RITTAL-CMC-TC-MIB
Rittal GmbH & Co. KGsnmptranslate -m RITTAL-CMC-TC-MIB -Tpsnmpwalk -v2c -c <community> -m RITTAL-CMC-TC-MIB <host> 1.3.6.1.4.1.2606Imports
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
|---|---|
| SNMPv2-MIB | sysContact, sysDescr, sysLocation, sysName |
| SNMPv2-SMI | Bits, Integer32, IpAddress, MODULE-IDENTITY, MibIdentifier, OBJECT-IDENTITY, OBJECT-TYPE, TRAP-TYPE, TimeTicks, Unsigned32, enterprises, iso |
| SNMPv2-TC | DisplayString, PhysAddress, TEXTUAL-CONVENTION |
OID tree
| Name | OID | Type | Access | Status | Example | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Nrittal | 1.3.6.1.4.1.2606 | ||||||||||||||||||||
| NcmcTc | 1.3.6.1.4.1.2606.4 | ||||||||||||||||||||
| !alarmSensorUnit1 | 1.3.6.1.4.1.2606.4.0.1 | ||||||||||||||||||||
notification Alarm of sensor unit 1 | |||||||||||||||||||||
| !alarmSensorUnit2 | 1.3.6.1.4.1.2606.4.0.2 | ||||||||||||||||||||
notification Alarm of sensor unit 2 | |||||||||||||||||||||
| !alarmSensorUnit3 | 1.3.6.1.4.1.2606.4.0.3 | ||||||||||||||||||||
notification Alarm of sensor unit 3 | |||||||||||||||||||||
| !alarmSensorUnit4 | 1.3.6.1.4.1.2606.4.0.4 | ||||||||||||||||||||
notification Alarm of sensor unit 4 | |||||||||||||||||||||
| !alarmUnit1 | 1.3.6.1.4.1.2606.4.0.5 | ||||||||||||||||||||
notification Alarm of unit 1
| |||||||||||||||||||||
| !alarmUnit2 | 1.3.6.1.4.1.2606.4.0.6 | ||||||||||||||||||||
notification Alarm of unit 2
| |||||||||||||||||||||
| !alarmUnit3 | 1.3.6.1.4.1.2606.4.0.7 | ||||||||||||||||||||
notification Alarm of unit 3
| |||||||||||||||||||||
| !alarmUnit4 | 1.3.6.1.4.1.2606.4.0.8 | ||||||||||||||||||||
notification Alarm of unit 4
| |||||||||||||||||||||
| !alarmValues | 1.3.6.1.4.1.2606.4.0.9 | ||||||||||||||||||||
notification Alarm of values measured by external card
| |||||||||||||||||||||
| !configChanged | 1.3.6.1.4.1.2606.4.0.10 | ||||||||||||||||||||
notification The configuration of the cmc has changed, this trap is send if new setup is saved. Configuration can be changed by Terminal, Telnet, Web or SNMP *** NOT IMPLEMENTED ***
| |||||||||||||||||||||
| NcmcTcMibRev | 1.3.6.1.4.1.2606.4.1 | ||||||||||||||||||||
| ScmcTcMibMajRev | 1.3.6.1.4.1.2606.4.1.1 | INTEGER (1..65535) | RO | mandatory | |||||||||||||||||
scalar · INTEGER (1..65535) · read-only · mandatory The Major Revision level. A change in the major revision level represents a major change in the architecture of the MIB. A change in the major revision level may indicate a significant change in the information, correct interpretation of data may require a MIB document with the same major revision level. | |||||||||||||||||||||
| ScmcTcMibMinRev | 1.3.6.1.4.1.2606.4.1.2 | INTEGER (0..65535) | RO | mandatory | |||||||||||||||||
scalar · INTEGER (0..65535) · read-only · mandatory The Minor Revision level. A change in the minor revision level may represent some minor additional support, no changes to any pre-existing information has occurred. | |||||||||||||||||||||
| ScmcTcMibCondition | 1.3.6.1.4.1.2606.4.1.3 | INTEGER | RO | mandatory | ok(2) | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The overall condition (status) of the system represented by
this MIB.
(2) OK
(3) a minor problem, warning condition (yellow LED on CMC)
(4) a major problem (red LED on CMC)
(5) configuration of sensor units changed or
unit detected (red/yellow/green LED on CMC)
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NcmcTcStatus | 1.3.6.1.4.1.2606.4.2 | ||||||||||||||||||||
| ScmcTcStatusDeviceCMC | 1.3.6.1.4.1.2606.4.2.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory General Status of CMC-TC unit itself (1) failed (2) OK
| |||||||||||||||||||||
| ScmcTcUnitsConnected | 1.3.6.1.4.1.2606.4.2.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Number of sensor units connected to the CMC, Port 1 to 4 | |||||||||||||||||||||
| NcmcTcStatusSensorUnit1 | 1.3.6.1.4.1.2606.4.2.3 | ||||||||||||||||||||
| ScmcTcUnit1TypeOfDevice | 1.3.6.1.4.1.2606.4.2.3.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Type of sensor unit connected to port 1
| |||||||||||||||||||||
| ScmcTcUnit1Text | 1.3.6.1.4.1.2606.4.2.3.2 | DisplayString (SIZE (0..10)) | RW | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..10)) · read-write · mandatory Descriptional text for sensor unit connected to port 1 | |||||||||||||||||||||
| ScmcTcUnit1Serial | 1.3.6.1.4.1.2606.4.2.3.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Serialnumber of sensor unit connected to port 1 | |||||||||||||||||||||
| ScmcTcUnit1Status | 1.3.6.1.4.1.2606.4.2.3.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory General Status sensor unit connected to port 1 (1) OK (2) error, e. g. value overflow (3) configuration of sensor unit has changed, confirmation required (4) Quit from sensor unit to confirm configuration changes (5) timeout of sensor unit, confirmation required to unload this unit (6) sensor unit detected, needs to be confirmed (7) unit is not available (8) supply voltage is too low
| |||||||||||||||||||||
| NcmcTcStatusUnit1Sensors | 1.3.6.1.4.1.2606.4.2.3.5 | ||||||||||||||||||||
| ScmcTcUnit1NumberOfSensors | 1.3.6.1.4.1.2606.4.2.3.5.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Number of sensors connected to sensor unit 1 | |||||||||||||||||||||
| TcmcTcUnit1SensorTable | 1.3.6.1.4.1.2606.4.2.3.5.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Headline of sensor table | |||||||||||||||||||||
| RcmcTcUnit1SensorEntry | 1.3.6.1.4.1.2606.4.2.3.5.2.1 | NA | mandatory | ||||||||||||||||||
| Cunit1SensorIndex | 1.3.6.1.4.1.2606.4.2.3.5.2.1.1 | INTEGER (1..65535) | RO | mandatory | 1 | ||||||||||||||||
column · INTEGER (1..65535) · read-only · mandatory Index for the list of value entries. Its value ranges between 1 and the value of cmcTcUnit1NumberOfSensors. Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cunit1SensorType | 1.3.6.1.4.1.2606.4.2.3.5.2.1.2 | INTEGER | RO | mandatory | leakage(23) | ||||||||||||||||
column · INTEGER · read-only · mandatory Type of sensor which is connected to sensor unit 1 to sensor[unit1SensorIndex]
1: no sensor connected
2: sensor failure
3: value overflow
4: sensor type 1, access sensor
5: sensor type 2, vibration sensor
6: sensor type 3, motion sensor
7: sensor type 4, smoke sensor
8: sensor type 5, air flow sensor
9: sensor type 6, reserved
10: sensor type 7, temperature sensor
11: sensor type 8, 4..20mA sensor
12: sensor type 9, humidity sensor
13: user sensor with normally opened contact
14: user sensor with normally closed contact
15: door locked sensor from locking device
16: remote unlock sensor (e.g. external keypad)
17: voltage sensor, indicates status of main voltage (OK, NOK)
18: voltage value
19: fan status, from CMC-TC-FAS-Unit
20: cardreader or keypad, connected to I2C port
21: duty cycle of fan, FCS-Unit
22: status of fan, FCS-Unit
23: leakage sensor
24: warning, RittalTopTherm(RTT)-Unit
25: alarm, RittalTopTherm-Unit
26: temperature difference filter monitor, RTT-Unit
27: heatflow RCT-Unit
28: alarm RCT-Unit
29: warning RCT-Unit
30: actual current*10, PSM-Unit
31: status PSM-Unit
32: position PSM-Unit, normal/reversed = circuit 1/2
33: air Flap
34: acoustic sensor
35: DET-AC fault (extinguisher)
36: DET-AC first alarm (extinguisher)
37: DET-AC main alarm (extinguisher)
40-47: RPM Fan 1.1 - Fan 4.2, LCP
48-55: Air temperature 1.1 - 4.2, LCP
56,57: actual temperature 1,2, LCP
58: water inlet temperature, LCP
59: water outlet temperature, LCP
60: water flow
61: fan speed (desired value)
62: status valve, LCP
63: status LCP
64: temperature difference water temperatures
65: control temperature 1, LCP
66: control temperature 2, LCP
67: condensate pump, duration, LCP
68: condensate pump, cycles, LCP
72: total energy*10 (kWh), PSM
73: total power*10 (kW), PSM
74: frequency*10 (Hz), PSM
75: voltage*10 (V), PSM
76: voltage status, PSM
77: current*10 (A), PSM
78: current status, PSM
79: power*10 (kW) per phase, PSM
80: energy*10 (kWh) per phase, PSM
81: temporary energy*10 (kWh) per phase, PSM
100: temperature sensor, wireless
101: temperature sensor (combi), wireless
102: humidity sensor, wireless
103: access sensor, wireless
104: user sensor with normally opened contact, wireless
105: user sensor with normally closed contact, wireless
106: analog sensor 4..20mA, wireless
Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cunit1SensorText | 1.3.6.1.4.1.2606.4.2.3.5.2.1.3 | DisplayString (SIZE (0..20)) | RW | mandatory | Leakage Sensor | ||||||||||||||||
column · DisplayString (SIZE (0..20)) · read-write · mandatory Descriptional text for each sensor (entry in the table) Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cunit1SensorStatus | 1.3.6.1.4.1.2606.4.2.3.5.2.1.4 | INTEGER | RO | mandatory | ok(4) | ||||||||||||||||
column · INTEGER · read-only · mandatory Actual status of the sensor
Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cunit1SensorValue | 1.3.6.1.4.1.2606.4.2.3.5.2.1.5 | INTEGER | RO | mandatory | 0 | ||||||||||||||||
column · INTEGER · read-only · mandatory Value of sensor Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cunit1SensorSetHigh | 1.3.6.1.4.1.2606.4.2.3.5.2.1.6 | INTEGER | RW | mandatory | 0 | ||||||||||||||||
column · INTEGER · read-write · mandatory Value for high setpoint of sensor Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cunit1SensorSetLow | 1.3.6.1.4.1.2606.4.2.3.5.2.1.7 | INTEGER | RW | mandatory | 0 | ||||||||||||||||
column · INTEGER · read-write · mandatory Value for low setpoint of sensor, also used as alarm delay Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cunit1SensorSetWarn | 1.3.6.1.4.1.2606.4.2.3.5.2.1.8 | INTEGER | RW | mandatory | 0 | ||||||||||||||||
column · INTEGER · read-write · mandatory Value for warning setpoint of sensor, also used as fan threshold Example values from LibreNMS test devices
| |||||||||||||||||||||
| NcmcTcStatusUnit1Outputs | 1.3.6.1.4.1.2606.4.2.3.6 | ||||||||||||||||||||
| ScmcTcUnit1NumberOfOutputs | 1.3.6.1.4.1.2606.4.2.3.6.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Number of outputs available on sensor unit 1 | |||||||||||||||||||||
| TcmcTcUnit1OutputTable | 1.3.6.1.4.1.2606.4.2.3.6.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Headline of output table | |||||||||||||||||||||
| RcmcTcUnit1OutputEntry | 1.3.6.1.4.1.2606.4.2.3.6.2.1 | NA | mandatory | ||||||||||||||||||
| Cunit1OutputIndex | 1.3.6.1.4.1.2606.4.2.3.6.2.1.1 | INTEGER (1..65535) | RO | mandatory | |||||||||||||||||
column · INTEGER (1..65535) · read-only · mandatory Index for the list of output entries. Its value ranges between 1 and the value of cmcTcUnit1NumberOfOutputs. | |||||||||||||||||||||
| Cunit1OutputType | 1.3.6.1.4.1.2606.4.2.3.6.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Type of output which is connected to sensor unit 1 to output[unit1OutputIndex] 1: no output connected 2: output failure 3: value overflow 4: output type 1, door locking TS8,Ergoform 5: output type 2, universal lock 1, lock with power 6: output type 3, universal lock 2, unlock with power 7: output type 4, fan relay 8: output type 5, fan controlled 9: output type 6, universal relay output 10: output type 7, room door lock 11: output type 8, power output 12: output type 9, door lock with Master key 13: output type 10, door lock FR(i) 14: setpoint (FCS, LCP) 15: setpoint temperature monitoring (LCP) 16: hysteresis of setpoint (LCP) 17: command for remote control of RCT 18: relay PSM, 1=On, 0=Off 19: high setpoint current monitoring PSM 20: low setpoint current monitoring PSM 21: setpoint temperature RTT 22: setpoint temperature monitoring RTT 23: power output 20A 30: control mode, LCP 31: min fan speed (fan control), LCP 32: min delta T (fan control), LCP 33: max delta T (fan control), LCP 34: PID controller, KP, LCP 35: PID controller, KI, LCP 36 PID controller, KD, LCP 37 flowrate flowmeter, LCP 38: cw value of water (default: 4187), LCP 39: deltaT, LCP 40: control mode, LCP 42: setpoint high voltage PSM 43: setpoint low voltage PSM 44: setpoint high current PSM 45: setpoint low current PSM 46: command PSM
| |||||||||||||||||||||
| Cunit1OutputText | 1.3.6.1.4.1.2606.4.2.3.6.2.1.3 | DisplayString (SIZE (0..20)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..20)) · read-write · mandatory Descriptional text for each output (entry in the table) | |||||||||||||||||||||
| Cunit1OutputStatus | 1.3.6.1.4.1.2606.4.2.3.6.2.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Actual status of the output
| |||||||||||||||||||||
| Cunit1OutputValue | 1.3.6.1.4.1.2606.4.2.3.6.2.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Value for output | |||||||||||||||||||||
| Cunit1OutputSet | 1.3.6.1.4.1.2606.4.2.3.6.2.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Command for output
| |||||||||||||||||||||
| Cunit1OutputConfig | 1.3.6.1.4.1.2606.4.2.3.6.2.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Configuration for output 1: disable remote control (e.g. keypad) 2: enable remote control
| |||||||||||||||||||||
| Cunit1OutputDelay | 1.3.6.1.4.1.2606.4.2.3.6.2.1.8 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Unsigned Value for delay, after this time the output will fall into the previous state | |||||||||||||||||||||
| Cunit1OutputTimeoutAction | 1.3.6.1.4.1.2606.4.2.3.6.2.1.9 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory State for output if timeout (RS422) occurs
| |||||||||||||||||||||
| NcmcTcStatusUnit1Msg | 1.3.6.1.4.1.2606.4.2.3.7 | ||||||||||||||||||||
| ScmcTcUnit1NumberOfMsgs | 1.3.6.1.4.1.2606.4.2.3.7.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Number of messages that can be created with sensor unit 1 | |||||||||||||||||||||
| TcmcTcUnit1MsgTable | 1.3.6.1.4.1.2606.4.2.3.7.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Headline of message table | |||||||||||||||||||||
| RcmcTcUnit1MsgEntry | 1.3.6.1.4.1.2606.4.2.3.7.2.1 | NA | mandatory | ||||||||||||||||||
| Cunit1MsgIndex | 1.3.6.1.4.1.2606.4.2.3.7.2.1.1 | INTEGER (1..65535) | RO | mandatory | |||||||||||||||||
column · INTEGER (1..65535) · read-only · mandatory Index for the list of message entries. Its value ranges between 1 and the value of cmcTcUnit1NumberOfMsgs. | |||||||||||||||||||||
| Cunit1MsgText | 1.3.6.1.4.1.2606.4.2.3.7.2.1.2 | DisplayString (SIZE (0..20)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..20)) · read-write · mandatory Descriptional text for each message (entry in the table) | |||||||||||||||||||||
| Cunit1MsgStatus | 1.3.6.1.4.1.2606.4.2.3.7.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Actual message status 1: not available 2: configuration has changed (sensor new, changed, lost) 3: error 4: OK 5: alarm, e.g. smoke, vibration... 6: warning of analog value, value reached warning threshold 7: analog value too low, value reached low threshold 8: analog value too high, value reached high threshold 9: output is set to OFF 10: output is set to ON 11: door is open 12: door is closed 13: door is locked 14: door is unlocked by remote input, e.g. external cardreader 15: door is unlocked by reader or keypad connected to I2C 16: door is unlocked by SNMP set command (unit1OutputSet) 17: door is unlocked by WEB 18: door is unlocked by timer 19: no access, wrong keycode or cardnumber 20: orientation of PSM-Unit is circuit 1 21: orientation of PSM-Unit is circuit 2 22: battery low, wireless sensor
| |||||||||||||||||||||
| Cunit1MsgRelay | 1.3.6.1.4.1.2606.4.2.3.7.2.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Setup of Alarm relay for this message/alarm 1: no switching of alarm relay 2: switching of alarm relay
| |||||||||||||||||||||
| Cunit1MsgBeeper | 1.3.6.1.4.1.2606.4.2.3.7.2.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Setup of Alarm beeper for this alarm 1: no audible alarm 2: audible alarm
| |||||||||||||||||||||
| Cunit1MsgTrap1 | 1.3.6.1.4.1.2606.4.2.3.7.2.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Trap receiver 1 activated
| |||||||||||||||||||||
| Cunit1MsgTrap2 | 1.3.6.1.4.1.2606.4.2.3.7.2.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Trap receiver 2 activated
| |||||||||||||||||||||
| Cunit1MsgTrap3 | 1.3.6.1.4.1.2606.4.2.3.7.2.1.8 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Trap receiver 3 activated
| |||||||||||||||||||||
| Cunit1MsgTrap4 | 1.3.6.1.4.1.2606.4.2.3.7.2.1.9 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Trap receiver 4 and Event Logging activated
| |||||||||||||||||||||
| Cunit1MsgQuit | 1.3.6.1.4.1.2606.4.2.3.7.2.1.10 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Reset of this alarm 1: auto 2: manual, alarm needs confirmation, e. g. with 'C' key
| |||||||||||||||||||||
| NcmcTcStatusSensorUnit2 | 1.3.6.1.4.1.2606.4.2.4 | ||||||||||||||||||||
| ScmcTcUnit2TypeOfDevice | 1.3.6.1.4.1.2606.4.2.4.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Type of sensor unit connected to port 2
| |||||||||||||||||||||
| ScmcTcUnit2Text | 1.3.6.1.4.1.2606.4.2.4.2 | DisplayString (SIZE (0..10)) | RW | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..10)) · read-write · mandatory Descriptional text for sensor unit connected to port 2 | |||||||||||||||||||||
| ScmcTcUnit2Serial | 1.3.6.1.4.1.2606.4.2.4.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Serialnumber of sensor unit connected to port 2 | |||||||||||||||||||||
| ScmcTcUnit2Status | 1.3.6.1.4.1.2606.4.2.4.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory General Status sensor unit connected to port 2 (1) OK (2) error (3) configuration of sensor unit has changed, confirmation required (4) Quit from sensor unit to confirm configuration changes (5) timeout of sensor unit, confirmation required (6) sensor unit detected, needs to be confirmed (8) supply voltage is too low
| |||||||||||||||||||||
| NcmcTcStatusUnit2Sensors | 1.3.6.1.4.1.2606.4.2.4.5 | ||||||||||||||||||||
| ScmcTcUnit2NumberOfSensors | 1.3.6.1.4.1.2606.4.2.4.5.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Number of sensors connected to sensor unit 2 | |||||||||||||||||||||
| TcmcTcUnit2SensorTable | 1.3.6.1.4.1.2606.4.2.4.5.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Headline of sensor table | |||||||||||||||||||||
| RcmcTcUnit2SensorEntry | 1.3.6.1.4.1.2606.4.2.4.5.2.1 | NA | mandatory | ||||||||||||||||||
| Cunit2SensorIndex | 1.3.6.1.4.1.2606.4.2.4.5.2.1.1 | INTEGER (1..65535) | RO | mandatory | 1 | ||||||||||||||||
column · INTEGER (1..65535) · read-only · mandatory Index for the list of value entries. Its value ranges between 1 and the value of cmcTcUnit2NumberOfSensors. Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cunit2SensorType | 1.3.6.1.4.1.2606.4.2.4.5.2.1.2 | INTEGER | RO | mandatory | temp1LCP(56) | ||||||||||||||||
column · INTEGER · read-only · mandatory Type of sensor which is connected to sensor unit 2 to sensor[unit2SensorIndex]
1: no sensor connected
2: sensor failure
3: value overflow
4: sensor type 1, access sensor
5: sensor type 2, vibration sensor
6: sensor type 3, motion sensor
7: sensor type 4, smoke sensor
8: sensor type 5, air flow sensor
9: sensor type 6, reserved
10: sensor type 7, temperature sensor
11: sensor type 8, 4..20mA sensor
12: sensor type 9, humidity sensor
13: user sensor with normally opened contact
14: user sensor with normally closed contact
15: door locked sensor from locking device
16: remote unlock sensor (e.g. external keypad)
17: voltage sensor, indicates status of main voltage
18: voltage value
19: fan status
20: cardreader or keypad, connected to I2C port
21: duty cycle of fan, FCS-Unit
22: status of fan, FCS-Unit
23: leakage sensor
24: warning, RittalTopTherm(RTT)-Unit
25: alarm, RittalTopTherm-Unit
26: temperature difference filter monitor, RTT-Unit
27: heatflow RCT-Unit
28: alarm RCT-Unit
29: warning RCT-Unit
30: actual current*10, PSM-Unit
31: status PSM-Unit
32: position PSM-Unit, normal/reversed = circuit 1/2
33: air Flap
34: acoustic sensor
35: DET-AC fault (extinguisher)
36: DET-AC first alarm (extinguisher)
37: DET-AC main alarm (extinguisher)
40-47: RPM Fan 1.1 - Fan 4.2, LCP
48-55: Air temperature 1.1 - 4.2, LCP
56,57: actual temperature 1,2, LCP
58: water inlet temperature, LCP
59: water outlet temperature, LCP
60: water flow
61: fan speed (desired value)
62: status valve, LCP
63: status LCP
64: temperature difference water temperatures
65: control temperature 1, LCP
66: control temperature 2, LCP
67: condensate pump, duration, LCP
68: condensate pump, cycles, LCP
72: total energy*10 (kWh), PSM
73: total power*10 (kW), PSM
74: frequency*10 (Hz), PSM
75: voltage*10 (V), PSM
76: voltage status, PSM
77: current*10 (A), PSM
78: current status, PSM
79: power*10 (kW) per phase, PSM
80: energy*10 (kWh) per phase, PSM
81: temporary energy*10 (kWh) per phase, PSM
100: temperature sensor, wireless
101: temperature sensor (combi), wireless
102: humidity sensor, wireless
103: access sensor, wireless
104: user sensor with normally opened contact, wireless
105: user sensor with normally closed contact, wireless
106: analog sensor 4..20mA, wireless
Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cunit2SensorText | 1.3.6.1.4.1.2606.4.2.4.5.2.1.3 | DisplayString (SIZE (0..20)) | RW | mandatory | Server-In-Temperat. | ||||||||||||||||
column · DisplayString (SIZE (0..20)) · read-write · mandatory Descriptional text for each sensor (entry in the table) Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cunit2SensorStatus | 1.3.6.1.4.1.2606.4.2.4.5.2.1.4 | INTEGER | RO | mandatory | ok(4) | ||||||||||||||||
column · INTEGER · read-only · mandatory Actual status of the sensor
Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cunit2SensorValue | 1.3.6.1.4.1.2606.4.2.4.5.2.1.5 | INTEGER | RO | mandatory | 16 | ||||||||||||||||
column · INTEGER · read-only · mandatory Value of sensor Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cunit2SensorSetHigh | 1.3.6.1.4.1.2606.4.2.4.5.2.1.6 | INTEGER | RW | mandatory | 40 | ||||||||||||||||
column · INTEGER · read-write · mandatory Value for high setpoint of sensor Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cunit2SensorSetLow | 1.3.6.1.4.1.2606.4.2.4.5.2.1.7 | INTEGER | RW | mandatory | 10 | ||||||||||||||||
column · INTEGER · read-write · mandatory Value for low setpoint of sensor, also used as alarm delay Example values from LibreNMS test devices
| |||||||||||||||||||||
| Cunit2SensorSetWarn | 1.3.6.1.4.1.2606.4.2.4.5.2.1.8 | INTEGER | RW | mandatory | 30 | ||||||||||||||||
column · INTEGER · read-write · mandatory Value for warning setpoint of sensor, also used as fan threshold Example values from LibreNMS test devices
| |||||||||||||||||||||
| NcmcTcStatusUnit2Outputs | 1.3.6.1.4.1.2606.4.2.4.6 | ||||||||||||||||||||
| ScmcTcUnit2NumberOfOutputs | 1.3.6.1.4.1.2606.4.2.4.6.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Number of outputs available on sensor unit 2 | |||||||||||||||||||||
| TcmcTcUnit2OutputTable | 1.3.6.1.4.1.2606.4.2.4.6.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Headline of output table | |||||||||||||||||||||
| RcmcTcUnit2OutputEntry | 1.3.6.1.4.1.2606.4.2.4.6.2.1 | NA | mandatory | ||||||||||||||||||
| Cunit2OutputIndex | 1.3.6.1.4.1.2606.4.2.4.6.2.1.1 | INTEGER (1..65535) | RO | mandatory | |||||||||||||||||
column · INTEGER (1..65535) · read-only · mandatory Index for the list of output entries. Its value ranges between 1 and the value of cmcTcUnit2NumberOfOutputs. | |||||||||||||||||||||
| Cunit2OutputType | 1.3.6.1.4.1.2606.4.2.4.6.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Type of output which is connected to sensor unit 2 to output[unit2OutputIndex] 1: no output connected 2: output failure 3: value overflow 4: output type 1, door locking TS8,Ergoform 5: output type 2, universal lock 1, lock with power 6: output type 3, universal lock 2, unlock with power 7: output type 4, fan relay 8: output type 5, fan controlled 9: output type 6, universal relay output 10: output type 7, room door lock 11: output type 8, power output 12: output type 9, door lock with Master key 13: output type 10, door lock FR(i) 14: setpoint (FCS, RTT) 15: setpoint temperature monitoring (RTT) 16: hysteresis of setpoint (RCT) 17: command for remote control of RCT 18: relay PSM, 1=On, 0=Off 19: high setpoint current monitoring PSM 20: low setpoint current monitoring PSM 21: setpoint temperature RTT 22: setpoint temperature monitoring RTT 23: power output 20A 30: control mode LCP 31: min fan speed (fan control) LCP 32: min delta T (fan control) LCP 33: max delta T (fan control) LCP 34: PID controller, KP, LCP 35: PID controller, KI, LCP 36 PID controller, KD, LCP 37 flowrate flowmeter, LCP 38: cw value of water (default: 4187) LCP 39: deltaT, LCP 40: control mode, LCP 42: setpoint high voltage PSM 43: setpoint low voltage PSM 44: setpoint high current PSM 45: setpoint low current PSM 46: command PSM
| |||||||||||||||||||||
| Cunit2OutputText | 1.3.6.1.4.1.2606.4.2.4.6.2.1.3 | DisplayString (SIZE (0..20)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..20)) · read-write · mandatory Descriptional text for each output (entry in the table) | |||||||||||||||||||||
| Cunit2OutputStatus | 1.3.6.1.4.1.2606.4.2.4.6.2.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Actual status of the output
| |||||||||||||||||||||
| Cunit2OutputValue | 1.3.6.1.4.1.2606.4.2.4.6.2.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Signed value for output | |||||||||||||||||||||
| Cunit2OutputSet | 1.3.6.1.4.1.2606.4.2.4.6.2.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Command for output
| |||||||||||||||||||||
| Cunit2OutputConfig | 1.3.6.1.4.1.2606.4.2.4.6.2.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Configuration for output 1: disable remote control (e.g. keypad) 2: enable remote control
| |||||||||||||||||||||
| Cunit2OutputDelay | 1.3.6.1.4.1.2606.4.2.4.6.2.1.8 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Unsigned Value for delay, after this time the output will fall into the previous state | |||||||||||||||||||||
| Cunit2OutputTimeoutAction | 1.3.6.1.4.1.2606.4.2.4.6.2.1.9 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory State for output if timeout (RS422) occurs
| |||||||||||||||||||||
| NcmcTcStatusUnit2Msg | 1.3.6.1.4.1.2606.4.2.4.7 | ||||||||||||||||||||
| ScmcTcUnit2NumberOfMsgs | 1.3.6.1.4.1.2606.4.2.4.7.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Number of alarms that can be created with sensor unit 2 | |||||||||||||||||||||
| TcmcTcUnit2MsgTable | 1.3.6.1.4.1.2606.4.2.4.7.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Headline of message table | |||||||||||||||||||||
| RcmcTcUnit2MsgEntry | 1.3.6.1.4.1.2606.4.2.4.7.2.1 | NA | mandatory | ||||||||||||||||||
| Cunit2MsgIndex | 1.3.6.1.4.1.2606.4.2.4.7.2.1.1 | INTEGER (1..65535) | RO | mandatory | |||||||||||||||||
column · INTEGER (1..65535) · read-only · mandatory Index for the list of alarm entries. Its value ranges between 1 and the value of cmcTcUnit2NumberOfMsgs. | |||||||||||||||||||||
| Cunit2MsgText | 1.3.6.1.4.1.2606.4.2.4.7.2.1.2 | DisplayString (SIZE (0..20)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..20)) · read-write · mandatory Descriptional text for each message (entry in the table) | |||||||||||||||||||||
| Cunit2MsgStatus | 1.3.6.1.4.1.2606.4.2.4.7.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Actual message status 1: not available 2: configuration has changed (sensor new, changed, lost) 3: error 4: OK 5: alarm, e.g. smoke, vibration... 6: warning of analog value, value reached warning threshold 7: analog value too low, value reached low threshold 8: analog value too high, value reached high threshold 9: output is set to OFF 10: output is set to ON 11: door is open 12: door is closed 13: door is locked 14: door is unlocked by remote input, e.g. external cardreader 15: door is unlocked by reader or keypad connected to I2C 16: door is unlocked by SNMP set command (unit1OutputSet) 17: door is unlocked by WEB 18: door is unlocked by timer 19: no access, wrong keycode or cardnumber 20: orientation of PSM-Unit is circuit 1 21: orientation of PSM-Unit is circuit 2 22: battery low, wireless sensor
| |||||||||||||||||||||
| Cunit2MsgRelay | 1.3.6.1.4.1.2606.4.2.4.7.2.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Setup of Alarm relay for this alarm 2: no switching of alarm relay 1: switching of alarm relay
| |||||||||||||||||||||
| Cunit2MsgBeeper | 1.3.6.1.4.1.2606.4.2.4.7.2.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Setup of Alarm beeper for this alarm 2: no audible alarm 1: audible alarm
| |||||||||||||||||||||
| Cunit2MsgTrap1 | 1.3.6.1.4.1.2606.4.2.4.7.2.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Trap receiver 1 activated
| |||||||||||||||||||||
| Cunit2MsgTrap2 | 1.3.6.1.4.1.2606.4.2.4.7.2.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Trap receiver 2 activated
| |||||||||||||||||||||
| Cunit2MsgTrap3 | 1.3.6.1.4.1.2606.4.2.4.7.2.1.8 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Trap receiver 3 activated
| |||||||||||||||||||||
| Cunit2MsgTrap4 | 1.3.6.1.4.1.2606.4.2.4.7.2.1.9 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Trap receiver 4 and Event Logging activated
| |||||||||||||||||||||
| Cunit2MsgQuit | 1.3.6.1.4.1.2606.4.2.4.7.2.1.10 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Reset of this alarm 1: auto 2: manual, alarm needs confirmation, e. g. with 'C' key
| |||||||||||||||||||||
| NcmcTcStatusSensorUnit3 | 1.3.6.1.4.1.2606.4.2.5 | ||||||||||||||||||||
| ScmcTcUnit3TypeOfDevice | 1.3.6.1.4.1.2606.4.2.5.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Type of sensor unit connected to port 3
| |||||||||||||||||||||
| ScmcTcUnit3Text | 1.3.6.1.4.1.2606.4.2.5.2 | DisplayString (SIZE (0..10)) | RW | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..10)) · read-write · mandatory Descriptional text for sensor unit connected to port 3 | |||||||||||||||||||||
| ScmcTcUnit3Serial | 1.3.6.1.4.1.2606.4.2.5.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Serialnumber of sensor unit connected to port 3 | |||||||||||||||||||||
| ScmcTcUnit3Status | 1.3.6.1.4.1.2606.4.2.5.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory General Status sensor unit connected to port 3 (1) OK (2) error, e. g. value overflow (3) configuration of sensor unit has changed, confirmation required (4) Quit from sensor unit to confirm configuration changes (5) timeout of sensor unit, confirmation required to unload this unit (6) sensor unit detected, needs to be confirmed (7) unit is not available (8) supply voltage is too low
| |||||||||||||||||||||
| NcmcTcStatusUnit3Sensors | 1.3.6.1.4.1.2606.4.2.5.5 | ||||||||||||||||||||
| ScmcTcUnit3NumberOfSensors | 1.3.6.1.4.1.2606.4.2.5.5.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Number of sensors connected to sensor unit 3 | |||||||||||||||||||||
| TcmcTcUnit3SensorTable | 1.3.6.1.4.1.2606.4.2.5.5.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Headline of sensor table | |||||||||||||||||||||
| RcmcTcUnit3SensorEntry | 1.3.6.1.4.1.2606.4.2.5.5.2.1 | NA | mandatory | ||||||||||||||||||
| Cunit3SensorIndex | 1.3.6.1.4.1.2606.4.2.5.5.2.1.1 | INTEGER (1..65535) | RO | mandatory | |||||||||||||||||
column · INTEGER (1..65535) · read-only · mandatory Index for the list of value entries. Its value ranges between 1 and the value of cmcTcUnit3NumberOfSensors. | |||||||||||||||||||||
| Cunit3SensorType | 1.3.6.1.4.1.2606.4.2.5.5.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Type of sensor which is connected to sensor unit 3 to sensor[unit3SensorIndex]
1: no sensor connected
2: sensor failure
3: value overflow
4: sensor type 1, access sensor
5: sensor type 2, vibration sensor
6: sensor type 3, motion sensor
7: sensor type 4, smoke sensor
8: sensor type 5, air flow sensor
9: sensor type 6, reserved
10: sensor type 7, temperature sensor
11: sensor type 8, 4..20mA sensor
12: sensor type 9, humidity sensor
13: user sensor with normally opened contact
14: user sensor with normally closed contact
15: door locked sensor from locking device
16: remote unlock sensor (e.g. external keypad)
17: voltage sensor, indicates status of main voltage
18: voltage value
19: fan status
20: cardreader or keypad, connected to I2C port
21: duty cycle of fan, FCS-Unit
22: status of fan, FCS-Unit
23: leakage sensor
24: warning, RittalTopTherm(RTT)-Unit
25: alarm, RittalTopTherm-Unit
26: temperature difference filter monitor, RTT-Unit
27: heatflow RCT-Unit
28: alarm RCT-Unit
29: warning RCT-Unit
30: actual current*10, PSM-Unit
31: status PSM-Unit
32: position PSM-Unit, normal/reversed = circuit 1/2
33: air Flap
34: acoustic sensor
35: DET-AC fault (extinguisher)
36: DET-AC first alarm (extinguisher)
37: DET-AC main alarm (extinguisher)
40-47: RPM Fan 1.1 - Fan 4.2, LCP
48-55: Air temperature 1.1 - 4.2, LCP
56,57: actual temperature 1,2, LCP
58: water inlet temperature, LCP
59: water outlet temperature, LCP
60: water flow
61: fan speed (desired value)
62: status valve, LCP
63: status LCP
64: temperature difference water temperatures
65: control temperature 1, LCP
66: control temperature 2, LCP
67: condensate pump, duration, LCP
68: condensate pump, cycles, LCP
72: total energy*10 (kWh), PSM
73: total power*10 (kW), PSM
74: frequency*10 (Hz), PSM
75: voltage*10 (V), PSM
76: voltage status, PSM
77: current*10 (A), PSM
78: current status, PSM
79: power*10 (kW) per phase, PSM
80: energy*10 (kWh) per phase, PSM
81: temporary energy*10 (kWh) per phase, PSM
100: temperature sensor, wireless
101: temperature sensor (combi), wireless
102: humidity sensor, wireless
103: access sensor, wireless
104: user sensor with normally opened contact, wireless
105: user sensor with normally closed contact, wireless
106: analog sensor 4..20mA, wireless
| |||||||||||||||||||||
| Cunit3SensorText | 1.3.6.1.4.1.2606.4.2.5.5.2.1.3 | DisplayString (SIZE (0..20)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..20)) · read-write · mandatory Descriptional text for each sensor (entry in the table) | |||||||||||||||||||||
| Cunit3SensorStatus | 1.3.6.1.4.1.2606.4.2.5.5.2.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Actual status of the sensor
| |||||||||||||||||||||
| Cunit3SensorValue | 1.3.6.1.4.1.2606.4.2.5.5.2.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Value of sensor | |||||||||||||||||||||
| Cunit3SensorSetHigh | 1.3.6.1.4.1.2606.4.2.5.5.2.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Value for high setpoint of sensor | |||||||||||||||||||||
| Cunit3SensorSetLow | 1.3.6.1.4.1.2606.4.2.5.5.2.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Value for low setpoint of sensor | |||||||||||||||||||||
| Cunit3SensorSetWarn | 1.3.6.1.4.1.2606.4.2.5.5.2.1.8 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Value for warning setpoint of sensor, also used as fan threshold | |||||||||||||||||||||
| NcmcTcStatusUnit3Outputs | 1.3.6.1.4.1.2606.4.2.5.6 | ||||||||||||||||||||
| ScmcTcUnit3NumberOfOutputs | 1.3.6.1.4.1.2606.4.2.5.6.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Number of outputs available on sensor unit 3 | |||||||||||||||||||||
| TcmcTcUnit3OutputTable | 1.3.6.1.4.1.2606.4.2.5.6.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Headline of output table | |||||||||||||||||||||
| RcmcTcUnit3OutputEntry | 1.3.6.1.4.1.2606.4.2.5.6.2.1 | NA | mandatory | ||||||||||||||||||
| Cunit3OutputIndex | 1.3.6.1.4.1.2606.4.2.5.6.2.1.1 | INTEGER (1..65535) | RO | mandatory | |||||||||||||||||
column · INTEGER (1..65535) · read-only · mandatory Index for the list of output entries. Its value ranges between 1 and the value of cmcTcUnit3NumberOfOutputs. | |||||||||||||||||||||
| Cunit3OutputType | 1.3.6.1.4.1.2606.4.2.5.6.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Type of output which is connected to sensor unit 3 to output[unit3OutputIndex] 1: no output connected 2: output failure 3: value overflow 4: output type 1, door locking TS8,Ergoform 5: output type 2, universal lock 1, lock with power 6: output type 3, universal lock 2, unlock with power 7: output type 4, fan relay 8: output type 5, fan controlled 9: output type 6, universal relay output 10: output type 7, room door lock 11: output type 8, power output 12: output type 9, door lock with Master key 13: output type 10, door lock FR(i) 14: setpoint (FCS, RTT) 15: setpoint temperature monitoring (RTT) 16: hysteresis of setpoint (RCT) 17: command for remote control of RCT 18: relay PSM, 1=On, 0=Off 19: high setpoint current monitoring PSM 20: low setpoint current monitoring PSM 21: setpoint temperature RTT 22: setpoint temperature monitoring RTT 23: power output 20A 30: control mode LCP 31: min fan speed (fan control) LCP 32: min delta T (fan control) LCP 33: max delta T (fan control) LCP 34: PID controller, KP, LCP 35: PID controller, KI, LCP 36 PID controller, KD, LCP 37 flowrate flowmeter, LCP 38: cw value of water (default: 4187) LCP 39: deltaT, LCP 40: control mode, LCP 42: setpoint high voltage PSM 43: setpoint low voltage PSM 44: setpoint high current PSM 45: setpoint low current PSM 46: command PSM
| |||||||||||||||||||||
| Cunit3OutputText | 1.3.6.1.4.1.2606.4.2.5.6.2.1.3 | DisplayString (SIZE (0..20)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..20)) · read-write · mandatory Descriptional text for each output (entry in the table) | |||||||||||||||||||||
| Cunit3OutputStatus | 1.3.6.1.4.1.2606.4.2.5.6.2.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Actual status of the output
| |||||||||||||||||||||
| Cunit3OutputValue | 1.3.6.1.4.1.2606.4.2.5.6.2.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Value for output | |||||||||||||||||||||
| Cunit3OutputSet | 1.3.6.1.4.1.2606.4.2.5.6.2.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Command for output
| |||||||||||||||||||||
| Cunit3OutputConfig | 1.3.6.1.4.1.2606.4.2.5.6.2.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Configuration for output 1: disable remote control (e.g. keypad) 2: enable remote control
| |||||||||||||||||||||
| Cunit3OutputDelay | 1.3.6.1.4.1.2606.4.2.5.6.2.1.8 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Unsigned Value for delay, after this time the output will fall into the previous state | |||||||||||||||||||||
| Cunit3OutputTimeoutAction | 1.3.6.1.4.1.2606.4.2.5.6.2.1.9 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory State for output if timeout (RS422) occurs
| |||||||||||||||||||||
| NcmcTcStatusUnit3Msg | 1.3.6.1.4.1.2606.4.2.5.7 | ||||||||||||||||||||
| ScmcTcUnit3NumberOfMsgs | 1.3.6.1.4.1.2606.4.2.5.7.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Number of alarms that can be created with sensor unit 3 | |||||||||||||||||||||
| TcmcTcUnit3MsgTable | 1.3.6.1.4.1.2606.4.2.5.7.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Headline of message table | |||||||||||||||||||||
| RcmcTcUnit3MsgEntry | 1.3.6.1.4.1.2606.4.2.5.7.2.1 | NA | mandatory | ||||||||||||||||||
| Cunit3MsgIndex | 1.3.6.1.4.1.2606.4.2.5.7.2.1.1 | INTEGER (1..65535) | RO | mandatory | |||||||||||||||||
column · INTEGER (1..65535) · read-only · mandatory Index for the list of alarm entries. Its value ranges between 1 and the value of cmcTcUnit3NumberOfMsgs. | |||||||||||||||||||||
| Cunit3MsgText | 1.3.6.1.4.1.2606.4.2.5.7.2.1.2 | DisplayString (SIZE (0..20)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..20)) · read-write · mandatory Descriptional text for each message (entry in the table) | |||||||||||||||||||||
| Cunit3MsgStatus | 1.3.6.1.4.1.2606.4.2.5.7.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Actual message status 1: not available 2: configuration has changed (sensor new, changed, lost) 3: error 4: OK 5: alarm, e.g. smoke, vibration... 6: warning of analog value, value reached warning threshold 7: analog value too low, value reached low threshold 8: analog value too high, value reached high threshold 9: output is set to OFF 10: output is set to ON 11: door is open 12: door is closed 13: door is locked 14: door is unlocked by remote input, e.g. external cardreader 15: door is unlocked by reader or keypad connected to I2C 16: door is unlocked by SNMP set command (unit1OutputSet) 17: door is unlocked by WEB 18: door is unlocked by timer 19: no access, wrong keycode or cardnumber 20: orientation of PSM-Unit is circuit 1 21: orientation of PSM-Unit is circuit 2 22: battery low, wireless sensor
| |||||||||||||||||||||
| Cunit3MsgRelay | 1.3.6.1.4.1.2606.4.2.5.7.2.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Setup of Alarm relay for this alarm 1: no switching of alarm relay 2: switching of alarm relay
| |||||||||||||||||||||
| Cunit3MsgBeeper | 1.3.6.1.4.1.2606.4.2.5.7.2.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Setup of Alarm beeper for this alarm 1: no audible alarm 2: audible alarm
| |||||||||||||||||||||
| Cunit3MsgTrap1 | 1.3.6.1.4.1.2606.4.2.5.7.2.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Trap receiver 1 activated
| |||||||||||||||||||||
| Cunit3MsgTrap2 | 1.3.6.1.4.1.2606.4.2.5.7.2.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Trap receiver 2 activated
| |||||||||||||||||||||
| Cunit3MsgTrap3 | 1.3.6.1.4.1.2606.4.2.5.7.2.1.8 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Trap receiver 3 activated
| |||||||||||||||||||||
| Cunit3MsgTrap4 | 1.3.6.1.4.1.2606.4.2.5.7.2.1.9 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Trap receiver 4 and Event Logging activated
| |||||||||||||||||||||
| Cunit3MsgQuit | 1.3.6.1.4.1.2606.4.2.5.7.2.1.10 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Reset of this alarm 1: auto 2: manual, alarm needs confirmation, e. g. with 'C' key
| |||||||||||||||||||||
| NcmcTcStatusSensorUnit4 | 1.3.6.1.4.1.2606.4.2.6 | ||||||||||||||||||||
| ScmcTcUnit4TypeOfDevice | 1.3.6.1.4.1.2606.4.2.6.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Type of sensor unit connected to port 4
| |||||||||||||||||||||
| ScmcTcUnit4Text | 1.3.6.1.4.1.2606.4.2.6.2 | DisplayString (SIZE (0..10)) | RW | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..10)) · read-write · mandatory Descriptional text for sensor unit connected to port 4 | |||||||||||||||||||||
| ScmcTcUnit4Serial | 1.3.6.1.4.1.2606.4.2.6.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Serialnumber of sensor unit connected to port 4 | |||||||||||||||||||||
| ScmcTcUnit4Status | 1.3.6.1.4.1.2606.4.2.6.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory General Status sensor unit connected to port 4 (1) OK (2) error, e. g. value overflow (3) configuration of sensor unit has changed, confirmation required (4) Quit from sensor unit to confirm configuration changes (5) timeout of sensor unit, confirmation required to unload this unit (6) sensor unit detected, needs to be confirmed (7) unit is not available (8) supply voltage is too low
| |||||||||||||||||||||
| NcmcTcStatusUnit4Sensors | 1.3.6.1.4.1.2606.4.2.6.5 | ||||||||||||||||||||
| ScmcTcUnit4NumberOfSensors | 1.3.6.1.4.1.2606.4.2.6.5.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Number of sensors connected to sensor unit 4 | |||||||||||||||||||||
| TcmcTcUnit4SensorTable | 1.3.6.1.4.1.2606.4.2.6.5.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Headline of sensor table | |||||||||||||||||||||
| RcmcTcUnit4SensorEntry | 1.3.6.1.4.1.2606.4.2.6.5.2.1 | NA | mandatory | ||||||||||||||||||
| Cunit4SensorIndex | 1.3.6.1.4.1.2606.4.2.6.5.2.1.1 | INTEGER (1..65535) | RO | mandatory | |||||||||||||||||
column · INTEGER (1..65535) · read-only · mandatory Index for the list of value entries. Its value ranges between 1 and the value of cmcTcUnit4NumberOfSensors. | |||||||||||||||||||||
| Cunit4SensorType | 1.3.6.1.4.1.2606.4.2.6.5.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Type of sensor which is connected to sensor unit 4 to sensor[unit4SensorIndex]
1: no sensor connected
2: sensor failure
3: value overflow
4: sensor type 1, access sensor
5: sensor type 2, vibration sensor
6: sensor type 3, motion sensor
7: sensor type 4, smoke sensor
8: sensor type 5, air flow sensor
9: sensor type 6, reserved
10: sensor type 7, temperature sensor
11: sensor type 8, 4..20mA sensor
12: sensor type 9, humidity sensor
13: user sensor with normally opened contact
14: user sensor with normally closed contact
15: door locked sensor from locking device
16: remote unlock sensor (e.g. external keypad)
17: voltage sensor, indicates status of main voltage
18: voltage value
19: fan status
20: cardreader or keypad, connected to I2C port
21: duty cycle of fan, FCS-Unit
22: status of fan, FCS-Unit
23: leakage sensor
24: warning, RittalTopTherm(RTT)-Unit
25: alarm, RittalTopTherm-Unit
26: temperature difference filter monitor, RTT-Unit
27: heatflow RCT-Unit
28: alarm RCT-Unit
29: warning RCT-Unit
30: actual current*10, PSM-Unit
31: status PSM-Unit
32: position PSM-Unit, normal/reversed = circuit 1/2
33: air Flap
34: acoustic sensor
35: DET-AC fault (extinguisher)
36: DET-AC first alarm (extinguisher)
37: DET-AC main alarm (extinguisher)
40-47: RPM Fan 1.1 - Fan 4.2, LCP
48-55: Air temperature 1.1 - 4.2, LCP
56,57: actual temperature 1,2, LCP
58: water inlet temperature, LCP
59: water outlet temperature, LCP
60: water flow
61: fan speed (desired value)
62: status valve, LCP
63: status LCP
64: temperature difference water temperatures
65: control temperature 1, LCP
66: control temperature 2, LCP
67: condensate pump, duration, LCP
68: condensate pump, cycles, LCP
72: total energy*10 (kWh), PSM
73: total power*10 (kW), PSM
74: frequency*10 (Hz), PSM
75: voltage*10 (V), PSM
76: voltage status, PSM
77: current*10 (A), PSM
78: current status, PSM
79: power*10 (kW) per phase, PSM
80: energy*10 (kWh) per phase, PSM
81: temporary energy*10 (kWh) per phase, PSM
100: temperature sensor, wireless
101: temperature sensor (combi), wireless
102: humidity sensor, wireless
103: access sensor, wireless
104: user sensor with normally opened contact, wireless
105: user sensor with normally closed contact, wireless
106: analog sensor 4..20mA, wireless
| |||||||||||||||||||||
| Cunit4SensorText | 1.3.6.1.4.1.2606.4.2.6.5.2.1.3 | DisplayString (SIZE (0..20)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..20)) · read-write · mandatory Descriptional text for each sensor (entry in the table) | |||||||||||||||||||||
| Cunit4SensorStatus | 1.3.6.1.4.1.2606.4.2.6.5.2.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Actual status of the sensor
| |||||||||||||||||||||
| Cunit4SensorValue | 1.3.6.1.4.1.2606.4.2.6.5.2.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Value of sensor | |||||||||||||||||||||
| Cunit4SensorSetHigh | 1.3.6.1.4.1.2606.4.2.6.5.2.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Value for high setpoint of sensor | |||||||||||||||||||||
| Cunit4SensorSetLow | 1.3.6.1.4.1.2606.4.2.6.5.2.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Value for low setpoint of sensor | |||||||||||||||||||||
| Cunit4SensorSetWarn | 1.3.6.1.4.1.2606.4.2.6.5.2.1.8 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Value for warning setpoint of sensor, also used as fan threshold | |||||||||||||||||||||
| NcmcTcStatusUnit4Outputs | 1.3.6.1.4.1.2606.4.2.6.6 | ||||||||||||||||||||
| ScmcTcUnit4NumberOfOutputs | 1.3.6.1.4.1.2606.4.2.6.6.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Number of outputs available on sensor unit 4 | |||||||||||||||||||||
| TcmcTcUnit4OutputTable | 1.3.6.1.4.1.2606.4.2.6.6.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Headline of output table | |||||||||||||||||||||
| RcmcTcUnit4OutputEntry | 1.3.6.1.4.1.2606.4.2.6.6.2.1 | NA | mandatory | ||||||||||||||||||
| Cunit4OutputIndex | 1.3.6.1.4.1.2606.4.2.6.6.2.1.1 | INTEGER (1..65535) | RO | mandatory | |||||||||||||||||
column · INTEGER (1..65535) · read-only · mandatory Index for the list of output entries. Its value ranges between 1 and the value of cmcTcUnit4NumberOfOutputs. | |||||||||||||||||||||
| Cunit4OutputType | 1.3.6.1.4.1.2606.4.2.6.6.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Type of output which is connected to sensor unit 4 to output[unit4OutputIndex] 1: no output connected 2: output failure 3: value overflow 4: output type 1, door locking TS8,Ergoform 5: output type 2, universal lock 1, lock with power 6: output type 3, universal lock 2, unlock with power 7: output type 4, fan relay 8: output type 5, fan controlled 9: output type 6, universal relay output 10: output type 7, room door lock 11: output type 8, power output 12: output type 9, door lock with Master key 13: output type 10, door lock FR(i) 14: setpoint (FCS, RTT) 15: setpoint temperature monitoring (RTT) 16: hysteresis of setpoint (RCT) 17: command for remote control of RCT 18: relay PSM, 1=On, 0=Off 19: high setpoint current monitoring PSM 20: low setpoint current monitoring PSM 21: setpoint temperature RTT 22: setpoint temperature monitoring RTT 23: power output 20A 30: control mode LCP 31: min fan speed (fan control) LCP 32: min delta T (fan control) LCP 33: max delta T (fan control) LCP 34: PID controller, KP, LCP 35: PID controller, KI, LCP 36 PID controller, KD, LCP 37 flowrate flowmeter, LCP 38: cw value of water (default: 4187) LCP 39: deltaT, LCP 40: control mode, LCP 42: setpoint high voltage PSM 43: setpoint low voltage PSM 44: setpoint high current PSM 45: setpoint low current PSM 46: command PSM
| |||||||||||||||||||||
| Cunit4OutputText | 1.3.6.1.4.1.2606.4.2.6.6.2.1.3 | DisplayString (SIZE (0..20)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..20)) · read-write · mandatory Descriptional text for each output (entry in the table) | |||||||||||||||||||||
| Cunit4OutputStatus | 1.3.6.1.4.1.2606.4.2.6.6.2.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Actual status of the output
| |||||||||||||||||||||
| Cunit4OutputValue | 1.3.6.1.4.1.2606.4.2.6.6.2.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Value for output | |||||||||||||||||||||
| Cunit4OutputSet | 1.3.6.1.4.1.2606.4.2.6.6.2.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Command for output
| |||||||||||||||||||||
| Cunit4OutputConfig | 1.3.6.1.4.1.2606.4.2.6.6.2.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Configuration for output 1: disable remote control (e.g. keypad) 2: enable remote control
| |||||||||||||||||||||
| Cunit4OutputDelay | 1.3.6.1.4.1.2606.4.2.6.6.2.1.8 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Unsigned Value for delay, after this time the output will fall into the previous state | |||||||||||||||||||||
| Cunit4OutputTimeoutAction | 1.3.6.1.4.1.2606.4.2.6.6.2.1.9 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory State for output if timeout (RS422) occurs
| |||||||||||||||||||||
| NcmcTcStatusUnit4Msg | 1.3.6.1.4.1.2606.4.2.6.7 | ||||||||||||||||||||
| ScmcTcUnit4NumberOfMsgs | 1.3.6.1.4.1.2606.4.2.6.7.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Number of alarms that can be created with sensor unit 4 | |||||||||||||||||||||
| TcmcTcUnit4MsgTable | 1.3.6.1.4.1.2606.4.2.6.7.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Headline of message table | |||||||||||||||||||||
| RcmcTcUnit4MsgEntry | 1.3.6.1.4.1.2606.4.2.6.7.2.1 | NA | mandatory | ||||||||||||||||||
| Cunit4MsgIndex | 1.3.6.1.4.1.2606.4.2.6.7.2.1.1 | INTEGER (1..65535) | RO | mandatory | |||||||||||||||||
column · INTEGER (1..65535) · read-only · mandatory Index for the list of alarm entries. Its value ranges between 1 and the value of cmcTcUnit4NumberOfMsgs. | |||||||||||||||||||||
| Cunit4MsgText | 1.3.6.1.4.1.2606.4.2.6.7.2.1.2 | DisplayString (SIZE (0..20)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..20)) · read-write · mandatory Descriptional text for each message (entry in the table) | |||||||||||||||||||||
| Cunit4MsgStatus | 1.3.6.1.4.1.2606.4.2.6.7.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Actual message status 1: not available 2: configuration has changed (sensor new, changed, lost) 3: error 4: OK 5: alarm, e.g. smoke, vibration... 6: warning of analog value, value reached warning threshold 7: analog value too low, value reached low threshold 8: analog value too high, value reached high threshold 9: output is set to OFF 10: output is set to ON 11: door is open 12: door is closed 13: door is locked 14: door is unlocked by remote input, e.g. external cardreader 15: door is unlocked by reader or keypad connected to I2C 16: door is unlocked by SNMP set command (unit1OutputSet) 17: door is unlocked by WEB 18: door is unlocked by timer 19: no access, wrong keycode or cardnumber 20: orientation of PSM-Unit is circuit 1 21: orientation of PSM-Unit is circuit 2 22: battery low, wireless sensor
| |||||||||||||||||||||
| Cunit4MsgRelay | 1.3.6.1.4.1.2606.4.2.6.7.2.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Setup of Alarm relay for this alarm 1: no switching of alarm relay 2: switching of alarm relay
| |||||||||||||||||||||
| Cunit4MsgBeeper | 1.3.6.1.4.1.2606.4.2.6.7.2.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Setup of Alarm beeper for this alarm 1: no audible alarm 2: audible alarm
| |||||||||||||||||||||
| Cunit4MsgTrap1 | 1.3.6.1.4.1.2606.4.2.6.7.2.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Trap receiver 1 activated
| |||||||||||||||||||||
| Cunit4MsgTrap2 | 1.3.6.1.4.1.2606.4.2.6.7.2.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Trap receiver 2 activated
| |||||||||||||||||||||
| Cunit4MsgTrap3 | 1.3.6.1.4.1.2606.4.2.6.7.2.1.8 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Trap receiver 3 activated
| |||||||||||||||||||||
| Cunit4MsgTrap4 | 1.3.6.1.4.1.2606.4.2.6.7.2.1.9 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Trap receiver 4 and Event Logging activated
| |||||||||||||||||||||
| Cunit4MsgQuit | 1.3.6.1.4.1.2606.4.2.6.7.2.1.10 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Reset of this alarm 1: auto 2: manual, alarm needs confirmation, e. g. with 'C' key
| |||||||||||||||||||||
| NcmcTcStatusExtUnit | 1.3.6.1.4.1.2606.4.2.7 | ||||||||||||||||||||
| ScmcTcValuesRelay | 1.3.6.1.4.1.2606.4.2.7.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Setup of Alarm relay for alarm ext. unit(s) 1: no switching of alarm relay 2: switching of alarm relay
| |||||||||||||||||||||
| ScmcTcValuesBeeper | 1.3.6.1.4.1.2606.4.2.7.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Setup of Alarm beeper for alarm ext. unit(s) 1: no audible alarm 2: audible alarm
| |||||||||||||||||||||
| ScmcTcValuesTrap1 | 1.3.6.1.4.1.2606.4.2.7.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Trap receiver 1 activated
| |||||||||||||||||||||
| ScmcTcValuesTrap2 | 1.3.6.1.4.1.2606.4.2.7.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Trap receiver 2 activated
| |||||||||||||||||||||
| ScmcTcValuesTrap3 | 1.3.6.1.4.1.2606.4.2.7.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Trap receiver 3 activated
| |||||||||||||||||||||
| ScmcTcValuesTrap4 | 1.3.6.1.4.1.2606.4.2.7.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Trap receiver 4 and Event Logging activated
| |||||||||||||||||||||
| ScmcTcNumberOfValues | 1.3.6.1.4.1.2606.4.2.7.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Number of values availabel on extension units connected to the CMC | |||||||||||||||||||||
| TcmcTcValuesTable | 1.3.6.1.4.1.2606.4.2.7.8 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Headline of values-table | |||||||||||||||||||||
| RcmcTcValuesEntry | 1.3.6.1.4.1.2606.4.2.7.8.1 | NA | mandatory | ||||||||||||||||||
| CvaluesIndex | 1.3.6.1.4.1.2606.4.2.7.8.1.1 | INTEGER (1..65535) | RO | mandatory | |||||||||||||||||
column · INTEGER (1..65535) · read-only · mandatory Index for the list of value entries. Its value ranges between 1 and the value of cmcTcNumberOfValues. | |||||||||||||||||||||
| CvaluesText | 1.3.6.1.4.1.2606.4.2.7.8.1.2 | DisplayString (SIZE (0..20)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..20)) · read-write · mandatory Descriptional text for each value (entry in the table) of the extension card | |||||||||||||||||||||
| CvaluesStatus | 1.3.6.1.4.1.2606.4.2.7.8.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Actual status of the value of the extension card
| |||||||||||||||||||||
| CvaluesValue | 1.3.6.1.4.1.2606.4.2.7.8.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Value of sensor | |||||||||||||||||||||
| CvaluesSetHigh | 1.3.6.1.4.1.2606.4.2.7.8.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Value for high setpoint of sensor | |||||||||||||||||||||
| CvaluesSetLow | 1.3.6.1.4.1.2606.4.2.7.8.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Value for low setpoint of sensor | |||||||||||||||||||||
| NcmcTcSetup | 1.3.6.1.4.1.2606.4.3 | ||||||||||||||||||||
| NcmcTcSetupGeneral | 1.3.6.1.4.1.2606.4.3.1 | ||||||||||||||||||||
| ScmcTcSetTempUnit | 1.3.6.1.4.1.2606.4.3.1.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Unit of all temperature values and setpoints, Celsius or Fahrenheit
| |||||||||||||||||||||
| ScmcTcSetBeeper | 1.3.6.1.4.1.2606.4.3.1.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Audible alarm in CMC-TC unit: (2): beeper is on (1): beeper is off (general)
| |||||||||||||||||||||
| ScmcTcQuitRelay | 1.3.6.1.4.1.2606.4.3.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Enable or disable acknowledging currently active alarm relay (with 'C' on CMC-TC).
| |||||||||||||||||||||
| ScmcTcLogicRelay | 1.3.6.1.4.1.2606.4.3.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Logic of alarm relay: (1) Relay will pick up in case of an alarm (2) Relay will release in case of an alarm (3) Relay off (general)
| |||||||||||||||||||||
| ScmcTcWebAccess | 1.3.6.1.4.1.2606.4.3.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Web access via HTTP: (1) view only (2) full Access, read and set (3) Web disabled (general)
| |||||||||||||||||||||
| ScmcTcSetupDate | 1.3.6.1.4.1.2606.4.3.1.6 | DisplayString (SIZE (0..10)) | RW | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..10)) · read-write · mandatory actual Date in format DD.MM.YYYY | |||||||||||||||||||||
| ScmcTcSetupTime | 1.3.6.1.4.1.2606.4.3.1.7 | DisplayString (SIZE (0..8)) | RW | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..8)) · read-write · mandatory actual Time in format HH:MM:SS, HH (0-23), MM (0-59), SS (0-59) | |||||||||||||||||||||
| NcmcTcTimerTable1 | 1.3.6.1.4.1.2606.4.3.1.8 | ||||||||||||||||||||
| ScmcTcTimerNumber | 1.3.6.1.4.1.2606.4.3.1.8.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Number of value-table entries=number of outlets available on this unit | |||||||||||||||||||||
| TcmcTcTimerTable | 1.3.6.1.4.1.2606.4.3.1.8.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Headline of status-table | |||||||||||||||||||||
| RcmcTcTimerEntry | 1.3.6.1.4.1.2606.4.3.1.8.2.1 | NA | mandatory | ||||||||||||||||||
| CcmcTcTimerIndex | 1.3.6.1.4.1.2606.4.3.1.8.2.1.1 | INTEGER (1..65535) | RO | mandatory | |||||||||||||||||
column · INTEGER (1..65535) · read-only · mandatory Index for the list of timer entries. Its value ranges between 1 and the value of cmcTcTimerNumber. | |||||||||||||||||||||
| CcmcTcTimerStatus | 1.3.6.1.4.1.2606.4.3.1.8.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Actual status of the timer
| |||||||||||||||||||||
| CcmcTcTimerDayOfWeek | 1.3.6.1.4.1.2606.4.3.1.8.2.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Selection of day of week for timer to switch
| |||||||||||||||||||||
| CcmcTcTimeOn | 1.3.6.1.4.1.2606.4.3.1.8.2.1.4 | DisplayString (SIZE (0..5)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..5)) · read-write · mandatory Time to switch on current function, Format: HH:MM | |||||||||||||||||||||
| CcmcTcTimeOff | 1.3.6.1.4.1.2606.4.3.1.8.2.1.5 | DisplayString (SIZE (0..5)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..5)) · read-write · mandatory Time to switch off current function, Format: HH:MM | |||||||||||||||||||||
| CcmcTcTimeControl | 1.3.6.1.4.1.2606.4.3.1.8.2.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Control via RTC
| |||||||||||||||||||||
| CcmcTcTimerFunction | 1.3.6.1.4.1.2606.4.3.1.8.2.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Function which is controlled via timer 1: unlock via keypad 1 on unit 1 or remote input lock 1 is disabled 2: unlock via keypad 2 on unit 1 or remote input lock 2 is disabled 3 unlock via keypad 1 on unit 2 or remote input lock 1 is disabled 4: unlock via keypad 2 on unit 2 or remote input lock 2 is disabled 5: unlock via keypad 1 on unit 3 or remote input lock 1 is disabled 6: unlock via keypad 2 on unit 3 or remote input lock 2 is disabled 7: unlock via keypad 1 on unit 4 or remote input lock 1 is disabled 8: unlock via keypad 2 on unit 4 or remote input lock 2 is disabled 9: Lock of door 1 on unit 1 will be unlocked 10: Lock of door 2 on unit 1 will be unlocked 11: Lock of door 1 on unit 2 will be unlocked 12: Lock of door 2 on unit 2 will be unlocked 13: Lock of door 1 on unit 3 will be unlocked 14: Lock of door 2 on unit 3 will be unlocked 15: Lock of door 1 on unit 4 will be unlocked 16: Lock of door 2 on unit 4 will be unlocked 17-20: sending Traps to this Trap receiver will be disabled 21: sending SMS will be disabled generally 22-25: Scheduled alarm off 26-29: sending SMS to phone number 1..4 will be disabled
| |||||||||||||||||||||
| NcmcTcTrapControl | 1.3.6.1.4.1.2606.4.4 | ||||||||||||||||||||
| NcmcTcTraps | 1.3.6.1.4.1.2606.4.4.7 | ||||||||||||||||||||
| ScmcTcTraptableNumber | 1.3.6.1.4.1.2606.4.4.7.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Number of trapTable entries. The number of trap-receiver | |||||||||||||||||||||
| TcmcTcTrapTableTable | 1.3.6.1.4.1.2606.4.4.7.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of trap-receiver entries | |||||||||||||||||||||
| RcmcTcTrapTableEntry | 1.3.6.1.4.1.2606.4.4.7.2.1 | NA | mandatory | ||||||||||||||||||
| CtrapIndex | 1.3.6.1.4.1.2606.4.4.7.2.1.1 | INTEGER (1..65535) | RO | mandatory | |||||||||||||||||
column · INTEGER (1..65535) · read-only · mandatory Index for the trap-receiver-table. Its value ranges between 1 and the value of traptableNumber | |||||||||||||||||||||
| CtrapStatus | 1.3.6.1.4.1.2606.4.4.7.2.1.2 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Enable or disable trap receiver
| |||||||||||||||||||||
| CtrapIPaddress | 1.3.6.1.4.1.2606.4.4.7.2.1.3 | DisplayString (SIZE (0..15)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..15)) · read-write · mandatory IP-address of trap-receiver | |||||||||||||||||||||
| NcmcTcControl | 1.3.6.1.4.1.2606.4.5 | ||||||||||||||||||||
| ScmcTcQuitUnit | 1.3.6.1.4.1.2606.4.5.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Command to quit (acknowledge) alarms of CMC-TC unit. Setting to 'quit' (2) will have same result as pressing 'C' on Units. Variable is automatically set back to 'noQuit' (1).
| |||||||||||||||||||||
Traps / Notifications
- alarmSensorUnit1
1.3.6.1.4.1.2606.4.0.1 - alarmSensorUnit2
1.3.6.1.4.1.2606.4.0.2 - alarmSensorUnit3
1.3.6.1.4.1.2606.4.0.3 - alarmSensorUnit4
1.3.6.1.4.1.2606.4.0.4 - alarmUnit1
1.3.6.1.4.1.2606.4.0.5 - alarmUnit2
1.3.6.1.4.1.2606.4.0.6 - alarmUnit3
1.3.6.1.4.1.2606.4.0.7 - alarmUnit4
1.3.6.1.4.1.2606.4.0.8 - alarmValues
1.3.6.1.4.1.2606.4.0.9 - configChanged
1.3.6.1.4.1.2606.4.0.10