TEMPAGER3E-MIB
AVTECH Software, Inc.snmptranslate -m TEMPAGER3E-MIB -Tpsnmpwalk -v2c -c <community> -m TEMPAGER3E-MIB <host> 1.3.6.1.4.1.20916Imports
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
|---|---|
| SNMPv2-SMI | Bits, Counter32, Integer32, IpAddress, MODULE-IDENTITY, MibIdentifier, OBJECT-IDENTITY, OBJECT-TYPE, TRAP-TYPE, TimeTicks, Unsigned32, enterprises, iso |
| SNMPv2-TC | DisplayString, PhysAddress, TEXTUAL-CONVENTION |
OID tree
| Name | OID | Type | Access | Status |
|---|---|---|---|---|
| Navtech | 1.3.6.1.4.1.20916 | |||
| Nproducts | 1.3.6.1.4.1.20916.1 | |||
| NTEMPAGER3E | 1.3.6.1.4.1.20916.1.7 | |||
| !tempager3e-snmp-trap | 1.3.6.1.4.1.20916.1.7.0.2 | |||
notification A tempager3e-snmp-trap indicates that an alarm condition has occurred on the sensor indicated by the alarmmessage variable.
| ||||
| Nsensors | 1.3.6.1.4.1.20916.1.7.1 | |||
| Ninternal | 1.3.6.1.4.1.20916.1.7.1.1 | |||
| Ntemperature | 1.3.6.1.4.1.20916.1.7.1.1.1 | |||
| Sinternal-tempc | 1.3.6.1.4.1.20916.1.7.1.1.1.1 | INTEGER (0..65535) | RO | mandatory |
scalar · INTEGER (0..65535) · read-only · mandatory The internal temperature reading in Celsius. Because the SNMP Protocol does not support floating point numbers, values are scaled by 100 and should be divided by 100 to get the actual value. | ||||
| Sinternal-tempf | 1.3.6.1.4.1.20916.1.7.1.1.1.2 | INTEGER (0..65535) | RO | mandatory |
scalar · INTEGER (0..65535) · read-only · mandatory The internal temperature reading in Fahrenheit. Because the SNMP Protocol does not support floating point numbers, values are scaled by 100 and should be divided by 100 to get the actual value. | ||||
| Ndigital | 1.3.6.1.4.1.20916.1.7.1.2 | |||
| Ndigital-sen1 | 1.3.6.1.4.1.20916.1.7.1.2.1 | |||
| Sdigital-sen1-1 | 1.3.6.1.4.1.20916.1.7.1.2.1.1 | INTEGER (0..65535) | RO | mandatory |
scalar · INTEGER (0..65535) · read-only · mandatory If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, this value represents the Current reading in Amperage. | ||||
| Sdigital-sen1-2 | 1.3.6.1.4.1.20916.1.7.1.2.1.2 | INTEGER (0..65535) | RO | mandatory |
scalar · INTEGER (0..65535) · read-only · mandatory If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Power reading in Watts. | ||||
| Sdigital-sen1-3 | 1.3.6.1.4.1.20916.1.7.1.2.1.3 | INTEGER (0..65535) | RO | mandatory |
scalar · INTEGER (0..65535) · read-only · mandatory If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor, this value represents the Voltage reading in Volts. | ||||
| Sdigital-sen1-4 | 1.3.6.1.4.1.20916.1.7.1.2.1.4 | INTEGER (0..65535) | RO | mandatory |
scalar · INTEGER (0..65535) · read-only · mandatory If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Reference reading in Volts. | ||||
| Ndigital-sen2 | 1.3.6.1.4.1.20916.1.7.1.2.2 | |||
| Sdigital-sen2-1 | 1.3.6.1.4.1.20916.1.7.1.2.2.1 | INTEGER (0..65535) | RO | mandatory |
scalar · INTEGER (0..65535) · read-only · mandatory If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, this value represents the Current reading in Amperage. | ||||
| Sdigital-sen2-2 | 1.3.6.1.4.1.20916.1.7.1.2.2.2 | INTEGER (0..65535) | RO | mandatory |
scalar · INTEGER (0..65535) · read-only · mandatory If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Power reading in Watts. | ||||
| Sdigital-sen2-3 | 1.3.6.1.4.1.20916.1.7.1.2.2.3 | INTEGER (0..65535) | RO | mandatory |
scalar · INTEGER (0..65535) · read-only · mandatory If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor, this value represents the Voltage reading in Volts. | ||||
| Sdigital-sen2-4 | 1.3.6.1.4.1.20916.1.7.1.2.2.4 | INTEGER (0..65535) | RO | mandatory |
scalar · INTEGER (0..65535) · read-only · mandatory If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Reference reading in Volts. | ||||
| Ntraps | 1.3.6.1.4.1.20916.1.7.2 | |||
| Salarmmessage | 1.3.6.1.4.1.20916.1.7.2.1 | OCTET STRING | RO | mandatory |
scalar · OCTET STRING · read-only · mandatory Last Alarm Message | ||||
Traps / Notifications
- tempager3e-snmp-trap
1.3.6.1.4.1.20916.1.7.0.2