LIEBERT-GP-POWER-MIB
Vertiv (formerly 'Emerson Computer Power')The MIB module used to register Liebert POWER related SNMP OIDs. Copyright 2000-2008 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification.
snmptranslate -m LIEBERT-GP-POWER-MIB -Tpsnmpwalk -v2c -c <community> -m LIEBERT-GP-POWER-MIB <host> 1.3.6.1.4.1.476.1.42.1.6.1Imports
| LIEBERT-GP-REGISTRATION-MIB | lgpPower, liebertPowerModuleReg |
|---|---|
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
| SNMPv2-SMI | Bits, Integer32, IpAddress, MODULE-IDENTITY, MibIdentifier, OBJECT-IDENTITY, OBJECT-TYPE, TimeTicks, Unsigned32, iso |
| SNMPv2-TC | DisplayString, PhysAddress, TEXTUAL-CONVENTION |
OID tree
| Name | OID | Type | Access | Status | Example | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| IliebertGlobalProductsPowerModule | 1.3.6.1.4.1.476.1.42.1.6.1 | ||||||||||||||||||||
identity The MIB module used to register Liebert POWER related SNMP OIDs. Copyright 2000-2008 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification. | |||||||||||||||||||||
| NlgpPwrBattery | 1.3.6.1.4.1.476.1.42.3.5.1 | ||||||||||||||||||||
node · current This sub-tree is used to register Liebert Power Battery object identifiers. | |||||||||||||||||||||
| SlgpPwrNumberInstalledBatteryModules | 1.3.6.1.4.1.476.1.42.3.5.1.1 | Integer32 | RO | ||||||||||||||||||
scalar · Integer32 · read-only · current The number of battery modules installed in the device. | |||||||||||||||||||||
| SlgpPwrNumberFailedBatteryModules | 1.3.6.1.4.1.476.1.42.3.5.1.2 | Integer32 | RO | ||||||||||||||||||
scalar · Integer32 · read-only · current The number of battery modules in the device that have failed. | |||||||||||||||||||||
| SlgpPwrNumberRedundantBatteryModules | 1.3.6.1.4.1.476.1.42.3.5.1.3 | Integer32 | RO | ||||||||||||||||||
scalar · Integer32 · read-only · current The number of redundant battery modules in the device. | |||||||||||||||||||||
| SlgpPwrNumberActiveBatteryModules | 1.3.6.1.4.1.476.1.42.3.5.1.4 | Integer32 | RO | ||||||||||||||||||
scalar · Integer32 · read-only · current The number of active battery modules in the device. | |||||||||||||||||||||
| SlgpPwrConfigLowBatteryWarningTime | 1.3.6.1.4.1.476.1.42.3.5.1.5 | Integer32 | RW | 2 | |||||||||||||||||
scalar · Integer32 · read-write · current The value of the device's estimated minutes of remaining battery at which a lgpEventLowBatteryWarning notification will be sent.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SlgpPwrNumberBatteryModuleWarnings | 1.3.6.1.4.1.476.1.42.3.5.1.6 | Integer32 | RO | ||||||||||||||||||
scalar · Integer32 · read-only · current The number of battery modules in the device that have a warning. | |||||||||||||||||||||
| SlgpPwrBatteryCount | 1.3.6.1.4.1.476.1.42.3.5.1.7 | Integer32 | RO | ||||||||||||||||||
scalar · Integer32 · read-only · current The number of batteries installed.
| |||||||||||||||||||||
| SlgpPwrBatteryTestResult | 1.3.6.1.4.1.476.1.42.3.5.1.8 | INTEGER | RO | passed(2) | |||||||||||||||||
scalar · INTEGER · read-only · current The outcome of the previous battery test.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SlgpPwrNominalBatteryCapacity | 1.3.6.1.4.1.476.1.42.3.5.1.9 | Integer32 | RW | 10 | |||||||||||||||||
scalar · Integer32 · read-write · current The nominal battery capacity of the system (in minutes) at full load.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SlgpPwrBatteryFloatVoltage | 1.3.6.1.4.1.476.1.42.3.5.1.10 | Integer32 | RW | 2147483647 | |||||||||||||||||
scalar · Integer32 · read-write · current The battery float voltage of the system.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SlgpPwrBatteryEndOfDischargeVoltage | 1.3.6.1.4.1.476.1.42.3.5.1.11 | Integer32 | RW | ||||||||||||||||||
scalar · Integer32 · read-write · current The battery voltage threshold at which the batteries are considered completely discharged. | |||||||||||||||||||||
| SlgpPwrAutomaticBatteryTestInterval | 1.3.6.1.4.1.476.1.42.3.5.1.12 | Integer32 | RW | ||||||||||||||||||
scalar · Integer32 · read-write · current The automatic battery test interval.
| |||||||||||||||||||||
| SlgpPwrAutomaticBatteryTestCountdown | 1.3.6.1.4.1.476.1.42.3.5.1.13 | Integer32 | RW | ||||||||||||||||||
scalar · Integer32 · read-write · current The time remaining before the next battery test.
| |||||||||||||||||||||
| SlgpPwrBatteryChargeStatus | 1.3.6.1.4.1.476.1.42.3.5.1.14 | INTEGER | RO | notfullycharged(2) | |||||||||||||||||
scalar · INTEGER · read-only · current The present state of the system's battery charge. A value of 'charging' indicates the batteries are currently charging. A value of 'discharging' indicates the batteries are currently discharging. A value of 'fullycharged' indicates the batteries are charged to their full capacity. A value of 'notfullycharged' indicates the battery charge is neither fully charged, charging or discharging.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SlgpPwrBatteryLifeEnhancer | 1.3.6.1.4.1.476.1.42.3.5.1.15 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The state of the battery life enhancer. When 'on', it will preserve battery life.
| |||||||||||||||||||||
| SlgpPwrBatteryCharger | 1.3.6.1.4.1.476.1.42.3.5.1.16 | INTEGER | RO | off(2) | |||||||||||||||||
scalar · INTEGER · read-only · current The state of the battery charger.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SlgpPwrBatteryChargeMode | 1.3.6.1.4.1.476.1.42.3.5.1.17 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The mode of the battery charger: 'float' charging or 'equalize' charging.
| |||||||||||||||||||||
| SlgpPwrBatteryTimeRemaining | 1.3.6.1.4.1.476.1.42.3.5.1.18 | Integer32 | RO | 40 | |||||||||||||||||
scalar · Integer32 · read-only · current An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off. NOTE: A UPS is expected to provide a battery time remaining value when not operating on battery. However, if the system is not capable of providing this information, then this point will return 65535 to indicate that the value is unavailable.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SlgpPwrBatteryCapacity | 1.3.6.1.4.1.476.1.42.3.5.1.19 | Integer32 | RO | 99 | |||||||||||||||||
scalar · Integer32 · read-only · current The present percentage of battery capacity.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NlgpPwrBatteryCabinet | 1.3.6.1.4.1.476.1.42.3.5.1.20 | ||||||||||||||||||||
node · current This sub-tree contains items related to battery cabinets. | |||||||||||||||||||||
| SlgpPwrBatteryCabinetCount | 1.3.6.1.4.1.476.1.42.3.5.1.20.1 | Integer32 | RW | 0 | |||||||||||||||||
scalar · Integer32 · read-write · current The number of battery cabinets installed with this device. Note some devices may not permit writing a value to this object.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SlgpPwrBatteryCabinetType | 1.3.6.1.4.1.476.1.42.3.5.1.20.2 | INTEGER | RW | internal(2) | |||||||||||||||||
scalar · INTEGER · read-write · current The type of battery cabinet(s) installed on this device.
Enumeration definitions:
notSpecified - The type has not been specified in the
device's configuration.
internal - Battery cabinets are internal to the device.
external - Device has external battery cabinets installed.
lrt - Long Run Time cabinets.
Note some devices may not permit writing a value to this object.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SlgpPwrBatteryCabinetRatedCapacity | 1.3.6.1.4.1.476.1.42.3.5.1.20.3 | Integer32 | RW | 90 | |||||||||||||||||
scalar · Integer32 · read-write · current Battery cabinet rated capacity (tenths of Amp-hours). This assumes that each cabinet is of the same type and capacity. This is not a sum of the rating for all attached cabinets. Note some devices may not permit writing a value to this object.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SlgpPwrBatteryLeadAcidCellCount | 1.3.6.1.4.1.476.1.42.3.5.1.20.4 | Integer32 | RW | ||||||||||||||||||
scalar · Integer32 · read-write · current Battery cell count - lead-acid. The number of cells that comprise the lead acid battery string.
| |||||||||||||||||||||
| SlgpPwrBatteryNiCadCellCount | 1.3.6.1.4.1.476.1.42.3.5.1.20.5 | Integer32 | RW | ||||||||||||||||||
scalar · Integer32 · read-write · current Battery cell count - nickel-cadmium. The number of cells that comprise the nickel-cadmium battery string.
| |||||||||||||||||||||
| SlgpPwrBatteryAmpHoursConsumed | 1.3.6.1.4.1.476.1.42.3.5.1.21 | Integer32 | RW | ||||||||||||||||||
scalar · Integer32 · read-write · current The cumulative battery Amp-hours withdrawn over the life of the battery. This value persists across reboots. Typically, this value is reset back to zero when the batteries are replaced.
| |||||||||||||||||||||
| SlgpPwrBatteryAmpHoursDischargeConsumed | 1.3.6.1.4.1.476.1.42.3.5.1.22 | Integer32 | RW | ||||||||||||||||||
scalar · Integer32 · read-write · current The battery Amp-hours withdrawn during the current/latest discharge. This value does not persist across reboots.
| |||||||||||||||||||||
| SlgpPwrBatteryLastDischargeTime | 1.3.6.1.4.1.476.1.42.3.5.1.23 | Unsigned32 | RW | ||||||||||||||||||
scalar · Unsigned32 · read-write · current The date and time of the last battery discharge. Typically this is the time when the discharge starts. This value persists across reboots. The date and time are determined in seconds since the epoch on January 1, 1970.
| |||||||||||||||||||||
| SlgpPwrBatteryLastCommissionTime | 1.3.6.1.4.1.476.1.42.3.5.1.24 | Unsigned32 | RW | 4294967295 | |||||||||||||||||
scalar · Unsigned32 · read-write · current The date and time when the battery system was put into service. This information persists across system reboot events. It is the responsibility of Service to reset this date/time when the batteries are replaced. The date and time are determined in seconds since the epoch on January 1, 1970.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SlgpPwrBatteryPresentDischargeTime | 1.3.6.1.4.1.476.1.42.3.5.1.25 | Integer32 | RO | ||||||||||||||||||
scalar · Integer32 · read-only · current The total time spent on battery during the current or last discharge. NOTE: While not discharging, some systems may display zero instead of the last discharge.
| |||||||||||||||||||||
| SlgpPwrBatteryCapacityStatus | 1.3.6.1.4.1.476.1.42.3.5.1.26 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The indication of the capacity remaining in the UPS system's batteries. NOTE: In a single-module system, this point is intended to have the same behavior as the RFC1628 point upsBatteryStatus.
| |||||||||||||||||||||
| SlgpPwrBatteryCircuitBreakerState | 1.3.6.1.4.1.476.1.42.3.5.1.27 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The state of the Battery Circuit Breaker.
| |||||||||||||||||||||
| NlgpPwrMeasurements | 1.3.6.1.4.1.476.1.42.3.5.2 | ||||||||||||||||||||
node · current This sub-tree registers Liebert Power Measurement object identifiers. The sub-tree contains tables and well known power measurement points. | |||||||||||||||||||||
| NlgpPwrWellKnownMeasurementPoints | 1.3.6.1.4.1.476.1.42.3.5.2.1 | ||||||||||||||||||||
node · current This sub-tree registers well known Liebert Power Measurement Points. The object identifier names usually imply locations where the measurement is taken -- such as 'input', 'output' and 'bypass'. | |||||||||||||||||||||
| NlgpPwrSource1Input | 1.3.6.1.4.1.476.1.42.3.5.2.1.1 | ||||||||||||||||||||
node · current This sub-tree is used to register a source 1 input as a well known measurement point. It is intended that no sub-trees be created below this node. Power input to the managed device from power source 1. Many power systems contain more than one input source and many of them have more than one measurement point per input source. This identifier represents one input source for the system but does not necessarily represent the 'first' one. The input sources' numbering with respect to 'lgpPwrSource1Input' etc. may depend on the physical wiring of the system when it was installed. | |||||||||||||||||||||
| NlgpPwrSource2Input | 1.3.6.1.4.1.476.1.42.3.5.2.1.2 | ||||||||||||||||||||
node · current This sub-tree is used to register a source 2 input as a well known measurement point. It is intended that no sub-trees be created below this node. Power input to the managed device from power source 2. Many power systems contain more than one input source and many of them have more than one measurement point per input source. This identifier represents one input source for the system but does not necessarily represent the 'first' one. The input sources' numbering with respect to 'lgpPwrSource2Input' etc. may depend on the physical wiring of the system when it was installed. | |||||||||||||||||||||
| NlgpPwrSourcePdu1Input | 1.3.6.1.4.1.476.1.42.3.5.2.1.3 | ||||||||||||||||||||
node · current This sub-tree is used to register a source PDU 1 input as a well known measurement point. It is intended that no sub-trees be created below this node. Power input to the managed device from power distribution unit 1. Many power systems contain more than one input source and many of them have more than one measurement point per input source. This identifier represents one input source for the system but does not necessarily represent the 'first' one. The input sources' numbering with respect to 'lgpPwrSourcePdu1Input' etc. may depend on the physical wiring of the system when it was installed. | |||||||||||||||||||||
| NlgpPwrSourcePdu2Input | 1.3.6.1.4.1.476.1.42.3.5.2.1.4 | ||||||||||||||||||||
node · current This sub-tree is used to register a source PDU 2 input as a well known measurement point. It is intended that no sub-trees be created below this node. Power input to the managed device from power distribution unit 1. Many power systems contain more than one input source and many of them have more than one measurement point per input source. This identifier represents one input source for the system but does not necessarily represent the 'first' one. The input sources' numbering with respect to 'lgpPwrSourcePdu2Input' etc. may depend on the physical wiring of the system when it was installed. | |||||||||||||||||||||
| NlgpPwrOutputToLoad | 1.3.6.1.4.1.476.1.42.3.5.2.1.5 | ||||||||||||||||||||
node · current This sub-tree is used to register the output to the critical load as a well known measurement point. It is intended that no sub-trees be created below this node. | |||||||||||||||||||||
| NlgpPwrMeasBattery | 1.3.6.1.4.1.476.1.42.3.5.2.1.6 | ||||||||||||||||||||
node · current This sub-tree is used to register a battery as a well known measurement point. It is intended that no sub-trees be created below this node. | |||||||||||||||||||||
| NlgpPwrMeasBypass | 1.3.6.1.4.1.476.1.42.3.5.2.1.7 | ||||||||||||||||||||
node · current This sub-tree is used to register a bypass as a well known measurement point. It is intended that no sub-trees be created below this node. | |||||||||||||||||||||
| NlgpPwrMeasDcBus | 1.3.6.1.4.1.476.1.42.3.5.2.1.8 | ||||||||||||||||||||
node · current This sub-tree is used to register a DC bus as a well known measurement point. It is intended that no sub-trees be created below this node. | |||||||||||||||||||||
| NlgpPwrMeasSystemOutput | 1.3.6.1.4.1.476.1.42.3.5.2.1.9 | ||||||||||||||||||||
node · current This sub-tree is used to register the output of a multi-module system as a well known measurement point. It is intended that no sub-trees be created below this node. This identifier represents the power related data of the system. | |||||||||||||||||||||
| NlgpPwrMeasBatteryCabinet | 1.3.6.1.4.1.476.1.42.3.5.2.1.10 | ||||||||||||||||||||
node · current This sub-tree is used to register the voltage between the
most negative and the most postive terminals of a battery
cabinet. To determine the cabinet being described in a
multi-cabinet system, this point implements an additional
two indexes. The first index describes the module the cabinet
is located in. The second index describes the cabinet
number. In an SMS(Single-Module System) the first index is
always 1.
Example: lgpPwrMeasBatteryCabinet.2.4
'lgpPwrMeasBatteryCabinet' = Point is a battery cabinet.
'.2' = Cabinet is in the second module.
'.4' = Cabinet number 4 | |||||||||||||||||||||
| TlgpPwrMeasurementPointTable | 1.3.6.1.4.1.476.1.42.3.5.2.2 | NA | |||||||||||||||||||
table · not-accessible · current This table contains a list of AC power measurement point entries. The table contains zero, one, or many rows, depending upon the number of power related measurement points available. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device. Each row in the table represents a series of measurements on a given point or location within the system. Measurement points/locations are identified by the object identifier 'lgpPwrMeasurementPointId' in the 'LgpPwrMeasurementPointEntry' object. The actual measurement being taken at that identified point is identified by the other corresponding columns in the LgpPwrMeasurementPointEntry for the particular row of the table. | |||||||||||||||||||||
| RlgpPwrMeasurementPointEntry | 1.3.6.1.4.1.476.1.42.3.5.2.2.1 | NA | |||||||||||||||||||
row · not-accessible · current This entry defines the measurements to be populated in the various columns of the 'lgpPwrMeasurementPointTable'. | |||||||||||||||||||||
| ClgpPwrMeasurementPointIndex | 1.3.6.1.4.1.476.1.42.3.5.2.2.1.1 | Unsigned32 | NA | ||||||||||||||||||
column · Unsigned32 · not-accessible · current This is the index that indicates the row of the 'lgpPwrMeasurementPointTable' for a power measurement point. | |||||||||||||||||||||
| ClgpPwrMeasurementPointId | 1.3.6.1.4.1.476.1.42.3.5.2.2.1.2 | OBJECT IDENTIFIER | RO | 1.3.6.1.4.1.476.1.42.3.5.2.1.1 | |||||||||||||||||
column · OBJECT IDENTIFIER · read-only · current An OID representing a well known measurement point. These object identifiers indicate a point or location of power measurement in a power system. The OID's name usually implies a location of the measurement point such as 'input', 'output', 'bypass' etc. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPwrMeasurementPointNumLines | 1.3.6.1.4.1.476.1.42.3.5.2.2.1.3 | Integer32 | RO | 3 | |||||||||||||||||
column · Integer32 · read-only · current The number of lines on the indicated power measurement point. (i.e. the number of phases on the power source being measured.)
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPwrMeasurementPointNomVolts | 1.3.6.1.4.1.476.1.42.3.5.2.2.1.4 | Integer32 | RO | 120 | |||||||||||||||||
column · Integer32 · read-only · current The magnitude of the nominal voltage on the power source being measured.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPwrMeasurementPointNomFrequency | 1.3.6.1.4.1.476.1.42.3.5.2.2.1.5 | Integer32 | RO | 60 | |||||||||||||||||
column · Integer32 · read-only · current The nominal or configured/expected frequency for the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPwrMeasurementPointFrequency | 1.3.6.1.4.1.476.1.42.3.5.2.2.1.6 | Integer32 | RO | 60 | |||||||||||||||||
column · Integer32 · read-only · current The present (actual) frequency for the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPwrMeasurementPointApparentPower | 1.3.6.1.4.1.476.1.42.3.5.2.2.1.7 | Integer32 | RO | 440 | |||||||||||||||||
column · Integer32 · read-only · current The present apparent AC power for the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPwrMeasurementPointTruePower | 1.3.6.1.4.1.476.1.42.3.5.2.2.1.8 | Integer32 | RO | 430 | |||||||||||||||||
column · Integer32 · read-only · current The present AC power for the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPwrMeasurementPointPowerFactor | 1.3.6.1.4.1.476.1.42.3.5.2.2.1.9 | Integer32 | RO | 99 | |||||||||||||||||
column · Integer32 · read-only · current The present Power Factor for the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPwrMeasurementPointWattHours | 1.3.6.1.4.1.476.1.42.3.5.2.2.1.10 | Integer32 | RO | 12768 | |||||||||||||||||
column · Integer32 · read-only · current The present number of Watt Hours for the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPwrMeasurementPointVAPercent | 1.3.6.1.4.1.476.1.42.3.5.2.2.1.11 | Integer32 | RO | 230 | |||||||||||||||||
column · Integer32 · read-only · current The percentage of the rated apparent AC power of the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPwrMeasurementPointNeutralCurrent | 1.3.6.1.4.1.476.1.42.3.5.2.2.1.12 | Integer32 | RO | 0 | |||||||||||||||||
column · Integer32 · read-only · current The present neutral current of the power point indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPwrMeasurementPointGroundCurrent | 1.3.6.1.4.1.476.1.42.3.5.2.2.1.13 | Integer32 | RO | 0 | |||||||||||||||||
column · Integer32 · read-only · current The present ground current of the power point indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPwrMeasurementPointNomCurrent | 1.3.6.1.4.1.476.1.42.3.5.2.2.1.14 | Integer32 | RO | 180 | |||||||||||||||||
column · Integer32 · read-only · current The nominal or configured/expected current of the power point indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPwrMeasurementPointNomPowerFactor | 1.3.6.1.4.1.476.1.42.3.5.2.2.1.15 | Integer32 | RO | 90 | |||||||||||||||||
column · Integer32 · read-only · current The nominal or configured/expected power factor of the power point indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPwrMeasurementPointNomVA | 1.3.6.1.4.1.476.1.42.3.5.2.2.1.16 | Integer32 | RW | 2000 | |||||||||||||||||
column · Integer32 · read-write · current The nominal or configured/expected apparent AC power for the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPwrMeasurementPointNomW | 1.3.6.1.4.1.476.1.42.3.5.2.2.1.17 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current The nominal or configured/expected true AC power for the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
| |||||||||||||||||||||
| ClgpPwrMeasurementPointPowerFactorTag | 1.3.6.1.4.1.476.1.42.3.5.2.2.1.19 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current The present description of the Power Factor for the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable. If Leading, the load is said to be capacitive and the phase of the current leads the voltage. If Lagging, the load is said to be inductive and the phase of the current lags the voltage.
| |||||||||||||||||||||
| TlgpPwrLineMeasurementTable | 1.3.6.1.4.1.476.1.42.3.5.2.3 | NA | |||||||||||||||||||
table · not-accessible · current A list of power measurements for each phase/line for a given power measurement point/location in the 'lgpPwrMeasurementPointTable'. The lgpPwrMeasurementPointIndex in this table corresponds to the index in the lgpPwrMeasurementPointTable. This table contains zero, one, or many rows, depending upon the number of power line source objects available. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device. | |||||||||||||||||||||
| RlgpPwrLineMeasurementEntry | 1.3.6.1.4.1.476.1.42.3.5.2.3.1 | NA | |||||||||||||||||||
row · not-accessible · current This entry defines the contents of the columns for the table 'lgpPwrLineMeasurementTable'. | |||||||||||||||||||||
| ClgpPwrMeasurementPtIndex | 1.3.6.1.4.1.476.1.42.3.5.2.3.1.1 | Unsigned32 | NA | ||||||||||||||||||
column · Unsigned32 · not-accessible · current This is the index indicating the row of the table 'lgpPwrMeasurementPointTable' for a power measurement point. | |||||||||||||||||||||
| ClgpPwrLineMeasurementIndex | 1.3.6.1.4.1.476.1.42.3.5.2.3.1.2 | Unsigned32 | NA | ||||||||||||||||||
column · Unsigned32 · not-accessible · current This is the index indicating the row of the table 'lgpPwrLineMeasurementTable' for a power measurement point. | |||||||||||||||||||||
| ClgpPwrMeasurementPoint | 1.3.6.1.4.1.476.1.42.3.5.2.3.1.3 | OBJECT IDENTIFIER | RO | 1.3.6.1.4.1.476.1.42.3.5.2.1.1 | |||||||||||||||||
column · OBJECT IDENTIFIER · read-only · current An OID representing a well known measurement point. These object identifiers indicate a point or location of power measurement in a power system. The OID name usually implies a location of the measurement point such as 'input', 'output', 'bypass', etc. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPwrLineMeasurementVoltsLL | 1.3.6.1.4.1.476.1.42.3.5.2.3.1.4 | Integer32 | RO | 479 | |||||||||||||||||
column · Integer32 · read-only · current The present Line-to-Line voltage measurement for the indicated source. The line being measured is given by the lgpPwrLineMeasurementIndex [1 = AB, 2 = BC, 3 = CA].
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPwrLineMeasurementVoltsLN | 1.3.6.1.4.1.476.1.42.3.5.2.3.1.5 | Integer32 | RO | 118 | |||||||||||||||||
column · Integer32 · read-only · current The present Line-to-neutral voltage measurement for the indicated source. The line being measured is given by the lgpPwrLineMeasurementIndex where [1 = A, 2 = B, 3 = C].
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPwrLineMeasurementCurrent | 1.3.6.1.4.1.476.1.42.3.5.2.3.1.6 | Integer32 | RO | 1 | |||||||||||||||||
column · Integer32 · read-only · current The present current measurement for the indicated source. The line being measured is given by the 'lgpPwrLineMeasurementIndex' where [1 = A, 2 = B, 3 = C].
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPwrLineMeasurementCapacity | 1.3.6.1.4.1.476.1.42.3.5.2.3.1.7 | Integer32 | RO | 49 | |||||||||||||||||
column · Integer32 · read-only · current The percentage of the power capacity presently being used on this line.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPwrLineMeasurementVA | 1.3.6.1.4.1.476.1.42.3.5.2.3.1.8 | Integer32 | RO | 440 | |||||||||||||||||
column · Integer32 · read-only · current The present apparent AC line power.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPwrLineMeasurementTruePower | 1.3.6.1.4.1.476.1.42.3.5.2.3.1.9 | Integer32 | RO | 430 | |||||||||||||||||
column · Integer32 · read-only · current The present AC line power measured in watts.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPwrLineMeasurementVoltageTHD | 1.3.6.1.4.1.476.1.42.3.5.2.3.1.10 | Integer32 | RO | 14 | |||||||||||||||||
column · Integer32 · read-only · current The present total harmonic distortion on the AC line voltage.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPwrLineMeasurementCurrentTHD | 1.3.6.1.4.1.476.1.42.3.5.2.3.1.11 | Integer32 | RO | 22 | |||||||||||||||||
column · Integer32 · read-only · current The present total harmonic distortion on the AC line current.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPwrLineMeasurementKFactorCurrent | 1.3.6.1.4.1.476.1.42.3.5.2.3.1.12 | Integer32 | RO | 10 | |||||||||||||||||
column · Integer32 · read-only · current The present line K Factor.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPwrLineMeasurementCrestFactorCurrent | 1.3.6.1.4.1.476.1.42.3.5.2.3.1.13 | Integer32 | RO | 14 | |||||||||||||||||
column · Integer32 · read-only · current The present crest factor of the line current.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPwrLineMeasurementPowerFactor | 1.3.6.1.4.1.476.1.42.3.5.2.3.1.14 | Integer32 | RO | 63 | |||||||||||||||||
column · Integer32 · read-only · current The present Power Factor for the line.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPwrLineMeasurementPowerFactorTag | 1.3.6.1.4.1.476.1.42.3.5.2.3.1.15 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current The present description of the Power Factor for the line. If Leading, the load is said to be capacitive and the phase of the current leads the voltage. If Lagging, the load is said to be inductive and the phase of the current lags the voltage.
| |||||||||||||||||||||
| ClgpPwrLineMeasurementMaxVolts | 1.3.6.1.4.1.476.1.42.3.5.2.3.1.16 | Integer32 | RO | 128 | |||||||||||||||||
column · Integer32 · read-only · current The maximum voltage measurement recorded for the indicated source since the command 'lgpPwrStatisticsReset' was executed.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPwrLineMeasurementMinVolts | 1.3.6.1.4.1.476.1.42.3.5.2.3.1.17 | Integer32 | RO | 0 | |||||||||||||||||
column · Integer32 · read-only · current The minimum voltage measurement recorded for the indicated source since the command 'lgpPwrStatisticsReset' was executed.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPwrLineMeasurementVAR | 1.3.6.1.4.1.476.1.42.3.5.2.3.1.18 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The present reactive AC line power of the power source indicated by 'lgpPwrMeasurementPoint'.
| |||||||||||||||||||||
| ClgpPwrLineMeasurementPercentLoad | 1.3.6.1.4.1.476.1.42.3.5.2.3.1.19 | Integer32 | RO | 23 | |||||||||||||||||
column · Integer32 · read-only · current The present percent load of the AC line power.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPwrLineMeasurementVolts | 1.3.6.1.4.1.476.1.42.3.5.2.3.1.20 | Integer32 | RO | 120 | |||||||||||||||||
column · Integer32 · read-only · current The present voltage measurement for the indicated source.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPwrLineMeasurementVACapacity | 1.3.6.1.4.1.476.1.42.3.5.2.3.1.21 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The percentage of the apparent power capacity presently being used on this line.
| |||||||||||||||||||||
| TlgpPwrDcMeasurementPointTable | 1.3.6.1.4.1.476.1.42.3.5.2.4 | NA | |||||||||||||||||||
table · not-accessible · current This table contains a list of DC power measurement point entries. The table contains zero, one, or many rows, depending upon the number of power related measurement points available. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device. Each row in the table represents a series of measurements on a given point or location within the system. Measurement points/locations are identified by the object identifier 'lgpPwrDcMeasurementPointId' in the 'LgpPwrDcMeasurementPointEntry' object. The actual measurement being taken at that identified point is identified by the other corresponding columns in the LgpPwrDcMeasurementPointEntry for the particular row of the table. | |||||||||||||||||||||
| RlgpPwrDcMeasurementPointEntry | 1.3.6.1.4.1.476.1.42.3.5.2.4.1 | NA | |||||||||||||||||||
row · not-accessible · current This entry defines the measurements to be populated in the various columns of the 'lgpPwrDcMeasurementPointTable'. | |||||||||||||||||||||
| ClgpPwrDcMeasurementPointIndex | 1.3.6.1.4.1.476.1.42.3.5.2.4.1.1 | Unsigned32 | NA | ||||||||||||||||||
column · Unsigned32 · not-accessible · current This is the index that indicates the row of the 'lgpPwrMeasurementPointTable' for a power measurement point. | |||||||||||||||||||||
| ClgpPwrDcMeasurementPointId | 1.3.6.1.4.1.476.1.42.3.5.2.4.1.2 | OBJECT IDENTIFIER | RO | 1.3.6.1.4.1.476.1.42.3.5.2.1.6 | |||||||||||||||||
column · OBJECT IDENTIFIER · read-only · current An OID representing a well known measurement point. These object identifiers indicate a point or location of power measurement in a power system. The OID's name usually implies a location of the measurement point such as 'input', 'output', 'bypass' etc. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPwrDcMeasurementPointSubID | 1.3.6.1.4.1.476.1.42.3.5.2.4.1.3 | Integer32 | RO | 1 | |||||||||||||||||
column · Integer32 · read-only · current The identifier used to differentiate between identical thresholds for a given point index and point ID in the DC measurements table.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPwrDcMeasurementPointVolts | 1.3.6.1.4.1.476.1.42.3.5.2.4.1.4 | Integer32 | RO | 53 | |||||||||||||||||
column · Integer32 · read-only · current The present DC voltage for the power source indicated by 'lgpPwrDcMeasurementPointId' in the corresponding row in the lgpPwrDcMeasurementPointTable.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPwrDcMeasurementPointCurrent | 1.3.6.1.4.1.476.1.42.3.5.2.4.1.5 | Integer32 | RO | 0 | |||||||||||||||||
column · Integer32 · read-only · current The present DC current for the power source indicated by 'lgpPwrDcMeasurementPointId' in the corresponding row in the lgpPwrDcMeasurementPointTable.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPwrDcMeasurementPointNomVolts | 1.3.6.1.4.1.476.1.42.3.5.2.4.1.6 | Integer32 | RO | 51 | |||||||||||||||||
column · Integer32 · read-only · current The nominal(configured/expected) DC voltage for the power source indicated by 'lgpPwrDcMeasurementPointId' in the corresponding row in the lgpPwrDcMeasurementPointTable.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPwrDcMeasurementPointTruePower | 1.3.6.1.4.1.476.1.42.3.5.2.4.1.7 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The present DC power for the power source indicated by 'lgpPwrDcMeasurementPointId' in the corresponding row in the lgpPwrDcMeasurementPointTable.
| |||||||||||||||||||||
| NlgpPwrWellKnownMeasurementTypes | 1.3.6.1.4.1.476.1.42.3.5.2.5 | ||||||||||||||||||||
node · current This sub-tree registers well known Liebert Power Measurement Types. The object identifier names usually encompass units of measure, lines of reference, and device location. The OID's name usually implies a measurement type such as 'voltsAC', 'current', 'voltsDc', 'VoltsLL', etc. | |||||||||||||||||||||
| NlgpPwrVoltsAc | 1.3.6.1.4.1.476.1.42.3.5.2.5.1 | ||||||||||||||||||||
node · current This identifier represents an AC voltage. | |||||||||||||||||||||
| NlgpPwrVoltsDc | 1.3.6.1.4.1.476.1.42.3.5.2.5.2 | ||||||||||||||||||||
node · current This identifier represents a DC voltage. | |||||||||||||||||||||
| NlgpPwrAmpsNeutral | 1.3.6.1.4.1.476.1.42.3.5.2.5.3 | ||||||||||||||||||||
node · current This identifier represents a current measurement in Amps on the neutral line. | |||||||||||||||||||||
| NlgpPwrStatus | 1.3.6.1.4.1.476.1.42.3.5.3 | ||||||||||||||||||||
node · current This sub-tree registers Liebert Power Status object identifiers. This is the location of power related status information that does not fit into a more specific category such as the lgpPwrConversion sub-tree. | |||||||||||||||||||||
| SlgpPwrTransferCount | 1.3.6.1.4.1.476.1.42.3.5.3.1 | Integer32 | RO | ||||||||||||||||||
scalar · Integer32 · read-only · current Number of times that the output load has been transferred between the available input sources.
| |||||||||||||||||||||
| SlgpPwrAutoTransferTimer | 1.3.6.1.4.1.476.1.42.3.5.3.2 | Integer32 | RO | ||||||||||||||||||
scalar · Integer32 · read-only · current The required wait time between output load auto transfer attempts between available input sources.
| |||||||||||||||||||||
| SlgpPwrAutoReTransferEnabled | 1.3.6.1.4.1.476.1.42.3.5.3.3 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The ability to retransfer the output load automatically to the well known measurement source from the 'lgpPwrWellKnownMeasurements' sub-tree that is the preferred input source of the system
| |||||||||||||||||||||
| SlgpPwrSyncPhaseAngle | 1.3.6.1.4.1.476.1.42.3.5.3.4 | Integer32 (-3600..3600) | RO | ||||||||||||||||||
scalar · Integer32 (-3600..3600) · read-only · current The phase angle difference of source 1 in relation to source 2.
| |||||||||||||||||||||
| SlgpPwrParallelSystemOutputToLoadSource | 1.3.6.1.4.1.476.1.42.3.5.3.5 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The source supporting the parallel system's load.
| |||||||||||||||||||||
| SlgpPwrDcToDcConverter | 1.3.6.1.4.1.476.1.42.3.5.3.6 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The state of the DC to DC converter.
| |||||||||||||||||||||
| SlgpPwrOutputToLoadOnInverter | 1.3.6.1.4.1.476.1.42.3.5.3.7 | INTEGER | RO | no(2) | |||||||||||||||||
scalar · INTEGER · read-only · current The present source of output power is the Inverter.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SlgpPwrBatteryChargeCompensating | 1.3.6.1.4.1.476.1.42.3.5.3.8 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The system is adjusting the battery charging algorithm to accommodate for the battery temperature.
| |||||||||||||||||||||
| SlgpPwrInverterReady | 1.3.6.1.4.1.476.1.42.3.5.3.9 | INTEGER | RO | yes(1) | |||||||||||||||||
scalar · INTEGER · read-only · current The ability of the inverter to support the output load of the system.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SlgpPwrOutputToLoadOnBypass | 1.3.6.1.4.1.476.1.42.3.5.3.10 | INTEGER | RO | yes(1) | |||||||||||||||||
scalar · INTEGER · read-only · current The present source of output power is the Bypass.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SlgpPwrBoost | 1.3.6.1.4.1.476.1.42.3.5.3.11 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The present state of the boost circuitry
| |||||||||||||||||||||
| SlgpPwrBuck | 1.3.6.1.4.1.476.1.42.3.5.3.12 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The present state of the buck circuitry
| |||||||||||||||||||||
| SlgpPwrShutdownOverTemperature | 1.3.6.1.4.1.476.1.42.3.5.3.13 | INTEGER | RO | no(2) | |||||||||||||||||
scalar · INTEGER · read-only · current The system has previously shutdown due to an over temperature condition.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SlgpPwrShutdownOverload | 1.3.6.1.4.1.476.1.42.3.5.3.14 | INTEGER | RO | no(2) | |||||||||||||||||
scalar · INTEGER · read-only · current The system has previously shutdown due to an over load condition.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SlgpPwrShutdownDcBusOverload | 1.3.6.1.4.1.476.1.42.3.5.3.15 | INTEGER | RO | no(2) | |||||||||||||||||
scalar · INTEGER · read-only · current The system has previously shutdown due to a DC bus over load condition.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SlgpPwrShutdownOutputShort | 1.3.6.1.4.1.476.1.42.3.5.3.16 | INTEGER | RO | no(2) | |||||||||||||||||
scalar · INTEGER · read-only · current The system has previously shutdown due to an output short condition.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SlgpPwrShutdownLineSwap | 1.3.6.1.4.1.476.1.42.3.5.3.17 | INTEGER | RO | no(2) | |||||||||||||||||
scalar · INTEGER · read-only · current The system has previously shutdown due to a condition where the line and neutral were reversed.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SlgpPwrShutdownLowBattery | 1.3.6.1.4.1.476.1.42.3.5.3.18 | INTEGER | RO | no(2) | |||||||||||||||||
scalar · INTEGER · read-only · current The system has previously shutdown due to a low battery condition.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SlgpPwrShutdownRemote | 1.3.6.1.4.1.476.1.42.3.5.3.19 | INTEGER | RO | no(2) | |||||||||||||||||
scalar · INTEGER · read-only · current The system has previously shutdown due to a remote shutdown command.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SlgpPwrShutdownInputUnderVoltage | 1.3.6.1.4.1.476.1.42.3.5.3.20 | INTEGER | RO | no(2) | |||||||||||||||||
scalar · INTEGER · read-only · current The system has previously shutdown due to an under voltage condition during startup.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SlgpPwrShutdownPowerFactorCorrectionFailure | 1.3.6.1.4.1.476.1.42.3.5.3.21 | INTEGER | RO | no(2) | |||||||||||||||||
scalar · INTEGER · read-only · current The system has previously shutdown due to a power factor correction startup failure.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SlgpPwrShutdownHardware | 1.3.6.1.4.1.476.1.42.3.5.3.22 | INTEGER | RO | no(2) | |||||||||||||||||
scalar · INTEGER · read-only · current The system has previously shutdown due external shutdown signal.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SlgpPwrRedundantSubModule | 1.3.6.1.4.1.476.1.42.3.5.3.23 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The system has a redundant battery module installed.
| |||||||||||||||||||||
| SlgpPwrBypassReady | 1.3.6.1.4.1.476.1.42.3.5.3.24 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The ability of the bypass to support the output load of the system. If Yes, the bypass is available to transfer to.
| |||||||||||||||||||||
| SlgpPwrGeneratorStatus | 1.3.6.1.4.1.476.1.42.3.5.3.25 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The state of the system generator.
| |||||||||||||||||||||
| SlgpPwrRotaryBreakerStatus | 1.3.6.1.4.1.476.1.42.3.5.3.26 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The state of the system rotary breaker.
| |||||||||||||||||||||
| SlgpPwrPowerFactorCorrection | 1.3.6.1.4.1.476.1.42.3.5.3.27 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The state of the power factor correction circuitry of the system.
| |||||||||||||||||||||
| SlgpPwrBypassSyncDiff | 1.3.6.1.4.1.476.1.42.3.5.3.28 | Integer32 | RO | ||||||||||||||||||
scalar · Integer32 · read-only · current The phase angle difference between the inverter output and bypass source. A positive value means the inverter leads the bypass source. A negative value means the inverter lags the bypass source.
| |||||||||||||||||||||
| SlgpPwrBypassOverloadShutdownTime | 1.3.6.1.4.1.476.1.42.3.5.3.29 | Integer32 | RO | ||||||||||||||||||
scalar · Integer32 · read-only · current The calculated time remaining before bypass static switch shutdown due to the present overload condition. If the bypass is not in an overload condition, this object returns -1.
| |||||||||||||||||||||
| SlgpPwrInverterOverloadShutdownTime | 1.3.6.1.4.1.476.1.42.3.5.3.30 | Integer32 | RO | ||||||||||||||||||
scalar · Integer32 · read-only · current The calculated time remaining before inverter shutdown. The calculated time of inverter operation remaining for the present overload event. Note: If the inverter is not experiencing an overload event this point will return 65535 indicating this value is unavailable.
| |||||||||||||||||||||
| SlgpPwrStateOutputSource | 1.3.6.1.4.1.476.1.42.3.5.3.31 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The UPS's output power source (inverter, bypass, or none). NOTE: It is possible that the load still has power from the Maintenance Bypass.
| |||||||||||||||||||||
| SlgpPwrStateInputSource | 1.3.6.1.4.1.476.1.42.3.5.3.32 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The system input power source (none, utility, generator).
| |||||||||||||||||||||
| SlgpPwrStateInputQualification | 1.3.6.1.4.1.476.1.42.3.5.3.33 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The current state of the system input. The unit may or may not operate normally under 'marginalLow' and 'marginalHigh' states.
| |||||||||||||||||||||
| SlgpPwrStateBypassStaticSwitchState | 1.3.6.1.4.1.476.1.42.3.5.3.34 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The current state of the bypass static switch.
| |||||||||||||||||||||
| SlgpPwrStateBypassQualification | 1.3.6.1.4.1.476.1.42.3.5.3.35 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The current operational state of the bypass static switch. The unit may or may not operate normally under 'marginalLow' and 'marginalHigh' states.
| |||||||||||||||||||||
| SlgpPwrStateDCBusQualification | 1.3.6.1.4.1.476.1.42.3.5.3.36 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The current operational state of the DC bus. The unit may or may not operate normally under 'marginalLow' and 'marginalHigh' states.
| |||||||||||||||||||||
| SlgpPwrStateOutQualification | 1.3.6.1.4.1.476.1.42.3.5.3.37 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The current operational state of the output. The unit may or may not operate normally under 'marginalLow' and 'marginalHigh' states.
| |||||||||||||||||||||
| SlgpPwrStateInverterQualification | 1.3.6.1.4.1.476.1.42.3.5.3.38 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The current operational state of the inverter. The unit may or may not operate normally under 'marginalLow' and 'marginalHigh' states.
| |||||||||||||||||||||
| SlgpPwrStateInverterState | 1.3.6.1.4.1.476.1.42.3.5.3.39 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The current state of the inverter.
| |||||||||||||||||||||
| SlgpPwrStateRectifierState | 1.3.6.1.4.1.476.1.42.3.5.3.40 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The current state of the rectifier.
| |||||||||||||||||||||
| NlgpPwrStateModuleGroup | 1.3.6.1.4.1.476.1.42.3.5.3.41 | ||||||||||||||||||||
node · current This group contains UPS module information. | |||||||||||||||||||||
| SlgpPwrStateUpsModuleCount | 1.3.6.1.4.1.476.1.42.3.5.3.41.1 | Integer32 | RW | ||||||||||||||||||
scalar · Integer32 · read-write · current Number of UPS modules in the system. In a single module system, this value is one.
| |||||||||||||||||||||
| SlgpPwrStateUpsModuleRedundantCount | 1.3.6.1.4.1.476.1.42.3.5.3.41.2 | Integer32 | RO | ||||||||||||||||||
scalar · Integer32 · read-only · current Number of redundant UPS modules in the system. In a single module system, the value is zero. This value is dependent upon the present load and the number of modules (i.e. the value may change during normal operation based upon a load change). This value represents the number of extra modules above the minimum needed to support the load.
| |||||||||||||||||||||
| SlgpPwrStateBackfeedBrkrState | 1.3.6.1.4.1.476.1.42.3.5.3.42 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The state of the Static Bypass Switch Line Disconnect Breaker.
| |||||||||||||||||||||
| SlgpPwrStateLoadDisconnectState | 1.3.6.1.4.1.476.1.42.3.5.3.43 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The state of the Static Bypass Switch Load Disconnect Breaker.
| |||||||||||||||||||||
| SlgpPwrStateInputBrkrState | 1.3.6.1.4.1.476.1.42.3.5.3.44 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The state of the Input Disconnect Breaker.
| |||||||||||||||||||||
| SlgpPwrStateTrapFilterBrkrState | 1.3.6.1.4.1.476.1.42.3.5.3.45 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The state of the Trap Filter Disconnect Breaker.
| |||||||||||||||||||||
| SlgpPwrStateInvOutputBrkrState | 1.3.6.1.4.1.476.1.42.3.5.3.46 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The state of the Inverter Output Disconnect Breaker.
| |||||||||||||||||||||
| SlgpPwrStateIntBypassBrkrState | 1.3.6.1.4.1.476.1.42.3.5.3.47 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The state of the Internal Bypass Breaker.
| |||||||||||||||||||||
| SlgpPwrStateBypassIsolBrkrState | 1.3.6.1.4.1.476.1.42.3.5.3.48 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The state of the Bypass Isolation Breaker.
| |||||||||||||||||||||
| SlgpPwrStateRectifierIsolBrkrState | 1.3.6.1.4.1.476.1.42.3.5.3.49 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The state of the Rectifier Isolation Breaker.
| |||||||||||||||||||||
| SlgpPwrStateMaintBypassBrkrState | 1.3.6.1.4.1.476.1.42.3.5.3.50 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The state of the Maintenance Bypass Breaker.
| |||||||||||||||||||||
| SlgpPwrStateMaintIsolBrkrState | 1.3.6.1.4.1.476.1.42.3.5.3.51 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The state of the Maintenance Isolation Breaker.
| |||||||||||||||||||||
| SlgpPwrStateOutStaticSwState | 1.3.6.1.4.1.476.1.42.3.5.3.52 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The state of the Output Series Static Switch.
| |||||||||||||||||||||
| SlgpPwrStateModuleOutBrkrState | 1.3.6.1.4.1.476.1.42.3.5.3.53 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The state of the Module Output Breaker.
| |||||||||||||||||||||
| SlgpPwrBypassReXfrRemainTime | 1.3.6.1.4.1.476.1.42.3.5.3.54 | Integer32 | RO | ||||||||||||||||||
scalar · Integer32 · read-only · current The time remaining before an inverter overload or inverter fault can be cleared and auto retransfer from the bypass to the inverter can take place. Note: If an inverter overload or fault is not taking place, this point will return 65535.
| |||||||||||||||||||||
| SlgpPwrStateUpsOutputSource | 1.3.6.1.4.1.476.1.42.3.5.3.55 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker. NOTE: In a single-module system, this point is intended to have the same behavior as the RFC1628 point upsOutputSource.
| |||||||||||||||||||||
| SlgpPwrStateLoadBusSynchronization | 1.3.6.1.4.1.476.1.42.3.5.3.56 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The state of the Load Bus Synchronizer (LBS).
| |||||||||||||||||||||
| NlgpPwrStateCircuitBrkrStateGroup | 1.3.6.1.4.1.476.1.42.3.5.3.57 | ||||||||||||||||||||
node · current This group contains Static Switch circuit breaker state information. | |||||||||||||||||||||
| SlgpPwrStateSource1InputBrkrState | 1.3.6.1.4.1.476.1.42.3.5.3.57.1 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The states of Source 1 Input Breaker.
| |||||||||||||||||||||
| SlgpPwrStateSource2InputBrkrState | 1.3.6.1.4.1.476.1.42.3.5.3.57.2 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The states of Source 2 Input Breaker.
| |||||||||||||||||||||
| SlgpPwrStateSource1BypassBrkrState | 1.3.6.1.4.1.476.1.42.3.5.3.57.3 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The states of Source 1 Bypass Breaker.
| |||||||||||||||||||||
| SlgpPwrStateSource2BypassBrkrState | 1.3.6.1.4.1.476.1.42.3.5.3.57.4 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The states of Source 2 Bypass Breaker.
| |||||||||||||||||||||
| SlgpPwrStateOutputBrkrState | 1.3.6.1.4.1.476.1.42.3.5.3.57.5 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The states of Output Breaker.
| |||||||||||||||||||||
| SlgpPwrStateAuxOutputBrkrState | 1.3.6.1.4.1.476.1.42.3.5.3.57.6 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The states of Auxiliary Output Breaker.
| |||||||||||||||||||||
| SlgpPwrStateSource1PduInputBrkrState | 1.3.6.1.4.1.476.1.42.3.5.3.57.7 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The states of Source 1 PDU Input Breaker.
| |||||||||||||||||||||
| SlgpPwrStateSource2PduInputBrkrState | 1.3.6.1.4.1.476.1.42.3.5.3.57.8 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The states of Source 2 PDU Input Breaker.
| |||||||||||||||||||||
| SlgpPwrEconomicOperation | 1.3.6.1.4.1.476.1.42.3.5.3.58 | INTEGER | RO | on(1) | |||||||||||||||||
scalar · INTEGER · read-only · current The present state of ECO mode operation, on(1) if system is on bypass due to ECO mode operation, off(0) any other time.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NlgpPwrSettings | 1.3.6.1.4.1.476.1.42.3.5.4 | ||||||||||||||||||||
node · current This sub-tree registers Liebert Power Static Switch object identifiers. | |||||||||||||||||||||
| SlgpPwrPreferredSource | 1.3.6.1.4.1.476.1.42.3.5.4.1 | OBJECT IDENTIFIER | RO | ||||||||||||||||||
scalar · OBJECT IDENTIFIER · read-only · current The well known measurement source from the 'lgpPwrWellKnownMeasurements' sub-tree that is the preferred input source of the system. | |||||||||||||||||||||
| SlgpPwrLoadOnSource | 1.3.6.1.4.1.476.1.42.3.5.4.2 | OBJECT IDENTIFIER | RO | ||||||||||||||||||
scalar · OBJECT IDENTIFIER · read-only · current The well known measurement source from the 'lgpPwrWellKnownMeasurements' sub-tree that is currently powering the output (load). | |||||||||||||||||||||
| SlgpPwrNominalVoltageDeviation | 1.3.6.1.4.1.476.1.42.3.5.4.3 | Integer32 | RO | ||||||||||||||||||
scalar · Integer32 · read-only · current The nominal voltage deviation between the well known measurement source lgpPwrSource1Input and lgpPwrSource2Input.
| |||||||||||||||||||||
| SlgpPwrNominalVoltageDeviationPercent | 1.3.6.1.4.1.476.1.42.3.5.4.4 | Integer32 | RO | ||||||||||||||||||
scalar · Integer32 · read-only · current The percentage of the nominal voltage deviation between the well known measurement source lgpPwrSource1Input and lgpPwrSource2Input.
| |||||||||||||||||||||
| SlgpPwrPhaseDifferenceLimit | 1.3.6.1.4.1.476.1.42.3.5.4.5 | Integer32 | RO | ||||||||||||||||||
scalar · Integer32 · read-only · current The maximum phase difference (between the well known input sources ) in which a transfer to an available input source is permitted.
| |||||||||||||||||||||
| SlgpPwrFrequencyDeviationLimit | 1.3.6.1.4.1.476.1.42.3.5.4.6 | Integer32 | RO | ||||||||||||||||||
scalar · Integer32 · read-only · current The maximum frequency deviation (between the well known input sources ) in which a transfer to an available input source is permitted.
| |||||||||||||||||||||
| TlgpPwrThresholdTable | 1.3.6.1.4.1.476.1.42.3.5.4.7 | NA | |||||||||||||||||||
table · not-accessible · current A list of power thresholds for a given power measurement at a point/location in the system. The lgpPwrThresholdType in this table corresponds to the type of measurement the high and low thresholds applies to. This table contains zero, one, or many rows, depending upon the number of 'lgpPwrThresholdPoint' and 'lgpPwrThresholdSubID' available in the table. The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device. | |||||||||||||||||||||
| RlgpPwrThresholdEntry | 1.3.6.1.4.1.476.1.42.3.5.4.7.1 | NA | |||||||||||||||||||
row · not-accessible · current This entry defines the contents of the columns for the table 'lgpPwrThresholdTable'.
| |||||||||||||||||||||
| ClgpPwrThresholdIndex | 1.3.6.1.4.1.476.1.42.3.5.4.7.1.1 | Unsigned32 | NA | ||||||||||||||||||
column · Unsigned32 · not-accessible · current This is the index indicating the row of the table 'lgpPwrLineMeasurementTable' for a power measurement point. | |||||||||||||||||||||
| ClgpPwrThresholdPoint | 1.3.6.1.4.1.476.1.42.3.5.4.7.1.2 | OBJECT IDENTIFIER | RO | ||||||||||||||||||
column · OBJECT IDENTIFIER · read-only · current An OID representing a well known measurement point. These object identifiers indicate a point or location of power measurement in a power system. The OID's name usually implies a location of the measurement point such as 'input', 'output', 'bypass' etc. | |||||||||||||||||||||
| ClgpPwrThresholdSubID | 1.3.6.1.4.1.476.1.42.3.5.4.7.1.3 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current This is a sub identifier for the 'lgpPwrThresholdPoint'. It indicates the instance number of the well known threshold point. | |||||||||||||||||||||
| ClgpPwrThresholdType | 1.3.6.1.4.1.476.1.42.3.5.4.7.1.4 | OBJECT IDENTIFIER | RO | ||||||||||||||||||
column · OBJECT IDENTIFIER · read-only · current An OID representing a well known measurement type. These object identifiers indicate the type of measurement referenced by the row of the table. These object identifiers can encompass units of measure, lines of reference, and device location. The OID's name usually implies a measurement type such as 'voltsAc', 'current', 'voltsDc', 'VoltsLL', etc. | |||||||||||||||||||||
| ClgpPwrThresholdHighWarning | 1.3.6.1.4.1.476.1.42.3.5.4.7.1.5 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current The high warning threshold of a type of measurement designated by the 'lgpPwrThresholdType' at a location designated by the 'lgpPwrThresholdPoint'. If multiple thresholds are available at a single 'lgpPwrThresholdPoint', of the same 'lgpPwrThresholdType', then the 'lgpPwrThresholdSubID' will differentiate between them. When this threshold is met, the agent will send a notification. | |||||||||||||||||||||
| ClgpPwrThresholdHighFailure | 1.3.6.1.4.1.476.1.42.3.5.4.7.1.6 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current The high failure threshold of a type of measurement designated by the 'lgpPwrThresholdType' at a location designated by the 'lgpPwrThresholdPoint'. If multiple thresholds are available at a single 'lgpPwrThresholdPoint', of the same 'lgpPwrThresholdType', then the 'lgpPwrThresholdSubID' will differentiate between them. When this threshold is met, the agent will send a notification. | |||||||||||||||||||||
| ClgpPwrThresholdLowWarning | 1.3.6.1.4.1.476.1.42.3.5.4.7.1.7 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current The low warning threshold of a type of measurement designated by the 'lgpPwrThresholdType' at a location designated by the 'lgpPwrThresholdPoint'. If multiple thresholds are available at a single 'lgpPwrThresholdPoint', of the same 'lgpPwrThresholdType', then the 'lgpPwrThresholdSubID' will differentiate between them. When this threshold is met, the agent will send a notification. | |||||||||||||||||||||
| ClgpPwrThresholdLowFailure | 1.3.6.1.4.1.476.1.42.3.5.4.7.1.8 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current The low failure threshold of a type of measurement designated by the 'lgpPwrThresholdType' at a location designated by the 'lgpPwrThresholdPoint'. If multiple thresholds are available at a single 'lgpPwrThresholdPoint', of the same 'lgpPwrThresholdType', then the 'lgpPwrThresholdSubID' will differentiate between them. When this threshold is met, the agent will send a notification. | |||||||||||||||||||||
| SlgpPwrUpsAutoRestart | 1.3.6.1.4.1.476.1.42.3.5.4.8 | INTEGER | RW | on(1) | |||||||||||||||||
scalar · INTEGER · read-write · current The device will automatically restart when utility power is restored following a battery discharge.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SlgpPwrUpsAutoRestartDelay | 1.3.6.1.4.1.476.1.42.3.5.4.9 | Integer32 | RW | 0 | |||||||||||||||||
scalar · Integer32 · read-write · current The device will automatically delay a certain number of seconds and then restart after utility power is restored following a battery discharge. The number of seconds to delay is subject to the precision of the device and should be kept to 10 second intervals.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SlgpPwrAutoRestartBatteryChargeThreshold | 1.3.6.1.4.1.476.1.42.3.5.4.10 | Integer32 | RW | ||||||||||||||||||
scalar · Integer32 · read-write · current The battery charge percentage required before the device can automatically restart.
| |||||||||||||||||||||
| SlgpPwrParallelModuleCount | 1.3.6.1.4.1.476.1.42.3.5.4.11 | Integer32 | RW | ||||||||||||||||||
scalar · Integer32 · read-write · current The number of modules in the parallel system.
| |||||||||||||||||||||
| SlgpPwrParallelRedundancyCount | 1.3.6.1.4.1.476.1.42.3.5.4.12 | Integer32 | RW | ||||||||||||||||||
scalar · Integer32 · read-write · current The number of redundant modules in the parallel system.
| |||||||||||||||||||||
| SlgpPwrLoadBusSyncMode | 1.3.6.1.4.1.476.1.42.3.5.4.13 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current The configuration of Load Bus Synchronization (LBS) between independent systems.
| |||||||||||||||||||||
| SlgpPwrEconomicOperationMode | 1.3.6.1.4.1.476.1.42.3.5.4.14 | INTEGER | RW | on(1) | |||||||||||||||||
scalar · INTEGER · read-write · current The configuration of the economic operation mode of the system.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SlgpPwrAutomaticBatteryTest | 1.3.6.1.4.1.476.1.42.3.5.4.15 | INTEGER | RW | on(1) | |||||||||||||||||
scalar · INTEGER · read-write · current Automatic battery test option. If enabled, the battery will be tested on a fixed interval. If disabled, the battery test must be initiated by a battery test command. The interval at which a battery test is performed is defined by 'lgpPwrAutomaticBatteryTestInterval'.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SlgpPwrMinimumRedundantPowerModule | 1.3.6.1.4.1.476.1.42.3.5.4.16 | Integer32 | RW | ||||||||||||||||||
scalar · Integer32 · read-write · current The minimum number of redundant power modules that must be present before sending a loss of power redundancy alarm. If 0, there is no redundant power functionality.
| |||||||||||||||||||||
| SlgpPwrMinimumRedundantBatteryModule | 1.3.6.1.4.1.476.1.42.3.5.4.17 | Integer32 | RW | ||||||||||||||||||
scalar · Integer32 · read-write · current The minimum number of redundant battery modules that must be present before sending an alarm. If 0, the redundant battery module alarm is disabled.
| |||||||||||||||||||||
| SlgpPwrOutputToLoadUserOverloadLimit | 1.3.6.1.4.1.476.1.42.3.5.4.18 | Integer32 | RW | ||||||||||||||||||
scalar · Integer32 · read-write · current This is the user specified maximum load the device can support without sending an alarm.
| |||||||||||||||||||||
| SlgpPwrNoLoadWarningLimit | 1.3.6.1.4.1.476.1.42.3.5.4.19 | Integer32 | RW | ||||||||||||||||||
scalar · Integer32 · read-write · current The minimum current draw on the output in which the device considers there to be a load present on the output. The condition lgpConditionWarningNoLoadDetected will be triggered if the output current falls below this value. If this value is '-1' then the lgpConditionNoLoadDetectedWarning condition is 'disabled'.
| |||||||||||||||||||||
| SlgpPwrNoLoadWarningDelay | 1.3.6.1.4.1.476.1.42.3.5.4.20 | Integer32 (0..10000) | RW | ||||||||||||||||||
scalar · Integer32 (0..10000) · read-write · current The amount of time to delay before annunciation of the condition lgpConditionNoLoadDetectedWarning after the output current load falls below the threshold lgpPwrOutputNoLoadWarningLimit.
| |||||||||||||||||||||
| SlgpPwrEconomicOperationModeControl | 1.3.6.1.4.1.476.1.42.3.5.4.21 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current The configuration of the economic operation mode of the system. Note that this supersedes lgpPwrEconomicOperationMode in newer devices.
| |||||||||||||||||||||
| NlgpPwrConversion | 1.3.6.1.4.1.476.1.42.3.5.5 | ||||||||||||||||||||
node · current This sub-tree is used to register Liebert Power Conversion object identifiers. | |||||||||||||||||||||
| SlgpPwrNumberInstalledPowerModules | 1.3.6.1.4.1.476.1.42.3.5.5.1 | Integer32 | RO | ||||||||||||||||||
scalar · Integer32 · read-only · current The number of power modules installed in the device.
| |||||||||||||||||||||
| SlgpPwrNumberFailedPowerModules | 1.3.6.1.4.1.476.1.42.3.5.5.2 | Integer32 | RO | ||||||||||||||||||
scalar · Integer32 · read-only · current The number of power modules in the device that have failed.
| |||||||||||||||||||||
| SlgpPwrNumberRedundantPowerModules | 1.3.6.1.4.1.476.1.42.3.5.5.3 | Integer32 | RO | ||||||||||||||||||
scalar · Integer32 · read-only · current The number of redundant power modules installed in the device.
| |||||||||||||||||||||
| SlgpPwrNumberActivePowerModules | 1.3.6.1.4.1.476.1.42.3.5.5.4 | Integer32 | RO | ||||||||||||||||||
scalar · Integer32 · read-only · current The number of active power modules in the device.
| |||||||||||||||||||||
| SlgpPwrNumberPowerModuleWarnings | 1.3.6.1.4.1.476.1.42.3.5.5.6 | Integer32 | RO | ||||||||||||||||||
scalar · Integer32 · read-only · current The number of power modules in the device that have a warning.
| |||||||||||||||||||||
| SlgpPwrUpsInverterStandby | 1.3.6.1.4.1.476.1.42.3.5.5.7 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current The output to the load is supported by the bypass and the inverter is on standby.
| |||||||||||||||||||||
| NlgpPwrControl | 1.3.6.1.4.1.476.1.42.3.5.6 | ||||||||||||||||||||
node · current This sub-tree is used to register Liebert Power Control object identifiers. | |||||||||||||||||||||
| NlgpPwrWellKnownControlPoints | 1.3.6.1.4.1.476.1.42.3.5.6.1 | ||||||||||||||||||||
node · current This sub-tree registers well known Liebert Power Control Points. The object identifier names usually imply locations where control of a device is available -- such 'output' or 'load circuits'. | |||||||||||||||||||||
| NlgpPwrLoadCircuit | 1.3.6.1.4.1.476.1.42.3.5.6.1.1 | ||||||||||||||||||||
node · current The managed device's controllable load circuit. Many power systems contain more than one load circuit. This identifier represents one load circuit for the system but does not necessarily represent the 'first' one. The load circuits' numbering with respect to 'lgpPwrLoadCircuit1' etc. may depend on the physical wiring of the system when it was installed. | |||||||||||||||||||||
| TlgpPwrLoadCircuitTable | 1.3.6.1.4.1.476.1.42.3.5.6.2 | NA | |||||||||||||||||||
table · not-accessible · current A list of load circuits that can be controlled(opened or closed). The NMS cannot create or delete rows from the table. The rows are created by the agent based upon the capabilities of the managed device. | |||||||||||||||||||||
| RlgpPwrLoadCircuitEntry | 1.3.6.1.4.1.476.1.42.3.5.6.2.1 | NA | |||||||||||||||||||
row · not-accessible · current This entry defines the contents of the columns for the table 'lgpPwrLoadCircuitTable'. | |||||||||||||||||||||
| ClgpPwrLoadCircuitIndex | 1.3.6.1.4.1.476.1.42.3.5.6.2.1.1 | Unsigned32 | NA | ||||||||||||||||||
column · Unsigned32 · not-accessible · current This is the index indicating the row of the table 'lgpPwrLoadCircuitTable'. | |||||||||||||||||||||
| ClgpPwrLoadCircuitId | 1.3.6.1.4.1.476.1.42.3.5.6.2.1.2 | OBJECT IDENTIFIER | RO | 1.3.6.1.4.1.476.1.42.3.5.6.1.1 | |||||||||||||||||
column · OBJECT IDENTIFIER · read-only · current An OID representing a well known load circuit identifier. These load circuit identifiers indicate the name or type of load circuit reference in the table. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPwrLoadCircuitSubID | 1.3.6.1.4.1.476.1.42.3.5.6.2.1.3 | Unsigned32 | RO | 1 | |||||||||||||||||
column · Unsigned32 · read-only · current This is a sub identifier for the 'lgpPwrLoadCircuitId'. It indicates the hardware identifier of the load control circuit. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPwrLoadCircuitState | 1.3.6.1.4.1.476.1.42.3.5.6.2.1.4 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current This identifier indicates the state of the load circuit. When read, only a closed or open response will be returned. When written to, the state of the circuit will transition to desired state.
| |||||||||||||||||||||
| ClgpPwrLoadCircuitStateAndControl | 1.3.6.1.4.1.476.1.42.3.5.6.2.1.5 | INTEGER | RW | on(1) | |||||||||||||||||
column · INTEGER · read-write · current This identifier indicates the state of the load circuit. When read, only a closed or open response will be returned. When written to, the state of the circuit will transition to desired state.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SlgpPwrAlarmSilence | 1.3.6.1.4.1.476.1.42.3.5.6.3 | Integer32 | RW | 0 | |||||||||||||||||
scalar · Integer32 · read-write · current Audible Alarm Silence Command. This command turns off the device's audible alarm. It will not affect the status of the alarm(s) that caused the audible alarm. This command should be sent with a parameter of 1. This variable doesn't return a value when read. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SlgpPwrBatteryTest | 1.3.6.1.4.1.476.1.42.3.5.6.4 | INTEGER | RW | 0 | |||||||||||||||||
scalar · INTEGER · read-write · current Battery Test Command. This command will initiate a battery test if one is not already in progress, or abort the current test if it is in progress.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SlgpPwrUpsAbortCommand | 1.3.6.1.4.1.476.1.42.3.5.6.5 | Integer32 | RW | ||||||||||||||||||
scalar · Integer32 · read-write · current UPS Abort command. This command will abort the pending command on the device. There is no guarantee a client using the abort command will cancel a command sent moments before from the same client. Another client could initiate a command and change what command is actually pending on the device. This command should be sent with a parameter of 1. This variable doesn't return a value when read. | |||||||||||||||||||||
| SlgpPwrTransferToBypass | 1.3.6.1.4.1.476.1.42.3.5.6.6 | Integer32 | RW | ||||||||||||||||||
scalar · Integer32 · read-write · current Transfer to Bypass Command. This command will initiate a transfer of the load to the bypass of the system. This command should be sent with a parameter of 1. This variable doesn't return a value when read. | |||||||||||||||||||||
| SlgpPwrTransferToInverter | 1.3.6.1.4.1.476.1.42.3.5.6.7 | Integer32 | RW | ||||||||||||||||||
scalar · Integer32 · read-write · current Transfer to Inverter Command. This command will initiate a transfer of the load to the inverter of the system. This command should be sent with a parameter of 1. This variable doesn't return a value when read. | |||||||||||||||||||||
| SlgpPwrOutputOnDelay | 1.3.6.1.4.1.476.1.42.3.5.6.8 | Integer32 | RW | 0 | |||||||||||||||||
scalar · Integer32 · read-write · current Output On Delay Command. This command will turn on the output of the device after a user specified delay. The number of seconds to delay is subject to the precision of the device and should be kept to 10 second intervals.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SlgpPwrOutputOffDelayWithRestart | 1.3.6.1.4.1.476.1.42.3.5.6.9 | Integer32 | RW | 0 | |||||||||||||||||
scalar · Integer32 · read-write · current Output Off Delay with Restart Command. This command will turn off the output of the device after a user specified delay. The number of seconds to delay is subject to the precision of the device and should be kept to 10 second intervals. The device will then turn the output on again after a specified amount of time.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SlgpPwrOutputOffDelayWithoutRestart | 1.3.6.1.4.1.476.1.42.3.5.6.10 | Integer32 | RW | 0 | |||||||||||||||||
scalar · Integer32 · read-write · current Output Off Delay without Restart Command. This command will turn off the output of the device after a specified delay. The number of seconds to delay is subject to the precision of the device and should be kept to 10 second intervals. The device will NOT automatically turn the output on following this command.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NlgpPwrTopology | 1.3.6.1.4.1.476.1.42.3.5.7 | ||||||||||||||||||||
node · current This sub-tree is used to register Liebert Power Topology object identifiers. | |||||||||||||||||||||
| SlgpPwrUpsTopOffline | 1.3.6.1.4.1.476.1.42.3.5.7.1 | INTEGER | RO | no(2) | |||||||||||||||||
scalar · INTEGER · read-only · current The UPS has an offline topology. Under normal operating conditions, AC power from the utility passes straight through the UPS to the critical load. The inverter is used to convert the DC power from the battery to create AC power to support the load when the utility fails. Normally the inverter is operating in the stand-by mode, keeping the batteries charged. Should the utility power go out of specification, the inverter will power the load by drawing energy from the battery.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SlgpPwrUpsTopLineInteractive | 1.3.6.1.4.1.476.1.42.3.5.7.2 | INTEGER | RO | no(2) | |||||||||||||||||
scalar · INTEGER · read-only · current The UPS has a line-interactive topology. This topology resembles the offline product, but inserts a transformer or inductor in series between the utility power source and the load. This inline inductor enables the UPS inverter to interact with incoming power and provide a measure of power conditioning to the load. This buck-and-boost circuitry helps with high and low input voltage conditions.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SlgpPwrUPSTopDualInput | 1.3.6.1.4.1.476.1.42.3.5.7.3 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The system has separate input sources for the bypass and inverter.
| |||||||||||||||||||||
| SlgpPwrTopFrequencyConverter | 1.3.6.1.4.1.476.1.42.3.5.7.4 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The system has a frequency converter.
| |||||||||||||||||||||
| SlgpPwrTopVoltageConverter | 1.3.6.1.4.1.476.1.42.3.5.7.5 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The system has a voltage converter.
| |||||||||||||||||||||
| SlgpPwrTopMaximumFrameCapacity | 1.3.6.1.4.1.476.1.42.3.5.7.6 | Integer32 | RW | ||||||||||||||||||
scalar · Integer32 · read-write · current The maximum device system capacity.
| |||||||||||||||||||||
| SlgpPwrTopRedundantControlModules | 1.3.6.1.4.1.476.1.42.3.5.7.7 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The device has a redundant control module installed.
| |||||||||||||||||||||
| SlgpPwrInputIsolationTransformerInstalled | 1.3.6.1.4.1.476.1.42.3.5.7.8 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current Indicates whether the input isolation transformer is installed.
| |||||||||||||||||||||
| SlgpPwrStateStaticSwitchType | 1.3.6.1.4.1.476.1.42.3.5.7.9 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current Static switch type (N/A, continous duty, or momentary duty).
| |||||||||||||||||||||
| SlgpPwrStateModuleType | 1.3.6.1.4.1.476.1.42.3.5.7.10 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current UPS module type.
SMS -- Single Module System
1 + 1 -- Redundant system for capacity
1 + N -- Distributed multi-module system
N + 1 -- A multi-module system with one bypass for the system
SCC -- System Control Cabinet used in an N+1 system to
provide a single bypass for the system.
MSS -- Main Static Switch
| |||||||||||||||||||||
| SlgpPwrStateBypassInputConfig | 1.3.6.1.4.1.476.1.42.3.5.7.11 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current Bypass input wire physical wiring configuration.
singlePhase2WireL1WithReturn
Single phase input with 2 wires (Line 1, and Return).
twoPhase2WireL1L2
Two phase input with 2 wires (Line 1, and Line 2).
twoPhase3WireL1L2WithNeutral
Two phase input with 3 wires (Line 1, Line 2, and Neutral)
threePhase3WireL1L2L3
Three phase input with 3 wires (Line 1, Line 2, and Line 3)
threePhase4WireL1L2L3WithNeutral
Three phase input with 4 wires (Line 1, Line 2, Line 3, and
Neutral).
| |||||||||||||||||||||
| SlgpPwrStateOutputConfig | 1.3.6.1.4.1.476.1.42.3.5.7.12 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current Output wire physical wiring configuration.
singlePhase2WireL1WithReturn
Single phase output with 2 wires (Line 1, and Return).
twoPhase2WireL1L2
Two phase output with 2 wires (Line 1, and Line 2).
twoPhase3WireL1L2WithNeutral
Two phase output with 3 wires (Line 1, Line 2, and Neutral)
threePhase3WireL1L2L3
Three phase output with 3 wires (Line 1, Line 2, and Line 3)
threePhase4WireL1L2L3WithNeutral
Three phase output with 4 wires (Line 1, Line 2, Line 3, and
Neutral).
| |||||||||||||||||||||
| SlgpPwrRectifierPassiveFilterInstalled | 1.3.6.1.4.1.476.1.42.3.5.7.13 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current Indicates whether the rectifier passive filter is installed.
| |||||||||||||||||||||
| SlgpPwrRectifierTrapInstalled | 1.3.6.1.4.1.476.1.42.3.5.7.14 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current Indicates whether the rectifier input passive filter is installed.
| |||||||||||||||||||||
| SlgpPwrRectifierActiveFilterInstalled | 1.3.6.1.4.1.476.1.42.3.5.7.15 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current Indicates whether the rectifier active filter is installed.
| |||||||||||||||||||||
| NlgpPwrStatistic | 1.3.6.1.4.1.476.1.42.3.5.8 | ||||||||||||||||||||
node · current This sub-tree is used to register Liebert Power Statistic object identifiers. | |||||||||||||||||||||
| SlgpPwrBrownOutCount | 1.3.6.1.4.1.476.1.42.3.5.8.1 | Integer32 | RO | 0 | |||||||||||||||||
scalar · Integer32 · read-only · current The number of occurrences where the input line voltage has fallen below a pre-determined threshold for a specified amount of time. This number resets when the command 'lgpPwrStatisticsReset' is executed.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SlgpPwrBlackOutCount | 1.3.6.1.4.1.476.1.42.3.5.8.2 | Integer32 | RO | 4 | |||||||||||||||||
scalar · Integer32 · read-only · current The number of occurrences where there is a total loss of electric power. This number resets when the command 'lgpPwrStatisticsReset' is executed.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SlgpPwrTransientCount | 1.3.6.1.4.1.476.1.42.3.5.8.3 | Integer32 | RO | ||||||||||||||||||
scalar · Integer32 · read-only · current The number of occurrences where the input line voltage spikes above a pre-determined threshold for a specified amount of time. This number resets when the command 'lgpPwrStatisticsReset' is executed.
| |||||||||||||||||||||
| SlgpPwrBatteryDischargeCount | 1.3.6.1.4.1.476.1.42.3.5.8.4 | Integer32 | RO | ||||||||||||||||||
scalar · Integer32 · read-only · current The number of battery discharges since the last reset.
| |||||||||||||||||||||
| SlgpPwrBatteryDischargeTime | 1.3.6.1.4.1.476.1.42.3.5.8.5 | Integer32 | RO | 2147483647 | |||||||||||||||||
scalar · Integer32 · read-only · current The total accumulated time spent on battery since the last reset.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SlgpPwrBatteryAmpHours | 1.3.6.1.4.1.476.1.42.3.5.8.6 | Integer32 | RO | ||||||||||||||||||
scalar · Integer32 · read-only · current The total accumulated Amp-hours removed from the battery since last reset.
| |||||||||||||||||||||
| SlgpPwrBatteryWattHours | 1.3.6.1.4.1.476.1.42.3.5.8.7 | Integer32 | RO | ||||||||||||||||||
scalar · Integer32 · read-only · current The total accumulated Watt-Hours removed from the battery since last reset. This command should be sent with a parameter of 1. This variable doesn't return a value when read.
| |||||||||||||||||||||
| SlgpPwrBatteryStatisticsReset | 1.3.6.1.4.1.476.1.42.3.5.8.8 | Integer32 | RW | ||||||||||||||||||
scalar · Integer32 · read-write · current Battery statistics clear command. The command to reset all battery statistics stored by the device. This command should be sent with a parameter of 1. This variable doesn't return a value when read. | |||||||||||||||||||||
| SlgpPwrStatisticsReset | 1.3.6.1.4.1.476.1.42.3.5.8.9 | Integer32 | RW | 0 | |||||||||||||||||
scalar · Integer32 · read-write · current Reset Power Statistics Command. This command will reset the power statistics stored in the system. This command should be sent with a parameter of 1. This variable doesn't return a value when read. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NlgpPwrConfig | 1.3.6.1.4.1.476.1.42.3.5.9 | ||||||||||||||||||||
node · current This sub-tree is used to register Liebert Power Configuration Object identifiers. | |||||||||||||||||||||
| SlgpPwrSysCapacity | 1.3.6.1.4.1.476.1.42.3.5.9.1 | Integer32 | RW | ||||||||||||||||||
scalar · Integer32 · read-write · current The current device system capacity.
| |||||||||||||||||||||
| SlgpPwrUPSModuleMode | 1.3.6.1.4.1.476.1.42.3.5.9.2 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current The module mode of the UPS.
| |||||||||||||||||||||
| SlgpPwrMaxRatedCurrent | 1.3.6.1.4.1.476.1.42.3.5.9.3 | Integer32 | RO | ||||||||||||||||||
scalar · Integer32 · read-only · current System output maximum amperage rating. The maximum rated amperage for the system. This value is based upon the model type and is typically limited by the wiring, breakers, power devices, etc.
| |||||||||||||||||||||
| SlgpPwrRectifierPulseCount | 1.3.6.1.4.1.476.1.42.3.5.9.4 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current Rectifier pulse count per waveform cycle (6-, 12-, 18-, or 24-pulse).
| |||||||||||||||||||||