DELL-SNMP-UPS-MIB
Dell Inc.snmptranslate -m DELL-SNMP-UPS-MIB -Tpsnmpwalk -v2c -c <community> -m DELL-SNMP-UPS-MIB <host> 1.3.6.1.4.1.674Imports
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
|---|---|
| SNMPv2-SMI | Bits, Integer32, IpAddress, MODULE-IDENTITY, MibIdentifier, OBJECT-IDENTITY, OBJECT-TYPE, TRAP-TYPE, TimeTicks, Unsigned32, enterprises, iso |
| SNMPv2-TC | DisplayString, PhysAddress, TEXTUAL-CONVENTION, TimeStamp |
OID tree
| Name | OID | Type | Access | Status | Example | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Ndell | 1.3.6.1.4.1.674 | ||||||||||||||||
| Nupsdell | 1.3.6.1.4.1.674.10902 | ||||||||||||||||
| Nhardware | 1.3.6.1.4.1.674.10902.2 | ||||||||||||||||
| NproductID | 1.3.6.1.4.1.674.10902.2.100 | ||||||||||||||||
| SproductIDDisplayName | 1.3.6.1.4.1.674.10902.2.100.1 | DisplayString | RO | mandatory | Dell UPS Rack 3750W High Efficiency Online HV | ||||||||||||
scalar · DisplayString · read-only · mandatory Name of this product for display purposes. Example values from LibreNMS test devices
| |||||||||||||||||
| SproductIDDescription | 1.3.6.1.4.1.674.10902.2.100.2 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory A short description of this product. | |||||||||||||||||
| SproductIDVendor | 1.3.6.1.4.1.674.10902.2.100.3 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The name of the product manufacturer. | |||||||||||||||||
| SproductIDVersion | 1.3.6.1.4.1.674.10902.2.100.4 | DisplayString (SIZE (0..32)) | RO | mandatory | 01.08 | ||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The version of this product. Example values from LibreNMS test devices
| |||||||||||||||||
| SproductIDBuildNumber | 1.3.6.1.4.1.674.10902.2.100.5 | DisplayString (SIZE (0..32)) | RO | mandatory | 0004 | ||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The software build number of the product populating the MIB. Example values from LibreNMS test devices
| |||||||||||||||||
| SproductIDURL | 1.3.6.1.4.1.674.10902.2.100.6 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The URL of the web-based application to manage this device, should the device provide one. | |||||||||||||||||
| SproductIDDeviceNetworkName | 1.3.6.1.4.1.674.10902.2.100.7 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory Operating system specific computer name if product SNMP service is hosted. | |||||||||||||||||
| NproductStatus | 1.3.6.1.4.1.674.10902.2.110 | ||||||||||||||||
| SproductStatusGlobalStatus | 1.3.6.1.4.1.674.10902.2.110.1 | INTEGER | RO | mandatory | ok(3) | ||||||||||||
scalar · INTEGER · read-only · mandatory Current status of the product. This is a rollup for the entire product including any monitored devices. The status is intended to give initiative to an SNMP monitor to get further data when this status is abnormal.
Example values from LibreNMS test devices
| |||||||||||||||||
| SproductStatusLastGlobalStatus | 1.3.6.1.4.1.674.10902.2.110.2 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory The status before the current status which induced an initiative to issue a global status change trap. | |||||||||||||||||
| SproductStatusTimeStamp | 1.3.6.1.4.1.674.10902.2.110.3 | TimeStamp | RO | mandatory | |||||||||||||
scalar · TimeStamp · read-only · mandatory The last time that the SNMP table geometries changed and/or attribute data was significantly updated. This is to be used by management applications to trigger a refresh of data acquired from the MIB. | |||||||||||||||||
| SproductStatusGetTimeOut | 1.3.6.1.4.1.674.10902.2.110.4 | INTEGER | RO | optional | |||||||||||||
scalar · INTEGER · read-only · optional Suggested time out value in milliseconds for how long the SNMP getter should wait while attempting to poll the product SNMP service. | |||||||||||||||||
| SproductStatusRefreshRate | 1.3.6.1.4.1.674.10902.2.110.5 | INTEGER | RO | optional | |||||||||||||
scalar · INTEGER · read-only · optional Rate in seconds at which the SNMP service cached data is being updated. | |||||||||||||||||
| SproductStatusGeneratingTrapFlag | 1.3.6.1.4.1.674.10902.2.110.6 | INTEGER | RO | optional | |||||||||||||
scalar · INTEGER · read-only · optional Indicates if this SNMP sub-agent is capable of and/or is generating SNMP Traps. This variable can take the following values: 1 True, this service is capable of sending traps and is the originator of SNMP traps generated for the devices represented in this MIB and is currently generating traps. 2 False, this service not capable of sending traps and is not the originator of any SNMP traps generated for the devices represented in this MIB. 3 Disabled, this service is capable of sending traps and is the originator of SNMP traps for the devices represented in this MIB, but traps are currently disabled.
| |||||||||||||||||
| Nphysical | 1.3.6.1.4.1.674.10902.2.120 | ||||||||||||||||
| NphysicalIdent | 1.3.6.1.4.1.674.10902.2.120.1 | ||||||||||||||||
| SphysicalIdentFamilyName | 1.3.6.1.4.1.674.10902.2.120.1.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory UPS Family name. | |||||||||||||||||
| SphysicalIdentSerialNumber | 1.3.6.1.4.1.674.10902.2.120.1.2 | DisplayString (SIZE (0..32)) | RO | mandatory | CN-0K804N-75162-2CH-0081-A03 | ||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory UPS Serial number. Example values from LibreNMS test devices
| |||||||||||||||||
| SphysicalIdentConverterType | 1.3.6.1.4.1.674.10902.2.120.1.3 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory UPS type.
| |||||||||||||||||
| SphysicalIdentReferenceNumber | 1.3.6.1.4.1.674.10902.2.120.1.4 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory Technical Reference of UPS firmware. | |||||||||||||||||
| NphysicalOutput | 1.3.6.1.4.1.674.10902.2.120.2 | ||||||||||||||||
| SphysicalOutputInstantHeadroom | 1.3.6.1.4.1.674.10902.2.120.2.1 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory This is the present amount of watt capacity remaining before overload. | |||||||||||||||||
| SphysicalOutputPeakHeadroom | 1.3.6.1.4.1.674.10902.2.120.2.2 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Statistical value holding the lowest value that Instantaneous Headroom Watts was ever set too since the last time this statistic was reset. | |||||||||||||||||
| SphysicalOutputPeakHeadroomTimestamp | 1.3.6.1.4.1.674.10902.2.120.2.3 | TimeStamp | RO | mandatory | |||||||||||||
scalar · TimeStamp · read-only · mandatory Time and date stamp of the last time the Peak Headroom Watts value was updated. | |||||||||||||||||
| SphysicalOutputPeakConsumption | 1.3.6.1.4.1.674.10902.2.120.2.4 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Statistical value of the maximum RMS Watts the UPS has seen since the last time this statistic was reset. | |||||||||||||||||
| SphysicalOutputPeakConsumptionTimestamp | 1.3.6.1.4.1.674.10902.2.120.2.5 | TimeStamp | RO | mandatory | |||||||||||||
scalar · TimeStamp · read-only · mandatory Time and date stamp of the last time the Peak Consumption Watts value was updated. | |||||||||||||||||
| SphysicalOutputPresentConsumption | 1.3.6.1.4.1.674.10902.2.120.2.6 | INTEGER | RO | mandatory | 307 | ||||||||||||
scalar · INTEGER · read-only · mandatory Derived by averaging the watt second consumption over the past hour. Use an array of 60 words to store the average watt seconds consumed over the last minute then after you have a full hours worth of data in the 60 word array, average those values to get your Present KWH Consumption meter. Then every minute after that update the oldest value in the array, average again and update the meter. Value is 0 until the minimum 1 hour of data has been accumulated. Example values from LibreNMS test devices
| |||||||||||||||||
| SphysicalOutputCumulativeConsumption | 1.3.6.1.4.1.674.10902.2.120.2.7 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory 64 bit meter value that is derived by reading the Present KWH Consumption meter once per hour and adding it to the last value of this meter. Value accumulates until it is reset from the LCD or via the SHUT protocol or the meter rolls over. | |||||||||||||||||
| SphysicalOutputCumulativeConsumptionTimestamp | 1.3.6.1.4.1.674.10902.2.120.2.8 | TimeStamp | RO | mandatory | |||||||||||||
scalar · TimeStamp · read-only · mandatory Time and date stamp of last time this meter value was reset. | |||||||||||||||||
| SphysicalOutputVA | 1.3.6.1.4.1.674.10902.2.120.2.9 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Output VA. | |||||||||||||||||
| NphysicalRectifier | 1.3.6.1.4.1.674.10902.2.120.3 | ||||||||||||||||
| SphysicalRectifierPosVoltage | 1.3.6.1.4.1.674.10902.2.120.3.1 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory DC bus positive voltage. | |||||||||||||||||
| SphysicalRectifierNegVoltage | 1.3.6.1.4.1.674.10902.2.120.3.2 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory DC bus negative voltage. | |||||||||||||||||
| NphysicalUPS | 1.3.6.1.4.1.674.10902.2.120.4 | ||||||||||||||||
| SphysicalUPSDateTime | 1.3.6.1.4.1.674.10902.2.120.4.1 | TimeStamp | RO | mandatory | |||||||||||||
scalar · TimeStamp · read-only · mandatory Real Time Clock with Date and Time. | |||||||||||||||||
| SphysicalUPSAlarmsStatus | 1.3.6.1.4.1.674.10902.2.120.4.2 | DisplayString | RO | mandatory | |||||||||||||
scalar · DisplayString · read-only · mandatory List of traps that are in active mode. This list is coded in ASCI format and each trap number is separated by a coma (ex: 1,5,23,77). Only odd traps are listed. | |||||||||||||||||
| SphysicalUPSRuntimeToShutdown | 1.3.6.1.4.1.674.10902.2.120.4.3 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Number of seconds remaining until UPS will receive a ShutdownAfterDelay command. 2147483647 if no countdown is in effect. | |||||||||||||||||
| SphysicalUPSOutpoutSwitchable | 1.3.6.1.4.1.674.10902.2.120.4.4 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Parameter to enable or not remote UPS commands coming from all communication ports.
| |||||||||||||||||
| NphysicalBattery | 1.3.6.1.4.1.674.10902.2.120.5 | ||||||||||||||||
| SphysicalBatteryABMStatus | 1.3.6.1.4.1.674.10902.2.120.5.1 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Advanced Battery Monitoring satus.
| |||||||||||||||||
| SphysicalBatteryTestStatus | 1.3.6.1.4.1.674.10902.2.120.5.2 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Battery test satus.
| |||||||||||||||||
| SphysicalBatterySecondsRemaining | 1.3.6.1.4.1.674.10902.2.120.5.3 | INTEGER | RO | mandatory | 11179 | ||||||||||||
scalar · INTEGER · read-only · mandatory Battery remaining time calculated by the autonometer. Example values from LibreNMS test devices
| |||||||||||||||||
| NphysicalLoadSegment | 1.3.6.1.4.1.674.10902.2.120.6 | ||||||||||||||||
| SphysicalLoadSegment1ShutdownAfterDelay | 1.3.6.1.4.1.674.10902.2.120.6.1 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Number of seconds remaining until load segment 1 will switch off. -1 if no shutdown countdown is in effect. | |||||||||||||||||
| SphysicalLoadSegment1StartupAfterDelay | 1.3.6.1.4.1.674.10902.2.120.6.2 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Number of seconds remaining until load segment 1 will switch on. -1 if no startup countdown is in effect. | |||||||||||||||||
| SphysicalLoadSegment2ShutdownAfterDelay | 1.3.6.1.4.1.674.10902.2.120.6.3 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Number of seconds remaining until load segment 2 will switch off. -1 if no shutdown countdown is in effect. | |||||||||||||||||
| SphysicalLoadSegment2StartupAfterDelay | 1.3.6.1.4.1.674.10902.2.120.6.4 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Number of seconds remaining until load segment 2 will switch on. -1 if no startup countdown is in effect. | |||||||||||||||||
| SphysicalLoadSegment1RuntimeToShutdown | 1.3.6.1.4.1.674.10902.2.120.6.5 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Number of seconds remaining until load segment 1 will receive a ShutdownAfterDelay command. 2147483647 if no countdown is in effect. | |||||||||||||||||
| SphysicalLoadSegment2RuntimeToShutdown | 1.3.6.1.4.1.674.10902.2.120.6.6 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Number of seconds remaining until load segment 2 will receive a ShutdownAfterDelay command. 2147483647 if no countdown is in effect. | |||||||||||||||||
| NphysicalEnvironment | 1.3.6.1.4.1.674.10902.2.120.7 | ||||||||||||||||
| SphysicalEnvironmentSensorPresent | 1.3.6.1.4.1.674.10902.2.120.7.1 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Informations, if there is Environment Measurement Probe connected. | |||||||||||||||||
| SphysicalEnvironmentSensorName | 1.3.6.1.4.1.674.10902.2.120.7.2 | DisplayString (SIZE (0..59)) | RO | mandatory | |||||||||||||
scalar · DisplayString (SIZE (0..59)) · read-only · mandatory User name of EMP. | |||||||||||||||||
| NphysicalEnvironmentValues | 1.3.6.1.4.1.674.10902.2.120.7.3 | ||||||||||||||||
| SphysicalEnvironmentValuesTemperatureUnit | 1.3.6.1.4.1.674.10902.2.120.7.3.1 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Temperature unit setting.
| |||||||||||||||||
| SphysicalEnvironmentValuesTemperature | 1.3.6.1.4.1.674.10902.2.120.7.3.2 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Current temperature value in 0.1 degree Celsius. | |||||||||||||||||
| SphysicalEnvironmentValuesHumidity | 1.3.6.1.4.1.674.10902.2.120.7.3.3 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Current humidity value in 0.1 percents. | |||||||||||||||||
| SphysicalEnvironmentValuesTemperatureLow | 1.3.6.1.4.1.674.10902.2.120.7.3.4 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Temperature low threshhold in units of degree Celsius. | |||||||||||||||||
| SphysicalEnvironmentValuesTemperatureHigh | 1.3.6.1.4.1.674.10902.2.120.7.3.5 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Temperature high threshhold in units of degree Celsius. | |||||||||||||||||
| SphysicalEnvironmentValuesTemperatureHysteresis | 1.3.6.1.4.1.674.10902.2.120.7.3.6 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Temperature hysteresis in units of degree Celsius. | |||||||||||||||||
| SphysicalEnvironmentValueshHumidityLow | 1.3.6.1.4.1.674.10902.2.120.7.3.7 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Humidity low threshhold in percents. | |||||||||||||||||
| SphysicalEnvironmentValuesHumidityHigh | 1.3.6.1.4.1.674.10902.2.120.7.3.8 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Humidity high threshhold in percents. | |||||||||||||||||
| SphysicalEnvironmentValuesHumidityHysteresis | 1.3.6.1.4.1.674.10902.2.120.7.3.9 | INTEGER | RO | mandatory | |||||||||||||
scalar · INTEGER · read-only · mandatory Humidity hysteresis in percents. | |||||||||||||||||
| TphysicalEnvironmentInputTable | 1.3.6.1.4.1.674.10902.2.120.7.4 | NA | mandatory | ||||||||||||||
table · not-accessible · mandatory The table containins dry contact inputs information. | |||||||||||||||||
| RphysicalEnvironmentInputEntry | 1.3.6.1.4.1.674.10902.2.120.7.4.1 | NA | mandatory | ||||||||||||||
row · not-accessible · mandatory The description of an entry in the table. | |||||||||||||||||
| CphysicalEnvironmentInputIndex | 1.3.6.1.4.1.674.10902.2.120.7.4.1.1 | INTEGER (0..1) | RO | mandatory | |||||||||||||
column · INTEGER (0..1) · read-only · mandatory The input index, ranging from 1 to 2. | |||||||||||||||||
| CphysicalEnvironmentInputName | 1.3.6.1.4.1.674.10902.2.120.7.4.1.2 | DisplayString (SIZE (0..27)) | RO | mandatory | |||||||||||||
column · DisplayString (SIZE (0..27)) · read-only · mandatory The input user-friendly name. | |||||||||||||||||
| CphysicalEnvironmentInputState | 1.3.6.1.4.1.674.10902.2.120.7.4.1.3 | INTEGER | RO | mandatory | |||||||||||||
column · INTEGER · read-only · mandatory Current state of input.
| |||||||||||||||||
| CphysicalEnvironmentInputOpenedState | 1.3.6.1.4.1.674.10902.2.120.7.4.1.4 | DisplayString (SIZE (0..21)) | RO | mandatory | |||||||||||||
column · DisplayString (SIZE (0..21)) · read-only · mandatory The input opened state user-friendly name. | |||||||||||||||||
| CphysicalEnvironmentInputClosedState | 1.3.6.1.4.1.674.10902.2.120.7.4.1.5 | DisplayString (SIZE (0..21)) | RO | mandatory | |||||||||||||
column · DisplayString (SIZE (0..21)) · read-only · mandatory The input closed state user-friendly name. | |||||||||||||||||
| Nlogical | 1.3.6.1.4.1.674.10902.2.130 | ||||||||||||||||
| Ntraps | 1.3.6.1.4.1.674.10902.2.140 | ||||||||||||||||
| !trapInverterOverVoltage | 1.3.6.1.4.1.674.10902.2.140.0.1 | ||||||||||||||||
notification Inverter AC over voltage. | |||||||||||||||||
| !trapInverterOverVoltageOk | 1.3.6.1.4.1.674.10902.2.140.0.2 | ||||||||||||||||
notification Inverter AC over voltage ok. | |||||||||||||||||
| !trapInverterUnderVoltage | 1.3.6.1.4.1.674.10902.2.140.0.3 | ||||||||||||||||
notification Inverter AC under voltage. | |||||||||||||||||
| !trapInverterUnderVoltageOk | 1.3.6.1.4.1.674.10902.2.140.0.4 | ||||||||||||||||
notification Inverter AC under voltage ok. | |||||||||||||||||
| !trapBypassFrequencyOutOfRange | 1.3.6.1.4.1.674.10902.2.140.0.5 | ||||||||||||||||
notification Bypass under or over frequency. | |||||||||||||||||
| !trapBypassFrequencyOutOfRangeOk | 1.3.6.1.4.1.674.10902.2.140.0.6 | ||||||||||||||||
notification Bypass under or over frequency ok. | |||||||||||||||||
| !trapOnBuck | 1.3.6.1.4.1.674.10902.2.140.0.7 | ||||||||||||||||
notification On Buck / Input Voltage Reducer. | |||||||||||||||||
| !trapReturnFromBuck | 1.3.6.1.4.1.674.10902.2.140.0.8 | ||||||||||||||||
notification Return from Buck. | |||||||||||||||||
| !trapOnBoost | 1.3.6.1.4.1.674.10902.2.140.0.9 | ||||||||||||||||
notification On Boost / Input Voltage Booster. | |||||||||||||||||
| !trapReturnFromBoost | 1.3.6.1.4.1.674.10902.2.140.0.10 | ||||||||||||||||
notification Return from Boost. | |||||||||||||||||
| !trapInputOverVoltage | 1.3.6.1.4.1.674.10902.2.140.0.11 | ||||||||||||||||
notification Input AC over voltage. | |||||||||||||||||
| !trapInputOverVoltageOk | 1.3.6.1.4.1.674.10902.2.140.0.12 | ||||||||||||||||
notification Input AC over voltage ok. | |||||||||||||||||
| !trapInputUnderVoltage | 1.3.6.1.4.1.674.10902.2.140.0.13 | ||||||||||||||||
notification Input AC under voltage. | |||||||||||||||||
| !trapInputUnderVoltageOk | 1.3.6.1.4.1.674.10902.2.140.0.14 | ||||||||||||||||
notification Input AC under voltage ok. | |||||||||||||||||
| !trapInputFrequencyOutOfRange | 1.3.6.1.4.1.674.10902.2.140.0.15 | ||||||||||||||||
notification Input under or over frequency. | |||||||||||||||||
| !trapInputFrequencyOutOfRangeOk | 1.3.6.1.4.1.674.10902.2.140.0.16 | ||||||||||||||||
notification Input under or over frequency ok. | |||||||||||||||||
| !trapRemoteEmergencyPowerOff | 1.3.6.1.4.1.674.10902.2.140.0.17 | ||||||||||||||||
notification Remote emergency power off. | |||||||||||||||||
| !trapReturnFromEmergencyPowerOff | 1.3.6.1.4.1.674.10902.2.140.0.18 | ||||||||||||||||
notification Return from remote emergency power off. | |||||||||||||||||
| !trapLevel1Overload | 1.3.6.1.4.1.674.10902.2.140.0.19 | ||||||||||||||||
notification Output Level 1 overload. | |||||||||||||||||
| !trapLevel1OverloadOk | 1.3.6.1.4.1.674.10902.2.140.0.20 | ||||||||||||||||
notification Output Level 1 overload ok. | |||||||||||||||||
| !trapLevel2Overload | 1.3.6.1.4.1.674.10902.2.140.0.21 | ||||||||||||||||
notification Level 2 overload. | |||||||||||||||||
| !trapLevel2OverloadOk | 1.3.6.1.4.1.674.10902.2.140.0.22 | ||||||||||||||||
notification Level 2 overload ok. | |||||||||||||||||
| !trapLevel3Overload | 1.3.6.1.4.1.674.10902.2.140.0.23 | ||||||||||||||||
notification Level 3 overload. | |||||||||||||||||
| !trapLevel3OverloadOk | 1.3.6.1.4.1.674.10902.2.140.0.24 | ||||||||||||||||
notification Level 3 overload ok. | |||||||||||||||||
| !trapPosDCLinkOverVoltage | 1.3.6.1.4.1.674.10902.2.140.0.25 | ||||||||||||||||
notification Positive DC link over voltage. | |||||||||||||||||
| !trapPosDCLinkOverVoltageOk | 1.3.6.1.4.1.674.10902.2.140.0.26 | ||||||||||||||||
notification Positive DC link over voltage ok. | |||||||||||||||||
| !trapPosDCLinkUnderVoltage | 1.3.6.1.4.1.674.10902.2.140.0.27 | ||||||||||||||||
notification Positive DC link under voltage. | |||||||||||||||||
| !trapPosDCLinkUnderVoltageOk | 1.3.6.1.4.1.674.10902.2.140.0.28 | ||||||||||||||||
notification Positive DC link under voltage ok. | |||||||||||||||||
| !trapNegDCLinkOverVoltage | 1.3.6.1.4.1.674.10902.2.140.0.29 | ||||||||||||||||
notification Negative DC link over voltage. | |||||||||||||||||
| !trapNegDCLinkOverVoltageOk | 1.3.6.1.4.1.674.10902.2.140.0.30 | ||||||||||||||||
notification Negative DC link over voltage ok. | |||||||||||||||||
| !trapNegDCLinkUnderVoltage | 1.3.6.1.4.1.674.10902.2.140.0.31 | ||||||||||||||||
notification Negative DC link under voltage. | |||||||||||||||||
| !trapNegDCLinkUnderVoltageOk | 1.3.6.1.4.1.674.10902.2.140.0.32 | ||||||||||||||||
notification Negative DC link under voltage ok. | |||||||||||||||||
| !trapRectifierFault | 1.3.6.1.4.1.674.10902.2.140.0.33 | ||||||||||||||||
notification Rectifier fault. | |||||||||||||||||
| !trapRectifierOk | 1.3.6.1.4.1.674.10902.2.140.0.34 | ||||||||||||||||
notification Rectifier ok. | |||||||||||||||||
| !trapInverterFault | 1.3.6.1.4.1.674.10902.2.140.0.35 | ||||||||||||||||
notification Inverter fault. | |||||||||||||||||
| !trapInverterOk | 1.3.6.1.4.1.674.10902.2.140.0.36 | ||||||||||||||||
notification Inverter ok. | |||||||||||||||||
| !trapChargerFailure | 1.3.6.1.4.1.674.10902.2.140.0.37 | ||||||||||||||||
notification Charger failure. | |||||||||||||||||
| !trapChargerOk | 1.3.6.1.4.1.674.10902.2.140.0.38 | ||||||||||||||||
notification Charger ok. | |||||||||||||||||
| !trapEepromFailure | 1.3.6.1.4.1.674.10902.2.140.0.39 | ||||||||||||||||
notification EEPROM failure. | |||||||||||||||||
| !trapEepromOk | 1.3.6.1.4.1.674.10902.2.140.0.40 | ||||||||||||||||
notification EEPROM off. | |||||||||||||||||
| !trapShutdownImminent | 1.3.6.1.4.1.674.10902.2.140.0.41 | ||||||||||||||||
notification Shutdown imminent. | |||||||||||||||||
| !trapShutdownImminentOver | 1.3.6.1.4.1.674.10902.2.140.0.42 | ||||||||||||||||
notification Shutdown imminent over. | |||||||||||||||||
| !trapBatteryLow | 1.3.6.1.4.1.674.10902.2.140.0.43 | ||||||||||||||||
notification Battery low. | |||||||||||||||||
| !trapBatteryOk | 1.3.6.1.4.1.674.10902.2.140.0.44 | ||||||||||||||||
notification Battery ok. | |||||||||||||||||
| !trapOutputShortCircuit | 1.3.6.1.4.1.674.10902.2.140.0.45 | ||||||||||||||||
notification Output short circuit. | |||||||||||||||||
| !trapOutputReturnFromShortCircuit | 1.3.6.1.4.1.674.10902.2.140.0.46 | ||||||||||||||||
notification Output return from short circuit. | |||||||||||||||||
| !trapUtilityNotPresent | 1.3.6.1.4.1.674.10902.2.140.0.47 | ||||||||||||||||
notification Utility not present. | |||||||||||||||||
| !trapUtilityPresent | 1.3.6.1.4.1.674.10902.2.140.0.48 | ||||||||||||||||
notification Utility present. | |||||||||||||||||
| !trapBatteryOverVoltage | 1.3.6.1.4.1.674.10902.2.140.0.49 | ||||||||||||||||
notification Battery DC over voltage. | |||||||||||||||||
| !trapBatteryOverVoltageOk | 1.3.6.1.4.1.674.10902.2.140.0.50 | ||||||||||||||||
notification Battery DC over voltage ok. | |||||||||||||||||
| !trapHeatsinkOvertemperature | 1.3.6.1.4.1.674.10902.2.140.0.51 | ||||||||||||||||
notification Heatsink overtemperature. | |||||||||||||||||
| !trapHeatsinkOvertemperatureOk | 1.3.6.1.4.1.674.10902.2.140.0.52 | ||||||||||||||||
notification Heatsink overtemperature ok. | |||||||||||||||||
| !trapBypassNotAvailable | 1.3.6.1.4.1.674.10902.2.140.0.53 | ||||||||||||||||
notification Bypass not available. | |||||||||||||||||
| !trapBypassNotAvailableOk | 1.3.6.1.4.1.674.10902.2.140.0.54 | ||||||||||||||||
notification Bypass not available ok. | |||||||||||||||||
| !trapOnManualBypass | 1.3.6.1.4.1.674.10902.2.140.0.55 | ||||||||||||||||
notification On manual/ maintenance bypass. | |||||||||||||||||
| !trapUPSOnBattery | 1.3.6.1.4.1.674.10902.2.140.0.57 | ||||||||||||||||
notification UPS on battery. | |||||||||||||||||
| !trapUPSReturnFromBattery | 1.3.6.1.4.1.674.10902.2.140.0.58 | ||||||||||||||||
notification UPS return from battery. | |||||||||||||||||
| !trapUPSOnBypass | 1.3.6.1.4.1.674.10902.2.140.0.59 | ||||||||||||||||
notification UPS on bypass. | |||||||||||||||||
| !trapUPSReturnFromBypass | 1.3.6.1.4.1.674.10902.2.140.0.60 | ||||||||||||||||
notification UPS return from bypass. | |||||||||||||||||
| !trapBatteryTestInProgress | 1.3.6.1.4.1.674.10902.2.140.0.61 | ||||||||||||||||
notification Battery manual or automatic test in progress. | |||||||||||||||||
| !trapBatteryTestDone | 1.3.6.1.4.1.674.10902.2.140.0.62 | ||||||||||||||||
| !trapBatteryNeedReplacement | 1.3.6.1.4.1.674.10902.2.140.0.63 | ||||||||||||||||
notification Battery test failed, battery needs to be replaced. | |||||||||||||||||
| !trapBatteryReplacementDone | 1.3.6.1.4.1.674.10902.2.140.0.64 | ||||||||||||||||
notification Battery replacement done. | |||||||||||||||||
| !trapFanFailure | 1.3.6.1.4.1.674.10902.2.140.0.65 | ||||||||||||||||
notification Fan failure. | |||||||||||||||||
| !trapFanOk | 1.3.6.1.4.1.674.10902.2.140.0.66 | ||||||||||||||||
notification Fan ok. | |||||||||||||||||
| !trapSiteWiringFault | 1.3.6.1.4.1.674.10902.2.140.0.67 | ||||||||||||||||
notification Site wiring fault. | |||||||||||||||||
| !trapSiteWiringOk | 1.3.6.1.4.1.674.10902.2.140.0.68 | ||||||||||||||||
notification Site wiring ok. | |||||||||||||||||
| !trapBatteryDisconnected | 1.3.6.1.4.1.674.10902.2.140.0.69 | ||||||||||||||||
notification Batteries disconnected. | |||||||||||||||||
| !trapBatteryConnected | 1.3.6.1.4.1.674.10902.2.140.0.70 | ||||||||||||||||
notification Batteries connected. | |||||||||||||||||
| !trapUPSOff | 1.3.6.1.4.1.674.10902.2.140.0.71 | ||||||||||||||||
notification UPS off. | |||||||||||||||||
| !trapUPSOn | 1.3.6.1.4.1.674.10902.2.140.0.72 | ||||||||||||||||
notification UPS on. | |||||||||||||||||
| !trapDCLinkImbalance | 1.3.6.1.4.1.674.10902.2.140.0.73 | ||||||||||||||||
notification DC link imbalance. | |||||||||||||||||
| !trapDCLinkImbalanceOk | 1.3.6.1.4.1.674.10902.2.140.0.74 | ||||||||||||||||
notification DC link imbalance ok. | |||||||||||||||||
| !trapABMOn | 1.3.6.1.4.1.674.10902.2.140.0.79 | ||||||||||||||||
| !trapABMOff | 1.3.6.1.4.1.674.10902.2.140.0.80 | ||||||||||||||||
notification ABM state off. | |||||||||||||||||
| !trapLoadSegment1Off | 1.3.6.1.4.1.674.10902.2.140.0.81 | ||||||||||||||||
notification Load segment 1 off. | |||||||||||||||||
| !trapLoadSegment1On | 1.3.6.1.4.1.674.10902.2.140.0.82 | ||||||||||||||||
notification Load segment 1 on. | |||||||||||||||||
| !trapLoadSegment2Off | 1.3.6.1.4.1.674.10902.2.140.0.83 | ||||||||||||||||
notification Load segment 2 off. | |||||||||||||||||
| !trapLoadSegment2On | 1.3.6.1.4.1.674.10902.2.140.0.84 | ||||||||||||||||
notification Load segment 2 on. | |||||||||||||||||
| !trapInHighEfficiencyMode | 1.3.6.1.4.1.674.10902.2.140.0.85 | ||||||||||||||||
notification In High Efficiency mode. | |||||||||||||||||
| !trapReturnFromHighEfficiencyMode | 1.3.6.1.4.1.674.10902.2.140.0.86 | ||||||||||||||||
notification Return from High Efficiency mode. | |||||||||||||||||
| !trapRectifierOverload | 1.3.6.1.4.1.674.10902.2.140.0.87 | ||||||||||||||||
notification Rectifier input over current. | |||||||||||||||||
| !trapRectifierOverloadOk | 1.3.6.1.4.1.674.10902.2.140.0.88 | ||||||||||||||||
notification Rectifier current ok. | |||||||||||||||||
| !trapInverterOverload | 1.3.6.1.4.1.674.10902.2.140.0.89 | ||||||||||||||||
notification Inverter output over current. | |||||||||||||||||
| !trapInverterOverloadOk | 1.3.6.1.4.1.674.10902.2.140.0.90 | ||||||||||||||||
notification Inverter output current ok. | |||||||||||||||||
| !trapBypassVoltageOutOfRange | 1.3.6.1.4.1.674.10902.2.140.0.91 | ||||||||||||||||
notification Bypass AC under or over voltage. | |||||||||||||||||
| !trapBypassVoltageOutOfRangeOk | 1.3.6.1.4.1.674.10902.2.140.0.92 | ||||||||||||||||
notification Bypass AC under or over voltage ok. | |||||||||||||||||
| !trapServiceBattery | 1.3.6.1.4.1.674.10902.2.140.0.93 | ||||||||||||||||
notification Service battery. | |||||||||||||||||
| !trapToBypassCommand | 1.3.6.1.4.1.674.10902.2.140.0.94 | ||||||||||||||||
notification UPS received command to switch on bypass. | |||||||||||||||||
| !trapFromBypassCommand | 1.3.6.1.4.1.674.10902.2.140.0.95 | ||||||||||||||||
notification UPS received command to switch on inverter. | |||||||||||||||||
| !trapCommunicationLost | 1.3.6.1.4.1.674.10902.2.140.0.96 | ||||||||||||||||
notification Lost communication with UPS, HID databasis is not updated. | |||||||||||||||||
| !trapCommunicationRestored | 1.3.6.1.4.1.674.10902.2.140.0.97 | ||||||||||||||||
notification Communication restored with UPS, HID databasis is updated. | |||||||||||||||||
| !trapEnvironComFailure | 1.3.6.1.4.1.674.10902.2.140.0.98 | ||||||||||||||||
notification Environment Probe communication failure. | |||||||||||||||||
| !trapEnvironComOK | 1.3.6.1.4.1.674.10902.2.140.0.99 | ||||||||||||||||
notification Environment Probe communication restored. | |||||||||||||||||
| !trapEnvironTemperatureLow | 1.3.6.1.4.1.674.10902.2.140.0.100 | ||||||||||||||||
notification Temperature is below low threshold. | |||||||||||||||||
| !trapEnvironTemperatureHigh | 1.3.6.1.4.1.674.10902.2.140.0.102 | ||||||||||||||||
notification Temperature is above high threshold. | |||||||||||||||||
| !trapEnvironTemperatureOK | 1.3.6.1.4.1.674.10902.2.140.0.103 | ||||||||||||||||
notification Temperature is in normal range. | |||||||||||||||||
| !trapEnvironHumidityLow | 1.3.6.1.4.1.674.10902.2.140.0.104 | ||||||||||||||||
notification Humidity is below low threshold. | |||||||||||||||||
| !trapEnvironHumidityHigh | 1.3.6.1.4.1.674.10902.2.140.0.106 | ||||||||||||||||
notification Humidity is above high threshold. | |||||||||||||||||
| !trapEnvironHumidityOK | 1.3.6.1.4.1.674.10902.2.140.0.107 | ||||||||||||||||
notification Humidity is in normal range. | |||||||||||||||||
| !trapEnvironInput1Closed | 1.3.6.1.4.1.674.10902.2.140.0.108 | ||||||||||||||||
notification Input #1 is Closed. | |||||||||||||||||
| !trapEnvironInput1Open | 1.3.6.1.4.1.674.10902.2.140.0.109 | ||||||||||||||||
notification Input #1 is Open. | |||||||||||||||||
| !trapEnvironInput2Closed | 1.3.6.1.4.1.674.10902.2.140.0.110 | ||||||||||||||||
notification Input #2 is Closed. | |||||||||||||||||
| !trapEnvironInput2Open | 1.3.6.1.4.1.674.10902.2.140.0.111 | ||||||||||||||||
notification Input #2 is Open. | |||||||||||||||||
Traps / Notifications
- trapABMOff
1.3.6.1.4.1.674.10902.2.140.0.80 - trapABMOn
1.3.6.1.4.1.674.10902.2.140.0.79 - trapBatteryConnected
1.3.6.1.4.1.674.10902.2.140.0.70 - trapBatteryDisconnected
1.3.6.1.4.1.674.10902.2.140.0.69 - trapBatteryLow
1.3.6.1.4.1.674.10902.2.140.0.43 - trapBatteryNeedReplacement
1.3.6.1.4.1.674.10902.2.140.0.63 - trapBatteryOk
1.3.6.1.4.1.674.10902.2.140.0.44 - trapBatteryOverVoltage
1.3.6.1.4.1.674.10902.2.140.0.49 - trapBatteryOverVoltageOk
1.3.6.1.4.1.674.10902.2.140.0.50 - trapBatteryReplacementDone
1.3.6.1.4.1.674.10902.2.140.0.64 - trapBatteryTestDone
1.3.6.1.4.1.674.10902.2.140.0.62 - trapBatteryTestInProgress
1.3.6.1.4.1.674.10902.2.140.0.61 - trapBypassFrequencyOutOfRange
1.3.6.1.4.1.674.10902.2.140.0.5 - trapBypassFrequencyOutOfRangeOk
1.3.6.1.4.1.674.10902.2.140.0.6 - trapBypassNotAvailable
1.3.6.1.4.1.674.10902.2.140.0.53 - trapBypassNotAvailableOk
1.3.6.1.4.1.674.10902.2.140.0.54 - trapBypassVoltageOutOfRange
1.3.6.1.4.1.674.10902.2.140.0.91 - trapBypassVoltageOutOfRangeOk
1.3.6.1.4.1.674.10902.2.140.0.92 - trapChargerFailure
1.3.6.1.4.1.674.10902.2.140.0.37 - trapChargerOk
1.3.6.1.4.1.674.10902.2.140.0.38 - trapCommunicationLost
1.3.6.1.4.1.674.10902.2.140.0.96 - trapCommunicationRestored
1.3.6.1.4.1.674.10902.2.140.0.97 - trapDCLinkImbalance
1.3.6.1.4.1.674.10902.2.140.0.73 - trapDCLinkImbalanceOk
1.3.6.1.4.1.674.10902.2.140.0.74 - trapEepromFailure
1.3.6.1.4.1.674.10902.2.140.0.39 - trapEepromOk
1.3.6.1.4.1.674.10902.2.140.0.40 - trapEnvironComFailure
1.3.6.1.4.1.674.10902.2.140.0.98 - trapEnvironComOK
1.3.6.1.4.1.674.10902.2.140.0.99 - trapEnvironHumidityHigh
1.3.6.1.4.1.674.10902.2.140.0.106 - trapEnvironHumidityLow
1.3.6.1.4.1.674.10902.2.140.0.104 - trapEnvironHumidityOK
1.3.6.1.4.1.674.10902.2.140.0.107 - trapEnvironInput1Closed
1.3.6.1.4.1.674.10902.2.140.0.108 - trapEnvironInput1Open
1.3.6.1.4.1.674.10902.2.140.0.109 - trapEnvironInput2Closed
1.3.6.1.4.1.674.10902.2.140.0.110 - trapEnvironInput2Open
1.3.6.1.4.1.674.10902.2.140.0.111 - trapEnvironTemperatureHigh
1.3.6.1.4.1.674.10902.2.140.0.102 - trapEnvironTemperatureLow
1.3.6.1.4.1.674.10902.2.140.0.100 - trapEnvironTemperatureOK
1.3.6.1.4.1.674.10902.2.140.0.103 - trapFanFailure
1.3.6.1.4.1.674.10902.2.140.0.65 - trapFanOk
1.3.6.1.4.1.674.10902.2.140.0.66 - trapFromBypassCommand
1.3.6.1.4.1.674.10902.2.140.0.95 - trapHeatsinkOvertemperature
1.3.6.1.4.1.674.10902.2.140.0.51 - trapHeatsinkOvertemperatureOk
1.3.6.1.4.1.674.10902.2.140.0.52 - trapInHighEfficiencyMode
1.3.6.1.4.1.674.10902.2.140.0.85 - trapInputFrequencyOutOfRange
1.3.6.1.4.1.674.10902.2.140.0.15 - trapInputFrequencyOutOfRangeOk
1.3.6.1.4.1.674.10902.2.140.0.16 - trapInputOverVoltage
1.3.6.1.4.1.674.10902.2.140.0.11 - trapInputOverVoltageOk
1.3.6.1.4.1.674.10902.2.140.0.12 - trapInputUnderVoltage
1.3.6.1.4.1.674.10902.2.140.0.13 - trapInputUnderVoltageOk
1.3.6.1.4.1.674.10902.2.140.0.14 - trapInverterFault
1.3.6.1.4.1.674.10902.2.140.0.35 - trapInverterOk
1.3.6.1.4.1.674.10902.2.140.0.36 - trapInverterOverVoltage
1.3.6.1.4.1.674.10902.2.140.0.1 - trapInverterOverVoltageOk
1.3.6.1.4.1.674.10902.2.140.0.2 - trapInverterOverload
1.3.6.1.4.1.674.10902.2.140.0.89 - trapInverterOverloadOk
1.3.6.1.4.1.674.10902.2.140.0.90 - trapInverterUnderVoltage
1.3.6.1.4.1.674.10902.2.140.0.3 - trapInverterUnderVoltageOk
1.3.6.1.4.1.674.10902.2.140.0.4 - trapLevel1Overload
1.3.6.1.4.1.674.10902.2.140.0.19 - trapLevel1OverloadOk
1.3.6.1.4.1.674.10902.2.140.0.20 - trapLevel2Overload
1.3.6.1.4.1.674.10902.2.140.0.21 - trapLevel2OverloadOk
1.3.6.1.4.1.674.10902.2.140.0.22 - trapLevel3Overload
1.3.6.1.4.1.674.10902.2.140.0.23 - trapLevel3OverloadOk
1.3.6.1.4.1.674.10902.2.140.0.24 - trapLoadSegment1Off
1.3.6.1.4.1.674.10902.2.140.0.81 - trapLoadSegment1On
1.3.6.1.4.1.674.10902.2.140.0.82 - trapLoadSegment2Off
1.3.6.1.4.1.674.10902.2.140.0.83 - trapLoadSegment2On
1.3.6.1.4.1.674.10902.2.140.0.84 - trapNegDCLinkOverVoltage
1.3.6.1.4.1.674.10902.2.140.0.29 - trapNegDCLinkOverVoltageOk
1.3.6.1.4.1.674.10902.2.140.0.30 - trapNegDCLinkUnderVoltage
1.3.6.1.4.1.674.10902.2.140.0.31 - trapNegDCLinkUnderVoltageOk
1.3.6.1.4.1.674.10902.2.140.0.32 - trapOnBoost
1.3.6.1.4.1.674.10902.2.140.0.9 - trapOnBuck
1.3.6.1.4.1.674.10902.2.140.0.7 - trapOnManualBypass
1.3.6.1.4.1.674.10902.2.140.0.55 - trapOutputReturnFromShortCircuit
1.3.6.1.4.1.674.10902.2.140.0.46 - trapOutputShortCircuit
1.3.6.1.4.1.674.10902.2.140.0.45 - trapPosDCLinkOverVoltage
1.3.6.1.4.1.674.10902.2.140.0.25 - trapPosDCLinkOverVoltageOk
1.3.6.1.4.1.674.10902.2.140.0.26 - trapPosDCLinkUnderVoltage
1.3.6.1.4.1.674.10902.2.140.0.27 - trapPosDCLinkUnderVoltageOk
1.3.6.1.4.1.674.10902.2.140.0.28 - trapRectifierFault
1.3.6.1.4.1.674.10902.2.140.0.33 - trapRectifierOk
1.3.6.1.4.1.674.10902.2.140.0.34 - trapRectifierOverload
1.3.6.1.4.1.674.10902.2.140.0.87 - trapRectifierOverloadOk
1.3.6.1.4.1.674.10902.2.140.0.88 - trapRemoteEmergencyPowerOff
1.3.6.1.4.1.674.10902.2.140.0.17 - trapReturnFromBoost
1.3.6.1.4.1.674.10902.2.140.0.10 - trapReturnFromBuck
1.3.6.1.4.1.674.10902.2.140.0.8 - trapReturnFromEmergencyPowerOff
1.3.6.1.4.1.674.10902.2.140.0.18 - trapReturnFromHighEfficiencyMode
1.3.6.1.4.1.674.10902.2.140.0.86 - trapServiceBattery
1.3.6.1.4.1.674.10902.2.140.0.93 - trapShutdownImminent
1.3.6.1.4.1.674.10902.2.140.0.41 - trapShutdownImminentOver
1.3.6.1.4.1.674.10902.2.140.0.42 - trapSiteWiringFault
1.3.6.1.4.1.674.10902.2.140.0.67 - trapSiteWiringOk
1.3.6.1.4.1.674.10902.2.140.0.68 - trapToBypassCommand
1.3.6.1.4.1.674.10902.2.140.0.94 - trapUPSOff
1.3.6.1.4.1.674.10902.2.140.0.71 - trapUPSOn
1.3.6.1.4.1.674.10902.2.140.0.72 - trapUPSOnBattery
1.3.6.1.4.1.674.10902.2.140.0.57 - trapUPSOnBypass
1.3.6.1.4.1.674.10902.2.140.0.59 - trapUPSReturnFromBattery
1.3.6.1.4.1.674.10902.2.140.0.58 - trapUPSReturnFromBypass
1.3.6.1.4.1.674.10902.2.140.0.60 - trapUtilityNotPresent
1.3.6.1.4.1.674.10902.2.140.0.47 - trapUtilityPresent
1.3.6.1.4.1.674.10902.2.140.0.48