ACS-MIB
Avocent CorporationThis module defines the Avocent MIB extensions to ACS60xx products.
snmptranslate -m ACS-MIB -Tpsnmpwalk -v2c -c <community> -m ACS-MIB <host> 1.3.6.1.4.1.10418.16Imports
| IF-MIB | InterfaceIndex, InterfaceIndexOrZero |
|---|---|
| RFC1155-SMI | Counter32, Gauge32 |
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
| SNMPv2-SMI | Bits, Integer32, IpAddress, MODULE-IDENTITY, MibIdentifier, OBJECT-IDENTITY, OBJECT-TYPE, TRAP-TYPE, TimeTicks, Unsigned32, enterprises, iso |
| SNMPv2-TC | DisplayString, PhysAddress, TEXTUAL-CONVENTION |
OID tree
| Name | OID | Type | Access | Status | Example | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Iacs | 1.3.6.1.4.1.10418.16 | ||||||||||||||||||||
identity This module defines the Avocent MIB extensions to ACS60xx products. | |||||||||||||||||||||
| NacsProducts | 1.3.6.1.4.1.10418.16.1 | ||||||||||||||||||||
| Nacs6016 | 1.3.6.1.4.1.10418.16.1.1 | ||||||||||||||||||||
| Nacs6032 | 1.3.6.1.4.1.10418.16.1.2 | ||||||||||||||||||||
| Nacs6048 | 1.3.6.1.4.1.10418.16.1.3 | ||||||||||||||||||||
| Nacs6004 | 1.3.6.1.4.1.10418.16.1.4 | ||||||||||||||||||||
| Nacs6008 | 1.3.6.1.4.1.10418.16.1.5 | ||||||||||||||||||||
| NacsManagement | 1.3.6.1.4.1.10418.16.2 | ||||||||||||||||||||
| NacsAppliance | 1.3.6.1.4.1.10418.16.2.1 | ||||||||||||||||||||
| SacsHostName | 1.3.6.1.4.1.10418.16.2.1.1 | DisplayString (SIZE (0..32)) | RO | ||||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · current The appliance name | |||||||||||||||||||||
| SacsProductModel | 1.3.6.1.4.1.10418.16.2.1.2 | DisplayString (SIZE (0..50)) | RO | ACS6048 with auxiliary port and dual power supp… | |||||||||||||||||
scalar · DisplayString (SIZE (0..50)) · read-only · current The appliance product model Example values from LibreNMS test devices
| |||||||||||||||||||||
| SacsPartNumber | 1.3.6.1.4.1.10418.16.2.1.3 | DisplayString (SIZE (0..32)) | RO | ||||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · current The part number of this appliance as shown on the label attached or imprinted on the appliance. | |||||||||||||||||||||
| SacsSerialNumber | 1.3.6.1.4.1.10418.16.2.1.4 | DisplayString (SIZE (0..32)) | RO | 0520227802 | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · current The serial number of this appliance as shown on the label attached or imprinted on the appliance. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SacsEIDNumber | 1.3.6.1.4.1.10418.16.2.1.5 | DisplayString (SIZE (0..32)) | RO | ||||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · current The electronic ID number (EID) of this appliance as shown on the label attached or imprinted on the appliance. | |||||||||||||||||||||
| SacsBootcodeVersion | 1.3.6.1.4.1.10418.16.2.1.6 | DisplayString (SIZE (0..32)) | RO | ||||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · current The version of the bootcode of this appliance. | |||||||||||||||||||||
| SacsFirmwareVersion | 1.3.6.1.4.1.10418.16.2.1.7 | DisplayString (SIZE (0..32)) | RO | 3.9.0.4 | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · current The version of the firmware of this appliance. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NacsPowerSupply | 1.3.6.1.4.1.10418.16.2.1.8 | ||||||||||||||||||||
node · current It gives information about Power Supply of this appliance | |||||||||||||||||||||
| SacsPowerSupplyNumber | 1.3.6.1.4.1.10418.16.2.1.8.1 | Integer32 | RO | ||||||||||||||||||
scalar · Integer32 · read-only · current Number of the power supplies of this appliance | |||||||||||||||||||||
| SacsPowerSupplyStatePw1 | 1.3.6.1.4.1.10418.16.2.1.8.2 | PowerSupplyState | RO | 1 | |||||||||||||||||
scalar · PowerSupplyState · read-only · current State of the first power supply Example values from LibreNMS test devices
| |||||||||||||||||||||
| SacsPowerSupplyStatePw2 | 1.3.6.1.4.1.10418.16.2.1.8.3 | PowerSupplyState | RO | 1 | |||||||||||||||||
scalar · PowerSupplyState · read-only · current State of the second power supply Example values from LibreNMS test devices
| |||||||||||||||||||||
| SacsReboot | 1.3.6.1.4.1.10418.16.2.1.9 | INTEGER | RW | ||||||||||||||||||
scalar · INTEGER · read-write · current A set value of reboot(2) will reboot the appliance. noAction(1) = always returned in a GET. Does nothing if SET. reboot(2) = when SET the appliance immediately reboots.
| |||||||||||||||||||||
| NacsSessions | 1.3.6.1.4.1.10418.16.2.2 | ||||||||||||||||||||
| SacsActiveSessionsNumberOfSession | 1.3.6.1.4.1.10418.16.2.2.1 | Integer32 | RO | 0 | |||||||||||||||||
scalar · Integer32 · read-only · current Number of active sessions. Example values from LibreNMS test devices
| |||||||||||||||||||||
| TacsActiveSessionsTable | 1.3.6.1.4.1.10418.16.2.2.2 | NA | |||||||||||||||||||
table · not-accessible · current This table contains the list of active sessions. | |||||||||||||||||||||
| RacsActiveSessionsTableEntry | 1.3.6.1.4.1.10418.16.2.2.2.1 | NA | |||||||||||||||||||
row · not-accessible · current each entry has the information about the active session | |||||||||||||||||||||
| CacsActiveSessionsTableIndex | 1.3.6.1.4.1.10418.16.2.2.2.1.1 | InterfaceIndexOrZero | RO | ||||||||||||||||||
column · InterfaceIndexOrZero · read-only · current A unique index representing an entry in this table. | |||||||||||||||||||||
| CacsActiveSessionsTableUser | 1.3.6.1.4.1.10418.16.2.2.2.1.2 | DisplayString (SIZE (0..32)) | RO | ||||||||||||||||||
column · DisplayString (SIZE (0..32)) · read-only · current The name of the user that opens this session. | |||||||||||||||||||||
| CacsActiveSessionsTableGroup | 1.3.6.1.4.1.10418.16.2.2.2.1.3 | DisplayString (SIZE (0..32)) | RO | ||||||||||||||||||
column · DisplayString (SIZE (0..32)) · read-only · current The name of the group that the user belongs to. | |||||||||||||||||||||
| CacsActiveSessionsTableType | 1.3.6.1.4.1.10418.16.2.2.2.1.4 | DisplayString (SIZE (0..32)) | RO | ||||||||||||||||||
column · DisplayString (SIZE (0..32)) · read-only · current The session type. | |||||||||||||||||||||
| CacsActiveSessionsTableConnection | 1.3.6.1.4.1.10418.16.2.2.2.1.5 | DisplayString (SIZE (0..32)) | RO | ||||||||||||||||||
column · DisplayString (SIZE (0..32)) · read-only · current Connection type. | |||||||||||||||||||||
| CacsActiveSessionsTableSessionTime | 1.3.6.1.4.1.10418.16.2.2.2.1.6 | DisplayString (SIZE (0..32)) | RO | ||||||||||||||||||
column · DisplayString (SIZE (0..32)) · read-only · current Time of the session | |||||||||||||||||||||
| CacsActiveSessionsTableFrom | 1.3.6.1.4.1.10418.16.2.2.2.1.7 | DisplayString (SIZE (0..32)) | RO | ||||||||||||||||||
column · DisplayString (SIZE (0..32)) · read-only · current The source IP address of the session. | |||||||||||||||||||||
| CacsActiveSessionsTableKill | 1.3.6.1.4.1.10418.16.2.2.2.1.8 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current A set value of killSession(2) will kill the session. noAction(1) = always returned in a GET. Does nothing if SET. killSession(2)= when SET the appliance immediately kills the session.
| |||||||||||||||||||||
| NacsSerialPort | 1.3.6.1.4.1.10418.16.2.3 | ||||||||||||||||||||
| SacsSerialPortNumberOfPorts | 1.3.6.1.4.1.10418.16.2.3.1 | Integer32 | RO | ||||||||||||||||||
scalar · Integer32 · read-only · current Number of Serial Ports (physical serial port plus Aux Port. | |||||||||||||||||||||
| TacsSerialPortTable | 1.3.6.1.4.1.10418.16.2.3.2 | NA | |||||||||||||||||||
table · not-accessible · current This table contains information about serial ports. | |||||||||||||||||||||
| RacsSerialPortTableEntry | 1.3.6.1.4.1.10418.16.2.3.2.1 | NA | |||||||||||||||||||
row · not-accessible · current each entry has the information about specific serial port. | |||||||||||||||||||||
| CacsSerialPortTableNumber | 1.3.6.1.4.1.10418.16.2.3.2.1.1 | Integer32 (1..49) | RO | 1 | |||||||||||||||||
column · Integer32 (1..49) · read-only · current A unique index representing an entry in this table. It is the number of the serial port. For AUX port, the number will be the number of physical serial ports plus 1. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CacsSerialPortTableDeviceName | 1.3.6.1.4.1.10418.16.2.3.2.1.2 | DisplayString (SIZE (0..25)) | RO | ttyS1 | |||||||||||||||||
column · DisplayString (SIZE (0..25)) · read-only · current The associated device name for the serial port. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CacsSerialPortTableStatus | 1.3.6.1.4.1.10418.16.2.3.2.1.3 | INTEGER | RO | idle(2) | |||||||||||||||||
column · INTEGER · read-only · current The status of the serial port: disabled(1) = it was configured as disable. idle(2) = there is not any session opened in this port. inUse(3) = there is session(s) opened in this port.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CacsSerialPortTableName | 1.3.6.1.4.1.10418.16.2.3.2.1.4 | DisplayString (SIZE (0..25)) | RO | <private> | |||||||||||||||||
column · DisplayString (SIZE (0..25)) · read-only · current Name associated with this serial port. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CacsSerialPortTableProfile | 1.3.6.1.4.1.10418.16.2.3.2.1.5 | INTEGER | RO | casProfile(1) | |||||||||||||||||
column · INTEGER · read-only · current Configured profile for this serial port.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CacsSerialPortTablePinOut | 1.3.6.1.4.1.10418.16.2.3.2.1.6 | SerialPortPinOut | RO | 2 | |||||||||||||||||
column · SerialPortPinOut · read-only · current RJ45 Pin-out configured for this serial port. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CacsSerialPortTableComSpeed | 1.3.6.1.4.1.10418.16.2.3.2.1.7 | SerialPortSpeed | RO | 9600 | |||||||||||||||||
column · SerialPortSpeed · read-only · current Speed configured for this serial port. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CacsSerialPortTableComParity | 1.3.6.1.4.1.10418.16.2.3.2.1.8 | INTEGER | RO | none(1) | |||||||||||||||||
column · INTEGER · read-only · current Parity configured for this serial port.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CacsSerialPortTableComDataSize | 1.3.6.1.4.1.10418.16.2.3.2.1.9 | Integer32 | RO | 8 | |||||||||||||||||
column · Integer32 · read-only · current Data Size configured for this serial port. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CacsSerialPortTableComStopBits | 1.3.6.1.4.1.10418.16.2.3.2.1.10 | Integer32 | RO | 1 | |||||||||||||||||
column · Integer32 · read-only · current Number of Stop Bits configured for this serial port. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CacsSerialPortTableComFlowControl | 1.3.6.1.4.1.10418.16.2.3.2.1.11 | INTEGER | RO | none(1) | |||||||||||||||||
column · INTEGER · read-only · current Flow Control configured for this serial port.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CacsSerialPortTableSignalStateDTR | 1.3.6.1.4.1.10418.16.2.3.2.1.12 | SerialPortSignalState | RO | 2 | |||||||||||||||||
column · SerialPortSignalState · read-only · current State of the DTR RS-232C signal. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CacsSerialPortTableSignalStateDCD | 1.3.6.1.4.1.10418.16.2.3.2.1.13 | SerialPortSignalState | RO | 2 | |||||||||||||||||
column · SerialPortSignalState · read-only · current State of the DCD RS-232C signal. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CacsSerialPortTableSignalStateRTS | 1.3.6.1.4.1.10418.16.2.3.2.1.14 | SerialPortSignalState | RO | 2 | |||||||||||||||||
column · SerialPortSignalState · read-only · current State of the RTS RS-232C signal. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CacsSerialPortTableSignalStateCTS | 1.3.6.1.4.1.10418.16.2.3.2.1.15 | SerialPortSignalState | RO | 1 | |||||||||||||||||
column · SerialPortSignalState · read-only · current State of the CTS RS-232C signal. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CacsSerialPortTableTxBytes | 1.3.6.1.4.1.10418.16.2.3.2.1.16 | Integer32 | RO | 889 | |||||||||||||||||
column · Integer32 · read-only · current The number of transmited bytes by the serial port. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CacsSerialPortTableRxBytes | 1.3.6.1.4.1.10418.16.2.3.2.1.17 | Integer32 | RO | 43443 | |||||||||||||||||
column · Integer32 · read-only · current The number of received bytes by the serial port. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CacsSerialPortTableFrameError | 1.3.6.1.4.1.10418.16.2.3.2.1.18 | Integer32 | RO | 0 | |||||||||||||||||
column · Integer32 · read-only · current The number of frame error detected in the serial port. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CacsSerialPortTableParityError | 1.3.6.1.4.1.10418.16.2.3.2.1.19 | Integer32 | RO | 0 | |||||||||||||||||
column · Integer32 · read-only · current The number of parity error detected in the serial port. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CacsSerialPortTableBreak | 1.3.6.1.4.1.10418.16.2.3.2.1.20 | Integer32 | RO | 0 | |||||||||||||||||
column · Integer32 · read-only · current The number of break detected in the serial port. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CacsSerialPortTableOverrun | 1.3.6.1.4.1.10418.16.2.3.2.1.21 | Integer32 | RO | 0 | |||||||||||||||||
column · Integer32 · read-only · current The number of overrun error detected in the serial port. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NacsPowerMgmt | 1.3.6.1.4.1.10418.16.2.5 | ||||||||||||||||||||
| SacsPowerMgmtNumSerialPorts | 1.3.6.1.4.1.10418.16.2.5.1 | Integer32 | RO | ||||||||||||||||||
scalar · Integer32 · read-only · current The number of Serial Ports that has PDU connected on the appliance. | |||||||||||||||||||||
| TacsPowerMgmtSerialTable | 1.3.6.1.4.1.10418.16.2.5.2 | NA | |||||||||||||||||||
table · not-accessible · current Information about each serial port thas has PDU connect. | |||||||||||||||||||||
| RacsPowerMgmtSerialTableEntry | 1.3.6.1.4.1.10418.16.2.5.2.1 | NA | |||||||||||||||||||
row · not-accessible · current Information about each serial port thas has PDU connect. | |||||||||||||||||||||
| CacsPowerMgmtSerialTableIndex | 1.3.6.1.4.1.10418.16.2.5.2.1.1 | InterfaceIndex | RO | ||||||||||||||||||
column · InterfaceIndex · read-only · current The index of the register. | |||||||||||||||||||||
| CacsPowerMgmtSerialTablePortNumber | 1.3.6.1.4.1.10418.16.2.5.2.1.2 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current The number of the serial port when the PDU is connected. | |||||||||||||||||||||
| CacsPowerMgmtSerialTableDeviceName | 1.3.6.1.4.1.10418.16.2.5.2.1.3 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current The device name of this serial port. | |||||||||||||||||||||
| CacsPowerMgmtSerialTableNumberPDUs | 1.3.6.1.4.1.10418.16.2.5.2.1.4 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Total number of units connected in this serial port. | |||||||||||||||||||||
| TacsPowerMgmtPDUTable | 1.3.6.1.4.1.10418.16.2.5.3 | NA | |||||||||||||||||||
table · not-accessible · current This table contains the list of detected PDUs. | |||||||||||||||||||||
| RacsPowerMgmtPDUTableEntry | 1.3.6.1.4.1.10418.16.2.5.3.1 | NA | |||||||||||||||||||
row · not-accessible · current each entry has the information about the PDU. | |||||||||||||||||||||
| CacsPowerMgmtPDUTablePortNumber | 1.3.6.1.4.1.10418.16.2.5.3.1.1 | InterfaceIndex | RO | ||||||||||||||||||
column · InterfaceIndex · read-only · current Number of serial port when the PDU is connected. | |||||||||||||||||||||
| CacsPowerMgmtPDUTablePduIndex | 1.3.6.1.4.1.10418.16.2.5.3.1.2 | InterfaceIndexOrZero | RO | ||||||||||||||||||
column · InterfaceIndexOrZero · read-only · current A PDU position in the chain. | |||||||||||||||||||||
| CacsPowerMgmtPDUTablePduId | 1.3.6.1.4.1.10418.16.2.5.3.1.3 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current PDU identification. | |||||||||||||||||||||
| CacsPowerMgmtPDUTablePortName | 1.3.6.1.4.1.10418.16.2.5.3.1.4 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current Name of serial port when the PDU is connected. | |||||||||||||||||||||
| CacsPowerMgmtPDUTableModel | 1.3.6.1.4.1.10418.16.2.5.3.1.5 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current Model of the PDU. | |||||||||||||||||||||
| CacsPowerMgmtPDUTableVendor | 1.3.6.1.4.1.10418.16.2.5.3.1.6 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current Vendor of the PDU. | |||||||||||||||||||||
| CacsPowerMgmtPDUTableFirmwareVersion | 1.3.6.1.4.1.10418.16.2.5.3.1.7 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current Version of the PDU firmware. | |||||||||||||||||||||
| CacsPowerMgmtPDUTableNumberOfOutlets | 1.3.6.1.4.1.10418.16.2.5.3.1.8 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Number of outlets of the PDU. | |||||||||||||||||||||
| CacsPowerMgmtPDUTableCurrentNOS | 1.3.6.1.4.1.10418.16.2.5.3.1.9 | Integer32 | RO | obsolete | |||||||||||||||||
column · Integer32 · read-only · obsolete Number of current sensors in the PDU. | |||||||||||||||||||||
| CacsPowerMgmtPDUTableCurrent1Value | 1.3.6.1.4.1.10418.16.2.5.3.1.10 | Integer32 | RO | obsolete | |||||||||||||||||
column · Integer32 · read-only · obsolete Current of the sensor 1 in this PDU unit in AMP. The value of this object is the actual current in AMP * 10. You need to translate the readed value (Ex. : value is 5, the current is 0.5 AMP.) | |||||||||||||||||||||
| CacsPowerMgmtPDUTableCurrent1Max | 1.3.6.1.4.1.10418.16.2.5.3.1.11 | Integer32 | RW | obsolete | |||||||||||||||||
column · Integer32 · read-write · obsolete Maximum current of the sensor 1 in this PDU unit in AMP. When the PDU does not have support for maximum value, the value will be 0. The value of this object is the actual current in AMP * 10. You need to translate the readed value (Ex. : value is 5, the current is 0.5 AMP.) Clear this value, set it with Zero value. | |||||||||||||||||||||
| CacsPowerMgmtPDUTableCurrent2Value | 1.3.6.1.4.1.10418.16.2.5.3.1.12 | Integer32 | RO | obsolete | |||||||||||||||||
column · Integer32 · read-only · obsolete Current of the sensor 2 in this PDU unit in AMP. The value of this object is the actual current in AMP * 10. You need to translate the readed value (Ex. : value is 5, the current is 0.5 AMP.) | |||||||||||||||||||||
| CacsPowerMgmtPDUTableCurrent2Max | 1.3.6.1.4.1.10418.16.2.5.3.1.13 | Integer32 | RW | obsolete | |||||||||||||||||
column · Integer32 · read-write · obsolete Maximum current of the sensor 2 in this PDU unit in AMP. When the PDU does not have support for maximum value, the value will be 0. The value of this object is the actual current in AMP * 10. You need to translate the readed value (Ex. : value is 5, the current is 0.5 AMP.) Clear this value, set it with Zero value. | |||||||||||||||||||||
| CacsPowerMgmtPDUTableCurrent3Value | 1.3.6.1.4.1.10418.16.2.5.3.1.14 | Integer32 | RO | obsolete | |||||||||||||||||
column · Integer32 · read-only · obsolete Current of the sensor 3 in this PDU unit in AMP. The value of this object is the actual current in AMP * 10. You need to translate the readed value (Ex. : value is 5, the current is 0.5 AMP.) | |||||||||||||||||||||
| CacsPowerMgmtPDUTableCurrent3Max | 1.3.6.1.4.1.10418.16.2.5.3.1.15 | Integer32 | RW | obsolete | |||||||||||||||||
column · Integer32 · read-write · obsolete Maximum current of the sensor 3 in this PDU unit in AMP. When the PDU does not have support for maximum value, the value will be 0. The value of this object is the actual current in AMP * 10. You need to translate the readed value (Ex. : value is 5, the current is 0.5 AMP.) Clear this value, set it with Zero value. | |||||||||||||||||||||
| CacsPowerMgmtPDUTableTemperatureNOS | 1.3.6.1.4.1.10418.16.2.5.3.1.16 | Integer32 | RO | obsolete | |||||||||||||||||
column · Integer32 · read-only · obsolete Number of temperature sensors in the PDU. | |||||||||||||||||||||
| CacsPowerMgmtPDUTableTemperature1Value | 1.3.6.1.4.1.10418.16.2.5.3.1.17 | Integer32 | RO | obsolete | |||||||||||||||||
column · Integer32 · read-only · obsolete Temperature of this PM unit in Celsius degrees. The value of this object is the actual temperature in degrees C * 10. You need to translate the readed value (Ex. : value is 240, the temperature is 24 Celsius.) If the temperature measurement is not installed this value will be 0. Valid values are 5 to 999 ( 0.5 to 99.9 Celsius). | |||||||||||||||||||||
| CacsPowerMgmtPDUTableTemperature1Max | 1.3.6.1.4.1.10418.16.2.5.3.1.18 | Integer32 | RW | obsolete | |||||||||||||||||
column · Integer32 · read-write · obsolete Maximum temperature detected in this PM unit in Celsius degrees. The value will be Zero when the PDU does not have support for maximum value. The value of this object is the actual temperature in degrees C * 10. You need to translate the readed value (Ex. : value is 240, the temperature is 24 Celsius.) If the temperature measurement is not installed this value will be 0. Valid values are 5 to 999 ( 0.5 to 99.9 Celsius). Set with Zero value to clear the max. temperature. | |||||||||||||||||||||
| CacsPowerMgmtPDUTableTemperature2Value | 1.3.6.1.4.1.10418.16.2.5.3.1.19 | Integer32 | RO | obsolete | |||||||||||||||||
column · Integer32 · read-only · obsolete Temperature of this PM unit in Celsius degrees. The value of this object is the actual temperature in degrees C * 10. You need to translate the readed value (Ex. : value is 240, the temperature is 24 Celsius.) If the temperature measurement is not installed this value will be 0. Valid values are 5 to 999 ( 0.5 to 99.9 Celsius). | |||||||||||||||||||||
| CacsPowerMgmtPDUTableTemperature2Max | 1.3.6.1.4.1.10418.16.2.5.3.1.20 | Integer32 | RW | obsolete | |||||||||||||||||
column · Integer32 · read-write · obsolete Maximum temperature detected in this PM unit in Celsius degrees. The value will be Zero when the PDU does not have support for maximum value. The value of this object is the actual temperature in degrees C * 10. You need to translate the readed value (Ex. : value is 240, the temperature is 24 Celsius.) If the temperature measurement is not installed this value will be 0. Valid values are 5 to 999 ( 0.5 to 99.9 Celsius). Set with Zero value to clear the max. temperature. | |||||||||||||||||||||
| CacsPowerMgmtPDUTableTemperature3Value | 1.3.6.1.4.1.10418.16.2.5.3.1.21 | Integer32 | RO | obsolete | |||||||||||||||||
column · Integer32 · read-only · obsolete Temperature of this PM unit in Celsius degrees. The value of this object is the actual temperature in degrees C * 10. You need to translate the readed value (Ex. : value is 240, the temperature is 24 Celsius.) If the temperature measurement is not installed this value will be 0. Valid values are 5 to 999 ( 0.5 to 99.9 Celsius). | |||||||||||||||||||||
| CacsPowerMgmtPDUTableTemperature3Max | 1.3.6.1.4.1.10418.16.2.5.3.1.22 | Integer32 | RW | obsolete | |||||||||||||||||
column · Integer32 · read-write · obsolete Maximum temperature detected in this PM unit in Celsius degrees. The value will be Zero when the PDU does not have support for maximum value. The value of this object is the actual temperature in degrees C * 10. You need to translate the readed value (Ex. : value is 240, the temperature is 24 Celsius.) If the temperature measurement is not installed this value will be 0. Valid values are 5 to 999 ( 0.5 to 99.9 Celsius). Set with Zero value to clear the max. temperature. | |||||||||||||||||||||
| CacsPowerMgmtPDUTableHumidityNOS | 1.3.6.1.4.1.10418.16.2.5.3.1.23 | Integer32 | RO | obsolete | |||||||||||||||||
column · Integer32 · read-only · obsolete Number of humidity sensors in the PDU. | |||||||||||||||||||||
| CacsPowerMgmtPDUTableHumidity1Value | 1.3.6.1.4.1.10418.16.2.5.3.1.24 | Integer32 | RO | obsolete | |||||||||||||||||
column · Integer32 · read-only · obsolete Humidity of this PM unit . If the humidity measurement is not installed this value will be 0. | |||||||||||||||||||||
| CacsPowerMgmtPDUTableHumidity1Max | 1.3.6.1.4.1.10418.16.2.5.3.1.25 | Integer32 | RW | obsolete | |||||||||||||||||
column · Integer32 · read-write · obsolete Maximum humidity detected in this PM unit. If the humidity measurement is not installed or the PDU does not have support for maximum value this value will be 0. Set with Zero value to clear the max. temperature. | |||||||||||||||||||||
| CacsPowerMgmtPDUTableHumidity2Value | 1.3.6.1.4.1.10418.16.2.5.3.1.26 | Integer32 | RO | obsolete | |||||||||||||||||
column · Integer32 · read-only · obsolete Humidity of this PM unit . If the humidity measurement is not installed this value will be 0. | |||||||||||||||||||||
| CacsPowerMgmtPDUTableHumidity2Max | 1.3.6.1.4.1.10418.16.2.5.3.1.27 | Integer32 | RW | obsolete | |||||||||||||||||
column · Integer32 · read-write · obsolete Maximum humidity detected in this PM unit. If the humidity measurement is not installed or the PDU does not have support for maximum value this value will be 0. Set with Zero value to clear the max. temperature. | |||||||||||||||||||||
| CacsPowerMgmtPDUTableHumidity3Value | 1.3.6.1.4.1.10418.16.2.5.3.1.28 | Integer32 | RO | obsolete | |||||||||||||||||
column · Integer32 · read-only · obsolete Humidity of this PM unit . If the humidity measurement is not installed this value will be 0. | |||||||||||||||||||||
| CacsPowerMgmtPDUTableHumidity3Max | 1.3.6.1.4.1.10418.16.2.5.3.1.29 | Integer32 | RW | obsolete | |||||||||||||||||
column · Integer32 · read-write · obsolete Maximum humidity detected in this PM unit. If the humidity measurement is not installed or the PDU does not have support for maximum value this value will be 0. Set with Zero value to clear the max. temperature. | |||||||||||||||||||||
| CacsPowerMgmtPDUTableVoltageNOS | 1.3.6.1.4.1.10418.16.2.5.3.1.30 | Integer32 | RO | obsolete | |||||||||||||||||
column · Integer32 · read-only · obsolete Number of voltage sensors in the PDU. | |||||||||||||||||||||
| CacsPowerMgmtPDUTableVoltage1Value | 1.3.6.1.4.1.10418.16.2.5.3.1.31 | Integer32 | RO | obsolete | |||||||||||||||||
column · Integer32 · read-only · obsolete Voltage of this sensor in this PDU unit. | |||||||||||||||||||||
| CacsPowerMgmtPDUTableVoltage1Max | 1.3.6.1.4.1.10418.16.2.5.3.1.32 | Integer32 | RW | obsolete | |||||||||||||||||
column · Integer32 · read-write · obsolete Maximum voltage of this sensor in this PDU unit. Set with Zero value to clear the maximum voltage. | |||||||||||||||||||||
| CacsPowerMgmtPDUTableVoltage2Value | 1.3.6.1.4.1.10418.16.2.5.3.1.33 | Integer32 | RO | obsolete | |||||||||||||||||
column · Integer32 · read-only · obsolete Voltage of this sensor in this PDU unit. | |||||||||||||||||||||
| CacsPowerMgmtPDUTableVoltage2Max | 1.3.6.1.4.1.10418.16.2.5.3.1.34 | Integer32 | RW | obsolete | |||||||||||||||||
column · Integer32 · read-write · obsolete Maximum voltage of this sensor in this PDU unit. Set with Zero value to clear the maximum voltage. | |||||||||||||||||||||
| CacsPowerMgmtPDUTableVoltage3Value | 1.3.6.1.4.1.10418.16.2.5.3.1.35 | Integer32 | RO | obsolete | |||||||||||||||||
column · Integer32 · read-only · obsolete Voltage of this sensor in this PDU unit. | |||||||||||||||||||||
| CacsPowerMgmtPDUTableVoltage3Max | 1.3.6.1.4.1.10418.16.2.5.3.1.36 | Integer32 | RW | obsolete | |||||||||||||||||
column · Integer32 · read-write · obsolete Maximum voltage of this sensor in this PDU unit. Set with Zero value to clear the maximum voltage. | |||||||||||||||||||||
| CacsPowerMgmtPDUTableNumberOfPhases | 1.3.6.1.4.1.10418.16.2.5.3.1.37 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current Number of phases of this PDU unit.
| |||||||||||||||||||||
| CacsPowerMgmtPDUTableNumberOfBanks | 1.3.6.1.4.1.10418.16.2.5.3.1.38 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Number of banks of this PDU unit. | |||||||||||||||||||||
| CacsPowerMgmtPDUTableCurrentValue | 1.3.6.1.4.1.10418.16.2.5.3.1.39 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Actual value of current sensor in this PDU.( A x 10 ) | |||||||||||||||||||||
| CacsPowerMgmtPDUTableCurrentMax | 1.3.6.1.4.1.10418.16.2.5.3.1.40 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Max detected value of current sensor in this PDU.( A x 10 ) | |||||||||||||||||||||
| CacsPowerMgmtPDUTableCurrentMin | 1.3.6.1.4.1.10418.16.2.5.3.1.41 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Min detected value of current sensor in this PDU.( A x 10 ) | |||||||||||||||||||||
| CacsPowerMgmtPDUTableCurrentAvg | 1.3.6.1.4.1.10418.16.2.5.3.1.42 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Average value for current sensor in this PDU.( A x 10 ) | |||||||||||||||||||||
| CacsPowerMgmtPDUTableCurrentReset | 1.3.6.1.4.1.10418.16.2.5.3.1.43 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current Reset max, min and avg values of current.
| |||||||||||||||||||||
| CacsPowerMgmtPDUTableVoltageType | 1.3.6.1.4.1.10418.16.2.5.3.1.44 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current Type of voltage values.
| |||||||||||||||||||||
| CacsPowerMgmtPDUTableVoltageValue | 1.3.6.1.4.1.10418.16.2.5.3.1.45 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Actual value of voltage sensor in this PDU unit.( V ) | |||||||||||||||||||||
| CacsPowerMgmtPDUTableVoltageMax | 1.3.6.1.4.1.10418.16.2.5.3.1.46 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Max detected value of voltage sensor in this PDU unit.( V ) | |||||||||||||||||||||
| CacsPowerMgmtPDUTableVoltageMin | 1.3.6.1.4.1.10418.16.2.5.3.1.47 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Min detected value of voltage sensor in this PDU unit.( V ) | |||||||||||||||||||||
| CacsPowerMgmtPDUTableVoltageAvg | 1.3.6.1.4.1.10418.16.2.5.3.1.48 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Average value for voltage sensor in this PDU unit.( V ) | |||||||||||||||||||||
| CacsPowerMgmtPDUTableVoltageReset | 1.3.6.1.4.1.10418.16.2.5.3.1.49 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current Reset max, min and avg values of voltage.
| |||||||||||||||||||||
| CacsPowerMgmtPDUTablePowerType | 1.3.6.1.4.1.10418.16.2.5.3.1.50 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current Type of power consumption values.( W x 10 )
| |||||||||||||||||||||
| CacsPowerMgmtPDUTablePowerValue | 1.3.6.1.4.1.10418.16.2.5.3.1.51 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Actual value of power consumption in this PDU unit.( W x 10 ) | |||||||||||||||||||||
| CacsPowerMgmtPDUTablePowerMax | 1.3.6.1.4.1.10418.16.2.5.3.1.52 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Max detected value of power consumption in this PDU unit.( W x 10 ) | |||||||||||||||||||||
| CacsPowerMgmtPDUTablePowerMin | 1.3.6.1.4.1.10418.16.2.5.3.1.53 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Min detected value of power consumption in this PDU unit.( W x 10 ) | |||||||||||||||||||||
| CacsPowerMgmtPDUTablePowerAvg | 1.3.6.1.4.1.10418.16.2.5.3.1.54 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Average value for power consumption in this PDU unit.( W x 10 ) | |||||||||||||||||||||
| CacsPowerMgmtPDUTablePowerReset | 1.3.6.1.4.1.10418.16.2.5.3.1.55 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current Reset max, min and avg values of power consumption.
| |||||||||||||||||||||
| CacsPowerMgmtPDUTablePowerFactorType | 1.3.6.1.4.1.10418.16.2.5.3.1.56 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current Type of power factor values.
| |||||||||||||||||||||
| CacsPowerMgmtPDUTablePowerFactorValue | 1.3.6.1.4.1.10418.16.2.5.3.1.57 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Actual value of power factor in this PDU unit.( PF x 100 ) | |||||||||||||||||||||
| CacsPowerMgmtPDUTablePowerFactorMax | 1.3.6.1.4.1.10418.16.2.5.3.1.58 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Max detected value of power factor in this PDU unit.( PF x 100 ) | |||||||||||||||||||||
| CacsPowerMgmtPDUTablePowerFactorMin | 1.3.6.1.4.1.10418.16.2.5.3.1.59 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Min detected value of power factor in this PDU unit.( PF x 100 ) | |||||||||||||||||||||
| CacsPowerMgmtPDUTablePowerFactorAvg | 1.3.6.1.4.1.10418.16.2.5.3.1.60 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Average value for power factor in this PDU unit.( PF x 100 ) | |||||||||||||||||||||
| CacsPowerMgmtPDUTablePowerFactorReset | 1.3.6.1.4.1.10418.16.2.5.3.1.61 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current Reset max, min and avg values of power factor.
| |||||||||||||||||||||
| CacsPowerMgmtPDUTableAlarm | 1.3.6.1.4.1.10418.16.2.5.3.1.62 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current Show the PDU alarm status.
| |||||||||||||||||||||
| CacsPowerMgmtPDUTableEnvSensors | 1.3.6.1.4.1.10418.16.2.5.3.1.63 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Number of environmental sensor in this PDU. | |||||||||||||||||||||
| SacsPowerMgmtTotalNumberOfOutlets | 1.3.6.1.4.1.10418.16.2.5.4 | Integer32 | RO | ||||||||||||||||||
scalar · Integer32 · read-only · current Number of outlets managed by the appliance. | |||||||||||||||||||||
| TacsPowerMgmtOutletsTable | 1.3.6.1.4.1.10418.16.2.5.5 | NA | |||||||||||||||||||
table · not-accessible · current This table contains the information about outlets. | |||||||||||||||||||||
| RacsPowerMgmtOutletsTableEntry | 1.3.6.1.4.1.10418.16.2.5.5.1 | NA | |||||||||||||||||||
row · not-accessible · current each entry has the information about the outlet. | |||||||||||||||||||||
| CacsPowerMgmtOutletsTablePortNumber | 1.3.6.1.4.1.10418.16.2.5.5.1.1 | InterfaceIndex | RO | ||||||||||||||||||
column · InterfaceIndex · read-only · current Serial Port number. | |||||||||||||||||||||
| CacsPowerMgmtOutletsTablePduNumber | 1.3.6.1.4.1.10418.16.2.5.5.1.2 | InterfaceIndex | RO | ||||||||||||||||||
column · InterfaceIndex · read-only · current Index. | |||||||||||||||||||||
| CacsPowerMgmtOutletsTableNumber | 1.3.6.1.4.1.10418.16.2.5.5.1.3 | InterfaceIndex | RO | ||||||||||||||||||
column · InterfaceIndex · read-only · current Number of the outlet in the PDU. | |||||||||||||||||||||
| CacsPowerMgmtOutletsTableName | 1.3.6.1.4.1.10418.16.2.5.5.1.4 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current Name of the outlet. | |||||||||||||||||||||
| CacsPowerMgmtOutletsTableStatus | 1.3.6.1.4.1.10418.16.2.5.5.1.5 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current Status of the outlet.
| |||||||||||||||||||||
| CacsPowerMgmtOutletsTablePowerControl | 1.3.6.1.4.1.10418.16.2.5.5.1.6 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current A set value of power*(2-6) will send command to PDU. noAction(1) = always returned in a GET. Does nothing if SET. powerOn(2) = when SET the power On command is sent to PDU. powerOff(3) = when SET the power Off command is sent to PDU. powerCycle(4)=when SET the power cycle command is sent to PDU. powerLock(5)= when SET the power lock command is sent to PDU. powerUnlock(6)=when SET the power unlock command is sent to PDU. The powerLock and powerUnlock are valid only for Cyclades-PM PDUs
| |||||||||||||||||||||
| CacsPowerMgmtOutletsTablePortName | 1.3.6.1.4.1.10418.16.2.5.5.1.7 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current Serial Port Name where the PDU is connected. | |||||||||||||||||||||
| CacsPowerMgmtOutletsTablePduId | 1.3.6.1.4.1.10418.16.2.5.5.1.8 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current PDU identification. | |||||||||||||||||||||
| SacsPowerMgmtNumberOfOutletGroup | 1.3.6.1.4.1.10418.16.2.5.6 | Integer32 | RO | ||||||||||||||||||
scalar · Integer32 · read-only · current Number of configured group of outlets. | |||||||||||||||||||||
| TacsPowerMgmtGroupTable | 1.3.6.1.4.1.10418.16.2.5.7 | NA | |||||||||||||||||||
table · not-accessible · current This table contains the information about group of outlets. | |||||||||||||||||||||
| RacsPowerMgmtGroupTableEntry | 1.3.6.1.4.1.10418.16.2.5.7.1 | NA | |||||||||||||||||||
row · not-accessible · current each entry has the information about group of outlets. | |||||||||||||||||||||
| CacsPowerMgmtGroupTableIndex | 1.3.6.1.4.1.10418.16.2.5.7.1.1 | InterfaceIndexOrZero | RO | ||||||||||||||||||
column · InterfaceIndexOrZero · read-only · current Index of the group. | |||||||||||||||||||||
| CacsPowerMgmtGroupTableName | 1.3.6.1.4.1.10418.16.2.5.7.1.2 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current Name of the group of outlets. | |||||||||||||||||||||
| CacsPowerMgmtGroupTableStatus | 1.3.6.1.4.1.10418.16.2.5.7.1.3 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current Status of the group of outlet.
| |||||||||||||||||||||
| CacsPowerMgmtGroupTablePowerControl | 1.3.6.1.4.1.10418.16.2.5.7.1.4 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current A set value of power*(2-6) will send command to PDU. noAction(1) = always returned in a GET. Does nothing if SET. powerOn(2) = when SET the power On command is sent to PDU. powerOff(3) = when SET the power Off command is sent to PDU. powerCycle(4)=when SET the power cycle command is sent to PDU.
| |||||||||||||||||||||
| TacsPowerMgmtPhasesTable | 1.3.6.1.4.1.10418.16.2.5.8 | NA | |||||||||||||||||||
table · not-accessible · current This table contains data monitoring of each detected phase. | |||||||||||||||||||||
| RacsPowerMgmtPhasesTableEntry | 1.3.6.1.4.1.10418.16.2.5.8.1 | NA | |||||||||||||||||||
row · not-accessible · current each entry has the data monitoring about phases. | |||||||||||||||||||||
| CacsPowerMgmtPhasesTablePortNumber | 1.3.6.1.4.1.10418.16.2.5.8.1.1 | InterfaceIndex | RO | ||||||||||||||||||
column · InterfaceIndex · read-only · current Number of serial port when the PDU is connected. | |||||||||||||||||||||
| CacsPowerMgmtPhasesTablePduIndex | 1.3.6.1.4.1.10418.16.2.5.8.1.2 | InterfaceIndexOrZero | RO | ||||||||||||||||||
column · InterfaceIndexOrZero · read-only · current A PDU position in the chain. | |||||||||||||||||||||
| CacsPowerMgmtPhasesTablePhaseIndex | 1.3.6.1.4.1.10418.16.2.5.8.1.3 | InterfaceIndexOrZero | RO | ||||||||||||||||||
column · InterfaceIndexOrZero · read-only · current phase index in the PDU. | |||||||||||||||||||||
| CacsPowerMgmtPhasesTablePhaseName | 1.3.6.1.4.1.10418.16.2.5.8.1.4 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current phase name in the PDU. | |||||||||||||||||||||
| CacsPowerMgmtPhasesTablePduId | 1.3.6.1.4.1.10418.16.2.5.8.1.5 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current PDU identification. | |||||||||||||||||||||
| CacsPowerMgmtPhasesTablePortName | 1.3.6.1.4.1.10418.16.2.5.8.1.6 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current Name of serial port when the PDU is connected. | |||||||||||||||||||||
| CacsPowerMgmtPhasesTableCurrentValue | 1.3.6.1.4.1.10418.16.2.5.8.1.7 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Actual value of current sensor in this phase.( A x 10 ) | |||||||||||||||||||||
| CacsPowerMgmtPhasesTableCurrentMax | 1.3.6.1.4.1.10418.16.2.5.8.1.8 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Max detected value of current sensor in this phase.( A x 10 ) | |||||||||||||||||||||
| CacsPowerMgmtPhasesTableCurrentMin | 1.3.6.1.4.1.10418.16.2.5.8.1.9 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Min detected value of current sensor in this phase.( A x 10 ) | |||||||||||||||||||||
| CacsPowerMgmtPhasesTableCurrentAvg | 1.3.6.1.4.1.10418.16.2.5.8.1.10 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Average value for current sensor in this phase.( A x 10 ) | |||||||||||||||||||||
| CacsPowerMgmtPhasesTableCurrentReset | 1.3.6.1.4.1.10418.16.2.5.8.1.11 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current Reset max, min and avg values of current.
| |||||||||||||||||||||
| CacsPowerMgmtPhasesTableVoltageType | 1.3.6.1.4.1.10418.16.2.5.8.1.12 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current Type of voltage values.
| |||||||||||||||||||||
| CacsPowerMgmtPhasesTableVoltageValue | 1.3.6.1.4.1.10418.16.2.5.8.1.13 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Actual value of voltage sensor in this phase.( V ) | |||||||||||||||||||||
| CacsPowerMgmtPhasesTableVoltageMax | 1.3.6.1.4.1.10418.16.2.5.8.1.14 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Max detected value of voltage sensor in this phase.( V ) | |||||||||||||||||||||
| CacsPowerMgmtPhasesTableVoltageMin | 1.3.6.1.4.1.10418.16.2.5.8.1.15 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Min detected value of voltage sensor in this phase.( V ) | |||||||||||||||||||||
| CacsPowerMgmtPhasesTableVoltageAvg | 1.3.6.1.4.1.10418.16.2.5.8.1.16 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Average value for voltage sensor in this phase.( V ) | |||||||||||||||||||||
| CacsPowerMgmtPhasesTableVoltageReset | 1.3.6.1.4.1.10418.16.2.5.8.1.17 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current Reset max, min and avg values of voltage.
| |||||||||||||||||||||
| CacsPowerMgmtPhasesTablePowerType | 1.3.6.1.4.1.10418.16.2.5.8.1.18 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current Type of power consumption values.
| |||||||||||||||||||||
| CacsPowerMgmtPhasesTablePowerValue | 1.3.6.1.4.1.10418.16.2.5.8.1.19 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Actual value of power consumption in this phase.( W x 10 ) | |||||||||||||||||||||
| CacsPowerMgmtPhasesTablePowerMax | 1.3.6.1.4.1.10418.16.2.5.8.1.20 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Max detected value of power consumption in this phase.( W x 10 ) | |||||||||||||||||||||
| CacsPowerMgmtPhasesTablePowerMin | 1.3.6.1.4.1.10418.16.2.5.8.1.21 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Min detected value of power consumption in this phase.( W x 10 ) | |||||||||||||||||||||
| CacsPowerMgmtPhasesTablePowerAvg | 1.3.6.1.4.1.10418.16.2.5.8.1.22 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Average value for power consumption in this phase.( W x 10 ) | |||||||||||||||||||||
| CacsPowerMgmtPhasesTablePowerReset | 1.3.6.1.4.1.10418.16.2.5.8.1.23 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current Reset max, min and avg values of power consumption.
| |||||||||||||||||||||
| CacsPowerMgmtPhasesTablePowerFactorType | 1.3.6.1.4.1.10418.16.2.5.8.1.24 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current Type of power factor values.
| |||||||||||||||||||||
| CacsPowerMgmtPhasesTablePowerFactorValue | 1.3.6.1.4.1.10418.16.2.5.8.1.25 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Actual value of power factor in this phase.( PF x 100 ) | |||||||||||||||||||||
| CacsPowerMgmtPhasesTablePowerFactorMax | 1.3.6.1.4.1.10418.16.2.5.8.1.26 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Max detected value of power factor in this phase.( PF x 100 ) | |||||||||||||||||||||
| CacsPowerMgmtPhasesTablePowerFactorMin | 1.3.6.1.4.1.10418.16.2.5.8.1.27 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Min detected value of power factor in this phase.( PF x 100 ) | |||||||||||||||||||||
| CacsPowerMgmtPhasesTablePowerFactorAvg | 1.3.6.1.4.1.10418.16.2.5.8.1.28 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Average value for power factor in this phase.( PF x 100 ) | |||||||||||||||||||||
| CacsPowerMgmtPhasesTablePowerFactorReset | 1.3.6.1.4.1.10418.16.2.5.8.1.29 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current Reset max, min and avg values of power factor.
| |||||||||||||||||||||
| CacsPowerMgmtPhasesTableAlarm | 1.3.6.1.4.1.10418.16.2.5.8.1.30 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current Show the phase alarm status.
| |||||||||||||||||||||
| TacsPowerMgmtBanksTable | 1.3.6.1.4.1.10418.16.2.5.9 | NA | |||||||||||||||||||
table · not-accessible · current This table contains data monitoring of each detected bank. | |||||||||||||||||||||
| RacsPowerMgmtBanksTableEntry | 1.3.6.1.4.1.10418.16.2.5.9.1 | NA | |||||||||||||||||||
row · not-accessible · current each entry has the data monitoring about bank. | |||||||||||||||||||||
| CacsPowerMgmtBanksTablePortNumber | 1.3.6.1.4.1.10418.16.2.5.9.1.1 | InterfaceIndex | RO | ||||||||||||||||||
column · InterfaceIndex · read-only · current Number of serial port when the PDU is connected. | |||||||||||||||||||||
| CacsPowerMgmtBanksTablePduIndex | 1.3.6.1.4.1.10418.16.2.5.9.1.2 | InterfaceIndexOrZero | RO | ||||||||||||||||||
column · InterfaceIndexOrZero · read-only · current A PDU position in the chain. | |||||||||||||||||||||
| CacsPowerMgmtBanksTableBankIndex | 1.3.6.1.4.1.10418.16.2.5.9.1.3 | InterfaceIndexOrZero | RO | ||||||||||||||||||
column · InterfaceIndexOrZero · read-only · current Bank index in the PDU. | |||||||||||||||||||||
| CacsPowerMgmtBanksTableBankName | 1.3.6.1.4.1.10418.16.2.5.9.1.4 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current Bank name in the PDU. | |||||||||||||||||||||
| CacsPowerMgmtBanksTablePduId | 1.3.6.1.4.1.10418.16.2.5.9.1.5 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current PDU identification. | |||||||||||||||||||||
| CacsPowerMgmtBanksTablePortName | 1.3.6.1.4.1.10418.16.2.5.9.1.6 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current Name of serial port when the PDU is connected. | |||||||||||||||||||||
| CacsPowerMgmtBanksTableCurrentValue | 1.3.6.1.4.1.10418.16.2.5.9.1.7 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Actual value of current sensor in this bank.( A x 10 ) | |||||||||||||||||||||
| CacsPowerMgmtBanksTableCurrentMax | 1.3.6.1.4.1.10418.16.2.5.9.1.8 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Max detected value of current sensor in this bank.( A x 10 ) | |||||||||||||||||||||
| CacsPowerMgmtBanksTableCurrentMin | 1.3.6.1.4.1.10418.16.2.5.9.1.9 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Min detected value of current sensor in this bank.( A x 10 ) | |||||||||||||||||||||
| CacsPowerMgmtBanksTableCurrentAvg | 1.3.6.1.4.1.10418.16.2.5.9.1.10 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Average value for current sensor in this bank.( A x 10 ) | |||||||||||||||||||||
| CacsPowerMgmtBanksTableCurrentReset | 1.3.6.1.4.1.10418.16.2.5.9.1.11 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current Reset max, min and avg values of current.
| |||||||||||||||||||||
| CacsPowerMgmtBanksTableVoltageType | 1.3.6.1.4.1.10418.16.2.5.9.1.12 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current Type of voltage values.
| |||||||||||||||||||||
| CacsPowerMgmtBanksTableVoltageValue | 1.3.6.1.4.1.10418.16.2.5.9.1.13 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Actual value of voltage sensor in this bank.( V ) | |||||||||||||||||||||
| CacsPowerMgmtBanksTableVoltageMax | 1.3.6.1.4.1.10418.16.2.5.9.1.14 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Max detected value of voltage sensor in this bank.( V ) | |||||||||||||||||||||
| CacsPowerMgmtBanksTableVoltageMin | 1.3.6.1.4.1.10418.16.2.5.9.1.15 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Min detected value of voltage sensor in this bank.( V ) | |||||||||||||||||||||
| CacsPowerMgmtBanksTableVoltageAvg | 1.3.6.1.4.1.10418.16.2.5.9.1.16 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Average value for voltage sensor in this bank.( V ) | |||||||||||||||||||||
| CacsPowerMgmtBanksTableVoltageReset | 1.3.6.1.4.1.10418.16.2.5.9.1.17 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current Reset max, min and avg values of voltage.
| |||||||||||||||||||||
| CacsPowerMgmtBanksTablePowerType | 1.3.6.1.4.1.10418.16.2.5.9.1.18 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current Type of power consumption values.
| |||||||||||||||||||||
| CacsPowerMgmtBanksTablePowerValue | 1.3.6.1.4.1.10418.16.2.5.9.1.19 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Actual value of power consumption in this bank.( W x 10 ) | |||||||||||||||||||||
| CacsPowerMgmtBanksTablePowerMax | 1.3.6.1.4.1.10418.16.2.5.9.1.20 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Max detected value of power consumption in this bank.( W x 10 ) | |||||||||||||||||||||
| CacsPowerMgmtBanksTablePowerMin | 1.3.6.1.4.1.10418.16.2.5.9.1.21 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Min detected value of power consumption in this bank.( W x 10 ) | |||||||||||||||||||||
| CacsPowerMgmtBanksTablePowerAvg | 1.3.6.1.4.1.10418.16.2.5.9.1.22 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Average value for power consumption in this bank.( W x 10 ) | |||||||||||||||||||||
| CacsPowerMgmtBanksTablePowerReset | 1.3.6.1.4.1.10418.16.2.5.9.1.23 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current Reset max, min and avg values of power consumption.
| |||||||||||||||||||||
| CacsPowerMgmtBanksTablePowerFactorType | 1.3.6.1.4.1.10418.16.2.5.9.1.24 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current Type of power factor values.
| |||||||||||||||||||||
| CacsPowerMgmtBanksTablePowerFactorValue | 1.3.6.1.4.1.10418.16.2.5.9.1.25 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Actual value of power factor in this bank.( PF x 100 ) | |||||||||||||||||||||
| CacsPowerMgmtBanksTablePowerFactorMax | 1.3.6.1.4.1.10418.16.2.5.9.1.26 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Max detected value of power factor in this bank.( PF x 100 ) | |||||||||||||||||||||
| CacsPowerMgmtBanksTablePowerFactorMin | 1.3.6.1.4.1.10418.16.2.5.9.1.27 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Min detected value of power factor in this bank.( PF x 100 ) | |||||||||||||||||||||
| CacsPowerMgmtBanksTablePowerFactorAvg | 1.3.6.1.4.1.10418.16.2.5.9.1.28 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Average value for power factor in this bank.( PF x 100 ) | |||||||||||||||||||||
| CacsPowerMgmtBanksTablePowerFactorReset | 1.3.6.1.4.1.10418.16.2.5.9.1.29 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current Reset max, min and avg values of power factor.
| |||||||||||||||||||||
| CacsPowerMgmtBanksTableAlarm | 1.3.6.1.4.1.10418.16.2.5.9.1.30 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current Show the bank alarm status.
| |||||||||||||||||||||
| TacsPowerMgmtEnvMonTable | 1.3.6.1.4.1.10418.16.2.5.10 | NA | |||||||||||||||||||
table · not-accessible · current This table contains data monitoring of each detected environmental sensor. | |||||||||||||||||||||
| RacsPowerMgmtEnvMonTableEntry | 1.3.6.1.4.1.10418.16.2.5.10.1 | NA | |||||||||||||||||||
row · not-accessible · current each entry has the data monitoring about environmental sensors. | |||||||||||||||||||||
| CacsPowerMgmtEnvMonTablePortNumber | 1.3.6.1.4.1.10418.16.2.5.10.1.1 | InterfaceIndex | RO | ||||||||||||||||||
column · InterfaceIndex · read-only · current Number of serial port when the PDU is connected. | |||||||||||||||||||||
| CacsPowerMgmtEnvMonTablePduIndex | 1.3.6.1.4.1.10418.16.2.5.10.1.2 | InterfaceIndexOrZero | RO | ||||||||||||||||||
column · InterfaceIndexOrZero · read-only · current A PDU position in the chain. | |||||||||||||||||||||
| CacsPowerMgmtEnvMonTableIndex | 1.3.6.1.4.1.10418.16.2.5.10.1.3 | InterfaceIndexOrZero | RO | ||||||||||||||||||
column · InterfaceIndexOrZero · read-only · current envmon sensor index. | |||||||||||||||||||||
| CacsPowerMgmtEnvMonTableName | 1.3.6.1.4.1.10418.16.2.5.10.1.4 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current envmon sensor name. | |||||||||||||||||||||
| CacsPowerMgmtEnvMonTablePduId | 1.3.6.1.4.1.10418.16.2.5.10.1.5 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current PDU identification. | |||||||||||||||||||||
| CacsPowerMgmtEnvMonTablePortName | 1.3.6.1.4.1.10418.16.2.5.10.1.6 | DisplayString | RO | ||||||||||||||||||
column · DisplayString · read-only · current Name of serial port when the PDU is connected. | |||||||||||||||||||||
| CacsPowerMgmtEnvMonTableType | 1.3.6.1.4.1.10418.16.2.5.10.1.7 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current The type of environmental monitor.
| |||||||||||||||||||||
| CacsPowerMgmtEnvMonTableStatus | 1.3.6.1.4.1.10418.16.2.5.10.1.8 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current Status of digital sensors: Dry-Contact, Water level, Smoke sensor, Motion sensor.
| |||||||||||||||||||||
| CacsPowerMgmtEnvMonTableValue | 1.3.6.1.4.1.10418.16.2.5.10.1.9 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Detected value for envmon sensors. Temperature: C x 10. Humidity: %. Air flow: afu. | |||||||||||||||||||||
| CacsPowerMgmtEnvMonTableMaxValue | 1.3.6.1.4.1.10418.16.2.5.10.1.10 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Max detected value for envmon sensors. Temperature: C x 10. Humidity: %. Air flow: afu. | |||||||||||||||||||||
| TacsPowerMgmtOutElecMonTable | 1.3.6.1.4.1.10418.16.2.5.11 | NA | |||||||||||||||||||
table · not-accessible · current This table contains the information about data monitoring of outlets. | |||||||||||||||||||||
| RacsPowerMgmtOutElecMonTableEntry | 1.3.6.1.4.1.10418.16.2.5.11.1 | NA | |||||||||||||||||||
row · not-accessible · current each entry has the information about the outlet. | |||||||||||||||||||||
| CacsPowerMgmtOutElecMonTablePortNumber | 1.3.6.1.4.1.10418.16.2.5.11.1.1 | InterfaceIndex | RO | ||||||||||||||||||
column · InterfaceIndex · read-only · current Serial Port number. | |||||||||||||||||||||
| CacsPowerMgmtOutElecMonTablePduNumber | 1.3.6.1.4.1.10418.16.2.5.11.1.2 | InterfaceIndex | RO | ||||||||||||||||||
column · InterfaceIndex · read-only · current Index. | |||||||||||||||||||||
| CacsPowerMgmtOutElecMonTableNumber | 1.3.6.1.4.1.10418.16.2.5.11.1.3 | InterfaceIndex | RO | ||||||||||||||||||
column · InterfaceIndex · read-only · current Number of the outlet in the PDU. | |||||||||||||||||||||
| CacsPowerMgmtOutElecMonTableCurrentValue | 1.3.6.1.4.1.10418.16.2.5.11.1.4 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Actual value of outlet current sensor.( A x 10 ) | |||||||||||||||||||||
| CacsPowerMgmtOutElecMonTableCurrentMax | 1.3.6.1.4.1.10418.16.2.5.11.1.5 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Max detected value of outlet current sensor.( A x 10 ) | |||||||||||||||||||||
| CacsPowerMgmtOutElecMonTableCurrentMin | 1.3.6.1.4.1.10418.16.2.5.11.1.6 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Min detected value of outlet current sensor.( A x 10 ) | |||||||||||||||||||||
| CacsPowerMgmtOutElecMonTableCurrentAvg | 1.3.6.1.4.1.10418.16.2.5.11.1.7 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Average value for outlet current sensor.( A x 10 ) | |||||||||||||||||||||
| CacsPowerMgmtOutElecMonTableCurrentReset | 1.3.6.1.4.1.10418.16.2.5.11.1.8 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current Reset max, min and avertage values of outlet current.
| |||||||||||||||||||||
| CacsPowerMgmtOutElecMonTablePowerValue | 1.3.6.1.4.1.10418.16.2.5.11.1.9 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Actual value of outlet power comsumption sensor.( W x 10 ) | |||||||||||||||||||||
| CacsPowerMgmtOutElecMonTablePowerMax | 1.3.6.1.4.1.10418.16.2.5.11.1.10 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Max detected value of outlet power comsumption sensor.( W x 10 ) | |||||||||||||||||||||
| CacsPowerMgmtOutElecMonTablePowerMin | 1.3.6.1.4.1.10418.16.2.5.11.1.11 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Min detected value of outlet power comsumption sensor.( W x 10 ) | |||||||||||||||||||||
| CacsPowerMgmtOutElecMonTablePowerAvg | 1.3.6.1.4.1.10418.16.2.5.11.1.12 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Average value for outlet power comsumption sensor.( W x 10 ) | |||||||||||||||||||||
| CacsPowerMgmtOutElecMonTablePowerReset | 1.3.6.1.4.1.10418.16.2.5.11.1.13 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current Reset max, min and avertage values of outlet power comsumption.
| |||||||||||||||||||||
| CacsPowerMgmtOutElecMonTableVoltageValue | 1.3.6.1.4.1.10418.16.2.5.11.1.14 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Actual value of outlet voltage sensor.( V ) | |||||||||||||||||||||
| CacsPowerMgmtOutElecMonTableVoltageMax | 1.3.6.1.4.1.10418.16.2.5.11.1.15 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Max detected value of outlet voltage sensor.( V ) | |||||||||||||||||||||
| CacsPowerMgmtOutElecMonTableVoltageMin | 1.3.6.1.4.1.10418.16.2.5.11.1.16 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Min detected value of outlet voltage sensor.( V ) | |||||||||||||||||||||
| CacsPowerMgmtOutElecMonTableVoltageAvg | 1.3.6.1.4.1.10418.16.2.5.11.1.17 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Average value for outlet voltage sensor.( V ) | |||||||||||||||||||||
| CacsPowerMgmtOutElecMonTableVoltageReset | 1.3.6.1.4.1.10418.16.2.5.11.1.18 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current Reset max, min and avertage values of outlet voltage.
| |||||||||||||||||||||
| CacsPowerMgmtOutElecMonTablePowerFactorValue | 1.3.6.1.4.1.10418.16.2.5.11.1.19 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Actual value of outlet power-factor sensor.( PF x 100 ) | |||||||||||||||||||||
| CacsPowerMgmtOutElecMonTablePowerFactorMax | 1.3.6.1.4.1.10418.16.2.5.11.1.20 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Max detected value of outlet power-factor sensor.( PF x 100 ) | |||||||||||||||||||||
| CacsPowerMgmtOutElecMonTablePowerFactorMin | 1.3.6.1.4.1.10418.16.2.5.11.1.21 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Min detected value of outlet power-factor sensor.( PF x 100 ) | |||||||||||||||||||||
| CacsPowerMgmtOutElecMonTablePowerFactorAvg | 1.3.6.1.4.1.10418.16.2.5.11.1.22 | Integer32 | RO | ||||||||||||||||||
column · Integer32 · read-only · current Average value for outlet power-factor sensor.( PF x 100 ) | |||||||||||||||||||||
| CacsPowerMgmtOutElecMonTablePowerFactorReset | 1.3.6.1.4.1.10418.16.2.5.11.1.23 | INTEGER | RW | ||||||||||||||||||
column · INTEGER · read-write · current Reset max, min and avertage values of outlet power-factor.
| |||||||||||||||||||||
| CacsPowerMgmtOutElecMonTableAlarm | 1.3.6.1.4.1.10418.16.2.5.11.1.24 | INTEGER | RO | ||||||||||||||||||
column · INTEGER · read-only · current Show the outlet alarm status.
| |||||||||||||||||||||
| NacsTrapObject | 1.3.6.1.4.1.10418.16.2.6 | ||||||||||||||||||||