LIEBERT-GP-PDU-MIB
Vertiv (formerly 'Emerson Computer Power')The MIB module used to register Liebert POWER related SNMP OIDs. Copyright 2008-2008 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification.
snmptranslate -m LIEBERT-GP-PDU-MIB -Tpsnmpwalk -v2c -c <community> -m LIEBERT-GP-PDU-MIB <host> 1.3.6.1.4.1.476.1.42.1.9.1Imports
| LIEBERT-GP-REGISTRATION-MIB | lgpPdu, liebertPduModuleReg |
|---|---|
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
| SNMPv2-SMI | Bits, Integer32, IpAddress, MODULE-IDENTITY, MibIdentifier, OBJECT-IDENTITY, OBJECT-TYPE, TimeTicks, Unsigned32, iso |
| SNMPv2-TC | DisplayString, PhysAddress, TEXTUAL-CONVENTION |
OID tree
| Name | OID | Type | Access | Status | Example | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| IliebertGlobalProductsPduModule | 1.3.6.1.4.1.476.1.42.1.9.1 | ||||||||||||||||||||
identity The MIB module used to register Liebert POWER related SNMP OIDs. Copyright 2008-2008 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification. | |||||||||||||||||||||
| NlgpPduGlobalData | 1.3.6.1.4.1.476.1.42.3.8.5 | ||||||||||||||||||||
node · current This sub-tree contains data and control associated with PDU's controlled by this agent. Data in this sub-tree will affect the behavior of all PDU's controlled by this agent. | |||||||||||||||||||||
| SlgpPduEntrySWOverTemperatureProtectionConfig | 1.3.6.1.4.1.476.1.42.3.8.5.5 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current This configures the scope of behavior for the PDU Software Over
Temperature Protection feature.
See lgpPduRcpEntrySwOverTemperatureProtection to enable this feature
and get further information about what actions will be performed.
local (0)
Only receptacles on the PDU with the alarming temperature sensor
will be affected.
array (1)
All receptacles in the PDU array will be affected, regardless of
which PDU the alarming temperature sensor is connected to.
| |||||||||||||||||||||
| SlgpPduEntrySWOverTemperatureProtectionDelay | 1.3.6.1.4.1.476.1.42.3.8.5.10 | Unsigned32 | RW | ||||||||||||||||||
scalar · Unsigned32 · read-write · current This sets the delay for the PDU Software Over Temperature Protection feature. This value determines the amount of time to delay, after the high temperature alarm becomes active, before taking action on the enabled receptacles. If the high temperature alarm becomes inactive before the expiration of the delay time, no action will be taken on the enabled receptacles. See lgpPduRcpEntrySwOverTemperatureProtection to enable this feature and get further information about what actions will be performed.
| |||||||||||||||||||||
| NlgpPduCluster | 1.3.6.1.4.1.476.1.42.3.8.10 | ||||||||||||||||||||
node · current This sub-tree contains information about PDU clusters. Clusters are groups of PDU's under a single monitoring or control domain. | |||||||||||||||||||||
| SlgpPduGrpSysStatus | 1.3.6.1.4.1.476.1.42.3.8.10.5 | Unsigned32 | RO | ||||||||||||||||||
scalar · Unsigned32 · read-only · current This value represents a bit-field of the various operational
states of the PDUs that are part of the cluster of PDUs
being monitored by this agent.
This value is the bit-wise logical OR of all of the
'lgpPduEntrySysStatus' columns in the 'lgpPduTable'
which represents the combined statuses of all PDUs for this agent.
Note the bit-position is given parenthetically next to the operational
state in the description below. The bit position is big-endian
(least significant digit is the right-most digit). The state is
present in the PDU when the bit is on (value = 1).
The value is a logical OR of all of the following potential states of
each PDU in the cluster.
normalOperation(1)
One or more PDUs in the cluster are operating normally with no
active warnings or alarms.
startUp(2)
One or more PDUs are in the startup state (initializing). Control
and monitoring operations may be inhibited or unavailable
while the PDU is in this state. This state will clear
automatically when the PDU(s) are fully initialized and ready to
accept control and monitoring commands.
unknownNoSupport(4)
The state of one or more PDUs are not known at this time or
there is no support for this piece of information from 1 or more
PDUs in the cluster/group.
normalWithWarning(8)
One or more PDUs are operating normally with one or more active
warnings. Appropriate personnel should investigate the
warning(s) as soon as possible and take appropriate action.
normalWithAlarm(16)
One or more PDUs are operating normally with one or more active
alarms. Appropriate personnel should investigate the alarm(s)
as soon as possible and take appropriate action.
abnormalOperation(32)
One ore more PDUs are operating abnormally. There is a
failure within the system that is unexpected under normal
operating conditions. Appropriate personnel should investigate
the cause as soon as possible. The normal functioning of
the system is likely inhibited.
unknownCommFailure(64)
The state of one or more PDUs are not known due to a communications
failure between the PDU hardware and the communications
module. This state is usually indicative of a hardware
problem. | |||||||||||||||||||||
| SlgpPduTableCount | 1.3.6.1.4.1.476.1.42.3.8.19 | Unsigned32 | RO | ||||||||||||||||||
scalar · Unsigned32 · read-only · current Number of PDUs being monitored by this agent. This is the number of entries in the lgpPduTable.
| |||||||||||||||||||||
| TlgpPduTable | 1.3.6.1.4.1.476.1.42.3.8.20 | NA | |||||||||||||||||||
table · not-accessible · current This table contains a list of PDU entries. The table contains zero, one, or many rows, depending upon the number of PDUs being monitored. The Network Management System (NMS) cannot create or delete rows in the table. The rows are created by the agent based upon the number of PDUs being managed. Each row in the table represents a PDU in the system. | |||||||||||||||||||||
| RlgpPduEntry | 1.3.6.1.4.1.476.1.42.3.8.20.1 | NA | |||||||||||||||||||
row · not-accessible · current This entry defines the columns to be populated in the 'lgpPduTable'. Each column represents an attribute of a PDU. This table is indexed by the PDU identifier that is unique within the agent.
| |||||||||||||||||||||
| ClgpPduEntryIndex | 1.3.6.1.4.1.476.1.42.3.8.20.1.1 | Unsigned32 | NA | ||||||||||||||||||
column · Unsigned32 · not-accessible · current This is the index that indicates the row of the 'lgpPduTable'. | |||||||||||||||||||||
| ClgpPduEntryId | 1.3.6.1.4.1.476.1.42.3.8.20.1.5 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current This is an internal index representing a unique identifier for each PDU represented by this agent. The value is assigned by the agent. | |||||||||||||||||||||
| ClgpPduEntryUsrLabel | 1.3.6.1.4.1.476.1.42.3.8.20.1.10 | DisplayString | RW | ||||||||||||||||||
column · DisplayString · read-write · current This is a user assigned label representing the PDU. | |||||||||||||||||||||
| ClgpPduEntrySysAssignLabel | 1.3.6.1.4.1.476.1.42.3.8.20.1.15 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current System assigned identifier representing the PDU. The value is independent of any user assigned label or tag. The exact format of this label is system dependent and is subject to change, therefore, it should not be referenced for programmatic use. | |||||||||||||||||||||
| ClgpPduEntryPositionRelative | 1.3.6.1.4.1.476.1.42.3.8.20.1.20 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current This is a one-based value that indicates the PDU's relative position within a rack or other enclosing entity.
| |||||||||||||||||||||
| ClgpPduEntrySysStatus | 1.3.6.1.4.1.476.1.42.3.8.20.1.25 | Unsigned32 | RO | 16 | |||||||||||||||||
column · Unsigned32 · read-only · current This value represents a bit-field of the various operational
states of the PDU. The value is a logical OR of all of the
following potential states of the PDU. Note the bit-position
is given parenthetically next to the operational state in the
description below. The bit position is assumed to be a big-endian
format (least significant digit is the right-most digit). The
state is present in the PDU when the bit is on (value = 1).
normalOperation(1)
The PDU is operating normally with no active warnings or alarms.
startUp(2)
The PDU is in the startup state (initializing). Control
and monitoring operations maybe inhibited or unavailable
while the PDU is in this state. This state will clear
automatically when the PDU(s) are fully initialized and
ready to accept control and monitoring commands.
normalWithWarning(8)
The PDU is operating normally with one or more active
warnings. Appropriate personnel should investigate the
warning(s) as soon as possible and take appropriate action.
normalWithAlarm(16)
The PDU is operating normally with one or more active
alarms. Appropriate personnel should investigate the alarm(s)
as soon as possible and take appropriate action.
abnormalOperation(32)
The PDU is operating abnormally. That is there is some
failure within the system that is unexpected under normal
operating conditions. Appropriate personnel should investigate
the cause as soon as possible. The normal functioning of
the system is likely inhibited.Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduEntryUsrTag1 | 1.3.6.1.4.1.476.1.42.3.8.20.1.35 | DisplayString | RW | ||||||||||||||||||
column · DisplayString · read-write · current This is a user assigned Tag for the PDU. This value may be useful for end-user grouping or asset tracking purposes. The value for this tag does not need to be unique for this unit or across other units. | |||||||||||||||||||||
| ClgpPduEntryUsrTag2 | 1.3.6.1.4.1.476.1.42.3.8.20.1.40 | DisplayString | RW | ||||||||||||||||||
column · DisplayString · read-write · current This is a user assigned Tag for the PDU. This value may be useful for end-user grouping or asset tracking purposes. The value for this tag does not need to be unique for this unit or across other units. | |||||||||||||||||||||
| ClgpPduEntrySerialNumber | 1.3.6.1.4.1.476.1.42.3.8.20.1.45 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current System assigned serial number for this PDU. This number is assigned at time of manufacture, is globally unique with respect to all PDU units. | |||||||||||||||||||||
| ClgpPduEntryRbCount | 1.3.6.1.4.1.476.1.42.3.8.20.1.50 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current Number of receptacle branches (Rb) within this PDU.
| |||||||||||||||||||||
| ClgpPduEntrySWOverCurrentProtection | 1.3.6.1.4.1.476.1.42.3.8.20.1.55 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current This is the PDU Software Over Current Protection feature which will
prevent unused receptacles from turning on when the
'PDU Over Current Warning' or 'PDU Over Current Alarm' threshold
is violated. Such receptacles shall get locked to prevent any user
from switching them ON. Only device-admin shall have the authorization
to unlock such receptacles.
If the feature is enabled, in case of PDU Over Current Warning or Alarm condition,
following action will be taken on the receptacles:
a. Locked & OFF No change
b. Locked & ON - No change
c. UnLocked & OFF Receptacle shall be locked
d. Unlocked & ON If the receptacle is being used (current>0), no change.
If that outlet is being unused(current=0), turn it off and lock it in that position.
No action will be taken if the feature is disabled.
Note: Only applicable to PDU models where receptacle measurement and control is supported.
Not applicable for PDU models that support only branch monitoring.
disabled
This function is disabled.
enable
This function is enabled.
| |||||||||||||||||||||
| NlgpPduPowerSource | 1.3.6.1.4.1.476.1.42.3.8.30 | ||||||||||||||||||||
node · current This sub-tree contains information about PDU power sources. | |||||||||||||||||||||
| SlgpPduPsTableCount | 1.3.6.1.4.1.476.1.42.3.8.30.19 | Unsigned32 | RO | ||||||||||||||||||
scalar · Unsigned32 · read-only · current Number of power sources in the lgpPduPsTable.
| |||||||||||||||||||||
| TlgpPduPsTable | 1.3.6.1.4.1.476.1.42.3.8.30.20 | NA | |||||||||||||||||||
table · not-accessible · current This table contains a list of the PDU's power source(s). The table contains zero, one, or more rows, depending upon the number of PDUs being monitored and the number of power sources installed for each PDU. The NMS cannot create or delete rows in the table. The rows are created by the agent based upon the capabilities of the PDUs being monitored. Each row in the table represents a PDU's Power Source. | |||||||||||||||||||||
| RlgpPduPsEntry | 1.3.6.1.4.1.476.1.42.3.8.30.20.1 | NA | |||||||||||||||||||
row · not-accessible · current This entry defines the attributes to be populated in the various columns of the 'lgpPduPsTable' (Power Source Table). This table is indexed by both the 'lgpPduEntryIndex' which is the sole index into the 'lgpPduTable' and the 'lgpPduPsEntryIndex' which is a unique identifier for the Power Source within a given PDU. Taken together these two indexes uniquely identify a Power Source within this agent. | |||||||||||||||||||||
| ClgpPduPsEntryIndex | 1.3.6.1.4.1.476.1.42.3.8.30.20.1.5 | Unsigned32 | NA | ||||||||||||||||||
column · Unsigned32 · not-accessible · current This is a unique identifier for the Power Source within a given PDU. This is one of two indexes used to indicate the row of the 'lgpPduTable'. | |||||||||||||||||||||
| ClgpPduPsEntryId | 1.3.6.1.4.1.476.1.42.3.8.30.20.1.10 | Unsigned32 | RO | 1 | |||||||||||||||||
column · Unsigned32 · read-only · current This is a unique entry id representing a given PDU power source for the PDU. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduPsEntrySysAssignLabel | 1.3.6.1.4.1.476.1.42.3.8.30.20.1.15 | DisplayString | RO | PEM: 1-1 | |||||||||||||||||
column · DisplayString · read-only · current System assigned identifier for this power source. The value is independent of any user assigned label or tag. The exact format of this label is system dependent and is subject to change, therefore, it should not be referenced for programmatic use. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduPsEntryModel | 1.3.6.1.4.1.476.1.42.3.8.30.20.1.20 | DisplayString | RO | MPH-NCV27AXXD30 | |||||||||||||||||
column · DisplayString · read-only · current This is the model name (identifier) of the power supply. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduPsEntryWiringType | 1.3.6.1.4.1.476.1.42.3.8.30.20.1.25 | INTEGER | RW | single-phase-3-wire-L1-N-PE(1) | |||||||||||||||||
column · INTEGER · read-write · current The PDU's power supply physical wiring type.
not-specified
The type has not been specified/configured. The end_user
must configure this object to specify the physical wiring
type.
single-phase-3-wire-L1-N-PE
Single Phase input with 3 wires (Line 1, Neutral and
Protective Earth).
two-phase-3-wire-L1-L2-PE
Two Phase input with 3 wires (Line 1, Line 2, and
Protective Earth).
three-phase-4-wire-L1-L2-L3-PE
Three Phase input with 4 wires (Line 1, Line 2, Line 3,
and Protective Earth).
three-phase-5-wire-L1-L2-L3-N-PE
Three Phase input with 5 wires (Line 1, Line 2, Line 3,
Neutral and Protective Earth).
two-phase-4-wire-L1-L2-N-PE
Two Phase input with 4 wires (Line 1, Line 2, Neutral,
and Protective Earth).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduPsEntryEpInputRated | 1.3.6.1.4.1.476.1.42.3.8.30.20.1.30 | Unsigned32 | RO | 120 | |||||||||||||||||
column · Unsigned32 · read-only · current Rated Input Line Voltage for the power source (i.e. this is the nominal line input voltage; it is NOT a measured voltage). The value is defined to be the rated line voltage (either line-to-neutral or line-to-line depending upon the power source's type).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduPsEntryEcInputRated | 1.3.6.1.4.1.476.1.42.3.8.30.20.1.35 | Unsigned32 | RO | 300 | |||||||||||||||||
column · Unsigned32 · read-only · current This is the rated input line current for the module (it is NOT the measured current).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduPsEntryFreqRated | 1.3.6.1.4.1.476.1.42.3.8.30.20.1.40 | Unsigned32 | RO | 60 | |||||||||||||||||
column · Unsigned32 · read-only · current Rated input line frequency for this power source (i.e. This is the expected line frequency; it is NOT a measured frequency; it is typically 50 Hz or 60 Hz).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduPsEntryEnergyAccum | 1.3.6.1.4.1.476.1.42.3.8.30.20.1.50 | Unsigned32 | RW | 959375 | |||||||||||||||||
column · Unsigned32 · read-write · current Total accumulated energy, measured at the power source input, since the last energy reset. Writing a value of 0 (zero) to this causes the accumulated energy to be reset. Writing a non-zero value is invalid and shall result in a write error and the total energy value remains unchanged. If the energy has not been reset and has not wrapped, then this is the total energy since installation. This value persists across boot events.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduPsEntrySerialNum | 1.3.6.1.4.1.476.1.42.3.8.30.20.1.55 | DisplayString | RO | DM2013JUN240015 | |||||||||||||||||
column · DisplayString · read-only · current This is a unique serial number of the power supply. This number is assigned to the power supply at the time of manufacture. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduPsEntryFirmwareVersion | 1.3.6.1.4.1.476.1.42.3.8.30.20.1.60 | DisplayString | RO | 0-3-2-3 | |||||||||||||||||
column · DisplayString · read-only · current This is the version of the firmware installed on the PDU's power supply. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduPsEntryPwrTotal | 1.3.6.1.4.1.476.1.42.3.8.30.20.1.65 | Unsigned32 | RO | 2411 | |||||||||||||||||
column · Unsigned32 · read-only · current Total input power for this power supply. This is the sum of the power for all phases
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduPsEntryEcNeutral | 1.3.6.1.4.1.476.1.42.3.8.30.20.1.70 | Unsigned32 | RO | 204 | |||||||||||||||||
column · Unsigned32 · read-only · current The neutral current measured at the PDU's power source.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduPsEntryEcNeutralThrshldOvrWarn | 1.3.6.1.4.1.476.1.42.3.8.30.20.1.75 | Unsigned32 | RW | 75 | |||||||||||||||||
column · Unsigned32 · read-write · current The threshold at which an over current warning is activated. If the measured neutral current (lgpPduPsEntryEcNeutral) is above this percentage of the full scale rated value (lgpPduPsEntryEcInputRated), an over neutral current warning (lgpConditionSource1NeutralOverCurrent) is activated.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduPsEntryEcNeutralThrshldOvrAlarm | 1.3.6.1.4.1.476.1.42.3.8.30.20.1.80 | Unsigned32 | RW | 80 | |||||||||||||||||
column · Unsigned32 · read-write · current The threshold at which an over current alarm is activated. If the measured neutral current (lgpPduPsEntryEcNeutral) is above this percentage of the full scale rated value (lgpPduPsEntryEcInputRated), an over neutral current alarm (lgpConditionSource1NeutralOverCurrent) is activated.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduPsEntryUnbalancedLoadThrshldAlarm | 1.3.6.1.4.1.476.1.42.3.8.30.20.1.85 | Unsigned32 | RW | 0 | |||||||||||||||||
column · Unsigned32 · read-write · current The parameter is for setting the maximum acceptable percentage of 'Unbalanced Load' between any two phases. This setting shall trigger an alarm when the % load between any two phases varies by a percentage higher than this configurable value. If this value is 0% then the alarm would be deactivated.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduPsEntryApTotal | 1.3.6.1.4.1.476.1.42.3.8.30.20.1.90 | Unsigned32 | RO | 551 | |||||||||||||||||
column · Unsigned32 · read-only · current Total Apparent power for this power supply. This is the sum of the apparent power for all phases
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduPsEntryPfTotal | 1.3.6.1.4.1.476.1.42.3.8.30.20.1.95 | Integer32 | RO | 0 | |||||||||||||||||
column · Integer32 · read-only · current Total power factor, which is real power/apparent power for all phases combined. This is the sum of the real power for all phases divided by the sum of the apparent power for all phases.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduPsEntryEcResidual | 1.3.6.1.4.1.476.1.42.3.8.30.20.1.100 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The measured residual current.
| |||||||||||||||||||||
| ClgpPduPsEntryEcResidualThrshldOvrAlarm | 1.3.6.1.4.1.476.1.42.3.8.30.20.1.105 | Unsigned32 | RW | ||||||||||||||||||
column · Unsigned32 · read-write · current The threshold at which an over current alarm is activated. If the measured residual current (lgpPduPsEntryEcResidual) is above this value, an over current alarm is activated. Setting this to 0mA disables the alarm.
| |||||||||||||||||||||
| TlgpPduPsLineTable | 1.3.6.1.4.1.476.1.42.3.8.30.40 | NA | |||||||||||||||||||
table · not-accessible · current This table contains a list of PDU's power source line/phase measurements. The table contains zero, one, or many rows, depending upon the number of PDU's Power Sources being monitored. The NMS cannot create or delete rows in the table. The rows are created by the agent based upon the capabilities of the managed PDU's power supply(s). Each row in the table represents a particular phase/line measurement of a power supply for a given PDU. | |||||||||||||||||||||
| RlgpPduPsLineEntry | 1.3.6.1.4.1.476.1.42.3.8.30.40.1 | NA | |||||||||||||||||||
row · not-accessible · current This entry defines the attributes to be populated in the various columns of the 'lgpPduPsLineTable'. The table is index by three indexes which taken together uniquely identify line/phase information for a given power source within a PDU. The 'lgpPduEntryIndex' is an index into the 'lgpPduTable'. This identifies the PDU that the power source is on. The 'lgpPduPsEntryIndex' is an index that together with the 'lgpPduEntryIndex' uniquely identifies the power source within the PDU that the row in this table represents. The final index 'lgpPduPsLineEntryIndex' identifies the particular line/phase that the measurement applies to within the identified power source. | |||||||||||||||||||||
| ClgpPduPsLineEntryIndex | 1.3.6.1.4.1.476.1.42.3.8.30.40.1.5 | Unsigned32 | NA | ||||||||||||||||||
column · Unsigned32 · not-accessible · current This is the index that indicates the line/phase of the measurements in the given row of the 'lgpPduPsLineTable'. | |||||||||||||||||||||
| ClgpPduPsLineEntryId | 1.3.6.1.4.1.476.1.42.3.8.30.40.1.10 | Unsigned32 | RO | 1 | |||||||||||||||||
column · Unsigned32 · read-only · current Unique identifier (within a PDU) for the PDU's power source. The object may not be available in non-modular systems. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduPsLineEntryLine | 1.3.6.1.4.1.476.1.42.3.8.30.40.1.15 | INTEGER | RO | phase1(1) | |||||||||||||||||
column · INTEGER · read-only · current The line number (phase) that the measurement represents for all
measurements in a given row of the table. Note that this always
matches the lgpPduPsLineEntryIndex of the same row in the table.
The line/phases are as follows:
Line# Description
----- ---------------------------------------------------
1 Line 1-N (A) for Line-to-Neutral measurements
2 Line 2-N (B) for Line-to-Neutral measurements
3 Line 3-N (C) for Line-to-Neutral measurements
1 Line 1-2 (A-B) for Line-to-Line measurements
2 Line 2-3 (B-C) for Line-to-Line measurements
3 Line 3-1 (C-A) for Line-to-Line measurements
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduPsLineEntryEpLNTenths | 1.3.6.1.4.1.476.1.42.3.8.30.40.1.19 | Unsigned32 | RO | 1196 | |||||||||||||||||
column · Unsigned32 · read-only · current Alternating Current RMS Line to Neutral Electrical Potential measurement. The line/phase being measured is indicated by the corresponding lgpPduPsLineEntryLine value of this row in the table.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduPsLineEntryEpLN | 1.3.6.1.4.1.476.1.42.3.8.30.40.1.20 | Unsigned32 | RO | 119 | |||||||||||||||||
column · Unsigned32 · read-only · current Alternating Current RMS Line to Neutral Electrical Potential measurement. The line/phase being measured is indicated by the corresponding lgpPduPsLineEntryLine value of this row in the table.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduPsLineEntryEc | 1.3.6.1.4.1.476.1.42.3.8.30.40.1.21 | Unsigned32 | RO | 204 | |||||||||||||||||
column · Unsigned32 · read-only · current Total input line-to-neutral electrical current. The line/phase being measured is indicated by the corresponding lgpPduPsLineEntryLine value of this row in the table.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduPsLineEntryEcHundredths | 1.3.6.1.4.1.476.1.42.3.8.30.40.1.22 | Unsigned32 | RO | 2045 | |||||||||||||||||
column · Unsigned32 · read-only · current Total input line-to-neutral electrical current. The line/phase being measured is indicated by the corresponding lgpPduPsLineEntryLine value of this row in the table.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduPsLineEntryEcThrshldUndrAlarm | 1.3.6.1.4.1.476.1.42.3.8.30.40.1.35 | Unsigned32 | RW | 0 | |||||||||||||||||
column · Unsigned32 · read-write · current The threshold at which an under current alarm is activated. If the measured current (lgpPduPsLineEntryEc) is equal to or below this percentage of the full scale rated value (lgpPduPsEntryEcInputRated), an under current alarm is activated.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduPsLineEntryEcThrshldOvrWarn | 1.3.6.1.4.1.476.1.42.3.8.30.40.1.36 | Unsigned32 | RW | 75 | |||||||||||||||||
column · Unsigned32 · read-write · current The threshold at which an over current warning is activated. If the measured current (lgpPduPsLineEntryEc) is equal to or over this percentage of the full scale rated value (lgpPduPsEntryEcInputRated), an over current warning is activated.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduPsLineEntryEcThrshldOvrAlarm | 1.3.6.1.4.1.476.1.42.3.8.30.40.1.37 | Unsigned32 | RW | 80 | |||||||||||||||||
column · Unsigned32 · read-write · current The threshold at which an over current alarm is activated. If the measured current (lgpPduPsLineEntryEc) is equal to or over this percentage of the full scale rated value (lgpPduPsEntryEcInputRated), an over current alarm is activated.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduPsLineEntryEcAvailBeforeAlarm | 1.3.6.1.4.1.476.1.42.3.8.30.40.1.38 | Unsigned32 | RO | 35 | |||||||||||||||||
column · Unsigned32 · read-only · current The amount that the current/amperage may increase from its present value before an over current alarm occurs.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduPsLineEntryEcUsedBeforeAlarm | 1.3.6.1.4.1.476.1.42.3.8.30.40.1.39 | Unsigned32 | RO | 682 | |||||||||||||||||
column · Unsigned32 · read-only · current The percent of current utilization relative to the over current alarm threshold.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduPsLineEntryEpLL | 1.3.6.1.4.1.476.1.42.3.8.30.40.1.60 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current Line to Line Electrical Potential. The line/phase being measured is indicated by the corresponding lgpPduPsLineEntryLine value of this row in the table.
| |||||||||||||||||||||
| ClgpPduPsLineEntryEpLLTenths | 1.3.6.1.4.1.476.1.42.3.8.30.40.1.61 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current Line to Line Electrical Potential. The line/phase being measured is indicated by the corresponding lgpPduPsLineEntryLine value of this row in the table.
| |||||||||||||||||||||
| ClgpPduPsLineEntryEcAvailBeforeAlarmHundredths | 1.3.6.1.4.1.476.1.42.3.8.30.40.1.62 | Unsigned32 | RO | 355 | |||||||||||||||||
column · Unsigned32 · read-only · current The amount that the current/amperage may increase from its present value before an over current alarm occurs.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduPsLineEntryPwrLN | 1.3.6.1.4.1.476.1.42.3.8.30.40.1.63 | Unsigned32 | RO | 498 | |||||||||||||||||
column · Unsigned32 · read-only · current The line-to-neutral measurement of the Real Power (Watts). The line/phase being measured is indicated by the corresponding lgpPduPsLineEntryLine value of this row in the table.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduPsLineEntryPwrLL | 1.3.6.1.4.1.476.1.42.3.8.30.40.1.64 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The line-to-line measurement of the Real Power (Watts). The line/phase being measured is indicated by the corresponding lgpPduPsLineEntryLine value of this row in the table.
| |||||||||||||||||||||
| ClgpPduPsLineEntryApLN | 1.3.6.1.4.1.476.1.42.3.8.30.40.1.65 | Unsigned32 | RO | 556 | |||||||||||||||||
column · Unsigned32 · read-only · current The line-to-neutral measurement of the Apparent Power (VA). The line/phase being measured is indicated by the corresponding lgpPduPsLineEntryLine value of this row in the table.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduPsLineEntryApLL | 1.3.6.1.4.1.476.1.42.3.8.30.40.1.66 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The line-to-line measurement of the Apparent Power (VA). The line/phase being measured is indicated by the corresponding lgpPduPsLineEntryLine value of this row in the table.
| |||||||||||||||||||||
| ClgpPduPsLineEntryPfLN | 1.3.6.1.4.1.476.1.42.3.8.30.40.1.67 | Integer32 | RO | 91 | |||||||||||||||||
column · Integer32 · read-only · current The line-to-neutral measurement of the Power Factor of the power source. The line/phase being measured is indicated by the corresponding lgpPduPsLineEntryLine value of this row in the table.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduPsLineEntryPfLL | 1.3.6.1.4.1.476.1.42.3.8.30.40.1.68 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The line-to-line measurement of the Power Factor of the power source. The line/phase being measured is indicated by the corresponding lgpPduPsLineEntryLine value of this row in the table.
| |||||||||||||||||||||
| NlgpPduReceptacleBranch | 1.3.6.1.4.1.476.1.42.3.8.40 | ||||||||||||||||||||
node · current This sub-tree contains information about PDU receptacle branches. | |||||||||||||||||||||
| SlgpPduRbTableCount | 1.3.6.1.4.1.476.1.42.3.8.40.19 | Unsigned32 | RO | ||||||||||||||||||
scalar · Unsigned32 · read-only · current Number of receptacle branches in the lgpPduRbTable.
| |||||||||||||||||||||
| TlgpPduRbTable | 1.3.6.1.4.1.476.1.42.3.8.40.20 | NA | |||||||||||||||||||
table · not-accessible · current This table contains a list of PDU Receptacle branches. The table contains zero, one, or many rows, depending upon the number of PDUs being managed and how many receptacle branches each PDU has installed. The NMS cannot create or delete rows in the table. The rows are created by the agent based upon the capabilities of the PDUs being managed. Each row in the table represents a receptacle branch for a given PDU. The PDU that a branch is installed on is indicated by the column lgpPduEntryIndex. The branch within the lgpPduEntryIndex PDU is indicated by the column lgpPduRbEntryIndex. | |||||||||||||||||||||
| RlgpPduRbEntry | 1.3.6.1.4.1.476.1.42.3.8.40.20.1 | NA | |||||||||||||||||||
row · not-accessible · current This entry defines the attributes to be populated in the various columns of the 'lgpPduRbTable'. The table is indexed by both the 'lgpPduEntryIndex' and 'lgpPduRbEntryIndex'. The lgpPduEntryIndex specifies the PDU, defined in the lgpPduTable that the branch is on. The lgpPduRbEntryIndex uniquely identifies the branch within that PDU. Taken together the two indexes uniquely identify a branch being monitored by this agent. | |||||||||||||||||||||
| ClgpPduRbEntryIndex | 1.3.6.1.4.1.476.1.42.3.8.40.20.1.1 | Unsigned32 | NA | ||||||||||||||||||
column · Unsigned32 · not-accessible · current This is the index that indicates the row of the 'lgpPduRbTable' | |||||||||||||||||||||
| ClgpPduRbEntryId | 1.3.6.1.4.1.476.1.42.3.8.40.20.1.5 | Unsigned32 | RO | 1 | |||||||||||||||||
column · Unsigned32 · read-only · current A unique id representing the receptacle branch within the collection of branches being monitored by this agent. The uniqueness of this id is within the PDUs being managed by a single agent. | |||||||||||||||||||||
| ClgpPduRbEntryUsrLabel | 1.3.6.1.4.1.476.1.42.3.8.40.20.1.8 | DisplayString | RW | Branch 1 | |||||||||||||||||
| ClgpPduRbEntrySysAssignLabel | 1.3.6.1.4.1.476.1.42.3.8.40.20.1.20 | DisplayString | RO | 1-1 | |||||||||||||||||
column · DisplayString · read-only · current System assigned identifier for this receptacle branch. The value is independent of any user assigned label or tag. The exact format of this label is system dependent and is subject to change, therefore, it should not be referenced for programmatic use. | |||||||||||||||||||||
| ClgpPduRbEntryPositionRelative | 1.3.6.1.4.1.476.1.42.3.8.40.20.1.25 | Unsigned32 | RO | 1 | |||||||||||||||||
| ClgpPduRbEntrySerialNum | 1.3.6.1.4.1.476.1.42.3.8.40.20.1.30 | DisplayString | RO | DM2013JUN240015-B1 | |||||||||||||||||
column · DisplayString · read-only · current A globally unique serial number for this branch. This number is assigned to the branch at the time of manufacture and can not be modified. NOTE: Generally only PDUs with replaceable receptacle branches will have serial numbers. | |||||||||||||||||||||
| ClgpPduRbEntryModel | 1.3.6.1.4.1.476.1.42.3.8.40.20.1.35 | DisplayString | RO | MPH-NCV27AXXD30 | |||||||||||||||||
column · DisplayString · read-only · current This is the model designation for this receptacle branch. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRbEntryFirmwareVersion | 1.3.6.1.4.1.476.1.42.3.8.40.20.1.40 | DisplayString | RO | 0-3-2-3 | |||||||||||||||||
column · DisplayString · read-only · current This is the firmware version number of the control software running on the receptacle branch. Only PDUs with replaceable receptacle branches will typically support this object. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRbEntryUsrTag1 | 1.3.6.1.4.1.476.1.42.3.8.40.20.1.41 | DisplayString | RW | | |||||||||||||||||
column · DisplayString · read-write · current This is a user assigned Tag for the receptacle branch. This value may be useful for end-user grouping or asset tracking purposes. The value for this tag does not need to be unique for this unit or across other units. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRbEntryUsrTag2 | 1.3.6.1.4.1.476.1.42.3.8.40.20.1.42 | DisplayString | RW | | |||||||||||||||||
column · DisplayString · read-write · current This is a user assigned Tag for the receptacle branch. This value may be useful for end-user grouping or asset tracking purposes. The value for this tag does not need to be unique for this unit or across other units. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRbEntryReceptacleType | 1.3.6.1.4.1.476.1.42.3.8.40.20.1.45 | INTEGER | RO | nema-5-20R-20-Amp(1) | |||||||||||||||||
column · INTEGER · read-only · current This enumeration represents the type of receptacles installed
on this receptacle branch. All receptacles on this branch are
of this type/style.
not-specified
If this value is returned, either the receptacle type has
not been specified/configured or the agent monitoring this
PDU does not have a SNMP enumeration defined to the type.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRbEntryCapabilities | 1.3.6.1.4.1.476.1.42.3.8.40.20.1.50 | INTEGER | RO | current-measurement-and-control(6) | |||||||||||||||||
column · INTEGER · read-only · current Receptacle branch capabilities describes what an individual branch
is capable of.
no-optional-capabilities
The branch is unable to report measurements and lacks
control capabilities.
measurement-only
The branch is capable of reporting multiple measurements.
measurement-and-control
The branch is capable of reporting multiple measurements
and controlling the state.
control-only
The branch is capable of controlling the state.
current-measurement-only
The branch is capable of reporting the current/amperage only.
current-measurement-and-control
The branch is capable of reporting the current/amperage and
has the ability to control the state.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRbEntryLineSource | 1.3.6.1.4.1.476.1.42.3.8.40.20.1.55 | INTEGER | RO | line-1-neutral(1) | |||||||||||||||||
column · INTEGER · read-only · current This represents the line source that is supplying power to this
receptacle branch.
not-specified
The line source supplying power to the load for this
receptacle branch has not been specified/configured.
line-1-N
The load for this receptacle branch is supplied by
a line-to-neutral configuration. (line 1 to neutral).
line-2-N
The load for this receptacle branch is supplied by
a line-to-neutral configuration. (line 2 to neutral).
line-3-N
The load for this receptacle branch is supplied by
a line-to-neutral configuration. (line 3 to neutral).
line-1-line-2
The load for this receptacle branch is supplied by
a line-to-line configuration (line 1 to line 2).
line-2-line-3
The load for this receptacle branch is supplied by
a line-to-line configuration (line 2 to line 3).
line-3-line-1
The load for this receptacle branch is supplied by
a line-to-line configuration (line 3 to line 1).
line-1-line-2-and-line-1-neutral
The load for this mixed receptacle branch is supplied by
a line-to-line and line-to-neutral configuration
(line 1 to line 2 and line 1 to neutral).
line-2-line-3-and-line-2-neutral
The load for this mixed receptacle branch is supplied by
a line-to-line and line-to-neutral configuration
(line 2 to line 3 and line 2 to neutral).
line-3-line-1-and-line-3-neutral
The load for this mixed receptacle branch is supplied by
a line-to-line and line-to-neutral configuration
(line 3 to line 1 and line 3 to neutral).
unknown-line-neutral
The load for this branch is supplied by
a line-to-neutral configuration. The system is unable to
determine which lines are supporting the load.
unknown-line-line
The load for this branch is supplied by
a line-to-line configuration. The system is unable to
determine which lines are supporting the load.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRbEntryRcpCount | 1.3.6.1.4.1.476.1.42.3.8.40.20.1.60 | Unsigned32 | RO | 9 | |||||||||||||||||
column · Unsigned32 · read-only · current The number of receptacles on this receptacle branch.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRbEntryEpRated | 1.3.6.1.4.1.476.1.42.3.8.40.20.1.70 | Unsigned32 | RO | 120 | |||||||||||||||||
column · Unsigned32 · read-only · current Rated Line Voltage for the receptacle branch and its associated receptacles (i.e. This is the nominal line voltage that is available to the connected load; it is NOT a measured voltage.)
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRbEntryEcRated | 1.3.6.1.4.1.476.1.42.3.8.40.20.1.75 | Unsigned32 | RO | 200 | |||||||||||||||||
column · Unsigned32 · read-only · current This is the rated input line current for the module (it is NOT the measured current).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRbEntryFreqRated | 1.3.6.1.4.1.476.1.42.3.8.40.20.1.80 | Unsigned32 | RO | 60 | |||||||||||||||||
column · Unsigned32 · read-only · current This is the rated electrical frequency for the receptacle branch and its associated receptacles
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRbEntryEnergyAccum | 1.3.6.1.4.1.476.1.42.3.8.40.20.1.85 | Unsigned32 | RW | 20452 | |||||||||||||||||
column · Unsigned32 · read-write · current Total accumulated energy, measured at the receptacle branch input, since the last energy reset. Writing a value of 0 (zero) to this causes the accumulated energy to be reset. Writing a non-zero value is invalid and shall result in a write error and the total energy value remains unchanged. If the energy has not been reset and has not wrapped, then this is the total energy since installation. This value persists across boot events. NOTE: Resetting this value does not reset the values for the individual receptacles.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRbEntryEpLNTenths | 1.3.6.1.4.1.476.1.42.3.8.40.20.1.100 | Unsigned32 | RO | 2385 | |||||||||||||||||
column · Unsigned32 · read-only · current The line-to-neutral measurement of the Electrical Potential measured in Volts RMS (Root Mean Squared).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRbEntryPwr | 1.3.6.1.4.1.476.1.42.3.8.40.20.1.115 | Unsigned32 | RO | 508 | |||||||||||||||||
column · Unsigned32 · read-only · current The line-to-neutral measurement of the Real Power (Wattage)
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRbEntryAp | 1.3.6.1.4.1.476.1.42.3.8.40.20.1.120 | Unsigned32 | RO | 553 | |||||||||||||||||
column · Unsigned32 · read-only · current The line-to-neutral measurement of the Apparent Power (VA)
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRbEntryPf | 1.3.6.1.4.1.476.1.42.3.8.40.20.1.125 | Integer32 | RO | 91 | |||||||||||||||||
column · Integer32 · read-only · current The line-to-neutral measurement of the Power Factor of the receptacle branches' input.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRbEntryEcHundredths | 1.3.6.1.4.1.476.1.42.3.8.40.20.1.130 | Unsigned32 | RO | 1428 | |||||||||||||||||
| ClgpPduRbEntryEcThrshldUndrAlm | 1.3.6.1.4.1.476.1.42.3.8.40.20.1.135 | Unsigned32 | RW | 0 | |||||||||||||||||
column · Unsigned32 · read-write · current The threshold at which an under current alarm is activated. If the measured current (lgpPduRbEntryEc) is equal to or below this percentage of the full scale rated value (lgpPduRbEntryEcRated), an under current alarm is activated
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRbEntryEcThrshldOvrWarn | 1.3.6.1.4.1.476.1.42.3.8.40.20.1.140 | Unsigned32 | RW | 90 | |||||||||||||||||
column · Unsigned32 · read-write · current The threshold at which an over current warning is activated. If the measured current (lgpPduRbEntryEc) is equal to or over this percentage of the full scale rated value (lgpPduRbEntryEcRated), an over current warning is activated
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRbEntryEcThrshldOvrAlm | 1.3.6.1.4.1.476.1.42.3.8.40.20.1.145 | Unsigned32 | RW | 95 | |||||||||||||||||
column · Unsigned32 · read-write · current The threshold at which an over current alarm is activated. If the measured current (lgpPduRbEntryEcLN) is equal to or over this percentage of the full scale rated value (lgpPduRbEntryEcRated), an over current alarm is activated
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRbEntryEcAvailBeforeAlarmHundredths | 1.3.6.1.4.1.476.1.42.3.8.40.20.1.150 | Unsigned32 | RO | 471 | |||||||||||||||||
column · Unsigned32 · read-only · current The amount that the current/amperage may increase from its present value before an over current alarm occurs.
| |||||||||||||||||||||
| ClgpPduRbEntryEcUsedBeforeAlarm | 1.3.6.1.4.1.476.1.42.3.8.40.20.1.160 | Unsigned32 | RO | 714 | |||||||||||||||||
| ClgpPduRbEntryEpLLTenths | 1.3.6.1.4.1.476.1.42.3.8.40.20.1.170 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current The line-to-line measurement of the Electrical Potential measured in Volts RMS (Root Mean Squared).
| |||||||||||||||||||||
| ClgpPduRbEntrySwOverCurrentProtection | 1.3.6.1.4.1.476.1.42.3.8.40.20.1.175 | INTEGER | RW | disable(0) | |||||||||||||||||
column · INTEGER · read-write · current The configuration parameter to enable or disable the Branch
SW Over Current Protection feature.If the feature is enabled, in case of Over Current Warning or Alarm condition, following action will be taken on the receptacles:
Locked & On - No Change
Locked & Off - No Change
Unlocked & Off - Turn it Off and Lock it
Unlocked & On - If load present, No Change. If no load, turn it Off and Lock it.
No action will be taken if the feature is disabled.
Note: Only applicable to PDU models where receptacle measurement and control is possible. Not applicable to branch monoitoring models
disabled
This function is disabled.
enable
This function is enabled.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| TlgpPduRbLineTable | 1.3.6.1.4.1.476.1.42.3.8.40.40 | NA | deprecated | ||||||||||||||||||
table · not-accessible · deprecated This table contains a list of PDU receptacle branch line/phase measurements. The table contains zero, one, or many rows, depending upon the number of PDUs and the number of receptacle branches on each PDU that are being monitored. The NMS cannot create or delete rows in the table. The rows are created by the agent based upon the capabilities of the PDU(s) being monitored. Each row in the table represents a particular phase/line measurement of a PDU Receptacle Branch. Rows in the table are uniquely identified by three indexes representing respectively the PDU (lgpPduEntryIndex), the receptacle branch (lgpPduRbEntryIndex) and the line/phase being measured (lgpPduRbLineEntryIndex). | |||||||||||||||||||||
| RlgpPduRbLineEntry | 1.3.6.1.4.1.476.1.42.3.8.40.40.1 | NA | deprecated | ||||||||||||||||||
row · not-accessible · deprecated This entry defines the attributes to be populated in the various columns of the 'lgpPduRbLineTable'. The table is indexed by three indexes. The 'lgpPduEntryIndex' references a PDU in the 'lgpPduTable' to which this receptacle branch line/phase measurement belongs. The 'lgpPduRbEntryIndex' together with the 'lgpPduEntryIndex' references the receptacle branch in the 'lgpPduRbTable'. The 'lgpPduRbLineEntryIndex' represents the line/phase of the measurements in the row of this table. Together these three indexes uniquely identify a phase/line measurement on a receptacle branch within a PDU being monitored by this agent. | |||||||||||||||||||||
| ClgpPduRbLineEntryIndex | 1.3.6.1.4.1.476.1.42.3.8.40.40.1.1 | Unsigned32 | NA | deprecated | |||||||||||||||||
column · Unsigned32 · not-accessible · deprecated This is the index that indicates the row of the 'lgpPduRbLineTable' | |||||||||||||||||||||
| ClgpPduRbLineEntryId | 1.3.6.1.4.1.476.1.42.3.8.40.40.1.5 | Unsigned32 | RO | deprecated | |||||||||||||||||
column · Unsigned32 · read-only · deprecated Runtime assigned branch identifier. | |||||||||||||||||||||
| ClgpPduRbLineEntryLine | 1.3.6.1.4.1.476.1.42.3.8.40.40.1.10 | INTEGER | RO | deprecated | |||||||||||||||||
column · INTEGER · read-only · deprecated The line number or phase that the measurement for this
receptacle branch represents for each measurement in this row of
the table. The phases are as follows:
Line# Description
----- ---------------------------------------------------
1 Line 1-N (A) for Line-to-Neutral measurements
2 Line 2-N (B) for Line-to-Neutral measurements
3 Line 3-N (C) for Line-to-Neutral measurements
1 Line 1-2 (A-B) for Line-to-Line measurements
2 Line 2-3 (B-C) for Line-to-Line measurements
3 Line 3-1 (C-A) for Line-to-Line measurements
| |||||||||||||||||||||
| ClgpPduRbLineEntryEpLNTenths | 1.3.6.1.4.1.476.1.42.3.8.40.40.1.19 | Unsigned32 | RO | deprecated | |||||||||||||||||
column · Unsigned32 · read-only · deprecated The line-to-neutral measurement of the Electrical Potential measured in Volts RMS (Root Mean Squared).
| |||||||||||||||||||||
| ClgpPduRbLineEntryEpLN | 1.3.6.1.4.1.476.1.42.3.8.40.40.1.20 | Unsigned32 | RO | deprecated | |||||||||||||||||
column · Unsigned32 · read-only · deprecated The line-to-neutral measurement of the Electrical Potential measured in Volts RMS (Root Mean Squared).
| |||||||||||||||||||||
| ClgpPduRbLineEntryEc | 1.3.6.1.4.1.476.1.42.3.8.40.40.1.21 | Unsigned32 | RO | deprecated | |||||||||||||||||
column · Unsigned32 · read-only · deprecated The line-to-neutral measurement of the Electrical Current measured in Amperes RMS (Root Mean Squared).
| |||||||||||||||||||||
| ClgpPduRbLineEntryPwr | 1.3.6.1.4.1.476.1.42.3.8.40.40.1.22 | Unsigned32 | RO | deprecated | |||||||||||||||||
column · Unsigned32 · read-only · deprecated The line-to-neutral measurement of the Real Power (Wattage)
| |||||||||||||||||||||
| ClgpPduRbLineEntryAp | 1.3.6.1.4.1.476.1.42.3.8.40.40.1.23 | Unsigned32 | RO | deprecated | |||||||||||||||||
column · Unsigned32 · read-only · deprecated The line-to-neutral measurement of the Apparent Power (VA)
| |||||||||||||||||||||
| ClgpPduRbLineEntryPf | 1.3.6.1.4.1.476.1.42.3.8.40.40.1.24 | Integer32 | RO | deprecated | |||||||||||||||||
column · Integer32 · read-only · deprecated The line-to-neutral measurement of the Power Factor of the receptacle branches' input.
| |||||||||||||||||||||
| ClgpPduRbLineEntryEcHundredths | 1.3.6.1.4.1.476.1.42.3.8.40.40.1.25 | Unsigned32 | RO | deprecated | |||||||||||||||||
column · Unsigned32 · read-only · deprecated The line-to-neutral measurement of the Electrical Current measured in Amperes RMS (Root Mean Squared).
| |||||||||||||||||||||
| ClgpPduRbLineEntryEcThrshldUndrAlm | 1.3.6.1.4.1.476.1.42.3.8.40.40.1.35 | Unsigned32 | RW | deprecated | |||||||||||||||||
column · Unsigned32 · read-write · deprecated The threshold at which an under current alarm is activated. If the measured current (lgpPduRbLineEntryEc) is equal to or below this percentage of the full scale rated value (lgpPduRbEntryEcRated), an under current alarm is activated
| |||||||||||||||||||||
| ClgpPduRbLineEntryEcThrshldOvrWarn | 1.3.6.1.4.1.476.1.42.3.8.40.40.1.36 | Unsigned32 | RW | deprecated | |||||||||||||||||
column · Unsigned32 · read-write · deprecated The threshold at which an over current warning is activated. If the measured current (lgpPduRbLineEntryEc) is equal to or over this percentage of the full scale rated value (lgpPduRbEntryEcRated), an over current warning is activated
| |||||||||||||||||||||
| ClgpPduRbLineEntryEcThrshldOvrAlm | 1.3.6.1.4.1.476.1.42.3.8.40.40.1.37 | Unsigned32 | RW | deprecated | |||||||||||||||||
column · Unsigned32 · read-write · deprecated The threshold at which an over current alarm is activated. If the measured current (lgpPduRbLineEntryEcLN) is equal to or over this percentage of the full scale rated value (lgpPduRbEntryEcRated), an over current alarm is activated
| |||||||||||||||||||||
| ClgpPduRbLineEntryEcAvailBeforeAlarmHundredths | 1.3.6.1.4.1.476.1.42.3.8.40.40.1.39 | Unsigned32 | RO | deprecated | |||||||||||||||||
column · Unsigned32 · read-only · deprecated The amount that the current/amperage may increase from its present value before an over current alarm occurs.
| |||||||||||||||||||||
| ClgpPduRbLineEntryEcAvailBeforeAlarm | 1.3.6.1.4.1.476.1.42.3.8.40.40.1.40 | Unsigned32 | RO | deprecated | |||||||||||||||||
column · Unsigned32 · read-only · deprecated The amount that the current/amperage may increase from its present value before an over current alarm occurs.
| |||||||||||||||||||||
| ClgpPduRbLineEntryEcUsedBeforeAlarm | 1.3.6.1.4.1.476.1.42.3.8.40.40.1.41 | Unsigned32 | RO | deprecated | |||||||||||||||||
column · Unsigned32 · read-only · deprecated The percent of current utilization relative to the over current alarm threshold.
| |||||||||||||||||||||
| ClgpPduRbLineEntryEpLL | 1.3.6.1.4.1.476.1.42.3.8.40.40.1.60 | Unsigned32 | RO | deprecated | |||||||||||||||||
column · Unsigned32 · read-only · deprecated The line-to-line measurement of the Electrical Potential measured in Volts RMS (Root Mean Squared).
| |||||||||||||||||||||
| ClgpPduRbLineEntryEpLLTenths | 1.3.6.1.4.1.476.1.42.3.8.40.40.1.61 | Unsigned32 | RO | deprecated | |||||||||||||||||
column · Unsigned32 · read-only · deprecated The line-to-line measurement of the Electrical Potential measured in Volts RMS (Root Mean Squared).
| |||||||||||||||||||||
| NlgpPduReceptacle | 1.3.6.1.4.1.476.1.42.3.8.50 | ||||||||||||||||||||
node · current This sub-tree contains information about PDU receptacles. | |||||||||||||||||||||
| SlgpPduRcpTableCount | 1.3.6.1.4.1.476.1.42.3.8.50.19 | Unsigned32 | RO | ||||||||||||||||||
scalar · Unsigned32 · read-only · current Number of receptacles in the lgpPduRcpTable.
| |||||||||||||||||||||
| TlgpPduRcpTable | 1.3.6.1.4.1.476.1.42.3.8.50.20 | NA | |||||||||||||||||||
table · not-accessible · current This table contains a list of PDU receptacle entries. The table contains numerous rows representing an individual receptacle, depending upon the number and configuration of the PDU(s) being monitored by the agent. The NMS cannot create or delete rows in the table. The rows are created by the agent based upon the capabilities of the managed PDU(s). Each row in the table represents a receptacle in the system. | |||||||||||||||||||||
| RlgpPduRcpEntry | 1.3.6.1.4.1.476.1.42.3.8.50.20.1 | NA | |||||||||||||||||||
row · not-accessible · current This entry defines the attributes to be populated in the various columns of the 'lgpPduRcpTable'. This table is indexed by three indexes. The 'lgpPduEntryIndex' references a PDU in the 'lgpPduTable' that a given row in this table represents. The 'lgpPduRbEntryIndex' together with the 'lgpPduEntryIndex' specifies a row in the 'lgpPduRbTable' that the receptacle belongs. The 'lgpPduRcpEntryIndex' identifies the particular receptacle within the branch. | |||||||||||||||||||||
| ClgpPduRcpEntryIndex | 1.3.6.1.4.1.476.1.42.3.8.50.20.1.1 | Unsigned32 | NA | ||||||||||||||||||
column · Unsigned32 · not-accessible · current This is the index that indicates the receptacle position on the receptacle branch. This along with the other two indexes on the lgpPduRcpTable uniquely identify the receptacle in this table. | |||||||||||||||||||||
| ClgpPduRcpEntryId | 1.3.6.1.4.1.476.1.42.3.8.50.20.1.5 | Unsigned32 | RO | 17 | |||||||||||||||||
column · Unsigned32 · read-only · current A runtime assigned receptacle identification number. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRcpEntryUsrLabel | 1.3.6.1.4.1.476.1.42.3.8.50.20.1.10 | DisplayString | RW | Server1_p13 | |||||||||||||||||
column · DisplayString · read-write · current User assigned label for this receptacle. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRcpEntryUsrTag1 | 1.3.6.1.4.1.476.1.42.3.8.50.20.1.15 | DisplayString | RW | | |||||||||||||||||
column · DisplayString · read-write · current User assigned Tag to assist in identifying or grouping this receptacle within the end-users domain. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRcpEntryUsrTag2 | 1.3.6.1.4.1.476.1.42.3.8.50.20.1.20 | DisplayString | RW | | |||||||||||||||||
column · DisplayString · read-write · current User assigned Tag to assist in identifying or grouping this receptacle within the end-users domain. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRcpEntrySysAssignLabel | 1.3.6.1.4.1.476.1.42.3.8.50.20.1.25 | DisplayString | RO | 1-A-1 | |||||||||||||||||
column · DisplayString · read-only · current System assigned identifier representing the receptacle. The value is independent of any user assigned label or tag. The exact format of this label is system dependent and is subject to change, therefore, it should not be referenced for programmatic use. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRcpEntryPosition | 1.3.6.1.4.1.476.1.42.3.8.50.20.1.30 | Unsigned32 | RO | 1 | |||||||||||||||||
column · Unsigned32 · read-only · current A number representing the position of the receptacle within the receptacle branch. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRcpEntryType | 1.3.6.1.4.1.476.1.42.3.8.50.20.1.40 | INTEGER | RO | iec-C13-sheet-F-10-Amp(2) | |||||||||||||||||
column · INTEGER · read-only · current The type or form of receptacle. The enumerations are specified in well-known industry standard terms and abbreviations.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRcpEntryLineSource | 1.3.6.1.4.1.476.1.42.3.8.50.20.1.45 | INTEGER | RO | line-1-N(1) | |||||||||||||||||
column · INTEGER · read-only · current This represents the line source that is supplying power to this
receptacle.
not-specified
The line source supplying power to the load for this
receptacle has not been specified/configured.
line-1-N
The load for this receptacle is supplied by
a line-to-neutral configuration. (line 1 to neutral).
line-2-N
The load for this receptacle is supplied by
a line-to-neutral configuration. (line 2 to neutral).
line-3-N
The load for this receptacle is supplied by
a line-to-neutral configuration. (line 3 to neutral).
line-1-line-2
The load for this receptacle is supplied by
a line-to-line configuration (line 1 to line 2).
line-2-line-3
The load for this receptacle is supplied by
a line-to-line configuration (line 2 to line 3).
line-3-line-1
The load for this receptacle is supplied by
a line-to-line configuration (line 3 to line 1).
unknown-line-neutral
The load for this receptacle is supplied by
a line-to-neutral configuration. The system is unable to
determine which lines are supporting the load.
unknown-line-line
The load for this receptacle is supplied by
a line-to-line configuration. The system is unable to
determine which lines are supporting the load.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRcpEntryCapabilities | 1.3.6.1.4.1.476.1.42.3.8.50.20.1.50 | INTEGER | RO | measurement-and-control(3) | |||||||||||||||||
column · INTEGER · read-only · current Receptacle capabilities describes what an individual receptacle is
capable of.
no-optional-capabilities
The receptacle is unable to report measurements and lacks
control capabilities.
measurement-only
The receptacle is capable of reporting multiple measurements.
measurement-and-control
The receptacle is capable of reporting multiple measurements
and controlling the state.
control-only
The receptacle is capable of controlling the state.
current-measurement-only
The receptacle is capable of reporting the current/amperage
only.
current-measurement-and-control
The receptacle is capable of reporting the current/amperage and
has the ability to control the state.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRcpEntryEp | 1.3.6.1.4.1.476.1.42.3.8.50.20.1.55 | Unsigned32 | RO | 238 | |||||||||||||||||
column · Unsigned32 · read-only · current Voltage being delivered to the load attached to the receptacle. Alternating Current RMS Electrical Potential measurement.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRcpEntryEpTenths | 1.3.6.1.4.1.476.1.42.3.8.50.20.1.56 | Unsigned32 | RO | 2387 | |||||||||||||||||
column · Unsigned32 · read-only · current Voltage being delivered to the load attached to the receptacle. Alternating Current RMS Electrical Potential measurement.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRcpEntryEc | 1.3.6.1.4.1.476.1.42.3.8.50.20.1.60 | Unsigned32 | RO | 0 | |||||||||||||||||
column · Unsigned32 · read-only · current Current (amperage) being delivered to the load attached to the receptacle. Electrical Current is measured in Amperes RMS (Root Mean Squared).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRcpEntryEcHundredths | 1.3.6.1.4.1.476.1.42.3.8.50.20.1.61 | Unsigned32 | RO | 0 | |||||||||||||||||
column · Unsigned32 · read-only · current Current (amperage) being delivered to the load attached to the receptacle. Electrical Current is measured in Amperes RMS (Root Mean Squared).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRcpEntryPwrOut | 1.3.6.1.4.1.476.1.42.3.8.50.20.1.65 | Unsigned32 | RO | 0 | |||||||||||||||||
column · Unsigned32 · read-only · current Real Power (watts) being delivered to the load attached to the receptacle.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRcpEntryApOut | 1.3.6.1.4.1.476.1.42.3.8.50.20.1.70 | Unsigned32 | RO | 0 | |||||||||||||||||
column · Unsigned32 · read-only · current Apparent Power (volt-amps) being delivered to the load attached to the receptacle.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRcpEntryPf | 1.3.6.1.4.1.476.1.42.3.8.50.20.1.75 | Unsigned32 | RO | 0 | |||||||||||||||||
column · Unsigned32 · read-only · current Receptacle Power Factor, which is the ratio of real power to apparent power (i.e. ratio of watts to volts-amps).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRcpEntryFreq | 1.3.6.1.4.1.476.1.42.3.8.50.20.1.80 | Unsigned32 | RO | 500 | |||||||||||||||||
column · Unsigned32 · read-only · current The measured line frequency being delivered to the load attached to the receptacle.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRcpEntryEnergyAccum | 1.3.6.1.4.1.476.1.42.3.8.50.20.1.85 | Unsigned32 | RW | 10 | |||||||||||||||||
column · Unsigned32 · read-write · current Total accumulated energy, measured at the module input, since the last energy reset. Writing a value of 0 (zero) to this causes the accumulated energy to be reset. Writing a non-zero value is invalid and shall result in a write error and the total energy value remains unchanged. If the energy has not been reset and has not wrapped, then this is the total energy since installation. This value persists across boot events.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRcpEntryPwrOnDelay | 1.3.6.1.4.1.476.1.42.3.8.50.20.1.90 | Unsigned32 | RW | 0 | |||||||||||||||||
column · Unsigned32 · read-write · current The amount of time to wait before power is applied to the receptacle after a power strip is turned on or rebooted. This can be used to stagger the powering of multiple receptacles in order to prevent a large initial current draw.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRcpEntryPwrState | 1.3.6.1.4.1.476.1.42.3.8.50.20.1.95 | INTEGER | RO | off(1) | |||||||||||||||||
column · INTEGER · read-only · current unknown The current power state is unknown. off The current power state of the receptacle is OFF. on The current power state of the receptacle is ON. off-pending-on-delay The current power state of the receptacle is OFF. The power will be ON at the expiration of the ON delay of this receptacle.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRcpEntryPwrUpState | 1.3.6.1.4.1.476.1.42.3.8.50.20.1.96 | INTEGER | RW | last-state(3) | |||||||||||||||||
column · INTEGER · read-write · current The 'Power Up State' defines the state to which the receptacle shall return
after a power cycle of the PDU.
on
The receptacle shall be switched to the ON state after the power on delay
timer (lgpPduRcpEntryPwrOnDelay).
off
The receptacle shall be in the OFF state upon power cycle.
last-state
The receptacle shall be put to the previous state. Again, on state will be
effective only after the power on delay (lgpPduRcpEntryPwrOnDelay).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRcpEntryControl | 1.3.6.1.4.1.476.1.42.3.8.50.20.1.100 | INTEGER | RW | off(0) | |||||||||||||||||
column · INTEGER · read-write · current This object represents the current and persistent (configured)
power state of the receptacle. The receptacle can also be
controlled by writing to this object.
off
The current and persisted (configured) power state of the
receptacle is 'off'. When writing 'off' to this object the
receptacle, if ON, will be turned OFF and its persistent
(configured) power state will be set to 'off'.
on
The current and persisted (configured) power state of the
receptacle is 'on'. When writing 'on' to this object the
receptacle, if 'off', will be turned 'on' and its persistent
(configured) power state will be set to 'on'.
cycle-power
The receptacle is currently in a power-cycle state. The
power to the receptacle is being turned off momentarily and
will then revert to being 'on'.
When writing 'cycle-power' to this OBJECT if the receptacle is
'on' it will be momentarily turned 'off' and then revert to the
'on' state. The receptacle's persistent (configured) power
state will be left unchanged ('on').
If the receptacle is OFF writing cycle-power has no
affect on the receptacle.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRcpEntryControlLock | 1.3.6.1.4.1.476.1.42.3.8.50.20.1.105 | INTEGER | RW | unlocked(1) | |||||||||||||||||
column · INTEGER · read-write · current This object represents the locked state of the receptacle.
unknown
The lock state of the receptacle is not known at this time.
locked
If the receptacle is 'locked' then its current persisted
(configured) state can not be changed.
unlocked
If the receptacle is 'unlocked', then a user with proper
permissions may change the receptacles state.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRcpEntryEcThrshldUnderAlarm | 1.3.6.1.4.1.476.1.42.3.8.50.20.1.150 | Unsigned32 | RW | 0 | |||||||||||||||||
column · Unsigned32 · read-write · current The threshold at which an under current alarm is activated. If the measured current (lgpPduRbLineEntryEcLL) is equal to or below this percentage of the full scale rated value (lgpPduRbEntryEcRated), an under current alarm is activated
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRcpEntryEcThrshldOverWarn | 1.3.6.1.4.1.476.1.42.3.8.50.20.1.151 | Unsigned32 | RW | 90 | |||||||||||||||||
column · Unsigned32 · read-write · current The threshold at which an over current warning is activated. If the measured current (lgpPduRbLineEntryEcLL) is equal to or over this percentage of the full scale rated value (lgpPduRbEntryEcRated), an over current warning is activated
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRcpEntryEcThrshldOverAlarm | 1.3.6.1.4.1.476.1.42.3.8.50.20.1.152 | Unsigned32 | RW | 95 | |||||||||||||||||
column · Unsigned32 · read-write · current The threshold at which an over current alarm is activated. If the measured current (lgpPduRbLineEntryEcLL) is equal to or over this percentage of the full scale rated value (lgpPduRbEntryEcRated), an over current alarm is activated
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRcpEntryEcAvailBeforeAlarmHundredths | 1.3.6.1.4.1.476.1.42.3.8.50.20.1.159 | Unsigned32 | RO | 950 | |||||||||||||||||
column · Unsigned32 · read-only · current The amount that the current/amperage may increase from its present value before an over current alarm occurs.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRcpEntryEcAvailBeforeAlarm | 1.3.6.1.4.1.476.1.42.3.8.50.20.1.160 | Unsigned32 | RO | 95 | |||||||||||||||||
column · Unsigned32 · read-only · current The amount that the current/amperage may increase from its present value before an over current alarm occurs.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRcpEntryEcUsedBeforeAlarm | 1.3.6.1.4.1.476.1.42.3.8.50.20.1.161 | Unsigned32 | RO | 0 | |||||||||||||||||
column · Unsigned32 · read-only · current The percent of current utilization relative to the over current alarm threshold.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRcpEntryEcCrestFactor | 1.3.6.1.4.1.476.1.42.3.8.50.20.1.162 | Unsigned32 | RO | 0 | |||||||||||||||||
column · Unsigned32 · read-only · current Receptacle current crest factor, which is the peak amplitude of the current waveform divided by the RMS value of the waveform.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRcpEntryBlinkLED | 1.3.6.1.4.1.476.1.42.3.8.50.20.1.200 | INTEGER | RW | noAction(1) | |||||||||||||||||
column · INTEGER · read-write · current Blink the receptacle LED. Writing blinkLED(2) will cause the LED to blink for a predefined duration of time. Reading this object will always return noAction(1).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRcpEntrySwOverTemperatureProtection | 1.3.6.1.4.1.476.1.42.3.8.50.20.1.205 | INTEGER | RW | disable(0) | |||||||||||||||||
column · INTEGER · read-write · current The configuration parameter to enable or disable the Receptacle SW Over Temperature Protection feature If the feature is enabled, in case of Over Temperature Alarm condition, following action will be taken on the receptacles: Locked & Off - No Change Unlocked & Off - No Change Unlocked & On - Turn it Off. Locked & On - Turn it Off and keep it Locked. No action will be taken if the feature is disabled.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRcpEntryOperationCondition | 1.3.6.1.4.1.476.1.42.3.8.50.20.1.210 | INTEGER | RO | normalOperation(1) | |||||||||||||||||
column · INTEGER · read-only · current Receptacle Operating Condition - indicates the condition of the receptacle.
The operating condition has the following:
Normal
Normal operation without any alarm or warning.
Alarm
An Alarm condition due to over/under current.
Warning
A Warning condition due to over/under current
Abnormal
A condition in which the outlet is in 'Power Off State' but still drawing current.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRcpEntryCriticality | 1.3.6.1.4.1.476.1.42.3.8.50.20.1.215 | INTEGER | RW | critical(0) | |||||||||||||||||
column · INTEGER · read-write · current The configuration parameter can be used by the user to mark a receptacle as critical or non-critical.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRcpEntryPostOnDelay | 1.3.6.1.4.1.476.1.42.3.8.50.20.1.220 | Unsigned32 | RW | 0 | |||||||||||||||||
column · Unsigned32 · read-write · current The 'Post On Delay' is the time interval (in seconds) that the PDU waits after a command is issued to switch ON a receptacle before applying power to the receptacle A value of zero implies that there is no delay (i.e. the receptacle is turned on immediately on command issue).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRcpEntryPostOffDelay | 1.3.6.1.4.1.476.1.42.3.8.50.20.1.225 | Unsigned32 | RW | 0 | |||||||||||||||||
column · Unsigned32 · read-write · current The 'Post Off Delay' is the time interval (in seconds) that the PDU waits after a command is issued to switch OFF a receptacle before removing power from the receptacle A value of zero implies that there is no delay (i.e. the receptacle is turned off immediately on command issue).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRcpEntryAddReceptacleToGroup | 1.3.6.1.4.1.476.1.42.3.8.50.20.1.230 | OBJECT IDENTIFIER | RW | 0 | |||||||||||||||||
column · OBJECT IDENTIFIER · read-write · current This receptacle can be added to a group by writing a corresponding OID to this column. The OID must be a pointer to the lgpPduRcpGroupUsrLabel from the lgpPduRcpGroupTable. For example, to add this receptacle to group 1, the oid .1.3.6.1.4.1.476.1.42.3.8.50.30.10.1.1 would be written to this column. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduRcpEntryRemoveReceptacleFromGroup | 1.3.6.1.4.1.476.1.42.3.8.50.20.1.235 | OBJECT IDENTIFIER | RW | 0 | |||||||||||||||||
column · OBJECT IDENTIFIER · read-write · current This receptacle can be removed from a group by writing a corresponding OID to this column. The OID must be a pointer to the lgpPduRcpGroupUsrLabel from the lgpPduRcpGroupTable. For example, to remove this receptacle from group 1, the oid .1.3.6.1.4.1.476.1.42.3.8.50.30.10.1.1 would be written to this column. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NlgpPduRcpGroup | 1.3.6.1.4.1.476.1.42.3.8.50.30 | ||||||||||||||||||||
node · current This sub-tree contains information about receptacle groups. Receptacle groups are supported by some PDU's and allow control of multiple receptacles at a time by issuing commands to an associated receptacle group. | |||||||||||||||||||||
| SlgpPduRcpGroupTableCount | 1.3.6.1.4.1.476.1.42.3.8.50.30.9 | Unsigned32 | RO | ||||||||||||||||||
scalar · Unsigned32 · read-only · current Number of receptacle groups (rows) in the lgpPduRcpGroupTable.
| |||||||||||||||||||||
| TlgpPduRcpGroupTable | 1.3.6.1.4.1.476.1.42.3.8.50.30.10 | NA | |||||||||||||||||||
table · not-accessible · current This table contains a list of the possible receptacle groups that can be created. The table contains a fixed number of rows, which is the maximum number of receptacle groups that can be used. | |||||||||||||||||||||
| RlgpPduRcpGroupEntry | 1.3.6.1.4.1.476.1.42.3.8.50.30.10.1 | NA | |||||||||||||||||||
row · not-accessible · current This entry defines the attributes to be populated in the various columns of the 'lgpPduRcpGroupTable'. This table is indexed by lgpPduRcpGroupIndex.
| |||||||||||||||||||||
| ClgpPduRcpGroupIndex | 1.3.6.1.4.1.476.1.42.3.8.50.30.10.1.1 | Unsigned32 | NA | ||||||||||||||||||
column · Unsigned32 · not-accessible · current This is an index into the table. There will always be 64 rows, each representing a separate receptacle group. | |||||||||||||||||||||
| ClgpPduRcpGroupUsrLabel | 1.3.6.1.4.1.476.1.42.3.8.50.30.10.1.10 | DisplayString | RW | ||||||||||||||||||
column · DisplayString · read-write · current User assigned identifier for this receptacle group. | |||||||||||||||||||||
| ClgpPduRcpGroupDeleteGroup | 1.3.6.1.4.1.476.1.42.3.8.50.30.10.1.20 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current This column will delete the receptacles from the group when written to.
| |||||||||||||||||||||
| ClgpPduRcpGroupControlPower | 1.3.6.1.4.1.476.1.42.3.8.50.30.10.1.30 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current This column controls the power to the group of receptacles. The corresponding operation will be performed on all receptacles that have been added to the group.
| |||||||||||||||||||||
| ClgpPduRcpGroupControlLock | 1.3.6.1.4.1.476.1.42.3.8.50.30.10.1.40 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current This column controls the locking of the group of receptacles. The corresponding operation will be performed on all receptacles that have been added to the group.
| |||||||||||||||||||||
| ClgpPduRcpGroupBlinkLED | 1.3.6.1.4.1.476.1.42.3.8.50.30.10.1.50 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current This column will blink the LED's associated with all receptacles that are part of the group.
| |||||||||||||||||||||
| SlgpPduRcpGroupDisplayTableCount | 1.3.6.1.4.1.476.1.42.3.8.50.30.19 | Unsigned32 | RO | ||||||||||||||||||
scalar · Unsigned32 · read-only · current Number of rows currently in the lgpPduRcpGroupDisplayTable.
| |||||||||||||||||||||
| TlgpPduRcpGroupDisplayTable | 1.3.6.1.4.1.476.1.42.3.8.50.30.20 | NA | |||||||||||||||||||
table · not-accessible · current This table is used to display which receptacle groups are currently defined and which receptacles are associated with each group. The table will have 0 rows when no receptacles have been added to any receptacle groups. If a single receptacle has been added to 2 different groups, there will be 2 rows in the table. | |||||||||||||||||||||
| RlgpPduRcpGroupDisplayEntry | 1.3.6.1.4.1.476.1.42.3.8.50.30.20.1 | NA | |||||||||||||||||||
row · not-accessible · current This entry defines the attributes to be populated in the various columns of the 'lgpPduRcpGroupDisplayTable'. This table is indexed by two indexes. The 'lgpPduRcpGroupIndex' references a receptacle group in the 'lgpPduRcpGroupTable' that a given row in this table represents. The 'lgpPduEntryIndex' references a PDU in the 'lgpPduTable' that identifies the particular PDU receptacle list within the receptacle group. | |||||||||||||||||||||
| ClgpPduRcpGroupDisplayIndex | 1.3.6.1.4.1.476.1.42.3.8.50.30.20.1.10 | Unsigned32 | NA | ||||||||||||||||||
column · Unsigned32 · not-accessible · current This is an index into the table. There can be zero or more rows in this table. | |||||||||||||||||||||
| ClgpPduRcpGroupDisplayGroup | 1.3.6.1.4.1.476.1.42.3.8.50.30.20.1.20 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current This column displays the PDU receptacle list of the specified
receptacle group. The value in this column is a comma delimted string that decribes
the list of receptacles of a PDU that are members of the receptacle group.
For example, if receptacles 1 and 3 of branch A and receptacles 2 and 4
of branch B are members of the receptacle group, this column
would show: A-1,A-3,B-2,B-4 | |||||||||||||||||||||
| NlgpPduAuxiliarySensors | 1.3.6.1.4.1.476.1.42.3.8.60 | ||||||||||||||||||||
node · current This sub-tree contains information about PDU Auxiliary Sensors. | |||||||||||||||||||||
| SlgpPduAuxSensorCount | 1.3.6.1.4.1.476.1.42.3.8.60.5 | Unsigned32 | RO | ||||||||||||||||||
scalar · Unsigned32 · read-only · current Number of auxiliary sensors in the lgpPduAuxSensorTable.
| |||||||||||||||||||||
| TlgpPduAuxSensorTable | 1.3.6.1.4.1.476.1.42.3.8.60.10 | NA | deprecated | ||||||||||||||||||
table · not-accessible · deprecated This table contains a list of the PDU's Auxiliary Sensors. The table contains zero, one, or more rows, depending upon the number of PDUs being monitored and the number of auxiliary sensors installed for each PDU. The NMS cannot create or delete rows in the table. The rows are created by the agent based upon the capabilities of the PDUs being monitored. Each row in the table represents an auxiliary sensor in a PDU. | |||||||||||||||||||||
| RlgpPduAuxSensorEntry | 1.3.6.1.4.1.476.1.42.3.8.60.10.1 | NA | deprecated | ||||||||||||||||||
row · not-accessible · deprecated This entry defines the attributes to be populated in the various columns of the 'lgpPduAuxSensorTable'. This table is indexed by both the 'lgpPduEntryIndex' which is the sole index into the 'lgpPduTable' and the 'lgpPduAuxSensorIndex'which is a unique identifier for the auxiliary sensor attached to the given PDU. Taken together these two indexes uniquely identify an Auxiliary Sensor within this agent. | |||||||||||||||||||||
| ClgpPduAuxSensorIndex | 1.3.6.1.4.1.476.1.42.3.8.60.10.1.1 | Unsigned32 | NA | deprecated | |||||||||||||||||
column · Unsigned32 · not-accessible · deprecated This is the index indicating the nth element of the table. | |||||||||||||||||||||
| ClgpPduAuxSensorMeasType | 1.3.6.1.4.1.476.1.42.3.8.60.10.1.5 | INTEGER | RO | deprecated | |||||||||||||||||
column · INTEGER · read-only · deprecated not-specified The type of sensor is unknown. temperature The sensor in this row of the table measures temperature. humidity The sensor in this row of the table measures relative humidity. temperature-and-humidity The sensor in this row of the table measures both temperature and relative humidity.
| |||||||||||||||||||||
| ClgpPduAuxSensorId | 1.3.6.1.4.1.476.1.42.3.8.60.10.1.10 | Unsigned32 | RO | deprecated | |||||||||||||||||
column · Unsigned32 · read-only · deprecated System assigned auxiliary sensor identification number. The value assigned is product specific. | |||||||||||||||||||||
| ClgpPduAuxSensorSysAssignLabel | 1.3.6.1.4.1.476.1.42.3.8.60.10.1.15 | DisplayString | RO | deprecated | |||||||||||||||||
column · DisplayString · read-only · deprecated Label assigned to the auxiliary sensor at runtime by the system. The value is independent of any user assigned label or asset tag. | |||||||||||||||||||||
| ClgpPduAuxSensorPositionRelative | 1.3.6.1.4.1.476.1.42.3.8.60.10.1.20 | Unsigned32 | RO | deprecated | |||||||||||||||||
column · Unsigned32 · read-only · deprecated Auxiliary sensor relative position. This is a one-based value that indicates the sensor's position relative to the sensor string connector. | |||||||||||||||||||||
| ClgpPduAuxSensorUsrLabel | 1.3.6.1.4.1.476.1.42.3.8.60.10.1.25 | DisplayString | RW | deprecated | |||||||||||||||||
column · DisplayString · read-write · deprecated User assigned auxiliary sensor label. | |||||||||||||||||||||
| ClgpPduAuxSensorUsrTag1 | 1.3.6.1.4.1.476.1.42.3.8.60.10.1.30 | DisplayString | RW | deprecated | |||||||||||||||||
column · DisplayString · read-write · deprecated User assigned Tag to assist in identifying or grouping this auxiliary sensor within the end-users domain. | |||||||||||||||||||||
| ClgpPduAuxSensorUsrTag2 | 1.3.6.1.4.1.476.1.42.3.8.60.10.1.35 | DisplayString | RW | deprecated | |||||||||||||||||
column · DisplayString · read-write · deprecated User assigned Tag to assist in identifying or grouping this auxiliary sensor within the end-users domain. | |||||||||||||||||||||
| ClgpPduAuxSensorTempSerialNum | 1.3.6.1.4.1.476.1.42.3.8.60.10.1.40 | DisplayString | RO | deprecated | |||||||||||||||||
column · DisplayString · read-only · deprecated The temperature sensor's globally unique serial number assigned at the time of manufacture. | |||||||||||||||||||||
| ClgpPduAuxSensorHumSerialNum | 1.3.6.1.4.1.476.1.42.3.8.60.10.1.45 | DisplayString | RO | deprecated | |||||||||||||||||
column · DisplayString · read-only · deprecated The humidity sensor's globally unique serial number assigned at the time of manufacture. | |||||||||||||||||||||
| ClgpPduAuxSensorTempMeasurementDegF | 1.3.6.1.4.1.476.1.42.3.8.60.10.1.50 | Integer32 | RO | deprecated | |||||||||||||||||
column · Integer32 · read-only · deprecated Temperature measured at the temperature sensor reported in degrees Fahrenheit.
| |||||||||||||||||||||
| ClgpPduAuxSensorTempThrshldUndrAlmDegF | 1.3.6.1.4.1.476.1.42.3.8.60.10.1.55 | Integer32 | RW | deprecated | |||||||||||||||||
column · Integer32 · read-write · deprecated Under temperature alarm threshold. An alarm is activated if the temperature is equal to or below this value.
| |||||||||||||||||||||
| ClgpPduAuxSensorTempThrshldOvrAlmDegF | 1.3.6.1.4.1.476.1.42.3.8.60.10.1.60 | Integer32 | RW | deprecated | |||||||||||||||||
column · Integer32 · read-write · deprecated Over temperature alarm threshold. An alarm is activated if the temperature is equal to or above this value.
| |||||||||||||||||||||
| ClgpPduAuxSensorTempThrshldUndrWarnDegF | 1.3.6.1.4.1.476.1.42.3.8.60.10.1.65 | Integer32 | RW | deprecated | |||||||||||||||||
column · Integer32 · read-write · deprecated Under temperature warning threshold. A warning is activated if the temperature is equal to or below this value.
| |||||||||||||||||||||
| ClgpPduAuxSensorTempThrshldOvrWarnDegF | 1.3.6.1.4.1.476.1.42.3.8.60.10.1.70 | Integer32 | RW | deprecated | |||||||||||||||||
column · Integer32 · read-write · deprecated Over temperature warning threshold. A warning is activated if the temperature is equal to or above this value.
| |||||||||||||||||||||
| ClgpPduAuxSensorTempMeasurementDegC | 1.3.6.1.4.1.476.1.42.3.8.60.10.1.75 | Integer32 | RO | deprecated | |||||||||||||||||
column · Integer32 · read-only · deprecated Temperature measured at the temperature sensor reported in degrees Celsius.
| |||||||||||||||||||||
| ClgpPduAuxSensorTempThrshldUndrAlmDegC | 1.3.6.1.4.1.476.1.42.3.8.60.10.1.80 | Integer32 | RW | deprecated | |||||||||||||||||
column · Integer32 · read-write · deprecated Under temperature alarm threshold. An alarm is activated if the temperature is equal to or below this value.
| |||||||||||||||||||||
| ClgpPduAuxSensorTempThrshldOvrAlmDegC | 1.3.6.1.4.1.476.1.42.3.8.60.10.1.85 | Integer32 | RW | deprecated | |||||||||||||||||
column · Integer32 · read-write · deprecated Over temperature alarm threshold. An alarm is activated if the temperature is equal to or above this value.
| |||||||||||||||||||||
| ClgpPduAuxSensorTempThrshldUndrWarnDegC | 1.3.6.1.4.1.476.1.42.3.8.60.10.1.90 | Integer32 | RW | deprecated | |||||||||||||||||
column · Integer32 · read-write · deprecated Under temperature warning threshold. A warning is activated if the temperature is equal to or below this value.
| |||||||||||||||||||||
| ClgpPduAuxSensorTempThrshldOvrWarnDegC | 1.3.6.1.4.1.476.1.42.3.8.60.10.1.95 | Integer32 | RW | deprecated | |||||||||||||||||
column · Integer32 · read-write · deprecated Over temperature warning threshold. A warning is activated if the temperature is equal to or above this value.
| |||||||||||||||||||||
| ClgpPduAuxSensorHumMeasurement | 1.3.6.1.4.1.476.1.42.3.8.60.10.1.100 | Unsigned32 | RO | deprecated | |||||||||||||||||
column · Unsigned32 · read-only · deprecated Relative Humidity measured at the humidity sensor.
| |||||||||||||||||||||
| ClgpPduAuxSensorHumThrshldUndrAlm | 1.3.6.1.4.1.476.1.42.3.8.60.10.1.105 | Unsigned32 | RW | deprecated | |||||||||||||||||
column · Unsigned32 · read-write · deprecated Under relative humidity alarm threshold. An alarm is activated if the relative humidity is equal to or below this value.
| |||||||||||||||||||||
| ClgpPduAuxSensorHumThrshldOvrAlm | 1.3.6.1.4.1.476.1.42.3.8.60.10.1.110 | Unsigned32 | RW | deprecated | |||||||||||||||||
column · Unsigned32 · read-write · deprecated Over relative humidity alarm threshold. An alarm is activated if the relative humidity is equal to or above this value.
| |||||||||||||||||||||
| ClgpPduAuxSensorHumThrshldUndrWarn | 1.3.6.1.4.1.476.1.42.3.8.60.10.1.115 | Unsigned32 | RW | deprecated | |||||||||||||||||
column · Unsigned32 · read-write · deprecated Under relative humidity warning threshold. A warning is activated if the relative humidity is equal to or below this value.
| |||||||||||||||||||||
| ClgpPduAuxSensorHumThrshldOvrWarn | 1.3.6.1.4.1.476.1.42.3.8.60.10.1.120 | Unsigned32 | RW | deprecated | |||||||||||||||||
column · Unsigned32 · read-write · deprecated Over relative humidity warning threshold. A warning is activated if the relative humidity is equal to or above this value.
| |||||||||||||||||||||
| TlgpPduAuxMeasTable | 1.3.6.1.4.1.476.1.42.3.8.60.15 | NA | |||||||||||||||||||
table · not-accessible · current This table contains a list of the PDU's Auxiliary Sensor Measurements. The table contains zero, one, or more rows, depending upon the number of PDUs being monitored, the number of auxiliary sensors installed for each PDU, and the number of measurements within each sensor. The NMS cannot create or delete rows in the table. The rows are created by the agent based upon the capabilities of the PDUs being monitored. Each row in the table represents an auxiliary sensor measurement in a PDU. | |||||||||||||||||||||
| RlgpPduAuxMeasEntry | 1.3.6.1.4.1.476.1.42.3.8.60.15.1 | NA | |||||||||||||||||||
row · not-accessible · current This entry defines the attributes to be populated in the various columns of the 'lgpPduAuxMeasTable'. This table is indexed by 'lgpPduEntryIndex' which is the sole index into the 'lgpPduTable', 'lgpPduAuxSensorIndex' which is a unique identifier for the auxiliary sensor attached to the given PDU, and 'lgpPduAuxMeasSensorMeasurementIndex' which is the measurement's index identified on the sensor. Taken together these three indexes uniquely identify an Auxiliary Sensor Measurement within this agent. | |||||||||||||||||||||
| ClgpPduAuxMeasSensorIndex | 1.3.6.1.4.1.476.1.42.3.8.60.15.1.1 | Unsigned32 | NA | ||||||||||||||||||
column · Unsigned32 · not-accessible · current This is the index indicating the sensor the measurement is accessed from. | |||||||||||||||||||||
| ClgpPduAuxMeasSensorMeasurementIndex | 1.3.6.1.4.1.476.1.42.3.8.60.15.1.5 | Unsigned32 | NA | ||||||||||||||||||
column · Unsigned32 · not-accessible · current This is the measurement's index identified on the sensor. | |||||||||||||||||||||
| ClgpPduAuxMeasType | 1.3.6.1.4.1.476.1.42.3.8.60.15.1.10 | INTEGER | RO | humidity(2) | |||||||||||||||||
column · INTEGER · read-only · current not-specified The type of measurement is unknown. temperature The measurement in this row of the table measures temperature. humidity The measurement in this row of the table measures relative humidity. door-closure The measurement in this row of the table measures the state of a door. contact-closure The measurement in this row of the table measures the state of a contact closure. differential-pressure The measurement in this row of the table measures differential pressure. leak-detection The measurement in this row of the table measures the state of a leak detection sensor.
| |||||||||||||||||||||
| ClgpPduAuxMeasSensorSysAssignLabel | 1.3.6.1.4.1.476.1.42.3.8.60.15.1.15 | DisplayString | RO | SNSR: 1-1 | |||||||||||||||||
column · DisplayString · read-only · current Label assigned to the auxiliary sensor at runtime by the system. The value is independent of any user assigned label or asset tag. | |||||||||||||||||||||
| ClgpPduAuxMeasUsrLabel | 1.3.6.1.4.1.476.1.42.3.8.60.15.1.20 | DisplayString | RW | 10000001ACA3F226 | |||||||||||||||||
| ClgpPduAuxMeasUsrTag1 | 1.3.6.1.4.1.476.1.42.3.8.60.15.1.25 | DisplayString | RW | | |||||||||||||||||
column · DisplayString · read-write · current User assigned Tag to assist in identifying or grouping this auxiliary sensor measurement within the end-users domain. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduAuxMeasUsrTag2 | 1.3.6.1.4.1.476.1.42.3.8.60.15.1.30 | DisplayString | RW | | |||||||||||||||||
column · DisplayString · read-write · current User assigned Tag to assist in identifying or grouping this auxiliary sensor measurement within the end-users domain. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduAuxMeasSensorSerialNum | 1.3.6.1.4.1.476.1.42.3.8.60.15.1.35 | DisplayString | RO | 10000001ACA3F226 | |||||||||||||||||
column · DisplayString · read-only · current The sensor's globally unique serial number assigned at the time of manufacture. | |||||||||||||||||||||
| ClgpPduAuxMeasTempDegF | 1.3.6.1.4.1.476.1.42.3.8.60.15.1.40 | Integer32 | RO | 635 | |||||||||||||||||
| ClgpPduAuxMeasTempThrshldUndrAlmDegF | 1.3.6.1.4.1.476.1.42.3.8.60.15.1.50 | Integer32 | RW | 644 | |||||||||||||||||
column · Integer32 · read-write · current Under temperature alarm threshold. An alarm is activated if the temperature is equal to or below this value.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduAuxMeasTempThrshldOvrAlmDegF | 1.3.6.1.4.1.476.1.42.3.8.60.15.1.55 | Integer32 | RW | 806 | |||||||||||||||||
column · Integer32 · read-write · current Over temperature alarm threshold. An alarm is activated if the temperature is equal to or above this value.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduAuxMeasTempThrshldUndrWarnDegF | 1.3.6.1.4.1.476.1.42.3.8.60.15.1.60 | Integer32 | RW | 680 | |||||||||||||||||
column · Integer32 · read-write · current Under temperature warning threshold. A warning is activated if the temperature is equal to or below this value.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduAuxMeasTempThrshldOvrWarnDegF | 1.3.6.1.4.1.476.1.42.3.8.60.15.1.65 | Integer32 | RW | 770 | |||||||||||||||||
column · Integer32 · read-write · current Over temperature warning threshold. A warning is activated if the temperature is equal to or above this value.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduAuxMeasTempDegC | 1.3.6.1.4.1.476.1.42.3.8.60.15.1.70 | Integer32 | RO | 175 | |||||||||||||||||
| ClgpPduAuxMeasTempThrshldUndrAlmDegC | 1.3.6.1.4.1.476.1.42.3.8.60.15.1.75 | Integer32 | RW | 180 | |||||||||||||||||
column · Integer32 · read-write · current Under temperature alarm threshold. An alarm is activated if the temperature is equal to or below this value.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduAuxMeasTempThrshldOvrAlmDegC | 1.3.6.1.4.1.476.1.42.3.8.60.15.1.80 | Integer32 | RW | 270 | |||||||||||||||||
column · Integer32 · read-write · current Over temperature alarm threshold. An alarm is activated if the temperature is equal to or above this value.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduAuxMeasTempThrshldUndrWarnDegC | 1.3.6.1.4.1.476.1.42.3.8.60.15.1.85 | Integer32 | RW | 200 | |||||||||||||||||
column · Integer32 · read-write · current Under temperature warning threshold. A warning is activated if the temperature is equal to or below this value.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduAuxMeasTempThrshldOvrWarnDegC | 1.3.6.1.4.1.476.1.42.3.8.60.15.1.90 | Integer32 | RW | 250 | |||||||||||||||||
column · Integer32 · read-write · current Over temperature warning threshold. A warning is activated if the temperature is equal to or above this value.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduAuxMeasHum | 1.3.6.1.4.1.476.1.42.3.8.60.15.1.95 | Unsigned32 | RO | 142 | |||||||||||||||||
| ClgpPduAuxMeasHumThrshldUndrAlm | 1.3.6.1.4.1.476.1.42.3.8.60.15.1.100 | Unsigned32 | RW | 400 | |||||||||||||||||
column · Unsigned32 · read-write · current Under relative humidity alarm threshold. An alarm is activated if the relative humidity is equal to or below this value.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduAuxMeasHumThrshldOvrAlm | 1.3.6.1.4.1.476.1.42.3.8.60.15.1.105 | Unsigned32 | RW | 600 | |||||||||||||||||
column · Unsigned32 · read-write · current Over relative humidity alarm threshold. An alarm is activated if the relative humidity is equal to or above this value.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduAuxMeasHumThrshldUndrWarn | 1.3.6.1.4.1.476.1.42.3.8.60.15.1.110 | Unsigned32 | RW | 440 | |||||||||||||||||
column · Unsigned32 · read-write · current Under relative humidity warning threshold. A warning is activated if the relative humidity is equal to or below this value.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduAuxMeasHumThrshldOvrWarn | 1.3.6.1.4.1.476.1.42.3.8.60.15.1.115 | Unsigned32 | RW | 560 | |||||||||||||||||
column · Unsigned32 · read-write · current Over relative humidity warning threshold. A warning is activated if the relative humidity is equal to or above this value.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ClgpPduAuxMeasDrClosureState | 1.3.6.1.4.1.476.1.42.3.8.60.15.1.120 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current The state of a door sensor measurement.
not-specified
The door state is unknown.
open
The door is in the open state.
closed
The door is in the closed state.
| |||||||||||||||||||||
| ClgpPduAuxMeasDrClosureConfig | 1.3.6.1.4.1.476.1.42.3.8.60.15.1.125 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current Configure door state alarms. This object provides the ability to
select when a door closure measurement should cause an alarm.
disabled
The door state will never result in alarm.
alarm-when-open
Activate an alarm when the door state becomes open.
| |||||||||||||||||||||
| ClgpPduAuxMeasCntctClosureState | 1.3.6.1.4.1.476.1.42.3.8.60.15.1.130 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current The state of a contact closure sensor measurement.
not-specified
The contact closure state is unknown.
open
The contact closure is in the open state.
closed
The contact closure is in the closed state.
| |||||||||||||||||||||
| ClgpPduAuxMeasCntctClosureConfig | 1.3.6.1.4.1.476.1.42.3.8.60.15.1.135 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current Configure contact closure state alarms. This object provides the
ability to select when a contact closure measurement should
activate an alarm.
disabled
The contact closure state will never result in alarm.
alarm-when-open
Activate an alarm when the contact closure state becomes
open.
alarm-when-closed
Activate an alarm when the contact closure state becomes
closed.
| |||||||||||||||||||||
| ClgpPduAuxMeasDiffPressure | 1.3.6.1.4.1.476.1.42.3.8.60.15.1.140 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Pressure difference measured at the differential pressure sensor.
| |||||||||||||||||||||
| ClgpPduAuxMeasDiffPressureThrshldUndrAlm | 1.3.6.1.4.1.476.1.42.3.8.60.15.1.145 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current Under differential pressure alarm threshold. An alarm is activated if the differential pressure is equal to or below this value.
| |||||||||||||||||||||
| ClgpPduAuxMeasDiffPressureThrshldOvrAlm | 1.3.6.1.4.1.476.1.42.3.8.60.15.1.150 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current Over differential pressure alarm threshold. An alarm is activated if the differential pressure is equal to or above this value.
| |||||||||||||||||||||
| ClgpPduAuxMeasDiffPressureThrshldUndrWarn | 1.3.6.1.4.1.476.1.42.3.8.60.15.1.155 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current Under differential pressure warning threshold. A warning is activated if the differential pressure is equal to or below this value.
| |||||||||||||||||||||
| ClgpPduAuxMeasDiffPressureThrshldOvrWarn | 1.3.6.1.4.1.476.1.42.3.8.60.15.1.160 | Integer32 | RW | ||||||||||||||||||
column · Integer32 · read-write · current Over differential pressure warning threshold. A warning is activated if the differential pressure is equal to or above this value.
| |||||||||||||||||||||
| ClgpPduAuxMeasLeakDetectState | 1.3.6.1.4.1.476.1.42.3.8.60.15.1.165 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current not-specified The leak detection state is unknown. no-leak-detected No leak has been detected. leak-detected A leak has been detected. leak-detection-pending Characterization of possible leak is pending further analysis based on new data received from the sensor. This state may not occur at all, but if it does, it should occur only for a small amount of time before transitioning to no-leak-detected or leak-detected. cable-fault A fault in the cable has been detected (for example, a disconnected cable). The sensor will not be able to detect a leak.
| |||||||||||||||||||||
| TlgpPduAuxMeasOrderTable | 1.3.6.1.4.1.476.1.42.3.8.60.20 | NA | |||||||||||||||||||
table · not-accessible · current This table contains a list of the PDU's Auxiliary Sensors and their respective 'location' in the lgpPduAuxMeasTable table. This table contains 1 row, for potential sensor for each PDU. The rows in this table are created by the agent based on the maximum number of sensor's supported for each PDU. Each row in the table represents an auxiliary sensor, identified by its factory assigned serial number and its placement in the lgpPduAuxMeasTable. If all serial numbers in this table are empty strings then the location of the sensors in the lgpPduAuxMeasTable will default to the agent's default placement algorithm. If sensors in the lgpPduAuxMeasTable and are not represented by an entry in this table then the location of the unrepresented sensor(s) in the lgpPduAuxMeasTable, and other display mediums, will be determined by the agent, but in no case will an unrepresented sensor occupy a position reserved for a sensor present in this table. Those unrepresented sensor's display location is not guaranteed to be consistent across reboots or rediscovery actions on the sensor bus. Only sensors represented in this table are guarantted consistent placement as specified by their index entries (position) in this table. Note that it is possible to have entries in this table representing sensors that may not exist on the given PDU at runtime. These allocated by not present sensors will reduce the total number of sensors that can be displayed for the given PDU. | |||||||||||||||||||||
| RlgpPduAuxMeasOrderEntry | 1.3.6.1.4.1.476.1.42.3.8.60.20.1 | NA | |||||||||||||||||||
row · not-accessible · current This entry defines the attributes to be populated in the various columns of the 'lgpPduAuxMeasOrderTable'. This table is indexed by 'lgpPduEntryIndex' which is the sole index into the 'lgpPduTable' and 'lgpPduAuxMeasSensorIndex' which is a unique identifier for the auxiliary sensor attached to the given PDU. Taken together these two indexes uniquely identify a Auxiliary Sensor within this agent. | |||||||||||||||||||||
| ClgpPduAuxSensorOrderIndex | 1.3.6.1.4.1.476.1.42.3.8.60.20.1.5 | Unsigned32 | NA | ||||||||||||||||||
column · Unsigned32 · not-accessible · current Index representing the position within the sensor string on the given PDU | |||||||||||||||||||||
| ClgpPduAuxMeasOrderSensorSerialNum | 1.3.6.1.4.1.476.1.42.3.8.60.20.1.15 | DisplayString | RW | ||||||||||||||||||
column · DisplayString · read-write · current The sensor's globally unique serial number assigned at the time of manufacture. The sensor represented by this serial number will be, if discovered, by the agent placed in the lgpPduAuxMeasTable at the location specified by the index entries herein. A empty string in this object indicates an open display position that can be occupied by any sensor not given a specific display position in this table. | |||||||||||||||||||||