DeltaUPS-MIB
Delta Electronics, Inc.snmptranslate -m DeltaUPS-MIB -Tpsnmpwalk -v2c -c <community> -m DeltaUPS-MIB <host> 1.3.6.1.4.1.2254Imports
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
|---|---|
| SNMPv2-SMI | Bits, Integer32, IpAddress, MODULE-IDENTITY, MibIdentifier, OBJECT-IDENTITY, OBJECT-TYPE, TRAP-TYPE, TimeTicks, Unsigned32, enterprises, iso |
| SNMPv2-TC | DisplayString, PhysAddress, TEXTUAL-CONVENTION |
OID tree
| Name | OID | Type | Access | Status | Example | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Ndelta | 1.3.6.1.4.1.2254 | ||||||||||||||||
| Nups | 1.3.6.1.4.1.2254.2 | ||||||||||||||||
| Nupsv4 | 1.3.6.1.4.1.2254.2.4 | ||||||||||||||||
| NdupsIdent | 1.3.6.1.4.1.2254.2.4.1 | ||||||||||||||||
| SdupsIdentManufacturer | 1.3.6.1.4.1.2254.2.4.1.1 | DisplayString (SIZE (0..20)) | RO | mandatory | Minuteman | ||||||||||||
scalar · DisplayString (SIZE (0..20)) · read-only · mandatory The name of the UPS manufacturer. Example values from LibreNMS test devices
| |||||||||||||||||
| SdupsIdentModel | 1.3.6.1.4.1.2254.2.4.1.2 | DisplayString (SIZE (0..31)) | RO | mandatory | E1500RTXL2U | ||||||||||||
scalar · DisplayString (SIZE (0..31)) · read-only · mandatory The UPS Model designation. Example values from LibreNMS test devices
| |||||||||||||||||
| SdupsIdentUPSSoftwareVersion | 1.3.6.1.4.1.2254.2.4.1.3 | DisplayString (SIZE (0..15)) | RO | mandatory | 03 | ||||||||||||
scalar · DisplayString (SIZE (0..15)) · read-only · mandatory The UPS firmware/software version(s). This variable may or may not has the same value as upsIdentAgentSoftwareVersion in some implementations. Example values from LibreNMS test devices
| |||||||||||||||||
| SdupsIdentAgentSoftwareVersion | 1.3.6.1.4.1.2254.2.4.1.4 | DisplayString (SIZE (0..15)) | RO | mandatory | |||||||||||||
scalar · DisplayString (SIZE (0..15)) · read-only · mandatory The UPS agent software version. This variable may or may not has the same value as upsIdentUPSSoftwareVersion in some implementations. | |||||||||||||||||
| SdupsIdentName | 1.3.6.1.4.1.2254.2.4.1.5 | DisplayString (SIZE (0..63)) | RW | mandatory | |||||||||||||
scalar · DisplayString (SIZE (0..63)) · read-write · mandatory A string identifying the UPS. This object should be set by the administrator. | |||||||||||||||||
| SdupsAttachedDevices | 1.3.6.1.4.1.2254.2.4.1.6 | DisplayString (SIZE (0..63)) | RW | mandatory | |||||||||||||
scalar · DisplayString (SIZE (0..63)) · read-write · mandatory A string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator. | |||||||||||||||||
| SdupsRatingOutputVA | 1.3.6.1.4.1.2254.2.4.1.7 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The magnitude of the nominal output VA rating. | |||||||||||||||||
| SdupsRatingOutputVoltage | 1.3.6.1.4.1.2254.2.4.1.8 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The magnitude of the nominal output voltage rating. | |||||||||||||||||
| SdupsRatingOutputFrequency | 1.3.6.1.4.1.2254.2.4.1.9 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The magnitude of the nominal output frequency rating. | |||||||||||||||||
| SdupsRatingInputVoltage | 1.3.6.1.4.1.2254.2.4.1.10 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The magnitude of the nominal input voltage rating. | |||||||||||||||||
| SdupsRatingInputFrequency | 1.3.6.1.4.1.2254.2.4.1.11 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The magnitude of the nominal input frequency rating. | |||||||||||||||||
| SdupsRatingBatteryVoltage | 1.3.6.1.4.1.2254.2.4.1.12 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The magnitude of the nominal battery voltage rating. | |||||||||||||||||
| SdupsLowTransferVoltUpBound | 1.3.6.1.4.1.2254.2.4.1.13 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The minimum input line voltage upper bound allowed before the UPS system transfers to battery backup.
| |||||||||||||||||
| SdupsLowTransferVoltLowBound | 1.3.6.1.4.1.2254.2.4.1.14 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The minimum input line voltage lower bound allowed before the UPS system transfers to battery backup.
| |||||||||||||||||
| SdupsHighTransferVoltUpBound | 1.3.6.1.4.1.2254.2.4.1.15 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The maximum input line voltage upper bound allowed before the UPS system transfers to battery backup.
| |||||||||||||||||
| SdupsHighTransferVoltLowBound | 1.3.6.1.4.1.2254.2.4.1.16 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The maximum input line voltage lower bound allowed before the UPS system transfers to battery backup.
| |||||||||||||||||
| SdupsLowBattTime | 1.3.6.1.4.1.2254.2.4.1.17 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Minutes, time from low battery to low battery shutdown. | |||||||||||||||||
| SdupsOutletRelays | 1.3.6.1.4.1.2254.2.4.1.18 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Number of outlet relay. If it is 0, the function is not available for the UPS. | |||||||||||||||||
| SdupsType | 1.3.6.1.4.1.2254.2.4.1.19 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Indicate the UPS type.
| |||||||||||||||||
| NdupsControl | 1.3.6.1.4.1.2254.2.4.2 | ||||||||||||||||
| SdupsShutdownType | 1.3.6.1.4.1.2254.2.4.2.1 | INTEGER | RW | mandatory | |||||||||||||
scalar · INTEGER · read-write · mandatory This object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRebootWithDuration objects reaches zero. Setting this object to output(1) indicates that shutdown requests should cause only the output of the UPS to turn off. Setting this object to system(2) indicates that shutdown requests will cause the entire UPS system to turn off.
| |||||||||||||||||
| SdupsAutoReboot | 1.3.6.1.4.1.2254.2.4.2.2 | INTEGER | RW | mandatory | |||||||||||||
scalar · INTEGER · read-write · mandatory In backup mode, the UPS may shutdown normally by SDA command, dry-contact remote shutdown signal or low battery shutdown. This command is used to determine the unit should restart or not next time when the power restores
| |||||||||||||||||
| SdupsShutdownAction | 1.3.6.1.4.1.2254.2.4.2.3 | INTEGER | RW | mandatory | |||||||||||||
scalar · INTEGER · read-write · mandatory If the value is greater than 0 the UPS performs shutdown action that defined by ShutdownType after the seconds. 0, aborted. | |||||||||||||||||
| SdupsRestartAction | 1.3.6.1.4.1.2254.2.4.2.4 | INTEGER | RW | mandatory | |||||||||||||
scalar · INTEGER · read-write · mandatory UPS will restart after the indicated number of minutes. -1, aborted. | |||||||||||||||||
| SdupsSetOutletRelay | 1.3.6.1.4.1.2254.2.4.2.5 | INTEGER | RW | mandatory | |||||||||||||
scalar · INTEGER · read-write · mandatory Indicate which outlet relay, from 1,2,3... . | |||||||||||||||||
| SdupsRelayOffDelay | 1.3.6.1.4.1.2254.2.4.2.6 | INTEGER | RW | mandatory | |||||||||||||
scalar · INTEGER · read-write · mandatory Turn the relay off after the seconds. The relay was indicated by SetOutletRelay. | |||||||||||||||||
| SdupsRelayOnDelay | 1.3.6.1.4.1.2254.2.4.2.7 | INTEGER | RW | mandatory | |||||||||||||
scalar · INTEGER · read-write · mandatory Turn the relay on after the seconds. The relay was indicated by SetOutletRelay. | |||||||||||||||||
| NdupsConfig | 1.3.6.1.4.1.2254.2.4.3 | ||||||||||||||||
| SdupsConfigBuzzerAlarm | 1.3.6.1.4.1.2254.2.4.3.1 | INTEGER | RW | mandatory | |||||||||||||
scalar · INTEGER · read-write · mandatory UPS will keep silence but will alarm again when next power event is occurred
| |||||||||||||||||
| SdupsConfigBuzzerState | 1.3.6.1.4.1.2254.2.4.3.2 | INTEGER | RW | mandatory | |||||||||||||
scalar · INTEGER · read-write · mandatory If it is disabled then the UPS is always muted.
| |||||||||||||||||
| SdupsConfigSensitivity | 1.3.6.1.4.1.2254.2.4.3.3 | INTEGER | RW | mandatory | |||||||||||||
scalar · INTEGER · read-write · mandatory The seneitivity of the UPS to utility line abnormalities or noises.
| |||||||||||||||||
| SdupsConfigLowVoltageTransferPoint | 1.3.6.1.4.1.2254.2.4.3.4 | INTEGER | RW | mandatory | |||||||||||||
scalar · INTEGER · read-write · mandatory The minimum input line voltage allowed before the UPS system transfers to battery backup.
| |||||||||||||||||
| SdupsConfigHighVoltageTransferPoint | 1.3.6.1.4.1.2254.2.4.3.5 | INTEGER | RW | mandatory | |||||||||||||
scalar · INTEGER · read-write · mandatory The maximum line voltage allowed before the UPS system transfers to battery backup.
| |||||||||||||||||
| SdupsConfigShutdownOSDelay | 1.3.6.1.4.1.2254.2.4.3.6 | INTEGER | RW | mandatory | |||||||||||||
scalar · INTEGER · read-write · mandatory The operating system shutdown delay time when the input power fail. -1 will disable this option.
| |||||||||||||||||
| SdupsConfigUPSBootDelay | 1.3.6.1.4.1.2254.2.4.3.7 | INTEGER | RW | mandatory | |||||||||||||
scalar · INTEGER · read-write · mandatory Delay the UPS startup after power restores. The power quality may not stable when power restores, this feature let the UPS wait a period of time to startup the system.
| |||||||||||||||||
| SdupsConfigExternalBatteryPack | 1.3.6.1.4.1.2254.2.4.3.8 | INTEGER | RW | mandatory | |||||||||||||
scalar · INTEGER · read-write · mandatory Indicate the number of external battery pack. | |||||||||||||||||
| NdupsInput | 1.3.6.1.4.1.2254.2.4.4 | ||||||||||||||||
| SdupsInputNumLines | 1.3.6.1.4.1.2254.2.4.4.1 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The number of input lines utilized in this device. | |||||||||||||||||
| SdupsInputFrequency1 | 1.3.6.1.4.1.2254.2.4.4.2 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The current input line 1 frequency to the UPS system in 1/10 Hz. | |||||||||||||||||
| SdupsInputVoltage1 | 1.3.6.1.4.1.2254.2.4.4.3 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The Input line 1 voltage of the UPS system in 1/10 V. | |||||||||||||||||
| SdupsInputCurrent1 | 1.3.6.1.4.1.2254.2.4.4.4 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The Input line 1 current to the UPS system in 1/10 A. | |||||||||||||||||
| SdupsInputFrequency2 | 1.3.6.1.4.1.2254.2.4.4.5 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The current input line 2 frequency to the UPS system in 1/10 Hz. | |||||||||||||||||
| SdupsInputVoltage2 | 1.3.6.1.4.1.2254.2.4.4.6 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The Input line 2 voltage of the UPS system in 1/10 V. | |||||||||||||||||
| SdupsInputCurrent2 | 1.3.6.1.4.1.2254.2.4.4.7 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The Input line 2 current to the UPS system in 1/10 A. | |||||||||||||||||
| SdupsInputFrequency3 | 1.3.6.1.4.1.2254.2.4.4.8 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The current input line 3 frequency to the UPS system in 1/10 Hz. | |||||||||||||||||
| SdupsInputVoltage3 | 1.3.6.1.4.1.2254.2.4.4.9 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The Input line 3 voltage of the UPS system in 1/10 V. | |||||||||||||||||
| SdupsInputCurrent3 | 1.3.6.1.4.1.2254.2.4.4.10 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The Input line 3 current to the UPS system in 1/10 A. | |||||||||||||||||
| NdupsOutput | 1.3.6.1.4.1.2254.2.4.5 | ||||||||||||||||
| SdupsOutputSource | 1.3.6.1.4.1.2254.2.4.5.1 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The present source of output power. The enumeration none(7) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker.
| |||||||||||||||||
| SdupsOutputFrequency | 1.3.6.1.4.1.2254.2.4.5.2 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The present output frequency in 1/10 Hz.
| |||||||||||||||||
| SdupsOutputNumLines | 1.3.6.1.4.1.2254.2.4.5.3 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The number of output lines utilized in this device. | |||||||||||||||||
| SdupsOutputVoltage1 | 1.3.6.1.4.1.2254.2.4.5.4 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The Output line 1 voltage of the UPS system in 1/10 V. | |||||||||||||||||
| SdupsOutputCurrent1 | 1.3.6.1.4.1.2254.2.4.5.5 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The Output line 1 current of the UPS system in 1/10 A. | |||||||||||||||||
| SdupsOutputPower1 | 1.3.6.1.4.1.2254.2.4.5.6 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The Output line 1 real power of the UPS system in watts. | |||||||||||||||||
| SdupsOutputLoad1 | 1.3.6.1.4.1.2254.2.4.5.7 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The current UPS output line 1 load expressed in percent of rated capacity. | |||||||||||||||||
| SdupsOutputVoltage2 | 1.3.6.1.4.1.2254.2.4.5.8 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The Output line 2 voltage of the UPS system in 1/10 V. | |||||||||||||||||
| SdupsOutputCurrent2 | 1.3.6.1.4.1.2254.2.4.5.9 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The Output line 2 current of the UPS system in 1/10 A. | |||||||||||||||||
| SdupsOutputPower2 | 1.3.6.1.4.1.2254.2.4.5.10 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The Output line 2 real power of the UPS system in watts. | |||||||||||||||||
| SdupsOutputLoad2 | 1.3.6.1.4.1.2254.2.4.5.11 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The current UPS output line 2 load expressed in percent of rated capacity. | |||||||||||||||||
| SdupsOutputVoltage3 | 1.3.6.1.4.1.2254.2.4.5.12 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The Output line 3 voltage of the UPS system in 1/10 V. | |||||||||||||||||
| SdupsOutputCurrent3 | 1.3.6.1.4.1.2254.2.4.5.13 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The Output line 3 current of the UPS system in 1/10 A. | |||||||||||||||||
| SdupsOutputPower3 | 1.3.6.1.4.1.2254.2.4.5.14 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The Output line 3 real power of the UPS system in watts. | |||||||||||||||||
| SdupsOutputLoad3 | 1.3.6.1.4.1.2254.2.4.5.15 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The current UPS output line 3 load expressed in percent of rated capacity. | |||||||||||||||||
| NdupsBypass | 1.3.6.1.4.1.2254.2.4.6 | ||||||||||||||||
| SdupsBypassFrequency | 1.3.6.1.4.1.2254.2.4.6.1 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The present bypass frequency in 1/10 Hz.
| |||||||||||||||||
| SdupsBypassNumLines | 1.3.6.1.4.1.2254.2.4.6.2 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The number of bypass lines utilized in this device. | |||||||||||||||||
| SdupsBypassVoltage1 | 1.3.6.1.4.1.2254.2.4.6.3 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The bypass line 1 voltage of the UPS system in 1/10 V. | |||||||||||||||||
| SdupsBypassCurrent1 | 1.3.6.1.4.1.2254.2.4.6.4 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The bypass line 1 current of the UPS system in 1/10 A. | |||||||||||||||||
| SdupsBypassPower1 | 1.3.6.1.4.1.2254.2.4.6.5 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The bypass line 1 real power of the UPS system in watts. | |||||||||||||||||
| SdupsBypassVoltage2 | 1.3.6.1.4.1.2254.2.4.6.6 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The bypass line 2 voltage of the UPS system in 1/10 V. | |||||||||||||||||
| SdupsBypassCurrent2 | 1.3.6.1.4.1.2254.2.4.6.7 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The bypass line 2 current of the UPS system in 1/10 A. | |||||||||||||||||
| SdupsBypassPower2 | 1.3.6.1.4.1.2254.2.4.6.8 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The bypass line 2 real power of the UPS system in watts. | |||||||||||||||||
| SdupsBypassVoltage3 | 1.3.6.1.4.1.2254.2.4.6.9 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The bypass line 3 voltage of the UPS system in 1/10 V. | |||||||||||||||||
| SdupsBypassCurrent3 | 1.3.6.1.4.1.2254.2.4.6.10 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The bypass line 3 current of the UPS system in 1/10 A. | |||||||||||||||||
| SdupsBypassPower3 | 1.3.6.1.4.1.2254.2.4.6.11 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The bypass line 3 real power of the UPS system in watts. | |||||||||||||||||
| NdupsBattery | 1.3.6.1.4.1.2254.2.4.7 | ||||||||||||||||
| SdupsBatteryCondiction | 1.3.6.1.4.1.2254.2.4.7.1 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The indication of the capacity remaining in the UPS system's batteries when AC normal.
| |||||||||||||||||
| SdupsBatteryStatus | 1.3.6.1.4.1.2254.2.4.7.2 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The indication of the capacity remaining in the UPS system's batteries when AC failed. A value of ok indicates that the remaining run-time is greater than upsConfigLowBattTime. A value of low indicates that the remaining battery run-time is less than or equal to upsConfigLowBattTime. A value of depleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output).
| |||||||||||||||||
| SdupsBatteryCharge | 1.3.6.1.4.1.2254.2.4.7.3 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory
| |||||||||||||||||
| SdupsSecondsOnBattery | 1.3.6.1.4.1.2254.2.4.7.4 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power.
| |||||||||||||||||
| SdupsBatteryEstimatedTime | 1.3.6.1.4.1.2254.2.4.7.5 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Estimated time from backup to low battery shutdown.
| |||||||||||||||||
| SdupsBatteryVoltage | 1.3.6.1.4.1.2254.2.4.7.6 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The magnitude of the present battery voltage in 1/10 V.
| |||||||||||||||||
| SdupsBatteryCurrent | 1.3.6.1.4.1.2254.2.4.7.7 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The present battery current in 1/10 A.
| |||||||||||||||||
| SdupsBatteryCapacity | 1.3.6.1.4.1.2254.2.4.7.8 | INTEGER (0..100) | RO | mandatory | |||||||||||||
scalar · INTEGER (0..100) · read-only · mandatory An estimate of the battery charge remaining expressed as a percent of full charge.
| |||||||||||||||||
| SdupsTemperature | 1.3.6.1.4.1.2254.2.4.7.9 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The ambient temperature at or near the UPS Battery casing.
| |||||||||||||||||
| SdupsLastReplaceDate | 1.3.6.1.4.1.2254.2.4.7.10 | DisplayString (SIZE (0..8)) | RO | mandatory | |||||||||||||
scalar · DisplayString (SIZE (0..8)) · read-only · mandatory The last battery replacement date. The format is YYYYMMDD. | |||||||||||||||||
| SdupsNextReplaceDate | 1.3.6.1.4.1.2254.2.4.7.11 | DisplayString (SIZE (0..8)) | RO | mandatory | |||||||||||||
scalar · DisplayString (SIZE (0..8)) · read-only · mandatory The next battery replacement date. The format is YYYYMMDD. | |||||||||||||||||
| NdupsTest | 1.3.6.1.4.1.2254.2.4.8 | ||||||||||||||||
| SdupsTestType | 1.3.6.1.4.1.2254.2.4.8.1 | INTEGER | RW | mandatory | |||||||||||||
scalar · INTEGER · read-write · mandatory Perform the UPS Test procedure.
| |||||||||||||||||
| SdupsTestResultsSummary | 1.3.6.1.4.1.2254.2.4.8.2 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The results of the current or last UPS diagnostics test performed. The values for donePass(1), generalTestFail(3), and batteryTestFail(4) indicate that the test completed either successfully, with a warning, or with an error, respectively.Tests which have not yet concluded are indicated by inProgress(2). The value noTestsInitiated(0) indicates that no previous test results are available.
| |||||||||||||||||
| SdupsTestResultsDetail | 1.3.6.1.4.1.2254.2.4.8.3 | DisplayString (SIZE (0..255)) | RO | mandatory | |||||||||||||
scalar · DisplayString (SIZE (0..255)) · read-only · mandatory Additional information about upsTestResultsSummary. If no additional information available, a zero length string is returned. | |||||||||||||||||
| NdupsAlarm | 1.3.6.1.4.1.2254.2.4.9 | ||||||||||||||||
| SdupsAlarmDisconnect | 1.3.6.1.4.1.2254.2.4.9.1 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Does the UPS disconnect?
| |||||||||||||||||
| SdupsAlarmPowerFail | 1.3.6.1.4.1.2254.2.4.9.2 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Does the input power fail?
| |||||||||||||||||
| SdupsAlarmBatteryLow | 1.3.6.1.4.1.2254.2.4.9.3 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Are the UPS batteries low?
| |||||||||||||||||
| SdupsAlarmLoadWarning | 1.3.6.1.4.1.2254.2.4.9.4 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Does the UPS load percent over the load warning value?
| |||||||||||||||||
| SdupsAlarmLoadSeverity | 1.3.6.1.4.1.2254.2.4.9.5 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Does the UPS load percent over the load severity value?
| |||||||||||||||||
| SdupsAlarmLoadOnBypass | 1.3.6.1.4.1.2254.2.4.9.6 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Does the UPS load on bypass?
| |||||||||||||||||
| SdupsAlarmUPSFault | 1.3.6.1.4.1.2254.2.4.9.7 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Does the UPS general fail?
| |||||||||||||||||
| SdupsAlarmBatteryGroundFault | 1.3.6.1.4.1.2254.2.4.9.8 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Does the UPS battery ground fault?
| |||||||||||||||||
| SdupsAlarmTestInProgress | 1.3.6.1.4.1.2254.2.4.9.9 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Does the UPS test in progress?
| |||||||||||||||||
| SdupsAlarmBatteryTestFail | 1.3.6.1.4.1.2254.2.4.9.10 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Does the UPS test fail?
| |||||||||||||||||
| SdupsAlarmFuseFailure | 1.3.6.1.4.1.2254.2.4.9.11 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Does the UPS fuse failure?
| |||||||||||||||||
| SdupsAlarmOutputOverload | 1.3.6.1.4.1.2254.2.4.9.12 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Does the UPS output overload?
| |||||||||||||||||
| SdupsAlarmOutputOverCurrent | 1.3.6.1.4.1.2254.2.4.9.13 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Does the UPS output overcurrent?
| |||||||||||||||||
| SdupsAlarmInverterAbnormal | 1.3.6.1.4.1.2254.2.4.9.14 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Does the UPS inverter abnormal?
| |||||||||||||||||
| SdupsAlarmRectifierAbnormal | 1.3.6.1.4.1.2254.2.4.9.15 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Does the UPS rectifier abnormal?
| |||||||||||||||||
| SdupsAlarmReserveAbnormal | 1.3.6.1.4.1.2254.2.4.9.16 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Does the UPS reserve abnormal?
| |||||||||||||||||
| SdupsAlarmLoadOnReserve | 1.3.6.1.4.1.2254.2.4.9.17 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Does the UPS load on reserve?
| |||||||||||||||||
| SdupsAlarmOverTemperature | 1.3.6.1.4.1.2254.2.4.9.18 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Does the UPS over heat?
| |||||||||||||||||
| SdupsAlarmOutputBad | 1.3.6.1.4.1.2254.2.4.9.19 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Is the UPS output abnormal?
| |||||||||||||||||
| SdupsAlarmBypassBad | 1.3.6.1.4.1.2254.2.4.9.20 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Is the UPS bypass bad?
| |||||||||||||||||
| SdupsAlarmUPSOff | 1.3.6.1.4.1.2254.2.4.9.21 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Is the UPS in standby mode?
| |||||||||||||||||
| SdupsAlarmChargerFail | 1.3.6.1.4.1.2254.2.4.9.22 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Does the UPS charger fail?
| |||||||||||||||||
| SdupsAlarmFanFail | 1.3.6.1.4.1.2254.2.4.9.23 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Does the UPS fan fail?
| |||||||||||||||||
| SdupsAlarmEconomicMode | 1.3.6.1.4.1.2254.2.4.9.24 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Indicates whether the UPS is in the economic mode.
| |||||||||||||||||
| SdupsAlarmOutputOff | 1.3.6.1.4.1.2254.2.4.9.25 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Indicates whether the UPS output is turned off or not.
| |||||||||||||||||
| SdupsAlarmSmartShutdown | 1.3.6.1.4.1.2254.2.4.9.26 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Indicates whether the Smart Shutdown is in progress.
| |||||||||||||||||
| SdupsAlarmEmergencyPowerOff | 1.3.6.1.4.1.2254.2.4.9.27 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory UPS emergency power off.
| |||||||||||||||||
| SdupsAlarmUPSShutdown | 1.3.6.1.4.1.2254.2.4.9.28 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory UPS shutdown.
| |||||||||||||||||
| NdupsEnvironment | 1.3.6.1.4.1.2254.2.4.10 | ||||||||||||||||
| SdupsEnvTemperature | 1.3.6.1.4.1.2254.2.4.10.1 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The ambient environmental temperature.
| |||||||||||||||||
| SdupsEnvHumidity | 1.3.6.1.4.1.2254.2.4.10.2 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The environmental humidity.
| |||||||||||||||||
| SdupsEnvSetTemperatureLimit | 1.3.6.1.4.1.2254.2.4.10.3 | INTEGER | RW | mandatory | |||||||||||||
scalar · INTEGER · read-write · mandatory Alarm dupsAlarmOverTemperature on when the environmental temperature over the value.
| |||||||||||||||||
| SdupsEnvSetHumidityLimit | 1.3.6.1.4.1.2254.2.4.10.4 | INTEGER | RW | mandatory | |||||||||||||
scalar · INTEGER · read-write · mandatory Alarm dupsAlarmOverHumidity on when the environmental humidity over the value.
| |||||||||||||||||
| SdupsEnvSetEnvRelay1 | 1.3.6.1.4.1.2254.2.4.10.5 | INTEGER | RW | mandatory | |||||||||||||
scalar · INTEGER · read-write · mandatory
| |||||||||||||||||
| SdupsEnvSetEnvRelay2 | 1.3.6.1.4.1.2254.2.4.10.6 | INTEGER | RW | mandatory | |||||||||||||
scalar · INTEGER · read-write · mandatory
| |||||||||||||||||
| SdupsEnvSetEnvRelay3 | 1.3.6.1.4.1.2254.2.4.10.7 | INTEGER | RW | mandatory | |||||||||||||
scalar · INTEGER · read-write · mandatory
| |||||||||||||||||
| SdupsEnvSetEnvRelay4 | 1.3.6.1.4.1.2254.2.4.10.8 | INTEGER | RW | mandatory | |||||||||||||
scalar · INTEGER · read-write · mandatory
| |||||||||||||||||
| SdupsAlarmOverEnvTemperature | 1.3.6.1.4.1.2254.2.4.10.9 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Does the environment over temperature?
| |||||||||||||||||
| SdupsAlarmOverEnvHumidity | 1.3.6.1.4.1.2254.2.4.10.10 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Does the environment over humidity?
| |||||||||||||||||
| SdupsAlarmEnvRelay1 | 1.3.6.1.4.1.2254.2.4.10.11 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory
| |||||||||||||||||
| SdupsAlarmEnvRelay2 | 1.3.6.1.4.1.2254.2.4.10.12 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory
| |||||||||||||||||
| SdupsAlarmEnvRelay3 | 1.3.6.1.4.1.2254.2.4.10.13 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory
| |||||||||||||||||
| SdupsAlarmEnvRelay4 | 1.3.6.1.4.1.2254.2.4.10.14 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory
| |||||||||||||||||
| NdupsTraps | 1.3.6.1.4.1.2254.2.4.20 | ||||||||||||||||
| !dupsCommunicationLost | 1.3.6.1.4.1.2254.2.4.20.0.1 | ||||||||||||||||
notification SEVER: Communication with the UPS failed. | |||||||||||||||||
| !dupsCommunicationEstablished | 1.3.6.1.4.1.2254.2.4.20.0.2 | ||||||||||||||||
notification INFORMATION: Communication with the UPS reestablished. | |||||||||||||||||
| !dupsPowerFail | 1.3.6.1.4.1.2254.2.4.20.0.3 | ||||||||||||||||
notification WARNING: Power failed! The UPS is operating on battery power. | |||||||||||||||||
| !dupsPowerRestored | 1.3.6.1.4.1.2254.2.4.20.0.4 | ||||||||||||||||
notification INFORMATION: Power restored! The utility power restored. | |||||||||||||||||
| !dupsLowBattery | 1.3.6.1.4.1.2254.2.4.20.0.5 | ||||||||||||||||
notification SEVER: The UPS batteries are low and will soon be exhausted. | |||||||||||||||||
| !dupsReturnFromLowBattery | 1.3.6.1.4.1.2254.2.4.20.0.6 | ||||||||||||||||
notification INFORMATION: The UPS has returned from a low battery condition. | |||||||||||||||||
| !dupsLoadWarning | 1.3.6.1.4.1.2254.2.4.20.0.7 | ||||||||||||||||
notification INFORMATION: Loading percent of the UPS over the Load Warning value. | |||||||||||||||||
| !dupsNoLongerLoadWarning | 1.3.6.1.4.1.2254.2.4.20.0.8 | ||||||||||||||||
notification INFORMATION: Returnd from Load Warning condition. | |||||||||||||||||
| !dupsLoadSeverity | 1.3.6.1.4.1.2254.2.4.20.0.9 | ||||||||||||||||
notification Warning: Loading percent of the UPS over the Load Severity value. | |||||||||||||||||
| !dupsNoLongerLoadSeverity | 1.3.6.1.4.1.2254.2.4.20.0.10 | ||||||||||||||||
notification INFORMATION: Returned from Load Severity condition. | |||||||||||||||||
| !dupsLoadOnBypass | 1.3.6.1.4.1.2254.2.4.20.0.11 | ||||||||||||||||
notification SEVER: The UPS loads on bypass. | |||||||||||||||||
| !dupsNoLongerLoadOnBypass | 1.3.6.1.4.1.2254.2.4.20.0.12 | ||||||||||||||||
notification INFORMATION: The UPS is not on bypass mode. | |||||||||||||||||
| !dupsUPSFault | 1.3.6.1.4.1.2254.2.4.20.0.13 | ||||||||||||||||
notification SEVER: A general fault caused in the UPS. | |||||||||||||||||
| !dupsReturnFromUPSFault | 1.3.6.1.4.1.2254.2.4.20.0.14 | ||||||||||||||||
notification INFORMATION: The UPS is returned from general fault. | |||||||||||||||||
| !dupsBatteryGroundFault | 1.3.6.1.4.1.2254.2.4.20.0.15 | ||||||||||||||||
notification SEVER: The UPS battery ground fault. | |||||||||||||||||
| !dupsNoLongerBatteryFault | 1.3.6.1.4.1.2254.2.4.20.0.16 | ||||||||||||||||
notification INFORMATION: The UPS recovered from battery ground fault. | |||||||||||||||||
| !dupsTestInProgress | 1.3.6.1.4.1.2254.2.4.20.0.17 | ||||||||||||||||
notification INFORMATION: The UPS test in progress. | |||||||||||||||||
| !dupsBatteryTestFail | 1.3.6.1.4.1.2254.2.4.20.0.18 | ||||||||||||||||
notification SEVER: The UPS test fail. | |||||||||||||||||
| !dupsFuseFailure | 1.3.6.1.4.1.2254.2.4.20.0.19 | ||||||||||||||||
notification SEVER: The UPS fuse failed. | |||||||||||||||||
| !dupsFuseRecovered | 1.3.6.1.4.1.2254.2.4.20.0.20 | ||||||||||||||||
notification INFORMATION: The UPS fuse recovered. | |||||||||||||||||
| !dupsOutputOverload | 1.3.6.1.4.1.2254.2.4.20.0.21 | ||||||||||||||||
notification SEVER: The UPS overload!. | |||||||||||||||||
| !dupsNoLongerOverload | 1.3.6.1.4.1.2254.2.4.20.0.22 | ||||||||||||||||
notification INFORMATION: Recovered from UPS overload. | |||||||||||||||||
| !dupsOutputOverCurrent | 1.3.6.1.4.1.2254.2.4.20.0.23 | ||||||||||||||||
notification SEVER: The UPS output overcurrent. | |||||||||||||||||
| !dupsNoLongerOutputOverCurrent | 1.3.6.1.4.1.2254.2.4.20.0.24 | ||||||||||||||||
notification INFORMATION: Recovered from UPS overcurrent. | |||||||||||||||||
| !dupsInverterAbnormal | 1.3.6.1.4.1.2254.2.4.20.0.25 | ||||||||||||||||
notification SEVER: The UPS inverter abnormal. | |||||||||||||||||
| !dupsInverterRecovered | 1.3.6.1.4.1.2254.2.4.20.0.26 | ||||||||||||||||
notification INFORMATION: Recovered from UPS inverter abnormal. | |||||||||||||||||
| !dupsRectifierAbnormal | 1.3.6.1.4.1.2254.2.4.20.0.27 | ||||||||||||||||
notification SEVER: The UPS rectifier abnormal. | |||||||||||||||||
| !dupsRectifierRecovered | 1.3.6.1.4.1.2254.2.4.20.0.28 | ||||||||||||||||
notification INFORMATION: The UPS recovered from rectifier abnormal. | |||||||||||||||||
| !dupsReserveAbnormal | 1.3.6.1.4.1.2254.2.4.20.0.29 | ||||||||||||||||
notification SEVER: The UPS rectifier abnormal. | |||||||||||||||||
| !dupsReserveRecovered | 1.3.6.1.4.1.2254.2.4.20.0.30 | ||||||||||||||||
notification INFORMATION: The UPS rectifier abnormal. | |||||||||||||||||
| !dupsLoadOnReserve | 1.3.6.1.4.1.2254.2.4.20.0.31 | ||||||||||||||||
notification SEVER: The UPS load on reserve. | |||||||||||||||||
| !dupsNoLongerLoadOnReserve | 1.3.6.1.4.1.2254.2.4.20.0.32 | ||||||||||||||||
notification INFORMATION: The UPS no longer load on reserve. | |||||||||||||||||
| !dupsEnvOverTemperature | 1.3.6.1.4.1.2254.2.4.20.0.33 | ||||||||||||||||
notification WARNING: The environment overtemperature. | |||||||||||||||||
| !dupsNoLongerEnvOverTemperature | 1.3.6.1.4.1.2254.2.4.20.0.34 | ||||||||||||||||
notification INFORMATION: The environment recovered from overtemperature. | |||||||||||||||||
| !dupsEnvOverHumidity | 1.3.6.1.4.1.2254.2.4.20.0.35 | ||||||||||||||||
notification WARNING: The environment overhumidity. | |||||||||||||||||
| !dupsNoLongerEnvOverHumidity | 1.3.6.1.4.1.2254.2.4.20.0.36 | ||||||||||||||||
notification INFORMATION: The environment recovered from overhumidity. | |||||||||||||||||
| !dupsEnvRelay1Alarm | 1.3.6.1.4.1.2254.2.4.20.0.37 | ||||||||||||||||
notification INFORMATION: The environment relay1 is not in normal state. | |||||||||||||||||
| !dupsEnvRelay1Normal | 1.3.6.1.4.1.2254.2.4.20.0.38 | ||||||||||||||||
notification INFORMATION: The environment relay1 is in normal state. | |||||||||||||||||
| !dupsEnvRelay2Alarm | 1.3.6.1.4.1.2254.2.4.20.0.39 | ||||||||||||||||
notification INFORMATION: The environment relay2 is not in normal state. | |||||||||||||||||
| !dupsEnvRelay2Normal | 1.3.6.1.4.1.2254.2.4.20.0.40 | ||||||||||||||||
notification INFORMATION: The environment relay2 is in normal state. | |||||||||||||||||
| !dupsEnvRelay3Alarm | 1.3.6.1.4.1.2254.2.4.20.0.41 | ||||||||||||||||
notification INFORMATION: The environment relay3 is not in normal state. | |||||||||||||||||
| !dupsEnvRelay3Normal | 1.3.6.1.4.1.2254.2.4.20.0.42 | ||||||||||||||||
notification INFORMATION: The environment relay3 is in normal state. | |||||||||||||||||
| !dupsEnvRelay4Alarm | 1.3.6.1.4.1.2254.2.4.20.0.43 | ||||||||||||||||
notification INFORMATION: The environment relay4 is not in normal state. | |||||||||||||||||
| !dupsEnvRelay4Normal | 1.3.6.1.4.1.2254.2.4.20.0.44 | ||||||||||||||||
notification INFORMATION: The environment relay4 is in normal state. | |||||||||||||||||
| !dupsSmartShutdown | 1.3.6.1.4.1.2254.2.4.20.0.45 | ||||||||||||||||
notification SEVER: Smart Shutdown is initiated. | |||||||||||||||||
| !dupsCancelShutdown | 1.3.6.1.4.1.2254.2.4.20.0.46 | ||||||||||||||||
notification INFORMATION: Cancel UPS Shutdown. | |||||||||||||||||
| !dupsTestCompleted | 1.3.6.1.4.1.2254.2.4.20.0.47 | ||||||||||||||||
notification INFORMATION: This trap is sent upon completion of a UPS diagnostic test. | |||||||||||||||||
| !dupsEPOON | 1.3.6.1.4.1.2254.2.4.20.0.48 | ||||||||||||||||
notification INFORMATION: This trap is sent when emergency power off is on. | |||||||||||||||||
| !dupsEPOOFF | 1.3.6.1.4.1.2254.2.4.20.0.49 | ||||||||||||||||
notification INFORMATION: This trap is sent when UPS recover from emergency power off. | |||||||||||||||||
| !dupsOverTemperature | 1.3.6.1.4.1.2254.2.4.20.0.50 | ||||||||||||||||
notification SEVER: This trap is sent when the UPS is over heat. | |||||||||||||||||
| !dupsNormalTemperature | 1.3.6.1.4.1.2254.2.4.20.0.51 | ||||||||||||||||
notification INFORMATION: This trap is sent when UPS recover from over heat. | |||||||||||||||||
| !dupsBattReplace | 1.3.6.1.4.1.2254.2.4.20.0.52 | ||||||||||||||||
notification WARNING: The battery needs to be replaced. | |||||||||||||||||
| !dupsReturnFromBattReplace | 1.3.6.1.4.1.2254.2.4.20.0.53 | ||||||||||||||||
notification INFORMATION: The UPS recovered from battery replacement. | |||||||||||||||||
Traps / Notifications
- dupsBattReplace
1.3.6.1.4.1.2254.2.4.20.0.52 - dupsBatteryGroundFault
1.3.6.1.4.1.2254.2.4.20.0.15 - dupsBatteryTestFail
1.3.6.1.4.1.2254.2.4.20.0.18 - dupsCancelShutdown
1.3.6.1.4.1.2254.2.4.20.0.46 - dupsCommunicationEstablished
1.3.6.1.4.1.2254.2.4.20.0.2 - dupsCommunicationLost
1.3.6.1.4.1.2254.2.4.20.0.1 - dupsEPOOFF
1.3.6.1.4.1.2254.2.4.20.0.49 - dupsEPOON
1.3.6.1.4.1.2254.2.4.20.0.48 - dupsEnvOverHumidity
1.3.6.1.4.1.2254.2.4.20.0.35 - dupsEnvOverTemperature
1.3.6.1.4.1.2254.2.4.20.0.33 - dupsEnvRelay1Alarm
1.3.6.1.4.1.2254.2.4.20.0.37 - dupsEnvRelay1Normal
1.3.6.1.4.1.2254.2.4.20.0.38 - dupsEnvRelay2Alarm
1.3.6.1.4.1.2254.2.4.20.0.39 - dupsEnvRelay2Normal
1.3.6.1.4.1.2254.2.4.20.0.40 - dupsEnvRelay3Alarm
1.3.6.1.4.1.2254.2.4.20.0.41 - dupsEnvRelay3Normal
1.3.6.1.4.1.2254.2.4.20.0.42 - dupsEnvRelay4Alarm
1.3.6.1.4.1.2254.2.4.20.0.43 - dupsEnvRelay4Normal
1.3.6.1.4.1.2254.2.4.20.0.44 - dupsFuseFailure
1.3.6.1.4.1.2254.2.4.20.0.19 - dupsFuseRecovered
1.3.6.1.4.1.2254.2.4.20.0.20 - dupsInverterAbnormal
1.3.6.1.4.1.2254.2.4.20.0.25 - dupsInverterRecovered
1.3.6.1.4.1.2254.2.4.20.0.26 - dupsLoadOnBypass
1.3.6.1.4.1.2254.2.4.20.0.11 - dupsLoadOnReserve
1.3.6.1.4.1.2254.2.4.20.0.31 - dupsLoadSeverity
1.3.6.1.4.1.2254.2.4.20.0.9 - dupsLoadWarning
1.3.6.1.4.1.2254.2.4.20.0.7 - dupsLowBattery
1.3.6.1.4.1.2254.2.4.20.0.5 - dupsNoLongerBatteryFault
1.3.6.1.4.1.2254.2.4.20.0.16 - dupsNoLongerEnvOverHumidity
1.3.6.1.4.1.2254.2.4.20.0.36 - dupsNoLongerEnvOverTemperature
1.3.6.1.4.1.2254.2.4.20.0.34 - dupsNoLongerLoadOnBypass
1.3.6.1.4.1.2254.2.4.20.0.12 - dupsNoLongerLoadOnReserve
1.3.6.1.4.1.2254.2.4.20.0.32 - dupsNoLongerLoadSeverity
1.3.6.1.4.1.2254.2.4.20.0.10 - dupsNoLongerLoadWarning
1.3.6.1.4.1.2254.2.4.20.0.8 - dupsNoLongerOutputOverCurrent
1.3.6.1.4.1.2254.2.4.20.0.24 - dupsNoLongerOverload
1.3.6.1.4.1.2254.2.4.20.0.22 - dupsNormalTemperature
1.3.6.1.4.1.2254.2.4.20.0.51 - dupsOutputOverCurrent
1.3.6.1.4.1.2254.2.4.20.0.23 - dupsOutputOverload
1.3.6.1.4.1.2254.2.4.20.0.21 - dupsOverTemperature
1.3.6.1.4.1.2254.2.4.20.0.50 - dupsPowerFail
1.3.6.1.4.1.2254.2.4.20.0.3 - dupsPowerRestored
1.3.6.1.4.1.2254.2.4.20.0.4 - dupsRectifierAbnormal
1.3.6.1.4.1.2254.2.4.20.0.27 - dupsRectifierRecovered
1.3.6.1.4.1.2254.2.4.20.0.28 - dupsReserveAbnormal
1.3.6.1.4.1.2254.2.4.20.0.29 - dupsReserveRecovered
1.3.6.1.4.1.2254.2.4.20.0.30 - dupsReturnFromBattReplace
1.3.6.1.4.1.2254.2.4.20.0.53 - dupsReturnFromLowBattery
1.3.6.1.4.1.2254.2.4.20.0.6 - dupsReturnFromUPSFault
1.3.6.1.4.1.2254.2.4.20.0.14 - dupsSmartShutdown
1.3.6.1.4.1.2254.2.4.20.0.45 - dupsTestCompleted
1.3.6.1.4.1.2254.2.4.20.0.47 - dupsTestInProgress
1.3.6.1.4.1.2254.2.4.20.0.17 - dupsUPSFault
1.3.6.1.4.1.2254.2.4.20.0.13