UPS2-MIB
Enterasys Networks Inc.snmptranslate -m UPS2-MIB -Tpsnmpwalk -v2c -c <community> -m UPS2-MIB <host> 1.3.6.1.4.1.52.4.1.1.10.1Imports
| CTRON-MIB-NAMES | ctUPS |
|---|---|
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
| SNMPv2-SMI | Bits, Integer32, IpAddress, MODULE-IDENTITY, MibIdentifier, OBJECT-IDENTITY, OBJECT-TYPE, TimeTicks, Unsigned32, iso |
| SNMPv2-TC | DisplayString, PhysAddress, TEXTUAL-CONVENTION |
OID tree
| Name | OID | Type | Access | Status |
|---|---|---|---|---|
| NupsSystem | 1.3.6.1.4.1.52.4.1.1.10.1 | |||
| SupsNumUPSs | 1.3.6.1.4.1.52.4.1.1.10.1.1 | INTEGER (0..2) | RO | mandatory |
scalar · INTEGER (0..2) · read-only · mandatory The number of UPSs available. | ||||
| NupsId | 1.3.6.1.4.1.52.4.1.1.10.2 | |||
| TupsIdTable | 1.3.6.1.4.1.52.4.1.1.10.2.1 | NA | mandatory | |
table · not-accessible · mandatory A list of identification table entries. The number of entries is given by the value of upsNumUPSs. | ||||
| RupsIdEntry | 1.3.6.1.4.1.52.4.1.1.10.2.1.1 | NA | mandatory | |
| CupsIndex | 1.3.6.1.4.1.52.4.1.1.10.2.1.1.1 | INTEGER | RO | mandatory |
column · INTEGER · read-only · mandatory A unique value which identifies a particular UPS. | ||||
| CupsName | 1.3.6.1.4.1.52.4.1.1.10.2.1.1.2 | DisplayString (SIZE (0..8)) | RW | mandatory |
column · DisplayString (SIZE (0..8)) · read-write · mandatory The UPS's name. A maximum of 8 characters may be specified. This object is initialized to the UPS's model name. | ||||
| CupsModelType | 1.3.6.1.4.1.52.4.1.1.10.2.1.1.3 | INTEGER | RO | mandatory |
column · INTEGER · read-only · mandatory The UPS's base model type.
| ||||
| CupsFwVersion | 1.3.6.1.4.1.52.4.1.1.10.2.1.1.4 | DisplayString (SIZE (0..8)) | RO | mandatory |
column · DisplayString (SIZE (0..8)) · read-only · mandatory The UPS's firmware version. | ||||
| CupsSerialNumber | 1.3.6.1.4.1.52.4.1.1.10.2.1.1.5 | DisplayString (SIZE (0..16)) | RO | mandatory |
column · DisplayString (SIZE (0..16)) · read-only · mandatory The UPS's serial number as set at the factory. | ||||
| CupsManufDate | 1.3.6.1.4.1.52.4.1.1.10.2.1.1.6 | DisplayString (SIZE (0..8)) | RO | mandatory |
column · DisplayString (SIZE (0..8)) · read-only · mandatory The UPS's date of manufacture in the format mm/dd/yy. | ||||
| NupsBattery | 1.3.6.1.4.1.52.4.1.1.10.3 | |||
| TupsBatteryTable | 1.3.6.1.4.1.52.4.1.1.10.3.1 | NA | mandatory | |
table · not-accessible · mandatory A list of battery table entries. The number of entries is given by the value of upsNumUPSs. | ||||
| RupsBatteryEntry | 1.3.6.1.4.1.52.4.1.1.10.3.1.1 | NA | mandatory | |
| CupsBatteryCapacity | 1.3.6.1.4.1.52.4.1.1.10.3.1.1.1 | INTEGER | RO | mandatory |
column · INTEGER · read-only · mandatory The UPS's remaining battery capacity expressed as a percent of the fully charged condition. The value of this object is the actual percentage * 10 (that is, to determine the actual percentage, divide the value of this object by 10). | ||||
| CupsBatteryVoltage | 1.3.6.1.4.1.52.4.1.1.10.3.1.1.2 | INTEGER | RO | mandatory |
column · INTEGER · read-only · mandatory The UPS's present battery voltage. The value of this object is the actual voltage * 100 (that is, to determine the actual voltage, divide the value of this object by 100). | ||||
| CupsBatteryTest | 1.3.6.1.4.1.52.4.1.1.10.3.1.1.3 | INTEGER | RW | mandatory |
column · INTEGER · read-write · mandatory This object may be written to initiate testing of the UPS's battery packs. Reading this object will always return a 0.
| ||||
| CupsBatteryTestResult | 1.3.6.1.4.1.52.4.1.1.10.3.1.1.4 | INTEGER | RO | mandatory |
column · INTEGER · read-only · mandatory The result of the last battery test performed.
| ||||
| CupsRunTimeCalibration | 1.3.6.1.4.1.52.4.1.1.10.3.1.1.5 | INTEGER | RW | mandatory |
column · INTEGER · read-write · mandatory This object may be written to initiate or terminate the test used to calibrate the returned run time value. This test will only run if battery capacity is 100%. Results of this test can be retrieved by upsEstimatedRunTimeRemaining. Valid values for writing are 1 (initiate test) and 2 (terminate test). In addition, this object may be read to determine whether the test is currently running. Valid values for reading are 3 (test is in progress) and 4 (test is not in progress).
| ||||
| CupsEstimatedRunTimeRemaining | 1.3.6.1.4.1.52.4.1.1.10.3.1.1.6 | INTEGER | RO | mandatory |
column · INTEGER · read-only · mandatory The UPS's estimated remaining run time in minutes. The UPS may be queried when operating in the on-line, bypass, or on-battery modes of operation. The run time estimate is based on available battery capacity and output load. | ||||
| CupsTransferCause | 1.3.6.1.4.1.52.4.1.1.10.3.1.1.7 | INTEGER | RO | mandatory |
column · INTEGER · read-only · mandatory The reason for the most recent transfer to on-battery operation.
| ||||
| CupsBatteryTestTime | 1.3.6.1.4.1.52.4.1.1.10.3.1.1.8 | INTEGER | RW | mandatory |
column · INTEGER · read-write · mandatory The frequency of execution of the UPS's automatic battery test. The test may be run immediately upon startup, upon startup and every 7 days thereafter, upon startup and every 14 days thereafter, or never.
| ||||
| CupsLowBatteryWarning | 1.3.6.1.4.1.52.4.1.1.10.3.1.1.9 | INTEGER | RW | mandatory |
column · INTEGER · read-write · mandatory The interval between activation of the UPS's low battery alarm warnings and shutdown of the UPS.
| ||||
| NupsInput | 1.3.6.1.4.1.52.4.1.1.10.4 | |||
| TupsInputTable | 1.3.6.1.4.1.52.4.1.1.10.4.1 | NA | mandatory | |
table · not-accessible · mandatory A list of input table entries. The number of entries is given by the value of upsNumUPSs. | ||||
| RupsInputEntry | 1.3.6.1.4.1.52.4.1.1.10.4.1.1 | NA | mandatory | |
| CupsInputUtilityVoltage | 1.3.6.1.4.1.52.4.1.1.10.4.1.1.1 | INTEGER | RO | mandatory |
column · INTEGER · read-only · mandatory The UPS's utility voltage version.
| ||||
| CupsInputVoltage | 1.3.6.1.4.1.52.4.1.1.10.4.1.1.2 | INTEGER | RO | mandatory |
column · INTEGER · read-only · mandatory The UPS's measured utility input voltage. The value of this object is the actual voltage * 10 (that is, to determine the actual voltage, divide the value of this object by 10). | ||||
| CupsInputFailureSensitivity | 1.3.6.1.4.1.52.4.1.1.10.4.1.1.3 | INTEGER | RW | mandatory |
column · INTEGER · read-write · mandatory The sensitivity of the UPS to rapid changes in utility voltage (e.g., blackouts, spikes, or notches) or abnormal changes in utility frequency.
| ||||
| CupsInputMaxVoltage | 1.3.6.1.4.1.52.4.1.1.10.4.1.1.4 | INTEGER | RO | mandatory |
column · INTEGER · read-only · mandatory The UPS's maximum input voltage recorded since this object was last read. The value of this object is the actual voltage * 10 (that is, to determine the actual voltage, divide the value of this object by 10). | ||||
| CupsInputMinVoltage | 1.3.6.1.4.1.52.4.1.1.10.4.1.1.5 | INTEGER | RO | mandatory |
column · INTEGER · read-only · mandatory The UPS's minimum input voltage recorded since this object was last read. The value of this object is the actual voltage * 10 (that is, to determine the actual voltage, divide the value of this object by 10). | ||||
| CupsInputFrequency | 1.3.6.1.4.1.52.4.1.1.10.4.1.1.6 | INTEGER | RO | mandatory |
column · INTEGER · read-only · mandatory The UPS's present internal operating frequency in Hz. The value of this object is the actual frequency * 100 (that is, to determine the actual frequency, divide the value of this object by 100). | ||||
| NupsOutput | 1.3.6.1.4.1.52.4.1.1.10.5 | |||
| TupsOutputTable | 1.3.6.1.4.1.52.4.1.1.10.5.1 | NA | mandatory | |
table · not-accessible · mandatory A list of output table entries. The number of entries is given by the value of upsNumUPSs. | ||||
| RupsOutputEntry | 1.3.6.1.4.1.52.4.1.1.10.5.1.1 | NA | mandatory | |
| CupsOutputVoltage | 1.3.6.1.4.1.52.4.1.1.10.5.1.1.1 | INTEGER | RO | mandatory |
column · INTEGER · read-only · mandatory The measured UPS output voltage. The value of this object is the actual voltage * 10 (that is, to determine the actual voltage, divide the value of this object by 10). | ||||
| CupsOutputUtilityVoltage | 1.3.6.1.4.1.52.4.1.1.10.5.1.1.2 | INTEGER | RW | mandatory |
column · INTEGER · read-write · mandatory The UPS's current on-battery output voltage setting (valid for 220/230/240 Vac version UPSs only). For other version UPSs, reading this object will always return a 0 and writing this object will have no effect.
| ||||
| CupsOutputPower | 1.3.6.1.4.1.52.4.1.1.10.5.1.1.3 | INTEGER | RO | mandatory |
column · INTEGER · read-only · mandatory The UPS's output load represented as a percentage of full rated load in Watts. The value of this object is the actual percentage * 10 (that is, to determine the actual percentage, divide the value of this object by 10). | ||||
| NupsStatus | 1.3.6.1.4.1.52.4.1.1.10.6 | |||
| TupsStatusTable | 1.3.6.1.4.1.52.4.1.1.10.6.1 | NA | mandatory | |
table · not-accessible · mandatory A list of status table entries. The number of entries is given by the value of upsNumUPSs. | ||||
| RupsStatusEntry | 1.3.6.1.4.1.52.4.1.1.10.6.1.1 | NA | mandatory | |
| CupsStatusOperational | 1.3.6.1.4.1.52.4.1.1.10.6.1.1.1 | INTEGER | RO | mandatory |
column · INTEGER · read-only · mandatory This object contains 8 bits of information about the current
operational status of the UPS. The bits are encoded as
follows:
BIT 7: 1=replace battery condition
BIT 6: 1=low battery condition
BIT 5: 1=overloaded output condition
BIT 4: 1=on-battery mode of operation
BIT 3: 1=on-line mode of operation
BIT 2: 1=Smart Boost mode of operation (where applicable)
BIT 1: 1=UPS shut down due to low battery, overload,
or `sleep' mode
BIT 0: 1=run time calibration running
Note that bit 0 is the low-order bit. | ||||
| CupsStatusFault | 1.3.6.1.4.1.52.4.1.1.10.6.1.1.2 | INTEGER | RO | mandatory |
column · INTEGER · read-only · mandatory This object contains 8 bits of information about the current
fault conditions of the UPS. The bits are encoded as
follows:
BIT 7: 1=UPS fault - internal temperature has exceeded
nominal limits
BIT 6: 1=UPS fault - bypass relay (where applicable) malfunction
BIT 5: 1=UPS fault - battery charger failure
BIT 4: 1=UPS in shut down mode via `S' command
BIT 3: 1=UPS in `sleep' mode via `@ddd' command
BIT 2: 1=UPS fault - main relay malfunction
BIT 1: 1=UPS unable to transfer to on-battery operation
due to overload
BIT 0: 1=UPS's output unpowered due to low battery shut down
Note that bit 0 is the low-order bit. | ||||
| CupsStatusTemp | 1.3.6.1.4.1.52.4.1.1.10.6.1.1.3 | INTEGER | RO | mandatory |
column · INTEGER · read-only · mandatory The UPS's present internal operating temperature in degrees Fahrenheit. The value of this object is the actual temperature * 10 (that is, to determine the actual temperature, divide the value of this object by 10). | ||||
| NupsConfig | 1.3.6.1.4.1.52.4.1.1.10.7 | |||
| TupsConfigTable | 1.3.6.1.4.1.52.4.1.1.10.7.1 | NA | mandatory | |
table · not-accessible · mandatory A list of configuration table entries. The number of entries is given by the value of upsNumUPSs. | ||||
| RupsConfigEntry | 1.3.6.1.4.1.52.4.1.1.10.7.1.1 | NA | mandatory | |
| CupsConfigAlarm | 1.3.6.1.4.1.52.4.1.1.10.7.1.1.1 | INTEGER | RW | mandatory |
column · INTEGER · read-write · mandatory The UPS's current audible alarm setting. The alarm may be set to activate immediately upon utility failure and for low battery condition, to activate 30 seconds after utility failure and immediately upon low battery condition, to activate upon low battery condition only, or to not activate under any conditions.
| ||||
| CupsConfigRestoreDefaults | 1.3.6.1.4.1.52.4.1.1.10.7.1.1.2 | INTEGER | RW | mandatory |
column · INTEGER · read-write · mandatory This object may be written to force the UPS to restore the factory default settings for most of the UPS's customizable parameters. Reading this object will always return a 0.
| ||||
| NupsExtMeas | 1.3.6.1.4.1.52.4.1.1.10.8 | |||
| TupsExtMeasTable | 1.3.6.1.4.1.52.4.1.1.10.8.1 | NA | mandatory | |
table · not-accessible · mandatory A list of external measurement table entries. The number of entries is the number of available UPSs to which External Measurement Units are attached. | ||||
| RupsExtMeasEntry | 1.3.6.1.4.1.52.4.1.1.10.8.1.1 | NA | mandatory | |
| CupsExtMeasFwVersion | 1.3.6.1.4.1.52.4.1.1.10.8.1.1.1 | DisplayString (SIZE (0..1)) | RO | mandatory |
column · DisplayString (SIZE (0..1)) · read-only · mandatory The External Measurement Unit's firmware version letter. | ||||
| CupsExtMeasTemp | 1.3.6.1.4.1.52.4.1.1.10.8.1.1.2 | INTEGER | RO | mandatory |
column · INTEGER · read-only · mandatory The local ambient temperature in degrees Fahrenheit as measured by the External Measurement Unit. The value of this object is the actual temperature * 100 (that is, to determine the actual temperature, divide the value of this object by 100). | ||||
| CupsExtMeasHumidity | 1.3.6.1.4.1.52.4.1.1.10.8.1.1.3 | INTEGER | RO | mandatory |
column · INTEGER · read-only · mandatory The local ambient relative humidity in percent as measured by the External Measurement Unit. The value of this object is the actual humidity * 10 (that is, to determine the actual humidity, divide the value of this object by 10). | ||||
| CupsExtMeasAlarmStatus | 1.3.6.1.4.1.52.4.1.1.10.8.1.1.4 | INTEGER | RO | mandatory |
column · INTEGER · read-only · mandatory This object contains 8 bits of information about the current alarm status of the External Measurement Unit. The bits are encoded as follows: BIT 7: 1=Upper temperature limit exceeded BIT 6: 1=Lower temperature limit exceeded BIT 5: 1=Upper relative humidity limit exceeded BIT 4: 1=Lower relative humidity limit exceeded BIT 3: 1=Contact input channel #4 alarm state BIT 2: 1=Contact input channel #3 alarm state BIT 1: 1=Contact input channel #2 alarm state BIT 0: 1=Contact input channel #1 alarm state Note that bit 0 is the low-order bit. | ||||
| CupsExtMeasMaxTemp | 1.3.6.1.4.1.52.4.1.1.10.8.1.1.5 | INTEGER | RW | mandatory |
column · INTEGER · read-write · mandatory The upper temperature limit at which an alarm will be sent.
| ||||
| CupsExtMeasMinTemp | 1.3.6.1.4.1.52.4.1.1.10.8.1.1.6 | INTEGER | RW | mandatory |
column · INTEGER · read-write · mandatory The lower temperature limit at which an alarm will be sent.
| ||||
| CupsExtMeasMaxHumidity | 1.3.6.1.4.1.52.4.1.1.10.8.1.1.7 | INTEGER | RW | mandatory |
column · INTEGER · read-write · mandatory The upper humidity limit at which an alarm will be sent.
| ||||
| CupsExtMeasMinHumidity | 1.3.6.1.4.1.52.4.1.1.10.8.1.1.8 | INTEGER | RW | mandatory |
column · INTEGER · read-write · mandatory The lower humidity limit at which an alarm will be sent.
| ||||
| CupsExtMeasContact1AlarmControl | 1.3.6.1.4.1.52.4.1.1.10.8.1.1.9 | INTEGER | RW | mandatory |
column · INTEGER · read-write · mandatory The alarm enable state for the External Measurement Unit's contact input channel #1. If enabled, an alarm will be sent when contact input channel #1 has changed to abnormal state.
| ||||
| CupsExtMeasContact2AlarmControl | 1.3.6.1.4.1.52.4.1.1.10.8.1.1.10 | INTEGER | RW | mandatory |
column · INTEGER · read-write · mandatory The alarm enable state for the External Measurement Unit's contact input channel #2. If enabled, an alarm will be sent when contact input channel #2 has changed to abnormal state.
| ||||
| CupsExtMeasContact3AlarmControl | 1.3.6.1.4.1.52.4.1.1.10.8.1.1.11 | INTEGER | RW | mandatory |
column · INTEGER · read-write · mandatory The alarm enable state for the External Measurement Unit's contact input channel #3. If enabled, an alarm will be sent when contact input channel #3 has changed to abnormal state.
| ||||
| CupsExtMeasContact4AlarmControl | 1.3.6.1.4.1.52.4.1.1.10.8.1.1.12 | INTEGER | RW | mandatory |
column · INTEGER · read-write · mandatory The alarm enable state for the External Measurement Unit's contact input channel #4. If enabled, an alarm will be sent when contact input channel #4 has changed to abnormal state.
| ||||
| CupsExtMeasMaxTempAlarmControl | 1.3.6.1.4.1.52.4.1.1.10.8.1.1.13 | INTEGER | RW | mandatory |
column · INTEGER · read-write · mandatory The alarm enable state for the External Measurement Unit's upper temperature limit. If enabled, an alarm will be sent when the ambient temperature rises above the upper temperature limit.
| ||||
| CupsExtMeasMinTempAlarmControl | 1.3.6.1.4.1.52.4.1.1.10.8.1.1.14 | INTEGER | RW | mandatory |
column · INTEGER · read-write · mandatory The alarm enable state for the External Measurement Unit's lower temperature limit. If enabled, an alarm will be sent when the ambient temperature falls below the lower temperature limit.
| ||||
| CupsExtMeasMaxHumidityAlarmControl | 1.3.6.1.4.1.52.4.1.1.10.8.1.1.15 | INTEGER | RW | mandatory |
column · INTEGER · read-write · mandatory The alarm enable state for the External Measurement Unit's upper humidity limit. If enabled, an alarm will be sent when the ambient relative humidity rises above the upper humidity limit.
| ||||
| CupsExtMeasMinHumidityAlarmControl | 1.3.6.1.4.1.52.4.1.1.10.8.1.1.16 | INTEGER | RW | mandatory |
column · INTEGER · read-write · mandatory The alarm enable state for the External Measurement Unit's lower humidity limit. If enabled, an alarm will be sent when the ambient relative humidity falls below the lower humidity limit.
| ||||
| NupsAddlFuncs | 1.3.6.1.4.1.52.4.1.1.10.9 | |||
| TupsAddlFuncsTable | 1.3.6.1.4.1.52.4.1.1.10.9.1 | NA | mandatory | |
table · not-accessible · mandatory A list of additional functions table entries. The number of entries is the number of available UPSs which are capable of supporting these additional functions. | ||||
| RupsAddlFuncsEntry | 1.3.6.1.4.1.52.4.1.1.10.9.1.1 | NA | mandatory | |
| CupsAddlFuncsNumBatteryPacks | 1.3.6.1.4.1.52.4.1.1.10.9.1.1.1 | INTEGER | RO | mandatory |
column · INTEGER · read-only · mandatory The number of battery pack units connected to the UPS. | ||||
| CupsAddlFuncsNumBadBatteryPacks | 1.3.6.1.4.1.52.4.1.1.10.9.1.1.2 | INTEGER | RO | mandatory |
column · INTEGER · read-only · mandatory The number of bad (faulty) battery pack units connected to the UPS. | ||||
| CupsAddlFuncsOutputCurrent | 1.3.6.1.4.1.52.4.1.1.10.9.1.1.3 | INTEGER | RO | mandatory |
column · INTEGER · read-only · mandatory The true rms load current drawn from the UPS. The value of this object is the actual amperage * 100 (that is, to determine the actual amperage, divide the value of this object by 100). | ||||
| CupsAddlFuncsOutputApparentPower | 1.3.6.1.4.1.52.4.1.1.10.9.1.1.4 | INTEGER | RO | mandatory |
column · INTEGER · read-only · mandatory The UPS's output load represented as a percentage of full rated load in Volt-Amps. The value of this object is the actual percentage * 10 (that is, to determine the actual percentage, divide the value of this object by 10). | ||||
| CupsAddlFuncsStatusOperational | 1.3.6.1.4.1.52.4.1.1.10.9.1.1.5 | INTEGER | RO | mandatory |
column · INTEGER · read-only · mandatory This object contains 8 bits of information about the current
operational status of the UPS. The bits are encoded as
follows:
BIT 7: 1=UPS ready to power load upon return of normal line
or upon user command
BIT 6: 1=UPS ready to power load upon user command
BIT 5: 1=UPS in bypass mode as a result of manual bypass
control
BIT 4: 1=UPS is returning from bypass mode
BIT 3: 1=UPS in bypass mode as a result of UPS-Link or
key command
BIT 2: 1=UPS going to bypass mode as a result of UPS-Link
or key command
BIT 1: 1=not defined
BIT 0: 1=wakeup mode - startup test lasting < 2 sec
Note that bit 0 is the low-order bit. | ||||
| CupsAddlFuncsStatusFault | 1.3.6.1.4.1.52.4.1.1.10.9.1.1.6 | INTEGER | RO | mandatory |
column · INTEGER · read-only · mandatory This object contains 8 bits of information about the current
fault conditions of the UPS. The bits are encoded as
follows:
BIT 7: reserved for future use
BIT 6: reserved for future use
BIT 5: reserved for future use
BIT 4: 1=UPS fault - DC imbalance, UPS in bypass
BIT 3: 1=UPS fault - output voltage select failure, UPS
in bypass
BIT 2: 1=UPS fault - bypass supply failure
BIT 1: 1=UPS fault - Isolation Unit fan failure
BIT 0: 1=UPS fault - Electronics Unit fan failure, UPS
in bypass
Note that bit 0 is the low-order bit. | ||||
| CupsAddlFuncsConfigPassword | 1.3.6.1.4.1.52.4.1.1.10.9.1.1.7 | OCTET STRING | RW | mandatory |
column · OCTET STRING · read-write · mandatory The password that controls access to the UPS's LCD display. A maximum of 4 characters may be entered. | ||||
| CupsAddlFuncsConfigDisable | 1.3.6.1.4.1.52.4.1.1.10.9.1.1.8 | INTEGER | RW | mandatory |
column · INTEGER · read-write · mandatory This object may be written to immediately shut down the UPS, requiring a manual reset. Reading this object will always return a 0.
| ||||
| CupsAddlFuncsConfigBypass | 1.3.6.1.4.1.52.4.1.1.10.9.1.1.9 | INTEGER | RW | mandatory |
column · INTEGER · read-write · mandatory This object may be written to cause the UPS to transfer to or from the bypass mode. Reading this object will always return a 0.
| ||||