RIELLOMDU-MIB
UPS Manufacturingsnmptranslate -m RIELLOMDU-MIB -Tpsnmpwalk -v2c -c <community> -m RIELLOMDU-MIB <host> 1.3.6.1.4.1.5491.11Imports
| RIELLO-MIB | rielloMIB |
|---|---|
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
| SNMPv2-SMI | Bits, Integer32, IpAddress, MODULE-IDENTITY, MibIdentifier, OBJECT-IDENTITY, OBJECT-TYPE, TRAP-TYPE, TimeTicks, Unsigned32, iso |
| SNMPv2-TC | DisplayString, PhysAddress, TEXTUAL-CONVENTION |
OID tree
| Name | OID | Type | Access | Status |
|---|---|---|---|---|
| NmduMIB | 1.3.6.1.4.1.5491.11 | |||
| NmduIdent | 1.3.6.1.4.1.5491.11.1 | |||
| SmduIdentManufacturer | 1.3.6.1.4.1.5491.11.1.1 | DisplayString | RO | mandatory |
scalar · DisplayString · read-only · mandatory The name of the mdu manufacturer. | ||||
| SmduIdentModel | 1.3.6.1.4.1.5491.11.1.2 | DisplayString | RO | mandatory |
scalar · DisplayString · read-only · mandatory The mdu Model designation. | ||||
| SmduIdentSoftwareVersion | 1.3.6.1.4.1.5491.11.1.3 | DisplayString | RO | mandatory |
scalar · DisplayString · read-only · mandatory The mdu Software version. | ||||
| SmduIdentIOConfiguration | 1.3.6.1.4.1.5491.11.1.4 | INTEGER | RO | mandatory |
scalar · INTEGER · read-only · mandatory The mdu input/output configuration (1 for Mono/mono, 4 for Tri/tri). | ||||
| SmduIdentInputSockets | 1.3.6.1.4.1.5491.11.1.5 | INTEGER | RO | mandatory |
scalar · INTEGER · read-only · mandatory The number of mdu input sockets. | ||||
| SmduIdentOutputSockets | 1.3.6.1.4.1.5491.11.1.6 | INTEGER | RO | mandatory |
scalar · INTEGER · read-only · mandatory The number of mdu output sockets. | ||||
| SmduIdentNominalCurrent | 1.3.6.1.4.1.5491.11.1.7 | INTEGER | RO | mandatory |
scalar · INTEGER · read-only · mandatory The mdu nominal current (A). | ||||
| SmduIdentNominalVoltage | 1.3.6.1.4.1.5491.11.1.8 | INTEGER | RO | mandatory |
scalar · INTEGER · read-only · mandatory The mdu nominal voltage (V). | ||||
| SmduIdentNominalFrequency | 1.3.6.1.4.1.5491.11.1.9 | INTEGER | RO | mandatory |
scalar · INTEGER · read-only · mandatory The mdu nominal frequency (0.1 Hz). | ||||
| NmduStatus | 1.3.6.1.4.1.5491.11.2 | |||
| SmduLineAFrequency | 1.3.6.1.4.1.5491.11.2.1 | INTEGER | RO | mandatory |
scalar · INTEGER · read-only · mandatory The frequency of source A (0.1 Hz). | ||||
| SmduLineAVoltage | 1.3.6.1.4.1.5491.11.2.2 | INTEGER | RO | mandatory |
scalar · INTEGER · read-only · mandatory The voltage of source 1 (V). | ||||
| SmduLineACurrent | 1.3.6.1.4.1.5491.11.2.3 | INTEGER | RO | mandatory |
scalar · INTEGER · read-only · mandatory The current of line A (0.1 A). | ||||
| TmduOutput | 1.3.6.1.4.1.5491.11.2.4 | NA | mandatory | |
table · not-accessible · mandatory A list of output table entries. | ||||
| RmduOutputSockets | 1.3.6.1.4.1.5491.11.2.4.1 | NA | mandatory | |
row · not-accessible · mandatory An entry containing information applicable to a particular output line.
| ||||
| CmduOutputLineIndex | 1.3.6.1.4.1.5491.11.2.4.1.1 | INTEGER (1..2147483647) | NA | mandatory |
column · INTEGER (1..2147483647) · not-accessible · mandatory The line identifier. | ||||
| CmduOutputCurrent | 1.3.6.1.4.1.5491.11.2.4.1.2 | INTEGER | RO | mandatory |
column · INTEGER · read-only · mandatory Output current (0.1 A) | ||||
| CmduOutputDisabled | 1.3.6.1.4.1.5491.11.2.4.1.3 | INTEGER | RO | mandatory |
column · INTEGER · read-only · mandatory 1->line active, 2->line deactivated
| ||||
| CmduOutputOverload | 1.3.6.1.4.1.5491.11.2.4.1.4 | INTEGER | RO | mandatory |
column · INTEGER · read-only · mandatory 1->line ok, 2->line deactivated for overload | ||||
| CmduOutputStatus | 1.3.6.1.4.1.5491.11.2.4.1.5 | INTEGER | RO | mandatory |
column · INTEGER · read-only · mandatory 0=OFF 1=ON 2= Shutdown active (when a CS or a CR command is received but shutdown is not yet been executed and the 'Imminent time' is not reached) 3= Shutdown imminent (S01 ÷ S08 code) 4= Restore active (when after that a CR command is received and the shutdown has been acted but the restore delay time is not expired) 5= Overload alarm (F01 ÷ F08 code) 6= Locked: OFF for overload (L01 ÷ L08 code)
| ||||
| SmduLowInputVoltage | 1.3.6.1.4.1.5491.11.2.5 | INTEGER | RO | mandatory |
scalar · INTEGER · read-only · mandatory 1= yes, 0= no. | ||||
| SmduHighInputVoltage | 1.3.6.1.4.1.5491.11.2.6 | INTEGER | RO | mandatory |
scalar · INTEGER · read-only · mandatory 1= yes, 0= no. | ||||
| SmduLowInputCurrent | 1.3.6.1.4.1.5491.11.2.7 | INTEGER | RO | mandatory |
scalar · INTEGER · read-only · mandatory 1= yes, 0= no. | ||||
| SmduHighInputCurrent | 1.3.6.1.4.1.5491.11.2.8 | INTEGER | RO | mandatory |
scalar · INTEGER · read-only · mandatory 1= yes, 0= no. | ||||
| SmduPowerFailAux1 | 1.3.6.1.4.1.5491.11.2.9 | INTEGER | RO | mandatory |
scalar · INTEGER · read-only · mandatory 1= yes, 0= no. | ||||
| SmduPowerFailAux2 | 1.3.6.1.4.1.5491.11.2.10 | INTEGER | RO | mandatory |
scalar · INTEGER · read-only · mandatory 1= yes, 0= no. | ||||
| SmduManualBypass | 1.3.6.1.4.1.5491.11.2.11 | INTEGER | RO | mandatory |
scalar · INTEGER · read-only · mandatory 1= on manual bypass, 0= no. | ||||
| SmduTemperature | 1.3.6.1.4.1.5491.11.2.12 | INTEGER | RO | mandatory |
scalar · INTEGER · read-only · mandatory The temperature (°C). | ||||
| NmduCommand | 1.3.6.1.4.1.5491.11.3 | |||
| SmduCommandCode | 1.3.6.1.4.1.5491.11.3.1 | INTEGER | RW | mandatory |
scalar · INTEGER · read-write · mandatory This object determines the nature of the action to be taken at the time when the countdown of the mduShutdownDelay and mduRestoreDelay objects reaches zero. Setting this object to shutdown(1) indicates that the specified sockets mduOutputSocketApplyCommand will yurn off. Setting this object to restore(2) indicates that the specified output sockets will turn on. command delete(3) will delete the applied command, test panel will perform a test of LCD panel and audible alarm
| ||||
| SmduShutdownDelay | 1.3.6.1.4.1.5491.11.3.2 | INTEGER | RW | mandatory |
scalar · INTEGER · read-write · mandatory Setting this object will shutdown (i.e., turn off) either the MDU output socket by the value of mduCommandCode at the time of shutdown after the indicated number of seconds. Setting this object to 0 will cause the shutdown to occur immediately | ||||
| SmduRestoreDelay | 1.3.6.1.4.1.5491.11.3.3 | INTEGER | RW | mandatory |
scalar · INTEGER · read-write · mandatory The restore delay. | ||||
| SmduOutputSocketApplyCommand | 1.3.6.1.4.1.5491.11.3.4 | INTEGER | RW | mandatory |
scalar · INTEGER · read-write · mandatory Specify the socket to apply the command, the value 0 apply to all sockets. | ||||
| SmduCommandResult | 1.3.6.1.4.1.5491.11.3.5 | INTEGER | RO | mandatory |
scalar · INTEGER · read-only · mandatory The command result, refer to the follow codes: 0+mduCommandCode Command in progress 256+mduCommandCode Wrong Command code 512+mduCommandCode Command is not handled 768+mduCommandCode Parameter out of range 3584+mduCommandCode Command sent to MDU 3840+mduCommandCode Command executed | ||||
| NmduTraps | 1.3.6.1.4.1.5491.11.4 | |||
| !mduNormal | 1.3.6.1.4.1.5491.11.4.0.1 | |||
notification This trap is sent when MDU is on normal status | ||||
| !mduAnomaly | 1.3.6.1.4.1.5491.11.4.0.2 | |||
notification This trap is sent when MDU is has some anomaly and is resent every minute | ||||
| !mduFault | 1.3.6.1.4.1.5491.11.4.0.3 | |||
notification This trap is sent when MDU is has some fault and is resent every minute | ||||
| !mduLock | 1.3.6.1.4.1.5491.11.4.0.4 | |||
notification This trap is sent when MDU is locked and is resent every minute | ||||
| !mduManualBypassEnabled | 1.3.6.1.4.1.5491.11.4.0.5 | |||
notification This trap is sent when MDU is on manual bypass and is resent every minute | ||||
Traps / Notifications
- mduAnomaly
1.3.6.1.4.1.5491.11.4.0.2 - mduFault
1.3.6.1.4.1.5491.11.4.0.3 - mduLock
1.3.6.1.4.1.5491.11.4.0.4 - mduManualBypassEnabled
1.3.6.1.4.1.5491.11.4.0.5 - mduNormal
1.3.6.1.4.1.5491.11.4.0.1