KELVIN-pCOWeb-Chiller-MIB
CARELThis is the MIB module for the kelvin-pCOWeb-Chiller device.
snmptranslate -m KELVIN-pCOWeb-Chiller-MIB -Tpsnmpwalk -v2c -c <community> -m KELVIN-pCOWeb-Chiller-MIB <host> 1.3.6.1.4.1.9839.2.1Imports
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP, OBJECT-GROUP |
|---|---|
| SNMPv2-MIB | sysContact, sysLocation, sysName |
| SNMPv2-SMI | Bits, Integer32, IpAddress, MODULE-IDENTITY, MibIdentifier, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, TimeTicks, Unsigned32, enterprises, iso |
| SNMPv2-TC | DisplayString, PhysAddress, TEXTUAL-CONVENTION |
OID tree
| Name | OID | Type | Access | Status | Example | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Ncarel | 1.3.6.1.4.1.9839 | ||||||||||||||||
| Nsystm | 1.3.6.1.4.1.9839.1 | ||||||||||||||||
| SagentRelease | 1.3.6.1.4.1.9839.1.1 | Integer32 | RO | 4 | |||||||||||||
scalar · Integer32 · read-only · current Release of the Agent.
Example values from LibreNMS test devices
| |||||||||||||||||
| SagentCode | 1.3.6.1.4.1.9839.1.2 | Integer32 | RO | 2 | |||||||||||||
scalar · Integer32 · read-only · current Code of the Agent. 2=pCOWeb.
Example values from LibreNMS test devices
| |||||||||||||||||
| Ninstruments | 1.3.6.1.4.1.9839.2 | ||||||||||||||||
| NpCOWebInfo | 1.3.6.1.4.1.9839.2.0 | ||||||||||||||||
| NpCOStatusgroup | 1.3.6.1.4.1.9839.2.0.10 | ||||||||||||||||
| SpCOId1-Status | 1.3.6.1.4.1.9839.2.0.10.1 | Integer32 | RO | 2 | |||||||||||||
scalar · Integer32 · read-only · current Status of pCOId1. 0=Offline, 1=Init, 2=Online
Example values from LibreNMS test devices
| |||||||||||||||||
| NpCOErrorsNumbergroup | 1.3.6.1.4.1.9839.2.0.11 | ||||||||||||||||
| SpCOId1-ErrorsNumber | 1.3.6.1.4.1.9839.2.0.11.1 | Integer32 | RO | 0 | |||||||||||||
scalar · Integer32 · read-only · current Number of Communication Errors from pCOId1 to pCOWeb.
Example values from LibreNMS test devices
| |||||||||||||||||
| Ikelvin-pCOWebMIB-Chiller | 1.3.6.1.4.1.9839.2.1 | ||||||||||||||||
identity This is the MIB module for the kelvin-pCOWeb-Chiller device. | |||||||||||||||||
| NdigitalObjects | 1.3.6.1.4.1.9839.2.1.1 | ||||||||||||||||
| Sal-pa1 | 1.3.6.1.4.1.9839.2.1.1.1 | Integer32 (0..1) | RO | 1 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current High pressure switch 1 alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-pa2 | 1.3.6.1.4.1.9839.2.1.1.2 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current High pressure switch 2 alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-pb1 | 1.3.6.1.4.1.9839.2.1.1.3 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Low pressure switch 1 alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-pb2 | 1.3.6.1.4.1.9839.2.1.1.4 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Low pressure switch 2 alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-le | 1.3.6.1.4.1.9839.2.1.1.6 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Water level alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-idrofrigo-fl1 | 1.3.6.1.4.1.9839.2.1.1.8 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Flow switch alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sstatic-press-alarm | 1.3.6.1.4.1.9839.2.1.1.9 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Water static pressure alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sw-static-press-alarm | 1.3.6.1.4.1.9839.2.1.1.10 | Integer32 (0..1) | RO | 1 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Water static pressure warning
Example values from LibreNMS test devices
| |||||||||||||||||
| Sflow-value-alarm | 1.3.6.1.4.1.9839.2.1.1.11 | Integer32 (0..1) | RO | 1 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Flow rate alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-q-comp1 | 1.3.6.1.4.1.9839.2.1.1.12 | Integer32 (0..1) | RO | 1 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Overload compressor 1 circuit 1 alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-q-comp2 | 1.3.6.1.4.1.9839.2.1.1.13 | Integer32 (0..1) | RO | 1 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Overload compressor 2 circuit 1 alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-q-comp3 | 1.3.6.1.4.1.9839.2.1.1.14 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Overload compressor 3 circuit 1 alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-q-comp4 | 1.3.6.1.4.1.9839.2.1.1.15 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Overload compressor 1 circuit 2 alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-q-comp5 | 1.3.6.1.4.1.9839.2.1.1.16 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Overload compressor 2 circuit 2 alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-q-comp6 | 1.3.6.1.4.1.9839.2.1.1.17 | Integer32 (0..1) | RO | 1 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Overload compressor 3 circuit 2 alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-q-fan-1 | 1.3.6.1.4.1.9839.2.1.1.18 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Overload fans circuit 1
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-q-fan-2 | 1.3.6.1.4.1.9839.2.1.1.19 | Integer32 (0..1) | RO | 1 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Overload fans circuit 2
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-q-fan11 | 1.3.6.1.4.1.9839.2.1.1.20 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Overload fan 1 circuit 1 alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-q-fan12 | 1.3.6.1.4.1.9839.2.1.1.21 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Overload fan 2 circuit 1 alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-q-fan13 | 1.3.6.1.4.1.9839.2.1.1.22 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Overload fan 3 circuit 1 alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-q-fan14 | 1.3.6.1.4.1.9839.2.1.1.23 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Overload fan 4 circuit 1 alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-q-fan21 | 1.3.6.1.4.1.9839.2.1.1.24 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Overload fan 1 circuit 2 alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-q-fan22 | 1.3.6.1.4.1.9839.2.1.1.25 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Overload fan 2 circuit 2 alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-q-fan-23 | 1.3.6.1.4.1.9839.2.1.1.26 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Overload fan 3 circuit 2 alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-q-fan24 | 1.3.6.1.4.1.9839.2.1.1.27 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Overload fan 4 circuit 2 alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-idrofrigo-pump1 | 1.3.6.1.4.1.9839.2.1.1.28 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Overload pump 1 alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-idrofrigo-pump2 | 1.3.6.1.4.1.9839.2.1.1.29 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Overload pump 2 alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-phase-cont | 1.3.6.1.4.1.9839.2.1.1.30 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Wrong phase rotation alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-door-sw | 1.3.6.1.4.1.9839.2.1.1.31 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Back Door open alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Scompressor-FlowRate | 1.3.6.1.4.1.9839.2.1.1.32 | Integer32 (0..1) | RW | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-write · current Compressor FlowRate Management
Example values from LibreNMS test devices
| |||||||||||||||||
| Ssetpoint-inv-pumps | 1.3.6.1.4.1.9839.2.1.1.33 | Integer32 (0..1) | RW | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-write · current Setpoint Type for Inverter pumps
Example values from LibreNMS test devices
| |||||||||||||||||
| Senable-pumps-redundance | 1.3.6.1.4.1.9839.2.1.1.34 | Integer32 (0..1) | RW | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-write · current Enable Pumps redundance
Example values from LibreNMS test devices
| |||||||||||||||||
| Senable-chiller-redundance | 1.3.6.1.4.1.9839.2.1.1.35 | Integer32 (0..1) | RW | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-write · current Enable Chiller redundance
Example values from LibreNMS test devices
| |||||||||||||||||
| Sstatus-in-alarm | 1.3.6.1.4.1.9839.2.1.1.36 | Integer32 (0..1) | RW | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-write · current Status in alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Scompressor-recovery | 1.3.6.1.4.1.9839.2.1.1.37 | Integer32 (0..1) | RW | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-write · current Compressor Recovery
Example values from LibreNMS test devices
| |||||||||||||||||
| Senable-thermal-redundance | 1.3.6.1.4.1.9839.2.1.1.38 | Integer32 (0..1) | RW | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-write · current Enable Thermal redundance
Example values from LibreNMS test devices
| |||||||||||||||||
| Senable-multi-pumps-function | 1.3.6.1.4.1.9839.2.1.1.39 | Integer32 (0..1) | RW | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-write · current Enable multi-pumps function
Example values from LibreNMS test devices
| |||||||||||||||||
| Senable-pumps-offline | 1.3.6.1.4.1.9839.2.1.1.40 | Integer32 (0..1) | RW | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-write · current Enable function pumps-Offline
Example values from LibreNMS test devices
| |||||||||||||||||
| Senable-3way-valve | 1.3.6.1.4.1.9839.2.1.1.41 | Integer32 (0..1) | RW | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-write · current Enable 3way valve
Example values from LibreNMS test devices
| |||||||||||||||||
| Senable-speed-up-FCM | 1.3.6.1.4.1.9839.2.1.1.42 | Integer32 (0..1) | RW | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-write · current Enable speed-up FCM
Example values from LibreNMS test devices
| |||||||||||||||||
| Senable-soft-start-FCM | 1.3.6.1.4.1.9839.2.1.1.43 | Integer32 (0..1) | RW | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-write · current Enable soft-start FCM
Example values from LibreNMS test devices
| |||||||||||||||||
| Senable-freecooling | 1.3.6.1.4.1.9839.2.1.1.44 | Integer32 (0..1) | RW | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-write · current Enable Freecooling
Example values from LibreNMS test devices
| |||||||||||||||||
| Senable-rot-FIFO-FC | 1.3.6.1.4.1.9839.2.1.1.45 | Integer32 (0..1) | RW | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-write · current Enable rotation FIFO Freecooling
Example values from LibreNMS test devices
| |||||||||||||||||
| Senable-HT-function | 1.3.6.1.4.1.9839.2.1.1.46 | Integer32 (0..1) | RW | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-write · current Enable HT-function
Example values from LibreNMS test devices
| |||||||||||||||||
| Senable-PID-Fc-valve | 1.3.6.1.4.1.9839.2.1.1.47 | Integer32 (0..1) | RW | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-write · current Enable PID-regulation for Freecooling valve
Example values from LibreNMS test devices
| |||||||||||||||||
| Senable-Fc-Thermal-Exclusion | 1.3.6.1.4.1.9839.2.1.1.48 | Integer32 (0..1) | RW | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-write · current Enable Freecooling Thermal Exclusion
Example values from LibreNMS test devices
| |||||||||||||||||
| Smanual-Reset-Ext-Drycooler-Alarm | 1.3.6.1.4.1.9839.2.1.1.49 | Integer32 (0..1) | RW | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-write · current Manual Reset External Dry-cooler Alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Senable-static-press-Alarm | 1.3.6.1.4.1.9839.2.1.1.50 | Integer32 (0..1) | RW | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-write · current Enable static pressure Alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Smanual-reset-static-press-Alarm | 1.3.6.1.4.1.9839.2.1.1.51 | Integer32 (0..1) | RW | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-write · current Manual reset static pressure Alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Senable-static-press-Warning | 1.3.6.1.4.1.9839.2.1.1.52 | Integer32 (0..1) | RW | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-write · current Enable static pressure Warning
Example values from LibreNMS test devices
| |||||||||||||||||
| Smanual-reset-static-press-Warning | 1.3.6.1.4.1.9839.2.1.1.53 | Integer32 (0..1) | RW | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-write · current Manual reset static pressure Warning
Example values from LibreNMS test devices
| |||||||||||||||||
| Senable-diff-press-Alarm | 1.3.6.1.4.1.9839.2.1.1.54 | Integer32 (0..1) | RW | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-write · current Enable differential pressure Alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Smanual-reset-diff-press-Alarm | 1.3.6.1.4.1.9839.2.1.1.55 | Integer32 (0..1) | RW | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-write · current Manual reset differential pressure Alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Senable-pressure-recovery | 1.3.6.1.4.1.9839.2.1.1.56 | Integer32 (0..1) | RW | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-write · current Enable pressure recovery
Example values from LibreNMS test devices
| |||||||||||||||||
| Senable-Flow-Rate-Alarm | 1.3.6.1.4.1.9839.2.1.1.57 | Integer32 (0..1) | RW | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-write · current Enable Flow-Rate Alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Smanual-reset-Flow-Rate-Alarm | 1.3.6.1.4.1.9839.2.1.1.58 | Integer32 (0..1) | RW | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-write · current Manual reset Flow-Rate Alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Senable-Flow-Rate-recovery | 1.3.6.1.4.1.9839.2.1.1.59 | Integer32 (0..1) | RW | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-write · current Enable Flow-Rate recovery
Example values from LibreNMS test devices
| |||||||||||||||||
| Senable-pCOWeb | 1.3.6.1.4.1.9839.2.1.1.60 | Integer32 (0..1) | RW | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-write · current Enable pCOWeb
Example values from LibreNMS test devices
| |||||||||||||||||
| Sfc-single-chiller | 1.3.6.1.4.1.9839.2.1.1.61 | Integer32 (0..1) | RW | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-write · current Freecooling single chiller function
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-idrofrigo-pump-c-1 | 1.3.6.1.4.1.9839.2.1.1.75 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Condensation pump 1 breaker switch alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-idrofrigo-pump-c-2 | 1.3.6.1.4.1.9839.2.1.1.76 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Condensation pump 2 breaker switch alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-idrofrigo-fl-C | 1.3.6.1.4.1.9839.2.1.1.80 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Condensation flow switch alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sc11-on | 1.3.6.1.4.1.9839.2.1.1.100 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Compressor 1 circuit 1 ON
Example values from LibreNMS test devices
| |||||||||||||||||
| Sc12-on | 1.3.6.1.4.1.9839.2.1.1.101 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Compressor 2 circuit 1 ON
Example values from LibreNMS test devices
| |||||||||||||||||
| Sc13-on | 1.3.6.1.4.1.9839.2.1.1.102 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Compressor 3 circuit 1 ON
Example values from LibreNMS test devices
| |||||||||||||||||
| Sc21-on | 1.3.6.1.4.1.9839.2.1.1.103 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Compressor 1 circuit 2 ON
Example values from LibreNMS test devices
| |||||||||||||||||
| Sc22-on | 1.3.6.1.4.1.9839.2.1.1.104 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Compressor 2 circuit 2 ON
Example values from LibreNMS test devices
| |||||||||||||||||
| Sc23-on | 1.3.6.1.4.1.9839.2.1.1.105 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Compressor 3 circuit 2 ON
Example values from LibreNMS test devices
| |||||||||||||||||
| Spump1-on | 1.3.6.1.4.1.9839.2.1.1.106 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Pump 1 ON
Example values from LibreNMS test devices
| |||||||||||||||||
| Spump2-on | 1.3.6.1.4.1.9839.2.1.1.107 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Pump 2 ON
Example values from LibreNMS test devices
| |||||||||||||||||
| Son-fan-gr1 | 1.3.6.1.4.1.9839.2.1.1.108 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Fans group 1 ON
Example values from LibreNMS test devices
| |||||||||||||||||
| Son-fan-gr2 | 1.3.6.1.4.1.9839.2.1.1.109 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Fans group 2 ON
Example values from LibreNMS test devices
| |||||||||||||||||
| Sfc-on | 1.3.6.1.4.1.9839.2.1.1.110 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Freecooling or external dry-cooler 1 ON
Example values from LibreNMS test devices
| |||||||||||||||||
| Sen-on-off-rem | 1.3.6.1.4.1.9839.2.1.1.130 | Integer32 (0..1) | RW | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-write · current Remote on-off
Example values from LibreNMS test devices
| |||||||||||||||||
| Sunit-on | 1.3.6.1.4.1.9839.2.1.1.131 | Integer32 (0..1) | RW | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-write · current Chiller ON
Example values from LibreNMS test devices
| |||||||||||||||||
| Sdisch-alarm-scw-1 | 1.3.6.1.4.1.9839.2.1.1.148 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Discharge screw compressor 1 alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sdisch-alarm-scw-2 | 1.3.6.1.4.1.9839.2.1.1.149 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Discharge screw compressor 2 alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-probe-inlet | 1.3.6.1.4.1.9839.2.1.1.150 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Inlet probe alarm (broken or disconnected)
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-probe-amb | 1.3.6.1.4.1.9839.2.1.1.151 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Ambient probe alarm (broken or disconnected)
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-frigo-fl1 | 1.3.6.1.4.1.9839.2.1.1.152 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Flow switch alarm (cooling alarm)
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-idro-pump1 | 1.3.6.1.4.1.9839.2.1.1.153 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Pump 1 hydraulic alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-idro-pump2 | 1.3.6.1.4.1.9839.2.1.1.154 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Pump 2 hydraulic alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-idro-fl1 | 1.3.6.1.4.1.9839.2.1.1.155 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Flow switch alarm (hydraulic alarm)
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-warning-fl1 | 1.3.6.1.4.1.9839.2.1.1.156 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Flow switch alarm (warning alarm)
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-hi-water-temp | 1.3.6.1.4.1.9839.2.1.1.157 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current High Temperature alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-lo-water-temp | 1.3.6.1.4.1.9839.2.1.1.158 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Low Temperature alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-ta-probe1 | 1.3.6.1.4.1.9839.2.1.1.159 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Antifreeze/evaporator probe 1 alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-hi-press | 1.3.6.1.4.1.9839.2.1.1.160 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current High condensation pressure alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-lo-press | 1.3.6.1.4.1.9839.2.1.1.161 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Low condensation pressure alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-probe-evap-1 | 1.3.6.1.4.1.9839.2.1.1.162 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Antifreeze/evaporator probe 1 alarm (broken or disconnected)
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-probe-evap-2 | 1.3.6.1.4.1.9839.2.1.1.163 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Antifreeze/evaporator probe 2 alarm (broken or disconnected)
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-hi-press-1 | 1.3.6.1.4.1.9839.2.1.1.164 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current High condensation pressure 1 alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-hi-press-2 | 1.3.6.1.4.1.9839.2.1.1.165 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current High condensation pressure 2 alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-lo-press-1 | 1.3.6.1.4.1.9839.2.1.1.166 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Low condensation pressure 1 alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-lo-press-2 | 1.3.6.1.4.1.9839.2.1.1.167 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Low condensation pressure 2 alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-probe-tank | 1.3.6.1.4.1.9839.2.1.1.168 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Tank/Out probe alarm (broken or disconnected)
Example values from LibreNMS test devices
| |||||||||||||||||
| Soff-line-1 | 1.3.6.1.4.1.9839.2.1.1.169 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Chiller 1 offline
Example values from LibreNMS test devices
| |||||||||||||||||
| Soff-line-2 | 1.3.6.1.4.1.9839.2.1.1.170 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Chiller 2 offline
Example values from LibreNMS test devices
| |||||||||||||||||
| Soff-line-3 | 1.3.6.1.4.1.9839.2.1.1.171 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Chiller 3 offline
Example values from LibreNMS test devices
| |||||||||||||||||
| Soff-line-4 | 1.3.6.1.4.1.9839.2.1.1.172 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Chiller 4 offline
Example values from LibreNMS test devices
| |||||||||||||||||
| Soff-line-5 | 1.3.6.1.4.1.9839.2.1.1.173 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Chiller 5 offline
Example values from LibreNMS test devices
| |||||||||||||||||
| Soff-line-6 | 1.3.6.1.4.1.9839.2.1.1.174 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Chiller 6 offline
Example values from LibreNMS test devices
| |||||||||||||||||
| Soff-line-7 | 1.3.6.1.4.1.9839.2.1.1.175 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Chiller 7 offline
Example values from LibreNMS test devices
| |||||||||||||||||
| Soff-line-8 | 1.3.6.1.4.1.9839.2.1.1.176 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Chiller 8 offline
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-ta-probe2 | 1.3.6.1.4.1.9839.2.1.1.177 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Antifreeze/evaporator probe 2 alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-sms | 1.3.6.1.4.1.9839.2.1.1.178 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current SMS alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-modem | 1.3.6.1.4.1.9839.2.1.1.179 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Modem alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Ssms-coda-alarm | 1.3.6.1.4.1.9839.2.1.1.180 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current SMS coda alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-probe-fc | 1.3.6.1.4.1.9839.2.1.1.181 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Freecooling probe alarm (broken or disconnected)
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-maint-pw1 | 1.3.6.1.4.1.9839.2.1.1.182 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Maintenance pump 1 alarm)
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-maint-pw2 | 1.3.6.1.4.1.9839.2.1.1.183 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Maintenance pump 2 alarm)
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-hi-temp-rid | 1.3.6.1.4.1.9839.2.1.1.184 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current High temperature alarm (redundance)
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-q-fc-sep | 1.3.6.1.4.1.9839.2.1.1.185 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current DryCooler breaker switch alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-p-wat2 | 1.3.6.1.4.1.9839.2.1.1.186 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Water pressure 2 alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-p-wat1 | 1.3.6.1.4.1.9839.2.1.1.187 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Water pressure 1 alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-foult-flow-p1 | 1.3.6.1.4.1.9839.2.1.1.188 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Pump 1 flow alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-foult-flow-p2 | 1.3.6.1.4.1.9839.2.1.1.189 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Pump 2 flow alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-foult-fl1-p1 | 1.3.6.1.4.1.9839.2.1.1.190 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Pump 1 flow-switch alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-foult-fl1-p2 | 1.3.6.1.4.1.9839.2.1.1.191 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Pump 2 flow-switch alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-warning-le | 1.3.6.1.4.1.9839.2.1.1.192 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Water level warning
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-frigo-fl-C | 1.3.6.1.4.1.9839.2.1.1.193 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Flow switch condensation alarm (cooling alarm)
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-idro-pump-c-1 | 1.3.6.1.4.1.9839.2.1.1.194 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Pump 1 condensation hydraulic alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-idro-pump-c-2 | 1.3.6.1.4.1.9839.2.1.1.195 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Pump 2 condensation hydraulic alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-idro-fl-C | 1.3.6.1.4.1.9839.2.1.1.196 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Flow switch condensation alarm (hydraulic alarm)
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-warning-fl-C | 1.3.6.1.4.1.9839.2.1.1.197 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Flow switch condensation alarm (warning alarm)
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-foul-fl-C-p1 | 1.3.6.1.4.1.9839.2.1.1.198 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Pump 1 condensation flow-switch alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| Sal-foul-fl-C-p2 | 1.3.6.1.4.1.9839.2.1.1.199 | Integer32 (0..1) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1) · read-only · current Pump 2 condensation flow-switch alarm
Example values from LibreNMS test devices
| |||||||||||||||||
| NanalogObjects | 1.3.6.1.4.1.9839.2.1.2 | ||||||||||||||||
| Ssetpoint-antifreeze1 | 1.3.6.1.4.1.9839.2.1.2.1 | Integer32 (-999..999) | RW | 1 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Setpoint Antifreeze 1
Example values from LibreNMS test devices
| |||||||||||||||||
| Ssetpoint-antifreeze2 | 1.3.6.1.4.1.9839.2.1.2.2 | Integer32 (-999..999) | RW | 50 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Setpoint Antifreeze 2
Example values from LibreNMS test devices
| |||||||||||||||||
| Ssetpoint-Compensation | 1.3.6.1.4.1.9839.2.1.2.3 | Integer32 (-999..999) | RW | 80 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Setpoint Compensation
Example values from LibreNMS test devices
| |||||||||||||||||
| Shysteresis-Compensation | 1.3.6.1.4.1.9839.2.1.2.4 | Integer32 (-999..999) | RW | 330 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Hysteresis Compensation
Example values from LibreNMS test devices
| |||||||||||||||||
| Smax-Compensation | 1.3.6.1.4.1.9839.2.1.2.5 | Integer32 (-999..999) | RW | 300 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Max. Compensation
Example values from LibreNMS test devices
| |||||||||||||||||
| Ssetpoint-Differential | 1.3.6.1.4.1.9839.2.1.2.6 | Integer32 (-999..999) | RW | 800 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Setpoint Differential
Example values from LibreNMS test devices
| |||||||||||||||||
| Shigh-Limit | 1.3.6.1.4.1.9839.2.1.2.7 | Integer32 (-999..999) | RW | 280 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current High Limit
Example values from LibreNMS test devices
| |||||||||||||||||
| Slow-Limit | 1.3.6.1.4.1.9839.2.1.2.8 | Integer32 (-999..999) | RW | 492 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Low Limit
Example values from LibreNMS test devices
| |||||||||||||||||
| Smax-Setpoint-Differential | 1.3.6.1.4.1.9839.2.1.2.9 | Integer32 (-999..999) | RW | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Max. Setpoint Differential
Example values from LibreNMS test devices
| |||||||||||||||||
| Smin-Setpoint-Differential | 1.3.6.1.4.1.9839.2.1.2.10 | Integer32 (-999..999) | RW | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Min. Setpoint Differential
Example values from LibreNMS test devices
| |||||||||||||||||
| Ssetpoint-ASB-Inverter-pumps | 1.3.6.1.4.1.9839.2.1.2.11 | Integer32 (-999..999) | RW | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Setpoint ASB Inverter pumps
Example values from LibreNMS test devices
| |||||||||||||||||
| Ssetpoint-DIFF-Inverter-pumps | 1.3.6.1.4.1.9839.2.1.2.12 | Integer32 (-999..999) | RW | 280 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Setpoint DIFF Inverter pumps
Example values from LibreNMS test devices
| |||||||||||||||||
| Spressure-Out | 1.3.6.1.4.1.9839.2.1.2.13 | Integer32 (-999..999) | RO | 492 | |||||||||||||
scalar · Integer32 (-999..999) · read-only · current Pressure Out
Example values from LibreNMS test devices
| |||||||||||||||||
| Sproportional-Band-Inverter-Pumps-PID | 1.3.6.1.4.1.9839.2.1.2.14 | Integer32 (-999..999) | RW | 491 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Proportional Band Inverter Pumps PID
Example values from LibreNMS test devices
| |||||||||||||||||
| Sintegral-Time-Inverter-Pumps-PID | 1.3.6.1.4.1.9839.2.1.2.15 | Integer32 (-999..999) | RW | -9999 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Integral Time Inverter Pumps PID
Example values from LibreNMS test devices
| |||||||||||||||||
| Sderivative-Time-Inverter-Pumps-PID | 1.3.6.1.4.1.9839.2.1.2.16 | Integer32 (-999..999) | RW | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Derivative Time Inverter Pumps PID
Example values from LibreNMS test devices
| |||||||||||||||||
| Shysteresis-Thermal-redundance | 1.3.6.1.4.1.9839.2.1.2.17 | Integer32 (-999..999) | RW | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Hysteresis Thermal redundance
Example values from LibreNMS test devices
| |||||||||||||||||
| Smin-Opening-3Way-Valve-Hydraulic | 1.3.6.1.4.1.9839.2.1.2.18 | Integer32 (-999..999) | RW | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Min. Opening 3Way Valve Hydraulic
Example values from LibreNMS test devices
| |||||||||||||||||
| Smax-Opening-3Way-Valve-Hydraulic | 1.3.6.1.4.1.9839.2.1.2.19 | Integer32 (-999..999) | RW | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Max. Opening 3Way Valve Hydraulic
Example values from LibreNMS test devices
| |||||||||||||||||
| Sproportional-Band-3Way-Valve-Hydrauli-PID | 1.3.6.1.4.1.9839.2.1.2.20 | Integer32 (-999..999) | RW | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Proportional Band 3Way Valve Hydraulic PID
Example values from LibreNMS test devices
| |||||||||||||||||
| Ssetpoint-FCM | 1.3.6.1.4.1.9839.2.1.2.21 | Integer32 (-999..999) | RW | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Setpoint FCM
Example values from LibreNMS test devices
| |||||||||||||||||
| Shysteresis-FCM | 1.3.6.1.4.1.9839.2.1.2.22 | Integer32 (-999..999) | RW | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Hysteresis FCM
Example values from LibreNMS test devices
| |||||||||||||||||
| Smax-Out-Speed-FCM | 1.3.6.1.4.1.9839.2.1.2.23 | Integer32 (-999..999) | RW | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Max. Out Speed FCM
Example values from LibreNMS test devices
| |||||||||||||||||
| Smin-Out-Speed-FCM | 1.3.6.1.4.1.9839.2.1.2.24 | Integer32 (-999..999) | RW | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Min. Out Speed FCM
Example values from LibreNMS test devices
| |||||||||||||||||
| Shysteresis-Cut-off-FCM | 1.3.6.1.4.1.9839.2.1.2.25 | Integer32 (-999..999) | RW | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Hysteresis Cut-off FCM
Example values from LibreNMS test devices
| |||||||||||||||||
| Smax-Pressure-Alarm-FCM | 1.3.6.1.4.1.9839.2.1.2.26 | Integer32 (-999..999) | RW | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Max. Pressure Alarm FCM
Example values from LibreNMS test devices
| |||||||||||||||||
| Shysteresis-Max-Pressure-Alarm-FCM | 1.3.6.1.4.1.9839.2.1.2.27 | Integer32 (-999..999) | RW | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Hysteresis Max.Pressure Alarm FCM
Example values from LibreNMS test devices
| |||||||||||||||||
| Smax-Out-FCM | 1.3.6.1.4.1.9839.2.1.2.28 | Integer32 (-999..999) | RW | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Max. Out FCM
Example values from LibreNMS test devices
| |||||||||||||||||
| Smin-Pressure-Alarm-FCM | 1.3.6.1.4.1.9839.2.1.2.29 | Integer32 (-999..999) | RW | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Min. Pressure Alarm FCM
Example values from LibreNMS test devices
| |||||||||||||||||
| Shysteresis-Min-Pressure-Alarm-FCM | 1.3.6.1.4.1.9839.2.1.2.30 | Integer32 (-999..999) | RW | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Hysteresis Min.Pressure Alarm FCM
Example values from LibreNMS test devices
| |||||||||||||||||
| Smin-Out-FCM | 1.3.6.1.4.1.9839.2.1.2.31 | Integer32 (-999..999) | RW | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Min. Out FCM
Example values from LibreNMS test devices
| |||||||||||||||||
| Sdelta-Freecooling | 1.3.6.1.4.1.9839.2.1.2.32 | Integer32 (-999..999) | RW | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Delta Freecooling
Example values from LibreNMS test devices
| |||||||||||||||||
| Shysteresis-Freecooling | 1.3.6.1.4.1.9839.2.1.2.33 | Integer32 (-999..999) | RW | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Hysteresis Freecooling
Example values from LibreNMS test devices
| |||||||||||||||||
| Sproportional-Band-Freecooling-PID | 1.3.6.1.4.1.9839.2.1.2.34 | Integer32 (-999..999) | RW | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Proportional Band Freecooling PID
Example values from LibreNMS test devices
| |||||||||||||||||
| Soffset-Freecooling-PID | 1.3.6.1.4.1.9839.2.1.2.35 | Integer32 (-999..999) | RW | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Offset Freecooling PID
Example values from LibreNMS test devices
| |||||||||||||||||
| Stemperature-Overlap-Freecooling | 1.3.6.1.4.1.9839.2.1.2.36 | Integer32 (-999..999) | RW | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Temperature Overlap Freecooling
Example values from LibreNMS test devices
| |||||||||||||||||
| Smin-out-freecooling | 1.3.6.1.4.1.9839.2.1.2.37 | Integer32 (-999..999) | RW | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Min. out freecooling
Example values from LibreNMS test devices
| |||||||||||||||||
| Sneutral-zone-K-costant | 1.3.6.1.4.1.9839.2.1.2.38 | Integer32 (-999..999) | RW | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Neutral zone K costant
Example values from LibreNMS test devices
| |||||||||||||||||
| Sneutral-zone-V-variable | 1.3.6.1.4.1.9839.2.1.2.39 | Integer32 (-999..999) | RW | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Neutral zone V variable
Example values from LibreNMS test devices
| |||||||||||||||||
| Sproportional-Band-freecooling-Valve-PID | 1.3.6.1.4.1.9839.2.1.2.40 | Integer32 (-999..999) | RW | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Proportional Band freecooling Valve PID
Example values from LibreNMS test devices
| |||||||||||||||||
| Soffset-Freecooling-Valve-PID | 1.3.6.1.4.1.9839.2.1.2.41 | Integer32 (-999..999) | RW | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Offset Freecooling Valve PID
Example values from LibreNMS test devices
| |||||||||||||||||
| Stemperature-A-B | 1.3.6.1.4.1.9839.2.1.2.42 | Integer32 (-999..999) | RO | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-only · current Temperature A-B
Example values from LibreNMS test devices
| |||||||||||||||||
| Sdelta-Thermal-Excusion-Freecoling | 1.3.6.1.4.1.9839.2.1.2.43 | Integer32 (-999..999) | RW | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Delta Thermal Excusion Freecoling
Example values from LibreNMS test devices
| |||||||||||||||||
| Shysteresis-Thermal-Excusion-Freecoling | 1.3.6.1.4.1.9839.2.1.2.44 | Integer32 (-999..999) | RW | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current hysteresis Thermal Excusion Freecoling
Example values from LibreNMS test devices
| |||||||||||||||||
| Salarm-Setpoint-Static-Pressure-Hydraulic-circuit | 1.3.6.1.4.1.9839.2.1.2.45 | Integer32 (-999..999) | RW | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Alarm Setpoint Static Pressure Hydraulic circuit
Example values from LibreNMS test devices
| |||||||||||||||||
| Swarnig-Setpoint-Static-Pressure-Hydraulic-circuit | 1.3.6.1.4.1.9839.2.1.2.46 | Integer32 (-999..999) | RW | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Warnig Setpoint Static Pressure Hydraulic circuit
Example values from LibreNMS test devices
| |||||||||||||||||
| Salarm-Setpoint-Differential-Pressure-Hydraulic-circuit | 1.3.6.1.4.1.9839.2.1.2.47 | Integer32 (-999..999) | RW | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Alarm Setpoint Differential Pressure Hydraulic circuit
Example values from LibreNMS test devices
| |||||||||||||||||
| Salarm-Setpoint-Flow-Rate-Hydraulic-circuit | 1.3.6.1.4.1.9839.2.1.2.48 | Integer32 (-999..999) | RW | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Alarm Setpoint Flow-Rate Hydraulic circuit
Example values from LibreNMS test devices
| |||||||||||||||||
| Stempertaure-Cut-off-FCM | 1.3.6.1.4.1.9839.2.1.2.50 | Integer32 (-999..999) | RW | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Tempertaure Cut-off FCM
Example values from LibreNMS test devices
| |||||||||||||||||
| Sset-effective | 1.3.6.1.4.1.9839.2.1.2.59 | Integer32 (-999..999) | RO | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-only · current Set-effective
Example values from LibreNMS test devices
| |||||||||||||||||
| Sset-fc | 1.3.6.1.4.1.9839.2.1.2.60 | Integer32 (-999..999) | RO | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-only · current Freecooling or drycooler Set-point
Example values from LibreNMS test devices
| |||||||||||||||||
| Ssetpoint-a-us | 1.3.6.1.4.1.9839.2.1.2.61 | Integer32 (-999..999) | RW | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Set-point MAIN
Example values from LibreNMS test devices
| |||||||||||||||||
| Smax-setpoint | 1.3.6.1.4.1.9839.2.1.2.62 | Integer32 (-999..999) | RW | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Max.setpoint
Example values from LibreNMS test devices
| |||||||||||||||||
| Smin-setpoint | 1.3.6.1.4.1.9839.2.1.2.63 | Integer32 (-999..999) | RW | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Min.setpoint
Example values from LibreNMS test devices
| |||||||||||||||||
| Sdiff | 1.3.6.1.4.1.9839.2.1.2.64 | Integer32 (-999..999) | RW | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current differential
Example values from LibreNMS test devices
| |||||||||||||||||
| Smax-diff | 1.3.6.1.4.1.9839.2.1.2.65 | Integer32 (-999..999) | RW | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Max. differential
Example values from LibreNMS test devices
| |||||||||||||||||
| Smin-diff | 1.3.6.1.4.1.9839.2.1.2.66 | Integer32 (-999..999) | RW | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-write · current Min.Differential
Example values from LibreNMS test devices
| |||||||||||||||||
| Sfcs-out | 1.3.6.1.4.1.9839.2.1.2.67 | Integer32 (0..1000) | RO | 0 | |||||||||||||
scalar · Integer32 (0..1000) · read-only · current Fans speed controller output %
Example values from LibreNMS test devices
| |||||||||||||||||
| Swater-temp | 1.3.6.1.4.1.9839.2.1.2.70 | Integer32 (-999..999) | RO | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-only · current Tank - Process water temperature
Example values from LibreNMS test devices
| |||||||||||||||||
| Stemp-inlet | 1.3.6.1.4.1.9839.2.1.2.71 | Integer32 (-999..999) | RO | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-only · current Water inlet temperature
Example values from LibreNMS test devices
| |||||||||||||||||
| Stemp-outlet | 1.3.6.1.4.1.9839.2.1.2.72 | Integer32 (-999..999) | RO | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-only · current Water outlet temperature
Example values from LibreNMS test devices
| |||||||||||||||||
| Sflow-value | 1.3.6.1.4.1.9839.2.1.2.73 | Integer32 (-9999..9999) | RO | 1413 | |||||||||||||
scalar · Integer32 (-9999..9999) · read-only · current Flow rate value
Example values from LibreNMS test devices
| |||||||||||||||||
| Samp-value | 1.3.6.1.4.1.9839.2.1.2.74 | Integer32 (-9999..9999) | RO | 10 | |||||||||||||
scalar · Integer32 (-9999..9999) · read-only · current Current cunsumption
Example values from LibreNMS test devices
| |||||||||||||||||
| Sta-probe-temp-1 | 1.3.6.1.4.1.9839.2.1.2.75 | Integer32 (-999..999) | RO | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-only · current Antifreeze 1 temperature monitoring
Example values from LibreNMS test devices
| |||||||||||||||||
| Sta-probe-temp-2 | 1.3.6.1.4.1.9839.2.1.2.76 | Integer32 (-999..999) | RO | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-only · current Antifreeze 2 temperature monitoring
Example values from LibreNMS test devices
| |||||||||||||||||
| Spressione1 | 1.3.6.1.4.1.9839.2.1.2.77 | Integer32 (-999..999) | RO | 70 | |||||||||||||
scalar · Integer32 (-999..999) · read-only · current Condensation pressure circuit 1
Example values from LibreNMS test devices
| |||||||||||||||||
| Spressione2 | 1.3.6.1.4.1.9839.2.1.2.78 | Integer32 (-999..999) | RO | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-only · current Condensation pressure circuit 2
Example values from LibreNMS test devices
| |||||||||||||||||
| Spump-sp-press | 1.3.6.1.4.1.9839.2.1.2.79 | Integer32 (-999..999) | RO | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-only · current Pump discharge pressure
Example values from LibreNMS test devices
| |||||||||||||||||
| Sp-wat2 | 1.3.6.1.4.1.9839.2.1.2.80 | Integer32 (-999..999) | RO | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-only · current Pump suction or static pressure
Example values from LibreNMS test devices
| |||||||||||||||||
| Stemp-amb | 1.3.6.1.4.1.9839.2.1.2.81 | Integer32 (-999..999) | RO | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-only · current Ambient temperature
Example values from LibreNMS test devices
| |||||||||||||||||
| Stemp-fc | 1.3.6.1.4.1.9839.2.1.2.82 | Integer32 (-999..999) | RO | 0 | |||||||||||||
scalar · Integer32 (-999..999) · read-only · current Inlet - freecooling temperature
Example values from LibreNMS test devices
| |||||||||||||||||
| Spp1 | 1.3.6.1.4.1.9839.2.1.2.90 | Integer32 (0..100) | RO | 1000 | |||||||||||||
scalar · Integer32 (0..100) · read-only · current Pump 1 speed
Example values from LibreNMS test devices
| |||||||||||||||||
| Spp2 | 1.3.6.1.4.1.9839.2.1.2.91 | Integer32 (0..100) | RO | 0 | |||||||||||||
scalar · Integer32 (0..100) · read-only · current Pump 2 speed
Example values from LibreNMS test devices
| |||||||||||||||||
| Scooling-capacity | 1.3.6.1.4.1.9839.2.1.2.100 | Integer32 (0..9999) | RO | 339 | |||||||||||||
scalar · Integer32 (0..9999) · read-only · current Cooling Capacity
Example values from LibreNMS test devices
| |||||||||||||||||
| Sfreecooling-capacity | 1.3.6.1.4.1.9839.2.1.2.101 | Integer32 (0..9999) | RO | 0 | |||||||||||||
scalar · Integer32 (0..9999) · read-only · current FreeCooling Capacity
Example values from LibreNMS test devices
| |||||||||||||||||
| Stotal-capacity | 1.3.6.1.4.1.9839.2.1.2.102 | Integer32 (0..9999) | RO | 339 | |||||||||||||
scalar · Integer32 (0..9999) · read-only · current TotalCooling Capacity
Example values from LibreNMS test devices
| |||||||||||||||||
| NintegerObjects | 1.3.6.1.4.1.9839.2.1.3 | ||||||||||||||||
| Sip-Address1 | 1.3.6.1.4.1.9839.2.1.3.6 | Integer32 (1..255) | RO | 0 | |||||||||||||
scalar · Integer32 (1..255) · read-only · current IP Address 1 (XXX.xxx.xxx.xxx)
Example values from LibreNMS test devices
| |||||||||||||||||
| Sip-Address2 | 1.3.6.1.4.1.9839.2.1.3.7 | Integer32 (1..255) | RO | 0 | |||||||||||||
scalar · Integer32 (1..255) · read-only · current IP Address 2 (xxx.XXX.xxx.xxx)
Example values from LibreNMS test devices
| |||||||||||||||||
| Sip-Address3 | 1.3.6.1.4.1.9839.2.1.3.8 | Integer32 (1..255) | RO | 0 | |||||||||||||
scalar · Integer32 (1..255) · read-only · current IP Address 3 (xxx.xxx.XXX.xxx)
Example values from LibreNMS test devices
| |||||||||||||||||
| Sip-Address4 | 1.3.6.1.4.1.9839.2.1.3.9 | Integer32 (1..255) | RO | 0 | |||||||||||||
scalar · Integer32 (1..255) · read-only · current IP Address 4 (xxx.xxx.xxx.XXX)
Example values from LibreNMS test devices
| |||||||||||||||||
| SnetMask | 1.3.6.1.4.1.9839.2.1.3.10 | Integer32 (8..32) | RO | 0 | |||||||||||||
scalar · Integer32 (8..32) · read-only · current NetMask 8-16-24-32
Example values from LibreNMS test devices
| |||||||||||||||||
| Sgateway1 | 1.3.6.1.4.1.9839.2.1.3.11 | Integer32 (1..255) | RO | 0 | |||||||||||||
scalar · Integer32 (1..255) · read-only · current Gateway 1 (XXX.xxx.xxx.xxx)
Example values from LibreNMS test devices
| |||||||||||||||||
| Sgateway2 | 1.3.6.1.4.1.9839.2.1.3.12 | Integer32 (1..255) | RO | 0 | |||||||||||||
scalar · Integer32 (1..255) · read-only · current Gateway 2 (xxx.XXX.xxx.xxx)
Example values from LibreNMS test devices
| |||||||||||||||||
| Sgateway3 | 1.3.6.1.4.1.9839.2.1.3.13 | Integer32 (1..255) | RO | 0 | |||||||||||||
scalar · Integer32 (1..255) · read-only · current Gateway 3 (xxx.xxx.XXX.xxx)
Example values from LibreNMS test devices
| |||||||||||||||||
| Sgateway4 | 1.3.6.1.4.1.9839.2.1.3.14 | Integer32 (1..255) | RO | 0 | |||||||||||||
scalar · Integer32 (1..255) · read-only · current Gateway 4 (xxx.xxx.xxx.XXX)
Example values from LibreNMS test devices
| |||||||||||||||||
| Sdns1-1 | 1.3.6.1.4.1.9839.2.1.3.15 | Integer32 (1..255) | RO | 0 | |||||||||||||
scalar · Integer32 (1..255) · read-only · current DNS (1) 1 (XXX.xxx.xxx.xxx)
Example values from LibreNMS test devices
| |||||||||||||||||
| Sdns1-2 | 1.3.6.1.4.1.9839.2.1.3.16 | Integer32 (1..255) | RO | 0 | |||||||||||||
scalar · Integer32 (1..255) · read-only · current DNS (1) 2 (xxx.XXX.xxx.xxx)
Example values from LibreNMS test devices
| |||||||||||||||||
| Sdns1-3 | 1.3.6.1.4.1.9839.2.1.3.17 | Integer32 (1..255) | RO | 0 | |||||||||||||
scalar · Integer32 (1..255) · read-only · current DNS (1) 3 (xxx.xxx.XXX.xxx)
Example values from LibreNMS test devices
| |||||||||||||||||
| Sdns1-4 | 1.3.6.1.4.1.9839.2.1.3.18 | Integer32 (1..255) | RO | 0 | |||||||||||||
scalar · Integer32 (1..255) · read-only · current DNS (1) 4 (xxx.xxx.xxx.XXX)
Example values from LibreNMS test devices
| |||||||||||||||||
| Sdns2-1 | 1.3.6.1.4.1.9839.2.1.3.19 | Integer32 (1..255) | RO | 0 | |||||||||||||
scalar · Integer32 (1..255) · read-only · current DNS (2) 1 (XXX.xxx.xxx.xxx)
Example values from LibreNMS test devices
| |||||||||||||||||
| Sdns2-2 | 1.3.6.1.4.1.9839.2.1.3.20 | Integer32 (1..255) | RO | 0 | |||||||||||||
scalar · Integer32 (1..255) · read-only · current DNS (2) 2 (xxx.XXX.xxx.xxx)
Example values from LibreNMS test devices
| |||||||||||||||||
| Sdns2-3 | 1.3.6.1.4.1.9839.2.1.3.21 | Integer32 (1..255) | RO | 0 | |||||||||||||
scalar · Integer32 (1..255) · read-only · current DNS (2) 3 (xxx.xxx.XXX.xxx)
Example values from LibreNMS test devices
| |||||||||||||||||
| Sdns2-4 | 1.3.6.1.4.1.9839.2.1.3.22 | Integer32 (1..255) | RO | 0 | |||||||||||||
scalar · Integer32 (1..255) · read-only · current DNS (2) 4 (xxx.xxx.xxx.XXX)
Example values from LibreNMS test devices
| |||||||||||||||||
| Sip-Address1-Out | 1.3.6.1.4.1.9839.2.1.3.26 | Integer32 (1..255) | RO | 0 | |||||||||||||
scalar · Integer32 (1..255) · read-only · current IP Address Out 1 (XXX.xxx.xxx.xxx)
Example values from LibreNMS test devices
| |||||||||||||||||
| Sip-Address2-Out | 1.3.6.1.4.1.9839.2.1.3.27 | Integer32 (1..255) | RO | 0 | |||||||||||||
scalar · Integer32 (1..255) · read-only · current IP Address Out 2 (xxx.XXX.xxx.xxx)
Example values from LibreNMS test devices
| |||||||||||||||||
| Sip-Address3-Out | 1.3.6.1.4.1.9839.2.1.3.28 | Integer32 (1..255) | RO | 0 | |||||||||||||
scalar · Integer32 (1..255) · read-only · current IP Address Out 3 (xxx.xxx.XXX.xxx)
Example values from LibreNMS test devices
| |||||||||||||||||
| Sip-Address4-Out | 1.3.6.1.4.1.9839.2.1.3.29 | Integer32 (1..255) | RO | 0 | |||||||||||||
scalar · Integer32 (1..255) · read-only · current IP Address Out 4 (xxx.xxx.xxx.XXX)
Example values from LibreNMS test devices
| |||||||||||||||||
| Sstarting-delay-Second-Pump | 1.3.6.1.4.1.9839.2.1.3.30 | Integer32 (0..99) | RW | 0 | |||||||||||||
scalar · Integer32 (0..99) · read-write · current Starting delay Second Pump
Example values from LibreNMS test devices
| |||||||||||||||||
| Sstarting-delay-btw-Pump-Compressor | 1.3.6.1.4.1.9839.2.1.3.31 | Integer32 (0..32767) | RW | 0 | |||||||||||||
scalar · Integer32 (0..32767) · read-write · current Starting delay btw Pump - Compressor
Example values from LibreNMS test devices
| |||||||||||||||||
| Soverlap-time-Pumps | 1.3.6.1.4.1.9839.2.1.3.32 | Integer32 (0..999) | RW | 0 | |||||||||||||
scalar · Integer32 (0..999) · read-write · current Overlap time Pumps
Example values from LibreNMS test devices
| |||||||||||||||||
| Sworking-time-Pumps | 1.3.6.1.4.1.9839.2.1.3.33 | Integer32 (1..9999) | RW | 0 | |||||||||||||
scalar · Integer32 (1..9999) · read-write · current Working time Pumps
Example values from LibreNMS test devices
| |||||||||||||||||
| Srunning-time-Chillers | 1.3.6.1.4.1.9839.2.1.3.34 | Integer32 (0..32767) | RW | 0 | |||||||||||||
scalar · Integer32 (0..32767) · read-write · current Running time Chillers
Example values from LibreNMS test devices
| |||||||||||||||||
| Soverlap-time-Chillers | 1.3.6.1.4.1.9839.2.1.3.35 | Integer32 (0..32767) | RW | 0 | |||||||||||||
scalar · Integer32 (0..32767) · read-write · current Overlap time Chillers
Example values from LibreNMS test devices
| |||||||||||||||||
| Sn-chillers-Max | 1.3.6.1.4.1.9839.2.1.3.36 | Integer32 (1..8) | RW | 0 | |||||||||||||
scalar · Integer32 (1..8) · read-write · current N chillers Max
Example values from LibreNMS test devices
| |||||||||||||||||
| Sn-chillers-ON | 1.3.6.1.4.1.9839.2.1.3.37 | Integer32 (1..8) | RW | 0 | |||||||||||||
scalar · Integer32 (1..8) · read-write · current N chillers ON
Example values from LibreNMS test devices
| |||||||||||||||||
| Sn-pumps-ON | 1.3.6.1.4.1.9839.2.1.3.38 | Integer32 (1..8) | RW | 0 | |||||||||||||
scalar · Integer32 (1..8) · read-write · current N pumps ON
Example values from LibreNMS test devices
| |||||||||||||||||
| Stime-Enable-Pumps-Chiller-Offline | 1.3.6.1.4.1.9839.2.1.3.39 | Integer32 (0..999) | RW | 0 | |||||||||||||
scalar · Integer32 (0..999) · read-write · current Time Enable Pumps - Chiller Offline
Example values from LibreNMS test devices
| |||||||||||||||||
| Stime-Running-Pumps-Chiller-Offline | 1.3.6.1.4.1.9839.2.1.3.40 | Integer32 (0..9999) | RW | 0 | |||||||||||||
scalar · Integer32 (0..9999) · read-write · current Time Running Pumps - Chiller Offline
Example values from LibreNMS test devices
| |||||||||||||||||
| Sintegral-Time-3Way-Valve-Hydraulic-PID | 1.3.6.1.4.1.9839.2.1.3.41 | Integer32 (0..999) | RW | 0 | |||||||||||||
scalar · Integer32 (0..999) · read-write · current Integral Time 3Way Valve Hydraulic (PID)
Example values from LibreNMS test devices
| |||||||||||||||||
| Sderivative-Time-3Way-Valve-Hydraulic-PID | 1.3.6.1.4.1.9839.2.1.3.42 | Integer32 (0..999) | RW | 0 | |||||||||||||
scalar · Integer32 (0..999) · read-write · current Derivative Time 3Way Valve Hydraulic (PID)
Example values from LibreNMS test devices
| |||||||||||||||||
| Soutput-Address-3Way-Valve-Hydraulic | 1.3.6.1.4.1.9839.2.1.3.43 | Integer32 (0..6) | RW | 0 | |||||||||||||
scalar · Integer32 (0..6) · read-write · current Output Address 3Way Valve Hydraulic
Example values from LibreNMS test devices
| |||||||||||||||||
| Stime-Speed-Up-FCM | 1.3.6.1.4.1.9839.2.1.3.44 | Integer32 (0..99) | RW | 0 | |||||||||||||
scalar · Integer32 (0..99) · read-write · current Time Speed-Up (FCM)
Example values from LibreNMS test devices
| |||||||||||||||||
| Stime-Soft-Start-FCM | 1.3.6.1.4.1.9839.2.1.3.45 | Integer32 (0..100) | RW | 0 | |||||||||||||
scalar · Integer32 (0..100) · read-write · current Time Soft-Start (FCM)
Example values from LibreNMS test devices
| |||||||||||||||||
| Sdelay-Freecooling | 1.3.6.1.4.1.9839.2.1.3.47 | Integer32 (0..9999) | RW | 0 | |||||||||||||
scalar · Integer32 (0..9999) · read-write · current Delay Freecooling
Example values from LibreNMS test devices
| |||||||||||||||||
| Sintegral-Time-Freeccoling-PID | 1.3.6.1.4.1.9839.2.1.3.48 | Integer32 (0..999) | RW | 0 | |||||||||||||
scalar · Integer32 (0..999) · read-write · current Integral Time Freeccoling (PID)
Example values from LibreNMS test devices
| |||||||||||||||||
| Sderivative-Time-Freeccoling-PID | 1.3.6.1.4.1.9839.2.1.3.49 | Integer32 (0..999) | RW | 0 | |||||||||||||
scalar · Integer32 (0..999) · read-write · current Derivative Time Freeccoling (PID)
Example values from LibreNMS test devices
| |||||||||||||||||
| Stime-Min-On-Freecooling-Chiller-timing | 1.3.6.1.4.1.9839.2.1.3.50 | Integer32 (0..32767) | RW | 0 | |||||||||||||
scalar · Integer32 (0..32767) · read-write · current Time Min. On (Freecooling - Chiller timing)
Example values from LibreNMS test devices
| |||||||||||||||||
| Stime-Min-Off-Freecooling-Chiller-timing | 1.3.6.1.4.1.9839.2.1.3.51 | Integer32 (0..32767) | RW | 0 | |||||||||||||
scalar · Integer32 (0..32767) · read-write · current Time Min. Off (Freecooling - Chiller timing)
Example values from LibreNMS test devices
| |||||||||||||||||
| Stime-Min-Different-Freecooling-Chiller-timing | 1.3.6.1.4.1.9839.2.1.3.52 | Integer32 (0..32767) | RW | 0 | |||||||||||||
scalar · Integer32 (0..32767) · read-write · current Time Min. Different (Freecooling - Chiller timing)
Example values from LibreNMS test devices
| |||||||||||||||||
| Stime-Min-Same-Freecooling-Chiller-timing | 1.3.6.1.4.1.9839.2.1.3.53 | Integer32 (0..32767) | RW | 0 | |||||||||||||
scalar · Integer32 (0..32767) · read-write · current Time Min. Same (Freecooling - Chiller timing)
Example values from LibreNMS test devices
| |||||||||||||||||
| Sintegral-Time-Freeccoling-Valve-PID | 1.3.6.1.4.1.9839.2.1.3.54 | Integer32 (0..999) | RW | 0 | |||||||||||||
scalar · Integer32 (0..999) · read-write · current Integral Time Freeccoling Valve (PID)
Example values from LibreNMS test devices
| |||||||||||||||||
| Sderivative-Time-Freeccoling-Valve-PID | 1.3.6.1.4.1.9839.2.1.3.55 | Integer32 (0..999) | RW | 0 | |||||||||||||
scalar · Integer32 (0..999) · read-write · current Derivative Time Freeccoling Valve (PID)
Example values from LibreNMS test devices
| |||||||||||||||||
| Soutput-Address-Valve-Freecooling | 1.3.6.1.4.1.9839.2.1.3.56 | Integer32 (0..6) | RW | 0 | |||||||||||||
scalar · Integer32 (0..6) · read-write · current Output Address Valve Freecooling
Example values from LibreNMS test devices
| |||||||||||||||||
| Sdelay-Freecooling-Thermal-Exclusion | 1.3.6.1.4.1.9839.2.1.3.57 | Integer32 (0..999) | RW | 0 | |||||||||||||
scalar · Integer32 (0..999) · read-write · current Delay Freecoolimg Thermal Exclusion
Example values from LibreNMS test devices
| |||||||||||||||||
| Sn-of-alarm-External-Dry-Cooler | 1.3.6.1.4.1.9839.2.1.3.58 | Integer32 (0..9) | RW | 0 | |||||||||||||
scalar · Integer32 (0..9) · read-write · current N of alarm (External Dry-Cooler)
Example values from LibreNMS test devices
| |||||||||||||||||
| Sdelay-Alarm-Static-Pressure | 1.3.6.1.4.1.9839.2.1.3.59 | Integer32 (0..99) | RW | 0 | |||||||||||||
scalar · Integer32 (0..99) · read-write · current Delay Alarm (Static Pressure)
Example values from LibreNMS test devices
| |||||||||||||||||
| Sn-of-Alarm-Static-Pressure | 1.3.6.1.4.1.9839.2.1.3.60 | Integer32 (1..10) | RW | 0 | |||||||||||||
scalar · Integer32 (1..10) · read-write · current N of Alarm (Static Pressure)
Example values from LibreNMS test devices
| |||||||||||||||||
| Sdelay-Warning-Static-Pressure | 1.3.6.1.4.1.9839.2.1.3.61 | Integer32 (0..99) | RW | 0 | |||||||||||||
scalar · Integer32 (0..99) · read-write · current Delay Warning (Static Pressure)
Example values from LibreNMS test devices
| |||||||||||||||||
| Sn-of-Warning-Static-Pressure | 1.3.6.1.4.1.9839.2.1.3.62 | Integer32 (1..10) | RW | 0 | |||||||||||||
scalar · Integer32 (1..10) · read-write · current N of Warning (Static Pressure)
Example values from LibreNMS test devices
| |||||||||||||||||
| Sn-of-Alarm-Differential-Pressure | 1.3.6.1.4.1.9839.2.1.3.63 | Integer32 (1..10) | RW | 0 | |||||||||||||
scalar · Integer32 (1..10) · read-write · current N of Alarm (Differential Pressure)
Example values from LibreNMS test devices
| |||||||||||||||||
| Spriming-Time-Hydraulic-Pressure | 1.3.6.1.4.1.9839.2.1.3.64 | Integer32 (0..99) | RW | 0 | |||||||||||||
scalar · Integer32 (0..99) · read-write · current Priming Time (Hydraulic Pressure)
Example values from LibreNMS test devices
| |||||||||||||||||
| Sdelay-priming-Time-Hydraulic-Pressure | 1.3.6.1.4.1.9839.2.1.3.65 | Integer32 (0..99) | RW | 0 | |||||||||||||
scalar · Integer32 (0..99) · read-write · current Delay Priming Time (Hydraulic Pressure)
Example values from LibreNMS test devices
| |||||||||||||||||
| Soutput-Address-Alarm-Static-Pressure | 1.3.6.1.4.1.9839.2.1.3.66 | Integer32 (0..18) | RW | 0 | |||||||||||||
scalar · Integer32 (0..18) · read-write · current Output Address Alarm (Static Pressure)
Example values from LibreNMS test devices
| |||||||||||||||||
| Sn-of-Alarm-Flow-Rate | 1.3.6.1.4.1.9839.2.1.3.67 | Integer32 (1..10) | RW | 0 | |||||||||||||
scalar · Integer32 (1..10) · read-write · current N of Alarm (Flow Rate)
Example values from LibreNMS test devices
| |||||||||||||||||
| Spriming-Time-Flow-Rate | 1.3.6.1.4.1.9839.2.1.3.68 | Integer32 (0..99) | RW | 0 | |||||||||||||
scalar · Integer32 (0..99) · read-write · current Priming Time (Flow Rate)
Example values from LibreNMS test devices
| |||||||||||||||||
| Sdelay-priming-Time-Flow-Rate | 1.3.6.1.4.1.9839.2.1.3.69 | Integer32 (0..99) | RW | 0 | |||||||||||||
scalar · Integer32 (0..99) · read-write · current Delay Priming Time (Flow Rate)
Example values from LibreNMS test devices
| |||||||||||||||||
| Sbms-address-IDENT | 1.3.6.1.4.1.9839.2.1.3.70 | Integer32 (1..200) | RO | 0 | |||||||||||||
scalar · Integer32 (1..200) · read-only · current BMS address (IDENT)
Example values from LibreNMS test devices
| |||||||||||||||||
| Schiller-name0 | 1.3.6.1.4.1.9839.2.1.3.99 | Integer32 (0..9999) | RO | 0 | |||||||||||||
scalar · Integer32 (0..9999) · read-only · current Chiller Model - Article Number - 0
Example values from LibreNMS test devices
| |||||||||||||||||
| Schiller-name1 | 1.3.6.1.4.1.9839.2.1.3.100 | Integer32 (0..999) | RO | 0 | |||||||||||||
scalar · Integer32 (0..999) · read-only · current Chiller Model - Article Number - 1
Example values from LibreNMS test devices
| |||||||||||||||||
| Scurrent-day | 1.3.6.1.4.1.9839.2.1.3.123 | Integer32 (1..31) | RO | 0 | |||||||||||||
scalar · Integer32 (1..31) · read-only · current Current Day
Example values from LibreNMS test devices
| |||||||||||||||||
| Scurrent-month | 1.3.6.1.4.1.9839.2.1.3.124 | Integer32 (1..12) | RO | 0 | |||||||||||||
scalar · Integer32 (1..12) · read-only · current Current Month
Example values from LibreNMS test devices
| |||||||||||||||||
| Scurrent-year | 1.3.6.1.4.1.9839.2.1.3.125 | Integer32 (0..99) | RO | 0 | |||||||||||||
scalar · Integer32 (0..99) · read-only · current Current Year
Example values from LibreNMS test devices
| |||||||||||||||||
| Scurrent-hour | 1.3.6.1.4.1.9839.2.1.3.126 | Integer32 (0..23) | RO | 0 | |||||||||||||
scalar · Integer32 (0..23) · read-only · current Current Hour
Example values from LibreNMS test devices
| |||||||||||||||||
| Scurrent-minute | 1.3.6.1.4.1.9839.2.1.3.127 | Integer32 (0..59) | RO | 0 | |||||||||||||
scalar · Integer32 (0..59) · read-only · current Current Minute
Example values from LibreNMS test devices
| |||||||||||||||||
| Schiller-mode-operation | 1.3.6.1.4.1.9839.2.1.3.150 | Integer32 (0..4) | RO | 0 | |||||||||||||
scalar · Integer32 (0..4) · read-only · current Chiller mode operation
Example values from LibreNMS test devices
| |||||||||||||||||
| NtrapObjects | 1.3.6.1.4.1.9839.2.1.100 | ||||||||||||||||
| !high-pressure-switch-1-alarm | 1.3.6.1.4.1.9839.2.1.100.1 | ||||||||||||||||
notification · current High pressure switch 1 alarm | |||||||||||||||||
| !high-pressure-switch-2-alarm | 1.3.6.1.4.1.9839.2.1.100.2 | ||||||||||||||||
notification · current High pressure switch 2 alarm | |||||||||||||||||
| !low-pressure-switch-1-alarm | 1.3.6.1.4.1.9839.2.1.100.3 | ||||||||||||||||
notification · current Low pressure switch 1 alarm | |||||||||||||||||
| !low-pressure-switch-2-alarm | 1.3.6.1.4.1.9839.2.1.100.4 | ||||||||||||||||
notification · current Low pressure switch 2 alarm | |||||||||||||||||
| !water-level-alarm | 1.3.6.1.4.1.9839.2.1.100.6 | ||||||||||||||||
notification · current Water level alarm | |||||||||||||||||
| !flow-switch-alarm | 1.3.6.1.4.1.9839.2.1.100.8 | ||||||||||||||||
notification · current Flow switch alarm | |||||||||||||||||
| !water-static-pressure-alarm | 1.3.6.1.4.1.9839.2.1.100.9 | ||||||||||||||||
notification · current Water static pressure alarm | |||||||||||||||||
| !water-static-pressure-warning | 1.3.6.1.4.1.9839.2.1.100.10 | ||||||||||||||||
notification · current Water static pressure warning | |||||||||||||||||
| !flow-rate-alarm | 1.3.6.1.4.1.9839.2.1.100.11 | ||||||||||||||||
notification · current Flow rate alarm | |||||||||||||||||
| !overload-compressor1-circuit1-alarm | 1.3.6.1.4.1.9839.2.1.100.12 | ||||||||||||||||
notification · current Overload compressor 1 circuit 1 alarm | |||||||||||||||||
| !overload-compressor2-circuit1-alarm | 1.3.6.1.4.1.9839.2.1.100.13 | ||||||||||||||||
notification · current Overload compressor 2 circuit 1 alarm | |||||||||||||||||
| !overload-compressor3-circuit1-alarm | 1.3.6.1.4.1.9839.2.1.100.14 | ||||||||||||||||
notification · current Overload compressor 3 circuit 1 alarm | |||||||||||||||||
| !overload-compressor1-circuit2-alarm | 1.3.6.1.4.1.9839.2.1.100.15 | ||||||||||||||||
notification · current Overload compressor 1 circuit 2 alarm | |||||||||||||||||
| !overload-compressor2-circuit2-alarm | 1.3.6.1.4.1.9839.2.1.100.16 | ||||||||||||||||
notification · current Overload compressor 2 circuit 2 alarm | |||||||||||||||||
| !overload-compressor3-circuit2-alarm | 1.3.6.1.4.1.9839.2.1.100.17 | ||||||||||||||||
notification · current Overload compressor 3 circuit 2 alarm | |||||||||||||||||
| !overload-fans-circuit1 | 1.3.6.1.4.1.9839.2.1.100.18 | ||||||||||||||||
notification · current Overload fans circuit 1 | |||||||||||||||||
| !overload-fans-circuit2 | 1.3.6.1.4.1.9839.2.1.100.19 | ||||||||||||||||
notification · current Overload fans circuit 2 | |||||||||||||||||
| !overload-fan1-circuit1-alarm | 1.3.6.1.4.1.9839.2.1.100.20 | ||||||||||||||||
notification · current Overload fan 1 circuit 1 alarm | |||||||||||||||||
| !overload-fan2-circuit1-alarm | 1.3.6.1.4.1.9839.2.1.100.21 | ||||||||||||||||
notification · current Overload fan 2 circuit 1 alarm | |||||||||||||||||
| !overload-fan3-circuit1-alarm | 1.3.6.1.4.1.9839.2.1.100.22 | ||||||||||||||||
notification · current Overload fan 3 circuit 1 alarm | |||||||||||||||||
| !overload-fan4-circuit1-alarm | 1.3.6.1.4.1.9839.2.1.100.23 | ||||||||||||||||
notification · current Overload fan 4 circuit 1 alarm | |||||||||||||||||
| !overload-fan1-circuit-2-alarm | 1.3.6.1.4.1.9839.2.1.100.24 | ||||||||||||||||
notification · current Overload fan 1 circuit 2 alarm | |||||||||||||||||
| !overload-fan2-circuit2-alarm | 1.3.6.1.4.1.9839.2.1.100.25 | ||||||||||||||||
notification · current Overload fan 2 circuit 2 alarm | |||||||||||||||||
| !overload-fan3-circuit2-alarm | 1.3.6.1.4.1.9839.2.1.100.26 | ||||||||||||||||
notification · current Overload fan 3 circuit 2 alarm | |||||||||||||||||
| !overload-fan4-circuit2-alarm | 1.3.6.1.4.1.9839.2.1.100.27 | ||||||||||||||||
notification · current Overload fan 4 circuit 2 alarm | |||||||||||||||||
| !overload-pump1-alarm | 1.3.6.1.4.1.9839.2.1.100.28 | ||||||||||||||||
notification · current Overload pump 1 alarm | |||||||||||||||||
| !overload-pump2-alarm | 1.3.6.1.4.1.9839.2.1.100.29 | ||||||||||||||||
notification · current Overload pump 2 alarm | |||||||||||||||||
| !wrong-phase-rotation-alarm | 1.3.6.1.4.1.9839.2.1.100.30 | ||||||||||||||||
notification · current Wrong phase rotation alarm | |||||||||||||||||
| !back-Door-open-alarm | 1.3.6.1.4.1.9839.2.1.100.31 | ||||||||||||||||
notification · current Back Door open alarm | |||||||||||||||||
| !alarm-idrofrigo-pump-c-1 | 1.3.6.1.4.1.9839.2.1.100.75 | ||||||||||||||||
notification · current Condensation pump 1 breaker switch alarm | |||||||||||||||||
| !alarm-idrofrigo-pump-c-2 | 1.3.6.1.4.1.9839.2.1.100.76 | ||||||||||||||||
notification · current Condensation pump 2 breaker switch alarm | |||||||||||||||||
| !alarm-idrofrigo-fl-C | 1.3.6.1.4.1.9839.2.1.100.80 | ||||||||||||||||
notification · current Condensation flow switch alarm | |||||||||||||||||
| !remote-on-off | 1.3.6.1.4.1.9839.2.1.100.130 | ||||||||||||||||
notification · current Remote on-off | |||||||||||||||||
| !chiller-ON-OFF | 1.3.6.1.4.1.9839.2.1.100.131 | ||||||||||||||||
notification · current Chiller ON/OFF | |||||||||||||||||
| !alarm-disch-scw-1 | 1.3.6.1.4.1.9839.2.1.100.148 | ||||||||||||||||
notification · current Discharge screw compressor 1 alarm | |||||||||||||||||
| !alarm-disch-scw-2 | 1.3.6.1.4.1.9839.2.1.100.149 | ||||||||||||||||
notification · current Discharge screw compressor 2 alarm | |||||||||||||||||
| !alarm-probe-inlet | 1.3.6.1.4.1.9839.2.1.100.150 | ||||||||||||||||
notification · current Inlet probe alarm (broken or disconnected) | |||||||||||||||||
| !alarm-probe-amb | 1.3.6.1.4.1.9839.2.1.100.151 | ||||||||||||||||
notification · current Ambient probe alarm (broken or disconnected) | |||||||||||||||||
| !alarm-frigo-fl1 | 1.3.6.1.4.1.9839.2.1.100.152 | ||||||||||||||||
notification · current Flow switch alarm (cooling alarm) | |||||||||||||||||
| !alarm-idro-pump1 | 1.3.6.1.4.1.9839.2.1.100.153 | ||||||||||||||||
notification · current Pump 1 hydraulic alarm | |||||||||||||||||
| !alarm-idro-pump2 | 1.3.6.1.4.1.9839.2.1.100.154 | ||||||||||||||||
notification · current Pump 2 hydraulic alarm | |||||||||||||||||
| !alarm-idro-fl1 | 1.3.6.1.4.1.9839.2.1.100.155 | ||||||||||||||||
notification · current Flow switch alarm (hydraulic alarm) | |||||||||||||||||
| !alarm-warning-fl1 | 1.3.6.1.4.1.9839.2.1.100.156 | ||||||||||||||||
notification · current Flow switch alarm (warning alarm) | |||||||||||||||||
| !alarm-hi-water-temp | 1.3.6.1.4.1.9839.2.1.100.157 | ||||||||||||||||
notification · current High Temperature alarm | |||||||||||||||||
| !alarm-lo-water-temp | 1.3.6.1.4.1.9839.2.1.100.158 | ||||||||||||||||
notification · current Low Temperature alarm | |||||||||||||||||
| !alarm-ta-probe1 | 1.3.6.1.4.1.9839.2.1.100.159 | ||||||||||||||||
notification · current Antifreeze/evaporator probe 1 alarm | |||||||||||||||||
| !alarm-hi-press | 1.3.6.1.4.1.9839.2.1.100.160 | ||||||||||||||||
notification · current High condensation pressure alarm | |||||||||||||||||
| !alarm-lo-press | 1.3.6.1.4.1.9839.2.1.100.161 | ||||||||||||||||
notification · current Low condensation pressure alarm | |||||||||||||||||
| !alarm-probe-evap-1 | 1.3.6.1.4.1.9839.2.1.100.162 | ||||||||||||||||
notification · current Antifreeze/evaporator probe 1 alarm (broken or disconnected) | |||||||||||||||||
| !alarm-probe-evap-2 | 1.3.6.1.4.1.9839.2.1.100.163 | ||||||||||||||||
notification · current Antifreeze/evaporator probe 2 alarm (broken or disconnected) | |||||||||||||||||
| !alarm-hi-press-1 | 1.3.6.1.4.1.9839.2.1.100.164 | ||||||||||||||||
notification · current High condensation pressure 1 alarm | |||||||||||||||||
| !alarm-hi-press-2 | 1.3.6.1.4.1.9839.2.1.100.165 | ||||||||||||||||
notification · current High condensation pressure 2 alarm | |||||||||||||||||
| !alarm-lo-press-1 | 1.3.6.1.4.1.9839.2.1.100.166 | ||||||||||||||||
notification · current Low condensation pressure 1 alarm | |||||||||||||||||
| !alarm-lo-press-2 | 1.3.6.1.4.1.9839.2.1.100.167 | ||||||||||||||||
notification · current Low condensation pressure 2 alarm | |||||||||||||||||
| !alarm-probe-tank | 1.3.6.1.4.1.9839.2.1.100.168 | ||||||||||||||||
notification · current Tank/Out probe alarm (broken or disconnected) | |||||||||||||||||
| !alarm-off-line-1 | 1.3.6.1.4.1.9839.2.1.100.169 | ||||||||||||||||
notification · current Chiller 1 offline | |||||||||||||||||
| !alarm-off-line-2 | 1.3.6.1.4.1.9839.2.1.100.170 | ||||||||||||||||
notification · current Chiller 2 offline | |||||||||||||||||
| !alarm-off-line-3 | 1.3.6.1.4.1.9839.2.1.100.171 | ||||||||||||||||
notification · current Chiller 3 offline | |||||||||||||||||
| !alarm-off-line-4 | 1.3.6.1.4.1.9839.2.1.100.172 | ||||||||||||||||
notification · current Chiller 4 offline | |||||||||||||||||
| !alarm-off-line-5 | 1.3.6.1.4.1.9839.2.1.100.173 | ||||||||||||||||
notification · current Chiller 5 offline | |||||||||||||||||
| !alarm-off-line-6 | 1.3.6.1.4.1.9839.2.1.100.174 | ||||||||||||||||
notification · current Chiller 6 offline | |||||||||||||||||
| !alarm-off-line-7 | 1.3.6.1.4.1.9839.2.1.100.175 | ||||||||||||||||
notification · current Chiller 7 offline | |||||||||||||||||
| !alarm-off-line-8 | 1.3.6.1.4.1.9839.2.1.100.176 | ||||||||||||||||
notification · current Chiller 8 offline | |||||||||||||||||
| !alarm-ta-probe2 | 1.3.6.1.4.1.9839.2.1.100.177 | ||||||||||||||||
notification · current Antifreeze/evaporator probe 2 alarm | |||||||||||||||||
| !alarm-sms | 1.3.6.1.4.1.9839.2.1.100.178 | ||||||||||||||||
notification · current SMS alarm | |||||||||||||||||
| !alarm-modem | 1.3.6.1.4.1.9839.2.1.100.179 | ||||||||||||||||
notification · current Modem alarm | |||||||||||||||||
| !alarm-sms-coda | 1.3.6.1.4.1.9839.2.1.100.180 | ||||||||||||||||
notification · current SMS coda alarm | |||||||||||||||||
| !alarm-probe-fc | 1.3.6.1.4.1.9839.2.1.100.181 | ||||||||||||||||
notification · current Freecooling probe alarm (broken or disconnected) | |||||||||||||||||
| !alarm-maint-pw1 | 1.3.6.1.4.1.9839.2.1.100.182 | ||||||||||||||||
notification · current Maintenance pump 1 alarm) | |||||||||||||||||
| !alarm-maint-pw2 | 1.3.6.1.4.1.9839.2.1.100.183 | ||||||||||||||||
notification · current Maintenance pump 2 alarm) | |||||||||||||||||
| !alarm-hi-temp-rid | 1.3.6.1.4.1.9839.2.1.100.184 | ||||||||||||||||
notification · current High temperature alarm (redundance) | |||||||||||||||||
| !alarm-q-fc-sep | 1.3.6.1.4.1.9839.2.1.100.185 | ||||||||||||||||
notification · current DryCooler breaker switch alarm | |||||||||||||||||
| !alarm-p-wat2 | 1.3.6.1.4.1.9839.2.1.100.186 | ||||||||||||||||
notification · current Water pressure 2 alarm | |||||||||||||||||
| !alarm-p-wat1 | 1.3.6.1.4.1.9839.2.1.100.187 | ||||||||||||||||
notification · current Water pressure 1 alarm | |||||||||||||||||
| !alarm-foult-flow-p1 | 1.3.6.1.4.1.9839.2.1.100.188 | ||||||||||||||||
notification · current Pump 1 flow alarm | |||||||||||||||||
| !alarm-foult-flow-p2 | 1.3.6.1.4.1.9839.2.1.100.189 | ||||||||||||||||
notification · current Pump 2 flow alarm | |||||||||||||||||
| !alarm-foult-fl1-p1 | 1.3.6.1.4.1.9839.2.1.100.190 | ||||||||||||||||
notification · current Pump 1 flow-switch alarm | |||||||||||||||||
| !alarm-foult-fl1-p2 | 1.3.6.1.4.1.9839.2.1.100.191 | ||||||||||||||||
notification · current Pump 2 flow-switch alarm | |||||||||||||||||
| !alarm-warning-le | 1.3.6.1.4.1.9839.2.1.100.192 | ||||||||||||||||
notification · current Water level warning | |||||||||||||||||
| !alarm-frigo-fl-C | 1.3.6.1.4.1.9839.2.1.100.193 | ||||||||||||||||
notification · current Flow switch condensation alarm (cooling alarm) | |||||||||||||||||
| !alarm-idro-pump-c-1 | 1.3.6.1.4.1.9839.2.1.100.194 | ||||||||||||||||
notification · current Pump 1 condensation hydraulic alarm | |||||||||||||||||
| !alarm-idro-pump-c-2 | 1.3.6.1.4.1.9839.2.1.100.195 | ||||||||||||||||
notification · current Pump 2 condensation hydraulic alarm | |||||||||||||||||
| !alarm-idro-fl-C | 1.3.6.1.4.1.9839.2.1.100.196 | ||||||||||||||||
notification · current Flow switch condensation alarm (hydraulic alarm) | |||||||||||||||||
| !alarm-warning-fl-C | 1.3.6.1.4.1.9839.2.1.100.197 | ||||||||||||||||
notification · current Flow switch condensation alarm (warning alarm) | |||||||||||||||||
| !alarm-foul-fl-C-p1 | 1.3.6.1.4.1.9839.2.1.100.198 | ||||||||||||||||
notification · current Pump 1 condensation flow-switch alarm | |||||||||||||||||
| !alarm-foul-fl-C-p2 | 1.3.6.1.4.1.9839.2.1.100.199 | ||||||||||||||||
notification · current Pump 2 condensation flow-switch alarm | |||||||||||||||||
Traps / Notifications
- alarm-disch-scw-1
1.3.6.1.4.1.9839.2.1.100.148 - alarm-disch-scw-2
1.3.6.1.4.1.9839.2.1.100.149 - alarm-foul-fl-C-p1
1.3.6.1.4.1.9839.2.1.100.198 - alarm-foul-fl-C-p2
1.3.6.1.4.1.9839.2.1.100.199 - alarm-foult-fl1-p1
1.3.6.1.4.1.9839.2.1.100.190 - alarm-foult-fl1-p2
1.3.6.1.4.1.9839.2.1.100.191 - alarm-foult-flow-p1
1.3.6.1.4.1.9839.2.1.100.188 - alarm-foult-flow-p2
1.3.6.1.4.1.9839.2.1.100.189 - alarm-frigo-fl1
1.3.6.1.4.1.9839.2.1.100.152 - alarm-frigo-fl-C
1.3.6.1.4.1.9839.2.1.100.193 - alarm-hi-press
1.3.6.1.4.1.9839.2.1.100.160 - alarm-hi-press-1
1.3.6.1.4.1.9839.2.1.100.164 - alarm-hi-press-2
1.3.6.1.4.1.9839.2.1.100.165 - alarm-hi-temp-rid
1.3.6.1.4.1.9839.2.1.100.184 - alarm-hi-water-temp
1.3.6.1.4.1.9839.2.1.100.157 - alarm-idro-fl1
1.3.6.1.4.1.9839.2.1.100.155 - alarm-idro-fl-C
1.3.6.1.4.1.9839.2.1.100.196 - alarm-idro-pump1
1.3.6.1.4.1.9839.2.1.100.153 - alarm-idro-pump2
1.3.6.1.4.1.9839.2.1.100.154 - alarm-idro-pump-c-1
1.3.6.1.4.1.9839.2.1.100.194 - alarm-idro-pump-c-2
1.3.6.1.4.1.9839.2.1.100.195 - alarm-idrofrigo-fl-C
1.3.6.1.4.1.9839.2.1.100.80 - alarm-idrofrigo-pump-c-1
1.3.6.1.4.1.9839.2.1.100.75 - alarm-idrofrigo-pump-c-2
1.3.6.1.4.1.9839.2.1.100.76 - alarm-lo-press
1.3.6.1.4.1.9839.2.1.100.161 - alarm-lo-press-1
1.3.6.1.4.1.9839.2.1.100.166 - alarm-lo-press-2
1.3.6.1.4.1.9839.2.1.100.167 - alarm-lo-water-temp
1.3.6.1.4.1.9839.2.1.100.158 - alarm-maint-pw1
1.3.6.1.4.1.9839.2.1.100.182 - alarm-maint-pw2
1.3.6.1.4.1.9839.2.1.100.183 - alarm-modem
1.3.6.1.4.1.9839.2.1.100.179 - alarm-off-line-1
1.3.6.1.4.1.9839.2.1.100.169 - alarm-off-line-2
1.3.6.1.4.1.9839.2.1.100.170 - alarm-off-line-3
1.3.6.1.4.1.9839.2.1.100.171 - alarm-off-line-4
1.3.6.1.4.1.9839.2.1.100.172 - alarm-off-line-5
1.3.6.1.4.1.9839.2.1.100.173 - alarm-off-line-6
1.3.6.1.4.1.9839.2.1.100.174 - alarm-off-line-7
1.3.6.1.4.1.9839.2.1.100.175 - alarm-off-line-8
1.3.6.1.4.1.9839.2.1.100.176 - alarm-p-wat1
1.3.6.1.4.1.9839.2.1.100.187 - alarm-p-wat2
1.3.6.1.4.1.9839.2.1.100.186 - alarm-probe-amb
1.3.6.1.4.1.9839.2.1.100.151 - alarm-probe-evap-1
1.3.6.1.4.1.9839.2.1.100.162 - alarm-probe-evap-2
1.3.6.1.4.1.9839.2.1.100.163 - alarm-probe-fc
1.3.6.1.4.1.9839.2.1.100.181 - alarm-probe-inlet
1.3.6.1.4.1.9839.2.1.100.150 - alarm-probe-tank
1.3.6.1.4.1.9839.2.1.100.168 - alarm-q-fc-sep
1.3.6.1.4.1.9839.2.1.100.185 - alarm-sms
1.3.6.1.4.1.9839.2.1.100.178 - alarm-sms-coda
1.3.6.1.4.1.9839.2.1.100.180 - alarm-ta-probe1
1.3.6.1.4.1.9839.2.1.100.159 - alarm-ta-probe2
1.3.6.1.4.1.9839.2.1.100.177 - alarm-warning-fl1
1.3.6.1.4.1.9839.2.1.100.156 - alarm-warning-fl-C
1.3.6.1.4.1.9839.2.1.100.197 - alarm-warning-le
1.3.6.1.4.1.9839.2.1.100.192 - back-Door-open-alarm
1.3.6.1.4.1.9839.2.1.100.31 - chiller-ON-OFF
1.3.6.1.4.1.9839.2.1.100.131 - flow-rate-alarm
1.3.6.1.4.1.9839.2.1.100.11 - flow-switch-alarm
1.3.6.1.4.1.9839.2.1.100.8 - high-pressure-switch-1-alarm
1.3.6.1.4.1.9839.2.1.100.1 - high-pressure-switch-2-alarm
1.3.6.1.4.1.9839.2.1.100.2 - low-pressure-switch-1-alarm
1.3.6.1.4.1.9839.2.1.100.3 - low-pressure-switch-2-alarm
1.3.6.1.4.1.9839.2.1.100.4 - overload-compressor1-circuit1-alarm
1.3.6.1.4.1.9839.2.1.100.12 - overload-compressor1-circuit2-alarm
1.3.6.1.4.1.9839.2.1.100.15 - overload-compressor2-circuit1-alarm
1.3.6.1.4.1.9839.2.1.100.13 - overload-compressor2-circuit2-alarm
1.3.6.1.4.1.9839.2.1.100.16 - overload-compressor3-circuit1-alarm
1.3.6.1.4.1.9839.2.1.100.14 - overload-compressor3-circuit2-alarm
1.3.6.1.4.1.9839.2.1.100.17 - overload-fan1-circuit1-alarm
1.3.6.1.4.1.9839.2.1.100.20 - overload-fan1-circuit-2-alarm
1.3.6.1.4.1.9839.2.1.100.24 - overload-fan2-circuit1-alarm
1.3.6.1.4.1.9839.2.1.100.21 - overload-fan2-circuit2-alarm
1.3.6.1.4.1.9839.2.1.100.25 - overload-fan3-circuit1-alarm
1.3.6.1.4.1.9839.2.1.100.22 - overload-fan3-circuit2-alarm
1.3.6.1.4.1.9839.2.1.100.26 - overload-fan4-circuit1-alarm
1.3.6.1.4.1.9839.2.1.100.23 - overload-fan4-circuit2-alarm
1.3.6.1.4.1.9839.2.1.100.27 - overload-fans-circuit1
1.3.6.1.4.1.9839.2.1.100.18 - overload-fans-circuit2
1.3.6.1.4.1.9839.2.1.100.19 - overload-pump1-alarm
1.3.6.1.4.1.9839.2.1.100.28 - overload-pump2-alarm
1.3.6.1.4.1.9839.2.1.100.29 - remote-on-off
1.3.6.1.4.1.9839.2.1.100.130 - water-level-alarm
1.3.6.1.4.1.9839.2.1.100.6 - water-static-pressure-alarm
1.3.6.1.4.1.9839.2.1.100.9 - water-static-pressure-warning
1.3.6.1.4.1.9839.2.1.100.10 - wrong-phase-rotation-alarm
1.3.6.1.4.1.9839.2.1.100.30