TRIPPLITE-MIB
Tripp LiteThis MIB module defines MIB objects which provide mechanisms for remote management capabilities of Tripplite PowerAlert and related software.
snmptranslate -m TRIPPLITE-MIB -Tpsnmpwalk -v2c -c <community> -m TRIPPLITE-MIB <host> 1.3.6.1.4.1.850Imports
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP, OBJECT-GROUP |
|---|---|
| SNMPv2-SMI | Bits, Gauge32, Integer32, IpAddress, MODULE-IDENTITY, MibIdentifier, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, TimeTicks, Unsigned32, enterprises, iso |
| SNMPv2-TC | AutonomousType, DateAndTime, DisplayString, PhysAddress, RowStatus, TEXTUAL-CONVENTION, TimeInterval, TimeStamp, TruthValue, VariablePointer |
| UPS-MIB | NonNegativeInteger, PositiveInteger |
OID tree
| Name | OID | Type | Access | Status | Example | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Itripplite | 1.3.6.1.4.1.850 | ||||||||||||||||||||
identity This MIB module defines MIB objects which provide mechanisms for remote management capabilities of Tripplite PowerAlert and related software. | |||||||||||||||||||||
| NtrippUPS | 1.3.6.1.4.1.850.1 | ||||||||||||||||||||
| NtlV11TrapsPrefix | 1.3.6.1.4.1.850.1.0 | ||||||||||||||||||||
| !tlV11upsCritical | 1.3.6.1.4.1.850.1.0.100 | obsolete | |||||||||||||||||||
| !tlV11upsWarning | 1.3.6.1.4.1.850.1.0.101 | obsolete | |||||||||||||||||||
| !tlV11upsInformation | 1.3.6.1.4.1.850.1.0.102 | obsolete | |||||||||||||||||||
| !tlV11upsAlarmCleared | 1.3.6.1.4.1.850.1.0.103 | obsolete | |||||||||||||||||||
| !tlV11upsAgentStarted | 1.3.6.1.4.1.850.1.0.104 | obsolete | |||||||||||||||||||
| !tlV11upsAgentStopped | 1.3.6.1.4.1.850.1.0.105 | obsolete | |||||||||||||||||||
| NtrippUpsReceptacles | 1.3.6.1.4.1.850.1.1 | ||||||||||||||||||||
| SupsReceptaclesNumReceptacles | 1.3.6.1.4.1.850.1.1.1 | NonNegativeInteger | RO | obsolete | |||||||||||||||||
scalar · NonNegativeInteger · read-only · obsolete The number of available receptacles in this device. This variable indicates the number of rows in the receptacle table. | |||||||||||||||||||||
| TupsReceptacleTable | 1.3.6.1.4.1.850.1.1.2 | NA | obsolete | ||||||||||||||||||
table · not-accessible · obsolete A list of receptacle table entries. The number of entries is given by the value of upsReceptaclesNumReceptacles. | |||||||||||||||||||||
| RupsReceptacleEntry | 1.3.6.1.4.1.850.1.1.2.1 | NA | obsolete | ||||||||||||||||||
row · not-accessible · obsolete An entry containing information applicable to a particular receptacle.
| |||||||||||||||||||||
| CupsReceptacleIndex | 1.3.6.1.4.1.850.1.1.2.1.1 | PositiveInteger | RO | obsolete | |||||||||||||||||
column · PositiveInteger · read-only · obsolete The receptacle identifier. | |||||||||||||||||||||
| CupsReceptacleType | 1.3.6.1.4.1.850.1.1.2.1.2 | INTEGER | RO | obsolete | |||||||||||||||||
column · INTEGER · read-only · obsolete The type of receptacle.
| |||||||||||||||||||||
| CupsReceptacleStatus | 1.3.6.1.4.1.850.1.1.2.1.3 | INTEGER | RO | obsolete | |||||||||||||||||
column · INTEGER · read-only · obsolete The status of receptacle.
| |||||||||||||||||||||
| CupsReceptacleControl | 1.3.6.1.4.1.850.1.1.2.1.4 | INTEGER | RW | obsolete | |||||||||||||||||
column · INTEGER · read-write · obsolete Setting this object to 'on' will turn on the receptacle. Setting this object to 'off' will turn off the receptacle. Setting this object to 'cycle' will turn off and then turn on the receptacle. This action will only take place if the receptacle is controllable (upsReceptacleType = controllableBatteryProtected(3)).
| |||||||||||||||||||||
| NtrippUpsTrapInfo | 1.3.6.1.4.1.850.1.2 | ||||||||||||||||||||
| SupsTrapCode | 1.3.6.1.4.1.850.1.2.1 | INTEGER (0..2147483647) | RO | deprecated | |||||||||||||||||
scalar · INTEGER (0..2147483647) · read-only · deprecated A numeric code identifiying the condition that caused the trap to be sent. If the trap number is 104 (upsAgentStarted) or 105 (upsAgentStopped), this code will indicate whether the SNMP agent is software (1) or hardware (2). | |||||||||||||||||||||
| SupsTrapDescription | 1.3.6.1.4.1.850.1.2.2 | DisplayString (SIZE (0..63)) | RO | deprecated | |||||||||||||||||
scalar · DisplayString (SIZE (0..63)) · read-only · deprecated The description of the trap. | |||||||||||||||||||||
| NtrippUpsEnvironment | 1.3.6.1.4.1.850.1.3 | ||||||||||||||||||||
| SupsEnvTemperature | 1.3.6.1.4.1.850.1.3.1 | Integer32 | RO | obsolete | |||||||||||||||||
scalar · Integer32 · read-only · obsolete The ambient temperature of the EnviroSense unit (1/10 Deg C). | |||||||||||||||||||||
| SupsEnvHumidity | 1.3.6.1.4.1.850.1.3.2 | INTEGER (0..100) | RO | obsolete | |||||||||||||||||
scalar · INTEGER (0..100) · read-only · obsolete The ambient humidity of the EnviroSense unit (% Humidity). | |||||||||||||||||||||
| NtrippUpsContacts | 1.3.6.1.4.1.850.1.4 | ||||||||||||||||||||
| TupsContactTable | 1.3.6.1.4.1.850.1.4.1 | NA | obsolete | ||||||||||||||||||
table · not-accessible · obsolete A table of contacts attached to the EnviroSense unit. | |||||||||||||||||||||
| RupsContactEntry | 1.3.6.1.4.1.850.1.4.1.1 | NA | obsolete | ||||||||||||||||||
row · not-accessible · obsolete An entry containing information applicable to a particular contact.
| |||||||||||||||||||||
| CupsContactIndex | 1.3.6.1.4.1.850.1.4.1.1.1 | PositiveInteger | RO | obsolete | |||||||||||||||||
column · PositiveInteger · read-only · obsolete The contact identifier. | |||||||||||||||||||||
| CupsContactName | 1.3.6.1.4.1.850.1.4.1.1.2 | DisplayString (SIZE (0..15)) | RW | obsolete | |||||||||||||||||
column · DisplayString (SIZE (0..15)) · read-write · obsolete The contact name. | |||||||||||||||||||||
| CupsContactStatus | 1.3.6.1.4.1.850.1.4.1.1.3 | INTEGER | RO | obsolete | |||||||||||||||||
column · INTEGER · read-only · obsolete The current status of the contact.
| |||||||||||||||||||||
| CupsContactConfig | 1.3.6.1.4.1.850.1.4.1.1.4 | INTEGER | RW | obsolete | |||||||||||||||||
column · INTEGER · read-write · obsolete The default configuration of the contact.
| |||||||||||||||||||||
| NtlEnumerations | 1.3.6.1.4.1.850.2 | ||||||||||||||||||||
| NtlOperatingSystems | 1.3.6.1.4.1.850.2.1 | ||||||||||||||||||||
| Nhpux9 | 1.3.6.1.4.1.850.2.1.1 | ||||||||||||||||||||
| Nsunos4 | 1.3.6.1.4.1.850.2.1.2 | ||||||||||||||||||||
| Nsolaris | 1.3.6.1.4.1.850.2.1.3 | ||||||||||||||||||||
| Nosf | 1.3.6.1.4.1.850.2.1.4 | ||||||||||||||||||||
| Nultrix | 1.3.6.1.4.1.850.2.1.5 | ||||||||||||||||||||
| Nhpux10 | 1.3.6.1.4.1.850.2.1.6 | ||||||||||||||||||||
| Nnetbsd1 | 1.3.6.1.4.1.850.2.1.7 | ||||||||||||||||||||
| Nfreebsd | 1.3.6.1.4.1.850.2.1.8 | ||||||||||||||||||||
| Nirix | 1.3.6.1.4.1.850.2.1.9 | ||||||||||||||||||||
| Nlinux | 1.3.6.1.4.1.850.2.1.10 | ||||||||||||||||||||
| Nbsdi | 1.3.6.1.4.1.850.2.1.11 | ||||||||||||||||||||
| Nopenbsd | 1.3.6.1.4.1.850.2.1.12 | ||||||||||||||||||||
| Nwin32 | 1.3.6.1.4.1.850.2.1.13 | ||||||||||||||||||||
| Nhpux11 | 1.3.6.1.4.1.850.2.1.14 | ||||||||||||||||||||
| Nwin9x | 1.3.6.1.4.1.850.2.1.50 | ||||||||||||||||||||
| Nwinnt | 1.3.6.1.4.1.850.2.1.51 | ||||||||||||||||||||
| Nsolspark | 1.3.6.1.4.1.850.2.1.52 | ||||||||||||||||||||
| Nsolintel | 1.3.6.1.4.1.850.2.1.53 | ||||||||||||||||||||
| Naix | 1.3.6.1.4.1.850.2.1.54 | ||||||||||||||||||||
| Nsco | 1.3.6.1.4.1.850.2.1.55 | ||||||||||||||||||||
| Nosx | 1.3.6.1.4.1.850.2.1.56 | ||||||||||||||||||||
| Nunknown | 1.3.6.1.4.1.850.2.1.255 | ||||||||||||||||||||
| NtlConformance | 1.3.6.1.4.1.850.20 | ||||||||||||||||||||
| NtlCompliances | 1.3.6.1.4.1.850.20.1 | ||||||||||||||||||||
| NtlGroups | 1.3.6.1.4.1.850.20.2 | ||||||||||||||||||||
| NtlSubsetGroups | 1.3.6.1.4.1.850.20.2.1 | ||||||||||||||||||||
| NtlBasicGroups | 1.3.6.1.4.1.850.20.2.2 | ||||||||||||||||||||
| NtlFullGroups | 1.3.6.1.4.1.850.20.2.3 | ||||||||||||||||||||
| NtlUpsFullGroups | 1.3.6.1.4.1.850.20.2.3.100 | ||||||||||||||||||||
| GtlUpsFullIdentGroup | 1.3.6.1.4.1.850.20.2.3.100.1 | ||||||||||||||||||||
group · current The tlUpsFullIdentGroup defines objects which are common to the Ident group of fully compliant Tripplite UPS's | |||||||||||||||||||||
| GtlUpsFullBatteryGroup | 1.3.6.1.4.1.850.20.2.3.100.2 | ||||||||||||||||||||
group · current The tlUpsFullBatteryGroup defines objects which are common to the Battery group of fully compliant Tripplite UPS's
| |||||||||||||||||||||
| NtlUpsFullAlarmGroup | 1.3.6.1.4.1.850.20.2.3.100.6 | ||||||||||||||||||||
| GtlUpsFullAlarmObjsGroup | 1.3.6.1.4.1.850.20.2.3.100.6.1 | ||||||||||||||||||||
group · current The tlUpsFullAlarmObjsGroup defines objects which are common to the Alarm group of fully compliant Tripplite UPS's | |||||||||||||||||||||
| GtlUpsFullTestGroup | 1.3.6.1.4.1.850.20.2.3.100.7 | ||||||||||||||||||||
group · current The tlUpsFullTestGroup defines objects which are common to the Test group of fully compliant Tripplite UPS's
| |||||||||||||||||||||
| GtlUpsFullControlGroup | 1.3.6.1.4.1.850.20.2.3.100.8 | ||||||||||||||||||||
group · current The tlUpsFullControlGroup defines objects which are common to the Control group of fully compliant Tripplite UPS's | |||||||||||||||||||||
| GtlUpsFullConfigGroup | 1.3.6.1.4.1.850.20.2.3.100.9 | ||||||||||||||||||||
group · current The tlUpsFullConfigGroup defines objects which are common to the Config group of fully compliant Tripplite UPS's
| |||||||||||||||||||||
| GtlUpsFullOutletGroup | 1.3.6.1.4.1.850.20.2.3.100.10 | ||||||||||||||||||||
group · current The tlUpsFullOutletGroup defines objects which are common to the Outlet group of fully compliant Tripplite UPS's
| |||||||||||||||||||||
| NtlV11Groups | 1.3.6.1.4.1.850.20.2.4 | ||||||||||||||||||||
| GtlDeprecatedV11Group | 1.3.6.1.4.1.850.20.2.4.1 | obsolete | |||||||||||||||||||
group · obsolete The tlDeprecatedV11Group defines objects which were used by Sinetica SNMP cards on Tripplite UPSs and PowerAlert version 11. These objects are currently only used when tlEngineLegacySNMPSupport == true.
| |||||||||||||||||||||
| GtlDeprecatedV11NotificationsGroup | 1.3.6.1.4.1.850.20.2.4.2 | obsolete | |||||||||||||||||||
group · obsolete The tlDeprecatedV11NotificationsGroup defines PowerAlert version 11 notifications. These notifications are being deprecated, but may still be used when tlEngineLegacySNMPSupport = true. | |||||||||||||||||||||
| GtlObsoleteV11Group | 1.3.6.1.4.1.850.20.2.4.3 | obsolete | |||||||||||||||||||
group · obsolete The tlObsoleteV11Group defines objects which were used by Sinetica SNMP cards on Tripplite UPSs. Most of these objects are obsolete. | |||||||||||||||||||||
| NtlUPS | 1.3.6.1.4.1.850.100 | ||||||||||||||||||||
| NtlUpsObjects | 1.3.6.1.4.1.850.100.1 | ||||||||||||||||||||
| NtlUpsIdent | 1.3.6.1.4.1.850.100.1.1 | ||||||||||||||||||||
| StlUpsIdentUpsSoftwareChecksum | 1.3.6.1.4.1.850.100.1.1.1 | Integer32 | RO | 0 | |||||||||||||||||
scalar · Integer32 · read-only · current A checksum for the UPS fostware. Example values from LibreNMS test devices
| |||||||||||||||||||||
| StlUpsIdentSerialNum | 1.3.6.1.4.1.850.100.1.1.2 | DisplayString | RO | upsserialnum | |||||||||||||||||
scalar · DisplayString · read-only · current Serial number for the UPS. Example values from LibreNMS test devices
| |||||||||||||||||||||
| StlUpsIdentID | 1.3.6.1.4.1.850.100.1.1.3 | Integer32 (0..65535) | RW | 65535 | |||||||||||||||||
scalar · Integer32 (0..65535) · read-write · current A user-supplied ID for the UPS. Example values from LibreNMS test devices
| |||||||||||||||||||||
| StlUpsSnmpCardSerialNum | 1.3.6.1.4.1.850.100.1.1.4 | DisplayString | RO | snmpcardserialnum | |||||||||||||||||
scalar · DisplayString · read-only · current Serial number for the UPS. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NtlUpsBattery | 1.3.6.1.4.1.850.100.1.2 | ||||||||||||||||||||
| StlUpsBatteryAge | 1.3.6.1.4.1.850.100.1.2.1 | DisplayString | RO | 4.6 | |||||||||||||||||
scalar · DisplayString · read-only · current The age of the battery, in the format YYYYMMDD. This is equal to the current date minus tlConfigBattReplDate. Example values from LibreNMS test devices
| |||||||||||||||||||||
| StlUpsTemperatureF | 1.3.6.1.4.1.850.100.1.2.2 | Integer32 | RO | 752 | |||||||||||||||||
scalar · Integer32 · read-only · current The temperature of the battery, in Farenheight degrees. This is calculated from upsBatteryTemperature, which is in Celsius degrees. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NtlUpsInput | 1.3.6.1.4.1.850.100.1.3 | ||||||||||||||||||||
| NtlUpsOutput | 1.3.6.1.4.1.850.100.1.4 | ||||||||||||||||||||
| NtlUpsBypass | 1.3.6.1.4.1.850.100.1.5 | ||||||||||||||||||||
| NtlUpsAlarm | 1.3.6.1.4.1.850.100.1.6 | ||||||||||||||||||||
| StlUpsAlarmsPresent | 1.3.6.1.4.1.850.100.1.6.1 | Gauge32 | RO | 2 | |||||||||||||||||
scalar · Gauge32 · read-only · current The present number of active alarm conditions. Example values from LibreNMS test devices
| |||||||||||||||||||||
| TtlUpsAlarmTable | 1.3.6.1.4.1.850.100.1.6.2 | NA | |||||||||||||||||||
table · not-accessible · current A list of alarm table entries. | |||||||||||||||||||||
| RtlUpsAlarmEntry | 1.3.6.1.4.1.850.100.1.6.2.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing information applicable to a particular alarm.
| |||||||||||||||||||||
| CtlUpsAlarmId | 1.3.6.1.4.1.850.100.1.6.2.1.1 | PositiveInteger | RO | 5679 | |||||||||||||||||
column · PositiveInteger · read-only · current A unique identifier for an alarm condition. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlUpsAlarmDescr | 1.3.6.1.4.1.850.100.1.6.2.1.2 | OCTET STRING | RO | 1.3.6.1.4.1.850.100.1.6.3.8 | |||||||||||||||||
column · OCTET STRING · read-only · current A description of the alarm condition. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlUpsAlarmTime | 1.3.6.1.4.1.850.100.1.6.2.1.3 | INTEGER | RO | 27800 | |||||||||||||||||
column · INTEGER · read-only · current The value of sysUpTime when the alarm condition was detected. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlUpsAlarmDetail | 1.3.6.1.4.1.850.100.1.6.2.1.4 | DisplayString | RO | Battery Bad | |||||||||||||||||
column · DisplayString · read-only · current A textual description of the alarm condition. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlUpsAlarmDeviceId | 1.3.6.1.4.1.850.100.1.6.2.1.5 | PositiveInteger | RO | 1 | |||||||||||||||||
column · PositiveInteger · read-only · current A numeric identifier for the device on which the alarm is active. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlUpsAlarmDeviceName | 1.3.6.1.4.1.850.100.1.6.2.1.6 | DisplayString | RO | Device 1 | |||||||||||||||||
column · DisplayString · read-only · current A string identifier for the device on which the alarm is active. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlUpsAlarmLocation | 1.3.6.1.4.1.850.100.1.6.2.1.7 | DisplayString | RO | | |||||||||||||||||
column · DisplayString · read-only · current The location of the device on which the alarm is active. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlUpsAlarmGroup | 1.3.6.1.4.1.850.100.1.6.2.1.8 | INTEGER | RO | critical(1) | |||||||||||||||||
column · INTEGER · read-only · current The category/group of this alarm.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlUpsAlarmIp | 1.3.6.1.4.1.850.100.1.6.2.1.9 | DisplayString | RO | 10.0.0.10 | |||||||||||||||||
column · DisplayString · read-only · current The originating IP address associated with this alarm. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlUpsAlarmMac | 1.3.6.1.4.1.850.100.1.6.2.1.10 | DisplayString | RO | 30:30:3a:34:30:3a:39:44:3a:34:33:3a:33:35:3a:39… | |||||||||||||||||
column · DisplayString · read-only · current The originating mac address associated with this alarm. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NtlUpsWellKnownAlarms | 1.3.6.1.4.1.850.100.1.6.3 | ||||||||||||||||||||
| NtlUpsAlarmPrimaryPowerOutage | 1.3.6.1.4.1.850.100.1.6.3.1 | ||||||||||||||||||||
node · current The primary power source is not present. | |||||||||||||||||||||
| NtlUpsAlarmSecondaryPowerOutage | 1.3.6.1.4.1.850.100.1.6.3.2 | ||||||||||||||||||||
node · current The secondary power source is not present. | |||||||||||||||||||||
| NtlUpsAlarmLoadLevelAboveThreshold | 1.3.6.1.4.1.850.100.1.6.3.3 | ||||||||||||||||||||
node · current The load level is above the designated threshold. | |||||||||||||||||||||
| NtlUpsAlarmOutputCurrentChanged | 1.3.6.1.4.1.850.100.1.6.3.4 | ||||||||||||||||||||
node · current The output current changed from its last known value. | |||||||||||||||||||||
| StlUpsAlarmDevName | 1.3.6.1.4.1.850.100.1.6.7 | DisplayString | RO | deprecated | |||||||||||||||||
scalar · DisplayString · read-only · deprecated The name of the device, tlDevName, corresponding to the device that is associated with this alarm. | |||||||||||||||||||||
| StlUpsAlarmDevLocation | 1.3.6.1.4.1.850.100.1.6.8 | DisplayString | RO | deprecated | |||||||||||||||||
scalar · DisplayString · read-only · deprecated The location of the device, tlDevLocation, corresponding to the device that is associated with this alarm. | |||||||||||||||||||||
| StlUpsAlarmCategory | 1.3.6.1.4.1.850.100.1.6.9 | Integer32 | RO | deprecated | |||||||||||||||||
scalar · Integer32 · read-only · deprecated The category, tlDevEvtCategory, of this alarm. | |||||||||||||||||||||
| NtlUpsTest | 1.3.6.1.4.1.850.100.1.7 | ||||||||||||||||||||
| StlUpsTestDate | 1.3.6.1.4.1.850.100.1.7.1 | DisplayString | RO | 2020-05-26 | |||||||||||||||||
scalar · DisplayString · read-only · current The date of the last self-test run on the ups, in the format YYYYMMDD. Example values from LibreNMS test devices
| |||||||||||||||||||||
| StlUpsTestResultsDetail | 1.3.6.1.4.1.850.100.1.7.2 | DisplayString | RO | Done and Error | |||||||||||||||||
scalar · DisplayString · read-only · current Result of the last self-test run on the ups. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NtlUpsControl | 1.3.6.1.4.1.850.100.1.8 | ||||||||||||||||||||
| StlUpsWatchdogSupported | 1.3.6.1.4.1.850.100.1.8.1 | TruthValue | RO | 0 | |||||||||||||||||
scalar · TruthValue · read-only · current Indicates whether or not this UPS supports a watchdog reboot. Example values from LibreNMS test devices
| |||||||||||||||||||||
| StlUpsWatchdogSecsBeforeReboot | 1.3.6.1.4.1.850.100.1.8.2 | NonNegativeInteger | RW | 0 | |||||||||||||||||
scalar · NonNegativeInteger · read-write · current The maximum number of seconds that can expire between polls that the engine makes to the UPS for data. If this time runs out, then the UPS will cycle its outputs. Set this to zero to turns disable this feature. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NtlUpsWellKnownControls | 1.3.6.1.4.1.850.100.1.8.3 | ||||||||||||||||||||
| StlUpsControlSelfTest | 1.3.6.1.4.1.850.100.1.8.3.1 | TruthValue | RW | 1 | |||||||||||||||||
scalar · TruthValue · read-write · current Set to TRUE to initiate Self Test Example values from LibreNMS test devices
| |||||||||||||||||||||
| StlUpsControlRamp | 1.3.6.1.4.1.850.100.1.8.3.2 | TruthValue | RW | 1 | |||||||||||||||||
scalar · TruthValue · read-write · current Set to TRUE to initiate Ramp Example values from LibreNMS test devices
| |||||||||||||||||||||
| StlUpsControlShed | 1.3.6.1.4.1.850.100.1.8.3.3 | TruthValue | RW | 1 | |||||||||||||||||
scalar · TruthValue · read-write · current Set to TRUE to initiate Shed Example values from LibreNMS test devices
| |||||||||||||||||||||
| StlUpsControlUpsOn | 1.3.6.1.4.1.850.100.1.8.3.4 | TruthValue | RW | 1 | |||||||||||||||||
scalar · TruthValue · read-write · current Set to TRUE to turn UPS on Example values from LibreNMS test devices
| |||||||||||||||||||||
| StlUpsControlUpsOff | 1.3.6.1.4.1.850.100.1.8.3.5 | TruthValue | RW | 2 | |||||||||||||||||
scalar · TruthValue · read-write · current Set to TRUE to turn UPS off Example values from LibreNMS test devices
| |||||||||||||||||||||
| NtlUpsConfig | 1.3.6.1.4.1.850.100.1.9 | ||||||||||||||||||||
| StlUpsConfigBattReplDate | 1.3.6.1.4.1.850.100.1.9.1 | DisplayString | RW | ||||||||||||||||||
scalar · DisplayString · read-write · current The date on which the battery was last replaced, in the format YYYYMMDD. | |||||||||||||||||||||
| StlUpsConfigTftpGetAddr | 1.3.6.1.4.1.850.100.1.9.2 | IpAddress | RW | ||||||||||||||||||
scalar · IpAddress · read-write · current The IP address of the TFTP server you wish to acquire a config ini file from, non persistent, 0.0.0.0 when empty | |||||||||||||||||||||
| StlUpsConfigTftpGetAcction | 1.3.6.1.4.1.850.100.1.9.3 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current setting this entry to get(1) will start a down load from the specified address, during the download this entry will read getting(2), when finished, the card will reboot to the new ini supplied parms. At all other times this entry will read idle(3)
| |||||||||||||||||||||
| NtlUpsOutlet | 1.3.6.1.4.1.850.100.1.10 | ||||||||||||||||||||
| StlUpsOutletNumOutlets | 1.3.6.1.4.1.850.100.1.10.1 | NonNegativeInteger | RO | 3 | |||||||||||||||||
scalar · NonNegativeInteger · read-only · current The number of available Outlets in this device. Example values from LibreNMS test devices
| |||||||||||||||||||||
| TtlUpsOutletTable | 1.3.6.1.4.1.850.100.1.10.2 | NA | |||||||||||||||||||
table · not-accessible · current A list of all device Outlets for all devices. | |||||||||||||||||||||
| RtlUpsOutletEntry | 1.3.6.1.4.1.850.100.1.10.2.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing Outlet information applicable to a particular device managed by this agent.
| |||||||||||||||||||||
| CtlUpsOutletIndex | 1.3.6.1.4.1.850.100.1.10.2.1.1 | PositiveInteger | RO | 1 | |||||||||||||||||
column · PositiveInteger · read-only · current This is the index number of this Outlet for the device indicated by tlDeviceIndex. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlUpsOutletState | 1.3.6.1.4.1.850.100.1.10.2.1.2 | INTEGER | RO | on(2) | |||||||||||||||||
column · INTEGER · read-only · current The current state of the Outlet.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlUpsOutletType | 1.3.6.1.4.1.850.100.1.10.2.1.3 | Integer32 | RO | 2 | |||||||||||||||||
column · Integer32 · read-only · current This is a bit field that indicates the type of this Outlet. Bit Display 0 Battery Protected 1 Controllable 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlUpsOutletControl | 1.3.6.1.4.1.850.100.1.10.2.1.4 | INTEGER | RW | 0 | |||||||||||||||||
column · INTEGER · read-write · current Controls the state of the Outlet.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlUpsOutletName | 1.3.6.1.4.1.850.100.1.10.2.1.5 | DisplayString | RW | | |||||||||||||||||
column · DisplayString · read-write · current A string identifying the devices attached to the output(s) of the device. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlUpsOutletRampAction | 1.3.6.1.4.1.850.100.1.10.2.1.6 | INTEGER | RW | remainOff(0) | |||||||||||||||||
column · INTEGER · read-write · current The ramp action to take on the Outlet.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlUpsOutletRampDataType | 1.3.6.1.4.1.850.100.1.10.2.1.7 | INTEGER | RW | delayInSeconds(0) | |||||||||||||||||
column · INTEGER · read-write · current The type of data associated with ramp action.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlUpsOutletRampData | 1.3.6.1.4.1.850.100.1.10.2.1.8 | Integer32 | RW | 0 | |||||||||||||||||
column · Integer32 · read-write · current The data value associated with type of ramp data. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlUpsOutletShedAction | 1.3.6.1.4.1.850.100.1.10.2.1.9 | INTEGER | RW | remainOn(0) | |||||||||||||||||
column · INTEGER · read-write · current The shed action to take on the Outlet.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlUpsOutletShedDataType | 1.3.6.1.4.1.850.100.1.10.2.1.10 | INTEGER | RW | delayInSeconds(0) | |||||||||||||||||
column · INTEGER · read-write · current The type of data associated with shed action.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlUpsOutletShedData | 1.3.6.1.4.1.850.100.1.10.2.1.11 | Integer32 | RW | 0 | |||||||||||||||||
column · Integer32 · read-write · current The data value associated with type of shed data. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlUpsOutletGroupNdx | 1.3.6.1.4.1.850.100.1.10.2.1.12 | Integer32 | RW | 0 | |||||||||||||||||
column · Integer32 · read-write · current tlUpsOutletGroupIndex of corresponding outlet group, or 0 if ungrouped. Example values from LibreNMS test devices
| |||||||||||||||||||||
| TtlUpsOutletCurrentTable | 1.3.6.1.4.1.850.100.1.10.3 | NA | |||||||||||||||||||
table · not-accessible · current A list of load currents. | |||||||||||||||||||||
| RtlUpsOutletCurrentEntry | 1.3.6.1.4.1.850.100.1.10.3.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing Outlet current information applicable to a particular device managed by this agent. | |||||||||||||||||||||
| CtlUpsOutletCurrentIndex | 1.3.6.1.4.1.850.100.1.10.3.1.1 | PositiveInteger | RO | ||||||||||||||||||
column · PositiveInteger · read-only · current This is the index number of this Outlet. | |||||||||||||||||||||
| CtlUpsOutletCurrentValue | 1.3.6.1.4.1.850.100.1.10.3.1.2 | PositiveInteger | RO | ||||||||||||||||||
column · PositiveInteger · read-only · current The value of this outlet's current, represented as 0.1A | |||||||||||||||||||||
| TtlUpsOutletPowerTable | 1.3.6.1.4.1.850.100.1.10.4 | NA | |||||||||||||||||||
table · not-accessible · current A list of load power. | |||||||||||||||||||||
| RtlUpsOutletPowerEntry | 1.3.6.1.4.1.850.100.1.10.4.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing Outlet power information applicable to a particular device managed by this agent. | |||||||||||||||||||||
| CtlUpsOutletPowerIndex | 1.3.6.1.4.1.850.100.1.10.4.1.1 | PositiveInteger | RO | ||||||||||||||||||
column · PositiveInteger · read-only · current This is the index number of this Outlet. | |||||||||||||||||||||
| CtlUpsOutletPowerValue | 1.3.6.1.4.1.850.100.1.10.4.1.2 | PositiveInteger | RO | ||||||||||||||||||
column · PositiveInteger · read-only · current The value of this outlet's power in watts. | |||||||||||||||||||||
| NtlUpsOutletGroup | 1.3.6.1.4.1.850.100.1.11 | ||||||||||||||||||||
| StlUpsOutletNumOutletGroups | 1.3.6.1.4.1.850.100.1.11.1 | NonNegativeInteger | RO | 0 | |||||||||||||||||
scalar · NonNegativeInteger · read-only · current The number of available Outlet Groups in this device. Example values from LibreNMS test devices
| |||||||||||||||||||||
| TtlUpsOutletGroupTable | 1.3.6.1.4.1.850.100.1.11.2 | NA | |||||||||||||||||||
table · not-accessible · current A list of device outlet group entries. The number of entries is given by the value of tlUpsOutletNumOutletGroups. | |||||||||||||||||||||
| RtlUpsOutletGroupEntry | 1.3.6.1.4.1.850.100.1.11.2.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing outlet group information applicable to a particular device managed by this agent | |||||||||||||||||||||
| CtlUpsOutletGroupIndex | 1.3.6.1.4.1.850.100.1.11.2.1.1 | PositiveInteger | RO | ||||||||||||||||||
column · PositiveInteger · read-only · current This is the index number of this load group for the device. | |||||||||||||||||||||
| CtlUpsOutletGroupUnused | 1.3.6.1.4.1.850.100.1.11.2.1.2 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Unused placeholder | |||||||||||||||||||||
| CtlUpsOutletGroupName | 1.3.6.1.4.1.850.100.1.11.2.1.3 | DisplayString | RW | ||||||||||||||||||
column · DisplayString · read-write · current The name of this outlet group. | |||||||||||||||||||||
| CtlUpsOutletGroupDesc | 1.3.6.1.4.1.850.100.1.11.2.1.4 | DisplayString | RW | ||||||||||||||||||
column · DisplayString · read-write · current A description for this outlet group. | |||||||||||||||||||||
| CtlUpsOutletGroupState | 1.3.6.1.4.1.850.100.1.11.2.1.5 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current The current state of the outlet group.
| |||||||||||||||||||||
| CtlUpsOutletGroupControl | 1.3.6.1.4.1.850.100.1.11.2.1.6 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current Controls the state of every outlet associated with the group.
| |||||||||||||||||||||
| NtlUpsTraps | 1.3.6.1.4.1.850.100.2 | ||||||||||||||||||||
| !tlUpsTrapAlarmEntryAddedV1 | 1.3.6.1.4.1.850.100.2.0.3 | ||||||||||||||||||||
notification This trap is sent each time an alarm is inserted into to the alarm table. | |||||||||||||||||||||
| !tlUpsTrapAlarmEntryRemovedV1 | 1.3.6.1.4.1.850.100.2.0.4 | ||||||||||||||||||||
notification This trap is sent each time an alarm is removed from the alarm table. | |||||||||||||||||||||
| !tlUpsTrapAlarmEntryAdded | 1.3.6.1.4.1.850.100.2.3 | ||||||||||||||||||||
notification · current This trap is sent each time an alarm is inserted into to the alarm table. | |||||||||||||||||||||
| !tlUpsTrapAlarmEntryRemoved | 1.3.6.1.4.1.850.100.2.4 | ||||||||||||||||||||
notification · current This trap is sent each time an alarm is removed from the alarm table. | |||||||||||||||||||||
| NtlEnviroSense | 1.3.6.1.4.1.850.101 | ||||||||||||||||||||
| NtlEnvEnvironment | 1.3.6.1.4.1.850.101.1 | ||||||||||||||||||||
| NtlEnvTemperatureData | 1.3.6.1.4.1.850.101.1.1 | ||||||||||||||||||||
| StlEnvTemperatureC | 1.3.6.1.4.1.850.101.1.1.1 | Integer32 | RO | 22 | |||||||||||||||||
scalar · Integer32 · read-only · current The ambient temperature (C). Example values from LibreNMS test devices
| |||||||||||||||||||||
| StlEnvTemperatureF | 1.3.6.1.4.1.850.101.1.1.2 | Integer32 | RO | 71 | |||||||||||||||||
scalar · Integer32 · read-only · current The ambient temperature (F). Example values from LibreNMS test devices
| |||||||||||||||||||||
| StlEnvTemperatureLowLimit | 1.3.6.1.4.1.850.101.1.1.3 | Integer32 | RW | 40 | |||||||||||||||||
scalar · Integer32 · read-write · current The lower alarm limit for ambient temperature (F). Example values from LibreNMS test devices
| |||||||||||||||||||||
| StlEnvTemperatureHighLimit | 1.3.6.1.4.1.850.101.1.1.4 | Integer32 | RW | 95 | |||||||||||||||||
scalar · Integer32 · read-write · current The upper alarm limit for ambient temperature (F). Example values from LibreNMS test devices
| |||||||||||||||||||||
| StlEnvTemperatureInAlarm | 1.3.6.1.4.1.850.101.1.1.5 | TruthValue | RO | 2 | |||||||||||||||||
scalar · TruthValue · read-only · current Indicates whether or not temperature is in alarm. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NtlEnvHumidityData | 1.3.6.1.4.1.850.101.1.2 | ||||||||||||||||||||
| StlEnvHumidity | 1.3.6.1.4.1.850.101.1.2.1 | Integer32 | RO | 18 | |||||||||||||||||
scalar · Integer32 · read-only · current The ambient humidity (%). Example values from LibreNMS test devices
| |||||||||||||||||||||
| StlEnvHumidityLowLimit | 1.3.6.1.4.1.850.101.1.2.2 | Integer32 | RW | 5 | |||||||||||||||||
scalar · Integer32 · read-write · current The lower alarm limit for ambient humidity (%). Example values from LibreNMS test devices
| |||||||||||||||||||||
| StlEnvHumidityHighLimit | 1.3.6.1.4.1.850.101.1.2.3 | Integer32 | RW | 80 | |||||||||||||||||
scalar · Integer32 · read-write · current The upper alarm limit for ambient humidity (%). Example values from LibreNMS test devices
| |||||||||||||||||||||
| StlEnvHumidityInAlarm | 1.3.6.1.4.1.850.101.1.2.4 | TruthValue | RO | 2 | |||||||||||||||||
scalar · TruthValue · read-only · current Indicates whether or not humidity is in alarm. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NtlEnvContacts | 1.3.6.1.4.1.850.101.2 | ||||||||||||||||||||
| TtlEnvContactTable | 1.3.6.1.4.1.850.101.2.1 | NA | |||||||||||||||||||
table · not-accessible · current A table of contacts. | |||||||||||||||||||||
| RtlEnvContactEntry | 1.3.6.1.4.1.850.101.2.1.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing information applicable to a particular contact.
| |||||||||||||||||||||
| CtlEnvContactIndex | 1.3.6.1.4.1.850.101.2.1.1.1 | PositiveInteger | RO | 1 | |||||||||||||||||
column · PositiveInteger · read-only · current The table row index for the contact. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlEnvContactName | 1.3.6.1.4.1.850.101.2.1.1.2 | DisplayString | RW | Contact Input #1 | |||||||||||||||||
column · DisplayString · read-write · current The name or description of the contact. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlEnvContactStatus | 1.3.6.1.4.1.850.101.2.1.1.3 | INTEGER | RO | normal(0) | |||||||||||||||||
column · INTEGER · read-only · current The current status of the contact.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlEnvContactConfig | 1.3.6.1.4.1.850.101.2.1.1.4 | INTEGER | RW | normallyOpen(0) | |||||||||||||||||
column · INTEGER · read-write · current The configuration of the contact.
Example values from LibreNMS test devices
| |||||||||||||||||||||
Traps / Notifications
- tlUpsTrapAlarmEntryAdded
1.3.6.1.4.1.850.100.2.3 - tlUpsTrapAlarmEntryAddedV1
1.3.6.1.4.1.850.100.2.0.3 - tlUpsTrapAlarmEntryRemoved
1.3.6.1.4.1.850.100.2.4 - tlUpsTrapAlarmEntryRemovedV1
1.3.6.1.4.1.850.100.2.0.4 - tlV11upsAgentStarted
1.3.6.1.4.1.850.1.0.104 - tlV11upsAgentStopped
1.3.6.1.4.1.850.1.0.105 - tlV11upsAlarmCleared
1.3.6.1.4.1.850.1.0.103 - tlV11upsCritical
1.3.6.1.4.1.850.1.0.100 - tlV11upsInformation
1.3.6.1.4.1.850.1.0.102 - tlV11upsWarning
1.3.6.1.4.1.850.1.0.101