ELTEK-DISTRIBUTED-MIB
ELTEK Energy ASBranch overview: Aeongold branch will be 1 AL175 branch will be 2 AL6000 branch will be 3 Internal used branch will be 4 Internal used branch will be 5 OEM Smartpack branch will be 6 ELTEK Common branch will be 7 (SmartPack, MCU, AEON w/WebPower sw V2.x) ELTEK Distributed branch will be 8 (SmartPack w/WebPower sw V3.x) ELTEK Distributed V2 branch will be 9 (SmartPack w/WebPower sw V4.0) ELTEK Distributed V3 branch will be 9 (SmartPack w/WebPower sw V4.1) ELTEK Distributed V4 branch will be 9 (SmartPack w/WebPower sw V4.1, V4.2, V4.3, V4.5 and compack V1.0, V1.01, V1.02, V1.03) ELTEK Distributed V5 branch will be 9 (SmartPack w/WebPower sw V4.1, V4.2, V4.3, V4.5, V4.6) ELTEK Distributed V6 branch will be 9 (SmartPack2 sw V1.1, V1.2, V1.3) ELTEK Distributed V7 branch will be 9 (SmartPack w/WebPower sw V4.1, V4.2, V4.3, V4.5, V4.6, V4.7 and compack V1.04, V1.05) ELTEK Distributed V8 branch will be 9 (SmartPack w/WebPower sw V4.9, V4.10, ComPack V1.04, V1.05, Smartpack2 V1.1, V1.2) ELTEK Distributed V9 branch will be 9 (SmartPack w/WebPower sw V4.11) ELTEK eNexus MIB branch will be 10 (SmartPack2 V2.x, SmartPack S V2.x and Compack V2.x) ELTEK Brasil office will have branch 11 ELTEK BMS-EM MIB will have branch 12 ELTEK TELMEX MIB will have branch 13
snmptranslate -m ELTEK-DISTRIBUTED-MIB -Tpsnmpwalk -v2c -c <community> -m ELTEK-DISTRIBUTED-MIB <host> 1.3.6.1.4.1.12148Imports
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
|---|---|
| SNMPv2-SMI | Bits, Counter32, Integer32, IpAddress, MODULE-IDENTITY, MibIdentifier, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, TimeTicks, Unsigned32, enterprises, iso |
| SNMPv2-TC | DisplayString, PhysAddress, TEXTUAL-CONVENTION |
OID tree
| Name | OID | Type | Access | Status | Example | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Ieltek | 1.3.6.1.4.1.12148 | ||||||||||||||||||||
identity Branch overview: Aeongold branch will be 1 AL175 branch will be 2 AL6000 branch will be 3 Internal used branch will be 4 Internal used branch will be 5 OEM Smartpack branch will be 6 ELTEK Common branch will be 7 (SmartPack, MCU, AEON w/WebPower sw V2.x) ELTEK Distributed branch will be 8 (SmartPack w/WebPower sw V3.x) ELTEK Distributed V2 branch will be 9 (SmartPack w/WebPower sw V4.0) ELTEK Distributed V3 branch will be 9 (SmartPack w/WebPower sw V4.1) ELTEK Distributed V4 branch will be 9 (SmartPack w/WebPower sw V4.1, V4.2, V4.3, V4.5 and compack V1.0, V1.01, V1.02, V1.03) ELTEK Distributed V5 branch will be 9 (SmartPack w/WebPower sw V4.1, V4.2, V4.3, V4.5, V4.6) ELTEK Distributed V6 branch will be 9 (SmartPack2 sw V1.1, V1.2, V1.3) ELTEK Distributed V7 branch will be 9 (SmartPack w/WebPower sw V4.1, V4.2, V4.3, V4.5, V4.6, V4.7 and compack V1.04, V1.05) ELTEK Distributed V8 branch will be 9 (SmartPack w/WebPower sw V4.9, V4.10, ComPack V1.04, V1.05, Smartpack2 V1.1, V1.2) ELTEK Distributed V9 branch will be 9 (SmartPack w/WebPower sw V4.11) ELTEK eNexus MIB branch will be 10 (SmartPack2 V2.x, SmartPack S V2.x and Compack V2.x) ELTEK Brasil office will have branch 11 ELTEK BMS-EM MIB will have branch 12 ELTEK TELMEX MIB will have branch 13 | |||||||||||||||||||||
| NeltekDistributedPlantV9 | 1.3.6.1.4.1.12148.9 | ||||||||||||||||||||
| NcontrolSystem | 1.3.6.1.4.1.12148.9.1 | ||||||||||||||||||||
| NsystemTime | 1.3.6.1.4.1.12148.9.1.1 | ||||||||||||||||||||
| SsystemTimeTime | 1.3.6.1.4.1.12148.9.1.1.1 | DisplayString (SIZE (0..255)) | RO | 2018-09-02,04:08 | |||||||||||||||||
scalar · DisplayString (SIZE (0..255)) · read-only · current The system date and time. Used for event timestamps and logging Example values from LibreNMS test devices
| |||||||||||||||||||||
| SsystemInfoRefresh | 1.3.6.1.4.1.12148.9.1.2 | INTEGER | RW | pushbutton(0) | |||||||||||||||||
scalar · INTEGER · read-write · current This is a push button function that will rebuild all the dynamic SNMP tables. When control units are removed or added this function must be executed to make sure the tables are updated.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SsystemTrapRepeatRate | 1.3.6.1.4.1.12148.9.1.3 | Integer32 (0..1440) | RW | 0 | |||||||||||||||||
scalar · Integer32 (0..1440) · read-write · current This object sets the repeat rate of any active traps, in minutes. Entering 0 (zero) will prevent repeating traps - one trap only will be sent per alarm event. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SsystemSendOffTrap | 1.3.6.1.4.1.12148.9.1.4 | INTEGER | RW | off(0) | |||||||||||||||||
scalar · INTEGER · read-write · current A separate off-trap will be issued when an alarm condition goes off, if this flag is set to 1. Entering 0 (zero) will prevent OFF traps from being transmitted.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SsystemNumOfControlUnits | 1.3.6.1.4.1.12148.9.1.5 | Integer32 (0..8) | RO | 1 | |||||||||||||||||
scalar · Integer32 (0..8) · read-only · current The number of Control units in a distributed system. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SsystemControlUnitIndex | 1.3.6.1.4.1.12148.9.1.6 | Integer32 (0..7) | AN | 0 | |||||||||||||||||
scalar · Integer32 (0..7) · accessible-for-notify · current Index used for navigating in the table for configurable inputs. Example values from LibreNMS test devices
| |||||||||||||||||||||
| TsystemControlUnitTable | 1.3.6.1.4.1.12148.9.1.7 | NA | |||||||||||||||||||
table · not-accessible · current This table contains the status of the programmable inputs. There is one row for each Control unit. | |||||||||||||||||||||
| RsystemControlUnitEntry | 1.3.6.1.4.1.12148.9.1.7.1 | NA | |||||||||||||||||||
row · not-accessible · current | |||||||||||||||||||||
| CinputControlUnitID | 1.3.6.1.4.1.12148.9.1.7.1.1 | Integer32 (1..8) | RO | 1 | |||||||||||||||||
column · Integer32 (1..8) · read-only · current The ID of which Control unit to be read. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputUserConfigurable1 | 1.3.6.1.4.1.12148.9.1.7.1.2 | INTEGER | RO | normal(0) | |||||||||||||||||
column · INTEGER · read-only · current Programmable input status. The description of the input is found in the systemControlUnitInputTable
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputUserConfigurable2 | 1.3.6.1.4.1.12148.9.1.7.1.3 | INTEGER | RO | normal(0) | |||||||||||||||||
column · INTEGER · read-only · current Programmable input status. The description of the input is found in the systemControlUnitInputTable
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputUserConfigurable3 | 1.3.6.1.4.1.12148.9.1.7.1.4 | INTEGER | RO | normal(0) | |||||||||||||||||
column · INTEGER · read-only · current Programmable input status. The description of the input is found in the systemControlUnitInputTable
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputUserConfigurable4 | 1.3.6.1.4.1.12148.9.1.7.1.5 | INTEGER | RO | normal(0) | |||||||||||||||||
column · INTEGER · read-only · current Programmable input status. The description of the input is found in the systemControlUnitInputTable
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputUserConfigurable5 | 1.3.6.1.4.1.12148.9.1.7.1.6 | INTEGER | RO | normal(0) | |||||||||||||||||
column · INTEGER · read-only · current Programmable input status. The description of the input is found in the systemControlUnitInputTable
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputUserConfigurable6 | 1.3.6.1.4.1.12148.9.1.7.1.7 | INTEGER | RO | normal(0) | |||||||||||||||||
column · INTEGER · read-only · current Programmable input status. The description of the input is found in the systemControlUnitInputTable
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputUserConfigurable7 | 1.3.6.1.4.1.12148.9.1.7.1.8 | INTEGER | RO | normal(0) | |||||||||||||||||
column · INTEGER · read-only · current Programmable input status. The description of the input is found in the systemControlUnitInputTable
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputUserConfigurable8 | 1.3.6.1.4.1.12148.9.1.7.1.9 | INTEGER | RO | normal(0) | |||||||||||||||||
column · INTEGER · read-only · current Programmable input status. The description of the input is found in the systemControlUnitInputTable
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputUserConfigurable9 | 1.3.6.1.4.1.12148.9.1.7.1.10 | INTEGER | RO | normal(0) | |||||||||||||||||
column · INTEGER · read-only · current Programmable input status. The description of the input is found in the systemControlUnitInputTable
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputUserConfigurable10 | 1.3.6.1.4.1.12148.9.1.7.1.11 | INTEGER | RO | normal(0) | |||||||||||||||||
column · INTEGER · read-only · current Programmable input status. The description of the input is found in the systemControlUnitInputTable
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SsystemLinkStatus | 1.3.6.1.4.1.12148.9.1.8 | INTEGER | RO | linkup(1) | |||||||||||||||||
scalar · INTEGER · read-only · current A flag showing the status of the serial port used between the HEIDI Webpower adapter or embedded WEB/SNMP card and the Smartpack Control system. If this flag shows status linkdown, the propable cause is that the wrong baudrate is set, which again is likely to happen when booting a brand new board. Execute a 'systemInitiateEEPROM' command to fix. Not applicable for ComPack control unit
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SsystemInitiateEEPROM | 1.3.6.1.4.1.12148.9.1.9 | INTEGER | RW | deprecated | pushbutton(0) | ||||||||||||||||
scalar · INTEGER · read-write · deprecated Pushbutton function that initiates a forced write of default data to the SB70/SB72 eeprom. This function is used for productiontest only. The 3rd party OS used in this application are not able to write default data to EEPROM at boot time. A minimum set of configuration is thus created in RAM. A production test facility must therefore run this command as a part of the production test for the unit to function properly.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SsystemLastDigInput | 1.3.6.1.4.1.12148.9.1.10 | Integer32 (1..10) | AN | ||||||||||||||||||
scalar · Integer32 (1..10) · accessible-for-notify · current The last Prog.Input that generated a trap. Used by Traps only. | |||||||||||||||||||||
| SsystemTrapCounter | 1.3.6.1.4.1.12148.9.1.11 | Counter32 | AN | ||||||||||||||||||
scalar · Counter32 · accessible-for-notify · current The number of times a trap has been repeated.. Only acessible for Traps. | |||||||||||||||||||||
| SsystemHeartBeatTrapRepeatRate | 1.3.6.1.4.1.12148.9.1.12 | Integer32 (0..1440) | RW | 0 | |||||||||||||||||
scalar · Integer32 (0..1440) · read-write · current The repeat rate for the systemHeartBeatTrap. Setting this value to zero will disable the HeartBeatTrap. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SsystemResetManualAlarms | 1.3.6.1.4.1.12148.9.1.13 | INTEGER | RW | pushbutton(0) | |||||||||||||||||
scalar · INTEGER · read-write · current A pushutton that resets all manually resettable alarms in the controlsystem. Alarms that is not manually resettable will not be affected by this.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SsystemControlUnitInputIndex | 1.3.6.1.4.1.12148.9.1.14 | Integer32 (0..7) | AN | 0 | |||||||||||||||||
scalar · Integer32 (0..7) · accessible-for-notify · current Index used for navigating in the table for configurable inputs. Example values from LibreNMS test devices
| |||||||||||||||||||||
| TsystemControlUnitInputTable | 1.3.6.1.4.1.12148.9.1.15 | NA | |||||||||||||||||||
table · not-accessible · current This table contains the description of the programmable inputs. There is one row for each Control unit. Programmable input alarms will have description attached to the traps that explains the alarm. Default description is: ProgInput <Control unit ID>.x | |||||||||||||||||||||
| RsystemControlUnitInputEntry | 1.3.6.1.4.1.12148.9.1.15.1 | NA | |||||||||||||||||||
row · not-accessible · current | |||||||||||||||||||||
| CinputUnitID | 1.3.6.1.4.1.12148.9.1.15.1.1 | Integer32 | RO | 1 | |||||||||||||||||
column · Integer32 · read-only · current The ID of which Control unit to be read. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputUserConfigurableText1 | 1.3.6.1.4.1.12148.9.1.15.1.2 | DisplayString | RO | ProgInput 1.1 | |||||||||||||||||
column · DisplayString · read-only · current Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.1. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputUserConfigurableText2 | 1.3.6.1.4.1.12148.9.1.15.1.3 | DisplayString | RO | ProgInput 1.2 | |||||||||||||||||
column · DisplayString · read-only · current Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.2. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputUserConfigurableText3 | 1.3.6.1.4.1.12148.9.1.15.1.4 | DisplayString | RO | ProgInput 1.3 | |||||||||||||||||
column · DisplayString · read-only · current Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.3. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputUserConfigurableText4 | 1.3.6.1.4.1.12148.9.1.15.1.5 | DisplayString | RO | ProgInput 1.4 | |||||||||||||||||
column · DisplayString · read-only · current Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.4. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputUserConfigurableText5 | 1.3.6.1.4.1.12148.9.1.15.1.6 | DisplayString | RO | ProgInput 1.5 | |||||||||||||||||
column · DisplayString · read-only · current Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.5. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputUserConfigurableText6 | 1.3.6.1.4.1.12148.9.1.15.1.7 | DisplayString | RO | ProgInput 1.6 | |||||||||||||||||
column · DisplayString · read-only · current Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.6. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputUserConfigurableText7 | 1.3.6.1.4.1.12148.9.1.15.1.8 | DisplayString | RO | ProgInput 1.7 | |||||||||||||||||
column · DisplayString · read-only · current Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.7. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputUserConfigurableText8 | 1.3.6.1.4.1.12148.9.1.15.1.9 | DisplayString | RO | ProgInput 1.8 | |||||||||||||||||
column · DisplayString · read-only · current Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.8. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputUserConfigurableText9 | 1.3.6.1.4.1.12148.9.1.15.1.10 | DisplayString | RO | ProgInput 1.9 | |||||||||||||||||
column · DisplayString · read-only · current Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.9. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputUserConfigurableText10 | 1.3.6.1.4.1.12148.9.1.15.1.11 | DisplayString | RO | ProgInput 1.10 | |||||||||||||||||
column · DisplayString · read-only · current Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.10. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SsystemResetCtrlSystem | 1.3.6.1.4.1.12148.9.1.16 | INTEGER | RW | deprecated | pushbutton(0) | ||||||||||||||||
scalar · INTEGER · read-write · deprecated A pushbutton function that resets the control system. Configuration data will be kept.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NioUnits | 1.3.6.1.4.1.12148.9.1.17 | ||||||||||||||||||||
| SioUnitNumberOfUnits | 1.3.6.1.4.1.12148.9.1.17.1 | Integer32 | RO | 0 | |||||||||||||||||
scalar · Integer32 · read-only · current Example values from LibreNMS test devices
| |||||||||||||||||||||
| SioUnitsIndex | 1.3.6.1.4.1.12148.9.1.17.2 | Integer32 (0..13) | AN | 0 | |||||||||||||||||
scalar · Integer32 (0..13) · accessible-for-notify · current Example values from LibreNMS test devices
| |||||||||||||||||||||
| TioUnitsTable | 1.3.6.1.4.1.12148.9.1.17.3 | NA | |||||||||||||||||||
| RioUnitsEntry | 1.3.6.1.4.1.12148.9.1.17.3.1 | NA | |||||||||||||||||||
row · not-accessible · current
| |||||||||||||||||||||
| CioUnitID | 1.3.6.1.4.1.12148.9.1.17.3.1.1 | Integer32 | RO | ||||||||||||||||||
| CioUnitOutDoorTemp1 | 1.3.6.1.4.1.12148.9.1.17.3.1.2 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The measured value of the temperature input. Depending on the global setting in the Control unit, this value will be presented in Celsius or Fahrenheit.
| |||||||||||||||||||||
| CioUnitOutDoorTemp2 | 1.3.6.1.4.1.12148.9.1.17.3.1.3 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The measured value of the temperature input. Depending on the global setting in the Control unit, this value will be presented in Celsius or Fahrenheit.
| |||||||||||||||||||||
| CioUnitFanSpeed1 | 1.3.6.1.4.1.12148.9.1.17.3.1.4 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The speed of the cooling/ circulation fan. The speed is a percentage of max RPM.
| |||||||||||||||||||||
| CioUnitFanSpeedDeltaValue1 | 1.3.6.1.4.1.12148.9.1.17.3.1.5 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The deviation of the cooling/circulation fans speed set value. Is a percentage of the desired value.
| |||||||||||||||||||||
| CioUnitFanSpeed2 | 1.3.6.1.4.1.12148.9.1.17.3.1.6 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The speed of the cooling/ circulation fan. The speed is a percentage of max RPM.
| |||||||||||||||||||||
| CioUnitFanSpeedDeltaValue2 | 1.3.6.1.4.1.12148.9.1.17.3.1.7 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The deviation of the cooling/circulation fans speed set value. Is a percentage of the desired value.
| |||||||||||||||||||||
| CioUnitProgInputText1 | 1.3.6.1.4.1.12148.9.1.17.3.1.8 | DisplayString (SIZE (0..32)) | RO | ||||||||||||||||||
column · DisplayString (SIZE (0..32)) · read-only · current Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <I/Ounit ID>.1 | |||||||||||||||||||||
| CioUnitProgInputStatus1 | 1.3.6.1.4.1.12148.9.1.17.3.1.9 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current Programmable input status.
| |||||||||||||||||||||
| CioUnitProgInputText2 | 1.3.6.1.4.1.12148.9.1.17.3.1.10 | DisplayString (SIZE (0..32)) | RO | ||||||||||||||||||
column · DisplayString (SIZE (0..32)) · read-only · current Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <I/Ounit ID>.2 | |||||||||||||||||||||
| CioUnitProgInputStatus2 | 1.3.6.1.4.1.12148.9.1.17.3.1.11 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current Programmable input status.
| |||||||||||||||||||||
| CioUnitProgInputText3 | 1.3.6.1.4.1.12148.9.1.17.3.1.12 | DisplayString (SIZE (0..32)) | RO | ||||||||||||||||||
column · DisplayString (SIZE (0..32)) · read-only · current Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <I/Ounit ID>.3 | |||||||||||||||||||||
| CioUnitProgInputStatus3 | 1.3.6.1.4.1.12148.9.1.17.3.1.13 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current Programmable input status.
| |||||||||||||||||||||
| CioUnitProgInputText4 | 1.3.6.1.4.1.12148.9.1.17.3.1.14 | DisplayString (SIZE (0..32)) | RO | ||||||||||||||||||
column · DisplayString (SIZE (0..32)) · read-only · current Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <I/Ounit ID>.4 | |||||||||||||||||||||
| CioUnitProgInputStatus4 | 1.3.6.1.4.1.12148.9.1.17.3.1.15 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current Programmable input status.
| |||||||||||||||||||||
| CioUnitProgInputText5 | 1.3.6.1.4.1.12148.9.1.17.3.1.16 | DisplayString (SIZE (0..32)) | RO | ||||||||||||||||||
column · DisplayString (SIZE (0..32)) · read-only · current Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <I/Ounit ID>.5 | |||||||||||||||||||||
| CioUnitProgInputStatus5 | 1.3.6.1.4.1.12148.9.1.17.3.1.17 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current Programmable input status.
| |||||||||||||||||||||
| CioUnitProgInputText6 | 1.3.6.1.4.1.12148.9.1.17.3.1.18 | DisplayString (SIZE (0..32)) | RO | ||||||||||||||||||
column · DisplayString (SIZE (0..32)) · read-only · current Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <I/Ounit ID>.6 | |||||||||||||||||||||
| CioUnitProgInputStatus6 | 1.3.6.1.4.1.12148.9.1.17.3.1.19 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current Programmable input status.
| |||||||||||||||||||||
| CioUnitProgInputValue1 | 1.3.6.1.4.1.12148.9.1.17.3.1.20 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The value read on input.
| |||||||||||||||||||||
| CioUnitProgInputValue2 | 1.3.6.1.4.1.12148.9.1.17.3.1.21 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The value read on input.
| |||||||||||||||||||||
| CioUnitProgInputValue3 | 1.3.6.1.4.1.12148.9.1.17.3.1.22 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The value read on input.
| |||||||||||||||||||||
| CioUnitProgInputValue4 | 1.3.6.1.4.1.12148.9.1.17.3.1.23 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The value read on input.
| |||||||||||||||||||||
| CioUnitProgInputValue5 | 1.3.6.1.4.1.12148.9.1.17.3.1.24 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The value read on input.
| |||||||||||||||||||||
| CioUnitProgInputValue6 | 1.3.6.1.4.1.12148.9.1.17.3.1.25 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The value read on input.
| |||||||||||||||||||||
| SsystemServiceMode | 1.3.6.1.4.1.12148.9.1.18 | INTEGER | RW | deprecated | deactivate(0) | ||||||||||||||||
scalar · INTEGER · read-write · deprecated This is a switch function to activate (1) or deactivate (0) servicemode. Status can also be read. Servicemode prevent the system to operate relays or send traps or mail.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NdcSystem | 1.3.6.1.4.1.12148.9.2 | ||||||||||||||||||||
| NdcPlant | 1.3.6.1.4.1.12148.9.2.1 | ||||||||||||||||||||
| NsystemSiteInfo | 1.3.6.1.4.1.12148.9.2.1.3 | ||||||||||||||||||||
| SsystemSiteInfoCustomer | 1.3.6.1.4.1.12148.9.2.1.3.1 | DisplayString (SIZE (0..32)) | RO | Palvelinpuisto Oy | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · current The Customer name (as stored in the Control Unit). Example values from LibreNMS test devices
| |||||||||||||||||||||
| SsystemSiteInfoLocation | 1.3.6.1.4.1.12148.9.2.1.3.2 | DisplayString (SIZE (0..32)) | RO | Tekniikantie 12, Espoo, Finland | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · current The system/site Location details (as stored in the Control Unit). Example values from LibreNMS test devices
| |||||||||||||||||||||
| SsystemSiteInfoMessage1 | 1.3.6.1.4.1.12148.9.2.1.3.3 | DisplayString (SIZE (0..32)) | RO | | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · current The system/site Info Message record #1 (as stored in the Control Unit). 31 Bytes. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SsystemSiteInfoMessage2 | 1.3.6.1.4.1.12148.9.2.1.3.4 | DisplayString (SIZE (0..32)) | RO | | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · current The system/site Info Message record #2 (as stored in the Control Unit). 31 Bytes. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SsystemSiteInfoInstalledDate | 1.3.6.1.4.1.12148.9.2.1.3.5 | DisplayString (SIZE (0..16)) | RO | 06-06 | |||||||||||||||||
scalar · DisplayString (SIZE (0..16)) · read-only · current The system's Installed Date text string (as stored in the Control Unit) 16bytes. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SsystemSiteInfoControllerType | 1.3.6.1.4.1.12148.9.2.1.3.6 | INTEGER | RO | smartpack(5) | |||||||||||||||||
scalar · INTEGER · read-only · current The system Controller Module currently connected. 0 = AL175 1 = AL4000 (Aeon Gold) 2 = AL6000 3 = AL175OEM 4 = MCU 5 = SmartPack 6 = ComPack
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SsystemSiteInfoSystemSeriaNum | 1.3.6.1.4.1.12148.9.2.1.3.7 | DisplayString (SIZE (0..16)) | RO | 142308329523 | |||||||||||||||||
scalar · DisplayString (SIZE (0..16)) · read-only · current The serial number for the complete system. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SsystemSiteInfoControllerSeriaNum | 1.3.6.1.4.1.12148.9.2.1.3.8 | DisplayString (SIZE (0..16)) | RO | 141371123532 | |||||||||||||||||
scalar · DisplayString (SIZE (0..16)) · read-only · current The serial number for Control unit 1. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SsystemNominalVoltage | 1.3.6.1.4.1.12148.9.2.1.4 | INTEGER | RO | prs48v(0) | |||||||||||||||||
scalar · INTEGER · read-only · current The nominal voltage rating. 24V/48V/60V systems. 0=48V 1=24V 2=Not used 3=Not used 4=60V
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SsystemOperationalStatus | 1.3.6.1.4.1.12148.9.2.2 | INTEGER | RO | floattempcomp(1) | |||||||||||||||||
scalar · INTEGER · read-only · current A summary status showing if the system is testing, boosting, floating etc. 0=Float, voltage regulated 1=Float, temperature comp. regulated; 2=boost 3=battery test
Example values from LibreNMS test devices
| |||||||||||||||||||||
| Nbattery | 1.3.6.1.4.1.12148.9.3 | ||||||||||||||||||||
| SbatteryName | 1.3.6.1.4.1.12148.9.3.1 | DisplayString (SIZE (0..31)) | RO | PowerSafe 12V170FS | |||||||||||||||||
scalar · DisplayString (SIZE (0..31)) · read-only · current A descriptive name of the battery installed in the system. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SbatteryVoltage | 1.3.6.1.4.1.12148.9.3.2 | Integer32 (0..7500) | RO | 5323 | |||||||||||||||||
scalar · Integer32 (0..7500) · read-only · current The measured battery voltage.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SbatteryCurrent | 1.3.6.1.4.1.12148.9.3.3 | Integer32 | RO | 0 | |||||||||||||||||
scalar · Integer32 · read-only · current The measured total battery current. This is the sum of all the enabled shunt measurements in the system. Negative battery current indicates discharging of the batteries. Positive battery current indicates charging of the batteries. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SbatteryTemp | 1.3.6.1.4.1.12148.9.3.4 | Integer32 (0..9999) | RO | 24 | |||||||||||||||||
scalar · Integer32 (0..9999) · read-only · current The highest value of the enabled battery temperature measurements. Depending on the global setting in the Control unit, this value will be presented in Celsius or Fahrenheit.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SbatteryBreakerStatus | 1.3.6.1.4.1.12148.9.3.5 | INTEGER | RO | normal(0) | |||||||||||||||||
scalar · INTEGER · read-only · current The state of the battery fuses/breakers can be either normal(0) or alarm(1).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SbatteryChargeCurrentLimitCtrl | 1.3.6.1.4.1.12148.9.3.6 | INTEGER | RW | disable(0) | |||||||||||||||||
scalar · INTEGER · read-write · current Enable/disable of the battery charge current limitation feature; 0=disable, 1=enable.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SbatteryChargeCurrentLimitValue | 1.3.6.1.4.1.12148.9.3.7 | Integer32 (0..32000) | RW | 100 | |||||||||||||||||
scalar · Integer32 (0..32000) · read-write · current Battery charging current limit value. Used only when AC source is mains feed. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SbatteryTempCompEnable | 1.3.6.1.4.1.12148.9.3.8 | INTEGER | RW | enable(1) | |||||||||||||||||
scalar · INTEGER · read-write · current Enable (0) or Disable (1) of Battery Temperature Compensated output regulation mode
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SbatteryFloatVoltConfig | 1.3.6.1.4.1.12148.9.3.9 | Integer32 (4300..6000) | RW | 5352 | |||||||||||||||||
scalar · Integer32 (4300..6000) · read-write · current The Voltage at which the DC System float charges. Acts as reference voltage when running temperature compensated charging.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SbatteryBoostVoltConfig | 1.3.6.1.4.1.12148.9.3.10 | Integer32 (4300..6000) | RW | 5450 | |||||||||||||||||
scalar · Integer32 (4300..6000) · read-write · current The Voltage at which the DC System boost charges the batteries.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SbatteryHighMajorAlarmVoltageConfig | 1.3.6.1.4.1.12148.9.3.11 | Integer32 | RW | 5700 | |||||||||||||||||
scalar · Integer32 · read-write · current The Major High Battery Voltage alarm limit set voltage
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SbatteryHighMinorAlarmVoltageConfig | 1.3.6.1.4.1.12148.9.3.12 | Integer32 | RW | 5680 | |||||||||||||||||
scalar · Integer32 · read-write · current The Minor High Battery Voltage alarm limit set voltage
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SbatteryLowMajorAlarmVoltageConfig | 1.3.6.1.4.1.12148.9.3.13 | Integer32 | RW | 4630 | |||||||||||||||||
scalar · Integer32 · read-write · current The Major Low Battery Voltage Alarm limit set voltage
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SbatteryLowMinorAlarmVoltageConfig | 1.3.6.1.4.1.12148.9.3.14 | Integer32 | RW | 4700 | |||||||||||||||||
scalar · Integer32 · read-write · current The Minor Low Battery Voltage Alarm limit set voltage
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SbatteryStartManualTest | 1.3.6.1.4.1.12148.9.3.15 | INTEGER | RW | pushbutton(0) | |||||||||||||||||
scalar · INTEGER · read-write · current This pushbutton will start or stop a manual battery test if the system allows it.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SbatteryStartManualBoost | 1.3.6.1.4.1.12148.9.3.16 | INTEGER | RW | pushbutton(0) | |||||||||||||||||
scalar · INTEGER · read-write · current This pushbutton will start or stop a manual battery boost if the system allows it.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NbatteryLVD | 1.3.6.1.4.1.12148.9.3.17 | ||||||||||||||||||||
| SbatteryLVDStatus | 1.3.6.1.4.1.12148.9.3.17.1 | INTEGER | RO | connected(0) | |||||||||||||||||
scalar · INTEGER · read-only · current The Battery Contactor is connected(0), disconnected(1) or disabled(2)
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SbatteryLVDDisconnectVoltage | 1.3.6.1.4.1.12148.9.3.17.2 | Integer32 (0..7200) | RW | 4300 | |||||||||||||||||
scalar · Integer32 (0..7200) · read-write · current The Battery Contactors Disconnect Voltage
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SbatteryLVDConnectVoltage | 1.3.6.1.4.1.12148.9.3.17.3 | Integer32 (0..7200) | RW | 4700 | |||||||||||||||||
scalar · Integer32 (0..7200) · read-write · current The Battery Contactors Reconnect Voltage
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SbatteryBanksNumofBanks | 1.3.6.1.4.1.12148.9.3.18 | Integer32 (1..8) | RO | 1 | |||||||||||||||||
scalar · Integer32 (1..8) · read-only · current The number of Control units that is used to measure battery parameters. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NbatteryBanks | 1.3.6.1.4.1.12148.9.3.19 | ||||||||||||||||||||
| SbatterySymmetryDeltaLimitVoltage | 1.3.6.1.4.1.12148.9.3.19.1 | Integer32 | RW | 150 | |||||||||||||||||
scalar · Integer32 · read-write · current The allowable deviation of the symmetry voltage from the theoretical. Exceeding this value in either direction (+/-) causes an alarm state.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SbatteryBanksIndex | 1.3.6.1.4.1.12148.9.3.19.2 | Integer32 (0..7) | AN | 0 | |||||||||||||||||
scalar · Integer32 (0..7) · accessible-for-notify · current Index used for navigating the rows 1..8 of batteryBanksTable Example values from LibreNMS test devices
| |||||||||||||||||||||
| TbatteryBanksTable | 1.3.6.1.4.1.12148.9.3.19.3 | NA | |||||||||||||||||||
table · not-accessible · current A table of up to 8 battery banks. Each banks may have up to 8 symmetry measuments. | |||||||||||||||||||||
| RbatteryBanksEntry | 1.3.6.1.4.1.12148.9.3.19.3.1 | NA | |||||||||||||||||||
row · not-accessible · current
| |||||||||||||||||||||
| CbatteryBankID | 1.3.6.1.4.1.12148.9.3.19.3.1.1 | Integer32 (1..8) | RO | 1 | |||||||||||||||||
column · Integer32 (1..8) · read-only · current The ID of the selected row in the table. i.e. the battery bank. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CbatteryBanksSymmetry1enable | 1.3.6.1.4.1.12148.9.3.19.3.1.2 | INTEGER | RW | disable(0) | |||||||||||||||||
column · INTEGER · read-write · current Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CbatteryBanksSymmetry1status | 1.3.6.1.4.1.12148.9.3.19.3.1.3 | INTEGER | RO | disabled(3) | |||||||||||||||||
column · INTEGER · read-only · current Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CbatteryBanksSymmetry1deltaVoltage | 1.3.6.1.4.1.12148.9.3.19.3.1.4 | Integer32 | RO | 0 | |||||||||||||||||
column · Integer32 · read-only · current The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CbatteryBanksSymmetry2enable | 1.3.6.1.4.1.12148.9.3.19.3.1.5 | INTEGER | RW | disable(0) | |||||||||||||||||
column · INTEGER · read-write · current Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CbatteryBanksSymmetry2status | 1.3.6.1.4.1.12148.9.3.19.3.1.6 | INTEGER | RO | disabled(3) | |||||||||||||||||
column · INTEGER · read-only · current Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CbatteryBanksSymmetry2deltaVoltage | 1.3.6.1.4.1.12148.9.3.19.3.1.7 | Integer32 | RO | 0 | |||||||||||||||||
column · Integer32 · read-only · current The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CbatteryBanksSymmetry3enable | 1.3.6.1.4.1.12148.9.3.19.3.1.8 | INTEGER | RW | disable(0) | |||||||||||||||||
column · INTEGER · read-write · current Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CbatteryBanksSymmetry3status | 1.3.6.1.4.1.12148.9.3.19.3.1.9 | INTEGER | RO | disabled(3) | |||||||||||||||||
column · INTEGER · read-only · current Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CbatteryBanksSymmetry3deltaVoltage | 1.3.6.1.4.1.12148.9.3.19.3.1.10 | Integer32 | RO | 0 | |||||||||||||||||
column · Integer32 · read-only · current The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CbatteryBanksSymmetry4enable | 1.3.6.1.4.1.12148.9.3.19.3.1.11 | INTEGER | RW | disable(0) | |||||||||||||||||
column · INTEGER · read-write · current Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CbatteryBanksSymmetry4status | 1.3.6.1.4.1.12148.9.3.19.3.1.12 | INTEGER | RO | disabled(3) | |||||||||||||||||
column · INTEGER · read-only · current Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CbatteryBanksSymmetry4deltaVoltage | 1.3.6.1.4.1.12148.9.3.19.3.1.13 | Integer32 | RO | 0 | |||||||||||||||||
column · Integer32 · read-only · current The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CbatteryBanksSymmetry5enable | 1.3.6.1.4.1.12148.9.3.19.3.1.14 | INTEGER | RW | disable(0) | |||||||||||||||||
column · INTEGER · read-write · current Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CbatteryBanksSymmetry5status | 1.3.6.1.4.1.12148.9.3.19.3.1.15 | INTEGER | RO | ok(0) | |||||||||||||||||
column · INTEGER · read-only · current Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CbatteryBanksSymmetry5deltaVoltage | 1.3.6.1.4.1.12148.9.3.19.3.1.16 | Integer32 | RO | 0 | |||||||||||||||||
column · Integer32 · read-only · current The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CbatteryBanksSymmetry6enable | 1.3.6.1.4.1.12148.9.3.19.3.1.17 | INTEGER | RW | disable(0) | |||||||||||||||||
column · INTEGER · read-write · current Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CbatteryBanksSymmetry6status | 1.3.6.1.4.1.12148.9.3.19.3.1.18 | INTEGER | RO | ok(0) | |||||||||||||||||
column · INTEGER · read-only · current Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CbatteryBanksSymmetry6deltaVoltage | 1.3.6.1.4.1.12148.9.3.19.3.1.19 | Integer32 | RO | 0 | |||||||||||||||||
column · Integer32 · read-only · current The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CbatteryBanksSymmetry7enable | 1.3.6.1.4.1.12148.9.3.19.3.1.20 | INTEGER | RW | disable(0) | |||||||||||||||||
column · INTEGER · read-write · current Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CbatteryBanksSymmetry7status | 1.3.6.1.4.1.12148.9.3.19.3.1.21 | INTEGER | RO | ok(0) | |||||||||||||||||
column · INTEGER · read-only · current Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CbatteryBanksSymmetry7deltaVoltage | 1.3.6.1.4.1.12148.9.3.19.3.1.22 | Integer32 | RO | 0 | |||||||||||||||||
column · Integer32 · read-only · current The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CbatteryBanksSymmetry8enable | 1.3.6.1.4.1.12148.9.3.19.3.1.23 | INTEGER | RW | disable(0) | |||||||||||||||||
column · INTEGER · read-write · current Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CbatteryBanksSymmetry8status | 1.3.6.1.4.1.12148.9.3.19.3.1.24 | INTEGER | RO | ok(0) | |||||||||||||||||
column · INTEGER · read-only · current Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CbatteryBanksSymmetry8deltaVoltage | 1.3.6.1.4.1.12148.9.3.19.3.1.25 | Integer32 | RO | 0 | |||||||||||||||||
column · Integer32 · read-only · current The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SbatteryBanksNumberOfStrings | 1.3.6.1.4.1.12148.9.3.19.4 | Integer32 | RO | 2 | |||||||||||||||||
scalar · Integer32 · read-only · current Number of strings in the power system. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SbatteryBanksExtensionIndex | 1.3.6.1.4.1.12148.9.3.19.5 | Integer32 (0..7) | AN | 0 | |||||||||||||||||
scalar · Integer32 (0..7) · accessible-for-notify · current Index used for navigating the rows 1..14 of batteryBanksExtensionTable Example values from LibreNMS test devices
| |||||||||||||||||||||
| TbatteryBanksExtensionTable | 1.3.6.1.4.1.12148.9.3.19.6 | NA | |||||||||||||||||||
table · not-accessible · current This table shows the measured value on the symmetry inputs. | |||||||||||||||||||||
| RbatteryBanksExtensionEntry | 1.3.6.1.4.1.12148.9.3.19.6.1 | NA | |||||||||||||||||||
row · not-accessible · current | |||||||||||||||||||||
| CbatteryBanksExtensionID | 1.3.6.1.4.1.12148.9.3.19.6.1.1 | Integer32 | RO | 1 | |||||||||||||||||
column · Integer32 · read-only · current The ID of the selected row in the table. i.e. the battery bank. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CbatteryBanksExtensionSymmetryInputValue1 | 1.3.6.1.4.1.12148.9.3.19.6.1.2 | Integer32 | RO | 0 | |||||||||||||||||
column · Integer32 · read-only · current The measured voltage on the symmetry input.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CbatteryBanksExtensionSymmetryInputValue2 | 1.3.6.1.4.1.12148.9.3.19.6.1.3 | Integer32 | RO | 0 | |||||||||||||||||
column · Integer32 · read-only · current The measured voltage on the symmetry input.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CbatteryBanksExtensionSymmetryInputValue3 | 1.3.6.1.4.1.12148.9.3.19.6.1.4 | Integer32 | RO | 1012 | |||||||||||||||||
column · Integer32 · read-only · current The measured voltage on the symmetry input.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CbatteryBanksExtensionSymmetryInputValue4 | 1.3.6.1.4.1.12148.9.3.19.6.1.5 | Integer32 | RO | 1012 | |||||||||||||||||
column · Integer32 · read-only · current The measured voltage on the symmetry input.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CbatteryBanksExtensionSymmetryInputValue5 | 1.3.6.1.4.1.12148.9.3.19.6.1.6 | Integer32 | RO | 0 | |||||||||||||||||
column · Integer32 · read-only · current The measured voltage on the symmetry input.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CbatteryBanksExtensionSymmetryInputValue6 | 1.3.6.1.4.1.12148.9.3.19.6.1.7 | Integer32 | RO | 0 | |||||||||||||||||
column · Integer32 · read-only · current The measured voltage on the symmetry input.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CbatteryBanksExtensionSymmetryInputValue7 | 1.3.6.1.4.1.12148.9.3.19.6.1.8 | Integer32 | RO | 0 | |||||||||||||||||
column · Integer32 · read-only · current The measured voltage on the symmetry input.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CbatteryBanksExtensionSymmetryInputValue8 | 1.3.6.1.4.1.12148.9.3.19.6.1.9 | Integer32 | RO | 0 | |||||||||||||||||
column · Integer32 · read-only · current The measured voltage on the symmetry input.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NbatteryCapacityData | 1.3.6.1.4.1.12148.9.3.20 | ||||||||||||||||||||
| SbatteryTimeToDisconnect | 1.3.6.1.4.1.12148.9.3.20.1 | Integer32 | RO | 1406 | |||||||||||||||||
scalar · Integer32 · read-only · current Remaining time to low voltage battery disconnect.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SbatteryCapacityLeft | 1.3.6.1.4.1.12148.9.3.20.2 | Integer32 | RO | 1360 | |||||||||||||||||
scalar · Integer32 · read-only · current Capacity left in the battery.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SbatteryCapacityUsed | 1.3.6.1.4.1.12148.9.3.20.3 | Integer32 | RO | 0 | |||||||||||||||||
scalar · Integer32 · read-only · current Capacity consumed.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SbatteryCapacityTotal | 1.3.6.1.4.1.12148.9.3.20.4 | Integer32 | RO | 1360 | |||||||||||||||||
scalar · Integer32 · read-only · current This is the total Capacity of the battery. This value is the installed capacity compensated with the last battery tests quality level
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SbatteryQuality | 1.3.6.1.4.1.12148.9.3.20.5 | Integer32 | RO | 0 | |||||||||||||||||
scalar · Integer32 · read-only · current This is the battery quality (%) of the latest battery test.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NbatteryMonitorUnits | 1.3.6.1.4.1.12148.9.3.21 | ||||||||||||||||||||
| SbattmonNumberOfUnits | 1.3.6.1.4.1.12148.9.3.21.1 | Integer32 | RO | 0 | |||||||||||||||||
scalar · Integer32 · read-only · current Number of battery monitor units in the power system. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SbattmonUnitsIndex | 1.3.6.1.4.1.12148.9.3.21.2 | Integer32 | AN | 0 | |||||||||||||||||
scalar · Integer32 · accessible-for-notify · current Index used for navigating the rows 1..14 of battmonUnitsTable Example values from LibreNMS test devices
| |||||||||||||||||||||
| TbattmonUnitsTable | 1.3.6.1.4.1.12148.9.3.21.3 | NA | |||||||||||||||||||
table · not-accessible · current A table of up to 14 battery monitor control units. | |||||||||||||||||||||
| RbattmonUnitsEntry | 1.3.6.1.4.1.12148.9.3.21.3.1 | NA | |||||||||||||||||||
row · not-accessible · current
| |||||||||||||||||||||
| CbatteryMonitorID | 1.3.6.1.4.1.12148.9.3.21.3.1.1 | Integer32 (1..14) | RO | 1 | |||||||||||||||||
column · Integer32 (1..14) · read-only · current The ID of the selected row Example values from LibreNMS test devices
| |||||||||||||||||||||
| CbatteryMonitorSymmetry1status | 1.3.6.1.4.1.12148.9.3.21.3.1.2 | INTEGER | RO | ok(0) | |||||||||||||||||
column · INTEGER · read-only · current Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CbatteryMonitorSymmetry1InputValue | 1.3.6.1.4.1.12148.9.3.21.3.1.3 | Integer32 | RO | 0 | |||||||||||||||||
column · Integer32 · read-only · current The measured voltage on the symmetry input.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CbatteryMonitorSymmetry2status | 1.3.6.1.4.1.12148.9.3.21.3.1.4 | INTEGER | RO | ok(0) | |||||||||||||||||
column · INTEGER · read-only · current Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CbatteryMonitorSymmetry2InputValue | 1.3.6.1.4.1.12148.9.3.21.3.1.5 | Integer32 | RO | 0 | |||||||||||||||||
column · Integer32 · read-only · current The measured voltage on the symmetry input.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CbatteryMonitorSymmetry3status | 1.3.6.1.4.1.12148.9.3.21.3.1.6 | INTEGER | RO | ok(0) | |||||||||||||||||
column · INTEGER · read-only · current Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CbatteryMonitorSymmetry3InputValue | 1.3.6.1.4.1.12148.9.3.21.3.1.7 | Integer32 | RO | 0 | |||||||||||||||||
column · Integer32 · read-only · current The measured voltage on the symmetry input.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CbatteryMonitorSymmetry4status | 1.3.6.1.4.1.12148.9.3.21.3.1.8 | INTEGER | RO | ok(0) | |||||||||||||||||
column · INTEGER · read-only · current Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CbatteryMonitorSymmetry4InputValue | 1.3.6.1.4.1.12148.9.3.21.3.1.9 | Integer32 | RO | 0 | |||||||||||||||||
column · Integer32 · read-only · current The measured voltage on the symmetry input.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CbatteryMonitorCurrentValue | 1.3.6.1.4.1.12148.9.3.21.3.1.10 | Integer32 | RO | 0 | |||||||||||||||||
column · Integer32 · read-only · current The measured current to/from the battery. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CbatteryMonitorFuseStatus | 1.3.6.1.4.1.12148.9.3.21.3.1.11 | INTEGER | RO | alarm(1) | |||||||||||||||||
column · INTEGER · read-only · current The state of the battery fuse/breaker can be either normal(0) or alarm(1).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CbatteryMonitorTemperature | 1.3.6.1.4.1.12148.9.3.21.3.1.12 | Integer32 | RO | 0 | |||||||||||||||||
column · Integer32 · read-only · current The battery temperature.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SbatteryHighMajorTempAlarmLevel | 1.3.6.1.4.1.12148.9.3.22 | Integer32 | RW | 40 | |||||||||||||||||
scalar · Integer32 · read-write · current This is the Major High Temperature Alarm level.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SbatteryHighMinorTempAlarmLevel | 1.3.6.1.4.1.12148.9.3.23 | Integer32 | RW | 30 | |||||||||||||||||
scalar · Integer32 · read-write · current This is the Minor High Temperature Alarm level.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NbatteryTest | 1.3.6.1.4.1.12148.9.3.24 | ||||||||||||||||||||
| SbatteryTestEndVoltage | 1.3.6.1.4.1.12148.9.3.24.1 | Integer32 | RW | 190 | |||||||||||||||||
scalar · Integer32 · read-write · current The end voltage for standard battery test (V/cell) 1/100 Volt; i.e. 190 = 1.90V
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SbatteryTestMaximumDischargeTime | 1.3.6.1.4.1.12148.9.3.24.2 | Integer32 | RW | 720 | |||||||||||||||||
scalar · Integer32 · read-write · current The maximum allowed run time for the battery test (Minutes)
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SbatteryTestMaximumDischargeAh | 1.3.6.1.4.1.12148.9.3.24.3 | Integer32 | RW | 100 | |||||||||||||||||
scalar · Integer32 · read-write · current The maximum allowed discharge for the batteries during a battery test (Ah)
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NloadDistribution | 1.3.6.1.4.1.12148.9.4 | ||||||||||||||||||||
| SloadDistributionCurrent | 1.3.6.1.4.1.12148.9.4.1 | Integer32 | RO | 58 | |||||||||||||||||
scalar · Integer32 · read-only · current The total load current Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SloadDistributionBreakerStatus | 1.3.6.1.4.1.12148.9.4.2 | INTEGER | RO | normal(0) | |||||||||||||||||
scalar · INTEGER · read-only · current The state of the load fuses/breakers can be either normal(0) or alarm(1)
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NloadDistributionLVDStatus | 1.3.6.1.4.1.12148.9.4.3 | ||||||||||||||||||||
| SloadLVD1Enable | 1.3.6.1.4.1.12148.9.4.3.1 | INTEGER | RO | enabled(1) | |||||||||||||||||
scalar · INTEGER · read-only · current The status of contactors configuration. 'enabled' means that the contactor is in use. 'disabled' means that the contactor is disconfigured and not in use.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SloadLVD1Status | 1.3.6.1.4.1.12148.9.4.3.2 | INTEGER | RO | connected(0) | |||||||||||||||||
scalar · INTEGER · read-only · current The load Contactor 1 is connected(0), disconnected(1) or disabled(2)
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SloadLVD1ConnectVoltage | 1.3.6.1.4.1.12148.9.4.3.3 | Integer32 (0..7200) | RW | 4800 | |||||||||||||||||
scalar · Integer32 (0..7200) · read-write · current LVLD1 Connect Voltage
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SloadLVD1DisconnectVoltage | 1.3.6.1.4.1.12148.9.4.3.4 | Integer32 (0..7200) | RW | 4400 | |||||||||||||||||
scalar · Integer32 (0..7200) · read-write · current LVLD1 Disconnect Voltage
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SloadLVD2Enable | 1.3.6.1.4.1.12148.9.4.3.5 | INTEGER | RO | disabled(0) | |||||||||||||||||
scalar · INTEGER · read-only · current The status of contactors configuration. 'enabled' means that the contactor is in use. 'disabled' means that the contactor is disconfigured and not in use.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SloadLVD2Status | 1.3.6.1.4.1.12148.9.4.3.6 | INTEGER | RO | disabled(2) | |||||||||||||||||
scalar · INTEGER · read-only · current The load Contactor 2 is connected(0), disconnected(1) or disabled(2)
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SloadLVD2ConnectVoltage | 1.3.6.1.4.1.12148.9.4.3.7 | Integer32 (0..7200) | RW | 4800 | |||||||||||||||||
scalar · Integer32 (0..7200) · read-write · current LVLD2 Connect Voltage
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SloadLVD2DisconnectVoltage | 1.3.6.1.4.1.12148.9.4.3.8 | Integer32 (0..7200) | RW | 4400 | |||||||||||||||||
scalar · Integer32 (0..7200) · read-write · current LVLD2 Disconnect Voltage
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SloadLVD3Enable | 1.3.6.1.4.1.12148.9.4.3.9 | INTEGER | RO | disabled(0) | |||||||||||||||||
scalar · INTEGER · read-only · current The status of contactors configuration. 'enabled' means that the contactor is in use. 'disabled' means that the contactor is disconfigured and not in use.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SloadLVD3Status | 1.3.6.1.4.1.12148.9.4.3.10 | INTEGER | RO | disabled(2) | |||||||||||||||||
scalar · INTEGER · read-only · current The load Contactor 3 is connected(0), disconnected(1) or disabled(2)
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SloadLVD3ConnectVoltage | 1.3.6.1.4.1.12148.9.4.3.11 | Integer32 (0..7200) | RW | 4800 | |||||||||||||||||
scalar · Integer32 (0..7200) · read-write · current LVLD3 Connect Voltage
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SloadLVD3DisconnectVoltage | 1.3.6.1.4.1.12148.9.4.3.12 | Integer32 (0..7200) | RW | 4400 | |||||||||||||||||
scalar · Integer32 (0..7200) · read-write · current LVLD3 Disconnect Voltage
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NloadMonitorUnits | 1.3.6.1.4.1.12148.9.4.4 | ||||||||||||||||||||
| SloadmonitorNumberOfUnits | 1.3.6.1.4.1.12148.9.4.4.1 | Integer32 | RO | 0 | |||||||||||||||||
scalar · Integer32 · read-only · current Example values from LibreNMS test devices
| |||||||||||||||||||||
| SloadMonitorUnitsIndex | 1.3.6.1.4.1.12148.9.4.4.2 | Integer32 (0..13) | AN | 0 | |||||||||||||||||
scalar · Integer32 (0..13) · accessible-for-notify · current Example values from LibreNMS test devices
| |||||||||||||||||||||
| TloadMonitorUnitsTable | 1.3.6.1.4.1.12148.9.4.4.3 | NA | |||||||||||||||||||
| RloadMonitorUnitsEntry | 1.3.6.1.4.1.12148.9.4.4.3.1 | NA | |||||||||||||||||||
row · not-accessible · current | |||||||||||||||||||||
| CloadMonitorID | 1.3.6.1.4.1.12148.9.4.4.3.1.1 | Integer32 | RO | ||||||||||||||||||
| CloadMonitorFuseStatus1 | 1.3.6.1.4.1.12148.9.4.4.3.1.2 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current The state of the load fuses/breakers can be either normal(0) or alarm(1)
| |||||||||||||||||||||
| CloadMonitorCurrent1 | 1.3.6.1.4.1.12148.9.4.4.3.1.3 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
| |||||||||||||||||||||
| CloadMonitorFuseStatus2 | 1.3.6.1.4.1.12148.9.4.4.3.1.4 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current The state of the load fuses/breakers can be either normal(0) or alarm(1)
| |||||||||||||||||||||
| CloadMonitorCurrent2 | 1.3.6.1.4.1.12148.9.4.4.3.1.5 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
| |||||||||||||||||||||
| CloadMonitorFuseStatus3 | 1.3.6.1.4.1.12148.9.4.4.3.1.6 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current The state of the load fuses/breakers can be either normal(0) or alarm(1)
| |||||||||||||||||||||
| CloadMonitorCurrent3 | 1.3.6.1.4.1.12148.9.4.4.3.1.7 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
| |||||||||||||||||||||
| CloadMonitorFuseStatus4 | 1.3.6.1.4.1.12148.9.4.4.3.1.8 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current The state of the load fuses/breakers can be either normal(0) or alarm(1)
| |||||||||||||||||||||
| CloadMonitorCurrent4 | 1.3.6.1.4.1.12148.9.4.4.3.1.9 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
| |||||||||||||||||||||
| CloadMonitorFuseStatus5 | 1.3.6.1.4.1.12148.9.4.4.3.1.10 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current The state of the load fuses/breakers can be either normal(0) or alarm(1)
| |||||||||||||||||||||
| CloadMonitorCurrent5 | 1.3.6.1.4.1.12148.9.4.4.3.1.11 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
| |||||||||||||||||||||
| CloadMonitorFuseStatus6 | 1.3.6.1.4.1.12148.9.4.4.3.1.12 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current The state of the load fuses/breakers can be either normal(0) or alarm(1)
| |||||||||||||||||||||
| CloadMonitorCurrent6 | 1.3.6.1.4.1.12148.9.4.4.3.1.13 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
| |||||||||||||||||||||
| CloadMonitorFuseStatus7 | 1.3.6.1.4.1.12148.9.4.4.3.1.14 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current The state of the load fuses/breakers can be either normal(0) or alarm(1)
| |||||||||||||||||||||
| CloadMonitorCurrent7 | 1.3.6.1.4.1.12148.9.4.4.3.1.15 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
| |||||||||||||||||||||
| CloadMonitorFuseStatus8 | 1.3.6.1.4.1.12148.9.4.4.3.1.16 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current The state of the load fuses/breakers can be either normal(0) or alarm(1)
| |||||||||||||||||||||
| CloadMonitorCurrent8 | 1.3.6.1.4.1.12148.9.4.4.3.1.17 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings
| |||||||||||||||||||||
| Nrectifier | 1.3.6.1.4.1.12148.9.5 | ||||||||||||||||||||
| SrectifierInstalledRectifiers | 1.3.6.1.4.1.12148.9.5.1 | Integer32 (1..101) | RO | 3 | |||||||||||||||||
scalar · Integer32 (1..101) · read-only · current The number of installed rectifiers for this DC Power System. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SrectifierRectifiersActive | 1.3.6.1.4.1.12148.9.5.2 | Integer32 (1..101) | RO | 3 | |||||||||||||||||
scalar · Integer32 (1..101) · read-only · current Not Used! Example values from LibreNMS test devices
| |||||||||||||||||||||
| SrectifierTotalCurrent | 1.3.6.1.4.1.12148.9.5.3 | Integer32 | RO | 58 | |||||||||||||||||
scalar · Integer32 · read-only · current The DC system's total delivered rectifier current
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SrectifierUtilization | 1.3.6.1.4.1.12148.9.5.4 | Integer32 (0..100) | RO | 46 | |||||||||||||||||
scalar · Integer32 (0..100) · read-only · current Utilization in % of available rectifier capacity
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NrectifierStatus | 1.3.6.1.4.1.12148.9.5.5 | ||||||||||||||||||||
| SrectifierStatusNoIndex | 1.3.6.1.4.1.12148.9.5.5.1 | Integer32 (0..95) | RW | 0 | |||||||||||||||||
scalar · Integer32 (0..95) · read-write · current An offset for the rectifierStatusTable array. The rectifier status table has a fixed number of 20 rows. This OID sets the offset for the rectifier in the first row i.e. setting the index to 11 will give a range from rectifier ID12 to ID31. Setting the index to 0 will give a range from rectifier ID1 to ID20. Example values from LibreNMS test devices
| |||||||||||||||||||||
| TrectifierStatusTable | 1.3.6.1.4.1.12148.9.5.5.2 | NA | |||||||||||||||||||
table · not-accessible · current A table listing up to 20 recifiers, starting from the rectifier number specified by rectifierStatusNoIndex | |||||||||||||||||||||
| RrectifierStatusEntry | 1.3.6.1.4.1.12148.9.5.5.2.1 | NA | |||||||||||||||||||
row · not-accessible · current A row of rectifier status data corresponding to the rectifierStatusNoIndex value
| |||||||||||||||||||||
| CrectifierStatusID | 1.3.6.1.4.1.12148.9.5.5.2.1.1 | Integer32 (1..100) | RO | 1 | |||||||||||||||||
column · Integer32 (1..100) · read-only · current The rectifier ID number of the rectifier. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrectifierStatusStatus | 1.3.6.1.4.1.12148.9.5.5.2.1.2 | INTEGER | RO | normal(1) | |||||||||||||||||
column · INTEGER · read-only · current The operational status of the rectifier record. Not Present (0), normal (1), alarm (2), notUsed (3), disabled (4)
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrectifierStatusOutputCurrent | 1.3.6.1.4.1.12148.9.5.5.2.1.3 | Integer32 (0..65535) | RO | 194 | |||||||||||||||||
column · Integer32 (0..65535) · read-only · current The output current of the rectifier.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrectifierStatusOutputVoltage | 1.3.6.1.4.1.12148.9.5.5.2.1.4 | Integer32 (0..65535) | RO | 5310 | |||||||||||||||||
column · Integer32 (0..65535) · read-only · current The rectifier voltage of the rectifier record.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrectifierStatusTemp | 1.3.6.1.4.1.12148.9.5.5.2.1.5 | Integer32 (0..65535) | RO | 30 | |||||||||||||||||
column · Integer32 (0..65535) · read-only · current The input air temperature of the rectifier.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrectifierStatusType | 1.3.6.1.4.1.12148.9.5.5.2.1.6 | DisplayString (SIZE (0..32)) | RO | FLATPACK2 48/2000 HE | |||||||||||||||||
column · DisplayString (SIZE (0..32)) · read-only · current The rectifier article number string of the rectifier record. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrectifierStatusSKU | 1.3.6.1.4.1.12148.9.5.5.2.1.7 | DisplayString (SIZE (1..32)) | RO | 241115.105 | |||||||||||||||||
column · DisplayString (SIZE (1..32)) · read-only · current The rectifier part number. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrectifierStatusSerialNo | 1.3.6.1.4.1.12148.9.5.5.2.1.8 | DisplayString (SIZE (0..16)) | RO | 140872100141 | |||||||||||||||||
column · DisplayString (SIZE (0..16)) · read-only · current The rectifier serial number string of the rectifier record. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrectifierStatusRevisionLevel | 1.3.6.1.4.1.12148.9.5.5.2.1.9 | DisplayString (SIZE (0..16)) | RO | 3.2 | |||||||||||||||||
column · DisplayString (SIZE (0..16)) · read-only · current The rectifier HW revision number string of the rectifier record. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NacDistribution | 1.3.6.1.4.1.12148.9.6 | ||||||||||||||||||||
| SacVoltage1 | 1.3.6.1.4.1.12148.9.6.1 | Integer32 | RO | 233 | |||||||||||||||||
scalar · Integer32 · read-only · current The AC Voltage of phase 1
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SacVoltage2 | 1.3.6.1.4.1.12148.9.6.2 | Integer32 | RO | 235 | |||||||||||||||||
scalar · Integer32 · read-only · current The AC Voltage of phase 2
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SacVoltage3 | 1.3.6.1.4.1.12148.9.6.3 | Integer32 | RO | 236 | |||||||||||||||||
scalar · Integer32 · read-only · current The AC Voltage of phase 3
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NalarmGroup | 1.3.6.1.4.1.12148.9.7 | ||||||||||||||||||||
| NalarmWellknownAlarms | 1.3.6.1.4.1.12148.9.7.1 | ||||||||||||||||||||
| SalarmMajorHighBattVolt | 1.3.6.1.4.1.12148.9.7.1.1 | INTEGER | RO | normal(0) | |||||||||||||||||
scalar · INTEGER · read-only · current The Major High Battery Voltage Alarm
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SalarmMinorHighBattVolt | 1.3.6.1.4.1.12148.9.7.1.2 | INTEGER | RO | normal(0) | |||||||||||||||||
scalar · INTEGER · read-only · current The Minor High Battery Voltage alarm
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SalarmMajorLowBattVolt | 1.3.6.1.4.1.12148.9.7.1.3 | INTEGER | RO | normal(0) | |||||||||||||||||
scalar · INTEGER · read-only · current The Major Low Battery Voltage Alarm
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SalarmMinorLowBattVolt | 1.3.6.1.4.1.12148.9.7.1.4 | INTEGER | RO | normal(0) | |||||||||||||||||
scalar · INTEGER · read-only · current The Minor Low Battery Voltage Alarm
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SalarmMajorBatteryHighTemp | 1.3.6.1.4.1.12148.9.7.1.5 | INTEGER | RO | normal(0) | |||||||||||||||||
scalar · INTEGER · read-only · current The Major High Battery Temperature alarm.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SalarmMinorBatteryHighTemp | 1.3.6.1.4.1.12148.9.7.1.6 | INTEGER | RO | normal(0) | |||||||||||||||||
scalar · INTEGER · read-only · current The Minor High Battery Temperature alarm.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SalarmBatteryDisconnectOpen | 1.3.6.1.4.1.12148.9.7.1.7 | INTEGER | RO | normal(0) | |||||||||||||||||
scalar · INTEGER · read-only · current The Battery Disconnect Contactor alarm
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SalarmLVD1open | 1.3.6.1.4.1.12148.9.7.1.8 | INTEGER | RO | normal(0) | |||||||||||||||||
scalar · INTEGER · read-only · current The load Contactor 1 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SalarmLVD2open | 1.3.6.1.4.1.12148.9.7.1.9 | INTEGER | RO | normal(0) | |||||||||||||||||
scalar · INTEGER · read-only · current The load Contactor 2 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SalarmLVD3open | 1.3.6.1.4.1.12148.9.7.1.10 | INTEGER | RO | normal(0) | |||||||||||||||||
scalar · INTEGER · read-only · current The load Contactor 3 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SalarmACmains | 1.3.6.1.4.1.12148.9.7.1.11 | INTEGER | RO | normal(0) | |||||||||||||||||
scalar · INTEGER · read-only · current The AC voltage has dropped below critical level, or one or more AC input phases was lost.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SalarmBatteryBreakerOpen | 1.3.6.1.4.1.12148.9.7.1.12 | INTEGER | RO | normal(0) | |||||||||||||||||
scalar · INTEGER · read-only · current A battery breaker/fuse alarm.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SalarmDistributionBreakerOpen | 1.3.6.1.4.1.12148.9.7.1.13 | INTEGER | RO | normal(0) | |||||||||||||||||
scalar · INTEGER · read-only · current A Load Distribution breaker/fuse alarm.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SalarmMajorRectifier | 1.3.6.1.4.1.12148.9.7.1.14 | INTEGER | RO | normal(0) | |||||||||||||||||
scalar · INTEGER · read-only · current This is a Major Rectifier alarm.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SalarmMinorRectifier | 1.3.6.1.4.1.12148.9.7.1.15 | INTEGER | RO | normal(0) | |||||||||||||||||
scalar · INTEGER · read-only · current This is a Minor Rectifier alarm.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SalarmMajorBatterySymmetry | 1.3.6.1.4.1.12148.9.7.1.16 | INTEGER | RO | normal(0) | |||||||||||||||||
scalar · INTEGER · read-only · current Battery Symmetry Delta Voltage Major alarm.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SalarmMinorBatterySymmetry | 1.3.6.1.4.1.12148.9.7.1.17 | INTEGER | RO | normal(0) | |||||||||||||||||
scalar · INTEGER · read-only · current Battery Symmetry Delta Voltage Minor alarm
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SalarmBatteryLifeEnded | 1.3.6.1.4.1.12148.9.7.1.18 | INTEGER | RO | normal(0) | |||||||||||||||||
scalar · INTEGER · read-only · current The battery quality has dropped below critical level. A battery test has measured the fully charged capacity to be too low, and thus probably the battery lifecycle to be near expired.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SalarmBatteryTestmodeEntered | 1.3.6.1.4.1.12148.9.7.1.19 | INTEGER | RO | normal(0) | |||||||||||||||||
scalar · INTEGER · read-only · current The system has lowered the battery charge voltage in order to discharge the batteries to a predefined level. When the criteria for stopping the battery testing is reached, the charge voltage is increased to commence normal charging.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SalarmBatteryBoostmodeEntered | 1.3.6.1.4.1.12148.9.7.1.20 | INTEGER | RO | normal(0) | |||||||||||||||||
scalar · INTEGER · read-only · current The system has increased the battery charge voltage in order to boost the battery. When the criteria for stopping the battery boost is reached, the charge voltage is lowered to commence normal charging.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SalarmIoUnitTemp1 | 1.3.6.1.4.1.12148.9.7.1.21 | INTEGER | RO | normal(0) | |||||||||||||||||
scalar · INTEGER · read-only · current High or low temperature alarm 1 from any of the IO units.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SalarmIoUnitTemp2 | 1.3.6.1.4.1.12148.9.7.1.22 | INTEGER | RO | normal(0) | |||||||||||||||||
scalar · INTEGER · read-only · current High or low temperature alarm 2 from any of the IO units.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SalarmIoUnitDeltaFanSpeed1 | 1.3.6.1.4.1.12148.9.7.1.23 | INTEGER | RO | normal(0) | |||||||||||||||||
scalar · INTEGER · read-only · current Delta fan speed 1 from any of the IO units.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SalarmIoUnitDeltaFanSpeed2 | 1.3.6.1.4.1.12148.9.7.1.24 | INTEGER | RO | normal(0) | |||||||||||||||||
scalar · INTEGER · read-only · current Delta fan speed 2 from any of the IO units.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SalarmMajorSolar | 1.3.6.1.4.1.12148.9.7.1.25 | INTEGER | RO | normal(0) | |||||||||||||||||
scalar · INTEGER · read-only · current This is a Major Solar alarm.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SalarmMinorSolar | 1.3.6.1.4.1.12148.9.7.1.26 | INTEGER | RO | normal(0) | |||||||||||||||||
scalar · INTEGER · read-only · current This is a Major Solar alarm.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SalarmMajorRectifierCapacity | 1.3.6.1.4.1.12148.9.7.1.27 | INTEGER | RO | normal(0) | |||||||||||||||||
scalar · INTEGER · read-only · current This is a Major Rectifier Capacity alarm.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SalarmMinorRectifierCapacity | 1.3.6.1.4.1.12148.9.7.1.28 | INTEGER | RO | normal(0) | |||||||||||||||||
scalar · INTEGER · read-only · current This is a Minor Rectifier Capacity alarm.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| GdcSystemTraps | 1.3.6.1.4.1.12148.9.8 | ||||||||||||||||||||
group · current This branch contains the Alarm Notification Traps, which duplicate the alarmGroup OIDs. Each alarm condition is represented by a Alarm Condition Trap and an associated OFF Trap, which is optionally transmitted according to the state of OID systemSendOffTrap
| |||||||||||||||||||||
| !alarmMajorHighBattVoltTrap | 1.3.6.1.4.1.12148.9.8.1 | ||||||||||||||||||||
notification · current The Major High Battery Voltage alarm | |||||||||||||||||||||
| !alarmMinorHighBattVoltTrap | 1.3.6.1.4.1.12148.9.8.2 | ||||||||||||||||||||
notification · current The Minor High Battery Voltage alarm | |||||||||||||||||||||
| !alarmMajorLowBattVoltTrap | 1.3.6.1.4.1.12148.9.8.3 | ||||||||||||||||||||
notification · current The Major Low Battery Voltage Alarm | |||||||||||||||||||||
| !alarmMinorLowBattVoltTrap | 1.3.6.1.4.1.12148.9.8.4 | ||||||||||||||||||||
notification · current The Minor Low Battery Voltage Alarm | |||||||||||||||||||||
| !alarmMajorBatteryHighTempTrap | 1.3.6.1.4.1.12148.9.8.5 | ||||||||||||||||||||
notification · current The Major High Battery Temperature alarm. | |||||||||||||||||||||
| !alarmMinorBatteryHighTempTrap | 1.3.6.1.4.1.12148.9.8.6 | ||||||||||||||||||||
notification · current The Minor High Battery Temperature alarm. | |||||||||||||||||||||
| !alarmBatteryDisconnectOpenTrap | 1.3.6.1.4.1.12148.9.8.7 | ||||||||||||||||||||
notification · current The Battery Disconnect Contactor alarm | |||||||||||||||||||||
| !alarmLVD1openTrap | 1.3.6.1.4.1.12148.9.8.8 | ||||||||||||||||||||
notification · current The load Contactor 1 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected.
| |||||||||||||||||||||
| !alarmLVD2openTrap | 1.3.6.1.4.1.12148.9.8.9 | ||||||||||||||||||||
notification · current The load Contactor 2 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected.
| |||||||||||||||||||||
| !alarmLVD3openTrap | 1.3.6.1.4.1.12148.9.8.10 | ||||||||||||||||||||
notification · current The load Contactor 3 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected.
| |||||||||||||||||||||
| !alarmACmainsTrap | 1.3.6.1.4.1.12148.9.8.11 | ||||||||||||||||||||
notification · current The AC voltage has dropped below critical level, or one or more AC input phases was lost.
| |||||||||||||||||||||
| !alarmBatteryBreakerOpenTrap | 1.3.6.1.4.1.12148.9.8.12 | ||||||||||||||||||||
notification · current A battery breaker/fuse alarm. | |||||||||||||||||||||
| !alarmDistributionBreakerOpenTrap | 1.3.6.1.4.1.12148.9.8.13 | ||||||||||||||||||||
notification · current A Load Distribution breaker/fuse alarm. | |||||||||||||||||||||
| !alarmMajorRectifierTrap | 1.3.6.1.4.1.12148.9.8.14 | ||||||||||||||||||||
| !alarmMinorRectifierTrap | 1.3.6.1.4.1.12148.9.8.15 | ||||||||||||||||||||
| !alarmMajorBatterySymmetryTrap | 1.3.6.1.4.1.12148.9.8.16 | ||||||||||||||||||||
notification · current Battery Symmetry Delta Voltage Major alarm | |||||||||||||||||||||
| !alarmMinorBatterySymmetryTrap | 1.3.6.1.4.1.12148.9.8.17 | ||||||||||||||||||||
notification · current Battery Symmetry Delta Voltage Minor alarm | |||||||||||||||||||||
| !alarmBatteryLifeEndedTrap | 1.3.6.1.4.1.12148.9.8.18 | ||||||||||||||||||||
notification · current The battery quality has dropped below critical level. A battery test has measured the fully charged capacity to be too low, and thus probably the battery lifecycle to be near expired. | |||||||||||||||||||||
| !alarmBatteryTestmodeEnteredTrap | 1.3.6.1.4.1.12148.9.8.19 | ||||||||||||||||||||
notification · current The system has lowered the battery charge voltage in order to discharge the batteries to a predefined level. When the criteria for stopping the battery testing is reached, the charge voltage is increased to commence normal charging. | |||||||||||||||||||||
| !alarmBatteryBoostmodeEnteredTrap | 1.3.6.1.4.1.12148.9.8.20 | ||||||||||||||||||||
notification · current The system has increased the battery charge voltage in order to boost the battery. When the criteria for stopping the battery boost is reached, the charge voltage is lowered to commence normal charging. | |||||||||||||||||||||
| !alarmController1proginputTrap | 1.3.6.1.4.1.12148.9.8.21 | ||||||||||||||||||||
notification · current Programmable input alarm for Control unit 1. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.x. | |||||||||||||||||||||
| !alarmController2proginputTrap | 1.3.6.1.4.1.12148.9.8.22 | ||||||||||||||||||||
notification · current Programmable input alarm for Control unit 2. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.x. | |||||||||||||||||||||
| !alarmController3proginputTrap | 1.3.6.1.4.1.12148.9.8.23 | ||||||||||||||||||||
notification · current Programmable input alarm for Control unit 3. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.x. | |||||||||||||||||||||
| !alarmController4proginputTrap | 1.3.6.1.4.1.12148.9.8.24 | ||||||||||||||||||||
notification · current Programmable input alarm for Control unit 4. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.x. | |||||||||||||||||||||
| !alarmController5proginputTrap | 1.3.6.1.4.1.12148.9.8.25 | ||||||||||||||||||||
notification · current Programmable input alarm for Control unit 5. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.x. | |||||||||||||||||||||
| !alarmController6proginputTrap | 1.3.6.1.4.1.12148.9.8.26 | ||||||||||||||||||||
notification · current Programmable input alarm for Control unit 6. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.x. | |||||||||||||||||||||
| !alarmController7proginputTrap | 1.3.6.1.4.1.12148.9.8.27 | ||||||||||||||||||||
notification · current Programmable input alarm for Control unit 7. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.x. | |||||||||||||||||||||
| !alarmController8proginputTrap | 1.3.6.1.4.1.12148.9.8.28 | ||||||||||||||||||||
notification · current Programmable input alarm for Control unit 8. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <Control unit ID>.x. | |||||||||||||||||||||
| !infoHeartBeatTrap | 1.3.6.1.4.1.12148.9.8.29 | ||||||||||||||||||||
notification · current When enabled, this trap will be transmitted at regular inervals. This trap is not intended to be an alarm but more like some information that the system is alive and the link is up.
| |||||||||||||||||||||
| !alarmIoUnitTemp1Trap | 1.3.6.1.4.1.12148.9.8.30 | ||||||||||||||||||||
notification · current High or low temperature alarm 1 from any of the IO units.
| |||||||||||||||||||||
| !alarmIoUnitTemp2Trap | 1.3.6.1.4.1.12148.9.8.31 | ||||||||||||||||||||
notification · current High or low temperature alarm 2 from any of the IO units.
| |||||||||||||||||||||
| !alarmIoUnitDeltaFanSpeed1Trap | 1.3.6.1.4.1.12148.9.8.32 | ||||||||||||||||||||
notification · current Delta fan speed 1 from any of the IO units. Occurs if the fan speed deviation is above/below the configured level. | |||||||||||||||||||||
| !alarmIoUnitDeltaFanSpeed2Trap | 1.3.6.1.4.1.12148.9.8.33 | ||||||||||||||||||||
notification · current Delta fan speed 2 from any of the IO units. Occurs if the fan speed deviation is above/below the configured level. | |||||||||||||||||||||
| !alarmIoUnit1proginputTrap | 1.3.6.1.4.1.12148.9.8.34 | ||||||||||||||||||||
notification · current Programmable input alarm for IO Unit 1. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x. | |||||||||||||||||||||
| !alarmIoUnit2proginputTrap | 1.3.6.1.4.1.12148.9.8.35 | ||||||||||||||||||||
notification · current Programmable input alarm for IO Unit 2. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x. | |||||||||||||||||||||
| !alarmIoUnit3proginputTrap | 1.3.6.1.4.1.12148.9.8.36 | ||||||||||||||||||||
notification · current Programmable input alarm for IO Unit 3. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x. | |||||||||||||||||||||
| !alarmIoUnit4proginputTrap | 1.3.6.1.4.1.12148.9.8.37 | ||||||||||||||||||||
notification · current Programmable input alarm for IO Unit 4. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x. | |||||||||||||||||||||
| !alarmIoUnit5proginputTrap | 1.3.6.1.4.1.12148.9.8.38 | ||||||||||||||||||||
notification · current Programmable input alarm for IO Unit 5. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x. | |||||||||||||||||||||
| !alarmIoUnit6proginputTrap | 1.3.6.1.4.1.12148.9.8.39 | ||||||||||||||||||||
notification · current Programmable input alarm for IO Unit 6. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x. | |||||||||||||||||||||
| !alarmIoUnit7proginputTrap | 1.3.6.1.4.1.12148.9.8.40 | ||||||||||||||||||||
notification · current Programmable input alarm for IO Unit 7. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x. | |||||||||||||||||||||
| !alarmIoUnit8proginputTrap | 1.3.6.1.4.1.12148.9.8.41 | ||||||||||||||||||||
notification · current Programmable input alarm for IO Unit 8. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x. | |||||||||||||||||||||
| !alarmIoUnit9proginputTrap | 1.3.6.1.4.1.12148.9.8.42 | ||||||||||||||||||||
notification · current Programmable input alarm for IO Unit 9. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x. | |||||||||||||||||||||
| !alarmIoUnit10proginputTrap | 1.3.6.1.4.1.12148.9.8.43 | ||||||||||||||||||||
notification · current Programmable input alarm for IO Unit 10. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x. | |||||||||||||||||||||
| !alarmIoUnit11proginputTrap | 1.3.6.1.4.1.12148.9.8.44 | ||||||||||||||||||||
notification · current Programmable input alarm for IO Unit 11. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x. | |||||||||||||||||||||
| !alarmIoUnit12proginputTrap | 1.3.6.1.4.1.12148.9.8.45 | ||||||||||||||||||||
notification · current Programmable input alarm for IO Unit 12. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x. | |||||||||||||||||||||
| !alarmIoUnit13proginputTrap | 1.3.6.1.4.1.12148.9.8.46 | ||||||||||||||||||||
notification · current Programmable input alarm for IO Unit 13. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x. | |||||||||||||||||||||
| !alarmIoUnit14proginputTrap | 1.3.6.1.4.1.12148.9.8.47 | ||||||||||||||||||||
notification · current Programmable input alarm for IO Unit 14. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput <IO Unit ID>.x. | |||||||||||||||||||||
| !alarmMajorSolarChargerTrap | 1.3.6.1.4.1.12148.9.8.48 | ||||||||||||||||||||
| !alarmMinorSolarChargerTrap | 1.3.6.1.4.1.12148.9.8.49 | ||||||||||||||||||||
| !alarmMajorRectifierCapacityTrap | 1.3.6.1.4.1.12148.9.8.50 | ||||||||||||||||||||
notification · current The Major Rectifier Capacity alarm | |||||||||||||||||||||
| !alarmMinorRectifierCapacityTrap | 1.3.6.1.4.1.12148.9.8.51 | ||||||||||||||||||||
notification · current The Minor Rectifier Capacity alarm | |||||||||||||||||||||
| NsolarCharger | 1.3.6.1.4.1.12148.9.9 | ||||||||||||||||||||
| SsolarChargerInstalledsolarChargers | 1.3.6.1.4.1.12148.9.9.1 | Integer32 (1..101) | RO | 0 | |||||||||||||||||
scalar · Integer32 (1..101) · read-only · current The number of installed solar chargers for this DC Power System. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SsolarChargersActive | 1.3.6.1.4.1.12148.9.9.2 | Integer32 (1..101) | RO | 0 | |||||||||||||||||
scalar · Integer32 (1..101) · read-only · current Not Used! Example values from LibreNMS test devices
| |||||||||||||||||||||
| SsolarChargerTotalCurrent | 1.3.6.1.4.1.12148.9.9.3 | Integer32 | RO | 58 | |||||||||||||||||
scalar · Integer32 · read-only · current The DC system's total delivered solar current
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SsolarChargerUtilization | 1.3.6.1.4.1.12148.9.9.4 | Integer32 (0..100) | RO | 0 | |||||||||||||||||
scalar · Integer32 (0..100) · read-only · current Utilization in % of available solar capacity Example values from LibreNMS test devices
| |||||||||||||||||||||
| NsolarChargerStatus | 1.3.6.1.4.1.12148.9.9.5 | ||||||||||||||||||||
| SsolarChargerStatusNoIndex | 1.3.6.1.4.1.12148.9.9.5.1 | Integer32 (0..95) | RW | 0 | |||||||||||||||||
scalar · Integer32 (0..95) · read-write · current An offset for the solarStatusTable array. The solar status table has a fixed number of 20 rows. This OID sets the offset for the solarcharger in the first row i.e. setting the index to 11 will give a range from solarcharger ID12 to ID31. Setting the index to 0 will give a range from solarcharger ID1 to ID20. Example values from LibreNMS test devices
| |||||||||||||||||||||
| TsolarChargerStatusTable | 1.3.6.1.4.1.12148.9.9.5.2 | NA | |||||||||||||||||||
table · not-accessible · current A table listing up to 20 solarchargers, starting from the solarcharger number specified by solarStatusNoIndex | |||||||||||||||||||||
| RsolarChargerStatusEntry | 1.3.6.1.4.1.12148.9.9.5.2.1 | NA | |||||||||||||||||||
row · not-accessible · current A row of rectifier status data corresponding to the rectifierStatusNoIndex value
| |||||||||||||||||||||
| CsolarChargerStatusID | 1.3.6.1.4.1.12148.9.9.5.2.1.1 | Integer32 (1..100) | RO | 1 | |||||||||||||||||
column · Integer32 (1..100) · read-only · current The ID number of the solarcharger. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CsolarChargerStatusStatus | 1.3.6.1.4.1.12148.9.9.5.2.1.2 | INTEGER | RO | notPresent(0) | |||||||||||||||||
column · INTEGER · read-only · current The operational status of the solarcharger record. Not Present (0), normal (1), alarm (2), notUsed (3), disabled (4)
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CsolarChargerOutputCurrent | 1.3.6.1.4.1.12148.9.9.5.2.1.3 | Integer32 (0..65535) | RO | 0 | |||||||||||||||||
column · Integer32 (0..65535) · read-only · current The output current of the solarcharger.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CsolarChargerOutputVoltage | 1.3.6.1.4.1.12148.9.9.5.2.1.4 | Integer32 (0..65535) | RO | 0 | |||||||||||||||||
column · Integer32 (0..65535) · read-only · current The output voltage of the solarcharger.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CsolarChargerTemp | 1.3.6.1.4.1.12148.9.9.5.2.1.5 | Integer32 (0..65535) | RO | 0 | |||||||||||||||||
column · Integer32 (0..65535) · read-only · current The input air temperature of the solarcharger. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CsolarChargerType | 1.3.6.1.4.1.12148.9.9.5.2.1.6 | DisplayString (SIZE (0..32)) | RO | - | |||||||||||||||||
column · DisplayString (SIZE (0..32)) · read-only · current The article number string of the solarcharger. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CsolarChargerSKU | 1.3.6.1.4.1.12148.9.9.5.2.1.7 | DisplayString (SIZE (1..32)) | RO | - | |||||||||||||||||
column · DisplayString (SIZE (1..32)) · read-only · current The solarcharger part number. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CsolarChargerSerialNo | 1.3.6.1.4.1.12148.9.9.5.2.1.8 | DisplayString (SIZE (0..16)) | RO | - | |||||||||||||||||
column · DisplayString (SIZE (0..16)) · read-only · current The serial number string of the solarcharger. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CsolarChargerRevisionLevel | 1.3.6.1.4.1.12148.9.9.5.2.1.9 | DisplayString (SIZE (0..16)) | RO | - | |||||||||||||||||
column · DisplayString (SIZE (0..16)) · read-only · current The HW revision number string of the solarcharger. Example values from LibreNMS test devices
| |||||||||||||||||||||
Traps / Notifications
- alarmACmainsTrap
1.3.6.1.4.1.12148.9.8.11 - alarmBatteryBoostmodeEnteredTrap
1.3.6.1.4.1.12148.9.8.20 - alarmBatteryBreakerOpenTrap
1.3.6.1.4.1.12148.9.8.12 - alarmBatteryDisconnectOpenTrap
1.3.6.1.4.1.12148.9.8.7 - alarmBatteryLifeEndedTrap
1.3.6.1.4.1.12148.9.8.18 - alarmBatteryTestmodeEnteredTrap
1.3.6.1.4.1.12148.9.8.19 - alarmController1proginputTrap
1.3.6.1.4.1.12148.9.8.21 - alarmController2proginputTrap
1.3.6.1.4.1.12148.9.8.22 - alarmController3proginputTrap
1.3.6.1.4.1.12148.9.8.23 - alarmController4proginputTrap
1.3.6.1.4.1.12148.9.8.24 - alarmController5proginputTrap
1.3.6.1.4.1.12148.9.8.25 - alarmController6proginputTrap
1.3.6.1.4.1.12148.9.8.26 - alarmController7proginputTrap
1.3.6.1.4.1.12148.9.8.27 - alarmController8proginputTrap
1.3.6.1.4.1.12148.9.8.28 - alarmDistributionBreakerOpenTrap
1.3.6.1.4.1.12148.9.8.13 - alarmIoUnit10proginputTrap
1.3.6.1.4.1.12148.9.8.43 - alarmIoUnit11proginputTrap
1.3.6.1.4.1.12148.9.8.44 - alarmIoUnit12proginputTrap
1.3.6.1.4.1.12148.9.8.45 - alarmIoUnit13proginputTrap
1.3.6.1.4.1.12148.9.8.46 - alarmIoUnit14proginputTrap
1.3.6.1.4.1.12148.9.8.47 - alarmIoUnit1proginputTrap
1.3.6.1.4.1.12148.9.8.34 - alarmIoUnit2proginputTrap
1.3.6.1.4.1.12148.9.8.35 - alarmIoUnit3proginputTrap
1.3.6.1.4.1.12148.9.8.36 - alarmIoUnit4proginputTrap
1.3.6.1.4.1.12148.9.8.37 - alarmIoUnit5proginputTrap
1.3.6.1.4.1.12148.9.8.38 - alarmIoUnit6proginputTrap
1.3.6.1.4.1.12148.9.8.39 - alarmIoUnit7proginputTrap
1.3.6.1.4.1.12148.9.8.40 - alarmIoUnit8proginputTrap
1.3.6.1.4.1.12148.9.8.41 - alarmIoUnit9proginputTrap
1.3.6.1.4.1.12148.9.8.42 - alarmIoUnitDeltaFanSpeed1Trap
1.3.6.1.4.1.12148.9.8.32 - alarmIoUnitDeltaFanSpeed2Trap
1.3.6.1.4.1.12148.9.8.33 - alarmIoUnitTemp1Trap
1.3.6.1.4.1.12148.9.8.30 - alarmIoUnitTemp2Trap
1.3.6.1.4.1.12148.9.8.31 - alarmLVD1openTrap
1.3.6.1.4.1.12148.9.8.8 - alarmLVD2openTrap
1.3.6.1.4.1.12148.9.8.9 - alarmLVD3openTrap
1.3.6.1.4.1.12148.9.8.10 - alarmMajorBatteryHighTempTrap
1.3.6.1.4.1.12148.9.8.5 - alarmMajorBatterySymmetryTrap
1.3.6.1.4.1.12148.9.8.16 - alarmMajorHighBattVoltTrap
1.3.6.1.4.1.12148.9.8.1 - alarmMajorLowBattVoltTrap
1.3.6.1.4.1.12148.9.8.3 - alarmMajorRectifierCapacityTrap
1.3.6.1.4.1.12148.9.8.50 - alarmMajorRectifierTrap
1.3.6.1.4.1.12148.9.8.14 - alarmMajorSolarChargerTrap
1.3.6.1.4.1.12148.9.8.48 - alarmMinorBatteryHighTempTrap
1.3.6.1.4.1.12148.9.8.6 - alarmMinorBatterySymmetryTrap
1.3.6.1.4.1.12148.9.8.17 - alarmMinorHighBattVoltTrap
1.3.6.1.4.1.12148.9.8.2 - alarmMinorLowBattVoltTrap
1.3.6.1.4.1.12148.9.8.4 - alarmMinorRectifierCapacityTrap
1.3.6.1.4.1.12148.9.8.51 - alarmMinorRectifierTrap
1.3.6.1.4.1.12148.9.8.15 - alarmMinorSolarChargerTrap
1.3.6.1.4.1.12148.9.8.49 - infoHeartBeatTrap
1.3.6.1.4.1.12148.9.8.29