PDU2-MIB
Raritan Computer, Inc.This MIB describes the SNMP functions of the PX2, PX3, PX4, PXC, SRC, PXO, and BCM/BCM2 series power distribution units by Raritan, the PRO3X and PRO4X series power distribution units by Server Technology, and the intelligent power distribution units by Legrand.
snmptranslate -m PDU2-MIB -Tpsnmpwalk -v2c -c <community> -m PDU2-MIB <host> 1.3.6.1.4.1.13742Imports
| INET-ADDRESS-MIB | InetAddress, InetAddressType, InetPortNumber |
|---|---|
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP, OBJECT-GROUP |
| SNMPv2-MIB | sysContact, sysLocation, sysName |
| SNMPv2-SMI | Bits, Integer32, IpAddress, MODULE-IDENTITY, MibIdentifier, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, TimeTicks, Unsigned32, enterprises, iso |
| SNMPv2-TC | DisplayString, MacAddress, PhysAddress, RowPointer, TEXTUAL-CONVENTION, TruthValue |
OID tree
| Name | OID | Type | Access | Status | Example | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Iraritan | 1.3.6.1.4.1.13742 | ||||||||||||||||||||
identity This MIB describes the SNMP functions of the PX2, PX3, PX4, PXC, SRC, PXO, and BCM/BCM2 series power distribution units by Raritan, the PRO3X and PRO4X series power distribution units by Server Technology, and the intelligent power distribution units by Legrand. | |||||||||||||||||||||
| Npdu2 | 1.3.6.1.4.1.13742.6 | ||||||||||||||||||||
| Ntraps | 1.3.6.1.4.1.13742.6.0 | ||||||||||||||||||||
| NtrapInformation | 1.3.6.1.4.1.13742.6.0.0 | ||||||||||||||||||||
| TtrapInformationTable | 1.3.6.1.4.1.13742.6.0.0.1 | NA | |||||||||||||||||||
table · not-accessible · current A group of objects used exclusively in traps. This is a table for historic reasons; it can't be queried from the SNMP agent. | |||||||||||||||||||||
| RtrapInformationEntry | 1.3.6.1.4.1.13742.6.0.0.1.1 | NA | |||||||||||||||||||
| CuserName | 1.3.6.1.4.1.13742.6.0.0.1.1.2 | DisplayString | AN | ||||||||||||||||||
column · DisplayString · accessible-for-notify · current The user currently logged in. | |||||||||||||||||||||
| CtargetUser | 1.3.6.1.4.1.13742.6.0.0.1.1.3 | DisplayString | AN | ||||||||||||||||||
column · DisplayString · accessible-for-notify · current The user added, deleted, or modified. | |||||||||||||||||||||
| CimageVersion | 1.3.6.1.4.1.13742.6.0.0.1.1.5 | DisplayString | AN | ||||||||||||||||||
column · DisplayString · accessible-for-notify · current The version of the upgrade image. | |||||||||||||||||||||
| CroleName | 1.3.6.1.4.1.13742.6.0.0.1.1.6 | DisplayString | AN | ||||||||||||||||||
column · DisplayString · accessible-for-notify · current The role added, deleted, or modified. | |||||||||||||||||||||
| CsmtpMessageRecipients | 1.3.6.1.4.1.13742.6.0.0.1.1.7 | DisplayString | AN | ||||||||||||||||||
column · DisplayString · accessible-for-notify · current Comma separated list of SMTP message recipients | |||||||||||||||||||||
| CsmtpServer | 1.3.6.1.4.1.13742.6.0.0.1.1.8 | DisplayString | AN | ||||||||||||||||||
column · DisplayString · accessible-for-notify · current The IP address/host name of the SMTP server | |||||||||||||||||||||
| CnewTargetUser | 1.3.6.1.4.1.13742.6.0.0.1.1.9 | DisplayString | AN | ||||||||||||||||||
column · DisplayString · accessible-for-notify · current The new name of a renamed user. | |||||||||||||||||||||
| SoldSensorState | 1.3.6.1.4.1.13742.6.0.0.2 | SensorStateEnumeration | AN | ||||||||||||||||||
scalar · SensorStateEnumeration · accessible-for-notify · current The old sensor state used in sensor state transition traps. | |||||||||||||||||||||
| SpduNumber | 1.3.6.1.4.1.13742.6.0.0.3 | Integer32 (1..256) | AN | ||||||||||||||||||
scalar · Integer32 (1..256) · accessible-for-notify · current A unique value for each PDU or power meter. This is the same as
pduId, but for use in traps.
For BCM2 and PMC, pduNumber can be:
- 0 for the main controller
- The meter ID (rotary switch) for power meter
For all other products, pduNumber is the PDU's link ID. If linking
is not used, pduNumber is 1. | |||||||||||||||||||||
| SinletPoleNumber | 1.3.6.1.4.1.13742.6.0.0.5 | Integer32 (1..256) | AN | ||||||||||||||||||
scalar · Integer32 (1..256) · accessible-for-notify · current A unique value for each inlet pole. Its value ranges between 1 and the value of inletPoleCount. | |||||||||||||||||||||
| SoutletPoleNumber | 1.3.6.1.4.1.13742.6.0.0.7 | Integer32 (1..256) | AN | ||||||||||||||||||
scalar · Integer32 (1..256) · accessible-for-notify · current A unique value for each outlet pole. Its value ranges between 1 and the value of outletPoleCount. | |||||||||||||||||||||
| SexternalSensorNumber | 1.3.6.1.4.1.13742.6.0.0.8 | Integer32 (1..256) | AN | ||||||||||||||||||
scalar · Integer32 (1..256) · accessible-for-notify · current A unique value for each external sensor. Its value ranges between 1 and the value of externalSensorCount. | |||||||||||||||||||||
| StypeOfSensor | 1.3.6.1.4.1.13742.6.0.0.10 | SensorTypeEnumeration | AN | ||||||||||||||||||
scalar · SensorTypeEnumeration · accessible-for-notify · current The type of sensor. | |||||||||||||||||||||
| SerrorDescription | 1.3.6.1.4.1.13742.6.0.0.11 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current Description of the error | |||||||||||||||||||||
| SdeviceChangedParameter | 1.3.6.1.4.1.13742.6.0.0.12 | DeviceIdentificationParameterEnumeration | AN | ||||||||||||||||||
scalar · DeviceIdentificationParameterEnumeration · accessible-for-notify · current Identifies the parameter that has changed. | |||||||||||||||||||||
| SchangedParameterNewValue | 1.3.6.1.4.1.13742.6.0.0.13 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current The new value of the changed parameter | |||||||||||||||||||||
| SlhxSupportEnabled | 1.3.6.1.4.1.13742.6.0.0.14 | TruthValue | AN | deprecated | |||||||||||||||||
scalar · TruthValue · accessible-for-notify · deprecated The new enabled state for Schroff LHX support. | |||||||||||||||||||||
| SwebcamModel | 1.3.6.1.4.1.13742.6.0.0.15 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current The model of the webcam | |||||||||||||||||||||
| SwebcamConnectionPort | 1.3.6.1.4.1.13742.6.0.0.16 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current The port to which the webcam is connected | |||||||||||||||||||||
| SagentInetPortNumber | 1.3.6.1.4.1.13742.6.0.0.18 | InetPortNumber | AN | ||||||||||||||||||
scalar · InetPortNumber · accessible-for-notify · current The UDP port number used for accessing the SNMP agent on the device. This is necessary to identify the expansion unit in a port forwarding cascade. | |||||||||||||||||||||
| SperipheralDeviceRomcode | 1.3.6.1.4.1.13742.6.0.0.19 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current The 1-wire romcode of a peripheral device | |||||||||||||||||||||
| SperipheralDeviceFirmwareUpdateState | 1.3.6.1.4.1.13742.6.0.0.20 | PeripheralDeviceFirmwareUpdateStateEnumeration | AN | ||||||||||||||||||
scalar · PeripheralDeviceFirmwareUpdateStateEnumeration · accessible-for-notify · current The firmware update state of a peripheral device | |||||||||||||||||||||
| ScircuitNumber | 1.3.6.1.4.1.13742.6.0.0.21 | Integer32 (1..33000) | AN | ||||||||||||||||||
scalar · Integer32 (1..33000) · accessible-for-notify · current A unique value for each circuit. Defined as follows:
circuitNumber = 1000 * panelId + circuitPosition
Examples:
1045 is the the circuit on panel 1 with lowest circuit position equal to 45
4067 is the the circuit on panel 4 with lowest circuit position equal to 67. | |||||||||||||||||||||
| ScircuitPoleNumber | 1.3.6.1.4.1.13742.6.0.0.22 | Integer32 (1..256) | AN | ||||||||||||||||||
scalar · Integer32 (1..256) · accessible-for-notify · current A unique value for each circuit pole. | |||||||||||||||||||||
| SphoneNumber | 1.3.6.1.4.1.13742.6.0.0.23 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current The phone number of e.g. an SMS receiver. | |||||||||||||||||||||
| SsmartCardReaderId | 1.3.6.1.4.1.13742.6.0.0.24 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current The ID of a smartcard reader. | |||||||||||||||||||||
| SsmartCardTimestamp | 1.3.6.1.4.1.13742.6.0.0.25 | Unsigned32 | AN | ||||||||||||||||||
scalar · Unsigned32 · accessible-for-notify · current The timestamp indicating when the smartcard was inserted or removed. It is measured in seconds since January 1, 1970 UTC | |||||||||||||||||||||
| SsmartCardType | 1.3.6.1.4.1.13742.6.0.0.26 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current The type of a smartcard. | |||||||||||||||||||||
| SsmartCardId | 1.3.6.1.4.1.13742.6.0.0.27 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current The ID/serial number of a smartcard. | |||||||||||||||||||||
| SsuspectedTripCauseLabel | 1.3.6.1.4.1.13742.6.0.0.28 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current The label of the outlet that likely caused the OCP trip, if it can be determined. | |||||||||||||||||||||
| SsmartCardReaderManufacturer | 1.3.6.1.4.1.13742.6.0.0.29 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current The manufacturer of a smartcard reader. | |||||||||||||||||||||
| SsmartCardReaderProduct | 1.3.6.1.4.1.13742.6.0.0.30 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current The product name of a smartcard reader. | |||||||||||||||||||||
| SsmartCardReaderSerialNumber | 1.3.6.1.4.1.13742.6.0.0.31 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current The serial number of a smartcard reader. | |||||||||||||||||||||
| SsmartCardReaderChannel | 1.3.6.1.4.1.13742.6.0.0.32 | Integer32 (-1..256) | AN | ||||||||||||||||||
scalar · Integer32 (-1..256) · accessible-for-notify · current The channel number of a smartcard reader. The channel number is used to differentiate multiple readers implemented in the same physical package. It will be -1 for single-channel readers. | |||||||||||||||||||||
| SoutletGroupNumber | 1.3.6.1.4.1.13742.6.0.0.33 | Integer32 (1..256) | AN | ||||||||||||||||||
scalar · Integer32 (1..256) · accessible-for-notify · current The ID of the outlet group. | |||||||||||||||||||||
| SserverPowerOperation | 1.3.6.1.4.1.13742.6.0.0.34 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current The power control operation that was initiated on the server (on/off) | |||||||||||||||||||||
| SserverPowerResult | 1.3.6.1.4.1.13742.6.0.0.35 | ServerPowerControlResultEnumeration | AN | ||||||||||||||||||
scalar · ServerPowerControlResultEnumeration · accessible-for-notify · current The result of the server power control operation. | |||||||||||||||||||||
| SwebcamName | 1.3.6.1.4.1.13742.6.0.0.36 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current The user-defined name of the webcam | |||||||||||||||||||||
| SwebcamFolderUrl | 1.3.6.1.4.1.13742.6.0.0.37 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current The URL of the folder containing the image | |||||||||||||||||||||
| SkeypadId | 1.3.6.1.4.1.13742.6.0.0.38 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current The ID of a keypad. | |||||||||||||||||||||
| SkeypadPinTimestamp | 1.3.6.1.4.1.13742.6.0.0.39 | Unsigned32 | AN | ||||||||||||||||||
scalar · Unsigned32 · accessible-for-notify · current The timestamp indicating when the PIN was entered. It is measured in seconds since January 1, 1970 UTC | |||||||||||||||||||||
| SkeypadPin | 1.3.6.1.4.1.13742.6.0.0.40 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current The PIN entered on a keypad. | |||||||||||||||||||||
| SkeypadManufacturer | 1.3.6.1.4.1.13742.6.0.0.41 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current The manufacturer of a keypad. | |||||||||||||||||||||
| SkeypadProduct | 1.3.6.1.4.1.13742.6.0.0.42 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current The product name of a keypad. | |||||||||||||||||||||
| SkeypadSerialNumber | 1.3.6.1.4.1.13742.6.0.0.43 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current The serial number of a keypad. | |||||||||||||||||||||
| SkeypadChannel | 1.3.6.1.4.1.13742.6.0.0.44 | Integer32 (-1..256) | AN | ||||||||||||||||||
scalar · Integer32 (-1..256) · accessible-for-notify · current The channel number of a keypad. The channel number is used to differentiate multiple keypads implemented in the same physical package. It will be -1 for single-channel keypads. | |||||||||||||||||||||
| SdoorAccessRuleId | 1.3.6.1.4.1.13742.6.0.0.45 | Integer32 (-1..256) | AN | ||||||||||||||||||
scalar · Integer32 (-1..256) · accessible-for-notify · current The ID of a door access control rule. -1 if undefined. | |||||||||||||||||||||
| SdoorAccessDenialReason | 1.3.6.1.4.1.13742.6.0.0.46 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current The reason for door access being denied. | |||||||||||||||||||||
| SdoorAccessRuleName | 1.3.6.1.4.1.13742.6.0.0.47 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current The name of a door access rule. Empty if undefined. | |||||||||||||||||||||
| SsmartCardReaderPosition | 1.3.6.1.4.1.13742.6.0.0.48 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current The position of a smartcard reader. Contains either the position in the 1-wire topology and the channel (e.g. D1:H1:C1-1) or, for usb card readers, a string like usb:<n> where n is a number increasing with usb card readers. | |||||||||||||||||||||
| SkeypadPosition | 1.3.6.1.4.1.13742.6.0.0.49 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current The position of a keypad. A string representing the position of the keypad in the 1-wire topology and the channel (e.g. D1:H1:C1-1) | |||||||||||||||||||||
| SkeypadDescription | 1.3.6.1.4.1.13742.6.0.0.50 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current The custom description of a keypad. | |||||||||||||||||||||
| SkeypadName | 1.3.6.1.4.1.13742.6.0.0.51 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current The custom name of a keypad. | |||||||||||||||||||||
| SsmartCardReaderDescription | 1.3.6.1.4.1.13742.6.0.0.52 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current The custom description of a smartcard reader. | |||||||||||||||||||||
| SsmartCardReaderName | 1.3.6.1.4.1.13742.6.0.0.53 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current The custom name of a smartcard reader. | |||||||||||||||||||||
| SinletLinePairNumber | 1.3.6.1.4.1.13742.6.0.0.54 | Integer32 (1..3) | AN | ||||||||||||||||||
scalar · Integer32 (1..3) · accessible-for-notify · current A unique value for each inlet line pair. Its value ranges between 1 and the value of inletLinePairCount. | |||||||||||||||||||||
| SdipSwellEventVoltage | 1.3.6.1.4.1.13742.6.0.0.55 | Unsigned32 | AN | ||||||||||||||||||
scalar · Unsigned32 · accessible-for-notify · current The minimum (dip) / maximum (swell) voltage seen during a dip/swell event. This value should be scaled by the number of decimal digits of the respective voltage sensor, found in the inletSensorDecimalDigits or inletPoleSensorDecimalDigits, respectively. | |||||||||||||||||||||
| SdipSwellEventTimeStamp | 1.3.6.1.4.1.13742.6.0.0.56 | Unsigned32 | AN | ||||||||||||||||||
scalar · Unsigned32 · accessible-for-notify · current The timestamp indicating when the dip/swell event occurred. It is measured in seconds since January 1, 1970 UTC | |||||||||||||||||||||
| SdipSwellEventDuration | 1.3.6.1.4.1.13742.6.0.0.57 | Unsigned32 | AN | ||||||||||||||||||
scalar · Unsigned32 · accessible-for-notify · current The dip/swell event duration, measured in milliseconds. | |||||||||||||||||||||
| SportFuseState | 1.3.6.1.4.1.13742.6.0.0.58 | PortFuseStateEnumeration | AN | ||||||||||||||||||
scalar · PortFuseStateEnumeration · accessible-for-notify · current The new fuse state used in fuse state transition traps. | |||||||||||||||||||||
| SexternalPortFuseId | 1.3.6.1.4.1.13742.6.0.0.59 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current The ID of the fuse that triggered a state transition. | |||||||||||||||||||||
| SexternalPortName | 1.3.6.1.4.1.13742.6.0.0.60 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current The human-readable name of an external port. | |||||||||||||||||||||
| SlinkUnitId | 1.3.6.1.4.1.13742.6.0.0.61 | Integer32 (2..256) | AN | ||||||||||||||||||
scalar · Integer32 (2..256) · accessible-for-notify · current The pduId value of the link unit. | |||||||||||||||||||||
| SlinkUnitAddress | 1.3.6.1.4.1.13742.6.0.0.62 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current The host name, IP address or bus address of the link unit. | |||||||||||||||||||||
| SdoorHandleName | 1.3.6.1.4.1.13742.6.0.0.63 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current The name of a door handle sensor. | |||||||||||||||||||||
| SdoorLockName | 1.3.6.1.4.1.13742.6.0.0.64 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current The name of a door lock sensor. | |||||||||||||||||||||
| SdoorStateName | 1.3.6.1.4.1.13742.6.0.0.65 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current The name of a door state sensor. | |||||||||||||||||||||
| !systemStarted | 1.3.6.1.4.1.13742.6.0.1 | ||||||||||||||||||||
notification · current The system has started. | |||||||||||||||||||||
| !systemReset | 1.3.6.1.4.1.13742.6.0.2 | ||||||||||||||||||||
notification · current The system was rebooted. | |||||||||||||||||||||
| !userLogin | 1.3.6.1.4.1.13742.6.0.3 | ||||||||||||||||||||
notification · current A user logged in. | |||||||||||||||||||||
| !userLogout | 1.3.6.1.4.1.13742.6.0.4 | ||||||||||||||||||||
notification · current A user logged out. | |||||||||||||||||||||
| !userAuthenticationFailure | 1.3.6.1.4.1.13742.6.0.5 | ||||||||||||||||||||
notification · current A user authentication attempt failed. | |||||||||||||||||||||
| !userSessionTimeout | 1.3.6.1.4.1.13742.6.0.8 | ||||||||||||||||||||
notification · current A user session timed out. | |||||||||||||||||||||
| !userAdded | 1.3.6.1.4.1.13742.6.0.11 | ||||||||||||||||||||
notification · current A user account was added to the system. | |||||||||||||||||||||
| !userModified | 1.3.6.1.4.1.13742.6.0.12 | ||||||||||||||||||||
notification · current A user account was modified. | |||||||||||||||||||||
| !userDeleted | 1.3.6.1.4.1.13742.6.0.13 | ||||||||||||||||||||
notification · current A user account was deleted from the system. | |||||||||||||||||||||
| !roleAdded | 1.3.6.1.4.1.13742.6.0.14 | ||||||||||||||||||||
notification · current A role was added to the system. | |||||||||||||||||||||
| !roleModified | 1.3.6.1.4.1.13742.6.0.15 | ||||||||||||||||||||
notification · current A role was modified. | |||||||||||||||||||||
| !roleDeleted | 1.3.6.1.4.1.13742.6.0.16 | ||||||||||||||||||||
notification · current A role was deleted from the system. | |||||||||||||||||||||
| !deviceUpdateStarted | 1.3.6.1.4.1.13742.6.0.20 | ||||||||||||||||||||
notification · current The device firmware update has started. | |||||||||||||||||||||
| !deviceUpdateCompleted | 1.3.6.1.4.1.13742.6.0.21 | ||||||||||||||||||||
notification · current The device firmware update has completed. | |||||||||||||||||||||
| !userBlocked | 1.3.6.1.4.1.13742.6.0.22 | ||||||||||||||||||||
notification · current A blocked user tried to log in. | |||||||||||||||||||||
| !powerControl | 1.3.6.1.4.1.13742.6.0.23 | ||||||||||||||||||||
notification · current An outlet switching operation has been performed. Note that measurementsOutletSensorState represents the state of the outlet at the time the trap was sent. This may be different from the final state of the outlet. For instance, if the outlet is cycled and the outlet cycle delay is 20 seconds, this variable will indicate OFF although the final state of the outlet will be ON. The final state of the outlet will be indicated in the outletSensorStateChange trap for the outlet onOff sensor. | |||||||||||||||||||||
| !userPasswordChanged | 1.3.6.1.4.1.13742.6.0.24 | ||||||||||||||||||||
notification · current User password was changed. | |||||||||||||||||||||
| !passwordSettingsChanged | 1.3.6.1.4.1.13742.6.0.28 | ||||||||||||||||||||
notification · current Strong password settings changed. | |||||||||||||||||||||
| !firmwareValidationFailed | 1.3.6.1.4.1.13742.6.0.38 | ||||||||||||||||||||
notification · current Validation of an uploaded firmware image failed. | |||||||||||||||||||||
| !logFileCleared | 1.3.6.1.4.1.13742.6.0.41 | ||||||||||||||||||||
notification · current The event log has been cleared. | |||||||||||||||||||||
| !bulkConfigurationSaved | 1.3.6.1.4.1.13742.6.0.53 | ||||||||||||||||||||
notification · current A bulk configuration file was downloaded from the device. | |||||||||||||||||||||
| !bulkConfigurationCopied | 1.3.6.1.4.1.13742.6.0.54 | ||||||||||||||||||||
notification · current A bulk configuration file was copied to the device. | |||||||||||||||||||||
| !pduSensorStateChange | 1.3.6.1.4.1.13742.6.0.60 | deprecated | |||||||||||||||||||
notification · deprecated Unit-level sensor state change. Which value field to use depends on the metadata of the sensor. measurementsUnitSensorValue is undefined for sensors which can have negative readings, measurementsUnitSensorSignedValue is undefined for sensors whose range exceeds the Integer32 range. Both fields do not apply to sensors without numerical readings. | |||||||||||||||||||||
| !inletSensorStateChange | 1.3.6.1.4.1.13742.6.0.61 | ||||||||||||||||||||
notification · current Inlet sensor state change. Which value field to use depends on the metadata of the sensor. measurementsInletSensorValue is undefined for sensors which can have negative readings, measurementsInletSensorSignedValue is undefined for sensors whose range exceeds the Integer32 range. Both fields do not apply to sensors without numerical readings. For an rcmState sensor transitioning to the fail state, the value is the residual current just before the sensor transitioned to the fail state i.e. if typeOfSensor = rcmState and measurementsInletSensorState = fail, then measurementsInletSensorValue = the residual current just before the sensor transitioned to the fail state
| |||||||||||||||||||||
| !inletPoleSensorStateChange | 1.3.6.1.4.1.13742.6.0.62 | ||||||||||||||||||||
notification · current Inlet pole sensor state change. Which value field to use depends on the metadata of the sensor. measurementsInletPoleSensorValue is undefined for sensors which can have negative readings, measurementsInletPoleSensorSignedValue is undefined for sensors whose range exceeds the Integer32 range. Both fields do not apply to sensors without numerical readings.
| |||||||||||||||||||||
| !outletSensorStateChange | 1.3.6.1.4.1.13742.6.0.63 | ||||||||||||||||||||
notification · current Outlet sensor state change. Which value field to use depends on the metadata of the sensor. measurementsOutletSensorValue is undefined for sensors which can have negative readings, measurementsOutletSensorSignedValue is undefined for sensors whose range exceeds the Integer32 range. Both fields do not apply to sensors without numerical readings.
| |||||||||||||||||||||
| !outletPoleSensorStateChange | 1.3.6.1.4.1.13742.6.0.64 | ||||||||||||||||||||
notification · current Outlet pole sensor state change. Which value field to use depends on the metadata of the sensor. measurementsOutletPoleSensorValue is undefined for sensors which can have negative readings, measurementsOutletPoleSensorSignedValue is undefined for sensors whose range exceeds the Integer32 range. Both fields do not apply to sensors without numerical readings.
| |||||||||||||||||||||
| !overCurrentProtectorSensorStateChange | 1.3.6.1.4.1.13742.6.0.65 | ||||||||||||||||||||
notification · current Overcurrent protector sensor state change. Which value field to use depends on the metadata of the sensor. measurementsOverCurrentProtectorSensorValue is undefined for sensors which can have negative readings, measurementsOverCurrentProtectorSensorSignedValue is undefined for sensors whose range exceeds the Integer32 range. Both fields do not apply to sensors without numerical readings. For trip sensor state changes, if a particular outlet is determined to be likely to have caused the OCP trip, its label is passed in suspectedTripCauseLabel. For an rcmState sensor transitioning to the fail state, the value is the residual current just before the sensor transitioned to the fail state.
| |||||||||||||||||||||
| !externalSensorStateChange | 1.3.6.1.4.1.13742.6.0.66 | ||||||||||||||||||||
notification · current External sensor state change.
| |||||||||||||||||||||
| !smtpMessageTransmissionFailure | 1.3.6.1.4.1.13742.6.0.67 | ||||||||||||||||||||
notification · current SMTP message transmission failure | |||||||||||||||||||||
| !ldapError | 1.3.6.1.4.1.13742.6.0.68 | ||||||||||||||||||||
notification · current An LDAP error occurred; errorDescription describes the error | |||||||||||||||||||||
| !deviceUpdateFailed | 1.3.6.1.4.1.13742.6.0.70 | ||||||||||||||||||||
notification · current The device firmware update has failed. | |||||||||||||||||||||
| !loadSheddingModeEntered | 1.3.6.1.4.1.13742.6.0.71 | ||||||||||||||||||||
notification · current The PDU has entered load shedding mode | |||||||||||||||||||||
| !loadSheddingModeExited | 1.3.6.1.4.1.13742.6.0.72 | ||||||||||||||||||||
notification · current The PDU has exited load shedding mode | |||||||||||||||||||||
| !pingServerEnabled | 1.3.6.1.4.1.13742.6.0.73 | ||||||||||||||||||||
notification · current The ping feature has been enabled for a server. | |||||||||||||||||||||
| !pingServerDisabled | 1.3.6.1.4.1.13742.6.0.74 | ||||||||||||||||||||
notification · current The ping feature has been disabled for a server. | |||||||||||||||||||||
| !serverNotReachable | 1.3.6.1.4.1.13742.6.0.75 | ||||||||||||||||||||
notification · current A monitored server has become unreachable. | |||||||||||||||||||||
| !serverReachable | 1.3.6.1.4.1.13742.6.0.76 | ||||||||||||||||||||
notification · current A monitored server has become reachable. | |||||||||||||||||||||
| !rfCodeTagConnected | 1.3.6.1.4.1.13742.6.0.77 | deprecated | |||||||||||||||||||
notification · deprecated An RF-Code tag has been connected. | |||||||||||||||||||||
| !rfCodeTagDisconnected | 1.3.6.1.4.1.13742.6.0.78 | deprecated | |||||||||||||||||||
notification · deprecated An RF-Code tag has been disconnected. | |||||||||||||||||||||
| !deviceIdentificationChanged | 1.3.6.1.4.1.13742.6.0.79 | ||||||||||||||||||||
notification · current A device identification parameter has been changed. | |||||||||||||||||||||
| !usbExpansionUnitConnected | 1.3.6.1.4.1.13742.6.0.80 | ||||||||||||||||||||
notification · current Connectivity to downstream expansion unit has been established.
It applies to the following interfaces:
USB
Ethernet
This trap is sent only if deviceCascadeType is portForwarding | |||||||||||||||||||||
| !usbExpansionUnitDisconnected | 1.3.6.1.4.1.13742.6.0.81 | ||||||||||||||||||||
notification · current Connectivity to downstream expansion unit has been lost
It applies to the following interfaces:
USB
Ethernet
This trap is sent only if deviceCascadeType is portForwarding | |||||||||||||||||||||
| !lhxSupportChanged | 1.3.6.1.4.1.13742.6.0.82 | deprecated | |||||||||||||||||||
notification · deprecated Schroff LHX support has been enabled or disabled. | |||||||||||||||||||||
| !userAcceptedRestrictedServiceAgreement | 1.3.6.1.4.1.13742.6.0.83 | ||||||||||||||||||||
notification · current A user accepted the Restricted Service Agreement. | |||||||||||||||||||||
| !userDeclinedRestrictedServiceAgreement | 1.3.6.1.4.1.13742.6.0.84 | ||||||||||||||||||||
notification · current A user declined the Restricted Service Agreement. | |||||||||||||||||||||
| !wireSensorStateChange | 1.3.6.1.4.1.13742.6.0.85 | obsolete | |||||||||||||||||||
notification · obsolete Wire sensor state change. | |||||||||||||||||||||
| !transferSwitchSensorStateChange | 1.3.6.1.4.1.13742.6.0.86 | ||||||||||||||||||||
notification · current Transfer switch sensor state change. Which value field to use depends on the metadata of the sensor. measurementsTransferSwitchSensorValue is undefined for sensors which can have negative readings, measurementsTransferSwitchSensorSignedValue is undefined for sensors whose range exceeds the Integer32 range. Both fields do not apply to sensors without numerical readings.
| |||||||||||||||||||||
| !deviceSettingsSaved | 1.3.6.1.4.1.13742.6.0.88 | ||||||||||||||||||||
notification · current A configuration backup has been downloaded from the device. | |||||||||||||||||||||
| !deviceSettingsRestored | 1.3.6.1.4.1.13742.6.0.89 | ||||||||||||||||||||
notification · current A configuration backup has been restored to the device. | |||||||||||||||||||||
| !webcamInserted | 1.3.6.1.4.1.13742.6.0.90 | ||||||||||||||||||||
notification · current A webcam has been connected. | |||||||||||||||||||||
| !webcamRemoved | 1.3.6.1.4.1.13742.6.0.91 | ||||||||||||||||||||
notification · current A webcam has been disconnected. | |||||||||||||||||||||
| !inletEnabled | 1.3.6.1.4.1.13742.6.0.92 | ||||||||||||||||||||
notification · current PDU operation has been enabled for an inlet | |||||||||||||||||||||
| !inletDisabled | 1.3.6.1.4.1.13742.6.0.93 | ||||||||||||||||||||
notification · current PDU operation has been disabled for an inlet | |||||||||||||||||||||
| !serverConnectivityUnrecoverable | 1.3.6.1.4.1.13742.6.0.94 | ||||||||||||||||||||
notification · current The connection to a monitored server could not be recovered. | |||||||||||||||||||||
| !radiusError | 1.3.6.1.4.1.13742.6.0.95 | ||||||||||||||||||||
notification · current A Radius error occurred; errorDescription describes the error | |||||||||||||||||||||
| !serverReachabilityError | 1.3.6.1.4.1.13742.6.0.96 | ||||||||||||||||||||
notification · current Server reachability error occurred; errorDescription describes the error.
This trap is sent when the Error state is entered.
Reasons for transitioning to the Error state include the following:
Unable to resolve the server hostname. | |||||||||||||||||||||
| !inletSensorReset | 1.3.6.1.4.1.13742.6.0.97 | ||||||||||||||||||||
notification · current An inlet sensor was reset. | |||||||||||||||||||||
| !outletSensorReset | 1.3.6.1.4.1.13742.6.0.98 | ||||||||||||||||||||
notification · current An outlet sensor was reset. | |||||||||||||||||||||
| !unknownPeripheralDeviceAttached | 1.3.6.1.4.1.13742.6.0.99 | ||||||||||||||||||||
notification · current An unsupported peripheral device was attached. | |||||||||||||||||||||
| !peripheralDeviceFirmwareUpdate | 1.3.6.1.4.1.13742.6.0.100 | ||||||||||||||||||||
notification · current The firmware update state of a peripheral device changed while performing update to peripheralDevicePackageFirmwareVersion. | |||||||||||||||||||||
| !unitSensorReset | 1.3.6.1.4.1.13742.6.0.101 | ||||||||||||||||||||
notification · current An unit sensor was reset. | |||||||||||||||||||||
| !unitSensorStateChange | 1.3.6.1.4.1.13742.6.0.102 | ||||||||||||||||||||
notification · current Unit-level sensor state change. Which value field to use depends on the metadata of the sensor. measurementsUnitSensorValue is undefined for sensors which can have negative readings, measurementsUnitSensorSignedValue is undefined for sensors whose range exceeds the Integer32 range. Both fields do not apply to sensors without numerical readings. | |||||||||||||||||||||
| !circuitSensorStateChange | 1.3.6.1.4.1.13742.6.0.103 | ||||||||||||||||||||
notification · current BCM2/PMC branch circuit sensor state change. Which value field to use depends on the metadata of the sensor. measurementsCircuitSensorValue is undefined for sensors which can have negative readings, measurementsCircuitSensorSignedValue is undefined for sensors whose range exceeds the Integer32 range. Both fields do not apply to sensors without numerical readings.
| |||||||||||||||||||||
| !circuitPoleSensorStateChange | 1.3.6.1.4.1.13742.6.0.104 | ||||||||||||||||||||
notification · current BCM2/PMC circuit pole sensor state change. Which value field to use depends on the metadata of the sensor. measurementsCircuitPoleSensorValue is undefined for sensors which can have negative readings, measurementsCircuitPoleSensorSignedValue is undefined for sensors whose range exceeds the Integer32 range. Both fields do not apply to sensors without numerical readings.
| |||||||||||||||||||||
| !circuitAdded | 1.3.6.1.4.1.13742.6.0.105 | ||||||||||||||||||||
notification · current A new branch circuit has been configured | |||||||||||||||||||||
| !circuitDeleted | 1.3.6.1.4.1.13742.6.0.106 | ||||||||||||||||||||
notification · current A configured branch circuit has been deleted | |||||||||||||||||||||
| !circuitModified | 1.3.6.1.4.1.13742.6.0.107 | ||||||||||||||||||||
notification · current A configured branch circuit has been modified | |||||||||||||||||||||
| !circuitSensorReset | 1.3.6.1.4.1.13742.6.0.108 | ||||||||||||||||||||
notification · current An circuit sensor was reset. | |||||||||||||||||||||
| !powerMeterAdded | 1.3.6.1.4.1.13742.6.0.109 | ||||||||||||||||||||
notification · current A new power meter or panel has been configured
| |||||||||||||||||||||
| !powerMeterDeleted | 1.3.6.1.4.1.13742.6.0.110 | ||||||||||||||||||||
notification · current A configured power meter has been deleted | |||||||||||||||||||||
| !powerMeterModified | 1.3.6.1.4.1.13742.6.0.111 | ||||||||||||||||||||
notification · current A configured power meter has been modified | |||||||||||||||||||||
| !smsMessageTransmissionFailure | 1.3.6.1.4.1.13742.6.0.112 | ||||||||||||||||||||
notification · current Sending an SMS message failed. | |||||||||||||||||||||
| !smartCardInserted | 1.3.6.1.4.1.13742.6.0.113 | ||||||||||||||||||||
notification · current A smartcard was inserted into a card reader.
| |||||||||||||||||||||
| !smartCardRemoved | 1.3.6.1.4.1.13742.6.0.114 | ||||||||||||||||||||
notification · current A smartcard was removed from a card reader.
| |||||||||||||||||||||
| !rawConfigurationDownloaded | 1.3.6.1.4.1.13742.6.0.115 | ||||||||||||||||||||
notification · current The raw configuration was downloaded from the device. | |||||||||||||||||||||
| !rawConfigurationUpdated | 1.3.6.1.4.1.13742.6.0.116 | ||||||||||||||||||||
notification · current A raw configuration update was applied on the device. | |||||||||||||||||||||
| !hwFailureStatusChanged | 1.3.6.1.4.1.13742.6.0.117 | ||||||||||||||||||||
notification · current A hardware component's failure state has changed. | |||||||||||||||||||||
| !outletGroupAdded | 1.3.6.1.4.1.13742.6.0.118 | ||||||||||||||||||||
notification · current A new outlet group has been configured | |||||||||||||||||||||
| !outletGroupModified | 1.3.6.1.4.1.13742.6.0.119 | ||||||||||||||||||||
notification · current A configured outlet group has been modified | |||||||||||||||||||||
| !outletGroupDeleted | 1.3.6.1.4.1.13742.6.0.120 | ||||||||||||||||||||
notification · current A configured outlet group has been deleted | |||||||||||||||||||||
| !outletGroupSensorStateChange | 1.3.6.1.4.1.13742.6.0.121 | ||||||||||||||||||||
notification · current Outlet group sensor state change. Which value field to use depends on the metadata of the sensor. measurementsOutletGroupSensorValue is undefined for sensors which can have negative readings, measurementsOutletGroupSensorSignedValue is undefined for sensors whose range exceeds the Integer32 range. Both fields do not apply to sensors without numerical readings.
| |||||||||||||||||||||
| !outletGroupSensorReset | 1.3.6.1.4.1.13742.6.0.122 | ||||||||||||||||||||
notification · current An outlet group sensor was reset. | |||||||||||||||||||||
| !outletGroupPowerControl | 1.3.6.1.4.1.13742.6.0.123 | ||||||||||||||||||||
notification · current An outlet group switching operation has been performed. | |||||||||||||||||||||
| !serverPowerControlInitiated | 1.3.6.1.4.1.13742.6.0.124 | ||||||||||||||||||||
notification · current A server power control operation was initiated. | |||||||||||||||||||||
| !serverPowerControlCompleted | 1.3.6.1.4.1.13742.6.0.125 | ||||||||||||||||||||
notification · current A server power control operation has completed. | |||||||||||||||||||||
| !webcamStorageUploadStarted | 1.3.6.1.4.1.13742.6.0.126 | ||||||||||||||||||||
notification · current A new snapshot upload to webcam storage has started. | |||||||||||||||||||||
| !testEventTriggered | 1.3.6.1.4.1.13742.6.0.127 | ||||||||||||||||||||
notification · current A test event was triggered. | |||||||||||||||||||||
| !actuatorSwitched | 1.3.6.1.4.1.13742.6.0.128 | ||||||||||||||||||||
notification · current An actuator control operation has been performed. | |||||||||||||||||||||
| !keypadPinEntered | 1.3.6.1.4.1.13742.6.0.129 | ||||||||||||||||||||
notification · current A PIN was entered into a keypad. | |||||||||||||||||||||
| !doorAccessGranted | 1.3.6.1.4.1.13742.6.0.130 | ||||||||||||||||||||
notification · current Door access was granted. | |||||||||||||||||||||
| !doorAccessDenied | 1.3.6.1.4.1.13742.6.0.131 | ||||||||||||||||||||
notification · current Door access was denied. | |||||||||||||||||||||
| !doorAccessRuleAdded | 1.3.6.1.4.1.13742.6.0.132 | ||||||||||||||||||||
notification · current A door access rule was added. | |||||||||||||||||||||
| !doorAccessRuleChanged | 1.3.6.1.4.1.13742.6.0.133 | ||||||||||||||||||||
notification · current A door access rule was changed. | |||||||||||||||||||||
| !doorAccessRuleDeleted | 1.3.6.1.4.1.13742.6.0.134 | ||||||||||||||||||||
notification · current A door access rule was deleted. | |||||||||||||||||||||
| !inletLinePairSensorStateChange | 1.3.6.1.4.1.13742.6.0.135 | ||||||||||||||||||||
notification · current Inlet line pair sensor state change. Which value field to use depends on the metadata of the sensor. measurementsInletLinePairSensorValue is undefined for sensors which can have negative readings, measurementsInletLinePairSensorSignedValue is undefined for sensors whose range exceeds the Integer32 range. Both fields do not apply to sensors without numerical readings.
| |||||||||||||||||||||
| !tacPlusError | 1.3.6.1.4.1.13742.6.0.136 | ||||||||||||||||||||
notification · current A TACACS+ error occurred; errorDescription describes the error | |||||||||||||||||||||
| !outletSuspended | 1.3.6.1.4.1.13742.6.0.137 | ||||||||||||||||||||
notification · current An outlet was suspended after being suspected to have caused an OCP trip event. | |||||||||||||||||||||
| !userRenamed | 1.3.6.1.4.1.13742.6.0.138 | ||||||||||||||||||||
notification · current A user account was renamed. | |||||||||||||||||||||
| !inletDipEvent | 1.3.6.1.4.1.13742.6.0.151 | ||||||||||||||||||||
notification · current Dip event on the inlet voltage sensor. | |||||||||||||||||||||
| !inletSwellEvent | 1.3.6.1.4.1.13742.6.0.152 | ||||||||||||||||||||
notification · current Dip event on the inlet voltage sensor. | |||||||||||||||||||||
| !inletPoleDipEvent | 1.3.6.1.4.1.13742.6.0.153 | ||||||||||||||||||||
notification · current Dip event on the voltage sensor of an inlet pole. | |||||||||||||||||||||
| !inletPoleSwellEvent | 1.3.6.1.4.1.13742.6.0.154 | ||||||||||||||||||||
notification · current Swell event on the voltage sensor of an inlet pole. | |||||||||||||||||||||
| !portFuseStateChange | 1.3.6.1.4.1.13742.6.0.155 | ||||||||||||||||||||
notification · current The state of a port fuse changed. | |||||||||||||||||||||
| !linkUnitAdded | 1.3.6.1.4.1.13742.6.0.156 | ||||||||||||||||||||
notification · current A new link unit has been added. | |||||||||||||||||||||
| !linkUnitReleased | 1.3.6.1.4.1.13742.6.0.157 | ||||||||||||||||||||
notification · current A link unit has been released. | |||||||||||||||||||||
| !linkUnitCommunicationOk | 1.3.6.1.4.1.13742.6.0.158 | ||||||||||||||||||||
notification · current Communication with link unit is OK. | |||||||||||||||||||||
| !linkUnitCommunicationFailed | 1.3.6.1.4.1.13742.6.0.159 | ||||||||||||||||||||
notification · current Communication with a link unit failed. | |||||||||||||||||||||
| !doorMechanicallyUnlocked | 1.3.6.1.4.1.13742.6.0.160 | ||||||||||||||||||||
notification · current A door handle was opened without being electronically unlocked. | |||||||||||||||||||||
| !doorForcedOpen | 1.3.6.1.4.1.13742.6.0.161 | ||||||||||||||||||||
notification · current A door was opened without unlocking the door handle. | |||||||||||||||||||||
| !outletServiceModeChanged | 1.3.6.1.4.1.13742.6.0.162 | ||||||||||||||||||||
notification · current Service mode was changed on an outlet. | |||||||||||||||||||||
| Nboard | 1.3.6.1.4.1.13742.6.1 | ||||||||||||||||||||
| Nenvironmental | 1.3.6.1.4.1.13742.6.2 | ||||||||||||||||||||
| Nconfiguration | 1.3.6.1.4.1.13742.6.3 | ||||||||||||||||||||
| SpduCount | 1.3.6.1.4.1.13742.6.3.1 | Integer32 | RO | ||||||||||||||||||
scalar · Integer32 · read-only · current The number of PDUs managed by this MIB. For BCM2 and PMC, pduCount is the number of power meters plus 1 (for the main controller). For all other products, pduCount is the number of link units, including the primary unit. | |||||||||||||||||||||
| Nunit | 1.3.6.1.4.1.13742.6.3.2 | ||||||||||||||||||||
| TnameplateTable | 1.3.6.1.4.1.13742.6.3.2.1 | NA | |||||||||||||||||||
table · not-accessible · current A list of PDU nameplate entries. The number of entries is given by the value of pduCount. | |||||||||||||||||||||
| RnameplateEntry | 1.3.6.1.4.1.13742.6.3.2.1.1 | NA | |||||||||||||||||||
| CpduId | 1.3.6.1.4.1.13742.6.3.2.1.1.1 | Integer32 (0..256) | NA | ||||||||||||||||||
column · Integer32 (0..256) · not-accessible · current A unique value for each PDU or power meter.
For BCM2 and PMC, pduId can be:
- 0 for the main controller
- The meter ID (rotary switch) for power meter
For all other products, pduId is the PDU's link ID. If linking
is not used, pduId is 1. | |||||||||||||||||||||
| CpduManufacturer | 1.3.6.1.4.1.13742.6.3.2.1.1.2 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current The PDU manufacturer. | |||||||||||||||||||||
| CpduModel | 1.3.6.1.4.1.13742.6.3.2.1.1.3 | DisplayString | RO | PX3-5493U-K2 | |||||||||||||||||
column · DisplayString · read-only · current The PDU model name. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CpduSerialNumber | 1.3.6.1.4.1.13742.6.3.2.1.1.4 | DisplayString | RO | <private> | |||||||||||||||||
column · DisplayString · read-only · current The PDU serial number. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CpduRatedVoltage | 1.3.6.1.4.1.13742.6.3.2.1.1.5 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current The PDU voltage rating. | |||||||||||||||||||||
| CpduRatedCurrent | 1.3.6.1.4.1.13742.6.3.2.1.1.6 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current The PDU current rating. | |||||||||||||||||||||
| CpduRatedFrequency | 1.3.6.1.4.1.13742.6.3.2.1.1.7 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current The PDU frequency rating. | |||||||||||||||||||||
| CpduRatedVA | 1.3.6.1.4.1.13742.6.3.2.1.1.8 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current The PDU VA (VoltAmps) rating. | |||||||||||||||||||||
| CpduImage | 1.3.6.1.4.1.13742.6.3.2.1.1.9 | URL | RO | ||||||||||||||||||
column · URL · read-only · current The URL of the wiring diagram for this PDU. | |||||||||||||||||||||
| TunitConfigurationTable | 1.3.6.1.4.1.13742.6.3.2.2 | NA | |||||||||||||||||||
table · not-accessible · current A list of PDU configuration entries. The number of entries is given by the value of pduCount. | |||||||||||||||||||||
| RunitConfigurationEntry | 1.3.6.1.4.1.13742.6.3.2.2.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing configuration objects for a particular PDU.
| |||||||||||||||||||||
| CinletCount | 1.3.6.1.4.1.13742.6.3.2.2.1.2 | Integer32 (0..256) | RO | ||||||||||||||||||
column · Integer32 (0..256) · read-only · current The number of inlets. | |||||||||||||||||||||
| CoverCurrentProtectorCount | 1.3.6.1.4.1.13742.6.3.2.2.1.3 | Integer32 (0..255) | RO | ||||||||||||||||||
column · Integer32 (0..255) · read-only · current The number of overcurrent protectors. | |||||||||||||||||||||
| CoutletCount | 1.3.6.1.4.1.13742.6.3.2.2.1.4 | Integer32 (0..256) | RO | ||||||||||||||||||
column · Integer32 (0..256) · read-only · current The number of outlets. | |||||||||||||||||||||
| CinletControllerCount | 1.3.6.1.4.1.13742.6.3.2.2.1.5 | Integer32 (0..255) | RO | ||||||||||||||||||
column · Integer32 (0..255) · read-only · current The number of inlet controllers. | |||||||||||||||||||||
| CoutletControllerCount | 1.3.6.1.4.1.13742.6.3.2.2.1.6 | Integer32 (0..255) | RO | ||||||||||||||||||
column · Integer32 (0..255) · read-only · current The number of outlet controllers. | |||||||||||||||||||||
| CexternalSensorCount | 1.3.6.1.4.1.13742.6.3.2.2.1.7 | Integer32 (0..255) | RO | ||||||||||||||||||
column · Integer32 (0..255) · read-only · current The maximum supported number of external sensors. This value is fixed and does not reflect how many sensors are actually connected. | |||||||||||||||||||||
| CpxIPAddress | 1.3.6.1.4.1.13742.6.3.2.2.1.8 | IpAddress | RO | deprecated | |||||||||||||||||
column · IpAddress · read-only · deprecated The current IP address. A value of 0.0.0.0 indicates an error or an unset option. | |||||||||||||||||||||
| Cnetmask | 1.3.6.1.4.1.13742.6.3.2.2.1.9 | IpAddress | RO | deprecated | |||||||||||||||||
column · IpAddress · read-only · deprecated The current netmask. A value of 0.0.0.0 indicates an error or an unset option. | |||||||||||||||||||||
| Cgateway | 1.3.6.1.4.1.13742.6.3.2.2.1.10 | IpAddress | RO | deprecated | |||||||||||||||||
column · IpAddress · read-only · deprecated The current gateway. A value of 0.0.0.0 indicates an error or an unset option. | |||||||||||||||||||||
| CpxMACAddress | 1.3.6.1.4.1.13742.6.3.2.2.1.11 | MacAddress | RO | deprecated | |||||||||||||||||
column · MacAddress · read-only · deprecated The current MAC address. If bridge interface is enabled, then equal to the MAC address of Ethernet 1 else if Ethernet 1 is enabled, then equal to the MAC address of Ethernet 1 else if Ethernet 2 is enabled, then equal to the MAC address of Ethernet 2 else if Wlan is enabled, then equal to the MAC address of Wlan else return SNMP_ERR_NOSUCHNAME | |||||||||||||||||||||
| CutcOffset | 1.3.6.1.4.1.13742.6.3.2.2.1.12 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current The current UTC offset. | |||||||||||||||||||||
| CpduName | 1.3.6.1.4.1.13742.6.3.2.2.1.13 | DisplayString | RW | ||||||||||||||||||
column · DisplayString · read-write · current The user-defined name for the PDU. | |||||||||||||||||||||
| CnetworkInterfaceType | 1.3.6.1.4.1.13742.6.3.2.2.1.14 | NetworkInterfaceTypeEnumeration | RO | deprecated | |||||||||||||||||
column · NetworkInterfaceTypeEnumeration · read-only · deprecated The network interface type: wired or wireless. If only the Wireless interface is enabled, then equal to wireless else equal to wired | |||||||||||||||||||||
| CexternalSensorsZCoordinateUnits | 1.3.6.1.4.1.13742.6.3.2.2.1.34 | ExternalSensorsZCoordinateUnitsEnumeration | RW | ||||||||||||||||||
column · ExternalSensorsZCoordinateUnitsEnumeration · read-write · current External sensor Z coordinate units: freeform text or rack units (U) Default is U. | |||||||||||||||||||||
| CunitDeviceCapabilities | 1.3.6.1.4.1.13742.6.3.2.2.1.35 | Bits | RO | ||||||||||||||||||
column · Bits · read-only · current A bit string indicating which unit sensors are available.
| |||||||||||||||||||||
| CoutletSequencingDelay | 1.3.6.1.4.1.13742.6.3.2.2.1.36 | Unsigned32 (100..10000) | RW | deprecated | |||||||||||||||||
column · Unsigned32 (100..10000) · read-write · deprecated This OID is deprecated, it is an alias for inrushGuardDelay | |||||||||||||||||||||
| CglobalOutletPowerCyclingPowerOffPeriod | 1.3.6.1.4.1.13742.6.3.2.2.1.37 | Unsigned32 (1..3600) | RW | ||||||||||||||||||
column · Unsigned32 (1..3600) · read-write · current The power-off period when an outlet is cycled; applies to all outlets unless overridden at the outlet level; specified in seconds; 1 <= value <= 3600 seconds. | |||||||||||||||||||||
| CglobalOutletStateOnStartup | 1.3.6.1.4.1.13742.6.3.2.2.1.38 | GlobalOutletStateOnStartupEnumeration | RW | ||||||||||||||||||
column · GlobalOutletStateOnStartupEnumeration · read-write · current The outlet state used when powering the respective inlet; applies to all outlets unless overridden at the outlet level. Note that this value is ignored if relayBehaviorOnPowerLoss is set to latching. | |||||||||||||||||||||
| CoutletPowerupSequence | 1.3.6.1.4.1.13742.6.3.2.2.1.39 | DisplayString | RW | ||||||||||||||||||
column · DisplayString · read-write · current The sequence in which will the outlets will be switched on under the following conditions. 1) Switch all outlets on operation is executed 2) Power to the PDU is cycled String must consist of a comma separated sequence of the outlet numbers and all outlet numbers must be included. The numbers entered must be a permutation of the numbers 1,2,3,-outletnumber. Example for a 12 outlet PDU: 1,12,3,5,6,7,10,2,4,11,9,8. The per outlet sequence delays are defined as outletSequenceDelay in the outletConfigurationTable | |||||||||||||||||||||
| CpduPowerCyclingPowerOffPeriod | 1.3.6.1.4.1.13742.6.3.2.2.1.40 | Unsigned32 (1..3600) | RW | ||||||||||||||||||
column · Unsigned32 (1..3600) · read-write · current When power to the PX is cycled (either manually or because of a temporary power loss), this number determines how many seconds the PX will wait before it provides power to the outlets. specified in seconds: 1 <= value <= 3600 seconds. Note that this value is ignored if relayBehaviorOnPowerLoss is set to latching. | |||||||||||||||||||||
| CpduDaisychainMemberType | 1.3.6.1.4.1.13742.6.3.2.2.1.41 | DaisychainMemberTypeEnumeration | RO | ||||||||||||||||||
column · DaisychainMemberTypeEnumeration · read-only · current The role of the unit in a port forwarding USB or Ethernet cascade | |||||||||||||||||||||
| CmanagedExternalSensorCount | 1.3.6.1.4.1.13742.6.3.2.2.1.42 | Integer32 (0..255) | RO | ||||||||||||||||||
column · Integer32 (0..255) · read-only · current The number of managed external sensors | |||||||||||||||||||||
| CpxInetAddressType | 1.3.6.1.4.1.13742.6.3.2.2.1.50 | InetAddressType | RO | deprecated | |||||||||||||||||
column · InetAddressType · read-only · deprecated The type of address format This object is deprecated in favor of ipAddressTable from the IP-MIB (rfc4293). | |||||||||||||||||||||
| CpxInetIPAddress | 1.3.6.1.4.1.13742.6.3.2.2.1.51 | InetAddress | RO | deprecated | |||||||||||||||||
column · InetAddress · read-only · deprecated The current IP address. A value of 0.0.0.0 indicates an error or an unset option. This object is deprecated in favor of ipAddressTable from the IP-MIB (rfc4293). For IPv6, its value is 0.0.0.0 | |||||||||||||||||||||
| CpxInetNetmask | 1.3.6.1.4.1.13742.6.3.2.2.1.52 | InetAddress | RO | deprecated | |||||||||||||||||
column · InetAddress · read-only · deprecated The current netmask. A value of 0.0.0.0 indicates an error or an unset option. This object is deprecated in favor of ipAddressTable from the IP-MIB (rfc4293). For IPv6, its value is 0.0.0.0 | |||||||||||||||||||||
| CpxInetGateway | 1.3.6.1.4.1.13742.6.3.2.2.1.53 | InetAddress | RO | deprecated | |||||||||||||||||
column · InetAddress · read-only · deprecated The current gateway. A value of 0.0.0.0 indicates an error or an unset option. This object is deprecated in favor of ipAddressTable from the IP-MIB (rfc4293). For IPv6, its value is 0.0.0.0 | |||||||||||||||||||||
| CloadShedding | 1.3.6.1.4.1.13742.6.3.2.2.1.55 | TruthValue | RW | ||||||||||||||||||
column · TruthValue · read-write · current Enter/Exit Load Shedding Mode | |||||||||||||||||||||
| CserverCount | 1.3.6.1.4.1.13742.6.3.2.2.1.56 | Integer32 (0..255) | RO | ||||||||||||||||||
column · Integer32 (0..255) · read-only · current The number of servers monitored with the server reachability feature | |||||||||||||||||||||
| CinrushGuardDelay | 1.3.6.1.4.1.13742.6.3.2.2.1.57 | Unsigned32 (100..10000) | RW | ||||||||||||||||||
column · Unsigned32 (100..10000) · read-write · current The time interval between switching on two outlets; specified in milliseconds; 100 <= value <= 10000 milliseconds. | |||||||||||||||||||||
| CcascadedDeviceConnected | 1.3.6.1.4.1.13742.6.3.2.2.1.58 | TruthValue | RO | ||||||||||||||||||
column · TruthValue · read-only · current Indicates whether another PX2 is connected using an USB cable to the USB-A port of this PX2 in a cascaded configuration. | |||||||||||||||||||||
| CsynchronizeWithNTPServer | 1.3.6.1.4.1.13742.6.3.2.2.1.59 | TruthValue | RW | ||||||||||||||||||
column · TruthValue · read-write · current Indicates whether time is synchronized with an NTP server. | |||||||||||||||||||||
| CuseDHCPProvidedNTPServer | 1.3.6.1.4.1.13742.6.3.2.2.1.60 | TruthValue | RW | obsolete | |||||||||||||||||
column · TruthValue · read-write · obsolete **NOTE: This object is obsolete. Its functionality has been replaced by the following: - If at least one of firstNTPServerAddress and secondNTPServerAddress has been configured then use the static NTP servers - else use the DHCP-provided NTP servers | |||||||||||||||||||||
| CfirstNTPServerAddressType | 1.3.6.1.4.1.13742.6.3.2.2.1.61 | InetAddressType | RW | ||||||||||||||||||
column · InetAddressType · read-write · current Represents the type of the corresponding instance of firstNTPServerAddress object. When setting this value, be sure that firstNTPServerAddress is of this address type, e.g. by setting both of them. | |||||||||||||||||||||
| CfirstNTPServerAddress | 1.3.6.1.4.1.13742.6.3.2.2.1.62 | InetAddress | RW | ||||||||||||||||||
column · InetAddress · read-write · current The address of the primary NTP server. When setting this value, be sure that it is of the type specified in firstNTPServerAddressType, e.g. by setting both of them. | |||||||||||||||||||||
| CsecondNTPServerAddressType | 1.3.6.1.4.1.13742.6.3.2.2.1.63 | InetAddressType | RW | ||||||||||||||||||
column · InetAddressType · read-write · current Represents the type of the corresponding instance of secondNTPServerAddress object. When setting this value, be sure that secondNTPServerAddress is of this address type, e.g. by setting both of them. Default is ipv4 | |||||||||||||||||||||
| CsecondNTPServerAddress | 1.3.6.1.4.1.13742.6.3.2.2.1.64 | InetAddress | RW | ||||||||||||||||||
column · InetAddress · read-write · current The address of the second NTP server. When setting this value, be sure that it is of the type specified in secondNTPServerAddressType, e.g. by setting both of them. | |||||||||||||||||||||
| CwireCount | 1.3.6.1.4.1.13742.6.3.2.2.1.65 | Integer32 (0..255) | RO | obsolete | |||||||||||||||||
column · Integer32 (0..255) · read-only · obsolete The number of wire objects in the PDU topology. This feature is no longer used, the returned value is always 0. | |||||||||||||||||||||
| CtransferSwitchCount | 1.3.6.1.4.1.13742.6.3.2.2.1.66 | Integer32 (0..255) | RO | ||||||||||||||||||
column · Integer32 (0..255) · read-only · current The number of transfer switches. | |||||||||||||||||||||
| CproductType | 1.3.6.1.4.1.13742.6.3.2.2.1.67 | ProductTypeEnumeration | RO | ||||||||||||||||||
column · ProductTypeEnumeration · read-only · current The product type (PDU, BCM, transfer switch or power meter). | |||||||||||||||||||||
| CmeteringControllerCount | 1.3.6.1.4.1.13742.6.3.2.2.1.68 | Integer32 (0..255) | RO | ||||||||||||||||||
column · Integer32 (0..255) · read-only · current The number of metering controllers. | |||||||||||||||||||||
| CrelayBehaviorOnPowerLoss | 1.3.6.1.4.1.13742.6.3.2.2.1.69 | RelayPowerLossBehaviorEnumeration | RW | ||||||||||||||||||
column · RelayPowerLossBehaviorEnumeration · read-write · current The relay behavior on power loss (latching or non-latching). | |||||||||||||||||||||
| CdeviceCascadeType | 1.3.6.1.4.1.13742.6.3.2.2.1.70 | DeviceCascadeTypeEnumeration | RO | ||||||||||||||||||
column · DeviceCascadeTypeEnumeration · read-only · current The type of network cascade this device is part of (none, bridging or port forwarding). | |||||||||||||||||||||
| CdeviceCascadePosition | 1.3.6.1.4.1.13742.6.3.2.2.1.71 | Integer32 (0..99) | RO | ||||||||||||||||||
column · Integer32 (0..99) · read-only · current The position of the device in the cascade chain. Only supported in port forwarding mode, 0 otherwise. | |||||||||||||||||||||
| CperipheralDevicesAutoManagement | 1.3.6.1.4.1.13742.6.3.2.2.1.72 | TruthValue | RW | ||||||||||||||||||
column · TruthValue · read-write · current Defines whether newly-connected peripheral devices are automatically assigned to an unused slot. | |||||||||||||||||||||
| CfrontPanelOutletSwitching | 1.3.6.1.4.1.13742.6.3.2.2.1.73 | TruthValue | RW | ||||||||||||||||||
column · TruthValue · read-write · current Enables/disables switching of outlets using the PDU front panel. | |||||||||||||||||||||
| CfrontPanelRCMSelfTest | 1.3.6.1.4.1.13742.6.3.2.2.1.74 | TruthValue | RW | ||||||||||||||||||
column · TruthValue · read-write · current Enables/disables front panel RCM self-test. | |||||||||||||||||||||
| CfrontPanelActuatorControl | 1.3.6.1.4.1.13742.6.3.2.2.1.75 | TruthValue | RW | ||||||||||||||||||
column · TruthValue · read-write · current Enables/disables front panel peripheral actuator control. | |||||||||||||||||||||
| CcircuitCount | 1.3.6.1.4.1.13742.6.3.2.2.1.76 | Integer32 (0..96) | RO | ||||||||||||||||||
column · Integer32 (0..96) · read-only · current The number of branch circuits in a panel. | |||||||||||||||||||||
| CactiveDNSServerCount | 1.3.6.1.4.1.13742.6.3.2.2.1.77 | Integer32 (0..16) | RO | ||||||||||||||||||
column · Integer32 (0..16) · read-only · current The number of active DNS servers | |||||||||||||||||||||
| CactiveNTPServerCount | 1.3.6.1.4.1.13742.6.3.2.2.1.78 | Integer32 (0..16) | RO | ||||||||||||||||||
column · Integer32 (0..16) · read-only · current The number of active NTP servers | |||||||||||||||||||||
| CperipheralDevicePackageCount | 1.3.6.1.4.1.13742.6.3.2.2.1.79 | Integer32 (0..256) | RO | ||||||||||||||||||
column · Integer32 (0..256) · read-only · current The number of peripheral device packages. | |||||||||||||||||||||
| CoutletGroupCount | 1.3.6.1.4.1.13742.6.3.2.2.1.80 | Integer32 (0..128) | RO | ||||||||||||||||||
column · Integer32 (0..128) · read-only · current The number of configured outlet groups | |||||||||||||||||||||
| CdemandUpdateInterval | 1.3.6.1.4.1.13742.6.3.2.2.1.81 | Unsigned32 (15..300) | RW | ||||||||||||||||||
column · Unsigned32 (15..300) · read-write · current The update interval (in seconds) for demand sensors (BCM2 only). Demand sensors report the average active power within the averaging period. The sensor reading is updated every 'demandUpdateInterval' seconds and averaged over the number of intervals configured in 'demandAveragingIntervals'. The resulting averaging period is the product of the two values. | |||||||||||||||||||||
| CdemandAveragingIntervals | 1.3.6.1.4.1.13742.6.3.2.2.1.82 | Unsigned32 (1..60) | RW | ||||||||||||||||||
column · Unsigned32 (1..60) · read-write · current The number of intervals for demand sensor averaging (BCM2 only). Demand sensors report the average active power within the averaging period. The sensor reading is updated every 'demandUpdateInterval' seconds and averaged over the number of intervals configured in 'demandAveragingIntervals'. The resulting averaging period is the product of the two values. | |||||||||||||||||||||
| ChasDCInlets | 1.3.6.1.4.1.13742.6.3.2.2.1.83 | TruthValue | RO | ||||||||||||||||||
column · TruthValue · read-only · current True if the PDU has at least one DC inlet | |||||||||||||||||||||
| CpduOrientation | 1.3.6.1.4.1.13742.6.3.2.2.1.84 | PduOrientationEnumeration | RO | ||||||||||||||||||
column · PduOrientationEnumeration · read-only · current The detected PDU orientation at startup (none if orientation is not supported). | |||||||||||||||||||||
| CpduUptime | 1.3.6.1.4.1.13742.6.3.2.2.1.85 | Unsigned32 (0..4294967295) | RO | ||||||||||||||||||
column · Unsigned32 (0..4294967295) · read-only · current The number of seconds elapsed since the PDU booted. Link units are not supported and return 0. | |||||||||||||||||||||
| CtripCauseOutletHandling | 1.3.6.1.4.1.13742.6.3.2.2.1.86 | TripCauseOutletHandlingEnumeration | RW | ||||||||||||||||||
column · TripCauseOutletHandlingEnumeration · read-write · current How to handle outlets that are suspected to have caused an OCP trip event. | |||||||||||||||||||||
| TcontrollerConfigurationTable | 1.3.6.1.4.1.13742.6.3.2.3 | NA | |||||||||||||||||||
table · not-accessible · current A list of entries for the boards in a PDU. The number of entries is one more than the sum of inletControllerCount, outletControllerCount and meterControllerCount. | |||||||||||||||||||||
| RcontrollerConfigurationEntry | 1.3.6.1.4.1.13742.6.3.2.3.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing objects for a controller.
| |||||||||||||||||||||
| CboardType | 1.3.6.1.4.1.13742.6.3.2.3.1.1 | BoardTypeEnumeration | NA | ||||||||||||||||||
column · BoardTypeEnumeration · not-accessible · current The type of board. | |||||||||||||||||||||
| CboardIndex | 1.3.6.1.4.1.13742.6.3.2.3.1.2 | Integer32 (1..256) | NA | ||||||||||||||||||
column · Integer32 (1..256) · not-accessible · current A unique value for each controller. | |||||||||||||||||||||
| CboardVersion | 1.3.6.1.4.1.13742.6.3.2.3.1.4 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current The board hardware version. | |||||||||||||||||||||
| CboardFirmwareVersion | 1.3.6.1.4.1.13742.6.3.2.3.1.6 | DisplayString | RO | 4.2.0.5-50274 | |||||||||||||||||
column · DisplayString · read-only · current The firmware version. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CboardFirmwareTimeStamp | 1.3.6.1.4.1.13742.6.3.2.3.1.8 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The time when the board firmware was updated as UNIX timestamp. It is measured in seconds since January 1, 1970 (midnight UTC/GMT) | |||||||||||||||||||||
| TlogConfigurationTable | 1.3.6.1.4.1.13742.6.3.2.4 | NA | |||||||||||||||||||
table · not-accessible · current A table of parameters for the data logging feature. The number of entries is given by the value of pduCount. | |||||||||||||||||||||
| RlogConfigurationEntry | 1.3.6.1.4.1.13742.6.3.2.4.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing data logging parameters for a particular PDU.
| |||||||||||||||||||||
| CdataLogging | 1.3.6.1.4.1.13742.6.3.2.4.1.1 | TruthValue | RW | ||||||||||||||||||
column · TruthValue · read-write · current Defines whether sensor data logging is enabled. | |||||||||||||||||||||
| CmeasurementPeriod | 1.3.6.1.4.1.13742.6.3.2.4.1.2 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Data collection periodicity. This is the periodicity of the data collected by the PDU. This value is fixed at 1 second. | |||||||||||||||||||||
| CmeasurementsPerLogEntry | 1.3.6.1.4.1.13742.6.3.2.4.1.3 | Integer32 (1..600) | RW | ||||||||||||||||||
column · Integer32 (1..600) · read-write · current The number of measurements aggregated into a data log entry. | |||||||||||||||||||||
| ClogSize | 1.3.6.1.4.1.13742.6.3.2.4.1.4 | Integer32 (60..20000) | RW | ||||||||||||||||||
column · Integer32 (60..20000) · read-write · current The capacity (number of entries) of the data log. Note: The value may be reduced due to memory limitations depending on the number of sensors with data logging enabled. | |||||||||||||||||||||
| CdataLoggingEnableForAllSensors | 1.3.6.1.4.1.13742.6.3.2.4.1.5 | TruthValue | RW | ||||||||||||||||||
column · TruthValue · read-write · current Operation to control data logging for all sensors: - when set to true, all *SensorLogAvailable OIDs are set to true - when set to false, all *SensorLogAvailable OIDs are set to false This OID is supposed to be written only. When reading it, it returns the last written value, or false if it was never written since device startup. | |||||||||||||||||||||
| TunitSensorConfigurationTable | 1.3.6.1.4.1.13742.6.3.2.5 | NA | |||||||||||||||||||
table · not-accessible · current A list of unit sensor configuration entries. | |||||||||||||||||||||
| RunitSensorConfigurationEntry | 1.3.6.1.4.1.13742.6.3.2.5.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing unit sensor configuration objects.
| |||||||||||||||||||||
| CsensorType | 1.3.6.1.4.1.13742.6.3.2.5.1.1 | SensorTypeEnumeration | NA | ||||||||||||||||||
column · SensorTypeEnumeration · not-accessible · current The type of sensor. | |||||||||||||||||||||
| CunitSensorLogAvailable | 1.3.6.1.4.1.13742.6.3.2.5.1.4 | TruthValue | RW | ||||||||||||||||||
column · TruthValue · read-write · current Is data logging enabled for this sensor? | |||||||||||||||||||||
| CunitSensorUnits | 1.3.6.1.4.1.13742.6.3.2.5.1.6 | SensorUnitsEnumeration | RO | ||||||||||||||||||
column · SensorUnitsEnumeration · read-only · current The unit in which the sensor reading is reported. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CunitSensorDecimalDigits | 1.3.6.1.4.1.13742.6.3.2.5.1.7 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The number of digits displayed to the right of the decimal point. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CunitSensorAccuracy | 1.3.6.1.4.1.13742.6.3.2.5.1.8 | HundredthsOfAPercentage | RO | deprecated | |||||||||||||||||
column · HundredthsOfAPercentage · read-only · deprecated The accuracy: the maximum relative difference (in percent) between measurement and the actual value. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CunitSensorResolution | 1.3.6.1.4.1.13742.6.3.2.5.1.9 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CunitSensorTolerance | 1.3.6.1.4.1.13742.6.3.2.5.1.10 | Unsigned32 | RO | deprecated | |||||||||||||||||
column · Unsigned32 · read-only · deprecated The tolerance: the maximum difference between measurement and the actual value. The value of this OID variable should be scaled by (unitSensorDecimalDigits + 1). For example, if the value is 50 and unitSensorDecimalDigits is 2, then actual value is 0.05. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CunitSensorMaximum | 1.3.6.1.4.1.13742.6.3.2.5.1.11 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The largest possible reading as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled maximum exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CunitSensorMinimum | 1.3.6.1.4.1.13742.6.3.2.5.1.12 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The smallest possible reading as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CunitSensorHysteresis | 1.3.6.1.4.1.13742.6.3.2.5.1.13 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The hysteresis used when crossing a threshold towards the normal state. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CunitSensorStateChangeDelay | 1.3.6.1.4.1.13742.6.3.2.5.1.14 | Unsigned32 (0..300) | RW | ||||||||||||||||||
column · Unsigned32 (0..300) · read-write · current The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the event is reported. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CunitSensorLowerCriticalThreshold | 1.3.6.1.4.1.13742.6.3.2.5.1.21 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The lower critical threshold as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CunitSensorLowerWarningThreshold | 1.3.6.1.4.1.13742.6.3.2.5.1.22 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The lower warning threshold as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CunitSensorUpperCriticalThreshold | 1.3.6.1.4.1.13742.6.3.2.5.1.23 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The upper critical threshold as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CunitSensorUpperWarningThreshold | 1.3.6.1.4.1.13742.6.3.2.5.1.24 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CunitSensorEnabledThresholds | 1.3.6.1.4.1.13742.6.3.2.5.1.25 | Bits | RW | ||||||||||||||||||
column · Bits · read-write · current A bit string indicating which thresholds are enabled. This parameter does not apply to sensors without numerical reading.
| |||||||||||||||||||||
| CunitSensorSignedMaximum | 1.3.6.1.4.1.13742.6.3.2.5.1.26 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The largest possible reading as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CunitSensorSignedMinimum | 1.3.6.1.4.1.13742.6.3.2.5.1.27 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The smallest possible reading as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. This value determines whether to use the signed or unsigned threshold and value columns: If the minimum is below zero the sensor can have negative readings and the signed columns should be used. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CunitSensorSignedLowerCriticalThreshold | 1.3.6.1.4.1.13742.6.3.2.5.1.28 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current The lower critical threshold as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CunitSensorSignedLowerWarningThreshold | 1.3.6.1.4.1.13742.6.3.2.5.1.29 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current The lower warning threshold as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CunitSensorSignedUpperCriticalThreshold | 1.3.6.1.4.1.13742.6.3.2.5.1.30 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current The upper critical threshold as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CunitSensorSignedUpperWarningThreshold | 1.3.6.1.4.1.13742.6.3.2.5.1.31 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current The upper warning threshold as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| TactiveDNSServerTable | 1.3.6.1.4.1.13742.6.3.2.6 | NA | |||||||||||||||||||
table · not-accessible · current A list of active DNS server entries. The number of rows in the table is given by the value of activeDNSServerCount in unitConfigurationTable. | |||||||||||||||||||||
| RactiveDNSServerEntry | 1.3.6.1.4.1.13742.6.3.2.6.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing an active DNS server for a particular PDU.
| |||||||||||||||||||||
| CactiveDNSServerIndex | 1.3.6.1.4.1.13742.6.3.2.6.1.2 | Integer32 (1..16) | NA | ||||||||||||||||||
column · Integer32 (1..16) · not-accessible · current A unique value for a DNS server. Its value ranges between 1 and activeDNSServerCount. | |||||||||||||||||||||
| CactiveDNSServerAddressType | 1.3.6.1.4.1.13742.6.3.2.6.1.3 | InetAddressType | RO | ||||||||||||||||||
column · InetAddressType · read-only · current Represents the type of the corresponding instance of activeDNSServerAddress object. | |||||||||||||||||||||
| CactiveDNSServerAddress | 1.3.6.1.4.1.13742.6.3.2.6.1.4 | InetAddress | RO | ||||||||||||||||||
column · InetAddress · read-only · current The address of the DNS server. | |||||||||||||||||||||
| CactiveDNSServerAddressSource | 1.3.6.1.4.1.13742.6.3.2.6.1.5 | AddressSourceEnumeration | RO | deprecated | |||||||||||||||||
column · AddressSourceEnumeration · read-only · deprecated How was the address obtained: static, DHCP, DHCPv6? No longer used, always set to static. | |||||||||||||||||||||
| TactiveNTPServerTable | 1.3.6.1.4.1.13742.6.3.2.7 | NA | |||||||||||||||||||
table · not-accessible · current A list of active NTP server entries. The number of rows in the table is given by the value of activeNTPServerCount in unitConfigurationTable. | |||||||||||||||||||||
| RactiveNTPServerEntry | 1.3.6.1.4.1.13742.6.3.2.7.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing an active NTP server for a particular PDU.
| |||||||||||||||||||||
| CactiveNTPServerIndex | 1.3.6.1.4.1.13742.6.3.2.7.1.2 | Integer32 (1..16) | NA | ||||||||||||||||||
column · Integer32 (1..16) · not-accessible · current A unique value for an NTP server. Its value ranges between 1 and activeNTPServerCount. | |||||||||||||||||||||
| CactiveNTPServerAddressType | 1.3.6.1.4.1.13742.6.3.2.7.1.3 | InetAddressType | RO | ||||||||||||||||||
column · InetAddressType · read-only · current Represents the type of the corresponding instance of activeNTPServerAddress object, e.g. IPv4, IPv6, DNS Name | |||||||||||||||||||||
| CactiveNTPServerAddress | 1.3.6.1.4.1.13742.6.3.2.7.1.4 | InetAddress | RO | ||||||||||||||||||
column · InetAddress · read-only · current The address of the NTP server. | |||||||||||||||||||||
| CactiveNTPServerAddressSource | 1.3.6.1.4.1.13742.6.3.2.7.1.5 | AddressSourceEnumeration | RO | deprecated | |||||||||||||||||
column · AddressSourceEnumeration · read-only · deprecated How was the address obtained: static, DHCP, DHCPv6? No longer used, always set to static. | |||||||||||||||||||||
| Ninlets | 1.3.6.1.4.1.13742.6.3.3 | ||||||||||||||||||||
| TinletConfigurationTable | 1.3.6.1.4.1.13742.6.3.3.3 | NA | |||||||||||||||||||
table · not-accessible · current A list of inlet configuration entries. The number of entries is given by the value of inletCount for the PDU. | |||||||||||||||||||||
| RinletConfigurationEntry | 1.3.6.1.4.1.13742.6.3.3.3.1 | NA | |||||||||||||||||||
| CinletId | 1.3.6.1.4.1.13742.6.3.3.3.1.1 | Integer32 (1..256) | NA | ||||||||||||||||||
column · Integer32 (1..256) · not-accessible · current A unique value for each inlet. Its value ranges between 1 and the value of inletCount. | |||||||||||||||||||||
| CinletLabel | 1.3.6.1.4.1.13742.6.3.3.3.1.2 | DisplayString | RO | I1 | |||||||||||||||||
column · DisplayString · read-only · current The label on the PDU identifying the inlet. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletName | 1.3.6.1.4.1.13742.6.3.3.3.1.3 | DisplayString | RW | | |||||||||||||||||
column · DisplayString · read-write · current The user-defined name. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletPlug | 1.3.6.1.4.1.13742.6.3.3.3.1.4 | PlugTypeEnumeration | RO | deprecated | 10 | ||||||||||||||||
column · PlugTypeEnumeration · read-only · deprecated The type of plug/receptacle wired to the inlet. Note: PlugTypeEnumeration is no longer updated, unlisted plugs will be reported as plugOTHER. Use inletPlugDescriptor to reliably determine the plug type. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletPoleCount | 1.3.6.1.4.1.13742.6.3.3.3.1.5 | Integer32 (2..5) | RO | 2 | |||||||||||||||||
column · Integer32 (2..5) · read-only · current The number of poles.
PDU:
2 for 1-phase circuits
3 for 3-phase delta-wired models
4 for 3-phase wye-wired models, pole 4 is neutral
Power Meter:
2 to 5 depending on the power meter type:
Pole 1 is Phase A
Pole 2 is Phase B
Pole 3 is Phase C
Pole 4 is Neutral
Pole 5 is EarthExample values from LibreNMS test devices
| |||||||||||||||||||||
| CinletRatedVoltage | 1.3.6.1.4.1.13742.6.3.3.3.1.6 | DisplayString | RO | 200-240V | |||||||||||||||||
column · DisplayString · read-only · current The inlet voltage rating. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletRatedCurrent | 1.3.6.1.4.1.13742.6.3.3.3.1.7 | DisplayString | RO | 32A | |||||||||||||||||
column · DisplayString · read-only · current The inlet current rating. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletRatedFrequency | 1.3.6.1.4.1.13742.6.3.3.3.1.8 | DisplayString | RO | deprecated | | ||||||||||||||||
column · DisplayString · read-only · deprecated The inlet frequency rating. Deprecated: use pduRatedFrequency for unit nameplate information. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletRatedVA | 1.3.6.1.4.1.13742.6.3.3.3.1.9 | DisplayString | RO | deprecated | | ||||||||||||||||
column · DisplayString · read-only · deprecated The inlet VA (VoltAmps) rating. Deprecated: use pduRatedVA for unit nameplate information. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletDeviceCapabilities | 1.3.6.1.4.1.13742.6.3.3.3.1.10 | Bits | RO | 9F 00 02 00 00 00 00 00 00 00 0 3 4 5 6 7 22 | |||||||||||||||||
column · Bits · read-only · current A bit string indicating which inlet sensors are available.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletPoleCapabilities | 1.3.6.1.4.1.13742.6.3.3.3.1.11 | Bits | RO | 00 00 00 00 00 00 00 00 00 00 | |||||||||||||||||
column · Bits · read-only · current A bit string indicating which inlet pole sensors are available.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletPlugDescriptor | 1.3.6.1.4.1.13742.6.3.3.3.1.12 | DisplayString | RO | IEC 60309 2P+E 6h 32A | |||||||||||||||||
column · DisplayString · read-only · current The inlet plug type as a string. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletEnableState | 1.3.6.1.4.1.13742.6.3.3.3.1.13 | TruthValue | RW | 1 | |||||||||||||||||
column · TruthValue · read-write · current Enable/disable PDU operation for this inlet. When PDU operation is disabled the sensors for this inlet and all children will no longer be updated, and outlet switching is no longer allowed. This is only meaningful for multi-inlet units if one inlet is temporarily expected to be powered down. Disabling the inlet of a single-inlet unit is forbidden and any attempt to do so will result in an error. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletRCMResidualOperatingCurrent | 1.3.6.1.4.1.13742.6.3.3.3.1.14 | Unsigned32 | RW | obsolete | |||||||||||||||||
column · Unsigned32 · read-write · obsolete **NOTE:This object is obsolete. Its functionality was implemented by existing RCM sensor thresholds. The Residual Operating Current (Threshold) for the RCM State sensor. For inlets without an RCM, any attempt to access this OID will return NoSuchInstance error. The value of this OID is in milliamps. | |||||||||||||||||||||
| CinletIsDC | 1.3.6.1.4.1.13742.6.3.3.3.1.15 | TruthValue | RO | 2 | |||||||||||||||||
column · TruthValue · read-only · current Inlet current type: true for DC, false for AC Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletLinePairCount | 1.3.6.1.4.1.13742.6.3.3.3.1.16 | Integer32 (0..3) | RO | 0 | |||||||||||||||||
column · Integer32 (0..3) · read-only · current The number of inlet line pairs. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletLinePairCapabilities | 1.3.6.1.4.1.13742.6.3.3.3.1.17 | Bits | RO | 00 00 00 00 00 00 00 00 00 00 | |||||||||||||||||
column · Bits · read-only · current A bit string indicating which inlet line pair sensors are available.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| TinletSensorConfigurationTable | 1.3.6.1.4.1.13742.6.3.3.4 | NA | |||||||||||||||||||
table · not-accessible · current A list of inlet sensor configuration entries. | |||||||||||||||||||||
| RinletSensorConfigurationEntry | 1.3.6.1.4.1.13742.6.3.3.4.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing inlet sensor configuration objects.
| |||||||||||||||||||||
| CinletSensorLogAvailable | 1.3.6.1.4.1.13742.6.3.3.4.1.4 | TruthValue | RW | 1 | |||||||||||||||||
column · TruthValue · read-write · current Is data logging enabled for this sensor? Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletSensorUnits | 1.3.6.1.4.1.13742.6.3.3.4.1.6 | SensorUnitsEnumeration | RO | 2 | |||||||||||||||||
column · SensorUnitsEnumeration · read-only · current The unit in which the sensor reading is reported. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletSensorDecimalDigits | 1.3.6.1.4.1.13742.6.3.3.4.1.7 | Unsigned32 | RO | 3 | |||||||||||||||||
column · Unsigned32 · read-only · current The number of digits displayed to the right of the decimal point. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletSensorAccuracy | 1.3.6.1.4.1.13742.6.3.3.4.1.8 | HundredthsOfAPercentage | RO | deprecated | 0 | ||||||||||||||||
column · HundredthsOfAPercentage · read-only · deprecated The accuracy: the maximum relative difference (in percent) between measurement and the actual value. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletSensorResolution | 1.3.6.1.4.1.13742.6.3.3.4.1.9 | Unsigned32 | RO | 1 | |||||||||||||||||
column · Unsigned32 · read-only · current The resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletSensorTolerance | 1.3.6.1.4.1.13742.6.3.3.4.1.10 | Unsigned32 | RO | deprecated | 0 | ||||||||||||||||
column · Unsigned32 · read-only · deprecated The tolerance: the maximum difference between measurement and the actual value. The value of this OID variable should be scaled by (inletSensorDecimalDigits + 1). For example, if the value is 50 and inletSensorDecimalDigits is 2, then actual value is 0.05. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletSensorMaximum | 1.3.6.1.4.1.13742.6.3.3.4.1.11 | Unsigned32 | RO | 3600000 | |||||||||||||||||
column · Unsigned32 · read-only · current The largest possible reading as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled maximum exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletSensorMinimum | 1.3.6.1.4.1.13742.6.3.3.4.1.12 | Unsigned32 | RO | 0 | |||||||||||||||||
column · Unsigned32 · read-only · current The smallest possible reading as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletSensorHysteresis | 1.3.6.1.4.1.13742.6.3.3.4.1.13 | Unsigned32 | RW | 1000 | |||||||||||||||||
column · Unsigned32 · read-write · current The hysteresis used when crossing a threshold towards the normal state. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletSensorStateChangeDelay | 1.3.6.1.4.1.13742.6.3.3.4.1.14 | Unsigned32 (0..300) | RW | 0 | |||||||||||||||||
column · Unsigned32 (0..300) · read-write · current The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the event is reported. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletSensorLowerCriticalThreshold | 1.3.6.1.4.1.13742.6.3.3.4.1.21 | Unsigned32 | RW | 0 | |||||||||||||||||
column · Unsigned32 · read-write · current The lower critical threshold as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletSensorLowerWarningThreshold | 1.3.6.1.4.1.13742.6.3.3.4.1.22 | Unsigned32 | RW | 0 | |||||||||||||||||
column · Unsigned32 · read-write · current The lower warning threshold as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletSensorUpperCriticalThreshold | 1.3.6.1.4.1.13742.6.3.3.4.1.23 | Unsigned32 | RW | 25600 | |||||||||||||||||
column · Unsigned32 · read-write · current The upper critical threshold as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletSensorUpperWarningThreshold | 1.3.6.1.4.1.13742.6.3.3.4.1.24 | Unsigned32 | RW | 20800 | |||||||||||||||||
column · Unsigned32 · read-write · current The upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletSensorEnabledThresholds | 1.3.6.1.4.1.13742.6.3.3.4.1.25 | Bits | RW | 30 2 3 | |||||||||||||||||
column · Bits · read-write · current A bit string indicating which thresholds are enabled. This parameter does not apply to sensors without numerical reading.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletSensorSignedMaximum | 1.3.6.1.4.1.13742.6.3.3.4.1.26 | Integer32 | RO | 3600000 | |||||||||||||||||
column · Integer32 · read-only · current The largest possible reading as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletSensorSignedMinimum | 1.3.6.1.4.1.13742.6.3.3.4.1.27 | Integer32 | RO | 0 | |||||||||||||||||
column · Integer32 · read-only · current The smallest possible reading as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value determines whether to use the signed or unsigned threshold and value columns: If the minimum is below zero the sensor can have negative readings and the signed columns should be used. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletSensorSignedLowerCriticalThreshold | 1.3.6.1.4.1.13742.6.3.3.4.1.28 | Integer32 | RW | 0 | |||||||||||||||||
column · Integer32 · read-write · current The lower critical threshold as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletSensorSignedLowerWarningThreshold | 1.3.6.1.4.1.13742.6.3.3.4.1.29 | Integer32 | RW | 0 | |||||||||||||||||
column · Integer32 · read-write · current The lower warning threshold as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletSensorSignedUpperCriticalThreshold | 1.3.6.1.4.1.13742.6.3.3.4.1.30 | Integer32 | RW | 25600 | |||||||||||||||||
column · Integer32 · read-write · current The upper critical threshold as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletSensorSignedUpperWarningThreshold | 1.3.6.1.4.1.13742.6.3.3.4.1.31 | Integer32 | RW | 20800 | |||||||||||||||||
column · Integer32 · read-write · current The upper warning threshold as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| TinletPoleConfigurationTable | 1.3.6.1.4.1.13742.6.3.3.5 | NA | |||||||||||||||||||
table · not-accessible · current A list of inlet pole configuration entries. The number of entries is given by the value of inletPoleCount for the inlet. | |||||||||||||||||||||
| RinletPoleConfigurationEntry | 1.3.6.1.4.1.13742.6.3.3.5.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing parameters for a particular inlet pole.
| |||||||||||||||||||||
| CinletPoleLine | 1.3.6.1.4.1.13742.6.3.3.5.1.1 | LineEnumeration | RO | ||||||||||||||||||
column · LineEnumeration · read-only · current The phase for this inlet pole. | |||||||||||||||||||||
| CinletPoleNode | 1.3.6.1.4.1.13742.6.3.3.5.1.2 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The node to which this inlet pole is connected | |||||||||||||||||||||
| TinletPoleSensorConfigurationTable | 1.3.6.1.4.1.13742.6.3.3.6 | NA | |||||||||||||||||||
table · not-accessible · current A list of inlet pole sensor configuration entries. | |||||||||||||||||||||
| RinletPoleSensorConfigurationEntry | 1.3.6.1.4.1.13742.6.3.3.6.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing inlet pole sensor configuration objects.
| |||||||||||||||||||||
| CinletPoleIndex | 1.3.6.1.4.1.13742.6.3.3.6.1.1 | Integer32 (1..256) | NA | ||||||||||||||||||
column · Integer32 (1..256) · not-accessible · current A unique value for each inlet pole. Its value ranges between 1 and the value of inletPoleCount. | |||||||||||||||||||||
| CinletPoleSensorLogAvailable | 1.3.6.1.4.1.13742.6.3.3.6.1.4 | TruthValue | RW | ||||||||||||||||||
column · TruthValue · read-write · current Is data logging enabled for this sensor? | |||||||||||||||||||||
| CinletPoleSensorUnits | 1.3.6.1.4.1.13742.6.3.3.6.1.6 | SensorUnitsEnumeration | RO | ||||||||||||||||||
column · SensorUnitsEnumeration · read-only · current The unit in which the sensor reading is reported. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CinletPoleSensorDecimalDigits | 1.3.6.1.4.1.13742.6.3.3.6.1.7 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The number of digits displayed to the right of the decimal point. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CinletPoleSensorAccuracy | 1.3.6.1.4.1.13742.6.3.3.6.1.8 | HundredthsOfAPercentage | RO | deprecated | |||||||||||||||||
column · HundredthsOfAPercentage · read-only · deprecated The accuracy: the maximum relative difference (in percent) between measurement and the actual value. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CinletPoleSensorResolution | 1.3.6.1.4.1.13742.6.3.3.6.1.9 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CinletPoleSensorTolerance | 1.3.6.1.4.1.13742.6.3.3.6.1.10 | Unsigned32 | RO | deprecated | |||||||||||||||||
column · Unsigned32 · read-only · deprecated The tolerance: the maximum difference between measurement and the actual value. The value of this OID variable should be scaled by (inletPoleSensorDecimalDigits + 1). For example, if the value is 50 and inletPoleSensorDecimalDigits is 2, then actual value is 0.05. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CinletPoleSensorMaximum | 1.3.6.1.4.1.13742.6.3.3.6.1.11 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The largest possible reading as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled maximum exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CinletPoleSensorMinimum | 1.3.6.1.4.1.13742.6.3.3.6.1.12 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The smallest possible reading as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CinletPoleSensorHysteresis | 1.3.6.1.4.1.13742.6.3.3.6.1.13 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The hysteresis used when crossing a threshold towards the normal state. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CinletPoleSensorStateChangeDelay | 1.3.6.1.4.1.13742.6.3.3.6.1.14 | Unsigned32 (0..300) | RW | ||||||||||||||||||
column · Unsigned32 (0..300) · read-write · current The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the event is reported. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CinletPoleSensorLowerCriticalThreshold | 1.3.6.1.4.1.13742.6.3.3.6.1.21 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The lower critical threshold as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CinletPoleSensorLowerWarningThreshold | 1.3.6.1.4.1.13742.6.3.3.6.1.22 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The lower warning threshold as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CinletPoleSensorUpperCriticalThreshold | 1.3.6.1.4.1.13742.6.3.3.6.1.23 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The upper critical threshold as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CinletPoleSensorUpperWarningThreshold | 1.3.6.1.4.1.13742.6.3.3.6.1.24 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CinletPoleSensorEnabledThresholds | 1.3.6.1.4.1.13742.6.3.3.6.1.25 | Bits | RW | ||||||||||||||||||
column · Bits · read-write · current A bit string indicating which thresholds are enabled. This parameter does not apply to sensors without numerical reading.
| |||||||||||||||||||||
| CinletPoleSensorSignedMaximum | 1.3.6.1.4.1.13742.6.3.3.6.1.26 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The largest possible reading as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CinletPoleSensorSignedMinimum | 1.3.6.1.4.1.13742.6.3.3.6.1.27 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The smallest possible reading as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value determines whether to use the signed or unsigned threshold and value columns: If the minimum is below zero the sensor can have negative readings and the signed columns should be used. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CinletPoleSensorSignedLowerCriticalThreshold | 1.3.6.1.4.1.13742.6.3.3.6.1.28 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current The lower critical threshold as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CinletPoleSensorSignedLowerWarningThreshold | 1.3.6.1.4.1.13742.6.3.3.6.1.29 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current The lower warning threshold as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CinletPoleSensorSignedUpperCriticalThreshold | 1.3.6.1.4.1.13742.6.3.3.6.1.30 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current The upper critical threshold as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CinletPoleSensorSignedUpperWarningThreshold | 1.3.6.1.4.1.13742.6.3.3.6.1.31 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current The upper warning threshold as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| TinletLinePairConfigurationTable | 1.3.6.1.4.1.13742.6.3.3.7 | NA | |||||||||||||||||||
table · not-accessible · current A list of inlet line pair configuration entries. The number of entries is given by the value of inletLinePairCount for the inlet. | |||||||||||||||||||||
| RinletLinePairConfigurationEntry | 1.3.6.1.4.1.13742.6.3.3.7.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing parameters for a particular inlet line pair.
| |||||||||||||||||||||
| CinletLinePairIndex | 1.3.6.1.4.1.13742.6.3.3.7.1.1 | Integer32 (1..256) | NA | ||||||||||||||||||
column · Integer32 (1..256) · not-accessible · current A unique value for each inlet line pair. Its value ranges between 1 and the value of inletLinePairCount. | |||||||||||||||||||||
| CinletLinePairLeftLine | 1.3.6.1.4.1.13742.6.3.3.7.1.2 | LineEnumeration | RO | ||||||||||||||||||
column · LineEnumeration · read-only · current The phase for the line pair's left power line. | |||||||||||||||||||||
| CinletLinePairRightLine | 1.3.6.1.4.1.13742.6.3.3.7.1.3 | LineEnumeration | RO | ||||||||||||||||||
column · LineEnumeration · read-only · current The phase for the line pair's right power line. | |||||||||||||||||||||
| CinletLinePairLeftNode | 1.3.6.1.4.1.13742.6.3.3.7.1.4 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The node number of the line pair's left power line | |||||||||||||||||||||
| CinletLinePairRightNode | 1.3.6.1.4.1.13742.6.3.3.7.1.5 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The node number of the line pair's right power line | |||||||||||||||||||||
| TinletLinePairSensorConfigurationTable | 1.3.6.1.4.1.13742.6.3.3.8 | NA | |||||||||||||||||||
table · not-accessible · current A list of inlet line pair sensor configuration entries. | |||||||||||||||||||||
| RinletLinePairSensorConfigurationEntry | 1.3.6.1.4.1.13742.6.3.3.8.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing inlet line pair sensor configuration objects.
| |||||||||||||||||||||
| CinletLinePairSensorLogAvailable | 1.3.6.1.4.1.13742.6.3.3.8.1.4 | TruthValue | RW | ||||||||||||||||||
column · TruthValue · read-write · current Is data logging enabled for this sensor? | |||||||||||||||||||||
| CinletLinePairSensorUnits | 1.3.6.1.4.1.13742.6.3.3.8.1.6 | SensorUnitsEnumeration | RO | ||||||||||||||||||
column · SensorUnitsEnumeration · read-only · current The unit in which the sensor reading is reported. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CinletLinePairSensorDecimalDigits | 1.3.6.1.4.1.13742.6.3.3.8.1.7 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The number of digits displayed to the right of the decimal point. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CinletLinePairSensorResolution | 1.3.6.1.4.1.13742.6.3.3.8.1.9 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CinletLinePairSensorMaximum | 1.3.6.1.4.1.13742.6.3.3.8.1.11 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The largest possible reading as an unsigned integer. The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled maximum exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CinletLinePairSensorMinimum | 1.3.6.1.4.1.13742.6.3.3.8.1.12 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The smallest possible reading as an unsigned integer. The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CinletLinePairSensorHysteresis | 1.3.6.1.4.1.13742.6.3.3.8.1.13 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The hysteresis used when crossing a threshold towards the normal state. The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CinletLinePairSensorStateChangeDelay | 1.3.6.1.4.1.13742.6.3.3.8.1.14 | Unsigned32 (0..300) | RW | ||||||||||||||||||
column · Unsigned32 (0..300) · read-write · current The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the event is reported. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CinletLinePairSensorLowerCriticalThreshold | 1.3.6.1.4.1.13742.6.3.3.8.1.21 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The lower critical threshold as an unsigned integer. The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CinletLinePairSensorLowerWarningThreshold | 1.3.6.1.4.1.13742.6.3.3.8.1.22 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The lower warning threshold as an unsigned integer. The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CinletLinePairSensorUpperCriticalThreshold | 1.3.6.1.4.1.13742.6.3.3.8.1.23 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The upper critical threshold as an unsigned integer. The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CinletLinePairSensorUpperWarningThreshold | 1.3.6.1.4.1.13742.6.3.3.8.1.24 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CinletLinePairSensorEnabledThresholds | 1.3.6.1.4.1.13742.6.3.3.8.1.25 | Bits | RW | ||||||||||||||||||
column · Bits · read-write · current A bit string indicating which thresholds are enabled. This parameter does not apply to sensors without numerical reading.
| |||||||||||||||||||||
| CinletLinePairSensorSignedMaximum | 1.3.6.1.4.1.13742.6.3.3.8.1.26 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The largest possible reading as a signed integer. The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CinletLinePairSensorSignedMinimum | 1.3.6.1.4.1.13742.6.3.3.8.1.27 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The smallest possible reading as a signed integer. The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalDigits is 2, then actual value is 0.01. This value determines whether to use the signed or unsigned threshold and value columns: If the minimum is below zero the sensor can have negative readings and the signed columns should be used. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CinletLinePairSensorSignedLowerCriticalThreshold | 1.3.6.1.4.1.13742.6.3.3.8.1.28 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current The lower critical threshold as a signed integer. The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CinletLinePairSensorSignedLowerWarningThreshold | 1.3.6.1.4.1.13742.6.3.3.8.1.29 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current The lower warning threshold as a signed integer. The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CinletLinePairSensorSignedUpperCriticalThreshold | 1.3.6.1.4.1.13742.6.3.3.8.1.30 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current The upper critical threshold as a signed integer. The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CinletLinePairSensorSignedUpperWarningThreshold | 1.3.6.1.4.1.13742.6.3.3.8.1.31 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current The upper warning threshold as a signed integer. The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| NoverCurrentProtector | 1.3.6.1.4.1.13742.6.3.4 | ||||||||||||||||||||
| ToverCurrentProtectorConfigurationTable | 1.3.6.1.4.1.13742.6.3.4.3 | NA | |||||||||||||||||||
table · not-accessible · current A list of overcurrent protector configuration entries. The number of entries is given by the value of overCurrentProtectorCount for the PDU. | |||||||||||||||||||||
| RoverCurrentProtectorConfigurationEntry | 1.3.6.1.4.1.13742.6.3.4.3.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing objects for a particular overcurrent protector. | |||||||||||||||||||||
| CoverCurrentProtectorIndex | 1.3.6.1.4.1.13742.6.3.4.3.1.1 | Integer32 (1..256) | NA | ||||||||||||||||||
column · Integer32 (1..256) · not-accessible · current A unique value for each overcurrent protector. Its value ranges between 1 and the value of overCurrentProtectorCount. | |||||||||||||||||||||
| CoverCurrentProtectorLabel | 1.3.6.1.4.1.13742.6.3.4.3.1.2 | DisplayString | RO | C1 | |||||||||||||||||
column · DisplayString · read-only · current The label on the PDU identifying the overcurrent protector. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoverCurrentProtectorName | 1.3.6.1.4.1.13742.6.3.4.3.1.3 | DisplayString | RW | | |||||||||||||||||
column · DisplayString · read-write · current The user-defined name. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoverCurrentProtectorType | 1.3.6.1.4.1.13742.6.3.4.3.1.4 | OverCurrentProtectorTypeEnumeration | RO | 1 | |||||||||||||||||
column · OverCurrentProtectorTypeEnumeration · read-only · current The type of overcurrent protector. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoverCurrentProtectorRatedCurrent | 1.3.6.1.4.1.13742.6.3.4.3.1.5 | DisplayString | RO | 16A | |||||||||||||||||
column · DisplayString · read-only · current The current rating. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoverCurrentProtectorPoleCount | 1.3.6.1.4.1.13742.6.3.4.3.1.6 | Integer32 (1..3) | RO | 1 | |||||||||||||||||
column · Integer32 (1..3) · read-only · current The number of overcurrent protector poles. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoverCurrentProtectorCapabilities | 1.3.6.1.4.1.13742.6.3.4.3.1.9 | Bits | RO | 80 02 00 00 00 00 00 00 00 00 00 0 14 | |||||||||||||||||
column · Bits · read-only · current A bit string indicating which overcurrent protector sensors are available.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoverCurrentProtectorPowerSource | 1.3.6.1.4.1.13742.6.3.4.3.1.10 | RowPointer | RO | 1.3.6.1.4.1.13742.6.3.3.3.1.2.1.1 | |||||||||||||||||
column · RowPointer · read-only · current This object allows discovery of how the PDU is wired. It indicates the overcurrent protector's power source which can be one of the following: - an inlet - another overcurrent protector - a transfer switch If the power source is an inlet, it contains the OID of an inletLabel in the inletConfigurationTable. The indices of the OID can then be used to reference other objects in the inlet tables. If the power source is an overcurrent protector, it contains the OID of an overCurrentProtectorLabel in the overCurrentProtectorConfigurationTable. The indices of the OID can then be used to reference other objects in the overcurrent protector tables. If the power source is a transfer switch, it contains the OID of a transferSwitchLabel in the transferSwitchConfigurationTable. The indices of the OID can then be used to reference other objects in the transfer switch tables. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ToverCurrentProtectorSensorConfigurationTable | 1.3.6.1.4.1.13742.6.3.4.4 | NA | |||||||||||||||||||
table · not-accessible · current A list of over current protector sensor configuration entries. | |||||||||||||||||||||
| RoverCurrentProtectorSensorConfigurationEntry | 1.3.6.1.4.1.13742.6.3.4.4.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing over current protector sensor configuration objects. | |||||||||||||||||||||
| CoverCurrentProtectorSensorLogAvailable | 1.3.6.1.4.1.13742.6.3.4.4.1.4 | TruthValue | RW | 1 | |||||||||||||||||
column · TruthValue · read-write · current Is data logging enabled for this sensor? Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoverCurrentProtectorSensorUnits | 1.3.6.1.4.1.13742.6.3.4.4.1.6 | SensorUnitsEnumeration | RO | 2 | |||||||||||||||||
column · SensorUnitsEnumeration · read-only · current The unit in which the sensor reading is reported. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoverCurrentProtectorSensorDecimalDigits | 1.3.6.1.4.1.13742.6.3.4.4.1.7 | Unsigned32 | RO | 3 | |||||||||||||||||
column · Unsigned32 · read-only · current The number of digits displayed to the right of the decimal point. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoverCurrentProtectorSensorAccuracy | 1.3.6.1.4.1.13742.6.3.4.4.1.8 | HundredthsOfAPercentage | RO | deprecated | 0 | ||||||||||||||||
column · HundredthsOfAPercentage · read-only · deprecated The accuracy: the maximum relative difference (in percent) between measurement and the actual value. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoverCurrentProtectorSensorResolution | 1.3.6.1.4.1.13742.6.3.4.4.1.9 | Unsigned32 | RO | 1 | |||||||||||||||||
column · Unsigned32 · read-only · current The resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoverCurrentProtectorSensorTolerance | 1.3.6.1.4.1.13742.6.3.4.4.1.10 | Unsigned32 | RO | deprecated | 0 | ||||||||||||||||
column · Unsigned32 · read-only · deprecated The tolerance: the maximum difference between measurement and the actual value. The value of this OID variable should be scaled by (overCurrentProtectorSensorDecimalDigits + 1). For example, if the value is 50 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.05. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoverCurrentProtectorSensorMaximum | 1.3.6.1.4.1.13742.6.3.4.4.1.11 | Unsigned32 | RO | 1800000 | |||||||||||||||||
column · Unsigned32 · read-only · current The largest possible reading as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled maximum exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoverCurrentProtectorSensorMinimum | 1.3.6.1.4.1.13742.6.3.4.4.1.12 | Unsigned32 | RO | 0 | |||||||||||||||||
column · Unsigned32 · read-only · current The smallest possible reading as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoverCurrentProtectorSensorHysteresis | 1.3.6.1.4.1.13742.6.3.4.4.1.13 | Unsigned32 | RW | 1000 | |||||||||||||||||
column · Unsigned32 · read-write · current The hysteresis used when crossing a threshold towards the normal state. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoverCurrentProtectorSensorStateChangeDelay | 1.3.6.1.4.1.13742.6.3.4.4.1.14 | Unsigned32 (0..300) | RW | 0 | |||||||||||||||||
column · Unsigned32 (0..300) · read-write · current The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the event is reported. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoverCurrentProtectorSensorLowerCriticalThreshold | 1.3.6.1.4.1.13742.6.3.4.4.1.21 | Unsigned32 | RW | 0 | |||||||||||||||||
column · Unsigned32 · read-write · current The lower critical threshold as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoverCurrentProtectorSensorLowerWarningThreshold | 1.3.6.1.4.1.13742.6.3.4.4.1.22 | Unsigned32 | RW | 0 | |||||||||||||||||
column · Unsigned32 · read-write · current The lower warning threshold as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoverCurrentProtectorSensorUpperCriticalThreshold | 1.3.6.1.4.1.13742.6.3.4.4.1.23 | Unsigned32 | RW | 12800 | |||||||||||||||||
column · Unsigned32 · read-write · current The upper critical threshold as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoverCurrentProtectorSensorUpperWarningThreshold | 1.3.6.1.4.1.13742.6.3.4.4.1.24 | Unsigned32 | RW | 10400 | |||||||||||||||||
column · Unsigned32 · read-write · current The upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoverCurrentProtectorSensorEnabledThresholds | 1.3.6.1.4.1.13742.6.3.4.4.1.25 | Bits | RW | 30 2 3 | |||||||||||||||||
column · Bits · read-write · current A bit string indicating which thresholds are enabled. This parameter does not apply to sensors without numerical reading.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoverCurrentProtectorSensorSignedMaximum | 1.3.6.1.4.1.13742.6.3.4.4.1.26 | Integer32 | RO | 1800000 | |||||||||||||||||
column · Integer32 · read-only · current The largest possible reading as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoverCurrentProtectorSensorSignedMinimum | 1.3.6.1.4.1.13742.6.3.4.4.1.27 | Integer32 | RO | 0 | |||||||||||||||||
column · Integer32 · read-only · current The smallest possible reading as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. This value determines whether to use the signed or unsigned threshold and value columns: If the minimum is below zero the sensor can have negative readings and the signed columns should be used. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoverCurrentProtectorSensorSignedLowerCriticalThreshold | 1.3.6.1.4.1.13742.6.3.4.4.1.28 | Integer32 | RW | 0 | |||||||||||||||||
column · Integer32 · read-write · current The lower critical threshold as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoverCurrentProtectorSensorSignedLowerWarningThreshold | 1.3.6.1.4.1.13742.6.3.4.4.1.29 | Integer32 | RW | 0 | |||||||||||||||||
column · Integer32 · read-write · current The lower warning threshold as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoverCurrentProtectorSensorSignedUpperCriticalThreshold | 1.3.6.1.4.1.13742.6.3.4.4.1.30 | Integer32 | RW | 12800 | |||||||||||||||||
column · Integer32 · read-write · current The upper critical threshold as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoverCurrentProtectorSensorSignedUpperWarningThreshold | 1.3.6.1.4.1.13742.6.3.4.4.1.31 | Integer32 | RW | 10400 | |||||||||||||||||
column · Integer32 · read-write · current The upper warning threshold as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ToverCurrentProtectorPoleConfigurationTable | 1.3.6.1.4.1.13742.6.3.4.5 | NA | |||||||||||||||||||
table · not-accessible · current A list of overcurrent protector pole configuration entries. The number of entries is given by the value of overCurrentProtectorPoleCount. | |||||||||||||||||||||
| RoverCurrentProtectorPoleConfigurationEntry | 1.3.6.1.4.1.13742.6.3.4.5.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing parameters for a particular overcurrent protector pole. | |||||||||||||||||||||
| CoverCurrentProtectorPoleIndex | 1.3.6.1.4.1.13742.6.3.4.5.1.1 | Integer32 (1..256) | NA | ||||||||||||||||||
column · Integer32 (1..256) · not-accessible · current A unique value for each overcurrent protector pole. Its value ranges between 1 and the value of overCurrentProtectorPoleCount. | |||||||||||||||||||||
| CoverCurrentProtectorPoleLine | 1.3.6.1.4.1.13742.6.3.4.5.1.2 | LineEnumeration | RO | ||||||||||||||||||
column · LineEnumeration · read-only · current The phase for this overcurrent protector pole. | |||||||||||||||||||||
| CoverCurrentProtectorPoleInNode | 1.3.6.1.4.1.13742.6.3.4.5.1.3 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The node to which this overcurrent protector pole input is connected | |||||||||||||||||||||
| CoverCurrentProtectorPoleOutNode | 1.3.6.1.4.1.13742.6.3.4.5.1.4 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The node to which this overcurrent protector pole output is connected | |||||||||||||||||||||
| Noutlets | 1.3.6.1.4.1.13742.6.3.5 | ||||||||||||||||||||
| ToutletConfigurationTable | 1.3.6.1.4.1.13742.6.3.5.3 | NA | |||||||||||||||||||
table · not-accessible · current A list of outlet configuration entries. The number of entries is given by the value of outletCount for the PDU. | |||||||||||||||||||||
| RoutletConfigurationEntry | 1.3.6.1.4.1.13742.6.3.5.3.1 | NA | |||||||||||||||||||
| CoutletId | 1.3.6.1.4.1.13742.6.3.5.3.1.1 | Integer32 (1..256) | NA | ||||||||||||||||||
column · Integer32 (1..256) · not-accessible · current A unique value for each outlet. Its value ranges between 1 and the value of outletCount. | |||||||||||||||||||||
| CoutletLabel | 1.3.6.1.4.1.13742.6.3.5.3.1.2 | DisplayString | RO | 1 | |||||||||||||||||
column · DisplayString · read-only · current The label on the PDU identifying the outlet. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletName | 1.3.6.1.4.1.13742.6.3.5.3.1.3 | DisplayString | RW | | |||||||||||||||||
column · DisplayString · read-write · current The user-defined name. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletReceptacle | 1.3.6.1.4.1.13742.6.3.5.3.1.4 | ReceptacleTypeEnumeration | RO | deprecated | 5 | ||||||||||||||||
column · ReceptacleTypeEnumeration · read-only · deprecated The receptacle type. Note: ReceptacleTypeEnumeration is no longer updated, unlisted receptacles will be listed as receptacleOTHER. Use outletReceptacleDescriptor to reliably determine the receptacle type. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletPoleCount | 1.3.6.1.4.1.13742.6.3.5.3.1.5 | Integer32 (2..4) | RO | 2 | |||||||||||||||||
column · Integer32 (2..4) · read-only · current The number of poles. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletRatedVoltage | 1.3.6.1.4.1.13742.6.3.5.3.1.6 | DisplayString | RO | 200-240V | |||||||||||||||||
column · DisplayString · read-only · current The outlet voltage rating. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletRatedCurrent | 1.3.6.1.4.1.13742.6.3.5.3.1.7 | DisplayString | RO | 10A | |||||||||||||||||
column · DisplayString · read-only · current The outlet current rating. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletRatedVA | 1.3.6.1.4.1.13742.6.3.5.3.1.8 | DisplayString | RO | | |||||||||||||||||
column · DisplayString · read-only · current The outlet VA (VoltAmps) rating. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletDeviceCapabilities | 1.3.6.1.4.1.13742.6.3.5.3.1.10 | Bits | RO | 9F 04 02 00 00 00 00 00 00 00 0 3 4 5 6 7 13 22 | |||||||||||||||||
column · Bits · read-only · current A bit string indicating which outlet sensors are available.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletPoleCapabilities | 1.3.6.1.4.1.13742.6.3.5.3.1.11 | Bits | RO | 00 00 00 00 00 00 00 00 00 00 | |||||||||||||||||
column · Bits · read-only · current A bit string indicating which outlet pole sensors are available.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletPowerCyclingPowerOffPeriod | 1.3.6.1.4.1.13742.6.3.5.3.1.12 | Unsigned32 (1..3600) | RW | 10 | |||||||||||||||||
column · Unsigned32 (1..3600) · read-write · current The power-off period when an outlet is cycled. Overrides the global value if outletUseGlobalPowerCyclingPowerOffPeriod is false. Specified in seconds, 1 <= value <= 3600. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletStateOnStartup | 1.3.6.1.4.1.13742.6.3.5.3.1.13 | OutletStateOnStartupEnumeration | RW | 3 | |||||||||||||||||
column · OutletStateOnStartupEnumeration · read-write · current The outlet state when powering the respective inlet. This value is ignored if relayBehaviorOnPowerLoss is set to latching. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletUseGlobalPowerCyclingPowerOffPeriod | 1.3.6.1.4.1.13742.6.3.5.3.1.14 | TruthValue | RW | 1 | |||||||||||||||||
column · TruthValue · read-write · current Indicates which power-off period to use when the outlet is cycled: - true: use globalOutletPowerCyclingPowerOffPeriod - false: use outletPowerCyclingPowerOffPeriod Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletSwitchable | 1.3.6.1.4.1.13742.6.3.5.3.1.28 | TruthValue | RO | 1 | |||||||||||||||||
column · TruthValue · read-only · current Is this outlet switchable? Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletReceptacleDescriptor | 1.3.6.1.4.1.13742.6.3.5.3.1.29 | DisplayString | RO | IEC 60320 C13 | |||||||||||||||||
column · DisplayString · read-only · current The outlet receptacle type as a string. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletNonCritical | 1.3.6.1.4.1.13742.6.3.5.3.1.30 | TruthValue | RW | 2 | |||||||||||||||||
column · TruthValue · read-write · current Is this outlet non-critical? Non-critical outlets will be switched off when load shedding is enabled. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletSequenceDelay | 1.3.6.1.4.1.13742.6.3.5.3.1.32 | Unsigned32 (0..3600) | RW | 0 | |||||||||||||||||
column · Unsigned32 (0..3600) · read-write · current The time interval between switching on this outlet and the next outlet in the outlet sequence. This applies to the following operations. 1) Switch all outlets on operation is executed 2) Power to the PDU is cycled It is specified in seconds, 0 <= value <= 3600 seconds. The effective time interval used can never be less than the inrushGuardDelay defined in the unitConfigurationTable. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletPowerSource | 1.3.6.1.4.1.13742.6.3.5.3.1.33 | RowPointer | RO | 1.3.6.1.4.1.13742.6.3.4.3.1.2.1.1 | |||||||||||||||||
column · RowPointer · read-only · current This object allows discovery of how the PDU is wired. It indicates the outlet's power source which can one of the following: - an inlet - an overcurrent protector - a transfer switch If the power source is an inlet, it contains the OID of an inletLabel in the inletConfigurationTable. The indices of the OID can then be used to reference other objects in the inlet tables. If the power source is an overcurrent protector, it contains the OID of an overCurrentProtectorLabel in the overCurrentProtectorConfigurationTable. The indices of the OID can then be used to reference other objects in the overcurrent protector tables. If the power source is a transfer switch, it contains the OID of a transferSwitchLabel in the transferSwitchConfigurationTable. The indices of the OID can then be used to reference other objects in the transfer switch tables. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletServiceMode | 1.3.6.1.4.1.13742.6.3.5.3.1.34 | TruthValue | RW | 2 | |||||||||||||||||
column · TruthValue · read-write · current Whether the outlet is currently in service mode Example values from LibreNMS test devices
| |||||||||||||||||||||
| ToutletSensorConfigurationTable | 1.3.6.1.4.1.13742.6.3.5.4 | NA | |||||||||||||||||||
table · not-accessible · current A list of outlet sensor configuration entries. | |||||||||||||||||||||
| RoutletSensorConfigurationEntry | 1.3.6.1.4.1.13742.6.3.5.4.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing outlet sensor configuration objects.
| |||||||||||||||||||||
| CoutletSensorLogAvailable | 1.3.6.1.4.1.13742.6.3.5.4.1.4 | TruthValue | RW | 1 | |||||||||||||||||
column · TruthValue · read-write · current Is data logging enabled for this sensor? Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletSensorUnits | 1.3.6.1.4.1.13742.6.3.5.4.1.6 | SensorUnitsEnumeration | RO | 2 | |||||||||||||||||
column · SensorUnitsEnumeration · read-only · current The unit in which the sensor reading is reported. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletSensorDecimalDigits | 1.3.6.1.4.1.13742.6.3.5.4.1.7 | Unsigned32 | RO | 3 | |||||||||||||||||
column · Unsigned32 · read-only · current The number of digits displayed to the right of the decimal point. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletSensorAccuracy | 1.3.6.1.4.1.13742.6.3.5.4.1.8 | HundredthsOfAPercentage | RO | deprecated | 0 | ||||||||||||||||
column · HundredthsOfAPercentage · read-only · deprecated The accuracy: the maximum relative difference (in percent) between measurement and the actual value. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletSensorResolution | 1.3.6.1.4.1.13742.6.3.5.4.1.9 | Unsigned32 | RO | 1 | |||||||||||||||||
column · Unsigned32 · read-only · current The resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletSensorTolerance | 1.3.6.1.4.1.13742.6.3.5.4.1.10 | Unsigned32 | RO | deprecated | 0 | ||||||||||||||||
column · Unsigned32 · read-only · deprecated The tolerance: the maximum difference between measurement and the actual value. The value of this OID variable should be scaled by (outletSensorDecimalDigits + 1). For example, if the value is 50 and outletSensorDecimalDigits is 2, then actual value is 0.05. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletSensorMaximum | 1.3.6.1.4.1.13742.6.3.5.4.1.11 | Unsigned32 | RO | 150000 | |||||||||||||||||
column · Unsigned32 · read-only · current The largest possible reading as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled maximum exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletSensorMinimum | 1.3.6.1.4.1.13742.6.3.5.4.1.12 | Unsigned32 | RO | 0 | |||||||||||||||||
column · Unsigned32 · read-only · current The smallest possible reading as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletSensorHysteresis | 1.3.6.1.4.1.13742.6.3.5.4.1.13 | Unsigned32 | RW | 1000 | |||||||||||||||||
column · Unsigned32 · read-write · current The hysteresis used when crossing a threshold towards the normal state. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletSensorStateChangeDelay | 1.3.6.1.4.1.13742.6.3.5.4.1.14 | Unsigned32 (0..300) | RW | 0 | |||||||||||||||||
column · Unsigned32 (0..300) · read-write · current The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the event is reported. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletSensorLowerCriticalThreshold | 1.3.6.1.4.1.13742.6.3.5.4.1.21 | Unsigned32 | RW | 0 | |||||||||||||||||
column · Unsigned32 · read-write · current The lower critical threshold as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletSensorLowerWarningThreshold | 1.3.6.1.4.1.13742.6.3.5.4.1.22 | Unsigned32 | RW | 0 | |||||||||||||||||
column · Unsigned32 · read-write · current The lower warning threshold as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletSensorUpperCriticalThreshold | 1.3.6.1.4.1.13742.6.3.5.4.1.23 | Unsigned32 | RW | 8000 | |||||||||||||||||
column · Unsigned32 · read-write · current The upper critical threshold as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletSensorUpperWarningThreshold | 1.3.6.1.4.1.13742.6.3.5.4.1.24 | Unsigned32 | RW | 6500 | |||||||||||||||||
column · Unsigned32 · read-write · current The upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletSensorEnabledThresholds | 1.3.6.1.4.1.13742.6.3.5.4.1.25 | Bits | RW | 30 2 3 | |||||||||||||||||
column · Bits · read-write · current A bit string indicating which thresholds are enabled. This parameter does not apply to sensors without numerical reading.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletSensorSignedMaximum | 1.3.6.1.4.1.13742.6.3.5.4.1.26 | Integer32 | RO | 150000 | |||||||||||||||||
column · Integer32 · read-only · current The largest possible reading as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletSensorSignedMinimum | 1.3.6.1.4.1.13742.6.3.5.4.1.27 | Integer32 | RO | 0 | |||||||||||||||||
column · Integer32 · read-only · current The smallest possible reading as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. This value determines whether to use the signed or unsigned threshold and value columns: If the minimum is below zero the sensor can have negative readings and the signed columns should be used. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletSensorSignedLowerCriticalThreshold | 1.3.6.1.4.1.13742.6.3.5.4.1.28 | Integer32 | RW | 0 | |||||||||||||||||
column · Integer32 · read-write · current The lower critical threshold as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletSensorSignedLowerWarningThreshold | 1.3.6.1.4.1.13742.6.3.5.4.1.29 | Integer32 | RW | 0 | |||||||||||||||||
column · Integer32 · read-write · current The lower warning threshold as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletSensorSignedUpperCriticalThreshold | 1.3.6.1.4.1.13742.6.3.5.4.1.30 | Integer32 | RW | 8000 | |||||||||||||||||
column · Integer32 · read-write · current The upper critical threshold as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletSensorSignedUpperWarningThreshold | 1.3.6.1.4.1.13742.6.3.5.4.1.31 | Integer32 | RW | 6500 | |||||||||||||||||
column · Integer32 · read-write · current The upper warning threshold as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ToutletPoleConfigurationTable | 1.3.6.1.4.1.13742.6.3.5.5 | NA | |||||||||||||||||||
table · not-accessible · current A list of outlet pole configuration entries. The number of entries is given by the value of outletPoleCount for the PDU. | |||||||||||||||||||||
| RoutletPoleConfigurationEntry | 1.3.6.1.4.1.13742.6.3.5.5.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing parameters for a particular outlet pole.
| |||||||||||||||||||||
| CoutletPoleLine | 1.3.6.1.4.1.13742.6.3.5.5.1.1 | LineEnumeration | RO | ||||||||||||||||||
column · LineEnumeration · read-only · current The phase for this outlet pole. | |||||||||||||||||||||
| CoutletPoleNode | 1.3.6.1.4.1.13742.6.3.5.5.1.2 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The node to which this outlet pole is connected | |||||||||||||||||||||
| ToutletPoleSensorConfigurationTable | 1.3.6.1.4.1.13742.6.3.5.6 | NA | |||||||||||||||||||
table · not-accessible · current A list of outlet pole sensor configuration entries. | |||||||||||||||||||||
| RoutletPoleSensorConfigurationEntry | 1.3.6.1.4.1.13742.6.3.5.6.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing outlet pole sensor configuration objects.
| |||||||||||||||||||||
| CoutletPoleIndex | 1.3.6.1.4.1.13742.6.3.5.6.1.1 | Integer32 (1..256) | NA | ||||||||||||||||||
column · Integer32 (1..256) · not-accessible · current A unique value for each outlet pole. Its value ranges between 1 and the value of outletPoleCount. | |||||||||||||||||||||
| CoutletPoleSensorLogAvailable | 1.3.6.1.4.1.13742.6.3.5.6.1.4 | TruthValue | RW | ||||||||||||||||||
column · TruthValue · read-write · current Is data logging enabled for this sensor? | |||||||||||||||||||||
| CoutletPoleSensorUnits | 1.3.6.1.4.1.13742.6.3.5.6.1.6 | SensorUnitsEnumeration | RO | ||||||||||||||||||
column · SensorUnitsEnumeration · read-only · current The unit in which the sensor reading is reported. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CoutletPoleSensorDecimalDigits | 1.3.6.1.4.1.13742.6.3.5.6.1.7 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The number of digits displayed to the right of the decimal point. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CoutletPoleSensorAccuracy | 1.3.6.1.4.1.13742.6.3.5.6.1.8 | HundredthsOfAPercentage | RO | deprecated | |||||||||||||||||
column · HundredthsOfAPercentage · read-only · deprecated The accuracy: the maximum relative difference (in percent) between measurement and the actual value. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CoutletPoleSensorResolution | 1.3.6.1.4.1.13742.6.3.5.6.1.9 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CoutletPoleSensorTolerance | 1.3.6.1.4.1.13742.6.3.5.6.1.10 | Unsigned32 | RO | deprecated | |||||||||||||||||
column · Unsigned32 · read-only · deprecated The tolerance: the maximum difference between measurement and the actual value. The value of this OID variable should be scaled by (outletPoleSensorDecimalDigits + 1). For example, if the value is 50 and outletPoleSensorDecimalDigits is 2, then actual value is 0.05. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CoutletPoleSensorMaximum | 1.3.6.1.4.1.13742.6.3.5.6.1.11 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The largest possible reading as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled maximum exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CoutletPoleSensorMinimum | 1.3.6.1.4.1.13742.6.3.5.6.1.12 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The smallest possible reading as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CoutletPoleSensorHysteresis | 1.3.6.1.4.1.13742.6.3.5.6.1.13 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The hysteresis used when crossing a threshold towards the normal state. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CoutletPoleSensorStateChangeDelay | 1.3.6.1.4.1.13742.6.3.5.6.1.14 | Unsigned32 (0..300) | RW | ||||||||||||||||||
column · Unsigned32 (0..300) · read-write · current The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the event is reported. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CoutletPoleSensorLowerCriticalThreshold | 1.3.6.1.4.1.13742.6.3.5.6.1.21 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The lower critical threshold as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CoutletPoleSensorLowerWarningThreshold | 1.3.6.1.4.1.13742.6.3.5.6.1.22 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The lower warning threshold as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CoutletPoleSensorUpperCriticalThreshold | 1.3.6.1.4.1.13742.6.3.5.6.1.23 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The upper critical threshold as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CoutletPoleSensorUpperWarningThreshold | 1.3.6.1.4.1.13742.6.3.5.6.1.24 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CoutletPoleSensorEnabledThresholds | 1.3.6.1.4.1.13742.6.3.5.6.1.25 | Bits | RW | ||||||||||||||||||
column · Bits · read-write · current A bit string indicating which thresholds are enabled. This parameter does not apply to sensors without numerical reading.
| |||||||||||||||||||||
| CoutletPoleSensorSignedMaximum | 1.3.6.1.4.1.13742.6.3.5.6.1.26 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The largest possible reading as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CoutletPoleSensorSignedMinimum | 1.3.6.1.4.1.13742.6.3.5.6.1.27 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The smallest possible reading as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value determines whether to use the signed or unsigned threshold and value columns: If the minimum is below zero the sensor can have negative readings and the signed columns should be used. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CoutletPoleSensorSignedLowerCriticalThreshold | 1.3.6.1.4.1.13742.6.3.5.6.1.28 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current The lower critical threshold as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CoutletPoleSensorSignedLowerWarningThreshold | 1.3.6.1.4.1.13742.6.3.5.6.1.29 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current The lower warning threshold as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CoutletPoleSensorSignedUpperCriticalThreshold | 1.3.6.1.4.1.13742.6.3.5.6.1.30 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current The upper critical threshold as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CoutletPoleSensorSignedUpperWarningThreshold | 1.3.6.1.4.1.13742.6.3.5.6.1.31 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current The upper warning threshold as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| NexternalSensors | 1.3.6.1.4.1.13742.6.3.6 | ||||||||||||||||||||
| TexternalSensorConfigurationTable | 1.3.6.1.4.1.13742.6.3.6.3 | NA | |||||||||||||||||||
table · not-accessible · current A list of external sensor configuration entries. The number of entries is given by the value of externalSensorCount for the PDU. | |||||||||||||||||||||
| RexternalSensorConfigurationEntry | 1.3.6.1.4.1.13742.6.3.6.3.1 | NA | |||||||||||||||||||
| CsensorID | 1.3.6.1.4.1.13742.6.3.6.3.1.1 | Integer32 (1..256) | NA | ||||||||||||||||||
column · Integer32 (1..256) · not-accessible · current A unique value for each sensor. Its value ranges between 1 and the value of externalSensorCount. | |||||||||||||||||||||
| CexternalSensorType | 1.3.6.1.4.1.13742.6.3.6.3.1.2 | SensorTypeEnumeration | RO | 10 | |||||||||||||||||
column · SensorTypeEnumeration · read-only · current The type of sensor. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CexternalSensorSerialNumber | 1.3.6.1.4.1.13742.6.3.6.3.1.3 | DisplayString | RO | AEI8801437 | |||||||||||||||||
column · DisplayString · read-only · current The sensor serial number. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CexternalSensorName | 1.3.6.1.4.1.13742.6.3.6.3.1.4 | DisplayString | RW | Temperature 1 | |||||||||||||||||
column · DisplayString · read-write · current The user-defined name. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CexternalSensorDescription | 1.3.6.1.4.1.13742.6.3.6.3.1.5 | DisplayString | RW | | |||||||||||||||||
column · DisplayString · read-write · current The user-defined description. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CexternalSensorXCoordinate | 1.3.6.1.4.1.13742.6.3.6.3.1.6 | DisplayString | RW | | |||||||||||||||||
column · DisplayString · read-write · current The X coordinate. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CexternalSensorYCoordinate | 1.3.6.1.4.1.13742.6.3.6.3.1.7 | DisplayString | RW | | |||||||||||||||||
column · DisplayString · read-write · current The Y coordinate. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CexternalSensorZCoordinate | 1.3.6.1.4.1.13742.6.3.6.3.1.8 | DisplayString | RW | | |||||||||||||||||
column · DisplayString · read-write · current The Z coordinate. The value must be a number if externalSensorsZCoordinateUnits is rackUnits. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CexternalSensorChannelNumber | 1.3.6.1.4.1.13742.6.3.6.3.1.9 | Integer32 | RO | -1 | |||||||||||||||||
column · Integer32 · read-only · current The channel number. This applies only to contact sensors, -1 for other sensors. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CexternalOnOffSensorSubtype | 1.3.6.1.4.1.13742.6.3.6.3.1.10 | SensorTypeEnumeration | RW | 31 | |||||||||||||||||
column · SensorTypeEnumeration · read-write · current The subtype of the binary sensor. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CexternalSensorLogAvailable | 1.3.6.1.4.1.13742.6.3.6.3.1.14 | TruthValue | RW | 1 | |||||||||||||||||
column · TruthValue · read-write · current Is data logging enabled for this sensor? Example values from LibreNMS test devices
| |||||||||||||||||||||
| CexternalSensorUnits | 1.3.6.1.4.1.13742.6.3.6.3.1.16 | SensorUnitsEnumeration | RO | 7 | |||||||||||||||||
column · SensorUnitsEnumeration · read-only · current The unit in which the sensor reading is reported. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CexternalSensorDecimalDigits | 1.3.6.1.4.1.13742.6.3.6.3.1.17 | Unsigned32 | RO | 1 | |||||||||||||||||
column · Unsigned32 · read-only · current The number of digits displayed to the right of the decimal point. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CexternalSensorAccuracy | 1.3.6.1.4.1.13742.6.3.6.3.1.18 | HundredthsOfAPercentage | RO | deprecated | 0 | ||||||||||||||||
column · HundredthsOfAPercentage · read-only · deprecated The accuracy: the maximum relative difference (in percent) between measurement and the actual value. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CexternalSensorResolution | 1.3.6.1.4.1.13742.6.3.6.3.1.19 | Unsigned32 | RO | 1 | |||||||||||||||||
column · Unsigned32 · read-only · current The resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CexternalSensorTolerance | 1.3.6.1.4.1.13742.6.3.6.3.1.20 | Unsigned32 | RO | deprecated | 0 | ||||||||||||||||
column · Unsigned32 · read-only · deprecated The tolerance: the maximum difference between measurement and the actual value. The value of this OID variable should be scaled by (externalSensorDecimalDigits + 1). For example, if the value is 50 and externalSensorDecimalDigits is 2, then actual value is 0.05. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CexternalSensorMaximum | 1.3.6.1.4.1.13742.6.3.6.3.1.21 | Integer32 | RO | 1250 | |||||||||||||||||
column · Integer32 · read-only · current The largest possible value The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CexternalSensorMinimum | 1.3.6.1.4.1.13742.6.3.6.3.1.22 | Integer32 | RO | -550 | |||||||||||||||||
column · Integer32 · read-only · current The smallest possible value The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CexternalSensorHysteresis | 1.3.6.1.4.1.13742.6.3.6.3.1.23 | Unsigned32 | RW | 10 | |||||||||||||||||
column · Unsigned32 · read-write · current The hysteresis used when crossing a threshold towards the normal state. The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CexternalSensorStateChangeDelay | 1.3.6.1.4.1.13742.6.3.6.3.1.24 | Unsigned32 (0..300) | RW | 0 | |||||||||||||||||
column · Unsigned32 (0..300) · read-write · current The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the event is reported. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CexternalSensorLowerCriticalThreshold | 1.3.6.1.4.1.13742.6.3.6.3.1.31 | Integer32 | RW | 100 | |||||||||||||||||
column · Integer32 · read-write · current The lower critical threshold The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CexternalSensorLowerWarningThreshold | 1.3.6.1.4.1.13742.6.3.6.3.1.32 | Integer32 | RW | 150 | |||||||||||||||||
column · Integer32 · read-write · current The lower warning threshold The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CexternalSensorUpperCriticalThreshold | 1.3.6.1.4.1.13742.6.3.6.3.1.33 | Integer32 | RW | 350 | |||||||||||||||||
column · Integer32 · read-write · current The upper critical threshold The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CexternalSensorUpperWarningThreshold | 1.3.6.1.4.1.13742.6.3.6.3.1.34 | Integer32 | RW | 300 | |||||||||||||||||
column · Integer32 · read-write · current The upper warning threshold The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CexternalSensorEnabledThresholds | 1.3.6.1.4.1.13742.6.3.6.3.1.35 | Bits | RW | F0 0 1 2 3 | |||||||||||||||||
column · Bits · read-write · current A bit string indicating which thresholds are enabled. This parameter does not apply to sensors without numerical reading.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CexternalSensorIsActuator | 1.3.6.1.4.1.13742.6.3.6.3.1.36 | TruthValue | RO | 2 | |||||||||||||||||
column · TruthValue · read-only · current Indicates whether the sensor is an actuator. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CexternalSensorPosition | 1.3.6.1.4.1.13742.6.3.6.3.1.37 | DisplayString | RO | DEVICE-1WIREPORT:1 | |||||||||||||||||
column · DisplayString · read-only · current The position of the sensor in the bus topology.
The format is a semicolon separated list of Keyword:value pairs.
Keyword can be one of the following:
ONBOARD, DEVICE-1WIREPORT, HUBPORT, CHAIN-POSITION, REMOTE-HUB,
WIRELESS-BRIDGE, WIRELESS-DEVICE
Examples:
1) Onboard sensor
ONBOARD:CC1
2) Old sensor connected to device 1-wire port
DEVICE-1WIREPORT:2
3) New-style sensor connected to device 1-wire port
DEVICE-1WIREPORT:2;CHAIN-POSITION:3
4) New-style sensor connected to hub port 3
DEVICE-1WIREPORT:2;CHAIN-POSITION:1;HUBPORT:3;CHAIN-POSITION:1
5) Old-style sensor connected to end of new-style sensor chain
DEVICE-1WIREPORT:2
6) Zigbee wireless sensor
WIRELESS-BRIDGE:1;WIRELESS-DEVICE:00540100Example values from LibreNMS test devices
| |||||||||||||||||||||
| CexternalSensorUseDefaultThresholds | 1.3.6.1.4.1.13742.6.3.6.3.1.38 | TruthValue | RW | 1 | |||||||||||||||||
column · TruthValue · read-write · current Use default thresholds for this sensor? True: Use default thresholds from externalSensorTypeDefaultThresholdsTable False: Use sensor-specific thresholds from this table Example values from LibreNMS test devices
| |||||||||||||||||||||
| CexternalSensorAlarmedToNormalDelay | 1.3.6.1.4.1.13742.6.3.6.3.1.39 | Integer32 (0..300) | RW | 0 | |||||||||||||||||
column · Integer32 (0..300) · read-write · current The delay (in seconds) before the sensor returns from alarmed to normal. This is supported for motion detectors only. For all other sensors the value is 0 and cannot be set to any other value. Example values from LibreNMS test devices
| |||||||||||||||||||||
| TexternalSensorTypeDefaultThresholdsTable | 1.3.6.1.4.1.13742.6.3.6.4 | NA | |||||||||||||||||||
table · not-accessible · current A table listing the default thresholds for each sensor type. The table contains a row for each supported type of external sensor with a numeric reading. | |||||||||||||||||||||
| RexternalSensorTypeDefaultThresholdsEntry | 1.3.6.1.4.1.13742.6.3.6.4.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing default thresholds for a sensor type.
| |||||||||||||||||||||
| CexternalSensorTypeDefaultHysteresis | 1.3.6.1.4.1.13742.6.3.6.4.1.3 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The hysteresis used when crossing a threshold towards the normal state. The value of this OID variable should be scaled by externalSensorTypeDefaultDecimalDigits. For example, if the value is 1 and externalSensorTypeDefaultDecimalDigits is 2, then actual value is 0.01. | |||||||||||||||||||||
| CexternalSensorTypeDefaultStateChangeDelay | 1.3.6.1.4.1.13742.6.3.6.4.1.4 | Unsigned32 (0..300) | RW | ||||||||||||||||||
column · Unsigned32 (0..300) · read-write · current The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the event is reported. | |||||||||||||||||||||
| CexternalSensorTypeDefaultLowerCriticalThreshold | 1.3.6.1.4.1.13742.6.3.6.4.1.5 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current The lower critical threshold The value of this OID variable should be scaled by externalSensorTypeDefaultDecimalDigits. For example, if the value is 1 and externalSensorTypeDefaultDecimalDigits is 2, then actual value is 0.01. | |||||||||||||||||||||
| CexternalSensorTypeDefaultLowerWarningThreshold | 1.3.6.1.4.1.13742.6.3.6.4.1.6 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current The lower warning threshold The value of this OID variable should be scaled by externalSensorTypeDefaultDecimalDigits. For example, if the value is 1 and externalSensorTypeDefaultDecimalDigits is 2, then actual value is 0.01. | |||||||||||||||||||||
| CexternalSensorTypeDefaultUpperCriticalThreshold | 1.3.6.1.4.1.13742.6.3.6.4.1.7 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current The upper critical threshold The value of this OID variable should be scaled by externalSensorTypeDefaultDecimalDigits. For example, if the value is 1 and externalSensorTypeDefaultDecimalDigits is 2, then actual value is 0.01. | |||||||||||||||||||||
| CexternalSensorTypeDefaultUpperWarningThreshold | 1.3.6.1.4.1.13742.6.3.6.4.1.8 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current The upper warning threshold The value of this OID variable should be scaled by externalSensorTypeDefaultDecimalDigits. For example, if the value is 1 and externalSensorTypeDefaultDecimalDigits is 2, then actual value is 0.01. | |||||||||||||||||||||
| CexternalSensorTypeDefaultEnabledThresholds | 1.3.6.1.4.1.13742.6.3.6.4.1.9 | Bits | RW | ||||||||||||||||||
column · Bits · read-write · current A bit string indicating which thresholds are enabled.
| |||||||||||||||||||||
| CexternalSensorTypeDefaultUnit | 1.3.6.1.4.1.13742.6.3.6.4.1.10 | SensorUnitsEnumeration | RO | ||||||||||||||||||
column · SensorUnitsEnumeration · read-only · current The unit in which the default threshold parameters are specified. | |||||||||||||||||||||
| CexternalSensorTypeDefaultDecimalDigits | 1.3.6.1.4.1.13742.6.3.6.4.1.11 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The number of digits displayed to the right of the decimal point. | |||||||||||||||||||||
| CexternalSensorTypeDefaultMaximum | 1.3.6.1.4.1.13742.6.3.6.4.1.12 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The largest possible threshold value for this sensor type. The value of this OID variable should be scaled by externalSensorTypeDefaultDecimalDigits. For example, if the value is 1 and externalSensorTypeDefaultDecimalDigits is 2, then the actual value is 0.01. | |||||||||||||||||||||
| CexternalSensorTypeDefaultMinimum | 1.3.6.1.4.1.13742.6.3.6.4.1.13 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The smallest possible threshold value for this sensor type. The value of this OID variable should be scaled by externalSensorTypeDefaultDecimalDigits. For example, if the value is 1 and externalSensorTypeDefaultDecimalDigits is 2, then the actual value is 0.01. | |||||||||||||||||||||
| TperipheralDevicePackageTable | 1.3.6.1.4.1.13742.6.3.6.5 | NA | |||||||||||||||||||
table · not-accessible · current A list of entries for the peripheral device packages connected to a PDU. The number of entries is given by the value of peripheralDevicePackagesCount. A peripheral device package contains one or more sensors or actuators in a single enclosure. | |||||||||||||||||||||
| RperipheralDevicePackageEntry | 1.3.6.1.4.1.13742.6.3.6.5.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing objects for a peripheral device package. | |||||||||||||||||||||
| CperipheralDevicePackageId | 1.3.6.1.4.1.13742.6.3.6.5.1.1 | Integer32 (0..256) | NA | ||||||||||||||||||
column · Integer32 (0..256) · not-accessible · current A unique value for each peripheral device package. | |||||||||||||||||||||
| CperipheralDevicePackageSerialNumber | 1.3.6.1.4.1.13742.6.3.6.5.1.3 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current The peripheral device package serial number. | |||||||||||||||||||||
| CperipheralDevicePackageModel | 1.3.6.1.4.1.13742.6.3.6.5.1.4 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current The peripheral device package model. Examples are DX-D2C6, DPX2-T1, DPX2-T1H1, DPX2-T2H1, DPX2-T3H1 | |||||||||||||||||||||
| CperipheralDevicePackageFirmwareVersion | 1.3.6.1.4.1.13742.6.3.6.5.1.5 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current The peripheral device package firmware version. | |||||||||||||||||||||
| CperipheralDevicePackageMinFirmwareVersion | 1.3.6.1.4.1.13742.6.3.6.5.1.6 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current The peripheral device package minimum firmware version. This field may be empty. If it is not empty, then it shall not be possible to downgrade the peripheral device firmware to an older version. | |||||||||||||||||||||
| CperipheralDevicePackageFirmwareTimeStamp | 1.3.6.1.4.1.13742.6.3.6.5.1.7 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The time when the peripheral device package firmware was last updated. It is measured in seconds since January 1, 1970 (midnight UTC/GMT). | |||||||||||||||||||||
| CperipheralDevicePackagePosition | 1.3.6.1.4.1.13742.6.3.6.5.1.8 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current The position of the package in the bus topology.
The format is a semicolon separated list of Keyword:value pairs.
Keyword can be one of the following:
ONBOARD, DEVICE-1WIREPORT, HUBPORT, CHAIN-POSITION, REMOTE-HUB
Examples:
1) Onboard Sensor
ONBOARD:CC1
2) Old sensor connected to device 1-wire port
DEVICE-1WIREPORT:2
3) New-style sensor connected to device 1-wire port
DEVICE-1WIREPORT:2;CHAIN-POSITION:3
4) New-style sensor connected to hub port 3
DEVICE-1WIREPORT:2;CHAIN-POSITION:1;HUBPORT:3;CHAIN-POSITION:1
5) Old-style sensor connected to end of new-style sensor chain
DEVICE-1WIREPORT:2; | |||||||||||||||||||||
| CperipheralDevicePackageState | 1.3.6.1.4.1.13742.6.3.6.5.1.9 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current The state of the package. | |||||||||||||||||||||
| NserverReachability | 1.3.6.1.4.1.13742.6.3.7 | ||||||||||||||||||||
| TserverReachabilityTable | 1.3.6.1.4.1.13742.6.3.7.3 | NA | |||||||||||||||||||
table · not-accessible · current A list of server entries. The number of entries is given by the value of serverCount for the PDU. | |||||||||||||||||||||
| RserverReachabilityEntry | 1.3.6.1.4.1.13742.6.3.7.3.1 | NA | |||||||||||||||||||
| CserverID | 1.3.6.1.4.1.13742.6.3.7.3.1.1 | Integer32 (1..256) | NA | ||||||||||||||||||
column · Integer32 (1..256) · not-accessible · current A unique value for each server. Its value ranges between 1 and the value of serverCount for that PDU | |||||||||||||||||||||
| CserverIPAddress | 1.3.6.1.4.1.13742.6.3.7.3.1.3 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current The IP Address/host name of the server | |||||||||||||||||||||
| CserverPingEnabled | 1.3.6.1.4.1.13742.6.3.7.3.1.4 | TruthValue | RW | ||||||||||||||||||
column · TruthValue · read-write · current Is ping enabled for this server? | |||||||||||||||||||||
| Nwires | 1.3.6.1.4.1.13742.6.3.8 | ||||||||||||||||||||
| TwireConfigurationTable | 1.3.6.1.4.1.13742.6.3.8.3 | NA | obsolete | ||||||||||||||||||
table · not-accessible · obsolete A list of wire configuration entries. The number of entries is given by the value of wireCount for the PDU. Note: This feature is no longer used, the table is always empty. | |||||||||||||||||||||
| RwireConfigurationEntry | 1.3.6.1.4.1.13742.6.3.8.3.1 | NA | obsolete | ||||||||||||||||||
| CwireId | 1.3.6.1.4.1.13742.6.3.8.3.1.1 | Integer32 (1..256) | NA | obsolete | |||||||||||||||||
column · Integer32 (1..256) · not-accessible · obsolete A unique value for each wire. Its value ranges between 1 and the value of wireCount. | |||||||||||||||||||||
| CwireLabel | 1.3.6.1.4.1.13742.6.3.8.3.1.2 | DisplayString | RO | obsolete | |||||||||||||||||
column · DisplayString · read-only · obsolete The label on the PDU identifying the wire. | |||||||||||||||||||||
| CwireCapabilities | 1.3.6.1.4.1.13742.6.3.8.3.1.3 | Bits | RO | obsolete | |||||||||||||||||
column · Bits · read-only · obsolete A bit string indicating which wire sensors are available.
| |||||||||||||||||||||
| CwirePowerSource | 1.3.6.1.4.1.13742.6.3.8.3.1.4 | RowPointer | RO | obsolete | |||||||||||||||||
column · RowPointer · read-only · obsolete This object allows discovery of how the PDU is wired. It indicates the wire's power source which can one of the following: - an inlet - an overcurrent protector - a transfer switch If the power source is an inlet, it contains the OID of an inletLabel in the inletConfigurationTable. The indices of the OID can then be used to reference other objects in the inlet tables. If the power source is an overcurrent protector, it contains the OID of an overCurrentProtectorLabel in the overCurrentProtectorConfigurationTable. The indices of the OID can then be used to reference other objects in the overcurrent protector tables. If the power source is a transfer switch, it contains the OID of a transferSwitchLabel in the transferSwitchConfigurationTable. The indices of the OID can then be used to reference other objects in the transfer switch tables. | |||||||||||||||||||||
| TwireSensorConfigurationTable | 1.3.6.1.4.1.13742.6.3.8.4 | NA | obsolete | ||||||||||||||||||
table · not-accessible · obsolete A list of wire sensor configuration entries. Note: This feature is no longer used, the table is always empty. | |||||||||||||||||||||
| RwireSensorConfigurationEntry | 1.3.6.1.4.1.13742.6.3.8.4.1 | NA | obsolete | ||||||||||||||||||
row · not-accessible · obsolete An entry containing wire sensor configuration objects.
| |||||||||||||||||||||
| CwireSensorLogAvailable | 1.3.6.1.4.1.13742.6.3.8.4.1.4 | TruthValue | RW | obsolete | |||||||||||||||||
column · TruthValue · read-write · obsolete Is data logging enabled for this sensor? | |||||||||||||||||||||
| CwireSensorUnits | 1.3.6.1.4.1.13742.6.3.8.4.1.6 | SensorUnitsEnumeration | RO | obsolete | |||||||||||||||||
column · SensorUnitsEnumeration · read-only · obsolete The unit in which the sensor reading is reported. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CwireSensorDecimalDigits | 1.3.6.1.4.1.13742.6.3.8.4.1.7 | Unsigned32 | RO | obsolete | |||||||||||||||||
column · Unsigned32 · read-only · obsolete The number of digits displayed to the right of the decimal point. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CwireSensorAccuracy | 1.3.6.1.4.1.13742.6.3.8.4.1.8 | HundredthsOfAPercentage | RO | obsolete | |||||||||||||||||
column · HundredthsOfAPercentage · read-only · obsolete The accuracy: the maximum relative difference (in percent) between measurement and the actual value. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CwireSensorResolution | 1.3.6.1.4.1.13742.6.3.8.4.1.9 | Unsigned32 | RO | obsolete | |||||||||||||||||
column · Unsigned32 · read-only · obsolete The resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CwireSensorTolerance | 1.3.6.1.4.1.13742.6.3.8.4.1.10 | Unsigned32 | RO | obsolete | |||||||||||||||||
column · Unsigned32 · read-only · obsolete The tolerance: the maximum difference between measurement and the actual value. The value of this OID variable should be scaled by (wireSensorDecimalDigits + 1). For example, if the value is 50 and wireSensorDecimalDigits is 2, then actual value is 0.05. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CwireSensorMaximum | 1.3.6.1.4.1.13742.6.3.8.4.1.11 | Unsigned32 | RO | obsolete | |||||||||||||||||
column · Unsigned32 · read-only · obsolete The largest possible reading as an unsigned integer. The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled maximum exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CwireSensorMinimum | 1.3.6.1.4.1.13742.6.3.8.4.1.12 | Unsigned32 | RO | obsolete | |||||||||||||||||
column · Unsigned32 · read-only · obsolete The smallest possible reading as an unsigned integer. The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CwireSensorHysteresis | 1.3.6.1.4.1.13742.6.3.8.4.1.13 | Unsigned32 | RW | obsolete | |||||||||||||||||
column · Unsigned32 · read-write · obsolete The hysteresis used when crossing a threshold towards the normal state. The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CwireSensorStateChangeDelay | 1.3.6.1.4.1.13742.6.3.8.4.1.14 | Unsigned32 (0..300) | RW | obsolete | |||||||||||||||||
column · Unsigned32 (0..300) · read-write · obsolete The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the event is reported. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CwireSensorLowerCriticalThreshold | 1.3.6.1.4.1.13742.6.3.8.4.1.21 | Unsigned32 | RW | obsolete | |||||||||||||||||
column · Unsigned32 · read-write · obsolete The lower critical threshold as an unsigned integer. The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CwireSensorLowerWarningThreshold | 1.3.6.1.4.1.13742.6.3.8.4.1.22 | Unsigned32 | RW | obsolete | |||||||||||||||||
column · Unsigned32 · read-write · obsolete The lower warning threshold as an unsigned integer. The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CwireSensorUpperCriticalThreshold | 1.3.6.1.4.1.13742.6.3.8.4.1.23 | Unsigned32 | RW | obsolete | |||||||||||||||||
column · Unsigned32 · read-write · obsolete The upper critical threshold as an unsigned integer. The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CwireSensorUpperWarningThreshold | 1.3.6.1.4.1.13742.6.3.8.4.1.24 | Unsigned32 | RW | obsolete | |||||||||||||||||
column · Unsigned32 · read-write · obsolete The upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CwireSensorEnabledThresholds | 1.3.6.1.4.1.13742.6.3.8.4.1.25 | Bits | RW | obsolete | |||||||||||||||||
column · Bits · read-write · obsolete A bit string indicating which thresholds are enabled. This parameter does not apply to sensors without numerical reading.
| |||||||||||||||||||||
| NtransferSwitch | 1.3.6.1.4.1.13742.6.3.9 | ||||||||||||||||||||
| TtransferSwitchConfigurationTable | 1.3.6.1.4.1.13742.6.3.9.3 | NA | |||||||||||||||||||
table · not-accessible · current A list of transfer switch configuration entries. The number of entries is given by the value of transferSwitchCount. | |||||||||||||||||||||
| RtransferSwitchConfigurationEntry | 1.3.6.1.4.1.13742.6.3.9.3.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing objects for a particular transfer switch.
| |||||||||||||||||||||
| CtransferSwitchId | 1.3.6.1.4.1.13742.6.3.9.3.1.1 | Integer32 (1..256) | NA | ||||||||||||||||||
column · Integer32 (1..256) · not-accessible · current A unique value for each transfer switch. Its value ranges between 1 and the value of transferSwitchCount. | |||||||||||||||||||||
| CtransferSwitchLabel | 1.3.6.1.4.1.13742.6.3.9.3.1.2 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current The label on the PDU identifying the transfer switch. | |||||||||||||||||||||
| CtransferSwitchName | 1.3.6.1.4.1.13742.6.3.9.3.1.3 | DisplayString | RW | ||||||||||||||||||
column · DisplayString · read-write · current The user-defined name of the transfer switch. | |||||||||||||||||||||
| CtransferSwitchPreferredInlet | 1.3.6.1.4.1.13742.6.3.9.3.1.4 | Integer32 (1..64) | RO | ||||||||||||||||||
column · Integer32 (1..64) · read-only · current The preferred inlet. This is the inlet to be selected in case both inlets have acceptable power. | |||||||||||||||||||||
| CtransferSwitchPoleCount | 1.3.6.1.4.1.13742.6.3.9.3.1.5 | Integer32 (2..4) | RO | ||||||||||||||||||
column · Integer32 (2..4) · read-only · current The number of poles. | |||||||||||||||||||||
| CtransferSwitchAutoReTransferEnabled | 1.3.6.1.4.1.13742.6.3.9.3.1.20 | TruthValue | RW | ||||||||||||||||||
column · TruthValue · read-write · current Enables or disables automatic retransfer from the standby inlet to the preferred inlet after power has been restored. | |||||||||||||||||||||
| CtransferSwitchAutoReTransferWaitTime | 1.3.6.1.4.1.13742.6.3.9.3.1.21 | Unsigned32 (1..180) | RW | ||||||||||||||||||
column · Unsigned32 (1..180) · read-write · current The delay for automatic retransfers. Retransfer occurs this many seconds after the condition causing the original transfer has been corrected. | |||||||||||||||||||||
| CtransferSwitchAutoReTransferRequiresPhaseSync | 1.3.6.1.4.1.13742.6.3.9.3.1.22 | TruthValue | RW | ||||||||||||||||||
column · TruthValue · read-write · current Enables or disables automatic retransfer in case the two inlets are not synchronized. If set to True, automatic retransfer is inhibited while a phase sync alarm is present, i.e. the phase difference between the two inlets is too large. | |||||||||||||||||||||
| CtransferSwitchFrontPanelManualTransferButtonEnabled | 1.3.6.1.4.1.13742.6.3.9.3.1.23 | TruthValue | RW | ||||||||||||||||||
column · TruthValue · read-write · current Enables or disables the Manual Transfer button on the unit's front panel. | |||||||||||||||||||||
| CtransferSwitchCapabilities | 1.3.6.1.4.1.13742.6.3.9.3.1.24 | Bits | RO | ||||||||||||||||||
column · Bits · read-only · current A bit string indicating which sensors are available for the transfer switch.
| |||||||||||||||||||||
| CtransferSwitchPowerSource1 | 1.3.6.1.4.1.13742.6.3.9.3.1.31 | RowPointer | RO | ||||||||||||||||||
column · RowPointer · read-only · current This object allows discovery of how the PDU is wired. It indicates the transfer switch's first power source, typically a fuse. It contains the OID of an overCurrentProtectorLabel in the overCurrentProtectorConfiguration Table. The indices of the OID can then be used to reference other objects in the overcurrent protector tables. | |||||||||||||||||||||
| CtransferSwitchPowerSource2 | 1.3.6.1.4.1.13742.6.3.9.3.1.32 | RowPointer | RO | ||||||||||||||||||
column · RowPointer · read-only · current This object allows discovery of how the PDU is wired. It indicates the transfer switch's second power source, typically a fuse. It contains the OID of an overCurrentProtectorLabel in the overCurrentProtectorConfiguration Table. The indices of the OID can then be used to reference other objects in the overcurrent protector tables. | |||||||||||||||||||||
| TtransferSwitchSensorConfigurationTable | 1.3.6.1.4.1.13742.6.3.9.4 | NA | |||||||||||||||||||
table · not-accessible · current A list of transfer switch sensor configuration entries. | |||||||||||||||||||||
| RtransferSwitchSensorConfigurationEntry | 1.3.6.1.4.1.13742.6.3.9.4.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing transfer switch sensor configuration objects.
| |||||||||||||||||||||
| CtransferSwitchSensorLogAvailable | 1.3.6.1.4.1.13742.6.3.9.4.1.4 | TruthValue | RW | ||||||||||||||||||
column · TruthValue · read-write · current Is data logging enabled for this sensor? | |||||||||||||||||||||
| CtransferSwitchSensorUnits | 1.3.6.1.4.1.13742.6.3.9.4.1.6 | SensorUnitsEnumeration | RO | ||||||||||||||||||
column · SensorUnitsEnumeration · read-only · current The unit in which the sensor reading is reported. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CtransferSwitchSensorDecimalDigits | 1.3.6.1.4.1.13742.6.3.9.4.1.7 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The number of digits displayed to the right of the decimal point. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CtransferSwitchSensorAccuracy | 1.3.6.1.4.1.13742.6.3.9.4.1.8 | HundredthsOfAPercentage | RO | deprecated | |||||||||||||||||
column · HundredthsOfAPercentage · read-only · deprecated The accuracy: the maximum relative difference (in percent) between measurement and the actual value. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CtransferSwitchSensorResolution | 1.3.6.1.4.1.13742.6.3.9.4.1.9 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CtransferSwitchSensorTolerance | 1.3.6.1.4.1.13742.6.3.9.4.1.10 | Unsigned32 | RO | deprecated | |||||||||||||||||
column · Unsigned32 · read-only · deprecated The tolerance: the maximum difference between measurement and the actual value. The value of this OID variable should be scaled by (transferSwitchSensorDecimalDigits + 1). For example, if the value is 50 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.05. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CtransferSwitchSensorMaximum | 1.3.6.1.4.1.13742.6.3.9.4.1.11 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The largest possible reading as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled maximum exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CtransferSwitchSensorMinimum | 1.3.6.1.4.1.13742.6.3.9.4.1.12 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The smallest possible reading as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CtransferSwitchSensorHysteresis | 1.3.6.1.4.1.13742.6.3.9.4.1.13 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The hysteresis used when crossing a threshold towards the normal state. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CtransferSwitchSensorStateChangeDelay | 1.3.6.1.4.1.13742.6.3.9.4.1.14 | Unsigned32 (0..300) | RW | ||||||||||||||||||
column · Unsigned32 (0..300) · read-write · current The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the event is reported. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CtransferSwitchSensorLowerCriticalThreshold | 1.3.6.1.4.1.13742.6.3.9.4.1.21 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The lower critical threshold as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CtransferSwitchSensorLowerWarningThreshold | 1.3.6.1.4.1.13742.6.3.9.4.1.22 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The lower warning threshold as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CtransferSwitchSensorUpperCriticalThreshold | 1.3.6.1.4.1.13742.6.3.9.4.1.23 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The upper critical threshold as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CtransferSwitchSensorUpperWarningThreshold | 1.3.6.1.4.1.13742.6.3.9.4.1.24 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CtransferSwitchSensorEnabledThresholds | 1.3.6.1.4.1.13742.6.3.9.4.1.25 | Bits | RW | ||||||||||||||||||
column · Bits · read-write · current A bit string indicating which thresholds are enabled. This parameter does not apply to sensors without numerical reading.
| |||||||||||||||||||||
| CtransferSwitchSensorSignedMaximum | 1.3.6.1.4.1.13742.6.3.9.4.1.26 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The largest possible reading as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CtransferSwitchSensorSignedMinimum | 1.3.6.1.4.1.13742.6.3.9.4.1.27 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The smallest possible reading as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. This value determines whether to use the signed or unsigned threshold and value columns: If the minimum is below zero the sensor can have negative readings and the signed columns should be used. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CtransferSwitchSensorSignedLowerCriticalThreshold | 1.3.6.1.4.1.13742.6.3.9.4.1.28 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current The lower critical threshold as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CtransferSwitchSensorSignedLowerWarningThreshold | 1.3.6.1.4.1.13742.6.3.9.4.1.29 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current The lower warning threshold as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CtransferSwitchSensorSignedUpperCriticalThreshold | 1.3.6.1.4.1.13742.6.3.9.4.1.30 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current The upper critical threshold as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CtransferSwitchSensorSignedUpperWarningThreshold | 1.3.6.1.4.1.13742.6.3.9.4.1.31 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current The upper warning threshold as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| TtransferSwitchPoleConfigurationTable | 1.3.6.1.4.1.13742.6.3.9.5 | NA | |||||||||||||||||||
table · not-accessible · current A list of transfer switch pole configuration entries. The number of entries is given by the value of transferSwitchPoleCount. | |||||||||||||||||||||
| RtransferSwitchPoleConfigurationEntry | 1.3.6.1.4.1.13742.6.3.9.5.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing parameters for a particular transfer switch pole. | |||||||||||||||||||||
| CtransferSwitchPoleIndex | 1.3.6.1.4.1.13742.6.3.9.5.1.1 | Integer32 (1..256) | NA | ||||||||||||||||||
column · Integer32 (1..256) · not-accessible · current A unique value for each transfer switch pole. Its value ranges between 1 and the value of transferSwitchPoleCount. | |||||||||||||||||||||
| CtransferSwitchPoleLine | 1.3.6.1.4.1.13742.6.3.9.5.1.2 | LineEnumeration | RO | ||||||||||||||||||
column · LineEnumeration · read-only · current The phase for this transfer switch pole. | |||||||||||||||||||||
| CtransferSwitchPoleIn1Node | 1.3.6.1.4.1.13742.6.3.9.5.1.3 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The node to which this transfer switch pole input 1 is connected | |||||||||||||||||||||
| CtransferSwitchPoleIn2Node | 1.3.6.1.4.1.13742.6.3.9.5.1.4 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The node to which this transfer switch pole input 2 is connected | |||||||||||||||||||||
| CtransferSwitchPoleOutNode | 1.3.6.1.4.1.13742.6.3.9.5.1.5 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The node to which this transfer switch pole output is connected | |||||||||||||||||||||
| NpowerMeter | 1.3.6.1.4.1.13742.6.3.10 | ||||||||||||||||||||
| TpowerMeterConfigurationTable | 1.3.6.1.4.1.13742.6.3.10.2 | NA | |||||||||||||||||||
table · not-accessible · current A list of power meter and panel configuration entries. Note: Also see inlet tables for settings and sensor information. | |||||||||||||||||||||
| RpowerMeterConfigurationEntry | 1.3.6.1.4.1.13742.6.3.10.2.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing configuration objects for power meters and panels.
| |||||||||||||||||||||
| CpowerMeterPhaseCTRating | 1.3.6.1.4.1.13742.6.3.10.2.1.2 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The rating of the phase CT in Amps, or 0 if no CT is present. At present, read-only access; see MIN-ACCESS in MODULE-COMPLIANCE ModulecomplianceRev2 | |||||||||||||||||||||
| CpowerMeterNeutralCTRating | 1.3.6.1.4.1.13742.6.3.10.2.1.3 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The rating of the neutral CT in Amps, or 0 if no CT is present. At present, read-only access; see MIN-ACCESS in MODULE-COMPLIANCE ModulecomplianceRev2 | |||||||||||||||||||||
| CpowerMeterEarthCTRating | 1.3.6.1.4.1.13742.6.3.10.2.1.4 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The rating of the earth CT in Amps, or 0 if no CT is present. At present, read-only access; see MIN-ACCESS in MODULE-COMPLIANCE ModulecomplianceRev2 | |||||||||||||||||||||
| CpowerMeterBranchCount | 1.3.6.1.4.1.13742.6.3.10.2.1.5 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The maximum number of circuits supported by the panel. This can be used to distinguish between panels (>0) and power meters (0). See circuitCount for the number of currently defined circuits. | |||||||||||||||||||||
| CpowerMeterPanelPositions | 1.3.6.1.4.1.13742.6.3.10.2.1.6 | Integer32 (0..256) | RO | ||||||||||||||||||
column · Integer32 (0..256) · read-only · current The number of circuit positions in the panel, or 0 for power meters. Its value is specified by the user when configuring a panel | |||||||||||||||||||||
| CpowerMeterPanelLayout | 1.3.6.1.4.1.13742.6.3.10.2.1.7 | PanelLayoutEnumeration | RO | ||||||||||||||||||
column · PanelLayoutEnumeration · read-only · current The panel circuit position layout: one or two columns. This is valid only for panels, the value is -1 for power meters. | |||||||||||||||||||||
| CpowerMeterPanelNumbering | 1.3.6.1.4.1.13742.6.3.10.2.1.8 | PanelNumberingEnumeration | RO | ||||||||||||||||||
column · PanelNumberingEnumeration · read-only · current The panel circuit position numbering scheme: odd/even or sequential. This is valid only for panels, the value is -1 for power meters. | |||||||||||||||||||||
| CpowerMeterType | 1.3.6.1.4.1.13742.6.3.10.2.1.9 | PowerMeterTypeEnumeration | RO | ||||||||||||||||||
column · PowerMeterTypeEnumeration · read-only · current The power meter type: 3-phase, single-phase or split-phase. | |||||||||||||||||||||
| Ncircuit | 1.3.6.1.4.1.13742.6.3.11 | ||||||||||||||||||||
| TcircuitConfigurationTable | 1.3.6.1.4.1.13742.6.3.11.2 | NA | |||||||||||||||||||
table · not-accessible · current A list of circuit configuration entries. The number of entries is given by the value of panelCircuitPositionCount. | |||||||||||||||||||||
| RcircuitConfigurationEntry | 1.3.6.1.4.1.13742.6.3.11.2.1 | NA | |||||||||||||||||||
| CcircuitId | 1.3.6.1.4.1.13742.6.3.11.2.1.1 | Integer32 (1..1024) | NA | ||||||||||||||||||
column · Integer32 (1..1024) · not-accessible · current A unique value for each circuit. Its value is the smallest panel position occupied by the circuit. | |||||||||||||||||||||
| CcircuitPoleCount | 1.3.6.1.4.1.13742.6.3.11.2.1.2 | Integer32 (1..256) | RO | ||||||||||||||||||
column · Integer32 (1..256) · read-only · current The number of panel positions occupied by the circuit. | |||||||||||||||||||||
| CcircuitName | 1.3.6.1.4.1.13742.6.3.11.2.1.3 | DisplayString | RW | ||||||||||||||||||
column · DisplayString · read-write · current The user-defined name for the circuit. | |||||||||||||||||||||
| CcircuitType | 1.3.6.1.4.1.13742.6.3.11.2.1.4 | CircuitTypeEnumeration | RO | ||||||||||||||||||
column · CircuitTypeEnumeration · read-only · current The circuit type: line-line, line-neutral, line-line-neutral or 3-phase | |||||||||||||||||||||
| CcircuitRatedCurrent | 1.3.6.1.4.1.13742.6.3.11.2.1.5 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The rating of the breaker for the circuit in Amps. At present, read-only access; see MIN-ACCESS in MODULE-COMPLIANCE ModulecomplianceRev2 | |||||||||||||||||||||
| CcircuitCTRating | 1.3.6.1.4.1.13742.6.3.11.2.1.6 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The rating of the CTs metering this circuit in Amps. At present, read-only access; see MIN-ACCESS in MODULE-COMPLIANCE ModulecomplianceRev2 | |||||||||||||||||||||
| CcircuitCapabilities | 1.3.6.1.4.1.13742.6.3.11.2.1.7 | Bits | RO | ||||||||||||||||||
column · Bits · read-only · current A bit string indicating which sensors are available for the circuit.
| |||||||||||||||||||||
| CcircuitPoleCapabilities | 1.3.6.1.4.1.13742.6.3.11.2.1.8 | Bits | RO | ||||||||||||||||||
column · Bits · read-only · current A bit string indicating which sensors are available for each circuit pole.
| |||||||||||||||||||||
| CcircuitPowerSource | 1.3.6.1.4.1.13742.6.3.11.2.1.9 | RowPointer | RO | ||||||||||||||||||
column · RowPointer · read-only · current This object allows discovery of how the circuit is wired. It indicates the circuit's power source, typically an inlet. It contains the OID of an inletLabel in the inletConfigurationTable. The indices of the OID can then be used to reference other objects in the inlet and power meter tables. | |||||||||||||||||||||
| TcircuitPoleConfigurationTable | 1.3.6.1.4.1.13742.6.3.11.3 | NA | |||||||||||||||||||
table · not-accessible · current A list of branch circuit pole configuration entries. The number of entries is given by the value of circuitPoleCount for the circuit. | |||||||||||||||||||||
| RcircuitPoleConfigurationEntry | 1.3.6.1.4.1.13742.6.3.11.3.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing configuration objects for the circuit poles.
| |||||||||||||||||||||
| CcircuitPoleId | 1.3.6.1.4.1.13742.6.3.11.3.1.1 | Integer32 (1..256) | NA | ||||||||||||||||||
column · Integer32 (1..256) · not-accessible · current A unique value for each circuit pole. Its value ranges between 1 and the value of circuitPoleCount. | |||||||||||||||||||||
| CcircuitPolePanelPosition | 1.3.6.1.4.1.13742.6.3.11.3.1.2 | Integer32 (1..256) | RO | ||||||||||||||||||
column · Integer32 (1..256) · read-only · current The panel position for this pole. | |||||||||||||||||||||
| CcircuitPoleCTNumber | 1.3.6.1.4.1.13742.6.3.11.3.1.3 | Integer32 (0..256) | RW | ||||||||||||||||||
column · Integer32 (0..256) · read-write · current The CT number for this circuit pole, or 0 if no CT is present. At present, read-only access; see MIN-ACCESS in MODULE-COMPLIANCE ModulecomplianceRev2 | |||||||||||||||||||||
| CcircuitPolePhase | 1.3.6.1.4.1.13742.6.3.11.3.1.4 | PhaseEnumeration | RW | ||||||||||||||||||
column · PhaseEnumeration · read-write · current The phase for this circuit pole. At present, read-only access; see MIN-ACCESS in MODULE-COMPLIANCE ModulecomplianceRev2 | |||||||||||||||||||||
| TcircuitSensorConfigurationTable | 1.3.6.1.4.1.13742.6.3.11.4 | NA | |||||||||||||||||||
table · not-accessible · current A list of circuit sensor configuration entries. | |||||||||||||||||||||
| RcircuitSensorConfigurationEntry | 1.3.6.1.4.1.13742.6.3.11.4.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing circuit sensor configuration objects.
| |||||||||||||||||||||
| CcircuitSensorLogAvailable | 1.3.6.1.4.1.13742.6.3.11.4.1.4 | TruthValue | RW | ||||||||||||||||||
column · TruthValue · read-write · current Is data logging enabled for this sensor? | |||||||||||||||||||||
| CcircuitSensorUnits | 1.3.6.1.4.1.13742.6.3.11.4.1.6 | SensorUnitsEnumeration | RO | ||||||||||||||||||
column · SensorUnitsEnumeration · read-only · current The unit in which the sensor reading is reported. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CcircuitSensorDecimalDigits | 1.3.6.1.4.1.13742.6.3.11.4.1.7 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The number of digits displayed to the right of the decimal point. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CcircuitSensorResolution | 1.3.6.1.4.1.13742.6.3.11.4.1.9 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CcircuitSensorMaximum | 1.3.6.1.4.1.13742.6.3.11.4.1.11 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The largest possible reading as an unsigned integer. The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled maximum exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CcircuitSensorMinimum | 1.3.6.1.4.1.13742.6.3.11.4.1.12 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The smallest possible reading as an unsigned integer. The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CcircuitSensorHysteresis | 1.3.6.1.4.1.13742.6.3.11.4.1.13 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The hysteresis used when crossing a threshold towards the normal state. The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CcircuitSensorStateChangeDelay | 1.3.6.1.4.1.13742.6.3.11.4.1.14 | Unsigned32 (0..300) | RW | ||||||||||||||||||
column · Unsigned32 (0..300) · read-write · current The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the event is reported. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CcircuitSensorLowerCriticalThreshold | 1.3.6.1.4.1.13742.6.3.11.4.1.21 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The lower critical threshold as an unsigned integer. The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CcircuitSensorLowerWarningThreshold | 1.3.6.1.4.1.13742.6.3.11.4.1.22 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The lower warning threshold as an unsigned integer. The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CcircuitSensorUpperCriticalThreshold | 1.3.6.1.4.1.13742.6.3.11.4.1.23 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The upper critical threshold as an unsigned integer. The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CcircuitSensorUpperWarningThreshold | 1.3.6.1.4.1.13742.6.3.11.4.1.24 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CcircuitSensorEnabledThresholds | 1.3.6.1.4.1.13742.6.3.11.4.1.25 | Bits | RW | ||||||||||||||||||
column · Bits · read-write · current A bit string indicating which thresholds are enabled. This parameter does not apply to sensors without numerical reading.
| |||||||||||||||||||||
| CcircuitSensorSignedMaximum | 1.3.6.1.4.1.13742.6.3.11.4.1.26 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The largest possible reading as a signed integer. The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CcircuitSensorSignedMinimum | 1.3.6.1.4.1.13742.6.3.11.4.1.27 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The smallest possible reading as a signed integer. The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2, then actual value is 0.01. This value determines whether to use the signed or unsigned threshold and value columns: If the minimum is below zero the sensor can have negative readings and the signed columns should be used. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CcircuitSensorSignedLowerCriticalThreshold | 1.3.6.1.4.1.13742.6.3.11.4.1.28 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current The lower critical threshold as a signed integer. The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CcircuitSensorSignedLowerWarningThreshold | 1.3.6.1.4.1.13742.6.3.11.4.1.29 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current The lower warning threshold as a signed integer. The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CcircuitSensorSignedUpperCriticalThreshold | 1.3.6.1.4.1.13742.6.3.11.4.1.30 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current The upper critical threshold as a signed integer. The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CcircuitSensorSignedUpperWarningThreshold | 1.3.6.1.4.1.13742.6.3.11.4.1.31 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current The upper warning threshold as a signed integer. The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| TcircuitPoleSensorConfigurationTable | 1.3.6.1.4.1.13742.6.3.11.6 | NA | |||||||||||||||||||
table · not-accessible · current A list of circuit pole sensor configuration entries. | |||||||||||||||||||||
| RcircuitPoleSensorConfigurationEntry | 1.3.6.1.4.1.13742.6.3.11.6.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing circuit pole sensor configuration objects.
| |||||||||||||||||||||
| CcircuitPoleSensorLogAvailable | 1.3.6.1.4.1.13742.6.3.11.6.1.4 | TruthValue | RW | ||||||||||||||||||
column · TruthValue · read-write · current Is data logging enabled for this sensor? | |||||||||||||||||||||
| CcircuitPoleSensorUnits | 1.3.6.1.4.1.13742.6.3.11.6.1.6 | SensorUnitsEnumeration | RO | ||||||||||||||||||
column · SensorUnitsEnumeration · read-only · current The unit in which the sensor reading is reported. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CcircuitPoleSensorDecimalDigits | 1.3.6.1.4.1.13742.6.3.11.6.1.7 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The number of digits displayed to the right of the decimal point. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CcircuitPoleSensorResolution | 1.3.6.1.4.1.13742.6.3.11.6.1.9 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CcircuitPoleSensorMaximum | 1.3.6.1.4.1.13742.6.3.11.6.1.11 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The largest possible reading as an unsigned integer. The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled maximum exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CcircuitPoleSensorMinimum | 1.3.6.1.4.1.13742.6.3.11.6.1.12 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The smallest possible reading as an unsigned integer. The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CcircuitPoleSensorHysteresis | 1.3.6.1.4.1.13742.6.3.11.6.1.13 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The hysteresis used when crossing a threshold towards the normal state. The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CcircuitPoleSensorStateChangeDelay | 1.3.6.1.4.1.13742.6.3.11.6.1.14 | Unsigned32 (0..300) | RW | ||||||||||||||||||
column · Unsigned32 (0..300) · read-write · current The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the event is reported. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CcircuitPoleSensorLowerCriticalThreshold | 1.3.6.1.4.1.13742.6.3.11.6.1.21 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The lower critical threshold as an unsigned integer. The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CcircuitPoleSensorLowerWarningThreshold | 1.3.6.1.4.1.13742.6.3.11.6.1.22 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The lower warning threshold as an unsigned integer. The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CcircuitPoleSensorUpperCriticalThreshold | 1.3.6.1.4.1.13742.6.3.11.6.1.23 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The upper critical threshold as an unsigned integer. The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CcircuitPoleSensorUpperWarningThreshold | 1.3.6.1.4.1.13742.6.3.11.6.1.24 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CcircuitPoleSensorEnabledThresholds | 1.3.6.1.4.1.13742.6.3.11.6.1.25 | Bits | RW | ||||||||||||||||||
column · Bits · read-write · current A bit string indicating which thresholds are enabled. This parameter does not apply to sensors without numerical reading.
| |||||||||||||||||||||
| CcircuitPoleSensorSignedMaximum | 1.3.6.1.4.1.13742.6.3.11.6.1.26 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The largest possible reading as a signed integer. The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CcircuitPoleSensorSignedMinimum | 1.3.6.1.4.1.13742.6.3.11.6.1.27 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The smallest possible reading as a signed integer. The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigits is 2, then actual value is 0.01. This value determines whether to use the signed or unsigned threshold and value columns: If the minimum is below zero the sensor can have negative readings and the signed columns should be used. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CcircuitPoleSensorSignedLowerCriticalThreshold | 1.3.6.1.4.1.13742.6.3.11.6.1.28 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current The lower critical threshold as a signed integer. The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CcircuitPoleSensorSignedLowerWarningThreshold | 1.3.6.1.4.1.13742.6.3.11.6.1.29 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current The lower warning threshold as a signed integer. The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CcircuitPoleSensorSignedUpperCriticalThreshold | 1.3.6.1.4.1.13742.6.3.11.6.1.30 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current The upper critical threshold as a signed integer. The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CcircuitPoleSensorSignedUpperWarningThreshold | 1.3.6.1.4.1.13742.6.3.11.6.1.31 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current The upper warning threshold as a signed integer. The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| NoutletGroups | 1.3.6.1.4.1.13742.6.3.12 | ||||||||||||||||||||
| ToutletGroupConfigurationTable | 1.3.6.1.4.1.13742.6.3.12.2 | NA | |||||||||||||||||||
table · not-accessible · current A list of outlet group configuration entries. | |||||||||||||||||||||
| RoutletGroupConfigurationEntry | 1.3.6.1.4.1.13742.6.3.12.2.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing configuration objects for outlet groups.
| |||||||||||||||||||||
| CoutletGroupId | 1.3.6.1.4.1.13742.6.3.12.2.1.1 | Integer32 (1..128) | NA | ||||||||||||||||||
column · Integer32 (1..128) · not-accessible · current A unique value for each outlet group. | |||||||||||||||||||||
| CoutletGroupName | 1.3.6.1.4.1.13742.6.3.12.2.1.2 | DisplayString | RW | ||||||||||||||||||
column · DisplayString · read-write · current The user-defined name. | |||||||||||||||||||||
| CoutletGroupCapabilities | 1.3.6.1.4.1.13742.6.3.12.2.1.3 | Bits | RO | ||||||||||||||||||
column · Bits · read-only · current A bit string indicating which sensors are available for the outlet group.
| |||||||||||||||||||||
| CoutletGroupMembers | 1.3.6.1.4.1.13742.6.3.12.2.1.4 | DisplayString | RW | ||||||||||||||||||
column · DisplayString · read-write · current The list of member outlets of this group. String must consist of a comma separated sequence of the outlet identifiers in the format PDUID-OUTLETID. Example: 1-1,1-5,2-2. | |||||||||||||||||||||
| ToutletGroupSensorConfigurationTable | 1.3.6.1.4.1.13742.6.3.12.3 | NA | |||||||||||||||||||
table · not-accessible · current A list of outlet group sensor configuration entries. | |||||||||||||||||||||
| RoutletGroupSensorConfigurationEntry | 1.3.6.1.4.1.13742.6.3.12.3.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing outlet group sensor configuration objects.
| |||||||||||||||||||||
| CoutletGroupSensorLogAvailable | 1.3.6.1.4.1.13742.6.3.12.3.1.4 | TruthValue | RW | ||||||||||||||||||
column · TruthValue · read-write · current Is data logging enabled for this sensor? | |||||||||||||||||||||
| CoutletGroupSensorUnits | 1.3.6.1.4.1.13742.6.3.12.3.1.6 | SensorUnitsEnumeration | RO | ||||||||||||||||||
column · SensorUnitsEnumeration · read-only · current The unit in which the sensor reading is reported. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CoutletGroupSensorDecimalDigits | 1.3.6.1.4.1.13742.6.3.12.3.1.7 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The number of digits displayed to the right of the decimal point. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CoutletGroupSensorResolution | 1.3.6.1.4.1.13742.6.3.12.3.1.9 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CoutletGroupSensorMaximum | 1.3.6.1.4.1.13742.6.3.12.3.1.11 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The largest possible reading as an unsigned integer. The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled maximum exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CoutletGroupSensorMinimum | 1.3.6.1.4.1.13742.6.3.12.3.1.12 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The smallest possible reading as an unsigned integer. The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CoutletGroupSensorHysteresis | 1.3.6.1.4.1.13742.6.3.12.3.1.13 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The hysteresis used when crossing a threshold towards the normal state. The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CoutletGroupSensorStateChangeDelay | 1.3.6.1.4.1.13742.6.3.12.3.1.14 | Unsigned32 (0..300) | RW | ||||||||||||||||||
column · Unsigned32 (0..300) · read-write · current The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the event is reported. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CoutletGroupSensorLowerCriticalThreshold | 1.3.6.1.4.1.13742.6.3.12.3.1.21 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The lower critical threshold as an unsigned integer. The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CoutletGroupSensorLowerWarningThreshold | 1.3.6.1.4.1.13742.6.3.12.3.1.22 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The lower warning threshold as an unsigned integer. The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CoutletGroupSensorUpperCriticalThreshold | 1.3.6.1.4.1.13742.6.3.12.3.1.23 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The upper critical threshold as an unsigned integer. The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CoutletGroupSensorUpperWarningThreshold | 1.3.6.1.4.1.13742.6.3.12.3.1.24 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CoutletGroupSensorEnabledThresholds | 1.3.6.1.4.1.13742.6.3.12.3.1.25 | Bits | RW | ||||||||||||||||||
column · Bits · read-write · current A bit string indicating which thresholds are enabled. This parameter does not apply to sensors without numerical reading.
| |||||||||||||||||||||
| CoutletGroupSensorSignedMaximum | 1.3.6.1.4.1.13742.6.3.12.3.1.26 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The largest possible reading as a signed integer. The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CoutletGroupSensorSignedMinimum | 1.3.6.1.4.1.13742.6.3.12.3.1.27 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The smallest possible reading as a signed integer. The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigits is 2, then actual value is 0.01. This value determines whether to use the signed or unsigned threshold and value columns: If the minimum is below zero the sensor can have negative readings and the signed columns should be used. This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CoutletGroupSensorSignedLowerCriticalThreshold | 1.3.6.1.4.1.13742.6.3.12.3.1.28 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current The lower critical threshold as a signed integer. The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CoutletGroupSensorSignedLowerWarningThreshold | 1.3.6.1.4.1.13742.6.3.12.3.1.29 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current The lower warning threshold as a signed integer. The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CoutletGroupSensorSignedUpperCriticalThreshold | 1.3.6.1.4.1.13742.6.3.12.3.1.30 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current The upper critical threshold as a signed integer. The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| CoutletGroupSensorSignedUpperWarningThreshold | 1.3.6.1.4.1.13742.6.3.12.3.1.31 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current The upper warning threshold as a signed integer. The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading. | |||||||||||||||||||||
| Ncontrol | 1.3.6.1.4.1.13742.6.4 | ||||||||||||||||||||
| NoutletControl | 1.3.6.1.4.1.13742.6.4.1 | ||||||||||||||||||||
| ToutletSwitchControlTable | 1.3.6.1.4.1.13742.6.4.1.2 | NA | |||||||||||||||||||
table · not-accessible · current A list of outlets for a PDU. The number of entries is given by the value of outletCount. | |||||||||||||||||||||
| RoutletSwitchControlEntry | 1.3.6.1.4.1.13742.6.4.1.2.1 | NA | |||||||||||||||||||
| CswitchingOperation | 1.3.6.1.4.1.13742.6.4.1.2.1.2 | OutletSwitchingOperationsEnumeration | RW | ||||||||||||||||||
column · OutletSwitchingOperationsEnumeration · read-write · current The switching operation: switch on, switch off or power-cycle. | |||||||||||||||||||||
| CoutletSwitchingState | 1.3.6.1.4.1.13742.6.4.1.2.1.3 | SensorStateEnumeration | RO | ||||||||||||||||||
column · SensorStateEnumeration · read-only · current The outlet state at present | |||||||||||||||||||||
| CoutletSwitchingTimeStamp | 1.3.6.1.4.1.13742.6.4.1.2.1.4 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The timestamp indicating when the outlet was last switched | |||||||||||||||||||||
| CoutletSuspendedState | 1.3.6.1.4.1.13742.6.4.1.2.1.5 | TruthValue | RO | ||||||||||||||||||
column · TruthValue · read-only · current Whether the outlet is currently off because it was suspected to have caused an OCP trip event | |||||||||||||||||||||
| NexternalSensorControl | 1.3.6.1.4.1.13742.6.4.2 | ||||||||||||||||||||
| TexternalSensorControlTable | 1.3.6.1.4.1.13742.6.4.2.1 | NA | |||||||||||||||||||
table · not-accessible · current A list of control entries for the external sensors. The set of valid indices is defined by the value of externalCount and the externalDeviceCapabilities entry for the selected external. | |||||||||||||||||||||
| RexternalSensorControlEntry | 1.3.6.1.4.1.13742.6.4.2.1.1 | NA | |||||||||||||||||||
| CexternalSensorResetMinMax | 1.3.6.1.4.1.13742.6.4.2.1.1.2 | TruthValue | RW | ||||||||||||||||||
column · TruthValue · read-write · current Writing True to this variable resets minimum / maximum values and their timestamps. | |||||||||||||||||||||
| NtransferSwitchControl | 1.3.6.1.4.1.13742.6.4.3 | ||||||||||||||||||||
| TtransferSwitchControlTable | 1.3.6.1.4.1.13742.6.4.3.1 | NA | |||||||||||||||||||
table · not-accessible · current A list of transfer switches for a PDU. The number of entries is given by the value of transferSwitchCount. | |||||||||||||||||||||
| RtransferSwitchControlEntry | 1.3.6.1.4.1.13742.6.4.3.1.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry for implementing switching operations on a transfer switch.
| |||||||||||||||||||||
| CtransferSwitchActiveInlet | 1.3.6.1.4.1.13742.6.4.3.1.1.1 | Integer32 (0..64) | RO | ||||||||||||||||||
column · Integer32 (0..64) · read-only · current The index of the currently active inlet. The value normally ranges between 1 and the value of inletCount, but can be 0 in case no inlet is active (e.g. overload alarm). | |||||||||||||||||||||
| CtransferSwitchTransferToInlet | 1.3.6.1.4.1.13742.6.4.3.1.1.2 | Integer32 (0..64) | RW | ||||||||||||||||||
column · Integer32 (0..64) · read-write · current Select the active inlet. The written value must be between 1 and the value of inletCount. If the selected inlet is available it will become both active and preferred, otherwise an inconsistentValue error will be returned. By default the switching operation will fail if the phase difference between the inlets is too large. In this case the switch can be forced by writing transferSwitchAlarmOverride as True in the same request. This variable will always read as 0. | |||||||||||||||||||||
| CtransferSwitchAlarmOverride | 1.3.6.1.4.1.13742.6.4.3.1.1.3 | TruthValue | RW | ||||||||||||||||||
column · TruthValue · read-write · current Force transfer even if the phase difference between the inlets is too large. This may only be written together with transferSwitchTransferToInlet, otherwise an inconsistentValue error will be returned. Always reads as false. | |||||||||||||||||||||
| CtransferSwitchLastTransferReason | 1.3.6.1.4.1.13742.6.4.3.1.1.4 | TransferSwitchTransferReasonEnumeration | RO | ||||||||||||||||||
column · TransferSwitchTransferReasonEnumeration · read-only · current The reason for the most recent transfer | |||||||||||||||||||||
| NactuatorControl | 1.3.6.1.4.1.13742.6.4.4 | ||||||||||||||||||||
| TactuatorControlTable | 1.3.6.1.4.1.13742.6.4.4.2 | NA | |||||||||||||||||||
table · not-accessible · current A list of actuators for a PDU. | |||||||||||||||||||||
| RactuatorControlEntry | 1.3.6.1.4.1.13742.6.4.4.2.1 | NA | |||||||||||||||||||
| CactuatorState | 1.3.6.1.4.1.13742.6.4.4.2.1.2 | SensorStateEnumeration | RW | ||||||||||||||||||
column · SensorStateEnumeration · read-write · current The actuator state. A get operation retrieves the state of the actuator. A set operation changes the state of the sensor. The valid states depend on the actuator type. See the comment for SensorStateEnumeration. Attempting to set the state to any other value will generate an error. | |||||||||||||||||||||
| NrcmControl | 1.3.6.1.4.1.13742.6.4.5 | ||||||||||||||||||||
| TrcmSelfTestTable | 1.3.6.1.4.1.13742.6.4.5.2 | NA | |||||||||||||||||||
table · not-accessible · current A list of inlet RCMs. | |||||||||||||||||||||
| RrcmSelfTestEntry | 1.3.6.1.4.1.13742.6.4.5.2.1 | NA | |||||||||||||||||||
| CrcmState | 1.3.6.1.4.1.13742.6.4.5.2.1.2 | SensorStateEnumeration | RW | ||||||||||||||||||
column · SensorStateEnumeration · read-write · current The rcm state. A Get operation retrieves the state of the RCM State Sensor. A Set operation changes the state of the sensor. The only valid state for set operations is selfTest(29). When rcmState is set to selfTest, self test of the RCM starts. Attempting to set the state to any other value will generate an error. If the current state is selfTest, then an attempt to set the value to selfTest will be ignored. | |||||||||||||||||||||
| ToverCurrentProtectorRcmSelfTestTable | 1.3.6.1.4.1.13742.6.4.5.3 | NA | |||||||||||||||||||
table · not-accessible · current A list of overcurrent protector RCMs. | |||||||||||||||||||||
| RoverCurrentProtectorRcmSelfTestEntry | 1.3.6.1.4.1.13742.6.4.5.3.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry for initiating the self test of an overcurrent protector RCM. | |||||||||||||||||||||
| CoverCurrentProtectorRcmState | 1.3.6.1.4.1.13742.6.4.5.3.1.2 | SensorStateEnumeration | RW | ||||||||||||||||||
column · SensorStateEnumeration · read-write · current The rcm state. A Get operation retrieves the state of the RCM State Sensor. A Set operation changes the state of the sensor. The only valid state for set operations is selfTest(29). When rcmState is set to selfTest, self test of the RCM starts. Attempting to set the state to any other value will generate an error. If the current state is selfTest, then an attempt to set the value to selfTest will be ignored. | |||||||||||||||||||||
| NinletSensorControl | 1.3.6.1.4.1.13742.6.4.6 | ||||||||||||||||||||
| TinletSensorControlTable | 1.3.6.1.4.1.13742.6.4.6.1 | NA | |||||||||||||||||||
table · not-accessible · current A list of control entries for the inlet sensors. The set of valid indices is defined by the value of inletCount and the inletDeviceCapabilities entry for the selected inlet. | |||||||||||||||||||||
| RinletSensorControlEntry | 1.3.6.1.4.1.13742.6.4.6.1.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry used for controlling an inlet sensor.
| |||||||||||||||||||||
| CinletSensorResetValue | 1.3.6.1.4.1.13742.6.4.6.1.1.1 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current Writing to this variable sets a new value for the addressed sensor. Only accumulating sensors (e.g. energy counters) can be reset, and currently the only supported value is 0. Writing any other value returns an error. This variable will always read as 0. | |||||||||||||||||||||
| CinletSensorResetMinMax | 1.3.6.1.4.1.13742.6.4.6.1.1.2 | TruthValue | RW | ||||||||||||||||||
column · TruthValue · read-write · current Writing True to this variable resets minimum / maximum values and their timestamps. | |||||||||||||||||||||
| TinletPoleSensorControlTable | 1.3.6.1.4.1.13742.6.4.6.2 | NA | |||||||||||||||||||
table · not-accessible · current A list of control entries for the inlet pole sensors. The set of valid indices is defined by the value of inletPoleCount and the inletPoleDeviceCapabilities entry for the selected inlet pole. | |||||||||||||||||||||
| RinletPoleSensorControlEntry | 1.3.6.1.4.1.13742.6.4.6.2.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry used for controlling an inlet pole sensor.
| |||||||||||||||||||||
| CinletPoleSensorResetMinMax | 1.3.6.1.4.1.13742.6.4.6.2.1.2 | TruthValue | RW | ||||||||||||||||||
column · TruthValue · read-write · current Writing True to this variable resets minimum / maximum values and their timestamps. | |||||||||||||||||||||
| TinletLinePairSensorControlTable | 1.3.6.1.4.1.13742.6.4.6.3 | NA | |||||||||||||||||||
table · not-accessible · current A list of control entries for the inlet line pair sensors. The set of valid indices is defined by the value of inletLinePairCount and the inletLinePairDeviceCapabilities entry for the selected inlet line pair. | |||||||||||||||||||||
| RinletLinePairSensorControlEntry | 1.3.6.1.4.1.13742.6.4.6.3.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry used for controlling an inlet line pair sensor.
| |||||||||||||||||||||
| CinletLinePairSensorResetMinMax | 1.3.6.1.4.1.13742.6.4.6.3.1.2 | TruthValue | RW | ||||||||||||||||||
column · TruthValue · read-write · current Writing True to this variable resets minimum / maximum values and their timestamps. | |||||||||||||||||||||
| NoutletSensorControl | 1.3.6.1.4.1.13742.6.4.7 | ||||||||||||||||||||
| ToutletSensorControlTable | 1.3.6.1.4.1.13742.6.4.7.1 | NA | |||||||||||||||||||
table · not-accessible · current A list of control entries for the outlet sensors. The set of valid indices is defined by the value of outletCount and the outletDeviceCapabilities entry for the selected outlet. | |||||||||||||||||||||
| RoutletSensorControlEntry | 1.3.6.1.4.1.13742.6.4.7.1.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry used for controlling an outlet sensor.
| |||||||||||||||||||||
| CoutletSensorResetValue | 1.3.6.1.4.1.13742.6.4.7.1.1.1 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current Writing to this variable sets a new value for the addressed sensor. Only accumulating sensors (e.g. energy counters) can be reset, and currently the only supported value is 0. Writing any other value returns an error. This variable will always read as 0. | |||||||||||||||||||||
| CoutletSensorResetMinMax | 1.3.6.1.4.1.13742.6.4.7.1.1.2 | TruthValue | RW | ||||||||||||||||||
column · TruthValue · read-write · current Writing True to this variable resets minimum / maximum values and their timestamps. | |||||||||||||||||||||
| ToutletPoleSensorControlTable | 1.3.6.1.4.1.13742.6.4.7.2 | NA | |||||||||||||||||||
table · not-accessible · current A list of control entries for the outlet pole sensors. The set of valid indices is defined by the value of outletPoleCount and the outletPoleDeviceCapabilities entry for the selected outlet pole. | |||||||||||||||||||||
| RoutletPoleSensorControlEntry | 1.3.6.1.4.1.13742.6.4.7.2.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry used for controlling an outlet pole sensor.
| |||||||||||||||||||||
| CoutletPoleSensorResetMinMax | 1.3.6.1.4.1.13742.6.4.7.2.1.2 | TruthValue | RW | ||||||||||||||||||
column · TruthValue · read-write · current Writing True to this variable resets minimum / maximum values and their timestamps. | |||||||||||||||||||||
| NunitSensorControl | 1.3.6.1.4.1.13742.6.4.8 | ||||||||||||||||||||
| TunitSensorControlTable | 1.3.6.1.4.1.13742.6.4.8.1 | NA | |||||||||||||||||||
table · not-accessible · current A list of control entries for the unit sensors. The set of valid indices is defined by the value of unitCount and the unitDeviceCapabilities entry for the selected unit. | |||||||||||||||||||||
| RunitSensorControlEntry | 1.3.6.1.4.1.13742.6.4.8.1.1 | NA | |||||||||||||||||||
| CunitSensorResetValue | 1.3.6.1.4.1.13742.6.4.8.1.1.1 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current Writing to this variable sets a new value for the addressed sensor. Only accumulating sensors (e.g. energy counters) can be reset, and currently the only supported value is 0. Writing any other value returns an error. This variable will always read as 0. This object applies only to multi-inlet PDUs. | |||||||||||||||||||||
| CunitSensorResetMinMax | 1.3.6.1.4.1.13742.6.4.8.1.1.2 | TruthValue | RW | ||||||||||||||||||
column · TruthValue · read-write · current Writing True to this variable resets minimum / maximum values and their timestamps. | |||||||||||||||||||||
| NcircuitSensorControl | 1.3.6.1.4.1.13742.6.4.9 | ||||||||||||||||||||
| TcircuitSensorControlTable | 1.3.6.1.4.1.13742.6.4.9.1 | NA | |||||||||||||||||||
table · not-accessible · current A list of control entries for the circuit sensors. The set of valid indices is defined by the value of circuitCount | |||||||||||||||||||||
| RcircuitSensorControlEntry | 1.3.6.1.4.1.13742.6.4.9.1.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry used for controlling an circuit sensor.
| |||||||||||||||||||||
| CcircuitSensorResetValue | 1.3.6.1.4.1.13742.6.4.9.1.1.1 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current Writing to this variable sets a new value for the addressed sensor. Only accumulating sensors (e.g. energy counters) can be reset, and currently the only supported value is 0. Writing any other value returns an error. This variable will always read as 0. | |||||||||||||||||||||
| CcircuitSensorResetMinMax | 1.3.6.1.4.1.13742.6.4.9.1.1.2 | TruthValue | RW | ||||||||||||||||||
column · TruthValue · read-write · current Writing True to this variable resets minimum / maximum values and their timestamps. | |||||||||||||||||||||
| TcircuitPoleSensorControlTable | 1.3.6.1.4.1.13742.6.4.9.2 | NA | |||||||||||||||||||
table · not-accessible · current A list of control entries for the circuit pole sensors. The set of valid indices is defined by the value of circuitPoleCount and the circuitPoleDeviceCapabilities entry for the selected circuit pole. | |||||||||||||||||||||
| RcircuitPoleSensorControlEntry | 1.3.6.1.4.1.13742.6.4.9.2.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry used for controlling an circuit pole sensor.
| |||||||||||||||||||||
| CcircuitPoleSensorResetMinMax | 1.3.6.1.4.1.13742.6.4.9.2.1.2 | TruthValue | RW | ||||||||||||||||||
column · TruthValue · read-write · current Writing True to this variable resets minimum / maximum values and their timestamps. | |||||||||||||||||||||
| NoutletGroupControl | 1.3.6.1.4.1.13742.6.4.10 | ||||||||||||||||||||
| ToutletGroupSwitchControlTable | 1.3.6.1.4.1.13742.6.4.10.2 | NA | |||||||||||||||||||
table · not-accessible · current A list of outlet groups. The number of entries is given by the value of outletGroupCount. | |||||||||||||||||||||
| RoutletGroupSwitchControlEntry | 1.3.6.1.4.1.13742.6.4.10.2.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry for implementing switching operations on an outlet group.
| |||||||||||||||||||||
| CoutletGroupSwitchingOperation | 1.3.6.1.4.1.13742.6.4.10.2.1.2 | OutletSwitchingOperationsEnumeration | RW | ||||||||||||||||||
column · OutletSwitchingOperationsEnumeration · read-write · current The switching operation: switch on, switch off or power-cycle. | |||||||||||||||||||||
| NoutletGroupSensorControl | 1.3.6.1.4.1.13742.6.4.11 | ||||||||||||||||||||
| ToutletGroupSensorControlTable | 1.3.6.1.4.1.13742.6.4.11.1 | NA | |||||||||||||||||||
table · not-accessible · current A list of control entries for the outlet group sensors. The set of valid indices is defined by the value of outletGroupCount and the outletGroupDeviceCapabilities entry for the selected outlet group. | |||||||||||||||||||||
| RoutletGroupSensorControlEntry | 1.3.6.1.4.1.13742.6.4.11.1.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry used for controlling an outlet group sensor.
| |||||||||||||||||||||
| CoutletGroupSensorResetValue | 1.3.6.1.4.1.13742.6.4.11.1.1.1 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current Writing to this variable sets a new value for the addressed sensor. Only accumulating sensors (e.g. energy counters) can be reset, and currently the only supported value is 0. Writing any other value returns an error. This variable will always read as 0. | |||||||||||||||||||||
| CoutletGroupSensorResetMinMax | 1.3.6.1.4.1.13742.6.4.11.1.1.2 | TruthValue | RW | ||||||||||||||||||
column · TruthValue · read-write · current Writing True to this variable resets minimum / maximum values and their timestamps. | |||||||||||||||||||||
| NserverPowerControl | 1.3.6.1.4.1.13742.6.4.12 | ||||||||||||||||||||
| TserverPowerControlTable | 1.3.6.1.4.1.13742.6.4.12.1 | NA | |||||||||||||||||||
table · not-accessible · current A list of server entries. The number of entries is given by the value of serverCount for the PDU. | |||||||||||||||||||||
| RserverPowerControlEntry | 1.3.6.1.4.1.13742.6.4.12.1.1 | NA | |||||||||||||||||||
| CserverPowerControlOperation | 1.3.6.1.4.1.13742.6.4.12.1.1.1 | ServerPowerStateEnumeration | RW | ||||||||||||||||||
column · ServerPowerStateEnumeration · read-write · current Reading the variable returns the current power state of the server. Writing on(1) or off(2) results in a power control operation, switching the configured power target on or initiating a graceful shutdown. Writing any other value results in an error. | |||||||||||||||||||||
| NoverCurrentProtectorSensorControl | 1.3.6.1.4.1.13742.6.4.13 | ||||||||||||||||||||
| ToverCurrentProtectorSensorControlTable | 1.3.6.1.4.1.13742.6.4.13.1 | NA | |||||||||||||||||||
table · not-accessible · current A list of control entries for the over current protector sensors. The set of valid indices is defined by the value of overCurrentProtectorCount and the overCurrentProtectorDeviceCapabilities entry for the selected over current protector. | |||||||||||||||||||||
| RoverCurrentProtectorSensorControlEntry | 1.3.6.1.4.1.13742.6.4.13.1.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry used for controlling an over current protector sensor. | |||||||||||||||||||||
| CoverCurrentProtectorSensorResetMinMax | 1.3.6.1.4.1.13742.6.4.13.1.1.2 | TruthValue | RW | ||||||||||||||||||
column · TruthValue · read-write · current Writing True to this variable resets minimum / maximum values and their timestamps. | |||||||||||||||||||||
| NtransferSwitchSensorControl | 1.3.6.1.4.1.13742.6.4.14 | ||||||||||||||||||||
| TtransferSwitchSensorControlTable | 1.3.6.1.4.1.13742.6.4.14.1 | NA | |||||||||||||||||||
table · not-accessible · current A list of control entries for the transfer switch sensors. The set of valid indices is defined by the value of transferSwitchCount and the transferSwitchDeviceCapabilities entry for the selected transfer switch. | |||||||||||||||||||||
| RtransferSwitchSensorControlEntry | 1.3.6.1.4.1.13742.6.4.14.1.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry used for controlling an transfer switch sensor.
| |||||||||||||||||||||
| CtransferSwitchSensorResetMinMax | 1.3.6.1.4.1.13742.6.4.14.1.1.2 | TruthValue | RW | ||||||||||||||||||
column · TruthValue · read-write · current Writing True to this variable resets minimum / maximum values and their timestamps. | |||||||||||||||||||||
| Nmeasurements | 1.3.6.1.4.1.13742.6.5 | ||||||||||||||||||||
| NmeasurementsUnit | 1.3.6.1.4.1.13742.6.5.1 | ||||||||||||||||||||
| TunitSensorMeasurementsTable | 1.3.6.1.4.1.13742.6.5.1.3 | NA | |||||||||||||||||||
table · not-accessible · current A list of unit sensor entries. | |||||||||||||||||||||
| RunitSensorMeasurementsEntry | 1.3.6.1.4.1.13742.6.5.1.3.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing unit sensor measurement objects.
| |||||||||||||||||||||
| CmeasurementsUnitSensorIsAvailable | 1.3.6.1.4.1.13742.6.5.1.3.1.2 | TruthValue | RO | ||||||||||||||||||
column · TruthValue · read-only · current The sensor is present. | |||||||||||||||||||||
| CmeasurementsUnitSensorState | 1.3.6.1.4.1.13742.6.5.1.3.1.3 | SensorStateEnumeration | RO | ||||||||||||||||||
column · SensorStateEnumeration · read-only · current The sensor state. | |||||||||||||||||||||
| CmeasurementsUnitSensorValue | 1.3.6.1.4.1.13742.6.5.1.3.1.4 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The sensor reading as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsUnitSensorTimeStamp | 1.3.6.1.4.1.13742.6.5.1.3.1.5 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The timestamp for reading. | |||||||||||||||||||||
| CmeasurementsUnitSensorSignedValue | 1.3.6.1.4.1.13742.6.5.1.3.1.6 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The sensor reading as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsUnitSensorMinMaxValid | 1.3.6.1.4.1.13742.6.5.1.3.1.7 | TruthValue | RO | ||||||||||||||||||
column · TruthValue · read-only · current The minimum and maximum values of sensor reading and their timestamps
provided as measurementsUnitSensor[Signed]{Min|Max}{Value|TimeStamp} are valid | |||||||||||||||||||||
| CmeasurementsUnitSensorMinValue | 1.3.6.1.4.1.13742.6.5.1.3.1.8 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The minimum value of sensor reading since last reset as an unsigned integer The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsUnitSensorSignedMinValue | 1.3.6.1.4.1.13742.6.5.1.3.1.9 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The minimum value of sensor reading since last reset as a signed integer The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsUnitSensorMinTimeStamp | 1.3.6.1.4.1.13742.6.5.1.3.1.10 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The timestamp of last change of the minimum value of sensor reading provided as measurementUnitSensor[Signed]MinValue | |||||||||||||||||||||
| CmeasurementsUnitSensorMaxValue | 1.3.6.1.4.1.13742.6.5.1.3.1.11 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The maximum value of sensor reading since last reset as an unsigned integer The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsUnitSensorSignedMaxValue | 1.3.6.1.4.1.13742.6.5.1.3.1.12 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The maximum value of sensor reading since last reset as a signed integer The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsUnitSensorMaxTimeStamp | 1.3.6.1.4.1.13742.6.5.1.3.1.13 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The timestamp of last change of the maximum value of sensor reading provided as measurementUnitSensor[Signed]MaxValue | |||||||||||||||||||||
| CmeasurementsUnitSensorMinMaxResetTimeStamp | 1.3.6.1.4.1.13742.6.5.1.3.1.14 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The timestamp of last reset of all minimum and maximum values of sensor reading
including their timestamps, provided as measurementsUnitSensor[Signed]{Min|Max}{Value|TimeStamp}
and measurementsUnitSensorMinMaxValid. The measurementsUnitSensorMinMaxResetTimeStamp is
always valid, even if measurementsUnitSensorMinMaxValid is false. | |||||||||||||||||||||
| CmeasurementsUnitSensorResetTimeStamp | 1.3.6.1.4.1.13742.6.5.1.3.1.15 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The timestamp indicating when the sensor value was last reset. If the sensor never was reset this will read 0. Only for accumulating sensors. | |||||||||||||||||||||
| NmeasurementsInlet | 1.3.6.1.4.1.13742.6.5.2 | ||||||||||||||||||||
| TinletSensorMeasurementsTable | 1.3.6.1.4.1.13742.6.5.2.3 | NA | |||||||||||||||||||
table · not-accessible · current A list of inlet sensor entries. | |||||||||||||||||||||
| RinletSensorMeasurementsEntry | 1.3.6.1.4.1.13742.6.5.2.3.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing inlet sensor measurement objects.
| |||||||||||||||||||||
| CmeasurementsInletSensorIsAvailable | 1.3.6.1.4.1.13742.6.5.2.3.1.2 | TruthValue | RO | 1 | |||||||||||||||||
column · TruthValue · read-only · current The sensor is present. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmeasurementsInletSensorState | 1.3.6.1.4.1.13742.6.5.2.3.1.3 | SensorStateEnumeration | RO | 4 | |||||||||||||||||
column · SensorStateEnumeration · read-only · current The sensor state. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmeasurementsInletSensorValue | 1.3.6.1.4.1.13742.6.5.2.3.1.4 | Unsigned32 | RO | 3497 | |||||||||||||||||
column · Unsigned32 · read-only · current The sensor reading as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmeasurementsInletSensorTimeStamp | 1.3.6.1.4.1.13742.6.5.2.3.1.5 | Unsigned32 | RO | 1747869708 | |||||||||||||||||
column · Unsigned32 · read-only · current The timestamp for reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmeasurementsInletSensorSignedValue | 1.3.6.1.4.1.13742.6.5.2.3.1.6 | Integer32 | RO | 7661 | |||||||||||||||||
column · Integer32 · read-only · current The sensor reading as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmeasurementsInletSensorMinMaxValid | 1.3.6.1.4.1.13742.6.5.2.3.1.7 | TruthValue | RO | 1 | |||||||||||||||||
column · TruthValue · read-only · current The minimum and maximum values of sensor reading and their timestamps
provided as measurementsInletSensor[Signed]{Min|Max}{Value|TimeStamp} are validExample values from LibreNMS test devices
| |||||||||||||||||||||
| CmeasurementsInletSensorMinValue | 1.3.6.1.4.1.13742.6.5.2.3.1.8 | Unsigned32 | RO | 5375 | |||||||||||||||||
column · Unsigned32 · read-only · current The minimum value of sensor reading since last reset as an unsigned integer The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmeasurementsInletSensorSignedMinValue | 1.3.6.1.4.1.13742.6.5.2.3.1.9 | Integer32 | RO | 5375 | |||||||||||||||||
column · Integer32 · read-only · current The minimum value of sensor reading since last reset as a signed integer The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmeasurementsInletSensorMinTimeStamp | 1.3.6.1.4.1.13742.6.5.2.3.1.10 | Unsigned32 | RO | 1742436705 | |||||||||||||||||
column · Unsigned32 · read-only · current The timestamp of last change of the minimum value of sensor reading provided as measurementInletSensor[Signed]MinValue Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmeasurementsInletSensorMaxValue | 1.3.6.1.4.1.13742.6.5.2.3.1.11 | Unsigned32 | RO | 10173 | |||||||||||||||||
column · Unsigned32 · read-only · current The maximum value of sensor reading since last reset as an unsigned integer The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmeasurementsInletSensorSignedMaxValue | 1.3.6.1.4.1.13742.6.5.2.3.1.12 | Integer32 | RO | 10173 | |||||||||||||||||
column · Integer32 · read-only · current The maximum value of sensor reading since last reset as a signed integer The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmeasurementsInletSensorMaxTimeStamp | 1.3.6.1.4.1.13742.6.5.2.3.1.13 | Unsigned32 | RO | 1737622836 | |||||||||||||||||
column · Unsigned32 · read-only · current The timestamp of last change of the maximum value of sensor reading provided as measurementInletSensor[Signed]MaxValue Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmeasurementsInletSensorMinMaxResetTimeStamp | 1.3.6.1.4.1.13742.6.5.2.3.1.14 | Unsigned32 | RO | 1709629970 | |||||||||||||||||
column · Unsigned32 · read-only · current The timestamp of last reset of all minimum and maximum values of sensor reading
including their timestamps, provided as measurementsInletSensor[Signed]{Min|Max}{Value|TimeStamp}
and measurementsInletSensorMinMaxValid. The measurementsInletSensorMinMaxResetTimeStamp is
always valid, even if measurementsInletSensorMinMaxValid is false.Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmeasurementsInletSensorResetTimeStamp | 1.3.6.1.4.1.13742.6.5.2.3.1.15 | Unsigned32 | RO | 1756889790 | |||||||||||||||||
column · Unsigned32 · read-only · current The timestamp indicating when the sensor value was last reset. If the sensor never was reset this will read 0. Only for accumulating sensors. Example values from LibreNMS test devices
| |||||||||||||||||||||
| TinletPoleSensorMeasurementsTable | 1.3.6.1.4.1.13742.6.5.2.4 | NA | |||||||||||||||||||
table · not-accessible · current A list of inlet pole sensor entries. | |||||||||||||||||||||
| RinletPoleSensorMeasurementsEntry | 1.3.6.1.4.1.13742.6.5.2.4.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing inlet pole sensor measurement objects.
| |||||||||||||||||||||
| CmeasurementsInletPoleSensorIsAvailable | 1.3.6.1.4.1.13742.6.5.2.4.1.2 | TruthValue | RO | ||||||||||||||||||
column · TruthValue · read-only · current The sensor is present. | |||||||||||||||||||||
| CmeasurementsInletPoleSensorState | 1.3.6.1.4.1.13742.6.5.2.4.1.3 | SensorStateEnumeration | RO | ||||||||||||||||||
column · SensorStateEnumeration · read-only · current The sensor state. | |||||||||||||||||||||
| CmeasurementsInletPoleSensorValue | 1.3.6.1.4.1.13742.6.5.2.4.1.4 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The sensor reading as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsInletPoleSensorTimeStamp | 1.3.6.1.4.1.13742.6.5.2.4.1.5 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The timestamp for reading. | |||||||||||||||||||||
| CmeasurementsInletPoleSensorSignedValue | 1.3.6.1.4.1.13742.6.5.2.4.1.6 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The sensor reading as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsInletPoleSensorMinMaxValid | 1.3.6.1.4.1.13742.6.5.2.4.1.7 | TruthValue | RO | ||||||||||||||||||
column · TruthValue · read-only · current The minimum and maximum values of sensor reading and their timestamps
provided as measurementsInletPoleSensor[Signed]{Min|Max}{Value|TimeStamp} are valid | |||||||||||||||||||||
| CmeasurementsInletPoleSensorMinValue | 1.3.6.1.4.1.13742.6.5.2.4.1.8 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The minimum value of sensor reading since last reset as an unsigned integer The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsInletPoleSensorSignedMinValue | 1.3.6.1.4.1.13742.6.5.2.4.1.9 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The minimum value of sensor reading since last reset as a signed integer The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsInletPoleSensorMinTimeStamp | 1.3.6.1.4.1.13742.6.5.2.4.1.10 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The timestamp of last change of the minimum value of sensor reading provided as measurementInletPoleSensor[Signed]MinValue | |||||||||||||||||||||
| CmeasurementsInletPoleSensorMaxValue | 1.3.6.1.4.1.13742.6.5.2.4.1.11 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The maximum value of sensor reading since last reset as an unsigned integer The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsInletPoleSensorSignedMaxValue | 1.3.6.1.4.1.13742.6.5.2.4.1.12 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The maximum value of sensor reading since last reset as a signed integer The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsInletPoleSensorMaxTimeStamp | 1.3.6.1.4.1.13742.6.5.2.4.1.13 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The timestamp of last change of the maximum value of sensor reading provided as measurementInletPoleSensor[Signed]MaxValue | |||||||||||||||||||||
| CmeasurementsInletPoleSensorMinMaxResetTimeStamp | 1.3.6.1.4.1.13742.6.5.2.4.1.14 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The timestamp of last reset of all minimum and maximum values of sensor reading
including their timestamps, provided as measurementsInletPoleSensor[Signed]{Min|Max}{Value|TimeStamp}
and measurementsInletPoleSensorMinMaxValid. The measurementsInletPoleSensorMinMaxResetTimeStamp is
always valid, even if measurementsInletPoleSensorMinMaxValid is false. | |||||||||||||||||||||
| TinletLinePairSensorMeasurementsTable | 1.3.6.1.4.1.13742.6.5.2.5 | NA | |||||||||||||||||||
table · not-accessible · current A list of inlet line pair sensor entries. | |||||||||||||||||||||
| RinletLinePairSensorMeasurementsEntry | 1.3.6.1.4.1.13742.6.5.2.5.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing inlet line pair sensor measurement objects.
| |||||||||||||||||||||
| CmeasurementsInletLinePairSensorIsAvailable | 1.3.6.1.4.1.13742.6.5.2.5.1.2 | TruthValue | RO | ||||||||||||||||||
column · TruthValue · read-only · current The sensor is present. | |||||||||||||||||||||
| CmeasurementsInletLinePairSensorState | 1.3.6.1.4.1.13742.6.5.2.5.1.3 | SensorStateEnumeration | RO | ||||||||||||||||||
column · SensorStateEnumeration · read-only · current The sensor state. | |||||||||||||||||||||
| CmeasurementsInletLinePairSensorValue | 1.3.6.1.4.1.13742.6.5.2.5.1.4 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The sensor reading as an unsigned integer. The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsInletLinePairSensorTimeStamp | 1.3.6.1.4.1.13742.6.5.2.5.1.5 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The timestamp for reading. | |||||||||||||||||||||
| CmeasurementsInletLinePairSensorSignedValue | 1.3.6.1.4.1.13742.6.5.2.5.1.6 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The sensor reading as a signed integer. The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsInletLinePairSensorMinMaxValid | 1.3.6.1.4.1.13742.6.5.2.5.1.7 | TruthValue | RO | ||||||||||||||||||
column · TruthValue · read-only · current The minimum and maximum values of sensor reading and their timestamps
provided as measurementsInletLinePairSensor[Signed]{Min|Max}{Value|TimeStamp} are valid | |||||||||||||||||||||
| CmeasurementsInletLinePairSensorMinValue | 1.3.6.1.4.1.13742.6.5.2.5.1.8 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The minimum value of sensor reading since last reset as an unsigned integer The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsInletLinePairSensorSignedMinValue | 1.3.6.1.4.1.13742.6.5.2.5.1.9 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The minimum value of sensor reading since last reset as a signed integer The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsInletLinePairSensorMinTimeStamp | 1.3.6.1.4.1.13742.6.5.2.5.1.10 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The timestamp of last change of the minimum value of sensor reading provided as measurementInletLinePairSensor[Signed]MinValue | |||||||||||||||||||||
| CmeasurementsInletLinePairSensorMaxValue | 1.3.6.1.4.1.13742.6.5.2.5.1.11 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The maximum value of sensor reading since last reset as an unsigned integer The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsInletLinePairSensorSignedMaxValue | 1.3.6.1.4.1.13742.6.5.2.5.1.12 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The maximum value of sensor reading since last reset as a signed integer The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsInletLinePairSensorMaxTimeStamp | 1.3.6.1.4.1.13742.6.5.2.5.1.13 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The timestamp of last change of the maximum value of sensor reading provided as measurementInletLinePairSensor[Signed]MaxValue | |||||||||||||||||||||
| CmeasurementsInletLinePairSensorMinMaxResetTimeStamp | 1.3.6.1.4.1.13742.6.5.2.5.1.14 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The timestamp of last reset of all minimum and maximum values of sensor reading
including their timestamps, provided as measurementsInletLinePairSensor[Signed]{Min|Max}{Value|TimeStamp}
and measurementsInletLinePairSensorMinMaxValid. The measurementsInletLinePairSensorMinMaxResetTimeStamp is
always valid, even if measurementsInletLinePairSensorMinMaxValid is false. | |||||||||||||||||||||
| NmeasurementsOverCurrentProtector | 1.3.6.1.4.1.13742.6.5.3 | ||||||||||||||||||||
| ToverCurrentProtectorSensorMeasurementsTable | 1.3.6.1.4.1.13742.6.5.3.3 | NA | |||||||||||||||||||
table · not-accessible · current A list of over current protector sensor entries. | |||||||||||||||||||||
| RoverCurrentProtectorSensorMeasurementsEntry | 1.3.6.1.4.1.13742.6.5.3.3.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing over current protector sensor measurement objects. | |||||||||||||||||||||
| CmeasurementsOverCurrentProtectorSensorIsAvailable | 1.3.6.1.4.1.13742.6.5.3.3.1.2 | TruthValue | RO | 1 | |||||||||||||||||
column · TruthValue · read-only · current The sensor is present. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmeasurementsOverCurrentProtectorSensorState | 1.3.6.1.4.1.13742.6.5.3.3.1.3 | SensorStateEnumeration | RO | 4 | |||||||||||||||||
column · SensorStateEnumeration · read-only · current The sensor state. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmeasurementsOverCurrentProtectorSensorValue | 1.3.6.1.4.1.13742.6.5.3.3.1.4 | Unsigned32 | RO | 485 | |||||||||||||||||
column · Unsigned32 · read-only · current The sensor reading as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmeasurementsOverCurrentProtectorSensorTimeStamp | 1.3.6.1.4.1.13742.6.5.3.3.1.5 | Unsigned32 | RO | 1756989553 | |||||||||||||||||
column · Unsigned32 · read-only · current The timestamp for reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmeasurementsOverCurrentProtectorSensorSignedValue | 1.3.6.1.4.1.13742.6.5.3.3.1.6 | Integer32 | RO | 485 | |||||||||||||||||
column · Integer32 · read-only · current The sensor reading as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmeasurementsOverCurrentProtectorSensorMinMaxValid | 1.3.6.1.4.1.13742.6.5.3.3.1.7 | TruthValue | RO | 1 | |||||||||||||||||
column · TruthValue · read-only · current The minimum and maximum values of sensor reading and their timestamps
provided as measurementsOverCurrentProtectorSensor[Signed]{Min|Max}{Value|TimeStamp} are validExample values from LibreNMS test devices
| |||||||||||||||||||||
| CmeasurementsOverCurrentProtectorSensorMinValue | 1.3.6.1.4.1.13742.6.5.3.3.1.8 | Unsigned32 | RO | 478 | |||||||||||||||||
column · Unsigned32 · read-only · current The minimum value of sensor reading since last reset as an unsigned integer The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmeasurementsOverCurrentProtectorSensorSignedMinValue | 1.3.6.1.4.1.13742.6.5.3.3.1.9 | Integer32 | RO | 478 | |||||||||||||||||
column · Integer32 · read-only · current The minimum value of sensor reading since last reset as a signed integer The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmeasurementsOverCurrentProtectorSensorMinTimeStamp | 1.3.6.1.4.1.13742.6.5.3.3.1.10 | Unsigned32 | RO | 1756813887 | |||||||||||||||||
column · Unsigned32 · read-only · current The timestamp of last change of the minimum value of sensor reading provided as measurementOverCurrentProtectorSensor[Signed]MinValue Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmeasurementsOverCurrentProtectorSensorMaxValue | 1.3.6.1.4.1.13742.6.5.3.3.1.11 | Unsigned32 | RO | 492 | |||||||||||||||||
column · Unsigned32 · read-only · current The maximum value of sensor reading since last reset as an unsigned integer The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmeasurementsOverCurrentProtectorSensorSignedMaxValue | 1.3.6.1.4.1.13742.6.5.3.3.1.12 | Integer32 | RO | 492 | |||||||||||||||||
column · Integer32 · read-only · current The maximum value of sensor reading since last reset as a signed integer The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmeasurementsOverCurrentProtectorSensorMaxTimeStamp | 1.3.6.1.4.1.13742.6.5.3.3.1.13 | Unsigned32 | RO | 1756853470 | |||||||||||||||||
column · Unsigned32 · read-only · current The timestamp of last change of the maximum value of sensor reading provided as measurementOverCurrentProtectorSensor[Signed]MaxValue Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmeasurementsOverCurrentProtectorSensorMinMaxResetTimeStamp | 1.3.6.1.4.1.13742.6.5.3.3.1.14 | Unsigned32 | RO | 1756811719 | |||||||||||||||||
column · Unsigned32 · read-only · current The timestamp of last reset of all minimum and maximum values of sensor reading
including their timestamps, provided as measurementsOverCurrentProtectorSensor[Signed]{Min|Max}{Value|TimeStamp}
and measurementsOverCurrentProtectorSensorMinMaxValid. The measurementsOverCurrentProtectorSensorMinMaxResetTimeStamp is
always valid, even if measurementsOverCurrentProtectorSensorMinMaxValid is false.Example values from LibreNMS test devices
| |||||||||||||||||||||
| NmeasurementsOutlet | 1.3.6.1.4.1.13742.6.5.4 | ||||||||||||||||||||
| ToutletSensorMeasurementsTable | 1.3.6.1.4.1.13742.6.5.4.3 | NA | |||||||||||||||||||
table · not-accessible · current A list of outlet sensor entries. | |||||||||||||||||||||
| RoutletSensorMeasurementsEntry | 1.3.6.1.4.1.13742.6.5.4.3.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing outlet sensor measurement objects.
| |||||||||||||||||||||
| CmeasurementsOutletSensorIsAvailable | 1.3.6.1.4.1.13742.6.5.4.3.1.2 | TruthValue | RO | 1 | |||||||||||||||||
column · TruthValue · read-only · current The sensor is present. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmeasurementsOutletSensorState | 1.3.6.1.4.1.13742.6.5.4.3.1.3 | SensorStateEnumeration | RO | 4 | |||||||||||||||||
column · SensorStateEnumeration · read-only · current The sensor state. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmeasurementsOutletSensorValue | 1.3.6.1.4.1.13742.6.5.4.3.1.4 | Unsigned32 | RO | 0 | |||||||||||||||||
column · Unsigned32 · read-only · current The sensor reading as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmeasurementsOutletSensorTimeStamp | 1.3.6.1.4.1.13742.6.5.4.3.1.5 | Unsigned32 | RO | 1747869694 | |||||||||||||||||
column · Unsigned32 · read-only · current The timestamp for reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmeasurementsOutletSensorSignedValue | 1.3.6.1.4.1.13742.6.5.4.3.1.6 | Integer32 | RO | 590 | |||||||||||||||||
column · Integer32 · read-only · current The sensor reading as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmeasurementsOutletSensorMinMaxValid | 1.3.6.1.4.1.13742.6.5.4.3.1.7 | TruthValue | RO | 1 | |||||||||||||||||
column · TruthValue · read-only · current The minimum and maximum values of sensor reading and their timestamps
provided as measurementsOutletSensor[Signed]{Min|Max}{Value|TimeStamp} are validExample values from LibreNMS test devices
| |||||||||||||||||||||
| CmeasurementsOutletSensorMinValue | 1.3.6.1.4.1.13742.6.5.4.3.1.8 | Unsigned32 | RO | 99 | |||||||||||||||||
column · Unsigned32 · read-only · current The minimum value of sensor reading since last reset as an unsigned integer The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmeasurementsOutletSensorSignedMinValue | 1.3.6.1.4.1.13742.6.5.4.3.1.9 | Integer32 | RO | 99 | |||||||||||||||||
column · Integer32 · read-only · current The minimum value of sensor reading since last reset as a signed integer The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmeasurementsOutletSensorMinTimeStamp | 1.3.6.1.4.1.13742.6.5.4.3.1.10 | Unsigned32 | RO | 1709639229 | |||||||||||||||||
column · Unsigned32 · read-only · current The timestamp of last change of the minimum value of sensor reading provided as measurementOutletSensor[Signed]MinValue Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmeasurementsOutletSensorMaxValue | 1.3.6.1.4.1.13742.6.5.4.3.1.11 | Unsigned32 | RO | 1563 | |||||||||||||||||
column · Unsigned32 · read-only · current The maximum value of sensor reading since last reset as an unsigned integer The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmeasurementsOutletSensorSignedMaxValue | 1.3.6.1.4.1.13742.6.5.4.3.1.12 | Integer32 | RO | 1563 | |||||||||||||||||
column · Integer32 · read-only · current The maximum value of sensor reading since last reset as a signed integer The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmeasurementsOutletSensorMaxTimeStamp | 1.3.6.1.4.1.13742.6.5.4.3.1.13 | Unsigned32 | RO | 1717667911 | |||||||||||||||||
column · Unsigned32 · read-only · current The timestamp of last change of the maximum value of sensor reading provided as measurementOutletSensor[Signed]MaxValue Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmeasurementsOutletSensorMinMaxResetTimeStamp | 1.3.6.1.4.1.13742.6.5.4.3.1.14 | Unsigned32 | RO | 1709629970 | |||||||||||||||||
column · Unsigned32 · read-only · current The timestamp of last reset of all minimum and maximum values of sensor reading
including their timestamps, provided as measurementsOutletSensor[Signed]{Min|Max}{Value|TimeStamp}
and measurementsOutletSensorMinMaxValid. The measurementsOutletSensorMinMaxResetTimeStamp is
always valid, even if measurementsOutletSensorMinMaxValid is false.Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmeasurementsOutletSensorResetTimeStamp | 1.3.6.1.4.1.13742.6.5.4.3.1.15 | Unsigned32 | RO | 1756892680 | |||||||||||||||||
column · Unsigned32 · read-only · current The timestamp indicating when the sensor value was last reset. If the sensor never was reset this will read 0. Only for accumulating sensors. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ToutletPoleSensorMeasurementsTable | 1.3.6.1.4.1.13742.6.5.4.4 | NA | |||||||||||||||||||
table · not-accessible · current A list of outlet pole sensor entries. | |||||||||||||||||||||
| RoutletPoleSensorMeasurementsEntry | 1.3.6.1.4.1.13742.6.5.4.4.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing outlet pole sensor measurement objects.
| |||||||||||||||||||||
| CmeasurementsOutletPoleSensorIsAvailable | 1.3.6.1.4.1.13742.6.5.4.4.1.2 | TruthValue | RO | ||||||||||||||||||
column · TruthValue · read-only · current The sensor is present. | |||||||||||||||||||||
| CmeasurementsOutletPoleSensorState | 1.3.6.1.4.1.13742.6.5.4.4.1.3 | SensorStateEnumeration | RO | ||||||||||||||||||
column · SensorStateEnumeration · read-only · current The sensor state. | |||||||||||||||||||||
| CmeasurementsOutletPoleSensorValue | 1.3.6.1.4.1.13742.6.5.4.4.1.4 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The sensor reading as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsOutletPoleSensorTimeStamp | 1.3.6.1.4.1.13742.6.5.4.4.1.5 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The timestamp for reading. | |||||||||||||||||||||
| CmeasurementsOutletPoleSensorSignedValue | 1.3.6.1.4.1.13742.6.5.4.4.1.6 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The sensor reading as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsOutletPoleSensorMinMaxValid | 1.3.6.1.4.1.13742.6.5.4.4.1.7 | TruthValue | RO | ||||||||||||||||||
column · TruthValue · read-only · current The minimum and maximum values of sensor reading and their timestamps
provided as measurementsOutletPoleSensor[Signed]{Min|Max}{Value|TimeStamp} are valid | |||||||||||||||||||||
| CmeasurementsOutletPoleSensorMinValue | 1.3.6.1.4.1.13742.6.5.4.4.1.8 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The minimum value of sensor reading since last reset as an unsigned integer The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsOutletPoleSensorSignedMinValue | 1.3.6.1.4.1.13742.6.5.4.4.1.9 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The minimum value of sensor reading since last reset as a signed integer The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsOutletPoleSensorMinTimeStamp | 1.3.6.1.4.1.13742.6.5.4.4.1.10 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The timestamp of last change of the minimum value of sensor reading provided as measurementOutletPoleSensor[Signed]MinValue | |||||||||||||||||||||
| CmeasurementsOutletPoleSensorMaxValue | 1.3.6.1.4.1.13742.6.5.4.4.1.11 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The maximum value of sensor reading since last reset as an unsigned integer The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsOutletPoleSensorSignedMaxValue | 1.3.6.1.4.1.13742.6.5.4.4.1.12 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The maximum value of sensor reading since last reset as a signed integer The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsOutletPoleSensorMaxTimeStamp | 1.3.6.1.4.1.13742.6.5.4.4.1.13 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The timestamp of last change of the maximum value of sensor reading provided as measurementOutletPoleSensor[Signed]MaxValue | |||||||||||||||||||||
| CmeasurementsOutletPoleSensorMinMaxResetTimeStamp | 1.3.6.1.4.1.13742.6.5.4.4.1.14 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The timestamp of last reset of all minimum and maximum values of sensor reading
including their timestamps, provided as measurementsOutletPoleSensor[Signed]{Min|Max}{Value|TimeStamp}
and measurementsOutletPoleSensorMinMaxValid. The measurementsOutletPoleSensorMinMaxResetTimeStamp is
always valid, even if measurementsOutletPoleSensorMinMaxValid is false. | |||||||||||||||||||||
| NmeasurementsExternalSensor | 1.3.6.1.4.1.13742.6.5.5 | ||||||||||||||||||||
| TexternalSensorMeasurementsTable | 1.3.6.1.4.1.13742.6.5.5.3 | NA | |||||||||||||||||||
table · not-accessible · current A list of external sensor entries. The number of entries is given by the value of externalSensorCount for the PDU. | |||||||||||||||||||||
| RexternalSensorMeasurementsEntry | 1.3.6.1.4.1.13742.6.5.5.3.1 | NA | |||||||||||||||||||
| CmeasurementsExternalSensorIsAvailable | 1.3.6.1.4.1.13742.6.5.5.3.1.2 | TruthValue | RO | 1 | |||||||||||||||||
column · TruthValue · read-only · current The sensor is present. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmeasurementsExternalSensorState | 1.3.6.1.4.1.13742.6.5.5.3.1.3 | SensorStateEnumeration | RO | 4 | |||||||||||||||||
column · SensorStateEnumeration · read-only · current The sensor state. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmeasurementsExternalSensorValue | 1.3.6.1.4.1.13742.6.5.5.3.1.4 | Integer32 | RO | 229 | |||||||||||||||||
column · Integer32 · read-only · current The sensor reading as a signed integer. The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmeasurementsExternalSensorTimeStamp | 1.3.6.1.4.1.13742.6.5.5.3.1.5 | Unsigned32 | RO | 1548197384 | |||||||||||||||||
column · Unsigned32 · read-only · current The timestamp for reading. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmeasurementsExternalSensorMinMaxValid | 1.3.6.1.4.1.13742.6.5.5.3.1.7 | TruthValue | RO | 1 | |||||||||||||||||
column · TruthValue · read-only · current The minimum and maximum values of sensor reading and their timestamps
provided as measurementsExternalSensor[Signed]{Min|Max}{Value|TimeStamp} are validExample values from LibreNMS test devices
| |||||||||||||||||||||
| CmeasurementsExternalSensorMinValue | 1.3.6.1.4.1.13742.6.5.5.3.1.8 | Integer32 | RO | 222 | |||||||||||||||||
column · Integer32 · read-only · current The minimum value of sensor reading since last reset as a signed integer The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmeasurementsExternalSensorMinTimeStamp | 1.3.6.1.4.1.13742.6.5.5.3.1.10 | Unsigned32 | RO | 1741000649 | |||||||||||||||||
column · Unsigned32 · read-only · current The timestamp of last change of the minimum value of sensor reading provided as measurementExternalSensor[Signed]MinValue Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmeasurementsExternalSensorMaxValue | 1.3.6.1.4.1.13742.6.5.5.3.1.11 | Integer32 | RO | 261 | |||||||||||||||||
column · Integer32 · read-only · current The maximum value of sensor reading since last reset as a signed integer The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmeasurementsExternalSensorMaxTimeStamp | 1.3.6.1.4.1.13742.6.5.5.3.1.13 | Unsigned32 | RO | 1719068548 | |||||||||||||||||
column · Unsigned32 · read-only · current The timestamp of last change of the maximum value of sensor reading provided as measurementExternalSensor[Signed]MaxValue Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmeasurementsExternalSensorMinMaxResetTimeStamp | 1.3.6.1.4.1.13742.6.5.5.3.1.14 | Unsigned32 | RO | 1709629971 | |||||||||||||||||
column · Unsigned32 · read-only · current The timestamp of last reset of all minimum and maximum values of sensor reading
including their timestamps, provided as measurementsExternalSensor[Signed]{Min|Max}{Value|TimeStamp}
and measurementsExternalSensorMinMaxValid. The measurementsExternalSensorMinMaxResetTimeStamp is
always valid, even if measurementsExternalSensorMinMaxValid is false.Example values from LibreNMS test devices
| |||||||||||||||||||||
| NmeasurementsWire | 1.3.6.1.4.1.13742.6.5.6 | ||||||||||||||||||||
| TwireSensorMeasurementsTable | 1.3.6.1.4.1.13742.6.5.6.3 | NA | obsolete | ||||||||||||||||||
table · not-accessible · obsolete A list of wire sensor entries. Note: This feature is no longer used, the table is always empty | |||||||||||||||||||||
| RwireSensorMeasurementsEntry | 1.3.6.1.4.1.13742.6.5.6.3.1 | NA | obsolete | ||||||||||||||||||
row · not-accessible · obsolete An entry containing wire sensor measurement objects.
| |||||||||||||||||||||
| CmeasurementsWireSensorIsAvailable | 1.3.6.1.4.1.13742.6.5.6.3.1.2 | TruthValue | RO | obsolete | |||||||||||||||||
column · TruthValue · read-only · obsolete The sensor is present. | |||||||||||||||||||||
| CmeasurementsWireSensorState | 1.3.6.1.4.1.13742.6.5.6.3.1.3 | SensorStateEnumeration | RO | obsolete | |||||||||||||||||
column · SensorStateEnumeration · read-only · obsolete The sensor state. | |||||||||||||||||||||
| CmeasurementsWireSensorValue | 1.3.6.1.4.1.13742.6.5.6.3.1.4 | Unsigned32 | RO | obsolete | |||||||||||||||||
column · Unsigned32 · read-only · obsolete The sensor reading as an unsigned integer. The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsWireSensorTimeStamp | 1.3.6.1.4.1.13742.6.5.6.3.1.5 | Unsigned32 | RO | obsolete | |||||||||||||||||
column · Unsigned32 · read-only · obsolete The timestamp for reading. | |||||||||||||||||||||
| NmeasurementsTransferSwitch | 1.3.6.1.4.1.13742.6.5.7 | ||||||||||||||||||||
| TtransferSwitchSensorMeasurementsTable | 1.3.6.1.4.1.13742.6.5.7.3 | NA | |||||||||||||||||||
table · not-accessible · current A list of transfer switch sensor entries. | |||||||||||||||||||||
| RtransferSwitchSensorMeasurementsEntry | 1.3.6.1.4.1.13742.6.5.7.3.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing transfer switch sensor measurement objects.
| |||||||||||||||||||||
| CmeasurementsTransferSwitchSensorIsAvailable | 1.3.6.1.4.1.13742.6.5.7.3.1.2 | TruthValue | RO | ||||||||||||||||||
column · TruthValue · read-only · current The sensor is present. | |||||||||||||||||||||
| CmeasurementsTransferSwitchSensorState | 1.3.6.1.4.1.13742.6.5.7.3.1.3 | SensorStateEnumeration | RO | ||||||||||||||||||
column · SensorStateEnumeration · read-only · current The sensor state. | |||||||||||||||||||||
| CmeasurementsTransferSwitchSensorValue | 1.3.6.1.4.1.13742.6.5.7.3.1.4 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The sensor reading as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsTransferSwitchSensorTimeStamp | 1.3.6.1.4.1.13742.6.5.7.3.1.5 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The timestamp for reading. | |||||||||||||||||||||
| CmeasurementsTransferSwitchSensorSignedValue | 1.3.6.1.4.1.13742.6.5.7.3.1.6 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The sensor reading as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsTransferSwitchSensorMinMaxValid | 1.3.6.1.4.1.13742.6.5.7.3.1.7 | TruthValue | RO | ||||||||||||||||||
column · TruthValue · read-only · current The minimum and maximum values of sensor reading and their timestamps
provided as measurementsTransferSwitchSensor[Signed]{Min|Max}{Value|TimeStamp} are valid | |||||||||||||||||||||
| CmeasurementsTransferSwitchSensorMinValue | 1.3.6.1.4.1.13742.6.5.7.3.1.8 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The minimum value of sensor reading since last reset as an unsigned integer The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsTransferSwitchSensorSignedMinValue | 1.3.6.1.4.1.13742.6.5.7.3.1.9 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The minimum value of sensor reading since last reset as a signed integer The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsTransferSwitchSensorMinTimeStamp | 1.3.6.1.4.1.13742.6.5.7.3.1.10 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The timestamp of last change of the minimum value of sensor reading provided as measurementTransferSwitchSensor[Signed]MinValue | |||||||||||||||||||||
| CmeasurementsTransferSwitchSensorMaxValue | 1.3.6.1.4.1.13742.6.5.7.3.1.11 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The maximum value of sensor reading since last reset as an unsigned integer The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsTransferSwitchSensorSignedMaxValue | 1.3.6.1.4.1.13742.6.5.7.3.1.12 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The maximum value of sensor reading since last reset as a signed integer The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsTransferSwitchSensorMaxTimeStamp | 1.3.6.1.4.1.13742.6.5.7.3.1.13 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The timestamp of last change of the maximum value of sensor reading provided as measurementTransferSwitchSensor[Signed]MaxValue | |||||||||||||||||||||
| CmeasurementsTransferSwitchSensorMinMaxResetTimeStamp | 1.3.6.1.4.1.13742.6.5.7.3.1.14 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The timestamp of last reset of all minimum and maximum values of sensor reading
including their timestamps, provided as measurementsTransferSwitchSensor[Signed]{Min|Max}{Value|TimeStamp}
and measurementsTransferSwitchSensorMinMaxValid. The measurementsTransferSwitchSensorMinMaxResetTimeStamp is
always valid, even if measurementsTransferSwitchSensorMinMaxValid is false. | |||||||||||||||||||||
| NmeasurementsCircuit | 1.3.6.1.4.1.13742.6.5.8 | ||||||||||||||||||||
| TcircuitSensorMeasurementsTable | 1.3.6.1.4.1.13742.6.5.8.3 | NA | |||||||||||||||||||
table · not-accessible · current A list of circuit sensor entries. | |||||||||||||||||||||
| RcircuitSensorMeasurementsEntry | 1.3.6.1.4.1.13742.6.5.8.3.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing circuit sensor measurement objects.
| |||||||||||||||||||||
| CmeasurementsCircuitSensorIsAvailable | 1.3.6.1.4.1.13742.6.5.8.3.1.2 | TruthValue | RO | ||||||||||||||||||
column · TruthValue · read-only · current The sensor is present. | |||||||||||||||||||||
| CmeasurementsCircuitSensorState | 1.3.6.1.4.1.13742.6.5.8.3.1.3 | SensorStateEnumeration | RO | ||||||||||||||||||
column · SensorStateEnumeration · read-only · current The sensor state. | |||||||||||||||||||||
| CmeasurementsCircuitSensorValue | 1.3.6.1.4.1.13742.6.5.8.3.1.4 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The sensor reading as an unsigned integer. The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsCircuitSensorTimeStamp | 1.3.6.1.4.1.13742.6.5.8.3.1.5 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The timestamp for reading. | |||||||||||||||||||||
| CmeasurementsCircuitSensorSignedValue | 1.3.6.1.4.1.13742.6.5.8.3.1.6 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The sensor reading as a signed integer. The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsCircuitSensorMinMaxValid | 1.3.6.1.4.1.13742.6.5.8.3.1.7 | TruthValue | RO | ||||||||||||||||||
column · TruthValue · read-only · current The minimum and maximum values of sensor reading and their timestamps
provided as measurementsCircuitSensor[Signed]{Min|Max}{Value|TimeStamp} are valid | |||||||||||||||||||||
| CmeasurementsCircuitSensorMinValue | 1.3.6.1.4.1.13742.6.5.8.3.1.8 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The minimum value of sensor reading since last reset as an unsigned integer The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsCircuitSensorSignedMinValue | 1.3.6.1.4.1.13742.6.5.8.3.1.9 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The minimum value of sensor reading since last reset as a signed integer The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsCircuitSensorMinTimeStamp | 1.3.6.1.4.1.13742.6.5.8.3.1.10 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The timestamp of last change of the minimum value of sensor reading provided as measurementCircuitSensor[Signed]MinValue | |||||||||||||||||||||
| CmeasurementsCircuitSensorMaxValue | 1.3.6.1.4.1.13742.6.5.8.3.1.11 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The maximum value of sensor reading since last reset as an unsigned integer The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsCircuitSensorSignedMaxValue | 1.3.6.1.4.1.13742.6.5.8.3.1.12 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The maximum value of sensor reading since last reset as a signed integer The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsCircuitSensorMaxTimeStamp | 1.3.6.1.4.1.13742.6.5.8.3.1.13 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The timestamp of last change of the maximum value of sensor reading provided as measurementCircuitSensor[Signed]MaxValue | |||||||||||||||||||||
| CmeasurementsCircuitSensorMinMaxResetTimeStamp | 1.3.6.1.4.1.13742.6.5.8.3.1.14 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The timestamp of last reset of all minimum and maximum values of sensor reading
including their timestamps, provided as measurementsCircuitSensor[Signed]{Min|Max}{Value|TimeStamp}
and measurementsCircuitSensorMinMaxValid. The measurementsCircuitSensorMinMaxResetTimeStamp is
always valid, even if measurementsCircuitSensorMinMaxValid is false. | |||||||||||||||||||||
| CmeasurementsCircuitSensorResetTimeStamp | 1.3.6.1.4.1.13742.6.5.8.3.1.15 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The timestamp indicating when the sensor value was last reset. If the sensor never was reset this will read 0. Only for accumulating sensors. | |||||||||||||||||||||
| TcircuitPoleSensorMeasurementsTable | 1.3.6.1.4.1.13742.6.5.8.4 | NA | |||||||||||||||||||
table · not-accessible · current A list of circuit pole sensor entries. | |||||||||||||||||||||
| RcircuitPoleSensorMeasurementsEntry | 1.3.6.1.4.1.13742.6.5.8.4.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing circuit pole sensor measurement objects.
| |||||||||||||||||||||
| CmeasurementsCircuitPoleSensorIsAvailable | 1.3.6.1.4.1.13742.6.5.8.4.1.2 | TruthValue | RO | ||||||||||||||||||
column · TruthValue · read-only · current The sensor is present. | |||||||||||||||||||||
| CmeasurementsCircuitPoleSensorState | 1.3.6.1.4.1.13742.6.5.8.4.1.3 | SensorStateEnumeration | RO | ||||||||||||||||||
column · SensorStateEnumeration · read-only · current The sensor state. | |||||||||||||||||||||
| CmeasurementsCircuitPoleSensorValue | 1.3.6.1.4.1.13742.6.5.8.4.1.4 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The sensor reading as an unsigned integer. The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsCircuitPoleSensorTimeStamp | 1.3.6.1.4.1.13742.6.5.8.4.1.5 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The timestamp for reading. | |||||||||||||||||||||
| CmeasurementsCircuitPoleSensorSignedValue | 1.3.6.1.4.1.13742.6.5.8.4.1.6 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The sensor reading as a signed integer. The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsCircuitPoleSensorMinMaxValid | 1.3.6.1.4.1.13742.6.5.8.4.1.7 | TruthValue | RO | ||||||||||||||||||
column · TruthValue · read-only · current The minimum and maximum values of sensor reading and their timestamps
provided as measurementsCircuitPoleSensor[Signed]{Min|Max}{Value|TimeStamp} are valid | |||||||||||||||||||||
| CmeasurementsCircuitPoleSensorMinValue | 1.3.6.1.4.1.13742.6.5.8.4.1.8 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The minimum value of sensor reading since last reset as an unsigned integer The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsCircuitPoleSensorSignedMinValue | 1.3.6.1.4.1.13742.6.5.8.4.1.9 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The minimum value of sensor reading since last reset as a signed integer The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsCircuitPoleSensorMinTimeStamp | 1.3.6.1.4.1.13742.6.5.8.4.1.10 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The timestamp of last change of the minimum value of sensor reading provided as measurementCircuitPoleSensor[Signed]MinValue | |||||||||||||||||||||
| CmeasurementsCircuitPoleSensorMaxValue | 1.3.6.1.4.1.13742.6.5.8.4.1.11 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The maximum value of sensor reading since last reset as an unsigned integer The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsCircuitPoleSensorSignedMaxValue | 1.3.6.1.4.1.13742.6.5.8.4.1.12 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The maximum value of sensor reading since last reset as a signed integer The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsCircuitPoleSensorMaxTimeStamp | 1.3.6.1.4.1.13742.6.5.8.4.1.13 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The timestamp of last change of the maximum value of sensor reading provided as measurementCircuitPoleSensor[Signed]MaxValue | |||||||||||||||||||||
| CmeasurementsCircuitPoleSensorMinMaxResetTimeStamp | 1.3.6.1.4.1.13742.6.5.8.4.1.14 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The timestamp of last reset of all minimum and maximum values of sensor reading
including their timestamps, provided as measurementsCircuitPoleSensor[Signed]{Min|Max}{Value|TimeStamp}
and measurementsCircuitPoleSensorMinMaxValid. The measurementsCircuitPoleSensorMinMaxResetTimeStamp is
always valid, even if measurementsCircuitPoleSensorMinMaxValid is false. | |||||||||||||||||||||
| NmeasurementsOutletGroup | 1.3.6.1.4.1.13742.6.5.9 | ||||||||||||||||||||
| ToutletGroupSensorMeasurementsTable | 1.3.6.1.4.1.13742.6.5.9.3 | NA | |||||||||||||||||||
table · not-accessible · current A list of outlet group sensor entries. | |||||||||||||||||||||
| RoutletGroupSensorMeasurementsEntry | 1.3.6.1.4.1.13742.6.5.9.3.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing outlet group sensor measurement objects.
| |||||||||||||||||||||
| CmeasurementsOutletGroupSensorIsAvailable | 1.3.6.1.4.1.13742.6.5.9.3.1.2 | TruthValue | RO | ||||||||||||||||||
column · TruthValue · read-only · current The sensor is present. | |||||||||||||||||||||
| CmeasurementsOutletGroupSensorState | 1.3.6.1.4.1.13742.6.5.9.3.1.3 | SensorStateEnumeration | RO | ||||||||||||||||||
column · SensorStateEnumeration · read-only · current The sensor state. | |||||||||||||||||||||
| CmeasurementsOutletGroupSensorValue | 1.3.6.1.4.1.13742.6.5.9.3.1.4 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The sensor reading as an unsigned integer. The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsOutletGroupSensorTimeStamp | 1.3.6.1.4.1.13742.6.5.9.3.1.5 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The timestamp for reading. | |||||||||||||||||||||
| CmeasurementsOutletGroupSensorSignedValue | 1.3.6.1.4.1.13742.6.5.9.3.1.6 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The sensor reading as a signed integer. The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsOutletGroupSensorMinMaxValid | 1.3.6.1.4.1.13742.6.5.9.3.1.7 | TruthValue | RO | ||||||||||||||||||
column · TruthValue · read-only · current The minimum and maximum values of sensor reading and their timestamps
provided as measurementsOutletGroupSensor[Signed]{Min|Max}{Value|TimeStamp} are valid | |||||||||||||||||||||
| CmeasurementsOutletGroupSensorMinValue | 1.3.6.1.4.1.13742.6.5.9.3.1.8 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The minimum value of sensor reading since last reset as an unsigned integer The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsOutletGroupSensorSignedMinValue | 1.3.6.1.4.1.13742.6.5.9.3.1.9 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The minimum value of sensor reading since last reset as a signed integer The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsOutletGroupSensorMinTimeStamp | 1.3.6.1.4.1.13742.6.5.9.3.1.10 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The timestamp of last change of the minimum value of sensor reading provided as measurementOutletGroupSensor[Signed]MinValue | |||||||||||||||||||||
| CmeasurementsOutletGroupSensorMaxValue | 1.3.6.1.4.1.13742.6.5.9.3.1.11 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The maximum value of sensor reading since last reset as an unsigned integer The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsOutletGroupSensorSignedMaxValue | 1.3.6.1.4.1.13742.6.5.9.3.1.12 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The maximum value of sensor reading since last reset as a signed integer The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state. | |||||||||||||||||||||
| CmeasurementsOutletGroupSensorMaxTimeStamp | 1.3.6.1.4.1.13742.6.5.9.3.1.13 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The timestamp of last change of the maximum value of sensor reading provided as measurementOutletGroupSensor[Signed]MaxValue | |||||||||||||||||||||
| CmeasurementsOutletGroupSensorMinMaxResetTimeStamp | 1.3.6.1.4.1.13742.6.5.9.3.1.14 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The timestamp of last reset of all minimum and maximum values of sensor reading
including their timestamps, provided as measurementsOutletGroupSensor[Signed]{Min|Max}{Value|TimeStamp}
and measurementsOutletGroupSensorMinMaxValid. The measurementsOutletGroupSensorMinMaxResetTimeStamp is
always valid, even if measurementsOutletGroupSensorMinMaxValid is false. | |||||||||||||||||||||
| CmeasurementsOutletGroupSensorResetTimeStamp | 1.3.6.1.4.1.13742.6.5.9.3.1.15 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The timestamp indicating when the sensor value was last reset. If the sensor never was reset this will read 0. Only for accumulating sensors. | |||||||||||||||||||||
| Nlog | 1.3.6.1.4.1.13742.6.6 | ||||||||||||||||||||
| NlogUnit | 1.3.6.1.4.1.13742.6.6.1 | ||||||||||||||||||||
| TlogIndexTable | 1.3.6.1.4.1.13742.6.6.1.1 | NA | |||||||||||||||||||
table · not-accessible · current A table containing current indices for the data log buffer. | |||||||||||||||||||||
| RlogIndexEntry | 1.3.6.1.4.1.13742.6.6.1.1.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing the current indices for a PDU's data log buffer.
| |||||||||||||||||||||
| ColdestLogID | 1.3.6.1.4.1.13742.6.6.1.1.1.2 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The index of the oldest data in the buffer for this PDU. | |||||||||||||||||||||
| CnewestLogID | 1.3.6.1.4.1.13742.6.6.1.1.1.3 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The index of the newest data in the buffer for this PDU. | |||||||||||||||||||||
| TlogTimeStampTable | 1.3.6.1.4.1.13742.6.6.1.2 | NA | |||||||||||||||||||
table · not-accessible · current A list of entries containing the timestamps of the entries in the log. | |||||||||||||||||||||
| RlogTimeStampEntry | 1.3.6.1.4.1.13742.6.6.1.2.1 | NA | |||||||||||||||||||
| ClogIndex | 1.3.6.1.4.1.13742.6.6.1.2.1.1 | Integer32 (1..20000) | NA | ||||||||||||||||||
column · Integer32 (1..20000) · not-accessible · current A unique value for each entry in the log. Its value ranges between 1 and the value of logSize. | |||||||||||||||||||||
| ClogTimeStamp | 1.3.6.1.4.1.13742.6.6.1.2.1.2 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The time when the data was collected. It is measured in seconds since January 1, 1970 (midnight UTC/GMT). | |||||||||||||||||||||
| TunitSensorLogTable | 1.3.6.1.4.1.13742.6.6.1.3 | NA | |||||||||||||||||||
table · not-accessible · current A list of unit sensor entries in the log. | |||||||||||||||||||||
| RunitSensorLogEntry | 1.3.6.1.4.1.13742.6.6.1.3.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing log objects for a unit sensor.
| |||||||||||||||||||||
| ClogUnitSensorDataAvailable | 1.3.6.1.4.1.13742.6.6.1.3.1.2 | TruthValue | RO | ||||||||||||||||||
column · TruthValue · read-only · current Is data available for this sensor during this measurement period? | |||||||||||||||||||||
| ClogUnitSensorState | 1.3.6.1.4.1.13742.6.6.1.3.1.3 | SensorStateEnumeration | RO | ||||||||||||||||||
column · SensorStateEnumeration · read-only · current The most critical sensor state during this measurement period. | |||||||||||||||||||||
| ClogUnitSensorAvgValue | 1.3.6.1.4.1.13742.6.6.1.3.1.4 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The average sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogUnitSensorMaxValue | 1.3.6.1.4.1.13742.6.6.1.3.1.5 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The maximum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogUnitSensorMinValue | 1.3.6.1.4.1.13742.6.6.1.3.1.6 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The minimum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogUnitSensorSignedAvgValue | 1.3.6.1.4.1.13742.6.6.1.3.1.7 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The average sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogUnitSensorSignedMaxValue | 1.3.6.1.4.1.13742.6.6.1.3.1.8 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The maximum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogUnitSensorSignedMinValue | 1.3.6.1.4.1.13742.6.6.1.3.1.9 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| NlogInlet | 1.3.6.1.4.1.13742.6.6.2 | ||||||||||||||||||||
| TinletSensorLogTable | 1.3.6.1.4.1.13742.6.6.2.3 | NA | |||||||||||||||||||
table · not-accessible · current A list of inlet sensor entries in the log. | |||||||||||||||||||||
| RinletSensorLogEntry | 1.3.6.1.4.1.13742.6.6.2.3.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing log objects for a inlet sensor.
| |||||||||||||||||||||
| ClogInletSensorDataAvailable | 1.3.6.1.4.1.13742.6.6.2.3.1.2 | TruthValue | RO | ||||||||||||||||||
column · TruthValue · read-only · current Is data available for this sensor during this measurement period? | |||||||||||||||||||||
| ClogInletSensorState | 1.3.6.1.4.1.13742.6.6.2.3.1.3 | SensorStateEnumeration | RO | ||||||||||||||||||
column · SensorStateEnumeration · read-only · current The most critical sensor state during this measurement period. | |||||||||||||||||||||
| ClogInletSensorAvgValue | 1.3.6.1.4.1.13742.6.6.2.3.1.4 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The average sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogInletSensorMaxValue | 1.3.6.1.4.1.13742.6.6.2.3.1.5 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The maximum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogInletSensorMinValue | 1.3.6.1.4.1.13742.6.6.2.3.1.6 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The minimum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogInletSensorSignedAvgValue | 1.3.6.1.4.1.13742.6.6.2.3.1.7 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The average sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogInletSensorSignedMaxValue | 1.3.6.1.4.1.13742.6.6.2.3.1.8 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The maximum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogInletSensorSignedMinValue | 1.3.6.1.4.1.13742.6.6.2.3.1.9 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| TinletPoleSensorLogTable | 1.3.6.1.4.1.13742.6.6.2.4 | NA | |||||||||||||||||||
table · not-accessible · current A list of inlet pole sensor entries in the log. | |||||||||||||||||||||
| RinletPoleSensorLogEntry | 1.3.6.1.4.1.13742.6.6.2.4.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing log objects for a inlet pole sensor.
| |||||||||||||||||||||
| ClogInletPoleSensorDataAvailable | 1.3.6.1.4.1.13742.6.6.2.4.1.2 | TruthValue | RO | ||||||||||||||||||
column · TruthValue · read-only · current Is data available for this sensor during this measurement period? | |||||||||||||||||||||
| ClogInletPoleSensorState | 1.3.6.1.4.1.13742.6.6.2.4.1.3 | SensorStateEnumeration | RO | ||||||||||||||||||
column · SensorStateEnumeration · read-only · current The most critical sensor state during this measurement period. | |||||||||||||||||||||
| ClogInletPoleSensorAvgValue | 1.3.6.1.4.1.13742.6.6.2.4.1.4 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The average sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogInletPoleSensorMaxValue | 1.3.6.1.4.1.13742.6.6.2.4.1.5 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The maximum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogInletPoleSensorMinValue | 1.3.6.1.4.1.13742.6.6.2.4.1.6 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The minimum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogInletPoleSensorSignedAvgValue | 1.3.6.1.4.1.13742.6.6.2.4.1.7 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The average sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogInletPoleSensorSignedMaxValue | 1.3.6.1.4.1.13742.6.6.2.4.1.8 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The maximum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogInletPoleSensorSignedMinValue | 1.3.6.1.4.1.13742.6.6.2.4.1.9 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| TinletLinePairSensorLogTable | 1.3.6.1.4.1.13742.6.6.2.5 | NA | |||||||||||||||||||
table · not-accessible · current A list of inlet line pair sensor entries in the log. | |||||||||||||||||||||
| RinletLinePairSensorLogEntry | 1.3.6.1.4.1.13742.6.6.2.5.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing log objects for a inlet line pair sensor.
| |||||||||||||||||||||
| ClogInletLinePairSensorDataAvailable | 1.3.6.1.4.1.13742.6.6.2.5.1.2 | TruthValue | RO | ||||||||||||||||||
column · TruthValue · read-only · current Is data available for this sensor during this measurement period? | |||||||||||||||||||||
| ClogInletLinePairSensorState | 1.3.6.1.4.1.13742.6.6.2.5.1.3 | SensorStateEnumeration | RO | ||||||||||||||||||
column · SensorStateEnumeration · read-only · current The most critical sensor state during this measurement period. | |||||||||||||||||||||
| ClogInletLinePairSensorAvgValue | 1.3.6.1.4.1.13742.6.6.2.5.1.4 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The average sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogInletLinePairSensorMaxValue | 1.3.6.1.4.1.13742.6.6.2.5.1.5 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The maximum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogInletLinePairSensorMinValue | 1.3.6.1.4.1.13742.6.6.2.5.1.6 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The minimum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogInletLinePairSensorSignedAvgValue | 1.3.6.1.4.1.13742.6.6.2.5.1.7 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The average sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogInletLinePairSensorSignedMaxValue | 1.3.6.1.4.1.13742.6.6.2.5.1.8 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The maximum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogInletLinePairSensorSignedMinValue | 1.3.6.1.4.1.13742.6.6.2.5.1.9 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| NlogOverCurrentProtector | 1.3.6.1.4.1.13742.6.6.3 | ||||||||||||||||||||
| ToverCurrentProtectorSensorLogTable | 1.3.6.1.4.1.13742.6.6.3.3 | NA | |||||||||||||||||||
table · not-accessible · current A list of over current protector sensor entries in the log. | |||||||||||||||||||||
| RoverCurrentProtectorSensorLogEntry | 1.3.6.1.4.1.13742.6.6.3.3.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing log objects for a over current protector sensor. | |||||||||||||||||||||
| ClogOverCurrentProtectorSensorDataAvailable | 1.3.6.1.4.1.13742.6.6.3.3.1.2 | TruthValue | RO | ||||||||||||||||||
column · TruthValue · read-only · current Is data available for this sensor during this measurement period? | |||||||||||||||||||||
| ClogOverCurrentProtectorSensorState | 1.3.6.1.4.1.13742.6.6.3.3.1.3 | SensorStateEnumeration | RO | ||||||||||||||||||
column · SensorStateEnumeration · read-only · current The most critical sensor state during this measurement period. | |||||||||||||||||||||
| ClogOverCurrentProtectorSensorAvgValue | 1.3.6.1.4.1.13742.6.6.3.3.1.4 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The average sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogOverCurrentProtectorSensorMaxValue | 1.3.6.1.4.1.13742.6.6.3.3.1.5 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The maximum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogOverCurrentProtectorSensorMinValue | 1.3.6.1.4.1.13742.6.6.3.3.1.6 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The minimum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogOverCurrentProtectorSensorSignedAvgValue | 1.3.6.1.4.1.13742.6.6.3.3.1.7 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The average sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogOverCurrentProtectorSensorSignedMaxValue | 1.3.6.1.4.1.13742.6.6.3.3.1.8 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The maximum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogOverCurrentProtectorSensorSignedMinValue | 1.3.6.1.4.1.13742.6.6.3.3.1.9 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| NlogOutlet | 1.3.6.1.4.1.13742.6.6.4 | ||||||||||||||||||||
| ToutletSensorLogTable | 1.3.6.1.4.1.13742.6.6.4.3 | NA | |||||||||||||||||||
table · not-accessible · current A list of outlet sensor entries in the log. | |||||||||||||||||||||
| RoutletSensorLogEntry | 1.3.6.1.4.1.13742.6.6.4.3.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing log objects for a outlet sensor.
| |||||||||||||||||||||
| ClogOutletSensorDataAvailable | 1.3.6.1.4.1.13742.6.6.4.3.1.2 | TruthValue | RO | ||||||||||||||||||
column · TruthValue · read-only · current Is data available for this sensor during this measurement period? | |||||||||||||||||||||
| ClogOutletSensorState | 1.3.6.1.4.1.13742.6.6.4.3.1.3 | SensorStateEnumeration | RO | ||||||||||||||||||
column · SensorStateEnumeration · read-only · current The most critical sensor state during this measurement period. | |||||||||||||||||||||
| ClogOutletSensorAvgValue | 1.3.6.1.4.1.13742.6.6.4.3.1.4 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The average sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogOutletSensorMaxValue | 1.3.6.1.4.1.13742.6.6.4.3.1.5 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The maximum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogOutletSensorMinValue | 1.3.6.1.4.1.13742.6.6.4.3.1.6 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The minimum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogOutletSensorSignedAvgValue | 1.3.6.1.4.1.13742.6.6.4.3.1.7 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The average sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogOutletSensorSignedMaxValue | 1.3.6.1.4.1.13742.6.6.4.3.1.8 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The maximum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogOutletSensorSignedMinValue | 1.3.6.1.4.1.13742.6.6.4.3.1.9 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ToutletPoleSensorLogTable | 1.3.6.1.4.1.13742.6.6.4.4 | NA | |||||||||||||||||||
table · not-accessible · current A list of outlet pole sensor entries in the log. | |||||||||||||||||||||
| RoutletPoleSensorLogEntry | 1.3.6.1.4.1.13742.6.6.4.4.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing log objects for a outlet pole sensor.
| |||||||||||||||||||||
| ClogOutletPoleSensorDataAvailable | 1.3.6.1.4.1.13742.6.6.4.4.1.2 | TruthValue | RO | ||||||||||||||||||
column · TruthValue · read-only · current Is data available for this sensor during this measurement period? | |||||||||||||||||||||
| ClogOutletPoleSensorState | 1.3.6.1.4.1.13742.6.6.4.4.1.3 | SensorStateEnumeration | RO | ||||||||||||||||||
column · SensorStateEnumeration · read-only · current The most critical sensor state during this measurement period. | |||||||||||||||||||||
| ClogOutletPoleSensorAvgValue | 1.3.6.1.4.1.13742.6.6.4.4.1.4 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The average sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogOutletPoleSensorMaxValue | 1.3.6.1.4.1.13742.6.6.4.4.1.5 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The maximum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogOutletPoleSensorMinValue | 1.3.6.1.4.1.13742.6.6.4.4.1.6 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The minimum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogOutletPoleSensorSignedAvgValue | 1.3.6.1.4.1.13742.6.6.4.4.1.7 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The average sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogOutletPoleSensorSignedMaxValue | 1.3.6.1.4.1.13742.6.6.4.4.1.8 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The maximum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogOutletPoleSensorSignedMinValue | 1.3.6.1.4.1.13742.6.6.4.4.1.9 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outletPoleSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| NlogExternalSensor | 1.3.6.1.4.1.13742.6.6.5 | ||||||||||||||||||||
| TexternalSensorLogTable | 1.3.6.1.4.1.13742.6.6.5.3 | NA | |||||||||||||||||||
table · not-accessible · current A list of external sensor entries in the log. | |||||||||||||||||||||
| RexternalSensorLogEntry | 1.3.6.1.4.1.13742.6.6.5.3.1 | NA | |||||||||||||||||||
| ClogExternalSensorDataAvailable | 1.3.6.1.4.1.13742.6.6.5.3.1.2 | TruthValue | RO | ||||||||||||||||||
column · TruthValue · read-only · current Is data available for this sensor during this measurement period? | |||||||||||||||||||||
| ClogExternalSensorState | 1.3.6.1.4.1.13742.6.6.5.3.1.3 | SensorStateEnumeration | RO | ||||||||||||||||||
column · SensorStateEnumeration · read-only · current The most critical sensor state during this measurement period. | |||||||||||||||||||||
| ClogExternalSensorAvgValue | 1.3.6.1.4.1.13742.6.6.5.3.1.4 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The average sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogExternalSensorMaxValue | 1.3.6.1.4.1.13742.6.6.5.3.1.5 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The maximum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogExternalSensorMinValue | 1.3.6.1.4.1.13742.6.6.5.3.1.6 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| NlogWire | 1.3.6.1.4.1.13742.6.6.6 | ||||||||||||||||||||
| TwireSensorLogTable | 1.3.6.1.4.1.13742.6.6.6.3 | NA | obsolete | ||||||||||||||||||
table · not-accessible · obsolete A list of wire sensor entries in the log. Note: This feature is no longer used, the table is always empty | |||||||||||||||||||||
| RwireSensorLogEntry | 1.3.6.1.4.1.13742.6.6.6.3.1 | NA | obsolete | ||||||||||||||||||
row · not-accessible · obsolete An entry containing log objects for a wire sensor.
| |||||||||||||||||||||
| ClogWireSensorDataAvailable | 1.3.6.1.4.1.13742.6.6.6.3.1.2 | TruthValue | RO | obsolete | |||||||||||||||||
column · TruthValue · read-only · obsolete Is data available for this sensor during this measurement period? | |||||||||||||||||||||
| ClogWireSensorState | 1.3.6.1.4.1.13742.6.6.6.3.1.3 | SensorStateEnumeration | RO | obsolete | |||||||||||||||||
column · SensorStateEnumeration · read-only · obsolete The most critical sensor state during this measurement period. | |||||||||||||||||||||
| ClogWireSensorAvgValue | 1.3.6.1.4.1.13742.6.6.6.3.1.4 | Unsigned32 | RO | obsolete | |||||||||||||||||
column · Unsigned32 · read-only · obsolete The average sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogWireSensorMaxValue | 1.3.6.1.4.1.13742.6.6.6.3.1.5 | Unsigned32 | RO | obsolete | |||||||||||||||||
column · Unsigned32 · read-only · obsolete The maximum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogWireSensorMinValue | 1.3.6.1.4.1.13742.6.6.6.3.1.6 | Unsigned32 | RO | obsolete | |||||||||||||||||
column · Unsigned32 · read-only · obsolete The minimum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| NlogTransferSwitch | 1.3.6.1.4.1.13742.6.6.7 | ||||||||||||||||||||
| TtransferSwitchSensorLogTable | 1.3.6.1.4.1.13742.6.6.7.3 | NA | |||||||||||||||||||
table · not-accessible · current A list of transfer switch sensor entries in the log. | |||||||||||||||||||||
| RtransferSwitchSensorLogEntry | 1.3.6.1.4.1.13742.6.6.7.3.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing log objects for a transfer switch sensor.
| |||||||||||||||||||||
| ClogTransferSwitchSensorDataAvailable | 1.3.6.1.4.1.13742.6.6.7.3.1.2 | TruthValue | RO | ||||||||||||||||||
column · TruthValue · read-only · current Is data available for this sensor during this measurement period? | |||||||||||||||||||||
| ClogTransferSwitchSensorState | 1.3.6.1.4.1.13742.6.6.7.3.1.3 | SensorStateEnumeration | RO | ||||||||||||||||||
column · SensorStateEnumeration · read-only · current The most critical sensor state during this measurement period. | |||||||||||||||||||||
| ClogTransferSwitchSensorAvgValue | 1.3.6.1.4.1.13742.6.6.7.3.1.4 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The average sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogTransferSwitchSensorMaxValue | 1.3.6.1.4.1.13742.6.6.7.3.1.5 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The maximum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogTransferSwitchSensorMinValue | 1.3.6.1.4.1.13742.6.6.7.3.1.6 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The minimum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogTransferSwitchSensorSignedAvgValue | 1.3.6.1.4.1.13742.6.6.7.3.1.7 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The average sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogTransferSwitchSensorSignedMaxValue | 1.3.6.1.4.1.13742.6.6.7.3.1.8 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The maximum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogTransferSwitchSensorSignedMinValue | 1.3.6.1.4.1.13742.6.6.7.3.1.9 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and transferSwitchSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| NlogCircuit | 1.3.6.1.4.1.13742.6.6.8 | ||||||||||||||||||||
| TcircuitSensorLogTable | 1.3.6.1.4.1.13742.6.6.8.3 | NA | |||||||||||||||||||
table · not-accessible · current A list of circuit sensor entries in the log. | |||||||||||||||||||||
| RcircuitSensorLogEntry | 1.3.6.1.4.1.13742.6.6.8.3.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing log objects for a circuit sensor.
| |||||||||||||||||||||
| ClogCircuitSensorDataAvailable | 1.3.6.1.4.1.13742.6.6.8.3.1.2 | TruthValue | RO | ||||||||||||||||||
column · TruthValue · read-only · current Is data available for this sensor during this measurement period? | |||||||||||||||||||||
| ClogCircuitSensorState | 1.3.6.1.4.1.13742.6.6.8.3.1.3 | SensorStateEnumeration | RO | ||||||||||||||||||
column · SensorStateEnumeration · read-only · current The most critical sensor state during this measurement period. | |||||||||||||||||||||
| ClogCircuitSensorAvgValue | 1.3.6.1.4.1.13742.6.6.8.3.1.4 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The average sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogCircuitSensorMaxValue | 1.3.6.1.4.1.13742.6.6.8.3.1.5 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The maximum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogCircuitSensorMinValue | 1.3.6.1.4.1.13742.6.6.8.3.1.6 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The minimum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogCircuitSensorSignedAvgValue | 1.3.6.1.4.1.13742.6.6.8.3.1.7 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The average sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogCircuitSensorSignedMaxValue | 1.3.6.1.4.1.13742.6.6.8.3.1.8 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The maximum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogCircuitSensorSignedMinValue | 1.3.6.1.4.1.13742.6.6.8.3.1.9 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by circuitSensorDecimalDigits. For example, if the value is 1 and circuitSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| TcircuitPoleSensorLogTable | 1.3.6.1.4.1.13742.6.6.8.5 | NA | |||||||||||||||||||
table · not-accessible · current A list of circuit pole sensor entries in the log. | |||||||||||||||||||||
| RcircuitPoleSensorLogEntry | 1.3.6.1.4.1.13742.6.6.8.5.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing log objects for a circuit pole sensor.
| |||||||||||||||||||||
| ClogCircuitPoleSensorDataAvailable | 1.3.6.1.4.1.13742.6.6.8.5.1.2 | TruthValue | RO | ||||||||||||||||||
column · TruthValue · read-only · current Is data available for this sensor during this measurement period? | |||||||||||||||||||||
| ClogCircuitPoleSensorState | 1.3.6.1.4.1.13742.6.6.8.5.1.3 | SensorStateEnumeration | RO | ||||||||||||||||||
column · SensorStateEnumeration · read-only · current The most critical sensor state during this measurement period. | |||||||||||||||||||||
| ClogCircuitPoleSensorAvgValue | 1.3.6.1.4.1.13742.6.6.8.5.1.4 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The average sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogCircuitPoleSensorMaxValue | 1.3.6.1.4.1.13742.6.6.8.5.1.5 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The maximum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogCircuitPoleSensorMinValue | 1.3.6.1.4.1.13742.6.6.8.5.1.6 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The minimum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogCircuitPoleSensorSignedAvgValue | 1.3.6.1.4.1.13742.6.6.8.5.1.7 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The average sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogCircuitPoleSensorSignedMaxValue | 1.3.6.1.4.1.13742.6.6.8.5.1.8 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The maximum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogCircuitPoleSensorSignedMinValue | 1.3.6.1.4.1.13742.6.6.8.5.1.9 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by circuitPoleSensorDecimalDigits. For example, if the value is 1 and circuitPoleSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| NlogOutletGroup | 1.3.6.1.4.1.13742.6.6.9 | ||||||||||||||||||||
| ToutletGroupSensorLogTable | 1.3.6.1.4.1.13742.6.6.9.3 | NA | |||||||||||||||||||
table · not-accessible · current A list of outlet group sensor entries in the log. | |||||||||||||||||||||
| RoutletGroupSensorLogEntry | 1.3.6.1.4.1.13742.6.6.9.3.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing log objects for a outlet group sensor.
| |||||||||||||||||||||
| ClogOutletGroupSensorDataAvailable | 1.3.6.1.4.1.13742.6.6.9.3.1.2 | TruthValue | RO | ||||||||||||||||||
column · TruthValue · read-only · current Is data available for this sensor during this measurement period? | |||||||||||||||||||||
| ClogOutletGroupSensorState | 1.3.6.1.4.1.13742.6.6.9.3.1.3 | SensorStateEnumeration | RO | ||||||||||||||||||
column · SensorStateEnumeration · read-only · current The most critical sensor state during this measurement period. | |||||||||||||||||||||
| ClogOutletGroupSensorAvgValue | 1.3.6.1.4.1.13742.6.6.9.3.1.4 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The average sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogOutletGroupSensorMaxValue | 1.3.6.1.4.1.13742.6.6.9.3.1.5 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The maximum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogOutletGroupSensorMinValue | 1.3.6.1.4.1.13742.6.6.9.3.1.6 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The minimum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogOutletGroupSensorSignedAvgValue | 1.3.6.1.4.1.13742.6.6.9.3.1.7 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The average sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogOutletGroupSensorSignedMaxValue | 1.3.6.1.4.1.13742.6.6.9.3.1.8 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The maximum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| ClogOutletGroupSensorSignedMinValue | 1.3.6.1.4.1.13742.6.6.9.3.1.9 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by outletGroupSensorDecimalDigits. For example, if the value is 1 and outletGroupSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading. | |||||||||||||||||||||
| Nconformance | 1.3.6.1.4.1.13742.6.9 | ||||||||||||||||||||
| Ncompliances | 1.3.6.1.4.1.13742.6.9.1 | ||||||||||||||||||||
| McomplianceRev1 | 1.3.6.1.4.1.13742.6.9.1.1 | deprecated | |||||||||||||||||||
compliance · deprecated The requirements for conformance to the PDU2-MIB.
| |||||||||||||||||||||
| McomplianceRev2 | 1.3.6.1.4.1.13742.6.9.1.2 | ||||||||||||||||||||
compliance · current The requirements for conformance to the PDU2-MIB. | |||||||||||||||||||||
| Ngroups | 1.3.6.1.4.1.13742.6.9.2 | ||||||||||||||||||||
| GconfigGroup | 1.3.6.1.4.1.13742.6.9.2.1 | ||||||||||||||||||||
group · current A collection of objects representing configuration data.
| |||||||||||||||||||||
| GlogGroup | 1.3.6.1.4.1.13742.6.9.2.2 | ||||||||||||||||||||
group · current A collection of objects providing logging (history of readings) capabilities about the PDU.
| |||||||||||||||||||||
| GmeasurementsGroup | 1.3.6.1.4.1.13742.6.9.2.3 | ||||||||||||||||||||
group · current A collection of objects providing measurements (most recent data) capabilities. about the PDU.
| |||||||||||||||||||||
| GcontrolGroup | 1.3.6.1.4.1.13742.6.9.2.4 | ||||||||||||||||||||
group · current A collection of objects providing the ability to control various components of a PDU.
| |||||||||||||||||||||
| GtrapInformationGroup | 1.3.6.1.4.1.13742.6.9.2.5 | ||||||||||||||||||||
group · current A collection of objects providing information in the traps.
| |||||||||||||||||||||
| GtrapsGroup | 1.3.6.1.4.1.13742.6.9.2.9 | ||||||||||||||||||||
group · current A collection of traps.
| |||||||||||||||||||||
| GreliabilityGroup | 1.3.6.1.4.1.13742.6.9.2.10 | ||||||||||||||||||||
group · current A collection of objects providing reliability data.
| |||||||||||||||||||||
| GipAddressGroup | 1.3.6.1.4.1.13742.6.9.2.12 | deprecated | |||||||||||||||||||
group · deprecated A collection of objects representing configuration data. | |||||||||||||||||||||
| GoldConfigGroup | 1.3.6.1.4.1.13742.6.9.2.13 | deprecated | |||||||||||||||||||
group · deprecated A collection of objects representing old (deprecated) configuration data.
| |||||||||||||||||||||
| GoldTrapsGroup | 1.3.6.1.4.1.13742.6.9.2.16 | deprecated | |||||||||||||||||||
group · deprecated A collection of objects representing old (deprecated) traps. | |||||||||||||||||||||
| GobsoleteTrapsGroup | 1.3.6.1.4.1.13742.6.9.2.17 | obsolete | |||||||||||||||||||
| GobsoleteObjectsGroup | 1.3.6.1.4.1.13742.6.9.2.20 | obsolete | |||||||||||||||||||
group · obsolete A collection of obsolete objects.
| |||||||||||||||||||||
| Nreliability | 1.3.6.1.4.1.13742.6.10 | ||||||||||||||||||||
| NreliabilityData | 1.3.6.1.4.1.13742.6.10.1 | ||||||||||||||||||||
| SreliabilityDataTableSequenceNumber | 1.3.6.1.4.1.13742.6.10.1.1 | Integer32 (1..2147483647) | RO | ||||||||||||||||||
scalar · Integer32 (1..2147483647) · read-only · current The sequence number for updates to the reliability data table | |||||||||||||||||||||
| TreliabilityDataTable | 1.3.6.1.4.1.13742.6.10.1.2 | NA | |||||||||||||||||||
table · not-accessible · current A list of PDU reliability data entries. | |||||||||||||||||||||
| RreliabilityDataEntry | 1.3.6.1.4.1.13742.6.10.1.2.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing reliability data for a particular PDU.
| |||||||||||||||||||||
| CreliabilityIndex | 1.3.6.1.4.1.13742.6.10.1.2.1.1 | Integer32 (1..4096) | NA | ||||||||||||||||||
column · Integer32 (1..4096) · not-accessible · current Index of the entry in the reliability data table. | |||||||||||||||||||||
| CreliabilityId | 1.3.6.1.4.1.13742.6.10.1.2.1.2 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current Unique ID of the entry.
POH
Power on hours.
CB.<label>.TRIPCNT
Trip count of circuit breaker with label <label>.
CTRL.<serial>.<addr>.MAIN.CSUMERRLASTHOUR
Number of checksum errors in sub (controller board) to main (CPU
board) communication in the last hour on controller with serial
number <serial> and bus address <addr>.
CTRL.<serial>.<addr>.SUB.CSUMERRLASTHOUR
Number of checksum errors in main (CPU board) to sub (controller
board) communication in the last hour on controller with serial
number <serial> and bus address <addr>.
CTRL.<serial>.<addr>.TOUTLASTHOUR
Number of communication timeouts to controller with serial
number <serial> and bus address <addr> in the last hour.
CTRL.<serial>.<addr>.RLY.<num>.CYCLECNT
Number of cycles the relay <num> on the controller board with serial
number <serial> and bus address <addr> has made. A cycle is an
off->on followed by an on->off event later. The count is increased on
the off->on transition.
CTRL.<serial>.<addr>.RLY.<num>.FAILLASTHOUR
Number of failed switching operations on relay <num> on the controller
board with serial number <serial> and bus address <addr> in the last
hour. It depends on the specific controller board hardware and what
error conditions are detected.
CTRL.<serial>.<addr>.EMRSTCNT
Number of energy-meter resets on the controller board with serial
number <serial> and bus address <addr>.
CTRL.<serial>.<addr>.RSTCNT
Number of resets of the controller board with serial number <serial>
and bus address <addr>. | |||||||||||||||||||||
| CreliabilityDataValue | 1.3.6.1.4.1.13742.6.10.1.2.1.3 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The normalized value | |||||||||||||||||||||
| CreliabilityDataMaxPossible | 1.3.6.1.4.1.13742.6.10.1.2.1.4 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The maximum possible normalized value | |||||||||||||||||||||
| CreliabilityDataWorstValue | 1.3.6.1.4.1.13742.6.10.1.2.1.5 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The worst normalized value seen so far | |||||||||||||||||||||
| CreliabilityDataThreshold | 1.3.6.1.4.1.13742.6.10.1.2.1.6 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The normalized Threshold value | |||||||||||||||||||||
| CreliabilityDataRawUpperBytes | 1.3.6.1.4.1.13742.6.10.1.2.1.7 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The upper 4 bytes of the raw (not normalized) data. reliabilityDataRawUpperBytes and reliabilityDataRawLowerBytes should be combined and interpreted as a signed 64-bit value | |||||||||||||||||||||
| CreliabilityDataRawLowerBytes | 1.3.6.1.4.1.13742.6.10.1.2.1.8 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The lower 4 bytes of the raw (not normalized) data. reliabilityDataRawUpperBytes and reliabilityDataRawLowerBytes should be combined and interpreted as a signed 64-bit value | |||||||||||||||||||||
| CreliabilityDataFlags | 1.3.6.1.4.1.13742.6.10.1.2.1.9 | Bits | RO | ||||||||||||||||||
column · Bits · read-only · current Flags
| |||||||||||||||||||||
| NreliabilityErrorLog | 1.3.6.1.4.1.13742.6.10.2 | ||||||||||||||||||||
| TreliabilityErrorLogTable | 1.3.6.1.4.1.13742.6.10.2.2 | NA | |||||||||||||||||||
table · not-accessible · current A list of PDU reliability error log entries. | |||||||||||||||||||||
| RreliabilityErrorLogEntry | 1.3.6.1.4.1.13742.6.10.2.2.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing reliability error log data for a particular PDU. | |||||||||||||||||||||
| CreliabilityErrorLogIndex | 1.3.6.1.4.1.13742.6.10.2.2.1.1 | Integer32 (1..2147483647) | NA | ||||||||||||||||||
column · Integer32 (1..2147483647) · not-accessible · current Index of the entry in the reliability error log table. | |||||||||||||||||||||
| CreliabilityErrorLogId | 1.3.6.1.4.1.13742.6.10.2.2.1.2 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current Unique ID of the entry.
POH
Power on hours.
CB.<label>.TRIPCNT
Trip count of circuit breaker with label <label>.
CTRL.<serial>.<addr>.MAIN.CSUMERRLASTHOUR
Number of checksum errors in sub (controller board) to main (CPU
board) communication in the last hour on controller with serial
number <serial> and bus address <addr>.
CTRL.<serial>.<addr>.SUB.CSUMERRLASTHOUR
Number of checksum errors in main (CPU board) to sub (controller
board) communication in the last hour on controller with serial
number <serial> and bus address <addr>.
CTRL.<serial>.<addr>.TOUTLASTHOUR
Number of communication timeouts to controller with serial
number <serial> and bus address <addr> in the last hour.
CTRL.<serial>.<addr>.RLY.<num>.CYCLECNT
Number of cycles the relay <num> on the controller board with serial
number <serial> and bus address <addr> has made. A cycle is an
off->on followed by an on->off event later. The count is increased on
the off->on transition.
CTRL.<serial>.<addr>.RLY.<num>.FAILLASTHOUR
Number of failed switching operations on relay <num> on the controller
board with serial number <serial> and bus address <addr> in the last
hour. It depends on the specific controller board hardware and what
error conditions are detected. | |||||||||||||||||||||
| CreliabilityErrorLogValue | 1.3.6.1.4.1.13742.6.10.2.2.1.3 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The normalized value | |||||||||||||||||||||
| CreliabilityErrorLogThreshold | 1.3.6.1.4.1.13742.6.10.2.2.1.6 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The normalized threshold value | |||||||||||||||||||||
| CreliabilityErrorLogRawUpperBytes | 1.3.6.1.4.1.13742.6.10.2.2.1.7 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The upper 4 bytes of the raw (not normalized) data. reliabilityErrorLogRawUpperBytes and reliabilityErrorLogRawLowerBytes should be combined and interpreted as a signed 64-bit value | |||||||||||||||||||||
| CreliabilityErrorLogRawLowerBytes | 1.3.6.1.4.1.13742.6.10.2.2.1.8 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The lower 4 bytes of the raw (not normalized) data. reliabilityErrorLogRawUpperBytes and reliabilityErrorLogRawLowerBytes should be combined and interpreted as a signed 64-bit value | |||||||||||||||||||||
| CreliabilityErrorLogPOH | 1.3.6.1.4.1.13742.6.10.2.2.1.9 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The time of occurrence of the event measured from the last time the PDU was powered on | |||||||||||||||||||||
| CreliabilityErrorLogTime | 1.3.6.1.4.1.13742.6.10.2.2.1.10 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The UTC time of occurrence of the event | |||||||||||||||||||||
| NreliabilityHardwareHealth | 1.3.6.1.4.1.13742.6.10.3 | ||||||||||||||||||||
| ThwFailureTable | 1.3.6.1.4.1.13742.6.10.3.1 | NA | |||||||||||||||||||
table · not-accessible · current A list of hardware failure entries. | |||||||||||||||||||||
| RhwFailureEntry | 1.3.6.1.4.1.13742.6.10.3.1.1 | NA | |||||||||||||||||||
| ChwFailureIndex | 1.3.6.1.4.1.13742.6.10.3.1.1.1 | Integer32 (1..65535) | NA | ||||||||||||||||||
column · Integer32 (1..65535) · not-accessible · current Index of the entry in the hardware failure table. | |||||||||||||||||||||
| ChwFailureComponentId | 1.3.6.1.4.1.13742.6.10.3.1.1.2 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current The id of the affected hardware component. | |||||||||||||||||||||
| ChwFailureType | 1.3.6.1.4.1.13742.6.10.3.1.1.3 | HwFailureTypeEnumeration | RO | ||||||||||||||||||
column · HwFailureTypeEnumeration · read-only · current The hardware failure type. | |||||||||||||||||||||
| ChwFailureAsserted | 1.3.6.1.4.1.13742.6.10.3.1.1.4 | TruthValue | RO | ||||||||||||||||||
column · TruthValue · read-only · current Reflects whether the failure state is asserted(true) or not(false). | |||||||||||||||||||||
| ChwFailureLastAssertTimeStamp | 1.3.6.1.4.1.13742.6.10.3.1.1.5 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The timestamp indicating when the failure was last asserted. It is measured in seconds since January 1, 1970 UTC. | |||||||||||||||||||||
| ChwFailureLastDeassertTimeStamp | 1.3.6.1.4.1.13742.6.10.3.1.1.6 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The timestamp indicating when the failure was last deasserted. It is measured in seconds since January 1, 1970 UTC. If the failure is currently asserted then this has no meaning and is reported as 0. | |||||||||||||||||||||
| ChwFailureAssertCount | 1.3.6.1.4.1.13742.6.10.3.1.1.7 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The number of times the failure was asserted. | |||||||||||||||||||||
Textual conventions
AddressSourceEnumerationINTEGERdhcp(2)dhcpv6(3)static(1)How was the address obtained?
BoardTypeEnumerationINTEGERinletController(2)mainController(1)meteringController(4)outletController(3)The types of boards.
CircuitTypeEnumerationINTEGERonePhaseLL(1)onePhaseLLN(3)onePhaseLN(2)threePhase(4)The panel circuit types.
DaisychainMemberTypeEnumerationINTEGERexpansionUnit(2)primaryUnit(1)standalone(0)The daisy chain member type.
DeviceCascadeTypeEnumerationINTEGERbridging(0)none(2)portForwarding(1)The type of configured cascading on this device.
DeviceIdentificationParameterEnumerationINTEGERpduName(0)sysContact(1)sysLocation(3)sysName(2)The configurable parameters.
ExternalSensorsZCoordinateUnitsEnumerationINTEGERrackUnits(0)text(1)The units of the external sensor Z coordinate. rackUnits implies that the Z coordinate for all external sensors is in rack units (U) text implies that the Z coordinate for all external sensors is a text string (label)
GlobalOutletStateOnStartupEnumerationINTEGERlastKnownState(2)off(0)on(1)The global outlet state on device start up; can be overridden per outlet.
HundredthsOfAPercentageUnsigned32 (0..10000)Display hint:
dData type for reporting values in hundredths of percentage, i.e. 0.01 %.
HwFailureTypeEnumerationINTEGERi2cBusStuck(2)networkDeviceNotDetected(1)outletPowerStateInconsistent(5)subCtrlMalfunction(4)subCtrlNotReachable(3)The hardware failure type.
LineEnumerationINTEGERlineDcNegative(6)lineDcPositive(5)lineL1(1)lineL2(2)lineL3(3)lineNeutral(4)The Lines: L1, L2, L3, N.
NetworkInterfaceTypeEnumerationINTEGERwired(0)wireless(1)The type of network interface.
OutletStateOnStartupEnumerationINTEGERglobalOutletStateOnStartup(3)lastKnownState(2)off(0)on(1)The outlet state on device start up; this overrides the global value.
OutletSwitchingOperationsEnumerationINTEGERcycle(2)off(0)on(1)The switching operations on an outlet.
OverCurrentProtectorTypeEnumerationINTEGERocpBREAKER1POLE(1)ocpBREAKER2POLE(2)ocpBREAKER3POLE(3)ocpFUSE(4)ocpFUSEPAIR(5)ocpRCBO2POLE(6)ocpRCBO3POLE(7)ocpRCBO4POLE(8)The types of overcurrent protectors.
PanelLayoutEnumerationINTEGERinvalid(-1)oneColumn(1)twoColumns(2)The panel circuit position layout.
PanelNumberingEnumerationINTEGERinvalid(-1)oddEven(1)sequential(2)The panel circuit position numbering scheme.
PduOrientationEnumerationINTEGERbottomFeed(1)none(0)topFeed(2)The detected pdu orientation on device startup.
PeripheralDeviceFirmwareUpdateStateEnumerationINTEGERfailed(3)started(1)successful(2)The state of a peripheral device firmware update.
PhaseEnumerationINTEGERearth(5)neutral(4)phaseA(1)phaseB(2)phaseC(3)The power phase.
PlugTypeEnumerationINTEGERplug56P320(1)plug56P320F(48)plug56P520(2)plug56P532(3)plug56PA320(49)plugCS8365C(4)plugIEC320C14(5)plugIEC320C20(6)plugIEC603093WIRE250V100A(13)plugIEC603093WIRE250V125A(14)plugIEC603093WIRE250V16A(7)plugIEC603093WIRE250V20A(8)plugIEC603093WIRE250V30A(9)plugIEC603093WIRE250V32A(10)plugIEC603093WIRE250V60A(11)plugIEC603093WIRE250V63A(12)plugIEC603094WIRE250V100A(18)plugIEC603094WIRE250V20A(15)plugIEC603094WIRE250V30A(16)plugIEC603094WIRE250V60A(17)plugIEC603095WIRE208V100A(26)plugIEC603095WIRE208V20A(23)plugIEC603095WIRE208V30A(24)plugIEC603095WIRE208V60A(25)plugIEC603095WIRE415V125A(30)plugIEC603095WIRE415V16A(27)plugIEC603095WIRE415V32A(28)plugIEC603095WIRE415V63A(29)plugIEC603095WIRE480V100A(34)plugIEC603095WIRE480V20A(31)plugIEC603095WIRE480V30A(32)plugIEC603095WIRE480V60A(33)plugNEMA515P(35)plugNEMA520P(37)plugNEMAL1520P(43)plugNEMAL1530P(44)plugNEMAL2120P(45)plugNEMAL2130P(46)plugNEMAL2230P(47)plugNEMAL515P(36)plugNEMAL520P(38)plugNEMAL530P(39)plugNEMAL615P(40)plugNEMAL620P(41)plugNEMAL630P(42)plugNONE(0)plugOTHER(-1)The types of inlet plug.
PortFuseStateEnumerationINTEGERgood(1)tripped(2)unknown(0)The states a port fuse can be in.
PowerMeterTypeEnumerationINTEGERsinglePhase(1)splitPhase(2)threePhase(3)The power meter types
ProductTypeEnumerationINTEGERbcm(1)powerMeter(3)rackPdu(0)transferSwitch(2)The product types.
ReceptacleTypeEnumerationINTEGERreceptacle56P532(3)receptacleBS1363(1)receptacleCS8364C(4)receptacleIEC320C13(5)receptacleIEC320C19(6)receptacleIEC603093WIRE250V100A(13)receptacleIEC603093WIRE250V125A(14)receptacleIEC603093WIRE250V16A(7)receptacleIEC603093WIRE250V20A(8)receptacleIEC603093WIRE250V30A(9)receptacleIEC603093WIRE250V32A(10)receptacleIEC603093WIRE250V60A(11)receptacleIEC603093WIRE250V63A(12)receptacleIEC603094WIRE250V100A(18)receptacleIEC603094WIRE250V20A(15)receptacleIEC603094WIRE250V30A(16)receptacleIEC603094WIRE250V60A(17)receptacleIEC603095WIRE208V100A(26)receptacleIEC603095WIRE208V20A(23)receptacleIEC603095WIRE208V30A(24)receptacleIEC603095WIRE208V60A(25)receptacleIEC603095WIRE415V125A(30)receptacleIEC603095WIRE415V16A(27)receptacleIEC603095WIRE415V32A(28)receptacleIEC603095WIRE415V63A(29)receptacleIEC603095WIRE480V100A(34)receptacleIEC603095WIRE480V20A(31)receptacleIEC603095WIRE480V30A(32)receptacleIEC603095WIRE480V60A(33)receptacleNEMA515R(35)receptacleNEMA520R(37)receptacleNEMAL1520R(43)receptacleNEMAL1530R(44)receptacleNEMAL2120RP(45)receptacleNEMAL2130R(46)receptacleNEMAL515R(36)receptacleNEMAL520R(38)receptacleNEMAL530R(39)receptacleNEMAL615R(40)receptacleNEMAL620R(41)receptacleNEMAL630R(42)receptacleNONE(0)receptacleOTHER(-1)receptacleSCHUKOTYPEE(47)receptacleSCHUKOTYPEF(48)The types of outlet receptacle.
RelayPowerLossBehaviorEnumerationINTEGERlatching(1)nonLatching(0)The type of relay behavior on power loss.
SensorStateEnumerationINTEGERaboveUpperCritical(6)aboveUpperWarning(5)alarmed(11)belowLowerCritical(2)belowLowerWarning(3)bypassActive(36)closed(1)critical(28)detected(9)fail(14)fault(26)i1OpenFault(22)i1Selected(32)i1SelectedAndActive(34)i1ShortFault(23)i2OpenFault(24)i2Selected(33)i2SelectedAndActive(35)i2ShortFault(25)inSync(20)inactive(31)no(16)nonRedundant(30)normal(4)notDetected(10)off(8)ok(12)on(7)one(18)open(0)outOfSync(21)selfTest(29)standby(17)two(19)unavailable(-1)warning(27)yes(15)The states a sensor can be in; unavailable means no sensor reading.
SensorTypeEnumerationINTEGERabsoluteHumidity(28)activeEnergy(8)activeInlet(41)activePower(5)activePowerDemand(54)airFlow(12)airPressure(13)apparentEnergy(9)apparentPower(6)batteryLevel(79)binary(19)contact(20)crestFactor(51)currentThd(58)dewPoint(63)displacementPowerFactor(35)distance(53)doorContact(43)doorHandleLock(50)doorLockState(49)electricFieldStrength(75)electricalImpedance(71)electricalResistance(70)fanSpeed(21)fanStatus(37)flux(65)frequency(23)humidity(11)i1smpsStatus(46)i2smpsStatus(47)illuminance(42)inletPhaseSync(39)inletPhaseSyncAngle(38)inrushCurrent(59)installFaultStatus(80)length(52)luminousEmittance(69)luminousEnergy(67)luminousFlux(68)luminousIntensity(66)magneticFieldStrength(73)magneticFluxDensity(74)mass(64)motionDetection(45)none(31)onOff(14)operatingState(40)other(30)overheatStatus(34)overloadStatus(33)particleDensity(56)peakCurrent(2)phaseAngle(24)powerFactor(7)powerQuality(32)rcmState(27)reactivePower(29)residualAcCurrent(55)residualCurrent(26)residualDcCurrent(36)rmsCurrent(1)rmsVoltage(4)rmsVoltageLN(25)rotationalSpeed(77)selection(76)smokeDetection(18)surgeProtectorStatus(22)switchStatus(48)tamperDetection(44)temperature(10)totalHarmonicDistortion(72)transferSwitchBypassState(78)transferSwitchOutputStatus(81)trip(15)unbalancedCurrent(3)unbalancedLineLineCurrent(61)unbalancedLineLineVoltage(62)unbalancedVoltage(60)vibration(16)voltageThd(57)waterDetection(17)The types a sensor can be.
SensorUnitsEnumerationINTEGERamp(2)becquerel(52)candela(39)cm(17)coulomb(30)cubicMeter(42)degreeC(7)degreeF(14)degrees(20)farad(50)feet(15)feetpersec(24)g(13)gram(35)grampercubicmeter(22)gray(53)henry(49)hertz(8)hour(27)inches(16)joule(46)kelvin(31)lbspercubicfoot(25)litersPerHour(37)lumen(40)lumenSecond(41)lux(21)meterPerSquareSec(36)meterpersec(10)meters(18)microgrampercubicmeter(26)minute(28)mol(51)newton(45)nit(38)none(-1)ohm(47)other(0)pascal(11)percent(9)psi(12)radiant(43)rpm(19)second(29)sievert(54)steradiant(44)tesla(48)var(23)volt(1)voltAmpReactiveHour(32)voltPerAmpere(33)voltPerMeter(34)voltamp(4)voltampHour(6)watt(3)wattHour(5)The sensor units.
ServerPowerControlResultEnumerationINTEGERnoError(0)powerCheckTimeout(4)shutdownCmdFailed(1)switchingOffFailed(2)switchingOnFailed(3)The result of a server power control operation.
ServerPowerStateEnumerationINTEGERoff(2)on(1)shuttingDown(3)unknown(0)The server power control state.
TransferSwitchTransferReasonEnumerationINTEGERautomaticReTransfer(3)bypassActive(9)internalFailure(8)manualTransfer(2)overheatAlarm(7)overloadAlarm(6)powerFailure(4)powerQuality(5)startup(1)unknown(0)Transfer Switch Transfer Reason
TripCauseOutletHandlingEnumerationINTEGERkeepUnchanged(0)suspend(1)How to handle outlets that are suspected to have caused an OCP trip event.
URLOCTET STRING (SIZE (0..255))Display hint:
255aA Uniform Resource Locator (URL), as defined in RFC1738.
Traps / Notifications
- actuatorSwitched
1.3.6.1.4.1.13742.6.0.128 - bulkConfigurationCopied
1.3.6.1.4.1.13742.6.0.54 - bulkConfigurationSaved
1.3.6.1.4.1.13742.6.0.53 - circuitAdded
1.3.6.1.4.1.13742.6.0.105 - circuitDeleted
1.3.6.1.4.1.13742.6.0.106 - circuitModified
1.3.6.1.4.1.13742.6.0.107 - circuitPoleSensorStateChange
1.3.6.1.4.1.13742.6.0.104 - circuitSensorReset
1.3.6.1.4.1.13742.6.0.108 - circuitSensorStateChange
1.3.6.1.4.1.13742.6.0.103 - deviceIdentificationChanged
1.3.6.1.4.1.13742.6.0.79 - deviceSettingsRestored
1.3.6.1.4.1.13742.6.0.89 - deviceSettingsSaved
1.3.6.1.4.1.13742.6.0.88 - deviceUpdateCompleted
1.3.6.1.4.1.13742.6.0.21 - deviceUpdateFailed
1.3.6.1.4.1.13742.6.0.70 - deviceUpdateStarted
1.3.6.1.4.1.13742.6.0.20 - doorAccessDenied
1.3.6.1.4.1.13742.6.0.131 - doorAccessGranted
1.3.6.1.4.1.13742.6.0.130 - doorAccessRuleAdded
1.3.6.1.4.1.13742.6.0.132 - doorAccessRuleChanged
1.3.6.1.4.1.13742.6.0.133 - doorAccessRuleDeleted
1.3.6.1.4.1.13742.6.0.134 - doorForcedOpen
1.3.6.1.4.1.13742.6.0.161 - doorMechanicallyUnlocked
1.3.6.1.4.1.13742.6.0.160 - externalSensorStateChange
1.3.6.1.4.1.13742.6.0.66 - firmwareValidationFailed
1.3.6.1.4.1.13742.6.0.38 - hwFailureStatusChanged
1.3.6.1.4.1.13742.6.0.117 - inletDipEvent
1.3.6.1.4.1.13742.6.0.151 - inletDisabled
1.3.6.1.4.1.13742.6.0.93 - inletEnabled
1.3.6.1.4.1.13742.6.0.92 - inletLinePairSensorStateChange
1.3.6.1.4.1.13742.6.0.135 - inletPoleDipEvent
1.3.6.1.4.1.13742.6.0.153 - inletPoleSensorStateChange
1.3.6.1.4.1.13742.6.0.62 - inletPoleSwellEvent
1.3.6.1.4.1.13742.6.0.154 - inletSensorReset
1.3.6.1.4.1.13742.6.0.97 - inletSensorStateChange
1.3.6.1.4.1.13742.6.0.61 - inletSwellEvent
1.3.6.1.4.1.13742.6.0.152 - keypadPinEntered
1.3.6.1.4.1.13742.6.0.129 - ldapError
1.3.6.1.4.1.13742.6.0.68 - lhxSupportChanged
1.3.6.1.4.1.13742.6.0.82 - linkUnitAdded
1.3.6.1.4.1.13742.6.0.156 - linkUnitCommunicationFailed
1.3.6.1.4.1.13742.6.0.159 - linkUnitCommunicationOk
1.3.6.1.4.1.13742.6.0.158 - linkUnitReleased
1.3.6.1.4.1.13742.6.0.157 - loadSheddingModeEntered
1.3.6.1.4.1.13742.6.0.71 - loadSheddingModeExited
1.3.6.1.4.1.13742.6.0.72 - logFileCleared
1.3.6.1.4.1.13742.6.0.41 - outletGroupAdded
1.3.6.1.4.1.13742.6.0.118 - outletGroupDeleted
1.3.6.1.4.1.13742.6.0.120 - outletGroupModified
1.3.6.1.4.1.13742.6.0.119 - outletGroupPowerControl
1.3.6.1.4.1.13742.6.0.123 - outletGroupSensorReset
1.3.6.1.4.1.13742.6.0.122 - outletGroupSensorStateChange
1.3.6.1.4.1.13742.6.0.121 - outletPoleSensorStateChange
1.3.6.1.4.1.13742.6.0.64 - outletSensorReset
1.3.6.1.4.1.13742.6.0.98 - outletSensorStateChange
1.3.6.1.4.1.13742.6.0.63 - outletServiceModeChanged
1.3.6.1.4.1.13742.6.0.162 - outletSuspended
1.3.6.1.4.1.13742.6.0.137 - overCurrentProtectorSensorStateChange
1.3.6.1.4.1.13742.6.0.65 - passwordSettingsChanged
1.3.6.1.4.1.13742.6.0.28 - pduSensorStateChange
1.3.6.1.4.1.13742.6.0.60 - peripheralDeviceFirmwareUpdate
1.3.6.1.4.1.13742.6.0.100 - pingServerDisabled
1.3.6.1.4.1.13742.6.0.74 - pingServerEnabled
1.3.6.1.4.1.13742.6.0.73 - portFuseStateChange
1.3.6.1.4.1.13742.6.0.155 - powerControl
1.3.6.1.4.1.13742.6.0.23 - powerMeterAdded
1.3.6.1.4.1.13742.6.0.109 - powerMeterDeleted
1.3.6.1.4.1.13742.6.0.110 - powerMeterModified
1.3.6.1.4.1.13742.6.0.111 - radiusError
1.3.6.1.4.1.13742.6.0.95 - rawConfigurationDownloaded
1.3.6.1.4.1.13742.6.0.115 - rawConfigurationUpdated
1.3.6.1.4.1.13742.6.0.116 - rfCodeTagConnected
1.3.6.1.4.1.13742.6.0.77 - rfCodeTagDisconnected
1.3.6.1.4.1.13742.6.0.78 - roleAdded
1.3.6.1.4.1.13742.6.0.14 - roleDeleted
1.3.6.1.4.1.13742.6.0.16 - roleModified
1.3.6.1.4.1.13742.6.0.15 - serverConnectivityUnrecoverable
1.3.6.1.4.1.13742.6.0.94 - serverNotReachable
1.3.6.1.4.1.13742.6.0.75 - serverPowerControlCompleted
1.3.6.1.4.1.13742.6.0.125 - serverPowerControlInitiated
1.3.6.1.4.1.13742.6.0.124 - serverReachabilityError
1.3.6.1.4.1.13742.6.0.96 - serverReachable
1.3.6.1.4.1.13742.6.0.76 - smartCardInserted
1.3.6.1.4.1.13742.6.0.113 - smartCardRemoved
1.3.6.1.4.1.13742.6.0.114 - smsMessageTransmissionFailure
1.3.6.1.4.1.13742.6.0.112 - smtpMessageTransmissionFailure
1.3.6.1.4.1.13742.6.0.67 - systemReset
1.3.6.1.4.1.13742.6.0.2 - systemStarted
1.3.6.1.4.1.13742.6.0.1 - tacPlusError
1.3.6.1.4.1.13742.6.0.136 - testEventTriggered
1.3.6.1.4.1.13742.6.0.127 - transferSwitchSensorStateChange
1.3.6.1.4.1.13742.6.0.86 - unitSensorReset
1.3.6.1.4.1.13742.6.0.101 - unitSensorStateChange
1.3.6.1.4.1.13742.6.0.102 - unknownPeripheralDeviceAttached
1.3.6.1.4.1.13742.6.0.99 - usbExpansionUnitConnected
1.3.6.1.4.1.13742.6.0.80 - usbExpansionUnitDisconnected
1.3.6.1.4.1.13742.6.0.81 - userAcceptedRestrictedServiceAgreement
1.3.6.1.4.1.13742.6.0.83 - userAdded
1.3.6.1.4.1.13742.6.0.11 - userAuthenticationFailure
1.3.6.1.4.1.13742.6.0.5 - userBlocked
1.3.6.1.4.1.13742.6.0.22 - userDeclinedRestrictedServiceAgreement
1.3.6.1.4.1.13742.6.0.84 - userDeleted
1.3.6.1.4.1.13742.6.0.13 - userLogin
1.3.6.1.4.1.13742.6.0.3 - userLogout
1.3.6.1.4.1.13742.6.0.4 - userModified
1.3.6.1.4.1.13742.6.0.12 - userPasswordChanged
1.3.6.1.4.1.13742.6.0.24 - userRenamed
1.3.6.1.4.1.13742.6.0.138 - userSessionTimeout
1.3.6.1.4.1.13742.6.0.8 - webcamInserted
1.3.6.1.4.1.13742.6.0.90 - webcamRemoved
1.3.6.1.4.1.13742.6.0.91 - webcamStorageUploadStarted
1.3.6.1.4.1.13742.6.0.126 - wireSensorStateChange
1.3.6.1.4.1.13742.6.0.85