PDU-MIB
Raritan Computer, Inc.This mib describes the SNMP functions of the Dominion PX Power Distribution Unit by Raritan Computer.
snmptranslate -m PDU-MIB -Tpsnmpwalk -v2c -c <community> -m PDU-MIB <host> 1.3.6.1.4.1.13742Imports
| INET-ADDRESS-MIB | InetAddress, InetAddressType |
|---|---|
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP, OBJECT-GROUP |
| SNMPv2-SMI | Bits, Integer32, IpAddress, MODULE-IDENTITY, MibIdentifier, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, TimeTicks, Unsigned32, enterprises, iso |
| SNMPv2-TC | DateAndTime, DisplayString, MacAddress, PhysAddress, TEXTUAL-CONVENTION, TruthValue |
OID tree
| Name | OID | Type | Access | Status | Example | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Iraritan | 1.3.6.1.4.1.13742 | ||||||||||||||||||||
identity This mib describes the SNMP functions of the Dominion PX Power Distribution Unit by Raritan Computer. | |||||||||||||||||||||
| Npdu | 1.3.6.1.4.1.13742.4 | ||||||||||||||||||||
| Ntraps | 1.3.6.1.4.1.13742.4.0 | ||||||||||||||||||||
| !rebootStarted | 1.3.6.1.4.1.13742.4.0.1 | ||||||||||||||||||||
| !rebootCompleted | 1.3.6.1.4.1.13742.4.0.2 | ||||||||||||||||||||
| !userLogin | 1.3.6.1.4.1.13742.4.0.3 | ||||||||||||||||||||
| !userLogout | 1.3.6.1.4.1.13742.4.0.4 | ||||||||||||||||||||
| !userAuthenticationFailure | 1.3.6.1.4.1.13742.4.0.5 | ||||||||||||||||||||
notification · current A user authentication attempt failed
| |||||||||||||||||||||
| !userSessionTimeout | 1.3.6.1.4.1.13742.4.0.8 | ||||||||||||||||||||
notification · current A user timed out from the device
| |||||||||||||||||||||
| !userAdded | 1.3.6.1.4.1.13742.4.0.11 | ||||||||||||||||||||
notification · current A user was added to the system
| |||||||||||||||||||||
| !userModified | 1.3.6.1.4.1.13742.4.0.12 | ||||||||||||||||||||
notification · current A user account was modified
| |||||||||||||||||||||
| !userDeleted | 1.3.6.1.4.1.13742.4.0.13 | ||||||||||||||||||||
notification · current A user was deleted from the system
| |||||||||||||||||||||
| !groupAdded | 1.3.6.1.4.1.13742.4.0.14 | ||||||||||||||||||||
notification · current A group was added to the system
| |||||||||||||||||||||
| !groupModified | 1.3.6.1.4.1.13742.4.0.15 | ||||||||||||||||||||
| !groupDeleted | 1.3.6.1.4.1.13742.4.0.16 | ||||||||||||||||||||
notification · current A group was deleted from the system
| |||||||||||||||||||||
| !deviceUpdateStarted | 1.3.6.1.4.1.13742.4.0.20 | ||||||||||||||||||||
notification · current The device update has started
| |||||||||||||||||||||
| !userBlocked | 1.3.6.1.4.1.13742.4.0.22 | ||||||||||||||||||||
notification · current A blocked user tried to log in
| |||||||||||||||||||||
| !powerControl | 1.3.6.1.4.1.13742.4.0.23 | ||||||||||||||||||||
notification · current An outlet has been switched | |||||||||||||||||||||
| !userPasswordChanged | 1.3.6.1.4.1.13742.4.0.24 | ||||||||||||||||||||
notification · current A user password was changed
| |||||||||||||||||||||
| !passwordSettingsChanged | 1.3.6.1.4.1.13742.4.0.28 | ||||||||||||||||||||
notification · current Strong password settings changed
| |||||||||||||||||||||
| !firmwareFileDiscarded | 1.3.6.1.4.1.13742.4.0.36 | ||||||||||||||||||||
| !firmwareValidationFailed | 1.3.6.1.4.1.13742.4.0.38 | ||||||||||||||||||||
| !securityViolation | 1.3.6.1.4.1.13742.4.0.39 | ||||||||||||||||||||
| !logFileCleared | 1.3.6.1.4.1.13742.4.0.41 | ||||||||||||||||||||
| !thresholdAlarm | 1.3.6.1.4.1.13742.4.0.45 | ||||||||||||||||||||
notification · current Configured sensor theshold event. The 'thresholdEventType' variable will indicate whether or not the threshold triggered or cleared. thresholdValue and sensorValue have valid values only for external temperature and humidity sensors. | |||||||||||||||||||||
| !outletGroupingConnectivityLost | 1.3.6.1.4.1.13742.4.0.50 | ||||||||||||||||||||
notification · current Master PDU lost contact with the slave PDU in an outlet grouping configuration.
| |||||||||||||||||||||
| !circuitBreakerTripped | 1.3.6.1.4.1.13742.4.0.51 | ||||||||||||||||||||
notification · current Circuit Breaker Tripped.
| |||||||||||||||||||||
| !circuitBreakerRecovered | 1.3.6.1.4.1.13742.4.0.52 | ||||||||||||||||||||
notification · current Circuit Breaker Recovered.
| |||||||||||||||||||||
| !bulkConfigurationSaved | 1.3.6.1.4.1.13742.4.0.53 | ||||||||||||||||||||
| !bulkConfigurationCopied | 1.3.6.1.4.1.13742.4.0.54 | ||||||||||||||||||||
| !environmentalSensorsConnectivityLost | 1.3.6.1.4.1.13742.4.0.55 | ||||||||||||||||||||
notification · current lost connectivity to environmental Sensors | |||||||||||||||||||||
| !externalOnOffSensorStateChange | 1.3.6.1.4.1.13742.4.0.56 | ||||||||||||||||||||
notification · current External OnOff Sensor State Change. | |||||||||||||||||||||
| !environmentalSensorsConnectivityRestored | 1.3.6.1.4.1.13742.4.0.57 | ||||||||||||||||||||
notification · current connectivity to environmental Sensor was restored | |||||||||||||||||||||
| !voltageMeasurementError | 1.3.6.1.4.1.13742.4.0.58 | ||||||||||||||||||||
notification · current voltage measurement error, a Psoc (Outlet Controller) reported zero voltage and non-zero current. Voltage, power and energy measurements may be in error
| |||||||||||||||||||||
| !fipsModeEnabled | 1.3.6.1.4.1.13742.4.0.59 | ||||||||||||||||||||
| !fipsModeDisabled | 1.3.6.1.4.1.13742.4.0.60 | ||||||||||||||||||||
| !managingenvironmentalSensor | 1.3.6.1.4.1.13742.4.0.61 | ||||||||||||||||||||
notification · current begin managing environmental Sensor | |||||||||||||||||||||
| !unmanagingenvironmentalSensor | 1.3.6.1.4.1.13742.4.0.62 | ||||||||||||||||||||
notification · current cease managing environmental Sensor | |||||||||||||||||||||
| !ipmiOverLANEnabled | 1.3.6.1.4.1.13742.4.0.63 | ||||||||||||||||||||
notification · current IPMI Over LAN Mode has been Enabled
| |||||||||||||||||||||
| !ipmiOverLANDisabled | 1.3.6.1.4.1.13742.4.0.64 | ||||||||||||||||||||
notification · current IPMI Over LAN Mode has been Disabled
| |||||||||||||||||||||
| Nboard | 1.3.6.1.4.1.13742.4.1 | ||||||||||||||||||||
| Ninfo | 1.3.6.1.4.1.13742.4.1.1 | ||||||||||||||||||||
| SfirmwareVersion | 1.3.6.1.4.1.13742.4.1.1.1 | DisplayString | RO | ||||||||||||||||||
scalar · DisplayString · read-only · current The current firmware version in the following format: major.minor.dot.buildnumber. Example: 1.3.5.7416 | |||||||||||||||||||||
| SserialNumber | 1.3.6.1.4.1.13742.4.1.1.2 | DisplayString | RO | ||||||||||||||||||
scalar · DisplayString · read-only · current The serial number. | |||||||||||||||||||||
| SipAddress | 1.3.6.1.4.1.13742.4.1.1.3 | IpAddress | RO | ||||||||||||||||||
scalar · IpAddress · read-only · current The current IP address. A value of 0.0.0.0 indicates an error or an unset option. | |||||||||||||||||||||
| Snetmask | 1.3.6.1.4.1.13742.4.1.1.4 | IpAddress | RO | ||||||||||||||||||
scalar · IpAddress · read-only · current The current Netmask. A value of 0.0.0.0 indicates an error or an unset option. | |||||||||||||||||||||
| Sgateway | 1.3.6.1.4.1.13742.4.1.1.5 | IpAddress | RO | ||||||||||||||||||
scalar · IpAddress · read-only · current The current Gateway. A value of 0.0.0.0 indicates an error or an unset option. | |||||||||||||||||||||
| Smac | 1.3.6.1.4.1.13742.4.1.1.6 | MacAddress | RO | ||||||||||||||||||
scalar · MacAddress · read-only · current The current MAC address. | |||||||||||||||||||||
| ShardwareRev | 1.3.6.1.4.1.13742.4.1.1.7 | Integer32 (0..255) | RO | ||||||||||||||||||
scalar · Integer32 (0..255) · read-only · current The hardware revision number. | |||||||||||||||||||||
| SuserName | 1.3.6.1.4.1.13742.4.1.1.10 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current The login of a user. | |||||||||||||||||||||
| SobjectName | 1.3.6.1.4.1.13742.4.1.1.12 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current The model type of the device | |||||||||||||||||||||
| SobjectInstance | 1.3.6.1.4.1.13742.4.1.1.13 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current The device name. | |||||||||||||||||||||
| StargetUser | 1.3.6.1.4.1.13742.4.1.1.14 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current The user record being operated on | |||||||||||||||||||||
| SgroupName | 1.3.6.1.4.1.13742.4.1.1.15 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current The group record being operated on | |||||||||||||||||||||
| SimageVersion | 1.3.6.1.4.1.13742.4.1.1.18 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current The version of the Upgrade image | |||||||||||||||||||||
| SsensorDescr | 1.3.6.1.4.1.13742.4.1.1.19 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current Sensor description indicating which sensor experienced a threshold event. When applicable, the description will indicate the sensor number. | |||||||||||||||||||||
| SthresholdDescr | 1.3.6.1.4.1.13742.4.1.1.20 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current Threshold description indicating which configured threshold has been triggered (or cleared). | |||||||||||||||||||||
| SthresholdSeverity | 1.3.6.1.4.1.13742.4.1.1.21 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current String (Warning, Critical, etc...) indicating the severity of the threshold which has been triggered (or cleared). | |||||||||||||||||||||
| SthresholdEventType | 1.3.6.1.4.1.13742.4.1.1.22 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current String (triggered, cleared) indicating if the threshold event indicates that a configured threshold has been triggered or cleared. | |||||||||||||||||||||
| Sstatus | 1.3.6.1.4.1.13742.4.1.1.23 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current The success status of an operation | |||||||||||||||||||||
| SslaveIpAddress | 1.3.6.1.4.1.13742.4.1.1.24 | IpAddress | RO | ||||||||||||||||||
scalar · IpAddress · read-only · current In an outlet grouping configuration, this is the IP address of slave PDU. A value of 0.0.0.0 indicates an error or an unset option. | |||||||||||||||||||||
| SinputCurrentRating | 1.3.6.1.4.1.13742.4.1.1.25 | MilliAmps | RO | ||||||||||||||||||
scalar · MilliAmps · read-only · current The input current Rating | |||||||||||||||||||||
| SratedVoltage | 1.3.6.1.4.1.13742.4.1.1.26 | DisplayString | RO | ||||||||||||||||||
scalar · DisplayString · read-only · current PDU Rated Voltage | |||||||||||||||||||||
| SratedPower | 1.3.6.1.4.1.13742.4.1.1.27 | DisplayString | RO | ||||||||||||||||||
scalar · DisplayString · read-only · current PDU Rated Power | |||||||||||||||||||||
| SoutletSwitching | 1.3.6.1.4.1.13742.4.1.1.28 | DisplayString | RW | ||||||||||||||||||
scalar · DisplayString · read-write · current Outlet switching: enabled/disabled; for non-switched PDUs, this value can be read, but cannot be written | |||||||||||||||||||||
| SdataLogging | 1.3.6.1.4.1.13742.4.1.1.29 | DisplayString | RW | ||||||||||||||||||
scalar · DisplayString · read-write · current Data Retrieval: enabled/disabled | |||||||||||||||||||||
| SdataLoggingInterval | 1.3.6.1.4.1.13742.4.1.1.30 | Integer32 | RW | deprecated | |||||||||||||||||
scalar · Integer32 · read-write · deprecated Data Logging periodicity in seconds. This is the periodicity of the data in the buffer.
This value must be a multiple of 3 between 3 and 600. For example, 60 is valid,
but 64 is not valid
This is being deprecated in favor of measurementsPerLogEntry.
The mapping is as follows.
dataLoggingInterval measurementsPerLogEntry
3n n
Example: dataLoggingInterval is 60, so every 60 seconds (or 20th sample)
data will be placed in the data log
measurementsPerLogEntry is 20, so the data log sill store the minimum, average
and maximum of every 20 samples | |||||||||||||||||||||
| SdataCollectionInterval | 1.3.6.1.4.1.13742.4.1.1.31 | Integer32 | RO | ||||||||||||||||||
scalar · Integer32 · read-only · current Data Collection periodicity. This is the periodicity of the data collected by the PX. This value is fixed at 3 seconds. | |||||||||||||||||||||
| SoutletEnergySupport | 1.3.6.1.4.1.13742.4.1.1.32 | DisplayString | RO | ||||||||||||||||||
scalar · DisplayString · read-only · current Outlet Energy Support: Yes/No If the value is No, then outletWattHours and dataLogOutletWattHours will be zero | |||||||||||||||||||||
| ScurrentUnbalanceSupport | 1.3.6.1.4.1.13742.4.1.1.33 | DisplayString | RW | ||||||||||||||||||
scalar · DisplayString · read-write · current current Unbalance calculations Supported: Yes/No If the value is No, then currentUnbalance will be zero Default is No | |||||||||||||||||||||
| SexternalSensorsZCoordinateUnits | 1.3.6.1.4.1.13742.4.1.1.34 | DisplayString | RW | ||||||||||||||||||
scalar · DisplayString · read-write · current External Sensor Z Coordinate units: Freeform or Rack Units (U) Default is U | |||||||||||||||||||||
| SinlineMeter | 1.3.6.1.4.1.13742.4.1.1.35 | DisplayString | RO | ||||||||||||||||||
scalar · DisplayString · read-only · current Is this unit an inline meter? Yes/No If Yes, then the folowing pairings hold: Inlet 1 <-> Outlet 1 Inlet 2 <-> Outlet 2 Inlet 3 <-> Outlet 3 Inlet 4 <-> Outlet 4 Use the inletTable to obtain inlet data Use the inletPoleTable to obtain the line data for an inlet. | |||||||||||||||||||||
| SoldSensorState | 1.3.6.1.4.1.13742.4.1.1.36 | StateOfSensorEnumeration | AN | ||||||||||||||||||
scalar · StateOfSensorEnumeration · accessible-for-notify · current The old sensor state used in Sensor State Transition traps. | |||||||||||||||||||||
| SexternalSensorNumber | 1.3.6.1.4.1.13742.4.1.1.37 | Integer32 (1..256) | AN | ||||||||||||||||||
scalar · Integer32 (1..256) · accessible-for-notify · current A unique value for each sensor. Its value ranges between 1 and the value of externalSensorCount. | |||||||||||||||||||||
| SsensorIdentificationString | 1.3.6.1.4.1.13742.4.1.1.38 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current String that uniquely identifies the external sensor. Format is: SensorType,ChannelNumber,SensorSubtype,SerialNumber Example external temperature sensor: Temperature,,,AEI8160083 Example external smoke detection sensor: onOff,2,contact,AEJ8160085 Example outlet Current: rmsCurrent,,, | |||||||||||||||||||||
| SlastUpgradeStatus | 1.3.6.1.4.1.13742.4.1.1.39 | Bits | RO | ||||||||||||||||||
scalar · Bits · read-only · current A bit string which indicates which the status of the last upgrade. A value of 1 for a bit position indicates that the corresponding upgrade failed. If all bits are zero, then the upgrade succeeded; otherwise check lastUpgradeErrorDescription for further information.
| |||||||||||||||||||||
| SlastUpgradeTimestamp | 1.3.6.1.4.1.13742.4.1.1.40 | DateAndTime | RO | ||||||||||||||||||
scalar · DateAndTime · read-only · current The time when the last upgrade completed | |||||||||||||||||||||
| SlastUpgradeErrorDescription | 1.3.6.1.4.1.13742.4.1.1.41 | DisplayString | RO | ||||||||||||||||||
scalar · DisplayString · read-only · current String that describes the upgrade errror.
This is an empty string if the upgrade succeeded.
Format is
Failed PSOCs: 1[O:1,2,3-7];3[O:6-9,10-12]
This indicates that upgrade of psocs 1 and 3 failed and
psoc1 affects outlets 1,2, 3-7
and psoc2 affects outlets 6-9,10-12 | |||||||||||||||||||||
| SpowerCIMStatus | 1.3.6.1.4.1.13742.4.1.1.42 | PowerCIMStatusEnumeration | RW | ||||||||||||||||||
scalar · PowerCIMStatusEnumeration · read-write · current The status of the Power CIM: on or off | |||||||||||||||||||||
| SmeasurementsPerLogEntry | 1.3.6.1.4.1.13742.4.1.1.43 | Integer32 | RW | ||||||||||||||||||
scalar · Integer32 · read-write · current The number of measurements used for each entry in the log.
1<= Value <= 200
Default is 20
This is related to dataLoggingInterval as shown below
dataLoggingInterval measurementsPerLogEntry
3n n
Example: dataLoggingInterval is 60, so every 60 seconds (or 20th sample)
data will be placed in the data log
measurementsPerLogEntry is 20, so the data log sill store the minimum, average
and maximum of every 20 samples | |||||||||||||||||||||
| SpsocNumber | 1.3.6.1.4.1.13742.4.1.1.44 | Integer32 | AN | ||||||||||||||||||
scalar · Integer32 · accessible-for-notify · current The psoc (Outlet Controller) number | |||||||||||||||||||||
| Saltitude | 1.3.6.1.4.1.13742.4.1.1.45 | Integer32 (0..3000) | RW | ||||||||||||||||||
scalar · Integer32 (0..3000) · read-write · current The altitude (height above sea level) of the PDU in meters. 0 <= Value <= 3000; default value is 0 meters | |||||||||||||||||||||
| SconfigureAlerts | 1.3.6.1.4.1.13742.4.1.1.46 | DisplayString | RW | ||||||||||||||||||
scalar · DisplayString · read-write · current This is an operation. It has write-only semantics.
GET operation will return the empty string.
For SET operations, it configures alerts
The format is a comma separated list of the following parameters.
sensorClass, eventType, eventDirection, policyName
For sensorclass: use the SensorClass eumeration
For eventType: use the EventType enumeration
For eventDirection: use the EventDirection enumeration
For Policy Name: use the name of the policy; the Policy Name is case sensitive
Note: setting this variable will overwrite the existing policy
Example: if the External Temperature upper non-critical threshold is either asserted and deasserted,
then execute the policy named multiple destinations
the string would be
0,1,2,multiple destinations | |||||||||||||||||||||
| SfipsMode | 1.3.6.1.4.1.13742.4.1.1.47 | EnabledDisabledEnumeration | RW | ||||||||||||||||||
scalar · EnabledDisabledEnumeration · read-write · current The fips mode: either enabled or disabled. The mode can be set (changed) only if both of the following conditions hold a) the user is admin b) snmpv3 is being used. Changing this mode will result in a reboot of the PX When the PX is in FIPS mode, the follwing conditions hold. a) FIPS approved algorithms must be used b) snmp v1 & v2c are not supported b) snmp v3 must be used with AES and SHA c) https must be used; http is not supported d) Radius authentication is not supported e) Ldaps must be used; ldap is not supported f) ipmi v2.0 must be used | |||||||||||||||||||||
| SsynchronizeWithNTPServer | 1.3.6.1.4.1.13742.4.1.1.48 | EnabledDisabledEnumeration | RW | ||||||||||||||||||
scalar · EnabledDisabledEnumeration · read-write · current Will time be obtained using NTP? Deafault is disabled, i.e. time will not be obtained from NTP servers. | |||||||||||||||||||||
| SuseDHCPProvidedNTPServer | 1.3.6.1.4.1.13742.4.1.1.49 | EnabledDisabledEnumeration | RW | ||||||||||||||||||
scalar · EnabledDisabledEnumeration · read-write · current Will the NTP server addresses be provided by DHCP/BOOTP? This is used only if synchronizeWithNTPServer is enabled Default is enabled, i.e. DHCP provided NTP servers will be used | |||||||||||||||||||||
| SprimaryNTPServerAddressType | 1.3.6.1.4.1.13742.4.1.1.50 | InetAddressType | RW | ||||||||||||||||||
scalar · InetAddressType · read-write · current Represents the type of the corresponding instance of primaryNTPServerAddress object. | |||||||||||||||||||||
| SprimaryNTPServerAddress | 1.3.6.1.4.1.13742.4.1.1.51 | InetAddress | RW | ||||||||||||||||||
scalar · InetAddress · read-write · current The address of the primary ntp server. | |||||||||||||||||||||
| SsecondaryNTPServerAddressType | 1.3.6.1.4.1.13742.4.1.1.52 | InetAddressType | RW | ||||||||||||||||||
scalar · InetAddressType · read-write · current Represents the type of the corresponding instance of secondaryNTPServerAddress object. Default is ipv4 | |||||||||||||||||||||
| SsecondaryNTPServerAddress | 1.3.6.1.4.1.13742.4.1.1.53 | InetAddress | RW | ||||||||||||||||||
scalar · InetAddress · read-write · current The address of the secondary ntp server. | |||||||||||||||||||||
| SdaylightSavingsTime | 1.3.6.1.4.1.13742.4.1.1.55 | EnabledDisabledEnumeration | RW | ||||||||||||||||||
scalar · EnabledDisabledEnumeration · read-write · current Is daylight savings time enabled? Default is disabled | |||||||||||||||||||||
| SthresholdValue | 1.3.6.1.4.1.13742.4.1.1.56 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current The value of the threshold that has been triggered (or cleared). It is used in the thresholdAlarm trap for external numeric sensors only. | |||||||||||||||||||||
| SsensorValue | 1.3.6.1.4.1.13742.4.1.1.57 | DisplayString | AN | ||||||||||||||||||
scalar · DisplayString · accessible-for-notify · current The sensor reading that triggered (or cleared) the threshold. It is used in the thresholdAlarm trap for external numeric sensors only. | |||||||||||||||||||||
| SipmiOverLAN | 1.3.6.1.4.1.13742.4.1.1.58 | EnabledDisabledEnumeration | RW | ||||||||||||||||||
scalar · EnabledDisabledEnumeration · read-write · current IPMI over LAN Mode: either enabled or disabled. It is strongly recommended that SNMPv3 be used to change the mode; SNMPv2c may also be used, but is not recommended. If SNMPv3 is used, then the change can be made only by users belonging to the Admin group. Changing the mode will result in a reboot of the PX. | |||||||||||||||||||||
| Noutlets | 1.3.6.1.4.1.13742.4.1.2 | ||||||||||||||||||||
| SoutletCount | 1.3.6.1.4.1.13742.4.1.2.1 | Integer32 | RO | ||||||||||||||||||
scalar · Integer32 · read-only · current The number of outlets (regardless of their current state) present on this pdu. | |||||||||||||||||||||
| ToutletTable | 1.3.6.1.4.1.13742.4.1.2.2 | NA | |||||||||||||||||||
table · not-accessible · current A list of outlet entries. The number of entries is given by the value of outletCount. | |||||||||||||||||||||
| RoutletEntry | 1.3.6.1.4.1.13742.4.1.2.2.1 | NA | |||||||||||||||||||
row · not-accessible · current An outlet entry containing objects at the for a particular outlet.
| |||||||||||||||||||||
| CoutletIndex | 1.3.6.1.4.1.13742.4.1.2.2.1.1 | Integer32 (1..256) | NA | 1 | |||||||||||||||||
column · Integer32 (1..256) · not-accessible · current A unique value for each outlet. Its value ranges between 1 and the value of outletCount. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletLabel | 1.3.6.1.4.1.13742.4.1.2.2.1.2 | DisplayString | RW | OUTLET1 | |||||||||||||||||
column · DisplayString · read-write · current A textual string containing information about the outlet. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletOperationalState | 1.3.6.1.4.1.13742.4.1.2.2.1.3 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current A value for each outlet which describes the operational state of the outlet. It is also used to set the operational state of the outlet
| |||||||||||||||||||||
| CoutletCurrent | 1.3.6.1.4.1.13742.4.1.2.2.1.4 | MilliAmps | RO | 0 | |||||||||||||||||
column · MilliAmps · read-only · current A unique value for the current sensor attached to the outlet. This value is reported in milliamps (1/1000th of an amp) Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletMaxCurrent | 1.3.6.1.4.1.13742.4.1.2.2.1.5 | MilliAmps | RO | ||||||||||||||||||
column · MilliAmps · read-only · current A unique value for the max. current sensor attached to the outlet. This value is reported in milliamps (1/1000th of an amp) | |||||||||||||||||||||
| CoutletVoltage | 1.3.6.1.4.1.13742.4.1.2.2.1.6 | MilliVolts | RO | ||||||||||||||||||
column · MilliVolts · read-only · current A unique value for the voltage sensor attached to the outlet.This value is reported in millivolts (1/1000th of a volt) | |||||||||||||||||||||
| CoutletActivePower | 1.3.6.1.4.1.13742.4.1.2.2.1.7 | Watts | RO | ||||||||||||||||||
column · Watts · read-only · current A unique value for the active power sensor attached to the outlet. This value is reported in Watts. | |||||||||||||||||||||
| CoutletApparentPower | 1.3.6.1.4.1.13742.4.1.2.2.1.8 | VoltAmps | RO | 0 | |||||||||||||||||
column · VoltAmps · read-only · current A unique value for the apparent power sensor attached to the outlet. This value is reported in Volt-Amps Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletPowerFactor | 1.3.6.1.4.1.13742.4.1.2.2.1.9 | PowerFactorPercentage | RO | ||||||||||||||||||
column · PowerFactorPercentage · read-only · current A unique value for the power factor of the outlet. The reading represents a percentage in the range of 0% to 100%. | |||||||||||||||||||||
| CoutletCurrentUpperWarning | 1.3.6.1.4.1.13742.4.1.2.2.1.20 | MilliAmps | RW | 6039 | |||||||||||||||||
column · MilliAmps · read-write · current The value of the upper warning (non-critical) current threshold for the outlet. This value is reported in milliamps (1/1000th of an amp) Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletCurrentUpperCritical | 1.3.6.1.4.1.13742.4.1.2.2.1.21 | MilliAmps | RW | 7979 | |||||||||||||||||
column · MilliAmps · read-write · current The value of the upper critical current threshold for the outlet. This value is reported in milliamps (1/1000th of an amp) Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletCurrentLowerWarning | 1.3.6.1.4.1.13742.4.1.2.2.1.22 | MilliAmps | RW | 1981 | |||||||||||||||||
column · MilliAmps · read-write · current The value of the lower warning (non-critical) current threshold for the outlet. This value is reported in milliamps (1/1000th of an amp) Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletCurrentLowerCritical | 1.3.6.1.4.1.13742.4.1.2.2.1.23 | MilliAmps | RW | 1000 | |||||||||||||||||
column · MilliAmps · read-write · current The value of the lower critical current threshold for the outlet. This value is reported in milliamps (1/1000th of an amp) Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletCurrentHysteresis | 1.3.6.1.4.1.13742.4.1.2.2.1.24 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The hysteresis used for deassertions. This value is reported in milliamps (1/1000th of an amp) | |||||||||||||||||||||
| CoutletCurrentRating | 1.3.6.1.4.1.13742.4.1.2.2.1.30 | MilliAmps | RO | ||||||||||||||||||
column · MilliAmps · read-only · current The current rating of the outlet. This value is reported in milliamps (1/1000th of an amp) | |||||||||||||||||||||
| CoutletWattHours | 1.3.6.1.4.1.13742.4.1.2.2.1.31 | WattHours | RO | ||||||||||||||||||
column · WattHours · read-only · current The value of the cumulative active energy for this outlet. This value is reported in WattHours | |||||||||||||||||||||
| Nunit | 1.3.6.1.4.1.13742.4.1.3 | ||||||||||||||||||||
| NunitReadings | 1.3.6.1.4.1.13742.4.1.3.1 | ||||||||||||||||||||
| SunitCurrent | 1.3.6.1.4.1.13742.4.1.3.1.1 | MilliAmps | RO | deprecated | |||||||||||||||||
scalar · MilliAmps · read-only · deprecated The value for the unit's current sensor in millamps.This object is deprecated in favour of lineCurrent corresponding to lineCurrentLabel = L1 | |||||||||||||||||||||
| SunitVoltage | 1.3.6.1.4.1.13742.4.1.3.1.2 | MilliVolts | RO | deprecated | |||||||||||||||||
scalar · MilliVolts · read-only · deprecated The value for the unit's voltage sensor in millivolts.This object is deprecated in favour of lineVoltage corresponding to lineVoltageLabel = L1 | |||||||||||||||||||||
| SunitActivePower | 1.3.6.1.4.1.13742.4.1.3.1.3 | Watts | RO | deprecated | |||||||||||||||||
scalar · Watts · read-only · deprecated The value for the unit's active power in watts.This object is deprecated in favour of inletTable.inletActivePower | |||||||||||||||||||||
| SunitApparentPower | 1.3.6.1.4.1.13742.4.1.3.1.4 | VoltAmps | RO | deprecated | |||||||||||||||||
scalar · VoltAmps · read-only · deprecated The value for the unit's apparent power in volt-amps. This object is deprecated in favour of inletTable.inletApparentPower | |||||||||||||||||||||
| SunitCpuTemp | 1.3.6.1.4.1.13742.4.1.3.1.5 | TenthDegreesCelsius | RO | 360 | |||||||||||||||||
scalar · TenthDegreesCelsius · read-only · current The value for the unit's CPU temperature sensor in tenth degrees celsius. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SunitVoltageLowerWarning | 1.3.6.1.4.1.13742.4.1.3.1.60 | MilliVolts | RW | deprecated | |||||||||||||||||
scalar · MilliVolts · read-write · deprecated The value of the lower warning (non-critical) unit level voltage threshold.This object is deprecated in favour of unitOrLineVoltageLowerWarning | |||||||||||||||||||||
| SunitVoltageLowerCritical | 1.3.6.1.4.1.13742.4.1.3.1.61 | MilliVolts | RW | deprecated | |||||||||||||||||
scalar · MilliVolts · read-write · deprecated The value of the lower critical unit level voltage threshold.This object is deprecated in favour of unitOrLineVoltageLowerCritical | |||||||||||||||||||||
| SunitVoltageUpperWarning | 1.3.6.1.4.1.13742.4.1.3.1.62 | MilliVolts | RW | deprecated | |||||||||||||||||
scalar · MilliVolts · read-write · deprecated The value of the upper warning (non-critical) unit level voltage threshold.This object is deprecated in favour of unitOrLineVoltageUpperWarning | |||||||||||||||||||||
| SunitVoltageUpperCritical | 1.3.6.1.4.1.13742.4.1.3.1.63 | MilliVolts | RW | deprecated | |||||||||||||||||
scalar · MilliVolts · read-write · deprecated The value of the upper critical unit level voltage threshold.This object is deprecated in favour of unitOrLineVoltageUpperCritical | |||||||||||||||||||||
| SunitCurrentUpperWarning | 1.3.6.1.4.1.13742.4.1.3.1.70 | MilliAmps | RW | deprecated | |||||||||||||||||
scalar · MilliAmps · read-write · deprecated The value of the upper warning (non-critical) unit level current threshold.This object is deprecated in favour of unitOrLineCurrentUpperWarning | |||||||||||||||||||||
| SunitCurrentUpperCritical | 1.3.6.1.4.1.13742.4.1.3.1.71 | MilliAmps | RO | deprecated | |||||||||||||||||
scalar · MilliAmps · read-only · deprecated The value of the upper critical unit level current threshold. NOTE: This particular threshold is NOT settable. This object is deprecated in favour of unitOrLineCurrentUpperCritica | |||||||||||||||||||||
| SunitTempLowerWarning | 1.3.6.1.4.1.13742.4.1.3.1.80 | DegreesCelsius | RW | 20 | |||||||||||||||||
scalar · DegreesCelsius · read-write · current The value of the lower warning (non-critical) unit level temperature threshold. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SunitTempLowerCritical | 1.3.6.1.4.1.13742.4.1.3.1.81 | DegreesCelsius | RW | 18 | |||||||||||||||||
scalar · DegreesCelsius · read-write · current The value of the lower critical unit level temperature threshold. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SunitTempUpperWarning | 1.3.6.1.4.1.13742.4.1.3.1.82 | DegreesCelsius | RW | 65 | |||||||||||||||||
scalar · DegreesCelsius · read-write · current The value of the upper warning (non-critical) unit level temperature threshold. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SunitTempUpperCritical | 1.3.6.1.4.1.13742.4.1.3.1.83 | DegreesCelsius | RW | 80 | |||||||||||||||||
scalar · DegreesCelsius · read-write · current The value of the upper critical unit level temperature threshold. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ScurrentUnbalance | 1.3.6.1.4.1.13742.4.1.3.1.84 | DisplayString | RO | ||||||||||||||||||
scalar · DisplayString · read-only · current A string displaying the current unbalance in percent. It will have the value NA if the PX is not a 3-phase unit (inletPoleCount = 1),or the feature is disabled (currentUnbalanceSupport = 'No'), or the average of the line currents is zero (inletPoleCurrent = 0 for 1 <= inlePoleIndex <= 3) | |||||||||||||||||||||
| ScurrentUnbalanceUpperWarning | 1.3.6.1.4.1.13742.4.1.3.1.85 | Percentage | RW | ||||||||||||||||||
scalar · Percentage · read-write · current The value of the upper warning (non-critical) current unbalance threshold. | |||||||||||||||||||||
| ScurrentUnbalanceUpperCritical | 1.3.6.1.4.1.13742.4.1.3.1.86 | Percentage | RW | ||||||||||||||||||
scalar · Percentage · read-write · current The value of the upper critical current Unbalance threshold. | |||||||||||||||||||||
| SunitOrLineVoltageLowerWarning | 1.3.6.1.4.1.13742.4.1.3.1.90 | MilliVolts | RW | ||||||||||||||||||
scalar · MilliVolts · read-write · current The value of the lower warning (non-critical) unit level voltage threshold. | |||||||||||||||||||||
| SunitOrLineVoltageLowerCritical | 1.3.6.1.4.1.13742.4.1.3.1.91 | MilliVolts | RW | ||||||||||||||||||
scalar · MilliVolts · read-write · current The value of the lower critical unit level voltage threshold. | |||||||||||||||||||||
| SunitOrLineVoltageUpperWarning | 1.3.6.1.4.1.13742.4.1.3.1.92 | MilliVolts | RW | ||||||||||||||||||
scalar · MilliVolts · read-write · current The value of the upper warning (non-critical) unit level voltage | |||||||||||||||||||||
| SunitOrLineVoltageUpperCritical | 1.3.6.1.4.1.13742.4.1.3.1.93 | MilliVolts | RW | ||||||||||||||||||
scalar · MilliVolts · read-write · current The value of the upper critical unit level voltage threshold. | |||||||||||||||||||||
| SunitOrLineCurrentUpperWarning | 1.3.6.1.4.1.13742.4.1.3.1.94 | MilliAmps | RW | ||||||||||||||||||
scalar · MilliAmps · read-write · current The value of the upper warning (non-critical) unit level current threshold | |||||||||||||||||||||
| SunitOrLineCurrentUpperCritical | 1.3.6.1.4.1.13742.4.1.3.1.95 | MilliAmps | RW | ||||||||||||||||||
scalar · MilliAmps · read-write · current The value of the upper critical unit level current threshold. | |||||||||||||||||||||
| SneutralCurrentUpperWarning | 1.3.6.1.4.1.13742.4.1.3.1.96 | MilliAmps | RW | ||||||||||||||||||
scalar · MilliAmps · read-write · current This object has an invalid value if inletPoleCount is not equal to 4. If inletPoleCount = 4, then it is the value of the upper warning (non-critical) threshold for the neutral current | |||||||||||||||||||||
| SneutralCurrentUpperCritical | 1.3.6.1.4.1.13742.4.1.3.1.97 | MilliAmps | RW | ||||||||||||||||||
scalar · MilliAmps · read-write · current This object has an invalid value if inletPoleCount is not equal to 4. If inletPoleCount = 4, then it is the value of the upper critical threshold for the neutral current. | |||||||||||||||||||||
| SunitOrLineCurrentHysteresis | 1.3.6.1.4.1.13742.4.1.3.1.98 | Unsigned32 | RW | ||||||||||||||||||
scalar · Unsigned32 · read-write · current The hysteresis used for deassertions. This value is reported in milliamps (1/1000th of an amp) | |||||||||||||||||||||
| SunitOrLineVoltageHysteresis | 1.3.6.1.4.1.13742.4.1.3.1.99 | Unsigned32 | RW | ||||||||||||||||||
scalar · Unsigned32 · read-write · current The hysteresis used for deassertions. This value is reported in millivolts (1/1000th of a volt) | |||||||||||||||||||||
| SunitTempHysteresis | 1.3.6.1.4.1.13742.4.1.3.1.100 | Unsigned32 | RW | ||||||||||||||||||
scalar · Unsigned32 · read-write · current The hysteresis used for deassertions | |||||||||||||||||||||
| ScurrentUnbalanceHysteresis | 1.3.6.1.4.1.13742.4.1.3.1.101 | Unsigned32 | RW | ||||||||||||||||||
scalar · Unsigned32 · read-write · current The hysteresis used for deassertions | |||||||||||||||||||||
| NlineCurrents | 1.3.6.1.4.1.13742.4.1.4 | ||||||||||||||||||||
| SlineCurrentCount | 1.3.6.1.4.1.13742.4.1.4.1 | Integer32 | RO | deprecated | |||||||||||||||||
scalar · Integer32 · read-only · deprecated The number of line currents (1 for single phase, 3 for 3 phase Delta-wired, 4 for 3 phase WYE wired).This object is deprecated in favour of inletPoleTable | |||||||||||||||||||||
| TlineCurrentTable | 1.3.6.1.4.1.13742.4.1.4.2 | NA | deprecated | ||||||||||||||||||
table · not-accessible · deprecated A list of line input entries. The number of entries is given by the value of lineInputCount. This object is deprecated in favour of inletPoleTable | |||||||||||||||||||||
| RlineCurrentEntry | 1.3.6.1.4.1.13742.4.1.4.2.1 | NA | deprecated | ||||||||||||||||||
row · not-accessible · deprecated An entry containing values and threshold settings for a particular line input.This object is deprecated in favour of inletPoleTable
| |||||||||||||||||||||
| ClineCurrentIndex | 1.3.6.1.4.1.13742.4.1.4.2.1.1 | Integer32 (1..256) | NA | deprecated | |||||||||||||||||
column · Integer32 (1..256) · not-accessible · deprecated A unique value for each line input. Its value ranges between 1 and lineInputCount. This object is deprecated in favour of inletPoleTable | |||||||||||||||||||||
| ClineCurrentLabel | 1.3.6.1.4.1.13742.4.1.4.2.1.2 | DisplayString | RO | deprecated | |||||||||||||||||
column · DisplayString · read-only · deprecated A string identifying the Line For Single Phase: L1 For 3phase Delta wired outlets: L1, L2, L3 For 3phase WYE Wired Outlets: L1, L2, L3, N This object is deprecated in favour of inletPoleTable | |||||||||||||||||||||
| ClineCurrent | 1.3.6.1.4.1.13742.4.1.4.2.1.3 | MilliAmps | RO | deprecated | |||||||||||||||||
column · MilliAmps · read-only · deprecated The value of the current reported in MilliAmps. This object is deprecated in favour of inletPoleTable | |||||||||||||||||||||
| NcircuitBreaker | 1.3.6.1.4.1.13742.4.1.5 | ||||||||||||||||||||
| ScircuitBreakerCount | 1.3.6.1.4.1.13742.4.1.5.1 | Integer32 | RO | ||||||||||||||||||
scalar · Integer32 · read-only · current The number of circuit breakers. | |||||||||||||||||||||
| TcircuitBreakerTable | 1.3.6.1.4.1.13742.4.1.5.2 | NA | |||||||||||||||||||
table · not-accessible · current A list of line input entries. The number of entries is given by the value of lineInputCount. | |||||||||||||||||||||
| RcircuitBreakerEntry | 1.3.6.1.4.1.13742.4.1.5.2.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing values and threshold settings for a particular line input.
| |||||||||||||||||||||
| CcircuitBreakerIndex | 1.3.6.1.4.1.13742.4.1.5.2.1.1 | Integer32 (1..256) | NA | ||||||||||||||||||
column · Integer32 (1..256) · not-accessible · current A unique value for each circuit breaker. Its value ranges between 1 and circuitBreakerCount. | |||||||||||||||||||||
| CcircuitBreakerLabel | 1.3.6.1.4.1.13742.4.1.5.2.1.2 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current A string identifying the circuit breaker | |||||||||||||||||||||
| CcircuitBreakerState | 1.3.6.1.4.1.13742.4.1.5.2.1.3 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current The value for the circuit breaker state .
| |||||||||||||||||||||
| CcircuitBreakerCurrentRating | 1.3.6.1.4.1.13742.4.1.5.2.1.4 | MilliAmps | RO | ||||||||||||||||||
column · MilliAmps · read-only · current The value of the circuit breaker current rating in MilliAmps. | |||||||||||||||||||||
| CcircuitBreakerCurrent | 1.3.6.1.4.1.13742.4.1.5.2.1.5 | MilliAmps | RO | ||||||||||||||||||
column · MilliAmps · read-only · current The value of the current reported in MilliAmps. | |||||||||||||||||||||
| CcircuitBreakerCurrentUpperWarning | 1.3.6.1.4.1.13742.4.1.5.2.1.7 | MilliAmps | RW | ||||||||||||||||||
column · MilliAmps · read-write · current The value of the upper warning (non-critical) threshold. | |||||||||||||||||||||
| CcircuitBreakerCurrentUpperCritical | 1.3.6.1.4.1.13742.4.1.5.2.1.9 | MilliAmps | RW | ||||||||||||||||||
column · MilliAmps · read-write · current The value of the upper critical threshold. | |||||||||||||||||||||
| CcircuitBreakerCurrentHysteresis | 1.3.6.1.4.1.13742.4.1.5.2.1.10 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The hysteresis used for deassertions reported in milliamps (1/1000th of an amp) | |||||||||||||||||||||
| NlineVoltages | 1.3.6.1.4.1.13742.4.1.6 | ||||||||||||||||||||
| SlineVoltageCount | 1.3.6.1.4.1.13742.4.1.6.1 | Integer32 | RO | deprecated | |||||||||||||||||
scalar · Integer32 · read-only · deprecated The number of line voltages (1 for single phase, 3 for 3 phase. This object is deprecated in favour of inletPoleTable | |||||||||||||||||||||
| TlineVoltageTable | 1.3.6.1.4.1.13742.4.1.6.2 | NA | deprecated | ||||||||||||||||||
table · not-accessible · deprecated A list of line input entries. The number of entries is given by the value of lineInputCount. This object is deprecated in favour of linletPoleTable | |||||||||||||||||||||
| RlineVoltageEntry | 1.3.6.1.4.1.13742.4.1.6.2.1 | NA | deprecated | ||||||||||||||||||
row · not-accessible · deprecated An entry containing values and threshold settings for a particular line input. This object is deprecated in favour of inletPoleTable
| |||||||||||||||||||||
| ClineVoltageIndex | 1.3.6.1.4.1.13742.4.1.6.2.1.1 | Integer32 (1..256) | NA | deprecated | |||||||||||||||||
column · Integer32 (1..256) · not-accessible · deprecated A unique value for each line input. Its value ranges between 1 and lineInputCount. This object is deprecated in favour of inletPoleTable | |||||||||||||||||||||
| ClineVoltageLabel | 1.3.6.1.4.1.13742.4.1.6.2.1.2 | DisplayString | RO | deprecated | |||||||||||||||||
column · DisplayString · read-only · deprecated A string identifying the Line For Single Phase: L1 For 3phase Delta-wired: L1-L2, L2-L3, L3-L1 For 3phase Wye-wired: L1-N, L2-N, L3-N This object is deprecated in favour of inletPoleTable | |||||||||||||||||||||
| ClineVoltage | 1.3.6.1.4.1.13742.4.1.6.2.1.3 | MilliVolts | RO | deprecated | |||||||||||||||||
column · MilliVolts · read-only · deprecated The value of the voltage reported in MilliVolts. This object is deprecated in favour of inletPoleTable | |||||||||||||||||||||
| NdataLog | 1.3.6.1.4.1.13742.4.1.7 | ||||||||||||||||||||
| SdataLogCount | 1.3.6.1.4.1.13742.4.1.7.1 | Integer32 | RO | ||||||||||||||||||
scalar · Integer32 · read-only · current The number of entries in the dataLog table which is a circular buffer. | |||||||||||||||||||||
| SdataLogLatestIndex | 1.3.6.1.4.1.13742.4.1.7.2 | Integer32 (1..256) | RO | ||||||||||||||||||
scalar · Integer32 (1..256) · read-only · current The index of the latest (most recent) entry in dataLogTable . | |||||||||||||||||||||
| TdataLogTable | 1.3.6.1.4.1.13742.4.1.7.3 | NA | |||||||||||||||||||
table · not-accessible · current A list of data log entries. The number of entries is given by the value of dataLogCount. | |||||||||||||||||||||
| RdataLogEntry | 1.3.6.1.4.1.13742.4.1.7.3.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry in the dataLog buffer containing the unit data collected at the instant specified by dataLogTimeStamp
| |||||||||||||||||||||
| CdataLogIndex | 1.3.6.1.4.1.13742.4.1.7.3.1.1 | Integer32 (1..256) | NA | ||||||||||||||||||
column · Integer32 (1..256) · not-accessible · current A unique value for each data sample. Its value ranges between 1 and dataLogCount . | |||||||||||||||||||||
| CdataLogTimeStamp | 1.3.6.1.4.1.13742.4.1.7.3.1.2 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The time when the data was collected. It is measured in seconds relative to January 1, 1970 (midnight UTC/GMT), i.e a value of 0 indicates January 1, 1970 (midnight UTC/GMT) | |||||||||||||||||||||
| CdataLogActivePower | 1.3.6.1.4.1.13742.4.1.7.3.1.3 | Watts | RO | deprecated | |||||||||||||||||
column · Watts · read-only · deprecated The value for the pdu's active power sensor in watts. This has been deprecated in favor of dataLogAvgActivePower, dataLogMaxActivePower,dataLogMinActivePower | |||||||||||||||||||||
| CdataLogApparentPower | 1.3.6.1.4.1.13742.4.1.7.3.1.4 | VoltAmps | RO | deprecated | |||||||||||||||||
column · VoltAmps · read-only · deprecated The value for the pdu's apparent power sensor in volt-amps. This has been deprecated in favor of dataLogAvgApparentPower, dataLogMaxApparentPower,dataLogMinApparentPower | |||||||||||||||||||||
| CdataLogAvgActivePower | 1.3.6.1.4.1.13742.4.1.7.3.1.5 | Watts | RO | ||||||||||||||||||
column · Watts · read-only · current The average active power for this measurement period | |||||||||||||||||||||
| CdataLogMaxActivePower | 1.3.6.1.4.1.13742.4.1.7.3.1.6 | Watts | RO | ||||||||||||||||||
column · Watts · read-only · current The maximum active power for this measurement period | |||||||||||||||||||||
| CdataLogMinActivePower | 1.3.6.1.4.1.13742.4.1.7.3.1.7 | Watts | RO | ||||||||||||||||||
column · Watts · read-only · current The minimum active power for this measurement period | |||||||||||||||||||||
| CdataLogAvgApparentPower | 1.3.6.1.4.1.13742.4.1.7.3.1.8 | VoltAmps | RO | ||||||||||||||||||
column · VoltAmps · read-only · current The average apparent power for this measurement period | |||||||||||||||||||||
| CdataLogMaxApparentPower | 1.3.6.1.4.1.13742.4.1.7.3.1.9 | VoltAmps | RO | ||||||||||||||||||
column · VoltAmps · read-only · current The maximum apparent power for this measurement period | |||||||||||||||||||||
| CdataLogMinApparentPower | 1.3.6.1.4.1.13742.4.1.7.3.1.10 | VoltAmps | RO | ||||||||||||||||||
column · VoltAmps · read-only · current The minimum apparent power for this measurement period | |||||||||||||||||||||
| NdataLogOutlet | 1.3.6.1.4.1.13742.4.1.10 | ||||||||||||||||||||
| TdataLogOutletTable | 1.3.6.1.4.1.13742.4.1.10.1 | NA | |||||||||||||||||||
table · not-accessible · current A list of outlet entries. The number of entries is given by the value of outletCount. | |||||||||||||||||||||
| RdataLogOutletEntry | 1.3.6.1.4.1.13742.4.1.10.1.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry in the data log containing outlet level data for a particular outlet. | |||||||||||||||||||||
| CdataLogOutletIndex | 1.3.6.1.4.1.13742.4.1.10.1.1.1 | Integer32 (1..256) | NA | ||||||||||||||||||
column · Integer32 (1..256) · not-accessible · current A unique value for each outlet. Its value ranges between 1 and the value of outletCount. | |||||||||||||||||||||
| CdataLogOutletCurrent | 1.3.6.1.4.1.13742.4.1.10.1.1.2 | MilliAmps | RO | deprecated | |||||||||||||||||
column · MilliAmps · read-only · deprecated A unique value for the current sensor attached to the outlet. This value is reported in milliamps (1/1000th of an amp) This has been deprecated in favor of dataLogAvgOutletCurrent , dataLogMaxOutletCurrent ,dataLogMinOutletCurrent | |||||||||||||||||||||
| CdataLogOutletVoltage | 1.3.6.1.4.1.13742.4.1.10.1.1.3 | MilliVolts | RO | deprecated | |||||||||||||||||
column · MilliVolts · read-only · deprecated A unique value for the voltage sensor attached to the outlet.This value is reported in millivolts (1/1000th of a volt) This has been deprecated in favor of dataLogAvgOutletVoltage , dataLogMaxOutletVoltage ,dataLogMinOutletVoltage | |||||||||||||||||||||
| CdataLogOutletPowerFactor | 1.3.6.1.4.1.13742.4.1.10.1.1.4 | PowerFactorPercentage | RO | deprecated | |||||||||||||||||
column · PowerFactorPercentage · read-only · deprecated A unique value for the power factor of the outlet. The reading represents a percentage in the range of 0% to 100%. This has been deprecated in favor of dataLogAvgOutletPowerFactor, dataLogMaxOutletPowerFactor,dataLogMinOutletPowerFactor | |||||||||||||||||||||
| CdataLogOutletOnTime | 1.3.6.1.4.1.13742.4.1.10.1.1.5 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The amount of time since this outlet was last switched on. This value is reported in seconds. | |||||||||||||||||||||
| CdataLogOutletWattHours | 1.3.6.1.4.1.13742.4.1.10.1.1.6 | WattHours | RO | deprecated | |||||||||||||||||
column · WattHours · read-only · deprecated The cumulative Active Energy for this outlet. This value is reported in WattHours This has been deprecated in favor of dataLogAvgOutletWattHours , dataLogMaxOutletWattHours ,dataLogMinOutletWattHours | |||||||||||||||||||||
| CdataLogAvgOutletCurrent | 1.3.6.1.4.1.13742.4.1.10.1.1.7 | MilliAmps | RO | ||||||||||||||||||
column · MilliAmps · read-only · current The Average value for the measurement period: A unique value for the current sensor attached to the outlet. This value is reported in milliamps (1/1000th of an amp) | |||||||||||||||||||||
| CdataLogMaxOutletCurrent | 1.3.6.1.4.1.13742.4.1.10.1.1.8 | MilliAmps | RO | ||||||||||||||||||
column · MilliAmps · read-only · current The Maximum value for the measurement period: A unique value for the current sensor attached to the outlet. This value is reported in milliamps (1/1000th of an amp) | |||||||||||||||||||||
| CdataLogMinOutletCurrent | 1.3.6.1.4.1.13742.4.1.10.1.1.9 | MilliAmps | RO | ||||||||||||||||||
column · MilliAmps · read-only · current The Minimum value for the measurement period: A unique value for the current sensor attached to the outlet. This value is reported in milliamps (1/1000th of an amp) | |||||||||||||||||||||
| CdataLogAvgOutletVoltage | 1.3.6.1.4.1.13742.4.1.10.1.1.10 | MilliVolts | RO | ||||||||||||||||||
column · MilliVolts · read-only · current The Average value for the measurement period: A unique value for the voltage sensor attached to the outlet.This value is reported in millivolts (1/1000th of a volt) | |||||||||||||||||||||
| CdataLogMaxOutletVoltage | 1.3.6.1.4.1.13742.4.1.10.1.1.11 | MilliVolts | RO | ||||||||||||||||||
column · MilliVolts · read-only · current The Maximum value for the measurement period: A unique value for the voltage sensor attached to the outlet.This value is reported in millivolts (1/1000th of a volt) | |||||||||||||||||||||
| CdataLogMinOutletVoltage | 1.3.6.1.4.1.13742.4.1.10.1.1.12 | MilliVolts | RO | ||||||||||||||||||
column · MilliVolts · read-only · current The Minimum value for the measurement period: A unique value for the voltage sensor attached to the outlet.This value is reported in millivolts (1/1000th of a volt) | |||||||||||||||||||||
| CdataLogAvgOutletPowerFactor | 1.3.6.1.4.1.13742.4.1.10.1.1.13 | PowerFactorPercentage | RO | ||||||||||||||||||
column · PowerFactorPercentage · read-only · current The Average value for the measurement period: A unique value for the power factor of the outlet. The reading represents a percentage in the range of 0% to 100% | |||||||||||||||||||||
| CdataLogMaxOutletPowerFactor | 1.3.6.1.4.1.13742.4.1.10.1.1.14 | PowerFactorPercentage | RO | ||||||||||||||||||
column · PowerFactorPercentage · read-only · current The Maximum value for the measurement period: A unique value for the power factor of the outlet. The reading represents a percentage in the range of 0% to 100% | |||||||||||||||||||||
| CdataLogMinOutletPowerFactor | 1.3.6.1.4.1.13742.4.1.10.1.1.15 | PowerFactorPercentage | RO | ||||||||||||||||||
column · PowerFactorPercentage · read-only · current The Minimum value for the measurement period: A unique value for the power factor of the outlet. The reading represents a percentage in the range of 0% to 100% | |||||||||||||||||||||
| CdataLogAvgOutletWattHours | 1.3.6.1.4.1.13742.4.1.10.1.1.16 | WattHours | RO | ||||||||||||||||||
column · WattHours · read-only · current The Average value for the measurement period: The cumulative Active Energy for this outlet. This value is reported in WattHours | |||||||||||||||||||||
| CdataLogMaxOutletWattHours | 1.3.6.1.4.1.13742.4.1.10.1.1.17 | WattHours | RO | ||||||||||||||||||
column · WattHours · read-only · current The Maximum value for the measurement period: The cumulative Active Energy for this outlet. This value is reported in WattHours | |||||||||||||||||||||
| CdataLogMinOutletWattHours | 1.3.6.1.4.1.13742.4.1.10.1.1.18 | WattHours | RO | ||||||||||||||||||
column · WattHours · read-only · current The Minimum value for the measurement period: The cumulative Active Energy for this outlet. This value is reported in WattHours | |||||||||||||||||||||
| NdataLogInlet | 1.3.6.1.4.1.13742.4.1.12 | ||||||||||||||||||||
| TdataLogInletTable | 1.3.6.1.4.1.13742.4.1.12.2 | NA | |||||||||||||||||||
table · not-accessible · current A list of inlet entries. The number of entries is given by the value of inletCount. | |||||||||||||||||||||
| RdataLogInletEntry | 1.3.6.1.4.1.13742.4.1.12.2.1 | NA | |||||||||||||||||||
row · not-accessible · current An inlet entry containing objects at the for a particular outlet. | |||||||||||||||||||||
| CdataLogInletIndex | 1.3.6.1.4.1.13742.4.1.12.2.1.1 | Integer32 (1..256) | NA | ||||||||||||||||||
column · Integer32 (1..256) · not-accessible · current A unique value for each inlet. Its value ranges between 1 and the value of inletCount. | |||||||||||||||||||||
| CdataLogInletCurrentUnbalance | 1.3.6.1.4.1.13742.4.1.12.2.1.10 | DisplayString | RO | deprecated | |||||||||||||||||
column · DisplayString · read-only · deprecated A string displaying the current unbalance in percent. It will have the value NA if the feature is disabled, the PX is not a 3-phase unit,or the average of the line currents is zero This has been deprecated in favor of dataLogAvgInletCurrentUnbalance, dataLogMaxInletCurrentUnbalance, dataLogMinInletCurrentUnbalance | |||||||||||||||||||||
| CdataLogInletActivePower | 1.3.6.1.4.1.13742.4.1.12.2.1.11 | Watts | RO | deprecated | |||||||||||||||||
column · Watts · read-only · deprecated The active power for the inlet This value is reported in Watts. This has been deprecated in favor of dataLogAvgInletActivePower, dataLogMaxInletActivePower, dataLogMinInletActivePower | |||||||||||||||||||||
| CdataLogInletApparentPower | 1.3.6.1.4.1.13742.4.1.12.2.1.12 | VoltAmps | RO | deprecated | |||||||||||||||||
column · VoltAmps · read-only · deprecated The apparent power for the inlet. This value is reported in Volt-Amps This has been deprecated in favor of dataLogAvgInletApparentPower, dataLogMaxInletApparentPower, dataLogMinInletApparentPower | |||||||||||||||||||||
| CdataLogInletActiveEnergy | 1.3.6.1.4.1.13742.4.1.12.2.1.13 | WattHours | RO | deprecated | |||||||||||||||||
column · WattHours · read-only · deprecated The value of the cumulative active energy for this inlet. This value is reported in WattHours This has been deprecated in favor of dataLogAvgInletActiveEnergy, dataLogMaxInletActiveEnergy, dataLogMinInletActiveEnergy | |||||||||||||||||||||
| CdataLogAvgInletCurrentUnbalance | 1.3.6.1.4.1.13742.4.1.12.2.1.14 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current The average value of the current unbalance for this measurement period A string displaying the current unbalance in percent. It will have the value NA if the feature is disabled, the PX is not a 3-phase unit,or the average of the line currents is zero | |||||||||||||||||||||
| CdataLogMaxInletCurrentUnbalance | 1.3.6.1.4.1.13742.4.1.12.2.1.15 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current The Maximum value for the measurement period: A string displaying the current unbalance in percent. It will have the value NA if the feature is disabled, the PX is not a 3-phase unit,or the average of the line currents is zero | |||||||||||||||||||||
| CdataLogMinInletCurrentUnbalance | 1.3.6.1.4.1.13742.4.1.12.2.1.16 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current The Minimum value for the measurement period: A string displaying the current unbalance in percent. It will have the value NA if the feature is disabled, the PX is not a 3-phase unit,or the average of the line currents is zero | |||||||||||||||||||||
| CdataLogAvgInletActivePower | 1.3.6.1.4.1.13742.4.1.12.2.1.17 | Watts | RO | ||||||||||||||||||
column · Watts · read-only · current The Average value for the measurement period: The active power for the inlet This value is reported in Watts. | |||||||||||||||||||||
| CdataLogMaxInletActivePower | 1.3.6.1.4.1.13742.4.1.12.2.1.18 | Watts | RO | ||||||||||||||||||
column · Watts · read-only · current The Maximum value for the measurement period: The active power for the inlet This value is reported in Watts. | |||||||||||||||||||||
| CdataLogMinInletActivePower | 1.3.6.1.4.1.13742.4.1.12.2.1.19 | Watts | RO | ||||||||||||||||||
column · Watts · read-only · current The Minimum value for the measurement period: The active power for the inlet This value is reported in Watts. | |||||||||||||||||||||
| CdataLogAvgInletApparentPower | 1.3.6.1.4.1.13742.4.1.12.2.1.20 | VoltAmps | RO | ||||||||||||||||||
column · VoltAmps · read-only · current The Average value for the measurement period: The apparent power for the inlet. This value is reported in Volt-Amps | |||||||||||||||||||||
| CdataLogMaxInletApparentPower | 1.3.6.1.4.1.13742.4.1.12.2.1.21 | VoltAmps | RO | ||||||||||||||||||
column · VoltAmps · read-only · current The Maximum value for the measurement period: The apparent power for the inlet. This value is reported in Volt-Amps | |||||||||||||||||||||
| CdataLogMinInletApparentPower | 1.3.6.1.4.1.13742.4.1.12.2.1.22 | VoltAmps | RO | ||||||||||||||||||
column · VoltAmps · read-only · current The Minimum value for the measurement period: The apparent power for the inlet. This value is reported in Volt-Amps | |||||||||||||||||||||
| CdataLogAvgInletActiveEnergy | 1.3.6.1.4.1.13742.4.1.12.2.1.23 | WattHours | RO | ||||||||||||||||||
column · WattHours · read-only · current The Average value for the measurement period: The value of the cumulative active energy for this inlet. This value is reported in WattHours | |||||||||||||||||||||
| CdataLogMaxInletActiveEnergy | 1.3.6.1.4.1.13742.4.1.12.2.1.24 | WattHours | RO | ||||||||||||||||||
column · WattHours · read-only · current The Maximum value for the measurement period: The value of the cumulative active energy for this inlet. This value is reported in WattHours | |||||||||||||||||||||
| CdataLogMinInletActiveEnergy | 1.3.6.1.4.1.13742.4.1.12.2.1.25 | WattHours | RO | ||||||||||||||||||
column · WattHours · read-only · current The Minimum value for the measurement period: The value of the cumulative active energy for this inlet. This value is reported in WattHours | |||||||||||||||||||||
| NdataLogInletPole | 1.3.6.1.4.1.13742.4.1.13 | ||||||||||||||||||||
| TdataLogInletPoleTable | 1.3.6.1.4.1.13742.4.1.13.1 | NA | |||||||||||||||||||
table · not-accessible · current A list of line input entries. The number of entries is given by the value of dataLoginletTable(dataLogInletIndex).inletPoleCount. | |||||||||||||||||||||
| RdataLogInletPoleEntry | 1.3.6.1.4.1.13742.4.1.13.1.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry in the data log containing input line values for a particular input line. | |||||||||||||||||||||
| CdataLogInletPoleIndex | 1.3.6.1.4.1.13742.4.1.13.1.1.1 | Integer32 (1..256) | NA | ||||||||||||||||||
column · Integer32 (1..256) · not-accessible · current A unique value for each line input. Its value ranges between 1 and lineCurrentCount. | |||||||||||||||||||||
| CdataLogInletPoleCurrent | 1.3.6.1.4.1.13742.4.1.13.1.1.2 | MilliAmps | RO | deprecated | |||||||||||||||||
column · MilliAmps · read-only · deprecated The value of the current reported
in MilliAmps.
For Single Phase: Input Line Current
For 3phase Delta-wired: Current for L1, L2, L3
For 3phase WYE-wired: Current for L1, L2, L3, N
This has been deprecated in favor of
dataLogAvgInletPoleCurrent, dataLogMaxInletPoleCurrent,
dataLogMinInletPoleCurrent | |||||||||||||||||||||
| CdataLogInletPoleVoltage | 1.3.6.1.4.1.13742.4.1.13.1.1.3 | MilliVolts | RO | deprecated | |||||||||||||||||
column · MilliVolts · read-only · deprecated The value of the voltage reported
in MilliVolts.
For Single Phase: Input Line Voltage
For 3phase Delta-wired: Voltages for L1-L2, L2-L3, L3-L1
For 3phase WYE-wired: Voltages for L1-N, L2-N, L3-N
This has been deprecated in favor of
dataLogAvgInletPoleVoltage, dataLogMaxInletPoleVoltage,
dataLogMinInletPoleVoltage | |||||||||||||||||||||
| CdataLogAvgInletPoleCurrent | 1.3.6.1.4.1.13742.4.1.13.1.1.4 | MilliAmps | RO | ||||||||||||||||||
column · MilliAmps · read-only · current The Average value for the measurement period: The value of the current reported in MilliAmps. For Single Phase: Input Line Current For 3phase Delta-wired: Current for L1, L2, L3 For 3phase WYE-wired: Current for L1, L2, L3, N | |||||||||||||||||||||
| CdataLogMaxInletPoleCurrent | 1.3.6.1.4.1.13742.4.1.13.1.1.5 | MilliAmps | RO | ||||||||||||||||||
column · MilliAmps · read-only · current The Maximum value for the measurement period: The value of the current reported in MilliAmps. For Single Phase: Input Line Current For 3phase Delta-wired: Current for L1, L2, L3 For 3phase WYE-wired: Current for L1, L2, L3, N | |||||||||||||||||||||
| CdataLogMinInletPoleCurrent | 1.3.6.1.4.1.13742.4.1.13.1.1.6 | MilliAmps | RO | ||||||||||||||||||
column · MilliAmps · read-only · current The Minimum value for the measurement period: The value of the current reported in MilliAmps. For Single Phase: Input Line Current For 3phase Delta-wired: Current for L1, L2, L3 For 3phase WYE-wired: Current for L1, L2, L3, N | |||||||||||||||||||||
| CdataLogAvgInletPoleVoltage | 1.3.6.1.4.1.13742.4.1.13.1.1.7 | MilliVolts | RO | ||||||||||||||||||
column · MilliVolts · read-only · current The Average value for the measurement period: The value of the voltage reported in MilliVolts. For Single Phase: Input Line Voltage For 3phase Delta-wired: Voltages for L1-L2, L2-L3, L3-L1 For 3phase WYE-wired: Voltages for L1-N, L2-N, L3-N | |||||||||||||||||||||
| CdataLogMaxInletPoleVoltage | 1.3.6.1.4.1.13742.4.1.13.1.1.8 | MilliVolts | RO | ||||||||||||||||||
column · MilliVolts · read-only · current The Maximum value for the measurement period: The value of the voltage reported in MilliVolts. For Single Phase: Input Line Voltage For 3phase Delta-wired: Voltages for L1-L2, L2-L3, L3-L1 For 3phase WYE-wired: Voltages for L1-N, L2-N, L3-N | |||||||||||||||||||||
| CdataLogMinInletPoleVoltage | 1.3.6.1.4.1.13742.4.1.13.1.1.9 | MilliVolts | RO | ||||||||||||||||||
column · MilliVolts · read-only · current The Minimum value for the measurement period: The value of the voltage reported in MilliVolts. For Single Phase: Input Line Voltage For 3phase Delta-wired: Voltages for L1-L2, L2-L3, L3-L1 For 3phase WYE-wired: Voltages for L1-N, L2-N, L3-N | |||||||||||||||||||||
| CdataLogAvgInletPoleActivePower | 1.3.6.1.4.1.13742.4.1.13.1.1.10 | Watts | RO | ||||||||||||||||||
column · Watts · read-only · current This object has a valid value only for inline meters. If inlineMeter = 'No', then the value is invalid; In all other cases, it is the the Average value of the active power for the measurement period. The value is reported in Watts. | |||||||||||||||||||||
| CdataLogMaxInletPoleActivePower | 1.3.6.1.4.1.13742.4.1.13.1.1.11 | Watts | RO | ||||||||||||||||||
column · Watts · read-only · current This object has a valid value only for inline meters. If inlineMeter = 'No', then the value is invalid; In all other cases, it is the the Maximum value of the active power for the measurement period. The value is reported in Watts. | |||||||||||||||||||||
| CdataLogMinInletPoleActivePower | 1.3.6.1.4.1.13742.4.1.13.1.1.12 | Watts | RO | ||||||||||||||||||
column · Watts · read-only · current This object has a valid value only for inline meters. If inlineMeter = 'No', then the value is invalid; In all other cases, it is the the Minimum value of the active power for the measurement period. The value is reported in Watts. | |||||||||||||||||||||
| CdataLogAvgInletPoleApparentPower | 1.3.6.1.4.1.13742.4.1.13.1.1.13 | VoltAmps | RO | ||||||||||||||||||
column · VoltAmps · read-only · current This object has a valid value only for inline meters. If inlineMeter = 'No', then the value is invalid; In all other cases, it is the the Average value of the apparent power for the measurement period. The value is reported in Volt-Amps | |||||||||||||||||||||
| CdataLogMaxInletPoleApparentPower | 1.3.6.1.4.1.13742.4.1.13.1.1.14 | VoltAmps | RO | ||||||||||||||||||
column · VoltAmps · read-only · current This object has a valid value only for inline meters. If inlineMeter = 'No', then the value is invalid; In all other cases, it is the the Maximum value of the apparent power for the measurement period. The value is reported in Volt-Amps | |||||||||||||||||||||
| CdataLogMinInletPoleApparentPower | 1.3.6.1.4.1.13742.4.1.13.1.1.15 | VoltAmps | RO | ||||||||||||||||||
column · VoltAmps · read-only · current This object has a valid value only for inline meters. If inlineMeter = 'No', then the value is invalid; In all other cases, it is the the Minimum value of the apparent power for the measurement period. The value is reported in Volt-Amps | |||||||||||||||||||||
| CdataLogAvgInletPoleActiveEnergy | 1.3.6.1.4.1.13742.4.1.13.1.1.16 | WattHours | RO | ||||||||||||||||||
column · WattHours · read-only · current This object has a valid value only for inline meters. If inlineMeter = 'No', then the value is invalid; In all other cases, it is the the Average value of the active energy for the measurement period. The value is reported in WattHours | |||||||||||||||||||||
| CdataLogMaxInletPoleActiveEnergy | 1.3.6.1.4.1.13742.4.1.13.1.1.17 | WattHours | RO | ||||||||||||||||||
column · WattHours · read-only · current This object has a valid value only for inline meters. If inlineMeter = 'No', then the value is invalid; In all other cases, it is the the Maximum value of the active energy for the measurement period. The value is reported in WattHours | |||||||||||||||||||||
| CdataLogMinInletPoleActiveEnergy | 1.3.6.1.4.1.13742.4.1.13.1.1.18 | WattHours | RO | ||||||||||||||||||
column · WattHours · read-only · current This object has a valid value only for inline meters. If inlineMeter = 'No', then the value is invalid; In all other cases, it is the the Minimum value of the active energy for the measurement period. The value is reported in WattHours | |||||||||||||||||||||
| NdataLogInputLine | 1.3.6.1.4.1.13742.4.1.14 | ||||||||||||||||||||
| TdataLogInputLineTable | 1.3.6.1.4.1.13742.4.1.14.1 | NA | deprecated | ||||||||||||||||||
table · not-accessible · deprecated A list of line input entries. The number of entries is given by the value of lineCurrentCount. This object is deprecated in favour of dataLogInletLineTable | |||||||||||||||||||||
| RdataLogInputLineEntry | 1.3.6.1.4.1.13742.4.1.14.1.1 | NA | deprecated | ||||||||||||||||||
row · not-accessible · deprecated An entry in the data log containing input line values for a particular input line. This object is deprecated in favour of dataLogInletLineTable | |||||||||||||||||||||
| CdataLogInputLineIndex | 1.3.6.1.4.1.13742.4.1.14.1.1.1 | Integer32 (1..256) | NA | deprecated | |||||||||||||||||
column · Integer32 (1..256) · not-accessible · deprecated A unique value for each line input. Its value ranges between 1 and inletTable(inletIndex).inletPoleCount. This object is deprecated in favour of dataLogInletLineTable | |||||||||||||||||||||
| CdataLogInputLineCurrent | 1.3.6.1.4.1.13742.4.1.14.1.1.2 | MilliAmps | RO | deprecated | |||||||||||||||||
column · MilliAmps · read-only · deprecated The value of the current reported in MilliAmps. For Single Phase: Input Line Current For 3phase Delta-wired: Current for L1, L2, L3 For 3phase WYE-wired: Current for L1, L2, L3, N This object is deprecated in favour of dataLogInletLineTable | |||||||||||||||||||||
| CdataLogInputLineVoltage | 1.3.6.1.4.1.13742.4.1.14.1.1.3 | MilliVolts | RO | deprecated | |||||||||||||||||
column · MilliVolts · read-only · deprecated The value of the voltage reported in MilliVolts. For Single Phase: Input Line Voltage For 3phase Delta-wired: Voltages for L1-L2, L2-L3, L3-L1 For 3phase WYE-wired: Voltages for L1-N, L2-N, L3-N This object is deprecated in favour of dataLogInletLineTable | |||||||||||||||||||||
| NdataLogCircuitBreaker | 1.3.6.1.4.1.13742.4.1.15 | ||||||||||||||||||||
| TdataLogCircuitBreakerTable | 1.3.6.1.4.1.13742.4.1.15.1 | NA | |||||||||||||||||||
table · not-accessible · current A list of circuit breaker entries. The number of entries is given by the value of circuitBreakerCount. | |||||||||||||||||||||
| RdataLogCircuitBreakerEntry | 1.3.6.1.4.1.13742.4.1.15.1.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry in the data log containing circuit breaker values | |||||||||||||||||||||
| CdataLogCircuitBreakerIndex | 1.3.6.1.4.1.13742.4.1.15.1.1.1 | Integer32 (1..256) | NA | ||||||||||||||||||
column · Integer32 (1..256) · not-accessible · current A unique value for each circuit breaker. Its value ranges between 1 and circuitBreakerCount. | |||||||||||||||||||||
| CdataLogCircuitBreakerCurrent | 1.3.6.1.4.1.13742.4.1.15.1.1.2 | MilliAmps | RO | deprecated | |||||||||||||||||
column · MilliAmps · read-only · deprecated The value of the current reported
in MilliAmps.
This has been deprecated in favor of
dataLogAvgCircuitBreakerCurrent, dataLogMaxOutletCircuitBreakerCurrent,
dataLogMinCircuitBreakerCurrent | |||||||||||||||||||||
| CdataLogAvgCircuitBreakerCurrent | 1.3.6.1.4.1.13742.4.1.15.1.1.3 | MilliAmps | RO | ||||||||||||||||||
column · MilliAmps · read-only · current The Average value for the measurement period: The value of the current reported in MilliAmps. | |||||||||||||||||||||
| CdataLogMaxCircuitBreakerCurrent | 1.3.6.1.4.1.13742.4.1.15.1.1.4 | MilliAmps | RO | ||||||||||||||||||
column · MilliAmps · read-only · current The Maximum value for the measurement period: The value of the current reported in MilliAmps. | |||||||||||||||||||||
| CdataLogMinCircuitBreakerCurrent | 1.3.6.1.4.1.13742.4.1.15.1.1.5 | MilliAmps | RO | ||||||||||||||||||
column · MilliAmps · read-only · current The Minimum value for the measurement period: The value of the current reported in MilliAmps. | |||||||||||||||||||||
| NdataLogExternalSensor | 1.3.6.1.4.1.13742.4.1.16 | ||||||||||||||||||||
| TdataLogExternalSensorTable | 1.3.6.1.4.1.13742.4.1.16.1 | NA | |||||||||||||||||||
table · not-accessible · current A list of external sensor entries. The number of entries is given by the value of externalSensorCount. | |||||||||||||||||||||
| RdataLogExternalSensorEntry | 1.3.6.1.4.1.13742.4.1.16.1.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry in the data log containing external sensor values | |||||||||||||||||||||
| CdataLogExternalSensorIndex | 1.3.6.1.4.1.13742.4.1.16.1.1.1 | Integer32 (1..256) | NA | ||||||||||||||||||
column · Integer32 (1..256) · not-accessible · current A unique value for each external sensor. Its value ranges between 1 and externalSensorCount. | |||||||||||||||||||||
| CdataLogExternalSensorChanged | 1.3.6.1.4.1.13742.4.1.16.1.1.2 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current Indicates whether there has been a change in the sensor type/subtype/channel number for this sensorID.
This can occur if sensorIDs have been reassigned as a result of
a GUI operation or a SET operation on reorderexternalSensorTableEntries.
Format: SerialNumber=xxxxxxxx; SensorType=dd; SensorSubType=d; ChannelNumber=d
SensorSubType and ChannelNumber are present only if NewSensorType=onOff
If there was no change from the previous sample, then
this string is empty.
Examples:
Sensor changed to Temperature:
SerialNumber=AEI8160083; SensorType=10;
Sensor changed to onOff/SmokeDetection:
SerialNumber=AEI8160083; SensorType=14; SensorSubType= 18; ChannelNumber=1
Sensor Channel Number changed:
SerialNumber=AEI8160083; SensorType=14; SensorSubType= 18; ChannelNumber=2
Sensor SubType changed:
SerialNumber=AEI8160083; SensorType=14; SensorSubType= 19; ChannelNumber=2 | |||||||||||||||||||||
| CdataLogExternalSensorState | 1.3.6.1.4.1.13742.4.1.16.1.1.3 | StateOfSensorEnumeration | RO | ||||||||||||||||||
column · StateOfSensorEnumeration · read-only · current The sensor state. | |||||||||||||||||||||
| CdataLogAvgExternalSensorValue | 1.3.6.1.4.1.13742.4.1.16.1.1.4 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The Average of the sensor values Does not apply (gets will return 0) to onOff, trip, vibration, waterDetection, smokeDetection sensors. This value is not valid if dataLogExternalSensorState is unavailable(-1). | |||||||||||||||||||||
| CdataLogMaxExternalSensorValue | 1.3.6.1.4.1.13742.4.1.16.1.1.5 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The Maximum of the sensor values Does not apply (gets will return 0) to onOff, trip, vibration, waterDetection, smokeDetection sensors This value is not valid if dataLogExternalSensorState is unavailable(-1). | |||||||||||||||||||||
| CdataLogMinExternalSensorValue | 1.3.6.1.4.1.13742.4.1.16.1.1.6 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The Minimum of the sensor values. Does not apply (gets will return 0) to onOff, trip, vibration, waterDetection, smokeDetection sensors This value is not valid if dataLogExternalSensorState is unavailable(-1). | |||||||||||||||||||||
| Ninlets | 1.3.6.1.4.1.13742.4.1.20 | ||||||||||||||||||||
| SinletCount | 1.3.6.1.4.1.13742.4.1.20.1 | Integer32 | RO | ||||||||||||||||||
scalar · Integer32 · read-only · current The number of inlets present on this pdu. | |||||||||||||||||||||
| TinletTable | 1.3.6.1.4.1.13742.4.1.20.2 | NA | |||||||||||||||||||
table · not-accessible · current A list of inlet entries. The number of entries is given by the value of inletCount. | |||||||||||||||||||||
| RinletEntry | 1.3.6.1.4.1.13742.4.1.20.2.1 | NA | |||||||||||||||||||
| CinletIndex | 1.3.6.1.4.1.13742.4.1.20.2.1.1 | Integer32 (1..256) | NA | 1 | |||||||||||||||||
column · Integer32 (1..256) · not-accessible · current A unique value for each inlet. Its value ranges between 1 and the value of inletCount. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletPoleCount | 1.3.6.1.4.1.13742.4.1.20.2.1.3 | Integer32 | RO | 1 | |||||||||||||||||
column · Integer32 · read-only · current The number of poles for an inlet (1 for single phase, 3 for 3 phase Delta-wired, 4 for 3 phase WYE wired). Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletCurrentRating | 1.3.6.1.4.1.13742.4.1.20.2.1.4 | MilliAmps | RO | 16000 | |||||||||||||||||
column · MilliAmps · read-only · current The input current Rating Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletCurrent | 1.3.6.1.4.1.13742.4.1.20.2.1.7 | MilliAmps | RO | 2971 | |||||||||||||||||
column · MilliAmps · read-only · current A unique value for the current sensor
attached to the inlet. This value is
reported in milliamps (1/1000th of an amp).
This OID does not apply to 3 phase systems;
a value of 0 will be reported for same.Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletVoltage | 1.3.6.1.4.1.13742.4.1.20.2.1.8 | MilliVolts | RO | 230000 | |||||||||||||||||
column · MilliVolts · read-only · current A unique value for the voltage sensor
attached to the intlet.This value is
reported in millivolts (1/1000th of a volt).
This OID does not apply to 3 phase systems;
a value of 0 will be reported for same.Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletActivePower | 1.3.6.1.4.1.13742.4.1.20.2.1.9 | Watts | RO | 580 | |||||||||||||||||
column · Watts · read-only · current The active power for the inlet This value is reported in Watts. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletApparentPower | 1.3.6.1.4.1.13742.4.1.20.2.1.10 | VoltAmps | RO | 692 | |||||||||||||||||
column · VoltAmps · read-only · current The apparent power for the inlet. This value is reported in Volt-Amps Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletPowerFactor | 1.3.6.1.4.1.13742.4.1.20.2.1.11 | PowerFactorPercentage | RO | 83 | |||||||||||||||||
column · PowerFactorPercentage · read-only · current A unique value for the power factor of the inlet. The reading represents a percentage in the range of 0% to 100%. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletActiveEnergy | 1.3.6.1.4.1.13742.4.1.20.2.1.12 | WattHours | RO | 0 | |||||||||||||||||
column · WattHours · read-only · current This object has an invalid value if outletEnergySupport = 'No'; In all other cases, it is the value of the cumulative active energy for this inlet. This value is reported in WattHours Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletCurrentUnbalance | 1.3.6.1.4.1.13742.4.1.20.2.1.15 | DisplayString | RO | Not Enabled (NE) | |||||||||||||||||
column · DisplayString · read-only · current A string displaying the current unbalance in percent. It will have the value NA if the feature is disabled, the PX is not a 3-phase unit,or the average of the line currents is zero Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletCurrentUpperWarning | 1.3.6.1.4.1.13742.4.1.20.2.1.20 | MilliAmps | RW | 10280 | |||||||||||||||||
column · MilliAmps · read-write · current The value of the upper warning (non-critical) current threshold for the inlet. This value is reported in milliamps (1/1000th of an amp) Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletCurrentUpperCritical | 1.3.6.1.4.1.13742.4.1.20.2.1.21 | MilliAmps | RW | 12589 | |||||||||||||||||
column · MilliAmps · read-write · current The value of the upper critical current threshold for the inlet. This value is reported in milliamps (1/1000th of an amp) Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletCurrentLowerWarning | 1.3.6.1.4.1.13742.4.1.20.2.1.22 | MilliAmps | RW | ||||||||||||||||||
column · MilliAmps · read-write · current The value of the lower warning (non-critical) current threshold for the inlet. This value is reported in milliamps (1/1000th of an amp). This OID is valid for inline meter PDU's. only | |||||||||||||||||||||
| CinletCurrentLowerCritical | 1.3.6.1.4.1.13742.4.1.20.2.1.23 | MilliAmps | RW | ||||||||||||||||||
column · MilliAmps · read-write · current The value of the lower critical current threshold for the inlet. This value is reported in milliamps (1/1000th of an amp). This OID is valid for inline meter PDU's only. | |||||||||||||||||||||
| CinletVoltageUpperWarning | 1.3.6.1.4.1.13742.4.1.20.2.1.24 | MilliVolts | RW | 243000 | |||||||||||||||||
column · MilliVolts · read-write · current The value of the upper warning (non-critical) current threshold for the inlet. This value is reported in millivolts (1/1000th of a volt) Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletVoltageUpperCritical | 1.3.6.1.4.1.13742.4.1.20.2.1.25 | MilliVolts | RW | 253000 | |||||||||||||||||
column · MilliVolts · read-write · current The value of the upper critical current threshold for the inlet. This value is reported in millivolts (1/1000th of a volt) Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletVoltageLowerWarning | 1.3.6.1.4.1.13742.4.1.20.2.1.26 | MilliVolts | RW | 207000 | |||||||||||||||||
column · MilliVolts · read-write · current The value of the lower warning (non-critical) current threshold for the inlet. This value is reported in millivolts (1/1000th of a volt) Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletVoltageLowerCritical | 1.3.6.1.4.1.13742.4.1.20.2.1.27 | MilliVolts | RW | 195000 | |||||||||||||||||
column · MilliVolts · read-write · current The value of the lower critical current threshold for the inlet. This value is reported in millivolts (1/1000th of a volt) Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletCurrentUnbalanceUpperCritical | 1.3.6.1.4.1.13742.4.1.20.2.1.28 | Percentage | RW | 0 | |||||||||||||||||
column · Percentage · read-write · current The value of the upper critical current Unbalance threshold. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletCurrentUnbalanceUpperWarning | 1.3.6.1.4.1.13742.4.1.20.2.1.29 | Percentage | RW | 0 | |||||||||||||||||
column · Percentage · read-write · current The value of the upper warning current Unbalance threshold. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletCurrentHysteresis | 1.3.6.1.4.1.13742.4.1.20.2.1.30 | Unsigned32 | RW | 1000 | |||||||||||||||||
column · Unsigned32 · read-write · current The hysteresis used for deassertions. This value is reported in milliamps (1/1000th of an amp) Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletVoltageHysteresis | 1.3.6.1.4.1.13742.4.1.20.2.1.31 | Unsigned32 | RW | 4000 | |||||||||||||||||
column · Unsigned32 · read-write · current The hysteresis used for deassertions. This value is reported in millivolts (1/1000th of a volt) Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletCurrentUnbalanceHysteresis | 1.3.6.1.4.1.13742.4.1.20.2.1.32 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The hysteresis used for deassertions. This value is reported in percent | |||||||||||||||||||||
| NinletPole | 1.3.6.1.4.1.13742.4.1.21 | ||||||||||||||||||||
| TinletPoleTable | 1.3.6.1.4.1.13742.4.1.21.2 | NA | |||||||||||||||||||
table · not-accessible · current A list of line input entries. The number of entries is given by the value of inletTable(inletIndex).inletPoleCount. | |||||||||||||||||||||
| RinletPoleEntry | 1.3.6.1.4.1.13742.4.1.21.2.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry in the data log containing input line values for a particular input line.
| |||||||||||||||||||||
| CinletPoleIndex | 1.3.6.1.4.1.13742.4.1.21.2.1.1 | Integer32 (1..256) | NA | 1 | |||||||||||||||||
column · Integer32 (1..256) · not-accessible · current A unique value for each line input. Its value ranges between 1 and of inletTable(inletIndex).inletPoleCount. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletPoleLabel | 1.3.6.1.4.1.13742.4.1.21.2.1.2 | DisplayString | RO | L1 | |||||||||||||||||
column · DisplayString · read-only · current A string identifying the Line For Single Phase: L1 For 3phase Delta wired outlets: L1, L2, L3 For 3phase WYE Wired Outlets: L1, L2, L3 Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletPoleCurrent | 1.3.6.1.4.1.13742.4.1.21.2.1.3 | MilliAmps | RO | 2971 | |||||||||||||||||
column · MilliAmps · read-only · current The value of the line current reported in MilliAmps. inletPoleIndex = 1; For Single Phase, Input Line Current; For 3-phase, L1 Current inletPoleIndex = 2; For 3-phase, L2 Current inletPoleIndex = 3; For 3-phase, L3 Current Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletPoleVoltage | 1.3.6.1.4.1.13742.4.1.21.2.1.4 | MilliVolts | RO | 230500 | |||||||||||||||||
column · MilliVolts · read-only · current The value of the line-line voltage reported in MilliVolts.
inletPoleIndex = 1; Single Phase Input Line Voltage
3-phase, L1-L2 Voltage or L1-N voltage
inletPoleIndex = 2; 3-phase L2-L3 Voltage or L2-N voltage
inletPoleaIndex = 3; 3-phase L3-L1 Voltage or L3-N voltageExample values from LibreNMS test devices
| |||||||||||||||||||||
| CinletPoleMaxCurrent | 1.3.6.1.4.1.13742.4.1.21.2.1.5 | MilliAmps | RO | 0 | |||||||||||||||||
column · MilliAmps · read-only · current This object has an invalid value for a single-phase PDU. If inletPoleCount = 1, then the value is invalid; In all other cases, it is the value of the max. current sensor attached to the inlet Pole. This value is reported in milliamps (1/1000th of an amp) Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletPoleActivePower | 1.3.6.1.4.1.13742.4.1.21.2.1.7 | Watts | RO | ||||||||||||||||||
column · Watts · read-only · current This object has a valid value only for inline meters. If inlineMeter = 'No', then the value is invalid; In all other cases, it is the active power for the line/pole. The value is reported in Watts. | |||||||||||||||||||||
| CinletPoleApparentPower | 1.3.6.1.4.1.13742.4.1.21.2.1.8 | VoltAmps | RO | ||||||||||||||||||
column · VoltAmps · read-only · current This object has a valid value only for inline meters. If inlineMeter = 'No', then the value is invalid; In all other cases, it is the apparent power for the line/pole. The value is reported in Volt-Amps | |||||||||||||||||||||
| CinletPolePowerFactor | 1.3.6.1.4.1.13742.4.1.21.2.1.9 | PowerFactorPercentage | RO | 0 | |||||||||||||||||
column · PowerFactorPercentage · read-only · current This object has a valid value only for inline meters. If inlineMeter = 'No', then the value is invalid; In all other cases, it is the power factor for the line/pole The reading represents a percentage in the range of 0% to 100%. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinletPoleActiveEnergy | 1.3.6.1.4.1.13742.4.1.21.2.1.11 | WattHours | RO | 0 | |||||||||||||||||
column · WattHours · read-only · current This object has a valid value only for inline meters. If inlineMeter = 'No', then the value is invalid; In all other cases, it is the cumulative active energy for the line/pole. The value is reported in WattHours Example values from LibreNMS test devices
| |||||||||||||||||||||
| Nenvironmental | 1.3.6.1.4.1.13742.4.2 | ||||||||||||||||||||
| StempSensorCount | 1.3.6.1.4.1.13742.4.2.1 | Integer32 | RO | deprecated | |||||||||||||||||
scalar · Integer32 · read-only · deprecated The number of external temperature sensors (regardless of their current state) present on this pdu. This is deprecated in favor of externalSensors | |||||||||||||||||||||
| TtempSensorTable | 1.3.6.1.4.1.13742.4.2.2 | NA | deprecated | ||||||||||||||||||
table · not-accessible · deprecated A list of temperature sensor entries. The number of entries is given by the value of tempSensorCount. This is deprecated in favor of externalSensors | |||||||||||||||||||||
| RtempSensorEntry | 1.3.6.1.4.1.13742.4.2.2.1 | NA | deprecated | ||||||||||||||||||
row · not-accessible · deprecated An entry containing sensor reading and threshold settings for a particular temperature sensor. This is deprecated in favor of externalSensors
| |||||||||||||||||||||
| CtempSensorIndex | 1.3.6.1.4.1.13742.4.2.2.1.1 | Integer32 (1..256) | NA | deprecated | |||||||||||||||||
column · Integer32 (1..256) · not-accessible · deprecated A unique value for each temperature sensor. Its value ranges between 1 and tempSensorCount. This is deprecated in favor of externalSensors | |||||||||||||||||||||
| CtempSensorLabel | 1.3.6.1.4.1.13742.4.2.2.1.2 | DisplayString | RW | deprecated | |||||||||||||||||
column · DisplayString · read-write · deprecated A settable human-readable label for the external temperature sensor. One possible use for this label is to convey sensor location. This is deprecated in favor of externalSensors | |||||||||||||||||||||
| Ctemperature | 1.3.6.1.4.1.13742.4.2.2.1.3 | TenthDegreesCelsius | RO | deprecated | |||||||||||||||||
column · TenthDegreesCelsius · read-only · deprecated The value of the external temperature sensor reported in tenth degrees celsius. This is deprecated in favor of externalSensors | |||||||||||||||||||||
| CtempLowerWarning | 1.3.6.1.4.1.13742.4.2.2.1.4 | DegreesCelsius | RW | deprecated | |||||||||||||||||
column · DegreesCelsius · read-write · deprecated The value of the lower warning (non-critical) threshold. This is deprecated in favor of externalSensors | |||||||||||||||||||||
| CtempUpperWarning | 1.3.6.1.4.1.13742.4.2.2.1.5 | DegreesCelsius | RW | deprecated | |||||||||||||||||
column · DegreesCelsius · read-write · deprecated The value of the upper warning (non-critical) threshold. This is deprecated in favor of externalSensors | |||||||||||||||||||||
| CtempLowerCritical | 1.3.6.1.4.1.13742.4.2.2.1.6 | DegreesCelsius | RW | deprecated | |||||||||||||||||
column · DegreesCelsius · read-write · deprecated The value of the lower critical threshold. This is deprecated in favor of externalSensors | |||||||||||||||||||||
| CtempUpperCritical | 1.3.6.1.4.1.13742.4.2.2.1.7 | DegreesCelsius | RW | deprecated | |||||||||||||||||
column · DegreesCelsius · read-write · deprecated The value of the upper critical threshold. This is deprecated in favor of externalSensors | |||||||||||||||||||||
| CtempXCoordinate | 1.3.6.1.4.1.13742.4.2.2.1.8 | DisplayString | RW | deprecated | |||||||||||||||||
column · DisplayString · read-write · deprecated The value of X coordinate in freeform with number of characters <= 24 This is deprecated in favor of externalSensors | |||||||||||||||||||||
| CtempYCoordinate | 1.3.6.1.4.1.13742.4.2.2.1.9 | DisplayString | RW | deprecated | |||||||||||||||||
column · DisplayString · read-write · deprecated The value of Y coordinate in freeform with number of characters <= 24 This is deprecated in favor of externalSensors | |||||||||||||||||||||
| CtempZCoordinate | 1.3.6.1.4.1.13742.4.2.2.1.10 | DisplayString | RW | deprecated | |||||||||||||||||
column · DisplayString · read-write · deprecated The value of Z coordinate in one of two formats: either freeform with number of characters <= 24 or in Z units so that 0 =< integer value <= 60 This is deprecated in favor of externalSensors | |||||||||||||||||||||
| ShumiditySensorCount | 1.3.6.1.4.1.13742.4.2.3 | Integer32 | RO | deprecated | |||||||||||||||||
scalar · Integer32 · read-only · deprecated The number of external humidity sensors (regardless of their current state) present on this pdu. This is deprecated in favor of externalSensors | |||||||||||||||||||||
| ThumiditySensorTable | 1.3.6.1.4.1.13742.4.2.4 | NA | deprecated | ||||||||||||||||||
table · not-accessible · deprecated A list of humidity sensor entries. The number of entries is given by the value of humiditySensorCount. This is deprecated in favor of externalSensors | |||||||||||||||||||||
| RhumiditySensorEntry | 1.3.6.1.4.1.13742.4.2.4.1 | NA | deprecated | ||||||||||||||||||
row · not-accessible · deprecated An entry containing sensor reading and threshold settings for a particular humidity sensor. This is deprecated in favor of externalSensors
| |||||||||||||||||||||
| ChumiditySensorIndex | 1.3.6.1.4.1.13742.4.2.4.1.1 | Integer32 (1..256) | NA | deprecated | |||||||||||||||||
column · Integer32 (1..256) · not-accessible · deprecated A unique value for each humidity sensor. Its value ranges between 1 and humiditySensorCount. This is deprecated in favor of externalSensors | |||||||||||||||||||||
| ChumiditySensorLabel | 1.3.6.1.4.1.13742.4.2.4.1.2 | DisplayString | RW | deprecated | |||||||||||||||||
column · DisplayString · read-write · deprecated A settable human-readable label for the external humidity sensor. One possible use for this label is to convey sensor location. This is deprecated in favor of externalSensors | |||||||||||||||||||||
| Chumidity | 1.3.6.1.4.1.13742.4.2.4.1.3 | RelativeHumidity | RO | deprecated | |||||||||||||||||
column · RelativeHumidity · read-only · deprecated The value of the external humidity sensor reported as relative humidity (a percentage). This is deprecated in favor of externalSensors | |||||||||||||||||||||
| ChumidityLowerWarning | 1.3.6.1.4.1.13742.4.2.4.1.4 | RelativeHumidity | RW | deprecated | |||||||||||||||||
column · RelativeHumidity · read-write · deprecated The value of the lower warning (non-critical) threshold. This is deprecated in favor of externalSensors | |||||||||||||||||||||
| ChumidityUpperWarning | 1.3.6.1.4.1.13742.4.2.4.1.5 | RelativeHumidity | RW | deprecated | |||||||||||||||||
column · RelativeHumidity · read-write · deprecated The value of the upper warning (non-critical) threshold. This is deprecated in favor of externalSensors | |||||||||||||||||||||
| ChumidityLowerCritical | 1.3.6.1.4.1.13742.4.2.4.1.6 | RelativeHumidity | RW | deprecated | |||||||||||||||||
column · RelativeHumidity · read-write · deprecated The value of the lower critical threshold. This is deprecated in favor of externalSensors | |||||||||||||||||||||
| ChumidityUpperCritical | 1.3.6.1.4.1.13742.4.2.4.1.7 | RelativeHumidity | RW | deprecated | |||||||||||||||||
column · RelativeHumidity · read-write · deprecated The value of the upper critical threshold. This is deprecated in favor of externalSensors | |||||||||||||||||||||
| ChumidityXCoordinate | 1.3.6.1.4.1.13742.4.2.4.1.8 | DisplayString | RW | deprecated | |||||||||||||||||
column · DisplayString · read-write · deprecated The value of X coordinate in freeform with number of characters <= 24 This is deprecated in favor of externalSensors | |||||||||||||||||||||
| ChumidityYCoordinate | 1.3.6.1.4.1.13742.4.2.4.1.9 | DisplayString | RW | deprecated | |||||||||||||||||
column · DisplayString · read-write · deprecated The value of Y coordinate in freeform with number of characters <= 24 This is deprecated in favor of externalSensors | |||||||||||||||||||||
| ChumidityZCoordinate | 1.3.6.1.4.1.13742.4.2.4.1.10 | DisplayString | RW | deprecated | |||||||||||||||||
column · DisplayString · read-write · deprecated The value of Z coordinate in one of two formats: either freeform with number of characters <= 24 or in Z units so that 0 =< integer value <= 60 This is deprecated in favor of externalSensors | |||||||||||||||||||||
| NexternalSensors | 1.3.6.1.4.1.13742.4.3 | ||||||||||||||||||||
| SexternalSensorCount | 1.3.6.1.4.1.13742.4.3.1 | Integer32 (0..255) | RO | ||||||||||||||||||
scalar · Integer32 (0..255) · read-only · current The number of external sensors | |||||||||||||||||||||
| SreorderexternalSensorTableEntries | 1.3.6.1.4.1.13742.4.3.2 | DisplayString | RW | ||||||||||||||||||
scalar · DisplayString · read-write · current This is an operation. It has write-only semantics.
GET operation will return the empty string.
For SET operations, it specifies the new order of the externalSensorTable entries.
a) The list must contain entries for each managed sensor, even if the sensor is not being moved.
b) The list must not have more than 16 entries.
c) 1 <= Valid sensorID <= 16
d) The length of the list is the value of the largest sensorID in the
original (before the move) list of managed sensors.
e) Each sensorID must appear only once in the list.
f) If there are missing numbers in the original list of sensorIDs,
then each missing number must be indicated by a comma.
EXAMPLE 1: Managed sensors have IDs 1,2,3,4,5
Move 1 to 13; 2 to 8; 3 to 9; 4 is not moved; 5 moves to 2
Existing Position New Position
1 --> 13
2 --> 8
3 --> 9
4 --> 4
5 --> 2
Since the largest sensorID before the move is 5, the length of the list is 5
Comma separated list is 13,8,9,4,2
EXAMPLE 2: Managed sensors have IDs 2,5,6,7,11
Sensor IDs 1,3,4,8,9,10 do not appear in the list.
These positions must be indicated by commas.
Move 2 to 13; 5 to 8; 6 to 9; 7 to 16; 11 does not move
Existing Position New Position
2 --> 13
5 --> 8
6 --> 9
7 --> 16
11 --> 11
Since the largest sensorID before the move is 11, the length of the list is 11
Comma separated list is ,13,,,8,9,16,,,,11 | |||||||||||||||||||||
| TexternalSensorTable | 1.3.6.1.4.1.13742.4.3.3 | NA | |||||||||||||||||||
table · not-accessible · current A list of externalSensor entries. The number of entries is given by the value of externalSensorCount for the pdu. | |||||||||||||||||||||
| RexternalSensorEntry | 1.3.6.1.4.1.13742.4.3.3.1 | NA | |||||||||||||||||||
row · not-accessible · current An externalSensor entry containing objects at the for a particular PDU.
| |||||||||||||||||||||
| CsensorID | 1.3.6.1.4.1.13742.4.3.3.1.1 | Integer32 (1..256) | NA | 2 | |||||||||||||||||
column · Integer32 (1..256) · not-accessible · current A unique value for each sesnor. Its value ranges between 1 and the value of externalSensorCount. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CexternalSensorType | 1.3.6.1.4.1.13742.4.3.3.1.2 | TypeOfSensorEnumeration | RO | 11 | |||||||||||||||||
column · TypeOfSensorEnumeration · read-only · current The type of sensor Example values from LibreNMS test devices
| |||||||||||||||||||||
| CexternalSensorSerialNumber | 1.3.6.1.4.1.13742.4.3.3.1.3 | DisplayString | RO | AEI8850418 | |||||||||||||||||
column · DisplayString · read-only · current The sensor serial number Example values from LibreNMS test devices
| |||||||||||||||||||||
| CexternalSensorName | 1.3.6.1.4.1.13742.4.3.3.1.4 | DisplayString | RW | Humidity AEI8850418 | |||||||||||||||||
column · DisplayString · read-write · current The user given name Example values from LibreNMS test devices
| |||||||||||||||||||||
| CexternalSensorChannelNumber | 1.3.6.1.4.1.13742.4.3.3.1.5 | Integer32 | RO | 1 | |||||||||||||||||
column · Integer32 · read-only · current The channel number, applies only to contact sensors; -1 for other sensors Example values from LibreNMS test devices
| |||||||||||||||||||||
| CexternalSensorXCoordinate | 1.3.6.1.4.1.13742.4.3.3.1.6 | DisplayString | RW | 0 | |||||||||||||||||
column · DisplayString · read-write · current The X coordinate Example values from LibreNMS test devices
| |||||||||||||||||||||
| CexternalSensorYCoordinate | 1.3.6.1.4.1.13742.4.3.3.1.7 | DisplayString | RW | 0 | |||||||||||||||||
column · DisplayString · read-write · current The Y coordinate Example values from LibreNMS test devices
| |||||||||||||||||||||
| CexternalSensorZCoordinate | 1.3.6.1.4.1.13742.4.3.3.1.8 | DisplayString | RW | 0 | |||||||||||||||||
column · DisplayString · read-write · current The Z coordinate Example values from LibreNMS test devices
| |||||||||||||||||||||
| CexternalBinarySensorSubtype | 1.3.6.1.4.1.13742.4.3.3.1.9 | TypeOfSensorEnumeration | RO | -1 | |||||||||||||||||
column · TypeOfSensorEnumeration · read-only · current The subtype of the binary sensor This OID is valid for discrete sensors only. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CexternalSensorUnits | 1.3.6.1.4.1.13742.4.3.3.1.16 | SensorUnitsEnumeration | RO | 9 | |||||||||||||||||
column · SensorUnitsEnumeration · read-only · current The base units. Does not apply (gets will return 0) to onOff, trip, vibration, waterDetection, smokeDetection sensors Example values from LibreNMS test devices
| |||||||||||||||||||||
| CexternalSensorDecimalDigits | 1.3.6.1.4.1.13742.4.3.3.1.17 | Unsigned32 | RO | 0 | |||||||||||||||||
column · Unsigned32 · read-only · current The number of digits displayed to the right of the decimal point. Does not apply (gets will return 0) to onOff, trip, vibration, waterDetection, smokeDetection sensors Example values from LibreNMS test devices
| |||||||||||||||||||||
| CexternalSensorLowerCriticalThreshold | 1.3.6.1.4.1.13742.4.3.3.1.31 | Integer32 | RW | 10 | |||||||||||||||||
column · Integer32 · read-write · current The lower critical threshold The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is .01 Does not apply (gets will return 0) to onOff, trip, vibration, waterDetection, smokeDetection sensors Example values from LibreNMS test devices
| |||||||||||||||||||||
| CexternalSensorLowerWarningThreshold | 1.3.6.1.4.1.13742.4.3.3.1.32 | Integer32 | RW | 15 | |||||||||||||||||
column · Integer32 · read-write · current The lower non-critical (warning) threshold The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is .01 Does not apply (gets will return 0) to onOff, trip, vibration, waterDetection, smokeDetection sensors Example values from LibreNMS test devices
| |||||||||||||||||||||
| CexternalSensorUpperCriticalThreshold | 1.3.6.1.4.1.13742.4.3.3.1.33 | Integer32 | RW | 90 | |||||||||||||||||
column · Integer32 · read-write · current The upper critical threshold The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is .01 Does not apply (gets will return 0) to onOff, trip, vibration, waterDetection, smokeDetection sensors Example values from LibreNMS test devices
| |||||||||||||||||||||
| CexternalSensorUpperWarningThreshold | 1.3.6.1.4.1.13742.4.3.3.1.34 | Integer32 | RW | 85 | |||||||||||||||||
column · Integer32 · read-write · current The upper non-critical (warning) threshold The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is .01 Does not apply (gets will return 0) to onOff, trip, vibration, waterDetection, smokeDetection sensors Example values from LibreNMS test devices
| |||||||||||||||||||||
| CexternalSensorHysteresis | 1.3.6.1.4.1.13742.4.3.3.1.35 | Unsigned32 | RW | 1 | |||||||||||||||||
column · Unsigned32 · read-write · current The hysteresis used for deassertions The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CexternalSensorState | 1.3.6.1.4.1.13742.4.3.3.1.40 | StateOfSensorEnumeration | RO | 4 | |||||||||||||||||
column · StateOfSensorEnumeration · read-only · current The sensor state Example values from LibreNMS test devices
| |||||||||||||||||||||
| CexternalSensorValue | 1.3.6.1.4.1.13742.4.3.3.1.41 | Integer32 | RO | 39 | |||||||||||||||||
column · Integer32 · read-only · current The sensor reading Does not apply (gets will return 0) to onOff, trip, vibration, waterDetection, smokeDetection sensors Example values from LibreNMS test devices
| |||||||||||||||||||||
| Nconformance | 1.3.6.1.4.1.13742.4.9 | ||||||||||||||||||||
| Ncompliances | 1.3.6.1.4.1.13742.4.9.1 | ||||||||||||||||||||
| Mcompliance | 1.3.6.1.4.1.13742.4.9.1.1 | deprecated | |||||||||||||||||||
compliance · deprecated The requirements for conformance to the PDU-MIB. This is deprecated and the new compliance ComplianceRev1 has been added | |||||||||||||||||||||
| McomplianceRev1 | 1.3.6.1.4.1.13742.4.9.1.2 | deprecated | |||||||||||||||||||
compliance · deprecated The requirements for conformance to the PDU-MIB. This is deprecated and the new compliance ComplianceRev2 has been added | |||||||||||||||||||||
| McomplianceRev2 | 1.3.6.1.4.1.13742.4.9.1.3 | deprecated | |||||||||||||||||||
compliance · deprecated The requirements for conformance to the PDU-MIB. This is deprecated and the new compliance ComplianceRev3 has been added | |||||||||||||||||||||
| McomplianceRev3 | 1.3.6.1.4.1.13742.4.9.1.4 | deprecated | |||||||||||||||||||
compliance · deprecated The requirements for conformance to the PDU-MIB.This is deprecated and the new compliance ComplianceRev4 has been added | |||||||||||||||||||||
| McomplianceRev4 | 1.3.6.1.4.1.13742.4.9.1.5 | deprecated | |||||||||||||||||||
compliance · deprecated The requirements for conformance to the PDU-MIB. This is deprecated and the new compliance ComplianceRev5 has been added | |||||||||||||||||||||
| McomplianceRev5 | 1.3.6.1.4.1.13742.4.9.1.6 | ||||||||||||||||||||
compliance · current The requirements for conformance to the PDU-MIB. | |||||||||||||||||||||
| Ngroups | 1.3.6.1.4.1.13742.4.9.2 | ||||||||||||||||||||
| GinfoGroup | 1.3.6.1.4.1.13742.4.9.2.1 | deprecated | |||||||||||||||||||
group · deprecated A collection of objects providing basic information about the pdu.
| |||||||||||||||||||||
| GoutletsGroup | 1.3.6.1.4.1.13742.4.9.2.2 | ||||||||||||||||||||
group · current A collection of objects providing basic information about the outlets, including sensor readings.
| |||||||||||||||||||||
| GunitSensorsGroup | 1.3.6.1.4.1.13742.4.9.2.4 | deprecated | |||||||||||||||||||
group · deprecated A collection of objects providing unit level sensor readings.This group is deprecated in favor of unitSensorsGroupRev
| |||||||||||||||||||||
| GexternalTemperatureGroup | 1.3.6.1.4.1.13742.4.9.2.6 | deprecated | |||||||||||||||||||
group · deprecated A collection of objects providing external temperature sensor readings and threshold settings. This group is deprecated in favor of the externalSensorsGroup | |||||||||||||||||||||
| GexternalHumidityGroup | 1.3.6.1.4.1.13742.4.9.2.7 | deprecated | |||||||||||||||||||
group · deprecated A collection of objects providing external humidity sensor readings and threshold settings. This group is deprecated in favor of the externalSensorsGroup | |||||||||||||||||||||
| GtrapsGroup | 1.3.6.1.4.1.13742.4.9.2.9 | ||||||||||||||||||||
group · current A collection of traps.
| |||||||||||||||||||||
| GlineCurrentGroup | 1.3.6.1.4.1.13742.4.9.2.10 | deprecated | |||||||||||||||||||
group · deprecated A collection of objects describing the line inputs. This group is deprecated in favor of inletPoleGroup
| |||||||||||||||||||||
| GcircuitBreakerGroup | 1.3.6.1.4.1.13742.4.9.2.11 | ||||||||||||||||||||
group · current A collection of objects describing the circuit breakers. | |||||||||||||||||||||
| GlineVoltageGroup | 1.3.6.1.4.1.13742.4.9.2.12 | deprecated | |||||||||||||||||||
group · deprecated A collection of objects describing the line voltages. This group is deprecated in favor of inletPoleGroup
| |||||||||||||||||||||
| GunitSensorsGroupRev | 1.3.6.1.4.1.13742.4.9.2.13 | deprecated | |||||||||||||||||||
group · deprecated A collection of objects providing unit level sensor readings.This group is deprecated in favor of unitSensorsGroupRev2
| |||||||||||||||||||||
| GdataLogGroup | 1.3.6.1.4.1.13742.4.9.2.14 | deprecated | |||||||||||||||||||
group · deprecated A collection of objects describing the pdu data. This group is being deprecated in favor of dataLogGroupRev | |||||||||||||||||||||
| GinletPoleGroup | 1.3.6.1.4.1.13742.4.9.2.15 | ||||||||||||||||||||
group · current A collection of objects describing the inlet poles. | |||||||||||||||||||||
| GinletsGroup | 1.3.6.1.4.1.13742.4.9.2.16 | ||||||||||||||||||||
group · current A collection of objects providing basic information about the inlets, including sensor readings.
| |||||||||||||||||||||
| GdataLogGroupRev | 1.3.6.1.4.1.13742.4.9.2.17 | deprecated | |||||||||||||||||||
group · deprecated A collection of objects describing the pdu data. This group is being deprecated in favor of dataLogGroupRev2
| |||||||||||||||||||||
| GunitSensorsGroupRev2 | 1.3.6.1.4.1.13742.4.9.2.18 | ||||||||||||||||||||
group · current A collection of objects providing unit level sensor readings.
| |||||||||||||||||||||
| GexternalSensorsGroup | 1.3.6.1.4.1.13742.4.9.2.20 | ||||||||||||||||||||
group · current A collection of objects providing external sensor readings and configuration settings.
| |||||||||||||||||||||
| GdataLogGroupRev2 | 1.3.6.1.4.1.13742.4.9.2.21 | ||||||||||||||||||||
group · current A collection of objects describing the pdu data.
| |||||||||||||||||||||
| GinfoGroupRev2 | 1.3.6.1.4.1.13742.4.9.2.22 | ||||||||||||||||||||
group · current A collection of objects providing basic information about the pdu.
| |||||||||||||||||||||
Textual conventions
DegreesCelsiusUnsigned32Display hint:
dData type for reporting thresholds associated with temperature sensors. If the underlying hardware sensor indicates 1 degree Celsius, then the SNMP agent will report a value of 1 degree Celsius. No scaling is performed for this type.
EnabledDisabledEnumerationINTEGERdisabled(0)enabled(1)The status of a PowerCIM
EventDirectionEnumerationINTEGERasserted(0)both(2)deasserted(1)The event direction
EventTypeEnumerationINTEGERaboveUpperCritical(0)aboveUpperNonCritical(1)belowLowerCritical(3)belowLowerNonCritical(2)The event type
HertzUnsigned32Display hint:
dData type for reporting sensor readings and thresholds associated with frequency sensors. If the underlying hardware sensor indicates 1 Hertz, then the SNMP agent will report a value of 1 Hertz. No scaling is performed for this type.
MilliAmpsUnsigned32Display hint:
dData type for reporting sensor readings and thresholds associated with current sensors. If the underlying hardware sensor indicates 1 amp, then the SNMP agent will report a value of 1000 milliamps. The value is scaled in this manner as a way to deal with floating point types that SNMP does not currently support.
MilliVoltsUnsigned32Display hint:
dData type for reporting sensor readings and thresholds associated with voltage sensors. If the underlying hardware sensor indicates 1 volts, then the SNMP agent will report a value of 1000 millivolts. The value is scaled in this manner as a way to deal with floating point types that SNMP does not currently support.
PercentageUnsigned32 (0..100)Display hint:
dData type for reporting values in percentage.
PowerCIMStatusEnumerationINTEGERoff(0)on(1)The status of a PowerCIM
PowerFactorPercentageUnsigned32 (0..100)Display hint:
dData type for reporting sensor readings and thresholds associated with power factor sensors. The power factor of an AC power system is defined as the ratio of the real or active power to the apparent power and is a number between 0 and 1. A PowerFactorPercentage value is calculated by taking this ratio and multiplying by 100. The power factor is used to indicate how efficiently a particular load is utilizing energy.
RelativeHumidityUnsigned32 (0..100)Display hint:
dData type for reporting sensor readings and thresholds associated with humidity sensors. Relative humidity is expressed as percentage and is defined as the ratio of the partial pressure of water vapor in a gaseous mixture of air and water vapor to the saturated vapor pressure of water at a given temperature.
SensorClassEnumerationINTEGERexternalAirFlow(2)externalAirPressure(3)externalHumidity(1)externalTemperature(0)The class of sensor in the event
SensorStateEnumerationINTEGERaboveUpperCritical(4)aboveUpperWarning(2)belowLowerCritical(3)belowLowerWarning(1)ok(0)unavailable(-1)The states a sensor can be in.This enumeration is deprecated starting with PX 1.3.5
SensorTypeEnumerationINTEGERenvironmentalHumidity1(400)environmentalHumidity2(401)environmentalHumidity3(402)environmentalHumidity4(403)environmentalHumidity5(404)environmentalHumidity6(405)environmentalHumidity7(406)environmentalHumidity8(407)environmentalTemp1(300)environmentalTemp2(301)environmentalTemp3(302)environmentalTemp4(303)environmentalTemp5(304)environmentalTemp6(305)environmentalTemp7(306)environmentalTemp8(307)outletActivePower(3)outletApparentPower(4)outletAverageActivePower(6)outletCurrent(0)outletMaxActivePower(5)outletMaxCurrent(1)outletPowerFactor(7)outletVoltage(2)powerBranchCurrent(203)powerBranchFrequency(201)powerBranchTemperature(202)powerBranchVoltage(200)unitActivePower(504)unitApparentPower(505)unitCircuitBreak0Current(600)unitCircuitBreak0State(550)unitCircuitBreak1Current(601)unitCircuitBreak1State(551)unitCircuitBreak2Current(602)unitCircuitBreak2State(552)unitCpuTemp(503)unitFrequency(506)unitMaxRmsCurrent(501)unitRmsCurrent(500)unitVoltage(502)The types a sensor can be. This enumeration is deprecated starting with PX 1.3.5
SensorUnitsEnumerationINTEGERamp(2)cm(17)degreeC(7)degreeF(14)feet(15)g(13)hertz(8)inches(16)meterpersec(10)meters(18)none(-1)other(0)pascal(11)percent(9)psi(12)volt(1)voltamp(4)voltampHour(6)watt(3)wattHour(5)The types a sensor can be.
StateOfSensorEnumerationINTEGERaboveUpperCritical(6)aboveUpperWarning(5)alarmed(11)belowLowerCritical(2)belowLowerWarning(3)closed(1)detected(9)normal(4)notDetected(10)off(8)on(7)open(0)unavailable(-1)The states a sensor can be in.
TenthDegreesCelsiusUnsigned32Display hint:
dData type for reporting sensor readings associated with temperature sensors. If the underlying hardware sensor indicates 1 degree Celsius, then the SNMP agent will report a value of 10 tenth degrees Celsius. The value is scaled in this manner as a way to deal with floating point types that SNMP does not currently support.
TypeOfSensorEnumerationINTEGERactiveEnergy(8)activePower(5)airFlow(12)airPressure(13)apparentEnergy(9)apparentPower(6)binary(19)contact(20)humidity(11)none(31)onOff(14)other(30)peakCurrent(2)powerFactor(7)rmsCurrent(1)rmsVoltage(4)smokeDetection(18)temperature(10)trip(15)unbalancedCurrent(3)vibration(16)waterDetection(17)The types a sensor can be.
VoltAmpsUnsigned32Display hint:
dData type for reporting sensor readings and thresholds associated with apparent power sensors. If the underlying hardware sensor indicates 1 volt-amp, then the SNMP agent will report a value of 1 volt-amp. No scaling is performed for this type.
WattHoursUnsigned32Display hint:
dData type for reporting the active energy
WattsUnsigned32Display hint:
dData type for reporting sensor readings and thresholds associated with active power sensors. If the underlying hardware sensor indicates 1 watt, then the SNMP agent will report a value of 1 watt. No scaling is performed for this type.
Traps / Notifications
- bulkConfigurationCopied
1.3.6.1.4.1.13742.4.0.54 - bulkConfigurationSaved
1.3.6.1.4.1.13742.4.0.53 - circuitBreakerRecovered
1.3.6.1.4.1.13742.4.0.52 - circuitBreakerTripped
1.3.6.1.4.1.13742.4.0.51 - deviceUpdateStarted
1.3.6.1.4.1.13742.4.0.20 - environmentalSensorsConnectivityLost
1.3.6.1.4.1.13742.4.0.55 - environmentalSensorsConnectivityRestored
1.3.6.1.4.1.13742.4.0.57 - externalOnOffSensorStateChange
1.3.6.1.4.1.13742.4.0.56 - fipsModeDisabled
1.3.6.1.4.1.13742.4.0.60 - fipsModeEnabled
1.3.6.1.4.1.13742.4.0.59 - firmwareFileDiscarded
1.3.6.1.4.1.13742.4.0.36 - firmwareValidationFailed
1.3.6.1.4.1.13742.4.0.38 - groupAdded
1.3.6.1.4.1.13742.4.0.14 - groupDeleted
1.3.6.1.4.1.13742.4.0.16 - groupModified
1.3.6.1.4.1.13742.4.0.15 - ipmiOverLANDisabled
1.3.6.1.4.1.13742.4.0.64 - ipmiOverLANEnabled
1.3.6.1.4.1.13742.4.0.63 - logFileCleared
1.3.6.1.4.1.13742.4.0.41 - managingenvironmentalSensor
1.3.6.1.4.1.13742.4.0.61 - outletGroupingConnectivityLost
1.3.6.1.4.1.13742.4.0.50 - passwordSettingsChanged
1.3.6.1.4.1.13742.4.0.28 - powerControl
1.3.6.1.4.1.13742.4.0.23 - rebootCompleted
1.3.6.1.4.1.13742.4.0.2 - rebootStarted
1.3.6.1.4.1.13742.4.0.1 - securityViolation
1.3.6.1.4.1.13742.4.0.39 - thresholdAlarm
1.3.6.1.4.1.13742.4.0.45 - unmanagingenvironmentalSensor
1.3.6.1.4.1.13742.4.0.62 - userAdded
1.3.6.1.4.1.13742.4.0.11 - userAuthenticationFailure
1.3.6.1.4.1.13742.4.0.5 - userBlocked
1.3.6.1.4.1.13742.4.0.22 - userDeleted
1.3.6.1.4.1.13742.4.0.13 - userLogin
1.3.6.1.4.1.13742.4.0.3 - userLogout
1.3.6.1.4.1.13742.4.0.4 - userModified
1.3.6.1.4.1.13742.4.0.12 - userPasswordChanged
1.3.6.1.4.1.13742.4.0.24 - userSessionTimeout
1.3.6.1.4.1.13742.4.0.8 - voltageMeasurementError
1.3.6.1.4.1.13742.4.0.58
Groups and compliance
- circuitBreakerGroup
- compliance
- complianceRev1
- complianceRev2
- complianceRev3
- complianceRev4
- complianceRev5
- dataLogGroup
- dataLogGroupRev
- dataLogGroupRev2
- externalHumidityGroup
- externalSensorsGroup
- externalTemperatureGroup
- infoGroup
- infoGroupRev2
- inletPoleGroup
- inletsGroup
- lineCurrentGroup
- lineVoltageGroup
- outletsGroup
- trapsGroup
- unitSensorsGroup
- unitSensorsGroupRev