companyMIB
Datalogic S.p.AThe MIB module to describe UPS
snmptranslate -m companyMIB -Tpsnmpwalk -v2c -c <community> -m companyMIB <host> 1.3.6.1.4.1.21111Imports
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
|---|---|
| SNMPv2-SMI | Bits, Integer32, IpAddress, MODULE-IDENTITY, MibIdentifier, OBJECT-IDENTITY, OBJECT-TYPE, TRAP-TYPE, TimeTicks, Unsigned32, enterprises, iso |
| SNMPv2-TC | DisplayString, PhysAddress, TEXTUAL-CONVENTION |
| UPS-MIB | NonNegativeInteger, PositiveInteger |
OID tree
| Name | OID | Type | Access | Status | Example | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| IcompanyMIB | 1.3.6.1.4.1.21111 | ||||||||||||||||
identity The MIB module to describe UPS | |||||||||||||||||
| Nproducts | 1.3.6.1.4.1.21111.1 | ||||||||||||||||
| Nups | 1.3.6.1.4.1.21111.1.1 | ||||||||||||||||
| NupsIdent | 1.3.6.1.4.1.21111.1.1.1 | ||||||||||||||||
| SupsIdManufacturer | 1.3.6.1.4.1.21111.1.1.1.1 | DisplayString (SIZE (0..31)) | RO | mandatory | |||||||||||||
scalar · DisplayString (SIZE (0..31)) · read-only · mandatory The name of the UPS manufacturer. | |||||||||||||||||
| SupsIdProtocol | 1.3.6.1.4.1.21111.1.1.1.2 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The UPS Protocol id.
| |||||||||||||||||
| SupsIdModelName | 1.3.6.1.4.1.21111.1.1.1.3 | DisplayString (SIZE (0..15)) | RO | mandatory | G2-6KL | ||||||||||||
scalar · DisplayString (SIZE (0..15)) · read-only · mandatory The UPS Model designation. Example values from LibreNMS test devices
| |||||||||||||||||
| SupsIdSerialNumber | 1.3.6.1.4.1.21111.1.1.1.4 | DisplayString (SIZE (0..31)) | RO | mandatory | 11112222333344 | ||||||||||||
scalar · DisplayString (SIZE (0..31)) · read-only · mandatory The UPS serial no. Example values from LibreNMS test devices
| |||||||||||||||||
| SupsIdName | 1.3.6.1.4.1.21111.1.1.1.5 | DisplayString (SIZE (0..31)) | RW | mandatory | |||||||||||||
scalar · DisplayString (SIZE (0..31)) · read-write · mandatory A string identifying the UPS. This object should be set by the administrator. | |||||||||||||||||
| SupsIdFWVersion | 1.3.6.1.4.1.21111.1.1.1.6 | DisplayString (SIZE (0..31)) | RO | mandatory | VERFW:01428.1400 | ||||||||||||
scalar · DisplayString (SIZE (0..31)) · read-only · mandatory Main CPU firmware version. Example values from LibreNMS test devices
| |||||||||||||||||
| SupsIdUPSType | 1.3.6.1.4.1.21111.1.1.1.7 | INTEGER | RO | mandatory | on-line(2) | ||||||||||||
scalar · INTEGER · read-only · mandatory UPS type.
Example values from LibreNMS test devices
| |||||||||||||||||
| NupsRating | 1.3.6.1.4.1.21111.1.1.2 | ||||||||||||||||
| SupsRatinVoltage | 1.3.6.1.4.1.21111.1.1.2.1 | NonNegativeInteger | RO | ||||||||||||||
scalar · NonNegativeInteger · read-only · current The rating input voltage of UPS
| |||||||||||||||||
| SupsRatoutVoltage | 1.3.6.1.4.1.21111.1.1.2.2 | NonNegativeInteger | RO | ||||||||||||||
scalar · NonNegativeInteger · read-only · current The rating output voltage of UPS
| |||||||||||||||||
| SupsRatoutFrequency | 1.3.6.1.4.1.21111.1.1.2.3 | NonNegativeInteger | RO | ||||||||||||||
scalar · NonNegativeInteger · read-only · current The rating output frequency of UPS
| |||||||||||||||||
| SupsRatoutCurrent | 1.3.6.1.4.1.21111.1.1.2.4 | NonNegativeInteger | RO | ||||||||||||||
scalar · NonNegativeInteger · read-only · current The rating output current of UPS
| |||||||||||||||||
| SupsRatoutApparentPower | 1.3.6.1.4.1.21111.1.1.2.5 | NonNegativeInteger | RO | ||||||||||||||
scalar · NonNegativeInteger · read-only · current The rating output apparent power of UPS
| |||||||||||||||||
| SupsRatoutTruePower | 1.3.6.1.4.1.21111.1.1.2.6 | NonNegativeInteger | RO | ||||||||||||||
scalar · NonNegativeInteger · read-only · current The rating output true power of UPS
| |||||||||||||||||
| SupsRatBatVoltage | 1.3.6.1.4.1.21111.1.1.2.7 | NonNegativeInteger | RO | ||||||||||||||
scalar · NonNegativeInteger · read-only · current The rating battery voltage of UPS
| |||||||||||||||||
| NupsBattery | 1.3.6.1.4.1.21111.1.1.3 | ||||||||||||||||
| SupsBatStatus | 1.3.6.1.4.1.21111.1.1.3.1 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The indication of the status in the UPS system's batteries.
| |||||||||||||||||
| SupsBatSecondsOnBattery | 1.3.6.1.4.1.21111.1.1.3.2 | INTEGER | RO | ||||||||||||||
scalar · INTEGER · read-only · current If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. -1 shall be returned if the unit is not on battery power.
| |||||||||||||||||
| SupsBatEstMinutesRemaining | 1.3.6.1.4.1.21111.1.1.3.3 | INTEGER | RO | ||||||||||||||
scalar · INTEGER · read-only · current An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.
| |||||||||||||||||
| SupsBatEstChargeRemaining | 1.3.6.1.4.1.21111.1.1.3.4 | INTEGER (0..100) | RO | ||||||||||||||
scalar · INTEGER (0..100) · read-only · current An estimate of the battery charge remaining expressed as a percent of full charge.
| |||||||||||||||||
| SupsBatPBatVoltage | 1.3.6.1.4.1.21111.1.1.3.5 | NonNegativeInteger | RO | ||||||||||||||
scalar · NonNegativeInteger · read-only · current The magnitude of the present Positive battery voltage.
| |||||||||||||||||
| SupsBatNBatVoltage | 1.3.6.1.4.1.21111.1.1.3.6 | NonNegativeInteger | RO | ||||||||||||||
scalar · NonNegativeInteger · read-only · current The magnitude of the present negative battery voltage.
| |||||||||||||||||
| SupsBatPBatCurrent | 1.3.6.1.4.1.21111.1.1.3.7 | INTEGER | RO | ||||||||||||||
scalar · INTEGER · read-only · current The positive battery present current.
| |||||||||||||||||
| SupsBatNBatCurrent | 1.3.6.1.4.1.21111.1.1.3.8 | INTEGER | RO | ||||||||||||||
scalar · INTEGER · read-only · current The present negative battery current.
| |||||||||||||||||
| SupsBatPBatChargCurrent | 1.3.6.1.4.1.21111.1.1.3.9 | INTEGER | RO | ||||||||||||||
scalar · INTEGER · read-only · current The Positive battery charging current.
| |||||||||||||||||
| SupsBatNBatchargCurrent | 1.3.6.1.4.1.21111.1.1.3.10 | INTEGER | RO | ||||||||||||||
scalar · INTEGER · read-only · current The present negative battery charging current.
| |||||||||||||||||
| SupsBatPBatDischargCurrent | 1.3.6.1.4.1.21111.1.1.3.11 | INTEGER | RO | ||||||||||||||
scalar · INTEGER · read-only · current The present positive battery discharging current.
| |||||||||||||||||
| SupsBatNBatDischargCurrent | 1.3.6.1.4.1.21111.1.1.3.12 | INTEGER | RO | ||||||||||||||
scalar · INTEGER · read-only · current The present negative battery discharging current.
| |||||||||||||||||
| SupsBatTemperature | 1.3.6.1.4.1.21111.1.1.3.13 | INTEGER | RO | ||||||||||||||
scalar · INTEGER · read-only · current The ambient temperature at or near the UPS Battery casing.
| |||||||||||||||||
| SupsBatNumberInSeries | 1.3.6.1.4.1.21111.1.1.3.14 | PositiveInteger | RO | 20 | |||||||||||||
scalar · PositiveInteger · read-only · current The number of battery in series. Example values from LibreNMS test devices
| |||||||||||||||||
| SupsBatNumberInParallel | 1.3.6.1.4.1.21111.1.1.3.15 | PositiveInteger | RO | 1 | |||||||||||||
scalar · PositiveInteger · read-only · current The number of battery in Parallel. Example values from LibreNMS test devices
| |||||||||||||||||
| SupsBatPBatDischargCurrent2 | 1.3.6.1.4.1.21111.1.1.3.16 | INTEGER | RO | ||||||||||||||
scalar · INTEGER · read-only · current The present positive battery pipe2 discharging current.
| |||||||||||||||||
| NupsInput | 1.3.6.1.4.1.21111.1.1.4 | ||||||||||||||||
| SupsInLineBads | 1.3.6.1.4.1.21111.1.1.4.1 | NonNegativeInteger | RO | ||||||||||||||
scalar · NonNegativeInteger · read-only · current A count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the input transitions from zero out-of-tolerance lines to one or more input lines out-of-tolerance. | |||||||||||||||||
| SupsInTtlApparentPower | 1.3.6.1.4.1.21111.1.1.4.2 | NonNegativeInteger | RO | ||||||||||||||
scalar · NonNegativeInteger · read-only · current Total input apparent power .
| |||||||||||||||||
| SupsInTtlTruePower | 1.3.6.1.4.1.21111.1.1.4.3 | NonNegativeInteger | RO | ||||||||||||||
scalar · NonNegativeInteger · read-only · current Total input active(true) power .
| |||||||||||||||||
| SupsInNumLines | 1.3.6.1.4.1.21111.1.1.4.4 | NonNegativeInteger | RO | ||||||||||||||
scalar · NonNegativeInteger · read-only · current The number of input lines utilized in this device. This variable indicates the number of rows in the input table. | |||||||||||||||||
| TupsInTable | 1.3.6.1.4.1.21111.1.1.4.5 | NA | |||||||||||||||
table · not-accessible · current A list of input table entries. The number of entries is given by the value of upsInputNumLines. | |||||||||||||||||
| RupsInEntry | 1.3.6.1.4.1.21111.1.1.4.5.1 | NA | |||||||||||||||
row · not-accessible · current An entry containing information applicable to a particular input line.
| |||||||||||||||||
| CupsInLineIndex | 1.3.6.1.4.1.21111.1.1.4.5.1.1 | INTEGER (0..10) | RO | ||||||||||||||
column · INTEGER (0..10) · read-only · current The number of output lines | |||||||||||||||||
| CupsInFrequency | 1.3.6.1.4.1.21111.1.1.4.5.1.2 | NonNegativeInteger | RO | ||||||||||||||
column · NonNegativeInteger · read-only · current The present input frequency.
| |||||||||||||||||
| CupsInVoltage | 1.3.6.1.4.1.21111.1.1.4.5.1.3 | INTEGER | RO | ||||||||||||||
column · INTEGER · read-only · current The input utility line voltage .
| |||||||||||||||||
| CupsInCurrent | 1.3.6.1.4.1.21111.1.1.4.5.1.4 | INTEGER | RO | ||||||||||||||
column · INTEGER · read-only · current The magnitude of the present input current
| |||||||||||||||||
| CupsInApparentPower | 1.3.6.1.4.1.21111.1.1.4.5.1.5 | NonNegativeInteger | RO | ||||||||||||||
column · NonNegativeInteger · read-only · current The magnitude of the present input Apparent power.
| |||||||||||||||||
| CupsInTruePower | 1.3.6.1.4.1.21111.1.1.4.5.1.6 | NonNegativeInteger | RO | ||||||||||||||
column · NonNegativeInteger · read-only · current The magnitude of the present input true power.
| |||||||||||||||||
| CupsInPowerFactor | 1.3.6.1.4.1.21111.1.1.4.5.1.7 | NonNegativeInteger | RO | ||||||||||||||
column · NonNegativeInteger · read-only · current Input true power/apparent power factor
| |||||||||||||||||
| CupsInLineVoltage | 1.3.6.1.4.1.21111.1.1.4.5.1.8 | INTEGER | RO | ||||||||||||||
column · INTEGER · read-only · current The input utility line voltage . if upsInLineIndex =1, upsInLineVoltage = Line voltage of RS phase; if upsInLineIndex =2, upsInLineVoltage = Line voltage of ST phase; if upsInLineIndex =3, upsInLineVoltage = Line voltage of TR phase.
| |||||||||||||||||
| SupsInTtlVoltage | 1.3.6.1.4.1.21111.1.1.4.6 | INTEGER | RO | ||||||||||||||
scalar · INTEGER · read-only · current The input utility line tatol voltage .
| |||||||||||||||||
| SupsInTtlCurrent | 1.3.6.1.4.1.21111.1.1.4.7 | INTEGER | RO | ||||||||||||||
scalar · INTEGER · read-only · current The input utility line tatol current.
| |||||||||||||||||
| NupsOutput | 1.3.6.1.4.1.21111.1.1.5 | ||||||||||||||||
| SupsOutSource | 1.3.6.1.4.1.21111.1.1.5.1 | INTEGER | RO | ||||||||||||||
scalar · INTEGER · read-only · current The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker.==UPS standby mode
| |||||||||||||||||
| SupsOutFrequency defined twice | 1.3.6.1.4.1.21111.1.1.5.2 | INTEGER | RO | ||||||||||||||
scalar · INTEGER · read-only · current The current output frequency of the UPS system
| |||||||||||||||||
| SupsOutTtlApparentPower | 1.3.6.1.4.1.21111.1.1.5.3 | NonNegativeInteger | RO | ||||||||||||||
scalar · NonNegativeInteger · read-only · current Total output apparent power .
| |||||||||||||||||
| SupsOutTtlTruePower | 1.3.6.1.4.1.21111.1.1.5.4 | NonNegativeInteger | RO | ||||||||||||||
scalar · NonNegativeInteger · read-only · current Total output active(true) power .
| |||||||||||||||||
| SupsOutTtlPercentLoad | 1.3.6.1.4.1.21111.1.1.5.5 | INTEGER (0..100) | RO | ||||||||||||||
scalar · INTEGER (0..100) · read-only · current The percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA.
| |||||||||||||||||
| SupsOutNumLines | 1.3.6.1.4.1.21111.1.1.5.6 | INTEGER | RO | ||||||||||||||
scalar · INTEGER · read-only · current The number of output lines utilized in this device. This variable indicates the number of rows in the output table. | |||||||||||||||||
| TupsOutTable | 1.3.6.1.4.1.21111.1.1.5.7 | NA | |||||||||||||||
table · not-accessible · current A list of output table entries. The number of entries is given by the value of upsOutputNumLines. | |||||||||||||||||
| RupsOutEntry | 1.3.6.1.4.1.21111.1.1.5.7.1 | NA | |||||||||||||||
row · not-accessible · current An entry containing information applicable to a particular output line.
| |||||||||||||||||
| CupsOutLineIndex | 1.3.6.1.4.1.21111.1.1.5.7.1.1 | INTEGER (0..10) | RO | ||||||||||||||
column · INTEGER (0..10) · read-only · current The output line identifier. | |||||||||||||||||
| CupsOutVoltage | 1.3.6.1.4.1.21111.1.1.5.7.1.2 | INTEGER | RO | ||||||||||||||
column · INTEGER · read-only · current The output voltage of the UPS system.
| |||||||||||||||||
| CupsOutCurrent | 1.3.6.1.4.1.21111.1.1.5.7.1.3 | INTEGER | RO | ||||||||||||||
column · INTEGER · read-only · current The output current of the UPS system
| |||||||||||||||||
| CupsOutApparentPower | 1.3.6.1.4.1.21111.1.1.5.7.1.4 | NonNegativeInteger | RO | ||||||||||||||
column · NonNegativeInteger · read-only · current The present output apparent power.
| |||||||||||||||||
| CupsOutTruePower | 1.3.6.1.4.1.21111.1.1.5.7.1.5 | NonNegativeInteger | RO | ||||||||||||||
column · NonNegativeInteger · read-only · current The present output true power.
| |||||||||||||||||
| CupsOutPowerFactor | 1.3.6.1.4.1.21111.1.1.5.7.1.6 | NonNegativeInteger | RO | ||||||||||||||
column · NonNegativeInteger · read-only · current Output true power/apparent power factor
| |||||||||||||||||
| CupsOutPercentLoad | 1.3.6.1.4.1.21111.1.1.5.7.1.7 | INTEGER (0..100) | RO | ||||||||||||||
column · INTEGER (0..100) · read-only · current The percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA.
| |||||||||||||||||
| CupsOutLineVoltage | 1.3.6.1.4.1.21111.1.1.5.7.1.8 | INTEGER | RO | ||||||||||||||
column · INTEGER · read-only · current The output line voltage of the UPS system.
if upsOutLineIndex =1, upsOutLineVoltage = Line voltage of RS phase;
if upsOutLineIndex =2, upsOutLineVoltage = Line voltage of ST phase;
if upsOutLineIndex =3, upsOutLineVoltage = Line voltage of TR phase.
| |||||||||||||||||
| SupsOutFrequency defined twice | 1.3.6.1.4.1.21111.1.1.5.7.1.9 | NonNegativeInteger | RO | ||||||||||||||
scalar · NonNegativeInteger · read-only · current The current output frequency of the UPS system
| |||||||||||||||||
| SupsOutTtlVoltage | 1.3.6.1.4.1.21111.1.1.5.8 | INTEGER | RO | ||||||||||||||
scalar · INTEGER · read-only · current Total output voltage .
| |||||||||||||||||
| SupsOutTtlCurrent | 1.3.6.1.4.1.21111.1.1.5.9 | INTEGER | RO | ||||||||||||||
scalar · INTEGER · read-only · current Total output current.
| |||||||||||||||||
| SupsOutStatus | 1.3.6.1.4.1.21111.1.1.5.10 | DisplayString (SIZE (4)) | RO | ||||||||||||||
scalar · DisplayString (SIZE (4)) · read-only · current For HVDC device.
char status[4];
status[0]status[1]:00, no output1; 01, line output1; 02, bat output1
status[2]status[3]:00, no output2; 01, line output2; 02, bat output2 | |||||||||||||||||
| SupsOutSource2 | 1.3.6.1.4.1.21111.1.1.5.11 | INTEGER | RO | ||||||||||||||
scalar · INTEGER · read-only · current For HVDC(protocol:P12) machine. The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker.==UPS standby mode
| |||||||||||||||||
| NupsBypass | 1.3.6.1.4.1.21111.1.1.6 | ||||||||||||||||
| SupsByFrequency | 1.3.6.1.4.1.21111.1.1.6.1 | INTEGER | RO | ||||||||||||||
scalar · INTEGER · read-only · current The present bypass frequency.
| |||||||||||||||||
| SupsByNumLines | 1.3.6.1.4.1.21111.1.1.6.2 | INTEGER | RO | ||||||||||||||
scalar · INTEGER · read-only · current The number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table. | |||||||||||||||||
| TupsByTable | 1.3.6.1.4.1.21111.1.1.6.3 | NA | |||||||||||||||
table · not-accessible · current A list of bypass table entries. The number of entries is given by the value of upsBypassNumLines. | |||||||||||||||||
| RupsByEntry | 1.3.6.1.4.1.21111.1.1.6.3.1 | NA | |||||||||||||||
row · not-accessible · current An entry containing information applicable to a particular bypass input.
| |||||||||||||||||
| CupsByLineIndex | 1.3.6.1.4.1.21111.1.1.6.3.1.1 | INTEGER (0..65535) | RO | ||||||||||||||
column · INTEGER (0..65535) · read-only · current The bypass line identifier. | |||||||||||||||||
| CupsByVoltage | 1.3.6.1.4.1.21111.1.1.6.3.1.2 | INTEGER | RO | ||||||||||||||
column · INTEGER · read-only · current The present bypass voltage.
| |||||||||||||||||
| CupsByCurrent | 1.3.6.1.4.1.21111.1.1.6.3.1.3 | INTEGER | RO | ||||||||||||||
column · INTEGER · read-only · current The present bypass current.
| |||||||||||||||||
| CupsByPower | 1.3.6.1.4.1.21111.1.1.6.3.1.4 | NonNegativeInteger | RO | ||||||||||||||
column · NonNegativeInteger · read-only · current The present true power conveyed by the bypass.
| |||||||||||||||||
| CupsByLineVoltage | 1.3.6.1.4.1.21111.1.1.6.3.1.5 | INTEGER | RO | ||||||||||||||
column · INTEGER · read-only · current The present bypass line voltage. if upsByLineIndex=1,upsByLineVoltage=Line voltage of RS phase; if upsByLineIndex=2,upsByLineVoltage=Line voltage of ST phase; if upsByLineIndex=3,upsByLineVoltage=Line voltage of TR phase.
| |||||||||||||||||
| NupsTest | 1.3.6.1.4.1.21111.1.1.7 | ||||||||||||||||
| SupsTstBatteryTest | 1.3.6.1.4.1.21111.1.1.7.1 | INTEGER | RW | ||||||||||||||
scalar · INTEGER · read-write · current This object specify the battery test type and initiate battery test. If battTestWithTime selected, the test time is refer to upsTestBatteryTestTime.
| |||||||||||||||||
| SupsTstBatteryTestResult | 1.3.6.1.4.1.21111.1.1.7.2 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The results of the current or last UPS diagnostics test performed. The values for donePassed(1), doneWarning(2), and doneError(3) indicate that the test completed either successfully, with a warning, or with an error, respectively. The value aborted(4) is returned for tests which are aborted by setting the value of upsTestId to upsTestAbortTestInProgress. Tests which have not yet concluded are indicated by inProgress(5). The value noTestsInitiated(6) indicates that no previous test results are available, such as is the case when no tests have been run since the last reinitialization of the network management subsystem and the system has no provision for non- volatile storage of test results.
| |||||||||||||||||
| SupsTstBatteryTestStartTime | 1.3.6.1.4.1.21111.1.1.7.3 | DisplayString (SIZE (19)) | RO | ||||||||||||||
scalar · DisplayString (SIZE (19)) · read-only · current The value of the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of upsTestBatteryTestResult is noTestsInitiated(6), upsTestStartTime has the value 01/01/1970 00:00:00. format is (MM/DD/YYYY hh:mm:ss) | |||||||||||||||||
| SupsTstBatterySettingTime | 1.3.6.1.4.1.21111.1.1.7.4 | INTEGER (12..5940) | RW | mandatory | |||||||||||||
scalar · INTEGER (12..5940) · read-write · mandatory The object specify the test time for battery test, the unit is seconds | |||||||||||||||||
| NupsControl | 1.3.6.1.4.1.21111.1.1.8 | ||||||||||||||||
| SupsCtlShutdownDelay | 1.3.6.1.4.1.21111.1.1.8.1 | INTEGER (-2..2147483648) | RW | ||||||||||||||
scalar · INTEGER (-2..2147483648) · read-write · current The delay in seconds the UPS remains on after being told to turn off. if value=-2 cancel shutdown, if value=-1 donothing, value=0 shutdown ups immediately
| |||||||||||||||||
| SupsCtlSleepTime | 1.3.6.1.4.1.21111.1.1.8.2 | INTEGER (-1..2147483648) | RW | ||||||||||||||
scalar · INTEGER (-1..2147483648) · read-write · current The time in minutes for the UPS to go to sleep when instructed. When in sleep mode, the UPS will not provide output power regardless of the input line state. Once the specified time has elapsed, output power will be restored. This is a configuration setting. The UPS will not go to sleep until told to do so by the manager from a management station. Any input value is allowed, however the UPS only recognizes 0 - 9999 minutes in one minute increments. If the provided value is higher than the highest acceptable value, the highest acceptable value is used.
| |||||||||||||||||
| SupsCtlStartupAfterDelay | 1.3.6.1.4.1.21111.1.1.8.3 | INTEGER (-1..2147483648) | RW | ||||||||||||||
scalar · INTEGER (-1..2147483648) · read-write · current Setting this object will start the output after the
indicated number of seconds, including starting the
UPS, if necessary. -1 mean not startup.
must set upsCtlStartupAfterDelay before upsCtlShutdownDelay ,
the value must larger than 59 if the value not equal -1
| |||||||||||||||||
| SupsCtlbuzzer | 1.3.6.1.4.1.21111.1.1.8.4 | INTEGER | RW | ||||||||||||||
scalar · INTEGER · read-write · current Setting this object to 'on' or 'off' to enable or disable buzzer
| |||||||||||||||||
| SupsCtlRemoteControlUPS | 1.3.6.1.4.1.21111.1.1.8.5 | INTEGER | RW | ||||||||||||||
scalar · INTEGER · read-write · current Setting this object to turn 'on' or 'off' UPS
| |||||||||||||||||
| SupsCtloutletPoweron | 1.3.6.1.4.1.21111.1.1.8.6 | INTEGER (1..2) | WO | ||||||||||||||
scalar · INTEGER (1..2) · write-only · current Setting this object to 1 means 1st outlet,2 means 2nd outlet , immediately process | |||||||||||||||||
| SupsCtloutletPoweroff | 1.3.6.1.4.1.21111.1.1.8.7 | INTEGER (1..2) | WO | ||||||||||||||
scalar · INTEGER (1..2) · write-only · current Setting this object to 1 means 1st outlet, 2 means 2nd outlet , immediately process | |||||||||||||||||
| SupsCtlOutlet1Powerofftime | 1.3.6.1.4.1.21111.1.1.8.8 | INTEGER (-1..999) | RW | ||||||||||||||
scalar · INTEGER (-1..999) · read-write · current setting this object to -1 means this control not effect,
0 means immediately process,
>0 means wait times unit is minutes
use in battery mode | |||||||||||||||||
| SupsCtlOutlet2Powerofftime | 1.3.6.1.4.1.21111.1.1.8.9 | INTEGER (-1..999) | RW | ||||||||||||||
scalar · INTEGER (-1..999) · read-write · current setting this object to -1 means this control not effect, 0 means immediately process , >0 means wait times unit is minutes .use in battery mode | |||||||||||||||||
| SupsCtlResetConfigure | 1.3.6.1.4.1.21111.1.1.8.10 | INTEGER | RW | ||||||||||||||
scalar · INTEGER · read-write · current reset all configure para to default.
| |||||||||||||||||
| NagentConfig | 1.3.6.1.4.1.21111.1.1.9 | ||||||||||||||||
| SagentConfigDatetime | 1.3.6.1.4.1.21111.1.1.9.1 | DisplayString (SIZE (19)) | RW | ||||||||||||||
scalar · DisplayString (SIZE (19)) · read-write · current The datetime in agent, format is (MM/DD/YYYY hh:mm:ss) | |||||||||||||||||
| NcommConfig | 1.3.6.1.4.1.21111.1.1.10 | ||||||||||||||||
| ScommBaudRate | 1.3.6.1.4.1.21111.1.1.10.1 | INTEGER | RW | ||||||||||||||
scalar · INTEGER · read-write · current The UPS communicate baudrate
| |||||||||||||||||
| ScommDatabits | 1.3.6.1.4.1.21111.1.1.10.2 | INTEGER (8..9) | RW | ||||||||||||||
scalar · INTEGER (8..9) · read-write · current The UPS communicate data bits | |||||||||||||||||
| ScommStopbits | 1.3.6.1.4.1.21111.1.1.10.3 | INTEGER (1..2) | RW | ||||||||||||||
scalar · INTEGER (1..2) · read-write · current The UPS communicate stop bits | |||||||||||||||||
| ScommParity | 1.3.6.1.4.1.21111.1.1.10.4 | INTEGER | RW | ||||||||||||||
scalar · INTEGER · read-write · current The UPS communicate Parity
| |||||||||||||||||
| ScommTimeout | 1.3.6.1.4.1.21111.1.1.10.5 | INTEGER (100..1000) | RW | ||||||||||||||
scalar · INTEGER (100..1000) · read-write · current The UPS communicate timeout | |||||||||||||||||
| NupsConfig | 1.3.6.1.4.1.21111.1.1.11 | ||||||||||||||||
| SupsCfgAlarmbypass | 1.3.6.1.4.1.21111.1.1.11.1 | INTEGER | RW | ||||||||||||||
scalar · INTEGER · read-write · current Setting this object enable /disable alarm bypass mode
| |||||||||||||||||
| SupsCfgAlarmbattery | 1.3.6.1.4.1.21111.1.1.11.2 | INTEGER | RW | ||||||||||||||
scalar · INTEGER · read-write · current Setting this object enable/disable alarm battery mode
| |||||||||||||||||
| SupsCfgAutoReboot | 1.3.6.1.4.1.21111.1.1.11.3 | INTEGER | RW | ||||||||||||||
scalar · INTEGER · read-write · current Setting this object enable/disable auto reboot
| |||||||||||||||||
| SupsCfgBypasswhenupsoff | 1.3.6.1.4.1.21111.1.1.11.4 | INTEGER | RW | ||||||||||||||
scalar · INTEGER · read-write · current Setting this object start/stop bypass when ups off
| |||||||||||||||||
| SupsCfgBatterDDP | 1.3.6.1.4.1.21111.1.1.11.5 | INTEGER | RW | ||||||||||||||
scalar · INTEGER · read-write · current Setting this object to enable/disable battery deep-discharge protection
| |||||||||||||||||
| SupsCfgConvertermode | 1.3.6.1.4.1.21111.1.1.11.6 | INTEGER | RW | ||||||||||||||
scalar · INTEGER · read-write · current Setting this object to enable/disable converter mode
| |||||||||||||||||
| SupsCfgECOmode | 1.3.6.1.4.1.21111.1.1.11.7 | INTEGER | RW | ||||||||||||||
scalar · INTEGER · read-write · current Setting this object to enable/disable ECO mode
| |||||||||||||||||
| SupsCfgAdvanceECOmode | 1.3.6.1.4.1.21111.1.1.11.8 | INTEGER | RW | ||||||||||||||
scalar · INTEGER · read-write · current Setting this object to enable/disable advance ECO mode
| |||||||||||||||||
| SupsCfgGreenPowerFunction | 1.3.6.1.4.1.21111.1.1.11.9 | INTEGER | RW | ||||||||||||||
scalar · INTEGER · read-write · current Setting this object to enable/disable green power function
| |||||||||||||||||
| SupsCfgBatteryOSC | 1.3.6.1.4.1.21111.1.1.11.10 | INTEGER | RW | ||||||||||||||
scalar · INTEGER · read-write · current Setting this object to enable/disable battery open status check
| |||||||||||||||||
| SupsCfgAllowShort3times | 1.3.6.1.4.1.21111.1.1.11.11 | INTEGER | RW | ||||||||||||||
scalar · INTEGER · read-write · current Setting this object to enable/disable short 3 times
| |||||||||||||||||
| SupsCfgColdstart | 1.3.6.1.4.1.21111.1.1.11.12 | INTEGER | RW | ||||||||||||||
scalar · INTEGER · read-write · current Setting this object to cold start ups
| |||||||||||||||||
| SupsCfgBypassNotAllowed | 1.3.6.1.4.1.21111.1.1.11.13 | INTEGER | RW | ||||||||||||||
scalar · INTEGER · read-write · current Setting this object to enable/disable bypass mode
| |||||||||||||||||
| SupsCfgBatterylowprotect | 1.3.6.1.4.1.21111.1.1.11.14 | INTEGER | RW | ||||||||||||||
scalar · INTEGER · read-write · current Setting this object to enable/disable battery low protect
| |||||||||||||||||
| SupsCfgP1progoutletcontrol | 1.3.6.1.4.1.21111.1.1.11.15 | INTEGER | RW | ||||||||||||||
scalar · INTEGER · read-write · current Setting this object to enable/disable p1 programmable outlet control (battery mode)
| |||||||||||||||||
| SupsCfgP2progoutletcontrol | 1.3.6.1.4.1.21111.1.1.11.16 | INTEGER | RW | ||||||||||||||
scalar · INTEGER · read-write · current Setting this object to enable/disable p2 programmable outlet control (battery mode)
| |||||||||||||||||
| SupsCfgInverterShortClear | 1.3.6.1.4.1.21111.1.1.11.17 | INTEGER | RW | ||||||||||||||
scalar · INTEGER · read-write · current Setting this object to enable/disable Inverter short clear function
| |||||||||||||||||
| SupsCfgSitefaildetection | 1.3.6.1.4.1.21111.1.1.11.18 | INTEGER | RW | ||||||||||||||
scalar · INTEGER · read-write · current Setting this object to enable/disable site fail detection
| |||||||||||||||||
| SupsCfgBatNumInParallel | 1.3.6.1.4.1.21111.1.1.11.19 | INTEGER (1..99) | RW | ||||||||||||||
scalar · INTEGER (1..99) · read-write · current Battery numbers in parallel (battery numbers setting) | |||||||||||||||||
| SupsCfgBatNumInSeries | 1.3.6.1.4.1.21111.1.1.11.20 | INTEGER (1..20) | RW | ||||||||||||||
scalar · INTEGER (1..20) · read-write · current Battery numbers in series (battery numbers setting) | |||||||||||||||||
| SupsCfgBypassmaxvoltage | 1.3.6.1.4.1.21111.1.1.11.21 | INTEGER (1760..2760) | RW | ||||||||||||||
scalar · INTEGER (1760..2760) · read-write · current Bypass mode max voltage
| |||||||||||||||||
| SupsCfgBypassminvoltage | 1.3.6.1.4.1.21111.1.1.11.22 | INTEGER (1760..2640) | RW | ||||||||||||||
scalar · INTEGER (1760..2640) · read-write · current Bypass mode min voltage
| |||||||||||||||||
| SupsCfgBypassmaxfrequency | 1.3.6.1.4.1.21111.1.1.11.23 | INTEGER (510..700) | RW | ||||||||||||||
scalar · INTEGER (510..700) · read-write · current Bypass mode max frequency ,for 50 HZ (510..600) for 60HZ (610..700)
| |||||||||||||||||
| SupsCfgBypassminfrequency | 1.3.6.1.4.1.21111.1.1.11.24 | INTEGER (400..590) | RW | ||||||||||||||
scalar · INTEGER (400..590) · read-write · current Bypass mode min frequency, for 50HZ (400..490) for 60Hz (500..590)
| |||||||||||||||||
| SupsCfgECOmaxvoltage | 1.3.6.1.4.1.21111.1.1.11.25 | INTEGER (10..3000) | RW | ||||||||||||||
scalar · INTEGER (10..3000) · read-write · current ECO mode max voltage
| |||||||||||||||||
| SupsCfgECOminvoltage | 1.3.6.1.4.1.21111.1.1.11.26 | INTEGER (10..3000) | RW | ||||||||||||||
scalar · INTEGER (10..3000) · read-write · current ECO mode min voltage
| |||||||||||||||||
| SupsCfgFreeRunMaxFrequency | 1.3.6.1.4.1.21111.1.1.11.27 | INTEGER (400..700) | RW | ||||||||||||||
scalar · INTEGER (400..700) · read-write · current Free run mode max frequency
| |||||||||||||||||
| SupsCfgFreeRunMinFrequency | 1.3.6.1.4.1.21111.1.1.11.28 | INTEGER (400..700) | RW | ||||||||||||||
scalar · INTEGER (400..700) · read-write · current Free run mode min frequency
| |||||||||||||||||
| SupsCfgEPOStatus | 1.3.6.1.4.1.21111.1.1.11.29 | INTEGER | RO | ||||||||||||||
scalar · INTEGER · read-only · current Get EPO status,configured by mamual
| |||||||||||||||||
| SupsCfgQSK1Status | 1.3.6.1.4.1.21111.1.1.11.30 | INTEGER | RO | ||||||||||||||
scalar · INTEGER · read-only · current Get QSK 1 status
| |||||||||||||||||
| SupsCfgQSK2Status | 1.3.6.1.4.1.21111.1.1.11.31 | INTEGER | RO | ||||||||||||||
scalar · INTEGER · read-only · current Get QSK 2 status
| |||||||||||||||||
| SupsCfgQSKT1Delaytime | 1.3.6.1.4.1.21111.1.1.11.32 | INTEGER (0..999) | RO | ||||||||||||||
scalar · INTEGER (0..999) · read-only · current Get QSKT 1 time delay
| |||||||||||||||||
| SupsCfgQSKT2Delaytime | 1.3.6.1.4.1.21111.1.1.11.33 | INTEGER (0..999) | RO | ||||||||||||||
scalar · INTEGER (0..999) · read-only · current Get QSKT 2 time delay
| |||||||||||||||||
| SupsCfgConstantPhaseAngle | 1.3.6.1.4.1.21111.1.1.11.34 | INTEGER | RW | ||||||||||||||
scalar · INTEGER · read-write · current setting this object to Enable/disable Constant Phase Angle function
| |||||||||||||||||
| SupsCfgInPhaseAngle | 1.3.6.1.4.1.21111.1.1.11.35 | INTEGER | RO | ||||||||||||||
scalar · INTEGER · read-only · current Get input phase angle
| |||||||||||||||||
| SupsCfgOutPhaseAngle | 1.3.6.1.4.1.21111.1.1.11.36 | INTEGER | RW | ||||||||||||||
scalar · INTEGER · read-write · current Set output phase angle
| |||||||||||||||||
| SupsCfgLimiRunOnBatMode | 1.3.6.1.4.1.21111.1.1.11.37 | INTEGER | RW | ||||||||||||||
scalar · INTEGER · read-write · current Enable/disable limited runtime on battery mode
| |||||||||||||||||
| SupsCfgChargingCurrent | 1.3.6.1.4.1.21111.1.1.11.38 | INTEGER | RO | ||||||||||||||
scalar · INTEGER · read-only · current Set charging current to battery .
| |||||||||||||||||
| SupsCfgBatSeftCheckVolt | 1.3.6.1.4.1.21111.1.1.11.39 | INTEGER (2400..2800) | RW | ||||||||||||||
scalar · INTEGER (2400..2800) · read-write · current BatTest until battery voltage lower than <nnn>
| |||||||||||||||||
| SupsCfgOverChargVolt | 1.3.6.1.4.1.21111.1.1.11.40 | INTEGER (130..143) | RW | ||||||||||||||
scalar · INTEGER (130..143) · read-write · current set over charging voltage to per battery
| |||||||||||||||||
| SupsCfgBattUnderVolt | 1.3.6.1.4.1.21111.1.1.11.41 | INTEGER (2000..2400) | RW | ||||||||||||||
scalar · INTEGER (2000..2400) · read-write · current set battery under voltage of setting value.value is a number ranging from 200V to 240V
| |||||||||||||||||
| SupsCfgBattLowVolt | 1.3.6.1.4.1.21111.1.1.11.42 | INTEGER | RW | ||||||||||||||
scalar · INTEGER · read-write · current set battery low voltage of setting value.it is 10 to 40V high than battery under voltage. it is 10 to 40V high than battery under voltage.default 20. it means that the battery low point is battery under add 20. for example, if the battery under voltage is 210V, the battry low point voltage is 230V.
| |||||||||||||||||
| SupsCfgIn1VoltHLoss | 1.3.6.1.4.1.21111.1.1.11.43 | INTEGER | RW | ||||||||||||||
scalar · INTEGER · read-write · current set input1 voltage high loss point.
| |||||||||||||||||
| SupsCfgIn1VoltLLoss | 1.3.6.1.4.1.21111.1.1.11.44 | INTEGER | RW | ||||||||||||||
scalar · INTEGER · read-write · current set input1 voltage low loss point.
| |||||||||||||||||
| SupsCfgIn2VoltHLoss | 1.3.6.1.4.1.21111.1.1.11.45 | INTEGER | RW | ||||||||||||||
scalar · INTEGER · read-write · current set input2 voltage high loss point.
| |||||||||||||||||
| SupsCfgIn2VoltLLoss | 1.3.6.1.4.1.21111.1.1.11.46 | INTEGER | RW | ||||||||||||||
scalar · INTEGER · read-write · current set input2 voltage low loss point.
| |||||||||||||||||
| SupsCfgBatteryTurnOn | 1.3.6.1.4.1.21111.1.1.11.47 | INTEGER | RW | ||||||||||||||
scalar · INTEGER · read-write · current Enable/disable battery turn on.
| |||||||||||||||||
| NupsTraps | 1.3.6.1.4.1.21111.1.1.12 | ||||||||||||||||
| !cmpACFailure | 1.3.6.1.4.1.21111.1.1.12.0.1 | ||||||||||||||||
notification AC failure | |||||||||||||||||
| !cmpFanFailure | 1.3.6.1.4.1.21111.1.1.12.0.2 | ||||||||||||||||
notification Fan failure | |||||||||||||||||
| !cmpUPSFailure | 1.3.6.1.4.1.21111.1.1.12.0.3 | ||||||||||||||||
notification UPS failure | |||||||||||||||||
| !cmpChargerFailure | 1.3.6.1.4.1.21111.1.1.12.0.4 | ||||||||||||||||
notification Charger failure | |||||||||||||||||
| !cmpOverloadFailure | 1.3.6.1.4.1.21111.1.1.12.0.5 | ||||||||||||||||
notification Overload failure | |||||||||||||||||
| !cmpOvertempFailure | 1.3.6.1.4.1.21111.1.1.12.0.6 | ||||||||||||||||
notification Over temperature fault. | |||||||||||||||||
| !cmpInvertershortcircuited | 1.3.6.1.4.1.21111.1.1.12.0.7 | ||||||||||||||||
notification Inverter short-circuited | |||||||||||||||||
| !cmpbatteryfusebeingoc | 1.3.6.1.4.1.21111.1.1.12.0.8 | ||||||||||||||||
notification Battery fuse being open-dcircuited failure | |||||||||||||||||
| !cmpLowbattery | 1.3.6.1.4.1.21111.1.1.12.0.9 | ||||||||||||||||
notification The UPS has returned from a low battery condition. | |||||||||||||||||
| !cmpSysgotoshutdown | 1.3.6.1.4.1.21111.1.1.12.0.10 | ||||||||||||||||
notification System is going to shutdown | |||||||||||||||||
| !cmpSitefault | 1.3.6.1.4.1.21111.1.1.12.0.11 | ||||||||||||||||
notification Site fault | |||||||||||||||||
| !cmpPhasesequenceincorrect | 1.3.6.1.4.1.21111.1.1.12.0.12 | ||||||||||||||||
notification Phase sequence incorrect | |||||||||||||||||
| !cmpPhasesequenceincorrectbypass | 1.3.6.1.4.1.21111.1.1.12.0.13 | ||||||||||||||||
notification Phase sequence incorrect in bypass | |||||||||||||||||
| !cmpFanalarm | 1.3.6.1.4.1.21111.1.1.12.0.14 | ||||||||||||||||
notification Fan alarm. | |||||||||||||||||
| !cmpEPOenabled | 1.3.6.1.4.1.21111.1.1.12.0.15 | ||||||||||||||||
notification EPO enabled | |||||||||||||||||
| !cmpUnabletotrunonUPS | 1.3.6.1.4.1.21111.1.1.12.0.16 | ||||||||||||||||
notification Unalbe to turn on UPS | |||||||||||||||||
| !cmpOvertemperaturealarm | 1.3.6.1.4.1.21111.1.1.12.0.17 | ||||||||||||||||
notification Over temperature alarm | |||||||||||||||||
| !cmpInputfrequnstablebypass | 1.3.6.1.4.1.21111.1.1.12.0.18 | ||||||||||||||||
notification Input frequency unstable in bypass | |||||||||||||||||
| !cmpChargeralarm | 1.3.6.1.4.1.21111.1.1.12.0.19 | ||||||||||||||||
notification Charger alarm | |||||||||||||||||
| !cmpL1inputfusenotwork | 1.3.6.1.4.1.21111.1.1.12.0.20 | ||||||||||||||||
notification L1 input fuse not working | |||||||||||||||||
| !cmpNeutralnotConnected | 1.3.6.1.4.1.21111.1.1.12.0.21 | ||||||||||||||||
notification Neutral not connected | |||||||||||||||||
| !cmpL2inputfusenotwork | 1.3.6.1.4.1.21111.1.1.12.0.22 | ||||||||||||||||
notification L2 input fuse not working | |||||||||||||||||
| !cmpL3inputfusenotwork | 1.3.6.1.4.1.21111.1.1.12.0.23 | ||||||||||||||||
notification L3 input fuse not working | |||||||||||||||||
| !cmpPositivePFCabnormalL1 | 1.3.6.1.4.1.21111.1.1.12.0.24 | ||||||||||||||||
notification Positive PFC abnormal in L1 | |||||||||||||||||
| !cmpNegativePFCabnormalL1 | 1.3.6.1.4.1.21111.1.1.12.0.25 | ||||||||||||||||
notification Negative PFC abnormal in L1 | |||||||||||||||||
| !cmpPositivePFCabnormalL2 | 1.3.6.1.4.1.21111.1.1.12.0.26 | ||||||||||||||||
notification Positive PFC abnormal in L2 | |||||||||||||||||
| !cmpNegativePFCabnormalL2 | 1.3.6.1.4.1.21111.1.1.12.0.27 | ||||||||||||||||
notification Negative PFC abnormal in L2 | |||||||||||||||||
| !cmpPositivePFCabnormalL3 | 1.3.6.1.4.1.21111.1.1.12.0.28 | ||||||||||||||||
notification Positive PFC abnormal in L3 | |||||||||||||||||
| !cmpNegativePFCabnormalL3 | 1.3.6.1.4.1.21111.1.1.12.0.29 | ||||||||||||||||
notification Negative PFC abnormal in L3 | |||||||||||||||||
| !cmpBusvoltagenotwds | 1.3.6.1.4.1.21111.1.1.12.0.30 | ||||||||||||||||
notification Bus voltage not within default setting | |||||||||||||||||
| !cmpBusvoltageovermaxvalue | 1.3.6.1.4.1.21111.1.1.12.0.31 | ||||||||||||||||
notification Bus voltage over maxinum value | |||||||||||||||||
| !cmpBusvoltagebelowminvalue | 1.3.6.1.4.1.21111.1.1.12.0.32 | ||||||||||||||||
notification Bus voltage below mininum value | |||||||||||||||||
| !cmpBusvoltagediffoutofrange | 1.3.6.1.4.1.21111.1.1.12.0.33 | ||||||||||||||||
notification Bus voltage differences out fo acceptable range | |||||||||||||||||
| !cmpBusvoltageofsloperatetoofast | 1.3.6.1.4.1.21111.1.1.12.0.34 | ||||||||||||||||
notification Bus voltage of slope rate drops too fast | |||||||||||||||||
| !cmpOvercurrentinPFCII | 1.3.6.1.4.1.21111.1.1.12.0.35 | ||||||||||||||||
notification WARNING:Over current in PFC input inductor. | |||||||||||||||||
| !cmpInvertervoloutofrange | 1.3.6.1.4.1.21111.1.1.12.0.36 | ||||||||||||||||
notification Inverter voltage not within default setting. | |||||||||||||||||
| !cmpInvertervolovermaxvalue | 1.3.6.1.4.1.21111.1.1.12.0.37 | ||||||||||||||||
notification Inverter voltage over maximum value. | |||||||||||||||||
| !cmpInvertervolbelowminvalue | 1.3.6.1.4.1.21111.1.1.12.0.38 | ||||||||||||||||
notification Inverter voltage below minimum value. | |||||||||||||||||
| !cmpBatteryoppositelyconnected | 1.3.6.1.4.1.21111.1.1.12.0.39 | ||||||||||||||||
notification Battery oppositely connected. | |||||||||||||||||
| !cmpL2phaseshortcicuited | 1.3.6.1.4.1.21111.1.1.12.0.40 | ||||||||||||||||
notification L2Phase inverter short-cicuited. | |||||||||||||||||
| !cmpL3phaseshortcicuited | 1.3.6.1.4.1.21111.1.1.12.0.41 | ||||||||||||||||
notification L3Phase inverter short-cicuited. | |||||||||||||||||
| !cmpL1L2invertershortcicuited | 1.3.6.1.4.1.21111.1.1.12.0.42 | ||||||||||||||||
notification L1L2Inverter short-cicuited. | |||||||||||||||||
| !cmpL2L3invertershortcicuited | 1.3.6.1.4.1.21111.1.1.12.0.43 | ||||||||||||||||
notification L2L3Inverter short-cicuited. | |||||||||||||||||
| !cmpL3L1invertershortcicuited | 1.3.6.1.4.1.21111.1.1.12.0.44 | ||||||||||||||||
notification L3L1Inverter short-cicuited. | |||||||||||||||||
| !cmpL1negativepoweroutofrange | 1.3.6.1.4.1.21111.1.1.12.0.45 | ||||||||||||||||
notification L1 inverter negative powere out of acceptable range. | |||||||||||||||||
| !cmpL2negativepoweroutofrange | 1.3.6.1.4.1.21111.1.1.12.0.46 | ||||||||||||||||
notification L2 inverter negative powere out of acceptable range. | |||||||||||||||||
| !cmpL3negativepoweroutofrange | 1.3.6.1.4.1.21111.1.1.12.0.47 | ||||||||||||||||
notification L3 inverter negative powere out of acceptable range. | |||||||||||||||||
| !cmpBatterySCRshortcircuited | 1.3.6.1.4.1.21111.1.1.12.0.48 | ||||||||||||||||
notification Battery SCR short-circuited. | |||||||||||||||||
| !cmpLineSCRshortcircuited | 1.3.6.1.4.1.21111.1.1.12.0.49 | ||||||||||||||||
notification Line SCR short-circuited. | |||||||||||||||||
| !cmpInverterrelayopenfault | 1.3.6.1.4.1.21111.1.1.12.0.50 | ||||||||||||||||
notification Inverter relay open fault. | |||||||||||||||||
| !cmpInverterrelayshortcircuited | 1.3.6.1.4.1.21111.1.1.12.0.51 | ||||||||||||||||
notification Inverter relay short-circuited. | |||||||||||||||||
| !cmpInoutwiresoppositelyconnected | 1.3.6.1.4.1.21111.1.1.12.0.52 | ||||||||||||||||
notification Input and output wires oppositely connected. | |||||||||||||||||
| !cmpabnormalcanbuscommunication | 1.3.6.1.4.1.21111.1.1.12.0.53 | ||||||||||||||||
notification Abnormal in CAN-bus communication. | |||||||||||||||||
| !cmpcommfailurebcupsboard | 1.3.6.1.4.1.21111.1.1.12.0.54 | ||||||||||||||||
notification Communication failure between cpus in control board.Or DSP and MCU communication error | |||||||||||||||||
| !cmpabnormalsyncsignalcircuit | 1.3.6.1.4.1.21111.1.1.12.0.55 | ||||||||||||||||
notification Abnomal in synchronous signal circuit. | |||||||||||||||||
| !cmpabnormalsyncpulsesignalcircuit | 1.3.6.1.4.1.21111.1.1.12.0.56 | ||||||||||||||||
notification Abnomal in synchronous pulse signal circuit. | |||||||||||||||||
| !cmpcurrent3punbalancedetected | 1.3.6.1.4.1.21111.1.1.12.0.57 | ||||||||||||||||
notification Warning for a three-phase input current unbalance detected. | |||||||||||||||||
| !cmpbatteryselftestfailure | 1.3.6.1.4.1.21111.1.1.12.0.58 | ||||||||||||||||
notification Battery self-test failure. | |||||||||||||||||
| !cmpintercurrentunbalance | 1.3.6.1.4.1.21111.1.1.12.0.59 | ||||||||||||||||
notification Inverter inter-current unbalance. | |||||||||||||||||
| !cmpbatterydisconnected | 1.3.6.1.4.1.21111.1.1.12.0.60 | ||||||||||||||||
notification Battery disconnected. | |||||||||||||||||
| !cmpabnormalhostsignalcircuit | 1.3.6.1.4.1.21111.1.1.12.0.61 | ||||||||||||||||
notification Abnormal in host signal circuit. | |||||||||||||||||
| !cmpbatteryovercharged | 1.3.6.1.4.1.21111.1.1.12.0.62 | ||||||||||||||||
notification Bettery overcharged. | |||||||||||||||||
| !cmpbatteryvoltoohigh | 1.3.6.1.4.1.21111.1.1.12.0.63 | ||||||||||||||||
notification Bettery voltage is too high. | |||||||||||||||||
| !cmpbatteryvoltoolow | 1.3.6.1.4.1.21111.1.1.12.0.64 | ||||||||||||||||
notification Bettery voltage is too low. | |||||||||||||||||
| !cmpfemaleconnectornotconnwell | 1.3.6.1.4.1.21111.1.1.12.0.65 | ||||||||||||||||
notification Female connector of parallel cable not connected well. | |||||||||||||||||
| !cmpmaleconnectornotconnwell | 1.3.6.1.4.1.21111.1.1.12.0.66 | ||||||||||||||||
notification Male connector of parallel cable not connected well. | |||||||||||||||||
| !cmplockingbypassA3COW30M | 1.3.6.1.4.1.21111.1.1.12.0.67 | ||||||||||||||||
notification Locking inbypass mode after 3 consecutive overloads within 30 minutes | |||||||||||||||||
| !cmpparallelcabledisconnected | 1.3.6.1.4.1.21111.1.1.12.0.68 | ||||||||||||||||
notification Parallel cable disconnected | |||||||||||||||||
| !cmpsyncpulsecircuitfault | 1.3.6.1.4.1.21111.1.1.12.0.69 | ||||||||||||||||
notification Synchronous pulse signal circuit fault | |||||||||||||||||
| !cmpsyncsignalcircuitfalt | 1.3.6.1.4.1.21111.1.1.12.0.70 | ||||||||||||||||
notification Synchronous signal circuit fault | |||||||||||||||||
| !cmphostsignalcircuitfault | 1.3.6.1.4.1.21111.1.1.12.0.71 | ||||||||||||||||
notification Host signal circuit fault | |||||||||||||||||
| !cmpcanbuscommunicationfault | 1.3.6.1.4.1.21111.1.1.12.0.72 | ||||||||||||||||
notification Can-bus communication fault | |||||||||||||||||
| !cmplowlosspointforvolinACmode | 1.3.6.1.4.1.21111.1.1.12.0.73 | ||||||||||||||||
notification Low loss point for voltage in ac mode not consistent in parallel systems | |||||||||||||||||
| !cmphighlosspointforvolinACmode | 1.3.6.1.4.1.21111.1.1.12.0.74 | ||||||||||||||||
notification High loss point for voltage in ac mode not consistent in parallel systems | |||||||||||||||||
| !cmplowlosspointforfreqinACmode | 1.3.6.1.4.1.21111.1.1.12.0.75 | ||||||||||||||||
notification Low loss point for frequency in ac mode not consistent in parallel systems | |||||||||||||||||
| !cmphighlosspointforfreqinACmode | 1.3.6.1.4.1.21111.1.1.12.0.76 | ||||||||||||||||
notification High loss point for frequency in ac mode not consistent in parallel systems | |||||||||||||||||
| !cmplowlosspointforvolinbypassmode | 1.3.6.1.4.1.21111.1.1.12.0.77 | ||||||||||||||||
notification Low loss point for voltage in bypass mode not consistent in parallel systems | |||||||||||||||||
| !cmphighlosspointforvolinbypassmode | 1.3.6.1.4.1.21111.1.1.12.0.78 | ||||||||||||||||
notification High loss point for voltage in bypass mode not consistent in parallel systems | |||||||||||||||||
| !cmplowlosspointforfreqinbypassmode | 1.3.6.1.4.1.21111.1.1.12.0.79 | ||||||||||||||||
notification Low loss point for frequency in bypass mode not consistent in parallel systems | |||||||||||||||||
| !cmphighlosspointforfreqinbypassmode | 1.3.6.1.4.1.21111.1.1.12.0.80 | ||||||||||||||||
notification High loss point for frequency in bypass mode not consistent in parallel systems | |||||||||||||||||
| !cmploadunbalanced | 1.3.6.1.4.1.21111.1.1.12.0.81 | ||||||||||||||||
notification Load unbalanced | |||||||||||||||||
| !cmpoverloadalarm | 1.3.6.1.4.1.21111.1.1.12.0.82 | ||||||||||||||||
notification Overload alarm | |||||||||||||||||
| !cmpparallelnotconnectedwell | 1.3.6.1.4.1.21111.1.1.12.0.83 | ||||||||||||||||
notification Parallel cable not connected well | |||||||||||||||||
| !cmpcommunicationlost | 1.3.6.1.4.1.21111.1.1.12.0.84 | ||||||||||||||||
notification Communication lost | |||||||||||||||||
| !cmpbatteryconnnotsonsistent | 1.3.6.1.4.1.21111.1.1.12.0.85 | ||||||||||||||||
notification Battery connection not consistent in parallel systems | |||||||||||||||||
| !cmpconverternotconsisstent | 1.3.6.1.4.1.21111.1.1.12.0.86 | ||||||||||||||||
notification Converter setting not consistent in parallel systems | |||||||||||||||||
| !cmpbypassnotallownotconsistent | 1.3.6.1.4.1.21111.1.1.12.0.87 | ||||||||||||||||
notification Bypass not allowed setting not consistent in parallel systems | |||||||||||||||||
| !cmpACconnnotconsistent | 1.3.6.1.4.1.21111.1.1.12.0.88 | ||||||||||||||||
notification AC connection not consistent in parallel systems | |||||||||||||||||
| !cmpinput3pcurrentunbalance | 1.3.6.1.4.1.21111.1.1.12.0.89 | ||||||||||||||||
notification Warning for three-phase ac input current unbalance | |||||||||||||||||
| !cmpbypassconnnotconsistent | 1.3.6.1.4.1.21111.1.1.12.0.90 | ||||||||||||||||
notification Bypass connection not consistent in parallel systems | |||||||||||||||||
| !cmpbatteryprotectionnotconsistent | 1.3.6.1.4.1.21111.1.1.12.0.91 | ||||||||||||||||
notification Battery protection setting not consistent in parallel systems | |||||||||||||||||
| !cmpbatterydetectionnotconsistent | 1.3.6.1.4.1.21111.1.1.12.0.92 | ||||||||||||||||
notification Battery detection setting not consistent in parallel systems | |||||||||||||||||
| !cmpupsmodeltypesnotconsistent | 1.3.6.1.4.1.21111.1.1.12.0.93 | ||||||||||||||||
notification UPS model types not consistent in parallel systems | |||||||||||||||||
| !cmpbypassnotconsistent | 1.3.6.1.4.1.21111.1.1.12.0.94 | ||||||||||||||||
notification Bypass setting not consistent in parallel systems | |||||||||||||||||
| !cmpcapacitynotconsistent | 1.3.6.1.4.1.21111.1.1.12.0.95 | ||||||||||||||||
notification Capacity of upss not consistent in parallel systems | |||||||||||||||||
| !cmpautorestartnotconsistent | 1.3.6.1.4.1.21111.1.1.12.0.96 | ||||||||||||||||
notification Auto restart setting not consistent in parallel systems | |||||||||||||||||
| !cmpBatteryReplace | 1.3.6.1.4.1.21111.1.1.12.0.97 | ||||||||||||||||
notification Battery need to be replace | |||||||||||||||||
| !cmpACNormal | 1.3.6.1.4.1.21111.1.1.12.0.100 | ||||||||||||||||
notification AC normal | |||||||||||||||||
| !cmpOutputBadAlarm | 1.3.6.1.4.1.21111.1.1.12.0.103 | ||||||||||||||||
notification Output bad alarm | |||||||||||||||||
| !cmpBypassBadAlarm | 1.3.6.1.4.1.21111.1.1.12.0.104 | ||||||||||||||||
notification Bypass bad alarm | |||||||||||||||||
| !cmpOutputOffAlarm | 1.3.6.1.4.1.21111.1.1.12.0.105 | ||||||||||||||||
notification Output off alarm | |||||||||||||||||
| !cmpUPSShutAlarm | 1.3.6.1.4.1.21111.1.1.12.0.106 | ||||||||||||||||
notification UPS shutdown alarm | |||||||||||||||||
| !cmpSystemOffAlarm | 1.3.6.1.4.1.21111.1.1.12.0.107 | ||||||||||||||||
notification System off alarm | |||||||||||||||||
| !cmpFuseFailureAlarm | 1.3.6.1.4.1.21111.1.1.12.0.108 | ||||||||||||||||
notification Fuse failure alarm | |||||||||||||||||
| !cmpGenFailureAlarm | 1.3.6.1.4.1.21111.1.1.12.0.109 | ||||||||||||||||
notification General failure alarm | |||||||||||||||||
| !cmpAwaitPowerAlarm | 1.3.6.1.4.1.21111.1.1.12.0.110 | ||||||||||||||||
notification Awaiting power alarm | |||||||||||||||||
| !cmpShutPendingAlarm | 1.3.6.1.4.1.21111.1.1.12.0.111 | ||||||||||||||||
notification Shutdown pending alarm | |||||||||||||||||
| !cmpBatDepleted | 1.3.6.1.4.1.21111.1.1.12.0.112 | ||||||||||||||||
notification Battery depleted | |||||||||||||||||
| !cmpUnknowStatus | 1.3.6.1.4.1.21111.1.1.12.0.113 | ||||||||||||||||
notification Battery unknow status | |||||||||||||||||
| !cmpOutputOn | 1.3.6.1.4.1.21111.1.1.12.0.114 | ||||||||||||||||
notification Output on | |||||||||||||||||
| !cmpTurntobypass | 1.3.6.1.4.1.21111.1.1.12.0.115 | ||||||||||||||||
notification Ups turn to bypass mode | |||||||||||||||||
| !cmpTurntobattery | 1.3.6.1.4.1.21111.1.1.12.0.116 | ||||||||||||||||
notification Ups turn to battery mode | |||||||||||||||||
| !cmpOutBooster | 1.3.6.1.4.1.21111.1.1.12.0.117 | ||||||||||||||||
notification Turn to booster | |||||||||||||||||
| !cmpOutReducer | 1.3.6.1.4.1.21111.1.1.12.0.118 | ||||||||||||||||
notification Turn to reducer | |||||||||||||||||
| !cmpOutBattest | 1.3.6.1.4.1.21111.1.1.12.0.119 | ||||||||||||||||
notification Turn to battery test mode | |||||||||||||||||
| !cmpOtherSource | 1.3.6.1.4.1.21111.1.1.12.0.120 | ||||||||||||||||
notification Other source | |||||||||||||||||
| !cmpBatfailure | 1.3.6.1.4.1.21111.1.1.12.0.121 | ||||||||||||||||
notification Battery failure | |||||||||||||||||
| !cmpBatTestDonePassed | 1.3.6.1.4.1.21111.1.1.12.0.122 | ||||||||||||||||
notification Battery test passed | |||||||||||||||||
| !cmpBatTestDoneWarning | 1.3.6.1.4.1.21111.1.1.12.0.123 | ||||||||||||||||
notification Battery test done warning | |||||||||||||||||
| !cmpBatTestDoneAborted | 1.3.6.1.4.1.21111.1.1.12.0.124 | ||||||||||||||||
notification Battery test done Aborted | |||||||||||||||||
| !cmpBatteryNormal | 1.3.6.1.4.1.21111.1.1.12.0.125 | ||||||||||||||||
notification Battery normal | |||||||||||||||||
| !cmpBatteryDischarging | 1.3.6.1.4.1.21111.1.1.12.0.126 | ||||||||||||||||
notification Battery Discharging | |||||||||||||||||
| !cmpP1cutoffprealarm | 1.3.6.1.4.1.21111.1.1.12.0.127 | ||||||||||||||||
notification P1 cut off pre-alarm | |||||||||||||||||
| !cmpInputPhaseError | 1.3.6.1.4.1.21111.1.1.12.0.128 | ||||||||||||||||
notification Warning for input phase error for LV 6-10K UPS | |||||||||||||||||
| !cmpMaintainSwitchOpenalarm | 1.3.6.1.4.1.21111.1.1.12.0.129 | ||||||||||||||||
notification Warning for maintain switch open | |||||||||||||||||
| !cmpEMDChAbnormal1 | 1.3.6.1.4.1.21111.1.1.12.0.130 | ||||||||||||||||
notification EMD Channels 1 Abnormal | |||||||||||||||||
| !cmpEMDChAbnormal2 | 1.3.6.1.4.1.21111.1.1.12.0.131 | ||||||||||||||||
notification EMD Channels 2 Abnormal | |||||||||||||||||
| !cmpEMDChAbnormal3 | 1.3.6.1.4.1.21111.1.1.12.0.132 | ||||||||||||||||
notification EMD Channels 3 Abnormal | |||||||||||||||||
| !cmpEMDChAbnormal4 | 1.3.6.1.4.1.21111.1.1.12.0.133 | ||||||||||||||||
notification EMD Channels 4 Abnormal | |||||||||||||||||
| !cmpEMDChAbnormal5 | 1.3.6.1.4.1.21111.1.1.12.0.134 | ||||||||||||||||
notification EMD Channels 5 Abnormal: smoke alarm | |||||||||||||||||
| !cmpEMDChAbnormal6 | 1.3.6.1.4.1.21111.1.1.12.0.135 | ||||||||||||||||
notification EMD Channels 6 Abnormal | |||||||||||||||||
| !cmpEMDChAbnormal7 | 1.3.6.1.4.1.21111.1.1.12.0.136 | ||||||||||||||||
notification EMD Channels 7 Abnormal | |||||||||||||||||
| !cmpEMDChAbnormal8 | 1.3.6.1.4.1.21111.1.1.12.0.137 | ||||||||||||||||
notification EMD Channels 8 Abnormal | |||||||||||||||||
| Strapleafnodev103 | 1.3.6.1.4.1.21111.1.1.12.998 | DisplayString (SIZE (16)) | NA | ||||||||||||||
scalar · DisplayString (SIZE (16)) · not-accessible · current The share trap-node for send all traps,snmpcard V1-03 and later use this trap-node char trap[16]; trap[0]: trap[0]=1,fault trap ; trap[0]=0,warn trap | |||||||||||||||||
| Strapleafnodev1v2 | 1.3.6.1.4.1.21111.1.1.12.999 | INTEGER (0..255) | NA | ||||||||||||||
scalar · INTEGER (0..255) · not-accessible · current The share trap-node for send all traps | |||||||||||||||||
| Nextend | 1.3.6.1.4.1.21111.1.1.13 | ||||||||||||||||
| SextendWorkTemperature | 1.3.6.1.4.1.21111.1.1.13.1 | INTEGER (-2200..2200) | RO | ||||||||||||||
scalar · INTEGER (-2200..2200) · read-only · current The temperature of work environment
| |||||||||||||||||
| SextendWorkhumidity | 1.3.6.1.4.1.21111.1.1.13.2 | INTEGER (0..100) | RO | ||||||||||||||
scalar · INTEGER (0..100) · read-only · current The humidity of work environment
| |||||||||||||||||
| SextendSmokeScope | 1.3.6.1.4.1.21111.1.1.13.3 | INTEGER (0..1000000) | RO | ||||||||||||||
scalar · INTEGER (0..1000000) · read-only · current The smokeScope of work environment
| |||||||||||||||||
| SextendEMDAlarm1 | 1.3.6.1.4.1.21111.1.1.13.4 | INTEGER | RO | ||||||||||||||
scalar · INTEGER · read-only · current Environment detector alarm 1
| |||||||||||||||||
| SextendEMDAlarm2 | 1.3.6.1.4.1.21111.1.1.13.5 | INTEGER | RO | ||||||||||||||
scalar · INTEGER · read-only · current Environment detector alarm 2
| |||||||||||||||||
| SextendEMDAlarm3 | 1.3.6.1.4.1.21111.1.1.13.6 | INTEGER | RO | ||||||||||||||
scalar · INTEGER · read-only · current Environment detector alarm 3
| |||||||||||||||||
| SextendEMDAlarm4 | 1.3.6.1.4.1.21111.1.1.13.7 | INTEGER | RO | ||||||||||||||
scalar · INTEGER · read-only · current Environment detector alarm 4
| |||||||||||||||||
| Ninverter | 1.3.6.1.4.1.21111.1.2 | ||||||||||||||||
| NsolarIdent | 1.3.6.1.4.1.21111.1.2.1 | ||||||||||||||||
| NsolarRating | 1.3.6.1.4.1.21111.1.2.2 | ||||||||||||||||
| NsolarBattery | 1.3.6.1.4.1.21111.1.2.3 | ||||||||||||||||
| NsolarGrid | 1.3.6.1.4.1.21111.1.2.4 | ||||||||||||||||
| NsolarACOutput | 1.3.6.1.4.1.21111.1.2.5 | ||||||||||||||||
| NsolarPV | 1.3.6.1.4.1.21111.1.2.6 | ||||||||||||||||
| NsolarEnergy | 1.3.6.1.4.1.21111.1.2.7 | ||||||||||||||||
| NsolarTest | 1.3.6.1.4.1.21111.1.2.8 | ||||||||||||||||
| NsolarDefValue | 1.3.6.1.4.1.21111.1.2.9 | ||||||||||||||||
| NsolarFaultInfo | 1.3.6.1.4.1.21111.1.2.10 | ||||||||||||||||
| NsolarControl | 1.3.6.1.4.1.21111.1.2.11 | ||||||||||||||||
| NsolarAgentConfig | 1.3.6.1.4.1.21111.1.2.12 | ||||||||||||||||
| NsolarCommConfig | 1.3.6.1.4.1.21111.1.2.13 | ||||||||||||||||
| NsolarConfig | 1.3.6.1.4.1.21111.1.2.14 | ||||||||||||||||
| NsolarTraps | 1.3.6.1.4.1.21111.1.2.15 | ||||||||||||||||
| NsolarExtend | 1.3.6.1.4.1.21111.1.2.16 | ||||||||||||||||
| Ncharger | 1.3.6.1.4.1.21111.1.3 | ||||||||||||||||
| NATS | 1.3.6.1.4.1.21111.1.4 | ||||||||||||||||
| NATSIdent | 1.3.6.1.4.1.21111.1.4.1 | ||||||||||||||||
| NATSRating | 1.3.6.1.4.1.21111.1.4.2 | ||||||||||||||||
| NATSInformation | 1.3.6.1.4.1.21111.1.4.3 | ||||||||||||||||
| NATSControl | 1.3.6.1.4.1.21111.1.4.4 | ||||||||||||||||
| NATSAgentConfig | 1.3.6.1.4.1.21111.1.4.5 | ||||||||||||||||
| NATSCommConfig | 1.3.6.1.4.1.21111.1.4.6 | ||||||||||||||||
| NATSConfig | 1.3.6.1.4.1.21111.1.4.7 | ||||||||||||||||
| NATSTraps | 1.3.6.1.4.1.21111.1.4.8 | ||||||||||||||||
| NATSExtend | 1.3.6.1.4.1.21111.1.4.9 | ||||||||||||||||
Traps / Notifications
- cmpACFailure
1.3.6.1.4.1.21111.1.1.12.0.1 - cmpACNormal
1.3.6.1.4.1.21111.1.1.12.0.100 - cmpACconnnotconsistent
1.3.6.1.4.1.21111.1.1.12.0.88 - cmpAwaitPowerAlarm
1.3.6.1.4.1.21111.1.1.12.0.110 - cmpBatDepleted
1.3.6.1.4.1.21111.1.1.12.0.112 - cmpBatTestDoneAborted
1.3.6.1.4.1.21111.1.1.12.0.124 - cmpBatTestDonePassed
1.3.6.1.4.1.21111.1.1.12.0.122 - cmpBatTestDoneWarning
1.3.6.1.4.1.21111.1.1.12.0.123 - cmpBatfailure
1.3.6.1.4.1.21111.1.1.12.0.121 - cmpBatteryDischarging
1.3.6.1.4.1.21111.1.1.12.0.126 - cmpBatteryNormal
1.3.6.1.4.1.21111.1.1.12.0.125 - cmpBatteryReplace
1.3.6.1.4.1.21111.1.1.12.0.97 - cmpBatterySCRshortcircuited
1.3.6.1.4.1.21111.1.1.12.0.48 - cmpBatteryoppositelyconnected
1.3.6.1.4.1.21111.1.1.12.0.39 - cmpBusvoltagebelowminvalue
1.3.6.1.4.1.21111.1.1.12.0.32 - cmpBusvoltagediffoutofrange
1.3.6.1.4.1.21111.1.1.12.0.33 - cmpBusvoltagenotwds
1.3.6.1.4.1.21111.1.1.12.0.30 - cmpBusvoltageofsloperatetoofast
1.3.6.1.4.1.21111.1.1.12.0.34 - cmpBusvoltageovermaxvalue
1.3.6.1.4.1.21111.1.1.12.0.31 - cmpBypassBadAlarm
1.3.6.1.4.1.21111.1.1.12.0.104 - cmpChargerFailure
1.3.6.1.4.1.21111.1.1.12.0.4 - cmpChargeralarm
1.3.6.1.4.1.21111.1.1.12.0.19 - cmpEMDChAbnormal1
1.3.6.1.4.1.21111.1.1.12.0.130 - cmpEMDChAbnormal2
1.3.6.1.4.1.21111.1.1.12.0.131 - cmpEMDChAbnormal3
1.3.6.1.4.1.21111.1.1.12.0.132 - cmpEMDChAbnormal4
1.3.6.1.4.1.21111.1.1.12.0.133 - cmpEMDChAbnormal5
1.3.6.1.4.1.21111.1.1.12.0.134 - cmpEMDChAbnormal6
1.3.6.1.4.1.21111.1.1.12.0.135 - cmpEMDChAbnormal7
1.3.6.1.4.1.21111.1.1.12.0.136 - cmpEMDChAbnormal8
1.3.6.1.4.1.21111.1.1.12.0.137 - cmpEPOenabled
1.3.6.1.4.1.21111.1.1.12.0.15 - cmpFanFailure
1.3.6.1.4.1.21111.1.1.12.0.2 - cmpFanalarm
1.3.6.1.4.1.21111.1.1.12.0.14 - cmpFuseFailureAlarm
1.3.6.1.4.1.21111.1.1.12.0.108 - cmpGenFailureAlarm
1.3.6.1.4.1.21111.1.1.12.0.109 - cmpInoutwiresoppositelyconnected
1.3.6.1.4.1.21111.1.1.12.0.52 - cmpInputPhaseError
1.3.6.1.4.1.21111.1.1.12.0.128 - cmpInputfrequnstablebypass
1.3.6.1.4.1.21111.1.1.12.0.18 - cmpInverterrelayopenfault
1.3.6.1.4.1.21111.1.1.12.0.50 - cmpInverterrelayshortcircuited
1.3.6.1.4.1.21111.1.1.12.0.51 - cmpInvertershortcircuited
1.3.6.1.4.1.21111.1.1.12.0.7 - cmpInvertervolbelowminvalue
1.3.6.1.4.1.21111.1.1.12.0.38 - cmpInvertervoloutofrange
1.3.6.1.4.1.21111.1.1.12.0.36 - cmpInvertervolovermaxvalue
1.3.6.1.4.1.21111.1.1.12.0.37 - cmpL1L2invertershortcicuited
1.3.6.1.4.1.21111.1.1.12.0.42 - cmpL1inputfusenotwork
1.3.6.1.4.1.21111.1.1.12.0.20 - cmpL1negativepoweroutofrange
1.3.6.1.4.1.21111.1.1.12.0.45 - cmpL2L3invertershortcicuited
1.3.6.1.4.1.21111.1.1.12.0.43 - cmpL2inputfusenotwork
1.3.6.1.4.1.21111.1.1.12.0.22 - cmpL2negativepoweroutofrange
1.3.6.1.4.1.21111.1.1.12.0.46 - cmpL2phaseshortcicuited
1.3.6.1.4.1.21111.1.1.12.0.40 - cmpL3L1invertershortcicuited
1.3.6.1.4.1.21111.1.1.12.0.44 - cmpL3inputfusenotwork
1.3.6.1.4.1.21111.1.1.12.0.23 - cmpL3negativepoweroutofrange
1.3.6.1.4.1.21111.1.1.12.0.47 - cmpL3phaseshortcicuited
1.3.6.1.4.1.21111.1.1.12.0.41 - cmpLineSCRshortcircuited
1.3.6.1.4.1.21111.1.1.12.0.49 - cmpLowbattery
1.3.6.1.4.1.21111.1.1.12.0.9 - cmpMaintainSwitchOpenalarm
1.3.6.1.4.1.21111.1.1.12.0.129 - cmpNegativePFCabnormalL1
1.3.6.1.4.1.21111.1.1.12.0.25 - cmpNegativePFCabnormalL2
1.3.6.1.4.1.21111.1.1.12.0.27 - cmpNegativePFCabnormalL3
1.3.6.1.4.1.21111.1.1.12.0.29 - cmpNeutralnotConnected
1.3.6.1.4.1.21111.1.1.12.0.21 - cmpOtherSource
1.3.6.1.4.1.21111.1.1.12.0.120 - cmpOutBattest
1.3.6.1.4.1.21111.1.1.12.0.119 - cmpOutBooster
1.3.6.1.4.1.21111.1.1.12.0.117 - cmpOutReducer
1.3.6.1.4.1.21111.1.1.12.0.118 - cmpOutputBadAlarm
1.3.6.1.4.1.21111.1.1.12.0.103 - cmpOutputOffAlarm
1.3.6.1.4.1.21111.1.1.12.0.105 - cmpOutputOn
1.3.6.1.4.1.21111.1.1.12.0.114 - cmpOvercurrentinPFCII
1.3.6.1.4.1.21111.1.1.12.0.35 - cmpOverloadFailure
1.3.6.1.4.1.21111.1.1.12.0.5 - cmpOvertempFailure
1.3.6.1.4.1.21111.1.1.12.0.6 - cmpOvertemperaturealarm
1.3.6.1.4.1.21111.1.1.12.0.17 - cmpP1cutoffprealarm
1.3.6.1.4.1.21111.1.1.12.0.127 - cmpPhasesequenceincorrect
1.3.6.1.4.1.21111.1.1.12.0.12 - cmpPhasesequenceincorrectbypass
1.3.6.1.4.1.21111.1.1.12.0.13 - cmpPositivePFCabnormalL1
1.3.6.1.4.1.21111.1.1.12.0.24 - cmpPositivePFCabnormalL2
1.3.6.1.4.1.21111.1.1.12.0.26 - cmpPositivePFCabnormalL3
1.3.6.1.4.1.21111.1.1.12.0.28 - cmpShutPendingAlarm
1.3.6.1.4.1.21111.1.1.12.0.111 - cmpSitefault
1.3.6.1.4.1.21111.1.1.12.0.11 - cmpSysgotoshutdown
1.3.6.1.4.1.21111.1.1.12.0.10 - cmpSystemOffAlarm
1.3.6.1.4.1.21111.1.1.12.0.107 - cmpTurntobattery
1.3.6.1.4.1.21111.1.1.12.0.116 - cmpTurntobypass
1.3.6.1.4.1.21111.1.1.12.0.115 - cmpUPSFailure
1.3.6.1.4.1.21111.1.1.12.0.3 - cmpUPSShutAlarm
1.3.6.1.4.1.21111.1.1.12.0.106 - cmpUnabletotrunonUPS
1.3.6.1.4.1.21111.1.1.12.0.16 - cmpUnknowStatus
1.3.6.1.4.1.21111.1.1.12.0.113 - cmpabnormalcanbuscommunication
1.3.6.1.4.1.21111.1.1.12.0.53 - cmpabnormalhostsignalcircuit
1.3.6.1.4.1.21111.1.1.12.0.61 - cmpabnormalsyncpulsesignalcircuit
1.3.6.1.4.1.21111.1.1.12.0.56 - cmpabnormalsyncsignalcircuit
1.3.6.1.4.1.21111.1.1.12.0.55 - cmpautorestartnotconsistent
1.3.6.1.4.1.21111.1.1.12.0.96 - cmpbatteryconnnotsonsistent
1.3.6.1.4.1.21111.1.1.12.0.85 - cmpbatterydetectionnotconsistent
1.3.6.1.4.1.21111.1.1.12.0.92 - cmpbatterydisconnected
1.3.6.1.4.1.21111.1.1.12.0.60 - cmpbatteryfusebeingoc
1.3.6.1.4.1.21111.1.1.12.0.8 - cmpbatteryovercharged
1.3.6.1.4.1.21111.1.1.12.0.62 - cmpbatteryprotectionnotconsistent
1.3.6.1.4.1.21111.1.1.12.0.91 - cmpbatteryselftestfailure
1.3.6.1.4.1.21111.1.1.12.0.58 - cmpbatteryvoltoohigh
1.3.6.1.4.1.21111.1.1.12.0.63 - cmpbatteryvoltoolow
1.3.6.1.4.1.21111.1.1.12.0.64 - cmpbypassconnnotconsistent
1.3.6.1.4.1.21111.1.1.12.0.90 - cmpbypassnotallownotconsistent
1.3.6.1.4.1.21111.1.1.12.0.87 - cmpbypassnotconsistent
1.3.6.1.4.1.21111.1.1.12.0.94 - cmpcanbuscommunicationfault
1.3.6.1.4.1.21111.1.1.12.0.72 - cmpcapacitynotconsistent
1.3.6.1.4.1.21111.1.1.12.0.95 - cmpcommfailurebcupsboard
1.3.6.1.4.1.21111.1.1.12.0.54 - cmpcommunicationlost
1.3.6.1.4.1.21111.1.1.12.0.84 - cmpconverternotconsisstent
1.3.6.1.4.1.21111.1.1.12.0.86 - cmpcurrent3punbalancedetected
1.3.6.1.4.1.21111.1.1.12.0.57 - cmpfemaleconnectornotconnwell
1.3.6.1.4.1.21111.1.1.12.0.65 - cmphighlosspointforfreqinACmode
1.3.6.1.4.1.21111.1.1.12.0.76 - cmphighlosspointforfreqinbypassmode
1.3.6.1.4.1.21111.1.1.12.0.80 - cmphighlosspointforvolinACmode
1.3.6.1.4.1.21111.1.1.12.0.74 - cmphighlosspointforvolinbypassmode
1.3.6.1.4.1.21111.1.1.12.0.78 - cmphostsignalcircuitfault
1.3.6.1.4.1.21111.1.1.12.0.71 - cmpinput3pcurrentunbalance
1.3.6.1.4.1.21111.1.1.12.0.89 - cmpintercurrentunbalance
1.3.6.1.4.1.21111.1.1.12.0.59 - cmploadunbalanced
1.3.6.1.4.1.21111.1.1.12.0.81 - cmplockingbypassA3COW30M
1.3.6.1.4.1.21111.1.1.12.0.67 - cmplowlosspointforfreqinACmode
1.3.6.1.4.1.21111.1.1.12.0.75 - cmplowlosspointforfreqinbypassmode
1.3.6.1.4.1.21111.1.1.12.0.79 - cmplowlosspointforvolinACmode
1.3.6.1.4.1.21111.1.1.12.0.73 - cmplowlosspointforvolinbypassmode
1.3.6.1.4.1.21111.1.1.12.0.77 - cmpmaleconnectornotconnwell
1.3.6.1.4.1.21111.1.1.12.0.66 - cmpoverloadalarm
1.3.6.1.4.1.21111.1.1.12.0.82 - cmpparallelcabledisconnected
1.3.6.1.4.1.21111.1.1.12.0.68 - cmpparallelnotconnectedwell
1.3.6.1.4.1.21111.1.1.12.0.83 - cmpsyncpulsecircuitfault
1.3.6.1.4.1.21111.1.1.12.0.69 - cmpsyncsignalcircuitfalt
1.3.6.1.4.1.21111.1.1.12.0.70 - cmpupsmodeltypesnotconsistent
1.3.6.1.4.1.21111.1.1.12.0.93