2.7.2 | NA | |||||||||||||||||||
table · not-accessible · current A table containing information of metered outlets of devices connected to the databus. | |||||||||||||||||||||
| RsdbDevOutMtEntry | 1.3.6.1.4.1.31034.12.1.1.2.7.2.1 | NA | |||||||||||||||||||
row · not-accessible · current Metered outlets entry containing objects of a metered outlet of a particular databus device. Note that this table has two indexes. sdbDevIdIndex to identify a particular device and sdbDevOutMtIndex to identify a particular outlet of the device identified by sdbDevIdIndex. | |||||||||||||||||||||
| CsdbDevOutMtIndex | 1.3.6.1.4.1.31034.12.1.1.2.7.2.1.1 | Integer32 (1..54) | NA | ||||||||||||||||||
column · Integer32 (1..54) · not-accessible · current A unique value for each outlet. Its value ranges between 1 and the value of sdbDevCfOutletsMetered. | |||||||||||||||||||||
| CsdbDevOutMtKWhTotal | 1.3.6.1.4.1.31034.12.1.1.2.7.2.1.2 | KiloWattHour | RO | 0 | |||||||||||||||||
column · KiloWattHour · read-only · current Total kWh value of an outlet. This value can not be reset.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CsdbDevOutMtKWhSubtotal | 1.3.6.1.4.1.31034.12.1.1.2.7.2.1.3 | KiloWattHour | RO | ||||||||||||||||||
column · KiloWattHour · read-only · current Subotal kWh value of an outlet. This value can be reset.
| |||||||||||||||||||||
| CsdbDevOutMtPowerFactor | 1.3.6.1.4.1.31034.12.1.1.2.7.2.1.4 | CentiPercent | RO | 10000 | |||||||||||||||||
column · CentiPercent · read-only · current Power factor of outlet. The power factor of an AC power system is defined as the ratio of the real or active power to the apparent power and is a number between 0 and 1. This number is expressed as a percentage between 0% and 100%.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CsdbDevOutMtActualCurrent | 1.3.6.1.4.1.31034.12.1.1.2.7.2.1.5 | CentiAmpere | RO | 0 | |||||||||||||||||
column · CentiAmpere · read-only · current Actual apparent, RMS current.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CsdbDevOutMtPeakCurrent | 1.3.6.1.4.1.31034.12.1.1.2.7.2.1.6 | CentiAmpere | RO | ||||||||||||||||||
column · CentiAmpere · read-only · current Peak apparent, RMS current. Highest value since last reset of the alerts.
| |||||||||||||||||||||
| CsdbDevOutMtActualVoltage | 1.3.6.1.4.1.31034.12.1.1.2.7.2.1.7 | CentiVolt | RO | 23433 | |||||||||||||||||
column · CentiVolt · read-only · current Actual voltage on outlet.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CsdbDevOutMtMaxAmps | 1.3.6.1.4.1.31034.12.1.1.2.7.2.1.8 | CentiAmpere | RW | 20000 | |||||||||||||||||
column · CentiAmpere · read-write · current Maximum current per outlet. Should last at least sdbDevStPeakDuration ms before triggering an alert.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CsdbDevOutMtCTRatio | 1.3.6.1.4.1.31034.12.1.1.2.7.2.1.9 | Integer32 (0..255) | RW | ||||||||||||||||||
column · Integer32 (0..255) · read-write · current The multiplier to use for the outlet CTs. | |||||||||||||||||||||
| CsdbDevOutMtPowerVoltAmpere | 1.3.6.1.4.1.31034.12.1.1.2.7.2.1.10 | Integer32 (0..327680) | RO | 0 | |||||||||||||||||
column · Integer32 (0..327680) · read-only · current Calculated apparent power.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CsdbDevOutMtPowerWatt | 1.3.6.1.4.1.31034.12.1.1.2.7.2.1.11 | Integer32 (0..327680) | RO | ||||||||||||||||||
column · Integer32 (0..327680) · read-only · current Calculated real power.
| |||||||||||||||||||||
| TsdbDevOutSwTable | 1.3.6.1.4.1.31034.12.1.1.2.7.3 | NA | |||||||||||||||||||
table · not-accessible · current A table containing information of switched outlets of devices connected to the databus. | |||||||||||||||||||||
| RsdbDevOutSwEntry | 1.3.6.1.4.1.31034.12.1.1.2.7.3.1 | NA | |||||||||||||||||||
row · not-accessible · current Switched outlets entry containing objects of a switched outlet of a particular databus device. Note that this table has two indexes. sdbDevIdIndex to identify a particular device and sdbDevOutSwIndex to identify a particular outlet of the device identified by sdbDevIdIndex. | |||||||||||||||||||||
| CsdbDevOutSwIndex | 1.3.6.1.4.1.31034.12.1.1.2.7.3.1.1 | Integer32 (1..54) | NA | ||||||||||||||||||
column · Integer32 (1..54) · not-accessible · current A unique value for each outlet. Its value ranges between 1 and the value of sdbDevCfOutletsSwitched. | |||||||||||||||||||||
| CsdbDevOutSwCurrentState | 1.3.6.1.4.1.31034.12.1.1.2.7.3.1.2 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current The actual state of the outlet relay. Note that Writing is only effective after setting sdbDevOutSwUnlock.
| |||||||||||||||||||||
| CsdbDevOutSwScheduled | 1.3.6.1.4.1.31034.12.1.1.2.7.3.1.3 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current A one indicates pending activity; the switch delay has not yet expired.
| |||||||||||||||||||||
| CsdbDevOutSwUnlock | 1.3.6.1.4.1.31034.12.1.1.2.7.3.1.4 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current Switching and rebooting is unlocked for 10 seconds by writing a 1.
| |||||||||||||||||||||
| CsdbDevOutSwIndividualOutletDelay | 1.3.6.1.4.1.31034.12.1.1.2.7.3.1.5 | Second (0..65535) | RW | ||||||||||||||||||
column · Second (0..65535) · read-write · current Delay before an individual outlet switches on at power-up.
| |||||||||||||||||||||
| CsdbDevOutSwReboot | 1.3.6.1.4.1.31034.12.1.1.2.7.3.1.6 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current Reboot outlet relay if current state is on and outlet is unlocked; The outlet will be turned on after 10 seconds.
| |||||||||||||||||||||
| NsdbDevSensor | 1.3.6.1.4.1.31034.12.1.1.2.8 | ||||||||||||||||||||
| TsdbDevMeasuresTable | 1.3.6.1.4.1.31034.12.1.1.2.8.1 | NA | |||||||||||||||||||
table · not-accessible · current A table containing information of temperatures of devices connected to the databus. | |||||||||||||||||||||
| RsdbDevMeasuresEntry | 1.3.6.1.4.1.31034.12.1.1.2.8.1.1 | NA | |||||||||||||||||||
row · not-accessible · current Device measures entry containing temperature information objects of a particular databus device.
| |||||||||||||||||||||
| CsdbDevMsIntTemperature | 1.3.6.1.4.1.31034.12.1.1.2.8.1.1.1 | CentiCelsius | RO | ||||||||||||||||||
column · CentiCelsius · read-only · current Actual internal device temperature in deg C
| |||||||||||||||||||||
| CsdbDevMsExtTemperature | 1.3.6.1.4.1.31034.12.1.1.2.8.1.1.2 | CentiCelsius | RO | ||||||||||||||||||
column · CentiCelsius · read-only · current Actual external device temperature sensor in deg C.
| |||||||||||||||||||||
| CsdbDevMsIntTemperaturePeak | 1.3.6.1.4.1.31034.12.1.1.2.8.1.1.3 | CentiCelsius | RO | ||||||||||||||||||
column · CentiCelsius · read-only · current Peak internal device temperature since last reset of alerts.
| |||||||||||||||||||||
| CsdbDevMsExtTemperaturePeak | 1.3.6.1.4.1.31034.12.1.1.2.8.1.1.4 | CentiCelsius | RO | ||||||||||||||||||
column · CentiCelsius · read-only · current Peak external device temperature since last reset of alerts.
| |||||||||||||||||||||
| CsdbDevMsResidualCurrent | 1.3.6.1.4.1.31034.12.1.1.2.8.1.1.5 | CentiAmpere | RO | ||||||||||||||||||
column · CentiAmpere · read-only · current Residual current.
| |||||||||||||||||||||
| CsdbDevMsResidualPeak | 1.3.6.1.4.1.31034.12.1.1.2.8.1.1.6 | CentiAmpere | RO | ||||||||||||||||||
column · CentiAmpere · read-only · current Peak residual current.
| |||||||||||||||||||||
| TsdbDevSnsTable | 1.3.6.1.4.1.31034.12.1.1.2.8.2 | NA | |||||||||||||||||||
table · not-accessible · current A table containing information of sensors of devices connected to the databus. | |||||||||||||||||||||
| RsdbDevSnsEntry | 1.3.6.1.4.1.31034.12.1.1.2.8.2.1 | NA | |||||||||||||||||||
row · not-accessible · current Sensors entry containing objects of a sensor of a particular databus device. Note that this table has two indexes. sdbDevIdIndex to identify a particular device and sdbDevSnsIndex to identify a particular sensor of the device identified by sdbDevIdIndex.
| |||||||||||||||||||||
| CsdbDevSnsIndex | 1.3.6.1.4.1.31034.12.1.1.2.8.2.1.1 | Integer32 (1..16) | NA | ||||||||||||||||||
column · Integer32 (1..16) · not-accessible · current A unique value for each sensor. Its value ranges between 1 and the value of sdbDevCfSensors. | |||||||||||||||||||||
| CsdbDevSnsType | 1.3.6.1.4.1.31034.12.1.1.2.8.2.1.2 | DisplayString (SIZE (1)) | RO | I | |||||||||||||||||
column · DisplayString (SIZE (1)) · read-only · current Type of connected sensor. T = Temperature (C) H = Humidity (%) I = dry switch contact Example values from LibreNMS test devices
| |||||||||||||||||||||
| CsdbDevSnsValue | 1.3.6.1.4.1.31034.12.1.1.2.8.2.1.3 | CentiValue (0..327680) | RO | ||||||||||||||||||
column · CentiValue (0..327680) · read-only · current Value of connected sensor | |||||||||||||||||||||
| CsdbDevSnsName | 1.3.6.1.4.1.31034.12.1.1.2.8.2.1.4 | DisplayString (SIZE (0..18)) | RW | | |||||||||||||||||
column · DisplayString (SIZE (0..18)) · read-write · current User definable name for sensors. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NsdbDevPerformance | 1.3.6.1.4.1.31034.12.1.1.2.9 | ||||||||||||||||||||
| TsdbDevPerformanceTable | 1.3.6.1.4.1.31034.12.1.1.2.9.1 | NA | |||||||||||||||||||
table · not-accessible · current A table containing information of sensors of devices connected to the databus. | |||||||||||||||||||||
| RsdbDevPerformanceEntry | 1.3.6.1.4.1.31034.12.1.1.2.9.1.1 | NA | |||||||||||||||||||
row · not-accessible · current Performance counters of a particular databus device. Note that this table has two indexes. sdbDevIdIndex to identify a particular device and sdbDevPerformanceIndex to identify a particular counter of the device identified by sdbDevIdIndex. | |||||||||||||||||||||
| CsdbDevPerformanceIndex | 1.3.6.1.4.1.31034.12.1.1.2.9.1.1.1 | Integer32 (1..16) | NA | ||||||||||||||||||
column · Integer32 (1..16) · not-accessible · current A unique value for each counter. Its value ranges between 1 and 16. | |||||||||||||||||||||
| CsdbDevPerformanceValue | 1.3.6.1.4.1.31034.12.1.1.2.9.1.1.2 | Integer32 (0..16777215) | RO | ||||||||||||||||||
column · Integer32 (0..16777215) · read-only · current Value of counter | |||||||||||||||||||||
| CsdbDevPerformanceMax | 1.3.6.1.4.1.31034.12.1.1.2.9.1.1.3 | Integer32 (0..16777215) | RO | ||||||||||||||||||
column · Integer32 (0..16777215) · read-only · current Max of counter | |||||||||||||||||||||
| CsdbDevPerformanceLimit | 1.3.6.1.4.1.31034.12.1.1.2.9.1.1.4 | Integer32 (0..16777215) | RO | ||||||||||||||||||
column · Integer32 (0..16777215) · read-only · current Limit of counter | |||||||||||||||||||||
| CsdbDevPerformanceName | 1.3.6.1.4.1.31034.12.1.1.2.9.1.1.5 | DisplayString (SIZE (0..12)) | RW | ||||||||||||||||||
column · DisplayString (SIZE (0..12)) · read-write · current User definable name for counter. | |||||||||||||||||||||
| TsdbDevPerformanceResetTable | 1.3.6.1.4.1.31034.12.1.1.2.9.2 | NA | |||||||||||||||||||
table · not-accessible · current A table containing the last reset reason of the device | |||||||||||||||||||||
| RsdbDevPerformanceResetEntry | 1.3.6.1.4.1.31034.12.1.1.2.9.2.1 | NA | |||||||||||||||||||
row · not-accessible · current Setting entry containing settings objects of a particular databus device.
| |||||||||||||||||||||
| CsdbDevPerformanceResetReason | 1.3.6.1.4.1.31034.12.1.1.2.9.2.1.1 | DisplayString (SIZE (0..64)) | RW | ||||||||||||||||||
column · DisplayString (SIZE (0..64)) · read-write · current Last reset reason. | |||||||||||||||||||||
| CsdbDevResetUptime | 1.3.6.1.4.1.31034.12.1.1.2.9.2.1.2 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current Uptime before last reset | |||||||||||||||||||||
| NsdbDevBranches | 1.3.6.1.4.1.31034.12.1.1.2.10 | ||||||||||||||||||||
| TsdbDevBranchTable | 1.3.6.1.4.1.31034.12.1.1.2.10.1 | NA | |||||||||||||||||||
table · not-accessible · current A table containing information of inputs of devices connected to the databus. | |||||||||||||||||||||
| RsdbDevBranchEntry | 1.3.6.1.4.1.31034.12.1.1.2.10.1.1 | NA | |||||||||||||||||||
row · not-accessible · current Inputs entry containing objects of an input of a particular databus device. Note that this table has two indexes. sdbDevIdIndex to identify a particular device and sdbDevBranchIndex to identify a particular input of the device identified by sdbDevIdIndex. | |||||||||||||||||||||
| CsdbDevBranchIndex | 1.3.6.1.4.1.31034.12.1.1.2.10.1.1.1 | Integer32 (1..54) | NA | ||||||||||||||||||
column · Integer32 (1..54) · not-accessible · current A unique value for each input. Its value ranges between 1 and the value of sdbDevCfPhases. | |||||||||||||||||||||
| CsdbDevBranchKWhTotal | 1.3.6.1.4.1.31034.12.1.1.2.10.1.1.2 | KiloWattHour | RO | ||||||||||||||||||
column · KiloWattHour · read-only · current Total kWh value of an input. This value can not be reset.
| |||||||||||||||||||||
| CsdbDevBranchKWhSubtotal | 1.3.6.1.4.1.31034.12.1.1.2.10.1.1.3 | KiloWattHour | RO | ||||||||||||||||||
column · KiloWattHour · read-only · current Subtotal kWh value of an input. This value can be reset.
| |||||||||||||||||||||
| CsdbDevBranchPowerFactor | 1.3.6.1.4.1.31034.12.1.1.2.10.1.1.4 | CentiPercent | RO | ||||||||||||||||||
column · CentiPercent · read-only · current Power factor of input. The power factor of an AC power system is defined as the ratio of the real or active power to the apparent power and is a number between 0 and 1. This value is expressed as a percentage between 0% and 100%.
| |||||||||||||||||||||
| CsdbDevBranchActualCurrent | 1.3.6.1.4.1.31034.12.1.1.2.10.1.1.5 | CentiAmpere | RO | ||||||||||||||||||
column · CentiAmpere · read-only · current Actual apparent, RMS current.
| |||||||||||||||||||||
| CsdbDevBranchPeakCurrent | 1.3.6.1.4.1.31034.12.1.1.2.10.1.1.6 | CentiAmpere | RO | ||||||||||||||||||
column · CentiAmpere · read-only · current Peak apparent, RMS current. Highest value since last reset of the alerts.
| |||||||||||||||||||||
| CsdbDevBranchActualVoltage | 1.3.6.1.4.1.31034.12.1.1.2.10.1.1.7 | CentiVolt | RO | ||||||||||||||||||
column · CentiVolt · read-only · current The actual voltage.
| |||||||||||||||||||||
| CsdbDevBranchMinVoltage | 1.3.6.1.4.1.31034.12.1.1.2.10.1.1.8 | CentiVolt | RO | ||||||||||||||||||
column · CentiVolt · read-only · current RMS voltage dip. Lowest value since reset of alerts.
| |||||||||||||||||||||
| CsdbDevBranchPowerVoltAmpere | 1.3.6.1.4.1.31034.12.1.1.2.10.1.1.9 | Integer32 (0..327680) | RO | ||||||||||||||||||
column · Integer32 (0..327680) · read-only · current Calculated apparent power.
| |||||||||||||||||||||
| CsdbDevBranchPowerWatt | 1.3.6.1.4.1.31034.12.1.1.2.10.1.1.10 | Integer32 (0..327680) | RO | ||||||||||||||||||
column · Integer32 (0..327680) · read-only · current Calculated real power.
| |||||||||||||||||||||
| CsdbDevBranchMaxAmps | 1.3.6.1.4.1.31034.12.1.1.2.10.1.1.11 | CentiAmpere | RW | ||||||||||||||||||
column · CentiAmpere · read-write · current Maximum current per input phase. Should last at least sdbDevStPeakDuration ms before triggering an alert.
| |||||||||||||||||||||
| CsdbDevBranchCTRatio | 1.3.6.1.4.1.31034.12.1.1.2.10.1.1.12 | Integer32 (0..255) | RW | ||||||||||||||||||
column · Integer32 (0..255) · read-write · current The multiplier to use for the input CTs. | |||||||||||||||||||||
| CsdbDevBranchName | 1.3.6.1.4.1.31034.12.1.1.2.10.1.1.13 | DisplayString (SIZE (0..8)) | RW | ||||||||||||||||||
column · DisplayString (SIZE (0..8)) · read-write · current User configurable naming of branches. | |||||||||||||||||||||
| CsdbDevBranchZeroKWhSubtotal | 1.3.6.1.4.1.31034.12.1.1.2.10.1.1.14 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current Reset input kWh subtotal counter of a single input to zero.
| |||||||||||||||||||||
| NsdbDevTotals | 1.3.6.1.4.1.31034.12.1.1.2.11 | ||||||||||||||||||||
| TsdbDevTotalsTable | 1.3.6.1.4.1.31034.12.1.1.2.11.1 | NA | |||||||||||||||||||
table · not-accessible · current A table containing information of inputs of devices connected to the databus. | |||||||||||||||||||||
| RsdbDevTotalsEntry | 1.3.6.1.4.1.31034.12.1.1.2.11.1.1 | NA | |||||||||||||||||||
row · not-accessible · current Inputs entry containing objects of an input of a particular databus device. Note that this table has two indexes. sdbDevIdIndex to identify a particular device and sdbDevTotalsIndex to identify a particular input of the device identified by sdbDevIdIndex. | |||||||||||||||||||||
| CsdbDevTotalsIndex | 1.3.6.1.4.1.31034.12.1.1.2.11.1.1.1 | Integer32 (1..54) | NA | ||||||||||||||||||
column · Integer32 (1..54) · not-accessible · current A unique value for each input. Its value ranges between 1 and the value of sdbDevCfPhases. | |||||||||||||||||||||
| CsdbDevTotalsKWhTotal | 1.3.6.1.4.1.31034.12.1.1.2.11.1.1.2 | KiloWattHour | RO | ||||||||||||||||||
column · KiloWattHour · read-only · current Total kWh value of an input. This value can not be reset.
| |||||||||||||||||||||
| CsdbDevTotalsPowerFactor | 1.3.6.1.4.1.31034.12.1.1.2.11.1.1.3 | CentiPercent | RO | ||||||||||||||||||
column · CentiPercent · read-only · current Power factor of input. The power factor of an AC power system is defined as the ratio of the real or active power to the apparent power and is a number between 0 and 1. This value is expressed as a percentage between 0% and 100%.
| |||||||||||||||||||||
| CsdbDevTotalsActualCurrent | 1.3.6.1.4.1.31034.12.1.1.2.11.1.1.4 | CentiAmpere | RO | ||||||||||||||||||
column · CentiAmpere · read-only · current Actual apparent, RMS current.
| |||||||||||||||||||||
| CsdbDevTotalsPeakCurrent | 1.3.6.1.4.1.31034.12.1.1.2.11.1.1.5 | CentiAmpere | RO | ||||||||||||||||||
column · CentiAmpere · read-only · current Peak apparent, RMS current. Highest value since last reset of the alerts.
| |||||||||||||||||||||
| CsdbDevTotalsPowerVoltAmpere | 1.3.6.1.4.1.31034.12.1.1.2.11.1.1.6 | Integer32 (0..327680) | RO | ||||||||||||||||||
column · Integer32 (0..327680) · read-only · current Calculated apparent power.
| |||||||||||||||||||||
| CsdbDevTotalsPowerWatt | 1.3.6.1.4.1.31034.12.1.1.2.11.1.1.7 | Integer32 (0..327680) | RO | ||||||||||||||||||
column · Integer32 (0..327680) · read-only · current Calculated real power.
| |||||||||||||||||||||
| CsdbDevTotalsNeutralCurrent | 1.3.6.1.4.1.31034.12.1.1.2.11.1.1.8 | CentiAmpere | RO | ||||||||||||||||||
column · CentiAmpere · read-only · current Neutral current of phases.
| |||||||||||||||||||||
| CsdbDevTotalsNeutralPeak | 1.3.6.1.4.1.31034.12.1.1.2.11.1.1.9 | CentiAmpere | RO | ||||||||||||||||||
column · CentiAmpere · read-only · current Peak neutral current of phases.
| |||||||||||||||||||||
| CsdbDevTotalsNeutralMaxAmps | 1.3.6.1.4.1.31034.12.1.1.2.11.1.1.10 | CentiAmpere | RW | ||||||||||||||||||
column · CentiAmpere · read-write · current Maximum neutral current. Should last at least sdbDevStPeakDuration ms before triggering an alert.
| |||||||||||||||||||||
| CsdbDevTotalsResidualMaxAmps | 1.3.6.1.4.1.31034.12.1.1.2.11.1.1.11 | CentiAmpere | RW | ||||||||||||||||||
column · CentiAmpere · read-write · current Maximum residual current. Should last at least sdbDevStPeakDuration ms before triggering an alert.
| |||||||||||||||||||||
| NsdbMIBConformance | 1.3.6.1.4.1.31034.12.1.2 | ||||||||||||||||||||
| NsdbMIBCompliances | 1.3.6.1.4.1.31034.12.1.2.1 | ||||||||||||||||||||
| MsdbMIBCompliance | 1.3.6.1.4.1.31034.12.1.2.1.1 | ||||||||||||||||||||
compliance · current The requirements for conformance to the SCHLEIFENBAUER-DATABUS-MIB. | |||||||||||||||||||||
| NsdbMIBGroups | 1.3.6.1.4.1.31034.12.1.2.2 | ||||||||||||||||||||
| GsdbMIBNotificationGroup | 1.3.6.1.4.1.31034.12.1.2.2.1 | ||||||||||||||||||||
group · current A collection of notifications.
| |||||||||||||||||||||
| GsdbMIBDevIdGroup | 1.3.6.1.4.1.31034.12.1.2.2.3 | ||||||||||||||||||||
group · current A collection of objects providing identification information about the device.
| |||||||||||||||||||||
| GsdbMIBDevCfGroup | 1.3.6.1.4.1.31034.12.1.2.2.4 | ||||||||||||||||||||
group · current A collection of objects providing configuration information about the device. | |||||||||||||||||||||
| GsdbMIBDevSsGroup | 1.3.6.1.4.1.31034.12.1.2.2.5 | ||||||||||||||||||||
group · current A collection of objects providing status information about the device.
| |||||||||||||||||||||
| GsdbMIBDevRsGroup | 1.3.6.1.4.1.31034.12.1.2.2.6 | ||||||||||||||||||||
group · current Groups resettable attributes op the device. | |||||||||||||||||||||
| GsdbMIBDevStGroup | 1.3.6.1.4.1.31034.12.1.2.2.7 | ||||||||||||||||||||
group · current A collection of objects providing the actual settings about the device.
| |||||||||||||||||||||
| GsdbMIBDevInGroup | 1.3.6.1.4.1.31034.12.1.2.2.8 | ||||||||||||||||||||
group · current A collection of objects providing the actual input measurements of the device. | |||||||||||||||||||||
| GsdbMIBDevOutGroup | 1.3.6.1.4.1.31034.12.1.2.2.9 | ||||||||||||||||||||
group · current A collection of objects providing the actual outlet measurements of the device.
| |||||||||||||||||||||
| GsdbMIBDevOutMtGroup | 1.3.6.1.4.1.31034.12.1.2.2.10 | ||||||||||||||||||||
group · current A collection of objects providing the actual outlet measurements of the device. | |||||||||||||||||||||
| GsdbMIBDevOutSwGroup | 1.3.6.1.4.1.31034.12.1.2.2.11 | ||||||||||||||||||||
group · current A collection of objects providing the actual outlet measurements of the device. | |||||||||||||||||||||
| GsdbMIBDevSensorGroup | 1.3.6.1.4.1.31034.12.1.2.2.12 | ||||||||||||||||||||
group · current A collection of objects providing the actual environmental measurements of the device. | |||||||||||||||||||||
| GsdbMIBMgmtStatusGroup | 1.3.6.1.4.1.31034.12.1.2.2.13 | ||||||||||||||||||||
group · current A collection of objects providing management status information about the databus. | |||||||||||||||||||||
| GsdbMIBMgmtControlGroup | 1.3.6.1.4.1.31034.12.1.2.2.14 | ||||||||||||||||||||
group · current A collection of objects providing management control information about the databus. | |||||||||||||||||||||
| GsdbMIBDevPerformanceGroup | 1.3.6.1.4.1.31034.12.1.2.2.15 | ||||||||||||||||||||
group · current A collection of objects providing performance information about the MCU | |||||||||||||||||||||
Textual conventions
CentiAmpereInteger32 (0..327680)Display hint:
d-2Data type for reporting measurements and thresholds associated with current sensors. If the underlying hardware sensor indicates 1.1 A, then the SNMP agent will report a value of 110 CentiAmpere.
CentiCelsiusInteger32 (0..9900)Display hint:
d-2Data type for reporting sensor readings associated with temperature sensors. If the underlying hardware sensor indicates 20.1 degrees Celsius, then the SNMP agent will report a value of 2010 CentiCelsius.
CentiPercentInteger32 (0..10000)Display hint:
d-2Data type for reporting calculated percentages. If the calculated percentage is 98.3%, then the SNMP agent will report a value of 9830 CentiPercent.
CentiValueInteger32 (0..327680)Display hint:
d-2Data type for reporting generic measurements associated with environmental sensors. If the underlying hardware sensor indicates 21.1 degrees Celsius, then the SNMP agent will report a value of 2110 CentiValue.
CentiVoltInteger32 (0..327680)Display hint:
d-2Data type for reporting measurements and thresholds associated with voltage sensors. If the underlying hardware sensor indicates 231.1 V, then the SNMP agent will report a value of 23110 CentiVolt.
KiloWattHourInteger32 (0..16777215)Display hint:
dData type for reporting measurements associated with energy accumulation sensors. If the underlying hardware sensor indicates 1 kWh, then the SNMP agent will report a value of 1 kWh.
MilliSecondInteger32Display hint:
dDuration in milliseconds
SecondInteger32Display hint:
dDuration in seconds.
Traps / Notifications
- sdbDevSsBranchCurrentAlertDetected
1.3.6.1.4.1.31034.12.1.0.11 - sdbDevSsBranchVoltageAlertDetected
1.3.6.1.4.1.31034.12.1.0.12 - sdbDevSsDeviceStatusCodeChanged
1.3.6.1.4.1.31034.12.1.0.1 - sdbDevSsHardwareAlertDetected
1.3.6.1.4.1.31034.12.1.0.15 - sdbDevSsInputCurrentAlertDetected
1.3.6.1.4.1.31034.12.1.0.3 - sdbDevSsInputCurrentDropAlertDetected
1.3.6.1.4.1.31034.12.1.0.7 - sdbDevSsInputVoltageAlertDetected
1.3.6.1.4.1.31034.12.1.0.5 - sdbDevSsNeutralCurrentAlertDetected
1.3.6.1.4.1.31034.12.1.0.13 - sdbDevSsOutletCurrentAlertDetected
1.3.6.1.4.1.31034.12.1.0.4 - sdbDevSsOutletCurrentDropAlertDetected
1.3.6.1.4.1.31034.12.1.0.6 - sdbDevSsOutletVoltageDropAlertDetected
1.3.6.1.4.1.31034.12.1.0.10 - sdbDevSsResidualCurrentAlertDetected
1.3.6.1.4.1.31034.12.1.0.14 - sdbDevSsSensorChangeAlertDetected
1.3.6.1.4.1.31034.12.1.0.8 - sdbDevSsTemperatureAlertDetected
1.3.6.1.4.1.31034.12.1.0.2 - sdbMgmtStsRingStateChanged
1.3.6.1.4.1.31034.12.1.0.9