TRIPPLITE-12X
Tripp LiteThis MIB module defines MIB objects which provide mechanisms for remote management capabilities of Tripplite PowerAlert and related software.
snmptranslate -m TRIPPLITE-12X -Tpsnmpwalk -v2c -c <community> -m TRIPPLITE-12X <host> 1.3.6.1.4.1.850.90Imports
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP, OBJECT-GROUP |
|---|---|
| SNMPv2-SMI | Bits, Gauge32, Integer32, IpAddress, MODULE-IDENTITY, MibIdentifier, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, TRAP-TYPE, TimeTicks, Unsigned32, iso |
| SNMPv2-TC | AutonomousType, DateAndTime, DisplayString, PhysAddress, RowStatus, TEXTUAL-CONVENTION, TimeInterval, TimeStamp, TruthValue, VariablePointer |
| TRIPPLITE | tripplite |
| UPS-MIB | NonNegativeInteger, PositiveInteger |
OID tree
| Name | OID | Type | Access | Status | Example | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| NtlEnumerations | 1.3.6.1.4.1.850.2 | ||||||||||||||||||||
| NtlOperatingSystems | 1.3.6.1.4.1.850.2.1 | ||||||||||||||||||||
| Nhpux9 | 1.3.6.1.4.1.850.2.1.1 | ||||||||||||||||||||
| Nsunos4 | 1.3.6.1.4.1.850.2.1.2 | ||||||||||||||||||||
| Nsolaris | 1.3.6.1.4.1.850.2.1.3 | ||||||||||||||||||||
| Nosf | 1.3.6.1.4.1.850.2.1.4 | ||||||||||||||||||||
| Nultrix | 1.3.6.1.4.1.850.2.1.5 | ||||||||||||||||||||
| Nhpux10 | 1.3.6.1.4.1.850.2.1.6 | ||||||||||||||||||||
| Nnetbsd1 | 1.3.6.1.4.1.850.2.1.7 | ||||||||||||||||||||
| Nfreebsd | 1.3.6.1.4.1.850.2.1.8 | ||||||||||||||||||||
| Nirix | 1.3.6.1.4.1.850.2.1.9 | ||||||||||||||||||||
| Nlinux | 1.3.6.1.4.1.850.2.1.10 | ||||||||||||||||||||
| Nbsdi | 1.3.6.1.4.1.850.2.1.11 | ||||||||||||||||||||
| Nopenbsd | 1.3.6.1.4.1.850.2.1.12 | ||||||||||||||||||||
| Nwin32 | 1.3.6.1.4.1.850.2.1.13 | ||||||||||||||||||||
| Nhpux11 | 1.3.6.1.4.1.850.2.1.14 | ||||||||||||||||||||
| Nwin9x | 1.3.6.1.4.1.850.2.1.50 | ||||||||||||||||||||
| Nwinnt | 1.3.6.1.4.1.850.2.1.51 | ||||||||||||||||||||
| Nsolspark | 1.3.6.1.4.1.850.2.1.52 | ||||||||||||||||||||
| Nsolintel | 1.3.6.1.4.1.850.2.1.53 | ||||||||||||||||||||
| Naix | 1.3.6.1.4.1.850.2.1.54 | ||||||||||||||||||||
| Nsco | 1.3.6.1.4.1.850.2.1.55 | ||||||||||||||||||||
| Nosx | 1.3.6.1.4.1.850.2.1.56 | ||||||||||||||||||||
| Nunknown | 1.3.6.1.4.1.850.2.1.255 | ||||||||||||||||||||
| NtlConformance | 1.3.6.1.4.1.850.20 | ||||||||||||||||||||
| NtlCompliances | 1.3.6.1.4.1.850.20.1 | ||||||||||||||||||||
| NtlGroups | 1.3.6.1.4.1.850.20.2 | ||||||||||||||||||||
| NtlSubsetGroups | 1.3.6.1.4.1.850.20.2.1 | ||||||||||||||||||||
| NtlBasicGroups | 1.3.6.1.4.1.850.20.2.2 | ||||||||||||||||||||
| NtlFullGroups | 1.3.6.1.4.1.850.20.2.3 | ||||||||||||||||||||
| NtlUpsFullGroups | 1.3.6.1.4.1.850.20.2.3.100 | ||||||||||||||||||||
| GtlUpsFullIdentGroup | 1.3.6.1.4.1.850.20.2.3.100.1 | ||||||||||||||||||||
group · current The tlUpsFullIdentGroup defines objects which are common to the Ident group of fully compliant Tripplite UPS's | |||||||||||||||||||||
| GtlUpsFullBatteryGroup | 1.3.6.1.4.1.850.20.2.3.100.2 | ||||||||||||||||||||
group · current The tlUpsFullBatteryGroup defines objects which are common to the Battery group of fully compliant Tripplite UPS's
| |||||||||||||||||||||
| NtlUpsFullAlarmGroup | 1.3.6.1.4.1.850.20.2.3.100.6 | ||||||||||||||||||||
| GtlUpsFullAlarmObjsGroup | 1.3.6.1.4.1.850.20.2.3.100.6.1 | ||||||||||||||||||||
group · current The tlUpsFullAlarmObjsGroup defines objects which are common to the Alarm group of fully compliant Tripplite UPS's | |||||||||||||||||||||
| GtlUpsFullTestGroup | 1.3.6.1.4.1.850.20.2.3.100.7 | ||||||||||||||||||||
group · current The tlUpsFullTestGroup defines objects which are common to the Test group of fully compliant Tripplite UPS's
| |||||||||||||||||||||
| GtlUpsFullControlGroup | 1.3.6.1.4.1.850.20.2.3.100.8 | ||||||||||||||||||||
group · current The tlUpsFullControlGroup defines objects which are common to the Control group of fully compliant Tripplite UPS's | |||||||||||||||||||||
| GtlUpsFullConfigGroup | 1.3.6.1.4.1.850.20.2.3.100.9 | ||||||||||||||||||||
group · current The tlUpsFullConfigGroup defines objects which are common to the Config group of fully compliant Tripplite UPS's
| |||||||||||||||||||||
| GtlUpsFullOutletGroup | 1.3.6.1.4.1.850.20.2.3.100.10 | ||||||||||||||||||||
group · current The tlUpsFullOutletGroup defines objects which are common to the Outlet group of fully compliant Tripplite UPS's
| |||||||||||||||||||||
| ItlPowerAlert | 1.3.6.1.4.1.850.90 | ||||||||||||||||||||
identity This MIB module defines MIB objects which provide mechanisms for remote management capabilities of Tripplite PowerAlert and related software. | |||||||||||||||||||||
| NtlPASystem | 1.3.6.1.4.1.850.90.1 | ||||||||||||||||||||
| NtlPAContacts | 1.3.6.1.4.1.850.90.1.1 | ||||||||||||||||||||
| NtlPAEmailContacts | 1.3.6.1.4.1.850.90.1.1.1 | ||||||||||||||||||||
| StlPANumberOfEmailContacts | 1.3.6.1.4.1.850.90.1.1.1.1 | NonNegativeInteger | RO | 2 | |||||||||||||||||
scalar · NonNegativeInteger · read-only · current The number email contacts currently defined. Example values from LibreNMS test devices
| |||||||||||||||||||||
| TtlPAEmailContactsTable | 1.3.6.1.4.1.850.90.1.1.1.2 | NA | |||||||||||||||||||
table · not-accessible · current A list email contact entries. The number of entries is given by the value of tlPANumberOfEmailContacts. | |||||||||||||||||||||
| RtlPAEmailContactEntry | 1.3.6.1.4.1.850.90.1.1.1.2.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing email contacts information. | |||||||||||||||||||||
| CtlPAEmailContactIndex | 1.3.6.1.4.1.850.90.1.1.1.2.1.1 | PositiveInteger | RO | 1 | |||||||||||||||||
column · PositiveInteger · read-only · current This is the index number of the email contact. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlPAEmailContactRowStatus | 1.3.6.1.4.1.850.90.1.1.1.2.1.2 | RowStatus | RW | 1 | |||||||||||||||||
column · RowStatus · read-write · current The row status for the tlPAEmailContactTable row Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlPAEmailContactName | 1.3.6.1.4.1.850.90.1.1.1.2.1.3 | DisplayString | RW | IT Notify | |||||||||||||||||
column · DisplayString · read-write · current The name of the email contact. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlPAEmailContactAddress | 1.3.6.1.4.1.850.90.1.1.1.2.1.4 | DisplayString | RW | [email protected] | |||||||||||||||||
column · DisplayString · read-write · current The address of the email contact. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NtlPASnmpContacts | 1.3.6.1.4.1.850.90.1.1.2 | ||||||||||||||||||||
| StlPANumberOfSnmpContacts | 1.3.6.1.4.1.850.90.1.1.2.1 | NonNegativeInteger | RO | 1 | |||||||||||||||||
scalar · NonNegativeInteger · read-only · current The number SNMP contacts currently defined. Example values from LibreNMS test devices
| |||||||||||||||||||||
| TtlPASnmpContactsTable | 1.3.6.1.4.1.850.90.1.1.2.2 | NA | |||||||||||||||||||
table · not-accessible · current A list SNMP contact entries. The number of entries is given by the value of tlPANumberOfSnmpContacts. | |||||||||||||||||||||
| RtlPASnmpContactEntry | 1.3.6.1.4.1.850.90.1.1.2.2.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing SNMP contacts information.
| |||||||||||||||||||||
| CtlPASnmpContactIndex | 1.3.6.1.4.1.850.90.1.1.2.2.1.1 | PositiveInteger | RO | 1 | |||||||||||||||||
column · PositiveInteger · read-only · current This is the index number of this SNMP contact. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlPASnmpContactRowStatus | 1.3.6.1.4.1.850.90.1.1.2.2.1.2 | RowStatus | RW | 1 | |||||||||||||||||
column · RowStatus · read-write · current The row status for the tlPASnmpContactTable row Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlPASnmpContactName | 1.3.6.1.4.1.850.90.1.1.2.2.1.3 | DisplayString | RW | public SNMP Trap | |||||||||||||||||
column · DisplayString · read-write · current The name of the SNMP contact. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlPASnmpContactIpAddress | 1.3.6.1.4.1.850.90.1.1.2.2.1.4 | DisplayString | RW | 10.1.0.10 | |||||||||||||||||
column · DisplayString · read-write · current The IP address of the SNMP contact. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlPASnmpContactPort | 1.3.6.1.4.1.850.90.1.1.2.2.1.5 | PositiveInteger | RW | 162 | |||||||||||||||||
column · PositiveInteger · read-write · current The port of the SNMP contact. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlPASnmpContactSnmpVersion | 1.3.6.1.4.1.850.90.1.1.2.2.1.6 | INTEGER | RW | snmpv1(1) | |||||||||||||||||
column · INTEGER · read-write · current The SNMP contact version to use for sending traps.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlPASnmpContactSecurityName | 1.3.6.1.4.1.850.90.1.1.2.2.1.7 | DisplayString | RW | public | |||||||||||||||||
column · DisplayString · read-write · current The SNMP contact security name. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlPASnmpContactPrivPassword | 1.3.6.1.4.1.850.90.1.1.2.2.1.8 | DisplayString | RW | | |||||||||||||||||
column · DisplayString · read-write · current The SNMP contact priv password to use for sending V3 traps. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlPASnmpContactAuthPassword | 1.3.6.1.4.1.850.90.1.1.2.2.1.9 | DisplayString | RW | | |||||||||||||||||
column · DisplayString · read-write · current The SNMP contact auth password to use for sending V3 traps. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NtlUPS | 1.3.6.1.4.1.850.100 | ||||||||||||||||||||
| NtlUpsObjects | 1.3.6.1.4.1.850.100.1 | ||||||||||||||||||||
| NtlUpsIdent | 1.3.6.1.4.1.850.100.1.1 | ||||||||||||||||||||
| StlUpsIdentUpsSoftwareChecksum | 1.3.6.1.4.1.850.100.1.1.1 | Integer32 | RO | 0 | |||||||||||||||||
scalar · Integer32 · read-only · current A checksum for the UPS software. Example values from LibreNMS test devices
| |||||||||||||||||||||
| StlUpsIdentSerialNum | 1.3.6.1.4.1.850.100.1.1.2 | DisplayString | RO | upsserialnum | |||||||||||||||||
scalar · DisplayString · read-only · current Serial number for the UPS. Example values from LibreNMS test devices
| |||||||||||||||||||||
| StlUpsIdentID | 1.3.6.1.4.1.850.100.1.1.3 | Integer32 (0..65535) | RW | 65535 | |||||||||||||||||
scalar · Integer32 (0..65535) · read-write · current A user-supplied ID for the UPS. Example values from LibreNMS test devices
| |||||||||||||||||||||
| StlUpsSnmpCardSerialNum | 1.3.6.1.4.1.850.100.1.1.4 | DisplayString | RO | snmpcardserialnum | |||||||||||||||||
scalar · DisplayString · read-only · current Serial number for the UPS. Example values from LibreNMS test devices
| |||||||||||||||||||||
| StlUpsSelectedDeviceID | 1.3.6.1.4.1.850.100.1.1.5 | Integer32 (0..65535) | RW | 1 | |||||||||||||||||
scalar · Integer32 (0..65535) · read-write · current The device ID selected to be used for retrieving data for this mib. As the snmp web card has only one device, this is read only for it Example values from LibreNMS test devices
| |||||||||||||||||||||
| StlUpsLocation | 1.3.6.1.4.1.850.100.1.1.6 | DisplayString | RW | location1 | |||||||||||||||||
scalar · DisplayString · read-write · current The device location string. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NtlUpsBattery | 1.3.6.1.4.1.850.100.1.2 | ||||||||||||||||||||
| StlUpsBatteryAge | 1.3.6.1.4.1.850.100.1.2.1 | DisplayString | RO | 4.6 | |||||||||||||||||
scalar · DisplayString · read-only · current The age of the battery in years. This is equal to the current date minus tlConfigBattReplDate. Example values from LibreNMS test devices
| |||||||||||||||||||||
| StlUpsTemperatureF | 1.3.6.1.4.1.850.100.1.2.2 | Integer32 | RO | 752 | |||||||||||||||||
scalar · Integer32 · read-only · current The temperature of the battery, in Farenheight degrees. This is calculated from upsBatteryTemperature, which is in Celsius degrees. Example values from LibreNMS test devices
| |||||||||||||||||||||
| StlUpsExternalBatteryAge | 1.3.6.1.4.1.850.100.1.2.3 | DisplayString | RO | ||||||||||||||||||
scalar · DisplayString · read-only · current The age of external battery in years. This is equal to the current date minus tlConfigExternalBattReplDate. | |||||||||||||||||||||
| NtlUpsInput | 1.3.6.1.4.1.850.100.1.3 | ||||||||||||||||||||
| StlUpsInputNumVoltages | 1.3.6.1.4.1.850.100.1.3.1 | NonNegativeInteger | RO | 1 | |||||||||||||||||
scalar · NonNegativeInteger · read-only · current The number of input voltages. Phase to phase or phase to neutral. This variable indicates the number of rows in the input table. Example values from LibreNMS test devices
| |||||||||||||||||||||
| TtlUpsInputVoltageTable | 1.3.6.1.4.1.850.100.1.3.2 | NA | |||||||||||||||||||
table · not-accessible · current A list of voltage input table entries. The number of entries is given by the value of tlUpsInputNumVoltages. | |||||||||||||||||||||
| RtlUpsInputVoltageEntry | 1.3.6.1.4.1.850.100.1.3.2.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing information applicable to a particular input voltage. | |||||||||||||||||||||
| CtlUpsInputVoltageIndex | 1.3.6.1.4.1.850.100.1.3.2.1.1 | PositiveInteger | NA | 1 | |||||||||||||||||
column · PositiveInteger · not-accessible · current The input voltage identifier. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlUpsInputVoltageType | 1.3.6.1.4.1.850.100.1.3.2.1.2 | INTEGER | RO | phaseToNeutral(0) | |||||||||||||||||
column · INTEGER · read-only · current Whether voltage measured is phase to phase or phase to neutral.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlUpsInputVoltage | 1.3.6.1.4.1.850.100.1.3.2.1.3 | NonNegativeInteger | RO | 122 | |||||||||||||||||
column · NonNegativeInteger · read-only · current The magnitude of the present input voltage. A value of 6553 indicates Unknown.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| StlUpsInputSourceSelect | 1.3.6.1.4.1.850.100.1.3.3 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current The determination as to which of two AC input lines is designated as the primary input source. The other is designated as the secondary input source. This value will always return inputSourceA(0) for devices with a single input source. Setting this value is supported only on selected models.
| |||||||||||||||||||||
| StlUpsPhaseImbalance | 1.3.6.1.4.1.850.100.1.3.4 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current Percentage of imbalance of the 3 phases.
| |||||||||||||||||||||
| StlUpsInputSourceAvailability | 1.3.6.1.4.1.850.100.1.3.5 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The determination as to which of two AC input lines are available. The agent will return either inputSourceA(1) or inputSourceB(2) if only one line is available, or inputSourceAB(3) if both lines are available. The agent will never return none(0) since the device will be powered off if neither line is available.
| |||||||||||||||||||||
| StlUpsInputSourceInUse | 1.3.6.1.4.1.850.100.1.3.6 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The determination as to which one of two AC input lines is in use.
| |||||||||||||||||||||
| StlUpsInputSourceTransitionCount | 1.3.6.1.4.1.850.100.1.3.7 | PositiveInteger | RO | ||||||||||||||||||
scalar · PositiveInteger · read-only · current The number of times the device transitions between primary and secondary sources. Most devices are limied to 65533 transitions, after which the value will not increment. | |||||||||||||||||||||
| NtlUpsOutput | 1.3.6.1.4.1.850.100.1.4 | ||||||||||||||||||||
| StlUpsOutputPowerTotal | 1.3.6.1.4.1.850.100.1.4.5 | PositiveInteger | RO | ||||||||||||||||||
scalar · PositiveInteger · read-only · current The power capacity of the device. | |||||||||||||||||||||
| StlUpsOutputCircuits | 1.3.6.1.4.1.850.100.1.4.6 | NonNegativeInteger | RO | 1 | |||||||||||||||||
scalar · NonNegativeInteger · read-only · current The number of output circuits. This variable indicates the number of rows in the output circuit table. Example values from LibreNMS test devices
| |||||||||||||||||||||
| TtlUpsOutputCircuitTable | 1.3.6.1.4.1.850.100.1.4.7 | NA | |||||||||||||||||||
table · not-accessible · current A list of output currents table entries. The number of entries is given by the value of tlUpsOutputNumCircuits. | |||||||||||||||||||||
| RtlUpsOutputCircuitEntry | 1.3.6.1.4.1.850.100.1.4.7.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing information applicable to a particular output circuit. | |||||||||||||||||||||
| CtlUpsOutputCircuitIndex | 1.3.6.1.4.1.850.100.1.4.7.1.1 | PositiveInteger | NA | ||||||||||||||||||
column · PositiveInteger · not-accessible · current The output circuit identifier. | |||||||||||||||||||||
| CtlUpsOutputCircuitStatus | 1.3.6.1.4.1.850.100.1.4.7.1.2 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current Whether the breaker is open or closed.
| |||||||||||||||||||||
| CtlUpsOutputCircuitLoadCurrent | 1.3.6.1.4.1.850.100.1.4.7.1.3 | NonNegativeInteger | RO | ||||||||||||||||||
column · NonNegativeInteger · read-only · current The magnitude of the present output current in tenths of an amp. A value of 65534 indicates Unknown.
| |||||||||||||||||||||
| CtlUpsOutputCircuitVoltage | 1.3.6.1.4.1.850.100.1.4.7.1.4 | NonNegativeInteger | RO | ||||||||||||||||||
column · NonNegativeInteger · read-only · current The magnitude of the present circuit voltage in tenths of an volt.
| |||||||||||||||||||||
| CtlUpsOutputCircuitPower | 1.3.6.1.4.1.850.100.1.4.7.1.5 | NonNegativeInteger | RO | ||||||||||||||||||
column · NonNegativeInteger · read-only · current The magnitude of the present power in watts. tenths of an amp.
| |||||||||||||||||||||
| CtlUpsOutputCircuitPowerFactor | 1.3.6.1.4.1.850.100.1.4.7.1.6 | NonNegativeInteger | RO | ||||||||||||||||||
column · NonNegativeInteger · read-only · current The power factor of all receptacles in a given circuit as a %.
| |||||||||||||||||||||
| StlUpsAggregatePowerFactor | 1.3.6.1.4.1.850.100.1.4.8 | PositiveInteger | RO | ||||||||||||||||||
scalar · PositiveInteger · read-only · current The aggregrate power factor of all phases.
| |||||||||||||||||||||
| NtlUpsAlarm | 1.3.6.1.4.1.850.100.1.6 | ||||||||||||||||||||
| StlUpsAlarmsPresent | 1.3.6.1.4.1.850.100.1.6.1 | Gauge32 | RO | 2 | |||||||||||||||||
scalar · Gauge32 · read-only · current The present number of active alarm conditions. Example values from LibreNMS test devices
| |||||||||||||||||||||
| TtlUpsAlarmTable | 1.3.6.1.4.1.850.100.1.6.2 | NA | |||||||||||||||||||
table · not-accessible · current A list of alarm table entries. | |||||||||||||||||||||
| RtlUpsAlarmEntry | 1.3.6.1.4.1.850.100.1.6.2.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing information applicable to a particular alarm.
| |||||||||||||||||||||
| CtlUpsAlarmId | 1.3.6.1.4.1.850.100.1.6.2.1.1 | PositiveInteger | RO | 5679 | |||||||||||||||||
column · PositiveInteger · read-only · current A unique identifier for an alarm condition. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlUpsAlarmDescr | 1.3.6.1.4.1.850.100.1.6.2.1.2 | AutonomousType | RO | 1.3.6.1.4.1.850.100.1.6.3.8 | |||||||||||||||||
column · AutonomousType · read-only · current A description of the alarm condition. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlUpsAlarmTime | 1.3.6.1.4.1.850.100.1.6.2.1.3 | TimeStamp | RO | 27800 | |||||||||||||||||
column · TimeStamp · read-only · current The value of sysUpTime when the alarm condition was detected. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlUpsAlarmDetail | 1.3.6.1.4.1.850.100.1.6.2.1.4 | DisplayString | RO | Battery Bad | |||||||||||||||||
column · DisplayString · read-only · current A textual description of the alarm condition. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlUpsAlarmDeviceId | 1.3.6.1.4.1.850.100.1.6.2.1.5 | PositiveInteger | RO | 1 | |||||||||||||||||
column · PositiveInteger · read-only · current A numeric identifier for the device on which the alarm is active. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlUpsAlarmDeviceName | 1.3.6.1.4.1.850.100.1.6.2.1.6 | DisplayString | RO | Device 1 | |||||||||||||||||
column · DisplayString · read-only · current A string identifier for the device on which the alarm is active. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlUpsAlarmLocation | 1.3.6.1.4.1.850.100.1.6.2.1.7 | DisplayString | RO | | |||||||||||||||||
column · DisplayString · read-only · current The location of the device on which the alarm is active. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlUpsAlarmGroup | 1.3.6.1.4.1.850.100.1.6.2.1.8 | INTEGER | RO | critical(1) | |||||||||||||||||
column · INTEGER · read-only · current The category/group of this alarm.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlUpsAlarmIp | 1.3.6.1.4.1.850.100.1.6.2.1.9 | IpAddress | RO | 10.0.0.10 | |||||||||||||||||
column · IpAddress · read-only · current The originating IP address associated with this alarm. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlUpsAlarmMac | 1.3.6.1.4.1.850.100.1.6.2.1.10 | DisplayString | RO | 30:30:3a:34:30:3a:39:44:3a:34:33:3a:33:35:3a:39… | |||||||||||||||||
column · DisplayString · read-only · current The originating mac address associated with this alarm. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NtlUpsWellKnownAlarms | 1.3.6.1.4.1.850.100.1.6.3 | ||||||||||||||||||||
| NtlUpsAlarmPrimaryPowerOutage | 1.3.6.1.4.1.850.100.1.6.3.1 | ||||||||||||||||||||
node · current The primary power source is not present. | |||||||||||||||||||||
| NtlUpsAlarmSecondaryPowerOutage | 1.3.6.1.4.1.850.100.1.6.3.2 | ||||||||||||||||||||
node · current The secondary power source is not present. | |||||||||||||||||||||
| NtlUpsAlarmLoadLevelAboveThreshold | 1.3.6.1.4.1.850.100.1.6.3.3 | ||||||||||||||||||||
node · current The load level is above the designated threshold. | |||||||||||||||||||||
| NtlUpsAlarmOutputCurrentChanged | 1.3.6.1.4.1.850.100.1.6.3.4 | ||||||||||||||||||||
node · current The output current changed from its last known value. | |||||||||||||||||||||
| NtlUpsAlarmBatteryAgeAboveThreshold | 1.3.6.1.4.1.850.100.1.6.3.5 | ||||||||||||||||||||
node · current One or more batteries have been determined to require replacement. | |||||||||||||||||||||
| NtlUpsAlarmLoadOff | 1.3.6.1.4.1.850.100.1.6.3.6 | ||||||||||||||||||||
node · current The load is off. | |||||||||||||||||||||
| NtlUpsAlarmUserDefined | 1.3.6.1.4.1.850.100.1.6.3.7 | ||||||||||||||||||||
node · current A user-defined event is in alarm. | |||||||||||||||||||||
| NtlUpsAlarmBatteryBad | 1.3.6.1.4.1.850.100.1.6.3.8 | ||||||||||||||||||||
node · current One or more batteries have been determined to require replacement. | |||||||||||||||||||||
| NtlUpsAlarmOnBattery | 1.3.6.1.4.1.850.100.1.6.3.9 | ||||||||||||||||||||
node · current The UPS is drawing power from the batteries. | |||||||||||||||||||||
| NtlUpsAlarmLowBattery | 1.3.6.1.4.1.850.100.1.6.3.10 | ||||||||||||||||||||
node · current The remaining battery run-time is less than or equal to upsConfigLowBattTime. | |||||||||||||||||||||
| NtlUpsAlarmDepletedBattery | 1.3.6.1.4.1.850.100.1.6.3.11 | ||||||||||||||||||||
node · current The UPS will be unable to sustain the present load when and if the utility power is lost. | |||||||||||||||||||||
| NtlUpsAlarmTempBad | 1.3.6.1.4.1.850.100.1.6.3.12 | ||||||||||||||||||||
node · current A temperature is out of tolerance. | |||||||||||||||||||||
| NtlUpsAlarmInputBad | 1.3.6.1.4.1.850.100.1.6.3.13 | ||||||||||||||||||||
node · current An input condition is out of tolerance. | |||||||||||||||||||||
| NtlUpsAlarmOutputBad | 1.3.6.1.4.1.850.100.1.6.3.14 | ||||||||||||||||||||
node · current An output condition (other than OutputOverload) is out of tolerance. | |||||||||||||||||||||
| NtlUpsAlarmOutputOverload | 1.3.6.1.4.1.850.100.1.6.3.15 | ||||||||||||||||||||
node · current The output load exceeds the UPS output capacity. | |||||||||||||||||||||
| NtlUpsAlarmOnBypass | 1.3.6.1.4.1.850.100.1.6.3.16 | ||||||||||||||||||||
node · current The Bypass is presently engaged on the UPS. | |||||||||||||||||||||
| NtlUpsAlarmBypassBad | 1.3.6.1.4.1.850.100.1.6.3.17 | ||||||||||||||||||||
node · current The Bypass is out of tolerance. | |||||||||||||||||||||
| NtlUpsAlarmOutputOffAsRequested | 1.3.6.1.4.1.850.100.1.6.3.18 | ||||||||||||||||||||
node · current The UPS has shutdown as requested, i.e., the output is off. | |||||||||||||||||||||
| NtlUpsAlarmUpsOffAsRequested | 1.3.6.1.4.1.850.100.1.6.3.19 | ||||||||||||||||||||
node · current The entire UPS has shutdown as commanded. | |||||||||||||||||||||
| NtlUpsAlarmChargerFailed | 1.3.6.1.4.1.850.100.1.6.3.20 | ||||||||||||||||||||
node · current An uncorrected problem has been detected within the UPS charger subsystem. | |||||||||||||||||||||
| NtlUpsAlarmUpsOutputOff | 1.3.6.1.4.1.850.100.1.6.3.21 | ||||||||||||||||||||
node · current The output of the UPS is in the off state. | |||||||||||||||||||||
| NtlUpsAlarmUpsSystemOff | 1.3.6.1.4.1.850.100.1.6.3.22 | ||||||||||||||||||||
node · current The UPS system is in the off state. | |||||||||||||||||||||
| NtlUpsAlarmFanFailure | 1.3.6.1.4.1.850.100.1.6.3.23 | ||||||||||||||||||||
node · current The failure of one or more fans in the UPS has been detected. | |||||||||||||||||||||
| NtlUpsAlarmFuseFailure | 1.3.6.1.4.1.850.100.1.6.3.24 | ||||||||||||||||||||
node · current The failure of one or more fuses has been detected. | |||||||||||||||||||||
| NtlUpsAlarmGeneralFault | 1.3.6.1.4.1.850.100.1.6.3.25 | ||||||||||||||||||||
node · current A general fault in the UPS has been detected. | |||||||||||||||||||||
| NtlUpsAlarmDiagnosticTestFailed | 1.3.6.1.4.1.850.100.1.6.3.26 | ||||||||||||||||||||
node · current The result of the last diagnostic test indicates a failure. | |||||||||||||||||||||
| NtlUpsAlarmCommunicationsLost | 1.3.6.1.4.1.850.100.1.6.3.27 | ||||||||||||||||||||
node · current A problem has been encountered in the communications between the agent and the UPS. | |||||||||||||||||||||
| NtlUpsAlarmAwaitingPower | 1.3.6.1.4.1.850.100.1.6.3.28 | ||||||||||||||||||||
node · current The UPS output is off and the UPS is awaiting the return of input power. | |||||||||||||||||||||
| NtlUpsAlarmShutdownPending | 1.3.6.1.4.1.850.100.1.6.3.29 | ||||||||||||||||||||
node · current A upsShutdownAfterDelay countdown is underway. | |||||||||||||||||||||
| NtlUpsAlarmShutdownImminent | 1.3.6.1.4.1.850.100.1.6.3.30 | ||||||||||||||||||||
node · current The UPS will turn off power to the load in less than 5 seconds; this may be either a timed shutdown or a low battery shutdown. | |||||||||||||||||||||
| NtlUpsAlarmTestInProgress | 1.3.6.1.4.1.850.100.1.6.3.31 | ||||||||||||||||||||
node · current A test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of the testing in the alarm table, if desired, via a OBJECT-IDENTITY macro in the MIB document specific to that implementation and are outside the scope of this OBJECT-IDENTITY. | |||||||||||||||||||||
| NtlUpsAlarmCircuitBreaker1Open | 1.3.6.1.4.1.850.100.1.6.3.32 | ||||||||||||||||||||
node · current Circuit breakers #1 is open. | |||||||||||||||||||||
| NtlUpsAlarmCircuitBreaker2Open | 1.3.6.1.4.1.850.100.1.6.3.33 | ||||||||||||||||||||
node · current Circuit breakers #2 is open. | |||||||||||||||||||||
| NtlUpsAlarmCircuitBreaker3Open | 1.3.6.1.4.1.850.100.1.6.3.34 | ||||||||||||||||||||
node · current Circuit breakers #3 is open. | |||||||||||||||||||||
| NtlUpsAlarmCircuitBreaker4Open | 1.3.6.1.4.1.850.100.1.6.3.35 | ||||||||||||||||||||
node · current Circuit breakers #4 is open. | |||||||||||||||||||||
| NtlUpsAlarmCircuitBreaker5Open | 1.3.6.1.4.1.850.100.1.6.3.36 | ||||||||||||||||||||
node · current Circuit breakers #5 is open. | |||||||||||||||||||||
| NtlUpsAlarmCircuitBreaker6Open | 1.3.6.1.4.1.850.100.1.6.3.37 | ||||||||||||||||||||
node · current Circuit breakers #6 is open. | |||||||||||||||||||||
| NtlUpsAlarmCircuitBreaker7Open | 1.3.6.1.4.1.850.100.1.6.3.38 | ||||||||||||||||||||
node · current Circuit breakers #7 is open. | |||||||||||||||||||||
| NtlUpsAlarmCircuitBreaker8Open | 1.3.6.1.4.1.850.100.1.6.3.39 | ||||||||||||||||||||
node · current Circuit breakers #8 is open. | |||||||||||||||||||||
| NtlUpsAlarmCurrent1AboveThreshold | 1.3.6.1.4.1.850.100.1.6.3.40 | ||||||||||||||||||||
node · current The output current on line 1 exceeds load limits. | |||||||||||||||||||||
| NtlUpsAlarmCurrent2AboveThreshold | 1.3.6.1.4.1.850.100.1.6.3.41 | ||||||||||||||||||||
node · current The output current on line 2 exceeds load limits. | |||||||||||||||||||||
| NtlUpsAlarmCurrent3AboveThreshold | 1.3.6.1.4.1.850.100.1.6.3.42 | ||||||||||||||||||||
node · current The output current on line 3 exceeds load limits. | |||||||||||||||||||||
| NtlUpsAlarmRuntimeBelowWarningLevel | 1.3.6.1.4.1.850.100.1.6.3.43 | ||||||||||||||||||||
node · current The battery seconds remaining is below warning level. | |||||||||||||||||||||
| NtlUpsAlarmBusStartVoltageLow | 1.3.6.1.4.1.850.100.1.6.3.44 | ||||||||||||||||||||
node · current The inverter start up bus voltage is too low. | |||||||||||||||||||||
| NtlUpsAlarmBusOverVoltage | 1.3.6.1.4.1.850.100.1.6.3.45 | ||||||||||||||||||||
node · current The inverter bus voltage is too high. | |||||||||||||||||||||
| NtlUpsAlarmBusUnderVoltage | 1.3.6.1.4.1.850.100.1.6.3.46 | ||||||||||||||||||||
node · current The inverter bus voltage is too low. | |||||||||||||||||||||
| NtlUpsAlarmBusVoltageUnbalanced | 1.3.6.1.4.1.850.100.1.6.3.47 | ||||||||||||||||||||
node · current The inverter bus voltage is not balanced. | |||||||||||||||||||||
| NtlUpsAlarmInverterSoftStartBad | 1.3.6.1.4.1.850.100.1.6.3.48 | ||||||||||||||||||||
node · current The inverter bus voltage cannot reach desired voltage within a specified duration. | |||||||||||||||||||||
| NtlUpsAlarmInverterOverVoltage | 1.3.6.1.4.1.850.100.1.6.3.49 | ||||||||||||||||||||
node · current The inverter voltage is too high. | |||||||||||||||||||||
| NtlUpsAlarmInverterUnderVoltage | 1.3.6.1.4.1.850.100.1.6.3.50 | ||||||||||||||||||||
node · current The inverter voltage is too low. | |||||||||||||||||||||
| NtlUpsAlarmInverterCircuitBad | 1.3.6.1.4.1.850.100.1.6.3.51 | ||||||||||||||||||||
node · current The inverter output is shorted. | |||||||||||||||||||||
| NtlUpsAlarmBatteryOverVoltage | 1.3.6.1.4.1.850.100.1.6.3.52 | ||||||||||||||||||||
node · current The battery voltage is too high. | |||||||||||||||||||||
| NtlUpsAlarmBatteryUnderVoltage | 1.3.6.1.4.1.850.100.1.6.3.53 | ||||||||||||||||||||
node · current The battery voltage is too low. | |||||||||||||||||||||
| NtlUpsAlarmSiteWiringFault | 1.3.6.1.4.1.850.100.1.6.3.54 | ||||||||||||||||||||
node · current The utility input wiring is faulty. | |||||||||||||||||||||
| NtlUpsAlarmOverTemperatureProtection | 1.3.6.1.4.1.850.100.1.6.3.55 | ||||||||||||||||||||
node · current The over temperature protection is activated. | |||||||||||||||||||||
| NtlUpsAlarmOverCharged | 1.3.6.1.4.1.850.100.1.6.3.56 | ||||||||||||||||||||
node · current The UPS is over charged. | |||||||||||||||||||||
| NtlUpsAlarmEPOActive | 1.3.6.1.4.1.850.100.1.6.3.57 | ||||||||||||||||||||
node · current The EPO is currently activate. | |||||||||||||||||||||
| NtlUpsAlarmBypassFrequencyBad | 1.3.6.1.4.1.850.100.1.6.3.58 | ||||||||||||||||||||
node · current The bypass frequency is out of tolerance. | |||||||||||||||||||||
| NtlUpsAlarmExternalSmartBatteryAgeAboveThreshold | 1.3.6.1.4.1.850.100.1.6.3.59 | ||||||||||||||||||||
node · current One or more external smart batteries have been determined to require replacement. | |||||||||||||||||||||
| NtlUpsAlarmExternalNonSmartBatteryAgeAboveThreshold | 1.3.6.1.4.1.850.100.1.6.3.60 | ||||||||||||||||||||
node · current One or more external non-smart batteries have been determined to require replacement. | |||||||||||||||||||||
| NtlUpsAlarmSmartBatteryCommLost | 1.3.6.1.4.1.850.100.1.6.3.61 | ||||||||||||||||||||
node · current Communications with the smart batteries was lost. | |||||||||||||||||||||
| NtlUpsAlarmSourceAOutage | 1.3.6.1.4.1.850.100.1.6.3.62 | ||||||||||||||||||||
node · current Input power source A is not present. | |||||||||||||||||||||
| NtlUpsAlarmSourceBOutage | 1.3.6.1.4.1.850.100.1.6.3.63 | ||||||||||||||||||||
node · current Input power source B is not present. | |||||||||||||||||||||
| NtlUpsAlarmWatchdogReset | 1.3.6.1.4.1.850.100.1.6.3.64 | ||||||||||||||||||||
node · current The internal watchdog triggered a reset of the device. | |||||||||||||||||||||
| StlUpsAlarmDevName | 1.3.6.1.4.1.850.100.1.6.7 | DisplayString | RO | deprecated | |||||||||||||||||
scalar · DisplayString · read-only · deprecated The name of the device, tlDevName, corresponding to the device that is associated with this alarm. | |||||||||||||||||||||
| StlUpsAlarmDevLocation | 1.3.6.1.4.1.850.100.1.6.8 | DisplayString | RO | deprecated | |||||||||||||||||
scalar · DisplayString · read-only · deprecated The location of the device, tlDevLocation, corresponding to the device that is associated with this alarm. | |||||||||||||||||||||
| StlUpsAlarmCategory | 1.3.6.1.4.1.850.100.1.6.9 | Integer32 | RO | deprecated | |||||||||||||||||
scalar · Integer32 · read-only · deprecated The category, tlDevEvtCategory, of this alarm. | |||||||||||||||||||||
| NtlUpsTest | 1.3.6.1.4.1.850.100.1.7 | ||||||||||||||||||||
| StlUpsTestDate | 1.3.6.1.4.1.850.100.1.7.1 | DisplayString | RO | 2020-05-26 | |||||||||||||||||
scalar · DisplayString · read-only · current The date of the last self-test run on the ups, in the format YYYYMMDD. Example values from LibreNMS test devices
| |||||||||||||||||||||
| StlUpsTestResultsDetail | 1.3.6.1.4.1.850.100.1.7.2 | DisplayString | RO | Done and Error | |||||||||||||||||
scalar · DisplayString · read-only · current Result of the last self-test run on the ups. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NtlUpsControl | 1.3.6.1.4.1.850.100.1.8 | ||||||||||||||||||||
| StlUpsWatchdogSupported | 1.3.6.1.4.1.850.100.1.8.1 | TruthValue | RO | 0 | |||||||||||||||||
scalar · TruthValue · read-only · current Indicates whether or not this UPS supports a watchdog reboot. Example values from LibreNMS test devices
| |||||||||||||||||||||
| StlUpsWatchdogSecsBeforeReboot | 1.3.6.1.4.1.850.100.1.8.2 | NonNegativeInteger | RW | 0 | |||||||||||||||||
scalar · NonNegativeInteger · read-write · current The maximum number of seconds that can expire between polls that the engine makes to the UPS for data. If this time runs out, then the UPS will cycle its outputs. Set this to zero to turns disable this feature. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NtlUpsWellKnownControls | 1.3.6.1.4.1.850.100.1.8.3 | ||||||||||||||||||||
| StlUpsControlSelfTest | 1.3.6.1.4.1.850.100.1.8.3.1 | TruthValue | RW | 1 | |||||||||||||||||
scalar · TruthValue · read-write · current Set to TRUE to initiate Self Test Example values from LibreNMS test devices
| |||||||||||||||||||||
| StlUpsControlRamp | 1.3.6.1.4.1.850.100.1.8.3.2 | TruthValue | RW | 1 | |||||||||||||||||
scalar · TruthValue · read-write · current Set to TRUE to initiate Ramp Example values from LibreNMS test devices
| |||||||||||||||||||||
| StlUpsControlShed | 1.3.6.1.4.1.850.100.1.8.3.3 | TruthValue | RW | 1 | |||||||||||||||||
scalar · TruthValue · read-write · current Set to TRUE to initiate Shed Example values from LibreNMS test devices
| |||||||||||||||||||||
| StlUpsControlUpsOn | 1.3.6.1.4.1.850.100.1.8.3.4 | TruthValue | RW | 1 | |||||||||||||||||
scalar · TruthValue · read-write · current Set to TRUE to turn UPS on Example values from LibreNMS test devices
| |||||||||||||||||||||
| StlUpsControlUpsOff | 1.3.6.1.4.1.850.100.1.8.3.5 | TruthValue | RW | 2 | |||||||||||||||||
scalar · TruthValue · read-write · current Set to TRUE to turn UPS off Example values from LibreNMS test devices
| |||||||||||||||||||||
| NtlUpsConfig | 1.3.6.1.4.1.850.100.1.9 | ||||||||||||||||||||
| StlUpsConfigBattReplDate | 1.3.6.1.4.1.850.100.1.9.1 | DisplayString | RW | ||||||||||||||||||
scalar · DisplayString · read-write · current The date on which the battery was last replaced, in the format YYYYMMDD. | |||||||||||||||||||||
| StlUpsConfigDisplayUnits | 1.3.6.1.4.1.850.100.1.9.4 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current Selects English or Metric display for all readings. This selection may not be available on all devices. Further, some devices may support this selection, but not via a software selector. In this latter case, selections must be performed on the device itself.
| |||||||||||||||||||||
| StlUpsConfigExternalBattReplDate | 1.3.6.1.4.1.850.100.1.9.5 | DisplayString | RW | ||||||||||||||||||
scalar · DisplayString · read-write · current The date on which the external battery was last replaced, in the format YYYYMMDD. | |||||||||||||||||||||
| NtlUpsOutlet | 1.3.6.1.4.1.850.100.1.10 | ||||||||||||||||||||
| StlUpsOutletNumOutlets | 1.3.6.1.4.1.850.100.1.10.1 | NonNegativeInteger | RO | 3 | |||||||||||||||||
scalar · NonNegativeInteger · read-only · current The number of available Outlets in this device. Example values from LibreNMS test devices
| |||||||||||||||||||||
| TtlUpsOutletTable | 1.3.6.1.4.1.850.100.1.10.2 | NA | |||||||||||||||||||
table · not-accessible · current A list of all device Outlets for all devices. | |||||||||||||||||||||
| RtlUpsOutletEntry | 1.3.6.1.4.1.850.100.1.10.2.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing Outlet information applicable to a particular device managed by this agent.
| |||||||||||||||||||||
| CtlUpsOutletIndex | 1.3.6.1.4.1.850.100.1.10.2.1.1 | PositiveInteger | RO | 1 | |||||||||||||||||
column · PositiveInteger · read-only · current This is the index number of this Outlet for the device indicated by tlDeviceIndex. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlUpsOutletState | 1.3.6.1.4.1.850.100.1.10.2.1.2 | INTEGER | RO | on(2) | |||||||||||||||||
column · INTEGER · read-only · current The current state of the Outlet.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlUpsOutletType | 1.3.6.1.4.1.850.100.1.10.2.1.3 | Integer32 | RO | 2 | |||||||||||||||||
column · Integer32 · read-only · current This is a bit field that indicates the type of this Outlet. When 0, the outlet is not controllable and has none of the other features indicated in the bit map. When non-zero, the features present for this outlet can be interpreted with the definition. Bit Display 0 Reserved, may be 1 or 0 1 Controllable 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlUpsOutletControl | 1.3.6.1.4.1.850.100.1.10.2.1.4 | INTEGER | RW | 0 | |||||||||||||||||
column · INTEGER · read-write · current Controls the state of the Outlet.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlUpsOutletName | 1.3.6.1.4.1.850.100.1.10.2.1.5 | DisplayString | RW | | |||||||||||||||||
column · DisplayString · read-write · current A string identifying the devices attached to the output(s) of the device. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlUpsOutletRampAction | 1.3.6.1.4.1.850.100.1.10.2.1.6 | INTEGER | RW | remainOff(0) | |||||||||||||||||
column · INTEGER · read-write · current The ramp action to take on the Outlet.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlUpsOutletRampDataType | 1.3.6.1.4.1.850.100.1.10.2.1.7 | INTEGER | RW | delayInSeconds(0) | |||||||||||||||||
column · INTEGER · read-write · current The type of data associated with ramp action.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlUpsOutletRampData | 1.3.6.1.4.1.850.100.1.10.2.1.8 | Integer32 | RW | 0 | |||||||||||||||||
column · Integer32 · read-write · current The data value associated with type of ramp data. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlUpsOutletShedAction | 1.3.6.1.4.1.850.100.1.10.2.1.9 | INTEGER | RW | remainOn(0) | |||||||||||||||||
column · INTEGER · read-write · current The shed action to take on the Outlet.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlUpsOutletShedDataType | 1.3.6.1.4.1.850.100.1.10.2.1.10 | INTEGER | RW | delayInSeconds(0) | |||||||||||||||||
column · INTEGER · read-write · current The type of data associated with shed action.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlUpsOutletShedData | 1.3.6.1.4.1.850.100.1.10.2.1.11 | Integer32 | RW | 0 | |||||||||||||||||
column · Integer32 · read-write · current The data value associated with type of shed data. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlUpsOutletGroupNdx | 1.3.6.1.4.1.850.100.1.10.2.1.12 | Integer32 | RW | 0 | |||||||||||||||||
column · Integer32 · read-write · current tlUpsOutletGroupIndex of corresponding outlet group, or 0 if ungrouped. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlUpsOutletCurrent | 1.3.6.1.4.1.850.100.1.10.2.1.13 | PositiveInteger | RO | ||||||||||||||||||
column · PositiveInteger · read-only · current The value of this outlet's current, represented as 0.1A.
| |||||||||||||||||||||
| CtlUpsOutletPower | 1.3.6.1.4.1.850.100.1.10.2.1.14 | PositiveInteger | RO | ||||||||||||||||||
column · PositiveInteger · read-only · current The value of this outlet's power in watts. | |||||||||||||||||||||
| NtlUpsOutletGroup | 1.3.6.1.4.1.850.100.1.11 | ||||||||||||||||||||
| StlUpsOutletNumOutletGroups | 1.3.6.1.4.1.850.100.1.11.1 | NonNegativeInteger | RO | 0 | |||||||||||||||||
scalar · NonNegativeInteger · read-only · current The number of available Outlet Groups in this device. Example values from LibreNMS test devices
| |||||||||||||||||||||
| TtlUpsOutletGroupTable | 1.3.6.1.4.1.850.100.1.11.2 | NA | |||||||||||||||||||
table · not-accessible · current A list of device outlet group entries. The number of entries is given by the value of tlUpsOutletNumOutletGroups. | |||||||||||||||||||||
| RtlUpsOutletGroupEntry | 1.3.6.1.4.1.850.100.1.11.2.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing outlet group information applicable to a particular device managed by this agent | |||||||||||||||||||||
| CtlUpsOutletGroupIndex | 1.3.6.1.4.1.850.100.1.11.2.1.1 | PositiveInteger | RO | ||||||||||||||||||
column · PositiveInteger · read-only · current This is the index number of this load group for the device. | |||||||||||||||||||||
| CtlUpsOutletGroupRowStatus | 1.3.6.1.4.1.850.100.1.11.2.1.2 | RowStatus | RW | ||||||||||||||||||
column · RowStatus · read-write · current Row status for the tlUpsOutletGroupTable | |||||||||||||||||||||
| CtlUpsOutletGroupName | 1.3.6.1.4.1.850.100.1.11.2.1.3 | DisplayString | RW | ||||||||||||||||||
column · DisplayString · read-write · current The name of this outlet group. | |||||||||||||||||||||
| CtlUpsOutletGroupDesc | 1.3.6.1.4.1.850.100.1.11.2.1.4 | DisplayString | RW | ||||||||||||||||||
column · DisplayString · read-write · current A description for this outlet group. | |||||||||||||||||||||
| CtlUpsOutletGroupState | 1.3.6.1.4.1.850.100.1.11.2.1.5 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current The current state of the outlet group.
| |||||||||||||||||||||
| CtlUpsOutletGroupControl | 1.3.6.1.4.1.850.100.1.11.2.1.6 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current Controls the state of every outlet associated with the group.
| |||||||||||||||||||||
| NtlUpsMainOutlet | 1.3.6.1.4.1.850.100.1.12 | ||||||||||||||||||||
| StlUpsMainOutletState | 1.3.6.1.4.1.850.100.1.12.1 | INTEGER | RO | on(2) | |||||||||||||||||
scalar · INTEGER · read-only · current The current state of the main output of the device.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| StlUpsMainOutletControllable | 1.3.6.1.4.1.850.100.1.12.2 | TruthValue | RO | 1 | |||||||||||||||||
scalar · TruthValue · read-only · current Indicates if this device has controllable outlets Example values from LibreNMS test devices
| |||||||||||||||||||||
| StlUpsMainOutletControl | 1.3.6.1.4.1.850.100.1.12.3 | INTEGER | RW | idle(0) | |||||||||||||||||
scalar · INTEGER · read-write · current Controls the state of the main outlet of the device.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NtlUpsEnvironment | 1.3.6.1.4.1.850.100.1.13 | ||||||||||||||||||||
| StlUpsTemperature | 1.3.6.1.4.1.850.100.1.13.1 | Integer32 | RO | ||||||||||||||||||
scalar · Integer32 · read-only · current The ambient temperature. The measurement returned will either be in units of Celsius (C) or Fahrenheit (F) depending upon whether Metric or English was selected for the reading by tlUpsConfigDisplayUnits. | |||||||||||||||||||||
| NtlUpsTraps | 1.3.6.1.4.1.850.100.2 | ||||||||||||||||||||
| !tlUpsTrapAlarmEntryAddedV1 | 1.3.6.1.4.1.850.100.2.0.3 | ||||||||||||||||||||
notification This trap is sent each time an alarm is inserted into to the alarm table. | |||||||||||||||||||||
| !tlUpsTrapAlarmEntryRemovedV1 | 1.3.6.1.4.1.850.100.2.0.4 | ||||||||||||||||||||
notification This trap is sent each time an alarm is removed from the alarm table. | |||||||||||||||||||||
| !tlUpsTrapAlarmEntryAdded | 1.3.6.1.4.1.850.100.2.3 | ||||||||||||||||||||
notification · current This trap is sent each time an alarm is inserted into to the alarm table. | |||||||||||||||||||||
| !tlUpsTrapAlarmEntryRemoved | 1.3.6.1.4.1.850.100.2.4 | ||||||||||||||||||||
notification · current This trap is sent each time an alarm is removed from the alarm table. | |||||||||||||||||||||
| !tlUpsTrapSystemStartup | 1.3.6.1.4.1.850.100.2.5 | ||||||||||||||||||||
notification · current Used to inform another entity of an engine's startup. The varbinds that follow are: OBJ1 = tlEngineType Obj1Value = The type of engine providing this data OBJ2 = tlEngineSoftwareVersion Obj2Value = The current version of the engine OBJ3 = tlEngineMACAddr Obj3Value = The MAC address of the engine OBJ4 = tlUpsSnmpCardSerialNum Obj4Value = The serial number of the SNMPWEBCARD [should be 0 on PC] --- if this trap is extended, place all static OIDs above this mark. all objects below --- the number of devices (tlNumDevices) is explicit as per device for enumeration by --- the target receiver OBJ5 = tlNumDevices Obj5Value = The number of devices attached --- The following objects will be replicated per each device: OBJ6 = The OID for an entry of tlDevManufacturer, indexed by device Obj6Value = The device's manufacturer OBJ7 = The OID for an entry of tlDevModel, indexed by device Obj7Value = The device's model name OBJ8 = The OID for an entry of tlDevName, indexed by device Obj8Value = The device's display name OBJ9 = The OID for an entry of tlDevLocation, indexed by device Obj9Value = The device's location OBJ10 = The OID for an entry of tlDevRegion, indexed by device Obj10Value= The device's region OBJ11 = The OID for an entry of tlDevProtocol, indexed by device Obj11Value= The device's protocol (display string format) | |||||||||||||||||||||
| !tlUpsTrapSystemShutdown | 1.3.6.1.4.1.850.100.2.6 | ||||||||||||||||||||
notification · current Used to inform another entity of an engine's startup. The varbinds that follow are: OBJ1 = tlEngineType Obj1Value = The type of engine providing this data OBJ2 = tlEngineSoftwareVersion Obj2Value = The current version of the engine OBJ3 = tlEngineMACAddr Obj3Value = The MAC address of the engine OBJ4 = tlUpsSnmpCardSerialNum Obj4Value = The serial number of the SNMPWEBCARD [should be 0 on PC] --- if this trap is extended, place all static OIDs above this mark. all objects below --- the number of devices (tlNumDevices) is explicit as per device for enumeration by --- the target receiver OBJ5 = tlNumDevices Obj5Value = The number of devices attached --- The following objects will be replicated per each device: OBJ6 = The OID for an entry of tlDevManufacturer, indexed by device Obj6Value = The device's manufacturer OBJ7 = The OID for an entry of tlDevModel, indexed by device Obj7Value = The device's model name OBJ8 = The OID for an entry of tlDevName, indexed by device Obj8Value = The device's display name OBJ9 = The OID for an entry of tlDevLocation, indexed by device Obj9Value = The device's location OBJ10 = The OID for an entry of tlDevRegion, indexed by device Obj10Value= The device's region OBJ11 = The OID for an entry of tlDevProtocol, indexed by device Obj11Value= The device's protocol (display string format) | |||||||||||||||||||||
| NtlEnviroSense | 1.3.6.1.4.1.850.101 | ||||||||||||||||||||
| NtlEnvEnvironment | 1.3.6.1.4.1.850.101.1 | ||||||||||||||||||||
| NtlEnvTemperatureData | 1.3.6.1.4.1.850.101.1.1 | ||||||||||||||||||||
| StlEnvTemperatureC | 1.3.6.1.4.1.850.101.1.1.1 | Integer32 | RO | 22 | |||||||||||||||||
scalar · Integer32 · read-only · current The ambient temperature (C). Example values from LibreNMS test devices
| |||||||||||||||||||||
| StlEnvTemperatureF | 1.3.6.1.4.1.850.101.1.1.2 | Integer32 | RO | 71 | |||||||||||||||||
scalar · Integer32 · read-only · current The ambient temperature (F). Example values from LibreNMS test devices
| |||||||||||||||||||||
| StlEnvTemperatureLowLimit | 1.3.6.1.4.1.850.101.1.1.3 | Integer32 | RW | 40 | |||||||||||||||||
scalar · Integer32 · read-write · current The lower alarm limit for ambient temperature (F). Example values from LibreNMS test devices
| |||||||||||||||||||||
| StlEnvTemperatureHighLimit | 1.3.6.1.4.1.850.101.1.1.4 | Integer32 | RW | 95 | |||||||||||||||||
scalar · Integer32 · read-write · current The upper alarm limit for ambient temperature (F). Example values from LibreNMS test devices
| |||||||||||||||||||||
| StlEnvTemperatureInAlarm | 1.3.6.1.4.1.850.101.1.1.5 | TruthValue | RO | 2 | |||||||||||||||||
scalar · TruthValue · read-only · current Indicates whether or not temperature is in alarm. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NtlEnvHumidityData | 1.3.6.1.4.1.850.101.1.2 | ||||||||||||||||||||
| StlEnvHumidity | 1.3.6.1.4.1.850.101.1.2.1 | Integer32 | RO | 18 | |||||||||||||||||
scalar · Integer32 · read-only · current The ambient humidity (%). Example values from LibreNMS test devices
| |||||||||||||||||||||
| StlEnvHumidityLowLimit | 1.3.6.1.4.1.850.101.1.2.2 | Integer32 | RW | 5 | |||||||||||||||||
scalar · Integer32 · read-write · current The lower alarm limit for ambient humidity (%). Example values from LibreNMS test devices
| |||||||||||||||||||||
| StlEnvHumidityHighLimit | 1.3.6.1.4.1.850.101.1.2.3 | Integer32 | RW | 80 | |||||||||||||||||
scalar · Integer32 · read-write · current The upper alarm limit for ambient humidity (%). Example values from LibreNMS test devices
| |||||||||||||||||||||
| StlEnvHumidityInAlarm | 1.3.6.1.4.1.850.101.1.2.4 | TruthValue | RO | 2 | |||||||||||||||||
scalar · TruthValue · read-only · current Indicates whether or not humidity is in alarm. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NtlEnvContacts | 1.3.6.1.4.1.850.101.2 | ||||||||||||||||||||
| TtlEnvContactTable | 1.3.6.1.4.1.850.101.2.1 | NA | |||||||||||||||||||
table · not-accessible · current A table of contacts. | |||||||||||||||||||||
| RtlEnvContactEntry | 1.3.6.1.4.1.850.101.2.1.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing information applicable to a particular contact.
| |||||||||||||||||||||
| CtlEnvContactIndex | 1.3.6.1.4.1.850.101.2.1.1.1 | PositiveInteger | RO | 1 | |||||||||||||||||
column · PositiveInteger · read-only · current The table row index for the contact. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlEnvContactName | 1.3.6.1.4.1.850.101.2.1.1.2 | DisplayString | RW | Contact Input #1 | |||||||||||||||||
column · DisplayString · read-write · current The name or description of the contact. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlEnvContactStatus | 1.3.6.1.4.1.850.101.2.1.1.3 | INTEGER | RO | normal(0) | |||||||||||||||||
column · INTEGER · read-only · current The current status of the contact.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtlEnvContactConfig | 1.3.6.1.4.1.850.101.2.1.1.4 | INTEGER | RW | normallyOpen(0) | |||||||||||||||||
column · INTEGER · read-write · current The configuration of the contact.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NtlCooling | 1.3.6.1.4.1.850.103 | ||||||||||||||||||||
| NtlCoolingEnvironment | 1.3.6.1.4.1.850.103.1 | ||||||||||||||||||||
| NtlCoolingIdent | 1.3.6.1.4.1.850.103.1.1 | ||||||||||||||||||||
| StlCoolingModel | 1.3.6.1.4.1.850.103.1.1.1 | DisplayString | RO | ||||||||||||||||||
scalar · DisplayString · read-only · current The model name for the AC Unit. | |||||||||||||||||||||
| StlCoolingManufacturer | 1.3.6.1.4.1.850.103.1.1.2 | DisplayString | RO | ||||||||||||||||||
scalar · DisplayString · read-only · current The manufacturer of the AC Unit. | |||||||||||||||||||||
| StlCoolingSerialNumber | 1.3.6.1.4.1.850.103.1.1.3 | DisplayString | RO | ||||||||||||||||||
scalar · DisplayString · read-only · current The serial number of the AC unit. | |||||||||||||||||||||
| StlCoolingFirmwareVersion | 1.3.6.1.4.1.850.103.1.1.4 | DisplayString | RO | ||||||||||||||||||
scalar · DisplayString · read-only · current The firmware version of the AC Unit. | |||||||||||||||||||||
| StlCoolingHostSoftwareVersion | 1.3.6.1.4.1.850.103.1.1.5 | DisplayString | RO | ||||||||||||||||||
scalar · DisplayString · read-only · current The hardware version of the AC unit. | |||||||||||||||||||||
| StlCoolingName | 1.3.6.1.4.1.850.103.1.1.6 | DisplayString | RW | ||||||||||||||||||
scalar · DisplayString · read-write · current The user defined name for the AC Unit. | |||||||||||||||||||||
| StlCoolingLocation | 1.3.6.1.4.1.850.103.1.1.7 | DisplayString | RW | ||||||||||||||||||
scalar · DisplayString · read-write · current The user defined location of the AC Unit. | |||||||||||||||||||||
| NtlCoolingStatus | 1.3.6.1.4.1.850.103.1.2 | ||||||||||||||||||||
| StlCoolingCondOutletTemp | 1.3.6.1.4.1.850.103.1.2.1 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The condenser outlet air stream temperature in tenths of degrees in the units Celsius/Fahrenheit as specified in tlCoolingDisplayUnits. | |||||||||||||||||||||
| StlCoolingCondInletTemp | 1.3.6.1.4.1.850.103.1.2.2 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The condenser inlet air stream temperature in tenths of degrees in the units Celsius/Fahrenheit as specified in tlCoolingDisplayUnits. | |||||||||||||||||||||
| StlCoolingRefrigerantTemp | 1.3.6.1.4.1.850.103.1.2.3 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The temperature of the refrigerant in the suction line. This is displayed in tenths of degrees in the units Celsius/Fahrenheit as specified in tlCoolingDisplayUnits. | |||||||||||||||||||||
| StlCoolingEvapSurfaceTemp | 1.3.6.1.4.1.850.103.1.2.4 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The surface temperature of the evaporator in tenths of degrees in the units Celsius/Fahrenheit as specified in tlCoolingDisplayUnits. | |||||||||||||||||||||
| StlCoolingSuctionPressure | 1.3.6.1.4.1.850.103.1.2.5 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The pressure of the compressor suction line in tenths of (Mpa/psi) depending on the value of tlCoolingDisplayUnits. | |||||||||||||||||||||
| StlCoolingDischargePressure | 1.3.6.1.4.1.850.103.1.2.6 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The pressure of the compressor discharge line in tenths of (Mpa/psi) depending on the value of tlCoolingDisplayUnits. | |||||||||||||||||||||
| StlCoolingEvapFanSpeed | 1.3.6.1.4.1.850.103.1.2.7 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The current speed of the evaporator fan.
| |||||||||||||||||||||
| StlCoolingCondFanSpeed | 1.3.6.1.4.1.850.103.1.2.8 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The current speed of the condenser fan.
| |||||||||||||||||||||
| StlCoolingCompFrequency | 1.3.6.1.4.1.850.103.1.2.9 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The operating frequency of the compressor in tenths of Arms. | |||||||||||||||||||||
| StlCoolingEEVPercentage | 1.3.6.1.4.1.850.103.1.2.10 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The opening percentage of the EEV. | |||||||||||||||||||||
| StlCoolingUnitCurrent | 1.3.6.1.4.1.850.103.1.2.11 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The the total current draw of the unit in tenths of Arms. | |||||||||||||||||||||
| StlCoolingFanCurrent | 1.3.6.1.4.1.850.103.1.2.12 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current Thethe current draw of the Evaporator and Condenser fans in tents of Arms. | |||||||||||||||||||||
| StlCoolingCompCurrent | 1.3.6.1.4.1.850.103.1.2.13 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The operating current of the compressor in Arms. | |||||||||||||||||||||
| StlCoolingReturnAirTemp | 1.3.6.1.4.1.850.103.1.2.14 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The return air temperature in tenths of degrees in the units Celsius/Fahrenheit as specified in tlCoolingDisplayUnits. | |||||||||||||||||||||
| StlCoolingSuctionTemp | 1.3.6.1.4.1.850.103.1.2.15 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The temperature of the compressor suction line in tenths of degrees in the units Celsius/Fahrenheit as specified in tlCoolingDisplayUnits. | |||||||||||||||||||||
| StlCoolingSupplyAirTemp | 1.3.6.1.4.1.850.103.1.2.16 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The supply air temperature in tenths of degrees in the units Celsius/Fahrenheit as specified in tlCoolingDisplayUnits. | |||||||||||||||||||||
| NtlCoolingRunTimes | 1.3.6.1.4.1.850.103.1.3 | ||||||||||||||||||||
| StlCoolingAirFilterRunHours | 1.3.6.1.4.1.850.103.1.3.1 | Integer32 | RO | ||||||||||||||||||
scalar · Integer32 · read-only · current Total hours the air filter has been under operation. | |||||||||||||||||||||
| StlCoolingEvapFanRunDays | 1.3.6.1.4.1.850.103.1.3.2 | Integer32 | RO | ||||||||||||||||||
scalar · Integer32 · read-only · current Total days the evaporator fan has been under operation. | |||||||||||||||||||||
| StlCoolingCondFanRunDays | 1.3.6.1.4.1.850.103.1.3.3 | Integer32 | RO | ||||||||||||||||||
scalar · Integer32 · read-only · current Total days the condenser fan has been under operation. | |||||||||||||||||||||
| StlCoolingCompressorRunDays | 1.3.6.1.4.1.850.103.1.3.4 | Integer32 | RO | ||||||||||||||||||
scalar · Integer32 · read-only · current Total days the compressor has been under operation. | |||||||||||||||||||||
| StlCoolingCondPumpRunDays | 1.3.6.1.4.1.850.103.1.3.5 | Integer32 | RO | ||||||||||||||||||
scalar · Integer32 · read-only · current Total days the condensate pump has been under operation. | |||||||||||||||||||||
| StlCoolingAtomizerRunDays | 1.3.6.1.4.1.850.103.1.3.6 | Integer32 | RO | ||||||||||||||||||
scalar · Integer32 · read-only · current Total days the atomizer has been under operation. | |||||||||||||||||||||
| NtlCoolingConfig | 1.3.6.1.4.1.850.103.1.4 | ||||||||||||||||||||
| StlCoolingOnOff | 1.3.6.1.4.1.850.103.1.4.1 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current Turn the unit off or on.
| |||||||||||||||||||||
| StlCoolingSetPointTemp | 1.3.6.1.4.1.850.103.1.4.2 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current The set point temperature the unit will control the temperature to in tenths of degrees in Celsius or Fahrenheit based upon tleCoolDisplayUnits. | |||||||||||||||||||||
| StlCoolingAutoStart | 1.3.6.1.4.1.850.103.1.4.3 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current Specified if the unit should start automatically on power up.
| |||||||||||||||||||||
| StlCoolingFanSpeedOverride | 1.3.6.1.4.1.850.103.1.4.4 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current Speed of evaporator fan set by the user.
| |||||||||||||||||||||
| StlCoolingControlType | 1.3.6.1.4.1.850.103.1.4.5 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current Which temperature to be used as a control point.
| |||||||||||||||||||||
| StlCoolingCurrentRemoteTemp | 1.3.6.1.4.1.850.103.1.4.6 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current The external remote temperature in tenths of degrees in Celsius or Fahrenheit depending upon value of tlCoolingDisplayUnits | |||||||||||||||||||||
| StlCoolingDisplayUnits | 1.3.6.1.4.1.850.103.1.4.7 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current Selects English or Metric display for all readings.
| |||||||||||||||||||||
| StlCoolingBeepOnKey | 1.3.6.1.4.1.850.103.1.4.8 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current Indicates if the display sounds a beep when a key is pressed.
| |||||||||||||||||||||
| StlCoolingOutputRelaySource | 1.3.6.1.4.1.850.103.1.4.9 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current The alarm level that causes the ouput relay to activate.
| |||||||||||||||||||||
| StlCoolingOffOnLeak | 1.3.6.1.4.1.850.103.1.4.10 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current Indicates if the unit should stop cooling when leak input is activated.
| |||||||||||||||||||||
| StlCoolingOffOnInputContact | 1.3.6.1.4.1.850.103.1.4.11 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current Indicates if the unit should stop cooling when input contact is activated.
| |||||||||||||||||||||
| StlCoolingInputContactType | 1.3.6.1.4.1.850.103.1.4.12 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current The input contact type.
| |||||||||||||||||||||
| StlCoolingOutputRelayDefault | 1.3.6.1.4.1.850.103.1.4.13 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current Type of contact to make when output relay is activated.
| |||||||||||||||||||||
| StlCoolingAirFilterInterval | 1.3.6.1.4.1.850.103.1.4.14 | Integer32 | RW | ||||||||||||||||||
scalar · Integer32 · read-write · current The number of weeks before the air filter needs to be changed. | |||||||||||||||||||||
| StlCoolingWaterLeakContactType | 1.3.6.1.4.1.850.103.1.4.15 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current The input contact type.
| |||||||||||||||||||||
| NtlCoolingThresholds | 1.3.6.1.4.1.850.103.1.5 | ||||||||||||||||||||
| StlCoolingMaxAirFilterRunHours | 1.3.6.1.4.1.850.103.1.5.1 | Integer32 | RW | ||||||||||||||||||
scalar · Integer32 · read-write · current The maximum interval for air filter run hours before warning is annunciated. | |||||||||||||||||||||
| StlCoolingEnableAirFilterAlarm | 1.3.6.1.4.1.850.103.1.5.2 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current When enabled indicated that an alarm should occur when the maximum number of air filter run hours has been exceeded.
| |||||||||||||||||||||
| StlCoolingMaxSupplyTemp | 1.3.6.1.4.1.850.103.1.5.3 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current Maximum allowed supply air temperature before firing an alarm. | |||||||||||||||||||||
| StlCoolingMinSupplyTemp | 1.3.6.1.4.1.850.103.1.5.4 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current Minimum allowed supply air temperature allowed before firing an alarm. | |||||||||||||||||||||
| StlCoolingTempDiffAlarm | 1.3.6.1.4.1.850.103.1.5.5 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current Maximum allowed air temperature deviation from set allowed before firing an alarm. | |||||||||||||||||||||
| StlCoolingMaxReturnAirTemp | 1.3.6.1.4.1.850.103.1.5.6 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current When enabled indicated that an alarm should occur when the maximum number of air filter run hours has been exceeded. | |||||||||||||||||||||
| NtlCoolingAlarm | 1.3.6.1.4.1.850.103.6 | ||||||||||||||||||||
| NtlCoolingWellKnownAlarms | 1.3.6.1.4.1.850.103.6.3 | ||||||||||||||||||||
| NtlCoolingSupplyAirSensorFault | 1.3.6.1.4.1.850.103.6.3.1 | ||||||||||||||||||||
node · current The supply air sensor is in fault. | |||||||||||||||||||||
| NtlCoolingReturnAirSensorFault | 1.3.6.1.4.1.850.103.6.3.2 | ||||||||||||||||||||
node · current The return air sensor is in fault. | |||||||||||||||||||||
| NtlCoolingCondenserInletAirSensorFault | 1.3.6.1.4.1.850.103.6.3.3 | ||||||||||||||||||||
node · current The condenser inlet air sensor is in fault. | |||||||||||||||||||||
| NtlCoolingCondenserOutletAirSensorFault | 1.3.6.1.4.1.850.103.6.3.4 | ||||||||||||||||||||
node · current The condenser outlet air sensor is in fault. | |||||||||||||||||||||
| NtlCoolingSuctionTemperatureSensorFault | 1.3.6.1.4.1.850.103.6.3.5 | ||||||||||||||||||||
node · current The suction temperature sensor is in fault. | |||||||||||||||||||||
| NtlCoolingEvaporatorTemperatureSensorFault | 1.3.6.1.4.1.850.103.6.3.6 | ||||||||||||||||||||
node · current The evaporator temperature sensor is in fault. | |||||||||||||||||||||
| NtlCoolingAirFilterClogged | 1.3.6.1.4.1.850.103.6.3.7 | ||||||||||||||||||||
node · current The air filter is clogged. | |||||||||||||||||||||
| NtlCoolingAirFilterRunHoursViolation | 1.3.6.1.4.1.850.103.6.3.8 | ||||||||||||||||||||
node · current The air filter run hours was violated. | |||||||||||||||||||||
| NtlCoolingSuctionPressureSensorFault | 1.3.6.1.4.1.850.103.6.3.9 | ||||||||||||||||||||
node · current The suction pressure sensor is in fault. | |||||||||||||||||||||
| NtlCoolingInverterCommunicationsFault | 1.3.6.1.4.1.850.103.6.3.10 | ||||||||||||||||||||
node · current The inverter communications is in fault. | |||||||||||||||||||||
| NtlCoolingRemoteShutdownViaInputContact | 1.3.6.1.4.1.850.103.6.3.11 | ||||||||||||||||||||
node · current A remote shutdown was triggerd by an input contact. | |||||||||||||||||||||
| NtlCoolingCondensatePumpFault | 1.3.6.1.4.1.850.103.6.3.12 | ||||||||||||||||||||
node · current The condensate pump is in fault. | |||||||||||||||||||||
| NtlCoolingLowRefrigerantStartupFault | 1.3.6.1.4.1.850.103.6.3.13 | ||||||||||||||||||||
node · current The low refrigerant startup is in fault. | |||||||||||||||||||||
| NtlCoolingCondenserFanFault | 1.3.6.1.4.1.850.103.6.3.14 | ||||||||||||||||||||
node · current The condenser fan is in fault. | |||||||||||||||||||||
| NtlCoolingCondenserFailure | 1.3.6.1.4.1.850.103.6.3.15 | ||||||||||||||||||||
node · current The condenser has failed. | |||||||||||||||||||||
| NtlCoolingEvaporatorCoolingFailure | 1.3.6.1.4.1.850.103.6.3.16 | ||||||||||||||||||||
node · current The evaporator cooling is in fault. | |||||||||||||||||||||
| NtlCoolingReturnAirTempHigh | 1.3.6.1.4.1.850.103.6.3.17 | ||||||||||||||||||||
node · current The return air temperature is high. | |||||||||||||||||||||
| NtlCoolingSupplyAirTempHigh | 1.3.6.1.4.1.850.103.6.3.18 | ||||||||||||||||||||
node · current The supply air temperature is high. | |||||||||||||||||||||
| NtlCoolingEvaporatorFailure | 1.3.6.1.4.1.850.103.6.3.19 | ||||||||||||||||||||
node · current The evaporator has failed. | |||||||||||||||||||||
| NtlCoolingEvaporatorFreezeUp | 1.3.6.1.4.1.850.103.6.3.20 | ||||||||||||||||||||
node · current The evaporator is frozen. | |||||||||||||||||||||
| NtlCoolingDischargePressureHigh | 1.3.6.1.4.1.850.103.6.3.21 | ||||||||||||||||||||
node · current The discharge pressure is high. | |||||||||||||||||||||
| NtlCoolingPressureGaugeFailure | 1.3.6.1.4.1.850.103.6.3.22 | ||||||||||||||||||||
node · current The pressure gauge has failed. | |||||||||||||||||||||
| NtlCoolingDischargePressurePersistentHigh | 1.3.6.1.4.1.850.103.6.3.23 | ||||||||||||||||||||
node · current The discharge pressure is persistently high. | |||||||||||||||||||||
| NtlCoolingSuctionPressureLowStartFailure | 1.3.6.1.4.1.850.103.6.3.24 | ||||||||||||||||||||
node · current Cannot start due to low suction pressure. | |||||||||||||||||||||
| NtlCoolingSuctionPressureLow | 1.3.6.1.4.1.850.103.6.3.25 | ||||||||||||||||||||
node · current The suction pressure is low. | |||||||||||||||||||||
| NtlCoolingSuctionPressurePersistentLow | 1.3.6.1.4.1.850.103.6.3.26 | ||||||||||||||||||||
node · current The suction pressure is persistently low. | |||||||||||||||||||||
| NtlCoolingStartupLinePressureImbalance | 1.3.6.1.4.1.850.103.6.3.27 | ||||||||||||||||||||
node · current The startup line pressure is in imbalance. | |||||||||||||||||||||
| NtlCoolingCompressorFailure | 1.3.6.1.4.1.850.103.6.3.28 | ||||||||||||||||||||
node · current The compressor has failed. | |||||||||||||||||||||
| NtlCoolingCurrentLimit | 1.3.6.1.4.1.850.103.6.3.29 | ||||||||||||||||||||
node · current The current is out of range. | |||||||||||||||||||||
| NtlCoolingWaterLeak | 1.3.6.1.4.1.850.103.6.3.30 | ||||||||||||||||||||
node · current Water is leaking. | |||||||||||||||||||||
| NtlCoolingFanUnderCurrent | 1.3.6.1.4.1.850.103.6.3.31 | ||||||||||||||||||||
node · current The fan is under current. | |||||||||||||||||||||
| NtlCoolingFanOverCurrent | 1.3.6.1.4.1.850.103.6.3.32 | ||||||||||||||||||||
node · current The fan is over current. | |||||||||||||||||||||
| NtlCoolingDischargePressureSensorFault | 1.3.6.1.4.1.850.103.6.3.33 | ||||||||||||||||||||
node · current The discharge pressure sensor is in fault. | |||||||||||||||||||||
| NtlCoolingWaterFull | 1.3.6.1.4.1.850.103.6.3.34 | ||||||||||||||||||||
node · current Water is Full. | |||||||||||||||||||||
| NtlCoolingAutoCoolingOn | 1.3.6.1.4.1.850.103.6.3.35 | ||||||||||||||||||||
node · current Automatic cooling was activated to lower the temperature below the remote set point. | |||||||||||||||||||||
| NtlCoolingPowerButtonPressed | 1.3.6.1.4.1.850.103.6.3.36 | ||||||||||||||||||||
node · current Power button was pressed on the front panel. | |||||||||||||||||||||
| NtlCoolingDisconnectedFromDevice | 1.3.6.1.4.1.850.103.6.3.37 | ||||||||||||||||||||
node · current The device communications is disconnected. | |||||||||||||||||||||
| NtlSrCoolNet | 1.3.6.1.4.1.850.104 | ||||||||||||||||||||
| NtlSrCoolNetData | 1.3.6.1.4.1.850.104.1 | ||||||||||||||||||||
| NtlSrCoolNetIdent | 1.3.6.1.4.1.850.104.1.1 | ||||||||||||||||||||
| StlSrCoolNetModel | 1.3.6.1.4.1.850.104.1.1.1 | DisplayString | RO | ||||||||||||||||||
scalar · DisplayString · read-only · current The model name for the device attached to the SRCOOLNET. | |||||||||||||||||||||
| StlSrCoolNetManufacturer | 1.3.6.1.4.1.850.104.1.1.2 | DisplayString | RO | ||||||||||||||||||
scalar · DisplayString · read-only · current The manufacturer of the AC Unit. | |||||||||||||||||||||
| StlSrCoolNetSerialNumber | 1.3.6.1.4.1.850.104.1.1.3 | DisplayString | RO | ||||||||||||||||||
scalar · DisplayString · read-only · current The serial number of the SRCOOLNET device. | |||||||||||||||||||||
| StlSrCoolNetHostSoftwareVersion | 1.3.6.1.4.1.850.104.1.1.4 | DisplayString | RO | ||||||||||||||||||
scalar · DisplayString · read-only · current The software version of the SRCOOLNET device. | |||||||||||||||||||||
| StlSrCoolNetName | 1.3.6.1.4.1.850.104.1.1.5 | DisplayString | RW | ||||||||||||||||||
scalar · DisplayString · read-write · current The user defined name for the AC Unit. | |||||||||||||||||||||
| StlSrCoolNetLocation | 1.3.6.1.4.1.850.104.1.1.6 | DisplayString | RW | ||||||||||||||||||
scalar · DisplayString · read-write · current The user defined location of the AC Unit. | |||||||||||||||||||||
| NtlSrCoolNetStatus | 1.3.6.1.4.1.850.104.1.2 | ||||||||||||||||||||
| StlSrCoolNetMode | 1.3.6.1.4.1.850.104.1.2.1 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The current mode of SRCOOLNET.
| |||||||||||||||||||||
| StlSrCoolNetFanSpeed | 1.3.6.1.4.1.850.104.1.2.2 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The current speed of the fan.
| |||||||||||||||||||||
| StlSrCoolNetReturnAirTemp | 1.3.6.1.4.1.850.104.1.2.3 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The return air stream temperature in tenths of degrees in the units Celsius/Fahrenheit as specified in tlSrCoolNetDisplayUnits. | |||||||||||||||||||||
| StlSrCoolNetWaterFull | 1.3.6.1.4.1.850.104.1.2.4 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current Indicates the water reservoir is full or not full.
| |||||||||||||||||||||
| StlSrCoolNetCurrentRemoteTemp | 1.3.6.1.4.1.850.104.1.2.5 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The EnviroSense temperature in tenths of degrees in Celsius or Fahrenheit depending upon value of tlSrCoolNetDisplayUnits. Only available if EnviroSense is connected to SRCOOLNET. | |||||||||||||||||||||
| StlSrCoolNetDisplayUnits | 1.3.6.1.4.1.850.104.1.2.6 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current Selects English or Metric display for all readings. AC unit must be manually configured to match this setting.
| |||||||||||||||||||||
| NtlSrCoolNetConfig | 1.3.6.1.4.1.850.104.1.3 | ||||||||||||||||||||
| StlSrCoolNetOnOff | 1.3.6.1.4.1.850.104.1.3.1 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current Turn the unit off or on.
| |||||||||||||||||||||
| StlSrCoolSetMode | 1.3.6.1.4.1.850.104.1.3.2 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current Set the operating mode of cooling unit. Unit must be ON to set mode.
| |||||||||||||||||||||
| StlSrCoolNetSetPointTemp | 1.3.6.1.4.1.850.104.1.3.3 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current The local set point temperature in tenths of degrees in Celsius or Fahrenheit based upon tlSrCoolNetDisplayUnits. | |||||||||||||||||||||
| StlSrCoolNetRemoteSetPointTemp | 1.3.6.1.4.1.850.104.1.3.4 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current The remote set point temperature in tenths of degrees in Celsius or Fahrenheit based upon tlSrCoolNetDisplayUnits. Only available when EnviroSense is connected to SRCOOLNET. | |||||||||||||||||||||
| StlSrCoolNetFanSpeedSetting | 1.3.6.1.4.1.850.104.1.3.5 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current Set the fan speed of the AC unit.
| |||||||||||||||||||||
| StlSrCoolNetRemoteSetpointEnable | 1.3.6.1.4.1.850.104.1.3.6 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current Use remote temperature setpoint for control point versus return air temp. Only available when EnviroSense is connected to SRCOOLNET.
| |||||||||||||||||||||
| StlSrCoolNetFanAlwaysOn | 1.3.6.1.4.1.850.104.1.3.7 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current Leave fans on when not cooling. Only available when EnviroSense is connected to SRCOOLNET.
| |||||||||||||||||||||
| NtlSrCoolNetAlarm | 1.3.6.1.4.1.850.104.2 | ||||||||||||||||||||
| NtlSrCoolNetWellKnownAlarms | 1.3.6.1.4.1.850.104.2.1 | ||||||||||||||||||||
| NtlSrCoolNetWaterFullAlarm | 1.3.6.1.4.1.850.104.2.1.1 | ||||||||||||||||||||
node · current Water reservoir full. | |||||||||||||||||||||
Traps / Notifications
- tlUpsTrapAlarmEntryAdded
1.3.6.1.4.1.850.100.2.3 - tlUpsTrapAlarmEntryAddedV1
1.3.6.1.4.1.850.100.2.0.3 - tlUpsTrapAlarmEntryRemoved
1.3.6.1.4.1.850.100.2.4 - tlUpsTrapAlarmEntryRemovedV1
1.3.6.1.4.1.850.100.2.0.4 - tlUpsTrapSystemShutdown
1.3.6.1.4.1.850.100.2.6 - tlUpsTrapSystemStartup
1.3.6.1.4.1.850.100.2.5