USHA-MIB
Ingrasyssnmptranslate -m USHA-MIB -Tpsnmpwalk -v2c -c <community> -m USHA-MIB <host> 1.3.6.1.4.1.2468Imports
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
|---|---|
| SNMPv2-SMI | Bits, Counter32, Integer32, IpAddress, MODULE-IDENTITY, MibIdentifier, OBJECT-IDENTITY, OBJECT-TYPE, TRAP-TYPE, TimeTicks, Unsigned32, enterprises, iso |
| SNMPv2-TC | DisplayString, PhysAddress, TEXTUAL-CONVENTION |
| UPS-MIB | NonNegativeInteger, PositiveInteger |
OID tree
| Name | OID | Type | Access | Status | Example | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Ningrasys | 1.3.6.1.4.1.2468 | ||||||||||||||||||||
| Nproduct | 1.3.6.1.4.1.2468.1 | ||||||||||||||||||||
| NupsAgent | 1.3.6.1.4.1.2468.1.2 | ||||||||||||||||||||
| Nushap | 1.3.6.1.4.1.2468.1.2.1 | ||||||||||||||||||||
| NupsObjectGroup | 1.3.6.1.4.1.2468.1.2.1.1 | ||||||||||||||||||||
| NupsIdentGroup | 1.3.6.1.4.1.2468.1.2.1.1.1 | ||||||||||||||||||||
| SupsIdentGroupManufacturer | 1.3.6.1.4.1.2468.1.2.1.1.1.1 | DisplayString (SIZE (0..31)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..31)) · read-only · mandatory The name of the UPS manufacturer. | |||||||||||||||||||||
| SupsIdentGroupModel | 1.3.6.1.4.1.2468.1.2.1.1.1.2 | DisplayString (SIZE (0..63)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..63)) · read-only · mandatory The UPS Model designation. | |||||||||||||||||||||
| SupsIdentGroupUPSFirmwareVersion | 1.3.6.1.4.1.2468.1.2.1.1.1.3 | DisplayString (SIZE (0..63)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..63)) · read-only · mandatory The UPS firmware/software version(s). This variable may or may not have the same value as upsIdentGroupAgentSoftwareVersion in some implementations. | |||||||||||||||||||||
| SupsIdentGroupAgentSoftwareVersion | 1.3.6.1.4.1.2468.1.2.1.1.1.4 | DisplayString (SIZE (0..31)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..31)) · read-only · mandatory The USHA software/firmware version. This variable may or may not have the same value as upsIdentGroupUPSSoftwareVersion in some implementations. | |||||||||||||||||||||
| SupsIdentGroupName | 1.3.6.1.4.1.2468.1.2.1.1.1.5 | DisplayString (SIZE (0..31)) | RW | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..31)) · read-write · mandatory A string identifying the UPS. This object should be set by the administrator. | |||||||||||||||||||||
| SupsIdentGroupAttachedDevices | 1.3.6.1.4.1.2468.1.2.1.1.1.6 | DisplayString (SIZE (0..63)) | RW | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..63)) · read-write · mandatory A string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator. | |||||||||||||||||||||
| SupsIdentGroupUpsSerialNumber | 1.3.6.1.4.1.2468.1.2.1.1.1.7 | DisplayString (SIZE (0..15)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..15)) · read-only · mandatory The UPS serial no. | |||||||||||||||||||||
| NupsBatteryGroup | 1.3.6.1.4.1.2468.1.2.1.1.2 | ||||||||||||||||||||
| SupsBatteryGroupStatus | 1.3.6.1.4.1.2468.1.2.1.1.2.1 | INTEGER | RO | mandatory | batteryNormal(2) | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The indication of the status in the UPS system's batteries.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SupsBatteryGroupSecondsOnBattery | 1.3.6.1.4.1.2468.1.2.1.1.2.2 | INTEGER | RO | mandatory | 0 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. 0 shall be returned if the unit is not on battery power. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SupsBatteryGroupEstimatedMinutesRemaining | 1.3.6.1.4.1.2468.1.2.1.1.2.3 | INTEGER | RO | mandatory | | ||||||||||||||||
scalar · INTEGER · read-only · mandatory An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SupsBatteryGroupEstimatedChargeRemaining | 1.3.6.1.4.1.2468.1.2.1.1.2.4 | INTEGER | RO | mandatory | 100 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory An estimate of the battery charge remaining expressed as a percent of full charge. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SupsBatteryGroupVoltage | 1.3.6.1.4.1.2468.1.2.1.1.2.5 | INTEGER | RO | mandatory | 414 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The magnitude of the present battery voltage in 0.1 Volt DC. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SupsBatteryGroupMandatory | 1.3.6.1.4.1.2468.1.2.1.1.2.6 | INTEGER | RO | mandatory | | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The present battery mandatory. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SupsBatteryGroupTemperature | 1.3.6.1.4.1.2468.1.2.1.1.2.7 | INTEGER | RO | mandatory | 285 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The ambient temperature at or near the UPS Battery casing. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NupsInputGroup | 1.3.6.1.4.1.2468.1.2.1.1.3 | ||||||||||||||||||||
| SupsInputGroupLineBads | 1.3.6.1.4.1.2468.1.2.1.1.3.1 | Counter | RO | mandatory | 6 | ||||||||||||||||
scalar · Counter · read-only · mandatory A count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the input transitions from zero out-of-tolerance lines to one or more input lines out-of-tolerance. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SupsInputGroupNumLines | 1.3.6.1.4.1.2468.1.2.1.1.3.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of input lines utilized in this device. This variable indicates the number of rows in the input table. | |||||||||||||||||||||
| TupsInputGroupTable | 1.3.6.1.4.1.2468.1.2.1.1.3.3 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of input table entries. The number of entries is given by the value of upsInputGroupNumLines. | |||||||||||||||||||||
| RupsInputGroupEntry | 1.3.6.1.4.1.2468.1.2.1.1.3.3.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular input line. | |||||||||||||||||||||
| CupsInputGroupLineIndex | 1.3.6.1.4.1.2468.1.2.1.1.3.3.1.1 | PositiveInteger (0..65535) | RO | mandatory | 1 | ||||||||||||||||
column · PositiveInteger (0..65535) · read-only · mandatory The index of UpsInputGroupEntry. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CupsInputGroupFrequency | 1.3.6.1.4.1.2468.1.2.1.1.3.3.1.2 | NonNegativeInteger | RO | mandatory | 500 | ||||||||||||||||
column · NonNegativeInteger · read-only · mandatory The present input frequency. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CupsInputGroupVoltage | 1.3.6.1.4.1.2468.1.2.1.1.3.3.1.3 | NonNegativeInteger | RO | mandatory | 2349 | ||||||||||||||||
column · NonNegativeInteger · read-only · mandatory The input utility line voltage in 0.1 volts. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CupsInputGroupCurrent | 1.3.6.1.4.1.2468.1.2.1.1.3.3.1.4 | NonNegativeInteger | RO | mandatory | | ||||||||||||||||
column · NonNegativeInteger · read-only · mandatory The magnitude of the present input current in 0.1 A. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CupsInputGroupTruePower | 1.3.6.1.4.1.2468.1.2.1.1.3.3.1.5 | NonNegativeInteger | RO | mandatory | | ||||||||||||||||
column · NonNegativeInteger · read-only · mandatory The magnitude of the present input true power. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CupsInputGroupVoltageMax | 1.3.6.1.4.1.2468.1.2.1.1.3.3.1.6 | NonNegativeInteger | RO | mandatory | 2363 | ||||||||||||||||
column · NonNegativeInteger · read-only · mandatory The maximum utility line voltage in 0.1 VAC for last 1 minute. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CupsInputGroupVoltageMin | 1.3.6.1.4.1.2468.1.2.1.1.3.3.1.7 | NonNegativeInteger | RO | mandatory | 2349 | ||||||||||||||||
column · NonNegativeInteger · read-only · mandatory The minimum utility line voltage in 0.1 VAC for last 1 minute. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NupsOutputGroup | 1.3.6.1.4.1.2468.1.2.1.1.4 | ||||||||||||||||||||
| SupsOutputGroupSource | 1.3.6.1.4.1.2468.1.2.1.1.4.1 | INTEGER | RO | mandatory | normal(3) | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SupsOutputGroupFrequency | 1.3.6.1.4.1.2468.1.2.1.1.4.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The current output frequency of the UPS system in 0.1 of HZ. | |||||||||||||||||||||
| SupsOutputGroupNumLines | 1.3.6.1.4.1.2468.1.2.1.1.4.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of output lines utilized in this device. This variable indicates the number of rows in the output table. | |||||||||||||||||||||
| TupsOutputGroupTable | 1.3.6.1.4.1.2468.1.2.1.1.4.4 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of output table entries. The number of entries is given by the value of upsOutputGroupNumLines. | |||||||||||||||||||||
| RupsOutputGroupEntry | 1.3.6.1.4.1.2468.1.2.1.1.4.4.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular output line. | |||||||||||||||||||||
| CupsOutputGroupLineIndex | 1.3.6.1.4.1.2468.1.2.1.1.4.4.1.1 | PositiveInteger (0..65535) | RO | mandatory | 1 | ||||||||||||||||
column · PositiveInteger (0..65535) · read-only · mandatory The output line identifier. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CupsOutputGroupVoltage | 1.3.6.1.4.1.2468.1.2.1.1.4.4.1.2 | NonNegativeInteger | RO | mandatory | 2210 | ||||||||||||||||
column · NonNegativeInteger · read-only · mandatory The output voltage of the UPS system in 0.1 volts. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CupsOutputGroupCurrent | 1.3.6.1.4.1.2468.1.2.1.1.4.4.1.3 | NonNegativeInteger | RO | mandatory | | ||||||||||||||||
column · NonNegativeInteger · read-only · mandatory The output current of the UPS system in 0.1 Amps. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CupsOutputGroupPower | 1.3.6.1.4.1.2468.1.2.1.1.4.4.1.4 | NonNegativeInteger | RO | mandatory | | ||||||||||||||||
column · NonNegativeInteger · read-only · mandatory The present output true power. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CupsOutputGroupPercentLoad | 1.3.6.1.4.1.2468.1.2.1.1.4.4.1.5 | INTEGER | RO | mandatory | 17 | ||||||||||||||||
column · INTEGER · read-only · mandatory The percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NupsBypassGroup | 1.3.6.1.4.1.2468.1.2.1.1.5 | ||||||||||||||||||||
| SupsBypassGroupFrequency | 1.3.6.1.4.1.2468.1.2.1.1.5.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The present bypass frequency. | |||||||||||||||||||||
| SupsBypassGroupNumLines | 1.3.6.1.4.1.2468.1.2.1.1.5.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table. | |||||||||||||||||||||
| TupsBypassGroupTable | 1.3.6.1.4.1.2468.1.2.1.1.5.3 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of bypass table entries. The number of entries is given by the value of upsBypassGroupNumLines. | |||||||||||||||||||||
| RupsBypassGroupEntry | 1.3.6.1.4.1.2468.1.2.1.1.5.3.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular bypass input. | |||||||||||||||||||||
| CupsBypassGroupLineIndex | 1.3.6.1.4.1.2468.1.2.1.1.5.3.1.1 | PositiveInteger (0..65535) | RO | mandatory | |||||||||||||||||
column · PositiveInteger (0..65535) · read-only · mandatory The bypass line identifier. | |||||||||||||||||||||
| CupsBypassGroupVoltage | 1.3.6.1.4.1.2468.1.2.1.1.5.3.1.2 | NonNegativeInteger | RO | mandatory | |||||||||||||||||
column · NonNegativeInteger · read-only · mandatory The present bypass voltage. | |||||||||||||||||||||
| CupsBypassGroupCurrent | 1.3.6.1.4.1.2468.1.2.1.1.5.3.1.3 | NonNegativeInteger | RO | mandatory | |||||||||||||||||
column · NonNegativeInteger · read-only · mandatory The present bypass current. | |||||||||||||||||||||
| CupsBypassGroupPower | 1.3.6.1.4.1.2468.1.2.1.1.5.3.1.4 | NonNegativeInteger | RO | mandatory | |||||||||||||||||
column · NonNegativeInteger · read-only · mandatory The present true power conveyed by the bypass. | |||||||||||||||||||||
| NupsTestGroup | 1.3.6.1.4.1.2468.1.2.1.1.6 | ||||||||||||||||||||
| SupsTestBatteryTestSettingTime | 1.3.6.1.4.1.2468.1.2.1.1.6.1 | INTEGER | RW | mandatory | 5 | ||||||||||||||||
scalar · INTEGER · read-write · mandatory The object specify the test time for battery test. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SupsBatteryTest | 1.3.6.1.4.1.2468.1.2.1.1.6.2 | INTEGER | RW | mandatory | none(1) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory This object specify the battery test type and initiate battery test. If battTestWithTime selected, the test time is refer to upsTestBatteryTestTime.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SupsTestBatteryTestResult | 1.3.6.1.4.1.2468.1.2.1.1.6.3 | INTEGER | RO | mandatory | donePassed(1) | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The results of the current or last UPS diagnostics test performed. The values for donePassed(1), doneWarning(2), and doneError(3) indicate that the test completed either successfully, with a warning, or with an error, respectively. The value aborted(4) is returned for tests which are aborted by setting the value of upsTestId to upsTestAbortTestInProgress. Tests which have not yet concluded are indicated by inProgress(5). The value noTestsInitiated(6) indicates that no previous test results are available, such as is the case when no tests have been run since the last reinitialization of the network management subsystem and the system has no provision for non- volatile storage of test results.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SupsTestBatteryTestStartTime | 1.3.6.1.4.1.2468.1.2.1.1.6.4 | DisplayString (SIZE (1..19)) | RO | mandatory | 08/05/2025 00:02:00 | ||||||||||||||||
scalar · DisplayString (SIZE (1..19)) · read-only · mandatory The value of the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of upsTestBatteryTestResult is noTestsInitiated(6), upsTestStartTime has the value 01/01/1970 00:00:00. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SupsTestBatteryTestElapsedTime | 1.3.6.1.4.1.2468.1.2.1.1.6.5 | DisplayString (SIZE (11)) | RO | mandatory | 00:00:14.00 | ||||||||||||||||
scalar · DisplayString (SIZE (11)) · read-only · mandatory The amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestElapsedTime has the value 00:00:00.00. Example values from LibreNMS test devices
| |||||||||||||||||||||
| TupsBatteryTestScheduleTable | 1.3.6.1.4.1.2468.1.2.1.1.6.6 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Table which describes the schedule for automatically battery test. | |||||||||||||||||||||
| RupsBatteryTestScheduleEntry | 1.3.6.1.4.1.2468.1.2.1.1.6.6.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory | |||||||||||||||||||||
| CupsBatteryTestScheduleIndex | 1.3.6.1.4.1.2468.1.2.1.1.6.6.1.1 | INTEGER (0..65535) | RO | mandatory | 1 | ||||||||||||||||
column · INTEGER (0..65535) · read-only · mandatory The index of battery test scheduled. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CupsBatteryTestScheduleDay | 1.3.6.1.4.1.2468.1.2.1.1.6.6.1.2 | INTEGER | RW | mandatory | monday(2) | ||||||||||||||||
column · INTEGER · read-write · mandatory The weekday on which the UPS should start battery test.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CupsBatteryTestScheduleTime | 1.3.6.1.4.1.2468.1.2.1.1.6.6.1.3 | DisplayString (SIZE (5)) | RW | mandatory | 00:02 | ||||||||||||||||
column · DisplayString (SIZE (5)) · read-write · mandatory The time that the battery test will be initiated in hh:mm format. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CupsBatteryTestScheduleType | 1.3.6.1.4.1.2468.1.2.1.1.6.6.1.4 | INTEGER | RW | mandatory | battTest10sec(2) | ||||||||||||||||
column · INTEGER · read-write · mandatory The type of battery test.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CupsBatteryTestScheduleTestWithTime | 1.3.6.1.4.1.2468.1.2.1.1.6.6.1.5 | INTEGER | RO | mandatory | supported(1) | ||||||||||||||||
column · INTEGER · read-only · mandatory The battTestWithTime of battery test is supported or not.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CupsBatteryTestScheduleSpecialDay | 1.3.6.1.4.1.2468.1.2.1.1.6.6.1.6 | DisplayString (SIZE (10)) | RW | mandatory | None | ||||||||||||||||
column · DisplayString (SIZE (10)) · read-write · mandatory The special day that the battery test will be initiated in dd/mm/yyyy format. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NupsControlGroup | 1.3.6.1.4.1.2468.1.2.1.1.7 | ||||||||||||||||||||
| SupsControlUpsShutdownDelay | 1.3.6.1.4.1.2468.1.2.1.1.7.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The delay in seconds the UPS remains on after being told to turn off. | |||||||||||||||||||||
| SupsControlUpsSleepTime | 1.3.6.1.4.1.2468.1.2.1.1.7.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The time in minutes for the UPS to go to sleep when instructed. When in sleep mode, the UPS will not provide output power regardless of the input line state. Once the specified time has elapsed, output power will be restored. This is a configuration setting. The UPS will not go to sleep until told to do so by the manager from a management station. Any input value is allowed, however the UPS only recognizes 0 - 9999 minutes in one minute increments. If the provided value is higher than the highest acceptable value, the highest acceptable value is used. | |||||||||||||||||||||
| SupsControlUpsOnOffControl | 1.3.6.1.4.1.2468.1.2.1.1.7.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Setting this variable to control UPS output status. turnUpsOff(1) will set UPS turn off output after upsControlUpsShutdownDelay period expired. putUpsToSleep(2) will set UPS turn off output after upsControlUpsShutdownDelay period expired, UPS output will stay off with the period defined by upsControlUpsSleepTime, then turn output on. turnOnUpsOrCancelShutdown(3) can used to turn on UPS output, or cancel any shutdown process.
| |||||||||||||||||||||
| TupsControlShutdownParametersTable | 1.3.6.1.4.1.2468.1.2.1.1.7.4 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Table which describes the parametes for shutdown process when shutdown event occurs | |||||||||||||||||||||
| RupsControlShutdownParametersEntry | 1.3.6.1.4.1.2468.1.2.1.1.7.4.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory
| |||||||||||||||||||||
| CupsControlEvent | 1.3.6.1.4.1.2468.1.2.1.1.7.4.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The shutdown event identification
| |||||||||||||||||||||
| CupsControlEventStatus | 1.3.6.1.4.1.2468.1.2.1.1.7.4.1.2 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Status of the corresponding shutdown Event. When set to disable(), shutdown process will not start when corresponding event occured.
| |||||||||||||||||||||
| CupsControlDelay | 1.3.6.1.4.1.2468.1.2.1.1.7.4.1.3 | INTEGER (0..10080) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..10080) · read-write · mandatory The Delay after the occurance of the curresponding shutdown event that USHA should issue shutdown request to connected clients. For WeeklyScheduledShutdown and SpecialScheduledShutdown, this is the time before the configured Shutdowntime when USHA will start sending the warning message to the connected clients. The value is in units of minutes. | |||||||||||||||||||||
| CupsControlFirstWarning | 1.3.6.1.4.1.2468.1.2.1.1.7.4.1.4 | INTEGER (0..3600) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..3600) · read-write · mandatory The delay after the occurance of the curresponding shutdown event that the USHA will start sending the warning message to the connected clients. The value is in units of seconds | |||||||||||||||||||||
| CupsControlWarningInterval | 1.3.6.1.4.1.2468.1.2.1.1.7.4.1.5 | INTEGER (0..3600) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..3600) · read-write · mandatory The frequency of sending warning messages to the connected clients when the curresponding shutdown event occurs. The value is in units of seconds. | |||||||||||||||||||||
| TupsControlWeeklyScheduleTable | 1.3.6.1.4.1.2468.1.2.1.1.7.5 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory The table to schedule shutting down the ups by weekly. | |||||||||||||||||||||
| RupsControlWeeklyScheduleEntry | 1.3.6.1.4.1.2468.1.2.1.1.7.5.1 | NA | mandatory | ||||||||||||||||||
| CupsControlWeeklyIndex | 1.3.6.1.4.1.2468.1.2.1.1.7.5.1.1 | INTEGER (0..65535) | RO | mandatory | |||||||||||||||||
column · INTEGER (0..65535) · read-only · mandatory The index of scheduled events. | |||||||||||||||||||||
| CupsControlWeeklyShutdownDay | 1.3.6.1.4.1.2468.1.2.1.1.7.5.1.2 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The weekday on which the UPS should shut down.
| |||||||||||||||||||||
| CupsControlWeeklyShutdownTime | 1.3.6.1.4.1.2468.1.2.1.1.7.5.1.3 | DisplayString (SIZE (5)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (5)) · read-write · mandatory The time that the process of shutting down the UPS will be initiated in hh:mm format. | |||||||||||||||||||||
| CupsControlWeeklyRestartDay | 1.3.6.1.4.1.2468.1.2.1.1.7.5.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The weekday on which the UPS should restart
| |||||||||||||||||||||
| CupsControlWeeklyRestartTime | 1.3.6.1.4.1.2468.1.2.1.1.7.5.1.5 | DisplayString (SIZE (5)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (5)) · read-write · mandatory The time the UPS will restart in hh:mm format. | |||||||||||||||||||||
| TupsControlSpecialScheduleTable | 1.3.6.1.4.1.2468.1.2.1.1.7.6 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory The table to schedule shutting down the ups. | |||||||||||||||||||||
| RupsControlSpecialScheduleEntry | 1.3.6.1.4.1.2468.1.2.1.1.7.6.1 | NA | mandatory | ||||||||||||||||||
| CupsControlSpecialIndex | 1.3.6.1.4.1.2468.1.2.1.1.7.6.1.1 | INTEGER (0..65535) | RO | mandatory | |||||||||||||||||
column · INTEGER (0..65535) · read-only · mandatory The index of scheduled events. | |||||||||||||||||||||
| CupsControlSpecialShutdownDay | 1.3.6.1.4.1.2468.1.2.1.1.7.6.1.2 | DisplayString (SIZE (10)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (10)) · read-write · mandatory The date on which the UPS should shut down in dd/mm/yyyy format. | |||||||||||||||||||||
| CupsControlSpecialShutdownTime | 1.3.6.1.4.1.2468.1.2.1.1.7.6.1.3 | DisplayString (SIZE (5)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (5)) · read-write · mandatory The time that the process of shutting down the UPS will be initiated in hh:mm format | |||||||||||||||||||||
| CupsControlSpecialRestartDay | 1.3.6.1.4.1.2468.1.2.1.1.7.6.1.4 | DisplayString (SIZE (10)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (10)) · read-write · mandatory The date on which the UPS should restart in dd/mm/yyyy format | |||||||||||||||||||||
| CupsControlSpecialRestartTime | 1.3.6.1.4.1.2468.1.2.1.1.7.6.1.5 | DisplayString (SIZE (5)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (5)) · read-write · mandatory The time the UPS will restart in hh:mm format. | |||||||||||||||||||||
| NupsConfigGroup | 1.3.6.1.4.1.2468.1.2.1.1.8 | ||||||||||||||||||||
| SupsConfigGroupInputVoltage | 1.3.6.1.4.1.2468.1.2.1.1.8.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The magnitude of the nominal input voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2. | |||||||||||||||||||||
| SupsConfigGroupInputFreq | 1.3.6.1.4.1.2468.1.2.1.1.8.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The nominal input frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2. | |||||||||||||||||||||
| SupsConfigGroupOutputVoltage | 1.3.6.1.4.1.2468.1.2.1.1.8.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The magnitude of the nominal output voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2. | |||||||||||||||||||||
| SupsConfigGroupOutputFreq | 1.3.6.1.4.1.2468.1.2.1.1.8.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The nominal output frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2. | |||||||||||||||||||||
| SupsConfigGroupOutputVA | 1.3.6.1.4.1.2468.1.2.1.1.8.5 | NonNegativeInteger | RO | mandatory | |||||||||||||||||
scalar · NonNegativeInteger · read-only · mandatory The magnitude of the nominal Volt-Amp rating. | |||||||||||||||||||||
| SupsConfigGroupOutputPower | 1.3.6.1.4.1.2468.1.2.1.1.8.6 | NonNegativeInteger | RO | mandatory | |||||||||||||||||
scalar · NonNegativeInteger · read-only · mandatory The magnitude of the nominal true power rating. | |||||||||||||||||||||
| SupsConfigGroupOverTemperatureSetPoint | 1.3.6.1.4.1.2468.1.2.1.1.8.7 | NonNegativeInteger (10..70) | RW | mandatory | |||||||||||||||||
scalar · NonNegativeInteger (10..70) · read-write · mandatory The maximum temperature allowed before the UPS operation temperature is too high. | |||||||||||||||||||||
| SupsConfigGroupOverLoadSetPoint | 1.3.6.1.4.1.2468.1.2.1.1.8.8 | NonNegativeInteger (0..120) | RW | mandatory | |||||||||||||||||
scalar · NonNegativeInteger (0..120) · read-write · mandatory The maximum output load allowed before the load is too high for UPS operation. | |||||||||||||||||||||
| NupsClients | 1.3.6.1.4.1.2468.1.2.1.1.9 | ||||||||||||||||||||
| SupsClientsConnectedNum | 1.3.6.1.4.1.2468.1.2.1.1.9.1 | NonNegativeInteger | RO | mandatory | |||||||||||||||||
scalar · NonNegativeInteger · read-only · mandatory The count of clients which have resgistered for UPS shutdown control. | |||||||||||||||||||||
| TupsDevicesTable | 1.3.6.1.4.1.2468.1.2.1.1.9.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory The devices powered by UPS and registered to USHA | |||||||||||||||||||||
| RupsDevicesEntry | 1.3.6.1.4.1.2468.1.2.1.1.9.2.1 | NA | mandatory | ||||||||||||||||||
| CindexOfDevice | 1.3.6.1.4.1.2468.1.2.1.1.9.2.1.1 | NonNegativeInteger | RO | mandatory | |||||||||||||||||
column · NonNegativeInteger · read-only · mandatory The index of the device that is plugged into the UPS. | |||||||||||||||||||||
| CaddrOfDevice | 1.3.6.1.4.1.2468.1.2.1.1.9.2.1.2 | IpAddress | RO | mandatory | |||||||||||||||||
column · IpAddress · read-only · mandatory The ip address of the device. | |||||||||||||||||||||
| CnameOfDevice | 1.3.6.1.4.1.2468.1.2.1.1.9.2.1.3 | DisplayString (SIZE (0..31)) | RO | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..31)) · read-only · mandatory The name/description of the device plugged into the UPS. | |||||||||||||||||||||
| CtimeOfConnection | 1.3.6.1.4.1.2468.1.2.1.1.9.2.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The device registered to USHA | |||||||||||||||||||||
| CtimeOfConnectionTime | 1.3.6.1.4.1.2468.1.2.1.1.9.2.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The device registered time to USHA. | |||||||||||||||||||||
| CtimeOfConnectionTimeout | 1.3.6.1.4.1.2468.1.2.1.1.9.2.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The device timeout counter. Unit: 10 seconds | |||||||||||||||||||||
| NagentConfig | 1.3.6.1.4.1.2468.1.2.1.1.10 | ||||||||||||||||||||
| SagentConfigIpaddress | 1.3.6.1.4.1.2468.1.2.1.1.10.1 | IpAddress | RW | mandatory | |||||||||||||||||
scalar · IpAddress · read-write · mandatory The ip address that NMS can identify the managed device | |||||||||||||||||||||
| SagentConfigGateway | 1.3.6.1.4.1.2468.1.2.1.1.10.2 | IpAddress | RW | mandatory | |||||||||||||||||
scalar · IpAddress · read-write · mandatory The default gateway that allow device managed through routers | |||||||||||||||||||||
| SagentConfigSubnetMask | 1.3.6.1.4.1.2468.1.2.1.1.10.3 | IpAddress | RW | mandatory | |||||||||||||||||
scalar · IpAddress · read-write · mandatory Internet address subnet mask | |||||||||||||||||||||
| SagentConfigDate | 1.3.6.1.4.1.2468.1.2.1.1.10.4 | DisplayString (SIZE (10)) | RW | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (10)) · read-write · mandatory The date in agent, format is (dd/mm/yyyy) | |||||||||||||||||||||
| SagentConfigTime | 1.3.6.1.4.1.2468.1.2.1.1.10.5 | DisplayString (SIZE (8)) | RW | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (8)) · read-write · mandatory The time in agent, format is (hh:mm:ss) | |||||||||||||||||||||
| SagentConfigPrimaryTimeServer | 1.3.6.1.4.1.2468.1.2.1.1.10.6 | IpAddress | RW | mandatory | |||||||||||||||||
scalar · IpAddress · read-write · mandatory The primary time server is responsible for sending the correct time to the agent. | |||||||||||||||||||||
| SagentConfigSecondaryTimeServer | 1.3.6.1.4.1.2468.1.2.1.1.10.7 | IpAddress | RW | mandatory | |||||||||||||||||
scalar · IpAddress · read-write · mandatory The secondary time server is responsible for sending the correct time to the agent. | |||||||||||||||||||||
| SagentConfigHistoryLogFrequency | 1.3.6.1.4.1.2468.1.2.1.1.10.8 | INTEGER (5..28800) | RW | mandatory | |||||||||||||||||
scalar · INTEGER (5..28800) · read-write · mandatory The frequency of the updation of the history log. The value is in seconds | |||||||||||||||||||||
| SagentConfigExtHistoryLogFrequency | 1.3.6.1.4.1.2468.1.2.1.1.10.9 | INTEGER (1..10080) | RW | mandatory | |||||||||||||||||
scalar · INTEGER (1..10080) · read-write · mandatory The ups parameters are sampled at the rate governed by the mconfigHistroyLogFrequency. These sampled values are further conslidated over period of time which is determined by this object. | |||||||||||||||||||||
| SagentConfigPollRate | 1.3.6.1.4.1.2468.1.2.1.1.10.10 | INTEGER (1..999) | RW | mandatory | |||||||||||||||||
scalar · INTEGER (1..999) · read-write · mandatory The frequency that proxy agent polls the connected UPS in JBUS protocol. (unit : second) | |||||||||||||||||||||
| SagentConfigBaudRate | 1.3.6.1.4.1.2468.1.2.1.1.10.11 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The serial port communication speed. only 9600 allowed | |||||||||||||||||||||
| SagentConfigDhcpStatue | 1.3.6.1.4.1.2468.1.2.1.1.10.12 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Enable or disable DHCP/BootP capability
| |||||||||||||||||||||
| SagentConfigTelnetStatue | 1.3.6.1.4.1.2468.1.2.1.1.10.13 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Enable or disable telnet access
| |||||||||||||||||||||
| SagentConfigTftpStatue | 1.3.6.1.4.1.2468.1.2.1.1.10.14 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Enable or disable network upgrade capability
| |||||||||||||||||||||
| SagentConfigResetToDefault | 1.3.6.1.4.1.2468.1.2.1.1.10.15 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Reset all parameters of USHA to default value
| |||||||||||||||||||||
| SagentConfigRestart | 1.3.6.1.4.1.2468.1.2.1.1.10.16 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Restart USHA
| |||||||||||||||||||||
| SagentConfigClearAgentLog | 1.3.6.1.4.1.2468.1.2.1.1.10.17 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Clear agent log data
| |||||||||||||||||||||
| SagentConfigClearEventLog | 1.3.6.1.4.1.2468.1.2.1.1.10.18 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Clear event log data
| |||||||||||||||||||||
| SagentConfigClearExtHistoryLog | 1.3.6.1.4.1.2468.1.2.1.1.10.19 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Clear extented history log data
| |||||||||||||||||||||
| SagentConfigClearHistoryLog | 1.3.6.1.4.1.2468.1.2.1.1.10.20 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Clear history log data
| |||||||||||||||||||||
| SagentConfigTrapRetryCount | 1.3.6.1.4.1.2468.1.2.1.1.10.21 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The count of repeat traps to send to NMS before trap acknowledge received. | |||||||||||||||||||||
| SagentConfigTrapRetryTime | 1.3.6.1.4.1.2468.1.2.1.1.10.22 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The time between retry traps sned to NMS. | |||||||||||||||||||||
| SagentConfigTrapAckSignature | 1.3.6.1.4.1.2468.1.2.1.1.10.23 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The signature of trap acknowledge. | |||||||||||||||||||||
| SagentConfigMibVersion | 1.3.6.1.4.1.2468.1.2.1.1.10.24 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The version of MIB spec. | |||||||||||||||||||||
| TagentConfigTrapsReceiversTable | 1.3.6.1.4.1.2468.1.2.1.1.10.25 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of managers to send traps to. The number of entries is given by the value of agentConfigNumTrapReceivers | |||||||||||||||||||||
| RagentConfigTrapsReceiversEntry | 1.3.6.1.4.1.2468.1.2.1.1.10.25.1 | NA | mandatory | ||||||||||||||||||
| CtrapsIndex | 1.3.6.1.4.1.2468.1.2.1.1.10.25.1.1 | INTEGER (0..65535) | RO | mandatory | |||||||||||||||||
column · INTEGER (0..65535) · read-only · mandatory The index to a trap receiver entry. | |||||||||||||||||||||
| CtrapsReceiverAddr | 1.3.6.1.4.1.2468.1.2.1.1.10.25.1.2 | IpAddress | RW | mandatory | |||||||||||||||||
column · IpAddress · read-write · mandatory The IP address of the manager to send a trap to. | |||||||||||||||||||||
| CreceiverCommunityString | 1.3.6.1.4.1.2468.1.2.1.1.10.25.1.3 | DisplayString (SIZE (0..19)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..19)) · read-write · mandatory The community name to use in the trap when sent to the manager. | |||||||||||||||||||||
| CreceiverNmsType | 1.3.6.1.4.1.2468.1.2.1.1.10.25.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The trap group that NMS desired.
| |||||||||||||||||||||
| CreceiverSeverityLevel | 1.3.6.1.4.1.2468.1.2.1.1.10.25.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The severity level of traps to be received by this manager.
| |||||||||||||||||||||
| CreceiverDescription | 1.3.6.1.4.1.2468.1.2.1.1.10.25.1.6 | DisplayString (SIZE (0..31)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..31)) · read-write · mandatory Description of trap receivers | |||||||||||||||||||||
| TagentConfigAccessControlTable | 1.3.6.1.4.1.2468.1.2.1.1.10.26 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of managers which can access USHA with private community string. | |||||||||||||||||||||
| RagentConfigAccessControlEntry | 1.3.6.1.4.1.2468.1.2.1.1.10.26.1 | NA | mandatory | ||||||||||||||||||
| CaccessIndex | 1.3.6.1.4.1.2468.1.2.1.1.10.26.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to a access control entry. | |||||||||||||||||||||
| CaccessControlAddr | 1.3.6.1.4.1.2468.1.2.1.1.10.26.1.2 | IpAddress | RW | mandatory | |||||||||||||||||
column · IpAddress · read-write · mandatory The IP address of the manager to access USHA | |||||||||||||||||||||
| CaccessCommunityString | 1.3.6.1.4.1.2468.1.2.1.1.10.26.1.3 | DisplayString (SIZE (0..19)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..19)) · read-write · mandatory The community name to use in the manager when access USHA | |||||||||||||||||||||
| CaccessControlMode | 1.3.6.1.4.1.2468.1.2.1.1.10.26.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Access type, only read/Write access type can change parameter of USHA
| |||||||||||||||||||||
| SagentConfigDefaultLanguage | 1.3.6.1.4.1.2468.1.2.1.1.10.27 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The default languauge for browser, when set to auto(1) USHA will send page in the language depends on the request language of browser.
| |||||||||||||||||||||
| NemdStatus | 1.3.6.1.4.1.2468.1.2.1.1.11 | ||||||||||||||||||||
| SemdSatatusEmdType | 1.3.6.1.4.1.2468.1.2.1.1.11.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The type of EMD plugged into the port.
| |||||||||||||||||||||
| SemdSatatusTemperature | 1.3.6.1.4.1.2468.1.2.1.1.11.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The measurement of EMD temperature, in 0.1 degree | |||||||||||||||||||||
| SemdSatatusHumidity | 1.3.6.1.4.1.2468.1.2.1.1.11.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The measurement of EMD humidity, in 0.1 degree | |||||||||||||||||||||
| SemdSatatusAlarm1 | 1.3.6.1.4.1.2468.1.2.1.1.11.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The EMD alarm-1 status
| |||||||||||||||||||||
| SemdSatatusAlarm2 | 1.3.6.1.4.1.2468.1.2.1.1.11.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The EMD alarm-2 status
| |||||||||||||||||||||
| NemdConfig | 1.3.6.1.4.1.2468.1.2.1.1.12 | ||||||||||||||||||||
| SusahEmdConfigEmdConfig | 1.3.6.1.4.1.2468.1.2.1.1.12.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Enable or disable to detect presence of EMD
| |||||||||||||||||||||
| SemdConfigEmdName | 1.3.6.1.4.1.2468.1.2.1.1.12.2 | DisplayString (SIZE (0..15)) | RW | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..15)) · read-write · mandatory Description of EMD | |||||||||||||||||||||
| NemdConfigTemperature | 1.3.6.1.4.1.2468.1.2.1.1.12.3 | ||||||||||||||||||||
| SemdConfigTempName | 1.3.6.1.4.1.2468.1.2.1.1.12.3.1 | DisplayString (SIZE (0..15)) | RW | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..15)) · read-write · mandatory Description of EMD temperature sensor | |||||||||||||||||||||
| SemdConfigTempHighSetPoint | 1.3.6.1.4.1.2468.1.2.1.1.12.3.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The set point for high temperature warning, in degrees | |||||||||||||||||||||
| SemdConfigTempHighStatus | 1.3.6.1.4.1.2468.1.2.1.1.12.3.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory To enable/disable high set point check with emd temperature.
| |||||||||||||||||||||
| SemdConfigTempLowSetPoint | 1.3.6.1.4.1.2468.1.2.1.1.12.3.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The set point for low temperature warning, in degrees | |||||||||||||||||||||
| SemdConfigTempLowStatus | 1.3.6.1.4.1.2468.1.2.1.1.12.3.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory To enable/disable low set point check with emd temperature.
| |||||||||||||||||||||
| SemdConfigTempOffset | 1.3.6.1.4.1.2468.1.2.1.1.12.3.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The offset to calibrate temperature of EMD, in degrees | |||||||||||||||||||||
| NemdConfigHumidity | 1.3.6.1.4.1.2468.1.2.1.1.12.4 | ||||||||||||||||||||
| SemdConfigHumidityName | 1.3.6.1.4.1.2468.1.2.1.1.12.4.1 | DisplayString (SIZE (0..15)) | RW | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..15)) · read-write · mandatory Description of EMD humidity sensor | |||||||||||||||||||||
| SemdConfigHumidityHighSetPoint | 1.3.6.1.4.1.2468.1.2.1.1.12.4.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The set point for high humidity warning, in % | |||||||||||||||||||||
| SemdConfigHumidityLowStatus | 1.3.6.1.4.1.2468.1.2.1.1.12.4.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory To enable/disable high set point check with emd humidity.
| |||||||||||||||||||||
| SemdConfigHumidityLowSetPoint | 1.3.6.1.4.1.2468.1.2.1.1.12.4.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The set point for low humidity warning, in % | |||||||||||||||||||||
| SemdConfigHumidityHighStatus | 1.3.6.1.4.1.2468.1.2.1.1.12.4.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory To enable/disable low set point check with emd humidity.
| |||||||||||||||||||||
| SemdConfigHumidityOffset | 1.3.6.1.4.1.2468.1.2.1.1.12.4.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The offset to calibrate humidity of EMD, in % | |||||||||||||||||||||
| NemdConfigAlarm1 | 1.3.6.1.4.1.2468.1.2.1.1.12.5 | ||||||||||||||||||||
| SemdConfigAlarm1Name | 1.3.6.1.4.1.2468.1.2.1.1.12.5.1 | DisplayString (SIZE (0..15)) | RW | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..15)) · read-write · mandatory Description of EMD alarm-1 | |||||||||||||||||||||
| SemdConfigAlarm1Type | 1.3.6.1.4.1.2468.1.2.1.1.12.5.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The alarm-1 operation type
| |||||||||||||||||||||
| NemdConfigAlarm2 | 1.3.6.1.4.1.2468.1.2.1.1.12.6 | ||||||||||||||||||||
| SemdConfigAlarm2Name | 1.3.6.1.4.1.2468.1.2.1.1.12.6.1 | DisplayString (SIZE (0..15)) | RW | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..15)) · read-write · mandatory Description of EMD alarm-2 | |||||||||||||||||||||
| SemdConfigAlarm2Type | 1.3.6.1.4.1.2468.1.2.1.1.12.6.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The alarm-1 operation type
| |||||||||||||||||||||
| NupsTrapGroup | 1.3.6.1.4.1.2468.1.2.1.2 | ||||||||||||||||||||
| !ushaPowerRestored | 1.3.6.1.4.1.2468.1.2.1.2.0.1 | ||||||||||||||||||||
notification INFORMATION: Utility power has been restore. | |||||||||||||||||||||
| !ushaPowerFail | 1.3.6.1.4.1.2468.1.2.1.2.0.2 | ||||||||||||||||||||
notification WARNING: Utility power not available. | |||||||||||||||||||||
| !ushaReturnFromLowBattery | 1.3.6.1.4.1.2468.1.2.1.2.0.3 | ||||||||||||||||||||
notification INFORMATION: The UPS has return from a low battery condition. | |||||||||||||||||||||
| !ushaLowBattery | 1.3.6.1.4.1.2468.1.2.1.2.0.4 | ||||||||||||||||||||
notification SEVERE: The UPS batteries are low and will soon be exhausted. | |||||||||||||||||||||
| !ushaUpsOk | 1.3.6.1.4.1.2468.1.2.1.2.0.5 | ||||||||||||||||||||
notification INFORMATION: The ups is working fine. | |||||||||||||||||||||
| !ushaUpsFailed | 1.3.6.1.4.1.2468.1.2.1.2.0.6 | ||||||||||||||||||||
notification SEVERE: The ups is not working fine. | |||||||||||||||||||||
| !ushaUpsNotOnBattery | 1.3.6.1.4.1.2468.1.2.1.2.0.7 | ||||||||||||||||||||
notification INFORMATION: The UPS is not on battery power. | |||||||||||||||||||||
| !ushaUpsOnBattery | 1.3.6.1.4.1.2468.1.2.1.2.0.8 | ||||||||||||||||||||
notification WARNING: The UPS has switched to battery backup power. | |||||||||||||||||||||
| !ushaTestOver | 1.3.6.1.4.1.2468.1.2.1.2.0.9 | ||||||||||||||||||||
notification INFORMATION: The testing of UPS is completed. | |||||||||||||||||||||
| !ushaTestInProgress | 1.3.6.1.4.1.2468.1.2.1.2.0.10 | ||||||||||||||||||||
notification INFORMATION: The testing is going on ups. | |||||||||||||||||||||
| !ushaBypassOn | 1.3.6.1.4.1.2468.1.2.1.2.0.11 | ||||||||||||||||||||
notification INFORMATION: The UPS has enabled bypass. | |||||||||||||||||||||
| !ushaUpsOnline | 1.3.6.1.4.1.2468.1.2.1.2.0.12 | ||||||||||||||||||||
notification INFORMATION: The UPS is not on Bypass and return to normal status. | |||||||||||||||||||||
| !ushaCommunicationLost | 1.3.6.1.4.1.2468.1.2.1.2.0.13 | ||||||||||||||||||||
notification SEVERE: Communication to the UPS has been lost. | |||||||||||||||||||||
| !ushaCommunicationEstablished | 1.3.6.1.4.1.2468.1.2.1.2.0.14 | ||||||||||||||||||||
notification INFORMATION: Communication with the UPS has been established. | |||||||||||||||||||||
| !ushaUpsGoingDown | 1.3.6.1.4.1.2468.1.2.1.2.0.15 | ||||||||||||||||||||
notification WARNING: The ups has been given shutdown command. | |||||||||||||||||||||
| !ushaUpsTurnedOff | 1.3.6.1.4.1.2468.1.2.1.2.0.16 | ||||||||||||||||||||
notification INFORMATION: UPS turn off. | |||||||||||||||||||||
| !ushaUpsSleeping | 1.3.6.1.4.1.2468.1.2.1.2.0.17 | ||||||||||||||||||||
| !ushaUpsWokeUp | 1.3.6.1.4.1.2468.1.2.1.2.0.18 | ||||||||||||||||||||
notification INFORMATION: The UPS woke up from sleep mode. | |||||||||||||||||||||
| !ushaUpsRebooted | 1.3.6.1.4.1.2468.1.2.1.2.0.19 | ||||||||||||||||||||
notification INFORMATION: The UPS is reboot. | |||||||||||||||||||||
| !ushaUpsShutdownCancelled | 1.3.6.1.4.1.2468.1.2.1.2.0.20 | ||||||||||||||||||||
notification INFORMATION: The UPS shutdown process had been cancelled. | |||||||||||||||||||||
| !ushaUpsNotOverTemperature | 1.3.6.1.4.1.2468.1.2.1.2.0.21 | ||||||||||||||||||||
notification INFORMATION: The UPS internal temperature return to normal. | |||||||||||||||||||||
| !ushaUpsOverTemperature | 1.3.6.1.4.1.2468.1.2.1.2.0.22 | ||||||||||||||||||||
notification SEVERE: The UPS temperature is too high. | |||||||||||||||||||||
| !ushaUpsNotOverLoad | 1.3.6.1.4.1.2468.1.2.1.2.0.23 | ||||||||||||||||||||
notification INFORMATION: The UPS load return from overload. | |||||||||||||||||||||
| !ushaUpsOverLoad | 1.3.6.1.4.1.2468.1.2.1.2.0.24 | ||||||||||||||||||||
notification SEVERE: The UPS is overload. | |||||||||||||||||||||
| !ushaUpsModuleInserted | 1.3.6.1.4.1.2468.1.2.1.2.0.25 | ||||||||||||||||||||
notification WARNING: UPS Battery Module plug-in. | |||||||||||||||||||||
| !ushaUpsModuleRemoved | 1.3.6.1.4.1.2468.1.2.1.2.0.26 | ||||||||||||||||||||
notification WARNING: UPS Battery Module unplug. | |||||||||||||||||||||
| !emdTemperatureNotHigh | 1.3.6.1.4.1.2468.1.2.1.2.0.27 | ||||||||||||||||||||
notification INFORMATION: EMD Temperature not over high Set point. | |||||||||||||||||||||
| !emdTemperatureTooHigh | 1.3.6.1.4.1.2468.1.2.1.2.0.28 | ||||||||||||||||||||
notification WARNING: EMD Temperature over high Set point. | |||||||||||||||||||||
| !emdTemperatureNotLow | 1.3.6.1.4.1.2468.1.2.1.2.0.29 | ||||||||||||||||||||
notification INFORMATION: EMD Temperature not under low Set point. | |||||||||||||||||||||
| !emdTemperatureTooLow | 1.3.6.1.4.1.2468.1.2.1.2.0.30 | ||||||||||||||||||||
notification WARNING: EMD Temperature under low Set point. | |||||||||||||||||||||
| !emdHumidityNotHigh | 1.3.6.1.4.1.2468.1.2.1.2.0.31 | ||||||||||||||||||||
notification INFORMATION: EMD Humidity not over high Set point. | |||||||||||||||||||||
| !emdHumidityTooHigh | 1.3.6.1.4.1.2468.1.2.1.2.0.32 | ||||||||||||||||||||
notification WARNING: EMD Humidity over high Set point. | |||||||||||||||||||||
| !emdHumidityNotLow | 1.3.6.1.4.1.2468.1.2.1.2.0.33 | ||||||||||||||||||||
notification INFORMATION: EMD Humidity not under low Set point. | |||||||||||||||||||||
| !emdHumidityTooLow | 1.3.6.1.4.1.2468.1.2.1.2.0.34 | ||||||||||||||||||||
notification WARNING: EMD Humidity under low Set point. | |||||||||||||||||||||
| !emdAlarm1Normal | 1.3.6.1.4.1.2468.1.2.1.2.0.35 | ||||||||||||||||||||
| !emdAlarm1Active | 1.3.6.1.4.1.2468.1.2.1.2.0.36 | ||||||||||||||||||||
| !emdAlarm2Normal | 1.3.6.1.4.1.2468.1.2.1.2.0.37 | ||||||||||||||||||||
| !emdAlarm2Active | 1.3.6.1.4.1.2468.1.2.1.2.0.38 | ||||||||||||||||||||
| !ushaUpsInternalwarning | 1.3.6.1.4.1.2468.1.2.1.2.0.39 | ||||||||||||||||||||
notification WARNING: Internal warning. | |||||||||||||||||||||
| !ushaUpsReturnFromInternalwarning | 1.3.6.1.4.1.2468.1.2.1.2.0.40 | ||||||||||||||||||||
notification INFORMATION: Return from Internal warning. | |||||||||||||||||||||
| !ushaUpsEPOActive | 1.3.6.1.4.1.2468.1.2.1.2.0.41 | ||||||||||||||||||||
notification WARNING: EPO Active. | |||||||||||||||||||||
| !ushaUpsReturnFromEPOActive | 1.3.6.1.4.1.2468.1.2.1.2.0.42 | ||||||||||||||||||||
notification INFORMATION: Return from EPO Active. | |||||||||||||||||||||
| !ushaUpsModuleUnlock | 1.3.6.1.4.1.2468.1.2.1.2.0.43 | ||||||||||||||||||||
notification WARNING: Module Unlock. | |||||||||||||||||||||
| !ushaUpsReturnFromModuleUnlock | 1.3.6.1.4.1.2468.1.2.1.2.0.44 | ||||||||||||||||||||
notification INFORMATION: Return from Module Unlock. | |||||||||||||||||||||
| !ushaUpsMain1Neutralloss | 1.3.6.1.4.1.2468.1.2.1.2.0.45 | ||||||||||||||||||||
notification WARNING: Main 1 Neutral loss. | |||||||||||||||||||||
| !ushaUpsReturnFromMain1Neutralloss | 1.3.6.1.4.1.2468.1.2.1.2.0.46 | ||||||||||||||||||||
notification INFORMATION: Return from Main 1 Neutral loss. | |||||||||||||||||||||
| !ushaUpsMain1phaseerror | 1.3.6.1.4.1.2468.1.2.1.2.0.47 | ||||||||||||||||||||
notification WARNING: Main 1 phase error. | |||||||||||||||||||||
| !ushaUpsReturnFromMain1phaseerror | 1.3.6.1.4.1.2468.1.2.1.2.0.48 | ||||||||||||||||||||
notification INFORMATION: Return from Main 1 phase error. | |||||||||||||||||||||
| !ushaUpsSitefault | 1.3.6.1.4.1.2468.1.2.1.2.0.49 | ||||||||||||||||||||
notification WARNING: Site fault. | |||||||||||||||||||||
| !ushaUpsReturnFromSitefault | 1.3.6.1.4.1.2468.1.2.1.2.0.50 | ||||||||||||||||||||
notification INFORMATION: Return from Site fault. | |||||||||||||||||||||
| !ushaUpsBypassAbnormal | 1.3.6.1.4.1.2468.1.2.1.2.0.51 | ||||||||||||||||||||
notification WARNING: Bypass Abnormal. | |||||||||||||||||||||
| !ushaUpsReturnFromBypassAbnormal | 1.3.6.1.4.1.2468.1.2.1.2.0.52 | ||||||||||||||||||||
notification INFORMATION: Return from Bypass Abnormal. | |||||||||||||||||||||
| !ushaUpsBypassPhaseError | 1.3.6.1.4.1.2468.1.2.1.2.0.53 | ||||||||||||||||||||
notification WARNING: Bypass Phase Error. | |||||||||||||||||||||
| !ushaUpsReturnFromBypassPhaseError | 1.3.6.1.4.1.2468.1.2.1.2.0.54 | ||||||||||||||||||||
notification INFORMATION: Return from Bypass Phase Error. | |||||||||||||||||||||
| !ushaUpsBatteryOpen | 1.3.6.1.4.1.2468.1.2.1.2.0.55 | ||||||||||||||||||||
notification WARNING: Battery Open. | |||||||||||||||||||||
| !ushaUpsReturnFromBatteryOpen | 1.3.6.1.4.1.2468.1.2.1.2.0.56 | ||||||||||||||||||||
notification INFORMATION: Return from Battery Open. | |||||||||||||||||||||
| !ushaUpsBatteryOverCharge | 1.3.6.1.4.1.2468.1.2.1.2.0.57 | ||||||||||||||||||||
notification WARNING: Battery Over Charge. | |||||||||||||||||||||
| !ushaUpsReturnFromBatteryOverCharge | 1.3.6.1.4.1.2468.1.2.1.2.0.58 | ||||||||||||||||||||
notification INFORMATION: Return from Battery Over Charge. | |||||||||||||||||||||
| !ushaUpsBatteryReverse | 1.3.6.1.4.1.2468.1.2.1.2.0.59 | ||||||||||||||||||||
notification WARNING: Battery Reverse. | |||||||||||||||||||||
| !ushaUpsReturnFromBatteryReverse | 1.3.6.1.4.1.2468.1.2.1.2.0.60 | ||||||||||||||||||||
notification INFORMATION: Return from Battery Reverse. | |||||||||||||||||||||
| !ushaUpsOverloadforewarning | 1.3.6.1.4.1.2468.1.2.1.2.0.61 | ||||||||||||||||||||
notification WARNING: Overload forewarning. | |||||||||||||||||||||
| !ushaUpsReturnFromOverloadforewarning | 1.3.6.1.4.1.2468.1.2.1.2.0.62 | ||||||||||||||||||||
notification INFORMATION: Return from Overload forewarning. | |||||||||||||||||||||
| !ushaUpsOverloadWarning | 1.3.6.1.4.1.2468.1.2.1.2.0.63 | ||||||||||||||||||||
notification WARNING: Overload Warning. | |||||||||||||||||||||
| !ushaUpsReturnFromOverloadWarning | 1.3.6.1.4.1.2468.1.2.1.2.0.64 | ||||||||||||||||||||
notification INFORMATION: Return from Overload Warning. | |||||||||||||||||||||
| !ushaUpsFanLock | 1.3.6.1.4.1.2468.1.2.1.2.0.65 | ||||||||||||||||||||
notification WARNING: Fan Lock. | |||||||||||||||||||||
| !ushaUpsReturnFromFanLock | 1.3.6.1.4.1.2468.1.2.1.2.0.66 | ||||||||||||||||||||
notification INFORMATION: Return from Fan Lock. | |||||||||||||||||||||
| !ushaUpsMaintaincoverisopen | 1.3.6.1.4.1.2468.1.2.1.2.0.67 | ||||||||||||||||||||
notification WARNING: Maintain cover is open. | |||||||||||||||||||||
| !ushaUpsReturnFromMaintaincoverisopen | 1.3.6.1.4.1.2468.1.2.1.2.0.68 | ||||||||||||||||||||
notification INFORMATION: Return from Maintain cover is open. | |||||||||||||||||||||
| !ushaUpsChargerfault | 1.3.6.1.4.1.2468.1.2.1.2.0.69 | ||||||||||||||||||||
notification WARNING: Charger fault. | |||||||||||||||||||||
| !ushaUpsReturnFromChargerfault | 1.3.6.1.4.1.2468.1.2.1.2.0.70 | ||||||||||||||||||||
notification INFORMATION: Return from Charger fault. | |||||||||||||||||||||
| !ushaUpsModulelocationerror | 1.3.6.1.4.1.2468.1.2.1.2.0.71 | ||||||||||||||||||||
notification WARNING: Module location error. | |||||||||||||||||||||
| !ushaUpsReturnFromModulelocationerror | 1.3.6.1.4.1.2468.1.2.1.2.0.72 | ||||||||||||||||||||
notification INFORMATION: Return from Module location error. | |||||||||||||||||||||
| !ushaUpsTurnonabnormal | 1.3.6.1.4.1.2468.1.2.1.2.0.73 | ||||||||||||||||||||
notification WARNING: Turn on abnormal. | |||||||||||||||||||||
| !ushaUpsReturnFromTurnonabnormal | 1.3.6.1.4.1.2468.1.2.1.2.0.74 | ||||||||||||||||||||
notification INFORMATION: Return from Turn on abnormal. | |||||||||||||||||||||
| !ushaUpsRedundancyloss | 1.3.6.1.4.1.2468.1.2.1.2.0.75 | ||||||||||||||||||||
notification WARNING: Redundancy loss. | |||||||||||||||||||||
| !ushaUpsReturnFromRedundancyloss | 1.3.6.1.4.1.2468.1.2.1.2.0.76 | ||||||||||||||||||||
notification INFORMATION: Return from Redundancy loss. | |||||||||||||||||||||
| !ushaUpsHotSwapActived | 1.3.6.1.4.1.2468.1.2.1.2.0.77 | ||||||||||||||||||||
notification WARNING: Hot Swap Actived. | |||||||||||||||||||||
| !ushaUpsReturnFromHotSwapActived | 1.3.6.1.4.1.2468.1.2.1.2.0.78 | ||||||||||||||||||||
notification INFORMATION: Return from Hot Swap Actived. | |||||||||||||||||||||
| !ushaUpsBatteryInform | 1.3.6.1.4.1.2468.1.2.1.2.0.79 | ||||||||||||||||||||
notification WARNING: Battery Inform. | |||||||||||||||||||||
| !ushaUpsReturnFromBatteryInform | 1.3.6.1.4.1.2468.1.2.1.2.0.80 | ||||||||||||||||||||
notification INFORMATION: Return from Battery Inform. | |||||||||||||||||||||
| !ushaUpsInspectionInform | 1.3.6.1.4.1.2468.1.2.1.2.0.81 | ||||||||||||||||||||
notification WARNING: Inspection Inform. | |||||||||||||||||||||
| !ushaUpsReturnFromInspectionInform | 1.3.6.1.4.1.2468.1.2.1.2.0.82 | ||||||||||||||||||||
notification INFORMATION: Return from Inspection Inform. | |||||||||||||||||||||
| !ushaUpsGuaranteeInform | 1.3.6.1.4.1.2468.1.2.1.2.0.83 | ||||||||||||||||||||
notification WARNING: Guarantee Inform. | |||||||||||||||||||||
| !ushaUpsReturnFromGuaranteeInform | 1.3.6.1.4.1.2468.1.2.1.2.0.84 | ||||||||||||||||||||
notification INFORMATION: Return from Guarantee Inform. | |||||||||||||||||||||
| !ushaUpsTemperatureLow | 1.3.6.1.4.1.2468.1.2.1.2.0.85 | ||||||||||||||||||||
notification WARNING: Temperature Low. | |||||||||||||||||||||
| !ushaUpsReturnFromTemperatureLow | 1.3.6.1.4.1.2468.1.2.1.2.0.86 | ||||||||||||||||||||
notification INFORMATION: Return from Temperature Low. | |||||||||||||||||||||
| !ushaUpsTemperatureHigh | 1.3.6.1.4.1.2468.1.2.1.2.0.87 | ||||||||||||||||||||
notification WARNING: Temperature High. | |||||||||||||||||||||
| !ushaUpsReturnFromTemperatureHigh | 1.3.6.1.4.1.2468.1.2.1.2.0.88 | ||||||||||||||||||||
notification INFORMATION: Return from Temperature High. | |||||||||||||||||||||
| !ushaUpsBatteryOverTemperature | 1.3.6.1.4.1.2468.1.2.1.2.0.89 | ||||||||||||||||||||
notification WARNING: Battery Over Temperature. | |||||||||||||||||||||
| !ushaUpsReturnFromBatteryOverTemperature | 1.3.6.1.4.1.2468.1.2.1.2.0.90 | ||||||||||||||||||||
notification INFORMATION: Return from Battery Over Temperature. | |||||||||||||||||||||
| !ushaUpsFanMaintainInform | 1.3.6.1.4.1.2468.1.2.1.2.0.91 | ||||||||||||||||||||
notification WARNING: Fan Maintain Inform. | |||||||||||||||||||||
| !ushaUpsReturnFromFanMaintainInform | 1.3.6.1.4.1.2468.1.2.1.2.0.92 | ||||||||||||||||||||
notification INFORMATION: Return from Fan Maintain Inform. | |||||||||||||||||||||
| !ushaUpsBusCapacitanceMaintainInform | 1.3.6.1.4.1.2468.1.2.1.2.0.93 | ||||||||||||||||||||
notification WARNING: Bus Capacitance Maintain Inform. | |||||||||||||||||||||
| !ushaUpsReturnFromBusCapacitanceMaintainInform | 1.3.6.1.4.1.2468.1.2.1.2.0.94 | ||||||||||||||||||||
notification INFORMATION: Return from Bus Capacitance Maintain Inform. | |||||||||||||||||||||
| !ushaUpsSystemOverCapacity | 1.3.6.1.4.1.2468.1.2.1.2.0.95 | ||||||||||||||||||||
notification WARNING: System Over Capacity. | |||||||||||||||||||||
| !ushaUpsReturnFromSystemOverCapacity | 1.3.6.1.4.1.2468.1.2.1.2.0.96 | ||||||||||||||||||||
notification INFORMATION: Return from System Over Capacity. | |||||||||||||||||||||
Traps / Notifications
- emdAlarm1Active
1.3.6.1.4.1.2468.1.2.1.2.0.36 - emdAlarm1Normal
1.3.6.1.4.1.2468.1.2.1.2.0.35 - emdAlarm2Active
1.3.6.1.4.1.2468.1.2.1.2.0.38 - emdAlarm2Normal
1.3.6.1.4.1.2468.1.2.1.2.0.37 - emdHumidityNotHigh
1.3.6.1.4.1.2468.1.2.1.2.0.31 - emdHumidityNotLow
1.3.6.1.4.1.2468.1.2.1.2.0.33 - emdHumidityTooHigh
1.3.6.1.4.1.2468.1.2.1.2.0.32 - emdHumidityTooLow
1.3.6.1.4.1.2468.1.2.1.2.0.34 - emdTemperatureNotHigh
1.3.6.1.4.1.2468.1.2.1.2.0.27 - emdTemperatureNotLow
1.3.6.1.4.1.2468.1.2.1.2.0.29 - emdTemperatureTooHigh
1.3.6.1.4.1.2468.1.2.1.2.0.28 - emdTemperatureTooLow
1.3.6.1.4.1.2468.1.2.1.2.0.30 - ushaBypassOn
1.3.6.1.4.1.2468.1.2.1.2.0.11 - ushaCommunicationEstablished
1.3.6.1.4.1.2468.1.2.1.2.0.14 - ushaCommunicationLost
1.3.6.1.4.1.2468.1.2.1.2.0.13 - ushaLowBattery
1.3.6.1.4.1.2468.1.2.1.2.0.4 - ushaPowerFail
1.3.6.1.4.1.2468.1.2.1.2.0.2 - ushaPowerRestored
1.3.6.1.4.1.2468.1.2.1.2.0.1 - ushaReturnFromLowBattery
1.3.6.1.4.1.2468.1.2.1.2.0.3 - ushaTestInProgress
1.3.6.1.4.1.2468.1.2.1.2.0.10 - ushaTestOver
1.3.6.1.4.1.2468.1.2.1.2.0.9 - ushaUpsBatteryInform
1.3.6.1.4.1.2468.1.2.1.2.0.79 - ushaUpsBatteryOpen
1.3.6.1.4.1.2468.1.2.1.2.0.55 - ushaUpsBatteryOverCharge
1.3.6.1.4.1.2468.1.2.1.2.0.57 - ushaUpsBatteryOverTemperature
1.3.6.1.4.1.2468.1.2.1.2.0.89 - ushaUpsBatteryReverse
1.3.6.1.4.1.2468.1.2.1.2.0.59 - ushaUpsBusCapacitanceMaintainInform
1.3.6.1.4.1.2468.1.2.1.2.0.93 - ushaUpsBypassAbnormal
1.3.6.1.4.1.2468.1.2.1.2.0.51 - ushaUpsBypassPhaseError
1.3.6.1.4.1.2468.1.2.1.2.0.53 - ushaUpsChargerfault
1.3.6.1.4.1.2468.1.2.1.2.0.69 - ushaUpsEPOActive
1.3.6.1.4.1.2468.1.2.1.2.0.41 - ushaUpsFailed
1.3.6.1.4.1.2468.1.2.1.2.0.6 - ushaUpsFanLock
1.3.6.1.4.1.2468.1.2.1.2.0.65 - ushaUpsFanMaintainInform
1.3.6.1.4.1.2468.1.2.1.2.0.91 - ushaUpsGoingDown
1.3.6.1.4.1.2468.1.2.1.2.0.15 - ushaUpsGuaranteeInform
1.3.6.1.4.1.2468.1.2.1.2.0.83 - ushaUpsHotSwapActived
1.3.6.1.4.1.2468.1.2.1.2.0.77 - ushaUpsInspectionInform
1.3.6.1.4.1.2468.1.2.1.2.0.81 - ushaUpsInternalwarning
1.3.6.1.4.1.2468.1.2.1.2.0.39 - ushaUpsMain1Neutralloss
1.3.6.1.4.1.2468.1.2.1.2.0.45 - ushaUpsMain1phaseerror
1.3.6.1.4.1.2468.1.2.1.2.0.47 - ushaUpsMaintaincoverisopen
1.3.6.1.4.1.2468.1.2.1.2.0.67 - ushaUpsModuleInserted
1.3.6.1.4.1.2468.1.2.1.2.0.25 - ushaUpsModuleRemoved
1.3.6.1.4.1.2468.1.2.1.2.0.26 - ushaUpsModuleUnlock
1.3.6.1.4.1.2468.1.2.1.2.0.43 - ushaUpsModulelocationerror
1.3.6.1.4.1.2468.1.2.1.2.0.71 - ushaUpsNotOnBattery
1.3.6.1.4.1.2468.1.2.1.2.0.7 - ushaUpsNotOverLoad
1.3.6.1.4.1.2468.1.2.1.2.0.23 - ushaUpsNotOverTemperature
1.3.6.1.4.1.2468.1.2.1.2.0.21 - ushaUpsOk
1.3.6.1.4.1.2468.1.2.1.2.0.5 - ushaUpsOnBattery
1.3.6.1.4.1.2468.1.2.1.2.0.8 - ushaUpsOnline
1.3.6.1.4.1.2468.1.2.1.2.0.12 - ushaUpsOverLoad
1.3.6.1.4.1.2468.1.2.1.2.0.24 - ushaUpsOverTemperature
1.3.6.1.4.1.2468.1.2.1.2.0.22 - ushaUpsOverloadWarning
1.3.6.1.4.1.2468.1.2.1.2.0.63 - ushaUpsOverloadforewarning
1.3.6.1.4.1.2468.1.2.1.2.0.61 - ushaUpsRebooted
1.3.6.1.4.1.2468.1.2.1.2.0.19 - ushaUpsRedundancyloss
1.3.6.1.4.1.2468.1.2.1.2.0.75 - ushaUpsReturnFromBatteryInform
1.3.6.1.4.1.2468.1.2.1.2.0.80 - ushaUpsReturnFromBatteryOpen
1.3.6.1.4.1.2468.1.2.1.2.0.56 - ushaUpsReturnFromBatteryOverCharge
1.3.6.1.4.1.2468.1.2.1.2.0.58 - ushaUpsReturnFromBatteryOverTemperature
1.3.6.1.4.1.2468.1.2.1.2.0.90 - ushaUpsReturnFromBatteryReverse
1.3.6.1.4.1.2468.1.2.1.2.0.60 - ushaUpsReturnFromBusCapacitanceMaintainInform
1.3.6.1.4.1.2468.1.2.1.2.0.94 - ushaUpsReturnFromBypassAbnormal
1.3.6.1.4.1.2468.1.2.1.2.0.52 - ushaUpsReturnFromBypassPhaseError
1.3.6.1.4.1.2468.1.2.1.2.0.54 - ushaUpsReturnFromChargerfault
1.3.6.1.4.1.2468.1.2.1.2.0.70 - ushaUpsReturnFromEPOActive
1.3.6.1.4.1.2468.1.2.1.2.0.42 - ushaUpsReturnFromFanLock
1.3.6.1.4.1.2468.1.2.1.2.0.66 - ushaUpsReturnFromFanMaintainInform
1.3.6.1.4.1.2468.1.2.1.2.0.92 - ushaUpsReturnFromGuaranteeInform
1.3.6.1.4.1.2468.1.2.1.2.0.84 - ushaUpsReturnFromHotSwapActived
1.3.6.1.4.1.2468.1.2.1.2.0.78 - ushaUpsReturnFromInspectionInform
1.3.6.1.4.1.2468.1.2.1.2.0.82 - ushaUpsReturnFromInternalwarning
1.3.6.1.4.1.2468.1.2.1.2.0.40 - ushaUpsReturnFromMain1Neutralloss
1.3.6.1.4.1.2468.1.2.1.2.0.46 - ushaUpsReturnFromMain1phaseerror
1.3.6.1.4.1.2468.1.2.1.2.0.48 - ushaUpsReturnFromMaintaincoverisopen
1.3.6.1.4.1.2468.1.2.1.2.0.68 - ushaUpsReturnFromModuleUnlock
1.3.6.1.4.1.2468.1.2.1.2.0.44 - ushaUpsReturnFromModulelocationerror
1.3.6.1.4.1.2468.1.2.1.2.0.72 - ushaUpsReturnFromOverloadWarning
1.3.6.1.4.1.2468.1.2.1.2.0.64 - ushaUpsReturnFromOverloadforewarning
1.3.6.1.4.1.2468.1.2.1.2.0.62 - ushaUpsReturnFromRedundancyloss
1.3.6.1.4.1.2468.1.2.1.2.0.76 - ushaUpsReturnFromSitefault
1.3.6.1.4.1.2468.1.2.1.2.0.50 - ushaUpsReturnFromSystemOverCapacity
1.3.6.1.4.1.2468.1.2.1.2.0.96 - ushaUpsReturnFromTemperatureHigh
1.3.6.1.4.1.2468.1.2.1.2.0.88 - ushaUpsReturnFromTemperatureLow
1.3.6.1.4.1.2468.1.2.1.2.0.86 - ushaUpsReturnFromTurnonabnormal
1.3.6.1.4.1.2468.1.2.1.2.0.74 - ushaUpsShutdownCancelled
1.3.6.1.4.1.2468.1.2.1.2.0.20 - ushaUpsSitefault
1.3.6.1.4.1.2468.1.2.1.2.0.49 - ushaUpsSleeping
1.3.6.1.4.1.2468.1.2.1.2.0.17 - ushaUpsSystemOverCapacity
1.3.6.1.4.1.2468.1.2.1.2.0.95 - ushaUpsTemperatureHigh
1.3.6.1.4.1.2468.1.2.1.2.0.87 - ushaUpsTemperatureLow
1.3.6.1.4.1.2468.1.2.1.2.0.85 - ushaUpsTurnedOff
1.3.6.1.4.1.2468.1.2.1.2.0.16 - ushaUpsTurnonabnormal
1.3.6.1.4.1.2468.1.2.1.2.0.73 - ushaUpsWokeUp
1.3.6.1.4.1.2468.1.2.1.2.0.18