HUAWEI-SITE-MONITOR-MIB
HUAWEI Technology Co.,LtdSite Monitor MIB defines MIB objects which provides load and backup management, patch management NMS interfaces. The current version is V1.01
snmptranslate -m HUAWEI-SITE-MONITOR-MIB -Tpsnmpwalk -v2c -c <community> -m HUAWEI-SITE-MONITOR-MIB <host> 1.3.6.1.4.1.2011.6.164Imports
| HUAWEI-MIB | huaweiUtility |
|---|---|
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP, OBJECT-GROUP |
| SNMPv2-SMI | Bits, Integer32, IpAddress, MODULE-IDENTITY, MibIdentifier, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, TimeTicks, Unsigned32, iso |
| SNMPv2-TC | DisplayString, PhysAddress, TEXTUAL-CONVENTION |
OID tree
| Name | OID | Type | Access | Status | Example | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| IhwSiteMonitorMIB | 1.3.6.1.4.1.2011.6.164 | ||||||||||||||||||||
identity Site Monitor MIB defines MIB objects which provides load and backup management, patch management NMS interfaces. The current version is V1.01 | |||||||||||||||||||||
| NhwSiteMonitorMIBObjects | 1.3.6.1.4.1.2011.6.164.1 | ||||||||||||||||||||
| NhwSiteInfo | 1.3.6.1.4.1.2011.6.164.1.1 | ||||||||||||||||||||
| NhwSiteSummary | 1.3.6.1.4.1.2011.6.164.1.1.1 | ||||||||||||||||||||
| ShwSiteId | 1.3.6.1.4.1.2011.6.164.1.1.1.1 | Unsigned32 | RO | 0 | |||||||||||||||||
scalar · Unsigned32 · read-only · current Site ID, default value: 000,000. Naming rule of the site device ID (six digits): The first three digits indicate the device name and the last three digits indicate the serial number (SN) of the device. If the last three digits are 000, it indicates a virtual device. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwSiteName | 1.3.6.1.4.1.2011.6.164.1.1.1.2 | OCTET STRING (SIZE (0..63)) | RW | Huawei eMap | |||||||||||||||||
scalar · OCTET STRING (SIZE (0..63)) · read-write · current Site name, which users can configure, is used to specify a site. Otherwise, the configured character can not be any other languages except English. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwSiteAdminAddr | 1.3.6.1.4.1.2011.6.164.1.1.1.3 | Unsigned32 (0..65535) | RW | 1 | |||||||||||||||||
scalar · Unsigned32 (0..65535) · read-write · current Site administrant address, which users can assigned, is the unique ID of a site. It is used for device management by NMS, and value range is 0 to 65535. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwSiteDescription | 1.3.6.1.4.1.2011.6.164.1.1.1.4 | OCTET STRING (SIZE (0..127)) | RW | HUAWEI SMU | |||||||||||||||||
scalar · OCTET STRING (SIZE (0..127)) · read-write · current Site description. It is of the character string type. It is used to describe the site information such as the site location, which users can configure. Otherwise, the configured character can not be any other languages except English. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwNetIdentifier | 1.3.6.1.4.1.2011.6.164.1.1.1.5 | OCTET STRING (SIZE (0..63)) | RW | net identifier | |||||||||||||||||
scalar · OCTET STRING (SIZE (0..63)) · read-write · current NE ID. It is of the character string type. It is the unique ID of the site (an independent network element (NE)) on the network. Otherwise, the configured character can not be any other languages except English. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwSiteIp | 1.3.6.1.4.1.2011.6.164.1.1.1.6 | OCTET STRING (SIZE (8..16)) | RO | 10.0.0.2 | |||||||||||||||||
scalar · OCTET STRING (SIZE (8..16)) · read-only · current Site IP address, default value is 192.168.0.10. Users need to configure the site IP address. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwSiteNetmask | 1.3.6.1.4.1.2011.6.164.1.1.1.7 | OCTET STRING (SIZE (8..16)) | RO | 255.255.255.0 | |||||||||||||||||
scalar · OCTET STRING (SIZE (8..16)) · read-only · current Site netmask, default value is 255.255.0.0. Users need to configure the site netmask. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwSiteGateway | 1.3.6.1.4.1.2011.6.164.1.1.1.8 | OCTET STRING (SIZE (8..16)) | RO | 10.0.0.1 | |||||||||||||||||
scalar · OCTET STRING (SIZE (8..16)) · read-only · current Site gateway, default value: 192.168.0.1. Users need to configure the site gateway. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwSiteDGWorkStatus | 1.3.6.1.4.1.2011.6.164.1.1.1.9 | INTEGER | RO | working(2) | |||||||||||||||||
scalar · INTEGER · read-only · current State of the diesel working state. It is an enumeration type: If the enumeration value is 1, it indicates that the diesel is in the idle state; If the enumeration value is 2, it indicates that the diesel is in the working state; If the enumeration value is 255, it indicates diesel operation status unknown.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NhwSiteAlarms | 1.3.6.1.4.1.2011.6.164.1.1.2 | ||||||||||||||||||||
| ShwDeviceTrapOrdinalNumber | 1.3.6.1.4.1.2011.6.164.1.1.2.1 | Unsigned32 | RW | 0 | |||||||||||||||||
scalar · Unsigned32 · read-write · current Site device event trap serial number (SN) is the unique ID of the device event trap. It is used to resend and synchronize event traps. Its value range is 0 to 4294967296. When the value exceeds the maximum value, the system automatically clears the value and numbers the alarm from 0 to 4294967296. If the network management system (NMS) recieve the alarm number is not consequential, in such case that it notifies the SNMP agent the event trap number required. So the monitor send the 50 event trap messages in maximum, after consequencial number required by NMS again. Specially, if NMS set the value to 0, the agent would clear the alarm queue automatically. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwAlarmTrapOrdinalNumber | 1.3.6.1.4.1.2011.6.164.1.1.2.2 | Unsigned32 | RW | 6 | |||||||||||||||||
scalar · Unsigned32 · read-write · current Site alarm serial number (SN) is the unique ID of the alarm Trap. It is used to resend and synchronize alarms. Its value range is 0 to 4294967296. When the value exceeds the maximum value, the system automatically clears the value and numbers the alarm from 0 to 4294967296. If the network management system (NMS) recieve the alarm number is not consequential, in such case that it notifies the SNMP agent the alarm number required. So the monitor send the 50 alarm messages in maximum, after consequencial number required by NMS again. Specially, if NMS set the value to 0, the agent would clear the alarm queue automatically. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwAlarmQuantity | 1.3.6.1.4.1.2011.6.164.1.1.2.3 | Unsigned32 (0..65535) | RO | 383 | |||||||||||||||||
scalar · Unsigned32 (0..65535) · read-only · current Alarm number in site alarm list which are support. It is used for alarm list management by NMS, and value range is 0 to 65535. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ThwSiteAlarmTable | 1.3.6.1.4.1.2011.6.164.1.1.2.100 | NA | |||||||||||||||||||
table · not-accessible · current Site alarms table. The table containing alarm information on the site management. Use this table to get site alarm name, alarm level, alarm signal description, and alarm port description, which can be used as VB of alarm traps. This table's index is hwAlarmIndex, clone site alarms table. | |||||||||||||||||||||
| RhwSiteAlarmEntry | 1.3.6.1.4.1.2011.6.164.1.1.2.100.1 | NA | |||||||||||||||||||
| ChwAlarmIndex | 1.3.6.1.4.1.2011.6.164.1.1.2.100.1.1 | Integer32 (1..65535) | RO | 538322929 | |||||||||||||||||
column · Integer32 (1..65535) · read-only · current Site alarm table index. It is the unique ID of the site alarm. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwAlarmText | 1.3.6.1.4.1.2011.6.164.1.1.2.100.1.2 | OCTET STRING (SIZE (0..63)) | RO | Abnormal System Voltage Check | |||||||||||||||||
column · OCTET STRING (SIZE (0..63)) · read-only · current Alarm name. It is of the character string type, and used to specify the content of a specific alarm. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwAlarmLevel | 1.3.6.1.4.1.2011.6.164.1.1.2.100.1.3 | INTEGER | RW | major(2) | |||||||||||||||||
column · INTEGER · read-write · current Alarm level, which users can configure the alarm severity, is an enumeration type: If the enumeration value is 1, it indicates a critical alarm; If the enumeration value is 2, it indicates a major alarm; If the enumeration value is 3, it indicates a minor alarm; If the enumeration value is 4, it indicates a warning; If the enumeration value is 5, it indicates the alarm is cleared.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwAlarmSigDesc | 1.3.6.1.4.1.2011.6.164.1.1.2.100.1.4 | OCTET STRING (SIZE (0..127)) | RW | | |||||||||||||||||
column · OCTET STRING (SIZE (0..127)) · read-write · current Alarm signal description. It is used to add and describe alarm content. Users can define the description of the alarm. Otherwise, the configured character can not be any other languages except English. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwAlarmRowStatus | 1.3.6.1.4.1.2011.6.164.1.1.2.100.1.100 | RowStatus | RC | 1 | |||||||||||||||||
column · RowStatus · read-create · current RowStatus of site alarms table. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NhwSiteMonitors | 1.3.6.1.4.1.2011.6.164.1.2 | ||||||||||||||||||||
| NhwMonitorsGroup | 1.3.6.1.4.1.2011.6.164.1.2.1 | ||||||||||||||||||||
| ShwMonsGroupId | 1.3.6.1.4.1.2011.6.164.1.2.1.1 | Unsigned32 | RO | 1000 | |||||||||||||||||
scalar · Unsigned32 · read-only · current Site monitor group ID, is the unique ID of the site monitors. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwMonsGroupName | 1.3.6.1.4.1.2011.6.164.1.2.1.2 | OCTET STRING (SIZE (0..63)) | RW | Monitor Group | |||||||||||||||||
scalar · OCTET STRING (SIZE (0..63)) · read-write · current Site monitor group name is of the character string type, used to specify the monitor group. Users can configure it. Otherwise, the configured character can not be any other languages except English. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwMonsQuantity | 1.3.6.1.4.1.2011.6.164.1.2.1.3 | Unsigned32 (0..100) | RO | 1 | |||||||||||||||||
scalar · Unsigned32 (0..100) · read-only · current Total site intelligent monitors.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NhwMonitor | 1.3.6.1.4.1.2011.6.164.1.2.2 | ||||||||||||||||||||
| ThwMonitorTable | 1.3.6.1.4.1.2011.6.164.1.2.2.1 | NA | |||||||||||||||||||
table · not-accessible · current Site monitors table. Use this table to get site monitor equipment ID, site monitor equipment name, equipment software version, equipment PCB version, manufacturer, manufacture date, equipment serial No, equipment description, total runing time, and equipment controlled status, as well as to control monitor reset. This table's index is hwMonIndex, clone site monitors table. | |||||||||||||||||||||
| RhwMonitorEntry | 1.3.6.1.4.1.2011.6.164.1.2.2.1.1 | NA | |||||||||||||||||||
| ChwMonIndex | 1.3.6.1.4.1.2011.6.164.1.2.2.1.1.1 | Integer32 (1..100) | RO | 1 | |||||||||||||||||
column · Integer32 (1..100) · read-only · current Table index of the site monitors (hwSiteMonsTab) is restricted by the quantity of the site monitors (hwMonsQuantity). Value range: 1 to 100 Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwMonEquipId | 1.3.6.1.4.1.2011.6.164.1.2.2.1.1.2 | Unsigned32 (1001..1100) | RO | 1001 | |||||||||||||||||
column · Unsigned32 (1001..1100) · read-only · current Site monitor ID. Value range: 001,001 to 001,100, in which the first three digits indicate the device type and the last three digits indicate the device SN. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwMonEquipName | 1.3.6.1.4.1.2011.6.164.1.2.2.1.1.3 | OCTET STRING (SIZE (0..63)) | RW | Monitor | |||||||||||||||||
column · OCTET STRING (SIZE (0..63)) · read-write · current Monitor name. It is of the character string type, and users can set the name of the monitor. Otherwise, the configured character can not be any other languages except English. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwMonEquipDescription | 1.3.6.1.4.1.2011.6.164.1.2.2.1.1.4 | OCTET STRING (SIZE (0..127)) | RW | Monitor | |||||||||||||||||
column · OCTET STRING (SIZE (0..127)) · read-write · current Monitor description. It is of the character string type. Users can set the description of the monitor. Otherwise, the configured character can not be any other languages except English. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwMonEquipSoftwareVersion | 1.3.6.1.4.1.2011.6.164.1.2.2.1.1.5 | OCTET STRING (SIZE (0..63)) | RO | V100R002C01B104SP04 | |||||||||||||||||
column · OCTET STRING (SIZE (0..63)) · read-only · current Monitor software version. It is of the character string type. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwMonEquipPcbVersion | 1.3.6.1.4.1.2011.6.164.1.2.2.1.1.6 | OCTET STRING (SIZE (0..63)) | RO | ||||||||||||||||||
column · OCTET STRING (SIZE (0..63)) · read-only · current Monitor printed circuit board (PCB) hardware version. It is of the character string type. | |||||||||||||||||||||
| ChwMonEquipManufacturer | 1.3.6.1.4.1.2011.6.164.1.2.2.1.1.7 | OCTET STRING (SIZE (0..63)) | RO | HUAWEI | |||||||||||||||||
column · OCTET STRING (SIZE (0..63)) · read-only · current Monitor manufacture. It is of the character string type, and is an inherent attribute of the device. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwMonEquipManuDate | 1.3.6.1.4.1.2011.6.164.1.2.2.1.1.8 | OCTET STRING (SIZE (0..127)) | RO | ||||||||||||||||||
column · OCTET STRING (SIZE (0..127)) · read-only · current Monitor production date. It is of the character string type, and is an inherent attribute of the device. | |||||||||||||||||||||
| ChwMonEquipSerialNo | 1.3.6.1.4.1.2011.6.164.1.2.2.1.1.9 | OCTET STRING (SIZE (0..127)) | RO | ||||||||||||||||||
column · OCTET STRING (SIZE (0..127)) · read-only · current Production SN of the monitor. It is the electronic tag of the products. | |||||||||||||||||||||
| ChwMonEquipOperTotalTime | 1.3.6.1.4.1.2011.6.164.1.2.2.1.1.10 | Unsigned32 (0..65536) | RO | ||||||||||||||||||
column · Unsigned32 (0..65536) · read-only · current Total monitor runtime. The monitor counts the data in real time. The value is an integer (.0), and unit is hour (h). It is used for performance measurement and evaluation of the monitor.
| |||||||||||||||||||||
| ChwSetMonEquipCtrlState | 1.3.6.1.4.1.2011.6.164.1.2.2.1.1.11 | INTEGER | RW | autoMode(2) | |||||||||||||||||
column · INTEGER · read-write · current Monitor control status. It is an enumeration type: If the enumeration value is 1, it indicates the background control; If the enumeration value is 2, it indicates the automatic control. In manual state, monitor works under background commands; while monitors runs well automatically in auto state. For details, see the corresponding user manual of the monitor.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwCtrlMonEquipReset | 1.3.6.1.4.1.2011.6.164.1.2.2.1.1.12 | INTEGER | RW | reset(2) | |||||||||||||||||
column · INTEGER · read-write · current Warm-reset control of the monitor. It is an enumeration type: If the network management system (NMS) notifies the SNMP agent that this node is set to 1, it indicates that the reset of the monitor is not triggered; If the NMS notifies the SNMP agent that this node is set to 2, it indicates that the background starts the reset of the monitor.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwMonitorOperStatus | 1.3.6.1.4.1.2011.6.164.1.2.2.1.1.99 | INTEGER | RO | other(255) | |||||||||||||||||
column · INTEGER · read-only · current State of the site monitor module. It is an enumeration type: If the enumeration value is 1, it indicates that the site monitor module is in the normal state; If the enumeration value is 2, it indicates that the monitor module RS485 port communication failed; If the enumeration value is 3, it indicates that the monitor module net port communication failed; If the enumeration value is 4, it indicates that a fault occurs on the monitor module; If the enumeration value is 254, it indicates monitor module alarm resume; If the enumeration value is 255, it indicates monitor module operation status unknown.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwMonRowStatus | 1.3.6.1.4.1.2011.6.164.1.2.2.1.1.100 | RowStatus | RC | 1 | |||||||||||||||||
column · RowStatus · read-create · current RowStatus of site monitor. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NhwSiteRectifiers | 1.3.6.1.4.1.2011.6.164.1.3 | ||||||||||||||||||||
| NhwRectsGroup | 1.3.6.1.4.1.2011.6.164.1.3.1 | ||||||||||||||||||||
| ShwRectsGroupId | 1.3.6.1.4.1.2011.6.164.1.3.1.1 | Unsigned32 | RO | 2000 | |||||||||||||||||
scalar · Unsigned32 · read-only · current Device group ID of the rectifier module. It is the unique ID of the rectifier module group, and its default value: 002,000. The first digits indicate the device type and the last three digits indicate the device SN. If the last three digits are 000, it indicates a virtual device. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwRectsGroupName | 1.3.6.1.4.1.2011.6.164.1.3.1.2 | OCTET STRING (SIZE (0..63)) | RW | Rectifier Group | |||||||||||||||||
scalar · OCTET STRING (SIZE (0..63)) · read-write · current Name of the rectifier module group, character string type, is used to specify the rectifier module group. Users can configure it. Otherwise, the configured character can not be any other languages except English. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwRectsTotalCurrent | 1.3.6.1.4.1.2011.6.164.1.3.1.3 | Unsigned32 (0..500000) | RO | 7 | |||||||||||||||||
scalar · Unsigned32 (0..500000) · read-only · current Total current of the rectifier module group on the site. It indicates the real-time statistics of the rectifier module group on the site. unit: A, and the value is accurate to one decimal place (.1).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwRectsTotalQuantity | 1.3.6.1.4.1.2011.6.164.1.3.1.4 | Unsigned32 (0..256) | RO | 2 | |||||||||||||||||
scalar · Unsigned32 (0..256) · read-only · current Total quantity of the rectifier modules. Value range: 0 to 256.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwRectsRatedVoltage | 1.3.6.1.4.1.2011.6.164.1.3.1.5 | Unsigned32 (420..580) | RO | 535 | |||||||||||||||||
scalar · Unsigned32 (420..580) · read-only · current Rated voltage of the rectifier module group. It is an inherent attribute. Value range: 42 to 58, Unit: V, and the value is accurate to one decimal place (.1).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwModifyRectsOutputVoltage | 1.3.6.1.4.1.2011.6.164.1.3.1.6 | Unsigned32 (420..580) | RW | 532 | |||||||||||||||||
scalar · Unsigned32 (420..580) · read-write · current Voltage adjustment of the rectifier module, which users can configure it. Value range: 42 to 58, Unit: V, and the value is accurate to one decimal space (.1). Based on the actual requirements, users can modify the output voltage of the rectifier module by modifying the value of the node. NOTES: Be cautious about changing the value of the node.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwSetRectsRedundEnable | 1.3.6.1.4.1.2011.6.164.1.3.1.7 | INTEGER | RW | disable(1) | |||||||||||||||||
scalar · INTEGER · read-write · current Sleep function of the rectifier module group on the site. It is an enumeration value: If the NMS notifies the SNMP agent that this node is set to 1, it means to disable the sleep function of the rectifier module group; If the NMS notifies the SNMP agent that this node is set to 2, it means to enable the sleep function of the rectifier module group. If NMS get the node value is 3, it indicates that this function is not support, and in such case the value set to the agent is invalid. Default value: to disable the sleep function of the rectifier module group. For details, see the corresponding user manual of the monitor.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwCtrlRectsAllOnOff | 1.3.6.1.4.1.2011.6.164.1.3.1.8 | INTEGER | RW | on(1) | |||||||||||||||||
scalar · INTEGER · read-write · current Power-on or power-off of the rectifier module group (all the rectifier modules) on the site. It is an enumeration value: If the NMS notifies the SNMP agent that this node is set to 1, it indicates power-on of all rectifier modules; If the NMS notifies the SNMP agent that this node is set to 2, it indicates power-off of all the rectifier modules.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NhwRectifier | 1.3.6.1.4.1.2011.6.164.1.3.2 | ||||||||||||||||||||
| ThwRectConfigTable | 1.3.6.1.4.1.2011.6.164.1.3.2.1 | NA | |||||||||||||||||||
table · not-accessible · current Rectifier config information table. Use this table to get rectifiers equipment ID, software version, manufacturer, rated current, efficency, AC input type, and to control equipment on or off. This table's index is hwRectConfigIndex, clone Rectifier config information table. | |||||||||||||||||||||
| RhwRectConfigEntry | 1.3.6.1.4.1.2011.6.164.1.3.2.1.1 | NA | |||||||||||||||||||
| ChwRectConfigIndex | 1.3.6.1.4.1.2011.6.164.1.3.2.1.1.1 | Integer32 (1..256) | RO | 28676 | |||||||||||||||||
column · Integer32 (1..256) · read-only · current Index of the device configuration list for the rectifier modules, which value range: 1 to 256. Lines of the device list are restricted by the total quantity of the rectifier modules (hwRectTotleQuantity). Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwRectEquipId | 1.3.6.1.4.1.2011.6.164.1.3.2.1.1.2 | Unsigned32 (2001..2255) | RO | 2002 | |||||||||||||||||
column · Unsigned32 (2001..2255) · read-only · current Rectifier module ID. Value range: 002'001 to 002'255. The first digits indicate the device type and last three digits indicate the device SN. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwRectEquipName | 1.3.6.1.4.1.2011.6.164.1.3.2.1.1.3 | OCTET STRING (SIZE (0..63)) | RW | Rectifier2 | |||||||||||||||||
column · OCTET STRING (SIZE (0..63)) · read-write · current Device name of the rectifier module, character string type, is used to specify the rectifier module. Users can configure it. Otherwise, the configured character can not be any other languages except English. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwRectType | 1.3.6.1.4.1.2011.6.164.1.3.2.1.1.4 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current Specific type of the rectifier module. It is an enumeration type: If the enumeration value is 1, it indicates a 5A rectifier module; If the enumeration value is 2, it indicates a 15A rectifier module; If the enumeration value is 3, it indicates a 30A rectifier module; If the enumeration value is 4, it indicates a 50A rectifier module; If the enumeration value is 5, it indicates a 100A rectifier module.
| |||||||||||||||||||||
| ChwRectSoftwareVersion | 1.3.6.1.4.1.2011.6.164.1.3.2.1.1.5 | OCTET STRING (SIZE (0..63)) | RO | V104 | |||||||||||||||||
column · OCTET STRING (SIZE (0..63)) · read-only · current Software version of the rectifier module. It indicates the software version ID of the module. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwRectManufacturer | 1.3.6.1.4.1.2011.6.164.1.3.2.1.1.6 | OCTET STRING (SIZE (0..63)) | RO | ||||||||||||||||||
column · OCTET STRING (SIZE (0..63)) · read-only · current Manufacture of the rectifier module. | |||||||||||||||||||||
| ChwRectManuDate | 1.3.6.1.4.1.2011.6.164.1.3.2.1.1.7 | OCTET STRING (SIZE (0..127)) | RO | ||||||||||||||||||
column · OCTET STRING (SIZE (0..127)) · read-only · current Manufacture date of rectifiers is of string type. | |||||||||||||||||||||
| ChwRectSerialNo | 1.3.6.1.4.1.2011.6.164.1.3.2.1.1.8 | OCTET STRING (SIZE (0..127)) | RO | 2102311KEMBTJ7000002 | |||||||||||||||||
column · OCTET STRING (SIZE (0..127)) · read-only · current Rectifier module SN. It indicates the electronic tag of the product. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwRectRatedCurrent | 1.3.6.1.4.1.2011.6.164.1.3.2.1.1.9 | Unsigned32 (0..1000) | RO | 345 | |||||||||||||||||
column · Unsigned32 (0..1000) · read-only · current Rated voltage of the rectifier module, is an inherent attribute. Value range: 0 to 100, Unit: A, and the value is accurate to one decimal place (.1).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwRectEfficency | 1.3.6.1.4.1.2011.6.164.1.3.2.1.1.10 | Unsigned32 (800..1000) | RO | 860 | |||||||||||||||||
column · Unsigned32 (800..1000) · read-only · current Efficiency of the rectifier module, is an inherent attribute. Value range: 80 to 100, Unit: %, and the value is accurate to one decimal place (.1).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwRectInputAcType | 1.3.6.1.4.1.2011.6.164.1.3.2.1.1.11 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current Input AC type of the rectifier module. It is an enumeration value: If the value of the node is 1, it indicates single-phase AC input; If the value of the node is 2, it indicates three-phase AC input.
| |||||||||||||||||||||
| ChwCtrlRectOnOff | 1.3.6.1.4.1.2011.6.164.1.3.2.1.1.12 | INTEGER | RW | on(1) | |||||||||||||||||
column · INTEGER · read-write · current Power-on or power-off of the rectifier module, is an enumeration value. Users can modify the enumeration value of this node, thus controlling of the power-on or power-off of the rectifier module: If the NMS notifies the SNMP agent that this node is set to 1, it indicates power-on of the rectifier module; If the NMS notifies the SNMP agent that this node is set to 2, it indicates power-off of the rectifier module.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwRectConfigRowStatus | 1.3.6.1.4.1.2011.6.164.1.3.2.1.1.100 | RowStatus | RC | 1 | |||||||||||||||||
column · RowStatus · read-create · current RowStatus of rectifier config table. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ThwRectOperTable | 1.3.6.1.4.1.2011.6.164.1.3.2.2 | NA | |||||||||||||||||||
table · not-accessible · current Rectifier runing information table. Use this table to get rectifiers output current, output voltage, totle runing time, and current run status. This table's index is hwRectRunIndex, clone rectifier runing information table. | |||||||||||||||||||||
| RhwRectOperEntry | 1.3.6.1.4.1.2011.6.164.1.3.2.2.1 | NA | |||||||||||||||||||
| ChwRectOperIndex | 1.3.6.1.4.1.2011.6.164.1.3.2.2.1.1 | Integer32 (1..256) | RO | 28676 | |||||||||||||||||
column · Integer32 (1..256) · read-only · current Table index of the running rectifier modules, which value range: 1 to 256. Lines of the device list are restricted by the total quantity of the rectifier modules (hwRectTotleQuantity). Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwRectOutputCurrent | 1.3.6.1.4.1.2011.6.164.1.3.2.2.1.2 | Unsigned32 (0..2000) | RO | 13 | |||||||||||||||||
column · Unsigned32 (0..2000) · read-only · current Output current of the rectifier module. It is a real-time analog parameter. Value range: 0 to 200, Unit: A, and the value is accurate to one decimal place (.1). Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwRectOutputVoltage | 1.3.6.1.4.1.2011.6.164.1.3.2.2.1.3 | Unsigned32 (0..600) | RO | 535 | |||||||||||||||||
column · Unsigned32 (0..600) · read-only · current Output voltage of the rectifier module. It is a real-time analog parameter. Value range: 0 to 60, Unit: V, the value is accurate to one decimal place (.1).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwRectTotalOperTime | 1.3.6.1.4.1.2011.6.164.1.3.2.2.1.4 | Unsigned32 | RO | ||||||||||||||||||
column · Unsigned32 · read-only · current Total runtime of the rectifier module. Value unit: minute (m), and the value is an integer (.0).
| |||||||||||||||||||||
| ChwRectOperStatus | 1.3.6.1.4.1.2011.6.164.1.3.2.2.1.99 | INTEGER | RO | normal(1) | |||||||||||||||||
column · INTEGER · read-only · current State of the rectifier module. It is an enumeration type: If the enumeration value is 1, it indicates that the rectifier module is in the normal state; If the enumeration value is 2, it indicates that a fault occurs on the rectifier module; If the enumeration value is 3, it indicates the automatic protection of the rectifier module; If the enumeration value is 4, it indicates that communication of the rectifier module fails; If the enumeration value is 5, it indicates that the rectifier module is shut down; If the enumeration value is 6, it indicates that the rectifier module is invalid; If the enumeration value is 7, it indicates that this rectifier is not configured; If the enumeration value is 254, it indicates rectifier alarm resume; If the enumeration value is 255, it indicates rectifier operation status unknown.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwRectOperRowStatus | 1.3.6.1.4.1.2011.6.164.1.3.2.2.1.100 | RowStatus | RC | 1 | |||||||||||||||||
column · RowStatus · read-create · current RowStatus of rectifier runing table. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NhwSiteBatterys | 1.3.6.1.4.1.2011.6.164.1.4 | ||||||||||||||||||||
| NhwBattsConfig | 1.3.6.1.4.1.2011.6.164.1.4.1 | ||||||||||||||||||||
| ShwBattsGroupId | 1.3.6.1.4.1.2011.6.164.1.4.1.1 | Unsigned32 | RO | 3000 | |||||||||||||||||
scalar · Unsigned32 · read-only · current Battery group ID. It is the unique ID of the battery group device. The first digits indicate the device type and the last three digits indicate the device SN. If the last three digits are 000, it indicates a virtual device. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwBattsGroupName | 1.3.6.1.4.1.2011.6.164.1.4.1.2 | OCTET STRING (SIZE (0..63)) | RW | Battery Group | |||||||||||||||||
scalar · OCTET STRING (SIZE (0..63)) · read-write · current Device name of the battery group. It is of the character string type, which can be configured by users. Otherwise, the configured character can not be any other languages except English. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwBattsTotalQuantity | 1.3.6.1.4.1.2011.6.164.1.4.1.3 | Unsigned32 (0..100) | RW | 2 | |||||||||||||||||
scalar · Unsigned32 (0..100) · read-write · current Total quantity of battery strings, which value range: 0 to 100.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwSetBattsHighTempAction | 1.3.6.1.4.1.2011.6.164.1.4.1.4 | INTEGER | RW | lowerDcOutput(2) | |||||||||||||||||
scalar · INTEGER · read-write · current Battery high-temperature protection mode. It is an enumeration value, and can be configured. If the enumeration value is 1, it indicates the power-off protection mode; If the enumeration value is 2, it indicates the protection mode of lowering the output voltage of the rectifier module. unknown(255) it is do nothing
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwSetBattsHighTempVoltLimit | 1.3.6.1.4.1.2011.6.164.1.4.1.5 | Unsigned32 (0..600) | RW | 515 | |||||||||||||||||
scalar · Unsigned32 (0..600) · read-write · current Battery protection voltage under high temperature. It works with the low-voltage power-off protection in battery high-temperature protection mode, which can be configured by users. If the low-voltage power-off protection mode (that is, the enumeration value is 1) is selected, the node is a low-voltage power-off node. Value range: 0 to 60, unit: V, and the value is accurate to one decimal place (.1).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwSetBattsHTDLimit | 1.3.6.1.4.1.2011.6.164.1.4.1.6 | Integer32 (0..100) | RW | 53 | |||||||||||||||||
scalar · Integer32 (0..100) · read-write · current Upper threshold of the battery high temperature disconnection(HTD), can be configured by users. Value range: 0 to 100, Unit: centigrade (°„C), and the value is an integer (.0). Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwSetBattsHTDEnable | 1.3.6.1.4.1.2011.6.164.1.4.1.7 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current Battery high temperature disconnection enable. It is an enumeration type: If the enumeration value is 1, enable the operation of the battery disconnection in high temperature; If the enumeration value is 2, disable the operation of the battery disconnection in high temperature. The operation of the battery disconnection in high temperature is disabled by default.
| |||||||||||||||||||||
| ShwSetBattsFloatVoltage | 1.3.6.1.4.1.2011.6.164.1.4.1.8 | Unsigned32 (420..580) | RW | 535 | |||||||||||||||||
scalar · Unsigned32 (420..580) · read-write · current Float charge voltage of the batteries, can be configured by users. Value range: 42 to 58, unit: V, and the value is accurate to one decimal place (.1)
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwSetBattsBoostVoltage | 1.3.6.1.4.1.2011.6.164.1.4.1.9 | Unsigned32 (420..580) | RW | 564 | |||||||||||||||||
scalar · Unsigned32 (420..580) · read-write · current Boostcharge voltage of the batteries, can be configured by users. Value range: 42 to 58, unit: V, and the value is accurate to one decimal place (.1).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwSetBattsCurrLimitCoefficient | 1.3.6.1.4.1.2011.6.164.1.4.1.10 | Unsigned32 (5..25) | RW | 15 | |||||||||||||||||
scalar · Unsigned32 (5..25) · read-write · current Current-limiting point coefficient of the batteries, can be configured by users. Value range: 0.05 to 0.25, unit: C10, and the value is accurate to two decimal places (.2).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwSetBattsCompFactor | 1.3.6.1.4.1.2011.6.164.1.4.1.11 | Unsigned32 (0..500) | RW | 80 | |||||||||||||||||
scalar · Unsigned32 (0..500) · read-write · current Temperature compensated coefficient of the batteries, can be configured by user. Value range: 0 to 500, unit: mv per centigrade, and the value is an integer (.0).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwCtrlBattsBoostFloat | 1.3.6.1.4.1.2011.6.164.1.4.1.12 | INTEGER | RW | floatCharge(1) | |||||||||||||||||
scalar · INTEGER · read-write · current Control batteries charge mode between boost and float. It is an enumeration value. Users actively control the conversion. If the NMS notifies the SNMP agent that this node is set to 1, it means to start the float charge mode of the batteries; If the NMS notifies the SNMP agent that this node is set to 2, it means to start the boost charge mode of the batteries.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NhwBattsOperate | 1.3.6.1.4.1.2011.6.164.1.4.2 | ||||||||||||||||||||
| ShwBattsTotalCurrent | 1.3.6.1.4.1.2011.6.164.1.4.2.1 | Integer32 (-10000..10000) | RO | 0 | |||||||||||||||||
scalar · Integer32 (-10000..10000) · read-only · current Total current of the battery group. It indicates the real-time statistics of the battery group on the site. Value range: -1000 to +1000, unit: A, and the value is accurate to one decimal place (.1).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwBattsPreDischargeTime | 1.3.6.1.4.1.2011.6.164.1.4.2.2 | Unsigned32 (0..65536) | RO | 240 | |||||||||||||||||
scalar · Unsigned32 (0..65536) · read-only · current Battery group backup time. It indicates the real-time statistics of the battery group. Value range: 0 to 65536, Unit: minute (m), and the value is an integer (.0).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwBattsChargeStatus | 1.3.6.1.4.1.2011.6.164.1.4.2.3 | INTEGER | RO | floatCharge(1) | |||||||||||||||||
scalar · INTEGER · read-only · current Battery charging state, indicates the charging and discharging information about the battery group. It is an enumeration type. If the enumeration value is 1, it indicates a battery group in the float charging state. If the enumeration value is 2, it indicates a battery group in the boost charging state. If the enumeration value is 3, it indicates a battery group in the discharging state.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwBattsCurrLimitStatus | 1.3.6.1.4.1.2011.6.164.1.4.2.4 | INTEGER | RO | unlimit(1) | |||||||||||||||||
scalar · INTEGER · read-only · current Battery group current-limiting state, indicates the state information about the battery group. It is an enumeration value. If the enumeration value is 1, it indicates that the current of the battery group is not limited. If the enumeration value is 2, it indicates the current of the battery group is limited.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NhwBattsTest | 1.3.6.1.4.1.2011.6.164.1.4.3 | ||||||||||||||||||||
| ShwBattsTestRecordCount | 1.3.6.1.4.1.2011.6.164.1.4.3.1 | Unsigned32 (0..100) | RO | ||||||||||||||||||
scalar · Unsigned32 (0..100) · read-only · current Battery test records number. | |||||||||||||||||||||
| ShwSetBattsManuStdTestTime | 1.3.6.1.4.1.2011.6.164.1.4.3.2 | Unsigned32 (1..100) | RW | 480 | |||||||||||||||||
scalar · Unsigned32 (1..100) · read-write · current Battery standard test time, It can be configured by users, and its value is an integer (.0). Here, if battery manual test is standard mode, value range defines between 1 to 6000, unit: minutes(m)
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwSetBattsManuStdTestEndVolt | 1.3.6.1.4.1.2011.6.164.1.4.3.3 | Unsigned32 (170..220) | RW | ||||||||||||||||||
scalar · Unsigned32 (170..220) · read-write · current Voltage when the battery test is ended, can be configured by users. Unit: V/cell, and the value is accurate to two decimal place (.2). Here, if battery manual test is standard mode, value range defines between 1.7 to 2.2
| |||||||||||||||||||||
| ShwSetBattsManuStdTestCellNum | 1.3.6.1.4.1.2011.6.164.1.4.3.4 | Unsigned32 (1..50) | RW | ||||||||||||||||||
scalar · Unsigned32 (1..50) · read-write · current Battery cell number in each Group, which is used in the battery standard manual test, can be configured by users. Unit: psc or cell, value range defines between 1 to 50. and the value is accurate to one decimal place (.0).
| |||||||||||||||||||||
| ShwSetBattsManuShortTestTime | 1.3.6.1.4.1.2011.6.164.1.4.3.5 | Unsigned32 (1..240) | RW | 5 | |||||||||||||||||
scalar · Unsigned32 (1..240) · read-write · current Battery short test time, It can be configured by users, and its value is an integer (.0). If battery manual test is simple mode, value range defines between 1 to 240, unit: minutes(m)
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwSetBattsManuShortTestEndVolt | 1.3.6.1.4.1.2011.6.164.1.4.3.6 | Unsigned32 (400..540) | RW | 450 | |||||||||||||||||
scalar · Unsigned32 (400..540) · read-write · current Voltage when the battery short test is ended, can be configured by users. Unit: V, and the value is accurate to one decimal place (.1). Here, if battery manual test is standard mode, value range defines between 40 to 54.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwCtrlBattsTestStartStop | 1.3.6.1.4.1.2011.6.164.1.4.3.7 | INTEGER | RW | testStop(3) | |||||||||||||||||
scalar · INTEGER · read-write · current Battery manualtest start and stop. It is an enumeration value.
If the NMS notifies the SNMP agent that the node is set to 1, it means to start a standard manual test;
If the NMS notifies the SNMP agent that the node is set to 2, it means to start a short manual test;
If the NMS notifies the SNMP agent that the node is set to 3, it means to stop the battery test.
Set the parameters, such as battery test time, and voltage when the battery test stops before the node controls the start of the battery test. If the parameters are not set this time, the system uses the configuration parameters by default; and if the battery test is started at the first time, the system uses the default value.
Battery test can only start up in some conditions, so that the reason of Start of battery short test failed may be as follow:
1. Interval between this test and the latest AC outage or test is longer than the preset duration.
2. No major alarm is raised.
3. The number of healthy modules is greater than 0.
4. The number of battery strings is greater than 0.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ThwBattsTestResultTable | 1.3.6.1.4.1.2011.6.164.1.4.3.100 | NA | |||||||||||||||||||
table · not-accessible · current Battery test result record table. Use this table to get battery test inital time, test result, battery efficiency, battery discharge time, terminated voltage, average current, discharge AH value, test temperature and test terminated course. This table's index is hwBattsTestResultIndex, clone Battery test result record table. | |||||||||||||||||||||
| RhwBattsTestResultEntry | 1.3.6.1.4.1.2011.6.164.1.4.3.100.1 | NA | |||||||||||||||||||
| ChwBattsTestResultIndex | 1.3.6.1.4.1.2011.6.164.1.4.3.100.1.1 | Integer32 (1..100) | RO | ||||||||||||||||||
column · Integer32 (1..100) · read-only · current Table index of the battery test results. Currently up to 10 times of the battery test results are saved by default. | |||||||||||||||||||||
| ChwBattsTestType | 1.3.6.1.4.1.2011.6.164.1.4.3.100.1.2 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current Record test type of the battery test. It is an enumeration value: If the NMS notifies the SNMP agent that this node is set to 1, it indicates a manual test; If the NMS notifies the SNMP agent that this node is set to 2, it indicates a simplified test; If the NMS notifies the SNMP agent that this node is set to 3, it indicates a timed test; If the NMS notifies the SNMP agent that this node is set to 4, it indicates a short test; If the NMS notifies the SNMP agent that this node is set to 255, it indicates a other test.
| |||||||||||||||||||||
| ChwBattsTestStartTime | 1.3.6.1.4.1.2011.6.164.1.4.3.100.1.3 | OCTET STRING (SIZE (0..127)) | RO | ||||||||||||||||||
column · OCTET STRING (SIZE (0..127)) · read-only · current Test start time of the record in the battery test. It is of the character string type. | |||||||||||||||||||||
| ChwBattsTestResult | 1.3.6.1.4.1.2011.6.164.1.4.3.100.1.4 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current Battery test result. It is an enumeration value. If the enumeration value of the node is 1, it indicates that the battery test has no result: If the enumeration value of the node is 2, it indicates that the battery is in the normal state: If the enumeration value of the node is 3, it indicates that the battery is in the minor abnormal state, If the enumeration value of the node is 4, it indicates that the battery is in the alarm state, If the enumeration value of the node is 255, it indicates that the battery state is unknown,
| |||||||||||||||||||||
| ChwBattsEfficiency | 1.3.6.1.4.1.2011.6.164.1.4.3.100.1.5 | Integer32 (0..100) | RO | ||||||||||||||||||
column · Integer32 (0..100) · read-only · current Battery efficiency test. Value range: 0 to 100, Unit: %, and the value is an integer (.0). If the value is -1, it indicates that the test value is inefficient.
| |||||||||||||||||||||
| ChwBattsDischargeTime | 1.3.6.1.4.1.2011.6.164.1.4.3.100.1.6 | Unsigned32 (0..10000) | RO | ||||||||||||||||||
column · Unsigned32 (0..10000) · read-only · current Discharge time of the battery test records. Value range: 0 to 100, unit: hour (h), and the value is accurate to two decimal places (.2).
| |||||||||||||||||||||
| ChwBattsDischargeEndVoltage | 1.3.6.1.4.1.2011.6.164.1.4.3.100.1.7 | Unsigned32 (0..600) | RO | ||||||||||||||||||
column · Unsigned32 (0..600) · read-only · current Discharge termination voltage of the battery test. Value range: 0 to 60, unit: V, and the value is accurate to one decimal place (.1).
| |||||||||||||||||||||
| ChwBattsDischargeAvCurrent | 1.3.6.1.4.1.2011.6.164.1.4.3.100.1.8 | Integer32 (-10000..10000) | RO | ||||||||||||||||||
column · Integer32 (-10000..10000) · read-only · current Average discharge current of the battery test. Value range: -10000 to 10000, unit: A, and the value is accurate to one decimal place (.1).
| |||||||||||||||||||||
| ChwBattsDischargeAhValue | 1.3.6.1.4.1.2011.6.164.1.4.3.100.1.9 | Unsigned32 (0..5000) | RO | ||||||||||||||||||
column · Unsigned32 (0..5000) · read-only · current Discharge ampere per hour the battery test. Value range: 0 to 5000, Unit: Ah, and the value is an integer (.0).
| |||||||||||||||||||||
| ChwBattsTestTemprature | 1.3.6.1.4.1.2011.6.164.1.4.3.100.1.10 | Integer32 (-50..100) | RO | ||||||||||||||||||
column · Integer32 (-50..100) · read-only · current Battery temperature of the battery test termination. Value range: -50 to +100, Unit: centigrade (°„C), and the value is an integer (.0). If the value is -1024, it indicates that no battery temperature value sensor is detected.
| |||||||||||||||||||||
| ChwBattsTestEndCourse | 1.3.6.1.4.1.2011.6.164.1.4.3.100.1.11 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current Termination factors of the battery test. It is an enumeration value. If the enumeration value is 1, it indicates that the voltage value of the battery test reaches the set termination voltage; If the enumeration value is 2, it indicates that the voltage value of the battery test reaches the timing limit; If the enumeration value is 3, it indicates that an alarm related to the battery leads to the stop of the battery test; If the enumeration value is 4, it indicates that a battery test is stopped manually, If the enumeration value is 5, it indicates that battery fault alarm happened, If the enumeration value is 255, it indicates that battery test end for other courses.
| |||||||||||||||||||||
| ChwBattsTestResultRowStatus | 1.3.6.1.4.1.2011.6.164.1.4.3.100.1.100 | RowStatus | RC | ||||||||||||||||||
column · RowStatus · read-create · current RowStatus of battery test table. | |||||||||||||||||||||
| NhwBattString | 1.3.6.1.4.1.2011.6.164.1.4.4 | ||||||||||||||||||||
| ThwBattStringConfigTable | 1.3.6.1.4.1.2011.6.164.1.4.4.1 | NA | |||||||||||||||||||
table · not-accessible · current Battery string config table. Use this table to get battery string equipment ID and equipment name, to set battery standard capacity and battery install time as well. This table's index is hwBattStringConfigIndex, clone battery string config table. | |||||||||||||||||||||
| RhwBattStringConfigEntry | 1.3.6.1.4.1.2011.6.164.1.4.4.1.1 | NA | |||||||||||||||||||
| ChwBattStringConfigIndex | 1.3.6.1.4.1.2011.6.164.1.4.4.1.1.1 | Integer32 (1..100) | RO | 5 | |||||||||||||||||
column · Integer32 (1..100) · read-only · current Device table index of the battery string, which value range: 1 to 100. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwBattStringEquipId | 1.3.6.1.4.1.2011.6.164.1.4.4.1.1.2 | Unsigned32 (3001..3100) | RO | 3001 | |||||||||||||||||
column · Unsigned32 (3001..3100) · read-only · current Batteries device ID, can be configured by users. Value range: 003,001 to 003,100, in which the first three digits specify the device type and the last three specify the device SN. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwBattStringEquipName | 1.3.6.1.4.1.2011.6.164.1.4.4.1.1.3 | OCTET STRING (SIZE (0..63)) | RW | Battery String1 | |||||||||||||||||
column · OCTET STRING (SIZE (0..63)) · read-write · current Batteries device name, of the character string type, is used to specify the batteries. Users can configure it. Otherwise, the configured character can not be any other languages except English. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwSetBattsTempUpperLimit | 1.3.6.1.4.1.2011.6.164.1.4.4.1.1.4 | Integer32 (-50..100) | RW | 50 | |||||||||||||||||
column · Integer32 (-50..100) · read-write · current Upper threshold of the battery temperature alarm, can be configured by users. Value range: -50 to 100, Unit: centigrade (°„C), and the value is an integer (.0).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwSetBattsTempLowerLimit | 1.3.6.1.4.1.2011.6.164.1.4.4.1.1.5 | Integer32 (-50..100) | RW | -10 | |||||||||||||||||
column · Integer32 (-50..100) · read-write · current Lower threshold of the battery temperature alarm, can be configured by users. Value range: -50 to 100, Unit: centigrade (°„C), and the value is an integer (.0).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwSetBattsTempMeasureUpperLimit | 1.3.6.1.4.1.2011.6.164.1.4.4.1.1.6 | Integer32 (0..100) | RW | ||||||||||||||||||
column · Integer32 (0..100) · read-write · current Upper threshold of the battery temperature measurement, can be configured by users. Value range: 0 to 100, Unit: centigrade (°„C), and the value is an integer (.0).
| |||||||||||||||||||||
| ChwSetBattsTempMeasureLowerLimit | 1.3.6.1.4.1.2011.6.164.1.4.4.1.1.7 | Integer32 (-50..0) | RW | ||||||||||||||||||
column · Integer32 (-50..0) · read-write · current Lower threshold of the battery temperature measurement, can be configured by users. Value range: -50 to 0, Unit: centigrade (°„C), and the value is an integer (.0).
| |||||||||||||||||||||
| ChwSetBattStdCapacity | 1.3.6.1.4.1.2011.6.164.1.4.4.1.1.8 | Integer32 (0..10000) | RW | 18 | |||||||||||||||||
column · Integer32 (0..10000) · read-write · current Set battery standard capacity, is an inherent attribute of the device. Value range: 0 to 10000, unit: Ah, the value is an integer (.0).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwSetBattInstallTime | 1.3.6.1.4.1.2011.6.164.1.4.4.1.1.9 | OCTET STRING (SIZE (0..128)) | RW | ||||||||||||||||||
column · OCTET STRING (SIZE (0..128)) · read-write · current Set battery install time, of the character string type, can be configured by users. Otherwise, the configured character can not be any other languages except English. | |||||||||||||||||||||
| ChwBattStringConfigRowStatus | 1.3.6.1.4.1.2011.6.164.1.4.4.1.1.100 | RowStatus | RC | 1 | |||||||||||||||||
column · RowStatus · read-create · current RowStatus of battery string config table. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ThwBattStringOperTable | 1.3.6.1.4.1.2011.6.164.1.4.4.2 | NA | |||||||||||||||||||
table · not-accessible · current Battery string runing table. Use this table to get battery string current, persent of remain capacity, battery remain capacity, battery actual capacity, as well as battery temperature. This table's index is hwBattStringRunIndex, clone battery string runing table. | |||||||||||||||||||||
| RhwBattStringOperEntry | 1.3.6.1.4.1.2011.6.164.1.4.4.2.1 | NA | |||||||||||||||||||
| ChwBattStringOperIndex | 1.3.6.1.4.1.2011.6.164.1.4.4.2.1.1 | Integer32 (1..100) | RO | 5 | |||||||||||||||||
column · Integer32 (1..100) · read-only · current Device table index of the battery string, which value range: 1 to 100. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwBattStringCurrent | 1.3.6.1.4.1.2011.6.164.1.4.4.2.1.2 | Integer32 (-10000..10000) | RO | 0 | |||||||||||||||||
column · Integer32 (-10000..10000) · read-only · current Batteries current. It is an analog parameter collected by the battery string in real time. Value range: -1000 to +1000, unit: A, and the value is accurate to one decimal place (.1).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwBattStringRemainCapacityPercent | 1.3.6.1.4.1.2011.6.164.1.4.4.2.1.3 | Unsigned32 (0..1000) | RO | 1000 | |||||||||||||||||
column · Unsigned32 (0..1000) · read-only · current Remaining capacity percentage of the battery string. Value range: 0 to 100, unit: %, and the value is accurate to one decimal place (.1).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwBattStringRemainCapacity | 1.3.6.1.4.1.2011.6.164.1.4.4.2.1.4 | Unsigned32 (0..5000) | RO | 18 | |||||||||||||||||
column · Unsigned32 (0..5000) · read-only · current Remaining capacity of the battery string. It is an analog parameter collected by the battery string in real time. Value range: 0 to 5000, unit: Ah, and the value is an integer (.0).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwBattStringActualCapacity | 1.3.6.1.4.1.2011.6.164.1.4.4.2.1.5 | Unsigned32 (0..5000) | RO | ||||||||||||||||||
column · Unsigned32 (0..5000) · read-only · current Batteries actual capacity. It is an analog parameter collected by the battery string in real time.Value range: 0 to 5000, unit: Ah, the value is an integer (.0).
| |||||||||||||||||||||
| ChwBattStringTemprature | 1.3.6.1.4.1.2011.6.164.1.4.4.2.1.6 | Integer32 (-500..1000) | RO | 2147483647 | |||||||||||||||||
column · Integer32 (-500..1000) · read-only · current Battery temperature. It is a battery parameter collected in real time. Value range: -50 to +100, unit: centigrade (°„C), and the value is an integer (.1). If the value is -99999, it indicates that battery temperature sensor is not configured.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwBattStringOperStatus | 1.3.6.1.4.1.2011.6.164.1.4.4.2.1.99 | INTEGER | RO | normal(1) | |||||||||||||||||
column · INTEGER · read-only · current State of the site battery string module. It is an enumeration type: If the enumeration value is 1, it indicates that the site battery string is in the normal state; If the enumeration value is 2, it indicates that the battery string is over upper alarm threshold of temperature; If the enumeration value is 3, it indicates that the battery string is under lower alarm threshold of temperature; If the enumeration value is 4, it indicates that battery string loop has disconnected; If the enumeration value is 5, it indicates that the current of batery is over upper charging threshold; If the enumeration value is 254, it indicates battery string alarm resume; If the enumeration value is 255, it indicates battery string operation status unknown.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwBattStringOperRowStatus | 1.3.6.1.4.1.2011.6.164.1.4.4.2.1.100 | RowStatus | RC | 1 | |||||||||||||||||
column · RowStatus · read-create · current RowStatus of battery string runing table. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NhwSiteAcDistributions | 1.3.6.1.4.1.2011.6.164.1.5 | ||||||||||||||||||||
| NhwAcDistributionsGroup | 1.3.6.1.4.1.2011.6.164.1.5.1 | ||||||||||||||||||||
| ShwAcsGroupId | 1.3.6.1.4.1.2011.6.164.1.5.1.1 | Unsigned32 | RO | 4000 | |||||||||||||||||
scalar · Unsigned32 · read-only · current AC group ID, is the unique ID of the AC group. The first three digits indicate the device type and the last three indicate the device SN. If the last three digits are 000, it indicates a virtual device. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwAcsGroupName | 1.3.6.1.4.1.2011.6.164.1.5.1.2 | OCTET STRING (SIZE (0..63)) | RW | AC Distribution Group | |||||||||||||||||
scalar · OCTET STRING (SIZE (0..63)) · read-write · current Device name of the AC group. It is of the character string type, and can be configured by users. Otherwise, the configured character can not be any other languages except English. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwAcsTotalCurrent | 1.3.6.1.4.1.2011.6.164.1.5.1.3 | Unsigned32 (0..10000) | RO | 8 | |||||||||||||||||
scalar · Unsigned32 (0..10000) · read-only · current Total current of the AC group. It indicates the real-time statistics of the AC group. Value range: 0 to 1000, unit: A, and the value is accurate to one decimal place (.1).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwAcsTotalQuantity | 1.3.6.1.4.1.2011.6.164.1.5.1.4 | Unsigned32 (0..100) | RO | 1 | |||||||||||||||||
scalar · Unsigned32 (0..100) · read-only · current Total quantity of the site ACUs. Value range: 0 to 100. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwSetAcsUpperVoltLimit | 1.3.6.1.4.1.2011.6.164.1.5.1.5 | Unsigned32 (60..500) | RW | 280 | |||||||||||||||||
scalar · Unsigned32 (60..500) · read-write · current Upper threshold of the AC voltage alarm, can be configured by users. Value range: 60 to 500, unit: V, and the value is an integer (.0).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwSetAcsLowerVoltLimit | 1.3.6.1.4.1.2011.6.164.1.5.1.6 | Unsigned32 (60..500) | RW | 180 | |||||||||||||||||
scalar · Unsigned32 (60..500) · read-write · current Lower threshold of the AC voltage alarm, can be configured by users. Value range: 60 to 500, unit: V, and the value is an integer (.0).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NhwAcDistribution | 1.3.6.1.4.1.2011.6.164.1.5.2 | ||||||||||||||||||||
| ThwAcInputTable | 1.3.6.1.4.1.2011.6.164.1.5.2.1 | NA | |||||||||||||||||||
table · not-accessible · current AC input table. Use this table to get AC distribution unit ID, AC distribution unit name, A phase or AB line voltage, B phase or BC line voltage, C phase or CA line voltage, AC input breaker status, as well as AC output breakers quantity, which defines hwAcOutputBreakerTable row number. This table's index is hwAcInputIndex, clone AC input table. | |||||||||||||||||||||
| RhwAcInputEntry | 1.3.6.1.4.1.2011.6.164.1.5.2.1.1 | NA | |||||||||||||||||||
| ChwAcInputIndex | 1.3.6.1.4.1.2011.6.164.1.5.2.1.1.1 | Integer32 (1..100) | RO | 1 | |||||||||||||||||
column · Integer32 (1..100) · read-only · current ACU device table index, which value range: 1 to 100. Lines of the device list are restricted by the total quantity of ACUs (hwAcsInputQuantity). Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwAcEquipId | 1.3.6.1.4.1.2011.6.164.1.5.2.1.1.2 | Unsigned32 (4001..4100) | RO | 4001 | |||||||||||||||||
column · Unsigned32 (4001..4100) · read-only · current ACU device ID, which users can configure. Value range: 004,001 to 004,100, in which The first digits indicate the device type and the last three digits indicate the device SN. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwAcEquipName | 1.3.6.1.4.1.2011.6.164.1.5.2.1.1.3 | OCTET STRING (SIZE (0..63)) | RW | AC Distribution | |||||||||||||||||
column · OCTET STRING (SIZE (0..63)) · read-write · current ACU device name, of the character string type, is used to specify the alternating current unit (ACU). Users can configure it. Otherwise, the configured character can not be any other languages except English. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwApOrAblVoltage | 1.3.6.1.4.1.2011.6.164.1.5.2.1.1.4 | Unsigned32 (0..5000) | RO | 2358 | |||||||||||||||||
column · Unsigned32 (0..5000) · read-only · current ACU A-phase or AB-line voltage. Value range: 0 to 500, unit: V, and the value is accurate to one decimal place (.1).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwBpOrBclVoltage | 1.3.6.1.4.1.2011.6.164.1.5.2.1.1.5 | Unsigned32 (0..5000) | RO | 2147483647 | |||||||||||||||||
column · Unsigned32 (0..5000) · read-only · current ACU B-phase or BC-line voltage. Value range: 0 to 500, unit: V, and the value is accurate to one decimal place (.1).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwCpOrCalVoltage | 1.3.6.1.4.1.2011.6.164.1.5.2.1.1.6 | Unsigned32 (0..5000) | RO | 2147483647 | |||||||||||||||||
column · Unsigned32 (0..5000) · read-only · current ACU C-phase or CA-line voltage. Value range: 0 to 500, unit: V, and the value is accurate to one decimal place (.1).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwAphaseCurrent | 1.3.6.1.4.1.2011.6.164.1.5.2.1.1.7 | Integer32 (0..1000) | RO | 8 | |||||||||||||||||
column · Integer32 (0..1000) · read-only · current ACU A-phase current. It is an analog parameter collected by the ACU in real time. Value range: 0 to 100, unit: A, and the value is accurate to one decimal place (.1).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwBphaseCurrent | 1.3.6.1.4.1.2011.6.164.1.5.2.1.1.8 | Integer32 (0..1000) | RO | 2147483647 | |||||||||||||||||
column · Integer32 (0..1000) · read-only · current ACU B-phase current. It is an analog parameter collected by the ACU in real time. Value range: 0 to 100, unit: A, and the value is accurate to one decimal place (.1).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwCphaseCurrent | 1.3.6.1.4.1.2011.6.164.1.5.2.1.1.9 | Integer32 (0..1000) | RO | 2147483647 | |||||||||||||||||
column · Integer32 (0..1000) · read-only · current ACU C-phase current. It is an analog parameter collected by the ACU in real time. Value range: 0 to 100, unit: A, and the value is accurate to one decimal place (.1).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwAcInputBreakersQuantity | 1.3.6.1.4.1.2011.6.164.1.5.2.1.1.10 | Unsigned32 (0..100) | RO | ||||||||||||||||||
column · Unsigned32 (0..100) · read-only · current Quantity of the AC air circuit breakers. As the ACU lower-level subset, the node indicates the quantity of the output air circuit breakers contained by each ACU lower-level subset. Value range: 0 to 100. | |||||||||||||||||||||
| ChwAcInputOperStatus | 1.3.6.1.4.1.2011.6.164.1.5.2.1.1.99 | INTEGER | RO | normal(1) | |||||||||||||||||
column · INTEGER · read-only · current State of the site AC distribution uint. It is an enumeration type: If the enumeration value is 1, it indicates that the site AC distribution uint is in the normal state; If the enumeration value is 2, it indicates that AC distribution uint power off; If the enumeration value is 3, it indicates that AC input phase absent; If the enumeration value is 4, it indicates that AC voltage is over upper alarm threshold; If the enumeration value is 5, it indicates that AC voltage is under lower alarm threshold; If the enumeration value is 254, it indicates AC distribution uint alarm resume; If the enumeration value is 255, it indicates AC distribution uint operation status unknown.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwAcRowStatus | 1.3.6.1.4.1.2011.6.164.1.5.2.1.1.100 | RowStatus | RC | 1 | |||||||||||||||||
column · RowStatus · read-create · current RowStatus of ACU. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ThwAcInputBreakerTable | 1.3.6.1.4.1.2011.6.164.1.5.2.2 | NA | |||||||||||||||||||
table · not-accessible · current Ac input breaker table. Use this table to get AC input breaker equipment ID, AC input breaker equipment name, and AC input breaker status. This table's index is hwAcInputBreakerIndex, which qualificated by hwAcInputBreakersQuantity in hwAcInputTable, clone Ac input breaker table. | |||||||||||||||||||||
| RhwAcInputBreakerEntry | 1.3.6.1.4.1.2011.6.164.1.5.2.2.1 | NA | |||||||||||||||||||
row · not-accessible · current Ac input breaker table entry. | |||||||||||||||||||||
| ChwAcInputBreakerIndex | 1.3.6.1.4.1.2011.6.164.1.5.2.2.1.1 | Integer32 (1..100) | RO | ||||||||||||||||||
column · Integer32 (1..100) · read-only · current Device table index of the AC air circuit breaker. Value range: 1 to 100. An input air circuit breaker device can be uniquely identified through the ACU table index and device index of the AC air circuit breaker. | |||||||||||||||||||||
| ChwAcInputBreakerEquipId | 1.3.6.1.4.1.2011.6.164.1.5.2.2.1.2 | Unsigned32 (5001..5100) | RO | ||||||||||||||||||
column · Unsigned32 (5001..5100) · read-only · current AC input air circuit breaker ID. Value range: 005,001 to 005,100. The first digits indicate the device type and the last three digits indicate the device SN. | |||||||||||||||||||||
| ChwAcInputBreakerEquipName | 1.3.6.1.4.1.2011.6.164.1.5.2.2.1.3 | OCTET STRING (SIZE (0..63)) | RW | ||||||||||||||||||
column · OCTET STRING (SIZE (0..63)) · read-write · current AC input air circuit breaker name, of the character string type, can configured by users. Otherwise, the configured character can not be any other languages except English. | |||||||||||||||||||||
| ChwAcInputBreakerOperStatus | 1.3.6.1.4.1.2011.6.164.1.5.2.2.1.99 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current Operation state of the site AC input breaker. It is an enumeration type: If the enumeration value is 1, it indicates that the site AC input breaker is in the normal state; If the enumeration value is 2, it indicates that the AC input breaker disconnect; If the enumeration value is 254, it indicates AC input breaker alarm resume; If the enumeration value is 255, it indicates AC input breaker operation status unknown.
| |||||||||||||||||||||
| ChwAcInputBreakerRowStatus | 1.3.6.1.4.1.2011.6.164.1.5.2.2.1.100 | RowStatus | RC | ||||||||||||||||||
column · RowStatus · read-create · current RowStatus of AC input breaker. | |||||||||||||||||||||
| NhwSiteDcDistributions | 1.3.6.1.4.1.2011.6.164.1.6 | ||||||||||||||||||||
| NhwDcDistributionsGroup | 1.3.6.1.4.1.2011.6.164.1.6.1 | ||||||||||||||||||||
| ShwDcsGroupId | 1.3.6.1.4.1.2011.6.164.1.6.1.1 | Unsigned32 | RO | 6000 | |||||||||||||||||
scalar · Unsigned32 · read-only · current DC group ID: unique ID of the DC group. in which The first digits indicate the device type and the last three digits indicate the device SN. If the last three digits are 000, it indicates a virtual device. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwDcsGroupName | 1.3.6.1.4.1.2011.6.164.1.6.1.2 | OCTET STRING (SIZE (0..63)) | RW | DC Distribution Group | |||||||||||||||||
scalar · OCTET STRING (SIZE (0..63)) · read-write · current Device name of the DC group, of the character string type, can be configured by users. Otherwise, the configured character can not be any other languages except English. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwDcsTotalVoltage | 1.3.6.1.4.1.2011.6.164.1.6.1.3 | Unsigned32 (0..600) | RO | 535 | |||||||||||||||||
scalar · Unsigned32 (0..600) · read-only · current Total voltage of the DC group. Value range: 0 to 60, unit: V, and the value is accurate to one decimal place (.1).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwDcsTotalCurrent | 1.3.6.1.4.1.2011.6.164.1.6.1.4 | Unsigned32 (0..1000000) | RO | 7 | |||||||||||||||||
scalar · Unsigned32 (0..1000000) · read-only · current Total current of the DC group. Value range: 0 to 10000, unit: A, and the value is accurate to one decimal place (.1).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwDcsTotalPower | 1.3.6.1.4.1.2011.6.164.1.6.1.5 | Unsigned32 (0..600000) | RO | 179 | |||||||||||||||||
scalar · Unsigned32 (0..600000) · read-only · current Total power of the DC group. Value range: 0 to 10000, unit: W, and the value is an integer (.0).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwDcsTotalQuantity | 1.3.6.1.4.1.2011.6.164.1.6.1.6 | Unsigned32 (0..100) | RO | 1 | |||||||||||||||||
scalar · Unsigned32 (0..100) · read-only · current Total quantity of the DC units, and its Value range: 0 to 100. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwSetDcsUpperVoltLimit | 1.3.6.1.4.1.2011.6.164.1.6.1.7 | Unsigned32 (300..600) | RW | 580 | |||||||||||||||||
scalar · Unsigned32 (300..600) · read-write · current Upper threshold of the DC voltage alarm, can be configued by users. Value range: 30 to 60, unit: V, and the value is accurate to one decimal space (.1).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwSetDcsLowerVoltLimit | 1.3.6.1.4.1.2011.6.164.1.6.1.8 | Unsigned32 (300..600) | RW | 450 | |||||||||||||||||
scalar · Unsigned32 (300..600) · read-write · current Lower threshold of the DC voltage alarm, can be configued by users. Value range: 30 to 60, unit: V, and the value is accurate to one decimal space (.1).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NhwDcDistribution | 1.3.6.1.4.1.2011.6.164.1.6.2 | ||||||||||||||||||||
| ThwDcOutputTable | 1.3.6.1.4.1.2011.6.164.1.6.2.1 | NA | |||||||||||||||||||
table · not-accessible · current DC output table. Use this table to get DC distribution unit ID, DC distribution unit name, DC output voltage, DC output power, and loads quantity in each DC distribution unit, which defines hwLoadsOutputTable row number. This table's index is hwDcOutputIndex, clone Dc output table. | |||||||||||||||||||||
| RhwDcOutputEntry | 1.3.6.1.4.1.2011.6.164.1.6.2.1.1 | NA | |||||||||||||||||||
| ChwDcOutputIndex | 1.3.6.1.4.1.2011.6.164.1.6.2.1.1.1 | Integer32 (1..100) | RO | 1 | |||||||||||||||||
column · Integer32 (1..100) · read-only · current Device table index of the DC units, which value range: 1 to 100. Lines of the device list are restricted by the total quantity of DC units (hwDcsQuantity). Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwDcOutputEquipId | 1.3.6.1.4.1.2011.6.164.1.6.2.1.1.2 | Unsigned32 (6001..6100) | RO | 6001 | |||||||||||||||||
column · Unsigned32 (6001..6100) · read-only · current DC unit device ID, which value range: 006,001 to 006,100. The first digits indicate the device type and the last three digits indicate the device SN. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwDcOutputEquipName | 1.3.6.1.4.1.2011.6.164.1.6.2.1.1.3 | OCTET STRING (SIZE (0..63)) | RW | DC Distribution | |||||||||||||||||
column · OCTET STRING (SIZE (0..63)) · read-write · current DC unit device name, of the character string type, can be configued by users. Otherwise, the configured character can not be any other languages except English. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwDcOutputVoltage | 1.3.6.1.4.1.2011.6.164.1.6.2.1.1.4 | Unsigned32 (0..600) | RO | 535 | |||||||||||||||||
column · Unsigned32 (0..600) · read-only · current DC output voltage. It is an analog parameter collected by the DC power in real time. Value range: 0 to 60, unit: V, and the value is accurate to one decimal space (.1).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwDcOutputCurrent | 1.3.6.1.4.1.2011.6.164.1.6.2.1.1.5 | Unsigned32 (0..100000) | RO | 7 | |||||||||||||||||
column · Unsigned32 (0..100000) · read-only · current DC output current. It is an analog parameter collected by the DC power in real time. Value range: 0 to 10000, unit: A, and the value is accurate to one decimal space (.1).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwDcOutputPower | 1.3.6.1.4.1.2011.6.164.1.6.2.1.1.6 | Unsigned32 (0..600000) | RO | 179 | |||||||||||||||||
column · Unsigned32 (0..600000) · read-only · current DC output power. It is an analog parameter collected by the DC power in real time. Value range: 0 to 600000, unit: W, and the value is an integer (.0).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwLoadsQuantity | 1.3.6.1.4.1.2011.6.164.1.6.2.1.1.7 | Unsigned32 (0..100) | RO | 0 | |||||||||||||||||
column · Unsigned32 (0..100) · read-only · current Quantity of the DC load output branches, which value range: 0 to 100. As the DC unit lower-level subset, the node indicates the quantity of the DC load output branches contained by each DC unit lower-level subset. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwDcOutputOperStatus | 1.3.6.1.4.1.2011.6.164.1.6.2.1.1.99 | INTEGER | RO | normal(1) | |||||||||||||||||
column · INTEGER · read-only · current State of the site DC distribution uint. It is an enumeration type: If the enumeration value is 1, it indicates that the site DC distribution uint is in the normal state; If the enumeration value is 2, it indicates that DC voltage is over the upper alarm threshold; If the enumeration value is 3, it indicates that DC voltage is under the lower alarm threshold; If the enumeration value is 254, it indicates DC distribution uint alarm resume; If the enumeration value is 255, it indicates DC distribution uint operation status unknown.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwDcOutputRowStatus | 1.3.6.1.4.1.2011.6.164.1.6.2.1.1.100 | RowStatus | RC | 1 | |||||||||||||||||
column · RowStatus · read-create · current RowStatus of Dc output equipments. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ThwLoadBranchTable | 1.3.6.1.4.1.2011.6.164.1.6.2.2 | NA | |||||||||||||||||||
table · not-accessible · current Loads output table. Use this table to get load branch equipment ID, load branch equipment name, load branch current, and load branch power. This table's index is hwLoadBranchIndex, which qualificated by hwloadsQuantity in hwDcOutputTable, clone loads output table. | |||||||||||||||||||||
| RhwLoadBranchEntry | 1.3.6.1.4.1.2011.6.164.1.6.2.2.1 | NA | |||||||||||||||||||
| ChwLoadBranchIndex | 1.3.6.1.4.1.2011.6.164.1.6.2.2.1.1 | Integer32 (1..100) | RO | ||||||||||||||||||
column · Integer32 (1..100) · read-only · current Device table index of the DC load output branch, which value range: 1 to 100. A DC load output branch can be uniquely identified through the DC unit table index and device index of the DC load output branch. | |||||||||||||||||||||
| ChwLoadBranchEquipId | 1.3.6.1.4.1.2011.6.164.1.6.2.2.1.2 | Unsigned32 (7001..7100) | RO | ||||||||||||||||||
column · Unsigned32 (7001..7100) · read-only · current Device ID of the DC load output branch. Value range: 007,001 to 007,100. The first digits indicate the device type and the last three digits indicate the SN of the device. | |||||||||||||||||||||
| ChwLoadBranchEquipName | 1.3.6.1.4.1.2011.6.164.1.6.2.2.1.3 | OCTET STRING (SIZE (0..63)) | RW | ||||||||||||||||||
column · OCTET STRING (SIZE (0..63)) · read-write · current Device name of the DC load output branch, of the character string type, can be configured by users. Otherwise, the configured character can not be any other languages except English. | |||||||||||||||||||||
| ChwLoadBranchCurrent | 1.3.6.1.4.1.2011.6.164.1.6.2.2.1.4 | Unsigned32 (0..100000) | RO | ||||||||||||||||||
column · Unsigned32 (0..100000) · read-only · current DC load output branch current. It is an analog parameter collected by the load branch in real time. Value range: 0 to 10000, unit: A, and the value is accurate to one decimal space (.1).
| |||||||||||||||||||||
| ChwLoadBranchPower | 1.3.6.1.4.1.2011.6.164.1.6.2.2.1.5 | Unsigned32 (0..600000) | RO | ||||||||||||||||||
column · Unsigned32 (0..600000) · read-only · current DC load branch power. It is an analog parameter collected by the DC power in real time. Value range: 0 to 600000, unit: W, and the value is an integer (.0).
| |||||||||||||||||||||
| ChwLoadBranchOperStatus | 1.3.6.1.4.1.2011.6.164.1.6.2.2.1.99 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current State of the site load output branch. It is an enumeration type: If the enumeration value is 1, it indicates that the site load output branch is in the normal state; If the enumeration value is 2, it indicates that the load output branch disconnect; If the enumeration value is 254, it indicates load output branch alarm resume; If the enumeration value is 255, it indicates load output branch operation status unknown.
| |||||||||||||||||||||
| ChwLoadBranchRowStatus | 1.3.6.1.4.1.2011.6.164.1.6.2.2.1.100 | RowStatus | RC | ||||||||||||||||||
column · RowStatus · read-create · current RowStatus of loads output branch. | |||||||||||||||||||||
| NhwLvdUnits | 1.3.6.1.4.1.2011.6.164.1.7 | ||||||||||||||||||||
| NhwLvdsGroup | 1.3.6.1.4.1.2011.6.164.1.7.1 | ||||||||||||||||||||
| ShwLvdsGroupId | 1.3.6.1.4.1.2011.6.164.1.7.1.1 | Unsigned32 | RO | 8000 | |||||||||||||||||
scalar · Unsigned32 · read-only · current LVD unit group ID. It is the unique ID of the LVD unit group. The first digits indicate the device type. The last three digits indicate the device SN. If the last three digits are 000, it indicates a virtual device. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwLvdsGroupName | 1.3.6.1.4.1.2011.6.164.1.7.1.2 | OCTET STRING (SIZE (0..63)) | RW | Lvd Unit Group | |||||||||||||||||
scalar · OCTET STRING (SIZE (0..63)) · read-write · current Low-voltage power-off unit group name, of the character string type, can be configured by users. Otherwise, the configured character can not be any other languages except English. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwLvdsTotalQuantity | 1.3.6.1.4.1.2011.6.164.1.7.1.3 | Unsigned32 (0..100) | RO | 1 | |||||||||||||||||
scalar · Unsigned32 (0..100) · read-only · current Total quantity of power-off units. Value range: 0 to 100. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NhwLvdUnit | 1.3.6.1.4.1.2011.6.164.1.7.2 | ||||||||||||||||||||
| ThwLvdBranchTable | 1.3.6.1.4.1.2011.6.164.1.7.2.1 | NA | |||||||||||||||||||
table · not-accessible · current Power-off unit table. Use this table to get Lvd unit equipment ID and power-off unit equipment name, set power-off enable and power-off voltage, as well as control power-off unit disconnected. This table's index is hwLvdBranchIndex, which qualificated by hwLvdsQuantity, clone power-off unit table. | |||||||||||||||||||||
| RhwLvdBranchEntry | 1.3.6.1.4.1.2011.6.164.1.7.2.1.1 | NA | |||||||||||||||||||
| ChwLvdBranchIndex | 1.3.6.1.4.1.2011.6.164.1.7.2.1.1.1 | Integer32 (1..100) | RO | 3 | |||||||||||||||||
column · Integer32 (1..100) · read-only · current Device table index of a power-off unit. Value range: 1 to 100. Lines of the device list are restricted by the total quantity of the power-off units (hwLvdsTotalQuantity). Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwLvdUnitEquipId | 1.3.6.1.4.1.2011.6.164.1.7.2.1.1.2 | Unsigned32 (8001..8100) | RO | 8003 | |||||||||||||||||
column · Unsigned32 (8001..8100) · read-only · current Device ID of a power-off unit. Value range: 8001 to 8100. The first digits indicate the device type and the last three digits indicate the device SN. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwLvdUnitEquipName | 1.3.6.1.4.1.2011.6.164.1.7.2.1.1.3 | OCTET STRING (SIZE (0..63)) | RW | Lvd1 | |||||||||||||||||
column · OCTET STRING (SIZE (0..63)) · read-write · current Device name of a power-off unit, of the character string type, is used to specify the low-voltage power-off unit. Users can configure it. Otherwise, the configured character can not be any other languages except English. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwSetLvdEnable | 1.3.6.1.4.1.2011.6.164.1.7.2.1.1.4 | INTEGER | RW | enabled(1) | |||||||||||||||||
column · INTEGER · read-write · current Control power-off unit enabling. It is an enumeration value, and users actively set it. If the enumeration value is 1, it means to enable the power-off unit; If the enumeration value is 2, it means to disable the power-off unit. When the power-off unit control is not configured, the power-off unit is enabled by default.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwSetLvdVoltage | 1.3.6.1.4.1.2011.6.164.1.7.2.1.1.5 | Integer32 (350..600) | RW | 440 | |||||||||||||||||
column · Integer32 (350..600) · read-write · current Low-voltage power-off voltage of a power-off unit can be configured by users. Its value range: 35 to 60, unit: V, and the value is accurate to one decimal space (.1).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwCtrlLvd | 1.3.6.1.4.1.2011.6.164.1.7.2.1.1.6 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current Control of the power-off unit. It is an enumeration value, users control it manually. If the NMS notifies the SNMP agent that the node is set to 1, it means to power off the power-off unit; If the NMS notifies the SNMP agent that the node is set to 2, it means that the background controls the power-on of the LVD unit.
| |||||||||||||||||||||
| ChwLvdBranchOperStatus | 1.3.6.1.4.1.2011.6.164.1.7.2.1.1.99 | INTEGER | RO | normal(1) | |||||||||||||||||
column · INTEGER · read-only · current State of the site LVD uint. It is an enumeration type: If the enumeration value is 1, it indicates that the site LVD uint is in the normal state; If the enumeration value is 2, it indicates that the power-off uint disconnect for low voltage; If the enumeration value is 3, it indicates that the power-off uint disconnect bakeground; If the enumeration value is 4, it indicates that the power-off uint local disconnect manually; If the enumeration value is 5, it indicates that the power-off uint disconnect for under temperature; If the enumeration value is 6, it indicates that the power-off uint disconnect for over temperature; If the enumeration value is 254, it indicates that the power-off uint alarm resume; If the enumeration value is 255, it indicates LVD uint operation status unknown.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwLvdBranchRowStatus | 1.3.6.1.4.1.2011.6.164.1.7.2.1.1.100 | RowStatus | RC | 1 | |||||||||||||||||
column · RowStatus · read-create · current RowStatus of lvd table. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NhwSiteEnvUnits | 1.3.6.1.4.1.2011.6.164.1.8 | ||||||||||||||||||||
| NhwEnvUnitsGroup | 1.3.6.1.4.1.2011.6.164.1.8.1 | ||||||||||||||||||||
| ShwEnvUnitsGroupId | 1.3.6.1.4.1.2011.6.164.1.8.1.1 | Unsigned32 | RO | 9000 | |||||||||||||||||
scalar · Unsigned32 · read-only · current Unit group ID of the site environment. It is the unique ID of the unit group on the site. The first digits indicate the device type. The last three digits indicate the device SN. If the last three digits are 000, it indicates a virtual device. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwEnvUnitsGroupName | 1.3.6.1.4.1.2011.6.164.1.8.1.2 | OCTET STRING (SIZE (0..63)) | RW | Environment Unit Group | |||||||||||||||||
scalar · OCTET STRING (SIZE (0..63)) · read-write · current Unit group name of the site environment, of the character string type, can be configured by users. Otherwise, the configured character can not be any other languages except English. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwCtrlSmokeReset | 1.3.6.1.4.1.2011.6.164.1.8.1.3 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current Smoke sensor reset. It manually controls clearance of the smoke sensor alarm, and this node is of the enumeration type. If the enumeration value is 1, it indicates that the reset of the smoke sensor is not required. If the enumeration value of the node is 2, it indicates that the background controls the reset of the smoke sensor.
| |||||||||||||||||||||
| ShwCtrlDoorReset | 1.3.6.1.4.1.2011.6.164.1.8.1.4 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current Door actuator reset control. It manually controls clearance of the door actuator alarm. This node is of the enumeration type. If the enumeration value is 1, it indicates that clearance of the door actuator is not required; If the enumeration value is 2, it indicates that the background controls clearance of the door actuator.
| |||||||||||||||||||||
| ShwCtrlBuzzerEnable | 1.3.6.1.4.1.2011.6.164.1.8.1.5 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current Buzzer enabling. It manually controls the enabling of the buzzer alarm. This node is of the enumeration type. When the enumeration value is 1, it means to enable the buzzer; When the enumeration value is 2, it means to disable the buzzer.
| |||||||||||||||||||||
| ShwEnvTempSensorsTotalQuantity | 1.3.6.1.4.1.2011.6.164.1.8.1.6 | Unsigned32 (0..256) | RO | 1 | |||||||||||||||||
scalar · Unsigned32 (0..256) · read-only · current Quantity of the environment temperature sensors, and its value range: 0 to 256. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwEnvHumiSensorsTotalQuantity | 1.3.6.1.4.1.2011.6.164.1.8.1.7 | Unsigned32 (0..256) | RO | 0 | |||||||||||||||||
scalar · Unsigned32 (0..256) · read-only · current Quantity of the environment humidity sensors, and its value range: 0 to 256. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ShwSpareDigitalsTotalQuantity | 1.3.6.1.4.1.2011.6.164.1.8.1.8 | Unsigned32 (0..256) | RO | 5 | |||||||||||||||||
scalar · Unsigned32 (0..256) · read-only · current Quantity of the Spare digitals, and its value range: 0 to 256. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NhwEnvSensor | 1.3.6.1.4.1.2011.6.164.1.8.2 | ||||||||||||||||||||
| ThwEnvTempSensorTable | 1.3.6.1.4.1.2011.6.164.1.8.2.1 | NA | |||||||||||||||||||
table · not-accessible · current Site environment temperature table. Use this table to get environment temperature equipment ID, environment temperature equipment name, and environment temperature, set environment temperature upper limit, environment temperature lower limit, and environment temperature alarm enable. This table's index is hwEnvTempSensorIndex, which qualificated by hwEnvTempSensorsQuantity, clone site environment temperature table. | |||||||||||||||||||||
| RhwEnvTempSensorEntry | 1.3.6.1.4.1.2011.6.164.1.8.2.1.1 | NA | |||||||||||||||||||
| ChwEnvTempSensorIndex | 1.3.6.1.4.1.2011.6.164.1.8.2.1.1.1 | Integer32 (1..256) | RO | 1 | |||||||||||||||||
column · Integer32 (1..256) · read-only · current Table index of the environment temperature sensors. Value range: 1 to 256. Lines of the device table are restricted by the quantity of environment temperature sensors (hwEnvTempSensorsTotalQuantity). Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwEnvTempEquipId | 1.3.6.1.4.1.2011.6.164.1.8.2.1.1.2 | Unsigned32 (9001..9255) | RO | 9001 | |||||||||||||||||
column · Unsigned32 (9001..9255) · read-only · current Environment temperature sensor ID. Value range: 009'001 to 009'255, in which the first digits indicate the device type and the last three digits indicate the device SN. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwEnvTempEquipName | 1.3.6.1.4.1.2011.6.164.1.8.2.1.1.3 | OCTET STRING (SIZE (0..63)) | RW | Environment temperature sensor1 | |||||||||||||||||
column · OCTET STRING (SIZE (0..63)) · read-write · current Environment temperature sensor name, of the character string type, is used to specify an environment temperature sensor. Users can configure it. Otherwise, the configured character can not be any other languages except English. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwEnvTemperature | 1.3.6.1.4.1.2011.6.164.1.8.2.1.1.4 | Integer32 (-50..100) | RO | 2147483647 | |||||||||||||||||
column · Integer32 (-50..100) · read-only · current Environment temperature. It is an environment parameter collected in real time. Value range: -50 to +100, unit: centigrade (°„C), and the value is an integer (.0). If the value is -1024, it indicates that the temperature sensor is not configured.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwSetEnvTempUpperLimit | 1.3.6.1.4.1.2011.6.164.1.8.2.1.1.5 | Integer32 (-50..100) | RW | 55 | |||||||||||||||||
column · Integer32 (-50..100) · read-write · current Upper threshold of the environment temperature alarm, can be configured by users. Value range: -50 to 100, unit: centigrade (°„C), and the value is an integer (.0).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwSetEnvTempLowerLimit | 1.3.6.1.4.1.2011.6.164.1.8.2.1.1.6 | Integer32 (-50..100) | RW | -20 | |||||||||||||||||
column · Integer32 (-50..100) · read-write · current Lower threshold of the environment temperature alarm, can be configured by users. Value range: -50 to 100, unit: centigrade (°„C), and the value is an integer (.0).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwSetEnvTempMeasureUpperLimit | 1.3.6.1.4.1.2011.6.164.1.8.2.1.1.7 | Integer32 (0..100) | RW | ||||||||||||||||||
column · Integer32 (0..100) · read-write · current Upper threshold of the environment temperature measurement, can be configured by users. Value range: 0 to 100, unit: centigrade (°„C), and the value is an integer (.0).
| |||||||||||||||||||||
| ChwSetEnvTempMeasureLowerLimit | 1.3.6.1.4.1.2011.6.164.1.8.2.1.1.8 | Integer32 (-50..0) | RW | ||||||||||||||||||
column · Integer32 (-50..0) · read-write · current Lower threshold of the environment temperature measurement, can be configured by users. Value range: -50 to 0, unit: centigrade (°„C), and the value is an integer (.0).
| |||||||||||||||||||||
| ChwSetEnvTempAlarmEnable | 1.3.6.1.4.1.2011.6.164.1.8.2.1.1.9 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current Environment temperature alarm. It is an enumeration type: If the enumeration value is 1, enable the alarm of the environment temperature; If the enumeration value is 2, disable the alarm of the environment temperature.
| |||||||||||||||||||||
| ChwEnvTempSensorOperStatus | 1.3.6.1.4.1.2011.6.164.1.8.2.1.1.99 | INTEGER | RO | normal(1) | |||||||||||||||||
column · INTEGER · read-only · current State of the site environment temperature sensor. It is an enumeration type: If the enumeration value is 1, it indicates that the site environment temperature sensor is in the normal state; If the enumeration value is 2, it indicates that the environment temperature sensor is over temperature; If the enumeration value is 3, it indicates that the environment temperature sensor is under temperature; If the enumeration value is 4, it indicates that the environment temperature sensor is not in slot; If the enumeration value is 254, it indicates that environment temperature alarm resume; If the enumeration value is 255, it indicates environment temperature sensor operation status unknown.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwEnvTempSensorRowStatus | 1.3.6.1.4.1.2011.6.164.1.8.2.1.1.100 | RowStatus | RC | ||||||||||||||||||
column · RowStatus · read-create · current RowStatus of Environment temperature table. | |||||||||||||||||||||
| ThwEnvHumiSensorTable | 1.3.6.1.4.1.2011.6.164.1.8.2.2 | NA | |||||||||||||||||||
table · not-accessible · current Environment humidity table. Use this table to get environment humidity equipment ID , environment humidity equipment name, and environment humidity, set environment humidity upper limit, environment humidity lower limit, and environment humidity alarm enable. This table's index is hwEnvHumiSensorIndex, which qualificated by hwEnvHumiSensorIndex, clone site environment humidity table. | |||||||||||||||||||||
| RhwEnvHumiSensorEntry | 1.3.6.1.4.1.2011.6.164.1.8.2.2.1 | NA | |||||||||||||||||||
| ChwEnvHumiSensorIndex | 1.3.6.1.4.1.2011.6.164.1.8.2.2.1.1 | Integer32 (1..256) | RO | ||||||||||||||||||
column · Integer32 (1..256) · read-only · current Table index of the environment humility sensors. Value range: 1 to 256. Lines of the device list are restricted by the quantity of environment humility sensors (hwEnvHumiSensorsTotalQuantity). | |||||||||||||||||||||
| ChwEnvHumiEquipId | 1.3.6.1.4.1.2011.6.164.1.8.2.2.1.2 | Unsigned32 (10001..10255) | RO | ||||||||||||||||||
column · Unsigned32 (10001..10255) · read-only · current Environment humility sensor ID, can be configured by users. Value range: 010'001 to 010'255, in which the first digits indicate the device type and the last three digits indicate the device SN. | |||||||||||||||||||||
| ChwEnvHumiEquipName | 1.3.6.1.4.1.2011.6.164.1.8.2.2.1.3 | OCTET STRING (SIZE (0..63)) | RW | ||||||||||||||||||
column · OCTET STRING (SIZE (0..63)) · read-write · current Environment humility sensor name, of the character string type, is used to specify an environment humility sensor. Users can configure it. Otherwise, the configured character can not be any other languages except English. | |||||||||||||||||||||
| ChwEnvHumidity | 1.3.6.1.4.1.2011.6.164.1.8.2.2.1.4 | Integer32 (0..100) | RO | ||||||||||||||||||
column · Integer32 (0..100) · read-only · current Environment humility. It is an environment parameter collected in real time. Value range: 0 to 100, unit: %RH, and the value is an integer (.0). If the value is 255, it indicates that the humidity sensor is not configured.
| |||||||||||||||||||||
| ChwSetEnvHumidityUpperLimit | 1.3.6.1.4.1.2011.6.164.1.8.2.2.1.5 | Integer32 (0..100) | RW | ||||||||||||||||||
column · Integer32 (0..100) · read-write · current Upper threshold of the environment humility alarm, can be configured by users. Value range: 0 to 100, unit: %RH, and the value is an integer (.0).
| |||||||||||||||||||||
| ChwSetEnvHumidityLowerLimit | 1.3.6.1.4.1.2011.6.164.1.8.2.2.1.6 | Integer32 (0..100) | RW | ||||||||||||||||||
column · Integer32 (0..100) · read-write · current Lower threshold of the environment humility alarm, can be configured by users. Value range: 0 to 100, unit: %RH, and the value is an integer (.0).
| |||||||||||||||||||||
| ChwSetEnvHumidityMeasureUpperLimit | 1.3.6.1.4.1.2011.6.164.1.8.2.2.1.7 | Integer32 (0..100) | RW | ||||||||||||||||||
column · Integer32 (0..100) · read-write · current Upper threshold of the environment humility measurement, can be configured by users. Value range: 0 to 100, unit: %RH, and the value is an integer (.0).
| |||||||||||||||||||||
| ChwSetEnvHumidityMeasureLowerLimit | 1.3.6.1.4.1.2011.6.164.1.8.2.2.1.8 | Integer32 (0..100) | RW | ||||||||||||||||||
column · Integer32 (0..100) · read-write · current Lower threshold of the environment humility measurement, can be configured by users. Value range: 0 to 100, unit: %RH, and the value is an integer (.0).
| |||||||||||||||||||||
| ChwSetEnvHumiAlarmEnable | 1.3.6.1.4.1.2011.6.164.1.8.2.2.1.9 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current Environment humility alarm. It is an enumeration type: If the enumeration value is 1, enable the alarm of the environment humility; If the enumeration value is 2, disable the alarm of the environment humility. The environment humility alarm is enabled by default.
| |||||||||||||||||||||
| ChwEnvHumiSensorOperStatus | 1.3.6.1.4.1.2011.6.164.1.8.2.2.1.99 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current State of the site environment humidity sensor. It is an enumeration type: If the enumeration value is 1, it indicates that the site environment humidity sensor is in the normal state; If the enumeration value is 2, it indicates that the environment humidity sensor is over humidity; If the enumeration value is 3, it indicates that the environment humidity sensor is under humidity; If the enumeration value is 4, it indicates that the environment humidity sensor is not in slot; If the enumeration value is 254, it indicates that environment humidity alarm resume; If the enumeration value is 255, it indicates environment humidity sensor operation status unknown.
| |||||||||||||||||||||
| ChwEnvHumiSensorRowStatus | 1.3.6.1.4.1.2011.6.164.1.8.2.2.1.100 | RowStatus | RC | ||||||||||||||||||
column · RowStatus · read-create · current RowStatus of Environment humidity table. | |||||||||||||||||||||
| ThwSpareDigitalTable | 1.3.6.1.4.1.2011.6.164.1.8.2.3 | NA | |||||||||||||||||||
table · not-accessible · current Spare digital table. Use this table to get Spare digital equipment ID , Spare digital equipment name, and current Spare digital alarm tension, ae well as to set Spare digital alarm enable. This table's index is hwSpareDigitalIndex, which qualificated by hwSpareDigitalsTotalQuantity, clone switch input table. | |||||||||||||||||||||
| RhwSpareDigitalEntry | 1.3.6.1.4.1.2011.6.164.1.8.2.3.1 | NA | |||||||||||||||||||
| ChwSpareDigitalIndex | 1.3.6.1.4.1.2011.6.164.1.8.2.3.1.1 | Integer32 (1..256) | RO | 1 | |||||||||||||||||
column · Integer32 (1..256) · read-only · current Spare digital table index, which value range: 1 to 256. Lines of the device list are restricted by the quantity of Spare digitals (hwSpareDigitalsTotalQuantity). Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwSpareDigitalEquipId | 1.3.6.1.4.1.2011.6.164.1.8.2.3.1.2 | Unsigned32 (11001..11255) | RO | 11001 | |||||||||||||||||
column · Unsigned32 (11001..11255) · read-only · current Spare digital device ID. Value range: 011'001 to 011'255, in which the first digits indicate the device type and the last three digits indicate the device SN. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwSpareDigitalEquipName | 1.3.6.1.4.1.2011.6.164.1.8.2.3.1.3 | OCTET STRING (SIZE (0..63)) | RW | DI1 | |||||||||||||||||
column · OCTET STRING (SIZE (0..63)) · read-write · current Spare digital name, of the character string type, is used to specify Spare digitals. Users can configure it. Otherwise, the configured character can not be any other languages except English. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwSetSpareDigitalAlarmTension | 1.3.6.1.4.1.2011.6.164.1.8.2.3.1.4 | INTEGER | RW | high(1) | |||||||||||||||||
column · INTEGER · read-write · current Spare digital alarm state. It is an enumeration value. If the value of the node is 0, it indicates a low-tension alarm; If the value of the node is 1, it indicates a high-tension alarm.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwSetSpareDigitalAlarmEnable | 1.3.6.1.4.1.2011.6.164.1.8.2.3.1.5 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current Spare digital alarm enabling. It is an enumeration type: If the enumeration value is 1, it means to enable the alarm; If the enumeration value is 2, it means to disable the alarm.
| |||||||||||||||||||||
| ChwSpareDigitalOperStatus | 1.3.6.1.4.1.2011.6.164.1.8.2.3.1.99 | INTEGER | RO | normal(1) | |||||||||||||||||
column · INTEGER · read-only · current State of the site Spare digital. It is an enumeration type: If the enumeration value is 1, it indicates that the Spare digital operation state is normal; If the enumeration value is 2, it indicates that a alarm occurs on the Spare digital; If the enumeration value is 254, it indicates that spare digital alarm resume; If the enumeration value is 255, it indicates Spare digital operation status unknown.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChwSpareDigitalRowStatus | 1.3.6.1.4.1.2011.6.164.1.8.2.3.1.100 | RowStatus | RC | ||||||||||||||||||
column · RowStatus · read-create · current RowStatus of Spare digital device table. | |||||||||||||||||||||
| NhwSitePDEs | 1.3.6.1.4.1.2011.6.164.1.9 | ||||||||||||||||||||
| NhwPDEGroup | 1.3.6.1.4.1.2011.6.164.1.9.1 | ||||||||||||||||||||
| ShwPDEGroupId | 1.3.6.1.4.1.2011.6.164.1.9.1.1 | Unsigned32 (12000..12255) | RO | ||||||||||||||||||
scalar · Unsigned32 (12000..12255) · read-only · current PDE unit group ID. It is the unique ID of the PDE unit group. The first digits indicate the device type. The last three digits indicate the device SN. If the last three digits are 000, it indicates a virtual device. | |||||||||||||||||||||
| ShwPDEGroupName | 1.3.6.1.4.1.2011.6.164.1.9.1.2 | OCTET STRING (SIZE (0..64)) | RW | ||||||||||||||||||
scalar · OCTET STRING (SIZE (0..64)) · read-write · current PDE unit group name, of the character string type, can be configured by users. Otherwise, the configured character can not be any other languages except English. | |||||||||||||||||||||
| ShwPDEGroupNum | 1.3.6.1.4.1.2011.6.164.1.9.1.3 | Unsigned32 (0..100) | RO | ||||||||||||||||||
scalar · Unsigned32 (0..100) · read-only · current PDE Num,Value range: 0 to 100. | |||||||||||||||||||||
| ShwPDEGroupCommNum | 1.3.6.1.4.1.2011.6.164.1.9.1.4 | Unsigned32 (0..100) | RO | ||||||||||||||||||
scalar · Unsigned32 (0..100) · read-only · current Communication PDE Num,Value range: 0 to 100. | |||||||||||||||||||||
| ShwPDEGroupTotalPower | 1.3.6.1.4.1.2011.6.164.1.9.1.5 | Unsigned32 (0..100000) | RO | ||||||||||||||||||
scalar · Unsigned32 (0..100000) · read-only · current PDE Total Power,Value range: 0.0 to 10000.0.Unit: W.and the value is accurate to one decimal space (.1).
| |||||||||||||||||||||
| ShwPDEGroupTotalCurrent | 1.3.6.1.4.1.2011.6.164.1.9.1.6 | Unsigned32 (0..3000) | RO | ||||||||||||||||||
scalar · Unsigned32 (0..3000) · read-only · current PDE Total Current,Value range: 0.0 to 300.0.Unit: A.and the value is accurate to one decimal space (.1).
| |||||||||||||||||||||
| ShwPDEGroupCommStatus | 1.3.6.1.4.1.2011.6.164.1.9.1.7 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current PDE Communication Status. It is an enumeration type: If the enumeration value is 1, it indicates that communication is normal; If the enumeration value is 2, it indicates that communication is abnormal. If the enumeration value is 255, it indicates that communication is unknown.
| |||||||||||||||||||||
| NhwPDE | 1.3.6.1.4.1.2011.6.164.1.9.3 | ||||||||||||||||||||
| ThwPDETable | 1.3.6.1.4.1.2011.6.164.1.9.3.1 | NA | |||||||||||||||||||
table · not-accessible · current PDE table. Use this table to get PDE equipment ID , PDE equipment name, and current PDE status. This table's index is hwPDEIndex. | |||||||||||||||||||||
| RhwPDEEntry | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1 | NA | |||||||||||||||||||
| ChwPDEIndex | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.1 | Integer32 (1..10) | RO | ||||||||||||||||||
column · Integer32 (1..10) · read-only · current PDE table index, which value range: 1 to 10. Lines of the device list are restricted by the quantity of PDE. | |||||||||||||||||||||
| ChwPDEEquipId | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.2 | Unsigned32 (12001..12255) | RO | ||||||||||||||||||
column · Unsigned32 (12001..12255) · read-only · current PDE device ID. Value range: 012'001 to 012'255, in which the first digits indicate the device type and the last three digits indicate the device SN. | |||||||||||||||||||||
| ChwPDEEquipName | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.3 | OCTET STRING (SIZE (0..64)) | RW | ||||||||||||||||||
column · OCTET STRING (SIZE (0..64)) · read-write · current PDE name, of the character string type, is used to specify PDEs. Users can configure it. Otherwise, the configured character can not be any other languages except English. | |||||||||||||||||||||
| ChwPDETotalRunningTime | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.4 | Unsigned32 (0..876000) | RO | ||||||||||||||||||
column · Unsigned32 (0..876000) · read-only · current PDE Total Running Time,Value range: 0 to 876000.Unit: H.
| |||||||||||||||||||||
| ChwPDEBranchNum | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.5 | Unsigned32 (0..6) | RO | ||||||||||||||||||
column · Unsigned32 (0..6) · read-only · current PDE Branch Number,Value range: 0 to 6. | |||||||||||||||||||||
| ChwPDETotalPower | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.6 | Unsigned32 (0..100000) | RO | ||||||||||||||||||
column · Unsigned32 (0..100000) · read-only · current PDE Total Power,Value range: 0.0 to 10000.0.Unit: W.and the value is accurate to one decimal space (.1).
| |||||||||||||||||||||
| ChwPDETotalCurrent | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.7 | Unsigned32 (0..300000) | RO | ||||||||||||||||||
column · Unsigned32 (0..300000) · read-only · current PDE Total Current,Value range: 0.0 to 30000.0.Unit: A.and the value is accurate to one decimal space (.1).
| |||||||||||||||||||||
| ChwPDEBranch1Power | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.8 | Unsigned32 (0..1000000) | RO | ||||||||||||||||||
column · Unsigned32 (0..1000000) · read-only · current PDE Branch1 Power,Value range: 0.0 to 100000.0.Unit: W.and the value is accurate to one decimal space (.1).
| |||||||||||||||||||||
| ChwPDEBranch2Power | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.9 | Unsigned32 (0..1000000) | RO | ||||||||||||||||||
column · Unsigned32 (0..1000000) · read-only · current PDE Branch2 Power,Value range: 0.0 to 100000.0.Unit: W.and the value is accurate to one decimal space (.1).
| |||||||||||||||||||||
| ChwPDEBranch3Power | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.10 | Unsigned32 (0..1000000) | RO | ||||||||||||||||||
column · Unsigned32 (0..1000000) · read-only · current PDE Branch3 Power,Value range: 0.0 to 100000.0.Unit: W.and the value is accurate to one decimal space (.1).
| |||||||||||||||||||||
| ChwPDEBranch4Power | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.11 | Unsigned32 (0..1000000) | RO | ||||||||||||||||||
column · Unsigned32 (0..1000000) · read-only · current PDE Branch4 Power,Value range: 0.0 to 100000.0.Unit: W.and the value is accurate to one decimal space (.1).
| |||||||||||||||||||||
| ChwPDEBranch1Current | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.12 | Unsigned32 (0..10000) | RO | ||||||||||||||||||
column · Unsigned32 (0..10000) · read-only · current PDE Branch1 Current,Value range: 0.0 to 1000.0.Unit: A.and the value is accurate to one decimal space (.1).
| |||||||||||||||||||||
| ChwPDEBranch2Current | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.13 | Unsigned32 (0..10000) | RO | ||||||||||||||||||
column · Unsigned32 (0..10000) · read-only · current PDE Branch2 Current,Value range: 0.0 to 1000.0.Unit: A.and the value is accurate to one decimal space (.1).
| |||||||||||||||||||||
| ChwPDEBranch3Current | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.14 | Unsigned32 (0..10000) | RO | ||||||||||||||||||
column · Unsigned32 (0..10000) · read-only · current PDE Branch3 Current,Value range: 0.0 to 1000.0.Unit: A.and the value is accurate to one decimal space (.1).
| |||||||||||||||||||||
| ChwPDEBranch4Current | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.15 | Unsigned32 (0..10000) | RO | ||||||||||||||||||
column · Unsigned32 (0..10000) · read-only · current PDE Branch4 Current,Value range: 0.0 to 1000.0.Unit: A.and the value is accurate to one decimal space (.1).
| |||||||||||||||||||||
| ChwPDEBranch1Voltage | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.16 | Unsigned32 (0..650) | RO | ||||||||||||||||||
column · Unsigned32 (0..650) · read-only · current PDE Branch1 Voltage,Value range: 0.0 to 65.0.Unit: V.and the value is accurate to one decimal space (.1).
| |||||||||||||||||||||
| ChwPDEBranch2Voltage | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.17 | Unsigned32 (0..650) | RO | ||||||||||||||||||
column · Unsigned32 (0..650) · read-only · current PDE Branch2 Voltage,Value range: 0.0 to 65.0.Unit: V.and the value is accurate to one decimal space (.1).
| |||||||||||||||||||||
| ChwPDEBranch3Voltage | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.18 | Unsigned32 (0..650) | RO | ||||||||||||||||||
column · Unsigned32 (0..650) · read-only · current PDE Branch3 Voltage,Value range: 0.0 to 65.0.Unit: V.and the value is accurate to one decimal space (.1).
| |||||||||||||||||||||
| ChwPDEBranch4Voltage | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.19 | Unsigned32 (0..650) | RO | ||||||||||||||||||
column · Unsigned32 (0..650) · read-only · current PDE Branch4 Voltage,Value range: 0.0 to 65.0.Unit: V.and the value is accurate to one decimal space (.1).
| |||||||||||||||||||||
| ChwPDEBranch1Temperature | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.20 | Unsigned32 (0..300) | RO | ||||||||||||||||||
column · Unsigned32 (0..300) · read-only · current PDE Branch1 Temperature,Value range: 0 to 300.Unit: deg.
| |||||||||||||||||||||
| ChwPDEBranch2Temperature | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.21 | Unsigned32 (0..300) | RO | ||||||||||||||||||
column · Unsigned32 (0..300) · read-only · current PDE Branch2 Temperature,Value range: 0 to 300.Unit: deg.
| |||||||||||||||||||||
| ChwPDEBranch3Temperature | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.22 | Unsigned32 (0..300) | RO | ||||||||||||||||||
column · Unsigned32 (0..300) · read-only · current PDE Branch3 Temperature,Value range: 0 to 300.Unit: deg.
| |||||||||||||||||||||
| ChwPDEBranch4Temperature | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.23 | Unsigned32 (0..300) | RO | ||||||||||||||||||
column · Unsigned32 (0..300) · read-only · current PDE Branch4 Temperature,Value range: 0 to 300.Unit: deg.
| |||||||||||||||||||||
| ChwPDEOperStatus | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.24 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current State of the PDE. It is an enumeration type: If the enumeration value is 1, it indicates that the PDE is in the normal state; If the enumeration value is 2, it indicates that the PDE is in the alarm state; If the enumeration value is 254, it indicates that the PDE is in the resume state; If the enumeration value is 255, it indicates PDE operation status unknown.
| |||||||||||||||||||||
| ChwPDERowStatus | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.100 | RowStatus | RC | ||||||||||||||||||
column · RowStatus · read-create · current RowStatus of PDE table. | |||||||||||||||||||||
| ThwPDEConfigTable | 1.3.6.1.4.1.2011.6.164.1.9.3.2 | NA | |||||||||||||||||||
table · not-accessible · current PDE Config table. Use this table to get PDE equipment ID , PDE equipment name, and current PDE config parameter. This table's index is hwPDEConfigIndex. | |||||||||||||||||||||
| RhwPDEConfigEntry | 1.3.6.1.4.1.2011.6.164.1.9.3.2.1 | NA | |||||||||||||||||||
| ChwPDEConfigIndex | 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.1 | Integer32 (1..10) | RO | ||||||||||||||||||
column · Integer32 (1..10) · read-only · current PDE Config table index, which value range: 1 to 10. Lines of the device list are restricted by the quantity of PDE. | |||||||||||||||||||||
| ChwPDEConfigEquipId | 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.2 | Unsigned32 (12001..12255) | RO | ||||||||||||||||||
column · Unsigned32 (12001..12255) · read-only · current PDE device ID. Value range: 012'001 to 012'255, in which the first digits indicate the device type and the last three digits indicate the device SN. | |||||||||||||||||||||
| ChwPDEConfigEquipName | 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.3 | OCTET STRING (SIZE (0..64)) | RW | ||||||||||||||||||
column · OCTET STRING (SIZE (0..64)) · read-write · current PDE name, of the character string type, is used to specify PDEs. Users can configure it. Otherwise, the configured character can not be any other languages except English. | |||||||||||||||||||||
| ChwPDEOverTempProtect | 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.4 | Unsigned32 (100..120) | RW | ||||||||||||||||||
column · Unsigned32 (100..120) · read-write · current PDE Over Temperature Protect,Value range: 100 to 120.Unit: deg.
| |||||||||||||||||||||
| ChwPDEVolProtectEnable | 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.5 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current PDE Over Protect Enable,It is an enumeration value, and users actively set it. If the enumeration value is 1, it means to enable the PDE voltage protect; If the enumeration value is 2, it means to disable the PDE voltage protect.
| |||||||||||||||||||||
| ChwPDEOverVoltageProtect | 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.6 | Unsigned32 (58..60) | RW | ||||||||||||||||||
column · Unsigned32 (58..60) · read-write · current PDE Over Voltage Protect,Value range: 58 to 60.Unit: V.
| |||||||||||||||||||||
| ChwPDEUnderVoltageProtect | 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.7 | Unsigned32 (40..48) | RW | ||||||||||||||||||
column · Unsigned32 (40..48) · read-write · current PDE Under Voltage Protect,Value range: 40 to 48.Unit: V.
| |||||||||||||||||||||
| ChwPDEHysteresis | 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.8 | Unsigned32 (1..3) | RW | ||||||||||||||||||
column · Unsigned32 (1..3) · read-write · current PDE Hysteresis,Value range: 1 to 3.Unit: V.
| |||||||||||||||||||||
| ChwPDEReset | 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.9 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current PDE Reset Control,It is an enumeration value, and users actively set it. If the enumeration value is 1, it means to reset the PDE;
| |||||||||||||||||||||
| ChwPDEBranch1Control | 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.10 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current PDE Branch1 Control,It is an enumeration value, and users actively set it. If the enumeration value is 1, it means to open the branch1; If the enumeration value is 2, it means to close the branch1;
| |||||||||||||||||||||
| ChwPDEBranch2Control | 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.11 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current PDE Branch2 Control,It is an enumeration value, and users actively set it. If the enumeration value is 1, it means to open the branch2; If the enumeration value is 2, it means to close the branch2;
| |||||||||||||||||||||
| ChwPDEBranch3Control | 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.12 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current PDE Branch3 Control,It is an enumeration value, and users actively set it. If the enumeration value is 1, it means to open the branch3; If the enumeration value is 2, it means to close the branch3;
| |||||||||||||||||||||
| ChwPDEBranch4Control | 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.13 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current PDE Branch4 Control,It is an enumeration value, and users actively set it. If the enumeration value is 1, it means to open the branch4; If the enumeration value is 2, it means to close the branch4;
| |||||||||||||||||||||
| ChwPDEBranch1CurrentLimit | 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.14 | Unsigned32 (1..20) | RW | ||||||||||||||||||
column · Unsigned32 (1..20) · read-write · current PDE Branch1 Current Limit,Value range: 1 to 20.Unit: A.
| |||||||||||||||||||||
| ChwPDEBranch2CurrentLimit | 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.15 | Unsigned32 (1..30) | RW | ||||||||||||||||||
column · Unsigned32 (1..30) · read-write · current PDE Branch2 Current Limit,Value range: 1 to 30.Unit: A.
| |||||||||||||||||||||
| ChwPDEBranch3CurrentLimit | 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.16 | Unsigned32 (1..30) | RW | ||||||||||||||||||
column · Unsigned32 (1..30) · read-write · current PDE Branch3 Current Limit,Value range: 1 to 30.Unit: A.
| |||||||||||||||||||||
| ChwPDEBranch4CurrentLimit | 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.17 | Unsigned32 (1..20) | RW | ||||||||||||||||||
column · Unsigned32 (1..20) · read-write · current PDE Branch4 Current Limit,Value range: 1 to 20.Unit: A.
| |||||||||||||||||||||
| ChwPDEConfigRowStatus | 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.100 | RowStatus | RC | ||||||||||||||||||
column · RowStatus · read-create · current RowStatus of PDE config table. | |||||||||||||||||||||
| NhwSiteMonitorMIBTraps | 1.3.6.1.4.1.2011.6.164.2 | ||||||||||||||||||||
| NhwSiteAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1 | ||||||||||||||||||||
| NhwSiteAlarmTrapsPrefix | 1.3.6.1.4.1.2011.6.164.2.1.0 | ||||||||||||||||||||
| !hwRectifierFaultAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.1 | ||||||||||||||||||||
notification · current When rectifiers fault alarms happen, a alarm trap will be send. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwRectifierFaultAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.2 | ||||||||||||||||||||
notification · current Rectifier Fault alarm resolved.Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwRectifierAbnormalAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.3 | ||||||||||||||||||||
notification · current Rectifier abnormal alarm, because of communication failure, module protection, or turnoff. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwRectifierAbnormalAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.4 | ||||||||||||||||||||
notification · current Rectifier abnormal alarm resume. Description.Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwBattLoopBreakAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.5 | ||||||||||||||||||||
notification · current Battery loop disconnect. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery string equipment ID and equipment name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwBattLoopBreakAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.6 | ||||||||||||||||||||
notification · current Battery loop break alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery string equipment ID and equipment name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwBattLvdAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.7 | ||||||||||||||||||||
notification · current Battery disconnect for low voltage. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery LVD unit equipment ID and equipment name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwBattLvdAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.8 | ||||||||||||||||||||
notification · current Battery LVD alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery LVD unit equipment ID and equipment name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwBattOverCurrAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.9 | ||||||||||||||||||||
notification · current Batterys charge in over current. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery string equipment ID and equipment name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwBattOverCurrAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.10 | ||||||||||||||||||||
notification · current Batterys over current alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery string equipment ID and equipment name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwBattStringTempAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.11 | ||||||||||||||||||||
notification · current Battery string temperature is too high or too low. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery group ID and group name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwBattStringTempAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.12 | ||||||||||||||||||||
notification · current Battery string temperature alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery group ID and group name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwBattDischargeAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.13 | ||||||||||||||||||||
notification · current Battery group discharge alarm. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery group ID and group name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwBattDischargeAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.14 | ||||||||||||||||||||
notification · current Battery group discharge alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery group ID and group name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwAcInputAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.15 | ||||||||||||||||||||
notification · current AC absent or AC power off alarms happened. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, AC equipment ID and equipment name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwAcInputAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.16 | ||||||||||||||||||||
notification · current AC input alarm resumed. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, AC equipment ID and equipment name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwAcVoltAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.17 | ||||||||||||||||||||
notification · current AC voltage too high or too low. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, AC equipment ID and equipment name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwAcVoltAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.18 | ||||||||||||||||||||
notification · current AC voltage alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, AC equipment ID and equipment name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwDcVoltAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.19 | ||||||||||||||||||||
notification · current DC voltage too high or too low. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, DC equipment ID and equipment name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwDcVoltAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.20 | ||||||||||||||||||||
notification · current DC voltage alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, DC equipment ID and equipment name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwLoadLvdAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.21 | ||||||||||||||||||||
notification · current Loads disconnect for low voltage. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, load LVD unit equipment ID and equipment name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwLoadLvdAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.22 | ||||||||||||||||||||
notification · current Load LVD alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, load LVD unit equipment ID and equipment name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwLoadFuseAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.23 | ||||||||||||||||||||
notification · current Load fuse broken down. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery string equipment ID and equipment name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwLoadFuseAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.24 | ||||||||||||||||||||
notification · current Load fuse alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery string equipment ID and equipment name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwEnvTempAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.25 | ||||||||||||||||||||
notification · current Environment temperature is too high or too low. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, envirenment temperature sensor equipment ID and equipment name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwEnvTempAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.26 | ||||||||||||||||||||
notification · current Environment temperature alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, envirenment temperature sensor equipment ID and equipment name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwEnvHumiAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.27 | ||||||||||||||||||||
notification · current Environment humidity is too high or too low. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, envirenment humidity sensor equipment ID and equipment name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwEnvHumiAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.28 | ||||||||||||||||||||
notification · current Environment humidity alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, envirenment humidity sensor equipment ID and equipment name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwSpareDigitalAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.29 | ||||||||||||||||||||
notification · current Spare digital fault. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, Spare digital equipment ID and equipment name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwSpareDigitalAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.30 | ||||||||||||||||||||
notification · current Spare digital alarm resume.Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, Spare digital equipment ID and equipment name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwDoorAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.31 | ||||||||||||||||||||
notification · current Door open. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, envirenment unit group ID and group name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwDoorAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.32 | ||||||||||||||||||||
notification · current Door alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, envirenment unit group ID and group name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwWaterAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.33 | ||||||||||||||||||||
notification · current Water alarm. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, envirenment unit group ID and group name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwWaterAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.34 | ||||||||||||||||||||
notification · current Water alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, envirenment unit group ID and group name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwSmokeAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.35 | ||||||||||||||||||||
notification · current Site is on fire, which is detected by smoke sensors. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, envirenment unit group ID and group name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwSmokeAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.36 | ||||||||||||||||||||
notification · current Smoke alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, envirenment unit group ID and group name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwWireAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.37 | ||||||||||||||||||||
notification · current Wire alarm.Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, envirenment unit group ID and group name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwWireAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.38 | ||||||||||||||||||||
notification · current Wire alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, envirenment unit group ID and group name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwAcBreakerAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.39 | ||||||||||||||||||||
notification · current AC breaker alarm.Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, AC distribution unit ID and its name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwAcBreakerAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.40 | ||||||||||||||||||||
notification · current AC breaker alarm resume.Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, AC distribution unit ID and its name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwMultiRectFailureAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.41 | ||||||||||||||||||||
notification · current More than one rectifier reported fault alarms in the same time. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, rectifier group ID and group name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwMultiRectFailureAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.42 | ||||||||||||||||||||
notification · current Multi-rectifiers fault alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, rectifier group ID and group name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwRectRedundAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.43 | ||||||||||||||||||||
notification · current Rectifiers work redundantly, in this case that some of rectifiers will going to sleep. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, rectifier group ID and group name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwRectRedundAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.44 | ||||||||||||||||||||
notification · current Rectifiers redundant alarm resume, when the power supply and requirement were in balance. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, rectifier group ID and group name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwBattUnbalanceAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.45 | ||||||||||||||||||||
notification · current Battery works in unbalance state. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery string equipment ID and equipment name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwBattUnbalanceAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.46 | ||||||||||||||||||||
notification · current Battery unbalance alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery string equipment ID and equipment name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwAcFreqFaultAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.47 | ||||||||||||||||||||
notification · current AC frequency is fault. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, AC equipment ID and equipment name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwAcFreqFaultAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.48 | ||||||||||||||||||||
notification · current AC frequency alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, AC equipment ID and equipment name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwXmuSelfFaultAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.49 | ||||||||||||||||||||
notification · current There are some fault in XMU itself. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, monitor equipment ID and equipment name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwXmuSelfFaultAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.50 | ||||||||||||||||||||
notification · current XMU fault alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, monitor equipment ID and equipment name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwRs485CommAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.51 | ||||||||||||||||||||
notification · current RS485 communication of monitors disconnect. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, monitor equipment ID and equipment name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwRs485CommAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.52 | ||||||||||||||||||||
notification · current RS485 communication alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, monitor equipment ID and equipment name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwNetCommAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.53 | ||||||||||||||||||||
notification · current Network communication of monitors disconnect. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, monitor equipment ID and equipment name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwNetCommAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.54 | ||||||||||||||||||||
notification · current Network communication alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, monitor equipment ID and equipment name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwAcOffLongTimeAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.55 | ||||||||||||||||||||
notification · current AC power off for a long time alarms happened. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, AC equipment ID and equipment name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwAcOffLongTimeAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.56 | ||||||||||||||||||||
notification · current AC power off for a long time alarms resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, AC equipment ID and equipment name are also include in VB(variable bondings). | |||||||||||||||||||||
| !hwSpdAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.57 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwSpdAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.58 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwBadBatteryTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.59 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwBadBatteryResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.60 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwLvd2DisconnectingTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.61 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwLvd2DisconnectingResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.62 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwBattHighTempTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.63 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwBattHighTempResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.64 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwBattLowTempTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.65 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwBattLowTempResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.66 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwDcUltraOverVoltageTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.67 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwDcUltraOverVoltageResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.68 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwDcUltraUnderVoltageTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.69 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwDcUltraUnderVoltageResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.70 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwUmiCommFailTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.71 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwUmiCommFailResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.72 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwShortTestFailTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.73 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwShortTestFailResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.74 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwMissingBattTempSensorTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.75 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwMissingBattTempSensorResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.76 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwBattTempSensorFaultTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.77 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwBattTempSensorFaultResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.78 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwAcOverVoltageTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.79 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwAcOverVoltageResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.80 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwAcUnderVoltageTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.81 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwAcUnderVoltageResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.82 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwPDELoadFaultTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.83 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwPDELoadFaultResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.84 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwPDENoResponseTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.85 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwPDENoResponseResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.86 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwPDEFailureTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.87 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwPDEFailureResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.88 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwPDEBr1FailureTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.89 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwPDEBr1FailureResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.90 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwPDEBr2FailureTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.91 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwPDEBr2FailureResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.92 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwPDEBr3FailureTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.93 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwPDEBr3FailureResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.94 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwPDEBr4FailureTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.95 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwPDEBr4FailureResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.96 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwPDEBr1ProtectTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.97 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwPDEBr1ProtectResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.98 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwPDEBr2ProtectTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.99 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwPDEBr2ProtectResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.100 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwPDEBr3ProtectTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.101 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwPDEBr3ProtectResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.102 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwPDEBr4ProtectTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.103 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwPDEBr4ProtectResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.104 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwPDELostTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.105 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| !hwPDELostResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.106 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| NhwSiteDevicesTraps | 1.3.6.1.4.1.2011.6.164.2.2 | ||||||||||||||||||||
| NhwDevicesTrapsPrefix | 1.3.6.1.4.1.2011.6.164.2.2.0 | ||||||||||||||||||||
| !hwRectifiersInslotChange defined twice | 1.3.6.1.4.1.2011.6.164.2.2.0.1 | ||||||||||||||||||||
notification · current When the presence status of a rectifier changes, the node reports an event. Then the NMS adds or deletes the corresponding entry to or from hwRectConfigTable or hwRectOperTable. The bound information includes the site address, site name, site description, and NE identifier. In addition, the ID, name, and status of the rectifier are bound to identify the specific rectifier and its operation type. When an entry is added, the device status is reported as normal (1); when an entry is deleted, the device status is reported as commFail (4). This trap is the unique trigger condition that causes the NMS to add or delete entries to or from hwRectConfigTable or hwRectOperTable. | |||||||||||||||||||||
| !hwBatterysInslotChange defined twice | 1.3.6.1.4.1.2011.6.164.2.2.0.2 | ||||||||||||||||||||
notification · current When the presence status of a battery string changes, the node reports an event. Then the NMS adds or deletes the corresponding entry to or from hwBatttConfigTable or hwBatttOperTable. The bound information includes the site address, site name, site description, and NE identifier. In addition, the ID, name, and status of the battery string are bound to identify the specific battery string and its operation type. When an entry is added, the device status is reported as normal (1); when an entry is deleted, the device status is reported as loopBreak (4). This trap is the unique trigger condition that causes the NMS to add or delete entries to or from hwBatttConfigTable or hwBatttOperTable. | |||||||||||||||||||||
| !hwBattTestRecordsAdd defined twice | 1.3.6.1.4.1.2011.6.164.2.2.0.3 | ||||||||||||||||||||
notification · current After a new discharge test is conducted on a battery group, the node reports an event. The bound information includes the site address, site name, site description, and NE identifier. The NMS needs to add the corresponding entry to the battery test table. The test records are sorted by time in descending order. The battery test table holds a maximum of 10 test records. If the number of test records exceeds 10, the earlier records starting from the last but one record are deleted at a time because the last record is saved permanently. This trap is the unique trigger condition that causes the NMS to add entries from hwBattsTestResultTable. The battery test table allows you only to add entries. | |||||||||||||||||||||
| !hwEnvTempSensInslotChange defined twice | 1.3.6.1.4.1.2011.6.164.2.2.0.4 | ||||||||||||||||||||
notification · current When the presence status of an environment temperature sensor changes, the node reports an event. Then the NMS adds or deletes the corresponding entry to or from hwEvnTempSensorTable. The bound information includes the site address, site name, site description, and NE identifier. In addition, the ID, name, and status of the environment temperature sensor are bound to identify the specific environment temperature sensor and its operation type. When an entry is added, the device status is reported as normal (1); when an entry is deleted, the device status is reported as notInslot (4). This trap is the unique trigger condition that causes the NMS to add or delete entries to or from hwEnvTempSensorTable. | |||||||||||||||||||||
| !hwEnvHumiSensInslotChange defined twice | 1.3.6.1.4.1.2011.6.164.2.2.0.5 | ||||||||||||||||||||
notification · current When the presence status of an environment humidity sensor changes, the trap reports an event. Then the NMS adds or deletes the corresponding entry to or from hwEvnHumiSensorTable. The bound information includes the site address, site name, site description, and NE identifier. In addition, the ID, name, and status of the environment humidity sensor are bound to identify the specific environment humidity sensor and its operation type. When an entry is added, the device status is reported as normal (1); when an entry is deleted, the device status is reported as notInslot (4). This trap is the unique trigger condition that causes the NMS to add or delete entries to or from hwEnvHumiSensorTable. | |||||||||||||||||||||
| !hwPDEsInslotChange defined twice | 1.3.6.1.4.1.2011.6.164.2.2.0.6 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| NhwV101SiteDevicesTraps | 1.3.6.1.4.1.2011.6.164.2.3 | ||||||||||||||||||||
| NhwV101DevicesTrapsPrefix | 1.3.6.1.4.1.2011.6.164.2.3.1 | ||||||||||||||||||||
| !hwRectifiersInslotChange defined twice | 1.3.6.1.4.1.2011.6.164.2.3.1.1 | ||||||||||||||||||||
notification · current When the presence status of a rectifier changes, the node reports an event. Then the NMS adds or deletes the corresponding entry to or from hwRectConfigTable or hwRectOperTable. The bound information includes the site address, site name, site description, and NE identifier. In addition, the ID, name, and status of the rectifier are bound to identify the specific rectifier and its operation type. When an entry is added, the device status is reported as normal (1); when an entry is deleted, the device status is reported as commFail (4). This trap is the unique trigger condition that causes the NMS to add or delete entries to or from hwRectConfigTable or hwRectOperTable. | |||||||||||||||||||||
| !hwBatterysInslotChange defined twice | 1.3.6.1.4.1.2011.6.164.2.3.1.2 | ||||||||||||||||||||
notification · current When the presence status of a battery string changes, the node reports an event. Then the NMS adds or deletes the corresponding entry to or from hwBatttConfigTable or hwBatttOperTable. The bound information includes the site address, site name, site description, and NE identifier. In addition, the ID, name, and status of the battery string are bound to identify the specific battery string and its operation type. When an entry is added, the device status is reported as normal (1); when an entry is deleted, the device status is reported as loopBreak (4). This trap is the unique trigger condition that causes the NMS to add or delete entries to or from hwBatttConfigTable or hwBatttOperTable. | |||||||||||||||||||||
| !hwBattTestRecordsAdd defined twice | 1.3.6.1.4.1.2011.6.164.2.3.1.3 | ||||||||||||||||||||
notification · current After a new discharge test is conducted on a battery group, the node reports an event. The bound information includes the site address, site name, site description, and NE identifier. The NMS needs to add the corresponding entry to the battery test table. The test records are sorted by time in descending order. The battery test table holds a maximum of 10 test records. If the number of test records exceeds 10, the earlier records starting from the last but one record are deleted at a time because the last record is saved permanently. This trap is the unique trigger condition that causes the NMS to add entries from hwBattsTestResultTable. The battery test table allows you only to add entries. | |||||||||||||||||||||
| !hwEnvTempSensInslotChange defined twice | 1.3.6.1.4.1.2011.6.164.2.3.1.4 | ||||||||||||||||||||
notification · current When the presence status of an environment temperature sensor changes, the node reports an event. Then the NMS adds or deletes the corresponding entry to or from hwEvnTempSensorTable. The bound information includes the site address, site name, site description, and NE identifier. In addition, the ID, name, and status of the environment temperature sensor are bound to identify the specific environment temperature sensor and its operation type. When an entry is added, the device status is reported as normal (1); when an entry is deleted, the device status is reported as notInslot (4). This trap is the unique trigger condition that causes the NMS to add or delete entries to or from hwEnvTempSensorTable. | |||||||||||||||||||||
| !hwEnvHumiSensInslotChange defined twice | 1.3.6.1.4.1.2011.6.164.2.3.1.5 | ||||||||||||||||||||
notification · current When the presence status of an environment humidity sensor changes, the trap reports an event. Then the NMS adds or deletes the corresponding entry to or from hwEvnHumiSensorTable. The bound information includes the site address, site name, site description, and NE identifier. In addition, the ID, name, and status of the environment humidity sensor are bound to identify the specific environment humidity sensor and its operation type. When an entry is added, the device status is reported as normal (1); when an entry is deleted, the device status is reported as notInslot (4). This trap is the unique trigger condition that causes the NMS to add or delete entries to or from hwEnvHumiSensorTable. | |||||||||||||||||||||
| !hwPDEsInslotChange defined twice | 1.3.6.1.4.1.2011.6.164.2.3.1.6 | ||||||||||||||||||||
notification · current Description. | |||||||||||||||||||||
| NhwSiteMonitorMIBConformance | 1.3.6.1.4.1.2011.6.164.3 | ||||||||||||||||||||
| NhwSiteMonitorGroups | 1.3.6.1.4.1.2011.6.164.3.1 | ||||||||||||||||||||
| GhwSiteInfoGroup | 1.3.6.1.4.1.2011.6.164.3.1.1 | ||||||||||||||||||||
group · current Site information group. | |||||||||||||||||||||
| GhwSiteMonitorsGroup | 1.3.6.1.4.1.2011.6.164.3.1.2 | ||||||||||||||||||||
group · current Site monitor group.
| |||||||||||||||||||||
| GhwSiteRectifiersGroup | 1.3.6.1.4.1.2011.6.164.3.1.3 | ||||||||||||||||||||
group · current Site rectifier group.
| |||||||||||||||||||||
| GhwSiteBatterysGroup | 1.3.6.1.4.1.2011.6.164.3.1.4 | ||||||||||||||||||||
group · current Site battery group.
| |||||||||||||||||||||
| GhwSiteAcDistributionsGroup | 1.3.6.1.4.1.2011.6.164.3.1.5 | ||||||||||||||||||||
group · current Site AC distribution group.
| |||||||||||||||||||||
| GhwSiteDcDistributionsGroup | 1.3.6.1.4.1.2011.6.164.3.1.6 | ||||||||||||||||||||
group · current Site DC distribution group.
| |||||||||||||||||||||
| GhwSiteLvdUnitsGroup | 1.3.6.1.4.1.2011.6.164.3.1.7 | ||||||||||||||||||||
group · current Site low voltage disconnection unit group. | |||||||||||||||||||||
| GhwSiteEnvUnitsGroup | 1.3.6.1.4.1.2011.6.164.3.1.8 | ||||||||||||||||||||
group · current Site envirenment unit group.
| |||||||||||||||||||||
| GhwSiteAlarmTrapsGroup | 1.3.6.1.4.1.2011.6.164.3.1.9 | ||||||||||||||||||||
group · current Site alarm trap group.
| |||||||||||||||||||||
| GhwSiteDeviceTrapsGroup | 1.3.6.1.4.1.2011.6.164.3.1.10 | ||||||||||||||||||||
group · current Description. | |||||||||||||||||||||
| GhwSiteEfusesGroup | 1.3.6.1.4.1.2011.6.164.3.1.11 | ||||||||||||||||||||
group · current Description.
| |||||||||||||||||||||
Textual conventions
DateAndTimeOCTET STRING (SIZE (8..11))Description.
DisplayStringOCTET STRING (SIZE (1..64))Description.
MeasuresRangeInteger32Description.
RowStatusINTEGERactive(1)createAndGo(4)createAndWait(5)destroy(6)notInService(2)notReady(3)Description.
RunStatusINTEGERalarm(3)normal(2)unknow(1)This integer value represents running status of the system. Depending on situation there may be limits on allowed values. Operational values: (1) unknown - status has not yet been defined (2) normal - there are no activated alarms (3) alarm - alarm status
TruthValueINTEGERflase(2)true(1)Description.
Traps / Notifications
- hwAcBreakerAlarmResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.40 - hwAcBreakerAlarmTraps
1.3.6.1.4.1.2011.6.164.2.1.0.39 - hwAcFreqFaultAlarmResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.48 - hwAcFreqFaultAlarmTraps
1.3.6.1.4.1.2011.6.164.2.1.0.47 - hwAcInputAlarmResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.16 - hwAcInputAlarmTraps
1.3.6.1.4.1.2011.6.164.2.1.0.15 - hwAcOffLongTimeAlarmResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.56 - hwAcOffLongTimeAlarmTraps
1.3.6.1.4.1.2011.6.164.2.1.0.55 - hwAcOverVoltageResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.80 - hwAcOverVoltageTraps
1.3.6.1.4.1.2011.6.164.2.1.0.79 - hwAcUnderVoltageResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.82 - hwAcUnderVoltageTraps
1.3.6.1.4.1.2011.6.164.2.1.0.81 - hwAcVoltAlarmResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.18 - hwAcVoltAlarmTraps
1.3.6.1.4.1.2011.6.164.2.1.0.17 - hwBadBatteryResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.60 - hwBadBatteryTraps
1.3.6.1.4.1.2011.6.164.2.1.0.59 - hwBattDischargeAlarmResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.14 - hwBattDischargeAlarmTraps
1.3.6.1.4.1.2011.6.164.2.1.0.13 - hwBattHighTempResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.64 - hwBattHighTempTraps
1.3.6.1.4.1.2011.6.164.2.1.0.63 - hwBattLoopBreakAlarmResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.6 - hwBattLoopBreakAlarmTraps
1.3.6.1.4.1.2011.6.164.2.1.0.5 - hwBattLowTempResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.66 - hwBattLowTempTraps
1.3.6.1.4.1.2011.6.164.2.1.0.65 - hwBattLvdAlarmResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.8 - hwBattLvdAlarmTraps
1.3.6.1.4.1.2011.6.164.2.1.0.7 - hwBattOverCurrAlarmResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.10 - hwBattOverCurrAlarmTraps
1.3.6.1.4.1.2011.6.164.2.1.0.9 - hwBattStringTempAlarmResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.12 - hwBattStringTempAlarmTraps
1.3.6.1.4.1.2011.6.164.2.1.0.11 - hwBattTempSensorFaultResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.78 - hwBattTempSensorFaultTraps
1.3.6.1.4.1.2011.6.164.2.1.0.77 - hwBattTestRecordsAdd
1.3.6.1.4.1.2011.6.164.2.2.0.3 - hwBattTestRecordsAdd
1.3.6.1.4.1.2011.6.164.2.3.1.3 - hwBattUnbalanceAlarmResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.46 - hwBattUnbalanceAlarmTraps
1.3.6.1.4.1.2011.6.164.2.1.0.45 - hwBatterysInslotChange
1.3.6.1.4.1.2011.6.164.2.2.0.2 - hwBatterysInslotChange
1.3.6.1.4.1.2011.6.164.2.3.1.2 - hwDcUltraOverVoltageResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.68 - hwDcUltraOverVoltageTraps
1.3.6.1.4.1.2011.6.164.2.1.0.67 - hwDcUltraUnderVoltageResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.70 - hwDcUltraUnderVoltageTraps
1.3.6.1.4.1.2011.6.164.2.1.0.69 - hwDcVoltAlarmResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.20 - hwDcVoltAlarmTraps
1.3.6.1.4.1.2011.6.164.2.1.0.19 - hwDoorAlarmResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.32 - hwDoorAlarmTraps
1.3.6.1.4.1.2011.6.164.2.1.0.31 - hwEnvHumiAlarmResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.28 - hwEnvHumiAlarmTraps
1.3.6.1.4.1.2011.6.164.2.1.0.27 - hwEnvHumiSensInslotChange
1.3.6.1.4.1.2011.6.164.2.2.0.5 - hwEnvHumiSensInslotChange
1.3.6.1.4.1.2011.6.164.2.3.1.5 - hwEnvTempAlarmResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.26 - hwEnvTempAlarmTraps
1.3.6.1.4.1.2011.6.164.2.1.0.25 - hwEnvTempSensInslotChange
1.3.6.1.4.1.2011.6.164.2.2.0.4 - hwEnvTempSensInslotChange
1.3.6.1.4.1.2011.6.164.2.3.1.4 - hwLoadFuseAlarmResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.24 - hwLoadFuseAlarmTraps
1.3.6.1.4.1.2011.6.164.2.1.0.23 - hwLoadLvdAlarmResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.22 - hwLoadLvdAlarmTraps
1.3.6.1.4.1.2011.6.164.2.1.0.21 - hwLvd2DisconnectingResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.62 - hwLvd2DisconnectingTraps
1.3.6.1.4.1.2011.6.164.2.1.0.61 - hwMissingBattTempSensorResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.76 - hwMissingBattTempSensorTraps
1.3.6.1.4.1.2011.6.164.2.1.0.75 - hwMultiRectFailureAlarmResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.42 - hwMultiRectFailureAlarmTraps
1.3.6.1.4.1.2011.6.164.2.1.0.41 - hwNetCommAlarmResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.54 - hwNetCommAlarmTraps
1.3.6.1.4.1.2011.6.164.2.1.0.53 - hwPDEBr1FailureResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.90 - hwPDEBr1FailureTraps
1.3.6.1.4.1.2011.6.164.2.1.0.89 - hwPDEBr1ProtectResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.98 - hwPDEBr1ProtectTraps
1.3.6.1.4.1.2011.6.164.2.1.0.97 - hwPDEBr2FailureResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.92 - hwPDEBr2FailureTraps
1.3.6.1.4.1.2011.6.164.2.1.0.91 - hwPDEBr2ProtectResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.100 - hwPDEBr2ProtectTraps
1.3.6.1.4.1.2011.6.164.2.1.0.99 - hwPDEBr3FailureResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.94 - hwPDEBr3FailureTraps
1.3.6.1.4.1.2011.6.164.2.1.0.93 - hwPDEBr3ProtectResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.102 - hwPDEBr3ProtectTraps
1.3.6.1.4.1.2011.6.164.2.1.0.101 - hwPDEBr4FailureResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.96 - hwPDEBr4FailureTraps
1.3.6.1.4.1.2011.6.164.2.1.0.95 - hwPDEBr4ProtectResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.104 - hwPDEBr4ProtectTraps
1.3.6.1.4.1.2011.6.164.2.1.0.103 - hwPDEFailureResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.88 - hwPDEFailureTraps
1.3.6.1.4.1.2011.6.164.2.1.0.87 - hwPDELoadFaultResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.84 - hwPDELoadFaultTraps
1.3.6.1.4.1.2011.6.164.2.1.0.83 - hwPDELostResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.106 - hwPDELostTraps
1.3.6.1.4.1.2011.6.164.2.1.0.105 - hwPDENoResponseResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.86 - hwPDENoResponseTraps
1.3.6.1.4.1.2011.6.164.2.1.0.85 - hwPDEsInslotChange
1.3.6.1.4.1.2011.6.164.2.2.0.6 - hwPDEsInslotChange
1.3.6.1.4.1.2011.6.164.2.3.1.6 - hwRectRedundAlarmResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.44 - hwRectRedundAlarmTraps
1.3.6.1.4.1.2011.6.164.2.1.0.43 - hwRectifierAbnormalAlarmResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.4 - hwRectifierAbnormalAlarmTraps
1.3.6.1.4.1.2011.6.164.2.1.0.3 - hwRectifierFaultAlarmResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.2 - hwRectifierFaultAlarmTraps
1.3.6.1.4.1.2011.6.164.2.1.0.1 - hwRectifiersInslotChange
1.3.6.1.4.1.2011.6.164.2.2.0.1 - hwRectifiersInslotChange
1.3.6.1.4.1.2011.6.164.2.3.1.1 - hwRs485CommAlarmResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.52 - hwRs485CommAlarmTraps
1.3.6.1.4.1.2011.6.164.2.1.0.51 - hwShortTestFailResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.74 - hwShortTestFailTraps
1.3.6.1.4.1.2011.6.164.2.1.0.73 - hwSmokeAlarmResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.36 - hwSmokeAlarmTraps
1.3.6.1.4.1.2011.6.164.2.1.0.35 - hwSpareDigitalAlarmResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.30 - hwSpareDigitalAlarmTraps
1.3.6.1.4.1.2011.6.164.2.1.0.29 - hwSpdAlarmResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.58 - hwSpdAlarmTraps
1.3.6.1.4.1.2011.6.164.2.1.0.57 - hwUmiCommFailResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.72 - hwUmiCommFailTraps
1.3.6.1.4.1.2011.6.164.2.1.0.71 - hwWaterAlarmResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.34 - hwWaterAlarmTraps
1.3.6.1.4.1.2011.6.164.2.1.0.33 - hwWireAlarmResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.38 - hwWireAlarmTraps
1.3.6.1.4.1.2011.6.164.2.1.0.37 - hwXmuSelfFaultAlarmResumeTraps
1.3.6.1.4.1.2011.6.164.2.1.0.50 - hwXmuSelfFaultAlarmTraps
1.3.6.1.4.1.2011.6.164.2.1.0.49