EATON-EPDU-MIB
Eaton CorporationThe MIB module for Eaton ePDUs (Enclosure Power Distribution Units).
snmptranslate -m EATON-EPDU-MIB -Tpsnmpwalk -v2c -c <community> -m EATON-EPDU-MIB <host> 1.3.6.1.4.1.534.6.6.7Imports
| EATON-OIDS | pduAgent |
|---|---|
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP, OBJECT-GROUP |
| SNMPv2-SMI | Bits, Counter32, Integer32, IpAddress, MODULE-IDENTITY, MibIdentifier, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, TimeTicks, Unsigned32, enterprises, iso |
| SNMPv2-TC | DateAndTime, DisplayString, PhysAddress, TEXTUAL-CONVENTION |
OID tree
| Name | OID | Type | Access | Status | Example | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Neaton | 1.3.6.1.4.1.534 | ||||||||||||||||||||
| Nproducts | 1.3.6.1.4.1.534.6 | ||||||||||||||||||||
| NpduAgent | 1.3.6.1.4.1.534.6.6 | ||||||||||||||||||||
| IeatonEpdu | 1.3.6.1.4.1.534.6.6.7 | ||||||||||||||||||||
identity The MIB module for Eaton ePDUs (Enclosure Power Distribution Units). | |||||||||||||||||||||
| Nnotifications | 1.3.6.1.4.1.534.6.6.7.0 | ||||||||||||||||||||
| !notifyUserLogin | 1.3.6.1.4.1.534.6.6.7.0.1 | ||||||||||||||||||||
| !notifyUserLogout | 1.3.6.1.4.1.534.6.6.7.0.2 | ||||||||||||||||||||
| !notifyFailedLogin | 1.3.6.1.4.1.534.6.6.7.0.3 | ||||||||||||||||||||
notification · current Sent when someone attempts to log in and fails. On some models, may be sent after three failed login attempts.
| |||||||||||||||||||||
| !notifyBootUp | 1.3.6.1.4.1.534.6.6.7.0.4 | ||||||||||||||||||||
notification · current Sent whenever an ePDU finishes booting up (hard or soft reboot).
| |||||||||||||||||||||
| !notifyInputVoltageThStatus | 1.3.6.1.4.1.534.6.6.7.0.11 | ||||||||||||||||||||
notification · current Sent whenever an input voltage threshold status changes. | |||||||||||||||||||||
| !notifyInputCurrentThStatus | 1.3.6.1.4.1.534.6.6.7.0.12 | ||||||||||||||||||||
notification · current Sent whenever an input current threshold status changes. | |||||||||||||||||||||
| !notifyInputFrequencyStatus | 1.3.6.1.4.1.534.6.6.7.0.13 | ||||||||||||||||||||
notification · current Sent whenever the input frequency status changes. | |||||||||||||||||||||
| !notifyGroupVoltageThStatus | 1.3.6.1.4.1.534.6.6.7.0.21 | ||||||||||||||||||||
notification · current Sent whenever a group voltage threshold status changes. | |||||||||||||||||||||
| !notifyGroupCurrentThStatus | 1.3.6.1.4.1.534.6.6.7.0.22 | ||||||||||||||||||||
notification · current Sent whenever a group current threshold status changes. | |||||||||||||||||||||
| !notifyGroupBreakerStatus | 1.3.6.1.4.1.534.6.6.7.0.23 | ||||||||||||||||||||
notification · current Sent whenever a group status changes to indicate whether the circuit breaker is on or off.
| |||||||||||||||||||||
| !notifyOutletVoltageThStatus | 1.3.6.1.4.1.534.6.6.7.0.31 | ||||||||||||||||||||
notification · current Sent whenever an outlet voltage threshold status changes. | |||||||||||||||||||||
| !notifyOutletCurrentThStatus | 1.3.6.1.4.1.534.6.6.7.0.32 | ||||||||||||||||||||
notification · current Sent whenever an outlet current threshold status changes. | |||||||||||||||||||||
| !notifyOutletControlStatus | 1.3.6.1.4.1.534.6.6.7.0.33 | ||||||||||||||||||||
notification · current Sent whenever an outlet state On / Off changes.
| |||||||||||||||||||||
| !notifyTemperatureThStatus | 1.3.6.1.4.1.534.6.6.7.0.41 | ||||||||||||||||||||
notification · current Sent whenever a temperature threshold status changes. | |||||||||||||||||||||
| !notifyHumidityThStatus | 1.3.6.1.4.1.534.6.6.7.0.42 | ||||||||||||||||||||
notification · current Sent whenever a humidity threshold status changes. | |||||||||||||||||||||
| !notifyContactState | 1.3.6.1.4.1.534.6.6.7.0.43 | ||||||||||||||||||||
notification · current Sent whenever a contact sensor state changes.
| |||||||||||||||||||||
| !notifyProbeStatus | 1.3.6.1.4.1.534.6.6.7.0.44 | ||||||||||||||||||||
notification · current Sent whenever the environment probe status changes. | |||||||||||||||||||||
| !notifyCommunicationStatus | 1.3.6.1.4.1.534.6.6.7.0.51 | ||||||||||||||||||||
notification · current Sent whenever the PDU communication status changes.
| |||||||||||||||||||||
| !notifyInternalStatus | 1.3.6.1.4.1.534.6.6.7.0.52 | ||||||||||||||||||||
notification · current Sent whenever the PDU internal status changes.
| |||||||||||||||||||||
| !notifyTest | 1.3.6.1.4.1.534.6.6.7.0.53 | ||||||||||||||||||||
notification · current Sent whenever the trap test feature is used by the communication card. | |||||||||||||||||||||
| !notifyStrappingStatus | 1.3.6.1.4.1.534.6.6.7.0.54 | ||||||||||||||||||||
notification · current Sent whenever the strapping communication status changes.
| |||||||||||||||||||||
| Nunits | 1.3.6.1.4.1.534.6.6.7.1 | ||||||||||||||||||||
| SunitsPresent | 1.3.6.1.4.1.534.6.6.7.1.1 | DisplayString | RO | ||||||||||||||||||
scalar · DisplayString · read-only · current Each unit is identified by a Strapping Index. This object returns a comma-delimited list of the Strapping Indexes of all units present in the strapping group. For example, if units 0, 1, 5, and 7 are present, this value will be '0,1,5,7'. For units that do not support strapping, a Strapping Index of '0' is assumed. | |||||||||||||||||||||
| TunitTable | 1.3.6.1.4.1.534.6.6.7.1.2 | NA | |||||||||||||||||||
table · not-accessible · current A list of units. In most cases this list will only contain one entry. However, some units have a 'strapping' feature which allow units to be daisy-chained together such that all of them can be accessed through the SNMP interface of the master. If strapping is enabled, the strapping indexes of the units that can be accessed will be listed in the unitsPresent object. | |||||||||||||||||||||
| RunitEntry | 1.3.6.1.4.1.534.6.6.7.1.2.1 | NA | |||||||||||||||||||
| CstrappingIndex | 1.3.6.1.4.1.534.6.6.7.1.2.1.1 | Integer32 (0..23) | AN | ||||||||||||||||||
column · Integer32 (0..23) · accessible-for-notify · current For units that support 'strapping' functionality, this will be a unique value for each unit. If units do not support 'strapping', this will always be '0'. | |||||||||||||||||||||
| CproductName | 1.3.6.1.4.1.534.6.6.7.1.2.1.2 | OCTET STRING (SIZE (1..127)) | RO | ||||||||||||||||||
column · OCTET STRING (SIZE (1..127)) · read-only · current Name of the product. | |||||||||||||||||||||
| CpartNumber | 1.3.6.1.4.1.534.6.6.7.1.2.1.3 | OCTET STRING | RO | EMA114-10 | |||||||||||||||||
column · OCTET STRING · read-only · current Part number of the unit. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CserialNumber | 1.3.6.1.4.1.534.6.6.7.1.2.1.4 | OCTET STRING | RO | H619P44058 | |||||||||||||||||
column · OCTET STRING · read-only · current Serial number of the unit. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CfirmwareVersion | 1.3.6.1.4.1.534.6.6.7.1.2.1.5 | OCTET STRING | RO | 05.01.0002 | |||||||||||||||||
column · OCTET STRING · read-only · current Firmware version. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CunitName | 1.3.6.1.4.1.534.6.6.7.1.2.1.6 | OCTET STRING (SIZE (1..63)) | RW | ||||||||||||||||||
column · OCTET STRING (SIZE (1..63)) · read-write · current Descriptive name for the unit. | |||||||||||||||||||||
| ClcdControl | 1.3.6.1.4.1.534.6.6.7.1.2.1.7 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current Control the local LCD.
| |||||||||||||||||||||
| CclockValue | 1.3.6.1.4.1.534.6.6.7.1.2.1.8 | DateAndTime | RW | ||||||||||||||||||
column · DateAndTime · read-write · current Clock value. This could be from either a real-time clock (in which case it is likely writeable) or from a time server via NTP (probably read-only). | |||||||||||||||||||||
| CtemperatureScale | 1.3.6.1.4.1.534.6.6.7.1.2.1.9 | INTEGER | RW | celsius(0) | |||||||||||||||||
column · INTEGER · read-write · current Scale used to return temperature objects.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CunitType | 1.3.6.1.4.1.534.6.6.7.1.2.1.10 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current Technical capabilities of the PDU. Functionality is as follows: Monitored (MI) - input and usually section/group monitoring. Advanced Monitored (AM) - input, section/group, and outlet monitoring. Switched (SW) - input and section/group monitoring, outlet switching. Basic (BA) - no communication card. Inline Monitored (IL) - input and usually one section/group monitoring.
| |||||||||||||||||||||
| CsystemType | 1.3.6.1.4.1.534.6.6.7.1.2.1.11 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current Architecture of the ePDU electronic.
| |||||||||||||||||||||
| CinputCount | 1.3.6.1.4.1.534.6.6.7.1.2.1.20 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Number of inputs on this ePDU. | |||||||||||||||||||||
| CgroupCount | 1.3.6.1.4.1.534.6.6.7.1.2.1.21 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Number of groups on this ePDU. Groups include breakers, outlet sections, and user-defined groups. | |||||||||||||||||||||
| CoutletCount | 1.3.6.1.4.1.534.6.6.7.1.2.1.22 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Number of outlets on this ePDU. | |||||||||||||||||||||
| CtemperatureCount | 1.3.6.1.4.1.534.6.6.7.1.2.1.23 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Max number of temperature measurements on this ePDU. | |||||||||||||||||||||
| ChumidityCount | 1.3.6.1.4.1.534.6.6.7.1.2.1.24 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Max number of humidity measurements on this ePDU. | |||||||||||||||||||||
| CcontactCount | 1.3.6.1.4.1.534.6.6.7.1.2.1.25 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Max number of contact sensors on this ePDU. | |||||||||||||||||||||
| CcommunicationStatus | 1.3.6.1.4.1.534.6.6.7.1.2.1.30 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current Status of the internal communication with the PDU.
| |||||||||||||||||||||
| CinternalStatus | 1.3.6.1.4.1.534.6.6.7.1.2.1.31 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current Status of the internal failure inside the PDU.
| |||||||||||||||||||||
| CstrappingStatus | 1.3.6.1.4.1.534.6.6.7.1.2.1.32 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current Status of the external communication with a strapping unit.
| |||||||||||||||||||||
| CuserName | 1.3.6.1.4.1.534.6.6.7.1.2.1.40 | OCTET STRING (SIZE (0..31)) | AN | ||||||||||||||||||
column · OCTET STRING (SIZE (0..31)) · accessible-for-notify · current Username used to log into the PDU. | |||||||||||||||||||||
| CcommInterface | 1.3.6.1.4.1.534.6.6.7.1.2.1.41 | INTEGER | AN | ||||||||||||||||||
column · INTEGER · accessible-for-notify · current Communications interface used to log into the PDU.
| |||||||||||||||||||||
| TunitControlTable | 1.3.6.1.4.1.534.6.6.7.1.3 | NA | |||||||||||||||||||
table · not-accessible · current A list of units that have controllable outlets. | |||||||||||||||||||||
| RunitControlEntry | 1.3.6.1.4.1.534.6.6.7.1.3.1 | NA | |||||||||||||||||||
| CunitControlOffCmd | 1.3.6.1.4.1.534.6.6.7.1.3.1.2 | Integer32 (-1..99999) | RW | ||||||||||||||||||
column · Integer32 (-1..99999) · read-write · current Unit-level outlet control command.
Once the command is issued, outlets will turn Off.
0-n : Time in seconds until the outlet Sequence Off command is issued
-1 : Cancel a pending unit-level Off command
When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command.
Certain ePDUs (mainly those with part numbers beginning with IPV or IPC) do not support delayed control
commands. These will respond with an error if a command value of > 0 is written to this object. | |||||||||||||||||||||
| CunitControlOnCmd | 1.3.6.1.4.1.534.6.6.7.1.3.1.3 | Integer32 (-1..99999) | RW | ||||||||||||||||||
column · Integer32 (-1..99999) · read-write · current Unit-level outlet control command.
Once the command is issued, outlets will turn On according to their outletControlSequenceDelay value.
0-n : Time in seconds until the outlet Sequence On command is issued
-1 : Cancel a pending unit-level On command
When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command.
Certain ePDUs (mainly those with part numbers beginning with IPV or IPC) do not support delayed control
commands. These will respond with an error if a command value of > 0 is written to this object. | |||||||||||||||||||||
| Ninputs | 1.3.6.1.4.1.534.6.6.7.3 | ||||||||||||||||||||
| TinputTable | 1.3.6.1.4.1.534.6.6.7.3.1 | NA | |||||||||||||||||||
table · not-accessible · current List of inputs to the PDU. | |||||||||||||||||||||
| RinputEntry | 1.3.6.1.4.1.534.6.6.7.3.1.1 | NA | |||||||||||||||||||
| CinputIndex | 1.3.6.1.4.1.534.6.6.7.3.1.1.1 | Integer32 (1..2) | AN | ||||||||||||||||||
column · Integer32 (1..2) · accessible-for-notify · current A unique value for each input. Its value ranges from 1 to inputCount. | |||||||||||||||||||||
| CinputType | 1.3.6.1.4.1.534.6.6.7.3.1.1.2 | INTEGER | RO | singlePhase(1) | |||||||||||||||||
column · INTEGER · read-only · current Type of input - single phase, split phase, three phase delta, or three phase wye.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputFrequency | 1.3.6.1.4.1.534.6.6.7.3.1.1.3 | Integer32 | RO | 600 | |||||||||||||||||
column · Integer32 · read-only · current Units are 0.1 Hz; divide by ten to get Hz. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputFrequencyStatus | 1.3.6.1.4.1.534.6.6.7.3.1.1.4 | INTEGER | RO | good(0) | |||||||||||||||||
column · INTEGER · read-only · current Status of the measured input frequency relative to the nominal frequency and the admitted tolerance.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputVoltageCount | 1.3.6.1.4.1.534.6.6.7.3.1.1.5 | Integer32 | RO | 1 | |||||||||||||||||
column · Integer32 · read-only · current Number of input voltage measurements on this ePDU. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputCurrentCount | 1.3.6.1.4.1.534.6.6.7.3.1.1.6 | Integer32 | RO | 1 | |||||||||||||||||
column · Integer32 · read-only · current Number of input current measurements on this ePDU. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputPowerCount | 1.3.6.1.4.1.534.6.6.7.3.1.1.7 | Integer32 | RO | 1 | |||||||||||||||||
column · Integer32 · read-only · current Number of rows in the inputPowerTable. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputPlugType | 1.3.6.1.4.1.534.6.6.7.3.1.1.8 | INTEGER | RO | nemaL520(123) | |||||||||||||||||
column · INTEGER · read-only · current Identifies which plug is on the input.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputFeedColor | 1.3.6.1.4.1.534.6.6.7.3.1.1.9 | Unsigned32 (0..16777215) | RW | 0 | |||||||||||||||||
column · Unsigned32 (0..16777215) · read-write · current Color code of the input feed. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputFeedName | 1.3.6.1.4.1.534.6.6.7.3.1.1.10 | OCTET STRING (SIZE (1..31)) | RW | Feed A | |||||||||||||||||
column · OCTET STRING (SIZE (1..31)) · read-write · current A descriptive name for the input. Example values from LibreNMS test devices
| |||||||||||||||||||||
| TinputVoltageTable | 1.3.6.1.4.1.534.6.6.7.3.2 | NA | |||||||||||||||||||
table · not-accessible · current A list of input voltage measurements. The number of entries is given by inputVoltageCount. | |||||||||||||||||||||
| RinputVoltageEntry | 1.3.6.1.4.1.534.6.6.7.3.2.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry for a particular input voltage measurement. | |||||||||||||||||||||
| CinputVoltageIndex | 1.3.6.1.4.1.534.6.6.7.3.2.1.1 | Integer32 (1..3) | AN | ||||||||||||||||||
column · Integer32 (1..3) · accessible-for-notify · current A unique value for each input voltage measurement. Its value ranges from 1 to inputVoltageCount. | |||||||||||||||||||||
| CinputVoltageMeasType | 1.3.6.1.4.1.534.6.6.7.3.2.1.2 | INTEGER | RO | singlePhase(1) | |||||||||||||||||
column · INTEGER · read-only · current Value indicates what input voltage is being measured in this table row - single phase voltage, phase 1 to neutral, phase 2 to neutral, phase 3 to neutral, phase 1 to phase 2, phase 2 to phase 3, or phase 3 to phase 1.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputVoltage | 1.3.6.1.4.1.534.6.6.7.3.2.1.3 | Integer32 | RO | 118450 | |||||||||||||||||
column · Integer32 · read-only · current An input voltage measurement value. Units are millivolts. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputVoltageThStatus | 1.3.6.1.4.1.534.6.6.7.3.2.1.4 | INTEGER | RO | good(0) | |||||||||||||||||
column · INTEGER · read-only · current Status of the measured input voltage relative to the configured thresholds.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputVoltageThLowerWarning | 1.3.6.1.4.1.534.6.6.7.3.2.1.5 | Integer32 (-1..500000) | RW | 95000 | |||||||||||||||||
column · Integer32 (-1..500000) · read-write · current Lower warning threshold. Units are millivolts. A negative value indicates that this object is not available. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputVoltageThLowerCritical | 1.3.6.1.4.1.534.6.6.7.3.2.1.6 | Integer32 (-1..500000) | RW | 90000 | |||||||||||||||||
column · Integer32 (-1..500000) · read-write · current Lower critical threshold. Units are millivolts. A negative value indicates that this object is not available. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputVoltageThUpperWarning | 1.3.6.1.4.1.534.6.6.7.3.2.1.7 | Integer32 (-1..500000) | RW | 130000 | |||||||||||||||||
column · Integer32 (-1..500000) · read-write · current Upper warning threshold. Units are millivolts. A negative value indicates that this object is not available. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputVoltageThUpperCritical | 1.3.6.1.4.1.534.6.6.7.3.2.1.8 | Integer32 (-1..500000) | RW | 140000 | |||||||||||||||||
column · Integer32 (-1..500000) · read-write · current Upper critical threshold. Units are millivolts. A negative value indicates that this object is not available. Example values from LibreNMS test devices
| |||||||||||||||||||||
| TinputCurrentTable | 1.3.6.1.4.1.534.6.6.7.3.3 | NA | |||||||||||||||||||
table · not-accessible · current A list of input current measurements. The number of entries is given by inputCurrentCount. | |||||||||||||||||||||
| RinputCurrentEntry | 1.3.6.1.4.1.534.6.6.7.3.3.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry for a particular input current measurement. | |||||||||||||||||||||
| CinputCurrentIndex | 1.3.6.1.4.1.534.6.6.7.3.3.1.1 | Integer32 (1..4) | AN | ||||||||||||||||||
column · Integer32 (1..4) · accessible-for-notify · current A unique value for each input current measurement. Its value ranges from 1 to inputCurrentCount. | |||||||||||||||||||||
| CinputCurrentMeasType | 1.3.6.1.4.1.534.6.6.7.3.3.1.2 | INTEGER | RO | singlePhase(1) | |||||||||||||||||
column · INTEGER · read-only · current Which input wire is being measured in this table row - single phase, neutral, phase 1, phase 2, or phase 3.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputCurrentCapacity | 1.3.6.1.4.1.534.6.6.7.3.3.1.3 | Integer32 | RO | 16000 | |||||||||||||||||
column · Integer32 · read-only · current Rated current capacity of the input. A negative value indicates that the hardware current capacity is unknown. Units are milliamps. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputCurrent | 1.3.6.1.4.1.534.6.6.7.3.3.1.4 | Integer32 | RO | 14108 | |||||||||||||||||
column · Integer32 · read-only · current An input current measurement value. Units are milliamps. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputCurrentThStatus | 1.3.6.1.4.1.534.6.6.7.3.3.1.5 | INTEGER | RO | highWarning(3) | |||||||||||||||||
column · INTEGER · read-only · current Status of the measured input current relative to the configured thresholds.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputCurrentThLowerWarning | 1.3.6.1.4.1.534.6.6.7.3.3.1.6 | Integer32 (-1..100000) | RW | 0 | |||||||||||||||||
column · Integer32 (-1..100000) · read-write · current Lower warning threshold. Units are milliamps. A negative value indicates that this object is not available. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputCurrentThLowerCritical | 1.3.6.1.4.1.534.6.6.7.3.3.1.7 | Integer32 (-1..100000) | RW | -1 | |||||||||||||||||
column · Integer32 (-1..100000) · read-write · current Lower critical threshold. Units are milliamps. A negative value indicates that this object is not available. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputCurrentThUpperWarning | 1.3.6.1.4.1.534.6.6.7.3.3.1.8 | Integer32 (-1..100000) | RW | 12800 | |||||||||||||||||
column · Integer32 (-1..100000) · read-write · current Upper warning threshold. Units are milliamps. A negative value indicates that this object is not available. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputCurrentThUpperCritical | 1.3.6.1.4.1.534.6.6.7.3.3.1.9 | Integer32 (-1..100000) | RW | 16000 | |||||||||||||||||
column · Integer32 (-1..100000) · read-write · current Upper critical threshold. Units are milliamps. A negative value indicates that this object is not available. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputCurrentCrestFactor | 1.3.6.1.4.1.534.6.6.7.3.3.1.10 | Integer32 | RO | 2212 | |||||||||||||||||
column · Integer32 · read-only · current Current crest factor. Units are in milli, for example a crest factor of
1.414 will be returned as 1414. A negative value indicates
that this object is not available.Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputCurrentPercentLoad | 1.3.6.1.4.1.534.6.6.7.3.3.1.11 | Integer32 | RO | 88 | |||||||||||||||||
column · Integer32 · read-only · current Current percent load, based on the rated current capacity. Units are percentage, for example 80% will be returned as 80. A negative value indicates that this object is not available. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputPhaseDesignator | 1.3.6.1.4.1.534.6.6.7.3.3.1.12 | DisplayString (SIZE (2..4)) | RO | L1 | |||||||||||||||||
column · DisplayString (SIZE (2..4)) · read-only · current Alphanumeric physical name for the input. Example values from LibreNMS test devices
| |||||||||||||||||||||
| TinputPowerTable | 1.3.6.1.4.1.534.6.6.7.3.4 | NA | |||||||||||||||||||
table · not-accessible · current A list of input power measurements. The number of entries is given by inputPowerCount. | |||||||||||||||||||||
| RinputPowerEntry | 1.3.6.1.4.1.534.6.6.7.3.4.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry for an input power measurement. | |||||||||||||||||||||
| CinputPowerIndex | 1.3.6.1.4.1.534.6.6.7.3.4.1.1 | Integer32 (1..12) | NA | ||||||||||||||||||
column · Integer32 (1..12) · not-accessible · current A unique value for each input power measurement. Its value ranges from 1 to inputPowerCount. | |||||||||||||||||||||
| CinputPowerMeasType | 1.3.6.1.4.1.534.6.6.7.3.4.1.2 | INTEGER | RO | phase1(1) | |||||||||||||||||
column · INTEGER · read-only · current Value indicates what is being measured in this table row.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputVA | 1.3.6.1.4.1.534.6.6.7.3.4.1.3 | Integer32 | RO | 1674 | |||||||||||||||||
column · Integer32 · read-only · current An input VA value. Units are VA. A negative value indicates that this object is not available. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputWatts | 1.3.6.1.4.1.534.6.6.7.3.4.1.4 | Integer32 | RO | 1589 | |||||||||||||||||
column · Integer32 · read-only · current An input Watts value. Units are Watts. A negative value indicates that this object is not available. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputWh | 1.3.6.1.4.1.534.6.6.7.3.4.1.5 | Unsigned32 (0..4294967295) | RW | 8185553 | |||||||||||||||||
column · Unsigned32 (0..4294967295) · read-write · current Units are Watt-hours. This object is writable so that it can be reset to 0. When it is written to, the inputWhTimer will be reset updated as well. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputWhTimer | 1.3.6.1.4.1.534.6.6.7.3.4.1.6 | UnixTimeStamp | RO | 0 | |||||||||||||||||
column · UnixTimeStamp · read-only · current Timestamp of when input Watt-hours (inputWh) was last reset. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputPowerFactor | 1.3.6.1.4.1.534.6.6.7.3.4.1.7 | Integer32 | RO | -946 | |||||||||||||||||
column · Integer32 · read-only · current An input PF value. Units are in thousandths, for example a power factor
of 0.958 would be returned as 958, and 0.92 would be returned
as 920. A negative value indicates that this object is not
available.Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputVAR | 1.3.6.1.4.1.534.6.6.7.3.4.1.8 | Integer32 | RO | -541 | |||||||||||||||||
column · Integer32 · read-only · current An input VAR value. Units are VAR. A negative value indicates that this object is not available. Example values from LibreNMS test devices
| |||||||||||||||||||||
| TinputTotalPowerTable | 1.3.6.1.4.1.534.6.6.7.3.5 | NA | |||||||||||||||||||
table · not-accessible · current A list of total input power measurements. | |||||||||||||||||||||
| RinputTotalPowerEntry | 1.3.6.1.4.1.534.6.6.7.3.5.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry for a total input power measurement.
| |||||||||||||||||||||
| CinputTotalVA | 1.3.6.1.4.1.534.6.6.7.3.5.1.3 | Integer32 | RO | 1673 | |||||||||||||||||
column · Integer32 · read-only · current An input VA value. Units are VA. A negative value indicates that this object is not available. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputTotalWatts | 1.3.6.1.4.1.534.6.6.7.3.5.1.4 | Integer32 | RO | 1584 | |||||||||||||||||
column · Integer32 · read-only · current An input Watts value. Units are Watts. A negative value indicates that this object is not available. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputTotalWh | 1.3.6.1.4.1.534.6.6.7.3.5.1.5 | Unsigned32 (0..4294967295) | RW | 8185493 | |||||||||||||||||
column · Unsigned32 (0..4294967295) · read-write · current Units are Watt-hours. This object is writable so that it can be reset to 0. When it is written to, the inputWhTimer will be reset updated as well. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputTotalWhTimer | 1.3.6.1.4.1.534.6.6.7.3.5.1.6 | UnixTimeStamp | RO | 1700853055 | |||||||||||||||||
column · UnixTimeStamp · read-only · current Timestamp of when input Watt-hours (inputWh) was last reset. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputTotalPowerFactor | 1.3.6.1.4.1.534.6.6.7.3.5.1.7 | Integer32 | RO | 946 | |||||||||||||||||
column · Integer32 · read-only · current An input PF value. Units are in thousandths, for example a power factor
of 0.958 would be returned as 958, and 0.92 would be returned
as 920. A negative value indicates that this object is not
available.Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputTotalVAR | 1.3.6.1.4.1.534.6.6.7.3.5.1.8 | Integer32 | RO | -541 | |||||||||||||||||
column · Integer32 · read-only · current An input VAR value. Units are VAR. A negative value indicates that this object is not available. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CinputPowerCapacity | 1.3.6.1.4.1.534.6.6.7.3.5.1.9 | Integer32 | RO | 1920 | |||||||||||||||||
column · Integer32 · read-only · current Typical power capacity of the input. A negative value indicates that the hardware current capacity is unknown. Example values from LibreNMS test devices
| |||||||||||||||||||||
| Ngroups | 1.3.6.1.4.1.534.6.6.7.5 | ||||||||||||||||||||
| TgroupTable | 1.3.6.1.4.1.534.6.6.7.5.1 | NA | |||||||||||||||||||
table · not-accessible · current A list of groups. The number of entries is given by groupCount. | |||||||||||||||||||||
| RgroupEntry | 1.3.6.1.4.1.534.6.6.7.5.1.1 | NA | |||||||||||||||||||
| CgroupIndex | 1.3.6.1.4.1.534.6.6.7.5.1.1.1 | Integer32 (1..64) | AN | ||||||||||||||||||
column · Integer32 (1..64) · accessible-for-notify · current A unique value for each group. Its value ranges from 1 to groupCount. | |||||||||||||||||||||
| CgroupID | 1.3.6.1.4.1.534.6.6.7.5.1.1.2 | DisplayString (SIZE (2..4)) | RO | ||||||||||||||||||
column · DisplayString (SIZE (2..4)) · read-only · current Alphanumeric designator for the group. This value may be written on the face of the unit. | |||||||||||||||||||||
| CgroupName | 1.3.6.1.4.1.534.6.6.7.5.1.1.3 | OCTET STRING (SIZE (1..31)) | RW | Section A | |||||||||||||||||
column · OCTET STRING (SIZE (1..31)) · read-write · current A descriptive name for the group. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CgroupType | 1.3.6.1.4.1.534.6.6.7.5.1.1.4 | INTEGER | RO | breaker1pole(1) | |||||||||||||||||
column · INTEGER · read-only · current The type of the group.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CgroupBreakerStatus | 1.3.6.1.4.1.534.6.6.7.5.1.1.5 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current Only applicable to breaker-groups. Indicates whether a breaker is turned off or on.
| |||||||||||||||||||||
| CgroupChildCount | 1.3.6.1.4.1.534.6.6.7.5.1.1.6 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Number of children for this group. | |||||||||||||||||||||
| CgroupColor | 1.3.6.1.4.1.534.6.6.7.5.1.1.7 | Unsigned32 (0..16777215) | RO | ||||||||||||||||||
column · Unsigned32 (0..16777215) · read-only · current Background color code of the group. Color codes are decimal values. | |||||||||||||||||||||
| CgroupDesignator | 1.3.6.1.4.1.534.6.6.7.5.1.1.8 | DisplayString (SIZE (2..4)) | RO | ||||||||||||||||||
column · DisplayString (SIZE (2..4)) · read-only · current Alphanumeric physical name for the group. This value may be written on the face of the unit. | |||||||||||||||||||||
| CgroupInputIndex | 1.3.6.1.4.1.534.6.6.7.5.1.1.9 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Identifies the input on which the group is connected. | |||||||||||||||||||||
| TgroupChildTable | 1.3.6.1.4.1.534.6.6.7.5.2 | NA | |||||||||||||||||||
table · not-accessible · current A list of children for this group. For example, this table will link to all of the outlets that are contained in a particular group. | |||||||||||||||||||||
| RgroupChildEntry | 1.3.6.1.4.1.534.6.6.7.5.2.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry for a particular child. | |||||||||||||||||||||
| CgroupChildIndex | 1.3.6.1.4.1.534.6.6.7.5.2.1.1 | Integer32 (1..32) | NA | ||||||||||||||||||
column · Integer32 (1..32) · not-accessible · current A unique value for each child. Its value ranges from 1 to groupChildCount. | |||||||||||||||||||||
| CgroupChildType | 1.3.6.1.4.1.534.6.6.7.5.2.1.2 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current The type of the child.
| |||||||||||||||||||||
| CgroupChildOID | 1.3.6.1.4.1.534.6.6.7.5.2.1.3 | OBJECT IDENTIFIER | RO | ||||||||||||||||||
column · OBJECT IDENTIFIER · read-only · current Object ID of a child object. | |||||||||||||||||||||
| TgroupVoltageTable | 1.3.6.1.4.1.534.6.6.7.5.3 | NA | |||||||||||||||||||
table · not-accessible · current A list of group voltage measurements. There can be only one voltage measurement for each group. | |||||||||||||||||||||
| RgroupVoltageEntry | 1.3.6.1.4.1.534.6.6.7.5.3.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry for a group voltage measurement.
| |||||||||||||||||||||
| CgroupVoltageMeasType | 1.3.6.1.4.1.534.6.6.7.5.3.1.2 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current Value indicates what voltage is being measured in this table row.
| |||||||||||||||||||||
| CgroupVoltage | 1.3.6.1.4.1.534.6.6.7.5.3.1.3 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Units are millivolts. | |||||||||||||||||||||
| CgroupVoltageThStatus | 1.3.6.1.4.1.534.6.6.7.5.3.1.4 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current Status of the measured group voltage relative to the configured thresholds.
| |||||||||||||||||||||
| CgroupVoltageThLowerWarning | 1.3.6.1.4.1.534.6.6.7.5.3.1.5 | Integer32 (-1..500000) | RW | ||||||||||||||||||
column · Integer32 (-1..500000) · read-write · current Lower warning threshold. Units are millivolts. A negative value indicates that this object is not available. | |||||||||||||||||||||
| CgroupVoltageThLowerCritical | 1.3.6.1.4.1.534.6.6.7.5.3.1.6 | Integer32 (-1..500000) | RW | ||||||||||||||||||
column · Integer32 (-1..500000) · read-write · current Lower critical threshold. Units are millivolts. A negative value indicates that this object is not available. | |||||||||||||||||||||
| CgroupVoltageThUpperWarning | 1.3.6.1.4.1.534.6.6.7.5.3.1.7 | Integer32 (-1..500000) | RW | ||||||||||||||||||
column · Integer32 (-1..500000) · read-write · current Upper warning threshold. Units are millivolts. A negative value indicates that this object is not available. | |||||||||||||||||||||
| CgroupVoltageThUpperCritical | 1.3.6.1.4.1.534.6.6.7.5.3.1.8 | Integer32 (-1..500000) | RW | ||||||||||||||||||
column · Integer32 (-1..500000) · read-write · current Upper critical threshold. Units are millivolts. A negative value indicates that this object is not available. | |||||||||||||||||||||
| TgroupCurrentTable | 1.3.6.1.4.1.534.6.6.7.5.4 | NA | |||||||||||||||||||
table · not-accessible · current A list of group current measurements. There can be only one current measurement for each group. | |||||||||||||||||||||
| RgroupCurrentEntry | 1.3.6.1.4.1.534.6.6.7.5.4.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry for a group current measurement.
| |||||||||||||||||||||
| CgroupCurrentCapacity | 1.3.6.1.4.1.534.6.6.7.5.4.1.2 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Rated current capacity of the group. Units are milliamps. A negative value indicates that the hardware current capacity is unknown (it will always be unknown for custom groups). | |||||||||||||||||||||
| CgroupCurrent | 1.3.6.1.4.1.534.6.6.7.5.4.1.3 | Integer32 | RO | 1520 | |||||||||||||||||
column · Integer32 · read-only · current A group current measurement value. Units are milliamps. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CgroupCurrentThStatus | 1.3.6.1.4.1.534.6.6.7.5.4.1.4 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current Status of the measured group current relative to the configured thresholds.
| |||||||||||||||||||||
| CgroupCurrentThLowerWarning | 1.3.6.1.4.1.534.6.6.7.5.4.1.5 | Integer32 (-1..100000) | RW | ||||||||||||||||||
column · Integer32 (-1..100000) · read-write · current Lower warning threshold. Units are milliamps. A negative value indicates that this object is not available. | |||||||||||||||||||||
| CgroupCurrentThLowerCritical | 1.3.6.1.4.1.534.6.6.7.5.4.1.6 | Integer32 (-1..100000) | RW | ||||||||||||||||||
column · Integer32 (-1..100000) · read-write · current Lower critical threshold. Units are milliamps. A negative value indicates that this object is not available. | |||||||||||||||||||||
| CgroupCurrentThUpperWarning | 1.3.6.1.4.1.534.6.6.7.5.4.1.7 | Integer32 (-1..100000) | RW | 12800 | |||||||||||||||||
column · Integer32 (-1..100000) · read-write · current Upper warning threshold. Units are milliamps. A negative value indicates that this object is not available. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CgroupCurrentThUpperCritical | 1.3.6.1.4.1.534.6.6.7.5.4.1.8 | Integer32 (-1..100000) | RW | 16000 | |||||||||||||||||
column · Integer32 (-1..100000) · read-write · current Upper critical threshold. Units are milliamps. A negative value indicates that this object is not available. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CgroupCurrentCrestFactor | 1.3.6.1.4.1.534.6.6.7.5.4.1.9 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Current crest factor. Units are in milli, for example a crest factor of
1.414 will be returned as 1414. A negative value indicates
that this object is not available. | |||||||||||||||||||||
| CgroupCurrentPercentLoad | 1.3.6.1.4.1.534.6.6.7.5.4.1.10 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Current percent load, based on the rated current capacity. Units are percentage, for example 80% will be returned as 80. A negative value indicates that this object is not available. | |||||||||||||||||||||
| TgroupPowerTable | 1.3.6.1.4.1.534.6.6.7.5.5 | NA | |||||||||||||||||||
table · not-accessible · current A list of group power measurements. There can be only one power measurement for each group. | |||||||||||||||||||||
| RgroupPowerEntry | 1.3.6.1.4.1.534.6.6.7.5.5.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry for a group power measurement.
| |||||||||||||||||||||
| CgroupVA | 1.3.6.1.4.1.534.6.6.7.5.5.1.2 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current A group VA value. Units are VA. A negative value indicates that this object is not available. | |||||||||||||||||||||
| CgroupWatts | 1.3.6.1.4.1.534.6.6.7.5.5.1.3 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current A group Watts value. Units are Watts. A negative value indicates that this object is not available. | |||||||||||||||||||||
| CgroupWh | 1.3.6.1.4.1.534.6.6.7.5.5.1.4 | Unsigned32 (0..4294967295) | RW | ||||||||||||||||||
column · Unsigned32 (0..4294967295) · read-write · current Units are Watt-hours. This object is writable so that it can be reset to 0. When it is written to, the inputWhTotalTimer will be reset to 0 as well. | |||||||||||||||||||||
| CgroupWhTimer | 1.3.6.1.4.1.534.6.6.7.5.5.1.5 | UnixTimeStamp | RO | ||||||||||||||||||
column · UnixTimeStamp · read-only · current Timestamp of when group Watt-hours (groupWh) was last reset. | |||||||||||||||||||||
| CgroupPowerFactor | 1.3.6.1.4.1.534.6.6.7.5.5.1.6 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current A group PF value. Units are in thousandths, for example a power factor
of 0.958 would be returned as 958, and 0.92 would be returned
as 920. A negative value indicates that this object is not available. | |||||||||||||||||||||
| CgroupVAR | 1.3.6.1.4.1.534.6.6.7.5.5.1.7 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current A group VAR value. Units are VAR. A negative value indicates that this object is not available. | |||||||||||||||||||||
| TgroupControlTable | 1.3.6.1.4.1.534.6.6.7.5.6 | NA | |||||||||||||||||||
table · not-accessible · current A list of controllable groups. | |||||||||||||||||||||
| RgroupControlEntry | 1.3.6.1.4.1.534.6.6.7.5.6.1 | NA | |||||||||||||||||||
| CgroupControlStatus | 1.3.6.1.4.1.534.6.6.7.5.6.1.2 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current Current state of a controlled group. A value of 'mixed' means that that the outlets within the group have differing states.
| |||||||||||||||||||||
| CgroupControlOffCmd | 1.3.6.1.4.1.534.6.6.7.5.6.1.3 | Integer32 (-1..99999) | RW | ||||||||||||||||||
column · Integer32 (-1..99999) · read-write · current Group-level outlet control command.
Once the command is issued, the outlets in the group will turn Off immediately.
0-n : Time in seconds until the group command is issued
-1 : Cancel a pending group-level Off command
When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command.
Certain ePDUs (mainly those with part numbers beginning with IPV or IPC) do not support delayed control
commands. These will respond with an error if a command value of > 0 is written to this object. | |||||||||||||||||||||
| CgroupControlOnCmd | 1.3.6.1.4.1.534.6.6.7.5.6.1.4 | Integer32 (-1..99999) | RW | ||||||||||||||||||
column · Integer32 (-1..99999) · read-write · current Group-level outlet control command.
Once the command is issued, the outlets in the group will turn On immediately.
0-n : Time in seconds until the group command is issued
-1 : Cancel a pending group-level On command
When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command.
Certain ePDUs (mainly those with part numbers beginning with IPV or IPC) do not support delayed control
commands. These will respond with an error if a command value of > 0 is written to this object. | |||||||||||||||||||||
| CgroupControlRebootCmd | 1.3.6.1.4.1.534.6.6.7.5.6.1.5 | Integer32 (-1..0) | RW | ||||||||||||||||||
column · Integer32 (-1..0) · read-write · current Group-level outlet control command.
For outlets that are On prior to the Reboot command, they will switch Off immediately when the command is
issued, remain Off for outletControlRebootOffTime seconds, and then turn back On.
For outlets that are Off prior to the Reboot command, they will turn On after a delay of outletControlRebootOffTime
seconds from when the command is issued.
0-n : Time in seconds until the Reboot command is issued
-1 : Cancel a pending group-level Reboot command
When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command.
Certain ePDUs (mainly those with part numbers beginning with IPV or IPC) do not support delayed control
commands. These will respond with an error if a command value of > 0 is written to this object. | |||||||||||||||||||||
| Noutlets | 1.3.6.1.4.1.534.6.6.7.6 | ||||||||||||||||||||
| ToutletTable | 1.3.6.1.4.1.534.6.6.7.6.1 | NA | |||||||||||||||||||
table · not-accessible · current A list of outlets. The number of entries is given by outletCount. | |||||||||||||||||||||
| RoutletEntry | 1.3.6.1.4.1.534.6.6.7.6.1.1 | NA | |||||||||||||||||||
| CoutletIndex | 1.3.6.1.4.1.534.6.6.7.6.1.1.1 | Integer32 (1..64) | AN | ||||||||||||||||||
column · Integer32 (1..64) · accessible-for-notify · current A unique value for each outlet. its value ranges from 1 to outletCount. | |||||||||||||||||||||
| CoutletID | 1.3.6.1.4.1.534.6.6.7.6.1.1.2 | DisplayString (SIZE (2..4)) | RO | 1 | |||||||||||||||||
column · DisplayString (SIZE (2..4)) · read-only · current Alphanumeric designator for the outlet. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletName | 1.3.6.1.4.1.534.6.6.7.6.1.1.3 | OCTET STRING (SIZE (1..31)) | RW | Power strip + s-rw-lab-rack | |||||||||||||||||
column · OCTET STRING (SIZE (1..31)) · read-write · current A descriptive name for the outlet. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletParentCount | 1.3.6.1.4.1.534.6.6.7.6.1.1.4 | Integer32 | RO | 1 | |||||||||||||||||
column · Integer32 · read-only · current Number of parents for this outlet. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletType | 1.3.6.1.4.1.534.6.6.7.6.1.1.5 | INTEGER | RO | nema520(22) | |||||||||||||||||
column · INTEGER · read-only · current The physical type of outlet.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletDesignator | 1.3.6.1.4.1.534.6.6.7.6.1.1.6 | DisplayString (SIZE (2..4)) | RO | A1 | |||||||||||||||||
column · DisplayString (SIZE (2..4)) · read-only · current Alphanumeric physical name for the outlet. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletPhaseID | 1.3.6.1.4.1.534.6.6.7.6.1.1.7 | INTEGER | RO | singlePhase(1) | |||||||||||||||||
column · INTEGER · read-only · current Value indicates which phases are connected to each outlet in this table row - single phase voltage, phase 1 to neutral, phase 2 to neutral, phase 3 to neutral, phase 1 to phase 2, phase 2 to phase 3, phase 3 to phase 1, split-phase with phases 1 and 2, split phase with phases 2 and 3, split phase with phases 3 and 1, three-phase delta, and three-phase wye.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ToutletParentTable | 1.3.6.1.4.1.534.6.6.7.6.2 | NA | |||||||||||||||||||
table · not-accessible · current A list of parents for this outlet. For example, this table will link to all of the groups that have this outlet as a child. | |||||||||||||||||||||
| RoutletParentEntry | 1.3.6.1.4.1.534.6.6.7.6.2.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry for a particular parent. | |||||||||||||||||||||
| CoutletParentIndex | 1.3.6.1.4.1.534.6.6.7.6.2.1.1 | Integer32 (1..32) | NA | ||||||||||||||||||
column · Integer32 (1..32) · not-accessible · current A unique value for each parent. Its value ranges from 1 to outletParentCount. | |||||||||||||||||||||
| CoutletParentType | 1.3.6.1.4.1.534.6.6.7.6.2.1.2 | INTEGER | RO | section(2) | |||||||||||||||||
column · INTEGER · read-only · current The type of the parent.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletParentOID | 1.3.6.1.4.1.534.6.6.7.6.2.1.3 | OBJECT IDENTIFIER | RO | 1.3.6.1.4.1.534.6.6.7.5.1.1.2.1 | |||||||||||||||||
column · OBJECT IDENTIFIER · read-only · current Object ID of a parent object. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ToutletVoltageTable | 1.3.6.1.4.1.534.6.6.7.6.3 | NA | |||||||||||||||||||
table · not-accessible · current A list of outlet voltage measurements. | |||||||||||||||||||||
| RoutletVoltageEntry | 1.3.6.1.4.1.534.6.6.7.6.3.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry for an outlet voltage measurement.
| |||||||||||||||||||||
| CoutletVoltage | 1.3.6.1.4.1.534.6.6.7.6.3.1.2 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Units are millivolts. | |||||||||||||||||||||
| CoutletVoltageThStatus | 1.3.6.1.4.1.534.6.6.7.6.3.1.3 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current Status of the measured outlet voltage relative to the configured thresholds.
| |||||||||||||||||||||
| CoutletVoltageThLowerWarning | 1.3.6.1.4.1.534.6.6.7.6.3.1.4 | Integer32 (-1..500000) | RW | ||||||||||||||||||
column · Integer32 (-1..500000) · read-write · current Lower warning threshold. Units are millivolts. A negative value indicates that this object is not available. | |||||||||||||||||||||
| CoutletVoltageThLowerCritical | 1.3.6.1.4.1.534.6.6.7.6.3.1.5 | Integer32 (-1..500000) | RW | ||||||||||||||||||
column · Integer32 (-1..500000) · read-write · current Lower critical threshold. Units are millivolts. A negative value indicates that this object is not available. | |||||||||||||||||||||
| CoutletVoltageThUpperWarning | 1.3.6.1.4.1.534.6.6.7.6.3.1.6 | Integer32 (-1..500000) | RW | ||||||||||||||||||
column · Integer32 (-1..500000) · read-write · current Upper warning threshold. Units are millivolts. A negative value indicates that this object is not available. | |||||||||||||||||||||
| CoutletVoltageThUpperCritical | 1.3.6.1.4.1.534.6.6.7.6.3.1.7 | Integer32 (-1..500000) | RW | ||||||||||||||||||
column · Integer32 (-1..500000) · read-write · current Upper critical threshold. Units are millivolts. A negative value indicates that this object is not available. | |||||||||||||||||||||
| ToutletCurrentTable | 1.3.6.1.4.1.534.6.6.7.6.4 | NA | |||||||||||||||||||
table · not-accessible · current A list of outlet current measurements. | |||||||||||||||||||||
| RoutletCurrentEntry | 1.3.6.1.4.1.534.6.6.7.6.4.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry for an outlet current measurement.
| |||||||||||||||||||||
| CoutletCurrentCapacity | 1.3.6.1.4.1.534.6.6.7.6.4.1.2 | Integer32 | RO | 16000 | |||||||||||||||||
column · Integer32 · read-only · current Rated current capacity of the outlet. Units are milliamps. A negative value indicates that the hardware current capacity is unknown. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletCurrent | 1.3.6.1.4.1.534.6.6.7.6.4.1.3 | Integer32 | RO | 790 | |||||||||||||||||
column · Integer32 · read-only · current An outlet current measurement value. Units are milliamps. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletCurrentThStatus | 1.3.6.1.4.1.534.6.6.7.6.4.1.4 | INTEGER | RO | good(0) | |||||||||||||||||
column · INTEGER · read-only · current Status of the measured outlet current relative to the configured thresholds. A negative value indicates that this object is not available.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletCurrentThLowerWarning | 1.3.6.1.4.1.534.6.6.7.6.4.1.5 | Integer32 (-1..100000) | RW | 0 | |||||||||||||||||
column · Integer32 (-1..100000) · read-write · current Lower warning threshold. Units are milliamps. A negative value indicates that this object is not available. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletCurrentThLowerCritical | 1.3.6.1.4.1.534.6.6.7.6.4.1.6 | Integer32 (-1..100000) | RW | -1 | |||||||||||||||||
column · Integer32 (-1..100000) · read-write · current Lower critical threshold. Units are milliamps. A negative value indicates that this object is not available. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletCurrentThUpperWarning | 1.3.6.1.4.1.534.6.6.7.6.4.1.7 | Integer32 (-1..100000) | RW | 12800 | |||||||||||||||||
column · Integer32 (-1..100000) · read-write · current Upper warning threshold. Units are milliamps. A negative value indicates that this object is not available. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletCurrentThUpperCritical | 1.3.6.1.4.1.534.6.6.7.6.4.1.8 | Integer32 (-1..100000) | RW | 16000 | |||||||||||||||||
column · Integer32 (-1..100000) · read-write · current Upper critical threshold. Units are milliamps. A negative value indicates that this object is not available. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletCurrentCrestFactor | 1.3.6.1.4.1.534.6.6.7.6.4.1.9 | Integer32 | RO | 2812 | |||||||||||||||||
column · Integer32 · read-only · current Current crest factor. Units are in milli, for example a crest factor of
1.414 will be returned as 1414. A negative value indicates
that this object is not available.Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletCurrentPercentLoad | 1.3.6.1.4.1.534.6.6.7.6.4.1.10 | Integer32 | RO | -1 | |||||||||||||||||
column · Integer32 · read-only · current Current percent load, based on the rated current capacity. Units are percentage, for example 80% will be returned as 80. A negative value indicates that this object is not available. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ToutletPowerTable | 1.3.6.1.4.1.534.6.6.7.6.5 | NA | |||||||||||||||||||
table · not-accessible · current A list of outlet power measurements. | |||||||||||||||||||||
| RoutletPowerEntry | 1.3.6.1.4.1.534.6.6.7.6.5.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry for an outlet power measurement.
| |||||||||||||||||||||
| CoutletVA | 1.3.6.1.4.1.534.6.6.7.6.5.1.2 | Integer32 | RO | 93 | |||||||||||||||||
column · Integer32 · read-only · current An outlet VA value. Units are VA. A negative value indicates that this object is not available. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletWatts | 1.3.6.1.4.1.534.6.6.7.6.5.1.3 | Integer32 | RO | 80 | |||||||||||||||||
column · Integer32 · read-only · current An outlet Watts value. Units are Watts. A negative value indicates that this object is not available. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletWh | 1.3.6.1.4.1.534.6.6.7.6.5.1.4 | Unsigned32 (0..4294967295) | RW | 785621 | |||||||||||||||||
column · Unsigned32 (0..4294967295) · read-write · current Units are Watt-hours. This object is writable so that it can be reset to 0. When it is written to, the inputWhTotalTimer will be reset to 0 as well. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletWhTimer | 1.3.6.1.4.1.534.6.6.7.6.5.1.5 | UnixTimeStamp | RO | 1700853056 | |||||||||||||||||
column · UnixTimeStamp · read-only · current Timestamp of when outlet Watt-hours (outletWh) was last reset. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletPowerFactor | 1.3.6.1.4.1.534.6.6.7.6.5.1.6 | Integer32 | RO | -842 | |||||||||||||||||
column · Integer32 · read-only · current An outlet PF value. Units are in thousandths, for example a power factor
of 0.958 would be returned as 958, and 0.92 would be returned
as 920. A negative value indicates that this object is not available.Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletVAR | 1.3.6.1.4.1.534.6.6.7.6.5.1.7 | Integer32 | RO | -49 | |||||||||||||||||
column · Integer32 · read-only · current An outlet VAR value. Units are VAR. A negative value indicates that this object is not available. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ToutletControlTable | 1.3.6.1.4.1.534.6.6.7.6.6 | NA | |||||||||||||||||||
table · not-accessible · current A list of controllable outlets. | |||||||||||||||||||||
| RoutletControlEntry | 1.3.6.1.4.1.534.6.6.7.6.6.1 | NA | |||||||||||||||||||
| CoutletControlStatus | 1.3.6.1.4.1.534.6.6.7.6.6.1.2 | INTEGER | RO | on(1) | |||||||||||||||||
column · INTEGER · read-only · current Current state of a controlled outlet.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletControlOffCmd | 1.3.6.1.4.1.534.6.6.7.6.6.1.3 | Integer32 (-1..99999) | RW | -1 | |||||||||||||||||
column · Integer32 (-1..99999) · read-write · current Outlet control command.
Once the command is issued, the outlet will turn Off immediately.
0-n : Time in seconds until the outlet command is issued
-1 : Cancel a pending outlet Off command
When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command.
Certain ePDUs (mainly those with part numbers beginning with IPV or IPC) do not support delayed control
commands. These will respond with an error if a command value of > 0 is written to this object.Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletControlOnCmd | 1.3.6.1.4.1.534.6.6.7.6.6.1.4 | Integer32 (-1..99999) | RW | -1 | |||||||||||||||||
column · Integer32 (-1..99999) · read-write · current Outlet control command.
Once the command is issued, the outlet will turn On immediately.
0-n : Time in seconds until the outlet command is issued
-1 : Cancel a pending outlet On command
When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command.
Certain ePDUs (mainly those with part numbers beginning with IPV or IPC) do not support delayed control
commands. These will respond with an error if a command value of > 0 is written to this object.Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletControlRebootCmd | 1.3.6.1.4.1.534.6.6.7.6.6.1.5 | Integer32 (-1..99999) | RW | -1 | |||||||||||||||||
column · Integer32 (-1..99999) · read-write · current Outlet control command.
For outlets that are On prior to this Reboot command, they will switch Off immediately when the command is
issued, remain Off for outletControlRebootOffTime seconds, and then turn back On.
For outlets that are Off prior to the Reboot command, they will turn On after a delay of outletControlRebootOffTime
seconds from when the command is issued.
0-n : Time in seconds until the Reboot command is issued
-1 : Cancel a pending outlet Reboot command
When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command.
Certain ePDUs (mainly those with part numbers beginning with IPV or IPC) do not support delayed control
commands. These will respond with an error if a command value of > 0 is written to this object.Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletControlPowerOnState | 1.3.6.1.4.1.534.6.6.7.6.6.1.6 | INTEGER | RW | on(1) | |||||||||||||||||
column · INTEGER · read-write · current Determines the outlet state when power is applied to the unit. 0 : not restart at device startup 1 : should sequence back ON in line with outletControlSequenceTime 2 : should take the state the outlet had when power was lost. If the state was ON, should sequence back ON in line with outletControlSequenceTime.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletControlSequenceDelay | 1.3.6.1.4.1.534.6.6.7.6.6.1.7 | Integer32 (-1..99999) | RW | 1 | |||||||||||||||||
column · Integer32 (-1..99999) · read-write · current Time delay in seconds from when a Global Sequence On command is issued to when the command is executed on this outlet. This delay is also used as a power-on delay. Set to -1 to exclude this outlet from Global Sequence On commands. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletControlRebootOffTime | 1.3.6.1.4.1.534.6.6.7.6.6.1.8 | Integer32 (1..99999) | RW | 10 | |||||||||||||||||
column · Integer32 (1..99999) · read-write · current Time delay in seconds that the outlet should remain in the Off state when executing a Reboot command. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletControlSwitchable | 1.3.6.1.4.1.534.6.6.7.6.6.1.9 | INTEGER | RW | switchable(1) | |||||||||||||||||
column · INTEGER · read-write · current Determines the outlet capability to be controlled On/Off from the communication channels. 1 : control On/Off enabled 2 : control On/Off disabled.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CoutletControlShutoffDelay | 1.3.6.1.4.1.534.6.6.7.6.6.1.10 | Integer32 (-1..99999) | RW | 120 | |||||||||||||||||
column · Integer32 (-1..99999) · read-write · current Time delay in seconds that could be taken in account before shutting of the outlet. An application which need to shutoff properly an outlet will read this parameter first then write it to the command outletControlOffCmd. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ToutletGlobalTable | 1.3.6.1.4.1.534.6.6.7.6.7 | NA | |||||||||||||||||||
table · not-accessible · current A list of globlal configuration on all outlets. | |||||||||||||||||||||
| RoutletGlobalEntry | 1.3.6.1.4.1.534.6.6.7.6.7.1 | NA | |||||||||||||||||||
| CoutletAutomaticShutoff | 1.3.6.1.4.1.534.6.6.7.6.7.1.2 | INTEGER | RW | notApplicable(0) | |||||||||||||||||
column · INTEGER · read-write · current Determines the state of all outlets when the unit is power off: 0 : not applicable (read only) 1 : Keep the outlet relays in the current position when the PDU is powered down 2 : Makes the outlet relays go to the position that shutoffs the outlets when the PDU is powered down
Example values from LibreNMS test devices
| |||||||||||||||||||||
| Nenvironmental | 1.3.6.1.4.1.534.6.6.7.7 | ||||||||||||||||||||
| TtemperatureTable | 1.3.6.1.4.1.534.6.6.7.7.1 | NA | |||||||||||||||||||
table · not-accessible · current A list of temperature probe measurements. The number of entries is given by temperatureCount. | |||||||||||||||||||||
| RtemperatureEntry | 1.3.6.1.4.1.534.6.6.7.7.1.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry for a temperature measurement. | |||||||||||||||||||||
| CtemperatureIndex | 1.3.6.1.4.1.534.6.6.7.7.1.1.1 | Integer32 (1..2) | AN | ||||||||||||||||||
column · Integer32 (1..2) · accessible-for-notify · current A unique value for each temperature probe measurement. Its value ranges from 1 to temperatureCount. | |||||||||||||||||||||
| CtemperatureName | 1.3.6.1.4.1.534.6.6.7.7.1.1.2 | OCTET STRING (SIZE (1..31)) | RW | Rack inlet | |||||||||||||||||
column · OCTET STRING (SIZE (1..31)) · read-write · current A descriptive name for the temperature probe. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtemperatureProbeStatus | 1.3.6.1.4.1.534.6.6.7.7.1.1.3 | INTEGER | RO | connected(1) | |||||||||||||||||
column · INTEGER · read-only · current Indicates whether a probe is connected or not.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtemperatureValue | 1.3.6.1.4.1.534.6.6.7.7.1.1.4 | Integer32 | RO | 215 | |||||||||||||||||
column · Integer32 · read-only · current Units are in tenths of a degree according to the scale specified by temperatureScale (either Fahrenheit or Celsius). Divide by ten to get degrees. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CtemperatureThStatus | 1.3.6.1.4.1.534.6.6.7.7.1.1.5 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current Status of the measured temperature relative to the configured thresholds.
| |||||||||||||||||||||
| CtemperatureThLowerWarning | 1.3.6.1.4.1.534.6.6.7.7.1.1.6 | Integer32 (-1..150000) | RW | ||||||||||||||||||
column · Integer32 (-1..150000) · read-write · current Lower warning threshold. Units are tenths of a degree. A negative value indicates that this object is not available. | |||||||||||||||||||||
| CtemperatureThLowerCritical | 1.3.6.1.4.1.534.6.6.7.7.1.1.7 | Integer32 (-1..150000) | RW | ||||||||||||||||||
column · Integer32 (-1..150000) · read-write · current Lower critical threshold. Units are tenths of a degree. A negative value indicates that this object is not available. | |||||||||||||||||||||
| CtemperatureThUpperWarning | 1.3.6.1.4.1.534.6.6.7.7.1.1.8 | Integer32 (-1..150000) | RW | ||||||||||||||||||
column · Integer32 (-1..150000) · read-write · current Upper warning threshold. Units are tenths of a degree. A negative value indicates that this object is not available. | |||||||||||||||||||||
| CtemperatureThUpperCritical | 1.3.6.1.4.1.534.6.6.7.7.1.1.9 | Integer32 (-1..150000) | RW | ||||||||||||||||||
column · Integer32 (-1..150000) · read-write · current Upper critical threshold. Units are tenths of a degree. A negative value indicates that this object is not available. | |||||||||||||||||||||
| ThumidityTable | 1.3.6.1.4.1.534.6.6.7.7.2 | NA | |||||||||||||||||||
table · not-accessible · current A list of humidity probe measurements. The number of entries is given by humidityCount. | |||||||||||||||||||||
| RhumidityEntry | 1.3.6.1.4.1.534.6.6.7.7.2.1 | NA | |||||||||||||||||||
row · not-accessible · current An entry for a humidity measurement.
| |||||||||||||||||||||
| ChumidityIndex | 1.3.6.1.4.1.534.6.6.7.7.2.1.1 | Integer32 (1..2) | AN | ||||||||||||||||||
column · Integer32 (1..2) · accessible-for-notify · current A unique value for each humidity probe measurement. Its value ranges from 1 to humidityCount. | |||||||||||||||||||||
| ChumidityName | 1.3.6.1.4.1.534.6.6.7.7.2.1.2 | OCTET STRING (SIZE (1..31)) | RW | | |||||||||||||||||
column · OCTET STRING (SIZE (1..31)) · read-write · current A descriptive name for the humidity probe. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChumidityProbeStatus | 1.3.6.1.4.1.534.6.6.7.7.2.1.3 | INTEGER | RO | disconnected(0) | |||||||||||||||||
column · INTEGER · read-only · current Indicates whether a probe is connected or not.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChumidityValue | 1.3.6.1.4.1.534.6.6.7.7.2.1.4 | Integer32 | RO | 0 | |||||||||||||||||
column · Integer32 · read-only · current Units are tenths of a percent relative humidity. Divide the value by 10 to get %RH. Example values from LibreNMS test devices
| |||||||||||||||||||||
| ChumidityThStatus | 1.3.6.1.4.1.534.6.6.7.7.2.1.5 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current Status of the measured humidity relative to the configured thresholds.
| |||||||||||||||||||||
| ChumidityThLowerWarning | 1.3.6.1.4.1.534.6.6.7.7.2.1.6 | Integer32 (-1..1000) | RW | ||||||||||||||||||
column · Integer32 (-1..1000) · read-write · current Lower warning threshold. Units are 0.1 %RH. A negative value indicates that this object is not available. | |||||||||||||||||||||
| ChumidityThLowerCritical | 1.3.6.1.4.1.534.6.6.7.7.2.1.7 | Integer32 (-1..1000) | RW | ||||||||||||||||||
column · Integer32 (-1..1000) · read-write · current Lower critical threshold. Units are 0.1 %RH. A negative value indicates that this object is not available. | |||||||||||||||||||||
| ChumidityThUpperWarning | 1.3.6.1.4.1.534.6.6.7.7.2.1.8 | Integer32 (-1..1000) | RW | ||||||||||||||||||
column · Integer32 (-1..1000) · read-write · current Upper warning threshold. Units are 0.1 %RH. A negative value indicates that this object is not available. | |||||||||||||||||||||
| ChumidityThUpperCritical | 1.3.6.1.4.1.534.6.6.7.7.2.1.9 | Integer32 (-1..1000) | RW | ||||||||||||||||||
column · Integer32 (-1..1000) · read-write · current Upper critical threshold. Units are 0.1 %RH. A negative value indicates that this object is not available. | |||||||||||||||||||||
| TcontactTable | 1.3.6.1.4.1.534.6.6.7.7.3 | NA | |||||||||||||||||||
table · not-accessible · current A list of contact sensors. The number of entries is given by contactCount. | |||||||||||||||||||||
| RcontactEntry | 1.3.6.1.4.1.534.6.6.7.7.3.1 | NA | |||||||||||||||||||
| CcontactIndex | 1.3.6.1.4.1.534.6.6.7.7.3.1.1 | Integer32 (1..3) | AN | ||||||||||||||||||
column · Integer32 (1..3) · accessible-for-notify · current A unique value for each contact sensor. Its value ranges from 1 to contactCount. | |||||||||||||||||||||
| CcontactName | 1.3.6.1.4.1.534.6.6.7.7.3.1.2 | OCTET STRING (SIZE (1..31)) | RW | ||||||||||||||||||
column · OCTET STRING (SIZE (1..31)) · read-write · current A descriptive name for the contact sensor. | |||||||||||||||||||||
| CcontactProbeStatus | 1.3.6.1.4.1.534.6.6.7.7.3.1.3 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current Indicates whether a probe is connected or not. Will not be returned if the contact sensor is internal to the ePDU, in that case only contactState should be read.
| |||||||||||||||||||||
| CcontactState | 1.3.6.1.4.1.534.6.6.7.7.3.1.4 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current The state of the contact sensor.
| |||||||||||||||||||||
| Nconformance | 1.3.6.1.4.1.534.6.6.7.25 | ||||||||||||||||||||
| MeatonEpduCompliances | 1.3.6.1.4.1.534.6.6.7.25.1 | ||||||||||||||||||||
compliance · current The requirements for conforming to the ePDU MIB. | |||||||||||||||||||||
| NobjectGroups | 1.3.6.1.4.1.534.6.6.7.25.5 | ||||||||||||||||||||
| GepduRequiredGroup | 1.3.6.1.4.1.534.6.6.7.25.5.1 | ||||||||||||||||||||
| GepduOptionalGroup | 1.3.6.1.4.1.534.6.6.7.25.5.2 | ||||||||||||||||||||
group · current Most objects in this MIB are optional.
| |||||||||||||||||||||
| GepduNotifyGroup | 1.3.6.1.4.1.534.6.6.7.25.5.3 | ||||||||||||||||||||
group · current These notifications will be supported depending on the features of the ePDU. Check the web interface for options to turn these notifications on/off. If an option is not listed, then the ePDU likely does not support that notification.
| |||||||||||||||||||||
Textual conventions
UnixTimeStampCounter32Unix time stamp. Measured in seconds since January 1, 1970.
Traps / Notifications
- notifyBootUp
1.3.6.1.4.1.534.6.6.7.0.4 - notifyCommunicationStatus
1.3.6.1.4.1.534.6.6.7.0.51 - notifyContactState
1.3.6.1.4.1.534.6.6.7.0.43 - notifyFailedLogin
1.3.6.1.4.1.534.6.6.7.0.3 - notifyGroupBreakerStatus
1.3.6.1.4.1.534.6.6.7.0.23 - notifyGroupCurrentThStatus
1.3.6.1.4.1.534.6.6.7.0.22 - notifyGroupVoltageThStatus
1.3.6.1.4.1.534.6.6.7.0.21 - notifyHumidityThStatus
1.3.6.1.4.1.534.6.6.7.0.42 - notifyInputCurrentThStatus
1.3.6.1.4.1.534.6.6.7.0.12 - notifyInputFrequencyStatus
1.3.6.1.4.1.534.6.6.7.0.13 - notifyInputVoltageThStatus
1.3.6.1.4.1.534.6.6.7.0.11 - notifyInternalStatus
1.3.6.1.4.1.534.6.6.7.0.52 - notifyOutletControlStatus
1.3.6.1.4.1.534.6.6.7.0.33 - notifyOutletCurrentThStatus
1.3.6.1.4.1.534.6.6.7.0.32 - notifyOutletVoltageThStatus
1.3.6.1.4.1.534.6.6.7.0.31 - notifyProbeStatus
1.3.6.1.4.1.534.6.6.7.0.44 - notifyStrappingStatus
1.3.6.1.4.1.534.6.6.7.0.54 - notifyTemperatureThStatus
1.3.6.1.4.1.534.6.6.7.0.41 - notifyTest
1.3.6.1.4.1.534.6.6.7.0.53 - notifyUserLogin
1.3.6.1.4.1.534.6.6.7.0.1 - notifyUserLogout
1.3.6.1.4.1.534.6.6.7.0.2