ELTEK-BC2000-DC-POWER-MIB
Eltek Valere Inc. (formerly 'Valere Power Inc')SNMP access to Eltek DC Power systems through the BC2000 controller.
snmptranslate -m ELTEK-BC2000-DC-POWER-MIB -Tpsnmpwalk -v2c -c <community> -m ELTEK-BC2000-DC-POWER-MIB <host> 1.3.6.1.4.1.13858Imports
| RFC1155-SMI | Gauge32 |
|---|---|
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
| SNMPv2-SMI | Bits, Counter32, Gauge32, Integer32, IpAddress, MODULE-IDENTITY, MibIdentifier, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, TimeTicks, Unsigned32, enterprises, iso |
| SNMPv2-TC | AutonomousType, DisplayString, PhysAddress, TEXTUAL-CONVENTION, TimeStamp |
OID tree
| Name | OID | Type | Access | Status | Example | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Ieltek | 1.3.6.1.4.1.13858 | ||||||||||||||||||||
identity SNMP access to Eltek DC Power systems through the BC2000 controller. | |||||||||||||||||||||
| NvpwrDcPowerSystem | 1.3.6.1.4.1.13858.2 | ||||||||||||||||||||
| NvpwrSystemIdentGroup | 1.3.6.1.4.1.13858.2.1 | ||||||||||||||||||||
| SvpwrIdentManufacturer | 1.3.6.1.4.1.13858.2.1.1 | DisplayString (SIZE (0..31)) | RO | Eltek Valere | |||||||||||||||||
scalar · DisplayString (SIZE (0..31)) · read-only · current The name of the DC Power manufacturer. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SvpwrIdentModel | 1.3.6.1.4.1.13858.2.1.2 | DisplayString (SIZE (0..15)) | RO | BC2000 | |||||||||||||||||
scalar · DisplayString (SIZE (0..15)) · read-only · current The DC Power Model designation. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SvpwrIdentControllerVersion | 1.3.6.1.4.1.13858.2.1.3 | DisplayString (SIZE (0..15)) | RO | 4.01.40 | |||||||||||||||||
scalar · DisplayString (SIZE (0..15)) · read-only · current The hardware/firmware version(s). This variable may or may not have the same value as vpwrIdentAgentSoftwareVersion. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SvpwrIdentAgentSoftwareVersion | 1.3.6.1.4.1.13858.2.1.4 | DisplayString (SIZE (0..15)) | RO | ||||||||||||||||||
scalar · DisplayString (SIZE (0..15)) · read-only · current The SNMP agent software version. This variable may or may not have the same value as vpwrIdentControllerVersion. | |||||||||||||||||||||
| SvpwrIdentName | 1.3.6.1.4.1.13858.2.1.5 | DisplayString (SIZE (0..31)) | RW | ||||||||||||||||||
scalar · DisplayString (SIZE (0..31)) · read-write · current A string identifying the system. This object should be set by the administrator. | |||||||||||||||||||||
| TvpwrSystemIdentTable | 1.3.6.1.4.1.13858.2.1.6 | NA | |||||||||||||||||||
table · not-accessible · current This table describes shelves and modules that make up the sysetm. | |||||||||||||||||||||
| RvpwrSystemIdentEntry | 1.3.6.1.4.1.13858.2.1.6.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing information applicable to a particular alarm.
| |||||||||||||||||||||
| CvpwrBayIndex | 1.3.6.1.4.1.13858.2.1.6.1.1 | PositiveInteger | RO | 1 | |||||||||||||||||
column · PositiveInteger · read-only · current Identifies shelf number that this module belongs to. The possible values are 1 through 16 limited by vpwrSystemShelfCapacity. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CvpwrModuleIndex | 1.3.6.1.4.1.13858.2.1.6.1.2 | PositiveInteger | RO | 1 | |||||||||||||||||
column · PositiveInteger · read-only · current This object identifies the module by its position in the shelf. Module numbering is left to right starting with module 1. So, the module in the first slot has an index of 1, the next module is 2 and so on. | |||||||||||||||||||||
| CvpwrModuleOID | 1.3.6.1.4.1.13858.2.1.6.1.3 | OBJECT IDENTIFIER | RO | 1.3.6.1.4.1.13858.3 | |||||||||||||||||
column · OBJECT IDENTIFIER · read-only · current It indicates the type of the module by specifiying its OID Example values from LibreNMS test devices
| |||||||||||||||||||||
| CvpwrModuleCurrent | 1.3.6.1.4.1.13858.2.1.6.1.4 | INTEGER | RO | 911 | |||||||||||||||||
column · INTEGER · read-only · current The meaning of this object depends upon the module type which is indicated by vpwrModuleOID as follows - Current for Rectifier module in centiamps. - Not Applicable for LVD module Example values from LibreNMS test devices
| |||||||||||||||||||||
| CvpwrModuleOperStatus | 1.3.6.1.4.1.13858.2.1.6.1.5 | INTEGER | RO | moduleStatusOK(0) | |||||||||||||||||
column · INTEGER · read-only · current This object indicates current over all status of the module.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CvpwrModuleCapacity | 1.3.6.1.4.1.13858.2.1.6.1.6 | INTEGER | RO | 5250 | |||||||||||||||||
column · INTEGER · read-only · current The meaning of this object depends upon the module type which is indicated by vpwrModuleOID as follows - Capacity for Rectifier module. - Not Applicable for LVD module Example values from LibreNMS test devices
| |||||||||||||||||||||
| NvpwrSystemConfigGroup | 1.3.6.1.4.1.13858.2.2 | ||||||||||||||||||||
| SvpwrSystemTempCompensation | 1.3.6.1.4.1.13858.2.2.1 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current This parameter enables/disables temperature compensation.
| |||||||||||||||||||||
| SvpwrSystemTempCompStartTemperature | 1.3.6.1.4.1.13858.2.2.2 | INTEGER (25..60) | RW | ||||||||||||||||||
scalar · INTEGER (25..60) · read-write · current The temperature at which temperature compensation becomes active.
| |||||||||||||||||||||
| SvpwrSystemTempCompStopVoltage | 1.3.6.1.4.1.13858.2.2.3 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current When temperature compensation is active, vpwrSystemTempCompStopVoltage is the
limit to which float voltage will be reduced.
For example, to set this voltage to 51.75 volts enter a value of 5175.
| |||||||||||||||||||||
| SvpwrSystemTempCompensationSlope | 1.3.6.1.4.1.13858.2.2.4 | INTEGER (0..250) | RW | ||||||||||||||||||
scalar · INTEGER (0..250) · read-write · current The rate at which float voltage is changed, within the specified limits, when temperature compensation is active.
| |||||||||||||||||||||
| SvpwrSystemThermalSenseType | 1.3.6.1.4.1.13858.2.2.5 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current This parameter selects the temperature sensing point for temperature compensation (in)activation.
| |||||||||||||||||||||
| SvpwrSystemHVAlarmSetpoint | 1.3.6.1.4.1.13858.2.2.6 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current System High voltage alarm voltage setting.
| |||||||||||||||||||||
| SvpwrSystemBDAlarmSetpoint | 1.3.6.1.4.1.13858.2.2.7 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current System Battery Discharge voltage setting.
| |||||||||||||||||||||
| SvpwrSystemInternalTempLThreshold | 1.3.6.1.4.1.13858.2.2.8 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current Temperature value at which temperature compensation inactive (clear) trap would be sent if temperature compensation was active when this value is reached.
| |||||||||||||||||||||
| SvpwrSystemInternalTempUThreshold | 1.3.6.1.4.1.13858.2.2.9 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current Temperature value at which temperature compensation active (set) trap would be sent.
| |||||||||||||||||||||
| NvpwrSystemParameterGroup | 1.3.6.1.4.1.13858.2.3 | ||||||||||||||||||||
| SvpwrSystemShelfCapacity | 1.3.6.1.4.1.13858.2.3.1 | INTEGER (1..16) | RO | 2 | |||||||||||||||||
scalar · INTEGER (1..16) · read-only · current It describes the maximum number of shelves that can/are controlled by the controller. Each shelf is uniquely numbered in the range from 1 to vpwrShelfCapacity. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SvpwrSystemVoltage | 1.3.6.1.4.1.13858.2.3.2 | INTEGER | RO | 5400 | |||||||||||||||||
scalar · INTEGER · read-only · current The current system voltage.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SvpwrSystemCurrent | 1.3.6.1.4.1.13858.2.3.3 | INTEGER | RO | 17 | |||||||||||||||||
scalar · INTEGER · read-only · current The current system current.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SvpwrSystemControllerState | 1.3.6.1.4.1.13858.2.3.4 | INTEGER | RO | systemControllerStateNormal(1) | |||||||||||||||||
scalar · INTEGER · read-only · current Current System state as shown on the enhanced display.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SvpwrSystemInternalTemperature | 1.3.6.1.4.1.13858.2.3.5 | INTEGER | RO | 25 | |||||||||||||||||
scalar · INTEGER · read-only · current The current controller internal temperature.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SvpwrSystemTempCompensationState | 1.3.6.1.4.1.13858.2.3.6 | INTEGER | RO | systemTempCompInactive(0) | |||||||||||||||||
scalar · INTEGER · read-only · current Active or Inactive. Applicable only if temperature compensation is enabled. This means that the controller is temperature compensating the float voltage.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SvpwrSystemType | 1.3.6.1.4.1.13858.2.3.7 | INTEGER | RO | sysType48V(0) | |||||||||||||||||
scalar · INTEGER · read-only · current This parameter describes the type of the system being managed. This object is set by Eltek Valere Inc.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SvpwrSystemCumulativeUpTime | 1.3.6.1.4.1.13858.2.3.8 | Gauge32 | RO | 713841620 (82d 14h 53m 36s) | |||||||||||||||||
scalar · Gauge32 · read-only · current This parameter describes the cumulative runtime in seconds of the Eltek Valere controller. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SvpwrSystemBatteryRemainingTime | 1.3.6.1.4.1.13858.2.3.9 | PositiveInteger | RO | 8 | |||||||||||||||||
scalar · PositiveInteger · read-only · current This parameter describes the remaining battery capacity based upon installed battery capacity and plant load. This number would change as the SOC parameters of the batteries changes.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NvpwrSystemPanelIdentGroup | 1.3.6.1.4.1.13858.2.4 | ||||||||||||||||||||
| TvpwrPanelStatusTable | 1.3.6.1.4.1.13858.2.4.1 | NA | |||||||||||||||||||
table · not-accessible · current This table describes shelves and modules that make up the panels. | |||||||||||||||||||||
| RvpwrPanelStatus | 1.3.6.1.4.1.13858.2.4.1.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing information applicable to a particular panel making up the system. | |||||||||||||||||||||
| CvpwrPanelStatusIndex | 1.3.6.1.4.1.13858.2.4.1.1.1 | PositiveInteger | RO | ||||||||||||||||||
column · PositiveInteger · read-only · current Identifies panel number that this module belongs to. The possible values are 1 through 8, starting from the top. | |||||||||||||||||||||
| CvpwrPanelStatusModuleIndex | 1.3.6.1.4.1.13858.2.4.1.1.2 | PositiveInteger | RO | ||||||||||||||||||
column · PositiveInteger · read-only · current This object identifies the module within the panel. The orentation of modules within the panel is mappable. | |||||||||||||||||||||
| CvpwrPanelStatusModuleOID | 1.3.6.1.4.1.13858.2.4.1.1.3 | OBJECT IDENTIFIER | RO | ||||||||||||||||||
column · OBJECT IDENTIFIER · read-only · current The module OID. | |||||||||||||||||||||
| CvpwrPanelStatusModuleCurrent | 1.3.6.1.4.1.13858.2.4.1.1.4 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current The current measured by the device (if applicable). LVD current reported in deciAmps. | |||||||||||||||||||||
| CvpwrpanelStatusModuleOperStatus | 1.3.6.1.4.1.13858.2.4.1.1.5 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current This object indicates current over all status of the module.
| |||||||||||||||||||||
| CvpwrPanelStatusModuleCapacity | 1.3.6.1.4.1.13858.2.4.1.1.6 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current The maximum capacity of the module (if applicable). | |||||||||||||||||||||
| TvpwrPanelIdentTable | 1.3.6.1.4.1.13858.2.4.2 | NA | |||||||||||||||||||
table · not-accessible · current This table describes shelves and modules that make up the panels. | |||||||||||||||||||||
| RvpwrPanelIdentEntry | 1.3.6.1.4.1.13858.2.4.2.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing information applicable to a particular panel making up the system. | |||||||||||||||||||||
| CvpwrPanelIndex | 1.3.6.1.4.1.13858.2.4.2.1.1 | PositiveInteger | RO | ||||||||||||||||||
column · PositiveInteger · read-only · current Identifies panel number that this module belongs to. The possible values are 1 through 8, starting from the top. | |||||||||||||||||||||
| CvpwrPanelModuleIndex | 1.3.6.1.4.1.13858.2.4.2.1.2 | PositiveInteger | RO | ||||||||||||||||||
column · PositiveInteger · read-only · current This object identifies the module within the panel. The orentation of modules within the panel is mappable. | |||||||||||||||||||||
| CvpwrPanelModuleSerNum | 1.3.6.1.4.1.13858.2.4.2.1.3 | OBJECT IDENTIFIER | RO | ||||||||||||||||||
column · OBJECT IDENTIFIER · read-only · current The module serial number. | |||||||||||||||||||||
| CvpwrPanelModuleModelName | 1.3.6.1.4.1.13858.2.4.2.1.4 | OBJECT IDENTIFIER | RO | ||||||||||||||||||
column · OBJECT IDENTIFIER · read-only · current The model name of the device. | |||||||||||||||||||||
| CvpwrPanelModuleFWVer | 1.3.6.1.4.1.13858.2.4.2.1.5 | OBJECT IDENTIFIER | RO | ||||||||||||||||||
column · OBJECT IDENTIFIER · read-only · current The module firmware version. | |||||||||||||||||||||
| CvpwrPanelModuleTestDate | 1.3.6.1.4.1.13858.2.4.2.1.6 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current The manufacturing test date. | |||||||||||||||||||||
| NvpwrSystemHistoryGroup | 1.3.6.1.4.1.13858.2.5 | ||||||||||||||||||||
| TvpwrSysHistAlarmTable | 1.3.6.1.4.1.13858.2.5.1 | NA | |||||||||||||||||||
table · not-accessible · current This table provides a list of most recent alarms. | |||||||||||||||||||||
| RvpwrSysHistAlarmEntry | 1.3.6.1.4.1.13858.2.5.1.1 | NA | |||||||||||||||||||
| CvpwrSysHistAlarmIndex | 1.3.6.1.4.1.13858.2.5.1.1.1 | PositiveInteger | RO | ||||||||||||||||||
column · PositiveInteger · read-only · current Alarm index. | |||||||||||||||||||||
| CvpwrSysHistAlarmDescription | 1.3.6.1.4.1.13858.2.5.1.1.2 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current Alarm description including time stamp. | |||||||||||||||||||||
| NvpwrSystemAlarmGroup | 1.3.6.1.4.1.13858.2.6 | ||||||||||||||||||||
| SvpwrSystemAlarmMajor | 1.3.6.1.4.1.13858.2.6.1 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current Indicates a Major Alarm exists on the system. | |||||||||||||||||||||
| SvpwrSystemAlarmMinor | 1.3.6.1.4.1.13858.2.6.2 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current Indicates a Minor Alarm exists on the system. | |||||||||||||||||||||
| SvpwrSystemACFailAlarm | 1.3.6.1.4.1.13858.2.6.3 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current One or more rectifiers have reported AC failure. If system is configured to report rectifier communication failure as AC fail this alarm will report. | |||||||||||||||||||||
| SvpwrSystemHighVoltageWarningAlarm | 1.3.6.1.4.1.13858.2.6.4 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current System has exceeded High Voltage Warning Setpoint. Check for high voltage on system bus. | |||||||||||||||||||||
| SvpwrSystemHighVoltageShutdownAlarm | 1.3.6.1.4.1.13858.2.6.5 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current One or more rectifiers have shut down due to high voltage present on output. Check bus voltage and reseat rectifiers that have indicated this problem. | |||||||||||||||||||||
| SvpwrSystemBatteryonDischargeAlarm | 1.3.6.1.4.1.13858.2.6.6 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current System voltage has currently dropped below the alarm setpoint. This may be due to battery testing or AC failure.
| |||||||||||||||||||||
| SvpwrSystemLowVoltageWarningAlarm | 1.3.6.1.4.1.13858.2.6.7 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current System Voltage has dropped below setpoint for Low Voltage Alarm. This may occur during battery testing or AC failure
| |||||||||||||||||||||
| SvpwrSystemLVDOpenAlarm | 1.3.6.1.4.1.13858.2.6.8 | Gauge32 | RO | ||||||||||||||||||
scalar · Gauge32 · read-only · current One or more contactors have opened. This occurs normally during system power on. If it occurs during operation this may indicate system is operating below LVD disconnect voltage. | |||||||||||||||||||||
| SvpwrSystemDistributionAlarm | 1.3.6.1.4.1.13858.2.6.9 | PositiveInteger | RO | ||||||||||||||||||
scalar · PositiveInteger · read-only · current One or more distribution alarm inputs are reporting an error condition. Check source of alarm and correct issue. | |||||||||||||||||||||
| SvpwrSystemAuxiliaryAlarm | 1.3.6.1.4.1.13858.2.6.10 | PositiveInteger | RO | ||||||||||||||||||
scalar · PositiveInteger · read-only · current One or more Auxliary alarm inputs are reporting an error condition. Check source of alarm and correct issue. | |||||||||||||||||||||
| SvpwrSystemRedundantCapAlarm | 1.3.6.1.4.1.13858.2.6.11 | PositiveInteger | RO | ||||||||||||||||||
scalar · PositiveInteger · read-only · current The system load has exceeded the requirements for redundancy. This may be a temporary system overload condition or caused by a rectifier alarm. | |||||||||||||||||||||
| SvpwrSystemRectIShareAlarm | 1.3.6.1.4.1.13858.2.6.12 | PositiveInteger | RO | ||||||||||||||||||
scalar · PositiveInteger · read-only · current One or more rectifiers are reporting a mismatch in current. This may be due to mismatched rectifier models or one or more rectifiers not current sharing | |||||||||||||||||||||
| SvpwrSystemSnglRectAlarm | 1.3.6.1.4.1.13858.2.6.13 | PositiveInteger | RO | ||||||||||||||||||
| SvpwrSystemMultRectAlarm | 1.3.6.1.4.1.13858.2.6.14 | PositiveInteger | RO | ||||||||||||||||||
| SvpwrSystemModlCommAlarm | 1.3.6.1.4.1.13858.2.6.15 | PositiveInteger | RO | ||||||||||||||||||
| SvpwrSystemOverTempAlarm | 1.3.6.1.4.1.13858.2.6.16 | PositiveInteger | RO | ||||||||||||||||||
| SvpwrSystemThermRAAlarm | 1.3.6.1.4.1.13858.2.6.17 | PositiveInteger | RO | ||||||||||||||||||
scalar · PositiveInteger · read-only · current Thermal Runaway has occurred on system. Check temperature inputs. | |||||||||||||||||||||
| SvpwrSystemBDTAlarm | 1.3.6.1.4.1.13858.2.6.18 | PositiveInteger | RO | ||||||||||||||||||
scalar · PositiveInteger · read-only · current System has entered Battery Discharge Test mode | |||||||||||||||||||||
| SvpwrSystemRectUVAlarm | 1.3.6.1.4.1.13858.2.6.19 | PositiveInteger | RO | ||||||||||||||||||
scalar · PositiveInteger · read-only · current Rectifier output has dropped 1V below Low Voltage Alarm setpoint | |||||||||||||||||||||
| SvpwrSystemMultRectUVAlarm | 1.3.6.1.4.1.13858.2.6.20 | PositiveInteger | RO | ||||||||||||||||||
| SvpwrSystemSnglRngrAlarm | 1.3.6.1.4.1.13858.2.6.21 | PositiveInteger | RO | ||||||||||||||||||
| SvpwrSystemMultRngrAlarm | 1.3.6.1.4.1.13858.2.6.22 | PositiveInteger | RO | ||||||||||||||||||
| SvpwrSystemTempProbeAlarm | 1.3.6.1.4.1.13858.2.6.23 | PositiveInteger | RO | ||||||||||||||||||
scalar · PositiveInteger · read-only · current Temp probe input missing or failed | |||||||||||||||||||||
| SvpwrSystemRngrCommAlarm | 1.3.6.1.4.1.13858.2.6.24 | PositiveInteger | RO | ||||||||||||||||||
scalar · PositiveInteger · read-only · current Ringer Module has stopped communicating with Controller. | |||||||||||||||||||||
| SvpwrSystemDistPMCommAlarm | 1.3.6.1.4.1.13858.2.6.25 | PositiveInteger | RO | ||||||||||||||||||
scalar · PositiveInteger · read-only · current One or more distribution alarm modules, TRIOs, or PM modules has stopped communicating with Controller. | |||||||||||||||||||||
| SvpwrSystemRectILimitAlarm | 1.3.6.1.4.1.13858.2.6.26 | PositiveInteger | RO | ||||||||||||||||||
scalar · PositiveInteger · read-only · current Rectifier has reached current limit setpoint. | |||||||||||||||||||||
| SvpwrSystemMultRectILimitAlarm | 1.3.6.1.4.1.13858.2.6.27 | PositiveInteger | RO | ||||||||||||||||||
| SvpwrSystemUnmappedI2CCANAlarm | 1.3.6.1.4.1.13858.2.6.28 | PositiveInteger | RO | ||||||||||||||||||
scalar · PositiveInteger · read-only · current Recheck all I2C and CAN dip switch settings. One or more devices in conflict. | |||||||||||||||||||||
| SvpwrSystemConfigErrAlarm | 1.3.6.1.4.1.13858.2.6.29 | PositiveInteger | RO | ||||||||||||||||||
scalar · PositiveInteger · read-only · current Recheck all I2C and CAN dip switch settings. One or more devices in conflict. | |||||||||||||||||||||
| SvpwrSystemDispFWAlarm | 1.3.6.1.4.1.13858.2.6.30 | PositiveInteger | RO | ||||||||||||||||||
| SvpwrSystemUndefinedAlarm | 1.3.6.1.4.1.13858.2.6.31 | PositiveInteger | RO | ||||||||||||||||||
| NvpwrDcPowerRectifier | 1.3.6.1.4.1.13858.3 | ||||||||||||||||||||
| NvpwrRectifierConfigGroup | 1.3.6.1.4.1.13858.3.1 | ||||||||||||||||||||
| SvpwrRectifierFVSetpoint | 1.3.6.1.4.1.13858.3.1.1 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current System Float Voltage setting
| |||||||||||||||||||||
| SvpwrRectifierHVSDSetpoint | 1.3.6.1.4.1.13858.3.1.2 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current System High Voltage Shutdown voltage setting
| |||||||||||||||||||||
| SvpwrRectifierCurrentLimitAdminState | 1.3.6.1.4.1.13858.3.1.3 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current This parameter allows enabling or rectifier current limit
| |||||||||||||||||||||
| SvpwrRectifierCurrentLimit | 1.3.6.1.4.1.13858.3.1.4 | INTEGER (5..220) | RW | ||||||||||||||||||
scalar · INTEGER (5..220) · read-write · current Rectifier current limit setpoint
| |||||||||||||||||||||
| SvpwrRectifierFallbackAdminState | 1.3.6.1.4.1.13858.3.1.5 | GenericEnableDisableTC | RW | ||||||||||||||||||
scalar · GenericEnableDisableTC · read-write · current Enables Rectifier to use Fallback Voltage when it loses communication with the controller. This applies to all rectifiers. | |||||||||||||||||||||
| SvpwrRectifierFallbackVoltage | 1.3.6.1.4.1.13858.3.1.6 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current Fallback Voltage setpoint to use when rectifier loses communication with the controller. This applies to all rectifiers.
| |||||||||||||||||||||
| NvpwrRectifierAlarmGroup | 1.3.6.1.4.1.13858.3.2 | ||||||||||||||||||||
| NvpwrRectAlarmDCFail | 1.3.6.1.4.1.13858.3.2.1 | ||||||||||||||||||||
| NvpwrRectAlarmBoostFail | 1.3.6.1.4.1.13858.3.2.2 | ||||||||||||||||||||
| NvpwrRectAlarmACFail | 1.3.6.1.4.1.13858.3.2.3 | ||||||||||||||||||||
| NvpwrRectAlarmHVSD | 1.3.6.1.4.1.13858.3.2.4 | ||||||||||||||||||||
| NvpwrRectAlarmFanFail | 1.3.6.1.4.1.13858.3.2.5 | ||||||||||||||||||||
| NvpwrRectAlarmAmbTemp | 1.3.6.1.4.1.13858.3.2.6 | ||||||||||||||||||||
| NvpwrRectAlarmIntTemp | 1.3.6.1.4.1.13858.3.2.7 | ||||||||||||||||||||
| NvpwrRectAlarmIShare | 1.3.6.1.4.1.13858.3.2.8 | ||||||||||||||||||||
| NvpwrRectAlarmUV | 1.3.6.1.4.1.13858.3.2.9 | ||||||||||||||||||||
| NvpwrRectAlarmLowVoltage | 1.3.6.1.4.1.13858.3.2.10 | ||||||||||||||||||||
| NvpwrRectAlarmReserved | 1.3.6.1.4.1.13858.3.2.11 | ||||||||||||||||||||
| NvpwrRectAlarmDCEnable | 1.3.6.1.4.1.13858.3.2.12 | ||||||||||||||||||||
| NvpwrRectAlarmRemoteShutdown | 1.3.6.1.4.1.13858.3.2.13 | ||||||||||||||||||||
| NvpwrRectAlarmModDisableShutdown | 1.3.6.1.4.1.13858.3.2.14 | ||||||||||||||||||||
| NvpwrRectAlarmShortPinShutdown | 1.3.6.1.4.1.13858.3.2.15 | ||||||||||||||||||||
| NvpwrRectAlarmBoostComm | 1.3.6.1.4.1.13858.3.2.16 | ||||||||||||||||||||
| NvpwrDcPowerLvd | 1.3.6.1.4.1.13858.4 | ||||||||||||||||||||
| NvpwrLvdConfigGroup | 1.3.6.1.4.1.13858.4.1 | ||||||||||||||||||||
| SvpwrLvdWarningSetpoint | 1.3.6.1.4.1.13858.4.1.1 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current LVD Warning voltage setpoint.
| |||||||||||||||||||||
| SvpwrLvdDisconnectSetpoint | 1.3.6.1.4.1.13858.4.1.2 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current LVD disconnect voltage setpoint.
| |||||||||||||||||||||
| SvpwrLvdReconnectSetpoint | 1.3.6.1.4.1.13858.4.1.3 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current LVD Reconnect voltage setpoint.
| |||||||||||||||||||||
| SvpwrLvdReconnectDelayTimer | 1.3.6.1.4.1.13858.4.1.4 | INTEGER (20..240) | RO | ||||||||||||||||||
scalar · INTEGER (20..240) · read-only · current The delay time, in seconds, before LVD is reconnected
| |||||||||||||||||||||
| SvpwrLvd2DisconnectSetpoint | 1.3.6.1.4.1.13858.4.1.7 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current LVD disconnect voltage setpoint.
| |||||||||||||||||||||
| SvpwrLvd2ReconnectSetpoint | 1.3.6.1.4.1.13858.4.1.8 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current LVD Reconnect voltage setpoint.
| |||||||||||||||||||||
| SvpwrLvd2ReconnectDelayTimer | 1.3.6.1.4.1.13858.4.1.9 | INTEGER (20..240) | RO | ||||||||||||||||||
scalar · INTEGER (20..240) · read-only · current The delay time, in seconds, before LVD is reconnected
| |||||||||||||||||||||
| SvpwrLvd3DisconnectSetpoint | 1.3.6.1.4.1.13858.4.1.11 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current LVD disconnect voltage setpoint.
| |||||||||||||||||||||
| SvpwrLvd3ReconnectSetpoint | 1.3.6.1.4.1.13858.4.1.12 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current LVD Reconnect voltage setpoint.
| |||||||||||||||||||||
| SvpwrLvd3ReconnectDelayTimer | 1.3.6.1.4.1.13858.4.1.13 | INTEGER (20..240) | RO | ||||||||||||||||||
scalar · INTEGER (20..240) · read-only · current The delay time, in seconds, before LVD is reconnected
| |||||||||||||||||||||
| SvpwrLvd4DisconnectSetpoint | 1.3.6.1.4.1.13858.4.1.15 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current LVD disconnect voltage setpoint.
| |||||||||||||||||||||
| SvpwrLvd4ReconnectSetpoint | 1.3.6.1.4.1.13858.4.1.16 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current LVD Reconnect voltage setpoint.
| |||||||||||||||||||||
| SvpwrLvd4ReconnectDelayTimer | 1.3.6.1.4.1.13858.4.1.17 | INTEGER (20..240) | RO | ||||||||||||||||||
scalar · INTEGER (20..240) · read-only · current The delay time, in seconds, before LVD is reconnected
| |||||||||||||||||||||
| SvpwrDCPowerLampTest | 1.3.6.1.4.1.13858.5 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current Lamp Test for modules
| |||||||||||||||||||||
| NvpwrDcPowerModuleIdent | 1.3.6.1.4.1.13858.6 | ||||||||||||||||||||
| TvpwrDcPowerModuleIdentTable | 1.3.6.1.4.1.13858.6.1 | NA | |||||||||||||||||||
table · not-accessible · current This table describes power modules that make up the system. | |||||||||||||||||||||
| RvpwrDcPowerModuleIdentEntry | 1.3.6.1.4.1.13858.6.1.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing information applicable to a power module. | |||||||||||||||||||||
| CvpwrBayIndex1 | 1.3.6.1.4.1.13858.6.1.1.1 | PositiveInteger | RO | ||||||||||||||||||
column · PositiveInteger · read-only · current Identifies shelf number that this module belongs to. The possible values are 1 through 2, starting from the top. | |||||||||||||||||||||
| CvpwrDCModuleIndex | 1.3.6.1.4.1.13858.6.1.1.2 | PositiveInteger | RO | ||||||||||||||||||
column · PositiveInteger · read-only · current This object identifies the module within the shelf. | |||||||||||||||||||||
| CvpwrModuleSerialNumber | 1.3.6.1.4.1.13858.6.1.1.3 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current Serial Number of the module | |||||||||||||||||||||
| CvpwrModuleModelNumber | 1.3.6.1.4.1.13858.6.1.1.4 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current Model Number of the module. | |||||||||||||||||||||
| CvpwrModuleFwVersion | 1.3.6.1.4.1.13858.6.1.1.5 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current Firmware version of the module. | |||||||||||||||||||||
| CvpwrModuleTestDate | 1.3.6.1.4.1.13858.6.1.1.6 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current Date when the module was last tested. | |||||||||||||||||||||
| CvpwrModuleOperHours | 1.3.6.1.4.1.13858.6.1.1.7 | Counter32 | RO | ||||||||||||||||||
column · Counter32 · read-only · current Cumulative Operating Hours. | |||||||||||||||||||||
| NvpwrDcPowerBatteryGroup | 1.3.6.1.4.1.13858.7 | ||||||||||||||||||||
| NvpwrBatteryTempGroup | 1.3.6.1.4.1.13858.7.1 | ||||||||||||||||||||
| TvpwrBatteryTempTable | 1.3.6.1.4.1.13858.7.1.1 | NA | |||||||||||||||||||
table · not-accessible · current This table describes battery temperature probes. | |||||||||||||||||||||
| RvpwrBatteryTempEntry | 1.3.6.1.4.1.13858.7.1.1.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing information applicable to a particular temperature probe.
| |||||||||||||||||||||
| CvpwrBatteryTempIndex | 1.3.6.1.4.1.13858.7.1.1.1.1 | INTEGER (0..255) | RO | 0 | |||||||||||||||||
| CvpwrBatteryTempName | 1.3.6.1.4.1.13858.7.1.1.1.2 | DisplayString (SIZE (1..8)) | RW | Main Batteries | |||||||||||||||||
| CvpwrBatteryTemp | 1.3.6.1.4.1.13858.7.1.1.1.3 | SysInputValue | RO | 30 | |||||||||||||||||
| SvpwrBatteryTempLThreshold | 1.3.6.1.4.1.13858.7.1.2 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current Temperature value at which a clear trap would be sent. All three battery temperature must be at or below this value to trigger this trap.
| |||||||||||||||||||||
| SvpwrBatteryTempUThreshold | 1.3.6.1.4.1.13858.7.1.3 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current Temperature value at which a set trap would be sent. Any one of the three battery temperatures at or exceeding this limit would trigger the trap.
| |||||||||||||||||||||
| SbatteryTempCompensation | 1.3.6.1.4.1.13858.7.1.4 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current This parameter enables/disables temperature compensation.
| |||||||||||||||||||||
| SbatteryTempCompHighStartTemperature | 1.3.6.1.4.1.13858.7.1.5 | INTEGER (25..60) | RW | ||||||||||||||||||
scalar · INTEGER (25..60) · read-write · current The temperature at which temperature compensation becomes active.
| |||||||||||||||||||||
| SbatteryTempCompHighStopVoltage | 1.3.6.1.4.1.13858.7.1.6 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current When temperature compensation is active, batteryTempCompHighStopVoltage is the
limit to which float voltage will be reduced.
For example, to set this voltage to 51.75 volts enter a value of 5175.
| |||||||||||||||||||||
| SbatteryTempCompHighSlope | 1.3.6.1.4.1.13858.7.1.7 | INTEGER (0..250) | RW | ||||||||||||||||||
scalar · INTEGER (0..250) · read-write · current The rate at which float voltage is changed, within the specified limits, when temperature compensation is active.
| |||||||||||||||||||||
| SbatteryTempCompLowStartTemperature | 1.3.6.1.4.1.13858.7.1.8 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current The temperature at which temperature compensation becomes active.
| |||||||||||||||||||||
| SbatteryTempCompLowStopVoltage | 1.3.6.1.4.1.13858.7.1.9 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current When temperature compensation is active, batteryTempCompLowStopVoltage is the
limit to which float voltage will be reduced.
For example, to set this voltage to 51.75 volts enter a value of 5175.
| |||||||||||||||||||||
| SbatteryTempCompLowSlope | 1.3.6.1.4.1.13858.7.1.10 | INTEGER (0..250) | RW | ||||||||||||||||||
scalar · INTEGER (0..250) · read-write · current The rate at which float voltage is changed, within the specified limits, when temperature compensation is active.
| |||||||||||||||||||||
| SbatteryTempCompRunawayTemperature | 1.3.6.1.4.1.13858.7.1.11 | INTEGER (25..60) | RW | ||||||||||||||||||
scalar · INTEGER (25..60) · read-write · current The temperature at which system voltage will be set to batteryTempCompRunawayStopVoltage.
| |||||||||||||||||||||
| SbatteryTempCompRunawayStopVoltage | 1.3.6.1.4.1.13858.7.1.12 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current When temperature compensation is enabled, float voltage will be reduced to batteryTempCompRunawayStopVoltage if temperature reaches batteryTempCompRunawayTemperature.
| |||||||||||||||||||||
| SbatteryTempCompSenseSource | 1.3.6.1.4.1.13858.7.1.13 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current This parameter selects the temperature sensing point for temperature compensation (in)activation.
| |||||||||||||||||||||
| SbatteryTempCompRunawayState | 1.3.6.1.4.1.13858.7.1.14 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current This parameter selects the temperature sensing point for temperature compensation (in)activation.
| |||||||||||||||||||||
| NvpwrBatteryCurrentGroup | 1.3.6.1.4.1.13858.7.2 | ||||||||||||||||||||
| SvpwrBatteryCurrentLimitAdminState | 1.3.6.1.4.1.13858.7.2.1 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current This parameter allows enabling or disabling battery current limit.
| |||||||||||||||||||||
| SvpwrBatteryCurrentLimit | 1.3.6.1.4.1.13858.7.2.2 | INTEGER (5..600) | RW | ||||||||||||||||||
scalar · INTEGER (5..600) · read-write · current
| |||||||||||||||||||||
| SvpwrBatteryCurrent | 1.3.6.1.4.1.13858.7.2.3 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current Battery current
| |||||||||||||||||||||
| NvpwrBatteryBoostGroup | 1.3.6.1.4.1.13858.7.3 | ||||||||||||||||||||
| SvpwrBoostAdminState | 1.3.6.1.4.1.13858.7.3.1 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current This parameter allows enabling or disabling boost.
| |||||||||||||||||||||
| SvpwrBoostVoltage | 1.3.6.1.4.1.13858.7.3.2 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current
| |||||||||||||||||||||
| SvpwrBoostDuration | 1.3.6.1.4.1.13858.7.3.3 | INTEGER (1..921599) | RW | ||||||||||||||||||
scalar · INTEGER (1..921599) · read-write · current Number of seconds for boost.
| |||||||||||||||||||||
| SvpwrBoostOperState | 1.3.6.1.4.1.13858.7.3.4 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current This parameter allows starting or stopping boost if it is enabled.
| |||||||||||||||||||||
| NvpwrBatteryDischargeTestGroup | 1.3.6.1.4.1.13858.7.4 | ||||||||||||||||||||
| SvpwrBDTAdminState | 1.3.6.1.4.1.13858.7.4.1 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current Enable / Disable Battery Discharge Test execution.
| |||||||||||||||||||||
| SvpwrBDTDuration | 1.3.6.1.4.1.13858.7.4.2 | INTEGER (0..64799) | RO | ||||||||||||||||||
scalar · INTEGER (0..64799) · read-only · current BDT Duration Setpoint.
| |||||||||||||||||||||
| SvpwrBDTAlarmVoltage | 1.3.6.1.4.1.13858.7.4.3 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current BDT Alarm Voltage Setpoint.
| |||||||||||||||||||||
| SvpwrBDTAbortVoltage | 1.3.6.1.4.1.13858.7.4.4 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current BDT Abort Voltage Setpoint.
| |||||||||||||||||||||
| SvpwrBDTAlarmCoefficient | 1.3.6.1.4.1.13858.7.4.5 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current Deprecated. Always returns 1
| |||||||||||||||||||||
| SvpwrBDTOperState | 1.3.6.1.4.1.13858.7.4.6 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current Start/Stop Battery Discharge Test execution.
| |||||||||||||||||||||
| SvpwrBDTClearAlarm | 1.3.6.1.4.1.13858.7.4.7 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current Clears any active BDT alarm.
| |||||||||||||||||||||
| SvpwrBDTActualTime | 1.3.6.1.4.1.13858.7.4.8 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current Actual BDT runtime in minutes.
| |||||||||||||||||||||
| SvpwrBDTAlarmDelay | 1.3.6.1.4.1.13858.7.4.9 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current Delay, in minutes, before checking and raising BDT alarm. Test: Plant Voltage <= BDTAlarmVoltage
| |||||||||||||||||||||
| SvpwrBDTResult | 1.3.6.1.4.1.13858.7.4.10 | BDTResultTC | RO | ||||||||||||||||||
scalar · BDTResultTC · read-only · current Results of BDT. | |||||||||||||||||||||
| SvpwrBDTAutoAdminState | 1.3.6.1.4.1.13858.7.4.11 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current Enable /Disable Battery Discharge Test data collection upon detecting AC Fail condition.
| |||||||||||||||||||||
| TvpwrBDTHistTable | 1.3.6.1.4.1.13858.7.4.12 | NA | |||||||||||||||||||
table · not-accessible · current This table provides results of past BDT test. | |||||||||||||||||||||
| RvpwrBDTHistEntry | 1.3.6.1.4.1.13858.7.4.12.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing information applicable to a particular BDT History.
| |||||||||||||||||||||
| CvpwrBDTHistIndex | 1.3.6.1.4.1.13858.7.4.12.1.1 | PositiveInteger | RO | ||||||||||||||||||
column · PositiveInteger · read-only · current BDT History index. | |||||||||||||||||||||
| CvpwrBDTHistDateTime | 1.3.6.1.4.1.13858.7.4.12.1.2 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current BDT run date as yr-mm-dd hh:mm | |||||||||||||||||||||
| CvpwrBDTHistDuration | 1.3.6.1.4.1.13858.7.4.12.1.3 | PositiveInteger | RO | ||||||||||||||||||
column · PositiveInteger · read-only · current BDT duration at the time this test was run.
| |||||||||||||||||||||
| CvpwrBDTHistAlarmVoltage | 1.3.6.1.4.1.13858.7.4.12.1.4 | PositiveInteger | RW | ||||||||||||||||||
column · PositiveInteger · read-write · current BDT Alarm Voltage setpoint when this test was run.
| |||||||||||||||||||||
| CvpwrBDTHistAbortVoltage | 1.3.6.1.4.1.13858.7.4.12.1.5 | PositiveInteger | RO | ||||||||||||||||||
column · PositiveInteger · read-only · current BDT Abort Voltage setpoint when this test was run.
| |||||||||||||||||||||
| CvpwrBDTHistStartMethod | 1.3.6.1.4.1.13858.7.4.12.1.6 | BDTStartSourceTC | RO | ||||||||||||||||||
column · BDTStartSourceTC · read-only · current How Battery Discharge Test was started. | |||||||||||||||||||||
| CvpwrBDTHistResult | 1.3.6.1.4.1.13858.7.4.12.1.7 | BDTResultTC | RO | ||||||||||||||||||
column · BDTResultTC · read-only · current Results of BDT. | |||||||||||||||||||||
| CvpwrBDTHistActualTime | 1.3.6.1.4.1.13858.7.4.12.1.8 | PositiveInteger | RO | ||||||||||||||||||
column · PositiveInteger · read-only · current Actual BDT runtime in minutes.
| |||||||||||||||||||||
| CvpwrBDTHistStartVoltage | 1.3.6.1.4.1.13858.7.4.12.1.9 | PositiveInteger | RO | ||||||||||||||||||
column · PositiveInteger · read-only · current Plant Voltage at the time the BDT was started.
| |||||||||||||||||||||
| CvpwrBDTHistEndVoltage | 1.3.6.1.4.1.13858.7.4.12.1.10 | PositiveInteger | RO | ||||||||||||||||||
column · PositiveInteger · read-only · current Plant Voltage at the time the BDT was completed.
| |||||||||||||||||||||
| TvpwrBDTSchedTable | 1.3.6.1.4.1.13858.7.4.13 | NA | |||||||||||||||||||
table · not-accessible · current This table provides the list of the 12 BDTs that can be scheduled. Need to set date(month and day) and time (hh and minutes) when the test should be started. | |||||||||||||||||||||
| RvpwrBDTSchedEntry | 1.3.6.1.4.1.13858.7.4.13.1 | NA | |||||||||||||||||||
| CvpwrBDTSchedIndex | 1.3.6.1.4.1.13858.7.4.13.1.1 | PositiveInteger | RO | ||||||||||||||||||
column · PositiveInteger · read-only · current BDT Sched index. | |||||||||||||||||||||
| CvpwrBDTSchedDay | 1.3.6.1.4.1.13858.7.4.13.1.2 | PositiveInteger | RW | ||||||||||||||||||
column · PositiveInteger · read-write · current 1 to 28,29,30 or 31 depending upon the month | |||||||||||||||||||||
| CvpwrBDTSchedMonth | 1.3.6.1.4.1.13858.7.4.13.1.3 | PositiveInteger | RW | ||||||||||||||||||
column · PositiveInteger · read-write · current range 1 to 12 | |||||||||||||||||||||
| CvpwrBDTSchedHour | 1.3.6.1.4.1.13858.7.4.13.1.4 | PositiveInteger | RW | ||||||||||||||||||
column · PositiveInteger · read-write · current range 0 to 23 | |||||||||||||||||||||
| CvpwrBDTSchedMinute | 1.3.6.1.4.1.13858.7.4.13.1.5 | PositiveInteger | RW | ||||||||||||||||||
column · PositiveInteger · read-write · current range 0 to 59 | |||||||||||||||||||||
| NvpwrDcPowerAlarmGroup | 1.3.6.1.4.1.13858.8 | ||||||||||||||||||||
| SvpwrAlarmsPresent | 1.3.6.1.4.1.13858.8.1 | Gauge32 | RO | ||||||||||||||||||
scalar · Gauge32 · read-only · current The present number of active alarm conditions. | |||||||||||||||||||||
| TvpwrAlarmTable | 1.3.6.1.4.1.13858.8.2 | NA | |||||||||||||||||||
table · not-accessible · current A list of alarm table entries. The table contains zero, one, or multiple rows at any time depending upon the number of alarm conditions in effect. The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row when that condition no longer exists. The vpwrAlarmIndex, for each type of module starts at 1 and is limited by the total number of alarms that can be generated by the module. Alarms are named by an AutonomousType (OBJECT IDENTIFIER), vpwrAlarmDescr, to allow a single table to reflect alarms for different types of modules. The number of rows in the table at any given time is reflected by the value of vpwrAlarmsPresent. | |||||||||||||||||||||
| RvpwrAlarmEntry | 1.3.6.1.4.1.13858.8.2.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing information applicable to a particular alarm. | |||||||||||||||||||||
| CvpwrAlarmIndex | 1.3.6.1.4.1.13858.8.2.1.1 | PositiveInteger | RO | ||||||||||||||||||
column · PositiveInteger · read-only · current Identifies the alarm associated with the module. It is unique on per module type basis. For example, multiple rectifiers can have the same alarm and therefore same vpwrAlarmIndex active at any one time. | |||||||||||||||||||||
| CvpwrAlarmDescr | 1.3.6.1.4.1.13858.8.2.1.2 | AutonomousType | RO | ||||||||||||||||||
column · AutonomousType · read-only · current A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition. | |||||||||||||||||||||
| CvpwrAlarmTime | 1.3.6.1.4.1.13858.8.2.1.3 | TimeStamp | RO | ||||||||||||||||||
column · TimeStamp · read-only · current The value of sysUpTime when the alarm condition was detected. | |||||||||||||||||||||
| TsysAlarmConfigTable | 1.3.6.1.4.1.13858.8.3 | NA | |||||||||||||||||||
table · not-accessible · current This table describes system alarm configuration and current status. | |||||||||||||||||||||
| RsysAlarmConfigEntry | 1.3.6.1.4.1.13858.8.3.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing information applicable to a particular system alarm.
| |||||||||||||||||||||
| CsysAlarmIndex | 1.3.6.1.4.1.13858.8.3.1.1 | INTEGER (0..255) | RO | ||||||||||||||||||
column · INTEGER (0..255) · read-only · current Index into system alarm table | |||||||||||||||||||||
| CsysAlarmDefaultName | 1.3.6.1.4.1.13858.8.3.1.2 | DisplayString (SIZE (1..8)) | RO | ||||||||||||||||||
column · DisplayString (SIZE (1..8)) · read-only · current Default alarm name. | |||||||||||||||||||||
| CsysAlarmCustomName | 1.3.6.1.4.1.13858.8.3.1.3 | DisplayString (SIZE (1..8)) | RW | ||||||||||||||||||
column · DisplayString (SIZE (1..8)) · read-write · current A custom alarm name. | |||||||||||||||||||||
| CsysAlarmSeverity | 1.3.6.1.4.1.13858.8.3.1.4 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current Alarm Severity as denoted by Major and Minor Alarm Mask
| |||||||||||||||||||||
| CsysAlarmToRelayMapping | 1.3.6.1.4.1.13858.8.3.1.5 | DisplayString (SIZE (1..8)) | RW | ||||||||||||||||||
column · DisplayString (SIZE (1..8)) · read-write · current No additional mapping = 0 Map to Relay A = 1 Map to Relay B = 2 Map to Relay C = 4 Map to Relay D = 8 Map to Relay E = 16 Map to Relay F = 32 Map to Relay A and B = (1 + 2) and so on The major/minor classification of alarms automatically associates it with Major/Minor relay. Assigning a null mapping here does not override vpwrPMRelayAlarmSeverity for the alarm. It should be used to define mapping to additional relays. | |||||||||||||||||||||
| CsysAlarmOperStatus | 1.3.6.1.4.1.13858.8.3.1.6 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current Indicates current alarm status
| |||||||||||||||||||||
| SsysAlarmComFailState | 1.3.6.1.4.1.13858.8.4 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current Enable/Disable generation of comm fail alarm.
| |||||||||||||||||||||
| SsysAlarmIShareState | 1.3.6.1.4.1.13858.8.5 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current Enable/Disable generation of current share alarm.
| |||||||||||||||||||||
| SsysAlarmRedundancyState | 1.3.6.1.4.1.13858.8.6 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current Enable/Disable generation of redundancy alarm.
| |||||||||||||||||||||
| SsysAlarmComFailToACFailState | 1.3.6.1.4.1.13858.8.7 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current Enable/Disable generation of ACF upon Com Fail
| |||||||||||||||||||||
| NvpwrDcPowerSnmpConfig | 1.3.6.1.4.1.13858.9 | ||||||||||||||||||||
| TvpwrTrapTable | 1.3.6.1.4.1.13858.9.1 | NA | |||||||||||||||||||
table · not-accessible · current A list of possible trap destinations depending upon the criticality of the trap. | |||||||||||||||||||||
| RvpwrTrapEntry | 1.3.6.1.4.1.13858.9.1.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing information applicable to a particular trap destination.
| |||||||||||||||||||||
| CvpwrTrapIpIndex | 1.3.6.1.4.1.13858.9.1.1.1 | INTEGER (0..255) | RO | ||||||||||||||||||
column · INTEGER (0..255) · read-only · current Trap Entry Index | |||||||||||||||||||||
| CvpwrTrapIpAddress | 1.3.6.1.4.1.13858.9.1.1.2 | IpAddress | RW | ||||||||||||||||||
column · IpAddress · read-write · current Trap destination IP Address | |||||||||||||||||||||
| CvpwrTrapCriticality | 1.3.6.1.4.1.13858.9.1.1.3 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current Criticality of traps sent to this IP Address | |||||||||||||||||||||
| SvpwrReadCommunityString | 1.3.6.1.4.1.13858.9.2 | DisplayString (SIZE (3..8)) | RW | ||||||||||||||||||
scalar · DisplayString (SIZE (3..8)) · read-write · current This allows setting password to be able to do Get operations | |||||||||||||||||||||
| SvpwrWriteCommunityString | 1.3.6.1.4.1.13858.9.3 | DisplayString (SIZE (3..8)) | RW | ||||||||||||||||||
scalar · DisplayString (SIZE (3..8)) · read-write · current This allows setting password to be able to do Get and Set operations. The read-access is not allowed in the actual implementation. | |||||||||||||||||||||
| SvpwrTrapCommunityString | 1.3.6.1.4.1.13858.9.4 | DisplayString (SIZE (3..8)) | RW | ||||||||||||||||||
scalar · DisplayString (SIZE (3..8)) · read-write · current This allows setting community string required for the trap to be accepted at the destination. | |||||||||||||||||||||
| SvpwrTrapVersion | 1.3.6.1.4.1.13858.9.5 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current This allows setting the version of trap message sent from the system | |||||||||||||||||||||
| NvpwrDcPowerTraps | 1.3.6.1.4.1.13858.10 | ||||||||||||||||||||
| !vpwrTrapPowerMajorAlarm | 1.3.6.1.4.1.13858.10.1 | ||||||||||||||||||||
| !vpwrTrapPowerMinorAlarm | 1.3.6.1.4.1.13858.10.2 | ||||||||||||||||||||
| !vpwrTrapACFAlarm | 1.3.6.1.4.1.13858.10.3 | ||||||||||||||||||||
| !vpwrTrapHVAlarm | 1.3.6.1.4.1.13858.10.4 | ||||||||||||||||||||
| !vpwrTrapHVSDAlarm | 1.3.6.1.4.1.13858.10.5 | ||||||||||||||||||||
| !vpwrTrapBDAlarm | 1.3.6.1.4.1.13858.10.6 | ||||||||||||||||||||
| !vpwrTrapLVDWarningAlarm | 1.3.6.1.4.1.13858.10.7 | ||||||||||||||||||||
| !vpwrTrapLVDOpenAlarm | 1.3.6.1.4.1.13858.10.8 | ||||||||||||||||||||
| !vpwrTrapDistAlarm | 1.3.6.1.4.1.13858.10.9 | ||||||||||||||||||||
| !vpwrTrapAuxAlarm | 1.3.6.1.4.1.13858.10.10 | ||||||||||||||||||||
| !vpwrTrapSystemRedundancyAlarm | 1.3.6.1.4.1.13858.10.11 | ||||||||||||||||||||
| !vpwrTrapIShareAlarm | 1.3.6.1.4.1.13858.10.12 | ||||||||||||||||||||
| !vpwrTrapModuleFailAlarm | 1.3.6.1.4.1.13858.10.13 | ||||||||||||||||||||
| !vpwrTrapMultipleModuleFailAlarm | 1.3.6.1.4.1.13858.10.14 | ||||||||||||||||||||
| !vpwrTrapModuleCommAlarm | 1.3.6.1.4.1.13858.10.15 | ||||||||||||||||||||
| !vpwrTrapSystemOverTemperatureAlarm | 1.3.6.1.4.1.13858.10.16 | ||||||||||||||||||||
| !vpwrTrapSystemOK | 1.3.6.1.4.1.13858.10.17 | ||||||||||||||||||||
| !vpwrTrapModuleInserted | 1.3.6.1.4.1.13858.10.18 | ||||||||||||||||||||
notification · current A new module has been inserted into the system | |||||||||||||||||||||
| !vpwrTrapModuleRemoved | 1.3.6.1.4.1.13858.10.19 | ||||||||||||||||||||
notification · current A module has been removed from the system | |||||||||||||||||||||
| !vpwrTrapThermalCompActive | 1.3.6.1.4.1.13858.10.20 | ||||||||||||||||||||
| !vpwrTrapThermalCompInactive | 1.3.6.1.4.1.13858.10.21 | ||||||||||||||||||||
| !vpwrTrapInternalTempAlarmSet | 1.3.6.1.4.1.13858.10.22 | ||||||||||||||||||||
notification · current !!! NOT VALID FOR BC2000 CONTROLLER !!! Internal Temperature upper threshold exceeded
| |||||||||||||||||||||
| !vpwrTrapInternalTempAlarmCleared | 1.3.6.1.4.1.13858.10.23 | ||||||||||||||||||||
notification · current !!! NOT VALID FOR BC2000 CONTROLLER !!! Internal Temperature within limits
| |||||||||||||||||||||
| !vpwrTrapBatteryTempAlarmSet | 1.3.6.1.4.1.13858.10.24 | ||||||||||||||||||||
notification · current !!! NOT VALID FOR BC2000 CONTROLLER !!! At least one Battery Temperature exceeded upper threshold
| |||||||||||||||||||||
| !vpwrTrapBatteryTempAlarmCleared | 1.3.6.1.4.1.13858.10.25 | ||||||||||||||||||||
notification · current !!! NOT VALID FOR BC2000 CONTROLLER !!! All Battery Temperatures within limits
| |||||||||||||||||||||
| !vpwrTrapLoginFail | 1.3.6.1.4.1.13858.10.26 | ||||||||||||||||||||
notification · current !!! NOT VALID FOR BC2000 CONTROLLER !!! Admin login failed due to wrong username/password
| |||||||||||||||||||||
| !vpwrTrapLoginSuccess | 1.3.6.1.4.1.13858.10.27 | ||||||||||||||||||||
notification · current !!! NOT VALID FOR BC2000 CONTROLLER !!! Admin login successful
| |||||||||||||||||||||
| !vpwrTrapLogout | 1.3.6.1.4.1.13858.10.28 | ||||||||||||||||||||
| !vpwrTrapAdminPwdChange | 1.3.6.1.4.1.13858.10.29 | ||||||||||||||||||||
notification · current !!! NOT VALID FOR BC2000 CONTROLLER !!! Config change submitted with invalid access
| |||||||||||||||||||||
| !vpwrTrapIllegalConfigSubmit | 1.3.6.1.4.1.13858.10.30 | ||||||||||||||||||||
notification · current !!! NOT VALID FOR BC2000 CONTROLLER !!! Config change submitted with invalid access
| |||||||||||||||||||||
| !vpwrTrapCfgChange | 1.3.6.1.4.1.13858.10.31 | ||||||||||||||||||||
notification · current !!! NOT VALID FOR BC2000 CONTROLLER !!! Config change submitted
| |||||||||||||||||||||
| !vpwrTrapClearEventHistory | 1.3.6.1.4.1.13858.10.32 | ||||||||||||||||||||
notification · current !!! NOT VALID FOR BC2000 CONTROLLER !!! Clear Event history buffer clear request
| |||||||||||||||||||||
| !vpwrTrapSwDownloadNoReboot | 1.3.6.1.4.1.13858.10.33 | ||||||||||||||||||||
notification · current !!! NOT VALID FOR BC2000 CONTROLLER !!! System software upgrade without reboot
| |||||||||||||||||||||
| !vpwrTrapSwDownloadAndReboot | 1.3.6.1.4.1.13858.10.34 | ||||||||||||||||||||
notification · current !!! NOT VALID FOR BC2000 CONTROLLER !!! System reboot due to software upgrade
| |||||||||||||||||||||
| !vpwrTrapSystemClockChange | 1.3.6.1.4.1.13858.10.35 | ||||||||||||||||||||
notification · current !!! NOT VALID FOR BC2000 CONTROLLER !!! System clock updated
| |||||||||||||||||||||
| !vpwrTrapModuleAlarm | 1.3.6.1.4.1.13858.10.36 | ||||||||||||||||||||
| !vpwrTrapOIDChange | 1.3.6.1.4.1.13858.10.37 | ||||||||||||||||||||
notification · current !!! NOT VALID FOR BC2000 CONTROLLER !!! Change in OID
| |||||||||||||||||||||
| !vpwrTrapThermalRunaway | 1.3.6.1.4.1.13858.10.38 | ||||||||||||||||||||
| !vpwrTrapBatteryDischargeTestAlarm | 1.3.6.1.4.1.13858.10.39 | ||||||||||||||||||||
| !vpwrTrapBayUnnameAlarm | 1.3.6.1.4.1.13858.10.40 | ||||||||||||||||||||
notification · current !!! NOT VALID FOR BC2000 CONTROLLER !!! Unassigned Bay Fail Alarm
| |||||||||||||||||||||
| !vpwrTrapPMComFailAlarm | 1.3.6.1.4.1.13858.10.41 | ||||||||||||||||||||
notification · current !!! NOT VALID FOR BC2000 CONTROLLER !!! PM Communication Fail Alarm
| |||||||||||||||||||||
| !vpwrTrapFuseOverloadAlarm | 1.3.6.1.4.1.13858.10.42 | ||||||||||||||||||||
notification · current !!! NOT VALID FOR BC2000 CONTROLLER !!! Fuse Overload Alarm
| |||||||||||||||||||||
| !vpwrTrapPeripheralAlarm | 1.3.6.1.4.1.13858.10.43 | ||||||||||||||||||||
notification · current !!! NOT VALID FOR BC2000 CONTROLLER !!! Peripheral Alarm.
| |||||||||||||||||||||
| !vpwrTrapThermalProbeAlarm | 1.3.6.1.4.1.13858.10.44 | ||||||||||||||||||||
| !vpwrTrapBayCommAlarm | 1.3.6.1.4.1.13858.10.45 | ||||||||||||||||||||
notification · current !!! NOT VALID FOR BC2000 CONTROLLER !!! Bay Communication Alarm
| |||||||||||||||||||||
| !vpwrTrapDistributionCommAlarm | 1.3.6.1.4.1.13858.10.46 | ||||||||||||||||||||
| !vpwrTrapConverterAlarm | 1.3.6.1.4.1.13858.10.47 | ||||||||||||||||||||
notification · current !!! NOT VALID FOR BC2000 CONTROLLER !!! Single Converter Fail Alarm
| |||||||||||||||||||||
| !vpwrTrapMultipleConvFailAlarm | 1.3.6.1.4.1.13858.10.48 | ||||||||||||||||||||
notification · current !!! NOT VALID FOR BC2000 CONTROLLER !!! Multiple Converter Fail Alarm
| |||||||||||||||||||||
| !vpwrTrapDGUAlarm | 1.3.6.1.4.1.13858.10.49 | ||||||||||||||||||||
| !vpwrTrapConfigErrorAlarm | 1.3.6.1.4.1.13858.10.50 | ||||||||||||||||||||
| !vpwrTrapDisplayFirmwareMismatchAlarm | 1.3.6.1.4.1.13858.10.51 | ||||||||||||||||||||
notification · current !!! NOT VALID FOR BC2000 CONTROLLER !!! Display Firmware Mismatch
| |||||||||||||||||||||
| !vpwrTrapConverterInputFailAlarm | 1.3.6.1.4.1.13858.10.52 | ||||||||||||||||||||
notification · current !!! NOT VALID FOR BC2000 CONTROLLER !!! Converter Input Fail Alarm
| |||||||||||||||||||||
| !vpwrTrapBatteryRechgIlimitFailAlarm | 1.3.6.1.4.1.13858.10.53 | ||||||||||||||||||||
notification · current !!! NOT VALID FOR BC2000 CONTROLLER !!! Battery Recharge Current Limit Fail
| |||||||||||||||||||||
| !vpwrTrapSystemAlive | 1.3.6.1.4.1.13858.10.54 | ||||||||||||||||||||
| !vpwrTrapSystemAuxAlmSource | 1.3.6.1.4.1.13858.10.55 | ||||||||||||||||||||
notification · current Source of Auxilary Alarms. Indicates the module and the aux within the module causing alarms | |||||||||||||||||||||
| !vpwrTrapSystemDistAlmSource | 1.3.6.1.4.1.13858.10.56 | ||||||||||||||||||||
notification · current Source of Distribution Alarms. Indicates the module and the dist within the module causing alarms | |||||||||||||||||||||
| !vpwrTrapSystemBatCapacityAlarm | 1.3.6.1.4.1.13858.10.58 | ||||||||||||||||||||
notification · current Plant Load exceeds Plant Battery Current Capacity. Useful for batteries that limit maximum discharge current It will not be sent out for VRLA batteries, eg | |||||||||||||||||||||
| !vpwrTrapSystemACFClearAlarm | 1.3.6.1.4.1.13858.10.61 | ||||||||||||||||||||
notification · current AC Fail (ACF) Conditioned Cleared Alarm. Duration is in minutes. | |||||||||||||||||||||
| !vpwrTrapSystemACFSetAlarm | 1.3.6.1.4.1.13858.10.62 | ||||||||||||||||||||
notification · current ACF Conditioned detected Alarm. The duration would always be zero. Msg String: ACF Alarm Set | |||||||||||||||||||||
| !vpwrTrapSystemBatCapacityLeft | 1.3.6.1.4.1.13858.10.64 | ||||||||||||||||||||
notification · current !!! For Future Use. !!! Battery Useful Capacity Remaining | |||||||||||||||||||||
| !vpwrTrapRectifierUVAlarm | 1.3.6.1.4.1.13858.10.65 | ||||||||||||||||||||
notification · current Rectifier Under Voltage Alarm | |||||||||||||||||||||
| !vpwrTrapMultRectifierUVAlarm | 1.3.6.1.4.1.13858.10.66 | ||||||||||||||||||||
notification · current !!! For Future Use. !!! Multiple Rectifier Under Voltage Alarm
| |||||||||||||||||||||
| !vpwrTrapRingerAlarm | 1.3.6.1.4.1.13858.10.67 | ||||||||||||||||||||
| !vpwrTrapMultRingerAlarm | 1.3.6.1.4.1.13858.10.68 | ||||||||||||||||||||
| !vpwrTrapI2CCANAlarm | 1.3.6.1.4.1.13858.10.69 | ||||||||||||||||||||
notification · current !!! For Future Use. !!! Unmapped I2C/CAN Address Alarm One of your I2C or CAN devices has a duplicate or invalid address and can not be mapped. Please recheck all device addresses.
| |||||||||||||||||||||
| !vpwrTrapRectifierIlimitAlarm | 1.3.6.1.4.1.13858.10.70 | ||||||||||||||||||||
notification · current Rectifier Current Limit Alarm | |||||||||||||||||||||
| !vpwrTrapMultRectifierIlimitAlarm | 1.3.6.1.4.1.13858.10.71 | ||||||||||||||||||||
notification · current !!! For Future Use. !!! Multiple Rectifier Current Limit Alarm
| |||||||||||||||||||||
| !vpwrTrapRingerCommAlarm | 1.3.6.1.4.1.13858.10.72 | ||||||||||||||||||||
| !vpwrTrapUnassignedAlarm | 1.3.6.1.4.1.13858.10.99 | ||||||||||||||||||||
notification · current !!! NOT VALID FOR BC2000 CONTROLLER !!! Unassigned Alarm(Trap) - Check Web Page
| |||||||||||||||||||||
| NvpwrDcPowerTrapVars | 1.3.6.1.4.1.13858.11 | ||||||||||||||||||||
| SvpwrTrapsMsgString | 1.3.6.1.4.1.13858.11.1 | DisplayString (SIZE (0..127)) | RO | ||||||||||||||||||
scalar · DisplayString (SIZE (0..127)) · read-only · current Place holder for trap notification message string | |||||||||||||||||||||
| SvpwrTrapUserIpAddress | 1.3.6.1.4.1.13858.11.2 | IpAddress | NA | ||||||||||||||||||
scalar · IpAddress · not-accessible · current Place holder for IP address of the user accessing the system | |||||||||||||||||||||
| SvpwrTrapAcfDuration | 1.3.6.1.4.1.13858.11.3 | NonNegativeInteger | RO | ||||||||||||||||||
scalar · NonNegativeInteger · read-only · current Place holder for duration. | |||||||||||||||||||||
| SvpwrAlarmingSubModuleBitMap | 1.3.6.1.4.1.13858.11.4 | PositiveInteger | RO | ||||||||||||||||||
scalar · PositiveInteger · read-only · current indices of alarming sources are encoded as a bit-map e.g., source 1 and source 2 will be encoded as hex 3. source 1 and 3 will be encoded as hex 5. | |||||||||||||||||||||
| SvpwrBatteryCurrentCapacity | 1.3.6.1.4.1.13858.11.5 | PositiveInteger | RO | ||||||||||||||||||
scalar · PositiveInteger · read-only · current Place holder for total battery capacity | |||||||||||||||||||||
| SvpwrAlarmingModuleIndex | 1.3.6.1.4.1.13858.11.6 | PositiveInteger | RO | ||||||||||||||||||
scalar · PositiveInteger · read-only · current index of alarming module. | |||||||||||||||||||||
| SvpwrAlarmingModuleOID | 1.3.6.1.4.1.13858.11.7 | OBJECT IDENTIFIER | RO | ||||||||||||||||||
scalar · OBJECT IDENTIFIER · read-only · current It indicates the type of the module by specifiying its OID | |||||||||||||||||||||
| SvpwrAlarmingModuleBitMap | 1.3.6.1.4.1.13858.11.8 | PositiveInteger | NA | ||||||||||||||||||
scalar · PositiveInteger · not-accessible · current indices of alarming sources are encoded as a bit-map e.g., source 1 and source 2 will be encoded as hex 3. source 1 and 3 will be encoded as hex 5. | |||||||||||||||||||||
| SvpwrBatteryRemainingTime | 1.3.6.1.4.1.13858.11.9 | PositiveInteger | RO | ||||||||||||||||||
scalar · PositiveInteger · read-only · current Place holder for remaining battery time at the current load | |||||||||||||||||||||
| NvpwrDcPowerRinger | 1.3.6.1.4.1.13858.12 | ||||||||||||||||||||
| NvpwrRingerConfigGroup | 1.3.6.1.4.1.13858.12.1 | ||||||||||||||||||||
| SvpwrRingerIndex | 1.3.6.1.4.1.13858.12.1.1 | INTEGER (0..2) | RW | ||||||||||||||||||
scalar · INTEGER (0..2) · read-write · current This parameter allows selecting ringer A or Ringer B as the active ringer. | |||||||||||||||||||||
| SvpwrRingerParameterAdminState | 1.3.6.1.4.1.13858.12.1.2 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current This parameter allows selecting ringer A or Ringer B as the active ringer.
| |||||||||||||||||||||
| SvpwrRingerParameterAcVoltage | 1.3.6.1.4.1.13858.12.1.3 | INTEGER (7000..10000) | RW | ||||||||||||||||||
scalar · INTEGER (7000..10000) · read-write · current This parameter sets the output AC voltage of the ringer.
| |||||||||||||||||||||
| SvpwrRingerParameterDcVoltage | 1.3.6.1.4.1.13858.12.1.4 | INTEGER (0..5500) | RW | ||||||||||||||||||
scalar · INTEGER (0..5500) · read-write · current This parameter sets the DC offset value of the ringer.
| |||||||||||||||||||||
| SvpwrRingerParameterFrequency | 1.3.6.1.4.1.13858.12.1.5 | INTEGER (17..50) | RW | ||||||||||||||||||
scalar · INTEGER (17..50) · read-write · current This parameter sets the ringer AC frequency.
| |||||||||||||||||||||
| SvpwrRingerNumberPresent | 1.3.6.1.4.1.13858.12.1.6 | Gauge32 | RO | ||||||||||||||||||
scalar · Gauge32 · read-only · current The present number of ringer modules. | |||||||||||||||||||||
| NvpwrRingerAlarmGroup | 1.3.6.1.4.1.13858.12.2 | ||||||||||||||||||||
| NvpwrRingerAlarmAFailed | 1.3.6.1.4.1.13858.12.2.1 | ||||||||||||||||||||
node · current Ringer A Failed | |||||||||||||||||||||
| NvpwrRingerAlarmAOverTemp | 1.3.6.1.4.1.13858.12.2.2 | ||||||||||||||||||||
node · current Ringer A Heatsink Over-Temperature | |||||||||||||||||||||
| NvpwrRingerAlarmAOverCurrent | 1.3.6.1.4.1.13858.12.2.3 | ||||||||||||||||||||
node · current Ringer A Over-Current protection | |||||||||||||||||||||
| NvpwrRingerAlarmBFailed | 1.3.6.1.4.1.13858.12.2.4 | ||||||||||||||||||||
node · current Ringer B Failed | |||||||||||||||||||||
| NvpwrRingerAlarmBOverTemp | 1.3.6.1.4.1.13858.12.2.5 | ||||||||||||||||||||
node · current Ringer B Heatsink Over-Temperature | |||||||||||||||||||||
| NvpwrRingerAlarmBOverCurrent | 1.3.6.1.4.1.13858.12.2.6 | ||||||||||||||||||||
node · current Ringer B Over-Current protection | |||||||||||||||||||||
| NvpwrRingerTestGroup | 1.3.6.1.4.1.13858.12.3 | ||||||||||||||||||||
| NvpwrDcPowerDcDcConverter | 1.3.6.1.4.1.13858.13 | ||||||||||||||||||||
| NvpwrDcDcConverterConfigGroup | 1.3.6.1.4.1.13858.13.1 | ||||||||||||||||||||
| NvpwrDcDcConverterAlarmGroup | 1.3.6.1.4.1.13858.13.2 | ||||||||||||||||||||
| NvpwrDcDcConverterTestGroup | 1.3.6.1.4.1.13858.13.3 | ||||||||||||||||||||
| NvpwrDcPowerDcAcInverter | 1.3.6.1.4.1.13858.14 | ||||||||||||||||||||
| NvpwrDcAcInverterConfigGroup | 1.3.6.1.4.1.13858.14.1 | ||||||||||||||||||||
| NvpwrDcAcInverterAlarmGroup | 1.3.6.1.4.1.13858.14.2 | ||||||||||||||||||||
| NvpwrDcAcInverterTestGroup | 1.3.6.1.4.1.13858.14.3 | ||||||||||||||||||||
| NvpwrDcPowerAcLineModule | 1.3.6.1.4.1.13858.15 | ||||||||||||||||||||
| NvpwrAcLineModuleConfigGroup | 1.3.6.1.4.1.13858.15.1 | ||||||||||||||||||||
| NvpwrAcLineModuleAlarmGroup | 1.3.6.1.4.1.13858.15.2 | ||||||||||||||||||||
| NvpwrAcLineModuleTestGroup | 1.3.6.1.4.1.13858.15.3 | ||||||||||||||||||||
| NvpwrDcPowerIoModule | 1.3.6.1.4.1.13858.16 | ||||||||||||||||||||
| NvpwrIoModuleConfigGroup | 1.3.6.1.4.1.13858.16.1 | ||||||||||||||||||||
| NvpwrIoModuleAlarmGroup | 1.3.6.1.4.1.13858.16.2 | ||||||||||||||||||||
| NvpwrIoModuleTestGroup | 1.3.6.1.4.1.13858.16.3 | ||||||||||||||||||||
| NvpwrDcPowerPMModule | 1.3.6.1.4.1.13858.17 | ||||||||||||||||||||
| TvpwrPMCnfgTable | 1.3.6.1.4.1.13858.17.1 | NA | |||||||||||||||||||
table · not-accessible · current This table shows the current configuration of the TRIO/PM86000/Controller inputs. | |||||||||||||||||||||
| RvpwrPMCnfgEntry | 1.3.6.1.4.1.13858.17.1.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing current configuration of the TRIO/PM86000/Controller inputs.
| |||||||||||||||||||||
| CvpwrPMIndex | 1.3.6.1.4.1.13858.17.1.1.1 | NonNegativeInteger | RO | ||||||||||||||||||
column · NonNegativeInteger · read-only · current This parameter describes which TRIO/PM86000 device is being accessed. | |||||||||||||||||||||
| CvpwrPMDescription | 1.3.6.1.4.1.13858.17.1.1.2 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current This parameter describes the configuration of the TRIO/PM86000 device. | |||||||||||||||||||||
| CvpwrPMCnfg1 | 1.3.6.1.4.1.13858.17.1.1.3 | VpwrPMCnfgValue | RW | ||||||||||||||||||
column · VpwrPMCnfgValue · read-write · current This parameter gets the current configuration of the TRIO/PM86000, input 1 | |||||||||||||||||||||
| CvpwrPMCnfg2 | 1.3.6.1.4.1.13858.17.1.1.4 | VpwrPMCnfgValue | RW | ||||||||||||||||||
column · VpwrPMCnfgValue · read-write · current This parameter gets the current configuration of the TRIO/PM86000, input 2 | |||||||||||||||||||||
| CvpwrPMCnfg3 | 1.3.6.1.4.1.13858.17.1.1.5 | VpwrPMCnfgValue | RW | ||||||||||||||||||
column · VpwrPMCnfgValue · read-write · current This parameter gets the current configuration of the TRIO/PM86000, input 3 | |||||||||||||||||||||
| CvpwrPMCnfg4 | 1.3.6.1.4.1.13858.17.1.1.6 | VpwrPMCnfgValue | RW | ||||||||||||||||||
column · VpwrPMCnfgValue · read-write · current This parameter gets the current configuration of the TRIO/PM86000, input 4 | |||||||||||||||||||||
| CvpwrPMCnfg5 | 1.3.6.1.4.1.13858.17.1.1.7 | VpwrPMCnfgValue | RW | ||||||||||||||||||
column · VpwrPMCnfgValue · read-write · current This parameter gets the current configuration of the TRIO/PM86000, input 5 | |||||||||||||||||||||
| CvpwrPMCnfg6 | 1.3.6.1.4.1.13858.17.1.1.8 | VpwrPMCnfgValue | RW | ||||||||||||||||||
column · VpwrPMCnfgValue · read-write · current This parameter gets the current configuration of the TRIO/PM86000, input 6 | |||||||||||||||||||||
| CvpwrPMCnfg7 | 1.3.6.1.4.1.13858.17.1.1.9 | VpwrPMCnfgValue | RW | ||||||||||||||||||
column · VpwrPMCnfgValue · read-write · current This parameter gets the current configuration of the TRIO (PM86000), input 7 | |||||||||||||||||||||
| CvpwrPMCnfg8 | 1.3.6.1.4.1.13858.17.1.1.10 | VpwrPMCnfgValue | RW | ||||||||||||||||||
column · VpwrPMCnfgValue · read-write · current This parameter gets the current configuration of the TRIO/PM86000, input 8 | |||||||||||||||||||||
| TvpwrPMInputStatusTable | 1.3.6.1.4.1.13858.17.2 | NA | |||||||||||||||||||
table · not-accessible · current This table shows the current values of the TRIO/PM86000/Controller inputs. | |||||||||||||||||||||
| RvpwrPMInputStatusEntry | 1.3.6.1.4.1.13858.17.2.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry containing current state of the TRIO/PM86000/Controller inputs.
| |||||||||||||||||||||
| CvpwrPMIndex1 | 1.3.6.1.4.1.13858.17.2.1.1 | NonNegativeInteger | RO | ||||||||||||||||||
column · NonNegativeInteger · read-only · current This parameter describes which TRIO/PM86000 device is being accessed. | |||||||||||||||||||||
| CvpwrPMDescription1 | 1.3.6.1.4.1.13858.17.2.1.2 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current This parameter describes the input values of the TRIO/PM86000 device. | |||||||||||||||||||||
| CvpwrPMInput1State | 1.3.6.1.4.1.13858.17.2.1.3 | SysInputValue | RO | ||||||||||||||||||
column · SysInputValue · read-only · current This parameter gets the current state of input 1 | |||||||||||||||||||||
| CvpwrPMInput2State | 1.3.6.1.4.1.13858.17.2.1.4 | SysInputValue | RO | ||||||||||||||||||
column · SysInputValue · read-only · current This parameter gets the current state of input 2 | |||||||||||||||||||||
| CvpwrPMInput3State | 1.3.6.1.4.1.13858.17.2.1.5 | SysInputValue | RO | ||||||||||||||||||
column · SysInputValue · read-only · current This parameter gets the current state of input 3 | |||||||||||||||||||||
| CvpwrPMInput4State | 1.3.6.1.4.1.13858.17.2.1.6 | SysInputValue | RO | ||||||||||||||||||
column · SysInputValue · read-only · current This parameter gets the current state of input 4 | |||||||||||||||||||||
| CvpwrPMInput5State | 1.3.6.1.4.1.13858.17.2.1.7 | SysInputValue | RO | ||||||||||||||||||
column · SysInputValue · read-only · current This parameter gets the current state of input 5 | |||||||||||||||||||||
| CvpwrPMInput6State | 1.3.6.1.4.1.13858.17.2.1.8 | SysInputValue | RO | ||||||||||||||||||
column · SysInputValue · read-only · current This parameter gets the current state of input 6 | |||||||||||||||||||||
| CvpwrPMInput7State | 1.3.6.1.4.1.13858.17.2.1.9 | SysInputValue | RO | ||||||||||||||||||
column · SysInputValue · read-only · current This parameter gets the current state of input 7 | |||||||||||||||||||||
| CvpwrPMInput8State | 1.3.6.1.4.1.13858.17.2.1.10 | SysInputValue | RO | ||||||||||||||||||
column · SysInputValue · read-only · current This parameter gets the current state of input 8 | |||||||||||||||||||||
| TvpwrPMRelayCtrlTable | 1.3.6.1.4.1.13858.17.3 | NA | |||||||||||||||||||
table · not-accessible · current This table describes/controls system relays. | |||||||||||||||||||||
| RvpwrPMRelayCtrlEntry | 1.3.6.1.4.1.13858.17.3.1 | NA | |||||||||||||||||||
| CvpwrPMIndex2 | 1.3.6.1.4.1.13858.17.3.1.1 | NonNegativeInteger | RO | ||||||||||||||||||
column · NonNegativeInteger · read-only · current This parameter describes the TRIO/PM device | |||||||||||||||||||||
| CvpwrPMDescription2 | 1.3.6.1.4.1.13858.17.3.1.2 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current This parameter describes the TRIO/PM device | |||||||||||||||||||||
| CvpwrPMRelay1State | 1.3.6.1.4.1.13858.17.3.1.3 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current This parameter sets the current state of relay 1
| |||||||||||||||||||||
| CvpwrPMRelay2State | 1.3.6.1.4.1.13858.17.3.1.4 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current This parameter sets the current state of relay 2
| |||||||||||||||||||||
| CvpwrPMRelay3State | 1.3.6.1.4.1.13858.17.3.1.5 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current This parameter sets the current state of relay 3
| |||||||||||||||||||||
| CvpwrPMRelay4State | 1.3.6.1.4.1.13858.17.3.1.6 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current This parameter sets the current state of relay 4
| |||||||||||||||||||||
| CvpwrPMRelay5State | 1.3.6.1.4.1.13858.17.3.1.7 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current This parameter sets the current state of relay 5
| |||||||||||||||||||||
| CvpwrPMRelay6State | 1.3.6.1.4.1.13858.17.3.1.8 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current This parameter sets the current state of relay 6
| |||||||||||||||||||||
| NvpwrPMModuleAlarmGroup | 1.3.6.1.4.1.13858.17.4 | ||||||||||||||||||||
| NvpwrPMModuleTestGroup | 1.3.6.1.4.1.13858.17.5 | ||||||||||||||||||||
| NvpwrDcPowerDistModule | 1.3.6.1.4.1.13858.18 | ||||||||||||||||||||
| NvpwrDcPowerBattery | 1.3.6.1.4.1.13858.19 | ||||||||||||||||||||
| NvpwrDcPowerController | 1.3.6.1.4.1.13858.20 | ||||||||||||||||||||
| NvpwrDcPowerUnkModule | 1.3.6.1.4.1.13858.499 | ||||||||||||||||||||
| NthirdPartyProduct | 1.3.6.1.4.1.13858.500 | ||||||||||||||||||||
Textual conventions
BDTResultTCINTEGERbdtResultAborted(4)bdtResultCleared(0)bdtResultFailed(2)bdtResultInProgress(5)bdtResultPassed(1)bdtResultStopped(3)The defines how was BDT started.
BDTStartSourceTCINTEGERbdtACFailStart(14)bdtInactive(0)bdtManualStart(1)bdtSched01Start1(2)bdtSched02Start2(3)bdtSched03Start3(4)bdtSched04Start4(5)bdtSched05Start5(6)bdtSched06Start6(7)bdtSched07Start7(8)bdtSched08Start8(9)bdtSched09Start9(10)bdtSched10Start10(11)bdtSched11Start11(12)bdtSched12Start12(13)The defines how was BDT started.
GenericEnableDisableTCINTEGERdisabled(0)enabled(1)The defines how was BDT started.
NonNegativeIntegerInteger32 (0..2147483647)Display hint:
dThis data type is a non-negative value.
PositiveIntegerInteger32 (1..2147483647)Display hint:
dThis data type is a non-zero and non-negative value.
SysInputValueINTEGERauxAlarm(-124)auxNormal(-123)disabled(-127)distAlarm(-122)distNormal(-121)removed(-126)shorted(-125)undefined(255)These are the results of the system input value definitions.
VpwrPMCnfgValueINTEGERauxNC(3)auxNO(2)disabled(0)distNC(5)distNO(4)tProbe(1)undefined(255)These are the results of the system input value definitions.
Traps / Notifications
- vpwrTrapACFAlarm
1.3.6.1.4.1.13858.10.3 - vpwrTrapAdminPwdChange
1.3.6.1.4.1.13858.10.29 - vpwrTrapAuxAlarm
1.3.6.1.4.1.13858.10.10 - vpwrTrapBDAlarm
1.3.6.1.4.1.13858.10.6 - vpwrTrapBatteryDischargeTestAlarm
1.3.6.1.4.1.13858.10.39 - vpwrTrapBatteryRechgIlimitFailAlarm
1.3.6.1.4.1.13858.10.53 - vpwrTrapBatteryTempAlarmCleared
1.3.6.1.4.1.13858.10.25 - vpwrTrapBatteryTempAlarmSet
1.3.6.1.4.1.13858.10.24 - vpwrTrapBayCommAlarm
1.3.6.1.4.1.13858.10.45 - vpwrTrapBayUnnameAlarm
1.3.6.1.4.1.13858.10.40 - vpwrTrapCfgChange
1.3.6.1.4.1.13858.10.31 - vpwrTrapClearEventHistory
1.3.6.1.4.1.13858.10.32 - vpwrTrapConfigErrorAlarm
1.3.6.1.4.1.13858.10.50 - vpwrTrapConverterAlarm
1.3.6.1.4.1.13858.10.47 - vpwrTrapConverterInputFailAlarm
1.3.6.1.4.1.13858.10.52 - vpwrTrapDGUAlarm
1.3.6.1.4.1.13858.10.49 - vpwrTrapDisplayFirmwareMismatchAlarm
1.3.6.1.4.1.13858.10.51 - vpwrTrapDistAlarm
1.3.6.1.4.1.13858.10.9 - vpwrTrapDistributionCommAlarm
1.3.6.1.4.1.13858.10.46 - vpwrTrapFuseOverloadAlarm
1.3.6.1.4.1.13858.10.42 - vpwrTrapHVAlarm
1.3.6.1.4.1.13858.10.4 - vpwrTrapHVSDAlarm
1.3.6.1.4.1.13858.10.5 - vpwrTrapI2CCANAlarm
1.3.6.1.4.1.13858.10.69 - vpwrTrapIShareAlarm
1.3.6.1.4.1.13858.10.12 - vpwrTrapIllegalConfigSubmit
1.3.6.1.4.1.13858.10.30 - vpwrTrapInternalTempAlarmCleared
1.3.6.1.4.1.13858.10.23 - vpwrTrapInternalTempAlarmSet
1.3.6.1.4.1.13858.10.22 - vpwrTrapLVDOpenAlarm
1.3.6.1.4.1.13858.10.8 - vpwrTrapLVDWarningAlarm
1.3.6.1.4.1.13858.10.7 - vpwrTrapLoginFail
1.3.6.1.4.1.13858.10.26 - vpwrTrapLoginSuccess
1.3.6.1.4.1.13858.10.27 - vpwrTrapLogout
1.3.6.1.4.1.13858.10.28 - vpwrTrapModuleAlarm
1.3.6.1.4.1.13858.10.36 - vpwrTrapModuleCommAlarm
1.3.6.1.4.1.13858.10.15 - vpwrTrapModuleFailAlarm
1.3.6.1.4.1.13858.10.13 - vpwrTrapModuleInserted
1.3.6.1.4.1.13858.10.18 - vpwrTrapModuleRemoved
1.3.6.1.4.1.13858.10.19 - vpwrTrapMultRectifierIlimitAlarm
1.3.6.1.4.1.13858.10.71 - vpwrTrapMultRectifierUVAlarm
1.3.6.1.4.1.13858.10.66 - vpwrTrapMultRingerAlarm
1.3.6.1.4.1.13858.10.68 - vpwrTrapMultipleConvFailAlarm
1.3.6.1.4.1.13858.10.48 - vpwrTrapMultipleModuleFailAlarm
1.3.6.1.4.1.13858.10.14 - vpwrTrapOIDChange
1.3.6.1.4.1.13858.10.37 - vpwrTrapPMComFailAlarm
1.3.6.1.4.1.13858.10.41 - vpwrTrapPeripheralAlarm
1.3.6.1.4.1.13858.10.43 - vpwrTrapPowerMajorAlarm
1.3.6.1.4.1.13858.10.1 - vpwrTrapPowerMinorAlarm
1.3.6.1.4.1.13858.10.2 - vpwrTrapRectifierIlimitAlarm
1.3.6.1.4.1.13858.10.70 - vpwrTrapRectifierUVAlarm
1.3.6.1.4.1.13858.10.65 - vpwrTrapRingerAlarm
1.3.6.1.4.1.13858.10.67 - vpwrTrapRingerCommAlarm
1.3.6.1.4.1.13858.10.72 - vpwrTrapSwDownloadAndReboot
1.3.6.1.4.1.13858.10.34 - vpwrTrapSwDownloadNoReboot
1.3.6.1.4.1.13858.10.33 - vpwrTrapSystemACFClearAlarm
1.3.6.1.4.1.13858.10.61 - vpwrTrapSystemACFSetAlarm
1.3.6.1.4.1.13858.10.62 - vpwrTrapSystemAlive
1.3.6.1.4.1.13858.10.54 - vpwrTrapSystemAuxAlmSource
1.3.6.1.4.1.13858.10.55 - vpwrTrapSystemBatCapacityAlarm
1.3.6.1.4.1.13858.10.58 - vpwrTrapSystemBatCapacityLeft
1.3.6.1.4.1.13858.10.64 - vpwrTrapSystemClockChange
1.3.6.1.4.1.13858.10.35 - vpwrTrapSystemDistAlmSource
1.3.6.1.4.1.13858.10.56 - vpwrTrapSystemOK
1.3.6.1.4.1.13858.10.17 - vpwrTrapSystemOverTemperatureAlarm
1.3.6.1.4.1.13858.10.16 - vpwrTrapSystemRedundancyAlarm
1.3.6.1.4.1.13858.10.11 - vpwrTrapThermalCompActive
1.3.6.1.4.1.13858.10.20 - vpwrTrapThermalCompInactive
1.3.6.1.4.1.13858.10.21 - vpwrTrapThermalProbeAlarm
1.3.6.1.4.1.13858.10.44 - vpwrTrapThermalRunaway
1.3.6.1.4.1.13858.10.38 - vpwrTrapUnassignedAlarm
1.3.6.1.4.1.13858.10.99