XUPS-MIB
Eaton CorporationDefines Eaton's proprietary PowerMIB for UPS and related device data. Copyright (C) Exide Electronics 1992-98 Copyright (C) Powerware Corporation 1999-2004 Copyright (C) Eaton Corporation (2005-).
snmptranslate -m XUPS-MIB -Tpsnmpwalk -v2c -c <community> -m XUPS-MIB <host> 1.3.6.1.4.1.534.1Imports
| EATON-EMP-MIB | xupsContactDescr, xupsContactIndex, xupsContactState, xupsContactType, xupsEnvRemoteHumidity, xupsEnvRemoteHumidityLowerLimit, xupsEnvRemoteHumidityUpperLimit, xupsEnvRemoteTemp, xupsEnvRemoteTempLowerLimit, xupsEnvRemoteTempUpperLimit |
|---|---|
| EATON-OIDS | eaton, xupsEnvironment |
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP, OBJECT-GROUP |
| SNMPv2-MIB | sysName |
| SNMPv2-SMI | Bits, Counter32, Gauge32, Integer32, IpAddress, MODULE-IDENTITY, MibIdentifier, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, TimeTicks, Unsigned32, iso |
| SNMPv2-TC | DisplayString, PhysAddress, TEXTUAL-CONVENTION |
OID tree
| Name | OID | Type | Access | Status | Example | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| IxupsMIB | 1.3.6.1.4.1.534.1 | ||||||||||||||||||||
identity Defines Eaton's proprietary PowerMIB for UPS and related device data. Copyright (C) Exide Electronics 1992-98 Copyright (C) Powerware Corporation 1999-2004 Copyright (C) Eaton Corporation (2005-). | |||||||||||||||||||||
| NxupsIdent | 1.3.6.1.4.1.534.1.1 | ||||||||||||||||||||
| SxupsIdentManufacturer | 1.3.6.1.4.1.534.1.1.1 | DisplayString (SIZE (0..31)) | RO | EATON | |||||||||||||||||
scalar · DisplayString (SIZE (0..31)) · read-only · current The UPS Manufacturer Name (e.g. Eaton Corporation). Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsIdentModel | 1.3.6.1.4.1.534.1.1.2 | DisplayString (SIZE (0..63)) | RO | Eaton 9PX 1000i RT 2U | |||||||||||||||||
scalar · DisplayString (SIZE (0..63)) · read-only · current The UPS Model (e.g. Powerware Plus Model 18). Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsIdentSoftwareVersion | 1.3.6.1.4.1.534.1.1.3 | DisplayString (SIZE (0..63)) | RO | INV: 01.16.4638 | |||||||||||||||||
scalar · DisplayString (SIZE (0..63)) · read-only · current The firmware revision level(s) of the UPS microcontroller(s). Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsIdentOemCode | 1.3.6.1.4.1.534.1.1.4 | Integer32 (0..255) | RO | 16 | |||||||||||||||||
scalar · Integer32 (0..255) · read-only · current A binary code indicating who the UPS was manufactured or labeled for. 0 or 255 indicates Eaton itself. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsIdentPartNumber | 1.3.6.1.4.1.534.1.1.5 | OCTET STRING (SIZE (1..31)) | RO | 9PX1000iRT2U | |||||||||||||||||
scalar · OCTET STRING (SIZE (1..31)) · read-only · current The catalog part number of the UPS device. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsIdentSerialNumber | 1.3.6.1.4.1.534.1.1.6 | OCTET STRING (SIZE (1..31)) | RO | GA10K33096 | |||||||||||||||||
scalar · OCTET STRING (SIZE (1..31)) · read-only · current The serial number of the UPS device. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NxupsBattery | 1.3.6.1.4.1.534.1.2 | ||||||||||||||||||||
| SxupsBatTimeRemaining | 1.3.6.1.4.1.534.1.2.1 | Integer32 (0..2147483647) | RO | 1132 | |||||||||||||||||
scalar · Integer32 (0..2147483647) · read-only · current Battery run time in seconds before UPS turns off due to low battery.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsBatVoltage | 1.3.6.1.4.1.534.1.2.2 | Integer32 (0..2147483647) | RO | 55 | |||||||||||||||||
scalar · Integer32 (0..2147483647) · read-only · current Battery voltage as reported by the UPS meters.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsBatCurrent | 1.3.6.1.4.1.534.1.2.3 | Integer32 (-2147483648..2147483647) | RO | 0 | |||||||||||||||||
scalar · Integer32 (-2147483648..2147483647) · read-only · current Battery Current as reported by the UPS metering. Current is positive when discharging, negative when recharging the battery.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsBatCapacity | 1.3.6.1.4.1.534.1.2.4 | Integer32 (0..100) | RO | 91 | |||||||||||||||||
scalar · Integer32 (0..100) · read-only · current Battery percent charge.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsBatteryAbmStatus | 1.3.6.1.4.1.534.1.2.5 | INTEGER | RO | batteryFloating(3) | |||||||||||||||||
scalar · INTEGER · read-only · current Gives the status of the Advanced Battery Management and Battery state; batteryFloating(3) status means that the charger is temporarily charging the battery to its float voltage; batteryResting(4) is the state when the battery is fully charged and none of the other actions (charging/discharging/floating) is being done. checkBattery(8) indicates that the Battery state is uncertain following a poor battery test result.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsBatteryLastReplacedDate | 1.3.6.1.4.1.534.1.2.6 | DisplayString (SIZE (0..16)) | RO | | |||||||||||||||||
scalar · DisplayString (SIZE (0..16)) · read-only · current The date when the Batteries in this UPS were last replaced. Free text format, so the preferred local date format may be used (MM/DD/YYYY, DD-Mon-YYYY, etc). Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsBatteryFailure | 1.3.6.1.4.1.534.1.2.7 | INTEGER | RO | no(2) | |||||||||||||||||
scalar · INTEGER · read-only · current Indicates if a battery fault detected or battery tests failed.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsBatteryNotPresent | 1.3.6.1.4.1.534.1.2.8 | INTEGER | RO | no(2) | |||||||||||||||||
scalar · INTEGER · read-only · current Indicates if the UPS has no battery either internal or external.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsBatteryAged | 1.3.6.1.4.1.534.1.2.9 | INTEGER | RO | no(2) | |||||||||||||||||
scalar · INTEGER · read-only · current Indicates if the battery is over aged.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsBatteryLowCapacity | 1.3.6.1.4.1.534.1.2.10 | INTEGER | RO | no(2) | |||||||||||||||||
scalar · INTEGER · read-only · current Indicates if the battery capacity is below the threshold set in the UPS.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NxupsInput | 1.3.6.1.4.1.534.1.3 | ||||||||||||||||||||
| SxupsInputFrequency | 1.3.6.1.4.1.534.1.3.1 | Integer32 (0..2147483647) | RO | 500 | |||||||||||||||||
scalar · Integer32 (0..2147483647) · read-only · current The utility line frequency in tenths of Hz.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsInputLineBads | 1.3.6.1.4.1.534.1.3.2 | Counter32 | RO | 2 | |||||||||||||||||
scalar · Counter32 · read-only · current The number of times the Input was out of tolerance in voltage or frequency. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsInputNumPhases | 1.3.6.1.4.1.534.1.3.3 | Integer32 (0..6) | RO | 1 | |||||||||||||||||
scalar · Integer32 (0..6) · read-only · current The number of input phases (normally 1 to 3). Example values from LibreNMS test devices
| |||||||||||||||||||||
| TxupsInputTable | 1.3.6.1.4.1.534.1.3.4 | NA | |||||||||||||||||||
table · not-accessible · current A list of input table entries. The number of entries is given by the value of xupsInputNumPhases. | |||||||||||||||||||||
| RxupsInputEntry | 1.3.6.1.4.1.534.1.3.4.1 | NA | |||||||||||||||||||
row · not-accessible · current The input table entry containing the current, voltage, etc. readings for one phase.
| |||||||||||||||||||||
| CxupsInputPhase | 1.3.6.1.4.1.534.1.3.4.1.1 | Integer32 (0..6) | RO | 1 | |||||||||||||||||
column · Integer32 (0..6) · read-only · current The number of the phase. Serves as index for input table. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CxupsInputVoltage | 1.3.6.1.4.1.534.1.3.4.1.2 | Integer32 (0..2147483647) | RO | 229 | |||||||||||||||||
column · Integer32 (0..2147483647) · read-only · current The measured input voltage from the UPS meters in volts.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CxupsInputCurrent | 1.3.6.1.4.1.534.1.3.4.1.3 | Integer32 (0..2147483647) | RO | 0 | |||||||||||||||||
column · Integer32 (0..2147483647) · read-only · current The measured input current from the UPS meters in amps.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CxupsInputWatts | 1.3.6.1.4.1.534.1.3.4.1.4 | Integer32 (0..2147483647) | RO | 0 | |||||||||||||||||
column · Integer32 (0..2147483647) · read-only · current The measured input real power in watts.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CxupsInputId | 1.3.6.1.4.1.534.1.3.4.1.5 | INTEGER | RO | phase1toN(1) | |||||||||||||||||
column · INTEGER · read-only · current value indicates what measurement is being stored in this table row : phase1 to neutral, phase2 to neutral, phase3 to neutral, phase1 to phase2, phase2 to phase3, phase3 to phase1.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CxupsInputName | 1.3.6.1.4.1.534.1.3.4.1.6 | OCTET STRING (SIZE (1..31)) | RO | L1/A | |||||||||||||||||
column · OCTET STRING (SIZE (1..31)) · read-only · current A descriptive name for the phase, example : L1/A for the phase 1. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CxupsInputCurrentHighPrecision | 1.3.6.1.4.1.534.1.3.4.1.7 | Integer32 (0..2147483647) | RO | ||||||||||||||||||
column · Integer32 (0..2147483647) · read-only · current The measured input current from the UPS meters in tenth of amps.
| |||||||||||||||||||||
| SxupsInputSource | 1.3.6.1.4.1.534.1.3.5 | INTEGER | RO | primaryUtility(3) | |||||||||||||||||
scalar · INTEGER · read-only · current The present external source of input power. The enumeration
'none(2)' indicates that there is no external source of
power, for example, the UPS is On Battery (an internal source).
'primaryUtility' indicates the normal case of utility input power.
The 'bypassFeed' can only be used when the Bypass source is known
to be a separate utility feed than the primaryUtility(3).
'secondaryUtility' indicates that a secondary utility feed is supplying
power (on a dual AC input UPS).
'generator' indicates that input power is provided by a generator.
Note that the alternate energy sources of 'flywheel' and 'fuelcell' are
not necessarily AC input sources.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsDualInputStatus | 1.3.6.1.4.1.534.1.3.6 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current The present status of the sources of input power in a dual source UPS.
The enumeration primarySourceGood(2) indicates that the primary source
of power is present and within 'normal' ranges for voltage and
frequency, but the secondary source is either not present or not in an
acceptable range.
'secondarySourceGood' indicates that only the Secondary power feed is
available and within its limits.
The enumeration bothSourcesGood(4) indicates that both sources are present
and within their respective 'normal' ranges;
bothSourcesBad(1) indicates that neither source is present, or, if present,
is not within acceptable ranges.
This object will only be implemented for UPSs with two sources of input
power, e.g., redundant AC feeds or a separate Bypass or Generator source.
The secondary source will not be an AC power source in all cases.
| |||||||||||||||||||||
| SxupsSecondaryInputWatch | 1.3.6.1.4.1.534.1.3.7 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current This object enables(2) or disables(1) the alarms and traps related to the availability and use of the secondary input of a dual-input UPS (i.e., OnAlternatePowerSource and AltPowerNotAvailable). To avoid nuisance alarms and traps, this object should be set to disabled(1) when the UPS is not wired to a secondary source of power. This object will only be implemented for UPSs with two sources of input power, i.e., redundant AC feeds or a separate Bypass or Generator source.
| |||||||||||||||||||||
| NxupsInputTotal | 1.3.6.1.4.1.534.1.3.8 | ||||||||||||||||||||
| SxupsInputAverageVoltage | 1.3.6.1.4.1.534.1.3.8.1 | Integer32 (0..2147483647) | RO | 238 | |||||||||||||||||
scalar · Integer32 (0..2147483647) · read-only · current The measured input voltage from the UPS meters in volts. Related to the phase 1 if the UPS is single phase, either it is average of all the simple phase voltage.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsInputTotalCurrent | 1.3.6.1.4.1.534.1.3.8.2 | Integer32 (0..2147483647) | RO | ||||||||||||||||||
scalar · Integer32 (0..2147483647) · read-only · current The measured input current from the UPS meters in tenth of amps. Related to the phase 1 if the UPS is single phase, either it is average of all the simple phase current.
| |||||||||||||||||||||
| SxupsInputTotalWatts | 1.3.6.1.4.1.534.1.3.8.3 | Integer32 (0..2147483647) | RO | ||||||||||||||||||
scalar · Integer32 (0..2147483647) · read-only · current The measured input active power in watts. Sum of all the simple phase watts.
| |||||||||||||||||||||
| SxupsInputTotalVA | 1.3.6.1.4.1.534.1.3.8.4 | Integer32 (0..2147483647) | RO | ||||||||||||||||||
scalar · Integer32 (0..2147483647) · read-only · current The measured input apparent power in VA. Sum of all the simple phase VA.
| |||||||||||||||||||||
| SxupsInputAveragePowerFactor | 1.3.6.1.4.1.534.1.3.8.5 | Integer32 | RO | ||||||||||||||||||
scalar · Integer32 · read-only · current Indicates the total power factor of the input in hundredths. 0.92 would be returned as 92. | |||||||||||||||||||||
| SxupsInputStatus | 1.3.6.1.4.1.534.1.3.9 | INTEGER | RO | inputGood(2) | |||||||||||||||||
scalar · INTEGER · read-only · current The present status of the primary AC input of the UPS. The enumeration inputGood(2) indicates that the primary source of power is present and within 'normal' ranges for voltage and frequency. inputBad(1) indicates that neither source is present, or, if present, is not within acceptable ranges.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NxupsOutput | 1.3.6.1.4.1.534.1.4 | ||||||||||||||||||||
| SxupsOutputLoad | 1.3.6.1.4.1.534.1.4.1 | Integer32 (0..200) | RO | 40 | |||||||||||||||||
scalar · Integer32 (0..200) · read-only · current The UPS output load in percent of rated capacity.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsOutputFrequency | 1.3.6.1.4.1.534.1.4.2 | Integer32 (0..2147483647) | RO | 500 | |||||||||||||||||
scalar · Integer32 (0..2147483647) · read-only · current The measured UPS output frequency in tenths of Hz.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsOutputNumPhases | 1.3.6.1.4.1.534.1.4.3 | Integer32 (0..6) | RO | 1 | |||||||||||||||||
scalar · Integer32 (0..6) · read-only · current The number of metered output phases. Example values from LibreNMS test devices
| |||||||||||||||||||||
| TxupsOutputTable | 1.3.6.1.4.1.534.1.4.4 | NA | |||||||||||||||||||
table · not-accessible · current A list of output table entries. The number of entries is given by the value of xupsOutputNumPhases. | |||||||||||||||||||||
| RxupsOutputEntry | 1.3.6.1.4.1.534.1.4.4.1 | NA | |||||||||||||||||||
row · not-accessible · current Output Table Entry containing voltage, current, etc.
| |||||||||||||||||||||
| CxupsOutputPhase | 1.3.6.1.4.1.534.1.4.4.1.1 | Integer32 (0..6) | RO | 1 | |||||||||||||||||
column · Integer32 (0..6) · read-only · current The number of the phase. Serves as index for output table. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CxupsOutputVoltage | 1.3.6.1.4.1.534.1.4.4.1.2 | Integer32 (0..2147483647) | RO | 230 | |||||||||||||||||
column · Integer32 (0..2147483647) · read-only · current The measured output voltage from the UPS metering in volts.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CxupsOutputCurrent | 1.3.6.1.4.1.534.1.4.4.1.3 | Integer32 (0..2147483647) | RO | 1 | |||||||||||||||||
column · Integer32 (0..2147483647) · read-only · current The measured UPS output current in amps.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CxupsOutputWatts | 1.3.6.1.4.1.534.1.4.4.1.4 | Integer32 (0..2147483647) | RO | 360 | |||||||||||||||||
column · Integer32 (0..2147483647) · read-only · current The measured real output power in watts.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CxupsOutputId | 1.3.6.1.4.1.534.1.4.4.1.5 | INTEGER | RO | phase1toN(1) | |||||||||||||||||
column · INTEGER · read-only · current value indicates what measurement is being stored in this table row : phase1 to neutral, phase2 to neutral, phase3 to neutral, phase1 to phase2, phase2 to phase3, phase3 to phase1.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CxupsOutputName | 1.3.6.1.4.1.534.1.4.4.1.6 | OCTET STRING (SIZE (1..31)) | RO | L1/A | |||||||||||||||||
column · OCTET STRING (SIZE (1..31)) · read-only · current A descriptive name for the phase. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CxupsOutputCurrentHighPrecision | 1.3.6.1.4.1.534.1.4.4.1.7 | Integer32 (0..2147483647) | RO | 0 | |||||||||||||||||
column · Integer32 (0..2147483647) · read-only · current The measured output current from the UPS meters in tenth of amps.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CxupsOutputPercentLoad | 1.3.6.1.4.1.534.1.4.4.1.8 | Integer32 (0..200) | RO | ||||||||||||||||||
column · Integer32 (0..200) · read-only · current The percentage of the UPS power capacity presently being used on this output line
| |||||||||||||||||||||
| CxupsOutputVA | 1.3.6.1.4.1.534.1.4.4.1.9 | Integer32 (0..2147483647) | RO | 0 | |||||||||||||||||
column · Integer32 (0..2147483647) · read-only · current The measured apparent output power in VA.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsOutputSource | 1.3.6.1.4.1.534.1.4.5 | INTEGER | RO | normal(3) | |||||||||||||||||
scalar · INTEGER · read-only · current The present source of output power. The enumeration
none(2) indicates that there is no source of output
power (and therefore no output power), for example,
the system has opened the output breaker.
'normal', 'bypass', and 'battery' indicate those common UPS statuses.
'booster' and 'reducer' indicate boost or buck operation, for
line-interactive UPSs only.
'parallelCapacity' and 'parallelRedundant' indicate a normal parallel
UPS system, in either Parallel for Capacity or Redundancy configuration.
'highEfficiencyMode' is normal but enhanced by High Efficiency mode.
'maintenanceBypass' indicates that the UPS is in Maintenance/Manual
Bypass mode.
'essMode' is normal but enhanced by Energy Saver System.
'other' covers any other, unusual conditions.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsOutputHourlyPowerUsage | 1.3.6.1.4.1.534.1.4.6 | Integer32 (0..2147483647) | RO | 362 | |||||||||||||||||
scalar · Integer32 (0..2147483647) · read-only · current Units are Watt-hours.This is the energy consumed during the last hour.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsOutputCumulativePowerUsage | 1.3.6.1.4.1.534.1.4.7 | Integer32 (0..2147483647) | RW | 8495327 | |||||||||||||||||
scalar · Integer32 (0..2147483647) · read-write · current Units are Watt-hours.This is the energy consumed since the last reset. This object is writable so that it can be reset to 0. When it is written to 0, the xupsOutputCumulativeWhTimer will be reset to 0 as well.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsOutputCumulativePowerUsageTimer | 1.3.6.1.4.1.534.1.4.8 | Counter32 | RO | 95355444 | |||||||||||||||||
scalar · Counter32 · read-only · current Time in seconds since the cumulative power usage was last reset.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NxupsOutputTotal | 1.3.6.1.4.1.534.1.4.9 | ||||||||||||||||||||
| SxupsOutputAverageVoltage | 1.3.6.1.4.1.534.1.4.9.1 | Integer32 (0..2147483647) | RO | 229 | |||||||||||||||||
scalar · Integer32 (0..2147483647) · read-only · current The measured output voltage from the UPS meters in volts. Related to the phase 1 if the UPS is single phase, either it is average of all the simple phase voltage.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsOutputTotalCurrent | 1.3.6.1.4.1.534.1.4.9.2 | Integer32 (0..2147483647) | RO | 0 | |||||||||||||||||
scalar · Integer32 (0..2147483647) · read-only · current The measured output current from the UPS meters in tenth of amps. Related to the phase 1 if the UPS is single phase, either it is average of all the simple phase current.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsOutputTotalWatts | 1.3.6.1.4.1.534.1.4.9.3 | Integer32 (0..2147483647) | RO | 0 | |||||||||||||||||
scalar · Integer32 (0..2147483647) · read-only · current The measured output active power in watts. Sum of all the simple phase watts.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsOutputTotalVA | 1.3.6.1.4.1.534.1.4.9.4 | Integer32 (0..2147483647) | RO | 0 | |||||||||||||||||
scalar · Integer32 (0..2147483647) · read-only · current The measured output apparent power in VA. Sum of all the simple phase VA.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsOutputAveragePowerFactor | 1.3.6.1.4.1.534.1.4.9.5 | Integer32 | RO | 0 | |||||||||||||||||
scalar · Integer32 · read-only · current Indicates the total power factor of the output in hundredths. 0.92 would be returned as 92. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsOutputStatus | 1.3.6.1.4.1.534.1.4.10 | INTEGER | RO | outputProtected(3) | |||||||||||||||||
scalar · INTEGER · read-only · current The present status of the AC output of the UPS. The enumeration outputNotPowered(1) indicates that the output is not powered. outputNotProtected(2) indicates that the output is powered but not protected, due to following reasons : On bypass, battery fault, or UPS internal failure that makes the ups will be inoperant in case of AC input failure. outputProtected(3) indicates that the output is powered and protected.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NxupsBypass | 1.3.6.1.4.1.534.1.5 | ||||||||||||||||||||
| SxupsBypassFrequency | 1.3.6.1.4.1.534.1.5.1 | Integer32 (0..2147483647) | RO | 500 | |||||||||||||||||
scalar · Integer32 (0..2147483647) · read-only · current The bypass frequency in tenths of Hz.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsBypassNumPhases | 1.3.6.1.4.1.534.1.5.2 | Integer32 (0..6) | RO | 1 | |||||||||||||||||
scalar · Integer32 (0..6) · read-only · current The number of lines in the UPS bypass table. Example values from LibreNMS test devices
| |||||||||||||||||||||
| TxupsBypassTable | 1.3.6.1.4.1.534.1.5.3 | NA | |||||||||||||||||||
table · not-accessible · current A list of bypass table entries. The number of entries is given by the value of xupsBypassNumPhases. | |||||||||||||||||||||
| RxupsBypassEntry | 1.3.6.1.4.1.534.1.5.3.1 | NA | |||||||||||||||||||
row · not-accessible · current Bypass Table Entry containing voltage for each phase.
| |||||||||||||||||||||
| CxupsBypassPhase | 1.3.6.1.4.1.534.1.5.3.1.1 | Integer32 (0..6) | RO | 1 | |||||||||||||||||
column · Integer32 (0..6) · read-only · current The Bypass Phase, index for the table. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CxupsBypassVoltage | 1.3.6.1.4.1.534.1.5.3.1.2 | Integer32 (0..2147483647) | RO | 227 | |||||||||||||||||
column · Integer32 (0..2147483647) · read-only · current The measured UPS bypass voltage in volts.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CxupsBypassId | 1.3.6.1.4.1.534.1.5.3.1.3 | INTEGER | RO | phase1toN(1) | |||||||||||||||||
column · INTEGER · read-only · current value indicates what measurement is being stored in this table row : phase1 to neutral, phase2 to neutral, phase3 to neutral, phase1 to phase2, phase2 to phase3, phase3 to phase1.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CxupsBypassName | 1.3.6.1.4.1.534.1.5.3.1.4 | OCTET STRING (SIZE (1..31)) | RO | L1/A | |||||||||||||||||
column · OCTET STRING (SIZE (1..31)) · read-only · current A descriptive name for the phase. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CxupsBypassCurrentHighPrecision | 1.3.6.1.4.1.534.1.5.3.1.5 | Integer32 (0..2147483647) | RO | 0 | |||||||||||||||||
column · Integer32 (0..2147483647) · read-only · current The measured bypass current from the UPS meters in tenth of amps.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CxupsBypassWatts | 1.3.6.1.4.1.534.1.5.3.1.6 | Integer32 (0..2147483647) | RO | ||||||||||||||||||
column · Integer32 (0..2147483647) · read-only · current The measured real bypass power in watts.
| |||||||||||||||||||||
| NxupsBypassTotal | 1.3.6.1.4.1.534.1.5.4 | ||||||||||||||||||||
| SxupsBypassAverageVoltage | 1.3.6.1.4.1.534.1.5.4.1 | Integer32 (0..2147483647) | RO | 238 | |||||||||||||||||
scalar · Integer32 (0..2147483647) · read-only · current The measured bypass voltage from the UPS meters in volts. Related to the phase 1 if the UPS is single phase, either it is average of all the simple phase voltage.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsBypassTotalCurrent | 1.3.6.1.4.1.534.1.5.4.2 | Integer32 (0..2147483647) | RO | 0 | |||||||||||||||||
scalar · Integer32 (0..2147483647) · read-only · current The measured bypass current from the UPS meters in tenth of amps. Related to the phase 1 if the UPS is single phase, either it is average of all the simple phase current.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsBypassTotalWatts | 1.3.6.1.4.1.534.1.5.4.3 | Integer32 (0..2147483647) | RO | ||||||||||||||||||
scalar · Integer32 (0..2147483647) · read-only · current The measured bypass active power in watts. Sum of all the simple phase watts.
| |||||||||||||||||||||
| SxupsBypassTotalVA | 1.3.6.1.4.1.534.1.5.4.4 | Integer32 (0..2147483647) | RO | ||||||||||||||||||
scalar · Integer32 (0..2147483647) · read-only · current The measured output apparent power in VA. Sum of all the simple phase VA.
| |||||||||||||||||||||
| SxupsBypassAveragePowerFactor | 1.3.6.1.4.1.534.1.5.4.5 | Integer32 | RO | ||||||||||||||||||
scalar · Integer32 · read-only · current Indicates the total power factor of the input in hundredths. 0.92 would be returned as 92. | |||||||||||||||||||||
| SxupsEnvAmbientTemp | 1.3.6.1.4.1.534.1.6.1 | Integer32 (-100..200) | RO | 0 | |||||||||||||||||
scalar · Integer32 (-100..200) · read-only · current The reading of the ambient temperature in the vicinity of the UPS or SNMP agent.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsEnvAmbientLowerLimit | 1.3.6.1.4.1.534.1.6.2 | Integer32 (-100..200) | RW | 0 | |||||||||||||||||
scalar · Integer32 (-100..200) · read-write · current The Lower Limit of the ambient temperature; if xupsEnvAmbientTemp falls below this value, the xupsAmbientTempBad alarm will occur.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsEnvAmbientUpperLimit | 1.3.6.1.4.1.534.1.6.3 | Integer32 (-100..200) | RW | 40 | |||||||||||||||||
scalar · Integer32 (-100..200) · read-write · current The Upper Limit of the ambient temperature; if xupsEnvAmbientTemp rises above this value, the xupsAmbientTempBad alarm will occur. This value should be greater than xupsEnvAmbientLowerLimit.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsEnvAmbientHumidity | 1.3.6.1.4.1.534.1.6.4 | Integer32 (0..100) | RO | ||||||||||||||||||
scalar · Integer32 (0..100) · read-only · current The reading of the ambient humidity in the vicinity of the UPS or SNMP agent.
| |||||||||||||||||||||
| NxupsAlarm | 1.3.6.1.4.1.534.1.7 | ||||||||||||||||||||
| SxupsAlarms | 1.3.6.1.4.1.534.1.7.1 | Gauge32 | RO | 1 | |||||||||||||||||
scalar · Gauge32 · read-only · current The current number of alarm conditions. Example values from LibreNMS test devices
| |||||||||||||||||||||
| TxupsAlarmTable | 1.3.6.1.4.1.534.1.7.2 | NA | |||||||||||||||||||
table · not-accessible · current A list of alarm table entries. The number of entries is given by the value of xupsAlarms. Note that this table is sparsely (non-consecutively) numbered and will be empty if there are no active alarms. | |||||||||||||||||||||
| RxupsAlarmEntry | 1.3.6.1.4.1.534.1.7.2.1 | NA | |||||||||||||||||||
row · not-accessible · current Alarm Table Entry containing descriptive information for one alarm entry.
| |||||||||||||||||||||
| CxupsAlarmID | 1.3.6.1.4.1.534.1.7.2.1.1 | Integer32 (1..2147483647) | RO | 12 | |||||||||||||||||
column · Integer32 (1..2147483647) · read-only · current A unique identifier for an alarm condition. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CxupsAlarmDescr | 1.3.6.1.4.1.534.1.7.2.1.2 | OBJECT IDENTIFIER | RO | 1.3.6.1.4.1.534.1.7.6 | |||||||||||||||||
column · OBJECT IDENTIFIER · read-only · current A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CxupsAlarmTime | 1.3.6.1.4.1.534.1.7.2.1.3 | TimeTicks | RO | 969824131 (112d 5h 57m 21s) | |||||||||||||||||
column · TimeTicks · read-only · current The value of the MIB-II variable sysUpTime when the alarm condition occurred. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NxupsOnBattery | 1.3.6.1.4.1.534.1.7.3 | ||||||||||||||||||||
| NxupsLowBattery | 1.3.6.1.4.1.534.1.7.4 | ||||||||||||||||||||
| NxupsUtilityPowerRestored | 1.3.6.1.4.1.534.1.7.5 | ||||||||||||||||||||
| NxupsReturnFromLowBattery | 1.3.6.1.4.1.534.1.7.6 | ||||||||||||||||||||
| NxupsOutputOverload | 1.3.6.1.4.1.534.1.7.7 | ||||||||||||||||||||
| NxupsInternalFailure | 1.3.6.1.4.1.534.1.7.8 | ||||||||||||||||||||
| NxupsBatteryDischarged | 1.3.6.1.4.1.534.1.7.9 | ||||||||||||||||||||
| NxupsInverterFailure | 1.3.6.1.4.1.534.1.7.10 | ||||||||||||||||||||
| NxupsOnBypass | 1.3.6.1.4.1.534.1.7.11 | ||||||||||||||||||||
| NxupsBypassNotAvailable | 1.3.6.1.4.1.534.1.7.12 | ||||||||||||||||||||
| NxupsOutputOff | 1.3.6.1.4.1.534.1.7.13 | ||||||||||||||||||||
| NxupsInputFailure | 1.3.6.1.4.1.534.1.7.14 | ||||||||||||||||||||
| NxupsBuildingAlarm | 1.3.6.1.4.1.534.1.7.15 | ||||||||||||||||||||
| NxupsShutdownImminent | 1.3.6.1.4.1.534.1.7.16 | ||||||||||||||||||||
| NxupsOnInverter | 1.3.6.1.4.1.534.1.7.17 | ||||||||||||||||||||
| SxupsAlarmNumEvents | 1.3.6.1.4.1.534.1.7.18 | Gauge32 | RO | 0 | |||||||||||||||||
scalar · Gauge32 · read-only · current The number of entries in the UPS event history queue. Example values from LibreNMS test devices
| |||||||||||||||||||||
| TxupsAlarmEventTable | 1.3.6.1.4.1.534.1.7.19 | NA | |||||||||||||||||||
table · not-accessible · current A table of the UPS internal event history queue. | |||||||||||||||||||||
| RxupsAlarmEventEntry | 1.3.6.1.4.1.534.1.7.19.1 | NA | |||||||||||||||||||
row · not-accessible · current One of the entries in the UPS event history queue.
| |||||||||||||||||||||
| CxupsAlarmEventID | 1.3.6.1.4.1.534.1.7.19.1.1 | Integer32 (1..400) | NA | ||||||||||||||||||
column · Integer32 (1..400) · not-accessible · current A unique number that reflects the order in which the event occurred. The oldest event in the queue will be number 1. Subsequent events will be numbered 2, 3, 4, etc. | |||||||||||||||||||||
| CxupsAlarmEventDateAndTime | 1.3.6.1.4.1.534.1.7.19.1.2 | DisplayString (SIZE (0..22)) | RO | deprecated | |||||||||||||||||
column · DisplayString (SIZE (0..22)) · read-only · deprecated The time and date that an event occurred as recorded in the UPS internal event queue. This string will reflect the time and date as set in the UPS itself and will not be referenced to sysUpTime. The format is MM/DD/YYYY:HH:MM:SS. Time is 24 hour standard. | |||||||||||||||||||||
| CxupsAlarmEventKind | 1.3.6.1.4.1.534.1.7.19.1.3 | INTEGER | RO | deprecated | |||||||||||||||||
column · INTEGER · read-only · deprecated Enumerated value that tells whether the event is an occurrence of an alarm condition or a clearing of an alarm condition.
| |||||||||||||||||||||
| CxupsAlarmEventDescr | 1.3.6.1.4.1.534.1.7.19.1.4 | Integer32 (0..2147483647) | RO | deprecated | |||||||||||||||||
column · Integer32 (0..2147483647) · read-only · deprecated A description of the event stored in the UPS event queue. This description will be a sixteen bit integer value representing one of the defined alarms in the Powerware Binary Computer Mode communication specification; for example, a value of 0 represents the 'Inverter AC Over Voltage' alarm (byte 1, bit 0 in the BCM Alarm Map). | |||||||||||||||||||||
| CxupsAlarmEventMsg | 1.3.6.1.4.1.534.1.7.19.1.5 | DisplayString (SIZE (0..80)) | RO | ||||||||||||||||||
column · DisplayString (SIZE (0..80)) · read-only · current A text string describing each entry in the Event Log. The format of this text message is free (not fixed) for the operator to read; good contents would be a time & date stamp, the event type, and a description of the event. | |||||||||||||||||||||
| NxupsBreakerOpen | 1.3.6.1.4.1.534.1.7.20 | ||||||||||||||||||||
| NxupsAlarmEntryAdded | 1.3.6.1.4.1.534.1.7.21 | ||||||||||||||||||||
| NxupsAlarmEntryRemoved | 1.3.6.1.4.1.534.1.7.22 | ||||||||||||||||||||
| NxupsAlarmBatteryBad | 1.3.6.1.4.1.534.1.7.23 | ||||||||||||||||||||
| NxupsOutputOffAsRequested | 1.3.6.1.4.1.534.1.7.24 | ||||||||||||||||||||
| NxupsDiagnosticTestFailed | 1.3.6.1.4.1.534.1.7.25 | ||||||||||||||||||||
| NxupsCommunicationsLost | 1.3.6.1.4.1.534.1.7.26 | ||||||||||||||||||||
| NxupsUpsShutdownPending | 1.3.6.1.4.1.534.1.7.27 | ||||||||||||||||||||
| NxupsAlarmTestInProgress | 1.3.6.1.4.1.534.1.7.28 | ||||||||||||||||||||
| NxupsAmbientTempBad | 1.3.6.1.4.1.534.1.7.29 | ||||||||||||||||||||
| NxupsLossOfRedundancy | 1.3.6.1.4.1.534.1.7.30 | ||||||||||||||||||||
| NxupsAlarmTempBad | 1.3.6.1.4.1.534.1.7.31 | ||||||||||||||||||||
| NxupsAlarmChargerFailed | 1.3.6.1.4.1.534.1.7.32 | ||||||||||||||||||||
| NxupsAlarmFanFailure | 1.3.6.1.4.1.534.1.7.33 | ||||||||||||||||||||
| NxupsAlarmFuseFailure | 1.3.6.1.4.1.534.1.7.34 | ||||||||||||||||||||
| NxupsPowerSwitchBad | 1.3.6.1.4.1.534.1.7.35 | ||||||||||||||||||||
| NxupsModuleFailure | 1.3.6.1.4.1.534.1.7.36 | ||||||||||||||||||||
| NxupsOnAlternatePowerSource | 1.3.6.1.4.1.534.1.7.37 | ||||||||||||||||||||
| NxupsAltPowerNotAvailable | 1.3.6.1.4.1.534.1.7.38 | ||||||||||||||||||||
| NxupsNoticeCondition | 1.3.6.1.4.1.534.1.7.39 | ||||||||||||||||||||
| NxupsRemoteTempBad | 1.3.6.1.4.1.534.1.7.40 | ||||||||||||||||||||
| NxupsRemoteHumidityBad | 1.3.6.1.4.1.534.1.7.41 | ||||||||||||||||||||
| NxupsAlarmOutputBad | 1.3.6.1.4.1.534.1.7.42 | ||||||||||||||||||||
| NxupsAlarmAwaitingPower | 1.3.6.1.4.1.534.1.7.43 | ||||||||||||||||||||
| NxupsOnMaintenanceBypass | 1.3.6.1.4.1.534.1.7.44 | ||||||||||||||||||||
| NxupsOutputNotProtected | 1.3.6.1.4.1.534.1.7.51 | ||||||||||||||||||||
| NxupsTest | 1.3.6.1.4.1.534.1.8 | ||||||||||||||||||||
| SxupsTestStart | 1.3.6.1.4.1.534.1.8.1 | INTEGER | RW | testBattery(1) | |||||||||||||||||
scalar · INTEGER · read-write · current Setting this object initiates the requested Test.
The test types which a UPS might support are 'testBattery',
'testSystem' (a UPS General Systems test, however defined by the UPS),
'testSecondarySource' (test if the Secondary power source is good on a
dual input UPS), and
'flashLightsTest' (start a test which flashes the UPS lights, and if
available, sounds the horn to help locate the UPS).
If a UPS does not support the requested test, the set operation may
succeed but the xupsTestBatteryStatus will end up as notSupported.
When read, this object indicates the last test requested via this object,
if any; 'noTestStarted' could be the initial value.
Currently only the 'flashLightsTest' can be canceled with 'cancelTest'.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsTestBatteryStatus | 1.3.6.1.4.1.534.1.8.2 | INTEGER | RO | passed(2) | |||||||||||||||||
scalar · INTEGER · read-only · current Reading this enumerated value gives an indication of the (last)
UPS Battery test status.
'inhibited' means that the battery test could not be run.
'scheduled' means that the battery test could not be run at the time
of request, but will be run at some later (UPS-determined) time.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsLastGeneralTest | 1.3.6.1.4.1.534.1.8.3 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current Indicates the last UPS test requested via xupsTestStart or by other non-SNMP means, other than for the testBattery (1) case. The results of the test indicated by this object are reported in xupsLastGeneralTestResult.
| |||||||||||||||||||||
| SxupsLastGeneralTestResult | 1.3.6.1.4.1.534.1.8.4 | INTEGER | RO | ||||||||||||||||||
scalar · INTEGER · read-only · current Reading this enumerated value gives the result of the test indicated in xupsLastGeneralTest.
| |||||||||||||||||||||
| SxupsTestTrap | 1.3.6.1.4.1.534.1.8.5 | INTEGER | RW | startTestTrap(1) | |||||||||||||||||
scalar · INTEGER · read-write · current Setting startTestTrap to 1 will initiate a test trap to be sent out from the agent. All other set values are invalid.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NxupsControl | 1.3.6.1.4.1.534.1.9 | ||||||||||||||||||||
| SxupsControlOutputOffDelay | 1.3.6.1.4.1.534.1.9.1 | Integer32 (0..2147483647) | RW | 0 | |||||||||||||||||
scalar · Integer32 (0..2147483647) · read-write · current Setting this value to other than zero will cause the UPS output to turn off after the number of seconds. Setting it to 0 will cause an attempt to abort a pending shutdown.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsControlOutputOnDelay | 1.3.6.1.4.1.534.1.9.2 | Integer32 (0..2147483647) | RW | 0 | |||||||||||||||||
scalar · Integer32 (0..2147483647) · read-write · current Setting this value to other than zero will cause the UPS output to turn on after the number of seconds. Setting it to 0 will cause an attempt to abort a pending startup.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsControlOutputOffTrapDelay | 1.3.6.1.4.1.534.1.9.3 | Integer32 (0..2147483647) | RW | 0 | |||||||||||||||||
scalar · Integer32 (0..2147483647) · read-write · current When xupsControlOutputOffDelay reaches this value, a trap will be sent.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsControlOutputOnTrapDelay | 1.3.6.1.4.1.534.1.9.4 | Integer32 (0..2147483647) | RW | deprecated | 0 | ||||||||||||||||
scalar · Integer32 (0..2147483647) · read-write · deprecated When xupsControlOutputOnDelay reaches this value, a xupsOutputOff trap will be sent.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsControlToBypassDelay | 1.3.6.1.4.1.534.1.9.5 | Integer32 (0..2147483647) | RW | 0 | |||||||||||||||||
scalar · Integer32 (0..2147483647) · read-write · current Setting this value to other than zero will cause the UPS output to go to Bypass after the number of seconds. If the Bypass is unavailable, this may cause the UPS to not supply power to the load. Setting it to 0 will cause an attempt to abort a pending shutdown.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsLoadShedSecsWithRestart | 1.3.6.1.4.1.534.1.9.6 | Integer32 (0..2147483647) | RW | 0 | |||||||||||||||||
scalar · Integer32 (0..2147483647) · read-write · current Setting this value will cause the UPS output to turn off after the set number of seconds, then restart (after a UPS-defined 'down time') when the utility is again available. Unlike xupsControlOutputOffDelay, which might or might not, this object always maps to the XCP 0x8A Load Dump & Restart command, so the desired shutdown and restart behavior is guaranteed to happen. Once set, this command cannot be aborted. This is the preferred Control object to use when performing an On Battery OS Shutdown.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsSwitchable | 1.3.6.1.4.1.534.1.9.7 | INTEGER | RO | 0 | |||||||||||||||||
scalar · INTEGER · read-only · current Parameter which indicates whether UPS commands received via any communication path (aside from manual controls) are able (switchable) or not able (notSwitchable) to control the UPS.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NxupsConfig | 1.3.6.1.4.1.534.1.10 | ||||||||||||||||||||
| SxupsConfigOutputVoltage | 1.3.6.1.4.1.534.1.10.1 | Integer32 (0..2147483647) | RO | 230 | |||||||||||||||||
scalar · Integer32 (0..2147483647) · read-only · current The nominal UPS Output voltage per phase in volts.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsConfigInputVoltage | 1.3.6.1.4.1.534.1.10.2 | Integer32 (0..2147483647) | RO | 230 | |||||||||||||||||
scalar · Integer32 (0..2147483647) · read-only · current The nominal UPS Input voltage per phase in volts.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsConfigOutputWatts | 1.3.6.1.4.1.534.1.10.3 | Integer32 (0..2147483647) | RO | 1000 | |||||||||||||||||
scalar · Integer32 (0..2147483647) · read-only · current The nominal UPS available real power output in watts.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsConfigOutputFreq | 1.3.6.1.4.1.534.1.10.4 | Integer32 (0..2147483647) | RO | 500 | |||||||||||||||||
scalar · Integer32 (0..2147483647) · read-only · current The nominal output frequency in tenths of Hz.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsConfigDateAndTime | 1.3.6.1.4.1.534.1.10.5 | DisplayString (SIZE (0..22)) | RW | 07/01/2021 07:53:10 | |||||||||||||||||
scalar · DisplayString (SIZE (0..22)) · read-write · current Date and time information for the UPS. Setting this variable will initiate a set UPS date and time to this value. Reading this variable will return the UPS time and date. This value is not referenced to sysUpTime. It is simply the clock value from the UPS real time clock. Format is as follows: MM/DD/YYYY:HH:MM:SS. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsConfigLowOutputVoltageLimit | 1.3.6.1.4.1.534.1.10.6 | Integer32 (0..2147483647) | RO | 100 | |||||||||||||||||
scalar · Integer32 (0..2147483647) · read-only · current The Lower limit for acceptable Output Voltage, per the UPS specifications.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsConfigHighOutputVoltageLimit | 1.3.6.1.4.1.534.1.10.7 | Integer32 (0..2147483647) | RO | 276 | |||||||||||||||||
scalar · Integer32 (0..2147483647) · read-only · current The Upper limit for acceptable Output Voltage, per the UPS specifications.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsConfigInstallDate | 1.3.6.1.4.1.534.1.10.8 | DisplayString (SIZE (0..16)) | RW | | |||||||||||||||||
scalar · DisplayString (SIZE (0..16)) · read-write · current The date when this UPS was installed. Free text format, so the preferred local date format may be used (MM/DD/YYYY, DD-Mon-YYYY, etc). Example values from LibreNMS test devices
| |||||||||||||||||||||
| NxupsTrapControl | 1.3.6.1.4.1.534.1.11 | ||||||||||||||||||||
| SxupsMaxTrapLevel | 1.3.6.1.4.1.534.1.11.1 | INTEGER | RW | allTraps(5) | |||||||||||||||||
scalar · INTEGER · read-write · current The level of severity of traps which will be sent to the
requesting host; individual trap receivers will have
individual values for this variable. Values are:
(1) none: no traps will be sent to this host;
(2) critical: only traps for Critical alarm conditions will
be sent to this host;
(3) major: Critical and Major traps will be sent;
(4) minor: All levels of alarming traps will be sent: Critical,
Major, and Minor
(This level was added in PowerMIB v3.11)
(5) allTraps: all Traps will be sent to this host
(Critical, Major, Minor, Informational).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsSendTrapType | 1.3.6.1.4.1.534.1.11.2 | INTEGER | RW | xups(2) | |||||||||||||||||
scalar · INTEGER · read-write · current The type of traps which will be sent to the requesting host; individual trap receivers will have individual values for this variable. The additional variables in types (3) and (4) are useful for determining which UPS is the source on multi-port network adapters, and for getting additional descriptive information. Types (1) through (4) are all SNMP version 1 trap PDUs. Values are: (1) stnd: Traps as defined in the Standard UPS MIB (RFC1628) and Generic (MIB II) traps as defined in RFC 1215. (2) xups: xupsTrapDefined Traps as defined in the PowerMIB and Generic (MIB II) traps as defined in RFC 1215. (3 Deprecated) stndPlus: same as stnd plus variables from the interface group and, where appropriate, xupsTrapMessage. (4 Deprecated) xupsPlus: xupsTrapPortN Traps (same as xups plus variables from the interface group) and, for authFail, xupsTrapMessage. (5 pxg: Traps as defined in the Power Xpert Gateway MIB (PXG-MIB).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsTrapMessage | 1.3.6.1.4.1.534.1.11.3 | DisplayString (SIZE (0..79)) | RO | | |||||||||||||||||
scalar · DisplayString (SIZE (0..79)) · read-only · current A descriptive text message which may be sent with traps to further explain the reason for the trap. This object is not-accessible to MIB browsers, but had to be changed to read-only to satisfy SMIv2 syntax checkers since it is included in traps. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NxupsTrapSource | 1.3.6.1.4.1.534.1.11.4 | ||||||||||||||||||||
| NxupsTrapDefined | 1.3.6.1.4.1.534.1.11.4.1 | ||||||||||||||||||||
| NxupsTrapOidDefined | 1.3.6.1.4.1.534.1.11.4.1.0 | ||||||||||||||||||||
| !xupstdControlOff | 1.3.6.1.4.1.534.1.11.4.1.0.1 | ||||||||||||||||||||
notification · current The UPS output power will turn off in a number of seconds equal to upsControlOutputOffTrapDelay.
| |||||||||||||||||||||
| !xupstdControlOn | 1.3.6.1.4.1.534.1.11.4.1.0.2 | ||||||||||||||||||||
notification · current The UPS output power will turn on in a number of seconds equal to upsControlOutputOnTrapDelay.
| |||||||||||||||||||||
| !xupstdOnBattery | 1.3.6.1.4.1.534.1.11.4.1.0.3 | ||||||||||||||||||||
notification · current The UPS has no AC input power and is running on battery.
| |||||||||||||||||||||
| !xupstdLowBattery | 1.3.6.1.4.1.534.1.11.4.1.0.4 | ||||||||||||||||||||
notification · current The UPS batteries are low. Tied to low battery alarm condition.
| |||||||||||||||||||||
| !xupstdUtilityPowerRestored | 1.3.6.1.4.1.534.1.11.4.1.0.5 | ||||||||||||||||||||
notification · current Input power has been restored after running on battery.
| |||||||||||||||||||||
| !xupstdReturnFromLowBattery | 1.3.6.1.4.1.534.1.11.4.1.0.6 | ||||||||||||||||||||
notification · current The battery has recovered from a low battery condition.
| |||||||||||||||||||||
| !xupstdOutputOverload | 1.3.6.1.4.1.534.1.11.4.1.0.7 | ||||||||||||||||||||
notification · current The ups has sensed an overload of greater than 106 percent. Tied to the 106% overload alarm.
| |||||||||||||||||||||
| !xupstdInternalFailure | 1.3.6.1.4.1.534.1.11.4.1.0.8 | ||||||||||||||||||||
notification · current Some component of the ups - rectifier, inverter, control panel has failed. Tied to alarms indi- cating failure.
| |||||||||||||||||||||
| !xupstdBatteryDischarged | 1.3.6.1.4.1.534.1.11.4.1.0.9 | ||||||||||||||||||||
notification · current The Battery Totally Discharged Alarm has occurred.
| |||||||||||||||||||||
| !xupstdInverterFailure | 1.3.6.1.4.1.534.1.11.4.1.0.10 | ||||||||||||||||||||
notification · current The ups inverter is unavailable or malfunctioning due to an internal failure.
| |||||||||||||||||||||
| !xupstdOnBypass | 1.3.6.1.4.1.534.1.11.4.1.0.11 | ||||||||||||||||||||
notification · current The ups has gone on bypass for some reason.
| |||||||||||||||||||||
| !xupstdBypassNotAvailable | 1.3.6.1.4.1.534.1.11.4.1.0.12 | ||||||||||||||||||||
notification · current The ups bypass is unavailable
| |||||||||||||||||||||
| !xupstdOutputOff | 1.3.6.1.4.1.534.1.11.4.1.0.13 | ||||||||||||||||||||
notification · current The ups output is switched off.
| |||||||||||||||||||||
| !xupstdInputFailure | 1.3.6.1.4.1.534.1.11.4.1.0.14 | ||||||||||||||||||||
notification · current The ups input power is incorrect in voltage, frequency, or phase rotation.
| |||||||||||||||||||||
| !xupstdBuildingAlarm | 1.3.6.1.4.1.534.1.11.4.1.0.15 | ||||||||||||||||||||
notification · current One of the defined building alarms has occurred.
| |||||||||||||||||||||
| !xupstdShutdownImminent | 1.3.6.1.4.1.534.1.11.4.1.0.16 | ||||||||||||||||||||
notification · current The ups shutdown imminent alarm has occurred.
| |||||||||||||||||||||
| !xupstdOnInverter | 1.3.6.1.4.1.534.1.11.4.1.0.17 | ||||||||||||||||||||
notification · current The ups is returned to utility power running the inverter after either a transfer to bypass or a run on battery.
| |||||||||||||||||||||
| !xupstdBreakerOpen | 1.3.6.1.4.1.534.1.11.4.1.0.20 | ||||||||||||||||||||
notification · current One of the UPS breakers or contactors has been opened.
| |||||||||||||||||||||
| !xupstdAlarmEntryAdded | 1.3.6.1.4.1.534.1.11.4.1.0.21 | ||||||||||||||||||||
notification · current An alarm not defined in the xups Well Known Alarms (eg, an alarm defined in RFC1628) has been added to the Alarm Table.
| |||||||||||||||||||||
| !xupstdAlarmEntryRemoved | 1.3.6.1.4.1.534.1.11.4.1.0.22 | ||||||||||||||||||||
notification · current An alarm not defined in the xups Well Known Alarms has been removed from the Alarm Table.
| |||||||||||||||||||||
| !xupstdAlarmBatteryBad | 1.3.6.1.4.1.534.1.11.4.1.0.23 | ||||||||||||||||||||
notification · current One or more batteries have been determined to require replacement.
| |||||||||||||||||||||
| !xupstdOutputOffAsRequested | 1.3.6.1.4.1.534.1.11.4.1.0.24 | ||||||||||||||||||||
notification · current The UPS has shutdown as requested, i.e., the output is off.
| |||||||||||||||||||||
| !xupstdDiagnosticTestFailed | 1.3.6.1.4.1.534.1.11.4.1.0.25 | ||||||||||||||||||||
notification · current The result of the last diagnostic test indicates a failure.
| |||||||||||||||||||||
| !xupstdCommunicationsLost | 1.3.6.1.4.1.534.1.11.4.1.0.26 | ||||||||||||||||||||
notification · current A problem has been encountered in the communications between the agent and the UPS.
| |||||||||||||||||||||
| !xupstdUpsShutdownPending | 1.3.6.1.4.1.534.1.11.4.1.0.27 | ||||||||||||||||||||
notification · current An xupsControlOutputOffDelay countdown is underway.
| |||||||||||||||||||||
| !xupstdAlarmTestInProgress | 1.3.6.1.4.1.534.1.11.4.1.0.28 | ||||||||||||||||||||
notification · current A test is in progress, as initiated and indicated by the xupsTest Group. When the test is complete, one of the following traps will be sent: - xupstdDiagnosticTestFailed if the test fails, - xupstdDiagnosticTestPassed on success, or - xupstdAlarmEntryRemoved in other cases (e.g., Test Canceled).
| |||||||||||||||||||||
| !xupstdAmbientTempBad | 1.3.6.1.4.1.534.1.11.4.1.0.29 | ||||||||||||||||||||
notification · current The ambient temperature, xupsEnvAmbientTemp, has fallen below the set lower limit, xupsEnvAmbientLowerLimit, or has risen above the set upper limit, xupsEnvAmbientUpperLimit. | |||||||||||||||||||||
| !xupstdContactActiveNotice | 1.3.6.1.4.1.534.1.11.4.1.0.30 | ||||||||||||||||||||
notification · current The Contact indicated by xupsContactIndex is in its Active state.
The following are the situations that generate this trap:
For xupsContactType: and xupsContactState:
normallyOpen(1) and closedWithNotice(4)
normallyClosed(2) and openWithNotice(3)
anyChange(3) and openWithNotice(3) or closedWithNotice(4) | |||||||||||||||||||||
| !xupstdContactInactiveNotice | 1.3.6.1.4.1.534.1.11.4.1.0.31 | ||||||||||||||||||||
notification · current The Contact indicated by xupsContactIndex has changed to its Inactive state. | |||||||||||||||||||||
| !xupstdLossOfRedundancy | 1.3.6.1.4.1.534.1.11.4.1.0.32 | ||||||||||||||||||||
notification · current A parallel UPS system is no longer operating in N+1 redundant mode; this may be due to module failure or removal, or due to overloading.
| |||||||||||||||||||||
| !xupstdAlarmTempBad | 1.3.6.1.4.1.534.1.11.4.1.0.33 | ||||||||||||||||||||
notification · current An internal temperature is out of tolerance.
| |||||||||||||||||||||
| !xupstdAlarmChargerFailed | 1.3.6.1.4.1.534.1.11.4.1.0.34 | ||||||||||||||||||||
notification · current An uncorrected problem has been detected within the UPS charger subsystem.
| |||||||||||||||||||||
| !xupstdAlarmFanFailure | 1.3.6.1.4.1.534.1.11.4.1.0.35 | ||||||||||||||||||||
notification · current The failure of one or more fans in the UPS has been detected.
| |||||||||||||||||||||
| !xupstdAlarmFuseFailure | 1.3.6.1.4.1.534.1.11.4.1.0.36 | ||||||||||||||||||||
notification · current The failure of one or more fuses has been detected.
| |||||||||||||||||||||
| !xupstdPowerSwitchBad | 1.3.6.1.4.1.534.1.11.4.1.0.37 | ||||||||||||||||||||
notification · current A Relay, Contactor, or Breaker has failed.
| |||||||||||||||||||||
| !xupstdModuleFailure | 1.3.6.1.4.1.534.1.11.4.1.0.38 | ||||||||||||||||||||
notification · current One module in a parallel or composite system has failed.
| |||||||||||||||||||||
| !xupstdOnAlternatePowerSource | 1.3.6.1.4.1.534.1.11.4.1.0.39 | ||||||||||||||||||||
notification · current The system is being powered by its Alternate Power Source, such as a Secondary utility feed (on a dual AC input UPS), generator, flywheel, or fuel cell. | |||||||||||||||||||||
| !xupstdAltPowerNotAvailable | 1.3.6.1.4.1.534.1.11.4.1.0.40 | ||||||||||||||||||||
notification · current On systems with a separate alternate power source (eg, dual AC inputs), that alternate power source is currently not available. This could be a problem if the primary power source (eg, utility) fails for a period of time longer than that for which the internal batteries can supply power.
| |||||||||||||||||||||
| !xupstdNoticeCondition | 1.3.6.1.4.1.534.1.11.4.1.0.41 | ||||||||||||||||||||
notification · current Some Notice condition exists which is not covered by the other traps. This is like an xupstdInternalFailure, but at a lower severity level.
| |||||||||||||||||||||
| !xupstdRemoteTempBad | 1.3.6.1.4.1.534.1.11.4.1.0.42 | ||||||||||||||||||||
notification · current The remote temperature, xupsEnvRemoteTemp, has fallen below the set lower limit, xupsEnvRemoteTempLowerLimit, or has risen above the set upper limit, xupsEnvRemoteTempUpperLimit. | |||||||||||||||||||||
| !xupstdRemoteHumidityBad | 1.3.6.1.4.1.534.1.11.4.1.0.43 | ||||||||||||||||||||
notification · current The remote temperature, xupsEnvRemoteHumidity, has fallen below the set lower limit, xupsEnvRemoteHumidityLowerLimit, or has risen above the set upper limit, xupsEnvRemoteHumidityUpperLimit. | |||||||||||||||||||||
| !xupstdHeartbeat | 1.3.6.1.4.1.534.1.11.4.1.0.44 | ||||||||||||||||||||
notification · current A periodic status trap message. It is sent at an interval set by object xupsHeartbeatMinsInterval. The included variables provide a brief statement of the UPS status.
| |||||||||||||||||||||
| !xupstdDiagnosticTestPassed | 1.3.6.1.4.1.534.1.11.4.1.0.45 | ||||||||||||||||||||
notification · current A diagnostic test just completed, and its result is Passed. The included variables provide additional information on the test. | |||||||||||||||||||||
| !xupstdOutputBad | 1.3.6.1.4.1.534.1.11.4.1.0.46 | ||||||||||||||||||||
notification · current The output condition (other than OutputOverload) is out of tolerance.
| |||||||||||||||||||||
| !xupstdAwaitingPower | 1.3.6.1.4.1.534.1.11.4.1.0.47 | ||||||||||||||||||||
notification · current The UPS output is off and the UPS is awaiting the return of input power.
| |||||||||||||||||||||
| !xupstdOnMaintenanceBypass | 1.3.6.1.4.1.534.1.11.4.1.0.48 | ||||||||||||||||||||
notification · current The UPS has been placed on Maintenance / Manual Bypass by an operator.
| |||||||||||||||||||||
| !xupstdCommEstablished | 1.3.6.1.4.1.534.1.11.4.1.0.49 | ||||||||||||||||||||
notification · current This trap is sent when the SNMP agent first establishes a communication link with the UPS. The included variables provide identification and UPS status information.
| |||||||||||||||||||||
| !xupstdAgentDown | 1.3.6.1.4.1.534.1.11.4.1.0.50 | ||||||||||||||||||||
notification · current This trap is sent when the SNMP agent is exiting or closing down gracefully. This may be triggered by a signal from the OS to stop this process. In many implementations, it will be followed quickly by a restart of this vital process. | |||||||||||||||||||||
| !xupstdOutputNotProtected | 1.3.6.1.4.1.534.1.11.4.1.0.51 | ||||||||||||||||||||
notification · current The ups output is not protectet for any reason in the UPS.
| |||||||||||||||||||||
| !xupstdTestTrap | 1.3.6.1.4.1.534.1.11.4.1.0.100 | ||||||||||||||||||||
notification · current This trap is sent to the trap receivers to check proper reception of traps.
| |||||||||||||||||||||
| SxupsHeartbeatMinsInterval | 1.3.6.1.4.1.534.1.11.5 | Integer32 (0..2147483647) | RW | ||||||||||||||||||
scalar · Integer32 (0..2147483647) · read-write · current How often to send the xupstdHeartbeat trap, in units of minutes. A setting of 0 disables the Heartbeat function.
| |||||||||||||||||||||
| NxupsRecep | 1.3.6.1.4.1.534.1.12 | ||||||||||||||||||||
| SxupsNumReceptacles | 1.3.6.1.4.1.534.1.12.1 | Integer32 (0..64) | RO | 2 | |||||||||||||||||
scalar · Integer32 (0..64) · read-only · current The number of independently controllable Receptacles, as described in the xupsRecepTable. Example values from LibreNMS test devices
| |||||||||||||||||||||
| TxupsRecepTable | 1.3.6.1.4.1.534.1.12.2 | NA | |||||||||||||||||||
table · not-accessible · current A list of receptacle table entries. The number of entries is given by the value of xupsNumReceptacles. | |||||||||||||||||||||
| RxupsRecepEntry | 1.3.6.1.4.1.534.1.12.2.1 | NA | |||||||||||||||||||
row · not-accessible · current A receptacle table entry containing the status and control values for one receptacle.
| |||||||||||||||||||||
| CxupsRecepIndex | 1.3.6.1.4.1.534.1.12.2.1.1 | Integer32 (1..64) | RO | 1 | |||||||||||||||||
column · Integer32 (1..64) · read-only · current The number of the Receptacle. Serves as index for Receptacle table. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CxupsRecepStatus | 1.3.6.1.4.1.534.1.12.2.1.2 | INTEGER | RO | on(1) | |||||||||||||||||
column · INTEGER · read-only · current The Recep Status 1=On/Close, 2=Off/Open, 3=On w/Pending Off, 4=Off w/Pending ON, 5=Unknown, 6=Reserved for future, 7=Failed in Closed position, 8=Failed in Open position.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CxupsRecepOffDelaySecs | 1.3.6.1.4.1.534.1.12.2.1.3 | Integer32 (-1..2147483647) | RW | -1 | |||||||||||||||||
column · Integer32 (-1..2147483647) · read-write · current The Delay until the Receptacle is turned Off. Setting this value to other than -1 will cause the UPS output to turn off after the number of seconds (0 is immediately). Setting it to -1 will cause an attempt to abort a pending shutdown. When this object is set while the UPS is On Battery, it is not necessary to set xupsRecepOnDelaySecs, since the outlet will turn back on automatically when power is available again.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CxupsRecepOnDelaySecs | 1.3.6.1.4.1.534.1.12.2.1.4 | Integer32 (-1..2147483647) | RW | -1 | |||||||||||||||||
column · Integer32 (-1..2147483647) · read-write · current The Delay until the Receptacle is turned On. Setting this value to other than -1 will cause the UPS output to turn on after the number of seconds (0 is immediately). Setting it to -1 will cause an attempt to abort a pending restart.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CxupsRecepAutoOffDelay | 1.3.6.1.4.1.534.1.12.2.1.5 | Integer32 (-1..32767) | RW | 999999 | |||||||||||||||||
column · Integer32 (-1..32767) · read-write · current The delay after going On Battery until the Receptacle is automatically turned Off. A value of -1 means that this Output should never be turned Off automatically, but must be turned Off only by command. Values from 0 to 30 are valid, but probably innappropriate. The AutoOffDelay can be used to prioritize loads in the event of a prolonged power outage; less critical loads will turn off earlier to extend battery time for the more critical loads. If the utility power is restored before the AutoOff delay counts down to 0 on an outlet, that outlet will not turn Off.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CxupsRecepAutoOnDelay | 1.3.6.1.4.1.534.1.12.2.1.6 | Integer32 (-1..32767) | RW | 3 | |||||||||||||||||
column · Integer32 (-1..32767) · read-write · current Seconds delay after the Outlet is signaled to turn On before the Output is Automatically turned ON. A value of -1 means that this Output should never be turned On automatically, but only when specifically commanded to do so. A value of 0 means that the Receptacle should come On immediately at power-up or for an On command.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CxupsRecepShedSecsWithRestart | 1.3.6.1.4.1.534.1.12.2.1.7 | Integer32 (0..2147483647) | RW | 0 | |||||||||||||||||
column · Integer32 (0..2147483647) · read-write · current Setting this value will cause the UPS output to turn off after the set number of seconds, then restart (after a UPS-defined 'down time') when the utility is again available. Unlike xupsRecepOffDelaySecs, which might or might not, this object always maps to the XCP 0x8A Load Dump & Restart command, so the desired shutdown and restart behavior is guaranteed to happen. Once set, this command cannot be aborted.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CxupsRecepHourlyPowerUsage | 1.3.6.1.4.1.534.1.12.2.1.8 | Integer32 (0..2147483647) | RO | 0 | |||||||||||||||||
column · Integer32 (0..2147483647) · read-only · current Units are Watt-hours.This is the energy consumed during the last hour.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CxupsRecepCumulativePowerUsage | 1.3.6.1.4.1.534.1.12.2.1.9 | Integer32 (0..2147483647) | RW | 10 | |||||||||||||||||
column · Integer32 (0..2147483647) · read-write · current Units are Watt-hours.This is the energy consumed since the last reset. This object is writable so that it can be reset to 0. When it is written to 0, the xupsRecepCumulativePowerUsageTimer will be reset to 0 as well.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CxupsRecepCumulativePowerUsageTimer | 1.3.6.1.4.1.534.1.12.2.1.10 | Counter32 | RO | 95355443 | |||||||||||||||||
column · Counter32 · read-only · current Time in seconds since the cumulative power usage was last reset.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NxupsTopology | 1.3.6.1.4.1.534.1.13 | ||||||||||||||||||||
| SxupsTopologyType | 1.3.6.1.4.1.534.1.13.1 | Integer32 (0..32767) | RO | 64 | |||||||||||||||||
scalar · Integer32 (0..32767) · read-only · current Value which denotes the type of UPS by its power topology. Values are the same as those described in the XCP Topology block's Overall Topology field. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsTopoMachineCode | 1.3.6.1.4.1.534.1.13.2 | Integer32 (0..32767) | RO | 9870 | |||||||||||||||||
scalar · Integer32 (0..32767) · read-only · current ID Value which denotes the Powerware model of the UPS for software. Values are the same as those described in the XCP Configuration block's Machine Code field. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsTopoUnitNumber | 1.3.6.1.4.1.534.1.13.3 | Integer32 (0..64) | RO | 0 | |||||||||||||||||
scalar · Integer32 (0..64) · read-only · current Identifies which unit and what type of data is being reported. A value of 0 means that this MIB information comes from the top-level system view (eg, manifold module or system bypass cabinet reporting total system output). Standalone units also use a value of 0, since they are the 'full system' view. A value of 1 or higher indicates the number of the module in the system which is reporting only its own data in the PowerMIB objects. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsTopoPowerStrategy | 1.3.6.1.4.1.534.1.13.4 | INTEGER | RW | standard(2) | |||||||||||||||||
scalar · INTEGER · read-write · current Value which denotes which Power Strategy is currently set for the UPS.
The values are:
highAlert(1) - The UPS shall optimize its operating state to maximize its
power-protection levels. This mode will be held for at most 24 hours.
standard(2) - Balanced, normal power protection strategy. UPS will not enter
HE operating mode from this setting.
enableHighEfficiency(3) - The UPS is enabled to enter HE operating mode to
optimize its operating state to maximize its efficiency, when
conditions change to permit it (as determined by the UPS).
forceHighEfficiency(4) - If this value is permitted to be Set for this UPS,
and if conditions permit, requires the UPS to enter High Efficiency
mode now, without delay (for as long as utility conditions permit).
After successfully set to forceHighEfficiency(4),
xupsTopoPowerStrategy changes to value enableHighEfficiency(3).
xupsOutputSource will indicate if the UPS status is actually operating in
High Efficiency mode.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NxupsAgent | 1.3.6.1.4.1.534.1.14 | ||||||||||||||||||||
| SxupsAgentManufacturer | 1.3.6.1.4.1.534.1.14.1 | DisplayString (SIZE (0..31)) | RO | Eaton | |||||||||||||||||
scalar · DisplayString (SIZE (0..31)) · read-only · current The card agent Manufacturer Name (e.g. Eaton Corporation). Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsAgentModel | 1.3.6.1.4.1.534.1.14.2 | DisplayString (SIZE (0..63)) | RO | Eaton Gigabit Network Card | |||||||||||||||||
scalar · DisplayString (SIZE (0..63)) · read-only · current The card agent model Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsAgentSoftwareVersion | 1.3.6.1.4.1.534.1.14.3 | DisplayString (SIZE (0..63)) | RO | 2.0.5 | |||||||||||||||||
scalar · DisplayString (SIZE (0..63)) · read-only · current The agent firmware version. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsAgentPartNumber | 1.3.6.1.4.1.534.1.14.4 | OCTET STRING (SIZE (1..31)) | RO | 744-A3983-02 | |||||||||||||||||
scalar · OCTET STRING (SIZE (1..31)) · read-only · current The card agent catalog part number. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxupsAgentSerialNumber | 1.3.6.1.4.1.534.1.14.5 | OCTET STRING (SIZE (1..31)) | RO | G312L20527 | |||||||||||||||||
scalar · OCTET STRING (SIZE (1..31)) · read-only · current The card agent catalog serial number. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NxupsConformance | 1.3.6.1.4.1.534.1.100 | ||||||||||||||||||||
| GxupsIdentFullGroup | 1.3.6.1.4.1.534.1.100.2 | ||||||||||||||||||||
group · current The Full set of xupsIdent subgroup objects. | |||||||||||||||||||||
| GxupsBatteryFullGroup | 1.3.6.1.4.1.534.1.100.3 | ||||||||||||||||||||
group · current The Full set of xupsBattery subgroup objects. | |||||||||||||||||||||
| GxupsInputFullGroup | 1.3.6.1.4.1.534.1.100.4 | ||||||||||||||||||||
group · current The Full set of xupsInput subgroup objects. | |||||||||||||||||||||
| GxupsInputTableFullGroup | 1.3.6.1.4.1.534.1.100.5 | ||||||||||||||||||||
group · current The Full set of xupsInputTable subgroup objects. | |||||||||||||||||||||
| GxupsOutputFullGroup | 1.3.6.1.4.1.534.1.100.6 | ||||||||||||||||||||
group · current The Full set of xupsOutput subgroup objects. | |||||||||||||||||||||
| GxupsOutputTableFullGroup | 1.3.6.1.4.1.534.1.100.7 | ||||||||||||||||||||
group · current The Full set of xupsOutputTable subgroup objects. | |||||||||||||||||||||
| GxupsBypassFullGroup | 1.3.6.1.4.1.534.1.100.8 | ||||||||||||||||||||
group · current The Full set of xupsBypass subgroup objects. | |||||||||||||||||||||
| GxupsEnvironmentFullGroup | 1.3.6.1.4.1.534.1.100.9 | ||||||||||||||||||||
group · current The Full set of xupsEnvironment subgroup objects. | |||||||||||||||||||||
| GxupsAlarmFullGroup | 1.3.6.1.4.1.534.1.100.10 | ||||||||||||||||||||
group · current The Full set of xupsAlarm subgroup objects.
| |||||||||||||||||||||
| GxupsAlarmEventsFullGroup | 1.3.6.1.4.1.534.1.100.11 | ||||||||||||||||||||
group · current The Full set of Alarm/Event history subgroup objects.
| |||||||||||||||||||||
| GxupsTestFullGroup | 1.3.6.1.4.1.534.1.100.12 | ||||||||||||||||||||
group · current The Full set of xupsTest subgroup objects. | |||||||||||||||||||||
| GxupsControlFullGroup | 1.3.6.1.4.1.534.1.100.13 | ||||||||||||||||||||
group · current The Full set of xupsControl subgroup objects. | |||||||||||||||||||||
| GxupsConfigFullGroup | 1.3.6.1.4.1.534.1.100.14 | ||||||||||||||||||||
group · current The Full set of xupsConfig subgroup objects. | |||||||||||||||||||||
| GxupsTrapControlFullGroup | 1.3.6.1.4.1.534.1.100.15 | ||||||||||||||||||||
group · current The Full set of xupsTrapControl subgroup objects. | |||||||||||||||||||||
| GxupsRecepFullGroup | 1.3.6.1.4.1.534.1.100.16 | ||||||||||||||||||||
group · current The Full set of xupsRecep subgroup objects. | |||||||||||||||||||||
| GxupsTopologyFullGroup | 1.3.6.1.4.1.534.1.100.17 | ||||||||||||||||||||
group · current The Full set of xupsTopology subgroup objects. | |||||||||||||||||||||
| GxupstdNotifyGroup | 1.3.6.1.4.1.534.1.100.18 | ||||||||||||||||||||
group · current The Alarm and Event notifications from the xupsTrapDefined source (xupstd).
| |||||||||||||||||||||
| GxupstdEMPNotifyGroup | 1.3.6.1.4.1.534.1.100.19 | ||||||||||||||||||||
group · current The EMP's Alarm and Event notifications from the xupsTrapDefined source (xupstd). | |||||||||||||||||||||
| MxupsMibFullCompliance | 1.3.6.1.4.1.534.1.100.20 | ||||||||||||||||||||
compliance · current A compliance statement for all of everything in this MIB.
| |||||||||||||||||||||
| GxupsDeprecatedGroup | 1.3.6.1.4.1.534.1.100.21 | deprecated | |||||||||||||||||||
group · deprecated Contains objects which are now deprecated. | |||||||||||||||||||||
| GxupsBypassTableFullGroup | 1.3.6.1.4.1.534.1.100.22 | ||||||||||||||||||||
group · current The Full set of xupsBypassTable subgroup objects. | |||||||||||||||||||||
| GxupsInputTotalFullGroup | 1.3.6.1.4.1.534.1.100.23 | ||||||||||||||||||||
group · current The Full set of xupsInputTotal subgroup objects. | |||||||||||||||||||||
| GxupsOutputTotalFullGroup | 1.3.6.1.4.1.534.1.100.24 | ||||||||||||||||||||
group · current The Full set of xupsOutputTotal subgroup objects. | |||||||||||||||||||||
| GxupsBypassTotalFullGroup | 1.3.6.1.4.1.534.1.100.25 | ||||||||||||||||||||
group · current The Full set of xupsOutputTotal subgroup objects. | |||||||||||||||||||||
| GxupsAgentFullGroup | 1.3.6.1.4.1.534.1.100.26 | ||||||||||||||||||||
group · current The Full set of xupsAgent subgroup objects. | |||||||||||||||||||||
Traps / Notifications
- xupstdAgentDown
1.3.6.1.4.1.534.1.11.4.1.0.50 - xupstdAlarmBatteryBad
1.3.6.1.4.1.534.1.11.4.1.0.23 - xupstdAlarmChargerFailed
1.3.6.1.4.1.534.1.11.4.1.0.34 - xupstdAlarmEntryAdded
1.3.6.1.4.1.534.1.11.4.1.0.21 - xupstdAlarmEntryRemoved
1.3.6.1.4.1.534.1.11.4.1.0.22 - xupstdAlarmFanFailure
1.3.6.1.4.1.534.1.11.4.1.0.35 - xupstdAlarmFuseFailure
1.3.6.1.4.1.534.1.11.4.1.0.36 - xupstdAlarmTempBad
1.3.6.1.4.1.534.1.11.4.1.0.33 - xupstdAlarmTestInProgress
1.3.6.1.4.1.534.1.11.4.1.0.28 - xupstdAltPowerNotAvailable
1.3.6.1.4.1.534.1.11.4.1.0.40 - xupstdAmbientTempBad
1.3.6.1.4.1.534.1.11.4.1.0.29 - xupstdAwaitingPower
1.3.6.1.4.1.534.1.11.4.1.0.47 - xupstdBatteryDischarged
1.3.6.1.4.1.534.1.11.4.1.0.9 - xupstdBreakerOpen
1.3.6.1.4.1.534.1.11.4.1.0.20 - xupstdBuildingAlarm
1.3.6.1.4.1.534.1.11.4.1.0.15 - xupstdBypassNotAvailable
1.3.6.1.4.1.534.1.11.4.1.0.12 - xupstdCommEstablished
1.3.6.1.4.1.534.1.11.4.1.0.49 - xupstdCommunicationsLost
1.3.6.1.4.1.534.1.11.4.1.0.26 - xupstdContactActiveNotice
1.3.6.1.4.1.534.1.11.4.1.0.30 - xupstdContactInactiveNotice
1.3.6.1.4.1.534.1.11.4.1.0.31 - xupstdControlOff
1.3.6.1.4.1.534.1.11.4.1.0.1 - xupstdControlOn
1.3.6.1.4.1.534.1.11.4.1.0.2 - xupstdDiagnosticTestFailed
1.3.6.1.4.1.534.1.11.4.1.0.25 - xupstdDiagnosticTestPassed
1.3.6.1.4.1.534.1.11.4.1.0.45 - xupstdHeartbeat
1.3.6.1.4.1.534.1.11.4.1.0.44 - xupstdInputFailure
1.3.6.1.4.1.534.1.11.4.1.0.14 - xupstdInternalFailure
1.3.6.1.4.1.534.1.11.4.1.0.8 - xupstdInverterFailure
1.3.6.1.4.1.534.1.11.4.1.0.10 - xupstdLossOfRedundancy
1.3.6.1.4.1.534.1.11.4.1.0.32 - xupstdLowBattery
1.3.6.1.4.1.534.1.11.4.1.0.4 - xupstdModuleFailure
1.3.6.1.4.1.534.1.11.4.1.0.38 - xupstdNoticeCondition
1.3.6.1.4.1.534.1.11.4.1.0.41 - xupstdOnAlternatePowerSource
1.3.6.1.4.1.534.1.11.4.1.0.39 - xupstdOnBattery
1.3.6.1.4.1.534.1.11.4.1.0.3 - xupstdOnBypass
1.3.6.1.4.1.534.1.11.4.1.0.11 - xupstdOnInverter
1.3.6.1.4.1.534.1.11.4.1.0.17 - xupstdOnMaintenanceBypass
1.3.6.1.4.1.534.1.11.4.1.0.48 - xupstdOutputBad
1.3.6.1.4.1.534.1.11.4.1.0.46 - xupstdOutputNotProtected
1.3.6.1.4.1.534.1.11.4.1.0.51 - xupstdOutputOff
1.3.6.1.4.1.534.1.11.4.1.0.13 - xupstdOutputOffAsRequested
1.3.6.1.4.1.534.1.11.4.1.0.24 - xupstdOutputOverload
1.3.6.1.4.1.534.1.11.4.1.0.7 - xupstdPowerSwitchBad
1.3.6.1.4.1.534.1.11.4.1.0.37 - xupstdRemoteHumidityBad
1.3.6.1.4.1.534.1.11.4.1.0.43 - xupstdRemoteTempBad
1.3.6.1.4.1.534.1.11.4.1.0.42 - xupstdReturnFromLowBattery
1.3.6.1.4.1.534.1.11.4.1.0.6 - xupstdShutdownImminent
1.3.6.1.4.1.534.1.11.4.1.0.16 - xupstdTestTrap
1.3.6.1.4.1.534.1.11.4.1.0.100 - xupstdUpsShutdownPending
1.3.6.1.4.1.534.1.11.4.1.0.27 - xupstdUtilityPowerRestored
1.3.6.1.4.1.534.1.11.4.1.0.5
Groups and compliance
- xupsAgentFullGroup
- xupsAlarmEventsFullGroup
- xupsAlarmFullGroup
- xupsBatteryFullGroup
- xupsBypassFullGroup
- xupsBypassTableFullGroup
- xupsBypassTotalFullGroup
- xupsConfigFullGroup
- xupsControlFullGroup
- xupsDeprecatedGroup
- xupsEnvironmentFullGroup
- xupsIdentFullGroup
- xupsInputFullGroup
- xupsInputTableFullGroup
- xupsInputTotalFullGroup
- xupsMibFullCompliance
- xupsOutputFullGroup
- xupsOutputTableFullGroup
- xupsOutputTotalFullGroup
- xupsRecepFullGroup
- xupsTestFullGroup
- xupsTopologyFullGroup
- xupsTrapControlFullGroup
- xupstdEMPNotifyGroup