ROOMALERT12S-MIB
AVTECH Software, Inc.snmptranslate -m ROOMALERT12S-MIB -Tpsnmpwalk -v2c -c <community> -m ROOMALERT12S-MIB <host> 1.3.6.1.4.1.20916Imports
| RFC1155-SMI | Gauge32 |
|---|---|
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
| SNMPv2-MIB | system |
| SNMPv2-SMI | Bits, Integer32, IpAddress, MODULE-IDENTITY, MibIdentifier, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, TimeTicks, Unsigned32, enterprises, iso |
| SNMPv2-TC | DisplayString, PhysAddress, TEXTUAL-CONVENTION |
OID tree
| Name | OID | Type | Access | Status | Example | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Navtech | 1.3.6.1.4.1.20916 | ||||||||||||
| Nproducts | 1.3.6.1.4.1.20916.1 | ||||||||||||
| Nroomalert12S | 1.3.6.1.4.1.20916.1.12 | ||||||||||||
| Nsensors | 1.3.6.1.4.1.20916.1.12.1 | ||||||||||||
| Ninternal | 1.3.6.1.4.1.20916.1.12.1.1 | ||||||||||||
| Ntemperature | 1.3.6.1.4.1.20916.1.12.1.1.1 | ||||||||||||
| Sinternal-tempf | 1.3.6.1.4.1.20916.1.12.1.1.1.1 | INTEGER (0..65535) | RO | mandatory | |||||||||
scalar · INTEGER (0..65535) · read-only · mandatory The internal temperature reading in Fahrenheit. | |||||||||||||
| Sinternal-tempc | 1.3.6.1.4.1.20916.1.12.1.1.1.2 | INTEGER (0..65535) | RO | mandatory | 2500 | ||||||||
scalar · INTEGER (0..65535) · read-only · mandatory The internal temperature reading in Celsius. Example values from LibreNMS test devices
| |||||||||||||
| Nanalog | 1.3.6.1.4.1.20916.1.12.1.1.2 | ||||||||||||
| Sinternal-analog1 | 1.3.6.1.4.1.20916.1.12.1.1.2.1 | INTEGER (0..65535) | RO | mandatory | |||||||||
scalar · INTEGER (0..65535) · read-only · mandatory The current status of the Room Alert 12S analog input (0-5VDC). | |||||||||||||
| Sinternal-analog-computed1 | 1.3.6.1.4.1.20916.1.12.1.1.2.2 | INTEGER (0..65535) | RO | mandatory | |||||||||
scalar · INTEGER (0..65535) · read-only · mandatory The current computed value of the Room Alert 12S analog input. | |||||||||||||
| Sinternal-analog-computed-units1 | 1.3.6.1.4.1.20916.1.12.1.1.2.3 | OCTET STRING | RO | mandatory | |||||||||
scalar · OCTET STRING · read-only · mandatory The computed analog units for the Room Alert 12S analog input.. | |||||||||||||
| Nrelay | 1.3.6.1.4.1.20916.1.12.1.1.3 | ||||||||||||
| Sinternal-relay1 | 1.3.6.1.4.1.20916.1.12.1.1.3.1 | INTEGER (0..1) | RW | mandatory | 0 | ||||||||
scalar · INTEGER (0..1) · read-write · mandatory The status of the on-board relay output Example values from LibreNMS test devices
| |||||||||||||
| Ndigital | 1.3.6.1.4.1.20916.1.12.1.2 | ||||||||||||
| Ndigital-sen1 | 1.3.6.1.4.1.20916.1.12.1.2.1 | ||||||||||||
| Sdigital-sen1-1 | 1.3.6.1.4.1.20916.1.12.1.2.1.1 | INTEGER (0..65535) | RO | mandatory | 2270 | ||||||||
scalar · INTEGER (0..65535) · read-only · mandatory The sensor's current temperature in Celsius. Example values from LibreNMS test devices
| |||||||||||||
| Sdigital-sen1-2 | 1.3.6.1.4.1.20916.1.12.1.2.1.2 | INTEGER (0..65535) | RO | mandatory | |||||||||
scalar · INTEGER (0..65535) · read-only · mandatory The sensor's current temperature in Fahrenheit. | |||||||||||||
| Sdigital-sen1-3 | 1.3.6.1.4.1.20916.1.12.1.2.1.3 | INTEGER (0..65535) | RO | mandatory | 1864 | ||||||||
scalar · INTEGER (0..65535) · read-only · mandatory Varies by sensor type: current % relative humidity, voltage reading (V), power state (1=Power Detected, 0=No Power Detected), thermocouple temperature (C), air speed (m/s), or PM2.5 (mcg/m3). Example values from LibreNMS test devices
| |||||||||||||
| Sdigital-sen1-4 | 1.3.6.1.4.1.20916.1.12.1.2.1.4 | INTEGER (0..65535) | RO | mandatory | |||||||||
scalar · INTEGER (0..65535) · read-only · mandatory Varies by sensor type: current heat index (F), custom analog reading, thermocouple temperature (F), air speed (f/m), or PM10 (mcg/m3). | |||||||||||||
| Sdigital-sen1-5 | 1.3.6.1.4.1.20916.1.12.1.2.1.5 | INTEGER (0..65535) | RO | mandatory | |||||||||
scalar · INTEGER (0..65535) · read-only · mandatory Varies by sensor type: current heat index (C), thermocouple fault code (0=No Fault), air flow (CMH), or particulate fault code (0=No Fault). | |||||||||||||
| Sdigital-sen1-6 | 1.3.6.1.4.1.20916.1.12.1.2.1.6 | INTEGER (0..65535) | RO | mandatory | |||||||||
scalar · INTEGER (0..65535) · read-only · mandatory Varies by sensor type: current dew point (C) or air flow (CFM). | |||||||||||||
| Sdigital-sen1-7 | 1.3.6.1.4.1.20916.1.12.1.2.1.7 | INTEGER (0..65535) | RO | mandatory | |||||||||
scalar · INTEGER (0..65535) · read-only · mandatory Varies by sensor type: current dew point (F). | |||||||||||||
| Sdigital-sen1-8 | 1.3.6.1.4.1.20916.1.12.1.2.1.8 | OCTET STRING | RO | mandatory | |||||||||
scalar · OCTET STRING · read-only · mandatory The computed analog units for the Room Alert 32S analog input.. | |||||||||||||
| Ndigital-sen2 | 1.3.6.1.4.1.20916.1.12.1.2.2 | ||||||||||||
| Sdigital-sen2-1 | 1.3.6.1.4.1.20916.1.12.1.2.2.1 | INTEGER (0..65535) | RO | mandatory | 2110 | ||||||||
scalar · INTEGER (0..65535) · read-only · mandatory The sensor's current temperature in Celsius. Example values from LibreNMS test devices
| |||||||||||||
| Sdigital-sen2-2 | 1.3.6.1.4.1.20916.1.12.1.2.2.2 | INTEGER (0..65535) | RO | mandatory | |||||||||
scalar · INTEGER (0..65535) · read-only · mandatory The sensor's current temperature in Fahrenheit. | |||||||||||||
| Sdigital-sen2-3 | 1.3.6.1.4.1.20916.1.12.1.2.2.3 | INTEGER (0..65535) | RO | mandatory | 2220 | ||||||||
scalar · INTEGER (0..65535) · read-only · mandatory Varies by sensor type: current % relative humidity, voltage reading (V), power state (1=Power Detected, 0=No Power Detected), thermocouple temperature (C), air speed (m/s), or PM2.5 (mcg/m3). Example values from LibreNMS test devices
| |||||||||||||
| Sdigital-sen2-4 | 1.3.6.1.4.1.20916.1.12.1.2.2.4 | INTEGER (0..65535) | RO | mandatory | |||||||||
scalar · INTEGER (0..65535) · read-only · mandatory Varies by sensor type: current heat index (F), custom analog reading, thermocouple temperature (F), air speed (f/m), or PM10 (mcg/m3). | |||||||||||||
| Sdigital-sen2-5 | 1.3.6.1.4.1.20916.1.12.1.2.2.5 | INTEGER (0..65535) | RO | mandatory | |||||||||
scalar · INTEGER (0..65535) · read-only · mandatory Varies by sensor type: current heat index (C), thermocouple fault code (0=No Fault), air flow (CMH), or particulate fault code (0=No Fault). | |||||||||||||
| Sdigital-sen2-6 | 1.3.6.1.4.1.20916.1.12.1.2.2.6 | INTEGER (0..65535) | RO | mandatory | |||||||||
scalar · INTEGER (0..65535) · read-only · mandatory Varies by sensor type: current dew point (C) or air flow (CFM). | |||||||||||||
| Sdigital-sen2-7 | 1.3.6.1.4.1.20916.1.12.1.2.2.7 | INTEGER (0..65535) | RO | mandatory | |||||||||
scalar · INTEGER (0..65535) · read-only · mandatory Varies by sensor type: current dew point (F). | |||||||||||||
| Sdigital-sen2-8 | 1.3.6.1.4.1.20916.1.12.1.2.2.8 | OCTET STRING | RO | mandatory | |||||||||
scalar · OCTET STRING · read-only · mandatory The computed analog units for the Room Alert 32S analog input.. | |||||||||||||
| Ndigital-sen3 | 1.3.6.1.4.1.20916.1.12.1.2.3 | ||||||||||||
| Sdigital-sen3-1 | 1.3.6.1.4.1.20916.1.12.1.2.3.1 | INTEGER (0..65535) | RO | mandatory | |||||||||
scalar · INTEGER (0..65535) · read-only · mandatory The sensor's current temperature in Celsius. | |||||||||||||
| Sdigital-sen3-2 | 1.3.6.1.4.1.20916.1.12.1.2.3.2 | INTEGER (0..65535) | RO | mandatory | |||||||||
scalar · INTEGER (0..65535) · read-only · mandatory The sensor's current temperature in Fahrenheit. | |||||||||||||
| Sdigital-sen3-3 | 1.3.6.1.4.1.20916.1.12.1.2.3.3 | INTEGER (0..65535) | RO | mandatory | |||||||||
scalar · INTEGER (0..65535) · read-only · mandatory Varies by sensor type: current % relative humidity, voltage reading (V), power state (1=Power Detected, 0=No Power Detected), thermocouple temperature (C), air speed (m/s), or PM2.5 (mcg/m3). | |||||||||||||
| Sdigital-sen3-4 | 1.3.6.1.4.1.20916.1.12.1.2.3.4 | INTEGER (0..65535) | RO | mandatory | |||||||||
scalar · INTEGER (0..65535) · read-only · mandatory Varies by sensor type: current heat index (F), custom analog reading, thermocouple temperature (F), air speed (f/m), or PM10 (mcg/m3). | |||||||||||||
| Sdigital-sen3-5 | 1.3.6.1.4.1.20916.1.12.1.2.3.5 | INTEGER (0..65535) | RO | mandatory | |||||||||
scalar · INTEGER (0..65535) · read-only · mandatory Varies by sensor type: current heat index (C), thermocouple fault code (0=No Fault), air flow (CMH), or particulate fault code (0=No Fault). | |||||||||||||
| Sdigital-sen3-6 | 1.3.6.1.4.1.20916.1.12.1.2.3.6 | INTEGER (0..65535) | RO | mandatory | |||||||||
scalar · INTEGER (0..65535) · read-only · mandatory Varies by sensor type: current dew point (C) or air flow (CFM). | |||||||||||||
| Sdigital-sen3-7 | 1.3.6.1.4.1.20916.1.12.1.2.3.7 | INTEGER (0..65535) | RO | mandatory | |||||||||
scalar · INTEGER (0..65535) · read-only · mandatory Varies by sensor type: current dew point (F). | |||||||||||||
| Sdigital-sen3-8 | 1.3.6.1.4.1.20916.1.12.1.2.3.8 | OCTET STRING | RO | mandatory | |||||||||
scalar · OCTET STRING · read-only · mandatory The computed analog units for the Room Alert 32S analog input.. | |||||||||||||
| Nswitch | 1.3.6.1.4.1.20916.1.12.1.3 | ||||||||||||
| Sswitch-sen1 | 1.3.6.1.4.1.20916.1.12.1.3.1 | INTEGER (0..1) | RO | mandatory | 0 | ||||||||
scalar · INTEGER (0..1) · read-only · mandatory The reading for switch sensor 1 (0 = OPEN, 1 = CLOSED). Example values from LibreNMS test devices
| |||||||||||||
| Sswitch-sen2 | 1.3.6.1.4.1.20916.1.12.1.3.2 | INTEGER (0..1) | RO | mandatory | 0 | ||||||||
scalar · INTEGER (0..1) · read-only · mandatory The reading for switch sensor 2 (0 = OPEN, 1 = CLOSED). Example values from LibreNMS test devices
| |||||||||||||
| Sswitch-sen3 | 1.3.6.1.4.1.20916.1.12.1.3.3 | INTEGER (0..1) | RO | mandatory | 0 | ||||||||
scalar · INTEGER (0..1) · read-only · mandatory The reading for switch sensor 3 (0 = OPEN, 1 = CLOSED). Example values from LibreNMS test devices
| |||||||||||||
| Sswitch-sen4 | 1.3.6.1.4.1.20916.1.12.1.3.4 | INTEGER (0..1) | RO | mandatory | 0 | ||||||||
scalar · INTEGER (0..1) · read-only · mandatory The reading for switch sensor 4 (0 = OPEN, 1 = CLOSED). Example values from LibreNMS test devices
| |||||||||||||
| Nlabels | 1.3.6.1.4.1.20916.1.12.1.4 | ||||||||||||
| Nint-labels | 1.3.6.1.4.1.20916.1.12.1.4.1 | ||||||||||||
| Slabels-internal-sen1 | 1.3.6.1.4.1.20916.1.12.1.4.1.1 | OCTET STRING | RO | mandatory | Internal Sensor | ||||||||
scalar · OCTET STRING · read-only · mandatory Internal Sensor Label Example values from LibreNMS test devices
| |||||||||||||
| Ndigital-labels | 1.3.6.1.4.1.20916.1.12.1.4.2 | ||||||||||||
| Slabels-digital-sen1 | 1.3.6.1.4.1.20916.1.12.1.4.2.1 | OCTET STRING | RO | mandatory | Ext Sensor 1 | ||||||||
scalar · OCTET STRING · read-only · mandatory Digital Sensor Port 1 Label Example values from LibreNMS test devices
| |||||||||||||
| Slabels-digital-sen2 | 1.3.6.1.4.1.20916.1.12.1.4.2.2 | OCTET STRING | RO | mandatory | Ext Sensor 2 | ||||||||
scalar · OCTET STRING · read-only · mandatory Digital Sensor Port 2 Label Example values from LibreNMS test devices
| |||||||||||||
| Slabels-digital-sen3 | 1.3.6.1.4.1.20916.1.12.1.4.2.3 | OCTET STRING | RO | mandatory | |||||||||
scalar · OCTET STRING · read-only · mandatory Digital Sensor Port 3 Label | |||||||||||||
| Nswitch-labels | 1.3.6.1.4.1.20916.1.12.1.4.3 | ||||||||||||
| Slabels-switch-sen1 | 1.3.6.1.4.1.20916.1.12.1.4.3.1 | OCTET STRING | RO | mandatory | Switch Sensor 1 | ||||||||
scalar · OCTET STRING · read-only · mandatory Switch 1 Label Example values from LibreNMS test devices
| |||||||||||||
| Slabels-switch-sen2 | 1.3.6.1.4.1.20916.1.12.1.4.3.2 | OCTET STRING | RO | mandatory | Switch Sensor 2 | ||||||||
scalar · OCTET STRING · read-only · mandatory Switch 2 Label Example values from LibreNMS test devices
| |||||||||||||
| Slabels-switch-sen3 | 1.3.6.1.4.1.20916.1.12.1.4.3.3 | OCTET STRING | RO | mandatory | Switch Sensor 3 | ||||||||
scalar · OCTET STRING · read-only · mandatory Switch 3 Label Example values from LibreNMS test devices
| |||||||||||||
| Slabels-switch-sen4 | 1.3.6.1.4.1.20916.1.12.1.4.3.4 | OCTET STRING | RO | mandatory | Switch Sensor 4 | ||||||||
scalar · OCTET STRING · read-only · mandatory Switch 4 Label Example values from LibreNMS test devices
| |||||||||||||
| Nanalog-labels | 1.3.6.1.4.1.20916.1.12.1.4.4 | ||||||||||||
| Slabels-analog-sen1 | 1.3.6.1.4.1.20916.1.12.1.4.4.1 | OCTET STRING | RO | mandatory | |||||||||
scalar · OCTET STRING · read-only · mandatory Analog Sensor 1 Label | |||||||||||||
| Ninternal-relay-labels | 1.3.6.1.4.1.20916.1.12.1.4.5 | ||||||||||||
| Sinternal-relay-labels1 | 1.3.6.1.4.1.20916.1.12.1.4.5.1 | OCTET STRING | RO | mandatory | Internal Relay 1 | ||||||||
scalar · OCTET STRING · read-only · mandatory Internal Relay 1 Label Example values from LibreNMS test devices
| |||||||||||||
| Nexternal-relay-labels | 1.3.6.1.4.1.20916.1.12.1.4.6 | ||||||||||||
| Sexternal-relay-labels1 | 1.3.6.1.4.1.20916.1.12.1.4.6.1 | OCTET STRING | RO | mandatory | |||||||||
scalar · OCTET STRING · read-only · mandatory External Relay 1 Label | |||||||||||||
| Ntraps | 1.3.6.1.4.1.20916.1.12.2 | ||||||||||||
| !alarmmessage | 1.3.6.1.4.1.20916.1.12.2.1 | ||||||||||||
notification · current Indicates that an alarm condition has occurred on the sensor indicated by the alarmMessage variable.
| |||||||||||||
| Nexternalrelays | 1.3.6.1.4.1.20916.1.12.3 | ||||||||||||
| Nexternalrelay1 | 1.3.6.1.4.1.20916.1.12.3.1 | ||||||||||||
| Sexternalrelay1-element-one | 1.3.6.1.4.1.20916.1.12.3.1.1 | INTEGER (0..1) | RW | mandatory | |||||||||
scalar · INTEGER (0..1) · read-write · mandatory The status of the first element on external relay 1. | |||||||||||||
| Sexternalrelay1-element-two | 1.3.6.1.4.1.20916.1.12.3.1.2 | INTEGER (0..1) | RW | mandatory | |||||||||
scalar · INTEGER (0..1) · read-write · mandatory The status of the second element on external relay 1. | |||||||||||||
| Sexternalrelay1-element-three | 1.3.6.1.4.1.20916.1.12.3.1.3 | INTEGER (0..1) | RW | mandatory | |||||||||
scalar · INTEGER (0..1) · read-write · mandatory The status of the third element on external relay 1. | |||||||||||||
| Sexternalrelay1-element-four | 1.3.6.1.4.1.20916.1.12.3.1.4 | INTEGER (0..1) | RW | mandatory | |||||||||
scalar · INTEGER (0..1) · read-write · mandatory The status of the fourth element on external relay 1. | |||||||||||||
| Sexternalrelay1-element-five | 1.3.6.1.4.1.20916.1.12.3.1.5 | INTEGER (0..1) | RW | mandatory | |||||||||
scalar · INTEGER (0..1) · read-write · mandatory The status of the fifth element on external relay 1. | |||||||||||||
| Sexternalrelay1-element-six | 1.3.6.1.4.1.20916.1.12.3.1.6 | INTEGER (0..1) | RW | mandatory | |||||||||
scalar · INTEGER (0..1) · read-write · mandatory The status of the sixth element on external relay 1. | |||||||||||||
| Sexternalrelay1-element-seven | 1.3.6.1.4.1.20916.1.12.3.1.7 | INTEGER (0..1) | RW | mandatory | |||||||||
scalar · INTEGER (0..1) · read-write · mandatory The status of the seventh element on external relay 1. | |||||||||||||
| Sexternalrelay1-element-eight | 1.3.6.1.4.1.20916.1.12.3.1.8 | INTEGER (0..1) | RW | mandatory | |||||||||
scalar · INTEGER (0..1) · read-write · mandatory The status of the eighth element on external relay 1 | |||||||||||||
Traps / Notifications
- alarmmessage
1.3.6.1.4.1.20916.1.12.2.1