GUDEADS-EPC1202-MIB
Gude Analog- und Digitalsysteme GmbHExpert Power Control 1202 MIB
snmptranslate -m GUDEADS-EPC1202-MIB -Tpsnmpwalk -v2c -c <community> -m GUDEADS-EPC1202-MIB <host> 1.3.6.1.4.1.28507Imports
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP, OBJECT-GROUP |
|---|---|
| SNMPv2-SMI | Bits, Gauge32, Integer32, IpAddress, MODULE-IDENTITY, MibIdentifier, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, TimeTicks, Unsigned32, enterprises, iso |
| SNMPv2-TC | DisplayString, PhysAddress, TEXTUAL-CONVENTION |
OID tree
| Name | OID | Type | Access | Status | Example | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Igudeads | 1.3.6.1.4.1.28507 | ||||||||||||||||
identity Expert Power Control 1202 MIB | |||||||||||||||||
| NgadsEPC1202 | 1.3.6.1.4.1.28507.43 | ||||||||||||||||
| Nepc1202Objects | 1.3.6.1.4.1.28507.43.1 | ||||||||||||||||
| Nepc1202CommonConfig | 1.3.6.1.4.1.28507.43.1.1 | ||||||||||||||||
| Nepc1202SNMPaccess | 1.3.6.1.4.1.28507.43.1.1.1 | ||||||||||||||||
| Sepc1202TrapCtrl | 1.3.6.1.4.1.28507.43.1.1.1.1 | Integer32 (0..3) | RW | ||||||||||||||
scalar · Integer32 (0..3) · read-write · current 0 = off 1 = Ver. 1 2 = Ver. 2c 3 = Ver. 3 | |||||||||||||||||
| Tepc1202TrapIPTable | 1.3.6.1.4.1.28507.43.1.1.1.2 | NA | |||||||||||||||
table · not-accessible · current list of all Trap receiver | |||||||||||||||||
| Repc1202TrapIPEntry | 1.3.6.1.4.1.28507.43.1.1.1.2.1 | NA | |||||||||||||||
row · not-accessible · current an entry containing management informations regarding the list of trap receivers
| |||||||||||||||||
| Cepc1202TrapIPIndex | 1.3.6.1.4.1.28507.43.1.1.1.2.1.1 | Integer32 (1..8) | RO | ||||||||||||||
column · Integer32 (1..8) · read-only · current A unique value, greater than zero, for each receiver slot. | |||||||||||||||||
| Cepc1202TrapAddr | 1.3.6.1.4.1.28507.43.1.1.1.2.1.2 | OCTET STRING (SIZE (0..99)) | RW | ||||||||||||||
column · OCTET STRING (SIZE (0..99)) · read-write · current DNS name or IP address specifying one Trap receiver slot. A port can optionally be specified: 'name:port' An empty string disables this slot. | |||||||||||||||||
| Nepc1202DeviceInfo | 1.3.6.1.4.1.28507.43.1.1.2 | ||||||||||||||||
| Sepc1202ProdName | 1.3.6.1.4.1.28507.43.1.1.2.1 | OCTET STRING | RO | Expert Power Control 1202-1 | |||||||||||||
scalar · OCTET STRING · read-only · current The Product Name of the device. Example values from LibreNMS test devices
| |||||||||||||||||
| Sepc1202FWVersion | 1.3.6.1.4.1.28507.43.1.1.2.2 | OCTET STRING | RO | 1.13.3 | |||||||||||||
scalar · OCTET STRING · read-only · current Firmware Version of the device. Example values from LibreNMS test devices
| |||||||||||||||||
| Sepc1202HostName | 1.3.6.1.4.1.28507.43.1.1.2.3 | OCTET STRING | RO | ||||||||||||||
scalar · OCTET STRING · read-only · current The configured Host Name. | |||||||||||||||||
| Sepc1202PhysAddress | 1.3.6.1.4.1.28507.43.1.1.2.4 | OCTET STRING | RO | ||||||||||||||
scalar · OCTET STRING · read-only · current The MAC address of the device. | |||||||||||||||||
| Sepc1202SerialNumber | 1.3.6.1.4.1.28507.43.1.1.2.5 | Unsigned32 | RO | ||||||||||||||
scalar · Unsigned32 · read-only · current The Serial Number of the device. Not available for all devices. Production start 2026. | |||||||||||||||||
| Nepc1202DeviceConfig | 1.3.6.1.4.1.28507.43.1.2 | ||||||||||||||||
| Nepc1202IntActors | 1.3.6.1.4.1.28507.43.1.3 | ||||||||||||||||
| Nepc1202relayports | 1.3.6.1.4.1.28507.43.1.3.1 | ||||||||||||||||
| Sepc1202portNumber | 1.3.6.1.4.1.28507.43.1.3.1.1 | Integer32 (1..4) | RO | ||||||||||||||
scalar · Integer32 (1..4) · read-only · current The number of Relay Ports | |||||||||||||||||
| Tepc1202portTable | 1.3.6.1.4.1.28507.43.1.3.1.2 | NA | |||||||||||||||
table · not-accessible · current list of all EPC Relay Ports | |||||||||||||||||
| Repc1202portEntry | 1.3.6.1.4.1.28507.43.1.3.1.2.1 | NA | |||||||||||||||
row · not-accessible · current An entry containing management information applicable to a particular relay port.
| |||||||||||||||||
| Cepc1202PortIndex | 1.3.6.1.4.1.28507.43.1.3.1.2.1.1 | Integer32 (1..4) | RO | ||||||||||||||
column · Integer32 (1..4) · read-only · current A unique value, greater than zero, for each Relay Port. | |||||||||||||||||
| Cepc1202PortName | 1.3.6.1.4.1.28507.43.1.3.1.2.1.2 | OCTET STRING (SIZE (0..15)) | RW | ||||||||||||||
column · OCTET STRING (SIZE (0..15)) · read-write · current A textual string containing name of a Relay Port. | |||||||||||||||||
| Cepc1202PortState | 1.3.6.1.4.1.28507.43.1.3.1.2.1.3 | INTEGER | RW | on(1) | |||||||||||||
column · INTEGER · read-write · current current state of a Relay Port
Example values from LibreNMS test devices
| |||||||||||||||||
| Cepc1202PortSwitchCount | 1.3.6.1.4.1.28507.43.1.3.1.2.1.4 | Integer32 | RO | 1 | |||||||||||||
column · Integer32 · read-only · current The total number of switch actions ocurred on a Relay Port. Does not count switch commands which will not switch the ralay state, so just real relay switches are displayed here. Example values from LibreNMS test devices
| |||||||||||||||||
| Cepc1202PortStartupMode | 1.3.6.1.4.1.28507.43.1.3.1.2.1.5 | INTEGER | RW | ||||||||||||||
column · INTEGER · read-write · current set Mode of startup sequence (off, on , remember last state)
| |||||||||||||||||
| Cepc1202PortStartupDelay | 1.3.6.1.4.1.28507.43.1.3.1.2.1.6 | Integer32 | RW | ||||||||||||||
column · Integer32 · read-write · current Delay in sec for startup action
| |||||||||||||||||
| Cepc1202PortRepowerTime | 1.3.6.1.4.1.28507.43.1.3.1.2.1.7 | Integer32 (0..65535) | RW | ||||||||||||||
column · Integer32 (0..65535) · read-write · current Delay in sec for repower port after switching off
| |||||||||||||||||
| Cepc1202PortResetDuration | 1.3.6.1.4.1.28507.43.1.3.1.2.1.8 | Integer32 (0..65535) | RW | ||||||||||||||
column · Integer32 (0..65535) · read-write · current Delay in sec for turning Port on again after Reset action
| |||||||||||||||||
| Nepc1202ExtActors | 1.3.6.1.4.1.28507.43.1.4 | ||||||||||||||||
| Nepc1202IntSensors | 1.3.6.1.4.1.28507.43.1.5 | ||||||||||||||||
| Nepc1202PowerChan | 1.3.6.1.4.1.28507.43.1.5.1 | ||||||||||||||||
| Sepc1202ActivePowerChan | 1.3.6.1.4.1.28507.43.1.5.1.1 | Unsigned32 (1) | RO | ||||||||||||||
scalar · Unsigned32 (1) · read-only · current Number of suppported Power Channels. | |||||||||||||||||
| Tepc1202PowerTable | 1.3.6.1.4.1.28507.43.1.5.1.2 | NA | |||||||||||||||
table · not-accessible · current All available Channel Interfaces. | |||||||||||||||||
| Repc1202PowerEntry | 1.3.6.1.4.1.28507.43.1.5.1.2.1 | NA | |||||||||||||||
row · not-accessible · current An entry containing management information applicable to a particular Power Channel.
| |||||||||||||||||
| Cepc1202PowerIndex | 1.3.6.1.4.1.28507.43.1.5.1.2.1.1 | Integer32 (1) | RO | ||||||||||||||
column · Integer32 (1) · read-only · current Index of Power Channel entries | |||||||||||||||||
| Cepc1202ChanStatus | 1.3.6.1.4.1.28507.43.1.5.1.2.1.2 | Integer32 (0..1) | RO | 1 | |||||||||||||
column · Integer32 (0..1) · read-only · current 0 = data not active, 1 = data valid Example values from LibreNMS test devices
| |||||||||||||||||
| Cepc1202AbsEnergyActive | 1.3.6.1.4.1.28507.43.1.5.1.2.1.3 | Gauge32 | RO | 2020584 | |||||||||||||
column · Gauge32 · read-only · current Absolute Active Energy counter.
Example values from LibreNMS test devices
| |||||||||||||||||
| Cepc1202PowerActive | 1.3.6.1.4.1.28507.43.1.5.1.2.1.4 | Integer32 | RO | 17 | |||||||||||||
column · Integer32 · read-only · current Active Power
Example values from LibreNMS test devices
| |||||||||||||||||
| Cepc1202Current | 1.3.6.1.4.1.28507.43.1.5.1.2.1.5 | Gauge32 | RO | 167 | |||||||||||||
column · Gauge32 · read-only · current Actual Curent on Power Channel.
Example values from LibreNMS test devices
| |||||||||||||||||
| Cepc1202Voltage | 1.3.6.1.4.1.28507.43.1.5.1.2.1.6 | Gauge32 | RO | 227 | |||||||||||||
column · Gauge32 · read-only · current Actual Voltage on Power Channel
Example values from LibreNMS test devices
| |||||||||||||||||
| Cepc1202Frequency | 1.3.6.1.4.1.28507.43.1.5.1.2.1.7 | Gauge32 | RO | 4999 | |||||||||||||
column · Gauge32 · read-only · current Frequency of Power Channel
Example values from LibreNMS test devices
| |||||||||||||||||
| Cepc1202PowerFactor | 1.3.6.1.4.1.28507.43.1.5.1.2.1.8 | Integer32 | RO | 464 | |||||||||||||
column · Integer32 · read-only · current Power Factor of Channel between -1.0 and 1.00
Example values from LibreNMS test devices
| |||||||||||||||||
| Cepc1202Pangle | 1.3.6.1.4.1.28507.43.1.5.1.2.1.9 | Integer32 | RO | ||||||||||||||
column · Integer32 · read-only · current Phase Angle between Voltage and L Line Current between -180.0 and 180.0
| |||||||||||||||||
| Cepc1202PowerApparent | 1.3.6.1.4.1.28507.43.1.5.1.2.1.10 | Integer32 | RO | 38 | |||||||||||||
column · Integer32 · read-only · current L Line Mean Apparent Power
Example values from LibreNMS test devices
| |||||||||||||||||
| Cepc1202PowerReactive | 1.3.6.1.4.1.28507.43.1.5.1.2.1.11 | Integer32 | RO | ||||||||||||||
column · Integer32 · read-only · current L Line Mean Reactive Power
| |||||||||||||||||
| Cepc1202AbsEnergyReactive | 1.3.6.1.4.1.28507.43.1.5.1.2.1.12 | Gauge32 | RO | ||||||||||||||
column · Gauge32 · read-only · current Absolute Reactive Energy counter.
| |||||||||||||||||
| Cepc1202AbsEnergyActiveResettable | 1.3.6.1.4.1.28507.43.1.5.1.2.1.13 | Gauge32 | RW | ||||||||||||||
column · Gauge32 · read-write · current Resettable Absolute Active Energy counter. Writing '0' resets all resettable counter.
| |||||||||||||||||
| Cepc1202AbsEnergyReactiveResettable | 1.3.6.1.4.1.28507.43.1.5.1.2.1.14 | Gauge32 | RO | ||||||||||||||
column · Gauge32 · read-only · current Resettable Absolute Reactive Energy counter.
| |||||||||||||||||
| Cepc1202ResetTime | 1.3.6.1.4.1.28507.43.1.5.1.2.1.15 | Gauge32 | RO | ||||||||||||||
column · Gauge32 · read-only · current Time in seconds since last Energy Counter reset.
| |||||||||||||||||
| Cepc1202ForwEnergyActive | 1.3.6.1.4.1.28507.43.1.5.1.2.1.16 | Gauge32 | RO | ||||||||||||||
column · Gauge32 · read-only · current Forward Active Energy counter.
| |||||||||||||||||
| Cepc1202ForwEnergyReactive | 1.3.6.1.4.1.28507.43.1.5.1.2.1.17 | Gauge32 | RO | ||||||||||||||
column · Gauge32 · read-only · current Forward Reactive Energy counter.
| |||||||||||||||||
| Cepc1202ForwEnergyActiveResettable | 1.3.6.1.4.1.28507.43.1.5.1.2.1.18 | Gauge32 | RO | ||||||||||||||
column · Gauge32 · read-only · current Resettable Forward Active Energy counter.
| |||||||||||||||||
| Cepc1202ForwEnergyReactiveResettable | 1.3.6.1.4.1.28507.43.1.5.1.2.1.19 | Gauge32 | RO | ||||||||||||||
column · Gauge32 · read-only · current Resettable Forward Reactive Energy counter.
| |||||||||||||||||
| Cepc1202RevEnergyActive | 1.3.6.1.4.1.28507.43.1.5.1.2.1.20 | Gauge32 | RO | ||||||||||||||
column · Gauge32 · read-only · current Reverse Active Energy counter.
| |||||||||||||||||
| Cepc1202RevEnergyReactive | 1.3.6.1.4.1.28507.43.1.5.1.2.1.21 | Gauge32 | RO | ||||||||||||||
column · Gauge32 · read-only · current Reverse Reactive Energy counter.
| |||||||||||||||||
| Cepc1202RevEnergyActiveResettable | 1.3.6.1.4.1.28507.43.1.5.1.2.1.22 | Gauge32 | RO | ||||||||||||||
column · Gauge32 · read-only · current Resettable Reverse Active Energy counter.
| |||||||||||||||||
| Cepc1202RevEnergyReactiveResettable | 1.3.6.1.4.1.28507.43.1.5.1.2.1.23 | Gauge32 | RO | ||||||||||||||
column · Gauge32 · read-only · current Resettable Reverse Reactive Energy counter.
| |||||||||||||||||
| Cepc1202LineSensorName | 1.3.6.1.4.1.28507.43.1.5.1.2.1.100 | OCTET STRING (SIZE (0..32)) | RW | ||||||||||||||
column · OCTET STRING (SIZE (0..32)) · read-write · current A textual string containing name of a Line Sensor | |||||||||||||||||
| Tepc1202OVPTable | 1.3.6.1.4.1.28507.43.1.5.2 | NA | |||||||||||||||
table · not-accessible · current Overvoltage Protection Table | |||||||||||||||||
| Repc1202OVPEntry | 1.3.6.1.4.1.28507.43.1.5.2.1 | NA | |||||||||||||||
row · not-accessible · current
| |||||||||||||||||
| Cepc1202OVPIndex | 1.3.6.1.4.1.28507.43.1.5.2.1.1 | Integer32 (1) | RO | ||||||||||||||
| Cepc1202OVPStatus | 1.3.6.1.4.1.28507.43.1.5.2.1.2 | INTEGER | RO | ok(1) | |||||||||||||
column · INTEGER · read-only · current shows the status of the built-in Overvoltage Protection
Example values from LibreNMS test devices
| |||||||||||||||||
| Nepc1202NTPClient | 1.3.6.1.4.1.28507.43.1.5.15 | ||||||||||||||||
| Sepc1202NTPTimeValid | 1.3.6.1.4.1.28507.43.1.5.15.1 | INTEGER | RO | valid(1) | |||||||||||||
scalar · INTEGER · read-only · current Show if valid Time is received
Example values from LibreNMS test devices
| |||||||||||||||||
| Sepc1202NTPUnixTime | 1.3.6.1.4.1.28507.43.1.5.15.2 | Unsigned32 | RO | ||||||||||||||
scalar · Unsigned32 · read-only · current show received NTP time as unixtime (secs since 1 January 1970)
| |||||||||||||||||
| Sepc1202NTPLastValidTimestamp | 1.3.6.1.4.1.28507.43.1.5.15.3 | Unsigned32 | RO | ||||||||||||||
scalar · Unsigned32 · read-only · current show seconds since last valid NTP timestamp received
| |||||||||||||||||
| Nepc1202ExtSensors | 1.3.6.1.4.1.28507.43.1.6 | ||||||||||||||||
| Tepc1202SensorTable | 1.3.6.1.4.1.28507.43.1.6.1 | NA | |||||||||||||||
| Repc1202SensorEntry | 1.3.6.1.4.1.28507.43.1.6.1.1 | NA | |||||||||||||||
row · not-accessible · current
| |||||||||||||||||
| Cepc1202SensorIndex | 1.3.6.1.4.1.28507.43.1.6.1.1.1 | Integer32 (1) | RO | ||||||||||||||
| Cepc1202TempSensor | 1.3.6.1.4.1.28507.43.1.6.1.1.2 | Integer32 | RO | ||||||||||||||
column · Integer32 · read-only · current actual temperature | |||||||||||||||||
| Cepc1202HygroSensor | 1.3.6.1.4.1.28507.43.1.6.1.1.3 | Integer32 | RO | ||||||||||||||
column · Integer32 · read-only · current actual humidity
| |||||||||||||||||
| Cepc1202InputSensor | 1.3.6.1.4.1.28507.43.1.6.1.1.4 | INTEGER | RO | ||||||||||||||
column · INTEGER · read-only · current logical state of input sensor
| |||||||||||||||||
| Cepc1202AirPressure | 1.3.6.1.4.1.28507.43.1.6.1.1.5 | Integer32 | RO | ||||||||||||||
column · Integer32 · read-only · current actual air pressure | |||||||||||||||||
| Cepc1202DewPoint | 1.3.6.1.4.1.28507.43.1.6.1.1.6 | Integer32 | RO | ||||||||||||||
column · Integer32 · read-only · current dew point for actual temperature and humidity | |||||||||||||||||
| Cepc1202DewPointDiff | 1.3.6.1.4.1.28507.43.1.6.1.1.7 | Integer32 | RO | ||||||||||||||
column · Integer32 · read-only · current difference between dew point and actual temperature (Temp - DewPoint) | |||||||||||||||||
| Cepc1202ExtSensorName | 1.3.6.1.4.1.28507.43.1.6.1.1.32 | OCTET STRING (SIZE (0..32)) | RW | ||||||||||||||
column · OCTET STRING (SIZE (0..32)) · read-write · current A textual string containing name of a external Sensor | |||||||||||||||||
| Nepc1202ExtInputs | 1.3.6.1.4.1.28507.43.1.6.2 | ||||||||||||||||
| Sepc1202ExtActiveInputs | 1.3.6.1.4.1.28507.43.1.6.2.1 | Unsigned32 (1..12) | RO | ||||||||||||||
scalar · Unsigned32 (1..12) · read-only · current Number of suppported Input Channels. | |||||||||||||||||
| Tepc1202ExtInputTable | 1.3.6.1.4.1.28507.43.1.6.2.2 | NA | |||||||||||||||
| Repc1202ExtInputEntry | 1.3.6.1.4.1.28507.43.1.6.2.2.1 | NA | |||||||||||||||
row · not-accessible · current
| |||||||||||||||||
| Cepc1202ExtInputIndex | 1.3.6.1.4.1.28507.43.1.6.2.2.1.1 | Unsigned32 | RO | ||||||||||||||
| Cepc1202ExtInput | 1.3.6.1.4.1.28507.43.1.6.2.2.1.2 | INTEGER | RO | ||||||||||||||
column · INTEGER · read-only · current Input state of device
| |||||||||||||||||
| Cepc1202ExtInputToggleCount | 1.3.6.1.4.1.28507.43.1.6.2.2.1.3 | Unsigned32 | RO | ||||||||||||||
column · Unsigned32 · read-only · current Number of times the Input has changed its state. | |||||||||||||||||
| Cepc1202ExtInputName | 1.3.6.1.4.1.28507.43.1.6.2.2.1.32 | OCTET STRING (SIZE (0..32)) | RW | ||||||||||||||
column · OCTET STRING (SIZE (0..32)) · read-write · current A textual string containing name of the Input | |||||||||||||||||
| Cepc1202ExtInputPortNum | 1.3.6.1.4.1.28507.43.1.6.2.2.1.33 | Integer32 | RO | ||||||||||||||
column · Integer32 · read-only · current Number of external Sensor Port when value greater zero, else device built-in Input. | |||||||||||||||||
| Cepc1202ExtInputBlockIndex | 1.3.6.1.4.1.28507.43.1.6.2.2.1.34 | Integer32 | RO | ||||||||||||||
column · Integer32 · read-only · current Either index of device built-in Input, or index of Input in external sensor. | |||||||||||||||||
| Nepc1202Conf | 1.3.6.1.4.1.28507.43.2 | ||||||||||||||||
| Nepc1202Groups | 1.3.6.1.4.1.28507.43.2.1 | ||||||||||||||||
| Gepc1202BasicGroup | 1.3.6.1.4.1.28507.43.2.1.1 | ||||||||||||||||
group · current Basic objects.
| |||||||||||||||||
| Nepc1202Compls | 1.3.6.1.4.1.28507.43.2.2 | ||||||||||||||||
| Gepc1202NotificationGroup | 1.3.6.1.4.1.28507.43.2.2.1 | ||||||||||||||||
| Nevents | 1.3.6.1.4.1.28507.43.3 | ||||||||||||||||
| !epc1202SwitchEvtPort | 1.3.6.1.4.1.28507.43.3.1 | ||||||||||||||||
notification · current Event is triggered when a port is switched | |||||||||||||||||
| !epc1202TempEvtSen | 1.3.6.1.4.1.28507.43.3.2 | ||||||||||||||||
| !epc1202HygroEvtSen | 1.3.6.1.4.1.28507.43.3.3 | ||||||||||||||||
| !epc1202InputEvtSen | 1.3.6.1.4.1.28507.43.3.4 | ||||||||||||||||
notification · current change of logical input sensor state
| |||||||||||||||||
| !epc1202AirPressureEvtSen | 1.3.6.1.4.1.28507.43.3.5 | ||||||||||||||||
| !epc1202DewPtDiffEvtSen | 1.3.6.1.4.1.28507.43.3.6 | ||||||||||||||||
notification · current Dew Point Difference limits exceeded | |||||||||||||||||
| !epc1202OVPEvt | 1.3.6.1.4.1.28507.43.3.7 | ||||||||||||||||
| !epc1202LineAmperageEvt | 1.3.6.1.4.1.28507.43.3.8 | ||||||||||||||||
notification · current Event is triggered when a measured current is crossing the entered limits | |||||||||||||||||
| !epc1202ExtInputEvt | 1.3.6.1.4.1.28507.43.3.25 | ||||||||||||||||
notification · current Change of external sensor input. | |||||||||||||||||
| !epc1202LineVoltageEvt | 1.3.6.1.4.1.28507.43.3.26 | ||||||||||||||||
notification · current Event is triggered when a measured voltage is crossing the entered limits | |||||||||||||||||
| !epc1202LinePowerEvt | 1.3.6.1.4.1.28507.43.3.27 | ||||||||||||||||
notification · current Event is triggered when a measured power is crossing the entered limits | |||||||||||||||||
Traps / Notifications
- epc1202AirPressureEvtSen
1.3.6.1.4.1.28507.43.3.5 - epc1202DewPtDiffEvtSen
1.3.6.1.4.1.28507.43.3.6 - epc1202ExtInputEvt
1.3.6.1.4.1.28507.43.3.25 - epc1202HygroEvtSen
1.3.6.1.4.1.28507.43.3.3 - epc1202InputEvtSen
1.3.6.1.4.1.28507.43.3.4 - epc1202LineAmperageEvt
1.3.6.1.4.1.28507.43.3.8 - epc1202LinePowerEvt
1.3.6.1.4.1.28507.43.3.27 - epc1202LineVoltageEvt
1.3.6.1.4.1.28507.43.3.26 - epc1202OVPEvt
1.3.6.1.4.1.28507.43.3.7 - epc1202SwitchEvtPort
1.3.6.1.4.1.28507.43.3.1 - epc1202TempEvtSen
1.3.6.1.4.1.28507.43.3.2