LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB
Vertiv (formerly 'Emerson Computer Power')The MIB module used to register Liebert SNMP OIDs. Copyright 2000-2022 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification.
snmptranslate -m LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB -Tpsnmpwalk -v2c -c <community> -m LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB <host> 1.3.6.1.4.1.476.1.42.1.11.1Imports
| LIEBERT-GP-CONDITIONS-MIB | lgpFlexConditions |
|---|---|
| LIEBERT-GP-REGISTRATION-MIB | liebertFlexibleConditionsModuleReg |
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
| SNMPv2-SMI | Bits, Integer32, IpAddress, MODULE-IDENTITY, MibIdentifier, OBJECT-IDENTITY, OBJECT-TYPE, TimeTicks, Unsigned32, iso |
| SNMPv2-TC | DisplayString, PhysAddress, TEXTUAL-CONVENTION |
OID tree
| Name | OID | Type | Access | Status |
|---|---|---|---|---|
| IliebertGlobalProductsFlexibleConditionsModule | 1.3.6.1.4.1.476.1.42.1.11.1 | |||
identity The MIB module used to register Liebert SNMP OIDs. Copyright 2000-2022 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification. | ||||
| NlgpFlexConditionsWellKnown | 1.3.6.1.4.1.476.1.42.3.2.7.1 | |||
| NlgpCondId4122SystemInputPowerProblem | 1.3.6.1.4.1.476.1.42.3.2.7.1.4122 | |||
node · current The input is not qualified to provide power to the system. | ||||
| NlgpCondId4132BypassOverloadPhaseA | 1.3.6.1.4.1.476.1.42.3.2.7.1.4132 | |||
node · current An overload exists on output phase A while operating on the bypass. | ||||
| NlgpCondId4133BypassOverloadPhaseB | 1.3.6.1.4.1.476.1.42.3.2.7.1.4133 | |||
node · current An overload exists on output phase B while operating on the bypass. | ||||
| NlgpCondId4134BypassOverloadPhaseC | 1.3.6.1.4.1.476.1.42.3.2.7.1.4134 | |||
node · current An overload exists on output phase C while operating on the bypass. | ||||
| NlgpCondId4135BypassNotAvailable | 1.3.6.1.4.1.476.1.42.3.2.7.1.4135 | |||
node · current A problem associated with the bypass has been detected. | ||||
| NlgpCondId4137BypassAutoRetransferPrimed | 1.3.6.1.4.1.476.1.42.3.2.7.1.4137 | |||
node · current Automatic retransfer from bypass to inverter is possible. | ||||
| NlgpCondId4138BypassAutoRetransferFailed | 1.3.6.1.4.1.476.1.42.3.2.7.1.4138 | |||
node · current After performing a recoverable transfer to bypass, an attempt to auto retransfer from bypass to inverter failed. | ||||
| NlgpCondId4139BypassExcessAutoRetransfers | 1.3.6.1.4.1.476.1.42.3.2.7.1.4139 | |||
node · current The number of auto retransfers, from bypass to inverter, has exceeded the maximum for a specified time interval. | ||||
| NlgpCondId4140BypassRestartInhibitExternal | 1.3.6.1.4.1.476.1.42.3.2.7.1.4140 | |||
node · current Restart of the bypass is inhibited by the state of an external signal. | ||||
| NlgpCondId4141BypassBreakerClosed | 1.3.6.1.4.1.476.1.42.3.2.7.1.4141 | |||
node · current The bypass breaker is closed. | ||||
| NlgpCondId4142BypassStaticSwitchOverload | 1.3.6.1.4.1.476.1.42.3.2.7.1.4142 | |||
node · current Bypass off due to static switch overload. | ||||
| NlgpCondId4143BypassStaticSwitchUnavailable | 1.3.6.1.4.1.476.1.42.3.2.7.1.4143 | |||
node · current The static bypass is unavailable to support the critical load. | ||||
| NlgpCondId4144BypassExcessivePulseParallel | 1.3.6.1.4.1.476.1.42.3.2.7.1.4144 | |||
node · current The system has performed too many pulse parallel operations within a specified time interval. | ||||
| NlgpCondId4145BypassAutoTransferFailed | 1.3.6.1.4.1.476.1.42.3.2.7.1.4145 | |||
node · current An automatic transfer to static bypass failed. | ||||
| NlgpCondId4146SystemInputPhsRotationError | 1.3.6.1.4.1.476.1.42.3.2.7.1.4146 | |||
node · current The power conductors on the input line are not wired to the UPS in the sequence preferred for the rectifier (A-B-C). | ||||
| NlgpCondId4147SystemInputCurrentLimit | 1.3.6.1.4.1.476.1.42.3.2.7.1.4147 | |||
node · current The RMS input current has reached the input current limit threshold. | ||||
| NlgpCondId4162BatteryLow | 1.3.6.1.4.1.476.1.42.3.2.7.1.4162 | |||
node · current The calculated battery time remaining has reached the low battery threshold. | ||||
| NlgpCondId4163OutputOffEndofDischarge | 1.3.6.1.4.1.476.1.42.3.2.7.1.4163 | |||
node · current Output turned off due to battery reaching end-of-discharge. | ||||
| NlgpCondId4164BatteryChargingError | 1.3.6.1.4.1.476.1.42.3.2.7.1.4164 | |||
node · current The battery is not charging properly. | ||||
| NlgpCondId4165BatteryChargingReducedExtrnl | 1.3.6.1.4.1.476.1.42.3.2.7.1.4165 | |||
node · current Using a reduced battery charging algorithm due to an external signal. | ||||
| NlgpCondId4166BatteryCapacityLow | 1.3.6.1.4.1.476.1.42.3.2.7.1.4166 | |||
node · current Battery capacity is low. | ||||
| NlgpCondId4167OutputOff | 1.3.6.1.4.1.476.1.42.3.2.7.1.4167 | |||
node · current Output is off. | ||||
| NlgpCondId4168BatteryDischarging | 1.3.6.1.4.1.476.1.42.3.2.7.1.4168 | |||
node · current The battery is discharging. | ||||
| NlgpCondId4169BatteryTemperatureImbalance | 1.3.6.1.4.1.476.1.42.3.2.7.1.4169 | |||
node · current Excessive temperature differences between battery sensors detected. | ||||
| NlgpCondId4170BatteryEqualize | 1.3.6.1.4.1.476.1.42.3.2.7.1.4170 | |||
node · current The rectifier output voltage is increased to equalize the battery voltage level. | ||||
| NlgpCondId4171BatteryManualTestInProgress | 1.3.6.1.4.1.476.1.42.3.2.7.1.4171 | |||
node · current Manual battery test is in progress. | ||||
| NlgpCondId4172BatteryAutoTestInProgress | 1.3.6.1.4.1.476.1.42.3.2.7.1.4172 | |||
node · current Automatic battery test is in progress. | ||||
| NlgpCondId4173MainBatteryDisconnectOpen | 1.3.6.1.4.1.476.1.42.3.2.7.1.4173 | |||
node · current Main battery disconnect is open. | ||||
| NlgpCondId4174BatteryTemperatureSensorFault | 1.3.6.1.4.1.476.1.42.3.2.7.1.4174 | |||
node · current A battery temperature sensor fault has been detected. | ||||
| NlgpCondId4175BypassFrequencyError | 1.3.6.1.4.1.476.1.42.3.2.7.1.4175 | |||
node · current The bypass frequency is outside the inverter synchronization limits. | ||||
| NlgpCondId4176BatteryCircuitBreaker1Open | 1.3.6.1.4.1.476.1.42.3.2.7.1.4176 | |||
node · current Battery circuit breaker 1 is open. | ||||
| NlgpCondId4177BatteryBreaker1OpenFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.4177 | |||
node · current Battery circuit breaker 1 failed to open. | ||||
| NlgpCondId4178BatteryBreaker1CloseFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.4178 | |||
node · current Battery circuit breaker 1 failed to close. | ||||
| NlgpCondId4179BatteryCircuitBreaker2Open | 1.3.6.1.4.1.476.1.42.3.2.7.1.4179 | |||
node · current Battery circuit breaker 2 is open. | ||||
| NlgpCondId4180BatteryBreaker2OpenFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.4180 | |||
node · current Battery circuit breaker 2 failed to open. | ||||
| NlgpCondId4181BatteryBreaker2CloseFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.4181 | |||
node · current Battery circuit breaker 2 failed to close. | ||||
| NlgpCondId4182BatteryCircuitBreaker3Open | 1.3.6.1.4.1.476.1.42.3.2.7.1.4182 | |||
node · current Battery circuit breaker 3 is open. | ||||
| NlgpCondId4183BatteryBreaker3OpenFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.4183 | |||
node · current Battery circuit breaker 3 failed to open. | ||||
| NlgpCondId4184BatteryBreaker3CloseFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.4184 | |||
node · current Battery circuit breaker 3 failed to close. | ||||
| NlgpCondId4185BatteryCircuitBreaker4Open | 1.3.6.1.4.1.476.1.42.3.2.7.1.4185 | |||
node · current Battery circuit breaker 4 is open. | ||||
| NlgpCondId4186BatteryBreaker4OpenFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.4186 | |||
node · current Battery circuit breaker 4 failed to open. | ||||
| NlgpCondId4187BatteryBreaker4CloseFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.4187 | |||
node · current Battery circuit breaker 4 failed to close. | ||||
| NlgpCondId4188BatteryCircuitBreaker5Open | 1.3.6.1.4.1.476.1.42.3.2.7.1.4188 | |||
node · current Battery circuit breaker 5 is open. | ||||
| NlgpCondId4189BatteryBreaker5OpenFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.4189 | |||
node · current Battery circuit breaker 5 failed to open. | ||||
| NlgpCondId4190BatteryBreaker5CloseFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.4190 | |||
node · current Battery circuit breaker 5 failed to close. | ||||
| NlgpCondId4191BatteryCircuitBreaker6Open | 1.3.6.1.4.1.476.1.42.3.2.7.1.4191 | |||
node · current Battery circuit breaker 6 is open. | ||||
| NlgpCondId4192BatteryBreaker6OpenFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.4192 | |||
node · current Battery circuit breaker 6 failed to open. | ||||
| NlgpCondId4193BatteryBreaker6CloseFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.4193 | |||
node · current Battery circuit breaker 6 failed to close. | ||||
| NlgpCondId4194BatteryCircuitBreaker7Open | 1.3.6.1.4.1.476.1.42.3.2.7.1.4194 | |||
node · current Battery circuit breaker 7 is open. | ||||
| NlgpCondId4195BatteryBreaker7OpenFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.4195 | |||
node · current Battery circuit breaker 7 failed to open. | ||||
| NlgpCondId4196BatteryBreaker7CloseFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.4196 | |||
node · current Battery circuit breaker 7 failed to close. | ||||
| NlgpCondId4197BatteryCircuitBreaker8Open | 1.3.6.1.4.1.476.1.42.3.2.7.1.4197 | |||
node · current Battery circuit breaker 8 is open. | ||||
| NlgpCondId4198BatteryBreaker8OpenFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.4198 | |||
node · current Battery circuit breaker 8 failed to open. | ||||
| NlgpCondId4199BatteryBreaker8CloseFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.4199 | |||
node · current Battery circuit breaker 8 failed to close. | ||||
| NlgpCondId4200BatteryChargingInhibited | 1.3.6.1.4.1.476.1.42.3.2.7.1.4200 | |||
node · current Battery charging is inhibited due to an external inhibit signal. | ||||
| NlgpCondId4213SystemShutdownEPO | 1.3.6.1.4.1.476.1.42.3.2.7.1.4213 | |||
node · current System shutdown due to Emergency Power Off (EPO). | ||||
| NlgpCondId4214SystemShutdownREPO | 1.3.6.1.4.1.476.1.42.3.2.7.1.4214 | |||
node · current System shutdown due to Remote Emergency Power Off (REPO). | ||||
| NlgpCondId4215SystemOutputOff | 1.3.6.1.4.1.476.1.42.3.2.7.1.4215 | |||
node · current The system output is off. | ||||
| NlgpCondId4216BypassBackfeedDetected | 1.3.6.1.4.1.476.1.42.3.2.7.1.4216 | |||
node · current The system detected a voltage on the bypass when none was expected. | ||||
| NlgpCondId4217BypassManualXfrInhibited | 1.3.6.1.4.1.476.1.42.3.2.7.1.4217 | |||
node · current Manual transfer from inverter to bypass is inhibited - bypass not qualified. | ||||
| NlgpCondId4218BypassManualRexfrInhibited | 1.3.6.1.4.1.476.1.42.3.2.7.1.4218 | |||
node · current Manual transfer from bypass to inverter is inhibited - inverter output not qualified. | ||||
| NlgpCondId4219BatteryOverTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.4219 | |||
node · current A battery temperature sensor is reporting a value above a threshold. | ||||
| NlgpCondId4220BatteryExternalMonitor1 | 1.3.6.1.4.1.476.1.42.3.2.7.1.4220 | |||
node · current External battery monitor 1 - battery maintenance required. | ||||
| NlgpCondId4221BatteryExternalMonitor2 | 1.3.6.1.4.1.476.1.42.3.2.7.1.4221 | |||
node · current External battery monitor 2 - battery maintenance required. | ||||
| NlgpCondId4222BatteryGroundFault | 1.3.6.1.4.1.476.1.42.3.2.7.1.4222 | |||
node · current Battery system ground fault amperage exceeds the threshold. | ||||
| NlgpCondId4229EmergencyPowerOffLatched | 1.3.6.1.4.1.476.1.42.3.2.7.1.4229 | |||
node · current System output is off - 'Emergency Power Off (EPO) - latched' requires manual reset. | ||||
| NlgpCondId4230SystemOutputLowPowerFactor | 1.3.6.1.4.1.476.1.42.3.2.7.1.4230 | |||
node · current The system output power factor is low, resulting in reduced output capacity. | ||||
| NlgpCondId4231OutputCurrentExceedsThreshold | 1.3.6.1.4.1.476.1.42.3.2.7.1.4231 | |||
node · current Output current for one or more phases exceeds a threshold. | ||||
| NlgpCondId4233InverterFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.4233 | |||
node · current Inverter failure - inverter output is off. | ||||
| NlgpCondId4234InverterOverloadPhaseA | 1.3.6.1.4.1.476.1.42.3.2.7.1.4234 | |||
node · current Inverter is operating with an overload on phase A. | ||||
| NlgpCondId4235InverterOverloadPhaseB | 1.3.6.1.4.1.476.1.42.3.2.7.1.4235 | |||
node · current Inverter is operating with an overload on phase B. | ||||
| NlgpCondId4236InverterOverloadPhaseC | 1.3.6.1.4.1.476.1.42.3.2.7.1.4236 | |||
node · current Inverter is operating with an overload on phase C. | ||||
| NlgpCondId4237InverterInhibitExternal | 1.3.6.1.4.1.476.1.42.3.2.7.1.4237 | |||
node · current Restart of the inverter is inhibited by an external signal. | ||||
| NlgpCondId4238InverterOutBreakerOpenFail | 1.3.6.1.4.1.476.1.42.3.2.7.1.4238 | |||
node · current Inverter output breaker failed to open. | ||||
| NlgpCondId4239InverterOutBreakerCloseFail | 1.3.6.1.4.1.476.1.42.3.2.7.1.4239 | |||
node · current Inverter output breaker failed to close. | ||||
| NlgpCondId4270InputContact01 | 1.3.6.1.4.1.476.1.42.3.2.7.1.4270 | |||
node · current The external input contact 1. | ||||
| NlgpCondId4271InputContact02 | 1.3.6.1.4.1.476.1.42.3.2.7.1.4271 | |||
node · current The external input contact 2. | ||||
| NlgpCondId4272InputContact03 | 1.3.6.1.4.1.476.1.42.3.2.7.1.4272 | |||
node · current The external input contact 3. | ||||
| NlgpCondId4273InputContact04 | 1.3.6.1.4.1.476.1.42.3.2.7.1.4273 | |||
node · current The external input contact 4. | ||||
| NlgpCondId4274InputContact05 | 1.3.6.1.4.1.476.1.42.3.2.7.1.4274 | |||
node · current The external input contact 5. | ||||
| NlgpCondId4275InputContact06 | 1.3.6.1.4.1.476.1.42.3.2.7.1.4275 | |||
node · current The external input contact 6. | ||||
| NlgpCondId4276InputContact07 | 1.3.6.1.4.1.476.1.42.3.2.7.1.4276 | |||
node · current The external input contact 7. | ||||
| NlgpCondId4277InputContact08 | 1.3.6.1.4.1.476.1.42.3.2.7.1.4277 | |||
node · current The external input contact 8. | ||||
| NlgpCondId4278InputContact09 | 1.3.6.1.4.1.476.1.42.3.2.7.1.4278 | |||
node · current The external input contact 9. | ||||
| NlgpCondId4279InputContact10 | 1.3.6.1.4.1.476.1.42.3.2.7.1.4279 | |||
node · current The external input contact 10. | ||||
| NlgpCondId4280InputContact11 | 1.3.6.1.4.1.476.1.42.3.2.7.1.4280 | |||
node · current The external input contact 11. | ||||
| NlgpCondId4281InputContact12 | 1.3.6.1.4.1.476.1.42.3.2.7.1.4281 | |||
node · current The external input contact 12. | ||||
| NlgpCondId4282InputContact13 | 1.3.6.1.4.1.476.1.42.3.2.7.1.4282 | |||
node · current The external input contact 13. | ||||
| NlgpCondId4283InputContact14 | 1.3.6.1.4.1.476.1.42.3.2.7.1.4283 | |||
node · current The external input contact 14. | ||||
| NlgpCondId4284InputContact15 | 1.3.6.1.4.1.476.1.42.3.2.7.1.4284 | |||
node · current The external input contact 15. | ||||
| NlgpCondId4285InputContact16 | 1.3.6.1.4.1.476.1.42.3.2.7.1.4285 | |||
node · current The external input contact 16. | ||||
| NlgpCondId4286OutputAmpOverUserLimitPhsA | 1.3.6.1.4.1.476.1.42.3.2.7.1.4286 | |||
node · current The phase A output has exceeded the user amperage threshold. | ||||
| NlgpCondId4287OutputAmpOverUserLimitPhsB | 1.3.6.1.4.1.476.1.42.3.2.7.1.4287 | |||
node · current The phase B output has exceeded the user amperage threshold. | ||||
| NlgpCondId4288OutputAmpOverUserLimitPhsC | 1.3.6.1.4.1.476.1.42.3.2.7.1.4288 | |||
node · current The phase C output has exceeded the user amperage threshold. | ||||
| NlgpCondId4289InverterTransferInhibitExt | 1.3.6.1.4.1.476.1.42.3.2.7.1.4289 | |||
node · current Transfer of critical bus source to inverter is inhibited by an external signal. | ||||
| NlgpCondId4290InverterShutdownOverload | 1.3.6.1.4.1.476.1.42.3.2.7.1.4290 | |||
node · current The inverter has shutdown due to a sustained overload. | ||||
| NlgpCondId4294InletAirOverTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.4294 | |||
node · current The inlet air exceeds the maximum temperature threshold. | ||||
| NlgpCondId4295RectifierFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.4295 | |||
node · current Rectifier failure - rectifier is off. | ||||
| NlgpCondId4296RectifierOperationInhibitExt | 1.3.6.1.4.1.476.1.42.3.2.7.1.4296 | |||
node · current The operation of the rectifier is inhibited by an external signal. | ||||
| NlgpCondId4297UPSOutputonInverter | 1.3.6.1.4.1.476.1.42.3.2.7.1.4297 | |||
node · current The output power is supplied by the inverter. | ||||
| NlgpCondId4298UPSOutputonBypass | 1.3.6.1.4.1.476.1.42.3.2.7.1.4298 | |||
node · current The output power is supplied by the bypass. | ||||
| NlgpCondId4299OutputLoadonMaintBypass | 1.3.6.1.4.1.476.1.42.3.2.7.1.4299 | |||
node · current The output power is supplied by the maintenance bypass. | ||||
| NlgpCondId4300InternalCommunicationsFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.4300 | |||
node · current The control has detected a communication failure of a component on the internal communication bus. | ||||
| NlgpCondId4308DCBusGroundFaultPositive | 1.3.6.1.4.1.476.1.42.3.2.7.1.4308 | |||
node · current A ground fault has been detected on the positive DC Bus link. | ||||
| NlgpCondId4309DCBusGroundFaultNegative | 1.3.6.1.4.1.476.1.42.3.2.7.1.4309 | |||
node · current A ground fault has been detected on the negative DC Bus link. | ||||
| NlgpCondId4310EquipmentOverTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.4310 | |||
node · current Equipment over temperature summary event. | ||||
| NlgpCondId4311SystemFanFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.4311 | |||
node · current System fan failure - one or more fans have failed. | ||||
| NlgpCondId4313PasswordChanged | 1.3.6.1.4.1.476.1.42.3.2.7.1.4313 | |||
node · current Password changed. | ||||
| NlgpCondId4314PowerSupplyFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.4314 | |||
node · current Power supply failure. | ||||
| NlgpCondId4315OnGenerator | 1.3.6.1.4.1.476.1.42.3.2.7.1.4315 | |||
node · current A generator is supplying the power to the system. | ||||
| NlgpCondId4316AutoRestartInProgress | 1.3.6.1.4.1.476.1.42.3.2.7.1.4316 | |||
node · current Auto restart is in progress. | ||||
| NlgpCondId4317AutoRestartInhibitedExt | 1.3.6.1.4.1.476.1.42.3.2.7.1.4317 | |||
node · current Auto restart inhibited due to an external signal. | ||||
| NlgpCondId4320InitiatedTransfertoBypass | 1.3.6.1.4.1.476.1.42.3.2.7.1.4320 | |||
node · current User initiated manual transfer to bypass. | ||||
| NlgpCondId4321InitiatedTransfertoInverter | 1.3.6.1.4.1.476.1.42.3.2.7.1.4321 | |||
node · current User initiated manual transfer to inverter. | ||||
| NlgpCondId4322BatteryTestPassed | 1.3.6.1.4.1.476.1.42.3.2.7.1.4322 | |||
node · current Battery test passed. | ||||
| NlgpCondId4323BatteryTestFailed | 1.3.6.1.4.1.476.1.42.3.2.7.1.4323 | |||
node · current Battery test failed. | ||||
| NlgpCondId4324BatteryTestManuallyStopped | 1.3.6.1.4.1.476.1.42.3.2.7.1.4324 | |||
node · current The battery test was manually stopped prior to completion. | ||||
| NlgpCondId4325BackfeedBreakerOpen | 1.3.6.1.4.1.476.1.42.3.2.7.1.4325 | |||
node · current The backfeed breaker is in the open position. | ||||
| NlgpCondId4341VelocityAuthenticationFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.4341 | |||
node · current Notification of a message rejected by Velocity due to an authentication failure. | ||||
| NlgpCondId4360ReceptacleOverCurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.4360 | |||
node · current The system has detected a receptacle over current condition. | ||||
| NlgpCondId4361ReceptacleUnderCurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.4361 | |||
node · current The system has detected a receptacle under current condition. | ||||
| NlgpCondId4382SystemInputCurrentImbalance | 1.3.6.1.4.1.476.1.42.3.2.7.1.4382 | |||
node · current System Input Currents are Imbalanced. | ||||
| NlgpCondId4383BypassStaticSwitchOffExtrnl | 1.3.6.1.4.1.476.1.42.3.2.7.1.4383 | |||
node · current Bypass static switch is off due to the state of an external signal. | ||||
| NlgpCondId4384BatteryEoDDisconnect | 1.3.6.1.4.1.476.1.42.3.2.7.1.4384 | |||
node · current Battery disconnect due to end-of-discharge. | ||||
| NlgpCondId4389SystemOutputFault | 1.3.6.1.4.1.476.1.42.3.2.7.1.4389 | |||
node · current A fault has been detected in the system output. | ||||
| NlgpCondId4390InverterOffExternal | 1.3.6.1.4.1.476.1.42.3.2.7.1.4390 | |||
node · current Inverter is off (operation is inhibited) due to external signal state. | ||||
| NlgpCondId4391InverterStaticSwitchSCRShort | 1.3.6.1.4.1.476.1.42.3.2.7.1.4391 | |||
node · current The system has detected a short across one or more inverter static switch Silicon Controlled Rectifiers (SCR). | ||||
| NlgpCondId4392TemperatureSensorError | 1.3.6.1.4.1.476.1.42.3.2.7.1.4392 | |||
node · current One or more temperature sensors cannot provide a valid temperature reading (i.e. sensor failure, wiring failure, sense circuit failure, etc). | ||||
| NlgpCondId4406BranchOverCurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.4406 | |||
node · current The system has detected a module over current condition. | ||||
| NlgpCondId4407BranchUnderCurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.4407 | |||
node · current The system has detected a module under current condition. | ||||
| NlgpCondId4416BranchOverCurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.4416 | |||
node · current The system has detected a module over current condition. | ||||
| NlgpCondId4417BranchUnderCurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.4417 | |||
node · current The system has detected a module under current condition. | ||||
| NlgpCondId4421BranchFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.4421 | |||
node · current One or more conditions indicate a Branch Receptacle Module failure , service is required. | ||||
| NlgpCondId4436PDUOverCurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.4436 | |||
node · current The system has detected a module over current condition. | ||||
| NlgpCondId4437PDUUnderCurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.4437 | |||
node · current The system has detected a module under current condition. | ||||
| NlgpCondId4438SystemInternalTemperatureRise | 1.3.6.1.4.1.476.1.42.3.2.7.1.4438 | |||
node · current Excessive temperature rise internal to the system (i.e. difference between the output versus input temperature is too large). | ||||
| NlgpCondId4439AutomaticRestartFailed | 1.3.6.1.4.1.476.1.42.3.2.7.1.4439 | |||
node · current Automatic restart failed. | ||||
| NlgpCondId4440FuseFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.4440 | |||
node · current A summary event indicating one or more fuse failures. | ||||
| NlgpCondId4441SystemControllerError | 1.3.6.1.4.1.476.1.42.3.2.7.1.4441 | |||
node · current System controller internal error. | ||||
| NlgpCondId4442SystemBreakersOpenFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.4442 | |||
node · current One or more breakers in the system failed to open. | ||||
| NlgpCondId4448PDUOverCurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.4448 | |||
node · current The system has detected a module over current condition. | ||||
| NlgpCondId4449PDUUnderCurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.4449 | |||
node · current The system has detected a module under current condition. | ||||
| NlgpCondId4468PDUOverCurrentL1 | 1.3.6.1.4.1.476.1.42.3.2.7.1.4468 | |||
node · current The system has detected a module over current condition on line 1. | ||||
| NlgpCondId4469PDUOverCurrentL2 | 1.3.6.1.4.1.476.1.42.3.2.7.1.4469 | |||
node · current The system has detected a module over current condition on line 2. | ||||
| NlgpCondId4470PDUOverCurrentL3 | 1.3.6.1.4.1.476.1.42.3.2.7.1.4470 | |||
node · current The system has detected a module over current condition on line 3. | ||||
| NlgpCondId4471PDUUnderCurrentL1 | 1.3.6.1.4.1.476.1.42.3.2.7.1.4471 | |||
node · current The system has detected a module under current condition on line 1. | ||||
| NlgpCondId4472PDUUnderCurrentL2 | 1.3.6.1.4.1.476.1.42.3.2.7.1.4472 | |||
node · current The system has detected a module under current condition on line 2. | ||||
| NlgpCondId4473PDUUnderCurrentL3 | 1.3.6.1.4.1.476.1.42.3.2.7.1.4473 | |||
node · current The system has detected a module under current condition on line 3. | ||||
| NlgpCondId4492ReceptaclePowerStateOn | 1.3.6.1.4.1.476.1.42.3.2.7.1.4492 | |||
node · current The receptacle power state changed to the ON state. | ||||
| NlgpCondId4493ReceptaclePowerStateOff | 1.3.6.1.4.1.476.1.42.3.2.7.1.4493 | |||
node · current The receptacle power state changed to the OFF state. | ||||
| NlgpCondId4494BranchBreakerOpen | 1.3.6.1.4.1.476.1.42.3.2.7.1.4494 | |||
node · current The Branch Receptacle Module's input breaker is open. | ||||
| NlgpCondId4495DeviceConfigurationChange | 1.3.6.1.4.1.476.1.42.3.2.7.1.4495 | |||
node · current Device Configuration Change. | ||||
| NlgpCondId4496BasicDisplayModuleRemoved | 1.3.6.1.4.1.476.1.42.3.2.7.1.4496 | |||
node · current Basic Display Module Removed. | ||||
| NlgpCondId4497BasicDisplayModuleDiscovered | 1.3.6.1.4.1.476.1.42.3.2.7.1.4497 | |||
node · current Basic Display Module Discovered. | ||||
| NlgpCondId4500PDUOverCurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.4500 | |||
node · current The system has detected a power module over current condition. | ||||
| NlgpCondId4501PDUUnderCurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.4501 | |||
node · current The system has detected a power module under current condition. | ||||
| NlgpCondId4502PDUFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.4502 | |||
node · current One or more conditions indicate a power module failure, service is required. | ||||
| NlgpCondId4503PDUCommunicationFail | 1.3.6.1.4.1.476.1.42.3.2.7.1.4503 | |||
node · current Internal communications failure with the Power Module. | ||||
| NlgpCondId4504BranchRemoved | 1.3.6.1.4.1.476.1.42.3.2.7.1.4504 | |||
node · current Branch Receptacle Module Removed. | ||||
| NlgpCondId4505BranchDiscovered | 1.3.6.1.4.1.476.1.42.3.2.7.1.4505 | |||
node · current Branch Receptacle Module Discovered. | ||||
| NlgpCondId4506BranchOverCurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.4506 | |||
node · current The system has detected a Branch Receptacle Module over current condition. | ||||
| NlgpCondId4507BranchCurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.4507 | |||
node · current The system has detected a Branch Receptacle Module under current condition. | ||||
| NlgpCondId4508ReceptacleLoadRemoved | 1.3.6.1.4.1.476.1.42.3.2.7.1.4508 | |||
node · current The receptacle's load stopped drawing power. | ||||
| NlgpCondId4509ReceptacleLoadAdded | 1.3.6.1.4.1.476.1.42.3.2.7.1.4509 | |||
node · current The receptacle's load started to draw power. | ||||
| NlgpCondId4523ModuleRemoved | 1.3.6.1.4.1.476.1.42.3.2.7.1.4523 | |||
node · current Module Removed. | ||||
| NlgpCondId4524ModuleAdded | 1.3.6.1.4.1.476.1.42.3.2.7.1.4524 | |||
node · current Module Added. | ||||
| NlgpCondId4550FirmwareUpdateRequired | 1.3.6.1.4.1.476.1.42.3.2.7.1.4550 | |||
node · current Module compatibility error requires a system firmware update to resolve. | ||||
| NlgpCondId4551GenericTestEvent | 1.3.6.1.4.1.476.1.42.3.2.7.1.4551 | |||
node · current A generic test event designed to evaluate system handling of events. | ||||
| NlgpCondId4580OverTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.4580 | |||
node · current An over temperature condition was detected. | ||||
| NlgpCondId4581UnderTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.4581 | |||
node · current An under temperature condition was detected. | ||||
| NlgpCondId4588OverRelativeHumidity | 1.3.6.1.4.1.476.1.42.3.2.7.1.4588 | |||
node · current An over relative humidity condition was detected. | ||||
| NlgpCondId4589UnderRelativeHumidity | 1.3.6.1.4.1.476.1.42.3.2.7.1.4589 | |||
node · current An under relative humidity condition was detected. | ||||
| NlgpCondId4601ExternalAirSensorAOverTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.4601 | |||
node · current [Ext Air Sensor A Temperature] has exceeded [External Air Over Temp Threshold]. | ||||
| NlgpCondId4604ExternalAirSensorBOverTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.4604 | |||
node · current [Ext Air Sensor B Temperature] has exceeded [External Air Over Temp Threshold]. | ||||
| NlgpCondId4608ExtAirSensorAUnderTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.4608 | |||
node · current [Ext Air Sensor A Temperature] has dropped below [Ext Air Under Temp Threshold]. | ||||
| NlgpCondId4611ExtAirSensorBUnderTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.4611 | |||
node · current [Ext Air Sensor B Temperature] has dropped below [Ext Air Under Temp Threshold]. | ||||
| NlgpCondId4615ExtDewPointOverTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.4615 | |||
node · current At least one dew point temperature reading ([Ext Air Sensor A Dew Point Temp], [Ext Air Sensor B Dew Point Temp]...) has exceeded [Ext Dew Point Over Temp Threshold]. | ||||
| NlgpCondId4618ExternalAirSensorAIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.4618 | |||
node · current The external air sensor A is disconnected or the signal is out of range. | ||||
| NlgpCondId4621ExternalAirSensorBIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.4621 | |||
node · current The external air sensor B is disconnected or the signal is out of range. | ||||
| NlgpCondId4626SupplyChilledWaterOverTemp | 1.3.6.1.4.1.476.1.42.3.2.7.1.4626 | |||
node · current [Supply Fluid Temperature] has exceeded [High Supply Fluid Temperature Threshold]. | ||||
| NlgpCondId4629SupplyChilledWaterTempSensorIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.4629 | |||
node · current The supply chilled water temperature sensor is disconnected or the signal is out of range. | ||||
| NlgpCondId4634SupplyRefrigerantOverTemp | 1.3.6.1.4.1.476.1.42.3.2.7.1.4634 | |||
node · current Event that is activated when [Supply Refrigerant Temperature] exceeds [Supply Refrig Over Temp Threshold]. The event is deactivated when the temperature drops below the threshold. | ||||
| NlgpCondId4637SupplyRefrigerantUnderTemp | 1.3.6.1.4.1.476.1.42.3.2.7.1.4637 | |||
node · current [Supply Refrigerant Temperature] has dropped below a specified threshold. | ||||
| NlgpCondId4640SupplyRefrigerantTempSensorIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.4640 | |||
node · current The supply refrigeramt temperature sensor is disconnected or the signal is out of range. | ||||
| NlgpCondId4645SupplyFluidOverTemp | 1.3.6.1.4.1.476.1.42.3.2.7.1.4645 | |||
node · current [Supply Fluid Temperature] has exceeded [Supply Fluid Over Temp Threshold]. | ||||
| NlgpCondId4648SupplyFluidUnderTemp | 1.3.6.1.4.1.476.1.42.3.2.7.1.4648 | |||
node · current [Supply Fluid Temperature] has dropped below a specified threshold. | ||||
| NlgpCondId4651SupplyFluidTempSensorIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.4651 | |||
node · current The supply fluid temperature sensor is disconnected or the signal is out of range. | ||||
| NlgpCondId4656Pump1LossofFlow | 1.3.6.1.4.1.476.1.42.3.2.7.1.4656 | |||
node · current Loss of flow is detected in pump 1. The loss of flow condition occurs when no differential pressure is detected across the pump. | ||||
| NlgpCondId4659Pump2LossofFlow | 1.3.6.1.4.1.476.1.42.3.2.7.1.4659 | |||
node · current Loss of flow is detected in pump 2. The loss of flow condition occurs when no differential pressure is detected across the pump. | ||||
| NlgpCondId4662PumpShortCycle | 1.3.6.1.4.1.476.1.42.3.2.7.1.4662 | |||
node · current Pumps have short cycled. A short cycle is defined as turning on and off a number of times over a set time period. | ||||
| NlgpCondId4669Compressor1AHighHeadPressure | 1.3.6.1.4.1.476.1.42.3.2.7.1.4669 | |||
node · current Compressor 1A high head pressure. | ||||
| NlgpCondId4672Compressor1BHighHeadPressure | 1.3.6.1.4.1.476.1.42.3.2.7.1.4672 | |||
node · current Compressor 1B high head pressure. | ||||
| NlgpCondId4675Compressor2AHighHeadPressure | 1.3.6.1.4.1.476.1.42.3.2.7.1.4675 | |||
node · current Compressor 2A high head pressure. | ||||
| NlgpCondId4678Compressor2BHighHeadPressure | 1.3.6.1.4.1.476.1.42.3.2.7.1.4678 | |||
node · current Compressor 2B high head pressure. | ||||
| NlgpCondId4681Compressor1AShortCycle | 1.3.6.1.4.1.476.1.42.3.2.7.1.4681 | |||
node · current Compressor 1A short cycle. A short cycle is defined as turning on and off a number of times over a set time period. | ||||
| NlgpCondId4684Compressor1BShortCycle | 1.3.6.1.4.1.476.1.42.3.2.7.1.4684 | |||
node · current Compressor 1B short cycle. A short cycle is defined as turning on and off a number of times over a set time period. | ||||
| NlgpCondId4687Compressor2AShortCycle | 1.3.6.1.4.1.476.1.42.3.2.7.1.4687 | |||
node · current Compressor 2A short cycle. A short cycle is defined as turning on and off a number of times over a set time period. | ||||
| NlgpCondId4690Compressor2BShortCycle | 1.3.6.1.4.1.476.1.42.3.2.7.1.4690 | |||
node · current Compressor 2B short cycle. A short cycle is defined as turning on and off a number of times over a set time period. | ||||
| NlgpCondId4693Tandem1LowSuctionPressure | 1.3.6.1.4.1.476.1.42.3.2.7.1.4693 | |||
node · current 'Tandem compressors' 1 low suction pressure. | ||||
| NlgpCondId4696Tandem2LowSuctionPressure | 1.3.6.1.4.1.476.1.42.3.2.7.1.4696 | |||
node · current 'Tandem compressors' 2 low suction pressure. | ||||
| NlgpCondId4703ChilledWaterControlValvePosition | 1.3.6.1.4.1.476.1.42.3.2.7.1.4703 | |||
node · current Chilled water valve out of position. Chilled water control valve position does not match expected value. | ||||
| NlgpCondId4711SystemCondensationDetected | 1.3.6.1.4.1.476.1.42.3.2.7.1.4711 | |||
node · current System condensation detected. | ||||
| NlgpCondId4714ShutdownLossOfPower | 1.3.6.1.4.1.476.1.42.3.2.7.1.4714 | |||
node · current System lost power. This event becomes active when the unit is powered on following an unexpected loss of power. | ||||
| NlgpCondId4720SmokeDetected | 1.3.6.1.4.1.476.1.42.3.2.7.1.4720 | |||
node · current Smoke detected. | ||||
| NlgpCondId4723WaterUnderFloor | 1.3.6.1.4.1.476.1.42.3.2.7.1.4723 | |||
node · current Water under the floor is detected. | ||||
| NlgpCondId4726ServiceRequired | 1.3.6.1.4.1.476.1.42.3.2.7.1.4726 | |||
node · current Unit requires servicing. | ||||
| NlgpCondId4729FanIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.4729 | |||
node · current One or more fans are not operating within their operational parameters. | ||||
| NlgpCondId4732ReceptacleLoadDropped | 1.3.6.1.4.1.476.1.42.3.2.7.1.4732 | |||
node · current The receptacle's load is not drawing power. | ||||
| NlgpCondId4740BatteryAutomaticTestInhibited | 1.3.6.1.4.1.476.1.42.3.2.7.1.4740 | |||
node · current Automatic (scheduled) battery tests are inhibited. | ||||
| NlgpCondId4741BatterySelfTest | 1.3.6.1.4.1.476.1.42.3.2.7.1.4741 | |||
node · current Battery self test is in progress. | ||||
| NlgpCondId4742BatteryLowShutdown | 1.3.6.1.4.1.476.1.42.3.2.7.1.4742 | |||
node · current Battery disconnect due to end-of-discharge. | ||||
| NlgpCondId4747EquipmentTemperatureSensorFail | 1.3.6.1.4.1.476.1.42.3.2.7.1.4747 | |||
node · current One or more temperature sensors report a temperature outside of the range of expected operation. | ||||
| NlgpCondId4749SystemFanFailureRedundant | 1.3.6.1.4.1.476.1.42.3.2.7.1.4749 | |||
node · current Redundant system fan failure. | ||||
| NlgpCondId4750MultipleFanFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.4750 | |||
node · current Multiple fan failure. | ||||
| NlgpCondId4753MainControllerFault | 1.3.6.1.4.1.476.1.42.3.2.7.1.4753 | |||
node · current A Main Controller fault has been detected. | ||||
| NlgpCondId4754SystemBreakersCloseFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.4754 | |||
node · current One or more breakers in the system failed to close. | ||||
| NlgpCondId4755InputFilterCycleLock | 1.3.6.1.4.1.476.1.42.3.2.7.1.4755 | |||
node · current The input filter disconnect is open due to exceeding the maximum number of cycles. | ||||
| NlgpCondId4756ServiceCodeActive | 1.3.6.1.4.1.476.1.42.3.2.7.1.4756 | |||
node · current Service code is running. | ||||
| NlgpCondId4757LBSActive | 1.3.6.1.4.1.476.1.42.3.2.7.1.4757 | |||
node · current The Load Bus Sync option is active. | ||||
| NlgpCondId4758LBSInhibited | 1.3.6.1.4.1.476.1.42.3.2.7.1.4758 | |||
node · current The system has detected that conditions to perform Load Bus Sync are not satisfied. | ||||
| NlgpCondId4759LeadingPowerFactor | 1.3.6.1.4.1.476.1.42.3.2.7.1.4759 | |||
node · current The leading output Power Factor has fallen below a specified value. | ||||
| NlgpCondId4760ControlsResetRequired | 1.3.6.1.4.1.476.1.42.3.2.7.1.4760 | |||
node · current A controls reset is required due to one or more critical settings changing. | ||||
| NlgpCondId4823ParallelCommWarning | 1.3.6.1.4.1.476.1.42.3.2.7.1.4823 | |||
node · current Parallel communication bus warning. | ||||
| NlgpCondId4824SystemCommFail | 1.3.6.1.4.1.476.1.42.3.2.7.1.4824 | |||
node · current Failure of a device on the multi-module system communication bus. | ||||
| NlgpCondId4825LossofRedundancy | 1.3.6.1.4.1.476.1.42.3.2.7.1.4825 | |||
node · current The multi-module collection doesn't have enough modules to satisfy the redundancy configuration. | ||||
| NlgpCondId4826BPSSStartupInhibit | 1.3.6.1.4.1.476.1.42.3.2.7.1.4826 | |||
node · current The Bypass Static Switch startup is inhibited. | ||||
| NlgpCondId4827MMSTransferInhibit | 1.3.6.1.4.1.476.1.42.3.2.7.1.4827 | |||
node · current The critical load can not be manually transferred from inverter to bypass. | ||||
| NlgpCondId4828MMSRetransferInhibit | 1.3.6.1.4.1.476.1.42.3.2.7.1.4828 | |||
node · current The critical load can not be manually retransferred from bypass to inverter. | ||||
| NlgpCondId4830MMSLossofSyncPulse | 1.3.6.1.4.1.476.1.42.3.2.7.1.4830 | |||
node · current Multi-module system loss of sync pulse. | ||||
| NlgpCondId4831MMSOverload | 1.3.6.1.4.1.476.1.42.3.2.7.1.4831 | |||
node · current Multi-module system overload. | ||||
| NlgpCondId4834MMSOnBattery | 1.3.6.1.4.1.476.1.42.3.2.7.1.4834 | |||
node · current The multi-module system is on battery. | ||||
| NlgpCondId4835MMSLowBatteryWarning | 1.3.6.1.4.1.476.1.42.3.2.7.1.4835 | |||
node · current Multi-module system low battery warning. | ||||
| NlgpCondId4906LowAmbientTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.4906 | |||
node · current The system has detected a low ambient temperature condition. | ||||
| NlgpCondId4907HighAmbientTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.4907 | |||
node · current The system has detected a high ambient temperature condition. | ||||
| NlgpCondId4908LowOverallVoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.4908 | |||
node · current The system has detected a low battery string overall voltage condition. | ||||
| NlgpCondId4909HighOverallVoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.4909 | |||
node · current The system has detected a high battery string overall voltage condition. | ||||
| NlgpCondId4910HighBatteryStringCurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.4910 | |||
node · current The system has detected a high battery string current condition. | ||||
| NlgpCondId4911LowBatteryStringFloatCurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.4911 | |||
node · current The system has detected a low battery string float current condition. | ||||
| NlgpCondId4912HighBatteryStringFloatCurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.4912 | |||
node · current The system has detected a high battery string float current condition. | ||||
| NlgpCondId4913HighBatteryStringRippleCurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.4913 | |||
node · current The system has detected a high battery string ripple current condition. | ||||
| NlgpCondId4914BatteryStringDischargeDetected | 1.3.6.1.4.1.476.1.42.3.2.7.1.4914 | |||
node · current The system has detected a battery string discharge condition. | ||||
| NlgpCondId4915MaximumDischargeTimeExceeded | 1.3.6.1.4.1.476.1.42.3.2.7.1.4915 | |||
node · current The system has detected an excessive discharge time condition. | ||||
| NlgpCondId4916DischargeLowOverallVoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.4916 | |||
node · current The system has detected a low battery string overall voltage condition during a discharge. | ||||
| NlgpCondId4917DischargeLowCellVoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.4917 | |||
node · current The system has detected a low cell voltage condition during a discharge. | ||||
| NlgpCondId4918DischargeHighBatteryStringCurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.4918 | |||
node · current The system has detected a high battery string current condition during a discharge. | ||||
| NlgpCondId4919ExcessiveCelltoCellTemperatureDeviation | 1.3.6.1.4.1.476.1.42.3.2.7.1.4919 | |||
node · current The system has detected an excessive cell to cell temperature deviation condition. | ||||
| NlgpCondId4920ExcessiveCelltoAmbientTemperatureDeviation | 1.3.6.1.4.1.476.1.42.3.2.7.1.4920 | |||
node · current The system has detected an excessive cell to ambient temperature deviation condition. | ||||
| NlgpCondId4964LowCellVoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.4964 | |||
node · current The system has detected a low cell voltage condition. | ||||
| NlgpCondId4965HighCellVoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.4965 | |||
node · current The system has detected a high cell voltage condition. | ||||
| NlgpCondId4966LowCellTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.4966 | |||
node · current The system has detected a low cell temperature condition. | ||||
| NlgpCondId4967HighCellTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.4967 | |||
node · current The system has detected a high cell temperature condition. | ||||
| NlgpCondId4968LowInternalResistance | 1.3.6.1.4.1.476.1.42.3.2.7.1.4968 | |||
node · current The system has detected a low internal resistance condition. | ||||
| NlgpCondId4969HighInternalResistance | 1.3.6.1.4.1.476.1.42.3.2.7.1.4969 | |||
node · current The system has detected a high internal resistance condition. | ||||
| NlgpCondId4970HighIntercellResistance | 1.3.6.1.4.1.476.1.42.3.2.7.1.4970 | |||
node · current The system has detected a high intercell resistance condition. | ||||
| NlgpCondId4978IntertierResistanceHigh | 1.3.6.1.4.1.476.1.42.3.2.7.1.4978 | |||
node · current The system has detected a high intertier resistance condition. | ||||
| NlgpCondId4980SupplyChilledWaterLossofFlow | 1.3.6.1.4.1.476.1.42.3.2.7.1.4980 | |||
node · current Supply chilled water or glycol flow is too low. | ||||
| NlgpCondId4983SupplyRefrigOverTempBand1 | 1.3.6.1.4.1.476.1.42.3.2.7.1.4983 | |||
node · current [Supply Refrigerant Temperature] is above the upper threshold specified by [Supply Refrig Temp Band 1]. | ||||
| NlgpCondId4986SupplyRefrigUnderTempBand1 | 1.3.6.1.4.1.476.1.42.3.2.7.1.4986 | |||
node · current [Supply Refrigerant Temperature] is below the lower threshold specified by [Supply Refrig Temp Band 1]. | ||||
| NlgpCondId4990SupplyRefrigOverTempBand2 | 1.3.6.1.4.1.476.1.42.3.2.7.1.4990 | |||
node · current [Supply Refrigerant Temperature] is above the upper threshold specified by [Supply Refrig Temp Band 2]. | ||||
| NlgpCondId4993SupplyRefrigUnderTempBand2 | 1.3.6.1.4.1.476.1.42.3.2.7.1.4993 | |||
node · current [Supply Refrigerant Temperature] is below the lower threshold specified by [Supply Refrig Temp Band 2]. | ||||
| NlgpCondId4996Inverter1ShortCycle | 1.3.6.1.4.1.476.1.42.3.2.7.1.4996 | |||
node · current Inverter for pump 1 has short cycled and is temporarily locked out from further operation to protect from thermal overload. A short cycle is defined as powering on and off a number of times over a set time period. | ||||
| NlgpCondId4999Inverter2ShortCycle | 1.3.6.1.4.1.476.1.42.3.2.7.1.4999 | |||
node · current Inverter for pump 2 has short cycled and is temporarily locked out from further operation to protect from thermal overload. A short cycle is defined as powering on and off a number of times over a set time period. | ||||
| NlgpCondId5015SupplyAirOverTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.5015 | |||
node · current [Supply Air Temperature] has exceeded [High Supply Air Temperature Threshold]. | ||||
| NlgpCondId5019SupplyAirUnderTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.5019 | |||
node · current [Supply Air Temperature] has dropped below [Low Supply Air Temperature Threshold]. | ||||
| NlgpCondId5023ReturnAirOverTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.5023 | |||
node · current [Return Air Temperature] has exceeded [High Return Air Temperature Threshold]. | ||||
| NlgpCondId5026SupplyAirSensorIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.5026 | |||
node · current The air sensor at the outlet of the unit is disconnected or the signal is out of range. | ||||
| NlgpCondId5034HighReturnHumidity | 1.3.6.1.4.1.476.1.42.3.2.7.1.5034 | |||
node · current [Return Humidity] has exceeded [High Return Humidity Threshold]. | ||||
| NlgpCondId5036LowReturnHumidity | 1.3.6.1.4.1.476.1.42.3.2.7.1.5036 | |||
node · current [Return Humidity] has dropped below [Low Return Humidity Threshold]. | ||||
| NlgpCondId5037HumidifierHoursExceeded | 1.3.6.1.4.1.476.1.42.3.2.7.1.5037 | |||
node · current Operating hours for the humidifier have exceeded the threshold. | ||||
| NlgpCondId5038DehumidifierHoursExceeded | 1.3.6.1.4.1.476.1.42.3.2.7.1.5038 | |||
node · current Operating hours for the dehumidifier have exceeded the threshold. | ||||
| NlgpCondId5039HumidifierUnderCurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.5039 | |||
node · current The electrical current to the humidifier has dropped below its lower threshold. | ||||
| NlgpCondId5040HumidifierOverCurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.5040 | |||
node · current The electrical current to the humidifier has exceeded its upper threshold. | ||||
| NlgpCondId5041HumidifierLowWater | 1.3.6.1.4.1.476.1.42.3.2.7.1.5041 | |||
node · current The water level in the humidifier has dropped below its threshold. | ||||
| NlgpCondId5042HumidifierCylinderWorn | 1.3.6.1.4.1.476.1.42.3.2.7.1.5042 | |||
node · current Humidifier cylinder is not operating properly and needs to be replaced. | ||||
| NlgpCondId5043HumidifierIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.5043 | |||
node · current Humidifier issue detected, causing it to be locked out. | ||||
| NlgpCondId5044ExtHumidifierLockout | 1.3.6.1.4.1.476.1.42.3.2.7.1.5044 | |||
node · current The humidifier is shut down and disabled by an external input signal. | ||||
| NlgpCondId5045HumidifierControlBoardNotDetected | 1.3.6.1.4.1.476.1.42.3.2.7.1.5045 | |||
node · current Humidifier control board is required to be connected, but no signal is detected. | ||||
| NlgpCondId5046ReturnHumidityOutOfProportionalBand | 1.3.6.1.4.1.476.1.42.3.2.7.1.5046 | |||
node · current [Return Humidity] has exceeded the upper limit of [Dehumidification Proportional Band], or has dropped below the lower limit of [Humidification Proportional Band] ], for an extended period of time. | ||||
| NlgpCondId5053LossofAirFlow | 1.3.6.1.4.1.476.1.42.3.2.7.1.5053 | |||
node · current No air flow through the unit due to failure of all fans. | ||||
| NlgpCondId5054FanHoursExceeded | 1.3.6.1.4.1.476.1.42.3.2.7.1.5054 | |||
node · current Operating hours for the unit blower fan have exceeded the threshold. | ||||
| NlgpCondId5055TopFanIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.5055 | |||
node · current The top fan is not operating within its normal parameters. | ||||
| NlgpCondId5056BottomFanIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.5056 | |||
node · current The bottom fan is not operating within its normal parameters. | ||||
| NlgpCondId5060RemoteSensorIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.5060 | |||
node · current Remote sensor is disconnected or the signal is out of range. | ||||
| NlgpCondId5062Compressor1LowSuctionPressure | 1.3.6.1.4.1.476.1.42.3.2.7.1.5062 | |||
node · current Compressor 1 low suction pressure. | ||||
| NlgpCondId5063Compressor1HoursExceeded | 1.3.6.1.4.1.476.1.42.3.2.7.1.5063 | |||
node · current Operating hours for compressor 1 have exceeded the threshold. | ||||
| NlgpCondId5064DigScrollComp1TempSensorIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.5064 | |||
node · current Digital scroll compressor 1 temperature sensor is disconnected or the signal is out of range. | ||||
| NlgpCondId5065DigScrollComp1OverTemp | 1.3.6.1.4.1.476.1.42.3.2.7.1.5065 | |||
node · current Digital scroll compressor 1 shut off because its head temperature has exceeded the upper threshold. | ||||
| NlgpCondId5066Compressor1LowPressureTransducerIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.5066 | |||
node · current Compressor 1 low pressure transducer is disconnected or the signal is out of range. | ||||
| NlgpCondId5067ExtCompressorLockout | 1.3.6.1.4.1.476.1.42.3.2.7.1.5067 | |||
node · current The compressor is shut down and disabled by an external input signal. | ||||
| NlgpCondId5068ReheaterOverTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.5068 | |||
node · current The temperature of the reheater has exceeded its threshold. | ||||
| NlgpCondId5069ElectricReheater1HoursExceeded | 1.3.6.1.4.1.476.1.42.3.2.7.1.5069 | |||
node · current Operating hours for electric reheater 1 have exceeded the threshold. | ||||
| NlgpCondId5070ExtReheatLockout | 1.3.6.1.4.1.476.1.42.3.2.7.1.5070 | |||
node · current The reheater is shut down and disabled by an external input signal. | ||||
| NlgpCondId5071Condenser1Issue | 1.3.6.1.4.1.476.1.42.3.2.7.1.5071 | |||
node · current Condenser 1 is not operating within its normal parameters. | ||||
| NlgpCondId5072CondenserVFDIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.5072 | |||
node · current The condenser fan Variable Frequency Drive is offline. | ||||
| NlgpCondId5073CondenserTVSSIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.5073 | |||
node · current The condenser Transient Voltage Surge Suppressor or Surge Protection Device has failed. | ||||
| NlgpCondId5104ExtOverTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.5104 | |||
node · current A temperature has exceeded its threshold, as indicated by an external input signal. | ||||
| NlgpCondId5105ExtLossofFlow | 1.3.6.1.4.1.476.1.42.3.2.7.1.5105 | |||
node · current Loss of flow is detected, as indicated by an external input signal. | ||||
| NlgpCondId5106ExtCondenserPumpHighWater | 1.3.6.1.4.1.476.1.42.3.2.7.1.5106 | |||
node · current High water is detected in the condensate pump by the auxiliary float, as indicated by an external input signal. | ||||
| NlgpCondId5107ExtStandbyGlycolPumpOn | 1.3.6.1.4.1.476.1.42.3.2.7.1.5107 | |||
node · current The standby glycol pump is on, as indicated by an external input signal. | ||||
| NlgpCondId5108ExternalFireDetected | 1.3.6.1.4.1.476.1.42.3.2.7.1.5108 | |||
node · current Fire detected, as indicated by an external input signal. | ||||
| NlgpCondId5109UnitOn | 1.3.6.1.4.1.476.1.42.3.2.7.1.5109 | |||
node · current Unit was turned on. | ||||
| NlgpCondId5110UnitOff | 1.3.6.1.4.1.476.1.42.3.2.7.1.5110 | |||
node · current Unit was turned off. | ||||
| NlgpCondId5111UnitStandby | 1.3.6.1.4.1.476.1.42.3.2.7.1.5111 | |||
node · current Unit was placed in standby mode. | ||||
| NlgpCondId5112UnitPartialShutdown | 1.3.6.1.4.1.476.1.42.3.2.7.1.5112 | |||
node · current An event has occurred requiring some system components to be shutdown and disabled. | ||||
| NlgpCondId5113UnitShutdown | 1.3.6.1.4.1.476.1.42.3.2.7.1.5113 | |||
node · current An event has occurred requiring the unit to be shutdown and disabled to prevent damage to the system. | ||||
| NlgpCondId5114WaterLeakageDetectorSensorIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.5114 | |||
node · current The water leakage detector sensor is disconnected or the signal is out of range. | ||||
| NlgpCondId5115BMSCommunicationsTimeout | 1.3.6.1.4.1.476.1.42.3.2.7.1.5115 | |||
node · current Building Management System (or external monitoring system) has not communicated with the system within the expected timeframe. | ||||
| NlgpCondId5116MaintenanceDue | 1.3.6.1.4.1.476.1.42.3.2.7.1.5116 | |||
node · current The calculated maintenance date has been reached. | ||||
| NlgpCondId5117MaintenanceCompleted | 1.3.6.1.4.1.476.1.42.3.2.7.1.5117 | |||
node · current Maintenance has been completed on the unit. | ||||
| NlgpCondId5118CloggedAirFilter | 1.3.6.1.4.1.476.1.42.3.2.7.1.5118 | |||
node · current Air filter is dirty and needs to be (cleaned or) replaced. | ||||
| NlgpCondId5119RAMBatteryIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.5119 | |||
node · current RAM or RAM backup battery is not operating correctly. | ||||
| NlgpCondId5120MasterUnitCommunicationLost | 1.3.6.1.4.1.476.1.42.3.2.7.1.5120 | |||
node · current Communication with master unit has been lost. | ||||
| NlgpCondId5121HighPowerShutdown | 1.3.6.1.4.1.476.1.42.3.2.7.1.5121 | |||
node · current Supply to high power components has been shutdown. | ||||
| NlgpCondId5126DigScrollComp2OverTemp | 1.3.6.1.4.1.476.1.42.3.2.7.1.5126 | |||
node · current Digital scroll compressor 2 shut off because its head temperature has exceeded the upper threshold. | ||||
| NlgpCondId5144OutputOfUf | 1.3.6.1.4.1.476.1.42.3.2.7.1.5144 | |||
node · current The output frequency has exceeded a specified range for a specified period of time. | ||||
| NlgpCondId5145MMSModuleAlarmActive | 1.3.6.1.4.1.476.1.42.3.2.7.1.5145 | |||
node · current Active alarm or fault of any module in a multi-module system. | ||||
| NlgpCondId5146CompressorPumpDownIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.5146 | |||
node · current Unable to pump down suction-side pressure during compressor shutdown. | ||||
| NlgpCondId5147ReturnAirSensorIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.5147 | |||
node · current The air sensor at the inlet of the unit is disconnected or the signal is out of range. | ||||
| NlgpCondId5148CompressorHighPressureTransducerIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.5148 | |||
node · current Compressor high pressure transducer is disconnected or the signal is out of range. | ||||
| NlgpCondId5149BatteryNotQualified | 1.3.6.1.4.1.476.1.42.3.2.7.1.5149 | |||
node · current The UPS battery voltage is not qualified. This event will be detected even in the absence of battery disconnect or when it is open. | ||||
| NlgpCondId5150BatteryTerminalsReversed | 1.3.6.1.4.1.476.1.42.3.2.7.1.5150 | |||
node · current The measured battery voltage is a negative value due to reverse battery terminal connections. | ||||
| NlgpCondId5151BatteryConverterFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.5151 | |||
node · current Battery converter failure. This is a summary event caused by one or more power sub-modules in a UPS module. | ||||
| NlgpCondId5152InverterSCROpen | 1.3.6.1.4.1.476.1.42.3.2.7.1.5152 | |||
node · current The system has detected an open across one or more inverter static switch Silicon Controlled Rectifiers. | ||||
| NlgpCondId5153LoadSharingFault | 1.3.6.1.4.1.476.1.42.3.2.7.1.5153 | |||
node · current Difference between any phase inverter current of unit and the relevant average output current of parallel system is more than a specific percent of nominal current. | ||||
| NlgpCondId5154DCBusAbnormal | 1.3.6.1.4.1.476.1.42.3.2.7.1.5154 | |||
node · current The system has detected an abnormal DC Bus Voltage. | ||||
| NlgpCondId5155MainsInputNeutralLost | 1.3.6.1.4.1.476.1.42.3.2.7.1.5155 | |||
node · current Loss of neutral in the input source is detected. | ||||
| NlgpCondId5156LoadImpactTransfer | 1.3.6.1.4.1.476.1.42.3.2.7.1.5156 | |||
node · current On bypass as result of load impact. | ||||
| NlgpCondId5157UserOperationInvalid | 1.3.6.1.4.1.476.1.42.3.2.7.1.5157 | |||
node · current User attempted an invalid operation. | ||||
| NlgpCondId5158PowerSubModuleFault | 1.3.6.1.4.1.476.1.42.3.2.7.1.5158 | |||
node · current One or more failures detected in power module, inverter or rectifier. | ||||
| NlgpCondId5178OutputOvervoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.5178 | |||
node · current One or more of the output phase voltages has exceeded the limit. | ||||
| NlgpCondId5179OutputUndervoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.5179 | |||
node · current One or more of the output phase voltages has dropped below the limit. | ||||
| NlgpCondId5180OutputOvercurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.5180 | |||
node · current One or more of the phase currents has exceeded the limit. | ||||
| NlgpCondId5181NeutralOvercurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.5181 | |||
node · current The system's neutral current has exceeded the limit. | ||||
| NlgpCondId5182GroundOvercurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.5182 | |||
node · current System ground current has exceeded the limit. | ||||
| NlgpCondId5183OutputVoltageTHD | 1.3.6.1.4.1.476.1.42.3.2.7.1.5183 | |||
node · current The Total Harmonic Distortion of the voltage on one or more of the output phases has exceeded the limit. | ||||
| NlgpCondId5184OutputFrequencyError | 1.3.6.1.4.1.476.1.42.3.2.7.1.5184 | |||
node · current The output frequency is outside a specified range. | ||||
| NlgpCondId5185TransformerOvertemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.5185 | |||
node · current Indicates a unit transformer overtemperature condition. | ||||
| NlgpCondId5212PanelSummaryStatus | 1.3.6.1.4.1.476.1.42.3.2.7.1.5212 | |||
node · current The status for the panel. Detects and annunciates upon occurrence of any branch or panelboard main breaker active event. | ||||
| NlgpCondId5213PanelOvervoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.5213 | |||
node · current One or more of the phase voltages of this panel has exceeded the limit. | ||||
| NlgpCondId5214PanelUndervoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.5214 | |||
node · current One or more of the phase voltages of this panel is less than the limit. | ||||
| NlgpCondId5215PanelOvercurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.5215 | |||
node · current One or more of the phase currents of this panel has exceeded the limit. | ||||
| NlgpCondId5216PanelNeutralOvercurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.5216 | |||
node · current The Neutral current of this panel has exceeded the limit. | ||||
| NlgpCondId5217PanelGroundOvercurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.5217 | |||
node · current The Ground current of this panel has exceeded the limit. | ||||
| NlgpCondId5226BranchOvercurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.5226 | |||
node · current The current in one or more phases of this branch exceeds the limit. | ||||
| NlgpCondId5227BranchUndercurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.5227 | |||
node · current The current in one or more phases of this branch is less than the limit. | ||||
| NlgpCondId5245SubfeedPhaseOvercurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.5245 | |||
node · current One or more of the phase currents in this subfeed has exceeded the limit. | ||||
| NlgpCondId5246SubfeedNeutralOvercurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.5246 | |||
node · current The Neutral current in this subfeed has exceeded the limit. | ||||
| NlgpCondId5247SubfeedGroundOvercurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.5247 | |||
node · current The Ground current of this subfeed has exceeded the limit. | ||||
| NlgpCondId5249EventState | 1.3.6.1.4.1.476.1.42.3.2.7.1.5249 | |||
node · current The present state of this digital event input. | ||||
| NlgpCondId5263CompressorNotStopping | 1.3.6.1.4.1.476.1.42.3.2.7.1.5263 | |||
node · current Compressor commanded to stop, but continues to run. | ||||
| NlgpCondId5269CompressorHoursExceeded | 1.3.6.1.4.1.476.1.42.3.2.7.1.5269 | |||
node · current [Compressor Hours] has exceeded [Compressor Hours Threshold]. | ||||
| NlgpCondId5270CompressorHighHeadPressure | 1.3.6.1.4.1.476.1.42.3.2.7.1.5270 | |||
node · current Compressor is shut down due to high head pressure. | ||||
| NlgpCondId5271CompressorLowSuctionPressure | 1.3.6.1.4.1.476.1.42.3.2.7.1.5271 | |||
node · current Compressor is shut down due to low suction pressure. | ||||
| NlgpCondId5272CompressorThermalOverload | 1.3.6.1.4.1.476.1.42.3.2.7.1.5272 | |||
node · current Compressor is shut down due to thermal overload. | ||||
| NlgpCondId5273CompressorLowOilPressure | 1.3.6.1.4.1.476.1.42.3.2.7.1.5273 | |||
node · current Compressor low oil pressure. | ||||
| NlgpCondId5274CompressorHeadPressureOverThreshold | 1.3.6.1.4.1.476.1.42.3.2.7.1.5274 | |||
node · current Compressor head pressure has exceeded an upper threshold. | ||||
| NlgpCondId5275CompressorLossofDifferentialPressure | 1.3.6.1.4.1.476.1.42.3.2.7.1.5275 | |||
node · current Compressor is shut down due to low differential pressure. | ||||
| NlgpCondId5277CondenserFanIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.5277 | |||
node · current Condenser fan is not operating within its operational parameters. | ||||
| NlgpCondId5278LowCondenserRefrigerantPressure | 1.3.6.1.4.1.476.1.42.3.2.7.1.5278 | |||
node · current Refrigerant pressure in condenser coil is too low. | ||||
| NlgpCondId5280LowFluidPressure | 1.3.6.1.4.1.476.1.42.3.2.7.1.5280 | |||
node · current [Fluid Pressure] has dropped below a specified threshold. | ||||
| NlgpCondId5293ReturnFluidOverTemp | 1.3.6.1.4.1.476.1.42.3.2.7.1.5293 | |||
node · current [Return Fluid Temperature] has exceeded a specified threshold. | ||||
| NlgpCondId5294ReturnFluidUnderTemp | 1.3.6.1.4.1.476.1.42.3.2.7.1.5294 | |||
node · current [Return Fluid Temperature] has dropped below a specified threshold. | ||||
| NlgpCondId5295ReturnFluidTempSensorIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.5295 | |||
node · current The return fluid temperature sensor is disconnected or the signal is out of range. | ||||
| NlgpCondId5296TeamworkReturnFluidTempSensorIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.5296 | |||
node · current The return fluid temperature sensors for all Teamwork units are disconnected or the signals are out of range. | ||||
| NlgpCondId5297AllPumpsLossofFlow | 1.3.6.1.4.1.476.1.42.3.2.7.1.5297 | |||
node · current System is shut down due to loss of flow in all available pumps. | ||||
| NlgpCondId5300PumpHoursExceeded | 1.3.6.1.4.1.476.1.42.3.2.7.1.5300 | |||
node · current [Pump Hours] has exceeded [Pump Hours Threshold]. | ||||
| NlgpCondId5306FreeCoolingValveHoursExceeded | 1.3.6.1.4.1.476.1.42.3.2.7.1.5306 | |||
node · current [Free Cooling Valve Hours] has exceeded [Free Cooling Valve Hours Threshold]. | ||||
| NlgpCondId5308EvaporatorInletTempSensorIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.5308 | |||
node · current The evaporator inlet temperature sensor is disconnected or the signal is out of range. | ||||
| NlgpCondId5309TeamworkEvaporatorInletTempSensorIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.5309 | |||
node · current The evaporator inlet temperature sensors for all Teamwork units are disconnected or the signals are out of range. | ||||
| NlgpCondId5310EvaporatorFluidFreezeAutoReset | 1.3.6.1.4.1.476.1.42.3.2.7.1.5310 | |||
node · current Evaporator outlet fluid temperature has dropped below the freeze threshold. Evaporator has been shut down, but will restart when the temperature rises above the threshold. | ||||
| NlgpCondId5311EvaporatorFluidFreezeManualResetRequired | 1.3.6.1.4.1.476.1.42.3.2.7.1.5311 | |||
node · current Evaporator outlet fluid temperature has dropped below the freeze threshold. Evaporator has been shut down and requires a manual reset. | ||||
| NlgpCondId5315SubgroupEventOccurredDuringCommunicationLoss | 1.3.6.1.4.1.476.1.42.3.2.7.1.5315 | |||
node · current While subgroup unit communication was lost, an event occurred on the subgroup unit. Please check subgroup unit event log. | ||||
| NlgpCondId5335ReturnAirUnderTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.5335 | |||
node · current [Return Air Temperature] has dropped below [Low Return Air Temperature Threshold]. | ||||
| NlgpCondId5349ExtAirSensorAHighHumidity | 1.3.6.1.4.1.476.1.42.3.2.7.1.5349 | |||
node · current [Ext Air Sensor A Humidity] has exceeded [Ext Air Sensor A High Humidity Threshold]. | ||||
| NlgpCondId5351ExtAirSensorALowHumidity | 1.3.6.1.4.1.476.1.42.3.2.7.1.5351 | |||
node · current [Ext Air Sensor A Humidity] has dropped below [Ext Air Sensor A Low Humidity Threshold]. | ||||
| NlgpCondId5352CompressorShortCycle | 1.3.6.1.4.1.476.1.42.3.2.7.1.5352 | |||
node · current Compressor short cycle. A short cycle is defined as turning on and off a number of times over a set time period. | ||||
| NlgpCondId5354DigScrollCompDischargeTempSensorIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.5354 | |||
node · current Digital scroll compressor discharge temperature sensor is disconnected or the signal is out of range. | ||||
| NlgpCondId5355DigScrollCompOverTemp | 1.3.6.1.4.1.476.1.42.3.2.7.1.5355 | |||
node · current Digital scroll compressor is shut down due to head temperature exceeding an upper threshold. | ||||
| NlgpCondId5361ExtFreeCoolingLockout | 1.3.6.1.4.1.476.1.42.3.2.7.1.5361 | |||
node · current Free cooling is disabled by an external input signal. | ||||
| NlgpCondId5362FreeCoolingTempSensorIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.5362 | |||
node · current The free cooling fluid temperature sensor is disconnected or the signal is out of range. | ||||
| NlgpCondId5365HotWaterHotGasValveHoursExceeded | 1.3.6.1.4.1.476.1.42.3.2.7.1.5365 | |||
node · current [Hot Water / Hot Gas Valve Hours] has exceeded [Hot Water / Hot Gas Valve Hours Threshold]. | ||||
| NlgpCondId5368ElectricReheaterHoursExceeded | 1.3.6.1.4.1.476.1.42.3.2.7.1.5368 | |||
node · current [Electric Reheater Hours] has exceeded [Electric Reheaters Hours Threshold]. | ||||
| NlgpCondId5376MainFanOverload | 1.3.6.1.4.1.476.1.42.3.2.7.1.5376 | |||
node · current Main fan is shut down due to thermal overload. | ||||
| NlgpCondId5377Condenser | 1.3.6.1.4.1.476.1.42.3.2.7.1.5377 | |||
node · current Condenser is not operating within its operational parameters. | ||||
| NlgpCondId5415ExtLossofAirBlower | 1.3.6.1.4.1.476.1.42.3.2.7.1.5415 | |||
node · current Loss of air blower is detected, as indicated by an external input signal. | ||||
| NlgpCondId5416ExtStandbyUnitOn | 1.3.6.1.4.1.476.1.42.3.2.7.1.5416 | |||
node · current Standby unit is on, as indicated by an external input signal. | ||||
| NlgpCondId5417DigitalOutputBoardNotDetected | 1.3.6.1.4.1.476.1.42.3.2.7.1.5417 | |||
node · current Digital output board is required to be connected, but no signal is detected. | ||||
| NlgpCondId5418UnitCodeMissing | 1.3.6.1.4.1.476.1.42.3.2.7.1.5418 | |||
node · current Unit code has not been entered and saved. | ||||
| NlgpCondId5419UnitCommunicationLost | 1.3.6.1.4.1.476.1.42.3.2.7.1.5419 | |||
node · current Master has lost communication with one or more networked units. | ||||
| NlgpCondId5422OvertemperaturePowerOff | 1.3.6.1.4.1.476.1.42.3.2.7.1.5422 | |||
node · current Power turned off because equipment over temperature limit. | ||||
| NlgpCondId5423TooManySensors | 1.3.6.1.4.1.476.1.42.3.2.7.1.5423 | |||
node · current The number of sensors connected to the PDU exceeds the allowable limit. | ||||
| NlgpCondId5432TransformerOvertemperaturePowerOff | 1.3.6.1.4.1.476.1.42.3.2.7.1.5432 | |||
node · current Output power shutdown due to high transformer temperature. | ||||
| NlgpCondId5433TransformerOvertemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.5433 | |||
node · current Transformer temperature has exceeded the limit. | ||||
| NlgpCondId5434TransformerTemperatureSensorFail | 1.3.6.1.4.1.476.1.42.3.2.7.1.5434 | |||
node · current Transformer temperature sensor has failed. | ||||
| NlgpCondId5436LowAmbientTemperatureProbeTwo | 1.3.6.1.4.1.476.1.42.3.2.7.1.5436 | |||
node · current The system has detected a low ambient temperature condition on temperature probe 2. | ||||
| NlgpCondId5437HighAmbientTemperatureProbeTwo | 1.3.6.1.4.1.476.1.42.3.2.7.1.5437 | |||
node · current The system has detected a high ambient temperature condition on temperature probe 2. | ||||
| NlgpCondId5438ThermalRunawayDetected | 1.3.6.1.4.1.476.1.42.3.2.7.1.5438 | |||
node · current The system has detected a thermal runaway condition. | ||||
| NlgpCondId5439BatteryStringEqualize | 1.3.6.1.4.1.476.1.42.3.2.7.1.5439 | |||
node · current The system has detected a battery string equalize condition. | ||||
| NlgpCondId5440BatteryStringOffline | 1.3.6.1.4.1.476.1.42.3.2.7.1.5440 | |||
node · current The system has detected the battery string is offline. | ||||
| NlgpCondId5442DischargeLowCellVoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.5442 | |||
node · current The system has detected a low cell voltage condition during a discharge. | ||||
| NlgpCondId5447MMSPowerSharing | 1.3.6.1.4.1.476.1.42.3.2.7.1.5447 | |||
node · current A module is not sharing power with the other modules in a multi -module system. | ||||
| NlgpCondId5453ModuleInStandbyIntelligentParalleling | 1.3.6.1.4.1.476.1.42.3.2.7.1.5453 | |||
node · current Module is placed into standby operation per Intelligent Paralleling. | ||||
| NlgpCondId5456ECOModeActive | 1.3.6.1.4.1.476.1.42.3.2.7.1.5456 | |||
node · current Conditions for Activation or Automatic Reactivation have been satisfied. | ||||
| NlgpCondId5457ECOModeSuspended | 1.3.6.1.4.1.476.1.42.3.2.7.1.5457 | |||
node · current ECO Mode session is suspended. | ||||
| NlgpCondId5458ExcessECOSuspends | 1.3.6.1.4.1.476.1.42.3.2.7.1.5458 | |||
node · current Number of automatic suspensions has exceeded the ECO Mode - Maximum Auto Suspensions setting. | ||||
| NlgpCondId5471DoorOpen | 1.3.6.1.4.1.476.1.42.3.2.7.1.5471 | |||
node · current An open door was detected. | ||||
| NlgpCondId5472DoorSensorDisconnected | 1.3.6.1.4.1.476.1.42.3.2.7.1.5472 | |||
node · current Door sensor disconnect detected. | ||||
| NlgpCondId5479ContactClosureOpen | 1.3.6.1.4.1.476.1.42.3.2.7.1.5479 | |||
node · current An open circuit was detected. | ||||
| NlgpCondId5480ContactClosureClosed | 1.3.6.1.4.1.476.1.42.3.2.7.1.5480 | |||
node · current A closed circuit was detected. | ||||
| NlgpCondId5492ExtSystemCondensationDetected | 1.3.6.1.4.1.476.1.42.3.2.7.1.5492 | |||
node · current External system condensation detected. | ||||
| NlgpCondId5495ExtFanIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.5495 | |||
node · current One or more fans are not operating within their operational parameters. | ||||
| NlgpCondId5500ExtRemoteShutdown | 1.3.6.1.4.1.476.1.42.3.2.7.1.5500 | |||
node · current Unit is shut down by a remote signal. | ||||
| NlgpCondId5505HotAisleTempOutofRange | 1.3.6.1.4.1.476.1.42.3.2.7.1.5505 | |||
node · current The air temperature in the Hot aisle is either above [Hot Aisle Over Temp Threshold] or below [Hot Aisle Under Temp Threshold]. | ||||
| NlgpCondId5508ColdAisleTempOutofRange | 1.3.6.1.4.1.476.1.42.3.2.7.1.5508 | |||
node · current The air temperature in the cold aisle is either above [Cold Aisle Over Temp Threshold] or below [Cold Aisle Under Temp Threshold]. | ||||
| NlgpCondId5512RemoteShutdown | 1.3.6.1.4.1.476.1.42.3.2.7.1.5512 | |||
node · current Unit is shut down by a remote signal. | ||||
| NlgpCondId5513CompressorCapacityReduced | 1.3.6.1.4.1.476.1.42.3.2.7.1.5513 | |||
node · current Compressor capacity has been reduced. | ||||
| NlgpCondId5514CompressorLowPressureTransducerIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.5514 | |||
node · current Compressor low pressure transducer is disconnected or the signal is out of range. | ||||
| NlgpCondId5524PDUNeutralOverCurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.5524 | |||
node · current The system has detected a neutral over current condition. | ||||
| NlgpCondId5531CondenserCommunicationLost | 1.3.6.1.4.1.476.1.42.3.2.7.1.5531 | |||
node · current Communication with condenser unit has been lost. | ||||
| NlgpCondId5535CondenserOutsideAirTempSensorIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.5535 | |||
node · current Condenser outside air temperature sensor is disconnected or the signal is out of range. | ||||
| NlgpCondId5536CondenserOutsideAirTempOutofOperatingRange | 1.3.6.1.4.1.476.1.42.3.2.7.1.5536 | |||
node · current [Condenser Outside Air Temperature] is either above an upper threshold or below a lower threshold. | ||||
| NlgpCondId5537CondenserControlBoardIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.5537 | |||
node · current The condenser control board is reporting an issue. | ||||
| NlgpCondId5539CondenserRefrigerantPressureOverThreshold | 1.3.6.1.4.1.476.1.42.3.2.7.1.5539 | |||
node · current Condenser refrigerant pressure has exceeded a threshold. | ||||
| NlgpCondId5540CondenserRefrigerantPressureUnderThreshold | 1.3.6.1.4.1.476.1.42.3.2.7.1.5540 | |||
node · current Condenser refrigerant pressure has dropped below a threshold. | ||||
| NlgpCondId5541CondenserRefrigerantPressureSensorIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.5541 | |||
node · current Condenser refrigerant pressure sensor is disconnected or the signal is out of range. | ||||
| NlgpCondId5542CondenserSupplyRefrigerantOverTemp | 1.3.6.1.4.1.476.1.42.3.2.7.1.5542 | |||
node · current Condenser supply refrigerant temperature has exceeded a threshold. | ||||
| NlgpCondId5543CondenserSupplyRefrigerantUnderTemp | 1.3.6.1.4.1.476.1.42.3.2.7.1.5543 | |||
node · current Condenser supply refrigerant temperature has dropped below a specified threshold. | ||||
| NlgpCondId5544CondenserSupplyRefrigerantTempSensorIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.5544 | |||
node · current Condenser supply refrigerant temperature sensor is disconnected or the signal is out of range. | ||||
| NlgpCondId5545CondenserMaxFanSpeedOverride | 1.3.6.1.4.1.476.1.42.3.2.7.1.5545 | |||
node · current Fan speed exceeding the maximum set point in order to alleviate a high temperature or pressure condition. | ||||
| NlgpCondId5559EvaporatorReturnFluidOverTemp | 1.3.6.1.4.1.476.1.42.3.2.7.1.5559 | |||
node · current [Evaporator Return Fluid Temperature] has exceeded a threshold. The event is deactivated when the temperature drops below the threshold. | ||||
| NlgpCondId5560EvaporatorReturnFluidUnderTemp | 1.3.6.1.4.1.476.1.42.3.2.7.1.5560 | |||
node · current [Evaporator Return Fluid Temperature] has dropped below a threshold. The event is deactivated when the temperature rises above the threshold. | ||||
| NlgpCondId5561LBSActiveMaster | 1.3.6.1.4.1.476.1.42.3.2.7.1.5561 | |||
node · current This UPS system has been selected as the functional Master Load Bus Synchronization (LBS) system. | ||||
| NlgpCondId5562LBSActiveSlave | 1.3.6.1.4.1.476.1.42.3.2.7.1.5562 | |||
node · current This UPS system is synchronized to the output bus of the UPS system that has been selected as the Master Load Bus Synchronization (LBS) system. | ||||
| NlgpCondId5563DCBusLowFault | 1.3.6.1.4.1.476.1.42.3.2.7.1.5563 | |||
node · current The DC Bus voltage has reached a critical low level. | ||||
| NlgpCondId5564FanContactorOpen | 1.3.6.1.4.1.476.1.42.3.2.7.1.5564 | |||
node · current The fan contactor is open. | ||||
| NlgpCondId5565FanContactorOpenFail | 1.3.6.1.4.1.476.1.42.3.2.7.1.5565 | |||
node · current The fan contactor failed to open. | ||||
| NlgpCondId5566FanContactorCloseFail | 1.3.6.1.4.1.476.1.42.3.2.7.1.5566 | |||
node · current The fan contactor failed to close. | ||||
| NlgpCondId5567IPInhibit | 1.3.6.1.4.1.476.1.42.3.2.7.1.5567 | |||
node · current The intelligent paralleling operation is inhibited. | ||||
| NlgpCondId5568InputUndervoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.5568 | |||
node · current One or more of the input phase voltages has dropped below the limit. | ||||
| NlgpCondId5569InputOvervoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.5569 | |||
node · current One or more of the input phase voltages has exceeded the limit. | ||||
| NlgpCondId5573AmbientAirSensorIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.5573 | |||
node · current Ambient air sensor is disconnected or the signal is out of range. | ||||
| NlgpCondId5577ExtDewPointUnderTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.5577 | |||
node · current At least one dew point temperature reading ([Ext Air Sensor A Dew Point Temp], [Ext Air Sensor B Dew Point Temp]...) has dropped below [Ext Dew Point Under Temp Threshold]. | ||||
| NlgpCondId5578DewPointOverTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.5578 | |||
node · current Dew point temperature reading has exceeded the upper threshold. | ||||
| NlgpCondId5579DewPointUnderTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.5579 | |||
node · current Dew point temperature reading has dropped below the lower threshold. | ||||
| NlgpCondId5588UnspecifiedGeneralEvent | 1.3.6.1.4.1.476.1.42.3.2.7.1.5588 | |||
node · current One or more unspecified events active. See local unit display for further details. | ||||
| NlgpCondId5593RemoteSensorAverageOverTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.5593 | |||
node · current [Remote Sensor Average Temperature] has exceeded [Remote Sensor Over Temp Threshold]. | ||||
| NlgpCondId5594RemoteSensorAverageUnderTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.5594 | |||
node · current [Remote Sensor Average Temperature] has dropped below [Remote Sensor Under Temp Threshold]. | ||||
| NlgpCondId5595RemoteSensorSystemAverageOverTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.5595 | |||
node · current [Remote Sensor System Average Temperature] has exceeded [Remote Sensor Over Temp Threshold]. | ||||
| NlgpCondId5596RemoteSensorSystemAverageUnderTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.5596 | |||
node · current [Remote Sensor System Average Temperature] has dropped below [Remote Sensor Under Temp Threshold]. | ||||
| NlgpCondId5597RemoteSensorOverTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.5597 | |||
node · current [Remote Sensor Temperature] has exceeded [Remote Sensor Over Temp Threshold]. | ||||
| NlgpCondId5598RemoteSensorUnderTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.5598 | |||
node · current [Remote Sensor Temperature] has dropped below [Remote Sensor Under Temp Threshold]. | ||||
| NlgpCondId5600AirEconomizerEmergencyOverride | 1.3.6.1.4.1.476.1.42.3.2.7.1.5600 | |||
node · current Indoor room temperature has exceeded its upper threshold and the outdoor air damper has been opened for emergency cooling. | ||||
| NlgpCondId5601AirEconomizerReducedAirflow | 1.3.6.1.4.1.476.1.42.3.2.7.1.5601 | |||
node · current Air economizer filter is dirty and needs to be cleaned or replaced. | ||||
| NlgpCondId5604CompressorSuperheatOverThreshold | 1.3.6.1.4.1.476.1.42.3.2.7.1.5604 | |||
node · current Compressor discharge refrigerant superheat temperature has exceeded an upper threshold. | ||||
| NlgpCondId5609ThermalRunawayCelltoAmbientTemperatureEvent | 1.3.6.1.4.1.476.1.42.3.2.7.1.5609 | |||
node · current The delta temperature between a cell temperature and the ambient temperature has exceeded the thermal runaway cell to ambient temperature threshold. | ||||
| NlgpCondId5610ThermalRunawayCelltoCellTemperatureEvent | 1.3.6.1.4.1.476.1.42.3.2.7.1.5610 | |||
node · current The delta temperature between two cells has exceeded the thermal runaway cell to cell temperature threshold. | ||||
| NlgpCondId5611ThermalRunawayChargerCurrentLevelOneEvent | 1.3.6.1.4.1.476.1.42.3.2.7.1.5611 | |||
node · current The Battery-String charger current has exceeded the thermal runaway charger current level one threshold. | ||||
| NlgpCondId5612ThermalRunawayChargerCurrentLevelTwoEvent | 1.3.6.1.4.1.476.1.42.3.2.7.1.5612 | |||
node · current The Battery-String charger current has exceeded the thermal runaway charger current level two threshold. | ||||
| NlgpCondId5617TemperatureControlSensorIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.5617 | |||
node · current The air sensor selected for cooling control is disconnected or the signal is out of range. | ||||
| NlgpCondId5621EEVSuperheatBelowThreshold | 1.3.6.1.4.1.476.1.42.3.2.7.1.5621 | |||
node · current Electronic expansion valve refrigerant low superheat event. | ||||
| NlgpCondId5622EEVDischargeTempAboveThreshold | 1.3.6.1.4.1.476.1.42.3.2.7.1.5622 | |||
node · current Electronic expansion valve refrigerant high discharge temperature event. | ||||
| NlgpCondId5623EEVBatteryIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.5623 | |||
node · current Electronic expansion valve battery cannot be recharged and needs to be replaced. | ||||
| NlgpCondId5624EEVPowerIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.5624 | |||
node · current Electronic expansion valve lost power and is running on battery backup. | ||||
| NlgpCondId5625EEVUnspecifiedGeneralEvent | 1.3.6.1.4.1.476.1.42.3.2.7.1.5625 | |||
node · current One or more unspecified electronic expansion valve events active. See local unit display for further details. | ||||
| NlgpCondId5629StaticPressureSensorIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.5629 | |||
node · current The static pressure sensor is disconnected or the signal is out of range. | ||||
| NlgpCondId5630HighStaticPressure | 1.3.6.1.4.1.476.1.42.3.2.7.1.5630 | |||
node · current High static pressure event. | ||||
| NlgpCondId5631LowStaticPressure | 1.3.6.1.4.1.476.1.42.3.2.7.1.5631 | |||
node · current Low static pressure event. | ||||
| NlgpCondId5636PumpUnspecifiedGeneralEvent | 1.3.6.1.4.1.476.1.42.3.2.7.1.5636 | |||
node · current One or more unspecified pump events active. See local unit display for further details. | ||||
| NlgpCondId5637CondenserUnitUnspecifiedGeneralEvent | 1.3.6.1.4.1.476.1.42.3.2.7.1.5637 | |||
node · current One or more unspecified condenser unit events active. See local unit display for further details. | ||||
| NlgpCondId5638CondenserCircuitUnspecifiedGeneralEvent | 1.3.6.1.4.1.476.1.42.3.2.7.1.5638 | |||
node · current One or more unspecified condenser circuit events active. See local unit display for further details. | ||||
| NlgpCondId5642SFAReservedEvent1 | 1.3.6.1.4.1.476.1.42.3.2.7.1.5642 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId5643SFAReservedEvent2 | 1.3.6.1.4.1.476.1.42.3.2.7.1.5643 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId5644SFAReservedEvent3 | 1.3.6.1.4.1.476.1.42.3.2.7.1.5644 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId5645SFAReservedEvent4 | 1.3.6.1.4.1.476.1.42.3.2.7.1.5645 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId5646SFAReservedEvent5 | 1.3.6.1.4.1.476.1.42.3.2.7.1.5646 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId5647SFAReservedEvent6 | 1.3.6.1.4.1.476.1.42.3.2.7.1.5647 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId5648SFAReservedEvent7 | 1.3.6.1.4.1.476.1.42.3.2.7.1.5648 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId5649SFAReservedEvent8 | 1.3.6.1.4.1.476.1.42.3.2.7.1.5649 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId5650SFAReservedEvent9 | 1.3.6.1.4.1.476.1.42.3.2.7.1.5650 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId5651SFAReservedEvent10 | 1.3.6.1.4.1.476.1.42.3.2.7.1.5651 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId5652SFAReservedEvent11 | 1.3.6.1.4.1.476.1.42.3.2.7.1.5652 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId5653SFAReservedEvent12 | 1.3.6.1.4.1.476.1.42.3.2.7.1.5653 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId5654SFAReservedEvent13 | 1.3.6.1.4.1.476.1.42.3.2.7.1.5654 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId5655SFAReservedEvent14 | 1.3.6.1.4.1.476.1.42.3.2.7.1.5655 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId5656SFAReservedEvent15 | 1.3.6.1.4.1.476.1.42.3.2.7.1.5656 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId5657SFAReservedEvent16 | 1.3.6.1.4.1.476.1.42.3.2.7.1.5657 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId5658SFAReservedEvent17 | 1.3.6.1.4.1.476.1.42.3.2.7.1.5658 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId5659SFAReservedEvent18 | 1.3.6.1.4.1.476.1.42.3.2.7.1.5659 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId5660SFAReservedEvent19 | 1.3.6.1.4.1.476.1.42.3.2.7.1.5660 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId5661SFAReservedEvent20 | 1.3.6.1.4.1.476.1.42.3.2.7.1.5661 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId5662SFAReservedEvent21 | 1.3.6.1.4.1.476.1.42.3.2.7.1.5662 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId5663SFAReservedEvent22 | 1.3.6.1.4.1.476.1.42.3.2.7.1.5663 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId5664SFAReservedEvent23 | 1.3.6.1.4.1.476.1.42.3.2.7.1.5664 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId5665SFAReservedEvent24 | 1.3.6.1.4.1.476.1.42.3.2.7.1.5665 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId5666SFAReservedEvent25 | 1.3.6.1.4.1.476.1.42.3.2.7.1.5666 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId5768OutletAirOvertemperatureLimit | 1.3.6.1.4.1.476.1.42.3.2.7.1.5768 | |||
node · current The difference between the outlet air temperature and inlet air temperature exceeds a specified maximum temperature. | ||||
| NlgpCondId5769EMOShutdown | 1.3.6.1.4.1.476.1.42.3.2.7.1.5769 | |||
node · current An Emergency Module Off command has been detected. | ||||
| NlgpCondId5770TopOutletFanFault | 1.3.6.1.4.1.476.1.42.3.2.7.1.5770 | |||
node · current Top outlet fan fault - one or more top outlet fans have failed. | ||||
| NlgpCondId5771MMSOverCapacity | 1.3.6.1.4.1.476.1.42.3.2.7.1.5771 | |||
node · current The multi-module system load is larger than the apparent power limit setting. | ||||
| NlgpCondId5773CompressorCapacityNormal | 1.3.6.1.4.1.476.1.42.3.2.7.1.5773 | |||
node · current Compressor has returned to normal load capacity. | ||||
| NlgpCondId5774CompressorContactorIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.5774 | |||
node · current Compressor contactor is not closing during compressor startup or is not opening during compressor shutdown. | ||||
| NlgpCondId5775UnitShutdownUnspecifiedGeneralEvent | 1.3.6.1.4.1.476.1.42.3.2.7.1.5775 | |||
node · current One or more unspecified unit shutdown events active. See local unit display for further details. | ||||
| NlgpCondId5776PDULowVoltageLN | 1.3.6.1.4.1.476.1.42.3.2.7.1.5776 | |||
node · current The system has detected a module under voltage condition (LN). | ||||
| NlgpCondId5777PDULowVoltageLL | 1.3.6.1.4.1.476.1.42.3.2.7.1.5777 | |||
node · current The system has detected a module under voltage condition (LL). | ||||
| NlgpCondId5778PDULowVoltageL1L2 | 1.3.6.1.4.1.476.1.42.3.2.7.1.5778 | |||
node · current The system has detected a line-to-line under voltage condition (L1 -L2). | ||||
| NlgpCondId5779PDULowVoltageL2L3 | 1.3.6.1.4.1.476.1.42.3.2.7.1.5779 | |||
node · current The system has detected a line-to-line under voltage condition (L2 -L3). | ||||
| NlgpCondId5780PDULowVoltageL3L1 | 1.3.6.1.4.1.476.1.42.3.2.7.1.5780 | |||
node · current The system has detected a line-to-line under voltage condition (L3 -L1). | ||||
| NlgpCondId5781PDULowVoltageL1N | 1.3.6.1.4.1.476.1.42.3.2.7.1.5781 | |||
node · current The system has detected a line to neutral under voltage condition (L1-N). | ||||
| NlgpCondId5782PDULowVoltageL2N | 1.3.6.1.4.1.476.1.42.3.2.7.1.5782 | |||
node · current The system has detected a line to neutral under voltage condition (L2-N). | ||||
| NlgpCondId5783PDULowVoltageL3N | 1.3.6.1.4.1.476.1.42.3.2.7.1.5783 | |||
node · current The system has detected a line to neutral under voltage condition (L3-N). | ||||
| NlgpCondId5784BranchLowVoltageLN | 1.3.6.1.4.1.476.1.42.3.2.7.1.5784 | |||
node · current The system has detected a module under voltage condition (LN). | ||||
| NlgpCondId5785BranchLowVoltageLL | 1.3.6.1.4.1.476.1.42.3.2.7.1.5785 | |||
node · current The system has detected a module under voltage condition (LL). | ||||
| NlgpCondId5786BranchLowVoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.5786 | |||
node · current The system has detected a module under voltage condition. | ||||
| NlgpCondId5788ContTieActive | 1.3.6.1.4.1.476.1.42.3.2.7.1.5788 | |||
node · current Continuous Power Tie Active. | ||||
| NlgpCondId5792UserkWhReset | 1.3.6.1.4.1.476.1.42.3.2.7.1.5792 | |||
node · current The user kWh accumulator was reset to zero by the operator. | ||||
| NlgpCondId5796PeakkWReset | 1.3.6.1.4.1.476.1.42.3.2.7.1.5796 | |||
node · current The Peak kW was reset. | ||||
| NlgpCondId5798BypassOverload | 1.3.6.1.4.1.476.1.42.3.2.7.1.5798 | |||
node · current Bypass overloaded, reduce load immediately. | ||||
| NlgpCondId5801LowBatteryShutdownImminent | 1.3.6.1.4.1.476.1.42.3.2.7.1.5801 | |||
node · current If active and guaranteed shutdown is enabled, a low battery reserve condition exists that will shutdown the UPS. | ||||
| NlgpCondId5806OutputOverload | 1.3.6.1.4.1.476.1.42.3.2.7.1.5806 | |||
node · current An overload exists on the output. | ||||
| NlgpCondId5807OutputOffPending | 1.3.6.1.4.1.476.1.42.3.2.7.1.5807 | |||
node · current Output off pending - shutdown imminent. | ||||
| NlgpCondId5808SystemShutdownOutputShort | 1.3.6.1.4.1.476.1.42.3.2.7.1.5808 | |||
node · current Shutdown was due to a short on the output. | ||||
| NlgpCondId5809SystemShutdownLowBattery | 1.3.6.1.4.1.476.1.42.3.2.7.1.5809 | |||
node · current Shutdown was due to a low battery condition. | ||||
| NlgpCondId5810SystemShutdownRemoteShutdown | 1.3.6.1.4.1.476.1.42.3.2.7.1.5810 | |||
node · current Shutdown was due to a remote communications shutdown command. | ||||
| NlgpCondId5811SystemShutdownHardwareFault | 1.3.6.1.4.1.476.1.42.3.2.7.1.5811 | |||
node · current Shutdown was due to an externally applied hardware control signal. | ||||
| NlgpCondId5817LossofRedundancy | 1.3.6.1.4.1.476.1.42.3.2.7.1.5817 | |||
node · current The system has an insufficient number of power modules to provide redundancy. | ||||
| NlgpCondId5818PowerModuleFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.5818 | |||
node · current One or more conditions indicate a power module failure, service is required. | ||||
| NlgpCondId5819PowerModuleWarning | 1.3.6.1.4.1.476.1.42.3.2.7.1.5819 | |||
node · current One or more power modules is reporting a warning condition. | ||||
| NlgpCondId5838PowerModuleFanFault | 1.3.6.1.4.1.476.1.42.3.2.7.1.5838 | |||
node · current The Power Module has detected a fan fault. | ||||
| NlgpCondId5839PowerModuleOverTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.5839 | |||
node · current The Power Module has detected an over temperature condition. | ||||
| NlgpCondId5840PowerModuleShutdownOverTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.5840 | |||
node · current Power Module has shutdown due to over temperature. | ||||
| NlgpCondId5842ChargerModuleFanFault | 1.3.6.1.4.1.476.1.42.3.2.7.1.5842 | |||
node · current The Charger Module has detected a fan fault. | ||||
| NlgpCondId5847BatteryModuleTemperatureSensorFault | 1.3.6.1.4.1.476.1.42.3.2.7.1.5847 | |||
node · current A Battery Module temperature sensor fault has been detected. | ||||
| NlgpCondId5848BatteryModuleOverTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.5848 | |||
node · current The Battery Module has detected an over temperature condition. | ||||
| NlgpCondId5849ReplaceBatteryModule | 1.3.6.1.4.1.476.1.42.3.2.7.1.5849 | |||
node · current The Battery Module needs to be replaced. | ||||
| NlgpCondId5850SystemShutdownTransformerOverTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.5850 | |||
node · current System shutdown due to transformer over temperature. | ||||
| NlgpCondId5851MaximumLoadAlarm | 1.3.6.1.4.1.476.1.42.3.2.7.1.5851 | |||
node · current Maximum load alarm indicating load setting has been exceeded. | ||||
| NlgpCondId5856BatteryModuleFault | 1.3.6.1.4.1.476.1.42.3.2.7.1.5856 | |||
node · current One or more battery modules are reporting a fault condition. | ||||
| NlgpCondId5857BatteryModuleWarning | 1.3.6.1.4.1.476.1.42.3.2.7.1.5857 | |||
node · current One or more battery modules are reporting a warning condition. | ||||
| NlgpCondId5862CheckAirFilter | 1.3.6.1.4.1.476.1.42.3.2.7.1.5862 | |||
node · current Please check air filter, it may need to be cleaned or replaced. | ||||
| NlgpCondId5863TransformerFanFault | 1.3.6.1.4.1.476.1.42.3.2.7.1.5863 | |||
node · current The transformer fan has failed. | ||||
| NlgpCondId5865NoLoadWarning | 1.3.6.1.4.1.476.1.42.3.2.7.1.5865 | |||
node · current Indicates the UPS has output voltage but the output current is below a set threshold [No Load Warning Current Threshold] for a set period of time [No Load Warning Delay]. | ||||
| NlgpCondId5871BatteryOverTemperatureLimit | 1.3.6.1.4.1.476.1.42.3.2.7.1.5871 | |||
node · current A battery temperature sensor is reporting a value above a predetermined limit. | ||||
| NlgpCondId5873UnexpectedMainBatteryDisconnectClosure | 1.3.6.1.4.1.476.1.42.3.2.7.1.5873 | |||
node · current The main battery disconnect has closed unexpectedly. | ||||
| NlgpCondId5874BatteryOverVoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.5874 | |||
node · current The system has detected that the battery voltage has exceeded a predetermined limit. | ||||
| NlgpCondId5875BatteryFuseFault | 1.3.6.1.4.1.476.1.42.3.2.7.1.5875 | |||
node · current One or more battery fuse faults has occurred. | ||||
| NlgpCondId5878MainBatteryDisconnectForcedToUnlock | 1.3.6.1.4.1.476.1.42.3.2.7.1.5878 | |||
node · current The main battery disconnect is forced to the unlocked state. | ||||
| NlgpCondId5879VdcBackfeed | 1.3.6.1.4.1.476.1.42.3.2.7.1.5879 | |||
node · current The voltage between battery and DC bus measurements is out of tolerance. | ||||
| NlgpCondId5880RectifierConfigurationChangeRequest | 1.3.6.1.4.1.476.1.42.3.2.7.1.5880 | |||
node · current This event indicates that the battery is not configured and PFC is not enabled. | ||||
| NlgpCondId5881RegenerationActive | 1.3.6.1.4.1.476.1.42.3.2.7.1.5881 | |||
node · current Regeneration operation is active. | ||||
| NlgpCondId5882RegenerationOperationTerminated | 1.3.6.1.4.1.476.1.42.3.2.7.1.5882 | |||
node · current Regeneration operation is not active. | ||||
| NlgpCondId5883RegenerationOperationFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.5883 | |||
node · current Regeneration operation has been terminated due to bypass source instability or unit misoperation. | ||||
| NlgpCondId5884ProgramInputContact01 | 1.3.6.1.4.1.476.1.42.3.2.7.1.5884 | |||
node · current When the signal from [Program Input Contact 01] is active the function assigned to this contact is executed. | ||||
| NlgpCondId5885ProgramInputContact02 | 1.3.6.1.4.1.476.1.42.3.2.7.1.5885 | |||
node · current When the signal from [Program Input Contact 02] is active the function assigned to this contact is executed. | ||||
| NlgpCondId5886ProgramInputContact03 | 1.3.6.1.4.1.476.1.42.3.2.7.1.5886 | |||
node · current When the signal from [Program Input Contact 03] is active the function assigned to this contact is executed. | ||||
| NlgpCondId5887ProgramInputContact04 | 1.3.6.1.4.1.476.1.42.3.2.7.1.5887 | |||
node · current When the signal from [Program Input Contact 04] is active the function assigned to this contact is executed. | ||||
| NlgpCondId5888ProgramInputContact05 | 1.3.6.1.4.1.476.1.42.3.2.7.1.5888 | |||
node · current When the signal from [Program Input Contact 05] is active the function assigned to this contact is executed. | ||||
| NlgpCondId5889ProgramInputContact06 | 1.3.6.1.4.1.476.1.42.3.2.7.1.5889 | |||
node · current When the signal from [Program Input Contact 06] is active the function assigned to this contact is executed. | ||||
| NlgpCondId5890ProgramInputContact07 | 1.3.6.1.4.1.476.1.42.3.2.7.1.5890 | |||
node · current When the signal from [Program Input Contact 07] is active the function assigned to this contact is executed. | ||||
| NlgpCondId5891ProgramInputContact08 | 1.3.6.1.4.1.476.1.42.3.2.7.1.5891 | |||
node · current When the signal from [Program Input Contact 08] is active the function assigned to this contact is executed. | ||||
| NlgpCondId5892ProgramInputContact09 | 1.3.6.1.4.1.476.1.42.3.2.7.1.5892 | |||
node · current When the signal from [Program Input Contact 09] is active the function assigned to this contact is executed. | ||||
| NlgpCondId5893ProgramInputContact10 | 1.3.6.1.4.1.476.1.42.3.2.7.1.5893 | |||
node · current When the signal from [Program Input Contact 10] is active the function assigned to this contact is executed. | ||||
| NlgpCondId5894ProgramInputContact11 | 1.3.6.1.4.1.476.1.42.3.2.7.1.5894 | |||
node · current When the signal from [Program Input Contact 11] is active the function assigned to this contact is executed. | ||||
| NlgpCondId5895ProgramInputContact12 | 1.3.6.1.4.1.476.1.42.3.2.7.1.5895 | |||
node · current When the signal from [Program Input Contact 12] is active the function assigned to this contact is executed. | ||||
| NlgpCondId5896GroundFaultDetected | 1.3.6.1.4.1.476.1.42.3.2.7.1.5896 | |||
node · current The system has detected a ground fault on a Battery-String. | ||||
| NlgpCondId5902ReturnHumiditySensorIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.5902 | |||
node · current The humidity sensor at the inlet of the unit is disconnected or the signal is out of range. | ||||
| NlgpCondId5903CompressorLowDifferentialPressureLockout | 1.3.6.1.4.1.476.1.42.3.2.7.1.5903 | |||
node · current Compressor exceeded maximum startup attempts due to low differential pressure. Compressor is shutdown and has been disabled. | ||||
| NlgpCondId5906AirflowSensorIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.5906 | |||
node · current Airflow sensor is disconnected or the signal is out of range. | ||||
| NlgpCondId5907ExtAirDamperPositionIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.5907 | |||
node · current Air damper position does not match expected value, as indicated by an external input signal. | ||||
| NlgpCondId5908ExtPowerSourceAFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.5908 | |||
node · current Unit main power source A failure, as indicated by an external input signal. | ||||
| NlgpCondId5909ExtPowerSourceBFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.5909 | |||
node · current Unit main power source B failure, as indicated by an external input signal. | ||||
| NlgpCondId5910StaticPressureSensorOutofRange | 1.3.6.1.4.1.476.1.42.3.2.7.1.5910 | |||
node · current Static pressure sensor signal is out of its configured range. | ||||
| NlgpCondId5911FluidTemperatureSensorIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.5911 | |||
node · current The fluid temperature sensor is disconnected or the signal is out of range. | ||||
| NlgpCondId5912FluidFlowSensorIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.5912 | |||
node · current The fluid flow sensor is disconnected or the signal is out of range. | ||||
| NlgpCondId5914OverDifferentialPressure | 1.3.6.1.4.1.476.1.42.3.2.7.1.5914 | |||
node · current An over differential pressure condition was detected. | ||||
| NlgpCondId5915UnderDifferentialPressure | 1.3.6.1.4.1.476.1.42.3.2.7.1.5915 | |||
node · current An under differential pressure condition was detected. | ||||
| NlgpCondId5924MixedModeLockout | 1.3.6.1.4.1.476.1.42.3.2.7.1.5924 | |||
node · current Mixed mode has been entered too many times over a rolling time period and has been temporarily disabled. Mixed mode is defined as the use of a compressor on one refrigeration circuit and the use of a refrigerant pump on the other circuit. | ||||
| NlgpCondId5928UnbalancedLoadCondition | 1.3.6.1.4.1.476.1.42.3.2.7.1.5928 | |||
node · current The system has detected a line-to-line unbalanced load condition. | ||||
| NlgpCondId5939BranchOverCurrentProtection | 1.3.6.1.4.1.476.1.42.3.2.7.1.5939 | |||
node · current The Branch Receptacle Module's over current protection is triggered. | ||||
| NlgpCondId5948BranchLowVoltageLL | 1.3.6.1.4.1.476.1.42.3.2.7.1.5948 | |||
node · current The system has detected a module under voltage condition (LL). | ||||
| NlgpCondId5957BypassInputVoltageFault | 1.3.6.1.4.1.476.1.42.3.2.7.1.5957 | |||
node · current The system has detected the bypass voltage is unqualified. | ||||
| NlgpCondId5958BatteryTemperatureOutofRange | 1.3.6.1.4.1.476.1.42.3.2.7.1.5958 | |||
node · current Battery temperature is outside of acceptable range. | ||||
| NlgpCondId5960InverterOverload | 1.3.6.1.4.1.476.1.42.3.2.7.1.5960 | |||
node · current Inverter in overload fault. | ||||
| NlgpCondId5966AuxAirTempDeviceCommunicationLost | 1.3.6.1.4.1.476.1.42.3.2.7.1.5966 | |||
node · current Communication with external auxiliary device providing an air temperature value has been lost. | ||||
| NlgpCondId5967ModbusPowerMeterCommunicationLost | 1.3.6.1.4.1.476.1.42.3.2.7.1.5967 | |||
node · current Communication with Modbus power meter has been lost. | ||||
| NlgpCondId5968InverterDesaturation | 1.3.6.1.4.1.476.1.42.3.2.7.1.5968 | |||
node · current Inverter Desaturation. | ||||
| NlgpCondId5969GenericDICFault | 1.3.6.1.4.1.476.1.42.3.2.7.1.5969 | |||
node · current The control board reports a fault - Service required. | ||||
| NlgpCondId5970GroundFault | 1.3.6.1.4.1.476.1.42.3.2.7.1.5970 | |||
node · current An AC phase to ground fault or three phase fault to ground exists on the output of the UPS. | ||||
| NlgpCondId5973InputBreakerOpen | 1.3.6.1.4.1.476.1.42.3.2.7.1.5973 | |||
node · current The main input breaker is open. | ||||
| NlgpCondId5974NeutralBreakerOpen | 1.3.6.1.4.1.476.1.42.3.2.7.1.5974 | |||
node · current The neutral breaker is open. | ||||
| NlgpCondId5975OutputBreakerOpen | 1.3.6.1.4.1.476.1.42.3.2.7.1.5975 | |||
node · current The output breaker is open. | ||||
| NlgpCondId5976MaintenanceBypassBreakerClosed | 1.3.6.1.4.1.476.1.42.3.2.7.1.5976 | |||
node · current The maintenance bypass breaker is closed. | ||||
| NlgpCondId5977BatteryBreakerOpen | 1.3.6.1.4.1.476.1.42.3.2.7.1.5977 | |||
node · current The battery circuit is open. | ||||
| NlgpCondId5978RectifierIsolationBreakerRFBOpen | 1.3.6.1.4.1.476.1.42.3.2.7.1.5978 | |||
node · current The rectifier isolation breaker (RFB) indicates that it is in the open position. | ||||
| NlgpCondId5982BypassBreakerSBBOpen | 1.3.6.1.4.1.476.1.42.3.2.7.1.5982 | |||
node · current The bypass circuit breaker (SBB) indicates that it is in the open position. | ||||
| NlgpCondId5983BypassIsolationBreakerBIBOpen | 1.3.6.1.4.1.476.1.42.3.2.7.1.5983 | |||
node · current The bypass isolation breaker (BIB) indicates that it is in the open position. | ||||
| NlgpCondId5984BypassUndervoltageWarning | 1.3.6.1.4.1.476.1.42.3.2.7.1.5984 | |||
node · current The voltage on one or more bypass phases is less than a specified percentage of the nominal voltage. | ||||
| NlgpCondId5985BypassStaticSwitchBPSSOn | 1.3.6.1.4.1.476.1.42.3.2.7.1.5985 | |||
node · current The Bypass Static Switch has been turned on. | ||||
| NlgpCondId5998BattOvtempWarning | 1.3.6.1.4.1.476.1.42.3.2.7.1.5998 | |||
node · current A battery temperature sensor is reporting a value above the setpoint. | ||||
| NlgpCondId6009InverterOutputBreakerOpen | 1.3.6.1.4.1.476.1.42.3.2.7.1.6009 | |||
node · current The inverter output breaker indicates that it is in the open position. | ||||
| NlgpCondId6011EquipmentOverTempWarning | 1.3.6.1.4.1.476.1.42.3.2.7.1.6011 | |||
node · current Equipment over temperature warning is a summary event based on the detection of at least one measured temperature exceeding a threshold. | ||||
| NlgpCondId6012EquipmentOvertemperatureLimit | 1.3.6.1.4.1.476.1.42.3.2.7.1.6012 | |||
node · current The equipment air temperature has exceeded its maximum set point. | ||||
| NlgpCondId6045RectifierInputBreakerOpen | 1.3.6.1.4.1.476.1.42.3.2.7.1.6045 | |||
node · current The rectifier isolation breaker indicates that it is in the open position. | ||||
| NlgpCondId6046LoadonUPS | 1.3.6.1.4.1.476.1.42.3.2.7.1.6046 | |||
node · current The output is being supplied power from the inverter. | ||||
| NlgpCondId6047Core2CoreFuseFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.6047 | |||
node · current Core-2-core fuse failure. | ||||
| NlgpCondId6052SystemOutputBreakerOpen | 1.3.6.1.4.1.476.1.42.3.2.7.1.6052 | |||
node · current The system output breaker is open. | ||||
| NlgpCondId6059InverterRelayFault | 1.3.6.1.4.1.476.1.42.3.2.7.1.6059 | |||
node · current The inverter relay has malfunctioned. | ||||
| NlgpCondId6060TransfertoBypassSystemOverload | 1.3.6.1.4.1.476.1.42.3.2.7.1.6060 | |||
node · current The UPS System has transferred to bypass because the active power modules cannot support the critical load. | ||||
| NlgpCondId6061InputSourceBackfeed | 1.3.6.1.4.1.476.1.42.3.2.7.1.6061 | |||
node · current The battery is backfeeding the input source. | ||||
| NlgpCondId6062LossofSynchronization | 1.3.6.1.4.1.476.1.42.3.2.7.1.6062 | |||
node · current The inverter and bypass are no longer synchronized. . | ||||
| NlgpCondId6063BatteryConverterCurrentLimit | 1.3.6.1.4.1.476.1.42.3.2.7.1.6063 | |||
node · current The battery converter has reached is maximum current limit. . | ||||
| NlgpCondId6064LBSCableFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.6064 | |||
node · current Load Bus Sync communications is abnormal. A problem with the LBS cable may exist. | ||||
| NlgpCondId6065BatteryChargeEqualizationTimeout | 1.3.6.1.4.1.476.1.42.3.2.7.1.6065 | |||
node · current The battery equalizing is time out. | ||||
| NlgpCondId6066ParallelCableFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.6066 | |||
node · current The UPS parallel system communications is abnormal. A problem with the parallel cable may exist. | ||||
| NlgpCondId6067BatteryFault | 1.3.6.1.4.1.476.1.42.3.2.7.1.6067 | |||
node · current A short circuit exists in the battery system. | ||||
| NlgpCondId6068BatteryRoomAlarm | 1.3.6.1.4.1.476.1.42.3.2.7.1.6068 | |||
node · current The ambient temperature of the battery room is abnormal. | ||||
| NlgpCondId6080UPSCCommunicationFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.6080 | |||
node · current The UPSC has failed to communicate in a designated time period. | ||||
| NlgpCondId6092Compressor1BThermalOverload | 1.3.6.1.4.1.476.1.42.3.2.7.1.6092 | |||
node · current Fixed compressor 1B is shut down due to thermal overload. | ||||
| NlgpCondId6093Compressor2BThermalOverload | 1.3.6.1.4.1.476.1.42.3.2.7.1.6093 | |||
node · current Fixed compressor 2B is shut down due to thermal overload. | ||||
| NlgpCondId6094Compressor1BHoursExceeded | 1.3.6.1.4.1.476.1.42.3.2.7.1.6094 | |||
node · current Fixed compressor 1B run hours have exceeded the threshold. | ||||
| NlgpCondId6095Compressor2BHoursExceeded | 1.3.6.1.4.1.476.1.42.3.2.7.1.6095 | |||
node · current Fixed compressor 2B run hours have exceeded the threshold. | ||||
| NlgpCondId6100CondenserRemoteShutdown | 1.3.6.1.4.1.476.1.42.3.2.7.1.6100 | |||
node · current Condenser is shut down by a remote signal. | ||||
| NlgpCondId6105ExternalCondenserTVSSIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.6105 | |||
node · current The condenser Transient Voltage Surge Suppressor or Surge Protection Device has failed, as indicated by an external input signal. | ||||
| NlgpCondId6106ExternalCondenserVFDIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.6106 | |||
node · current The condenser fan Variable Frequency Drive is offline, as indicated by an external input signal. | ||||
| NlgpCondId6107ExternalCondenserIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.6107 | |||
node · current Condenser is not operating within its operational parameters, as indicated by an external input signal. | ||||
| NlgpCondId6119Slotsnotavailable | 1.3.6.1.4.1.476.1.42.3.2.7.1.6119 | |||
node · current The number of sensors exceeds the number of allocated slots and cannot be displayed. | ||||
| NlgpCondId6180BatteryUnderVoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.6180 | |||
node · current Battery voltage is too low. | ||||
| NlgpCondId6182ReplaceBattery | 1.3.6.1.4.1.476.1.42.3.2.7.1.6182 | |||
node · current The battery is due for replacement. | ||||
| NlgpCondId6186InputFrequencyDeviation | 1.3.6.1.4.1.476.1.42.3.2.7.1.6186 | |||
node · current The input frequency is outside of the normal range. | ||||
| NlgpCondId6187ShutdownPending | 1.3.6.1.4.1.476.1.42.3.2.7.1.6187 | |||
node · current Shutdown is pending. | ||||
| NlgpCondId6194SystemRebootCommandIssued | 1.3.6.1.4.1.476.1.42.3.2.7.1.6194 | |||
node · current Reboot command issued to the system. | ||||
| NlgpCondId6203SensorAdded | 1.3.6.1.4.1.476.1.42.3.2.7.1.6203 | |||
node · current Sensor Added. | ||||
| NlgpCondId6204SensorRemoved | 1.3.6.1.4.1.476.1.42.3.2.7.1.6204 | |||
node · current Sensor Removed. | ||||
| NlgpCondId6205WaterLeakDetected | 1.3.6.1.4.1.476.1.42.3.2.7.1.6205 | |||
node · current Water leak detected. | ||||
| NlgpCondId6210FirmwareUpdateInProgress | 1.3.6.1.4.1.476.1.42.3.2.7.1.6210 | |||
node · current Firmware update has started and is in progress. | ||||
| NlgpCondId6211FirmwareUpdateCompletedSuccessfully | 1.3.6.1.4.1.476.1.42.3.2.7.1.6211 | |||
node · current Firmware update has completed successfully. | ||||
| NlgpCondId6212FirmwareUpdateCompletedUnsuccessfully | 1.3.6.1.4.1.476.1.42.3.2.7.1.6212 | |||
node · current Firmware update has completed, but was not successful. | ||||
| NlgpCondId6216PrechargeCircuitFailed | 1.3.6.1.4.1.476.1.42.3.2.7.1.6216 | |||
node · current DC Bus precharge/discharge didn't reach specified level within a specified time. | ||||
| NlgpCondId6217MemoryCardRemoved | 1.3.6.1.4.1.476.1.42.3.2.7.1.6217 | |||
node · current The memory card on the control board has been removed. | ||||
| NlgpCondId6218AutoCalibrationActive | 1.3.6.1.4.1.476.1.42.3.2.7.1.6218 | |||
node · current The system is automatically calibrating ADC channels. | ||||
| NlgpCondId6219AutoCalibrationFailed | 1.3.6.1.4.1.476.1.42.3.2.7.1.6219 | |||
node · current ADC channel calibration has failed. | ||||
| NlgpCondId6220ModuleOutputBreakerOpen | 1.3.6.1.4.1.476.1.42.3.2.7.1.6220 | |||
node · current The module output breaker is open. | ||||
| NlgpCondId6221NeutralVoltageFault | 1.3.6.1.4.1.476.1.42.3.2.7.1.6221 | |||
node · current Voltage observed on neutral line. | ||||
| NlgpCondId6222BranchLoadLoss | 1.3.6.1.4.1.476.1.42.3.2.7.1.6222 | |||
node · current Loss of load on branch detected. Branch circuit breaker might be open. | ||||
| NlgpCondId6225RemoteSensorLowHumidity | 1.3.6.1.4.1.476.1.42.3.2.7.1.6225 | |||
node · current Remote sensor humidity has dropped below a lower threshold. The event is deactivated when the humidity rises above the threshold. | ||||
| NlgpCondId6226RemoteSensorHighHumidity | 1.3.6.1.4.1.476.1.42.3.2.7.1.6226 | |||
node · current Remote sensor humidity has exceeded an upper threshold. The event is deactivated when the humidity drops below the threshold. | ||||
| NlgpCondId6227RemoteSensorAverageLowHumidity | 1.3.6.1.4.1.476.1.42.3.2.7.1.6227 | |||
node · current The average humidity of multiple remote sensors on the cooling unit has dropped below a lower threshold. The event is deactivated when the humidity rises above the threshold. | ||||
| NlgpCondId6228RemoteSensorAverageHighHumidity | 1.3.6.1.4.1.476.1.42.3.2.7.1.6228 | |||
node · current The average humidity of multiple remote sensors on the cooling unit has exceeded an upper threshold. The event is deactivated when the humidity drops below the threshold. | ||||
| NlgpCondId6229RemoteSensorSystemAverageLowHumidity | 1.3.6.1.4.1.476.1.42.3.2.7.1.6229 | |||
node · current The average humidity of multiple remote sensors on interconnected cooling units in a single system has dropped below a lower threshold. The event is deactivated when the humidity rises above the threshold. | ||||
| NlgpCondId6230RemoteSensorSystemAverageHighHumidity | 1.3.6.1.4.1.476.1.42.3.2.7.1.6230 | |||
node · current The average humidity of multiple remote sensors on interconnected cooling units in a single system has exceeded an upper threshold. The event is deactivated when the humidity drops below the threshold. | ||||
| NlgpCondId6231LowCompressorSuperheat | 1.3.6.1.4.1.476.1.42.3.2.7.1.6231 | |||
node · current Compressor suction superheat has dropped below a lower threshold. | ||||
| NlgpCondId6232SECUnspecifiedGeneralEvent | 1.3.6.1.4.1.476.1.42.3.2.7.1.6232 | |||
node · current One or more unspecified events active for the Superheat and Envelope Controller. See local unit display for further details. | ||||
| NlgpCondId6233SECCommunicationLost | 1.3.6.1.4.1.476.1.42.3.2.7.1.6233 | |||
node · current Communication with the Superheat and Envelope Controller has been lost. The event is deactivated when communication is re -established. | ||||
| NlgpCondId6236PowerSourceAIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.6236 | |||
node · current No power is detected at power source input 'A'. | ||||
| NlgpCondId6237PowerSourceBIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.6237 | |||
node · current No power is detected at power source input 'B'. | ||||
| NlgpCondId6239FluidValveHoursExceeded | 1.3.6.1.4.1.476.1.42.3.2.7.1.6239 | |||
node · current Operating hours for the fluid valve have exceeded the threshold. | ||||
| NlgpCondId6253BoosterFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.6253 | |||
node · current Booster failure - boost is off. | ||||
| NlgpCondId6254ChargerFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.6254 | |||
node · current Charger Failure - Charger is off. | ||||
| NlgpCondId6274UnitTopReturnAirSensorFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.6274 | |||
node · current Return air sensor at the top of the unit is disconnected or the signal is out of range. | ||||
| NlgpCondId6275UnitMiddleReturnAirSensorFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.6275 | |||
node · current Return air sensor in the middle of the unit is disconnected or the signal is out of range. | ||||
| NlgpCondId6276UnitBottomReturnAirSensorFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.6276 | |||
node · current Return air sensor at the bottom of the unit is disconnected or the signal is out of range. | ||||
| NlgpCondId6277UnitTopSupplyAirSensorFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.6277 | |||
node · current Supply air sensor at the top of the unit is disconnected or the signal is out of range. | ||||
| NlgpCondId6278UnitMiddleFirstSupplyAirSensorFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.6278 | |||
node · current First supply air sensor in the middle of the unit is disconnected or the signal is out of range. | ||||
| NlgpCondId6279UnitBottomSupplyAirSensorFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.6279 | |||
node · current Supply air sensor at the bottom of the unit is disconnected or the signal is out of range. | ||||
| NlgpCondId6284UnitMiddleSecondSupplyAirSensorFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.6284 | |||
node · current Second supply air sensor in the middle of the unit is disconnected or the signal is out of range. | ||||
| NlgpCondId6293ChilledWaterControlActive | 1.3.6.1.4.1.476.1.42.3.2.7.1.6293 | |||
node · current Chilled water inlet temperature control function is enabled due to 'bad' water. | ||||
| NlgpCondId6294ChilledWaterFlowTransducerFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.6294 | |||
node · current Chilled water flow transducer is disconnected or the signal is out of range. | ||||
| NlgpCondId6295ChilledWaterInletTemperatureSensorFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.6295 | |||
node · current Chilled water inlet temperature sensor is disconnected or the signal is out of range. The sensor is mandatory for the chilled water flow function. | ||||
| NlgpCondId6296ChilledWaterHighInletTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.6296 | |||
node · current Chilled water inlet temperature has exceeded an upper threshold. | ||||
| NlgpCondId6297Modbus010VModuleCommunicationFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.6297 | |||
node · current Modbus 0-10V module for managing the second Chilled Water circuit valve is disconnected or the signal is out of range. | ||||
| NlgpCondId6299RackDoorsOpen | 1.3.6.1.4.1.476.1.42.3.2.7.1.6299 | |||
node · current Rack doors opened due to supply air temperature exceeding the [Rack Door Open High Supply Air Temperature Threshold]. | ||||
| NlgpCondId6303TeamStaticPressureSensorFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.6303 | |||
node · current The team static pressure sensor is disconnected or the signal is out of range. | ||||
| NlgpCondId6304HeatingLockout | 1.3.6.1.4.1.476.1.42.3.2.7.1.6304 | |||
node · current Heating is shut down and disabled. | ||||
| NlgpCondId6305FreeCoolingStoppedHighRoomTemp | 1.3.6.1.4.1.476.1.42.3.2.7.1.6305 | |||
node · current Free cooling is temporarily disabled due to room temperature exceeding a preset delta above the the set point. | ||||
| NlgpCondId6306ColdAisleTemperatureHumidityTeamSensorFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.6306 | |||
node · current Cold aisle team sensor measuring air temperature and humidity is disconnected or the signal is out of range. | ||||
| NlgpCondId6309ColdAisleAirSensorFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.6309 | |||
node · current Cold aisle sensor measuring air temperature and humidity is disconnected or the signal is out of range. | ||||
| NlgpCondId6310ChilledWaterInletTemperatureControlActive | 1.3.6.1.4.1.476.1.42.3.2.7.1.6310 | |||
node · current Chilled water inlet temperature control is active. | ||||
| NlgpCondId6313ChilledWaterInletTemperatureSensorFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.6313 | |||
node · current Chilled water inlet temperature sensor is disconnected or the signal is out of range. | ||||
| NlgpCondId6314ChilledWaterOutletTemperatureSensorFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.6314 | |||
node · current Chilled water outlet temperature sensor is disconnected or the signal is out of range. | ||||
| NlgpCondId6315ChilledWaterFlowMeterSensorFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.6315 | |||
node · current Chilled water flow meter sensor is disconnected or the signal is out of range. | ||||
| NlgpCondId6333Bypassoutofsync | 1.3.6.1.4.1.476.1.42.3.2.7.1.6333 | |||
node · current Bypass and Inverter inputs are not in sync. | ||||
| NlgpCondId6348SystemOutputoffasrequested | 1.3.6.1.4.1.476.1.42.3.2.7.1.6348 | |||
node · current The UPS has shutdown as requested, i.e., the output is off. | ||||
| NlgpCondId6349SystemOffasrequested | 1.3.6.1.4.1.476.1.42.3.2.7.1.6349 | |||
node · current The entire UPS has shutdown as commanded. | ||||
| NlgpCondId6350GeneralFault | 1.3.6.1.4.1.476.1.42.3.2.7.1.6350 | |||
node · current A general fault in the UPS has been detected. | ||||
| NlgpCondId6351UPSAwaitingPower | 1.3.6.1.4.1.476.1.42.3.2.7.1.6351 | |||
node · current The UPS output is off and the UPS is awaiting the return of input power. | ||||
| NlgpCondId6352AutonomyCalibration | 1.3.6.1.4.1.476.1.42.3.2.7.1.6352 | |||
node · current Calibration test occurred. | ||||
| NlgpCondId6353GeneralWarning | 1.3.6.1.4.1.476.1.42.3.2.7.1.6353 | |||
node · current A warning in the UPS has been detected. | ||||
| NlgpCondId6354BatteryCharging | 1.3.6.1.4.1.476.1.42.3.2.7.1.6354 | |||
node · current The UPS battery is charging (battery charge percentage lower than 98). | ||||
| NlgpCondId6355BackfeedRelayFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.6355 | |||
node · current Bypass SCR is wrongly on or commutated. | ||||
| NlgpCondId6356BatteryCircuitOpen | 1.3.6.1.4.1.476.1.42.3.2.7.1.6356 | |||
node · current Battery Circuit Open. | ||||
| NlgpCondId6357SystemRestartPending | 1.3.6.1.4.1.476.1.42.3.2.7.1.6357 | |||
node · current A request for UPS restart has been received. | ||||
| NlgpCondId6358PipeTemperatureSensorFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.6358 | |||
node · current Air temperature sensor located in the pipe is not sending a valid value. | ||||
| NlgpCondId6362SFAReservedEvent26 | 1.3.6.1.4.1.476.1.42.3.2.7.1.6362 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId6363SFAReservedEvent27 | 1.3.6.1.4.1.476.1.42.3.2.7.1.6363 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId6364SFAReservedEvent28 | 1.3.6.1.4.1.476.1.42.3.2.7.1.6364 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId6365SFAReservedEvent29 | 1.3.6.1.4.1.476.1.42.3.2.7.1.6365 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId6366SFAReservedEvent30 | 1.3.6.1.4.1.476.1.42.3.2.7.1.6366 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId6367SFAReservedEvent31 | 1.3.6.1.4.1.476.1.42.3.2.7.1.6367 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId6368SFAReservedEvent32 | 1.3.6.1.4.1.476.1.42.3.2.7.1.6368 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId6369SFAReservedEvent33 | 1.3.6.1.4.1.476.1.42.3.2.7.1.6369 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId6370SFAReservedEvent34 | 1.3.6.1.4.1.476.1.42.3.2.7.1.6370 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId6371SFAReservedEvent35 | 1.3.6.1.4.1.476.1.42.3.2.7.1.6371 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId6372SFAReservedEvent36 | 1.3.6.1.4.1.476.1.42.3.2.7.1.6372 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId6373SFAReservedEvent37 | 1.3.6.1.4.1.476.1.42.3.2.7.1.6373 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId6374SFAReservedEvent38 | 1.3.6.1.4.1.476.1.42.3.2.7.1.6374 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId6375SFAReservedEvent39 | 1.3.6.1.4.1.476.1.42.3.2.7.1.6375 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId6376SFAReservedEvent40 | 1.3.6.1.4.1.476.1.42.3.2.7.1.6376 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId6377SFAReservedEvent41 | 1.3.6.1.4.1.476.1.42.3.2.7.1.6377 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId6378SFAReservedEvent42 | 1.3.6.1.4.1.476.1.42.3.2.7.1.6378 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId6379SFAReservedEvent43 | 1.3.6.1.4.1.476.1.42.3.2.7.1.6379 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId6380SFAReservedEvent44 | 1.3.6.1.4.1.476.1.42.3.2.7.1.6380 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId6381SFAReservedEvent45 | 1.3.6.1.4.1.476.1.42.3.2.7.1.6381 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId6382SFAReservedEvent46 | 1.3.6.1.4.1.476.1.42.3.2.7.1.6382 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId6383SFAReservedEvent47 | 1.3.6.1.4.1.476.1.42.3.2.7.1.6383 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId6384SFAReservedEvent48 | 1.3.6.1.4.1.476.1.42.3.2.7.1.6384 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId6385SFAReservedEvent49 | 1.3.6.1.4.1.476.1.42.3.2.7.1.6385 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId6386SFAReservedEvent50 | 1.3.6.1.4.1.476.1.42.3.2.7.1.6386 | |||
node · current Reserved event for SFA use. | ||||
| NlgpCondId6438PowerModuleInputCurrentAbnormal | 1.3.6.1.4.1.476.1.42.3.2.7.1.6438 | |||
node · current Input current of the power module is abnormal. | ||||
| NlgpCondId6439PowerModuleBalancerofDCBusFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.6439 | |||
node · current Balancer of DC Bus in the power module has failed. | ||||
| NlgpCondId6440PowerModuleFuseFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.6440 | |||
node · current A summary event indicating one or more fuse failures in the power module. | ||||
| NlgpCondId6441PowerModulePowerSupplyFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.6441 | |||
node · current Power module power supply failure. | ||||
| NlgpCondId6450PDUPoweredOn | 1.3.6.1.4.1.476.1.42.3.2.7.1.6450 | |||
node · current The PDU was powered on. | ||||
| NlgpCondId6453InputWiringFault | 1.3.6.1.4.1.476.1.42.3.2.7.1.6453 | |||
node · current The neutral/ground conductors on the input wiring are not properly bonded, or the line/neutral conductors have been swapped. | ||||
| NlgpCondId6454DCtoDCConverterFault | 1.3.6.1.4.1.476.1.42.3.2.7.1.6454 | |||
node · current A failure has occurred in the battery discharge circuit. | ||||
| NlgpCondId6455LeakSensorCableFault | 1.3.6.1.4.1.476.1.42.3.2.7.1.6455 | |||
node · current A fault is detected in the 'Leak Sensor' cable. | ||||
| NlgpCondId6464RebootMonitoringAgent | 1.3.6.1.4.1.476.1.42.3.2.7.1.6464 | |||
node · current Request from managed device to reboot the monitoring agent. | ||||
| NlgpCondId6474SaveIPv4SettingstoAgent | 1.3.6.1.4.1.476.1.42.3.2.7.1.6474 | |||
node · current Request from managed device for the monitoring agent to save/set IPv4 settings. | ||||
| NlgpCondId6488SaveIPv6SettingstoAgent | 1.3.6.1.4.1.476.1.42.3.2.7.1.6488 | |||
node · current Request from managed device for the monitoring agent to save/set IPv6 settings. | ||||
| NlgpCondId6508SaveLIFETMSettingstoAgent | 1.3.6.1.4.1.476.1.42.3.2.7.1.6508 | |||
node · current Request from managed device for the monitoring agent to save/set LIFE (TM) settings. | ||||
| NlgpCondId6518StandbyUnitActivatedDuetoChillerFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.6518 | |||
node · current External chiller unit has failed for this unit, so the standby cooling unit has been activated. | ||||
| NlgpCondId6522PDUResidualOverCurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.6522 | |||
node · current The system has detected a PDU residual over current condition. | ||||
| NlgpCondId6527PDUOverCurrentProtection | 1.3.6.1.4.1.476.1.42.3.2.7.1.6527 | |||
node · current The PDU over current protection is triggered. | ||||
| NlgpCondId6528PowerModuleLeverUnlocked | 1.3.6.1.4.1.476.1.42.3.2.7.1.6528 | |||
node · current The power module is inactive because the lever is in the unlocked position. | ||||
| NlgpCondId6529HardwareMismatch | 1.3.6.1.4.1.476.1.42.3.2.7.1.6529 | |||
node · current The assigned system model settings do not match the actual installed hardware. The module count is wrong, or a module of the wrong type is installed. | ||||
| NlgpCondId6530SupplyNTCAirSensorIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.6530 | |||
node · current The supply NTC air sensor is disconnected or the signal is out of range. | ||||
| NlgpCondId6531ExternalAirSensorCIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.6531 | |||
node · current The external air sensor C is disconnected or the signal is out of range. | ||||
| NlgpCondId6532ExternalAirSensorDIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.6532 | |||
node · current The external air sensor D is disconnected or the signal is out of range. | ||||
| NlgpCondId6533ExternalAirSensorEIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.6533 | |||
node · current The external air sensor E is disconnected or the signal is out of range. | ||||
| NlgpCondId6534PumpThermalOverload | 1.3.6.1.4.1.476.1.42.3.2.7.1.6534 | |||
node · current Pump is shut down due to thermal overload. | ||||
| NlgpCondId6535XDModuleCommunicationLost | 1.3.6.1.4.1.476.1.42.3.2.7.1.6535 | |||
node · current Communication with XD Module has been lost. | ||||
| NlgpCondId6536MMSCapacityExceeded | 1.3.6.1.4.1.476.1.42.3.2.7.1.6536 | |||
node · current The critical load is larger than the redundant rating of a 1+N redundant multi-module system. | ||||
| NlgpCondId6538TSAControlInputIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.6538 | |||
node · current The analog input used to set the air temperature set point for cooling control is disconnected or the signal is out of range. | ||||
| NlgpCondId6539ChilledWaterValveHoursExceeded | 1.3.6.1.4.1.476.1.42.3.2.7.1.6539 | |||
node · current [Chilled Water Valve Hours] has exceeded [Chilled Water Valve Operating Hours Threshold]. | ||||
| NlgpCondId6540FSAControlInputIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.6540 | |||
node · current The analog input used to set the air temperature set point for fan speed control is disconnected or the signal is out of range. | ||||
| NlgpCondId6541AutoTuneLicenseExpiring | 1.3.6.1.4.1.476.1.42.3.2.7.1.6541 | |||
node · current License for the AutoTune feature has not been refreshed in 30 days and will be expiring soon. | ||||
| NlgpCondId6542AutoTuneLicenseExpired | 1.3.6.1.4.1.476.1.42.3.2.7.1.6542 | |||
node · current License for the AutoTune feature has expired. | ||||
| NlgpCondId6543UnitInStandbyDueToCoolingLoss | 1.3.6.1.4.1.476.1.42.3.2.7.1.6543 | |||
node · current Unit forced into standby because it is unable to provide any cooling. | ||||
| NlgpCondId6544ControlUnitsRemoteShutdownMismatch | 1.3.6.1.4.1.476.1.42.3.2.7.1.6544 | |||
node · current The remote shutdown status of the primary control unit does not match the remote shutdown status of the secondary control unit. | ||||
| NlgpCondId6545SecondaryControlUnitCommunicationLost | 1.3.6.1.4.1.476.1.42.3.2.7.1.6545 | |||
node · current The primary control unit has lost Ethernet communications with the secondary control unit. | ||||
| NlgpCondId6546ControlUnitsUnitCodeMismatch | 1.3.6.1.4.1.476.1.42.3.2.7.1.6546 | |||
node · current Unit codes for the primary and secondary control units do not match. | ||||
| NlgpCondId6547SSAControlInputIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.6547 | |||
node · current The analog input used to set the static pressure set point for fan speed control is disconnected or the signal is out of range. | ||||
| NlgpCondId6587TransferCountCleared | 1.3.6.1.4.1.476.1.42.3.2.7.1.6587 | |||
node · current A system event indicating the transfer count has been cleared. | ||||
| NlgpCondId6588EnergyCounterCleared | 1.3.6.1.4.1.476.1.42.3.2.7.1.6588 | |||
node · current A system event indicating the energy counter (e.g. KWH) has been cleared. | ||||
| NlgpCondId6589HistoryLogsFull | 1.3.6.1.4.1.476.1.42.3.2.7.1.6589 | |||
node · current The history logs are full. | ||||
| NlgpCondId6590HistoryLogsCleared | 1.3.6.1.4.1.476.1.42.3.2.7.1.6590 | |||
node · current History logs have been cleared. | ||||
| NlgpCondId6591EventLogCleared | 1.3.6.1.4.1.476.1.42.3.2.7.1.6591 | |||
node · current All past alarms and faults have been cleared. | ||||
| NlgpCondId6592SystemDateChanged | 1.3.6.1.4.1.476.1.42.3.2.7.1.6592 | |||
node · current The system date has been updated. | ||||
| NlgpCondId6593SystemTimeChanged | 1.3.6.1.4.1.476.1.42.3.2.7.1.6593 | |||
node · current The system time has been updated. | ||||
| NlgpCondId6594AccessPasswordChanged | 1.3.6.1.4.1.476.1.42.3.2.7.1.6594 | |||
node · current The access password has been changed. | ||||
| NlgpCondId6595ConfigModified | 1.3.6.1.4.1.476.1.42.3.2.7.1.6595 | |||
node · current A setpoint has been updated. | ||||
| NlgpCondId6612SCRShort | 1.3.6.1.4.1.476.1.42.3.2.7.1.6612 | |||
node · current The SCR is in a short condition. | ||||
| NlgpCondId6613SCROpen | 1.3.6.1.4.1.476.1.42.3.2.7.1.6613 | |||
node · current The SCR is in an open condition. | ||||
| NlgpCondId6614ACPowerSupplyFail | 1.3.6.1.4.1.476.1.42.3.2.7.1.6614 | |||
node · current A failure of the AC Power Supply has been detected. | ||||
| NlgpCondId6615DCPowerSupplyFail | 1.3.6.1.4.1.476.1.42.3.2.7.1.6615 | |||
node · current A failure of the DC Power Supply has been detected. | ||||
| NlgpCondId6616VoltageSensorFail | 1.3.6.1.4.1.476.1.42.3.2.7.1.6616 | |||
node · current A voltage sensor failure has been detected. | ||||
| NlgpCondId6617SCRSensorFail | 1.3.6.1.4.1.476.1.42.3.2.7.1.6617 | |||
node · current The SCR sensor module failed. | ||||
| NlgpCondId6618CurrentSensorFail | 1.3.6.1.4.1.476.1.42.3.2.7.1.6618 | |||
node · current The current sensor module failed. | ||||
| NlgpCondId6619GateDriveFail | 1.3.6.1.4.1.476.1.42.3.2.7.1.6619 | |||
node · current The Gate Drive module failed. | ||||
| NlgpCondId6620SurgeFail | 1.3.6.1.4.1.476.1.42.3.2.7.1.6620 | |||
node · current The surge module failed for the input source. | ||||
| NlgpCondId6621FastUnderVoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.6621 | |||
node · current Fast under voltage detected. | ||||
| NlgpCondId6622SlowUnderVoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.6622 | |||
node · current Slow under voltage detected. | ||||
| NlgpCondId6623OverVoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.6623 | |||
node · current Over voltage detected. | ||||
| NlgpCondId6624OverUnderFrequencyFail | 1.3.6.1.4.1.476.1.42.3.2.7.1.6624 | |||
node · current An over or under frequency condition has been detected. | ||||
| NlgpCondId6625GeneralSourceFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.6625 | |||
node · current A non-specific failure has been detected in the source. | ||||
| NlgpCondId6626OverCurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.6626 | |||
node · current An over current has been detected. | ||||
| NlgpCondId6627PeakCurrentOffLimit | 1.3.6.1.4.1.476.1.42.3.2.7.1.6627 | |||
node · current The peak current has exceeded the setpoint defined by I-PK Xfer Lockout. | ||||
| NlgpCondId6628SyncFail | 1.3.6.1.4.1.476.1.42.3.2.7.1.6628 | |||
node · current A phase rotation/out of synchronization failure has been detected. | ||||
| NlgpCondId6629InputOverVoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.6629 | |||
node · current Input over voltage. | ||||
| NlgpCondId6630InputUnderVoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.6630 | |||
node · current Input under voltage. | ||||
| NlgpCondId6631InputOverUnderFrequency | 1.3.6.1.4.1.476.1.42.3.2.7.1.6631 | |||
node · current Input over/under frequency. | ||||
| NlgpCondId6635VoltageSenseFail | 1.3.6.1.4.1.476.1.42.3.2.7.1.6635 | |||
node · current Output voltage sense failure. | ||||
| NlgpCondId6636LoadonAlternateSource | 1.3.6.1.4.1.476.1.42.3.2.7.1.6636 | |||
node · current The load is on the alternate source. | ||||
| NlgpCondId6637UnderVoltageFail | 1.3.6.1.4.1.476.1.42.3.2.7.1.6637 | |||
node · current Output under voltage failure. | ||||
| NlgpCondId6638OutputOverCurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.6638 | |||
node · current Output is over current. | ||||
| NlgpCondId6639GroundOverCurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.6639 | |||
node · current Ground is over current. | ||||
| NlgpCondId6640NeutralOverCurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.6640 | |||
node · current Neutral is over current. | ||||
| NlgpCondId6641LoadVoltageTHD | 1.3.6.1.4.1.476.1.42.3.2.7.1.6641 | |||
node · current Load voltage THD has exceeded the set limit. | ||||
| NlgpCondId6662ControlLogicFail | 1.3.6.1.4.1.476.1.42.3.2.7.1.6662 | |||
node · current A control logic module has failed. | ||||
| NlgpCondId6663PowerSupplyLogicFail | 1.3.6.1.4.1.476.1.42.3.2.7.1.6663 | |||
node · current A power supply module has failed. | ||||
| NlgpCondId6664ExternalCommsFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.6664 | |||
node · current External communications failure. | ||||
| NlgpCondId6665HeatSinkOverTemp | 1.3.6.1.4.1.476.1.42.3.2.7.1.6665 | |||
node · current The system heat sink temperature has exceeded design limits. | ||||
| NlgpCondId6666AutomaticTransferInhibited | 1.3.6.1.4.1.476.1.42.3.2.7.1.6666 | |||
node · current Automatic transfer is inhibited. | ||||
| NlgpCondId6667InputSourceTransferInhibited | 1.3.6.1.4.1.476.1.42.3.2.7.1.6667 | |||
node · current Input source transfer is inhibited. | ||||
| NlgpCondId6676CB1ShuntTrip | 1.3.6.1.4.1.476.1.42.3.2.7.1.6676 | |||
node · current CB1 Shunt Trip event. | ||||
| NlgpCondId6677CB2ShuntTrip | 1.3.6.1.4.1.476.1.42.3.2.7.1.6677 | |||
node · current CB2 Shunt Trip event. | ||||
| NlgpCondId6678CB6NeutralOpen | 1.3.6.1.4.1.476.1.42.3.2.7.1.6678 | |||
node · current CB6 neutral open event. | ||||
| NlgpCondId6679ContactorNeutralFail | 1.3.6.1.4.1.476.1.42.3.2.7.1.6679 | |||
node · current Contactor Neutral Fail event. | ||||
| NlgpCondId6680CB1BreakerOpen | 1.3.6.1.4.1.476.1.42.3.2.7.1.6680 | |||
node · current CB1 Breaker open event. Normal state is breaker closed. Latched state is breaker open. | ||||
| NlgpCondId6681CB2BreakerOpen | 1.3.6.1.4.1.476.1.42.3.2.7.1.6681 | |||
node · current CB2 Breaker open event. Normal state is breaker closed. Latched state is breaker open. | ||||
| NlgpCondId6682CB4BreakerClosed | 1.3.6.1.4.1.476.1.42.3.2.7.1.6682 | |||
node · current CB4 breaker closed event. Normal state is breaker open. Latched state is breaker closed. | ||||
| NlgpCondId6683CB5BreakerClosed | 1.3.6.1.4.1.476.1.42.3.2.7.1.6683 | |||
node · current CB5 breaker closed event. Normal state is breaker open. Latched state is breaker closed. | ||||
| NlgpCondId6684CB3BreakerOpen | 1.3.6.1.4.1.476.1.42.3.2.7.1.6684 | |||
node · current CB3 breaker open event. Normal state is breaker closed. Latched state is breaker open. | ||||
| NlgpCondId6685CB3ABreakerOpen | 1.3.6.1.4.1.476.1.42.3.2.7.1.6685 | |||
node · current CB3A breaker open event. Normal state is breaker closed. Latched state is breaker open. | ||||
| NlgpCondId6686CB6BreakerOpen | 1.3.6.1.4.1.476.1.42.3.2.7.1.6686 | |||
node · current CB6 breaker open event. Normal state is breaker closed. Latched state is breaker open. | ||||
| NlgpCondId6687CB7BreakerOpen | 1.3.6.1.4.1.476.1.42.3.2.7.1.6687 | |||
node · current CB7 breaker open event. Normal state is breaker closed. Latched state is breaker open. | ||||
| NlgpCondId6691GroupIndependentOn | 1.3.6.1.4.1.476.1.42.3.2.7.1.6691 | |||
node · current The group standby/cascade state for this unit has been overridden. The unit has been forced on. | ||||
| NlgpCondId6692GroupIndependentOff | 1.3.6.1.4.1.476.1.42.3.2.7.1.6692 | |||
node · current The group standby/cascade state for this unit has been overridden. The unit has been forced off. | ||||
| NlgpCondId6693BranchResidualOverCurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.6693 | |||
node · current The system has detected a branch residual over current condition. | ||||
| NlgpCondId6694ReceptacleResidualOverCurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.6694 | |||
node · current The system has detected a receptacle residual over current condition. | ||||
| NlgpCondId6728BuckOn | 1.3.6.1.4.1.476.1.42.3.2.7.1.6728 | |||
node · current The input voltage is currently being bucked (lowered) by the inverter. | ||||
| NlgpCondId6729BoostOn | 1.3.6.1.4.1.476.1.42.3.2.7.1.6729 | |||
node · current The input voltage is currently being boosted (raised) by the inverter. | ||||
| NlgpCondId6739Compressor1HighPressure | 1.3.6.1.4.1.476.1.42.3.2.7.1.6739 | |||
node · current Compressor 1 High Pressure. | ||||
| NlgpCondId6740Compressor2HighPressure | 1.3.6.1.4.1.476.1.42.3.2.7.1.6740 | |||
node · current Compressor 2 High Pressure. | ||||
| NlgpCondId6741Compressor1ThermalOverload | 1.3.6.1.4.1.476.1.42.3.2.7.1.6741 | |||
node · current Compressor 1 Thermal Overload. | ||||
| NlgpCondId6742Compressor2ThermalOverload | 1.3.6.1.4.1.476.1.42.3.2.7.1.6742 | |||
node · current Compressor 2 Thermal Overload. | ||||
| NlgpCondId6758CompressorFreezeProtection | 1.3.6.1.4.1.476.1.42.3.2.7.1.6758 | |||
node · current Compressor has entered the freeze protection phase. | ||||
| NlgpCondId6773FanTemperatureCompensationLimitReached | 1.3.6.1.4.1.476.1.42.3.2.7.1.6773 | |||
node · current Unit is configured for fan temperature compensation, and the fan control set point cannot be reduced any further due to high remote air temperature sensor readings. | ||||
| NlgpCondId6774ModbusECFanCommunicationLost | 1.3.6.1.4.1.476.1.42.3.2.7.1.6774 | |||
node · current Communication with Modbus EC fan has been lost. | ||||
| NlgpCondId6785AnalogTemperatureControlIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.6785 | |||
node · current Analog input used for creating the control temperature (instead of reading a sensor) is disconnected or the signal is out of range. | ||||
| NlgpCondId6786SubgroupFirmwareUpdateRequired | 1.3.6.1.4.1.476.1.42.3.2.7.1.6786 | |||
node · current Mismatch of subgroup firmware. Both the primary and secondary control boards must be running the same firmware version. | ||||
| NlgpCondId6787SubgroupSecondaryControlUnitIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.6787 | |||
node · current Subgroup secondary control unit is reporting an unspecified issue. | ||||
| NlgpCondId6788EEVCommunicationLost | 1.3.6.1.4.1.476.1.42.3.2.7.1.6788 | |||
node · current Communication with Electronic Expansion Valve unit has been lost. | ||||
| NlgpCondId6789EEVMotorIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.6789 | |||
node · current Electronic Expansion Valve stepper motor issue. | ||||
| NlgpCondId6790EEVFeedbackIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.6790 | |||
node · current Electronic Expansion Valve feedback error. | ||||
| NlgpCondId6791EEVPressureSensorIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.6791 | |||
node · current Electronic Expansion Valve refrigerant pressure sensor is disconnected or the signal is out of range. | ||||
| NlgpCondId6792EEVCoilTemperatureSensorIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.6792 | |||
node · current Electronic Expansion Valve coil temperature sensor is disconnected or the signal is out of range. | ||||
| NlgpCondId6793EEVDischargeTemperatureSensorIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.6793 | |||
node · current Electronic Expansion Valve discharge temperature sensor is disconnected or the signal is out of range. | ||||
| NlgpCondId6794EEVSumpTemperatureSensorIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.6794 | |||
node · current Electronic Expansion Valve sump temperature sensor is disconnected or the signal is out of range. | ||||
| NlgpCondId6795EEVBatteryTestIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.6795 | |||
node · current Electronic Expansion Valve battery state cannot be determined. | ||||
| NlgpCondId6796EEVBatteryPersistentIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.6796 | |||
node · current Electronic Expansion Valve has continuously detected a 'bad' battery condition for an extended period of time. | ||||
| NlgpCondId6798PumpCycleLockOut | 1.3.6.1.4.1.476.1.42.3.2.7.1.6798 | |||
node · current Pump is locked out due to multiple pump-to-compressor transitions at cold ambient air temperature. | ||||
| NlgpCondId6799PumpBoardFirmwareUpdateRequired | 1.3.6.1.4.1.476.1.42.3.2.7.1.6799 | |||
node · current Mismatch of pump board firmware. All pump boards must be running the same firmware version. | ||||
| NlgpCondId6800PumpControlBoardIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.6800 | |||
node · current Pump is shut down due to a pump control board issue. Control board must be rebooted. | ||||
| NlgpCondId6801PumpInvalidDataShutdown | 1.3.6.1.4.1.476.1.42.3.2.7.1.6801 | |||
node · current Pump is shut down due to invalid data. | ||||
| NlgpCondId6802PumpInputPressureSensorIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.6802 | |||
node · current Pump input refrigerant pressure sensor is disconnected or the signal is out of range. | ||||
| NlgpCondId6803PumpInputTemperatureSensorIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.6803 | |||
node · current Pump input refrigerant temperature sensor is disconnected or the signal is out of range. | ||||
| NlgpCondId6804PumpOutputPressureSensorIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.6804 | |||
node · current Pump output refrigerant pressure sensor is disconnected or the signal is out of range. | ||||
| NlgpCondId6805PumpOutputTemperatureSensorIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.6805 | |||
node · current Pump output refrigerant temperature sensor is disconnected or the signal is out of range. | ||||
| NlgpCondId6806PumpCommunicationLost | 1.3.6.1.4.1.476.1.42.3.2.7.1.6806 | |||
node · current Communication with pump unit has been lost. | ||||
| NlgpCondId6807PumpRemoteShutdown | 1.3.6.1.4.1.476.1.42.3.2.7.1.6807 | |||
node · current Pump is shut down by a remote signal. | ||||
| NlgpCondId6808PumpUSBEthernetPortIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.6808 | |||
node · current Pump control board USB or Ethernet interface has failed. | ||||
| NlgpCondId6809PumpStartupFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.6809 | |||
node · current Multiple attempts to start the pump have failed. | ||||
| NlgpCondId6810PumpInverterFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.6810 | |||
node · current Pump inverter is reporting a failure. | ||||
| NlgpCondId6811PumpTVSSIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.6811 | |||
node · current Pump Transient Voltage Surge Suppressor or Surge Protection Device has failed. | ||||
| NlgpCondId6812PumpHighSuperheat | 1.3.6.1.4.1.476.1.42.3.2.7.1.6812 | |||
node · current Pump inlet refrigerant superheat temperature is too high, or the pump has been running too long with the condenser fan off. | ||||
| NlgpCondId6813CondenserHighAmbientAirTempDelta | 1.3.6.1.4.1.476.1.42.3.2.7.1.6813 | |||
node · current The difference between condenser measured ambient air temperatures has been too large for an extended period of time. | ||||
| NlgpCondId6814CondenserLeeTempOptionMismatch | 1.3.6.1.4.1.476.1.42.3.2.7.1.6814 | |||
node · current Lee-Temp option configured at a condenser unit does not match Lee -Temp option configured at the control unit. | ||||
| NlgpCondId6815CondenserBoardFirmwareUpdateRequired | 1.3.6.1.4.1.476.1.42.3.2.7.1.6815 | |||
node · current Mismatch of condenser board firmware. All condenser boards must be running the same firmware version. | ||||
| NlgpCondId6816CondenserToPumpHighRefrigerantTempDelta | 1.3.6.1.4.1.476.1.42.3.2.7.1.6816 | |||
node · current Temperature delta between the condenser output refrigerant and pump inlet refrigerant is too large. | ||||
| NlgpCondId6817CondenserRefrigerantTypeMismatch | 1.3.6.1.4.1.476.1.42.3.2.7.1.6817 | |||
node · current Refrigerant type configured at condenser unit does not match refrigerant type configured at the control unit. | ||||
| NlgpCondId6818ExternalSupplyFluidHighTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.6818 | |||
node · current Supply fluid temperature has exceeded a threshold, as indicated by an external input signal. | ||||
| NlgpCondId6819ExternalSupplyFluidTempSensorIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.6819 | |||
node · current Supply fluid temperature sensor is disconnected or the signal is out of range, as indicated by an external input signal. | ||||
| NlgpCondId6822AuditLogUpdate | 1.3.6.1.4.1.476.1.42.3.2.7.1.6822 | |||
node · current Audit log has been updated. | ||||
| NlgpCondId6824ExternalSupplyFluidFlowIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.6824 | |||
node · current Supply fluid flow issue, as indicated by an external input signal. | ||||
| NlgpCondId7163ModbusAutomaticTransferSwitchCommunicationLost | 1.3.6.1.4.1.476.1.42.3.2.7.1.7163 | |||
node · current Communications with Modbus Automatic Transfer Switch has been lost. | ||||
| NlgpCondId7164BatteryDeepDischarge | 1.3.6.1.4.1.476.1.42.3.2.7.1.7164 | |||
node · current UPS depleted the batteries to the end of discharge(EOD) voltage. | ||||
| NlgpCondId7461BatteryBreakerOpenFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.7461 | |||
node · current Battery circuit breaker failed to open. | ||||
| NlgpCondId7464LithiumIonBatterySystemAbnormal | 1.3.6.1.4.1.476.1.42.3.2.7.1.7464 | |||
node · current Lithium-Ion Battery System Abnormal. | ||||
| NlgpCondId7465LithiumIonBatterySystemDisconnectRequest | 1.3.6.1.4.1.476.1.42.3.2.7.1.7465 | |||
node · current A request to disconnect the Lithium-Ion battery system was received. | ||||
| NlgpCondId7467ThermalMarginWarning | 1.3.6.1.4.1.476.1.42.3.2.7.1.7467 | |||
node · current The thermal margin has dropped below the threshold value. | ||||
| NlgpCondId7474FlowSensorFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.7474 | |||
node · current Fluid flow sensor failure. | ||||
| NlgpCondId7475CheckWaterSystem | 1.3.6.1.4.1.476.1.42.3.2.7.1.7475 | |||
node · current Fluid check water system. | ||||
| NlgpCondId7476PumpOperatingWithoutFlow | 1.3.6.1.4.1.476.1.42.3.2.7.1.7476 | |||
node · current Fluid pump operation with no flow. | ||||
| NlgpCondId7483PumpInverterFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.7483 | |||
node · current Fluid pump inverter failure. | ||||
| NlgpCondId7484PumpFlowFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.7484 | |||
node · current Fluid pump flow failure. | ||||
| NlgpCondId7485BatteryCircuitBreakerOpen | 1.3.6.1.4.1.476.1.42.3.2.7.1.7485 | |||
node · current Battery circuit breaker is open. | ||||
| NlgpCondId7486LithiumIonBatterySystemCommunicationAbnormal | 1.3.6.1.4.1.476.1.42.3.2.7.1.7486 | |||
node · current Lithium-Ion Battery System Communication Abnormal. | ||||
| NlgpCondId7487LithiumIonBatterySystemWarning | 1.3.6.1.4.1.476.1.42.3.2.7.1.7487 | |||
node · current The Lithium-Ion Battery system has one or more warnings. | ||||
| NlgpCondId7488LithiumIonBatterySystemFault | 1.3.6.1.4.1.476.1.42.3.2.7.1.7488 | |||
node · current The Lithium-Ion Battery system has one or more faults. | ||||
| NlgpCondId7489LowSupplyAirHumidity | 1.3.6.1.4.1.476.1.42.3.2.7.1.7489 | |||
node · current Supply air humidity has dropped below a threshold. | ||||
| NlgpCondId7490HighSupplyAirHumidity | 1.3.6.1.4.1.476.1.42.3.2.7.1.7490 | |||
node · current Supply air humidity has exceeded a threshold. | ||||
| NlgpCondId7491LowRemoteAirHumidity | 1.3.6.1.4.1.476.1.42.3.2.7.1.7491 | |||
node · current Remote air humidity has dropped below a threshold. | ||||
| NlgpCondId7492HighRemoteAirHumidity | 1.3.6.1.4.1.476.1.42.3.2.7.1.7492 | |||
node · current Remote air humidity has exceeded a threshold. | ||||
| NlgpCondId7493SupplyHumiditySensorIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.7493 | |||
node · current The humidity sensor at the outlet of the unit is disconnected or the signal is out of range. | ||||
| NlgpCondId7494ExternalHumiditySensorIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.7494 | |||
node · current The external humidity sensor is disconnected or the signal is out of range. | ||||
| NlgpCondId7495ExternalAirSensorIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.7495 | |||
node · current The external air sensor is disconnected or the signal is out of range. | ||||
| NlgpCondId7496CompressorDriverFailureLockout | 1.3.6.1.4.1.476.1.42.3.2.7.1.7496 | |||
node · current Compressor lockout occurred due to multiple failures of the compressor driver board. | ||||
| NlgpCondId7497CompressorDriverFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.7497 | |||
node · current Compressor driver board failure detected. | ||||
| NlgpCondId7498CompressorDriverCommunicationFailureLockout | 1.3.6.1.4.1.476.1.42.3.2.7.1.7498 | |||
node · current Compressor lockout occurred due to multiple communication failures with the compressor driver board. | ||||
| NlgpCondId7499CompressorPressureDifferenceLockout | 1.3.6.1.4.1.476.1.42.3.2.7.1.7499 | |||
node · current Compressor lockout occurred due to multiple compressor pressure differences. | ||||
| NlgpCondId7500CompressorDriverCommunicationFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.7500 | |||
node · current A communication failure occurred with the compressor driver board. | ||||
| NlgpCondId7501CompressorPressureDifference | 1.3.6.1.4.1.476.1.42.3.2.7.1.7501 | |||
node · current Compressor pressure difference is out of range. | ||||
| NlgpCondId7503ElectricalHeaterFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.7503 | |||
node · current The electric heater temperature exceeded a threshold. | ||||
| NlgpCondId7504WaterValveFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.7504 | |||
node · current There is an issue with the chilled water valve. | ||||
| NlgpCondId7506SupplyFluidLowFlow | 1.3.6.1.4.1.476.1.42.3.2.7.1.7506 | |||
node · current Supply fluid flow has dropped below a threshold. | ||||
| NlgpCondId7507InletFluidLowPressure | 1.3.6.1.4.1.476.1.42.3.2.7.1.7507 | |||
node · current Inlet fluid pressure has dropped below a threshold. | ||||
| NlgpCondId7508InletFluidHighPressure | 1.3.6.1.4.1.476.1.42.3.2.7.1.7508 | |||
node · current Inlet fluid pressure has exceeded a threshold. | ||||
| NlgpCondId7509OutletFluidUnderTemp | 1.3.6.1.4.1.476.1.42.3.2.7.1.7509 | |||
node · current Outlet fluid temperature has dropped below a threshold. | ||||
| NlgpCondId7510OutletFluidOverTemp | 1.3.6.1.4.1.476.1.42.3.2.7.1.7510 | |||
node · current Outlet fluid temperature has exceeded a threshold. | ||||
| NlgpCondId7511InletFluidOverTemp | 1.3.6.1.4.1.476.1.42.3.2.7.1.7511 | |||
node · current Inlet fluid temperature has exceeded a threshold. | ||||
| NlgpCondId7512InletFluidUnderTemp | 1.3.6.1.4.1.476.1.42.3.2.7.1.7512 | |||
node · current Inlet fluid temperature has dropped below a threshold. | ||||
| NlgpCondId7515FanDetectionBoardCommunicationFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.7515 | |||
node · current Communication with the fan detection board has failed. | ||||
| NlgpCondId7518SurgeProtectionDeviceAlarm | 1.3.6.1.4.1.476.1.42.3.2.7.1.7518 | |||
node · current Surge Protection Device Alarm. | ||||
| NlgpCondId7519PowerOppositePhase | 1.3.6.1.4.1.476.1.42.3.2.7.1.7519 | |||
node · current The power input phases are incorrectly connected. | ||||
| NlgpCondId7520PowerLossOfPhase | 1.3.6.1.4.1.476.1.42.3.2.7.1.7520 | |||
node · current One of the input phases has been lost. | ||||
| NlgpCondId7522LossofAirflow | 1.3.6.1.4.1.476.1.42.3.2.7.1.7522 | |||
node · current Loss of airflow detected. | ||||
| NlgpCondId7523TeamworkMasterisofflineornotconnectedtothenetwork | 1.3.6.1.4.1.476.1.42.3.2.7.1.7523 | |||
node · current Loss of Teamwork Master. | ||||
| NlgpCondId7524LossofTeamworkSlave | 1.3.6.1.4.1.476.1.42.3.2.7.1.7524 | |||
node · current Teamwork Slave is offline or not connected to the network. | ||||
| NlgpCondId7525RepeatedTeamworkAddress | 1.3.6.1.4.1.476.1.42.3.2.7.1.7525 | |||
node · current The network address of two or more units in a teamwork are the same. | ||||
| NlgpCondId7526AirDamperFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.7526 | |||
node · current There is an issue with the air damper. | ||||
| NlgpCondId7537FilterMaintenanceDue | 1.3.6.1.4.1.476.1.42.3.2.7.1.7537 | |||
node · current The operating hours of the filter has exceeded the threshold and needs to be maintained or replaced. | ||||
| NlgpCondId7538HeaterMaintenanceDue | 1.3.6.1.4.1.476.1.42.3.2.7.1.7538 | |||
node · current The operating hours of the heater has exceeded the threshold. | ||||
| NlgpCondId7539HighCompressorPressure | 1.3.6.1.4.1.476.1.42.3.2.7.1.7539 | |||
node · current Compressor pressure has exceeded a threshold. | ||||
| NlgpCondId7540HighCompressorPresssureLockout | 1.3.6.1.4.1.476.1.42.3.2.7.1.7540 | |||
node · current Compressor lockout occurred due to high compressor pressure. | ||||
| NlgpCondId7541LowCompressorPressure | 1.3.6.1.4.1.476.1.42.3.2.7.1.7541 | |||
node · current Compressor pressure has dropped below a threshold. | ||||
| NlgpCondId7542LowCompressorPressureLockout | 1.3.6.1.4.1.476.1.42.3.2.7.1.7542 | |||
node · current Compressor lockout occurred due to low compressor pressure. | ||||
| NlgpCondId7543HighCompressorDischargeTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.7543 | |||
node · current Compressor discharge temperature has exceeded a threshold. | ||||
| NlgpCondId7544HighCompressorDischargeTemperatureLockout | 1.3.6.1.4.1.476.1.42.3.2.7.1.7544 | |||
node · current Compressor Lockout occurred due to high compressor discharge temperature. | ||||
| NlgpCondId7545LowCompressorDischargeTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.7545 | |||
node · current Compressor discharge temperature has dropped below a threshold. | ||||
| NlgpCondId7546LowCompressorDischargeTemperatureLockout | 1.3.6.1.4.1.476.1.42.3.2.7.1.7546 | |||
node · current Compressor lockout occurred due to low compressor discharge temperature. | ||||
| NlgpCondId7547LowCompressorDischargeSuperheat | 1.3.6.1.4.1.476.1.42.3.2.7.1.7547 | |||
node · current Compressor discharge superheat has dropped below a threshold. | ||||
| NlgpCondId7548LowCompressorDischargeSuperheatLockout | 1.3.6.1.4.1.476.1.42.3.2.7.1.7548 | |||
node · current Compressor lockout occurred due to low compressor discharge superheat temperature. | ||||
| NlgpCondId7549HighCompressorPressureAbnormal | 1.3.6.1.4.1.476.1.42.3.2.7.1.7549 | |||
node · current Compressor pressure has exceeded a normal threshold. | ||||
| NlgpCondId7550LowCompressorPressureAbnormal | 1.3.6.1.4.1.476.1.42.3.2.7.1.7550 | |||
node · current Compressor pressure has dropped below a normal threshold. | ||||
| NlgpCondId7551EEVDriverCommunicationFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.7551 | |||
node · current A communication failure occurred with the EEV driver board. | ||||
| NlgpCondId7552EEVDriverFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.7552 | |||
node · current EEV driver board failure detected. | ||||
| NlgpCondId7553HighCompressorPressureSensorFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.7553 | |||
node · current High compressor pressure sensor is disconnected or the signal is out of range. | ||||
| NlgpCondId7554LowCompressorPressureSensorFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.7554 | |||
node · current Low compressor pressure sensor is disconnected or the signal is out of range. | ||||
| NlgpCondId7555LowCompressorPressureSensorFailureLockout | 1.3.6.1.4.1.476.1.42.3.2.7.1.7555 | |||
node · current Compressor lockout occurred due to low compressor pressure. | ||||
| NlgpCondId7556CompressorDischargeTemperatureSensorFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.7556 | |||
node · current Compressor discharge temperature sensor is disconnected or the signal is out of range. | ||||
| NlgpCondId7557CompressorSuctionTemperatureSensorFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.7557 | |||
node · current Compressor suction temperature sensor is disconnected or the signal is out of range. | ||||
| NlgpCondId7558WaterFlowSensorFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.7558 | |||
node · current Water flow sensor is disconnected or the signal is out of range. | ||||
| NlgpCondId7559LossofAirflowSensorFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.7559 | |||
node · current Airflow sensor is disconnected or the signal is out of range. | ||||
| NlgpCondId7560FilterPressureDifferenceSensorFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.7560 | |||
node · current Filter pressure difference sensor is disconnected or the signal is out of range. | ||||
| NlgpCondId7561CustomAlarm | 1.3.6.1.4.1.476.1.42.3.2.7.1.7561 | |||
node · current Custom Alarm. | ||||
| NlgpCondId7562WaterPressureSensorFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.7562 | |||
node · current Water pressure sensor is disconnected or the signal is out of range. | ||||
| NlgpCondId7563FanStaticPressureSensorFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.7563 | |||
node · current Fan static pressure sensor is disconnected or the signal is out of range. | ||||
| NlgpCondId7568SystemShutdownEPO | 1.3.6.1.4.1.476.1.42.3.2.7.1.7568 | |||
node · current Unit shutdown by Emergency Power Off (EPO) switch. | ||||
| NlgpCondId7569SystemShutdownUndervoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.7569 | |||
node · current System shutdown due to an undervoltage condition. | ||||
| NlgpCondId7570TransformerHighTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.7570 | |||
node · current The transformer crossed the high temperature threshold. | ||||
| NlgpCondId7571TransformerTemperatureSensorFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.7571 | |||
node · current The transformer temperature sensor is reporting an invalid state. | ||||
| NlgpCondId7572MeteringBoardCommunicationFail | 1.3.6.1.4.1.476.1.42.3.2.7.1.7572 | |||
node · current The metering board(s) reported a communication failure. | ||||
| NlgpCondId7573AccessoryBoardCommunicationFail | 1.3.6.1.4.1.476.1.42.3.2.7.1.7573 | |||
node · current The accessory board(s) reported a communication failure. | ||||
| NlgpCondId7574SystemMisconfiguration | 1.3.6.1.4.1.476.1.42.3.2.7.1.7574 | |||
node · current The system reported a misconfiguration. | ||||
| NlgpCondId7575SystemFirmwareIncompatibility | 1.3.6.1.4.1.476.1.42.3.2.7.1.7575 | |||
node · current The system reported a firmware incompatibility. | ||||
| NlgpCondId7576MainInputBreaker1Tripped | 1.3.6.1.4.1.476.1.42.3.2.7.1.7576 | |||
node · current The main input circuit breaker 1 reported a tripped state. | ||||
| NlgpCondId7577MainInputBreaker1AccessoryError | 1.3.6.1.4.1.476.1.42.3.2.7.1.7577 | |||
node · current The main input circuit breaker 1 reported an invalid state. | ||||
| NlgpCondId7578MainInputBreaker1OpenFail | 1.3.6.1.4.1.476.1.42.3.2.7.1.7578 | |||
node · current The main input circuit breaker 1 failed to open as commanded. | ||||
| NlgpCondId7579MainInputBreaker2Tripped | 1.3.6.1.4.1.476.1.42.3.2.7.1.7579 | |||
node · current The main input circuit breaker 2 reported a tripped state. | ||||
| NlgpCondId7580MainInputBreaker2AccessoryError | 1.3.6.1.4.1.476.1.42.3.2.7.1.7580 | |||
node · current The main input circuit breaker 2 reported an invalid state. | ||||
| NlgpCondId7581MainInputBreaker2OpenFail | 1.3.6.1.4.1.476.1.42.3.2.7.1.7581 | |||
node · current The main input circuit breaker 2 failed to open as commanded. | ||||
| NlgpCondId7588LossofCommunication | 1.3.6.1.4.1.476.1.42.3.2.7.1.7588 | |||
node · current The system board has stopped communicating. | ||||
| NlgpCondId7589NoInitialCommunication | 1.3.6.1.4.1.476.1.42.3.2.7.1.7589 | |||
node · current The system board has not established initial communications. | ||||
| NlgpCondId7590Misconfiguration | 1.3.6.1.4.1.476.1.42.3.2.7.1.7590 | |||
node · current The system board is misconfigured. | ||||
| NlgpCondId7591FirmwareIncompatibility | 1.3.6.1.4.1.476.1.42.3.2.7.1.7591 | |||
node · current The system board firmware is incompatible with the other components. | ||||
| NlgpCondId7697OutputOvervoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.7697 | |||
node · current The output voltage crossed above the threshold. | ||||
| NlgpCondId7698OutputUndervoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.7698 | |||
node · current The output voltage crossed below the threshold. | ||||
| NlgpCondId7699PhaseOvercurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.7699 | |||
node · current The phase current crossed above the threshold. | ||||
| NlgpCondId7700NeutralOvercurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.7700 | |||
node · current The neutral current crossed above the threshold. | ||||
| NlgpCondId7701GroundOvercurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.7701 | |||
node · current The ground current crossed above the threshold. | ||||
| NlgpCondId7702OutputFrequencyDeviation | 1.3.6.1.4.1.476.1.42.3.2.7.1.7702 | |||
node · current The output frequency deviated beyond the threshold. | ||||
| NlgpCondId7703EnergyMeasurementRollover | 1.3.6.1.4.1.476.1.42.3.2.7.1.7703 | |||
node · current The total accumulated energy value reached its limit and was reset to zero. | ||||
| NlgpCondId7704Input1Overvoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.7704 | |||
node · current The voltage crossed above the threshold of input 1. | ||||
| NlgpCondId7705Input1Undervoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.7705 | |||
node · current The voltage crossed below the threshold of input 1 . | ||||
| NlgpCondId7706Input1PhaseLoss | 1.3.6.1.4.1.476.1.42.3.2.7.1.7706 | |||
node · current The voltage of one or more phases dropped below the threshold of input 1. | ||||
| NlgpCondId7707Input1InvalidPhaseRotation | 1.3.6.1.4.1.476.1.42.3.2.7.1.7707 | |||
node · current The phases are not in the expected sequence for input 1. | ||||
| NlgpCondId7708Input1FrequencyDeviation | 1.3.6.1.4.1.476.1.42.3.2.7.1.7708 | |||
node · current The frequency deviated beyond the threshold of input 1. | ||||
| NlgpCondId7709Input1HighVoltageTHD | 1.3.6.1.4.1.476.1.42.3.2.7.1.7709 | |||
node · current The voltage total harmonic distortion crossed above the threshold of input 1. | ||||
| NlgpCondId7710Input2Overvoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.7710 | |||
node · current The voltage crossed above the threshold of input 2. | ||||
| NlgpCondId7711Input2Undervoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.7711 | |||
node · current The voltage crossed below the threshold of input 2. | ||||
| NlgpCondId7712Input2PhaseLoss | 1.3.6.1.4.1.476.1.42.3.2.7.1.7712 | |||
node · current The voltage of one or more phases dropped below the threshold of input 2. | ||||
| NlgpCondId7713Input2InvalidPhaseRotation | 1.3.6.1.4.1.476.1.42.3.2.7.1.7713 | |||
node · current The phases are not in the expected sequence for input 2. | ||||
| NlgpCondId7714Input2FrequencyDeviation | 1.3.6.1.4.1.476.1.42.3.2.7.1.7714 | |||
node · current The frequency deviated beyond the threshold of input 2. | ||||
| NlgpCondId7715Input2HighVoltageTHD | 1.3.6.1.4.1.476.1.42.3.2.7.1.7715 | |||
node · current The voltage total harmonic distortion crossed above the threshold of input 2. | ||||
| NlgpCondId7792PanelboardPhaseOvercurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.7792 | |||
node · current The phase current crossed above the threshold of the panelboard. | ||||
| NlgpCondId7793PanelboardNeutralOvercurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.7793 | |||
node · current The neutral current crossed above the threshold of the panelboard. | ||||
| NlgpCondId7794PanelboardGroundOvercurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.7794 | |||
node · current The ground current crossed above the threshold of the panelboard. | ||||
| NlgpCondId7795PanelboardMainBreakerTripped | 1.3.6.1.4.1.476.1.42.3.2.7.1.7795 | |||
node · current The main panelboard circuit breaker reported a tripped state. | ||||
| NlgpCondId7796PanelboardMainBreakerAccessoryError | 1.3.6.1.4.1.476.1.42.3.2.7.1.7796 | |||
node · current The main panelboard circuit breaker reported an invalid state. | ||||
| NlgpCondId7797PanelboardEnergyMeasurementRollover | 1.3.6.1.4.1.476.1.42.3.2.7.1.7797 | |||
node · current The total accumulated energy value of the panelboard reached its limit and was reset to zero. | ||||
| NlgpCondId7822BranchPhaseOvercurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.7822 | |||
node · current The phase current crossed above the threshold of the branch. | ||||
| NlgpCondId7823BranchPhaseUndercurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.7823 | |||
node · current The phase current crossed below the threshold of the branch. | ||||
| NlgpCondId7824BranchEnergyMeasurementRollover | 1.3.6.1.4.1.476.1.42.3.2.7.1.7824 | |||
node · current The total accumulated energy value of the branch reached its limit and was reset to zero. | ||||
| NlgpCondId7896PanelboardPhaseOvercurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.7896 | |||
node · current The phase current crossed above the threshold of the panelboard. | ||||
| NlgpCondId7897PanelboardNeutralOvercurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.7897 | |||
node · current The neutral current crossed above the threshold of the panelboard. | ||||
| NlgpCondId7898PanelboardGroundOvercurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.7898 | |||
node · current The ground current crossed above the threshold of the panelboard. | ||||
| NlgpCondId7899PanelboardMainBreakerTripped | 1.3.6.1.4.1.476.1.42.3.2.7.1.7899 | |||
node · current The main panelboard circuit breaker reported a tripped state. | ||||
| NlgpCondId7900PanelboardMainBreakerAccessoryError | 1.3.6.1.4.1.476.1.42.3.2.7.1.7900 | |||
node · current The main panelboard circuit breaker reported an invalid state. | ||||
| NlgpCondId7901PanelboardEnergyMeasurementRollover | 1.3.6.1.4.1.476.1.42.3.2.7.1.7901 | |||
node · current The total accumulated energy value of the panelboard reached its limit and was reset to zero. | ||||
| NlgpCondId7953SubfeedPhaseOvercurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.7953 | |||
node · current The phase current crossed above the threshold of the subfeed. | ||||
| NlgpCondId7954SubfeedNeutralOvercurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.7954 | |||
node · current The neutral current crossed above the threshold of the subfeed. | ||||
| NlgpCondId7955SubfeedGroundOvercurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.7955 | |||
node · current The ground current crossed above the threshold of the subfeed. | ||||
| NlgpCondId7956SubfeedBreakerTripped | 1.3.6.1.4.1.476.1.42.3.2.7.1.7956 | |||
node · current The subfeed circuit breaker reported a tripped state. | ||||
| NlgpCondId7957SubfeedBreakerAccessoryError | 1.3.6.1.4.1.476.1.42.3.2.7.1.7957 | |||
node · current The subfeed circuit breaker reported an invalid state. | ||||
| NlgpCondId7958SubfeedEnergyMeasurementRollover | 1.3.6.1.4.1.476.1.42.3.2.7.1.7958 | |||
node · current The total accumulated energy value reached its limit and was reset to zero. | ||||
| NlgpCondId8029SubfeedPhaseOvercurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.8029 | |||
node · current The phase current crossed above the threshold of the subfeed. | ||||
| NlgpCondId8030SubfeedNeutralOvercurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.8030 | |||
node · current The neutral current crossed above the threshold of the subfeed. | ||||
| NlgpCondId8031SubfeedGroundOvercurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.8031 | |||
node · current The ground current crossed above the threshold of the subfeed. | ||||
| NlgpCondId8032SubfeedBreakerTripped | 1.3.6.1.4.1.476.1.42.3.2.7.1.8032 | |||
node · current The subfeed circuit breaker reported a tripped state. | ||||
| NlgpCondId8033SubfeedBreakerAccessoryError | 1.3.6.1.4.1.476.1.42.3.2.7.1.8033 | |||
node · current The subfeed circuit breaker reported an invalid state. | ||||
| NlgpCondId8034SubfeedEnergyMeasurementRollover | 1.3.6.1.4.1.476.1.42.3.2.7.1.8034 | |||
node · current The total accumulated energy value reached its limit and was reset to zero. | ||||
| NlgpCondId8045ExternalInputContactState | 1.3.6.1.4.1.476.1.42.3.2.7.1.8045 | |||
node · current The state of the external input contact. | ||||
| NlgpCondId8047InternalInputContactState | 1.3.6.1.4.1.476.1.42.3.2.7.1.8047 | |||
node · current The state of the internal input contact. | ||||
| NlgpCondId8051CompressorDriveFailureU00 | 1.3.6.1.4.1.476.1.42.3.2.7.1.8051 | |||
node · current Compressor Drive Failure U00. | ||||
| NlgpCondId8052CompressorDriveFailureU01 | 1.3.6.1.4.1.476.1.42.3.2.7.1.8052 | |||
node · current Compressor Drive Failure U01. | ||||
| NlgpCondId8053CompressorDriveFailureU02 | 1.3.6.1.4.1.476.1.42.3.2.7.1.8053 | |||
node · current Compressor Drive Failure U02. | ||||
| NlgpCondId8054CompressorDriveFailureU03 | 1.3.6.1.4.1.476.1.42.3.2.7.1.8054 | |||
node · current Compressor Drive Failure U03. | ||||
| NlgpCondId8055CompressorDriveFailureU04 | 1.3.6.1.4.1.476.1.42.3.2.7.1.8055 | |||
node · current Compressor Drive Failure U04. | ||||
| NlgpCondId8056CompressorDriveFailureU05 | 1.3.6.1.4.1.476.1.42.3.2.7.1.8056 | |||
node · current Compressor Drive Failure U05. | ||||
| NlgpCondId8057CompressorDriveFailureU06 | 1.3.6.1.4.1.476.1.42.3.2.7.1.8057 | |||
node · current Compressor Drive Failure U06. | ||||
| NlgpCondId8058CompressorDriveFailureU07 | 1.3.6.1.4.1.476.1.42.3.2.7.1.8058 | |||
node · current Compressor Drive Failure U07. | ||||
| NlgpCondId8059CompressorDriveFailureU08 | 1.3.6.1.4.1.476.1.42.3.2.7.1.8059 | |||
node · current Compressor Drive Failure U08. | ||||
| NlgpCondId8060CompressorDriveFailureU09 | 1.3.6.1.4.1.476.1.42.3.2.7.1.8060 | |||
node · current Compressor Drive Failure U09. | ||||
| NlgpCondId8061CompressorDriveFailureU10 | 1.3.6.1.4.1.476.1.42.3.2.7.1.8061 | |||
node · current Compressor Drive Failure U10. | ||||
| NlgpCondId8062CompressorDriveFailureU11 | 1.3.6.1.4.1.476.1.42.3.2.7.1.8062 | |||
node · current Compressor Drive Failure U11. | ||||
| NlgpCondId8063CompressorDriveFailureU12 | 1.3.6.1.4.1.476.1.42.3.2.7.1.8063 | |||
node · current Compressor Drive Failure U12. | ||||
| NlgpCondId8064CompressorDriveFailureU13 | 1.3.6.1.4.1.476.1.42.3.2.7.1.8064 | |||
node · current Compressor Drive Failure U13. | ||||
| NlgpCondId8065CompressorDriveFailureU14 | 1.3.6.1.4.1.476.1.42.3.2.7.1.8065 | |||
node · current Compressor Drive Failure U14. | ||||
| NlgpCondId8066CompressorDriveFailureU15 | 1.3.6.1.4.1.476.1.42.3.2.7.1.8066 | |||
node · current Compressor Drive Failure U15. | ||||
| NlgpCondId8067EEVDriverUnselectRefrigerant | 1.3.6.1.4.1.476.1.42.3.2.7.1.8067 | |||
node · current EEV Driver Unselect Refrigerant. | ||||
| NlgpCondId8068CompressorDriveHeatsinkHighTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.8068 | |||
node · current Compressor Drive Heatsink High Temperature. | ||||
| NlgpCondId8069CompressorDriveOverCurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.8069 | |||
node · current Compressor Drive Over Current. | ||||
| NlgpCondId8070CompressorDrivePhaseLoss | 1.3.6.1.4.1.476.1.42.3.2.7.1.8070 | |||
node · current Compressor Drive Phase Loss. | ||||
| NlgpCondId8071CompressorDriveDCPowerAbnormal | 1.3.6.1.4.1.476.1.42.3.2.7.1.8071 | |||
node · current Compressor Drive DC Power Abnormal. | ||||
| NlgpCondId807210DISensorCommunicationFail | 1.3.6.1.4.1.476.1.42.3.2.7.1.8072 | |||
node · current 10DI Sensor Communication Fail. | ||||
| NlgpCondId8073SystemLackOfRefrigerant | 1.3.6.1.4.1.476.1.42.3.2.7.1.8073 | |||
node · current System Lack Of Refrigerant. | ||||
| NlgpCondId8075ValveCommunicationsFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.8075 | |||
node · current A valve is configured to exist but communications cannot be established. | ||||
| NlgpCondId8076ValveIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.8076 | |||
node · current Valve is reporting abnormal operating condition. | ||||
| NlgpCondId8083CondensatePumpFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.8083 | |||
node · current Condensate Pump Failure. | ||||
| NlgpCondId8096BypasscontrollingtheSCRautonomously | 1.3.6.1.4.1.476.1.42.3.2.7.1.8096 | |||
node · current The bypass is controlling the SCR autonomously because not all inverters are online. | ||||
| NlgpCondId8098PowerModuleCommunicationstatus | 1.3.6.1.4.1.476.1.42.3.2.7.1.8098 | |||
node · current The control has detected a power module communication failure. | ||||
| NlgpCondId8100ECOmodeInhibited | 1.3.6.1.4.1.476.1.42.3.2.7.1.8100 | |||
node · current ECO mode is inhibited due to an external inhibit signal. | ||||
| NlgpCondId8105SupplyFanCommunicationLost | 1.3.6.1.4.1.476.1.42.3.2.7.1.8105 | |||
node · current Communications with Supply Fan has been lost. | ||||
| NlgpCondId8119CommunicationBusError | 1.3.6.1.4.1.476.1.42.3.2.7.1.8119 | |||
node · current The system board is experiencing an abnormal number of communication errors. | ||||
| NlgpCondId8120ExternalBatteryCabinetRemoved | 1.3.6.1.4.1.476.1.42.3.2.7.1.8120 | |||
node · current One or more external battery cabinets have been removed. | ||||
| NlgpCondId8125InternalBatteryBreakerOpen | 1.3.6.1.4.1.476.1.42.3.2.7.1.8125 | |||
node · current The internal battery breaker is open. | ||||
| NlgpCondId8126AllChargersShutdown | 1.3.6.1.4.1.476.1.42.3.2.7.1.8126 | |||
node · current All chargers in system are shut down to avoid incompatibility in external charger application, or to avoid over-charging in Lithium-ion battery application. | ||||
| NlgpCondId8127SpecificChargerShutdown | 1.3.6.1.4.1.476.1.42.3.2.7.1.8127 | |||
node · current The charger in this power module is shut down to detect battery connection status or to avoid Lithium-ion battery over-charging. | ||||
| NlgpCondId8166BIBBatteryBreakerPowerSupplyFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.8166 | |||
node · current Battery Interface Board power supply has failed. | ||||
| NlgpCondId8170XDPumpCommunicationLost | 1.3.6.1.4.1.476.1.42.3.2.7.1.8170 | |||
node · current Communications with XD Pump has been lost. | ||||
| NlgpCondId8178EmergencyCooling | 1.3.6.1.4.1.476.1.42.3.2.7.1.8178 | |||
node · current Emergency Cooling. | ||||
| NlgpCondId8179BatteryManagementSystemPowerSupplyFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.8179 | |||
node · current The battery management system has reported a power supply failure. | ||||
| NlgpCondId8180SupplyFluidLowTemp | 1.3.6.1.4.1.476.1.42.3.2.7.1.8180 | |||
node · current [Supply Fluid Temperature] below Supply Fluid Low Temp Threshold. | ||||
| NlgpCondId8181ReturnFluidLowTemp | 1.3.6.1.4.1.476.1.42.3.2.7.1.8181 | |||
node · current [Return Fluid Temperature] below Return Fluid Low Temp Threshold. | ||||
| NlgpCondId8182FluidHighDifferentialPressure | 1.3.6.1.4.1.476.1.42.3.2.7.1.8182 | |||
node · current Fluid Loop High Differential Pressure (Supply - Return). | ||||
| NlgpCondId8183FluidLowDifferentialPressure | 1.3.6.1.4.1.476.1.42.3.2.7.1.8183 | |||
node · current Fluid Loop Low Differential Pressure (Supply - Return). | ||||
| NlgpCondId8184FluidFlowLowInletPressure | 1.3.6.1.4.1.476.1.42.3.2.7.1.8184 | |||
node · current Fluid Loop Flow Low Inlet Pressure. | ||||
| NlgpCondId8185FluidFlowHighSupplyPressure | 1.3.6.1.4.1.476.1.42.3.2.7.1.8185 | |||
node · current Fluid Loop Flow High Supply Pressure. | ||||
| NlgpCondId8186FluidLowSystemFlow | 1.3.6.1.4.1.476.1.42.3.2.7.1.8186 | |||
node · current Fluid Loop Low System Flow (Low total flow for units in group). | ||||
| NlgpCondId8187FluidFlowBlocked | 1.3.6.1.4.1.476.1.42.3.2.7.1.8187 | |||
node · current Fluid Loop Flow Blocked (Loss of Flow with High Supply Pressure). | ||||
| NlgpCondId8188FluidDewpointMarginControl | 1.3.6.1.4.1.476.1.42.3.2.7.1.8188 | |||
node · current Fluid Loop Dewpoint Margin Control is active. | ||||
| NlgpCondId8189FluidSupplyPressureSensorIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.8189 | |||
node · current Fluid Loop Supply Pressure Sensor Issue. | ||||
| NlgpCondId8190FluidReturnPressureSensorIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.8190 | |||
node · current Fluid Loop Return Pressure Sensor Issue. | ||||
| NlgpCondId8191FluidInletPressureSensorIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.8191 | |||
node · current Fluid Loop Inlet Pressure Sensor Issue. | ||||
| NlgpCondId8192WaterLeakage | 1.3.6.1.4.1.476.1.42.3.2.7.1.8192 | |||
node · current Water Leakage - Typically indicates unit internal water leakage. | ||||
| NlgpCondId8194BatteryManagementSystemRackisOfflineWarning | 1.3.6.1.4.1.476.1.42.3.2.7.1.8194 | |||
node · current The Battery Management System has reported a rack-is-offline warning. | ||||
| NlgpCondId8195BatteryManagementSystemGeneralWarning | 1.3.6.1.4.1.476.1.42.3.2.7.1.8195 | |||
node · current The Battery Management System has reported a General Warning. | ||||
| NlgpCondId8196BatteryManagementSystemFault | 1.3.6.1.4.1.476.1.42.3.2.7.1.8196 | |||
node · current The Battery Management System has reported a Fault. | ||||
| NlgpCondId8197BatteryManagementSystemEndOfDischargeWarning | 1.3.6.1.4.1.476.1.42.3.2.7.1.8197 | |||
node · current The Battery Management System has reported an End-Of-Discharge Warning. | ||||
| NlgpCondId8199LoadonBypassUnion | 1.3.6.1.4.1.476.1.42.3.2.7.1.8199 | |||
node · current The output power is supplied by the bypass and maintenance bypass. | ||||
| NlgpCondId8200BypassControlModuleNotAvailable | 1.3.6.1.4.1.476.1.42.3.2.7.1.8200 | |||
node · current The bypass control module is not available. | ||||
| NlgpCondId8201BypassModuleNotAvailable | 1.3.6.1.4.1.476.1.42.3.2.7.1.8201 | |||
node · current The bypass module is not available. | ||||
| NlgpCondId8208BranchOverCurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.8208 | |||
node · current The PDU branch current is over limit. | ||||
| NlgpCondId8209BranchCurrentOverHL | 1.3.6.1.4.1.476.1.42.3.2.7.1.8209 | |||
node · current The current of pdu branch is over the high level. | ||||
| NlgpCondId8210BranchCurrentOverLL | 1.3.6.1.4.1.476.1.42.3.2.7.1.8210 | |||
node · current The current of pdu branch is over the low level. | ||||
| NlgpCondId8211BranchInrushOC | 1.3.6.1.4.1.476.1.42.3.2.7.1.8211 | |||
node · current The instantaneous current of pdu branch is large. | ||||
| NlgpCondId8212BranchBreakerFail | 1.3.6.1.4.1.476.1.42.3.2.7.1.8212 | |||
node · current A failure has been detected with the branch breaker. | ||||
| NlgpCondId8227SPMInternalCommFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.8227 | |||
node · current The communication with Server Power Management is lost. | ||||
| NlgpCondId8228SPMCRCCheckError | 1.3.6.1.4.1.476.1.42.3.2.7.1.8228 | |||
node · current Server Power Management CRC Check Error. | ||||
| NlgpCondId8229SPMBoardNotReady | 1.3.6.1.4.1.476.1.42.3.2.7.1.8229 | |||
node · current The Server Power Management sample board is not ready. | ||||
| NlgpCondId8231PHESupTemSnsrFail | 1.3.6.1.4.1.476.1.42.3.2.7.1.8231 | |||
node · current Plate Heat Exchanger Supply Temperature Sensor Fail. | ||||
| NlgpCondId8253PanelboardOvervoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.8253 | |||
node · current The panelboard voltage crossed above the threshold. | ||||
| NlgpCondId8254PanelboardUndervoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.8254 | |||
node · current The panelboard voltage crossed below the threshold. | ||||
| NlgpCondId8255PanelboardFrequencyDeviation | 1.3.6.1.4.1.476.1.42.3.2.7.1.8255 | |||
node · current The panelboard frequency deviated beyond the threshold. | ||||
| NlgpCondId8259BranchNeutralOvercurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.8259 | |||
node · current The neutral current crossed above the threshold of the branch. | ||||
| NlgpCondId8262PanelboardOvervoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.8262 | |||
node · current The Panelboard voltage crossed above the threshold. | ||||
| NlgpCondId8263PanelboardUndervoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.8263 | |||
node · current The panelboard voltage crossed below the threshold. | ||||
| NlgpCondId8264PanelboardFrequencyDeviation | 1.3.6.1.4.1.476.1.42.3.2.7.1.8264 | |||
node · current The panelboard frequency deviated beyond the threshold. | ||||
| NlgpCondId8267SubfeedOvervoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.8267 | |||
node · current The subfeed voltage crossed above the threshold. | ||||
| NlgpCondId8268SubfeedUndervoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.8268 | |||
node · current The subfeed voltage crossed below the threshold. | ||||
| NlgpCondId8269SubfeedFrequencyDeviation | 1.3.6.1.4.1.476.1.42.3.2.7.1.8269 | |||
node · current The subfeed frequency deviated beyond the threshold. | ||||
| NlgpCondId8273BatteryTempAbnormal | 1.3.6.1.4.1.476.1.42.3.2.7.1.8273 | |||
node · current Battery temperature is abnormal. | ||||
| NlgpCondId8274DischargerShutdown | 1.3.6.1.4.1.476.1.42.3.2.7.1.8274 | |||
node · current A condition is present that prevents the Battery Discharger from working. | ||||
| NlgpCondId8283BypassUnabletoTrace | 1.3.6.1.4.1.476.1.42.3.2.7.1.8283 | |||
node · current The voltage amplitude or frequency of bypass is out of the range of trace. | ||||
| NlgpCondId8284OutputBreakerOpen | 1.3.6.1.4.1.476.1.42.3.2.7.1.8284 | |||
node · current UPS internal or external output breaker is open. | ||||
| NlgpCondId8285PowerModuleInputCurrentHigh | 1.3.6.1.4.1.476.1.42.3.2.7.1.8285 | |||
node · current Input current of the power module is over limit. | ||||
| NlgpCondId8286ParameterConfigurationFailed | 1.3.6.1.4.1.476.1.42.3.2.7.1.8286 | |||
node · current Parameter configuration failed. | ||||
| NlgpCondId8287OutputDisabled | 1.3.6.1.4.1.476.1.42.3.2.7.1.8287 | |||
node · current Output Disabled. | ||||
| NlgpCondId8288BatteryTerminalAbnormal | 1.3.6.1.4.1.476.1.42.3.2.7.1.8288 | |||
node · current Battery Terminal Abnormal. | ||||
| NlgpCondId8290MOBAuxSensingFault | 1.3.6.1.4.1.476.1.42.3.2.7.1.8290 | |||
node · current There was a Master Output Breaker Aux Sensing Failure. | ||||
| NlgpCondId8294SMPSInputPowerSupplyFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.8294 | |||
node · current Bypass Input power supply or Rectifier input power supply has failed. | ||||
| NlgpCondId8295Rectifieroffduetofanpowernotavailable | 1.3.6.1.4.1.476.1.42.3.2.7.1.8295 | |||
node · current The Rectifier is off due to fan power not available. | ||||
| NlgpCondId8305Rectifieroverload | 1.3.6.1.4.1.476.1.42.3.2.7.1.8305 | |||
node · current Rectifier overload. | ||||
| NlgpCondId8306Rectifiersoftstartfailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.8306 | |||
node · current Rectifier soft start failure. | ||||
| NlgpCondId8307Batterycabinetconnectionabnormal | 1.3.6.1.4.1.476.1.42.3.2.7.1.8307 | |||
node · current Battery cabinet connection abnormal. | ||||
| NlgpCondId8308Insufficientcapacitytostart | 1.3.6.1.4.1.476.1.42.3.2.7.1.8308 | |||
node · current Insufficient capacity to start. | ||||
| NlgpCondId8309Bypassdisabled | 1.3.6.1.4.1.476.1.42.3.2.7.1.8309 | |||
node · current Bypass disabled. | ||||
| NlgpCondId8310Auxiliarypowerfault | 1.3.6.1.4.1.476.1.42.3.2.7.1.8310 | |||
node · current Auxiliary power fault. | ||||
| NlgpCondId8311Outputoffduetoabnormalbypass | 1.3.6.1.4.1.476.1.42.3.2.7.1.8311 | |||
node · current Output off due to abnormal bypass. | ||||
| NlgpCondId8312Localoutputisdisconnected | 1.3.6.1.4.1.476.1.42.3.2.7.1.8312 | |||
node · current Local output is disconnected. | ||||
| NlgpCondId8313Outputoffvoltageisnotzero | 1.3.6.1.4.1.476.1.42.3.2.7.1.8313 | |||
node · current Output off voltage is not zero. | ||||
| NlgpCondId8314Paralleloutputfrequencyabnormal | 1.3.6.1.4.1.476.1.42.3.2.7.1.8314 | |||
node · current Parallel output frequency abnormal. | ||||
| NlgpCondId8315ManualPowerOn | 1.3.6.1.4.1.476.1.42.3.2.7.1.8315 | |||
node · current Manual Power On. | ||||
| NlgpCondId8316RemotePowerOn | 1.3.6.1.4.1.476.1.42.3.2.7.1.8316 | |||
node · current Remote Power On. | ||||
| NlgpCondId8317Batterytoutilitytransition | 1.3.6.1.4.1.476.1.42.3.2.7.1.8317 | |||
node · current Battery to utility transition. | ||||
| NlgpCondId8318UPSwasresettofactorydefaults | 1.3.6.1.4.1.476.1.42.3.2.7.1.8318 | |||
node · current UPS was reset to factory defaults. | ||||
| NlgpCondId8319DeviceFaultswereclearedasrequested | 1.3.6.1.4.1.476.1.42.3.2.7.1.8319 | |||
node · current Device Faults were cleared, as requested. | ||||
| NlgpCondId8320Scheduledpoweronoccurred | 1.3.6.1.4.1.476.1.42.3.2.7.1.8320 | |||
node · current Scheduled power on occurred. | ||||
| NlgpCondId8321Scheduledpoweroffoccurred | 1.3.6.1.4.1.476.1.42.3.2.7.1.8321 | |||
node · current Scheduled power off occurred. | ||||
| NlgpCondId8323NeutralSCRShort | 1.3.6.1.4.1.476.1.42.3.2.7.1.8323 | |||
node · current The Neutral SCR is in a short condition. | ||||
| NlgpCondId8324NeutralSCROpen | 1.3.6.1.4.1.476.1.42.3.2.7.1.8324 | |||
node · current The Neutral SCR is in an open condition. | ||||
| NlgpCondId8325InputNeutralOverCurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.8325 | |||
node · current An over current has been detected on the system input neutral. | ||||
| NlgpCondId8326NeutralSnubberFail | 1.3.6.1.4.1.476.1.42.3.2.7.1.8326 | |||
node · current The neutral snubber has failed. | ||||
| NlgpCondId8331BatteryCabinetSerialNumberIllegalError | 1.3.6.1.4.1.476.1.42.3.2.7.1.8331 | |||
node · current Serial Number of the battery cabinet is illegal. | ||||
| NlgpCondId8332LithiumBatteryCabinetOnlineNumberError | 1.3.6.1.4.1.476.1.42.3.2.7.1.8332 | |||
node · current The online battery cabinet number is different from the cofigured number. | ||||
| NlgpCondId8333LithiumBatteryCabinetCommunicationFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.8333 | |||
node · current Battery cabinet communication has been disrupted. | ||||
| NlgpCondId8334LithiumBatteryCabinetmismatchtheunit | 1.3.6.1.4.1.476.1.42.3.2.7.1.8334 | |||
node · current The warning is triggered when the online lithium battery cabinet can't be used by the UPS. | ||||
| NlgpCondId8335LithiumBatteryCabinetAddressSetError | 1.3.6.1.4.1.476.1.42.3.2.7.1.8335 | |||
node · current Lithium battery cabinet addresses have been set incorrectly. | ||||
| NlgpCondId8336LithiumBatteryCabinetWaitCharge | 1.3.6.1.4.1.476.1.42.3.2.7.1.8336 | |||
node · current The battery is waiting for charge. | ||||
| NlgpCondId8337NumberofLithiumBatteryCabinetsOverLimit | 1.3.6.1.4.1.476.1.42.3.2.7.1.8337 | |||
node · current The number of batteries connected to the system exceeds the maximum. | ||||
| NlgpCondId8338LithiumBatteryCabinetCheck | 1.3.6.1.4.1.476.1.42.3.2.7.1.8338 | |||
node · current Check if the battery is present. | ||||
| NlgpCondId8339ManualLithiumBatteryWakeUpOccurred | 1.3.6.1.4.1.476.1.42.3.2.7.1.8339 | |||
node · current Manual lithium battery wake up occurred. | ||||
| NlgpCondId8344BatteryVoltageAbnormal | 1.3.6.1.4.1.476.1.42.3.2.7.1.8344 | |||
node · current Battery voltage out-of-range in the online lithium battery cabinet. | ||||
| NlgpCondId8345BatteryTemperatureAbnormal | 1.3.6.1.4.1.476.1.42.3.2.7.1.8345 | |||
node · current Battery Temperature out-of-range of the online Lithium Battery Cabinet. | ||||
| NlgpCondId8346BatteryCurrentAbnormal | 1.3.6.1.4.1.476.1.42.3.2.7.1.8346 | |||
node · current Battery current out-of-range of the online lithium battery cabinet. | ||||
| NlgpCondId8347BatteryCabinetAddressFault | 1.3.6.1.4.1.476.1.42.3.2.7.1.8347 | |||
node · current Battery Cabinet Addresses are set incorrectly. | ||||
| NlgpCondId8348BatteryCabinetConnectFault | 1.3.6.1.4.1.476.1.42.3.2.7.1.8348 | |||
node · current Battery cabinet ports have reversed connections. | ||||
| NlgpCondId8349BatteryCabinetCommunicationFail | 1.3.6.1.4.1.476.1.42.3.2.7.1.8349 | |||
node · current Battery Cabinet Cable failure. | ||||
| NlgpCondId8362Turnonfailed | 1.3.6.1.4.1.476.1.42.3.2.7.1.8362 | |||
node · current Turn on failed. | ||||
| NlgpCondId8368SystemoutputInhibitExt | 1.3.6.1.4.1.476.1.42.3.2.7.1.8368 | |||
node · current System output is inhibited by an external signal. | ||||
| NlgpCondId8397BatteryCabinetOverTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.8397 | |||
node · current Battery Cabinet Over Temperature. | ||||
| NlgpCondId8398BatteryStringOpen | 1.3.6.1.4.1.476.1.42.3.2.7.1.8398 | |||
node · current Battery String Open. | ||||
| NlgpCondId8399BatterySystemAbnormal | 1.3.6.1.4.1.476.1.42.3.2.7.1.8399 | |||
node · current Battery System Abnormal. | ||||
| NlgpCondId8404AirFilterDifferentialPressureSensorFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.8404 | |||
node · current Air Filter Differential Pressure Sensor Failure. | ||||
| NlgpCondId8405SupplyAirVolumeSensorCommunicationFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.8405 | |||
node · current Supply Air Volume Sensor Communication Failure. | ||||
| NlgpCondId8407CompressorinAlarmCondition | 1.3.6.1.4.1.476.1.42.3.2.7.1.8407 | |||
node · current Compressor in Alarm Condition. | ||||
| NlgpCondId8410FanCommunicationFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.8410 | |||
node · current Fan Communication Failure. | ||||
| NlgpCondId8412CondensatePressureSensorAlarm | 1.3.6.1.4.1.476.1.42.3.2.7.1.8412 | |||
node · current Condensate Pressure Sensor Alarm. | ||||
| NlgpCondId8421MotorizedBallValveFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.8421 | |||
node · current Motorized Ball Valve Failure. | ||||
| NlgpCondId8422AisleStaticPressureSensorFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.8422 | |||
node · current Aisle static pressure sensor failure. | ||||
| NlgpCondId8423BPHECommunicationFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.8423 | |||
node · current Brazed Plate Heat Exchanger Communication Failure. | ||||
| NlgpCondId8424DataCollectorCommunicationFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.8424 | |||
node · current Data Collector Communication Failure. | ||||
| NlgpCondId8425EPIVFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.8425 | |||
node · current Electronic Pressure Independent Control Valve Failure. | ||||
| NlgpCondId8426ATSCommunicationFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.8426 | |||
node · current ATS Communication Failure. | ||||
| NlgpCondId8427APFCommunicationFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.8427 | |||
node · current Active Power Filter Communication Failure. | ||||
| NlgpCondId8429BatterySystemCommunicationAbnormal | 1.3.6.1.4.1.476.1.42.3.2.7.1.8429 | |||
node · current Battery System Communication Abnormal. | ||||
| NlgpCondId8430BatterySystemWarning | 1.3.6.1.4.1.476.1.42.3.2.7.1.8430 | |||
node · current Battery System Warning. | ||||
| NlgpCondId8431BatterySystemFault | 1.3.6.1.4.1.476.1.42.3.2.7.1.8431 | |||
node · current Battery System Fault. | ||||
| NlgpCondId8435PanelboardMainBreakerOpenFail | 1.3.6.1.4.1.476.1.42.3.2.7.1.8435 | |||
node · current The main panelboard circuit breaker failed to open when tripped. | ||||
| NlgpCondId8436LoadLossDetected | 1.3.6.1.4.1.476.1.42.3.2.7.1.8436 | |||
node · current Load loss detected. | ||||
| NlgpCondId8438BatteryCabinetParallelFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.8438 | |||
node · current Battery Cabinet Parallel failure of the online lithium battery cabinet. | ||||
| NlgpCondId8439BatteryCabinetSOHLow | 1.3.6.1.4.1.476.1.42.3.2.7.1.8439 | |||
node · current Battery cabinet state of health is low. | ||||
| NlgpCondId8446ShutdownDueToSystemInputBackfeedFault | 1.3.6.1.4.1.476.1.42.3.2.7.1.8446 | |||
node · current UPS will shutdown due to a system input backfeed fault. | ||||
| NlgpCondId8447InputNeutralGroundAbnormal | 1.3.6.1.4.1.476.1.42.3.2.7.1.8447 | |||
node · current Input neutral ground abnormal. | ||||
| NlgpCondId8448BypassAbnormalInECOMode | 1.3.6.1.4.1.476.1.42.3.2.7.1.8448 | |||
node · current UPS will return to inverter from bypass due to ECO Mode bypass abnormal condition. | ||||
| NlgpCondId8449ShutdownDueToBypassOvercurrentTimeout | 1.3.6.1.4.1.476.1.42.3.2.7.1.8449 | |||
node · current UPS will shutdown due to bypass overcurrent. | ||||
| NlgpCondId8450ShutdownDueToBypassBackfeedFault | 1.3.6.1.4.1.476.1.42.3.2.7.1.8450 | |||
node · current UPS will shutdown due to a bypass backfeed fault. | ||||
| NlgpCondId8451ECOBypassMode | 1.3.6.1.4.1.476.1.42.3.2.7.1.8451 | |||
node · current ECO Mode Operation. Unit is On Bypass. | ||||
| NlgpCondId8452ParallelBypassCableConnectionAbnormal | 1.3.6.1.4.1.476.1.42.3.2.7.1.8452 | |||
node · current Parallel bypass cable wiring error. | ||||
| NlgpCondId8454FanReplacementRequired | 1.3.6.1.4.1.476.1.42.3.2.7.1.8454 | |||
node · current Fan replacement required. | ||||
| NlgpCondId8455LoadOffDueToShutdownOnBattery | 1.3.6.1.4.1.476.1.42.3.2.7.1.8455 | |||
node · current Load Off Due To Shutdown On Battery. | ||||
| NlgpCondId8456SystemRedundantOverload | 1.3.6.1.4.1.476.1.42.3.2.7.1.8456 | |||
node · current System loss of redundancy. | ||||
| NlgpCondId8457DSPFaultCondition | 1.3.6.1.4.1.476.1.42.3.2.7.1.8457 | |||
node · current DSP Fault Condition. | ||||
| NlgpCondId8458OnIntelligentSleepMode | 1.3.6.1.4.1.476.1.42.3.2.7.1.8458 | |||
node · current Unit in intelligent sleep mode operation. | ||||
| NlgpCondId8459FanReplaced | 1.3.6.1.4.1.476.1.42.3.2.7.1.8459 | |||
node · current Fan has been replaced. | ||||
| NlgpCondId8461THCardAlarm | 1.3.6.1.4.1.476.1.42.3.2.7.1.8461 | |||
node · current TH Card Alarm. | ||||
| NlgpCondId8462CompressorLimitingAlarm | 1.3.6.1.4.1.476.1.42.3.2.7.1.8462 | |||
node · current Compressor Limiting Alarm. | ||||
| NlgpCondId8463OutdoorFanCommunicationFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.8463 | |||
node · current Outdoor Fan Communication Failure. | ||||
| NlgpCondId8464OutdoorFanDriverFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.8464 | |||
node · current Outdoor Fan Driver Failure. | ||||
| NlgpCondId8467ProductRunOverTimeAlarm | 1.3.6.1.4.1.476.1.42.3.2.7.1.8467 | |||
node · current Product Run Over Time Alarm. | ||||
| NlgpCondId8468EnergyMeterCommunicationFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.8468 | |||
node · current Energy Meter Communication Failure. | ||||
| NlgpCondId8469ATSFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.8469 | |||
node · current ATS Failure. | ||||
| NlgpCondId8470SMSStopInverterInhibit | 1.3.6.1.4.1.476.1.42.3.2.7.1.8470 | |||
node · current When active a single inverter stop cannot be initiated. | ||||
| NlgpCondId8471UnitInSpecialCapacityMode | 1.3.6.1.4.1.476.1.42.3.2.7.1.8471 | |||
node · current When active in a MMS, the system will always be in capacity condition, regardless of actual load. | ||||
| NlgpCondId8472RectifierOvercurrentWarning | 1.3.6.1.4.1.476.1.42.3.2.7.1.8472 | |||
node · current The rectifier stopped for overcurrent. | ||||
| NlgpCondId8474IncompatibleBatteryManagementSystemversion | 1.3.6.1.4.1.476.1.42.3.2.7.1.8474 | |||
node · current The Battery Management System software version is incompatible. | ||||
| NlgpCondId8475LithiumBatteryEOL | 1.3.6.1.4.1.476.1.42.3.2.7.1.8475 | |||
node · current Lithium battery is at the end of its life. | ||||
| NlgpCondId8476LithiumBatterySamplingCircuitFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.8476 | |||
node · current Lithium battery has sampling circuit failure. | ||||
| NlgpCondId8477LithiumBatteryHardwareCircuitProtectionActive | 1.3.6.1.4.1.476.1.42.3.2.7.1.8477 | |||
node · current Lithium battery has activated hardware circuit protection. | ||||
| NlgpCondId8478LithiumBatteryCellCapacityLow | 1.3.6.1.4.1.476.1.42.3.2.7.1.8478 | |||
node · current Lithium battery cell capacity is very low. | ||||
| NlgpCondId8479LithiumBatteryCableConnectionIssue | 1.3.6.1.4.1.476.1.42.3.2.7.1.8479 | |||
node · current Check the Lithium Battery cable connections. | ||||
| NlgpCondId8480DischargeableBatteryCountLessThanConfiguredNumber | 1.3.6.1.4.1.476.1.42.3.2.7.1.8480 | |||
node · current The number of connected battery cabinets is less than the configured number. Prevent Discharge. | ||||
| NlgpCondId8481Ambienttemperaturelowerthanrecommended | 1.3.6.1.4.1.476.1.42.3.2.7.1.8481 | |||
node · current The ambient temperature is lower than the lower limit of the recommended temperature. | ||||
| NlgpCondId8482Ambienttemperaturehigherthanrecommended | 1.3.6.1.4.1.476.1.42.3.2.7.1.8482 | |||
node · current The ambient temperature is higher than the upper limit of the recommended temperature. | ||||
| NlgpCondId8483Ambienttemperaturelowprealarm | 1.3.6.1.4.1.476.1.42.3.2.7.1.8483 | |||
node · current The ambient temperature is close to the lower limit of the operating temperature. | ||||
| NlgpCondId8484Ambienttemperaturehighprealarm | 1.3.6.1.4.1.476.1.42.3.2.7.1.8484 | |||
node · current The ambient temperature is close to the upper limit of the operating temperature. | ||||
| NlgpCondId8489SystemBypassPhaseRotationError | 1.3.6.1.4.1.476.1.42.3.2.7.1.8489 | |||
node · current The power conductors on the input line are not wired to the UPS in the sequence preferred for the bypass (A-B-C). | ||||
| NlgpCondId8494SystemControlCardNotReady | 1.3.6.1.4.1.476.1.42.3.2.7.1.8494 | |||
node · current System control card is not ready. | ||||
| NlgpCondId8495SystemControlCardPowerSupplyFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.8495 | |||
node · current System control card power supply failure. | ||||
| NlgpCondId8496SystemControlCardCommunicationFail | 1.3.6.1.4.1.476.1.42.3.2.7.1.8496 | |||
node · current System control card communication fail. | ||||
| NlgpCondId8501BypassModuleNotReady | 1.3.6.1.4.1.476.1.42.3.2.7.1.8501 | |||
node · current Bypass Module is not ready. | ||||
| NlgpCondId8502BypassModulePowerSupplyFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.8502 | |||
node · current Bypass module power supply failure. | ||||
| NlgpCondId8503BypassModuleCommunicationFault | 1.3.6.1.4.1.476.1.42.3.2.7.1.8503 | |||
node · current The bypass module communication failure. | ||||
| NlgpCondId8504BypassModuleOverTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.8504 | |||
node · current The Bypass Module has detected an over temperature condition. | ||||
| NlgpCondId8505BypassModuleFanFault | 1.3.6.1.4.1.476.1.42.3.2.7.1.8505 | |||
node · current The Bypass Module has detected a fan fault. | ||||
| NlgpCondId8510DischargerFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.8510 | |||
node · current Discharger failure. | ||||
| NlgpCondId8512PowerModuleNotReady | 1.3.6.1.4.1.476.1.42.3.2.7.1.8512 | |||
node · current Power module not ready. | ||||
| NlgpCondId8517BatteryCircuitBreaker9Open | 1.3.6.1.4.1.476.1.42.3.2.7.1.8517 | |||
node · current Battery circuit breaker 9 is open. | ||||
| NlgpCondId8518BatteryCircuitBreaker10Open | 1.3.6.1.4.1.476.1.42.3.2.7.1.8518 | |||
node · current Battery circuit breaker 10 is open. | ||||
| NlgpCondId8519BatteryCircuitBreaker11Open | 1.3.6.1.4.1.476.1.42.3.2.7.1.8519 | |||
node · current Battery circuit breaker 11 is open. | ||||
| NlgpCondId8520BatteryCircuitBreaker12Open | 1.3.6.1.4.1.476.1.42.3.2.7.1.8520 | |||
node · current Battery circuit breaker 12 is open. | ||||
| NlgpCondId8521BatteryBreaker9OpenFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.8521 | |||
node · current Battery circuit breaker 9 failed to open. | ||||
| NlgpCondId8522BatteryBreaker10OpenFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.8522 | |||
node · current Battery circuit breaker 10 failed to open. | ||||
| NlgpCondId8523BatteryBreaker11OpenFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.8523 | |||
node · current Battery circuit breaker 11 failed to open. | ||||
| NlgpCondId8524BatteryBreaker12OpenFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.8524 | |||
node · current Battery circuit breaker 12 failed to open. | ||||
| NlgpCondId8537BatteryCabinetHighOverallVoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.8537 | |||
node · current The system has detected a high battery cabinet overall voltage condition. | ||||
| NlgpCondId8538BatteryCabinetLowOverallVoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.8538 | |||
node · current The system has detected a low battery cabinet overall voltage condition. | ||||
| NlgpCondId8539BatteryCabinetHighCellVoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.8539 | |||
node · current The system has detected a high cell voltage condition. | ||||
| NlgpCondId8540BatteryCabinetLowCellVoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.8540 | |||
node · current The system has detected a low cell voltage condition. | ||||
| NlgpCondId8541BatteryCabinetOverOverallVoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.8541 | |||
node · current The system has detected a battery cabinet over overall voltage condition. | ||||
| NlgpCondId8542BatteryCabinetUnderOverallVoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.8542 | |||
node · current The system has detected a battery cabinet under overall voltage condition. | ||||
| NlgpCondId8543BatteryCabinetOverCellVoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.8543 | |||
node · current The system has detected a battery cabinet over cell voltage condition. | ||||
| NlgpCondId8544BatteryCabinetUnderCellVoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.8544 | |||
node · current The system has detected a battery cabinet under cell voltage condition. | ||||
| NlgpCondId8545BatteryCabinetChargeOverCurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.8545 | |||
node · current Battery Cabinet Charge over current. | ||||
| NlgpCondId8546BatteryCabinetDischargeOverCurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.8546 | |||
node · current Battery Cabinet Discharge over current. | ||||
| NlgpCondId8547BatteryCabinetOverTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.8547 | |||
node · current The system has detected a battery cabinet over temperature condition. | ||||
| NlgpCondId8548BatteryCabinetUnderTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.8548 | |||
node · current The system has detected a battery cabinet under temperature condition. | ||||
| NlgpCondId8558BatteryStringHighCellVoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.8558 | |||
node · current The system has detected a high cell voltage condition. | ||||
| NlgpCondId8559BatteryStringLowCellVoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.8559 | |||
node · current The system has detected a low cell voltage condition. | ||||
| NlgpCondId8560BatteryStringOverOverallVoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.8560 | |||
node · current The system has detected a battery string over overall voltage condition. | ||||
| NlgpCondId8561BatteryStringUnderOverallVoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.8561 | |||
node · current The system has detected a battery string under overall voltage condition. | ||||
| NlgpCondId8562BatteryStringOverCellVoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.8562 | |||
node · current The system has detected a battery string over cell voltage condition. | ||||
| NlgpCondId8563BatteryStringUnderCellVoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.8563 | |||
node · current The system has detected a battery string under cell voltage condition. | ||||
| NlgpCondId8564BatteryStringChargeOverCurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.8564 | |||
node · current Battery string Charge over current. | ||||
| NlgpCondId8565BatteryStringDischargeOverCurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.8565 | |||
node · current Battery string Discharge over current. | ||||
| NlgpCondId8566BatteryStringOverTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.8566 | |||
node · current The system has detected a battery string over temperature condition. | ||||
| NlgpCondId8567BatteryStringUnderTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.8567 | |||
node · current The system has detected a battery string under temperature condition. | ||||
| NlgpCondId8579BatteryModuleHighOverallVoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.8579 | |||
node · current The system has detected a high battery module overall voltage condition. | ||||
| NlgpCondId8580BatteryModuleLowOverallVoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.8580 | |||
node · current The system has detected a low battery module overall voltage condition. | ||||
| NlgpCondId8581BatteryModuleHighCellVoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.8581 | |||
node · current The system has detected a high cell voltage condition. | ||||
| NlgpCondId8582BatteryModuleLowCellVoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.8582 | |||
node · current The system has detected a low cell voltage condition. | ||||
| NlgpCondId8583BatteryModuleOverOverallVoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.8583 | |||
node · current The system has detected a battery module over overall voltage condition. | ||||
| NlgpCondId8584BatteryModuleUnderOverallVoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.8584 | |||
node · current The system has detected a battery module under overall voltage condition. | ||||
| NlgpCondId8585BatteryModuleOverCellVoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.8585 | |||
node · current The system has detected a battery module over cell voltage condition. | ||||
| NlgpCondId8586BatteryModuleUnderCellVoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.8586 | |||
node · current The system has detected a battery module under cell voltage condition. | ||||
| NlgpCondId8587BatteryModuleDisconnected | 1.3.6.1.4.1.476.1.42.3.2.7.1.8587 | |||
node · current Battery Module is disconnected. | ||||
| NlgpCondId8588BatteryModuleChargeOverCurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.8588 | |||
node · current Battery Module Charge over current. | ||||
| NlgpCondId8589BatteryModuleDischargeOverCurrent | 1.3.6.1.4.1.476.1.42.3.2.7.1.8589 | |||
node · current Battery Module Discharge over current. | ||||
| NlgpCondId8590BatteryModuleOverTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.8590 | |||
node · current The system has detected a battery module over temperature condition. | ||||
| NlgpCondId8591BatteryModuleUnderTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.8591 | |||
node · current The system has detected a battery module under temperature condition. | ||||
| NlgpCondId8592BatteryModuleFault | 1.3.6.1.4.1.476.1.42.3.2.7.1.8592 | |||
node · current Battery module fault. | ||||
| NlgpCondId8605BatteryStringHighOverallVoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.8605 | |||
node · current The system has detected a high battery string overall voltage condition. | ||||
| NlgpCondId8606BatteryStringLowOverallVoltage | 1.3.6.1.4.1.476.1.42.3.2.7.1.8606 | |||
node · current The system has detected a low battery string overall voltage condition. | ||||
| NlgpCondId8608BypassSCROpen | 1.3.6.1.4.1.476.1.42.3.2.7.1.8608 | |||
node · current The bypass SCR is in an open circuit condition. | ||||
| NlgpCondId8609BypassSCRShort | 1.3.6.1.4.1.476.1.42.3.2.7.1.8609 | |||
node · current The bypass SCR is in short circuit condition. | ||||
| NlgpCondId8612RectifierOverTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.8612 | |||
node · current Rectifier temperature is too high to keep rectifier running. | ||||
| NlgpCondId8613RectifierCommunicationsFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.8613 | |||
node · current Communication between internal monitor and Rectifier has failed. | ||||
| NlgpCondId8615InverterOverTemperature | 1.3.6.1.4.1.476.1.42.3.2.7.1.8615 | |||
node · current Inverter temperature is too high to keep inverter running. | ||||
| NlgpCondId8616InverterCommunicationsFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.8616 | |||
node · current Communication between internal monitor and Inverter has failed. | ||||
| NlgpCondId8617UPSisinServiceMode | 1.3.6.1.4.1.476.1.42.3.2.7.1.8617 | |||
node · current UPS is in Service Mode. | ||||
| NlgpCondId8619AirEconHighMixedTemp | 1.3.6.1.4.1.476.1.42.3.2.7.1.8619 | |||
node · current Air Economizer High Mixed Temperature. | ||||
| NlgpCondId8620AirEconLowMixedTemp | 1.3.6.1.4.1.476.1.42.3.2.7.1.8620 | |||
node · current Air Economizer Low Mixed Temperature. | ||||
| NlgpCondId8621RetDampFdbackFail | 1.3.6.1.4.1.476.1.42.3.2.7.1.8621 | |||
node · current Return Damper Feedback Failure. | ||||
| NlgpCondId8622OutdoorDmpFdbackFail | 1.3.6.1.4.1.476.1.42.3.2.7.1.8622 | |||
node · current Outdoor Damper Feedback Failure. | ||||
| NlgpCondId8623ThermalRunaway | 1.3.6.1.4.1.476.1.42.3.2.7.1.8623 | |||
node · current Thermal Runaway. | ||||
| NlgpCondId8624XDMMixValvePositionError | 1.3.6.1.4.1.476.1.42.3.2.7.1.8624 | |||
node · current XDM Mix Valve is reporting Out of Position. | ||||
| NlgpCondId8625XDMPumpNoFlow | 1.3.6.1.4.1.476.1.42.3.2.7.1.8625 | |||
node · current XDM Pump Indicates No Flow. | ||||
| NlgpCondId8626XDMPumpPressureSensorFail | 1.3.6.1.4.1.476.1.42.3.2.7.1.8626 | |||
node · current XDM Pump Pressure Sensor Has Failed. | ||||
| NlgpCondId8627XDMPumpNotAvail | 1.3.6.1.4.1.476.1.42.3.2.7.1.8627 | |||
node · current XDM Pump is Not Available. | ||||
| NlgpCondId8628XDMFlowandLoadCycling | 1.3.6.1.4.1.476.1.42.3.2.7.1.8628 | |||
node · current XDM Flow is Cycling Between Flow and Load. | ||||
| NlgpCondId8629ShuntTripUnavailable | 1.3.6.1.4.1.476.1.42.3.2.7.1.8629 | |||
node · current Shunt trip power has failed. The voltage is insufficient to shunt trip the input breaker. | ||||
| NlgpCondId8630PanelboardShuntTripUnavailable | 1.3.6.1.4.1.476.1.42.3.2.7.1.8630 | |||
node · current Shunt trip power has failed. The voltage is insufficient to shunt trip the panelboard main breaker. | ||||
| NlgpCondId8718SystemControlCardsMissing | 1.3.6.1.4.1.476.1.42.3.2.7.1.8718 | |||
node · current System control cards missing. | ||||
| NlgpCondId8719LossofControlRedundancy | 1.3.6.1.4.1.476.1.42.3.2.7.1.8719 | |||
node · current Loss of control redundancy. | ||||
| NlgpCondId8724BatteryModuleNotReady | 1.3.6.1.4.1.476.1.42.3.2.7.1.8724 | |||
node · current Battery module is not ready. | ||||
| NlgpCondId8725BatteryModuleBalancingAbnormal | 1.3.6.1.4.1.476.1.42.3.2.7.1.8725 | |||
node · current Battery module voltage is not balanced. | ||||
| NlgpCondId8726MainBatteryCircuitBreakerisOpen | 1.3.6.1.4.1.476.1.42.3.2.7.1.8726 | |||
node · current Main battery circuit is open. | ||||
| NlgpCondId8727MainBatteryBreakerOpenFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.8727 | |||
node · current Main battery circuit breaker failed to open. | ||||
| NlgpCondId8734ExhaustDamperFeedbackFail | 1.3.6.1.4.1.476.1.42.3.2.7.1.8734 | |||
node · current Exhaust Damper Feedback Failure Alarm. | ||||
| NlgpCondId8735HighUnitDifferentialPressure | 1.3.6.1.4.1.476.1.42.3.2.7.1.8735 | |||
node · current High Unit Differential Pressure Alarm. | ||||
| NlgpCondId8736InputSurgeProtectionDeviceAlarm | 1.3.6.1.4.1.476.1.42.3.2.7.1.8736 | |||
node · current Input Surge Protection Device alarm. | ||||
| NlgpCondId8737BypassSurgeProtectionDeviceAlarm | 1.3.6.1.4.1.476.1.42.3.2.7.1.8737 | |||
node · current Bypass Surge Protection Device alarm. | ||||
| NlgpCondId8738ReturnTHSensorFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.8738 | |||
node · current Return Temperature/Humidity Sensor Failure. | ||||
| NlgpCondId8742AggregateRemoteAirTempSensorFail | 1.3.6.1.4.1.476.1.42.3.2.7.1.8742 | |||
node · current Failure of Aggregated Remote Air Temperature Sensor. This event is active when all configured Remote Sensor Issue events are active. | ||||
| NlgpCondId8743AggregateMixedAirTempSensorFail | 1.3.6.1.4.1.476.1.42.3.2.7.1.8743 | |||
node · current Failure of Aggregated Mixed Air Temperature Sensor. This event is active when Remote Sensor Issue and External Air Sensor E Issue are active. | ||||
| NlgpCondId8745FixedCompressorFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.8745 | |||
node · current Fixed Compressor Failure. | ||||
| NlgpCondId8746FixedCompressorFailureLock | 1.3.6.1.4.1.476.1.42.3.2.7.1.8746 | |||
node · current Fixed Compressor Failure Lock. | ||||
| NlgpCondId8748SecondaryPowerSourceSupplyFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.8748 | |||
node · current Secondary Power Source Supply Failure. | ||||
| NlgpCondId8751SprayCommunicationFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.8751 | |||
node · current Spray Communication Failure. | ||||
| NlgpCondId8752SprayHighPressureFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.8752 | |||
node · current Spray High Pressure Failure. | ||||
| NlgpCondId8753SprayHighPressureFailureLock | 1.3.6.1.4.1.476.1.42.3.2.7.1.8753 | |||
node · current Spray High Pressure Failure Lock. | ||||
| NlgpCondId8754SprayLowPressureFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.8754 | |||
node · current Spray Low Pressure Failure. | ||||
| NlgpCondId8755SprayAntifreezeMaintenance | 1.3.6.1.4.1.476.1.42.3.2.7.1.8755 | |||
node · current Spray Antifreeze Maintenance. | ||||
| NlgpCondId8756PowerMeterCommunicationFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.8756 | |||
node · current Power Meter Communication Failure. | ||||
| NlgpCondId8757WetFilmMaintenanceAlarm | 1.3.6.1.4.1.476.1.42.3.2.7.1.8757 | |||
node · current Wet Film Maintenance Alarm. | ||||
| NlgpCondId8758LowRefrigerant | 1.3.6.1.4.1.476.1.42.3.2.7.1.8758 | |||
node · current Low Refrigerant. | ||||
| NlgpCondId8759RefrigerantLeakDetected | 1.3.6.1.4.1.476.1.42.3.2.7.1.8759 | |||
node · current Refrigerant Leak Detected. | ||||
| NlgpCondId8760RefrigerantLeakDetectorCommunicationsFailure | 1.3.6.1.4.1.476.1.42.3.2.7.1.8760 | |||
node · current Refrigerant Leak Detector Communications Failure. | ||||
| NlgpCondId8761RefrigerantLeakDetectLock | 1.3.6.1.4.1.476.1.42.3.2.7.1.8761 | |||
node · current Refrigerant Leak Detect Lock. | ||||
| NlgpCondId8762HighPressureSwitchAlarm | 1.3.6.1.4.1.476.1.42.3.2.7.1.8762 | |||
node · current High Pressure Switch Alarm. | ||||
| NlgpCondId8763HighPressureSwitchAlarmLock | 1.3.6.1.4.1.476.1.42.3.2.7.1.8763 | |||
node · current High Pressure Switch Alarm Lock. | ||||