PowerNet-MIB
American Power Conversion Corp.snmptranslate -m PowerNet-MIB -Tpsnmpwalk -v2c -c <community> -m PowerNet-MIB <host> 1.3.6.1.4.1.318Imports
| SNMP-FRAMEWORK-MIB | SnmpAdminString |
|---|---|
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
| SNMPv2-SMI | Bits, Gauge32, Integer32, IpAddress, MODULE-IDENTITY, MibIdentifier, OBJECT-IDENTITY, OBJECT-TYPE, TRAP-TYPE, TimeTicks, Unsigned32, enterprises, iso |
| SNMPv2-TC | DisplayString, PhysAddress, TEXTUAL-CONVENTION |
OID tree
| Name | OID | Type | Access | Status | Example | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Napc | 1.3.6.1.4.1.318 | ||||||||||||||||||||
| !communicationLost | 1.3.6.1.4.1.318.0.1 | ||||||||||||||||||||
notification SEVERE: Communication to the UPS has been lost. Steps to reestablish communication are in progress.
| |||||||||||||||||||||
| !upsOverload | 1.3.6.1.4.1.318.0.2 | ||||||||||||||||||||
notification SEVERE: The UPS has sensed a load greater than 100 percent of its rated capacity.
| |||||||||||||||||||||
| !upsDiagnosticsFailed | 1.3.6.1.4.1.318.0.3 | ||||||||||||||||||||
| !upsDischarged | 1.3.6.1.4.1.318.0.4 | ||||||||||||||||||||
notification SEVERE: The UPS batteries are discharged; if utility power fails an immediate low battery condition will exist. Sufficient runtime for necessary action cannot be guaranteed.
| |||||||||||||||||||||
| !upsOnBattery | 1.3.6.1.4.1.318.0.5 | ||||||||||||||||||||
| !smartBoostOn | 1.3.6.1.4.1.318.0.6 | ||||||||||||||||||||
| !lowBattery | 1.3.6.1.4.1.318.0.7 | ||||||||||||||||||||
notification SEVERE: The UPS batteries are low and will soon be exhausted. If utility power is not restored the UPS will put itself to 'sleep' and immediately cut power to the load.
| |||||||||||||||||||||
| !communicationEstablished | 1.3.6.1.4.1.318.0.8 | ||||||||||||||||||||
| !powerRestored | 1.3.6.1.4.1.318.0.9 | ||||||||||||||||||||
| !upsDiagnosticsPassed | 1.3.6.1.4.1.318.0.10 | ||||||||||||||||||||
| !returnFromLowBattery | 1.3.6.1.4.1.318.0.11 | ||||||||||||||||||||
| !upsTurnedOff | 1.3.6.1.4.1.318.0.12 | ||||||||||||||||||||
| !upsSleeping | 1.3.6.1.4.1.318.0.13 | ||||||||||||||||||||
notification WARNING: The UPS is entering 'sleep' mode. Power to the load will be cut off.
| |||||||||||||||||||||
| !upsWokeUp | 1.3.6.1.4.1.318.0.14 | ||||||||||||||||||||
notification INFORMATION: The UPS has returned from 'sleep' mode. Power to the load has been restored.
| |||||||||||||||||||||
| !upsRebootStarted | 1.3.6.1.4.1.318.0.15 | ||||||||||||||||||||
notification WARNING: The UPS has started its reboot sequence. The UPS will reboot itself at this time.
| |||||||||||||||||||||
| !upsDipSwitchChanged | 1.3.6.1.4.1.318.0.16 | ||||||||||||||||||||
notification WARNING: The dip switch settings on the UPS have been changed, possibly altering UPS performance.
| |||||||||||||||||||||
| !upsBatteryNeedsReplacement | 1.3.6.1.4.1.318.0.17 | ||||||||||||||||||||
| !contactFault | 1.3.6.1.4.1.318.0.18 | ||||||||||||||||||||
notification SEVERE: One of the contacts on the Environmental Monitor has changed from its default position. The first variable is the contact number that is faulted.
| |||||||||||||||||||||
| !contactFaultResolved | 1.3.6.1.4.1.318.0.19 | ||||||||||||||||||||
notification INFORMATIONAL: A fault on one of the Environmental Monitor contacts has been resolved. The first variable is the contact number that has been resolved.
| |||||||||||||||||||||
| !hardwareFailureBypass | 1.3.6.1.4.1.318.0.20 | ||||||||||||||||||||
| !softwareBypass | 1.3.6.1.4.1.318.0.21 | ||||||||||||||||||||
| !switchedBypass | 1.3.6.1.4.1.318.0.22 | ||||||||||||||||||||
| !returnFromBypass | 1.3.6.1.4.1.318.0.23 | ||||||||||||||||||||
| !bypassPowerSupplyFailure | 1.3.6.1.4.1.318.0.24 | ||||||||||||||||||||
| !baseFanFailure | 1.3.6.1.4.1.318.0.25 | ||||||||||||||||||||
| !batteryPackCommLost | 1.3.6.1.4.1.318.0.26 | ||||||||||||||||||||
| !batteryPackCommEstablished | 1.3.6.1.4.1.318.0.27 | ||||||||||||||||||||
notification INFORMATIONAL: UPS is communicating with the external battery packs.
| |||||||||||||||||||||
| !calibrationStart | 1.3.6.1.4.1.318.0.28 | ||||||||||||||||||||
notification INFORMATIONAL: A battery calibration test has been initiated on the UPS.
| |||||||||||||||||||||
| !restartAgent | 1.3.6.1.4.1.318.0.29 | ||||||||||||||||||||
| !upsTurnedOn | 1.3.6.1.4.1.318.0.30 | ||||||||||||||||||||
| !smartAvrReducing | 1.3.6.1.4.1.318.0.31 | ||||||||||||||||||||
| !codeAuthenticationDone | 1.3.6.1.4.1.318.0.32 | ||||||||||||||||||||
notification INFORMATIONAL: Authentication on agent code image is done. | |||||||||||||||||||||
| !upsOverloadCleared | 1.3.6.1.4.1.318.0.33 | ||||||||||||||||||||
| !smartBoostOff | 1.3.6.1.4.1.318.0.34 | ||||||||||||||||||||
| !smartAvrReducingOff | 1.3.6.1.4.1.318.0.35 | ||||||||||||||||||||
| !upsBatteryReplaced | 1.3.6.1.4.1.318.0.36 | ||||||||||||||||||||
| !calibrationEnd | 1.3.6.1.4.1.318.0.37 | ||||||||||||||||||||
| !dischargeCleared | 1.3.6.1.4.1.318.0.38 | ||||||||||||||||||||
| !gracefulShutdown | 1.3.6.1.4.1.318.0.39 | ||||||||||||||||||||
| !outletOn | 1.3.6.1.4.1.318.0.41 | ||||||||||||||||||||
notification WARNING: The specified PDU outlet has turned on. If sPDUOutletControlIndex equals zero, then all outlets have turned on.
| |||||||||||||||||||||
| !outletOff | 1.3.6.1.4.1.318.0.42 | ||||||||||||||||||||
notification WARNING: The specified PDU outlet has turned off. If sPDUOutletControlIndex equals zero, then all outlets have turned off.
| |||||||||||||||||||||
| !outletReboot | 1.3.6.1.4.1.318.0.43 | ||||||||||||||||||||
notification WARNING: The specified PDU outlet has rebooted. If sPDUOutletControlIndex equals zero, then all outlets have rebooted.
| |||||||||||||||||||||
| !configChangeSNMP | 1.3.6.1.4.1.318.0.44 | ||||||||||||||||||||
| !configChangeOutlet | 1.3.6.1.4.1.318.0.45 | ||||||||||||||||||||
notification WARNING: The specified PDU outlet has changed configuration. If sPDUOutletConfigIndex equals zero, then the Master outlet has changed configuration.
| |||||||||||||||||||||
| !accessViolationConsole | 1.3.6.1.4.1.318.0.46 | ||||||||||||||||||||
notification WARNING: Someone has attempted to login via the console with the incorrect password.
| |||||||||||||||||||||
| !accessViolationHTTP | 1.3.6.1.4.1.318.0.47 | ||||||||||||||||||||
notification WARNING: Someone has attempted to login via HTTP with the incorrect password.
| |||||||||||||||||||||
| !passwordChange | 1.3.6.1.4.1.318.0.48 | ||||||||||||||||||||
| !badVoltage | 1.3.6.1.4.1.318.0.49 | ||||||||||||||||||||
| !badVoltageCleared | 1.3.6.1.4.1.318.0.50 | ||||||||||||||||||||
notification INFORMATIONAL: The output voltage has returned to an acceptable level.
| |||||||||||||||||||||
| !chargerFailure | 1.3.6.1.4.1.318.0.51 | ||||||||||||||||||||
| !chargerFailureCleared | 1.3.6.1.4.1.318.0.52 | ||||||||||||||||||||
notification INFORMATIONAL: The battery charger failure condition has been cleared.
| |||||||||||||||||||||
| !batteryOverTemperature | 1.3.6.1.4.1.318.0.53 | ||||||||||||||||||||
| !batteryOverTemperatureCleared | 1.3.6.1.4.1.318.0.54 | ||||||||||||||||||||
| !smartRelayFault | 1.3.6.1.4.1.318.0.55 | ||||||||||||||||||||
| !smartRelayFaultCleared | 1.3.6.1.4.1.318.0.56 | ||||||||||||||||||||
notification INFORMATIONAL: SmartBoost(TM) or SmartTrim(TM) relay fault has been cleared.
| |||||||||||||||||||||
| !humidityThresholdViolation1 | 1.3.6.1.4.1.318.0.57 | ||||||||||||||||||||
notification SEVERE: Probe 1 humidity threshold violated. The first variable is the current humidity.
| |||||||||||||||||||||
| !humidityThresholdViolationCleared1 | 1.3.6.1.4.1.318.0.58 | ||||||||||||||||||||
notification INFORMATIONAL: An Environmental Monitor humidity threshold violation has been cleared on probe 1.
| |||||||||||||||||||||
| !temperatureThresholdViolation1 | 1.3.6.1.4.1.318.0.59 | ||||||||||||||||||||
notification SEVERE: An Environmental Monitor temperature threshold has been violated on probe 1. The first variable is the current temperature.
| |||||||||||||||||||||
| !temperatureThresholdViolationCleared1 | 1.3.6.1.4.1.318.0.60 | ||||||||||||||||||||
notification INFORMATIONAL: An Environmental Monitor temperature threshold violation has been cleared on probe 1.
| |||||||||||||||||||||
| !humidityThresholdViolation2 | 1.3.6.1.4.1.318.0.61 | ||||||||||||||||||||
notification SEVERE: An Environmental Monitor humidity threshold has been violated on probe 2. The first variable is the current humidity.
| |||||||||||||||||||||
| !humidityThresholdViolationCleared2 | 1.3.6.1.4.1.318.0.62 | ||||||||||||||||||||
notification INFORMATIONAL: An Environmental Monitor humidity threshold violation has been cleared on probe 2.
| |||||||||||||||||||||
| !temperatureThresholdViolation2 | 1.3.6.1.4.1.318.0.63 | ||||||||||||||||||||
notification SEVERE: An Environmental Monitor temperature threshold has been violated on probe 2. The first variable is the current temperature.
| |||||||||||||||||||||
| !temperatureThresholdViolationCleared2 | 1.3.6.1.4.1.318.0.64 | ||||||||||||||||||||
notification INFORMATIONAL: An Environmental Monitor temperature threshold violation has been cleared on probe 2.
| |||||||||||||||||||||
| !mupsCommunicationEstablished | 1.3.6.1.4.1.318.0.65 | ||||||||||||||||||||
notification INFORMATIONAL: Communication with the Environmental Monitor has been established.
| |||||||||||||||||||||
| !mupsCommunicationLost | 1.3.6.1.4.1.318.0.66 | ||||||||||||||||||||
notification SEVERE: Communication to the Environmental Monitor has been lost. Steps to reestablish communication are in progress.
| |||||||||||||||||||||
| !batteryIncrease | 1.3.6.1.4.1.318.0.67 | ||||||||||||||||||||
| !batteryDecrease | 1.3.6.1.4.1.318.0.68 | ||||||||||||||||||||
| !powerModuleIncrease | 1.3.6.1.4.1.318.0.69 | ||||||||||||||||||||
| !powerModuleDecrease | 1.3.6.1.4.1.318.0.70 | ||||||||||||||||||||
| !intelligenceModuleInserted | 1.3.6.1.4.1.318.0.71 | ||||||||||||||||||||
| !intelligenceModuleRemoved | 1.3.6.1.4.1.318.0.72 | ||||||||||||||||||||
| !rintelligenceModuleInserted | 1.3.6.1.4.1.318.0.73 | ||||||||||||||||||||
| !rintelligenceModuleRemoved | 1.3.6.1.4.1.318.0.74 | ||||||||||||||||||||
| !extBatteryFrameIncease | 1.3.6.1.4.1.318.0.75 | ||||||||||||||||||||
| !extBatteryFrameDecrease | 1.3.6.1.4.1.318.0.76 | ||||||||||||||||||||
| !abnormalCondition | 1.3.6.1.4.1.318.0.77 | ||||||||||||||||||||
notification SEVERE: An abnormal condition has been detected. The first variable is the fault condition.
| |||||||||||||||||||||
| !abnormalConditionCleared | 1.3.6.1.4.1.318.0.78 | ||||||||||||||||||||
notification INFORMATIONAL: An abnormal condition has been cleared. The first variable is the fault condition.
| |||||||||||||||||||||
| !deviceStatusChange | 1.3.6.1.4.1.318.0.79 | ||||||||||||||||||||
notification INFORMATIONAL: The status of the device being monitored has changed.
| |||||||||||||||||||||
| !noBatteries | 1.3.6.1.4.1.318.0.80 | ||||||||||||||||||||
| !noBatteriesCleared | 1.3.6.1.4.1.318.0.81 | ||||||||||||||||||||
| !userAdded | 1.3.6.1.4.1.318.0.82 | ||||||||||||||||||||
| !userDeleted | 1.3.6.1.4.1.318.0.83 | ||||||||||||||||||||
| !userModified | 1.3.6.1.4.1.318.0.84 | ||||||||||||||||||||
| !msvmCommunicationEstablished | 1.3.6.1.4.1.318.0.85 | ||||||||||||||||||||
notification INFORMATIONAL: Communications with the MasterSwitch VM has been established. | |||||||||||||||||||||
| !msvmCommunicationLost | 1.3.6.1.4.1.318.0.86 | ||||||||||||||||||||
notification SEVERE: Communications with the MasterSwitch VM has been lost. | |||||||||||||||||||||
| !msvmOverload | 1.3.6.1.4.1.318.0.87 | ||||||||||||||||||||
notification SEVERE: The MasterSwitch VM in an overload condition. | |||||||||||||||||||||
| !msvmOverloadCleared | 1.3.6.1.4.1.318.0.88 | ||||||||||||||||||||
notification INFORMATIONAL: The overload condition on the MasterSwitch VM has been cleared. | |||||||||||||||||||||
| !msvmOutletOn | 1.3.6.1.4.1.318.0.89 | ||||||||||||||||||||
notification INFORMATIONAL: An outlet on the MasterSwitch VM has turned on. | |||||||||||||||||||||
| !msvmOutletOff | 1.3.6.1.4.1.318.0.90 | ||||||||||||||||||||
notification INFORMATIONAL: An outlet on the MasterSwitch VM has turned off. | |||||||||||||||||||||
| !msvmDeviceConfigChange | 1.3.6.1.4.1.318.0.91 | ||||||||||||||||||||
notification INFORMATIONAL: A device configuration change has been made on a MasterSwitch VM. | |||||||||||||||||||||
| !msvmOutletConfigChange | 1.3.6.1.4.1.318.0.92 | ||||||||||||||||||||
notification INFORMATIONAL: An outlet configuration change has been made on a MasterSwitch VM. | |||||||||||||||||||||
| !msvmLowLoad | 1.3.6.1.4.1.318.0.93 | ||||||||||||||||||||
notification INFORMATIONAL: The MasterSwitch VM has violated the low load threshold. | |||||||||||||||||||||
| !msvmLowLoadCleared | 1.3.6.1.4.1.318.0.94 | ||||||||||||||||||||
notification INFORMATIONAL: The low load condition on the MasterSwitch VM has been cleared. | |||||||||||||||||||||
| !msvmNearOverload | 1.3.6.1.4.1.318.0.95 | ||||||||||||||||||||
notification SEVERE: The MasterSwitch VM is approaching an overload condition. | |||||||||||||||||||||
| !msvmNearOverloadCleared | 1.3.6.1.4.1.318.0.96 | ||||||||||||||||||||
notification INFORMATIONAL: The near overload condition on the MasterSwitch VM has been cleared. | |||||||||||||||||||||
| !msvmPowerSupplyStatusChange | 1.3.6.1.4.1.318.0.97 | ||||||||||||||||||||
notification WARNING: The power supply status of the MasterSwitch VM has changed. | |||||||||||||||||||||
| !mspCommunicationEstablished | 1.3.6.1.4.1.318.0.98 | ||||||||||||||||||||
notification INFORMATIONAL: Communications with the MasterSwitch plus has been established. | |||||||||||||||||||||
| !mspCommunicationLost | 1.3.6.1.4.1.318.0.99 | ||||||||||||||||||||
notification SEVERE: Communications with the MasterSwitch plus has been lost. | |||||||||||||||||||||
| !mspOutletOn | 1.3.6.1.4.1.318.0.100 | ||||||||||||||||||||
notification INFORMATIONAL: An outlet on the MasterSwitch plus has turned on. | |||||||||||||||||||||
| !mspOutletOff | 1.3.6.1.4.1.318.0.101 | ||||||||||||||||||||
notification INFORMATIONAL: An outlet on the MasterSwitch plus has turned off. | |||||||||||||||||||||
| !mspDeviceConfigChange | 1.3.6.1.4.1.318.0.102 | ||||||||||||||||||||
notification INFORMATIONAL: A device configuration change has been made on a MasterSwitch plus. | |||||||||||||||||||||
| !mspOutletConfigChange | 1.3.6.1.4.1.318.0.103 | ||||||||||||||||||||
notification INFORMATIONAL: An outlet configuration change has been made on a MasterSwitch plus. | |||||||||||||||||||||
| !rsSourceSwitched | 1.3.6.1.4.1.318.0.104 | ||||||||||||||||||||
notification INFORMATIONAL: The Redundant Switch has switched source. The first variable is an integer representing the current source: 0=A, 1=B. The second variable is the 32-character name of the current source. The third variable is an integer representing the transfer cause: 0=No Transfers Recorded, 1=Due to user action or preferred switching, 3=Due to line notch or spike, 5=Due to low line voltage, 7=Transfer due to high line voltage, 9=Transfer due to frequency out of range. The fourth variable is a character string listing the transfer cause. | |||||||||||||||||||||
| !rsLostRedundancy | 1.3.6.1.4.1.318.0.105 | ||||||||||||||||||||
notification SEVERE: The Redundant Switch has lost redundancy. The first variable is an integer representing the source which is no longer available: 0=A, 1=B. The second variable is the 32-character name of the source which is no longer available. | |||||||||||||||||||||
| !rsRedundancyRestored | 1.3.6.1.4.1.318.0.106 | ||||||||||||||||||||
notification INFORMATIONAL: Redundancy has been restored to the Redundant Switch . The first variable is an integer representing the source which has been restored: 0=A, 1=B. The second variable is the 32-character name of the source which has been restored. | |||||||||||||||||||||
| !rsConfigChange | 1.3.6.1.4.1.318.0.107 | ||||||||||||||||||||
notification INFORMATIONAL: A configuration change has been made on a Redundant Switch.
| |||||||||||||||||||||
| !rsCommunicationEstablished | 1.3.6.1.4.1.318.0.108 | ||||||||||||||||||||
notification INFORMATIONAL: Communications with the Redundant Switch has been established.
| |||||||||||||||||||||
| !rsCommunicationLost | 1.3.6.1.4.1.318.0.109 | ||||||||||||||||||||
| !dcCommunicationEstablished | 1.3.6.1.4.1.318.0.110 | ||||||||||||||||||||
notification INFORMATIONAL: Communications with the DC power plant has been established.
| |||||||||||||||||||||
| !dcCommunicationLost | 1.3.6.1.4.1.318.0.111 | ||||||||||||||||||||
| !dcPINChanged | 1.3.6.1.4.1.318.0.112 | ||||||||||||||||||||
notification INFORMATIONAL: The active PIN on the DC controller has been changed.
| |||||||||||||||||||||
| !dcMajorAlarm | 1.3.6.1.4.1.318.0.113 | ||||||||||||||||||||
| !dcMajorAlarmCleared | 1.3.6.1.4.1.318.0.114 | ||||||||||||||||||||
notification INFORMATIONAL: A Major alarm is no longer active in the DC power plant.
| |||||||||||||||||||||
| !dcMinorAlarm | 1.3.6.1.4.1.318.0.115 | ||||||||||||||||||||
| !dcMinorAlarmCleared | 1.3.6.1.4.1.318.0.116 | ||||||||||||||||||||
notification INFORMATIONAL: A Minor alarm is no longer active in the DC power plant.
| |||||||||||||||||||||
| !dcOutputRelayOn | 1.3.6.1.4.1.318.0.117 | ||||||||||||||||||||
notification WARNING: An output relay for the powerplant has been activated (state changed to on). The first variable is an integer representing the output relay number that has gone on. The second variable is the 16-character name of the output relay. | |||||||||||||||||||||
| !dcOutputRelayOff | 1.3.6.1.4.1.318.0.118 | ||||||||||||||||||||
notification INFORMATIONAL: An output relay for the powerplant has been deactivated (state changed to off). The first variable is an integer representing the output relay number that has gone off. The second variable is the 16-character name of the output relay. | |||||||||||||||||||||
| !dcInputRelayOn | 1.3.6.1.4.1.318.0.119 | ||||||||||||||||||||
notification WARNING: An input relay for the powerplant has been activated (state changed to on). The first variable is an integer representing the input relay number that has gone on. The second variable is the 16-character name of the input relay. | |||||||||||||||||||||
| !dcInputRelayOff | 1.3.6.1.4.1.318.0.120 | ||||||||||||||||||||
notification INFORMATIONAL: An input relay for the powerplant has been deactivated (state changed to off). The first variable is an integer representing the input relay number that has gone off. The second variable is the 16-character name of the input relay. | |||||||||||||||||||||
| !logicPowerSuppliesIncreased | 1.3.6.1.4.1.318.0.121 | ||||||||||||||||||||
| !logicPowerSuppliesDecreased | 1.3.6.1.4.1.318.0.122 | ||||||||||||||||||||
| !externalSwitchGearClosed | 1.3.6.1.4.1.318.0.123 | ||||||||||||||||||||
| !externalSwitchGearOpened | 1.3.6.1.4.1.318.0.124 | ||||||||||||||||||||
| !generalDeviceEvent | 1.3.6.1.4.1.318.0.125 | ||||||||||||||||||||
| !atsSourceSwitched | 1.3.6.1.4.1.318.0.126 | ||||||||||||||||||||
notification INFORMATIONAL: The Automatic Transfer Switch has switched source. The first variable is an integer representing the current source: 0=A, 1=B. The second variable is the 32-character name of the current source. | |||||||||||||||||||||
| !atsLostRedundancy | 1.3.6.1.4.1.318.0.127 | ||||||||||||||||||||
notification SEVERE: The Automatic Transfer Switch has lost redundancy. The first variable is an integer representing the source which is no longer available: 0=A, 1=B. The second variable is the 32-character name of the source which is no longer available. | |||||||||||||||||||||
| !atsRedundancyRestored | 1.3.6.1.4.1.318.0.128 | ||||||||||||||||||||
notification INFORMATIONAL: Redundancy has been restored to the Automatic Transfer Switch. The first variable is an integer representing the source which has been restored: 0=A, 1=B. The second variable is the 32-character name of the source which has been restored. | |||||||||||||||||||||
| !atsConfigChange | 1.3.6.1.4.1.318.0.129 | ||||||||||||||||||||
notification INFORMATIONAL: A configuration change has been made on the Automatic Transfer Switch.
The first variable is an integer representing the configuration setting which changed:
0=Transfer Voltage Range, 1=Sensitivity, 2=Preferred Source
3=Front Panel Lockout, 4=Current Limit, 5=Reset XA Processor,
6=Reset to defaults, 7=Product Name, 8=Nominal Voltage, 9=Nominal Line Frequency,
10=Narrow VRMS, 11=Medium VRMS, 12=Wide VRMS,13=Frequency Deviation,
14=ColdStart ATS, 15=Events Count Cleared, 16=Phase or Bank Threshold.
| |||||||||||||||||||||
| !atsCommunicationEstablished | 1.3.6.1.4.1.318.0.130 | ||||||||||||||||||||
notification INFORMATIONAL: Communications with the Automatic Transfer Switch has been established.
| |||||||||||||||||||||
| !atsCommunicationLost | 1.3.6.1.4.1.318.0.131 | ||||||||||||||||||||
notification SEVERE: Communications with the Automatic Transfer Switch has been lost.
| |||||||||||||||||||||
| !atsOverCurrent | 1.3.6.1.4.1.318.0.132 | ||||||||||||||||||||
notification SEVERE: Output Current has exceeded threshold. This is same as atsOverload Trap for phase or total in case banked units
| |||||||||||||||||||||
| !atsOverCurrentCleared | 1.3.6.1.4.1.318.0.133 | ||||||||||||||||||||
notification INFORMATIONAL: Output Current has returned below threshold.This is same as atsOverloadCleared Trap for phase or total in case banked units
| |||||||||||||||||||||
| !atsPowerSupplyFailure | 1.3.6.1.4.1.318.0.134 | ||||||||||||||||||||
notification SEVERE: The Automatic Transfer Switch Power Supply has failed.
The first variable is an integer representing the Power Supply which
has failed: 0 = Source A 24V,
1 = 12V,
2 = 5V,
3 = Source B 24V.
| |||||||||||||||||||||
| !atsPowerSupplyFailureCleared | 1.3.6.1.4.1.318.0.135 | ||||||||||||||||||||
notification INFORMATIONAL: The Automatic Transfer Power Supply Failure Cleared.
The first variable is an integer representing the Power Supply which
has cleared: 0 = Source A 24V,
1 = 12V,
2 = 5V,
3 = Source B 24V.
| |||||||||||||||||||||
| !dcMainsFailAlarm | 1.3.6.1.4.1.318.0.136 | ||||||||||||||||||||
| !dcMainsFailAlarmCleared | 1.3.6.1.4.1.318.0.137 | ||||||||||||||||||||
notification INFORMATIONAL: Mains Fail alarm is no longer active in the DC power plant.
| |||||||||||||||||||||
| !dcFanFailAlarm | 1.3.6.1.4.1.318.0.138 | ||||||||||||||||||||
| !dcFanFailAlarmCleared | 1.3.6.1.4.1.318.0.139 | ||||||||||||||||||||
notification INFORMATIONAL: A Fan Fail alarm is no longer active in the DC power plant.
| |||||||||||||||||||||
| !dcRectifierOvertempAlarm | 1.3.6.1.4.1.318.0.140 | ||||||||||||||||||||
| !dcRectifierOvertempAlarmCleared | 1.3.6.1.4.1.318.0.141 | ||||||||||||||||||||
notification INFORMATIONAL: Rect. Overtemp alarm is no longer active in the power plant.
| |||||||||||||||||||||
| !dcCurrentLimitAlarm | 1.3.6.1.4.1.318.0.142 | ||||||||||||||||||||
| !dcCurrentLimitAlarmCleared | 1.3.6.1.4.1.318.0.143 | ||||||||||||||||||||
notification INFORMATIONAL: Current Limit alarm is no longer active in the power plant.
| |||||||||||||||||||||
| !dcRectifierFailAlarm | 1.3.6.1.4.1.318.0.144 | ||||||||||||||||||||
| !dcRectifierFailAlarmCleared | 1.3.6.1.4.1.318.0.145 | ||||||||||||||||||||
notification INFORMATIONAL: Rect. Fail alarm is no longer active in the power plant.
| |||||||||||||||||||||
| !dcMultRectFailAlarm | 1.3.6.1.4.1.318.0.146 | ||||||||||||||||||||
| !dcMultRectFailAlarmCleared | 1.3.6.1.4.1.318.0.147 | ||||||||||||||||||||
notification INFORMATIONAL: Multiple Rect Fail alarm is no longer active in the powerplant.
| |||||||||||||||||||||
| !dcBatteryBreakerAlarm | 1.3.6.1.4.1.318.0.148 | ||||||||||||||||||||
| !dcBatteryBreakerAlarmCleared | 1.3.6.1.4.1.318.0.149 | ||||||||||||||||||||
notification INFORMATIONAL: Batt. Breaker alarm is no longer active in the power plant.
| |||||||||||||||||||||
| !dcRectifierOVPAlarm | 1.3.6.1.4.1.318.0.150 | ||||||||||||||||||||
| !dcRectifierOVPAlarmCleared | 1.3.6.1.4.1.318.0.151 | ||||||||||||||||||||
notification INFORMATIONAL: A Rect. OVP alarm is no longer active in the power plant.
| |||||||||||||||||||||
| !dcLVDImminentAlarm | 1.3.6.1.4.1.318.0.152 | ||||||||||||||||||||
| !dcLVDImminentAlarmCleared | 1.3.6.1.4.1.318.0.153 | ||||||||||||||||||||
notification INFORMATIONAL: A LVD Imminent alarm is no longer active in the powerplant.
| |||||||||||||||||||||
| !dcFuseCBAlarm | 1.3.6.1.4.1.318.0.154 | ||||||||||||||||||||
| !dcFuseCBAlarmCleared | 1.3.6.1.4.1.318.0.155 | ||||||||||||||||||||
notification INFORMATIONAL: A Fuse/CB alarm is no longer active in the DC power plant.
| |||||||||||||||||||||
| !dcBatteryTestFail | 1.3.6.1.4.1.318.0.156 | ||||||||||||||||||||
| !dcTemperatureAlarm | 1.3.6.1.4.1.318.0.157 | ||||||||||||||||||||
| !dcTemperatureAlarmCleared | 1.3.6.1.4.1.318.0.158 | ||||||||||||||||||||
notification INFORMATIONAL: A Temperature alarm is no longer active in the power plant.
| |||||||||||||||||||||
| !dcHumidityAlarm | 1.3.6.1.4.1.318.0.159 | ||||||||||||||||||||
| !dcHumidityAlarmCleared | 1.3.6.1.4.1.318.0.160 | ||||||||||||||||||||
notification INFORMATIONAL: A Humidity alarm is no longer active in the DC power plant.
| |||||||||||||||||||||
| !dcBBCommunicationEstablished | 1.3.6.1.4.1.318.0.161 | ||||||||||||||||||||
notification INFORMATIONAL: Power plant bridging board communications established.
| |||||||||||||||||||||
| !dcBBCommunicationLost | 1.3.6.1.4.1.318.0.162 | ||||||||||||||||||||
| !iemHighTempThresholdViolation | 1.3.6.1.4.1.318.0.163 | ||||||||||||||||||||
notification SEVERE: High temperature threshold violated on Integrated Environmental Monitor probe. The first variable is the current temperature. The second variable is the temperature scale. The third variable is the probe number. The fourth variable is the probe name. | |||||||||||||||||||||
| !iemHighTempThresholdViolationCleared | 1.3.6.1.4.1.318.0.164 | ||||||||||||||||||||
notification INFORMATIONAL: High temperature threshold violated on Integrated Environmental Monitor probe has been cleared. The first variable is the probe number. The second variable is the probe name. | |||||||||||||||||||||
| !iemLowTempThresholdViolation | 1.3.6.1.4.1.318.0.165 | ||||||||||||||||||||
notification SEVERE: Low temperature threshold violated on integrated probe. The first variable is the current temperature. The second variable is the temperature scale. The third variable is the probe number. The fourth variable is the probe name. | |||||||||||||||||||||
| !iemLowTempThresholdViolationCleared | 1.3.6.1.4.1.318.0.166 | ||||||||||||||||||||
notification INFORMATIONAL: Low temperature threshold violated on integrated probe has been cleared. The first variable is the probe number. The second variable is the probe name. | |||||||||||||||||||||
| !iemHighHumidThresholdViolation | 1.3.6.1.4.1.318.0.167 | ||||||||||||||||||||
notification SEVERE: High humidity threshold violated on integrated probe. The first variable is the current humidity. The second variable is the probe number. The third variable is the probe name. | |||||||||||||||||||||
| !iemHighHumidThresholdViolationCleared | 1.3.6.1.4.1.318.0.168 | ||||||||||||||||||||
notification INFORMATIONAL: High humidity threshold violated on integrated probe cleared. The first variable is the probe number. The second variable is the probe name. | |||||||||||||||||||||
| !iemLowHumidThresholdViolation | 1.3.6.1.4.1.318.0.169 | ||||||||||||||||||||
notification SEVERE: Low humidity threshold violated on integrated probe. The first variable is the current humidity. The second variable is the probe number. The third variable is the probe name. | |||||||||||||||||||||
| !iemLowHumidThresholdViolationCleared | 1.3.6.1.4.1.318.0.170 | ||||||||||||||||||||
notification INFORMATIONAL: Low humidity threshold violated on integrated probe cleared. The first variable is the probe number. The second variable is the probe name. | |||||||||||||||||||||
| !iemProbeDisconnected | 1.3.6.1.4.1.318.0.171 | ||||||||||||||||||||
notification WARNING: The temperature/humidity probe on the Integrated Environmental Monitor has been disconnected. This trap is generated when a probe that has been in communication with the Environmental Monitor has been disconnected or can no longer communicate.
| |||||||||||||||||||||
| !iemProbeConnected | 1.3.6.1.4.1.318.0.172 | ||||||||||||||||||||
notification INFORMATIONAL: The temperature/humidity probe on the Integrated Environmental Monitor has been connected. This trap is generated when the Environmental Monitor establishes communication with a probe that had previously not been connected.
| |||||||||||||||||||||
| !iemContactFault | 1.3.6.1.4.1.318.0.173 | ||||||||||||||||||||
notification SEVERE: There is a contact fault on the Integrated Environmental Monitor. The first argument is the number of the contact. The second argument is the name of the contact. | |||||||||||||||||||||
| !iemContactFaultCleared | 1.3.6.1.4.1.318.0.174 | ||||||||||||||||||||
notification INFORMATIONAL: The contact fault on the Integrated Environmental Monitor has been cleared. The first argument is the number of the contact. The second argument is the name of the contact. | |||||||||||||||||||||
| !iemRelayFault | 1.3.6.1.4.1.318.0.175 | ||||||||||||||||||||
notification SEVERE: The output relay on the Integrated Environmental Monitor has switched to the fault state. The first argument is the number of the output relay. The second argument is the name of the output relay. The third argument is the event that caused the fault. | |||||||||||||||||||||
| !iemRelayFaultCleared | 1.3.6.1.4.1.318.0.176 | ||||||||||||||||||||
notification INFORMATIONAL: The fault condition on the output relay on the Integrated Environmental Monitor has cleared. The first argument is the number of the output relay. The second argument is the name of the output relay. | |||||||||||||||||||||
| !bmBatManCommEstab | 1.3.6.1.4.1.318.0.177 | ||||||||||||||||||||
notification INFORMATIONAL: Serial Communications Established with Battery Manager.
| |||||||||||||||||||||
| !bmBatManCommLost | 1.3.6.1.4.1.318.0.178 | ||||||||||||||||||||
notification SEVERE: Serial Communications Lost with Battery Manager.
| |||||||||||||||||||||
| !bmBatManKneeAlarm | 1.3.6.1.4.1.318.0.179 | ||||||||||||||||||||
notification SEVERE: Battery Voltage Knee Threshold Alarm Detected.
| |||||||||||||||||||||
| !bmBatManKneeAlarmCleared | 1.3.6.1.4.1.318.0.180 | ||||||||||||||||||||
notification INFORMATIONAL: Battery Voltage Knee Threshold Alarm Cleared.
| |||||||||||||||||||||
| !bmBatManChargerAlarm | 1.3.6.1.4.1.318.0.181 | ||||||||||||||||||||
| !bmBatManChargerAlarmCleared | 1.3.6.1.4.1.318.0.182 | ||||||||||||||||||||
| !bmBatManBatteryAlarm | 1.3.6.1.4.1.318.0.183 | ||||||||||||||||||||
| !bmBatManBatteryAlarmCleared | 1.3.6.1.4.1.318.0.184 | ||||||||||||||||||||
| !bmBatManEnvironmentAlarm | 1.3.6.1.4.1.318.0.185 | ||||||||||||||||||||
| !bmBatManEnvironmentAlarmCleared | 1.3.6.1.4.1.318.0.186 | ||||||||||||||||||||
| !bmBatManMaintenanceAlarm | 1.3.6.1.4.1.318.0.187 | ||||||||||||||||||||
| !bmBatManMaintenanceAlarmCleared | 1.3.6.1.4.1.318.0.188 | ||||||||||||||||||||
| !pduCommunicationEstablished | 1.3.6.1.4.1.318.0.189 | ||||||||||||||||||||
notification INFORMATIONAL: Communication Established. The first argument is the serial number. The second argument is the device name. | |||||||||||||||||||||
| !pduCommunicationLost | 1.3.6.1.4.1.318.0.190 | ||||||||||||||||||||
notification SEVERE: Communication Lost. The first argument is the serial number. The second argument is the device name. | |||||||||||||||||||||
| !pduUtilityLineUndervoltage | 1.3.6.1.4.1.318.0.191 | ||||||||||||||||||||
notification SEVERE: Utility Line Undervoltage. The first argument is the serial number. The second argument is the device name. The third argument is the phase number. | |||||||||||||||||||||
| !pduUtilityLineUndervoltageCleared | 1.3.6.1.4.1.318.0.192 | ||||||||||||||||||||
notification INFORMATIONAL: Utility Line Undervoltage Cleared. The first argument is the serial number. The second argument is the device name. The third argument is the phase number. | |||||||||||||||||||||
| !pduUtilityLineOvervoltage | 1.3.6.1.4.1.318.0.193 | ||||||||||||||||||||
notification SEVERE: Utility Line Overvoltage. The first argument is the serial number. The second argument is the device name. The third argument is the phase number. | |||||||||||||||||||||
| !pduUtilityLineOvervoltageCleared | 1.3.6.1.4.1.318.0.194 | ||||||||||||||||||||
notification INFORMATIONAL: Utility Line Overvoltage Cleared. The first argument is the serial number. The second argument is the device name. The third argument is the phase number. | |||||||||||||||||||||
| !pduGroundOvercurrent | 1.3.6.1.4.1.318.0.195 | ||||||||||||||||||||
notification SEVERE: Ground Overcurrent. The first argument is the serial number. The second argument is the device name. | |||||||||||||||||||||
| !pduGroundOvercurrentCleared | 1.3.6.1.4.1.318.0.196 | ||||||||||||||||||||
notification INFORMATIONAL: Ground Overcurrent Cleared. The first argument is the serial number. The second argument is the device name. | |||||||||||||||||||||
| !pduCircuitPanelInputUndervoltage | 1.3.6.1.4.1.318.0.197 | ||||||||||||||||||||
notification SEVERE: Circuit Panel Input Undervoltage. The first argument is the serial number. The second argument is the device name. The third argument is the phase number. | |||||||||||||||||||||
| !pduCircuitPanelInputUndervoltageCleared | 1.3.6.1.4.1.318.0.198 | ||||||||||||||||||||
notification INFORMATIONAL: Circuit Panel Input Undervoltage Cleared. The first argument is the serial number. The second argument is the device name. The third argument is the phase number. | |||||||||||||||||||||
| !pduCircuitPanelInputOvervoltage | 1.3.6.1.4.1.318.0.199 | ||||||||||||||||||||
notification SEVERE: Circuit Panel Input Overvoltage. The first argument is the serial number. The second argument is the device name. The third argument is the phase number. | |||||||||||||||||||||
| !pduCircuitPanelInputOvervoltageCleared | 1.3.6.1.4.1.318.0.200 | ||||||||||||||||||||
notification INFORMATIONAL: Circuit Panel Input Overvoltage Cleared. The first argument is the serial number. The second argument is the device name. The third argument is the phase number. | |||||||||||||||||||||
| !pduCircuitPanelInputUndercurrent | 1.3.6.1.4.1.318.0.201 | ||||||||||||||||||||
notification SEVERE: Circuit Panel Input Undercurrent. The first argument is the serial number. The second argument is the device name. The third argument is the phase number. | |||||||||||||||||||||
| !pduCircuitPanelInputUndercurrentCleared | 1.3.6.1.4.1.318.0.202 | ||||||||||||||||||||
notification INFORMATIONAL: Circuit Panel Input Undercurrent Cleared. The first argument is the serial number. The second argument is the device name. The third argument is the phase number. | |||||||||||||||||||||
| !pduCircuitPanelInputOvercurrent | 1.3.6.1.4.1.318.0.203 | ||||||||||||||||||||
notification SEVERE: Circuit Panel Input Overcurrent. The first argument is the serial number. The second argument is the device name. The third argument is the phase number. | |||||||||||||||||||||
| !pduCircuitPanelInputOvercurrentCleared | 1.3.6.1.4.1.318.0.204 | ||||||||||||||||||||
notification INFORMATIONAL: Circuit Panel Input Overcurrent Cleared. The first argument is the serial number. The second argument is the device name. The third argument is the phase number. | |||||||||||||||||||||
| !pduCircuitPanelFrequencyOutOfRange | 1.3.6.1.4.1.318.0.205 | ||||||||||||||||||||
notification SEVERE: Circuit Panel Input Frequency Out Of Range. The first argument is the serial number. The second argument is the device name. | |||||||||||||||||||||
| !pduCircuitPanelFrequencyOutofRangeCleared | 1.3.6.1.4.1.318.0.206 | ||||||||||||||||||||
notification INFORMATIONAL: Circuit Panel Input Frequency No Longer Out Of Range. The first argument is the serial number. The second argument is the device name. | |||||||||||||||||||||
| !pduCircuitPanelNeutralOvercurrent | 1.3.6.1.4.1.318.0.207 | ||||||||||||||||||||
notification SEVERE: Circuit Panel Input Neutral Overcurrent. The first argument is the serial number. The second argument is the device name. | |||||||||||||||||||||
| !pduCircuitPanelNeutralOvercurrentCleared | 1.3.6.1.4.1.318.0.208 | ||||||||||||||||||||
notification INFORMATIONAL: Circuit Panel Input Neutral Overcurrent Cleared. The first argument is the serial number. The second argument is the device name. | |||||||||||||||||||||
| !pduSystemOff | 1.3.6.1.4.1.318.0.209 | ||||||||||||||||||||
notification SEVERE: PDU System Off. The first argument is the serial number. The second argument is the device name. | |||||||||||||||||||||
| !pduOnBatteryMode | 1.3.6.1.4.1.318.0.210 | ||||||||||||||||||||
notification SEVERE: PDU is in On Battery Mode. The first argument is the serial number. The second argument is the device name. | |||||||||||||||||||||
| !pduMaintenanceBypassMode | 1.3.6.1.4.1.318.0.211 | ||||||||||||||||||||
notification INFORMATIONAL: PDU is in Maintenance Bypass Mode. The first argument is the serial number. The second argument is the device name. | |||||||||||||||||||||
| !pduAtypicalBypassMode | 1.3.6.1.4.1.318.0.212 | ||||||||||||||||||||
notification WARNING: PDU is in Atypical Bypass Mode. The first argument is the serial number. The second argument is the device name. | |||||||||||||||||||||
| !pduNoPanelFeedMode | 1.3.6.1.4.1.318.0.213 | ||||||||||||||||||||
notification SEVERE: PDU is in No Panel Feed Mode. The first argument is the serial number. The second argument is the device name. | |||||||||||||||||||||
| !pduUpsOperationMode | 1.3.6.1.4.1.318.0.214 | ||||||||||||||||||||
notification INFORMATIONAL: PDU is in Ups Operation Mode. The first argument is the serial number. The second argument is the device name. | |||||||||||||||||||||
| !pduForcedBypassMode | 1.3.6.1.4.1.318.0.215 | ||||||||||||||||||||
notification WARNING: PDU is in Forced Bypass Mode. The first argument is the serial number. The second argument is the device name. | |||||||||||||||||||||
| !pduInputTransformerOverTemperature | 1.3.6.1.4.1.318.0.216 | ||||||||||||||||||||
notification SEVERE: Input Transformer Over Temperature. The first argument is the serial number. The second argument is the device name. | |||||||||||||||||||||
| !pduInputTransformerOverTemperatureCleared | 1.3.6.1.4.1.318.0.217 | ||||||||||||||||||||
notification INFORMATIONAL: Input Transformer Over Temperature Cleared. The first argument is the serial number. The second argument is the device name. | |||||||||||||||||||||
| !pduUPSInputVoltageLost | 1.3.6.1.4.1.318.0.218 | ||||||||||||||||||||
notification SEVERE: UPS Input Voltage phase-N Lost. The first argument is the serial number. The second argument is the device name. The third argument is the phase number. | |||||||||||||||||||||
| !pduUPSInputVoltageRestored | 1.3.6.1.4.1.318.0.219 | ||||||||||||||||||||
notification INFORMATIONAL: UPS Input Voltage phase-N Restored. The first argument is the serial number. The second argument is the device name. The third argument is the phase number. | |||||||||||||||||||||
| !pduContactFault | 1.3.6.1.4.1.318.0.220 | ||||||||||||||||||||
notification SEVERE: A contact closure in the PDU is in an abnormal position. The first argument is the serial number. The second argument is the device name. The third argument is the number of the contact. | |||||||||||||||||||||
| !pduContactFaultCleared | 1.3.6.1.4.1.318.0.221 | ||||||||||||||||||||
notification INFORMATIONAL: A contact closure in the PDU is in a normal position. The first argument is the serial number. The second argument is the device name. The third argument is the number of the contact. | |||||||||||||||||||||
| !rPDUBankPhaseLowLoad | 1.3.6.1.4.1.318.0.222 | ||||||||||||||||||||
notification WARNING: A bank or phase on the Rack PDU has violated the low load threshold. The first argument is the serial number. The second argument is the device name. The third argument is the bank number (0 if this is phase data). The fourth argument is the phase number (0 if this is bank data). | |||||||||||||||||||||
| !rPDUBankPhaseLowLoadCleared | 1.3.6.1.4.1.318.0.223 | ||||||||||||||||||||
notification INFORMATIONAL: The bank or phase low load condition on a Rack PDU has been cleared. The first argument is the serial number. The second argument is the device name. The third argument is the bank number (0 if this is phase data). The fourth argument is the phase number (0 if this is bank data). | |||||||||||||||||||||
| !rPDUBankPhaseNearOverload | 1.3.6.1.4.1.318.0.224 | ||||||||||||||||||||
notification WARNING: A bank or phase of the Rack PDU is near an overload condition. The first argument is the serial number. The second argument is the device name. The third argument is the bank number (0 if this is phase data). The fourth argument is the phase number (0 if this is bank data). | |||||||||||||||||||||
| !rPDUBankPhaseNearOverloadCleared | 1.3.6.1.4.1.318.0.225 | ||||||||||||||||||||
notification INFORMATIONAL: The bank or phase near overload condition on a Rack PDU has been cleared. The first argument is the serial number. The second argument is the device name. The third argument is the bank number (0 if this is phase data). The fourth argument is the phase number (0 if this is bank data). | |||||||||||||||||||||
| !rPDUBankPhaseOverload | 1.3.6.1.4.1.318.0.226 | ||||||||||||||||||||
notification SEVERE: A bank or phase of the Rack PDU is in an overload condition. The first argument is the serial number. The second argument is the device name. The third argument is the phase number. The third argument is the bank number (0 if this is phase data). The fourth argument is the phase number (0 if this is bank data). | |||||||||||||||||||||
| !rPDUBankPhaseOverloadCleared | 1.3.6.1.4.1.318.0.227 | ||||||||||||||||||||
notification INFORMATIONAL: The bank or phase overload condition on a Rack PDU has been cleared. The first argument is the serial number. The second argument is the device name. The third argument is the bank number (0 if this is phase data). The fourth argument is the phase number (0 if this is bank data). | |||||||||||||||||||||
| !aruDeviceConfigChange | 1.3.6.1.4.1.318.0.228 | ||||||||||||||||||||
notification INFORMATIONAL: Remote ARU Device Configuration change. The first argument is the host device serial number. The second argument is the host device name. The third argument is the ARU number. The fourth argument is the ARU name. | |||||||||||||||||||||
| !rmPDUCommunicationLost | 1.3.6.1.4.1.318.0.229 | ||||||||||||||||||||
notification SEVERE: Communication Lost. The first argument is the serial number. The second argument is the device name. | |||||||||||||||||||||
| !emsCommunicationEstablished | 1.3.6.1.4.1.318.0.230 | ||||||||||||||||||||
notification INFORMATIONAL: Communication Established. The first argument is the serial number. The second argument is the device name. | |||||||||||||||||||||
| !emsCommunicationLost | 1.3.6.1.4.1.318.0.231 | ||||||||||||||||||||
notification SEVERE: Communication Lost. The first argument is the serial number. The second argument is the device name. | |||||||||||||||||||||
| !emsProbeConnected | 1.3.6.1.4.1.318.0.232 | ||||||||||||||||||||
notification INFORMATIONAL: A probe has been connected to the EMS. The first argument is the host device serial number. The second argument is the host device name. The third argument is the probe number. The fourth argument is the probe name. | |||||||||||||||||||||
| !emsProbeDisconnected | 1.3.6.1.4.1.318.0.233 | ||||||||||||||||||||
notification SEVERE: A probe has been disconnected from the EMS. The first argument is the host device serial number. The second argument is the host device name. The third argument is the probe number. The fourth argument is the probe name. | |||||||||||||||||||||
| !emsSensorConnected | 1.3.6.1.4.1.318.0.234 | ||||||||||||||||||||
notification INFORMATIONAL: A sensor has been connected to the EMS. The first argument is the host device serial number. The second argument is the host device name. The third argument is the sensor number. The fourth argument is the sensor name. | |||||||||||||||||||||
| !emsSensorDisconnected | 1.3.6.1.4.1.318.0.235 | ||||||||||||||||||||
notification SEVERE: A sensor has been disconnected from the EMS. The first argument is the host device serial number. The second argument is the host device name. The third argument is the sensor number. The fourth argument is the sensor name. | |||||||||||||||||||||
| !emsSensorFault | 1.3.6.1.4.1.318.0.236 | ||||||||||||||||||||
notification SEVERE: A EMS sensor is in the fault condition. The first argument is the host device serial number. The second argument is the host device name. The third argument is the sensor number. The fourth argument is the sensor name. | |||||||||||||||||||||
| !emsSensorFaultCleared | 1.3.6.1.4.1.318.0.237 | ||||||||||||||||||||
notification INFORMATIONAL: A EMS sensor fault condition has cleared. The first argument is the host device serial number. The second argument is the host device name. The third argument is the sensor number. The fourth argument is the sensor name. | |||||||||||||||||||||
| !emsBeaconConnected | 1.3.6.1.4.1.318.0.238 | ||||||||||||||||||||
notification INFORMATIONAL: A beacon has been connected to the EMS. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !emsBeaconDisconnected | 1.3.6.1.4.1.318.0.239 | ||||||||||||||||||||
notification SEVERE: A beacon has been disconnected from the EMS. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !emsBeaconOn | 1.3.6.1.4.1.318.0.240 | ||||||||||||||||||||
notification INFORMATIONAL: A EMS beacon has gone on. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !emsBeaconOff | 1.3.6.1.4.1.318.0.241 | ||||||||||||||||||||
notification INFORMATIONAL: A EMS beacon has gone off. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !emsMajorAlarm | 1.3.6.1.4.1.318.0.242 | ||||||||||||||||||||
notification SEVERE: A Major Alarm is present in the EMS. The first argument is the EMS serial number. The second argument is the EMS name. | |||||||||||||||||||||
| !emsMajorAlarmCleared | 1.3.6.1.4.1.318.0.243 | ||||||||||||||||||||
notification INFORMATIONAL: A Major Alarm condition has been cleared in the EMS. The first argument is the EMS serial number. The second argument is the EMS name. | |||||||||||||||||||||
| !emsMinorAlarm | 1.3.6.1.4.1.318.0.244 | ||||||||||||||||||||
notification SEVERE: A Minor Alarm is present in the EMS. The first argument is the EMS serial number. The second argument is the EMS name. | |||||||||||||||||||||
| !emsMinorAlarmCleared | 1.3.6.1.4.1.318.0.245 | ||||||||||||||||||||
notification INFORMATIONAL: A Minor Alarm condition has been cleared in the EMS. The first argument is the EMS serial number. The second argument is the EMS name. | |||||||||||||||||||||
| !emsOutletStateAbnormal | 1.3.6.1.4.1.318.0.246 | ||||||||||||||||||||
notification WARNING: An outlet on the EMS has changed to its abnormal state. The first argument is the host device serial number. The second argument is the host device name. The third argument is the outlet number. The fourth argument is the outlet name. The fifth argument is the current outlet state (1=ON, 2=OFF). The sixth argument is the configured normal outlet state (1=ON, 2=OFF). | |||||||||||||||||||||
| !emsOutletStateNormal | 1.3.6.1.4.1.318.0.247 | ||||||||||||||||||||
notification INFORMATIONAL: An outlet on the EMS has changed to its normal state. The first argument is the host device serial number. The second argument is the host device name. The third argument is the outlet number. The fourth argument is the outlet name. The fifth argument is the current outlet state (1=ON, 2=OFF). The sixth argument is the configured normal outlet state (1=ON, 2=OFF). | |||||||||||||||||||||
| !emsInputContactStateAbnormal | 1.3.6.1.4.1.318.0.248 | ||||||||||||||||||||
notification WARNING: An input contact on the EMS has changed to its abnormal state. The first argument is the host device serial number. The second argument is the host device name. The third argument is the input contact number. The fourth argument is the input contact name. The fifth argument is the input contact state (1=CLOSED, 2=OPEN). The sixth argument is the configured normal input contact state (1=CLOSED, 2=OPEN). | |||||||||||||||||||||
| !emsInputContactStateNormal | 1.3.6.1.4.1.318.0.249 | ||||||||||||||||||||
notification INFORMATIONAL: An input contact on the EMS has changed to its normal state. The first argument is the host device serial number. The second argument is the host device name. The third argument is the input contact number. The fourth argument is the input contact name. The fifth argument is the input contact state (1=CLOSED, 2=OPEN). The sixth argument is the configured normal input contact state (1=CLOSED, 2=OPEN). | |||||||||||||||||||||
| !emsOutputRelayStateAbnormal | 1.3.6.1.4.1.318.0.250 | ||||||||||||||||||||
notification WARNING: An output relay on the EMS has changed to its abnormal state. The first argument is the host device serial number. The second argument is the host device name. The third argument is the output relay number. The fourth argument is the output relay name. The fifth argument is the current output relay state (1=CLOSED, 2=OPEN). The sixth argument is the configured normal output relay state (1=CLOSED, 2=OPEN). | |||||||||||||||||||||
| !emsOutputRelayStateNormal | 1.3.6.1.4.1.318.0.251 | ||||||||||||||||||||
notification INFORMATIONAL: An output relay on the EMS has changed to its normal state. The first argument is the host device serial number. The second argument is the host device name. The third argument is the output relay number. The fourth argument is the output relay name. The fifth argument is the current output relay state (1=CLOSED, 2=OPEN). The sixth argument is the configured normal output relay state (1=CLOSED, 2=OPEN). | |||||||||||||||||||||
| !emsDeviceConfigChange | 1.3.6.1.4.1.318.0.252 | ||||||||||||||||||||
notification INFORMATIONAL: A device configuration change has been made on the EMS. The first argument is the EMS serial number. The second argument is the EMS name. | |||||||||||||||||||||
| !envHighTempThresholdViolation | 1.3.6.1.4.1.318.0.253 | ||||||||||||||||||||
notification SEVERE: High temperature threshold violated on the probe. The first argument is the host device serial number. The second argument is the host device name. The third argument is the current temperature. The fourth argument is the temperature scale. The fifth argument is the probe number. The sixth argument is the probe name. | |||||||||||||||||||||
| !envHighTempThresholdViolationCleared | 1.3.6.1.4.1.318.0.254 | ||||||||||||||||||||
notification INFORMATIONAL: High temperature threshold violation cleared on the probe. The first argument is the host device serial number. The second argument is the host device name. The third argument is the current temperature. The fourth argument is the temperature scale. The fifth argument is the probe number. The sixth argument is the probe name. | |||||||||||||||||||||
| !envLowTempThresholdViolation | 1.3.6.1.4.1.318.0.255 | ||||||||||||||||||||
notification SEVERE: Low temperature threshold violated on the probe. The first argument is the host device serial number. The second argument is the host device name. The third argument is the current temperature. The fourth argument is the temperature scale. The fifth argument is the probe number. The sixth argument is the probe name. | |||||||||||||||||||||
| !envLowTempThresholdViolationCleared | 1.3.6.1.4.1.318.0.256 | ||||||||||||||||||||
notification INFORMATIONAL: Low temperature threshold violation cleared on the probe. The first argument is the host device serial number. The second argument is the host device name. The third argument is the current temperature. The fourth argument is the temperature scale. The fifth argument is the probe number. The sixth argument is the probe name. | |||||||||||||||||||||
| !envHighHumidityThresholdViolation | 1.3.6.1.4.1.318.0.257 | ||||||||||||||||||||
notification SEVERE: High humidity threshold violated on the probe. The first argument is the host device serial number. The second argument is the host device name. The third argument is the current humidity The fourth argument is the probe number. The fifth argument is the probe name. | |||||||||||||||||||||
| !envHighHumidityThresholdViolationCleared | 1.3.6.1.4.1.318.0.258 | ||||||||||||||||||||
notification INFORMATIONAL: High humidity threshold violation cleared on the probe. The first argument is the host device serial number. The second argument is the host device name. The third argument is the current humidity. The fourth argument is the probe number. The fifth argument is the probe name. | |||||||||||||||||||||
| !envLowHumidityThresholdViolation | 1.3.6.1.4.1.318.0.259 | ||||||||||||||||||||
notification SEVERE: Low humidity threshold violated on the probe. The first argument is the host device serial number. The second argument is the host device name. The third argument is the current humidity The fourth argument is the probe number. The fifth argument is the probe name. | |||||||||||||||||||||
| !envLowHumidityThresholdViolationCleared | 1.3.6.1.4.1.318.0.260 | ||||||||||||||||||||
notification INFORMATIONAL: Low humidity threshold violation cleared on the probe. The first argument is the host device serial number. The second argument is the host device name. The third argument is the current humidity. The fourth argument is the probe number. The fifth argument is the probe name. | |||||||||||||||||||||
| !rPDUCommunicationEstablished | 1.3.6.1.4.1.318.0.266 | ||||||||||||||||||||
notification INFORMATIONAL: Communication with a Rack PDU has been established. The first argument is the serial number. The second argument is the device name. | |||||||||||||||||||||
| !rPDUCommunicationLost | 1.3.6.1.4.1.318.0.267 | ||||||||||||||||||||
notification SEVERE: Communication with a Rack PDU has been lost. The first argument is the serial number. The second argument is the device name. | |||||||||||||||||||||
| !rPDUOutletOn | 1.3.6.1.4.1.318.0.268 | ||||||||||||||||||||
notification INFORMATIONAL: An outlet on a Switched Rack PDU has turned on. The first argument is the serial number. The second argument is the device name. The third argument is the outlet index number. The fourth argument is the outlet name. | |||||||||||||||||||||
| !rPDUOutletOff | 1.3.6.1.4.1.318.0.269 | ||||||||||||||||||||
notification INFORMATIONAL: An outlet on a Switched Rack PDU has turned off. The first argument is the serial number. The second argument is the device name. The third argument is the outlet index number. The fourth argument is the outlet name. | |||||||||||||||||||||
| !rPDUDeviceConfigChange | 1.3.6.1.4.1.318.0.270 | ||||||||||||||||||||
notification INFORMATIONAL: A device configuration change has been made on a Rack PDU. The first argument is the serial number. The second argument is the device name. | |||||||||||||||||||||
| !rPDUOutletConfigChange | 1.3.6.1.4.1.318.0.271 | ||||||||||||||||||||
notification INFORMATIONAL: An outlet configuration change has been made on a Switched Rack PDU. The first argument is the serial number. The second argument is the device name. The third argument is the outlet index number. The fourth argument is the outlet name. | |||||||||||||||||||||
| !rPDULowLoad | 1.3.6.1.4.1.318.0.272 | ||||||||||||||||||||
notification WARNING: A Rack PDU has violated the low load threshold. The first argument is the serial number. The second argument is the device name. The third argument is the phase number. | |||||||||||||||||||||
| !rPDULowLoadCleared | 1.3.6.1.4.1.318.0.273 | ||||||||||||||||||||
notification INFORMATIONAL: The low load condition on a Rack PDU has been cleared. The first argument is the serial number. The second argument is the device name. The third argument is the phase number. | |||||||||||||||||||||
| !rPDUNearOverload | 1.3.6.1.4.1.318.0.274 | ||||||||||||||||||||
notification WARNING: A Rack PDU is near an overload condition. The first argument is the serial number. The second argument is the device name. The third argument is the phase number. | |||||||||||||||||||||
| !rPDUNearOverloadCleared | 1.3.6.1.4.1.318.0.275 | ||||||||||||||||||||
notification INFORMATIONAL: The near overload condition on a Rack PDU has been cleared. The first argument is the serial number. The second argument is the device name. The third argument is the phase number. | |||||||||||||||||||||
| !rPDUOverload | 1.3.6.1.4.1.318.0.276 | ||||||||||||||||||||
notification SEVERE: A Rack PDU is in an overload condition. The first argument is the serial number. The second argument is the device name. The third argument is the phase number. | |||||||||||||||||||||
| !rPDUOverloadCleared | 1.3.6.1.4.1.318.0.277 | ||||||||||||||||||||
notification INFORMATIONAL: The overload condition on a Rack PDU has been cleared. The first argument is the serial number. The second argument is the device name. The third argument is the phase number. | |||||||||||||||||||||
| !rPDUPowerSupply1Fail | 1.3.6.1.4.1.318.0.278 | ||||||||||||||||||||
notification SEVERE: Power Supply 1 on Rack PDU is in FAIL state. The first argument is the serial number. The second argument is the device name. | |||||||||||||||||||||
| !rPDUPowerSupply1Ok | 1.3.6.1.4.1.318.0.279 | ||||||||||||||||||||
notification INFORMATIONAL: Power Supply 1 on Rack PDU is operating normally. The first argument is the serial number. The second argument is the device name. | |||||||||||||||||||||
| !rPDUPowerSupply2Fail | 1.3.6.1.4.1.318.0.280 | ||||||||||||||||||||
notification SEVERE: Power Supply 2 on Rack PDU is in FAIL state. The first argument is the serial number. The second argument is the device name. | |||||||||||||||||||||
| !rPDUPowerSupply2Ok | 1.3.6.1.4.1.318.0.281 | ||||||||||||||||||||
notification INFORMATIONAL: Power Supply 2 on Rack PDU is operating normally. The first argument is the serial number. The second argument is the device name. | |||||||||||||||||||||
| !rPDUPhaseConfigChange | 1.3.6.1.4.1.318.0.282 | ||||||||||||||||||||
notification INFORMATIONAL: A phase configuration change has been made on a Rack PDU. The first argument is the serial number. The second argument is the device name. The third argument is the phase index number. | |||||||||||||||||||||
| !rPDUCancelPendingCommand | 1.3.6.1.4.1.318.0.283 | ||||||||||||||||||||
notification INFORMATIONAL: A cancel pending command has been made on a Switched Rack PDU. The first argument is the serial number. The second argument is the device name. The third argument is the outlet index number (0 indicates all outlets). The fourth argument is the outlet name (or device name if all outlets). | |||||||||||||||||||||
| !aruAlinkCommunicationEstablished | 1.3.6.1.4.1.318.0.284 | ||||||||||||||||||||
notification INFORMATIONAL: Remote ARU Communication Established. The first argument is the host device serial number. The second argument is the host device name. The third argument is the ARU number. The fourth argument is the ARU name. | |||||||||||||||||||||
| !aruAlinkCommunicationLost | 1.3.6.1.4.1.318.0.285 | ||||||||||||||||||||
notification SEVERE: Remote ARU Communication Lost. The first argument is the host device serial number. The second argument is the host device name. The third argument is the ARU number. The fourth argument is the ARU name. | |||||||||||||||||||||
| !aruFanFail | 1.3.6.1.4.1.318.0.286 | ||||||||||||||||||||
notification SEVERE: Remote ARU Fan Fail. The first argument is the host device serial number. The second argument is the host device name. The third argument is the ARU number. The fourth argument is the ARU name. | |||||||||||||||||||||
| !aruFanFailCleared | 1.3.6.1.4.1.318.0.287 | ||||||||||||||||||||
notification INFORMATIONAL: Remote ARU Fan Fail Cleared. The first argument is the host device serial number. The second argument is the host device name. The third argument is the ARU number. The fourth argument is the ARU name. | |||||||||||||||||||||
| !aruSmokeAlarm | 1.3.6.1.4.1.318.0.288 | ||||||||||||||||||||
notification SEVERE: Remote ARU Smoke Alarm. The first argument is the host device serial number. The second argument is the host device name. The third argument is the ARU number. The fourth argument is the ARU name. | |||||||||||||||||||||
| !aruSmokeAlarmCleared | 1.3.6.1.4.1.318.0.289 | ||||||||||||||||||||
notification INFORMATIONAL: Remote ARU Smoke Alarm Cleared. The first argument is the host device serial number. The second argument is the host device name. The third argument is the ARU number. The fourth argument is the ARU name. | |||||||||||||||||||||
| !aruHighTemperatureAlarm | 1.3.6.1.4.1.318.0.290 | ||||||||||||||||||||
notification WARNING: ARU Exhaust temperature has exceeded the override threshold and the ARU has increased fan speed to maintain a safe environment in the rack. The first argument is the host device serial number. The second argument is the host device name. The third argument is the ARU number. The fourth argument is the ARU name. | |||||||||||||||||||||
| !aruHighTemperatureAlarmCleared | 1.3.6.1.4.1.318.0.291 | ||||||||||||||||||||
notification INFORMATIONAL: ARU temperature override state has been cleared. The first argument is the host device serial number. The second argument is the host device name. The third argument is the ARU number. The fourth argument is the ARU name. | |||||||||||||||||||||
| !aruExhaustTemperatureAlarm | 1.3.6.1.4.1.318.0.292 | ||||||||||||||||||||
notification SEVERE: ARU Extreme Exhaust Temperature Alarm. The ARU is unable to control the temperature within the rack The first argument is the host device serial number. The second argument is the host device name. The third argument is the ARU number. The fourth argument is the ARU name. | |||||||||||||||||||||
| !aruExhaustTemperatureAlarmCleared | 1.3.6.1.4.1.318.0.293 | ||||||||||||||||||||
notification INFORMATIONAL: Remote ARU Exhaust Temperature Alarm Cleared. The first argument is the host device serial number. The second argument is the host device name. The third argument is the ARU number. The fourth argument is the ARU name. | |||||||||||||||||||||
| !envAlinkCommunicationEstablished | 1.3.6.1.4.1.318.0.294 | ||||||||||||||||||||
notification INFORMATIONAL: Remote Probe Communication Established. The first argument is the host device serial number. The second argument is the host device name. The third argument is the probe number. The fourth argument is the probe name. | |||||||||||||||||||||
| !envAlinkCommunicationLost | 1.3.6.1.4.1.318.0.295 | ||||||||||||||||||||
notification SEVERE: Remote Probe Communication Lost. The first argument is the host device serial number. The second argument is the host device name. The third argument is the probe number. The fourth argument is the probe name. | |||||||||||||||||||||
| !emsAlinkPowerOverload | 1.3.6.1.4.1.318.0.296 | ||||||||||||||||||||
notification SEVERE: Alink Power Overload. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !emsAlinkPowerOverloadCleared | 1.3.6.1.4.1.318.0.297 | ||||||||||||||||||||
notification INFORMATIONAL: Alink Power Overload Cleared. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !upsOutletGroupTurnedOn | 1.3.6.1.4.1.318.0.298 | ||||||||||||||||||||
notification INFORMATIONAL: The specified Outlet Group turned on. | |||||||||||||||||||||
| !upsOutletGroupTurnedOff | 1.3.6.1.4.1.318.0.299 | ||||||||||||||||||||
notification WARNING: The specified Outlet Group turned off. | |||||||||||||||||||||
| !smwCriticalCondition | 1.3.6.1.4.1.318.0.300 | ||||||||||||||||||||
notification SEVERE: A Symmetra MW UPS critical condition has been detected. The first variable is the fault condition.
| |||||||||||||||||||||
| !smwCriticalConditionCleared | 1.3.6.1.4.1.318.0.301 | ||||||||||||||||||||
notification INFORMATIONAL: A Symmetra MW UPS critical condition has been cleared. The first variable is the fault condition.
| |||||||||||||||||||||
| !smwWarningCondition | 1.3.6.1.4.1.318.0.302 | ||||||||||||||||||||
notification WARNING: A Symmetra MW UPS warning condition has been detected. The first variable is the fault condition.
| |||||||||||||||||||||
| !smwWarningConditionCleared | 1.3.6.1.4.1.318.0.303 | ||||||||||||||||||||
notification WARNING: A Symmetra MW UPS warning condition has been cleared. The first variable is the fault condition.
| |||||||||||||||||||||
| !smwInformationalCondition | 1.3.6.1.4.1.318.0.304 | ||||||||||||||||||||
notification INFORMATIONAL: A Symmetra MW UPS informational condition has been detected. The first variable is the fault condition.
| |||||||||||||||||||||
| !smwInformationalConditionCleared | 1.3.6.1.4.1.318.0.305 | ||||||||||||||||||||
notification INFORMATIONAL: A Symmetra MW UPS informational condition has been cleared. The first variable is the fault condition.
| |||||||||||||||||||||
| !airCriticalCondition | 1.3.6.1.4.1.318.0.306 | ||||||||||||||||||||
notification SEVERE: An Air critical condition was detected. The first variable is the error condition text message. The second variable is the error number. | |||||||||||||||||||||
| !airCriticalConditionCleared | 1.3.6.1.4.1.318.0.307 | ||||||||||||||||||||
notification INFORMATIONAL: An Air critical condition was cleared. The first variable is the error condition text message. The second variable is the error number. | |||||||||||||||||||||
| !airWarningCondition | 1.3.6.1.4.1.318.0.308 | ||||||||||||||||||||
notification WARNING: An Air warning condition was detected. The first variable is the error condition text message. The second variable is the error number. | |||||||||||||||||||||
| !airWarningConditionCleared | 1.3.6.1.4.1.318.0.309 | ||||||||||||||||||||
notification WARNING: An Air warning condition was cleared. The first variable is the error condition text message. The second variable is the error number. | |||||||||||||||||||||
| !airInformationalCondition | 1.3.6.1.4.1.318.0.310 | ||||||||||||||||||||
notification INFORMATIONAL: An Air informational condition was detected. The first variable is the error condition text message. The second variable is the error number. | |||||||||||||||||||||
| !airInformationalConditionCleared | 1.3.6.1.4.1.318.0.311 | ||||||||||||||||||||
notification INFORMATIONAL: An Air informational condition was cleared. The first variable is the error condition text message. The second variable is the error number. | |||||||||||||||||||||
| !xPDUInputVoltageLowAlarm | 1.3.6.1.4.1.318.0.312 | ||||||||||||||||||||
notification SEVERE: Three-phase input voltage to the device is outside the specified limits. The first argument is the host device serial number. The second argument is the host device name. The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N, 4=unused, 5=L1-L2, 6=L2-L3, 7=L3-L1). The fourth argument is the measured voltage in tenths of Volts. The fifth argument is the threshold, in tenths of Volts, from which the alarm was generated. | |||||||||||||||||||||
| !xPDUInputVoltageLowAlarmCleared | 1.3.6.1.4.1.318.0.313 | ||||||||||||||||||||
notification INFORMATIONAL: Three-phase input voltage to the device is back within the specified limits. The first argument is the host device serial number. The second argument is the host device name. The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N, 4=unused, 5=L1-L2, 6=L2-L3, 7=L3-L1). The fourth argument is the measured voltage in tenths of Volts. | |||||||||||||||||||||
| !xPDUInputVoltageHighAlarm | 1.3.6.1.4.1.318.0.314 | ||||||||||||||||||||
notification SEVERE: Three-phase input voltage to the device is outside the specified limits. The first argument is the host device serial number. The second argument is the host device name. The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N, 4=unused, 5=L1-L2, 6=L2-L3, 7=L3-L1). The fourth argument is the measured voltage in tenths of Volts. The fifth argument is the threshold, in tenths of Volts, above which the alarm was generated. | |||||||||||||||||||||
| !xPDUInputVoltageHighAlarmCleared | 1.3.6.1.4.1.318.0.315 | ||||||||||||||||||||
notification INFORMATIONAL: Three-phase input voltage to the device is back within the specified limits. The first argument is the host device serial number. The second argument is the host device name. The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N, 4=unused, 5=L1-L2, 6=L2-L3, 7=L3-L1). The fourth argument is the measured voltage in tenths of Volts. | |||||||||||||||||||||
| !xPDUBypassVoltageLowAlarm | 1.3.6.1.4.1.318.0.316 | ||||||||||||||||||||
notification SEVERE: Three-phase bypass input voltage to the device is outside the specified limits. The first argument is the host device serial number. The second argument is the host device name. The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N). The fourth argument is the measured voltage in tenths of Volts. The fifth argument is the threshold, in tenths of Volts, from which the alarm was generated. | |||||||||||||||||||||
| !xPDUBypassVoltageLowAlarmCleared | 1.3.6.1.4.1.318.0.317 | ||||||||||||||||||||
notification INFORMATIONAL: Three-phase bypass input voltage to the device is back within the specified limits. The first argument is the host device serial number. The second argument is the host device name. The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N). The fourth argument is the measured voltage in tenths of Volts. | |||||||||||||||||||||
| !xPDUBypassVoltageHighAlarm | 1.3.6.1.4.1.318.0.318 | ||||||||||||||||||||
notification SEVERE: Three-phase bypass input voltage to the device is outside the specified limits. The first argument is the host device serial number. The second argument is the host device name. The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N). The fourth argument is the measured voltage in tenths of Volts. The fifth argument is the threshold, in tenths of Volts, above which the alarm was generated. | |||||||||||||||||||||
| !xPDUBypassVoltageHighAlarmCleared | 1.3.6.1.4.1.318.0.319 | ||||||||||||||||||||
notification INFORMATIONAL: Three-phase bypass input voltage to the device is back within the specified limits. The first argument is the host device serial number. The second argument is the host device name. The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N). The fourth argument is the measured voltage in tenths of Volts. | |||||||||||||||||||||
| !xPDUOutputVoltageLowAlarm | 1.3.6.1.4.1.318.0.320 | ||||||||||||||||||||
notification SEVERE: The three-phase output voltage of the device is outside the specified limits. The first argument is the host device serial number. The second argument is the host device name. The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N). The fourth argument is the measured voltage in tenths of Volts. The fifth argument is the threshold, in tenths of Volts, from which the alarm was generated. | |||||||||||||||||||||
| !xPDUOutputVoltageLowAlarmCleared | 1.3.6.1.4.1.318.0.321 | ||||||||||||||||||||
notification INFORMATIONAL: The three-phase output voltage of the device is back within the specified limits. The first argument is the host device serial number. The second argument is the host device name. The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N). The fourth argument is the measured voltage in tenths of Volts. | |||||||||||||||||||||
| !xPDUOutputVoltageHighAlarm | 1.3.6.1.4.1.318.0.322 | ||||||||||||||||||||
notification SEVERE: The three-phase output voltage of the device is outside the specified limits. The first argument is the host device serial number. The second argument is the host device name. The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N). The fourth argument is the measured voltage in tenths of Volts. The fifth argument is the threshold, in tenths of Volts, above which the alarm was generated. | |||||||||||||||||||||
| !xPDUOutputVoltageHighAlarmCleared | 1.3.6.1.4.1.318.0.323 | ||||||||||||||||||||
notification INFORMATIONAL: The three-phase output voltage of the device is back within the specified limits. The first argument is the host device serial number. The second argument is the host device name. The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N). The fourth argument is the measured voltage in tenths of Volts. | |||||||||||||||||||||
| !xPDUOutputCurrentLowAlarm | 1.3.6.1.4.1.318.0.324 | ||||||||||||||||||||
notification SEVERE: The three-phase output load current of the device is outside the specified limits. The first argument is the host device serial number. The second argument is the host device name. The third argument is the phase (1=L1, 2=L2, 3=L3). The fourth argument is the measured current in tenths of Amps. The fifth argument is the threshold, in tenths of Amps, from which the alarm was generated. | |||||||||||||||||||||
| !xPDUOutputCurrentLowAlarmCleared | 1.3.6.1.4.1.318.0.325 | ||||||||||||||||||||
notification INFORMATIONAL: The three-phase output load current of the device is back within the specified limits. The first argument is the host device serial number. The second argument is the host device name. The third argument is the phase (1=L1, 2=L2, 3=L3). The fourth argument is the measured current in tenths of Amps. | |||||||||||||||||||||
| !xPDUOutputCurrentHighAlarm | 1.3.6.1.4.1.318.0.326 | ||||||||||||||||||||
notification SEVERE: The three-phase load current of the device is outside the specified limits. The first argument is the host device serial number. The second argument is the host device name. The third argument is the phase (1=L1, 2=L2, 3=L3). The fourth argument is the measured current in tenths of Amps. The fifth argument is the threshold, in tenths of Amps, above which the alarm was generated. | |||||||||||||||||||||
| !xPDUOutputCurrentHighAlarmCleared | 1.3.6.1.4.1.318.0.327 | ||||||||||||||||||||
notification INFORMATIONAL: The three-phase output current of the device is back within the specified limits. The first argument is the host device serial number. The second argument is the host device name. The third argument is the phase (1=L1, 2=L2, 3=L3). The fourth argument is the measured current in tenths of Amps. | |||||||||||||||||||||
| !xPDUOutputFrequencyAlarm | 1.3.6.1.4.1.318.0.328 | ||||||||||||||||||||
notification SEVERE: The devices output frequency is outside the specified limits. The first argument is the host device serial number. The second argument is the host device name. The third argument is the frequency deviation from the nominal in tenths of Hertz. | |||||||||||||||||||||
| !xPDUOutputFrequencyAlarmCleared | 1.3.6.1.4.1.318.0.329 | ||||||||||||||||||||
notification INFORMATIONAL: The devices output frequency is back within the specified limits. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !xPDUSystemGroundCurrentAlarm | 1.3.6.1.4.1.318.0.330 | ||||||||||||||||||||
notification SEVERE: The earth ground current of the device is over the specified limits. The first argument is the host device serial number. The second argument is the host device name. The third argument is the measured current in tenths of Amps. The fourth argument is the threshold, in tenths of Amps, above which the alarm was generated. | |||||||||||||||||||||
| !xPDUSystemGroundCurrentAlarmCleared | 1.3.6.1.4.1.318.0.331 | ||||||||||||||||||||
notification INFORMATIONAL: The earth ground current of the device is back within the specified limits. The first argument is the host device serial number. The second argument is the host device name. The third argument is the measured current in tenths of Amps. | |||||||||||||||||||||
| !xPDUInputContactStateAbnormal | 1.3.6.1.4.1.318.0.332 | ||||||||||||||||||||
notification SEVERE: A user input contact on the device has changed to its abnormal state. The first argument is the host device serial number. The second argument is the host device name. The third argument is the input contact number. The fourth argument is the input contact name. The fifth argument is the input contact state (1=OPEN, 2=CLOSED). The sixth argument is the configured normal input contact state (1=OPEN, 2=CLOSED). | |||||||||||||||||||||
| !xPDUInputContactStateNormal | 1.3.6.1.4.1.318.0.333 | ||||||||||||||||||||
notification INFORMATIONAL: A user input contact on the device has changed to its normal state. The first argument is the host device serial number. The second argument is the host device name. The third argument is the input contact number. The fourth argument is the input contact name. The fifth argument is the input contact state (1=CLOSED, 2=OPEN). The sixth argument is the configured normal input contact state (1=OPEN, 2=CLOSED). | |||||||||||||||||||||
| !xPDUOutputNeutralCurrentHighAlarm | 1.3.6.1.4.1.318.0.334 | ||||||||||||||||||||
notification WARNING: The three-phase neutral current of the device is outside the specified limits. The first argument is the host device serial number. The second argument is the host device name. The third argument is the measured current in tenths of Amps. The fourth argument is the threshold, in tenths of Amps, above which the alarm was generated. | |||||||||||||||||||||
| !xPDUOutputNeutralCurrentHighAlarmCleared | 1.3.6.1.4.1.318.0.335 | ||||||||||||||||||||
notification INFORMATIONAL: The output neutral current of the device is back within the specified limits. The first argument is the host device serial number. The second argument is the host device name. The third argument is the measured current in tenths of Amps. | |||||||||||||||||||||
| !xPDUCoolingFanAlarm | 1.3.6.1.4.1.318.0.336 | ||||||||||||||||||||
notification SEVERE: The device's internal cooling fans have failed. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !xPDUCoolingFanAlarmCleared | 1.3.6.1.4.1.318.0.337 | ||||||||||||||||||||
notification INFORMATIONAL: The device's cooling fans are now functioning properly. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !xPDUTransformerTempAlarm | 1.3.6.1.4.1.318.0.338 | ||||||||||||||||||||
notification SEVERE: The device's isolation transformer is over temperature. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !xPDUTransformerTempAlarmCleared | 1.3.6.1.4.1.318.0.339 | ||||||||||||||||||||
notification INFORMATIONAL: The device's isolation transformer is no longer over temperature. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !xPDUBranchCurrentLowAlarm | 1.3.6.1.4.1.318.0.340 | ||||||||||||||||||||
notification WARNING: The current in a branch circuit is outside the limits specified for that branch circuit. The first argument is the host device serial number. The second argument is the host device name. The third argument is the panel position of the branch circuit (1-based index). The fourth argument is the measured current in tenths of Amps. The fifth argument is the threshold, in tenths of Amps, from which the alarm was generated. | |||||||||||||||||||||
| !xPDUBranchCurrentLowAlarmCleared | 1.3.6.1.4.1.318.0.341 | ||||||||||||||||||||
notification INFORMATIONAL: The current in a branch circuit is back within the limits specified for that branch circuit. The first argument is the host device serial number. The second argument is the host device name. The third argument is the panel position of the branch circuit (1-based index). The fourth argument is the measured current in tenths of Amps. | |||||||||||||||||||||
| !xPDUBranchCurrentHighAlarm | 1.3.6.1.4.1.318.0.342 | ||||||||||||||||||||
notification WARNING: The current in a branch circuit is outside the limits specified for that branch circuit. The first argument is the host device serial number. The second argument is the host device name. The third argument is the panel position of the branch circuit (1-based index). The fourth argument is the measured current in tenths of Amps. The fifth argument is the threshold, in tenths of Amps, above which the alarm was generated. | |||||||||||||||||||||
| !xPDUBranchCurrentHighAlarmCleared | 1.3.6.1.4.1.318.0.343 | ||||||||||||||||||||
notification INFORMATIONAL: The current in a branch circuit is back within the limits specified for that branch circuit. The first argument is the host device serial number. The second argument is the host device name. The third argument is the panel position of the branch circuit (1-based index). The fourth argument is the measured current in tenths of Amps. | |||||||||||||||||||||
| !xPDUInternalCommError | 1.3.6.1.4.1.318.0.344 | ||||||||||||||||||||
notification SEVERE: There is an internal communication error in the device. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !emsHardwareStateAbnormal | 1.3.6.1.4.1.318.0.345 | ||||||||||||||||||||
notification SEVERE: The device's hardware is improperly configured and operating outside normal bounds for the hardware. This can be caused by improper devices being connected to the EMS ports or Alink Current limit detection. | |||||||||||||||||||||
| !emsHardwareStateNormal | 1.3.6.1.4.1.318.0.346 | ||||||||||||||||||||
notification INFORMATIONAL: The device's hardware is in its normal operational state. The first argument is the host device serial number. | |||||||||||||||||||||
| !ceSevereCondition | 1.3.6.1.4.1.318.0.347 | ||||||||||||||||||||
notification SEVERE: A Custom Event severe condition was detected. The first variable is the custom event text message. The second variable is the custom event number. | |||||||||||||||||||||
| !ceSevereConditionCleared | 1.3.6.1.4.1.318.0.348 | ||||||||||||||||||||
notification INFORMATIONAL: A Custom Event severe condition was cleared. The first variable is the custom event text message. The second variable is the custom event number. | |||||||||||||||||||||
| !ceWarningCondition | 1.3.6.1.4.1.318.0.349 | ||||||||||||||||||||
notification WARNING: A Custom Event warning condition was detected. The first variable is the custom event text message. The second variable is the custom event number. | |||||||||||||||||||||
| !ceWarningConditionCleared | 1.3.6.1.4.1.318.0.350 | ||||||||||||||||||||
notification INFORMATIONAL: A Custom Event warning condition was cleared. The first variable is the custom event text message. The second variable is the custom event number. | |||||||||||||||||||||
| !ceInformationalCondition | 1.3.6.1.4.1.318.0.351 | ||||||||||||||||||||
notification INFORMATIONAL: A Custom Event informational condition was detected. The first variable is the custom event text message. The second variable is the custom event number. | |||||||||||||||||||||
| !ceInformationalConditionCleared | 1.3.6.1.4.1.318.0.352 | ||||||||||||||||||||
notification INFORMATIONAL: A Custom Event informational condition was cleared. The first variable is the custom event text message. The second variable is the custom event number. | |||||||||||||||||||||
| !upsInternalOverTemperature | 1.3.6.1.4.1.318.0.353 | ||||||||||||||||||||
| !upsInternalOverTemperatureCleared | 1.3.6.1.4.1.318.0.354 | ||||||||||||||||||||
| !upsMpuReset | 1.3.6.1.4.1.318.0.355 | ||||||||||||||||||||
| !upsOutputSwitchClosed | 1.3.6.1.4.1.318.0.356 | ||||||||||||||||||||
| !upsOutputSwitchOpened | 1.3.6.1.4.1.318.0.357 | ||||||||||||||||||||
| !upsCalibrationStackChanged | 1.3.6.1.4.1.318.0.358 | ||||||||||||||||||||
| !envMaxTempThresholdViolation | 1.3.6.1.4.1.318.0.359 | ||||||||||||||||||||
notification SEVERE: Max temperature threshold violated on the probe. The first argument is the host device serial number. The second argument is the host device name. The third argument is the current temperature. The fourth argument is the temperature scale. The fifth argument is the probe number. The sixth argument is the probe name. | |||||||||||||||||||||
| !envMaxTempThresholdViolationCleared | 1.3.6.1.4.1.318.0.360 | ||||||||||||||||||||
notification INFORMATIONAL: Max temperature threshold violation cleared on the probe. The first argument is the host device serial number. The second argument is the host device name. The third argument is the current temperature. The fourth argument is the temperature scale. The fifth argument is the probe number. The sixth argument is the probe name. | |||||||||||||||||||||
| !envMinTempThresholdViolation | 1.3.6.1.4.1.318.0.361 | ||||||||||||||||||||
notification SEVERE: Min temperature threshold violated on the probe. The first argument is the host device serial number. The second argument is the host device name. The third argument is the current temperature. The fourth argument is the temperature scale. The fifth argument is the probe number. The sixth argument is the probe name. | |||||||||||||||||||||
| !envMinTempThresholdViolationCleared | 1.3.6.1.4.1.318.0.362 | ||||||||||||||||||||
notification INFORMATIONAL: Min temperature threshold violation cleared on the probe. The first argument is the host device serial number. The second argument is the host device name. The third argument is the current temperature. The fourth argument is the temperature scale. The fifth argument is the probe number. The sixth argument is the probe name. | |||||||||||||||||||||
| !envMaxHumidityThresholdViolation | 1.3.6.1.4.1.318.0.363 | ||||||||||||||||||||
notification SEVERE: Max humidity threshold violated on the probe. The first argument is the host device serial number. The second argument is the host device name. The third argument is the current humidity The fourth argument is the probe number. The fifth argument is the probe name. | |||||||||||||||||||||
| !envMaxHumidityThresholdViolationCleared | 1.3.6.1.4.1.318.0.364 | ||||||||||||||||||||
notification INFORMATIONAL: Max humidity threshold violation cleared on the probe. The first argument is the host device serial number. The second argument is the host device name. The third argument is the current humidity. The fourth argument is the probe number. The fifth argument is the probe name. | |||||||||||||||||||||
| !envMinHumidityThresholdViolation | 1.3.6.1.4.1.318.0.365 | ||||||||||||||||||||
notification SEVERE: Min humidity threshold violated on the probe. The first argument is the host device serial number. The second argument is the host device name. The third argument is the current humidity The fourth argument is the probe number. The fifth argument is the probe name. | |||||||||||||||||||||
| !envMinHumidityThresholdViolationCleared | 1.3.6.1.4.1.318.0.366 | ||||||||||||||||||||
notification INFORMATIONAL: Min humidity threshold violation cleared on the probe. The first argument is the host device serial number. The second argument is the host device name. The third argument is the current humidity. The fourth argument is the probe number. The fifth argument is the probe name. | |||||||||||||||||||||
| !envSTIncTempRateViolation | 1.3.6.1.4.1.318.0.367 | ||||||||||||||||||||
notification SEVERE: Short-term increasing temperature rate violated on the probe. The first argument is the host device serial number. The second argument is the host device name. The third argument is the current temperature. The fourth argument is the temperature scale. The fifth argument is the probe number. The sixth argument is the probe name. | |||||||||||||||||||||
| !envSTIncTempRateViolationCleared | 1.3.6.1.4.1.318.0.368 | ||||||||||||||||||||
notification INFORMATIONAL: Short-term increasing temperature rate cleared on the probe. The first argument is the host device serial number. The second argument is the host device name. The third argument is the current temperature. The fourth argument is the temperature scale. The fifth argument is the probe number. The sixth argument is the probe name. | |||||||||||||||||||||
| !envSTDecTempRateViolation | 1.3.6.1.4.1.318.0.369 | ||||||||||||||||||||
notification SEVERE: Short-term decreasing temperature rate violated on the probe. The first argument is the host device serial number. The second argument is the host device name. The third argument is the current temperature. The fourth argument is the temperature scale. The fifth argument is the probe number. The sixth argument is the probe name. | |||||||||||||||||||||
| !envSTDecTempRateViolationCleared | 1.3.6.1.4.1.318.0.370 | ||||||||||||||||||||
notification INFORMATIONAL: Short-term decreasing temperature rate cleared on the probe. The first argument is the host device serial number. The second argument is the host device name. The third argument is the current temperature. The fourth argument is the temperature scale. The fifth argument is the probe number. The sixth argument is the probe name. | |||||||||||||||||||||
| !envLTIncTempRateViolation | 1.3.6.1.4.1.318.0.371 | ||||||||||||||||||||
notification SEVERE: Long-term increasing temperature rate violated on the probe. The first argument is the host device serial number. The second argument is the host device name. The third argument is the current temperature. The fourth argument is the temperature scale. The fifth argument is the probe number. The sixth argument is the probe name. | |||||||||||||||||||||
| !envLTIncTempRateViolationCleared | 1.3.6.1.4.1.318.0.372 | ||||||||||||||||||||
notification INFORMATIONAL: Long-term increasing temperature rate cleared on the probe. The first argument is the host device serial number. The second argument is the host device name. The third argument is the current temperature. The fourth argument is the temperature scale. The fifth argument is the probe number. The sixth argument is the probe name. | |||||||||||||||||||||
| !envLTDecTempRateViolation | 1.3.6.1.4.1.318.0.373 | ||||||||||||||||||||
notification SEVERE: Long-term decreasing temperature rate violated on the probe. The first argument is the host device serial number. The second argument is the host device name. The third argument is the current temperature. The fourth argument is the temperature scale. The fifth argument is the probe number. The sixth argument is the probe name. | |||||||||||||||||||||
| !envLTDecTempRateViolationCleared | 1.3.6.1.4.1.318.0.374 | ||||||||||||||||||||
notification INFORMATIONAL: Long-term decreasing temperature rate cleared on the probe. The first argument is the host device serial number. The second argument is the host device name. The third argument is the current temperature. The fourth argument is the temperature scale. The fifth argument is the probe number. The sixth argument is the probe name. | |||||||||||||||||||||
| !bmsCriticalCondition | 1.3.6.1.4.1.318.0.375 | ||||||||||||||||||||
notification SEVERE: A Battery Management System critical condition was detected. The first variable is the error condition text message. The second variable is the error number. | |||||||||||||||||||||
| !bmsCriticalConditionCleared | 1.3.6.1.4.1.318.0.376 | ||||||||||||||||||||
notification INFORMATIONAL: A Battery Management System critical condition was cleared. The first variable is the error condition text message. The second variable is the error number. | |||||||||||||||||||||
| !bmsWarningCondition | 1.3.6.1.4.1.318.0.377 | ||||||||||||||||||||
notification WARNING: A Battery Management System warning condition was detected. The first variable is the error condition text message. The second variable is the error number. | |||||||||||||||||||||
| !bmsWarningConditionCleared | 1.3.6.1.4.1.318.0.378 | ||||||||||||||||||||
notification WARNING: A Battery Management System warning condition was cleared. The first variable is the error condition text message. The second variable is the error number. | |||||||||||||||||||||
| !bmsInformationalCondition | 1.3.6.1.4.1.318.0.379 | ||||||||||||||||||||
notification INFORMATIONAL: A Battery Management System informational condition was detected. The first variable is the error condition text message. The second variable is the error number. | |||||||||||||||||||||
| !bmsInformationalConditionCleared | 1.3.6.1.4.1.318.0.380 | ||||||||||||||||||||
notification INFORMATIONAL: A Battery Management System informational condition was cleared. The first variable is the error condition text message. The second variable is the error number. | |||||||||||||||||||||
| !xATSOutputVoltageLowAlarm | 1.3.6.1.4.1.318.0.381 | ||||||||||||||||||||
notification SEVERE: The device three-phase output voltage of the device is outside the specified limits. The first argument is the host device serial number. The second argument is the host device name. The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N, 4=unused, 5=L1-L2, 6=L2-L3, 7=L3-L1). The fourth argument is the measured voltage in tenths of Volts. The fifth argument is the threshold, in tenths of Volts, from which the alarm was generated. | |||||||||||||||||||||
| !xATSOutputVoltageLowAlarmCleared | 1.3.6.1.4.1.318.0.382 | ||||||||||||||||||||
notification INFORMATIONAL: The devices three-phase output voltage is back within the specified limits. The first argument is the host device serial number. The second argument is the host device name. The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N, 4=unused, 5=L1-L2, 6=L2-L3, 7=L3-L1). The fourth argument is the measured voltage in tenths of Volts. | |||||||||||||||||||||
| !xATSOutputVoltageHighAlarm | 1.3.6.1.4.1.318.0.383 | ||||||||||||||||||||
notification SEVERE: The device three-phase output voltage of the device is outside the specified limits. The first argument is the host device serial number. The second argument is the host device name. The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N, 4=unused, 5=L1-L2, 6=L2-L3, 7=L3-L1). The fourth argument is the measured voltage in tenths of Volts. The fifth argument is the threshold, in tenths of Volts, above which the alarm is generated. | |||||||||||||||||||||
| !xATSOutputVoltageHighAlarmCleared | 1.3.6.1.4.1.318.0.384 | ||||||||||||||||||||
notification INFORMATIONAL: The devices three-phase output voltage is back within the specified limits. The first argument is the host device serial number. The second argument is the host device name. The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N, 4=unused, 5=L1-L2, 6=L2-L3, 7=L3-L1). The fourth argument is the measured voltage in tenths of Volts. | |||||||||||||||||||||
| !xATSOutputCurrentLowAlarm | 1.3.6.1.4.1.318.0.385 | ||||||||||||||||||||
notification SEVERE: The three-phase load current of the device is outside the specified limits. The first argument is the host device serial number. The second argument is the host device name. The third argument is the phase (1=L1, 2=L2, 3=L3). The fourth argument is the measured current in Amps. The fifth argument is the threshold, in Amps, from which the alarm was generated. | |||||||||||||||||||||
| !xATSOutputCurrentLowAlarmCleared | 1.3.6.1.4.1.318.0.386 | ||||||||||||||||||||
notification INFORMATIONAL: The three-phase load current of the device is back within the specified limits. The first argument is the host device serial number. The second argument is the host device name. The third argument is the phase (1=L1, 2=L2, 3=L3). The fourth argument is the measured current in Amps. | |||||||||||||||||||||
| !xATSOutputCurrentHighAlarm | 1.3.6.1.4.1.318.0.387 | ||||||||||||||||||||
notification SEVERE: The three-phase output load current of the device is outside the specified limits. The first argument is the host device serial number. The second argument is the host device name. The third argument is the phase (1=L1, 2=L2, 3=L3). The fourth argument is the measured current in Amps. The fifth argument is the threshold, in Amps, from which the alarm was generated. | |||||||||||||||||||||
| !xATSOutputCurrentHighAlarmCleared | 1.3.6.1.4.1.318.0.388 | ||||||||||||||||||||
notification INFORMATIONAL: The three-phase output load current of the device is back within the specified limits. The first argument is the host device serial number. The second argument is the host device name. The third argument is the phase (1=L1, 2=L2, 3=L3). The fourth argument is the measured current in Amps. | |||||||||||||||||||||
| !xATSOutputFrequencyAlarm | 1.3.6.1.4.1.318.0.389 | ||||||||||||||||||||
notification SEVERE: The devices output frequency is outside the specified limits. The first argument is the host device serial number. The second argument is the host device name. The third argument is the frequency deviation from the nominal in tenths of Hertz. The fourth argument is the frequency deviation threshold in tenths of Hertz, from which the alarm was generated. | |||||||||||||||||||||
| !xATSOutputFrequencyAlarmCleared | 1.3.6.1.4.1.318.0.390 | ||||||||||||||||||||
notification INFORMATIONAL: The devices output frequency is back within the specified limits. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !xATSInternalCommError | 1.3.6.1.4.1.318.0.391 | ||||||||||||||||||||
notification SEVERE: There is an internal communication error in the device. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !xATSInternalCommErrorCleared | 1.3.6.1.4.1.318.0.392 | ||||||||||||||||||||
notification INFORMATIONAL: Internal communication has been restored. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !xATSDataCommMismatchError | 1.3.6.1.4.1.318.0.393 | ||||||||||||||||||||
notification SEVERE: A data incompatibility exists within the device. This is typically the result of mismatches between firmware revisions of the transfer switch controller and the Network Management interface. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !xATSDataCommMismatchErrorCleared | 1.3.6.1.4.1.318.0.394 | ||||||||||||||||||||
notification INFORMATIONAL: The internal data incompatibility has been resolved. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !xATSGenCommLost | 1.3.6.1.4.1.318.0.395 | ||||||||||||||||||||
notification WARNING: The XATS cannot communicate with the generator. This will make unavailable all the xATSGenerator OIDs. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !xATSGenCommEstablished | 1.3.6.1.4.1.318.0.396 | ||||||||||||||||||||
notification INFORMATIONAL: The XATS has established communication with the generator. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !xATSNeutralPosition | 1.3.6.1.4.1.318.0.397 | ||||||||||||||||||||
notification WARNING: XATS has transferred to neutral position. In this position neither Source 1 nor Source 2 is selected, and the XATS will have no output voltage. The first argument is the host device serial number. The second argument is the host device name. The third argument is the mode in which the switch is operating (1=Auto, 2=Not-in-Auto, Abnormal Condition 3=Not-in-Auto, manual). | |||||||||||||||||||||
| !xATSSwitchTransferEvent | 1.3.6.1.4.1.318.0.398 | ||||||||||||||||||||
notification INFORMATIONAL: XATS has transferred from one source to the other. The first argument is the host device serial number. The second argument is the host device name. The third argument is the mode in which the switch is operating. (1=Auto, 2=Not-in-Auto, Abnormal Condition 3=Not-in-Auto, manual). The fourth argument is the input source selected (1=Source 1, 2=Source 2). The fifth argument is type of transfer that took place. (1=Closed, 2=Open, 3=Unknown) | |||||||||||||||||||||
| !xATSInternalATSFault | 1.3.6.1.4.1.318.0.399 | ||||||||||||||||||||
notification SEVERE: An internal XATS fault has been detected. The XATS may have forced itself to not-in-auto mode (abnormal condition), as indicated by the xATSSwitchStatusAutoSwitchOperationalMode OID. The first argument is the host device serial number. The second argument is the host device name. The third argument indicates the detected fault. 1=Cannot Close S1 2=Cannot Close S2 3=Cannot Open S1 4=Cannot Open S2 5=Cannot Trip Open S1 6=Cannot Trip Open S2 7=Start Contact Failure 8=Voltage Sensing Failure | |||||||||||||||||||||
| !xATSInternalATSFaultCleared | 1.3.6.1.4.1.318.0.400 | ||||||||||||||||||||
notification INFORMATIONAL: The detected internal XATS fault has been cleared. The first argument is the host device serial number. The second argument is the host device name. The third argument indicates the detected fault. 1=Cannot Close S1 2=Cannot Close S2 3=Cannot Open S1 4=Cannot Open S2 5=Cannot Trip Open S1 6=Cannot Trip Open S2 7=Start Contact Failure 8=Voltage Sensing Failure | |||||||||||||||||||||
| !xATSEngineStartAsserted | 1.3.6.1.4.1.318.0.401 | ||||||||||||||||||||
notification INFORMATIONAL: The XATS has asserted the Engine Start contact. This should result in the generator producing output voltage. The first argument is the host device serial number. The second argument is the host device name. The third argument indicates the reason that the start signal was asserted 1=Unknown, 2=S1 Low Voltage, 3=S1 High Voltage, 4=S1 Line Imbalance, 5=S1 Freq Range, 6=S1 Bad Rotation. | |||||||||||||||||||||
| !xATSEngineStopAsserted | 1.3.6.1.4.1.318.0.402 | ||||||||||||||||||||
notification INFORMATIONAL: The XATS has de-asserted the Engine Start contact. This should result in the generator shutting down, and producing no output voltage. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !xATSStartFailure | 1.3.6.1.4.1.318.0.403 | ||||||||||||||||||||
notification SEVERE: The generator failed to start. After assertion of the Engine Start signal, the quality of Source 2 was not seen as good. This alarm can be cleared using the xATSSwitchStatusClearLatchedAlarms OID. The first argument is the host device serial number. The second argument is the host device name. The third argument indicates the line quality at S2 1=Unknown, 2=S2 Low Voltage, 3=S2 High Voltage, 4=S2 Line Imbalance, 4=S2 Freq Range, 5=S2 Bad Rotation. | |||||||||||||||||||||
| !xATSStopFailure | 1.3.6.1.4.1.318.0.404 | ||||||||||||||||||||
notification WARNING: The generator failed to stop. After de-assertion of the Engine Start signal, the quality of Source 2 continued to be seen as good. This alarm can be cleared using the xATSSwitchStatusClearLatchedAlarms OID. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !xATSNotInAutomaticMode | 1.3.6.1.4.1.318.0.405 | ||||||||||||||||||||
notification SEVERE: Automatic Transfer Switch is not in automatic mode. The first argument is the host device serial number. The second argument is the host device name. The xATSSwitchStatusAutoSwitchStatus OID and the xATSSwitchStatusAutoSwitchOperationalMode OID can provide more information about the state of the XATS. | |||||||||||||||||||||
| !xATSNotInAutomaticModeCleared | 1.3.6.1.4.1.318.0.406 | ||||||||||||||||||||
notification INFORMATIONAL: Automatic Transfer Switch is in automatic mode. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !xATSEpoTripped | 1.3.6.1.4.1.318.0.407 | ||||||||||||||||||||
notification SEVERE: The device's Emergency Power Off (EPO) circuit is tripped. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !xATSEpoReset | 1.3.6.1.4.1.318.0.408 | ||||||||||||||||||||
notification INFORMATIONAL: The device's Emergency Power Off (EPO) circuit has been reset to the armed position. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !xATSEpoTestMode | 1.3.6.1.4.1.318.0.409 | ||||||||||||||||||||
notification WARNING: The device's Emergency Power Off (EPO) circuit has been switched back to the test position. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !xATSEpoArmed | 1.3.6.1.4.1.318.0.410 | ||||||||||||||||||||
notification INFORMATIONAL: The device's Emergency Power Off (EPO) circuit has been switched back to the armed position. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !xATSTestInitiated | 1.3.6.1.4.1.318.0.411 | ||||||||||||||||||||
notification INFORMATIONAL: A scheduled test has been initiated. The first argument is the host device serial number. The second argument is the host device name. The third argument is the type of test initiated (1=scheduled, 2=manual). | |||||||||||||||||||||
| !xATSTestCanceled | 1.3.6.1.4.1.318.0.412 | ||||||||||||||||||||
notification INFORMATIONAL: The scheduled test has been canceled The first argument is the host device serial number. The second argument is the host device name. The third argument is the type of test initiated (1=scheduled, 2=manual). | |||||||||||||||||||||
| !xATSTestFailed | 1.3.6.1.4.1.318.0.413 | ||||||||||||||||||||
notification SEVERE: The initiated test has failed. This alarm can be cleared using the xATSSwitchStatusClearLatchedAlarms OID. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !xATSTestPassed | 1.3.6.1.4.1.318.0.414 | ||||||||||||||||||||
notification INFORMATIONAL: The initiated test has passed switched back to the armed position. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !xATSInputContactStateAbnormal | 1.3.6.1.4.1.318.0.415 | ||||||||||||||||||||
notification SEVERE: A user input contact on the device has changed to its abnormal state. The first argument is the host device serial number. The second argument is the host device name. The third argument is the input contact number. The fourth argument is the input contact name. The fifth argument is the input contact state (1=OPEN, 2=CLOSED). The sixth argument is the configured normal input contact state (1=OPEN, 2=CLOSED). | |||||||||||||||||||||
| !xATSInputContactStateNormal | 1.3.6.1.4.1.318.0.416 | ||||||||||||||||||||
notification INFORMATIONAL: A user input contact on the device has changed to its normal state. The first argument is the host device serial number. The second argument is the host device name. The third argument is the input contact number. The fourth argument is the input contact name. The fifth argument is the input contact state (1=OPEN, 2=CLOSED). The sixth argument is the configured normal input contact state (1=OPEN, 2=CLOSED). | |||||||||||||||||||||
| !xATSRemoteStartContactMismatch | 1.3.6.1.4.1.318.0.417 | ||||||||||||||||||||
notification SEVERE: The state of the generator's Remote Start input and the ATS's Engine Start output do not match. This indicates something wrong in the Engine Start wiring, which must be corrected. This condition will prevent the generator from being started when needed. (See also: xATSGeneratorStatusRemoteStart and xATSSwitchStatusEngineStartSignal OIDs) The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !xATSRemoteStartContactMismatchCleared | 1.3.6.1.4.1.318.0.418 | ||||||||||||||||||||
notification INFORMATIONAL: Mismatch in the state of the generator's Remote Start input and the ATS's Engine Start output as been resolved. This indicates something wrong in the Engine Start wiring, which must be corrected. This condition will prevent the generator from being started when needed. (See also: xATSGeneratorStatusRemoteStart and xATSSwitchStatusEngineStartSignal OIDs) The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !xATSDoorOpenAlarm | 1.3.6.1.4.1.318.0.419 | ||||||||||||||||||||
notification WARNING: The XATS exterior panel door is open. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !xATSDoorOpenAlarmCleared | 1.3.6.1.4.1.318.0.420 | ||||||||||||||||||||
notification INFORMATIONAL: The external door to the device is closed. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !xATSDCBackupAlarm | 1.3.6.1.4.1.318.0.421 | ||||||||||||||||||||
notification WARNING: The XATS's DC backup has been lost. The XATS will lose power on Source 1 failure, causing the Engine Start signal to be asserted. The XATS will then restart from Source 2. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !xATSDCBackupAlarmCleared | 1.3.6.1.4.1.318.0.422 | ||||||||||||||||||||
notification INFORMATIONAL: DC backup alarm has been cleared in the device. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !xATSGeneratorLowCoolantLevelAlarm | 1.3.6.1.4.1.318.0.423 | ||||||||||||||||||||
notification SEVERE: Low coolant level has been detected in the generator. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. | |||||||||||||||||||||
| !xATSGeneratorLowCoolantLevelAlarmCleared | 1.3.6.1.4.1.318.0.424 | ||||||||||||||||||||
notification INFORMATIONAL: The detected low coolant level has been cleared in the generator. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. | |||||||||||||||||||||
| !xATSGeneratorVeryLowCoolantLevelAlarm | 1.3.6.1.4.1.318.0.425 | ||||||||||||||||||||
notification SEVERE: Very low coolant level has been detected in the generator. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. | |||||||||||||||||||||
| !xATSGeneratorVeryLowCoolantLevelAlarmCleared | 1.3.6.1.4.1.318.0.426 | ||||||||||||||||||||
notification INFORMATIONAL: The detected Very low coolant level has been cleared in the generator. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. | |||||||||||||||||||||
| !xATSGeneratorHighCoolantTempAlarm | 1.3.6.1.4.1.318.0.427 | ||||||||||||||||||||
notification SEVERE: High coolant temperature has been detected in the generator. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. | |||||||||||||||||||||
| !xATSGeneratorHighCoolantTempAlarmCleared | 1.3.6.1.4.1.318.0.428 | ||||||||||||||||||||
notification INFORMATIONAL: The detected high coolant temperature has been cleared in the generator. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. | |||||||||||||||||||||
| !xATSGeneratorVeryHighCoolantTempAlarm | 1.3.6.1.4.1.318.0.429 | ||||||||||||||||||||
notification SEVERE: Very high coolant temperature has been detected in the generator. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. | |||||||||||||||||||||
| !xATSGeneratorVeryHighCoolantTempAlarmCleared | 1.3.6.1.4.1.318.0.430 | ||||||||||||||||||||
notification INFORMATIONAL: The Very high coolant temperature condition has been cleared in the generator. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. | |||||||||||||||||||||
| !xATSGeneratorLowCoolantTempAlarm | 1.3.6.1.4.1.318.0.431 | ||||||||||||||||||||
notification WARNING: Low coolant temperature has been detected in the generator. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. | |||||||||||||||||||||
| !xATSGeneratorLowCoolantTempAlarmCleared | 1.3.6.1.4.1.318.0.432 | ||||||||||||||||||||
notification INFORMATIONAL: The low coolant temperature condition has been cleared in the generator. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. | |||||||||||||||||||||
| !xATSGeneratorLowOilLevelAlarm | 1.3.6.1.4.1.318.0.433 | ||||||||||||||||||||
notification SEVERE: Low oil level has been detected in the generator. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. | |||||||||||||||||||||
| !xATSGeneratorLowOilLevelAlarmCleared | 1.3.6.1.4.1.318.0.434 | ||||||||||||||||||||
notification INFORMATIONAL: Low oil level alarm has been cleared in the generator. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. | |||||||||||||||||||||
| !xATSGeneratorLowBatteryVoltDuringCrankAlarm | 1.3.6.1.4.1.318.0.435 | ||||||||||||||||||||
notification SEVERE: The generator's battery voltage has been detected as low while cranking the engine. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. | |||||||||||||||||||||
| !xATSGeneratorLowBatteryVoltDuringCrankAlarmCleared | 1.3.6.1.4.1.318.0.436 | ||||||||||||||||||||
notification INFORMATIONAL: The generator's low battery voltage while cranking condition has been cleared. The second argument is the host device name. The third argument is the OEM's fault/event code. | |||||||||||||||||||||
| !xATSGeneratorVeryLowBatteryVoltDuringCrankAlarm | 1.3.6.1.4.1.318.0.437 | ||||||||||||||||||||
notification SEVERE: The generator's battery voltage has been detected as very low while cranking the engine. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. | |||||||||||||||||||||
| !xATSGeneratorVeryLowBatteryVoltDuringCrankAlarmCleared | 1.3.6.1.4.1.318.0.438 | ||||||||||||||||||||
notification INFORMATIONAL: The generator's high battery voltage while cranking condition has been cleared. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. | |||||||||||||||||||||
| !xATSGeneratorEStop | 1.3.6.1.4.1.318.0.439 | ||||||||||||||||||||
notification SEVERE: The generator's emergency stop input has been activated. After the emergency stop signal has been removed, the E-Stop condition must be cleared before the generator can be started again. E-Stop conditions can only be cleared via the generator front panel. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. The fourth argument is the type of E-Stop (1=LOCAL, 2=REMOTE). | |||||||||||||||||||||
| !xATSGeneratorEStopCleared | 1.3.6.1.4.1.318.0.440 | ||||||||||||||||||||
notification INFORMATIONAL: The generator's emergency stop condition has been cleared. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. The fourth argument is the type of E-Stop (1=LOCAL, 2=REMOTE). | |||||||||||||||||||||
| !xATSGeneratorHighBatteryVolt | 1.3.6.1.4.1.318.0.441 | ||||||||||||||||||||
notification WARNING: The generator's battery voltage has been detected as high. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. | |||||||||||||||||||||
| !xATSGeneratorHighBatteryVoltCleared | 1.3.6.1.4.1.318.0.442 | ||||||||||||||||||||
notification INFORMATIONAL: The detected high battery voltage has been cleared, on the generator. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. | |||||||||||||||||||||
| !xATSGeneratorLowBatteryVolt | 1.3.6.1.4.1.318.0.443 | ||||||||||||||||||||
notification SEVERE: The generator's battery voltage has been detected as low. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. | |||||||||||||||||||||
| !xATSGeneratorLowBatteryVoltCleared | 1.3.6.1.4.1.318.0.444 | ||||||||||||||||||||
notification INFORMATIONAL: The detected low battery voltage has been cleared, on the generator. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. | |||||||||||||||||||||
| !xATSGeneratorControlSwitchNotAuto | 1.3.6.1.4.1.318.0.445 | ||||||||||||||||||||
notification SEVERE: The control switch on the generator is not in auto position. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. | |||||||||||||||||||||
| !xATSGeneratorControlSwitchNotAutoCleared | 1.3.6.1.4.1.318.0.446 | ||||||||||||||||||||
notification INFORMATIONAL: The control switch on the generator is in auto position. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. | |||||||||||||||||||||
| !xATSGeneratorLowOilPressure | 1.3.6.1.4.1.318.0.447 | ||||||||||||||||||||
notification SEVERE: The generator's oil pressure has been detected as low. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. | |||||||||||||||||||||
| !xATSGeneratorLowOilPressureCleared | 1.3.6.1.4.1.318.0.448 | ||||||||||||||||||||
notification INFORMATIONAL: The detected low oil pressure has been cleared, on the generator. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. | |||||||||||||||||||||
| !xATSGeneratorVeryLowOilPressure | 1.3.6.1.4.1.318.0.449 | ||||||||||||||||||||
notification SEVERE: The generator's oil pressure has been detected as very low. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. | |||||||||||||||||||||
| !xATSGeneratorVeryLowOilPressureCleared | 1.3.6.1.4.1.318.0.450 | ||||||||||||||||||||
notification INFORMATIONAL: The detected v.low oil pressure has been cleared, on the generator. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. | |||||||||||||||||||||
| !xATSGeneratorOverload | 1.3.6.1.4.1.318.0.451 | ||||||||||||||||||||
notification SEVERE: The generator is overloaded. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. | |||||||||||||||||||||
| !xATSGeneratorOverloadCleared | 1.3.6.1.4.1.318.0.452 | ||||||||||||||||||||
notification INFORMATIONAL: The generator is running within loading limits. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. | |||||||||||||||||||||
| !xATSGeneratorLowACVEvent | 1.3.6.1.4.1.318.0.453 | ||||||||||||||||||||
notification SEVERE: The generator AC voltage is outside the acceptable bounds. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. | |||||||||||||||||||||
| !xATSGeneratorLowACVEventCleared | 1.3.6.1.4.1.318.0.454 | ||||||||||||||||||||
notification INFORMATIONAL: The generator AC voltage is within normal bounds. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. | |||||||||||||||||||||
| !xATSGeneratorHighACVEvent | 1.3.6.1.4.1.318.0.455 | ||||||||||||||||||||
notification SEVERE: The generator AC voltage is outside the acceptable bounds. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. | |||||||||||||||||||||
| !xATSGeneratorHighACVEventCleared | 1.3.6.1.4.1.318.0.456 | ||||||||||||||||||||
notification INFORMATIONAL: The generator AC voltage is within normal bounds. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. | |||||||||||||||||||||
| !xATSGeneratorOverspeed | 1.3.6.1.4.1.318.0.457 | ||||||||||||||||||||
notification SEVERE: The generator is running over the acceptable RPM. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. | |||||||||||||||||||||
| !xATSGeneratorOverspeedCleared | 1.3.6.1.4.1.318.0.458 | ||||||||||||||||||||
notification INFORMATIONAL: The generator overspeed shutdown has been cleared. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. | |||||||||||||||||||||
| !xATSGeneratorEngineCold | 1.3.6.1.4.1.318.0.459 | ||||||||||||||||||||
notification SEVERE: The generator engine is cold, may not start. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. | |||||||||||||||||||||
| !xATSGeneratorEngineColdCleared | 1.3.6.1.4.1.318.0.460 | ||||||||||||||||||||
notification INFORMATIONAL: The engine is not cold to start. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. | |||||||||||||||||||||
| !xATSGeneratorOutputBreakerOpen | 1.3.6.1.4.1.318.0.461 | ||||||||||||||||||||
notification SEVERE: The generators output breaker has been detected as open. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. | |||||||||||||||||||||
| !xATSGeneratorOutputBreakerOpenCleared | 1.3.6.1.4.1.318.0.462 | ||||||||||||||||||||
notification INFORMATIONAL: The engine is not cold to start. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. | |||||||||||||||||||||
| !xATSGeneratorLowFuelLevelAlarm | 1.3.6.1.4.1.318.0.463 | ||||||||||||||||||||
notification WARNING: The tank fuel level is below the limits specified in the xATSGeneratorFuelSystemLowFuelLevelThreshold OID. The first argument is the host device serial number. The second argument is the host device name. The third argument is the measured fuel level in percent of full. | |||||||||||||||||||||
| !xATSGeneratorLowFuelLevelAlarmCleared | 1.3.6.1.4.1.318.0.464 | ||||||||||||||||||||
notification INFORMATIONAL: The tank fuel level is back above the specified limit. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !xATSGeneratorVeryLowFuelLevelAlarm | 1.3.6.1.4.1.318.0.465 | ||||||||||||||||||||
notification SEVERE: The tank fuel level is below the low threshold limits. The first argument is the host device serial number. The second argument is the host device name. The third argument is the measured tank fuel level in percent of full. | |||||||||||||||||||||
| !xATSGeneratorVeryLowFuelLevelAlarmCleared | 1.3.6.1.4.1.318.0.466 | ||||||||||||||||||||
notification INFORMATIONAL: The detected low tank level has been cleared in the device. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !xATSGeneratorLowRunTimeAlarm | 1.3.6.1.4.1.318.0.467 | ||||||||||||||||||||
notification WARNING: The estimated runtime is below the limits specified. The first argument is the host device serial number. The second argument is the host device name. The third argument is the estimated runtime in hours. | |||||||||||||||||||||
| !xATSGeneratorLowRunTimeAlarmCleared | 1.3.6.1.4.1.318.0.468 | ||||||||||||||||||||
notification INFORMATIONAL: The detected low runtime has been cleared in the device. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !xATSGeneratorVeryLowRunTimeAlarm | 1.3.6.1.4.1.318.0.469 | ||||||||||||||||||||
notification SEVERE: The estimated runtime is below the limits specified in the xATSGeneratorFuelSystemVeryLowRunTimeThreshold OID. The first argument is the host device serial number. The second argument is the host device name. The third argument is the estimated runtime in hours. | |||||||||||||||||||||
| !xATSGeneratorVeryLowRunTimeAlarmCleared | 1.3.6.1.4.1.318.0.470 | ||||||||||||||||||||
notification INFORMATIONAL: The detected low runtime has been cleared in the device. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !xATSGeneratorServiceDueAlarm | 1.3.6.1.4.1.318.0.471 | ||||||||||||||||||||
notification WARNING: The generator is due for scheduled service. Generation of this alarm is based on calendar days since and/or actual generator run-hours since last service. This alarm is cleared using the xATSGeneratorServiceResetRecord OID. (See also: xATSGeneratorServiceCalendarIntervalThreshold and xATSGeneratorServiceRunHoursThreshold OIDs) The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !xATSGeneratorServiceDueAlarmCleared | 1.3.6.1.4.1.318.0.472 | ||||||||||||||||||||
notification INFORMATIONAL: The generator's service registers have been reset. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !xATSGeneratorShutdown | 1.3.6.1.4.1.318.0.473 | ||||||||||||||||||||
notification SEVERE: The generator is shutdown. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. | |||||||||||||||||||||
| !xATSGeneratorShutdownCleared | 1.3.6.1.4.1.318.0.474 | ||||||||||||||||||||
notification INFORMATIONAL: The generator shutdown alarm is cleared. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. | |||||||||||||||||||||
| !xATSGeneratorBatteryCharger | 1.3.6.1.4.1.318.0.475 | ||||||||||||||||||||
notification SEVERE: The generator battery charger is nonfunctional. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. | |||||||||||||||||||||
| !xATSGeneratorBatteryChargerCleared | 1.3.6.1.4.1.318.0.476 | ||||||||||||||||||||
notification INFORMATIONAL: Fault in the generator battery charger is cleared. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. | |||||||||||||||||||||
| !xATSGeneratorGenericEvent | 1.3.6.1.4.1.318.0.477 | ||||||||||||||||||||
notification WARNING: Any generic generator event. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. | |||||||||||||||||||||
| !xATSGeneratorGenericEventCleared | 1.3.6.1.4.1.318.0.478 | ||||||||||||||||||||
notification INFORMATIONAL: Generated generic generator event is cleared. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. | |||||||||||||||||||||
| !xPDUInternalCommErrorCleared | 1.3.6.1.4.1.318.0.479 | ||||||||||||||||||||
notification INFORMATIONAL: Internal communication has been restored. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !xPDUSystemStateAlarm | 1.3.6.1.4.1.318.0.480 | ||||||||||||||||||||
notification SEVERE: The PDU's breakers (Q1, Q2 & Q3) are in a configuration that might lead to system unavailability. it may signify a temporary condition, when the breakers are placed in an atypical manner as the user transitions to (UPS OPERATION or MAINTENANCE BYPASS) The first argument is the host device serial number. The second argument is the host device name. The third argument is the type of state change (1=NO UPS INPUT, 2=NO PANEL FEED, 3=ATYPICAL BYPASS MODE). note: The NO_PANEL_FEED alarm is applicable only for PDUs with system bypass. | |||||||||||||||||||||
| !xPDUSystemStateAlarmCleared | 1.3.6.1.4.1.318.0.481 | ||||||||||||||||||||
notification INFORMATIONAL: The PDU's breakers (Q1, Q2 & Q3) are set in a configuration that is a non-alarm state. The first argument is the host device serial number. The second argument is the host device name. The third argument is the type of state change (1=NO UPS INPUT, 2=NO PANEL FEED, 3=ATYPICAL BYPASS MODE). note: The NO_PANEL_FEED alarm is applicable only for PDUs with system bypass. | |||||||||||||||||||||
| !xPDUEpoTestMode | 1.3.6.1.4.1.318.0.482 | ||||||||||||||||||||
notification WARNING: The device's Emergency Power Off (EPO) circuit has been switched back to the test position. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !xPDUEpoArmed | 1.3.6.1.4.1.318.0.483 | ||||||||||||||||||||
notification INFORMATIONAL: The device's Emergency Power Off (EPO) circuit has been switched back to the armed position. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !xPDUFuseBlownAlarm | 1.3.6.1.4.1.318.0.484 | ||||||||||||||||||||
notification SEVERE: One or more fuses in this PDU have been detected as open. These fuses are in the feed to the UPS associated with this PDU. The first argument is the host device serial number. The second argument is the host device name. The third argument is the phase (1=L1, 2=L2, 3=L3). | |||||||||||||||||||||
| !xPDUFuseBlownAlarmCleared | 1.3.6.1.4.1.318.0.485 | ||||||||||||||||||||
notification INFORMATIONAL: A previous check fuse alarm in this PDU has cleared. These fuses are in the feed to the UPS associated with this PDU. The first argument is the host device serial number. The second argument is the host device name. The third argument is the phase (1=L1, 2=L2, 3=L3). | |||||||||||||||||||||
| !xPDUBreakerPositionAlarm | 1.3.6.1.4.1.318.0.486 | ||||||||||||||||||||
notification SEVERE: A PDU breaker is in a state that compromises system availability. The first argument is the host device serial number. The second argument is the host device name. The third argument is the breaker (1=MAIN INPUT, 2=BYPASS INPUT, 3=CROSS TIE, 4=OUTPUT). note: The OUTPUT breaker position alarm is applicable only for PDUs with no system bypass. The fourth argument is the breaker position (1=OPEN, 2=CLOSED). | |||||||||||||||||||||
| !xPDUBreakerPositionAlarmCleared | 1.3.6.1.4.1.318.0.487 | ||||||||||||||||||||
notification INFORMATIONAL: A PDU breaker is no longer in a state that compromises system availability. The first argument is the host device serial number. The second argument is the host device name. The third argument is the breaker (1=MAIN INPUT, 2=BYPASS INPUT, 3=CROSS TIE, 4=OUTPUT). note: The OUTPUT breaker position alarm cleared is applicable only for PDUs with no system bypass. | |||||||||||||||||||||
| !xPDUBreakerChangeEvent | 1.3.6.1.4.1.318.0.488 | ||||||||||||||||||||
notification INFORMATIONAL: A system breaker or switch within the device has changed state. They are generated when any of the Q1, Q2 or Q3 breakers have changed states. The first argument is the host device serial number. The second argument is the host device name. The third argument is the breaker that has changed (1=UPS FEED (Q1), 2=UPS OUTPUT(Q2), 3=MAINTENANCE BYPASS (Q3). The fourth argument is the state of the breaker that has changed (1=OPEN, 2=CLOSED). The fifth argument is a 8-bit field representing the state of all breakers in the system, when any of one of the Q1, Q2 or Q3 breakers have changed state. The bit map is represented in the following manner (b7, b6 ... b0) b0 - UPS FEED (Q1) b1 - MAINTENANCE BYPASS (Q3) b2 - UPS OUTPUT (Q2) b3 - MAIN INPUT b4 - BYPASS INPUT b5 - CROSS-TIE OUTPUT Example: value of 60 (0x3C) indicates that the CROSS_TIE, BYPASS and MAIN INPUT, and Q2 breakers are CLOSED and Q3, Q1 breakers are OPEN. | |||||||||||||||||||||
| !xPDUDataCommMismatchError | 1.3.6.1.4.1.318.0.489 | ||||||||||||||||||||
notification SEVERE: A data incompatibility exists within the device. This is typically the result of mismatches between firmware revisions of the transfer switch controller and the Network Management interface. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !xPDUDataCommMismatchErrorCleared | 1.3.6.1.4.1.318.0.490 | ||||||||||||||||||||
notification INFORMATIONAL: The internal data incompatibility has been resolved. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !xPDUSystemInMaintenanceBypassMode | 1.3.6.1.4.1.318.0.491 | ||||||||||||||||||||
notification WARNING: The PDU state has changed to maintenance bypass mode. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !xPDUSystemInUPSOperationalMode | 1.3.6.1.4.1.318.0.492 | ||||||||||||||||||||
notification INFORMATIONAL: The PDU state has changed to UPS operational mode. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !xATSGeneratorFuelTankRuptureAlarm | 1.3.6.1.4.1.318.0.493 | ||||||||||||||||||||
notification WARNING: Detected a rupture in the inner wall of the generator fuel tank. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. | |||||||||||||||||||||
| !xATSGeneratorFuelTankRuptureAlarmCleared | 1.3.6.1.4.1.318.0.494 | ||||||||||||||||||||
notification INFORMATIONAL: The rupture in the inner wall of the generator is not detected. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. | |||||||||||||||||||||
| !xATSGeneratorGroundFaultAlarm | 1.3.6.1.4.1.318.0.495 | ||||||||||||||||||||
notification SEVERE: Generator ground fault alarm. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. | |||||||||||||||||||||
| !xATSGeneratorGroundFaultAlarmCleared | 1.3.6.1.4.1.318.0.496 | ||||||||||||||||||||
notification INFORMATIONAL: Generator ground fault alarm cleared. The first argument is the host device serial number. The second argument is the host device name. The third argument is the OEM's fault/event code. | |||||||||||||||||||||
| !xATSOutputLoadPoweredByGeneratorAlarm | 1.3.6.1.4.1.318.0.497 | ||||||||||||||||||||
notification WARNING: The system load on the output of the ATS is being powered by source 2 (generator). The first argument is the host device serial number. The second argument is the host device name. The third argument indicates if the load is powered by the generator, when 'load testing' the generator (1 = LIVE, 2 = TEST). | |||||||||||||||||||||
| !xATSOutputLoadPoweredByGeneratorAlarmCleared | 1.3.6.1.4.1.318.0.498 | ||||||||||||||||||||
notification INFORMATIONAL: The system load on the output of the ATS is no longer being powered by source 2 (generator). The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !xAPCControllerFirmwareUpdateTransferStart | 1.3.6.1.4.1.318.0.499 | ||||||||||||||||||||
notification INFORMATIONAL: Start controller firmware transfer in the device. The first argument is the host device serial number. The second argument is the host model name that initiated the transfer. The third argument is the name of the file that is transferred. The fourth argument is the updated revision of the file, if available The fifth argument is the reason for the update, if available (1=User request, 2=Automatic upgrade by NMC, 3=Unknown). | |||||||||||||||||||||
| !xAPCControllerFirmwareUpdateTransferComplete | 1.3.6.1.4.1.318.0.500 | ||||||||||||||||||||
notification INFORMATIONAL: Transfer of controller firmware was completed in the device. The first argument is the host device serial number. The second argument is the host device model name that completed the transfer. The third argument is the name of the file that was transferred. The fourth argument is the revision of the file that was transferred, if available. | |||||||||||||||||||||
| !xAPCControllerFirmwareUpdateTransferFailed | 1.3.6.1.4.1.318.0.501 | ||||||||||||||||||||
notification SEVERE: Transfer of controller firmware failed. The first argument is the host device serial number. The second argument is the host device model name that failed to transfer. The third argument is the name of the file that failed the transfer, if available. The fourth argument is the reason for failure. | |||||||||||||||||||||
| !upsPfcInputRelayFailure | 1.3.6.1.4.1.318.0.502 | ||||||||||||||||||||
notification WARNING: The PFC (Power Factor Correction) input relay failure exists.
| |||||||||||||||||||||
| !upsPfcInputRelayFailureCleared | 1.3.6.1.4.1.318.0.503 | ||||||||||||||||||||
notification INFORMATIONAL: The PFC (Power Factor Correction) input relay failure cleared.
| |||||||||||||||||||||
| !upsInverterOverTemperature | 1.3.6.1.4.1.318.0.504 | ||||||||||||||||||||
| !upsInverterOverTemperatureCleared | 1.3.6.1.4.1.318.0.505 | ||||||||||||||||||||
| !upsBatteryOverVoltage | 1.3.6.1.4.1.318.0.506 | ||||||||||||||||||||
| !upsBatteryOverVoltageCleared | 1.3.6.1.4.1.318.0.507 | ||||||||||||||||||||
| !upsEepromFault | 1.3.6.1.4.1.318.0.508 | ||||||||||||||||||||
| !upsEepromFaultCleared | 1.3.6.1.4.1.318.0.509 | ||||||||||||||||||||
| !aruFanRuntimeAlarm | 1.3.6.1.4.1.318.0.510 | ||||||||||||||||||||
notification WARNING: The total running hours for a fan has exceeded the run hour threshold. The first argument is the host device serial number. The second argument is the host device name. The third argument is the ARU number. The fourth argument is the ARU name. The fifth argument indicates which fan in the ARU. | |||||||||||||||||||||
| !aruFanRuntimeAlarmCleared | 1.3.6.1.4.1.318.0.511 | ||||||||||||||||||||
notification INFORMATIONAL: The total running hours for a fan is no longer above the fan runhour threshold. The first argument is the host device serial number. The second argument is the host device name. The third argument is the ARU number. The fourth argument is the ARU name. The fifth argument indicates which fan in the ARU. | |||||||||||||||||||||
| !aruFanPoorPerformanceAlarm | 1.3.6.1.4.1.318.0.512 | ||||||||||||||||||||
notification WARNING: Poor fan performance has been detected in the ARU, indicating that the fan may be close to failing. The first argument is the host device serial number. The second argument is the host device name. The third argument is the ARU number. The fourth argument is the ARU name. The fifth argument indicates which fan in the ARU. | |||||||||||||||||||||
| !aruFanPoorPerformanceAlarmCleared | 1.3.6.1.4.1.318.0.513 | ||||||||||||||||||||
notification INFORMATIONAL: Fan performance is no longer degraded. The first argument is the host device serial number. The second argument is the host device name. The third argument is the ARU number. The fourth argument is the ARU name. The fifth argument indicates which fan in the ARU. | |||||||||||||||||||||
| !aruRedundantPowerLostAlarm | 1.3.6.1.4.1.318.0.514 | ||||||||||||||||||||
notification WARNING: One of the redundant line cords on the ARU is no longer receiving AC power. The first argument is the host device serial number. The second argument is the host device name. The third argument is the ARU number. The fourth argument is the ARU name. | |||||||||||||||||||||
| !aruRedundantPowerLostAlarmCleared | 1.3.6.1.4.1.318.0.515 | ||||||||||||||||||||
notification INFORMATIONAL: Line-cord redundancy has been restored to the ARU. The first argument is the host device serial number. The second argument is the host device name. The third argument is the ARU number. The fourth argument is the ARU name. | |||||||||||||||||||||
| !apcDeviceConfigChange | 1.3.6.1.4.1.318.0.516 | ||||||||||||||||||||
notification INFORMATIONAL: A device configuration change has been made on the device. The first argument is the device serial number. The second argument is the device name. The third argument is a secondary device id number. | |||||||||||||||||||||
| !apcEnvSensorConnected | 1.3.6.1.4.1.318.0.517 | ||||||||||||||||||||
notification INFORMATIONAL: A sensor has been connected to the host device. The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. The fourth argument is the sensor number. The fifth argument is the sensor name. | |||||||||||||||||||||
| !apcEnvSensorDisconnected | 1.3.6.1.4.1.318.0.518 | ||||||||||||||||||||
notification SEVERE: A sensor has been disconnected from the device. The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. The fourth argument is the sensor number. The fifth argument is the sensor name. | |||||||||||||||||||||
| !apcEnvMaxTempThresholdViolation | 1.3.6.1.4.1.318.0.519 | ||||||||||||||||||||
notification SEVERE: Max temperature threshold violated on the sensor. The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. The fourth argument is the sensor number. The fifth argument is the sensor name. | |||||||||||||||||||||
| !apcEnvMaxTempThresholdViolationCleared | 1.3.6.1.4.1.318.0.520 | ||||||||||||||||||||
notification INFORMATIONAL: Max temperature threshold violation cleared on the sensor. The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. The fourth argument is the sensor number. The fifth argument is the sensor name. | |||||||||||||||||||||
| !apcEnvHighTempThresholdViolation | 1.3.6.1.4.1.318.0.521 | ||||||||||||||||||||
notification WARNING: High temperature threshold violated on the sensor. The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. The fourth argument is the sensor number. The fifth argument is the sensor name. | |||||||||||||||||||||
| !apcEnvHighTempThresholdViolationCleared | 1.3.6.1.4.1.318.0.522 | ||||||||||||||||||||
notification INFORMATIONAL: High temperature threshold violation cleared on the sensor. The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. The fourth argument is the sensor number. The fifth argument is the sensor name. | |||||||||||||||||||||
| !apcEnvLowTempThresholdViolation | 1.3.6.1.4.1.318.0.523 | ||||||||||||||||||||
notification WARNING: Low temperature threshold violated on the sensor. The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. The fourth argument is the sensor number. The fifth argument is the sensor name. | |||||||||||||||||||||
| !apcEnvLowTempThresholdViolationCleared | 1.3.6.1.4.1.318.0.524 | ||||||||||||||||||||
notification INFORMATIONAL: Low temperature threshold violation cleared on the sensor. The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. The fourth argument is the sensor number. The fifth argument is the sensor name. | |||||||||||||||||||||
| !apcEnvMinTempThresholdViolation | 1.3.6.1.4.1.318.0.525 | ||||||||||||||||||||
notification SEVERE: Min temperature threshold violated on the sensor. The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. The fourth argument is the sensor number. The fifth argument is the sensor name. | |||||||||||||||||||||
| !apcEnvMinTempThresholdViolationCleared | 1.3.6.1.4.1.318.0.526 | ||||||||||||||||||||
notification INFORMATIONAL: Min temperature threshold violation cleared on the sensor. The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. The sixth argument is the sensor number. The seventh argument is the sensor name. | |||||||||||||||||||||
| !apcEnvSTIncTempRateViolation | 1.3.6.1.4.1.318.0.527 | ||||||||||||||||||||
notification SEVERE: Short-term increasing temperature rate violated on the sensor. The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. The fourth argument is the sensor number. The fifth argument is the sensor name. | |||||||||||||||||||||
| !apcEnvSTIncTempRateViolationCleared | 1.3.6.1.4.1.318.0.528 | ||||||||||||||||||||
notification INFORMATIONAL: Short-term increasing temperature rate cleared on the sensor. The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. The fourth argument is the sensor number. The fifth argument is the sensor name. | |||||||||||||||||||||
| !apcEnvSTDecTempRateViolation | 1.3.6.1.4.1.318.0.529 | ||||||||||||||||||||
notification SEVERE: Short-term decreasing temperature rate violated on the sensor. The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. The fourth argument is the sensor number. The fifth argument is the sensor name. | |||||||||||||||||||||
| !apcEnvSTDecTempRateViolationCleared | 1.3.6.1.4.1.318.0.530 | ||||||||||||||||||||
notification INFORMATIONAL: Short-term decreasing temperature rate cleared on the sensor. The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. The fourth argument is the sensor number. The fifth argument is the sensor name. | |||||||||||||||||||||
| !apcEnvLTIncTempRateViolation | 1.3.6.1.4.1.318.0.531 | ||||||||||||||||||||
notification SEVERE: Long-term increasing temperature rate violated on the sensor. The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. The fourth argument is the sensor number. The fifth argument is the sensor name. | |||||||||||||||||||||
| !apcEnvLTIncTempRateViolationCleared | 1.3.6.1.4.1.318.0.532 | ||||||||||||||||||||
notification INFORMATIONAL: Long-term increasing temperature rate cleared on the sensor. The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. The fourth argument is the sensor number. The fifth argument is the sensor name. | |||||||||||||||||||||
| !apcEnvLTDecTempRateViolation | 1.3.6.1.4.1.318.0.533 | ||||||||||||||||||||
notification SEVERE: Long-term decreasing temperature rate violated on the sensor. The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. The fourth argument is the sensor number. The fifth argument is the sensor name. | |||||||||||||||||||||
| !apcEnvLTDecTempRateViolationCleared | 1.3.6.1.4.1.318.0.534 | ||||||||||||||||||||
notification INFORMATIONAL: Long-term decreasing temperature rate cleared on the sensor. The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. The fourth argument is the sensor number. The fifth argument is the sensor name. | |||||||||||||||||||||
| !apcEnvMaxHumidityThresholdViolation | 1.3.6.1.4.1.318.0.535 | ||||||||||||||||||||
notification SEVERE: Max humidity threshold violated on the sensor. The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. The fourth argument is the sensor number. The fifth argument is the sensor name. | |||||||||||||||||||||
| !apcEnvMaxHumidityThresholdViolationCleared | 1.3.6.1.4.1.318.0.536 | ||||||||||||||||||||
notification INFORMATIONAL: Max humidity threshold violation cleared on the sensor. The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. The fourth argument is the sensor number. The fifth argument is the sensor name. | |||||||||||||||||||||
| !apcEnvHighHumidityThresholdViolation | 1.3.6.1.4.1.318.0.537 | ||||||||||||||||||||
notification WARNING: High humidity threshold violated on the sensor. The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. The fourth argument is the sensor number. The fifth argument is the sensor name. | |||||||||||||||||||||
| !apcEnvHighHumidityThresholdViolationCleared | 1.3.6.1.4.1.318.0.538 | ||||||||||||||||||||
notification INFORMATIONAL: High humidity threshold violation cleared on the sensor. The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. The fourth argument is the sensor number. The fifth argument is the sensor name. | |||||||||||||||||||||
| !apcEnvLowHumidityThresholdViolation | 1.3.6.1.4.1.318.0.539 | ||||||||||||||||||||
notification WARNING: Low humidity threshold violated on the sensor. The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. The fourth argument is the sensor number. The fifth argument is the sensor name. | |||||||||||||||||||||
| !apcEnvLowHumidityThresholdViolationCleared | 1.3.6.1.4.1.318.0.540 | ||||||||||||||||||||
notification INFORMATIONAL: Low humidity threshold violation cleared on the sensor. The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. The fourth argument is the sensor number. The fifth argument is the sensor name. | |||||||||||||||||||||
| !apcEnvMinHumidityThresholdViolation | 1.3.6.1.4.1.318.0.541 | ||||||||||||||||||||
notification SEVERE: Min humidity threshold violated on the sensor. The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. The fourth argument is the sensor number. The fifth argument is the sensor name. | |||||||||||||||||||||
| !apcEnvMinHumidityThresholdViolationCleared | 1.3.6.1.4.1.318.0.542 | ||||||||||||||||||||
notification INFORMATIONAL: Min humidity threshold violation cleared on the sensor. The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. The fourth argument is the sensor number. The fifth argument is the sensor name. | |||||||||||||||||||||
| !apcBeaconConnected | 1.3.6.1.4.1.318.0.543 | ||||||||||||||||||||
notification INFORMATIONAL: A beacon has been connected to the device. The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. | |||||||||||||||||||||
| !apcBeaconDisconnected | 1.3.6.1.4.1.318.0.544 | ||||||||||||||||||||
notification SEVERE: A beacon has been disconnected from the device. The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. | |||||||||||||||||||||
| !apcBeaconOn | 1.3.6.1.4.1.318.0.545 | ||||||||||||||||||||
notification INFORMATIONAL: A beacon has gone on (activated). The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. | |||||||||||||||||||||
| !apcBeaconOff | 1.3.6.1.4.1.318.0.546 | ||||||||||||||||||||
notification INFORMATIONAL: A beacon has gone off (deactivated). The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. | |||||||||||||||||||||
| !apcOutletStateAbnormal | 1.3.6.1.4.1.318.0.547 | ||||||||||||||||||||
notification WARNING: An outlet on the device has changed to its abnormal state. The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. The fourth argument is the outlet number. The fifth argument is the outlet name. The sixth argument is the current outlet state (1=ON, 2=OFF). The seventh argument is the configured normal outlet state (1=ON, 2=OFF). | |||||||||||||||||||||
| !apcOutletStateNormal | 1.3.6.1.4.1.318.0.548 | ||||||||||||||||||||
notification INFORMATIONAL: An outlet on the device has changed to its normal state. The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. The fourth argument is the outlet number. The fifth argument is the outlet name. The sixth argument is the current outlet state (1=ON, 2=OFF). The seventh argument is the configured normal outlet state (1=ON, 2=OFF). | |||||||||||||||||||||
| !apcOutputRelayStateAbnormal | 1.3.6.1.4.1.318.0.549 | ||||||||||||||||||||
notification WARNING: An output relay on the device has changed to its abnormal state. The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. The fourth argument is the output relay number. The fifth argument is the output relay name. The sixth argument is the current output relay state (1=CLOSED, 2=OPEN). The seventh argument is the configured normal output relay state (1=CLOSED, 2=OPEN). | |||||||||||||||||||||
| !apcOutputRelayStateNormal | 1.3.6.1.4.1.318.0.550 | ||||||||||||||||||||
notification INFORMATIONAL: An output relay on the device has changed to its normal state. The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. The fourth argument is the output relay number. The fifth argument is the output relay name. The sixth argument is the current output relay state (1=CLOSED, 2=OPEN). The seventh argument is the configured normal output relay state (1=CLOSED, 2=OPEN). | |||||||||||||||||||||
| !apcHardwareStateAbnormal | 1.3.6.1.4.1.318.0.551 | ||||||||||||||||||||
notification SEVERE: The device's hardware is improperly configured and operating outside normal bounds for the hardware. This can be caused by improper devices being connected to device ports or Alink Current limit detection. The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. The fourth argument is a hardware specific state code. | |||||||||||||||||||||
| !apcHardwareStateNormal | 1.3.6.1.4.1.318.0.552 | ||||||||||||||||||||
notification INFORMATIONAL: The device's hardware is in its normal operational state. The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. | |||||||||||||||||||||
| !apcCriticalDiscreteInputContactStateAbnormal | 1.3.6.1.4.1.318.0.553 | ||||||||||||||||||||
notification SEVERE: A discrete input contact on the device has changed to its abnormal state. The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. The fourth argument is the input contact number. The fifth argument is the input contact name. The sixth argument is the input contact state (1=CLOSED, 2=OPEN). The seventh argument is the configured normal input contact state (1=CLOSED, 2=OPEN). | |||||||||||||||||||||
| !apcCriticalDiscreteInputContactStateNormal | 1.3.6.1.4.1.318.0.554 | ||||||||||||||||||||
notification INFORMATIONAL: A discrete input contact on the device has changed to its normal state. The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. The fourth argument is the input contact number. The fifth argument is the input contact name. The sixth argument is the input contact state (1=CLOSED, 2=OPEN). The seventh argument is the configured normal input contact state (1=CLOSED, 2=OPEN). | |||||||||||||||||||||
| !apcWarningDiscreteInputContactStateAbnormal | 1.3.6.1.4.1.318.0.555 | ||||||||||||||||||||
notification WARNING: A discrete input contact on the device has changed to its abnormal state. The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. The fourth argument is the input contact number. The fifth argument is the input contact name. The sixth argument is the input contact state (1=CLOSED, 2=OPEN). The seventh argument is the configured normal input contact state (1=CLOSED, 2=OPEN). | |||||||||||||||||||||
| !apcWarningDiscreteInputContactStateNormal | 1.3.6.1.4.1.318.0.556 | ||||||||||||||||||||
notification INFORMATIONAL: A discrete input contact on the device has changed to its normal state. The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. The fourth argument is the input contact number. The fifth argument is the input contact name. The sixth argument is the input contact state (1=CLOSED, 2=OPEN). The seventh argument is the configured normal input contact state (1=CLOSED, 2=OPEN). | |||||||||||||||||||||
| !apcInformationalDiscreteInputContactStateAbnormal | 1.3.6.1.4.1.318.0.557 | ||||||||||||||||||||
notification INFORMATIONAL: A discrete input contact on the device has changed to its abnormal state. The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. The fourth argument is the input contact number. The fifth argument is the input contact name. The sixth argument is the input contact state (1=CLOSED, 2=OPEN). The seventh argument is the configured normal input contact state (1=CLOSED, 2=OPEN). | |||||||||||||||||||||
| !apcInformationalDiscreteInputContactStateNormal | 1.3.6.1.4.1.318.0.558 | ||||||||||||||||||||
notification INFORMATIONAL: A discrete input contact on the device has changed to its normal state. The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. The fourth argument is the input contact number. The fifth argument is the input contact name. The sixth argument is the input contact state (1=CLOSED, 2=OPEN). The seventh argument is the configured normal input contact state (1=CLOSED, 2=OPEN). | |||||||||||||||||||||
| !apcAnalogInputMaxThresholdViolation | 1.3.6.1.4.1.318.0.559 | ||||||||||||||||||||
notification SEVERE: Maximum threshold violated on an analog input. The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. The fourth argument is the input number. The fifth argument is the input name. | |||||||||||||||||||||
| !apcAnalogInputMaxThresholdViolationCleared | 1.3.6.1.4.1.318.0.560 | ||||||||||||||||||||
notification INFORMATIONAL: Maximum threshold violation cleared on the analog input. The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. The fourth argument is the input number. The fifth argument is the input name. | |||||||||||||||||||||
| !apcAnalogInputHighThresholdViolation | 1.3.6.1.4.1.318.0.561 | ||||||||||||||||||||
notification WARNING: High threshold violated on an analog input. The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. The fourth argument is the input number. The fifth argument is the input name. | |||||||||||||||||||||
| !apcAnalogInputHighThresholdViolationCleared | 1.3.6.1.4.1.318.0.562 | ||||||||||||||||||||
notification INFORMATIONAL: High threshold violation cleared on the analog input. The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. The fourth argument is the input number. The fifth argument is the input name. | |||||||||||||||||||||
| !apcAnalogInputLowThresholdViolation | 1.3.6.1.4.1.318.0.563 | ||||||||||||||||||||
notification WARNING: Low threshold violated on an analog input. The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. The fourth argument is the input number. The fifth argument is the input name. | |||||||||||||||||||||
| !apcAnalogInputLowThresholdViolationCleared | 1.3.6.1.4.1.318.0.564 | ||||||||||||||||||||
notification INFORMATIONAL: Low threshold violation cleared on the analog input. The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. The fourth argument is the input number. The fifth argument is the input name. | |||||||||||||||||||||
| !apcAnalogInputMinThresholdViolation | 1.3.6.1.4.1.318.0.565 | ||||||||||||||||||||
notification SEVERE: Minimum threshold violated on an analog input. The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. The fourth argument is the input number. The fifth argument is the input name. | |||||||||||||||||||||
| !apcAnalogInputMinThresholdViolationCleared | 1.3.6.1.4.1.318.0.566 | ||||||||||||||||||||
notification INFORMATIONAL: Minimum threshold violation cleared on the analog input. The first argument is the host device serial number. The second argument is the host device name. The third argument is a secondary device id number. The fourth argument is the input number. The fifth argument is the input name. | |||||||||||||||||||||
| !apcDeviceClearLostComms | 1.3.6.1.4.1.318.0.567 | ||||||||||||||||||||
notification INFORMATIONAL: Lost communications reset command has been issued. The first argument is the device serial number. The second argument is the device name. The third argument is a secondary device id number. | |||||||||||||||||||||
| !apcDeviceConnected | 1.3.6.1.4.1.318.0.568 | ||||||||||||||||||||
notification INFORMATIONAL: A device has been connected to the host. The first argument is the host serial number. The second argument is the host name. The third argument is the device number. The fourth argument is the device name. | |||||||||||||||||||||
| !apcDeviceDisconnected | 1.3.6.1.4.1.318.0.569 | ||||||||||||||||||||
notification SEVERE: A device has been disconnected from the host. The first argument is the host serial number. The second argument is the host name. The third argument is the device number. The fourth argument is the device name. | |||||||||||||||||||||
| !apcUnregisteredUserAccessDenied | 1.3.6.1.4.1.318.0.570 | ||||||||||||||||||||
notification INFORMATIONAL: An unregistered user has tried to access the device. The first argument is the host device serial number. The second argument is the host device name. The third argument is the host device location. The fourth argumant is the door identifier. The fifth argument is the unregistered user's RFID. | |||||||||||||||||||||
| !apcRegisteredUserAccessDenied | 1.3.6.1.4.1.318.0.571 | ||||||||||||||||||||
notification INFORMATIONAL: A registered user has been denied access to the device. The first argument is the host device serial number. The second argument is the host device name. The third argument is the host device location. The fourth argumant is the door identifier. The fifth argument is the user name. | |||||||||||||||||||||
| !apcRegisteredUserConfigChange | 1.3.6.1.4.1.318.0.572 | ||||||||||||||||||||
notification INFORMATIONAL: Registered user configuration change. The first argument is the host device serial number. The second argument is the host device name. The third argument is the host device location. The fourth argument is the user name. | |||||||||||||||||||||
| !apcDoorUnlocked | 1.3.6.1.4.1.318.0.573 | ||||||||||||||||||||
notification INFORMATIONAL: A door has been unlocked. The first argument is the host device serial number. The second argument is the host device name. The third argument is the host device location. The fourth argument is the door identifier. The fifth argument is the door access user. The sixth argument is the door access type. | |||||||||||||||||||||
| !apcDoorLocked | 1.3.6.1.4.1.318.0.574 | ||||||||||||||||||||
notification INFORMATIONAL: A door has been locked. The first argument is the host device serial number. The second argument is the host device name. The third argument is the host device location. The fourth argument is the door identifier. The fifth argument is the door access user. The sixth argument is the door access type. | |||||||||||||||||||||
| !apcHandleOpened | 1.3.6.1.4.1.318.0.575 | ||||||||||||||||||||
notification INFORMATIONAL: A door handle has been opened. The first argument is the host device serial number. The second argument is the host device name. The third argument is the host device location. The fourth argument is the door identifier, (1=front, 2=rear). | |||||||||||||||||||||
| !apcHandleClosed | 1.3.6.1.4.1.318.0.576 | ||||||||||||||||||||
notification INFORMATIONAL: A door handle has been closed. The first argument is the host device serial number. The second argument is the host device name. The third argument is the host device location. The fourth argument is the door identifier, (1=front, 2=rear). | |||||||||||||||||||||
| !apcDoorOpened | 1.3.6.1.4.1.318.0.577 | ||||||||||||||||||||
notification INFORMATIONAL: A door has been opened. The first argument is the host device serial number. The second argument is the host device name. The third argument is the host device location. The fourth argument is the door identifier, (1=front, 2=rear). | |||||||||||||||||||||
| !apcDoorClosed | 1.3.6.1.4.1.318.0.578 | ||||||||||||||||||||
notification INFORMATIONAL: A door has been closed. The first argument is the host device serial number. The second argument is the host device name. The third argument is the host device location. The fourth argument is the door identifier, (1=front, 2=rear). | |||||||||||||||||||||
| !apcKeyOverrideUnlocked | 1.3.6.1.4.1.318.0.580 | ||||||||||||||||||||
notification SEVERE: Key override unlock has occurred. The first argument is the host device serial number. The second argument is the host device name. The third argument is the host device location. The fourth argument is the door identifier, (1=front, 2=rear). | |||||||||||||||||||||
| !apcKeyOverrideLocked | 1.3.6.1.4.1.318.0.581 | ||||||||||||||||||||
notification INFORMATIONAL: Key override lock has occurred. The first argument is the host device serial number. The second argument is the host device name. The third argument is the host device location. The fourth argument is the door identifier, (1=front, 2=rear). | |||||||||||||||||||||
| !apcForcedEntry | 1.3.6.1.4.1.318.0.582 | ||||||||||||||||||||
notification SEVERE: A forced entry condition has occurred. The first argument is the host device serial number. The second argument is the host device name. The third argument is the host device location. The fourth argument is the door identifier, (1=front, 2=rear). | |||||||||||||||||||||
| !apcForcedEntryCleared | 1.3.6.1.4.1.318.0.583 | ||||||||||||||||||||
notification INFORMATIONAL: A forced entry condition has been cleared. The first argument is the host device serial number. The second argument is the host device name. The third argument is the host device location. The fourth argument is the door identifier, (1=front, 2=rear). | |||||||||||||||||||||
| !apcRelockTimeout | 1.3.6.1.4.1.318.0.584 | ||||||||||||||||||||
notification SEVERE: A relock timout has occurred. The first argument is the host device serial number. The second argument is the host device name. The third argument is the host device location. The fourth argument is the door identifier, (1=front, 2=rear). | |||||||||||||||||||||
| !apcRelockTimeoutCleared | 1.3.6.1.4.1.318.0.585 | ||||||||||||||||||||
notification INFORMATIONAL: A relock timout has been cleared. The first argument is the host device serial number. The second argument is the host device name. The third argument is the host device location. The fourth argument is the door identifier, (1=front, 2=rear). | |||||||||||||||||||||
| !apcDoorSenseDisconnected | 1.3.6.1.4.1.318.0.586 | ||||||||||||||||||||
notification SEVERE: A door sensor was disconnected. The first argument is the host device serial number. The second argument is the host device name. The third argument is the host device location. The fourth argument is the door identifier, (1=front, 2=rear). | |||||||||||||||||||||
| !apcDoorSenseConnected | 1.3.6.1.4.1.318.0.587 | ||||||||||||||||||||
notification INFORMATIONAL: A forced entry condition has been cleared. The first argument is the host device serial number. The second argument is the host device name. The third argument is the host device location. The fourth argument is the door identifier, (1=front, 2=rear). | |||||||||||||||||||||
| !apcDoorLostComms | 1.3.6.1.4.1.318.0.588 | ||||||||||||||||||||
notification SEVERE: Communications have been lost with the door. The first argument is the host device serial number. The second argument is the host device name. The third argument is the host device location. The fourth argument is the door identifier, (1=front, 2=rear). | |||||||||||||||||||||
| !apcDoorEstablishedComms | 1.3.6.1.4.1.318.0.589 | ||||||||||||||||||||
notification INFORMATIONAL: Communications have been established with the door. The first argument is the host device serial number. The second argument is the host device name. The third argument is the host device location. The fourth argument is the door identifier, (1=front, 2=rear). | |||||||||||||||||||||
| !apcRegisteredUserAccessChange | 1.3.6.1.4.1.318.0.590 | ||||||||||||||||||||
notification INFORMATIONAL: Registered user access changed. The first argument is the host device serial number. The second argument is the host device name. The third argument is the host device location. The fourth argument is the user name. | |||||||||||||||||||||
| !apcUnregisteredUserStatusChange | 1.3.6.1.4.1.318.0.591 | ||||||||||||||||||||
notification INFORMATIONAL: Unregistered user status changed. The first argument is the host device serial number. The second argument is the host device name. The third argument is the host device location. The fourth argument is the user name. | |||||||||||||||||||||
| !apcDeviceClearUserConfigs | 1.3.6.1.4.1.318.0.592 | ||||||||||||||||||||
notification INFORMATIONAL: User configurations reset command has been issued. The first argument is the device serial number. The second argument is the device name. The third argument is a secondary device id number. | |||||||||||||||||||||
| !upsBatteryTempSensorFault | 1.3.6.1.4.1.318.0.600 | ||||||||||||||||||||
| !upsBatteryTempSensorFaultCleared | 1.3.6.1.4.1.318.0.601 | ||||||||||||||||||||
| !upsBatterySoftBusStartFault | 1.3.6.1.4.1.318.0.602 | ||||||||||||||||||||
| !upsBatterySoftBusStartFaultCleared | 1.3.6.1.4.1.318.0.603 | ||||||||||||||||||||
| !apcOutputShortCircuit | 1.3.6.1.4.1.318.0.604 | ||||||||||||||||||||
| !apcOutputShortCircuitCleared | 1.3.6.1.4.1.318.0.605 | ||||||||||||||||||||
| !apcOutputRelayFault | 1.3.6.1.4.1.318.0.606 | ||||||||||||||||||||
| !apcOutputRelayFaultCleared | 1.3.6.1.4.1.318.0.607 | ||||||||||||||||||||
| !upsPfcFault | 1.3.6.1.4.1.318.0.608 | ||||||||||||||||||||
| !upsPfcFaultCleared | 1.3.6.1.4.1.318.0.609 | ||||||||||||||||||||
| !apcDcBusOverVoltage | 1.3.6.1.4.1.318.0.610 | ||||||||||||||||||||
| !apcDcBusOverVoltageCleared | 1.3.6.1.4.1.318.0.611 | ||||||||||||||||||||
| !upsInverterFault | 1.3.6.1.4.1.318.0.612 | ||||||||||||||||||||
| !upsInverterFaultCleared | 1.3.6.1.4.1.318.0.613 | ||||||||||||||||||||
| !apcAdConverterFault | 1.3.6.1.4.1.318.0.614 | ||||||||||||||||||||
| !apcAdConverterFaultCleared | 1.3.6.1.4.1.318.0.615 | ||||||||||||||||||||
| !apcLogicPowerSupplyFault | 1.3.6.1.4.1.318.0.616 | ||||||||||||||||||||
| !apcLogicPowerSupplyFaultCleared | 1.3.6.1.4.1.318.0.617 | ||||||||||||||||||||
| !apcTransformerDCImbalanceFault | 1.3.6.1.4.1.318.0.618 | ||||||||||||||||||||
notification WARNING: The DC component of the transformer's current is too high.
| |||||||||||||||||||||
| !apcTransformerDCImbalanceFaultCleared | 1.3.6.1.4.1.318.0.619 | ||||||||||||||||||||
| !upsBackfeedRelayFault | 1.3.6.1.4.1.318.0.620 | ||||||||||||||||||||
| !upsBackfeedRelayFaultCleared | 1.3.6.1.4.1.318.0.621 | ||||||||||||||||||||
| !upsBypassRelayFault | 1.3.6.1.4.1.318.0.622 | ||||||||||||||||||||
| !upsBypassRelayFaultCleared | 1.3.6.1.4.1.318.0.623 | ||||||||||||||||||||
| !xPDUBranchCurrentMinAlarm | 1.3.6.1.4.1.318.0.626 | ||||||||||||||||||||
notification SEVERE: The current in a branch circuit is outside the limits specified for that branch circuit. The first argument is the host device serial number. The second argument is the host device name. The third argument is the panel position of the branch circuit (1-based index). The fourth argument is the measured current in tenths of Amps. The fifth argument is the threshold, in tenths of Amps, from which the alarm was generated. | |||||||||||||||||||||
| !xPDUBranchCurrentMinAlarmCleared | 1.3.6.1.4.1.318.0.627 | ||||||||||||||||||||
notification INFORMATIONAL: The current in a branch circuit is back within the limits specified for that branch circuit. The first argument is the host device serial number. The second argument is the host device name. The third argument is the panel position of the branch circuit (1-based index). The fourth argument is the measured current in tenths of Amps. | |||||||||||||||||||||
| !xPDUBranchCurrentMaxAlarm | 1.3.6.1.4.1.318.0.628 | ||||||||||||||||||||
notification SEVERE: The current in a branch circuit is outside the limits specified for that branch circuit. The first argument is the host device serial number. The second argument is the host device name. The third argument is the panel position of the branch circuit (1-based index). The fourth argument is the measured current in tenths of Amps. The fifth argument is the threshold, in tenths of Amps, above which the alarm was generated. | |||||||||||||||||||||
| !xPDUBranchCurrentMaxAlarmCleared | 1.3.6.1.4.1.318.0.629 | ||||||||||||||||||||
notification INFORMATIONAL: The current in a branch circuit is back within the limits specified for that branch circuit. The first argument is the host device serial number. The second argument is the host device name. The third argument is the panel position of the branch circuit (1-based index). The fourth argument is the measured current in tenths of Amps. | |||||||||||||||||||||
| !rPDUOutletLowLoad | 1.3.6.1.4.1.318.0.630 | ||||||||||||||||||||
notification WARNING: A Rack PDU has violated the outlet low load threshold. The first argument is the serial number. The second argument is the device name. The third argument is the outlet number. | |||||||||||||||||||||
| !rPDUOutletLowLoadCleared | 1.3.6.1.4.1.318.0.631 | ||||||||||||||||||||
notification INFORMATIONAL: The outlet low load condition on a Rack PDU has been cleared. The first argument is the serial number. The second argument is the device name. The third argument is the outlet number. | |||||||||||||||||||||
| !rPDUOutletNearOverload | 1.3.6.1.4.1.318.0.632 | ||||||||||||||||||||
notification WARNING: A Rack PDU is near an outlet overload condition. The first argument is the serial number. The second argument is the device name. The third argument is the outlet number. | |||||||||||||||||||||
| !rPDUOutletNearOverloadCleared | 1.3.6.1.4.1.318.0.633 | ||||||||||||||||||||
notification INFORMATIONAL: The outlet near overload condition on a Rack PDU has been cleared. The first argument is the serial number. The second argument is the device name. The third argument is the outlet number. | |||||||||||||||||||||
| !rPDUOutletOverload | 1.3.6.1.4.1.318.0.634 | ||||||||||||||||||||
notification SEVERE: A Rack PDU is in an overload condition. The first argument is the serial number. The second argument is the device name. The third argument is the outlet number. | |||||||||||||||||||||
| !rPDUOutletOverloadCleared | 1.3.6.1.4.1.318.0.635 | ||||||||||||||||||||
notification INFORMATIONAL: The outlet overload condition on a Rack PDU has been cleared. The first argument is the serial number. The second argument is the device name. The third argument is the outlet number. | |||||||||||||||||||||
| !apcTestTrap | 1.3.6.1.4.1.318.0.636 | ||||||||||||||||||||
notification INFORMATIONAL: Trap used to test SNMP trap functionality. The first argument is a place holder for test variables.
| |||||||||||||||||||||
| !baseFanFailureCleared | 1.3.6.1.4.1.318.0.637 | ||||||||||||||||||||
| !atsLowLoad | 1.3.6.1.4.1.318.0.638 | ||||||||||||||||||||
notification WARNING: ATS has violated the bank or phase low load threshold. The first argument is the serial number. The second argument is the product name. The third argument is the phase number The fourth argument is the bank number. -1 is returned if bank does not exist. | |||||||||||||||||||||
| !atsLowLoadCleared | 1.3.6.1.4.1.318.0.639 | ||||||||||||||||||||
notification INFORMATIONAL: The bank or phase low load condition on an ATS has been cleared. The first argument is the serial number. The second argument is the product name. The third argument is the phase number The fourth argument is the bank number. -1 is returned if bank does not exist. | |||||||||||||||||||||
| !atsNearOverload | 1.3.6.1.4.1.318.0.640 | ||||||||||||||||||||
notification WARNING: ATS has violated the bank or phase near overload threshold. The first argument is the serial number. The second argument is the product name. The third argument is the phase number The fourth argument is the bank number. -1 is returned if bank does not exist. | |||||||||||||||||||||
| !atsNearOverloadCleared | 1.3.6.1.4.1.318.0.641 | ||||||||||||||||||||
notification INFORMATIONAL: The bank or phase near overload condition on an ATS has been cleared. The first argument is the serial number. The second argument is the product name. The third argument is the phase number The fourth argument is the bank number. -1 is returned if bank does not exist. | |||||||||||||||||||||
| !atsOverload | 1.3.6.1.4.1.318.0.642 | ||||||||||||||||||||
notification SEVERE: ATS is in an overload condition. The first argument is the serial number. The second argument is the product name. The third argument is the phase number. The fourth argument is the bank number. -1 is returned if bank does not exist. | |||||||||||||||||||||
| !atsOverloadCleared | 1.3.6.1.4.1.318.0.643 | ||||||||||||||||||||
notification INFORMATIONAL: The bank or phase overload condition on an ATS has been cleared. The first argument is the serial number. The second argument is the product name. The third argument is the phase number. The fourth argument is the bank number. -1 is returned if bank does not exist. | |||||||||||||||||||||
| !atsRMSOverVoltage | 1.3.6.1.4.1.318.0.644 | ||||||||||||||||||||
notification SEVERE: Overvoltage condition violated. The first argument is the serial number. The second argument is the product name. The third argument is an integer representing the source: 0=A, 1=B. | |||||||||||||||||||||
| !atsRMSOverVoltageCleared | 1.3.6.1.4.1.318.0.645 | ||||||||||||||||||||
notification INFORMATIONAL: Overvoltage condition cleared. The first argument is the serial number. The second argument is the product name. The third argument is an integer representing the source: 0=A, 1=B. | |||||||||||||||||||||
| !atsRMSUnderVoltage | 1.3.6.1.4.1.318.0.646 | ||||||||||||||||||||
notification SEVERE: Undervoltage condition violated. The first argument is the serial number. The second argument is the product name. The third argument is an integer representing the source: 0=A, 1=B. | |||||||||||||||||||||
| !atsRMSUnderVoltageCleared | 1.3.6.1.4.1.318.0.647 | ||||||||||||||||||||
notification INFORMATIONAL: Undervoltage condition cleared. The first argument is the serial number. The second argument is the product name. The third argument is an integer representing the source: 0=A, 1=B. | |||||||||||||||||||||
| !atsRMSOverFrequency | 1.3.6.1.4.1.318.0.648 | ||||||||||||||||||||
notification SEVERE: OverFrequency condition violated. The first argument is the serial number. The second argument is the product name. The third argument is an integer representing the source: 0=A, 1=B. | |||||||||||||||||||||
| !atsRMSOverFrequencyCleared | 1.3.6.1.4.1.318.0.649 | ||||||||||||||||||||
notification INFORMATIONAL: OverFrequency condition cleared. The first argument is the serial number. The second argument is the product name. The third argument is an integer representing the source: 0=A, 1=B. | |||||||||||||||||||||
| !atsRMSUnderFrequency | 1.3.6.1.4.1.318.0.650 | ||||||||||||||||||||
notification SEVERE: UnderFrequency condition violated. The first argument is the serial number. The second argument is the product name. The third argument is an integer representing the source: 0=A, 1=B. | |||||||||||||||||||||
| !atsRMSUnderFrequencyCleared | 1.3.6.1.4.1.318.0.651 | ||||||||||||||||||||
notification INFORMATIONAL: UnderFrequency condition cleared. The first argument is the serial number. The second argument is the product name. The third argument is an integer representing the source: 0=A, 1=B. | |||||||||||||||||||||
| !isxModularDistributionCommLost | 1.3.6.1.4.1.318.0.652 | ||||||||||||||||||||
notification SEVERE: Communication with a metering segment of the modular distribution system has been lost. The first argument is the host device serial number. The second argument is the host device name. The third argument is the segment number. The fourth argument describes the modules served by this metering segment. | |||||||||||||||||||||
| !isxModularDistributionCommEstablished | 1.3.6.1.4.1.318.0.653 | ||||||||||||||||||||
notification INFORMATIONAL: Communication with a metering segment of the modular distribution system has been restored. The first argument is the host device serial number. The second argument is the host device name. The third argument is the segment number. The fourth argument describes the modules served by this metering segment. | |||||||||||||||||||||
| !isxModularDistributionModuleInserted | 1.3.6.1.4.1.318.0.654 | ||||||||||||||||||||
notification INFORMATIONAL: A distribution module has been inserted into the system. The first argument is the host device serial number. The second argument is the host device name. The third argument is the module location number. | |||||||||||||||||||||
| !isxModularDistributionModuleRemoved | 1.3.6.1.4.1.318.0.655 | ||||||||||||||||||||
notification INFORMATIONAL: A distribution module has been removed from the system. The first argument is the host device serial number. The second argument is the host device name. The third argument is the module location number. | |||||||||||||||||||||
| !isxModularBreakerOpenAlarm | 1.3.6.1.4.1.318.0.656 | ||||||||||||||||||||
notification SEVERE: A distribution module breaker is open and in an alarm condition. The first argument is the host device serial number. The second argument is the host device name. The third argument is the module number. The fourth argument is the module breaker(s) (1=L1, 2=L2, 3=L3, 4=L12, 5=L23, 6=L123). The fifth argument is the load name associated with the circuit/cable fed by this breaker. | |||||||||||||||||||||
| !isxModularBreakerOpenAlarmCleared | 1.3.6.1.4.1.318.0.657 | ||||||||||||||||||||
notification INFORMATIONAL: An alarm caused by a distribution breaker being open has been cleared. The first argument is the host device serial number. The second argument is the host device name. The third argument is the module number. The fourth argument is the breaker(s) (1=L1, 2=L2, 3=L3, 4=L12, 5=L23, 6=L123). The fifth argument is the load name associated with the circuit/cable fed by this breaker. | |||||||||||||||||||||
| !isxModularMinCurrentThresholdViolation | 1.3.6.1.4.1.318.0.658 | ||||||||||||||||||||
notification SEVERE: The current in a distribution module is below the minimum/critical limit specified for the circuit/cable. The first argument is the host device serial number. The second argument is the host device name. The third argument is the module number. The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3). The fifth argument is the threshold, in tenths of Amps, from which the alarm was generated. The sixth argument is the load name associated with the circuit/cable fed by this breaker. | |||||||||||||||||||||
| !isxModularMinCurrentThresholdViolationCleared | 1.3.6.1.4.1.318.0.659 | ||||||||||||||||||||
notification INFORMATIONAL: The current in a distribution module is no longer below the minimum/critical limit specified for the circuit/cable. The first argument is the host device serial number. The second argument is the host device name. The third argument is the module number. The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3). The fifth argument is the load name associated with the circuit/cable fed by this breaker. | |||||||||||||||||||||
| !isxModularLowCurrentThresholdViolation | 1.3.6.1.4.1.318.0.660 | ||||||||||||||||||||
notification WARNING: The current in a distribution module is below the low/warning limit specified for the circuit/cable. The first argument is the host device serial number. The second argument is the host device name. The third argument is the module number. The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3). The fifth argument is the threshold, in tenths of Amps, from which the alarm was generated. The sixth argument is the load name associated with the circuit/cable fed by this breaker. | |||||||||||||||||||||
| !isxModularLowCurrentThresholdViolationCleared | 1.3.6.1.4.1.318.0.661 | ||||||||||||||||||||
notification INFORMATIONAL: The current in a distribution module is no longer below the low/warning limit specified for the circuit/cable. The first argument is the host device serial number. The second argument is the host device name. The third argument is the module number. The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3). The fifth argument is the load name associated with the circuit/cable fed by this breaker. | |||||||||||||||||||||
| !isxModularHighCurrentThresholdViolation | 1.3.6.1.4.1.318.0.662 | ||||||||||||||||||||
notification WARNING: The current in a distribution module is above the high/warning limit specified for the circuit/cable. The first argument is the host device serial number. The second argument is the host device name. The third argument is the module number. The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3). The fifth argument is the threshold, in tenths of Amps, from which the alarm was generated. The sixth argument is the load name associated with the circuit/cable fed by this breaker. | |||||||||||||||||||||
| !isxModularHighCurrentThresholdViolationCleared | 1.3.6.1.4.1.318.0.663 | ||||||||||||||||||||
notification INFORMATIONAL: The current in a distribution module is no longer above the high/warning limit specified for the circuit/cable. The first argument is the host device serial number. The second argument is the host device name. The third argument is the module number. The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3). The fifth argument is the load name associated with the circuit/cable fed by this breaker. | |||||||||||||||||||||
| !isxModularMaxCurrentThresholdViolation | 1.3.6.1.4.1.318.0.664 | ||||||||||||||||||||
notification SEVERE: The current in a distribution module is above the maximum/critical limit specified for the circuit/cable. The first argument is the host device serial number. The second argument is the host device name. The third argument is the module number. The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3). The fifth argument is the threshold, in tenths of Amps, from which the alarm was generated. The sixth argument is the load name associated with the circuit/cable fed by this breaker. | |||||||||||||||||||||
| !isxModularMaxCurrentThresholdViolationCleared | 1.3.6.1.4.1.318.0.665 | ||||||||||||||||||||
notification INFORMATIONAL: The current in a distribution module is no longer above the maximum/critical limit specified for the circuit/cable. The first argument is the host device serial number. The second argument is the host device name. The third argument is the module number. The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3). The fifth argument is the load name associated with the circuit/cable fed by this breaker. | |||||||||||||||||||||
| !isxModularSubfeedBreakerOpenAlarm | 1.3.6.1.4.1.318.0.666 | ||||||||||||||||||||
notification SEVERE: A distribution subfeed breaker is open and in an alarm condition. The first argument is the host device serial number. The second argument is the host device name. The third argument is the subfeed number. The fourth argument is the load name associated with the subfeed. | |||||||||||||||||||||
| !isxModularSubfeedBreakerOpenAlarmCleared | 1.3.6.1.4.1.318.0.667 | ||||||||||||||||||||
notification INFORMATIONAL: An alarm caused by a distribution subfeed breaker being open has been cleared. The first argument is the host device serial number. The second argument is the host device name. The third argument is the subfeed number. The fourth argument is the load name associated with the subfeed. | |||||||||||||||||||||
| !isxModularSubfeedMinCurrentThresholdViolation | 1.3.6.1.4.1.318.0.668 | ||||||||||||||||||||
notification SEVERE: The current in a distribution subfeed is below the minimum/critical limit specified. The first argument is the host device serial number. The second argument is the host device name. The third argument is the subfeed number. The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3). The fifth argument is the threshold, in tenths of Amps, from which the alarm was generated. The sixth argument is the load name associated with the subfeed. | |||||||||||||||||||||
| !isxModularSubfeedMinCurrentThresholdViolationCleared | 1.3.6.1.4.1.318.0.669 | ||||||||||||||||||||
notification INFORMATIONAL: The current in a distribution subfeed is no longer below the minimum/critical limit specified. The first argument is the host device serial number. The second argument is the host device name. The third argument is the subfeed number. The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3). The fifth argument is the load name associated with the subfeed. | |||||||||||||||||||||
| !isxModularSubfeedLowCurrentThresholdViolation | 1.3.6.1.4.1.318.0.670 | ||||||||||||||||||||
notification WARNING: The current in a distribution subfeed is below the low/warning limit specified. The first argument is the host device serial number. The second argument is the host device name. The third argument is the subfeed number. The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3). The fifth argument is the threshold, in tenths of Amps, from which the alarm was generated. The sixth argument is the load name associated with the subfeed. | |||||||||||||||||||||
| !isxModularSubfeedLowCurrentThresholdViolationCleared | 1.3.6.1.4.1.318.0.671 | ||||||||||||||||||||
notification INFORMATIONAL: The current in a distribution subfeed is no longer below the low/warning limit specified. The first argument is the host device serial number. The second argument is the host device name. The third argument is the subfeed number. The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3). The fifth argument is the load name associated with the subfeed. | |||||||||||||||||||||
| !isxModularSubfeedHighCurrentThresholdViolation | 1.3.6.1.4.1.318.0.672 | ||||||||||||||||||||
notification WARNING: The current in a distribution subfeed is above the high/warning limit specified. The first argument is the host device serial number. The second argument is the host device name. The third argument is the subfeed number. The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3). The fifth argument is the threshold, in tenths of Amps, from which the alarm was generated. The sixth argument is the load name associated with the subfeed. | |||||||||||||||||||||
| !isxModularSubfeedHighCurrentThresholdViolationCleared | 1.3.6.1.4.1.318.0.673 | ||||||||||||||||||||
notification INFORMATIONAL: The current in a distribution subfeed is no longer above the high/warning limit specified. The first argument is the host device serial number. The second argument is the host device name. The third argument is the subfeed number. The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3). The fifth argument is the load name associated with the subfeed. | |||||||||||||||||||||
| !isxModularSubfeedMaxCurrentThresholdViolation | 1.3.6.1.4.1.318.0.674 | ||||||||||||||||||||
notification SEVERE: The current in a distribution subfeed is above the maximum/critical limit specified. The first argument is the host device serial number. The second argument is the host device name. The third argument is the subfeed number. The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3). The fifth argument is the threshold, in tenths of Amps, from which the alarm was generated. The sixth argument is the load name associated with the subfeed. | |||||||||||||||||||||
| !isxModularSubfeedMaxCurrentThresholdViolationCleared | 1.3.6.1.4.1.318.0.675 | ||||||||||||||||||||
notification INFORMATIONAL: The current in a distribution subfeed is no longer above the maximum/critical limit specified. The first argument is the host device serial number. The second argument is the host device name. The third argument is the subfeed number. The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3). The fifth argument is the load name associated with the subfeed. | |||||||||||||||||||||
| !isxModularTotalOutputCurrentMinThresholdViolation | 1.3.6.1.4.1.318.0.676 | ||||||||||||||||||||
notification SEVERE: The total output current of the distribution is below the minimum/critical limit specified. The first argument is the host device serial number. The second argument is the host device name. The third argument is the phase index (1=L1, 2=L2, 3=L3). The fourth argument is the threshold, in tenths of Amps, from which the alarm was generated. | |||||||||||||||||||||
| !isxModularTotalOutputCurrentMinThresholdViolationCleared | 1.3.6.1.4.1.318.0.677 | ||||||||||||||||||||
notification INFORMATIONAL: The total output current of the distribution is no longer below the minimum/critical limit specified. The first argument is the host device serial number. The second argument is the host device name. The third argument is the phase index (1=L1, 2=L2, 3=L3). | |||||||||||||||||||||
| !isxModularTotalOutputCurrentLowThresholdViolation | 1.3.6.1.4.1.318.0.678 | ||||||||||||||||||||
notification WARNING: The total output current of the distribution is below the low/warning limit specified. The first argument is the host device serial number. The second argument is the host device name. The third argument is the phase index (1=L1, 2=L2, 3=L3). The fourth argument is the threshold, in tenths of Amps, from which the alarm was generated. | |||||||||||||||||||||
| !isxModularTotalOutputCurrentLowThresholdViolationCleared | 1.3.6.1.4.1.318.0.679 | ||||||||||||||||||||
notification INFORMATIONAL: The total output current of the distribution is no longer below the low/warning limit specified. The first argument is the host device serial number. The second argument is the host device name. The third argument is the phase index (1=L1, 2=L2, 3=L3). | |||||||||||||||||||||
| !isxModularTotalOutputCurrentHighThresholdViolation | 1.3.6.1.4.1.318.0.680 | ||||||||||||||||||||
notification WARNING: The total output current of the distribution is above the high/warning limit specified. The first argument is the host device serial number. The second argument is the host device name. The third argument is the phase index (1=L1, 2=L2, 3=L3). The fourth argument is the threshold, in tenths of Amps, from which the alarm was generated. | |||||||||||||||||||||
| !isxModularTotalOutputCurrentHighThresholdViolationCleared | 1.3.6.1.4.1.318.0.681 | ||||||||||||||||||||
notification INFORMATIONAL: The total output current of the distribution is no longer above the high/warning limit specified. The first argument is the host device serial number. The second argument is the host device name. The third argument is the phase index (1=L1, 2=L2, 3=L3). | |||||||||||||||||||||
| !isxModularTotalOutputCurrentMaxThresholdViolation | 1.3.6.1.4.1.318.0.682 | ||||||||||||||||||||
notification SEVERE: The total output current of the distribution is above the maximum/critical limit specified. The first argument is the host device serial number. The second argument is the host device name. The third argument is the phase index (1=L1, 2=L2, 3=L3). The fourth argument is the threshold, in tenths of Amps, from which the alarm was generated. | |||||||||||||||||||||
| !isxModularTotalOutputCurrentMaxThresholdViolationCleared | 1.3.6.1.4.1.318.0.683 | ||||||||||||||||||||
notification INFORMATIONAL: The total output current of the distribution is no longer above the maximum/critical limit specified. The first argument is the host device serial number. The second argument is the host device name. The third argument is the phase index (1=L1, 2=L2, 3=L3). | |||||||||||||||||||||
| !isxModularOutputVoltageMinThresholdViolation | 1.3.6.1.4.1.318.0.684 | ||||||||||||||||||||
notification SEVERE: The distribution output voltage is below the minimum/critical limit specified. The first argument is the host device serial number. The second argument is the host device name. The third argument is the phase index (1=L1, 2=L2, 3=L3). The fourth argument is the threshold, in tenths of Volts, from which the alarm was generated. | |||||||||||||||||||||
| !isxModularOutputVoltageMinThresholdViolationCleared | 1.3.6.1.4.1.318.0.685 | ||||||||||||||||||||
notification INFORMATIONAL: The distribution output voltage is no longer below the minimum/critical limit specified. The first argument is the host device serial number. The second argument is the host device name. The third argument is the phase index (1=L1, 2=L2, 3=L3). | |||||||||||||||||||||
| !isxModularOutputVoltageLowThresholdViolation | 1.3.6.1.4.1.318.0.686 | ||||||||||||||||||||
notification WARNING: The distribution output voltage is below the low/warning limit specified. The first argument is the host device serial number. The second argument is the host device name. The third argument is the phase index (1=L1, 2=L2, 3=L3). The fourth argument is the threshold, in tenths of Volts, from which the alarm was generated. | |||||||||||||||||||||
| !isxModularOutputVoltageLowThresholdViolationCleared | 1.3.6.1.4.1.318.0.687 | ||||||||||||||||||||
notification INFORMATIONAL: The distribution output voltage is no longer below the low/warning limit specified. The first argument is the host device serial number. The second argument is the host device name. The third argument is the phase index (1=L1, 2=L2, 3=L3). | |||||||||||||||||||||
| !isxModularOutputVoltageHighThresholdViolation | 1.3.6.1.4.1.318.0.688 | ||||||||||||||||||||
notification WARNING: The distribution output voltage is above the high/warning limit specified. The first argument is the host device serial number. The second argument is the host device name. The third argument is the phase index (1=L1, 2=L2, 3=L3). The fourth argument is the threshold, in tenths of Volts, from which the alarm was generated. | |||||||||||||||||||||
| !isxModularOutputVoltageHighThresholdViolationCleared | 1.3.6.1.4.1.318.0.689 | ||||||||||||||||||||
notification INFORMATIONAL: The distribution output voltage is no longer above the high/warning limit specified. The first argument is the host device serial number. The second argument is the host device name. The third argument is the phase index (1=L1, 2=L2, 3=L3). | |||||||||||||||||||||
| !isxModularOutputVoltageMaxThresholdViolation | 1.3.6.1.4.1.318.0.690 | ||||||||||||||||||||
notification SEVERE: The distribution output voltage is above the maximum/critical limit specified. The first argument is the host device serial number. The second argument is the host device name. The third argument is the phase index (1=L1, 2=L2, 3=L3). The fourth argument is the threshold, in tenths of Volts, from which the alarm was generated. | |||||||||||||||||||||
| !isxModularOutputVoltageMaxThresholdViolationCleared | 1.3.6.1.4.1.318.0.691 | ||||||||||||||||||||
notification INFORMATIONAL: The distribution output voltage is no longer above the maximum/critical limit specified. The first argument is the host device serial number. The second argument is the host device name. The third argument is the phase index (1=L1, 2=L2, 3=L3). | |||||||||||||||||||||
| !apcDoorClosedImproperly | 1.3.6.1.4.1.318.0.692 | ||||||||||||||||||||
notification SEVERE: A door has been closed improperly. The first argument is the host device serial number. The second argument is the host device name. The third argument is the host device location. The fourth argument is the door identifier, (1=front, 2=rear). | |||||||||||||||||||||
| !apcDoorClosedImproperlyCleared | 1.3.6.1.4.1.318.0.693 | ||||||||||||||||||||
notification INFORMATIONAL: A door is no longer closed improperly. The first argument is the host device serial number. The second argument is the host device name. The third argument is the host device location. The fourth argument is the door identifier, (1=front, 2=rear). | |||||||||||||||||||||
| !apcUserScheduleViolation | 1.3.6.1.4.1.318.0.694 | ||||||||||||||||||||
notification SEVERE: A user has had a door opened past the scheduled access period. The first argument is the host device serial number. The second argument is the host device name. The third argument is the host device location. The fourth argument is the door identifier, (1=front, 2=rear). | |||||||||||||||||||||
| !apcUserScheduleViolationCleared | 1.3.6.1.4.1.318.0.695 | ||||||||||||||||||||
notification INFORMATIONAL: User schedule violation has been cleared. The first argument is the host device serial number. The second argument is the host device name. The third argument is the host device location. The fourth argument is the door identifier, (1=front, 2=rear). | |||||||||||||||||||||
| !isxModularOutputFrequencyThresholdViolation | 1.3.6.1.4.1.318.0.696 | ||||||||||||||||||||
notification SEVERE: The distribution output frequency is outside of the operating range specified. The first argument is the host device serial number. The second argument is the host device name. The third argument is the threshold, in tenths of Hertz, from which the alarm was generated. | |||||||||||||||||||||
| !isxModularOutputFrequencyViolationCleared | 1.3.6.1.4.1.318.0.697 | ||||||||||||||||||||
notification INFORMATIONAL: The distribution output frequency is no longer out of range. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !atsSourceStatusFail | 1.3.6.1.4.1.318.0.698 | ||||||||||||||||||||
notification SEVERE: ATS Source failed. The first argument is the serial number. The second argument is the product name. The third argument is an integer representing the source: 0=A, 1=B. | |||||||||||||||||||||
| !atsSourceStatusOk | 1.3.6.1.4.1.318.0.699 | ||||||||||||||||||||
notification INFORMATIONAL: ATS Source OK. The first argument is the serial number. The second argument is the product name. The third argument is an integer representing the source: 0=A, 1=B. | |||||||||||||||||||||
| !atsHardwareStatusFail | 1.3.6.1.4.1.318.0.700 | ||||||||||||||||||||
notification SEVERE: ATS display board hardware failed. The first argument is the serial number. The second argument is the product name. The third argument is an integer representing the failed hardware: 0= Phase LEDs/Push-button hardware failure 1= Seven-segment display hardware failure. | |||||||||||||||||||||
| !atsHardwareStatusOk | 1.3.6.1.4.1.318.0.701 | ||||||||||||||||||||
notification INFORMATIONAL: ATS display board hardware ok. The first argument is the serial number. The second argument is the product name. The third argument is an integer representing the hardware: 0= Phase LEDs/Push-button hardware failure 1= Seven-segment display hardware failure. | |||||||||||||||||||||
| !atsControllerRestart | 1.3.6.1.4.1.318.0.702 | ||||||||||||||||||||
| !inputWarningError | 1.3.6.1.4.1.318.0.703 | ||||||||||||||||||||
notification WARNING: Input warning error has been detected. The first variable is the fault condition.
| |||||||||||||||||||||
| !inputOK | 1.3.6.1.4.1.318.0.704 | ||||||||||||||||||||
notification INFORMATIONAL: Input warning error has been cleared. The first variable is the fault condition.
| |||||||||||||||||||||
| !bypassWarningError | 1.3.6.1.4.1.318.0.705 | ||||||||||||||||||||
notification WARNING: Bypass warning error has been detected. The first variable is the fault condition.
| |||||||||||||||||||||
| !bypassOK | 1.3.6.1.4.1.318.0.706 | ||||||||||||||||||||
notification INFORMATIONAL: Bypass warning error has been cleared. The first variable is the fault condition.
| |||||||||||||||||||||
| !communicationWarningError | 1.3.6.1.4.1.318.0.707 | ||||||||||||||||||||
notification WARNING: Communication warning error has been detected. The first variable is the fault condition.
| |||||||||||||||||||||
| !communicationOK | 1.3.6.1.4.1.318.0.708 | ||||||||||||||||||||
notification INFORMATIONAL: Communication warning error has been cleared. The first variable is the fault condition.
| |||||||||||||||||||||
| !powerModuleSevereError | 1.3.6.1.4.1.318.0.709 | ||||||||||||||||||||
notification SEVERE: Power module severe error has been detected. The first variable is the fault condition.
| |||||||||||||||||||||
| !powerModuleOK | 1.3.6.1.4.1.318.0.710 | ||||||||||||||||||||
notification INFORMATIONAL: Power module severe error has been cleared. The first variable is the fault condition.
| |||||||||||||||||||||
| !outputVoltageWaveformError | 1.3.6.1.4.1.318.0.711 | ||||||||||||||||||||
| !outputVoltageWaveformOK | 1.3.6.1.4.1.318.0.712 | ||||||||||||||||||||
| !bypassStaticSwitchOverload | 1.3.6.1.4.1.318.0.713 | ||||||||||||||||||||
| !noOverloadOnBypassStaticSwitch | 1.3.6.1.4.1.318.0.714 | ||||||||||||||||||||
notification INFORMATIONAL: Overload on static bypass switch no longer present.
| |||||||||||||||||||||
| !batteryVoltageCollapse | 1.3.6.1.4.1.318.0.715 | ||||||||||||||||||||
| !batteryVoltageOK | 1.3.6.1.4.1.318.0.716 | ||||||||||||||||||||
| !overloadOnInstallation | 1.3.6.1.4.1.318.0.717 | ||||||||||||||||||||
| !noOverloadOnInstallation | 1.3.6.1.4.1.318.0.718 | ||||||||||||||||||||
| !bypassStaticSwitchError | 1.3.6.1.4.1.318.0.719 | ||||||||||||||||||||
| !bypassStaticSwitchOK | 1.3.6.1.4.1.318.0.720 | ||||||||||||||||||||
| !forcedBypassSwitchActivated | 1.3.6.1.4.1.318.0.721 | ||||||||||||||||||||
| !forcedBypassSwitchReleased | 1.3.6.1.4.1.318.0.722 | ||||||||||||||||||||
| !epoActivated | 1.3.6.1.4.1.318.0.723 | ||||||||||||||||||||
| !xATSS1BadPhaseRotation | 1.3.6.1.4.1.318.0.724 | ||||||||||||||||||||
notification SEVERE: The device's source 1 phase rotation is bad. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !xATSS1BadPhaseRotationCleared | 1.3.6.1.4.1.318.0.725 | ||||||||||||||||||||
notification INFORMATIONAL: The device's source 1 phase rotation is back to normal. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !xATSS1BadPhaseBalance | 1.3.6.1.4.1.318.0.726 | ||||||||||||||||||||
notification SEVERE: The device's source 1 phase balance is out of bounds. The first argument is the host device serial number. The second argument is the host device name. The third argument is the minimum phase balance as a percentage. | |||||||||||||||||||||
| !xATSS1BadPhaseBalanceCleared | 1.3.6.1.4.1.318.0.727 | ||||||||||||||||||||
notification INFORMATIONAL: The device's source 1 phase balance is back to normal. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !isxModularTransformerOverheating | 1.3.6.1.4.1.318.0.728 | ||||||||||||||||||||
notification SEVERE: The distribution transformer temperature is too hot. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !isxModularTransformerOverheatingCleared | 1.3.6.1.4.1.318.0.729 | ||||||||||||||||||||
notification INFORMATIONAL: The distribution transformer temperature has returned to normal. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !apcInternalCommunicationFault | 1.3.6.1.4.1.318.0.730 | ||||||||||||||||||||
| !apcInternalCommunicationFaultCleared | 1.3.6.1.4.1.318.0.731 | ||||||||||||||||||||
notification INFORMATIONAL: An internal UPS communication fault no longer exists.
| |||||||||||||||||||||
| !upsOutletGroupCommand | 1.3.6.1.4.1.318.0.732 | ||||||||||||||||||||
notification WARNING: The specified Outlet Group command has been issued. | |||||||||||||||||||||
| !onbatterycommunicationLost | 1.3.6.1.4.1.318.0.733 | ||||||||||||||||||||
notification SEVERE: Communication to the UPS when the UPS is on Battery. Steps to reestablish communication are in progress.
| |||||||||||||||||||||
| !upsCriticalCondition | 1.3.6.1.4.1.318.0.734 | ||||||||||||||||||||
notification SEVERE: A UPS critical condition was detected. The first variable is the error condition text message. The second variable is the error number. | |||||||||||||||||||||
| !upsCriticalConditionCleared | 1.3.6.1.4.1.318.0.735 | ||||||||||||||||||||
notification INFORMATIONAL: A UPS critical condition has been cleared. The first variable is the fault condition. | |||||||||||||||||||||
| !upsWarningCondition | 1.3.6.1.4.1.318.0.736 | ||||||||||||||||||||
notification WARNING: A UPS warning condition has been detected. The first variable is the fault condition. | |||||||||||||||||||||
| !upsWarningConditionCleared | 1.3.6.1.4.1.318.0.737 | ||||||||||||||||||||
notification WARNING: A UPS warning condition has been cleared. The first variable is the fault condition. | |||||||||||||||||||||
| !upsInformationalCondition | 1.3.6.1.4.1.318.0.738 | ||||||||||||||||||||
notification INFORMATIONAL: A UPS informational condition has been detected. The first variable is the fault condition. | |||||||||||||||||||||
| !upsInformationalConditionCleared | 1.3.6.1.4.1.318.0.739 | ||||||||||||||||||||
notification INFORMATIONAL: A UPS informational condition has been cleared. The first variable is the fault condition. | |||||||||||||||||||||
| !isxcInformationalAlarm | 1.3.6.1.4.1.318.0.740 | ||||||||||||||||||||
notification INFORMATIONAL: An ISXC Alarm exists. The first argument is the unique ISXC alarm ID. The second argument is the ISXC alarm label as a UTF8 string. The third argument is the ISXC alarm code. The fourth argument is the unique ISXC device ID. The fifth argument is the ISXC device label as a UTF8 string. The sixth argument is the ISXC parent host. The seventh argument is the ISXC device type as a UTF8 string. The eighth argument is the device serial number. The ninth argument is the device model number. The tenth argument is the device host. The eleventh argument is the device location as a UTF8 string. The twelfth argument is the device contact as a UTF8 string. The thirteenth argument is the unique ISXC sensor ID. The fourteenth argument is the ISXC sensor label as a UTF8 string. The fifteenth argument is the sensor value as a UTF8 string. The sixteenth argument is the ISXC alarm start time. The seventeenth argument is the ISXC alarm resolution time. The eighteenth argument is the description as a UTF8 string.
| |||||||||||||||||||||
| !isxcInformationalAlarmCleared | 1.3.6.1.4.1.318.0.741 | ||||||||||||||||||||
notification INFORMATIONAL: An ISXC Alarm has been cleared. The first argument is the unique ISXC alarm ID. The second argument is the ISXC alarm label as a UTF8 string. The third argument is the ISXC alarm code. The fourth argument is the unique ISXC device ID. The fifth argument is the ISXC device label as a UTF8 string. The sixth argument is the ISXC parent host. The seventh argument is the ISXC device type as a UTF8 string. The eighth argument is the device serial number. The ninth argument is the device model number. The tenth argument is the device host. The eleventh argument is the device location as a UTF8 string. The twelfth argument is the device contact as a UTF8 string. The thirteenth argument is the unique ISXC sensor ID. The fourteenth argument is the ISXC sensor label as a UTF8 string. The fifteenth argument is the sensor value as a UTF8 string. The sixteenth argument is the ISXC alarm start time. The seventeenth argument is the ISXC alarm resolution time. The eighteenth argument is the description as a UTF8 string.
| |||||||||||||||||||||
| !isxcWarningAlarm | 1.3.6.1.4.1.318.0.742 | ||||||||||||||||||||
notification WARNING: An ISXC Alarm exists. The first argument is the unique ISXC alarm ID. The second argument is the ISXC alarm label as a UTF8 string. The third argument is the ISXC alarm code. The fourth argument is the unique ISXC device ID. The fifth argument is the ISXC device label as a UTF8 string. The sixth argument is the ISXC parent host. The seventh argument is the ISXC device type as a UTF8 string. The eighth argument is the device serial number. The ninth argument is the device model number. The tenth argument is the device host. The eleventh argument is the device location as a UTF8 string. The twelfth argument is the device contact as a UTF8 string. The thirteenth argument is the unique ISXC sensor ID. The fourteenth argument is the ISXC sensor label as a UTF8 string. The fifteenth argument is the sensor value as a UTF8 string. The sixteenth argument is the ISXC alarm start time. The seventeenth argument is the ISXC alarm resolution time. The eighteenth argument is the description as a UTF8 string.
| |||||||||||||||||||||
| !isxcWarningAlarmCleared | 1.3.6.1.4.1.318.0.743 | ||||||||||||||||||||
notification WARNING: An ISXC Alarm has been cleared. The first argument is the unique ISXC alarm ID. The second argument is the ISXC alarm label as a UTF8 string. The third argument is the ISXC alarm code. The fourth argument is the unique ISXC device ID. The fifth argument is the ISXC device label as a UTF8 string. The sixth argument is the ISXC parent host. The seventh argument is the ISXC device type as a UTF8 string. The eighth argument is the device serial number. The ninth argument is the device model number. The tenth argument is the device host. The eleventh argument is the device location as a UTF8 string. The twelfth argument is the device contact as a UTF8 string. The thirteenth argument is the unique ISXC sensor ID. The fourteenth argument is the ISXC sensor label as a UTF8 string. The fifteenth argument is the sensor value as a UTF8 string. The sixteenth argument is the ISXC alarm start time. The seventeenth argument is the ISXC alarm resolution time. The eighteenth argument is the description as a UTF8 string.
| |||||||||||||||||||||
| !isxcErrorAlarm | 1.3.6.1.4.1.318.0.744 | ||||||||||||||||||||
notification ERROR: An ISXC Alarm exists. The first argument is the unique ISXC alarm ID. The second argument is the ISXC alarm label as a UTF8 string. The third argument is the ISXC alarm code. The fourth argument is the unique ISXC device ID. The fifth argument is the ISXC device label as a UTF8 string. The sixth argument is the ISXC parent host. The seventh argument is the ISXC device type as a UTF8 string. The eighth argument is the device serial number. The ninth argument is the device model number. The tenth argument is the device host. The eleventh argument is the device location as a UTF8 string. The twelfth argument is the device contact as a UTF8 string. The thirteenth argument is the unique ISXC sensor ID. The fourteenth argument is the ISXC sensor label as a UTF8 string. The fifteenth argument is the sensor value as a UTF8 string. The sixteenth argument is the ISXC alarm start time. The seventeenth argument is the ISXC alarm resolution time. The eighteenth argument is the description as a UTF8 string.
| |||||||||||||||||||||
| !isxcErrorAlarmCleared | 1.3.6.1.4.1.318.0.745 | ||||||||||||||||||||
notification ERROR: An ISXC Alarm has been cleared. The first argument is the unique ISXC alarm ID. The second argument is the ISXC alarm label as a UTF8 string. The third argument is the ISXC alarm code. The fourth argument is the unique ISXC device ID. The fifth argument is the ISXC device label as a UTF8 string. The sixth argument is the ISXC parent host. The seventh argument is the ISXC device type as a UTF8 string. The eighth argument is the device serial number. The ninth argument is the device model number. The tenth argument is the device host. The eleventh argument is the device location as a UTF8 string. The twelfth argument is the device contact as a UTF8 string. The thirteenth argument is the unique ISXC sensor ID. The fourteenth argument is the ISXC sensor label as a UTF8 string. The fifteenth argument is the sensor value as a UTF8 string. The sixteenth argument is the ISXC alarm start time. The seventeenth argument is the ISXC alarm resolution time. The eighteenth argument is the description as a UTF8 string.
| |||||||||||||||||||||
| !isxcCriticalAlarm | 1.3.6.1.4.1.318.0.746 | ||||||||||||||||||||
notification CRITICAL: An ISXC Alarm exists. The first argument is the unique ISXC alarm ID. The second argument is the ISXC alarm label as a UTF8 string. The third argument is the ISXC alarm code. The fourth argument is the unique ISXC device ID. The fifth argument is the ISXC device label as a UTF8 string. The sixth argument is the ISXC parent host. The seventh argument is the ISXC device type as a UTF8 string. The eighth argument is the device serial number. The ninth argument is the device model number. The tenth argument is the device host. The eleventh argument is the device location as a UTF8 string. The twelfth argument is the device contact as a UTF8 string. The thirteenth argument is the unique ISXC sensor ID. The fourteenth argument is the ISXC sensor label as a UTF8 string. The fifteenth argument is the sensor value as a UTF8 string. The sixteenth argument is the ISXC alarm start time. The seventeenth argument is the ISXC alarm resolution time. The eighteenth argument is the description as a UTF8 string.
| |||||||||||||||||||||
| !isxcCriticalAlarmCleared | 1.3.6.1.4.1.318.0.747 | ||||||||||||||||||||
notification CRITICAL: An ISXC Alarm has been cleared. The first argument is the unique ISXC alarm ID. The second argument is the ISXC alarm label as a UTF8 string. The third argument is the ISXC alarm code. The fourth argument is the unique ISXC device ID. The fifth argument is the ISXC device label as a UTF8 string. The sixth argument is the ISXC parent host. The seventh argument is the ISXC device type as a UTF8 string. The eighth argument is the device serial number. The ninth argument is the device model number. The tenth argument is the device host. The eleventh argument is the device location as a UTF8 string. The twelfth argument is the device contact as a UTF8 string. The thirteenth argument is the unique ISXC sensor ID. The fourteenth argument is the ISXC sensor label as a UTF8 string. The fifteenth argument is the sensor value as a UTF8 string. The sixteenth argument is the ISXC alarm start time. The seventeenth argument is the ISXC alarm resolution time. The eighteenth argument is the description as a UTF8 string.
| |||||||||||||||||||||
| !isxcFailureAlarm | 1.3.6.1.4.1.318.0.748 | ||||||||||||||||||||
notification FAILURE: An ISXC Alarm exists. The first argument is the unique ISXC alarm ID. The second argument is the ISXC alarm label as a UTF8 string. The third argument is the ISXC alarm code. The fourth argument is the unique ISXC device ID. The fifth argument is the ISXC device label as a UTF8 string. The sixth argument is the ISXC parent host. The seventh argument is the ISXC device type as a UTF8 string. The eighth argument is the device serial number. The ninth argument is the device model number. The tenth argument is the device host. The eleventh argument is the device location as a UTF8 string. The twelfth argument is the device contact as a UTF8 string. The thirteenth argument is the unique ISXC sensor ID. The fourteenth argument is the ISXC sensor label as a UTF8 string. The fifteenth argument is the sensor value as a UTF8 string. The sixteenth argument is the ISXC alarm start time. The seventeenth argument is the ISXC alarm resolution time. The eighteenth argument is the description as a UTF8 string.
| |||||||||||||||||||||
| !isxcFailureAlarmCleared | 1.3.6.1.4.1.318.0.749 | ||||||||||||||||||||
notification FAILURE: An ISXC Alarm has been cleared. The first argument is the unique ISXC alarm ID. The second argument is the ISXC alarm label as a UTF8 string. The third argument is the ISXC alarm code. The fourth argument is the unique ISXC device ID. The fifth argument is the ISXC device label as a UTF8 string. The sixth argument is the ISXC parent host. The seventh argument is the ISXC device type as a UTF8 string. The eighth argument is the device serial number. The ninth argument is the device model number. The tenth argument is the device host. The eleventh argument is the device location as a UTF8 string. The twelfth argument is the device contact as a UTF8 string. The thirteenth argument is the unique ISXC sensor ID. The fourteenth argument is the ISXC sensor label as a UTF8 string. The fifteenth argument is the sensor value as a UTF8 string. The sixteenth argument is the ISXC alarm start time. The seventeenth argument is the ISXC alarm resolution time. The eighteenth argument is the description as a UTF8 string.
| |||||||||||||||||||||
| !rpduCriticalCondition | 1.3.6.1.4.1.318.0.750 | ||||||||||||||||||||
notification SEVERE: A RPDU critical condition has been detected. The first variable is the serial number. The second variable is the device name. The third variable is the error number. The fourth variable is the device number. The fifth variable is the instance number. The sixth variable is the trap text message. | |||||||||||||||||||||
| !rpduCriticalConditionCleared | 1.3.6.1.4.1.318.0.751 | ||||||||||||||||||||
notification INFORMATIONAL: A RPDU critical condition has been cleared. The first variable is the serial number. The second variable is the device name. The third variable is the error number. The fourth variable is the device number. The fifth variable is the instance number. The sixth variable is the trap text message. | |||||||||||||||||||||
| !rpduWarningCondition | 1.3.6.1.4.1.318.0.752 | ||||||||||||||||||||
notification WARNING: A RPDU warning condition has been detected. The first variable is the serial number. The second variable is the device name. The third variable is the error number. The fourth variable is the device number. The fifth variable is the instance number. The sixth variable is the trap text message. | |||||||||||||||||||||
| !rpduWarningConditionCleared | 1.3.6.1.4.1.318.0.753 | ||||||||||||||||||||
notification WARNING: A RPDU warning condition has been cleared. The first variable is the serial number. The second variable is the device name. The third variable is the error number. The fourth variable is the device number. The fifth variable is the instance number. The sixth variable is the trap text message. | |||||||||||||||||||||
| !rpduInformationalCondition | 1.3.6.1.4.1.318.0.754 | ||||||||||||||||||||
notification INFORMATIONAL: A RPDU informational condition has been detected. The first variable is the serial number. The second variable is the device name. The third variable is the error number. The fourth variable is the device number. The fifth variable is the instance number. The sixth variable is the trap text message. | |||||||||||||||||||||
| !rpduInformationalConditionCleared | 1.3.6.1.4.1.318.0.755 | ||||||||||||||||||||
notification INFORMATIONAL: A RPDU informational condition has been cleared. The first variable is the serial number. The second variable is the device name. The third variable is the error number. The fourth variable is the device number. The fifth variable is the instance number. The sixth variable is the trap text message. | |||||||||||||||||||||
| !isxModularCoolingFanAlarm | 1.3.6.1.4.1.318.0.756 | ||||||||||||||||||||
notification SEVERE: The device's internal cooling fans have failed. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !isxModularCoolingFanAlarmCleared | 1.3.6.1.4.1.318.0.757 | ||||||||||||||||||||
notification INFORMATIONAL: The device's internal cooling fans are now functioning properly. The first argument is the host device serial number. The second argument is the host device name. | |||||||||||||||||||||
| !upsFirmwareUpdateStarted | 1.3.6.1.4.1.318.0.758 | ||||||||||||||||||||
| !upsFirmwareUpdateFinished | 1.3.6.1.4.1.318.0.759 | ||||||||||||||||||||
| !upsFirmwareUpdateSucceeded | 1.3.6.1.4.1.318.0.760 | ||||||||||||||||||||
| !upsFirmwareUpdateFailed | 1.3.6.1.4.1.318.0.761 | ||||||||||||||||||||
| !upsHasNoValidFirmware | 1.3.6.1.4.1.318.0.762 | ||||||||||||||||||||
| !upsHasNoValidFirmwareCleared | 1.3.6.1.4.1.318.0.763 | ||||||||||||||||||||
| !upsLocalDisplayButtonFault | 1.3.6.1.4.1.318.0.767 | ||||||||||||||||||||
| !upsLocalDisplayButtonFaultCleared | 1.3.6.1.4.1.318.0.768 | ||||||||||||||||||||
| !upsNeedsFactorySetupFault | 1.3.6.1.4.1.318.0.769 | ||||||||||||||||||||
| !upsNeedsFactorySetupFaultCleared | 1.3.6.1.4.1.318.0.770 | ||||||||||||||||||||
| !upsEPOActive | 1.3.6.1.4.1.318.0.771 | ||||||||||||||||||||
| !upsEPOActiveCleared | 1.3.6.1.4.1.318.0.772 | ||||||||||||||||||||
| !upsFirmwareMismatch | 1.3.6.1.4.1.318.0.773 | ||||||||||||||||||||
| !upsFirmwareMismatchCleared | 1.3.6.1.4.1.318.0.774 | ||||||||||||||||||||
| !upsOscillatorFailed | 1.3.6.1.4.1.318.0.775 | ||||||||||||||||||||
| !upsOscillatorFailedCleared | 1.3.6.1.4.1.318.0.776 | ||||||||||||||||||||
| !upsOnBatteryDueToFault | 1.3.6.1.4.1.318.0.777 | ||||||||||||||||||||
notification SEVERE: The UPS is on battery due to an error. Symmetra UPS devices: Intelligence module has reported being in self-test for too long. When this happens, the UPS is not usually in self-test, but the batteries are draining slowly. If left uncorrected, the batteries will become depleted and the UPS will not be able to turn on. If the UPS has at least N+1 redundancy, check power modules one by one to determine which keeps the UPS in self-test. Once identified, replace the module.
| |||||||||||||||||||||
| !upsOnBatteryDueToFaultCleared | 1.3.6.1.4.1.318.0.778 | ||||||||||||||||||||
| !pcnsCriticalEventActive | 1.3.6.1.4.1.318.0.779 | ||||||||||||||||||||
notification SEVERE: PowerChute Network Shutdown has begun a safe shutdown of the host.
| |||||||||||||||||||||
| !pcnsCriticalEventResolved | 1.3.6.1.4.1.318.0.780 | ||||||||||||||||||||
notification INFORMATIONAL: PowerChute Network Shutdown critical event resolved. Safe shutdown will continue.
| |||||||||||||||||||||
| !pcnsNetworkComsLost | 1.3.6.1.4.1.318.0.781 | ||||||||||||||||||||
| !pcnsNetworkComsLostResolved | 1.3.6.1.4.1.318.0.782 | ||||||||||||||||||||
| !pcnsNMCComsLost | 1.3.6.1.4.1.318.0.783 | ||||||||||||||||||||
| !pcnsNMCComsLostResolved | 1.3.6.1.4.1.318.0.784 | ||||||||||||||||||||
| !pcnsTest | 1.3.6.1.4.1.318.0.785 | ||||||||||||||||||||
| !pcnsUpdateAvailable | 1.3.6.1.4.1.318.0.786 | ||||||||||||||||||||
notification INFORMATIONAL: PowerChute has detected that a newer version is available.
| |||||||||||||||||||||
| !temporaryBypass | 1.3.6.1.4.1.318.0.787 | ||||||||||||||||||||
| !pcbeCriticalEventActive | 1.3.6.1.4.1.318.0.790 | ||||||||||||||||||||
notification SEVERE: PowerChute Business Edition has begun a safe shutdown of the host.
| |||||||||||||||||||||
| !pcbeCriticalEventResolved | 1.3.6.1.4.1.318.0.791 | ||||||||||||||||||||
notification INFORMATIONAL: PowerChute Business Edition critical event resolved. Safe shutdown will continue.
| |||||||||||||||||||||
| !pcbeComsLost | 1.3.6.1.4.1.318.0.792 | ||||||||||||||||||||
| !pcbeComsLostResolved | 1.3.6.1.4.1.318.0.793 | ||||||||||||||||||||
| !pcbeTest | 1.3.6.1.4.1.318.0.794 | ||||||||||||||||||||
| !pcbeUpdateAvailable | 1.3.6.1.4.1.318.0.795 | ||||||||||||||||||||
notification INFORMATIONAL: PowerChute has detected that a newer version is available.
| |||||||||||||||||||||
| !pmmCriticalCondition | 1.3.6.1.4.1.318.0.796 | ||||||||||||||||||||
notification SEVERE: A PMM critical condition has been detected. The first variable is the serial number. The second variable is the device name. The third variable is the event ID. The fourth variable is the instance number. The fifth variable is the trap text message. | |||||||||||||||||||||
| !pmmCriticalConditionCleared | 1.3.6.1.4.1.318.0.797 | ||||||||||||||||||||
notification INFORMATIONAL: A PMM critical condition has been cleared. The first variable is the serial number. The second variable is the device name. The third variable is the event ID. The fourth variable is the instance number. The fifth variable is the trap text message. | |||||||||||||||||||||
| !pmmWarningCondition | 1.3.6.1.4.1.318.0.798 | ||||||||||||||||||||
notification WARNING: A PMM warning condition has been detected. The first variable is the serial number. The second variable is the device name. The third variable is the event ID. The fourth variable is the instance number. The fifth variable is the trap text message. | |||||||||||||||||||||
| !pmmWarningConditionCleared | 1.3.6.1.4.1.318.0.799 | ||||||||||||||||||||
notification WARNING: A PMM warning condition has been cleared. The first variable is the serial number. The second variable is the device name. The third variable is the event ID. The fourth variable is the instance number. The fifth variable is the trap text message. | |||||||||||||||||||||
| !pmmInformationalCondition | 1.3.6.1.4.1.318.0.800 | ||||||||||||||||||||
notification INFORMATIONAL: A PMM informational condition has been detected. The first variable is the serial number. The second variable is the device name. The third variable is the event ID. The fourth variable is the instance number. The fifth variable is the trap text message. | |||||||||||||||||||||
| !pmmInformationalConditionCleared | 1.3.6.1.4.1.318.0.801 | ||||||||||||||||||||
notification INFORMATIONAL: A PMM informational condition has been cleared. The first variable is the serial number. The second variable is the device name. The third variable is the event ID. The fourth variable is the instance number. The fifth variable is the trap text message. | |||||||||||||||||||||
| !upsInputContactOutputRelayFault | 1.3.6.1.4.1.318.0.802 | ||||||||||||||||||||
notification SEVERE: A fault exists in the UPS input contact / output relay hardware.
| |||||||||||||||||||||
| !upsInputContactOutputRelayFaultCleared | 1.3.6.1.4.1.318.0.803 | ||||||||||||||||||||
notification INFORMATIONAL: Fault no longer exists in the UPS input contact / output relay hardware.
| |||||||||||||||||||||
| !upsAirFilterWarning | 1.3.6.1.4.1.318.0.804 | ||||||||||||||||||||
| !upsAirFilterWarningCleared | 1.3.6.1.4.1.318.0.805 | ||||||||||||||||||||
| !upsBatteryPackIncompatible | 1.3.6.1.4.1.318.0.806 | ||||||||||||||||||||
| !upsBatteryPackIncompatibleCleared | 1.3.6.1.4.1.318.0.807 | ||||||||||||||||||||
| !upsInputContactAbnormal | 1.3.6.1.4.1.318.0.808 | ||||||||||||||||||||
| !upsInputContactAbnormalCleared | 1.3.6.1.4.1.318.0.809 | ||||||||||||||||||||
notification INFORMATIONAL: UPS input contact has returned to its normal state.
| |||||||||||||||||||||
| !upsOutputRelayAbnormal | 1.3.6.1.4.1.318.0.810 | ||||||||||||||||||||
| !upsOutputRelayAbnormalCleared | 1.3.6.1.4.1.318.0.811 | ||||||||||||||||||||
notification INFORMATIONAL: A UPS output relay has returned to its normal state.
| |||||||||||||||||||||
| !ePDUCriticalCondition | 1.3.6.1.4.1.318.0.812 | ||||||||||||||||||||
| !ePDUCriticalConditionCleared | 1.3.6.1.4.1.318.0.813 | ||||||||||||||||||||
| !ePDUWarningCondition | 1.3.6.1.4.1.318.0.814 | ||||||||||||||||||||
| !ePDUWarningConditionCleared | 1.3.6.1.4.1.318.0.815 | ||||||||||||||||||||
| !upsBreakerQ2Open | 1.3.6.1.4.1.318.0.822 | ||||||||||||||||||||
| !upsBreakerQ2Closed | 1.3.6.1.4.1.318.0.823 | ||||||||||||||||||||
| !bypassPowerSupplyFailureCleared | 1.3.6.1.4.1.318.0.824 | ||||||||||||||||||||
notification INFORMATIONAL: Base module bypass power supply needs repair condition has been cleared
| |||||||||||||||||||||
| !atsCriticalCondition | 1.3.6.1.4.1.318.0.825 | ||||||||||||||||||||
notification SEVERE: A ATS critical condition has been detected. The first variable is the serial number. The second variable is the device name. The third variable is the event ID. The fourth variable is the instance number. The fifth variable is the trap text message. | |||||||||||||||||||||
| !atsCriticalConditionCleared | 1.3.6.1.4.1.318.0.826 | ||||||||||||||||||||
notification INFORMATIONAL: A ATS critical condition has been cleared. The first variable is the serial number. The second variable is the device name. The third variable is the event ID. The fourth variable is the instance number. The fifth variable is the trap text message. | |||||||||||||||||||||
| !atsWarningCondition | 1.3.6.1.4.1.318.0.827 | ||||||||||||||||||||
notification WARNING: A ATS warning condition has been detected. The first variable is the serial number. The second variable is the device name. The third variable is the event ID. The fourth variable is the instance number. The fifth variable is the trap text message. | |||||||||||||||||||||
| !atsWarningConditionCleared | 1.3.6.1.4.1.318.0.828 | ||||||||||||||||||||
notification WARNING: A ATS warning condition has been cleared. The first variable is the serial number. The second variable is the device name. The third variable is the event ID. The fourth variable is the instance number. The fifth variable is the trap text message. | |||||||||||||||||||||
| !atsInformationalCondition | 1.3.6.1.4.1.318.0.829 | ||||||||||||||||||||
notification INFORMATIONAL: A ATS informational condition has been detected. The first variable is the serial number. The second variable is the device name. The third variable is the event ID. The fourth variable is the instance number. The fifth variable is the trap text message. | |||||||||||||||||||||
| !atsInformationalConditionCleared | 1.3.6.1.4.1.318.0.830 | ||||||||||||||||||||
notification INFORMATIONAL: A ATS informational condition has been cleared. The first variable is the serial number. The second variable is the device name. The third variable is the event ID. The fourth variable is the instance number. The fifth variable is the trap text message. | |||||||||||||||||||||
| !uioFluidDetected | 1.3.6.1.4.1.318.0.831 | ||||||||||||||||||||
notification SEVERE: Fluid detected by the UIO's fluid sensor. The first argument is the number of the fluid sensor. The second argument is the name of the fluid sensor. | |||||||||||||||||||||
| !uioFluidDetectedCleared | 1.3.6.1.4.1.318.0.832 | ||||||||||||||||||||
notification INFORMATIONAL: Fluid no longer detected by the UIO's fluid sensor. The first argument is the number of the fluid sensor. The second argument is the name of the fluid sensor. | |||||||||||||||||||||
| Nproducts | 1.3.6.1.4.1.318.1 | ||||||||||||||||||||
| Nhardware | 1.3.6.1.4.1.318.1.1 | ||||||||||||||||||||
| Nups | 1.3.6.1.4.1.318.1.1.1 | ||||||||||||||||||||
| NupsIdent | 1.3.6.1.4.1.318.1.1.1.1 | ||||||||||||||||||||
| NupsBasicIdent | 1.3.6.1.4.1.318.1.1.1.1.1 | ||||||||||||||||||||
| SupsBasicIdentModel | 1.3.6.1.4.1.318.1.1.1.1.1.1 | DisplayString | RO | mandatory | Smart-UPS 1000 | ||||||||||||||||
scalar · DisplayString · read-only · mandatory The UPS model name (e.g. 'APC Smart-UPS 600'). Example values from LibreNMS test devices
| |||||||||||||||||||||
| SupsBasicIdentName | 1.3.6.1.4.1.318.1.1.1.1.1.2 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory An 8 byte ID string identifying the UPS. This object can be set by the administrator. For GVS, GPX and GVL products, this string can be up to 32 bytes. | |||||||||||||||||||||
| SupsBasicIdentFamilyName | 1.3.6.1.4.1.318.1.1.1.1.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The UPS model family name for the product. | |||||||||||||||||||||
| SupsBasicIdentModelType | 1.3.6.1.4.1.318.1.1.1.1.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The detailed model information of the system. | |||||||||||||||||||||
| NupsAdvIdent | 1.3.6.1.4.1.318.1.1.1.1.2 | ||||||||||||||||||||
| SupsAdvIdentFirmwareRevision | 1.3.6.1.4.1.318.1.1.1.1.2.1 | DisplayString | RO | mandatory | UPS 08.3 / MCU 14.0 (18 - 10) | ||||||||||||||||
scalar · DisplayString · read-only · mandatory The firmware revision of the UPS system's microprocessor. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SupsAdvIdentDateOfManufacture | 1.3.6.1.4.1.318.1.1.1.1.2.2 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The date when the UPS was manufactured in mm/dd/yy (or yyyy) format. | |||||||||||||||||||||
| SupsAdvIdentSerialNumber | 1.3.6.1.4.1.318.1.1.1.1.2.3 | DisplayString | RO | mandatory | AS1322126155 | ||||||||||||||||
scalar · DisplayString · read-only · mandatory An 8-character string (between 12 and 15 characters in case of 3 phase UPS) identifying the serial number of the UPS internal microprocessor. This number is set at the factory. NOTE: This number does NOT correspond to the serial number on the rear of the UPS. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SupsAdvIdentFirmwareRevision2 | 1.3.6.1.4.1.318.1.1.1.1.2.4 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The firmware revision of a UPS system co-microprocessor. | |||||||||||||||||||||
| SupsAdvIdentSkuNumber | 1.3.6.1.4.1.318.1.1.1.1.2.5 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The SKU number of a UPS system. | |||||||||||||||||||||
| SupsAdvIdentHardwareRevision | 1.3.6.1.4.1.318.1.1.1.1.2.6 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The hardware revision of a UPS system. | |||||||||||||||||||||
| SupsAdvIdentUpsPhaseConfigType | 1.3.6.1.4.1.318.1.1.1.1.2.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The type definition, based on phase configuration. 1 - Unknown 2 - 3 phase in/out 3 - 1 phase in/out 4 - 3 phase in/1 phase out
| |||||||||||||||||||||
| SupsAdvEnergyStorageType | 1.3.6.1.4.1.318.1.1.1.1.2.8 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The energy storage type connected to the UPS. It states battery type and battery chemistry. 1 - Unknown 2 - VRLA or wet cells 3 - NiCd batteries 4 - Lithium-ion batteries 5 - No energy storage 6 - Flywheel 7 - Ultracaps
| |||||||||||||||||||||
| SupsAdvIdentApparentPowerRating | 1.3.6.1.4.1.318.1.1.1.1.2.9 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The apparent power rating of the UPS in Volt-Amps. | |||||||||||||||||||||
| NupsBattery | 1.3.6.1.4.1.318.1.1.1.2 | ||||||||||||||||||||
| NupsBasicBattery | 1.3.6.1.4.1.318.1.1.1.2.1 | ||||||||||||||||||||
| SupsBasicBatteryStatus | 1.3.6.1.4.1.318.1.1.1.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The status of the UPS batteries. A batteryLow(3) value indicates the UPS will be unable to sustain the current load, and its services will be lost if power is not restored. The amount of run time in reserve at the time of low battery can be configured by the upsAdvConfigLowBatteryRunTime OID. A batteryInFaultCondition(4)value indicates that a battery installed has an internal error condition. noBatteryPresent(5) indicate that no battery is present (no battery, battery breaker open, etc)to perform the battery diagnostic test
| |||||||||||||||||||||
| SupsBasicBatteryTimeOnBattery | 1.3.6.1.4.1.318.1.1.1.2.1.2 | TimeTicks | RO | mandatory | |||||||||||||||||
scalar · TimeTicks · read-only · mandatory The elapsed time since the UPS has switched to battery power. | |||||||||||||||||||||
| SupsBasicBatteryLastReplaceDate | 1.3.6.1.4.1.318.1.1.1.2.1.3 | DisplayString | RW | mandatory | 04/30/25 | ||||||||||||||||
scalar · DisplayString · read-write · mandatory The date when the UPS system's batteries were last replaced in mm/dd/yy (or yyyy) format. For Smart-UPS models, this value is originally set in the factory. When the UPS batteries are replaced, this value should be reset by the administrator. For Symmetra PX 250/500, this OID is read only and is configurable in the local display only. For Gutor modular, the format is YYYY-MM-DD.If not defined return 2000-01-01. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NupsAdvBattery | 1.3.6.1.4.1.318.1.1.1.2.2 | ||||||||||||||||||||
| SupsAdvBatteryCapacity | 1.3.6.1.4.1.318.1.1.1.2.2.1 | Gauge | RO | mandatory | 100 | ||||||||||||||||
scalar · Gauge · read-only · mandatory The remaining battery capacity expressed in percent of full capacity. If not supported, return 0. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SupsAdvBatteryTemperature | 1.3.6.1.4.1.318.1.1.1.2.2.2 | Gauge | RO | mandatory | 21 | ||||||||||||||||
scalar · Gauge · read-only · mandatory The current internal UPS temperature expressed in Celsius. Temperatures below zero read as 0. Consider using upsHighPrecExtdBatteryTemperature instead. If not present return maximum temperature value(255). Example values from LibreNMS test devices
| |||||||||||||||||||||
| SupsAdvBatteryRunTimeRemaining | 1.3.6.1.4.1.318.1.1.1.2.2.3 | TimeTicks | RO | mandatory | 756000 (0d 2h 6m 0s) | ||||||||||||||||
scalar · TimeTicks · read-only · mandatory The UPS battery run time remaining before battery exhaustion. If not present return maximum value(4,294,967,295). Example values from LibreNMS test devices
| |||||||||||||||||||||
| SupsAdvBatteryReplaceIndicator | 1.3.6.1.4.1.318.1.1.1.2.2.4 | INTEGER | RO | mandatory | noBatteryNeedsReplacing(1) | ||||||||||||||||
scalar · INTEGER · read-only · mandatory Indicates whether the UPS batteries need replacing.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SupsAdvBatteryNumOfBattPacks | 1.3.6.1.4.1.318.1.1.1.2.2.5 | INTEGER | RO | mandatory | 3 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of external battery packs connected to the UPS. If the UPS does not use smart cells then the agent reports ERROR_NO_SUCH_NAME. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SupsAdvBatteryNumOfBadBattPacks | 1.3.6.1.4.1.318.1.1.1.2.2.6 | INTEGER | RO | mandatory | -1 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of external battery packs connected to the UPS that are defective. If the UPS does not use smart cells then the agent reports ERROR_NO_SUCH_NAME. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SupsAdvBatteryNominalVoltage | 1.3.6.1.4.1.318.1.1.1.2.2.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The nominal battery voltage in Volts. | |||||||||||||||||||||
| SupsAdvBatteryActualVoltage | 1.3.6.1.4.1.318.1.1.1.2.2.8 | INTEGER | RO | mandatory | 27 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The actual battery bus voltage in Volts. If not supported, return -1. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SupsAdvBatteryCurrent | 1.3.6.1.4.1.318.1.1.1.2.2.9 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The battery current in Amps. If not supported, return -1. | |||||||||||||||||||||
| SupsAdvTotalDCCurrent | 1.3.6.1.4.1.318.1.1.1.2.2.10 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The total DC current in Amps. | |||||||||||||||||||||
| SupsAdvBatteryFullCapacity | 1.3.6.1.4.1.318.1.1.1.2.2.11 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The full chargeable capacity of the battery which is expressed in percentage. | |||||||||||||||||||||
| TupsAdvBatteryActualVoltageTable | 1.3.6.1.4.1.318.1.1.1.2.2.12 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of battery table entries. The number of battery frames present in UPS. | |||||||||||||||||||||
| RupsAdvBatteryActualVoltageEntry | 1.3.6.1.4.1.318.1.1.1.2.2.12.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory Information applicable to each of the Battery frames. | |||||||||||||||||||||
| CupsAdvBatteryActualVoltageTableIndex | 1.3.6.1.4.1.318.1.1.1.2.2.12.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The Battery Frame identifier. Battery Frame index. | |||||||||||||||||||||
| CupsAdvBatteryActualVoltagePolarity | 1.3.6.1.4.1.318.1.1.1.2.2.12.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The selected Battery Voltage Polarity. 0 indicates positive polarity. 1 indicates negative polarity.
| |||||||||||||||||||||
| CupsAdvBatteryFrameActualVoltage | 1.3.6.1.4.1.318.1.1.1.2.2.12.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The actual battery bus voltage in Volts. | |||||||||||||||||||||
| TupsAdvTotalDCCurrentTable | 1.3.6.1.4.1.318.1.1.1.2.2.13 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of Battery Frame table entries. The number of entries is given by the value of Number of Battery Frames. | |||||||||||||||||||||
| RupsAdvTotalDCCurrentEntry | 1.3.6.1.4.1.318.1.1.1.2.2.13.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular Battery Frame. | |||||||||||||||||||||
| CupsAdvTotalDCCurrentTableIndex | 1.3.6.1.4.1.318.1.1.1.2.2.13.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The Battery Frame identifier. Total DC Current Table Index. | |||||||||||||||||||||
| CupsAdvTotalDCCurrentPolarity | 1.3.6.1.4.1.318.1.1.1.2.2.13.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The selected Battery Current Polarity. 0 indicates positive polarity. 1 indicates negative polarity.
| |||||||||||||||||||||
| CupsAdvTotalFrameDCCurrent | 1.3.6.1.4.1.318.1.1.1.2.2.13.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The Total DC Current of battery in Amperes. | |||||||||||||||||||||
| TupsAdvBatteryCurrentTable | 1.3.6.1.4.1.318.1.1.1.2.2.14 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of Battery Frame table entries. The number of entries is given by number of Battery frames present. | |||||||||||||||||||||
| RupsAdvBatteryCurrentEntry | 1.3.6.1.4.1.318.1.1.1.2.2.14.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular battery frame. | |||||||||||||||||||||
| CupsAdvBatteryCurrentTableIndex | 1.3.6.1.4.1.318.1.1.1.2.2.14.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The Battery Frame identifier. Battery Current Table Index. | |||||||||||||||||||||
| CupsAdvBatteryCurrentIndex | 1.3.6.1.4.1.318.1.1.1.2.2.14.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The battery frame identifier. | |||||||||||||||||||||
| CupsAdvBatteryCurrentPolarity | 1.3.6.1.4.1.318.1.1.1.2.2.14.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The selected Battery current polarity. 0 indicates positive polarity. 1 indicates negative polarity
| |||||||||||||||||||||
| CupsAdvBatteryFrameCurrent | 1.3.6.1.4.1.318.1.1.1.2.2.14.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The Battery current measured in Amperes | |||||||||||||||||||||
| SupsAdvBatteryEstimatedChargeTime | 1.3.6.1.4.1.318.1.1.1.2.2.15 | TimeTicks | RO | mandatory | |||||||||||||||||
scalar · TimeTicks · read-only · mandatory The estimated remaining time required to charge the UPS to a full state of charge. If not present return maximum value(4,294,967,295). | |||||||||||||||||||||
| SupsAdvBatteryPower | 1.3.6.1.4.1.318.1.1.1.2.2.16 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The measured battery power in kW. | |||||||||||||||||||||
| SupsAdvBatteryChargerStatus | 1.3.6.1.4.1.318.1.1.1.2.2.17 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The status of the battery charger. If the UPS is unable to find the state of charger, this variable is set to unknown(1).
| |||||||||||||||||||||
| SupsAdvBatteryInternalSKU | 1.3.6.1.4.1.318.1.1.1.2.2.19 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The SKU of the internal battery. | |||||||||||||||||||||
| SupsAdvBatteryExternalSKU | 1.3.6.1.4.1.318.1.1.1.2.2.20 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The SKU of the external battery. | |||||||||||||||||||||
| SupsAdvBatteryRecommendedReplaceDate | 1.3.6.1.4.1.318.1.1.1.2.2.21 | DisplayString | RO | mandatory | 11/10/2027 | ||||||||||||||||
scalar · DisplayString · read-only · mandatory The recommended replacement date for the battery based on the UPS internal battery life algorithm. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SupsAdvBatteryNominalBackupTime | 1.3.6.1.4.1.318.1.1.1.2.2.22 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Defines the runtime of the user supplied battery in minutes, when battery is new. | |||||||||||||||||||||
| SupsAdvBatteryCondition | 1.3.6.1.4.1.318.1.1.1.2.2.23 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Health of the battries based on the battery test.
| |||||||||||||||||||||
| SupsAdvBatteryChargingCurrentRestricted | 1.3.6.1.4.1.318.1.1.1.2.2.24 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Indicates whether battery charging current is restricted or not. The value of yes(1) indicates that battery charging current is restricted . The value of no(2) indicates that battery charging current is not restricted.
| |||||||||||||||||||||
| SupsAdvBatteryTotalCapacity | 1.3.6.1.4.1.318.1.1.1.2.2.25 | Gauge | RO | mandatory | |||||||||||||||||
scalar · Gauge · read-only · mandatory The actual available battery capacity of the system expressed in ampere hours (Ah). The value is updated continuously, for example when battery breakers are opened or closed, or when battery strings/battery blocks are added or removed. | |||||||||||||||||||||
| SupsAdvBatteryFuseStatus | 1.3.6.1.4.1.318.1.1.1.2.2.26 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory If battery system has one common fuse for the battery system, the status is given by this value. 1 = Fuse Open 2 = Fuse Ok 3 = Not present
| |||||||||||||||||||||
| SupsAdvBatteryBreakerStatus | 1.3.6.1.4.1.318.1.1.1.2.2.27 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The value indicates the aggregated status of the battery breakers in the system. disconnected(1) indicates none of the battery breakers are closed, and the battery system is disconnected closed(2) indicates at least one of the battery breakers in the system is closed notPresent(3) if not present
| |||||||||||||||||||||
| SupsAdvBatteryWiringConfiguration | 1.3.6.1.4.1.318.1.1.1.2.2.28 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The value indicates the wiring configuration, whether the battery is 2-wire or 3-wire. If it's a 3-wire battery system, the system can have 2 voltages and currents per cabinet. 1 = 2-wire (a non-split battery) 2 = 3-wire (a split battery)
| |||||||||||||||||||||
| NupsHighPrecBattery | 1.3.6.1.4.1.318.1.1.1.2.3 | ||||||||||||||||||||
| SupsHighPrecBatteryCapacity | 1.3.6.1.4.1.318.1.1.1.2.3.1 | Gauge | RO | mandatory | 1000 | ||||||||||||||||
scalar · Gauge · read-only · mandatory The remaining battery capacity expressed in tenths of percent of full capacity. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SupsHighPrecBatteryTemperature | 1.3.6.1.4.1.318.1.1.1.2.3.2 | Gauge | RO | mandatory | 300 | ||||||||||||||||
scalar · Gauge · read-only · mandatory The current internal UPS temperature expressed in tenths of degrees Celsius. Temperatures below zero read as 0. Consider using upsHighPrecExtdBatteryTemperature instead. If not present, return maximum temperature value(255). Example values from LibreNMS test devices
| |||||||||||||||||||||
| SupsHighPrecBatteryNominalVoltage | 1.3.6.1.4.1.318.1.1.1.2.3.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The nominal battery voltage in tenths of Volts. | |||||||||||||||||||||
| SupsHighPrecBatteryActualVoltage | 1.3.6.1.4.1.318.1.1.1.2.3.4 | INTEGER | RO | mandatory | 270 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The actual battery bus voltage in tenths of Volts. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SupsHighPrecBatteryCurrent | 1.3.6.1.4.1.318.1.1.1.2.3.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The battery current in tenths of Amps. If not supported, return -1. | |||||||||||||||||||||
| SupsHighPrecTotalDCCurrent | 1.3.6.1.4.1.318.1.1.1.2.3.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The total DC current in tenths of Amps. | |||||||||||||||||||||
| TupsHighPrecBatteryActualVoltageTable | 1.3.6.1.4.1.318.1.1.1.2.3.7 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of Battery frame table entries. The number of entries is given by the number of Battery frames. | |||||||||||||||||||||
| RupsHighPrecBatteryActualVoltageEntry | 1.3.6.1.4.1.318.1.1.1.2.3.7.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular battery frame. | |||||||||||||||||||||
| CupsHighPrecBatteryActualVoltageTableIndex | 1.3.6.1.4.1.318.1.1.1.2.3.7.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The Battery Frame identifier. High Precision Actual Voltage Table Index. | |||||||||||||||||||||
| CupsHighPrecBatteryActualVoltagePolarity | 1.3.6.1.4.1.318.1.1.1.2.3.7.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The selected Battery Voltage polarity. 0 indicates positive polarity. 1 indicates negative polarity.
| |||||||||||||||||||||
| CupsHighPrecBatteryVoltage | 1.3.6.1.4.1.318.1.1.1.2.3.7.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The actual battery bus voltage expressed as tenths of Volts. If not supported, return -1. | |||||||||||||||||||||
| TupsHighPrecTotalDCCurrentTable | 1.3.6.1.4.1.318.1.1.1.2.3.8 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of Battery Frame table entries. The number of entries is given by the number of battery frames. | |||||||||||||||||||||
| RupsHighPrecTotalDCCurrentEntry | 1.3.6.1.4.1.318.1.1.1.2.3.8.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular battery frame. | |||||||||||||||||||||
| CupsHighPrecTotalDCCurrentTableIndex | 1.3.6.1.4.1.318.1.1.1.2.3.8.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The Battery Frame identifier. High precision Total DC Current index. | |||||||||||||||||||||
| CupsHighPrecTotalDCCurrentPolarity | 1.3.6.1.4.1.318.1.1.1.2.3.8.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The selected Battery Current polarity. 0 indicates positive polarity. 1 indicates negative polarity.
| |||||||||||||||||||||
| CupsHighPrecTotalDCFrameCurrent | 1.3.6.1.4.1.318.1.1.1.2.3.8.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The total DC current in tenths of Amperes. | |||||||||||||||||||||
| TupsHighPrecBatteryCurrentTable | 1.3.6.1.4.1.318.1.1.1.2.3.9 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of Battery Frame table entries. The number of entries is given by the number of battery frames. | |||||||||||||||||||||
| RupsHighPrecBatteryCurrentEntry | 1.3.6.1.4.1.318.1.1.1.2.3.9.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular battery frame. | |||||||||||||||||||||
| CupsHighPrecBatteryCurrentTableIndex | 1.3.6.1.4.1.318.1.1.1.2.3.9.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The Battery frame identifier. Battery Frame index. | |||||||||||||||||||||
| CupsHighPrecBatteryCurrentIndex | 1.3.6.1.4.1.318.1.1.1.2.3.9.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The Battery frame identifier. Battery Index for each frame. | |||||||||||||||||||||
| CupsHighPrecBatteryCurrentPolarity | 1.3.6.1.4.1.318.1.1.1.2.3.9.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The selected Battery Current polarity. 0 indicates positive polarity. 1 indicates negative polarity.
| |||||||||||||||||||||
| CupsHighPrecBatteryFrameCurrent | 1.3.6.1.4.1.318.1.1.1.2.3.9.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The Battery current in tenths of Amperes. | |||||||||||||||||||||
| NupsHighPrecBatteryPacks | 1.3.6.1.4.1.318.1.1.1.2.3.10 | ||||||||||||||||||||
| SupsHighPrecBatteryPackTableSize | 1.3.6.1.4.1.318.1.1.1.2.3.10.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the upsHighPrecBatteryPacks. | |||||||||||||||||||||
| TupsHighPrecBatteryPackTable | 1.3.6.1.4.1.318.1.1.1.2.3.10.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of Battery Pack table entries. The number of entries is given by number of Battery Packs present. | |||||||||||||||||||||
| RupsHighPrecBatteryPackEntry | 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular battery pack. | |||||||||||||||||||||
| CupsHighPrecBatteryPackIndex | 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The battery pack identifier. | |||||||||||||||||||||
| CupsHighPrecBatteryCartridgeIndex | 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The battery cartridge identifier. | |||||||||||||||||||||
| CupsHighPrecBatteryPackFirmwareRevision | 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The battery pack firmware revision. | |||||||||||||||||||||
| CupsHighPrecBatteryPackSerialNumber | 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The battery pack serial number. | |||||||||||||||||||||
| CupsHighPrecBatteryPackTemperature | 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The battery pack temperature measured in 10ths of degree Celcius | |||||||||||||||||||||
| CupsHighPrecBatteryPackStatus | 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.6 | OCTET STRING | RO | mandatory | |||||||||||||||||
column · OCTET STRING · read-only · mandatory The battery status for the pack only. bit 0 Disconnected bit 1 Overvoltage bit 2 NeedsReplacement bit 3 OvertemperatureCritical bit 4 Charger bit 5 TemperatureSensor bit 6 BusSoftStart bit 7 OvertemperatureWarning bit 8 GeneralError bit 9 Communication bit 10 DisconnectedFrame bit 11 FirmwareMismatch | |||||||||||||||||||||
| CupsHighPrecBatteryPackCartridgeHealth | 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.7 | OCTET STRING | RO | mandatory | |||||||||||||||||
column · OCTET STRING · read-only · mandatory The battery cartridge health. bit 0 Battery lifetime okay bit 1 Battery lifetime near end, order replacement cartridge bit 2 Battery lifetime exceeded, replace battery bit 3 Battery lifetime near end acknowledged, order replacement cartridge bit 4 Battery lifetime exceeded acknowledged, replace battery bit 5 Battery measured lifetime near end, order replacement cartridge bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge | |||||||||||||||||||||
| CupsHighPrecBatteryPackCartridgeReplaceDate | 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.8 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The battery cartridge estimated battery replace date. | |||||||||||||||||||||
| CupsHighPrecBatteryPackCartridgeInstallDate | 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.9 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The battery cartridge install date. | |||||||||||||||||||||
| CupsHighPrecBatteryPackCartridgeStatus | 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.10 | OCTET STRING | RO | mandatory | |||||||||||||||||
column · OCTET STRING · read-only · mandatory The battery cartridge status. bit 0 Disconnected bit 1 Overvoltage bit 2 NeedsReplacement bit 3 OvertemperatureCritical bit 4 Charger bit 5 TemperatureSensor bit 6 BusSoftStart bit 7 OvertemperatureWarning bit 8 GeneralError bit 9 Communication bit 10 DisconnectedFrame bit 11 FirmwareMismatch | |||||||||||||||||||||
| SupsHighPrecBatteryPackOnlyTableSize | 1.3.6.1.4.1.318.1.1.1.2.3.10.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the upsHighPrecBatteryPacks. | |||||||||||||||||||||
| TupsHighPrecBatteryPackOnlyTable | 1.3.6.1.4.1.318.1.1.1.2.3.10.4 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of Battery Pack table entries. The number of entries is given by number of Battery Packs present. | |||||||||||||||||||||
| RupsHighPrecBatteryPackOnlyEntry | 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular battery pack. | |||||||||||||||||||||
| CupsHighPrecBatteryPackOnlyIndex | 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The battery pack identifier. | |||||||||||||||||||||
| CupsHighPrecBatteryPackOnlyFirmwareRevision | 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The battery pack firmware revision. | |||||||||||||||||||||
| CupsHighPrecBatteryPackOnlySerialNumber | 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The battery pack serial number. | |||||||||||||||||||||
| CupsHighPrecBatteryPackOnlyTemperature | 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The battery pack temperature measured in 10ths of degree Celcius | |||||||||||||||||||||
| CupsHighPrecBatteryPackOnlyStatus | 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.5 | OCTET STRING | RO | mandatory | |||||||||||||||||
column · OCTET STRING · read-only · mandatory The battery status for the pack only. bit 0 Disconnected bit 1 Overvoltage bit 2 NeedsReplacement bit 3 OvertemperatureCritical bit 4 Charger bit 5 TemperatureSensor bit 6 BusSoftStart bit 7 OvertemperatureWarning bit 8 GeneralError bit 9 Communication bit 10 DisconnectedFrame bit 11 FirmwareMismatch bit 12 VoltageSenseError bit 13 IncompatiblePack | |||||||||||||||||||||
| CupsHighPrecBatteryPackOnlyHealth | 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.6 | OCTET STRING | RO | mandatory | |||||||||||||||||
column · OCTET STRING · read-only · mandatory The battery pack health. bit 0 Battery lifetime okay bit 1 Battery lifetime near end, order replacement pack bit 2 Battery lifetime exceeded, replace battery bit 3 Battery lifetime near end acknowledged, order replacement pack bit 4 Battery lifetime exceeded acknowledged, replace battery bit 5 Battery measured lifetime near end, order replacement pack bit 6 Battery measured lifetime near end acknowledged, order replacement pack | |||||||||||||||||||||
| CupsHighPrecBatteryPackOnlyReplaceDate | 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.7 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The battery pack estimated battery replace date. | |||||||||||||||||||||
| CupsHighPrecBatteryPackOnlyInstallDate | 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.8 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The battery pack install date. | |||||||||||||||||||||
| CupsHighPrecBatteryPackOnlyManufactureDate | 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.9 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The battery pack manufacture date. | |||||||||||||||||||||
| CupsHighPrecBatteryPackOnlySKU | 1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.10 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The battery pack SKU. | |||||||||||||||||||||
| SupsHighPrecBatteryHealth | 1.3.6.1.4.1.318.1.1.1.2.3.11 | OCTET STRING | RO | mandatory | |||||||||||||||||
scalar · OCTET STRING · read-only · mandatory The battery health.
Bit 0 Battery life okay
Bit 1 Battery life near end, order battery cartridge
Bit 2 Battery life exceeded, replace battery cartridge
Bit 3 Battery life near end acknowledged, order battery
cartridge
Bit 4 Battery life exceeded acknowledged, replace battery
cartridge
Bit 5 Battery measured life near end, order battery cartridge
Bit 6 Battery measured life near end acknowledged, order
battery cartridge | |||||||||||||||||||||
| SupsHighPrecActivePower | 1.3.6.1.4.1.318.1.1.1.2.3.12 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Active Power of Battery in tenths of kW | |||||||||||||||||||||
| SupsHighPrecExtdBatteryTemperature | 1.3.6.1.4.1.318.1.1.1.2.3.13 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The current internal UPS temperature expressed in tenths of degrees Celsius. Can be negative. | |||||||||||||||||||||
| SupsHighPrecMaximumModuleTemperature | 1.3.6.1.4.1.318.1.1.1.2.3.14 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The current maximum temperature across all battery modules in tenths of degrees Celsius. Can be negative. | |||||||||||||||||||||
| SupsHighPrecMinimumModuleTemperature | 1.3.6.1.4.1.318.1.1.1.2.3.15 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The current minimum temperature across all battery modules in tenths of degrees Celsius. Can be negative. | |||||||||||||||||||||
| SupsHighPrecMaximumCellVoltage | 1.3.6.1.4.1.318.1.1.1.2.3.16 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The current maximum cell voltage in mVDC across all batteries. | |||||||||||||||||||||
| SupsHighPrecMinimumCellVoltage | 1.3.6.1.4.1.318.1.1.1.2.3.17 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The current minimum cell voltage in mVDC across all batteries. | |||||||||||||||||||||
| SupsBatteryNumberOfCabinets | 1.3.6.1.4.1.318.1.1.1.2.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The value indicates the number of battery cabinets in total, internal and external. If the UPS only has internal batteries, that number should be 1. If the UPS has external and internal, the number is 1 + number of external cabinets. | |||||||||||||||||||||
| TupsBatteryCabinetTable | 1.3.6.1.4.1.318.1.1.1.2.5 | NA | optional | ||||||||||||||||||
table · not-accessible · optional Table of battery cabinets | |||||||||||||||||||||
| RupsBatteryCabinetEntry | 1.3.6.1.4.1.318.1.1.1.2.5.1 | NA | optional | ||||||||||||||||||
row · not-accessible · optional An entry containing information applicable to a particular battery cabinet. | |||||||||||||||||||||
| CupsBatteryCabinetIndex | 1.3.6.1.4.1.318.1.1.1.2.5.1.1 | INTEGER | RO | optional | |||||||||||||||||
column · INTEGER · read-only · optional The Battery Cabinet identifier. Battery Cabinet Table Index. | |||||||||||||||||||||
| CupsBatteryCabinetLocalIndex | 1.3.6.1.4.1.318.1.1.1.2.5.1.2 | INTEGER | RO | optional | |||||||||||||||||
column · INTEGER · read-only · optional The identification number for the actual battery cabinet in the system. 0 corresponds to the internal batteries 1 and higher corresponds to external battery cabinets | |||||||||||||||||||||
| CupsBatteryCabinetWiringConfiguration | 1.3.6.1.4.1.318.1.1.1.2.5.1.3 | INTEGER | RO | optional | |||||||||||||||||
column · INTEGER · read-only · optional The value indicates the wiring configuration, whether the battery is 2-wire or 3-wire. If it's a 3-wire battery system, the system can have two voltages and currents per cabinet. 1 = 2-wire (a non-split battery) 2 = 3-wire (a split battery)
| |||||||||||||||||||||
| CupsBatteryCabinetVoltagePolarity1 | 1.3.6.1.4.1.318.1.1.1.2.5.1.4 | INTEGER | RO | optional | |||||||||||||||||
column · INTEGER · read-only · optional The battery voltage. For a non-split battery, it is the full voltage. For a split battery, the value is the voltage for one side/half of the battery | |||||||||||||||||||||
| CupsBatteryCabinetVoltagePolarity2 | 1.3.6.1.4.1.318.1.1.1.2.5.1.5 | INTEGER | RO | optional | |||||||||||||||||
column · INTEGER · read-only · optional The voltage for the second side/half of the battery in a split battery system. If it is not a split battery, this reports -1 | |||||||||||||||||||||
| CupsBatteryCabinetCurrentPolarity1 | 1.3.6.1.4.1.318.1.1.1.2.5.1.6 | INTEGER | RO | optional | |||||||||||||||||
column · INTEGER · read-only · optional The battery current. For a non-split battery, it is the full current. For a split battery, the value is the current for one side/half of the battery | |||||||||||||||||||||
| CupsBatteryCabinetCurrentPolarity2 | 1.3.6.1.4.1.318.1.1.1.2.5.1.7 | INTEGER | RO | optional | |||||||||||||||||
column · INTEGER · read-only · optional The current for the second side/half of the battery in a split battery system. If it is not a split battery, this reports -1 | |||||||||||||||||||||
| CupsBatteryCabinetTemperature | 1.3.6.1.4.1.318.1.1.1.2.5.1.8 | INTEGER | RO | optional | |||||||||||||||||
column · INTEGER · read-only · optional The measured temperature of the battery cabinet in tenths of degrees Celcius | |||||||||||||||||||||
| CupsBatteryCabinetMaxTemperature | 1.3.6.1.4.1.318.1.1.1.2.5.1.9 | INTEGER | RO | optional | |||||||||||||||||
column · INTEGER · read-only · optional The highest temperature measured for the battery in the battery cabinet in tenths of degrees Celcius. If there are multiple sensors in the battery cabinet, it is the selected highest actual value of measured temperatures. If there is battery string information, it is the highest actual battery string temperature value. | |||||||||||||||||||||
| CupsBatteryCabinetMinTemperature | 1.3.6.1.4.1.318.1.1.1.2.5.1.10 | INTEGER | RO | optional | |||||||||||||||||
column · INTEGER · read-only · optional The lowest temperature measured for the battery in the battery cabinet in tenths of degrees Celcius. If there are multiple sensors in the battery cabinet, it is the selected lowest actual value of measured temperatures. If there is string information, it is the lowest actual battery string temperature value. | |||||||||||||||||||||
| CupsBatteryCabinetAverageTemperature | 1.3.6.1.4.1.318.1.1.1.2.5.1.11 | INTEGER | RO | optional | |||||||||||||||||
column · INTEGER · read-only · optional The average temperature for all the battery sensors in the battery cabinet and for the battery strings, if battery strings are present. Measured in tenths of degrees Celcius. | |||||||||||||||||||||
| CupsBatteryCabinetFuse | 1.3.6.1.4.1.318.1.1.1.2.5.1.12 | INTEGER | RO | optional | |||||||||||||||||
column · INTEGER · read-only · optional If the battery cabinet has a common fuse, the status is given by this value. 1 = Fuse open 2 = Fuse OK 3 = Not present
| |||||||||||||||||||||
| CupsBatteryCabinetBreaker | 1.3.6.1.4.1.318.1.1.1.2.5.1.13 | INTEGER | RO | optional | |||||||||||||||||
column · INTEGER · read-only · optional The value indicates the battery cabinet breaker status. Reports 1 if no breaker is present. 1 = No breaker 2 = Unknown 3 = Breaker open 4 = Breaker closed
| |||||||||||||||||||||
| CupsBatteryCabinetNumberOfStrings | 1.3.6.1.4.1.318.1.1.1.2.5.1.14 | INTEGER | RO | optional | |||||||||||||||||
column · INTEGER · read-only · optional The number of battery strings in the battery cabinet. The value can be 0, meaning that no additional information on the battery string is available. 1 and higher means data in the table is provided. | |||||||||||||||||||||
| CupsBatteryCabinetNumberOfVerticalPositions | 1.3.6.1.4.1.318.1.1.1.2.5.1.15 | INTEGER | RO | optional | |||||||||||||||||
column · INTEGER · read-only · optional The number of vertical levels or shelves for battery blocks/modules. The levels are indexed from the bottom up | |||||||||||||||||||||
| CupsBatteryCabinetNumberOfHorizontalPositions | 1.3.6.1.4.1.318.1.1.1.2.5.1.16 | INTEGER | RO | optional | |||||||||||||||||
column · INTEGER · read-only · optional The number of horizontal positions for battery blocks/modules. The levels are indexed from left to right | |||||||||||||||||||||
| TupsBatteryCabStringTable | 1.3.6.1.4.1.318.1.1.1.2.6 | NA | optional | ||||||||||||||||||
table · not-accessible · optional Table of battery strings in the complete battery solution | |||||||||||||||||||||
| RupsBatteryCabStringEntry | 1.3.6.1.4.1.318.1.1.1.2.6.1 | NA | optional | ||||||||||||||||||
row · not-accessible · optional An entry containing information applicable to a particular battery string in the battery cabinet. | |||||||||||||||||||||
| CupsBatteryCabStringIndex | 1.3.6.1.4.1.318.1.1.1.2.6.1.1 | INTEGER | RO | optional | |||||||||||||||||
column · INTEGER · read-only · optional The battery cabinet string identifier. Battery cabinet string or halfstring table index. | |||||||||||||||||||||
| CupsBatteryCabStringCabReference | 1.3.6.1.4.1.318.1.1.1.2.6.1.2 | INTEGER | RO | optional | |||||||||||||||||
column · INTEGER · read-only · optional Reference to the global battery cabinet index where the battery string is placed. | |||||||||||||||||||||
| CupsBatteryCabStringLocalIndex | 1.3.6.1.4.1.318.1.1.1.2.6.1.3 | INTEGER | RO | optional | |||||||||||||||||
column · INTEGER · read-only · optional Local battery string identification index in the actual battery cabinet (e.g. String 2 in cabinet) | |||||||||||||||||||||
| CupsBatteryCabStringCurrent | 1.3.6.1.4.1.318.1.1.1.2.6.1.4 | INTEGER | RO | optional | |||||||||||||||||
column · INTEGER · read-only · optional The current in a battery string or battery halfstring, in tenths of Amps. | |||||||||||||||||||||
| CupsBatteryCabStringAverageTemperature | 1.3.6.1.4.1.318.1.1.1.2.6.1.5 | INTEGER | RO | optional | |||||||||||||||||
column · INTEGER · read-only · optional Temperature of the battery string or the average of the aggregated temperature of each battery block/module (in tenths of degrees Celcius). If not available, this variable is set to (-1999). | |||||||||||||||||||||
| CupsBatteryCabStringMaxTemperature | 1.3.6.1.4.1.318.1.1.1.2.6.1.6 | INTEGER | RO | optional | |||||||||||||||||
column · INTEGER · read-only · optional The actual highest battery temperature measurement for the battery blocks/modules (in tenths of degrees Celcius). | |||||||||||||||||||||
| CupsBatteryCabStringMinTemperature | 1.3.6.1.4.1.318.1.1.1.2.6.1.7 | INTEGER | RO | optional | |||||||||||||||||
column · INTEGER · read-only · optional The actual lowest battery temperature measurement for the battery blocks/modules (in tenths of degrees Celcius). | |||||||||||||||||||||
| CupsBatteryCabStringFuseStatus | 1.3.6.1.4.1.318.1.1.1.2.6.1.8 | INTEGER | RO | optional | |||||||||||||||||
column · INTEGER · read-only · optional If the battery string has a common fuse, the status is given by this value. 1 = Fuse open 2 = Fuse OK 3 = Not present
| |||||||||||||||||||||
| CupsBatteryCabStringNumberOfBlocks | 1.3.6.1.4.1.318.1.1.1.2.6.1.9 | INTEGER | RO | optional | |||||||||||||||||
column · INTEGER · read-only · optional The number of battery blocks/modules in a battery string. Can be 0, if no data is available in the table of individual battery blocks/cartridges | |||||||||||||||||||||
| TupsBatteryCabBlockTable | 1.3.6.1.4.1.318.1.1.1.2.7 | NA | optional | ||||||||||||||||||
table · not-accessible · optional Table of battery blocks/modules in the complete battery solution. | |||||||||||||||||||||
| RupsBatteryCabBlockEntry | 1.3.6.1.4.1.318.1.1.1.2.7.1 | NA | optional | ||||||||||||||||||
row · not-accessible · optional An entry containing information applicable to a particular battery block in the battery cabinet. | |||||||||||||||||||||
| CupsBatteryCabBlockIndex | 1.3.6.1.4.1.318.1.1.1.2.7.1.1 | INTEGER | RO | optional | |||||||||||||||||
column · INTEGER · read-only · optional The battery cabinet block identifier. Global battery cabinet block table index. | |||||||||||||||||||||
| CupsBatteryCabBlockStringReference | 1.3.6.1.4.1.318.1.1.1.2.7.1.2 | INTEGER | RO | optional | |||||||||||||||||
column · INTEGER · read-only · optional Reference to the specific global battery string index | |||||||||||||||||||||
| CupsBatteryCabBlockLocalIndex | 1.3.6.1.4.1.318.1.1.1.2.7.1.3 | INTEGER | RO | optional | |||||||||||||||||
column · INTEGER · read-only · optional Local battery block/module identification index in the actual battery string (e.g. Battery block 3 in the battery string) | |||||||||||||||||||||
| CupsBatteryCabBlockPresent | 1.3.6.1.4.1.318.1.1.1.2.7.1.4 | INTEGER | RO | optional | |||||||||||||||||
column · INTEGER · read-only · optional Value indicates if battery block/module is present in the system. Typically battery modules are removable and battery blocks are static. Reports notAvailable(3) if data is not available
| |||||||||||||||||||||
| CupsBatteryCabBlockType | 1.3.6.1.4.1.318.1.1.1.2.7.1.5 | DisplayString | RO | optional | |||||||||||||||||
column · DisplayString · read-only · optional Text string value, showing the vendor and model of the battery in the battery block/module | |||||||||||||||||||||
| CupsBatteryCabBlockTemperature | 1.3.6.1.4.1.318.1.1.1.2.7.1.6 | INTEGER | RO | optional | |||||||||||||||||
column · INTEGER · read-only · optional The temperature for the battery block/module in tenths of degrees Celcius. If multiple sensors are available it is the highest temperature in the battery block/module | |||||||||||||||||||||
| CupsBatteryCabBlockFuseStatus | 1.3.6.1.4.1.318.1.1.1.2.7.1.7 | INTEGER | RO | optional | |||||||||||||||||
column · INTEGER · read-only · optional If the battery module has a fuse, the status is given by this value. 1 = Fuse open 2 = Fuse OK 3 = Not present
| |||||||||||||||||||||
| CupsBatteryCabBlockVoltage | 1.3.6.1.4.1.318.1.1.1.2.7.1.8 | INTEGER | RO | optional | |||||||||||||||||
column · INTEGER · read-only · optional The voltage of the battery block/module | |||||||||||||||||||||
| CupsBatteryCabBlockNumberOfCells | 1.3.6.1.4.1.318.1.1.1.2.7.1.9 | INTEGER | RO | optional | |||||||||||||||||
column · INTEGER · read-only · optional The number of cells in the battery block/module | |||||||||||||||||||||
| CupsBatteryCabBlockVerticalPosition | 1.3.6.1.4.1.318.1.1.1.2.7.1.10 | INTEGER | RO | optional | |||||||||||||||||
column · INTEGER · read-only · optional The vertical position of the battery block/module in the actual battery cabinet (e.g. 4, if it is the 4th shelf counting from the bottom) | |||||||||||||||||||||
| CupsBatteryCabBlockHorizontalPosition | 1.3.6.1.4.1.318.1.1.1.2.7.1.11 | INTEGER | RO | optional | |||||||||||||||||
column · INTEGER · read-only · optional The horizontal position of the battery block/module in the actual battery cabinet (e.g. 3, if it is the 3rd position counting from the left) | |||||||||||||||||||||
| TupsBatteryCabBlockCellTable | 1.3.6.1.4.1.318.1.1.1.2.8 | NA | optional | ||||||||||||||||||
table · not-accessible · optional Table of battery cells in a battery block/module in the complete battery solution | |||||||||||||||||||||
| RupsBatteryCabBlockCellEntry | 1.3.6.1.4.1.318.1.1.1.2.8.1 | NA | optional | ||||||||||||||||||
row · not-accessible · optional An entry containing information applicable to a particular battery cell inside the battery block. | |||||||||||||||||||||
| CupsBatteryCabBlockCellIndex | 1.3.6.1.4.1.318.1.1.1.2.8.1.1 | INTEGER | RO | optional | |||||||||||||||||
column · INTEGER · read-only · optional The battery block cell identifier. Global battery block cell table index. | |||||||||||||||||||||
| CupsBatteryCabBlockCellReference | 1.3.6.1.4.1.318.1.1.1.2.8.1.2 | INTEGER | RO | optional | |||||||||||||||||
column · INTEGER · read-only · optional Reference to the specific global battery block/module index. | |||||||||||||||||||||
| CupsBatteryCabBlockCellLocalIndex | 1.3.6.1.4.1.318.1.1.1.2.8.1.3 | INTEGER | RO | optional | |||||||||||||||||
column · INTEGER · read-only · optional Local battery block/module identification index in the actual battery block (e.g. battery cell 5 in the battery block) | |||||||||||||||||||||
| CupsBatteryCabBlockCellVoltage | 1.3.6.1.4.1.318.1.1.1.2.8.1.4 | INTEGER | RO | optional | |||||||||||||||||
column · INTEGER · read-only · optional The measured battery cell voltage | |||||||||||||||||||||
| CupsBatteryCabBlockCellTemperature | 1.3.6.1.4.1.318.1.1.1.2.8.1.5 | INTEGER | RO | optional | |||||||||||||||||
column · INTEGER · read-only · optional The temperature for the battery cell in tenths of degrees Celcius. If there is not a temperature sensor for each battery cell, then report -1 for those, which are not present. | |||||||||||||||||||||
| NupsInput | 1.3.6.1.4.1.318.1.1.1.3 | ||||||||||||||||||||
| NupsBasicInput | 1.3.6.1.4.1.318.1.1.1.3.1 | ||||||||||||||||||||
| SupsBasicInputPhase | 1.3.6.1.4.1.318.1.1.1.3.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The current AC input phase. | |||||||||||||||||||||
| NupsAdvInput | 1.3.6.1.4.1.318.1.1.1.3.2 | ||||||||||||||||||||
| SupsAdvInputLineVoltage | 1.3.6.1.4.1.318.1.1.1.3.2.1 | Gauge | RO | mandatory | 244 | ||||||||||||||||
scalar · Gauge · read-only · mandatory The current utility line voltage in VAC. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SupsAdvInputMaxLineVoltage | 1.3.6.1.4.1.318.1.1.1.3.2.2 | Gauge | RO | mandatory | |||||||||||||||||
scalar · Gauge · read-only · mandatory The maximum utility line voltage in VAC over the previous 1 minute period. | |||||||||||||||||||||
| SupsAdvInputMinLineVoltage | 1.3.6.1.4.1.318.1.1.1.3.2.3 | Gauge | RO | mandatory | |||||||||||||||||
scalar · Gauge · read-only · mandatory The minimum utility line voltage in VAC over the previous 1 minute period. | |||||||||||||||||||||
| SupsAdvInputFrequency | 1.3.6.1.4.1.318.1.1.1.3.2.4 | Gauge | RO | mandatory | 50 | ||||||||||||||||
scalar · Gauge · read-only · mandatory The current input frequency to the UPS system in Hz. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SupsAdvInputLineFailCause | 1.3.6.1.4.1.318.1.1.1.3.2.5 | INTEGER | RO | mandatory | noTransfer(1) | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The reason for the occurrence of the last transfer to UPS battery power. The variable is set to: - noTransfer(1) -- if there is no transfer yet. - highLineVoltage(2) -- if the transfer to battery is caused by an over voltage greater than the high transfer voltage. - brownout(3) -- if the duration of the outage is greater than five seconds and the line voltage is between 40% of the rated output voltage and the low transfer voltage. - blackout(4) -- if the duration of the outage is greater than five seconds and the line voltage is between 40% of the rated output voltage and ground. - smallMomentarySag(5) -- if the duration of the outage is less than five seconds and the line voltage is between 40% of the rated output voltage and the low transfer voltage. - deepMomentarySag(6) -- if the duration of the outage is less than five seconds and the line voltage is between 40% of the rated output voltage and ground. The variable is set to - smallMomentarySpike(7) -- if the line failure is caused by a rate of change of input voltage less than ten volts per cycle. - largeMomentarySpike(8) -- if the line failure is caused by a rate of change of input voltage greater than ten volts per cycle. - selfTest(9) -- if the UPS was commanded to do a self test. - rateOfVoltageChange(10) -- if the failure is due to the rate of change of the line voltage.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SupsAdvInputNominalFrequency | 1.3.6.1.4.1.318.1.1.1.3.2.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The nominal input frequency of the UPS system in Hz. | |||||||||||||||||||||
| SupsAdvInputNominalVoltage | 1.3.6.1.4.1.318.1.1.1.3.2.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The nominal input voltage of the UPS system in VAC. | |||||||||||||||||||||
| SupsAdvInputBypassNominalFrequency | 1.3.6.1.4.1.318.1.1.1.3.2.8 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The nominal bypass input frequency of the UPS system in Hz. | |||||||||||||||||||||
| SupsAdvInputBypassNominalVoltage | 1.3.6.1.4.1.318.1.1.1.3.2.9 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The nominal bypass input voltage of the UPS system in VAC. | |||||||||||||||||||||
| TupsAdvInputStatisticsTable | 1.3.6.1.4.1.318.1.1.1.3.2.10 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of input table entries. The number of entries is given by the value of upsPhaseNumInputs. | |||||||||||||||||||||
| RupsAdvInputStatisticsEntry | 1.3.6.1.4.1.318.1.1.1.3.2.10.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular input. | |||||||||||||||||||||
| CupsAdvInputStatisticsIndex | 1.3.6.1.4.1.318.1.1.1.3.2.10.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The input identifier. | |||||||||||||||||||||
| CupsAdvInputApparentPower | 1.3.6.1.4.1.318.1.1.1.3.2.10.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The input apparent power(sum of all of the three phases) measured in kVA. | |||||||||||||||||||||
| CupsAdvInputVoltageTHD | 1.3.6.1.4.1.318.1.1.1.3.2.10.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The input voltage Total Harmonic Distortion in percent. | |||||||||||||||||||||
| CupsAdvInputBypassVoltageTHD | 1.3.6.1.4.1.318.1.1.1.3.2.10.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The bypass input voltage Total Harmonic Distortion in percent. | |||||||||||||||||||||
| CupsAdvInputPeakCurrent | 1.3.6.1.4.1.318.1.1.1.3.2.10.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The input peak current in Amperes. | |||||||||||||||||||||
| CupsAdvInputBypassPeakCurrent | 1.3.6.1.4.1.318.1.1.1.3.2.10.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The bypass input peak current in Amperes. | |||||||||||||||||||||
| CupsAdvInputActivePower | 1.3.6.1.4.1.318.1.1.1.3.2.10.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The input active power measured in kW. | |||||||||||||||||||||
| SupsAdvInputTotalApparentPower | 1.3.6.1.4.1.318.1.1.1.3.2.11 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The input total apparent power(sum of all three phases) of the UPS system in kVA. | |||||||||||||||||||||
| SupsAdvInputTotalActivePower | 1.3.6.1.4.1.318.1.1.1.3.2.12 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The input total active power(sum of all three phases) of the UPS system in kW. If not supported, return -1 | |||||||||||||||||||||
| SupsAdvInputBypassTotalApparentPower | 1.3.6.1.4.1.318.1.1.1.3.2.13 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The input bypass total apparent power(sum of all three phases) of the UPS system in kVA. | |||||||||||||||||||||
| SupsAdvInputBypassTotalActivePower | 1.3.6.1.4.1.318.1.1.1.3.2.14 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The input bypass total active power(sum of all three phases) of the UPS system in kW. | |||||||||||||||||||||
| SupsAdvInputEnergyUsage | 1.3.6.1.4.1.318.1.1.1.3.2.15 | Unsigned32 | RO | mandatory | |||||||||||||||||
scalar · Unsigned32 · read-only · mandatory The input energy usage of the UPS in kWh. | |||||||||||||||||||||
| SupsAdvInputDCVoltage | 1.3.6.1.4.1.318.1.1.1.3.2.16 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The DC input voltage in Volts. | |||||||||||||||||||||
| SupsAdvInputDCCurrent | 1.3.6.1.4.1.318.1.1.1.3.2.17 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The DC input current in Amps. | |||||||||||||||||||||
| SupsAdvInputNominalDCVoltage | 1.3.6.1.4.1.318.1.1.1.3.2.18 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The nominal input DC voltage of the inverter in Volts. If not supported, return -1. | |||||||||||||||||||||
| NupsHighPrecInput | 1.3.6.1.4.1.318.1.1.1.3.3 | ||||||||||||||||||||
| SupsHighPrecInputLineVoltage | 1.3.6.1.4.1.318.1.1.1.3.3.1 | Gauge | RO | mandatory | 2476 | ||||||||||||||||
scalar · Gauge · read-only · mandatory The current utility line voltage in tenths of VAC. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SupsHighPrecInputMaxLineVoltage | 1.3.6.1.4.1.318.1.1.1.3.3.2 | Gauge | RO | mandatory | |||||||||||||||||
scalar · Gauge · read-only · mandatory The maximum utility line voltage in tenths of VAC over the previous 1 minute period. | |||||||||||||||||||||
| SupsHighPrecInputMinLineVoltage | 1.3.6.1.4.1.318.1.1.1.3.3.3 | Gauge | RO | mandatory | |||||||||||||||||
scalar · Gauge · read-only · mandatory The minimum utility line voltage in tenths of VAC over the previous 1 minute period. | |||||||||||||||||||||
| SupsHighPrecInputFrequency | 1.3.6.1.4.1.318.1.1.1.3.3.4 | Gauge | RO | mandatory | 500 | ||||||||||||||||
scalar · Gauge · read-only · mandatory The current input frequency to the UPS system in tenths of Hz. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SupsHighPrecInputEnergyUsage | 1.3.6.1.4.1.318.1.1.1.3.3.5 | Unsigned32 | RO | mandatory | |||||||||||||||||
scalar · Unsigned32 · read-only · mandatory The input energy usage of the UPS in hundredths of kWh. | |||||||||||||||||||||
| SupsHighPrecInputBypassVoltage | 1.3.6.1.4.1.318.1.1.1.3.3.6 | Unsigned32 | RO | mandatory | |||||||||||||||||
scalar · Unsigned32 · read-only · mandatory The current bypass line voltage in tenths of VAC. | |||||||||||||||||||||
| SupsHighPrecInputBypassFrequency | 1.3.6.1.4.1.318.1.1.1.3.3.7 | Unsigned32 | RO | mandatory | |||||||||||||||||
scalar · Unsigned32 · read-only · mandatory The current input bypass frequency to the UPS system in tenths of Hz. | |||||||||||||||||||||
| SupsHighPrecInputDCVoltage | 1.3.6.1.4.1.318.1.1.1.3.3.8 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The DC input voltage, in tenths, of Volts on the inverter. If not supported, return -1. | |||||||||||||||||||||
| SupsHighPrecInputDCCurrent | 1.3.6.1.4.1.318.1.1.1.3.3.9 | Gauge | RO | mandatory | |||||||||||||||||
scalar · Gauge · read-only · mandatory The DC input current, in tenths of amperes, of the inverter. | |||||||||||||||||||||
| NupsOutput | 1.3.6.1.4.1.318.1.1.1.4 | ||||||||||||||||||||
| NupsBasicOutput | 1.3.6.1.4.1.318.1.1.1.4.1 | ||||||||||||||||||||
| SupsBasicOutputStatus | 1.3.6.1.4.1.318.1.1.1.4.1.1 | INTEGER | RO | mandatory | onLine(2) | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The current state of the UPS. If the UPS is unable to determine the state of the UPS this variable is set to unknown(1).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SupsBasicOutputPhase | 1.3.6.1.4.1.318.1.1.1.4.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The actual number of output phases in a UPS | |||||||||||||||||||||
| SupsBasicSystemStatus | 1.3.6.1.4.1.318.1.1.1.4.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Current state for the whole system (UPS and surrounding breakers). If the UPS is unable to determine the state of the system, this variable is set to unknown(1).
| |||||||||||||||||||||
| SupsBasicSystemInternalTemperature | 1.3.6.1.4.1.318.1.1.1.4.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The actual internal temperature of the UPS system in Celsius. | |||||||||||||||||||||
| SupsBasicSystemInverterStatus | 1.3.6.1.4.1.318.1.1.1.4.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The current state of the UPS inverter. If the UPS is unable to determine the state of the inverter, this variable is set to unknown(1).
| |||||||||||||||||||||
| SupsBasicSystemPFCStatus | 1.3.6.1.4.1.318.1.1.1.4.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The general status of the power factor correction (AC input stage of the UPS). If the UPS is unable to determine the state of PFC, this variable is set to unknown(1).
| |||||||||||||||||||||
| SupsBasicOutputACwiringConfiguration | 1.3.6.1.4.1.318.1.1.1.4.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Indicates if neutral wire on output side of the UPS is used (load wired line to neutral). If the UPS is unable to determine the state of neutral, this variable is set to unknown(1).
| |||||||||||||||||||||
| NupsAdvOutput | 1.3.6.1.4.1.318.1.1.1.4.2 | ||||||||||||||||||||
| SupsAdvOutputVoltage | 1.3.6.1.4.1.318.1.1.1.4.2.1 | Gauge | RO | mandatory | 244 | ||||||||||||||||
scalar · Gauge · read-only · mandatory The output voltage of the UPS system in VAC. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SupsAdvOutputFrequency | 1.3.6.1.4.1.318.1.1.1.4.2.2 | Gauge | RO | mandatory | 50 | ||||||||||||||||
scalar · Gauge · read-only · mandatory The current output frequency of the UPS system in Hz. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SupsAdvOutputLoad | 1.3.6.1.4.1.318.1.1.1.4.2.3 | Gauge | RO | mandatory | 31 | ||||||||||||||||
scalar · Gauge · read-only · mandatory The current UPS load expressed in percent of rated capacity. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SupsAdvOutputCurrent | 1.3.6.1.4.1.318.1.1.1.4.2.4 | Gauge | RO | mandatory | |||||||||||||||||
scalar · Gauge · read-only · mandatory The current in amperes drawn by the load on the UPS. | |||||||||||||||||||||
| SupsAdvOutputRedundancy | 1.3.6.1.4.1.318.1.1.1.4.2.5 | Gauge | RO | mandatory | |||||||||||||||||
scalar · Gauge · read-only · mandatory The number of power modules which can fail or be removed without causing the UPS to generate a Minimum Redundancy Lost event. | |||||||||||||||||||||
| SupsAdvOutputKVACapacity | 1.3.6.1.4.1.318.1.1.1.4.2.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The maximum load that this UPS can support. This value is dynamic for scalable 3-phase UPS devices where power modules can be added for increased capacity. The value indicates the actual available output capacity. For non-scalable 3-phase UPS devices the value is fixed to the UPS rating. | |||||||||||||||||||||
| SupsAdvOutputNominalFrequency | 1.3.6.1.4.1.318.1.1.1.4.2.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The nominal output frequency of the UPS system in Hz. | |||||||||||||||||||||
| SupsAdvOutputActivePower | 1.3.6.1.4.1.318.1.1.1.4.2.8 | INTEGER | RO | mandatory | 169 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The total output active power of the UPS system in W. The total active power is the sum of phase 1, phase 2 and phase 3 power. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SupsAdvOutputApparentPower | 1.3.6.1.4.1.318.1.1.1.4.2.9 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The total output apparent power of all phases of the UPS system in VA. If not supported, return -1. | |||||||||||||||||||||
| TupsAdvOutputStatisticsTable | 1.3.6.1.4.1.318.1.1.1.4.2.10 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of input table entries. The number of entries is given by the value of upsPhaseNumOutputs. | |||||||||||||||||||||
| RupsAdvOutputStatisticsEntry | 1.3.6.1.4.1.318.1.1.1.4.2.10.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular output. | |||||||||||||||||||||
| CupsAdvOutputStatisticsIndex | 1.3.6.1.4.1.318.1.1.1.4.2.10.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The output identifier. | |||||||||||||||||||||
| CupsAdvOutputPeakCurrent | 1.3.6.1.4.1.318.1.1.1.4.2.10.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The output peak current in Amperes. | |||||||||||||||||||||
| CupsAdvOutputCurrentTHD | 1.3.6.1.4.1.318.1.1.1.4.2.10.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The output current Total Harmonic Distortion in percent. | |||||||||||||||||||||
| CupsAdvOutputCrestFactor | 1.3.6.1.4.1.318.1.1.1.4.2.10.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The output current crest factor expressed in tenths. | |||||||||||||||||||||
| SupsAdvOutputNeutralCurrent | 1.3.6.1.4.1.318.1.1.1.4.2.11 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The neutral current in amperes. | |||||||||||||||||||||
| SupsAdvOutputEnergyUsage | 1.3.6.1.4.1.318.1.1.1.4.2.12 | Unsigned32 | RO | mandatory | |||||||||||||||||
scalar · Unsigned32 · read-only · mandatory The output energy usage of the UPS in kWh. | |||||||||||||||||||||
| SupsAdvOutputSourceSynchronization | 1.3.6.1.4.1.318.1.1.1.4.2.13 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Indicates the synchronization source for the inverter output frequency. 1. Main 2. Internal 3. External 4. On AC Bypass. 5. External / On Bypass For other values it is unknown | |||||||||||||||||||||
| SupsAdvOutputInverterFrequency | 1.3.6.1.4.1.318.1.1.1.4.2.14 | Gauge | RO | mandatory | |||||||||||||||||
scalar · Gauge · read-only · mandatory Output frequency in Hz measured at the output of inverter. | |||||||||||||||||||||
| SupsAdvOutputInverterLoad | 1.3.6.1.4.1.318.1.1.1.4.2.15 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The total active power at the output of all inverter modules in percent of rated system power (% of kW) If not supported, return -1. | |||||||||||||||||||||
| SupsAdvOutputPercentPower | 1.3.6.1.4.1.318.1.1.1.4.2.16 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The relative active power at the output of the inverter system (static switch output) in percent of rated system power (% of kW). If not supported, return -1. | |||||||||||||||||||||
| SupsAdvOutputInverterActivePower | 1.3.6.1.4.1.318.1.1.1.4.2.17 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The total active power at the output of all inverter modules in kW. If not supported, return -1. | |||||||||||||||||||||
| SupsAdvOutputPercentLoad | 1.3.6.1.4.1.318.1.1.1.4.2.18 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The relative apparent power at the output of the inverter system (static switch output) in percent of rated system load (% of kVA) If not supported, return -1. | |||||||||||||||||||||
| SupsAdvOutputInverterCurrent | 1.3.6.1.4.1.318.1.1.1.4.2.19 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The current, in amperes, drawn by the load on the inverter. | |||||||||||||||||||||
| SupsAdvOutputReactivePower | 1.3.6.1.4.1.318.1.1.1.4.2.20 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The total output reactive power of all phases of the UPS system in VAR. If not supported, return -1. | |||||||||||||||||||||
| SupsAdvOutputInverterVoltage | 1.3.6.1.4.1.318.1.1.1.4.2.21 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The output voltage of the inverter in VAC. | |||||||||||||||||||||
| SupsAdvOutputUpperAcceptPowerSettingPct | 1.3.6.1.4.1.318.1.1.1.4.2.22 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Upper acceptable voltage as percent of nominal voltage | |||||||||||||||||||||
| NupsHighPrecOutput | 1.3.6.1.4.1.318.1.1.1.4.3 | ||||||||||||||||||||
| SupsHighPrecOutputVoltage | 1.3.6.1.4.1.318.1.1.1.4.3.1 | Gauge | RO | mandatory | 2476 | ||||||||||||||||
scalar · Gauge · read-only · mandatory The output voltage of the UPS system in tenths of VAC. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SupsHighPrecOutputFrequency | 1.3.6.1.4.1.318.1.1.1.4.3.2 | Gauge | RO | mandatory | 500 | ||||||||||||||||
scalar · Gauge · read-only · mandatory The current output frequency of the UPS system in tenths of Hz. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SupsHighPrecOutputLoad | 1.3.6.1.4.1.318.1.1.1.4.3.3 | Gauge | RO | mandatory | 176 | ||||||||||||||||
scalar · Gauge · read-only · mandatory The current UPS load expressed in tenths of percent of rated capacity. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SupsHighPrecOutputCurrent | 1.3.6.1.4.1.318.1.1.1.4.3.4 | Gauge | RO | mandatory | 10 | ||||||||||||||||
scalar · Gauge · read-only · mandatory The current in tenths of amperes drawn by the load on the UPS. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SupsHighPrecOutputEfficiency | 1.3.6.1.4.1.318.1.1.1.4.3.5 | Integer32 | RO | mandatory | |||||||||||||||||
scalar · Integer32 · read-only · mandatory The positive values represent efficiency of the UPS in tenths of percent. -1 If UPS supports this OID but the result is not available -2 Load is too low to report efficiency -3 Output off and efficiency is 0 -4 On battery, efficiency is not measured or calculated in this mode -5 In Bypass, efficiency is not measured or calculated in this mode -6 Battery charging, battery is charging and adversely affecting efficiency -7 Poor AC input, the main input is outside the optimum efficiency range | |||||||||||||||||||||
| SupsHighPrecOutputEnergyUsage | 1.3.6.1.4.1.318.1.1.1.4.3.6 | Unsigned32 | RO | mandatory | |||||||||||||||||
scalar · Unsigned32 · read-only · mandatory The output energy usage of the UPS in hundredths of kWh. | |||||||||||||||||||||
| NupsConfig | 1.3.6.1.4.1.318.1.1.1.5 | ||||||||||||||||||||
| NupsBasicConfig | 1.3.6.1.4.1.318.1.1.1.5.1 | ||||||||||||||||||||
| SupsBasicConfigNumDevices | 1.3.6.1.4.1.318.1.1.1.5.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of devices that are plugged into the UPS. This value is customer configurable from the device entry table | |||||||||||||||||||||
| TupsBasicConfigDeviceTable | 1.3.6.1.4.1.318.1.1.1.5.1.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of devices that are plugged into the UPS. The number of entries is given by the value of upsBasicConfigNumDevices. | |||||||||||||||||||||
| RupsBasicConfigDeviceEntry | 1.3.6.1.4.1.318.1.1.1.5.1.2.1 | NA | mandatory | ||||||||||||||||||
| CdeviceIndex | 1.3.6.1.4.1.318.1.1.1.5.1.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of the device that is plugged into the UPS. | |||||||||||||||||||||
| CdeviceName | 1.3.6.1.4.1.318.1.1.1.5.1.2.1.2 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The name/description of the device plugged into the UPS. | |||||||||||||||||||||
| CvaRating | 1.3.6.1.4.1.318.1.1.1.5.1.2.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The volt-amp rating of the device plugged into the UPS. | |||||||||||||||||||||
| CacceptThisDevice | 1.3.6.1.4.1.318.1.1.1.5.1.2.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory An entry is added if yes, the entry is deleted if no.
| |||||||||||||||||||||
| NupsAdvConfig | 1.3.6.1.4.1.318.1.1.1.5.2 | ||||||||||||||||||||
| SupsAdvConfigRatedOutputVoltage | 1.3.6.1.4.1.318.1.1.1.5.2.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The nominal output voltage from the UPS in VAC. For a list of allowed values supported by your UPS model, see the UPS User's Manual. If a value other than a supported value is provided in a set request, the UPS interprets it as the next lower acceptable value. If the provided value is lower than the lowest acceptable value, the lowest acceptable value is used. | |||||||||||||||||||||
| SupsAdvConfigHighTransferVolt | 1.3.6.1.4.1.318.1.1.1.5.2.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The maximum line voltage in VAC allowed before the UPS system transfers to battery backup. For a list of allowed values supported by your UPS model, see the UPS User's Manual. If a value other than a supported value is provided in a set request, the UPS interprets it as the next higher acceptable value. If the provided value is higher than the highest acceptable value, the highest acceptable value is used. | |||||||||||||||||||||
| SupsAdvConfigLowTransferVolt | 1.3.6.1.4.1.318.1.1.1.5.2.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The minimum line voltage in VAC allowed before the UPS system transfers to battery backup. For a list of allowed values supported by your UPS model, see the UPS User's Manual. If a value other than a supported value is provided in a set request, the UPS interprets it as the next lower acceptable value. If the provided value is lower than the lowest acceptable value, the lowest acceptable value is used. | |||||||||||||||||||||
| SupsAdvConfigAlarm | 1.3.6.1.4.1.318.1.1.1.5.2.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory A flag indicating how the UPS should handle audible line fail alarms: timed(1): UPS alarm will sound after a preset timed duration starting from the line fail condition (see OID upsAdvConfigAlarmTimer for the alarm timer value) atLowBattery(2): UPS alarm will sound when the UPS has reached a Low Battery condition during a line fail never(3): Disables the UPS audible alarm mute(4): Mutes the current alarm for some UPS devices only when it is in an alarm state and will return to the previously configured option when the UPS recovers from the alarm condition
| |||||||||||||||||||||
| SupsAdvConfigAlarmTimer | 1.3.6.1.4.1.318.1.1.1.5.2.5 | TimeTicks | RW | mandatory | |||||||||||||||||
scalar · TimeTicks · read-write · mandatory The time after initial line failure at which the UPS begins emitting audible alarms (beeping). This timer is observed only if the value of extControlAlarm is timed(2). Allowed values are 0 or 30 seconds. If a value other than a supported value is provided in a set request, the UPS interprets it as the next lower acceptable value. If the provided value is lower than the lowest acceptable value, the lowest acceptable value is used. | |||||||||||||||||||||
| SupsAdvConfigMinReturnCapacity | 1.3.6.1.4.1.318.1.1.1.5.2.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The minimum battery capacity required before the UPS will return from a low battery shutdown condition. The capacity is measured from 0% battery capacity (or Low Battery) as a percent of full capacity (100%). In other words, the UPS will not re-energize the output until the battery has charged so that its' capacity is equal to this value. For a list of allowed values supported by your UPS model, see the UPS User's Manual. If a value other than a supported value is provided in a set request, the UPS interprets it as the next higher acceptable value. If the provided value is higher than the highest acceptable value, the highest acceptable value is used. | |||||||||||||||||||||
| SupsAdvConfigSensitivity | 1.3.6.1.4.1.318.1.1.1.5.2.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The sensitivity of the UPS to utility line abnormalities or noises.
| |||||||||||||||||||||
| SupsAdvConfigLowBatteryRunTime | 1.3.6.1.4.1.318.1.1.1.5.2.8 | TimeTicks | RW | mandatory | |||||||||||||||||
scalar · TimeTicks · read-write · mandatory The desired run time of the UPS, in seconds, once the low battery condition is reached. During this time the UPS may produce a constant warning tone, which cannot be disabled, depending on the UPS model. For a list of allowed values supported by your UPS model, see the UPS User's Manual. If a value other than a supported value is provided in a set request, the UPS interprets the value as the next higher acceptable value. If the provided value is higher than the highest acceptable value, the highest acceptable value is used. | |||||||||||||||||||||
| SupsAdvConfigReturnDelay | 1.3.6.1.4.1.318.1.1.1.5.2.9 | TimeTicks | RW | mandatory | |||||||||||||||||
scalar · TimeTicks · read-write · mandatory The delay in seconds after utility line power returns before the UPS will turn on. This value is also used when the UPS comes out of a reboot and before the UPS wakes up from 'sleep' mode. For a list of allowed values supported by your UPS model, see the UPS User's Manual. If a value other than a supported value is provided in a set request, the UPS interprets it as the next higher acceptable value. If the provided value is higher than the highest acceptable value, the highest acceptable value is used. | |||||||||||||||||||||
| SupsAdvConfigShutoffDelay | 1.3.6.1.4.1.318.1.1.1.5.2.10 | TimeTicks | RW | mandatory | |||||||||||||||||
scalar · TimeTicks · read-write · mandatory The delay in seconds the UPS remains on after being told to turn off. For a list of allowed values supported by your UPS model, see the UPS User's Manual. If a value other than a supported value is provided in a set request, the UPS interprets it as the next higher acceptable value. If the provided value is higher than the highest acceptable value, the highest acceptable value is used. | |||||||||||||||||||||
| SupsAdvConfigUpsSleepTime | 1.3.6.1.4.1.318.1.1.1.5.2.11 | TimeTicks | RW | mandatory | |||||||||||||||||
scalar · TimeTicks · read-write · mandatory The time in seconds for the UPS to go to 'sleep' when instructed. When in sleep mode, the UPS will not provide output power regardless of the input line state. Once the specified time has elapsed, output power will be restored. This is a configuration setting. The UPS will not go to sleep until told to do so by the manager from a management station. Any input value is allowed, however the UPS only recognizes 1/10 of an hour increments. The provided value will be rounded to the closest 1/10 of an hour with one exception: Any value entered between 1 and 540 seconds will be rounded to 360 seconds (or 6 minutes). | |||||||||||||||||||||
| SupsAdvConfigSetEEPROMDefaults | 1.3.6.1.4.1.318.1.1.1.5.2.12 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory WRITE: Resets the UPS EEPROM variables to default values. READ: returns 1
| |||||||||||||||||||||
| TupsAdvConfigDipSwitchTable | 1.3.6.1.4.1.318.1.1.1.5.2.13 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Current settings of UPS dip switches. | |||||||||||||||||||||
| RupsAdvConfigDipSwitchEntry | 1.3.6.1.4.1.318.1.1.1.5.2.13.1 | NA | mandatory | ||||||||||||||||||
| CdipSwitchIndex | 1.3.6.1.4.1.318.1.1.1.5.2.13.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of a UPS dip switch. | |||||||||||||||||||||
| CdipSwitchStatus | 1.3.6.1.4.1.318.1.1.1.5.2.13.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The setting of a UPS dip switch.
| |||||||||||||||||||||
| SupsAdvConfigBattExhaustThresh | 1.3.6.1.4.1.318.1.1.1.5.2.14 | TimeTicks | RW | mandatory | |||||||||||||||||
scalar · TimeTicks · read-write · mandatory The number of seconds prior to battery exhaustion when the UPS will switch off power to its load. | |||||||||||||||||||||
| SupsAdvConfigPassword | 1.3.6.1.4.1.318.1.1.1.5.2.15 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory The password entered at the UPS front panel to enable local configuration of the EEProm. If the password is disabled or is not supported, then the agent returns a null string. | |||||||||||||||||||||
| TupsAdvConfigAllowedSetTable | 1.3.6.1.4.1.318.1.1.1.5.2.16 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory The table listing the allowed values for all discrete configurable UPS variables. | |||||||||||||||||||||
| RupsAdvConfigAllowedSetEntry | 1.3.6.1.4.1.318.1.1.1.5.2.16.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The table entry for a configurable UPS variable. | |||||||||||||||||||||
| CapcUpsConfigFieldIndex | 1.3.6.1.4.1.318.1.1.1.5.2.16.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to an eeprom field entry. | |||||||||||||||||||||
| CapcUpsConfigFieldOID | 1.3.6.1.4.1.318.1.1.1.5.2.16.1.2 | OBJECT IDENTIFIER | RO | mandatory | |||||||||||||||||
column · OBJECT IDENTIFIER · read-only · mandatory The OID of the current configurable value. | |||||||||||||||||||||
| CapcUpsConfigFieldValueRange | 1.3.6.1.4.1.318.1.1.1.5.2.16.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The discrete set of allowed values of a configurable register. Individual values are delimited by a comma. | |||||||||||||||||||||
| SupsAdvConfigBattCabAmpHour | 1.3.6.1.4.1.318.1.1.1.5.2.17 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Configure the amp-hour setting of the UPS battery solution. The value shows the maximum battery capacity configured for the UPS when using a third party battery solution regardless of the breaker positions. The actual available battery capacity based on breaker positions or connected/disconnected battery strings, is presented in OID upsAdvBatteryTotalCapacity | |||||||||||||||||||||
| SupsAdvConfigPositionSelector | 1.3.6.1.4.1.318.1.1.1.5.2.18 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Configure UPS position selector. If the UPS doesn't support this configuration it will report unknown (1). The positions are either rack (2) for rack mounted or tower (3) for tower unit.
| |||||||||||||||||||||
| SupsAdvConfigOutputFreqRange | 1.3.6.1.4.1.318.1.1.1.5.2.19 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Configure the output frequency tolerance range. unknown(1) indicates the output frequency is unknown. freqRangeAUTO(2) configure the output frequency range for automatic. freqRange60Var1(3) configure the output frequency range for 60 +/- 0.1 Hz freqRange60Var3(4) configure the output frequency range for 60 +/- 3.0 Hz freqRange50Var1(5) configure the output frequency range for 50 +/- 0.1 Hz freqRange50Var3(6) configure the output frequency range for 50 +/- 3.0 Hz freqRange60Var10(7) configure the output frequency range for 60 +/- 10 Hz freqRange50Var10(8) configure the output frequency range for 50 +/- 10 Hz freqRange60Var1dot0(9) configure the output frequency range for 60 +/- 1.0 Hz freqRange50Var1dot0(10) configure the output frequency range for 50 +/- 1.0 Hz freqRange50Pct0dot5(11) configure the output frequency range for 50 Hz +/- 0.5 % freqRange50Pct1(12) configure the output frequency range for 50 Hz +/- 1.0 % freqRange50Pct2(13) configure the output frequency range for 50 Hz +/- 2.0 % freqRange50Pct4(14) configure the output frequency range for 50 Hz +/- 4.0 % freqRange50Pct6(15) configure the output frequency range for 50 Hz +/- 6.0 % freqRange50Pct8(16) configure the output frequency range for 50 Hz +/- 8.0 % freqRange60Pct0dot5(17) configure the output frequency range for 60 Hz +/- 0.5 % freqRange60Pct1(18) configure the output frequency range for 60 Hz +/- 1.0 % freqRange60Pct2(19) configure the output frequency range for 60 Hz +/- 2.0 % freqRange60Pct4(20) configure the output frequency range for 60 Hz +/- 4.0 % freqRange60Pct6(21) configure the output frequency range for 60 Hz +/- 6.0 % freqRange60Pct8(22) configure the output frequency range for 60 Hz +/- 8.0 % freqRange50Var4(23) configure the output frequency range for 50 +/- 4.0 Hz freqRange60Var4(24) configure the output frequency range for 60 +/- 4.0 Hz For a list of allowed values and conditions when variable can be set by your UPS model, see the UPS User's Manual.
| |||||||||||||||||||||
| SupsAdvConfigUPSFail | 1.3.6.1.4.1.318.1.1.1.5.2.20 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Configure the UPS fail action. If UPS fails, and frequency or voltage is out of range it will either GotoBypass (2) or DropLoad (3). This OID will report unknown (1) if it is not supported feature or option.
| |||||||||||||||||||||
| SupsAdvConfigAlarmRedundancy | 1.3.6.1.4.1.318.1.1.1.5.2.21 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Configure settings of UPS alarm if the redundancy is under the current redundancy. Use 0 for never. | |||||||||||||||||||||
| SupsAdvConfigAlarmLoadOver | 1.3.6.1.4.1.318.1.1.1.5.2.22 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Configure settings of UPS alarm if the load is over the current load in kVA. Use -1 for never. | |||||||||||||||||||||
| SupsAdvConfigAlarmRuntimeUnder | 1.3.6.1.4.1.318.1.1.1.5.2.23 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Configure settings of UPS alarm if the runtime is under the current time of minutes. Use -1 for never. | |||||||||||||||||||||
| SupsAdvConfigVoutReporting | 1.3.6.1.4.1.318.1.1.1.5.2.24 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Configure the way the UPS scales its output voltage readings. unknown(1) indicates the Vout Reporting is unknown. voutAUTO(2) configure the Vout Reporting for automatic scaling. vout208(3) configure the Vout Reporting for 208 Volts. vout240(4) configure the Vout Reporting for 240 Volts.
| |||||||||||||||||||||
| SupsAdvConfigNumExternalBatteries | 1.3.6.1.4.1.318.1.1.1.5.2.25 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Configure the number of external batteries connected to the UPS. | |||||||||||||||||||||
| SupsAdvConfigSimpleSignalShutdowns | 1.3.6.1.4.1.318.1.1.1.5.2.26 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Configure Simple Signal shutdown commands from the Simple Signal port to be issued to the UPS. unknown(1) indicates the Simple Signal Shutdown setting is unknown. disabled(2) configure to disable Simple Signal Shutdowns. enabled(3) configure to enable Simple Signal Shutdowns.
| |||||||||||||||||||||
| SupsAdvConfigMaxShutdownTime | 1.3.6.1.4.1.318.1.1.1.5.2.27 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The maximum amount of time for server shutdown to complete before a UPS shutdown occurs. | |||||||||||||||||||||
| SupsAsiUpsControlServerRequestShutdown | 1.3.6.1.4.1.318.1.1.1.5.2.28 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Start a server shutdown sequence: serverShutdownOff: Shutdown server and turn off UPS serverShutdownReboot: Shutdown server and turn reboot UPS.
| |||||||||||||||||||||
| SupsAdvConfigMinReturnRuntime | 1.3.6.1.4.1.318.1.1.1.5.2.29 | TimeTicks | RW | mandatory | |||||||||||||||||
scalar · TimeTicks · read-write · mandatory The minimum amount of run time in seconds required before the output will be turned on, using power calculation captured at start of last shutdown. | |||||||||||||||||||||
| SupsAdvConfigBasicSignalLowBatteryDuration | 1.3.6.1.4.1.318.1.1.1.5.2.30 | TimeTicks | RW | mandatory | |||||||||||||||||
scalar · TimeTicks · read-write · mandatory The duration of runtime in seconds during an on-battery condition at which the UPS will signal the basic low battery shutdown condition. | |||||||||||||||||||||
| SupsAdvConfigBypassPhaseLockRequired | 1.3.6.1.4.1.318.1.1.1.5.2.31 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Sets the condition for when bypass is an acceptable mode of operation as a requirement.
| |||||||||||||||||||||
| SupsAdvConfigOutputFreqSlewRate | 1.3.6.1.4.1.318.1.1.1.5.2.32 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The rate at which the UPS will change its output frequency in response to utility frequency changes.
| |||||||||||||||||||||
| SupsAdvConfigChargerLevel | 1.3.6.1.4.1.318.1.1.1.5.2.33 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Sets the rate at which the UPS charges its batteries.
| |||||||||||||||||||||
| SupsAdvConfigBypassToleranceSetting | 1.3.6.1.4.1.318.1.1.1.5.2.34 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory This setting allows selecting from standard bypass tolerance configurations to suit their situation.
| |||||||||||||||||||||
| SupsAdvConfigMainsSetting | 1.3.6.1.4.1.318.1.1.1.5.2.35 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Configure the type of mains supply system. singleInput (1) indicates a single supply system. dualInput (2) indicates a dual supply system.
| |||||||||||||||||||||
| SupsAdvConfigACWiringSetting | 1.3.6.1.4.1.318.1.1.1.5.2.36 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Configure the AC wiring of the system. threeWire (1) indicates 3-wire system configuration. fourWire (2) indicates 4-wire system configuration. fourWireHRG (3) indicates a 4-wire High resistive Grounding system.
| |||||||||||||||||||||
| SupsAdvConfigUpperOutputVoltTolerance | 1.3.6.1.4.1.318.1.1.1.5.2.37 | INTEGER (0..100) | RW | mandatory | |||||||||||||||||
scalar · INTEGER (0..100) · read-write · mandatory Upper tolerance of the output RMS voltage before transferring to bypass. Expressed as percent of nominal voltage. | |||||||||||||||||||||
| SupsAdvConfigLowerOutputVoltTolerance | 1.3.6.1.4.1.318.1.1.1.5.2.38 | INTEGER (0..100) | RW | mandatory | |||||||||||||||||
scalar · INTEGER (0..100) · read-write · mandatory Lower tolerance of the output RMS voltage before transferring to bypass. Expressed as percent of nominal voltage. | |||||||||||||||||||||
| SupsAdvConfigUpperBypassVoltTolerance | 1.3.6.1.4.1.318.1.1.1.5.2.39 | INTEGER (0..100) | RW | mandatory | |||||||||||||||||
scalar · INTEGER (0..100) · read-write · mandatory Upper tolerance of the bypass voltage that allows transfer to bypass by user. Expressed as percent of nominal voltage. | |||||||||||||||||||||
| SupsAdvConfigLowerBypassVoltTolerance | 1.3.6.1.4.1.318.1.1.1.5.2.40 | INTEGER (0..100) | RW | mandatory | |||||||||||||||||
scalar · INTEGER (0..100) · read-write · mandatory Lower tolerance of the bypass voltage that allows transfer to bypass by user. Expressed as percent of nominal voltage. | |||||||||||||||||||||
| SupsAdvConfigOutofSyncBypassTransferDelay | 1.3.6.1.4.1.318.1.1.1.5.2.41 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Configure the time (in milliseconds), indicating the gap in output voltage if an asynchronous transfer to bypass needs to occur. | |||||||||||||||||||||
| SupsAdvConfigWarningAlarmDelay | 1.3.6.1.4.1.318.1.1.1.5.2.43 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Configure the time delay for reporting warning alarms (in seconds). | |||||||||||||||||||||
| SupsAdvConfigInformationalAlarmDelay | 1.3.6.1.4.1.318.1.1.1.5.2.44 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Configure the time delay for reporting informational alarms (in seconds). | |||||||||||||||||||||
| SupsAdvConfigGreenMode | 1.3.6.1.4.1.318.1.1.1.5.2.45 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Enable/Disable UPS green mode feature.
| |||||||||||||||||||||
| SupsAdvConfigLCDLocalLanguage | 1.3.6.1.4.1.318.1.1.1.5.2.46 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Configure the language setting of the UPS LCD display information.
| |||||||||||||||||||||
| SupsAdvConfigLCDLockOut | 1.3.6.1.4.1.318.1.1.1.5.2.47 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Enable/Disable the control function of the UPS via the LCD Display.
| |||||||||||||||||||||
| SupsAdvConfigChargerRate | 1.3.6.1.4.1.318.1.1.1.5.2.48 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Change the maximum allowed UPS charge rate on select products where 100% represents the manufacturer's recommended rate. A charge/discharge rate of C/10 for a 10 Ah battery would be 1 where C is defined as the charge or discharge rate equal to the capacity of a battery divided by 1 hour. To increase the charge rate by a factor of 2 to C/5, this oid would be set to 200%. This number would not change when external packs are added or removed. Charging at too high a rate can result in boiling and/or venting of electrolyte and/or high gas pressure. | |||||||||||||||||||||
| SupsAdvConfigBatterySelection | 1.3.6.1.4.1.318.1.1.1.5.2.49 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Configure the installed battery type; VRLA is a Valve Regulated Lead Acid type battery, Vented Cell is a wet cell type (car) battery, NiCd is a Nickel-Cadmium type battery, and Li-Ion is Lithium Ion type battery. Please use the OID defined under upsIdent: upsAdvEnergyStorageType
| |||||||||||||||||||||
| SupsAdvConfigBatteryHealthAlarmWarningTime | 1.3.6.1.4.1.318.1.1.1.5.2.50 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Configure the number of days before the battery health is depleted that the battery health alarm is activated. Setting this to -1, if supported by the UPS, will suppress the battery health alarm. | |||||||||||||||||||||
| SupsAdvConfigBatteryHealthAlarmSleepTime | 1.3.6.1.4.1.318.1.1.1.5.2.51 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Configure the number of days that the UPS device's battery health alarm should sleep before being activated again after being acknowledged. Setting this to -1, if supported by the UPS, displays no other alarms after the first alarm is acknowledged. | |||||||||||||||||||||
| SupsAdvConfigSignalFlashVoltage | 1.3.6.1.4.1.318.1.1.1.5.2.52 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Configure the signal flash voltage in tenths of volts. | |||||||||||||||||||||
| SupsAdvConfigBatteryTemperatureCompensation | 1.3.6.1.4.1.318.1.1.1.5.2.53 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Configure the battery temperature compensation voltage in hundreds of volts per degree C. On products which support this field, the charger voltage is reduced for each degree C rise by the value configured in this setting multiplied by the number of battery cells attached to the UPS. | |||||||||||||||||||||
| SupsAdvConfigBatteryChargerType | 1.3.6.1.4.1.318.1.1.1.5.2.54 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory This OID describes type of battery charger used: standard or extended. 1 - Internal charger, 2 - Extended (CLA), 3 - Large extension (other cases), 4 - Extra large extension (XL), 5 - Double extra large extension (XXL) For other numbers charger type is unknown | |||||||||||||||||||||
| SupsAdvConfigAutomaticRestart | 1.3.6.1.4.1.318.1.1.1.5.2.55 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Indicates whether Automatic Restart is enabled or disabled.
| |||||||||||||||||||||
| SupsAdvConfigDeepDischargeProtection | 1.3.6.1.4.1.318.1.1.1.5.2.56 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Indicates whether protection against deep discharge is enabled or disabled.
| |||||||||||||||||||||
| SupsAdvConfigFreqBypassTransferRange | 1.3.6.1.4.1.318.1.1.1.5.2.57 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Tolerance of bypass AC frequency to switch on bypass. The frequency must be in range of -X% to +X% around the nominal value. | |||||||||||||||||||||
| SupsAdvConfigUpsPowerconverterType | 1.3.6.1.4.1.318.1.1.1.5.2.58 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory This value indicates the type of UPS in terms of output phase and redundancy. 2 - Galaxy 7000 Unitary 3:3 3 - Galaxy 7000 Redundant 3:3 4 - Galaxy 7000 Parallel SSC 3:3 6 - Galaxy 7000 SSC 3:3 10 - Galaxy 300 Unitary 3:3 11 - Galaxy 300 Unitary 3:1 12 - Galaxy 300 Redundant 3:3 13 - Galaxy 300 Redundant 3:1 14 - Galaxy 5000/5500 Unitary 15 - Galaxy 5000/5500 Parallel 16 - Galaxy 5000/5500 Unitary Frequency Converter 17 - Galaxy 5000/5500 Parallel Frequency Converter For other values UPS is unknown. | |||||||||||||||||||||
| SupsAdvConfigFrequencyConverterMode | 1.3.6.1.4.1.318.1.1.1.5.2.59 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Indicates whether the output frequency is in Auto Ranging or Frequency converter mode. In Auto Ranging mode the inverter provides output frequency in the same range as the input. In Frequency converter mode it is possible to have 50Hz input and 60 Hz output and vice versa.
| |||||||||||||||||||||
| SupsAdvConfigACQualificationTime | 1.3.6.1.4.1.318.1.1.1.5.2.60 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The time in seconds that the voltage is required to be in the acceptable range before being declared to be acceptable. | |||||||||||||||||||||
| SupsAdvConfigRebootDuration | 1.3.6.1.4.1.318.1.1.1.5.2.61 | TimeTicks | RW | mandatory | |||||||||||||||||
scalar · TimeTicks · read-write · mandatory During a reboot sequence, power is turned off and then back on. This OID defines the minimum amount of time to wait (seconds) after turning the power off, at the start of the sequence, before initiating the power on sequence. | |||||||||||||||||||||
| SupsAdvConfigAutoShutdownControlSkipOffDelay | 1.3.6.1.4.1.318.1.1.1.5.2.62 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Configures whether the UPS device's off delay setting (upsAdvConfigShutoffDelay) will be used for automatic shutdown.
| |||||||||||||||||||||
| SupsAdvConfigAutoShutdownControlAutoRestart | 1.3.6.1.4.1.318.1.1.1.5.2.63 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Configures whether the UPS will automatically restart after an automatic shutdown.
| |||||||||||||||||||||
| SupsAdvConfigAutoShutdownControlTimeOnBattery | 1.3.6.1.4.1.318.1.1.1.5.2.64 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Configures whether the UPS will turn off automatically after the UPS device's time on battery has exceeded the upsAdvConfigAutoShutdownTimeOnBattery OID setting.
| |||||||||||||||||||||
| SupsAdvConfigAutoShutdownControlRuntimeRemaining | 1.3.6.1.4.1.318.1.1.1.5.2.65 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Configures whether the UPS will turn off when the UPS is on battery and the remaining runtime is less than the upsAdvConfigAutoShutdownRuntimeRemaining OID setting.
| |||||||||||||||||||||
| SupsAdvConfigAutoShutdownTimeOnBattery | 1.3.6.1.4.1.318.1.1.1.5.2.66 | TimeTicks | RW | mandatory | |||||||||||||||||
scalar · TimeTicks · read-write · mandatory When the UPS has been on battery for more time than this value, the UPS will turn off if this condition is enabled by the upsAdvConfigAutoShutdownControlTimeOnBattery OID. | |||||||||||||||||||||
| SupsAdvConfigAutoShutdownRuntimeRemaining | 1.3.6.1.4.1.318.1.1.1.5.2.67 | TimeTicks | RW | mandatory | |||||||||||||||||
scalar · TimeTicks · read-write · mandatory When the UPS runtime remaining is less than this setting, the UPS will turn off if this condition is enabled by the upsAdvConfigAutoShutdownControlRuntimeRemaining OID. | |||||||||||||||||||||
| SupsAdvConfigHighLLTransferVolt | 1.3.6.1.4.1.318.1.1.1.5.2.68 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The maximum line to line voltage in VAC allowed before the UPS system transfers to battery backup. For a list of allowed values supported by your UPS model, see the UPS User's Manual. If a value other than a supported value is provided in a set request, the UPS interprets it as the next higher acceptable value. If the provided value is higher than the highest acceptable value, the highest acceptable value is used. | |||||||||||||||||||||
| SupsAdvConfigLowLLTransferVolt | 1.3.6.1.4.1.318.1.1.1.5.2.69 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The minimum line to line voltage in VAC allowed before the UPS system transfers to battery backup. For a list of allowed values supported by your UPS model, see the UPS User's Manual. If a value other than a supported value is provided in a set request, the UPS interprets it as the next lower acceptable value. If the provided value is lower than the lowest acceptable value, the lowest acceptable value is used. | |||||||||||||||||||||
| SupsAdvConfigHighBypassTransferVolt | 1.3.6.1.4.1.318.1.1.1.5.2.70 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The maximum line voltage, in VAC, that the UPS system will allow a transfer to bypass. | |||||||||||||||||||||
| SupsAdvConfigLowBypassTransferVolt | 1.3.6.1.4.1.318.1.1.1.5.2.71 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The minimum line voltage, in VAC, that the UPS system will allow a transfer to bypass. | |||||||||||||||||||||
| SupsAdvConfigHighBypassLLTransferVolt | 1.3.6.1.4.1.318.1.1.1.5.2.72 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The maximum line to line voltage, in VAC, that the UPS system will allow a transfer to bypass. | |||||||||||||||||||||
| SupsAdvConfigLowBypassLLTransferVolt | 1.3.6.1.4.1.318.1.1.1.5.2.73 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The minimum line to line voltage, in VAC, that the UPS system will allow a transfer to bypass. | |||||||||||||||||||||
| SupsAdvConfigAutoShutdownControlBatteryCapacity | 1.3.6.1.4.1.318.1.1.1.5.2.74 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory This setting only shuts down the UPS when the UPS is on battery and when the battery capacity is less than the upsAdvConfigAutoShutdownBatteryCapacity OID setting.
| |||||||||||||||||||||
| SupsAdvConfigAutoShutdownBatteryCapacity | 1.3.6.1.4.1.318.1.1.1.5.2.75 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory When the Battery capacity is less than this value, the UPS will turn off, if this condition is enabled by upsAdvConfigAutoShutdownControlBatteryCapacity OID setting. | |||||||||||||||||||||
| SupsAdvConfigAutoShutdownControlLoadPercentOnUps | 1.3.6.1.4.1.318.1.1.1.5.2.76 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory This setting only shuts down the UPS when the UPS is on battery and when the load percent on UPS is less than the upsAdvConfigAutoShutdownLoadPercentOnUps OID setting.
| |||||||||||||||||||||
| SupsAdvConfigAutoShutdownLoadPercentOnUps | 1.3.6.1.4.1.318.1.1.1.5.2.77 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory When the Load percent on UPS is less than this value, the UPS will turn off, if this condition is enabled by the upsAdvConfigAutoShutdownControlLoadPercentOnUps OID setting. | |||||||||||||||||||||
| SupsAdvConfigBypassFrequencyRangeLowerLimit | 1.3.6.1.4.1.318.1.1.1.5.2.78 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Lower Limit of Bypass Frequency Range in Hz. | |||||||||||||||||||||
| SupsAdvConfigBypassFrequencyRangeUpperLimit | 1.3.6.1.4.1.318.1.1.1.5.2.79 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Upper Limit of Bypass Frequency Range in Hz. | |||||||||||||||||||||
| SupsAdvConfigEcoVoltageRangeLowerLimit | 1.3.6.1.4.1.318.1.1.1.5.2.80 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Lower Limit of ECO Voltage Range in Volts. | |||||||||||||||||||||
| SupsAdvConfigEcoVoltageRangeUpperLimit | 1.3.6.1.4.1.318.1.1.1.5.2.81 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Upper Limit of ECO Voltage Range in Volts. | |||||||||||||||||||||
| NupsControl | 1.3.6.1.4.1.318.1.1.1.6 | ||||||||||||||||||||
| NupsBasicControl | 1.3.6.1.4.1.318.1.1.1.6.1 | ||||||||||||||||||||
| SupsBasicControlConserveBattery | 1.3.6.1.4.1.318.1.1.1.6.1.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Setting this variable to turnUpsOffToConserveBattery(2) causes a UPS on battery to be put into 'sleep' mode. The UPS will turn back on when utility power is restored. Attempting to turn off a UPS that is not on battery will result in a badValue error. Setting this value to noTurnOffUps(1) has no effect. The value noTurnOffUps(1) will always be returned when the variable is read.
| |||||||||||||||||||||
| NupsAdvControl | 1.3.6.1.4.1.318.1.1.1.6.2 | ||||||||||||||||||||
| SupsAdvControlUpsOff | 1.3.6.1.4.1.318.1.1.1.6.2.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Setting this variable to turnUpsOff(2) causes the UPS to shut off. When in this state, the UPS will not provide output power regardless of the input line state. Setting this variable to turnUpsOffGracefully(3) causes the UPS to shut off after a delay period. This allows the host to shut down in a graceful manner. When in this state, the UPS will not provide output power regardless of the input line state. If this UPS is an active member of a Synchronized Control Group (SCG) the turnUpsSyncGroupOff(4) command will perform a Synchronized Turn Off of all active Group members regardless of their current AC output status. If this UPS is an active member of a Synchronized Control Group (SCG) the turnUpsSyncGroupOffAfterDelay(5) command will perform a Synchronized Turn Off After Delay of all active Group members regardless of their current AC output status. This unit's Shutdown Delay will be used to execute the Turn Off After Delay command. If this UPS is an active member of an SCG, the turnUpsSyncGroupOffGracefully(6) command will perform a Synchronized Turn Off Gracefully of all active Group members regardless of their current AC output status. This unit's Maximum Shutdown Time and Shutdown Delay will be used to execute the Turn Off Gracefully command. Setting this value to noTurnUpsOff(1) has no effect. The value noTurnUpsOff(1) will always be returned when the variable is read.
| |||||||||||||||||||||
| SupsAdvControlRebootShutdownUps | 1.3.6.1.4.1.318.1.1.1.6.2.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Setting this variable to rebootShutdownUps(2) causes the UPS to shut off and turn back on (as long as good AC input power is available, otherwise the UPS will remain off until good AC input power is available). Setting this variable to rebootShutdownUpsGracefully(3) causes the UPS to shut off after a delay period and then turn back on. This allows the host to shut down in a graceful manner. If this UPS is an active member of a Synchronized Control Group (SCG) the rebootShutdownSyncGroupUps(4) command will perform a Synchronized Reboot of all active Group members regardless of their current AC output status. If applicable, this unit's Power Synchronization Delay, Shutdown Delay, Return Delay, Return Battery Capacity, and Return Battery Capacity Offset will be used to execute the Reboot command. If this UPS is an active member of a SCG the rebootShutdownSyncGroupUpsGracefully(5) command will perform a Synchronized Reboot of all active Group members regardless of their current AC output status. If applicable, this unit's Power Synchronization Delay, Maximum Shutdown Time, Shutdown Delay, Return Delay, Return Battery Capacity, and Return Battery Capacity Offset will be used to execute the Reboot command. Setting this value to noRebootShutdownUps(1) has no effect. The value noRebootShutdownUps(1) will always be returned when the variable is read.
| |||||||||||||||||||||
| SupsAdvControlUpsSleep | 1.3.6.1.4.1.318.1.1.1.6.2.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Setting this variable to putUpsToSleep(2) causes the UPS to go to sleep for the time specified by upsAdvConfigUpsSleepTime. Setting this variable to putUpsToSleepGracefully(3) causes the UPS to go to sleep for the time specified by upsAdvConfigUpsSleepTime after a delay period. This allows the host to shut down in a graceful manner. If this UPS is an active member of a Synchronized Control Group (SCG), the putUpsSyncGroupToSleep(4) command will perform a Synchronized Sleep of all active Group members regardless of their current AC output status. This unit's Power Synchronization Delay, Shutdown Delay, Sleep Time, and Return Delay will be used to execute the sleep command. If this UPS is an active member of a SCG the putUpsSyncGroupToSleepGracefully(5) command will perform a Synchronized Sleep Gracefully of all active Group members regardless of their current AC output status. This unit's Power Synchronization Delay, Maximum Shutdown Time, Shutdown Delay, Sleep Time, and Return Delay to execute the sleep command. When in sleep mode, the UPS will not provide output power regardless of the input line state. Once the specified time has elapsed, output power will be restored. Setting this value to noPutUpsToSleep(1) has no effect. The value noPutUpsToSleep(1) will always be returned when the variable is read.
| |||||||||||||||||||||
| SupsAdvControlSimulatePowerFail | 1.3.6.1.4.1.318.1.1.1.6.2.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Setting this variable to simulatePowerFailure(2) causes the UPS switch to battery power. Setting this value to noSimulatePowerFailure(1) has no effect. The value noSimulatePowerFailure(1) will always be returned when the variable is read.
| |||||||||||||||||||||
| SupsAdvControlFlashAndBeep | 1.3.6.1.4.1.318.1.1.1.6.2.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Setting this variable to flashAndBeep(2) causes the UPS to beep and simultaneously turn on the UPS front panel lights (Smart-UPS only). If this UPS is an active member of a Synchronized Control Group (SCG), the flashAndBeepSyncGroup(3) command will Flash and Beep all active Group members regardless of current AC output status. Setting this value to noFlashAndBeep(1) has no effect. Setting this value to flashAndBeepCont (4) commandcauses the UPS to beep and light the front panel lights until the flashAndBeepCancel (5) command is received. The value noFlashAndBeep(1) will always be returned when the variable is read.
| |||||||||||||||||||||
| SupsAdvControlTurnOnUPS | 1.3.6.1.4.1.318.1.1.1.6.2.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Setting this variable to turnOnUPS(2) causes the UPS to be turned on immediately. If this UPS is an active member of a Synchronized Control Group (SCG), the turnOnUPSSyncGroup(3) command will perform a Synchronized Turn On of all active Group members regardless of their current AC output status. Setting this variable to turnOnUPSDelayed(4) causes the UPS to be turned on after any set delays. Setting this value to noTurnOnUPS(1) has no effect. The value noTurnOnUPS(1) will always be returned when the variable is read.
| |||||||||||||||||||||
| SupsAdvControlBypassSwitch | 1.3.6.1.4.1.318.1.1.1.6.2.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory This switch puts the UPS in or out of bypass mode.
| |||||||||||||||||||||
| SupsAdvControlRebootUpsWithOrWithoutAC | 1.3.6.1.4.1.318.1.1.1.6.2.8 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Setting this variable to rebootUpsImmediatelyWithOrWithoutAC (2) causes the UPS to turn off immediately, wait for a minimum time (typically 8 seconds), and then turn back on regardless of the AC input power on the UPS. Any supported switched outlet groups will be turned off immediately but will turn on based on their individual settings (to allow on sequencing). Setting this variable to rebootUpsDelayedWithOrWithoutAC (3) causes the UPS to turn off after a delay period, wait for a minimum time (typically 8 seconds), and then turn back on regardless of the AC input power on the UPS. Any supported switched outlet groups will be turned off and on based on their individual settings (to allow off and/or on sequencing). Setting this value to noRebootUpsWithOrWithoutAC (1) has no effect. The value noRebootUpsWithOrWithoutAC (1) will always be returned when the variable is read.
| |||||||||||||||||||||
| SupsAdvControlFirmwareUpdate | 1.3.6.1.4.1.318.1.1.1.6.2.9 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Setting this variable to firmwareUpdate(2) causes the UPS to begin a firmware update if possible. Setting this value to noFirmwareUpdate(1) will clear the previous results, if any, or otherwise has no effect. Reading this variable will return noFirmwareUpdate(1) when the UPS firmware has not been updated (or previous results have been cleared), updateInProcess(3) when the UPS firmware is being updated, updateSuccessful(4) when the UPS firmware has been successfully updated, or updateFailed(5) if the UPS firmware update failed.
| |||||||||||||||||||||
| NupsTest | 1.3.6.1.4.1.318.1.1.1.7 | ||||||||||||||||||||
| NupsBasicTest | 1.3.6.1.4.1.318.1.1.1.7.1 | ||||||||||||||||||||
| NupsAdvTest | 1.3.6.1.4.1.318.1.1.1.7.2 | ||||||||||||||||||||
| SupsAdvTestDiagnosticSchedule | 1.3.6.1.4.1.318.1.1.1.7.2.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The UPS system's automatic battery test schedule.
| |||||||||||||||||||||
| SupsAdvTestDiagnostics | 1.3.6.1.4.1.318.1.1.1.7.2.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Setting this variable to testDiagnostics(2) causes the UPS to perform a diagnostic self test. Setting this value to noTestDiagnostics(1) has no effect. The value noTestDiagnostics(1) will always be returned when the variable is read.
| |||||||||||||||||||||
| SupsAdvTestDiagnosticsResults | 1.3.6.1.4.1.318.1.1.1.7.2.3 | INTEGER | RO | mandatory | invalidTest(3) | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The results of the last UPS diagnostics test performed.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SupsAdvTestLastDiagnosticsDate | 1.3.6.1.4.1.318.1.1.1.7.2.4 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The date the last UPS diagnostics test was performed in mm/dd/yy format. | |||||||||||||||||||||
| SupsAdvTestRuntimeCalibration | 1.3.6.1.4.1.318.1.1.1.7.2.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Setting this variable to performCalibration(2) causes the UPS to discharge to calibrate the UPS. The test will only start if the battery capacity is 100%. The test runs until capacity is less than 25%. Setting this variable to cancelCurrentCalibration(3) after setting performCalibration(2) will cancel the current discharge. Setting this variable to noPerformCalibration(1) will have no effect. The value noPerformCalibration(1) will always be returned when the variable is read. The result of the calibration will be saved in upsAdvTestCalibrationResult.
| |||||||||||||||||||||
| SupsAdvTestCalibrationResults | 1.3.6.1.4.1.318.1.1.1.7.2.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The results of the last runtime calibration. Value ok(1) means a successful runtime calibration. Value invalidCalibration(2) indicates last calibration did not take place since the battery capacity was below 100%. Value calibrationInProgress(3) means a calibration is occurring now. Value refused(4) means the test was refused, it did not take place. Value aborted(5) indicates the test started but either someone cancelled it or the system encountered an error. Value pending(6) the test will commence shortly.
| |||||||||||||||||||||
| SupsAdvTestCalibrationDate | 1.3.6.1.4.1.318.1.1.1.7.2.7 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The date the last UPS runtime calibration was performed in mm/dd/yy format. | |||||||||||||||||||||
| SupsAdvTestDiagnosticTime | 1.3.6.1.4.1.318.1.1.1.7.2.8 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory The time of the day to perform automatic battery test. Expressed in 24 hour notation - hh:mm. | |||||||||||||||||||||
| SupsAdvTestDiagnosticDay | 1.3.6.1.4.1.318.1.1.1.7.2.9 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The day of the week to perform automatic battery test.
| |||||||||||||||||||||
| SupsAdvTestBatteryInterval | 1.3.6.1.4.1.318.1.1.1.7.2.10 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory The UPS system's automatic battery test period. | |||||||||||||||||||||
| SupsAdvTestCalibrationLastSuccessfulDate | 1.3.6.1.4.1.318.1.1.1.7.2.11 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The latest date when the UPS performed a successful runtime calibration test. The format is YYYY-MM-DD | |||||||||||||||||||||
| SupsAdvTestBatteryLastSuccessfulDate | 1.3.6.1.4.1.318.1.1.1.7.2.12 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The latest date when the UPS performed a successful battery diagnostic test (battery monitoring test). The format is YYYY-MM-DD | |||||||||||||||||||||
| SupsAdvTestBatteryLastDate | 1.3.6.1.4.1.318.1.1.1.7.2.13 | DisplayString | RO | optional | |||||||||||||||||
scalar · DisplayString · read-only · optional The latest date when the UPS performed a battery diagnostic test (battery monitoring test), regardless of the test result.The format is YYYY-MM-DD. If not defined, return 2000-01-01 | |||||||||||||||||||||
| SupsAdvTestBatteryProcessStatus | 1.3.6.1.4.1.318.1.1.1.7.2.14 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The results of the latest battery diagnostic test (battery monitoring test). ok(1) indicates a successful completion of the test. preconditionNotMeet(2) indicates that the test did not start, due to low capacity or low load. batteryTestInProgress(3) indicates that a test is in progress. refused(4) indicates that the test was refused and did not take place. aborted(5) indicates that the test started but it was either cancelled or the system encountered an error. pending(6) the test will commence shortly. noBatteryPresent(8) indicates that no battery is present (no battery, battery breaker open, etc.) to perform the battery diagnostic test.
| |||||||||||||||||||||
| SupsAdvTestBatteryConditionStatus | 1.3.6.1.4.1.318.1.1.1.7.2.15 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Result of the latest successful test 1 = unknown 2 = battery OK 3 = battery capacity decreased 4 = battery defect 5 = indicate that no battery is present (no battery, battery breaker open,..) to perform the battery diagnostic test
| |||||||||||||||||||||
| SupsAdvTestDiagnosticsBatteryInterval | 1.3.6.1.4.1.318.1.1.1.7.2.16 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The battery test is a diagnostic test (also referred to as battery monitoring test). The test will be performed on the day stated in upsAdvTestDiagnosticDay and at the time stated in upsAdvTestDiagnosticTime. The result can be read in upsAdvTestBatteryConditionStatus. 1 = Never 2 = Weekly 3 = biweekly 4 = Every 4 weeks 5 = Every 8 weeks 6 = Every 12 weeks 7 = Every 26 weeks 8 = Every 52 weeks
| |||||||||||||||||||||
| NupsComm | 1.3.6.1.4.1.318.1.1.1.8 | ||||||||||||||||||||
| SupsCommStatus | 1.3.6.1.4.1.318.1.1.1.8.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The status of agent's communication with UPS.
| |||||||||||||||||||||
| NupsPhase | 1.3.6.1.4.1.318.1.1.1.9 | ||||||||||||||||||||
| NupsPhaseResetValues | 1.3.6.1.4.1.318.1.1.1.9.1 | ||||||||||||||||||||
| SupsPhaseResetMaxMinValues | 1.3.6.1.4.1.318.1.1.1.9.1.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Reset the maximum and minimum UPS values: upsPhaseInputMaxVoltage, upsPhaseInputMinVoltage, upsPhaseInputMaxCurrent, upsPhaseInputMinCurrent, upsPhaseInputMaxPower, upsPhaseInputMinPower, upsPhaseOutputMaxCurrent, upsPhaseOutputMinCurrent, upsPhaseOutputMaxLoad, upsPhaseOutputMinLoad, upsPhaseOutputMaxPercentLoad, upsPhaseOutputMinPercentLoad, upsPhaseOutputMaxPower, upsPhaseOutputMinPower, upsPhaseOutputMaxPercentPower, upsPhaseOutputMinPercentPower.
| |||||||||||||||||||||
| NupsPhaseInput | 1.3.6.1.4.1.318.1.1.1.9.2 | ||||||||||||||||||||
| SupsPhaseNumInputs | 1.3.6.1.4.1.318.1.1.1.9.2.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of input feeds to this device. This variable indicates the number of rows in the input table. | |||||||||||||||||||||
| TupsPhaseInputTable | 1.3.6.1.4.1.318.1.1.1.9.2.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of input table entries. The number of entries is given by the value of upsPhaseNumInputs. | |||||||||||||||||||||
| RupsPhaseInputEntry | 1.3.6.1.4.1.318.1.1.1.9.2.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular input. | |||||||||||||||||||||
| CupsPhaseInputTableIndex | 1.3.6.1.4.1.318.1.1.1.9.2.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The input identifier. | |||||||||||||||||||||
| CupsPhaseNumInputPhases | 1.3.6.1.4.1.318.1.1.1.9.2.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The number of input phases utilized in this device. The sum of all the upsPhaseNumInputPhases variable indicates the number of rows in the input phase table. | |||||||||||||||||||||
| CupsPhaseInputVoltageOrientation | 1.3.6.1.4.1.318.1.1.1.9.2.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The input voltage orientation: 1: unknown for this UPS 2: singlePhase - phase 1 voltage is between Phase 1 and Neutral. 3: splitPhase - phase 1 voltage is between Phase 1 and Neutral; phase 2 voltage is between Phase 2 and Neutral; phase 3 voltage is between Phase 1 and Phase 2. 4: threePhasePhaseToNeutral - phase 1 voltage is between Phase 1 and Neutral; phase 2 voltage is between Phase 2 and Neutral; phase 3 voltage is between Phase 3 and Neutral. 5: threePhasePhaseToPhase - phase 1 voltage is between Phase 1 and Phase 2; phase 2 voltage is between Phase 2 and Phase 3; phase 3 voltage is between Phase 3 and Phase 1.
| |||||||||||||||||||||
| CupsPhaseInputFrequency | 1.3.6.1.4.1.318.1.1.1.9.2.2.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The input frequency in 0.1 Hertz, or -1 if it's unsupported by this UPS. | |||||||||||||||||||||
| CupsPhaseInputType | 1.3.6.1.4.1.318.1.1.1.9.2.2.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The input type.
| |||||||||||||||||||||
| CupsPhaseInputName | 1.3.6.1.4.1.318.1.1.1.9.2.2.1.6 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory A name given to a particular input. | |||||||||||||||||||||
| TupsPhaseInputPhaseTable | 1.3.6.1.4.1.318.1.1.1.9.2.3 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of input table entries. The number of entries is given by the sum of the upsPhaseNumInputPhases. | |||||||||||||||||||||
| RupsPhaseInputPhaseEntry | 1.3.6.1.4.1.318.1.1.1.9.2.3.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular input phase. | |||||||||||||||||||||
| CupsPhaseInputPhaseTableIndex | 1.3.6.1.4.1.318.1.1.1.9.2.3.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The input identifier. | |||||||||||||||||||||
| CupsPhaseInputPhaseIndex | 1.3.6.1.4.1.318.1.1.1.9.2.3.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The input phase identifier. | |||||||||||||||||||||
| CupsPhaseInputVoltage | 1.3.6.1.4.1.318.1.1.1.9.2.3.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The input voltage in VAC, or -1 if it's unsupported by this UPS. | |||||||||||||||||||||
| CupsPhaseInputMaxVoltage | 1.3.6.1.4.1.318.1.1.1.9.2.3.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The maximum input voltage in VAC measured since the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds. | |||||||||||||||||||||
| CupsPhaseInputMinVoltage | 1.3.6.1.4.1.318.1.1.1.9.2.3.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The minimum input voltage in VAC measured since the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds. | |||||||||||||||||||||
| CupsPhaseInputCurrent | 1.3.6.1.4.1.318.1.1.1.9.2.3.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The input current in 0.1 amperes, or -1 if it's unsupported by this UPS. | |||||||||||||||||||||
| CupsPhaseInputMaxCurrent | 1.3.6.1.4.1.318.1.1.1.9.2.3.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The maximum input current in 0.1 amperes measured since the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds. | |||||||||||||||||||||
| CupsPhaseInputMinCurrent | 1.3.6.1.4.1.318.1.1.1.9.2.3.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The minimum input current in 0.1 amperes measured since the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds. | |||||||||||||||||||||
| CupsPhaseInputPower | 1.3.6.1.4.1.318.1.1.1.9.2.3.1.9 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The input power in Watts, or -1 if it's unsupported by this UPS. | |||||||||||||||||||||
| CupsPhaseInputMaxPower | 1.3.6.1.4.1.318.1.1.1.9.2.3.1.10 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The maximum input power in Watts measured since the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds. | |||||||||||||||||||||
| CupsPhaseInputMinPower | 1.3.6.1.4.1.318.1.1.1.9.2.3.1.11 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The minimum input power in Watts measured since the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds. | |||||||||||||||||||||
| CupsPhaseInputApparentPower | 1.3.6.1.4.1.318.1.1.1.9.2.3.1.12 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The input apparent power of the UPS in kVA. | |||||||||||||||||||||
| CupsPhaseInputPowerFactor | 1.3.6.1.4.1.318.1.1.1.9.2.3.1.13 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The input power factor measured in hundredth. | |||||||||||||||||||||
| CupsPhaseInputVoltagePN | 1.3.6.1.4.1.318.1.1.1.9.2.3.1.14 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The input voltage measured across Phase to Neutral in VAC, or -1 if it's unsupported by this UPS. | |||||||||||||||||||||
| NupsPhaseOutput | 1.3.6.1.4.1.318.1.1.1.9.3 | ||||||||||||||||||||
| SupsPhaseNumOutputs | 1.3.6.1.4.1.318.1.1.1.9.3.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of output feeds to this device. This variable indicates the number of rows in the output table. | |||||||||||||||||||||
| TupsPhaseOutputTable | 1.3.6.1.4.1.318.1.1.1.9.3.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of output table entries. The number of entries is given by the value of upsOutputNumPhases. | |||||||||||||||||||||
| RupsPhaseOutputEntry | 1.3.6.1.4.1.318.1.1.1.9.3.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular output. | |||||||||||||||||||||
| CupsPhaseOutputTableIndex | 1.3.6.1.4.1.318.1.1.1.9.3.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The output identifier. | |||||||||||||||||||||
| CupsPhaseNumOutputPhases | 1.3.6.1.4.1.318.1.1.1.9.3.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The number of output phases utilized in this device. The sum of all the upsPhaseNumOutputPhases variable indicates the number of rows in the output phase table. | |||||||||||||||||||||
| CupsPhaseOutputVoltageOrientation | 1.3.6.1.4.1.318.1.1.1.9.3.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The output voltage orientation: 1: unknown for this UPS 2: singlePhase - phase 1 voltage is between Phase 1 and Neutral. 3: splitPhase - phase 1 voltage is between Phase 1 and Neutral; phase 2 voltage is between Phase 2 and Neutral; phase 3 voltage is between Phase 1 and Phase 2. 4: threePhasePhaseToNeutral - phase 1 voltage is between Phase 1 and Neutral; phase 2 voltage is between Phase 2 and Neutral; phase 3 voltage is between Phase 3 and Neutral. 5: threePhasePhaseToPhase - phase 1 voltage is between Phase 1 and Phase 2; phase 2 voltage is between Phase 2 and Phase 3; phase 3 voltage is between Phase 3 and Phase 1.
| |||||||||||||||||||||
| CupsPhaseOutputFrequency | 1.3.6.1.4.1.318.1.1.1.9.3.2.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The output frequency in 0.1 Hertz, or -1 if it's unsupported by this UPS. | |||||||||||||||||||||
| TupsPhaseOutputPhaseTable | 1.3.6.1.4.1.318.1.1.1.9.3.3 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of output table entries. The number of entries is given by the sum of the upsPhaseNumOutputPhases. | |||||||||||||||||||||
| RupsPhaseOutputPhaseEntry | 1.3.6.1.4.1.318.1.1.1.9.3.3.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular output phase. | |||||||||||||||||||||
| CupsPhaseOutputPhaseTableIndex | 1.3.6.1.4.1.318.1.1.1.9.3.3.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The output identifier. | |||||||||||||||||||||
| CupsPhaseOutputPhaseIndex | 1.3.6.1.4.1.318.1.1.1.9.3.3.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The output phase identifier. | |||||||||||||||||||||
| CupsPhaseOutputVoltage | 1.3.6.1.4.1.318.1.1.1.9.3.3.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The output voltage in VAC, or -1 if it's unsupported by this UPS. | |||||||||||||||||||||
| CupsPhaseOutputCurrent | 1.3.6.1.4.1.318.1.1.1.9.3.3.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The output current in 0.1 amperes drawn by the load on the UPS, or -1 if it's unsupported by this UPS. | |||||||||||||||||||||
| CupsPhaseOutputMaxCurrent | 1.3.6.1.4.1.318.1.1.1.9.3.3.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The maximum output current in 0.1 amperes measured since the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds. | |||||||||||||||||||||
| CupsPhaseOutputMinCurrent | 1.3.6.1.4.1.318.1.1.1.9.3.3.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The minimum output current in 0.1 amperes measured since the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds. | |||||||||||||||||||||
| CupsPhaseOutputLoad | 1.3.6.1.4.1.318.1.1.1.9.3.3.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The output load in VA, or -1 if it's unsupported by this UPS. | |||||||||||||||||||||
| CupsPhaseOutputMaxLoad | 1.3.6.1.4.1.318.1.1.1.9.3.3.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The maximum output load in VA measured since the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds. | |||||||||||||||||||||
| CupsPhaseOutputMinLoad | 1.3.6.1.4.1.318.1.1.1.9.3.3.1.9 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The minimum output load in VA measured since the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds. | |||||||||||||||||||||
| CupsPhaseOutputPercentLoad | 1.3.6.1.4.1.318.1.1.1.9.3.3.1.10 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The percentage of the UPS load capacity in VA at redundancy @ (n + x) presently being used on this output phase, or -1 if it's unsupported by this UPS. | |||||||||||||||||||||
| CupsPhaseOutputMaxPercentLoad | 1.3.6.1.4.1.318.1.1.1.9.3.3.1.11 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The maximum percentage of the UPS load capacity in VA measured at redundancy @ (n + x) presently being used on this output phase since the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds. | |||||||||||||||||||||
| CupsPhaseOutputMinPercentLoad | 1.3.6.1.4.1.318.1.1.1.9.3.3.1.12 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The minimum percentage of the UPS load capacity in VA measured at redundancy @ (n + x) presently being used on this output phase since the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds. | |||||||||||||||||||||
| CupsPhaseOutputPower | 1.3.6.1.4.1.318.1.1.1.9.3.3.1.13 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The output power in Watts, or -1 if it's unsupported by this UPS. | |||||||||||||||||||||
| CupsPhaseOutputMaxPower | 1.3.6.1.4.1.318.1.1.1.9.3.3.1.14 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The maximum output power in Watts measured since the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds. | |||||||||||||||||||||
| CupsPhaseOutputMinPower | 1.3.6.1.4.1.318.1.1.1.9.3.3.1.15 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The minimum output power in Watts measured since the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds. | |||||||||||||||||||||
| CupsPhaseOutputPercentPower | 1.3.6.1.4.1.318.1.1.1.9.3.3.1.16 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The percentage of the UPS power capacity in Watts at redundancy @ (n + x) presently being used on this output phase, or -1 if it's unsupported by this UPS. | |||||||||||||||||||||
| CupsPhaseOutputMaxPercentPower | 1.3.6.1.4.1.318.1.1.1.9.3.3.1.17 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The maximum percentage of the UPS power capacity in Watts measured at redundancy @ (n + x) presently being used on this output phase since the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds. | |||||||||||||||||||||
| CupsPhaseOutputMinPercentPower | 1.3.6.1.4.1.318.1.1.1.9.3.3.1.18 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The maximum percentage of the UPS power capacity in Watts measured at redundancy @ (n + x) presently being used on this output phase since the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds. | |||||||||||||||||||||
| CupsPhaseOutputPowerFactor | 1.3.6.1.4.1.318.1.1.1.9.3.3.1.19 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The Output power factor of the UPS in hundredth. | |||||||||||||||||||||
| CupsPhaseOutputApparentPower | 1.3.6.1.4.1.318.1.1.1.9.3.3.1.20 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Apparent power in kVA | |||||||||||||||||||||
| CupsPhaseOutputInverterVoltage | 1.3.6.1.4.1.318.1.1.1.9.3.3.1.21 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Output voltage in VAC measured at the output of inverter. | |||||||||||||||||||||
| CupsPhaseOutputVoltagePN | 1.3.6.1.4.1.318.1.1.1.9.3.3.1.22 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The output voltage measured across Phase to Neutral in VAC, or -1 if it's unsupported by this UPS. | |||||||||||||||||||||
| CupsPhaseOutputEnergyUsage | 1.3.6.1.4.1.318.1.1.1.9.3.3.1.23 | Unsigned32 | RO | mandatory | |||||||||||||||||
column · Unsigned32 · read-only · mandatory The output energy usage of the phase in hundredths of kWh. | |||||||||||||||||||||
| NupsSyncCtrlGroup | 1.3.6.1.4.1.318.1.1.1.10 | ||||||||||||||||||||
| NupsSyncCtrlGroupConfig | 1.3.6.1.4.1.318.1.1.1.10.1 | ||||||||||||||||||||
| SupsSCGMembershipGroupNumber | 1.3.6.1.4.1.318.1.1.1.10.1.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The SCG Membership Group number (MGN) is a 16-bit number allowing up to 65534 separate groups that can be identified and distinguished per IP subnet. Zero and 65535 are not used. The MGN is used in all communication between members of the SCG and a Network Management Card (NMC) will listen and only respond to commands sent to it using its configured SCG ID. | |||||||||||||||||||||
| SupsSCGActiveMembershipStatus | 1.3.6.1.4.1.318.1.1.1.10.1.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Membership in the configured SCG can be enabled and disabled. If an NMC is configured for an SCG, but has its membership disabled, all synchronized control commands received will be ignored.
| |||||||||||||||||||||
| SupsSCGPowerSynchronizationDelayTime | 1.3.6.1.4.1.318.1.1.1.10.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The Power Synchronization Delay Time (PSD) setting is the maximum number of seconds an SCG Initiator will wait for all SCG members to recover utility power before completing the reboot sequence of a reboot or sleep command. If all SCG members are ready to proceed, no additional delay is introduced. | |||||||||||||||||||||
| SupsSCGReturnBatteryCapacityOffset | 1.3.6.1.4.1.318.1.1.1.10.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory A reboot command uses the Initiator's Return battery Capacity (RBC) to control when the SCG completes this operation. In a Normal Control Operation (NCC) the UPS will only complete the reboot if RBC is reached. Due to normal battery charge rate variations it may be desirable for the Followers to complete the reboot if they are within some range of the Initiator's RBC when the Initiator is prepared (charged to RBC) to complete the reboot. The Return Battery Capacity Offset (RBCO) defines a percent battery capacity subtracted from an RBC above which a Follower's battery must be charged for it to complete a reboot. For example, if the Initiator's RBC is 50% and the Initiator's RBCO is 5% then a Follower's battery capacity is within range if it is greater or equal to 45% (50% - 5%) at the time when the Initiator tries to complete the reboot command. The default RBCO is 10%. | |||||||||||||||||||||
| SupsSCGMultiCastIP | 1.3.6.1.4.1.318.1.1.1.10.1.5 | IpAddress | RW | mandatory | |||||||||||||||||
scalar · IpAddress · read-write · mandatory The MultiCast IP address of the SCG Group. | |||||||||||||||||||||
| NupsSyncCtrlGroupStatus | 1.3.6.1.4.1.318.1.1.1.10.2 | ||||||||||||||||||||
| SupsSCGNumOfGroupMembers | 1.3.6.1.4.1.318.1.1.1.10.2.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of active, communicating members in the Sync Control Group (SCG). This variable indicates the number of rows in the SCG Status Table. | |||||||||||||||||||||
| TupsSCGStatusTable | 1.3.6.1.4.1.318.1.1.1.10.2.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of SCG status table entries. The number of entries is given by the value of upsSCGNumOfGroupMembers. | |||||||||||||||||||||
| RupsSCGStatusEntry | 1.3.6.1.4.1.318.1.1.1.10.2.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular SCG Member. | |||||||||||||||||||||
| CupsSCGStatusTableIndex | 1.3.6.1.4.1.318.1.1.1.10.2.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of a status entry for an active, communicating SCG member. | |||||||||||||||||||||
| CupsSCGMemberIP | 1.3.6.1.4.1.318.1.1.1.10.2.2.1.2 | IpAddress | RO | mandatory | |||||||||||||||||
column · IpAddress · read-only · mandatory The IP address of an active, communicating SCG Member. | |||||||||||||||||||||
| CupsSCGACInputStatus | 1.3.6.1.4.1.318.1.1.1.10.2.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This OID indicates the AC Input Status of the SCG Member. acInGood(1) indicates the AC Input is within tolerance. acInBad(2) indicates the AC Input is not within tolerance.
| |||||||||||||||||||||
| CupsSCGACOutputStatus | 1.3.6.1.4.1.318.1.1.1.10.2.2.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This OID indicates the AC Output Status of the SCG Member. acOutOn(1) indicates the UPS output is providing power to the load. acOutOff(2) indicates the UPS output is not providing power to the load.
| |||||||||||||||||||||
| NupsState | 1.3.6.1.4.1.318.1.1.1.11 | ||||||||||||||||||||
| NupsBasicState | 1.3.6.1.4.1.318.1.1.1.11.1 | ||||||||||||||||||||
| SupsBasicStateOutputState | 1.3.6.1.4.1.318.1.1.1.11.1.1 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory An ASCII string containing the 64 flags representing the current state(s) of the UPS. If the Network Card is unable to determine the state of the UPS, this variable is set to 'UNKNOWN'. The flags are numbered 1 to 64, read from left to right. The flags are defined as follows: Flag 1: Abnormal Condition Present Flag 2: On Battery Flag 3: Low Battery Flag 4: On Line Flag 5: Replace Battery Flag 6: Serial Communication Established Flag 7: AVR Boost Active Flag 8: AVR Trim Active Flag 9: Overload Flag 10: Runtime Calibration Flag 11: Batteries Discharged Flag 12: Manual Bypass Flag 13: Software Bypass Flag 14: In Bypass due to Internal Fault Flag 15: In Bypass due to Supply Failure Flag 16: In Bypass due to Fan Failure Flag 17: Sleeping on a Timer Flag 18: Sleeping until Utility Power Returns Flag 19: On Flag 20: Rebooting Flag 21: Battery Communication Lost Flag 22: Graceful Shutdown Initiated Flag 23: Smart Boost or Smart Trim Fault Flag 24: Bad Output Voltage Flag 25: Battery Charger Failure Flag 26: High Battery Temperature Flag 27: Warning Battery Temperature Flag 28: Critical Battery Temperature Flag 29: Self Test In Progress Flag 30: Low Battery / On Battery Flag 31: Graceful Shutdown Issued by Upstream Device Flag 32: Graceful Shutdown Issued by Downstream Device Flag 33: No Batteries Attached Flag 34: Synchronized Command is in Progress Flag 35: Synchronized Sleeping Command is in Progress Flag 36: Synchronized Rebooting Command is in Progress Flag 37: Inverter DC Imbalance Flag 38: Transfer Relay Failure Flag 39: Shutdown or Unable to Transfer Flag 40: Low Battery Shutdown Flag 41: Electronic Unit Fan Failure Flag 42: Main Relay Failure Flag 43: Bypass Relay Failure Flag 44: Temporary Bypass Flag 45: High Internal Temperature Flag 46: Battery Temperature Sensor Fault Flag 47: Input Out of Range for Bypass Flag 48: DC Bus Overvoltage Flag 49: PFC Failure Flag 50: Critical Hardware Fault Flag 51: Green Mode/ECO Mode Flag 52: Hot Standby Flag 53: Emergency Power Off (EPO) Activated Flag 54: Load Alarm Violation Flag 55: Bypass Phase Fault Flag 56: UPS Internal Communication Failure Flag 57: Efficiency Booster Mode Flag 58: Off Flag 59: Standby Flag 60: Minor or Environment Alarm Flag 61: <Not Used> Flag 62: <Not Used> Flag 63: <Not Used> Flag 64: <Not Used> | |||||||||||||||||||||
| SupsBasicStateAlarmStatus | 1.3.6.1.4.1.318.1.1.1.11.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The alarm status of the Power Module. noAlarms(1) indicates the device has no alarms present. infoAlarm (2) indicates the device has alarms and the highest severity of the alarms present is infomational. warningAlarm (3) indicates the device has alarms and the highest severity of the alarms present is warning. criticalAlarm (4) indicates the device has alarms and the highest severity of the alarms present is critical.
| |||||||||||||||||||||
| NupsAdvState | 1.3.6.1.4.1.318.1.1.1.11.2 | ||||||||||||||||||||
| SupsAdvStateAbnormalConditions | 1.3.6.1.4.1.318.1.1.1.11.2.1 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory An ASCII string containing the 32 flags representing the current active UPS faults. If the Network Card is unable to determine the values of the flags, this variable is set to 'UNKNOWN'. If this variable is not supported by the connected UPS, this variable is set to 'NOT SUPPORTED'. The flags are numbered from 1 to 32, and read from left to right. The flags are defined as follows: Flag 1: Power Module Failure Flag 2: Main Intelligence Module Failure Flag 3: Redundant Intelligence Module Failure Flag 4: Battery Failure Flag 5: Load(kVA) Alarm Threshold Violation Flag 6: Redundancy Lost Flag 7: Redundancy Below Alarm Threshold Flag 8: Bypass not in Range; Either Frequency or Voltage Flag 9: Bypass Contactor Stuck in Bypass Condition Flag 10: Bypass Contactor Stuck in On-Line Condition Flag 11: In Bypass due to an Internal Fault Flag 12: In Bypass due to an Overload Flag 13: In Maintenance Bypass Flag 14: Input Circuit Breaker Tripped Open Flag 15: System Level Fan Failure Flag 16: Redundant Intelligent Module in Control Flag 17: IIC Inter-Module Communication Failure Flag 18: No Working Power Modules Flag 19: Load Shutdown From Bypass; Input Frequency Flag 20: Runtime Below Alarm Threshold Flag 21: Extended Run Frame Fault Flag 22: Output Voltage out of Range Flag 23: UPS Not Synchronized Flag 24: No Batteries Installed Flag 25: Battery Voltage High Flag 26: UPS Specific Fault Detected Flag 27: Site Wiring Fault Flag 28: Backfeed Protection Relay Opened Flag 29: EPO (Emergency Power Off) switch is activated Flag 30: UPS surveillance has detected a fault Flag 31: System overload detected or short circuit detected on the output Flag 32: Ambient temperature is out of tolerance | |||||||||||||||||||||
| SupsAdvStateSymmetra3PhaseSpecificFaults | 1.3.6.1.4.1.318.1.1.1.11.2.2 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory An ASCII string containing the 64 flags representing the current active UPS specific faults for the Symmetra 3-Phase UPS models. If the Network Card is unable to determine the values of the flags, this variable is set to 'UNKNOWN'. If the connected UPS does not use this variable, it is set to 'NOT SUPPORTED'. The flags are numbered from 1 to 64, and read from left to right. The bits are defined as follows: Flag 1: External Switch Gear Failure Flag 2: External Transformer Over Temperature Flag 3: External DC Circuit Breaker Tripped Flag 4: System Power Supply Failure Flag 5: Battery Monitor Card Failure Flag 6: Battery Monitor Card Removed Flag 7: XR Communication Card Failure Flag 8: XR Communication Card Removed Flag 9: External Switch Gear Monitoring Card Failure Flag 10: External Switch Gear Monitoring Card Removed Flag 11: Internal DC Circuit Breaker Tripped Flag 12: Static Bypass Switch Failure Flag 13: System EEPROM Removed Flag 14: System EEPROM Failure Flag 15: UPS in Forced Bypass Flag 16: Static Bypass Switch Module Removed Flag 17: System Start-Up Configuration Fault Flag 18: Battery Charger Shutdown Externally Flag 19: <Not Used> Flag 20: <Not Used> Flag 21: <Not Used> Flag 22: <Not Used> Flag 23: <Not Used> Flag 24: <Not Used> Flag 25: <Not Used> Flag 26: <Not Used> Flag 27: <Not Used> Flag 28: <Not Used> Flag 29: <Not Used> Flag 30: <Not Used> Flag 31: <Not Used> Flag 32: <Not Used> Flag 33: Cooling Fan Outage Alarm Flag 34: <Not Used> Flag 35: <Not Used> Flag 36: <Not Used> Flag 37: <Not Used> Flag 38: <Not Used> Flag 39: <Not Used> Flag 40: <Not Used> Flag 41: <Not Used> Flag 42: <Not Used> Flag 43: <Not Used> Flag 44: <Not Used> Flag 45: <Not Used> Flag 46: <Not Used> Flag 47: <Not Used> Flag 48: <Not Used> Flag 49: Bypass static switch communication error Flag 50: Bypass static switch error, module has a critical error Flag 51: <Not Used> Flag 52: <Not Used> Flag 53: <Not Used> Flag 54: <Not Used> Flag 55: <Not Used> Flag 56: <Not Used> Flag 57: <Not Used> Flag 58: <Not Used> Flag 59: <Not Used> Flag 60: <Not Used> Flag 61: <Not Used> Flag 62: <Not Used> Flag 63: <Not Used> Flag 64: <Not Used> | |||||||||||||||||||||
| SupsAdvStateDP300ESpecificFaults | 1.3.6.1.4.1.318.1.1.1.11.2.3 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory An ASCII string containing the 64 flags representing the current active UPS specific faults for the Silcon DP300E UPS models. If the Network Card is unable to determine the values of the flags, this variable is set to 'UNKNOWN'. If the connected UPS does not use this variable, it is set to 'NOT SUPPORTED'. The flags are numbered from 1 to 64, and read from left to right. The bits are defined as follows: Flag 1: Peak Current Limiter Active Flag 2: Bypass Power Supply Fault Flag 3: Delta Current Limiter Active Flag 4: Fan Fault Flag 5: High DC warning Flag 6: Inverter Voltage Error Flag 7: Parallel Synchronization Error Flag 8: Second Power Supply Fault Flag 9: Internal Power Supply Fault Flag 10: <Not Used> Flag 11: <Not Used> Flag 12: <Not Used> Flag 13: <Not Used> Flag 14: Bypass Static Switch High Temperature Flag 15: High Battery Temperature Flag 16: Battery Weak Flag 17: <Not Used> Flag 18: System Locked in Operation Mode Flag 19: RAM1 Memory Write Error Flag 20: Memory Write Error Flag 21: Communication to VQ Bypass Lost Flag 22: Communication to VQ Output Lost Flag 23: Communication to DMU Lost Flag 24: Communication to Controller Lost Flag 25: Communication to Parallel IF Lost Flag 26: External Shutdown Accepted Flag 27: DC Capacitor Charge Error Flag 28: Communication to VQ Mains Lost Flag 29: Bypass Synchronization Error Flag 30: Charge Error Flag 31: SII Aux Input Activiated Flag 32: <Not Used> Flag 33: Blown Inverter Fuse Flag 34: Blown Rectifier Fuse Flag 35: Auxilliary 1 Fault Flag 36: <Not Used> Flag 37: <Not Used> Flag 38: <Not Used> Flag 39: <Not Used> Flag 40: <Not Used> Flag 41: <Not Used> Flag 42: <Not Used> Flag 43: <Not Used> Flag 44: <Not Used> Flag 45: <Not Used> Flag 46: High Temperature Charger Magnetic Flag 47: <Not Used> Flag 48: Battery Monitor Warning Flag 49: Battery Monitor Alarm Flag 50: <Not Used> Flag 51: <Not Used> Flag 52: <Not Used> Flag 53: TSM 1/2/3 Temperature Shutdown Flag 54: Charger 0/30 Temperature Warning Flag 55: Charger 0/30 Temperature Shutdown Flag 56: High Output Voltage Flag 57: SSW Temperature Over 90 Flag 58: <Not Used> Flag 59: Low Current Failure In AC Capacitors Flag 60: <Not Used> Flag 61: Advanced Battery Management Not Installed Flag 62: <Not Used> Flag 63: <Not Used> Flag 64: <Not Used> | |||||||||||||||||||||
| SupsAdvStateSymmetraSpecificFaults | 1.3.6.1.4.1.318.1.1.1.11.2.4 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory An ASCII string containing the 64 flags representing the current active UPS specific faults for the Symmetra UPS models. If the Network Card is unable to determine the values of the flags, this variable is set to 'UNKNOWN'. If the connected UPS does not use this variable, it is set to 'NOT SUPPORTED'. The flags are numbered from 1 to 64, and read from left to right. The bits are defined as follows: Flag 1: System Fault Flag 2: Bypass Relay Fault Flag 3: Power Module Turn Off Failure Flag 4: Frame Identification Fault Flag 5: <Not Used> Flag 6: <Not Used> Flag 7: <Not Used> Flag 8: <Not Used> Flag 9: <Not Used> Flag 10: <Not Used> Flag 11: <Not Used> Flag 12: <Not Used> Flag 13: <Not Used> Flag 14: <Not Used> Flag 15: <Not Used> Flag 16: <Not Used> Flag 17: <Not Used> Flag 18: <Not Used> Flag 19: <Not Used> Flag 20: <Not Used> Flag 21: <Not Used> Flag 22: <Not Used> Flag 23: <Not Used> Flag 24: <Not Used> Flag 25: <Not Used> Flag 26: <Not Used> Flag 27: <Not Used> Flag 28: <Not Used> Flag 29: <Not Used> Flag 30: <Not Used> Flag 31: <Not Used> Flag 32: <Not Used> Flag 33: <Not Used> Flag 34: <Not Used> Flag 35: <Not Used> Flag 36: <Not Used> Flag 37: <Not Used> Flag 38: <Not Used> Flag 39: <Not Used> Flag 40: <Not Used> Flag 41: <Not Used> Flag 42: <Not Used> Flag 43: <Not Used> Flag 44: <Not Used> Flag 45: <Not Used> Flag 46: <Not Used> Flag 47: <Not Used> Flag 48: <Not Used> Flag 49: <Not Used> Flag 50: <Not Used> Flag 51: <Not Used> Flag 52: <Not Used> Flag 53: <Not Used> Flag 54: <Not Used> Flag 55: <Not Used> Flag 56: <Not Used> Flag 57: <Not Used> Flag 58: <Not Used> Flag 59: <Not Used> Flag 60: <Not Used> Flag 61: <Not Used> Flag 62: <Not Used> Flag 63: <Not Used> Flag 64: <Not Used> | |||||||||||||||||||||
| SupsAdvStateSmartUPSSpecificFaults | 1.3.6.1.4.1.318.1.1.1.11.2.5 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory An ASCII string containing the 64 flags representing the current active UPS specific faults for the Smart-UPS UPS models. If the Network Card is unable to determine the values of the flags, this variable is set to 'UNKNOWN'. If the connected UPS does not use this variable, it is set to 'NOT SUPPORTED'. The flags are numbered from 1 to 64, and read from left to right. The bits are defined as follows: Flag 1: EPO Switch Activated Flag 2: Static Bypass Switch Fault Flag 3: System Configuration Fault Flag 4: Power Supply Unit Fault Flag 5: Weak Battery Flag 6: High Battery Temperature Flag 7: Internal Mechanical Bypass Flag 8: Loss Of Parallel Redundancy Flag 9: Parallel Bus Communication Fault on Cable 1 Flag 10: Parallel Bus Communication Fault on Cable 2 Flag 11: Auxiliary Bus Communication Fault Flag 12: Parallel Bus Termination Fault on Cable 1 Flag 13: Parallel Bus Termination Fault on Cable 2 Flag 14: Auxiliary Bus Termination Fault Flag 15: No Master Present In The Parallel System Flag 16: Overload on a Parallel Unit Flag 17: Parallel Configuration Fault Flag 18: <Not Used> Flag 19: <Not Used> Flag 20: <Not Used> Flag 21: <Not Used> Flag 22: <Not Used> Flag 23: <Not Used> Flag 24: <Not Used> Flag 25: <Not Used> Flag 26: <Not Used> Flag 27: <Not Used> Flag 28: <Not Used> Flag 29: <Not Used> Flag 30: <Not Used> Flag 31: <Not Used> Flag 32: <Not Used> Flag 33: <Not Used> Flag 34: <Not Used> Flag 35: <Not Used> Flag 36: <Not Used> Flag 37: <Not Used> Flag 38: <Not Used> Flag 39: <Not Used> Flag 40: <Not Used> Flag 41: <Not Used> Flag 42: <Not Used> Flag 43: <Not Used> Flag 44: <Not Used> Flag 45: <Not Used> Flag 46: <Not Used> Flag 47: <Not Used> Flag 48: <Not Used> Flag 49: <Not Used> Flag 50: <Not Used> Flag 51: <Not Used> Flag 52: <Not Used> Flag 53: <Not Used> Flag 54: <Not Used> Flag 55: <Not Used> Flag 56: <Not Used> Flag 57: <Not Used> Flag 58: <Not Used> Flag 59: <Not Used> Flag 60: <Not Used> Flag 61: <Not Used> Flag 62: <Not Used> Flag 63: <Not Used> Flag 64: <Not Used> | |||||||||||||||||||||
| SupsAdvStateSystemMessages | 1.3.6.1.4.1.318.1.1.1.11.2.6 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory An ASCII string containing the 3 digit Decimal code representing the current active message from the System Message Register. Each code should remain active for a minimum of 15 seconds. However, in the worst case scenario, a code could be cleared after only 5 seconds. It is recommended that this object be polled at least once every 4 seconds in order to get the most accurate representation of the current UPS System Message. If the Network Card is unable to determine the value of the System Message Register, this variable is set to 'UNKNOWN'. | |||||||||||||||||||||
| SupsAdvStateTotaltimeonbattery | 1.3.6.1.4.1.318.1.1.1.11.2.7 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory Total time the UPS has been in battery operation. | |||||||||||||||||||||
| SupsAdvStateTotaltimeonbypass | 1.3.6.1.4.1.318.1.1.1.11.2.8 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory Total time the UPS has been in bypass operation. | |||||||||||||||||||||
| SupsAdvStateTotaltimeonNormal | 1.3.6.1.4.1.318.1.1.1.11.2.9 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory Total time the UPS has been in normal operation. | |||||||||||||||||||||
| SupsAdvStateNumberoftimesonbattery | 1.3.6.1.4.1.318.1.1.1.11.2.10 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Number of times the UPS was on battery. Since the last reset of statistical data. | |||||||||||||||||||||
| SupsAdvStateNumberoftimesbypass | 1.3.6.1.4.1.318.1.1.1.11.2.11 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Number of times the UPS was in bypass. Since the last reset of statistical data. | |||||||||||||||||||||
| SupsAdvStateNumberoftimesNormal | 1.3.6.1.4.1.318.1.1.1.11.2.12 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Number of times the UPS was in normal operation. Since the last reset of statistical data. | |||||||||||||||||||||
| SupsAdvStateEcomode | 1.3.6.1.4.1.318.1.1.1.11.2.13 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Eco mode status. 1: UPS is on Eco-mode 2: UPS is not on Eco-mode.
| |||||||||||||||||||||
| SupsAdvStateLifeCycleManagement | 1.3.6.1.4.1.318.1.1.1.11.2.14 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory An ASCII string containing the 16 flags representing the life cycle management alerts for the device. If the Network Card is unable to determine the values of the flags, this variable is set to 'UNKNOWN'. If the connected UPS does not use this variable, it is set to 'NOT SUPPORTED'. The flags are numbered from 1 to 16, and read from left to right. The bits are defined as follows: Flag 1: End of Warranty Soon Flag 2: Battery Check Recommended Flag 3: Service Period On Wearing Parts Expired Flag 4: Secure Start-up Recommended Flag 5: Fan Life Expired Flag 6: DC Capacitor Life Expired Flag 7: AC Capacitor Life Expired Flag 8: Supply Service Life Expired Flag 9: Ups Out Of Limits Warning Flag 10: Air Filter Life Expired Flag 11: <Not Used> Flag 12: <Not Used> Flag 13: <Not Used> Flag 14: <Not Used> Flag 15: <Not Used> Flag 16: <Not Used> | |||||||||||||||||||||
| SupsAdvStateGalaxyVseriesSpecificFault | 1.3.6.1.4.1.318.1.1.1.11.2.15 | DisplayString | RO | optional | |||||||||||||||||
scalar · DisplayString · read-only · optional An ASCII string containing 32 flags representing current active faults on a Galaxy V series UPS. The upsAdvStateAbnormalConditions OID shall be used to report active faults as per its description. Additional fault information shall be provided through the upsAdvStateGalaxyVseriesSpecificFault OID. If the Network Card is unable to determine the values of the flags, this variable is set to 'UNKNOWN'. If this variable is not supported by the connected UPS, this variable is set to 'NOT SUPPORTED'. The flags are numbered from 1 to 32, and read from left to right. The flags are defined as follows: Flag 1: Input voltage is out of tolerance Flag 2: Input frequency is out of tolerance Flag 3: External sync frequency is out of tolerance Flag 4: Output frequency is out of tolerance Flag 5: The static bypass switch needs a technical check but is still fully operational Flag 6: Static bypass switch is inoperable. UPS is prevented from going into static bypass operation Flag 7: PBUS cable 1 may be damaged Flag 8: PBUS cable 2 may be damaged Flag 9: The parallel system is not configured correctly or is not working correctly Flag 10: The UC in the controller box is not working correctly Flag 11: Power module surveillance detected a fault Flag 12: The SLC in the controller box is not working correctly Flag 13: No SBS present Flag 14: No power module(s) present Flag 15: Controller box disabled Flag 16: Display communication lost - disconnected Flag 17: The energy storage surveillance has detected a battery temperature above shutdown limit Flag 18: Modular battery cabinet fuse blown Flag 19: Battery module temperature sensor not working correctly Flag 20: The energy storage surveillance has detected a battery discharge current above shutdown limit Flag 21: Ground fault detected Flag 22: External energy storage monitoring: Minor alarm Flag 23: External energy storage monitoring: Major alarm Flag 24: Temperature of input and/or output transformer is too high Flag 25: Parallel breaker status inconsistency detected Flag 26: UC communication lost - disconnected Flag 27: PMC communication lost - disconnected Flag 28: NMC communication lost - disconnected Flag 29: BMC communication lost - disconnected Flag 30: <Reserved> Flag 31: <Reserved> Flag 32: <Reserved> | |||||||||||||||||||||
| SupsAdvStateGutorModularSpecificFaults | 1.3.6.1.4.1.318.1.1.1.11.2.16 | DisplayString | RO | optional | |||||||||||||||||
scalar · DisplayString · read-only · optional An ASCII string containing the 64 flags representing the current active Charger Rectifier and UPS specific faults for Gutor Modular models. Flag allocation: Flag 1 to 16 for breakers status (Charger Rectifier + UPS). 16 Flags Flag 17 to 32 for module errors. 16 Flags Flag 33 to 44 For charger errors. 12 Flags Flag 45 to 54 for battery errors. 10 flags Flag 55 to 64 for temperature errors. 10 flags If the Network Card is unable to determine the values of the flags, this variable is set to 'UNKNOWN'. If the connected UPS does not use this variable, it is set to 'NOT SUPPORTED'. The flags are numbered from 1 to 64 and read from left to right. The bits are defined as follows: Breaker (16 signals) Flag 1: Rectifier AC mains breaker 1 is OPEN Flag 2: Battery breaker 1 is OPEN Flag 3: Rectifier DC output breaker is OPEN Flag 4: PSU redundancy lost Flag 5: DC distribution feeder is OPEN Flag 6: Surge protection device is OPEN Flag 7: Option input 1 is ACTIVE Flag 8: Emergency power OFF is ACTIVE Flag 9: Inverter DC input breaker is OPEN Flag 10: Bypass AC mains breaker is OPEN Flag 11: System AC output breaker is OPEN Flag 12: AC distribution feeder is OPEN Flag 13: Rectifier AC mains breaker 2 is OPEN Flag 14: Battery breaker 2 is OPEN Flag 15: <Not Used> Flag 16: Roof fan disturbance is ACTIVE Flag 1 to Flag 16 should be accessible for device type charger, inverter and UPS Charger modules (16 signals) Flag 17: < 1431 - Module configuration mismatch > Flag 18: < 1433 - Load sharing error (All power modules) > Flag 19: < 1435 - Fan fault (All power modules) > Flag 20: < 1437 - Output voltage out of range (All power modules) > Flag 21: < 1436 - Input voltage out of range (All power modules) > Flag 22: < 1504 - System switched off > Flag 23: < 1513 - Warning address reserve > Flag 24: < 1514 - Address reserve error > Flag 25: < 1515 - Power reserve error > Flag 26: <Not Used> Flag 27: <Not Used> Flag 28: <Not Used> Flag 29: <Not Used> Flag 30: <Not Used> Flag 31: <Not Used> Flag 32: <Not Used> ALL (12 signals) Flag 33: < 6 - Common Alarm > Flag 34: < 7 - Urgent incident > Flag 35: < 8 - Non-urgent alarm > Flag 36: < 9 - HMI-MCU Com. Error > Flag 37: < 1428 - Equalization charge blocked > Flag 38: < 1432 - Boost charge blocked > Flag 39: < 1440 - High DC warning > Flag 40: < 1441 - High DC shutdown > Flag 41: < 1442 - Low DC warning > Flag 42: < 1443 - Low DC shutdown > Flag 43: <Not Used> Flag 44: <Not Used> Battery (10 signals) Flag 45: < 11 - Battery symmetry fault > Flag 46: < 1429 - Battery current limitation active > Flag 47: < 1430 - Battery current limitation configuration error > Flag 48: < 1512 - Battery temperature sensor defective > Flag 49: <Not Used> Flag 50: <Not Used> Flag 51: <Not Used> Flag 52: <Not Used> Flag 53: <Not Used> Flag 54: <Not Used> Temperature (10 signals) Flag 55: < 1444 - MCU temperature too high > Flag 56: <Not Used> Flag 57: <Not Used> Flag 58: <Not Used> Flag 59: <Not Used> Flag 60: <Not Used> Flag 61: <Not Used> Flag 62: <Not Used> Flag 63: <Not Used> Flag 64: <Not Used> | |||||||||||||||||||||
| NupsOutletGroups | 1.3.6.1.4.1.318.1.1.1.12 | ||||||||||||||||||||
| NupsOutletGroupStatus | 1.3.6.1.4.1.318.1.1.1.12.1 | ||||||||||||||||||||
| SupsOutletGroupStatusTableSize | 1.3.6.1.4.1.318.1.1.1.12.1.1 | INTEGER | RO | mandatory | 2 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of outlet groups for the UPS. Example values from LibreNMS test devices
| |||||||||||||||||||||
| TupsOutletGroupStatusTable | 1.3.6.1.4.1.318.1.1.1.12.1.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting status of the outlet groups. The number of entries is contained in the upsOutletGroupStatusTableSize OID. | |||||||||||||||||||||
| RupsOutletGroupStatusEntry | 1.3.6.1.4.1.318.1.1.1.12.1.2.1 | NA | mandatory | ||||||||||||||||||
| CupsOutletGroupStatusIndex | 1.3.6.1.4.1.318.1.1.1.12.1.2.1.1 | INTEGER | RO | mandatory | 1 | ||||||||||||||||
column · INTEGER · read-only · mandatory The index to the outlet group entry. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CupsOutletGroupStatusName | 1.3.6.1.4.1.318.1.1.1.12.1.2.1.2 | DisplayString | RO | mandatory | UPS Outlets | ||||||||||||||||
column · DisplayString · read-only · mandatory The name of the outlet group. This OID is provided for informational purposes only. This value is set by the upsOutletGroupConfigName OID. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CupsOutletGroupStatusGroupState | 1.3.6.1.4.1.318.1.1.1.12.1.2.1.3 | INTEGER | RO | mandatory | upsOutletGroupStatusOn(1) | ||||||||||||||||
column · INTEGER · read-only · mandatory Getting this variable will return the outlet group state. If the outlet group is on, the upsOutletGroupStatusOn (1) value will be returned. If the outlet group is off, the upsOutletGroupStatusOff (2) value will be returned. If the state of the outlet group cannot be determined, the upsOutletGroupStatusUnknown (3) value will be returned.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CupsOutletGroupStatusCommandPending | 1.3.6.1.4.1.318.1.1.1.12.1.2.1.4 | INTEGER | RO | mandatory | upsOutletGroupNoCommandPending(2) | ||||||||||||||||
column · INTEGER · read-only · mandatory Getting this variable will return the command pending state of the outlet group. If a command is pending on the outlet group, the upsOutletGroupCommandPending (1) value will be returned. If there is not a command pending on the outlet group, the upsOutletGroupNoCommandPending (2) will be returned.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CupsOutletGroupStatusOutletType | 1.3.6.1.4.1.318.1.1.1.12.1.2.1.5 | INTEGER | RO | mandatory | upsMainOutletGroup(2) | ||||||||||||||||
column · INTEGER · read-only · mandatory Getting this variable will return the type of outlet group. If present in the system, the main outlet group is 'unswitched' and must be on in order for any of the switched outlet groups to be on. Conversely, if the main outlet group is off, all the switched outlet groups must also be off. Therefore, any commands made to the main outlet group that turn it off will also be applied to all switched outlet groups that are on, unless the state of a switched outlet group prevents it, in which case the command will fail.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CupsOutletGroupStatusGroupFullState | 1.3.6.1.4.1.318.1.1.1.12.1.2.1.6 | DisplayString | RO | mandatory | 1000000000000000000000000000000 | ||||||||||||||||
column · DisplayString · read-only · mandatory An ASCII string containing the 32 flags representing the current state(s) of the outlet group. If the Network Card is unable to determine the state of the outlet group, this variable is set to 'UNKNOWN'. The flags are numbered from 1 to 32, and read from left to right. The flags are defined as follows: Flag 1: On Flag 2: Off Flag 3: Reboot in Progress Flag 4: Shutdown in Progress Flag 5: Sleep in Progress Flag 6: <Not Used> Flag 7: <Not Used> Flag 8: Pending Load Shed Flag 9: Pending On Delay Flag 10: Pending Off Delay Flag 11: Pending AC Presence Flag 12: Pending On Minimum Runtime Flag 13: Member Group Process 1 Flag 14: Member Group Process 2 Flag 15: Runtime Below Turn On Setting Flag 16: <Not Used> Flag 17: <Not Used> Flag 18: <Not Used> Flag 19: <Not Used> Flag 20: <Not Used> Flag 21: <Not Used> Flag 22: <Not Used> Flag 23: <Not Used> Flag 24: <Not Used> Flag 25: <Not Used> Flag 26: <Not Used> Flag 27: <Not Used> Flag 28: <Not Used> Flag 29: <Not Used> Flag 30: <Not Used> Flag 31: <Not Used> Flag 32: <Not Used> Example values from LibreNMS test devices
| |||||||||||||||||||||
| NupsOutletGroupConfig | 1.3.6.1.4.1.318.1.1.1.12.2 | ||||||||||||||||||||
| SupsOutletGroupConfigTableSize | 1.3.6.1.4.1.318.1.1.1.12.2.1 | INTEGER | RO | mandatory | 2 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of outlet groups for the UPS. Example values from LibreNMS test devices
| |||||||||||||||||||||
| TupsOutletGroupConfigTable | 1.3.6.1.4.1.318.1.1.1.12.2.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory The list of outlet groups to configure. The number of entries is defined by the upsOutletGroupConfigTableSize OID. | |||||||||||||||||||||
| RupsOutletGroupConfigEntry | 1.3.6.1.4.1.318.1.1.1.12.2.2.1 | NA | mandatory | ||||||||||||||||||
| CupsOutletGroupConfigIndex | 1.3.6.1.4.1.318.1.1.1.12.2.2.1.1 | INTEGER | RO | mandatory | 1 | ||||||||||||||||
column · INTEGER · read-only · mandatory The index to the outlet group entry. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CupsOutletGroupConfigName | 1.3.6.1.4.1.318.1.1.1.12.2.2.1.2 | DisplayString | RW | mandatory | UPS Outlets | ||||||||||||||||
column · DisplayString · read-write · mandatory The name of the outlet group. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CupsOutletGroupConfigPowerOnDelay | 1.3.6.1.4.1.318.1.1.1.12.2.2.1.3 | INTEGER | RW | mandatory | 0 | ||||||||||||||||
column · INTEGER · read-write · mandatory The amount of time (seconds) the outlet group will delay powering on when the delayed on, reboot, or shutdown command is applied. Allowed values vary by UPS model. The value of -1 is used for Never if supported by the UPS and the outlet group. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CupsOutletGroupConfigPowerOffDelay | 1.3.6.1.4.1.318.1.1.1.12.2.2.1.4 | INTEGER | RW | mandatory | 0 | ||||||||||||||||
column · INTEGER · read-write · mandatory The amount of time (seconds) the outlet group will delay powering off when the delayed off, reboot, or shutdown command is applied. Allowed values vary by UPS model. The value of -1 is used for Never if supported by the UPS and the outlet group. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CupsOutletGroupConfigRebootDuration | 1.3.6.1.4.1.318.1.1.1.12.2.2.1.5 | INTEGER | RW | mandatory | 8 | ||||||||||||||||
column · INTEGER · read-write · mandatory During a reboot sequence, power is turned off and then back on. This OID defines the amount of time to wait (seconds) after turning the power off, at the start of the sequence, before initiating the power on sequence. Allowed values vary by UPS model. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CupsOutletGroupConfigMinReturnRuntime | 1.3.6.1.4.1.318.1.1.1.12.2.2.1.6 | INTEGER | RW | mandatory | 0 | ||||||||||||||||
column · INTEGER · read-write · mandatory In an Outlet Group shutdown sequence, the Outlet Group cycles power off then on. This OID defines the minimum amount of UPS runtime (seconds) that is required in order to power the Outlet Group on. Allowed values vary by UPS model. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CupsOutletGroupConfigOutletType | 1.3.6.1.4.1.318.1.1.1.12.2.2.1.7 | INTEGER | RO | mandatory | upsMainOutletGroup(2) | ||||||||||||||||
column · INTEGER · read-only · mandatory Getting this variable will return the type of outlet group. If present in the system, the main outlet group is 'unswitched' and must be on in order for any of the switched outlet groups to be on. Conversely, if the main outlet group is off, all the switched outlet groups must also be off. Therefore, any commands made to the main outlet group that turn it off will also be applied to all switched outlet groups that are on, unless the state of a switched outlet group prevents it, in which case the command will fail.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CupsOutletGroupConfigLoadShedControlSkipOffDelay | 1.3.6.1.4.1.318.1.1.1.12.2.2.1.8 | INTEGER | RW | mandatory | upsOutletGroupConfigSkipOffDelay(1) | ||||||||||||||||
column · INTEGER · read-write · mandatory Configures whether the outlet group's off delay setting (upsOutletGroupConfigPowerOffDelay) will be used in a load shedding situation, where applicable.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CupsOutletGroupConfigLoadShedControlAutoRestart | 1.3.6.1.4.1.318.1.1.1.12.2.2.1.9 | INTEGER | RW | mandatory | upsOutletGroupConfigAutoRestart(1) | ||||||||||||||||
column · INTEGER · read-write · mandatory Configures whether the outlet group will automatically restart after a load shedding situation, where applicable.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CupsOutletGroupConfigLoadShedControlTimeOnBattery | 1.3.6.1.4.1.318.1.1.1.12.2.2.1.10 | INTEGER | RW | mandatory | upsOutletGroupConfigDisableTimeOnBatteryLoadShe… | ||||||||||||||||
column · INTEGER · read-write · mandatory Configures whether the outlet group will load shed (turn off) after the UPS device's time on battery has exceeded the upsOutletGroupConfigLoadShedTimeOnBattery OID setting. The settings for upsOutletGroupConfigLoadShedControlSkipOffDelay and upsOutletGroupConfigLoadShedControlAutoRestart are valid for this load shed condition.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CupsOutletGroupConfigLoadShedControlRuntimeRemaining | 1.3.6.1.4.1.318.1.1.1.12.2.2.1.11 | INTEGER | RW | mandatory | upsOutletGroupConfigDisableRuntimeRemainingLoad… | ||||||||||||||||
column · INTEGER · read-write · mandatory Configures whether the outlet group will load shed (turn off) when the UPS is on battery and the remaining runtime is less than the upsOutletGroupConfigLoadShedRuntimeRemaining OID setting. The settings for upsOutletGroupConfigLoadShedControlSkipOffDelay and upsOutletGroupConfigLoadShedControlAutoRestart are valid for this load shed condition.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CupsOutletGroupConfigLoadShedControlInOverload | 1.3.6.1.4.1.318.1.1.1.12.2.2.1.12 | INTEGER | RW | mandatory | -1 | ||||||||||||||||
column · INTEGER · read-write · mandatory Configures whether the outlet group will load shed (turn off) when the UPS is in an overload condition. The setting for upsOutletGroupConfigLoadShedControlSkipOffDelay is valid for this load shed condition. Returns -1 if not supported by this outlet group.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CupsOutletGroupConfigLoadShedTimeOnBattery | 1.3.6.1.4.1.318.1.1.1.12.2.2.1.13 | INTEGER | RW | mandatory | 32767 | ||||||||||||||||
column · INTEGER · read-write · mandatory When the UPS has been on battery for more time than this value, the outlet group will turn off if this condition is enabled by the upsOutletGroupConfigLoadShedControlTimeOnBattery OID. Allowed values vary by UPS model. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CupsOutletGroupConfigLoadShedRuntimeRemaining | 1.3.6.1.4.1.318.1.1.1.12.2.2.1.14 | INTEGER | RW | mandatory | 0 | ||||||||||||||||
column · INTEGER · read-write · mandatory When the runtime remaining is less than this value, the outlet group will turn off if this condition is enabled by the upsOutletGroupConfigLoadShedControlRuntimeRemaining OID. Allowed values vary by UPS model. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NupsOutletGroupControl | 1.3.6.1.4.1.318.1.1.1.12.3 | ||||||||||||||||||||
| SupsOutletGroupControlTableSize | 1.3.6.1.4.1.318.1.1.1.12.3.1 | INTEGER | RO | mandatory | 2 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of outlet groups for the UPS. Example values from LibreNMS test devices
| |||||||||||||||||||||
| TupsOutletGroupControlTable | 1.3.6.1.4.1.318.1.1.1.12.3.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for control of individual outlet groups. The number of entries is contained in the upsOutletGroupControlTableSize OID. | |||||||||||||||||||||
| RupsOutletGroupControlEntry | 1.3.6.1.4.1.318.1.1.1.12.3.2.1 | NA | mandatory | ||||||||||||||||||
| CupsOutletGroupControlIndex | 1.3.6.1.4.1.318.1.1.1.12.3.2.1.1 | INTEGER | RO | mandatory | 1 | ||||||||||||||||
column · INTEGER · read-only · mandatory The index to the outlet group entry. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CupsOutletGroupControlName | 1.3.6.1.4.1.318.1.1.1.12.3.2.1.2 | DisplayString | RO | mandatory | UPS Outlets | ||||||||||||||||
column · DisplayString · read-only · mandatory The name of the outlet group. This OID is provided for informational purposes only. This value is set by the upsOutletGroupConfigName OID. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CupsOutletGroupControlCommand | 1.3.6.1.4.1.318.1.1.1.12.3.2.1.3 | INTEGER | RW | mandatory | upsOutletGroupImmediateOn(1) | ||||||||||||||||
column · INTEGER · read-write · mandatory Getting this variable will return the outlet group state. If the outlet group is on, the upsOutletGroupImmediateOn (1) value will be returned. If the outlet group is off, the upsOutletGroupImmediateOff (2) value will be returned. If the state of the outlet group cannot be determined, the upsOutletGroupControlUnknown (8) value will be returned. Setting this variable to upsOutletGroupImmediateOn (1) will turn the outlet group on immediately. Setting this variable to upsOutletGroupImmediateOff (2) will turn the outlet group off immediately. Setting this variable to upsOutletGroupImmediateRebootWithOrWithoutAC (3) will turn the outlet group off immediately, wait the upsOutletGroupConfigRebootDuration OID time, wait the upsOutletGroupConfigPowerOnDelay OID, and then turn the outlet group on regardless of the AC input power on the UPS. Setting this variable to upsOutletGroupDelayedOn (4) will turn the outlet group on after the upsOutletGroupConfigPowerOnDelay OID has elapsed. Setting this variable to upsOutletGroupDelayedOff (5) will turn the outlet group off after the upsOutletGroupConfigPowerOffDelay OID has elapsed. Setting this variable to upsOutletGroupDelayedRebootWithOrWithoutAC (6) will turn the outlet group off after the upsOutletGroupConfigPowerOffDelay OID has elapsed, wait the upsOutletGroupConfigRebootDuration OID time, wait the upsOutletGroupConfigPowerOnDelay OID, and then turn the outlet group on regardless of the AC input power on the UPS. Setting this variable to upsOutletGroupCancelPendingCommand (7) will cause any pending command to this outlet group to be canceled. Setting this variable to upsOutletGroupImmediateRebootShutdown (9) will turn the outlet group off immediately, wait for the AC power to return to normal (a minimum of the upsOutletGroupConfigRebootDuration OID time), wait the upsOutletGroupConfigPowerOnDelay OID time, and then turn the outlet group on. Setting this variable to upsOutletGroupDelayedRebootShutdown (10) will turn the outlet group off after the upsOutletGroupConfigPowerOffDelay OID has elapsed, wait for the AC power to return to normal (a minimum of the upsOutletGroupConfigRebootDuration OID time), wait the upsOutletGroupConfigPowerOnDelay OID time, and then turn the outlet group on. In systems with a main outlet group, commands to the main outlet group must be performed with caution. It may be clearer to use the ups control commands available from upsAdvControl... OIDs. If any command is made to the main outlet group that will turn it off, one of two things will happen: 1) If any switched outlet group is in a state that prevents this command from occurring on the main outlet group, the command will be rejected. Note that a switched outlet group being on without a command in progress is not a state that normally prevents the command. 2) The command will be accepted and applied to the main outlet group and all switched outlet groups that are on. There is one additional special case for systems with a main outlet group. If the main outlet group is off and a switched outlet group is commanded to turn on, the on command will be applied to both the main outlet group and that switched outlet group.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CupsOutletGroupControlOutletType | 1.3.6.1.4.1.318.1.1.1.12.3.2.1.4 | INTEGER | RO | mandatory | upsMainOutletGroup(2) | ||||||||||||||||
column · INTEGER · read-only · mandatory Getting this variable will return the type of outlet group. If present in the system, the main outlet group is 'unswitched' and must be on in order for any of the switched outlet groups to be on. Conversely, if the main outlet group is off, all the switched outlet groups must also be off. Therefore, any commands made to the main outlet group that turn it off will also be applied to all switched outlet groups that are on, unless the state of a switched outlet group prevents it, in which case the command will fail.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NupsDiagnostics | 1.3.6.1.4.1.318.1.1.1.13 | ||||||||||||||||||||
| NupsDiagnosticIM | 1.3.6.1.4.1.318.1.1.1.13.1 | ||||||||||||||||||||
| SupsDiagIMTableSize | 1.3.6.1.4.1.318.1.1.1.13.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of Intelligence Modules in or attached to the UPS. | |||||||||||||||||||||
| TupsDiagIMTable | 1.3.6.1.4.1.318.1.1.1.13.1.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for diagnostics of individual Intelligence Modules. The number of entries is contained in the upsDiagIMTableSize OID. | |||||||||||||||||||||
| RupsDiagIMEntry | 1.3.6.1.4.1.318.1.1.1.13.1.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The diagnostics and information of an Intelligence Module.
| |||||||||||||||||||||
| CupsDiagIMIndex | 1.3.6.1.4.1.318.1.1.1.13.1.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the Intelligence Module entry. | |||||||||||||||||||||
| CupsDiagIMType | 1.3.6.1.4.1.318.1.1.1.13.1.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The type of the Intelligence Module. imUnknown(1) indicates the IM type is unknown. imMIM(2) indicates the IM type is a Main Intelligence Module. imRIM(3) indicates the IM type is Redundant Intelligence Module.
| |||||||||||||||||||||
| CupsDiagIMStatus | 1.3.6.1.4.1.318.1.1.1.13.1.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The status of the Intelligence Module. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the device status is off and OK. onOk(4) indicates the device status is on and OK. offFail(5) indicates the device status is off and failed. onFail(6) indicates the device status is on and failed. lostComm(7) indicates the device has lost communication.
| |||||||||||||||||||||
| CupsDiagIMFirmwareRev | 1.3.6.1.4.1.318.1.1.1.13.1.2.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The firmware revision of the Intelligence Module. | |||||||||||||||||||||
| CupsDiagIMSlaveFirmwareRev | 1.3.6.1.4.1.318.1.1.1.13.1.2.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The slave firmware revision of the Intelligence Module. | |||||||||||||||||||||
| CupsDiagIMHardwareRev | 1.3.6.1.4.1.318.1.1.1.13.1.2.1.6 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The hardware revision of the Intelligence Module. | |||||||||||||||||||||
| CupsDiagIMSerialNum | 1.3.6.1.4.1.318.1.1.1.13.1.2.1.7 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The serial number of the Intelligence Module. | |||||||||||||||||||||
| CupsDiagIMManufactureDate | 1.3.6.1.4.1.318.1.1.1.13.1.2.1.8 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The manufacture date of the Intelligence Module. | |||||||||||||||||||||
| CupsDiagIMInControl | 1.3.6.1.4.1.318.1.1.1.13.1.2.1.9 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The Intelligence Module state. activeInControl(1) indicates the IM is active and in control. passive(2) indicates the IM is in passive state. unknown(3) indicates the IM is in unknown state. fault(4) indicates the IM is in fault state.
| |||||||||||||||||||||
| CupsDiagIMSKU | 1.3.6.1.4.1.318.1.1.1.13.1.2.1.10 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The SKU of the Intelligence Module. | |||||||||||||||||||||
| NupsDiagnosticPowerModules | 1.3.6.1.4.1.318.1.1.1.13.2 | ||||||||||||||||||||
| SupsDiagPMTableSize | 1.3.6.1.4.1.318.1.1.1.13.2.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The maximum number of Power Modules supported by the UPS. | |||||||||||||||||||||
| TupsDiagPMTable | 1.3.6.1.4.1.318.1.1.1.13.2.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for diagnostics of Individual Power modules. The number of entries is contained in the upsDiagPMTableSize OID. | |||||||||||||||||||||
| RupsDiagPMEntry | 1.3.6.1.4.1.318.1.1.1.13.2.2.1 | NA | mandatory | ||||||||||||||||||
| CupsDiagPMIndex | 1.3.6.1.4.1.318.1.1.1.13.2.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the Power Module entry. | |||||||||||||||||||||
| CupsDiagPMStatus | 1.3.6.1.4.1.318.1.1.1.13.2.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The status of the Power Module. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the device status is off and OK. onOk(4) indicates the device status is on and OK. offFail(5) indicates the device status is off and failed. onFail(6) indicates the device status is on and failed. lostComm(7) indicates the device has lost communication.
| |||||||||||||||||||||
| CupsDiagPMFirmwareRev | 1.3.6.1.4.1.318.1.1.1.13.2.2.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The firmware revision of the Power Module. | |||||||||||||||||||||
| CupsDiagPMHardwareRev | 1.3.6.1.4.1.318.1.1.1.13.2.2.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The hardware revision of the Power Module. | |||||||||||||||||||||
| CupsDiagPMSerialNum | 1.3.6.1.4.1.318.1.1.1.13.2.2.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The serial number of the Power Module. | |||||||||||||||||||||
| CupsDiagPMManufactureDate | 1.3.6.1.4.1.318.1.1.1.13.2.2.1.6 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The manufacture date of the Power Module. | |||||||||||||||||||||
| CupsDiagPMModelNum | 1.3.6.1.4.1.318.1.1.1.13.2.2.1.7 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The model number of the Power Module. | |||||||||||||||||||||
| CupsDiagPMRating | 1.3.6.1.4.1.318.1.1.1.13.2.2.1.8 | DisplayString | RO | optional | |||||||||||||||||
column · DisplayString · read-only · optional The power rating (in kVA) of the Power Module | |||||||||||||||||||||
| CupsDiagPMSKU | 1.3.6.1.4.1.318.1.1.1.13.2.2.1.9 | DisplayString | RO | optional | |||||||||||||||||
column · DisplayString · read-only · optional The SKU of the Power Module | |||||||||||||||||||||
| CupsDiagPMAverageFanSpeed | 1.3.6.1.4.1.318.1.1.1.13.2.2.1.10 | INTEGER | RO | optional | |||||||||||||||||
column · INTEGER · read-only · optional The average fan speed of the working fans in the Power Module in revolutions per minute (RPM). Returns (-1) if not set. | |||||||||||||||||||||
| CupsDiagPMAmbientTemperature | 1.3.6.1.4.1.318.1.1.1.13.2.2.1.11 | INTEGER | RO | optional | |||||||||||||||||
column · INTEGER · read-only · optional The ambient temperature inside the Power Module in tenths of degrees celsius. If not available, this variable is set to (-1999). | |||||||||||||||||||||
| TupsDiagPMLifetimeInfoTable | 1.3.6.1.4.1.318.1.1.1.13.2.3 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for diagnostics of individual power module's lifetime information. The number of entries is contained in the upsDiagPMTableSize OID. | |||||||||||||||||||||
| RupsDiagPMLifetimeInfoEntry | 1.3.6.1.4.1.318.1.1.1.13.2.3.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The diagnostics of a Power Module lifetime information. | |||||||||||||||||||||
| CupsDiagPMLifetimeInfoIndex | 1.3.6.1.4.1.318.1.1.1.13.2.3.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the Power Module lifetime information entry. | |||||||||||||||||||||
| CupsDiagPMLifetimeStatus | 1.3.6.1.4.1.318.1.1.1.13.2.3.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The status of the Power Module lifetime information. ok(1) indicates the device lifetime status is OK. nearEnd(2) indicates the device lifetime status is near end. exceeded(3) indicates the device lifetime status is exceeded. unknown(4) indicates the device lifetime status is unknown.
| |||||||||||||||||||||
| CupsDiagPMEstmtdLifetimeRmng | 1.3.6.1.4.1.318.1.1.1.13.2.3.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Displays the time remaining for the module before it should be replaced. Measured in months. This value is set when you originally install the module. | |||||||||||||||||||||
| CupsDiagPMEstmtdLifetimeRmngPct | 1.3.6.1.4.1.318.1.1.1.13.2.3.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Displays the percentage of the total lifetime remaining for the module before it should be replaced. | |||||||||||||||||||||
| CupsDiagPMFanLifetimeStatus | 1.3.6.1.4.1.318.1.1.1.13.2.3.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The status of the Power Module Fan lifetime information. ok(1) indicates the device lifetime status is OK. nearEnd(2) indicates the device lifetime status is near end. exceeded(3) indicates the device lifetime status is exceeded. unknown(4) indicates the device lifetime status is unknown.
| |||||||||||||||||||||
| CupsDiagPMFanEstmtdLifetimeRmng | 1.3.6.1.4.1.318.1.1.1.13.2.3.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Displays the time remaining, measured in months, before the module's fan should be replaced. It is reset by the field service engineer when a new fan is installed. | |||||||||||||||||||||
| CupsDiagPMFanEstmtdLifetimeRmngPct | 1.3.6.1.4.1.318.1.1.1.13.2.3.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Displays the percentage of the total lifetime remaining before the module's fan should be replaced. | |||||||||||||||||||||
| SupsDiagPMEnclDoorFltrTableSize | 1.3.6.1.4.1.318.1.1.1.13.2.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The maximum number of power module enclosures attached to the UPS. | |||||||||||||||||||||
| TupsDiagPMEnclDoorFltrTable | 1.3.6.1.4.1.318.1.1.1.13.2.5 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for the diagnostics of individual power module enclosure door filters. The number of entries is contained in the upsDiagPMEnclDoorFltrTableSize OID. | |||||||||||||||||||||
| RupsDiagPMEnclDoorFltrEntry | 1.3.6.1.4.1.318.1.1.1.13.2.5.1 | NA | mandatory | ||||||||||||||||||
| CupsDiagPMEnclIndex | 1.3.6.1.4.1.318.1.1.1.13.2.5.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the power module enclosure entry. Enclosure 0 indicates the Power enclosure 1. Enclosure 1 indicates the Power enclosure 2. | |||||||||||||||||||||
| CupsDiagPMEnclDoorFltrLifetime | 1.3.6.1.4.1.318.1.1.1.13.2.5.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Door filter replacement time interval, based on the installation enivironment. heavyFiltration15days (1) indicates door filter needs to be replaced within 15 days. normalFiltration30days (2) indicates door filter needs to be replaced within 30 days. lightFiltration60days (3) indicates door filter needs to be replaced within 60 days. notPresent(4) indicates that the door filter is not present.
| |||||||||||||||||||||
| CupsDiagPMEnclDoorFltrStatus | 1.3.6.1.4.1.318.1.1.1.13.2.5.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Indicates the current status of the door filter. ok(1) indicates the device lifetime status is OK. nearEnd(2) indicates the device lifetime status is near end. exceeded(3) indicates the device lifetime status is exceeded. unknown(4) indicates the device lifetime status is unknown.
| |||||||||||||||||||||
| CupsDiagPMEnclDoorFltrEstmtdLifetimeRmng | 1.3.6.1.4.1.318.1.1.1.13.2.5.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Displays the time remaining, measured in days, before the module door filter should be replaced. This value is set when you originally install the module. | |||||||||||||||||||||
| CupsDiagPMEnclDoorFltrEstmtdLifetimeRmngPct | 1.3.6.1.4.1.318.1.1.1.13.2.5.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Displays the percentage of the total lifetime remaining for the module door filter before it should be replaced. | |||||||||||||||||||||
| NupsDiagnosticBatteries | 1.3.6.1.4.1.318.1.1.1.13.3 | ||||||||||||||||||||
| SupsDiagBatteryTableSize | 1.3.6.1.4.1.318.1.1.1.13.3.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The maximum number of batteries supported by the UPS. | |||||||||||||||||||||
| TupsDiagBatteryTable | 1.3.6.1.4.1.318.1.1.1.13.3.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for diagnostics of individual batteries. The number of entries is contained in the upsDiagBattTableSize OID. | |||||||||||||||||||||
| RupsDiagBatteryEntry | 1.3.6.1.4.1.318.1.1.1.13.3.2.1 | NA | mandatory | ||||||||||||||||||
| CupsDiagBatteryFrameIndex | 1.3.6.1.4.1.318.1.1.1.13.3.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the battery frame entry. Frame 0 indicates the Main frame. Extended Run (XR) frames start from index 1. | |||||||||||||||||||||
| CupsDiagBatteryIndex | 1.3.6.1.4.1.318.1.1.1.13.3.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the battery entry. | |||||||||||||||||||||
| CupsDiagBatteryStatus | 1.3.6.1.4.1.318.1.1.1.13.3.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The status of the battery. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. ok(3) indicates the battery status is OK. failed(4) indicates the battery status is failed. highTemperature(5) indicates the battery has a high temperature condition. replaceImmediately(6) indicates the battery must be replaced immediately. lowCapacity(7) indicates the battery has a low capacity.
| |||||||||||||||||||||
| CupsDiagBatterySerialNumber | 1.3.6.1.4.1.318.1.1.1.13.3.2.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The serial number of the battery. | |||||||||||||||||||||
| CupsDiagBatteryFirmwareRev | 1.3.6.1.4.1.318.1.1.1.13.3.2.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The firmware revision of the battery. | |||||||||||||||||||||
| CupsDiagBatteryManufactureDate | 1.3.6.1.4.1.318.1.1.1.13.3.2.1.6 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The manufacture date of the battery. | |||||||||||||||||||||
| CupsDiagBatteryType | 1.3.6.1.4.1.318.1.1.1.13.3.2.1.7 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The battery type or rating for the battery. | |||||||||||||||||||||
| CupsDiagBatteryFramePresent | 1.3.6.1.4.1.318.1.1.1.13.3.2.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The battery frame/cabinet status. 0 indicates frame/cabinet is not present. 1 indicates frame/cabinet is present.
| |||||||||||||||||||||
| CupsDiagBatteryFrameTemperature | 1.3.6.1.4.1.318.1.1.1.13.3.2.1.9 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The battery frame/cabinet temperature in tenths of degrees celsius. If the frame/cabinet is not present, this variable is set to (-1). | |||||||||||||||||||||
| CupsDiagBatterySKU | 1.3.6.1.4.1.318.1.1.1.13.3.2.1.10 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The SKU of the battery. | |||||||||||||||||||||
| CupsDiagBatteryHealth | 1.3.6.1.4.1.318.1.1.1.13.3.2.1.11 | OCTET STRING | RO | mandatory | |||||||||||||||||
column · OCTET STRING · read-only · mandatory The battery health. bit 0 Battery lifetime okay bit 1 Battery lifetime near end, order replacement module bit 2 Battery lifetime exceeded, replace battery bit 3 Battery lifetime near end acknowledged, order replacement module bit 4 Battery lifetime exceeded acknowledged, replace battery bit 5 Battery measured lifetime near end, order replacement module bit 6 Battery measured lifetime near end acknowledged, order replacement module | |||||||||||||||||||||
| SupsDiagBatteryFrameTableSize | 1.3.6.1.4.1.318.1.1.1.13.3.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The maximum number of battery frames supported by the UPS. | |||||||||||||||||||||
| TupsDiagBatteryFrameTable | 1.3.6.1.4.1.318.1.1.1.13.3.4 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for diagnostics of individual battery frame. The number of entries is contained in the upsDiagBatteryFrameTableSize OID. | |||||||||||||||||||||
| RupsDiagBatteryFrameEntry | 1.3.6.1.4.1.318.1.1.1.13.3.4.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The diagnostics of a battery frame. | |||||||||||||||||||||
| CupsDiagBatteryFrameTableIndex | 1.3.6.1.4.1.318.1.1.1.13.3.4.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the battery frame entry. | |||||||||||||||||||||
| CupsDiagBatteryModuleStatusPerFrame | 1.3.6.1.4.1.318.1.1.1.13.3.4.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory An ASCII string containing the 64 flags representing the status of battery modules. 1 indicates battery module installed, 0 indicates battery module not installed. The flags are numbered from 1 to 64, and read from left to right. The flags are defined as follows: Flag 1: Battery Module Level 1 A Flag 2: Battery Module Level 1 B Flag 3: Battery Module Level 1 C Flag 4: Battery Module Level 1 D Flag 5: Battery Module Level 1 E Flag 6: Battery Module Level 1 F Flag 7: Battery Module Level 2 A Flag 8: Battery Module Level 2 B Flag 9: Battery Module Level 2 C Flag 10: Battery Module Level 2 D Flag 11: Battery Module Level 2 E Flag 12: Battery Module Level 2 F Flag 13: Battery Module Level 3 A Flag 14: Battery Module Level 3 B Flag 15: Battery Module Level 3 C Flag 16: Battery Module Level 3 D Flag 17: Battery Module Level 3 E Flag 18: Battery Module Level 3 F Flag 19: Battery Module Level 4 A Flag 20: Battery Module Level 4 B Flag 21: Battery Module Level 4 C Flag 22: Battery Module Level 4 D Flag 23: Battery Module Level 4 E Flag 24: Battery Module Level 4 F Flag 25: Battery Module Level 7 A Flag 26: Battery Module Level 7 B Flag 27: Battery Module Level 7 C Flag 28: Battery Module Level 7 D Flag 29: Battery Module Level 7 E Flag 30: Battery Module Level 7 F Flag 31: Battery Module Level 8 A Flag 32: Battery Module Level 8 B Flag 33: Battery Module Level 8 C Flag 34: Battery Module Level 8 D Flag 35: Battery Module Level 8 E Flag 36: Battery Module Level 8 F Flag 37: Battery Module Level 9 A Flag 38: Battery Module Level 9 B Flag 39: Battery Module Level 9 C Flag 40: Battery Module Level 9 D Flag 41: Battery Module Level 9 E Flag 42: Battery Module Level 9 F Flag 43: Battery Module Level 10 A Flag 44: Battery Module Level 10 B Flag 45: Battery Module Level 10 C Flag 46: Battery Module Level 10 D Flag 47: Battery Module Level 10 E Flag 48: Battery Module Level 10 F Flag 49: <Not Used> Flag 50: <Not Used> Flag 51: <Not Used> Flag 52: <Not Used> Flag 53: <Not Used> Flag 54: <Not Used> Flag 55: <Not Used> Flag 56: <Not Used> Flag 57: <Not Used> Flag 58: <Not Used> Flag 59: <Not Used> Flag 60: <Not Used> Flag 61: <Not Used> Flag 62: <Not Used> Flag 63: <Not Used> Flag 64: <Not Used> | |||||||||||||||||||||
| CupsDiagBatteryPositiveVoltage | 1.3.6.1.4.1.318.1.1.1.13.3.4.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The battery positive voltage, in Volts. | |||||||||||||||||||||
| CupsDiagBatteryNegativeVoltage | 1.3.6.1.4.1.318.1.1.1.13.3.4.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The battery negative voltage, in Volts. | |||||||||||||||||||||
| CupsDiagBatteryTemperature | 1.3.6.1.4.1.318.1.1.1.13.3.4.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The battery frame/cabinet temperature in tenths of degrees celsius. If the frame/cabinet is not present, this variable is set to (-1). | |||||||||||||||||||||
| NupsDiagnosticSubsystem | 1.3.6.1.4.1.318.1.1.1.13.4 | ||||||||||||||||||||
| SupsDiagSubSysFrameTableSize | 1.3.6.1.4.1.318.1.1.1.13.4.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of frames attached to the UPS including the Main frame. | |||||||||||||||||||||
| TupsDiagSubSysFrameTable | 1.3.6.1.4.1.318.1.1.1.13.4.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for diagnostics of individual XR Frames. | |||||||||||||||||||||
| RupsDiagSubSysFrameEntry | 1.3.6.1.4.1.318.1.1.1.13.4.2.1 | NA | mandatory | ||||||||||||||||||
| CupsDiagSubSysFrameIndex | 1.3.6.1.4.1.318.1.1.1.13.4.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The frame index entry. | |||||||||||||||||||||
| CupsDiagSubSysFrameType | 1.3.6.1.4.1.318.1.1.1.13.4.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The type of Frame. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. frameTypeMain(3) indicates the frame type is the Main Frame. frameTypeXR(4) indicates the frame type is an XR Frame. frameTypeLXR(5) indicates the frame type is an LXR Frame.
| |||||||||||||||||||||
| CupsDiagSubSysFrameFirmwareRev | 1.3.6.1.4.1.318.1.1.1.13.4.2.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The firmware revision of the frame. | |||||||||||||||||||||
| CupsDiagSubSysFrameHardwareRev | 1.3.6.1.4.1.318.1.1.1.13.4.2.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The hardware revision of the frame. | |||||||||||||||||||||
| CupsDiagSubSysFrameSerialNum | 1.3.6.1.4.1.318.1.1.1.13.4.2.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The serial number of the frame. | |||||||||||||||||||||
| CupsDiagSubSysFrameManufactureDate | 1.3.6.1.4.1.318.1.1.1.13.4.2.1.6 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The manufacture date of the frame. | |||||||||||||||||||||
| CupsDiagSubSysFrameSKU | 1.3.6.1.4.1.318.1.1.1.13.4.2.1.7 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The SKU of the frame. | |||||||||||||||||||||
| SupsDiagSubSysIntBypSwitchTableSize | 1.3.6.1.4.1.318.1.1.1.13.4.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of Internal Bypass switches attached to the UPS. | |||||||||||||||||||||
| TupsDiagSubSysIntBypSwitchTable | 1.3.6.1.4.1.318.1.1.1.13.4.4 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for diagnostics of the Internal Bypass Switch. | |||||||||||||||||||||
| RupsDiagSubSysIntBypSwitchEntry | 1.3.6.1.4.1.318.1.1.1.13.4.4.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The diagnostics of the Internal Bypass Switch. | |||||||||||||||||||||
| CupsDiagSubSysIntBypSwitchFrameIndex | 1.3.6.1.4.1.318.1.1.1.13.4.4.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The frame index entry. | |||||||||||||||||||||
| CupsDiagSubSysIntBypSwitchIndex | 1.3.6.1.4.1.318.1.1.1.13.4.4.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The Internal Bypass Switch index entry. | |||||||||||||||||||||
| CupsDiagSubSysIntBypSwitchStatus | 1.3.6.1.4.1.318.1.1.1.13.4.4.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The Internal Bypass Switch status. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the device status is off and OK. onOk(4) indicates the device status is on and OK. offFail(5) indicates the device status is off and failed. onFail(6) indicates the device status is on and failed. lostComm(7) indicates the device has lost communication.
| |||||||||||||||||||||
| CupsDiagSubSysIntBypSwitchFirmwareRev | 1.3.6.1.4.1.318.1.1.1.13.4.4.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The firmware revision of the Internal Bypass Switch. | |||||||||||||||||||||
| CupsDiagSubSysIntBypSwitchHardwareRev | 1.3.6.1.4.1.318.1.1.1.13.4.4.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The hardware revision of the Internal Bypass Switch. | |||||||||||||||||||||
| CupsDiagSubSysIntBypSwitchSerialNum | 1.3.6.1.4.1.318.1.1.1.13.4.4.1.6 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The serial number of the Internal Bypass Switch. | |||||||||||||||||||||
| CupsDiagSubSysIntBypSwitchManufactureDate | 1.3.6.1.4.1.318.1.1.1.13.4.4.1.7 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The manufacture date of the Internal Bypass Switch. | |||||||||||||||||||||
| CupsDiagSubSysIntBypSwitchModelNum | 1.3.6.1.4.1.318.1.1.1.13.4.4.1.8 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The model number of the Internal Bypass Switch. | |||||||||||||||||||||
| CupsDiagSubSysIntBypFanSpeed | 1.3.6.1.4.1.318.1.1.1.13.4.4.1.9 | INTEGER | RO | optional | |||||||||||||||||
column · INTEGER · read-only · optional The average fan speed of the working fans in the Internal Bypass Switch in revolutions per minute (RPM). Returns (-1) if not set. | |||||||||||||||||||||
| CupsDiagSubSysIntBypAmbientTemperature | 1.3.6.1.4.1.318.1.1.1.13.4.4.1.10 | INTEGER | RO | optional | |||||||||||||||||
column · INTEGER · read-only · optional The ambient temperature in tenths of degrees celcius inside the Internal Bypass Switch. If not available, this variable is set to (-1999). | |||||||||||||||||||||
| SupsDiagSubSysBattMonitorTableSize | 1.3.6.1.4.1.318.1.1.1.13.4.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of Battery Monitor Boards attached to the UPS. | |||||||||||||||||||||
| TupsDiagSubSysBattMonitorTable | 1.3.6.1.4.1.318.1.1.1.13.4.6 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for diagnostics of the Battery Monitor Board. | |||||||||||||||||||||
| RupsDiagSubSysBattMonitorEntry | 1.3.6.1.4.1.318.1.1.1.13.4.6.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The diagnostics of the Battery Monitor Board. | |||||||||||||||||||||
| CupsDiagSubSysBattMonitorFrameIndex | 1.3.6.1.4.1.318.1.1.1.13.4.6.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The frame index entry. | |||||||||||||||||||||
| CupsDiagSubSysBattMonitorIndex | 1.3.6.1.4.1.318.1.1.1.13.4.6.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of the Battery Monitor Board. | |||||||||||||||||||||
| CupsDiagSubSysBattMonitorStatus | 1.3.6.1.4.1.318.1.1.1.13.4.6.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The status of the Battery Monitor Board. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the device status is off and OK. onOk(4) indicates the device status is on and OK. offFail(5) indicates the device status is off and failed. onFail(6) indicates the device status is on and failed. lostComm(7) indicates the device has lost communication.
| |||||||||||||||||||||
| CupsDiagSubSysBattMonitorFirmwareRev | 1.3.6.1.4.1.318.1.1.1.13.4.6.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The firmware revision of the Battery Monitor Board. | |||||||||||||||||||||
| CupsDiagSubSysBattMonitorHardwareRev | 1.3.6.1.4.1.318.1.1.1.13.4.6.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The hardware revision of the Battery Monitor Board. | |||||||||||||||||||||
| CupsDiagSubSysBattMonitorSerialNum | 1.3.6.1.4.1.318.1.1.1.13.4.6.1.6 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The serial number of the Battery Monitor Board. | |||||||||||||||||||||
| CupsDiagSubSysBattMonitorManufactureDate | 1.3.6.1.4.1.318.1.1.1.13.4.6.1.7 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The date of the manufacture for the Battery Monitor Board. | |||||||||||||||||||||
| SupsDiagSubSysExternalSwitchGearTableSize | 1.3.6.1.4.1.318.1.1.1.13.4.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of External Switch Gears attached to the UPS. | |||||||||||||||||||||
| TupsDiagSubSysExternalSwitchGearTable | 1.3.6.1.4.1.318.1.1.1.13.4.8 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for diagnostics of the individual External Switch Gear. | |||||||||||||||||||||
| RupsDiagSubSysExternalSwitchGearEntry | 1.3.6.1.4.1.318.1.1.1.13.4.8.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The diagnostics of an individual External Switch Gear. | |||||||||||||||||||||
| CupsDiagSubSysExternalSwitchGearFrameIndex | 1.3.6.1.4.1.318.1.1.1.13.4.8.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The frame index entry. | |||||||||||||||||||||
| CupsDiagSubSysExternalSwitchGearIndex | 1.3.6.1.4.1.318.1.1.1.13.4.8.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of the External Switch Gear. | |||||||||||||||||||||
| CupsDiagSubSysExternalSwitchGearStatus | 1.3.6.1.4.1.318.1.1.1.13.4.8.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The status of the External Switch Gear. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the device status is off and OK. onOk(4) indicates the device status is on and OK. offFail(5) indicates the device status is off and failed. onFail(6) indicates the device status is on and failed. lostComm(7) indicates the device has lost communication.
| |||||||||||||||||||||
| CupsDiagSubSysExternalSwitchGearFirmwareRev | 1.3.6.1.4.1.318.1.1.1.13.4.8.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The firmware revision of the External Switch Gear monitor card. | |||||||||||||||||||||
| CupsDiagSubSysExternalSwitchGearHardwareRev | 1.3.6.1.4.1.318.1.1.1.13.4.8.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The hardware revision of the External Switch Gear monitor card. | |||||||||||||||||||||
| CupsDiagSubSysExternalSwitchGearSerialNum | 1.3.6.1.4.1.318.1.1.1.13.4.8.1.6 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The serial number of the External Switch Gear monitor card. | |||||||||||||||||||||
| CupsDiagSubSysExternalSwitchGearManufactureDate | 1.3.6.1.4.1.318.1.1.1.13.4.8.1.7 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The date of the manufacture for the External Switch Gear monitor card. | |||||||||||||||||||||
| CupsDiagSubSysExternalSwitchGearTemperature | 1.3.6.1.4.1.318.1.1.1.13.4.8.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The temperature of the air around the External Switch Gear monitor card in tenths of degrees Celsius. | |||||||||||||||||||||
| SupsDiagSubSysDisplayInterfaceCardTableSize | 1.3.6.1.4.1.318.1.1.1.13.4.9 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of Display Interface Cards attached to the UPS. | |||||||||||||||||||||
| TupsDiagSubSysDisplayInterfaceCardTable | 1.3.6.1.4.1.318.1.1.1.13.4.10 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for diagnostics of individual Display Interface Cards. | |||||||||||||||||||||
| RupsDiagSubSysDisplayInterfaceCardEntry | 1.3.6.1.4.1.318.1.1.1.13.4.10.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The diagnostics of a Display Interface Card. | |||||||||||||||||||||
| CupsDiagSubSysDisplayInterfaceCardFrameIndex | 1.3.6.1.4.1.318.1.1.1.13.4.10.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The frame index entry. | |||||||||||||||||||||
| CupsDiagSubSysDisplayInterfaceCardIndex | 1.3.6.1.4.1.318.1.1.1.13.4.10.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of the Display Interface Card. | |||||||||||||||||||||
| CupsDiagSubSysDisplayInterfaceCardStatus | 1.3.6.1.4.1.318.1.1.1.13.4.10.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The status of the Display Interface Card. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the device status is off and OK. onOk(4) indicates the device status is on and OK. offFail(5) indicates the device status is off and failed. onFail(6) indicates the device status is on and failed. lostComm(7) indicates the device has lost communication.
| |||||||||||||||||||||
| SupsDiagSubSysDCCircuitBreakerTableSize | 1.3.6.1.4.1.318.1.1.1.13.4.11 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of DC Circuit Breakers attached to the UPS. | |||||||||||||||||||||
| TupsDiagSubSysDCCircuitBreakerTable | 1.3.6.1.4.1.318.1.1.1.13.4.12 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for diagnostics of individual DC Circuit Breakers. | |||||||||||||||||||||
| RupsDiagSubSysDCCircuitBreakerEntry | 1.3.6.1.4.1.318.1.1.1.13.4.12.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The diagnostics of a DC Circuit Breaker. | |||||||||||||||||||||
| CupsDiagSubSysDCCircuitBreakerFrameIndex | 1.3.6.1.4.1.318.1.1.1.13.4.12.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The frame index entry. | |||||||||||||||||||||
| CupsDiagSubSysDCCircuitBreakerIndex | 1.3.6.1.4.1.318.1.1.1.13.4.12.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of the DC Circuit Breaker. | |||||||||||||||||||||
| CupsDiagSubSysDCCircuitBreakerStatus | 1.3.6.1.4.1.318.1.1.1.13.4.12.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The status of the DC Circuit Breaker. unknown(1) indicates the circuit breaker status is unknown. notInstalled(2) indicates the circuit breaker is not installed. opened(3) indicates the circuit breaker is opened. closed(4) indicates the circuit breaker is closed.
| |||||||||||||||||||||
| SupsDiagSubSysSystemPowerSupplyTableSize | 1.3.6.1.4.1.318.1.1.1.13.4.13 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of System Power Supplies attached to the UPS. | |||||||||||||||||||||
| TupsDiagSubSysSystemPowerSupplyTable | 1.3.6.1.4.1.318.1.1.1.13.4.14 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for diagnostics of individual System Power Supplies. | |||||||||||||||||||||
| RupsDiagSubSysSystemPowerSupplyEntry | 1.3.6.1.4.1.318.1.1.1.13.4.14.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The diagnostics of a System Power Supply. | |||||||||||||||||||||
| CupsDiagSubSysSystemPowerSupplyFrameIndex | 1.3.6.1.4.1.318.1.1.1.13.4.14.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The frame index entry. | |||||||||||||||||||||
| CupsDiagSubSysSystemPowerSupplyIndex | 1.3.6.1.4.1.318.1.1.1.13.4.14.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of a System Power Supply. | |||||||||||||||||||||
| CupsDiagSubSysSystemPowerSupplyStatus | 1.3.6.1.4.1.318.1.1.1.13.4.14.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The status of the System Power Supply. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the device status is off and OK. onOk(4) indicates the device status is on and OK. offFail(5) indicates the device status is off and failed. onFail(6) indicates the device status is on and failed. lostComm(7) indicates the device has lost communication.
| |||||||||||||||||||||
| CupsDiagSubSysSystemPowerSupplyFirmwareRev | 1.3.6.1.4.1.318.1.1.1.13.4.14.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The firmware revision of the System Power Supply monitor card. | |||||||||||||||||||||
| CupsDiagSubSysSystemPowerSupplyHardwareRev | 1.3.6.1.4.1.318.1.1.1.13.4.14.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The hardware revision of the System Power Supply monitor card. | |||||||||||||||||||||
| CupsDiagSubSysSystemPowerSupplySerialNum | 1.3.6.1.4.1.318.1.1.1.13.4.14.1.6 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The serial number of the System Power Supply monitor card. | |||||||||||||||||||||
| CupsDiagSubSysSystemPowerSupplyManufactureDate | 1.3.6.1.4.1.318.1.1.1.13.4.14.1.7 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The date of the manufacture for the System Power Supply monitor card. | |||||||||||||||||||||
| SupsDiagSubSysXRCommunicationCardTableSize | 1.3.6.1.4.1.318.1.1.1.13.4.15 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of XR Communication Cards attached to the UPS. | |||||||||||||||||||||
| TupsDiagSubSysXRCommunicationCardTable | 1.3.6.1.4.1.318.1.1.1.13.4.16 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for diagnostics of individual XR Communication Cards. | |||||||||||||||||||||
| RupsDiagSubSysXRCommunicationCardEntry | 1.3.6.1.4.1.318.1.1.1.13.4.16.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The diagnostics of an XR Communication Card. | |||||||||||||||||||||
| CupsDiagSubSysXRCommunicationCardFrameIndex | 1.3.6.1.4.1.318.1.1.1.13.4.16.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The frame index entry. | |||||||||||||||||||||
| CupsDiagSubSysXRCommunicationCardIndex | 1.3.6.1.4.1.318.1.1.1.13.4.16.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of an XR Communication Card. | |||||||||||||||||||||
| CupsDiagSubSysXRCommunicationCardStatus | 1.3.6.1.4.1.318.1.1.1.13.4.16.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The status of the XR Communication Card. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the device status is off and OK. onOk(4) indicates the device status is on and OK. offFail(5) indicates the device status is off and failed. onFail(6) indicates the device status is on and failed. lostComm(7) indicates the device has lost communication.
| |||||||||||||||||||||
| CupsDiagSubSysXRCommunicationCardFirmwareRev | 1.3.6.1.4.1.318.1.1.1.13.4.16.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The firmware revision of the XR Communication card. | |||||||||||||||||||||
| CupsDiagSubSysXRCommunicationCardSerialNum | 1.3.6.1.4.1.318.1.1.1.13.4.16.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The serial number of the XR Communication card. | |||||||||||||||||||||
| SupsDiagSubSysExternalPowerFrameBoardTableSize | 1.3.6.1.4.1.318.1.1.1.13.4.17 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of External Power Frame Boards attached to the UPS. | |||||||||||||||||||||
| TupsDiagSubSysExternalPowerFrameBoardTable | 1.3.6.1.4.1.318.1.1.1.13.4.18 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for diagnostics of individual External Power Frame Boards. | |||||||||||||||||||||
| RupsDiagSubSysExternalPowerFrameBoardEntry | 1.3.6.1.4.1.318.1.1.1.13.4.18.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The diagnostics of an External Power Frame Board. | |||||||||||||||||||||
| CupsDiagSubSysExternalPowerFrameBoardFrameIndex | 1.3.6.1.4.1.318.1.1.1.13.4.18.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The frame index entry. | |||||||||||||||||||||
| CupsDiagSubSysExternalPowerFrameBoardIndex | 1.3.6.1.4.1.318.1.1.1.13.4.18.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of an External Power Frame Board. | |||||||||||||||||||||
| CupsDiagSubSysExternalPowerFrameBoardStatus | 1.3.6.1.4.1.318.1.1.1.13.4.18.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The status of the External Power Frame Board. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the device status is off and OK. onOk(4) indicates the device status is on and OK. offFail(5) indicates the device status is off and failed. onFail(6) indicates the device status is on and failed. lostComm(7) indicates the device has lost communication.
| |||||||||||||||||||||
| SupsDiagSubSysChargerTableSize | 1.3.6.1.4.1.318.1.1.1.13.4.19 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of Chargers attached to the UPS. | |||||||||||||||||||||
| TupsDiagSubSysChargerTable | 1.3.6.1.4.1.318.1.1.1.13.4.20 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for diagnostics of individual chargers. | |||||||||||||||||||||
| RupsDiagSubSysChargerEntry | 1.3.6.1.4.1.318.1.1.1.13.4.20.1 | NA | mandatory | ||||||||||||||||||
| CupsDiagSubSysChargerFrameIndex | 1.3.6.1.4.1.318.1.1.1.13.4.20.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The frame index entry. | |||||||||||||||||||||
| CupsDiagSubSysChargerIndex | 1.3.6.1.4.1.318.1.1.1.13.4.20.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of a charger. | |||||||||||||||||||||
| CupsDiagSubSysChargerStatus | 1.3.6.1.4.1.318.1.1.1.13.4.20.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The status of the Charger. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the device status is off and OK. onOk(4) indicates the device status is on and OK. offFail(5) indicates the device status is off and failed. onFail(6) indicates the device status is on and failed. lostComm(7) indicates the device has lost communication.
| |||||||||||||||||||||
| SupsDiagSubSysInverterTableSize | 1.3.6.1.4.1.318.1.1.1.13.4.21 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of Inverters attached to the UPS. | |||||||||||||||||||||
| TupsDiagSubSysInverterTable | 1.3.6.1.4.1.318.1.1.1.13.4.22 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for diagnostics of individual Inverters. | |||||||||||||||||||||
| RupsDiagSubSysInverterEntry | 1.3.6.1.4.1.318.1.1.1.13.4.22.1 | NA | mandatory | ||||||||||||||||||
| CupsDiagSubSysInverterFrameIndex | 1.3.6.1.4.1.318.1.1.1.13.4.22.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The frame index entry. | |||||||||||||||||||||
| CupsDiagSubSysInverterIndex | 1.3.6.1.4.1.318.1.1.1.13.4.22.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of an Inverter. | |||||||||||||||||||||
| CupsDiagSubSysInverterStatus | 1.3.6.1.4.1.318.1.1.1.13.4.22.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The status of the Inverter. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the device status is off and OK. onOk(4) indicates the device status is on and OK. offFail(5) indicates the device status is off and failed. onFail(6) indicates the device status is on and failed. lostComm(7) indicates the device has lost communication.
| |||||||||||||||||||||
| CupsDiagSubSysInverterFirmwareRev | 1.3.6.1.4.1.318.1.1.1.13.4.22.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The firmware revision of the Inverter monitor. | |||||||||||||||||||||
| CupsDiagSubSysInverterHardwareRev | 1.3.6.1.4.1.318.1.1.1.13.4.22.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The hardware revision of the Inverter monitor. | |||||||||||||||||||||
| CupsDiagSubSysInverterSerialNum | 1.3.6.1.4.1.318.1.1.1.13.4.22.1.6 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The serial number of the Inverter monitor. | |||||||||||||||||||||
| CupsDiagSubSysInverterManufactureDate | 1.3.6.1.4.1.318.1.1.1.13.4.22.1.7 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The date of manufacture for the Inverter monitor. | |||||||||||||||||||||
| SupsDiagSubSysPowerFactorCorrectionTableSize | 1.3.6.1.4.1.318.1.1.1.13.4.23 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of Power Factor Correction devices attached to the UPS. | |||||||||||||||||||||
| TupsDiagSubSysPowerFactorCorrectionTable | 1.3.6.1.4.1.318.1.1.1.13.4.24 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for diagnostics of individual PowerFactorCorrections. | |||||||||||||||||||||
| RupsDiagSubSysPowerFactorCorrectionEntry | 1.3.6.1.4.1.318.1.1.1.13.4.24.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The diagnostics of a Power Factor Correction. | |||||||||||||||||||||
| CupsDiagSubSysPowerFactorCorrectionFrameIndex | 1.3.6.1.4.1.318.1.1.1.13.4.24.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The frame index entry. | |||||||||||||||||||||
| CupsDiagSubSysPowerFactorCorrectionIndex | 1.3.6.1.4.1.318.1.1.1.13.4.24.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of a Power Factor Correction. | |||||||||||||||||||||
| CupsDiagSubSysPowerFactorCorrectionStatus | 1.3.6.1.4.1.318.1.1.1.13.4.24.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The status of the Power Factor Correction. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the device status is off and OK. onOk(4) indicates the device status is on and OK. offFail(5) indicates the device status is off and failed. onFail(6) indicates the device status is on and failed. lostComm(7) indicates the device has lost communication.
| |||||||||||||||||||||
| CupsDiagSubSysPowerFactorCorrectionFirmwareRev | 1.3.6.1.4.1.318.1.1.1.13.4.24.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The firmware revision of the Power Factor Correction monitor. | |||||||||||||||||||||
| CupsDiagSubSysPowerFactorCorrectionHardwareRev | 1.3.6.1.4.1.318.1.1.1.13.4.24.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The hardware revision of the Power Factor Correction monitor. | |||||||||||||||||||||
| CupsDiagSubSysPowerFactorCorrectionSerialNum | 1.3.6.1.4.1.318.1.1.1.13.4.24.1.6 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The serial number of the Power Factor Correction monitor. | |||||||||||||||||||||
| CupsDiagSubSysPowerFactorCorrectionManufactureDate | 1.3.6.1.4.1.318.1.1.1.13.4.24.1.7 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The date of the manufacture for the Power Factor Correction monitor. | |||||||||||||||||||||
| SupsDiagSubSysNetworkComCardTableSize | 1.3.6.1.4.1.318.1.1.1.13.4.25 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of Network Communication Cards attached to the UPS. | |||||||||||||||||||||
| TupsDiagSubSysNetworkComCardTable | 1.3.6.1.4.1.318.1.1.1.13.4.26 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting diagnostics information of an individual Network Communication Card. | |||||||||||||||||||||
| RupsDiagSubSysNetworkComCardEntry | 1.3.6.1.4.1.318.1.1.1.13.4.26.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The diagnostics of a Network Communication Card. | |||||||||||||||||||||
| CupsDiagSubSysNetworkComCardIndex | 1.3.6.1.4.1.318.1.1.1.13.4.26.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The UPS network and display interface communication card index entry. | |||||||||||||||||||||
| CupsDiagSubSysNetworkComCardModelNumber | 1.3.6.1.4.1.318.1.1.1.13.4.26.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory A character string identifying the model number of the UPS network and display interface communication card. This value is set at the factory. | |||||||||||||||||||||
| CupsDiagSubSysNetworkComCardSerialNumber | 1.3.6.1.4.1.318.1.1.1.13.4.26.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory A character string identifying the serial number of the UPS network and display interface communication card. This value is set at the factory. | |||||||||||||||||||||
| CupsDiagSubSysNetworkComCardDateOfManufacture | 1.3.6.1.4.1.318.1.1.1.13.4.26.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The date when the UPS network and display interface communication card was manufactured in mm/dd/yyyy format. This value is set at the factory. | |||||||||||||||||||||
| CupsDiagSubSysNetworkComCardHardwareRev | 1.3.6.1.4.1.318.1.1.1.13.4.26.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The hardware revision of the UPS network and display interface communication card. This value is set at the factory. | |||||||||||||||||||||
| CupsDiagSubSysNetworkComCardFirmwareAppRev | 1.3.6.1.4.1.318.1.1.1.13.4.26.1.6 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory An ID string identifying the application firmware revision of the UPS network and display interface communication card. | |||||||||||||||||||||
| CupsDiagSubSysNetworkComCardFirmwareAppOSRev | 1.3.6.1.4.1.318.1.1.1.13.4.26.1.7 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory An ID string identifying the application operating system firmware revision of the UPS network and display interface communication card. | |||||||||||||||||||||
| SupsDiagSubSysUsrSuppBattMonitorTableSize | 1.3.6.1.4.1.318.1.1.1.13.4.27 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of user supplied Battery Monitor Boards attached to the UPS. | |||||||||||||||||||||
| TupsDiagSubSysUsrSuppBattMonitorTable | 1.3.6.1.4.1.318.1.1.1.13.4.28 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for diagnostics of the user supplied Battery Monitor Board. | |||||||||||||||||||||
| RupsDiagSubSysUsrSuppBattMonitorEntry | 1.3.6.1.4.1.318.1.1.1.13.4.28.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The diagnostics of the user supplied Battery Monitor Board. | |||||||||||||||||||||
| CupsDiagSubSysUsrSuppBattMonitorIndex | 1.3.6.1.4.1.318.1.1.1.13.4.28.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of the user supplied Battery Monitor Board. | |||||||||||||||||||||
| CupsDiagSubSysUsrSuppBattMonitorStatus | 1.3.6.1.4.1.318.1.1.1.13.4.28.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The status of the user supplied Battery Monitor Board. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the device status is off and OK. onOk(4) indicates the device status is on and OK. offFail(5) indicates the device status is off and failed. onFail(6) indicates the device status is on and failed. lostComm(7) indicates the device has lost communication.
| |||||||||||||||||||||
| CupsDiagSubSysUsrSuppBattMonitorFirmwareRev | 1.3.6.1.4.1.318.1.1.1.13.4.28.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The firmware revision of the user supplied Battery Monitor Board. | |||||||||||||||||||||
| CupsDiagSubSysUsrSuppBattMonitorHardwareRev | 1.3.6.1.4.1.318.1.1.1.13.4.28.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The hardware revision of the user supplied Battery Monitor Board. | |||||||||||||||||||||
| CupsDiagSubSysUsrSuppBattMonitorSerialNum | 1.3.6.1.4.1.318.1.1.1.13.4.28.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The serial number of the user supplied Battery Monitor Board. | |||||||||||||||||||||
| CupsDiagSubSysUsrSuppBattMonitorTemperature | 1.3.6.1.4.1.318.1.1.1.13.4.28.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The temperature of the air around the user supplied Battery Monitor Board in tenths of degrees Celsius. | |||||||||||||||||||||
| SupsDiagSubSysUsrSuppBattBreakerStatus | 1.3.6.1.4.1.318.1.1.1.13.4.29 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The status of the user supplied Battery Breaker. unknown(1) indicates the circuit breaker status is unknown. notInstalled(2) indicates the circuit breaker is not installed. opened(3) indicates the circuit breaker is opened. closed(4) indicates the circuit breaker is closed.
| |||||||||||||||||||||
| SupsDiagSubSysPSUTableSize | 1.3.6.1.4.1.318.1.1.1.13.4.30 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of Power Supply Units in the UPS. | |||||||||||||||||||||
| TupsDiagSubSysPSUTable | 1.3.6.1.4.1.318.1.1.1.13.4.31 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for diagnostics of individual Power Supply Units. The number of entries is contained in the upsDiagSubSysPSUTableSize OID. | |||||||||||||||||||||
| RupsDiagSubSysPSUEntry | 1.3.6.1.4.1.318.1.1.1.13.4.31.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The diagnostics information of a Power Supply Unit. | |||||||||||||||||||||
| CupsDiagSubSysPSUIndex | 1.3.6.1.4.1.318.1.1.1.13.4.31.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the Power Supply Unit entry. | |||||||||||||||||||||
| CupsDiagSubSysPSUStatus | 1.3.6.1.4.1.318.1.1.1.13.4.31.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The status of the Power Supply Unit. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the device status is off and OK. onOk(4) indicates the device status is on and OK. offFail(5) indicates the device status is off and failed. onFail(6) indicates the device status is on and failed. lostComm(7) indicates the device has lost communication.
| |||||||||||||||||||||
| SupsDiagSubSysIDRCTableSize | 1.3.6.1.4.1.318.1.1.1.13.4.32 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of ID and Relay Controller Cards attached to the UPS. | |||||||||||||||||||||
| TupsDiagSubSysIDRCTable | 1.3.6.1.4.1.318.1.1.1.13.4.33 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for diagnostics of the ID and Relay Controller Card. | |||||||||||||||||||||
| RupsDiagSubSysIDRCEntry | 1.3.6.1.4.1.318.1.1.1.13.4.33.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The diagnostics of the ID and Relay Controller Card. | |||||||||||||||||||||
| CupsDiagSubSysIDRCIndex | 1.3.6.1.4.1.318.1.1.1.13.4.33.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of the ID and Relay Controller Card. | |||||||||||||||||||||
| CupsDiagSubSysIDRCStatus | 1.3.6.1.4.1.318.1.1.1.13.4.33.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The status of the ID and Relay Controller Card. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the device status is off and OK. onOk(4) indicates the device status is on and OK. offFail(5) indicates the device status is off and failed. onFail(6) indicates the device status is on and failed. lostComm(7) indicates the device has lost communication.
| |||||||||||||||||||||
| CupsDiagSubSysIDRCFirmwareRev | 1.3.6.1.4.1.318.1.1.1.13.4.33.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The firmware revision of the ID and Relay Controller Card. | |||||||||||||||||||||
| CupsDiagSubSysIDRCHardwareRev | 1.3.6.1.4.1.318.1.1.1.13.4.33.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The hardware revision of the ID and Relay Controller Card. | |||||||||||||||||||||
| CupsDiagSubSysIDRCSerialNum | 1.3.6.1.4.1.318.1.1.1.13.4.33.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The serial number of the ID and Relay Controller Card. | |||||||||||||||||||||
| SupsDiagSubSysExternalConnectorStatus | 1.3.6.1.4.1.318.1.1.1.13.4.34 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The status of the external connector board. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the device status is off and OK. onOk(4) indicates the device status is on and OK. offFail(5) indicates the device status is off and failed. onFail(6) indicates the device status is on and failed. lostComm(7) indicates the device has lost communication.
| |||||||||||||||||||||
| SupsDiagSubSysBackfeedContactorTableSize | 1.3.6.1.4.1.318.1.1.1.13.4.35 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of backfeed protection contactor attached to the UPS. | |||||||||||||||||||||
| TupsDiagSubSysBackfeedContactorTable | 1.3.6.1.4.1.318.1.1.1.13.4.36 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Backfeed protection contactor table. | |||||||||||||||||||||
| RupsDiagSubSysBackfeedContactorEntry | 1.3.6.1.4.1.318.1.1.1.13.4.36.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory A list of backfeed protection contactors. | |||||||||||||||||||||
| CupsDiagSubSysbackfeedContactorIndex | 1.3.6.1.4.1.318.1.1.1.13.4.36.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of the backfeed protection contactor. | |||||||||||||||||||||
| CupsDiagSubSysbackfeedContactorName | 1.3.6.1.4.1.318.1.1.1.13.4.36.1.2 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The name of the backfeed protection contactor. | |||||||||||||||||||||
| CupsDiagSubSysbackfeedContactorType | 1.3.6.1.4.1.318.1.1.1.13.4.36.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Indicates the backfeed protection contactor types available in the UPS system. If the UPS is unable to find any attached contactors, this variable is set to unknown(1).
| |||||||||||||||||||||
| CupsDiagSubSysbackfeedContactorStatus | 1.3.6.1.4.1.318.1.1.1.13.4.36.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The status of backfeed protection contactor. unknown(1) indicates the contactor status is unknown. opened (2) indicates the contactor is opened. closed (3) indicates the contactor is closed.
| |||||||||||||||||||||
| SupsDiagSubSysIntBypSwitchFanLifetimeInfoTableSize | 1.3.6.1.4.1.318.1.1.1.13.4.37 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of backfeed protection contactor attached to the UPS. | |||||||||||||||||||||
| TupsDiagSubSysIntBypSwitchFanLifetimeInfoTable | 1.3.6.1.4.1.318.1.1.1.13.4.38 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for diagnostics of the Internal Bypass Switch life time infomation. | |||||||||||||||||||||
| RupsDiagSubSysIntBypSwitchFanLifetimeInfoEntry | 1.3.6.1.4.1.318.1.1.1.13.4.38.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The diagnostics of the Internal Bypass Switch. | |||||||||||||||||||||
| CupsDiagSubSysIntBypSwitchFanLifetimeInfoIndex | 1.3.6.1.4.1.318.1.1.1.13.4.38.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the Internal Bypass Switch Fan liftime information entry | |||||||||||||||||||||
| CupsDiagSubSysIntBypSwitchFanLifetimeStatus | 1.3.6.1.4.1.318.1.1.1.13.4.38.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The status of the Internal Bypass Switch Fan lifetime information. ok(1) indicates the device lifetime status is OK. nearEnd(2) indicates the device lifetime status is near end. exceeded(3) indicates the device lifetime status is exceeded. unknown(4) indicates the device lifetime status is unknown.
| |||||||||||||||||||||
| CupsDiagSubSysIntBypSwitchFanEstmtdLifetimeRmng | 1.3.6.1.4.1.318.1.1.1.13.4.38.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Displays the time remaining for the module before it should be replaced. Measured in months. This value is set when you originally install the module. | |||||||||||||||||||||
| CupsDiagSubSysIntBypSwitchFanEstmtdLifetimeRmngPct | 1.3.6.1.4.1.318.1.1.1.13.4.38.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Displays the percentage of the total lifetime remaining for the module before it should be replaced. | |||||||||||||||||||||
| NupsDiagnosticExternalDevices | 1.3.6.1.4.1.318.1.1.1.13.5 | ||||||||||||||||||||
| NupsDiagSwitchGear | 1.3.6.1.4.1.318.1.1.1.13.5.1 | ||||||||||||||||||||
| SupsDiagSwitchGearStatus | 1.3.6.1.4.1.318.1.1.1.13.5.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The status of the Switch Gear. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. ok(3) indicates the device status is OK. fail(4) indicates the device status has failed. lostComm(5) indicates the device has lost communication. overtemp(6) indicates the device has an over temperature condition.
| |||||||||||||||||||||
| SupsDiagSwitchGearInputSwitchStatus | 1.3.6.1.4.1.318.1.1.1.13.5.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The status of the Switch Gear Input Switch. unknown(1) indicates the switch status is unknown. notInstalled(2) indicates the switch is not installed. opened(3) indicates the switch is opened. closed(4) indicates the switch is closed.
| |||||||||||||||||||||
| SupsDiagSwitchGearOutputSwitchStatus | 1.3.6.1.4.1.318.1.1.1.13.5.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The status of the Switch Gear Output Switch. unknown(1) indicates the switch status is unknown. notInstalled(2) indicates the switch is not installed. opened(3) indicates the switch is opened. closed(4) indicates the switch is closed.
| |||||||||||||||||||||
| SupsDiagSwitchGearBypassSwitchStatus | 1.3.6.1.4.1.318.1.1.1.13.5.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The status of the Switch Gear Bypass Switch. unknown(1) indicates the switch status is unknown. notInstalled(2) indicates the switch is not installed. opened(3) indicates the switch is opened. closed(4) indicates the switch is closed.
| |||||||||||||||||||||
| SupsDiagSwitchGearBypassInputSwitchStatus | 1.3.6.1.4.1.318.1.1.1.13.5.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The status of the Switch Gear Bypass Input Switch. unknown(1) indicates the switch status is unknown. notInstalled(2) indicates the switch is not installed. opened(3) indicates the switch is opened. closed(4) indicates the switch is closed.
| |||||||||||||||||||||
| SupsDiagSwitchGearBreakerTableSize | 1.3.6.1.4.1.318.1.1.1.13.5.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of switchgear breakers attached to the UPS. | |||||||||||||||||||||
| TupsDiagSwitchGearBreakerTable | 1.3.6.1.4.1.318.1.1.1.13.5.1.7 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Switchgear breaker table. | |||||||||||||||||||||
| RupsDiagSwitchGearBreakerEntry | 1.3.6.1.4.1.318.1.1.1.13.5.1.7.1 | NA | mandatory | ||||||||||||||||||
| CswitchgearBreakerIndex | 1.3.6.1.4.1.318.1.1.1.13.5.1.7.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of the switchgear breaker. | |||||||||||||||||||||
| CswitchgearBreakerPresent | 1.3.6.1.4.1.318.1.1.1.13.5.1.7.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Indicates if the switchgear breaker is present. notPresent(1) indicates that the breaker is not present. present(2) indicates that the breaker is present.
| |||||||||||||||||||||
| CswitchgearBreakerName | 1.3.6.1.4.1.318.1.1.1.13.5.1.7.1.3 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The name of the switchgear breaker. | |||||||||||||||||||||
| CswitchgearBreakerType | 1.3.6.1.4.1.318.1.1.1.13.5.1.7.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Indicates the switchgear breaker types available in the UPS system. If the UPS is unable to find any attached breakers, this variable is set to unknown(1). If the system has multiple breakers of the same type (e.g. multiple battery breakers) the status shown in OID switchgearBreakerStatus will be the aggregated status.
| |||||||||||||||||||||
| CswitchgearBreakerStatus | 1.3.6.1.4.1.318.1.1.1.13.5.1.7.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The status of switchgear breaker. unknown(1) indicates the breaker status is unknown. opened (2) indicates the breaker is opened. closed (3) indicates the breaker is closed. NOTE: If there are more than one breaker of the same type, the status reflects the aggregated value. For battery breakers as example, closed would mean that at least one breaker is closed.
| |||||||||||||||||||||
| SupsDiagSubFeedBreakerTableSize | 1.3.6.1.4.1.318.1.1.1.13.5.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of subfeed breakers attached to the UPS. | |||||||||||||||||||||
| TupsDiagSubFeedBreakerTable | 1.3.6.1.4.1.318.1.1.1.13.5.1.9 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Subfeed breaker table. | |||||||||||||||||||||
| RupsDiagSubFeedBreakerEntry | 1.3.6.1.4.1.318.1.1.1.13.5.1.9.1 | NA | mandatory | ||||||||||||||||||
| CsubfeedBreakerIndex | 1.3.6.1.4.1.318.1.1.1.13.5.1.9.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of the subfeed breakers. | |||||||||||||||||||||
| CsubfeedBreakerPresent | 1.3.6.1.4.1.318.1.1.1.13.5.1.9.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Indicates if the subfeed breaker is present. notPresent (1) indicates that the breaker is not present. present (2) indicates that the breaker is present.
| |||||||||||||||||||||
| CsubfeedBreakerRating | 1.3.6.1.4.1.318.1.1.1.13.5.1.9.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The current rating of the installed subfeed breaker. | |||||||||||||||||||||
| CsubfeedBreakerUpperAcceptPowerWarning | 1.3.6.1.4.1.318.1.1.1.13.5.1.9.1.4 | INTEGER (0..100) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..100) · read-write · mandatory The maximum acceptable load before warning is issued. Expressed as percent of the subfeed breaker rating. | |||||||||||||||||||||
| CsubfeedBreakerUpperAcceptPowerCritical | 1.3.6.1.4.1.318.1.1.1.13.5.1.9.1.5 | INTEGER (0..125) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..125) · read-write · mandatory The maximum load before a critical alarm occurs. Expressed as percent of the subfeed breaker rating. | |||||||||||||||||||||
| CsubfeedBreakerStatus | 1.3.6.1.4.1.318.1.1.1.13.5.1.9.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The status of the Circuit Breaker. unknown(1) indicates the circuit breaker status is unknown. notInstalled(2) indicates the circuit breaker is not installed. opened(3) indicates the circuit breaker is opened. closed(4) indicates the circuit breaker is closed.
| |||||||||||||||||||||
| CsubfeedBreakerName | 1.3.6.1.4.1.318.1.1.1.13.5.1.9.1.7 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The name of the subfeed breaker. | |||||||||||||||||||||
| CsubfeedBreakerCurrent | 1.3.6.1.4.1.318.1.1.1.13.5.1.9.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The subfeed current in tenths of Amps. | |||||||||||||||||||||
| SupsDiagSwitchGearInstallationLoadPct | 1.3.6.1.4.1.318.1.1.1.13.5.1.10 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The actual output load expressed as a percentage of the rating of the UPS. | |||||||||||||||||||||
| TupsDiagSubFeedPhaseTable | 1.3.6.1.4.1.318.1.1.1.13.5.1.11 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of subfeed phase table. | |||||||||||||||||||||
| RupsDiagSubFeedPhaseEntry | 1.3.6.1.4.1.318.1.1.1.13.5.1.11.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular phase. | |||||||||||||||||||||
| CupsDiagSubFeedBreakerIndex | 1.3.6.1.4.1.318.1.1.1.13.5.1.11.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The subfeed breaker index. | |||||||||||||||||||||
| CupsDiagSubFeedPhaseIndex | 1.3.6.1.4.1.318.1.1.1.13.5.1.11.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The subfeed phase index. | |||||||||||||||||||||
| CupsDiagSubFeedPhaseCurrent | 1.3.6.1.4.1.318.1.1.1.13.5.1.11.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The subfeed phase current in Amps. | |||||||||||||||||||||
| CupsDiagSubFeedPhaseCurrentAlternate | 1.3.6.1.4.1.318.1.1.1.13.5.1.11.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The subfeed phase current in tenths of Amps. | |||||||||||||||||||||
| SupsDiagSwitchgearSerialNumber | 1.3.6.1.4.1.318.1.1.1.13.5.1.12 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The serial number of the UPS I/O Cabinet. | |||||||||||||||||||||
| SupsDiagSwitchgearAmbientTemperature | 1.3.6.1.4.1.318.1.1.1.13.5.1.13 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The ambient temperature of I/O Cabinet in tenths of degrees Celsius. | |||||||||||||||||||||
| SupsDiagUsrSuppSwitchgearMonitorTableSize | 1.3.6.1.4.1.318.1.1.1.13.5.1.14 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of user supplied Switch Gear Monitor Boards attached to the UPS. | |||||||||||||||||||||
| TupsDiagUsrSuppSwitchgearMonitorTable | 1.3.6.1.4.1.318.1.1.1.13.5.1.15 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for diagnostics of the user supplied Switch Gear Monitor Board. | |||||||||||||||||||||
| RupsDiagUsrSuppSwitchgearMonitorEntry | 1.3.6.1.4.1.318.1.1.1.13.5.1.15.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The diagnostics of the user supplied Switch Gear Monitor Board. | |||||||||||||||||||||
| CupsDiagUsrSuppSwitchgearMonitorIndex | 1.3.6.1.4.1.318.1.1.1.13.5.1.15.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of the user supplied Switch Gear Monitor Board. | |||||||||||||||||||||
| CupsDiagUsrSuppSwitchgearMonitorStatus | 1.3.6.1.4.1.318.1.1.1.13.5.1.15.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The status of the user supplied Switch Gear Monitor Board. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the device status is off and OK. onOk(4) indicates the device status is on and OK. offFail(5) indicates the device status is off and failed. onFail(6) indicates the device status is on and failed. lostComm(7) indicates the device has lost communication.
| |||||||||||||||||||||
| CupsDiagUsrSuppSwitchgearMonitorFirmwareRev | 1.3.6.1.4.1.318.1.1.1.13.5.1.15.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The firmware revision of the user supplied Switch Gear Monitor Board. | |||||||||||||||||||||
| CupsDiagUsrSuppSwitchgearMonitorHardwareRev | 1.3.6.1.4.1.318.1.1.1.13.5.1.15.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The hardware revision of the user supplied Switch Gear Monitor Board. | |||||||||||||||||||||
| CupsDiagUsrSuppSwitchgearMonitorSerialNum | 1.3.6.1.4.1.318.1.1.1.13.5.1.15.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The serial number of the user supplied Switch Gear Monitor Board. | |||||||||||||||||||||
| CupsDiagUsrSuppSwitchgearMonitorTemperature | 1.3.6.1.4.1.318.1.1.1.13.5.1.15.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The temperature of the air around the user supplied Switch Gear Monitor Board in tenths of degrees Celsius. | |||||||||||||||||||||
| NupsDiagMCCBBox | 1.3.6.1.4.1.318.1.1.1.13.5.2 | ||||||||||||||||||||
| SupsDiagMCCBBoxStatus | 1.3.6.1.4.1.318.1.1.1.13.5.2.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The status of the MCCB Box (Molded Case Circuit Breaker Box) external device. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. opened(3) indicates the circuit is opened. closed(4) indicates the circuit is closed.
| |||||||||||||||||||||
| NupsDiagTransformer | 1.3.6.1.4.1.318.1.1.1.13.5.3 | ||||||||||||||||||||
| SupsDiagTransformerStatus | 1.3.6.1.4.1.318.1.1.1.13.5.3.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The status of the External Transformer. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. ok(3) indicates the device status is OK. fail(4) indicates the device status has failed. lostComm(5) indicates the device has lost communication. overtemp(6) indicates the device has an over temperature condition. opened(7) indicates the circuit is opened. closed(8) indicates the circuit is closed.
| |||||||||||||||||||||
| NupsDiagFlyWheel | 1.3.6.1.4.1.318.1.1.1.13.5.4 | ||||||||||||||||||||
| SupsDiagFlyWheelStatus | 1.3.6.1.4.1.318.1.1.1.13.5.4.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Indicates the status of flywheel connected to UPS. If the UPS is unable to determine the state of flywheel, this variable is set to unknown(1).
| |||||||||||||||||||||
| NupsDiagnosticComBus | 1.3.6.1.4.1.318.1.1.1.13.6 | ||||||||||||||||||||
| SupsDiagComBusInternalMIMStatus | 1.3.6.1.4.1.318.1.1.1.13.6.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The status of the internal MIM communication bus. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. ok(3) indicates the device status is OK. lostComm(4) indicates the device has lost communication. rxFailure(5) indicates the device has a receive failure. txFailure(6) indicates the device has a transmit failure.
| |||||||||||||||||||||
| SupsDiagComBusInternalRIMStatus | 1.3.6.1.4.1.318.1.1.1.13.6.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The status of the internal RIM communication bus. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. ok(3) indicates the device status is OK. lostComm(4) indicates the device has lost communication. rxFailure(5) indicates the device has a receive failure. txFailure(6) indicates the device has a transmit failure.
| |||||||||||||||||||||
| SupsDiagComBusMIMtoRIMStatus | 1.3.6.1.4.1.318.1.1.1.13.6.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The status of the MIM to RIM communication bus. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. ok(3) indicates the device status is OK. lostComm(4) indicates the device has lost communication. rxFailure(5) indicates the device has a receive failure. txFailure(6) indicates the device has a transmit failure.
| |||||||||||||||||||||
| SupsDiagComBusExternalMIMStatus | 1.3.6.1.4.1.318.1.1.1.13.6.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The status of the external MIM communication bus. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. ok(3) indicates the device status is OK. lostComm(4) indicates the device has lost communication. rxFailure(5) indicates the device has a receive failure. txFailure(6) indicates the device has a transmit failure.
| |||||||||||||||||||||
| SupsDiagComBusExternalRIMStatus | 1.3.6.1.4.1.318.1.1.1.13.6.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The status of the external RIM communication bus. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. ok(3) indicates the device status is OK. lostComm(4) indicates the device has lost communication. rxFailure(5) indicates the device has a receive failure. txFailure(6) indicates the device has a transmit failure.
| |||||||||||||||||||||
| NupsDiagnosticPowerCabinet | 1.3.6.1.4.1.318.1.1.1.13.7 | ||||||||||||||||||||
| SupsDiagnosticPowerCabinetTableSize | 1.3.6.1.4.1.318.1.1.1.13.7.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The maximum number of Power Cabinets supported by the UPS. | |||||||||||||||||||||
| TupsDiagnosticPowerCabinetTable | 1.3.6.1.4.1.318.1.1.1.13.7.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for diagnostics of individual Power Cabinets. The number of entries is contained in the upsDiagnosticPowerCabinetTableSize OID. | |||||||||||||||||||||
| RupsDiagnosticPowerCabinetEntry | 1.3.6.1.4.1.318.1.1.1.13.7.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The diagnostics of a Power Cabinet. | |||||||||||||||||||||
| CupsDiagnosticPowerCabinetIndex | 1.3.6.1.4.1.318.1.1.1.13.7.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the Power Cabinet. | |||||||||||||||||||||
| CupsDiagnosticPowerCabinetAmbientTemperature | 1.3.6.1.4.1.318.1.1.1.13.7.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The ambient temperature of Power Cabinet in tenths of degrees Celsius. If the Power Cabinet is not present, this variable is set to (-1). | |||||||||||||||||||||
| NupsDiagnosticDisplay | 1.3.6.1.4.1.318.1.1.1.13.8 | ||||||||||||||||||||
| SupsDiagnosticDisplayHardwareRev | 1.3.6.1.4.1.318.1.1.1.13.8.1 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The hardware revision of the Display. | |||||||||||||||||||||
| SupsDiagnosticDisplaySerialNum | 1.3.6.1.4.1.318.1.1.1.13.8.2 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The serial number of the Display. | |||||||||||||||||||||
| SupsDiagnosticDisplayFirmwareRev | 1.3.6.1.4.1.318.1.1.1.13.8.3 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The firmware revision of the Display. | |||||||||||||||||||||
| SupsDiagnosticDisplayModelNum | 1.3.6.1.4.1.318.1.1.1.13.8.4 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The model number of the Display. | |||||||||||||||||||||
| SupsDiagnosticDisplayStatus | 1.3.6.1.4.1.318.1.1.1.13.8.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The System Level Controller Status. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the device status is off and OK. onOk(4) indicates the device status is on and OK. offFail(5) indicates the device status is off and failed. onFail(6) indicates the device status is on and failed. lostComm(7) indicates the device has lost communication.
| |||||||||||||||||||||
| NupsDiagnosticUnitController | 1.3.6.1.4.1.318.1.1.1.13.9 | ||||||||||||||||||||
| SupsDiagUnitControllerTableSize | 1.3.6.1.4.1.318.1.1.1.13.9.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of Unit Controllers in or attached to the UPS. | |||||||||||||||||||||
| TupsDiagUnitControllerTable | 1.3.6.1.4.1.318.1.1.1.13.9.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for diagnostics of individual Intelligence Modules. The number of entries is contained in the upsDiagUnitControllerTableSize OID. | |||||||||||||||||||||
| RupsDiagUnitControllerEntry | 1.3.6.1.4.1.318.1.1.1.13.9.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The diagnostics and information of an Intelligence Module. | |||||||||||||||||||||
| CupsDiagUnitControllerIndex | 1.3.6.1.4.1.318.1.1.1.13.9.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the Unit Controller entry. | |||||||||||||||||||||
| CupsDiagUnitControllerStatus | 1.3.6.1.4.1.318.1.1.1.13.9.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The status of the Unit Controller. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the device status is off and OK. onOk(4) indicates the device status is on and OK. offFail(5) indicates the device status is off and failed. onFail(6) indicates the device status is on and failed. lostComm(7) indicates the device has lost communication.
| |||||||||||||||||||||
| CupsDiagUnitControllerFirmwareRev | 1.3.6.1.4.1.318.1.1.1.13.9.2.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The firmware revision of the Unit Controller. | |||||||||||||||||||||
| CupsDiagUnitControllerHardwareRev | 1.3.6.1.4.1.318.1.1.1.13.9.2.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The hardware revision of the Unit Controller. | |||||||||||||||||||||
| CupsDiagUnitControllerSerialNum | 1.3.6.1.4.1.318.1.1.1.13.9.2.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The serial number of the Unit Controller. | |||||||||||||||||||||
| CupsDiagUnitControllerModelNum | 1.3.6.1.4.1.318.1.1.1.13.9.2.1.6 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The model number of the Unit Controller. | |||||||||||||||||||||
| NupsDiagnosticSLC | 1.3.6.1.4.1.318.1.1.1.13.10 | ||||||||||||||||||||
| SupsDiagnosticSLCHardwareRev | 1.3.6.1.4.1.318.1.1.1.13.10.1 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The hardware revision of the System Level Controller. | |||||||||||||||||||||
| SupsDiagnosticSLCSerialNum | 1.3.6.1.4.1.318.1.1.1.13.10.2 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The serial number of the System Level Controller. | |||||||||||||||||||||
| SupsDiagnosticSLCFirmwareRev | 1.3.6.1.4.1.318.1.1.1.13.10.3 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The firmware revision of the System Level Controller. | |||||||||||||||||||||
| SupsDiagnosticSLCModelNumber | 1.3.6.1.4.1.318.1.1.1.13.10.4 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The Model number of the System Level Controller. | |||||||||||||||||||||
| SupsDiagSLCStatus | 1.3.6.1.4.1.318.1.1.1.13.10.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The System Level Controller Status. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the device status is off and OK. onOk(4) indicates the device status is on and OK. offFail(5) indicates the device status is off and failed. onFail(6) indicates the device status is on and failed. lostComm(7) indicates the device has lost communication.
| |||||||||||||||||||||
| NupsDiagnosticTemperature | 1.3.6.1.4.1.318.1.1.1.13.11 | ||||||||||||||||||||
| SupsDiagnosticTemperatureAmbientTemperature | 1.3.6.1.4.1.318.1.1.1.13.11.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The ambient temperature in tenths of degrees Celsius. If not available, this variable is set to (-1999). | |||||||||||||||||||||
| NupsDiagnosticLifeCycleManagement | 1.3.6.1.4.1.318.1.1.1.13.12 | ||||||||||||||||||||
| SupsDiagLCMDCCapacitorMaintenanceInterval | 1.3.6.1.4.1.318.1.1.1.13.12.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory DC capacitor maintenance interval in days. | |||||||||||||||||||||
| SupsDiagLCMDCCapacitorTimeSinceMaintenance | 1.3.6.1.4.1.318.1.1.1.13.12.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory DC capacitor time since last maintenance in days. Note: Some UPS devices only internally support a higher reporting value such as tenths of months or even months so this value may jump rather than count daily as expected. | |||||||||||||||||||||
| SupsDiagLCMACCapacitorMaintenanceInterval | 1.3.6.1.4.1.318.1.1.1.13.12.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory AC capacitor maintenance interval in days. | |||||||||||||||||||||
| SupsDiagLCMACCapacitorTimeSinceMaintenance | 1.3.6.1.4.1.318.1.1.1.13.12.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory AC capacitor time since last maintenance in days. Note: Some UPS devices only internally support a higher reporting value such as tenths of months or even months so this value may jump rather than count daily as expected. | |||||||||||||||||||||
| SupsDiagLCMBatteryMaintenanceInterval | 1.3.6.1.4.1.318.1.1.1.13.12.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Battery maintenance interval in days. | |||||||||||||||||||||
| SupsDiagLCMBatteryTimeSinceMaintenance | 1.3.6.1.4.1.318.1.1.1.13.12.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Battery time since last maintenance in days. Note: Some UPS devices only internally support a higher reporting value such as tenths of months or even months so this value may jump rather than count daily as expected. | |||||||||||||||||||||
| SupsDiagLCMAuxPowerSupplyMaintenanceInterval | 1.3.6.1.4.1.318.1.1.1.13.12.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Auxiliary Power Supply maintenance interval in days | |||||||||||||||||||||
| SupsDiagLCMAuxPowerSupplyTimeSinceMaintenance | 1.3.6.1.4.1.318.1.1.1.13.12.8 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Auxiliary Power Supply time since last maintenance in days. Note: Some UPS devices only internally support a higher reporting value such as tenths of months or even months so this value may jump rather than count daily as expected. | |||||||||||||||||||||
| SupsDiagLCMAirFilterMaintenanceInterval | 1.3.6.1.4.1.318.1.1.1.13.12.9 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Air Filter maintenance interval in days. | |||||||||||||||||||||
| SupsDiagLCMAirFilterTimeSinceMaintenance | 1.3.6.1.4.1.318.1.1.1.13.12.10 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Air Filter time since last maintenance in days. Note: Some UPS devices only internally support a higher reporting value such as tenths of months or even months so this value may jump rather than count daily as expected. | |||||||||||||||||||||
| SupsDiagLCMWarrantyInterval | 1.3.6.1.4.1.318.1.1.1.13.12.11 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Warranty interval in days. | |||||||||||||||||||||
| SupsDiagLCMWarrantyElapsedTime | 1.3.6.1.4.1.318.1.1.1.13.12.12 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Elapsed Warranty time since system start-up in days. Note: Some UPS devices only internally support a higher reporting value such as tenths of months or even months so this value may jump rather than count daily as expected. | |||||||||||||||||||||
| NupsDiagnosticRelativeHumidity | 1.3.6.1.4.1.318.1.1.1.13.13 | ||||||||||||||||||||
| SupsDiagnosticRelativeHumidityPct | 1.3.6.1.4.1.318.1.1.1.13.13.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The relative humidity in percentage. If not available, this variable is set to (-1). | |||||||||||||||||||||
| NupsParallelSystem | 1.3.6.1.4.1.318.1.1.1.14 | ||||||||||||||||||||
| SupsParallelSysLocalAddress | 1.3.6.1.4.1.318.1.1.1.14.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Defines the UPS ID number in the parallel system. | |||||||||||||||||||||
| SupsParallelSysRemoteAddress | 1.3.6.1.4.1.318.1.1.1.14.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Defines the total number of UPS devices in parallel. | |||||||||||||||||||||
| SupsParallelSysRedundancy | 1.3.6.1.4.1.318.1.1.1.14.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The redundancy warning level for paralleled UPS nplus0 (1) indicates that there are no redundant units. nplus1 (2) indicates that there is one redundant unit. nplus2 (3) indicates that there are two redundant units. nplus3 (4) indicates that there are three redundant units. nplus4 (5) indicates that there are four redundant unit. nplus5 (6) indicates that there are five redundant units.
| |||||||||||||||||||||
| SupsParallelInputMaximumCurrent | 1.3.6.1.4.1.318.1.1.1.14.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Maximum input RMS current of the parallel system measured in Amperes. | |||||||||||||||||||||
| SupsParallelTotalOutputPower | 1.3.6.1.4.1.318.1.1.1.14.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The Total Output power of UPS in kW when UPS are configured in parallel or -1 if it's unsupported by this UPS. | |||||||||||||||||||||
| SupsParallelTotalOutputApparentPower | 1.3.6.1.4.1.318.1.1.1.14.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The Total Output Apparent power of UPS in kVA when UPS are configured in parallel or -1 if it's unsupported by this UPS. | |||||||||||||||||||||
| TupsParallelInputPhaseTable | 1.3.6.1.4.1.318.1.1.1.14.7 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of input table entries. | |||||||||||||||||||||
| RupsParallelInputPhaseEntry | 1.3.6.1.4.1.318.1.1.1.14.7.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular input phase. | |||||||||||||||||||||
| CupsParallelInputPhaseTableIndex | 1.3.6.1.4.1.318.1.1.1.14.7.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The parallel unit identifier. | |||||||||||||||||||||
| CupsParallelInputPhaseIndex | 1.3.6.1.4.1.318.1.1.1.14.7.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The input phase identifier. | |||||||||||||||||||||
| CupsParallelInputCurrent | 1.3.6.1.4.1.318.1.1.1.14.7.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The input current in amperes, or -1 if it's unsupported by this UPS. | |||||||||||||||||||||
| CupsParallelInputActivePower | 1.3.6.1.4.1.318.1.1.1.14.7.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The input power in kW, or -1 if it's unsupported by this UPS. | |||||||||||||||||||||
| CupsParallelInputApparentPower | 1.3.6.1.4.1.318.1.1.1.14.7.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The input apparent power in kVA, or -1 if it's unsupported by this UPS. | |||||||||||||||||||||
| CupsParallelInputVoltage | 1.3.6.1.4.1.318.1.1.1.14.7.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The input voltage of UPS in volts, or -1 if it's unsupported by this UPS. | |||||||||||||||||||||
| CupsParallelInputMaxVoltage | 1.3.6.1.4.1.318.1.1.1.14.7.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The peak input voltage in VAC measured since the last reset, or -1 if it's unsupported by this UPS. | |||||||||||||||||||||
| CupsParallelInputMaxCurrent | 1.3.6.1.4.1.318.1.1.1.14.7.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The peak input current in amperes measured since last reset, or -1 if it's unsupported by this UPS. | |||||||||||||||||||||
| CupsParallelInputTotalActivePower | 1.3.6.1.4.1.318.1.1.1.14.7.1.9 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Total active input power of the parallel system in kW. | |||||||||||||||||||||
| CupsParallelInputTotalApparentPower | 1.3.6.1.4.1.318.1.1.1.14.7.1.10 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Total apparent input power of the parallel system in kVA. | |||||||||||||||||||||
| TupsParallelOutputPhaseTable | 1.3.6.1.4.1.318.1.1.1.14.8 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of output table entries. The number of entries is given by the sum of the upsPhaseNumOutputPhases. | |||||||||||||||||||||
| RupsParallelOutputPhaseEntry | 1.3.6.1.4.1.318.1.1.1.14.8.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular output phase. | |||||||||||||||||||||
| CupsParallelOutputPhaseTableIndex | 1.3.6.1.4.1.318.1.1.1.14.8.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The output identifier. | |||||||||||||||||||||
| CupsParallelOutputPhaseIndex | 1.3.6.1.4.1.318.1.1.1.14.8.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The output phase identifier. | |||||||||||||||||||||
| CupsParallelOutputCurrent | 1.3.6.1.4.1.318.1.1.1.14.8.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The output current in amperes drawn by the load on the UPS, or -1 if it's unsupported by this UPS. | |||||||||||||||||||||
| CupsParallelOutputLoad | 1.3.6.1.4.1.318.1.1.1.14.8.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The output load in VA, or -1 if it's unsupported by this UPS. | |||||||||||||||||||||
| CupsParallelOutputPercentLoad | 1.3.6.1.4.1.318.1.1.1.14.8.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The percentage of the UPS load capacity in VA at present redundancy being used on this output phase, or -1 if it's unsupported by this UPS. | |||||||||||||||||||||
| CupsParallelOutputPower | 1.3.6.1.4.1.318.1.1.1.14.8.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The output power in Watts, or -1 if it's unsupported by this UPS. | |||||||||||||||||||||
| TupsParallelOutputApparentPowerTable | 1.3.6.1.4.1.318.1.1.1.14.9 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of output table entries. The number of entries is given by the value of upsOutputNumPhases. | |||||||||||||||||||||
| RupsParallelOutputApparentPowerEntry | 1.3.6.1.4.1.318.1.1.1.14.9.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular output. | |||||||||||||||||||||
| CupsParallelOutputApparentPowerTableIndex | 1.3.6.1.4.1.318.1.1.1.14.9.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The UPS parallel output identifier. | |||||||||||||||||||||
| CupsParallelOutputApparentPower | 1.3.6.1.4.1.318.1.1.1.14.9.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The apparent power of each of UPS in kVA when UPS are configured in parallel. | |||||||||||||||||||||
| TupsParallelDiagSubSysBreakerTable | 1.3.6.1.4.1.318.1.1.1.14.10 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for diagnostics of parallel Circuit Breakers. | |||||||||||||||||||||
| RupsParallelDiagSubSysBreakerEntry | 1.3.6.1.4.1.318.1.1.1.14.10.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The diagnostics of Circuit Breaker. | |||||||||||||||||||||
| CupsParallelDiagSubSysBreakerFrameIndex | 1.3.6.1.4.1.318.1.1.1.14.10.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The Parallel UPS index entry. | |||||||||||||||||||||
| CupsParallelDiagSubSysBreakerIndex | 1.3.6.1.4.1.318.1.1.1.14.10.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of the Circuit Breaker. | |||||||||||||||||||||
| CupsParallelDiagSubSysBreakerStatus | 1.3.6.1.4.1.318.1.1.1.14.10.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The status of the Circuit Breaker. unknown(1) indicates the circuit breaker status is unknown. notInstalled(2) indicates the circuit breaker is not installed. opened(3) indicates the circuit breaker is opened. closed(4) indicates the circuit breaker is closed.
| |||||||||||||||||||||
| CupsParallelDiagSubSysBreakerName | 1.3.6.1.4.1.318.1.1.1.14.10.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The name of Circuit Breaker. | |||||||||||||||||||||
| SupsParallelOutputTotalPercentLoad | 1.3.6.1.4.1.318.1.1.1.14.11 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The percentage of the UPS total load capacity in kVA or -1 if it's unsupported by this UPS. | |||||||||||||||||||||
| TupsParallelOutputActivePowerTable | 1.3.6.1.4.1.318.1.1.1.14.12 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of output table entries. The number of entries is given by the value of upsParallelSysRemoteAddress. | |||||||||||||||||||||
| RupsParallelOutputActivePowerEntry | 1.3.6.1.4.1.318.1.1.1.14.12.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular output. | |||||||||||||||||||||
| CupsParallelOutputActivePowerTableIndex | 1.3.6.1.4.1.318.1.1.1.14.12.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The UPS parallel output identifier. | |||||||||||||||||||||
| CupsParallelOutputActivePower | 1.3.6.1.4.1.318.1.1.1.14.12.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The active power of each UPS in kW when UPS devices are configured in parallel. | |||||||||||||||||||||
| SupsParallelSysSwitchGearInstallationLoadPct | 1.3.6.1.4.1.318.1.1.1.14.13 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The actual output load expressed as a percentage of the rating of the Parallel UPS system. | |||||||||||||||||||||
| SupsParallelSysRedundancyStatus | 1.3.6.1.4.1.318.1.1.1.14.14 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Displays the number of backup or redundant UPS devices set up on the parallel system. nplus0 (1) no redundant units. nplus1 (2) one redundant unit. nplus2 (3) two redundant units. nplus3 (4) three redundant units. nplus4 (5) four redundant units. nplus5 (6) five redundant units.
| |||||||||||||||||||||
| SupsParallelSysName | 1.3.6.1.4.1.318.1.1.1.14.15 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory An ID string for the group of UPS units in the same parallel system. Some products do not allow write operations for this OID. | |||||||||||||||||||||
| SupsParallelSysUpsTableSize | 1.3.6.1.4.1.318.1.1.1.14.16 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of UPS devices in parallel. | |||||||||||||||||||||
| TupsParallelSysUpsTable | 1.3.6.1.4.1.318.1.1.1.14.17 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of UPS table entries. The number of entries is given by the value of upsParallelSysUpsTableize. | |||||||||||||||||||||
| RupsParallelSysUpsEntry | 1.3.6.1.4.1.318.1.1.1.14.17.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular UPS in parallel. | |||||||||||||||||||||
| CupsParallelSysUpsIndex | 1.3.6.1.4.1.318.1.1.1.14.17.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the Parallel System UPS table entry. | |||||||||||||||||||||
| CupsParallelSysUpsName | 1.3.6.1.4.1.318.1.1.1.14.17.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The UPS id as assigned by the system. | |||||||||||||||||||||
| CupsParallelSysUpsAlarmStatus | 1.3.6.1.4.1.318.1.1.1.14.17.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The alarm status of the UPS. unknown(1) indicates the UPS status is unknown. normal(2) indicates UPS is functioning normally. informational(3) indicates informational alarm present in the UPS. warning(4) indicates warning alarm present in the UPS. critical(5) indicates critical alarm present in the UPS.
| |||||||||||||||||||||
| CupsParallelSysUpsMode | 1.3.6.1.4.1.318.1.1.1.14.17.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The current operating mode of the UPS. If the UPS is unable to determine the state of the UPS, this variable is set to unknown(1).
| |||||||||||||||||||||
| CupsParallelSysUpsSerialNumber | 1.3.6.1.4.1.318.1.1.1.14.17.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The Serial number of the UPS in parallel. Equivalent to OID 1.3.6.1.4.1.318.1.1.1.1.2.3 (upsAdvIdentSerialNumber). | |||||||||||||||||||||
| SupsParallelNumOfUpsPoweringLoad | 1.3.6.1.4.1.318.1.1.1.14.18 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Number of UPS powered and protecting the load which are not defective (no battery fault, no internal fault). | |||||||||||||||||||||
| SupsParallelMinNumOfRequiredUps | 1.3.6.1.4.1.318.1.1.1.14.19 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Minimal number of UPS required to guarantee the availability of power. | |||||||||||||||||||||
| NupsPhysicalLayout | 1.3.6.1.4.1.318.1.1.1.15 | ||||||||||||||||||||
| SupsIOFrameLayoutPositionID | 1.3.6.1.4.1.318.1.1.1.15.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Defines the position ID of UPS frame. | |||||||||||||||||||||
| SupsBottomFeedFrameLayoutPositionID | 1.3.6.1.4.1.318.1.1.1.15.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Defines the position ID of bottom feed frame. | |||||||||||||||||||||
| SupsSwitchGearLayoutPositionID | 1.3.6.1.4.1.318.1.1.1.15.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Defines the position ID of switchgear. | |||||||||||||||||||||
| SupsBatteryFrameLayoutTableSize | 1.3.6.1.4.1.318.1.1.1.15.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of battery frames. | |||||||||||||||||||||
| TupsBatteryFrameLayoutTable | 1.3.6.1.4.1.318.1.1.1.15.5 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Battery frame layout position ID table. | |||||||||||||||||||||
| RupsBatteryFrameLayoutEntry | 1.3.6.1.4.1.318.1.1.1.15.5.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory A list of layout position IDs of battery frames.
| |||||||||||||||||||||
| CbatteryFrameIndex | 1.3.6.1.4.1.318.1.1.1.15.5.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of the battery frame. | |||||||||||||||||||||
| CbatteryFramePositionID | 1.3.6.1.4.1.318.1.1.1.15.5.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Defines the position ID of each of the battery frames in the row. | |||||||||||||||||||||
| SupsSideCarFrameLayoutTableSize | 1.3.6.1.4.1.318.1.1.1.15.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of sidecar frames. | |||||||||||||||||||||
| TupsSideCarFrameLayoutTable | 1.3.6.1.4.1.318.1.1.1.15.7 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Sidecar frame layout position ID table. | |||||||||||||||||||||
| RupsSideCarFrameLayoutEntry | 1.3.6.1.4.1.318.1.1.1.15.7.1 | NA | mandatory | ||||||||||||||||||
| CsideCarFrameIndex | 1.3.6.1.4.1.318.1.1.1.15.7.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of the sidecar frame. | |||||||||||||||||||||
| CsideCarFramePositionID | 1.3.6.1.4.1.318.1.1.1.15.7.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Defines the position ID of each of the sidecar frames in the row. | |||||||||||||||||||||
| SupsPowerFrameLayoutTableSize | 1.3.6.1.4.1.318.1.1.1.15.8 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of power frames. | |||||||||||||||||||||
| TupsPowerFrameLayoutTable | 1.3.6.1.4.1.318.1.1.1.15.9 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Power frame layout position ID table. | |||||||||||||||||||||
| RupsPowerFrameLayoutEntry | 1.3.6.1.4.1.318.1.1.1.15.9.1 | NA | mandatory | ||||||||||||||||||
| CpowerFrameIndex | 1.3.6.1.4.1.318.1.1.1.15.9.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of the power frame. | |||||||||||||||||||||
| CpowerFramePositionID | 1.3.6.1.4.1.318.1.1.1.15.9.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Defines the position ID of each of the power frames in the row. | |||||||||||||||||||||
| NupsIntegratedATS | 1.3.6.1.4.1.318.1.1.1.16 | ||||||||||||||||||||
| SupsIntegratedATSSelectedSource | 1.3.6.1.4.1.318.1.1.1.16.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The source which is currently selected by the ATS to supply the UPS.
| |||||||||||||||||||||
| SupsIntegratedATSPreferredSource | 1.3.6.1.4.1.318.1.1.1.16.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The preferred source of power when both sources are OK.
| |||||||||||||||||||||
| SupsIntegratedATSUpsReturnStaggering | 1.3.6.1.4.1.318.1.1.1.16.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory This is a delay factor applied to the retransfer of this UPS with integrated ATS. When multiple UPS devices are in use from a single source, each UPS can have a unique delay value, which will reduce inrush by preventing all UPS devices from transferring at the same time. | |||||||||||||||||||||
| SupsIntegratedATSSourceTableSize | 1.3.6.1.4.1.318.1.1.1.16.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of input sources for this integrated ATS. | |||||||||||||||||||||
| TupsIntegratedATSSourceTable | 1.3.6.1.4.1.318.1.1.1.16.5 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting status and settings for the ATS input sources. The number of entries is contained in the upsIntegratedATSSourceTableSize OID. | |||||||||||||||||||||
| RupsIntegratedATSSourceEntry | 1.3.6.1.4.1.318.1.1.1.16.5.1 | NA | mandatory | ||||||||||||||||||
| CupsIntegratedATSSourceIndex | 1.3.6.1.4.1.318.1.1.1.16.5.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the input source entry. | |||||||||||||||||||||
| CupsIntegratedATSSourceName | 1.3.6.1.4.1.318.1.1.1.16.5.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The name of the input source. This OID is provided for informational purposes only. | |||||||||||||||||||||
| CupsIntegratedATSSourceStatus | 1.3.6.1.4.1.318.1.1.1.16.5.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this variable will return the input source status.
| |||||||||||||||||||||
| CupsIntegratedATSLineFailDelay | 1.3.6.1.4.1.318.1.1.1.16.5.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The delay between a selected input source becoming bad, and the ATS switching away from that source. This delay is used to make sure that the line has truly failed before the ATS will be switched. Specified in seconds. | |||||||||||||||||||||
| CupsIntegratedATSLineStabilityDelay | 1.3.6.1.4.1.318.1.1.1.16.5.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The delay between an unselected input source becoming good, and the ATS switching to that source. This delay is used to make sure that the line has truly returned before the ATS will be switched. Specified in seconds. | |||||||||||||||||||||
| NupsDCOutput | 1.3.6.1.4.1.318.1.1.1.17 | ||||||||||||||||||||
| NupsDCOutputStatus | 1.3.6.1.4.1.318.1.1.1.17.1 | ||||||||||||||||||||
| SupsDCOutputStatusTableSize | 1.3.6.1.4.1.318.1.1.1.17.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of DC outputs on the UPS. | |||||||||||||||||||||
| TupsDCOutputStatusTable | 1.3.6.1.4.1.318.1.1.1.17.1.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Provides status information on UPS DC outputs. The number of entries is contained in the upsDCOutputStatusTableSize OID. | |||||||||||||||||||||
| RupsDCOutputStatusEntry | 1.3.6.1.4.1.318.1.1.1.17.1.2.1 | NA | mandatory | ||||||||||||||||||
| CupsDCOutputStatusTableIndex | 1.3.6.1.4.1.318.1.1.1.17.1.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the DC output status entry. | |||||||||||||||||||||
| CupsDCOutputStatusVoltageNominal | 1.3.6.1.4.1.318.1.1.1.17.1.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The desired voltage for this output in tenths of VDC. When the output is on and there are no fault conditions, the actual voltage should be near the nominal. If not supported, return -1. | |||||||||||||||||||||
| CupsDCOutputStatusCurrentRating | 1.3.6.1.4.1.318.1.1.1.17.1.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The amount of current this output is able to supply in tenths of amperes. If not supported, return -1. | |||||||||||||||||||||
| CupsDCOutputStatusVoltage | 1.3.6.1.4.1.318.1.1.1.17.1.2.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The voltage measured on this output in tenths of VDC. If not supported, return -1. | |||||||||||||||||||||
| CupsDCOutputStatusCurrent | 1.3.6.1.4.1.318.1.1.1.17.1.2.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The current drawn by the load measured on this output in tenths of amperes. If not supported, return -1. | |||||||||||||||||||||
| CupsDCOutputStatusAbnormalConditions | 1.3.6.1.4.1.318.1.1.1.17.1.2.1.6 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory An ASCII string containing flags representing active output faults. If the Network Card is unable to determine the state of the faults, this variable is set to 'UNKNOWN'. The flags are numbered 1 onward, read from left to right. The flags are defined as follows starting from 1: Flag 1: Output Overload Flag 2: Output Short Circuit Flag 3: Output Over Voltage Flag 4: <Not Used> Flag 5: Overtemperature Flag 6: Backfeed Relay Fault Flag 7: <Not Used> Flag 8: PFC Input Relay Fault Flag 9: <Not Used> Flag 10: Bypass Relay Fault Flag 11: <Not Used> Flag 12: <Not Used> Flag 13: <Not Used> Flag 14: <Not Used> Flag 15: <Not Used> Flag 16: <Not Used> Flag 17: <Not Used> Flag 18: <Not Used> Flag 19: Output Fault (over or undervoltage) Flag 20: Bus Converter Fault Flag 21: Sensor Fault Flag 21: <Not Used> Flag 22: <Not Used> Flag 23: <Not Used> Flag 24: <Not Used> Flag 25: <Not Used> Flag 26: <Not Used> Flag 27: <Not Used> Flag 28: <Not Used> Flag 29: <Not Used> Flag 30: <Not Used> Flag 31: <Not Used> Flag 32: <Not Used> | |||||||||||||||||||||
| NupsIntegratedUIO | 1.3.6.1.4.1.318.1.1.1.18 | ||||||||||||||||||||
| NupsOutputRelays | 1.3.6.1.4.1.318.1.1.1.18.1 | ||||||||||||||||||||
| SupsOutputRelayStatusTableSize | 1.3.6.1.4.1.318.1.1.1.18.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of integrated output relays on the UPS. | |||||||||||||||||||||
| TupsOutputRelayStatusTable | 1.3.6.1.4.1.318.1.1.1.18.1.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for access of individual relays. | |||||||||||||||||||||
| RupsOutputRelayStatusEntry | 1.3.6.1.4.1.318.1.1.1.18.1.2.1 | NA | mandatory | ||||||||||||||||||
| CupsOutputRelayIndex | 1.3.6.1.4.1.318.1.1.1.18.1.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the output relay entry. | |||||||||||||||||||||
| CupsOutputRelayState | 1.3.6.1.4.1.318.1.1.1.18.1.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this variable will return the output relay state. 1 - normal state 2 - abnormal state
| |||||||||||||||||||||
| CupsOutputRelayDetailedStatus | 1.3.6.1.4.1.318.1.1.1.18.1.2.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory An ASCII string containing the 16 flags representing the status of the output relay. The flags are numbered from 1 to 16, and read from left to right. The bits are defined as follows: Flag 1: Cause is true which makes the output relay active if not pending a condition Flag 2: Pending delay Flag 3: Pending peak period Flag 4: <Not Used> Flag 5: <Not Used> Flag 6: <Not Used> Flag 7: <Not Used> Flag 8: <Not Used> Flag 9: <Not Used> Flag 10: <Not Used> Flag 11: <Not Used> Flag 12: <Not Used> Flag 13: <Not Used> Flag 14: <Not Used> Flag 15: <Not Used> Flag 16: <Not Used> | |||||||||||||||||||||
| SupsOutputRelayConfigTableSize | 1.3.6.1.4.1.318.1.1.1.18.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of integrated output relays on the UPS. | |||||||||||||||||||||
| TupsOutputRelayConfigTable | 1.3.6.1.4.1.318.1.1.1.18.1.4 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for access of individual relays. | |||||||||||||||||||||
| RupsOutputRelayConfigEntry | 1.3.6.1.4.1.318.1.1.1.18.1.4.1 | NA | mandatory | ||||||||||||||||||
| CupsOutputRelayConfigIndex | 1.3.6.1.4.1.318.1.1.1.18.1.4.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the output relay entry. | |||||||||||||||||||||
| CupsOutputRelayConfigDelay | 1.3.6.1.4.1.318.1.1.1.18.1.4.1.2 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Output relay delay 0 - 86400 seconds. | |||||||||||||||||||||
| CupsOutputRelayConfigCause | 1.3.6.1.4.1.318.1.1.1.18.1.4.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory This variable sets what causes the output relay state to change. 1 - none 2 - on battery power failure 3 - on battery power failure expect during peak period 4 - low battery while on battery 5 - alarm 6 - fault 7 - output on 8 - output off 9 - online 10 - in bypass
| |||||||||||||||||||||
| SupsOutputRelayConfigPolarity | 1.3.6.1.4.1.318.1.1.1.18.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Configures all output relays with one setting. 1 - all relays act normally open, when logic condition is true, relays are energized 2 - all relays act normally close, when logic condition is true relays are deenergized
| |||||||||||||||||||||
| SupsOutputRelayConfigPeakPeriod | 1.3.6.1.4.1.318.1.1.1.18.1.6 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory An ASCII string containing the 64 flags representing the peak period setting of the UPS. Flags are numbered 1-64 starting from the left. Each flag is either a '1', representing a flag that is set, or a '0', representing a flag that is /not/ set. The peak period intervals are times that are both: - on the days of the week set by the first 7 flags AND - within the time periods set by the remaining flags. UPS output relays triggered by 'On battery except peak period' will not signal when the UPS is on battery during a peak period. The flags are defined as follows: Flag 1: Sunday Flag 2: Monday Flag 3: Tuesday Flag 4: Wednesday Flag 5: Thursday Flag 6: Friday Flag 7: Saturday Flag 8: 00:00-00:29 Flag 9: 00:30-00:59 Flag 10: 01:00-01:29 Flag 11: 01:30-01:59 Flag 12: 02:00-02:29 Flag 13: 02:30-02:59 Flag 14: 03:00-03:29 Flag 15: 03:30-03:59 Flag 16: 04:00-04:29 Flag 17: 04:30-04:59 Flag 18: 05:00-05:29 Flag 19: 05:30-05:59 Flag 20: 06:00-06:29 Flag 21: 06:30-06:59 Flag 22: 07:00-07:29 Flag 23: 07:30-07:59 Flag 24: 08:00-08:29 Flag 25: 08:30-08:59 Flag 26: 09:00-09:29 Flag 27: 09:30-09:59 Flag 28: 10:00-00:29 Flag 29: 10:30-10:59 Flag 30: 11:00-11:29 Flag 31: 11:30-11:59 Flag 32: 12:00-12:29 Flag 33: 12:30-12:59 Flag 34: 13:00-13:29 Flag 35: 13:30-13:59 Flag 36: 14:00-14:29 Flag 37: 14:30-14:59 Flag 38: 15:00-15:29 Flag 39: 15:30-15:59 Flag 40: 16:00-16:29 Flag 41: 16:30-16:59 Flag 42: 17:00-17:29 Flag 43: 17:30-17:59 Flag 44: 18:00-18:29 Flag 45: 18:30-18:59 Flag 46: 19:00-19:29 Flag 47: 19:30-19:59 Flag 48: 20:00-20:29 Flag 49: 20:30-20:59 Flag 50: 21:00-21:29 Flag 51: 21:30-21:59 Flag 52: 22:00-22:29 Flag 53: 22:30-22:59 Flag 54: 23:00-23:29 Flag 55: 23:30-23:59 Flag 56: <Not Used> Flag 57: <Not Used> Flag 58: <Not Used> Flag 59: <Not Used> Flag 60: <Not Used> Flag 61: <Not Used> Flag 62: <Not Used> Flag 63: <Not Used> Flag 64: <Not Used> To set this OID you can either: - set the 64 flag bits as an ASCII string of '1's and '0's as described above. The same format is used when this OID is read. - or turn on/off an individual flags. Examples: Set for Sundays and Tuesdays from 00:00-01:29: 1010000111000000000000000000000000000000000000000000000000000000 Set Mondays to be part of the peak periods: +2 Set Tuesdays to not be part of the peak periods: -3 Include interval 23:30-23:59 in the peak period: +55 | |||||||||||||||||||||
| NupsInputContacts | 1.3.6.1.4.1.318.1.1.1.18.2 | ||||||||||||||||||||
| SupsInputContactStatusTableSize | 1.3.6.1.4.1.318.1.1.1.18.2.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of integrated input contacts on the UPS. | |||||||||||||||||||||
| TupsInputContactStatusTable | 1.3.6.1.4.1.318.1.1.1.18.2.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for access of individual contacts. | |||||||||||||||||||||
| RupsInputContactStatusEntry | 1.3.6.1.4.1.318.1.1.1.18.2.2.1 | NA | mandatory | ||||||||||||||||||
| CupsInputContactIndex | 1.3.6.1.4.1.318.1.1.1.18.2.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the input contact entry. | |||||||||||||||||||||
| CupsInputContactState | 1.3.6.1.4.1.318.1.1.1.18.2.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this variable will return the input contact state. 1 - normal state 2 - abnormal state
| |||||||||||||||||||||
| SupsInputContactConfigTableSize | 1.3.6.1.4.1.318.1.1.1.18.2.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of integrated input contacts on the UPS. | |||||||||||||||||||||
| TupsInputContactConfigTable | 1.3.6.1.4.1.318.1.1.1.18.2.4 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for access of individual contacts. | |||||||||||||||||||||
| RupsInputContactConfigEntry | 1.3.6.1.4.1.318.1.1.1.18.2.4.1 | NA | mandatory | ||||||||||||||||||
| CupsInputContactConfigIndex | 1.3.6.1.4.1.318.1.1.1.18.2.4.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the input contact entry. | |||||||||||||||||||||
| CupsInputContactConfigAction | 1.3.6.1.4.1.318.1.1.1.18.2.4.1.2 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory When the input contact changes state, this action occurs. 1 - none 2 - self test 3 - external alarm on 4 - external alarm off 5 - output off no delay 6 - output on
| |||||||||||||||||||||
| SupsInputContactConfigPolarity | 1.3.6.1.4.1.318.1.1.1.18.2.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Configures all input contacts with one setting. 1 - all contacts act as normally open 2 - all contacts act as normally closed
| |||||||||||||||||||||
| NupsEnergyEfficiency | 1.3.6.1.4.1.318.1.1.1.20 | ||||||||||||||||||||
| NupsECOmode | 1.3.6.1.4.1.318.1.1.1.20.1 | ||||||||||||||||||||
| SupsEcoModeFreqTransferRange | 1.3.6.1.4.1.318.1.1.1.20.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Indicates tolerance of bypass AC frequency in Hz to switch on ECO mode. | |||||||||||||||||||||
| SupsEcoModeHighVoltThreshold | 1.3.6.1.4.1.318.1.1.1.20.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Indicates high threshold on AC voltage in volts to switch on ECO mode. | |||||||||||||||||||||
| SupsEcoModeLowVoltThreshold | 1.3.6.1.4.1.318.1.1.1.20.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Indicates low threshold on AC voltage in volts to switch on ECO mode. | |||||||||||||||||||||
| SupsEcoModeSetting | 1.3.6.1.4.1.318.1.1.1.20.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Indicates whether ECO feature is avaiable to this UPS or not.
| |||||||||||||||||||||
| SupsEcoModeStatus | 1.3.6.1.4.1.318.1.1.1.20.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Indicates whether UPS is running in ECO mode or not.
| |||||||||||||||||||||
| SupsEcoModeCountSinceReset | 1.3.6.1.4.1.318.1.1.1.20.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Number of times UPS entered into ECO mode since maintenance reset. | |||||||||||||||||||||
| SupsEcoModeOnlineSinceCommission | 1.3.6.1.4.1.318.1.1.1.20.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Total runtime in online mode with ECO feature enabled once product is authorized to use (in minutes). | |||||||||||||||||||||
| SupsEcoModeOnlineSinceReset | 1.3.6.1.4.1.318.1.1.1.20.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Total runtime in online mode with ECO feature enabled since maintenance reset (in minutes). | |||||||||||||||||||||
| SupsEcoModeTotalPercentTimeSinceReset | 1.3.6.1.4.1.318.1.1.1.20.1.9 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Indicates percentage of runtime in ECO mode since maintenance reset. | |||||||||||||||||||||
| SupsEcoModePercentTimeSinceCommission | 1.3.6.1.4.1.318.1.1.1.20.1.10 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Indicates percentage of operation time in ECO mode once product is authorized to use. | |||||||||||||||||||||
| SupsEcoModeTotalTimeSinceReset | 1.3.6.1.4.1.318.1.1.1.20.1.11 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Total runtime of UPS in ECO mode since maintenance reset (in minutes). | |||||||||||||||||||||
| SupsEcoModeTotalTimeSinceCommission | 1.3.6.1.4.1.318.1.1.1.20.1.12 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Total runtime in ECO mode once product is authorized to use (in minutes). | |||||||||||||||||||||
| SupsEcoModeTotalTimeInMonth | 1.3.6.1.4.1.318.1.1.1.20.1.13 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Total runtime of UPS in ECO mode since beginning of month (in minutes). | |||||||||||||||||||||
| NupsEBMmode | 1.3.6.1.4.1.318.1.1.1.20.2 | ||||||||||||||||||||
| SupsEbmModeSetting | 1.3.6.1.4.1.318.1.1.1.20.2.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Indicates whether efficiency booster mode feature is avaiable to this UPS or not.
| |||||||||||||||||||||
| SupsEbmModeStatus | 1.3.6.1.4.1.318.1.1.1.20.2.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Indicates whether UPS is running on EBM mode or not.
| |||||||||||||||||||||
| SupsEbmModeCountSinceReset | 1.3.6.1.4.1.318.1.1.1.20.2.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Number of times UPS entered into efficiency booster mode since maintenance reset. | |||||||||||||||||||||
| SupsEbmModeTotalTimeInMonth | 1.3.6.1.4.1.318.1.1.1.20.2.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Total runtime of UPS in efficiency booster mode since beginning of month (in minutes). | |||||||||||||||||||||
| SupsEbmModeTotalTimeSinceReset | 1.3.6.1.4.1.318.1.1.1.20.2.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Total runtime of UPS in efficiency booster mode since maintenance reset (in minutes). | |||||||||||||||||||||
| SupsEbmModeTotalPercentTimeSinceReset | 1.3.6.1.4.1.318.1.1.1.20.2.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Indicates percentage of runtime in efficiency booster mode since maintenance reset. | |||||||||||||||||||||
| SupsEbmModeOnlineSinceCommission | 1.3.6.1.4.1.318.1.1.1.20.2.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Indicates runtime in online mode with EBM feature enabled once product is authorized to use (in minutes). | |||||||||||||||||||||
| SupsEbmModePercentTimeSinceCommission | 1.3.6.1.4.1.318.1.1.1.20.2.8 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Indicates percentage of operation time in efficiency booster mode once product is authorized to use. | |||||||||||||||||||||
| SupsEbmModeRuntimeSinceCommission | 1.3.6.1.4.1.318.1.1.1.20.2.9 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Total runtime in efficiency booster mode once product is authorized to use (in minutes). | |||||||||||||||||||||
| SupsEbmModeOnlineSinceReset | 1.3.6.1.4.1.318.1.1.1.20.2.10 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Total runtime in online mode with EBM feature enabled since maintenance reset (in minutes). | |||||||||||||||||||||
| SupsEbmModeUpsCount | 1.3.6.1.4.1.318.1.1.1.20.2.11 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Number of UPS devices running in efficiency booster mode. | |||||||||||||||||||||
| NupsStatistics | 1.3.6.1.4.1.318.1.1.1.22 | ||||||||||||||||||||
| NupsBatteryStats | 1.3.6.1.4.1.318.1.1.1.22.1 | ||||||||||||||||||||
| SupsBatteryStatsReset | 1.3.6.1.4.1.318.1.1.1.22.1.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Setting this OID to reset(3) will reset the Battery Stats timer. Getting this OID will return: notSupported(1) - reset feature is not supported. noOperation(2) - indicates reset is supported, does nothing.
| |||||||||||||||||||||
| SupsBatteryStatsTimeSinceReset | 1.3.6.1.4.1.318.1.1.1.22.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Time since battery timer reset (in minutes). | |||||||||||||||||||||
| SupsBatteryStatsTimeOnBattery | 1.3.6.1.4.1.318.1.1.1.22.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Total time for UPS in battery operation (in minutes). | |||||||||||||||||||||
| NupsOperationalStats | 1.3.6.1.4.1.318.1.1.1.22.2 | ||||||||||||||||||||
| SupsOpStatsReset | 1.3.6.1.4.1.318.1.1.1.22.2.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Setting this OID to reset(3) will reset the Operational Stats timer. Getting this OID will return: notSupported(1) - reset feature is not supported. noOperation(2) - indicates reset is supported, does nothing.
| |||||||||||||||||||||
| SupsOpStatsTimeSinceReset | 1.3.6.1.4.1.318.1.1.1.22.2.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Time since timer reset (in minutes). | |||||||||||||||||||||
| SupsOpStatsTimeInNormalOperation | 1.3.6.1.4.1.318.1.1.1.22.2.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Total time for UPS in normal operation since timer reset via upsOpStatsReset (in minutes). | |||||||||||||||||||||
| SupsOpStatsTimeInBypassOperation | 1.3.6.1.4.1.318.1.1.1.22.2.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Total time for UPS in bypass operation since timer reset via upsOpStatsReset (in minutes). | |||||||||||||||||||||
| SupsOpStatsTimeInECOmodeOperation | 1.3.6.1.4.1.318.1.1.1.22.2.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Total time for UPS in ECO mode since timer reset via upsOpStatsReset (in minutes). | |||||||||||||||||||||
| SupsOpStatsTimeInEconversionOperation | 1.3.6.1.4.1.318.1.1.1.22.2.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Total time for UPS in eConversion since timer reset via upsOpStatsReset (in minutes). | |||||||||||||||||||||
| NupsEnergyEfficiencyStats | 1.3.6.1.4.1.318.1.1.1.22.3 | ||||||||||||||||||||
| SupsEnergyEfficiencyStatsReset | 1.3.6.1.4.1.318.1.1.1.22.3.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Setting this OID to reset(3) will reset the Energy Efficiency Stats timer. Getting this OID will return: notSupported(1) - reset feature is not supported. noOperation(2) - indicates reset is supported, does nothing.
| |||||||||||||||||||||
| SupsEnergyEfficiencyStatsOutputEnergyTimeSinceReset | 1.3.6.1.4.1.318.1.1.1.22.3.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Time (in minutes) since last timer reset of the OID upsEnergyEfficiencyStatsOutputEnergyUsage | |||||||||||||||||||||
| SupsEnergyEfficiencyStatsTimeInECOmode | 1.3.6.1.4.1.318.1.1.1.22.3.3 | INTEGER | RO | optional | |||||||||||||||||
scalar · INTEGER · read-only · optional Total time (in minutes) for UPS in ECO mode since last timer reset via upsEnergyEfficiencyStatsReset | |||||||||||||||||||||
| SupsEnergyEfficiencyStatsTimeInEconversion | 1.3.6.1.4.1.318.1.1.1.22.3.4 | INTEGER | RO | optional | |||||||||||||||||
scalar · INTEGER · read-only · optional Total time (in minutes) for UPS in eConversion since last timer reset via upsEnergyEfficiencyStatsReset | |||||||||||||||||||||
| SupsEnergyEfficiencyStatsInputEnergyUsage | 1.3.6.1.4.1.318.1.1.1.22.3.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The input energy usage of the UPS in kWh since timer reset. | |||||||||||||||||||||
| SupsEnergyEfficiencyStatsOutputEnergyUsage | 1.3.6.1.4.1.318.1.1.1.22.3.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The output energy usage of the UPS in kWh since timer reset. | |||||||||||||||||||||
| SupsEnergyEfficiencyStatsInputEnergyTimeSinceReset | 1.3.6.1.4.1.318.1.1.1.22.3.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Time (in minutes) since last timer reset of the OID upsEnergyEfficiencyStatsInputEnergyUsage | |||||||||||||||||||||
| SupsEnergyEfficiencyStatsECOmodeTimeSinceReset | 1.3.6.1.4.1.318.1.1.1.22.3.8 | INTEGER | RO | optional | |||||||||||||||||
scalar · INTEGER · read-only · optional Time (in minutes) since last timer reset of the OID upsEnergyEfficiencyStatsTimeInECOmode | |||||||||||||||||||||
| SupsEnergyEfficiencyStatsEconversionTimeSinceReset | 1.3.6.1.4.1.318.1.1.1.22.3.9 | INTEGER | RO | optional | |||||||||||||||||
scalar · INTEGER · read-only · optional Time (in minutes) since last timer reset of the OID upsEnergyEfficiencyStatsTimeInEconversion | |||||||||||||||||||||
| NmeasureUps | 1.3.6.1.4.1.318.1.1.2 | ||||||||||||||||||||
| NmUpsEnviron | 1.3.6.1.4.1.318.1.1.2.1 | ||||||||||||||||||||
| SmUpsEnvironAmbientTemperature | 1.3.6.1.4.1.318.1.1.2.1.1 | Gauge | RO | mandatory | |||||||||||||||||
scalar · Gauge · read-only · mandatory The ambient temperature in Celsius for Probe 1. | |||||||||||||||||||||
| SmUpsEnvironRelativeHumidity | 1.3.6.1.4.1.318.1.1.2.1.2 | Gauge | RO | mandatory | |||||||||||||||||
scalar · Gauge · read-only · mandatory The relative humidity as a percentage for Probe 1. | |||||||||||||||||||||
| SmUpsEnvironAmbientTemperature2 | 1.3.6.1.4.1.318.1.1.2.1.3 | Gauge | RO | mandatory | |||||||||||||||||
scalar · Gauge · read-only · mandatory The ambient temperature in Celsius for Probe 2. | |||||||||||||||||||||
| SmUpsEnvironRelativeHumidity2 | 1.3.6.1.4.1.318.1.1.2.1.4 | Gauge | RO | mandatory | |||||||||||||||||
scalar · Gauge · read-only · mandatory The relative humidity as a percentage for Probe 2. | |||||||||||||||||||||
| NmUpsContact | 1.3.6.1.4.1.318.1.1.2.2 | ||||||||||||||||||||
| SmUpsContactNumContacts | 1.3.6.1.4.1.318.1.1.2.2.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of contacts supported by the Measure-UPS. | |||||||||||||||||||||
| TmUpsContactTable | 1.3.6.1.4.1.318.1.1.2.2.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of contacts supported by the Measure-UPS. | |||||||||||||||||||||
| RmUpsContactEntry | 1.3.6.1.4.1.318.1.1.2.2.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory A contact entry containing information for a given contact.
| |||||||||||||||||||||
| CcontactNumber | 1.3.6.1.4.1.318.1.1.2.2.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory An index identifying the contact on the Measure-UPS. | |||||||||||||||||||||
| CnormalState | 1.3.6.1.4.1.318.1.1.2.2.2.1.2 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The normal operating position of the contact. If the normal operating position cannot be set then it is controlled via the dip switch on the Measure-UPS and is therefore read-only.
| |||||||||||||||||||||
| Cdescription | 1.3.6.1.4.1.318.1.1.2.2.2.1.3 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The description of the purpose/use of the contact. | |||||||||||||||||||||
| CmonitoringStatus | 1.3.6.1.4.1.318.1.1.2.2.2.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory A flag indicating whether this contact is monitored, or not.
| |||||||||||||||||||||
| CcurrentStatus | 1.3.6.1.4.1.318.1.1.2.2.2.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This value indicates the current state of the contact. If the contact is not in its normal state. This value is set to fault(2).
| |||||||||||||||||||||
| NminiSNMPadapter | 1.3.6.1.4.1.318.1.1.3 | ||||||||||||||||||||
| NserialPort | 1.3.6.1.4.1.318.1.1.3.1 | ||||||||||||||||||||
| NserialPort1 | 1.3.6.1.4.1.318.1.1.3.1.1 | ||||||||||||||||||||
| NserialPort2 | 1.3.6.1.4.1.318.1.1.3.1.2 | ||||||||||||||||||||
| NserialPort2Config | 1.3.6.1.4.1.318.1.1.3.1.2.1 | ||||||||||||||||||||
| SserialPort2Mode | 1.3.6.1.4.1.318.1.1.3.1.2.1.1 | INTEGER | RW | obsolete | 0 | ||||||||||||||||
scalar · INTEGER · read-write · obsolete Setting this variable to passthrough will enable mini's port2 behave like a UPS port. Choosing localConsole will enable the port to be used as local console.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NserialPort2Control | 1.3.6.1.4.1.318.1.1.3.1.2.2 | ||||||||||||||||||||
| SsetPulseOnTXD | 1.3.6.1.4.1.318.1.1.3.1.2.2.1 | INTEGER | RW | obsolete | |||||||||||||||||
scalar · INTEGER · read-write · obsolete Setting this variable to setPulseOnTXD(2) causes adapter to generate a PULSE on TXD pin of serial port 2. The duration in the prototype implementation will be 1 second. Setting this value to noSetPulseOnTXD(1) has no effect. The value noSetPulseOnTXD(1) will always be returned when the variable is read. Setting this value to setTXDLow(3), or setTXDHigh(4) will keep TXD always low or high respectively.
| |||||||||||||||||||||
| Nmasterswitch | 1.3.6.1.4.1.318.1.1.4 | ||||||||||||||||||||
| NsPDUIdent | 1.3.6.1.4.1.318.1.1.4.1 | ||||||||||||||||||||
| SsPDUIdentHardwareRev | 1.3.6.1.4.1.318.1.1.4.1.1 | DisplayString | RO | mandatory | B2 | ||||||||||||||||
scalar · DisplayString · read-only · mandatory The hardware revision of the PDU. This value is set at the factory. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SsPDUIdentFirmwareRev | 1.3.6.1.4.1.318.1.1.4.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory An 8 byte ID string identifying the PDU firmware revision. This value is set at the factory. | |||||||||||||||||||||
| SsPDUIdentDateOfManufacture | 1.3.6.1.4.1.318.1.1.4.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The date when the PDU was manufactured in mm/dd/yy format. This value is set at the factory. The year 2000 will be represented by 00. | |||||||||||||||||||||
| SsPDUIdentModelNumber | 1.3.6.1.4.1.318.1.1.4.1.4 | DisplayString | RO | mandatory | AP7900B | ||||||||||||||||
scalar · DisplayString · read-only · mandatory A 10-character string identifying the model number of the PDU internal. This value is set at the factory. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SsPDUIdentSerialNumber | 1.3.6.1.4.1.318.1.1.4.1.5 | DisplayString | RO | mandatory | ZA1732000177 | ||||||||||||||||
scalar · DisplayString · read-only · mandatory A 12-character string identifying the serial number of the PDU internal microprocessor. This value is set at the factory. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NsPDUMasterControl | 1.3.6.1.4.1.318.1.1.4.2 | ||||||||||||||||||||
| SsPDUMasterControlSwitch | 1.3.6.1.4.1.318.1.1.4.2.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Setting this OID to turnAllOnNow (1) will turn all outlets on immediately. Setting this OID to turnAllOnSequence (2) will turn all outlets on as defined by each outlet's sPDUOutletPowerOnTime OID value. Setting this OID to turnAllOff (3) will turn all outlets off immediately. Setting this OID to rebootAllNow (4) will reboot all outlets immediately. For MasterSwitch firmware version 1.X, setting this OID to rebootAllSequence (5) reboots all outlets, with power returned to the outlets in the sequence defined by each outlet's sPDUOutletPowerOnTime OID value. For MasterSwitch firmware version 2.X, setting this OID to rebootAllSequence (5) will cause a turnAllOffSequence to be performed. Once all outlets are off, the MasterSwitch will then delay the sPDUMasterConfigReboot OID time, and then perform a turnAllOnSequence. For MasterSwitch firmware version 2.X, setting this OID to turnAllOffSequence (7) will turn all outlets off as defined by each outlet's sPDUOutletPowerOffTime OID value. For MasterSwitch firmware version 1.X, setting this OID to turnAllOffSequence (7) will have no effect. Getting this OID will return the noCommand (6) value.
| |||||||||||||||||||||
| SsPDUMasterState | 1.3.6.1.4.1.318.1.1.4.2.2 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory Getting this OID will cause the status of all outlets to be returned. This OID is provided for informational purposes only. To change the outlet state, the user should use the sPDUOutletCtl OID in the sPDUOutletControlTable. The format of the data returned is a character string consisting of the word 'On' if the outlet is on or 'Off' if the outlet is off. At least one space will delimit each outlet entry in the string. If the outlet states are unknown, the character string 'Unknown' will be returned. This signifies that there is an inconsistency in the PDU. In the rare case that this should happen, the user is advised to shut down all equipment powered by the PDU and then cycle the PDU's power. This will put the PDU in a consistent state. | |||||||||||||||||||||
| SsPDUMasterPending | 1.3.6.1.4.1.318.1.1.4.2.3 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory Getting this OID will cause the command pending status of all outlets to be returned. The format of the data returned is a character string consisting of the word 'Yes' if a command is pending for the outlet or 'No' if there is no command pending for the outlet. At least one space will delimit each outlet entry in the string. If the pending states are unknown, the character string 'Unknown' will be returned. This signifies that there is an inconsistency in the PDU. In the rare case that this should happen, the user is advised to shut down all equipment powered by the PDU and then cycle the PDU's power. This will put the PDU in a consistent state. | |||||||||||||||||||||
| NsPDUMasterConfig | 1.3.6.1.4.1.318.1.1.4.3 | ||||||||||||||||||||
| SsPDUMasterConfigPowerOn | 1.3.6.1.4.1.318.1.1.4.3.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The amount of delay, in seconds, between when power is provided to the PDU and when the PDU provides basic master power to the outlets. Allowed values are: -1 never apply power automatically. 0 apply power immediately. 15 apply power in 15 seconds. 30 apply power in 30 seconds. 45 apply power in 45 seconds. 60 apply power in 60 seconds (1 minute). 120 apply power in 120 seconds (2 minutes). 300 apply power in 300 seconds (5 minutes). If a value other than a supported value is provided in a set request, the PDU interprets it as the next lower acceptable value. If the provided value is lower than the lowest acceptable value, the lowest acceptable value is used. | |||||||||||||||||||||
| SsPDUMasterConfigReboot | 1.3.6.1.4.1.318.1.1.4.3.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory During a reboot sequence, power is turned off and then back on. This OID defines the amount of time to wait, in seconds, after turning the power off, at the start of the sequence, before turning power back on, at the end of the reboot sequence. Allowed values are: 5 wait 5 seconds between off/on. 10 wait 10 seconds between off/on. 15 wait 15 seconds between off/on. 20 wait 20 seconds between off/on. 30 wait 30 seconds between off/on. 45 wait 45 seconds between off/on. 60 wait 60 seconds (1 minute) between off/on. If a value other than a supported value is provided in a set request, the PDU interprets it as the next lower acceptable value. If the provided value is lower than the lowest acceptable value, the lowest acceptable value is used. This OID is read-only for the MasterSwitch version 2.X and is the maximum sPDUOutletRebootDuration OID of the individual outlets. | |||||||||||||||||||||
| SsPDUMasterConfigPDUName | 1.3.6.1.4.1.318.1.1.4.3.3 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory The name of the PDU. | |||||||||||||||||||||
| NsPDUOutletControl | 1.3.6.1.4.1.318.1.1.4.4 | ||||||||||||||||||||
| SsPDUOutletControlTableSize | 1.3.6.1.4.1.318.1.1.4.4.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of outlets for the PDU. | |||||||||||||||||||||
| TsPDUOutletControlTable | 1.3.6.1.4.1.318.1.1.4.4.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for control of individual outlet switches. The number of entries is contained in the sPDUOutletControlTableSize OID. | |||||||||||||||||||||
| RsPDUOutletControlEntry | 1.3.6.1.4.1.318.1.1.4.4.2.1 | NA | mandatory | ||||||||||||||||||
| CsPDUOutletControlIndex | 1.3.6.1.4.1.318.1.1.4.4.2.1.1 | INTEGER | RO | mandatory | 1 | ||||||||||||||||
column · INTEGER · read-only · mandatory The index to the outlet entry. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CsPDUOutletPending | 1.3.6.1.4.1.318.1.1.4.4.2.1.2 | INTEGER | RO | mandatory | noCommandPending(2) | ||||||||||||||||
column · INTEGER · read-only · mandatory Reports whether the current outlet has a pending command. If the commandPendingUnknown (3) value is returned, all devices powered by the PDU should be shut down. The PDU's power should then be cycled to clear this condition.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CsPDUOutletCtl | 1.3.6.1.4.1.318.1.1.4.4.2.1.3 | INTEGER | RW | mandatory | outletOn(1) | ||||||||||||||||
column · INTEGER · read-write · mandatory Getting this variable will return the outlet state. If the outlet is on, the outletOn (1) value will be returned. If the outlet is off, the outletOff (2) value will be returned. If the state of the outlet cannot be determined, the outletUnknown (4) value will be returned. If the outletUnknown condition should occur, all devices powered by the PDU should be shut down. The PDU's power should then be cycled to clear this condition. Setting this variable to outletOn (1) will turn the outlet on. Setting this variable to outletOff (2) will turn the outlet off. Setting this variable to outletReboot (3) will reboot the outlet. Setting this variable to outletOnWithDelay (5) will turn the outlet on after the sPDUOutletPowerOnTime OID has elapsed. This option is not valid for MasterSwitch firmware version 1.X. Setting this variable to outletOffWithDelay (6) will turn the outlet off after the sPDUOutletPowerOffTime OID has elapsed. This option is not valid for MasterSwitch firmware version 1.X. Setting this variable to outletRebootWithDelay (7) will turn the outlet off after the sPDUOutletPowerOffTime OID has elapsed, wait the sPDUOutletRebootDuration OID time, then turn the outlet back on. This option is not valid for MasterSwitch firmware version 1.X.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CsPDUOutletCtlName | 1.3.6.1.4.1.318.1.1.4.4.2.1.4 | DisplayString | RO | mandatory | NAS PSU | ||||||||||||||||
column · DisplayString · read-only · mandatory The name of the outlet. Maximum size is 20 characters. This OID is provided for informational purposes only. This value is set by the sPDUOutletName OID. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NsPDUOutletConfig | 1.3.6.1.4.1.318.1.1.4.5 | ||||||||||||||||||||
| SsPDUOutletConfigTableSize | 1.3.6.1.4.1.318.1.1.4.5.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of outlets for the PDU. | |||||||||||||||||||||
| TsPDUOutletConfigTable | 1.3.6.1.4.1.318.1.1.4.5.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory The list of outlets to configure. The number of entries is defined by the sPDUOutletConfigTableSize OID. | |||||||||||||||||||||
| RsPDUOutletConfigEntry | 1.3.6.1.4.1.318.1.1.4.5.2.1 | NA | mandatory | ||||||||||||||||||
| CsPDUOutletConfigIndex | 1.3.6.1.4.1.318.1.1.4.5.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the outlet entry. | |||||||||||||||||||||
| CsPDUOutletPowerOnTime | 1.3.6.1.4.1.318.1.1.4.5.2.1.2 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The amount of time (in seconds) the outlet will delay powering on when the MasterSwitch is powered on. Allowed values are: -1 never power on automatically. 0 power on with the Master Switch. 15 power on 15 seconds after the MasterSwitch has power applied. 30 power on 30 seconds after the MasterSwitch has power applied. 45 power on 45 seconds after the MasterSwitch has power applied. 60 power on 60 seconds (1 minute) after the MasterSwitch has power applied. 120 power on 120 seconds (2 minutes) after the MasterSwitch has power applied. 300 power on 300 seconds (5 minutes) after the MasterSwitch has power applied. If a value other than a supported value is provided in a set request, the PDU interprets it as the next lower acceptable value. If the provided value is lower than the lowest acceptable value, the lowest acceptable value is used. | |||||||||||||||||||||
| CsPDUOutletName | 1.3.6.1.4.1.318.1.1.4.5.2.1.3 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The name of the outlet. Maximum size is 20 characters. | |||||||||||||||||||||
| CsPDUOutletPowerOffTime | 1.3.6.1.4.1.318.1.1.4.5.2.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The amount of time (in seconds) the outlet will delay powering off. Allowed values are: -1 never power off automatically. 0 power off with the MasterSwitch. 15 power off 15 seconds after being commanded. 30 power off 30 seconds after being commanded. 45 power off 45 seconds after being commanded. 60 power off 60 seconds (1 minute) after being commanded. 120 power off 120 seconds (2 minutes) after being commanded. 300 power off 300 seconds (5 minutes) after being commanded. If a value other than a supported value is provided in a set request, the PDU interprets it as the next lower acceptable value. If the provided value is lower than the lowest acceptable value, the lowest acceptable value is used. This OID is not available for MasterSwitch firmware version 1.X. | |||||||||||||||||||||
| CsPDUOutletRebootDuration | 1.3.6.1.4.1.318.1.1.4.5.2.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory During a reboot sequence, power is turned off and then back on. This OID defines the amount of time to wait, in seconds, after turning the power off, at the start of the sequence, before turning power back on, at the end of the reboot sequence. Allowed values are: 5 wait 5 seconds between off/on. 10 wait 10 seconds between off/on. 15 wait 15 seconds between off/on. 20 wait 20 seconds between off/on. 30 wait 30 seconds between off/on. 45 wait 45 seconds between off/on. 60 wait 60 seconds (1 minute) between off/on. If a value other than a supported value is provided in a set request, the PDU interprets it as the next lower acceptable value. If the provided value is lower than the lowest acceptable value, the lowest acceptable value is used. This OID is not available for MasterSwitch firmware version 1.X. | |||||||||||||||||||||
| NmasterswitchVM | 1.3.6.1.4.1.318.1.1.5 | ||||||||||||||||||||
| NsPDUIdentVM | 1.3.6.1.4.1.318.1.1.5.1 | ||||||||||||||||||||
| SsPDUIdentVMTableSize | 1.3.6.1.4.1.318.1.1.5.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of MasterSwitch VMs controllable by this IP address. | |||||||||||||||||||||
| TsPDUIdentVMTable | 1.3.6.1.4.1.318.1.1.5.1.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for query of the individual MasterSwitch VMs. The number of entries is contained in the sPDUIdentVMTableSize OID. | |||||||||||||||||||||
| RsPDUIdentVMEntry | 1.3.6.1.4.1.318.1.1.5.1.2.1 | NA | mandatory | ||||||||||||||||||
| CsPDUIdentVMIndex | 1.3.6.1.4.1.318.1.1.5.1.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the MasterSwitch VM entry. | |||||||||||||||||||||
| CsPDUIdentNameVM | 1.3.6.1.4.1.318.1.1.5.1.2.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory A 23-character string identifying the MasterSwitch VM. | |||||||||||||||||||||
| CsPDUIdentHardwareRevVM | 1.3.6.1.4.1.318.1.1.5.1.2.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The hardware version of the MasterSwitch VM. This value is set at the factory. | |||||||||||||||||||||
| CsPDUIdentFirmwareRevVM | 1.3.6.1.4.1.318.1.1.5.1.2.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory An 6-character ID string identifying the MasterSwitch VM firmware version. This value is set at the factory. | |||||||||||||||||||||
| CsPDUIdentDateOfManufactureVM | 1.3.6.1.4.1.318.1.1.5.1.2.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The date when the MasterSwitch VM was manufactured in mm/dd/yyyy format. This value is set at the factory. | |||||||||||||||||||||
| CsPDUIdentModelNumberVM | 1.3.6.1.4.1.318.1.1.5.1.2.1.6 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory A 17-character string identifying the model number of the MasterSwitch VM. This value is set at the factory. | |||||||||||||||||||||
| CsPDUIdentSerialNumberVM | 1.3.6.1.4.1.318.1.1.5.1.2.1.7 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory A 17-character string identifying the serial number of the MasterSwitch VM. This value is set at the factory. | |||||||||||||||||||||
| NsPDUMasterControlVM | 1.3.6.1.4.1.318.1.1.5.2 | ||||||||||||||||||||
| SsPDUMasterControlVMTableSize | 1.3.6.1.4.1.318.1.1.5.2.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of MasterSwitch VMs controllable by this IP address. | |||||||||||||||||||||
| TsPDUMasterControlVMTable | 1.3.6.1.4.1.318.1.1.5.2.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for control of the individual MasterSwitch VMs. The number of entries is contained in the sPDUMasterControlVMTableSize OID. | |||||||||||||||||||||
| RsPDUMasterControlVMEntry | 1.3.6.1.4.1.318.1.1.5.2.2.1 | NA | mandatory | ||||||||||||||||||
| CsPDUMasterControlVMIndex | 1.3.6.1.4.1.318.1.1.5.2.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the MasterSwitch VM entry. | |||||||||||||||||||||
| CsPDUMasterControlVMName | 1.3.6.1.4.1.318.1.1.5.2.2.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The name of the MasterSwitch VM. The maximum value is 23 characters. The name is set by using the sPDUMasterConfigVMName OID. | |||||||||||||||||||||
| CsPDUMasterControlVMCommand | 1.3.6.1.4.1.318.1.1.5.2.2.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Setting this OID to immediateAllOnVM (2) will turn all outlets on immediately. Setting this OID to immediateAllOffVM (3) will turn all outlets off immediately. Setting this OID to immediateAllRebootVM (4) will reboot all outlets immediately. Setting this OID to delayedAllOnVM (5) will turn all outlets on as defined by each outlet's sPDUOutletConfigVMPowerOnTime OID value. Setting this OID to delayedAllOffVM (6) will turn all outlets off as defined by each outlet's sPDUOutletConfigVMPowerOffTime OID value. Setting this OID to sequencedAllRebootVM (7) will cause a immediateAllOffVM command to be performed. The MasterSwitch VM will then delay the sPDUMasterStatusVMRebootDuration OID time, and then perform a delayedAllOnVM command. Setting this OID to delayedAllRebootVM (8) will cause a delayedAllOffVM command to be performed. Each outlet will then wait its sPDUOutletConfigVMRebootDuration before returning power to the outlet. Setting this OID to delayedSequenceAllRebootVM (9) will cause a delayedAllOffVM command to be performed. Once all outlets are off, the MasterSwitch VM will then delay the sPDUMasterStatusVMRebootDuration OID time, and then perform a delayedAllOnVM command. Setting this OID to cancelAllPendingCommandsVM (10) will cause all pending commands on the MasterSwitch VM to be canceled. Setting this OID to audioAlarmMute (11) will temporarily silence the audible alarm for the duration of the current overload condition. The audible alarm will be activated on subsequent overload alarms. Getting this OID will return the noCommandAllVM (1) value.
| |||||||||||||||||||||
| NsPDUMasterConfigVM | 1.3.6.1.4.1.318.1.1.5.3 | ||||||||||||||||||||
| SsPDUMasterConfigVMTableSize | 1.3.6.1.4.1.318.1.1.5.3.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of MasterSwitch VMs configurable by this IP address. | |||||||||||||||||||||
| TsPDUMasterConfigVMTable | 1.3.6.1.4.1.318.1.1.5.3.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for configuration of the individual MasterSwitch VMs. The number of entries is contained in the sPDUMasterConfigVMTableSize OID. | |||||||||||||||||||||
| RsPDUMasterConfigVMEntry | 1.3.6.1.4.1.318.1.1.5.3.2.1 | NA | mandatory | ||||||||||||||||||
| CsPDUMasterConfigVMIndex | 1.3.6.1.4.1.318.1.1.5.3.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the MasterSwitch VM entry. | |||||||||||||||||||||
| CsPDUMasterConfigVMName | 1.3.6.1.4.1.318.1.1.5.3.2.1.2 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The name of the MasterSwitch VM. Maximum size is 23 characters. | |||||||||||||||||||||
| CsPDUMasterConfigVMColdstartDelay | 1.3.6.1.4.1.318.1.1.5.3.2.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The amount of delay, in seconds, between when power is provided to the MasterSwitch VM and when the MasterSwitch VM provides basic master power to the outlets. Allowed values are: -1 never apply power automatically. 0 apply power immediately. 15 apply power in 15 seconds. 30 apply power in 30 seconds. 45 apply power in 45 seconds. 60 apply power in 60 seconds (1 minute). 120 apply power in 120 seconds (2 minutes). 300 apply power in 300 seconds (5 minutes). If a value other than a supported value is provided in a set request, the MasterSwitch VM interprets it as the next lower acceptable value. If the provided value is lower than the lowest acceptable value, the lowest acceptable value is used. | |||||||||||||||||||||
| CsPDUMasterConfigVMAudioAlarmActivated | 1.3.6.1.4.1.318.1.1.5.3.2.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Setting this OID to audioAlarmActiveNever (1) will disable the audio alarm on the MasterSwitch VM. Setting this OID to audioAlarmActiveOnOverload (2) will activate the audio alarm on the MasterSwitch VM when an overload condition is present. Setting this OID to audioAlarmActiveOnOverloadImminent (3) will activate the audio alarm on the MasterSwitch VM when the load on the MasterSwitch VM has surpassed the sPDUMasterConfigVMHighLoadWarningThreshold OID value.
| |||||||||||||||||||||
| CsPDUMasterConfigVMHighLoadWarningThreshold | 1.3.6.1.4.1.318.1.1.5.3.2.1.5 | INTEGER (0..100) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..100) · read-write · mandatory A threshold that indicates the power consumption of the load is nearing an overload condition. It is represented as a percentage of full load. | |||||||||||||||||||||
| CsPDUMasterConfigVMLowLoadWarningThreshold | 1.3.6.1.4.1.318.1.1.5.3.2.1.6 | INTEGER (0..100) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..100) · read-write · mandatory A threshold that indicates the power consumption of the load is nearing a low consumption condition. It is represented as a percentage of full load. | |||||||||||||||||||||
| CsPDUMasterConfigVMOverloadRestriction | 1.3.6.1.4.1.318.1.1.5.3.2.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory This OID controls the behavior of the MasterSwitch VM when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will always allow the outlets to turn on. Setting this OID to restrictOnWarning (2) will not allow outlets to turn on if the sPDUMasterConfigVMHighLoadWarningThreshold OID is exceeded. Setting this OID to restrictOnOverload (3) will not allow outlets to turn on if the MasterSwitch Vm is in an overload condition.
| |||||||||||||||||||||
| NsPDUMasterStatusVM | 1.3.6.1.4.1.318.1.1.5.4 | ||||||||||||||||||||
| SsPDUMasterStatusVMTableSize | 1.3.6.1.4.1.318.1.1.5.4.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of MasterSwitch VMs at this IP address. | |||||||||||||||||||||
| TsPDUMasterStatusVMTable | 1.3.6.1.4.1.318.1.1.5.4.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for gathering of status from the individual MasterSwitch VMs. The number of entries is contained in the sPDUMasterStatusVMTableSize OID. | |||||||||||||||||||||
| RsPDUMasterStatusVMEntry | 1.3.6.1.4.1.318.1.1.5.4.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The MasterSwitch VMs to gather status from. | |||||||||||||||||||||
| CsPDUMasterStatusVMIndex | 1.3.6.1.4.1.318.1.1.5.4.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the MasterSwitch VM entry. | |||||||||||||||||||||
| CsPDUMasterStatusVMName | 1.3.6.1.4.1.318.1.1.5.4.2.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The name of the MasterSwitch VM. Maximum size is 23 characters. | |||||||||||||||||||||
| CsPDUMasterStatusVMCommandPending | 1.3.6.1.4.1.318.1.1.5.4.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this OID will return commandPendingMasterTrueVM (1) if the MasterSwitch VM has a pending command on any of its outlets. commandPendingMasterFalseVM (2) will be returned if there are no pending commands.
| |||||||||||||||||||||
| CsPDUMasterStatusVMOverloadCondition | 1.3.6.1.4.1.318.1.1.5.4.2.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this OID will return overloadConditionTrueVM (1) if the sPDUMasterConfigVMHighLoadWarningThreshold OID is violated. overloadConditionFalseVM (2) will be returned if the sPDUMasterConfigVMHighLoadWarningThreshold OID is not violated.
| |||||||||||||||||||||
| CsPDUMasterStatusVMLowLoadCondition | 1.3.6.1.4.1.318.1.1.5.4.2.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this OID will return lowLoadConditionTrueVM (1) if the sPDUMasterConfigVMLowLoadWarningThreshold OID is violated. lowLoadConditionFalseVM (2) will be returned if the sPDUMasterConfigVMHighLoadWarningThreshold OID is not violated.
| |||||||||||||||||||||
| CsPDUMasterStatusVMCurrentLoad | 1.3.6.1.4.1.318.1.1.5.4.2.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this OID will return the total amount of power being consumed by the load. It is represented as a percentage of full load. | |||||||||||||||||||||
| CsPDUMasterStatusVMMaxLoad | 1.3.6.1.4.1.318.1.1.5.4.2.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this OID will return the total amount of power that this MasterSwitch VM can provide. It is represented in Amps. | |||||||||||||||||||||
| CsPDUMasterStatusVMOutletCount | 1.3.6.1.4.1.318.1.1.5.4.2.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this OID will return the number of controllable outlets for this MasterSwitch VM. | |||||||||||||||||||||
| CsPDUMasterStatusVMRebootDuration | 1.3.6.1.4.1.318.1.1.5.4.2.1.9 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this OID will return the largest sPDUOutletConfigVMRebootDuration OID time for this MasterSwitch VM. | |||||||||||||||||||||
| NsPDUOutletControlVM | 1.3.6.1.4.1.318.1.1.5.5 | ||||||||||||||||||||
| TsPDUOutletControlVMTable | 1.3.6.1.4.1.318.1.1.5.5.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for control of individual outlet switches. The number of entries is contained in the sPDUMasterStatusOutletCount OID. | |||||||||||||||||||||
| RsPDUOutletControlVMEntry | 1.3.6.1.4.1.318.1.1.5.5.1.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The outlets to control. | |||||||||||||||||||||
| CsPDUOutletControlVMIndex | 1.3.6.1.4.1.318.1.1.5.5.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the MasterSwitch VM. | |||||||||||||||||||||
| CsPDUOutletControlVMName | 1.3.6.1.4.1.318.1.1.5.5.1.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The name of the MasterSwitch VM. Maximum size is 23 characters. This OID is provided for informational purposes only. | |||||||||||||||||||||
| CsPDUOutletControlVMOutletIndex | 1.3.6.1.4.1.318.1.1.5.5.1.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the outlet entry. | |||||||||||||||||||||
| CsPDUOutletControlVMOutletName | 1.3.6.1.4.1.318.1.1.5.5.1.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The name of the outlet. Maximum size is 23 characters. This OID is provided for informational purposes only. | |||||||||||||||||||||
| CsPDUOutletControlVMOutletCommand | 1.3.6.1.4.1.318.1.1.5.5.1.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Getting this variable will return the outlet state. If the outlet is on, the immediateOnVM (1) value will be returned. If the outlet is off, the immediateOffVM (2) value will be returned. Setting this variable to immediateOnVM (1) will immediately turn the outlet on. Setting this variable to immediateOffVM (2) will immediately turn the outlet off. Setting this variable to immediateRebootVM (3) will immediately reboot the outlet. Setting this variable to delayedOnVM (4) will turn the outlet on after the sPDUOutletConfigVMPowerOnTime OID time has elapsed. Setting this variable to delayedOffVM (5) will turn the outlet off after the sPDUOutletConfigVMPowerOffTime OID time has elapsed. Setting this variable to delayedRebootVM (6) will cause the MasterSwitch VM to perform a delayedOffVM command, wait the sPDUOutletConfigVMRebootDuration OID time, and then perform the immediateOnVM command. Setting this variable to cancelPendingCommandVM (7) will cause any pending command to this outlet to be canceled.
| |||||||||||||||||||||
| NsPDUOutletConfigVM | 1.3.6.1.4.1.318.1.1.5.6 | ||||||||||||||||||||
| TsPDUOutletConfigVMTable | 1.3.6.1.4.1.318.1.1.5.6.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for configuration of individual outlets. The number of entries is contained in the sPDUMasterStatusOutletCount OID. | |||||||||||||||||||||
| RsPDUOutletConfigVMEntry | 1.3.6.1.4.1.318.1.1.5.6.1.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The outlets to configure. | |||||||||||||||||||||
| CsPDUOutletConfigVMIndex | 1.3.6.1.4.1.318.1.1.5.6.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the MasterSwitch VM. | |||||||||||||||||||||
| CsPDUOutletConfigVMName | 1.3.6.1.4.1.318.1.1.5.6.1.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The name of the MasterSwitch VM. Maximum size is 23 characters. | |||||||||||||||||||||
| CsPDUOutletConfigVMOutletIndex | 1.3.6.1.4.1.318.1.1.5.6.1.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the outlet entry. | |||||||||||||||||||||
| CsPDUOutletConfigVMOutletName | 1.3.6.1.4.1.318.1.1.5.6.1.1.4 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The name of the outlet. Maximum size is 23 characters. | |||||||||||||||||||||
| CsPDUOutletConfigVMPowerOnTime | 1.3.6.1.4.1.318.1.1.5.6.1.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The amount of time (in seconds) the outlet will delay powering on at coldstart or when a command that requires a turn-on delay is issued. Allowed values are: -1 never power on. 0 power on immediately. 15 power on 15 seconds after being commanded. 30 power on 30 seconds after being commanded. 45 power on 45 seconds after being commanded. 60 power on 60 seconds (1 minute) after being commanded. 120 power on 120 seconds (2 minutes) after being commanded. 300 power on 300 seconds (5 minutes) after being commanded. If a value other than a supported value is provided in a set request, the MasterSwitch VM interprets it as the next lower acceptable value. If the provided value is lower than the lowest acceptable value, the lowest acceptable value is used. | |||||||||||||||||||||
| CsPDUOutletConfigVMPowerOffTime | 1.3.6.1.4.1.318.1.1.5.6.1.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The amount of time (in seconds) the outlet will delay powering off when a command that requires a turn-off delay is issued. Allowed values are: -1 never power off automatically. 0 power off immediately. 15 power off 15 seconds after being commanded. 30 power off 30 seconds after being commanded. 45 power off 45 seconds after being commanded. 60 power off 60 seconds (1 minute) after being commanded. 120 power off 120 seconds (2 minutes) after being commanded. 300 power off 300 seconds (5 minutes) after being commanded. If a value other than a supported value is provided in a set request, the MasterSwitch VM interprets it as the next lower acceptable value. If the provided value is lower than the lowest acceptable value, the lowest acceptable value is used. | |||||||||||||||||||||
| CsPDUOutletConfigVMRebootDuration | 1.3.6.1.4.1.318.1.1.5.6.1.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory During a reboot sequence, power is turned off and then back on. This OID defines the amount of time to wait, in seconds, after turning the power off, at the start of the sequence, before turning power back on, at the end of the reboot sequence. Allowed values are: 5 wait 5 seconds between off/on. 10 wait 10 seconds between off/on. 15 wait 15 seconds between off/on. 20 wait 20 seconds between off/on. 30 wait 30 seconds between off/on. 45 wait 45 seconds between off/on. 60 wait 60 seconds (1 minute) between off/on. If a value other than a supported value is provided in a set request, the MasterSwitch VM interprets it as the next lower acceptable value. If the provided value is lower than the lowest acceptable value, the lowest acceptable value is used. | |||||||||||||||||||||
| NsPDUOutletStatusVM | 1.3.6.1.4.1.318.1.1.5.7 | ||||||||||||||||||||
| TsPDUOutletStatusVMTable | 1.3.6.1.4.1.318.1.1.5.7.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting of status of individual outlets. The number of entries is contained in the sPDUMasterStatusOutletCount OID. | |||||||||||||||||||||
| RsPDUOutletStatusVMEntry | 1.3.6.1.4.1.318.1.1.5.7.1.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The outlets to gather status from. | |||||||||||||||||||||
| CsPDUOutletStatusVMIndex | 1.3.6.1.4.1.318.1.1.5.7.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the MasterSwitch VM. | |||||||||||||||||||||
| CsPDUOutletStatusVMName | 1.3.6.1.4.1.318.1.1.5.7.1.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The name of the MasterSwitch VM. Maximum size is 23 characters. | |||||||||||||||||||||
| CsPDUOutletStatusVMOutletIndex | 1.3.6.1.4.1.318.1.1.5.7.1.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the outlet entry. | |||||||||||||||||||||
| CsPDUOutletStatusVMOutletName | 1.3.6.1.4.1.318.1.1.5.7.1.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The name of the outlet. Maximum size is 23 characters. | |||||||||||||||||||||
| CsPDUOutletStatusVMOutletState | 1.3.6.1.4.1.318.1.1.5.7.1.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this variable will return the outlet state. If the outlet is on, the outletStatusOnVM (1) value will be returned. If the outlet is off, the outletStatusOffVM (2) value will be returned.
| |||||||||||||||||||||
| CsPDUOutletStatusVMCommandPending | 1.3.6.1.4.1.318.1.1.5.7.1.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this variable will return the command pending state of the outlet. If a command is pending on the outlet, the outletStatusVMCommandPending (1) value will be returned. If there is not a command pending on the outlet, the outletStatusVMNoCommandPending (2) will be returned.
| |||||||||||||||||||||
| NmasterswitchMSP | 1.3.6.1.4.1.318.1.1.6 | ||||||||||||||||||||
| NsPDUIdentMSP | 1.3.6.1.4.1.318.1.1.6.1 | ||||||||||||||||||||
| SsPDUIdentMSPTableSize | 1.3.6.1.4.1.318.1.1.6.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of MasterSwitch pluses controllable by this IP address. | |||||||||||||||||||||
| TsPDUIdentMSPTable | 1.3.6.1.4.1.318.1.1.6.1.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for query of the individual MasterSwitch pluses. The number of entries is contained in the sPDUIdentMSPTableSize OID. | |||||||||||||||||||||
| RsPDUIdentMSPEntry | 1.3.6.1.4.1.318.1.1.6.1.2.1 | NA | mandatory | ||||||||||||||||||
| CsPDUIdentMSPIndex | 1.3.6.1.4.1.318.1.1.6.1.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the MasterSwitch plus entry. | |||||||||||||||||||||
| CsPDUIdentNameMSP | 1.3.6.1.4.1.318.1.1.6.1.2.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The name of the MasterSwitch plus. The maximum value is 23 characters. The name is set by using the sPDUMasterConfigMSPName OID. | |||||||||||||||||||||
| CsPDUIdentHardwareRevMSP | 1.3.6.1.4.1.318.1.1.6.1.2.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The hardware version of the MasterSwitch plus. This value is set at the factory. | |||||||||||||||||||||
| CsPDUIdentFirmwareRevMSP | 1.3.6.1.4.1.318.1.1.6.1.2.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory An 6-character ID string identifying the MasterSwitch plus firmware version. This value is set at the factory. | |||||||||||||||||||||
| CsPDUIdentDateOfManufactureMSP | 1.3.6.1.4.1.318.1.1.6.1.2.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The date when the MasterSwitch plus was manufactured in mm/dd/yyyy format. This value is set at the factory. | |||||||||||||||||||||
| CsPDUIdentModelNumberMSP | 1.3.6.1.4.1.318.1.1.6.1.2.1.6 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory A 17-character string identifying the model number of the MasterSwitch plus. This value is set at the factory. | |||||||||||||||||||||
| CsPDUIdentSerialNumberMSP | 1.3.6.1.4.1.318.1.1.6.1.2.1.7 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory A 17-character string identifying the serial number of the MasterSwitch plus. This value is set at the factory. | |||||||||||||||||||||
| NsPDUMasterControlMSP | 1.3.6.1.4.1.318.1.1.6.2 | ||||||||||||||||||||
| SsPDUMasterControlMSPTableSize | 1.3.6.1.4.1.318.1.1.6.2.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of MasterSwitch pluses controllable by this IP address. | |||||||||||||||||||||
| TsPDUMasterControlMSPTable | 1.3.6.1.4.1.318.1.1.6.2.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for control of the individual MasterSwitch pluses. The number of entries is contained in the sPDUMasterControlMSPTableSize OID. | |||||||||||||||||||||
| RsPDUMasterControlMSPEntry | 1.3.6.1.4.1.318.1.1.6.2.2.1 | NA | mandatory | ||||||||||||||||||
| CsPDUMasterControlMSPIndex | 1.3.6.1.4.1.318.1.1.6.2.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the MasterSwitch plus entry. | |||||||||||||||||||||
| CsPDUMasterControlMSPName | 1.3.6.1.4.1.318.1.1.6.2.2.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The name of the MasterSwitch plus. The maximum value is 23 characters. The name is set by using the sPDUMasterConfigMSPName OID. | |||||||||||||||||||||
| CsPDUMasterControlMSPCommand | 1.3.6.1.4.1.318.1.1.6.2.2.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Setting this OID to immediateAllOnMSP (2) will turn all outlets on immediately. Setting this OID to sequencedAllOnMSP (3) will turn all outlets on as defined by each outlet's sPDUOutletConfigMSPPowerOnDelay OID value. Setting this OID to immediateAllOffMSP (4) will turn all outlets off immediately. Setting this OID to gracefulAllRebootMSP (5) will reboot all outlets (after the device running PowerChute confirms shutdown) as defined by each outlet's sPDUOutletConfigMSPRebootDuration OID time value. Setting this OID to immediateAllRebootMSP (6) will reboot all outlets immediately. Setting this OID to gracefulAllShutdownMSP (7) will shutdown all outlets (after the device running PowerChute confirms shutdown) as defined by each outlet's sPDUOutletConfigMSPPowerOffDelay OID time value. Each outlet will then turn on after the sum of its sPDUOutletConfigMSPRestartDelay and sPDUOutletConfigMSPPowerOnDelay OID values. Setting this OID to overrideAllBatCapThreshMSP (8) will cause the outlet to ignore the Battery Capacity Threshold and proceed turning on the outlets as defined by each outlet's sPDUOutletConfigMSPPowerOnDelay OID value. Setting this OID to cancelAllPendingCommandsMSP (9) will cause all pending commands on the MasterSwitch plus to be canceled. Setting this OID to restoreFactoryDefaultsMSP (10) will cause the settings of the MasterSwitch plus to be restored to the factory defaults. Getting this OID will return the noCommandAllMSP (1) value.
| |||||||||||||||||||||
| NsPDUMasterConfigMSP | 1.3.6.1.4.1.318.1.1.6.3 | ||||||||||||||||||||
| SsPDUMasterConfigMSPTableSize | 1.3.6.1.4.1.318.1.1.6.3.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of MasterSwitch pluses configurable by this IP address. | |||||||||||||||||||||
| TsPDUMasterConfigMSPTable | 1.3.6.1.4.1.318.1.1.6.3.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for configuration of the individual MasterSwitch pluses. The number of entries is contained in the sPDUMasterConfigMSPTableSize OID. | |||||||||||||||||||||
| RsPDUMasterConfigMSPEntry | 1.3.6.1.4.1.318.1.1.6.3.2.1 | NA | mandatory | ||||||||||||||||||
| CsPDUMasterConfigMSPIndex | 1.3.6.1.4.1.318.1.1.6.3.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the MasterSwitch plus entry. | |||||||||||||||||||||
| CsPDUMasterConfigMSPName | 1.3.6.1.4.1.318.1.1.6.3.2.1.2 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The name of the MasterSwitch plus. Maximum size is 23 characters. | |||||||||||||||||||||
| CsPDUMasterConfigMSPPowerOnTimeDelay | 1.3.6.1.4.1.318.1.1.6.3.2.1.3 | INTEGER (0..9999) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..9999) · read-write · mandatory The amount of delay, in seconds, between when power is provided to the MasterSwitch plus and when the MasterSwitch plus provides basic master power to the outlets. Allowed values are: 0 - 9999 seconds (0 - 2hrs, 46 mins, 39 secs). 0 indicates to apply power immediately. | |||||||||||||||||||||
| CsPDUMasterConfigMSPManualButton | 1.3.6.1.4.1.318.1.1.6.3.2.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Setting this OID to manualButtonDisabled (1) will disable the manual button on the MasterSwitch plus. Setting this OID to manualButtonEnabled (2) will enable the manual button on the MasterSwitch plus.
| |||||||||||||||||||||
| NsPDUMasterStatusMSP | 1.3.6.1.4.1.318.1.1.6.4 | ||||||||||||||||||||
| SsPDUMasterStatusMSPTableSize | 1.3.6.1.4.1.318.1.1.6.4.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of MasterSwitch pluses at this IP address. | |||||||||||||||||||||
| TsPDUMasterStatusMSPTable | 1.3.6.1.4.1.318.1.1.6.4.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for gathering of status from the individual MasterSwitch pluses. The number of entries is contained in the sPDUMasterStatusMSPTableSize OID. | |||||||||||||||||||||
| RsPDUMasterStatusMSPEntry | 1.3.6.1.4.1.318.1.1.6.4.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The MasterSwitch pluses to gather status from. | |||||||||||||||||||||
| CsPDUMasterStatusMSPIndex | 1.3.6.1.4.1.318.1.1.6.4.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the MasterSwitch plus entry. | |||||||||||||||||||||
| CsPDUMasterStatusMSPName | 1.3.6.1.4.1.318.1.1.6.4.2.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The name of the MasterSwitch plus. The maximum value is 23 characters. The name is set by using the sPDUMasterConfigMSPName OID. | |||||||||||||||||||||
| CsPDUMasterStatusMSPOutletCount | 1.3.6.1.4.1.318.1.1.6.4.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this OID will return the number of controllable outlets for this MasterSwitch plus. | |||||||||||||||||||||
| NsPDUOutletControlMSP | 1.3.6.1.4.1.318.1.1.6.5 | ||||||||||||||||||||
| TsPDUOutletControlMSPTable | 1.3.6.1.4.1.318.1.1.6.5.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for control of individual outlet switches. The number of entries is contained in the sPDUMasterStatusMSPOutletCount OID. | |||||||||||||||||||||
| RsPDUOutletControlMSPEntry | 1.3.6.1.4.1.318.1.1.6.5.1.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The outlets to control. | |||||||||||||||||||||
| CsPDUOutletControlMSPIndex | 1.3.6.1.4.1.318.1.1.6.5.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the MasterSwitch plus. | |||||||||||||||||||||
| CsPDUOutletControlMSPName | 1.3.6.1.4.1.318.1.1.6.5.1.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The name of the MasterSwitch plus. The maximum value is 23 characters. The name is set by using the sPDUMasterConfigMSPName OID. | |||||||||||||||||||||
| CsPDUOutletControlMSPOutletIndex | 1.3.6.1.4.1.318.1.1.6.5.1.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the outlet entry. | |||||||||||||||||||||
| CsPDUOutletControlMSPOutletName | 1.3.6.1.4.1.318.1.1.6.5.1.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The name of the outlet. The maximum size is 23 characters. The name is set by using the sPDUOutletConfigMSPallOutletName OID. This OID is provided for informational purposes only. | |||||||||||||||||||||
| CsPDUOutletControlMSPOutletCommand | 1.3.6.1.4.1.318.1.1.6.5.1.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Getting this variable will return the outlet state. If the outlet is on, the immediateOnMSP (1) value will be returned. If the outlet is off, the immediateOffMSP (3) value will be returned. Setting this variable to immediateOnMSP (1) will immediately turn the outlet on. Setting this variable to delayedOnMSP (2) will turn the outlet on after the sPDUOutletConfigMSPPowerOnDelay OID time has elapsed. Setting this variable to immediateOffMSP (3) will immediately turn the outlet off. Setting this variable to gracefulRebootMSP (4) will cause the outlet to wait for device confirmation (if applicable) and then turn the outlet off after the sPDUOutletConfigMSPPowerOffDelay OID time has elapsed. The outlet will then turn on after the sPDUOutletConfigMSPRebootDuration OID time has elapsed. Setting this variable to immediateRebootMSP (5) will immediately reboot the outlet. Setting this variable to gracefulshutdownMSP (6) will cause the outlet to wait for device confirmation (if applicable) and then turn the outlet off after the sPDUOutletConfigMSPPowerOffDelay OID time has elapsed. The outlet will then turn on after the sum of the sPDUOutletConfigMSPRestartTime OID time and the sPDUOutletConfigMSPPowerOnDelay OID time has elapsed. Setting this variable to overrideBatCapThreshMSP (7) will cause the outlet to ignore the Battery Capacity Threshold and proceed waiting on the sPDUOutletConfigMSPPowerOnDelay OID time before turning the outlet on. Setting this variable to cancelPendingCommandMSP (8) will cause any pending command to this outlet to be canceled.
| |||||||||||||||||||||
| NsPDUOutletConfigMSP | 1.3.6.1.4.1.318.1.1.6.6 | ||||||||||||||||||||
| NsPDUOutletConfigMSPall | 1.3.6.1.4.1.318.1.1.6.6.1 | ||||||||||||||||||||
| TsPDUOutletConfigMSPallTable | 1.3.6.1.4.1.318.1.1.6.6.1.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for configuration of individual outlets. The number of entries is contained in the sPDUMasterStatusMSPOutletCount OID. | |||||||||||||||||||||
| RsPDUOutletConfigMSPallEntry | 1.3.6.1.4.1.318.1.1.6.6.1.1.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The outlets to configure. | |||||||||||||||||||||
| CsPDUOutletConfigMSPallIndex | 1.3.6.1.4.1.318.1.1.6.6.1.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the MasterSwitch plus. | |||||||||||||||||||||
| CsPDUOutletConfigMSPallName | 1.3.6.1.4.1.318.1.1.6.6.1.1.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The name of the MasterSwitch plus. The maximum value is 23 characters. The name is set by using the sPDUMasterConfigMSPName OID. | |||||||||||||||||||||
| CsPDUOutletConfigMSPallOutletIndex | 1.3.6.1.4.1.318.1.1.6.6.1.1.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the outlet entry. | |||||||||||||||||||||
| CsPDUOutletConfigMSPallOutletName | 1.3.6.1.4.1.318.1.1.6.6.1.1.1.4 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The name of the outlet. Maximum size is 23 characters. | |||||||||||||||||||||
| CsPDUOutletConfigMSPallOutletCtrlMode | 1.3.6.1.4.1.318.1.1.6.6.1.1.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Setting this OID to modeGracefulShutdown (1) will put this outlet into the Graceful Shutdown control mode. Setting this OID to modeAnnunciator (2) will put this outlet into the Annunciator control mode.
| |||||||||||||||||||||
| NsPDUOutletConfigMSPgs | 1.3.6.1.4.1.318.1.1.6.6.2 | ||||||||||||||||||||
| TsPDUOutletConfigMSPgsTable | 1.3.6.1.4.1.318.1.1.6.6.2.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for configuration of individual outlets. The number of entries is contained in the sPDUMasterStatusMSPOutletCount OID. | |||||||||||||||||||||
| RsPDUOutletConfigMSPgsEntry | 1.3.6.1.4.1.318.1.1.6.6.2.1.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The outlets to configure. | |||||||||||||||||||||
| CsPDUOutletConfigMSPgsIndex | 1.3.6.1.4.1.318.1.1.6.6.2.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the MasterSwitch plus. | |||||||||||||||||||||
| CsPDUOutletConfigMSPgsName | 1.3.6.1.4.1.318.1.1.6.6.2.1.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The name of the MasterSwitch plus. The maximum value is 23 characters. The name is set by using the sPDUMasterConfigMSPName OID. | |||||||||||||||||||||
| CsPDUOutletConfigMSPgsOutletIndex | 1.3.6.1.4.1.318.1.1.6.6.2.1.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the outlet entry. | |||||||||||||||||||||
| CsPDUOutletConfigMSPgsOutletName | 1.3.6.1.4.1.318.1.1.6.6.2.1.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The name of the outlet. The maximum size is 23 characters. The name is set by using the sPDUOutletConfigMSPallOutletName OID. This OID is provided for informational purposes only. | |||||||||||||||||||||
| CsPDUOutletConfigMSPgsOutletCtrlMode | 1.3.6.1.4.1.318.1.1.6.6.2.1.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The Control Mode of the outlet. This OID is provided for informational purposes only.
| |||||||||||||||||||||
| CsPDUOutletConfigMSPgsDeviceConfirm | 1.3.6.1.4.1.318.1.1.6.6.2.1.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Setting this OID to deviceConfirmNo (1) cause the outlet to NOT wait for device confirmation while performing graceful operations. Setting this OID to deviceConfirmYes (2) cause the outlet to wait for device confirmation while performing graceful operations.
| |||||||||||||||||||||
| CsPDUOutletConfigMSPgsLowBattWarning | 1.3.6.1.4.1.318.1.1.6.6.2.1.1.7 | INTEGER (-2..9999) | RW | mandatory | |||||||||||||||||
column · INTEGER (-2..9999) · read-write · mandatory The amount of delay, in 6 second intervals, between when the UPS goes on battery and the power down sequence for the outlet is initiated. Allowed values are: -2 - Never initiate the power down sequence on low battery warning. -1 - Initiate power down sequence based on remaining runtime. 1 - 9999 six second intervals (6 secs - 16hrs, 39 mins, 54 secs). 0 indicates to immediately initiate power down sequence on low battery warning. | |||||||||||||||||||||
| CsPDUOutletConfigMSPgsLowBattMult | 1.3.6.1.4.1.318.1.1.6.6.2.1.1.8 | INTEGER (1..7) | RW | mandatory | |||||||||||||||||
column · INTEGER (1..7) · read-write · mandatory Only applicable if sPDUOutletConfigMSPgsLowBattWarning OID is set to -1 (On Runtime Remaining). Allows you to set the value to stagger the shutdown sequence of the outlets. 1 provides the longest delay (the outlet to shutoff first), and 7 would provide the shortest delay (the outlet to shut off last). Allowed values are: 1 - 7. | |||||||||||||||||||||
| CsPDUOutletConfigMSPgsRestartDelay | 1.3.6.1.4.1.318.1.1.6.6.2.1.1.9 | INTEGER (-1..9999) | RW | mandatory | |||||||||||||||||
column · INTEGER (-1..9999) · read-write · mandatory The amount of delay, in 6 minute intervals, between when the outlet is turned off and the outlet is turned back on when performing a Graceful Shutdown. Allowed values are: -1 - Never turn outlet back on after a Graceful shutdown. 0 - 9999 six minute intervals (0 - 999hrs, 54 mins). | |||||||||||||||||||||
| CsPDUOutletConfigMSPgsPowerOnDelay | 1.3.6.1.4.1.318.1.1.6.6.2.1.1.10 | INTEGER (-1..9999) | RW | mandatory | |||||||||||||||||
column · INTEGER (-1..9999) · read-write · mandatory The amount of delay, in seconds, between the UPS entering normal (on-line) state and the outlet being powered on. Allowed values are: -1 - Remain Off when the UPS enters the on-line state. 0 - 9999 seconds (0 - 2 hrs, 46 mins, 39 secs). | |||||||||||||||||||||
| CsPDUOutletConfigMSPgsPowerOffDelay | 1.3.6.1.4.1.318.1.1.6.6.2.1.1.11 | INTEGER (0..9999) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..9999) · read-write · mandatory The amount of delay, in seconds, between when the server shuts down and the outlet is powered off. Allowed values are: 0 - 9999 seconds (0 - 2 hrs, 46 mins, 39 secs). | |||||||||||||||||||||
| CsPDUOutletConfigMSPgsBattCapThresh | 1.3.6.1.4.1.318.1.1.6.6.2.1.1.12 | INTEGER (0..100) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..100) · read-write · mandatory The minimum battery capacity, as a percent (0-100%), required of the UPS before an outlet will be allowed to power on. Allowed values are: 0 - 100 percent. | |||||||||||||||||||||
| CsPDUOutletConfigMSPgsRebootDuration | 1.3.6.1.4.1.318.1.1.6.6.2.1.1.13 | INTEGER (0..9999) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..9999) · read-write · mandatory The amount of delay, in seconds, from outlet off until outlet on during a reboot. Allowed values are: 0 - 9999 seconds (0 - 2 hrs, 46 mins, 39 secs). | |||||||||||||||||||||
| NsPDUOutletConfigMSPannun | 1.3.6.1.4.1.318.1.1.6.6.3 | ||||||||||||||||||||
| TsPDUOutletConfigMSPannunTable | 1.3.6.1.4.1.318.1.1.6.6.3.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for configuration of individual outlets. The number of entries is contained in the sPDUMasterStatusMSPOutletCount OID. | |||||||||||||||||||||
| RsPDUOutletConfigMSPannunEntry | 1.3.6.1.4.1.318.1.1.6.6.3.1.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The outlets to configure. | |||||||||||||||||||||
| CsPDUOutletConfigMSPannunIndex | 1.3.6.1.4.1.318.1.1.6.6.3.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the MasterSwitch plus. | |||||||||||||||||||||
| CsPDUOutletConfigMSPannunName | 1.3.6.1.4.1.318.1.1.6.6.3.1.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The name of the MasterSwitch plus. The maximum value is 23 characters. The name is set by using the sPDUMasterConfigMSPName OID. | |||||||||||||||||||||
| CsPDUOutletConfigMSPannunOutletIndex | 1.3.6.1.4.1.318.1.1.6.6.3.1.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the outlet entry. | |||||||||||||||||||||
| CsPDUOutletConfigMSPannunOutletName | 1.3.6.1.4.1.318.1.1.6.6.3.1.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The name of the outlet. The maximum size is 23 characters. The name is set by using the sPDUOutletConfigMSPallOutletName OID. This OID is provided for informational purposes only. | |||||||||||||||||||||
| CsPDUOutletConfigMSPannunOutletCtrlMode | 1.3.6.1.4.1.318.1.1.6.6.3.1.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The Control Mode of the outlet. This OID is provided for informational purposes only.
| |||||||||||||||||||||
| CsPDUOutletConfigMSPannunInitialState | 1.3.6.1.4.1.318.1.1.6.6.3.1.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Setting this OID to initialStateOff (1) causes the outlet to default to off when in the non-alarmed condition. Setting this OID to initialStateOn (2) causes the outlet to default to on when in the non-alarmed condition.
| |||||||||||||||||||||
| CsPDUOutletConfigMSPannunAlarmActionDly | 1.3.6.1.4.1.318.1.1.6.6.3.1.1.7 | INTEGER (0..9999) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..9999) · read-write · mandatory The amount of time, in seconds, that an enabled Measure-UPS alarm must be asserted before an alarm condition is recognized. Allowed values are: 0 - 9999 seconds (0 - 2 hrs, 46 mins, 39 secs). | |||||||||||||||||||||
| NsPDUOutletConfigMSPmups | 1.3.6.1.4.1.318.1.1.6.6.4 | ||||||||||||||||||||
| TsPDUOutletConfigMSPmupsTable | 1.3.6.1.4.1.318.1.1.6.6.4.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for configuration of individual outlets. The number of entries is contained in the sPDUMasterStatusMSPOutletCount OID. | |||||||||||||||||||||
| RsPDUOutletConfigMSPmupsEntry | 1.3.6.1.4.1.318.1.1.6.6.4.1.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The outlets to configure. | |||||||||||||||||||||
| CsPDUOutletConfigMSPmupsIndex | 1.3.6.1.4.1.318.1.1.6.6.4.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the MasterSwitch plus. | |||||||||||||||||||||
| CsPDUOutletConfigMSPmupsName | 1.3.6.1.4.1.318.1.1.6.6.4.1.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The name of the MasterSwitch plus. The maximum value is 23 characters. The name is set by using the sPDUMasterConfigMSPName OID. | |||||||||||||||||||||
| CsPDUOutletConfigMSPmupsOutletIndex | 1.3.6.1.4.1.318.1.1.6.6.4.1.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the outlet entry. | |||||||||||||||||||||
| CsPDUOutletConfigMSPmupsOutletName | 1.3.6.1.4.1.318.1.1.6.6.4.1.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The name of the outlet. The maximum size is 23 characters. The name is set by using the sPDUOutletConfigMSPallOutletName OID. This OID is provided for informational purposes only. | |||||||||||||||||||||
| CsPDUOutletConfigMSPmupsZone1 | 1.3.6.1.4.1.318.1.1.6.6.4.1.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Setting this OID to disableAlarm (1) disables the Zone 1 alarm for this outlet. Setting this OID to enableAlarm (2) enables the Zone 1 alarm for this outlet.
| |||||||||||||||||||||
| CsPDUOutletConfigMSPmupsZone2 | 1.3.6.1.4.1.318.1.1.6.6.4.1.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Setting this OID to disableAlarm (1) disables the Zone 2 alarm for this outlet. Setting this OID to enableAlarm (2) enables the Zone 2 alarm for this outlet.
| |||||||||||||||||||||
| CsPDUOutletConfigMSPmupsZone3 | 1.3.6.1.4.1.318.1.1.6.6.4.1.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Setting this OID to disableAlarm (1) disables the Zone 3 alarm for this outlet. Setting this OID to enableAlarm (2) enables the Zone 3 alarm for this outlet.
| |||||||||||||||||||||
| CsPDUOutletConfigMSPmupsZone4 | 1.3.6.1.4.1.318.1.1.6.6.4.1.1.8 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Setting this OID to disableAlarm (1) disables the Zone 4 alarm for this outlet. Setting this OID to enableAlarm (2) enables the Zone 4 alarm for this outlet.
| |||||||||||||||||||||
| CsPDUOutletConfigMSPmupsP1LowHum | 1.3.6.1.4.1.318.1.1.6.6.4.1.1.9 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Setting this OID to disableAlarm (1) disables the Probe 1 low humidity alarm for this outlet. Setting this OID to enableAlarm (2) enables the Probe 1 low humidity alarm for this outlet.
| |||||||||||||||||||||
| CsPDUOutletConfigMSPmupsP1HiHum | 1.3.6.1.4.1.318.1.1.6.6.4.1.1.10 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Setting this OID to disableAlarm (1) disables the Probe 1 high humidity alarm for this outlet. Setting this OID to enableAlarm (2) enables the Probe 1 high humidity alarm for this outlet.
| |||||||||||||||||||||
| CsPDUOutletConfigMSPmupsP1LowTemp | 1.3.6.1.4.1.318.1.1.6.6.4.1.1.11 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Setting this OID to disableAlarm (1) disables the Probe 1 low temperature alarm for this outlet. Setting this OID to enableAlarm (2) enables the Probe 1 low temperature alarm for this outlet.
| |||||||||||||||||||||
| CsPDUOutletConfigMSPmupsP1HiTemp | 1.3.6.1.4.1.318.1.1.6.6.4.1.1.12 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Setting this OID to disableAlarm (1) disables the Probe 1 high temperature alarm for this outlet. Setting this OID to enableAlarm (2) enables the Probe 1 high temperature alarm for this outlet.
| |||||||||||||||||||||
| CsPDUOutletConfigMSPmupsP2LowHum | 1.3.6.1.4.1.318.1.1.6.6.4.1.1.13 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Setting this OID to disableAlarm (1) disables the Probe 2 low humidity alarm for this outlet. Setting this OID to enableAlarm (2) enables the Probe 2 low humidity alarm for this outlet.
| |||||||||||||||||||||
| CsPDUOutletConfigMSPmupsP2HiHum | 1.3.6.1.4.1.318.1.1.6.6.4.1.1.14 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Setting this OID to disableAlarm (1) disables the Probe 2 high humidity alarm for this outlet. Setting this OID to enableAlarm (2) enables the Probe 2 high humidity alarm for this outlet.
| |||||||||||||||||||||
| CsPDUOutletConfigMSPmupsP2LowTemp | 1.3.6.1.4.1.318.1.1.6.6.4.1.1.15 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Setting this OID to disableAlarm (1) disables the Probe 2 low temperature alarm for this outlet. Setting this OID to enableAlarm (2) enables the Probe 2 low temperature alarm for this outlet.
| |||||||||||||||||||||
| CsPDUOutletConfigMSPmupsP2HiTemp | 1.3.6.1.4.1.318.1.1.6.6.4.1.1.16 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Setting this OID to disableAlarm (1) disables the Probe 2 high temperature alarm for this outlet. Setting this OID to enableAlarm (2) enables the Probe 2 high temperature alarm for this outlet.
| |||||||||||||||||||||
| NsPDUOutletStatusMSP | 1.3.6.1.4.1.318.1.1.6.7 | ||||||||||||||||||||
| TsPDUOutletStatusMSPTable | 1.3.6.1.4.1.318.1.1.6.7.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting of status of individual outlets. The number of entries is contained in the sPDUMasterStatusOutletCount OID. | |||||||||||||||||||||
| RsPDUOutletStatusMSPEntry | 1.3.6.1.4.1.318.1.1.6.7.1.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The outlets to gather status from. | |||||||||||||||||||||
| CsPDUOutletStatusMSPIndex | 1.3.6.1.4.1.318.1.1.6.7.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the MasterSwitch MSP. | |||||||||||||||||||||
| CsPDUOutletStatusMSPName | 1.3.6.1.4.1.318.1.1.6.7.1.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The name of the MasterSwitch plus. The maximum value is 23 characters. The name is set by using the sPDUMasterConfigMSPName OID. | |||||||||||||||||||||
| CsPDUOutletStatusMSPOutletIndex | 1.3.6.1.4.1.318.1.1.6.7.1.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the outlet entry. | |||||||||||||||||||||
| CsPDUOutletStatusMSPOutletName | 1.3.6.1.4.1.318.1.1.6.7.1.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The name of the outlet. The maximum size is 23 characters. The name is set by using the sPDUOutletConfigMSPallOutletName OID. This OID is provided for informational purposes only. | |||||||||||||||||||||
| CsPDUOutletStatusMSPOutletState | 1.3.6.1.4.1.318.1.1.6.7.1.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this variable will return the outlet state. If the outlet is on, the outletStatusMSPOn (1) value will be returned. If the outlet is off, the outletStatusMSPOff (2) value will be returned.
| |||||||||||||||||||||
| CsPDUOutletStatusMSPCommandPending | 1.3.6.1.4.1.318.1.1.6.7.1.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this variable will return the command pending state of the outlet. If a command is pending on the outlet, the outletStatusMSPCommandPending (1) value will be returned. If there is not a command pending on the outlet, the outletStatusMSPNoCommandPending (2) will be returned.
| |||||||||||||||||||||
| CsPDUOutletStatusMSPOutletCtrlMode | 1.3.6.1.4.1.318.1.1.6.7.1.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The Control Mode of the outlet. This OID is provided for informational purposes only.
| |||||||||||||||||||||
| NdcDM3 | 1.3.6.1.4.1.318.1.1.7 | ||||||||||||||||||||
| Ndm3Ident | 1.3.6.1.4.1.318.1.1.7.1 | ||||||||||||||||||||
| Ndm3IdentSystem | 1.3.6.1.4.1.318.1.1.7.1.1 | ||||||||||||||||||||
| Sdm3IdentSysDescriptionTableSize | 1.3.6.1.4.1.318.1.1.7.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of DC description records. | |||||||||||||||||||||
| Tdm3IdentSysDescriptionTable | 1.3.6.1.4.1.318.1.1.7.1.1.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for accessing description records of the powerplant. The number of entries is contained in the dm3IdentSysDescriptionTableSize OID. | |||||||||||||||||||||
| Rdm3IdentSysDescriptionEntry | 1.3.6.1.4.1.318.1.1.7.1.1.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The powerplant description record to reference. | |||||||||||||||||||||
| Cdm3IdentSysDescriptionIndex | 1.3.6.1.4.1.318.1.1.7.1.1.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the DC powerplant description record. | |||||||||||||||||||||
| Cdm3IdentSysDescriptionText | 1.3.6.1.4.1.318.1.1.7.1.1.2.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory A 16 character text field describing the DC power plant device. This field can be configured from the dm3ConfigSysDescriptionText OID. | |||||||||||||||||||||
| Sdm3IdentSysModel | 1.3.6.1.4.1.318.1.1.7.1.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Model type of the DC power plant. | |||||||||||||||||||||
| Sdm3IdentSysCntrlRev | 1.3.6.1.4.1.318.1.1.7.1.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Integer representation of the hardware revision of the Master Controller board. | |||||||||||||||||||||
| Sdm3IdentSysFWVersion | 1.3.6.1.4.1.318.1.1.7.1.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Integer representation of the power plant Master Controller firmware revision. | |||||||||||||||||||||
| Ndm3Config | 1.3.6.1.4.1.318.1.1.7.2 | ||||||||||||||||||||
| Ndm3ConfigSystem | 1.3.6.1.4.1.318.1.1.7.2.1 | ||||||||||||||||||||
| Sdm3ConfigSysDescriptionTableSize | 1.3.6.1.4.1.318.1.1.7.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of DC description records. | |||||||||||||||||||||
| Tdm3ConfigSysDescriptionTable | 1.3.6.1.4.1.318.1.1.7.2.1.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for accessing description records of the powerplant. The number of entries is contained in the dm3ConfigSysDescriptionTableSize OID. | |||||||||||||||||||||
| Rdm3ConfigSysDescriptionEntry | 1.3.6.1.4.1.318.1.1.7.2.1.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The powerplant description record to reference. | |||||||||||||||||||||
| Cdm3ConfigSysDescriptionIndex | 1.3.6.1.4.1.318.1.1.7.2.1.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the DC powerplant description record. | |||||||||||||||||||||
| Cdm3ConfigSysDescriptionText | 1.3.6.1.4.1.318.1.1.7.2.1.2.1.2 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory 16 character text field describing the DC power plant device. | |||||||||||||||||||||
| Sdm3ConfigSysHighTempThresh | 1.3.6.1.4.1.318.1.1.7.2.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Ambient high temperature threshold. Temperature sensor located on Master Controller board. Values are represented in thousandths of a degree. Units are displayed in the scale shown in the 'dm3StatusSysTempUnits' OID (Celsius or Fahrenheit). Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively. | |||||||||||||||||||||
| Sdm3ConfigSysHighTempAlarm | 1.3.6.1.4.1.318.1.1.7.2.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory For the System High Temperature Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition.
| |||||||||||||||||||||
| Sdm3ConfigSysLowTempThresh | 1.3.6.1.4.1.318.1.1.7.2.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Ambient low temperature threshold. Temperature sensor located on Master Controller board. Values are represented in thousandths of a degree. Units are displayed in the scale shown in the 'dm3StatusSysTempUnits' OID (Celsius or Fahrenheit). Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively. | |||||||||||||||||||||
| Sdm3ConfigSysLowTempAlarm | 1.3.6.1.4.1.318.1.1.7.2.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory For the System Low Temperature Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition.
| |||||||||||||||||||||
| Sdm3ConfigSysHardwareTempAlarm | 1.3.6.1.4.1.318.1.1.7.2.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory For the System Hardware Temperature Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition.
| |||||||||||||||||||||
| Sdm3ConfigSysRemoteAccess | 1.3.6.1.4.1.318.1.1.7.2.1.8 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory This OID is used to disable remote write access to the power plant. Setting this OID to accessEnabled (1) will have no affect. Setting this OID to accessDisabled (2) will disable the ability to remotely configure the DC powerplant. Once remote access is disabled, it can only be restored from the front panel of the DC power plant.
| |||||||||||||||||||||
| Ndm3ConfigLVD | 1.3.6.1.4.1.318.1.1.7.2.2 | ||||||||||||||||||||
| Sdm3ConfigLVDTableSize | 1.3.6.1.4.1.318.1.1.7.2.2.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of DC powerplant LVDs controllable by this IP address. | |||||||||||||||||||||
| Tdm3ConfigLVDTable | 1.3.6.1.4.1.318.1.1.7.2.2.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for accessing settings of the LVDs. The number of entries is contained in the dm3ConfigLVDTableSize OID. | |||||||||||||||||||||
| Rdm3ConfigLVDEntry | 1.3.6.1.4.1.318.1.1.7.2.2.2.1 | NA | mandatory | ||||||||||||||||||
| Cdm3ConfigLVDIndex | 1.3.6.1.4.1.318.1.1.7.2.2.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the DC powerplant LVD. | |||||||||||||||||||||
| Cdm3ConfigLVDName | 1.3.6.1.4.1.318.1.1.7.2.2.2.1.2 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The name of the LVD. The maximum value is 16 characters. | |||||||||||||||||||||
| Cdm3ConfigLVDEnable | 1.3.6.1.4.1.318.1.1.7.2.2.2.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory This OID is used to control and indicate if the LVD is on or off. Setting this OID to enabledYes (1) will enable (turn on) the LVD. Setting this OID to enabledNo (2) will disable (turn off) the LVD.
| |||||||||||||||||||||
| Cdm3ConfigLVDTripThresh | 1.3.6.1.4.1.318.1.1.7.2.2.2.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory LVD Trip threshold. If voltage exceeds threshold, the LVD will trip. Values are represented in thousandths of Volts (mV). Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively. | |||||||||||||||||||||
| Cdm3ConfigLVDResetThresh | 1.3.6.1.4.1.318.1.1.7.2.2.2.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory LVD Reset threshold. If voltage exceeds threshold, the LVD will reset. Values are represented in thousandths of Volts (mV). Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively. | |||||||||||||||||||||
| Cdm3ConfigLVDOpenAlarm | 1.3.6.1.4.1.318.1.1.7.2.2.2.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory For the LVD Open Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition.
| |||||||||||||||||||||
| Cdm3ConfigLVDHWAlarm | 1.3.6.1.4.1.318.1.1.7.2.2.2.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory For the LVD Hardware Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition.
| |||||||||||||||||||||
| Ndm3ConfigBattery | 1.3.6.1.4.1.318.1.1.7.2.3 | ||||||||||||||||||||
| Sdm3ConfigBattFloatVolt | 1.3.6.1.4.1.318.1.1.7.2.3.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Battery Float Voltage. This setting controls the power plant voltage. Values are represented in thousandths of Volts (mV). Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively. | |||||||||||||||||||||
| Sdm3ConfigBattMaxRecharge | 1.3.6.1.4.1.318.1.1.7.2.3.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Battery Maximum Recharge Rate. This setting controls the battery max recharge rate. The value is based on C/20 for 240 AHr battery string. Values are represented in thousandths of Amps (mA). Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively. | |||||||||||||||||||||
| Sdm3ConfigBattDischargeThresh | 1.3.6.1.4.1.318.1.1.7.2.3.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Battery discharge threshold. If battery output current exceeds threshold a battery discharge alarm will occur. Values are represented in thousandths of Amps (mA). Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively. | |||||||||||||||||||||
| Sdm3ConfigBattDischargeAlarm | 1.3.6.1.4.1.318.1.1.7.2.3.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory For the Battery Discharge Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition.
| |||||||||||||||||||||
| Sdm3ConfigBattHighVoltThresh | 1.3.6.1.4.1.318.1.1.7.2.3.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Battery high voltage threshold. If system battery voltage exceeds threshold a battery high voltage alarm will occur. Values are represented in thousandths of Volts (mV). Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively. | |||||||||||||||||||||
| Sdm3ConfigBattHighVoltAlarm | 1.3.6.1.4.1.318.1.1.7.2.3.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory For the Battery High Voltage Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition.
| |||||||||||||||||||||
| Sdm3ConfigBattLowVoltThresh | 1.3.6.1.4.1.318.1.1.7.2.3.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Battery low voltage threshold. If system battery voltage is under threshold a battery low voltage alarm will occur. Values are represented in thousandths of Volts (mV). Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively. | |||||||||||||||||||||
| Sdm3ConfigBattLowVoltAlarm | 1.3.6.1.4.1.318.1.1.7.2.3.8 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory For the Battery Low Voltage Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition.
| |||||||||||||||||||||
| Sdm3ConfigBattHighTempThresh | 1.3.6.1.4.1.318.1.1.7.2.3.9 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Battery high temperature threshold. If system battery temperature exceeds threshold a battery high temperature alarm will occur. Values are represented in thousandths of a degree. Units are displayed in the scale shown in the 'dm3StatusSysTempUnits' OID (Celsius or Fahrenheit). Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively. | |||||||||||||||||||||
| Sdm3ConfigBattHighTempAlarm | 1.3.6.1.4.1.318.1.1.7.2.3.10 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory For the Battery High Temperature Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition.
| |||||||||||||||||||||
| Sdm3ConfigBattLowTempThresh | 1.3.6.1.4.1.318.1.1.7.2.3.11 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Battery low temperature threshold. If system battery temperature is under threshold a battery low temperature alarm will occur. Values are represented in thousandths of a degree. Units are displayed in the scale shown in the 'dm3StatusSysTempUnits' OID (Celsius or Fahrenheit). Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively. | |||||||||||||||||||||
| Sdm3ConfigBattLowTempAlarm | 1.3.6.1.4.1.318.1.1.7.2.3.12 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory For the Battery Low Temperature Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition.
| |||||||||||||||||||||
| Sdm3ConfigBattAmpHour | 1.3.6.1.4.1.318.1.1.7.2.3.13 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Battery Amp-Hour Size. Units are thousandths of Amp hours (mAHr). Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively. | |||||||||||||||||||||
| Sdm3ConfigCompMethod | 1.3.6.1.4.1.318.1.1.7.2.3.14 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory This OID is used to configure and get the state of the battery temperature compensation. Setting this OID to tempcompOn (1) will enable/turn on the battery temperature compensation. Setting this OID to tempcompOff (2) will disable/turn off the battery temperature compensation.
| |||||||||||||||||||||
| Sdm3ConfigCompTempCoeff | 1.3.6.1.4.1.318.1.1.7.2.3.15 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Compensation Temperature Coefficient. (uV/degC/cell). Units are presented in microvolts. Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively. | |||||||||||||||||||||
| Sdm3ConfigHighKneeTemp | 1.3.6.1.4.1.318.1.1.7.2.3.16 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory High Knee for temperature compensation: Compensation temperature coefficient becomes 0mV/degC/cell. Values are represented in thousandths of degrees Celsius. Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively. | |||||||||||||||||||||
| Sdm3ConfigLowKneeTemp | 1.3.6.1.4.1.318.1.1.7.2.3.17 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Low Knee for temperature compensation: Compensation temperature coefficient becomes 0mV/degC/cell. Values are represented in thousandths of degrees Celsius. Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively. | |||||||||||||||||||||
| Sdm3ConfigBattHwCurrentAlarm | 1.3.6.1.4.1.318.1.1.7.2.3.18 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory For the Battery Current Hardware Alarm (indicating current is outside realistic limits, or a possible measurement fault; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition.
| |||||||||||||||||||||
| Sdm3ConfigBattHwTempAlarm | 1.3.6.1.4.1.318.1.1.7.2.3.19 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory For the Battery Temperature Hardware Alarm (indicating temperature is outside realistic limits, or a possible measurement fault; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition.
| |||||||||||||||||||||
| Ndm3ConfigPowerModules | 1.3.6.1.4.1.318.1.1.7.2.4 | ||||||||||||||||||||
| Ndm3ConfigRectifier | 1.3.6.1.4.1.318.1.1.7.2.4.1 | ||||||||||||||||||||
| Ndm3ConfigRectThresh | 1.3.6.1.4.1.318.1.1.7.2.4.1.1 | ||||||||||||||||||||
| Sdm3ConfigRectHighVoltThresh | 1.3.6.1.4.1.318.1.1.7.2.4.1.1.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Rectifier high voltage threshold. If rectifier voltage exceeds threshold a rectifier high voltage alarm will occur. Values are represented in thousandths of Volts (mV). Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively. | |||||||||||||||||||||
| Sdm3ConfigRectLowVoltThresh | 1.3.6.1.4.1.318.1.1.7.2.4.1.1.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Rectifier low voltage threshold. If rectifier voltage is under threshold a rectifier low voltage alarm will occur. Values are represented in thousandths of Volts (mV). Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively. | |||||||||||||||||||||
| Sdm3ConfigRectFailSafe | 1.3.6.1.4.1.318.1.1.7.2.4.1.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Rectifier Fail Safe point. This OID represents the value sent to rectifier controllers to use in the event of communications loss with the Master Controller or Master Controller board failure. Values are represented in thousandths of Volts (mV). Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively. | |||||||||||||||||||||
| Sdm3ConfigRectFailComm | 1.3.6.1.4.1.318.1.1.7.2.4.1.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Rectifier Communication Fail timeout. This OID represents the time interval in which there is no communication between the rectifier and the master controller at which the rectifier will reset all its values to default. Values are represented in hundredths of Seconds. Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively. | |||||||||||||||||||||
| Ndm3ConfigRectAlarms | 1.3.6.1.4.1.318.1.1.7.2.4.1.2 | ||||||||||||||||||||
| Sdm3ConfigRectHighVoltAlarm | 1.3.6.1.4.1.318.1.1.7.2.4.1.2.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory For the Rectifier High Voltage Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition.
| |||||||||||||||||||||
| Sdm3ConfigRectLowVoltAlarm | 1.3.6.1.4.1.318.1.1.7.2.4.1.2.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory For the Rectifier Low Voltage Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition.
| |||||||||||||||||||||
| Sdm3ConfigRectConfigAlarm | 1.3.6.1.4.1.318.1.1.7.2.4.1.2.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory This alarm is activated when a new rectifier is detected; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition.
| |||||||||||||||||||||
| Sdm3ConfigRect1ofNAlarm | 1.3.6.1.4.1.318.1.1.7.2.4.1.2.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory This setting indicates the action if ONE rectifier of a N+1 system has failed; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition.
| |||||||||||||||||||||
| Sdm3ConfigRect2ofNAlarm | 1.3.6.1.4.1.318.1.1.7.2.4.1.2.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory This setting indicates the action if TWO OR MORE rectifiers of a N+1 system have failed; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition.
| |||||||||||||||||||||
| Sdm3ConfigRectDiagAlarm | 1.3.6.1.4.1.318.1.1.7.2.4.1.2.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory For the Rectifier Controller Diagnostics Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition. Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigRect1ofNAlarm OID to be activated if ONE rectifier fails in an N+1 system. It causes the alarm specified in the dm3ConfigRect2ofNAlarm OID to be activated if TWO OR MORE rectifiers fail in an N+1 system.
| |||||||||||||||||||||
| Sdm3ConfigRectImbalanceAlarm | 1.3.6.1.4.1.318.1.1.7.2.4.1.2.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory For the Rectifier Imbalance Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition.
| |||||||||||||||||||||
| Sdm3ConfigRectCurrLimitAlarm | 1.3.6.1.4.1.318.1.1.7.2.4.1.2.8 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory For the Rectifier Current Limit Alarm (indicating rectifier in the Current Limit state); Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition. Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigRect1ofNAlarm OID to be activated if ONE rectifier fails in an N+1 system. It causes the alarm specified in the dm3ConfigRect2ofNAlarm OID to be activated if TWO OR MORE rectifiers fail in an N+1 system.
| |||||||||||||||||||||
| Sdm3ConfigRectStandbyAlarm | 1.3.6.1.4.1.318.1.1.7.2.4.1.2.9 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory For the Rectifier Standby Alarm (indicating output DC has been turned off); Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition. Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigRect1ofNAlarm OID to be activated if ONE rectifier fails in an N+1 system. It causes the alarm specified in the dm3ConfigRect2ofNAlarm OID to be activated if TWO OR MORE rectifiers fail in an N+1 system.
| |||||||||||||||||||||
| Sdm3ConfigRectFanFailAlarm | 1.3.6.1.4.1.318.1.1.7.2.4.1.2.10 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory For the Rectifier Fan Fail Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition. Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigRect1ofNAlarm OID to be activated if ONE rectifier fails in an N+1 system. It causes the alarm specified in the dm3ConfigRect2ofNAlarm OID to be activated if TWO OR MORE rectifiers fail in an N+1 system.
| |||||||||||||||||||||
| Sdm3ConfigRectFailAlarm | 1.3.6.1.4.1.318.1.1.7.2.4.1.2.11 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory For the Rectifier Fail Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition. Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigRect1ofNAlarm OID to be activated if ONE rectifier fails in an N+1 system. It causes the alarm specified in the dm3ConfigRect2ofNAlarm OID to be activated if TWO OR MORE rectifiers fail in an N+1 system.
| |||||||||||||||||||||
| Sdm3ConfigRectHwVoltAlarm | 1.3.6.1.4.1.318.1.1.7.2.4.1.2.12 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory For the Rectifier Hardware Voltage Alarm (indicating voltage outside realistic limits, or a possible measurement fault); Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition.
| |||||||||||||||||||||
| Ndm3ConfigConverter | 1.3.6.1.4.1.318.1.1.7.2.4.2 | ||||||||||||||||||||
| Ndm3ConfigConvThresh | 1.3.6.1.4.1.318.1.1.7.2.4.2.1 | ||||||||||||||||||||
| Sdm3ConfigConvHighVoltThresh | 1.3.6.1.4.1.318.1.1.7.2.4.2.1.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Converter high voltage threshold. If converter voltage exceeds threshold a converter high voltage alarm will occur. Values are represented in thousandths of Volts (mV). Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively. | |||||||||||||||||||||
| Sdm3ConfigConvLowVoltThresh | 1.3.6.1.4.1.318.1.1.7.2.4.2.1.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Converter low voltage threshold. If converter voltage exceeds threshold a converter low voltage alarm will occur. Values are represented in thousandths of Volts (mV). Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively. | |||||||||||||||||||||
| Sdm3ConfigConvFailSafe | 1.3.6.1.4.1.318.1.1.7.2.4.2.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Converter Fail Safe point. This OID represents the value sent to converter controllers to use in the event of communications loss with the Master Controller or Master Controller board failure. Values are represented in thousandths of Volts (mV). Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively. | |||||||||||||||||||||
| Sdm3ConfigConvSetPoint | 1.3.6.1.4.1.318.1.1.7.2.4.2.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Converter Set point. This OID represents the initial set point used in the voltage control loop. Units are thousandths of Volts (mV). Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively. | |||||||||||||||||||||
| Sdm3ConfigConvFailMax | 1.3.6.1.4.1.318.1.1.7.2.4.2.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Converter Fail Maximum limit. This OID represents the value sent to the converter controllers to define the maximum set point allowed. Units are thousandths of Volts (mV). Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively. | |||||||||||||||||||||
| Sdm3ConfigConvFailMin | 1.3.6.1.4.1.318.1.1.7.2.4.2.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Converter Fail Minimum limit. This OID represents the value sent to the converter controllers to define the minimum set point allowed. Units are thousandths of Volts (mV). Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively. | |||||||||||||||||||||
| Sdm3ConfigConvFailComm | 1.3.6.1.4.1.318.1.1.7.2.4.2.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Converter Communication Fail timeout. This OID represents the time interval in which there is no communication between the converter and the master controller at which the converter will reset all its values to default. Values are represented in hundredths of Seconds. Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively. | |||||||||||||||||||||
| Ndm3ConfigConvAlarms | 1.3.6.1.4.1.318.1.1.7.2.4.2.2 | ||||||||||||||||||||
| Sdm3ConfigConvHighVoltAlarm | 1.3.6.1.4.1.318.1.1.7.2.4.2.2.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory For the Converter High Voltage Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition.
| |||||||||||||||||||||
| Sdm3ConfigConvLowVoltAlarm | 1.3.6.1.4.1.318.1.1.7.2.4.2.2.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory For the Converter Low Voltage Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition.
| |||||||||||||||||||||
| Sdm3ConfigConvConfigAlarm | 1.3.6.1.4.1.318.1.1.7.2.4.2.2.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory For the Converter Configuration Alarm (indicating a new converter has been detected); Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition.
| |||||||||||||||||||||
| Sdm3ConfigConv1ofNAlarm | 1.3.6.1.4.1.318.1.1.7.2.4.2.2.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory For the Converter 1ofN Alarm (indicating action if ONE converter of a N+1 system has failed); Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition.
| |||||||||||||||||||||
| Sdm3ConfigConv2ofNAlarm | 1.3.6.1.4.1.318.1.1.7.2.4.2.2.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory For the Converter 2ofN Alarm (indicating action if TWO OR MORE converters of a N+1 system has failed); Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition.
| |||||||||||||||||||||
| Sdm3ConfigConvDiagAlarm | 1.3.6.1.4.1.318.1.1.7.2.4.2.2.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory For the Converter Diagnostics Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition. Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigConv1ofNAlarm OID to be activated if ONE converter fails in an N+1 system. It causes the alarm specified in the dm3ConfigConv2ofNAlarm OID to be activated if TWO OR MORE converters fail in an N+1 system.
| |||||||||||||||||||||
| Sdm3ConfigConvImbalanceAlarm | 1.3.6.1.4.1.318.1.1.7.2.4.2.2.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory For the Converter Imbalance Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition. Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigConv1ofNAlarm OID to be activated if ONE converter fails in an N+1 system. It causes the alarm specified in the dm3ConfigConv2ofNAlarm OID to be activated if TWO OR MORE converters fail in an N+1 system.
| |||||||||||||||||||||
| Sdm3ConfigConvCurrLimitAlarm | 1.3.6.1.4.1.318.1.1.7.2.4.2.2.8 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory For the Converter Current Limit Alarm (indicating the converter is in the Current Limit state); Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition. Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigConv1ofNAlarm OID to be activated if ONE converter fails in an N+1 system. It causes the alarm specified in the dm3ConfigConv2ofNAlarm OID to be activated if TWO OR MORE converters fail in an N+1 system.
| |||||||||||||||||||||
| Sdm3ConfigConvStandbyAlarm | 1.3.6.1.4.1.318.1.1.7.2.4.2.2.9 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory For the Converter Standby Alarm (indicating the converter is in the Standby state); Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition. Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigConv1ofNAlarm OID to be activated if ONE converter fails in an N+1 system. It causes the alarm specified in the dm3ConfigConv2ofNAlarm OID to be activated if TWO OR MORE converters fail in an N+1 system.
| |||||||||||||||||||||
| Sdm3ConfigConvFanFailAlarm | 1.3.6.1.4.1.318.1.1.7.2.4.2.2.10 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory For the Converter Fan Fail Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition. Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigConv1ofNAlarm OID to be activated if ONE converter fails in an N+1 system. It causes the alarm specified in the dm3ConfigConv2ofNAlarm OID to be activated if TWO OR MORE converters fail in an N+1 system.
| |||||||||||||||||||||
| Sdm3ConfigConvFailAlarm | 1.3.6.1.4.1.318.1.1.7.2.4.2.2.11 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory For the Converter Fail Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition. Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigConv1ofNAlarm OID to be activated if ONE converter fails in an N+1 system. It causes the alarm specified in the dm3ConfigConv2ofNAlarm OID to be activated if TWO OR MORE converters fail in an N+1 system.
| |||||||||||||||||||||
| Sdm3ConfigConvHwVoltAlarm | 1.3.6.1.4.1.318.1.1.7.2.4.2.2.12 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory For the Converter Voltage Alarm (indicating voltage outside realistic limits, or a possible measurement fault); Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition. Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigConv1ofNAlarm OID to be activated if ONE converter fails in an N+1 system. It causes the alarm specified in the dm3ConfigConv2ofNAlarm OID to be activated if TWO OR MORE converters fail in an N+1 system.
| |||||||||||||||||||||
| Ndm3ConfigRelays | 1.3.6.1.4.1.318.1.1.7.2.5 | ||||||||||||||||||||
| Ndm3ConfigOutputRelays | 1.3.6.1.4.1.318.1.1.7.2.5.1 | ||||||||||||||||||||
| Sdm3ConfigOutRlyTableSize | 1.3.6.1.4.1.318.1.1.7.2.5.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of DC powerplant Output Relays controllable by this IP address. | |||||||||||||||||||||
| Tdm3ConfigOutRlyTable | 1.3.6.1.4.1.318.1.1.7.2.5.1.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for accessing settings of the Output Relays. The number of entries is contained in the dm3ConfigOutRlyTableSize OID. | |||||||||||||||||||||
| Rdm3ConfigOutRlyEntry | 1.3.6.1.4.1.318.1.1.7.2.5.1.2.1 | NA | mandatory | ||||||||||||||||||
| Cdm3ConfigOutRlyIndex | 1.3.6.1.4.1.318.1.1.7.2.5.1.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the DC powerplant output relay. | |||||||||||||||||||||
| Cdm3ConfigOutRlyName | 1.3.6.1.4.1.318.1.1.7.2.5.1.2.1.2 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The name of the output relay. The maximum value is 16 characters. | |||||||||||||||||||||
| Cdm3ConfigOutRlyDelay | 1.3.6.1.4.1.318.1.1.7.2.5.1.2.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Output Relay Delay. This OID represents the time delay from the initiation of an output relay action to when the output relay action does occur. If the alarm condition disappears before the end of the delay, no action will occur. Delay for Major and Minor alarms is not configurable and is always set to 0. Values are represented in hundredths of seconds. Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively. | |||||||||||||||||||||
| Cdm3ConfigOutRlyAlarm | 1.3.6.1.4.1.318.1.1.7.2.5.1.2.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Output Relay Alarm. This setting indicates what action to perform in the event of an output relay alarm condition; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition. Relay Alarm for Major and Minor alarms is not configurable and is always set to alarmMajor and alarmMinor respectively.
| |||||||||||||||||||||
| Ndm3ConfigInputRelays | 1.3.6.1.4.1.318.1.1.7.2.5.2 | ||||||||||||||||||||
| Sdm3ConfigInRlyTableSize | 1.3.6.1.4.1.318.1.1.7.2.5.2.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of DC powerplant Input Relays controllable by this IP address. | |||||||||||||||||||||
| Tdm3ConfigInRlyTable | 1.3.6.1.4.1.318.1.1.7.2.5.2.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for accessing settings of the Input Relays. The number of entries is contained in the dm3ConfigInRlyTableSize OID. | |||||||||||||||||||||
| Rdm3ConfigInRlyEntry | 1.3.6.1.4.1.318.1.1.7.2.5.2.2.1 | NA | mandatory | ||||||||||||||||||
| Cdm3ConfigInRlyIndex | 1.3.6.1.4.1.318.1.1.7.2.5.2.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the DC powerplant input relay. | |||||||||||||||||||||
| Cdm3ConfigInRlyName | 1.3.6.1.4.1.318.1.1.7.2.5.2.2.1.2 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The name of the input relay. The maximum value is 16 characters. | |||||||||||||||||||||
| Cdm3ConfigInRlyDelay | 1.3.6.1.4.1.318.1.1.7.2.5.2.2.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Input Relay Delay. This OID represents the time delay from the initiation of an input relay action to when the input relay action does occur. If the alarm condition disappears before the end of the delay, no action will occur. Values are represented in hundredths of seconds. Attempts to set the value above or below the acceptable range of the powerplant will cause the value to be set at the high or low point of the range respectively. | |||||||||||||||||||||
| Cdm3ConfigInRlyAlarm | 1.3.6.1.4.1.318.1.1.7.2.5.2.2.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Input Relay Alarm. This setting indicates what action to perform in the event of an input relay alarm condition; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition.
| |||||||||||||||||||||
| Ndm3ConfigDistribution | 1.3.6.1.4.1.318.1.1.7.2.6 | ||||||||||||||||||||
| Ndm3ConfigBreakers | 1.3.6.1.4.1.318.1.1.7.2.6.1 | ||||||||||||||||||||
| Sdm3ConfigBreakersTableSize | 1.3.6.1.4.1.318.1.1.7.2.6.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of DC powerplant circuit breakers controllable by this IP address. | |||||||||||||||||||||
| Tdm3ConfigBreakersTable | 1.3.6.1.4.1.318.1.1.7.2.6.1.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for accessing settings of the circuit breakers. The number of entries is contained in the dm3ConfigBreakersTableSize OID. | |||||||||||||||||||||
| Rdm3ConfigBreakersEntry | 1.3.6.1.4.1.318.1.1.7.2.6.1.2.1 | NA | mandatory | ||||||||||||||||||
| Cdm3ConfigBreakersIndex | 1.3.6.1.4.1.318.1.1.7.2.6.1.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the DC powerplant circuit breaker. | |||||||||||||||||||||
| Cdm3ConfigBreakersName | 1.3.6.1.4.1.318.1.1.7.2.6.1.2.1.2 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The name of the circuit breaker. The maximum value is 16 characters. | |||||||||||||||||||||
| Cdm3ConfigBreakersAlarm | 1.3.6.1.4.1.318.1.1.7.2.6.1.2.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Circuit Breaker Alarm. This setting indicates what action to perform in the event of a circuit breaker alarm condition; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition.
| |||||||||||||||||||||
| Ndm3ConfigFuses | 1.3.6.1.4.1.318.1.1.7.2.6.2 | ||||||||||||||||||||
| Sdm3ConfigFusesTableSize | 1.3.6.1.4.1.318.1.1.7.2.6.2.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of DC powerplant Fuses controllable by this IP address. | |||||||||||||||||||||
| Tdm3ConfigFusesTable | 1.3.6.1.4.1.318.1.1.7.2.6.2.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for accessing settings of the Fuses. The number of entries is contained in the dm3ConfigFusesTableSize OID. | |||||||||||||||||||||
| Rdm3ConfigFusesEntry | 1.3.6.1.4.1.318.1.1.7.2.6.2.2.1 | NA | mandatory | ||||||||||||||||||
| Cdm3ConfigFusesIndex | 1.3.6.1.4.1.318.1.1.7.2.6.2.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the DC powerplant fuse. | |||||||||||||||||||||
| Cdm3ConfigFusesName | 1.3.6.1.4.1.318.1.1.7.2.6.2.2.1.2 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The name of the fuse. The maximum value is 16 characters. | |||||||||||||||||||||
| Cdm3ConfigFusesAlarm | 1.3.6.1.4.1.318.1.1.7.2.6.2.2.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Fuses Alarm. This setting indicates what action to perform in the event of a Fuse alarm condition; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition.
| |||||||||||||||||||||
| Ndm3Status | 1.3.6.1.4.1.318.1.1.7.3 | ||||||||||||||||||||
| Ndm3StatusSystem | 1.3.6.1.4.1.318.1.1.7.3.1 | ||||||||||||||||||||
| Sdm3StatusSystemTemp | 1.3.6.1.4.1.318.1.1.7.3.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory System temperature based on sensor on Master Controller PCB. Values are represented in thousandths of a degree. Units are displayed in the scale shown in the 'dm3StatusSysTempUnits' OID (Celsius or Fahrenheit). | |||||||||||||||||||||
| Sdm3StatusSystemStart | 1.3.6.1.4.1.318.1.1.7.3.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory Time stamp at DC powerplant initialization. The time is represented as MMM,DD,YYYY,HH:MM:SS. | |||||||||||||||||||||
| Sdm3StatusSysRemoteAccess | 1.3.6.1.4.1.318.1.1.7.3.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Remote Access indicator This setting indicates if configuration (write) access to the powerplant is enabled or disabled at the powerplant level. This value will be accessEnabled (1) if remote configuration is enabled, and accessDisabled (2) if remote configuration is disabled.
| |||||||||||||||||||||
| Sdm3StatusSysSecurityLevel | 1.3.6.1.4.1.318.1.1.7.3.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory This variable shows the current active security access level of controller. This can only be changed directly from the front panel. | |||||||||||||||||||||
| Sdm3StatusSysTempSanity | 1.3.6.1.4.1.318.1.1.7.3.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory System temperature sanity indicator. Indicates if the system temperature is reasonable. Reasonable is defined based on powerplant type. A value of saneYes (1) indicates temperature is reasonable, a value of saneNo (2) indicates it is not.
| |||||||||||||||||||||
| Sdm3StatusSysAlarmState | 1.3.6.1.4.1.318.1.1.7.3.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory System Alarm State. Reflects the alarm status of the overall DC system. If a minor alarm is present, the value will be alarmMinor(1). If a major alarm is present, the value will be alarmMajor(2). If both minor and a major alarm is present, the value will be alarmBoth(3). If no alarm is present, the value will be alarmNone(4).
| |||||||||||||||||||||
| Sdm3StatusSysTempUnits | 1.3.6.1.4.1.318.1.1.7.3.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The temperature scale used to display the temperature in the DC system, Celsius(1) or Fahrenheit(2). This setting is based on the system preferences configuration in the agent.
| |||||||||||||||||||||
| Ndm3StatusAlarms | 1.3.6.1.4.1.318.1.1.7.3.2 | ||||||||||||||||||||
| Sdm3StatusAlarmsTableSize | 1.3.6.1.4.1.318.1.1.7.3.2.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of DC powerplant alarms viewable by this IP address. | |||||||||||||||||||||
| Tdm3StatusAlarmsTable | 1.3.6.1.4.1.318.1.1.7.3.2.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for accessing system alarms. The number of entries is contained in the dm3StatusAlarmsTableSize OID. | |||||||||||||||||||||
| Rdm3StatusAlarmsEntry | 1.3.6.1.4.1.318.1.1.7.3.2.2.1 | NA | mandatory | ||||||||||||||||||
| Cdm3StatusAlarmsIndex | 1.3.6.1.4.1.318.1.1.7.3.2.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of the system alarm. | |||||||||||||||||||||
| Cdm3StatusAlarmsText | 1.3.6.1.4.1.318.1.1.7.3.2.2.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The 16 character text describing the active alarm condition. | |||||||||||||||||||||
| Ndm3StatusBattery | 1.3.6.1.4.1.318.1.1.7.3.3 | ||||||||||||||||||||
| Sdm3StatusBattCurrent | 1.3.6.1.4.1.318.1.1.7.3.3.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Battery Current: This OID shows the battery current in thousandths of Amps (mA). | |||||||||||||||||||||
| Sdm3StatusBattTemp | 1.3.6.1.4.1.318.1.1.7.3.3.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Battery Temperature: Values are represented in thousandths of a degree. Units are displayed in the scale shown in the 'dm3StatusSysTempUnits' OID (Celsius or Fahrenheit). | |||||||||||||||||||||
| Sdm3StatusBattCurrentSanity | 1.3.6.1.4.1.318.1.1.7.3.3.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Battery current sanity indicator. Indicates if the battery current is reasonable. Reasonable is defined based on powerplant type. A value of saneYes (1) indicates current is reasonable, a value of saneNo (2) indicates it is not.
| |||||||||||||||||||||
| Sdm3StatusBattTempSanity | 1.3.6.1.4.1.318.1.1.7.3.3.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Battery temperature sanity indicator. Indicates if the battery temperature is reasonable. Reasonable is defined based on powerplant type. A value of saneYes (1) indicates temperature is reasonable, a value of saneNo (2) indicates it is not.
| |||||||||||||||||||||
| Ndm3StatusOEM | 1.3.6.1.4.1.318.1.1.7.3.4 | ||||||||||||||||||||
| Sdm3StatusOEMrectOffset | 1.3.6.1.4.1.318.1.1.7.3.4.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory This OID shows the rectifier offset value in thousandths of Volts (mV). | |||||||||||||||||||||
| Sdm3StatusOEMrectGain | 1.3.6.1.4.1.318.1.1.7.3.4.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory This OID shows the rectifier gain value in thousandths of Volts (mV/V). | |||||||||||||||||||||
| Sdm3StatusOEMconvOffset | 1.3.6.1.4.1.318.1.1.7.3.4.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory This OID shows the converter offset value in thousandths of Volts (mV). | |||||||||||||||||||||
| Sdm3StatusOEMconvGain | 1.3.6.1.4.1.318.1.1.7.3.4.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory This OID shows the converter gain value in thousandths of Volts (mV/V). | |||||||||||||||||||||
| Sdm3StatusOEMshuntOffset | 1.3.6.1.4.1.318.1.1.7.3.4.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory This OID shows the shunt offset value in thousandths of Amps (mA). | |||||||||||||||||||||
| Sdm3StatusOEMshuntGain | 1.3.6.1.4.1.318.1.1.7.3.4.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory This OID shows the shunt gain value in thousandths of Amps (mA/A). | |||||||||||||||||||||
| Ndm3StatusLVD | 1.3.6.1.4.1.318.1.1.7.3.5 | ||||||||||||||||||||
| Sdm3StatusLVDTableSize | 1.3.6.1.4.1.318.1.1.7.3.5.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of DC powerplant LVDs viewable by this IP address. | |||||||||||||||||||||
| Tdm3StatusLVDTable | 1.3.6.1.4.1.318.1.1.7.3.5.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for accessing settings of the LVDs. The number of entries is contained in the dm3StatusLVDTableSize OID. | |||||||||||||||||||||
| Rdm3StatusLVDEntry | 1.3.6.1.4.1.318.1.1.7.3.5.2.1 | NA | mandatory | ||||||||||||||||||
| Cdm3StatusLVDIndex | 1.3.6.1.4.1.318.1.1.7.3.5.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the DC powerplant LVD. | |||||||||||||||||||||
| Cdm3StatusLVDName | 1.3.6.1.4.1.318.1.1.7.3.5.2.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The name of the LVD. The maximum size is 16 characters. The name is set by using the dm3ConfigLVDName OID. This OID is provided for informational purposes only. | |||||||||||||||||||||
| Cdm3StatusLVDState | 1.3.6.1.4.1.318.1.1.7.3.5.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this OID will return statusClosed (1) if the LVD is closed. statusOpened (2) will be returned if the LVD is opened.
| |||||||||||||||||||||
| Cdm3StatusLVDHwFault | 1.3.6.1.4.1.318.1.1.7.3.5.2.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this OID will return statusFault (1) if the LVD is faulted. statusNofault (2) will be returned if the LVD is not faulted.
| |||||||||||||||||||||
| Ndm3StatusPowerModules | 1.3.6.1.4.1.318.1.1.7.3.6 | ||||||||||||||||||||
| Ndm3StatusRectifier | 1.3.6.1.4.1.318.1.1.7.3.6.1 | ||||||||||||||||||||
| Sdm3StatusRectTableSize | 1.3.6.1.4.1.318.1.1.7.3.6.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of DC powerplant rectifiers viewable by this IP address. | |||||||||||||||||||||
| Tdm3StatusRectTable | 1.3.6.1.4.1.318.1.1.7.3.6.1.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for accessing settings of the rectifiers. The number of entries is contained in the dm3StatusRectTableSize OID. | |||||||||||||||||||||
| Rdm3StatusRectEntry | 1.3.6.1.4.1.318.1.1.7.3.6.1.2.1 | NA | mandatory | ||||||||||||||||||
| Cdm3StatusRectIndex | 1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the DC powerplant rectifier. | |||||||||||||||||||||
| Cdm3StatusRectID | 1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This OID shows the rectifier ID. This enumerates the number of the rectifier within a group of rectifiers. | |||||||||||||||||||||
| Cdm3StatusRectDesc | 1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory This OID shows the 16-character rectifier description. | |||||||||||||||||||||
| Cdm3StatusRectCurrent | 1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This OID shows the rectifier current in thousandths of Amps (mA). | |||||||||||||||||||||
| Cdm3StatusRectCurrentLimit | 1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this OID will return statusTrue (1) if the rectifier is in the Current Limit state. statusFalse (2) will be returned if the rectifier is not in the Current Limit state.
| |||||||||||||||||||||
| Cdm3StatusRectStandby | 1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this OID will return statusTrue (1) if the rectifier is in the Standby state. statusFalse (2) will be returned if the rectifier is not in the Standby state.
| |||||||||||||||||||||
| Cdm3StatusRectFanFail | 1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this OID will return statusTrue (1) if the rectifier Fan has failed. statusFalse (2) will be returned if the rectifier Fan has not failed.
| |||||||||||||||||||||
| Cdm3StatusRectFail | 1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this OID will return statusTrue (1) if the rectifier has failed. statusFalse (2) will be returned if the rectifier has not failed.
| |||||||||||||||||||||
| Cdm3StatusRectDevType | 1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.9 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This OID shows the rectifier device type. | |||||||||||||||||||||
| Cdm3StatusRectPhyAddr | 1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.10 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This OID shows the rectifier physical address (the address on the bus). | |||||||||||||||||||||
| Cdm3StatusRectCfg | 1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.11 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this OID will return statusTrue (1) if the rectifier is present after power-up or set-configuration. statusFalse (2) will be returned if the rectifier is not configured.
| |||||||||||||||||||||
| Cdm3StatusRectPcbRev | 1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.12 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This OID shows the rectifier device PCB serial number. | |||||||||||||||||||||
| Cdm3StatusRectFwVer | 1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.13 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This OID shows the rectifier device firmware revision. | |||||||||||||||||||||
| Cdm3StatusRectPresent | 1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.14 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this OID will return statusTrue (1) if the rectifier is present. statusFalse (2) will be returned if the rectifier is not present.
| |||||||||||||||||||||
| Cdm3StatusRectDiagPass | 1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.15 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this OID will return statusTrue (1) if the rectifier diagnostics have passed. statusFalse (2) will be returned if the rectifier diagnostics have not passed.
| |||||||||||||||||||||
| Cdm3StatusRectState | 1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.16 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This OID shows the rectifier device state as defined by the device status register. | |||||||||||||||||||||
| Sdm3StatusSysRectVoltSanity | 1.3.6.1.4.1.318.1.1.7.3.6.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Rectifier voltage sanity indicator. Indicates if the rectifier voltage is reasonable. Reasonable is defined based on powerplant type. A value of saneYes (1) indicates voltage is reasonable, a value of saneNo (2) indicates it is not.
| |||||||||||||||||||||
| Sdm3StatusSysRectAvailable | 1.3.6.1.4.1.318.1.1.7.3.6.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Getting this OID will return statusTrue (1) if the rectifier is available. statusFalse (2) will be returned if the rectifier is not available.
| |||||||||||||||||||||
| Sdm3StatusSysRectType | 1.3.6.1.4.1.318.1.1.7.3.6.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory This OID shows the type of rectifier the system has. There can only be a single type of rectifier in the power plant | |||||||||||||||||||||
| Sdm3StatusSysRectVoltage | 1.3.6.1.4.1.318.1.1.7.3.6.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory This OID shows the system level rectifier voltage in thousandths of Volts (mV). | |||||||||||||||||||||
| Sdm3StatusSysRectCurrent | 1.3.6.1.4.1.318.1.1.7.3.6.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory This OID shows the system level rectifier current in thousandths of Amps (mA). | |||||||||||||||||||||
| Ndm3StatusConverter | 1.3.6.1.4.1.318.1.1.7.3.6.2 | ||||||||||||||||||||
| Sdm3StatusConvTableSize | 1.3.6.1.4.1.318.1.1.7.3.6.2.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of DC powerplant converters viewable by this IP address. | |||||||||||||||||||||
| Tdm3StatusConvTable | 1.3.6.1.4.1.318.1.1.7.3.6.2.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for viewing status of the converters. The number of entries is contained in the dm3StatusConvTableSize OID. | |||||||||||||||||||||
| Rdm3StatusConvEntry | 1.3.6.1.4.1.318.1.1.7.3.6.2.2.1 | NA | mandatory | ||||||||||||||||||
| Cdm3StatusConvIndex | 1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the DC powerplant converter. | |||||||||||||||||||||
| Cdm3StatusConvID | 1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This OID shows the converter ID. This enumerates the number of the converter within a group of converters. | |||||||||||||||||||||
| Cdm3StatusConvDesc | 1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory This OID shows the 16 character converter description. | |||||||||||||||||||||
| Cdm3StatusConvCurrent | 1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This OID shows the converter current in thousandths of Amps (mA). | |||||||||||||||||||||
| Cdm3StatusConvCurrentLimit | 1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this OID will return statusTrue (1) if the converter is in the Current Limit state. statusFalse (2) will be returned if the converter is not in the Current Limit state.
| |||||||||||||||||||||
| Cdm3StatusConvStandby | 1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this OID will return statusTrue (1) if the converter is in the Standby state. statusFalse (2) will be returned if the converter is not in the Standby state.
| |||||||||||||||||||||
| Cdm3StatusConvFanFail | 1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this OID will return statusTrue (1) if the converter Fan has failed. statusFalse (2) will be returned if the converter Fan has not failed.
| |||||||||||||||||||||
| Cdm3StatusConvFail | 1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this OID will return statusTrue (1) if the converter has failed. statusFalse (2) will be returned if the converter has not failed.
| |||||||||||||||||||||
| Cdm3StatusConvDevType | 1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.9 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This OID shows the converter device type. | |||||||||||||||||||||
| Cdm3StatusConvPhyAddr | 1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.10 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This OID shows the converter physical address (the address on the bus). | |||||||||||||||||||||
| Cdm3StatusConvCfg | 1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.11 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this OID will return statusTrue (1) if the converter is present after power-up or set-configuration. statusFalse (2) will be returned if the converter is not configured.
| |||||||||||||||||||||
| Cdm3StatusConvPcbRev | 1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.12 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This OID shows the converter device PCB serial number. | |||||||||||||||||||||
| Cdm3StatusConvFwVer | 1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.13 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This OID shows the converter device firmware version. | |||||||||||||||||||||
| Cdm3StatusConvPresent | 1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.14 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this OID will return statusTrue (1) if the converter is present. statusFalse (2) will be returned if the converter is not present.
| |||||||||||||||||||||
| Cdm3StatusConvDiagPass | 1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.15 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this OID will return statusTrue (1) if the converter diagnostics have passed. statusFalse (2) will be returned if the converter diagnostics have not passed.
| |||||||||||||||||||||
| Cdm3StatusConvState | 1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.16 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This OID shows the converter state as defined by the device status register. | |||||||||||||||||||||
| Sdm3StatusSysConvVoltSanity | 1.3.6.1.4.1.318.1.1.7.3.6.2.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Converter voltage sanity indicator. Indicates if the converter voltage is reasonable. Reasonable is defined based on powerplant type. A value of saneYes (1) indicates voltage is reasonable, a value of saneNo (2) indicates it is not.
| |||||||||||||||||||||
| Sdm3StatusSysConvAvailable | 1.3.6.1.4.1.318.1.1.7.3.6.2.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Getting this OID will return statusTrue (1) if the converter is available. statusFalse (2) will be returned if the converter is not available.
| |||||||||||||||||||||
| Sdm3StatusSysConvType | 1.3.6.1.4.1.318.1.1.7.3.6.2.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory This OID shows the converter type. | |||||||||||||||||||||
| Sdm3StatusSysConvVoltage | 1.3.6.1.4.1.318.1.1.7.3.6.2.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory This OID shows the system level converter voltage in thousandths of volts (mV). | |||||||||||||||||||||
| Sdm3StatusSysConvCurrent | 1.3.6.1.4.1.318.1.1.7.3.6.2.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory This OID shows the system level converter current in thousandths of Amps (mA). | |||||||||||||||||||||
| Ndm3StatusRelays | 1.3.6.1.4.1.318.1.1.7.3.7 | ||||||||||||||||||||
| Ndm3StatusOutputRelays | 1.3.6.1.4.1.318.1.1.7.3.7.1 | ||||||||||||||||||||
| Sdm3StatusOutRlyTableSize | 1.3.6.1.4.1.318.1.1.7.3.7.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of DC powerplant output relays viewable by this IP address. | |||||||||||||||||||||
| Tdm3StatusOutRlyTable | 1.3.6.1.4.1.318.1.1.7.3.7.1.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for viewing status of the output relays. The number of entries is contained in the dm3StatusOutRlyTableSize OID. | |||||||||||||||||||||
| Rdm3StatusOutRlyEntry | 1.3.6.1.4.1.318.1.1.7.3.7.1.2.1 | NA | mandatory | ||||||||||||||||||
| Cdm3StatusOutRlyIndex | 1.3.6.1.4.1.318.1.1.7.3.7.1.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the DC powerplant output relay. | |||||||||||||||||||||
| Cdm3StatusOutRlyName | 1.3.6.1.4.1.318.1.1.7.3.7.1.2.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The name of the output relay. The maximum size is 16 characters. The name is set by using the dm3ConfigOutRlyName OID. This OID is provided for informational purposes only. | |||||||||||||||||||||
| Cdm3StatusOutRlyStatus | 1.3.6.1.4.1.318.1.1.7.3.7.1.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this OID will return statusOn (1) if the output relay is enabled/on. statusOff (2) will be returned if the output relay is disabled/off.
| |||||||||||||||||||||
| Ndm3StatusInputRelays | 1.3.6.1.4.1.318.1.1.7.3.7.2 | ||||||||||||||||||||
| Sdm3StatusInRlyTableSize | 1.3.6.1.4.1.318.1.1.7.3.7.2.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of DC powerplant input relays viewable by this IP address. | |||||||||||||||||||||
| Tdm3StatusInRlyTable | 1.3.6.1.4.1.318.1.1.7.3.7.2.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for viewing status of the input relays. The number of entries is contained in the dm3StatusInRlyTableSize OID. | |||||||||||||||||||||
| Rdm3StatusInRlyEntry | 1.3.6.1.4.1.318.1.1.7.3.7.2.2.1 | NA | mandatory | ||||||||||||||||||
| Cdm3StatusInRlyIndex | 1.3.6.1.4.1.318.1.1.7.3.7.2.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the DC powerplant input relay. | |||||||||||||||||||||
| Cdm3StatusInRlyName | 1.3.6.1.4.1.318.1.1.7.3.7.2.2.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The name of the input relay. The maximum size is 16 characters. The name is set by using the dm3ConfigInRlyName OID. This OID is provided for informational purposes only. | |||||||||||||||||||||
| Cdm3StatusInRlyStatus | 1.3.6.1.4.1.318.1.1.7.3.7.2.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this OID will return statusOn (1) if the input relay is enabled/on. statusOff (2) will be returned if the input relay is disabled/off.
| |||||||||||||||||||||
| Ndm3StatusDistribution | 1.3.6.1.4.1.318.1.1.7.3.8 | ||||||||||||||||||||
| Ndm3StatusBreakers | 1.3.6.1.4.1.318.1.1.7.3.8.1 | ||||||||||||||||||||
| Sdm3StatusBreakersTableSize | 1.3.6.1.4.1.318.1.1.7.3.8.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of DC powerplant circuit breakers viewable by this IP address. | |||||||||||||||||||||
| Tdm3StatusBreakersTable | 1.3.6.1.4.1.318.1.1.7.3.8.1.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for viewing status of the circuit breakers. The number of entries is contained in the dm3StatusBreakersTableSize OID. | |||||||||||||||||||||
| Rdm3StatusBreakersEntry | 1.3.6.1.4.1.318.1.1.7.3.8.1.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The circuit breaker to gather status from. | |||||||||||||||||||||
| Cdm3StatusBreakersIndex | 1.3.6.1.4.1.318.1.1.7.3.8.1.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the DC powerplant circuit breaker. | |||||||||||||||||||||
| Cdm3StatusBreakersName | 1.3.6.1.4.1.318.1.1.7.3.8.1.2.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The name of the circuit breaker. The maximum size is 16 characters. The name is set by using the dm3ConfigBreakersName OID. This OID is provided for informational purposes only. | |||||||||||||||||||||
| Cdm3StatusBreakersStatus | 1.3.6.1.4.1.318.1.1.7.3.8.1.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this OID will return statusClosed (1) if the circuit breaker is closed. statusOpen (2) will be returned if the circuit breaker is open.
| |||||||||||||||||||||
| Ndm3StatusFuses | 1.3.6.1.4.1.318.1.1.7.3.8.2 | ||||||||||||||||||||
| Sdm3StatusFusesTableSize | 1.3.6.1.4.1.318.1.1.7.3.8.2.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of DC powerplant fuses controllable by this IP address. | |||||||||||||||||||||
| Tdm3StatusFusesTable | 1.3.6.1.4.1.318.1.1.7.3.8.2.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for viewing status of the fuses. The number of entries is contained in the dm3StatusFusesTableSize OID. | |||||||||||||||||||||
| Rdm3StatusFusesEntry | 1.3.6.1.4.1.318.1.1.7.3.8.2.2.1 | NA | mandatory | ||||||||||||||||||
| Cdm3StatusFusesIndex | 1.3.6.1.4.1.318.1.1.7.3.8.2.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the DC powerplant fuse. | |||||||||||||||||||||
| Cdm3StatusFusesName | 1.3.6.1.4.1.318.1.1.7.3.8.2.2.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The name of the fuse. The maximum size is 16 characters. The name is set by using the dm3ConfigFuseName OID. This OID is provided for informational purposes only. | |||||||||||||||||||||
| Cdm3StatusFusesStatus | 1.3.6.1.4.1.318.1.1.7.3.8.2.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this OID will return statusClosed (1) if the fuse is closed. statusOpen (2) will be returned if the fuse is open.
| |||||||||||||||||||||
| NautomaticTransferSwitch | 1.3.6.1.4.1.318.1.1.8 | ||||||||||||||||||||
| NatsIdent | 1.3.6.1.4.1.318.1.1.8.1 | ||||||||||||||||||||
| SatsIdentHardwareRev | 1.3.6.1.4.1.318.1.1.8.1.1 | DisplayString | RO | mandatory | R01 | ||||||||||||||||
scalar · DisplayString · read-only · mandatory The hardware revision of the Automatic Transfer Switch. This value is set at the factory. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SatsIdentFirmwareRev | 1.3.6.1.4.1.318.1.1.8.1.2 | DisplayString | RO | mandatory | 4.1.9 | ||||||||||||||||
scalar · DisplayString · read-only · mandatory A string identifying the Automatic Transfer Switch firmware revision. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SatsIdentFirmwareDate | 1.3.6.1.4.1.318.1.1.8.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The date of release for this Automatic Transfer Switch firmware revision. | |||||||||||||||||||||
| SatsIdentDateOfManufacture | 1.3.6.1.4.1.318.1.1.8.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The date when the Automatic Transfer Switch was manufactured in mm/dd/yyyy format. This value is set at the factory. | |||||||||||||||||||||
| SatsIdentModelNumber | 1.3.6.1.4.1.318.1.1.8.1.5 | DisplayString | RO | mandatory | AP4423 | ||||||||||||||||
scalar · DisplayString · read-only · mandatory A string identifying the model number of the Automatic Transfer Switch. This value is set at the factory. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SatsIdentSerialNumber | 1.3.6.1.4.1.318.1.1.8.1.6 | DisplayString | RO | mandatory | <private> | ||||||||||||||||
scalar · DisplayString · read-only · mandatory A string identifying the serial number of the Automatic Transfer Switch. This value is set at the factory. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SatsIdentNominalLineVoltage | 1.3.6.1.4.1.318.1.1.8.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory RMS Utility Voltage measured in Volts. | |||||||||||||||||||||
| SatsIdentNominalLineFrequency | 1.3.6.1.4.1.318.1.1.8.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Utility Power Frequency measured in Hertz. | |||||||||||||||||||||
| SatsIdentDeviceRating | 1.3.6.1.4.1.318.1.1.8.1.9 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory This gives the device rating in Amps | |||||||||||||||||||||
| SatsIdentDeviceName | 1.3.6.1.4.1.318.1.1.8.1.10 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A user-defined string identifying the ATS | |||||||||||||||||||||
| SatsIdentDeviceLocation | 1.3.6.1.4.1.318.1.1.8.1.11 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A user-defined string identifying the location of ATS | |||||||||||||||||||||
| SatsIdentContact | 1.3.6.1.4.1.318.1.1.8.1.12 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A user-defined string identifying the person to contact regarding the ATS | |||||||||||||||||||||
| SatsIdentBootMonitorRev | 1.3.6.1.4.1.318.1.1.8.1.13 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The ATS Boot Monitor version | |||||||||||||||||||||
| SatsIdentLongDescription | 1.3.6.1.4.1.318.1.1.8.1.14 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The ATS Long Description name | |||||||||||||||||||||
| SatsIdentNMCSerialNumber | 1.3.6.1.4.1.318.1.1.8.1.15 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The ATS Network Management Card (NMC) serial number | |||||||||||||||||||||
| SatsIdentAppBuildDate | 1.3.6.1.4.1.318.1.1.8.1.16 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The ATS Application build date | |||||||||||||||||||||
| SatsIdentAOSBuildDate | 1.3.6.1.4.1.318.1.1.8.1.17 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The ATS AOS build date | |||||||||||||||||||||
| SatsIdentBootMonBuildDate | 1.3.6.1.4.1.318.1.1.8.1.18 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The ATS Boot Monitor build date | |||||||||||||||||||||
| NatsCalibration | 1.3.6.1.4.1.318.1.1.8.2 | ||||||||||||||||||||
| NatsCalibrationInput | 1.3.6.1.4.1.318.1.1.8.2.1 | ||||||||||||||||||||
| SatsCalibrationNumInputs | 1.3.6.1.4.1.318.1.1.8.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of inputs to this device. It is not applicable to AP44xxA units or newer. | |||||||||||||||||||||
| SatsCalibrationNumInputPhases | 1.3.6.1.4.1.318.1.1.8.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of phases per input for this device. It is not applicable to AP44xxA units or newer. | |||||||||||||||||||||
| TatsCalibrationInputPhaseTable | 1.3.6.1.4.1.318.1.1.8.2.1.3 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory The number of phases per input line to this device. It is not applicable to AP44xxA units or newer. | |||||||||||||||||||||
| RatsCalibrationInputPhaseEntry | 1.3.6.1.4.1.318.1.1.8.2.1.3.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing calibration information applicable to a particular input phase. It is not applicable to AP44xxA units or newer. | |||||||||||||||||||||
| CatsCalibrationInputTableIndex | 1.3.6.1.4.1.318.1.1.8.2.1.3.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The input identifier. It is not applicable to AP44xxA units or newer. | |||||||||||||||||||||
| CatsCalibrationInputPhaseTableIndex | 1.3.6.1.4.1.318.1.1.8.2.1.3.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The input phase identifier. It is not applicable to AP44xxA units or newer. | |||||||||||||||||||||
| CatsLineVoltageCalibrationFactor | 1.3.6.1.4.1.318.1.1.8.2.1.3.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The Line Voltage Calibration factor. This value is set at the factory. It is not applicable to AP44xxA units or newer. | |||||||||||||||||||||
| NatsCalibrationPowerSupply | 1.3.6.1.4.1.318.1.1.8.2.2 | ||||||||||||||||||||
| SatsCalibrationPowerSupplyVoltages | 1.3.6.1.4.1.318.1.1.8.2.2.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of power supply voltages supported by this device. This variable indicates the number of rows in the atsCalibrationPowerSupplyTable. It is not applicable to AP44xxA units or newer. | |||||||||||||||||||||
| TatsCalibrationPowerSupplyVoltageTable | 1.3.6.1.4.1.318.1.1.8.2.2.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of Power Supply table entries. It is not applicable to AP44xxA units or newer. | |||||||||||||||||||||
| RatsCalibrationPowerSupplyVoltageEntry | 1.3.6.1.4.1.318.1.1.8.2.2.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular Power Supply Voltage. It is not applicable to AP44xxA units or newer. | |||||||||||||||||||||
| CatsCalibrationPowerSupplyVoltageTableIndex | 1.3.6.1.4.1.318.1.1.8.2.2.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The power supply voltage identifier. It is not applicable to AP44xxA units or newer. | |||||||||||||||||||||
| CatsCalibrationPowerSupplyVoltage | 1.3.6.1.4.1.318.1.1.8.2.2.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This value describes the power supply voltage of 24V Source A, 24V Source B, +12V, -12V and 5V. It is not applicable to AP44xxA units or newer.
| |||||||||||||||||||||
| CatsPowerSupplyVoltageCalibrationFactor | 1.3.6.1.4.1.318.1.1.8.2.2.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The Line Voltage Calibration factor. This value is set at the factory. It is not applicable to AP44xxA units or newer. | |||||||||||||||||||||
| Tats4gCalibrationPowerSupplyVoltageTable | 1.3.6.1.4.1.318.1.1.8.2.2.3 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of Power Supply table entries. It is applicable only to AP44xx units. | |||||||||||||||||||||
| Rats4gCalibrationPowerSupplyVoltageEntry | 1.3.6.1.4.1.318.1.1.8.2.2.3.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular Power Supply Voltage. It is applicable only to AP44xx ATS units. | |||||||||||||||||||||
| Cats4gCalibrationPowerSupplyVoltageTableIndex | 1.3.6.1.4.1.318.1.1.8.2.2.3.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The power supply voltage identifier. It is applicable only to AP44xx ATS units. | |||||||||||||||||||||
| Cats4gCalibrationPowerSupplyVoltage | 1.3.6.1.4.1.318.1.1.8.2.2.3.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This value describes the power supply voltage of 24V Source A, 24V Source B, VBoost Source A, VBoost Source B, 3.3V, 1.0V. It is applicable only to AP44xx units.
| |||||||||||||||||||||
| Cats4gPowerSupplyVoltageCalibrationFactor | 1.3.6.1.4.1.318.1.1.8.2.2.3.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The Line Voltage Calibration factor. This value is set at the factory. It is applicable only to AP44xx units. | |||||||||||||||||||||
| NatsCalibrationOutput | 1.3.6.1.4.1.318.1.1.8.2.3 | ||||||||||||||||||||
| SatsCalibrationNumOutputs | 1.3.6.1.4.1.318.1.1.8.2.3.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of output lines from this device. This variable indicates the number of rows in the atsCalibrationOutputTable. It is not applicable to AP44xxA units or newer. | |||||||||||||||||||||
| SatsCalibrationNumOutputPhases | 1.3.6.1.4.1.318.1.1.8.2.3.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of output phases utilized in this device. It is not applicable to AP44xxA units or newer. | |||||||||||||||||||||
| TatsCalibrationOutputTable | 1.3.6.1.4.1.318.1.1.8.2.3.3 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of output table entries. It is not applicable to AP44xxA units or newer. | |||||||||||||||||||||
| RatsCalibrationOutputEntry | 1.3.6.1.4.1.318.1.1.8.2.3.3.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular output. It is not applicable to AP44xxA units or newer. | |||||||||||||||||||||
| CatsCalibrationOutputTableIndex | 1.3.6.1.4.1.318.1.1.8.2.3.3.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The output identifier. It is not applicable to AP44xxA units or newer. | |||||||||||||||||||||
| CatsCalibrationOutputPhasesTableIndex | 1.3.6.1.4.1.318.1.1.8.2.3.3.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Description of each calibration factor for each output phase utilized in this device and one for neutral. It is not applicable to AP44xxA units or newer.
| |||||||||||||||||||||
| CatsOutputCurrentCalibrationFactor | 1.3.6.1.4.1.318.1.1.8.2.3.3.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The output current calibration factor. It is not applicable to AP44xxA units or newer. | |||||||||||||||||||||
| NatsControl | 1.3.6.1.4.1.318.1.1.8.3 | ||||||||||||||||||||
| SatsControlResetATS | 1.3.6.1.4.1.318.1.1.8.3.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Setting this variable will cause the Automatic Transfer Switch to perform a power-on reset. It is not applicable to AP44xx or newer.
| |||||||||||||||||||||
| SatsControlClearAllAlarms | 1.3.6.1.4.1.318.1.1.8.3.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Setting this variable will clear all alarms in the Automatic Transfer Switch. Returns (-1) if unsupported.
| |||||||||||||||||||||
| NatsConfig | 1.3.6.1.4.1.318.1.1.8.4 | ||||||||||||||||||||
| SatsConfigProductName | 1.3.6.1.4.1.318.1.1.8.4.1 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory A configurable character string. | |||||||||||||||||||||
| SatsConfigPreferredSource | 1.3.6.1.4.1.318.1.1.8.4.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory This variable returns the preferred source of power when both sources are OK.
| |||||||||||||||||||||
| SatsConfigFrontPanelLockout | 1.3.6.1.4.1.318.1.1.8.4.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Setting this variable to disableFrontPanel(1), prevents source preference configuration of the Automatic Transfer Switch via the Front Panel. Setting this variable to enableFrontPanel(2)allows, source preference configuration of the Automatic Transfer Switch via the Front Panel.
| |||||||||||||||||||||
| SatsConfigVoltageSensitivity | 1.3.6.1.4.1.318.1.1.8.4.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory This variable defines the sensitivity to changes in voltage: high(1) for best protection, low(2) for frequent small line voltage changes.
| |||||||||||||||||||||
| SatsConfigTransferVoltageRange | 1.3.6.1.4.1.318.1.1.8.4.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory This variable defines the range of acceptable voltage from a power source. If the voltage measured from the selected input source is not within this range, the Automatic Transfer Switch will switch over (transfer) to the alternate power source.
| |||||||||||||||||||||
| SatsConfigCurrentLimit | 1.3.6.1.4.1.318.1.1.8.4.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The threshold (in Amps) at which an Over Current Alarm will be generated. This OID returns the overload threshold value of the OID atsConfigPhaseOverLoadThreshold for the 1U ATS and OID atsConfigBankOverLoadThreshold of total for the 2U ATS. Setting this OID does not have any impact on the device. | |||||||||||||||||||||
| SatsConfigResetValues | 1.3.6.1.4.1.318.1.1.8.4.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Resets the ATS configuration to its default values. Returns (-1) if not supported.
| |||||||||||||||||||||
| SatsConfigLineVRMS | 1.3.6.1.4.1.318.1.1.8.4.8 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory To configure the input RMS voltage. | |||||||||||||||||||||
| SatsConfigLineVRMSNarrowLimit | 1.3.6.1.4.1.318.1.1.8.4.9 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory To configure the Line VRMS Narrow Limit. | |||||||||||||||||||||
| SatsConfigLineVRMSMediumLimit | 1.3.6.1.4.1.318.1.1.8.4.10 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory To configure the Line VRMS Medium Limit. | |||||||||||||||||||||
| SatsConfigLineVRMSWideLimit | 1.3.6.1.4.1.318.1.1.8.4.11 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory To configure the Line VRMS Wide Limit. | |||||||||||||||||||||
| SatsConfigFrequencyDeviation | 1.3.6.1.4.1.318.1.1.8.4.12 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory To configure the frequency deviation. AP77xx units may use 1, 2, or 3 (Hz). AP44xx and AP44xxA units may use 3, 5, or 10 (Hz).
| |||||||||||||||||||||
| SatsConfigBankTableSize | 1.3.6.1.4.1.318.1.1.8.4.13 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The size of the bank table. | |||||||||||||||||||||
| TatsConfigBankTable | 1.3.6.1.4.1.318.1.1.8.4.14 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for configuration of each ATS bank. | |||||||||||||||||||||
| RatsConfigBankEntry | 1.3.6.1.4.1.318.1.1.8.4.14.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory This gives access to bank current threshold | |||||||||||||||||||||
| CatsConfigBankTableIndex | 1.3.6.1.4.1.318.1.1.8.4.14.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory An index to the bank table entry. | |||||||||||||||||||||
| CatsConfigBank | 1.3.6.1.4.1.318.1.1.8.4.14.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The bank number of an ATS
| |||||||||||||||||||||
| CatsConfigBankLowLoadThreshold | 1.3.6.1.4.1.318.1.1.8.4.14.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory A threshold that indicates the current drawn is nearing a low consumption condition. It is represented in Amps. A warning will be issued when the load is less than the threshold value. A threshold value of 0 Amps disables this warning. Maximum value must be less than the value returned by the atsConfigBankNearOverLoadThreshold OID. | |||||||||||||||||||||
| CatsConfigBankNearOverLoadThreshold | 1.3.6.1.4.1.318.1.1.8.4.14.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory A threshold that indicates the current drawn is nearing an overload condition. It is represented in Amps. A warning will be issued when the load is greater than or equal to the threshold value. Minimum value must be greater than the value returned by the atsConfigBankLowLoadThreshold OID. Maximum value must be less than or equal to the value returned by the atsConfigBankOverLoadThreshold OID. | |||||||||||||||||||||
| CatsConfigBankOverLoadThreshold | 1.3.6.1.4.1.318.1.1.8.4.14.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory A threshold that indicates the current drawn has entered an overload condition. It is represented in Amps. A warning will be issued when the load is greater than or equal to the threshold value. Minimum value must be greater than or equal to the value returned by the atsConfigBankNearOverLoadThreshold OID. Maximum value must be less than or equal to the value returned by atsIdentDeviceRating OID. | |||||||||||||||||||||
| SatsConfigPhaseTableSize | 1.3.6.1.4.1.318.1.1.8.4.15 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The size of the phase table. | |||||||||||||||||||||
| TatsConfigPhaseTable | 1.3.6.1.4.1.318.1.1.8.4.16 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for configuration of each ATS phase. | |||||||||||||||||||||
| RatsConfigPhaseEntry | 1.3.6.1.4.1.318.1.1.8.4.16.1 | NA | mandatory | ||||||||||||||||||
| CatsConfigPhaseTableIndex | 1.3.6.1.4.1.318.1.1.8.4.16.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the phase table entry. | |||||||||||||||||||||
| CatsConfigPhase | 1.3.6.1.4.1.318.1.1.8.4.16.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The phase number of an ATS
| |||||||||||||||||||||
| CatsConfigPhaseLowLoadThreshold | 1.3.6.1.4.1.318.1.1.8.4.16.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory A threshold that indicates the current drawn is nearing a low consumption condition. It is represented in Amps. A warning will be issued when the load is less than the threshold value. A threshold value of 0 Amps disables this warning. Maximum value must be less than the value returned by the atsConfigPhaseNearOverLoadThreshold OID. | |||||||||||||||||||||
| CatsConfigPhaseNearOverLoadThreshold | 1.3.6.1.4.1.318.1.1.8.4.16.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory A threshold that indicates the current drawn is nearing an overload condition. It is represented in Amps. A warning will be issued when the load is greater than or equal to the threshold value. Minimum value must be greater than the value returned by the atsConfigPhaseLowLoadThreshold OID. Maximum value must be less than or equal to the value returned by the atsConfigPhaseOverLoadThreshold OID. | |||||||||||||||||||||
| CatsConfigPhaseOverLoadThreshold | 1.3.6.1.4.1.318.1.1.8.4.16.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory A threshold that indicates the current drawn has entered an overload condition. It is represented in Amps. A warning will be issued when the load is greater than or equal to the threshold value. Minimum value must be greater than or equal to the value returned by the atsConfigPhaseNearOverLoadThreshold OID. Maximum value must be less than or equal to the value returned by atsIdentDeviceRating OID. | |||||||||||||||||||||
| SatsConfigDeviceLocation | 1.3.6.1.4.1.318.1.1.8.4.17 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory A user-defined string identifying the location of the ATS | |||||||||||||||||||||
| SatsConfigContact | 1.3.6.1.4.1.318.1.1.8.4.18 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory A user-defined string identifying the person to contact regarding the ATS | |||||||||||||||||||||
| NatsStatus | 1.3.6.1.4.1.318.1.1.8.5 | ||||||||||||||||||||
| NatsStatusDeviceStatus | 1.3.6.1.4.1.318.1.1.8.5.1 | ||||||||||||||||||||
| SatsStatusCommStatus | 1.3.6.1.4.1.318.1.1.8.5.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory This variable returns the current communication status of the Automatic Transfer Switch.
| |||||||||||||||||||||
| SatsStatusSelectedSource | 1.3.6.1.4.1.318.1.1.8.5.1.2 | INTEGER | RO | mandatory | sourceA(1) | ||||||||||||||||
scalar · INTEGER · read-only · mandatory This variable returns the current source of power.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SatsStatusRedundancyState | 1.3.6.1.4.1.318.1.1.8.5.1.3 | INTEGER | RO | mandatory | atsFullyRedundant(2) | ||||||||||||||||
scalar · INTEGER · read-only · mandatory This variable returns the current redundancy state of the ATS. atsRedundancyLost(1) indicates that the ATS is unable to switch over to the alternate power source if the current source fails. atsFullyRedundant(2) indicates that the ATS will switch over to the alternate power source if the current source fails.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SatsStatusOverCurrentState | 1.3.6.1.4.1.318.1.1.8.5.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory This variable returns the output current state of the ATS. atsOverCurrent(1) indicates that the ATS has exceeded the output current threshold and will not allow a switch over to the alternate power source if the current source fails. atsCurrentOK(2) indicates that the output current is below the output current threshold. This OID returns the value of the OID atsOutputPhaseState for the 1U ATS and OID atsOutputBankState for the 2U ATS.
| |||||||||||||||||||||
| SatsStatus5VPowerSupply | 1.3.6.1.4.1.318.1.1.8.5.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory This variable returns the present state of the ATS 5V power supply. atsPowerSupplyFailure(1) indicates the 5V power supply has failed and that the ATS serial port Configuration Menu is not accessible . atsPowerSupplyOK(2) indicates that the ATS 5V power supply is operating within tolerance. This is only supported by AP77xx SKUs.
| |||||||||||||||||||||
| SatsStatus24VPowerSupply | 1.3.6.1.4.1.318.1.1.8.5.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory This variable returns the present state of the ATS 24V power supply for Source A. atsPowerSupplyFailure(1) indicates the 24V power supply has failed and the ATS is unable to switch over to the alternate power source if the current source fails. atsPowerSupplyOK(2) indicates that the ATS 24V power supply is operating within tolerance.
| |||||||||||||||||||||
| SatsStatus24VSourceBPowerSupply | 1.3.6.1.4.1.318.1.1.8.5.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory This variable returns the present state of the ATS 24V power supply for Source B. atsPowerSupplyFailure(1) indicates the 24V power supply has failed and the ATS is unable to switch over to the alternate power source if the current source fails. atsPowerSupplyOK(2) indicates that the ATS 24V power supply is operating within tolerance.
| |||||||||||||||||||||
| SatsStatusPlus12VPowerSupply | 1.3.6.1.4.1.318.1.1.8.5.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory This variable returns the present state of the ATS 12V power supply. atsPowerSupplyFailure(1) indicates the 12V power supply has failed and the ATS is unable to monitor the current sensors. atsPowerSupplyOK(2) indicates that the ATS 12V power supply is operating within tolerance. This is only supported by AP77xx SKUs.
| |||||||||||||||||||||
| SatsStatusMinus12VPowerSupply | 1.3.6.1.4.1.318.1.1.8.5.1.9 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory This variable returns the present state of the ATS -12V power supply. atsPowerSupplyFailure(1) indicates the -12V power supply has failed and the ATS is unable to monitor the current sensors. atsPowerSupplyOK(2) indicates that the ATS -12V power supply is operating within tolerance. This is only supported by AP77xx SKUs.
| |||||||||||||||||||||
| SatsStatusSwitchStatus | 1.3.6.1.4.1.318.1.1.8.5.1.10 | INTEGER | RO | mandatory | ok(2) | ||||||||||||||||
scalar · INTEGER · read-only · mandatory This variable returns the status of the ATS.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SatsStatusFrontPanel | 1.3.6.1.4.1.318.1.1.8.5.1.11 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory This variable returns the present state of the ATS front panel. locked(1): Front panel button cannot be used to change the sources. unlocked(2): Front panel button can be used to change the sources.
| |||||||||||||||||||||
| SatsStatusSourceAStatus | 1.3.6.1.4.1.318.1.1.8.5.1.12 | INTEGER | RO | mandatory | ok(2) | ||||||||||||||||
scalar · INTEGER · read-only · mandatory This variable returns the status of the Source A.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SatsStatusSourceBStatus | 1.3.6.1.4.1.318.1.1.8.5.1.13 | INTEGER | RO | mandatory | ok(2) | ||||||||||||||||
scalar · INTEGER · read-only · mandatory This variable returns the status of the Source B.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SatsStatusPhaseSyncStatus | 1.3.6.1.4.1.318.1.1.8.5.1.14 | INTEGER | RO | mandatory | inSync(1) | ||||||||||||||||
scalar · INTEGER · read-only · mandatory This variable returns the status of the phase synch.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SatsStatusVoltageOutStatus | 1.3.6.1.4.1.318.1.1.8.5.1.15 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory This variable returns the output voltage status.
| |||||||||||||||||||||
| SatsStatusHardwareStatus | 1.3.6.1.4.1.318.1.1.8.5.1.16 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory This variable returns the status of display board hardware.
| |||||||||||||||||||||
| SatsStatus3dot3VPowerSupply | 1.3.6.1.4.1.318.1.1.8.5.1.17 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory This variable returns the present state of the ATS 3.3V supply. atsPowerSupplyOK(2) indicates that the 3.3V power supply is operating within tolerance, while atsPowerSupplyFailure(1) indicates that it has failed. This is supported by AP44xx units and newer.
| |||||||||||||||||||||
| SatsStatus1Dot0VPowerSupply | 1.3.6.1.4.1.318.1.1.8.5.1.18 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory This variable returns the present state of the ATS 1.0V supply. atsPowerSupplyOK(2) indicates that the 1.0V power supply is operating within tolerance, while atsPowerSupplyFailure(1) indicates that it has failed. This is only supported for AP44xx units.
| |||||||||||||||||||||
| SatsStatusVBoostSourceA | 1.3.6.1.4.1.318.1.1.8.5.1.19 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory This variable returns the present state of the ATS Source A Boost 48V supply. atsPowerSupplyOK(2) indicates that the Source A 48V power supply is operating within tolerance, while atsPowerSupplyFailure(1) indicates that it has failed. This is supported by AP44xx units and newer.
| |||||||||||||||||||||
| SatsStatusVBoostSourceB | 1.3.6.1.4.1.318.1.1.8.5.1.20 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory This variable returns the present state of the ATS Source B Boost 48V supply. atsPowerSupplyOK(2) indicates that the Source B 48V power supply is operating within tolerance, while atsPowerSupplyFailure(1) indicates that it has failed. This is supported by AP44xx units and newer.
| |||||||||||||||||||||
| SatsStatusFuseSourceA | 1.3.6.1.4.1.318.1.1.8.5.1.21 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory This variable returns the Souce A Fuse State. atsFuseStatusClose(1) indicates that Source A Fuse is close(normal), atsFuseStatusOpen(2) indicates that Source A Fuse is open.
| |||||||||||||||||||||
| SatsStatusFuseSourceB | 1.3.6.1.4.1.318.1.1.8.5.1.22 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory This variable returns the Souce B Fuse State. atsFuseStatusClose(1) indicates that Source B Fuse is close(normal), atsFuseStatusOpen(2) indicates that Source B Fuse is open.
| |||||||||||||||||||||
| NatsStatusResetValues | 1.3.6.1.4.1.318.1.1.8.5.2 | ||||||||||||||||||||
| SatsStatusResetMaxMinValues | 1.3.6.1.4.1.318.1.1.8.5.2.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Resets the maximum and minimum ATS values: atsInputMaxVoltage, atsInputMinVoltage, atsInputMaxCurrent, atsInputMinCurrent, atsInputMaxPower, atsInputMinPower, atsOutputMaxCurrent, atsOutputMinCurrent, atsOutputMaxLoad, atsOutputMinLoad, atsOutputMaxPercentLoad, atsOutputMinPercentLoad, atsOutputMaxPower, atsOutputMinPower, atsOutputMaxPercentPower, atsOutputMinPercentPower. These variables represent the maximum and minimum ATS values since the last time they were read or reset by this OID. Values unsupported by this ATS will return (-1).
| |||||||||||||||||||||
| NatsStatusInput | 1.3.6.1.4.1.318.1.1.8.5.3 | ||||||||||||||||||||
| SatsNumInputs | 1.3.6.1.4.1.318.1.1.8.5.3.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of input feeds to this device. This variable indicates the number of rows in the input table. | |||||||||||||||||||||
| TatsInputTable | 1.3.6.1.4.1.318.1.1.8.5.3.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of input table entries. The number of entries is given by the value of atsNumInputs. | |||||||||||||||||||||
| RatsInputEntry | 1.3.6.1.4.1.318.1.1.8.5.3.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular input.
| |||||||||||||||||||||
| CatsInputTableIndex | 1.3.6.1.4.1.318.1.1.8.5.3.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The input identifier. | |||||||||||||||||||||
| CatsNumInputPhases | 1.3.6.1.4.1.318.1.1.8.5.3.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The number of input phases utilized in this device. The sum of all the atsNumInputPhases variable indicates the number of rows in the input phase table. | |||||||||||||||||||||
| CatsInputVoltageOrientation | 1.3.6.1.4.1.318.1.1.8.5.3.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The input voltage orientation: 1: unknown for this Source 2: singlePhase - phase 1 voltage is between Phase 1 and Neutral. 3: splitPhase - phase 1 voltage is between Phase 1 and Neutral; phase 2 voltage is between Phase 2 and Neutral; phase 3 voltage is between Phase 1 and Phase 2. 4: threePhasePhaseToNeutral - phase 1 voltage is between Phase 1 and Neutral; phase 2 voltage is between Phase 2 and Neutral; phase 3 voltage is between Phase 3 and Neutral. 5: threePhasePhaseToPhase - phase 1 voltage is between Phase 1 and Phase 2; phase 2 voltage is between Phase 2 and Phase 3; phase 3 voltage is between Phase 3 and Phase 1.
| |||||||||||||||||||||
| CatsInputFrequency | 1.3.6.1.4.1.318.1.1.8.5.3.2.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The input frequency in Hertz, or -1 if it's unsupported by this Source. | |||||||||||||||||||||
| CatsInputType | 1.3.6.1.4.1.318.1.1.8.5.3.2.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The input type.
| |||||||||||||||||||||
| CatsInputName | 1.3.6.1.4.1.318.1.1.8.5.3.2.1.6 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory A name given to a particular input. | |||||||||||||||||||||
| TatsInputPhaseTable | 1.3.6.1.4.1.318.1.1.8.5.3.3 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of input table entries. The number of entries is given by the sum of the atsNumInputPhases. | |||||||||||||||||||||
| RatsInputPhaseEntry | 1.3.6.1.4.1.318.1.1.8.5.3.3.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular input phase. | |||||||||||||||||||||
| CatsInputPhaseTableIndex | 1.3.6.1.4.1.318.1.1.8.5.3.3.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The input identifier. | |||||||||||||||||||||
| CatsInputPhaseIndex | 1.3.6.1.4.1.318.1.1.8.5.3.3.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The input phase identifier. | |||||||||||||||||||||
| CatsInputVoltage | 1.3.6.1.4.1.318.1.1.8.5.3.3.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The input voltage in VAC, or -1 if it's unsupported by this Source. | |||||||||||||||||||||
| CatsInputMaxVoltage | 1.3.6.1.4.1.318.1.1.8.5.3.3.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The maximum input voltage in VAC measured since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported. | |||||||||||||||||||||
| CatsInputMinVoltage | 1.3.6.1.4.1.318.1.1.8.5.3.3.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The minimum input voltage in VAC measured since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported. | |||||||||||||||||||||
| CatsInputCurrent | 1.3.6.1.4.1.318.1.1.8.5.3.3.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The input current in amperes, or -1 if it's unsupported by this Source. | |||||||||||||||||||||
| CatsInputMaxCurrent | 1.3.6.1.4.1.318.1.1.8.5.3.3.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The maximum input current in amperes measured since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported. | |||||||||||||||||||||
| CatsInputMinCurrent | 1.3.6.1.4.1.318.1.1.8.5.3.3.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The minimum input current in amperes measured since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported. | |||||||||||||||||||||
| CatsInputPower | 1.3.6.1.4.1.318.1.1.8.5.3.3.1.9 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The input power in Watts, or -1 if it's unsupported by this Source. | |||||||||||||||||||||
| CatsInputMaxPower | 1.3.6.1.4.1.318.1.1.8.5.3.3.1.10 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The maximum input power in Watts measured since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported. | |||||||||||||||||||||
| CatsInputMinPower | 1.3.6.1.4.1.318.1.1.8.5.3.3.1.11 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The minimum input power in Watts measured since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported. | |||||||||||||||||||||
| NatsStatusOutput | 1.3.6.1.4.1.318.1.1.8.5.4 | ||||||||||||||||||||
| SatsNumOutputs | 1.3.6.1.4.1.318.1.1.8.5.4.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of output feeds to this device. This variable indicates the number of rows in the output table. | |||||||||||||||||||||
| TatsOutputTable | 1.3.6.1.4.1.318.1.1.8.5.4.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of output table entries. The number of entries is given by the value of atsOutputNumPhases. | |||||||||||||||||||||
| RatsOutputEntry | 1.3.6.1.4.1.318.1.1.8.5.4.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular output.
| |||||||||||||||||||||
| CatsOutputTableIndex | 1.3.6.1.4.1.318.1.1.8.5.4.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The output identifier. | |||||||||||||||||||||
| CatsNumOutputPhases | 1.3.6.1.4.1.318.1.1.8.5.4.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The number of output phases utilized in this device. The sum of all the atsNumOutputPhases variable indicates the number of rows in the output phase table. | |||||||||||||||||||||
| CatsOutputVoltageOrientation | 1.3.6.1.4.1.318.1.1.8.5.4.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The output voltage orientation: 1: unknown for this ATS 2: singlePhase - phase 1 voltage is between Phase 1 and Neutral. 3: splitPhase - phase 1 voltage is between Phase 1 and Neutral; phase 2 voltage is between Phase 2 and Neutral; phase 3 voltage is between Phase 1 and Phase 2. 4: threePhasePhaseToNeutral - phase 1 voltage is between Phase 1 and Neutral; phase 2 voltage is between Phase 2 and Neutral; phase 3 voltage is between Phase 3 and Neutral. 5: threePhasePhaseToPhase - phase 1 voltage is between Phase 1 and Phase 2; phase 2 voltage is between Phase 2 and Phase 3; phase 3 voltage is between Phase 3 and Phase 1.
| |||||||||||||||||||||
| CatsOutputFrequency | 1.3.6.1.4.1.318.1.1.8.5.4.2.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The output frequency in Hertz, or -1 if it's unsupported by this ATS. | |||||||||||||||||||||
| TatsOutputPhaseTable | 1.3.6.1.4.1.318.1.1.8.5.4.3 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of output table entries. The number of entries is given by the sum of the atsNumOutputPhases. | |||||||||||||||||||||
| RatsOutputPhaseEntry | 1.3.6.1.4.1.318.1.1.8.5.4.3.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular output phase. | |||||||||||||||||||||
| CatsOutputPhaseTableIndex | 1.3.6.1.4.1.318.1.1.8.5.4.3.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The output identifier. | |||||||||||||||||||||
| CatsOutputPhaseIndex | 1.3.6.1.4.1.318.1.1.8.5.4.3.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Description of each output phase utilized in this device and one for neutral.
| |||||||||||||||||||||
| CatsOutputVoltage | 1.3.6.1.4.1.318.1.1.8.5.4.3.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The output voltage in VAC, or -1 if it's unsupported by this ATS. | |||||||||||||||||||||
| CatsOutputCurrent | 1.3.6.1.4.1.318.1.1.8.5.4.3.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The output current in 0.1 amperes drawn by the load on the ATS, or -1 if it's unsupported by this ATS. | |||||||||||||||||||||
| CatsOutputMaxCurrent | 1.3.6.1.4.1.318.1.1.8.5.4.3.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The maximum output current in 0.1 amperes measured since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported. | |||||||||||||||||||||
| CatsOutputMinCurrent | 1.3.6.1.4.1.318.1.1.8.5.4.3.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The minimum output current in 0.1 amperes measured since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported. | |||||||||||||||||||||
| CatsOutputLoad | 1.3.6.1.4.1.318.1.1.8.5.4.3.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The output load in VA, or -1 if it's unsupported by this ATS. | |||||||||||||||||||||
| CatsOutputMaxLoad | 1.3.6.1.4.1.318.1.1.8.5.4.3.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The maximum output load in VA measured since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported. | |||||||||||||||||||||
| CatsOutputMinLoad | 1.3.6.1.4.1.318.1.1.8.5.4.3.1.9 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The minimum output load in VA measured since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported. | |||||||||||||||||||||
| CatsOutputPercentLoad | 1.3.6.1.4.1.318.1.1.8.5.4.3.1.10 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The percentage of the ATS load capacity in VA at redundancy @ (n + x) presently being used on this output phase, or -1 if it's unsupported by this ATS. | |||||||||||||||||||||
| CatsOutputMaxPercentLoad | 1.3.6.1.4.1.318.1.1.8.5.4.3.1.11 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The maximum percentage of the ATS load capacity in VA measured at redundancy @ (n + x) presently being used on this output phase since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported. | |||||||||||||||||||||
| CatsOutputMinPercentLoad | 1.3.6.1.4.1.318.1.1.8.5.4.3.1.12 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The minimum percentage of the ATS load capacity in VA measured at redundancy @ (n + x) presently being used on this output phase since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported. | |||||||||||||||||||||
| CatsOutputPower | 1.3.6.1.4.1.318.1.1.8.5.4.3.1.13 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The output apparent power in VA, or -1 if it's unsupported by this ATS. | |||||||||||||||||||||
| CatsOutputMaxPower | 1.3.6.1.4.1.318.1.1.8.5.4.3.1.14 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The maximum output power in VAs measured since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported. | |||||||||||||||||||||
| CatsOutputMinPower | 1.3.6.1.4.1.318.1.1.8.5.4.3.1.15 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The minimum output power in VA measured since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported. | |||||||||||||||||||||
| CatsOutputPercentPower | 1.3.6.1.4.1.318.1.1.8.5.4.3.1.16 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The percentage of the ATSpower capacity in VA at redundancy @ (n + x) presently being used on this output phase, or -1 if it's unsupported by this ATS. | |||||||||||||||||||||
| CatsOutputMaxPercentPower | 1.3.6.1.4.1.318.1.1.8.5.4.3.1.17 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The maximum percentage of the ATSpower capacity in VA measured at redundancy @ (n + x) presently being used on this output phase since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported. | |||||||||||||||||||||
| CatsOutputMinPercentPower | 1.3.6.1.4.1.318.1.1.8.5.4.3.1.18 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The minimum percentage of the ATSpower capacity in VA measured at redundancy @ (n + x) presently being used on this output phase since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported. | |||||||||||||||||||||
| CatsOutputPhaseState | 1.3.6.1.4.1.318.1.1.8.5.4.3.1.19 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this OID will return the phase load state. normal(1) indicates that the bank is operating properly within the atsConfigPhaseLowLoadThreshold and atsConfigPhaseNearOverLoadThreshold OID values. lowload(2) indicates that the bank load has dropped below the atsConfigPhaseLowLoadThreshold OID value. An SNMP trap will occur when this state is entered or cleared. nearoverload(3) indicates that the bank load is greater than or equal to the atsConfigPhaseNearOverLoadThreshold OID value. An SNMP trap will occur when this state is entered or cleared. overload(4) indicates that the bank load is greater than or equal to the atsConfigPhaseOverLoadThreshold OID value. An SNMP trap will occur when this state is entered or cleared.
| |||||||||||||||||||||
| SatsOutputBankTableSize | 1.3.6.1.4.1.318.1.1.8.5.4.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The size of the bank table. | |||||||||||||||||||||
| TatsOutputBankTable | 1.3.6.1.4.1.318.1.1.8.5.4.5 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting table entries. | |||||||||||||||||||||
| RatsOutputBankEntry | 1.3.6.1.4.1.318.1.1.8.5.4.5.1 | NA | mandatory | ||||||||||||||||||
| CatsOutputBankTableIndex | 1.3.6.1.4.1.318.1.1.8.5.4.5.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the bank table entry. | |||||||||||||||||||||
| CatsOutputPhase | 1.3.6.1.4.1.318.1.1.8.5.4.5.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The phase number of an ATS
| |||||||||||||||||||||
| CatsOutputBank | 1.3.6.1.4.1.318.1.1.8.5.4.5.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The bank number of an ATS
| |||||||||||||||||||||
| CatsOutputBankCurrent | 1.3.6.1.4.1.318.1.1.8.5.4.5.1.4 | Gauge | RO | mandatory | |||||||||||||||||
column · Gauge · read-only · mandatory Getting this OID will return the bank current measured in tenths of Amps. | |||||||||||||||||||||
| CatsOutputBankState | 1.3.6.1.4.1.318.1.1.8.5.4.5.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this OID will return the bank load state. normal(1) indicates that the bank is operating properly within the atsConfigBankLowLoadThreshold and atsConfigBankNearOverLoadThreshold OID values. lowload(2) indicates that the bank load has dropped below the atsConfigBankLowLoadThreshold OID value. An SNMP trap will occur when this state is entered or cleared. nearoverload(3) indicates that the bank load is greater than or equal to the atsConfigBankNearOverLoadThreshold OID value. An SNMP trap will occur when this state is entered or cleared. overload(4) indicates that the bank load is greater than or equal to the atsConfigBankOverLoadThreshold OID value. An SNMP trap will occur when this state is entered or cleared.
| |||||||||||||||||||||
| CatsOutputBankOutputVoltage | 1.3.6.1.4.1.318.1.1.8.5.4.5.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The output voltage in VAC, or -1 if it's unsupported by this ATS. | |||||||||||||||||||||
| CatsOutputBankMaxCurrent | 1.3.6.1.4.1.318.1.1.8.5.4.5.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The maximum output current, on the bank represented by OID atsOutputBank, in 0.1 amperes measured since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported. | |||||||||||||||||||||
| CatsOutputBankMinCurrent | 1.3.6.1.4.1.318.1.1.8.5.4.5.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The minimum output current, on the bank represented by OID atsOutputBank, in 0.1 amperes measured since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported. | |||||||||||||||||||||
| CatsOutputBankLoad | 1.3.6.1.4.1.318.1.1.8.5.4.5.1.9 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The output load, on the bank represented by OID atsOutputBank, in VA, or -1 if it's unsupported by this ATS. | |||||||||||||||||||||
| CatsOutputBankMaxLoad | 1.3.6.1.4.1.318.1.1.8.5.4.5.1.10 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The maximum output load, on the bank represented by OID atsOutputBank, in VA measured since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported. | |||||||||||||||||||||
| CatsOutputBankMinLoad | 1.3.6.1.4.1.318.1.1.8.5.4.5.1.11 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The minimum output load, on the bank represented by OID atsOutputBank, in VA measured since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported. | |||||||||||||||||||||
| CatsOutputBankPercentLoad | 1.3.6.1.4.1.318.1.1.8.5.4.5.1.12 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The percentage of the ATS load capacity in VA at redundancy @ (n + x) presently being used on this bank, represented by OID atsOutputBank. Returns (-1) if unsupported. | |||||||||||||||||||||
| CatsOutputBankMaxPercentLoad | 1.3.6.1.4.1.318.1.1.8.5.4.5.1.13 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The maximum percentage of the ATS load capacity in VA measured at redundancy @ (n + x) presently being used on this bank, represented by OID atsOutputBank, since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported. | |||||||||||||||||||||
| CatsOutputBankMinPercentLoad | 1.3.6.1.4.1.318.1.1.8.5.4.5.1.14 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The minimum percentage of the ATS load capacity in VA measured at redundancy @ (n + x) presently being used on this bank, represented by OID atsOutputBank, since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported. | |||||||||||||||||||||
| CatsOutputBankPower | 1.3.6.1.4.1.318.1.1.8.5.4.5.1.15 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The output apparent power in VA on the bank represented by OID atsOutputBank or -1 if it's unsupported by this ATS. | |||||||||||||||||||||
| CatsOutputBankMaxPower | 1.3.6.1.4.1.318.1.1.8.5.4.5.1.16 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The maximum output power in VA measured on the bank represented by OID atsOutputBank since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported. | |||||||||||||||||||||
| CatsOutputBankMinPower | 1.3.6.1.4.1.318.1.1.8.5.4.5.1.17 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The minimum output power in VA measured on the bank represented by OID atsOutputBank since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported. | |||||||||||||||||||||
| CatsOutputBankPercentPower | 1.3.6.1.4.1.318.1.1.8.5.4.5.1.18 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The percentage of the ATSpower capacity in Watts at redundancy @ (n + x) presently being used on this bank, represented by OID atsOutputBank, or -1 if it's unsupported by this ATS. | |||||||||||||||||||||
| CatsOutputBankMaxPercentPower | 1.3.6.1.4.1.318.1.1.8.5.4.5.1.19 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The maximum percentage of the ATSpower capacity in VA measured at redundancy @ (n + x) presently being used on this bank, represented by OID atsOutputBank, since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported. | |||||||||||||||||||||
| CatsOutputBankMinPercentPower | 1.3.6.1.4.1.318.1.1.8.5.4.5.1.20 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The minimum percentage of the ATSpower capacity in VA measured at redundancy @ (n + x) presently being used on this bank, represented by OID atsOutputBank since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported. | |||||||||||||||||||||
| Ndc2 | 1.3.6.1.4.1.318.1.1.9 | ||||||||||||||||||||
| Ndcmim2Ident | 1.3.6.1.4.1.318.1.1.9.1 | ||||||||||||||||||||
| Ndcmim2IdentSystem | 1.3.6.1.4.1.318.1.1.9.1.1 | ||||||||||||||||||||
| Sdcmim2IdentSysFWVersion | 1.3.6.1.4.1.318.1.1.9.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Integer representation of the power plant Master Controller firmware revision. | |||||||||||||||||||||
| Ndcmim2Control | 1.3.6.1.4.1.318.1.1.9.2 | ||||||||||||||||||||
| Ndcmim2ControlSystem | 1.3.6.1.4.1.318.1.1.9.2.1 | ||||||||||||||||||||
| Sdcmim2ControlRunFunctBatteryTest | 1.3.6.1.4.1.318.1.1.9.2.1.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Getting this OID will return the battery functional test state. If the test is off, the battTestOff (1) value will be returned. If the test is on, the battTestOn (2) value will be returned. Setting this OID to battTestOff (1) will turn the battery functional test off. Setting this OID to battTestOn (2) will turn the battery functional test on.
| |||||||||||||||||||||
| Sdcmim2ControlRunCapacityBatteryTest | 1.3.6.1.4.1.318.1.1.9.2.1.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Getting this OID will return the battery capacity test state. If the test is off, the battTestOff (1) value will be returned. If the test is on, the battTestOn (2) value will be returned. Setting this OID to battTestOff (1) will turn the battery capacity test off. Setting this OID to battTestOn (2) will turn the battery capacity test on.
| |||||||||||||||||||||
| Ndcmim2Config | 1.3.6.1.4.1.318.1.1.9.3 | ||||||||||||||||||||
| Ndcmim2ConfigSystem | 1.3.6.1.4.1.318.1.1.9.3.1 | ||||||||||||||||||||
| Sdcmim2ConfigSysHighTempTrip | 1.3.6.1.4.1.318.1.1.9.3.1.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Trip level (threshold) at which System High Temp alarm condition is created. Range 28 to 100 (degC). Values are represented in thousandths of a degree. Units are displayed in the scale shown in the 'dcmim2StatusSysTempUnits' OID (Celsius or Fahrenheit). | |||||||||||||||||||||
| Sdcmim2ConfigSysHighTempReset | 1.3.6.1.4.1.318.1.1.9.3.1.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Level at which System High Temp alarm condition is reset (cleared). Range 25 to (upper temp - 3) (degC). Values are represented in thousandths of a degree. Units are displayed in the scale shown in the 'dcmim2StatusSysTempUnits' OID (Celsius or Fahrenheit). | |||||||||||||||||||||
| Sdcmim2ConfigSysLowTempTrip | 1.3.6.1.4.1.318.1.1.9.3.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Trip level (threshold) at which System Low Temp alarm condition is created. Range -100 to 10 (degC). Values are represented in thousandths of a degree. Units are displayed in the scale shown in the 'dcmim2StatusSysTempUnits' OID (Celsius or Fahrenheit). | |||||||||||||||||||||
| Sdcmim2ConfigSysLowTempReset | 1.3.6.1.4.1.318.1.1.9.3.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Level at which System Low Temp alarm condition is reset (cleared). Range (lower temp + 3) to 13 (degC). Values are represented in thousandths of a degree. Units are displayed in the scale shown in the 'dcmim2StatusSysTempUnits' OID (Celsius or Fahrenheit). | |||||||||||||||||||||
| Ndcmim2ConfigBattery | 1.3.6.1.4.1.318.1.1.9.3.2 | ||||||||||||||||||||
| Sdcmim2ConfigBattFloatVolt | 1.3.6.1.4.1.318.1.1.9.3.2.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Battery Float Voltage defined at 25 degrees Celsius. Values are represented in thousandths of Volts (mV). | |||||||||||||||||||||
| Sdcmim2ConfigBattMaxRecharge | 1.3.6.1.4.1.318.1.1.9.3.2.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Battery Maximum Recharge Rate. This is the maximum current used during battery charging. Values are represented in thousandths of Amps (mA). | |||||||||||||||||||||
| Sdcmim2ConfigBattMfgCapacity | 1.3.6.1.4.1.318.1.1.9.3.2.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Battery capacity (Amp-Hour Size) as specified by the battery manufacturer. Values are represented in thousandths of Amp hours (mAHr). | |||||||||||||||||||||
| Sdcmim2ConfigBattType | 1.3.6.1.4.1.318.1.1.9.3.2.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Type of battery in the powerplant Valid values range from 0 to 254. | |||||||||||||||||||||
| Sdcmim2ConfigBattFunctTestDuration | 1.3.6.1.4.1.318.1.1.9.3.2.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Duration of the battery functional test. Values are represented in thousandths of seconds (mSecs). | |||||||||||||||||||||
| Sdcmim2ConfigBattFunctTestThresh | 1.3.6.1.4.1.318.1.1.9.3.2.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Threshold the battery voltage of the system must remain above in order to pass the battery functional test. Values are represented in thousandths of Volts (mV). | |||||||||||||||||||||
| Sdcmim2ConfigBattCapacityTestPercent | 1.3.6.1.4.1.318.1.1.9.3.2.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Threshold for good battery capacity test results. Values range from 0 to 100 percent. | |||||||||||||||||||||
| Sdcmim2ConfigBattCapacityTestEndThresh | 1.3.6.1.4.1.318.1.1.9.3.2.8 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Safeguard voltage at which battery capacity test will end if there is a battery problem. Values are represented in thousandths of Volts (mV). | |||||||||||||||||||||
| Sdcmim2ConfigBattCapacityTestCurrent | 1.3.6.1.4.1.318.1.1.9.3.2.9 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Constant current value used during battery capacity testing. Values are represented in thousandths of Amps (mA). | |||||||||||||||||||||
| Ndcmim2ConfigLVD | 1.3.6.1.4.1.318.1.1.9.3.3 | ||||||||||||||||||||
| Sdcmim2ConfigLVDTableSize | 1.3.6.1.4.1.318.1.1.9.3.3.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of DC powerplant LVDs controllable by this IP address. | |||||||||||||||||||||
| Tdcmim2ConfigLVDTable | 1.3.6.1.4.1.318.1.1.9.3.3.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for accessing settings of the LVDs. The number of entries is contained in the dcmim2ConfigLVDTableSize OID. | |||||||||||||||||||||
| Rdcmim2ConfigLVDEntry | 1.3.6.1.4.1.318.1.1.9.3.3.2.1 | NA | mandatory | ||||||||||||||||||
| Cdcmim2ConfigLVDIndex | 1.3.6.1.4.1.318.1.1.9.3.3.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the DC powerplant LVD. | |||||||||||||||||||||
| Cdcmim2ConfigLVDTrip | 1.3.6.1.4.1.318.1.1.9.3.3.2.1.2 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory LVD Trip threshold. System bus voltage at which LVD will trip (open) during a battery backup operation. Values are represented in thousandths of Volts (mV). | |||||||||||||||||||||
| Cdcmim2ConfigLVDReset | 1.3.6.1.4.1.318.1.1.9.3.3.2.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory LVD Reset threshold. System bus voltage at which LVD will reset (close) after AC power has been restored. Values are represented in thousandths of Volts (mV). | |||||||||||||||||||||
| Cdcmim2ConfigLVDState | 1.3.6.1.4.1.318.1.1.9.3.3.2.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this OID will return statusClosed (1) if the LVD is closed. statusOpened (2) will be returned if the LVD is opened.
| |||||||||||||||||||||
| Ndcmim2Status | 1.3.6.1.4.1.318.1.1.9.4 | ||||||||||||||||||||
| Ndcmim2StatusSystem | 1.3.6.1.4.1.318.1.1.9.4.1 | ||||||||||||||||||||
| Sdcmim2StatusSysRectCurrent | 1.3.6.1.4.1.318.1.1.9.4.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory System (Total Rectifier) current in thousandths of Amps (mA). | |||||||||||||||||||||
| Sdcmim2StatusSysLoadCurrent | 1.3.6.1.4.1.318.1.1.9.4.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Load current in thousandths of Amps (mA). | |||||||||||||||||||||
| Sdcmim2StatusSysBusVoltage | 1.3.6.1.4.1.318.1.1.9.4.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory System bus voltage in thousandths of Volts (mV). | |||||||||||||||||||||
| Sdcmim2StatusSysAmbientTemp | 1.3.6.1.4.1.318.1.1.9.4.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory System temperature based on sensor on Master Controller PCB. Values are represented in thousandths of a degree. Units are displayed in the scale shown in the 'dcmim2StatusSysTempUnits' OID (Celsius or Fahrenheit). | |||||||||||||||||||||
| Sdcmim2StatusSysUpTime | 1.3.6.1.4.1.318.1.1.9.4.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory Length of time since the DC Powerplant controller has been powered up. | |||||||||||||||||||||
| Sdcmim2StatusSysTempUnits | 1.3.6.1.4.1.318.1.1.9.4.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The temperature scale used to display the temperature in the DC system, Celsius(1) or Fahrenheit(2). This setting is based on the system preferences configuration in the agent.
| |||||||||||||||||||||
| Ndcmim2StatusRectifier | 1.3.6.1.4.1.318.1.1.9.4.2 | ||||||||||||||||||||
| Sdcmim2StatusRectTableSize | 1.3.6.1.4.1.318.1.1.9.4.2.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of DC powerplant rectifiers viewable by this IP address. | |||||||||||||||||||||
| Tdcmim2StatusRectTable | 1.3.6.1.4.1.318.1.1.9.4.2.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for accessing settings of the rectifiers. The number of entries is contained in the dcmim2StatusRectTableSize OID. | |||||||||||||||||||||
| Rdcmim2StatusRectEntry | 1.3.6.1.4.1.318.1.1.9.4.2.2.1 | NA | mandatory | ||||||||||||||||||
| Cdcmim2StatusRectIndex | 1.3.6.1.4.1.318.1.1.9.4.2.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the DC powerplant rectifier. | |||||||||||||||||||||
| Cdcmim2StatusRectDevType | 1.3.6.1.4.1.318.1.1.9.4.2.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This OID shows the rectifier device type. | |||||||||||||||||||||
| Cdcmim2StatusRectID | 1.3.6.1.4.1.318.1.1.9.4.2.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This OID shows the rectifier ID. This enumerates the number of the rectifier within a group of rectifiers. | |||||||||||||||||||||
| Cdcmim2StatusRectPhyAddr | 1.3.6.1.4.1.318.1.1.9.4.2.2.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This OID shows the rectifier physical address (the address on the bus). | |||||||||||||||||||||
| Cdcmim2StatusRectFail | 1.3.6.1.4.1.318.1.1.9.4.2.2.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this OID will return statusTrue (1) if the rectifier has failed. statusFalse (2) will be returned if the rectifier has not failed.
| |||||||||||||||||||||
| Cdcmim2StatusRectCurrent | 1.3.6.1.4.1.318.1.1.9.4.2.2.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This OID shows the individual rectifier current in thousandths of Amps (mA). | |||||||||||||||||||||
| Ndcmim2StatusBattery | 1.3.6.1.4.1.318.1.1.9.4.3 | ||||||||||||||||||||
| Sdcmim2StatusBattFloatVolt | 1.3.6.1.4.1.318.1.1.9.4.3.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Battery Float Voltage represented in thousandths of Volts (mV). | |||||||||||||||||||||
| Sdcmim2StatusBattCurrent | 1.3.6.1.4.1.318.1.1.9.4.3.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Battery Current: This OID shows the battery current in thousandths of Amps (mA). | |||||||||||||||||||||
| Sdcmim2StatusBattTemp | 1.3.6.1.4.1.318.1.1.9.4.3.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Battery Temperature: Values are represented in thousandths of a degree. Units are displayed in the scale shown in the 'dcmim2StatusSysTempUnits' OID (Celsius or Fahrenheit). | |||||||||||||||||||||
| Sdcmim2StatusBattMfgCapacity | 1.3.6.1.4.1.318.1.1.9.4.3.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Battery capacity (Amp-Hour Size) as specified by the battery manufacturer. Values are represented in thousandths of Amp hours (mAHr). | |||||||||||||||||||||
| Sdcmim2StatusBattTestCapacity | 1.3.6.1.4.1.318.1.1.9.4.3.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Battery capacity (Amp-Hour Size) as determined by the battery capacity test. Values are represented in thousandths of Amp hours (mAHr). | |||||||||||||||||||||
| Sdcmim2StatusBattFunctTestResult | 1.3.6.1.4.1.318.1.1.9.4.3.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Results of the last battery functional test that was run.
| |||||||||||||||||||||
| Sdcmim2StatusBattCapacityTestResult | 1.3.6.1.4.1.318.1.1.9.4.3.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Results of the last battery capacity test that was run.
| |||||||||||||||||||||
| Ndcmim2StatusLVD | 1.3.6.1.4.1.318.1.1.9.4.4 | ||||||||||||||||||||
| Sdcmim2StatusLVDTableSize | 1.3.6.1.4.1.318.1.1.9.4.4.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of DC powerplant LVDs accessible by this IP address. | |||||||||||||||||||||
| Tdcmim2StatusLVDTable | 1.3.6.1.4.1.318.1.1.9.4.4.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for accessing the LVDs. The number of entries is contained in the dcmim2StatusLVDTableSize OID. | |||||||||||||||||||||
| Rdcmim2StatusLVDEntry | 1.3.6.1.4.1.318.1.1.9.4.4.2.1 | NA | mandatory | ||||||||||||||||||
| Cdcmim2StatusLVDIndex | 1.3.6.1.4.1.318.1.1.9.4.4.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the DC powerplant LVD. | |||||||||||||||||||||
| Cdcmim2StatusLVDState | 1.3.6.1.4.1.318.1.1.9.4.4.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this OID will return statusClosed (1) if the LVD is closed. statusOpened (2) will be returned if the LVD is opened.
| |||||||||||||||||||||
| Ndcmim2StatusAlarms | 1.3.6.1.4.1.318.1.1.9.4.5 | ||||||||||||||||||||
| Sdcmim2StatusAlarmsTableSize | 1.3.6.1.4.1.318.1.1.9.4.5.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of DC powerplant alarms viewable by this IP address. | |||||||||||||||||||||
| Tdcmim2StatusAlarmsTable | 1.3.6.1.4.1.318.1.1.9.4.5.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for accessing system alarms. The number of entries is contained in the dcmim2StatusAlarmsTableSize OID. | |||||||||||||||||||||
| Rdcmim2StatusAlarmsEntry | 1.3.6.1.4.1.318.1.1.9.4.5.2.1 | NA | mandatory | ||||||||||||||||||
| Cdcmim2StatusAlarmsIndex | 1.3.6.1.4.1.318.1.1.9.4.5.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of the system alarm. | |||||||||||||||||||||
| Cdcmim2StatusAlarmsText | 1.3.6.1.4.1.318.1.1.9.4.5.2.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The 16 character text describing the active alarm condition. | |||||||||||||||||||||
| NenvironmentalMonitor | 1.3.6.1.4.1.318.1.1.10 | ||||||||||||||||||||
| Nexternal | 1.3.6.1.4.1.318.1.1.10.1 | ||||||||||||||||||||
| NemIdent | 1.3.6.1.4.1.318.1.1.10.1.1 | ||||||||||||||||||||
| SemIdentFirmwareRevision | 1.3.6.1.4.1.318.1.1.10.1.1.1 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The firmware revision of the Environmental Monitor. | |||||||||||||||||||||
| NemConfig | 1.3.6.1.4.1.318.1.1.10.1.2 | ||||||||||||||||||||
| SemConfigProbesNumProbes | 1.3.6.1.4.1.318.1.1.10.1.2.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of temperature and humidity probes available. | |||||||||||||||||||||
| TemConfigProbesTable | 1.3.6.1.4.1.318.1.1.10.1.2.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of probes supported by the Environmental Monitor and their configurations. | |||||||||||||||||||||
| RemConfigProbesEntry | 1.3.6.1.4.1.318.1.1.10.1.2.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The Environmental Monitor probe configurations.
| |||||||||||||||||||||
| CemConfigProbeNumber | 1.3.6.1.4.1.318.1.1.10.1.2.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index into an Environmental Monitor probe entry. | |||||||||||||||||||||
| CemConfigProbeName | 1.3.6.1.4.1.318.1.1.10.1.2.2.1.2 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory A descriptive name of the probe set by the user, possibly denoting its location or purpose. | |||||||||||||||||||||
| CemConfigProbeHighTempThreshold | 1.3.6.1.4.1.318.1.1.10.1.2.2.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The high temperature alarm threshold for the probe. Units are displayed in the scale selected in the 'emConfigProbeTempUnits' OID (Celsius or Fahrenheit). | |||||||||||||||||||||
| CemConfigProbeLowTempThreshold | 1.3.6.1.4.1.318.1.1.10.1.2.2.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The low temperature alarm threshold for the probe. Units are displayed in the scale selected in the 'emConfigProbeTempUnits' OID (Celsius or Fahrenheit). | |||||||||||||||||||||
| CemConfigProbeTempUnits | 1.3.6.1.4.1.318.1.1.10.1.2.2.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The temperature scale used to display the temperature thresholds of the probe, Celsius(1) or Fahrenheit(2). This setting is based on the system preferences configuration in the agent.
| |||||||||||||||||||||
| CemConfigProbeHighHumidThreshold | 1.3.6.1.4.1.318.1.1.10.1.2.2.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The high humidity alarm threshold for the probe in percent relative humidity. | |||||||||||||||||||||
| CemConfigProbeLowHumidThreshold | 1.3.6.1.4.1.318.1.1.10.1.2.2.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The low humidity alarm threshold for the probe in percent relative humidity. | |||||||||||||||||||||
| CemConfigProbeHighTempEnable | 1.3.6.1.4.1.318.1.1.10.1.2.2.1.8 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The high temperature alarm enable/disable for the probe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this value is set to enabled(2) and the threshold has been violated.
| |||||||||||||||||||||
| CemConfigProbeLowTempEnable | 1.3.6.1.4.1.318.1.1.10.1.2.2.1.9 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The low temperature alarm enable/disable for the probe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this value is set to enabled(2) and the threshold has been violated.
| |||||||||||||||||||||
| CemConfigProbeHighHumidEnable | 1.3.6.1.4.1.318.1.1.10.1.2.2.1.10 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The high humidity alarm enable/disable for the probe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this value is set to enabled(2) and the threshold has been violated.
| |||||||||||||||||||||
| CemConfigProbeLowHumidEnable | 1.3.6.1.4.1.318.1.1.10.1.2.2.1.11 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The low humidity alarm enable/disable for the probe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this value is set to enabled(2) and the threshold has been violated.
| |||||||||||||||||||||
| CemConfigProbeMaxTempThreshold | 1.3.6.1.4.1.318.1.1.10.1.2.2.1.12 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The maximum temperature alarm threshold for the probe. Units are displayed in the scale selected in the 'emConfigProbeTempUnits' OID (Celsius or Fahrenheit). | |||||||||||||||||||||
| CemConfigProbeMinTempThreshold | 1.3.6.1.4.1.318.1.1.10.1.2.2.1.13 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The minimum temperature alarm threshold for the probe. Units are displayed in the scale selected in the 'emConfigProbeTempUnits' OID (Celsius or Fahrenheit). | |||||||||||||||||||||
| CemConfigProbeMaxHumidThreshold | 1.3.6.1.4.1.318.1.1.10.1.2.2.1.14 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The maximun humidity alarm threshold for the probe in percent relative humidity. | |||||||||||||||||||||
| CemConfigProbeMinHumidThreshold | 1.3.6.1.4.1.318.1.1.10.1.2.2.1.15 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The minimum humidity alarm threshold for the probe in percent relative humidity. | |||||||||||||||||||||
| CemConfigProbeMaxTempEnable | 1.3.6.1.4.1.318.1.1.10.1.2.2.1.16 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The maximum temperature alarm enable/disable for the probe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this value is set to enabled(2) and the threshold has been violated.
| |||||||||||||||||||||
| CemConfigProbeMinTempEnable | 1.3.6.1.4.1.318.1.1.10.1.2.2.1.17 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The minimum temperature alarm enable/disable for the probe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this value is set to enabled(2) and the threshold has been violated.
| |||||||||||||||||||||
| CemConfigProbeMaxHumidEnable | 1.3.6.1.4.1.318.1.1.10.1.2.2.1.18 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The maximum humidity alarm enable/disable for the probe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this value is set to enabled(2) and the threshold has been violated.
| |||||||||||||||||||||
| CemConfigProbeMinHumidEnable | 1.3.6.1.4.1.318.1.1.10.1.2.2.1.19 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The minimum humidity alarm enable/disable for the probe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this value is set to enabled(2) and the threshold has been violated.
| |||||||||||||||||||||
| CemConfigProbeTempHysteresis | 1.3.6.1.4.1.318.1.1.10.1.2.2.1.20 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The number of degrees beyond the temperature thresholds at which an active temperature alarm will be cleared. This configuration setting applies to all temperature thresholds. Units are displayed in the scale selected in the 'emConfigProbeTempUnits' OID (Celsius or Fahrenheit). | |||||||||||||||||||||
| CemConfigProbeHumidHysteresis | 1.3.6.1.4.1.318.1.1.10.1.2.2.1.21 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The number of percent RH points beyond the humidity thresholds at which an active humidity alarm will be cleared. This configuration setting applies to all humidity thresholds. Units are displayed in the scale selected in the 'emConfigProbeTempUnits' OID (Celsius or Fahrenheit). | |||||||||||||||||||||
| CemConfigProbeLocation | 1.3.6.1.4.1.318.1.1.10.1.2.2.1.22 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory A string describing the location of the probe. | |||||||||||||||||||||
| SemConfigContactsNumContacts | 1.3.6.1.4.1.318.1.1.10.1.2.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of contacts supported by the Environmental Monitor. | |||||||||||||||||||||
| TemConfigContactsTable | 1.3.6.1.4.1.318.1.1.10.1.2.4 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of contacts supported by the Environmental Monitor and their configurations. | |||||||||||||||||||||
| RemConfigContactsEntry | 1.3.6.1.4.1.318.1.1.10.1.2.4.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The Environmental Monitor contact configurations. | |||||||||||||||||||||
| CemConfigContactNumber | 1.3.6.1.4.1.318.1.1.10.1.2.4.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of an Environmental Monitor contact. | |||||||||||||||||||||
| CemConfigContactName | 1.3.6.1.4.1.318.1.1.10.1.2.4.1.2 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory A descriptive name for an Environmental Monitor contact set by the user, possibly denoting its location or purpose. | |||||||||||||||||||||
| CemConfigContactEnable | 1.3.6.1.4.1.318.1.1.10.1.2.4.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory An Environmental Monitor contact alarm enable/disable. No alarm will be generated if the contact is disabled(1). An alarm will be generated if the contact is enabled(2) and the contact has been faulted.
| |||||||||||||||||||||
| CemConfigContactSeverity | 1.3.6.1.4.1.318.1.1.10.1.2.4.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The severity of the alarm that will be triggered when the input contact is activated. The alarms can be critical(1), warning(2) or informational(3).
| |||||||||||||||||||||
| CemConfigContactNormalState | 1.3.6.1.4.1.318.1.1.10.1.2.4.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The contact state that will be considered normal, i.e. will not trigger an alarm. The states are open(1) or closed(2).
| |||||||||||||||||||||
| CemConfigContactLocation | 1.3.6.1.4.1.318.1.1.10.1.2.4.1.6 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory A descriptive label for the contact denoting its location or purpose. | |||||||||||||||||||||
| NemStatus | 1.3.6.1.4.1.318.1.1.10.1.3 | ||||||||||||||||||||
| SemStatusCommStatus | 1.3.6.1.4.1.318.1.1.10.1.3.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The communication status between the agent and the Environmental Monitor. noComm(1), Communication has never been established. comm(2), Communication has been established. commLost(3), Communication was established, but was lost.
| |||||||||||||||||||||
| SemStatusProbesNumProbes | 1.3.6.1.4.1.318.1.1.10.1.3.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of available probes on the Environmental Monitor. | |||||||||||||||||||||
| TemStatusProbesTable | 1.3.6.1.4.1.318.1.1.10.1.3.3 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of probes supported by the Environmental Monitor and their status. | |||||||||||||||||||||
| RemStatusProbesEntry | 1.3.6.1.4.1.318.1.1.10.1.3.3.1 | NA | mandatory | ||||||||||||||||||
| CemStatusProbeNumber | 1.3.6.1.4.1.318.1.1.10.1.3.3.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of the probe. | |||||||||||||||||||||
| CemStatusProbeName | 1.3.6.1.4.1.318.1.1.10.1.3.3.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory A descriptive name for the probe set by the user, possibly denoting its location or purpose. | |||||||||||||||||||||
| CemStatusProbeStatus | 1.3.6.1.4.1.318.1.1.10.1.3.3.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The connected status of the probe, either disconnected(1) or connected(2).
| |||||||||||||||||||||
| CemStatusProbeCurrentTemp | 1.3.6.1.4.1.318.1.1.10.1.3.3.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The current temperature reading from the probe displayed in the units shown in the 'emStatusProbeTempUnits' OID (Celsius or Fahrenheit). | |||||||||||||||||||||
| CemStatusProbeTempUnits | 1.3.6.1.4.1.318.1.1.10.1.3.3.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The temperature scale used to display the temperature thresholds of the probe, Celsius(1) or Fahrenheit(2). This setting is based on the system preferences configuration in the agent.
| |||||||||||||||||||||
| CemStatusProbeCurrentHumid | 1.3.6.1.4.1.318.1.1.10.1.3.3.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The current humidity reading from the probe in percent relative humidity. | |||||||||||||||||||||
| CemStatusProbeHighTempViolation | 1.3.6.1.4.1.318.1.1.10.1.3.3.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The high temperature violation status of the probe temperature reading. This OID will show a highTempViolation(2) if the current temperature reading shown in the 'emStatusProbeCurrentTemp' OID is greater than or equal to the high temperature threshold value, the 'emConfigProbeHighTempThreshold' OID, and the value of the 'emConfigProbeHighTempEnable' OID is enabled. Otherwise it will show noViolation(1). If the 'emConfigProbeHighTempEnable' OID is disabled, this OID will show disabled(3).
| |||||||||||||||||||||
| CemStatusProbeLowTempViolation | 1.3.6.1.4.1.318.1.1.10.1.3.3.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The high temperature violation status of the probe temperature reading. This OID will show a lowTempViolation(2) if the current temperature reading shown in the 'emStatusProbeCurrentTemp' OID is less than or equal to the low temperature threshold value, the 'emConfigProbeLowTempThreshold' OID, and the value of the 'emConfigProbeLowTempEnable' OID is enabled. Otherwise it will show noViolation(1). If the 'emConfigProbeLowTempEnable' OID is disabled, this OID will show disabled(3).
| |||||||||||||||||||||
| CemStatusProbeHighHumidViolation | 1.3.6.1.4.1.318.1.1.10.1.3.3.1.9 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The high humidity violation status of the probe humidity reading. This OID will show a highTempViolation(2) if the current humidity reading shown in the 'emStatusProbeCurrentHumid' OID is greater than or equal to the high humidity threshold value, the 'emConfigProbeHighHumidThreshold' OID, and the value of the 'emConfigProbeHighHumidEnable' OID is enabled. Otherwise it will show noViolation(1). If the 'emConfigProbeHighHumidEnable' OID is disabled, this OID will show disabled(3)
| |||||||||||||||||||||
| CemStatusProbeLowHumidViolation | 1.3.6.1.4.1.318.1.1.10.1.3.3.1.10 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The low humidity violation status of the probe humidity reading. This OID will show a lowTempViolation(2) if the current humidity reading shown in the 'emStatusProbeCurrentHumid' OID is less than or equal to the low humidity threshold value, the 'emConfigProbeLowHumidThreshold' OID, and the value of the 'emConfigProbeLowHumidEnable' OID is enabled. Otherwise it will show noViolation(1). If the 'emConfigProbeLowHumidEnable' OID is disabled, this OID will show disabled(3).
| |||||||||||||||||||||
| CemStatusProbeMaxTempViolation | 1.3.6.1.4.1.318.1.1.10.1.3.3.1.11 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The max temperature violation status of the probe temperature reading. This OID will show a maxTempViolation(2) if the current temperature reading shown in the 'emStatusProbeCurrentTemp' OID is greater than or equal to the maximun temperature threshold value, the 'emConfigProbeMaxTempThreshold' OID, and the value of the 'emConfigProbeMaxTempEnable' OID is enabled. Otherwise it will show noViolation(1). If the 'emConfigProbeMaxTempEnable' OID is disabled, this OID will show disabled(3).
| |||||||||||||||||||||
| CemStatusProbeMinTempViolation | 1.3.6.1.4.1.318.1.1.10.1.3.3.1.12 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The minimum temperature violation status of the probe temperature reading. This OID will show a minTempViolation(2) if the current temperature reading shown in the 'emStatusProbeCurrentTemp' OID is less than or equal to the minimum temperature threshold value, the 'emConfigProbeMinTempThreshold' OID, and the value of the 'emConfigProbeMinTempEnable' OID is enabled. Otherwise it will show noViolation(1). If the 'emConfigProbeMinTempEnable' OID is disabled, this OID will show disabled(3).
| |||||||||||||||||||||
| CemStatusProbeMaxHumidViolation | 1.3.6.1.4.1.318.1.1.10.1.3.3.1.13 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The maximum humidity violation status of the probe humidity reading. This OID will show a maxTempViolation(2) if the current humidity reading shown in the 'emStatusProbeCurrentHumid' OID is greater than or equal to the maximum humidity threshold value, the 'emConfigProbeMaxHumidThreshold' OID, and the value of the 'emConfigProbeMaxHumidEnable' OID is enabled. Otherwise it will show noViolation(1). If the 'emConfigProbeMaxHumidEnable' OID is disabled, this OID will show disabled(3)
| |||||||||||||||||||||
| CemStatusProbeMinHumidViolation | 1.3.6.1.4.1.318.1.1.10.1.3.3.1.14 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The minimum humidity violation status of the probe humidity reading. This OID will show a minTempViolation(2) if the current humidity reading shown in the 'emStatusProbeCurrentHumid' OID is less than or equal to the minimum humidity threshold value, the 'emConfigProbeMinHumidThreshold' OID, and the value of the 'emConfigProbeMinHumidEnable' OID is enabled. Otherwise it will show noViolation(1). If the 'emConfigProbeMinHumidEnable' OID is disabled, this OID will show disabled(3).
| |||||||||||||||||||||
| SemStatusContactsNumContacts | 1.3.6.1.4.1.318.1.1.10.1.3.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of contacts supported by the Environmental Monitor. | |||||||||||||||||||||
| TemStatusContactsTable | 1.3.6.1.4.1.318.1.1.10.1.3.5 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of contacts supported by the Environmental Monitor and their status. | |||||||||||||||||||||
| RemStatusContactsEntry | 1.3.6.1.4.1.318.1.1.10.1.3.5.1 | NA | mandatory | ||||||||||||||||||
| CemStatusContactNumber | 1.3.6.1.4.1.318.1.1.10.1.3.5.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of the Environmental Monitor contact. | |||||||||||||||||||||
| CemStatusContactName | 1.3.6.1.4.1.318.1.1.10.1.3.5.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory A descriptive name for the Environmental Monitor contact set by the user, possibly denoting its location or purpose. | |||||||||||||||||||||
| CemStatusContactStatus | 1.3.6.1.4.1.318.1.1.10.1.3.5.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The status of the Environmental Monitor contact. The status will show noFault(1) if the contact is in the normal state and the 'emConfigContactEnable' OID is enabled. The status will show a fault(2) if the contact is faulted and the 'emContactEnable' OID is enabled. If the 'emConfigContactEnable' OID is disabled, the status will show disabled(3).
| |||||||||||||||||||||
| Nintegrated | 1.3.6.1.4.1.318.1.1.10.2 | ||||||||||||||||||||
| NiemIdent | 1.3.6.1.4.1.318.1.1.10.2.1 | ||||||||||||||||||||
| SiemIdentHardwareRevision | 1.3.6.1.4.1.318.1.1.10.2.1.1 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The hardware revision of the Integrated Environmental Monitor. | |||||||||||||||||||||
| NiemConfig | 1.3.6.1.4.1.318.1.1.10.2.2 | ||||||||||||||||||||
| SiemConfigProbesNumProbes | 1.3.6.1.4.1.318.1.1.10.2.2.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of temperature and humidity probes available. | |||||||||||||||||||||
| TiemConfigProbesTable | 1.3.6.1.4.1.318.1.1.10.2.2.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of probes supported by the Environmental Monitor and their configurations. | |||||||||||||||||||||
| RiemConfigProbesEntry | 1.3.6.1.4.1.318.1.1.10.2.2.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The Environmental Monitor probe configurations.
| |||||||||||||||||||||
| CiemConfigProbeNumber | 1.3.6.1.4.1.318.1.1.10.2.2.2.1.1 | INTEGER | RO | mandatory | 1 | ||||||||||||||||
column · INTEGER · read-only · mandatory The index to a Environmental Monitor probe entry. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CiemConfigProbeName | 1.3.6.1.4.1.318.1.1.10.2.2.2.1.2 | DisplayString | RW | mandatory | Port 1 Temp 1 | ||||||||||||||||
column · DisplayString · read-write · mandatory A descriptive name for the probe set by the user, possibly denoting its location or purpose. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CiemConfigProbeHighTempThreshold | 1.3.6.1.4.1.318.1.1.10.2.2.2.1.3 | INTEGER | RW | mandatory | 40 | ||||||||||||||||
column · INTEGER · read-write · mandatory The high temperature alarm threshold for the probe. Units are displayed in the scale selected in the 'iemConfigProbeTempUnits' OID (Celsius or Fahrenheit). Example values from LibreNMS test devices
| |||||||||||||||||||||
| CiemConfigProbeLowTempThreshold | 1.3.6.1.4.1.318.1.1.10.2.2.2.1.4 | INTEGER | RW | mandatory | 10 | ||||||||||||||||
column · INTEGER · read-write · mandatory The low temperature alarm threshold for the probe. Units are displayed in the scale selected in the 'iemConfigProbeTempUnits' OID (Celsius or Fahrenheit). Example values from LibreNMS test devices
| |||||||||||||||||||||
| CiemConfigProbeTempUnits | 1.3.6.1.4.1.318.1.1.10.2.2.2.1.5 | INTEGER | RO | mandatory | celsius(1) | ||||||||||||||||
column · INTEGER · read-only · mandatory The temperature scale used to display the temperature thresholds of the probe, Celsius(1) or Fahrenheit(2). This setting is based on the system preferences configuration in the agent.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CiemConfigProbeHighHumidThreshold | 1.3.6.1.4.1.318.1.1.10.2.2.2.1.6 | INTEGER | RW | mandatory | -1 | ||||||||||||||||
column · INTEGER · read-write · mandatory The high humidity alarm threshold for the probe in percent relative humidity. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CiemConfigProbeLowHumidThreshold | 1.3.6.1.4.1.318.1.1.10.2.2.2.1.7 | INTEGER | RW | mandatory | -1 | ||||||||||||||||
column · INTEGER · read-write · mandatory The low humidity alarm threshold for the probe in percent relative humidity. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CiemConfigProbeHighTempEnable | 1.3.6.1.4.1.318.1.1.10.2.2.2.1.8 | INTEGER | RW | mandatory | disabled(1) | ||||||||||||||||
column · INTEGER · read-write · mandatory The high temperature alarm enable/disable for the probe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this value is set to enabled(2) and the threshold has been violated.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CiemConfigProbeLowTempEnable | 1.3.6.1.4.1.318.1.1.10.2.2.2.1.9 | INTEGER | RW | mandatory | disabled(1) | ||||||||||||||||
column · INTEGER · read-write · mandatory The low temperature alarm enable/disable for the probe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this value is set to enabled(2) and the threshold has been violated.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CiemConfigProbeHighHumidEnable | 1.3.6.1.4.1.318.1.1.10.2.2.2.1.10 | INTEGER | RW | mandatory | disabled(1) | ||||||||||||||||
column · INTEGER · read-write · mandatory The high humidity alarm enable/disable for the probe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this value is set to enabled(2) and the threshold has been violated.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CiemConfigProbeLowHumidEnable | 1.3.6.1.4.1.318.1.1.10.2.2.2.1.11 | INTEGER | RW | mandatory | disabled(1) | ||||||||||||||||
column · INTEGER · read-write · mandatory The low humidity alarm enable/disable for the probe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this value is set to enabled(2) and the threshold has been violated.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CiemConfigProbeMaxTempThreshold | 1.3.6.1.4.1.318.1.1.10.2.2.2.1.12 | INTEGER | RW | mandatory | 60 | ||||||||||||||||
column · INTEGER · read-write · mandatory The maximun temperature alarm threshold for the probe. Units are displayed in the scale selected in the 'iemConfigProbeTempUnits' OID (Celsius or Fahrenheit). Example values from LibreNMS test devices
| |||||||||||||||||||||
| CiemConfigProbeMinTempThreshold | 1.3.6.1.4.1.318.1.1.10.2.2.2.1.13 | INTEGER | RW | mandatory | 0 | ||||||||||||||||
column · INTEGER · read-write · mandatory The minimun temperature alarm threshold for the probe. Units are displayed in the scale selected in the 'iemConfigProbeTempUnits' OID (Celsius or Fahrenheit). Example values from LibreNMS test devices
| |||||||||||||||||||||
| CiemConfigProbeMaxHumidThreshold | 1.3.6.1.4.1.318.1.1.10.2.2.2.1.14 | INTEGER | RW | mandatory | -1 | ||||||||||||||||
column · INTEGER · read-write · mandatory The maximum humidity alarm threshold for the probe in percent relative humidity. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CiemConfigProbeMinHumidThreshold | 1.3.6.1.4.1.318.1.1.10.2.2.2.1.15 | INTEGER | RW | mandatory | -1 | ||||||||||||||||
column · INTEGER · read-write · mandatory The minimum humidity alarm threshold for the probe in percent relative humidity. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CiemConfigProbeMaxTempEnable | 1.3.6.1.4.1.318.1.1.10.2.2.2.1.16 | INTEGER | RW | mandatory | disabled(1) | ||||||||||||||||
column · INTEGER · read-write · mandatory The maximum temperature alarm enable/disable for the probe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this value is set to enabled(2) and the threshold has been violated.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CiemConfigProbeMinTempEnable | 1.3.6.1.4.1.318.1.1.10.2.2.2.1.17 | INTEGER | RW | mandatory | disabled(1) | ||||||||||||||||
column · INTEGER · read-write · mandatory The low temperature alarm enable/disable for the probe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this value is set to enabled(2) and the threshold has been violated.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CiemConfigProbeMaxHumidEnable | 1.3.6.1.4.1.318.1.1.10.2.2.2.1.18 | INTEGER | RW | mandatory | disabled(1) | ||||||||||||||||
column · INTEGER · read-write · mandatory The maximum humidity alarm enable/disable for the probe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this value is set to enabled(2) and the threshold has been violated.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CiemConfigProbeMinHumidEnable | 1.3.6.1.4.1.318.1.1.10.2.2.2.1.19 | INTEGER | RW | mandatory | disabled(1) | ||||||||||||||||
column · INTEGER · read-write · mandatory The minimum humidity alarm enable/disable for the probe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this value is set to enabled(2) and the threshold has been violated.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CiemConfigProbeTempHysteresis | 1.3.6.1.4.1.318.1.1.10.2.2.2.1.20 | INTEGER | RW | mandatory | 0 | ||||||||||||||||
column · INTEGER · read-write · mandatory The number of degrees beyond the temperature thresholds at which an active temperature alarm will be cleared. This configuration setting applies to all temperature thresholds. Units are displayed in the scale selected in the 'emConfigProbeTempUnits' OID (Celsius or Fahrenheit). Example values from LibreNMS test devices
| |||||||||||||||||||||
| CiemConfigProbeHumidHysteresis | 1.3.6.1.4.1.318.1.1.10.2.2.2.1.21 | INTEGER | RW | mandatory | -1 | ||||||||||||||||
column · INTEGER · read-write · mandatory The number of percent RH points beyond the humidity thresholds at which an active humidity alarm will be cleared. This configuration setting applies to all humidity thresholds. Units are displayed in the scale selected in the 'emConfigProbeTempUnits' OID (Celsius or Fahrenheit). Example values from LibreNMS test devices
| |||||||||||||||||||||
| CiemConfigProbeLocation | 1.3.6.1.4.1.318.1.1.10.2.2.2.1.22 | DisplayString | RW | mandatory | Port 1 | ||||||||||||||||
column · DisplayString · read-write · mandatory A string describing the location of the probe. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SiemConfigContactsNumContacts | 1.3.6.1.4.1.318.1.1.10.2.2.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of contacts available on the Environmental Monitor. | |||||||||||||||||||||
| TiemConfigContactsTable | 1.3.6.1.4.1.318.1.1.10.2.2.4 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of contacts supported by the Environmental Monitor and their configurations. | |||||||||||||||||||||
| RiemConfigContactsEntry | 1.3.6.1.4.1.318.1.1.10.2.2.4.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The Environmental Monitor contact configurations. | |||||||||||||||||||||
| CiemConfigContactNumber | 1.3.6.1.4.1.318.1.1.10.2.2.4.1.1 | INTEGER | RO | mandatory | 1 | ||||||||||||||||
column · INTEGER · read-only · mandatory The index of an Environmental Monitor contact. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CiemConfigContactName | 1.3.6.1.4.1.318.1.1.10.2.2.4.1.2 | DisplayString | RW | mandatory | Unknown | ||||||||||||||||
column · DisplayString · read-write · mandatory A descriptive name for the Environmental Monitor contact set by the user, possibly denoting its location or purpose. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CiemConfigContactEnable | 1.3.6.1.4.1.318.1.1.10.2.2.4.1.3 | INTEGER | RW | mandatory | disabled(1) | ||||||||||||||||
column · INTEGER · read-write · mandatory An Environmental Monitor contact alarm enable/disable.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CiemConfigContactSeverity | 1.3.6.1.4.1.318.1.1.10.2.2.4.1.4 | INTEGER | RW | mandatory | critical(1) | ||||||||||||||||
column · INTEGER · read-write · mandatory The severtity of the alarm that will be triggered when the input contact is activated. The alarms can be critical(1), warning(2) or informational(3). NOTE: informational(3) is deprecated (and no longer valid) for this OID.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CiemConfigContactNormalState | 1.3.6.1.4.1.318.1.1.10.2.2.4.1.5 | INTEGER | RW | mandatory | open(1) | ||||||||||||||||
column · INTEGER · read-write · mandatory The contact state that will be considered normal, i.e. will not trigger an alarm. The states are open(1) or closed(2).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CiemConfigContactLocation | 1.3.6.1.4.1.318.1.1.10.2.2.4.1.6 | DisplayString | RW | mandatory | Unknown | ||||||||||||||||
column · DisplayString · read-write · mandatory A descriptive label for the contact denoting its location or purpose. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SiemConfigConfigRelaysNumRelays | 1.3.6.1.4.1.318.1.1.10.2.2.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of output relays supported by the Environmental Monitor. | |||||||||||||||||||||
| TiemConfigRelaysTable | 1.3.6.1.4.1.318.1.1.10.2.2.6 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of output relays supported by the Environmental Monitor and their configurations. | |||||||||||||||||||||
| RiemConfigRelaysEntry | 1.3.6.1.4.1.318.1.1.10.2.2.6.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The Environmental Monitor output relay configurations.
| |||||||||||||||||||||
| CiemConfigRelayNumber | 1.3.6.1.4.1.318.1.1.10.2.2.6.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of an Environmental Monitor output relay. | |||||||||||||||||||||
| CiemConfigRelayName | 1.3.6.1.4.1.318.1.1.10.2.2.6.1.2 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory A descriptive name of an Environmental Monitor output relay, set by the user, describing its location or purpose. | |||||||||||||||||||||
| CiemConfigRelayNormalState | 1.3.6.1.4.1.318.1.1.10.2.2.6.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The normal state (non-fault state) of an Environmental Monitor output relay, either open(1) or closed(2).
| |||||||||||||||||||||
| CiemConfigRelayFaultCondition | 1.3.6.1.4.1.318.1.1.10.2.2.6.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The fault condition used to activate the output relay. | |||||||||||||||||||||
| NiemStatus | 1.3.6.1.4.1.318.1.1.10.2.3 | ||||||||||||||||||||
| SiemStatusProbesNumProbes | 1.3.6.1.4.1.318.1.1.10.2.3.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of available probes on the Environmental Monitor. | |||||||||||||||||||||
| TiemStatusProbesTable | 1.3.6.1.4.1.318.1.1.10.2.3.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of probes supported by the Environmental Monitor and their status. | |||||||||||||||||||||
| RiemStatusProbesEntry | 1.3.6.1.4.1.318.1.1.10.2.3.2.1 | NA | mandatory | ||||||||||||||||||
| CiemStatusProbeNumber | 1.3.6.1.4.1.318.1.1.10.2.3.2.1.1 | INTEGER | RO | mandatory | 1 | ||||||||||||||||
column · INTEGER · read-only · mandatory The index of the probe. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CiemStatusProbeName | 1.3.6.1.4.1.318.1.1.10.2.3.2.1.2 | DisplayString | RO | mandatory | Port 1 Temp 1 | ||||||||||||||||
column · DisplayString · read-only · mandatory A descriptive name for the probe set by the user. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CiemStatusProbeStatus | 1.3.6.1.4.1.318.1.1.10.2.3.2.1.3 | INTEGER | RO | mandatory | connected(2) | ||||||||||||||||
column · INTEGER · read-only · mandatory The connected status of the probe, either disconnected(1) or connected(2).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CiemStatusProbeCurrentTemp | 1.3.6.1.4.1.318.1.1.10.2.3.2.1.4 | INTEGER | RO | mandatory | 23 | ||||||||||||||||
column · INTEGER · read-only · mandatory The current temperature reading from the probe displayed in the units shown in the 'iemStatusProbeTempUnits' OID (Celsius or Fahrenheit). Example values from LibreNMS test devices
| |||||||||||||||||||||
| CiemStatusProbeTempUnits | 1.3.6.1.4.1.318.1.1.10.2.3.2.1.5 | INTEGER | RO | mandatory | celsius(1) | ||||||||||||||||
column · INTEGER · read-only · mandatory The temperature scale used to display the temperature thresholds of the probe, Celsius(1) or Fahrenheit(2). This setting is based on the system preferences configuration in the agent.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CiemStatusProbeCurrentHumid | 1.3.6.1.4.1.318.1.1.10.2.3.2.1.6 | INTEGER | RO | mandatory | 0 | ||||||||||||||||
column · INTEGER · read-only · mandatory The current humidity reading from the probe in percent relative humidity. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CiemStatusProbeHighTempViolation | 1.3.6.1.4.1.318.1.1.10.2.3.2.1.7 | INTEGER | RO | mandatory | disabled(3) | ||||||||||||||||
column · INTEGER · read-only · mandatory The high temperature violation status of the probe temperature reading. This OID will show a highTempViolation(2) if the current temperature reading shown in the 'iemStatusProbeCurrentTemp' OID is greater than or equal to the high temperature threshold value, the 'iemConfigProbeHighTempThreshold' OID, and the value of the 'iemConfigProbeHighTempEnable' OID is enabled. Otherwise it will show noViolation(1). If the 'iemConfigProbeHighTempEnable' OID is disabled, this OID will show disabled(3).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CiemStatusProbeLowTempViolation | 1.3.6.1.4.1.318.1.1.10.2.3.2.1.8 | INTEGER | RO | mandatory | disabled(3) | ||||||||||||||||
column · INTEGER · read-only · mandatory The high temperature violation status of the probe temperature reading. This OID will show a lowTempViolation(2) if the current temperature reading shown in the 'iemStatusProbeCurrentTemp' OID is less than or equal to the low temperature threshold value, the 'iemConfigProbeLowTempThreshold' OID, and the value of the 'iemPConfigrobeLowTempEnable' OID is enabled. Otherwise it will show noViolation(1). If the 'iemConfigProbeLowTempEnable' OID is disabled, this OID will show disabled(3).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CiemStatusProbeHighHumidViolation | 1.3.6.1.4.1.318.1.1.10.2.3.2.1.9 | INTEGER | RO | mandatory | noViolation(1) | ||||||||||||||||
column · INTEGER · read-only · mandatory The high humidity violation status of the probe humidity reading. This OID will show a highTempViolation(2) if the current humidity reading shown in the 'iemStatusProbeCurrentHumid' OID is greater than or equal to the high humidity threshold value, the 'iemConfigProbeHighHumidThreshold' OID, and the value of the 'iemConfigProbeHighHumidEnable' OID is enabled. Otherwise it will show noViolation(1). If the 'iemConfigProbeHighHumidEnable' OID is disabled, this OID will show disabled(3).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CiemStatusProbeLowHumidViolation | 1.3.6.1.4.1.318.1.1.10.2.3.2.1.10 | INTEGER | RO | mandatory | noViolation(1) | ||||||||||||||||
column · INTEGER · read-only · mandatory The low humidity violation status of the probe humidity reading. This OID will show a lowTempViolation(2) if the current humidity reading shown in the 'iemStatusProbeCurrentHumid' OID is less than or equal to the low humidity threshold value, the 'iemConfigProbeLowHumidThreshold' OID, and the value of the 'iemConfigProbeLowHumidEnable' OID is enabled. Otherwise it will show noViolation(1). If the 'iemConfigProbeLowHumidEnable' OID is disabled, this OID will show disabled(3).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CiemStatusProbeMaxTempViolation | 1.3.6.1.4.1.318.1.1.10.2.3.2.1.11 | INTEGER | RO | mandatory | disabled(3) | ||||||||||||||||
column · INTEGER · read-only · mandatory The max temperature violation status of the probe temperature reading. This OID will show a maxTempViolation(2) if the current temperature reading shown in the 'iemStatusProbeCurrentTemp' OID is greater than or equal to the maximun temperature threshold value, the 'iemConfigProbeMaxTempThreshold' OID, and the value of the 'iemConfigProbeMaxTempEnable' OID is enabled. Otherwise it will show noViolation(1). If the 'iemConfigProbeMaxTempEnable' OID is disabled, this OID will show disabled(3).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CiemStatusProbeMinTempViolation | 1.3.6.1.4.1.318.1.1.10.2.3.2.1.12 | INTEGER | RO | mandatory | disabled(3) | ||||||||||||||||
column · INTEGER · read-only · mandatory The minimum temperature violation status of the probe temperature reading. This OID will show a minTempViolation(2) if the current temperature reading shown in the 'iemStatusProbeCurrentTemp' OID is less than or equal to the minimum temperature threshold value, the 'iemConfigProbeMinTempThreshold' OID, and the value of the 'iemConfigProbeMinTempEnable' OID is enabled. Otherwise it will show noViolation(1). If the 'iemConfigProbeMinTempEnable' OID is disabled, this OID will show disabled(3).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CiemStatusProbeMaxHumidViolation | 1.3.6.1.4.1.318.1.1.10.2.3.2.1.13 | INTEGER | RO | mandatory | noViolation(1) | ||||||||||||||||
column · INTEGER · read-only · mandatory The maximum humidity violation status of the probe humidity reading. This OID will show a maxTempViolation(2) if the current humidity reading shown in the 'iemStatusProbeCurrentHumid' OID is greater than or equal to the maximum humidity threshold value, the 'iemConfigProbeMaxHumidThreshold' OID, and the value of the 'iemConfigProbeMaxHumidEnable' OID is enabled. Otherwise it will show noViolation(1). If the 'iemConfigProbeMaxHumidEnable' OID is disabled, this OID will show disabled(3)
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CiemStatusProbeMinHumidViolation | 1.3.6.1.4.1.318.1.1.10.2.3.2.1.14 | INTEGER | RO | mandatory | noViolation(1) | ||||||||||||||||
column · INTEGER · read-only · mandatory The minimum humidity violation status of the probe humidity reading. This OID will show a minTempViolation(2) if the current humidity reading shown in the 'iemStatusProbeCurrentHumid' OID is less than or equal to the minimum humidity threshold value, the 'iemConfigProbeMinHumidThreshold' OID, and the value of the 'iemConfigProbeMinHumidEnable' OID is enabled. Otherwise it will show noViolation(1). If the 'iemConfigProbeMinHumidEnable' OID is disabled, this OID will show disabled(3).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CiemStatusProbeLocation | 1.3.6.1.4.1.318.1.1.10.2.3.2.1.15 | DisplayString | RO | mandatory | Port 1 | ||||||||||||||||
column · DisplayString · read-only · mandatory A descriptive location for the probe set by the user. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SiemStatusContactsNumContacts | 1.3.6.1.4.1.318.1.1.10.2.3.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of contacts supported on the Environmental Monitor. | |||||||||||||||||||||
| TiemStatusContactsTable | 1.3.6.1.4.1.318.1.1.10.2.3.4 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of contacts supported by the Environmental Monitor and their status. | |||||||||||||||||||||
| RiemStatusContactsEntry | 1.3.6.1.4.1.318.1.1.10.2.3.4.1 | NA | mandatory | ||||||||||||||||||
| CiemStatusContactNumber | 1.3.6.1.4.1.318.1.1.10.2.3.4.1.1 | INTEGER | RO | mandatory | 1 | ||||||||||||||||
column · INTEGER · read-only · mandatory The index of the Environmental Monitor contact. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CiemStatusContactName | 1.3.6.1.4.1.318.1.1.10.2.3.4.1.2 | DisplayString | RO | mandatory | Unknown | ||||||||||||||||
column · DisplayString · read-only · mandatory A descriptive name for the Environmental Monitor contact set by the user, denoting its location or purpose. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CiemStatusContactStatus | 1.3.6.1.4.1.318.1.1.10.2.3.4.1.3 | INTEGER | RO | mandatory | noFault(1) | ||||||||||||||||
column · INTEGER · read-only · mandatory The status of the Environmental Monitor contact. The status will show noFault(1) if the contact is in the normal state and the 'iemConfigContactEnable' OID is enabled. The status will show a fault(2) if the contact is faulted and the 'iemConfigContactEnable' OID is enabled. If the 'iemConfigContactEnable' OID is disabled, the status will show disabled(3).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SiemStatusRelaysNumRelays | 1.3.6.1.4.1.318.1.1.10.2.3.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of output relays supported on the Environmental Monitor. | |||||||||||||||||||||
| TiemStatusRelaysTable | 1.3.6.1.4.1.318.1.1.10.2.3.7 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of output relays supported by the Environmental Monitor and their status. | |||||||||||||||||||||
| RiemStatusRelaysEntry | 1.3.6.1.4.1.318.1.1.10.2.3.7.1 | NA | mandatory | ||||||||||||||||||
| CiemStatusRelayNumber | 1.3.6.1.4.1.318.1.1.10.2.3.7.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of the output relay. | |||||||||||||||||||||
| CiemStatusRelayName | 1.3.6.1.4.1.318.1.1.10.2.3.7.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory A descriptive name for the output relay set by the user, denoting its location or purpose. | |||||||||||||||||||||
| CiemStatusRelayStatus | 1.3.6.1.4.1.318.1.1.10.2.3.7.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The status of the output relay, either faultState(1) or normalState(2).
| |||||||||||||||||||||
| NenvMgtSystem | 1.3.6.1.4.1.318.1.1.10.3 | ||||||||||||||||||||
| NemsIdent | 1.3.6.1.4.1.318.1.1.10.3.1 | ||||||||||||||||||||
| SemsIdentEMSName | 1.3.6.1.4.1.318.1.1.10.3.1.1 | DisplayString | RO | mandatory | SCP-EMU | ||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the device. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SemsIdentProductNumber | 1.3.6.1.4.1.318.1.1.10.3.1.2 | DisplayString | RO | mandatory | AP9320 | ||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the model number of the device. This value is set at the factory. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SemsIdentFirmwareRev | 1.3.6.1.4.1.318.1.1.10.3.1.3 | DisplayString | RO | mandatory | v2.6.7 | ||||||||||||||||
scalar · DisplayString · read-only · mandatory The firmware revision of the device. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SemsIdentHardwareRev | 1.3.6.1.4.1.318.1.1.10.3.1.4 | DisplayString | RO | mandatory | 4 | ||||||||||||||||
scalar · DisplayString · read-only · mandatory The hardware revision of the device. This value is set at the factory. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SemsIdentDateOfManufacture | 1.3.6.1.4.1.318.1.1.10.3.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The date when the device was manufactured in mm/dd/yyyy format. This value is set at the factory. | |||||||||||||||||||||
| SemsIdentSerialNumber | 1.3.6.1.4.1.318.1.1.10.3.1.6 | DisplayString | RO | mandatory | ZA0604022112 | ||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the serial number of the device. This value is set at the factory. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NemsOutputRelayControl | 1.3.6.1.4.1.318.1.1.10.3.2 | ||||||||||||||||||||
| TemsOutputRelayControlTable | 1.3.6.1.4.1.318.1.1.10.3.2.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for control of individual output relays. The number of entries is contained in the emsStatusOutputRelayCount OID. | |||||||||||||||||||||
| RemsOutputRelayControlEntry | 1.3.6.1.4.1.318.1.1.10.3.2.1.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The output relays to control. | |||||||||||||||||||||
| CemsOutputRelayControlOutputRelayIndex | 1.3.6.1.4.1.318.1.1.10.3.2.1.1.1 | INTEGER | RO | mandatory | 1 | ||||||||||||||||
column · INTEGER · read-only · mandatory The index to the output relay entry. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CemsOutputRelayControlOutputRelayName | 1.3.6.1.4.1.318.1.1.10.3.2.1.1.2 | DisplayString | RO | mandatory | Relay | ||||||||||||||||
column · DisplayString · read-only · mandatory The name of the output relay. This OID is provided for informational purposes only. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CemsOutputRelayControlOutputRelayCommand | 1.3.6.1.4.1.318.1.1.10.3.2.1.1.3 | INTEGER | RW | mandatory | immediateOpenEMS(2) | ||||||||||||||||
column · INTEGER · read-write · mandatory Getting this variable will return the output relay state. If the output relay is closed, the immediateCloseEMS (1) value will be returned. If the output relay is open, the immediateOpenEMS (2) value will be returned. Setting this variable to immediateCloseEMS (1) will immediately close the relay. Setting this variable to immediateOpenEMS (2) will immediately open the relay.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NemsOutletControl | 1.3.6.1.4.1.318.1.1.10.3.3 | ||||||||||||||||||||
| TemsOutletControlTable | 1.3.6.1.4.1.318.1.1.10.3.3.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for control of individual outlet switches. The number of entries is contained in the emsStatusOutletCount OID. | |||||||||||||||||||||
| RemsOutletControlEntry | 1.3.6.1.4.1.318.1.1.10.3.3.1.1 | NA | mandatory | ||||||||||||||||||
| CemsOutletControlOutletIndex | 1.3.6.1.4.1.318.1.1.10.3.3.1.1.1 | INTEGER | RO | mandatory | 1 | ||||||||||||||||
column · INTEGER · read-only · mandatory The index to the outlet entry. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CemsOutletControlOutletName | 1.3.6.1.4.1.318.1.1.10.3.3.1.1.2 | DisplayString | RO | mandatory | Outlet | ||||||||||||||||
column · DisplayString · read-only · mandatory The name of the outlet. This OID is provided for informational purposes only. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CemsOutletControlOutletCommand | 1.3.6.1.4.1.318.1.1.10.3.3.1.1.3 | INTEGER | RW | mandatory | immediateOffEMS(2) | ||||||||||||||||
column · INTEGER · read-write · mandatory Getting this variable will return the outlet state. If the outlet is on, the immediateOnEMS (1) value will be returned. If the outlet is off, the immediateOffEMS (2) value will be returned. Setting this variable to immediateOnEMS (1) will immediately turn the outlet on. Setting this variable to immediateOffEMS (2) will immediately turn the outlet off.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NemsSensorControl | 1.3.6.1.4.1.318.1.1.10.3.4 | ||||||||||||||||||||
| TemsSensorControlTable | 1.3.6.1.4.1.318.1.1.10.3.4.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for control/reset of individual sensors. The number of entries is contained in the emsStatusSensorCount OID. | |||||||||||||||||||||
| RemsSensorControlEntry | 1.3.6.1.4.1.318.1.1.10.3.4.1.1 | NA | mandatory | ||||||||||||||||||
| CemsSensorControlSensorIndex | 1.3.6.1.4.1.318.1.1.10.3.4.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the sensor entry. | |||||||||||||||||||||
| CemsSensorControlSensorSystemName | 1.3.6.1.4.1.318.1.1.10.3.4.1.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The system name of the sensor. This describes the hardware system intent of this sensor. | |||||||||||||||||||||
| CemsSensorControlSensorUserName | 1.3.6.1.4.1.318.1.1.10.3.4.1.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The name of the sensor as given by the system user. | |||||||||||||||||||||
| CemsSensorControlSensorCommand | 1.3.6.1.4.1.318.1.1.10.3.4.1.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Getting this variable will return noCommandEMS(1). Setting this variable to resetCommandEMS(2) will issue a reset command to the sensor. Some sensors cannot be manually reset and will not be affected by this command.
| |||||||||||||||||||||
| NemsAlarmDeviceControl | 1.3.6.1.4.1.318.1.1.10.3.5 | ||||||||||||||||||||
| TemsAlarmDeviceControlTable | 1.3.6.1.4.1.318.1.1.10.3.5.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for control of individual alarm devices. Note: Some alarm devices are not controllable. The number of entries is contained in the emsStatusAlarmDeviceCount OID. | |||||||||||||||||||||
| RemsAlarmDeviceControlEntry | 1.3.6.1.4.1.318.1.1.10.3.5.1.1 | NA | mandatory | ||||||||||||||||||
| CemsAlarmDeviceControlDeviceIndex | 1.3.6.1.4.1.318.1.1.10.3.5.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the alarm device entry. | |||||||||||||||||||||
| CemsAlarmDeviceControlDeviceName | 1.3.6.1.4.1.318.1.1.10.3.5.1.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The name of the alarm device. This OID is provided for informational purposes only. | |||||||||||||||||||||
| CemsAlarmDeviceControlDeviceCommand | 1.3.6.1.4.1.318.1.1.10.3.5.1.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Getting this variable will return the device state. If the device is active, the alarmDeviceOnEMS (1) value will be returned. If the device is inactive, the alarmDeviceOffEMS (2) value will be returned. If the device is not installed, the alarmDeviceNotInstalledEMS (3) value will be returned. Actions resulting from setting this variable are device-dependent. Setting this variable to alarmDeviceOnEMS (1) will turn that device (ex. Beacon) on. Setting this variable to alarmDeviceOffEMS (2) will turn that device off.
| |||||||||||||||||||||
| NemsConfig | 1.3.6.1.4.1.318.1.1.10.3.6 | ||||||||||||||||||||
| SemsConfigName | 1.3.6.1.4.1.318.1.1.10.3.6.1 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory The name of the device. | |||||||||||||||||||||
| SemsConfigCheckLogLight | 1.3.6.1.4.1.318.1.1.10.3.6.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The setting of this OID determines the level of event that will trigger the check-log light on the EMS. This is not available on the EMU2. lightDisabled (1) disables the check-log light. lightOnInformational (2) lights check-log for any event of informational severity or above. lightOnWarning (3) lights check-log for any event of warning severity or above. lightOnSevere (4) lights check-log for any event of severe severity.
| |||||||||||||||||||||
| NemsProbeConfig | 1.3.6.1.4.1.318.1.1.10.3.7 | ||||||||||||||||||||
| TemsProbeConfigTable | 1.3.6.1.4.1.318.1.1.10.3.7.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for configuration of individual probes. The number of entries is contained in the emsStatusProbeCount OID. | |||||||||||||||||||||
| RemsProbeConfigEntry | 1.3.6.1.4.1.318.1.1.10.3.7.1.1 | NA | mandatory | ||||||||||||||||||
| CemsProbeConfigProbeIndex | 1.3.6.1.4.1.318.1.1.10.3.7.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the probe entry. | |||||||||||||||||||||
| CemsProbeConfigProbeName | 1.3.6.1.4.1.318.1.1.10.3.7.1.1.2 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The name of the probe. | |||||||||||||||||||||
| CemsProbeConfigProbeHighTempThresh | 1.3.6.1.4.1.318.1.1.10.3.7.1.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Probe high temperature threshold. Values are represented in whole number degrees. Units are displayed in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | |||||||||||||||||||||
| CemsProbeConfigProbeLowTempThresh | 1.3.6.1.4.1.318.1.1.10.3.7.1.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Probe low temperature threshold. Values are represented in whole number degrees. Units are displayed in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | |||||||||||||||||||||
| CemsProbeConfigProbeHighHumidityThresh | 1.3.6.1.4.1.318.1.1.10.3.7.1.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Probe high humidity threshold. Values are represented in whole number percentage. | |||||||||||||||||||||
| CemsProbeConfigProbeLowHumidityThresh | 1.3.6.1.4.1.318.1.1.10.3.7.1.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Probe low humidity threshold. Values are represented in whole number percentage. | |||||||||||||||||||||
| CemsProbeConfigProbeMaxTempThresh | 1.3.6.1.4.1.318.1.1.10.3.7.1.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Probe maximum temperature threshold. Values are represented in whole number degrees. Units are displayed in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | |||||||||||||||||||||
| CemsProbeConfigProbeMinTempThresh | 1.3.6.1.4.1.318.1.1.10.3.7.1.1.8 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Probe minimum temperature threshold. Values are represented in whole number degrees. Units are displayed in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | |||||||||||||||||||||
| CemsProbeConfigProbeDeltaTemp | 1.3.6.1.4.1.318.1.1.10.3.7.1.1.9 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Probe delta temperature. Values are represented in whole number degrees. Units are displayed in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | |||||||||||||||||||||
| CemsProbeConfigProbeMaxHumidityThresh | 1.3.6.1.4.1.318.1.1.10.3.7.1.1.10 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Probe maximum humidity threshold. Values are represented in whole number percentage. | |||||||||||||||||||||
| CemsProbeConfigProbeMinHumidityThresh | 1.3.6.1.4.1.318.1.1.10.3.7.1.1.11 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Probe minimum humidity threshold. Values are represented in whole number percentage. | |||||||||||||||||||||
| CemsProbeConfigProbeDeltaHumidity | 1.3.6.1.4.1.318.1.1.10.3.7.1.1.12 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Probe delta humidity. Values are represented in whole number percentage. | |||||||||||||||||||||
| CemsProbeConfigProbeSTIncTempVariance | 1.3.6.1.4.1.318.1.1.10.3.7.1.1.13 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Probe short-term increasing temperature variance used for rate of change alarms. Values are represented in whole number degrees. Units are displayed in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | |||||||||||||||||||||
| CemsProbeConfigProbeSTIncTempTime | 1.3.6.1.4.1.318.1.1.10.3.7.1.1.14 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Probe short-term increasing temperature time used for rate of change alarms. Values are represented in whole number minutes. | |||||||||||||||||||||
| CemsProbeConfigProbeSTDecTempVariance | 1.3.6.1.4.1.318.1.1.10.3.7.1.1.15 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Probe short-term decreasing temperature variance used for rate of change alarms. Values are represented in whole number degrees. Units are displayed in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | |||||||||||||||||||||
| CemsProbeConfigProbeSTDecTempTime | 1.3.6.1.4.1.318.1.1.10.3.7.1.1.16 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Probe short-term decreasing temperature time used for rate of change alarms. Values are represented in whole number minutes. | |||||||||||||||||||||
| CemsProbeConfigProbeLTIncTempVariance | 1.3.6.1.4.1.318.1.1.10.3.7.1.1.17 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Probe long-term increasing temperature variance used for rate of change alarms. Values are represented in whole number degrees. Units are displayed in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | |||||||||||||||||||||
| CemsProbeConfigProbeLTIncTempTime | 1.3.6.1.4.1.318.1.1.10.3.7.1.1.18 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Probe long-term increasing temperature time used for rate of change alarms. Values are represented in whole number hours. | |||||||||||||||||||||
| CemsProbeConfigProbeLTDecTempVariance | 1.3.6.1.4.1.318.1.1.10.3.7.1.1.19 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Probe long-term decreasing temperature variance used for rate of change alarms. Values are represented in whole number degrees. Units are displayed in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | |||||||||||||||||||||
| CemsProbeConfigProbeLTDecTempTime | 1.3.6.1.4.1.318.1.1.10.3.7.1.1.20 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Probe long-term decreasing temperature time used for rate of change alarms. Values are represented in whole number hours. | |||||||||||||||||||||
| CemsProbeConfigProbeMaxVoltThresh | 1.3.6.1.4.1.318.1.1.10.3.7.1.1.21 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Probe maximum voltage threshold in tenths of Volts. | |||||||||||||||||||||
| CemsProbeConfigProbeMinVoltThresh | 1.3.6.1.4.1.318.1.1.10.3.7.1.1.22 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Probe minimum voltage threshold in tenths of Volts. | |||||||||||||||||||||
| NemsInputContactConfig | 1.3.6.1.4.1.318.1.1.10.3.8 | ||||||||||||||||||||
| TemsInputContactConfigTable | 1.3.6.1.4.1.318.1.1.10.3.8.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for configuration of individual input contacts. The number of entries is contained in the emsStatusInputContactCount OID. | |||||||||||||||||||||
| RemsInputContactConfigEntry | 1.3.6.1.4.1.318.1.1.10.3.8.1.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The input contacts to configure. | |||||||||||||||||||||
| CemsInputContactConfigInputContactIndex | 1.3.6.1.4.1.318.1.1.10.3.8.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the input contact entry. | |||||||||||||||||||||
| CemsInputContactConfigInputContactName | 1.3.6.1.4.1.318.1.1.10.3.8.1.1.2 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The name of the input contact. | |||||||||||||||||||||
| CemsInputContactConfigInputContactNormalState | 1.3.6.1.4.1.318.1.1.10.3.8.1.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Getting this variable will return the normal state of the input contact. If the normal state is closed, the normallyClosedEMS (1) value will be returned. If the normal state is closed, the normallyOpenEMS (2) value will be returned. Setting this variable will change the normal state of the input contact
| |||||||||||||||||||||
| NemsOutputRelayConfig | 1.3.6.1.4.1.318.1.1.10.3.9 | ||||||||||||||||||||
| TemsOutputRelayConfigTable | 1.3.6.1.4.1.318.1.1.10.3.9.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for configuration of individual output relays. The number of entries is contained in the emsStatusOutputRelayCount OID. | |||||||||||||||||||||
| RemsOutputRelayConfigEntry | 1.3.6.1.4.1.318.1.1.10.3.9.1.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The output relays to configure. | |||||||||||||||||||||
| CemsOutputRelayConfigOutputRelayIndex | 1.3.6.1.4.1.318.1.1.10.3.9.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the output relay entry. | |||||||||||||||||||||
| CemsOutputRelayConfigOutputRelayName | 1.3.6.1.4.1.318.1.1.10.3.9.1.1.2 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The name of the output relay. | |||||||||||||||||||||
| CemsOutputRelayConfigOutputRelayNormalState | 1.3.6.1.4.1.318.1.1.10.3.9.1.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Getting this variable will return the normal state of the output relay. If the normal state is closed, the normallyClosedEMS (1) value will be returned. If the normal state is closed, the normallyOpenEMS (2) value will be returned. Setting this variable will change the normal state of the output relay
| |||||||||||||||||||||
| NemsOutletConfig | 1.3.6.1.4.1.318.1.1.10.3.10 | ||||||||||||||||||||
| TemsOutletConfigTable | 1.3.6.1.4.1.318.1.1.10.3.10.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for configuration of individual outlets. The number of entries is contained in the emsStatusOutletCount OID. | |||||||||||||||||||||
| RemsOutletConfigEntry | 1.3.6.1.4.1.318.1.1.10.3.10.1.1 | NA | mandatory | ||||||||||||||||||
| CemsOutletConfigOutletIndex | 1.3.6.1.4.1.318.1.1.10.3.10.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the outlet entry. | |||||||||||||||||||||
| CemsOutletConfigOutletName | 1.3.6.1.4.1.318.1.1.10.3.10.1.1.2 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The name of the outlet. | |||||||||||||||||||||
| CemsOutletConfigOutletNormalState | 1.3.6.1.4.1.318.1.1.10.3.10.1.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Getting this variable will return the normal state of the outlet. If the normal state is on, the normallyOnEMS (1) value will be returned. If the normal state is off, the normallyOffEMS (2) value will be returned. Setting this variable will change the normal state of the outlet
| |||||||||||||||||||||
| NemsSensorConfig | 1.3.6.1.4.1.318.1.1.10.3.11 | ||||||||||||||||||||
| TemsSensorConfigTable | 1.3.6.1.4.1.318.1.1.10.3.11.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for configuration of individual sensors. The number of entries is contained in the emsStatusSensorCount OID. | |||||||||||||||||||||
| RemsSensorConfigEntry | 1.3.6.1.4.1.318.1.1.10.3.11.1.1 | NA | mandatory | ||||||||||||||||||
| CemsSensorConfigSensorIndex | 1.3.6.1.4.1.318.1.1.10.3.11.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the sensor entry. | |||||||||||||||||||||
| CemsSensorConfigSensorSystemName | 1.3.6.1.4.1.318.1.1.10.3.11.1.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The system name of the sensor. This describes the hardware system intent of this sensor. | |||||||||||||||||||||
| CemsSensorConfigSensorUserName | 1.3.6.1.4.1.318.1.1.10.3.11.1.1.3 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The name of the sensor as given by the system user. | |||||||||||||||||||||
| CemsSensorConfigSensorNormalState | 1.3.6.1.4.1.318.1.1.10.3.11.1.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Getting this variable will return the normal state of the sensor. If the normal state is closed, the normallyClosedEMS (1) value will be returned. If the normal state is closed, the normallyOpenEMS (2) value will be returned. Setting this variable will change the normal state of the sensor. Note: Only the AUX sensor in the EMS has a configurable Normal State
| |||||||||||||||||||||
| CemsSensorConfigSensorAlarmDelay | 1.3.6.1.4.1.318.1.1.10.3.11.1.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The delay (in seconds) after a sensor detects an alarm condition before the condition is reported. | |||||||||||||||||||||
| NemsStatus | 1.3.6.1.4.1.318.1.1.10.3.12 | ||||||||||||||||||||
| SemsStatusEMSName | 1.3.6.1.4.1.318.1.1.10.3.12.1 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the device. | |||||||||||||||||||||
| SemsStatusCommStatus | 1.3.6.1.4.1.318.1.1.10.3.12.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The communication status between the agent and the device. noComm(1), Communication has never been established. comm(2), Communication has been established. commLost(3), Communication was established, but was lost.
| |||||||||||||||||||||
| SemsStatusProbeCount | 1.3.6.1.4.1.318.1.1.10.3.12.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The total number of T/H probes (both local and remote) that is supported by this device. | |||||||||||||||||||||
| SemsStatusInputContactCount | 1.3.6.1.4.1.318.1.1.10.3.12.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The total number of Input Contacts that is supported by this device. | |||||||||||||||||||||
| SemsStatusOutputRelayCount | 1.3.6.1.4.1.318.1.1.10.3.12.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The total number of Output Relays that is supported by this device. | |||||||||||||||||||||
| SemsStatusOutletCount | 1.3.6.1.4.1.318.1.1.10.3.12.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The total number of AC Outlets that is supported by this device. | |||||||||||||||||||||
| SemsStatusSensorCount | 1.3.6.1.4.1.318.1.1.10.3.12.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The total number of Sensors that is supported by this device. | |||||||||||||||||||||
| SemsStatusAlinkAruDeviceCount | 1.3.6.1.4.1.318.1.1.10.3.12.8 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The total number of remote Aru's supported by this device. | |||||||||||||||||||||
| SemsStatusAlinkProbeDeviceCount | 1.3.6.1.4.1.318.1.1.10.3.12.9 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The total number of remote T/H probes supported by this device. | |||||||||||||||||||||
| SemsStatusAlarmDeviceCount | 1.3.6.1.4.1.318.1.1.10.3.12.10 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of alarm devices supported by this device. | |||||||||||||||||||||
| SemsStatusSysTempUnits | 1.3.6.1.4.1.318.1.1.10.3.12.11 | INTEGER | RO | mandatory | fahrenheit(2) | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The temperature scale used to display the temperature in the system, Celsius(1) or Fahrenheit(2). This setting is based on the system preferences configuration in the agent.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SemsStatusCheckLogLight | 1.3.6.1.4.1.318.1.1.10.3.12.12 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The status of the check-log light on the device. For the EMU2, this will always indicate lightOff(1). lightOff (1) indicates the light is off (no new log entries). lightOn (2) indicates the light is on (new log entries present).
| |||||||||||||||||||||
| SemsStatusHardwareStatus | 1.3.6.1.4.1.318.1.1.10.3.12.13 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The status of the EMS hardware. This integer should be interpreted as a bit map, with each bit representing the presence or absence of a specific hardware error condition. 0 indicates there are no error conditions detected in the EMS hardware. 1 indicates a Current Limit error condition related to the Alink port. 2 indicates incorrect hardware is plugged into an EMS port. 3 indicates that both of these error conditions are present. | |||||||||||||||||||||
| NemsProbeStatus | 1.3.6.1.4.1.318.1.1.10.3.13 | ||||||||||||||||||||
| TemsProbeStatusTable | 1.3.6.1.4.1.318.1.1.10.3.13.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for access of individual probes. The number of entries is contained in the emsStatusProbeCount OID. | |||||||||||||||||||||
| RemsProbeStatusEntry | 1.3.6.1.4.1.318.1.1.10.3.13.1.1 | NA | mandatory | ||||||||||||||||||
| CemsProbeStatusProbeIndex | 1.3.6.1.4.1.318.1.1.10.3.13.1.1.1 | INTEGER | RO | mandatory | 1 | ||||||||||||||||
column · INTEGER · read-only · mandatory The index to the probe entry. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CemsProbeStatusProbeName | 1.3.6.1.4.1.318.1.1.10.3.13.1.1.2 | DisplayString | RO | mandatory | Loc Env Probe 1 | ||||||||||||||||
column · DisplayString · read-only · mandatory The name of the probe. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CemsProbeStatusProbeTemperature | 1.3.6.1.4.1.318.1.1.10.3.13.1.1.3 | INTEGER | RO | mandatory | 81 | ||||||||||||||||
column · INTEGER · read-only · mandatory Probe temperature reading. Values are represented in whole number degrees. Units are displayed in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). Example values from LibreNMS test devices
| |||||||||||||||||||||
| CemsProbeStatusProbeHighTempThresh | 1.3.6.1.4.1.318.1.1.10.3.13.1.1.4 | INTEGER | RO | mandatory | 85 | ||||||||||||||||
column · INTEGER · read-only · mandatory Probe high temperature threshold. Values are represented in whole number degrees. Units are displayed in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). Example values from LibreNMS test devices
| |||||||||||||||||||||
| CemsProbeStatusProbeLowTempThresh | 1.3.6.1.4.1.318.1.1.10.3.13.1.1.5 | INTEGER | RO | mandatory | 33 | ||||||||||||||||
column · INTEGER · read-only · mandatory Probe low temperature threshold. Values are represented in whole number degrees. Units are displayed in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). Example values from LibreNMS test devices
| |||||||||||||||||||||
| CemsProbeStatusProbeHumidity | 1.3.6.1.4.1.318.1.1.10.3.13.1.1.6 | INTEGER | RO | mandatory | -1 | ||||||||||||||||
column · INTEGER · read-only · mandatory Probe humidity reading. Values are represented in whole number percentage. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CemsProbeStatusProbeHighHumidityThresh | 1.3.6.1.4.1.318.1.1.10.3.13.1.1.7 | INTEGER | RO | mandatory | 90 | ||||||||||||||||
column · INTEGER · read-only · mandatory Probe high humidity threshold. Values are represented in whole number percentage. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CemsProbeStatusProbeLowHumidityThresh | 1.3.6.1.4.1.318.1.1.10.3.13.1.1.8 | INTEGER | RO | mandatory | 10 | ||||||||||||||||
column · INTEGER · read-only · mandatory Probe low humidity threshold. Values are represented in whole number percentage. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CemsProbeStatusProbeSerialNumber | 1.3.6.1.4.1.318.1.1.10.3.13.1.1.9 | DisplayString | RO | mandatory | L1 | ||||||||||||||||
column · DisplayString · read-only · mandatory A label indicating the type (Local[L] or Remote[R]) and Number of the probe. For example, the first local probe would be L1 and the third remote probe would be R3. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CemsProbeStatusProbeCommStatus | 1.3.6.1.4.1.318.1.1.10.3.13.1.1.10 | INTEGER | RO | mandatory | commsEstablished(2) | ||||||||||||||||
column · INTEGER · read-only · mandatory The state of communications to the probe. commNeverDiscovered(1) indicates there has never been communications with this device. commsEstablished(2) indicates communication is normal and active with this device. commsLost(3) indicates communication had been established, but is no longer.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CemsProbeStatusProbeAlarmStatus | 1.3.6.1.4.1.318.1.1.10.3.13.1.1.11 | INTEGER | RO | mandatory | 0 | ||||||||||||||||
column · INTEGER · read-only · mandatory The alarm status of the probe. This integer should be interpreted as a bit map, with each bit representing the presence or absence of the specific alarm conditions listed below. The bit will be '1' if the condition is present, and '0' if the condition is not present. Bit Hex. Value Description 1 0x0001 Maximum temperature exceeded. 2 0x0002 High temperature exceeded. 3 0x0004 Low temperature exceeded. 4 0x0008 Minimum temperature exceeded. 5 0x0010 Short-term increasing temperature rate exceeded. 6 0x0020 Short-term decreasing temperature rate exceeded. 7 0x0040 Long-term increasing temperature rate exceeded. 8 0x0080 Long-term decreasing temperature rate exceeded. 9 0x0100 Maximum humidity exceeded. 10 0x0200 High humidity exceeded. 11 0x0400 Low humidity exceeded. 12 0x0800 Minimum humidity exceeded. 13 0x1000 Maximum voltage exceeded. 14 0x2000 Minimum voltage exceeded. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CemsProbeStatusProbeMaxTempThresh | 1.3.6.1.4.1.318.1.1.10.3.13.1.1.12 | INTEGER | RO | mandatory | 140 | ||||||||||||||||
column · INTEGER · read-only · mandatory Probe maximum temperature threshold. Values are represented in whole number degrees. Units are displayed in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). Example values from LibreNMS test devices
| |||||||||||||||||||||
| CemsProbeStatusProbeMinTempThresh | 1.3.6.1.4.1.318.1.1.10.3.13.1.1.13 | INTEGER | RO | mandatory | 32 | ||||||||||||||||
column · INTEGER · read-only · mandatory Probe minimum temperature threshold. Values are represented in whole number degrees. Units are displayed in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). Example values from LibreNMS test devices
| |||||||||||||||||||||
| CemsProbeStatusProbeMaxHumidityThresh | 1.3.6.1.4.1.318.1.1.10.3.13.1.1.14 | INTEGER | RO | mandatory | 99 | ||||||||||||||||
column · INTEGER · read-only · mandatory Probe maximum humidity threshold. Values are represented in whole number percentage. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CemsProbeStatusProbeMinHumidityThresh | 1.3.6.1.4.1.318.1.1.10.3.13.1.1.15 | INTEGER | RO | mandatory | 0 | ||||||||||||||||
column · INTEGER · read-only · mandatory Probe minimum humidity threshold. Values are represented in whole number percentage. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CemsProbeStatusProbeVoltage | 1.3.6.1.4.1.318.1.1.10.3.13.1.1.16 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Probe voltage reading. Values are displayed in tenths of Volts DC. | |||||||||||||||||||||
| CemsProbeStatusProbeMaxVoltThresh | 1.3.6.1.4.1.318.1.1.10.3.13.1.1.17 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Probe maximum voltage threshold in Volts. | |||||||||||||||||||||
| CemsProbeStatusProbeMinVoltThresh | 1.3.6.1.4.1.318.1.1.10.3.13.1.1.18 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Probe minimum voltage threshold in Volts. | |||||||||||||||||||||
| NemsInputContactStatus | 1.3.6.1.4.1.318.1.1.10.3.14 | ||||||||||||||||||||
| TemsInputContactStatusTable | 1.3.6.1.4.1.318.1.1.10.3.14.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for access of individual input contacts. The number of entries is contained in the emsStatusInputContactCount OID. | |||||||||||||||||||||
| RemsInputContactStatusEntry | 1.3.6.1.4.1.318.1.1.10.3.14.1.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The input contacts to access. | |||||||||||||||||||||
| CemsInputContactStatusInputContactIndex | 1.3.6.1.4.1.318.1.1.10.3.14.1.1.1 | INTEGER | RO | mandatory | 1 | ||||||||||||||||
column · INTEGER · read-only · mandatory The index to the input contact entry. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CemsInputContactStatusInputContactName | 1.3.6.1.4.1.318.1.1.10.3.14.1.1.2 | DisplayString | RO | mandatory | Contact 1 | ||||||||||||||||
column · DisplayString · read-only · mandatory The name of the input contact. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CemsInputContactStatusInputContactState | 1.3.6.1.4.1.318.1.1.10.3.14.1.1.3 | INTEGER | RO | mandatory | contactOpenEMS(2) | ||||||||||||||||
column · INTEGER · read-only · mandatory Getting this variable will return the state of the input contact. If the input contact is closed, the contactClosedEMS (1) value will be returned. If the input contact state is open, the contactOpenEMS (2) value will be returned.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CemsInputContactStatusInputContactNormalState | 1.3.6.1.4.1.318.1.1.10.3.14.1.1.4 | INTEGER | RO | mandatory | normallyOpenEMS(2) | ||||||||||||||||
column · INTEGER · read-only · mandatory Getting this variable will return the normal state of the input contact. If the normal state is closed, the normallyClosedEMS (1) value will be returned. If the normal state is open, the normallyOpenEMS (2) value will be returned.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NemsOutputRelayStatus | 1.3.6.1.4.1.318.1.1.10.3.15 | ||||||||||||||||||||
| TemsOutputRelayStatusTable | 1.3.6.1.4.1.318.1.1.10.3.15.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for access of individual output relays. The number of entries is contained in the emsStatusOutputRelayCount OID. | |||||||||||||||||||||
| RemsOutputRelayStatusEntry | 1.3.6.1.4.1.318.1.1.10.3.15.1.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The output relays to access. | |||||||||||||||||||||
| CemsOutputRelayStatusOutputRelayIndex | 1.3.6.1.4.1.318.1.1.10.3.15.1.1.1 | INTEGER | RO | mandatory | 1 | ||||||||||||||||
column · INTEGER · read-only · mandatory The index to the output relay entry. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CemsOutputRelayStatusOutputRelayName | 1.3.6.1.4.1.318.1.1.10.3.15.1.1.2 | DisplayString | RO | mandatory | Relay 1 | ||||||||||||||||
column · DisplayString · read-only · mandatory The name of the output relay. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CemsOutputRelayStatusOutputRelayState | 1.3.6.1.4.1.318.1.1.10.3.15.1.1.3 | INTEGER | RO | mandatory | relayOpenEMS(2) | ||||||||||||||||
column · INTEGER · read-only · mandatory Getting this variable will return the state of the output relay. If the output relay is closed, the relayClosedEMS (1) value will be returned. If the output relay is open, the relayOpenEMS (2) value will be returned.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CemsOutputRelayStatusOutputRelayNormalState | 1.3.6.1.4.1.318.1.1.10.3.15.1.1.4 | INTEGER | RO | mandatory | normallyOpenEMS(2) | ||||||||||||||||
column · INTEGER · read-only · mandatory Getting this variable will return the normal state of the output relay. If the normal state is closed, the normallyClosedEMS (1) value will be returned. If the normal state is open, the normallyOpenEMS (2) value will be returned.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NemsOutletStatus | 1.3.6.1.4.1.318.1.1.10.3.16 | ||||||||||||||||||||
| TemsOutletStatusTable | 1.3.6.1.4.1.318.1.1.10.3.16.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for access of individual outlets. The number of entries is contained in the emsStatusOutletCount OID. | |||||||||||||||||||||
| RemsOutletStatusEntry | 1.3.6.1.4.1.318.1.1.10.3.16.1.1 | NA | mandatory | ||||||||||||||||||
| CemsOutletStatusOutletIndex | 1.3.6.1.4.1.318.1.1.10.3.16.1.1.1 | INTEGER | RO | mandatory | 1 | ||||||||||||||||
column · INTEGER · read-only · mandatory The index to the outlet entry. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CemsOutletStatusOutletName | 1.3.6.1.4.1.318.1.1.10.3.16.1.1.2 | DisplayString | RO | mandatory | Outlet 1 | ||||||||||||||||
column · DisplayString · read-only · mandatory The name of the outlet. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CemsOutletStatusOutletState | 1.3.6.1.4.1.318.1.1.10.3.16.1.1.3 | INTEGER | RO | mandatory | outletOffEMS(2) | ||||||||||||||||
column · INTEGER · read-only · mandatory Getting this variable will return the state of the outlet. If the outlet is on, the outletOnEMS (1) value will be returned. If the outlet is off, the outletOffEMS (2) value will be returned.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CemsOutletStatusOutletNormalState | 1.3.6.1.4.1.318.1.1.10.3.16.1.1.4 | INTEGER | RO | mandatory | normallyOffEMS(2) | ||||||||||||||||
column · INTEGER · read-only · mandatory Getting this variable will return the normal state of the outlet. If the normal state is on, the normallyOnEMS (1) value will be returned. If the normal state is off, the normallyOffEMS (2) value will be returned.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NemsAlarmDeviceStatus | 1.3.6.1.4.1.318.1.1.10.3.17 | ||||||||||||||||||||
| TemsAlarmDeviceStatusTable | 1.3.6.1.4.1.318.1.1.10.3.17.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for access of individual alarm devices. The number of entries is contained in the emsStatusAlarmDeviceCount OID. | |||||||||||||||||||||
| RemsAlarmDeviceStatusEntry | 1.3.6.1.4.1.318.1.1.10.3.17.1.1 | NA | mandatory | ||||||||||||||||||
| CemsAlarmDeviceStatusDeviceIndex | 1.3.6.1.4.1.318.1.1.10.3.17.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the alarm device entry. | |||||||||||||||||||||
| CemsAlarmDeviceStatusDeviceName | 1.3.6.1.4.1.318.1.1.10.3.17.1.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The name of the alarm device. This OID is provided for informational purposes only. | |||||||||||||||||||||
| CemsAlarmDeviceStatusDeviceState | 1.3.6.1.4.1.318.1.1.10.3.17.1.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this variable will return the device state. If the device is active, the alarmDeviceOnEMS (1) value will be returned. If the device is inactive, the alarmDeviceOffEMS (2) value will be returned. If the device is not installed, the alarmDeviceNotInstalledEMS (3) value will be returned.
| |||||||||||||||||||||
| NemsSensorStatus | 1.3.6.1.4.1.318.1.1.10.3.18 | ||||||||||||||||||||
| TemsSensorStatusTable | 1.3.6.1.4.1.318.1.1.10.3.18.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for access of individual sensors. The number of entries is contained in the emsStatusSensorCount OID. | |||||||||||||||||||||
| RemsSensorStatusEntry | 1.3.6.1.4.1.318.1.1.10.3.18.1.1 | NA | mandatory | ||||||||||||||||||
| CemsSensorStatusSensorIndex | 1.3.6.1.4.1.318.1.1.10.3.18.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the sensor entry. | |||||||||||||||||||||
| CemsSensorStatusSensorSystemName | 1.3.6.1.4.1.318.1.1.10.3.18.1.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The system name of the sensor. This describes the hardware system intent of this sensor. | |||||||||||||||||||||
| CemsSensorStatusSensorName | 1.3.6.1.4.1.318.1.1.10.3.18.1.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The name of the sensor as given by the system user. | |||||||||||||||||||||
| CemsSensorStatusSensorState | 1.3.6.1.4.1.318.1.1.10.3.18.1.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this variable will return the sensor state. If the sensor is faulted, the sensorFaultedEMS (1) value will be returned. If the sensor is not faulted, the sensorOKEMS (2) value will be returned. If the sensor is not installed, the sensorNotInstalledEMS (3) value will be returned.
| |||||||||||||||||||||
| CemsSensorStatusSensorNormalState | 1.3.6.1.4.1.318.1.1.10.3.18.1.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this variable will return the normal state of the sensor. If the normal state is closed, the normallyClosedEMS (1) value will be returned. If the normal state is closed, the normallyOpenEMS (2) value will be returned.
| |||||||||||||||||||||
| CemsSensorStatusSensorAlarmDelay | 1.3.6.1.4.1.318.1.1.10.3.18.1.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The delay (in seconds) after a sensor detects an alarm condition before the condition is reported. | |||||||||||||||||||||
| NemsInputStateSensorConfig | 1.3.6.1.4.1.318.1.1.10.3.19 | ||||||||||||||||||||
| TemsSmokeSensorConfigTable | 1.3.6.1.4.1.318.1.1.10.3.19.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for the configuration of individual sensors. | |||||||||||||||||||||
| RemsSmokeSensorConfigEntry | 1.3.6.1.4.1.318.1.1.10.3.19.1.1 | NA | mandatory | ||||||||||||||||||
| CemsSmokeSensorConfigSensorIndex | 1.3.6.1.4.1.318.1.1.10.3.19.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the sensor entry. | |||||||||||||||||||||
| CemsSmokeSensorConfigSensorName | 1.3.6.1.4.1.318.1.1.10.3.19.1.1.2 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The user defined name of the smoke sensor. | |||||||||||||||||||||
| CemsSmokeSensorConfigSensorLocation | 1.3.6.1.4.1.318.1.1.10.3.19.1.1.3 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The user defined location of the smoke sensor. | |||||||||||||||||||||
| CemsSmokeSensorConfigSensorSeverity | 1.3.6.1.4.1.318.1.1.10.3.19.1.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The severity of the alarm that will be triggered when the smoke sensor is activated. The alarms can be critical(1), warning(2) or informational(3).
| |||||||||||||||||||||
| TemsVibrationSensorConfigTable | 1.3.6.1.4.1.318.1.1.10.3.19.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for the configuration of individual sensors. | |||||||||||||||||||||
| RemsVibrationSensorConfigEntry | 1.3.6.1.4.1.318.1.1.10.3.19.2.1 | NA | mandatory | ||||||||||||||||||
| CemsVibrationSensorConfigSensorIndex | 1.3.6.1.4.1.318.1.1.10.3.19.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the sensor entry. | |||||||||||||||||||||
| CemsVibrationSensorConfigSensorName | 1.3.6.1.4.1.318.1.1.10.3.19.2.1.2 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The user defined name of the vibration sensor. | |||||||||||||||||||||
| CemsVibrationSensorConfigSensorLocation | 1.3.6.1.4.1.318.1.1.10.3.19.2.1.3 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The user defined location of the vibration sensor. | |||||||||||||||||||||
| CemsVibrationSensorConfigSensorSeverity | 1.3.6.1.4.1.318.1.1.10.3.19.2.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The severity of the alarm that will be triggered when the vibration sensor is activated. The alarms can be critical(1), warning(2) or informational(3).
| |||||||||||||||||||||
| TemsFluidSensorConfigTable | 1.3.6.1.4.1.318.1.1.10.3.19.3 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for the configuration of individual sensors. | |||||||||||||||||||||
| RemsFluidSensorConfigEntry | 1.3.6.1.4.1.318.1.1.10.3.19.3.1 | NA | mandatory | ||||||||||||||||||
| CemsFluidSensorConfigSensorIndex | 1.3.6.1.4.1.318.1.1.10.3.19.3.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the sensor entry. | |||||||||||||||||||||
| CemsFluidSensorConfigSensorName | 1.3.6.1.4.1.318.1.1.10.3.19.3.1.2 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The user defined name of the fluid sensor. | |||||||||||||||||||||
| CemsFluidSensorConfigSensorLocation | 1.3.6.1.4.1.318.1.1.10.3.19.3.1.3 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The user defined location of the fluid sensor. | |||||||||||||||||||||
| CemsFluidSensorConfigSensorSeverity | 1.3.6.1.4.1.318.1.1.10.3.19.3.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The severity of the alarm that will be triggered when the fluid sensor is activated. The alarms can be critical(1), warning(2) or informational(3).
| |||||||||||||||||||||
| TemsDoorSensorConfigTable | 1.3.6.1.4.1.318.1.1.10.3.19.4 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for the configuration of individual sensors. | |||||||||||||||||||||
| RemsDoorSensorConfigEntry | 1.3.6.1.4.1.318.1.1.10.3.19.4.1 | NA | mandatory | ||||||||||||||||||
| CemsDoorSensorConfigSensorIndex | 1.3.6.1.4.1.318.1.1.10.3.19.4.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the sensor entry. | |||||||||||||||||||||
| CemsDoorSensorConfigSensorName | 1.3.6.1.4.1.318.1.1.10.3.19.4.1.2 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The user defined name of the door sensor. | |||||||||||||||||||||
| CemsDoorSensorConfigSensorLocation | 1.3.6.1.4.1.318.1.1.10.3.19.4.1.3 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The user defined location of the door sensor. | |||||||||||||||||||||
| CemsDoorSensorConfigSensorSeverity | 1.3.6.1.4.1.318.1.1.10.3.19.4.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The severity of the alarm that will be triggered when the door sensor is activated. The alarms can be critical(1), warning(2) or informational(3).
| |||||||||||||||||||||
| TemsLeakRopeConfigTable | 1.3.6.1.4.1.318.1.1.10.3.19.5 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for the configuration of an individual leak rope. | |||||||||||||||||||||
| RemsLeakRopeConfigEntry | 1.3.6.1.4.1.318.1.1.10.3.19.5.1 | NA | mandatory | ||||||||||||||||||
| CemsLeakRopeConfigIndex | 1.3.6.1.4.1.318.1.1.10.3.19.5.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of the leak rope entry. | |||||||||||||||||||||
| CemsLeakRopeConfigName | 1.3.6.1.4.1.318.1.1.10.3.19.5.1.2 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The user-defined name of the leak rope. | |||||||||||||||||||||
| CemsLeakRopeConfigLocation | 1.3.6.1.4.1.318.1.1.10.3.19.5.1.3 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The user-defined location of the leak rope. | |||||||||||||||||||||
| CemsLeakRopeConfigSeverity | 1.3.6.1.4.1.318.1.1.10.3.19.5.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The severity of the alarm that will be triggered when the leak rope is activated.
| |||||||||||||||||||||
| NemsInputStateSensorStatus | 1.3.6.1.4.1.318.1.1.10.3.20 | ||||||||||||||||||||
| SemsSmokeSensorStatusTableSize | 1.3.6.1.4.1.318.1.1.10.3.20.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the emsSmokeSensorStatusTable. | |||||||||||||||||||||
| TemsSmokeSensorStatusTable | 1.3.6.1.4.1.318.1.1.10.3.20.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for the access of individual sensors. | |||||||||||||||||||||
| RemsSmokeSensorStatusEntry | 1.3.6.1.4.1.318.1.1.10.3.20.2.1 | NA | mandatory | ||||||||||||||||||
| CemsSmokeSensorStatusSensorIndex | 1.3.6.1.4.1.318.1.1.10.3.20.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the sensor entry. | |||||||||||||||||||||
| CemsSmokeSensorStatusSensorName | 1.3.6.1.4.1.318.1.1.10.3.20.2.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The user defined name of the smoke sensor. | |||||||||||||||||||||
| CemsSmokeSensorStatusSensorLocation | 1.3.6.1.4.1.318.1.1.10.3.20.2.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The user defined location of the smoke sensor. | |||||||||||||||||||||
| CemsSmokeSensorStatusSensorState | 1.3.6.1.4.1.318.1.1.10.3.20.2.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The state of the smoke sensor. smokeDetected (1) indicates there is smoke. noSmoke (2) indicates there is no smoke. unknown (3) indicates the state is unknown.
| |||||||||||||||||||||
| CemsSmokeSensorStatusSensorSeverity | 1.3.6.1.4.1.318.1.1.10.3.20.2.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The severity of the alarm that will be triggered when the smoke sensor is activated. The alarms can be critical(1), warning(2) or informational(3).
| |||||||||||||||||||||
| CemsSmokeSensorCommStatus | 1.3.6.1.4.1.318.1.1.10.3.20.2.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The communication status of the smoke sensor.
| |||||||||||||||||||||
| SemsVibrationSensorStatusTableSize | 1.3.6.1.4.1.318.1.1.10.3.20.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the emsVibrationSensorStatusTable. | |||||||||||||||||||||
| TemsVibrationSensorStatusTable | 1.3.6.1.4.1.318.1.1.10.3.20.4 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for the access of individual sensors. | |||||||||||||||||||||
| RemsVibrationSensorStatusEntry | 1.3.6.1.4.1.318.1.1.10.3.20.4.1 | NA | mandatory | ||||||||||||||||||
| CemsVibrationSensorStatusSensorIndex | 1.3.6.1.4.1.318.1.1.10.3.20.4.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the sensor entry. | |||||||||||||||||||||
| CemsVibrationSensorStatusSensorName | 1.3.6.1.4.1.318.1.1.10.3.20.4.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The user defined name of the vibration sensor. | |||||||||||||||||||||
| CemsVibrationSensorStatusSensorLocation | 1.3.6.1.4.1.318.1.1.10.3.20.4.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The user defined location of the vibration sensor. | |||||||||||||||||||||
| CemsVibrationSensorStatusSensorState | 1.3.6.1.4.1.318.1.1.10.3.20.4.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The state of the vibration sensor. vibrationDetected (1) indicates there is vibration. noVibration (2) indicates there is no vibration. unknown (3) indicates the state is unknown.
| |||||||||||||||||||||
| CemsVibrationSensorStatusSensorSeverity | 1.3.6.1.4.1.318.1.1.10.3.20.4.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The severity of the alarm that will be triggered when the vibration sensor is activated. The alarms can be critical(1), warning(2) or informational(3).
| |||||||||||||||||||||
| CemsVibrationSensorCommStatus | 1.3.6.1.4.1.318.1.1.10.3.20.4.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The communication status of the vibration sensor.
| |||||||||||||||||||||
| SemsFluidSensorStatusTableSize | 1.3.6.1.4.1.318.1.1.10.3.20.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the emsFluidSensorStatusTable. | |||||||||||||||||||||
| TemsFluidSensorStatusTable | 1.3.6.1.4.1.318.1.1.10.3.20.6 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for the access of individual sensors. | |||||||||||||||||||||
| RemsFluidSensorStatusEntry | 1.3.6.1.4.1.318.1.1.10.3.20.6.1 | NA | mandatory | ||||||||||||||||||
| CemsFluidSensorStatusSensorIndex | 1.3.6.1.4.1.318.1.1.10.3.20.6.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the sensor entry. | |||||||||||||||||||||
| CemsFluidSensorStatusSensorName | 1.3.6.1.4.1.318.1.1.10.3.20.6.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The user defined name of the fluid sensor. | |||||||||||||||||||||
| CemsFluidSensorStatusSensorLocation | 1.3.6.1.4.1.318.1.1.10.3.20.6.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The user defined location of the fluid sensor. | |||||||||||||||||||||
| CemsFluidSensorStatusSensorState | 1.3.6.1.4.1.318.1.1.10.3.20.6.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The state of the fluid sensor. fluidDetected (1) indicates there is fluid leak. noFluid (2) indicates there is no fluid leak. unknown (3) indicates the state is unknown.
| |||||||||||||||||||||
| CemsFluidSensorStatusSensorSeverity | 1.3.6.1.4.1.318.1.1.10.3.20.6.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The severity of the alarm that will be triggered when the fluid sensor is activated. The alarms can be critical(1), warning(2) or informational(3).
| |||||||||||||||||||||
| CemsFluidSensorCommStatus | 1.3.6.1.4.1.318.1.1.10.3.20.6.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The communication status of the fluid sensor.
| |||||||||||||||||||||
| SemsDoorSensorStatusTableSize | 1.3.6.1.4.1.318.1.1.10.3.20.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the emsDoorSensorStatusTable. | |||||||||||||||||||||
| TemsDoorSensorStatusTable | 1.3.6.1.4.1.318.1.1.10.3.20.8 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for the access of individual sensors. | |||||||||||||||||||||
| RemsDoorSensorStatusEntry | 1.3.6.1.4.1.318.1.1.10.3.20.8.1 | NA | mandatory | ||||||||||||||||||
| CemsDoorSensorStatusSensorIndex | 1.3.6.1.4.1.318.1.1.10.3.20.8.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the sensor entry. | |||||||||||||||||||||
| CemsDoorSensorStatusSensorName | 1.3.6.1.4.1.318.1.1.10.3.20.8.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The user defined name of the door sensor. | |||||||||||||||||||||
| CemsDoorSensorStatusSensorLocation | 1.3.6.1.4.1.318.1.1.10.3.20.8.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The user defined location of the door sensor. | |||||||||||||||||||||
| CemsDoorSensorStatusSensorState | 1.3.6.1.4.1.318.1.1.10.3.20.8.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The state of the door sensor. open (1) indicates door open. closed (2) indicates door closed. unknown (3) indicates the state is unknown.
| |||||||||||||||||||||
| CemsDoorSensorStatusSensorSeverity | 1.3.6.1.4.1.318.1.1.10.3.20.8.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The severity of the alarm that will be triggered when the door sensor is activated. The alarms can be critical(1), warning(2) or informational(3).
| |||||||||||||||||||||
| CemsDoorSensorCommStatus | 1.3.6.1.4.1.318.1.1.10.3.20.8.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The communication status of the door sensor.
| |||||||||||||||||||||
| SemsLeakRopeStatusTableSize | 1.3.6.1.4.1.318.1.1.10.3.20.9 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the emsLeakRopeStatusTable. | |||||||||||||||||||||
| TemsLeakRopeStatusTable | 1.3.6.1.4.1.318.1.1.10.3.20.10 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for the access of individual leak ropes. | |||||||||||||||||||||
| RemsLeakRopeStatusEntry | 1.3.6.1.4.1.318.1.1.10.3.20.10.1 | NA | mandatory | ||||||||||||||||||
| CemsLeakRopeStatusIndex | 1.3.6.1.4.1.318.1.1.10.3.20.10.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of the leak rope entry. | |||||||||||||||||||||
| CemsLeakRopeStatusName | 1.3.6.1.4.1.318.1.1.10.3.20.10.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The user defined name of the leak rope. | |||||||||||||||||||||
| CemsLeakRopeStatusLocation | 1.3.6.1.4.1.318.1.1.10.3.20.10.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The user defined location of the leak rope. | |||||||||||||||||||||
| CemsLeakRopeStatusState | 1.3.6.1.4.1.318.1.1.10.3.20.10.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The state of the leak rope. The values can be noleak(1), leakdetected(2), or unknown(3).
| |||||||||||||||||||||
| CemsLeakRopeStatusSeverity | 1.3.6.1.4.1.318.1.1.10.3.20.10.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The severity of the alarm that will be triggered when the leak rope is activated.
| |||||||||||||||||||||
| CemsLeakRopeCommStatus | 1.3.6.1.4.1.318.1.1.10.3.20.10.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The communication status of the leak rope. The values can be connected(1), disconnected(2), or commsLost(3).
| |||||||||||||||||||||
| NmodEnvMgr | 1.3.6.1.4.1.318.1.1.10.4 | ||||||||||||||||||||
| NmemModules | 1.3.6.1.4.1.318.1.1.10.4.1 | ||||||||||||||||||||
| SmemModulesStatusTableSize | 1.3.6.1.4.1.318.1.1.10.4.1.1 | INTEGER | RO | mandatory | 1 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the memModulesStatusTable. Example values from LibreNMS test devices
| |||||||||||||||||||||
| TmemModulesStatusTable | 1.3.6.1.4.1.318.1.1.10.4.1.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting status information from the modules attached to the system. | |||||||||||||||||||||
| RmemModulesStatusEntry | 1.3.6.1.4.1.318.1.1.10.4.1.2.1 | NA | mandatory | ||||||||||||||||||
| CmemModulesStatusModuleNumber | 1.3.6.1.4.1.318.1.1.10.4.1.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The module number. | |||||||||||||||||||||
| CmemModulesStatusModuleName | 1.3.6.1.4.1.318.1.1.10.4.1.2.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The module name. | |||||||||||||||||||||
| CmemModulesStatusModuleLocation | 1.3.6.1.4.1.318.1.1.10.4.1.2.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The location of the module. | |||||||||||||||||||||
| CmemModulesStatusModelNumber | 1.3.6.1.4.1.318.1.1.10.4.1.2.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The model number of the module. | |||||||||||||||||||||
| CmemModulesStatusSerialNumber | 1.3.6.1.4.1.318.1.1.10.4.1.2.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The serial number of the module. | |||||||||||||||||||||
| CmemModulesStatusFirmwareRev | 1.3.6.1.4.1.318.1.1.10.4.1.2.1.6 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The firmware revision of the module. | |||||||||||||||||||||
| CmemModulesStatusHardwareRev | 1.3.6.1.4.1.318.1.1.10.4.1.2.1.7 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The hardware revision. | |||||||||||||||||||||
| SmemModulesConfigTableSize | 1.3.6.1.4.1.318.1.1.10.4.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the memModulesConfigTable. | |||||||||||||||||||||
| TmemModulesConfigTable | 1.3.6.1.4.1.318.1.1.10.4.1.4 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting status information from the modules attached to the system. | |||||||||||||||||||||
| RmemModulesConfigEntry | 1.3.6.1.4.1.318.1.1.10.4.1.4.1 | NA | mandatory | ||||||||||||||||||
| CmemModulesConfigModuleNumber | 1.3.6.1.4.1.318.1.1.10.4.1.4.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The module number. | |||||||||||||||||||||
| CmemModulesConfigModuleName | 1.3.6.1.4.1.318.1.1.10.4.1.4.1.2 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The module name. | |||||||||||||||||||||
| CmemModulesConfigModuleLocation | 1.3.6.1.4.1.318.1.1.10.4.1.4.1.3 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The location of the module. | |||||||||||||||||||||
| NmemSensors | 1.3.6.1.4.1.318.1.1.10.4.2 | ||||||||||||||||||||
| SmemSensorsStatusSysTempUnits | 1.3.6.1.4.1.318.1.1.10.4.2.1 | INTEGER | RO | mandatory | celsius(1) | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The temperature scale used to display the temperature in the system, Celsius(1) or Fahrenheit(2). This setting is based on the system preferences configuration in the agent.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SmemSensorsStatusTableSize | 1.3.6.1.4.1.318.1.1.10.4.2.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the memSensorsStatusTable. | |||||||||||||||||||||
| TmemSensorsStatusTable | 1.3.6.1.4.1.318.1.1.10.4.2.3 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting sensor status information. | |||||||||||||||||||||
| RmemSensorsStatusEntry | 1.3.6.1.4.1.318.1.1.10.4.2.3.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The unit to get data from. | |||||||||||||||||||||
| CmemSensorsStatusModuleNumber | 1.3.6.1.4.1.318.1.1.10.4.2.3.1.1 | INTEGER | RO | mandatory | 0 | ||||||||||||||||
column · INTEGER · read-only · mandatory The number of the module that the sensor is attached to. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmemSensorsStatusSensorNumber | 1.3.6.1.4.1.318.1.1.10.4.2.3.1.2 | INTEGER | RO | mandatory | 1 | ||||||||||||||||
column · INTEGER · read-only · mandatory The number of this sensor on the module. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmemSensorsStatusSensorName | 1.3.6.1.4.1.318.1.1.10.4.2.3.1.3 | DisplayString | RO | mandatory | ENVMONS1 | ||||||||||||||||
column · DisplayString · read-only · mandatory The sensor name. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmemSensorsStatusSensorLocation | 1.3.6.1.4.1.318.1.1.10.4.2.3.1.4 | DisplayString | RO | mandatory | Basement | ||||||||||||||||
column · DisplayString · read-only · mandatory The location of the sensor. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmemSensorsTemperature | 1.3.6.1.4.1.318.1.1.10.4.2.3.1.5 | INTEGER | RO | mandatory | 18 | ||||||||||||||||
column · INTEGER · read-only · mandatory The sensor's current temperature reading. Units are displayed in the scale shown in the memSensorsStatusSysTempUnits OID (Celsius or Fahrenheit). | |||||||||||||||||||||
| CmemSensorsHumidity | 1.3.6.1.4.1.318.1.1.10.4.2.3.1.6 | INTEGER | RO | mandatory | 30 | ||||||||||||||||
| CmemSensorsCommStatus | 1.3.6.1.4.1.318.1.1.10.4.2.3.1.7 | INTEGER | RO | mandatory | commsOK(2) | ||||||||||||||||
column · INTEGER · read-only · mandatory The communications status of the sensor.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmemSensorsAlarmStatus | 1.3.6.1.4.1.318.1.1.10.4.2.3.1.8 | INTEGER | RO | mandatory | memNormal(1) | ||||||||||||||||
column · INTEGER · read-only · mandatory The alarm status of the sensor. memWarning is not applicable to voltage sensor.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmemSensorsTemperatureHighPrec | 1.3.6.1.4.1.318.1.1.10.4.2.3.1.9 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The current temperature is displayed in tenths of degrees in the scale shown in the memSensorsStatusSysTempUnits OID (Celsius or Fahrenheit). | |||||||||||||||||||||
| CmemSensorsVoltage | 1.3.6.1.4.1.318.1.1.10.4.2.3.1.10 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The sensor's current voltage reading. Values are displayed in tenths of Volts DC. | |||||||||||||||||||||
| SmemSensorsConfigTableSize | 1.3.6.1.4.1.318.1.1.10.4.2.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the memSensorsConfigTable. | |||||||||||||||||||||
| TmemSensorsConfigTable | 1.3.6.1.4.1.318.1.1.10.4.2.5 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting configuration information from sensors attached to the system. | |||||||||||||||||||||
| RmemSensorsConfigEntry | 1.3.6.1.4.1.318.1.1.10.4.2.5.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The unit to get data from. | |||||||||||||||||||||
| CmemSensorsConfigModuleNumber | 1.3.6.1.4.1.318.1.1.10.4.2.5.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The number of the module that the sensor is attached to. | |||||||||||||||||||||
| CmemSensorsConfigSensorNumber | 1.3.6.1.4.1.318.1.1.10.4.2.5.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The number of this sensor on the module. | |||||||||||||||||||||
| CmemSensorsName | 1.3.6.1.4.1.318.1.1.10.4.2.5.1.3 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory A descriptive name for the sensor. | |||||||||||||||||||||
| CmemSensorsLocation | 1.3.6.1.4.1.318.1.1.10.4.2.5.1.4 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The location of the sensor. | |||||||||||||||||||||
| CmemSensorsAlarmGeneration | 1.3.6.1.4.1.318.1.1.10.4.2.5.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Enable or disable alarm generation on this sensor.
| |||||||||||||||||||||
| CmemSensorsTempMaxThresh | 1.3.6.1.4.1.318.1.1.10.4.2.5.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The temperature at which the MEM will generate a maximum temperature threshold violation alarm on this sensor. The temperature scale is based on the memSensorsStatusSysTempUnits OID. | |||||||||||||||||||||
| CmemSensorsTempHighThresh | 1.3.6.1.4.1.318.1.1.10.4.2.5.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The temperature at which the MEM will generate a high temperature threshold violation alarm on this sensor. The temperature scale is based on the memSensorsStatusSysTempUnits OID. | |||||||||||||||||||||
| CmemSensorsTempLowThresh | 1.3.6.1.4.1.318.1.1.10.4.2.5.1.8 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The temperature at which the MEM will generate a low temperature threshold violation alarm on this sensor. The temperature scale is based on the memSensorsStatusSysTempUnits OID. | |||||||||||||||||||||
| CmemSensorsTempMinThresh | 1.3.6.1.4.1.318.1.1.10.4.2.5.1.9 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The temperature at which the MEM will generate a minimum temperature threshold violation alarm on this sensor. The temperature scale is based on the memSensorsStatusSysTempUnits OID. | |||||||||||||||||||||
| CmemSensorsTempThreshHysteresis | 1.3.6.1.4.1.318.1.1.10.4.2.5.1.10 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The change in temperature required to cause a temperature alarm to change from an active to an inactive state. The temperature scale is based on the memSensorsStatusSysTempUnits OID. | |||||||||||||||||||||
| CmemSensorsTempShortDecRateThreshValue | 1.3.6.1.4.1.318.1.1.10.4.2.5.1.11 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The value of the temperature short-term decreasing rate time that will cause an alarm to be generated. The temperature scale is based on the memSensorsStatusSysTempUnits OID. | |||||||||||||||||||||
| CmemSensorsTempShortDecRateThreshTime | 1.3.6.1.4.1.318.1.1.10.4.2.5.1.12 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The time over which the temperature may not decrease beyond the value specified by the temperature short-term decreasing rate threshold value. | |||||||||||||||||||||
| CmemSensorsTempShortIncRateThreshValue | 1.3.6.1.4.1.318.1.1.10.4.2.5.1.13 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The value of the temperature short-term increasing rate time that will cause an alarm to be generated. The temperature scale is based on the memSensorsStatusSysTempUnits OID. | |||||||||||||||||||||
| CmemSensorsTempShortIncRateThreshTime | 1.3.6.1.4.1.318.1.1.10.4.2.5.1.14 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The time over which the temperature may not increase beyond the value specified by the temperature short-term increasing rate threshold value. | |||||||||||||||||||||
| CmemSensorsTempLongDecRateThreshValue | 1.3.6.1.4.1.318.1.1.10.4.2.5.1.15 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The value of the temperature long-term decreasing rate time that will cause an alarm to be generated. The temperature scale is based on the memSensorsStatusSysTempUnits OID. | |||||||||||||||||||||
| CmemSensorsTempLongDecRateThreshTime | 1.3.6.1.4.1.318.1.1.10.4.2.5.1.16 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The time over which the temperature may not decrease beyond the value specified by the temperature long-term decreasing rate threshold value. | |||||||||||||||||||||
| CmemSensorsTempLongIncRateThreshValue | 1.3.6.1.4.1.318.1.1.10.4.2.5.1.17 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The value of the temperature long-term increasing rate time that will cause an alarm to be generated. The temperature scale is based on the memSensorsStatusSysTempUnits OID. | |||||||||||||||||||||
| CmemSensorsTempLongIncRateThreshTime | 1.3.6.1.4.1.318.1.1.10.4.2.5.1.18 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The time over which the temperature may not increase beyond the value specified by the temperature long-term increasing rate threshold value. | |||||||||||||||||||||
| CmemSensorsHumidityMaxThresh | 1.3.6.1.4.1.318.1.1.10.4.2.5.1.19 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The humidity at which the maximum humidity threshold alarm will be generated. | |||||||||||||||||||||
| CmemSensorsHumidityHighThresh | 1.3.6.1.4.1.318.1.1.10.4.2.5.1.20 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The humidity at which the high humidity threshold alarm will be generated. | |||||||||||||||||||||
| CmemSensorsHumidityLowThresh | 1.3.6.1.4.1.318.1.1.10.4.2.5.1.21 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The humidity at which the low humidity threshold alarm will be generated. | |||||||||||||||||||||
| CmemSensorsHumidityMinThresh | 1.3.6.1.4.1.318.1.1.10.4.2.5.1.22 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The humidity at which the minimum humidity threshold alarm will be generated. | |||||||||||||||||||||
| CmemSensorsHumidityThreshHysteresis | 1.3.6.1.4.1.318.1.1.10.4.2.5.1.23 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The change in humidity required to cause an active humidity alarm to change to the inactive state. | |||||||||||||||||||||
| CmemSensorsVoltMaxThresh | 1.3.6.1.4.1.318.1.1.10.4.2.5.1.24 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The voltage in tenths of volts at which the MEM will generate a maximum voltage threshold violation alarm on this sensor. | |||||||||||||||||||||
| CmemSensorsVoltMinThresh | 1.3.6.1.4.1.318.1.1.10.4.2.5.1.25 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The voltage in tenths of volts at which the MEM will generate a minimum voltage threshold violation alarm on this sensor. | |||||||||||||||||||||
| NmemInputs | 1.3.6.1.4.1.318.1.1.10.4.3 | ||||||||||||||||||||
| SmemInputsStatusTableSize | 1.3.6.1.4.1.318.1.1.10.4.3.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the memInputsStatusTable. | |||||||||||||||||||||
| TmemInputsStatusTable | 1.3.6.1.4.1.318.1.1.10.4.3.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting input status information. | |||||||||||||||||||||
| RmemInputsStatusEntry | 1.3.6.1.4.1.318.1.1.10.4.3.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The unit to get data from. | |||||||||||||||||||||
| CmemInputsStatusModuleNumber | 1.3.6.1.4.1.318.1.1.10.4.3.2.1.1 | INTEGER | RO | mandatory | 0 | ||||||||||||||||
column · INTEGER · read-only · mandatory The number of the module that the input is attached to. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmemInputsStatusInputNumber | 1.3.6.1.4.1.318.1.1.10.4.3.2.1.2 | INTEGER | RO | mandatory | 1 | ||||||||||||||||
| CmemInputsStatusInputName | 1.3.6.1.4.1.318.1.1.10.4.3.2.1.3 | DisplayString | RO | mandatory | Brand storing | ||||||||||||||||
| CmemInputsStatusInputLocation | 1.3.6.1.4.1.318.1.1.10.4.3.2.1.4 | DisplayString | RO | mandatory | SCP | ||||||||||||||||
column · DisplayString · read-only · mandatory The location of the input. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmemInputsStatusCurrentState | 1.3.6.1.4.1.318.1.1.10.4.3.2.1.5 | INTEGER | RO | mandatory | inputClosedHighMEM(1) | ||||||||||||||||
column · INTEGER · read-only · mandatory The current state of the input. This OID will return inputStateNotAplicable(4) for analog input types.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmemInputsStatusCurrentAnalogValue | 1.3.6.1.4.1.318.1.1.10.4.3.2.1.6 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The current analog value of the input in the units defined by the user. | |||||||||||||||||||||
| CmemInputsStatusAlarmStatus | 1.3.6.1.4.1.318.1.1.10.4.3.2.1.7 | INTEGER | RO | mandatory | memCritical(3) | ||||||||||||||||
| CmemInputsCommStatus | 1.3.6.1.4.1.318.1.1.10.4.3.2.1.8 | INTEGER | RO | mandatory | commsOK(2) | ||||||||||||||||
column · INTEGER · read-only · mandatory The communications status of the input. This OID is only supported by NBRK0200.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SmemInputsConfigTableSize | 1.3.6.1.4.1.318.1.1.10.4.3.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the memInputsConfigTable. | |||||||||||||||||||||
| TmemInputsConfigTable | 1.3.6.1.4.1.318.1.1.10.4.3.4 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting input configuration information. | |||||||||||||||||||||
| RmemInputsConfigEntry | 1.3.6.1.4.1.318.1.1.10.4.3.4.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The unit to get data from. | |||||||||||||||||||||
| CmemInputsConfigModuleNumber | 1.3.6.1.4.1.318.1.1.10.4.3.4.1.1 | INTEGER | RO | mandatory | 0 | ||||||||||||||||
column · INTEGER · read-only · mandatory The number of the module that the input is attached to. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmemInputsConfigInputNumber | 1.3.6.1.4.1.318.1.1.10.4.3.4.1.2 | INTEGER | RO | mandatory | 1 | ||||||||||||||||
| CmemInputName | 1.3.6.1.4.1.318.1.1.10.4.3.4.1.3 | DisplayString | RW | mandatory | NSA Hoofdalarm | ||||||||||||||||
| CmemInputLocation | 1.3.6.1.4.1.318.1.1.10.4.3.4.1.4 | DisplayString | RW | mandatory | SCP | ||||||||||||||||
column · DisplayString · read-write · mandatory The location of the input. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmemInputType | 1.3.6.1.4.1.318.1.1.10.4.3.4.1.5 | INTEGER | RW | mandatory | dryContact(2) | ||||||||||||||||
| CmemInputAlarmGeneration | 1.3.6.1.4.1.318.1.1.10.4.3.4.1.6 | INTEGER | RW | mandatory | enabled(2) | ||||||||||||||||
| CmemInputNormalState | 1.3.6.1.4.1.318.1.1.10.4.3.4.1.7 | INTEGER | RW | mandatory | inputClosedHighMEM(1) | ||||||||||||||||
column · INTEGER · read-write · mandatory Defines the normal (no alarm) state of the input.
| |||||||||||||||||||||
| CmemInputAbnormalSeverity | 1.3.6.1.4.1.318.1.1.10.4.3.4.1.8 | INTEGER | RW | mandatory | inputSeveritysevere(3) | ||||||||||||||||
column · INTEGER · read-write · mandatory Defines the severity of the event that is associated with the abnormal state of the input. This OID will return inputSeverityNotApplicable(4) for analog input types.
| |||||||||||||||||||||
| CmemInputNumberCalibrationPoints | 1.3.6.1.4.1.318.1.1.10.4.3.4.1.9 | INTEGER | RW | mandatory | -1 | ||||||||||||||||
column · INTEGER · read-write · mandatory The number of calibration points that are required for this input. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmemInputAnalogCalibrationPoint1 | 1.3.6.1.4.1.318.1.1.10.4.3.4.1.10 | DisplayString | RW | mandatory | | ||||||||||||||||
column · DisplayString · read-write · mandatory The electrical value that the input sensor will measure at the first calibration point. This OID is relevant only for inputs configured as analog type (ma or V). Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmemInputAnalogCalibrationPoint2 | 1.3.6.1.4.1.318.1.1.10.4.3.4.1.11 | DisplayString | RW | mandatory | | ||||||||||||||||
column · DisplayString · read-write · mandatory The electrical value that the input sensor will measure at the second calibration point. This OID is relevant only for inputs configured as analog type (ma or V). Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmemInputAnalogCalibrationPoint3 | 1.3.6.1.4.1.318.1.1.10.4.3.4.1.12 | DisplayString | RW | mandatory | | ||||||||||||||||
column · DisplayString · read-write · mandatory The electrical value that the input sensor will measure at the third calibration point. This OID is relevant only for inputs configured as analog type (ma or V). Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmemInputAnalogCalibrationPoint4 | 1.3.6.1.4.1.318.1.1.10.4.3.4.1.13 | DisplayString | RW | mandatory | | ||||||||||||||||
column · DisplayString · read-write · mandatory The electrical value that the input sensor will measure at the fourth calibration point. This OID is relevant only for inputs configured as analog type (ma or V). Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmemInputAnalogCalibrationPoint5 | 1.3.6.1.4.1.318.1.1.10.4.3.4.1.14 | DisplayString | RW | mandatory | | ||||||||||||||||
column · DisplayString · read-write · mandatory The electrical value that the input sensor will measure at the fifth calibration point. This OID is relevant only for inputs configured as analog type (ma or V). Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmemInputAnalogCalibrationPoint1Value | 1.3.6.1.4.1.318.1.1.10.4.3.4.1.15 | DisplayString | RW | mandatory | | ||||||||||||||||
column · DisplayString · read-write · mandatory The value of the input, in units of measure defined by the user, that corresponds to the current setting at the first calibration point. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmemInputAnalogCalibrationPoint2Value | 1.3.6.1.4.1.318.1.1.10.4.3.4.1.16 | DisplayString | RW | mandatory | | ||||||||||||||||
column · DisplayString · read-write · mandatory The value of the input, in units of measure defined by the user, that corresponds to the current setting at the second calibration point. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmemInputAnalogCalibrationPoint3Value | 1.3.6.1.4.1.318.1.1.10.4.3.4.1.17 | DisplayString | RW | mandatory | | ||||||||||||||||
column · DisplayString · read-write · mandatory The value of the input, in units of measure defined by the user, that corresponds to the current setting at the third calibration point. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmemInputAnalogCalibrationPoint4Value | 1.3.6.1.4.1.318.1.1.10.4.3.4.1.18 | DisplayString | RW | mandatory | | ||||||||||||||||
column · DisplayString · read-write · mandatory The value of the input, in units of measure defined by the user, that corresponds to the current setting at the fourth calibration point. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmemInputAnalogCalibrationPoint5Value | 1.3.6.1.4.1.318.1.1.10.4.3.4.1.19 | DisplayString | RW | mandatory | | ||||||||||||||||
column · DisplayString · read-write · mandatory The value of the input, in units of measure defined by the user, that corresponds to the current setting at the fifth calibration point. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmemInputAnalogMeasurementUnits | 1.3.6.1.4.1.318.1.1.10.4.3.4.1.20 | DisplayString | RW | mandatory | | ||||||||||||||||
column · DisplayString · read-write · mandatory The units of measure to be used for this input. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmemInputAnalogMaxThresh | 1.3.6.1.4.1.318.1.1.10.4.3.4.1.21 | DisplayString | RW | mandatory | | ||||||||||||||||
column · DisplayString · read-write · mandatory The input value at which a maximum threshold violation alarm will be generated on this input. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmemInputAnalogHighThresh | 1.3.6.1.4.1.318.1.1.10.4.3.4.1.22 | DisplayString | RW | mandatory | | ||||||||||||||||
column · DisplayString · read-write · mandatory The input value at which a high threshold violation alarm will be generated on this input. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmemInputAnalogLowThresh | 1.3.6.1.4.1.318.1.1.10.4.3.4.1.23 | DisplayString | RW | mandatory | | ||||||||||||||||
column · DisplayString · read-write · mandatory The input value at which a low threshold violation alarm will be generated on this input. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmemInputAnalogMinThresh | 1.3.6.1.4.1.318.1.1.10.4.3.4.1.24 | DisplayString | RW | mandatory | | ||||||||||||||||
column · DisplayString · read-write · mandatory The input value at which a minimum threshold violation alarm will be generated on this input. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CmemInputAnalogThreshHysteresis | 1.3.6.1.4.1.318.1.1.10.4.3.4.1.25 | DisplayString | RW | mandatory | | ||||||||||||||||
column · DisplayString · read-write · mandatory The change in value required to cause an alarm on this input to change from active to inactive. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NmemOutputs | 1.3.6.1.4.1.318.1.1.10.4.4 | ||||||||||||||||||||
| SmemOutputStatusTableSize | 1.3.6.1.4.1.318.1.1.10.4.4.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the memOutputStatusTable. | |||||||||||||||||||||
| TmemOutputStatusTable | 1.3.6.1.4.1.318.1.1.10.4.4.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting output status information. | |||||||||||||||||||||
| RmemOutputStatusEntry | 1.3.6.1.4.1.318.1.1.10.4.4.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The unit to get data from. | |||||||||||||||||||||
| CmemOutputStatusModuleNumber | 1.3.6.1.4.1.318.1.1.10.4.4.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The number of the module that the output is attached to. | |||||||||||||||||||||
| CmemOutputStatusOutputNumber | 1.3.6.1.4.1.318.1.1.10.4.4.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The number of this output on the module. | |||||||||||||||||||||
| CmemOutputStatusOutputName | 1.3.6.1.4.1.318.1.1.10.4.4.2.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The output name. | |||||||||||||||||||||
| CmemOutputStatusOutputLocation | 1.3.6.1.4.1.318.1.1.10.4.4.2.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The location of the output. | |||||||||||||||||||||
| CmemOutputStatusCurrentState | 1.3.6.1.4.1.318.1.1.10.4.4.2.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The state of the output.
| |||||||||||||||||||||
| CmemOutputStatusAlarmState | 1.3.6.1.4.1.318.1.1.10.4.4.2.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The alarm state of the output.
| |||||||||||||||||||||
| SmemOutputConfigTableSize | 1.3.6.1.4.1.318.1.1.10.4.4.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the memOutputConfigTable. | |||||||||||||||||||||
| TmemOutputConfigTable | 1.3.6.1.4.1.318.1.1.10.4.4.4 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting output configuration information. | |||||||||||||||||||||
| RmemOutputConfigEntry | 1.3.6.1.4.1.318.1.1.10.4.4.4.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The unit to get data from. | |||||||||||||||||||||
| CmemOutputConfigModuleNumber | 1.3.6.1.4.1.318.1.1.10.4.4.4.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The number of the module that the output is attached to. | |||||||||||||||||||||
| CmemOutputConfigOutputNumber | 1.3.6.1.4.1.318.1.1.10.4.4.4.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The number of this output on the module. | |||||||||||||||||||||
| CmemOutputName | 1.3.6.1.4.1.318.1.1.10.4.4.4.1.3 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The name of the output. | |||||||||||||||||||||
| CmemOutputLocation | 1.3.6.1.4.1.318.1.1.10.4.4.4.1.4 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The location of the output. | |||||||||||||||||||||
| CmemOutputNormalState | 1.3.6.1.4.1.318.1.1.10.4.4.4.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The state of the output that will not generate an alarm.
| |||||||||||||||||||||
| CmemOutputAction | 1.3.6.1.4.1.318.1.1.10.4.4.4.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Manual control actions for the output. SNMP get command will return the state of the output, SNMP set of this OID controls the output.
| |||||||||||||||||||||
| NmemOutlets | 1.3.6.1.4.1.318.1.1.10.4.5 | ||||||||||||||||||||
| SmemOutletStatusTableSize | 1.3.6.1.4.1.318.1.1.10.4.5.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the memOutletStatusTable. | |||||||||||||||||||||
| TmemOutletStatusTable | 1.3.6.1.4.1.318.1.1.10.4.5.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting outlet status information. | |||||||||||||||||||||
| RmemOutletStatusEntry | 1.3.6.1.4.1.318.1.1.10.4.5.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The unit to get data from. | |||||||||||||||||||||
| CmemOutletStatusModuleNumber | 1.3.6.1.4.1.318.1.1.10.4.5.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The number of the module that the outlet is attached to. | |||||||||||||||||||||
| CmemOutletStatusOutletNumber | 1.3.6.1.4.1.318.1.1.10.4.5.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The number of this outlet on the module. | |||||||||||||||||||||
| CmemOutletStatusOutletName | 1.3.6.1.4.1.318.1.1.10.4.5.2.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The outlet name. | |||||||||||||||||||||
| CmemOutletStatusOutletLocation | 1.3.6.1.4.1.318.1.1.10.4.5.2.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The location of the outlet. | |||||||||||||||||||||
| CmemOutletStatusCurrentState | 1.3.6.1.4.1.318.1.1.10.4.5.2.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The state of the outlet.
| |||||||||||||||||||||
| CmemOutletStatusAlarmState | 1.3.6.1.4.1.318.1.1.10.4.5.2.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The alarm state of the outlet.
| |||||||||||||||||||||
| SmemOutletConfigTableSize | 1.3.6.1.4.1.318.1.1.10.4.5.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the memOutletConfigTable. | |||||||||||||||||||||
| TmemOutletConfigTable | 1.3.6.1.4.1.318.1.1.10.4.5.4 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting outlet configuration information. | |||||||||||||||||||||
| RmemOutletConfigEntry | 1.3.6.1.4.1.318.1.1.10.4.5.4.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The unit to get data from. | |||||||||||||||||||||
| CmemOutletConfigModuleNumber | 1.3.6.1.4.1.318.1.1.10.4.5.4.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The number of the module that the Outlet is attached to. | |||||||||||||||||||||
| CmemOutletConfigOutletNumber | 1.3.6.1.4.1.318.1.1.10.4.5.4.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The number of this Outlet on the module. | |||||||||||||||||||||
| CmemOutletName | 1.3.6.1.4.1.318.1.1.10.4.5.4.1.3 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The name of the Outlet. | |||||||||||||||||||||
| CmemOutletLocation | 1.3.6.1.4.1.318.1.1.10.4.5.4.1.4 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The location of the Outlet. | |||||||||||||||||||||
| CmemOutletNormalState | 1.3.6.1.4.1.318.1.1.10.4.5.4.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The state of the Outlet that will not generate an alarm.
| |||||||||||||||||||||
| CmemOutletAction | 1.3.6.1.4.1.318.1.1.10.4.5.4.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Manual control actions for the Outlet. Get displays state of outlet, set controls outlet.
| |||||||||||||||||||||
| NmemBeacons | 1.3.6.1.4.1.318.1.1.10.4.6 | ||||||||||||||||||||
| SmemBeaconStatusTableSize | 1.3.6.1.4.1.318.1.1.10.4.6.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the memBeaconStatusTable. | |||||||||||||||||||||
| TmemBeaconStatusTable | 1.3.6.1.4.1.318.1.1.10.4.6.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting beacon status information. | |||||||||||||||||||||
| RmemBeaconStatusEntry | 1.3.6.1.4.1.318.1.1.10.4.6.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The unit to get data from. | |||||||||||||||||||||
| CmemBeaconStatusModuleNumber | 1.3.6.1.4.1.318.1.1.10.4.6.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The number of the module that the beacon is attached to. | |||||||||||||||||||||
| CmemBeaconStatusBeaconNumber | 1.3.6.1.4.1.318.1.1.10.4.6.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The number of this beacon on the module. | |||||||||||||||||||||
| CmemBeaconStatusBeaconName | 1.3.6.1.4.1.318.1.1.10.4.6.2.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The beacon name. | |||||||||||||||||||||
| CmemBeaconStatusBeaconLocation | 1.3.6.1.4.1.318.1.1.10.4.6.2.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The location of the beacon. | |||||||||||||||||||||
| CmemBeaconStatusCurrentState | 1.3.6.1.4.1.318.1.1.10.4.6.2.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The state of the beacon.
| |||||||||||||||||||||
| CmemBeaconStatusAlarmState | 1.3.6.1.4.1.318.1.1.10.4.6.2.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The alarm state of the beacon.
| |||||||||||||||||||||
| SmemBeaconConfigTableSize | 1.3.6.1.4.1.318.1.1.10.4.6.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the memBeaconConfigTable. | |||||||||||||||||||||
| TmemBeaconConfigTable | 1.3.6.1.4.1.318.1.1.10.4.6.4 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting beacon configuration information. | |||||||||||||||||||||
| RmemBeaconConfigEntry | 1.3.6.1.4.1.318.1.1.10.4.6.4.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The unit to get data from. | |||||||||||||||||||||
| CmemBeaconConfigModuleNumber | 1.3.6.1.4.1.318.1.1.10.4.6.4.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The number of the module that the beacon is attached to. | |||||||||||||||||||||
| CmemBeaconConfigBeaconNumber | 1.3.6.1.4.1.318.1.1.10.4.6.4.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The number of this beacon on the module. | |||||||||||||||||||||
| CmemBeaconConfigName | 1.3.6.1.4.1.318.1.1.10.4.6.4.1.3 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The name of the beacon. | |||||||||||||||||||||
| CmemBeaconConfigLocation | 1.3.6.1.4.1.318.1.1.10.4.6.4.1.4 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The location of the beacon. | |||||||||||||||||||||
| CmemBeaconAction | 1.3.6.1.4.1.318.1.1.10.4.6.4.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Control action (on/off) for the beacon. Setting this OID will turn the beacon on/off. Getting this OID will respond with the current state.
| |||||||||||||||||||||
| NmemInputStateSensors | 1.3.6.1.4.1.318.1.1.10.4.7 | ||||||||||||||||||||
| SmemSmokeSensorStatusTableSize | 1.3.6.1.4.1.318.1.1.10.4.7.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the memSmokeSensorStatusTable. | |||||||||||||||||||||
| TmemSmokeSensorStatusTable | 1.3.6.1.4.1.318.1.1.10.4.7.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for the access of individual sensors. | |||||||||||||||||||||
| RmemSmokeSensorStatusEntry | 1.3.6.1.4.1.318.1.1.10.4.7.2.1 | NA | mandatory | ||||||||||||||||||
| CmemSmokeSensorStatusModuleIndex | 1.3.6.1.4.1.318.1.1.10.4.7.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the module entry. | |||||||||||||||||||||
| CmemSmokeSensorStatusSensorIndex | 1.3.6.1.4.1.318.1.1.10.4.7.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the sensor entry. | |||||||||||||||||||||
| CmemSmokeSensorStatusSensorName | 1.3.6.1.4.1.318.1.1.10.4.7.2.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The user defined name of the smoke sensor. | |||||||||||||||||||||
| CmemSmokeSensorStatusSensorLocation | 1.3.6.1.4.1.318.1.1.10.4.7.2.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The user defined location of the smoke sensor. | |||||||||||||||||||||
| CmemSmokeSensorStatusSensorState | 1.3.6.1.4.1.318.1.1.10.4.7.2.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The state of the smoke sensor. smokeDetected (1) indicates there is smoke. noSmoke (2) indicates there is no smoke. unknown (3) indicates the state is unknown.
| |||||||||||||||||||||
| CmemSmokeSensorStatusSensorSeverity | 1.3.6.1.4.1.318.1.1.10.4.7.2.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The severity of the alarm that will be triggered when the smoke sensor is activated. The alarms can be critical(1), warning(2) or informational(3).
| |||||||||||||||||||||
| CmemSmokeStatusAlarmStatus | 1.3.6.1.4.1.318.1.1.10.4.7.2.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The alarm status of the smoke sensor.
| |||||||||||||||||||||
| CmemSmokeSensorCommStatus | 1.3.6.1.4.1.318.1.1.10.4.7.2.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The communication status of the smoke sensor.
| |||||||||||||||||||||
| SmemVibrationSensorStatusTableSize | 1.3.6.1.4.1.318.1.1.10.4.7.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the memVibrationSensorStatusTable. | |||||||||||||||||||||
| TmemVibrationSensorStatusTable | 1.3.6.1.4.1.318.1.1.10.4.7.4 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for the access of individual sensors. | |||||||||||||||||||||
| RmemVibrationSensorStatusEntry | 1.3.6.1.4.1.318.1.1.10.4.7.4.1 | NA | mandatory | ||||||||||||||||||
| CmemVibrationSensorStatusModuleIndex | 1.3.6.1.4.1.318.1.1.10.4.7.4.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the sensor module entry. | |||||||||||||||||||||
| CmemVibrationSensorStatusSensorIndex | 1.3.6.1.4.1.318.1.1.10.4.7.4.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the sensor entry. | |||||||||||||||||||||
| CmemVibrationSensorStatusSensorName | 1.3.6.1.4.1.318.1.1.10.4.7.4.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The user defined name of the vibration sensor. | |||||||||||||||||||||
| CmemVibrationSensorStatusSensorLocation | 1.3.6.1.4.1.318.1.1.10.4.7.4.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The user defined location of the vibration sensor. | |||||||||||||||||||||
| CmemVibrationSensorStatusSensorState | 1.3.6.1.4.1.318.1.1.10.4.7.4.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The state of the vibration sensor. vibrationDetected (1) indicates there is vibration. noVibration (2) indicates there is no vibration. unknown (3) indicates the state is unknown.
| |||||||||||||||||||||
| CmemVibrationSensorStatusSensorSeverity | 1.3.6.1.4.1.318.1.1.10.4.7.4.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The severity of the alarm that will be triggered when the vibration sensor is activated. The alarms can be critical(1), warning(2) or informational(3).
| |||||||||||||||||||||
| CmemVibrationStatusAlarmStatus | 1.3.6.1.4.1.318.1.1.10.4.7.4.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The alarm status of the vibration sensor.
| |||||||||||||||||||||
| CmemVibrationSensorCommStatus | 1.3.6.1.4.1.318.1.1.10.4.7.4.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The communication status of the vibration sensor.
| |||||||||||||||||||||
| SmemFluidSensorStatusTableSize | 1.3.6.1.4.1.318.1.1.10.4.7.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the memFluidSensorStatusTable. | |||||||||||||||||||||
| TmemFluidSensorStatusTable | 1.3.6.1.4.1.318.1.1.10.4.7.6 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for access of individual sensors. | |||||||||||||||||||||
| RmemFluidSensorStatusEntry | 1.3.6.1.4.1.318.1.1.10.4.7.6.1 | NA | mandatory | ||||||||||||||||||
| CmemFluidSensorStatusModuleIndex | 1.3.6.1.4.1.318.1.1.10.4.7.6.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the sensor module entry. | |||||||||||||||||||||
| CmemFluidSensorStatusSensorIndex | 1.3.6.1.4.1.318.1.1.10.4.7.6.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the sensor entry. | |||||||||||||||||||||
| CmemFluidSensorStatusSensorName | 1.3.6.1.4.1.318.1.1.10.4.7.6.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The user defined name of the fluid sensor. | |||||||||||||||||||||
| CmemFluidSensorStatusSensorLocation | 1.3.6.1.4.1.318.1.1.10.4.7.6.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The user defined location of the fluid sensor. | |||||||||||||||||||||
| CmemFluidSensorStatusSensorState | 1.3.6.1.4.1.318.1.1.10.4.7.6.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The state of the fluid sensor. fluidDetected (1) indicates there is fluid leak. noFluid (2) indicates there is no fluid leak. unknown (3) indicates the state is unknown.
| |||||||||||||||||||||
| CmemFluidSensorStatusSensorSeverity | 1.3.6.1.4.1.318.1.1.10.4.7.6.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The severity of the alarm that will be triggered when the fluid sensor is activated. The alarms can be critical(1), warning(2) or informational(3).
| |||||||||||||||||||||
| CmemFluidStatusAlarmStatus | 1.3.6.1.4.1.318.1.1.10.4.7.6.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The alarm status of the fluid sensor.
| |||||||||||||||||||||
| CmemFluidSensorCommStatus | 1.3.6.1.4.1.318.1.1.10.4.7.6.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The communication status of the fluid sensor.
| |||||||||||||||||||||
| SmemDoorSensorStatusTableSize | 1.3.6.1.4.1.318.1.1.10.4.7.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the memDoorSensorStatusTable. | |||||||||||||||||||||
| TmemDoorSensorStatusTable | 1.3.6.1.4.1.318.1.1.10.4.7.8 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for the access of individual sensors. | |||||||||||||||||||||
| RmemDoorSensorStatusEntry | 1.3.6.1.4.1.318.1.1.10.4.7.8.1 | NA | mandatory | ||||||||||||||||||
| CmemDoorSensorStatusModuleIndex | 1.3.6.1.4.1.318.1.1.10.4.7.8.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the sensor module entry. | |||||||||||||||||||||
| CmemDoorSensorStatusSensorIndex | 1.3.6.1.4.1.318.1.1.10.4.7.8.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the sensor entry. | |||||||||||||||||||||
| CmemDoorSensorStatusSensorName | 1.3.6.1.4.1.318.1.1.10.4.7.8.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The user defined name of the door sensor. | |||||||||||||||||||||
| CmemDoorSensorStatusSensorLocation | 1.3.6.1.4.1.318.1.1.10.4.7.8.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The user defined location of the door sensor. | |||||||||||||||||||||
| CmemDoorSensorStatusSensorState | 1.3.6.1.4.1.318.1.1.10.4.7.8.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The state of the door sensor. open (1) indicates door open. closed (2) indicates door closed. unknown (3) indicates the state is unknown.
| |||||||||||||||||||||
| CmemDoorSensorStatusSensorSeverity | 1.3.6.1.4.1.318.1.1.10.4.7.8.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The severity of the alarm that will be triggered when the door sensor is activated. The alarms can be critical(1), warning(2) or informational(3).
| |||||||||||||||||||||
| CmemDoorStatusAlarmStatus | 1.3.6.1.4.1.318.1.1.10.4.7.8.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The alarm status of the door sensor.
| |||||||||||||||||||||
| CmemDoorSensorCommStatus | 1.3.6.1.4.1.318.1.1.10.4.7.8.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The communication status of the door sensor.
| |||||||||||||||||||||
| TmemSmokeSensorConfigTable | 1.3.6.1.4.1.318.1.1.10.4.7.9 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for the configuration of individual sensors. | |||||||||||||||||||||
| RmemSmokeSensorConfigEntry | 1.3.6.1.4.1.318.1.1.10.4.7.9.1 | NA | mandatory | ||||||||||||||||||
| CmemSmokeSensorConfigSensorModuleIndex | 1.3.6.1.4.1.318.1.1.10.4.7.9.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the sensor module entry. | |||||||||||||||||||||
| CmemSmokeSensorConfigSensorIndex | 1.3.6.1.4.1.318.1.1.10.4.7.9.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the sensor entry. | |||||||||||||||||||||
| CmemSmokeSensorConfigSensorName | 1.3.6.1.4.1.318.1.1.10.4.7.9.1.3 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The user defined name of the smoke sensor. | |||||||||||||||||||||
| CmemSmokeSensorConfigSensorLocation | 1.3.6.1.4.1.318.1.1.10.4.7.9.1.4 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The user defined location of the smoke sensor. | |||||||||||||||||||||
| CmemSmokeSensorConfigSensorSeverity | 1.3.6.1.4.1.318.1.1.10.4.7.9.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The severity of the alarm that will be triggered when the smoke sensor is activated. The alarms can be critical(1), warning(2) or informational(3).
| |||||||||||||||||||||
| CmemSmokeSensorConfigAlarmGeneration | 1.3.6.1.4.1.318.1.1.10.4.7.9.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Enable or disable alarm generation on this input.
| |||||||||||||||||||||
| TmemVibrationSensorConfigTable | 1.3.6.1.4.1.318.1.1.10.4.7.10 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for the configuration of individual sensors. | |||||||||||||||||||||
| RmemVibrationSensorConfigEntry | 1.3.6.1.4.1.318.1.1.10.4.7.10.1 | NA | mandatory | ||||||||||||||||||
| CmemVibrationSensorModuleConfigIndex | 1.3.6.1.4.1.318.1.1.10.4.7.10.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the sensor module entry. | |||||||||||||||||||||
| CmemVibrationSensorConfigSensorIndex | 1.3.6.1.4.1.318.1.1.10.4.7.10.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the sensor entry. | |||||||||||||||||||||
| CmemVibrationSensorConfigSensorName | 1.3.6.1.4.1.318.1.1.10.4.7.10.1.3 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The user defined name of the vibration sensor. | |||||||||||||||||||||
| CmemVibrationSensorConfigSensorLocation | 1.3.6.1.4.1.318.1.1.10.4.7.10.1.4 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The user defined location of the vibration sensor. | |||||||||||||||||||||
| CmemVibrationSensorConfigSensorSeverity | 1.3.6.1.4.1.318.1.1.10.4.7.10.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The severity of the alarm that will be triggered when the vibration sensor is activated. The alarms can be critical(1), warning(2) or informational(3).
| |||||||||||||||||||||
| CmemVibrationSensorConfigAlarmGeneration | 1.3.6.1.4.1.318.1.1.10.4.7.10.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Enable or disable alarm generation on this input.
| |||||||||||||||||||||
| TmemFluidSensorConfigTable | 1.3.6.1.4.1.318.1.1.10.4.7.11 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for the configuration of individual sensors. | |||||||||||||||||||||
| RmemFluidSensorConfigEntry | 1.3.6.1.4.1.318.1.1.10.4.7.11.1 | NA | mandatory | ||||||||||||||||||
| CmemFluidSensorModuleConfigIndex | 1.3.6.1.4.1.318.1.1.10.4.7.11.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the sensor module entry. | |||||||||||||||||||||
| CmemFluidSensorConfigSensorIndex | 1.3.6.1.4.1.318.1.1.10.4.7.11.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the sensor entry. | |||||||||||||||||||||
| CmemFluidSensorConfigSensorName | 1.3.6.1.4.1.318.1.1.10.4.7.11.1.3 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The user defined name of the fluid sensor. | |||||||||||||||||||||
| CmemFluidSensorConfigSensorLocation | 1.3.6.1.4.1.318.1.1.10.4.7.11.1.4 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The user defined location of the fluid sensor. | |||||||||||||||||||||
| CmemFluidSensorConfigSensorSeverity | 1.3.6.1.4.1.318.1.1.10.4.7.11.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The severity of the alarm that will be triggered when the fluid sensor is activated. The alarms can be critical(1), warning(2) or informational(3).
| |||||||||||||||||||||
| CmemFluidSensorConfigAlarmGeneration | 1.3.6.1.4.1.318.1.1.10.4.7.11.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Enable or disable alarm generation on this input.
| |||||||||||||||||||||
| TmemDoorSensorConfigTable | 1.3.6.1.4.1.318.1.1.10.4.7.12 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for the configuration of individual sensors. | |||||||||||||||||||||
| RmemDoorSensorConfigEntry | 1.3.6.1.4.1.318.1.1.10.4.7.12.1 | NA | mandatory | ||||||||||||||||||
| CmemDoorSensorModuleConfigIndex | 1.3.6.1.4.1.318.1.1.10.4.7.12.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the sensor module entry. | |||||||||||||||||||||
| CmemDoorSensorConfigSensorIndex | 1.3.6.1.4.1.318.1.1.10.4.7.12.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the sensor entry. | |||||||||||||||||||||
| CmemDoorSensorConfigSensorName | 1.3.6.1.4.1.318.1.1.10.4.7.12.1.3 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The user defined name of the door sensor. | |||||||||||||||||||||
| CmemDoorSensorConfigSensorLocation | 1.3.6.1.4.1.318.1.1.10.4.7.12.1.4 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The user defined location of the door sensor. | |||||||||||||||||||||
| CmemDoorSensorConfigSensorSeverity | 1.3.6.1.4.1.318.1.1.10.4.7.12.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The severity of the alarm that will be triggered when the door sensor is activated. The alarms can be critical(1), warning(2) or informational(3).
| |||||||||||||||||||||
| CmemDoorSensorConfigAlarmGeneration | 1.3.6.1.4.1.318.1.1.10.4.7.12.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Enable or disable alarm generation on this input.
| |||||||||||||||||||||
| SmemLeakRopeStatusTableSize | 1.3.6.1.4.1.318.1.1.10.4.7.13 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the memLeakRopeStatusTable. | |||||||||||||||||||||
| TmemLeakRopeStatusTable | 1.3.6.1.4.1.318.1.1.10.4.7.14 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for access of individual leak ropes. | |||||||||||||||||||||
| RmemLeakRopeStatusEntry | 1.3.6.1.4.1.318.1.1.10.4.7.14.1 | NA | mandatory | ||||||||||||||||||
| CmemLeakRopeStatusModuleIndex | 1.3.6.1.4.1.318.1.1.10.4.7.14.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of the leak rope entry. | |||||||||||||||||||||
| CmemLeakRopeStatusSensorIndex | 1.3.6.1.4.1.318.1.1.10.4.7.14.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of the leak rope sensor. | |||||||||||||||||||||
| CmemLeakRopeStatusSensorName | 1.3.6.1.4.1.318.1.1.10.4.7.14.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The user defined name of the leak rope sensor. | |||||||||||||||||||||
| CmemLeakRopeStatusSensorLocation | 1.3.6.1.4.1.318.1.1.10.4.7.14.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The user-defined location of the leak rope sensor. | |||||||||||||||||||||
| CmemLeakRopeStatusSensorState | 1.3.6.1.4.1.318.1.1.10.4.7.14.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The state of the leak rope sensor. noleak (1) indicates there is no leak. leakdetected (2) indicates there is a detected leak. unknown (3) indicates the state is unknown.
| |||||||||||||||||||||
| CmemLeakRopeStatusSensorSeverity | 1.3.6.1.4.1.318.1.1.10.4.7.14.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The severity of the alarm that will be triggered when the leak rope sensor is activated. The alarms can be critical(1), warning(2) or informational(3).
| |||||||||||||||||||||
| CmemLeakRopeAlarmStatus | 1.3.6.1.4.1.318.1.1.10.4.7.14.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The alarm status of the rope link sensor.
| |||||||||||||||||||||
| CmemLeakRopeCommStatus | 1.3.6.1.4.1.318.1.1.10.4.7.14.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The communication status of the rope link sensor.
| |||||||||||||||||||||
| TmemLeakRopeConfigTable | 1.3.6.1.4.1.318.1.1.10.4.7.15 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for the configuration of individual leak ropes. | |||||||||||||||||||||
| RmemLeakRopeConfigEntry | 1.3.6.1.4.1.318.1.1.10.4.7.15.1 | NA | mandatory | ||||||||||||||||||
| CmemLeakRopeConfigModuleIndex | 1.3.6.1.4.1.318.1.1.10.4.7.15.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of the leak rope module entry. | |||||||||||||||||||||
| CmemLeakRopeConfigSensorIndex | 1.3.6.1.4.1.318.1.1.10.4.7.15.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of the leak rope sensor entry. | |||||||||||||||||||||
| CmemLeakRopeConfigSensorName | 1.3.6.1.4.1.318.1.1.10.4.7.15.1.3 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The user-defined name of the leak rope sensor. | |||||||||||||||||||||
| CmemLeakRopeConfigSensorLocation | 1.3.6.1.4.1.318.1.1.10.4.7.15.1.4 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The user-defined location of the leak rope sensor. | |||||||||||||||||||||
| CmemLeakRopeConfigSensorSeverity | 1.3.6.1.4.1.318.1.1.10.4.7.15.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The severity level of the leak rope sensor.
| |||||||||||||||||||||
| CmemLeakRopeConfigAlarmGeneration | 1.3.6.1.4.1.318.1.1.10.4.7.15.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Enable or disable alarm generation on this input.
| |||||||||||||||||||||
| NenvWireless | 1.3.6.1.4.1.318.1.1.10.5 | ||||||||||||||||||||
| NwirelessSensorStatus | 1.3.6.1.4.1.318.1.1.10.5.1 | ||||||||||||||||||||
| TwirelessSensorStatusTable | 1.3.6.1.4.1.318.1.1.10.5.1.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for the access of individual sensors. | |||||||||||||||||||||
| RwirelessSensorStatusEntry | 1.3.6.1.4.1.318.1.1.10.5.1.1.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory A list of wireless sensor status table entries. | |||||||||||||||||||||
| CwirelessSensorStatusIndex | 1.3.6.1.4.1.318.1.1.10.5.1.1.1.1 | INTEGER | RO | mandatory | 1 | ||||||||||||||||
column · INTEGER · read-only · mandatory The index to the sensor entry. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CwirelessSensorStatusExtAddr | 1.3.6.1.4.1.318.1.1.10.5.1.1.1.2 | DisplayString | RO | mandatory | 28298600009a5705
00 | ||||||||||||||||
column · DisplayString · read-only · mandatory The extended address is the combination of the unique 10 byte MAC address of the sensor concatenated with its short address. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CwirelessSensorStatusName | 1.3.6.1.4.1.318.1.1.10.5.1.1.1.3 | DisplayString | RO | mandatory | THUM-01-A3-F | ||||||||||||||||
column · DisplayString · read-only · mandatory The name of the wireless sensor. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CwirelessSensorStatusAlarmGeneration | 1.3.6.1.4.1.318.1.1.10.5.1.1.1.4 | INTEGER | RO | mandatory | enabled(1) | ||||||||||||||||
column · INTEGER · read-only · mandatory Indicates whether alarm generation is enabled or disabled for the sensor.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CwirelessSensorStatusTemperature | 1.3.6.1.4.1.318.1.1.10.5.1.1.1.5 | INTEGER | RO | mandatory | 238 | ||||||||||||||||
column · INTEGER · read-only · mandatory The current temperature are displayed in tenths of degrees in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). Example values from LibreNMS test devices
| |||||||||||||||||||||
| CwirelessSensorStatusHighTempThresh | 1.3.6.1.4.1.318.1.1.10.5.1.1.1.6 | INTEGER | RO | mandatory | 280 | ||||||||||||||||
column · INTEGER · read-only · mandatory Values are displayed in tenths of degrees in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). Example values from LibreNMS test devices
| |||||||||||||||||||||
| CwirelessSensorStatusLowTempThresh | 1.3.6.1.4.1.318.1.1.10.5.1.1.1.7 | INTEGER | RO | mandatory | 160 | ||||||||||||||||
column · INTEGER · read-only · mandatory Values are displayed in tenths of degrees in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). Example values from LibreNMS test devices
| |||||||||||||||||||||
| CwirelessSensorStatusHumidity | 1.3.6.1.4.1.318.1.1.10.5.1.1.1.8 | INTEGER | RO | mandatory | 45 | ||||||||||||||||
column · INTEGER · read-only · mandatory Values are represented in whole number percentage. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CwirelessSensorStatusHighHumidityThresh | 1.3.6.1.4.1.318.1.1.10.5.1.1.1.9 | INTEGER | RO | mandatory | 80 | ||||||||||||||||
column · INTEGER · read-only · mandatory Values are represented in whole number percentage. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CwirelessSensorStatusLowHumidityThresh | 1.3.6.1.4.1.318.1.1.10.5.1.1.1.10 | INTEGER | RO | mandatory | 15 | ||||||||||||||||
column · INTEGER · read-only · mandatory Values are represented in whole number percentage. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CwirelessSensorStatusCommStatus | 1.3.6.1.4.1.318.1.1.10.5.1.1.1.11 | INTEGER | RO | mandatory | active(1) | ||||||||||||||||
column · INTEGER · read-only · mandatory The communication status of the wireless sensor. inactive(0) indicates sensor is in the wireless network but not sending information. active(1) indicates wireless sensor is live and sending information.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CwirelessSensorStatusMaxTempThresh | 1.3.6.1.4.1.318.1.1.10.5.1.1.1.12 | INTEGER | RO | mandatory | 320 | ||||||||||||||||
column · INTEGER · read-only · mandatory Values are displayed in tenths of degrees in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). Example values from LibreNMS test devices
| |||||||||||||||||||||
| CwirelessSensorStatusMinTempThresh | 1.3.6.1.4.1.318.1.1.10.5.1.1.1.13 | INTEGER | RO | mandatory | 140 | ||||||||||||||||
column · INTEGER · read-only · mandatory Values are displayed in tenths of degrees in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). Example values from LibreNMS test devices
| |||||||||||||||||||||
| CwirelessSensorStatusMaxHumidityThresh | 1.3.6.1.4.1.318.1.1.10.5.1.1.1.14 | INTEGER | RO | mandatory | 90 | ||||||||||||||||
column · INTEGER · read-only · mandatory Values are represented in whole number percentage. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CwirelessSensorStatusMinHumidityThresh | 1.3.6.1.4.1.318.1.1.10.5.1.1.1.15 | INTEGER | RO | mandatory | 10 | ||||||||||||||||
column · INTEGER · read-only · mandatory Values are represented in whole number percentage. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CwirelessSensorStatusBattery | 1.3.6.1.4.1.318.1.1.10.5.1.1.1.16 | INTEGER | RO | mandatory | 28 | ||||||||||||||||
column · INTEGER · read-only · mandatory Values are displayed in tenths of Volts DC. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CwirelessSensorStatusLowBatteryThresh | 1.3.6.1.4.1.318.1.1.10.5.1.1.1.17 | INTEGER | RO | mandatory | 25 | ||||||||||||||||
column · INTEGER · read-only · mandatory Values are displayed in tenths of Volts DC. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CwirelessSensorStatusMinBatteryThresh | 1.3.6.1.4.1.318.1.1.10.5.1.1.1.18 | INTEGER | RO | mandatory | 22 | ||||||||||||||||
column · INTEGER · read-only · mandatory Values are displayed in tenths of Volts DC. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CwirelessSensorStatusRssi | 1.3.6.1.4.1.318.1.1.10.5.1.1.1.19 | INTEGER | RO | mandatory | 50 | ||||||||||||||||
column · INTEGER · read-only · mandatory Values are represented in whole number percentage. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CwirelessSensorStatusLowRssiThresh | 1.3.6.1.4.1.318.1.1.10.5.1.1.1.20 | INTEGER | RO | mandatory | 9 | ||||||||||||||||
column · INTEGER · read-only · mandatory Values are represented in whole number percentage. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CwirelessSensorStatusMinRssiThresh | 1.3.6.1.4.1.318.1.1.10.5.1.1.1.21 | INTEGER | RO | mandatory | 8 | ||||||||||||||||
column · INTEGER · read-only · mandatory Values are represented in whole number percentage. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CwirelessSensorStatusLocation | 1.3.6.1.4.1.318.1.1.10.5.1.1.1.22 | DisplayString | RO | mandatory | Rack-A3-F | ||||||||||||||||
column · DisplayString · read-only · mandatory A user-defined string identifying the location of the wireless sensor. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CwirelessSensorStatusAlarmStatus | 1.3.6.1.4.1.318.1.1.10.5.1.1.1.23 | INTEGER | RO | mandatory | 0 | ||||||||||||||||
column · INTEGER · read-only · mandatory The alarm status of the wireless sensor. This integer should be interpreted as a bit map, with each bit representing the presence or absence of the specific alarm conditions listed below. The bit will be '1' if the condition is present, and '0' if the condition is not present. Bit Hex. Value Description 1 0x0001 Maximum temperature exceeded. 2 0x0002 High temperature exceeded. 3 0x0004 Low temperature exceeded. 4 0x0008 Minimum temperature exceeded. 5 0x0010 Maximum humidity exceeded. 6 0x0020 High humidity exceeded. 7 0x0040 Low humidity exceeded. 8 0x0080 Minimum humidity exceeded. 9 0x0100 Low battery exceeded. 10 0x0200 Minimum battery exceeded. 11 0x0400 Low signal strength exceeded. 12 0x0800 Minimum signal strength exceeded. 13 0x1000 Sensor inactive. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NwirelessSensorPodStatus | 1.3.6.1.4.1.318.1.1.10.5.2 | ||||||||||||||||||||
| TwirelessSensorPodStatusTable | 1.3.6.1.4.1.318.1.1.10.5.2.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for the access of individual pod sensors. | |||||||||||||||||||||
| RwirelessSensorPodStatusEntry | 1.3.6.1.4.1.318.1.1.10.5.2.1.1 | NA | mandatory | ||||||||||||||||||
| CwirelessSensorPodStatusIndex | 1.3.6.1.4.1.318.1.1.10.5.2.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the pod sensor entry. | |||||||||||||||||||||
| CwirelessSensorPodPortIndex | 1.3.6.1.4.1.318.1.1.10.5.2.1.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The pod sensor port index. | |||||||||||||||||||||
| CwirelessSensorPodStatusExtAddr | 1.3.6.1.4.1.318.1.1.10.5.2.1.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The extended address is the combination of the unique 10 byte MAC address of the sensor concatenated with its short address. | |||||||||||||||||||||
| CwirelessSensorPodStatusName | 1.3.6.1.4.1.318.1.1.10.5.2.1.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The name of the sensor pod. | |||||||||||||||||||||
| CwirelessSensorPodStatusAlarmGeneration | 1.3.6.1.4.1.318.1.1.10.5.2.1.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Status of whether alarm generation is enabled or disabled.
| |||||||||||||||||||||
| CwirelessSensorPodStatusTemperature | 1.3.6.1.4.1.318.1.1.10.5.2.1.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Values are displayed in tenths of degrees in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | |||||||||||||||||||||
| CwirelessSensorPodStatusHighTempThresh | 1.3.6.1.4.1.318.1.1.10.5.2.1.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Values are displayed in tenths of degrees in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | |||||||||||||||||||||
| CwirelessSensorPodStatusLowTempThresh | 1.3.6.1.4.1.318.1.1.10.5.2.1.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Values are displayed in tenths of degrees in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | |||||||||||||||||||||
| CwirelessSensorPodStatusHumidity | 1.3.6.1.4.1.318.1.1.10.5.2.1.1.9 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Values are represented in whole number percentage. | |||||||||||||||||||||
| CwirelessSensorPodStatusHighHumidityThresh | 1.3.6.1.4.1.318.1.1.10.5.2.1.1.10 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Values are represented in whole number percentage. | |||||||||||||||||||||
| CwirelessSensorPodStatusLowHumidityThresh | 1.3.6.1.4.1.318.1.1.10.5.2.1.1.11 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Values are represented in whole number percentage. | |||||||||||||||||||||
| CwirelessSensorPodStatusCommStatus | 1.3.6.1.4.1.318.1.1.10.5.2.1.1.12 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The communication status of the wireless sensor. inactive(0) indicates pod sensor is in the wireless network but not sending information. active(1) indicates wireless sensor is live and sending information.
| |||||||||||||||||||||
| CwirelessSensorPodStatusMaxTempThresh | 1.3.6.1.4.1.318.1.1.10.5.2.1.1.13 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Values are displayed in tenths of degrees in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | |||||||||||||||||||||
| CwirelessSensorPodStatusMinTempThresh | 1.3.6.1.4.1.318.1.1.10.5.2.1.1.14 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Values are displayed in tenths of degrees in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | |||||||||||||||||||||
| CwirelessSensorPodStatusMaxHumidityThresh | 1.3.6.1.4.1.318.1.1.10.5.2.1.1.15 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Values are represented in whole number percentage. | |||||||||||||||||||||
| CwirelessSensorPodStatusMinHumidityThresh | 1.3.6.1.4.1.318.1.1.10.5.2.1.1.16 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Values are represented in whole number percentage. | |||||||||||||||||||||
| CwirelessSensorPodStatusDryContactState | 1.3.6.1.4.1.318.1.1.10.5.2.1.1.17 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory State of the dry contact. If the dry contact is closed, the drycontactClosed (1) value will be returned. If the dry contact state is open, the drycontactOpen (0) value will be returned.
| |||||||||||||||||||||
| CwirelessSensorPodStatusDryContactNormalState | 1.3.6.1.4.1.318.1.1.10.5.2.1.1.18 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The normal state of the dry contact. If the normal state is closed, the normallyClosed (1) value will be returned. If the normal state is open, the normallyOpen (0) value will be returned.
| |||||||||||||||||||||
| CwirelessSensorPodStatusBattery | 1.3.6.1.4.1.318.1.1.10.5.2.1.1.19 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Values are displayed in tenths of Volts DC. | |||||||||||||||||||||
| CwirelessSensorPodStatusLowBatteryThresh | 1.3.6.1.4.1.318.1.1.10.5.2.1.1.20 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Values are displayed in tenths of Volts DC. | |||||||||||||||||||||
| CwirelessSensorPodStatusMinBatteryThresh | 1.3.6.1.4.1.318.1.1.10.5.2.1.1.21 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Values are displayed in tenths of Volts DC. | |||||||||||||||||||||
| CwirelessSensorPodStatusRssi | 1.3.6.1.4.1.318.1.1.10.5.2.1.1.22 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Values are represented in whole number percentage. | |||||||||||||||||||||
| CwirelessSensorPodStatusLowRssiThresh | 1.3.6.1.4.1.318.1.1.10.5.2.1.1.23 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Values are represented in whole number percentage. | |||||||||||||||||||||
| CwirelessSensorPodStatusMinRssiThresh | 1.3.6.1.4.1.318.1.1.10.5.2.1.1.24 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Values are represented in whole number percentage. | |||||||||||||||||||||
| CwirelessSensorPodStatusLocation | 1.3.6.1.4.1.318.1.1.10.5.2.1.1.25 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The location of the wireless sensor pod. | |||||||||||||||||||||
| CwirelessSensorPodStatusAlarmStatus | 1.3.6.1.4.1.318.1.1.10.5.2.1.1.26 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The alarm status of the wireless pod sensor. This integer should be interpreted as a bit map, with each bit representing the presence or absence of the specific alarm conditions listed below. The bit will be '1' if the condition is present, and '0' if the condition is not present. Bit Hex. Value Description 1 0x0001 Maximum temperature exceeded. 2 0x0002 High temperature exceeded. 3 0x0004 Low temperature exceeded. 4 0x0008 Minimum temperature exceeded. 5 0x0010 Maximum humidity exceeded. 6 0x0020 High humidity exceeded. 7 0x0040 Low humidity exceeded. 8 0x0080 Minimum humidity exceeded. 9 0x0100 Low battery exceeded. 10 0x0200 Minimum battery exceeded. 11 0x0400 Low signal strength exceeded. 12 0x0800 Minimum signal strength exceeded. 13 0x1000 Sensor inactive. 14 0x2000 Dry contact in Critical state. 15 0x4000 Dry contact in warning state. | |||||||||||||||||||||
| NwirelessSensorConfig | 1.3.6.1.4.1.318.1.1.10.5.3 | ||||||||||||||||||||
| TwirelessSensorConfigTable | 1.3.6.1.4.1.318.1.1.10.5.3.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for the configuration of individual sensors. | |||||||||||||||||||||
| RwirelessSensorConfigEntry | 1.3.6.1.4.1.318.1.1.10.5.3.1.1 | NA | mandatory | ||||||||||||||||||
| CwirelessSensorConfigIndex | 1.3.6.1.4.1.318.1.1.10.5.3.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the entry. | |||||||||||||||||||||
| CwirelessSensorConfigName | 1.3.6.1.4.1.318.1.1.10.5.3.1.1.2 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The user-defined wireless sensor ID string. | |||||||||||||||||||||
| CwirelessSensorConfigAlarmGeneration | 1.3.6.1.4.1.318.1.1.10.5.3.1.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Enable or disable alarm generation for this sensor.
| |||||||||||||||||||||
| CwirelessSensorConfigHighTempThresh | 1.3.6.1.4.1.318.1.1.10.5.3.1.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Values are displayed in tenths of degrees in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | |||||||||||||||||||||
| CwirelessSensorConfigLowTempThresh | 1.3.6.1.4.1.318.1.1.10.5.3.1.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Values are displayed in tenths of degrees in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | |||||||||||||||||||||
| CwirelessSensorConfigHighHumidityThresh | 1.3.6.1.4.1.318.1.1.10.5.3.1.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Values are represented in whole number percentage. | |||||||||||||||||||||
| CwirelessSensorConfigLowHumidityThresh | 1.3.6.1.4.1.318.1.1.10.5.3.1.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Values are represented in whole number percentage. | |||||||||||||||||||||
| CwirelessSensorConfigMaxTempThresh | 1.3.6.1.4.1.318.1.1.10.5.3.1.1.8 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Values are displayed in tenths of degrees in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | |||||||||||||||||||||
| CwirelessSensorConfigMinTempThresh | 1.3.6.1.4.1.318.1.1.10.5.3.1.1.9 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Values are displayed in tenths of degrees in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | |||||||||||||||||||||
| CwirelessSensorConfigMaxHumidityThresh | 1.3.6.1.4.1.318.1.1.10.5.3.1.1.10 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Values are represented in whole number percentage. | |||||||||||||||||||||
| CwirelessSensorConfigMinHumidityThresh | 1.3.6.1.4.1.318.1.1.10.5.3.1.1.11 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Values are represented in whole number percentage. | |||||||||||||||||||||
| CwirelessSensorConfigLowBatteryThresh | 1.3.6.1.4.1.318.1.1.10.5.3.1.1.12 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Values are displayed in tenths of Volts DC. | |||||||||||||||||||||
| CwirelessSensorConfigMinBatteryThresh | 1.3.6.1.4.1.318.1.1.10.5.3.1.1.13 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Values are displayed in tenths of Volts DC. | |||||||||||||||||||||
| CwirelessSensorConfigLowRssiThresh | 1.3.6.1.4.1.318.1.1.10.5.3.1.1.14 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Values are represented in whole number percentage. | |||||||||||||||||||||
| CwirelessSensorConfigMinRssiThresh | 1.3.6.1.4.1.318.1.1.10.5.3.1.1.15 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Values are represented in whole number percentage. | |||||||||||||||||||||
| CwirelessSensorConfigLocation | 1.3.6.1.4.1.318.1.1.10.5.3.1.1.16 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory A user-defined string identifying the location of the wireless sensor. Maximum text input is 20 characters. | |||||||||||||||||||||
| NwirelessSensorPodConfig | 1.3.6.1.4.1.318.1.1.10.5.4 | ||||||||||||||||||||
| TwirelessSensorPodConfigTable | 1.3.6.1.4.1.318.1.1.10.5.4.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for the configuration of individual sensors. | |||||||||||||||||||||
| RwirelessSensorPodConfigEntry | 1.3.6.1.4.1.318.1.1.10.5.4.1.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The sensor to configure. | |||||||||||||||||||||
| CwirelessSensorPodConfigIndex | 1.3.6.1.4.1.318.1.1.10.5.4.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the entry. | |||||||||||||||||||||
| CwirelessSensorPodConfigPortIndex | 1.3.6.1.4.1.318.1.1.10.5.4.1.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The sensor pod port index. | |||||||||||||||||||||
| CwirelessSensorPodConfigName | 1.3.6.1.4.1.318.1.1.10.5.4.1.1.3 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The user defined name of the sensor pod. | |||||||||||||||||||||
| CwirelessSensorPodConfigAlarmGeneration | 1.3.6.1.4.1.318.1.1.10.5.4.1.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Enable or disable alarm generation for this sensor.
| |||||||||||||||||||||
| CwirelessSensorPodConfigDryContactNormalState | 1.3.6.1.4.1.318.1.1.10.5.4.1.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The normal state of the dry contact. If the normal state is closed, the normallyClosed (1) value will be returned. If the normal state is open, the normallyOpen (0) value will be returned. Setting this variable will change the normal state of the dry contact.
| |||||||||||||||||||||
| CwirelessSensorPodConfigHighTempThresh | 1.3.6.1.4.1.318.1.1.10.5.4.1.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Values are displayed in tenths of degrees in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | |||||||||||||||||||||
| CwirelessSensorPodConfigLowTempThresh | 1.3.6.1.4.1.318.1.1.10.5.4.1.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Values are displayed in tenths of degrees in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | |||||||||||||||||||||
| CwirelessSensorPodConfigHighHumidityThresh | 1.3.6.1.4.1.318.1.1.10.5.4.1.1.8 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Values are represented in whole number percentage. | |||||||||||||||||||||
| CwirelessSensorPodConfigLowHumidityThresh | 1.3.6.1.4.1.318.1.1.10.5.4.1.1.9 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Values are represented in whole number percentage. | |||||||||||||||||||||
| CwirelessSensorPodConfigMaxTempThresh | 1.3.6.1.4.1.318.1.1.10.5.4.1.1.10 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Values are displayed in tenths of degrees in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | |||||||||||||||||||||
| CwirelessSensorPodConfigMinTempThresh | 1.3.6.1.4.1.318.1.1.10.5.4.1.1.11 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Values are represented in whole number degrees. Units are displayed in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | |||||||||||||||||||||
| CwirelessSensorPodConfigMaxHumidityThresh | 1.3.6.1.4.1.318.1.1.10.5.4.1.1.12 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Values are represented in whole number percentage. | |||||||||||||||||||||
| CwirelessSensorPodConfigMinHumidityThresh | 1.3.6.1.4.1.318.1.1.10.5.4.1.1.13 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Values are represented in whole number percentage. | |||||||||||||||||||||
| CwirelessSensorPodConfigLowBatteryThresh | 1.3.6.1.4.1.318.1.1.10.5.4.1.1.14 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Values are displayed in tenths of Volts DC. | |||||||||||||||||||||
| CwirelessSensorPodConfigMinBatteryThresh | 1.3.6.1.4.1.318.1.1.10.5.4.1.1.15 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Values are displayed in tenths of Volts DC. | |||||||||||||||||||||
| CwirelessSensorPodConfigLowRssiThresh | 1.3.6.1.4.1.318.1.1.10.5.4.1.1.16 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Values are represented in whole number percentage. | |||||||||||||||||||||
| CwirelessSensorPodConfigMinRssiThresh | 1.3.6.1.4.1.318.1.1.10.5.4.1.1.17 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Values are represented in whole number percentage. | |||||||||||||||||||||
| CwirelessSensorPodConfigLocation | 1.3.6.1.4.1.318.1.1.10.5.4.1.1.18 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory A user-defined string identifying the location of the wireless pod sensor. Maximum text input is 20 characters. | |||||||||||||||||||||
| Nnetlock | 1.3.6.1.4.1.318.1.1.11 | ||||||||||||||||||||
| NnlIdent | 1.3.6.1.4.1.318.1.1.11.1 | ||||||||||||||||||||
| NnlStatus | 1.3.6.1.4.1.318.1.1.11.2 | ||||||||||||||||||||
| NrPDU | 1.3.6.1.4.1.318.1.1.12 | ||||||||||||||||||||
| NrPDUIdent | 1.3.6.1.4.1.318.1.1.12.1 | ||||||||||||||||||||
| SrPDUIdentName | 1.3.6.1.4.1.318.1.1.12.1.1 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory The name of the Rack PDU. The maximum string size is device dependent. | |||||||||||||||||||||
| SrPDUIdentHardwareRev | 1.3.6.1.4.1.318.1.1.12.1.2 | DisplayString | RO | mandatory | B2 | ||||||||||||||||
scalar · DisplayString · read-only · mandatory The hardware revision of the Rack PDU. This value is set at the factory. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SrPDUIdentFirmwareRev | 1.3.6.1.4.1.318.1.1.12.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory An 8-byte ID string identifying the Rack PDU firmware revision. This value is set at the factory. | |||||||||||||||||||||
| SrPDUIdentDateOfManufacture | 1.3.6.1.4.1.318.1.1.12.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The date when the Rack PDU was manufactured in mm/dd/yyyy format. This value is set at the factory. The year 2000 will be represented by 00. | |||||||||||||||||||||
| SrPDUIdentModelNumber | 1.3.6.1.4.1.318.1.1.12.1.5 | DisplayString | RO | mandatory | AP7900B | ||||||||||||||||
scalar · DisplayString · read-only · mandatory A 10-character string identifying the model number of the Rack PDU. This value is set at the factory. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SrPDUIdentSerialNumber | 1.3.6.1.4.1.318.1.1.12.1.6 | DisplayString | RO | mandatory | ZA1732000177 | ||||||||||||||||
scalar · DisplayString · read-only · mandatory A 12-character string identifying the serial number of the Rack PDU. This value is set at the factory. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SrPDUIdentDeviceRating | 1.3.6.1.4.1.318.1.1.12.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Getting this OID will return the electrical rating of the device in Amps. | |||||||||||||||||||||
| SrPDUIdentDeviceNumOutlets | 1.3.6.1.4.1.318.1.1.12.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Getting this OID will return the number of outlets contained in the device. | |||||||||||||||||||||
| SrPDUIdentDeviceNumPhases | 1.3.6.1.4.1.318.1.1.12.1.9 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Getting this OID will return the number of phases supported by the device. | |||||||||||||||||||||
| SrPDUIdentDeviceNumBreakers | 1.3.6.1.4.1.318.1.1.12.1.10 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Getting this OID will return the number of circuit breakers supported by the device. This is the same as the number of banks of outlets. 0 will be returned if the unit has no phase breakers. | |||||||||||||||||||||
| SrPDUIdentDeviceBreakerRating | 1.3.6.1.4.1.318.1.1.12.1.11 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Getting this OID will return rating of the circuit breakers on the device in Amps if it has any. | |||||||||||||||||||||
| SrPDUIdentDeviceOrientation | 1.3.6.1.4.1.318.1.1.12.1.12 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Getting this OID will return the intended physical orientation of the device. OrientHorizonatal(1) indicates Horizontal. OrientVertical(2) indicates Vertical.
| |||||||||||||||||||||
| SrPDUIdentDeviceOutletLayout | 1.3.6.1.4.1.318.1.1.12.1.13 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Getting this OID will return outlet layout for the device. seqPhaseToNeutral(1) indicates outlet layout as follows: 1:1-N,2:2-N,3:3-N,4:1-N,5:2-N,... seqPhaseToPhase(2) indicates outlet layout as follows: 1:1-2,2:2-3,3:3-1,4:1-2,5:2-3,... seqPhToNeu21PhToPh(3) indicates outlet layout as follows: 1:1-N,2:2-N...21:3-N,22:1-2,23:2-3,24:3-1,... seqPhToPhGrouped(4) indicates outlet layout as follows: For AP8xxx SKU's Group 1:1-2, Group 2:2-3, Group 3:3-1. For AP7xxx SKU's Group 1:3-1. Group 2:2-3, Group 3:1-2. seqPhToNGrouped(5) indicates outlet layout as follows: This unit has 3 outlet groups. Group 1:1-N, Group 2:2-N, Group 3:3-N. seqPToN1516PToPGrouped(6) indicates outlet layout as follows: This unit has 4 outlet groups. Group 1 (Outlets 1-14):1-2, Group 2 (Outlets 15-16):1-N, Group 3:2-3, Group 4:3-1. seqPhToPh2xGrouped(7) indicates outlet layout as follows: This unit has 6 outlet groups. Group 1:1-2, Group 2:1-2, Group 3:2-3, Group 4:2-3, Group 5:3-1, Group 6:3-1. seqPhToN2xGrouped(8) indicates outlet layout as follows: This unit has 6 outlet groups. Group 1:1-N, Group 2:1-N, Group 3:2-N, Group 4:2-N, Group 5:3-N, Group 6:3-N. seqNotApplicable(9): Outlet layout does not affect any of the user interfaces. These SKUs may report seqNotApplicable(9) if there is not an exact outlet layout match available. Only AP7xxx, AP8xxx SKUs support this feature. Product which does not support this feature will respond to this OID with a value of -1.
| |||||||||||||||||||||
| SrPDUIdentDeviceDisplayOrientation | 1.3.6.1.4.1.318.1.1.12.1.14 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Getting this OID will return the intended physical orientation of the Seven-Segment Display or LCD. Normal(1) indicates Normal. Reverse(2)indicates Upside-Down.
| |||||||||||||||||||||
| SrPDUIdentDeviceLinetoLineVoltage | 1.3.6.1.4.1.318.1.1.12.1.15 | INTEGER | RW | mandatory | 120 | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Getting/Setting this OID will return/set the Line to Line Voltage. This OID defaults to the nominal input line voltage in volts AC. This setting is used to calculate total power and must be configured for best accuracy. Only AP7xxx SKUs support this feature. The valid range is between 0V to 440V Example values from LibreNMS test devices
| |||||||||||||||||||||
| SrPDUIdentDevicePowerWatts | 1.3.6.1.4.1.318.1.1.12.1.16 | INTEGER | RO | mandatory | 312 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory Getting this OID will return the Power in Watts. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SrPDUIdentDevicePowerFactor | 1.3.6.1.4.1.318.1.1.12.1.17 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Getting/setting this OID will return/set the Power Factor in thousandths (1000 is power factor of 1). This OID is only writable for AP7xxx SKUs Valid range is from 0 to 1000. | |||||||||||||||||||||
| SrPDUIdentDevicePowerVA | 1.3.6.1.4.1.318.1.1.12.1.18 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Getting this OID will return the Power in VA. | |||||||||||||||||||||
| SrPDUIdentDeviceLinetoNeutralVoltage | 1.3.6.1.4.1.318.1.1.12.1.19 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Getting/Setting this OID will return/set the Line to Neutral Voltage. This OID defaults to the nominal line to neutral voltage in volts AC. This setting is used to calculate total power and must be configured for best accuracy. This OID applies only to AP7823. For all other models, the OID is fixed at 0. The valid range is between 0V to 440V. | |||||||||||||||||||||
| NrPDULoad | 1.3.6.1.4.1.318.1.1.12.2 | ||||||||||||||||||||
| NrPDULoadDevice | 1.3.6.1.4.1.318.1.1.12.2.1 | ||||||||||||||||||||
| SrPDULoadDevMaxPhaseLoad | 1.3.6.1.4.1.318.1.1.12.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Getting this OID will return the maximum rated power that each phase of the Rack PDU can provide. It is represented in Amps. 0 will be returned if the unit is banked. | |||||||||||||||||||||
| SrPDULoadDevNumPhases | 1.3.6.1.4.1.318.1.1.12.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of phases available with this Rack PDU. | |||||||||||||||||||||
| SrPDULoadDevMaxBankLoad | 1.3.6.1.4.1.318.1.1.12.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Getting this OID will return the maximum rated power that a bank of the Rack PDU can provide. It is represented in Amps. 0 will be returned if the device does not have any banks. | |||||||||||||||||||||
| SrPDULoadDevNumBanks | 1.3.6.1.4.1.318.1.1.12.2.1.4 | INTEGER | RO | mandatory | 2 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of banks of outlets available with this Rack PDU. A bank of outlets has a unique circuit breaker for a subset of the total number of outlets on the rPDU. 0 will be returned if the unit has no banks. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SrPDULoadDevBankTableSize | 1.3.6.1.4.1.318.1.1.12.2.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The size of the Bank Table. | |||||||||||||||||||||
| TrPDULoadDevBankTable | 1.3.6.1.4.1.318.1.1.12.2.1.6 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting the Bank Max Load in the Rack PDU. | |||||||||||||||||||||
| RrPDULoadDevBankEntry | 1.3.6.1.4.1.318.1.1.12.2.1.6.1 | NA | mandatory | ||||||||||||||||||
| CrPDULoadDevBankIndex | 1.3.6.1.4.1.318.1.1.12.2.1.6.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the Rack PDU bank entry. | |||||||||||||||||||||
| CrPDULoadDevBankNumber | 1.3.6.1.4.1.318.1.1.12.2.1.6.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this OID will return the bank number. | |||||||||||||||||||||
| CrPDULoadDevBankMaxLoad | 1.3.6.1.4.1.318.1.1.12.2.1.6.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this OID will return the maximum rated power that each bank of the Rack PDU can provide. It is represented in Amps. | |||||||||||||||||||||
| SrPDULoadDevMaxOutletTableSize | 1.3.6.1.4.1.318.1.1.12.2.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The size of the Outlet Table. | |||||||||||||||||||||
| TrPDULoadDevMaxOutletTable | 1.3.6.1.4.1.318.1.1.12.2.1.8 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting the Max Outlet Load in an Outlet Monitored Rack PDU. | |||||||||||||||||||||
| RrPDULoadDevMaxOutletEntry | 1.3.6.1.4.1.318.1.1.12.2.1.8.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory This gives access to Max Outlet Load of an Outlet Monitored Rack PDU | |||||||||||||||||||||
| CrPDULoadDevOutletIndex | 1.3.6.1.4.1.318.1.1.12.2.1.8.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the Outlet Monitored Rack PDU Max Outlet Load entry. | |||||||||||||||||||||
| CrPDULoadDevOutletNumber | 1.3.6.1.4.1.318.1.1.12.2.1.8.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this OID will return the Outlet number. | |||||||||||||||||||||
| CrPDULoadDevMaxOutletLoad | 1.3.6.1.4.1.318.1.1.12.2.1.8.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this OID will return the maximum rated power that each Outlet of an Outlet Monitored Rack PDU can provide. It is represented in Amps. | |||||||||||||||||||||
| NrPDULoadPhaseConfig | 1.3.6.1.4.1.318.1.1.12.2.2 | ||||||||||||||||||||
| TrPDULoadPhaseConfigTable | 1.3.6.1.4.1.318.1.1.12.2.2.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for configuration of each Rack PDU phase. The number of entries is contained in the rPDULoadDevNumPhases OID. | |||||||||||||||||||||
| RrPDULoadPhaseConfigEntry | 1.3.6.1.4.1.318.1.1.12.2.2.1.1 | NA | mandatory | ||||||||||||||||||
| CrPDULoadPhaseConfigIndex | 1.3.6.1.4.1.318.1.1.12.2.2.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the Rack PDU phase entry.
| |||||||||||||||||||||
| CrPDULoadPhaseConfigLowLoadThreshold | 1.3.6.1.4.1.318.1.1.12.2.2.1.1.2 | INTEGER | RW | mandatory | 0 | ||||||||||||||||
column · INTEGER · read-write · mandatory A threshold that indicates the power consumption of the load is nearing a low consumption condition. It is represented in Amps. A warning will be issued when the load is less than the threshold value. A threshold value of 0 Amps effectively disables this warning. Maximum value must be less than the value returned by the rPDULoadPhaseConfigNearOverloadThreshold OID. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDULoadPhaseConfigNearOverloadThreshold | 1.3.6.1.4.1.318.1.1.12.2.2.1.1.3 | INTEGER | RW | mandatory | 10 | ||||||||||||||||
column · INTEGER · read-write · mandatory A threshold that indicates the power consumption of the load is nearing an overload condition. It is represented in Amps. A warning will be issued when the load is greater than or equal to the threshold value. Minimum value must be greater than the value returned by the rPDULoadPhaseConfigLowLoadThreshold OID. Maximum value must be less than or equal to the value returned by the rPDULoadPhaseConfigOverloadThreshold OID. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDULoadPhaseConfigOverloadThreshold | 1.3.6.1.4.1.318.1.1.12.2.2.1.1.4 | INTEGER | RW | mandatory | 12 | ||||||||||||||||
column · INTEGER · read-write · mandatory A threshold that indicates the power consumption of the load has entered an overload condition. It is represented in Amps. A warning will be issued when the load is greater than or equal to the threshold value. Minimum value must be greater than or equal to the value returned by the rPDULoadPhaseConfigNearOverloadThreshold OID. Maximum value must be less than or equal to the value returned by the rPDULoadDevMaxPhaseLoad OID. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDULoadPhaseConfigAlarm | 1.3.6.1.4.1.318.1.1.12.2.2.1.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this OID will return the current Phase Alarm.
| |||||||||||||||||||||
| NrPDULoadStatus | 1.3.6.1.4.1.318.1.1.12.2.3 | ||||||||||||||||||||
| TrPDULoadStatusTable | 1.3.6.1.4.1.318.1.1.12.2.3.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting of status of each Rack PDU phase/bank. The number of entries is calculated by adding the number of phases (rPDULoadDevNumPhases OID) and the number of banks of outlets (rPDULoadDevNumBanks) Number of entries = #phases + #banks. NOTE: If a device has phase and bank information, all phase information shall precede the bank information. If a device has total information, it shall precede both the bank and the phase information. | |||||||||||||||||||||
| RrPDULoadStatusEntry | 1.3.6.1.4.1.318.1.1.12.2.3.1.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The Rack PDU phase/bank to gather status from.
| |||||||||||||||||||||
| CrPDULoadStatusIndex | 1.3.6.1.4.1.318.1.1.12.2.3.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the Rack PDU phase/bank entry. All phase information will precede any bank information | |||||||||||||||||||||
| CrPDULoadStatusLoad | 1.3.6.1.4.1.318.1.1.12.2.3.1.1.2 | Gauge | RO | mandatory | 28 | ||||||||||||||||
column · Gauge · read-only · mandatory Getting this OID will return the phase/bank load measured in tenths of Amps. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDULoadStatusLoadState | 1.3.6.1.4.1.318.1.1.12.2.3.1.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this OID will return the phase/bank load state. phaseLoadNormal(1) indicates that the phase/bank is operating properly within the rPDULoadConfigLowLoadThreshold and rPDULoadConfigNearOverloadThreshold OID values. phaseLoadLow(2) indicates that the phase/bank load has dropped below the rPDULoadConfigLowLoadThreshold OID value. An SNMP trap will occur when this state is entered or cleared. phaseLoadNearOverload(3) indicates that the phase/bank load is greater than or equal to the rPDULoadConfigNearOverloadThreshold OID value. An SNMP trap will occur when this state is entered or cleared. phaseLoadOverload(4) indicates that the phase/bank load is greater than or equal to the rPDULoadConfigOverloadThreshold OID value. An SNMP trap will occur when this state is entered or cleared.
| |||||||||||||||||||||
| CrPDULoadStatusPhaseNumber | 1.3.6.1.4.1.318.1.1.12.2.3.1.1.4 | INTEGER | RO | mandatory | 1 | ||||||||||||||||
column · INTEGER · read-only · mandatory The phase number to which this record refers. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDULoadStatusBankNumber | 1.3.6.1.4.1.318.1.1.12.2.3.1.1.5 | INTEGER | RO | mandatory | 0 | ||||||||||||||||
column · INTEGER · read-only · mandatory The bank number to which this record refers. A value of 0 will be returned if any bank is not present or if it is phase related. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NrPDULoadBankConfig | 1.3.6.1.4.1.318.1.1.12.2.4 | ||||||||||||||||||||
| TrPDULoadBankConfigTable | 1.3.6.1.4.1.318.1.1.12.2.4.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for configuration of each Rack PDU bank. The number of entries is contained in the rPDULoadDevNumBanks OID. | |||||||||||||||||||||
| RrPDULoadBankConfigEntry | 1.3.6.1.4.1.318.1.1.12.2.4.1.1 | NA | mandatory | ||||||||||||||||||
| CrPDULoadBankConfigIndex | 1.3.6.1.4.1.318.1.1.12.2.4.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the Rack PDU bank entry. | |||||||||||||||||||||
| CrPDULoadBankConfigLowLoadThreshold | 1.3.6.1.4.1.318.1.1.12.2.4.1.1.2 | INTEGER | RW | mandatory | 0 | ||||||||||||||||
column · INTEGER · read-write · mandatory A threshold that indicates the power consumption of the load is nearing a low consumption condition. It is represented in Amps. A warning will be issued when the load is less than the threshold value. A threshold value of 0 Amps effectively disables this warning. Maximum value must be less than the value returned by the rPDULoadBankConfigNearOverloadThreshold OID. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDULoadBankConfigNearOverloadThreshold | 1.3.6.1.4.1.318.1.1.12.2.4.1.1.3 | INTEGER | RW | mandatory | 6 | ||||||||||||||||
column · INTEGER · read-write · mandatory A threshold that indicates the power consumption of the load is nearing an overload condition. It is represented in Amps. A warning will be issued when the load is greater than or equal to the threshold value. Minimum value must be greater than the value returned by the rPDULoadBankConfigLowLoadThreshold OID. Maximum value must be less than or equal to the value returned by the rPDULoadBankConfigOverloadThreshold OID. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDULoadBankConfigOverloadThreshold | 1.3.6.1.4.1.318.1.1.12.2.4.1.1.4 | INTEGER | RW | mandatory | 8 | ||||||||||||||||
column · INTEGER · read-write · mandatory A threshold that indicates the power consumption of the load has entered an overload condition. It is represented in Amps. A warning will be issued when the load is greater than or equal to the threshold value. Minimum value must be greater than or equal to the value returned by the rPDULoadBankConfigNearOverloadThreshold OID. Maximum value must be less than or equal to the value returned by the rPDULoadDevMaxBankLoad OID. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDULoadBankConfigAlarm | 1.3.6.1.4.1.318.1.1.12.2.4.1.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this OID will return the current Bank Alarm.
| |||||||||||||||||||||
| NrPDUOutlet | 1.3.6.1.4.1.318.1.1.12.3 | ||||||||||||||||||||
| NrPDUOutletDevice | 1.3.6.1.4.1.318.1.1.12.3.1 | ||||||||||||||||||||
| SrPDUOutletDevCommand | 1.3.6.1.4.1.318.1.1.12.3.1.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Setting this OID to immediateAllOn (2) will turn all outlets on immediately. Setting this OID to immediateAllOff (3) will turn all outlets off immediately. Setting this OID to immediateAllReboot (4) will reboot all outlets immediately. Setting this OID to delayedAllOn (5) will turn all outlets on as defined by each outlet's rPDUOutletConfigPowerOnTime OID value. Setting this OID to delayedAllOff (6) will turn all outlets off as defined by each outlet's rPDUOutletConfigPowerOffTime OID value. Setting this OID to delayedAllReboot (7) will cause a delayedAllOff command to be performed. Once all outlets are off, the Switched Rack PDU will then delay the largest rPDUOutletConfigRebootDuration OID time, and then perform a delayedAllOn command. Setting this OID to cancelAllPendingCommands (8) will cause all pending commands on the Switched Rack PDU to be canceled. Getting this OID will return the noCommandAll (1) value.
| |||||||||||||||||||||
| SrPDUOutletDevColdstartDelay | 1.3.6.1.4.1.318.1.1.12.3.1.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The amount of delay, in seconds, between when power is provided to the Switched Rack PDU and when the Switched Rack PDU provides basic master power to the outlets. Allowed values are: -1 - never apply power automatically. 0 - apply power immediately. 1 to 300 - delay up to 300 seconds (5 minutes). | |||||||||||||||||||||
| SrPDUOutletDevNumCntrlOutlets | 1.3.6.1.4.1.318.1.1.12.3.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of controlled outlets on this Switched Rack PDU. | |||||||||||||||||||||
| SrPDUOutletDevNumTotalOutlets | 1.3.6.1.4.1.318.1.1.12.3.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The total number of outlets on this Rack PDU. | |||||||||||||||||||||
| SrPDUOutletDevMonitoredOutlets | 1.3.6.1.4.1.318.1.1.12.3.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The total number of monitored outlets on this Rack PDU. | |||||||||||||||||||||
| NrPDUOutletPhase | 1.3.6.1.4.1.318.1.1.12.3.2 | ||||||||||||||||||||
| TrPDUOutletPhaseTable | 1.3.6.1.4.1.318.1.1.12.3.2.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for management of outlets on a per phase basis. | |||||||||||||||||||||
| RrPDUOutletPhaseEntry | 1.3.6.1.4.1.318.1.1.12.3.2.1.1 | NA | mandatory | ||||||||||||||||||
| CrPDUOutletPhaseIndex | 1.3.6.1.4.1.318.1.1.12.3.2.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the Switched Rack PDU phase entry.
| |||||||||||||||||||||
| CrPDUOutletPhaseOverloadRestriction | 1.3.6.1.4.1.318.1.1.12.3.2.1.1.2 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory This OID controls the behavior of a Switched Rack PDU phase when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will always allow the outlets on the corresponding phase to turn on. Setting this OID to restrictOnNearOverload (2) will not allow outlets on the corresponding phase to turn on if the rPDULoadConfigNearOverloadThreshold OID is exceeded. Setting this OID to restrictOnOverload (3) will not allow outlets on the corresponding phase to turn on if the rPDULoadConfigOverloadThreshold OID is exceeded.
| |||||||||||||||||||||
| NrPDUOutletControl | 1.3.6.1.4.1.318.1.1.12.3.3 | ||||||||||||||||||||
| TrPDUOutletControlTable | 1.3.6.1.4.1.318.1.1.12.3.3.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for control of the individual outlets. The number of entries is contained in the rPDUOutletDevNumCntrlOutlets OID. | |||||||||||||||||||||
| RrPDUOutletControlEntry | 1.3.6.1.4.1.318.1.1.12.3.3.1.1 | NA | mandatory | ||||||||||||||||||
| CrPDUOutletControlIndex | 1.3.6.1.4.1.318.1.1.12.3.3.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the outlet entry. | |||||||||||||||||||||
| CrPDUOutletControlOutletName | 1.3.6.1.4.1.318.1.1.12.3.3.1.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The name of the outlet. The maximum string size is device dependent. An error will be returned if the set request exceeds the max size. This OID is provided for informational purposes only. | |||||||||||||||||||||
| CrPDUOutletControlOutletPhase | 1.3.6.1.4.1.318.1.1.12.3.3.1.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The phase/s associated with this outlet. For single phase devices, this object will always return phase1(1). For 3-phase devices, this object will return phase1 (1), phase2 (2), or phase3 (3) for outlets tied to a single phase. For outlets tied to two phases, this object will return phase1-2 (4) for phases 1 and 2, phase2-3 (5) for phases 2 and 3, and phase3-1 (6) for phases 3 and 1.
| |||||||||||||||||||||
| CrPDUOutletControlOutletCommand | 1.3.6.1.4.1.318.1.1.12.3.3.1.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Getting this variable will return the outlet state. If the outlet is on, the immediateOn (1) value will be returned. If the outlet is off, the immediateOff (2) value will be returned. Setting this variable to immediateOn (1) will immediately turn the outlet on. Setting this variable to immediateOff (2) will immediately turn the outlet off. Setting this variable to immediateReboot (3) will immediately reboot the outlet. Setting this variable to delayedOn (4) will turn the outlet on after the rPDUOutletConfigPowerOnTime OID time has elapsed. Setting this variable to delayedOff (5) will turn the outlet off after the rPDUOutletConfigPowerOffTime OID time has elapsed. Setting this variable to delayedReboot (6) will cause the Switched Rack PDU to perform a delayedOff command, wait the rPDUOutletConfigRebootDuration OID time, and then perform a delayedOn command. Setting this variable to cancelPendingCommand (7) will cause any pending command to this outlet to be canceled.
| |||||||||||||||||||||
| CrPDUOutletControlOutletBank | 1.3.6.1.4.1.318.1.1.12.3.3.1.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The bank associated with this outlet. | |||||||||||||||||||||
| NrPDUOutletConfig | 1.3.6.1.4.1.318.1.1.12.3.4 | ||||||||||||||||||||
| TrPDUOutletConfigTable | 1.3.6.1.4.1.318.1.1.12.3.4.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for configuration of individual outlets. The number of entries is contained in the rPDUOutletDevNumCntrlOutlets OID. | |||||||||||||||||||||
| RrPDUOutletConfigEntry | 1.3.6.1.4.1.318.1.1.12.3.4.1.1 | NA | mandatory | ||||||||||||||||||
| CrPDUOutletConfigIndex | 1.3.6.1.4.1.318.1.1.12.3.4.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the outlet entry. | |||||||||||||||||||||
| CrPDUOutletConfigOutletName | 1.3.6.1.4.1.318.1.1.12.3.4.1.1.2 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The name of the outlet. The maximum string size is device dependent. An error will be returned if the set request exceeds the max size. | |||||||||||||||||||||
| CrPDUOutletConfigOutletPhase | 1.3.6.1.4.1.318.1.1.12.3.4.1.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The phase/s associated with this outlet. For single phase devices, this object will always return phase1(1). For 3-phase devices, this object will return phase1 (1), phase2 (2), or phase3 (3) for outlets tied to a single phase. For outlets tied to two phases, this object will return phase1-2 (4) for phases 1 and 2, phase2-3 (5) for phases 2 and 3, and phase3-1 (6) for phases 3 and 1.
| |||||||||||||||||||||
| CrPDUOutletConfigPowerOnTime | 1.3.6.1.4.1.318.1.1.12.3.4.1.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The amount of time (in seconds) the outlet will delay
powering on at coldstart or when a command that requires
a turn-on delay is issued.
Allowed values are:
-1 - never power on.
0 - power on immediately.
1 to 7200 - power on up to 7200 seconds after being
commanded. | |||||||||||||||||||||
| CrPDUOutletConfigPowerOffTime | 1.3.6.1.4.1.318.1.1.12.3.4.1.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The amount of time (in seconds) the outlet will delay
powering off when a command that requires
a turn-off delay is issued.
Allowed values are:
-1 - never power off.
0 - power off immediately.
1 to 7200 - power off up to 7200 seconds after being
commanded. | |||||||||||||||||||||
| CrPDUOutletConfigRebootDuration | 1.3.6.1.4.1.318.1.1.12.3.4.1.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory During a reboot sequence, power is turned off and then back on. This OID defines the amount of time to wait, in seconds, after turning the power off, at the start of the sequence, before turning power back on, at the end of the reboot sequence. Allowed range is any value between 5 and 60 seconds (1 minute). | |||||||||||||||||||||
| CrPDUOutletConfigOutletBank | 1.3.6.1.4.1.318.1.1.12.3.4.1.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The bank associated with this outlet. | |||||||||||||||||||||
| SrPDUOutletConfigMonitoredTableSize | 1.3.6.1.4.1.318.1.1.12.3.4.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The size of the Outlet Config Monitored Table | |||||||||||||||||||||
| TrPDUOutletConfigMonitoredTable | 1.3.6.1.4.1.318.1.1.12.3.4.3 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting/setting of outlet thresholds of an Outlet Monitored Rack PDU. | |||||||||||||||||||||
| RrPDUOutletConfigMonitoredEntry | 1.3.6.1.4.1.318.1.1.12.3.4.3.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory This gives access to Monitored Outlet entries | |||||||||||||||||||||
| CrPDUOutletConfigMonitoredIndex | 1.3.6.1.4.1.318.1.1.12.3.4.3.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the RACK PDU Phase entry. | |||||||||||||||||||||
| CrPDUOutletConfigMonitoredName | 1.3.6.1.4.1.318.1.1.12.3.4.3.1.2 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The name of the Monitored Outlet. The maximum string size is device dependent. An error will be returned if the set request exceeds the max size. | |||||||||||||||||||||
| CrPDUOutletConfigMonitoredNumber | 1.3.6.1.4.1.318.1.1.12.3.4.3.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The outlet number of an Outlet Monitored RACK PDU. | |||||||||||||||||||||
| CrPDUOutletConfigMonitoredLowLoadThreshold | 1.3.6.1.4.1.318.1.1.12.3.4.3.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory A threshold that indicates the power consumption of the load is nearing a low consumption condition. It is represented in Amps. A warning will be issued when the load is less than the threshold value. A threshold value of 0 Amps effectively disables this warning. Maximum value must be less than the value returned by the rPDUOutletConfigMonitoredNearOverloadThreshold OID. 0 will be returned if the unit is not Outlet Monitored Rack PDU. | |||||||||||||||||||||
| CrPDUOutletConfigMonitoredNearOverloadThreshold | 1.3.6.1.4.1.318.1.1.12.3.4.3.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory A threshold that indicates the power consumption of the load is nearing an overload condition. It is represented in Amps. A warning will be issued when the load is greater than or equal to the threshold value. Minimum value must be greater than the value returned by the rPDUOutletConfigMonitoredLowLoadThreshold OID. Maximum value must be less than or equal to the value returned by the rPDUOutletConfigMonitoredOverloadThreshold OID. 0 will be returned if the unit is not Outlet Monitored Rack PDU. | |||||||||||||||||||||
| CrPDUOutletConfigMonitoredOverloadThreshold | 1.3.6.1.4.1.318.1.1.12.3.4.3.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory A threshold that indicates the power consumption of the load has entered an overload condition. It is represented in Amps. A warning will be issued when the load is greater than or equal to the threshold value. Minimum value must be greater than or equal to the value returned by the rPDUOutletConfigMonitoredNearOverloadThreshold OID. Maximum value must be less than or equal to the value returned by the rPDULoadDevMaxOutletLoad OID. 0 will be returned if the unit is not Outlet Monitored Rack PDU. | |||||||||||||||||||||
| NrPDUOutletStatus | 1.3.6.1.4.1.318.1.1.12.3.5 | ||||||||||||||||||||
| TrPDUOutletStatusTable | 1.3.6.1.4.1.318.1.1.12.3.5.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting of status of individual outlets. The number of entries is contained in the rPDUOutletDevNumCntrlOutlets OID or rPDUOutletDevMonitoredOutlets OID. | |||||||||||||||||||||
| RrPDUOutletStatusEntry | 1.3.6.1.4.1.318.1.1.12.3.5.1.1 | NA | mandatory | ||||||||||||||||||
| CrPDUOutletStatusIndex | 1.3.6.1.4.1.318.1.1.12.3.5.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the outlet entry. | |||||||||||||||||||||
| CrPDUOutletStatusOutletName | 1.3.6.1.4.1.318.1.1.12.3.5.1.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The name of the outlet. The maximum string size is device dependent. This OID is provided for informational purposes only. | |||||||||||||||||||||
| CrPDUOutletStatusOutletPhase | 1.3.6.1.4.1.318.1.1.12.3.5.1.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The phase/s associated with this outlet. For single phase devices, this object will always return phase1(1). For 3-phase devices, this object will return phase1 (1), phase2 (2), or phase3 (3) for outlets tied to a single phase. For outlets tied to two phases, this object will return phase1-2 (4) for phases 1 and 2, phase2-3 (5) for phases 2 and 3, and phase3-1 (6) for phases 3 and 1.
| |||||||||||||||||||||
| CrPDUOutletStatusOutletState | 1.3.6.1.4.1.318.1.1.12.3.5.1.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this variable will return the outlet state. If the outlet is on, the outletStatusOn (1) value will be returned. If the outlet is off, the outletStatusOff (2) value will be returned.
| |||||||||||||||||||||
| CrPDUOutletStatusCommandPending | 1.3.6.1.4.1.318.1.1.12.3.5.1.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this variable will return the command pending state of the outlet. If a command is pending on the outlet, the outletStatusCommandPending (1) value will be returned. If there is not a command pending on the outlet, the outletStatusNoCommandPending (2) will be returned.
| |||||||||||||||||||||
| CrPDUOutletStatusOutletBank | 1.3.6.1.4.1.318.1.1.12.3.5.1.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The bank associated with this outlet. | |||||||||||||||||||||
| CrPDUOutletStatusLoad | 1.3.6.1.4.1.318.1.1.12.3.5.1.1.7 | Gauge | RO | mandatory | |||||||||||||||||
column · Gauge · read-only · mandatory Getting this OID will return the measured Outlet load for an Outlet Monitored Rack PDU in tenths of Amps. For other models this OID is not supported. | |||||||||||||||||||||
| NrPDUOutletBank | 1.3.6.1.4.1.318.1.1.12.3.6 | ||||||||||||||||||||
| TrPDUOutletBankTable | 1.3.6.1.4.1.318.1.1.12.3.6.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for management of outlets on a per bank basis. | |||||||||||||||||||||
| RrPDUOutletBankEntry | 1.3.6.1.4.1.318.1.1.12.3.6.1.1 | NA | mandatory | ||||||||||||||||||
| CrPDUOutletBankIndex | 1.3.6.1.4.1.318.1.1.12.3.6.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the Switched Rack PDU bank entry. | |||||||||||||||||||||
| CrPDUOutletBankOverloadRestriction | 1.3.6.1.4.1.318.1.1.12.3.6.1.1.2 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory This OID controls the behavior of a Switched Rack PDU bank when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will always allow the outlets on the corresponding bank to turn on. Setting this OID to restrictOnNearOverload (2) will not allow outlets on the corresponding bank to turn on if the rPDULoadBankConfigNearOverloadThreshold OID is exceeded. Setting this OID to restrictOnOverload (3) will not allow outlets on the corresponding bank to turn on if the rPDULoadBankConfigOverloadThreshold OID is exceeded.
| |||||||||||||||||||||
| NrPDUPowerSupply | 1.3.6.1.4.1.318.1.1.12.4 | ||||||||||||||||||||
| NrPDUPowerSupplyDevice | 1.3.6.1.4.1.318.1.1.12.4.1 | ||||||||||||||||||||
| SrPDUPowerSupply1Status | 1.3.6.1.4.1.318.1.1.12.4.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Getting this OID will return powerSupply1Ok(1) if power supply 1 is functioning normally. If not functioning normally, this OID will return powerSupply1Failed(2).
| |||||||||||||||||||||
| SrPDUPowerSupply2Status | 1.3.6.1.4.1.318.1.1.12.4.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Getting this OID will return powerSupply2Ok(1) if power supply 2 is functioning normally. If not functioning normally, this OID will return powerSupply2Failed(2). Metered Rack PDUs do not have a redundant powersupply.
| |||||||||||||||||||||
| SrPDUPowerSupplyAlarm | 1.3.6.1.4.1.318.1.1.12.4.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Getting this OID will return powerSupply Alarm
| |||||||||||||||||||||
| NrPDUStatus | 1.3.6.1.4.1.318.1.1.12.5 | ||||||||||||||||||||
| SrPDUStatusBankTableSize | 1.3.6.1.4.1.318.1.1.12.5.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The size of the Status Bank Table | |||||||||||||||||||||
| TrPDUStatusBankTable | 1.3.6.1.4.1.318.1.1.12.5.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting of status of each Rack PDU Bank | |||||||||||||||||||||
| RrPDUStatusBankEntry | 1.3.6.1.4.1.318.1.1.12.5.2.1 | NA | mandatory | ||||||||||||||||||
| CrPDUStatusBankIndex | 1.3.6.1.4.1.318.1.1.12.5.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the RACK PDU Bank entry. | |||||||||||||||||||||
| CrPDUStatusBankNumber | 1.3.6.1.4.1.318.1.1.12.5.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this OID will return the bank number. | |||||||||||||||||||||
| CrPDUStatusBankState | 1.3.6.1.4.1.318.1.1.12.5.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this OID will return the bank load state. bankLoadNormal(1) indicates that the bank is operating properly within the rPDULoadBankConfigLowLoadThreshold and rPDULoadBankConfigNearOverloadThreshold OID values. bankLoadLow(2) indicates that the bank load has dropped below the rPDULoadBankConfigLowLoadThreshold OID value. An SNMP trap will occur when this state is entered or cleared. bankLoadNearOverload(3) indicates that the bank load is greater than or equal to the rPDULoadBankConfigNearOverloadThreshold OID value. An SNMP trap will occur when this state is entered or cleared. bankLoadOverload(4) indicates that the bank load is greater than or equal to the rPDULoadBankConfigOverloadThreshold OID value. An SNMP trap will occur when this state is entered or cleared.
| |||||||||||||||||||||
| SrPDUStatusPhaseTableSize | 1.3.6.1.4.1.318.1.1.12.5.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The size of the Status Phase Table | |||||||||||||||||||||
| TrPDUStatusPhaseTable | 1.3.6.1.4.1.318.1.1.12.5.4 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting of status of each Rack PDU Phase | |||||||||||||||||||||
| RrPDUStatusPhaseEntry | 1.3.6.1.4.1.318.1.1.12.5.4.1 | NA | mandatory | ||||||||||||||||||
| CrPDUStatusPhaseIndex | 1.3.6.1.4.1.318.1.1.12.5.4.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the RACK PDU Phase entry. | |||||||||||||||||||||
| CrPDUStatusPhaseNumber | 1.3.6.1.4.1.318.1.1.12.5.4.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this OID will return the phase number. | |||||||||||||||||||||
| CrPDUStatusPhaseState | 1.3.6.1.4.1.318.1.1.12.5.4.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this OID will return the Phase load state. phaseLoadNormal(1) indicates that the Phase is operating properly within the rPDULoadPhaseConfigLowLoadThreshold and rPDULoadPhaseConfigNearOverloadThreshold OID values. phaseLoadLow(2) indicates that the Phase load has dropped below the rPDULoadPhaseConfigLowLoadThreshold OID value. An SNMP trap will occur when this state is entered or cleared. phaseLoadNearOverload(3) indicates that the Phase load is greater than or equal to the rPDULoadPhaseConfigNearOverloadThreshold OID value. An SNMP trap will occur when this state is entered or cleared. phaseLoadOverload(4) indicates that the Phase load is greater than or equal to the rPDULoadPhaseConfigOverloadThreshold OID value. An SNMP trap will occur when this state is entered or cleared.
| |||||||||||||||||||||
| SrPDUStatusOutletTableSize | 1.3.6.1.4.1.318.1.1.12.5.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The size of the Status Outlet Table | |||||||||||||||||||||
| TrPDUStatusOutletTable | 1.3.6.1.4.1.318.1.1.12.5.6 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting of status of each Outlet of an Outlet Monitored Rack PDU. | |||||||||||||||||||||
| RrPDUStatusOutletEntry | 1.3.6.1.4.1.318.1.1.12.5.6.1 | NA | mandatory | ||||||||||||||||||
| CrPDUStatusOutletIndex | 1.3.6.1.4.1.318.1.1.12.5.6.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the RACK PDU Outlet entry. | |||||||||||||||||||||
| CrPDUStatusOutletNumber | 1.3.6.1.4.1.318.1.1.12.5.6.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this OID will return the Outlet number. | |||||||||||||||||||||
| CrPDUStatusOutletState | 1.3.6.1.4.1.318.1.1.12.5.6.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this OID will return the Outlet load state. outletLoadNormal(1) indicates that the Outlet is operating properly within the rPDUOutletConfigMonitoredLowLoadThreshold and rPDUOutletConfigMonitoredNearOverloadThreshold OID values. outletLoadLow(2) indicates that the Outlet load has dropped below the rPDUOutletConfigMonitoredLowLoadThreshold OID value. An SNMP trap will occur when this state is entered or cleared. outletLoadNearOverload(3) indicates that the Outlet load is greater than or equal to the rPDUOutletConfigMonitoredNearOverloadThreshold OID value. An SNMP trap will occur when this state is entered or cleared. outletLoadOverload(4) indicates that the Outlet load is greater than or equal to the rPDUOutletConfigMonitoredOverloadThreshold OID value. An SNMP trap will occur when this state is entered or cleared.
| |||||||||||||||||||||
| NairConditioners | 1.3.6.1.4.1.318.1.1.13 | ||||||||||||||||||||
| NairFM | 1.3.6.1.4.1.318.1.1.13.1 | ||||||||||||||||||||
| NairFMIdent | 1.3.6.1.4.1.318.1.1.13.1.1 | ||||||||||||||||||||
| SairFMIdentName | 1.3.6.1.4.1.318.1.1.13.1.1.1 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory A character string identifying the device. | |||||||||||||||||||||
| SairFMIdentTableSize | 1.3.6.1.4.1.318.1.1.13.1.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the airFMIdentTable. | |||||||||||||||||||||
| TairFMIdentTable | 1.3.6.1.4.1.318.1.1.13.1.1.3 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting identification information from each module in the system. | |||||||||||||||||||||
| RairFMIdentEntry | 1.3.6.1.4.1.318.1.1.13.1.1.3.1 | NA | mandatory | ||||||||||||||||||
| CairFMIdentModuleIndex | 1.3.6.1.4.1.318.1.1.13.1.1.3.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of the module information. | |||||||||||||||||||||
| CairFMIdentModuleModelNumber | 1.3.6.1.4.1.318.1.1.13.1.1.3.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory A character string identifying the model number. | |||||||||||||||||||||
| CairFMIdentModuleDateOfMfg | 1.3.6.1.4.1.318.1.1.13.1.1.3.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory A character string identifying the manufacture date. | |||||||||||||||||||||
| CairFMIdentModuleSerialNumber | 1.3.6.1.4.1.318.1.1.13.1.1.3.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory A character string identifying the unit serial number. | |||||||||||||||||||||
| CairFMIdentModuleFirmwareRev | 1.3.6.1.4.1.318.1.1.13.1.1.3.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory A character string identifying the firmware revision. | |||||||||||||||||||||
| CairFMIdentModuleHardwareRev | 1.3.6.1.4.1.318.1.1.13.1.1.3.1.6 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory A character string identifying the hardware revision. | |||||||||||||||||||||
| SairFMIdentLocation | 1.3.6.1.4.1.318.1.1.13.1.1.4 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory A character string identifying the location of the device. | |||||||||||||||||||||
| SairFMIdentContact | 1.3.6.1.4.1.318.1.1.13.1.1.5 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory A character string identifying the person to contact regarding the device. | |||||||||||||||||||||
| NairFMStatus | 1.3.6.1.4.1.318.1.1.13.1.2 | ||||||||||||||||||||
| SairFMStatusSystemOn | 1.3.6.1.4.1.318.1.1.13.1.2.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The operating state of the system. This OID has been deprecated in favor of airFMGroupSysStatus.
| |||||||||||||||||||||
| SairFMStatusSystemAverageRetTempC | 1.3.6.1.4.1.318.1.1.13.1.2.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The system average return air temperature in tenths of degrees Celsius. This OID has been deprecated in favor of airFMSysAvgReturnTempC. | |||||||||||||||||||||
| SairFMStatusSystemAverageRetTempF | 1.3.6.1.4.1.318.1.1.13.1.2.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The system average return air temperature in tenths of degrees Fahrenheit. This OID has been deprecated in favor of airFMSysAvgReturnTempF. | |||||||||||||||||||||
| SairFMStatusSystemAverageRetHum | 1.3.6.1.4.1.318.1.1.13.1.2.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The system average return air humidity in tenths of percent RH. This OID has been deprecated in favor of airFMSysAvgReturnHum. | |||||||||||||||||||||
| SairFMStatusSystemActionTempC | 1.3.6.1.4.1.318.1.1.13.1.2.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The system action air temperature in tenths of degrees Celsius. This OID has been deprecated in favor of airFMSysCtrlTempC. | |||||||||||||||||||||
| SairFMStatusSystemActionTempF | 1.3.6.1.4.1.318.1.1.13.1.2.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The system action air temperature in tenths of degrees Fahrenheit. This OID has been deprecated in favor of airFMSysCtrlTempF. | |||||||||||||||||||||
| SairFMStatusSystemActionHum | 1.3.6.1.4.1.318.1.1.13.1.2.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The system action air humidity in tenths of percent RH. This OID has been deprecated in favor of airFMSysCtrlHum. | |||||||||||||||||||||
| SairFMStatusSystemRemoteHighTempC | 1.3.6.1.4.1.318.1.1.13.1.2.8 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The system remote high air temperature in tenths of degrees Celsius. This OID has been deprecated in favor of airFMSysMaxRemoteTempC. | |||||||||||||||||||||
| SairFMStatusSystemRemoteHighTempF | 1.3.6.1.4.1.318.1.1.13.1.2.9 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The system remote high air temperature in tenths of degrees Fahrenheit. This OID has been deprecated in favor of airFMSysMaxRemoteTempF. | |||||||||||||||||||||
| SairFMStatusSystemRemoteAvgTempC | 1.3.6.1.4.1.318.1.1.13.1.2.10 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The system remote average air temperature in tenths of degrees Celsius. This OID has been deprecated in favor of airFMSysAvgRemoteTempC. | |||||||||||||||||||||
| SairFMStatusSystemRemoteAvgTempF | 1.3.6.1.4.1.318.1.1.13.1.2.11 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The system remote average air temperature in tenths of degrees Fahrenheit. This OID has been deprecated in favor of airFMSysAvgRemoteTempF. | |||||||||||||||||||||
| SairFMStatusSystemRemoteAvgHum | 1.3.6.1.4.1.318.1.1.13.1.2.12 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The system remote average air humidity in tenths of percent RH. This OID has been deprecated in favor of airFMSysAvgRemoteHum. | |||||||||||||||||||||
| SairFMStatusSystemRemoteLowTempC | 1.3.6.1.4.1.318.1.1.13.1.2.13 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The system remote low air temperature in tenths of degrees Celsius. This OID has been deprecated in favor of airFMSysMinRemoteTempC. | |||||||||||||||||||||
| SairFMStatusSystemRemoteLowTempF | 1.3.6.1.4.1.318.1.1.13.1.2.14 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The system remote low air temperature in tenths of degrees Fahrenheit. This OID has been deprecated in favor of airFMSysMinRemoteTempF. | |||||||||||||||||||||
| SairFMStatusSystemCoolingEnabled | 1.3.6.1.4.1.318.1.1.13.1.2.15 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The state of the system cooling function enable. This OID has been deprecated in favor of airFMSysCoolState.
| |||||||||||||||||||||
| SairFMStatusSystemReheatingEnabled | 1.3.6.1.4.1.318.1.1.13.1.2.16 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The state of the system reheating function enable. This OID has been deprecated in favor of airFMSysReheatState.
| |||||||||||||||||||||
| SairFMStatusSystemHumidifyEnabled | 1.3.6.1.4.1.318.1.1.13.1.2.17 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The state of the system humidify function enable. This OID has been deprecated in favor of airFMSysHumState.
| |||||||||||||||||||||
| SairFMStatusSystemDehumidifyEnabled | 1.3.6.1.4.1.318.1.1.13.1.2.18 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The state of the system dehumidify function enable. This OID has been deprecated in favor of airFMSysDehumState.
| |||||||||||||||||||||
| SairFMStatusModuleTableSize | 1.3.6.1.4.1.318.1.1.13.1.2.19 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the airFMStatusModuleTable. | |||||||||||||||||||||
| TairFMStatusModuleTable | 1.3.6.1.4.1.318.1.1.13.1.2.20 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting information from each module in the system. | |||||||||||||||||||||
| RairFMStatusModuleEntry | 1.3.6.1.4.1.318.1.1.13.1.2.20.1 | NA | mandatory | ||||||||||||||||||
| CairFMStatusModuleIndex | 1.3.6.1.4.1.318.1.1.13.1.2.20.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of the module information. | |||||||||||||||||||||
| CairFMStatusModuleOutputCapacity | 1.3.6.1.4.1.318.1.1.13.1.2.20.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The module output capacity in kilowatts. This OID has been deprecated in favor of airFMModOutputCapacity. | |||||||||||||||||||||
| CairFMStatusModuleSupplyTempC | 1.3.6.1.4.1.318.1.1.13.1.2.20.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The module supply air temperature in tenths of degrees Celsius. This OID has been deprecated in favor of airFMModSupplyTempC. | |||||||||||||||||||||
| CairFMStatusModuleSupplyTempF | 1.3.6.1.4.1.318.1.1.13.1.2.20.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The module supply air temperature in tenths of degrees Fahrenheit. This OID has been deprecated in favor of airFMModSupplyTempF. | |||||||||||||||||||||
| CairFMStatusModuleSupplyHum | 1.3.6.1.4.1.318.1.1.13.1.2.20.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The module supply air humidity in tenths of percent RH. This OID has been deprecated in favor of airFMModSupplyHum. | |||||||||||||||||||||
| CairFMStatusModuleReturnTempC | 1.3.6.1.4.1.318.1.1.13.1.2.20.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The module return air temperature in tenths of degrees Celsius. This OID has been deprecated in favor of airFMModReturnTempC. | |||||||||||||||||||||
| CairFMStatusModuleReturnTempF | 1.3.6.1.4.1.318.1.1.13.1.2.20.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The module return air temperature in tenths of degrees Fahrenheit. This OID has been deprecated in favor of airFMModReturnTempF. | |||||||||||||||||||||
| CairFMStatusModuleReturnHum | 1.3.6.1.4.1.318.1.1.13.1.2.20.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The module return air humidity in tenths of percent RH. This OID has been deprecated in favor of airFMModReturnHum. | |||||||||||||||||||||
| NairFMGroup | 1.3.6.1.4.1.318.1.1.13.1.3 | ||||||||||||||||||||
| SairFMGroupSysStatus | 1.3.6.1.4.1.318.1.1.13.1.3.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The status of this system within the group.
| |||||||||||||||||||||
| SairFMGroupSysRuntime | 1.3.6.1.4.1.318.1.1.13.1.3.2 | INTEGER | RO | mandatory | -2147483648 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of hours the system has been running. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMGroupSysRole | 1.3.6.1.4.1.318.1.1.13.1.3.3 | INTEGER | RO | mandatory | rolePrimary(1) | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The role of this system within the group.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NairFMGroupSysRoles | 1.3.6.1.4.1.318.1.1.13.1.3.4 | ||||||||||||||||||||
| SairFMGroupSysRolesTableSize | 1.3.6.1.4.1.318.1.1.13.1.3.4.1 | INTEGER | RO | mandatory | 1 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the airFMGroupSysRolesTable. Example values from LibreNMS test devices
| |||||||||||||||||||||
| TairFMGroupSysRolesTable | 1.3.6.1.4.1.318.1.1.13.1.3.4.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting information from each system in the group. | |||||||||||||||||||||
| RairFMGroupSysRolesEntry | 1.3.6.1.4.1.318.1.1.13.1.3.4.2.1 | NA | mandatory | ||||||||||||||||||
| CairFMGroupSysIndex | 1.3.6.1.4.1.318.1.1.13.1.3.4.2.1.1 | INTEGER | RO | mandatory | 1 | ||||||||||||||||
column · INTEGER · read-only · mandatory The index of the system information. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CairFMGroupSysRoleStatus | 1.3.6.1.4.1.318.1.1.13.1.3.4.2.1.2 | INTEGER | RO | mandatory | reserved2(2) | ||||||||||||||||
column · INTEGER · read-only · mandatory The present mode of the System.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CairFMGroupSysPresentRole | 1.3.6.1.4.1.318.1.1.13.1.3.4.2.1.3 | INTEGER | RO | mandatory | backup(2) | ||||||||||||||||
column · INTEGER · read-only · mandatory The present role of the System in a Group.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CairFMGroupSysManualRoleSetting | 1.3.6.1.4.1.318.1.1.13.1.3.4.2.1.4 | INTEGER | RW | mandatory | primary(1) | ||||||||||||||||
column · INTEGER · read-write · mandatory The manual role setting of the System in a Group. Only applies if Role Assignment Method is set to static (Manually Assigned Roles).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CairFMGroupSysRunHours | 1.3.6.1.4.1.318.1.1.13.1.3.4.2.1.5 | INTEGER | RO | mandatory | 0 | ||||||||||||||||
column · INTEGER · read-only · mandatory The total number of hours the System has been contributing to environmental control. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CairFMGroupSysComm | 1.3.6.1.4.1.318.1.1.13.1.3.4.2.1.6 | INTEGER | RO | mandatory | commEstablished(2) | ||||||||||||||||
column · INTEGER · read-only · mandatory Indicates whether a system is communicating with the other Systems in the Group.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CairFMGroupSysIPAddress | 1.3.6.1.4.1.318.1.1.13.1.3.4.2.1.7 | IpAddress | RO | mandatory | 10.14.88.22 | ||||||||||||||||
column · IpAddress · read-only · mandatory The IP Address of the System. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMGroupSysRoleAssignment | 1.3.6.1.4.1.318.1.1.13.1.3.4.3 | INTEGER | RW | mandatory | dynamicAutomatic(2) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory The method used to assign roles (i.e. Primary, Backup) to the Systems in a Group. staticManual: Manually assign Primary or Backup to regulate run hours across the Group. dynamicAutomatic: User indicates the number of Systems that will be assigned a primary role in this Group.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMGroupAutoRoleNumPrimary | 1.3.6.1.4.1.318.1.1.13.1.3.4.4 | INTEGER | RW | mandatory | one(1) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory The number of Systems assigned the 'primary' role in this Group. Only applies if Role Assignment Method is set to dynamic (Automatic Run Hour Balancing).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NairFMGroupCfg | 1.3.6.1.4.1.318.1.1.13.1.3.5 | ||||||||||||||||||||
| SairFMGroupCfgName | 1.3.6.1.4.1.318.1.1.13.1.3.5.1 | DisplayString | RW | mandatory | Unknown | ||||||||||||||||
scalar · DisplayString · read-write · mandatory A character string identifying the group name. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMGroupCfgNumSystems | 1.3.6.1.4.1.318.1.1.13.1.3.5.2 | INTEGER | RW | mandatory | one(1) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory The number of Systems in this Group.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMGroupCfgIdleBlower | 1.3.6.1.4.1.318.1.1.13.1.3.5.3 | INTEGER | RW | mandatory | off(1) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Blower behavior for backup Systems and Systems that have entered a failure mode.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMGroupCfgShutdownSmoke | 1.3.6.1.4.1.318.1.1.13.1.3.5.4 | INTEGER | RW | mandatory | disable(1) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory If enabled, all Systems in the Group will shut down if smoke is detected.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMGroupCfgShutdownFire | 1.3.6.1.4.1.318.1.1.13.1.3.5.5 | INTEGER | RW | mandatory | disable(1) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory If enabled, all Systems in the Group will shut down if fire is detected.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMGroupCfgFailoverCommLoss | 1.3.6.1.4.1.318.1.1.13.1.3.5.6 | INTEGER | RW | mandatory | disable(1) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Failover on Comm Loss enables an available backup System to run in place of a System that has lost communication with the Group.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMGroupCfgDmdFightStatus | 1.3.6.1.4.1.318.1.1.13.1.3.5.7 | INTEGER | RO | mandatory | on(2) | ||||||||||||||||
scalar · INTEGER · read-only · mandatory Demand Fighting and Setpoint Sharing are automatically enabled when a System is responding to a Load Sharing Request.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMGroupCfgDmdFightSetting | 1.3.6.1.4.1.318.1.1.13.1.3.5.8 | INTEGER | RW | mandatory | disable(1) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Demand Fighting prevents a System from engaging reheat in a Group where any System is cooling.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMGroupCfgSetpointShareStatus | 1.3.6.1.4.1.318.1.1.13.1.3.5.9 | INTEGER | RO | mandatory | on(2) | ||||||||||||||||
scalar · INTEGER · read-only · mandatory Demand Fighting and Setpoint Sharing are automatically enabled when a System is responding to Load Sharing Request.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMGroupCfgSetpointShareSetting | 1.3.6.1.4.1.318.1.1.13.1.3.5.10 | INTEGER | RW | mandatory | disable(1) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory All Systems in the Group use the same setpoints.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMGroupCfgResetFieldServiceDefaults | 1.3.6.1.4.1.318.1.1.13.1.3.5.11 | INTEGER | RW | mandatory | 0 | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Setting this OID to reset(2) will reset all Group parameters, which can only be edited by a field service engineer, to their factory default values. Getting this OID will do nothing and return the noOperation(1) value.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NairFMGroupLoadShare | 1.3.6.1.4.1.318.1.1.13.1.3.6 | ||||||||||||||||||||
| SairFMGroupLoadShareCoolRequests | 1.3.6.1.4.1.318.1.1.13.1.3.6.1 | INTEGER | RW | mandatory | disable(1) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Systems that are cooling may request assistance from other Systems in the Group.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMGroupLoadShareCoolThreshC | 1.3.6.1.4.1.318.1.1.13.1.3.6.2 | INTEGER | RW | mandatory | 22 | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Temperature threshold at which a System will generate a load sharing request for cooling. Measured in tenths of degrees Celsius. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMGroupLoadShareCoolThreshF | 1.3.6.1.4.1.318.1.1.13.1.3.6.3 | INTEGER | RW | mandatory | 40 | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Temperature threshold at which a System will generate a load sharing request for cooling. Measured in tenths of degrees Fahrenheit. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMGroupLoadShareReheatRequests | 1.3.6.1.4.1.318.1.1.13.1.3.6.4 | INTEGER | RW | mandatory | disable(1) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Systems that are reheating may request assistance from other Systems in the Group.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMGroupLoadShareReheatThreshC | 1.3.6.1.4.1.318.1.1.13.1.3.6.5 | INTEGER | RW | mandatory | 22 | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Temperature threshold at which a System will generate a load sharing request for reheating. Measured in tenths of degrees Celsius. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMGroupLoadShareReheatThreshF | 1.3.6.1.4.1.318.1.1.13.1.3.6.6 | INTEGER | RW | mandatory | 40 | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Temperature threshold at which a System will generate a load sharing request for reheating. Measured in tenths of degrees Fahrenheit. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMGroupLoadShareHumRequests | 1.3.6.1.4.1.318.1.1.13.1.3.6.7 | INTEGER | RW | mandatory | enable(2) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Systems that are humidifying may request humidification assistance from other Systems in the Group.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMGroupLoadShareHumThresh | 1.3.6.1.4.1.318.1.1.13.1.3.6.8 | INTEGER | RW | mandatory | 100 | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Humidity threshold at which a System will generate a load sharing request for humidification. Measured in tenths of percent relative humidity. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMGroupLoadShareDehumRequests | 1.3.6.1.4.1.318.1.1.13.1.3.6.9 | INTEGER | RW | mandatory | disable(1) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Systems that are dehumidifying may request assistance from other Systems in the Group.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMGroupLoadShareDehumThresh | 1.3.6.1.4.1.318.1.1.13.1.3.6.10 | INTEGER | RW | mandatory | 100 | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Humidity threshold at which a System will generate a load sharing request for dehumidification. Measured in tenths of percent relative humidity. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NairFMGroupFailover | 1.3.6.1.4.1.318.1.1.13.1.3.7 | ||||||||||||||||||||
| NairFMGroupFailoverSys | 1.3.6.1.4.1.318.1.1.13.1.3.7.1 | ||||||||||||||||||||
| SairFMGroupFailoverSysAnyMinorAlarm | 1.3.6.1.4.1.318.1.1.13.1.3.7.1.1 | INTEGER | RW | mandatory | disable(2) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Enabling this OID will cause the system to enter a failure state if any minor system alarm is active. Once in the failure state, environmental control ceases for the system, and the blowers enter the Idle Blower Operation mode. A value of notApplicable indicates that this alarm does not apply to this device due to its configuration.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMGroupFailoverSysAnyMajorAlarm | 1.3.6.1.4.1.318.1.1.13.1.3.7.1.2 | INTEGER | RW | mandatory | disable(2) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Enabling this OID will cause the system to enter a failure state if any major system alarm is active. Once in the failure state, environmental control ceases for the system, and the blowers enter the Idle Blower Operation mode. A value of notApplicable indicates that this alarm does not apply to this device due to its configuration.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMGroupFailoverSysHighEnvTemp | 1.3.6.1.4.1.318.1.1.13.1.3.7.1.3 | INTEGER | RW | mandatory | disable(2) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Enabling this OID will cause the system to enter a failure state if the high environmental temperature alarm is active. Once in the failure state, environmental control ceases for the system, and the blowers enter the Idle Blower Operation mode. A value of notApplicable indicates that this alarm does not apply to this device due to its configuration.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMGroupFailoverSysLowEnvTemp | 1.3.6.1.4.1.318.1.1.13.1.3.7.1.4 | INTEGER | RW | mandatory | disable(2) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Enabling this OID will cause the system to enter a failure state if the low environmental temperature alarm is active. Once in the failure state, environmental control ceases for the system, and the blowers enter the Idle Blower Operation mode. A value of notApplicable indicates that this alarm does not apply to this device due to its configuration.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMGroupFailoverSysHighEnvHum | 1.3.6.1.4.1.318.1.1.13.1.3.7.1.5 | INTEGER | RW | mandatory | disable(2) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Enabling this OID will cause the system to enter a failure state if the high environmental humidity alarm is active. Once in the failure state, environmental control ceases for the system, and the blowers enter the Idle Blower Operation mode. A value of notApplicable indicates that this alarm does not apply to this device due to its configuration.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMGroupFailoverSysLowEnvHum | 1.3.6.1.4.1.318.1.1.13.1.3.7.1.6 | INTEGER | RW | mandatory | disable(2) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Enabling this OID will cause the system to enter a failure state if the low environmental humidity alarm is active. Once in the failure state, environmental control ceases for the system, and the blowers enter the Idle Blower Operation mode. A value of notApplicable indicates that this alarm does not apply to this device due to its configuration.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMGroupFailoverSysFireAlarm | 1.3.6.1.4.1.318.1.1.13.1.3.7.1.7 | INTEGER | RW | mandatory | notApplicable(1) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Enabling this OID will cause the system to enter a failure state if the fire alarm is active. Once in the failure state, environmental control ceases for the system, and the blowers enter the Idle Blower Operation mode. A value of notApplicable indicates that this alarm does not apply to this device due to its configuration.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMGroupFailoverSysSmokeAlarm | 1.3.6.1.4.1.318.1.1.13.1.3.7.1.8 | INTEGER | RW | mandatory | notApplicable(1) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Enabling this OID will cause the system to enter a failure state if the smoke alarm is active. Once in the failure state, environmental control ceases for the system, and the blowers enter the Idle Blower Operation mode. A value of notApplicable indicates that this alarm does not apply to this device due to its configuration.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMGroupFailoverSysCommLost | 1.3.6.1.4.1.318.1.1.13.1.3.7.1.9 | INTEGER | RW | mandatory | notApplicable(1) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Enabling this OID will cause the system to enter a failure state if the system has lost comm. Once in the failure state, environmental control ceases for the system, and the blowers enter the Idle Blower Operation mode. A value of notApplicable indicates that this alarm does not apply to this device due to its configuration.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMGroupFailoverSysSupplySensorFail | 1.3.6.1.4.1.318.1.1.13.1.3.7.1.10 | INTEGER | RW | mandatory | disable(2) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Enabling this OID will cause the system to enter a failure state if the supply sensor has failed. Once in the failure state, environmental control ceases for the system, and the blowers enter the Idle Blower Operation mode. A value of notApplicable indicates that this alarm does not apply to this device due to its configuration.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMGroupFailoverSysReturnSensorFail | 1.3.6.1.4.1.318.1.1.13.1.3.7.1.11 | INTEGER | RW | mandatory | disable(2) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Enabling this OID will cause the system to enter a failure state if the return sensor has failed. Once in the failure state, environmental control ceases for the system, and the blowers enter the Idle Blower Operation mode. A value of notApplicable indicates that this alarm does not apply to this device due to its configuration.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMGroupFailoverSysPrimarySensorFail | 1.3.6.1.4.1.318.1.1.13.1.3.7.1.12 | INTEGER | RW | mandatory | notApplicable(1) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Enabling this OID will cause the system to enter a failure state if the primary sensor has failed. Once in the failure state, environmental control ceases for the system, and the blowers enter the Idle Blower Operation mode. A value of notApplicable indicates that this alarm does not apply to this device due to its configuration.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMGroupFailoverSysSecondarySensorFail | 1.3.6.1.4.1.318.1.1.13.1.3.7.1.13 | INTEGER | RW | mandatory | notApplicable(1) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Enabling this OID will cause the system to enter a failure state if the secondary sensor has failed. Once in the failure state, environmental control ceases for the system, and the blowers enter the Idle Blower Operation mode. A value of notApplicable indicates that this alarm does not apply to this device due to its configuration.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMGroupFailoverSysNoSensorsAvailable | 1.3.6.1.4.1.318.1.1.13.1.3.7.1.14 | INTEGER | RW | mandatory | enable(3) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Enabling this OID will cause the system to enter a failure state if no sensors are available. Once in the failure state, environmental control ceases for the system, and the blowers enter the Idle Blower Operation mode. A value of notApplicable indicates that this alarm does not apply to this device due to its configuration.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NairFMGroupFailoverMod | 1.3.6.1.4.1.318.1.1.13.1.3.7.2 | ||||||||||||||||||||
| SairFMGroupFailoverModMaintRequired | 1.3.6.1.4.1.318.1.1.13.1.3.7.2.1 | INTEGER | RW | mandatory | disable(2) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Enabling this OID will cause the system to enter a failure state if maintenance is required on a module. Once in the failure state, environmental control ceases for the system, and the blowers enter the Idle Blower Operation mode. A value of notApplicable indicates that this alarm does not apply to this device due to its configuration.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMGroupFailoverModCoolFail | 1.3.6.1.4.1.318.1.1.13.1.3.7.2.2 | INTEGER | RW | mandatory | enable(3) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Enabling this OID will cause the system to enter a failure state if cooling has failed on a module. Once in the failure state, environmental control ceases for the system, and the blowers enter the Idle Blower Operation mode. A value of notApplicable indicates that this alarm does not apply to this device due to its configuration.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMGroupFailoverModHumFail | 1.3.6.1.4.1.318.1.1.13.1.3.7.2.3 | INTEGER | RW | mandatory | enable(3) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Enabling this OID will cause the system to enter a failure state if the humidifier has failed on a module. Once in the failure state, environmental control ceases for the system, and the blowers enter the Idle Blower Operation mode. A value of notApplicable indicates that this alarm does not apply to this device due to its configuration.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMGroupFailoverModBlwrCntrl1Fail | 1.3.6.1.4.1.318.1.1.13.1.3.7.2.4 | INTEGER | RW | mandatory | enable(3) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Enabling this OID will cause the system to enter a failure state if blower controller 1 has failed on a module. Once in the failure state, environmental control ceases for the system, and the blowers enter the Idle Blower Operation mode. A value of notApplicable indicates that this alarm does not apply to this device due to its configuration.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMGroupFailoverModBlwrCntrl2Fail | 1.3.6.1.4.1.318.1.1.13.1.3.7.2.5 | INTEGER | RW | mandatory | enable(3) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Enabling this OID will cause the system to enter a failure state if blower controller 2 has failed on a module. Once in the failure state, environmental control ceases for the system, and the blowers enter the Idle Blower Operation mode. A value of notApplicable indicates that this alarm does not apply to this device due to its configuration.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMGroupFailoverModHighFilterDP | 1.3.6.1.4.1.318.1.1.13.1.3.7.2.6 | INTEGER | RW | mandatory | disable(2) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Enabling this OID will cause the system to enter a failure state if a high filter differential pressure is present on a module. Once in the failure state, environmental control ceases for the system, and the blowers enter the Idle Blower Operation mode. A value of notApplicable indicates that this alarm does not apply to this device due to its configuration.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMGroupFailoverModHighSupplyTemp | 1.3.6.1.4.1.318.1.1.13.1.3.7.2.7 | INTEGER | RW | mandatory | disable(2) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Enabling this OID will cause the system to enter a failure state if a high supply temperature is active on a module. Once in the failure state, environmental control ceases for the system, and the blowers enter the Idle Blower Operation mode. A value of notApplicable indicates that this alarm does not apply to this device due to its configuration.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMGroupFailoverModLowSupplyTemp | 1.3.6.1.4.1.318.1.1.13.1.3.7.2.8 | INTEGER | RW | mandatory | disable(2) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Enabling this OID will cause the system to enter a failure state if a low supply temperature is active on a module. Once in the failure state, environmental control ceases for the system, and the blowers enter the Idle Blower Operation mode. A value of notApplicable indicates that this alarm does not apply to this device due to its configuration.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMGroupFailoverModLossOrLowAirFlow | 1.3.6.1.4.1.318.1.1.13.1.3.7.2.9 | INTEGER | RW | mandatory | enable(3) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Enabling this OID will cause the system to enter a failure state if there is a loss of air flow or low air flow on a module. Once in the failure state, environmental control ceases for the system, and the blowers enter the Idle Blower Operation mode. A value of notApplicable indicates that this alarm does not apply to this device due to its configuration.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMGroupFailoverModHumReplaceCylinder | 1.3.6.1.4.1.318.1.1.13.1.3.7.2.10 | INTEGER | RW | mandatory | disable(2) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Enabling this OID will cause the system to enter a failure state if a humidifier needs its cylinder replaced on a module. Once in the failure state, environmental control ceases for the system, and the blowers enter the Idle Blower Operation mode. A value of notApplicable indicates that this alarm does not apply to this device due to its configuration.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMGroupFailoverModAirBlockInterlockOpen | 1.3.6.1.4.1.318.1.1.13.1.3.7.2.11 | INTEGER | RW | mandatory | enable(3) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Enabling this OID will cause the system to enter a failure state if the air block interlock is open on a module. Once in the failure state, environmental control ceases for the system, and the blowers enter the Idle Blower Operation mode. A value of notApplicable indicates that this alarm does not apply to this device due to its configuration.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMGroupFailoverModWaterDetected | 1.3.6.1.4.1.318.1.1.13.1.3.7.2.12 | INTEGER | RW | mandatory | notApplicable(1) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Enabling this OID will cause the system to enter a failure state if water is detected by a module. Once in the failure state, environmental control ceases for the system, and the blowers enter the Idle Blower Operation mode. A value of notApplicable indicates that this alarm does not apply to this device due to its configuration.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMGroupFailoverModCondensatePumpFail | 1.3.6.1.4.1.318.1.1.13.1.3.7.2.13 | INTEGER | RW | mandatory | enable(3) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Enabling this OID will cause the system to enter a failure state if the condensate pump has failed in a module. Once in the failure state, environmental control ceases for the system, and the blowers enter the Idle Blower Operation mode. A value of notApplicable indicates that this alarm does not apply to this device due to its configuration.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NairFMSystem | 1.3.6.1.4.1.318.1.1.13.1.4 | ||||||||||||||||||||
| NairFMSysStatus | 1.3.6.1.4.1.318.1.1.13.1.4.1 | ||||||||||||||||||||
| SairFMSysNumber | 1.3.6.1.4.1.318.1.1.13.1.4.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of the system within the group. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| SairFMSysPresentStatus | 1.3.6.1.4.1.318.1.1.13.1.4.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The present mode of the System. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| SairFMSysPresentRole | 1.3.6.1.4.1.318.1.1.13.1.4.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The present role of the System in the Group. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| SairFMSysRunHours | 1.3.6.1.4.1.318.1.1.13.1.4.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The total number of hours the System has been contributing to environmental control. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysCoilFluidTempC | 1.3.6.1.4.1.318.1.1.13.1.4.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The temperature of the coolant at the fluid coil inlet. Measured in degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysCoilFluidTempF | 1.3.6.1.4.1.318.1.1.13.1.4.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The temperature of the coolant at the fluid coil inlet. Measured in degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysHotWaterTempC | 1.3.6.1.4.1.318.1.1.13.1.4.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The hot water temperature. Measured in degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysHotWaterTempF | 1.3.6.1.4.1.318.1.1.13.1.4.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The hot water temperature. Measured in degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysAvgReturnTempC | 1.3.6.1.4.1.318.1.1.13.1.4.1.9 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The average return temperature calculated from all present modules. Measured in tenths of degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysAvgReturnTempF | 1.3.6.1.4.1.318.1.1.13.1.4.1.10 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The average return temperature calculated from all present modules. Measured in tenths of degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysAvgReturnHum | 1.3.6.1.4.1.318.1.1.13.1.4.1.11 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The average return humidity calculated from all present modules. Measured in tenths of percent RH. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysAvgRemoteTempC | 1.3.6.1.4.1.318.1.1.13.1.4.1.12 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The average temperature calculated from all operational remote sensors. Measured in tenths of degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysAvgRemoteTempF | 1.3.6.1.4.1.318.1.1.13.1.4.1.13 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The average temperature calculated from all operational remote sensors. Measured in tenths of degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysAvgRemoteHum | 1.3.6.1.4.1.318.1.1.13.1.4.1.14 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The average return humidity calculated from all present modules. Measured in tenths of percent RH. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysMaxRemoteTempC | 1.3.6.1.4.1.318.1.1.13.1.4.1.15 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The maximum temperature reading from all operational remote sensors. Measured in tenths of degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysMaxRemoteTempF | 1.3.6.1.4.1.318.1.1.13.1.4.1.16 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The maximum temperature reading from all operational remote sensors. Measured in tenths of degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysMinRemoteTempC | 1.3.6.1.4.1.318.1.1.13.1.4.1.17 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The minimum temperature reading from all operational remote sensors. Measured in tenths of degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysMinRemoteTempF | 1.3.6.1.4.1.318.1.1.13.1.4.1.18 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The minimum temperature reading from all operational remote sensors. Measured in tenths of degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysTempCtrlMethod | 1.3.6.1.4.1.318.1.1.13.1.4.1.19 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The method of environment temperature control selected to regulate the temperature. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| SairFMSysActualTempCtrlMethod | 1.3.6.1.4.1.318.1.1.13.1.4.1.20 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The actual method of environment temperature control being used to regulate the temperature. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| SairFMSysHumCtrlMethod | 1.3.6.1.4.1.318.1.1.13.1.4.1.21 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The method of environment humidity control selected to regulate the humidity. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| SairFMSysActualHumCtrlMethod | 1.3.6.1.4.1.318.1.1.13.1.4.1.22 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The actual method of environment humidity control being used to regulate the humidity. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| SairFMSysCtrlTempC | 1.3.6.1.4.1.318.1.1.13.1.4.1.23 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The system environmental control air temperature from the sensor denoted by airFMSysActualTempCtrl. Measured in tenths of degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysCtrlTempF | 1.3.6.1.4.1.318.1.1.13.1.4.1.24 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The system environmental control air temperature from the sensor denoted by airFMSysActualTempCtrl. Measured in tenths of degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysCtrlHum | 1.3.6.1.4.1.318.1.1.13.1.4.1.25 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The system environmental control air humidity from the sensor denoted by airFMSysActualHumCtrl. Measured in percent relative humidity. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| NairFMSysDemands | 1.3.6.1.4.1.318.1.1.13.1.4.2 | ||||||||||||||||||||
| SairFMSysDXCoolingDmd | 1.3.6.1.4.1.318.1.1.13.1.4.2.1 | INTEGER | RO | mandatory | 50 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The direct expansion cooling output demanded by the System. Measured in percent. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMSysDXDehumDmd | 1.3.6.1.4.1.318.1.1.13.1.4.2.2 | INTEGER | RO | mandatory | 0 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The direct expansion dehumidification output demanded by the System. Measured in percent. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMSysDXActualCoolDehum | 1.3.6.1.4.1.318.1.1.13.1.4.2.3 | INTEGER | RO | mandatory | 50 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The direct expansion cooling or dehumidification output measured by the System. Measured in percent. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMSysCoilFluidCoolDmd | 1.3.6.1.4.1.318.1.1.13.1.4.2.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The fluid coil cooling output demanded by the System. Measured in percent. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysCoilFluidDehumDmd | 1.3.6.1.4.1.318.1.1.13.1.4.2.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The fluid coil dehumidification output demanded by the System. Measured in percent. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysCoilFluidActualCoolDehum | 1.3.6.1.4.1.318.1.1.13.1.4.2.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The fluid coil cooling or dehumidification output measured by the System. Measured in percent. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysElectricReheatDmd | 1.3.6.1.4.1.318.1.1.13.1.4.2.7 | INTEGER | RO | mandatory | 0 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The electric reheating output demanded by the System. Measured in percent. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMSysActualElectricReheat | 1.3.6.1.4.1.318.1.1.13.1.4.2.8 | INTEGER | RO | mandatory | 0 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The electric reheating output of the System. Measured in percent. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMSysSteamHotGasReheatDmd | 1.3.6.1.4.1.318.1.1.13.1.4.2.9 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The steam, hot water, or hot gas reheating output demanded by the System. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| SairFMSysActualSteamHotGasReheat | 1.3.6.1.4.1.318.1.1.13.1.4.2.10 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The steam, hot water, or hot gas reheating output of the System. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| SairFMSysSteamElectrodeHumDmd | 1.3.6.1.4.1.318.1.1.13.1.4.2.11 | INTEGER | RO | mandatory | 28 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The steam electrode humidification output demanded by the System. Measured in percent. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMSysActualSteamElectrodeHum | 1.3.6.1.4.1.318.1.1.13.1.4.2.12 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The average steam electrode humidification output measured for the Modules in the System. Measured in percent. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysSteamHumDmd | 1.3.6.1.4.1.318.1.1.13.1.4.2.13 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The steam humidification output demanded by the System. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| SairFMSysActualSteamHum | 1.3.6.1.4.1.318.1.1.13.1.4.2.14 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The steam humidification output for the System. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| NairFMSysSetup | 1.3.6.1.4.1.318.1.1.13.1.4.3 | ||||||||||||||||||||
| SairFMSysNumModules | 1.3.6.1.4.1.318.1.1.13.1.4.3.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of Modules in this System. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| SairFMSysNumPCIOMs | 1.3.6.1.4.1.318.1.1.13.1.4.3.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of Programmable Customer Input/Output Modules (PCIOMs) installed in the Main Module of this System. Each PCIOM adds four input contacts and four output relays to the System. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| SairFMSysMainsVlt | 1.3.6.1.4.1.318.1.1.13.1.4.3.3 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The mains voltage for the Modules in this System. A value of N/A indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysUPSVlt | 1.3.6.1.4.1.318.1.1.13.1.4.3.4 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The UPS voltage for the Modules in this System. A value of N/A indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysCoilCfg | 1.3.6.1.4.1.318.1.1.13.1.4.3.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The type of cooling coils installed in the Modules in this System: DX coil, DX and MultiCool (chilled water) coils, DX and Economizer coils, or only a Chilled Liquid coil. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| SairFMSysRefrigType | 1.3.6.1.4.1.318.1.1.13.1.4.3.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The type of refrigerant used by each compressor in the system. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| SairFMSysHeatRejection | 1.3.6.1.4.1.318.1.1.13.1.4.3.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The method the Modules in this System use to transfer heat away from the refrigerant. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| SairFMSysDischAirPtrn | 1.3.6.1.4.1.318.1.1.13.1.4.3.8 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The discharge air pattern for the Modules in this System. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| SairFMSysAirFltr | 1.3.6.1.4.1.318.1.1.13.1.4.3.9 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The type of air filters (standard or high efficiency) installed in the Modules of this System. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| SairFMSysFlowSwitch | 1.3.6.1.4.1.318.1.1.13.1.4.3.10 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The location of the optional flow switch. None: No flow switch is installed in this System. DX: Coolant input to the heat exchanger (condenser). MultiCool: Chilled water input to the MultiCool coil. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| SairFMSysCoilFluidVlvAct | 1.3.6.1.4.1.318.1.1.13.1.4.3.11 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The type of valve actuator installed on the coil fluid valve. The coil fluid valve controls the flow of coolant into a fluid cooling coil, such as a MultiCool or Economizer coil. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| SairFMSysCoilFluidVlvType | 1.3.6.1.4.1.318.1.1.13.1.4.3.12 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The type of coil fluid valve installed for the Modules in this System. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| SairFMSysCndsrFluidVlvAct | 1.3.6.1.4.1.318.1.1.13.1.4.3.13 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The type of valve actuator installed on the Condenser fluid valve. The Condenser fluid valve controls the flow of coolant into the heat exchanger (condenser) to regulate head pressure. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| SairFMSysCndsrFluidVlvType | 1.3.6.1.4.1.318.1.1.13.1.4.3.14 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The type of Condenser fluid valve installed for the Modules in this System. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| SairFMSysHotWaterVlvAct | 1.3.6.1.4.1.318.1.1.13.1.4.3.15 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The type of valve actuator installed on the hot water valve. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| SairFMSysNumRemoteSensors | 1.3.6.1.4.1.318.1.1.13.1.4.3.16 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of remote sensors detected by the system. | |||||||||||||||||||||
| NairFMSysConfig | 1.3.6.1.4.1.318.1.1.13.1.4.4 | ||||||||||||||||||||
| SairFMSysPrimaryControlSensor | 1.3.6.1.4.1.318.1.1.13.1.4.4.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Selects whether return or remote sensors will control the system. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| SairFMSysRemoteSensorData | 1.3.6.1.4.1.318.1.1.13.1.4.4.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Selects whether average temperature or max temperature will be used when remote sensors are selected for control of the system. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| SairFMSysFastStartup | 1.3.6.1.4.1.318.1.1.13.1.4.4.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Minimizes the time for the cooling process to begin after other delay constraints have been met. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| SairFMSysStartupDelay | 1.3.6.1.4.1.318.1.1.13.1.4.4.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Set the delay that begins when power is applied and ends when the System starts. This allows you to create a staged restart among your Systems after a power loss. Measured in seconds. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysModeDelay | 1.3.6.1.4.1.318.1.1.13.1.4.4.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Set the delay between starting the blowers and engaging the modes. It allows the sensors to read room conditions accurately and allows the controller to check for major alarms before engaging a mode. Measured in seconds. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysCommLossShutdownDelay | 1.3.6.1.4.1.318.1.1.13.1.4.4.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Set the delay between an Expansion Module losing communication with the Main Module and the Expansion Module shutting down. A value of -1 will keep the Expansion Module running after a communication loss. Measured in hours. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysResetSysFailure | 1.3.6.1.4.1.318.1.1.13.1.4.4.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Setting this OID to reset(2) will allows the system to return from any failure condition, if the failure(s) have cleared. Getting this OID will do nothing and return the noOperation(1) value. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| SairFMSysResetUserDflts | 1.3.6.1.4.1.318.1.1.13.1.4.4.8 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Setting this OID to reset(2) will reset all system parameters that can be edited by the user to their factory default values. Getting this OID will do nothing and return the noOperation(1) value. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| SairFMSysResetFldSrvcDflts | 1.3.6.1.4.1.318.1.1.13.1.4.4.9 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Setting this OID to reset(2) will reset all system parameters that can only be edited by the field service engineer to their factory default values. Getting this OID will do nothing and return the noOperation(1) value. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| SairFMSysResetRunHours | 1.3.6.1.4.1.318.1.1.13.1.4.4.10 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Setting this OID to reset(2) will reset the system Run Hours. Getting this OID will do nothing and return the noOperation(1) value. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| NairFMSysCooling | 1.3.6.1.4.1.318.1.1.13.1.4.5 | ||||||||||||||||||||
| SairFMSysCompMinOnTime | 1.3.6.1.4.1.318.1.1.13.1.4.5.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Set the minimum time the compressor continues to operate after it is started. The delay protects the compressor from damage. Caution: Reducing this delay shortens compressor life. Measured in seconds. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysCompMinOffTime | 1.3.6.1.4.1.318.1.1.13.1.4.5.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Set the minimum time the compressor will remain off after it ceases operation. The delay protects the compressor from damage. Caution: Reducing this delay shortens compressor life. Measured in seconds. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysCompRotPeriod | 1.3.6.1.4.1.318.1.1.13.1.4.5.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Set how often to perform compressor runtime balancing. Measured in hours. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysEconIsolVlvOpenDelay | 1.3.6.1.4.1.318.1.1.13.1.4.5.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Set the delay between opening the Economizer Isolator output relay and engaging the compressors. Measured in seconds. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysEconIsolVlvCloseDelay | 1.3.6.1.4.1.318.1.1.13.1.4.5.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Set the delay between disengaging the compressor and closing the Economizer Isolator output relay. Measured in seconds. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysCndsrFluidVlvCloseDelay | 1.3.6.1.4.1.318.1.1.13.1.4.5.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Set the time the condenser valve remains open after the compressors disengage. Measured in seconds. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysInterstageDelay | 1.3.6.1.4.1.318.1.1.13.1.4.5.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The DX interstage delay allows the first compressor's cooling to take effect before engaging the second compressor. This prevents the second compressor from cycling on and off excessively. Measured in seconds. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysCoolState | 1.3.6.1.4.1.318.1.1.13.1.4.5.8 | INTEGER | RW | mandatory | enabled(3) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Set the mode to enabled or disabled. Disabled modes will not operate, and you cannot make changes to their settings while they are disabled. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMSysCoolEssFunction | 1.3.6.1.4.1.318.1.1.13.1.4.5.9 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Set the priority of the mode for alarms and events with the nonessential stop behavior. Nonessential modes are disabled during nonessential stop alarms and events. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| SairFMSysCoolSetpointC | 1.3.6.1.4.1.318.1.1.13.1.4.5.10 | INTEGER | RW | mandatory | 222 | ||||||||||||||||
scalar · INTEGER · read-write · mandatory The target value for the selected control sensor air for this mode. It must be at least 1.0 C above the reheat setpoint if a heater is installed. Measured in tenths of degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMSysCoolSetpointF | 1.3.6.1.4.1.318.1.1.13.1.4.5.11 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The target value for the selected control sensor air for this mode. It must be at least 1.0 C above the reheat setpoint if a heater is installed. Measured in tenths of degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysCoolDeadbandC | 1.3.6.1.4.1.318.1.1.13.1.4.5.12 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The temperature range that controls output when the selected control sensor temperature is above the setpoint. At the top of this range, the cool mode outputs at 100%. The deadband does not apply to PID- controlled modes. Measured in tenths of degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysCoolDeadbandF | 1.3.6.1.4.1.318.1.1.13.1.4.5.13 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The temperature range that controls output when the selected control sensor temperature is above the setpoint. At the top of this range, the cool mode outputs at 100%. The deadband does not apply to PID- controlled modes. Measured in tenths of degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysCoolEconIsolFunction | 1.3.6.1.4.1.318.1.1.13.1.4.5.14 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Set the Economizer Automatic Coolant Isolation valve to enabled or disabled. This valve anticipates a cooling demand and opens the coil fluid valve. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| SairFMSysSuctPresCompensation | 1.3.6.1.4.1.318.1.1.13.1.4.5.15 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Set the Suction Pressure Compensation to enabled or disabled. This function attempts to keep the suction pressure from exceeding 95 psi. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| SairFMSysCoilFluidActivThreshC | 1.3.6.1.4.1.318.1.1.13.1.4.5.16 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The minimum coolant temperature required to use the optional MultiCool or Economizer coil. Measured in tenths of degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysCoilFluidActivThreshF | 1.3.6.1.4.1.318.1.1.13.1.4.5.17 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The minimum coolant temperature required to use the optional MultiCool or Economizer coil. Measured in tenths of degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysCoilFluidActivDeadbandC | 1.3.6.1.4.1.318.1.1.13.1.4.5.18 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The controller will disengage the MultiCool or Economizer coil when the coolant temperature reaches the coil fluid temperature activation threshold plus the deadband. Measured in tenths of degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysCoilFluidActivDeadbandF | 1.3.6.1.4.1.318.1.1.13.1.4.5.19 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The controller will disengage the MultiCool or Economizer coil when the coolant temperature reaches the coil fluid temperature activation threshold plus the deadband. Measured in tenths of degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysCoolPIDMethod | 1.3.6.1.4.1.318.1.1.13.1.4.5.20 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Set the multipliers that the PID algorithm will use to calculate the cool output. Proportional, Proportional + Integral, or Proportional + Integral + Derivative. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| SairFMSysCoolPIDGainP | 1.3.6.1.4.1.318.1.1.13.1.4.5.21 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Set the proportional multiplier to correct for differences between the selected control sensor actual temperature and the setpoint. Measured in %/C. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysCoolPIDResetRateI | 1.3.6.1.4.1.318.1.1.13.1.4.5.22 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Set the integral multiplier to correct for the proportional offset. Measured in %/(C * min). A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysCoolPIDDerivativeD | 1.3.6.1.4.1.318.1.1.13.1.4.5.23 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Set the derivative multiplier to counteract overshoot and droop during changes in the room load. Measured in %/(C / min). A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| NairFMSysHumidify | 1.3.6.1.4.1.318.1.1.13.1.4.6 | ||||||||||||||||||||
| SairFMSysHumState | 1.3.6.1.4.1.318.1.1.13.1.4.6.1 | INTEGER | RW | mandatory | enabled(3) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Set the mode to enabled or disabled. Disabled modes will not operate, and you cannot make changes to their settings while they are disabled. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMSysHumEssFunction | 1.3.6.1.4.1.318.1.1.13.1.4.6.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Set the priority of the mode for alarms and events with the nonessential stop behavior. Nonessential modes are disabled during nonessential stop alarms and events. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| SairFMSysHumSetpoint | 1.3.6.1.4.1.318.1.1.13.1.4.6.3 | INTEGER | RW | mandatory | 450 | ||||||||||||||||
scalar · INTEGER · read-write · mandatory The target value for the selected control sensor air for this mode. It must be at least 1.0 % RH below the dehumidification setpoint. Measured in tenths of percent relative humidity. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMSysHumDeadband | 1.3.6.1.4.1.318.1.1.13.1.4.6.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The humidity range that controls output when the selected control sensor humidity is below the setpoint. At the top of this range, the humidification mode outputs at 100%. The deadband does not apply to PID-controlled modes. Measured in tenths of percent relative humidity. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysHumCtrlSetting | 1.3.6.1.4.1.318.1.1.13.1.4.6.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Set the method to control the humidity in the room. The two methods are Relative Humidity (RH) or Dew Point of the selected control sensor air. The dew point method helps correct for hot spots near the selected control sensors. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| SairFMSysActualHumCtrl | 1.3.6.1.4.1.318.1.1.13.1.4.6.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The humidity control method the system is using. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| SairFMSysHumSensBand | 1.3.6.1.4.1.318.1.1.13.1.4.6.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The percentage of relative humidity below the setpoint at which the humidifier will output at 100% of capacity. Measured in percent relative humidity. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| NairFMSysDehumidify | 1.3.6.1.4.1.318.1.1.13.1.4.7 | ||||||||||||||||||||
| SairFMSysDehumState | 1.3.6.1.4.1.318.1.1.13.1.4.7.1 | INTEGER | RW | mandatory | enabled(3) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Set the mode to enabled or disabled. Disabled modes will not operate, and you cannot make changes to their settings while they are disabled. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMSysDehumEssFunction | 1.3.6.1.4.1.318.1.1.13.1.4.7.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Set the priority of the mode for alarms and events with the nonessential stop behavior. Nonessential modes are disabled during nonessential stop alarms and events. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| SairFMSysDehumSetpoint | 1.3.6.1.4.1.318.1.1.13.1.4.7.3 | INTEGER | RW | mandatory | 550 | ||||||||||||||||
scalar · INTEGER · read-write · mandatory The target value for the selected control sensor air for this mode. It must be at least 1.0 % RH above the humidification setpoint if a humidifier is installed. Measured in tenths of percent relative humidity. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMSysDehumDeadband | 1.3.6.1.4.1.318.1.1.13.1.4.7.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The humidity range above the setpoint at which the dehumidification mode will output at 100%. The deadband does not apply to PID controlled modes. Measured in tenths of percent relative humidity. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysDehumCapacity | 1.3.6.1.4.1.318.1.1.13.1.4.7.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Set the dehumidification mode to use either half of the cooling coil or the full coil when dehumidifying the room. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| SairFMSysDehumPIDMethod | 1.3.6.1.4.1.318.1.1.13.1.4.7.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Set the multipliers that the PID algorithm will use to calculate the output. Proportional, Proportional + Integral, or Proportional + Integral + Derivative. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| SairFMSysDehumPIDGainP | 1.3.6.1.4.1.318.1.1.13.1.4.7.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Set the proportional multiplier to correct for differences between the selected control sensor actual humidity and the setpoint. Measured in %/%RH. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysDehumPIDResetRateI | 1.3.6.1.4.1.318.1.1.13.1.4.7.8 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Set the integral multiplier to correct for the proportional offset. Measured in %/(%RH * min). A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysDehumPIDDerivativeD | 1.3.6.1.4.1.318.1.1.13.1.4.7.9 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Set the derivative multiplier to counteract overshoot and droop during changes in the room humidity. Measure in %/(%RH / min). A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| NairFMSysReheat | 1.3.6.1.4.1.318.1.1.13.1.4.8 | ||||||||||||||||||||
| SairFMSysReheatState | 1.3.6.1.4.1.318.1.1.13.1.4.8.1 | INTEGER | RW | mandatory | enabled(3) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Set the mode to enabled or disabled. Disabled modes will not operate, and you cannot make changes to their settings while they are disabled. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMSysReheatEssFunction | 1.3.6.1.4.1.318.1.1.13.1.4.8.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Set the priority of the mode for alarms and events with the nonessential stop behavior. Nonessential modes are disabled during nonessential stop alarms and events. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| SairFMSysReheatSetpointC | 1.3.6.1.4.1.318.1.1.13.1.4.8.3 | INTEGER | RW | mandatory | 200 | ||||||||||||||||
scalar · INTEGER · read-write · mandatory The target value for the selected control sensor air for this mode. It must be at least 1.0 C below the cooling setpoint. Measured in tenths of degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairFMSysReheatSetpointF | 1.3.6.1.4.1.318.1.1.13.1.4.8.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The target value for the selected control sensor air for this mode. It must be at least 1.0 C below the cooling setpoint. Measured in tenths of degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysReheatDeadbandC | 1.3.6.1.4.1.318.1.1.13.1.4.8.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The temperature range that controls output when the selected control sensor temperature is below the setpoint. At the bottom of this range, the reheat mode outputs at 100%. The deadband does not apply to PID-controlled modes. Measured in tenths of degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysReheatDeadbandF | 1.3.6.1.4.1.318.1.1.13.1.4.8.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The temperature range that controls output when the selected control sensor temperature is below the setpoint. At the bottom of this range, the reheat mode outputs at 100%. The deadband does not apply to PID-controlled modes. Measured in tenths of degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysReheatPIDMethod | 1.3.6.1.4.1.318.1.1.13.1.4.8.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Set the multipliers that the PID algorithm will use to calculate the output. Proportional, Proportional + Integral, or Proportional + Integral + Derivative. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| SairFMSysReheatPIDGainP | 1.3.6.1.4.1.318.1.1.13.1.4.8.8 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Set the proportional multiplier to correct for differences between the selected control sensor actual temperature and the setpoint. Measured in %/C. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysReheatPIDResetRateI | 1.3.6.1.4.1.318.1.1.13.1.4.8.9 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Set the integral multiplier to correct for the proportional offset. Measured in %/(C * min). A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysReheatPIDDerivativeD | 1.3.6.1.4.1.318.1.1.13.1.4.8.10 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Set the derivative multiplier to counteract overshoot and droop during changes in the room load. Measured in %/(C / min). A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| NairFMSysThresholds | 1.3.6.1.4.1.318.1.1.13.1.4.9 | ||||||||||||||||||||
| SairFMSysHighSplyTempC | 1.3.6.1.4.1.318.1.1.13.1.4.9.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The high temperature threshold for air blown into the room (supply). If the supply temperature exceeds the threshold, an alarm will occur. Measured in tenths of degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysHighSplyTempF | 1.3.6.1.4.1.318.1.1.13.1.4.9.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The high temperature threshold for air blown into the room (supply). If the supply temperature exceeds the threshold, an alarm will occur. Measured in tenths of degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysLowSplyTempC | 1.3.6.1.4.1.318.1.1.13.1.4.9.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The low temperature threshold for air blown into the room (supply). If the supply temperature drops below the threshold, an alarm will occur. Measured in tenths of degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysLowSplyTempF | 1.3.6.1.4.1.318.1.1.13.1.4.9.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The low temperature threshold for air blown into the room (supply). If the supply temperature drops below the threshold, an alarm will occur. Measured in tenths of degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysHighCoilFluidTempC | 1.3.6.1.4.1.318.1.1.13.1.4.9.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The high temperature threshold for coolant at the inlet to the fluid coil. If the fluid coil coolant temperature exceeds the threshold, an alarm will occur. Measured in tenths of degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysHighCoilFluidTempF | 1.3.6.1.4.1.318.1.1.13.1.4.9.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The high temperature threshold for coolant at the inlet to the fluid coil. If the fluid coil coolant temperature exceeds the threshold, an alarm will occur. Measured in tenths of degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysLowCoilFluidTempC | 1.3.6.1.4.1.318.1.1.13.1.4.9.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The low temperature threshold for coolant at the inlet to the fluid coil. If the fluid coil coolant temperature drops below the threshold, an alarm will occur. Measured in tenths of degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysLowCoilFluidTempF | 1.3.6.1.4.1.318.1.1.13.1.4.9.8 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The low temperature threshold for coolant at the inlet to the fluid coil. If the fluid coil coolant temperature drops below the threshold, an alarm will occur. Measured in tenths of degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysHighCtrlTempC | 1.3.6.1.4.1.318.1.1.13.1.4.9.9 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The high temperature threshold for air monitored by the System. If the temperature exceeds the threshold, an alarm will occur. Measured in tenths of degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysHighCtrlTempF | 1.3.6.1.4.1.318.1.1.13.1.4.9.10 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The high temperature threshold for air monitored by the System. If the temperature exceeds the threshold, an alarm will occur. Measured in tenths of degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysLowCtrlTempC | 1.3.6.1.4.1.318.1.1.13.1.4.9.11 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The low temperature threshold for air monitored by the System. If the temperature drops below the threshold, an alarm will occur. Measured in tenths of degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysLowCtrlTempF | 1.3.6.1.4.1.318.1.1.13.1.4.9.12 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The low temperature threshold for air monitored by the System. If the temperature drops below the threshold, an alarm will occur. Measured in tenths of degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysHighCtrlHum | 1.3.6.1.4.1.318.1.1.13.1.4.9.13 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The high humidity threshold for air monitored by the System. If the humidity exceeds the threshold, an alarm will occur. Measured in tenths of percent relative humidity. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysLowCtrlHum | 1.3.6.1.4.1.318.1.1.13.1.4.9.14 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The low humidity threshold for air monitored by the System. If the humidity drops below the threshold, an alarm will occur. Measured in tenths of percent relative humidity. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysTempAlarmDelay | 1.3.6.1.4.1.318.1.1.13.1.4.9.15 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The amount of time the blower must be on before a temperature alarm can be issued. Measured in seconds. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMSysHumAlarmDelay | 1.3.6.1.4.1.318.1.1.13.1.4.9.16 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The amount of time the blower must be on before a humidity alarm can be issued. Measured in seconds. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| NairFMSysInputs | 1.3.6.1.4.1.318.1.1.13.1.4.10 | ||||||||||||||||||||
| SairFMSysInputTableSize | 1.3.6.1.4.1.318.1.1.13.1.4.10.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the airFMSysInputTable. | |||||||||||||||||||||
| TairFMSysInputTable | 1.3.6.1.4.1.318.1.1.13.1.4.10.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting information from each input contact. | |||||||||||||||||||||
| RairFMSysInputEntry | 1.3.6.1.4.1.318.1.1.13.1.4.10.2.1 | NA | mandatory | ||||||||||||||||||
| CairFMSysInputIndex | 1.3.6.1.4.1.318.1.1.13.1.4.10.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The number designator of the Input Contact. | |||||||||||||||||||||
| CairFMSysInputName | 1.3.6.1.4.1.318.1.1.13.1.4.10.2.1.2 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The configurable name for the Input Contact. Maximum text input is 13 characters. | |||||||||||||||||||||
| CairFMSysInputStatus | 1.3.6.1.4.1.318.1.1.13.1.4.10.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The state of this contact: Open or Closed. A violation will occur when this relay is not in its normal state.
| |||||||||||||||||||||
| CairFMSysInputNormalState | 1.3.6.1.4.1.318.1.1.13.1.4.10.2.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Set the normal state of this contact (the state when no alarm/event exists).
| |||||||||||||||||||||
| CairFMSysInputDelay | 1.3.6.1.4.1.318.1.1.13.1.4.10.2.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Set the delay between this contact exiting its normal state and an alarm being triggered. Measured in seconds. | |||||||||||||||||||||
| CairFMSysInputAlarmAction | 1.3.6.1.4.1.318.1.1.13.1.4.10.2.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Sets the behavior for this contact when it exits its normal state.
| |||||||||||||||||||||
| NairFMSysOutputs | 1.3.6.1.4.1.318.1.1.13.1.4.11 | ||||||||||||||||||||
| SairFMSysOutputTableSize | 1.3.6.1.4.1.318.1.1.13.1.4.11.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the airFMSysOutputTable. | |||||||||||||||||||||
| TairFMSysOutputTable | 1.3.6.1.4.1.318.1.1.13.1.4.11.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting information from each output relay. | |||||||||||||||||||||
| RairFMSysOutputEntry | 1.3.6.1.4.1.318.1.1.13.1.4.11.2.1 | NA | mandatory | ||||||||||||||||||
| CairFMSysOutputIndex | 1.3.6.1.4.1.318.1.1.13.1.4.11.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The number designator of the output relay. | |||||||||||||||||||||
| CairFMSysOutputStatus | 1.3.6.1.4.1.318.1.1.13.1.4.11.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The state of this relay: Open or Closed. A violation will occur when this relay is not in its normal state.
| |||||||||||||||||||||
| CairFMSysOutputNormalState | 1.3.6.1.4.1.318.1.1.13.1.4.11.2.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Set the normal state of this relay (the state when no alarm/event exists).
| |||||||||||||||||||||
| NairFMSysAlarmMap | 1.3.6.1.4.1.318.1.1.13.1.4.12 | ||||||||||||||||||||
| NairFMSysAlarmMapSys | 1.3.6.1.4.1.318.1.1.13.1.4.12.1 | ||||||||||||||||||||
| SairFMSysAlarmMapSysTableSize | 1.3.6.1.4.1.318.1.1.13.1.4.12.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the airFMSysAlarmMapSysTable. | |||||||||||||||||||||
| TairFMSysAlarmMapSysTable | 1.3.6.1.4.1.318.1.1.13.1.4.12.1.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting alarm map information. | |||||||||||||||||||||
| RairFMSysAlarmMapSysEntry | 1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The system alarm map type to reference. | |||||||||||||||||||||
| CairFMSysAlarmMapSysOutputIndex | 1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of the output relay. | |||||||||||||||||||||
| CairFMSysAlarmMapSysAnyAlarm | 1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.2 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory System alarm map setting for Any Alarm. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapSystemOn | 1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory System alarm map setting for System On. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapSystemOffline | 1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory System alarm map setting for System Offline. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapSysHighEnvTemp | 1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory System alarm map setting for High Environmental Temperature. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapSysLowEnvTemp | 1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory System alarm map setting for Low Environmental Temperature. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapSysHighEnvHum | 1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory System alarm map setting for High Environmental Humidity. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapSysLowEnvHum | 1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.8 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory System alarm map setting for Low Environmental Humidity. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapSysFireDet | 1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.9 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory System alarm map setting for Fire Detected. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapSysSmokeDet | 1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.10 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory System alarm map setting for Smoke Detected. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapSysEconIsol | 1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.11 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory System alarm map setting for Econ Isolator. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapSysSupplySensFail | 1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.12 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory System alarm map setting for Supply Sensor Failure. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapSysReturnSensFail | 1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.13 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory System alarm map setting for Return Sensor Failure. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapSysRemSensRemoved | 1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.14 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory System alarm map setting for Remote Sensor Removed. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapSysPrimSensFail | 1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.15 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory System alarm map setting for Primary Sensor Failure. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapSysSecSensFail | 1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.16 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory System alarm map setting for Secondary Sensor Failure. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapSysSecSensActive | 1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.17 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory System alarm map setting for Secondary Sensor Active. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| NairFMSysAlarmMapMainMod | 1.3.6.1.4.1.318.1.1.13.1.4.12.2 | ||||||||||||||||||||
| SairFMSysAlarmMapMainModTableSize | 1.3.6.1.4.1.318.1.1.13.1.4.12.2.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the airFMSysAlarmMapMainModTable. | |||||||||||||||||||||
| TairFMSysAlarmMapMainModTable | 1.3.6.1.4.1.318.1.1.13.1.4.12.2.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting alarm map information. | |||||||||||||||||||||
| RairFMSysAlarmMapMainModEntry | 1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The main module alarm map type to reference. | |||||||||||||||||||||
| CairFMSysAlarmMapMainModOutputIndex | 1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of the output relay. | |||||||||||||||||||||
| CairFMSysAlarmMapMainModAnyAlarm | 1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.2 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Main Module alarm map setting for Any Alarm. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapMainModMaintReq | 1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Main Module alarm map setting for Module Maintenance Required. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapMainModCoolFail | 1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Main Module alarm map setting for Module Cooling Failure. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapMainModHighSupplyTemp | 1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Main Module alarm map setting for High Supply Temperature. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapMainModLowSupplyTemp | 1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Main Module alarm map setting for Low Supply Temperature. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapMainModHumFail | 1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Main Module alarm map setting for Humidifier Failure. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapMainModHumReplCyl | 1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.8 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Main Module alarm map setting for Humidifier Replace Cylinder. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapMainModCondPumpFail | 1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.9 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Main Module alarm map setting for Condensate Pump Failure. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapMainModBlwrCntl1Fail | 1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.10 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Main Module alarm map setting for Blower Controller 1 Failure. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapMainModBlwrCntl2Fail | 1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.11 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Main Module alarm map setting for Blower Controller 2 Failure. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapMainModHighFltrDP | 1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.12 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Main Module alarm map setting for High Filter Differential Pressure. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapMainModLowAirFlow | 1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.13 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Main Module alarm map setting for Low Air Flow. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapMainModAirBlckIntOpen | 1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.14 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Main Module alarm map setting for Air Block Interlock Open. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapMainModWaterDetected | 1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.15 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Main Module alarm map setting for Water Detected. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| NairFMSysAlarmMapExpMod1 | 1.3.6.1.4.1.318.1.1.13.1.4.12.3 | ||||||||||||||||||||
| SairFMSysAlarmMapExpMod1TableSize | 1.3.6.1.4.1.318.1.1.13.1.4.12.3.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the airFMSysAlarmMapExpMod1Table. | |||||||||||||||||||||
| TairFMSysAlarmMapExpMod1Table | 1.3.6.1.4.1.318.1.1.13.1.4.12.3.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting alarm map information. | |||||||||||||||||||||
| RairFMSysAlarmMapExpMod1Entry | 1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The expansion module 1 alarm map type to reference. | |||||||||||||||||||||
| CairFMSysAlarmMapExpMod1OutputIndex | 1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of the output relay. | |||||||||||||||||||||
| CairFMSysAlarmMapExpMod1AnyAlarm | 1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.2 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Exp Module 1 alarm map setting for Any Alarm. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapExpMod1MaintReq | 1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Exp Module 1 alarm map setting for Module Maintenance Required. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapExpMod1CoolFail | 1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Exp Module 1 alarm map setting for Module Cooling Failure. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapExpMod1HighSupplyTemp | 1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Exp Module 1 alarm map setting for High Supply Temperature. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapExpMod1LowSupplyTemp | 1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Exp Module 1 alarm map setting for Low Supply Temperature. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapExpMod1HumFail | 1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Exp Module 1 alarm map setting for Humidifier Failure. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapExpMod1HumReplCyl | 1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.8 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Exp Module 1 alarm map setting for Humidifier Replace Cylinder. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapExpMod1CondPumpFail | 1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.9 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Exp Module 1 alarm map setting for Condensate Pump Failure. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapExpMod1BlwrCntl1Fail | 1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.10 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Exp Module 1 alarm map setting for Blower Controller 1 Failure. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapExpMod1BlwrCntl2Fail | 1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.11 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Exp Module 1 alarm map setting for Blower Controller 2 Failure. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapExpMod1HighFltrDP | 1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.12 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Exp Module 1 alarm map setting for High Filter Differential Pressure. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapExpMod1LowAirFlow | 1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.13 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Exp Module 1 alarm map setting for Low Air Flow. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapExpMod1AirBlckIntOpen | 1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.14 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Exp Module 1 alarm map setting for Air Block Interlock Open. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapExpMod1WaterDetected | 1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.15 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Exp Module 1 alarm map setting for Water Detected. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| NairFMSysAlarmMapExpMod2 | 1.3.6.1.4.1.318.1.1.13.1.4.12.4 | ||||||||||||||||||||
| SairFMSysAlarmMapExpMod2TableSize | 1.3.6.1.4.1.318.1.1.13.1.4.12.4.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the airFMSysAlarmMapExpMod2Table. | |||||||||||||||||||||
| TairFMSysAlarmMapExpMod2Table | 1.3.6.1.4.1.318.1.1.13.1.4.12.4.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting alarm map information. | |||||||||||||||||||||
| RairFMSysAlarmMapExpMod2Entry | 1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The expansion module 2 alarm map type to reference. | |||||||||||||||||||||
| CairFMSysAlarmMapExpMod2OutputIndex | 1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of the output relay. | |||||||||||||||||||||
| CairFMSysAlarmMapExpMod2AnyAlarm | 1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.2 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Exp Module 2 alarm map setting for Any Alarm. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapExpMod2MaintReq | 1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Exp Module 2 alarm map setting for Module Maintenance Required. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapExpMod2CoolFail | 1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Exp Module 2 alarm map setting for Module Cooling Failure. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapExpMod2HighSupplyTemp | 1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Exp Module 2 alarm map setting for High Supply Temperature. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapExpMod2LowSupplyTemp | 1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Exp Module 2 alarm map setting for Low Supply Temperature. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapExpMod2HumFail | 1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Exp Module 2 alarm map setting for Humidifier Failure. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapExpMod2HumReplCyl | 1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.8 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Exp Module 2 alarm map setting for Humidifier Replace Cylinder. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapExpMod2CondPumpFail | 1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.9 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Exp Module 2 alarm map setting for Condensate Pump Failure. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapExpMod2BlwrCntl1Fail | 1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.10 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Exp Module 2 alarm map setting for Blower Controller 1 Failure. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapExpMod2BlwrCntl2Fail | 1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.11 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Exp Module 2 alarm map setting for Blower Controller 2 Failure. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapExpMod2HighFltrDP | 1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.12 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Exp Module 2 alarm map setting for High Filter Differential Pressure. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapExpMod2LowAirFlow | 1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.13 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Exp Module 2 alarm map setting for Low Air Flow. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapExpMod2AirBlckIntOpen | 1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.14 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Exp Module 2 alarm map setting for Air Block Interlock Open. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapExpMod2WaterDetected | 1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.15 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Exp Module 2 alarm map setting for Water Detected. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| NairFMSysAlarmMapInput | 1.3.6.1.4.1.318.1.1.13.1.4.12.5 | ||||||||||||||||||||
| SairFMSysAlarmMapInputTableSize | 1.3.6.1.4.1.318.1.1.13.1.4.12.5.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the airFMSysAlarmMapInputTable. | |||||||||||||||||||||
| TairFMSysAlarmMapInputTable | 1.3.6.1.4.1.318.1.1.13.1.4.12.5.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting alarm map information. | |||||||||||||||||||||
| RairFMSysAlarmMapInputEntry | 1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The input contact alarm map type to reference. | |||||||||||||||||||||
| CairFMSysAlarmMapInputOutputIndex | 1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of the output relay. | |||||||||||||||||||||
| CairFMSysAlarmMapInput1 | 1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.2 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Input contact 1 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapInput2 | 1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Input contact 2 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapInput3 | 1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Input contact 3 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapInput4 | 1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Input contact 4 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapInput5 | 1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Input contact 5 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapInput6 | 1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Input contact 6 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapInput7 | 1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.8 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Input contact 7 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapInput8 | 1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.9 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Input contact 8 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapInput9 | 1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.10 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Input contact 9 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapInput10 | 1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.11 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Input contact 10 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapInput11 | 1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.12 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Input contact 11 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapInput12 | 1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.13 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Input contact 12 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapInput13 | 1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.14 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Input contact 13 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapInput14 | 1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.15 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Input contact 14 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapInput15 | 1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.16 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Input contact 15 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapInput16 | 1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.17 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Input contact 16 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| NairFMSysAlarmMapOutput | 1.3.6.1.4.1.318.1.1.13.1.4.12.6 | ||||||||||||||||||||
| SairFMSysAlarmMapOutputTableSize | 1.3.6.1.4.1.318.1.1.13.1.4.12.6.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the airFMSysAlarmMapOutputTable. | |||||||||||||||||||||
| TairFMSysAlarmMapOutputTable | 1.3.6.1.4.1.318.1.1.13.1.4.12.6.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting alarm map information. | |||||||||||||||||||||
| RairFMSysAlarmMapOutputEntry | 1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The input contact alarm map type to reference. | |||||||||||||||||||||
| CairFMSysAlarmMapOutputIndex | 1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of the output relay. | |||||||||||||||||||||
| CairFMSysAlarmMapOutput1 | 1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.2 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Output relay 1 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapOutput2 | 1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Output relay 2 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapOutput3 | 1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Output relay 3 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapOutput4 | 1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Output relay 4 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapOutput5 | 1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Output relay 5 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapOutput6 | 1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Output relay 6 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapOutput7 | 1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.8 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Output relay 7 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapOutput8 | 1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.9 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Output relay 8 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapOutput9 | 1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.10 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Output relay 9 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapOutput10 | 1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.11 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Output relay 10 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapOutput11 | 1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.12 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Output relay 11 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapOutput12 | 1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.13 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Output relay 12 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapOutput13 | 1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.14 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Output relay 13 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapOutput14 | 1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.15 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Output relay 14 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapOutput15 | 1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.16 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Output relay 15 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMSysAlarmMapOutput16 | 1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.17 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Output relay 16 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| NairFMModule | 1.3.6.1.4.1.318.1.1.13.1.5 | ||||||||||||||||||||
| NairFMModIdent | 1.3.6.1.4.1.318.1.1.13.1.5.1 | ||||||||||||||||||||
| SairFMModIdentTableSize | 1.3.6.1.4.1.318.1.1.13.1.5.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the airFMModIdentTable. | |||||||||||||||||||||
| TairFMModIdentTable | 1.3.6.1.4.1.318.1.1.13.1.5.1.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting information from each module in the system. | |||||||||||||||||||||
| RairFMModIdentEntry | 1.3.6.1.4.1.318.1.1.13.1.5.1.2.1 | NA | mandatory | ||||||||||||||||||
| CairFMModIdentModuleIndex | 1.3.6.1.4.1.318.1.1.13.1.5.1.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of the module. | |||||||||||||||||||||
| CairFMModModelNumber | 1.3.6.1.4.1.318.1.1.13.1.5.1.2.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory Model number of the Module. | |||||||||||||||||||||
| CairFMModSerialNumber | 1.3.6.1.4.1.318.1.1.13.1.5.1.2.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory Unique identification number for this Module. | |||||||||||||||||||||
| CairFMModManufactureDate | 1.3.6.1.4.1.318.1.1.13.1.5.1.2.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory Date the Module was manufactured. | |||||||||||||||||||||
| CairFMModFirmwareRev | 1.3.6.1.4.1.318.1.1.13.1.5.1.2.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory Revision number of the firmware installed on this Module. | |||||||||||||||||||||
| CairFMModHardwareRev | 1.3.6.1.4.1.318.1.1.13.1.5.1.2.1.6 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory Revision number of the hardware installed on this Module. | |||||||||||||||||||||
| NairFMModStatus | 1.3.6.1.4.1.318.1.1.13.1.5.2 | ||||||||||||||||||||
| SairFMModStatusTableSize | 1.3.6.1.4.1.318.1.1.13.1.5.2.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the airFMModStatusTable. | |||||||||||||||||||||
| TairFMModStatusTable | 1.3.6.1.4.1.318.1.1.13.1.5.2.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting information from each module in the system. | |||||||||||||||||||||
| RairFMModStatusEntry | 1.3.6.1.4.1.318.1.1.13.1.5.2.2.1 | NA | mandatory | ||||||||||||||||||
| CairFMModStatusModuleIndex | 1.3.6.1.4.1.318.1.1.13.1.5.2.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of the module. | |||||||||||||||||||||
| CairFMModSupplyTempC | 1.3.6.1.4.1.318.1.1.13.1.5.2.2.1.2 | INTEGER | RO | mandatory | 148 | ||||||||||||||||
column · INTEGER · read-only · mandatory The temperature measured at the supply sensor. Measured in tenths of degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CairFMModSupplyTempF | 1.3.6.1.4.1.318.1.1.13.1.5.2.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The temperature measured at the supply sensor. Measured in tenths of degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| CairFMModSupplyHum | 1.3.6.1.4.1.318.1.1.13.1.5.2.2.1.4 | INTEGER | RO | mandatory | 719 | ||||||||||||||||
column · INTEGER · read-only · mandatory The humidity measured at the supply sensor. Measured in tenths of percent relative humidity. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CairFMModReturnTempC | 1.3.6.1.4.1.318.1.1.13.1.5.2.2.1.5 | INTEGER | RO | mandatory | 225 | ||||||||||||||||
column · INTEGER · read-only · mandatory The temperature measured at the return sensor. Measured in tenths of degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CairFMModReturnTempF | 1.3.6.1.4.1.318.1.1.13.1.5.2.2.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The temperature measured at the return sensor. Measured in tenths of degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| CairFMModReturnHum | 1.3.6.1.4.1.318.1.1.13.1.5.2.2.1.7 | INTEGER | RO | mandatory | 436 | ||||||||||||||||
column · INTEGER · read-only · mandatory The humidity measured at the return sensor. Measured in tenths of percent relative humidity. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CairFMModFilterDiffPresPa | 1.3.6.1.4.1.318.1.1.13.1.5.2.2.1.8 | INTEGER | RO | mandatory | 0 | ||||||||||||||||
column · INTEGER · read-only · mandatory The difference in pressure on either side of the air filters. A high differential pressure indicates a clogged filter. Measured in Pascals. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CairFMModFilterDiffPresInWC | 1.3.6.1.4.1.318.1.1.13.1.5.2.2.1.9 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The difference in pressure on either side of the air filters. A high differential pressure indicates a clogged filter. Measured in hundredths of inches water column. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| CairFMModCoilDiffPresPa | 1.3.6.1.4.1.318.1.1.13.1.5.2.2.1.10 | INTEGER | RO | mandatory | 122 | ||||||||||||||||
column · INTEGER · read-only · mandatory The difference in pressure on either side of the cooling/dehumidification coils. Measured in Pascals. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CairFMModCoilDiffPresInWC | 1.3.6.1.4.1.318.1.1.13.1.5.2.2.1.11 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The difference in pressure on either side of the cooling/dehumidification coils. Measured in hundredths of inches water column. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| NairFMModProperties | 1.3.6.1.4.1.318.1.1.13.1.5.3 | ||||||||||||||||||||
| SairFMModPropTableSize | 1.3.6.1.4.1.318.1.1.13.1.5.3.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the airFMModPropTable. | |||||||||||||||||||||
| TairFMModPropTable | 1.3.6.1.4.1.318.1.1.13.1.5.3.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting information from each module in the system. | |||||||||||||||||||||
| RairFMModPropEntry | 1.3.6.1.4.1.318.1.1.13.1.5.3.2.1 | NA | mandatory | ||||||||||||||||||
| CairFMModPropModuleIndex | 1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of the module. | |||||||||||||||||||||
| CairFMModOutputCapacity | 1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The cooling capacity (in Kilowatts) of the displayed Module. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMModCapacityCtrl | 1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The method used to load and unload the compressors. Tandem compressor Modules use two stages (one compressor each). Single compressor Modules use hot gas bypass. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMModHeaterType | 1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The type of reheating device installed in this Module. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMModElectricHeaterType | 1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The type/capacity of the electric heater, if installed. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMModHumidifierType | 1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The type of equipment installed in the Module to run the humidification mode. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMModBlwrFreqSetting | 1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Frequency of the blower in tenths of hertz. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| CairFMModNomCoilDiffPresPa | 1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The difference in pressure on either side of the cooling/dehumidification coils. Measured in Pascals. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| CairFMModNomCoilDiffPresInWC | 1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.9 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The difference in pressure on either side of the cooling/dehumidification coils. Measured in hundredths of inches water column. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| CairFMModCondPump | 1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.10 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Indicates the presence of a condensate pump in the Modules of this System. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMModFireDetector | 1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.11 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Indicates the presence of a fire detector for each of the Modules in this System. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMModSmokeDetector | 1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.12 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Indicates the presence of a smoke detector for each of the Modules in this System. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMModWaterDetector | 1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.13 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Indicates the presence of a water leak detector for each of the Modules in this System. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| NairFMModCooling | 1.3.6.1.4.1.318.1.1.13.1.5.4 | ||||||||||||||||||||
| SairFMModCoolTableSize | 1.3.6.1.4.1.318.1.1.13.1.5.4.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the airFMModCoolTable. | |||||||||||||||||||||
| TairFMModCoolTable | 1.3.6.1.4.1.318.1.1.13.1.5.4.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting information from each module in the system. | |||||||||||||||||||||
| RairFMModCoolEntry | 1.3.6.1.4.1.318.1.1.13.1.5.4.2.1 | NA | mandatory | ||||||||||||||||||
| CairFMModCoolModuleIndex | 1.3.6.1.4.1.318.1.1.13.1.5.4.2.1.1 | INTEGER | RO | mandatory | 1 | ||||||||||||||||
column · INTEGER · read-only · mandatory The index of the module. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CairFMModComp1 | 1.3.6.1.4.1.318.1.1.13.1.5.4.2.1.2 | INTEGER | RO | mandatory | off(3) | ||||||||||||||||
column · INTEGER · read-only · mandatory The status of compressor 1 of the tandem compressor unit (on or off). A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CairFMModComp2 | 1.3.6.1.4.1.318.1.1.13.1.5.4.2.1.3 | INTEGER | RO | mandatory | on(2) | ||||||||||||||||
column · INTEGER · read-only · mandatory The status of compressor 2 of the tandem compressor unit (on or off). A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CairFMModSuctPresKPa | 1.3.6.1.4.1.318.1.1.13.1.5.4.2.1.4 | INTEGER | RO | mandatory | 531 | ||||||||||||||||
column · INTEGER · read-only · mandatory The refrigerant pressure measured at the suction inlet of the compressor. Measured in kiloPascals. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CairFMModSuctPresPSI | 1.3.6.1.4.1.318.1.1.13.1.5.4.2.1.5 | INTEGER | RO | mandatory | 76 | ||||||||||||||||
column · INTEGER · read-only · mandatory The refrigerant pressure measured at the suction inlet of the compressor. Measured in pounds per square inch. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CairFMModDischPresKPa | 1.3.6.1.4.1.318.1.1.13.1.5.4.2.1.6 | INTEGER | RO | mandatory | 1427 | ||||||||||||||||
column · INTEGER · read-only · mandatory The refrigerant pressure measured at the discharge outlet of the compressor. Measured in kiloPascals. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CairFMModDischPresPSI | 1.3.6.1.4.1.318.1.1.13.1.5.4.2.1.7 | INTEGER | RO | mandatory | 205 | ||||||||||||||||
column · INTEGER · read-only · mandatory The refrigerant pressure measured at the discharge outlet of the compressor. Measured in pounds per square inch. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CairFMModCondFluidVlvPos | 1.3.6.1.4.1.318.1.1.13.1.5.4.2.1.8 | INTEGER | RO | mandatory | -2147483648 | ||||||||||||||||
column · INTEGER · read-only · mandatory The position of the condenser fluid valve. The valve regulates the flow of liquid coolant into the heat exchanger (condenser). 100% indicates the valve is completely open, and 0% indicates that the valve is closed. Measured in percent. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CairFMModCoilFluidVlvPos | 1.3.6.1.4.1.318.1.1.13.1.5.4.2.1.9 | INTEGER | RO | mandatory | -2147483648 | ||||||||||||||||
column · INTEGER · read-only · mandatory The position of the coil fluid valve. The valve regulates the flow of liquid coolant in the fluid cooling coil (MultiCool, Economizer, or Chilled Water). 100% indicates the valve is completely open, and 0% indicates that the valve is closed. Measured in percent. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NairFMModHumidity | 1.3.6.1.4.1.318.1.1.13.1.5.5 | ||||||||||||||||||||
| SairFMModHumTableSize | 1.3.6.1.4.1.318.1.1.13.1.5.5.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the airFMModHumTable. | |||||||||||||||||||||
| TairFMModHumTable | 1.3.6.1.4.1.318.1.1.13.1.5.5.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting information from each module in the system. | |||||||||||||||||||||
| RairFMModHumEntry | 1.3.6.1.4.1.318.1.1.13.1.5.5.2.1 | NA | mandatory | ||||||||||||||||||
| CairFMModHumModuleIndex | 1.3.6.1.4.1.318.1.1.13.1.5.5.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of the module. | |||||||||||||||||||||
| CairFMModHumidifier | 1.3.6.1.4.1.318.1.1.13.1.5.5.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The type of equipment installed in the Module to run the humidification mode. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMModElectrodeCurrent | 1.3.6.1.4.1.318.1.1.13.1.5.5.2.1.3 | INTEGER | RO | mandatory | 0 | ||||||||||||||||
column · INTEGER · read-only · mandatory The current drawn by the electrodes of the steam cylinder humidifier. Measured in tenths of amps. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CairFMModHumActualOutput | 1.3.6.1.4.1.318.1.1.13.1.5.5.2.1.4 | INTEGER | RO | mandatory | 34 | ||||||||||||||||
column · INTEGER · read-only · mandatory The humidification output of an individual Module. Measured in percent. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CairFMModWaterConductivity | 1.3.6.1.4.1.318.1.1.13.1.5.5.2.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The conductivity of the water in the humidifier cylinder. Measured in microSiemens per centimeter. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| CairFMModHotWaterVlvPos | 1.3.6.1.4.1.318.1.1.13.1.5.5.2.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The position of the hot water valve. 100% indicates the valve is completely open, and 0% indicates that the valve is closed. Measured in percent. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| CairFMModStmElectHumMode | 1.3.6.1.4.1.318.1.1.13.1.5.5.2.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Set the humidifier function mode. Off: Remove power from electrodes. Auto: Humidifier controlled by Module controller. Drain: Remove power from electrodes and drain the cylinder. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| NairFMModBlower1 | 1.3.6.1.4.1.318.1.1.13.1.5.6 | ||||||||||||||||||||
| SairFMModBlwr1TableSize | 1.3.6.1.4.1.318.1.1.13.1.5.6.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the airFMModBlwr1Table. | |||||||||||||||||||||
| TairFMModBlwr1Table | 1.3.6.1.4.1.318.1.1.13.1.5.6.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting information from each module in the system. | |||||||||||||||||||||
| RairFMModBlwr1Entry | 1.3.6.1.4.1.318.1.1.13.1.5.6.2.1 | NA | mandatory | ||||||||||||||||||
| CairFMModBlwr1ModuleIndex | 1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of the module. | |||||||||||||||||||||
| CairFMModBlwr1CtrlType | 1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The type of blower controller. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMModBlwr1CmdFreq | 1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.3 | INTEGER | RO | mandatory | 428 | ||||||||||||||||
column · INTEGER · read-only · mandatory The requested operating frequency for the blower. Measured in tenths of hertz. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CairFMModBlwr1ActFreq | 1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.4 | INTEGER | RO | mandatory | 428 | ||||||||||||||||
column · INTEGER · read-only · mandatory The frequency at which the blower controller is operating. Measured in tenths of hertz. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CairFMModBlwr1Poles | 1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The number of poles of the blower motor that the blower controller is controlling. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| CairFMModBlwr1RatedHorsePower | 1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The power rating of the blower motor. Measured in hundredths of horsepower. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| CairFMModBlwr1RatedCurrent | 1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The current rating of the blower motor. Measured in hundredths of amps. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| CairFMModBlwr1ActTorq | 1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.8 | INTEGER | RO | mandatory | 6242 | ||||||||||||||||
column · INTEGER · read-only · mandatory The actual torque of the blower motor. Measured in hundredths of percent. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CairFMModBlwr1Current | 1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.9 | INTEGER | RO | mandatory | 5891 | ||||||||||||||||
column · INTEGER · read-only · mandatory The percent of rated current drawn by the blower motor. Measured in hundredths of percent. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CairFMModBlwr1Vlt | 1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.10 | INTEGER | RO | mandatory | 2435 | ||||||||||||||||
column · INTEGER · read-only · mandatory The voltage supplied to the blower motor. Measured in tenths of volts RMS. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CairFMModBlwr1DCLinkVlt | 1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.11 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The voltage of the blower controller's DC bus. Measured in volts DC. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| CairFMModBlwr1AccTime | 1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.12 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The time to accelerate the blower to the specified frequency. Measured in tenths of seconds. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| CairFMModBlwr1DecTime | 1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.13 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The time to decelerate the blower frequency to zero. Measured in tenths of seconds. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| CairFMModBlwr1CapLife | 1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.14 | INTEGER | RO | mandatory | 1000 | ||||||||||||||||
column · INTEGER · read-only · mandatory The remaining life of the main circuit capacitor. Measured in tenths of percent. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CairFMModBlwr1CtrlCoolFanLife | 1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.15 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The total operation time of the blower controller cooling fan. Measured in hours. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| CairFMModBlwr1ElOvMode | 1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.16 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Enables or disables the electronic overload relay. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMModBlwr1ElOvSetting | 1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.17 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The electronic overload relay is activated when the current exceeds this threshold. Measured in hundredths of amps. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| CairFMModBlwr1ElOvTimeConst | 1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.18 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The delay between the current exceeding the overload threshold and the activation of the electronic overload relay. Measured in tenths of minutes. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| CairFMModBlwr1FanPower | 1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.19 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The actual power of the blower motor. Measured in tenths of percent. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| CairFMModBlwr1HeatsinkTempC | 1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.20 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The temperature of the heatsink on the blower controller. Measured in degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| CairFMModBlwr1HeatsinkTempF | 1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.21 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The temperature of the heatsink on the blower controller. Measured in degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| CairFMModBlwr1ChokeTempC | 1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.22 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The temperature of the choke on the blower controller. Measured in degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| CairFMModBlwr1ChokeTempF | 1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.23 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The temperature of the choke on the blower controller. Measured in degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| CairFMModBlwr1InverterTempC | 1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.24 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The temperature of the inverter on the blower controller. Measured in degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| CairFMModBlwr1InverterTempF | 1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.25 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The temperature of the inverter on the blower controller. Measured in degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| NairFMModBlower2 | 1.3.6.1.4.1.318.1.1.13.1.5.7 | ||||||||||||||||||||
| SairFMModBlwr2TableSize | 1.3.6.1.4.1.318.1.1.13.1.5.7.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the airFMModBlwr2Table. | |||||||||||||||||||||
| TairFMModBlwr2Table | 1.3.6.1.4.1.318.1.1.13.1.5.7.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting information from each module in the system. | |||||||||||||||||||||
| RairFMModBlwr2Entry | 1.3.6.1.4.1.318.1.1.13.1.5.7.2.1 | NA | mandatory | ||||||||||||||||||
| CairFMModBlwr2ModuleIndex | 1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of the module. | |||||||||||||||||||||
| CairFMModBlwr2CtrlType | 1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The type of blower controller. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMModBlwr2CmdFreq | 1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.3 | INTEGER | RO | mandatory | 428 | ||||||||||||||||
column · INTEGER · read-only · mandatory The requested operating frequency for the blower. Measured in tenths of hertz. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CairFMModBlwr2ActFreq | 1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.4 | INTEGER | RO | mandatory | 428 | ||||||||||||||||
column · INTEGER · read-only · mandatory The frequency at which the blower controller is operating. Measured in tenths of hertz. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CairFMModBlwr2Poles | 1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The number of poles of the blower motor that the blower controller is controlling. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| CairFMModBlwr2RatedHorsePower | 1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The power rating of the blower motor. Measured in hundredths of horsepower. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| CairFMModBlwr2RatedCurrent | 1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The current rating of the blower motor. Measured in hundredths of amps. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| CairFMModBlwr2ActTorq | 1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.8 | INTEGER | RO | mandatory | 5026 | ||||||||||||||||
column · INTEGER · read-only · mandatory The actual torque of the blower motor. Measured in hundredths of percent. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CairFMModBlwr2Current | 1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.9 | INTEGER | RO | mandatory | 4597 | ||||||||||||||||
column · INTEGER · read-only · mandatory The percent of rated current drawn by the blower motor. Measured in hundredths of percent. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CairFMModBlwr2Vlt | 1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.10 | INTEGER | RO | mandatory | 2437 | ||||||||||||||||
column · INTEGER · read-only · mandatory The voltage supplied to the blower motor. Measured in tenths of volts RMS. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CairFMModBlwr2DCLinkVlt | 1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.11 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The voltage of the blower controller's DC bus. Measured in volts DC. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| CairFMModBlwr2AccTime | 1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.12 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The time to accelerate the blower to the specified frequency. Measured in tenths of seconds. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| CairFMModBlwr2DecTime | 1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.13 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The time to decelerate the blower frequency to zero. Measured in tenths of seconds. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| CairFMModBlwr2CapLife | 1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.14 | INTEGER | RO | mandatory | 1000 | ||||||||||||||||
column · INTEGER · read-only · mandatory The remaining life of the main circuit capacitor. Measured in tenths of percent. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CairFMModBlwr2CtrlCoolFanLife | 1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.15 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The total operation time of the blower controller cooling fan. Measured in hours. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| CairFMModBlwr2ElOvMode | 1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.16 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Enables or disables the electronic overload relay. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMModBlwr2ElOvSetting | 1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.17 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The electronic overload relay is activated when the current exceeds this threshold. Measured in hundredths of amps. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| CairFMModBlwr2ElOvTimeConst | 1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.18 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The delay between the current exceeding the overload threshold and the activation of the electronic overload relay. Measured in tenths of minutes. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| CairFMModBlwr2FanPower | 1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.19 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The actual power of the blower motor. Measured in tenths of percent. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| CairFMModBlwr2HeatsinkTempC | 1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.20 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The temperature of the heatsink on the blower controller. Measured in degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| CairFMModBlwr2HeatsinkTempF | 1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.21 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The temperature of the heatsink on the blower controller. Measured in degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| CairFMModBlwr2ChokeTempC | 1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.22 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The temperature of the choke on the blower controller. Measured in degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| CairFMModBlwr2ChokeTempF | 1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.23 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The temperature of the choke on the blower controller. Measured in degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| CairFMModBlwr2InverterTempC | 1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.24 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The temperature of the inverter on the blower controller. Measured in degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| CairFMModBlwr2InverterTempF | 1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.25 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The temperature of the inverter on the blower controller. Measured in degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| NairFMModRunHours | 1.3.6.1.4.1.318.1.1.13.1.5.8 | ||||||||||||||||||||
| SairFMModRHTableSize | 1.3.6.1.4.1.318.1.1.13.1.5.8.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the airFMModRHTable. | |||||||||||||||||||||
| TairFMModRHTable | 1.3.6.1.4.1.318.1.1.13.1.5.8.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting information from each module in the system. | |||||||||||||||||||||
| RairFMModRHEntry | 1.3.6.1.4.1.318.1.1.13.1.5.8.2.1 | NA | mandatory | ||||||||||||||||||
| CairFMModRHModuleIndex | 1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of the module. | |||||||||||||||||||||
| CairFMModRHComp1 | 1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Compressor 1 run hours. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| CairFMModRHComp2 | 1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Compressor 2 run hours. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| CairFMModRHHeater | 1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Heater run hours. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| CairFMModRHHum | 1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Humidifier run hours A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| CairFMModRHBlwr1 | 1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Blower 1 run hours. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| CairFMModRHBlwr2 | 1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Blower 2 run hours. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| CairFMModRHBlwrCtrl1 | 1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Blower Controller 1 run hours. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| CairFMModRHBlwrCtrl2 | 1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.9 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Blower Controller 2 run hours. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| CairFMModRHComp1Reset | 1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.10 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Reset the compressor 1 run hours. Getting this OID will do nothing and return the noOperation value. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMModRHComp2Reset | 1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.11 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Reset the compressor 2 run hours. Getting this OID will do nothing and return the noOperation value. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMModRHHeaterReset | 1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.12 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Reset the heater run hours. Getting this OID will do nothing and return the noOperation value. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMModRHHumReset | 1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.13 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Reset the humidifier run hours. Getting this OID will do nothing and return the noOperation value. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMModRHBlwr1Reset | 1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.14 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Reset the blower 1 run hours. Getting this OID will do nothing and return the noOperation value. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMModRHBlwr2Reset | 1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.15 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Reset the blower 2 run hours. Getting this OID will do nothing and return the noOperation value. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| NairFMModServIntervals | 1.3.6.1.4.1.318.1.1.13.1.5.9 | ||||||||||||||||||||
| SairFMModServIntComp1 | 1.3.6.1.4.1.318.1.1.13.1.5.9.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The interval at which to generate a maintenance alarm for compressor 1. Values stored in increments of 100 hours. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMModServIntComp2 | 1.3.6.1.4.1.318.1.1.13.1.5.9.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The interval at which to generate a maintenance alarm for compressor 2. Values stored in increments of 100 hours. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMModServIntHeater | 1.3.6.1.4.1.318.1.1.13.1.5.9.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The interval at which to generate a maintenance alarm for the reheat components. Values stored in increments of 100 hours. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMModServIntHum | 1.3.6.1.4.1.318.1.1.13.1.5.9.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The interval at which to generate a maintenance alarm for the humidifier. Values stored in increments of 100 hours. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMModServIntBlwr1 | 1.3.6.1.4.1.318.1.1.13.1.5.9.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The interval at which to generate a maintenance alarm for blower 1. Values stored in increments of 100 hours. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMModServIntBlwr2 | 1.3.6.1.4.1.318.1.1.13.1.5.9.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The interval at which to generate a maintenance alarm for blower 2. Values stored in increments of 100 hours. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMModServIntBlwrCtrl1 | 1.3.6.1.4.1.318.1.1.13.1.5.9.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The interval at which to generate a maintenance alarm for blower controller 1. Values stored in increments of 100 hours. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| SairFMModServIntBlwrCtrl2 | 1.3.6.1.4.1.318.1.1.13.1.5.9.8 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The interval at which to generate a maintenance alarm for blower controller 2. Values stored in increments of 100 hours. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | |||||||||||||||||||||
| NairFMModServIntResets | 1.3.6.1.4.1.318.1.1.13.1.5.10 | ||||||||||||||||||||
| SairFMModServIntResetTableSize | 1.3.6.1.4.1.318.1.1.13.1.5.10.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the airFMModServIntTable. | |||||||||||||||||||||
| TairFMModServIntResetTable | 1.3.6.1.4.1.318.1.1.13.1.5.10.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting information from each module in the system. | |||||||||||||||||||||
| RairFMModServIntResetEntry | 1.3.6.1.4.1.318.1.1.13.1.5.10.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The module to get information from. | |||||||||||||||||||||
| CairFMModServIntResetModuleIndex | 1.3.6.1.4.1.318.1.1.13.1.5.10.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of the module. | |||||||||||||||||||||
| CairFMModServIntComp1Reset | 1.3.6.1.4.1.318.1.1.13.1.5.10.2.1.2 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Reset the compressor 1 service interval maintenance alarm. Getting this OID will do nothing and return the noOperation value. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMModServIntComp2Reset | 1.3.6.1.4.1.318.1.1.13.1.5.10.2.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Reset the compressor 2 service interval maintenance alarm. Getting this OID will do nothing and return the noOperation value. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMModServIntHeaterReset | 1.3.6.1.4.1.318.1.1.13.1.5.10.2.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Reset the heater service interval maintenance alarm. Getting this OID will do nothing and return the noOperation value. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMModServIntHumReset | 1.3.6.1.4.1.318.1.1.13.1.5.10.2.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Reset the humidifier service interval maintenance alarm. Getting this OID will do nothing and return the noOperation value. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMModServIntBlwr1Reset | 1.3.6.1.4.1.318.1.1.13.1.5.10.2.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Reset the blower 1 service interval maintenance alarm. Getting this OID will do nothing and return the noOperation value. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMModServIntBlwr2Reset | 1.3.6.1.4.1.318.1.1.13.1.5.10.2.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Reset the blower 2 service interval maintenance alarm. Getting this OID will do nothing and return the noOperation value. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMModServIntBlwrCtrl1Reset | 1.3.6.1.4.1.318.1.1.13.1.5.10.2.1.8 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Reset the blower controller 1 service interval maintenance alarm. Getting this OID will do nothing and return the noOperation value. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| CairFMModServIntBlwrCtrl2Reset | 1.3.6.1.4.1.318.1.1.13.1.5.10.2.1.9 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Reset the blower controller 2 service interval maintenance alarm. Getting this OID will do nothing and return the noOperation value. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
| |||||||||||||||||||||
| NairFMAlarms | 1.3.6.1.4.1.318.1.1.13.1.6 | ||||||||||||||||||||
| SairFMAlarmClearActiveGroupAlarms | 1.3.6.1.4.1.318.1.1.13.1.6.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Clear active group alarms. If alarm conditions are still present, new alarms will be generated for those conditions. Getting this OID will do nothing and return the noOperation value.
| |||||||||||||||||||||
| SairFMAlarmClearActiveSysModAlarms | 1.3.6.1.4.1.318.1.1.13.1.6.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Clear active system and module alarms. If alarm conditions are still present, new alarms will be generated for those conditions. Getting this OID will do nothing and return the noOperation value.
| |||||||||||||||||||||
| SairFMAlarmConditionsTableSize | 1.3.6.1.4.1.318.1.1.13.1.6.3 | INTEGER | RO | mandatory | 1 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of active alarm conditions in the airFMAlarmConditionTable. Example values from LibreNMS test devices
| |||||||||||||||||||||
| TairFMAlarmConditionsTable | 1.3.6.1.4.1.318.1.1.13.1.6.4 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Table of active alarm conditions for the device. | |||||||||||||||||||||
| RairFMAlarmConditionsEntry | 1.3.6.1.4.1.318.1.1.13.1.6.4.1 | NA | mandatory | ||||||||||||||||||
| CairFMAlarmConditionsIndex | 1.3.6.1.4.1.318.1.1.13.1.6.4.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Alarm condition index. | |||||||||||||||||||||
| CairFMAlarmSeverity | 1.3.6.1.4.1.318.1.1.13.1.6.4.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Severity of the alarm.
| |||||||||||||||||||||
| CairFMAlarmType | 1.3.6.1.4.1.318.1.1.13.1.6.4.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Type of alarm.
| |||||||||||||||||||||
| CairFMEventCode | 1.3.6.1.4.1.318.1.1.13.1.6.4.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory APC event code for the alarm. | |||||||||||||||||||||
| CairFMAlarmDate | 1.3.6.1.4.1.318.1.1.13.1.6.4.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory Date the alarm was recorded. | |||||||||||||||||||||
| CairFMAlarmTime | 1.3.6.1.4.1.318.1.1.13.1.6.4.1.6 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory Time the alarm was recorded. | |||||||||||||||||||||
| CairFMAlarmDescription | 1.3.6.1.4.1.318.1.1.13.1.6.4.1.7 | DisplayString (SIZE (0..64)) | RO | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..64)) · read-only · mandatory Description of the alarm. | |||||||||||||||||||||
| NairPA | 1.3.6.1.4.1.318.1.1.13.2 | ||||||||||||||||||||
| NairPAIdent | 1.3.6.1.4.1.318.1.1.13.2.1 | ||||||||||||||||||||
| SairPAIdentName | 1.3.6.1.4.1.318.1.1.13.2.1.1 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the device name. | |||||||||||||||||||||
| SairPAModelNumber | 1.3.6.1.4.1.318.1.1.13.2.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the device model number. | |||||||||||||||||||||
| SairPADateOfManufacture | 1.3.6.1.4.1.318.1.1.13.2.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying when the device was produced. | |||||||||||||||||||||
| SairPASerialNumber | 1.3.6.1.4.1.318.1.1.13.2.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the device serial number. | |||||||||||||||||||||
| SairPAFirmwareRevision | 1.3.6.1.4.1.318.1.1.13.2.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the device firmware revision. | |||||||||||||||||||||
| SairPAHardwareRevision | 1.3.6.1.4.1.318.1.1.13.2.1.6 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the device hardware revision. | |||||||||||||||||||||
| NairPAStatus | 1.3.6.1.4.1.318.1.1.13.2.2 | ||||||||||||||||||||
| SairPASystemPower | 1.3.6.1.4.1.318.1.1.13.2.2.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The status of the unit's system power setting. ON(1) The system power is turned on. OFF(2) The system power is turned off.
| |||||||||||||||||||||
| SairPAOperatingMode | 1.3.6.1.4.1.318.1.1.13.2.2.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The current operating mode of the unit. OFF(1) The system is off. VENTING(2) The system's venting function is active. COOLING(3) The system's cooling function is active.
| |||||||||||||||||||||
| SairPASetpointTempF | 1.3.6.1.4.1.318.1.1.13.2.2.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The temperature setpoint in Fahrenheit to which the unit is controlling. | |||||||||||||||||||||
| SairPASetpointTempC | 1.3.6.1.4.1.318.1.1.13.2.2.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The temperature setpoint in Celsius to which the unity is controlling. | |||||||||||||||||||||
| SairPABlowerSpeed | 1.3.6.1.4.1.318.1.1.13.2.2.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit's blower speed setting. LOW(1) The blower speed is low. HIGH(2) The blower speed is high.
| |||||||||||||||||||||
| SairPACompressor | 1.3.6.1.4.1.318.1.1.13.2.2.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit's compressor status. ON(1) The compressor is turned on. OFF(2) The compressor is turned off.
| |||||||||||||||||||||
| SairPACondenserFan | 1.3.6.1.4.1.318.1.1.13.2.2.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit's condenser fan status. ON(1) The condenser fan is turned on. OFF(2) The condenser fan is turned off.
| |||||||||||||||||||||
| SairPACondensatePump | 1.3.6.1.4.1.318.1.1.13.2.2.8 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit's condensate pump status. ON(1) The condensate pump is turned on. OFF(2) The condensate pump is turned off.
| |||||||||||||||||||||
| SairPASupplyTempF | 1.3.6.1.4.1.318.1.1.13.2.2.9 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The supply temperature in degrees Fahrenheit. | |||||||||||||||||||||
| SairPASupplyTempC | 1.3.6.1.4.1.318.1.1.13.2.2.10 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The supply temperature in degrees Celsius. | |||||||||||||||||||||
| SairPAReturnTempF | 1.3.6.1.4.1.318.1.1.13.2.2.11 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The return temperature in degrees Fahrenheit. | |||||||||||||||||||||
| SairPAReturnTempC | 1.3.6.1.4.1.318.1.1.13.2.2.12 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The return temperature in degrees Celsius. | |||||||||||||||||||||
| SairPARemoteTempF | 1.3.6.1.4.1.318.1.1.13.2.2.13 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The remote temperature in degrees Fahrenheit. | |||||||||||||||||||||
| SairPARemoteTempC | 1.3.6.1.4.1.318.1.1.13.2.2.14 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The remote temperature in degrees Celsius. | |||||||||||||||||||||
| SairPARemoteHumidity | 1.3.6.1.4.1.318.1.1.13.2.2.15 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The remote humidity. | |||||||||||||||||||||
| NairIR | 1.3.6.1.4.1.318.1.1.13.3 | ||||||||||||||||||||
| NairIRAlarms | 1.3.6.1.4.1.318.1.1.13.3.1 | ||||||||||||||||||||
| SairIRAlarmConditionsTableSize | 1.3.6.1.4.1.318.1.1.13.3.1.1 | INTEGER | RO | mandatory | 0 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of active alarm conditions in the airIRAlarmConditionTable. Example values from LibreNMS test devices
| |||||||||||||||||||||
| TairIRAlarmConditionsTable | 1.3.6.1.4.1.318.1.1.13.3.1.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Table of active alarm conditions for the device. | |||||||||||||||||||||
| RairIRAlarmConditionsEntry | 1.3.6.1.4.1.318.1.1.13.3.1.2.1 | NA | mandatory | ||||||||||||||||||
| CairIRAlarmConditionsIndex | 1.3.6.1.4.1.318.1.1.13.3.1.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Alarm condition index. | |||||||||||||||||||||
| CairIREventCode | 1.3.6.1.4.1.318.1.1.13.3.1.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Code for the alarm. | |||||||||||||||||||||
| CairIRAlarmDescription | 1.3.6.1.4.1.318.1.1.13.3.1.2.1.3 | DisplayString (SIZE (0..64)) | RO | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..64)) · read-only · mandatory Description of the alarm. | |||||||||||||||||||||
| NairIRRC | 1.3.6.1.4.1.318.1.1.13.3.2 | ||||||||||||||||||||
| NairIRRCGroup | 1.3.6.1.4.1.318.1.1.13.3.2.1 | ||||||||||||||||||||
| NairIRRCGroupStatus | 1.3.6.1.4.1.318.1.1.13.3.2.1.1 | ||||||||||||||||||||
| SairIRRCGroupStatusCoolOutput | 1.3.6.1.4.1.318.1.1.13.3.2.1.1.1 | INTEGER | RO | mandatory | 0 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory Group coolant output in tenths of kW. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCGroupStatusCoolDemand | 1.3.6.1.4.1.318.1.1.13.3.2.1.1.2 | INTEGER | RO | mandatory | 0 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory Group coolant demand in tenths of kW. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCGroupStatusAirFlowUS | 1.3.6.1.4.1.318.1.1.13.3.2.1.1.3 | INTEGER | RO | mandatory | 3444 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory Group air flow in cubic feet per minute. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCGroupStatusAirFlowMetric | 1.3.6.1.4.1.318.1.1.13.3.2.1.1.4 | INTEGER | RO | mandatory | 1626 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory Group air flow in liters per second. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCGroupStatusMaxRackInletTempUS | 1.3.6.1.4.1.318.1.1.13.3.2.1.1.5 | INTEGER | RO | mandatory | 715 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory Group maximum rack inlet temperature in tenths of degrees Fahrenheit. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCGroupStatusMaxRackInletTempMetric | 1.3.6.1.4.1.318.1.1.13.3.2.1.1.6 | INTEGER | RO | mandatory | 219 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory Group maximum rack inlet temperature in tenths of degrees Celsius. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCGroupStatusMinRackInletTempUS | 1.3.6.1.4.1.318.1.1.13.3.2.1.1.7 | INTEGER | RO | mandatory | 704 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory Group minimum rack inlet temperature in tenths of degrees Fahrenheit. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCGroupStatusMinRackInletTempMetric | 1.3.6.1.4.1.318.1.1.13.3.2.1.1.8 | INTEGER | RO | mandatory | 213 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory Group minimum rack inlet temperature in tenths of degrees Celsius. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCGroupStatusActiveFlowControlStatus | 1.3.6.1.4.1.318.1.1.13.3.2.1.1.9 | INTEGER | RO | mandatory | notApplicable(4) | ||||||||||||||||
scalar · INTEGER · read-only · mandatory Status of the active flow control system.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NairIRRCGroupSetpoints | 1.3.6.1.4.1.318.1.1.13.3.2.1.2 | ||||||||||||||||||||
| SairIRRCGroupSetpointsCoolUS | 1.3.6.1.4.1.318.1.1.13.3.2.1.2.1 | INTEGER | RW | mandatory | 770 | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Group cooling setpoint in tenths of degrees Fahrenheit. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCGroupSetpointsCoolMetric | 1.3.6.1.4.1.318.1.1.13.3.2.1.2.2 | INTEGER | RW | mandatory | 250 | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Group cooling setpoint in tenths of degrees Celsius. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCGroupSetpointsSupplyAirUS | 1.3.6.1.4.1.318.1.1.13.3.2.1.2.3 | INTEGER | RW | mandatory | 716 | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Group supply air setpoint in tenths of degrees Fahrenheit. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCGroupSetpointsSupplyAirMetric | 1.3.6.1.4.1.318.1.1.13.3.2.1.2.4 | INTEGER | RW | mandatory | 220 | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Group supply air setpoint in tenths of degrees Celsius. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCGroupSetpointsFanSpeedPreference | 1.3.6.1.4.1.318.1.1.13.3.2.1.2.5 | INTEGER | RW | mandatory | med-low(2) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory The preferred fan speed setting.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCGroupSetpointsFanSpeedControl | 1.3.6.1.4.1.318.1.1.13.3.2.1.2.6 | INTEGER | RW | mandatory | automatic(1) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory The fan speed control setting. Automatic(1) - controller manages fan speed. Manual(2) - fan speed is fixed and set by the fan speed preference. See airIRRCGroupSetpointsFanSpeedPreference.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCGroupSetpointsActiveFlowControlBias | 1.3.6.1.4.1.318.1.1.13.3.2.1.2.7 | INTEGER | RW | mandatory | zero(3) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory The active flow control bias setting.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NairIRRCGroupConfig | 1.3.6.1.4.1.318.1.1.13.3.2.1.3 | ||||||||||||||||||||
| SairIRRCGroupConfigNumberofCoolingUnits | 1.3.6.1.4.1.318.1.1.13.3.2.1.3.1 | INTEGER | RW | mandatory | 2 | ||||||||||||||||
scalar · INTEGER · read-write · mandatory The number of cooling units present in the group. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCGroupConfigConfigurationType | 1.3.6.1.4.1.318.1.1.13.3.2.1.3.2 | INTEGER | RW | mandatory | hacs(2) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory The group configuration type.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCGroupConfigPctGlycol | 1.3.6.1.4.1.318.1.1.13.3.2.1.3.3 | INTEGER | RW | mandatory | 0 | ||||||||||||||||
scalar · INTEGER · read-write · mandatory The glycol mixture in percent. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCGroupConfigCoolGainP | 1.3.6.1.4.1.318.1.1.13.3.2.1.3.4 | INTEGER | RW | mandatory | 67 | ||||||||||||||||
scalar · INTEGER · read-write · mandatory The gain component of the PID in hundredths. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCGroupConfigCoolResetRateI | 1.3.6.1.4.1.318.1.1.13.3.2.1.3.5 | INTEGER | RW | mandatory | 37 | ||||||||||||||||
scalar · INTEGER · read-write · mandatory The integral component of the PID in hundredths. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCGroupConfigCoolDerivativeD | 1.3.6.1.4.1.318.1.1.13.3.2.1.3.6 | INTEGER | RW | mandatory | 26 | ||||||||||||||||
scalar · INTEGER · read-write · mandatory The derivative component of the PID in hundredths. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCGroupConfigMaxFanSpeed | 1.3.6.1.4.1.318.1.1.13.3.2.1.3.7 | INTEGER | RW | mandatory | 100 | ||||||||||||||||
scalar · INTEGER · read-write · mandatory The maximum desired fan speed setting in percent. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCGroupConfigNumberOfActiveFlowControllers | 1.3.6.1.4.1.318.1.1.13.3.2.1.3.8 | INTEGER | RW | mandatory | 0 | ||||||||||||||||
scalar · INTEGER · read-write · mandatory The number of active flow controllers present in the group. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCGroupConfigActiveFlowControllerLampTest | 1.3.6.1.4.1.318.1.1.13.3.2.1.3.9 | INTEGER | RW | mandatory | off(1) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Turns off/on the active flow controller lamp test.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCGroupConfigAltitudeUS | 1.3.6.1.4.1.318.1.1.13.3.2.1.3.10 | INTEGER | RW | mandatory | 1394 | ||||||||||||||||
scalar · INTEGER · read-write · mandatory The group altitude of the units above sea level in feet. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCGroupConfigAltitudeMetric | 1.3.6.1.4.1.318.1.1.13.3.2.1.3.11 | INTEGER | RW | mandatory | 425 | ||||||||||||||||
scalar · INTEGER · read-write · mandatory The group altitude of the units above sea level in meters. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NairIRRCUnit | 1.3.6.1.4.1.318.1.1.13.3.2.2 | ||||||||||||||||||||
| NairIRRCUnitIdent | 1.3.6.1.4.1.318.1.1.13.3.2.2.1 | ||||||||||||||||||||
| SairIRRCUnitIdentID | 1.3.6.1.4.1.318.1.1.13.3.2.2.1.1 | INTEGER | RW | mandatory | 1 | ||||||||||||||||
scalar · INTEGER · read-write · mandatory The unit identification number. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitIdentName | 1.3.6.1.4.1.318.1.1.13.3.2.2.1.2 | DisplayString | RW | mandatory | inrow-test-1 | ||||||||||||||||
scalar · DisplayString · read-write · mandatory A character string identifying the unit name. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitIdentLocation | 1.3.6.1.4.1.318.1.1.13.3.2.2.1.3 | DisplayString | RW | mandatory | Test Location | ||||||||||||||||
scalar · DisplayString · read-write · mandatory A character string identifying the unit location. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitIdentModelNumber | 1.3.6.1.4.1.318.1.1.13.3.2.2.1.4 | DisplayString | RO | mandatory | ACRC103 | ||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the unit model number. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitIdentSerialNumber | 1.3.6.1.4.1.318.1.1.13.3.2.2.1.5 | DisplayString | RO | mandatory | JK1323004050 | ||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the unit serial number. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitIdentFirmwareRevision | 1.3.6.1.4.1.318.1.1.13.3.2.2.1.6 | DisplayString | RO | mandatory | 7.5.0 | ||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the unit firmware version. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitIdentHardwareRevision | 1.3.6.1.4.1.318.1.1.13.3.2.2.1.7 | DisplayString | RO | mandatory | C8 | ||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the unit controller hardware revision. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitIdentManufactureDate | 1.3.6.1.4.1.318.1.1.13.3.2.2.1.8 | DisplayString | RO | mandatory | 06/08/2013 | ||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the unit manufacture date. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NairIRRCUnitStatus | 1.3.6.1.4.1.318.1.1.13.3.2.2.2 | ||||||||||||||||||||
| SairIRRCUnitStatusOperateMode | 1.3.6.1.4.1.318.1.1.13.3.2.2.2.1 | INTEGER | RO | mandatory | on(2) | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The cooling unit operating mode.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitStatusCoolOutput | 1.3.6.1.4.1.318.1.1.13.3.2.2.2.2 | INTEGER | RO | mandatory | 0 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit cooling output in tenths of kW. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitStatusCoolDemand | 1.3.6.1.4.1.318.1.1.13.3.2.2.2.3 | INTEGER | RO | mandatory | 0 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit cooling demand in tenths of kW. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitStatusAirFlowUS | 1.3.6.1.4.1.318.1.1.13.3.2.2.2.4 | INTEGER | RO | mandatory | 1717 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit air flow in cubic feet per minute. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitStatusAirFlowMetric | 1.3.6.1.4.1.318.1.1.13.3.2.2.2.5 | INTEGER | RO | mandatory | 810 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit air flow in hundredths of liters per second. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitStatusRackInletTempUS | 1.3.6.1.4.1.318.1.1.13.3.2.2.2.6 | INTEGER | RO | mandatory | 706 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit rack inlet temperature in tenths of degrees Fahrenheit. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitStatusRackInletTempMetric | 1.3.6.1.4.1.318.1.1.13.3.2.2.2.7 | INTEGER | RO | mandatory | 214 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit rack inlet temperature in tenths of degrees Celsius. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitStatusSupplyAirTempUS | 1.3.6.1.4.1.318.1.1.13.3.2.2.2.8 | INTEGER | RO | mandatory | 715 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit supply air temperature in tenths of degrees Fahrenheit. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitStatusSupplyAirTempMetric | 1.3.6.1.4.1.318.1.1.13.3.2.2.2.9 | INTEGER | RO | mandatory | 219 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit supply air temperature in tenths of degrees Celsius. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitStatusReturnAirTempUS | 1.3.6.1.4.1.318.1.1.13.3.2.2.2.10 | INTEGER | RO | mandatory | 749 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit return air temperature in tenths of degrees Fahrenheit. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitStatusReturnAirTempMetric | 1.3.6.1.4.1.318.1.1.13.3.2.2.2.11 | INTEGER | RO | mandatory | 238 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit return air temperature in tenths of degrees Celsius. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitStatusContainmtDPUS | 1.3.6.1.4.1.318.1.1.13.3.2.2.2.12 | INTEGER | RO | mandatory | -1 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit containment differential pressure in hundredths of inches of water. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitStatusContainmtDPMetric | 1.3.6.1.4.1.318.1.1.13.3.2.2.2.13 | INTEGER | RO | mandatory | -1 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit containment differential pressure in Pa. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitStatusFilterDPUS | 1.3.6.1.4.1.318.1.1.13.3.2.2.2.14 | INTEGER | RO | mandatory | 0 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit air filter differential pressure in hundredths of inches of water. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitStatusFilterDPMetric | 1.3.6.1.4.1.318.1.1.13.3.2.2.2.15 | INTEGER | RO | mandatory | 0 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit air filter differential pressure in Pa. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitStatusFanSpeed | 1.3.6.1.4.1.318.1.1.13.3.2.2.2.16 | INTEGER | RO | mandatory | 518 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit average fan speed in tenths of percent. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitStatusInputState | 1.3.6.1.4.1.318.1.1.13.3.2.2.2.17 | INTEGER | RO | mandatory | open(1) | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The state of the input contact.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitStatusOutputState | 1.3.6.1.4.1.318.1.1.13.3.2.2.2.18 | INTEGER | RO | mandatory | open(1) | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The state of the output relay.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitStatusActivePowerSource | 1.3.6.1.4.1.318.1.1.13.3.2.2.2.19 | INTEGER | RO | mandatory | sourceB(2) | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The power source that is powering the unit.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitStatusFluidValvePosition | 1.3.6.1.4.1.318.1.1.13.3.2.2.2.20 | INTEGER | RO | mandatory | 30 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The fluid valve position in percent open. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitStatusFluidFlowUS | 1.3.6.1.4.1.318.1.1.13.3.2.2.2.21 | INTEGER | RO | mandatory | 0 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The fluid flow in tenths of gallons per minute. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitStatusFluidFlowMetric | 1.3.6.1.4.1.318.1.1.13.3.2.2.2.22 | INTEGER | RO | mandatory | 0 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The fluid flow in hundredths of liters per second. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitStatusEnteringFluidTemperatureUS | 1.3.6.1.4.1.318.1.1.13.3.2.2.2.23 | INTEGER | RO | mandatory | 554 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The temperature of the entering fluid in tenths of degrees Fahrenheit. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitStatusEnteringFluidTemperatureMetric | 1.3.6.1.4.1.318.1.1.13.3.2.2.2.24 | INTEGER | RO | mandatory | 130 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The temperature of the entering fluid in tenths of degrees Celsius. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitStatusLeavingFluidTemperatureUS | 1.3.6.1.4.1.318.1.1.13.3.2.2.2.25 | INTEGER | RO | mandatory | 705 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The temperature of the Leaving fluid in tenths of degrees Fahrenheit. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitStatusLeavingFluidTemperatureMetric | 1.3.6.1.4.1.318.1.1.13.3.2.2.2.26 | INTEGER | RO | mandatory | 214 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The temperature of the Leaving fluid in tenths of degrees Celsius. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitStatusLeakSensor | 1.3.6.1.4.1.318.1.1.13.3.2.2.2.27 | INTEGER | RO | mandatory | no-leak(1) | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The state (no-leak/leak) of the leak sensor.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NairIRRCUnitRunHours | 1.3.6.1.4.1.318.1.1.13.3.2.2.3 | ||||||||||||||||||||
| SairIRRCUnitRunHoursAirFilter | 1.3.6.1.4.1.318.1.1.13.3.2.2.3.1 | INTEGER | RO | mandatory | 3150 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit air filter run hours. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitRunHoursFan1 | 1.3.6.1.4.1.318.1.1.13.3.2.2.3.2 | INTEGER | RO | mandatory | 111758 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit fan 1 run hours. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitRunHoursFan2 | 1.3.6.1.4.1.318.1.1.13.3.2.2.3.3 | INTEGER | RO | mandatory | 111758 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit fan 2 run hours. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitRunHoursFan3 | 1.3.6.1.4.1.318.1.1.13.3.2.2.3.4 | INTEGER | RO | mandatory | 111758 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit fan 3 run hours. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitRunHoursFan4 | 1.3.6.1.4.1.318.1.1.13.3.2.2.3.5 | INTEGER | RO | mandatory | 111758 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit fan 4 run hours. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitRunHoursFan5 | 1.3.6.1.4.1.318.1.1.13.3.2.2.3.6 | INTEGER | RO | mandatory | 111758 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit fan 5 run hours. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitRunHoursFan6 | 1.3.6.1.4.1.318.1.1.13.3.2.2.3.7 | INTEGER | RO | mandatory | 111758 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit fan 6 run hours. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitRunHoursFan7 | 1.3.6.1.4.1.318.1.1.13.3.2.2.3.8 | INTEGER | RO | mandatory | 111758 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit fan 7 run hours. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitRunHoursFan8 | 1.3.6.1.4.1.318.1.1.13.3.2.2.3.9 | INTEGER | RO | mandatory | 111758 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit fan 8 run hours. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitRunHoursFanPowerSupplyLeft | 1.3.6.1.4.1.318.1.1.13.3.2.2.3.10 | INTEGER | RO | mandatory | 111760 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit fan left power supply run hours. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitRunHoursFanPowerSupplyRight | 1.3.6.1.4.1.318.1.1.13.3.2.2.3.11 | INTEGER | RO | mandatory | 111764 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit fan right power supply run hours. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitRunHoursCondensatePump | 1.3.6.1.4.1.318.1.1.13.3.2.2.3.12 | INTEGER | RO | mandatory | 0 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit condensate pump run hours. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitRunHoursFanPowerSupplyFeedALeft | 1.3.6.1.4.1.318.1.1.13.3.2.2.3.13 | INTEGER | RO | mandatory | 0 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit fan, DC power feed A, left power supply run hours. This is only valid for a DC input unit. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitRunHoursFanPowerSupplyFeedARight | 1.3.6.1.4.1.318.1.1.13.3.2.2.3.14 | INTEGER | RO | mandatory | 0 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit fan, DC power feed A, right power supply run hours. This is only valid for a DC input unit. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitRunHoursFanPowerSupplyFeedBLeft | 1.3.6.1.4.1.318.1.1.13.3.2.2.3.15 | INTEGER | RO | mandatory | 0 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit fan, DC power feed B, left power supply run hours. This is only valid for a DC input unit. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitRunHoursFanPowerSupplyFeedBRight | 1.3.6.1.4.1.318.1.1.13.3.2.2.3.16 | INTEGER | RO | mandatory | 0 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit fan, DC power feed B, right power supply run hours. This is only valid for a DC input unit. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NairIRRCUnitServiceIntervals | 1.3.6.1.4.1.318.1.1.13.3.2.2.4 | ||||||||||||||||||||
| SairIRRCUnitServiceIntervalsAirFilter | 1.3.6.1.4.1.318.1.1.13.3.2.2.4.1 | INTEGER | RW | mandatory | 52 | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Air filter service interval in weeks. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitServiceIntervalsAirFilterAlarm | 1.3.6.1.4.1.318.1.1.13.3.2.2.4.2 | INTEGER | RW | mandatory | enable(1) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory The air filter service interval alarm enable/disable.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NairIRRCUnitThresholds | 1.3.6.1.4.1.318.1.1.13.3.2.2.5 | ||||||||||||||||||||
| SairIRRCUnitThresholdsRackInletHighTempUS | 1.3.6.1.4.1.318.1.1.13.3.2.2.5.1 | INTEGER | RW | mandatory | 860 | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Unit rack inlet air high temperature threshold in tenths of degrees Fahrenheit. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitThresholdsRackInletHighTempMetric | 1.3.6.1.4.1.318.1.1.13.3.2.2.5.2 | INTEGER | RW | mandatory | 300 | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Unit rack inlet air high temperature threshold in tenths of degrees Celsius. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitThresholdsSupplyAirHighTempUS | 1.3.6.1.4.1.318.1.1.13.3.2.2.5.3 | INTEGER | RW | mandatory | 860 | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Unit supply air high temperature threshold in tenths of degrees Fahrenheit. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitThresholdsSupplyAirHighTempMetric | 1.3.6.1.4.1.318.1.1.13.3.2.2.5.4 | INTEGER | RW | mandatory | 300 | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Unit supply air high temperature threshold in tenths of degrees Celsius. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitThresholdsReturnAirHighTempUS | 1.3.6.1.4.1.318.1.1.13.3.2.2.5.5 | INTEGER | RW | mandatory | 1040 | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Unit return air high temperature threshold in tenths of degrees Fahrenheit. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitThresholdsReturnAirHighTempMetric | 1.3.6.1.4.1.318.1.1.13.3.2.2.5.6 | INTEGER | RW | mandatory | 400 | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Unit return air high temperature threshold in tenths of degrees Celsius. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitThresholdsEnteringFluidHighTempUS | 1.3.6.1.4.1.318.1.1.13.3.2.2.5.7 | INTEGER | RW | mandatory | 770 | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Unit entering fluid high temperature threshold in tenths of degrees Fahrenheit. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitThresholdsEnteringFluidHighTempMetric | 1.3.6.1.4.1.318.1.1.13.3.2.2.5.8 | INTEGER | RW | mandatory | 250 | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Unit incoming fluid high temperature threshold in tenths of degrees Celsius. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NairIRRCUnitConfig | 1.3.6.1.4.1.318.1.1.13.3.2.2.6 | ||||||||||||||||||||
| SairIRRCUnitConfigCoolCapacity | 1.3.6.1.4.1.318.1.1.13.3.2.2.6.1 | INTEGER | RW | mandatory | automatic(1) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory The cooling capacity options setting.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitConfigStartupDelay | 1.3.6.1.4.1.318.1.1.13.3.2.2.6.2 | INTEGER | RW | mandatory | 0 | ||||||||||||||||
scalar · INTEGER · read-write · mandatory The startup delay in seconds. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitConfigIdleOnLeakDetect | 1.3.6.1.4.1.318.1.1.13.3.2.2.6.3 | INTEGER | RW | mandatory | no(2) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory The idle on leak options setting.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitConfigPowerSource | 1.3.6.1.4.1.318.1.1.13.3.2.2.6.4 | INTEGER | RW | mandatory | sourceAandB(3) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory The configured power source of the unit.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitConfigInputNormalState | 1.3.6.1.4.1.318.1.1.13.3.2.2.6.5 | INTEGER | RW | mandatory | open(1) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory The normal state of the input contact.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitConfigOutputNormalState | 1.3.6.1.4.1.318.1.1.13.3.2.2.6.6 | INTEGER | RW | mandatory | open(1) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory The normal state of the output relay.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitConfigOutputSource | 1.3.6.1.4.1.318.1.1.13.3.2.2.6.7 | INTEGER | RW | mandatory | anyAlarm(1) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory The source of output relay change.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SairIRRCUnitConfigIdleOnCoolFail | 1.3.6.1.4.1.318.1.1.13.3.2.2.6.8 | INTEGER | RW | mandatory | yes(1) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory The idle on cool fail options setting. If yes, the system will go into idle mode when a cooling failure is detected. If no, the system will not go into idle mode when a cooling failure is detected.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NairIRRP | 1.3.6.1.4.1.318.1.1.13.3.3 | ||||||||||||||||||||
| NairIRRP100 | 1.3.6.1.4.1.318.1.1.13.3.3.1 | ||||||||||||||||||||
| NairIRRP100Group | 1.3.6.1.4.1.318.1.1.13.3.3.1.1 | ||||||||||||||||||||
| NairIRRP100GroupStatus | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.1 | ||||||||||||||||||||
| SairIRRP100GroupStatusAirFlowUS | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Group air flow in cubic feet per minute. | |||||||||||||||||||||
| SairIRRP100GroupStatusAirFlowMetric | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Group air flow in liters per second. | |||||||||||||||||||||
| SairIRRP100GroupStatusMaxRackInletTempUS | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Group maximum rack inlet temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRRP100GroupStatusMaxRackInletTempMetric | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Group maximum rack inlet temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRRP100GroupStatusMinRackInletTempUS | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Group minimum rack inlet temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRRP100GroupStatusMinRackInletTempMetric | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Group minimum rack inlet temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRRP100GroupStatusCoolDemand | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Group coolant demand in tenths of kiloWatts. | |||||||||||||||||||||
| SairIRRP100GroupStatusCoolOutput | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Group coolant output in tenths of kiloWatts. | |||||||||||||||||||||
| SairIRRP100GroupStatusHumidifyDemand | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.1.9 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The amount of humidification the group is demanding from the humidifiers in percent. | |||||||||||||||||||||
| SairIRRP100GroupStatusHumidifyOutput | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.1.10 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The actual amount of humidification the group is supplying in percent. | |||||||||||||||||||||
| SairIRRP100GroupStatusDehumidifyDemand | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.1.11 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The amount of dehumidification the group is demanding from the electric heaters in percent. | |||||||||||||||||||||
| SairIRRP100GroupStatusDehumidifyOutput | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.1.12 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The actual amount of dehumidification the group is supplying in percent. | |||||||||||||||||||||
| SairIRRP100GroupStatusReheatDemand | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.1.13 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The amount of heating the group is demanding from the electric heaters in percent. | |||||||||||||||||||||
| SairIRRP100GroupStatusReheatOutput | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.1.14 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The actual amount of heating the group is supplying in percent. | |||||||||||||||||||||
| SairIRRP100GroupStatusActiveFlowControlStatus | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.1.15 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Status of the active flow control system.
| |||||||||||||||||||||
| SairIRRP100GroupStatusDewPointTempUS | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.1.16 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Group average dew point temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRRP100GroupStatusDewPointTempMetric | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.1.17 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Group average dew point temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| NairIRRP100GroupSetpoints | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.2 | ||||||||||||||||||||
| SairIRRP100GroupSetpointsCoolUS | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.2.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Group cooling setpoint in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRRP100GroupSetpointsCoolMetric | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.2.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Group cooling setpoint in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRRP100GroupSetpointsSupplyAirUS | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.2.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Group supply air setpoint in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRRP100GroupSetpointsSupplyAirMetric | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.2.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Group supply air setpoint in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRRP100GroupSetpointsHumidify | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.2.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Group humidify setpoint in tenths of percent relative humidity. | |||||||||||||||||||||
| SairIRRP100GroupSetpointsDehumidify | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.2.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Group dehumidify setpoint in tenths of percent relative humidity. | |||||||||||||||||||||
| SairIRRP100GroupSetpointsDehumidifyDeadband | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.2.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Group dehumidify deadband in percent relative humidity. | |||||||||||||||||||||
| SairIRRP100GroupSetpointsReheatUS | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.2.8 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Group supply air setpoint in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRRP100GroupSetpointsReheatMetric | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.2.9 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Group supply air setpoint in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRRP100GroupSetpointsFanSpeedPreference | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.2.10 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The preferred fan speed setting.
| |||||||||||||||||||||
| SairIRRP100GroupSetpointsFanSpeedControl | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.2.11 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The fan speed control setting.
| |||||||||||||||||||||
| SairIRRP100GroupSetpointsActiveFlowControlBias | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.2.12 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The active flow control bias setting.
| |||||||||||||||||||||
| NairIRRP100GroupConfig | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.3 | ||||||||||||||||||||
| SairIRRP100GroupConfigNumberofCoolingUnits | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.3.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The number of cooling units present in the group. | |||||||||||||||||||||
| SairIRRP100GroupConfigConfigurationType | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.3.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The group configuration type.
| |||||||||||||||||||||
| SairIRRP100GroupConfigCoolGainP | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.3.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The gain component of the cool PID in hundredths. | |||||||||||||||||||||
| SairIRRP100GroupConfigCoolResetRateI | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.3.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The integral component of the cool PID in hundredths. | |||||||||||||||||||||
| SairIRRP100GroupConfigCoolDerivativeD | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.3.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The derivative component of the cool PID in hundredths. | |||||||||||||||||||||
| SairIRRP100GroupConfigHumidifySensitivityBand | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.3.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The percent relative humidity below the setpoint that will cause the humidifier to run at 100% capacity. | |||||||||||||||||||||
| SairIRRP100GroupConfigReheatGainP | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.3.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The gain component of the reheat PID in hundredths. | |||||||||||||||||||||
| SairIRRP100GroupConfigReheatResetRateI | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.3.8 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The integral component of the reheat PID in hundredths. | |||||||||||||||||||||
| SairIRRP100GroupConfigReheatDerivativeD | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.3.9 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The derivative component of the reheat PID in hundredths. | |||||||||||||||||||||
| SairIRRP100GroupConfigNumberofBackupUnits | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.3.10 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The number of backup units. | |||||||||||||||||||||
| SairIRRP100GroupConfigRuntimeBalancingEnable | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.3.11 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Enable or disable runtime balancing feature.
| |||||||||||||||||||||
| SairIRRP100GroupConfigLoadAssistEnable | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.3.12 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Enable or disable load assist feature.
| |||||||||||||||||||||
| SairIRRP100GroupConfigFullRPBackups | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.3.13 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The number of full featured RPs that can be used as backup units. | |||||||||||||||||||||
| SairIRRP100GroupConfigMaxFanSpeed | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.3.14 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The maximum desired fan speed setting in percent. | |||||||||||||||||||||
| SairIRRP100GroupConfigNumberOfActiveFlowControllers | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.3.15 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The number of active flow controllers present in the group. | |||||||||||||||||||||
| SairIRRP100GroupConfigActiveFlowControllerLampTest | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.3.16 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Turns off/on the active flow controller lamp test.
| |||||||||||||||||||||
| SairIRRP100GroupConfigAltitudeUS | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.3.17 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The group altitude of the units above sea level in feet. | |||||||||||||||||||||
| SairIRRP100GroupConfigAltitudeMetric | 1.3.6.1.4.1.318.1.1.13.3.3.1.1.3.18 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The group altitude of the units above sea level in meters. | |||||||||||||||||||||
| NairIRRP100Unit | 1.3.6.1.4.1.318.1.1.13.3.3.1.2 | ||||||||||||||||||||
| NairIRRP100UnitIdent | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.1 | ||||||||||||||||||||
| SairIRRP100UnitIdentID | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.1.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The unit identification number. | |||||||||||||||||||||
| SairIRRP100UnitIdentName | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.1.2 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory A character string identifying the unit name. | |||||||||||||||||||||
| SairIRRP100UnitIdentLocation | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.1.3 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory A character string identifying the unit location. | |||||||||||||||||||||
| SairIRRP100UnitIdentModelNumber | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the unit model number. | |||||||||||||||||||||
| SairIRRP100UnitIdentSerialNumber | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the unit serial number. | |||||||||||||||||||||
| SairIRRP100UnitIdentFirmwareRevision | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.1.6 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the unit firmware version. | |||||||||||||||||||||
| SairIRRP100UnitIdentHardwareRevision | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.1.7 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the unit controller hardware revision. | |||||||||||||||||||||
| SairIRRP100UnitIdentManufactureDate | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.1.8 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the unit manufacture date. | |||||||||||||||||||||
| NairIRRP100UnitStatus | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2 | ||||||||||||||||||||
| SairIRRP100UnitStatusOperateMode | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The cooling unit operating mode.
| |||||||||||||||||||||
| SairIRRP100UnitStatusRackInletTempUS | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit rack inlet temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRRP100UnitStatusRackInletTempMetric | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit rack inlet temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRRP100UnitStatusSupplyAirTempUS | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit supply air temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRRP100UnitStatusSupplyAirTempMetric | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit supply air temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRRP100UnitStatusReturnAirTempUS | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit return air temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRRP100UnitStatusReturnAirTempMetric | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit return air temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRRP100UnitStatusSupplyHumidity | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.8 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The relative humidity of the supply air in tenths of percent. | |||||||||||||||||||||
| SairIRRP100UnitStatusReturnHumidity | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.9 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The relative humidity of the return air in tenths of percent. | |||||||||||||||||||||
| SairIRRP100UnitStatusAirFlowUS | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.10 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit air flow in cubic feet per minute. | |||||||||||||||||||||
| SairIRRP100UnitStatusAirFlowMetric | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.11 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit air flow in hundredths of liters per second. | |||||||||||||||||||||
| SairIRRP100UnitStatusFanSpeed | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.12 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit average fan speed in tenths of percent. | |||||||||||||||||||||
| SairIRRP100UnitStatusCoolDemand | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.13 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit cooling demand in tenths of kiloWatts. | |||||||||||||||||||||
| SairIRRP100UnitStatusCoolOutput | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.14 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit cooling output in tenths of kiloWatts. | |||||||||||||||||||||
| SairIRRP100UnitStatusHumidifyDemand | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.15 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The amount of humidification the unit is demanding from the humidifier in percent. | |||||||||||||||||||||
| SairIRRP100UnitStatusHumidifyOutput | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.16 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The actual humidification output of the unit in percent. | |||||||||||||||||||||
| SairIRRP100UnitStatusDehumidifyDemand | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.17 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The amount of dehumidification the unit is demanding in percent. | |||||||||||||||||||||
| SairIRRP100UnitStatusDehumidifyOutput | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.18 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The actual dehumidification output of the unit in percent. | |||||||||||||||||||||
| SairIRRP100UnitStatusReheatDemand | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.19 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The amount of heating the unit is demanding from the electric heater in percent. | |||||||||||||||||||||
| SairIRRP100UnitStatusReheatOutput | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.20 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The actual heating output of the unit in percent. | |||||||||||||||||||||
| SairIRRP100UnitStatusInputState | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.21 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The state of the input contact.
| |||||||||||||||||||||
| SairIRRP100UnitStatusOutputState | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.22 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The state of the output relay.
| |||||||||||||||||||||
| SairIRRP100UnitStatusRackInletTemperature1US | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.23 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit rack inlet temperature sensor in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRRP100UnitStatusRackInletTemperature1Metric | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.24 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit rack inlet temperature sensor in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRRP100UnitStatusRackInletTemperature2US | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.25 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit rack inlet temperature sensor in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRRP100UnitStatusRackInletTemperature2Metric | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.26 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit rack inlet temperature sensor in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRRP100UnitStatusRackInletTemperature3US | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.27 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit rack inlet temperature sensor in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRRP100UnitStatusRackInletTemperature3Metric | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.28 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit rack inlet temperature sensor in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRRP100UnitStatusFilterDPUS | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.29 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit air filter differential pressure in hundredths of inches of water. | |||||||||||||||||||||
| SairIRRP100UnitStatusFilterDPMetric | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.30 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit air filter differential pressure in Pa. | |||||||||||||||||||||
| SairIRRP100UnitStatusContainmtDPUS | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.31 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit containment differential pressure in hundredths of inches of water. | |||||||||||||||||||||
| SairIRRP100UnitStatusContainmtDPMetric | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.32 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit containment differential pressure in Pa. | |||||||||||||||||||||
| SairIRRP100UnitStatusHumidifierCurrent | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.33 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The humidifier current of the unit in tenths of amperes. | |||||||||||||||||||||
| SairIRRP100UnitStatusHumidifierWaterConductivity | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.34 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The water conductivity in the humidifier of the unit in microSiemens/cm. | |||||||||||||||||||||
| SairIRRP100UnitStatusCompressorDriveSpeed | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.35 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The compressor drive speed in hundredths of Hertz. | |||||||||||||||||||||
| SairIRRP100UnitStatusCompressorDrivePower | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.36 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The compressor drive power consumption in tenths of kiloWatts. | |||||||||||||||||||||
| SairIRRP100UnitStatusCompressorDriveVoltage | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.37 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The compressor drive voltage consumption in tenths of volts. | |||||||||||||||||||||
| SairIRRP100UnitStatusCompressorDriveCurrent | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.38 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The compressor drive voltage consumption in tenths of amperes. | |||||||||||||||||||||
| SairIRRP100UnitStatusCompressorDriveDCLinkVoltage | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.39 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The compressor drive DC link voltage in tenths of volts. | |||||||||||||||||||||
| SairIRRP100UnitStatusCompressorDriveHeatSinkTempUS | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.40 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The temperature of the compressor drive heatsink in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRRP100UnitStatusCompressorDriveHeatSinkTempMetric | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.41 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The temperature of the compressor drive heatsink in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRRP100UnitStatusCompressorDriveControlCardTempUS | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.42 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The temperature of the compressor drive control card in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRRP100UnitStatusCompressorDriveControlCardTempMetric | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.43 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The temperature of the compressor drive control card in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRRP100UnitStatusCompressorDriveWarningStatus | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.44 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The four byte warning status of the compressor drive in hexadecimal. | |||||||||||||||||||||
| SairIRRP100UnitStatusCompressorDriveAlarmStatus | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.45 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The four byte alarm status of the compressor drive in hexadecimal. | |||||||||||||||||||||
| SairIRRP100UnitStatusSuctionPressureUS | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.46 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit suction pressure in pounds per square inch (PSI). | |||||||||||||||||||||
| SairIRRP100UnitStatusSuctionPressureMetric | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.47 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit suction pressure in kiloPascals (kPa). | |||||||||||||||||||||
| SairIRRP100UnitStatusDischargePressureUS | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.48 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit discharge pressure in pounds per square inch (PSI). | |||||||||||||||||||||
| SairIRRP100UnitStatusDischargePressureMetric | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.49 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit discharge pressure in kiloPascals (kPa). | |||||||||||||||||||||
| SairIRRP100UnitStatusLeakSensor | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.50 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The state (no-leak/leak) of the leak sensor.
| |||||||||||||||||||||
| NairIRRP100UnitRunHours | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.3 | ||||||||||||||||||||
| SairIRRP100UnitRunHoursAirFilter | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.3.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit air filter run hours. | |||||||||||||||||||||
| SairIRRP100UnitRunHoursCondensatePump | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.3.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit condensate pump run hours. | |||||||||||||||||||||
| SairIRRP100UnitRunHoursHumidifier | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.3.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit fan right power supply run hours. | |||||||||||||||||||||
| SairIRRP100UnitRunHoursFan1 | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.3.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit fan 1 run hours. | |||||||||||||||||||||
| SairIRRP100UnitRunHoursHeater1 | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.3.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit heater 1 run hours. | |||||||||||||||||||||
| SairIRRP100UnitRunHoursFan2 | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.3.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit fan 2 run hours. | |||||||||||||||||||||
| SairIRRP100UnitRunHoursHeater2 | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.3.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit Heater 2 run hours. | |||||||||||||||||||||
| SairIRRP100UnitRunHoursCompressor | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.3.8 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit compressor run hours. | |||||||||||||||||||||
| SairIRRP100UnitRunHoursSystem | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.3.9 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Total system run hours. | |||||||||||||||||||||
| NairIRRP100UnitServiceIntervals | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.4 | ||||||||||||||||||||
| SairIRRP100UnitServiceIntervalAirFilter | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.4.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Air filter service interval in weeks. | |||||||||||||||||||||
| SairIRRP100UnitServiceIntervalAirFilterAlarm | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.4.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The air filter service interval alarm enable/disable.
| |||||||||||||||||||||
| SairIRRP100UnitServiceIntervalHumidifier | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.4.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Humidifier service interval in weeks. | |||||||||||||||||||||
| SairIRRP100UnitServiceIntervalHumidifierAlarm | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.4.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The humidifier service interval alarm enable/disable.
| |||||||||||||||||||||
| SairIRRP100UnitServiceIntervalHeater | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.4.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Heater service interval in weeks. | |||||||||||||||||||||
| SairIRRP100UnitServiceIntervalHeaterAlarm | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.4.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The heater service interval alarm enable/disable.
| |||||||||||||||||||||
| SairIRRP100UnitServiceIntervalCompressor | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.4.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Compressor service interval in weeks. | |||||||||||||||||||||
| SairIRRP100UnitServiceIntervalCompressorAlarm | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.4.8 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The compressor service interval alarm enable/disable.
| |||||||||||||||||||||
| SairIRRP100UnitServiceIntervalCondensatePump | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.4.9 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Condensate pump service interval in weeks. | |||||||||||||||||||||
| SairIRRP100UnitServiceIntervalCondensatePumpAlarm | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.4.10 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The condensate pump service interval alarm enable/disable.
| |||||||||||||||||||||
| SairIRRP100UnitServiceIntervalFans | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.4.11 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Fans service interval in weeks. | |||||||||||||||||||||
| SairIRRP100UnitServiceIntervalFansAlarm | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.4.12 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The fans service interval alarm enable/disable.
| |||||||||||||||||||||
| NairIRRP100UnitThresholds | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.5 | ||||||||||||||||||||
| SairIRRP100UnitThresholdsRackInletHighTempUS | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.5.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Unit rack inlet air high temperature threshold in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRRP100UnitThresholdsRackInletHighTempMetric | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.5.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Unit rack inlet air high temperature threshold in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRRP100UnitThresholdsSupplyAirHighTempUS | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.5.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Unit supply air high temperature threshold in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRRP100UnitThresholdsSupplyAirHighTempMetric | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.5.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Unit supply air high temperature threshold in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRRP100UnitThresholdsReturnAirHighTempUS | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.5.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Unit return air high temperature threshold in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRRP100UnitThresholdsReturnAirHighTempMetric | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.5.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Unit return air high temperature threshold in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRRP100UnitThresholdsSupplyHumidityHigh | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.5.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Unit supply humidity high threshold in tenths of percent relative humidity. | |||||||||||||||||||||
| SairIRRP100UnitThresholdsSupplyHumidityLow | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.5.8 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Unit supply humidity low threshold in tenths of percent relative humidity. | |||||||||||||||||||||
| NairIRRP100UnitConfig | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.6 | ||||||||||||||||||||
| SairIRRP100UnitConfigStartupDelay | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.6.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The startup delay in seconds. | |||||||||||||||||||||
| SairIRRP100UnitConfigCoolCapacity | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.6.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The cooling capacity options setting.
| |||||||||||||||||||||
| SairIRRP100UnitConfigIdleOnLeakDetect | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.6.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The idle on leak options setting.
| |||||||||||||||||||||
| SairIRRP100UnitConfigInputNormalState | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.6.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The normal state of the input contact.
| |||||||||||||||||||||
| SairIRRP100UnitConfigOutputNormalState | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.6.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The normal state of the output relay.
| |||||||||||||||||||||
| SairIRRP100UnitConfigOutputSource | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.6.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The source of output relay change.
| |||||||||||||||||||||
| SairIRRP100UnitConfigHumidifyEnable | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.6.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Enable/disable humidification.
| |||||||||||||||||||||
| SairIRRP100UnitConfigHumidifierControl | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.6.8 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The humidifier drain control.
| |||||||||||||||||||||
| SairIRRP100UnitConfigDehumidifyEnable | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.6.9 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Enable/disable dehumidification.
| |||||||||||||||||||||
| SairIRRP100UnitConfigReheatEnable | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.6.10 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Enable/disable reheat.
| |||||||||||||||||||||
| SairIRRP100UnitConfigHeatAssistEnable | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.6.11 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Enable/disable heat assist.
| |||||||||||||||||||||
| SairIRRP100UnitConfigPowerSourceConfig | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.6.12 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Configure the input power source: (1) single feed or (2) dual feed.
| |||||||||||||||||||||
| SairIRRP100UnitConfigUnitRoleOverride | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.6.13 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory When this OID value is (1) automatic, the system determines which units are used as primary units and which units are used as backups. When this OID value is (2) forcedOn, the connected unit is set as a primary unit.
| |||||||||||||||||||||
| SairIRRP100UnitConfigSecondaryPowerFeedCapability | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.6.14 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Available on chilled water units. When the power source config setting is set to dual, setting this value to reduced (2) will inhibit the heater and humdifier when the unit is being powered from the secondary input.
| |||||||||||||||||||||
| SairIRRP100UnitConfigIdleOnCoolFail | 1.3.6.1.4.1.318.1.1.13.3.3.1.2.6.15 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory When this OID value is (1) enable, the unit idles if it detects that it is blowing warm air into the cold aisle. The unit will attempt to restart at 5 minute intervals.
| |||||||||||||||||||||
| NairIRRP500 | 1.3.6.1.4.1.318.1.1.13.3.3.2 | ||||||||||||||||||||
| NairIRRP500Group | 1.3.6.1.4.1.318.1.1.13.3.3.2.1 | ||||||||||||||||||||
| NairIRRP500GroupStatus | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.1 | ||||||||||||||||||||
| SairIRRP500GroupStatusAirFlowUS | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Group air flow in cubic feet per minute. | |||||||||||||||||||||
| SairIRRP500GroupStatusAirFlowMetric | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Group air flow in liters per second. | |||||||||||||||||||||
| SairIRRP500GroupStatusMaxRackInletTempUS | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Group maximum rack inlet temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRRP500GroupStatusMaxRackInletTempMetric | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Group maximum rack inlet temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRRP500GroupStatusMinRackInletTempUS | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Group minimum rack inlet temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRRP500GroupStatusMinRackInletTempMetric | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Group minimum rack inlet temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRRP500GroupStatusCoolDemand | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Group coolant demand in tenths of kiloWatts. | |||||||||||||||||||||
| SairIRRP500GroupStatusCoolOutput | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Group coolant output in tenths of kiloWatts. | |||||||||||||||||||||
| SairIRRP500GroupStatusHumidifyDemand | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.1.9 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The amount of humidification the group is demanding from the humidifiers in percent. | |||||||||||||||||||||
| SairIRRP500GroupStatusHumidifyOutput | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.1.10 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The actual amount of humidification the group is supplying in percent. | |||||||||||||||||||||
| SairIRRP500GroupStatusDehumidifyDemand | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.1.11 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The amount of dehumidification the group is demanding from the electric heaters in percent. | |||||||||||||||||||||
| SairIRRP500GroupStatusDehumidifyOutput | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.1.12 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The actual amount of dehumidification the group is supplying in percent. | |||||||||||||||||||||
| SairIRRP500GroupStatusReheatDemand | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.1.13 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The amount of heating the group is demanding from the electric heaters in percent. | |||||||||||||||||||||
| SairIRRP500GroupStatusReheatOutput | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.1.14 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The actual amount of heating the group is supplying in percent. | |||||||||||||||||||||
| SairIRRP500GroupStatusActiveFlowControlStatus | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.1.15 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Status of the active flow control system.
| |||||||||||||||||||||
| SairIRRP500GroupStatusDewPointTempUS | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.1.16 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Group average dew point temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRRP500GroupStatusDewPointTempMetric | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.1.17 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Group average dew point temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| NairIRRP500GroupSetpoints | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.2 | ||||||||||||||||||||
| SairIRRP500GroupSetpointsCoolUS | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.2.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Group cooling setpoint in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRRP500GroupSetpointsCoolMetric | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.2.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Group cooling setpoint in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRRP500GroupSetpointsSupplyAirUS | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.2.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Group supply air setpoint in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRRP500GroupSetpointsSupplyAirMetric | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.2.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Group supply air setpoint in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRRP500GroupSetpointsHumidify | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.2.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Group humidify setpoint in tenths of percent relative humidity. | |||||||||||||||||||||
| SairIRRP500GroupSetpointsDehumidify | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.2.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Group dehumidify setpoint in tenths of percent relative humidity. | |||||||||||||||||||||
| SairIRRP500GroupSetpointsDehumidifyDeadband | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.2.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Group dehumidify deadband in percent relative humidity. | |||||||||||||||||||||
| SairIRRP500GroupSetpointsReheatUS | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.2.8 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Group supply air setpoint in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRRP500GroupSetpointsReheatMetric | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.2.9 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Group supply air setpoint in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRRP500GroupSetpointsFanSpeedPreference | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.2.10 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The preferred fan speed setting.
| |||||||||||||||||||||
| SairIRRP500GroupSetpointsFanSpeedControl | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.2.11 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The fan speed control setting.
| |||||||||||||||||||||
| SairIRRP500GroupSetpointsActiveFlowControlBias | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.2.12 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The active flow control bias setting.
| |||||||||||||||||||||
| NairIRRP500GroupConfig | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.3 | ||||||||||||||||||||
| SairIRRP500GroupConfigNumberofCoolingUnits | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.3.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The number of cooling units. | |||||||||||||||||||||
| SairIRRP500GroupConfigConfigurationType | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.3.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The group configuration type.
| |||||||||||||||||||||
| SairIRRP500GroupConfigPercentGlycol | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.3.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The glycol mixture in percent. | |||||||||||||||||||||
| SairIRRP500GroupConfigCoolGainP | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.3.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The gain component of the cool PID in hundredths. | |||||||||||||||||||||
| SairIRRP500GroupConfigCoolResetRateI | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.3.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The integral component of the cool PID in hundredths. | |||||||||||||||||||||
| SairIRRP500GroupConfigCoolDerivativeD | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.3.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The derivative component of the cool PID in hundredths. | |||||||||||||||||||||
| SairIRRP500GroupConfigHumidifySensitivityBand | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.3.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The percent relative humidity below the setpoint that will cause the humidifier to run at 100% capacity. | |||||||||||||||||||||
| SairIRRP500GroupConfigReheatGainP | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.3.8 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The gain component of the reheat PID in hundredths. | |||||||||||||||||||||
| SairIRRP500GroupConfigReheatResetRateI | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.3.9 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The integral component of the reheat PID in hundredths. | |||||||||||||||||||||
| SairIRRP500GroupConfigReheatDerivativeD | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.3.10 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The derivative component of the reheat PID in hundredths. | |||||||||||||||||||||
| SairIRRP500GroupConfigMaxFanSpeed | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.3.11 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The maximum desired fan speed setting in percent. | |||||||||||||||||||||
| SairIRRP500GroupConfigNumberofBackupUnits | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.3.12 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The number of backup units. | |||||||||||||||||||||
| SairIRRP500GroupConfigRuntimeBalancingEnable | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.3.13 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Enable or disable runtime balancing feature.
| |||||||||||||||||||||
| SairIRRP500GroupConfigLoadAssistEnable | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.3.14 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Enable or disable load assist feature.
| |||||||||||||||||||||
| SairIRRP500GroupConfigFullRPBackups | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.3.15 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The number of full featured RPs that can be used as backup units. | |||||||||||||||||||||
| SairIRRP500GroupConfigNumberOfActiveFlowControllers | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.3.16 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The number of active flow controllers present in the group. | |||||||||||||||||||||
| SairIRRP500GroupConfigActiveFlowControllerLampTest | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.3.17 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Turns off/on the active flow controller lamp test.
| |||||||||||||||||||||
| SairIRRP500GroupConfigAltitudeUS | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.3.18 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The group altitude of the units above sea level in feet. | |||||||||||||||||||||
| SairIRRP500GroupConfigAltitudeMetric | 1.3.6.1.4.1.318.1.1.13.3.3.2.1.3.19 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The group altitude of the units above sea level in meters. | |||||||||||||||||||||
| NairIRRP500Unit | 1.3.6.1.4.1.318.1.1.13.3.3.2.2 | ||||||||||||||||||||
| NairIRRP500UnitIdent | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.1 | ||||||||||||||||||||
| SairIRRP500UnitIdentID | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.1.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The unit identification number. | |||||||||||||||||||||
| SairIRRP500UnitIdentName | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.1.2 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory A character string identifying the unit name. | |||||||||||||||||||||
| SairIRRP500UnitIdentLocation | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.1.3 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory A character string identifying the unit location. | |||||||||||||||||||||
| SairIRRP500UnitIdentModelNumber | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the unit model number. | |||||||||||||||||||||
| SairIRRP500UnitIdentSerialNumber | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the unit serial number. | |||||||||||||||||||||
| SairIRRP500UnitIdentFirmwareRevision | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.1.6 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the unit firmware version. | |||||||||||||||||||||
| SairIRRP500UnitIdentHardwareRevision | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.1.7 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the unit controller hardware revision. | |||||||||||||||||||||
| SairIRRP500UnitIdentManufactureDate | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.1.8 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the unit manufacture date. | |||||||||||||||||||||
| NairIRRP500UnitStatus | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.2 | ||||||||||||||||||||
| SairIRRP500UnitStatusOperateMode | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The cooling unit operating mode.
| |||||||||||||||||||||
| SairIRRP500UnitStatusMaximumRackInletTempUS | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The maximum unit rack inlet temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRRP500UnitStatusMaximumRackInletTempMetric | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The maximum unit rack inlet temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRRP500UnitStatusSupplyAirTempUS | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit supply air temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRRP500UnitStatusSupplyAirTempMetric | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit supply air temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRRP500UnitStatusReturnAirTempUS | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit return air temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRRP500UnitStatusReturnAirTempMetric | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit return air temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRRP500UnitStatusSupplyHumidity | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.8 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The relative humidity of the supply air in tenths of percent. | |||||||||||||||||||||
| SairIRRP500UnitStatusReturnHumidity | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.9 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The relative humidity of the return air in tenths of percent. | |||||||||||||||||||||
| SairIRRP500UnitStatusAirFlowUS | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.10 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit air flow in cubic feet per minute. | |||||||||||||||||||||
| SairIRRP500UnitStatusAirFlowMetric | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.11 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit air flow in hundredths of liters per second. | |||||||||||||||||||||
| SairIRRP500UnitStatusFanSpeed | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.12 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit average fan speed in tenths of percent. | |||||||||||||||||||||
| SairIRRP500UnitStatusCoolDemand | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.13 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit cooling demand in tenths of kiloWatts. | |||||||||||||||||||||
| SairIRRP500UnitStatusCoolOutput | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.14 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit cooling output in tenths of kiloWatts. | |||||||||||||||||||||
| SairIRRP500UnitStatusHumidifyDemand | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.15 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The amount of humidification the unit is demanding from the humidifier in percent. | |||||||||||||||||||||
| SairIRRP500UnitStatusHumidifyOutput | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.16 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The actual humidification output of the unit in percent. | |||||||||||||||||||||
| SairIRRP500UnitStatusDehumidifyDemand | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.17 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The amount of dehumidification the unit is demanding in percent. | |||||||||||||||||||||
| SairIRRP500UnitStatusDehumidifyOutput | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.18 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The actual dehumidification output of the unit in percent. | |||||||||||||||||||||
| SairIRRP500UnitStatusReheatDemand | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.19 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The amount of heating the unit is demanding from the electric heater in percent. | |||||||||||||||||||||
| SairIRRP500UnitStatusReheatOutput | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.20 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The actual heating output of the unit in percent. | |||||||||||||||||||||
| SairIRRP500UnitStatusInputState | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.21 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The state of the input contact.
| |||||||||||||||||||||
| SairIRRP500UnitStatusOutputState | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.22 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The state of the output relay.
| |||||||||||||||||||||
| SairIRRP500UnitStatusRackInletTemperature1US | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.23 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit rack inlet temperature sensor in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRRP500UnitStatusRackInletTemperature1Metric | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.24 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit rack inlet temperature sensor in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRRP500UnitStatusRackInletTemperature2US | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.25 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit rack inlet temperature sensor in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRRP500UnitStatusRackInletTemperature2Metric | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.26 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit rack inlet temperature sensor in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRRP500UnitStatusRackInletTemperature3US | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.27 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit rack inlet temperature sensor in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRRP500UnitStatusRackInletTemperature3Metric | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.28 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit rack inlet temperature sensor in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRRP500UnitStatusContainmtDPUS | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.29 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit containment differential pressure in hundredths of inches of water. | |||||||||||||||||||||
| SairIRRP500UnitStatusContainmtDPMetric | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.30 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit containment differential pressure in Pa. | |||||||||||||||||||||
| SairIRRP500UnitStatusFilterDPUS | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.31 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit air filter differential pressure in hundredths of inches of water. | |||||||||||||||||||||
| SairIRRP500UnitStatusFilterDPMetric | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.32 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit air filter differential pressure in Pa. | |||||||||||||||||||||
| SairIRRP500UnitStatusHumidifierCurrent | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.33 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The humidifier current of the unit in tenths of amperes. | |||||||||||||||||||||
| SairIRRP500UnitStatusHumidifierWaterConductivity | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.34 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The water conductivity in the humidifier of the unit in microSiemens/cm. | |||||||||||||||||||||
| SairIRRP500UnitStatusActivePowerSource | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.35 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The power source that is powering the unit.
| |||||||||||||||||||||
| SairIRRP500UnitStatusFluidValvePosition | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.36 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The fluid valve position in percent open. | |||||||||||||||||||||
| SairIRRP500UnitStatusFluidFlowUS | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.37 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The fluid flow in tenths of gallons per minute. | |||||||||||||||||||||
| SairIRRP500UnitStatusFluidFlowMetric | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.38 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The fluid flow in hundredths of liters per second. | |||||||||||||||||||||
| SairIRRP500UnitStatusEnteringFluidTemperatureUS | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.39 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The temperature of the entering fluid in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRRP500UnitStatusEnteringFluidTemperatureMetric | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.40 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The temperature of the entering fluid in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRRP500UnitStatusLeavingFluidTemperatureUS | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.41 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The temperature of the Leaving fluid in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRRP500UnitStatusLeavingFluidTemperatureMetric | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.42 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The temperature of the Leaving fluid in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRRP500UnitStatusLeakSensor | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.43 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The state (no-leak/leak) of the leak sensor.
| |||||||||||||||||||||
| NairIRRP500UnitRunHours | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.3 | ||||||||||||||||||||
| SairIRRP500UnitRunHoursAirFilter | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.3.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit air filter run hours in hours. | |||||||||||||||||||||
| SairIRRP500UnitRunHoursCondensatePump | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.3.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit condensate pump run hours in hours. | |||||||||||||||||||||
| SairIRRP500UnitRunHoursHumidifier | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.3.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit fan right power supply run hours in hours. | |||||||||||||||||||||
| SairIRRP500UnitRunHoursFan1 | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.3.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit fan 1 run hours in hours. | |||||||||||||||||||||
| SairIRRP500UnitRunHoursHeater1 | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.3.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit heater 1 run hours in hours. | |||||||||||||||||||||
| SairIRRP500UnitRunHoursFan2 | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.3.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit fan 2 run hours in hours. | |||||||||||||||||||||
| SairIRRP500UnitRunHoursHeater2 | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.3.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit Heater 2 run hours in hours. | |||||||||||||||||||||
| SairIRRP500UnitRunHoursFan3 | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.3.8 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit fan 3 run hours in hours. | |||||||||||||||||||||
| SairIRRP500UnitRunHoursHeater3 | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.3.9 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit heater 3 run hours in hours. | |||||||||||||||||||||
| SairIRRP500UnitRunHoursSystem | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.3.10 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Total system run hours. | |||||||||||||||||||||
| NairIRRP500UnitServiceIntervals | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.4 | ||||||||||||||||||||
| SairIRRP500UnitServiceIntervalAirFilter | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.4.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Air filter service interval in weeks. | |||||||||||||||||||||
| SairIRRP500UnitServiceIntervalAirFilterAlarm | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.4.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The air filter service interval alarm enable/disable.
| |||||||||||||||||||||
| SairIRRP500UnitServiceIntervalHumidifier | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.4.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Humidifier service interval in weeks. | |||||||||||||||||||||
| SairIRRP500UnitServiceIntervalHumidifierAlarm | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.4.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The humidifier service interval alarm enable/disable.
| |||||||||||||||||||||
| SairIRRP500UnitServiceIntervalHeater | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.4.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Heater service interval in weeks. | |||||||||||||||||||||
| SairIRRP500UnitServiceIntervalHeaterAlarm | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.4.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The heater service interval alarm enable/disable.
| |||||||||||||||||||||
| SairIRRP500UnitServiceIntervalCondensatePump | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.4.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Condensate pump service interval in weeks. | |||||||||||||||||||||
| SairIRRP500UnitServiceIntervalCondensatePumpAlarm | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.4.8 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The condensate pump service interval alarm enable/disable.
| |||||||||||||||||||||
| SairIRRP500UnitServiceIntervalFans | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.4.9 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Fans service interval in weeks. | |||||||||||||||||||||
| SairIRRP500UnitServiceIntervalFansAlarm | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.4.10 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The fans service interval alarm enable/disable.
| |||||||||||||||||||||
| NairIRRP500UnitThresholds | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.5 | ||||||||||||||||||||
| SairIRRP500UnitThresholdsRackInletHighTempUS | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.5.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Unit rack inlet air high temperature threshold in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRRP500UnitThresholdsRackInletHighTempMetric | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.5.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Unit rack inlet air high temperature threshold in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRRP500UnitThresholdsSupplyAirHighTempUS | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.5.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Unit supply air temperature high threshold in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRRP500UnitThresholdsSupplyAirHighTempMetric | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.5.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Unit supply air high temperature high threshold in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRRP500UnitThresholdsReturnAirHighTempUS | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.5.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Unit return air high temperature threshold in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRRP500UnitThresholdsReturnAirHighTempMetric | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.5.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Unit return air high temperature threshold in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRRP500UnitThresholdsReturnHumidityHigh | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.5.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Unit return humidity high threshold in tenths of percent relative humidity. | |||||||||||||||||||||
| SairIRRP500UnitThresholdsReturnHumidityLow | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.5.8 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Unit return humidity low threshold in tenths of percent relative humidity. | |||||||||||||||||||||
| SairIRRP500UnitThresholdsEnteringFluidHighTempUS | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.5.9 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Entering fluid high temperature threshold in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRRP500UnitThresholdsEnteringFluidHighTempMetric | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.5.10 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Entering fluid high temperature threshold in tenths of degrees Celsius. | |||||||||||||||||||||
| NairIRRP500UnitConfig | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.6 | ||||||||||||||||||||
| SairIRRP500UnitConfigStartupDelay | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.6.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The startup delay in seconds. | |||||||||||||||||||||
| SairIRRP500UnitConfigCoolCapacity | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.6.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The cooling capacity options setting.
| |||||||||||||||||||||
| SairIRRP500UnitConfigIdleOnLeakDetect | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.6.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The idle on leak options setting.
| |||||||||||||||||||||
| SairIRRP500UnitConfigInputNormalState | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.6.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The normal state of the input contact.
| |||||||||||||||||||||
| SairIRRP500UnitConfigOutputNormalState | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.6.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The normal state of the output relay.
| |||||||||||||||||||||
| SairIRRP500UnitConfigOutputSource | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.6.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The source of output relay change.
| |||||||||||||||||||||
| SairIRRP500UnitConfigHumidifyEnable | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.6.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Enable/disable humidification.
| |||||||||||||||||||||
| SairIRRP500UnitConfigHumidifierControl | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.6.8 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The humidifier drain control.
| |||||||||||||||||||||
| SairIRRP500UnitConfigDehumidifyEnable | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.6.9 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Enable/disable dehumidification.
| |||||||||||||||||||||
| SairIRRP500UnitConfigReheatEnable | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.6.10 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Enable/disable reheat.
| |||||||||||||||||||||
| SairIRRP500UnitConfigHeatAssistEnable | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.6.11 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Enable/disable heat assist.
| |||||||||||||||||||||
| SairIRRP500UnitConfigPowerSourceConfig | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.6.12 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Configure the input power source: (1) single feed or (2) dual feed.
| |||||||||||||||||||||
| SairIRRP500UnitConfigUnitRoleOverride | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.6.13 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory When this OID value is (1) automatic, the system determines which units are used as primary units and which units are used as backups. When this OID value is (2) forcedOn, the connected unit is set as a primary unit.
| |||||||||||||||||||||
| SairIRRP500UnitConfigSecondaryPowerFeedCapability | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.6.14 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Available on chilled water units. When the power source config setting is set to dual, setting this value to reduced (2) will inhibit the heater and humdifier when the unit is being powered from the secondary input.
| |||||||||||||||||||||
| SairIRRP500UnitConfigIdleOnCoolFail | 1.3.6.1.4.1.318.1.1.13.3.3.2.2.6.15 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory When this OID value is (1) enable, the unit idles if it detects that it is blowing warm air into the cold aisle. The unit will attempt to restart at 5 minute intervals.
| |||||||||||||||||||||
| NairIRSC | 1.3.6.1.4.1.318.1.1.13.3.4 | ||||||||||||||||||||
| NairIRSCUnit | 1.3.6.1.4.1.318.1.1.13.3.4.1 | ||||||||||||||||||||
| NairIRSCUnitIdent | 1.3.6.1.4.1.318.1.1.13.3.4.1.1 | ||||||||||||||||||||
| SairIRSCUnitIdentName | 1.3.6.1.4.1.318.1.1.13.3.4.1.1.1 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory A character string identifying the unit name. | |||||||||||||||||||||
| SairIRSCUnitIdentLocation | 1.3.6.1.4.1.318.1.1.13.3.4.1.1.2 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory A character string identifying the unit location. | |||||||||||||||||||||
| SairIRSCUnitIdentModelNumber | 1.3.6.1.4.1.318.1.1.13.3.4.1.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the unit model number. | |||||||||||||||||||||
| SairIRSCUnitIdentSerialNumber | 1.3.6.1.4.1.318.1.1.13.3.4.1.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the unit serial number. | |||||||||||||||||||||
| SairIRSCUnitIdentFirmwareRevision | 1.3.6.1.4.1.318.1.1.13.3.4.1.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the unit firmware version. | |||||||||||||||||||||
| SairIRSCUnitIdentHardwareRevision | 1.3.6.1.4.1.318.1.1.13.3.4.1.1.6 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the unit controller hardware revision. | |||||||||||||||||||||
| SairIRSCUnitIdentManufactureDate | 1.3.6.1.4.1.318.1.1.13.3.4.1.1.7 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the unit manufacture date. | |||||||||||||||||||||
| NairIRSCUnitStatus | 1.3.6.1.4.1.318.1.1.13.3.4.1.2 | ||||||||||||||||||||
| SairIRSCUnitStatusOperateMode | 1.3.6.1.4.1.318.1.1.13.3.4.1.2.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The cooling unit operating mode.
| |||||||||||||||||||||
| SairIRSCUnitStatusCoolOutput | 1.3.6.1.4.1.318.1.1.13.3.4.1.2.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit cooling output in tenths of kW. | |||||||||||||||||||||
| SairIRSCUnitStatusCoolDemand | 1.3.6.1.4.1.318.1.1.13.3.4.1.2.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit cooling demand in tenths of kW. | |||||||||||||||||||||
| SairIRSCUnitStatusAirFlowUS | 1.3.6.1.4.1.318.1.1.13.3.4.1.2.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit air flow in cubic feet per minute. | |||||||||||||||||||||
| SairIRSCUnitStatusAirFlowMetric | 1.3.6.1.4.1.318.1.1.13.3.4.1.2.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit air flow in liters per second. | |||||||||||||||||||||
| SairIRSCUnitStatusRackInletTempUS | 1.3.6.1.4.1.318.1.1.13.3.4.1.2.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit rack inlet temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRSCUnitStatusRackInletTempMetric | 1.3.6.1.4.1.318.1.1.13.3.4.1.2.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit rack inlet temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRSCUnitStatusSupplyAirTempUS | 1.3.6.1.4.1.318.1.1.13.3.4.1.2.8 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit supply air temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRSCUnitStatusSupplyAirTempMetric | 1.3.6.1.4.1.318.1.1.13.3.4.1.2.9 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit supply air temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRSCUnitStatusReturnAirTempUS | 1.3.6.1.4.1.318.1.1.13.3.4.1.2.10 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit return air temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRSCUnitStatusReturnAirTempMetric | 1.3.6.1.4.1.318.1.1.13.3.4.1.2.11 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit return air temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRSCUnitStatusSuctionTempUS | 1.3.6.1.4.1.318.1.1.13.3.4.1.2.12 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit suction temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRSCUnitStatusSuctionTempMetric | 1.3.6.1.4.1.318.1.1.13.3.4.1.2.13 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit suction temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRSCUnitStatusSuperheatTempUS | 1.3.6.1.4.1.318.1.1.13.3.4.1.2.14 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit superheat temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRSCUnitStatusSuperheatTempMetric | 1.3.6.1.4.1.318.1.1.13.3.4.1.2.15 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit superheat temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRSCUnitStatusContainmtDPUS | 1.3.6.1.4.1.318.1.1.13.3.4.1.2.16 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit containment differential pressure in hundredths of inches of water. | |||||||||||||||||||||
| SairIRSCUnitStatusContainmtDPMetric | 1.3.6.1.4.1.318.1.1.13.3.4.1.2.17 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit containment differential pressure in Pa. | |||||||||||||||||||||
| SairIRSCUnitStatusFilterDPUS | 1.3.6.1.4.1.318.1.1.13.3.4.1.2.18 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit air filter differential pressure in hundredths of inches of water. | |||||||||||||||||||||
| SairIRSCUnitStatusFilterDPMetric | 1.3.6.1.4.1.318.1.1.13.3.4.1.2.19 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit air filter differential pressure in Pa. | |||||||||||||||||||||
| SairIRSCUnitStatusSuctionPressureUS | 1.3.6.1.4.1.318.1.1.13.3.4.1.2.20 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit suction pressure in pounds per square inch (PSI). | |||||||||||||||||||||
| SairIRSCUnitStatusSuctionPressureMetric | 1.3.6.1.4.1.318.1.1.13.3.4.1.2.21 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit suction pressure in kiloPascals (kPa). | |||||||||||||||||||||
| SairIRSCUnitStatusDischargePressureUS | 1.3.6.1.4.1.318.1.1.13.3.4.1.2.22 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit discharge pressure in pounds per square inch (PSI). | |||||||||||||||||||||
| SairIRSCUnitStatusDischargePressureMetric | 1.3.6.1.4.1.318.1.1.13.3.4.1.2.23 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit discharge pressure in kiloPascals (kPa). | |||||||||||||||||||||
| SairIRSCUnitStatusEvaporatorFanSpeed | 1.3.6.1.4.1.318.1.1.13.3.4.1.2.24 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit average evaporator fan speed in tenths of percent. | |||||||||||||||||||||
| SairIRSCUnitStatusCondenserFanSpeed | 1.3.6.1.4.1.318.1.1.13.3.4.1.2.25 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit average condenser fan speed in tenths of percent. | |||||||||||||||||||||
| SairIRSCUnitStatusInputState | 1.3.6.1.4.1.318.1.1.13.3.4.1.2.26 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The state of the input contact.
| |||||||||||||||||||||
| SairIRSCUnitStatusOutputState | 1.3.6.1.4.1.318.1.1.13.3.4.1.2.27 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The state of the output relay.
| |||||||||||||||||||||
| SairIRSCUnitStatusCondOutletTempUS | 1.3.6.1.4.1.318.1.1.13.3.4.1.2.28 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit condenser outlet air temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRSCUnitStatusCondOutletTempMetric | 1.3.6.1.4.1.318.1.1.13.3.4.1.2.29 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit condenser outlet air temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRSCUnitStatusCondInletTempUS | 1.3.6.1.4.1.318.1.1.13.3.4.1.2.30 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit condenser inlet air temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRSCUnitStatusCondInletTempMetric | 1.3.6.1.4.1.318.1.1.13.3.4.1.2.31 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit condenser inlet air temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRSCUnitStatusCompressor | 1.3.6.1.4.1.318.1.1.13.3.4.1.2.32 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The state (off/on) of the compressor.
| |||||||||||||||||||||
| SairIRSCUnitStatusLeakSensor | 1.3.6.1.4.1.318.1.1.13.3.4.1.2.33 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The state (no-leak/leak) of the leak sensor.
| |||||||||||||||||||||
| NairIRSCUnitRunHours | 1.3.6.1.4.1.318.1.1.13.3.4.1.3 | ||||||||||||||||||||
| SairIRSCUnitRunHoursAirFilter | 1.3.6.1.4.1.318.1.1.13.3.4.1.3.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit air filter run hours. | |||||||||||||||||||||
| SairIRSCUnitRunHoursEvaporatorFan1 | 1.3.6.1.4.1.318.1.1.13.3.4.1.3.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit evaporator fan 1 run hours. | |||||||||||||||||||||
| SairIRSCUnitRunHoursEvaporatorFan2 | 1.3.6.1.4.1.318.1.1.13.3.4.1.3.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit evaporator fan 2 run hours. | |||||||||||||||||||||
| SairIRSCUnitRunHoursEvaporatorFan3 | 1.3.6.1.4.1.318.1.1.13.3.4.1.3.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit evaporator fan 3 run hours. | |||||||||||||||||||||
| SairIRSCUnitRunHoursCondenserFan1 | 1.3.6.1.4.1.318.1.1.13.3.4.1.3.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit condenser fan 1 run hours. | |||||||||||||||||||||
| SairIRSCUnitRunHoursCondenserFan2 | 1.3.6.1.4.1.318.1.1.13.3.4.1.3.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit condenser fan 2 run hours. | |||||||||||||||||||||
| SairIRSCUnitRunHoursCondenserFan3 | 1.3.6.1.4.1.318.1.1.13.3.4.1.3.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit condenser fan 3 run hours. | |||||||||||||||||||||
| SairIRSCUnitRunHoursFanPowerSupplyLeft | 1.3.6.1.4.1.318.1.1.13.3.4.1.3.8 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit fan left power supply run hours. | |||||||||||||||||||||
| SairIRSCUnitRunHoursFanPowerSupplyRight | 1.3.6.1.4.1.318.1.1.13.3.4.1.3.9 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit fan right power supply run hours. | |||||||||||||||||||||
| SairIRSCUnitRunHoursCondensatePump | 1.3.6.1.4.1.318.1.1.13.3.4.1.3.10 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit condensate pump run hours. | |||||||||||||||||||||
| SairIRSCUnitRunHoursCompressor | 1.3.6.1.4.1.318.1.1.13.3.4.1.3.11 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit compressor run hours. | |||||||||||||||||||||
| NairIRSCUnitServiceIntervals | 1.3.6.1.4.1.318.1.1.13.3.4.1.4 | ||||||||||||||||||||
| SairIRSCUnitServiceIntervalsAirFilter | 1.3.6.1.4.1.318.1.1.13.3.4.1.4.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Air filter service interval in weeks. | |||||||||||||||||||||
| SairIRSCUnitServiceIntervalsAirFilterAlarm | 1.3.6.1.4.1.318.1.1.13.3.4.1.4.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The air filter service interval alarm enable/disable.
| |||||||||||||||||||||
| NairIRSCUnitThresholds | 1.3.6.1.4.1.318.1.1.13.3.4.1.5 | ||||||||||||||||||||
| SairIRSCUnitThresholdsRackInletHighTempUS | 1.3.6.1.4.1.318.1.1.13.3.4.1.5.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Unit rack inlet air high temperature threshold in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRSCUnitThresholdsRackInletHighTempMetric | 1.3.6.1.4.1.318.1.1.13.3.4.1.5.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Unit rack inlet air high temperature threshold in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRSCUnitThresholdsSupplyAirHighTempUS | 1.3.6.1.4.1.318.1.1.13.3.4.1.5.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Unit supply air high temperature threshold in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRSCUnitThresholdsSupplyAirHighTempMetric | 1.3.6.1.4.1.318.1.1.13.3.4.1.5.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Unit supply air high temperature threshold in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRSCUnitThresholdsReturnAirHighTempUS | 1.3.6.1.4.1.318.1.1.13.3.4.1.5.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Unit return air high temperature threshold in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRSCUnitThresholdsReturnAirHighTempMetric | 1.3.6.1.4.1.318.1.1.13.3.4.1.5.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Unit return air high temperature threshold in tenths of degrees Celsius. | |||||||||||||||||||||
| NairIRSCUnitSetpoints | 1.3.6.1.4.1.318.1.1.13.3.4.1.6 | ||||||||||||||||||||
| SairIRSCUnitSetptsCoolSetpointUS | 1.3.6.1.4.1.318.1.1.13.3.4.1.6.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Unit cooling setpoint in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRSCUnitSetptsCoolSetpointMetric | 1.3.6.1.4.1.318.1.1.13.3.4.1.6.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Unit cooling setpoint in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRSCUnitSetptsCoolDeadbandUS | 1.3.6.1.4.1.318.1.1.13.3.4.1.6.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Unit cooling deadband in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRSCUnitSetptsCoolDeadbandMetric | 1.3.6.1.4.1.318.1.1.13.3.4.1.6.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Unit cooling deadband in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRSCUnitSetptsFanSpeedPreference | 1.3.6.1.4.1.318.1.1.13.3.4.1.6.5 | AirIRSCFanSpeedPreference | RW | mandatory | |||||||||||||||||
scalar · AirIRSCFanSpeedPreference · read-write · mandatory The preferred fan speed setting. | |||||||||||||||||||||
| SairIRSCUnitSetptsSupplyAirSetpointUS | 1.3.6.1.4.1.318.1.1.13.3.4.1.6.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Unit supply air setpoint in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRSCUnitSetptsSupplyAirSetpointMetric | 1.3.6.1.4.1.318.1.1.13.3.4.1.6.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Unit supply air setpoint in tenths of degrees Celsius. | |||||||||||||||||||||
| NairIRSCUnitConfig | 1.3.6.1.4.1.318.1.1.13.3.4.1.7 | ||||||||||||||||||||
| SairIRSCUnitConfigConfigurationType | 1.3.6.1.4.1.318.1.1.13.3.4.1.7.1 | AirIRSCConfigType | RW | mandatory | |||||||||||||||||
scalar · AirIRSCConfigType · read-write · mandatory The unit configuration type. | |||||||||||||||||||||
| SairIRSCUnitConfigCapacityControlType | 1.3.6.1.4.1.318.1.1.13.3.4.1.7.2 | AirIRSCCapacityControlType | RW | mandatory | |||||||||||||||||
scalar · AirIRSCCapacityControlType · read-write · mandatory The unit capacity control. | |||||||||||||||||||||
| SairIRSCUnitConfigStartupDelay | 1.3.6.1.4.1.318.1.1.13.3.4.1.7.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The startup delay in seconds. | |||||||||||||||||||||
| SairIRSCUnitConfigIdleOnLeakDetect | 1.3.6.1.4.1.318.1.1.13.3.4.1.7.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The idle on leak options setting.
| |||||||||||||||||||||
| SairIRSCUnitConfigInputNormalState | 1.3.6.1.4.1.318.1.1.13.3.4.1.7.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The normal state of the input contact.
| |||||||||||||||||||||
| SairIRSCUnitConfigOutputNormalState | 1.3.6.1.4.1.318.1.1.13.3.4.1.7.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The normal state of the output relay.
| |||||||||||||||||||||
| SairIRSCUnitConfigOutputSource | 1.3.6.1.4.1.318.1.1.13.3.4.1.7.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The source of output relay change.
| |||||||||||||||||||||
| SairIRSCUnitConfigAltitudeUS | 1.3.6.1.4.1.318.1.1.13.3.4.1.7.8 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The altitude of the unit above sea level in feet. | |||||||||||||||||||||
| SairIRSCUnitConfigAltitudeMetric | 1.3.6.1.4.1.318.1.1.13.3.4.1.7.9 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The altitude of the unit above sea level in meters. | |||||||||||||||||||||
| SairIRSCUnitConfigOpControl | 1.3.6.1.4.1.318.1.1.13.3.4.1.7.10 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The unit operational control.
| |||||||||||||||||||||
| NairIRSCGroup | 1.3.6.1.4.1.318.1.1.13.3.4.2 | ||||||||||||||||||||
| NairIRSCGroupStatus | 1.3.6.1.4.1.318.1.1.13.3.4.2.1 | ||||||||||||||||||||
| SairIRSCGroupStatusCoolOutput | 1.3.6.1.4.1.318.1.1.13.3.4.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The group cooling output in tenths of kW. | |||||||||||||||||||||
| SairIRSCGroupStatusCoolDemand | 1.3.6.1.4.1.318.1.1.13.3.4.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The group cooling demand in tenths of kW. | |||||||||||||||||||||
| SairIRSCGroupStatusAirFlowUS | 1.3.6.1.4.1.318.1.1.13.3.4.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The group air flow in cubic feet per minute. | |||||||||||||||||||||
| SairIRSCGroupStatusAirFlowMetric | 1.3.6.1.4.1.318.1.1.13.3.4.2.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The group air flow in liters per second. | |||||||||||||||||||||
| SairIRSCGroupStatusMaxRackInletTempUS | 1.3.6.1.4.1.318.1.1.13.3.4.2.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The group maximum rack inlet temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRSCGroupStatusMaxRackInletTempMetric | 1.3.6.1.4.1.318.1.1.13.3.4.2.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The group maximum rack inlet temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRSCGroupStatusMinRackInletTempUS | 1.3.6.1.4.1.318.1.1.13.3.4.2.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The group minimum rack inlet temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRSCGroupStatusMinRackInletTempMetric | 1.3.6.1.4.1.318.1.1.13.3.4.2.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The group minimum rack inlet temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRSCGroupStatusMaxReturnAirTempUS | 1.3.6.1.4.1.318.1.1.13.3.4.2.1.9 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The group maximum return air temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRSCGroupStatusMaxReturnAirTempMetric | 1.3.6.1.4.1.318.1.1.13.3.4.2.1.10 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The group maximum return air temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRSCGroupStatusMinReturnAirTempUS | 1.3.6.1.4.1.318.1.1.13.3.4.2.1.11 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The group minimum return air temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRSCGroupStatusMinReturnAirTempMetric | 1.3.6.1.4.1.318.1.1.13.3.4.2.1.12 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The group minimum return air temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRSCGroupStatusActiveFlowControlStatus | 1.3.6.1.4.1.318.1.1.13.3.4.2.1.13 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Status of the active flow control system.
| |||||||||||||||||||||
| NairIRSCGroupSetpoints | 1.3.6.1.4.1.318.1.1.13.3.4.2.2 | ||||||||||||||||||||
| SairIRSCGroupSetptsCoolSetpointUS | 1.3.6.1.4.1.318.1.1.13.3.4.2.2.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Group cooling setpoint in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRSCGroupSetptsCoolSetpointMetric | 1.3.6.1.4.1.318.1.1.13.3.4.2.2.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Group cooling setpoint in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRSCGroupSetptsCoolDeadbandUS | 1.3.6.1.4.1.318.1.1.13.3.4.2.2.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Group cooling deadband in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRSCGroupSetptsCoolDeadbandMetric | 1.3.6.1.4.1.318.1.1.13.3.4.2.2.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Group cooling deadband in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRSCGroupSetptsFanSpeedPreference | 1.3.6.1.4.1.318.1.1.13.3.4.2.2.5 | AirIRSCFanSpeedPreference | RW | mandatory | |||||||||||||||||
scalar · AirIRSCFanSpeedPreference · read-write · mandatory The group preferred fan speed setting. | |||||||||||||||||||||
| SairIRSCGroupSetptsSupplyAirSetpointUS | 1.3.6.1.4.1.318.1.1.13.3.4.2.2.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Group supply air setpoint in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRSCGroupSetptsSupplyAirSetpointMetric | 1.3.6.1.4.1.318.1.1.13.3.4.2.2.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Group supply air setpoint in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRSCGroupSetpointsActiveFlowControlBias | 1.3.6.1.4.1.318.1.1.13.3.4.2.2.8 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The active flow control bias setting.
| |||||||||||||||||||||
| NairIRSCGroupConfig | 1.3.6.1.4.1.318.1.1.13.3.4.2.3 | ||||||||||||||||||||
| SairIRSCGroupConfigNumberofCoolingUnits | 1.3.6.1.4.1.318.1.1.13.3.4.2.3.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The number of cooling units. | |||||||||||||||||||||
| SairIRSCGroupConfigConfigurationType | 1.3.6.1.4.1.318.1.1.13.3.4.2.3.2 | AirIRSCConfigType | RW | mandatory | |||||||||||||||||
scalar · AirIRSCConfigType · read-write · mandatory The group configuration type. | |||||||||||||||||||||
| SairIRSCGroupConfigCapacityControlType | 1.3.6.1.4.1.318.1.1.13.3.4.2.3.3 | AirIRSCCapacityControlType | RW | mandatory | |||||||||||||||||
scalar · AirIRSCCapacityControlType · read-write · mandatory The group capacity control. | |||||||||||||||||||||
| SairIRSCGroupConfigAltitudeUS | 1.3.6.1.4.1.318.1.1.13.3.4.2.3.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The group altitude of the units above sea level in feet. | |||||||||||||||||||||
| SairIRSCGroupConfigAltitudeMetric | 1.3.6.1.4.1.318.1.1.13.3.4.2.3.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The group altitude of the units above sea level in meters. | |||||||||||||||||||||
| SairIRSCGroupConfigFanSpeedControl | 1.3.6.1.4.1.318.1.1.13.3.4.2.3.6 | AirIRSCFanSpeedControl | RW | mandatory | |||||||||||||||||
scalar · AirIRSCFanSpeedControl · read-write · mandatory The group fan speed control. | |||||||||||||||||||||
| SairIRSCGroupConfigNumberOfActiveFlowControllers | 1.3.6.1.4.1.318.1.1.13.3.4.2.3.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The number of active flow controllers present in the group. | |||||||||||||||||||||
| SairIRSCGroupConfigActiveFlowControllerLampTest | 1.3.6.1.4.1.318.1.1.13.3.4.2.3.8 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Turns off/on the active flow controller lamp test.
| |||||||||||||||||||||
| NairIRGen2 | 1.3.6.1.4.1.318.1.1.13.4 | ||||||||||||||||||||
| NairIRG2Ident | 1.3.6.1.4.1.318.1.1.13.4.1 | ||||||||||||||||||||
| SairIRG2IdentName | 1.3.6.1.4.1.318.1.1.13.4.1.1 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory A character string identifying the unit name. | |||||||||||||||||||||
| SairIRG2IdentLocation | 1.3.6.1.4.1.318.1.1.13.4.1.2 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory A character string identifying the unit location. | |||||||||||||||||||||
| SairIRG2IdentModelNumber | 1.3.6.1.4.1.318.1.1.13.4.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the unit model number. | |||||||||||||||||||||
| SairIRG2IdentSerialNumber | 1.3.6.1.4.1.318.1.1.13.4.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the unit serial number. | |||||||||||||||||||||
| SairIRG2IdentFirmwareRevision | 1.3.6.1.4.1.318.1.1.13.4.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the unit firmware version. | |||||||||||||||||||||
| SairIRG2IdentHardwareRevision | 1.3.6.1.4.1.318.1.1.13.4.1.6 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the unit controller hardware revision. | |||||||||||||||||||||
| SairIRG2IdentManufactureDate | 1.3.6.1.4.1.318.1.1.13.4.1.7 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the unit manufacture date. | |||||||||||||||||||||
| SairIRG2IdentUnitSysOID | 1.3.6.1.4.1.318.1.1.13.4.1.8 | OBJECT IDENTIFIER | RO | mandatory | |||||||||||||||||
scalar · OBJECT IDENTIFIER · read-only · mandatory This OID contains an OID path to the device's top level unit data. | |||||||||||||||||||||
| SairIRG2IdentGroupSysOID | 1.3.6.1.4.1.318.1.1.13.4.1.9 | OBJECT IDENTIFIER | RO | mandatory | |||||||||||||||||
scalar · OBJECT IDENTIFIER · read-only · mandatory This OID contains an OID path to the device's top level group data. | |||||||||||||||||||||
| NairIRG2Group | 1.3.6.1.4.1.318.1.1.13.4.2 | ||||||||||||||||||||
| NairIRG2GroupStatus | 1.3.6.1.4.1.318.1.1.13.4.2.1 | ||||||||||||||||||||
| SairIRG2GroupStatusCoolOutput | 1.3.6.1.4.1.318.1.1.13.4.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The group cooling output in tenths of kilowatts (kW). | |||||||||||||||||||||
| SairIRG2GroupStatusCoolDemand | 1.3.6.1.4.1.318.1.1.13.4.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The group cooling demand in tenths of kilowatts (kW). | |||||||||||||||||||||
| SairIRG2GroupStatusAirFlowUS | 1.3.6.1.4.1.318.1.1.13.4.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The group air flow in cubic feet per minute. | |||||||||||||||||||||
| SairIRG2GroupStatusAirFlowMetric | 1.3.6.1.4.1.318.1.1.13.4.2.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The group air flow in hundredths of liters per second. | |||||||||||||||||||||
| SairIRG2GroupStatusMaxRackInletTempUS | 1.3.6.1.4.1.318.1.1.13.4.2.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The group maximum rack inlet temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRG2GroupStatusMaxRackInletTempMetric | 1.3.6.1.4.1.318.1.1.13.4.2.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The group maximum rack inlet temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRG2GroupStatusMinRackInletTempUS | 1.3.6.1.4.1.318.1.1.13.4.2.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The group minimum rack inlet temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRG2GroupStatusMinRackInletTempMetric | 1.3.6.1.4.1.318.1.1.13.4.2.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The group minimum rack inlet temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRG2GroupStatusMaxReturnAirTempUS | 1.3.6.1.4.1.318.1.1.13.4.2.1.9 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The group maximum return air temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRG2GroupStatusMaxReturnAirTempMetric | 1.3.6.1.4.1.318.1.1.13.4.2.1.10 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The group maximum return air temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRG2GroupStatusMinReturnAirTempUS | 1.3.6.1.4.1.318.1.1.13.4.2.1.11 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The group minimum return air temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRG2GroupStatusMinReturnAirTempMetric | 1.3.6.1.4.1.318.1.1.13.4.2.1.12 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The group minimum return air temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRG2GroupStatusActiveFlowControlStatus | 1.3.6.1.4.1.318.1.1.13.4.2.1.13 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Status of the active flow control system.
| |||||||||||||||||||||
| NairIRG2GroupSetpoints | 1.3.6.1.4.1.318.1.1.13.4.2.2 | ||||||||||||||||||||
| SairIRG2GroupSetptsCoolSetpointUS | 1.3.6.1.4.1.318.1.1.13.4.2.2.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Group cooling setpoint in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRG2GroupSetptsCoolSetpointMetric | 1.3.6.1.4.1.318.1.1.13.4.2.2.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Group cooling setpoint in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRG2GroupSetptsCoolDeadbandUS | 1.3.6.1.4.1.318.1.1.13.4.2.2.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Group cooling deadband in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRG2GroupSetptsCoolDeadbandMetric | 1.3.6.1.4.1.318.1.1.13.4.2.2.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Group cooling deadband in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRG2GroupSetptsFanSpeedPreference | 1.3.6.1.4.1.318.1.1.13.4.2.2.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The group preferred fan speed setting.
| |||||||||||||||||||||
| SairIRG2GroupSetptsSupplyAirSetpointUS | 1.3.6.1.4.1.318.1.1.13.4.2.2.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Group supply air setpoint in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRG2GroupSetptsSupplyAirSetpointMetric | 1.3.6.1.4.1.318.1.1.13.4.2.2.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Group supply air setpoint in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRG2GroupSetpointsActiveFlowControlBias | 1.3.6.1.4.1.318.1.1.13.4.2.2.8 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The active flow control bias setting.
| |||||||||||||||||||||
| NairIRG2GroupConfig | 1.3.6.1.4.1.318.1.1.13.4.2.3 | ||||||||||||||||||||
| SairIRG2GroupConfigNumberofCoolingUnits | 1.3.6.1.4.1.318.1.1.13.4.2.3.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The number of cooling units. | |||||||||||||||||||||
| SairIRG2GroupConfigConfigurationType | 1.3.6.1.4.1.318.1.1.13.4.2.3.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The group configuration type.
| |||||||||||||||||||||
| SairIRG2GroupConfigCapacityControlType | 1.3.6.1.4.1.318.1.1.13.4.2.3.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The group capacity control.
| |||||||||||||||||||||
| SairIRG2GroupConfigFanSpeedControl | 1.3.6.1.4.1.318.1.1.13.4.2.3.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The group fan speed control.
| |||||||||||||||||||||
| SairIRG2GroupConfigCoolGainP | 1.3.6.1.4.1.318.1.1.13.4.2.3.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The gain component of the PID in hundredths. | |||||||||||||||||||||
| SairIRG2GroupConfigCoolResetRateI | 1.3.6.1.4.1.318.1.1.13.4.2.3.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The integral component of the PID in hundredths. | |||||||||||||||||||||
| SairIRG2GroupConfigCoolDerivativeD | 1.3.6.1.4.1.318.1.1.13.4.2.3.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The derivative component of the PID in hundredths. | |||||||||||||||||||||
| SairIRG2GroupConfigCoolPIDReset | 1.3.6.1.4.1.318.1.1.13.4.2.3.8 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Will reset the PID coefficients back to the factory defaults.
| |||||||||||||||||||||
| SairIRG2GroupConfigNumberofBackupUnits | 1.3.6.1.4.1.318.1.1.13.4.2.3.9 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The number of backup units. | |||||||||||||||||||||
| SairIRG2GroupConfigRuntimeBalancingEnable | 1.3.6.1.4.1.318.1.1.13.4.2.3.10 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Enable or disable runtime balancing feature.
| |||||||||||||||||||||
| SairIRG2GroupConfigLoadAssistEnable | 1.3.6.1.4.1.318.1.1.13.4.2.3.11 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Enable or disable load assist feature.
| |||||||||||||||||||||
| SairIRG2GroupConfigNumberOfActiveFlowControllers | 1.3.6.1.4.1.318.1.1.13.4.2.3.12 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The number of active flow controllers present in the group. | |||||||||||||||||||||
| SairIRG2GroupConfigActiveFlowControllerLampTest | 1.3.6.1.4.1.318.1.1.13.4.2.3.13 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Turns off/on the active flow controller lamp test.
| |||||||||||||||||||||
| SairIRG2GroupConfigAltitudeUS | 1.3.6.1.4.1.318.1.1.13.4.2.3.14 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The group altitude of the units above sea level in feet. | |||||||||||||||||||||
| SairIRG2GroupConfigAltitudeMetric | 1.3.6.1.4.1.318.1.1.13.4.2.3.15 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The group altitude of the units above sea level in meters. | |||||||||||||||||||||
| NairIRG2Alarms | 1.3.6.1.4.1.318.1.1.13.4.3 | ||||||||||||||||||||
| SairIRG2AlarmsTableSize | 1.3.6.1.4.1.318.1.1.13.4.3.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of active alarms in the airIRG2AlarmsTable. | |||||||||||||||||||||
| TairIRG2AlarmsTable | 1.3.6.1.4.1.318.1.1.13.4.3.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Table of active alarms for the device. | |||||||||||||||||||||
| RairIRG2AlarmsEntry | 1.3.6.1.4.1.318.1.1.13.4.3.2.1 | NA | mandatory | ||||||||||||||||||
| CairIRG2AlarmsIndex | 1.3.6.1.4.1.318.1.1.13.4.3.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Alarm index. | |||||||||||||||||||||
| CairIRG2AlarmsEventCode | 1.3.6.1.4.1.318.1.1.13.4.3.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Code for the alarm. | |||||||||||||||||||||
| CairIRG2AlarmsDescription | 1.3.6.1.4.1.318.1.1.13.4.3.2.1.3 | DisplayString (SIZE (0..64)) | RO | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..64)) · read-only · mandatory Description of the alarm. | |||||||||||||||||||||
| NairIRG2RC | 1.3.6.1.4.1.318.1.1.13.4.4 | ||||||||||||||||||||
| NairIRG2RD | 1.3.6.1.4.1.318.1.1.13.4.5 | ||||||||||||||||||||
| NairIRG2RDType1 | 1.3.6.1.4.1.318.1.1.13.4.5.1 | ||||||||||||||||||||
| NairIRG2RDType2 | 1.3.6.1.4.1.318.1.1.13.4.5.2 | ||||||||||||||||||||
| NairIRG2RDT2Status | 1.3.6.1.4.1.318.1.1.13.4.5.2.1 | ||||||||||||||||||||
| SairIRG2RDT2StatusOperateMode | 1.3.6.1.4.1.318.1.1.13.4.5.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The cooling unit operating mode.
| |||||||||||||||||||||
| SairIRG2RDT2StatusCoolOutput | 1.3.6.1.4.1.318.1.1.13.4.5.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit cooling output in tenths of kilowatts (kW). | |||||||||||||||||||||
| SairIRG2RDT2StatusCoolDemand | 1.3.6.1.4.1.318.1.1.13.4.5.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit cooling demand in tenths of kilowatts (kW). | |||||||||||||||||||||
| SairIRG2RDT2StatusAirFlowUS | 1.3.6.1.4.1.318.1.1.13.4.5.2.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit air flow in cubic feet per minute. | |||||||||||||||||||||
| SairIRG2RDT2StatusAirFlowMetric | 1.3.6.1.4.1.318.1.1.13.4.5.2.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit air flow in liters per second. | |||||||||||||||||||||
| SairIRG2RDT2StatusRackInletTempUS | 1.3.6.1.4.1.318.1.1.13.4.5.2.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit rack inlet temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRG2RDT2StatusRackInletTempMetric | 1.3.6.1.4.1.318.1.1.13.4.5.2.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit rack inlet temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRG2RDT2StatusSupplyAirTempUS | 1.3.6.1.4.1.318.1.1.13.4.5.2.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit supply air temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRG2RDT2StatusSupplyAirTempMetric | 1.3.6.1.4.1.318.1.1.13.4.5.2.1.9 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit supply air temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRG2RDT2StatusReturnAirTempUS | 1.3.6.1.4.1.318.1.1.13.4.5.2.1.10 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit return air temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRG2RDT2StatusReturnAirTempMetric | 1.3.6.1.4.1.318.1.1.13.4.5.2.1.11 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit return air temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRG2RDT2StatusSuctionTempUS | 1.3.6.1.4.1.318.1.1.13.4.5.2.1.12 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit suction temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRG2RDT2StatusSuctionTempMetric | 1.3.6.1.4.1.318.1.1.13.4.5.2.1.13 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit suction temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRG2RDT2StatusSuperheatTempUS | 1.3.6.1.4.1.318.1.1.13.4.5.2.1.14 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit superheat temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRG2RDT2StatusSuperheatTempMetric | 1.3.6.1.4.1.318.1.1.13.4.5.2.1.15 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit superheat temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRG2RDT2StatusFilterDPUS | 1.3.6.1.4.1.318.1.1.13.4.5.2.1.16 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit air filter differential pressure in hundredths of inches of water. | |||||||||||||||||||||
| SairIRG2RDT2StatusFilterDPMetric | 1.3.6.1.4.1.318.1.1.13.4.5.2.1.17 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit air filter differential pressure in pascals (Pa). | |||||||||||||||||||||
| SairIRG2RDT2StatusSuctionPressureUS | 1.3.6.1.4.1.318.1.1.13.4.5.2.1.18 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit suction pressure in pounds per square inch (PSI). | |||||||||||||||||||||
| SairIRG2RDT2StatusSuctionPressureMetric | 1.3.6.1.4.1.318.1.1.13.4.5.2.1.19 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit suction pressure in kiloPascals (kPa). | |||||||||||||||||||||
| SairIRG2RDT2StatusDischargePressureUS | 1.3.6.1.4.1.318.1.1.13.4.5.2.1.20 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit discharge pressure in pounds per square inch (PSI). | |||||||||||||||||||||
| SairIRG2RDT2StatusDischargePressureMetric | 1.3.6.1.4.1.318.1.1.13.4.5.2.1.21 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit discharge pressure in kiloPascals (kPa). | |||||||||||||||||||||
| SairIRG2RDT2StatusEvaporatorFanSpeed | 1.3.6.1.4.1.318.1.1.13.4.5.2.1.22 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The unit average evaporator fan speed in tenths of percent. | |||||||||||||||||||||
| SairIRG2RDT2StatusInputState | 1.3.6.1.4.1.318.1.1.13.4.5.2.1.23 | AirIRG2RDType2IOState | RO | mandatory | |||||||||||||||||
scalar · AirIRG2RDType2IOState · read-only · mandatory The state of the input contact. | |||||||||||||||||||||
| SairIRG2RDT2StatusOutputState | 1.3.6.1.4.1.318.1.1.13.4.5.2.1.24 | AirIRG2RDType2IOState | RO | mandatory | |||||||||||||||||
scalar · AirIRG2RDType2IOState · read-only · mandatory The state of the output relay. | |||||||||||||||||||||
| SairIRG2RDT2StatusOHEInputState | 1.3.6.1.4.1.318.1.1.13.4.5.2.1.25 | AirIRG2RDType2IOState | RO | mandatory | |||||||||||||||||
scalar · AirIRG2RDType2IOState · read-only · mandatory The state of the outside heat exchanger(OHE) input contact. | |||||||||||||||||||||
| SairIRG2RDT2StatusOHEOutputState | 1.3.6.1.4.1.318.1.1.13.4.5.2.1.26 | AirIRG2RDType2IOState | RO | mandatory | |||||||||||||||||
scalar · AirIRG2RDType2IOState · read-only · mandatory The state of the outside heat exchanger(OHE) output relay. | |||||||||||||||||||||
| SairIRG2RDT2StatusCompressor | 1.3.6.1.4.1.318.1.1.13.4.5.2.1.27 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The state (off/on) of the compressor.
| |||||||||||||||||||||
| SairIRG2RDT2StatusFluidValvePos | 1.3.6.1.4.1.318.1.1.13.4.5.2.1.28 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The position of the fluid valve in percent. This OID is only valid when airIRG2RDT2ConfigUnitType indicates fluidCooled(1). | |||||||||||||||||||||
| SairIRG2RDT2StatusHotGasBypassValvePos | 1.3.6.1.4.1.318.1.1.13.4.5.2.1.29 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The position of the hot gas bypass valve in hundredths of percent. | |||||||||||||||||||||
| SairIRG2RDT2StatusLeakSensor | 1.3.6.1.4.1.318.1.1.13.4.5.2.1.30 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The state (no-leak/leak) of the leak sensor.
| |||||||||||||||||||||
| NairIRG2RDT2RunHours | 1.3.6.1.4.1.318.1.1.13.4.5.2.2 | ||||||||||||||||||||
| SairIRG2RDT2RunHoursAirFilter | 1.3.6.1.4.1.318.1.1.13.4.5.2.2.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit air filter run hours. | |||||||||||||||||||||
| SairIRG2RDT2RunHoursCondensatePump | 1.3.6.1.4.1.318.1.1.13.4.5.2.2.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit condensate pump run hours. | |||||||||||||||||||||
| SairIRG2RDT2RunHoursCompressor | 1.3.6.1.4.1.318.1.1.13.4.5.2.2.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit compressor run hours. | |||||||||||||||||||||
| SairIRG2RDT2RunHoursFanPSTableSize | 1.3.6.1.4.1.318.1.1.13.4.5.2.2.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the run hour fan power supply table (airIRG2RDT2RunHoursFanPSTable). | |||||||||||||||||||||
| TairIRG2RDT2RunHoursFanPSTable | 1.3.6.1.4.1.318.1.1.13.4.5.2.2.5 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting run hour information from each power supply. | |||||||||||||||||||||
| RairIRG2RDT2RunHoursFanPSEntry | 1.3.6.1.4.1.318.1.1.13.4.5.2.2.5.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The run hours fan power supply table entry. | |||||||||||||||||||||
| CairIRG2RDT2RunHoursFanPSIndex | 1.3.6.1.4.1.318.1.1.13.4.5.2.2.5.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Index of run hours fan power supply table. | |||||||||||||||||||||
| CairIRG2RDT2RunHoursFanPSHours | 1.3.6.1.4.1.318.1.1.13.4.5.2.2.5.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Fan power supply run time in hours. | |||||||||||||||||||||
| CairIRG2RDT2RunHoursFanPSPosition | 1.3.6.1.4.1.318.1.1.13.4.5.2.2.5.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Position of fan power supply within the unit.
| |||||||||||||||||||||
| SairIRG2RDT2RunHoursEvapFanTableSize | 1.3.6.1.4.1.318.1.1.13.4.5.2.2.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the run hour evaporator fan table (airIRG2RDT2RunHoursEvapFanTable). | |||||||||||||||||||||
| TairIRG2RDT2RunHoursEvapFanTable | 1.3.6.1.4.1.318.1.1.13.4.5.2.2.7 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting information from each evaporator fan run hour in the system. | |||||||||||||||||||||
| RairIRG2RDT2RunHoursEvapFanEntry | 1.3.6.1.4.1.318.1.1.13.4.5.2.2.7.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory Allows for getting information from each evaporator fan run hour in the system. | |||||||||||||||||||||
| CairIRG2RDT2RunHoursEvapFanIndex | 1.3.6.1.4.1.318.1.1.13.4.5.2.2.7.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Index of run hours evaporator fan table. | |||||||||||||||||||||
| CairIRG2RDT2RunHoursEvapFanHours | 1.3.6.1.4.1.318.1.1.13.4.5.2.2.7.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Evaporator fan run time in hours. | |||||||||||||||||||||
| SairIRG2RDT2RunHoursUnit | 1.3.6.1.4.1.318.1.1.13.4.5.2.2.8 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit run time in hours. | |||||||||||||||||||||
| NairIRG2RDT2ServiceIntervals | 1.3.6.1.4.1.318.1.1.13.4.5.2.3 | ||||||||||||||||||||
| SairIRG2RDT2ServiceIntervalsAirFilter | 1.3.6.1.4.1.318.1.1.13.4.5.2.3.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Air filter service interval in weeks. | |||||||||||||||||||||
| SairIRG2RDT2ServiceIntervalsAirFilterAlarm | 1.3.6.1.4.1.318.1.1.13.4.5.2.3.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The air filter service interval alarm enable/disable.
| |||||||||||||||||||||
| NairIRG2RDT2Thresholds | 1.3.6.1.4.1.318.1.1.13.4.5.2.4 | ||||||||||||||||||||
| SairIRG2RDT2ThresholdsRackInletHighTempUS | 1.3.6.1.4.1.318.1.1.13.4.5.2.4.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Unit rack inlet air high temperature threshold in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRG2RDT2ThresholdsRackInletHighTempMetric | 1.3.6.1.4.1.318.1.1.13.4.5.2.4.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Unit rack inlet air high temperature threshold in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRG2RDT2ThresholdsSupplyAirHighTempUS | 1.3.6.1.4.1.318.1.1.13.4.5.2.4.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Unit supply air high temperature threshold in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRG2RDT2ThresholdsSupplyAirHighTempMetric | 1.3.6.1.4.1.318.1.1.13.4.5.2.4.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Unit supply air high temperature threshold in tenths of degrees Celsius. | |||||||||||||||||||||
| SairIRG2RDT2ThresholdsReturnAirHighTempUS | 1.3.6.1.4.1.318.1.1.13.4.5.2.4.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Unit return air high temperature threshold in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SairIRG2RDT2ThresholdsReturnAirHighTempMetric | 1.3.6.1.4.1.318.1.1.13.4.5.2.4.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Unit return air high temperature threshold in tenths of degrees Celsius. | |||||||||||||||||||||
| NairIRG2RDT2Setpoints | 1.3.6.1.4.1.318.1.1.13.4.5.2.5 | ||||||||||||||||||||
| NairIRG2RDT2Config | 1.3.6.1.4.1.318.1.1.13.4.5.2.6 | ||||||||||||||||||||
| SairIRG2RDT2ConfigUnitType | 1.3.6.1.4.1.318.1.1.13.4.5.2.6.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The type of the unit.
| |||||||||||||||||||||
| SairIRG2RDT2ConfigStartupDelay | 1.3.6.1.4.1.318.1.1.13.4.5.2.6.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The startup delay in seconds. | |||||||||||||||||||||
| SairIRG2RDT2ConfigIdleOnLeakDetect | 1.3.6.1.4.1.318.1.1.13.4.5.2.6.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The idle on leak options setting.
| |||||||||||||||||||||
| SairIRG2RDT2ConfigInputNormalState | 1.3.6.1.4.1.318.1.1.13.4.5.2.6.4 | AirIRG2RDType2IOState | RW | mandatory | |||||||||||||||||
scalar · AirIRG2RDType2IOState · read-write · mandatory The normal state of the input contact. | |||||||||||||||||||||
| SairIRG2RDT2ConfigOutputNormalState | 1.3.6.1.4.1.318.1.1.13.4.5.2.6.5 | AirIRG2RDType2IOState | RW | mandatory | |||||||||||||||||
scalar · AirIRG2RDType2IOState · read-write · mandatory The normal state of the output relay. | |||||||||||||||||||||
| SairIRG2RDT2ConfigOutputSource | 1.3.6.1.4.1.318.1.1.13.4.5.2.6.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The source of output relay change.
| |||||||||||||||||||||
| SairIRG2RDT2ConfigOHEInputNormalState | 1.3.6.1.4.1.318.1.1.13.4.5.2.6.7 | AirIRG2RDType2IOState | RW | mandatory | |||||||||||||||||
scalar · AirIRG2RDType2IOState · read-write · mandatory The normal state of the outside heat exchanger(OHE) input relay. | |||||||||||||||||||||
| SairIRG2RDT2ConfigUnitRoleOverride | 1.3.6.1.4.1.318.1.1.13.4.5.2.6.8 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory When this OID value is (1) automatic, the system determines which units are used as primary units and which units are used as backups. When this OID value is (2) forcedOn, the connected unit is set as a primary unit.
| |||||||||||||||||||||
| SairIRG2RDT2ConfigUnitIdleOnCoolFail | 1.3.6.1.4.1.318.1.1.13.4.5.2.6.9 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory When this OID value is (2) yes, the unit idles if it detects that it is blowing warm air into the cold aisle. The unit will attempt to restart at 5 minute intervals.
| |||||||||||||||||||||
| NairIRG2SC | 1.3.6.1.4.1.318.1.1.13.4.6 | ||||||||||||||||||||
| NairIRG2RA | 1.3.6.1.4.1.318.1.1.13.4.7 | ||||||||||||||||||||
| NairInRoom | 1.3.6.1.4.1.318.1.1.13.5 | ||||||||||||||||||||
| NairIRmIdent | 1.3.6.1.4.1.318.1.1.13.5.1 | ||||||||||||||||||||
| SairIRmIdentName | 1.3.6.1.4.1.318.1.1.13.5.1.1 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory A character string identifying the unit name. | |||||||||||||||||||||
| SairIRmIdentLocation | 1.3.6.1.4.1.318.1.1.13.5.1.2 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory A character string identifying the unit location. | |||||||||||||||||||||
| SairIRmIdentModelNumber | 1.3.6.1.4.1.318.1.1.13.5.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the unit model number. | |||||||||||||||||||||
| SairIRmIdentSerialNumber | 1.3.6.1.4.1.318.1.1.13.5.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the unit serial number. | |||||||||||||||||||||
| SairIRmIdentFirmwareRevision | 1.3.6.1.4.1.318.1.1.13.5.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the unit firmware version. | |||||||||||||||||||||
| SairIRmIdentHardwareRevision | 1.3.6.1.4.1.318.1.1.13.5.1.6 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the unit controller hardware revision. | |||||||||||||||||||||
| SairIRmIdentManufactureDate | 1.3.6.1.4.1.318.1.1.13.5.1.7 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the unit manufacture date. | |||||||||||||||||||||
| SairIRmIdentSysOID | 1.3.6.1.4.1.318.1.1.13.5.1.8 | OBJECT IDENTIFIER | RO | mandatory | |||||||||||||||||
scalar · OBJECT IDENTIFIER · read-only · mandatory This OID contains an OID path to the device's top level data. | |||||||||||||||||||||
| NairIRmAlarms | 1.3.6.1.4.1.318.1.1.13.5.2 | ||||||||||||||||||||
| SairIRmAlarmsTableSize | 1.3.6.1.4.1.318.1.1.13.5.2.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of active alarms in the airIRG2AlarmsTable. | |||||||||||||||||||||
| TairIRmAlarmsTable | 1.3.6.1.4.1.318.1.1.13.5.2.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Table of active alarms for the device. | |||||||||||||||||||||
| RairIRmAlarmsEntry | 1.3.6.1.4.1.318.1.1.13.5.2.2.1 | NA | mandatory | ||||||||||||||||||
| CairIRmAlarmsIndex | 1.3.6.1.4.1.318.1.1.13.5.2.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Alarm index. | |||||||||||||||||||||
| CairIRmAlarmsEventCode | 1.3.6.1.4.1.318.1.1.13.5.2.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Code for the alarm. | |||||||||||||||||||||
| CairIRmAlarmsDescription | 1.3.6.1.4.1.318.1.1.13.5.2.2.1.3 | DisplayString (SIZE (0..64)) | RO | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..64)) · read-only · mandatory Description of the alarm. | |||||||||||||||||||||
| NairIRmPerimeter | 1.3.6.1.4.1.318.1.1.13.5.3 | ||||||||||||||||||||
| NairIRmPmCommon1 | 1.3.6.1.4.1.318.1.1.13.5.3.2 | ||||||||||||||||||||
| SairIRmPmUnitType | 1.3.6.1.4.1.318.1.1.13.5.3.2.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit type (1).
| |||||||||||||||||||||
| SairIRmPmSwVersion | 1.3.6.1.4.1.318.1.1.13.5.3.2.3 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory Software version (3). | |||||||||||||||||||||
| SairIRmPmBusAddress | 1.3.6.1.4.1.318.1.1.13.5.3.2.5 | INTEGER (0..65535) | RO | mandatory | |||||||||||||||||
scalar · INTEGER (0..65535) · read-only · mandatory Bus addresss of unit (5). | |||||||||||||||||||||
| SairIRmPmControllerType | 1.3.6.1.4.1.318.1.1.13.5.3.2.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Controller type (7).
| |||||||||||||||||||||
| SairIRmPmGeneralError | 1.3.6.1.4.1.318.1.1.13.5.3.2.8 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory General Error (8) | |||||||||||||||||||||
| SairIRmPmErrorOnBus | 1.3.6.1.4.1.318.1.1.13.5.3.2.9 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Error On Bus (9) | |||||||||||||||||||||
| NairIRmPmCommon2 | 1.3.6.1.4.1.318.1.1.13.5.3.3 | ||||||||||||||||||||
| SairIRmPmPCStop | 1.3.6.1.4.1.318.1.1.13.5.3.3.1 | AirIRmStopState | RO | mandatory | |||||||||||||||||
scalar · AirIRmStopState · read-only · mandatory PC-STOP (1000) | |||||||||||||||||||||
| SairIRmPmRemoteStop | 1.3.6.1.4.1.318.1.1.13.5.3.3.2 | AirIRmStopState | RO | mandatory | |||||||||||||||||
scalar · AirIRmStopState · read-only · mandatory Remote Stop (1001) | |||||||||||||||||||||
| SairIRmPmLocalStop | 1.3.6.1.4.1.318.1.1.13.5.3.3.3 | AirIRmStopState | RO | mandatory | |||||||||||||||||
scalar · AirIRmStopState · read-only · mandatory Local Stop (1002) | |||||||||||||||||||||
| SairIRmPmTimerStop | 1.3.6.1.4.1.318.1.1.13.5.3.3.4 | AirIRmStopState | RO | mandatory | |||||||||||||||||
scalar · AirIRmStopState · read-only · mandatory Timer Stop (1003) | |||||||||||||||||||||
| SairIRmPmSeqStop | 1.3.6.1.4.1.318.1.1.13.5.3.3.5 | AirIRmStopState | RO | mandatory | |||||||||||||||||
scalar · AirIRmStopState · read-only · mandatory Seq. Stop (1004) | |||||||||||||||||||||
| SairIRmPmRemoteUPS | 1.3.6.1.4.1.318.1.1.13.5.3.3.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Remote UPS (1006)
| |||||||||||||||||||||
| SairIRmPmLocalUPS | 1.3.6.1.4.1.318.1.1.13.5.3.3.8 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Local UPS (1007) | |||||||||||||||||||||
| SairIRmPmCommonAlarm | 1.3.6.1.4.1.318.1.1.13.5.3.3.11 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Common alarm (1010). | |||||||||||||||||||||
| SairIRmPmResetAllAlarms | 1.3.6.1.4.1.318.1.1.13.5.3.3.12 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Reset all alarms control (1011).
| |||||||||||||||||||||
| SairIRmPmUnitOnOff | 1.3.6.1.4.1.318.1.1.13.5.3.3.14 | AirIRmControlState | RO | mandatory | |||||||||||||||||
scalar · AirIRmControlState · read-only · mandatory Unit running state (1013). | |||||||||||||||||||||
| SairIRmPmMaintenance | 1.3.6.1.4.1.318.1.1.13.5.3.3.15 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Maintenance necessary state (1014).
| |||||||||||||||||||||
| SairIRmPmUnitTemperatureScale | 1.3.6.1.4.1.318.1.1.13.5.3.3.23 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Current Unit Temperature Scale (1022).
| |||||||||||||||||||||
| SairIRmPmUnitWinterMode | 1.3.6.1.4.1.318.1.1.13.5.3.3.24 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Winter or summer configuration mode (1023).
| |||||||||||||||||||||
| SairIRmPmDayNightMode | 1.3.6.1.4.1.318.1.1.13.5.3.3.25 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Day or night configuration mode (1024).
| |||||||||||||||||||||
| NairIRmPmCommon3 | 1.3.6.1.4.1.318.1.1.13.5.3.4 | ||||||||||||||||||||
| SairIRmPmLastMaintenanceYear | 1.3.6.1.4.1.318.1.1.13.5.3.4.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Last maintenance year (1160). | |||||||||||||||||||||
| SairIRmPmLastMaintenanceMonth | 1.3.6.1.4.1.318.1.1.13.5.3.4.2 | INTEGER (1..12) | RO | mandatory | |||||||||||||||||
scalar · INTEGER (1..12) · read-only · mandatory Last maintenance month (1161). | |||||||||||||||||||||
| SairIRmPmLastMaintenanceDay | 1.3.6.1.4.1.318.1.1.13.5.3.4.3 | INTEGER (1..31) | RO | mandatory | |||||||||||||||||
scalar · INTEGER (1..31) · read-only · mandatory Last maintenance day (1162). | |||||||||||||||||||||
| SairIRmPmUnitMaintenanceInterval | 1.3.6.1.4.1.318.1.1.13.5.3.4.4 | INTEGER (1..255) | RO | mandatory | |||||||||||||||||
scalar · INTEGER (1..255) · read-only · mandatory Unit maintenance interval in months (1163). | |||||||||||||||||||||
| SairIRmPmRuntimeUnit | 1.3.6.1.4.1.318.1.1.13.5.3.4.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Runtime unit in hours (1164). | |||||||||||||||||||||
| SairIRmPmStoptimeUnit | 1.3.6.1.4.1.318.1.1.13.5.3.4.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit stoptime in hours (1165) | |||||||||||||||||||||
| SairIRmPmRuntimeCooling | 1.3.6.1.4.1.318.1.1.13.5.3.4.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Cooling runtime in hours (1166) | |||||||||||||||||||||
| SairIRmPmRuntimeHeating | 1.3.6.1.4.1.318.1.1.13.5.3.4.8 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Heating runtime in hours (1167) | |||||||||||||||||||||
| SairIRmPmRuntimeHumidification | 1.3.6.1.4.1.318.1.1.13.5.3.4.9 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Humidification runtime in hours (1168) | |||||||||||||||||||||
| SairIRmPmRuntimeDehumidification | 1.3.6.1.4.1.318.1.1.13.5.3.4.10 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Dehumidification runtime in hours (1169) | |||||||||||||||||||||
| NairIRmPmUnitTemperature | 1.3.6.1.4.1.318.1.1.13.5.3.4.11 | ||||||||||||||||||||
| SairIRmPmUnitTemperatureC | 1.3.6.1.4.1.318.1.1.13.5.3.4.11.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit temperature in tenths of degrees Celsius (1170). | |||||||||||||||||||||
| SairIRmPmUnitTemperatureF | 1.3.6.1.4.1.318.1.1.13.5.3.4.11.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit temperature in tenths of degrees Fahrenheit (1170). | |||||||||||||||||||||
| SairIRmPmUnitHumidity | 1.3.6.1.4.1.318.1.1.13.5.3.4.12 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit humidity in tenths of %RH (1171). | |||||||||||||||||||||
| NairIRmPmSetpointTemperatureDay | 1.3.6.1.4.1.318.1.1.13.5.3.4.14 | ||||||||||||||||||||
| SairIRmPmSetpointTemperatureDayC | 1.3.6.1.4.1.318.1.1.13.5.3.4.14.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Setpoint daytime temperature in tenths of degrees Celsius (1173). | |||||||||||||||||||||
| SairIRmPmSetpointTemperatureDayF | 1.3.6.1.4.1.318.1.1.13.5.3.4.14.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Setpoint daytime temperature in tenths of degrees Fahrenheit (1173). | |||||||||||||||||||||
| NairIRmPmSetpointTemperatureNight | 1.3.6.1.4.1.318.1.1.13.5.3.4.15 | ||||||||||||||||||||
| SairIRmPmSetpointTemperatureNightC | 1.3.6.1.4.1.318.1.1.13.5.3.4.15.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Setpoint nighttime temperature in tenths of degrees Celsius (1174). | |||||||||||||||||||||
| SairIRmPmSetpointTemperatureNightF | 1.3.6.1.4.1.318.1.1.13.5.3.4.15.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Setpoint nighttime temperature in tenths of degrees Fahrenheit (1174). | |||||||||||||||||||||
| SairIRmPmSetpointHumidity | 1.3.6.1.4.1.318.1.1.13.5.3.4.17 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Setpoint humidity in tenths of %RH (1176). | |||||||||||||||||||||
| SairIRmPmUnitControlType | 1.3.6.1.4.1.318.1.1.13.5.3.4.24 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Current unit control type (1183).
| |||||||||||||||||||||
| NairIRmPmWinterModeStartTemp | 1.3.6.1.4.1.318.1.1.13.5.3.4.29 | ||||||||||||||||||||
| SairIRmPmWinterModeStartTempC | 1.3.6.1.4.1.318.1.1.13.5.3.4.29.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Winter mode start temperature in tenths of degrees Celsius (1188). | |||||||||||||||||||||
| SairIRmPmWinterModeStartTempF | 1.3.6.1.4.1.318.1.1.13.5.3.4.29.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Winter mode start temperature in tenths of degrees Fahrenheit (1188). | |||||||||||||||||||||
| NairIRmPmWinterModeHysteresis | 1.3.6.1.4.1.318.1.1.13.5.3.4.30 | ||||||||||||||||||||
| SairIRmPmWinterModeHysteresisK | 1.3.6.1.4.1.318.1.1.13.5.3.4.30.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Winter mode hysteresis in tenths of Kelvins (1189) | |||||||||||||||||||||
| SairIRmPmWinterModeHysteresisF | 1.3.6.1.4.1.318.1.1.13.5.3.4.30.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Winter mode hysteresis in tenths of degrees Fahrenheit (1189) | |||||||||||||||||||||
| NairIRmPmWaterTemperature | 1.3.6.1.4.1.318.1.1.13.5.3.4.32 | ||||||||||||||||||||
| SairIRmPmWaterTemperatureC | 1.3.6.1.4.1.318.1.1.13.5.3.4.32.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Water temperature in tenths of degrees Celsius (1191). | |||||||||||||||||||||
| SairIRmPmWaterTemperatureF | 1.3.6.1.4.1.318.1.1.13.5.3.4.32.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Water temperature in tenths of degrees Fahrenheit (1191). | |||||||||||||||||||||
| NairIRmPmReturnAirTemperature | 1.3.6.1.4.1.318.1.1.13.5.3.4.33 | ||||||||||||||||||||
| SairIRmPmReturnAirTemperatureC | 1.3.6.1.4.1.318.1.1.13.5.3.4.33.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Return air temperature in tenths of degrees Celsius (1192). | |||||||||||||||||||||
| SairIRmPmReturnAirTemperatureF | 1.3.6.1.4.1.318.1.1.13.5.3.4.33.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Return air temperature in tenths of degrees Fahrenheit (1192). | |||||||||||||||||||||
| NairIRmPmSupplyAirTemperature | 1.3.6.1.4.1.318.1.1.13.5.3.4.34 | ||||||||||||||||||||
| SairIRmPmSupplyAirTemperatureC | 1.3.6.1.4.1.318.1.1.13.5.3.4.34.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Supply air temperature in tenths of degrees Celsius (1193). | |||||||||||||||||||||
| SairIRmPmSupplyAirTemperatureF | 1.3.6.1.4.1.318.1.1.13.5.3.4.34.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Supply air temperature in tenths of degrees Fahrenheit (1193). | |||||||||||||||||||||
| SairIRmPmReturnAirHumidity | 1.3.6.1.4.1.318.1.1.13.5.3.4.35 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Return air humidity in tenths of %RH (1194). | |||||||||||||||||||||
| SairIRmPmSupplyAirHumidity | 1.3.6.1.4.1.318.1.1.13.5.3.4.36 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Supply air humidity in tenths of %RH (1195). | |||||||||||||||||||||
| NairIRmPmOutsideAirTemperature | 1.3.6.1.4.1.318.1.1.13.5.3.4.37 | ||||||||||||||||||||
| SairIRmPmOutsideAirTemperatureC | 1.3.6.1.4.1.318.1.1.13.5.3.4.37.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Outside air temperature in tenths of degrees Celsius (1196) | |||||||||||||||||||||
| SairIRmPmOutsideAirTemperatureF | 1.3.6.1.4.1.318.1.1.13.5.3.4.37.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Outside air temperature in tenths of degrees Fahrenheit (1196) | |||||||||||||||||||||
| SairIRmPmOutsideAirHumidity | 1.3.6.1.4.1.318.1.1.13.5.3.4.38 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Outside air humidity in tenths of percent relative humidity (1197) | |||||||||||||||||||||
| SairIRmPmCoolingPriority | 1.3.6.1.4.1.318.1.1.13.5.3.4.39 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Cooling priority (1198).
| |||||||||||||||||||||
| NairIRmPmWaterTemperature2 | 1.3.6.1.4.1.318.1.1.13.5.3.4.43 | ||||||||||||||||||||
| SairIRmPmWaterTemperature2C | 1.3.6.1.4.1.318.1.1.13.5.3.4.43.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Water temperature 2 in tenths of degrees Celsius (1202). | |||||||||||||||||||||
| SairIRmPmWaterTemperature2F | 1.3.6.1.4.1.318.1.1.13.5.3.4.43.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Water temperature 2 in tenths of degrees Fahrenheit (1202). | |||||||||||||||||||||
| SairIRmPmRuntimeFreeCooling | 1.3.6.1.4.1.318.1.1.13.5.3.4.44 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Freecooling runtime in hours (1203) | |||||||||||||||||||||
| SairIRmPmRuntimeMixedModeFreeCooling | 1.3.6.1.4.1.318.1.1.13.5.3.4.45 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Mixed mode freecooling runtime in hours (1203) | |||||||||||||||||||||
| NairIRmPmCommon4 | 1.3.6.1.4.1.318.1.1.13.5.3.5 | ||||||||||||||||||||
| SairIRmPmNumberOfCompressors | 1.3.6.1.4.1.318.1.1.13.5.3.5.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Number of compressors (1761) | |||||||||||||||||||||
| SairIRmPmNumberOfSuctionValves | 1.3.6.1.4.1.318.1.1.13.5.3.5.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Number of suction valves (1762) | |||||||||||||||||||||
| SairIRmPmNumberOfDryCoolers | 1.3.6.1.4.1.318.1.1.13.5.3.5.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Number of drycoolers (1763) | |||||||||||||||||||||
| SairIRmPmNumberOfPumps | 1.3.6.1.4.1.318.1.1.13.5.3.5.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Number of pumps (1764) | |||||||||||||||||||||
| SairIRmPmNumberOfElectricHeaters | 1.3.6.1.4.1.318.1.1.13.5.3.5.8 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Number of electric heaters (1765) | |||||||||||||||||||||
| SairIRmPmNumberOfHumidifiers | 1.3.6.1.4.1.318.1.1.13.5.3.5.9 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Number of humidifiers (1766) | |||||||||||||||||||||
| SairIRmPmNumberOfFans | 1.3.6.1.4.1.318.1.1.13.5.3.5.10 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Number of fans (1767) | |||||||||||||||||||||
| SairIRmPmNumberOfLouvers | 1.3.6.1.4.1.318.1.1.13.5.3.5.11 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Number of louvers (1768) | |||||||||||||||||||||
| SairIRmPmNumberOfSensors | 1.3.6.1.4.1.318.1.1.13.5.3.5.12 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Number of sensors (1769) | |||||||||||||||||||||
| SairIRmPmNumberOfExternalAlarmInputs | 1.3.6.1.4.1.318.1.1.13.5.3.5.13 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Number of external alarm inputs (1770) | |||||||||||||||||||||
| SairIRmPmNumberOfGECWValves | 1.3.6.1.4.1.318.1.1.13.5.3.5.14 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Number of GE/CW valves (1771) | |||||||||||||||||||||
| SairIRmPmNumberOfHotGasReheat | 1.3.6.1.4.1.318.1.1.13.5.3.5.15 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Number of hot gas reheaters (1772) | |||||||||||||||||||||
| SairIRmPmNumberOfPWWReheat | 1.3.6.1.4.1.318.1.1.13.5.3.5.16 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Number of PWW reheaters (1773) | |||||||||||||||||||||
| SairIRmPmNumberOfDehumidifiers | 1.3.6.1.4.1.318.1.1.13.5.3.5.17 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Number of dehumidifiers (1774) | |||||||||||||||||||||
| NairIRmPmCommon5 | 1.3.6.1.4.1.318.1.1.13.5.3.6 | ||||||||||||||||||||
| NairIRmPmUnitEvaporationTemperature1 | 1.3.6.1.4.1.318.1.1.13.5.3.6.1 | ||||||||||||||||||||
| SairIRmPmUnitEvaporationTemperature1C | 1.3.6.1.4.1.318.1.1.13.5.3.6.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit evaporation temperature 1 in tenths of degrees Celsius (2232) | |||||||||||||||||||||
| SairIRmPmUnitEvaporationTemperature1F | 1.3.6.1.4.1.318.1.1.13.5.3.6.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit evaporation temperature 1 in tenths of degrees Fahrenheit (2232) | |||||||||||||||||||||
| SairIRmPmUnitEvaporationPressure1 | 1.3.6.1.4.1.318.1.1.13.5.3.6.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit evaporation pressure 1 in tenths of Bars (2233) | |||||||||||||||||||||
| NairIRmPmUnitCondensationTemperature1 | 1.3.6.1.4.1.318.1.1.13.5.3.6.3 | ||||||||||||||||||||
| SairIRmPmUnitCondensationTemperature1C | 1.3.6.1.4.1.318.1.1.13.5.3.6.3.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit condensation temperature 1 in tenths of degrees Celsius (2234) | |||||||||||||||||||||
| SairIRmPmUnitCondensationTemperature1F | 1.3.6.1.4.1.318.1.1.13.5.3.6.3.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit condensation temperature 1 in tenths of degrees Fahrenheit (2234) | |||||||||||||||||||||
| SairIRmPmUnitCondensationPressure1 | 1.3.6.1.4.1.318.1.1.13.5.3.6.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit condensation pressure 1 in tenths of Bars (2235) | |||||||||||||||||||||
| NairIRmPmMaxLimitReturnAirTemperature | 1.3.6.1.4.1.318.1.1.13.5.3.6.8 | ||||||||||||||||||||
| SairIRmPmMaxLimitReturnAirTemperatureC | 1.3.6.1.4.1.318.1.1.13.5.3.6.8.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Maximum limit return air temperature in tenths of degrees Celsius (2239). | |||||||||||||||||||||
| SairIRmPmMaxLimitReturnAirTemperatureF | 1.3.6.1.4.1.318.1.1.13.5.3.6.8.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Maximum limit return air temperature in tenths of degrees Fahrenheit (2239). | |||||||||||||||||||||
| NairIRmPmMinLimitReturnAirTemperature | 1.3.6.1.4.1.318.1.1.13.5.3.6.9 | ||||||||||||||||||||
| SairIRmPmMinLimitReturnAirTemperatureC | 1.3.6.1.4.1.318.1.1.13.5.3.6.9.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Minimum limit return air temperature in tenths of degrees Celsius (2240). | |||||||||||||||||||||
| SairIRmPmMinLimitReturnAirTemperatureF | 1.3.6.1.4.1.318.1.1.13.5.3.6.9.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Minimum limit return air temperature in tenths of degrees Fahrenheit (2240). | |||||||||||||||||||||
| NairIRmPmMaxLimitSupplyAirTemperature | 1.3.6.1.4.1.318.1.1.13.5.3.6.10 | ||||||||||||||||||||
| SairIRmPmMaxLimitSupplyAirTemperatureC | 1.3.6.1.4.1.318.1.1.13.5.3.6.10.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Maximum limit supply air temperature in tenths of degrees Celsius (2241). | |||||||||||||||||||||
| SairIRmPmMaxLimitSupplyAirTemperatureF | 1.3.6.1.4.1.318.1.1.13.5.3.6.10.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Maximum limit supply air temperature in tenths of degrees Fahrenheit (2241). | |||||||||||||||||||||
| NairIRmPmMinLimitSupplyAirTemperature | 1.3.6.1.4.1.318.1.1.13.5.3.6.11 | ||||||||||||||||||||
| SairIRmPmMinLimitSupplyAirTemperatureC | 1.3.6.1.4.1.318.1.1.13.5.3.6.11.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Minimum limit supply air temperature in tenths of degrees Celsius (2242). | |||||||||||||||||||||
| SairIRmPmMinLimitSupplyAirTemperatureF | 1.3.6.1.4.1.318.1.1.13.5.3.6.11.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Minimum limit supply air temperature in tenths of degrees Fahrenheit (2242). | |||||||||||||||||||||
| NairIRmPmMaxLimitWaterTemperature | 1.3.6.1.4.1.318.1.1.13.5.3.6.12 | ||||||||||||||||||||
| SairIRmPmMaxLimitWaterTemperatureC | 1.3.6.1.4.1.318.1.1.13.5.3.6.12.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Maximum limit water temperature in tenths of degrees Celsius (2243). | |||||||||||||||||||||
| SairIRmPmMaxLimitWaterTemperatureF | 1.3.6.1.4.1.318.1.1.13.5.3.6.12.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Maximum limit water temperature in tenths of degrees Fahrenheit (2243). | |||||||||||||||||||||
| NairIRmPmMinLimitWaterTemperature | 1.3.6.1.4.1.318.1.1.13.5.3.6.13 | ||||||||||||||||||||
| SairIRmPmMinLimitWaterTemperatureC | 1.3.6.1.4.1.318.1.1.13.5.3.6.13.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Minimum limit water temperature in tenths of degrees Celsius (2244). | |||||||||||||||||||||
| SairIRmPmMinLimitWaterTemperatureF | 1.3.6.1.4.1.318.1.1.13.5.3.6.13.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Minimum limit water temperature in tenths of degrees Fahrenheit (2244). | |||||||||||||||||||||
| SairIRmPmMaxLimitReturnAirHumidity | 1.3.6.1.4.1.318.1.1.13.5.3.6.14 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Maximum limit return air humidity in tenths of %RH (2245). | |||||||||||||||||||||
| SairIRmPmMinLimitReturnAirHumidity | 1.3.6.1.4.1.318.1.1.13.5.3.6.15 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Minimum limit return air humidity in tenths of %RH (2246). | |||||||||||||||||||||
| SairIRmPmMaxLimitSupplyAirHumidity | 1.3.6.1.4.1.318.1.1.13.5.3.6.16 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Maximum limit supply air humidity in tenths of %RH (2247). | |||||||||||||||||||||
| SairIRmPmMinLimitSupplyAirHumidity | 1.3.6.1.4.1.318.1.1.13.5.3.6.17 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Minimum limit supply air humidity in tenths of %RH (2248). | |||||||||||||||||||||
| SairIRmPmLowPressureWinterDelay | 1.3.6.1.4.1.318.1.1.13.5.3.6.18 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Winter mode low pressure delay in seconds (2249) | |||||||||||||||||||||
| SairIRmPmUnitCondensationPressure2 | 1.3.6.1.4.1.318.1.1.13.5.3.6.19 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit condensation pressure 2 in tenths of Bars (2250) | |||||||||||||||||||||
| SairIRmPmUnitOverloadSwitch | 1.3.6.1.4.1.318.1.1.13.5.3.6.20 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit overload switch setting in tenths of Kelvins (2251) | |||||||||||||||||||||
| NairIRmPmUnitCondensationTemperature2 | 1.3.6.1.4.1.318.1.1.13.5.3.6.41 | ||||||||||||||||||||
| SairIRmPmUnitCondensationTemperature2C | 1.3.6.1.4.1.318.1.1.13.5.3.6.41.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit condensation temperature 2 in tenths of degrees Celsius (2272) | |||||||||||||||||||||
| SairIRmPmUnitCondensationTemperature2F | 1.3.6.1.4.1.318.1.1.13.5.3.6.41.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit condensation temperature 2 in tenths of degrees Fahrenheit (2272) | |||||||||||||||||||||
| SairIRmPmUnitEvaporationPressure2 | 1.3.6.1.4.1.318.1.1.13.5.3.6.42 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit evaporation pressure 2 in tenths of Bars (2273) | |||||||||||||||||||||
| NairIRmPmUnitEvaporationTemperature2 | 1.3.6.1.4.1.318.1.1.13.5.3.6.43 | ||||||||||||||||||||
| SairIRmPmUnitEvaporationTemperature2C | 1.3.6.1.4.1.318.1.1.13.5.3.6.43.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit evaporation temperature 2 in tenths of degrees Celsius (2274) | |||||||||||||||||||||
| SairIRmPmUnitEvaporationTemperature2F | 1.3.6.1.4.1.318.1.1.13.5.3.6.43.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Unit evaporation temperature 2 in tenths of degrees Fahrenheit (2274) | |||||||||||||||||||||
| NairIRmPmCompressor1 | 1.3.6.1.4.1.318.1.1.13.5.3.7 | ||||||||||||||||||||
| SairIRmPmCmp1ManOperationActive | 1.3.6.1.4.1.318.1.1.13.5.3.7.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Compressor 1 manual operation active (4401)
| |||||||||||||||||||||
| SairIRmPmCmp1ManOperationState | 1.3.6.1.4.1.318.1.1.13.5.3.7.3 | AirIRmControlState | RO | mandatory | |||||||||||||||||
scalar · AirIRmControlState · read-only · mandatory Compressor 1 manual operation state (4402) | |||||||||||||||||||||
| SairIRmPmCmp1Running | 1.3.6.1.4.1.318.1.1.13.5.3.7.4 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Compressor 1 running (4403) | |||||||||||||||||||||
| NairIRmPmCmp1StartTempSummer | 1.3.6.1.4.1.318.1.1.13.5.3.7.17 | ||||||||||||||||||||
| SairIRmPmCmp1StartTempSummerK | 1.3.6.1.4.1.318.1.1.13.5.3.7.17.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Compressor 1 summer mode start temperature in tenths of Kelvins (4416) | |||||||||||||||||||||
| SairIRmPmCmp1StartTempSummerF | 1.3.6.1.4.1.318.1.1.13.5.3.7.17.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Compressor 1 summer mode start temperature in tenths of degrees Fahrenheit (4416) | |||||||||||||||||||||
| NairIRmPmCmp1HysteresisSummer | 1.3.6.1.4.1.318.1.1.13.5.3.7.18 | ||||||||||||||||||||
| SairIRmPmCmp1HysteresisSummerK | 1.3.6.1.4.1.318.1.1.13.5.3.7.18.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Compressor 1 summer mode hysteresis setting in tenths of Kelvins (4417) | |||||||||||||||||||||
| SairIRmPmCmp1HysteresisSummerF | 1.3.6.1.4.1.318.1.1.13.5.3.7.18.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Compressor 1 summer mode hysteresis setting in tenths of Fahrenheit (4417) | |||||||||||||||||||||
| NairIRmPmCmp1StartTempWinter | 1.3.6.1.4.1.318.1.1.13.5.3.7.19 | ||||||||||||||||||||
| SairIRmPmCmp1StartTempWinterK | 1.3.6.1.4.1.318.1.1.13.5.3.7.19.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Compressor 1 winter mode start temperature in tenths of Kelvins (4418) | |||||||||||||||||||||
| SairIRmPmCmp1StartTempWinterF | 1.3.6.1.4.1.318.1.1.13.5.3.7.19.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Compressor 1 winter mode start temperature in tenths of degrees Fahrenheit (4418) | |||||||||||||||||||||
| NairIRmPmCmp1HysteresisWinter | 1.3.6.1.4.1.318.1.1.13.5.3.7.20 | ||||||||||||||||||||
| SairIRmPmCmp1HysteresisWinterK | 1.3.6.1.4.1.318.1.1.13.5.3.7.20.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Compressor 1 Winter mode hysteresis setting in tenths of Kelvins (4419) | |||||||||||||||||||||
| SairIRmPmCmp1HysteresisWinterF | 1.3.6.1.4.1.318.1.1.13.5.3.7.20.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Compressor 1 Winter mode hysteresis setting in tenths of Fahrenheit (4419) | |||||||||||||||||||||
| SairIRmPmCmp1Runtime | 1.3.6.1.4.1.318.1.1.13.5.3.7.29 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Compressor 1 runtime in hours (4428) | |||||||||||||||||||||
| NairIRmPmCompressor2 | 1.3.6.1.4.1.318.1.1.13.5.3.8 | ||||||||||||||||||||
| SairIRmPmCmp2ManOperationActive | 1.3.6.1.4.1.318.1.1.13.5.3.8.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Compressor 2 manual operation active (4501)
| |||||||||||||||||||||
| SairIRmPmCmp2ManOperationState | 1.3.6.1.4.1.318.1.1.13.5.3.8.3 | AirIRmControlState | RO | mandatory | |||||||||||||||||
scalar · AirIRmControlState · read-only · mandatory Compressor 2 manual operation state (4502) | |||||||||||||||||||||
| SairIRmPmCmp2Running | 1.3.6.1.4.1.318.1.1.13.5.3.8.4 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Compressor 2 running (4503) | |||||||||||||||||||||
| NairIRmPmCmp2StartTempSummer | 1.3.6.1.4.1.318.1.1.13.5.3.8.17 | ||||||||||||||||||||
| SairIRmPmCmp2StartTempSummerK | 1.3.6.1.4.1.318.1.1.13.5.3.8.17.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Compressor 2 summer mode start temperature in tenths of Kelvins (4516) | |||||||||||||||||||||
| SairIRmPmCmp2StartTempSummerF | 1.3.6.1.4.1.318.1.1.13.5.3.8.17.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Compressor 2 summer mode start temperature in tenths of degrees Fahrenheit (4516) | |||||||||||||||||||||
| NairIRmPmCmp2HysteresisSummer | 1.3.6.1.4.1.318.1.1.13.5.3.8.18 | ||||||||||||||||||||
| SairIRmPmCmp2HysteresisSummerK | 1.3.6.1.4.1.318.1.1.13.5.3.8.18.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Compressor 2 summer mode hysteresis setting in tenths of Kelvins (4517) | |||||||||||||||||||||
| SairIRmPmCmp2HysteresisSummerF | 1.3.6.1.4.1.318.1.1.13.5.3.8.18.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Compressor 2 summer mode hysteresis setting in tenths of Fahrenheit (4517) | |||||||||||||||||||||
| NairIRmPmCmp2StartTempWinter | 1.3.6.1.4.1.318.1.1.13.5.3.8.19 | ||||||||||||||||||||
| SairIRmPmCmp2StartTempWinterK | 1.3.6.1.4.1.318.1.1.13.5.3.8.19.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Compressor 2 winter mode start temperature in tenths of Kelvins (4518) | |||||||||||||||||||||
| SairIRmPmCmp2StartTempWinterF | 1.3.6.1.4.1.318.1.1.13.5.3.8.19.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Compressor 2 winter mode start temperature in tenths of degrees Fahrenheit (4518) | |||||||||||||||||||||
| NairIRmPmCmp2HysteresisWinter | 1.3.6.1.4.1.318.1.1.13.5.3.8.20 | ||||||||||||||||||||
| SairIRmPmCmp2HysteresisWinterK | 1.3.6.1.4.1.318.1.1.13.5.3.8.20.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Compressor 2 Winter mode hysteresis setting in tenths of Kelvins (4519) | |||||||||||||||||||||
| SairIRmPmCmp2HysteresisWinterF | 1.3.6.1.4.1.318.1.1.13.5.3.8.20.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Compressor 2 Winter mode hysteresis setting in tenths of Fahrenheit (4519) | |||||||||||||||||||||
| SairIRmPmCmp2Runtime | 1.3.6.1.4.1.318.1.1.13.5.3.8.29 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Compressor 2 runtime in hours (4528) | |||||||||||||||||||||
| NairIRmPmSuctionValve1 | 1.3.6.1.4.1.318.1.1.13.5.3.9 | ||||||||||||||||||||
| NairIRmPmSuctionValve2 | 1.3.6.1.4.1.318.1.1.13.5.3.10 | ||||||||||||||||||||
| NairIRmPmEheating1 | 1.3.6.1.4.1.318.1.1.13.5.3.11 | ||||||||||||||||||||
| SairIRmPmEheating1ManOpEnable | 1.3.6.1.4.1.318.1.1.13.5.3.11.2 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Electric heater #1 manual operation enable (4801) | |||||||||||||||||||||
| SairIRmPmEheating1Running | 1.3.6.1.4.1.318.1.1.13.5.3.11.4 | AirIRmControlState | RO | mandatory | |||||||||||||||||
scalar · AirIRmControlState · read-only · mandatory Electric heater #1 running state (4803) | |||||||||||||||||||||
| SairIRmPmEheating1ManOpRunning | 1.3.6.1.4.1.318.1.1.13.5.3.11.5 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Electric heater #1 running in manual operation mode (4804) | |||||||||||||||||||||
| SairIRmPmEheating1Type | 1.3.6.1.4.1.318.1.1.13.5.3.11.9 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Electric heater #1 type (4808)
| |||||||||||||||||||||
| NairIRmPmEheating1StartTemperature | 1.3.6.1.4.1.318.1.1.13.5.3.11.10 | ||||||||||||||||||||
| SairIRmPmEheating1StartTemperatureK | 1.3.6.1.4.1.318.1.1.13.5.3.11.10.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Electric heater #1 start temperature in tenths of Kelvins (4809) | |||||||||||||||||||||
| SairIRmPmEheating1StartTemperatureF | 1.3.6.1.4.1.318.1.1.13.5.3.11.10.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Electric heater #1 start temperature in tenths of degrees Fahrenheit (4809) | |||||||||||||||||||||
| NairIRmPmEheating1Hysteresis | 1.3.6.1.4.1.318.1.1.13.5.3.11.11 | ||||||||||||||||||||
| SairIRmPmEheating1HysteresisK | 1.3.6.1.4.1.318.1.1.13.5.3.11.11.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Electric heater #1 hysteresis in tenths of Kelvins (4810) | |||||||||||||||||||||
| SairIRmPmEheating1HysteresisF | 1.3.6.1.4.1.318.1.1.13.5.3.11.11.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Electric heater #1 hysteresis in tenths of degrees Fahrenheit (4810) | |||||||||||||||||||||
| SairIRmPmEheating1Runtime | 1.3.6.1.4.1.318.1.1.13.5.3.11.17 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Electric heater #1 runtime in hours (4816) | |||||||||||||||||||||
| NairIRmPmEheating2 | 1.3.6.1.4.1.318.1.1.13.5.3.12 | ||||||||||||||||||||
| SairIRmPmEheating2ManOpEnable | 1.3.6.1.4.1.318.1.1.13.5.3.12.2 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Electric heater #2 manual operation enable (4901) | |||||||||||||||||||||
| SairIRmPmEheating2Running | 1.3.6.1.4.1.318.1.1.13.5.3.12.4 | AirIRmControlState | RO | mandatory | |||||||||||||||||
scalar · AirIRmControlState · read-only · mandatory Electric heater #2 running state (4903) | |||||||||||||||||||||
| SairIRmPmEheating2ManOpRunning | 1.3.6.1.4.1.318.1.1.13.5.3.12.5 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Electric heater #2 running in manual operation mode (4904) | |||||||||||||||||||||
| SairIRmPmEheating2Type | 1.3.6.1.4.1.318.1.1.13.5.3.12.9 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Electric heater #2 type (4908)
| |||||||||||||||||||||
| NairIRmPmEheating2StartTemperature | 1.3.6.1.4.1.318.1.1.13.5.3.12.10 | ||||||||||||||||||||
| SairIRmPmEheating2StartTemperatureK | 1.3.6.1.4.1.318.1.1.13.5.3.12.10.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Electric heater #2 start temperature in tenths of Kelvins (4909) | |||||||||||||||||||||
| SairIRmPmEheating2StartTemperatureF | 1.3.6.1.4.1.318.1.1.13.5.3.12.10.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Electric heater #2 start temperature in tenths of degrees Fahrenheit (4909) | |||||||||||||||||||||
| NairIRmPmEheating2Hysteresis | 1.3.6.1.4.1.318.1.1.13.5.3.12.11 | ||||||||||||||||||||
| SairIRmPmEheating2HysteresisK | 1.3.6.1.4.1.318.1.1.13.5.3.12.11.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Electric heater #2 hysteresis in tenths of Kelvins (4910) | |||||||||||||||||||||
| SairIRmPmEheating2HysteresisF | 1.3.6.1.4.1.318.1.1.13.5.3.12.11.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Electric heater #2 hysteresis in tenths of degrees Fahrenheit (4910) | |||||||||||||||||||||
| SairIRmPmEheating2Runtime | 1.3.6.1.4.1.318.1.1.13.5.3.12.17 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Electric heater #2 runtime in hours (4916) | |||||||||||||||||||||
| NairIRmPmEheating3 | 1.3.6.1.4.1.318.1.1.13.5.3.13 | ||||||||||||||||||||
| SairIRmPmEheating3ManOpEnable | 1.3.6.1.4.1.318.1.1.13.5.3.13.2 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Electric heater #3 manual operation enable (5001) | |||||||||||||||||||||
| SairIRmPmEheating3Running | 1.3.6.1.4.1.318.1.1.13.5.3.13.4 | AirIRmControlState | RO | mandatory | |||||||||||||||||
scalar · AirIRmControlState · read-only · mandatory Electric heater #3 running state (5003) | |||||||||||||||||||||
| SairIRmPmEheating3ManOpRunning | 1.3.6.1.4.1.318.1.1.13.5.3.13.5 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Electric heater #3 running in manual operation mode (5004) | |||||||||||||||||||||
| SairIRmPmEheating3Type | 1.3.6.1.4.1.318.1.1.13.5.3.13.9 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Electric heater #3 type (5008)
| |||||||||||||||||||||
| NairIRmPmEheating3StartTemperature | 1.3.6.1.4.1.318.1.1.13.5.3.13.10 | ||||||||||||||||||||
| SairIRmPmEheating3StartTemperatureK | 1.3.6.1.4.1.318.1.1.13.5.3.13.10.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Electric heater #3 start temperature in tenths of Kelvins (5009) | |||||||||||||||||||||
| SairIRmPmEheating3StartTemperatureF | 1.3.6.1.4.1.318.1.1.13.5.3.13.10.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Electric heater #3 start temperature in tenths of degrees Fahrenheit (5009) | |||||||||||||||||||||
| NairIRmPmEheating3Hysteresis | 1.3.6.1.4.1.318.1.1.13.5.3.13.11 | ||||||||||||||||||||
| SairIRmPmEheating3HysteresisK | 1.3.6.1.4.1.318.1.1.13.5.3.13.11.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Electric heater #3 hysteresis in tenths of Kelvins (5010) | |||||||||||||||||||||
| SairIRmPmEheating3HysteresisF | 1.3.6.1.4.1.318.1.1.13.5.3.13.11.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Electric heater #3 hysteresis in tenths of degrees Fahrenheit (5010) | |||||||||||||||||||||
| SairIRmPmEheating3Runtime | 1.3.6.1.4.1.318.1.1.13.5.3.13.17 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Electric heater #3 runtime in hours (5016) | |||||||||||||||||||||
| NairIRmPmEheating4 | 1.3.6.1.4.1.318.1.1.13.5.3.14 | ||||||||||||||||||||
| SairIRmPmEheating4ManOpEnable | 1.3.6.1.4.1.318.1.1.13.5.3.14.2 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Electric heater #4 manual operation enable (5101) | |||||||||||||||||||||
| SairIRmPmEheating4Running | 1.3.6.1.4.1.318.1.1.13.5.3.14.4 | AirIRmControlState | RO | mandatory | |||||||||||||||||
scalar · AirIRmControlState · read-only · mandatory Electric heater #4 running state (5103) | |||||||||||||||||||||
| SairIRmPmEheating4ManOpRunning | 1.3.6.1.4.1.318.1.1.13.5.3.14.5 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Electric heater #4 running in manual operation mode (5104) | |||||||||||||||||||||
| SairIRmPmEheating4Type | 1.3.6.1.4.1.318.1.1.13.5.3.14.9 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Electric heater #4 type (5108)
| |||||||||||||||||||||
| NairIRmPmEheating4StartTemperature | 1.3.6.1.4.1.318.1.1.13.5.3.14.10 | ||||||||||||||||||||
| SairIRmPmEheating4StartTemperatureK | 1.3.6.1.4.1.318.1.1.13.5.3.14.10.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Electric heater #4 start temperature in tenths of Kelvins (5109) | |||||||||||||||||||||
| SairIRmPmEheating4StartTemperatureF | 1.3.6.1.4.1.318.1.1.13.5.3.14.10.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Electric heater #4 start temperature in tenths of degrees Fahrenheit (5109) | |||||||||||||||||||||
| NairIRmPmEheating4Hysteresis | 1.3.6.1.4.1.318.1.1.13.5.3.14.11 | ||||||||||||||||||||
| SairIRmPmEheating4HysteresisK | 1.3.6.1.4.1.318.1.1.13.5.3.14.11.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Electric heater #4 hysteresis in tenths of Kelvins (5110) | |||||||||||||||||||||
| SairIRmPmEheating4HysteresisF | 1.3.6.1.4.1.318.1.1.13.5.3.14.11.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Electric heater #4 hysteresis in tenths of degrees Fahrenheit (5110) | |||||||||||||||||||||
| SairIRmPmEheating4Runtime | 1.3.6.1.4.1.318.1.1.13.5.3.14.17 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Electric heater #4 runtime in hours (5116) | |||||||||||||||||||||
| NairIRmPmGECWvalve | 1.3.6.1.4.1.318.1.1.13.5.3.15 | ||||||||||||||||||||
| SairIRmPmGECWvalveManOpEnable | 1.3.6.1.4.1.318.1.1.13.5.3.15.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory GE/CW valve manual operation enable (5201) | |||||||||||||||||||||
| NairIRmPmGECWvalveStartTemperature | 1.3.6.1.4.1.318.1.1.13.5.3.15.9 | ||||||||||||||||||||
| SairIRmPmGECWvalveStartTemperatureK | 1.3.6.1.4.1.318.1.1.13.5.3.15.9.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory GE/CW valve start temperature in tenths of Kelvins (5208) | |||||||||||||||||||||
| SairIRmPmGECWvalveStartTemperatureF | 1.3.6.1.4.1.318.1.1.13.5.3.15.9.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory GE/CW valve start temperature in tenths of degrees Fahrenheit (5208) | |||||||||||||||||||||
| NairIRmPmGECWvalveLinearRange | 1.3.6.1.4.1.318.1.1.13.5.3.15.10 | ||||||||||||||||||||
| SairIRmPmGECWvalveLinearRangeK | 1.3.6.1.4.1.318.1.1.13.5.3.15.10.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory GE/CW valve linear range in tenths of Kelvins (5209) | |||||||||||||||||||||
| SairIRmPmGECWvalveLinearRangeF | 1.3.6.1.4.1.318.1.1.13.5.3.15.10.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory GE/CW valve linear range in tenths of degrees Fahrenheit (5209) | |||||||||||||||||||||
| NairIRmPmGECWvalveGEOffTemp | 1.3.6.1.4.1.318.1.1.13.5.3.15.12 | ||||||||||||||||||||
| SairIRmPmGECWvalveGEOffTempC | 1.3.6.1.4.1.318.1.1.13.5.3.15.12.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory GE/CW valve GE off temperature in tenths of degrees Celsius (5211) | |||||||||||||||||||||
| SairIRmPmGECWvalveGEOffTempF | 1.3.6.1.4.1.318.1.1.13.5.3.15.12.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory GE/CW valve GE off temperature in tenths of degrees Fahrenheit (5211) | |||||||||||||||||||||
| SairIRmPmGECWvalveOpeningGrade | 1.3.6.1.4.1.318.1.1.13.5.3.15.15 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory GE/CW valve opening grade in percent (5214) | |||||||||||||||||||||
| SairIRmPmGECWvalveManOpOpeningGrade | 1.3.6.1.4.1.318.1.1.13.5.3.15.16 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory GE/CW valve manual operation opening grade in percent (5215) | |||||||||||||||||||||
| NairIRmPmGvalve | 1.3.6.1.4.1.318.1.1.13.5.3.16 | ||||||||||||||||||||
| SairIRmPmGvalveManOperationEnable | 1.3.6.1.4.1.318.1.1.13.5.3.16.2 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory G-valve manual operation enable (5301) | |||||||||||||||||||||
| SairIRmPmGvalvePreOpeningTime | 1.3.6.1.4.1.318.1.1.13.5.3.16.11 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory G-valve pre-opening time in seconds (5310) | |||||||||||||||||||||
| SairIRmPmGvalvePreOpeningGrade | 1.3.6.1.4.1.318.1.1.13.5.3.16.12 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory G-valve pre-opening grade in percent (5311) | |||||||||||||||||||||
| SairIRmPmGvalveOpeningGrade | 1.3.6.1.4.1.318.1.1.13.5.3.16.13 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory G-valve opening grade in percent (5312) | |||||||||||||||||||||
| SairIRmPmGvalveManOpOpeningGrade | 1.3.6.1.4.1.318.1.1.13.5.3.16.14 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory G-valve manual operation opening grade in percent (5313) | |||||||||||||||||||||
| NairIRmPmDrycooler1 | 1.3.6.1.4.1.318.1.1.13.5.3.17 | ||||||||||||||||||||
| SairIRmPmDrycooler1ManOpEnable | 1.3.6.1.4.1.318.1.1.13.5.3.17.2 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Drycooler 1 manual operation enable setting (5401) | |||||||||||||||||||||
| SairIRmPmDrycooler1Running | 1.3.6.1.4.1.318.1.1.13.5.3.17.3 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Drycooler 1 running (5402) | |||||||||||||||||||||
| SairIRmPmDrycooler1ManOpRunning | 1.3.6.1.4.1.318.1.1.13.5.3.17.5 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Drycooler 1 manual operation running (5404) | |||||||||||||||||||||
| NairIRmPmDrycooler1WinterStartTemp | 1.3.6.1.4.1.318.1.1.13.5.3.17.9 | ||||||||||||||||||||
| SairIRmPmDrycooler1WinterStartTempC | 1.3.6.1.4.1.318.1.1.13.5.3.17.9.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Drycooler 1 winter mode start temperature in tenths of degrees Celsius (5408) | |||||||||||||||||||||
| SairIRmPmDrycooler1WinterStartTempF | 1.3.6.1.4.1.318.1.1.13.5.3.17.9.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Drycooler 1 winter mode start temperature in tenths of degrees Fahrenheit (5408) | |||||||||||||||||||||
| NairIRmPmDrycooler1SummerStartTemp | 1.3.6.1.4.1.318.1.1.13.5.3.17.10 | ||||||||||||||||||||
| SairIRmPmDrycooler1SummerStartTempC | 1.3.6.1.4.1.318.1.1.13.5.3.17.10.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Drycooler 1 summer mode start temperature in tenths of degrees Celsius (5409) | |||||||||||||||||||||
| SairIRmPmDrycooler1SummerStartTempF | 1.3.6.1.4.1.318.1.1.13.5.3.17.10.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Drycooler 1 summer mode start temperature in tenths of degrees Fahrenheit (5409) | |||||||||||||||||||||
| NairIRmPmDrycooler1Hysteresis | 1.3.6.1.4.1.318.1.1.13.5.3.17.11 | ||||||||||||||||||||
| SairIRmPmDrycooler1HysteresisK | 1.3.6.1.4.1.318.1.1.13.5.3.17.11.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Drycooler 1 hysteresis in tenths of Kelvins (5410) | |||||||||||||||||||||
| SairIRmPmDrycooler1HysteresisF | 1.3.6.1.4.1.318.1.1.13.5.3.17.11.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Drycooler 1 hysteresis in tenths of degrees Fahrenheit (5410) | |||||||||||||||||||||
| SairIRmPmDrycooler1Runtime | 1.3.6.1.4.1.318.1.1.13.5.3.17.16 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Drycooler 1 runtime in hours (5415) | |||||||||||||||||||||
| NairIRmPmDrycooler2 | 1.3.6.1.4.1.318.1.1.13.5.3.18 | ||||||||||||||||||||
| SairIRmPmDrycooler2ManOpEnable | 1.3.6.1.4.1.318.1.1.13.5.3.18.2 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Drycooler 2 manual operation enable setting (5501) | |||||||||||||||||||||
| SairIRmPmDrycooler2Running | 1.3.6.1.4.1.318.1.1.13.5.3.18.3 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Drycooler 2 running (5502) | |||||||||||||||||||||
| SairIRmPmDrycooler2ManOpRunning | 1.3.6.1.4.1.318.1.1.13.5.3.18.5 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Drycooler 2 manual operation running (5504) | |||||||||||||||||||||
| NairIRmPmDrycooler2WinterStartTemp | 1.3.6.1.4.1.318.1.1.13.5.3.18.9 | ||||||||||||||||||||
| SairIRmPmDrycooler2WinterStartTempC | 1.3.6.1.4.1.318.1.1.13.5.3.18.9.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Drycooler 2 winter mode start temperature in tenths of degrees Celsius (5508) | |||||||||||||||||||||
| SairIRmPmDrycooler2WinterStartTempF | 1.3.6.1.4.1.318.1.1.13.5.3.18.9.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Drycooler 2 winter mode start temperature in tenths of degrees Fahrenheit (5508) | |||||||||||||||||||||
| NairIRmPmDrycooler2SummerStartTemp | 1.3.6.1.4.1.318.1.1.13.5.3.18.10 | ||||||||||||||||||||
| SairIRmPmDrycooler2SummerStartTempC | 1.3.6.1.4.1.318.1.1.13.5.3.18.10.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Drycooler 2 summer mode start temperature in tenths of degrees Celsius (5509) | |||||||||||||||||||||
| SairIRmPmDrycooler2SummerStartTempF | 1.3.6.1.4.1.318.1.1.13.5.3.18.10.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Drycooler 2 summer mode start temperature in tenths of degrees Fahrenheit (5509) | |||||||||||||||||||||
| NairIRmPmDrycooler2Hysteresis | 1.3.6.1.4.1.318.1.1.13.5.3.18.11 | ||||||||||||||||||||
| SairIRmPmDrycooler2HysteresisK | 1.3.6.1.4.1.318.1.1.13.5.3.18.11.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Drycooler 2 hysteresis in tenths of Kelvins (5510) | |||||||||||||||||||||
| SairIRmPmDrycooler2HysteresisF | 1.3.6.1.4.1.318.1.1.13.5.3.18.11.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Drycooler 2 hysteresis in tenths of degrees Fahrenheit (5510) | |||||||||||||||||||||
| SairIRmPmDrycooler2Runtime | 1.3.6.1.4.1.318.1.1.13.5.3.18.16 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Drycooler 2 runtime in hours (5515) | |||||||||||||||||||||
| NairIRmPmDrycooler3 | 1.3.6.1.4.1.318.1.1.13.5.3.19 | ||||||||||||||||||||
| SairIRmPmDrycooler3ManOpEnable | 1.3.6.1.4.1.318.1.1.13.5.3.19.2 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Drycooler 3 manual operation enable setting (5601) | |||||||||||||||||||||
| SairIRmPmDrycooler3Running | 1.3.6.1.4.1.318.1.1.13.5.3.19.3 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Drycooler 3 running (5602) | |||||||||||||||||||||
| SairIRmPmDrycooler3ManOpRunning | 1.3.6.1.4.1.318.1.1.13.5.3.19.5 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Drycooler 3 manual operation running (5604) | |||||||||||||||||||||
| NairIRmPmDrycooler3WinterStartTemp | 1.3.6.1.4.1.318.1.1.13.5.3.19.9 | ||||||||||||||||||||
| SairIRmPmDrycooler3WinterStartTempC | 1.3.6.1.4.1.318.1.1.13.5.3.19.9.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Drycooler 3 winter mode start temperature in tenths of degrees Celsius (5608) | |||||||||||||||||||||
| SairIRmPmDrycooler3WinterStartTempF | 1.3.6.1.4.1.318.1.1.13.5.3.19.9.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Drycooler 3 winter mode start temperature in tenths of degrees Fahrenheit (5608) | |||||||||||||||||||||
| NairIRmPmDrycooler3SummerStartTemp | 1.3.6.1.4.1.318.1.1.13.5.3.19.10 | ||||||||||||||||||||
| SairIRmPmDrycooler3SummerStartTempC | 1.3.6.1.4.1.318.1.1.13.5.3.19.10.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Drycooler 3 summer mode start temperature in tenths of degrees Celsius (5609) | |||||||||||||||||||||
| SairIRmPmDrycooler3SummerStartTempF | 1.3.6.1.4.1.318.1.1.13.5.3.19.10.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Drycooler 3 summer mode start temperature in tenths of degrees Fahrenheit (5609) | |||||||||||||||||||||
| NairIRmPmDrycooler3Hysteresis | 1.3.6.1.4.1.318.1.1.13.5.3.19.11 | ||||||||||||||||||||
| SairIRmPmDrycooler3HysteresisK | 1.3.6.1.4.1.318.1.1.13.5.3.19.11.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Drycooler 3 hysteresis in tenths of Kelvins (5610) | |||||||||||||||||||||
| SairIRmPmDrycooler3HysteresisF | 1.3.6.1.4.1.318.1.1.13.5.3.19.11.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Drycooler 3 hysteresis in tenths of degrees Fahrenheit (5610) | |||||||||||||||||||||
| SairIRmPmDrycooler3Runtime | 1.3.6.1.4.1.318.1.1.13.5.3.19.16 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Drycooler 3 runtime in hours (5615) | |||||||||||||||||||||
| NairIRmPmDrycooler4 | 1.3.6.1.4.1.318.1.1.13.5.3.20 | ||||||||||||||||||||
| SairIRmPmDrycooler4ManOpEnable | 1.3.6.1.4.1.318.1.1.13.5.3.20.2 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Drycooler 4 manual operation enable setting (5701) | |||||||||||||||||||||
| SairIRmPmDrycooler4Running | 1.3.6.1.4.1.318.1.1.13.5.3.20.3 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Drycooler 4 running (5702) | |||||||||||||||||||||
| SairIRmPmDrycooler4ManOpRunning | 1.3.6.1.4.1.318.1.1.13.5.3.20.5 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Drycooler 4 manual operation running (5704) | |||||||||||||||||||||
| NairIRmPmDrycooler4WinterStartTemp | 1.3.6.1.4.1.318.1.1.13.5.3.20.9 | ||||||||||||||||||||
| SairIRmPmDrycooler4WinterStartTempC | 1.3.6.1.4.1.318.1.1.13.5.3.20.9.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Drycooler 4 winter mode start temperature in tenths of degrees Celsius (5708) | |||||||||||||||||||||
| SairIRmPmDrycooler4WinterStartTempF | 1.3.6.1.4.1.318.1.1.13.5.3.20.9.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Drycooler 4 winter mode start temperature in tenths of degrees Fahrenheit (5708) | |||||||||||||||||||||
| NairIRmPmDrycooler4SummerStartTemp | 1.3.6.1.4.1.318.1.1.13.5.3.20.10 | ||||||||||||||||||||
| SairIRmPmDrycooler4SummerStartTempC | 1.3.6.1.4.1.318.1.1.13.5.3.20.10.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Drycooler 4 summer mode start temperature in tenths of degrees Celsius (5709) | |||||||||||||||||||||
| SairIRmPmDrycooler4SummerStartTempF | 1.3.6.1.4.1.318.1.1.13.5.3.20.10.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Drycooler 4 summer mode start temperature in tenths of degrees Fahrenheit (5709) | |||||||||||||||||||||
| NairIRmPmDrycooler4Hysteresis | 1.3.6.1.4.1.318.1.1.13.5.3.20.11 | ||||||||||||||||||||
| SairIRmPmDrycooler4HysteresisK | 1.3.6.1.4.1.318.1.1.13.5.3.20.11.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Drycooler 4 hysteresis in tenths of Kelvins (5710) | |||||||||||||||||||||
| SairIRmPmDrycooler4HysteresisF | 1.3.6.1.4.1.318.1.1.13.5.3.20.11.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Drycooler 4 hysteresis in tenths of degrees Fahrenheit (5710) | |||||||||||||||||||||
| SairIRmPmDrycooler4Runtime | 1.3.6.1.4.1.318.1.1.13.5.3.20.16 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Drycooler 4 runtime in hours (5715) | |||||||||||||||||||||
| NairIRmPmPump1 | 1.3.6.1.4.1.318.1.1.13.5.3.21 | ||||||||||||||||||||
| SairIRmPmPump1ManOpEnable | 1.3.6.1.4.1.318.1.1.13.5.3.21.2 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Pump 1 manual operation enable state (5801) | |||||||||||||||||||||
| SairIRmPmPump1Running | 1.3.6.1.4.1.318.1.1.13.5.3.21.3 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Pump 1 running (5802) | |||||||||||||||||||||
| SairIRmPmPump1ManOpRunning | 1.3.6.1.4.1.318.1.1.13.5.3.21.6 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Pump 1 manual operation running (5805) | |||||||||||||||||||||
| NairIRmPmPump1StartTemperature | 1.3.6.1.4.1.318.1.1.13.5.3.21.10 | ||||||||||||||||||||
| SairIRmPmPump1StartTemperatureK | 1.3.6.1.4.1.318.1.1.13.5.3.21.10.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Pump 1 starting temperature in tenths of Kelvins (5809) | |||||||||||||||||||||
| SairIRmPmPump1StartTemperatureF | 1.3.6.1.4.1.318.1.1.13.5.3.21.10.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Pump 1 starting temperature in tenths of degrees Fahrenheit (5809) | |||||||||||||||||||||
| NairIRmPmPump1Hysteresis | 1.3.6.1.4.1.318.1.1.13.5.3.21.11 | ||||||||||||||||||||
| SairIRmPmPump1HysteresisK | 1.3.6.1.4.1.318.1.1.13.5.3.21.11.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Pump 1 hysteresis in tenths of Kelvins (5810) | |||||||||||||||||||||
| SairIRmPmPump1HysteresisF | 1.3.6.1.4.1.318.1.1.13.5.3.21.11.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Pump 1 hysteresis in tenths of degrees Fahrenheit (5810) | |||||||||||||||||||||
| NairIRmPmPump1LinearRange | 1.3.6.1.4.1.318.1.1.13.5.3.21.12 | ||||||||||||||||||||
| SairIRmPmPump1LinearRangeK | 1.3.6.1.4.1.318.1.1.13.5.3.21.12.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Pump 1 linear range in tenths of Kelvins (5811) | |||||||||||||||||||||
| SairIRmPmPump1LinearRangeF | 1.3.6.1.4.1.318.1.1.13.5.3.21.12.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Pump 1 linear range in tenths of degrees Fahrenheit (5811) | |||||||||||||||||||||
| SairIRmPmPump1PressureSetpoint | 1.3.6.1.4.1.318.1.1.13.5.3.21.13 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Pump 1 pressure setpoint in tenths of Bars (5812) | |||||||||||||||||||||
| SairIRmPmPump1Runtime | 1.3.6.1.4.1.318.1.1.13.5.3.21.21 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Pump 1 runtime in hours (5820) | |||||||||||||||||||||
| SairIRmPmPump1Speed | 1.3.6.1.4.1.318.1.1.13.5.3.21.22 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Pump 1 speed in percent (5821) | |||||||||||||||||||||
| SairIRmPmPump1ControlCycle | 1.3.6.1.4.1.318.1.1.13.5.3.21.28 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Pump 1 control cycle length in seconds (5827) | |||||||||||||||||||||
| SairIRmPmPump1MaxAdjust | 1.3.6.1.4.1.318.1.1.13.5.3.21.29 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Pump 1 maximum adjustment in percent (5828) | |||||||||||||||||||||
| SairIRmPmPump1ControlFactor | 1.3.6.1.4.1.318.1.1.13.5.3.21.30 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Pump 1 control factor setting (5829) | |||||||||||||||||||||
| NairIRmPmPump2 | 1.3.6.1.4.1.318.1.1.13.5.3.22 | ||||||||||||||||||||
| SairIRmPmPump2ManOpEnable | 1.3.6.1.4.1.318.1.1.13.5.3.22.2 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Pump 2 manual operation enable state (5901) | |||||||||||||||||||||
| SairIRmPmPump2Running | 1.3.6.1.4.1.318.1.1.13.5.3.22.3 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Pump 2 running (5902) | |||||||||||||||||||||
| SairIRmPmPump2ManOpRunning | 1.3.6.1.4.1.318.1.1.13.5.3.22.6 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Pump 2 manual operation running (5905) | |||||||||||||||||||||
| NairIRmPmPump2StartTemperature | 1.3.6.1.4.1.318.1.1.13.5.3.22.10 | ||||||||||||||||||||
| SairIRmPmPump2StartTemperatureK | 1.3.6.1.4.1.318.1.1.13.5.3.22.10.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Pump 2 starting temperature in tenths of Kelvins (5909) | |||||||||||||||||||||
| SairIRmPmPump2StartTemperatureF | 1.3.6.1.4.1.318.1.1.13.5.3.22.10.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Pump 2 starting temperature in tenths of degrees Fahrenheit (5909) | |||||||||||||||||||||
| NairIRmPmPump2Hysteresis | 1.3.6.1.4.1.318.1.1.13.5.3.22.11 | ||||||||||||||||||||
| SairIRmPmPump2HysteresisK | 1.3.6.1.4.1.318.1.1.13.5.3.22.11.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Pump 2 hysteresis in tenths of Kelvins (5910) | |||||||||||||||||||||
| SairIRmPmPump2HysteresisF | 1.3.6.1.4.1.318.1.1.13.5.3.22.11.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Pump 2 hysteresis in tenths of degrees Fahrenheit (5910) | |||||||||||||||||||||
| NairIRmPmPump2LinearRange | 1.3.6.1.4.1.318.1.1.13.5.3.22.12 | ||||||||||||||||||||
| SairIRmPmPump2LinearRangeK | 1.3.6.1.4.1.318.1.1.13.5.3.22.12.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Pump 2 linear range in tenths of Kelvins (5911) | |||||||||||||||||||||
| SairIRmPmPump2LinearRangeF | 1.3.6.1.4.1.318.1.1.13.5.3.22.12.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Pump 2 linear range in tenths of degrees Fahrenheit (5911) | |||||||||||||||||||||
| SairIRmPmPump2PressureSetpoint | 1.3.6.1.4.1.318.1.1.13.5.3.22.13 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Pump 2 pressure setpoint in tenths of Bars (5912) | |||||||||||||||||||||
| SairIRmPmPump2Runtime | 1.3.6.1.4.1.318.1.1.13.5.3.22.21 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Pump 2 runtime in hours (5920) | |||||||||||||||||||||
| SairIRmPmPump2Speed | 1.3.6.1.4.1.318.1.1.13.5.3.22.22 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Pump 2 speed in percent (5921) | |||||||||||||||||||||
| SairIRmPmPump2ControlCycle | 1.3.6.1.4.1.318.1.1.13.5.3.22.28 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Pump 2 control cycle length in seconds (5927) | |||||||||||||||||||||
| SairIRmPmPump2MaxAdjust | 1.3.6.1.4.1.318.1.1.13.5.3.22.29 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Pump 2 maximum adjustment in percent (5928) | |||||||||||||||||||||
| SairIRmPmPump2ControlFactor | 1.3.6.1.4.1.318.1.1.13.5.3.22.30 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Pump 2 control factor setting (5929) | |||||||||||||||||||||
| NairIRmPmPump3 | 1.3.6.1.4.1.318.1.1.13.5.3.23 | ||||||||||||||||||||
| SairIRmPmPump3ManOpEnable | 1.3.6.1.4.1.318.1.1.13.5.3.23.2 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Pump 3 manual operation enable state (6001) | |||||||||||||||||||||
| SairIRmPmPump3Running | 1.3.6.1.4.1.318.1.1.13.5.3.23.3 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Pump 3 running (6002) | |||||||||||||||||||||
| SairIRmPmPump3ManOpRunning | 1.3.6.1.4.1.318.1.1.13.5.3.23.6 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Pump 3 manual operation running (6005) | |||||||||||||||||||||
| NairIRmPmPump3StartTemperature | 1.3.6.1.4.1.318.1.1.13.5.3.23.10 | ||||||||||||||||||||
| SairIRmPmPump3StartTemperatureK | 1.3.6.1.4.1.318.1.1.13.5.3.23.10.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Pump 3 starting temperature in tenths of Kelvins (6009) | |||||||||||||||||||||
| SairIRmPmPump3StartTemperatureF | 1.3.6.1.4.1.318.1.1.13.5.3.23.10.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Pump 3 starting temperature in tenths of degrees Fahrenheit (6009) | |||||||||||||||||||||
| NairIRmPmPump3Hysteresis | 1.3.6.1.4.1.318.1.1.13.5.3.23.11 | ||||||||||||||||||||
| SairIRmPmPump3HysteresisK | 1.3.6.1.4.1.318.1.1.13.5.3.23.11.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Pump 3 hysteresis in tenths of Kelvins (6010) | |||||||||||||||||||||
| SairIRmPmPump3HysteresisF | 1.3.6.1.4.1.318.1.1.13.5.3.23.11.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Pump 3 hysteresis in tenths of degrees Fahrenheit (6010) | |||||||||||||||||||||
| NairIRmPmPump3LinearRange | 1.3.6.1.4.1.318.1.1.13.5.3.23.12 | ||||||||||||||||||||
| SairIRmPmPump3LinearRangeK | 1.3.6.1.4.1.318.1.1.13.5.3.23.12.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Pump 3 linear range in tenths of Kelvins (6011) | |||||||||||||||||||||
| SairIRmPmPump3LinearRangeF | 1.3.6.1.4.1.318.1.1.13.5.3.23.12.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Pump 3 linear range in tenths of degrees Fahrenheit (6011) | |||||||||||||||||||||
| SairIRmPmPump3PressureSetpoint | 1.3.6.1.4.1.318.1.1.13.5.3.23.13 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Pump 3 pressure setpoint in tenths of Bars (6012) | |||||||||||||||||||||
| SairIRmPmPump3Runtime | 1.3.6.1.4.1.318.1.1.13.5.3.23.21 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Pump 3 runtime in hours (6020) | |||||||||||||||||||||
| SairIRmPmPump3Speed | 1.3.6.1.4.1.318.1.1.13.5.3.23.22 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Pump 3 speed in percent (6021) | |||||||||||||||||||||
| SairIRmPmPump3ControlCycle | 1.3.6.1.4.1.318.1.1.13.5.3.23.28 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Pump 3 control cycle length in seconds (6027) | |||||||||||||||||||||
| SairIRmPmPump3MaxAdjust | 1.3.6.1.4.1.318.1.1.13.5.3.23.29 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Pump 3 maximum adjustment in percent (6028) | |||||||||||||||||||||
| SairIRmPmPump3ControlFactor | 1.3.6.1.4.1.318.1.1.13.5.3.23.30 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Pump 3 control factor setting (6029) | |||||||||||||||||||||
| NairIRmPmPump4 | 1.3.6.1.4.1.318.1.1.13.5.3.24 | ||||||||||||||||||||
| SairIRmPmPump4ManOpEnable | 1.3.6.1.4.1.318.1.1.13.5.3.24.2 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Pump 4 manual operation enable state (6101) | |||||||||||||||||||||
| SairIRmPmPump4Running | 1.3.6.1.4.1.318.1.1.13.5.3.24.3 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Pump 4 running (6102) | |||||||||||||||||||||
| SairIRmPmPump4ManOpRunning | 1.3.6.1.4.1.318.1.1.13.5.3.24.6 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Pump 4 manual operation running (6105) | |||||||||||||||||||||
| NairIRmPmPump4StartTemperature | 1.3.6.1.4.1.318.1.1.13.5.3.24.10 | ||||||||||||||||||||
| SairIRmPmPump4StartTemperatureK | 1.3.6.1.4.1.318.1.1.13.5.3.24.10.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Pump 4 starting temperature in tenths of Kelvins (6109) | |||||||||||||||||||||
| SairIRmPmPump4StartTemperatureF | 1.3.6.1.4.1.318.1.1.13.5.3.24.10.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Pump 4 starting temperature in tenths of degrees Fahrenheit (6109) | |||||||||||||||||||||
| NairIRmPmPump4Hysteresis | 1.3.6.1.4.1.318.1.1.13.5.3.24.11 | ||||||||||||||||||||
| SairIRmPmPump4HysteresisK | 1.3.6.1.4.1.318.1.1.13.5.3.24.11.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Pump 4 hysteresis in tenths of Kelvins (6110) | |||||||||||||||||||||
| SairIRmPmPump4HysteresisF | 1.3.6.1.4.1.318.1.1.13.5.3.24.11.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Pump 4 hysteresis in tenths of degrees Fahrenheit (6110) | |||||||||||||||||||||
| NairIRmPmPump4LinearRange | 1.3.6.1.4.1.318.1.1.13.5.3.24.12 | ||||||||||||||||||||
| SairIRmPmPump4LinearRangeK | 1.3.6.1.4.1.318.1.1.13.5.3.24.12.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Pump 4 linear range in tenths of Kelvins (6111) | |||||||||||||||||||||
| SairIRmPmPump4LinearRangeF | 1.3.6.1.4.1.318.1.1.13.5.3.24.12.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Pump 4 linear range in tenths of degrees Fahrenheit (6111) | |||||||||||||||||||||
| SairIRmPmPump4PressureSetpoint | 1.3.6.1.4.1.318.1.1.13.5.3.24.13 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Pump 4 pressure setpoint in tenths of Bars (6112) | |||||||||||||||||||||
| SairIRmPmPump4Runtime | 1.3.6.1.4.1.318.1.1.13.5.3.24.21 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Pump 4 runtime in hours (6120) | |||||||||||||||||||||
| SairIRmPmPump4Speed | 1.3.6.1.4.1.318.1.1.13.5.3.24.22 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Pump 4 speed in percent (6121) | |||||||||||||||||||||
| SairIRmPmPump4ControlCycle | 1.3.6.1.4.1.318.1.1.13.5.3.24.28 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Pump 4 control cycle length in seconds (6127) | |||||||||||||||||||||
| SairIRmPmPump4MaxAdjust | 1.3.6.1.4.1.318.1.1.13.5.3.24.29 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Pump 4 maximum adjustment in percent (6128) | |||||||||||||||||||||
| SairIRmPmPump4ControlFactor | 1.3.6.1.4.1.318.1.1.13.5.3.24.30 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Pump 4 control factor setting (6129) | |||||||||||||||||||||
| NairIRmPmHotgasHeating | 1.3.6.1.4.1.318.1.1.13.5.3.25 | ||||||||||||||||||||
| SairIRmPmHotgasHeatRunning | 1.3.6.1.4.1.318.1.1.13.5.3.25.3 | AirIRmControlState | RO | mandatory | |||||||||||||||||
scalar · AirIRmControlState · read-only · mandatory Hotgas heat running state. (6202) | |||||||||||||||||||||
| NairIRmPmPWWHeating | 1.3.6.1.4.1.318.1.1.13.5.3.26 | ||||||||||||||||||||
| SairIRmPmPWWHeatingManOpEnable | 1.3.6.1.4.1.318.1.1.13.5.3.26.2 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory PWW-heating manual operation enable (6301) | |||||||||||||||||||||
| SairIRmPmPWWHeatingRunning | 1.3.6.1.4.1.318.1.1.13.5.3.26.3 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory PWW-heating running (6302) | |||||||||||||||||||||
| SairIRmPmPWWHeatingManOpRunning | 1.3.6.1.4.1.318.1.1.13.5.3.26.4 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory PWW-heating manual operation running (6303) | |||||||||||||||||||||
| SairIRmPmPWWHeatingType | 1.3.6.1.4.1.318.1.1.13.5.3.26.9 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory PWW-heating type (6308)
| |||||||||||||||||||||
| NairIRmPmPWWHeatingStartTemp | 1.3.6.1.4.1.318.1.1.13.5.3.26.10 | ||||||||||||||||||||
| SairIRmPmPWWHeatingStartTempK | 1.3.6.1.4.1.318.1.1.13.5.3.26.10.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory PWW-heating starting temperature in Kelvins (6309) | |||||||||||||||||||||
| SairIRmPmPWWHeatingStartTempF | 1.3.6.1.4.1.318.1.1.13.5.3.26.10.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory PWW-heating starting temperature in degrees Fahrenheit (6309) | |||||||||||||||||||||
| NairIRmPmPWWHeatingHysteresis | 1.3.6.1.4.1.318.1.1.13.5.3.26.12 | ||||||||||||||||||||
| SairIRmPmPWWHeatingHysteresisK | 1.3.6.1.4.1.318.1.1.13.5.3.26.12.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory PWW-heating hysteresis in Kelvins (6311) | |||||||||||||||||||||
| SairIRmPmPWWHeatingHysteresisF | 1.3.6.1.4.1.318.1.1.13.5.3.26.12.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory PWW-heating hysteresis in degrees Fahrenheit (6311) | |||||||||||||||||||||
| NairIRmPmPWWHeatingLinearRange | 1.3.6.1.4.1.318.1.1.13.5.3.26.13 | ||||||||||||||||||||
| SairIRmPmPWWHeatingLinearRangeK | 1.3.6.1.4.1.318.1.1.13.5.3.26.13.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory PWW-heating linear range in Kelvins (6312) | |||||||||||||||||||||
| SairIRmPmPWWHeatingLinearRangeF | 1.3.6.1.4.1.318.1.1.13.5.3.26.13.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory PWW-heating linear range in degrees Fahrenheit (6312) | |||||||||||||||||||||
| SairIRmPmPWWHeatingCurrentValue | 1.3.6.1.4.1.318.1.1.13.5.3.26.16 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory PWW-heating current value in percent (6315) | |||||||||||||||||||||
| SairIRmPmPWWHeatingManOpValue | 1.3.6.1.4.1.318.1.1.13.5.3.26.17 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory PWW-heating manual operation value in percent (6316) | |||||||||||||||||||||
| NairIRmPmHumidifier1 | 1.3.6.1.4.1.318.1.1.13.5.3.27 | ||||||||||||||||||||
| SairIRmPmHumidifier1ManOpEnable | 1.3.6.1.4.1.318.1.1.13.5.3.27.2 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Humidifier #1 manual operation enable (6401) | |||||||||||||||||||||
| SairIRmPmHumidifier1Running | 1.3.6.1.4.1.318.1.1.13.5.3.27.3 | AirIRmControlState | RO | mandatory | |||||||||||||||||
scalar · AirIRmControlState · read-only · mandatory Humidifier #1 running state (6402) | |||||||||||||||||||||
| SairIRmPmHumidifier1ManOpRunning | 1.3.6.1.4.1.318.1.1.13.5.3.27.5 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Humidifier #1 manual operation running state (6404) | |||||||||||||||||||||
| SairIRmPmHumidifier1Type | 1.3.6.1.4.1.318.1.1.13.5.3.27.17 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Humidifier #1 type (6416)
| |||||||||||||||||||||
| SairIRmPmHumidifier1StartHumidity | 1.3.6.1.4.1.318.1.1.13.5.3.27.18 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Humidifier #1 start humidity in tenths of percent relative humidity (6417) | |||||||||||||||||||||
| SairIRmPmHumidifier1Hysteresis | 1.3.6.1.4.1.318.1.1.13.5.3.27.20 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Humidifier #1 hysteresis in tenths of percent relative humidity (6419) | |||||||||||||||||||||
| SairIRmPmHumidifier1LinearRange | 1.3.6.1.4.1.318.1.1.13.5.3.27.21 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Humidifier #1 linear range in tenths of percent relative humidity per Kelvin (6420) | |||||||||||||||||||||
| SairIRmPmHumidifier1Runtime | 1.3.6.1.4.1.318.1.1.13.5.3.27.27 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Humidifier #1 runtime in hours (6426) | |||||||||||||||||||||
| SairIRmPmHumidifier1CurrentValue | 1.3.6.1.4.1.318.1.1.13.5.3.27.28 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Humidifier #1 current value in percent (6427) | |||||||||||||||||||||
| SairIRmPmHumidifier1ManOpValue | 1.3.6.1.4.1.318.1.1.13.5.3.27.29 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Humidifier #1 manual operation value in percent (6428) | |||||||||||||||||||||
| NairIRmPmHumidifier2 | 1.3.6.1.4.1.318.1.1.13.5.3.28 | ||||||||||||||||||||
| SairIRmPmHumidifier2ManOpEnable | 1.3.6.1.4.1.318.1.1.13.5.3.28.2 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Humidifier #2 manual operation enable (6501) | |||||||||||||||||||||
| SairIRmPmHumidifier2Running | 1.3.6.1.4.1.318.1.1.13.5.3.28.3 | AirIRmControlState | RO | mandatory | |||||||||||||||||
scalar · AirIRmControlState · read-only · mandatory Humidifier #2 running state (6502) | |||||||||||||||||||||
| SairIRmPmHumidifier2ManOpRunning | 1.3.6.1.4.1.318.1.1.13.5.3.28.5 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Humidifier #2 manual operation running state (6504) | |||||||||||||||||||||
| SairIRmPmHumidifier2Type | 1.3.6.1.4.1.318.1.1.13.5.3.28.17 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Humidifier #2 type (6516)
| |||||||||||||||||||||
| SairIRmPmHumidifier2StartHumidity | 1.3.6.1.4.1.318.1.1.13.5.3.28.18 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Humidifier #2 start humidity in tenths of percent relative humidity (6517) | |||||||||||||||||||||
| SairIRmPmHumidifier2Hysteresis | 1.3.6.1.4.1.318.1.1.13.5.3.28.20 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Humidifier #2 hysteresis in tenths of percent relative humidity (6519) | |||||||||||||||||||||
| SairIRmPmHumidifier2LinearRange | 1.3.6.1.4.1.318.1.1.13.5.3.28.21 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Humidifier #2 linear range in tenths of percent relative humidity per Kelvin (6520) | |||||||||||||||||||||
| SairIRmPmHumidifier2Runtime | 1.3.6.1.4.1.318.1.1.13.5.3.28.27 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Humidifier #2 runtime in hours (6526) | |||||||||||||||||||||
| SairIRmPmHumidifier2CurrentValue | 1.3.6.1.4.1.318.1.1.13.5.3.28.28 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Humidifier #2 current value in percent (6527) | |||||||||||||||||||||
| SairIRmPmHumidifier2ManOpValue | 1.3.6.1.4.1.318.1.1.13.5.3.28.29 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Humidifier #2 manual operation value in percent (6528) | |||||||||||||||||||||
| NairIRmPmDehumidification | 1.3.6.1.4.1.318.1.1.13.5.3.31 | ||||||||||||||||||||
| SairIRmPmDehumidificManOpEnable | 1.3.6.1.4.1.318.1.1.13.5.3.31.2 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Dehumidifier manual operation enable setting (6801) | |||||||||||||||||||||
| SairIRmPmDehumidificRunning | 1.3.6.1.4.1.318.1.1.13.5.3.31.3 | AirIRmControlState | RO | mandatory | |||||||||||||||||
scalar · AirIRmControlState · read-only · mandatory Dehumidifier running state (6802) | |||||||||||||||||||||
| SairIRmPmDehumidificManOpRunning | 1.3.6.1.4.1.318.1.1.13.5.3.31.5 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Dehumidifier manual operation running (6804) | |||||||||||||||||||||
| SairIRmPmDehumidificStartHumidity | 1.3.6.1.4.1.318.1.1.13.5.3.31.10 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Dehumidifier start humidity in tenths of percent relative humidity (6809) | |||||||||||||||||||||
| SairIRmPmDehumidificHysteresis | 1.3.6.1.4.1.318.1.1.13.5.3.31.12 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Dehumidifier hysteresis in tenths of percent relative humidity (6811) | |||||||||||||||||||||
| NairIRmPmDehumidificMinWaterTemp | 1.3.6.1.4.1.318.1.1.13.5.3.31.18 | ||||||||||||||||||||
| SairIRmPmDehumidificMinWaterTempC | 1.3.6.1.4.1.318.1.1.13.5.3.31.18.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Dehumidifier minimum water temperature in tenths of degrees Celsius (6817) | |||||||||||||||||||||
| SairIRmPmDehumidificMinWaterTempF | 1.3.6.1.4.1.318.1.1.13.5.3.31.18.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Dehumidifier minimum water temperature in tenths of degrees Fahrenheit (6817) | |||||||||||||||||||||
| NairIRmPmDehumidificMaxWaterTemp | 1.3.6.1.4.1.318.1.1.13.5.3.31.19 | ||||||||||||||||||||
| SairIRmPmDehumidificMaxWaterTempC | 1.3.6.1.4.1.318.1.1.13.5.3.31.19.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Dehumidifier maximum water temperature in tenths of degrees Celsius (6818) | |||||||||||||||||||||
| SairIRmPmDehumidificMaxWaterTempF | 1.3.6.1.4.1.318.1.1.13.5.3.31.19.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Dehumidifier maximum water temperature in tenths of degrees Fahrenheit (6818) | |||||||||||||||||||||
| SairIRmPmDehumidificRuntime | 1.3.6.1.4.1.318.1.1.13.5.3.31.21 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Dehumidifier runtime in hours (6820) | |||||||||||||||||||||
| NairIRmPmFan1 | 1.3.6.1.4.1.318.1.1.13.5.3.32 | ||||||||||||||||||||
| SairIRmPmFan1ManOpEnable | 1.3.6.1.4.1.318.1.1.13.5.3.32.2 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Fan 1 manual operation enable (6901) | |||||||||||||||||||||
| SairIRmPmFan1Running | 1.3.6.1.4.1.318.1.1.13.5.3.32.3 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Fan 1 running (6902) | |||||||||||||||||||||
| SairIRmPmFan1ManOpRunning | 1.3.6.1.4.1.318.1.1.13.5.3.32.6 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Fan 1 manual operation running (6905) | |||||||||||||||||||||
| SairIRmPmFan1Type | 1.3.6.1.4.1.318.1.1.13.5.3.32.9 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Fan 1 type (6908)
| |||||||||||||||||||||
| SairIRmPmFan1Runtime | 1.3.6.1.4.1.318.1.1.13.5.3.32.32 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Fan 1 runtime in hours (6931) | |||||||||||||||||||||
| SairIRmPmFan1Speed | 1.3.6.1.4.1.318.1.1.13.5.3.32.33 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Fan 1 speed in percent (6932) | |||||||||||||||||||||
| SairIRmPmFan1ManOpSpeed | 1.3.6.1.4.1.318.1.1.13.5.3.32.34 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Fan 1 manual operation speed in percent (6933) | |||||||||||||||||||||
| NairIRmPmFan2 | 1.3.6.1.4.1.318.1.1.13.5.3.33 | ||||||||||||||||||||
| SairIRmPmFan2ManOpEnable | 1.3.6.1.4.1.318.1.1.13.5.3.33.2 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Fan 1 manual operation enable (7001) | |||||||||||||||||||||
| SairIRmPmFan2Running | 1.3.6.1.4.1.318.1.1.13.5.3.33.3 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Fan 1 running (7002) | |||||||||||||||||||||
| SairIRmPmFan2ManOpRunning | 1.3.6.1.4.1.318.1.1.13.5.3.33.6 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Fan 1 manual operation running (7005) | |||||||||||||||||||||
| SairIRmPmFan2Type | 1.3.6.1.4.1.318.1.1.13.5.3.33.9 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Fan 2 type (7008)
| |||||||||||||||||||||
| SairIRmPmFan2Runtime | 1.3.6.1.4.1.318.1.1.13.5.3.33.32 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Fan 1 runtime in hours (7031) | |||||||||||||||||||||
| SairIRmPmFan2Speed | 1.3.6.1.4.1.318.1.1.13.5.3.33.33 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Fan 1 speed in percent (7032) | |||||||||||||||||||||
| SairIRmPmFan2ManOpSpeed | 1.3.6.1.4.1.318.1.1.13.5.3.33.34 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Fan 1 manual operation speed in percent (7033) | |||||||||||||||||||||
| NairIRmPmFan3 | 1.3.6.1.4.1.318.1.1.13.5.3.34 | ||||||||||||||||||||
| SairIRmPmFan3ManOpEnable | 1.3.6.1.4.1.318.1.1.13.5.3.34.2 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Fan 1 manual operation enable (7101) | |||||||||||||||||||||
| SairIRmPmFan3Running | 1.3.6.1.4.1.318.1.1.13.5.3.34.3 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Fan 1 running (7102) | |||||||||||||||||||||
| SairIRmPmFan3ManOpRunning | 1.3.6.1.4.1.318.1.1.13.5.3.34.6 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Fan 1 manual operation running (7105) | |||||||||||||||||||||
| SairIRmPmFan3Type | 1.3.6.1.4.1.318.1.1.13.5.3.34.9 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Fan 3 type (7108)
| |||||||||||||||||||||
| SairIRmPmFan3Runtime | 1.3.6.1.4.1.318.1.1.13.5.3.34.32 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Fan 1 runtime in hours (7131) | |||||||||||||||||||||
| SairIRmPmFan3Speed | 1.3.6.1.4.1.318.1.1.13.5.3.34.33 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Fan 1 speed in percent (7132) | |||||||||||||||||||||
| SairIRmPmFan3ManOpSpeed | 1.3.6.1.4.1.318.1.1.13.5.3.34.34 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Fan 1 manual operation speed in percent (7133) | |||||||||||||||||||||
| NairIRmPmLouver1 | 1.3.6.1.4.1.318.1.1.13.5.3.35 | ||||||||||||||||||||
| SairIRmPmLouver1ManOpEnable | 1.3.6.1.4.1.318.1.1.13.5.3.35.2 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Louver 1 manual operation enable (7201) | |||||||||||||||||||||
| SairIRmPmLouver1Position | 1.3.6.1.4.1.318.1.1.13.5.3.35.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Louver 1 position (7202)
| |||||||||||||||||||||
| SairIRmPmLouver1ManOpPosition | 1.3.6.1.4.1.318.1.1.13.5.3.35.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Louver 1 manual operation position setting (7203)
| |||||||||||||||||||||
| NairIRmPmLouver2 | 1.3.6.1.4.1.318.1.1.13.5.3.36 | ||||||||||||||||||||
| SairIRmPmLouver2ManOpEnable | 1.3.6.1.4.1.318.1.1.13.5.3.36.2 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Louver 2 manual operation enable (7301) | |||||||||||||||||||||
| SairIRmPmLouver2Position | 1.3.6.1.4.1.318.1.1.13.5.3.36.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Louver 2 position (7302)
| |||||||||||||||||||||
| SairIRmPmLouver2ManOpPosition | 1.3.6.1.4.1.318.1.1.13.5.3.36.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Louver 2 manual operation position setting (7303)
| |||||||||||||||||||||
| NairIRmPmLouver3 | 1.3.6.1.4.1.318.1.1.13.5.3.37 | ||||||||||||||||||||
| SairIRmPmLouver3ManOpEnable | 1.3.6.1.4.1.318.1.1.13.5.3.37.2 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Louver 3 manual operation enable (7401) | |||||||||||||||||||||
| SairIRmPmLouver3Position | 1.3.6.1.4.1.318.1.1.13.5.3.37.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Louver 3 position (7402)
| |||||||||||||||||||||
| SairIRmPmLouver3ManOpPosition | 1.3.6.1.4.1.318.1.1.13.5.3.37.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Louver 3 manual operation position setting (7403)
| |||||||||||||||||||||
| NairIRmPmAuxAlarm1 | 1.3.6.1.4.1.318.1.1.13.5.3.38 | ||||||||||||||||||||
| NairIRmPmAuxAlarm2 | 1.3.6.1.4.1.318.1.1.13.5.3.39 | ||||||||||||||||||||
| NairIRmPmAuxAlarm3 | 1.3.6.1.4.1.318.1.1.13.5.3.40 | ||||||||||||||||||||
| NairIRmPmAuxAlarm4 | 1.3.6.1.4.1.318.1.1.13.5.3.41 | ||||||||||||||||||||
| NairIRmPmAuxAlarm5 | 1.3.6.1.4.1.318.1.1.13.5.3.42 | ||||||||||||||||||||
| NairIRmPmAlarmBits | 1.3.6.1.4.1.318.1.1.13.5.3.43 | ||||||||||||||||||||
| SairIRmPmFan1Failure | 1.3.6.1.4.1.318.1.1.13.5.3.43.1 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Fan #1 failure (8500). | |||||||||||||||||||||
| SairIRmPmFan2Failure | 1.3.6.1.4.1.318.1.1.13.5.3.43.2 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Fan #2 failure (8501). | |||||||||||||||||||||
| SairIRmPmFan3Failure | 1.3.6.1.4.1.318.1.1.13.5.3.43.3 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Fan #3 failure (8502). | |||||||||||||||||||||
| SairIRmPmCompressor1Failure | 1.3.6.1.4.1.318.1.1.13.5.3.43.4 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Compressor #1 failure (8503). | |||||||||||||||||||||
| SairIRmPmCompressor2Failure | 1.3.6.1.4.1.318.1.1.13.5.3.43.5 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Compressor #2 failure (8504). | |||||||||||||||||||||
| SairIRmPmWaterDetector | 1.3.6.1.4.1.318.1.1.13.5.3.43.6 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Water detector alarm (8505). | |||||||||||||||||||||
| SairIRmPmPhaseFailure | 1.3.6.1.4.1.318.1.1.13.5.3.43.7 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Phase failure (8506). | |||||||||||||||||||||
| SairIRmPmFireSmokeDetector | 1.3.6.1.4.1.318.1.1.13.5.3.43.8 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Fire/smoke detector (8507). | |||||||||||||||||||||
| SairIRmPmReturnAirTemperatureTooHigh | 1.3.6.1.4.1.318.1.1.13.5.3.43.9 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Return air temperature too high (8508). | |||||||||||||||||||||
| SairIRmPmReturnAirHumidityTooHigh | 1.3.6.1.4.1.318.1.1.13.5.3.43.10 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Return air humidity too high (8509). | |||||||||||||||||||||
| SairIRmPmSupplyAirTemperatureTooHigh | 1.3.6.1.4.1.318.1.1.13.5.3.43.11 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Supply air temperature too high (8510). | |||||||||||||||||||||
| SairIRmPmSupplyAirHumidityTooHigh | 1.3.6.1.4.1.318.1.1.13.5.3.43.12 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Supply air humidity too high (8511). | |||||||||||||||||||||
| SairIRmPmWaterTemperatureTooHigh | 1.3.6.1.4.1.318.1.1.13.5.3.43.13 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Water temperature too high (8512). | |||||||||||||||||||||
| SairIRmPmReturnAirTemperatureTooLow | 1.3.6.1.4.1.318.1.1.13.5.3.43.14 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Return air temperature too low (8513). | |||||||||||||||||||||
| SairIRmPmReturnAirHumidityTooLow | 1.3.6.1.4.1.318.1.1.13.5.3.43.15 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Return air humidity too low (8514). | |||||||||||||||||||||
| SairIRmPmSupplyAirTemperatureTooLow | 1.3.6.1.4.1.318.1.1.13.5.3.43.16 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Supply air temperature too low (8515). | |||||||||||||||||||||
| SairIRmPmSupplyAirHumidityTooLow | 1.3.6.1.4.1.318.1.1.13.5.3.43.17 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Supply air humidity too low (8516). | |||||||||||||||||||||
| SairIRmPmWaterTemperatureTooLow | 1.3.6.1.4.1.318.1.1.13.5.3.43.18 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Water temperature too low (8517). | |||||||||||||||||||||
| SairIRmPmSensor1Failure | 1.3.6.1.4.1.318.1.1.13.5.3.43.19 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Sensor #1 failure (8518). | |||||||||||||||||||||
| SairIRmPmSensor2Failure | 1.3.6.1.4.1.318.1.1.13.5.3.43.20 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Sensor #2 failure (8519). | |||||||||||||||||||||
| SairIRmPmSensor3Failure | 1.3.6.1.4.1.318.1.1.13.5.3.43.21 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Sensor #3 failure (8520). | |||||||||||||||||||||
| SairIRmPmSensor4Failure | 1.3.6.1.4.1.318.1.1.13.5.3.43.22 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Sensor #4 failure (8521). | |||||||||||||||||||||
| SairIRmPmSensor5Failure | 1.3.6.1.4.1.318.1.1.13.5.3.43.23 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Sensor #5 failure (8522). | |||||||||||||||||||||
| SairIRmPmSensor6Failure | 1.3.6.1.4.1.318.1.1.13.5.3.43.24 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Sensor #6 failure (8523). | |||||||||||||||||||||
| SairIRmPmSensor7Failure | 1.3.6.1.4.1.318.1.1.13.5.3.43.25 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Sensor #7 failure (8524). | |||||||||||||||||||||
| SairIRmPmSensor8Failure | 1.3.6.1.4.1.318.1.1.13.5.3.43.26 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Sensor #8 failure (8525). | |||||||||||||||||||||
| SairIRmPmSensor9Failure | 1.3.6.1.4.1.318.1.1.13.5.3.43.27 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Sensor #9 failure (8526). | |||||||||||||||||||||
| SairIRmPmSensor10Failure | 1.3.6.1.4.1.318.1.1.13.5.3.43.28 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Sensor #10 failure (8527). | |||||||||||||||||||||
| SairIRmPmSensor11Failure | 1.3.6.1.4.1.318.1.1.13.5.3.43.29 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Sensor #11 failure (8528). | |||||||||||||||||||||
| SairIRmPmSensor12Failure | 1.3.6.1.4.1.318.1.1.13.5.3.43.30 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Sensor #12 failure (8529). | |||||||||||||||||||||
| SairIRmPmSensor13Failure | 1.3.6.1.4.1.318.1.1.13.5.3.43.31 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Sensor #13 failure (8530). | |||||||||||||||||||||
| SairIRmPmSensor14Failure | 1.3.6.1.4.1.318.1.1.13.5.3.43.32 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Sensor #14 failure (8531). | |||||||||||||||||||||
| SairIRmPmSensor15Failure | 1.3.6.1.4.1.318.1.1.13.5.3.43.33 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Sensor #15 failure (8532). | |||||||||||||||||||||
| SairIRmPmSensor16Failure | 1.3.6.1.4.1.318.1.1.13.5.3.43.34 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Sensor #16 failure (8533). | |||||||||||||||||||||
| SairIRmPmSensor17Failure | 1.3.6.1.4.1.318.1.1.13.5.3.43.35 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Sensor #17 failure (8534). | |||||||||||||||||||||
| SairIRmPmSensor18Failure | 1.3.6.1.4.1.318.1.1.13.5.3.43.36 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Sensor #18 failure (8535). | |||||||||||||||||||||
| SairIRmPmSensor19Failure | 1.3.6.1.4.1.318.1.1.13.5.3.43.37 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Sensor #19 failure (8536). | |||||||||||||||||||||
| SairIRmPmSensor20Failure | 1.3.6.1.4.1.318.1.1.13.5.3.43.38 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Sensor #20 failure (8537). | |||||||||||||||||||||
| SairIRmPmSensor21Failure | 1.3.6.1.4.1.318.1.1.13.5.3.43.39 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Sensor #21 failure (8538). | |||||||||||||||||||||
| SairIRmPmSensor1Defect | 1.3.6.1.4.1.318.1.1.13.5.3.43.40 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Sensor #1 defect (8539). | |||||||||||||||||||||
| SairIRmPmSensor2Defect | 1.3.6.1.4.1.318.1.1.13.5.3.43.41 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Sensor #2 defect (8540). | |||||||||||||||||||||
| SairIRmPmSensor3Defect | 1.3.6.1.4.1.318.1.1.13.5.3.43.42 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Sensor #3 defect (8541). | |||||||||||||||||||||
| SairIRmPmSensor4Defect | 1.3.6.1.4.1.318.1.1.13.5.3.43.43 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Sensor #4 defect (8542). | |||||||||||||||||||||
| SairIRmPmSensor5Defect | 1.3.6.1.4.1.318.1.1.13.5.3.43.44 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Sensor #5 defect (8543). | |||||||||||||||||||||
| SairIRmPmSensor6Defect | 1.3.6.1.4.1.318.1.1.13.5.3.43.45 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Sensor #6 defect (8544). | |||||||||||||||||||||
| SairIRmPmSensor7Defect | 1.3.6.1.4.1.318.1.1.13.5.3.43.46 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Sensor #7 defect (8545). | |||||||||||||||||||||
| SairIRmPmSensor8Defect | 1.3.6.1.4.1.318.1.1.13.5.3.43.47 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Sensor #8 defect (8546). | |||||||||||||||||||||
| SairIRmPmSensor9Defect | 1.3.6.1.4.1.318.1.1.13.5.3.43.48 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Sensor #9 defect (8547). | |||||||||||||||||||||
| SairIRmPmSensor10Defect | 1.3.6.1.4.1.318.1.1.13.5.3.43.49 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Sensor #10 defect (8548). | |||||||||||||||||||||
| SairIRmPmSensor11Defect | 1.3.6.1.4.1.318.1.1.13.5.3.43.50 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Sensor #11 defect (8549). | |||||||||||||||||||||
| SairIRmPmSensor12Defect | 1.3.6.1.4.1.318.1.1.13.5.3.43.51 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Sensor #12 defect (8550). | |||||||||||||||||||||
| SairIRmPmSensor13Defect | 1.3.6.1.4.1.318.1.1.13.5.3.43.52 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Sensor #13 defect (8551). | |||||||||||||||||||||
| SairIRmPmSensor14Defect | 1.3.6.1.4.1.318.1.1.13.5.3.43.53 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Sensor #14 defect (8552). | |||||||||||||||||||||
| SairIRmPmSensor15Defect | 1.3.6.1.4.1.318.1.1.13.5.3.43.54 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Sensor #15 defect (8553). | |||||||||||||||||||||
| SairIRmPmSensor16Defect | 1.3.6.1.4.1.318.1.1.13.5.3.43.55 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Sensor #16 defect (8554). | |||||||||||||||||||||
| SairIRmPmSensor17Defect | 1.3.6.1.4.1.318.1.1.13.5.3.43.56 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Sensor #17 defect (8555). | |||||||||||||||||||||
| SairIRmPmSensor18Defect | 1.3.6.1.4.1.318.1.1.13.5.3.43.57 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Sensor #18 defect (8556) | |||||||||||||||||||||
| SairIRmPmSensor19Defect | 1.3.6.1.4.1.318.1.1.13.5.3.43.58 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Sensor #19 defect (8557). | |||||||||||||||||||||
| SairIRmPmSensor20Defect | 1.3.6.1.4.1.318.1.1.13.5.3.43.59 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Sensor #20 defect (8558). | |||||||||||||||||||||
| SairIRmPmSensor21Defect | 1.3.6.1.4.1.318.1.1.13.5.3.43.60 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Sensor #21 defect (8559). | |||||||||||||||||||||
| SairIRmPmCompressor1Alarm | 1.3.6.1.4.1.318.1.1.13.5.3.43.61 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Compressor #1 alarm (8560). | |||||||||||||||||||||
| SairIRmPmCompressor2Alarm | 1.3.6.1.4.1.318.1.1.13.5.3.43.62 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Compressor #2 alarm (8561). | |||||||||||||||||||||
| SairIRmPmCompressor1LowPressure | 1.3.6.1.4.1.318.1.1.13.5.3.43.63 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Compressor #1 low pressure (8562). | |||||||||||||||||||||
| SairIRmPmCompressor2LowPressure | 1.3.6.1.4.1.318.1.1.13.5.3.43.64 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Compressor #2 low pressure (8563). | |||||||||||||||||||||
| SairIRmPmReheat1Failure | 1.3.6.1.4.1.318.1.1.13.5.3.43.65 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Reheat #1 failure (8564). | |||||||||||||||||||||
| SairIRmPmReheat2Failure | 1.3.6.1.4.1.318.1.1.13.5.3.43.66 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Reheat #2 failure (8565). | |||||||||||||||||||||
| SairIRmPmReheat3Failure | 1.3.6.1.4.1.318.1.1.13.5.3.43.67 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Reheat #3 failure (8566). | |||||||||||||||||||||
| SairIRmPmReheat4Failure | 1.3.6.1.4.1.318.1.1.13.5.3.43.68 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Reheat #4 failure (8567). | |||||||||||||||||||||
| SairIRmPmDrycooler1Failure | 1.3.6.1.4.1.318.1.1.13.5.3.43.69 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Drycooler #1 failure (8568). | |||||||||||||||||||||
| SairIRmPmDrycooler2Failure | 1.3.6.1.4.1.318.1.1.13.5.3.43.70 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Drycooler #2 failure (8569). | |||||||||||||||||||||
| SairIRmPmDrycooler3Failure | 1.3.6.1.4.1.318.1.1.13.5.3.43.71 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Drycooler #3 failure (8570). | |||||||||||||||||||||
| SairIRmPmDrycooler4Failure | 1.3.6.1.4.1.318.1.1.13.5.3.43.72 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Drycooler #4 failure (8571). | |||||||||||||||||||||
| SairIRmPmPump1Failure | 1.3.6.1.4.1.318.1.1.13.5.3.43.73 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Pump #1 failure (8572). | |||||||||||||||||||||
| SairIRmPmPump2Failure | 1.3.6.1.4.1.318.1.1.13.5.3.43.74 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Pump #2 failure (8573). | |||||||||||||||||||||
| SairIRmPmPump3Failure | 1.3.6.1.4.1.318.1.1.13.5.3.43.75 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Pump #3 failure (8574). | |||||||||||||||||||||
| SairIRmPmPump4Failure | 1.3.6.1.4.1.318.1.1.13.5.3.43.76 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Pump #4 failure (8575). | |||||||||||||||||||||
| SairIRmPmHumidifier1Failure | 1.3.6.1.4.1.318.1.1.13.5.3.43.77 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Humidifier #1 failure (8576). | |||||||||||||||||||||
| SairIRmPmHumidifier2Failure | 1.3.6.1.4.1.318.1.1.13.5.3.43.78 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Humidifier #2 failure (8577). | |||||||||||||||||||||
| SairIRmPmHumidifier3Failure | 1.3.6.1.4.1.318.1.1.13.5.3.43.79 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Humidifier #3 failure (8578). | |||||||||||||||||||||
| SairIRmPmHumidifier1Alarm5us | 1.3.6.1.4.1.318.1.1.13.5.3.43.80 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Humidifier #1 5us alarm (8579). | |||||||||||||||||||||
| SairIRmPmHumidifier2Alarm5us | 1.3.6.1.4.1.318.1.1.13.5.3.43.81 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Humidifier #2 5us alarm (8580). | |||||||||||||||||||||
| SairIRmPmHumidifier3Alarm5us | 1.3.6.1.4.1.318.1.1.13.5.3.43.82 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Humidifier #3 5us alarm (8581). | |||||||||||||||||||||
| SairIRmPmHumidifier1Alarm20us | 1.3.6.1.4.1.318.1.1.13.5.3.43.83 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Humidifier #1 20us alarm (8582). | |||||||||||||||||||||
| SairIRmPmHumidifier2Alarm20us | 1.3.6.1.4.1.318.1.1.13.5.3.43.84 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Humidifier #2 20us alarm (8583). | |||||||||||||||||||||
| SairIRmPmHumidifier3Alarm20us | 1.3.6.1.4.1.318.1.1.13.5.3.43.85 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Humidifier #3 20us alarm (8584). | |||||||||||||||||||||
| SairIRmPmFan1Alarm | 1.3.6.1.4.1.318.1.1.13.5.3.43.86 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Fan #1 alarm (8585). | |||||||||||||||||||||
| SairIRmPmFan2Alarm | 1.3.6.1.4.1.318.1.1.13.5.3.43.87 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Fan #2 alarm (8586). | |||||||||||||||||||||
| SairIRmPmFan3Alarm | 1.3.6.1.4.1.318.1.1.13.5.3.43.88 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Fan #3 alarm (8587). | |||||||||||||||||||||
| SairIRmPmFilter1Clogged | 1.3.6.1.4.1.318.1.1.13.5.3.43.89 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Filter #1 clogged (8588). | |||||||||||||||||||||
| SairIRmPmFilter2Clogged | 1.3.6.1.4.1.318.1.1.13.5.3.43.90 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Filter #2 clogged (8589). | |||||||||||||||||||||
| SairIRmPmFilter3Clogged | 1.3.6.1.4.1.318.1.1.13.5.3.43.91 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Filter #3 clogged (8590). | |||||||||||||||||||||
| SairIRmPmAuxiliaryAlarm1 | 1.3.6.1.4.1.318.1.1.13.5.3.43.92 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Auxiliary #1 alarm (8591). | |||||||||||||||||||||
| SairIRmPmAuxiliaryAlarm2 | 1.3.6.1.4.1.318.1.1.13.5.3.43.93 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Auxiliary #2 alarm (8592). | |||||||||||||||||||||
| SairIRmPmAuxiliaryAlarm3 | 1.3.6.1.4.1.318.1.1.13.5.3.43.94 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Auxiliary #3 alarm (8593). | |||||||||||||||||||||
| SairIRmPmAuxiliaryAlarm4 | 1.3.6.1.4.1.318.1.1.13.5.3.43.95 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Auxiliary #4 alarm (8594). | |||||||||||||||||||||
| SairIRmPmAuxiliaryAlarm5 | 1.3.6.1.4.1.318.1.1.13.5.3.43.96 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Auxiliary #5 alarm (8595). | |||||||||||||||||||||
| SairIRmPmAuxiliaryAlarm6 | 1.3.6.1.4.1.318.1.1.13.5.3.43.97 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Auxiliary #6 alarm (8596). | |||||||||||||||||||||
| SairIRmPmAuxiliaryAlarm7 | 1.3.6.1.4.1.318.1.1.13.5.3.43.98 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Auxiliary #7 alarm (8597). | |||||||||||||||||||||
| SairIRmPmAuxiliaryAlarm8 | 1.3.6.1.4.1.318.1.1.13.5.3.43.99 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Auxiliary #8 alarm (8598). | |||||||||||||||||||||
| SairIRmPmAuxiliaryAlarm9 | 1.3.6.1.4.1.318.1.1.13.5.3.43.100 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Auxiliary #9 alarm (8599). | |||||||||||||||||||||
| SairIRmPmAuxiliaryAlarm10 | 1.3.6.1.4.1.318.1.1.13.5.3.43.101 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Auxiliary #10 alarm (8600). | |||||||||||||||||||||
| SairIRmPmHotGasHeatingAlarm | 1.3.6.1.4.1.318.1.1.13.5.3.43.102 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory Hot gas heating alarm (8601). | |||||||||||||||||||||
| SairIRmPmEEV1PressureSensorError | 1.3.6.1.4.1.318.1.1.13.5.3.43.103 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory EEV1 pressure sensor error (8602). | |||||||||||||||||||||
| SairIRmPmEEV1TemperatureSensorError | 1.3.6.1.4.1.318.1.1.13.5.3.43.104 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory EEV1 temperature sensor error (8603). | |||||||||||||||||||||
| SairIRmPmEEV1StepperMotorError | 1.3.6.1.4.1.318.1.1.13.5.3.43.105 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory EEV1 stepper motor error (8604). | |||||||||||||||||||||
| SairIRmPmEEV2PressureSensorError | 1.3.6.1.4.1.318.1.1.13.5.3.43.106 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory EEV2 pressure sensor error (8605). | |||||||||||||||||||||
| SairIRmPmEEV2TemperatureSensorError | 1.3.6.1.4.1.318.1.1.13.5.3.43.107 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory EEV2 temperature sensor error (8606). | |||||||||||||||||||||
| SairIRmPmEEV2StepperMotorError | 1.3.6.1.4.1.318.1.1.13.5.3.43.108 | AirIRmAlarmState | RO | mandatory | |||||||||||||||||
scalar · AirIRmAlarmState · read-only · mandatory EEV2 stepper motor error (8607). | |||||||||||||||||||||
| NairIRmPmMyZone | 1.3.6.1.4.1.318.1.1.13.5.3.44 | ||||||||||||||||||||
| SairIRmPmMyZoneNumber | 1.3.6.1.4.1.318.1.1.13.5.3.44.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory My zone number (11700). | |||||||||||||||||||||
| NairIRmPmMyZoneRoomTemperature | 1.3.6.1.4.1.318.1.1.13.5.3.44.2 | ||||||||||||||||||||
| SairIRmPmMyZoneRoomTemperatureC | 1.3.6.1.4.1.318.1.1.13.5.3.44.2.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory My zone room temperature in tenths of degrees Celsius (11701). | |||||||||||||||||||||
| SairIRmPmMyZoneRoomTemperatureF | 1.3.6.1.4.1.318.1.1.13.5.3.44.2.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory My zone room temperature in tenths of degrees Fahrenheit (11701). | |||||||||||||||||||||
| SairIRmPmMyZoneRoomHumidity | 1.3.6.1.4.1.318.1.1.13.5.3.44.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory My zone room humidity in tenths of %RH (11702). | |||||||||||||||||||||
| NairIRmPmMyZoneSupplyTemperature | 1.3.6.1.4.1.318.1.1.13.5.3.44.4 | ||||||||||||||||||||
| SairIRmPmMyZoneSupplyTemperatureC | 1.3.6.1.4.1.318.1.1.13.5.3.44.4.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory My zone supply temperature in tenths of degrees Celsius (11703). | |||||||||||||||||||||
| SairIRmPmMyZoneSupplyTemperatureF | 1.3.6.1.4.1.318.1.1.13.5.3.44.4.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory My zone supply temperature in tenths of degrees Fahrenheit (11703). | |||||||||||||||||||||
| SairIRmPmMyZoneSupplyHumidity | 1.3.6.1.4.1.318.1.1.13.5.3.44.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory My zone supply humidity in tenths of %RH (11704). | |||||||||||||||||||||
| SairIRmPmMyZoneSequencingTime | 1.3.6.1.4.1.318.1.1.13.5.3.44.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory My zone sequencing time in minutes (11705). | |||||||||||||||||||||
| SairIRmPmMyZoneNumberOfErrorUnits | 1.3.6.1.4.1.318.1.1.13.5.3.44.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Number of error units in my zone (11706). | |||||||||||||||||||||
| NairIRmPmMyZoneEmergencyTemperature | 1.3.6.1.4.1.318.1.1.13.5.3.44.8 | ||||||||||||||||||||
| SairIRmPmMyZoneEmergencyTemperatureC | 1.3.6.1.4.1.318.1.1.13.5.3.44.8.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory My zone emergency temperature in tenths of degrees Celsius (11707). | |||||||||||||||||||||
| SairIRmPmMyZoneEmergencyTemperatureF | 1.3.6.1.4.1.318.1.1.13.5.3.44.8.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory My zone emergency temperature in tenths of degrees Fahrenheit (11707). | |||||||||||||||||||||
| SairIRmPmMyZoneCWEnergySaveMode | 1.3.6.1.4.1.318.1.1.13.5.3.44.9 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory My zone CW energy save mode (11708). | |||||||||||||||||||||
| NairIRmPmGlobalZoneData | 1.3.6.1.4.1.318.1.1.13.5.3.45 | ||||||||||||||||||||
| SairIRmPmGlobalZoneDataEmergencyOpMode | 1.3.6.1.4.1.318.1.1.13.5.3.45.1 | AirIRmActivityState | RO | mandatory | |||||||||||||||||
scalar · AirIRmActivityState · read-only · mandatory Emergency operation mode (11800). | |||||||||||||||||||||
| NairIRGen3 | 1.3.6.1.4.1.318.1.1.13.6 | ||||||||||||||||||||
| NairIRG3Ident | 1.3.6.1.4.1.318.1.1.13.6.1 | ||||||||||||||||||||
| SairIRG3IdentTableSize | 1.3.6.1.4.1.318.1.1.13.6.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The ident table size. | |||||||||||||||||||||
| TairIRG3IdentTable | 1.3.6.1.4.1.318.1.1.13.6.1.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows to get ident information of current RDU and its assigned CM's. | |||||||||||||||||||||
| RairIRG3IdentEntry | 1.3.6.1.4.1.318.1.1.13.6.1.2.1 | NA | mandatory | ||||||||||||||||||
| CairIRG3IdentIndex | 1.3.6.1.4.1.318.1.1.13.6.1.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Index of ident table. | |||||||||||||||||||||
| CairIRG3IdentName | 1.3.6.1.4.1.318.1.1.13.6.1.2.1.2 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory A character string identifying the unit name. | |||||||||||||||||||||
| CairIRG3IdentLocation | 1.3.6.1.4.1.318.1.1.13.6.1.2.1.3 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory A character string identifying the unit location. | |||||||||||||||||||||
| CairIRG3IdentModelNumber | 1.3.6.1.4.1.318.1.1.13.6.1.2.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory A character string identifying the unit model number. | |||||||||||||||||||||
| CairIRG3IdentSerialNumber | 1.3.6.1.4.1.318.1.1.13.6.1.2.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory A character string identifying the unit serial number. | |||||||||||||||||||||
| CairIRG3IdentFirmwareRevision | 1.3.6.1.4.1.318.1.1.13.6.1.2.1.6 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory A character string identifying the unit firmware version. | |||||||||||||||||||||
| CairIRG3IdentHardwareRevision | 1.3.6.1.4.1.318.1.1.13.6.1.2.1.7 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory A character string identifying the unit controller hardware revision. | |||||||||||||||||||||
| CairIRG3IdentManufactureDate | 1.3.6.1.4.1.318.1.1.13.6.1.2.1.8 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory A character string identifying the unit manufacture date. | |||||||||||||||||||||
| CairIRG3IdentRDUSysOID | 1.3.6.1.4.1.318.1.1.13.6.1.2.1.9 | OBJECT IDENTIFIER | RO | mandatory | |||||||||||||||||
column · OBJECT IDENTIFIER · read-only · mandatory This OID contains an OID path to the RDU data. | |||||||||||||||||||||
| CairIRG3IdentCMSysOID | 1.3.6.1.4.1.318.1.1.13.6.1.2.1.10 | OBJECT IDENTIFIER | RO | mandatory | |||||||||||||||||
column · OBJECT IDENTIFIER · read-only · mandatory This OID contains an OID path to the cooling module data. | |||||||||||||||||||||
| CairIRG3IdentGroupSysOID | 1.3.6.1.4.1.318.1.1.13.6.1.2.1.11 | OBJECT IDENTIFIER | RO | mandatory | |||||||||||||||||
column · OBJECT IDENTIFIER · read-only · mandatory This OID contains an OID path to the group data. | |||||||||||||||||||||
| NairIRG3Group | 1.3.6.1.4.1.318.1.1.13.6.2 | ||||||||||||||||||||
| SairIRG3GroupTableSize | 1.3.6.1.4.1.318.1.1.13.6.2.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The group table size. | |||||||||||||||||||||
| TairIRG3GroupStatusTable | 1.3.6.1.4.1.318.1.1.13.6.2.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows to get group status information. | |||||||||||||||||||||
| RairIRG3GroupStatusEntry | 1.3.6.1.4.1.318.1.1.13.6.2.2.1 | NA | mandatory | ||||||||||||||||||
| CairIRG3GroupStatusIndex | 1.3.6.1.4.1.318.1.1.13.6.2.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Index of group status table. | |||||||||||||||||||||
| CairIRG3GroupStatusCoolOutput | 1.3.6.1.4.1.318.1.1.13.6.2.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The group cooling output in tenths of kilowatts (kW). Returns (-1) if not supported. | |||||||||||||||||||||
| CairIRG3GroupStatusCoolDemand | 1.3.6.1.4.1.318.1.1.13.6.2.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The group cooling demand in tenths of kilowatts (kW). Returns (-1) if not supported. | |||||||||||||||||||||
| CairIRG3GroupStatusAirFlowUS | 1.3.6.1.4.1.318.1.1.13.6.2.2.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The group air flow in cubic feet per minute (CFM). Returns (-1) if not supported. | |||||||||||||||||||||
| CairIRG3GroupStatusAirFlowMetric | 1.3.6.1.4.1.318.1.1.13.6.2.2.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The group air flow in liters per second (L/s). Returns (-1) if not supported. | |||||||||||||||||||||
| CairIRG3GroupStatusMaxRackInletTempUS | 1.3.6.1.4.1.318.1.1.13.6.2.2.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The group maximum rack inlet temperature in tenths of degrees Fahrenheit. Returns (-1) if not supported. | |||||||||||||||||||||
| CairIRG3GroupStatusMaxRackInletTempMetric | 1.3.6.1.4.1.318.1.1.13.6.2.2.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The group maximum rack inlet temperature in tenths of degrees Celsius. Returns (-1) if not supported. | |||||||||||||||||||||
| CairIRG3GroupStatusMinRackInletTempUS | 1.3.6.1.4.1.318.1.1.13.6.2.2.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The group minimum rack inlet temperature in tenths of degrees Fahrenheit. Returns (-1) if not supported. | |||||||||||||||||||||
| CairIRG3GroupStatusMinRackInletTempMetric | 1.3.6.1.4.1.318.1.1.13.6.2.2.1.9 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The group minimum rack inlet temperature in tenths of degrees Celsius. Returns (-1) if not supported. | |||||||||||||||||||||
| CairIRG3GroupStatusMaxReturnAirTempUS | 1.3.6.1.4.1.318.1.1.13.6.2.2.1.10 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The group maximum return air temperature in tenths of degrees Fahrenheit. Returns (-1) if not supported. | |||||||||||||||||||||
| CairIRG3GroupStatusMaxReturnAirTempMetric | 1.3.6.1.4.1.318.1.1.13.6.2.2.1.11 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The group maximum return air temperature in tenths of degrees Celsius. Returns (-1) if not supported. | |||||||||||||||||||||
| CairIRG3GroupStatusMinReturnAirTempUS | 1.3.6.1.4.1.318.1.1.13.6.2.2.1.12 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The group minimum return air temperature in tenths of degrees Fahrenheit. Returns (-1) if not supported. | |||||||||||||||||||||
| CairIRG3GroupStatusMinReturnAirTempMetric | 1.3.6.1.4.1.318.1.1.13.6.2.2.1.13 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The group minimum return air temperature in tenths of degrees Celsius. Returns (-1) if not supported. | |||||||||||||||||||||
| CairIRG3GroupStatusAvgSupplyTempUS | 1.3.6.1.4.1.318.1.1.13.6.2.2.1.14 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The group average supply air temperature in tenths of degrees Fahrenheit. Returns (-1) if not supported. | |||||||||||||||||||||
| CairIRG3GroupStatusAvgSupplyTempMetric | 1.3.6.1.4.1.318.1.1.13.6.2.2.1.15 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The group average supply air temperature in tenths of degrees Celsius. Returns (-1) if not supported. | |||||||||||||||||||||
| CairIRG3GroupStatusAvgReturnTempUS | 1.3.6.1.4.1.318.1.1.13.6.2.2.1.16 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The group average return air temperature in tenths of degrees Fahrenheit. Returns (-1) if not supported. | |||||||||||||||||||||
| CairIRG3GroupStatusAvgReturnTempMetric | 1.3.6.1.4.1.318.1.1.13.6.2.2.1.17 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The group average return air temperature in tenths of degrees Celsius. Returns (-1) if not supported. | |||||||||||||||||||||
| CairIRG3GroupStatusAvgFanSpeed | 1.3.6.1.4.1.318.1.1.13.6.2.2.1.18 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The group average fan speed in revolutions per minute (RPM). Returns (-1) if not supported. | |||||||||||||||||||||
| CairIRG3GroupStatusAvgAirFlowUS | 1.3.6.1.4.1.318.1.1.13.6.2.2.1.19 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The group average air flow in cubic feet per minute (CFM). Returns (-1) if not supported. | |||||||||||||||||||||
| CairIRG3GroupStatusAvgAirFlowMetric | 1.3.6.1.4.1.318.1.1.13.6.2.2.1.20 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The group average air flow in liters per second (L/s). Returns (-1) if not supported. | |||||||||||||||||||||
| CairIRG3GroupStatusTotalAirFlowUS | 1.3.6.1.4.1.318.1.1.13.6.2.2.1.21 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The group total air flow in cubic feet per minute (CFM). Returns (-1) if not supported. | |||||||||||||||||||||
| CairIRG3GroupStatusTotalAirFlowMetric | 1.3.6.1.4.1.318.1.1.13.6.2.2.1.22 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The group total air flow in liters per second (L/s). Returns (-1) if not supported. | |||||||||||||||||||||
| TairIRG3GroupSetpointsTable | 1.3.6.1.4.1.318.1.1.13.6.2.3 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows to access the group setpoints. | |||||||||||||||||||||
| RairIRG3GroupSetpointsEntry | 1.3.6.1.4.1.318.1.1.13.6.2.3.1 | NA | mandatory | ||||||||||||||||||
| CairIRG3GroupSetpointsIndex | 1.3.6.1.4.1.318.1.1.13.6.2.3.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Index of group setpoints table. | |||||||||||||||||||||
| CairIRG3GroupSetpointsCoolSetpointUS | 1.3.6.1.4.1.318.1.1.13.6.2.3.1.2 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Group cooling setpoint in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| CairIRG3GroupSetpointsCoolSetpointMetric | 1.3.6.1.4.1.318.1.1.13.6.2.3.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Group cooling setpoint in tenths of degrees Celsius. | |||||||||||||||||||||
| CairIRG3GroupSetpointsCoolDeadbandUS | 1.3.6.1.4.1.318.1.1.13.6.2.3.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Group cooling deadband in tenths of degrees Fahrenheit. Returns (-1) if not supported. | |||||||||||||||||||||
| CairIRG3GroupSetpointsCoolDeadbandMetric | 1.3.6.1.4.1.318.1.1.13.6.2.3.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Group cooling deadband in tenths of degrees Celsius. Returns (-1) if not supported. | |||||||||||||||||||||
| CairIRG3GroupSetpointsFanSpeedPreference | 1.3.6.1.4.1.318.1.1.13.6.2.3.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The group preferred fan speed setting.
| |||||||||||||||||||||
| CairIRG3GroupSetpointsSupplyAirSetpointUS | 1.3.6.1.4.1.318.1.1.13.6.2.3.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Group supply air setpoint in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| CairIRG3GroupSetpointsSupplyAirSetpointMetric | 1.3.6.1.4.1.318.1.1.13.6.2.3.1.8 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Group supply air setpoint in tenths of degrees Celsius. | |||||||||||||||||||||
| CairIRG3GroupSetpointsAirFlowControl | 1.3.6.1.4.1.318.1.1.13.6.2.3.1.9 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The group air flow control.
| |||||||||||||||||||||
| CairIRG3GroupSetpointsLightingOnTime | 1.3.6.1.4.1.318.1.1.13.6.2.3.1.10 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The group lighting on time in minutes. | |||||||||||||||||||||
| TairIRG3GroupConfigTable | 1.3.6.1.4.1.318.1.1.13.6.2.4 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows to access group configuration table. | |||||||||||||||||||||
| RairIRG3GroupConfigEntry | 1.3.6.1.4.1.318.1.1.13.6.2.4.1 | NA | mandatory | ||||||||||||||||||
| CairIRG3GroupConfigIndex | 1.3.6.1.4.1.318.1.1.13.6.2.4.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Index of group config table. | |||||||||||||||||||||
| CairIRG3GroupConfigNumberofCoolingUnits | 1.3.6.1.4.1.318.1.1.13.6.2.4.1.2 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The number of cooling units. | |||||||||||||||||||||
| CairIRG3GroupConfigConfigurationType | 1.3.6.1.4.1.318.1.1.13.6.2.4.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The group configuration type. The spot configuration type is not supported. Returns (-1) if not supported.
| |||||||||||||||||||||
| CairIRG3GroupConfigCapacityControlType | 1.3.6.1.4.1.318.1.1.13.6.2.4.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The group capacity control. Returns (-1) if not supported.
| |||||||||||||||||||||
| CairIRG3GroupConfigFanSpeedControl | 1.3.6.1.4.1.318.1.1.13.6.2.4.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The group fan speed control.
| |||||||||||||||||||||
| CairIRG3GroupConfigCoolGainP | 1.3.6.1.4.1.318.1.1.13.6.2.4.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The gain component of the PID in hundredths. | |||||||||||||||||||||
| CairIRG3GroupConfigCoolResetRateI | 1.3.6.1.4.1.318.1.1.13.6.2.4.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The integral component of the PID in hundredths. | |||||||||||||||||||||
| CairIRG3GroupConfigCoolDerivativeD | 1.3.6.1.4.1.318.1.1.13.6.2.4.1.8 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The derivative component of the PID in hundredths. | |||||||||||||||||||||
| CairIRG3GroupConfigCoolPIDReset | 1.3.6.1.4.1.318.1.1.13.6.2.4.1.9 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Will reset the PID coefficients back to the factory defaults. Readback is not supported, returns -1.
| |||||||||||||||||||||
| CairIRG3GroupConfigNumberofBackupUnits | 1.3.6.1.4.1.318.1.1.13.6.2.4.1.10 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The number of backup units. | |||||||||||||||||||||
| CairIRG3GroupConfigRuntimeBalancingEnable | 1.3.6.1.4.1.318.1.1.13.6.2.4.1.11 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Enable or disable runtime balancing feature.
| |||||||||||||||||||||
| CairIRG3GroupConfigLoadAssistEnable | 1.3.6.1.4.1.318.1.1.13.6.2.4.1.12 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Enable or disable load assist feature.
| |||||||||||||||||||||
| NairIRG3Alarms | 1.3.6.1.4.1.318.1.1.13.6.3 | ||||||||||||||||||||
| SairIRG3AlarmsTableSize | 1.3.6.1.4.1.318.1.1.13.6.3.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of active alarms in the airIRG3AlarmsTable. | |||||||||||||||||||||
| TairIRG3AlarmsTable | 1.3.6.1.4.1.318.1.1.13.6.3.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Table of active alarms for the device. | |||||||||||||||||||||
| RairIRG3AlarmsEntry | 1.3.6.1.4.1.318.1.1.13.6.3.2.1 | NA | mandatory | ||||||||||||||||||
| CairIRG3AlarmsIndex | 1.3.6.1.4.1.318.1.1.13.6.3.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Alarm index. | |||||||||||||||||||||
| CairIRG3AlarmsEventCode | 1.3.6.1.4.1.318.1.1.13.6.3.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Event Code for the alarm. Returns (-1) if not supported. | |||||||||||||||||||||
| CairIRG3AlarmsDescription | 1.3.6.1.4.1.318.1.1.13.6.3.2.1.3 | DisplayString (SIZE (0..64)) | RO | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..64)) · read-only · mandatory Description of the alarm. Returns (-1) if not supported. | |||||||||||||||||||||
| NairIRG3RDU | 1.3.6.1.4.1.318.1.1.13.6.4 | ||||||||||||||||||||
| SairIRG3RDUTableSize | 1.3.6.1.4.1.318.1.1.13.6.4.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The RDU table size. | |||||||||||||||||||||
| TairIRG3RDUStatusTable | 1.3.6.1.4.1.318.1.1.13.6.4.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows to access RDU status table. | |||||||||||||||||||||
| RairIRG3RDUStatusEntry | 1.3.6.1.4.1.318.1.1.13.6.4.2.1 | NA | mandatory | ||||||||||||||||||
| CairIRG3RDUStatusDeviceIndex | 1.3.6.1.4.1.318.1.1.13.6.4.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Index of RDU status table. | |||||||||||||||||||||
| CairIRG3RDUID | 1.3.6.1.4.1.318.1.1.13.6.4.2.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The current RDU ID (1 to F). Configured RDU only shall display ID, else return -1. | |||||||||||||||||||||
| CairIRG3RDUStatusOnReadyStandby | 1.3.6.1.4.1.318.1.1.13.6.4.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The RDU current status.
| |||||||||||||||||||||
| CairIRG3RDUStatusOperatingMode | 1.3.6.1.4.1.318.1.1.13.6.4.2.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The RDU actual operating mode.
| |||||||||||||||||||||
| CairIRG3RDUStatusLeadPump | 1.3.6.1.4.1.318.1.1.13.6.4.2.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The RDU lead pump.
| |||||||||||||||||||||
| CairIRG3RDUStatusStartupDelay | 1.3.6.1.4.1.318.1.1.13.6.4.2.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The RDU start up delay in seconds. | |||||||||||||||||||||
| CairIRG3RDUStatusPumpChangeOverInterval | 1.3.6.1.4.1.318.1.1.13.6.4.2.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The RDU pump change over interval in days. | |||||||||||||||||||||
| CairIRG3RDUStatusStopOnLeakDetect | 1.3.6.1.4.1.318.1.1.13.6.4.2.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The RDU status of stop on leak detect.
| |||||||||||||||||||||
| CairIRG3RDUStatusPowerSource | 1.3.6.1.4.1.318.1.1.13.6.4.2.1.9 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The RDU power source status.
| |||||||||||||||||||||
| CairIRG3RDUStatusTotalRDUOutputPower | 1.3.6.1.4.1.318.1.1.13.6.4.2.1.10 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The RDU output power in tenths of kilowatts (kW). | |||||||||||||||||||||
| CairIRG3RDUStatusInletWaterTempUS | 1.3.6.1.4.1.318.1.1.13.6.4.2.1.11 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The RDU inlet water temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| CairIRG3RDUStatusInletWaterTempMetric | 1.3.6.1.4.1.318.1.1.13.6.4.2.1.12 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The RDU inlet water temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| CairIRG3RDUStatusOutletWaterTempUS | 1.3.6.1.4.1.318.1.1.13.6.4.2.1.13 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The RDU outlet water temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| CairIRG3RDUStatusOutletWaterTempMetric | 1.3.6.1.4.1.318.1.1.13.6.4.2.1.14 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The RDU outlet water temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| CairIRG3RDUStatusCondenserSaturationTempUS | 1.3.6.1.4.1.318.1.1.13.6.4.2.1.15 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The RDU condenser saturation temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| CairIRG3RDUStatusCondenserSaturationTempMetric | 1.3.6.1.4.1.318.1.1.13.6.4.2.1.16 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The RDU condenser saturation temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| CairIRG3RDUStatusDewPointTempUS | 1.3.6.1.4.1.318.1.1.13.6.4.2.1.17 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The RDU dew point temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| CairIRG3RDUStatusDewPointTempMetric | 1.3.6.1.4.1.318.1.1.13.6.4.2.1.18 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The RDU dew point temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| CairIRG3RDUStatusPumpOutletTempUS | 1.3.6.1.4.1.318.1.1.13.6.4.2.1.19 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The RDU pump outlet temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| CairIRG3RDUStatusPumpOutletTempMetric | 1.3.6.1.4.1.318.1.1.13.6.4.2.1.20 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The RDU pump outlet temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| CairIRG3RDUStatusSubcoolerOutletTempUS | 1.3.6.1.4.1.318.1.1.13.6.4.2.1.21 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The RDU sub cooler outlet temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| CairIRG3RDUStatusSubcoolerOutletTempMetric | 1.3.6.1.4.1.318.1.1.13.6.4.2.1.22 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The RDU sub cooler outlet temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| CairIRG3RDUStatusCondenserOutletTempUS | 1.3.6.1.4.1.318.1.1.13.6.4.2.1.23 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The RDU condenser outlet temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| CairIRG3RDUStatusCondenserOutletTempMetric | 1.3.6.1.4.1.318.1.1.13.6.4.2.1.24 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The RDU condenser outlet temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| CairIRG3RDUStatusCondenserInletTempUS | 1.3.6.1.4.1.318.1.1.13.6.4.2.1.25 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The RDU condenser inlet temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| CairIRG3RDUStatusCondenserInletTempMetric | 1.3.6.1.4.1.318.1.1.13.6.4.2.1.26 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The RDU condenser inlet temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| CairIRG3RDUStatusCondenserOutletPressureUS | 1.3.6.1.4.1.318.1.1.13.6.4.2.1.27 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The RDU condenser outlet pressure in pounds per square inch (PSI). | |||||||||||||||||||||
| CairIRG3RDUStatusCondenserOutletPressureMetric | 1.3.6.1.4.1.318.1.1.13.6.4.2.1.28 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The RDU condenser outlet pressure in kiloPascals (KPa). | |||||||||||||||||||||
| CairIRG3RDUStatusPump1HeadPressureUS | 1.3.6.1.4.1.318.1.1.13.6.4.2.1.29 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The RDU Pump 1 head pressure in pounds per square inch (PSI). | |||||||||||||||||||||
| CairIRG3RDUStatusPump1HeadPressureMetric | 1.3.6.1.4.1.318.1.1.13.6.4.2.1.30 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The RDU Pump 1 head pressure in kiloPascals (KPa). | |||||||||||||||||||||
| CairIRG3RDUStatusPump2HeadPressureUS | 1.3.6.1.4.1.318.1.1.13.6.4.2.1.31 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The RDU Pump 2 head pressure in pounds per square inch (PSI). | |||||||||||||||||||||
| CairIRG3RDUStatusPump2HeadPressureMetric | 1.3.6.1.4.1.318.1.1.13.6.4.2.1.32 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The RDU Pump 2 head pressure in kiloPascals (KPa). | |||||||||||||||||||||
| CairIRG3RDUStatusPump1Speed | 1.3.6.1.4.1.318.1.1.13.6.4.2.1.33 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The RDU Pump 1 speed in revolutions per minute (RPM). | |||||||||||||||||||||
| CairIRG3RDUStatusPump2Speed | 1.3.6.1.4.1.318.1.1.13.6.4.2.1.34 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The RDU Pump 2 speed in revolutions per minute (RPM). | |||||||||||||||||||||
| CairIRG3RDUStatusCWValvePosition | 1.3.6.1.4.1.318.1.1.13.6.4.2.1.35 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The RDU CW Valve position in % open | |||||||||||||||||||||
| CairIRG3RDUStatusReceiverLiquidLevel | 1.3.6.1.4.1.318.1.1.13.6.4.2.1.36 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The RDU receiver liquid level in % Full | |||||||||||||||||||||
| CairIRG3RDUStatusDCPowerSupply1Current | 1.3.6.1.4.1.318.1.1.13.6.4.2.1.37 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The RDU DC Power Supply 1 Current in Amps | |||||||||||||||||||||
| CairIRG3RDUStatusDCPowerSupply2Current | 1.3.6.1.4.1.318.1.1.13.6.4.2.1.38 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The RDU DC Power Supply 2 Current in Amps | |||||||||||||||||||||
| CairIRG3RDUStatusTotalDCPowerSupplyCurrent | 1.3.6.1.4.1.318.1.1.13.6.4.2.1.39 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The RDU Total DC Power Supply Current in Amps | |||||||||||||||||||||
| CairIRG3RDUStatusInputState | 1.3.6.1.4.1.318.1.1.13.6.4.2.1.40 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The RDU Input state.
| |||||||||||||||||||||
| CairIRG3RDUStatusOutputState | 1.3.6.1.4.1.318.1.1.13.6.4.2.1.41 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The RDU Output state
| |||||||||||||||||||||
| CairIRG3RDUStatusByPassValvePosition | 1.3.6.1.4.1.318.1.1.13.6.4.2.1.42 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The RDU By Pass Valve position in % open | |||||||||||||||||||||
| CairIRG3RDUStatusRefrigerantLeakDetector | 1.3.6.1.4.1.318.1.1.13.6.4.2.1.43 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The RDU refrigerant leak detector status.
| |||||||||||||||||||||
| TairIRG3RDURunHoursTable | 1.3.6.1.4.1.318.1.1.13.6.4.3 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows to access RDU run hours table. | |||||||||||||||||||||
| RairIRG3RDURunHoursEntry | 1.3.6.1.4.1.318.1.1.13.6.4.3.1 | NA | mandatory | ||||||||||||||||||
| CairIRG3RDURunHoursDeviceIndex | 1.3.6.1.4.1.318.1.1.13.6.4.3.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Index of RDU run hours table. | |||||||||||||||||||||
| CairIRG3RDURunHoursRDUID | 1.3.6.1.4.1.318.1.1.13.6.4.3.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The current RDU ID (1 to F). Configured RDU only shall display ID, else return -1. | |||||||||||||||||||||
| CairIRG3RDURunHoursPump1 | 1.3.6.1.4.1.318.1.1.13.6.4.3.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The RDU run hours of Pump 1. | |||||||||||||||||||||
| CairIRG3RDURunHoursPump2 | 1.3.6.1.4.1.318.1.1.13.6.4.3.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The RDU run hours of Pump 2. | |||||||||||||||||||||
| CairIRG3RDURunHoursPowerSupply1 | 1.3.6.1.4.1.318.1.1.13.6.4.3.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The RDU run hours of power supply 1. | |||||||||||||||||||||
| CairIRG3RDURunHoursPowerSupply2 | 1.3.6.1.4.1.318.1.1.13.6.4.3.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The RDU run hours of power supply 2. | |||||||||||||||||||||
| TairIRG3RDUServiceIntervalsTable | 1.3.6.1.4.1.318.1.1.13.6.4.4 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows to access RDU service intervals table. | |||||||||||||||||||||
| RairIRG3RDUServiceIntervalsEntry | 1.3.6.1.4.1.318.1.1.13.6.4.4.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The service interval table entry. | |||||||||||||||||||||
| CairIRG3RDUServiceIntervalsDeviceIndex | 1.3.6.1.4.1.318.1.1.13.6.4.4.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Index of service interval table. | |||||||||||||||||||||
| CairIRG3RDUServiceIntervalsRDUID | 1.3.6.1.4.1.318.1.1.13.6.4.4.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The current RDU ID (1 to F). Configured RDU only shall display ID, else return -1. | |||||||||||||||||||||
| CairIRG3RDUServiceIntervalsAirFilterInterval | 1.3.6.1.4.1.318.1.1.13.6.4.4.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The RDU service interval for air filter in hours. Returns -1 if not supported. | |||||||||||||||||||||
| CairIRG3RDUServiceIntervalsAirFilterAlarm | 1.3.6.1.4.1.318.1.1.13.6.4.4.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The RDU service interval air filter alarm status. Returns -1 if not supported.
| |||||||||||||||||||||
| TairIRG3RDUThresholdsTable | 1.3.6.1.4.1.318.1.1.13.6.4.5 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows to access RDU thresholds table. | |||||||||||||||||||||
| RairIRG3RDUThresholdsEntry | 1.3.6.1.4.1.318.1.1.13.6.4.5.1 | NA | mandatory | ||||||||||||||||||
| CairIRG3RDUThresholdsDeviceIndex | 1.3.6.1.4.1.318.1.1.13.6.4.5.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Index of RDU thresholds table. | |||||||||||||||||||||
| CairIRG3RDUThresholdsRDUID | 1.3.6.1.4.1.318.1.1.13.6.4.5.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The current RDU ID (1 to F). Configured RDU only shall display ID, else return -1. | |||||||||||||||||||||
| CairIRG3RDUThresholdsEnteringFluidTempHighUS | 1.3.6.1.4.1.318.1.1.13.6.4.5.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The RDU threshold for entering fluid temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| CairIRG3RDUThresholdsEnteringFluidTempHighMetric | 1.3.6.1.4.1.318.1.1.13.6.4.5.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The RDU threshold for entering fluid temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| TairIRG3RDUSetpointsTable | 1.3.6.1.4.1.318.1.1.13.6.4.6 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows to access RDU set points table. | |||||||||||||||||||||
| RairIRG3RDUSetpointsEntry | 1.3.6.1.4.1.318.1.1.13.6.4.6.1 | NA | mandatory | ||||||||||||||||||
| CairIRG3RDUSetpointsDeviceIndex | 1.3.6.1.4.1.318.1.1.13.6.4.6.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Index of RDU set points table. | |||||||||||||||||||||
| TairIRG3RDUConfigTable | 1.3.6.1.4.1.318.1.1.13.6.4.7 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows to access RDU configuration table. | |||||||||||||||||||||
| RairIRG3RDUConfigEntry | 1.3.6.1.4.1.318.1.1.13.6.4.7.1 | NA | mandatory | ||||||||||||||||||
| CairIRG3RDUConfigDeviceIndex | 1.3.6.1.4.1.318.1.1.13.6.4.7.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Index of RDU configuration table. | |||||||||||||||||||||
| CairIRG3RDUConfigRDUID | 1.3.6.1.4.1.318.1.1.13.6.4.7.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The current RDU ID (1 to F). Configured RDU only shall display ID, else return -1. | |||||||||||||||||||||
| CairIRG3RDUConfigStopOnLeakDetect | 1.3.6.1.4.1.318.1.1.13.6.4.7.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The RDU stop on leak detect set.
| |||||||||||||||||||||
| CairIRG3RDUConfigStartupDelay | 1.3.6.1.4.1.318.1.1.13.6.4.7.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The RDU start up delay in seconds. | |||||||||||||||||||||
| CairIRG3RDUConfigPumpChangeOverInterval | 1.3.6.1.4.1.318.1.1.13.6.4.7.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The RDU pump change over interval in days. | |||||||||||||||||||||
| CairIRG3RDUConfigPowerSource | 1.3.6.1.4.1.318.1.1.13.6.4.7.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The RDU power source.
| |||||||||||||||||||||
| CairIRG3RDUConfigOutputSource | 1.3.6.1.4.1.318.1.1.13.6.4.7.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The RDU output source.
| |||||||||||||||||||||
| CairIRG3RDUConfigInputNormalState | 1.3.6.1.4.1.318.1.1.13.6.4.7.1.8 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The RDU Input Normal State.
| |||||||||||||||||||||
| CairIRG3RDUConfigOutputNormalState | 1.3.6.1.4.1.318.1.1.13.6.4.7.1.9 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The RDU Output Normal State.
| |||||||||||||||||||||
| CairIRG3RDUConfigByPassValveEnabled | 1.3.6.1.4.1.318.1.1.13.6.4.7.1.10 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The RDU By Pass Valve Enabled State.
| |||||||||||||||||||||
| CairIRG3RDUConfigRefrigerantLeakDetectorEnabled | 1.3.6.1.4.1.318.1.1.13.6.4.7.1.11 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The RDU Refrigerant Leak Detector Enabled State.
| |||||||||||||||||||||
| CairIRG3RDUConfigCalibrateRefrigerantLeakDetector | 1.3.6.1.4.1.318.1.1.13.6.4.7.1.12 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory This parameter allows to calibrate the RDU Refrigerant Leak Detector and is write only. The read returns -1. Only 'yes' is supported.
| |||||||||||||||||||||
| CairIRG3RDUConfigOnReadyStandby | 1.3.6.1.4.1.318.1.1.13.6.4.7.1.13 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory This parameter allows to configure RDU on/standby parameter. Ready is currently not supported. If unsupported returns -1.
| |||||||||||||||||||||
| NairIRG3CM | 1.3.6.1.4.1.318.1.1.13.6.5 | ||||||||||||||||||||
| SairIRG3CMTableSize | 1.3.6.1.4.1.318.1.1.13.6.5.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The cooling module table size. | |||||||||||||||||||||
| TairIRG3CMStatusTable | 1.3.6.1.4.1.318.1.1.13.6.5.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows to access CM status table. | |||||||||||||||||||||
| RairIRG3CMStatusEntry | 1.3.6.1.4.1.318.1.1.13.6.5.2.1 | NA | mandatory | ||||||||||||||||||
| CairIRG3CMStatusDeviceIndex | 1.3.6.1.4.1.318.1.1.13.6.5.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Index of CM status table. | |||||||||||||||||||||
| CairIRG3CMStatusCMID | 1.3.6.1.4.1.318.1.1.13.6.5.2.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The CM ID (RDU Number - Group Number - CM Unit Number). | |||||||||||||||||||||
| CairIRG3CMStatusOperatingMode | 1.3.6.1.4.1.318.1.1.13.6.5.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The current operating mode of the CM.
| |||||||||||||||||||||
| CairIRG3CMStatusUnitType | 1.3.6.1.4.1.318.1.1.13.6.5.2.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The current CM unit type.
| |||||||||||||||||||||
| CairIRG3CMStatusRackInletTempUS | 1.3.6.1.4.1.318.1.1.13.6.5.2.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The CM rack inlet temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| CairIRG3CMStatusRackInletTempMetric | 1.3.6.1.4.1.318.1.1.13.6.5.2.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The CM rack inlet temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| CairIRG3CMStatusReturnAirTempUS | 1.3.6.1.4.1.318.1.1.13.6.5.2.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The CM return air temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| CairIRG3CMStatusReturnAirTempMetric | 1.3.6.1.4.1.318.1.1.13.6.5.2.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The CM return air temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| CairIRG3CMStatusLiquidTempUS | 1.3.6.1.4.1.318.1.1.13.6.5.2.1.9 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The CM liquid temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| CairIRG3CMStatusLiquidTempMetric | 1.3.6.1.4.1.318.1.1.13.6.5.2.1.10 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The CM liquid temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| CairIRG3CMStatusVaporTempUS | 1.3.6.1.4.1.318.1.1.13.6.5.2.1.11 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The CM vapor temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| CairIRG3CMStatusVaporTempMetric | 1.3.6.1.4.1.318.1.1.13.6.5.2.1.12 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The CM vapor temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| CairIRG3CMStatusEvaporatorTempUS | 1.3.6.1.4.1.318.1.1.13.6.5.2.1.13 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The CM saturation temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| CairIRG3CMStatusEvaporatorTempMetric | 1.3.6.1.4.1.318.1.1.13.6.5.2.1.14 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The CM saturation temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| CairIRG3CMStatusLiquidInletPressureUS | 1.3.6.1.4.1.318.1.1.13.6.5.2.1.15 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The CM Liquid Inlet pressure in pounds per square inch (PSI). | |||||||||||||||||||||
| CairIRG3CMStatusLiquidInletPressureMetric | 1.3.6.1.4.1.318.1.1.13.6.5.2.1.16 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The CM Liquid Inlet pressure in kiloPascals (kPa). | |||||||||||||||||||||
| CairIRG3CMStatusVaporOutletPressureUS | 1.3.6.1.4.1.318.1.1.13.6.5.2.1.17 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The CM Vapor Outlet pressure in pounds per square inch (PSI). | |||||||||||||||||||||
| CairIRG3CMStatusVaporOutletPressureMetric | 1.3.6.1.4.1.318.1.1.13.6.5.2.1.18 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The CM Vapor Outlet pressure in kiloPascals (kPa). | |||||||||||||||||||||
| CairIRG3CMStatusExpansionValvePosition | 1.3.6.1.4.1.318.1.1.13.6.5.2.1.19 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The CM expansion valve position in % open | |||||||||||||||||||||
| CairIRG3CMStatusEPRValvePosition | 1.3.6.1.4.1.318.1.1.13.6.5.2.1.20 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The CM Evaporator Pressure Regulator Valve Position in tenths of percent open | |||||||||||||||||||||
| CairIRG3CMStatusLocalDisplayOnOffEnabled | 1.3.6.1.4.1.318.1.1.13.6.5.2.1.21 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The status of the on/off control on the CM local display.
| |||||||||||||||||||||
| CairIRG3CMStatusAverageFanSpeed | 1.3.6.1.4.1.318.1.1.13.6.5.2.1.22 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The CM Average Fan Speed. | |||||||||||||||||||||
| TairIRG3CMRunHoursTable | 1.3.6.1.4.1.318.1.1.13.6.5.3 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows to access CM run hours table. | |||||||||||||||||||||
| RairIRG3CMRunHoursEntry | 1.3.6.1.4.1.318.1.1.13.6.5.3.1 | NA | mandatory | ||||||||||||||||||
| CairIRG3CMRunHoursDeviceIndex | 1.3.6.1.4.1.318.1.1.13.6.5.3.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Index of CM run hours table. | |||||||||||||||||||||
| CairIRG3CMRunHoursCMID | 1.3.6.1.4.1.318.1.1.13.6.5.3.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The CM ID (RDU Number - Group Number - CM Unit Number). | |||||||||||||||||||||
| CairIRG3CMRunHoursFan1 | 1.3.6.1.4.1.318.1.1.13.6.5.3.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The CM run hours for Fan1. Returns (-1) if not appilcable. | |||||||||||||||||||||
| CairIRG3CMRunHoursFan2 | 1.3.6.1.4.1.318.1.1.13.6.5.3.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The CM run hours for Fan2. Returns (-1) if not appilcable. | |||||||||||||||||||||
| CairIRG3CMRunHoursFan3 | 1.3.6.1.4.1.318.1.1.13.6.5.3.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The CM run hours for Fan3. Returns (-1) if not appilcable. | |||||||||||||||||||||
| CairIRG3CMRunHoursFan4 | 1.3.6.1.4.1.318.1.1.13.6.5.3.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The CM run hours for Fan4. Returns (-1) if not appilcable. | |||||||||||||||||||||
| CairIRG3CMRunHoursFan5 | 1.3.6.1.4.1.318.1.1.13.6.5.3.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The CM run hours for Fan5. Returns (-1) if not appilcable. | |||||||||||||||||||||
| CairIRG3CMRunHoursAirFilter | 1.3.6.1.4.1.318.1.1.13.6.5.3.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The CM run hours for air filter. | |||||||||||||||||||||
| TairIRG3CMServiceIntervalsTable | 1.3.6.1.4.1.318.1.1.13.6.5.4 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows to access CM service intervals table. | |||||||||||||||||||||
| RairIRG3CMServiceIntervalsEntry | 1.3.6.1.4.1.318.1.1.13.6.5.4.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The CM service interval table entry. | |||||||||||||||||||||
| CairIRG3CMServiceIntervalsDeviceIndex | 1.3.6.1.4.1.318.1.1.13.6.5.4.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Index of CM service intervals table. | |||||||||||||||||||||
| CairIRG3CMServiceIntervalsCMID | 1.3.6.1.4.1.318.1.1.13.6.5.4.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The CM ID (RDU Number - Group Number - CM Unit Number). | |||||||||||||||||||||
| CairIRG3CMServiceIntervalsAirFilterInterval | 1.3.6.1.4.1.318.1.1.13.6.5.4.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The CM service interval for air filter in weeks. Supported only for RA. Returns -1 if not supported. | |||||||||||||||||||||
| CairIRG3CMServiceIntervalsAirFilterAlarm | 1.3.6.1.4.1.318.1.1.13.6.5.4.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The CM service interval air filter alarm status. Supported only for RA. Returns -1 if not supported.
| |||||||||||||||||||||
| TairIRG3CMThresholdsTable | 1.3.6.1.4.1.318.1.1.13.6.5.5 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows to access CM thresholds table. | |||||||||||||||||||||
| RairIRG3CMThresholdsEntry | 1.3.6.1.4.1.318.1.1.13.6.5.5.1 | NA | mandatory | ||||||||||||||||||
| CairIRG3CMThresholdsDeviceIndex | 1.3.6.1.4.1.318.1.1.13.6.5.5.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Index for CM thresholds table. | |||||||||||||||||||||
| CairIRG3CMThresholdsCMID | 1.3.6.1.4.1.318.1.1.13.6.5.5.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The CM ID (RDU Number - Group Number - CM Unit Number). | |||||||||||||||||||||
| CairIRG3CMThresholdsRackInletTempHighUS | 1.3.6.1.4.1.318.1.1.13.6.5.5.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The CM high threshold for rack inlet temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| CairIRG3CMThresholdsRackInletTempHighMetric | 1.3.6.1.4.1.318.1.1.13.6.5.5.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The CM high threshold for rack inlet temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| CairIRG3CMThresholdsSupplyAirTempHighUS | 1.3.6.1.4.1.318.1.1.13.6.5.5.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The CM high threshold for supply air temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| CairIRG3CMThresholdsSupplyAirTempHighMetric | 1.3.6.1.4.1.318.1.1.13.6.5.5.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The CM high threshold for supply air temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| CairIRG3CMThresholdsReturnAirTempHighUS | 1.3.6.1.4.1.318.1.1.13.6.5.5.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The CM high threshold for return air temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| CairIRG3CMThresholdsReturnAirTempHighMetric | 1.3.6.1.4.1.318.1.1.13.6.5.5.1.8 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The CM high threshold for return air temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| TairIRG3CMSetpointsTable | 1.3.6.1.4.1.318.1.1.13.6.5.6 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows to access CM set points table. | |||||||||||||||||||||
| RairIRG3CMSetpointsEntry | 1.3.6.1.4.1.318.1.1.13.6.5.6.1 | NA | mandatory | ||||||||||||||||||
| CairIRG3CMSetpointsDeviceIndex | 1.3.6.1.4.1.318.1.1.13.6.5.6.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Index of CM set points table. | |||||||||||||||||||||
| TairIRG3CMConfigTable | 1.3.6.1.4.1.318.1.1.13.6.5.7 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows to access CM configuration table. | |||||||||||||||||||||
| RairIRG3CMConfigEntry | 1.3.6.1.4.1.318.1.1.13.6.5.7.1 | NA | mandatory | ||||||||||||||||||
| CairIRG3CMConfigDeviceIndex | 1.3.6.1.4.1.318.1.1.13.6.5.7.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Index of CM configuration table. | |||||||||||||||||||||
| CairIRG3CMConfigCMID | 1.3.6.1.4.1.318.1.1.13.6.5.7.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The CM ID (RDU Number - Group Number - CM Unit Number). | |||||||||||||||||||||
| CairIRG3CMConfigStopOnCoolFail | 1.3.6.1.4.1.318.1.1.13.6.5.7.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Enable/Disable Stop On cool fail. When enabled, stops the unit if it detects that it is blowing warm air into the cold aisle.
| |||||||||||||||||||||
| CairIRG3CMConfigStartupDelay | 1.3.6.1.4.1.318.1.1.13.6.5.7.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The CM start up delay in seconds. | |||||||||||||||||||||
| CairIRG3CMConfigRemoteOnStandby | 1.3.6.1.4.1.318.1.1.13.6.5.7.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The CM configuration for operating mode.
| |||||||||||||||||||||
| CairIRG3CMConfigPowerSource | 1.3.6.1.4.1.318.1.1.13.6.5.7.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The CM power source.
| |||||||||||||||||||||
| NrARU | 1.3.6.1.4.1.318.1.1.14 | ||||||||||||||||||||
| NrARUIdent | 1.3.6.1.4.1.318.1.1.14.1 | ||||||||||||||||||||
| TrARUIdentTable | 1.3.6.1.4.1.318.1.1.14.1.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for query of the individual devices. The number of entries is contained in the rARUStatusAruDeviceCount OID. | |||||||||||||||||||||
| RrARUIdentEntry | 1.3.6.1.4.1.318.1.1.14.1.1.1 | NA | mandatory | ||||||||||||||||||
| CrARUIdentAruIndex | 1.3.6.1.4.1.318.1.1.14.1.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the ARU entry. | |||||||||||||||||||||
| CrARUIdentName | 1.3.6.1.4.1.318.1.1.14.1.1.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory A character string identifying the device. | |||||||||||||||||||||
| NrARUConfig | 1.3.6.1.4.1.318.1.1.14.2 | ||||||||||||||||||||
| TrARUConfigTable | 1.3.6.1.4.1.318.1.1.14.2.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for configuration of the individual ARU devices accessible from this IP address. The number of entries is contained in the rARUStatusAruDeviceCount OID. | |||||||||||||||||||||
| RrARUConfigEntry | 1.3.6.1.4.1.318.1.1.14.2.1.1 | NA | mandatory | ||||||||||||||||||
| CrARUConfigAruIndex | 1.3.6.1.4.1.318.1.1.14.2.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the ARU entry. | |||||||||||||||||||||
| CrARUConfigAruName | 1.3.6.1.4.1.318.1.1.14.2.1.1.2 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The name of the ARU. | |||||||||||||||||||||
| CrARUConfigAruRemoteSetpoint | 1.3.6.1.4.1.318.1.1.14.2.1.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory This OID defines the desired base airflow of the ARU, and sets the speed of the ARU fans when the temperature override is inactive. Values specified in cfm (cubic feet per minute) can be converted to metric values using the conversion factor: 1 cfm = 1.70 m^3/hr (cubic meters per hour). Values (1) through (9) are for support of legacy (1st generation) ARUs. Writing these values to a 2nd generation ARU will result in the following: A value greater than (9) will be ignored by a 1st generation ARU. aruOff (1) - Ignored aru85F-29C (2) - 1200 cfm aru90F-32C (3) - 800 cfm aru95F-35C (4) - 500 cfm aru100F-38C (5) - 400 cfm aru7kW (6) - 1200 cfm aru5kW (7) - 800 cfm aru3kW (8) - 500 cfm aru2kW (9) - 400 cfm NOTE: -1 will be returned if the ARU is not communicating.
| |||||||||||||||||||||
| CrARUConfigAruTempOvrdEnableDisable | 1.3.6.1.4.1.318.1.1.14.2.1.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory This OID is used to enable/disable the remote temperature override setting of the ARU. If this OID is set to 1, the remote setting for temperature override is disabled. If this OID is set to 2, the remote setting for temperature override is enabled.
| |||||||||||||||||||||
| CrARUConfigAruTempOvrdSetpoint | 1.3.6.1.4.1.318.1.1.14.2.1.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory This OID is the Temperature Override setpoint of the ARU. NOTE: -1 will be returned if the ARU is not communicating. Values are represented in whole number degrees using the units specified in the rARUStatusSysTempUnits OID (Celsius or Fahrenheit). | |||||||||||||||||||||
| CrARUConfigAruMasterControl | 1.3.6.1.4.1.318.1.1.14.2.1.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory This is the master on/off control for the ARU.
| |||||||||||||||||||||
| NrARUStatus | 1.3.6.1.4.1.318.1.1.14.3 | ||||||||||||||||||||
| SrARUStatusAruDeviceCount | 1.3.6.1.4.1.318.1.1.14.3.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The total number of ARUs accessible from this IP. | |||||||||||||||||||||
| SrARUStatusSysTempUnits | 1.3.6.1.4.1.318.1.1.14.3.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The temperature scale used to display the temperature in the system, Celsius(1) or Fahrenheit(2). This setting is based on the system preferences configuration in the agent.
| |||||||||||||||||||||
| TrARUStatusTable | 1.3.6.1.4.1.318.1.1.14.3.3 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for query of the individual ARUs accessible from this IP address. The number of entries is contained in the rARUStatusAruDeviceCount OID. | |||||||||||||||||||||
| RrARUStatusEntry | 1.3.6.1.4.1.318.1.1.14.3.3.1 | NA | mandatory | ||||||||||||||||||
| CrARUStatusAruIndex | 1.3.6.1.4.1.318.1.1.14.3.3.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the ARU entry. | |||||||||||||||||||||
| CrARUStatusAruName | 1.3.6.1.4.1.318.1.1.14.3.3.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The name of the ARU. | |||||||||||||||||||||
| CrARUStatusAruRemoteSetpoint | 1.3.6.1.4.1.318.1.1.14.3.3.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This OID defines the desired base airflow of the ARU, or the speed of the ARU fans when the temperature override is inactive. See also the rARUConfigAruRemoteSetpoint OID. NOTE: -1 will be returned if the ARU is not communicating.
| |||||||||||||||||||||
| CrARUStatusAruManualSetpoint | 1.3.6.1.4.1.318.1.1.14.3.3.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Manual operating setpoint of the ARU, which is set on the panel of the ARU. If the ARU doesn't have a manual , the OID will always return a value of aruRem (10). NOTE: -1 will be returned if the ARU is not communicating. Values are represented in whole number degrees or kW. If the manual setpoint is set to Remote, or if the ARU doesn't have a manual switch, this OID will return aruRem.
| |||||||||||||||||||||
| CrARUStatusAruTemp1 | 1.3.6.1.4.1.318.1.1.14.3.3.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory ARU temperature probe #1 reading. The summary exhaust temperature on 2nd generation ARUs. NOTE: -1 will be returned if the ARU is not communicating. Values are represented in whole number degrees. Units are displayed in the scale shown in the rARUStatusSysTempUnits OID (Celsius or Fahrenheit). | |||||||||||||||||||||
| CrARUStatusAruTemp2 | 1.3.6.1.4.1.318.1.1.14.3.3.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory ARU temperature probe #2 reading. The exhaust temperature in the upper plenum on 2nd generation ARUs. NOTE: -1 will be returned if the ARU is not communicating. Values are represented in whole number degrees. Units are displayed in the scale shown in the rARUStatusSysTempUnits OID (Celsius or Fahrenheit). | |||||||||||||||||||||
| CrARUStatusAruTemp3 | 1.3.6.1.4.1.318.1.1.14.3.3.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory ARU temperature probe #3 reading. The exhaust temperature in the lower plenum on 2nd generation ARUs. NOTE: -1 will be returned if the ARU is not communicating. Values are represented in whole number degrees. Units are displayed in the scale shown in the rARUStatusSysTempUnits OID (Celsius or Fahrenheit). | |||||||||||||||||||||
| CrARUStatusAruTempOvrdEnableDisable | 1.3.6.1.4.1.318.1.1.14.3.3.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This OID indicates whether the ARU remote temperature override is enabled or disabled. If this OID is a 1, the remote setting for temperature override is disabled. If this OID is a 2, the remote setting for temperature override is enabled.
| |||||||||||||||||||||
| CrARUStatusAruTempOvrdSetpoint | 1.3.6.1.4.1.318.1.1.14.3.3.1.9 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory ARU remote temperature override setpoint setting. NOTE: -1 will be returned if the ARU is not communicating. Values are represented in whole number degrees. Units are displayed in the scale shown in the rARUStatusSysTempUnits OID (Celsius or Fahrenheit). | |||||||||||||||||||||
| CrARUStatusAruAlarmState | 1.3.6.1.4.1.318.1.1.14.3.3.1.10 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory An ASCII string containing the 8 flags representing the current alarm state of the ARU. If the state of the ARU is unknown, this variable is set to 'UNKNOWN'. The flags are numbered 1 to 8, read from left to right. The flags are defined as follows: Flag 1: Fan Fail 1 Flag 2: Fan Fail 2 Flag 3: Fan Fail 3 Flag 4: Smoke (if ARU is equipped with smoke detector) Flag 5: High Temp (Out of Thermal Control) Flag 6: Over Temp (Exhaust Temp. Exceeds Override Setpoint) Flag 7: Fan Fail 4 (Gen 2 ARU only) Flag 8: Reserved | |||||||||||||||||||||
| CrARUStatusAruCommStatus | 1.3.6.1.4.1.318.1.1.14.3.3.1.11 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The state of communications to the device. commNeverDiscovered(1) indicates there has never been communications with this device. commsEstablished(2) indicates communication is normal and active with this device. commsLost(3) indicates communication had been established, but is no device.
| |||||||||||||||||||||
| CrARUStatusAruTempOvrdStatus | 1.3.6.1.4.1.318.1.1.14.3.3.1.12 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Specifies whether the ARU is increasing airflow because exhaust air temperature has exceeded the setting specified in the rARUConfigAruTempOvrdSetpoint OID.
| |||||||||||||||||||||
| CrARUStatusAruMasterControl | 1.3.6.1.4.1.318.1.1.14.3.3.1.13 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This is the master on/off control for the ARU.
| |||||||||||||||||||||
| CrARUStatusAruTotalAirflow | 1.3.6.1.4.1.318.1.1.14.3.3.1.14 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The total airflow provided by the aru. Specified in cfm (cubic feet per minute). Can be converted to metric values using the conversion factor: 1 cfm = 1.70 m^3/hr (cubic meters per hour). | |||||||||||||||||||||
| NrARUFanStatus | 1.3.6.1.4.1.318.1.1.14.4 | ||||||||||||||||||||
| TrARUFanStatusTable | 1.3.6.1.4.1.318.1.1.14.4.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for query of the individual devices. The number of entries is contained in the rARUStatusAruDeviceCount OID. | |||||||||||||||||||||
| RrARUFanStatusEntry | 1.3.6.1.4.1.318.1.1.14.4.1.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The device to query. | |||||||||||||||||||||
| CrARUFanStatusAruIndex | 1.3.6.1.4.1.318.1.1.14.4.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the ARU entry. | |||||||||||||||||||||
| CrARUFanStatusNominalFanSpeed | 1.3.6.1.4.1.318.1.1.14.4.1.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The nominal rotational speed (RPM) of the fans when they are operating at the 100% level. | |||||||||||||||||||||
| CrARUFanStatusSelectedFanLevel | 1.3.6.1.4.1.318.1.1.14.4.1.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The currently selected ARU speed level, specified in percent of full capacity. | |||||||||||||||||||||
| CrARUFanStatusReplacementThreshold | 1.3.6.1.4.1.318.1.1.14.4.1.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Threshold above which a run hour alarm will exist, indicating that it might be time to proactively replace a fan.
| |||||||||||||||||||||
| CrARUFanStatusFanIndex | 1.3.6.1.4.1.318.1.1.14.4.1.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to an individual fan table entry. | |||||||||||||||||||||
| CrARUFanStatusFanOperatingStatus | 1.3.6.1.4.1.318.1.1.14.4.1.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The current operating state of the fan.
| |||||||||||||||||||||
| CrARUFanStatusFanRpmSpeed | 1.3.6.1.4.1.318.1.1.14.4.1.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The current rotational speed of the fan, specified in rotations per minute (RPM). | |||||||||||||||||||||
| CrARUFanStatusFanFlowRate | 1.3.6.1.4.1.318.1.1.14.4.1.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The flow rate provided by the fan, based on its measured rotational speed. Specified in cfm (cubic feet per minute). Can be converted to metric values using the conversion factor: 1 cfm = 1.70 m^3/hr (cubic meters per hour). | |||||||||||||||||||||
| CrARUFanStatusFanInServiceDate | 1.3.6.1.4.1.318.1.1.14.4.1.1.9 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The installation/replacement date of the fan. | |||||||||||||||||||||
| CrARUFanStatusFanRunhourCounter | 1.3.6.1.4.1.318.1.1.14.4.1.1.10 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The total time for which the fan has been running. Specified in 10ths of hours. | |||||||||||||||||||||
| CrARUFanStatusFanRunhourReset | 1.3.6.1.4.1.318.1.1.14.4.1.1.11 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Writing yes to this This OID will reset a fan's total run hour counter, which is shown in the rARUFanStatusFanRunhourCounter OID.
| |||||||||||||||||||||
| NrARUPower | 1.3.6.1.4.1.318.1.1.14.5 | ||||||||||||||||||||
| TrARUPowerStatusTable | 1.3.6.1.4.1.318.1.1.14.5.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for query of the individual ARUs accessible from this IP address. The number of entries is contained in the rARUStatusAruDeviceCount OID. | |||||||||||||||||||||
| RrARUPowerStatusEntry | 1.3.6.1.4.1.318.1.1.14.5.1.1 | NA | mandatory | ||||||||||||||||||
| CrARUPowerStatusAruIndex | 1.3.6.1.4.1.318.1.1.14.5.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the ARU entry. | |||||||||||||||||||||
| CrARUPowerStatusPrimaryAcPresent | 1.3.6.1.4.1.318.1.1.14.5.1.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Indicates whether or not line voltage is present on AC input 1.
| |||||||||||||||||||||
| CrARUPowerStatusAuxiliaryAcPresent | 1.3.6.1.4.1.318.1.1.14.5.1.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Indicates whether or not line voltage is present on AC input 2.
| |||||||||||||||||||||
| CrARUPowerStatusRedundantAcConfig | 1.3.6.1.4.1.318.1.1.14.5.1.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Indicates whether or not a dual cord is in use. When this setting is set to dualCord (2), aruRedundantPowerLostAlarm traps will be generated when either primary or auxiliary input voltage is not present. When this setting is set to singleCord (1), aruRedundantPowerLostAlarm traps will not be generated.
| |||||||||||||||||||||
| NrARUSensors | 1.3.6.1.4.1.318.1.1.14.6 | ||||||||||||||||||||
| SrARUSensorsStatusTableSize | 1.3.6.1.4.1.318.1.1.14.6.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the rARUSensorsStatusTable. | |||||||||||||||||||||
| TrARUSensorsStatusTable | 1.3.6.1.4.1.318.1.1.14.6.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting environmental sensor status information. | |||||||||||||||||||||
| RrARUSensorsStatusEntry | 1.3.6.1.4.1.318.1.1.14.6.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The unit to get data from. | |||||||||||||||||||||
| CrARUSensorsStatusAruIndex | 1.3.6.1.4.1.318.1.1.14.6.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the ARU entry. | |||||||||||||||||||||
| CrARUSensorsStatusSensorNumber | 1.3.6.1.4.1.318.1.1.14.6.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The number of the sensor on the device. | |||||||||||||||||||||
| CrARUSensorsTemperature | 1.3.6.1.4.1.318.1.1.14.6.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The sensor's current temperature reading. The temperature scale is based on the system preferences configuration. | |||||||||||||||||||||
| SrARUSensorsConfigTableSize | 1.3.6.1.4.1.318.1.1.14.6.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the rARUSensorsConfigTable. | |||||||||||||||||||||
| TrARUSensorsConfigTable | 1.3.6.1.4.1.318.1.1.14.6.4 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting configuration information from environmental sensors attached to the device. | |||||||||||||||||||||
| RrARUSensorsConfigEntry | 1.3.6.1.4.1.318.1.1.14.6.4.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The unit to get data from. | |||||||||||||||||||||
| CrARUSensorsConfigAruIndex | 1.3.6.1.4.1.318.1.1.14.6.4.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the ARU entry. | |||||||||||||||||||||
| CrARUSensorsConfigSensorNumber | 1.3.6.1.4.1.318.1.1.14.6.4.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The number of the sensor on the device. | |||||||||||||||||||||
| CrARUSensorsName | 1.3.6.1.4.1.318.1.1.14.6.4.1.3 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory A descriptive name for the sensor. | |||||||||||||||||||||
| CrARUSensorsLocation | 1.3.6.1.4.1.318.1.1.14.6.4.1.4 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The location of the sensor. | |||||||||||||||||||||
| CrARUSensorsTempMaxThresh | 1.3.6.1.4.1.318.1.1.14.6.4.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The temperature at which a maximum temperature threshold violation alarm will be generated for this sensor. The temperature scale is based on the system preferences configuration. | |||||||||||||||||||||
| CrARUSensorsTempHighThresh | 1.3.6.1.4.1.318.1.1.14.6.4.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The temperature at which a high temperature threshold violation alarm will be generated for this sensor. The temperature scale is based on the system preferences configuration. | |||||||||||||||||||||
| CrARUSensorsTempLowThresh | 1.3.6.1.4.1.318.1.1.14.6.4.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The temperature at which a low temperature threshold violation alarm will be generated for this sensor. The temperature scale is based on the system preferences configuration. | |||||||||||||||||||||
| CrARUSensorsTempMinThresh | 1.3.6.1.4.1.318.1.1.14.6.4.1.8 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The temperature at which a min temperature threshold violation alarm will be generated for this sensor. The temperature scale is based on the system preferences configuration. | |||||||||||||||||||||
| CrARUSensorsTempThreshHysteresis | 1.3.6.1.4.1.318.1.1.14.6.4.1.9 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The change in temperature required to cause a temperature alarm to change from an active to an inactive state. The temperature scale is based on the system preferences configuration. | |||||||||||||||||||||
| CrARUSensorsTempShortDecRateThreshValue | 1.3.6.1.4.1.318.1.1.14.6.4.1.10 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The value of the temperature short-term decreasing rate time that will cause an alarm to be generated. The temperature scale is based on the system preferences configuration. | |||||||||||||||||||||
| CrARUSensorsTempShortDecRateThreshTime | 1.3.6.1.4.1.318.1.1.14.6.4.1.11 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The time over which the temperature may not decrease beyond the value specified by the temperature short-term decreasing rate threshold value. | |||||||||||||||||||||
| CrARUSensorsTempShortIncRateThreshValue | 1.3.6.1.4.1.318.1.1.14.6.4.1.12 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The value of the temperature short-term increasing rate time that will cause an alarm to be generated. The temperature scale is based on the system preferences configuration. | |||||||||||||||||||||
| CrARUSensorsTempShortIncRateThreshTime | 1.3.6.1.4.1.318.1.1.14.6.4.1.13 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The time over which the temperature may not increase beyond the value specified by the temperature short-term increasing rate threshold value. | |||||||||||||||||||||
| CrARUSensorsTempLongDecRateThreshValue | 1.3.6.1.4.1.318.1.1.14.6.4.1.14 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The value of the temperature long-term decreasing rate time that will cause an alarm to be generated. The temperature scale is based on the system preferences configuration. | |||||||||||||||||||||
| CrARUSensorsTempLongDecRateThreshTime | 1.3.6.1.4.1.318.1.1.14.6.4.1.15 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The time over which the temperature may not decrease beyond the value specified by the temperature long-term decreasing rate threshold value. | |||||||||||||||||||||
| CrARUSensorsTempLongIncRateThreshValue | 1.3.6.1.4.1.318.1.1.14.6.4.1.16 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The value of the temperature long-term increasing rate time that will cause an alarm to be generated. The temperature scale is based on the system preferences configuration. | |||||||||||||||||||||
| CrARUSensorsTempLongIncRateThreshTime | 1.3.6.1.4.1.318.1.1.14.6.4.1.17 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The time over which the temperature may not increase beyond the value specified by the temperature long-term increasing rate threshold value. | |||||||||||||||||||||
| NxPDU | 1.3.6.1.4.1.318.1.1.15 | ||||||||||||||||||||
| NxPDUIdent | 1.3.6.1.4.1.318.1.1.15.1 | ||||||||||||||||||||
| SxPDUIdentProductName | 1.3.6.1.4.1.318.1.1.15.1.1 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory The name of the PDU. | |||||||||||||||||||||
| SxPDUIdentHardwareRev | 1.3.6.1.4.1.318.1.1.15.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The hardware revision of the PDU. This value is set at the factory. | |||||||||||||||||||||
| SxPDUIdentFirmwareAppRev | 1.3.6.1.4.1.318.1.1.15.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory An ID string identifying the application firmware revision of the PDU. | |||||||||||||||||||||
| SxPDUIdentFirmwareAppOSRev | 1.3.6.1.4.1.318.1.1.15.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory An ID string identifying the application operating system firmware revision of the PDU. | |||||||||||||||||||||
| SxPDUIdentFirmwareControllerRev | 1.3.6.1.4.1.318.1.1.15.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory An ID string identifying the PDU controller firmware revision. | |||||||||||||||||||||
| SxPDUIdentDateOfManufacture | 1.3.6.1.4.1.318.1.1.15.1.6 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The date when the PDU was manufactured in mm/dd/yyyy format. This value is set at the factory. | |||||||||||||||||||||
| SxPDUIdentModelNumber | 1.3.6.1.4.1.318.1.1.15.1.7 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the model number of the PDU. This value is set at the factory. | |||||||||||||||||||||
| SxPDUIdentSerialNumber | 1.3.6.1.4.1.318.1.1.15.1.8 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the serial number of the PDU. This value is set at the factory. | |||||||||||||||||||||
| NxPDUDevice | 1.3.6.1.4.1.318.1.1.15.2 | ||||||||||||||||||||
| SxPDUDeviceNominalMainInputVoltage | 1.3.6.1.4.1.318.1.1.15.2.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The nominal main input voltage to the PDU. Measured in Volts, line-to-line for a 3-wire (delta) service or line-to-neutral for a 4-wire (wye) service. | |||||||||||||||||||||
| SxPDUDeviceServiceType | 1.3.6.1.4.1.318.1.1.15.2.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The type of utility input to the PDU. Either 3 wires (delta), or 4 wires (wye).
| |||||||||||||||||||||
| SxPDUDeviceNominalOutputVoltage | 1.3.6.1.4.1.318.1.1.15.2.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The nominal line-to-neutral output voltage to the load measured in Volts. | |||||||||||||||||||||
| SxPDUDeviceMainInputBreakerRating | 1.3.6.1.4.1.318.1.1.15.2.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The rating of the main input breaker measured in Amps. | |||||||||||||||||||||
| SxPDUDevicePanelBreakerRating | 1.3.6.1.4.1.318.1.1.15.2.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The rating of the panel breaker measured in Amps. | |||||||||||||||||||||
| SxPDUDeviceTransformerPresent | 1.3.6.1.4.1.318.1.1.15.2.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Indicates whether or not a transformer is installed in the PDU.
| |||||||||||||||||||||
| SxPDUDeviceLoadTieBreakerPresent | 1.3.6.1.4.1.318.1.1.15.2.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Indicates whether or not a load tie breaker is installed in the PDU.
| |||||||||||||||||||||
| SxPDUDeviceLoadTestPortPresent | 1.3.6.1.4.1.318.1.1.15.2.8 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Indicates whether or not a load test port is installed in the PDU.
| |||||||||||||||||||||
| SxPDUDeviceFusesPresent | 1.3.6.1.4.1.318.1.1.15.2.9 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Indicates whether or not the UPS feed from the PDU includes fuses.
| |||||||||||||||||||||
| SxPDUDeviceFansPresent | 1.3.6.1.4.1.318.1.1.15.2.10 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Indicates whether or not cooling fans are installed in the PDU.
| |||||||||||||||||||||
| SxPDUDeviceBypassInputPresent | 1.3.6.1.4.1.318.1.1.15.2.11 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Indicates whether or not the PDU is equipped with a second feed for the UPS device's bypass input.
| |||||||||||||||||||||
| SxPDUDeviceCrossTieOutputPresent | 1.3.6.1.4.1.318.1.1.15.2.12 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Indicates whether or not the PDU is equipped with a cross-tie output.
| |||||||||||||||||||||
| SxPDUDeviceEarthGroundMonitorPresent | 1.3.6.1.4.1.318.1.1.15.2.13 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Indicates whether or not the PDU can provide ground current measurements.
| |||||||||||||||||||||
| SxPDUDeviceInfraStruXureType | 1.3.6.1.4.1.318.1.1.15.2.14 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Indicates the configuration of this PDU system. Type-B PDU is in a distributed UPS system and has bypass capabilities. Type-C PDU receives power from a larger central UPS.
| |||||||||||||||||||||
| NxPDUACMonitoringPoint | 1.3.6.1.4.1.318.1.1.15.3 | ||||||||||||||||||||
| NxPDUMainInput | 1.3.6.1.4.1.318.1.1.15.3.1 | ||||||||||||||||||||
| SxPDUMainInputOverVoltThreshold | 1.3.6.1.4.1.318.1.1.15.3.1.1 | INTEGER (0..30) | RW | mandatory | |||||||||||||||||
scalar · INTEGER (0..30) · read-write · mandatory Threshold above which an input over voltage condition will be generated. Specified as percent deviation from nominal. | |||||||||||||||||||||
| SxPDUMainInputUnderVoltThreshold | 1.3.6.1.4.1.318.1.1.15.3.1.2 | INTEGER (0..30) | RW | mandatory | |||||||||||||||||
scalar · INTEGER (0..30) · read-write · mandatory Threshold below which an input under voltage condition will be generated. Specified as percent deviation from nominal. A value of zero indicates that the threshold is disabled. | |||||||||||||||||||||
| SxPDUMainInputVoltageTableSize | 1.3.6.1.4.1.318.1.1.15.3.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of Main input voltage entries. | |||||||||||||||||||||
| TxPDUMainInputVoltagePhaseTable | 1.3.6.1.4.1.318.1.1.15.3.1.4 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of input voltage table entries. The number of entries are the phase entries. The number of entries is contained in the xPDUMainInputVoltageTableSize OID. | |||||||||||||||||||||
| RxPDUMainInputVoltagePhaseEntry | 1.3.6.1.4.1.318.1.1.15.3.1.4.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular main input voltage phase. | |||||||||||||||||||||
| CxPDUMainInputVoltagePhaseIndex | 1.3.6.1.4.1.318.1.1.15.3.1.4.1.1 | INTEGER | RO | mandatory | phase1(1) | ||||||||||||||||
column · INTEGER · read-only · mandatory Description of each input phase entry in the table.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CxPDUMainInputVoltageLtoL | 1.3.6.1.4.1.318.1.1.15.3.1.4.1.2 | INTEGER | RO | mandatory | 4664 | ||||||||||||||||
column · INTEGER · read-only · mandatory Line-to-line PDU input voltage when an isolation transformer is present, or -1 if no transformer present in this PDU. Measured in tenths of Volts. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CxPDUMainInputVoltageLtoN | 1.3.6.1.4.1.318.1.1.15.3.1.4.1.3 | INTEGER | RO | mandatory | -1 | ||||||||||||||||
column · INTEGER · read-only · mandatory Line-to-neutral PDU input voltage when an isolation transformer is not present, or -1 if a transformer is present in this PDU. Measured in tenths of Volts. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NxPDUBypassInput | 1.3.6.1.4.1.318.1.1.15.3.2 | ||||||||||||||||||||
| SxPDUBypassInputOverVoltThreshold | 1.3.6.1.4.1.318.1.1.15.3.2.1 | INTEGER (0..30) | RW | mandatory | |||||||||||||||||
scalar · INTEGER (0..30) · read-write · mandatory Threshold above which a bypass input over voltage condition will be generated. Specified as percent deviation from nominal. | |||||||||||||||||||||
| SxPDUBypassInputUnderVoltThreshold | 1.3.6.1.4.1.318.1.1.15.3.2.2 | INTEGER (0..30) | RW | mandatory | |||||||||||||||||
scalar · INTEGER (0..30) · read-write · mandatory Threshold below which an bypass input under voltage condition will be generated. Specified as percent deviation from nominal. A value of zero indicates that the threshold is disabled. | |||||||||||||||||||||
| SxPDUBypassInputVoltagePhaseTableSize | 1.3.6.1.4.1.318.1.1.15.3.2.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of bypass input voltage entries. | |||||||||||||||||||||
| TxPDUBypassInputVoltagePhaseTable | 1.3.6.1.4.1.318.1.1.15.3.2.4 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of output table entries. The number of entries are the phase entries. The number of entries is contained in the xPDUBypassInputVoltagePhaseTableSize OID. | |||||||||||||||||||||
| RxPDUBypassInputVoltagePhaseEntry | 1.3.6.1.4.1.318.1.1.15.3.2.4.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular bypass input voltage phase. | |||||||||||||||||||||
| CxPDUBypassInputVoltagePhaseIndex | 1.3.6.1.4.1.318.1.1.15.3.2.4.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Index of each bypass input phase entry in the table.
| |||||||||||||||||||||
| CxPDUBypassInputVoltageLtoL | 1.3.6.1.4.1.318.1.1.15.3.2.4.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Line-to-line bypass input voltage, or -1 if no bypass feed is present in this PDU. Measured in tenths of Volts. | |||||||||||||||||||||
| CxPDUBypassInputVoltageLtoN | 1.3.6.1.4.1.318.1.1.15.3.2.4.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Line-to-neutral bypass input voltage, or -1 if no bypass feed is present in this PDU. Measured in tenths of Volts. | |||||||||||||||||||||
| NxPDUUPSInput | 1.3.6.1.4.1.318.1.1.15.3.3 | ||||||||||||||||||||
| SxPDUUPSInputVoltagePhaseTableSize | 1.3.6.1.4.1.318.1.1.15.3.3.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of UPS input voltage entries. | |||||||||||||||||||||
| TxPDUUPSInputVoltagePhaseTable | 1.3.6.1.4.1.318.1.1.15.3.3.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of UPS input table entries. The number of entries are the phase entries. The number of entries is contained in the xPDUUPSInputVoltagePhaseTableSize OID. | |||||||||||||||||||||
| RxPDUUPSInputVoltagePhaseEntry | 1.3.6.1.4.1.318.1.1.15.3.3.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular UPS input voltage phase. | |||||||||||||||||||||
| CxPDUUPSInputVoltagePhaseIndex | 1.3.6.1.4.1.318.1.1.15.3.3.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Description of each UPS input phase entry in the table.
| |||||||||||||||||||||
| CxPDUUPSInputVoltageLtoNPresent | 1.3.6.1.4.1.318.1.1.15.3.3.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Indicates whether or not voltage is present at the UPS feed.
| |||||||||||||||||||||
| NxPDUSystemOutput | 1.3.6.1.4.1.318.1.1.15.3.4 | ||||||||||||||||||||
| SxPDUSystemOutputFrequency | 1.3.6.1.4.1.318.1.1.15.3.4.1 | INTEGER | RO | mandatory | 600 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The system output frequency in tenths of Hertz. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxPDUSystemOutputNeutralCurrent | 1.3.6.1.4.1.318.1.1.15.3.4.2 | INTEGER | RO | mandatory | 121 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory Shows the neutral current measured at the system output in tenths of Amps. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxPDUSystemOutputTotalPower | 1.3.6.1.4.1.318.1.1.15.3.4.3 | INTEGER | RO | mandatory | 192 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory Shows the total system output power in tenths of kW. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxPDUSystemOutputTotalApparentPower | 1.3.6.1.4.1.318.1.1.15.3.4.4 | INTEGER | RO | mandatory | 186 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory Shows the total system output power in tenths of kVA. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxPDUSystemOutputTotalPowerFactor | 1.3.6.1.4.1.318.1.1.15.3.4.5 | INTEGER | RO | mandatory | 100 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory Indicates the total power factor of the system output. A value of 100 representing a unity power factor (1.00). Measured in hundredths. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxPDUSystemOutputFrequencyTolerance | 1.3.6.1.4.1.318.1.1.15.3.4.6 | INTEGER | RW | mandatory | freqToleranceFive(9) | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Shows the circuit panel output frequency tolerance in Hertz.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxPDUSystemOutputMaxKWPower | 1.3.6.1.4.1.318.1.1.15.3.4.7 | INTEGER | RW | mandatory | 80 | ||||||||||||||||
scalar · INTEGER · read-write · mandatory Defines 100% load in kW. Purpose is to set to match UPS capabilities. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxPDUSystemOutputOverVoltThreshold | 1.3.6.1.4.1.318.1.1.15.3.4.8 | INTEGER (0..30) | RW | mandatory | 12 | ||||||||||||||||
scalar · INTEGER (0..30) · read-write · mandatory Threshold above which an output over voltage condition will be generated. Specified as percent deviation from nominal. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxPDUSystemOutputUnderVoltThreshold | 1.3.6.1.4.1.318.1.1.15.3.4.9 | INTEGER (0..30) | RW | mandatory | 12 | ||||||||||||||||
scalar · INTEGER (0..30) · read-write · mandatory Threshold below which an output under voltage condition will be generated. Specified as percent deviation from nominal. A value of zero indicates that the threshold is disabled. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxPDUSystemOutputOverCurrentThreshold | 1.3.6.1.4.1.318.1.1.15.3.4.10 | INTEGER (0..110) | RW | mandatory | 80 | ||||||||||||||||
scalar · INTEGER (0..110) · read-write · mandatory Threshold above which an over current condition will be generated. Specified as a percent of the panel breaker rating. A value of zero indicates that the threshold is disabled. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxPDUSystemOutputOverCurrentNeutralThreshold | 1.3.6.1.4.1.318.1.1.15.3.4.11 | INTEGER (0..110) | RW | mandatory | 80 | ||||||||||||||||
scalar · INTEGER (0..110) · read-write · mandatory Threshold above which an Over current neutral condition will be generated. Specified as a percent of the panel breaker rating. A value of zero indicates that the threshold is disabled. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxPDUSystemOutputUnderCurrentThreshold | 1.3.6.1.4.1.318.1.1.15.3.4.12 | INTEGER (0..100) | RW | mandatory | 0 | ||||||||||||||||
scalar · INTEGER (0..100) · read-write · mandatory Threshold below which an under current condition will be generated. Specified as a percent of the panel breaker rating. A value of zero indicates that the threshold is disabled. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxPDUSystemOutputTableSize | 1.3.6.1.4.1.318.1.1.15.3.4.13 | INTEGER | RO | mandatory | 3 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of System Output phase entries. Example values from LibreNMS test devices
| |||||||||||||||||||||
| TxPDUSystemOutputPhaseTable | 1.3.6.1.4.1.318.1.1.15.3.4.14 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of system output table entries. The number of entries is contained in the xPDUSystemOutputTableSize OID. | |||||||||||||||||||||
| RxPDUSystemOutputPhaseEntry | 1.3.6.1.4.1.318.1.1.15.3.4.14.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular system output phase. | |||||||||||||||||||||
| CxPDUSystemOutputPhaseIndex | 1.3.6.1.4.1.318.1.1.15.3.4.14.1.1 | INTEGER | RO | mandatory | phase1(1) | ||||||||||||||||
column · INTEGER · read-only · mandatory Description of each output phase entry in the table.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CxPDUSystemOutputVoltageLtoL | 1.3.6.1.4.1.318.1.1.15.3.4.14.1.2 | INTEGER | RO | mandatory | 2140 | ||||||||||||||||
column · INTEGER · read-only · mandatory Line-to-line system output voltage available at the circuit panel. Measured in tenths of Volts. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CxPDUSystemOutputVoltageLtoN | 1.3.6.1.4.1.318.1.1.15.3.4.14.1.3 | INTEGER | RO | mandatory | 1212 | ||||||||||||||||
column · INTEGER · read-only · mandatory Line-to-neutral system output voltage available at the circuit panel. Measured in tenths of Volts. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CxPDUSystemOutputPhaseCurrent | 1.3.6.1.4.1.318.1.1.15.3.4.14.1.4 | INTEGER | RO | mandatory | 449 | ||||||||||||||||
column · INTEGER · read-only · mandatory System load current per phase. Measured in tenths of Amps. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CxPDUSystemOutputPower | 1.3.6.1.4.1.318.1.1.15.3.4.14.1.5 | INTEGER | RO | mandatory | 55 | ||||||||||||||||
column · INTEGER · read-only · mandatory System output power per phase. Measured in tenths of kW. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CxPDUSystemOutputApparentPower | 1.3.6.1.4.1.318.1.1.15.3.4.14.1.6 | INTEGER | RO | mandatory | 54 | ||||||||||||||||
column · INTEGER · read-only · mandatory System output power per phase. Measured in tenths of kVA. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CxPDUSystemOutputPowerFactor | 1.3.6.1.4.1.318.1.1.15.3.4.14.1.7 | INTEGER | RO | mandatory | 100 | ||||||||||||||||
column · INTEGER · read-only · mandatory Indicates the Power Factor of the system output per phase. A value of 100 representing a unity Power Factor (1.00). Measured in hundredths. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NxPDUGroundMonitorPoint | 1.3.6.1.4.1.318.1.1.15.3.5 | ||||||||||||||||||||
| SxPDUGroundCurrent | 1.3.6.1.4.1.318.1.1.15.3.5.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Shows the current measured in the earth ground conductor. Measured in tenths of Amps, or -1 if not available. | |||||||||||||||||||||
| SxPDUGroundCurrentThreshold | 1.3.6.1.4.1.318.1.1.15.3.5.2 | INTEGER (0..50) | RW | mandatory | |||||||||||||||||
scalar · INTEGER (0..50) · read-write · mandatory Threshold above which a ground current over current condition will be generated. Specified in tenths of Amps. | |||||||||||||||||||||
| NxPDUCircuitBreakers | 1.3.6.1.4.1.318.1.1.15.4 | ||||||||||||||||||||
| NxPDUSystemBreakers | 1.3.6.1.4.1.318.1.1.15.4.1 | ||||||||||||||||||||
| SxPDUSystemBreakerTableSize | 1.3.6.1.4.1.318.1.1.15.4.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of system breaker entries. | |||||||||||||||||||||
| TxPDUSystemBreakerTable | 1.3.6.1.4.1.318.1.1.15.4.1.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of system breaker entries. The number of entries is contained in the xPDUSystemBreakerTableSize OID. | |||||||||||||||||||||
| RxPDUSystemBreakerEntry | 1.3.6.1.4.1.318.1.1.15.4.1.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular system breaker. | |||||||||||||||||||||
| CxPDUSystemBreakerTableIndex | 1.3.6.1.4.1.318.1.1.15.4.1.2.1.1 | INTEGER | RO | mandatory | 1 | ||||||||||||||||
column · INTEGER · read-only · mandatory Index of system breaker entries in the table. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CxPDUSystemBreakerDescription | 1.3.6.1.4.1.318.1.1.15.4.1.2.1.2 | DisplayString (SIZE (0..79)) | RO | mandatory | Main Input | ||||||||||||||||
column · DisplayString (SIZE (0..79)) · read-only · mandatory A brief description of the system breakers. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CxPDUSystemBreakerPosition | 1.3.6.1.4.1.318.1.1.15.4.1.2.1.3 | INTEGER | RO | mandatory | closed(2) | ||||||||||||||||
column · INTEGER · read-only · mandatory Indicates whether this breaker is open(1) or closed(2).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NxPDUBranchBreakers | 1.3.6.1.4.1.318.1.1.15.4.2 | ||||||||||||||||||||
| SxPDUNumOfBranchBreakers | 1.3.6.1.4.1.318.1.1.15.4.2.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of branch breakers (panel positions) in the Panel. returns 42 for a 1-panel or 84 for a 2-panel system. | |||||||||||||||||||||
| SxPDUBranchBreakerTableSize | 1.3.6.1.4.1.318.1.1.15.4.2.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of branch breaker entries determined by the xPDUNumOfBranchBreakers OID. | |||||||||||||||||||||
| TxPDUBranchBreakerTable | 1.3.6.1.4.1.318.1.1.15.4.2.3 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of branch breaker table entries. The number of entries is given by the value of xPDUBranchBreakerTableSize The number of entries is contained in the xPDUBranchBreakerTableSize OID. | |||||||||||||||||||||
| RxPDUBranchBreakerEntry | 1.3.6.1.4.1.318.1.1.15.4.2.3.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular branch breaker (panel position). | |||||||||||||||||||||
| CxPDUBranchBreakerTableIndex | 1.3.6.1.4.1.318.1.1.15.4.2.3.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Index of branch breaker entries in the table. | |||||||||||||||||||||
| CxPDUBranchBreakerRating | 1.3.6.1.4.1.318.1.1.15.4.2.3.1.2 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Indicates current rating of this breaker. 0=Breaker is not present. 1=Earth leakage connection. 2=Neutral connection. A value greater than 2 indicates breaker current rating in Amps. A value above 60 Amp will signify a remote feed. The xPDUBranchBreakerRDPFeed OID will indicate which breakers are configured as a remote drop. Note: When setting branch circuit thresholds/ratings for an entry, all positions tied (see the xPDUBranchBreakerTieIndicator OID) to this entry will inherit the new threshold/rating. | |||||||||||||||||||||
| CxPDUBranchBreakerRDPFeed | 1.3.6.1.4.1.318.1.1.15.4.2.3.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Indicates that a breaker position is feeding a remote distribution panel.
| |||||||||||||||||||||
| CxPDUBranchBreakerTieIndicator | 1.3.6.1.4.1.318.1.1.15.4.2.3.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Indicates whether or not the breaker in this position is logically associated with the breaker immediately below it. This setting is used grouping the breakers feeding a multi-pole branch circuit. Note: When setting an entry's branch breaker tie indicator to breakerTied, all the positions that are tied to this breaker will take on the rating and thresholds for this entry of the table.
| |||||||||||||||||||||
| CxPDUBranchBreakerCurrent | 1.3.6.1.4.1.318.1.1.15.4.2.3.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Indicates the branch current in tenths of Amps or -1 when not available. | |||||||||||||||||||||
| CxPDUBranchBreakerOverCurrentThreshold | 1.3.6.1.4.1.318.1.1.15.4.2.3.1.6 | INTEGER (0..100) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..100) · read-write · mandatory Threshold above which a branch circuit high current condition will be generated. Specified as a percent of the branch breaker rating. A value of zero indicates that the threshold is disabled. Note: When setting branch circuit thresholds/ratings for an entry, all positions tied (see the xPDUBranchBreakerTieIndicator OID) to this entry will inherit the new threshold/rating. | |||||||||||||||||||||
| CxPDUBranchBreakerUnderCurrentThreshold | 1.3.6.1.4.1.318.1.1.15.4.2.3.1.7 | INTEGER (0..100) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..100) · read-write · mandatory Threshold below which a branch circuit low current condition will be generated. Specified as a percent of the branch breaker rating. A value of zero indicates that the threshold is disabled. Note: When setting branch circuit thresholds/ratings for an entry, all positions tied (see the xPDUBranchBreakerTieIndicator OID) to this entry will inherit the new threshold/rating. | |||||||||||||||||||||
| CxPDUBranchBreakerMaxCurrentThreshold | 1.3.6.1.4.1.318.1.1.15.4.2.3.1.8 | INTEGER (0..100) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..100) · read-write · mandatory Threshold above which a branch circuit maximum current condition will be generated. Specified as a percent of the branch breaker rating. A value of zero indicates that the threshold is disabled. Note: When setting branch circuit thresholds/ratings for an entry, all positions tied (see the xPDUBranchBreakerTieIndicator OID) to this entry will inherit the new threshold/rating. | |||||||||||||||||||||
| CxPDUBranchBreakerMinCurrentThreshold | 1.3.6.1.4.1.318.1.1.15.4.2.3.1.9 | INTEGER (0..100) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..100) · read-write · mandatory Threshold below which a branch circuit minimum current condition will be generated. Specified as a percent of the branch breaker rating. A value of zero indicates that the threshold is disabled. Note: When setting branch circuit thresholds/ratings for an entry, all positions tied (see the xPDUBranchBreakerTieIndicator OID) to this entry will inherit the new threshold/rating. | |||||||||||||||||||||
| CxPDUBranchBreakerName | 1.3.6.1.4.1.318.1.1.15.4.2.3.1.10 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The description of the purpose/use of the breaker. | |||||||||||||||||||||
| CxPDUBranchBreakerLocation | 1.3.6.1.4.1.318.1.1.15.4.2.3.1.11 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The description of the location of the breaker. | |||||||||||||||||||||
| NxPDUInputContacts | 1.3.6.1.4.1.318.1.1.15.5 | ||||||||||||||||||||
| SxPDUInputContactNumContacts | 1.3.6.1.4.1.318.1.1.15.5.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of contacts supported by the PDU. | |||||||||||||||||||||
| SxPDUInputContactTableSize | 1.3.6.1.4.1.318.1.1.15.5.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of input contact entries. | |||||||||||||||||||||
| TxPDUInputContactTable | 1.3.6.1.4.1.318.1.1.15.5.3 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of contacts supported by the PDU. The number of entries is contained in the xPDUInputContactTableSize OID. | |||||||||||||||||||||
| RxPDUInputContactEntry | 1.3.6.1.4.1.318.1.1.15.5.3.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory A contact entry containing information for a given contact. | |||||||||||||||||||||
| CxPDUInputContactNumber | 1.3.6.1.4.1.318.1.1.15.5.3.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory An index identifying the contact on the PDU. | |||||||||||||||||||||
| CxPDUInputContactName | 1.3.6.1.4.1.318.1.1.15.5.3.1.2 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The description of the purpose/use of the contact. | |||||||||||||||||||||
| CxPDUInputContactNormalState | 1.3.6.1.4.1.318.1.1.15.5.3.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The normal operating position of the contact.
| |||||||||||||||||||||
| CxPDUInputContactCurrentState | 1.3.6.1.4.1.318.1.1.15.5.3.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This value indicates the current state of the contact.
| |||||||||||||||||||||
| NxPDUOutputRelays | 1.3.6.1.4.1.318.1.1.15.6 | ||||||||||||||||||||
| SxPDUOutputRelaysNumRelays | 1.3.6.1.4.1.318.1.1.15.6.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of output relays supported by the PDU. | |||||||||||||||||||||
| SxPDUOutputRelaysTableSize | 1.3.6.1.4.1.318.1.1.15.6.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of output relay entries. | |||||||||||||||||||||
| TxPDUOutputRelayTable | 1.3.6.1.4.1.318.1.1.15.6.3 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of output relays supported by the PDU. The number of entries is contained in the xPDUOutputRelayTableSize OID. | |||||||||||||||||||||
| RxPDUOutputRelayEntry | 1.3.6.1.4.1.318.1.1.15.6.3.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory A output relay entry containing information for a given contact. | |||||||||||||||||||||
| CxPDUOutputRelayNumber | 1.3.6.1.4.1.318.1.1.15.6.3.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory An index identifying the output relay on the PDU. | |||||||||||||||||||||
| CxPDUOutputRelayName | 1.3.6.1.4.1.318.1.1.15.6.3.1.2 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The description of the purpose/use of the output relay. | |||||||||||||||||||||
| CxPDUOutputRelayNormalState | 1.3.6.1.4.1.318.1.1.15.6.3.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The normal operating position of the output relay.
| |||||||||||||||||||||
| CxPDUOutputRelayCurrentState | 1.3.6.1.4.1.318.1.1.15.6.3.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This value indicates the current state of the output relay.
| |||||||||||||||||||||
| NxPDUMiscGroup | 1.3.6.1.4.1.318.1.1.15.7 | ||||||||||||||||||||
| SxPDUEPOMode | 1.3.6.1.4.1.318.1.1.15.7.1 | INTEGER | RO | mandatory | armed(1) | ||||||||||||||||
scalar · INTEGER · read-only · mandatory Indicates whether the EPO System is armed(1) or disarmed(2).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxPDUTransformTempStatus | 1.3.6.1.4.1.318.1.1.15.7.2 | INTEGER | RO | mandatory | normal(1) | ||||||||||||||||
scalar · INTEGER · read-only · mandatory Indicates if the PDU's isolation transformer is over temperature.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxPDUCoolingFanStatus | 1.3.6.1.4.1.318.1.1.15.7.3 | INTEGER | RO | mandatory | noCoolingFansPresent(3) | ||||||||||||||||
scalar · INTEGER · read-only · mandatory Indicates if one or more of the PDU's cooling fans have failed.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NbattMan | 1.3.6.1.4.1.318.1.1.16 | ||||||||||||||||||||
| NbattManIdent | 1.3.6.1.4.1.318.1.1.16.1 | ||||||||||||||||||||
| SbattManIdentProductName | 1.3.6.1.4.1.318.1.1.16.1.1 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory The name of the battery manager. | |||||||||||||||||||||
| SbattManIdentHardwareRev | 1.3.6.1.4.1.318.1.1.16.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The battery manager network interface hardware revision. This value is set at the factory. | |||||||||||||||||||||
| SbattManIdentFirmwareRev | 1.3.6.1.4.1.318.1.1.16.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The battery manager network interface firmware revision. This value is set at the factory and can change with firmware update. | |||||||||||||||||||||
| SbattManIdentDateOfManufacture | 1.3.6.1.4.1.318.1.1.16.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The date the battery manager was manufactured in mm/dd/yyyy format. This value is set at the factory. | |||||||||||||||||||||
| SbattManIdentModelNumber | 1.3.6.1.4.1.318.1.1.16.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The battery manager model number character string. This value is set at the factory. | |||||||||||||||||||||
| SbattManIdentSerialNumber | 1.3.6.1.4.1.318.1.1.16.1.6 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The battery manager serial number character string. This value is set at the factory. | |||||||||||||||||||||
| NbattManSystemCalib | 1.3.6.1.4.1.318.1.1.16.2 | ||||||||||||||||||||
| SbattManOhmicValueCorrectionFactor | 1.3.6.1.4.1.318.1.1.16.2.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The system ohmic value correction factor in percent. | |||||||||||||||||||||
| NbattManUnitCalib | 1.3.6.1.4.1.318.1.1.16.3 | ||||||||||||||||||||
| SbattManUnitCalibTableSize | 1.3.6.1.4.1.318.1.1.16.3.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the battManUnitCalibTable. | |||||||||||||||||||||
| TbattManUnitCalibTable | 1.3.6.1.4.1.318.1.1.16.3.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting calibration information from each unit in the system. | |||||||||||||||||||||
| RbattManUnitCalibEntry | 1.3.6.1.4.1.318.1.1.16.3.2.1 | NA | mandatory | ||||||||||||||||||
| CbattManUnitCalibIndex | 1.3.6.1.4.1.318.1.1.16.3.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Index of unit calibration entries in the table. | |||||||||||||||||||||
| CbattManUnitSerialNumber | 1.3.6.1.4.1.318.1.1.16.3.2.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The serial number of the unit. | |||||||||||||||||||||
| CbattManBatteryVoltageZeroCalib | 1.3.6.1.4.1.318.1.1.16.3.2.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The unit battery voltage zero calibration in millivolts. | |||||||||||||||||||||
| CbattManBatteryVoltageSpanCalib | 1.3.6.1.4.1.318.1.1.16.3.2.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The unit battery voltage span calibration in hundredths of percent. | |||||||||||||||||||||
| NbattManStringCalib | 1.3.6.1.4.1.318.1.1.16.4 | ||||||||||||||||||||
| SbattManStringCalibTableSize | 1.3.6.1.4.1.318.1.1.16.4.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the battManStringCalibTable. | |||||||||||||||||||||
| TbattManStringCalibTable | 1.3.6.1.4.1.318.1.1.16.4.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting calibration information from each string in the system. | |||||||||||||||||||||
| RbattManStringCalibEntry | 1.3.6.1.4.1.318.1.1.16.4.2.1 | NA | mandatory | ||||||||||||||||||
| CbattManStringCalibIndex | 1.3.6.1.4.1.318.1.1.16.4.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Index of string calibration entries in the table. | |||||||||||||||||||||
| CbattManDCCurrentZeroCalib | 1.3.6.1.4.1.318.1.1.16.4.2.1.2 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The string DC current zero calibration in tenths of amps. | |||||||||||||||||||||
| CbattManACCurrentZeroCalib | 1.3.6.1.4.1.318.1.1.16.4.2.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The string AC current zero calibration in tenths of amps. | |||||||||||||||||||||
| CbattManProbeRange | 1.3.6.1.4.1.318.1.1.16.4.2.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The string probe range in amps.
| |||||||||||||||||||||
| NbattManBatteryCalib | 1.3.6.1.4.1.318.1.1.16.5 | ||||||||||||||||||||
| SbattManString1BatteryCalibTableSize | 1.3.6.1.4.1.318.1.1.16.5.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the battManString1BatteryCalibTable. | |||||||||||||||||||||
| TbattManString1BatteryCalibTable | 1.3.6.1.4.1.318.1.1.16.5.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting calibration information from each battery in String 1. | |||||||||||||||||||||
| RbattManString1BatteryCalibEntry | 1.3.6.1.4.1.318.1.1.16.5.2.1 | NA | mandatory | ||||||||||||||||||
| CbattManString1BatteryCalibIndex | 1.3.6.1.4.1.318.1.1.16.5.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Index of battery calibration entries in the table. | |||||||||||||||||||||
| CbattManString1BatteryInterTierOhmicValue | 1.3.6.1.4.1.318.1.1.16.5.2.1.2 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The battery inter-tier ohmic value in ohms. This corresponds to the ohmic value for the positive terminal of the battery. | |||||||||||||||||||||
| SbattManString2BatteryCalibTableSize | 1.3.6.1.4.1.318.1.1.16.5.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the battManString2BatteryCalibTable. | |||||||||||||||||||||
| TbattManString2BatteryCalibTable | 1.3.6.1.4.1.318.1.1.16.5.4 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting calibration information from each battery in String 2. | |||||||||||||||||||||
| RbattManString2BatteryCalibEntry | 1.3.6.1.4.1.318.1.1.16.5.4.1 | NA | mandatory | ||||||||||||||||||
| CbattManString2BatteryCalibIndex | 1.3.6.1.4.1.318.1.1.16.5.4.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Index of battery calibration entries in the table. | |||||||||||||||||||||
| CbattManString2BatteryInterTierOhmicValue | 1.3.6.1.4.1.318.1.1.16.5.4.1.2 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The battery inter-tier ohmic value in ohms. | |||||||||||||||||||||
| NbattManConfig | 1.3.6.1.4.1.318.1.1.16.6 | ||||||||||||||||||||
| SbattManConfigApplication | 1.3.6.1.4.1.318.1.1.16.6.1 | INTEGER | RW | deprecated | |||||||||||||||||
scalar · INTEGER · read-write · deprecated This OID has been deprecated.
| |||||||||||||||||||||
| SbattManConfigBatteryChemistry | 1.3.6.1.4.1.318.1.1.16.6.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The battery chemistry of the monitored batteries: LeadAcid(1) Lead Acid or Nickel-Cadmium(2) Nickel-Cadmium.
| |||||||||||||||||||||
| SbattManConfigBatteryAHCapacity | 1.3.6.1.4.1.318.1.1.16.6.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The amp hour capacity of the monitored batteries 5-4000 AH. | |||||||||||||||||||||
| SbattManConfigNumberofStrings | 1.3.6.1.4.1.318.1.1.16.6.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The number of strings in the battery manager system. | |||||||||||||||||||||
| SbattManConfigBatteriesperString | 1.3.6.1.4.1.318.1.1.16.6.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The number of batteries per string. | |||||||||||||||||||||
| SbattManConfigCellsperBattery | 1.3.6.1.4.1.318.1.1.16.6.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The number of cells per battery (1, 2, 4 or 6 for lead-acid, 1 or 2 for NiCd.
| |||||||||||||||||||||
| SbattManConfigMinCellVoltage | 1.3.6.1.4.1.318.1.1.16.6.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The minimum battery cell voltage alarm limit in millivolts DC. | |||||||||||||||||||||
| SbattManConfigMaxCellVoltage | 1.3.6.1.4.1.318.1.1.16.6.8 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The maximum battery cell voltage alarm limit in millivolts DC. | |||||||||||||||||||||
| SbattManConfigMaxPilotTempF | 1.3.6.1.4.1.318.1.1.16.6.9 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The maximum pilot battery temperature alarm limit in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SbattManConfigMaxPilotTempC | 1.3.6.1.4.1.318.1.1.16.6.10 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The maximum pilot battery temperature alarm limit in tenths of degrees Celsius. | |||||||||||||||||||||
| SbattManConfigMaxAmbientTempF | 1.3.6.1.4.1.318.1.1.16.6.11 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The maximum ambient temperature alarm limit in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SbattManConfigMaxAmbientTempC | 1.3.6.1.4.1.318.1.1.16.6.12 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The maximum ambient temperature alarm limit in tenths of degrees Celsius. | |||||||||||||||||||||
| SbattManConfigMinAmbientTempF | 1.3.6.1.4.1.318.1.1.16.6.13 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The Minimum Ambient Temperature alarm limit in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SbattManConfigMinAmbientTempC | 1.3.6.1.4.1.318.1.1.16.6.14 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The Minimum Ambient Temperature alarm limit in tenths of degrees Celsius. | |||||||||||||||||||||
| SbattManConfigMaxRippleCurrent | 1.3.6.1.4.1.318.1.1.16.6.15 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The maximum ripple current alarm limit for the monitored battery strings in percent of AH capacity. | |||||||||||||||||||||
| SbattManConfigMaxCurrentAcceptanceDeviation | 1.3.6.1.4.1.318.1.1.16.6.16 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The maximum current acceptance deviation alarm limit in percent. | |||||||||||||||||||||
| SbattManConfigMonitorWireLength | 1.3.6.1.4.1.318.1.1.16.6.17 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The monitor wire length: fiftyFeetOrLess (1) indicates that the wire length is less than or equal to 50 feet. moreThanFiftyFeet (2) indicates that the wire length is greater than 50 feet.
| |||||||||||||||||||||
| SbattManConfigDischargeVoltageAlarmLevel | 1.3.6.1.4.1.318.1.1.16.6.18 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The discharge voltage alarm level in percent. | |||||||||||||||||||||
| SbattManConfigAutoAnnunciatorReset | 1.3.6.1.4.1.318.1.1.16.6.19 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The annunciator output signal reset method: disabled(1) means the annunciator signal output will be reset when the reset button is pressed. enabled(2) means the annunciator will stop signaling when all alarm conditions clear.
| |||||||||||||||||||||
| SbattManConfigSuspendCellVoltage | 1.3.6.1.4.1.318.1.1.16.6.20 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory This is used along with the number of cells per battery and the number of batteries per string to determine if a battery string has violated the low voltage limit. If so, the Battery Management System will enter suspend mode. Measured in millivolts DC | |||||||||||||||||||||
| SbattManConfigOhmicTestWaitTime | 1.3.6.1.4.1.318.1.1.16.6.21 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The amount of time in seconds after a discharge event before data will be collected for the ohmic value calculation. | |||||||||||||||||||||
| SbattManConfigNumberOfBoosts | 1.3.6.1.4.1.318.1.1.16.6.22 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The number of consecutive times the Battery Management System applies a charge to each battery during a boost cycle. Batteries with a Rated Battery AH Capacity less than or equal to 120 AH will always have a value of one for Number of Boosts. | |||||||||||||||||||||
| NbattManAlarm | 1.3.6.1.4.1.318.1.1.16.7 | ||||||||||||||||||||
| SbattManAlarmManagementController | 1.3.6.1.4.1.318.1.1.16.7.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The Management Controller Alarm is : normal(1) no alarm conditions identified alarm(2) an alarm condition exists.
| |||||||||||||||||||||
| SbattManAlarmBatteries | 1.3.6.1.4.1.318.1.1.16.7.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The Batteries Alarm is : normal(1) no alarm conditions identified alarm(2) an alarm condition exists.
| |||||||||||||||||||||
| SbattManAlarmCharger | 1.3.6.1.4.1.318.1.1.16.7.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The Charger Alarm is : normal(1) no alarm conditions identified alarm(2) an alarm condition exists.
| |||||||||||||||||||||
| SbattManAlarmEnvironment | 1.3.6.1.4.1.318.1.1.16.7.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The Environment Alarm is : normal(1) no alarm conditions identified alarm(2) an alarm condition exists.
| |||||||||||||||||||||
| NbattManSystemStatus | 1.3.6.1.4.1.318.1.1.16.8 | ||||||||||||||||||||
| SbattManSystemAmbientTempC | 1.3.6.1.4.1.318.1.1.16.8.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The system ambient temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| SbattManSystemAmbientTempF | 1.3.6.1.4.1.318.1.1.16.8.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The system ambient temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SbattManSystemPilotTempC | 1.3.6.1.4.1.318.1.1.16.8.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The system pilot temperature in tenths of degrees Celsius. | |||||||||||||||||||||
| SbattManSystemPilotTempF | 1.3.6.1.4.1.318.1.1.16.8.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The system pilot temperature in tenths of degrees Fahrenheit. | |||||||||||||||||||||
| SbattManSystemAmbientHighTempAlarm | 1.3.6.1.4.1.318.1.1.16.8.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory When set to alarm(2), indicates that the system has a high temperature alarm.
| |||||||||||||||||||||
| SbattManSystemAmbientLowTempAlarm | 1.3.6.1.4.1.318.1.1.16.8.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory When set to alarm(2), indicates that the system has a low temperature alarm.
| |||||||||||||||||||||
| SbattManSystemPilotBatteryHighTempAlarm | 1.3.6.1.4.1.318.1.1.16.8.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory When set to alarm(2), indicates that the system has a pilot battery high temperature alarm.
| |||||||||||||||||||||
| SbattManSystemPilotProbeDisconnected | 1.3.6.1.4.1.318.1.1.16.8.8 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory When set to alarm(2), indicates that the system pilot probe is disconnected.
| |||||||||||||||||||||
| SbattManSystemAmbientProbeDisconnected | 1.3.6.1.4.1.318.1.1.16.8.9 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory When set to alarm(2), indicates that the system ambient probe is disconnected.
| |||||||||||||||||||||
| SbattManSystemConfigurationInvalid | 1.3.6.1.4.1.318.1.1.16.8.10 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory When set to alarm(2), indicates that the system is not configured correctly.
| |||||||||||||||||||||
| SbattManSystemSuspendVoltage | 1.3.6.1.4.1.318.1.1.16.8.11 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory When set to alarm(2), indicates that the system has suspended voltage scans.
| |||||||||||||||||||||
| NbattManStringStatus | 1.3.6.1.4.1.318.1.1.16.9 | ||||||||||||||||||||
| SbattManStringTableSize | 1.3.6.1.4.1.318.1.1.16.9.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the battManStringTable. | |||||||||||||||||||||
| TbattManStringTable | 1.3.6.1.4.1.318.1.1.16.9.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting information from each string in the system. | |||||||||||||||||||||
| RbattManStringEntry | 1.3.6.1.4.1.318.1.1.16.9.2.1 | NA | mandatory | ||||||||||||||||||
| CbattManStringIndex | 1.3.6.1.4.1.318.1.1.16.9.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Index of string entries in the table. | |||||||||||||||||||||
| CbattManStringCurrent | 1.3.6.1.4.1.318.1.1.16.9.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The string current in tenths of amps. | |||||||||||||||||||||
| CbattManStringRippleCurrent | 1.3.6.1.4.1.318.1.1.16.9.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The string ripple current in tenths of amps. | |||||||||||||||||||||
| CbattManStringChargerHighVoltageAlarm | 1.3.6.1.4.1.318.1.1.16.9.2.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory When set to alarm(2), indicates that the string charger has a high voltage alarm.
| |||||||||||||||||||||
| CbattManStringChargerLowVoltageAlarm | 1.3.6.1.4.1.318.1.1.16.9.2.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory When set to alarm(2), indicates that the string charger has a low voltage alarm.
| |||||||||||||||||||||
| CbattManStringCurrentProbeDisconnected | 1.3.6.1.4.1.318.1.1.16.9.2.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory When set to alarm(2), indicates that the string charger probe is disconnected.
| |||||||||||||||||||||
| CbattManStringOnBattery | 1.3.6.1.4.1.318.1.1.16.9.2.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory When set to alarm(2), indicates that the string is in the on-battery state.
| |||||||||||||||||||||
| CbattManStringHighRippleCurrent | 1.3.6.1.4.1.318.1.1.16.9.2.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory When set to alarm(2), indicates that the string has a high ripple current.
| |||||||||||||||||||||
| CbattManStringVoltage | 1.3.6.1.4.1.318.1.1.16.9.2.1.9 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The sum of the voltages for all of the batteries on a string in millivolts DC. | |||||||||||||||||||||
| CbattManStringDischargeLess5Seconds | 1.3.6.1.4.1.318.1.1.16.9.2.1.10 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The number of recorded discharges lasting less than 5 seconds. | |||||||||||||||||||||
| CbattManStringDischarge5to10Seconds | 1.3.6.1.4.1.318.1.1.16.9.2.1.11 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The number of recorded discharges lasting between 5 and 10 seconds. | |||||||||||||||||||||
| CbattManStringDischarge10to60Seconds | 1.3.6.1.4.1.318.1.1.16.9.2.1.12 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The number of recorded discharges lasting between 10 and 60 seconds. | |||||||||||||||||||||
| CbattManStringDischargeMore60Seconds | 1.3.6.1.4.1.318.1.1.16.9.2.1.13 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The number of recorded discharges lasting more than 60 seconds (1 minute). | |||||||||||||||||||||
| NbattManBatteryStatus | 1.3.6.1.4.1.318.1.1.16.10 | ||||||||||||||||||||
| SbattManString1BatteryTableSize | 1.3.6.1.4.1.318.1.1.16.10.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the battManString1BatteryTable. | |||||||||||||||||||||
| TbattManString1BatteryTable | 1.3.6.1.4.1.318.1.1.16.10.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting information from each string in the system. | |||||||||||||||||||||
| RbattManString1BatteryEntry | 1.3.6.1.4.1.318.1.1.16.10.2.1 | NA | mandatory | ||||||||||||||||||
| CbattManString1BatteryIndex | 1.3.6.1.4.1.318.1.1.16.10.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Index of string entries in the table. | |||||||||||||||||||||
| CbattManString1BatteryVoltage | 1.3.6.1.4.1.318.1.1.16.10.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The battery voltage in millivolts DC. | |||||||||||||||||||||
| CbattManString1BatteryLowestVoltage | 1.3.6.1.4.1.318.1.1.16.10.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The lowest battery discharge voltage during the last power event in millivolts DC. | |||||||||||||||||||||
| CbattManString1BatteryCellShorted | 1.3.6.1.4.1.318.1.1.16.10.2.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory When set to alarm(2), indicates that a battery cell is shorted.
| |||||||||||||||||||||
| CbattManString1BatteryOpenFuseOrConnection | 1.3.6.1.4.1.318.1.1.16.10.2.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory When set to alarm(2), indicates that a fuse or connection is open.
| |||||||||||||||||||||
| CbattManString1BatteryLowCapacity | 1.3.6.1.4.1.318.1.1.16.10.2.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory When set to alarm(2), indicates a battery has low capacity.
| |||||||||||||||||||||
| CbattManString1BatteryHighOhmicValue | 1.3.6.1.4.1.318.1.1.16.10.2.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory When set to alarm(2), indicates a battery has a high ohmic value.
| |||||||||||||||||||||
| CbattManString1BatteryThermalRunaway | 1.3.6.1.4.1.318.1.1.16.10.2.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory When set to alarm(2), indicates a battery has a thermal runaway condition.
| |||||||||||||||||||||
| CbattManString1BatteryDryout | 1.3.6.1.4.1.318.1.1.16.10.2.1.9 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory When set to alarm(2), indicates a battery has a dryout condition.
| |||||||||||||||||||||
| CbattManString1BatteryUserHighVoltageAlarm | 1.3.6.1.4.1.318.1.1.16.10.2.1.10 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory When set to alarm(2), indicates a battery has violated the user level high voltage limit.
| |||||||||||||||||||||
| CbattManString1BatteryUserLowVoltageAlarm | 1.3.6.1.4.1.318.1.1.16.10.2.1.11 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory When set to alarm(2), indicates a battery has violated the user level low voltage limit.
| |||||||||||||||||||||
| CbattManString1BatteryChemHighVoltageAlarm | 1.3.6.1.4.1.318.1.1.16.10.2.1.12 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory When set to alarm(2), indicates a battery has violated the chemistry level high voltage limit.
| |||||||||||||||||||||
| CbattManString1BatteryChemLowVoltageAlarm | 1.3.6.1.4.1.318.1.1.16.10.2.1.13 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory When set to alarm(2), indicates a battery has violated the chemistry level low voltage limit.
| |||||||||||||||||||||
| CbattManString1BatteryOpenCell | 1.3.6.1.4.1.318.1.1.16.10.2.1.14 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory When set to alarm(2), indicates the battery has an open cell or an inter-connection is abnormal.
| |||||||||||||||||||||
| SbattManString2BatteryTableSize | 1.3.6.1.4.1.318.1.1.16.10.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the battManString2BatteryTable. | |||||||||||||||||||||
| TbattManString2BatteryTable | 1.3.6.1.4.1.318.1.1.16.10.4 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting information from each string in the system. | |||||||||||||||||||||
| RbattManString2BatteryEntry | 1.3.6.1.4.1.318.1.1.16.10.4.1 | NA | mandatory | ||||||||||||||||||
| CbattManString2BatteryIndex | 1.3.6.1.4.1.318.1.1.16.10.4.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Index of string entries in the table. | |||||||||||||||||||||
| CbattManString2BatteryVoltage | 1.3.6.1.4.1.318.1.1.16.10.4.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The battery voltage in millivolts DC. | |||||||||||||||||||||
| CbattManString2BatteryLowestVoltage | 1.3.6.1.4.1.318.1.1.16.10.4.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The lowest battery discharge voltage during the last power event in millivolts DC. | |||||||||||||||||||||
| CbattManString2BatteryCellShorted | 1.3.6.1.4.1.318.1.1.16.10.4.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory When set to alarm(2), indicates that a battery cell is shorted.
| |||||||||||||||||||||
| CbattManString2BatteryOpenFuseOrConnection | 1.3.6.1.4.1.318.1.1.16.10.4.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory When set to alarm(2), indicates that a fuse or connection is open.
| |||||||||||||||||||||
| CbattManString2BatteryLowCapacity | 1.3.6.1.4.1.318.1.1.16.10.4.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory When set to alarm(2), indicates a battery has low capacity.
| |||||||||||||||||||||
| CbattManString2BatteryHighOhmicValue | 1.3.6.1.4.1.318.1.1.16.10.4.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory When set to alarm(2), indicates a battery has a high ohmic value.
| |||||||||||||||||||||
| CbattManString2BatteryThermalRunaway | 1.3.6.1.4.1.318.1.1.16.10.4.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory When set to alarm(2), indicates a battery has a thermal runaway condition.
| |||||||||||||||||||||
| CbattManString2BatteryDryout | 1.3.6.1.4.1.318.1.1.16.10.4.1.9 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory When set to alarm(2), indicates a battery has a dryout condition.
| |||||||||||||||||||||
| CbattManString2BatteryUserHighVoltageAlarm | 1.3.6.1.4.1.318.1.1.16.10.4.1.10 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory When set to alarm(2), indicates a battery has violated the user level high voltage limit.
| |||||||||||||||||||||
| CbattManString2BatteryUserLowVoltageAlarm | 1.3.6.1.4.1.318.1.1.16.10.4.1.11 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory When set to alarm(2), indicates a battery has violated the user level low voltage limit.
| |||||||||||||||||||||
| CbattManString2BatteryChemHighVoltageAlarm | 1.3.6.1.4.1.318.1.1.16.10.4.1.12 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory When set to alarm(2), indicates a battery has violated the chemistry level high voltage limit.
| |||||||||||||||||||||
| CbattManString2BatteryChemLowVoltageAlarm | 1.3.6.1.4.1.318.1.1.16.10.4.1.13 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory When set to alarm(2), indicates a battery has violated the chemistry level low voltage limit.
| |||||||||||||||||||||
| CbattManString2BatteryOpenCell | 1.3.6.1.4.1.318.1.1.16.10.4.1.14 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory When set to alarm(2), indicates the battery has an open cell or an inter-connection is abnormal.
| |||||||||||||||||||||
| NbattManInputContactStatus | 1.3.6.1.4.1.318.1.1.16.11 | ||||||||||||||||||||
| SbattManInputContactTableSize | 1.3.6.1.4.1.318.1.1.16.11.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the battManInputContactTable. | |||||||||||||||||||||
| TbattManInputContactTable | 1.3.6.1.4.1.318.1.1.16.11.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting information from each contact in the system. | |||||||||||||||||||||
| RbattManInputContactEntry | 1.3.6.1.4.1.318.1.1.16.11.2.1 | NA | mandatory | ||||||||||||||||||
| CbattManInputContactIndex | 1.3.6.1.4.1.318.1.1.16.11.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Index of contact entries in the table. | |||||||||||||||||||||
| CbattManInputContactName | 1.3.6.1.4.1.318.1.1.16.11.2.1.2 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The name of the input contact. | |||||||||||||||||||||
| CbattManInputContactAlarmState | 1.3.6.1.4.1.318.1.1.16.11.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory When set to alarm(2), indicates that the alarm condition is active for this contact.
| |||||||||||||||||||||
| CbattManInputContactState | 1.3.6.1.4.1.318.1.1.16.11.2.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory When set to open(1), the input contact is in the open state. When set to closed(2), the input contact is in the closed state.
| |||||||||||||||||||||
| CbattManInputContactNormalState | 1.3.6.1.4.1.318.1.1.16.11.2.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory When set to open(1), the input contact is normally open. When set to closed(2), the input contact is normally closed.
| |||||||||||||||||||||
| CbattManInputContactAlarmDelay | 1.3.6.1.4.1.318.1.1.16.11.2.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The input contact alarm delay time in seconds. | |||||||||||||||||||||
| NbattManControl | 1.3.6.1.4.1.318.1.1.16.12 | ||||||||||||||||||||
| SbattManRemoteAnnunciatorReset | 1.3.6.1.4.1.318.1.1.16.12.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Setting this OID to reset(2) will reset the user interface annunciator. Getting this OID will do nothing and return the noOperation(1) value.
| |||||||||||||||||||||
| SbattManResetChargeCurrentDeviationBenchmark | 1.3.6.1.4.1.318.1.1.16.12.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Setting this OID to reset(2) will reset the charge current deviation benchmark. Getting this OID will do nothing and return the noOperation(1) value.
| |||||||||||||||||||||
| SbattManResetLowestDischargeVoltages | 1.3.6.1.4.1.318.1.1.16.12.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Setting this OID to reset(2) will reset the lowest discharge voltages. Getting this OID will do nothing and return the noOperation(1) value.
| |||||||||||||||||||||
| SbattManResetDischargeCounters | 1.3.6.1.4.1.318.1.1.16.12.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Setting this OID to reset(2) will reset all discharge event counters. Getting this OID will do nothing and return the noOperation(1) value.
| |||||||||||||||||||||
| NbattManTestResults | 1.3.6.1.4.1.318.1.1.16.13 | ||||||||||||||||||||
| SbattManString1OhmicValueLastDischargeInfo | 1.3.6.1.4.1.318.1.1.16.13.1 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory Informational text showing the date/time, load, and pilot temperature for the string during the last discharge when ohmic values were recorded. | |||||||||||||||||||||
| SbattManString1OhmicValueTableSize | 1.3.6.1.4.1.318.1.1.16.13.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the battManString1OhmicValueTable. | |||||||||||||||||||||
| TbattManString1OhmicValueTable | 1.3.6.1.4.1.318.1.1.16.13.3 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting ohmic value information from each battery in String 1. | |||||||||||||||||||||
| RbattManString1OhmicValueEntry | 1.3.6.1.4.1.318.1.1.16.13.3.1 | NA | mandatory | ||||||||||||||||||
| CbattManString1OhmicValueIndex | 1.3.6.1.4.1.318.1.1.16.13.3.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The battery number. | |||||||||||||||||||||
| CbattManString1OhmicValueData | 1.3.6.1.4.1.318.1.1.16.13.3.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The battery inter-tier ohmic value in tenths of milli-Ohms. Note: Zero or negative values are invalid and may indicate faulty calibration of ohmic value correction factors. | |||||||||||||||||||||
| SbattManString1ResponseTestChangeTableSize | 1.3.6.1.4.1.318.1.1.16.13.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the battManString1ResponseTestChangeTable. | |||||||||||||||||||||
| TbattManString1ResponseTestChangeTable | 1.3.6.1.4.1.318.1.1.16.13.5 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting response test change information from each battery in String 1. | |||||||||||||||||||||
| RbattManString1ResponseTestChangeEntry | 1.3.6.1.4.1.318.1.1.16.13.5.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The string to get data from. | |||||||||||||||||||||
| CbattManString1ResponseTestChangeIndex | 1.3.6.1.4.1.318.1.1.16.13.5.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Index of the entries in the table. | |||||||||||||||||||||
| CbattManString1ResponseTestChangeData | 1.3.6.1.4.1.318.1.1.16.13.5.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The battery response test change in percent. | |||||||||||||||||||||
| SbattManString2OhmicValueLastDischargeInfo | 1.3.6.1.4.1.318.1.1.16.13.6 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory Informational text showing the date/time, load, and pilot temperature for the string during the last discharge when ohmic values were recorded. | |||||||||||||||||||||
| SbattManString2OhmicValueTableSize | 1.3.6.1.4.1.318.1.1.16.13.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the battManString2OhmicValueTable. | |||||||||||||||||||||
| TbattManString2OhmicValueTable | 1.3.6.1.4.1.318.1.1.16.13.8 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting ohmic value information from each battery in String 2. | |||||||||||||||||||||
| RbattManString2OhmicValueEntry | 1.3.6.1.4.1.318.1.1.16.13.8.1 | NA | mandatory | ||||||||||||||||||
| CbattManString2OhmicValueIndex | 1.3.6.1.4.1.318.1.1.16.13.8.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Index of battery calibration entries in the table. | |||||||||||||||||||||
| CbattManString2OhmicValueData | 1.3.6.1.4.1.318.1.1.16.13.8.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The battery inter-tier ohmic value in ohms. Note: Zero or negative values are invalid and may indicate faulty calibration of ohmic value correction factors. | |||||||||||||||||||||
| SbattManString2ResponseTestChangeTableSize | 1.3.6.1.4.1.318.1.1.16.13.9 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the battManString2ResponseTestChangeTable. | |||||||||||||||||||||
| TbattManString2ResponseTestChangeTable | 1.3.6.1.4.1.318.1.1.16.13.10 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting response test change information from each battery in String 2. | |||||||||||||||||||||
| RbattManString2ResponseTestChangeEntry | 1.3.6.1.4.1.318.1.1.16.13.10.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The string to get data from. | |||||||||||||||||||||
| CbattManString2ResponseTestChangeIndex | 1.3.6.1.4.1.318.1.1.16.13.10.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Index of the entries in the table. | |||||||||||||||||||||
| CbattManString2ResponseTestChangeData | 1.3.6.1.4.1.318.1.1.16.13.10.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The battery response test change in percent. | |||||||||||||||||||||
| SbattManString1ResponseTestCurrentTableSize | 1.3.6.1.4.1.318.1.1.16.13.11 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the battManString1ResponseTestCurrentTable. | |||||||||||||||||||||
| TbattManString1ResponseTestCurrentTable | 1.3.6.1.4.1.318.1.1.16.13.12 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting response test current information from each battery in String 1. | |||||||||||||||||||||
| RbattManString1ResponseTestCurrentEntry | 1.3.6.1.4.1.318.1.1.16.13.12.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The string to get data from. | |||||||||||||||||||||
| CbattManString1ResponseTestCurrentIndex | 1.3.6.1.4.1.318.1.1.16.13.12.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Index of the entries in the table. | |||||||||||||||||||||
| CbattManString1ResponseTestCurrentData | 1.3.6.1.4.1.318.1.1.16.13.12.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The battery response test current in milliamps. | |||||||||||||||||||||
| SbattManString2ResponseTestCurrentTableSize | 1.3.6.1.4.1.318.1.1.16.13.13 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the battManString2ResponseTestCurrentTable. | |||||||||||||||||||||
| TbattManString2ResponseTestCurrentTable | 1.3.6.1.4.1.318.1.1.16.13.14 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting response test current information from each battery in String 2. | |||||||||||||||||||||
| RbattManString2ResponseTestCurrentEntry | 1.3.6.1.4.1.318.1.1.16.13.14.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The string to get data from. | |||||||||||||||||||||
| CbattManString2ResponseTestCurrentIndex | 1.3.6.1.4.1.318.1.1.16.13.14.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Index of the entries in the table. | |||||||||||||||||||||
| CbattManString2ResponseTestCurrentData | 1.3.6.1.4.1.318.1.1.16.13.14.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The battery response test current in milliamps. | |||||||||||||||||||||
| SbattManString1ResponseTestCurrentBenchmarkTableSize | 1.3.6.1.4.1.318.1.1.16.13.15 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the battManString1ResponseTestCurrentBenchmarkTable. | |||||||||||||||||||||
| TbattManString1ResponseTestCurrentBenchmarkTable | 1.3.6.1.4.1.318.1.1.16.13.16 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting response test current benchmark information from each battery in String 1. | |||||||||||||||||||||
| RbattManString1ResponseTestCurrentBenchmarkEntry | 1.3.6.1.4.1.318.1.1.16.13.16.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The string to get data from. | |||||||||||||||||||||
| CbattManString1ResponseTestCurrentBenchmarkIndex | 1.3.6.1.4.1.318.1.1.16.13.16.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Index of the entries in the table. | |||||||||||||||||||||
| CbattManString1ResponseTestCurrentBenchmarkData | 1.3.6.1.4.1.318.1.1.16.13.16.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The battery response test current benchmark in milliamps. | |||||||||||||||||||||
| SbattManString2ResponseTestCurrentBenchmarkTableSize | 1.3.6.1.4.1.318.1.1.16.13.17 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the battManString2ResponseTestCurrentBenchmarkTable. | |||||||||||||||||||||
| TbattManString2ResponseTestCurrentBenchmarkTable | 1.3.6.1.4.1.318.1.1.16.13.18 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting response test current benchmark information from each battery in String 2. | |||||||||||||||||||||
| RbattManString2ResponseTestCurrentBenchmarkEntry | 1.3.6.1.4.1.318.1.1.16.13.18.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The string to get data from. | |||||||||||||||||||||
| CbattManString2ResponseTestCurrentBenchmarkIndex | 1.3.6.1.4.1.318.1.1.16.13.18.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Index of the entries in the table. | |||||||||||||||||||||
| CbattManString2ResponseTestCurrentBenchmarkData | 1.3.6.1.4.1.318.1.1.16.13.18.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The battery response test current benchmark in milliamps. | |||||||||||||||||||||
| NbattManUnitStatus | 1.3.6.1.4.1.318.1.1.16.14 | ||||||||||||||||||||
| SbattManUnitStatusTableSize | 1.3.6.1.4.1.318.1.1.16.14.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the battManUnitStatusTable. | |||||||||||||||||||||
| TbattManUnitStatusTable | 1.3.6.1.4.1.318.1.1.16.14.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting status information from each unit in the system. | |||||||||||||||||||||
| RbattManUnitStatusEntry | 1.3.6.1.4.1.318.1.1.16.14.2.1 | NA | mandatory | ||||||||||||||||||
| CbattManUnitStatusIndex | 1.3.6.1.4.1.318.1.1.16.14.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Index of unit status entries in the table. | |||||||||||||||||||||
| CbattManUnitStatusSerialNumber | 1.3.6.1.4.1.318.1.1.16.14.2.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The battery manager unit serial number character string. This value is set at the factory. | |||||||||||||||||||||
| CbattManUnitHardwareRev | 1.3.6.1.4.1.318.1.1.16.14.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The battery manager unit hardware revision. This value is set at the factory. | |||||||||||||||||||||
| CbattManUnitFirmwareRev | 1.3.6.1.4.1.318.1.1.16.14.2.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The battery manager unit firmware revision. This value is set at the factory and can change with firmware update. | |||||||||||||||||||||
| CbattManUnitCommLoss | 1.3.6.1.4.1.318.1.1.16.14.2.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory When set to alarm(2), indicates the system has lost communication with the unit.
| |||||||||||||||||||||
| CbattManUnitRelayStuck | 1.3.6.1.4.1.318.1.1.16.14.2.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory When set to alarm(2), indicates the unit monitor relay is stuck.
| |||||||||||||||||||||
| NxATS | 1.3.6.1.4.1.318.1.1.17 | ||||||||||||||||||||
| NxATSIdent | 1.3.6.1.4.1.318.1.1.17.1 | ||||||||||||||||||||
| SxATSIdentProductName | 1.3.6.1.4.1.318.1.1.17.1.1 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory The name of the transfer switch unit. | |||||||||||||||||||||
| SxATSIdentHardwareRev | 1.3.6.1.4.1.318.1.1.17.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The hardware revision of the transfer switch. This value is set at the factory. | |||||||||||||||||||||
| SxATSIdentFirmwareAppRev | 1.3.6.1.4.1.318.1.1.17.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory An ID string identifying the application firmware revision of the transfer switch. | |||||||||||||||||||||
| SxATSIdentFirmwareAppOSRev | 1.3.6.1.4.1.318.1.1.17.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory An ID string identifying the application operating system firmware revision of the transfer switch. | |||||||||||||||||||||
| SxATSIdentFirmwareControllerRev | 1.3.6.1.4.1.318.1.1.17.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory An ID string identifying the transfer switch controller firmware revision. | |||||||||||||||||||||
| SxATSIdentDateOfManufacture | 1.3.6.1.4.1.318.1.1.17.1.6 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The date when the transfer switch was manufactured in mm/dd/yyyy format. This value is set at the factory. | |||||||||||||||||||||
| SxATSIdentModelNumber | 1.3.6.1.4.1.318.1.1.17.1.7 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the model number of the transfer switch. This value is set at the factory. | |||||||||||||||||||||
| SxATSIdentSerialNumber | 1.3.6.1.4.1.318.1.1.17.1.8 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the serial number of the transfer switch. This value is set at the factory. | |||||||||||||||||||||
| NxATSDevice | 1.3.6.1.4.1.318.1.1.17.2 | ||||||||||||||||||||
| SxATSDeviceServiceType | 1.3.6.1.4.1.318.1.1.17.2.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The type of utility input to the transfer switch. Either 3 wires (delta), or 4 wires (wye).
| |||||||||||||||||||||
| SxATSDeviceNominalVoltage | 1.3.6.1.4.1.318.1.1.17.2.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The nominal line-to-neutral system voltage. Measured in Volts, line-to-line for a 3-wire service or line-to-neutral for a 4-wire service. -1 if not available. | |||||||||||||||||||||
| SxATSDeviceNominalFrequency | 1.3.6.1.4.1.318.1.1.17.2.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The nominal system frequency. Measured in tenths of Hertz. -1 if not available. | |||||||||||||||||||||
| SxATSDeviceTransferSwitchRating | 1.3.6.1.4.1.318.1.1.17.2.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The rating of the transfer switch. Measured in Amps. | |||||||||||||||||||||
| SxATSDeviceDCBackUpPresent | 1.3.6.1.4.1.318.1.1.17.2.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Indicates if a DC backup is present or not.
| |||||||||||||||||||||
| NxATSSwitch | 1.3.6.1.4.1.318.1.1.17.3 | ||||||||||||||||||||
| NxATSSwitchStatus | 1.3.6.1.4.1.318.1.1.17.3.1 | ||||||||||||||||||||
| SxATSSwitchStatusSelectedSource | 1.3.6.1.4.1.318.1.1.17.3.1.1 | INTEGER | RO | mandatory | source1(2) | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The source which is currently selected, i.e. supplying power to the load.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxATSSwitchStatusOperationalMode | 1.3.6.1.4.1.318.1.1.17.3.1.2 | INTEGER | RO | mandatory | automatic(1) | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The current operating mode of the transfer switch. When the ATS is in automatic mode, generator starting and ATS transferring is all done automatically as needed based on the state of source 1. Automatic operation is halted when the ATS is in either of the notInAuto modes. A mode of notInAuto indicates that the automatic operation switch is in the disabled position, as indicated by the xATSSwitchStatusAutomaticOperationSwitch OID. The notInAutoAbnormal condition indicates that an abnormal condition has caused the transfer switch to halt automatic operation. In this case, traps can indicate the exact problem. In the case of notInAutoAbnormal, refer to the operation manual for details on how debug the condition and restore automatic operation.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxATSSwitchStatusAutomaticOperationSwitch | 1.3.6.1.4.1.318.1.1.17.3.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The position of the automatic operation switch on the front of the transfer switch.
| |||||||||||||||||||||
| SxATSSwitchStatusEngineStartSignal | 1.3.6.1.4.1.318.1.1.17.3.1.4 | INTEGER | RO | mandatory | stop(2) | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The position of the Start/Stop contact which signals the generator engine to start/run. When the ATS is in automatic mode, generator starting/stopping is under ATS control.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NxATSSwitchSettings | 1.3.6.1.4.1.318.1.1.17.3.2 | ||||||||||||||||||||
| SxATSSwitchSettingsLowVoltageTransferPoint | 1.3.6.1.4.1.318.1.1.17.3.2.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The lowest acceptable voltage condition at source 1. When any phase of source 1 is lower than this voltage, source quality is considered bad and the generator run signal is asserted to begin generator operation. Specified in volts, line-to-line for a 3-wire service or line-to-neutral for a 4-wire service. -1 if not available. | |||||||||||||||||||||
| SxATSSwitchSettingsHighVoltageTransferPoint | 1.3.6.1.4.1.318.1.1.17.3.2.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The highest acceptable voltage condition at source 1. When any phase of source 1 is greater than this voltage, source quality is considered bad and the generator run signal is asserted to begin generator operation. Specified in volts, line-to-line for a 3-wire service or line-to-neutral for a 4-wire service. -1 if not available. | |||||||||||||||||||||
| SxATSSwitchSettingsMaxFrequencyDeviation | 1.3.6.1.4.1.318.1.1.17.3.2.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The maximum acceptable frequency deviation condition from nominal at source 1. When source 1 frequency is outside the specified range, source quality is considered bad and the generator run signal is asserted to begin generator operation. Specified in tenths of Hertz above or below nominal. A value of zero indicates that frequency is ignored when determining source quality. -1 if not available. | |||||||||||||||||||||
| SxATSSwitchSettingsMinPhaseBalance | 1.3.6.1.4.1.318.1.1.17.3.2.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The minimum required phase balance at source 1. When the percentage difference between the minimum and maximum phase voltage measurements at source 1 is greater than this value, source quality is considered bad and the generator run signal is asserted to begin generator operation. Specified as a percentage. A value of zero indicates that phase balance is ignored when determining source quality. -1 if not available. | |||||||||||||||||||||
| SxATSSwitchSettingsNominalRotation | 1.3.6.1.4.1.318.1.1.17.3.2.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The nominal phase rotation (or phase sequence) required by the load. For certain types of equipment, such as rotating machinery, phase rotation is critical for proper operation as it determines the direction which motors will rotate (clockwise or counterclockwise). Source quality will be seen as bad if the rotation measured at that ATS input does not match this setting. If this setting is set to any, phase rotation is ignored.
| |||||||||||||||||||||
| SxATSSwitchSettingsAllowClosedTransfer | 1.3.6.1.4.1.318.1.1.17.3.2.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory This setting enables seamless (closed) transfers between sources. When possible, both source 1 and source 2 are closed to the output for a brief time. If closed transfer is not possible within the amount of time specified by the xATSSwitchSettingsMaxSyncTime OID, an open transfer will be executed.
| |||||||||||||||||||||
| SxATSSwitchSettingsMaxSyncTime | 1.3.6.1.4.1.318.1.1.17.3.2.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory When attempting/seeking to perform a closed transfer, this setting defines the maximum time allowed before the transfer switch will give up and perform an open transfer. Specified in seconds. -1 if not available. | |||||||||||||||||||||
| SxATSSwitchSettingsNeutralTransferTime | 1.3.6.1.4.1.318.1.1.17.3.2.8 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory This setting defines how long both source 1 and source 2 will be disconnected from the output, during an open transfer. Specified in seconds. -1 if not available. | |||||||||||||||||||||
| SxATSSwitchSettingsClearLatchedAlarms | 1.3.6.1.4.1.318.1.1.17.3.2.9 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Clears any latched alarm conditions.
| |||||||||||||||||||||
| SxATSSwitchSettingsSetToFactoryDefaults | 1.3.6.1.4.1.318.1.1.17.3.2.10 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Sets all transfer switch settings to factory default values.
| |||||||||||||||||||||
| NxATSSwitchTimers | 1.3.6.1.4.1.318.1.1.17.3.3 | ||||||||||||||||||||
| SxATSSwitchTimersTableSize | 1.3.6.1.4.1.318.1.1.17.3.3.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of transfer switch timer entries. | |||||||||||||||||||||
| TxATSSwitchTimersTable | 1.3.6.1.4.1.318.1.1.17.3.3.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of timers supported by ATS. The number of entries is contained in the xATSSwitchTimersTableSize OID. | |||||||||||||||||||||
| RxATSSwitchTimersEntry | 1.3.6.1.4.1.318.1.1.17.3.3.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information about an individual ATS timer. | |||||||||||||||||||||
| CxATSSwitchTimersIndex | 1.3.6.1.4.1.318.1.1.17.3.3.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Index of timer entries in the table. | |||||||||||||||||||||
| CxATSSwitchTimersName | 1.3.6.1.4.1.318.1.1.17.3.3.2.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory Name of the individual timer.Refer to ATS operation manual, or on-line help, for detailed descriptions of ATS timers. | |||||||||||||||||||||
| CxATSSwitchTimersAbort | 1.3.6.1.4.1.318.1.1.17.3.3.2.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory This aborts the individual timer.
| |||||||||||||||||||||
| CxATSSwitchTimersStatus | 1.3.6.1.4.1.318.1.1.17.3.3.2.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The status of the individual timer. Designates whether this timer entry is currently running or inactive.
| |||||||||||||||||||||
| CxATSSwitchTimersRemainingTime | 1.3.6.1.4.1.318.1.1.17.3.3.2.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The time remaining for this timer entry. Specified in seconds. | |||||||||||||||||||||
| CxATSSwitchTimersDelaySetting | 1.3.6.1.4.1.318.1.1.17.3.3.2.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The delay settings associated with this timer entry. When this timer entry is active, the timer value must exceed this setting before the ATS behavior associated with this timer is executed. Refer to ATS operation manual, or on-line help, for detailed descriptions of ATS timers. | |||||||||||||||||||||
| NxATSSwitchBlockMap | 1.3.6.1.4.1.318.1.1.17.3.4 | ||||||||||||||||||||
| SxATSSwitchBlockMapTableSize | 1.3.6.1.4.1.318.1.1.17.3.4.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of blocking map entries, or how many ATS actions can be blocked. | |||||||||||||||||||||
| TxATSSwitchBlockMapTable | 1.3.6.1.4.1.318.1.1.17.3.4.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of blocking maps supported by the ATS. The number of entries is contained in the xATSSwitchBlockMapTableSize OID. | |||||||||||||||||||||
| RxATSSwitchBlockMapEntry | 1.3.6.1.4.1.318.1.1.17.3.4.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information about a specific ATS blocking map. | |||||||||||||||||||||
| CxATSSwitchBlockMapIndex | 1.3.6.1.4.1.318.1.1.17.3.4.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Index of blocking map entries in the table. | |||||||||||||||||||||
| CxATSSwitchBlockMapName | 1.3.6.1.4.1.318.1.1.17.3.4.2.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory A string describing the ATS action to be blocked. | |||||||||||||||||||||
| CxATSSwitchBlockMapStatus | 1.3.6.1.4.1.318.1.1.17.3.4.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Represents the status of this blocking map entry, in bit-mapped format. A non-zero value indicates that this entry's ATS action is currently being blocked. The bit(s) set indicate which input(s) are causing the blocking (bit0, bit1, etc). bit 0 - Contact 1 bit 1 - Contact 2 bit 2 - Contact 3 bit 3 - Contact 4. | |||||||||||||||||||||
| CxATSSwitchBlockMapSetting | 1.3.6.1.4.1.318.1.1.17.3.4.2.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory This setting designates the inputs that block the ATS action The mapping is specified as a bit-field, where each bit set indicates the input that blocks the ATS action associated with the entry. bit 0 - Contact 1 bit 1 - Contact 2 bit 2 - Contact 3 bit 3 - Contact 4. | |||||||||||||||||||||
| NxATSSwitchStatistics | 1.3.6.1.4.1.318.1.1.17.3.5 | ||||||||||||||||||||
| SxATSSwitchStatisticsTableSize | 1.3.6.1.4.1.318.1.1.17.3.5.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of transfer switch statistics entries. | |||||||||||||||||||||
| TxATSSwitchStatisticsTable | 1.3.6.1.4.1.318.1.1.17.3.5.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of statistics supported by ATS. The number of entries is contained in the xATSSwitchStatisticsTableSize OID. | |||||||||||||||||||||
| RxATSSwitchStatisticsEntry | 1.3.6.1.4.1.318.1.1.17.3.5.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information about an individual ATS statistic. | |||||||||||||||||||||
| CxATSSwitchStatisticsIndex | 1.3.6.1.4.1.318.1.1.17.3.5.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Index of ATS statistics entries in the table. | |||||||||||||||||||||
| CxATSSwitchStatisticsName | 1.3.6.1.4.1.318.1.1.17.3.5.2.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory This is the name of the ATS statistic associated with this entry. | |||||||||||||||||||||
| CxATSSwitchStatisticsValue | 1.3.6.1.4.1.318.1.1.17.3.5.2.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory This is the value of the ATS statistic associated with this entry. | |||||||||||||||||||||
| CxATSSwitchStatisticsReset | 1.3.6.1.4.1.318.1.1.17.3.5.2.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory This will reset the individual ATS statistic associated with this entry.
| |||||||||||||||||||||
| NxATSACMonitoringPoint | 1.3.6.1.4.1.318.1.1.17.4 | ||||||||||||||||||||
| NxATSSource1 | 1.3.6.1.4.1.318.1.1.17.4.1 | ||||||||||||||||||||
| SxATSSource1Name | 1.3.6.1.4.1.318.1.1.17.4.1.1 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory String used to identify source 1. | |||||||||||||||||||||
| SxATSSource1Position | 1.3.6.1.4.1.318.1.1.17.4.1.2 | INTEGER | RO | mandatory | closed(2) | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The current position of the switch at source 1.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxATSSource1Frequency | 1.3.6.1.4.1.318.1.1.17.4.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The frequency at source 1 in tenths of Hertz. -1 if unavailable. | |||||||||||||||||||||
| SxATSSource1Quality | 1.3.6.1.4.1.318.1.1.17.4.1.4 | INTEGER | RO | mandatory | sourceGood(1) | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The current line quality of source 1.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxATSSource1Rotation | 1.3.6.1.4.1.318.1.1.17.4.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The phase rotation measured at the source 1 input of the ATS. The sequence is a reference to the order in which the three phases pass the zero-crossing boundary in time.
| |||||||||||||||||||||
| SxATSSource1TableSize | 1.3.6.1.4.1.318.1.1.17.4.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of input voltage entries at the source 1 input of the ATS. | |||||||||||||||||||||
| TxATSSource1PhaseTable | 1.3.6.1.4.1.318.1.1.17.4.1.7 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of voltage table entries for source 1. The number of entries are the phase entries. The number of entries is contained in the xATSSource1TableSize OID. | |||||||||||||||||||||
| RxATSSource1PhaseEntry | 1.3.6.1.4.1.318.1.1.17.4.1.7.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular input voltage phase at the source 1 input of the ATS.
| |||||||||||||||||||||
| CxATSSource1Index | 1.3.6.1.4.1.318.1.1.17.4.1.7.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Description of each phase utilized at source 1.
| |||||||||||||||||||||
| CxATSSource1VoltageLtoL | 1.3.6.1.4.1.318.1.1.17.4.1.7.1.2 | INTEGER | RO | mandatory | 4704 | ||||||||||||||||
| CxATSSource1VoltageLtoN | 1.3.6.1.4.1.318.1.1.17.4.1.7.1.3 | INTEGER | RO | mandatory | -1 | ||||||||||||||||
column · INTEGER · read-only · mandatory Source 1 line-to-neutral input voltage. Measured in tenths of Volts. -1 for a 3-wire service type. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NxATSSource2 | 1.3.6.1.4.1.318.1.1.17.4.2 | ||||||||||||||||||||
| SxATSSource2Name | 1.3.6.1.4.1.318.1.1.17.4.2.1 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory String used to identify source 2. | |||||||||||||||||||||
| SxATSSource2Position | 1.3.6.1.4.1.318.1.1.17.4.2.2 | INTEGER | RO | mandatory | open(1) | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The current position of the switch at source 2.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxATSSource2Frequency | 1.3.6.1.4.1.318.1.1.17.4.2.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The frequency at source 2 in tenths of Hertz. -1 if not available. | |||||||||||||||||||||
| SxATSSource2Quality | 1.3.6.1.4.1.318.1.1.17.4.2.4 | INTEGER | RO | mandatory | lowVoltage(2) | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The current line quality of source 2.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxATSSource2Rotation | 1.3.6.1.4.1.318.1.1.17.4.2.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The phase rotation measured at the source 2 input of the ATS. -1 if not available.
| |||||||||||||||||||||
| SxATSSource2TableSize | 1.3.6.1.4.1.318.1.1.17.4.2.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of input voltage entries at the source 2 input of the ATS. | |||||||||||||||||||||
| TxATSSource2PhaseTable | 1.3.6.1.4.1.318.1.1.17.4.2.7 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of voltage table entries for the source 2. The number of entries are the phase entries. The number of entries is contained in the xATSSource2TableSize OID. | |||||||||||||||||||||
| RxATSSource2PhaseEntry | 1.3.6.1.4.1.318.1.1.17.4.2.7.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular input voltage phase at the source 2 input of the ATS.
| |||||||||||||||||||||
| CxATSSource2Index | 1.3.6.1.4.1.318.1.1.17.4.2.7.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Description of each phase utilized at the source 2.
| |||||||||||||||||||||
| CxATSSource2VoltageLtoL | 1.3.6.1.4.1.318.1.1.17.4.2.7.1.2 | INTEGER | RO | mandatory | 4 | ||||||||||||||||
| CxATSSource2VoltageLtoN | 1.3.6.1.4.1.318.1.1.17.4.2.7.1.3 | INTEGER | RO | mandatory | -1 | ||||||||||||||||
column · INTEGER · read-only · mandatory Source 2 line-to-neutral input voltage. Measured in tenths of Volts. -1 for a 3-wire service type. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NxATSSystemOutput | 1.3.6.1.4.1.318.1.1.17.4.3 | ||||||||||||||||||||
| SxATSSystemOutputFrequency | 1.3.6.1.4.1.318.1.1.17.4.3.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The system output frequency in tenths of Hertz. | |||||||||||||||||||||
| SxATSSystemOutputTotalPower | 1.3.6.1.4.1.318.1.1.17.4.3.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Shows the total system output power in tenths of kW. | |||||||||||||||||||||
| SxATSSystemOutputTotalApparentPower | 1.3.6.1.4.1.318.1.1.17.4.3.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Shows the total system output power in tenths of kVA. | |||||||||||||||||||||
| SxATSSystemOutputTotalPowerFactor | 1.3.6.1.4.1.318.1.1.17.4.3.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Indicates the total power factor of the system output. A value of 100 representing a unity power factor (1.00) Specified in hundredths. | |||||||||||||||||||||
| SxATSSystemOutputFrequencyTolerance | 1.3.6.1.4.1.318.1.1.17.4.3.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Shows the panel output frequency tolerance in +/- Hertz.
| |||||||||||||||||||||
| SxATSSystemOutputOverVoltThreshold | 1.3.6.1.4.1.318.1.1.17.4.3.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Threshold above which an output over voltage condition will be generated. Specified as tenths of percent deviation from nominal. A value of zero indicates that the threshold is disabled. | |||||||||||||||||||||
| SxATSSystemOutputUnderVoltThreshold | 1.3.6.1.4.1.318.1.1.17.4.3.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Threshold below which an output under voltage condition will be generated. Specified as tenths of percent deviation from nominal. A value of zero indicates that the threshold is disabled. | |||||||||||||||||||||
| SxATSSystemOutputOverCurrentThreshold | 1.3.6.1.4.1.318.1.1.17.4.3.8 | INTEGER (0..100) | RW | mandatory | |||||||||||||||||
scalar · INTEGER (0..100) · read-write · mandatory Threshold above which an over current condition will be generated. Specified as a percent of the transfer switch rating (xATSDeviceTransferSwitchRating OID). A value of zero indicates that the threshold is disabled. | |||||||||||||||||||||
| SxATSSystemOutputUnderCurrentThreshold | 1.3.6.1.4.1.318.1.1.17.4.3.9 | INTEGER (0..100) | RW | mandatory | |||||||||||||||||
scalar · INTEGER (0..100) · read-write · mandatory Threshold below which an under current condition will be generated. Specified as a percent of the transfer switch rating (xATSDeviceTransferSwitchRating OID). A value of zero indicates that the threshold is disabled. | |||||||||||||||||||||
| SxATSSystemOutputAlarmDelayThreshold | 1.3.6.1.4.1.318.1.1.17.4.3.10 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Delay the generation of an output alarm. Specified in seconds. | |||||||||||||||||||||
| SxATSSystemOutputTableSize | 1.3.6.1.4.1.318.1.1.17.4.3.11 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of system output phase entries. | |||||||||||||||||||||
| TxATSSystemOutputPhaseTable | 1.3.6.1.4.1.318.1.1.17.4.3.12 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of system output table entries. The number of entries is contained in the xATSSystemOutputTableSize OID. | |||||||||||||||||||||
| RxATSSystemOutputPhaseEntry | 1.3.6.1.4.1.318.1.1.17.4.3.12.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular system output phase. | |||||||||||||||||||||
| CxATSSystemOutputPhaseIndex | 1.3.6.1.4.1.318.1.1.17.4.3.12.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Description of each system output phase utilized in this device.
| |||||||||||||||||||||
| CxATSSystemOutputVoltageLtoL | 1.3.6.1.4.1.318.1.1.17.4.3.12.1.2 | INTEGER | RO | mandatory | 4678 | ||||||||||||||||
| CxATSSystemOutputVoltageLtoN | 1.3.6.1.4.1.318.1.1.17.4.3.12.1.3 | INTEGER | RO | mandatory | -1 | ||||||||||||||||
column · INTEGER · read-only · mandatory Line-to-neutral system output voltage available at the circuit panel. Measured in tenths of Volts. -1 for a 3-wire service type or if not available. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CxATSSystemOutputPhaseCurrent | 1.3.6.1.4.1.318.1.1.17.4.3.12.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory System load current per phase. Measured in Amps. -1 if not available. | |||||||||||||||||||||
| CxATSSystemOutputPower | 1.3.6.1.4.1.318.1.1.17.4.3.12.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory System output power per phase. Measured in tenths of kW. | |||||||||||||||||||||
| CxATSSystemOutputApparentPower | 1.3.6.1.4.1.318.1.1.17.4.3.12.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory system output power per phase. Measured in tenths of kVA. | |||||||||||||||||||||
| CxATSSystemOutputPowerFactor | 1.3.6.1.4.1.318.1.1.17.4.3.12.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory indicates the power factor of the system output per phase. A value of 100 representing a unity power factor (1.00). Measured in hundredths. | |||||||||||||||||||||
| NxATSTesting | 1.3.6.1.4.1.318.1.1.17.5 | ||||||||||||||||||||
| NxATSTestingStatus | 1.3.6.1.4.1.318.1.1.17.5.1 | ||||||||||||||||||||
| SxATSTestingStatusSelectTestProcess | 1.3.6.1.4.1.318.1.1.17.5.1.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Type of tests that can be selected when no test has been scheduled. engineStartTest and systemLoadTest may be selected when no tests are running. Tests that are selected may be canceled manually.
| |||||||||||||||||||||
| SxATSTestingStatusTestStatus | 1.3.6.1.4.1.318.1.1.17.5.1.2 | INTEGER | RO | mandatory | noTestInProcess(1) | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The present system test status/state.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxATSTestingStatusProfileWarmupTime | 1.3.6.1.4.1.318.1.1.17.5.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The amount of time that the generator will warm up during a test. This is portion of the test when the xATSTestingStatusTestStatus OID returns the value engineWarmingUp. Specified in seconds. | |||||||||||||||||||||
| SxATSTestingStatusProfileLoadedTime | 1.3.6.1.4.1.318.1.1.17.5.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The amount of time that ATS will apply the system load to the generator during a system load test. This is portion of the test when the xATSTestingStatusTestStatus OID returns the value testingWithLoad. Specified in minutes. | |||||||||||||||||||||
| SxATSTestingStatusProfileUnloadedTime | 1.3.6.1.4.1.318.1.1.17.5.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The amount of time that the generator will run following the warm up portion of a start test, or the loaded portion of a load test. This is portion of the test when the xATSTestingStatusTestStatus OID returns the value testingWithoutLoad. Specified in seconds. | |||||||||||||||||||||
| NxATSTestingResults | 1.3.6.1.4.1.318.1.1.17.5.2 | ||||||||||||||||||||
| SxATSTestingResultsLastDateOfTest | 1.3.6.1.4.1.318.1.1.17.5.2.1 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory Date of the last test that was performed, either scheduled or manual. Test results are available in the xATSTestingResultsLastResult OID. Specified in the dd/mm/yyyy format, or 'none' if not available. | |||||||||||||||||||||
| SxATSTestingResultsLastResult | 1.3.6.1.4.1.318.1.1.17.5.2.2 | INTEGER | RO | mandatory | startTestPassed(2) | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The result of the last ATS/generator system test.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxATSTestingResultsTestLastTestTime | 1.3.6.1.4.1.318.1.1.17.5.2.3 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory Time of day at which the last test was performed, either scheduled or manual. Test results are available in the xATSTestingResultsLastResult OID. Specified in the hh:mm:ss format, or 'none' if not available. | |||||||||||||||||||||
| SxATSTestingResultsLastCrankDuration | 1.3.6.1.4.1.318.1.1.17.5.2.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The time spent cranking the generator before it started during the last test. Specified in seconds, or -1 if not available. | |||||||||||||||||||||
| SxATSTestingResultsLastWarmupDuration | 1.3.6.1.4.1.318.1.1.17.5.2.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The time spent in the engineWarmingUp state during the last system test. Specified in seconds, or -1 if not available. | |||||||||||||||||||||
| SxATSTestingResultsLastLoadedDuration | 1.3.6.1.4.1.318.1.1.17.5.2.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The time spent in the testingWithLoad state during the last system test. Specified in seconds, or -1 if not available. | |||||||||||||||||||||
| SxATSTestingResultsLastUnloadedDuration | 1.3.6.1.4.1.318.1.1.17.5.2.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The time spent in the testingWithoutLoad state during the last system test. Specified in seconds, or -1 if not available. | |||||||||||||||||||||
| NxATSTestingSchedule | 1.3.6.1.4.1.318.1.1.17.5.3 | ||||||||||||||||||||
| SxATSTestingScheduleFrequency | 1.3.6.1.4.1.318.1.1.17.5.3.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The frequency of running scheduled tests.
| |||||||||||||||||||||
| SxATSTestingScheduleTestDay | 1.3.6.1.4.1.318.1.1.17.5.3.2 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory The desired day for the scheduled test. This object applies only
when the xATSTestingScheduleFrequency OID is set to weekly or monthly.
For weekly test frequency, the string is the day the test will be run.
For monthly test frequency, the string indicates the day,
and the instance within the month.
For example, for monthly frequency: 2nd Sunday, 3rd Monday, 4th Tuesday,
for weekly frequency: Sunday, Monday, Tuesday. | |||||||||||||||||||||
| SxATSTestingScheduleTestTime | 1.3.6.1.4.1.318.1.1.17.5.3.3 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory The time of day that the scheduled test will occur. Specified in the format hh:mm. | |||||||||||||||||||||
| SxATSTestingScheduleTestWithLoadInterval | 1.3.6.1.4.1.318.1.1.17.5.3.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory This setting specifies which system tests should include applying the load to the generator. The applyLoadMonthlyDetailed entry in the list will apply load once, for each month represented in the xATSTestingScheduleTestWithLoadSelectMonth OID.
| |||||||||||||||||||||
| SxATSTestingScheduleTestWithLoadSelectMonth | 1.3.6.1.4.1.318.1.1.17.5.3.5 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory The detailed selection for testing with load on a month-by-month basis. This object is applicable when the xATSTestingScheduleTestWithLoadInterval is set to applyLoadMonthlyDetailed. Otherwise this selection will be ignored. Format for this string is a comma-separated entry of months. For example: Jan,Mar,Dec. The string will return 'No Months Scheduled' if no months have been selected. | |||||||||||||||||||||
| SxATSTestingScheduleNextTestDate | 1.3.6.1.4.1.318.1.1.17.5.3.6 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The date of the next scheduled test, in the format dd-mmm-yyyy. | |||||||||||||||||||||
| NxATSTestingSimulatePowerFail | 1.3.6.1.4.1.318.1.1.17.5.4 | ||||||||||||||||||||
| SxATSTestingSimulatePowerFailTest | 1.3.6.1.4.1.318.1.1.17.5.4.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory This object executes a simulated power failure for the duration indicated. Simulation can be aborted by selecting cancelSimulation.
| |||||||||||||||||||||
| SxATSTestingSimulatePowerFailTimeRemaining | 1.3.6.1.4.1.318.1.1.17.5.4.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Indicates the time remaining in seconds, for a simulated power failure. a value of zero indicates that simulated power failure is not active. | |||||||||||||||||||||
| NxATSInputContacts | 1.3.6.1.4.1.318.1.1.17.6 | ||||||||||||||||||||
| SxATSInputContactNumContacts | 1.3.6.1.4.1.318.1.1.17.6.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of contacts supported by the ATS. | |||||||||||||||||||||
| SxATSInputContactTableSize | 1.3.6.1.4.1.318.1.1.17.6.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of input contact entries. | |||||||||||||||||||||
| TxATSInputContactTable | 1.3.6.1.4.1.318.1.1.17.6.3 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of contacts supported by the ATS. The number of entries is contained in the xATSInputContactTableSize OID. | |||||||||||||||||||||
| RxATSInputContactEntry | 1.3.6.1.4.1.318.1.1.17.6.3.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory A contact entry containing information for a given contact. | |||||||||||||||||||||
| CxATSInputContactNumber | 1.3.6.1.4.1.318.1.1.17.6.3.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory An index identifying the contact on the ATS. | |||||||||||||||||||||
| CxATSInputContactName | 1.3.6.1.4.1.318.1.1.17.6.3.1.2 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The description of the purpose/use of the contact. | |||||||||||||||||||||
| CxATSInputContactNormalState | 1.3.6.1.4.1.318.1.1.17.6.3.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The normal operating position of the contact.
| |||||||||||||||||||||
| CxATSInputContactCurrentState | 1.3.6.1.4.1.318.1.1.17.6.3.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This value indicates the current state of the contact.
| |||||||||||||||||||||
| NxATSOutputRelays | 1.3.6.1.4.1.318.1.1.17.7 | ||||||||||||||||||||
| SxATSOutputRelayNumRelays | 1.3.6.1.4.1.318.1.1.17.7.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of output relays supported by the ATS. | |||||||||||||||||||||
| SxATSOutputRelayTableSize | 1.3.6.1.4.1.318.1.1.17.7.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of output relay entries. | |||||||||||||||||||||
| TxATSOutputRelayTable | 1.3.6.1.4.1.318.1.1.17.7.3 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of output relays supported by the ATS. The number of entries is contained in the xATSOutputRelayTableSize OID. | |||||||||||||||||||||
| RxATSOutputRelayEntry | 1.3.6.1.4.1.318.1.1.17.7.3.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory A output relay entry containing information for a given contact. | |||||||||||||||||||||
| CxATSOutputRelayNumber | 1.3.6.1.4.1.318.1.1.17.7.3.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory An index identifying the output relay on the ATS. | |||||||||||||||||||||
| CxATSOutputRelayName | 1.3.6.1.4.1.318.1.1.17.7.3.1.2 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The description of the purpose/use of the output relay. | |||||||||||||||||||||
| CxATSOutputRelayNormalState | 1.3.6.1.4.1.318.1.1.17.7.3.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The normal operating position of the output relay.
| |||||||||||||||||||||
| CxATSOutputRelayCurrentState | 1.3.6.1.4.1.318.1.1.17.7.3.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This value indicates the current state of the output relay.
| |||||||||||||||||||||
| NxATSMisc | 1.3.6.1.4.1.318.1.1.17.8 | ||||||||||||||||||||
| Ngenerator | 1.3.6.1.4.1.318.1.1.18 | ||||||||||||||||||||
| NxATSGenerator | 1.3.6.1.4.1.318.1.1.18.1 | ||||||||||||||||||||
| NxATSGeneratorIdent | 1.3.6.1.4.1.318.1.1.18.1.1 | ||||||||||||||||||||
| SxATSGeneratorIdentModelNumber | 1.3.6.1.4.1.318.1.1.18.1.1.1 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the model number of the generator. This value is set at the factory. | |||||||||||||||||||||
| SxATSGeneratorIdentSerialNumber | 1.3.6.1.4.1.318.1.1.18.1.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the serial number of the generator. This value is set at the factory. | |||||||||||||||||||||
| SxATSGeneratorIdentDateofManufacture | 1.3.6.1.4.1.318.1.1.18.1.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying when the generator was manufactured in mm/dd/yyyy format. This value is set at the factory. | |||||||||||||||||||||
| SxATSGeneratorIdentVoltageConfiguration | 1.3.6.1.4.1.318.1.1.18.1.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The voltage for which the generator's alternator is designed. Specified in Volts line-to-line. | |||||||||||||||||||||
| SxATSGeneratorIdentMaxPowerRating | 1.3.6.1.4.1.318.1.1.18.1.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The max power rating of the generator. Specified in kW. | |||||||||||||||||||||
| SxATSGeneratorIdentAlternatorFrequency | 1.3.6.1.4.1.318.1.1.18.1.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The frequency for which the generator's alternator is designed. Specified in Hertz. | |||||||||||||||||||||
| NxATSGeneratorStatus | 1.3.6.1.4.1.318.1.1.18.1.2 | ||||||||||||||||||||
| SxATSGeneratorStatusGeneratorName | 1.3.6.1.4.1.318.1.1.18.1.2.1 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory The name or label for the generator connected to the source 2 of the ATS. | |||||||||||||||||||||
| SxATSGeneratorStatusOperational | 1.3.6.1.4.1.318.1.1.18.1.2.2 | INTEGER | RO | mandatory | ready(3) | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The operational status of the generator. unavailable when unrecognized status is received.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxATSGeneratorStatusModeSwitchPosition | 1.3.6.1.4.1.318.1.1.18.1.2.3 | INTEGER | RO | mandatory | automatic(3) | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The position of the generator's auto-mode switch. In automatic mode, the generator is started and stopped via the remote start contact, which has state indicated in the xATSGeneratorStatusRemoteStart OID. In manual mode generator start/stop control is via local command only. Off prevents the generator from running.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxATSGeneratorStatusRemoteStart | 1.3.6.1.4.1.318.1.1.18.1.2.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The status of the generator's remote start contact, which is provided as an output from the transfer switch to start/stop the generator when in automatic mode.
| |||||||||||||||||||||
| NxATSGeneratorAdvStatus | 1.3.6.1.4.1.318.1.1.18.1.3 | ||||||||||||||||||||
| SxATSGeneratorAdvStatusBatteryVoltage | 1.3.6.1.4.1.318.1.1.18.1.3.1 | INTEGER | RO | mandatory | 141 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The voltage of the generator's starting battery. Measured in tenths of VDC, or -1 if not available. Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxATSGeneratorAdvStatusOilPressure | 1.3.6.1.4.1.318.1.1.18.1.3.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The generator's engine oil pressure. Measured in tenths of Psi or kPa, based on the value of the xATSGeneratorSettingsMetricUnit OID, or -1 if not available. | |||||||||||||||||||||
| SxATSGeneratorAdvStatusCoolantTemperature | 1.3.6.1.4.1.318.1.1.18.1.3.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Current coolant temperature in the generator. Measured in degrees Celsius or Fahrenheit, based on the value of the xATSGeneratorSettingsMetricUnit OID, or -1 if not available. | |||||||||||||||||||||
| SxATSGeneratorAdvStatusEngineRPM | 1.3.6.1.4.1.318.1.1.18.1.3.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Current engine speed of the generator. Measured in RPM, or -1 if not available. | |||||||||||||||||||||
| SxATSGeneratorAdvStatusOilLevel | 1.3.6.1.4.1.318.1.1.18.1.3.5 | INTEGER | RO | mandatory | ok(1) | ||||||||||||||||
scalar · INTEGER · read-only · mandatory Indicates adequate oil level in the generator.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SxATSGeneratorAdvStatusCoolantLevel | 1.3.6.1.4.1.318.1.1.18.1.3.6 | INTEGER | RO | mandatory | ok(1) | ||||||||||||||||
scalar · INTEGER · read-only · mandatory Indicates adequate coolant level in the generator.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NxATSGeneratorOutput | 1.3.6.1.4.1.318.1.1.18.1.4 | ||||||||||||||||||||
| SxATSGeneratorOutputFrequency | 1.3.6.1.4.1.318.1.1.18.1.4.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The output frequency of the generator. Measured in tenths of Hertz, or -1 if not available. | |||||||||||||||||||||
| SxATSGeneratorOutputTotalPower | 1.3.6.1.4.1.318.1.1.18.1.4.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The total output power of the generator. Measured in tenths of tenths of kW, or -1 if not available. | |||||||||||||||||||||
| SxATSGeneratorOutputTotalApparentPower | 1.3.6.1.4.1.318.1.1.18.1.4.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The total output power of the generator. Measured in tenths of kVA, or -1 if not available. | |||||||||||||||||||||
| SxATSGeneratorOutputTotalPowerFactor | 1.3.6.1.4.1.318.1.1.18.1.4.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Indicates the total load power factor of the generator. A value of 100 representing a unity power factor (1.00), or -1 when if not available. | |||||||||||||||||||||
| SxATSGeneratorOutputTableSize | 1.3.6.1.4.1.318.1.1.18.1.4.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of generator output phase entries. | |||||||||||||||||||||
| TxATSGeneratorOutputPhaseTable | 1.3.6.1.4.1.318.1.1.18.1.4.6 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of generator output table entries. The number of entries is contained in the xATSGeneratorOutputTableSize OID. | |||||||||||||||||||||
| RxATSGeneratorOutputPhaseEntry | 1.3.6.1.4.1.318.1.1.18.1.4.6.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular generator output phase. | |||||||||||||||||||||
| CxATSGeneratorOutputPhaseIndex | 1.3.6.1.4.1.318.1.1.18.1.4.6.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Description of each generator output phase utilized in this device.
| |||||||||||||||||||||
| CxATSGeneratorOutputVoltageLtoL | 1.3.6.1.4.1.318.1.1.18.1.4.6.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Line-to-line generator output voltage. Measured in Volts, or -1 if not available. | |||||||||||||||||||||
| CxATSGeneratorOutputVoltageLtoN | 1.3.6.1.4.1.318.1.1.18.1.4.6.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Line-to-neutral generator output voltage. Measured in volts, or -1 if not available. | |||||||||||||||||||||
| CxATSGeneratorOutputPhaseCurrent | 1.3.6.1.4.1.318.1.1.18.1.4.6.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Generator load current per phase. Measured in Amps, or -1 if not available. | |||||||||||||||||||||
| CxATSGeneratorOutputPower | 1.3.6.1.4.1.318.1.1.18.1.4.6.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Generator output power per phase. Measured in tenths of kW, or -1 if not available. | |||||||||||||||||||||
| CxATSGeneratorOutputApparentPower | 1.3.6.1.4.1.318.1.1.18.1.4.6.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Generator output power per phase. Measured in tenths of kVA, or -1 if not available. | |||||||||||||||||||||
| CxATSGeneratorOutputPowerFactor | 1.3.6.1.4.1.318.1.1.18.1.4.6.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Indicates the load power factor of the generator output per phase. A value of 100 representing a unity power factor (1.00), or -1 if not available. | |||||||||||||||||||||
| NxATSGeneratorSettings | 1.3.6.1.4.1.318.1.1.18.1.5 | ||||||||||||||||||||
| SxATSGeneratorSettingsVoltageAdjust | 1.3.6.1.4.1.318.1.1.18.1.5.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The voltage adjust of the generator. Specified in volts line-to-line, or -1 if not available. | |||||||||||||||||||||
| SxATSGeneratorSettingsFrequencyAdjust | 1.3.6.1.4.1.318.1.1.18.1.5.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The frequency adjust of the generator. Specified in tenths of Hertz. | |||||||||||||||||||||
| SxATSGeneratorSettingsStartDelay | 1.3.6.1.4.1.318.1.1.18.1.5.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The delay, in seconds, after the remote run signal is activated before the generator's engine will be cranked to start, or -1 if not available. | |||||||||||||||||||||
| SxATSGeneratorSettingsStopDelay | 1.3.6.1.4.1.318.1.1.18.1.5.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The delay, in seconds, before the generator will stop after the remote run signal is deactivated, or -1 if not available. | |||||||||||||||||||||
| SxATSGeneratorSettingsCrankCycleEnable | 1.3.6.1.4.1.318.1.1.18.1.5.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory When Crank Cycle is enabled, the engine will be cranked up to the time specified by the xATSGeneratorSettingsCrankTime OID. If the generator's engine does not start, there will be a pause as specified by the xATSGeneratorSettingsCrankRestTime OID before the engine will be cranked again. This cycle is repeated as specified by the xATSGeneratorSettingsNumberCrank OID. When crank cycle is disabled, the generator's engine will be cranked continuously until it starts.
| |||||||||||||||||||||
| SxATSGeneratorSettingsCrankTime | 1.3.6.1.4.1.318.1.1.18.1.5.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The duration of engine cranking, in seconds, when starting the generator. Applicable when the xATSGeneratorSettingsCrankCycleEnable OID is enabled. -1 if not available. | |||||||||||||||||||||
| SxATSGeneratorSettingsCrankRestTime | 1.3.6.1.4.1.318.1.1.18.1.5.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The pause duration, in seconds, following an unsuccessful attempt to start the generator. Applicable when the xATSGeneratorSettingsCrankCycleEnable OID is enabled. -1 if not available. | |||||||||||||||||||||
| SxATSGeneratorSettingsNumberCrank | 1.3.6.1.4.1.318.1.1.18.1.5.8 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of failed crank attempts before giving up on starting the generator. Applicable when the xATSGeneratorSettingsCrankCycleEnable OID is enabled. -1 if not available. | |||||||||||||||||||||
| SxATSGeneratorSettingsMetricUnit | 1.3.6.1.4.1.318.1.1.18.1.5.9 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Specifies the use of metric units in generator related OIDs, as well as on all other interfaces including the generator's local interface.
| |||||||||||||||||||||
| NxATSGeneratorService | 1.3.6.1.4.1.318.1.1.18.1.6 | ||||||||||||||||||||
| SxATSGeneratorServiceTotalRunHoursLifetime | 1.3.6.1.4.1.318.1.1.18.1.6.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Total time that the generator engine has been run, over the life of the generator. Measured in hours. -1 if not available. | |||||||||||||||||||||
| SxATSGeneratorServiceEngineStartsLifetime | 1.3.6.1.4.1.318.1.1.18.1.6.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Number of engine starts over the life of the generator. -1 if not available. | |||||||||||||||||||||
| SxATSGeneratorServiceTotalkWhLifetime | 1.3.6.1.4.1.318.1.1.18.1.6.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Total kWh of operation over the life of the generator. -1 if not available. | |||||||||||||||||||||
| SxATSGeneratorServiceTotalRunHoursSinceMaintenance | 1.3.6.1.4.1.318.1.1.18.1.6.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Total time that the generator engine has been run, since last service maintenance. Measured in tenths of hours. -1 if not available. | |||||||||||||||||||||
| SxATSGeneratorServiceEngineStartsSinceMaintenance | 1.3.6.1.4.1.318.1.1.18.1.6.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Number of engine starts since last service maintenance. -1 if not available. | |||||||||||||||||||||
| SxATSGeneratorServiceTotalkWhMaintenance | 1.3.6.1.4.1.318.1.1.18.1.6.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Total kWh of operation since last service maintenance. -1 if not available. | |||||||||||||||||||||
| SxATSGeneratorServiceResetRecord | 1.3.6.1.4.1.318.1.1.18.1.6.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Resets the engine start counter, engine run-hours, and kWh values that have accumulated in the generator since last maintenance. Also, the last service date will be reset to the current system date, and any service alarms will be cleared.
| |||||||||||||||||||||
| SxATSGeneratorServiceRecordResetDate | 1.3.6.1.4.1.318.1.1.18.1.6.8 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory Date at which the generator's service record was reset, in dd-mmm-yyyy format. | |||||||||||||||||||||
| SxATSGeneratorServiceNextServiceDate | 1.3.6.1.4.1.318.1.1.18.1.6.9 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory Date at which the next generator service is due in dd-mmm-yyyy format. Based on the xATSGeneratorServiceCalendarIntervalThreshold OID or '' if the calendar-based threshold is set to off. | |||||||||||||||||||||
| SxATSGeneratorServiceRunHoursUntilServiceDate | 1.3.6.1.4.1.318.1.1.18.1.6.10 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Run hours until the next generator service is due, in hours. Based on the xATSGeneratorServiceRunHoursThreshold OID or -1 if the run hour-based threshold is set to off. | |||||||||||||||||||||
| SxATSGeneratorServiceRunHoursThreshold | 1.3.6.1.4.1.318.1.1.18.1.6.11 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Run hour-based service interval. When the run-hours since service surpasses this threshold, generator service is due.
| |||||||||||||||||||||
| SxATSGeneratorServiceCalendarIntervalThreshold | 1.3.6.1.4.1.318.1.1.18.1.6.12 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Calendar-based service interval. When the next service date, as indicated by the xATSGeneratorServiceNextServiceDate OID is in the past, generator is due for service.
| |||||||||||||||||||||
| NxATSGeneratorFuelSystem | 1.3.6.1.4.1.318.1.1.18.1.7 | ||||||||||||||||||||
| SxATSGeneratorFuelSystemType | 1.3.6.1.4.1.318.1.1.18.1.7.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The type of fuel used by the generator.
| |||||||||||||||||||||
| SxATSGeneratorFuelSystemTankSize | 1.3.6.1.4.1.318.1.1.18.1.7.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Size of the generator's fuel tank. Specified in gallons or liters, based on the value of the xATSGeneratorSettingsMetricUnit OID, or -1 if not available. | |||||||||||||||||||||
| SxATSGeneratorFuelSystemFuelLevel | 1.3.6.1.4.1.318.1.1.18.1.7.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Fuel remaining in the generator tank. Measured in percent of tank fill, or -1 if not available. | |||||||||||||||||||||
| SxATSGeneratorFuelSystemRuntimePower | 1.3.6.1.4.1.318.1.1.18.1.7.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The power value used in the runtime remaining calculation. Measured in tenths of kW, or -1 if not available. | |||||||||||||||||||||
| SxATSGeneratorFuelSystemEstimatedRunTime | 1.3.6.1.4.1.318.1.1.18.1.7.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory An estimate of available runtime for the generator, based on available fuel as specified in the xATSGeneratorFuelSystemFuelLevel OID and kW load as specified in the xATSGeneratorFuelSystemRuntimePower OID. Measured in tenths of hours, or -1 if not available. | |||||||||||||||||||||
| SxATSGeneratorFuelSystemLowRunTimeThreshold | 1.3.6.1.4.1.318.1.1.18.1.7.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Threshold below which a low runtime alarm will exist.
| |||||||||||||||||||||
| SxATSGeneratorFuelSystemVeryLowRunTimeThreshold | 1.3.6.1.4.1.318.1.1.18.1.7.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Threshold below which a very low runtime alarm will exist.
| |||||||||||||||||||||
| SxATSGeneratorFuelSystemLowFuelLevelThreshold | 1.3.6.1.4.1.318.1.1.18.1.7.8 | INTEGER (0..100) | RW | mandatory | |||||||||||||||||
scalar · INTEGER (0..100) · read-write · mandatory Threshold below which a low fuel alarm will exist, with a value of 0 indicating disabled. Specified as percent of tank fill. | |||||||||||||||||||||
| SxATSGeneratorFuelSystemVeryLowFuelLevelThreshold | 1.3.6.1.4.1.318.1.1.18.1.7.9 | INTEGER (0..100) | RW | mandatory | |||||||||||||||||
scalar · INTEGER (0..100) · read-write · mandatory Threshold below which a very low fuel alarm will exist, with a value of 0 indicating disabled. Specified as percent of tank fill. | |||||||||||||||||||||
| NconsolePortServer | 1.3.6.1.4.1.318.1.1.19 | ||||||||||||||||||||
| NcpsAP930x | 1.3.6.1.4.1.318.1.1.19.1 | ||||||||||||||||||||
| NcpsAP930xSys | 1.3.6.1.4.1.318.1.1.19.1.1 | ||||||||||||||||||||
| SapCPSpname | 1.3.6.1.4.1.318.1.1.19.1.1.1 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The product's name. | |||||||||||||||||||||
| SapCPSversion | 1.3.6.1.4.1.318.1.1.19.1.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The firmware's version. | |||||||||||||||||||||
| NapCPSPower | 1.3.6.1.4.1.318.1.1.19.1.1.3 | ||||||||||||||||||||
| SapCPSPwNum | 1.3.6.1.4.1.318.1.1.19.1.1.3.1 | Integer32 | RO | mandatory | |||||||||||||||||
scalar · Integer32 · read-only · mandatory The number of the power supplies. | |||||||||||||||||||||
| SapCPSPw1 | 1.3.6.1.4.1.318.1.1.19.1.1.3.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory State of the first power supply. 0 will indicate not installed, 1 will indicate power ON, 2 will indicate power OFF. | |||||||||||||||||||||
| SapCPSPw2 | 1.3.6.1.4.1.318.1.1.19.1.1.3.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory State of the second power supply. 0 will indicate not installed, 1 will indicate power ON, 2 will indicate power OFF. | |||||||||||||||||||||
| NapCPSPcmcia | 1.3.6.1.4.1.318.1.1.19.1.1.4 | ||||||||||||||||||||
| SapCPSNPcmcia | 1.3.6.1.4.1.318.1.1.19.1.1.4.1 | Integer32 | RO | mandatory | |||||||||||||||||
scalar · Integer32 · read-only · mandatory Number of PCMCIA cards available. | |||||||||||||||||||||
| TcpsCardIdentTable | 1.3.6.1.4.1.318.1.1.19.1.1.4.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A table of PCMCIA card identifications. | |||||||||||||||||||||
| RcpsCardIdentEntry | 1.3.6.1.4.1.318.1.1.19.1.1.4.2.1 | NA | mandatory | ||||||||||||||||||
| CcpsCardIdentIndex | 1.3.6.1.4.1.318.1.1.19.1.1.4.2.1.1 | Integer32 | RO | mandatory | |||||||||||||||||
column · Integer32 · read-only · mandatory Number to identify the socket Card. | |||||||||||||||||||||
| CcpsCardIdentProd | 1.3.6.1.4.1.318.1.1.19.1.1.4.2.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory Product identification string. | |||||||||||||||||||||
| CcpsCardIdentMan | 1.3.6.1.4.1.318.1.1.19.1.1.4.2.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory Manufacturer ID code. | |||||||||||||||||||||
| CcpsCardIdentFunc | 1.3.6.1.4.1.318.1.1.19.1.1.4.2.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory Function ID code. | |||||||||||||||||||||
| CcpsCardIdentPCI | 1.3.6.1.4.1.318.1.1.19.1.1.4.2.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory PCI ID | |||||||||||||||||||||
| TcpsCardConfTable | 1.3.6.1.4.1.318.1.1.19.1.1.4.3 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A table of socket configuration information. | |||||||||||||||||||||
| RcpsCardConfEntry | 1.3.6.1.4.1.318.1.1.19.1.1.4.3.1 | NA | mandatory | ||||||||||||||||||
| CcpsCardConfIndex | 1.3.6.1.4.1.318.1.1.19.1.1.4.3.1.1 | Integer32 | RO | mandatory | |||||||||||||||||
column · Integer32 · read-only · mandatory Number to identify the socket PCMCIA. | |||||||||||||||||||||
| CcpsCardConfPower | 1.3.6.1.4.1.318.1.1.19.1.1.4.3.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory Power Settings. | |||||||||||||||||||||
| CcpsCardConfType | 1.3.6.1.4.1.318.1.1.19.1.1.4.3.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory Interface Type. | |||||||||||||||||||||
| CcpsCardConfInter | 1.3.6.1.4.1.318.1.1.19.1.1.4.3.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory Interrupt number. | |||||||||||||||||||||
| CcpsCardConfFunc | 1.3.6.1.4.1.318.1.1.19.1.1.4.3.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory Function. | |||||||||||||||||||||
| CcpsCardConfCardv | 1.3.6.1.4.1.318.1.1.19.1.1.4.3.1.6 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory Card values. | |||||||||||||||||||||
| CcpsCardConfPort1 | 1.3.6.1.4.1.318.1.1.19.1.1.4.3.1.7 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory I/O Port 1. | |||||||||||||||||||||
| CcpsCardConfPort2 | 1.3.6.1.4.1.318.1.1.19.1.1.4.3.1.8 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory I/O Port 2. | |||||||||||||||||||||
| TcpsCardStatusTable | 1.3.6.1.4.1.318.1.1.19.1.1.4.4 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A table of current socket status information. | |||||||||||||||||||||
| RcpsCardStatusEntry | 1.3.6.1.4.1.318.1.1.19.1.1.4.4.1 | NA | mandatory | ||||||||||||||||||
| CcpsCardStatusIndex | 1.3.6.1.4.1.318.1.1.19.1.1.4.4.1.1 | Integer32 (0..2) | RO | mandatory | |||||||||||||||||
column · Integer32 (0..2) · read-only · mandatory Number to identify the socket PCMCIA. | |||||||||||||||||||||
| CcpsCardStatusCard | 1.3.6.1.4.1.318.1.1.19.1.1.4.4.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory Current Card State. | |||||||||||||||||||||
| CcpsCardStatusFunc | 1.3.6.1.4.1.318.1.1.19.1.1.4.4.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory Current Function. | |||||||||||||||||||||
| SapCPSFlashSize | 1.3.6.1.4.1.318.1.1.19.1.1.5 | Integer32 | RO | mandatory | |||||||||||||||||
scalar · Integer32 · read-only · mandatory Total amount of flash memory in Mbytes. | |||||||||||||||||||||
| SapCPSRAMSize | 1.3.6.1.4.1.318.1.1.19.1.1.6 | Integer32 | RO | mandatory | |||||||||||||||||
scalar · Integer32 · read-only · mandatory Total amount of RAM in Mbytes. | |||||||||||||||||||||
| SapCPSCPUfreq | 1.3.6.1.4.1.318.1.1.19.1.1.7 | Integer32 | RO | mandatory | |||||||||||||||||
scalar · Integer32 · read-only · mandatory CPU clock in MHz. | |||||||||||||||||||||
| SapCPSDevId | 1.3.6.1.4.1.318.1.1.19.1.1.8 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The product's identifier. | |||||||||||||||||||||
| NcpsAP930xConf | 1.3.6.1.4.1.318.1.1.19.1.2 | ||||||||||||||||||||
| ScpsHostName | 1.3.6.1.4.1.318.1.1.19.1.2.1 | DisplayString (SIZE (0..40)) | RW | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..40)) · read-write · mandatory The Host Name. | |||||||||||||||||||||
| ScpsConsoleBanner | 1.3.6.1.4.1.318.1.1.19.1.2.2 | DisplayString (SIZE (0..255)) | RW | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..255)) · read-write · mandatory The console banner. | |||||||||||||||||||||
| ScpsMotd | 1.3.6.1.4.1.318.1.1.19.1.2.3 | DisplayString (SIZE (0..255)) | RW | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..255)) · read-write · mandatory The motd message. | |||||||||||||||||||||
| NcpsEthItf | 1.3.6.1.4.1.318.1.1.19.1.2.4 | ||||||||||||||||||||
| ScpsEthDhcpc | 1.3.6.1.4.1.318.1.1.19.1.2.4.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory 0 will indicate DHCP inactive, 1 will indicate DHCP active, 2 will indicate DHCP active and the last parameter is saved. | |||||||||||||||||||||
| ScpsEthIPaddr | 1.3.6.1.4.1.318.1.1.19.1.2.4.2 | IpAddress | RW | mandatory | |||||||||||||||||
scalar · IpAddress · read-write · mandatory This is the IP address of the Ethernet Interface. | |||||||||||||||||||||
| ScpsEthIPmask | 1.3.6.1.4.1.318.1.1.19.1.2.4.3 | IpAddress | RW | mandatory | |||||||||||||||||
scalar · IpAddress · read-write · mandatory The mask for the Ethernet network. | |||||||||||||||||||||
| ScpsEthMTU | 1.3.6.1.4.1.318.1.1.19.1.2.4.4 | Integer32 | RW | mandatory | |||||||||||||||||
scalar · Integer32 · read-write · mandatory The Maximum Transmission Unit size, which determines whether packets should be broken up. | |||||||||||||||||||||
| ScpsEthIPaddr2 | 1.3.6.1.4.1.318.1.1.19.1.2.4.5 | IpAddress | RW | mandatory | |||||||||||||||||
scalar · IpAddress · read-write · mandatory The Ethernet secondary IP address. | |||||||||||||||||||||
| ScpsEthIPmask2 | 1.3.6.1.4.1.318.1.1.19.1.2.4.6 | IpAddress | RW | mandatory | |||||||||||||||||
scalar · IpAddress · read-write · mandatory The Ethernet secondary IP mask. | |||||||||||||||||||||
| NcpsNameService | 1.3.6.1.4.1.318.1.1.19.1.2.5 | ||||||||||||||||||||
| ScpsResolverOrder | 1.3.6.1.4.1.318.1.1.19.1.2.5.1 | DisplayString (SIZE (0..15)) | RW | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..15)) · read-write · mandatory Specifies how host lookups are to be performed. Valid values : empty, 'hosts', 'bind', 'hosts, bind', 'bind, hosts' | |||||||||||||||||||||
| ScpsMultipleIP | 1.3.6.1.4.1.318.1.1.19.1.2.5.2 | DisplayString (SIZE (0..3)) | RW | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..3)) · read-write · mandatory Valid values are ON or OFF. If set to ON, the resolve library will return all valid addresses for a host that appears in the /etc/hosts file, instead of only the first. | |||||||||||||||||||||
| NcpsDNSserv | 1.3.6.1.4.1.318.1.1.19.1.2.5.3 | ||||||||||||||||||||
| ScpsDNSpriserv | 1.3.6.1.4.1.318.1.1.19.1.2.5.3.1 | IpAddress | RW | mandatory | |||||||||||||||||
scalar · IpAddress · read-write · mandatory Internet Address (in dot notation) of primary name server that the resolver should query. | |||||||||||||||||||||
| ScpsDNSsecserv | 1.3.6.1.4.1.318.1.1.19.1.2.5.3.2 | IpAddress | RW | mandatory | |||||||||||||||||
scalar · IpAddress · read-write · mandatory Internet Address (in dot notation) of secondary name server that the resolver should query. | |||||||||||||||||||||
| ScpsDNSdomain | 1.3.6.1.4.1.318.1.1.19.1.2.5.3.3 | DisplayString (SIZE (0..40)) | RW | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..40)) · read-write · mandatory Local domain name. | |||||||||||||||||||||
| NcpsSerialPortConf | 1.3.6.1.4.1.318.1.1.19.1.2.6 | ||||||||||||||||||||
| NcpsSerialGlobal | 1.3.6.1.4.1.318.1.1.19.1.2.6.1 | ||||||||||||||||||||
| ScpsSerialInclude | 1.3.6.1.4.1.318.1.1.19.1.2.6.1.1 | DisplayString (SIZE (0..40)) | RW | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..40)) · read-write · mandatory File used in centralized management. | |||||||||||||||||||||
| ScpsSerialNFS | 1.3.6.1.4.1.318.1.1.19.1.2.6.1.2 | DisplayString (SIZE (0..50)) | RW | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..50)) · read-write · mandatory Remote Network File System where data buffering will be written instead of the default directory '/var/run/DB'. | |||||||||||||||||||||
| ScpsSerialLockDir | 1.3.6.1.4.1.318.1.1.19.1.2.6.1.3 | DisplayString (SIZE (0..50)) | RW | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..50)) · read-write · mandatory The lock directory. | |||||||||||||||||||||
| ScpsSerialRlogin | 1.3.6.1.4.1.318.1.1.19.1.2.6.1.4 | DisplayString (SIZE (0..50)) | RW | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..50)) · read-write · mandatory Location of the rlogin binary that accepts the -i flag. | |||||||||||||||||||||
| ScpsSerialPppd | 1.3.6.1.4.1.318.1.1.19.1.2.6.1.5 | DisplayString (SIZE (0..50)) | RW | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..50)) · read-write · mandatory Location of the pppd binary. | |||||||||||||||||||||
| ScpsSerialTelnet | 1.3.6.1.4.1.318.1.1.19.1.2.6.1.6 | DisplayString (SIZE (0..50)) | RW | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..50)) · read-write · mandatory Location of the telnet application. | |||||||||||||||||||||
| ScpsSerialSsh | 1.3.6.1.4.1.318.1.1.19.1.2.6.1.7 | DisplayString (SIZE (0..50)) | RW | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..50)) · read-write · mandatory Location of the ssh application. | |||||||||||||||||||||
| ScpsSerialLocalLogins | 1.3.6.1.4.1.318.1.1.19.1.2.6.1.8 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory This parameter is only necessary when authentication is being performed for a port. This is useful if the Radius authentication server is down. 0 indicates OFF, 1 indicates ON. | |||||||||||||||||||||
| ScpsSerialFacility | 1.3.6.1.4.1.318.1.1.19.1.2.6.1.9 | Integer32 | RW | mandatory | |||||||||||||||||
scalar · Integer32 · read-write · mandatory This value (0-7) is the Local facility sent to the syslog daemon. | |||||||||||||||||||||
| ScpsSerialDBFacility | 1.3.6.1.4.1.318.1.1.19.1.2.6.1.10 | Integer32 | RW | mandatory | |||||||||||||||||
scalar · Integer32 · read-write · mandatory This value (0-7) is the Local facility sent to the syslog daemon. | |||||||||||||||||||||
| TcpsSerialGroupTable | 1.3.6.1.4.1.318.1.1.19.1.2.6.1.11 | NA | mandatory | ||||||||||||||||||
| RcpsSerialGroupEntry | 1.3.6.1.4.1.318.1.1.19.1.2.6.1.11.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory
| |||||||||||||||||||||
| CcpsSerialGroupIndex | 1.3.6.1.4.1.318.1.1.19.1.2.6.1.11.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Number to identify the group. | |||||||||||||||||||||
| CcpsSerialGroupName | 1.3.6.1.4.1.318.1.1.19.1.2.6.1.11.1.2 | DisplayString (SIZE (0..20)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..20)) · read-write · mandatory The group name. | |||||||||||||||||||||
| CcpsSerialGroupUsers | 1.3.6.1.4.1.318.1.1.19.1.2.6.1.11.1.3 | DisplayString (SIZE (0..80)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..80)) · read-write · mandatory The user's names. | |||||||||||||||||||||
| NcpsSerialSpec | 1.3.6.1.4.1.318.1.1.19.1.2.6.2 | ||||||||||||||||||||
| TcpsSerialPortTable | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory This is the specific configuration per serial port. | |||||||||||||||||||||
| RcpsSerialPortEntry | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1 | NA | mandatory | ||||||||||||||||||
| CcpsSerialPortNumber | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Number to identify the serial port. Value 0 is ALL. | |||||||||||||||||||||
| CcpsSerialPortTty | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.2 | DisplayString (SIZE (0..25)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..25)) · read-write · mandatory The device name for the serial port. | |||||||||||||||||||||
| CcpsSerialPortName | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.3 | DisplayString (SIZE (0..40)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..40)) · read-write · mandatory Alias name given to the server connected to the serial port. | |||||||||||||||||||||
| CcpsSerialPortSpeed | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.4 | Integer32 | RW | mandatory | |||||||||||||||||
column · Integer32 · read-write · mandatory The speed of the serial port. Supported values are: 50, 75, 110, 134, 150, 200, 300, 600, 1200, 1800, 2400, 4800, 9600, 14400, 19200, 28800, 38400, 57600, 115200, 230400, and 460800 | |||||||||||||||||||||
| CcpsSerialPortDataSize | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.5 | Integer32 (4..8) | RW | mandatory | |||||||||||||||||
column · Integer32 (4..8) · read-write · mandatory The data size for the serial port. | |||||||||||||||||||||
| CcpsSerialPortStopBits | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.6 | Integer32 (0..2) | RW | mandatory | |||||||||||||||||
column · Integer32 (0..2) · read-write · mandatory The number of stop bits for the serial port. | |||||||||||||||||||||
| CcpsSerialPortParity | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.7 | DisplayString (SIZE (0..5)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..5)) · read-write · mandatory The parity for the serial port. | |||||||||||||||||||||
| CcpsSerialPortFlowCtrl | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.8 | DisplayString (SIZE (0..5)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..5)) · read-write · mandatory The flow control for the serial port. | |||||||||||||||||||||
| CcpsSerialPortDTRdelay | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.9 | Integer32 | RW | mandatory | |||||||||||||||||
column · Integer32 · read-write · mandatory This specifies how long (in milliseconds) a DTR signal will be turned off before it is turned on again. | |||||||||||||||||||||
| CcpsSerialPortDCDCtrl | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.10 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory DCD signal controls the connection request. 0 will indicate nocontrol, 1 will indicate control. | |||||||||||||||||||||
| CcpsSerialPortLogUtmp | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.11 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Update the login records in /var/run/utmp file. 0 will indicate inactive, 1 will indicate active. | |||||||||||||||||||||
| CcpsSerialPortLogWtmp | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.12 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Update the login records in /var/run/wtmp file. 0 will indicate inactive, 1 will indicate active. | |||||||||||||||||||||
| CcpsSerialPortLogform | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.13 | DisplayString (SIZE (0..40)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..40)) · read-write · mandatory This is the format to write the login record. | |||||||||||||||||||||
| CcpsSerialPortAuthtype | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.14 | DisplayString (SIZE (0..25)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..25)) · read-write · mandatory Authentication type. | |||||||||||||||||||||
| CcpsSerialPortAuthSrv1 | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.15 | IpAddress | RW | mandatory | |||||||||||||||||
column · IpAddress · read-write · mandatory IP address of the primary authentication server. | |||||||||||||||||||||
| CcpsSerialPortAccSrv1 | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.16 | IpAddress | RW | mandatory | |||||||||||||||||
column · IpAddress · read-write · mandatory IP address of the primary accounting server. | |||||||||||||||||||||
| CcpsSerialPortAuthTmo | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.17 | Integer32 | RW | mandatory | |||||||||||||||||
column · Integer32 · read-write · mandatory This is the timeout (in seconds) for the authentication query to be answered. | |||||||||||||||||||||
| CcpsSerialPortAuthRetr | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.18 | Integer32 | RW | mandatory | |||||||||||||||||
column · Integer32 · read-write · mandatory This defines the number of times each server is tried before another is contacted. | |||||||||||||||||||||
| CcpsSerialPortAuthSrv2 | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.19 | IpAddress | RW | mandatory | |||||||||||||||||
column · IpAddress · read-write · mandatory IP address of the secondary authentication server. | |||||||||||||||||||||
| CcpsSerialPortAccSrv2 | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.20 | IpAddress | RW | mandatory | |||||||||||||||||
column · IpAddress · read-write · mandatory IP address of the secondary accounting server. | |||||||||||||||||||||
| CcpsSerialPortAuthSecret | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.21 | DisplayString (SIZE (0..40)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..40)) · read-write · mandatory This is the shared secret with authentication servers. | |||||||||||||||||||||
| CcpsSerialPortAuthRadP | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.22 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Radius state. 0 will indicate inactive, 1 will indicate active. | |||||||||||||||||||||
| CcpsSerialPortAuthAcc | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.23 | DisplayString (SIZE (0..40)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..40)) · read-write · mandatory Access restriction. | |||||||||||||||||||||
| CcpsSerialPortProtocol | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.24 | DisplayString (SIZE (0..40)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..40)) · read-write · mandatory Defines the serial port's protocol. | |||||||||||||||||||||
| CcpsSerialPortRemoteIP | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.25 | DisplayString (SIZE (0..20)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..20)) · read-write · mandatory This is the default IP address of the serial port. | |||||||||||||||||||||
| CcpsSerialPortSocketPort | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.26 | DisplayString (SIZE (0..10)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..10)) · read-write · mandatory This defines an alternative labeling system for the serial port. | |||||||||||||||||||||
| CcpsSerialPortRemHost | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.27 | IpAddress | RW | mandatory | |||||||||||||||||
column · IpAddress · read-write · mandatory The IP address of the host to which the serial port will connect. | |||||||||||||||||||||
| CcpsSerialPortBanner | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.28 | DisplayString (SIZE (0..250)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..250)) · read-write · mandatory This defines the banner. | |||||||||||||||||||||
| CcpsSerialPortPrompt | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.29 | DisplayString (SIZE (0..250)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..250)) · read-write · mandatory This defines the login prompt to the serial port. | |||||||||||||||||||||
| CcpsSerialPortTermType | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.30 | DisplayString (SIZE (0..20)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..20)) · read-write · mandatory This defines the terminal type. | |||||||||||||||||||||
| CcpsSerialPortAutomUsr | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.31 | DisplayString (SIZE (0..40)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..40)) · read-write · mandatory This defines the automatic user. | |||||||||||||||||||||
| CcpsSerialPortNetMask | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.32 | IpAddress | RW | mandatory | |||||||||||||||||
column · IpAddress · read-write · mandatory The network mask used in dial in connection. | |||||||||||||||||||||
| CcpsSerialPortPppMtu | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.33 | Integer32 | RW | mandatory | |||||||||||||||||
column · Integer32 · read-write · mandatory The PPP MTU - dial in connection. | |||||||||||||||||||||
| CcpsSerialPortPppMru | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.34 | Integer32 | RW | mandatory | |||||||||||||||||
column · Integer32 · read-write · mandatory The PPP MRU - dial in connection. | |||||||||||||||||||||
| CcpsSerialPortPppOptions | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.35 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The PPP options when the PPP session is autodetected. | |||||||||||||||||||||
| CcpsSerialPortPppFoption | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.36 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The PPP forced options when the user has already been authenticated. | |||||||||||||||||||||
| CcpsSerialPortModemChat | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.37 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The initchat send to modem connected. | |||||||||||||||||||||
| CcpsSerialPortSttyCmd | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.38 | DisplayString (SIZE (0..180)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..180)) · read-write · mandatory The tty settings after socket connection is established. | |||||||||||||||||||||
| CcpsSerialPortSockTx | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.39 | Integer32 | RW | mandatory | |||||||||||||||||
column · Integer32 · read-write · mandatory Defines the delay (in milliseconds) before transmission to the Ethernet of data received through a serial port. | |||||||||||||||||||||
| CcpsSerialPortSockPoll | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.40 | Integer32 | RW | mandatory | |||||||||||||||||
column · Integer32 · read-write · mandatory Keep-alive timer (milliseconds) for the TCP connection. | |||||||||||||||||||||
| CcpsSerialPortSockIdle | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.41 | Integer32 | RW | mandatory | |||||||||||||||||
column · Integer32 · read-write · mandatory The idle timeout in seconds. | |||||||||||||||||||||
| CcpsSerialPortDBsize | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.42 | Integer32 | RW | mandatory | |||||||||||||||||
column · Integer32 · read-write · mandatory Maximum size of the data buffering file. | |||||||||||||||||||||
| CcpsSerialPortDBtime | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.43 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Timestamp in data buffering. 0 will indicate inactive, 1 will indicate active. | |||||||||||||||||||||
| CcpsSerialPortDBmode | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.44 | DisplayString (SIZE (0..5)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..5)) · read-write · mandatory Data buffering mode : circ or line. | |||||||||||||||||||||
| CcpsSerialPortDBsyslog | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.45 | Integer32 | RW | mandatory | |||||||||||||||||
column · Integer32 · read-write · mandatory Size of the data buffer sent to syslog. | |||||||||||||||||||||
| CcpsSerialPortDBmenu | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.46 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Menu type for data buffering. 0 will indicate display Menu, 1 will indicate inactive, 2 will indicate DB, 3 will indicate Parc. | |||||||||||||||||||||
| CcpsSerialPortDBalarm | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.47 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Alarm generation status. 0 will indicate inactive, 1 will indicate active. | |||||||||||||||||||||
| CcpsSerialPortSSHbreak | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.48 | DisplayString (SIZE (0..16)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..16)) · read-write · mandatory Break sequence - ssh session. | |||||||||||||||||||||
| CcpsSerialPortSniffSess | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.49 | DisplayString (SIZE (0..5)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..5)) · read-write · mandatory Sniff session type. | |||||||||||||||||||||
| CcpsSerialPortSniffAdm | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.50 | DisplayString (SIZE (0..40)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..40)) · read-write · mandatory List of admin users allowed to sniff session. | |||||||||||||||||||||
| CcpsSerialPortSniffEsc | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.51 | DisplayString (SIZE (0..6)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..6)) · read-write · mandatory Escape sequence used in sniff session. | |||||||||||||||||||||
| CcpsSerialPortSniffMsess | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.52 | DisplayString (SIZE (0..20)) | RW | mandatory | |||||||||||||||||
| CcpsSerialPortTelnetMode | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.53 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Mode negotiated by client telnet with the server. 0 will indicate text, 1 will indicate binary. | |||||||||||||||||||||
| CcpsSerialPortSysBufSess | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.54 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Syslog Buffering at all times. 0 will indicate yes, 1 will indicate no. | |||||||||||||||||||||
| CcpsSerialPortLFSuppress | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.55 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory LF suppression in socket_server session. 0 will indicate inactive, 1 will indicate active. | |||||||||||||||||||||
| CcpsSerialPortAutoInput | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.56 | DisplayString (SIZE (0..40)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..40)) · read-write · mandatory Input string used for auto answer. | |||||||||||||||||||||
| CcpsSerialPortAutoOutput | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.57 | DisplayString (SIZE (0..40)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..40)) · read-write · mandatory Output string used for auto answer. | |||||||||||||||||||||
| CcpsSerialPortBreakInterval | 1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.58 | Integer32 | RW | mandatory | |||||||||||||||||
column · Integer32 · read-write · mandatory The break interval in milliseconds. | |||||||||||||||||||||
| NcpsAP930xInfo | 1.3.6.1.4.1.318.1.1.19.1.3 | ||||||||||||||||||||
| TcpsInfoSerialPortTable | 1.3.6.1.4.1.318.1.1.19.1.3.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory This is the information of the specific serial port. | |||||||||||||||||||||
| RcpsInfoSerialPortEntry | 1.3.6.1.4.1.318.1.1.19.1.3.1.1 | NA | mandatory | ||||||||||||||||||
| CcpsInfoSerialPortNumber | 1.3.6.1.4.1.318.1.1.19.1.3.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Number to identify the serial port. | |||||||||||||||||||||
| CcpsInfoSerialPortTty | 1.3.6.1.4.1.318.1.1.19.1.3.1.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The device name for the serial port. | |||||||||||||||||||||
| CcpsInfoSerialPortName | 1.3.6.1.4.1.318.1.1.19.1.3.1.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory Alias name given to the server connected to the serial port. | |||||||||||||||||||||
| CcpsInfoSerialPortSpeed | 1.3.6.1.4.1.318.1.1.19.1.3.1.1.4 | Integer32 | RO | mandatory | |||||||||||||||||
column · Integer32 · read-only · mandatory The speed for serial port. | |||||||||||||||||||||
| CcpsInfoSerialPortTxBytes | 1.3.6.1.4.1.318.1.1.19.1.3.1.1.5 | Integer32 | RO | mandatory | |||||||||||||||||
column · Integer32 · read-only · mandatory The number of transmitted bytes by the serial port. | |||||||||||||||||||||
| CcpsInfoSerialPortRXBytes | 1.3.6.1.4.1.318.1.1.19.1.3.1.1.6 | Integer32 | RO | mandatory | |||||||||||||||||
column · Integer32 · read-only · mandatory The number of received bytes by the serial port. | |||||||||||||||||||||
| CcpsInfoSerialPortErrFrame | 1.3.6.1.4.1.318.1.1.19.1.3.1.1.7 | Integer32 | RO | mandatory | |||||||||||||||||
column · Integer32 · read-only · mandatory The number of frame errors. | |||||||||||||||||||||
| CcpsInfoSerialPortErrParity | 1.3.6.1.4.1.318.1.1.19.1.3.1.1.8 | Integer32 | RO | mandatory | |||||||||||||||||
column · Integer32 · read-only · mandatory The number of parity errors. | |||||||||||||||||||||
| CcpsInfoSerialPortErrBreaks | 1.3.6.1.4.1.318.1.1.19.1.3.1.1.9 | Integer32 | RO | mandatory | |||||||||||||||||
column · Integer32 · read-only · mandatory The number of breaks errors. | |||||||||||||||||||||
| CcpsInfoSerialPortErrOverrun | 1.3.6.1.4.1.318.1.1.19.1.3.1.1.10 | Integer32 | RO | mandatory | |||||||||||||||||
column · Integer32 · read-only · mandatory The number of overrun errors. | |||||||||||||||||||||
| CcpsInfoSerialPortSigDTR | 1.3.6.1.4.1.318.1.1.19.1.3.1.1.11 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The state of the DTR signal. 0 will indicate down, 1 will indicate up. | |||||||||||||||||||||
| CcpsInfoSerialPortSigCD | 1.3.6.1.4.1.318.1.1.19.1.3.1.1.12 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The state of the DCD signal. 0 will indicate down, 1 will indicate up. | |||||||||||||||||||||
| CcpsInfoSerialPortSigDSR | 1.3.6.1.4.1.318.1.1.19.1.3.1.1.13 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The state of the DSR signal. 0 will indicate down, 1 will indicate up. | |||||||||||||||||||||
| CcpsInfoSerialPortSigRTS | 1.3.6.1.4.1.318.1.1.19.1.3.1.1.14 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The state of the RTS signal. 0 will indicate down, 1 will indicate up. | |||||||||||||||||||||
| CcpsInfoSerialPortSigCTS | 1.3.6.1.4.1.318.1.1.19.1.3.1.1.15 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The state of the CTS signal. 0 will indicate down, 1 will indicate up. | |||||||||||||||||||||
| CcpsInfoSerialPortSigRI | 1.3.6.1.4.1.318.1.1.19.1.3.1.1.16 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The state of the RI signal. 0 will indicate down, 1 will indicate up. | |||||||||||||||||||||
| NcpsAP930xAdm | 1.3.6.1.4.1.318.1.1.19.1.4 | ||||||||||||||||||||
| SapCPSSave | 1.3.6.1.4.1.318.1.1.19.1.4.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Exec saveconf command. 0 will indicate don't save, 1 will indicate save. | |||||||||||||||||||||
| SapCPSSerialHUP | 1.3.6.1.4.1.318.1.1.19.1.4.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Exec signal_ras hup command. 0 will indicate no restart, 1 will indicate restart. | |||||||||||||||||||||
| NaccessControl | 1.3.6.1.4.1.318.1.1.20 | ||||||||||||||||||||
| NaccessPX | 1.3.6.1.4.1.318.1.1.20.1 | ||||||||||||||||||||
| NaccessPXIdent | 1.3.6.1.4.1.318.1.1.20.1.1 | ||||||||||||||||||||
| SaccessPXIdentAlarmStatus | 1.3.6.1.4.1.318.1.1.20.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Access PX alarm status 1 = Normal 2 = Warning 3 = Critical. | |||||||||||||||||||||
| SaccessPXIdentProductNumber | 1.3.6.1.4.1.318.1.1.20.1.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The product number of the Access PX. | |||||||||||||||||||||
| SaccessPXIdentHardwareRev | 1.3.6.1.4.1.318.1.1.20.1.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The hardware revision number of the Access PX. | |||||||||||||||||||||
| SaccessPXIdentDateOfManufacture | 1.3.6.1.4.1.318.1.1.20.1.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The date of manufacture of the Access PX. | |||||||||||||||||||||
| SaccessPXIdentSerialNumber | 1.3.6.1.4.1.318.1.1.20.1.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The serial number of the Access PX. | |||||||||||||||||||||
| NaccessPXConfig | 1.3.6.1.4.1.318.1.1.20.1.2 | ||||||||||||||||||||
| SaccessPXConfigCardReaderEnableDisableAction | 1.3.6.1.4.1.318.1.1.20.1.2.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Action to disable/enable the card reader.
| |||||||||||||||||||||
| SaccessPXConfigAutoRelockTime | 1.3.6.1.4.1.318.1.1.20.1.2.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Time (10 - 60) in seconds when the door will automatically relock after it has been unlocked and the handle has not been opened. | |||||||||||||||||||||
| SaccessPXConfigCardFormat | 1.3.6.1.4.1.318.1.1.20.1.2.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Indicates and controls the various card format.
| |||||||||||||||||||||
| NaccessPXConfigFront | 1.3.6.1.4.1.318.1.1.20.1.3 | ||||||||||||||||||||
| SaccessPXConfigFrontDoorLockControl | 1.3.6.1.4.1.318.1.1.20.1.3.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Control action (unlock, lock) for the front door. Setting this OID will unlock or lock the front door. Getting this OID will respond with the current state of the front door lock which could be 1 = unlocked, 2 = locked, 3 = not installed, 4 = disconnected.
| |||||||||||||||||||||
| SaccessPXConfigFrontDoorMaxOpenTime | 1.3.6.1.4.1.318.1.1.20.1.3.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Time in minutes, (1 - 120), that the front door can be allowed to remain open without generating an alarm condition. | |||||||||||||||||||||
| NaccessPXStatusFront | 1.3.6.1.4.1.318.1.1.20.1.4 | ||||||||||||||||||||
| SaccessPXStatusFrontDoorLock | 1.3.6.1.4.1.318.1.1.20.1.4.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Present state of the front door lock: unlocked, locked, not installed, or disconnected.
| |||||||||||||||||||||
| SaccessPXStatusFrontDoor | 1.3.6.1.4.1.318.1.1.20.1.4.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Present state of the front door: open, closed, not installed, or disconnected.
| |||||||||||||||||||||
| SaccessPXStatusFrontDoorHandle | 1.3.6.1.4.1.318.1.1.20.1.4.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Present state of the front door handle: open, closed, not installed, or disconnected.
| |||||||||||||||||||||
| SaccessPXStatusFrontDoorMaxOpenTime | 1.3.6.1.4.1.318.1.1.20.1.4.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Time in minutes, (1 - 120), that the front door can be allowed to remain open without generating an alarm condition. | |||||||||||||||||||||
| SaccessPXStatusFrontDoorAlarmStatus | 1.3.6.1.4.1.318.1.1.20.1.4.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Front door alarm status 1 = Normal 2 = Warning 3 = Critical 4 = Front door not installed. | |||||||||||||||||||||
| NaccessPXConfigRear | 1.3.6.1.4.1.318.1.1.20.1.5 | ||||||||||||||||||||
| SaccessPXConfigRearDoorLockControl | 1.3.6.1.4.1.318.1.1.20.1.5.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Control action (unlock, lock) for the rear door. Setting this OID will unlock or lock the rear door. Getting this OID will respond with the current state of the rear door lock which could be 1 = unlocked, 2 = locked, 3 = not installed, 4 = disconnected.
| |||||||||||||||||||||
| SaccessPXConfigRearDoorMaxOpenTime | 1.3.6.1.4.1.318.1.1.20.1.5.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Time in minutes, (1 - 120), that the rear door can be allowed to remain open without generating an alarm condition. | |||||||||||||||||||||
| NaccessPXStatusRear | 1.3.6.1.4.1.318.1.1.20.1.6 | ||||||||||||||||||||
| SaccessPXStatusRearDoorLock | 1.3.6.1.4.1.318.1.1.20.1.6.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Present state of the rear door lock: unlocked, locked, not installed, or disconnected.
| |||||||||||||||||||||
| SaccessPXStatusRearDoor | 1.3.6.1.4.1.318.1.1.20.1.6.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Present state of the rear door: open, closed, not installed, or disconnected.
| |||||||||||||||||||||
| SaccessPXStatusRearDoorHandle | 1.3.6.1.4.1.318.1.1.20.1.6.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Present state of the rear door handle: open, closed, not installed, or disconnected.
| |||||||||||||||||||||
| SaccessPXStatusRearDoorMaxOpenTime | 1.3.6.1.4.1.318.1.1.20.1.6.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Time in minutes, (1 - 120), that the rear door can be allowed to remain open without generating an alarm condition. | |||||||||||||||||||||
| SaccessPXStatusRearDoorAlarmStatus | 1.3.6.1.4.1.318.1.1.20.1.6.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Rear door alarm status 1 = Normal 2 = Warning 3 = Critical 4 = Rear door not installed. | |||||||||||||||||||||
| NaccessPXConfigBeacon | 1.3.6.1.4.1.318.1.1.20.1.7 | ||||||||||||||||||||
| SaccessPXConfigBeaconName | 1.3.6.1.4.1.318.1.1.20.1.7.1 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory A descriptive name for the Beacon. | |||||||||||||||||||||
| SaccessPXConfigBeaconLocation | 1.3.6.1.4.1.318.1.1.20.1.7.2 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory A descriptive name for the location of the Beacon. | |||||||||||||||||||||
| SaccessPXConfigBeaconAction | 1.3.6.1.4.1.318.1.1.20.1.7.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Control action (turnOff, turnOn) for the beacon. Setting this OID will turn the beacon off or on. Getting this OID will respond with the current state which could be 1 = off, 2 = on, 3 = not installed, 4 = disconnected.
| |||||||||||||||||||||
| NaccessPXStatusBeacon | 1.3.6.1.4.1.318.1.1.20.1.8 | ||||||||||||||||||||
| SaccessPXStatusBeaconName | 1.3.6.1.4.1.318.1.1.20.1.8.1 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The name of the beacon. | |||||||||||||||||||||
| SaccessPXStatusBeaconLocation | 1.3.6.1.4.1.318.1.1.20.1.8.2 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The name of the location of the beacon. | |||||||||||||||||||||
| SaccessPXStatusBeaconCurrentState | 1.3.6.1.4.1.318.1.1.20.1.8.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The current state of the beacon: off, on, not installed, or disconnected.
| |||||||||||||||||||||
| NapcLocalDisplay | 1.3.6.1.4.1.318.1.1.21 | ||||||||||||||||||||
| NapcLocalDisplayIdent | 1.3.6.1.4.1.318.1.1.21.1 | ||||||||||||||||||||
| SapcLocalDisplayIdentDisplayType | 1.3.6.1.4.1.318.1.1.21.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Numeric value used to identify the type of display in use.
| |||||||||||||||||||||
| SapcLocalDisplayIdentModelNumber | 1.3.6.1.4.1.318.1.1.21.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The model number of the local display. | |||||||||||||||||||||
| SapcLocalDisplayIdentFirmwareRev | 1.3.6.1.4.1.318.1.1.21.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The firmware revision number of the local display. | |||||||||||||||||||||
| SapcLocalDisplayIdentOptions | 1.3.6.1.4.1.318.1.1.21.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A display-specific string identifying options in the local display. | |||||||||||||||||||||
| SapcLocalDisplayIdentDateOfManufacture | 1.3.6.1.4.1.318.1.1.21.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The date of manufacture of the local display, if available. | |||||||||||||||||||||
| SapcLocalDisplayIdentSerialNumber | 1.3.6.1.4.1.318.1.1.21.1.6 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The serial number of the local display, if available. | |||||||||||||||||||||
| NapcLocalDisplayConfig | 1.3.6.1.4.1.318.1.1.21.2 | ||||||||||||||||||||
| SapcLocalDisplayConfigAlarmBeeper | 1.3.6.1.4.1.318.1.1.21.2.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The alarm beeper setting for the local display. When enabled, the alarm beeper will begin to sound whenever there a new alarm becomes active. The alarm beeper will continue to periodically sound until a key is pressed on the display.
| |||||||||||||||||||||
| SapcLocalDisplayConfigBeeperVolume | 1.3.6.1.4.1.318.1.1.21.2.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The volume setting of the beeper on the local display.
| |||||||||||||||||||||
| SapcLocalDisplayConfigCheckLogIndicator | 1.3.6.1.4.1.318.1.1.21.2.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The minimum level event severity level required to illuminate the check log light on the local display. notPresent (1) indicates that the display does not have a check log light.
| |||||||||||||||||||||
| SapcLocalDisplayConfigKeyClick | 1.3.6.1.4.1.318.1.1.21.2.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The key click setting of the local display.
| |||||||||||||||||||||
| SapcLocalDisplayConfigContrast | 1.3.6.1.4.1.318.1.1.21.2.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The contrast level of the local display.
| |||||||||||||||||||||
| NisxModularDistribution | 1.3.6.1.4.1.318.1.1.22 | ||||||||||||||||||||
| NisxModularDistInfo | 1.3.6.1.4.1.318.1.1.22.1 | ||||||||||||||||||||
| SisxModularDistInfoTableSize | 1.3.6.1.4.1.318.1.1.22.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the isxModularDistInfoTable. | |||||||||||||||||||||
| TisxModularDistInfoTable | 1.3.6.1.4.1.318.1.1.22.1.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting information about the modular distribution metering equipment. | |||||||||||||||||||||
| RisxModularDistInfoEntry | 1.3.6.1.4.1.318.1.1.22.1.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information about an individual metering segment. | |||||||||||||||||||||
| CisxModularDistInfoSegmentIndex | 1.3.6.1.4.1.318.1.1.22.1.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of the metering segment. | |||||||||||||||||||||
| CisxModularDistInfoMeterModelNumber | 1.3.6.1.4.1.318.1.1.22.1.2.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The model number of the metering board for this segment. | |||||||||||||||||||||
| CisxModularDistInfoMeterSerialNumber | 1.3.6.1.4.1.318.1.1.22.1.2.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The serial number of the metering board for this segment. | |||||||||||||||||||||
| CisxModularDistInfoMeterDateOfManufacture | 1.3.6.1.4.1.318.1.1.22.1.2.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The date of manufacture for the metering board for this segment, in the format mm/dd/yyyy. | |||||||||||||||||||||
| CisxModularDistInfoMeterFirmwareRev | 1.3.6.1.4.1.318.1.1.22.1.2.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The firmware revision number of the metering board for this segment. | |||||||||||||||||||||
| CisxModularDistInfoMeterHardwareRev | 1.3.6.1.4.1.318.1.1.22.1.2.1.6 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The hardware revision number of the metering board for this segment. | |||||||||||||||||||||
| NisxModularDistModules | 1.3.6.1.4.1.318.1.1.22.2 | ||||||||||||||||||||
| SisxModularDistModuleInfoTableSize | 1.3.6.1.4.1.318.1.1.22.2.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the isxModularDistModuleInfoTable. | |||||||||||||||||||||
| TisxModularDistModuleInfoTable | 1.3.6.1.4.1.318.1.1.22.2.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting basic information about the distribution modules installed in the system. | |||||||||||||||||||||
| RisxModularDistModuleInfoEntry | 1.3.6.1.4.1.318.1.1.22.2.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information about a specific distribution module. | |||||||||||||||||||||
| CisxModularDistModuleInfoModIndex | 1.3.6.1.4.1.318.1.1.22.2.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The number of the distribution module. | |||||||||||||||||||||
| CisxModularDistModuleInfoAlarmStatus | 1.3.6.1.4.1.318.1.1.22.2.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The status of this module. This reflects the indicator lamp(s) on the front of the module. A value of notPresent indicates that the module is not installed. A value of unknown indicates that there is no communication with the metering segment for this module.
| |||||||||||||||||||||
| CisxModularDistModuleInfoModelNumber | 1.3.6.1.4.1.318.1.1.22.2.2.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The model number of the distribution module. | |||||||||||||||||||||
| CisxModularDistModuleInfoSerialNumber | 1.3.6.1.4.1.318.1.1.22.2.2.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The serial number of the distribution module. | |||||||||||||||||||||
| CisxModularDistModuleInfoDateOfManufacture | 1.3.6.1.4.1.318.1.1.22.2.2.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The date that the distribution module was manufactured. | |||||||||||||||||||||
| CisxModularDistModuleInfoNumCables | 1.3.6.1.4.1.318.1.1.22.2.2.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The number of cables provided by this distribution module. | |||||||||||||||||||||
| SisxModularDistModuleBreakerTableSize | 1.3.6.1.4.1.318.1.1.22.2.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the isxModularDistModuleBreakerTable. | |||||||||||||||||||||
| TisxModularDistModuleBreakerTable | 1.3.6.1.4.1.318.1.1.22.2.4 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting operational information about the distribution modules. | |||||||||||||||||||||
| RisxModularDistModuleBreakerEntry | 1.3.6.1.4.1.318.1.1.22.2.4.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information about a specific distribution modules and circuit breakers. | |||||||||||||||||||||
| CisxModularDistModuleBreakerModIndex | 1.3.6.1.4.1.318.1.1.22.2.4.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The distribution module number. | |||||||||||||||||||||
| CisxModularDistModuleBreakerPhaseIndex | 1.3.6.1.4.1.318.1.1.22.2.4.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to an individual breaker in the distribution module. The index also corresponds to the system phase to which the breaker is attached.
| |||||||||||||||||||||
| CisxModularDistModuleBreakerAlarmStatus | 1.3.6.1.4.1.318.1.1.22.2.4.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This is a bit map representing the active alarms for this breaker: b0 - Minimum current threshold exceeded (critical) b1 - Low current threshold exceeded (warning) b2 - High current threshold exceeded (warning) b3 - Maximum current threshold exceeded (critical) b4 - Breaker is open (critical) If a bit is set, the corresponding alarm is active. | |||||||||||||||||||||
| CisxModularDistModuleBreakerRating | 1.3.6.1.4.1.318.1.1.22.2.4.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The current rating of the breaker. | |||||||||||||||||||||
| CisxModularDistModuleBreakerPhysicalGroup | 1.3.6.1.4.1.318.1.1.22.2.4.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Numeric value used to indicate that a breaker is a part of a multi-pole breaker. Breakers within a distribution module, with equivalent physical group numbers, may have their handles physically tied together. A value of 1 indicates breakers that are physically tied together as part of a multi-pole breaker. A value of 0 indicates a single-handle breaker that is not physically tied to another breaker. | |||||||||||||||||||||
| CisxModularDistModuleBreakerCableNum | 1.3.6.1.4.1.318.1.1.22.2.4.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Numeric value used to indicate the distribution cable to which this breaker is connected. These distribution cables are described in the table isxModularDistModuleOutputTable, and indexed by the OID isxModularDistModuleOutputCordIndex. | |||||||||||||||||||||
| CisxModularDistModuleBreakerPosition | 1.3.6.1.4.1.318.1.1.22.2.4.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The physical status of this breaker pole, either closed or open (including tripped).
| |||||||||||||||||||||
| CisxModularDistModuleBreakerPositionAlarms | 1.3.6.1.4.1.318.1.1.22.2.4.1.8 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Enable or disable breaker position alarms for this circuit breaker.
| |||||||||||||||||||||
| CisxModularDistModuleBreakerCurrent | 1.3.6.1.4.1.318.1.1.22.2.4.1.9 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The current flowing though this breaker. Measured in tenths of amps. | |||||||||||||||||||||
| CisxModularDistModuleBreakerPercent | 1.3.6.1.4.1.318.1.1.22.2.4.1.10 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The loading on this breaker as a percentage of the breaker's current rating. Expressed in tenths of percent. | |||||||||||||||||||||
| CisxModularDistModuleBreakerPower | 1.3.6.1.4.1.318.1.1.22.2.4.1.11 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The power being supplied through this breaker. Measured in tenths of kW. | |||||||||||||||||||||
| SisxModularDistModuleOutputsTableSize | 1.3.6.1.4.1.318.1.1.22.2.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the isxModularDistModuleOutputTable. | |||||||||||||||||||||
| TisxModularDistModuleOutputTable | 1.3.6.1.4.1.318.1.1.22.2.6 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting and setting information related to the load equipment being fed by the distribution modules in the ISX Modular Distribution System. | |||||||||||||||||||||
| RisxModularDistModuleOutputEntry | 1.3.6.1.4.1.318.1.1.22.2.6.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information about a specific distribution module and its output distribution cables. | |||||||||||||||||||||
| CisxModularDistModuleOutputModIndex | 1.3.6.1.4.1.318.1.1.22.2.6.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The number of the distribution module supplying power to the load equipment. | |||||||||||||||||||||
| CisxModularDistModuleOutputNumCables | 1.3.6.1.4.1.318.1.1.22.2.6.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The number of distribution cables provided by this module. | |||||||||||||||||||||
| CisxModularDistModuleOutputCordIndex | 1.3.6.1.4.1.318.1.1.22.2.6.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of an individual distribution cable supplied by this module. | |||||||||||||||||||||
| CisxModularDistModuleOutputName | 1.3.6.1.4.1.318.1.1.22.2.6.1.4 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory A string describing the load equipment being supplied by this distribution cable. | |||||||||||||||||||||
| CisxModularDistModuleOutputLocation | 1.3.6.1.4.1.318.1.1.22.2.6.1.5 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory A string describing the location of equipment being supplied by distribution cable. | |||||||||||||||||||||
| CisxModularDistModuleOutputStatus | 1.3.6.1.4.1.318.1.1.22.2.6.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This reflects the worse case severity for alarms associated with this distribution cable. A value of notPresent indicates that the cable does not exist for this module. A value of unknown indicates that the there is no communication with the metering segment for this distribution cable's module.
| |||||||||||||||||||||
| CisxModularDistModuleOutputAlarmGeneration | 1.3.6.1.4.1.318.1.1.22.2.6.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Enable or disable all alarm generation related to this distribution cable.
| |||||||||||||||||||||
| CisxModularDistModuleOutputBreakerMap | 1.3.6.1.4.1.318.1.1.22.2.6.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This is a bit map representing the breaker poles within the module that are associated with this distribution cable. The following 3 bits are used to indicate the indices of the breakers feeding the cable: b0 - Module breaker L1 b1 - Module breaker L2 b2 - Module breaker L3 If a bit is set, the breaker is used to feed this distribution cable. These breakers are described in the table isxModularDistModuleBreakerTable, and indexed by the OID isxModularDistModuleBreakerPhaseIndex. | |||||||||||||||||||||
| CisxModularDistModuleOutputThresholdMin | 1.3.6.1.4.1.318.1.1.22.2.6.1.9 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory When the current drops below this value a critical alarm will exist. | |||||||||||||||||||||
| CisxModularDistModuleOutputThresholdLow | 1.3.6.1.4.1.318.1.1.22.2.6.1.10 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory When the current drops below this value a warning alarm will exist. | |||||||||||||||||||||
| CisxModularDistModuleOutputThresholdHigh | 1.3.6.1.4.1.318.1.1.22.2.6.1.11 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory When the current exceeds this value a warning alarm will exist. | |||||||||||||||||||||
| CisxModularDistModuleOutputThresholdMax | 1.3.6.1.4.1.318.1.1.22.2.6.1.12 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory When the current exceeds this value a critical alarm will exist. | |||||||||||||||||||||
| CisxModularDistModuleOutputAlarmMinEnable | 1.3.6.1.4.1.318.1.1.22.2.6.1.13 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Enable or disable minimum current alarm generation for this distribution cable.
| |||||||||||||||||||||
| CisxModularDistModuleOutputAlarmLowEnable | 1.3.6.1.4.1.318.1.1.22.2.6.1.14 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Enable or disable low current alarm generation for this distribution cable.
| |||||||||||||||||||||
| CisxModularDistModuleOutputAlarmHighEnable | 1.3.6.1.4.1.318.1.1.22.2.6.1.15 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Enable or disable high current alarm generation for this distribution cable.
| |||||||||||||||||||||
| CisxModularDistModuleOutputAlarmMaxEnable | 1.3.6.1.4.1.318.1.1.22.2.6.1.16 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Enable or disable maximum current alarm generation for this distribution cable.
| |||||||||||||||||||||
| CisxModularDistModuleOutputCableLength | 1.3.6.1.4.1.318.1.1.22.2.6.1.17 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The length of this distribution cable. Specified in tenths of meters. | |||||||||||||||||||||
| CisxModularDistModuleOutputConnectorType | 1.3.6.1.4.1.318.1.1.22.2.6.1.18 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory A string describing the connector on the end of this distribution cable. | |||||||||||||||||||||
| CisxModularDistModuleOutputAvailableVoltages | 1.3.6.1.4.1.318.1.1.22.2.6.1.19 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This is a bit map representing the voltages that are available at the connector. 6 bits are used to indicate the following: b0 - L1 b1 - L2 b2 - L3 b3 - L1-2 b4 - L2-3 b5 - L3-1 | |||||||||||||||||||||
| CisxModularDistModuleOutputTotalPower | 1.3.6.1.4.1.318.1.1.22.2.6.1.20 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The total power being consumed by the load equipment supplied by this distribution cable. Measured in tenths of kW. | |||||||||||||||||||||
| CisxModularDistModuleOutputKwhUsage | 1.3.6.1.4.1.318.1.1.22.2.6.1.21 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The total energy consumed by the load equipment fed by this distribution cable. This is the total since the date specified in the isxModularDistModuleOutputKwhResetDate OID, and may be cleared using the isxModularDistModuleOutputKwhReset OID. Measured in tenths of kWh. | |||||||||||||||||||||
| CisxModularDistModuleOutputKwhReset | 1.3.6.1.4.1.318.1.1.22.2.6.1.22 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Writing yes to this OID will reset the total kWh usage shown in the isxModularDistModuleOutputKwhUsage OID.
| |||||||||||||||||||||
| CisxModularDistModuleOutputKwhResetDate | 1.3.6.1.4.1.318.1.1.22.2.6.1.23 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The date that the kWh usage was reset, in the format mm/dd/yyyy. Example: 01/01/2000. | |||||||||||||||||||||
| NisxModularDistSubFeeds | 1.3.6.1.4.1.318.1.1.22.3 | ||||||||||||||||||||
| SisxModularDistSubFeedInfoTableSize | 1.3.6.1.4.1.318.1.1.22.3.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the isxModularDistSubFeedInfoTable. | |||||||||||||||||||||
| TisxModularDistSubFeedInfoTable | 1.3.6.1.4.1.318.1.1.22.3.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting information about distribution subfeed breakers. | |||||||||||||||||||||
| RisxModularDistSubFeedInfoEntry | 1.3.6.1.4.1.318.1.1.22.3.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information about a specific distribution subfeed. | |||||||||||||||||||||
| CisxModularDistSubFeedInfoSubIndex | 1.3.6.1.4.1.318.1.1.22.3.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of an individual subfeed. | |||||||||||||||||||||
| CisxModularDistSubFeedInfoName | 1.3.6.1.4.1.318.1.1.22.3.2.1.2 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory A string describing the load equipment being supplied by this subfeed. | |||||||||||||||||||||
| CisxModularDistSubFeedInfoLocation | 1.3.6.1.4.1.318.1.1.22.3.2.1.3 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory A string describing the location of the equipment being supplied by this subfeed. | |||||||||||||||||||||
| CisxModularDistSubFeedInfoBreakerRating | 1.3.6.1.4.1.318.1.1.22.3.2.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The current rating of this subfeed breaker. | |||||||||||||||||||||
| CisxModularDistSubFeedInfoBreakerPosition | 1.3.6.1.4.1.318.1.1.22.3.2.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The operational status of this breaker, either closed or open (including tripped).
| |||||||||||||||||||||
| CisxModularDistSubFeedInfoAlarmStatus | 1.3.6.1.4.1.318.1.1.22.3.2.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The worst case alarm status for this subfeed.
| |||||||||||||||||||||
| CisxModularDistSubFeedInfoAlarmGeneration | 1.3.6.1.4.1.318.1.1.22.3.2.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Enable or disable all alarm generation related to this subfeed.
| |||||||||||||||||||||
| CisxModularDistSubFeedInfoThresholdMin | 1.3.6.1.4.1.318.1.1.22.3.2.1.8 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory When the current drops below this value a critical alarm will exist. | |||||||||||||||||||||
| CisxModularDistSubFeedInfoThresholdLow | 1.3.6.1.4.1.318.1.1.22.3.2.1.9 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory When the current drops below this value a warning alarm will exist. | |||||||||||||||||||||
| CisxModularDistSubFeedInfoThresholdHigh | 1.3.6.1.4.1.318.1.1.22.3.2.1.10 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory When the current exceeds this value a warning alarm will exist. | |||||||||||||||||||||
| CisxModularDistSubFeedInfoThresholdMax | 1.3.6.1.4.1.318.1.1.22.3.2.1.11 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory When the current exceeds this value a critical alarm will exist. | |||||||||||||||||||||
| CisxModularDistSubFeedInfoAlarmMinEnable | 1.3.6.1.4.1.318.1.1.22.3.2.1.12 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Enable or disable minimum current alarm generation for this subfeed.
| |||||||||||||||||||||
| CisxModularDistSubFeedInfoAlarmLowEnable | 1.3.6.1.4.1.318.1.1.22.3.2.1.13 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Enable or disable low current alarm generation for this subfeed.
| |||||||||||||||||||||
| CisxModularDistSubFeedInfoAlarmHighEnable | 1.3.6.1.4.1.318.1.1.22.3.2.1.14 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Enable or disable high current alarm generation for this subfeed.
| |||||||||||||||||||||
| CisxModularDistSubFeedInfoAlarmMaxEnable | 1.3.6.1.4.1.318.1.1.22.3.2.1.15 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Enable or disable maximum current alarm generation for this subfeed.
| |||||||||||||||||||||
| CisxModularDistSubFeedInfoBreakerAlarmEnable | 1.3.6.1.4.1.318.1.1.22.3.2.1.16 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Enable or disable breaker position alarms for this subfeed.
| |||||||||||||||||||||
| CisxModularDistSubFeedInfoTotalPower | 1.3.6.1.4.1.318.1.1.22.3.2.1.17 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The total power being supplied by this subfeed. Measured in tenths of kW. | |||||||||||||||||||||
| CisxModularDistSubFeedInfoKwhUsage | 1.3.6.1.4.1.318.1.1.22.3.2.1.18 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The total energy consumed by the load equipment fed by this subfeed. This is the total since the date specified in the isxModularDistSubFeedInfoKwhResetDate OID, and may be cleared using the isxModularDistSubFeedInfoKwhReset OID. Measured in tenths of kWh. | |||||||||||||||||||||
| CisxModularDistSubFeedInfoKwhReset | 1.3.6.1.4.1.318.1.1.22.3.2.1.19 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Writing yes to this OID will reset the total kWh usage shown in the isxModularDistSubFeedInfoKwhUsage OID.
| |||||||||||||||||||||
| CisxModularDistSubFeedInfoKwhResetDate | 1.3.6.1.4.1.318.1.1.22.3.2.1.20 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The date that the kWh usage was reset, in the format mm/dd/yyyy. Example: 01/01/2000. | |||||||||||||||||||||
| SisxModularDistSubFeedLoadingTableSize | 1.3.6.1.4.1.318.1.1.22.3.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the isxModularDistSubFeedLoadingTable. | |||||||||||||||||||||
| TisxModularDistSubFeedLoadingTable | 1.3.6.1.4.1.318.1.1.22.3.4 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting subfeed phase loading information. | |||||||||||||||||||||
| RisxModularDistSubFeedLoadingEntry | 1.3.6.1.4.1.318.1.1.22.3.4.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing data for an individual subfeed. | |||||||||||||||||||||
| CisxModularDistSubFeedLoadingSubIndex | 1.3.6.1.4.1.318.1.1.22.3.4.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index of an individual subfeed. | |||||||||||||||||||||
| CisxModularDistSubFeedLoadingPhaseIndex | 1.3.6.1.4.1.318.1.1.22.3.4.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Description of each input phase entry in the table.
| |||||||||||||||||||||
| CisxModularDistSubFeedLoadingAlarmStatus | 1.3.6.1.4.1.318.1.1.22.3.4.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This is a bit map representing the active alarms for this subfeed: b0 - Minimum current threshold exceeded (critical) b1 - Low current threshold exceeded (warning) b2 - High current threshold exceeded (warning) b3 - Maximum current threshold exceeded (critical) b4 - Breaker is open (critical) If a bit is set, the corresponding alarm is active. | |||||||||||||||||||||
| CisxModularDistSubFeedLoadingCurrent | 1.3.6.1.4.1.318.1.1.22.3.4.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The current flowing though this subfeed phase. Measured in tenths of amps. | |||||||||||||||||||||
| CisxModularDistSubFeedLoadingPercent | 1.3.6.1.4.1.318.1.1.22.3.4.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The loading on this subfeed phase as a percentage of the subfeed's current rating. Expressed in tenths of percent. | |||||||||||||||||||||
| CisxModularDistSubFeedLoadingPower | 1.3.6.1.4.1.318.1.1.22.3.4.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The power being supplied by this subfeed phase. Measured in tenths of kW. | |||||||||||||||||||||
| NisxModularDistTotals | 1.3.6.1.4.1.318.1.1.22.4 | ||||||||||||||||||||
| NisxModularDistSysVoltage | 1.3.6.1.4.1.318.1.1.22.4.1 | ||||||||||||||||||||
| SisxModularDistSysOutputVoltageNominalLineToNeutral | 1.3.6.1.4.1.318.1.1.22.4.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The nominal line-to-neutral voltage available at the distribution panel. | |||||||||||||||||||||
| SisxModularDistSysOutputVoltageNominalLineToLine | 1.3.6.1.4.1.318.1.1.22.4.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The nominal line-to-line voltage available at the distribution panel. | |||||||||||||||||||||
| SisxModularDistSysOutputNominalFrequency | 1.3.6.1.4.1.318.1.1.22.4.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The nominal system output frequency. Measured in tenths of Hertz. | |||||||||||||||||||||
| SisxModularDistSysOutputFrequency | 1.3.6.1.4.1.318.1.1.22.4.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The system output frequency in tenths of Hertz. -1 if not available. | |||||||||||||||||||||
| SisxModularDistSysOutputVoltageMonitoring | 1.3.6.1.4.1.318.1.1.22.4.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Indicates whether or not output voltage alarm generation is present.
| |||||||||||||||||||||
| SisxModularDistSysOutputVoltageThresholdMin | 1.3.6.1.4.1.318.1.1.22.4.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory When the line-to-neutral voltage of any phase drops below this value a critical alarm will exist. Specified as a percent of the nominal voltage, isxModularDistSysOutputVoltageNominalLineToNeutral. This value is returned as a positive number which represents a negative percentage. A value of -1 indicates that the threshold is not available in the device. | |||||||||||||||||||||
| SisxModularDistSysOutputVoltageThresholdLow | 1.3.6.1.4.1.318.1.1.22.4.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory When the line-to-neutral voltage of any phase drops below this value a warning alarm will exist. Specified as a percent of the nominal voltage, isxModularDistSysOutputVoltageNominalLineToNeutral. This value is returned as a positive number which represents a negative percentage. A value of -1 indicates that the threshold is not available in the device. | |||||||||||||||||||||
| SisxModularDistSysOutputVoltageThresholdHigh | 1.3.6.1.4.1.318.1.1.22.4.1.8 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory When the line-to-neutral voltage of any phase exceeds this value a warning alarm will exist. Specified as a percent of the nominal voltage, isxModularDistSysOutputVoltageNominalLineToNeutral. A value of -1 indicates that the threshold is not available in the device. | |||||||||||||||||||||
| SisxModularDistSysOutputVoltageThresholdMax | 1.3.6.1.4.1.318.1.1.22.4.1.9 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory When the line-to-neutral voltage of any phase exceeds this value a critical alarm will exist. Specified as a percent of the nominal voltage, isxModularDistSysOutputVoltageNominalLineToNeutral. A value of -1 indicates that the threshold is not available in the device. | |||||||||||||||||||||
| SisxModularDistSysOutputVoltageAlarmMinEnable | 1.3.6.1.4.1.318.1.1.22.4.1.10 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Enable or disable minimum voltage alarm generation for the distribution panel.
| |||||||||||||||||||||
| SisxModularDistSysOutputVoltageAlarmLowEnable | 1.3.6.1.4.1.318.1.1.22.4.1.11 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Enable or disable low voltage alarm generation for the distribution panel.
| |||||||||||||||||||||
| SisxModularDistSysOutputVoltageAlarmHighEnable | 1.3.6.1.4.1.318.1.1.22.4.1.12 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Enable or disable high voltage alarm generation for the distribution panel.
| |||||||||||||||||||||
| SisxModularDistSysOutputVoltageAlarmMaxEnable | 1.3.6.1.4.1.318.1.1.22.4.1.13 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Enable or disable maximum voltage alarm generation for the distribution panel.
| |||||||||||||||||||||
| SisxModularDistSysOutputVoltageFrequencyTolerance | 1.3.6.1.4.1.318.1.1.22.4.1.14 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory The circuit panel output frequency tolerance in Hertz. When the system output frequency deviates from the nominal by more than this range, a critical alarm will be generated.
| |||||||||||||||||||||
| TisxModularDistSysVoltageTable | 1.3.6.1.4.1.318.1.1.22.4.1.15 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting the system output voltage information. | |||||||||||||||||||||
| RisxModularDistSysVoltageEntry | 1.3.6.1.4.1.318.1.1.22.4.1.15.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing data for an individual system output phase. | |||||||||||||||||||||
| CisxModularDistSysVoltagePhaseIndex | 1.3.6.1.4.1.318.1.1.22.4.1.15.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Description of each phase entry in the table.
| |||||||||||||||||||||
| CisxModularDistSysVoltageAlarmStatus | 1.3.6.1.4.1.318.1.1.22.4.1.15.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This is a bit map representing the active alarms for this output phase: b0 - Minimum voltage threshold exceeded (critical) b1 - Low voltage threshold exceeded (warning) b2 - High voltage threshold exceeded (warning) b3 - Maximum voltage threshold exceeded (critical) If a bit is set, the corresponding alarm is active. | |||||||||||||||||||||
| CisxModularDistSysVoltageLtoN | 1.3.6.1.4.1.318.1.1.22.4.1.15.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Line-to-neutral system output voltage available at the distribution panel. Measured in tenths of Volts. | |||||||||||||||||||||
| CisxModularDistSysVoltageLtoL | 1.3.6.1.4.1.318.1.1.22.4.1.15.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Line-to-line system output voltage available at the distribution panel. Measured in tenths of Volts. | |||||||||||||||||||||
| NisxModularDistSysCurrent | 1.3.6.1.4.1.318.1.1.22.4.2 | ||||||||||||||||||||
| SisxModularDistSysCurrentRating | 1.3.6.1.4.1.318.1.1.22.4.2.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The 100 percent current rating of the distribution panel. | |||||||||||||||||||||
| SisxModularDistSysCurrentMonitoring | 1.3.6.1.4.1.318.1.1.22.4.2.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Indicates whether or not total output current measurements and alarm generation are present.
| |||||||||||||||||||||
| SisxModularDistSysCurrentThresholdMin | 1.3.6.1.4.1.318.1.1.22.4.2.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory When total system current in any phase drops below this value a critical alarm will exist. Specified as a percent of the panel rating, isxModularDistSysCurrentRating. A value of -1 indicates that the threshold is not available in the device. | |||||||||||||||||||||
| SisxModularDistSysCurrentThresholdLow | 1.3.6.1.4.1.318.1.1.22.4.2.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory When total system current in any phase drops below this value a warning alarm will exist. Specified as a percent of the panel rating, isxModularDistSysCurrentRating. A value of -1 indicates that the threshold is not available in the device. | |||||||||||||||||||||
| SisxModularDistSysCurrentThresholdHigh | 1.3.6.1.4.1.318.1.1.22.4.2.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory When total system current in any phase exceeds this value a warning alarm will exist. Specified as a percent of the panel rating, isxModularDistSysCurrentRating. A value of -1 indicates that the threshold is not available in the device. | |||||||||||||||||||||
| SisxModularDistSysCurrentThresholdMax | 1.3.6.1.4.1.318.1.1.22.4.2.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory When total system current in any phase exceeds this value a critical alarm will exist. Specified as a percent of the panel rating, isxModularDistSysCurrentRating. A value of -1 indicates that the threshold is not available in the device. | |||||||||||||||||||||
| SisxModularDistSysCurrentAlarmMinEnable | 1.3.6.1.4.1.318.1.1.22.4.2.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Enable or disable minimum total output current alarm generation.
| |||||||||||||||||||||
| SisxModularDistSysCurrentAlarmLowEnable | 1.3.6.1.4.1.318.1.1.22.4.2.8 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Enable or disable low total output current alarm generation.
| |||||||||||||||||||||
| SisxModularDistSysCurrentAlarmHighEnable | 1.3.6.1.4.1.318.1.1.22.4.2.9 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Enable or disable high total output current alarm generation.
| |||||||||||||||||||||
| SisxModularDistSysCurrentAlarmMaxEnable | 1.3.6.1.4.1.318.1.1.22.4.2.10 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Enable or disable maximum total output current alarm generation.
| |||||||||||||||||||||
| TisxModularDistSysCurrentTable | 1.3.6.1.4.1.318.1.1.22.4.2.11 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting the total system phase current information. | |||||||||||||||||||||
| RisxModularDistSysCurrentEntry | 1.3.6.1.4.1.318.1.1.22.4.2.11.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing data for an individual system output phase. | |||||||||||||||||||||
| CisxModularDistSysCurrentPhaseIndex | 1.3.6.1.4.1.318.1.1.22.4.2.11.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Description of each phase entry in the table.
| |||||||||||||||||||||
| CisxModularDistSysCurrentAlarmStatus | 1.3.6.1.4.1.318.1.1.22.4.2.11.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This is a bit map representing the active alarms for this output phase: b0 - Minimum current threshold exceeded (critical) b1 - Low current threshold exceeded (warning) b2 - High current threshold exceeded (warning) b3 - Maximum current threshold exceeded (critical) If a bit is set, the corresponding alarm is active. | |||||||||||||||||||||
| CisxModularDistSysCurrentAmps | 1.3.6.1.4.1.318.1.1.22.4.2.11.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The current flowing though this system output phase. Measured in tenths of amps. | |||||||||||||||||||||
| CisxModularDistSysCurrentPercent | 1.3.6.1.4.1.318.1.1.22.4.2.11.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The loading on this system output phase as a percentage of the panel current rating. Expressed in tenths of percent. | |||||||||||||||||||||
| NisxModularDistSysPower | 1.3.6.1.4.1.318.1.1.22.4.3 | ||||||||||||||||||||
| SisxModularDistSysPowerTotal | 1.3.6.1.4.1.318.1.1.22.4.3.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The total system power being supplied. Measured in tenths of kW. | |||||||||||||||||||||
| SisxModularDistSysPowerKwhUsage | 1.3.6.1.4.1.318.1.1.22.4.3.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The total system energy consumed by the load equipment. This is the total since the date specified in the isxModularDistSysOutputKwhResetDate OID, and may be cleared using the isxModularDistSysOutputKwhReset OID. Measured in tenths of kWh. | |||||||||||||||||||||
| SisxModularDistSysPowerKwhReset | 1.3.6.1.4.1.318.1.1.22.4.3.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Writing yes to this OID will reset the total kWh usage shown in the isxModularDistSysPowerKwhUsage OID.
| |||||||||||||||||||||
| SisxModularDistSysPowerKwhResetDate | 1.3.6.1.4.1.318.1.1.22.4.3.4 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The date that the kWh usage was reset, in the format mm/dd/yyyy. Example: 01/01/2000. | |||||||||||||||||||||
| TisxModularDistSysPowerTable | 1.3.6.1.4.1.318.1.1.22.4.3.5 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting the total system phase power loading information. | |||||||||||||||||||||
| RisxModularDistSysPowerEntry | 1.3.6.1.4.1.318.1.1.22.4.3.5.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing data for an individual system output phase. | |||||||||||||||||||||
| CisxModularDistSysPowerPhaseIndex | 1.3.6.1.4.1.318.1.1.22.4.3.5.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Description of each phase entry in the table.
| |||||||||||||||||||||
| CisxModularDistSysPowerKw | 1.3.6.1.4.1.318.1.1.22.4.3.5.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The power being supplied by this system output phase. Measured in tenths of kW. | |||||||||||||||||||||
| CisxModularDistSysPowerKwhPhaseUsage | 1.3.6.1.4.1.318.1.1.22.4.3.5.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The energy consumed by the load equipment on this system output phase. This is the total since the date specified in the isxModularDistSysPowerKwhResetDate OID, and may be cleared using the isxModularDistSysPowerKwhReset OID. Measured in tenths of kWh. | |||||||||||||||||||||
| NisxModularPdu | 1.3.6.1.4.1.318.1.1.23 | ||||||||||||||||||||
| NisxModularPduIdent | 1.3.6.1.4.1.318.1.1.23.1 | ||||||||||||||||||||
| SisxModularPduIdentModelNumber | 1.3.6.1.4.1.318.1.1.23.1.1 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the model number of the PDU. This value is set at the factory. | |||||||||||||||||||||
| SisxModularPduIdentSerialNumber | 1.3.6.1.4.1.318.1.1.23.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the serial number of the PDU. This value is set at the factory. | |||||||||||||||||||||
| SisxModularPduIdentDateOfManufacture | 1.3.6.1.4.1.318.1.1.23.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The date when the PDU was manufactured in mm/dd/yyyy format. This value is set at the factory. | |||||||||||||||||||||
| SisxModularPduIdentMonitorCardSerialNumber | 1.3.6.1.4.1.318.1.1.23.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the serial number of the PDU monitor card. This value is set at the factory. | |||||||||||||||||||||
| SisxModularPduIdentMonitorCardHardwareRev | 1.3.6.1.4.1.318.1.1.23.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The hardware revision of the PDU monitor card. This value is set at the factory. | |||||||||||||||||||||
| SisxModularPduIdentMonitorCardFirmwareAppRev | 1.3.6.1.4.1.318.1.1.23.1.6 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory An ID string identifying the application firmware revision of the PDU monitor card. | |||||||||||||||||||||
| SisxModularPduIdentMonitorCardFirmwareAppOSRev | 1.3.6.1.4.1.318.1.1.23.1.7 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory An ID string identifying the application operating system firmware revision of the PDU monitor card. | |||||||||||||||||||||
| NisxModularPduDevice | 1.3.6.1.4.1.318.1.1.23.2 | ||||||||||||||||||||
| SisxModularPduDeviceTransformerPresent | 1.3.6.1.4.1.318.1.1.23.2.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Indicates the type of transformer present in this PDU.
| |||||||||||||||||||||
| SisxModularPduDeviceServiceType | 1.3.6.1.4.1.318.1.1.23.2.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The type of utility input to the PDU. Either 3 wires (delta), or 4 wires (wye).
| |||||||||||||||||||||
| SisxModularPduDeviceFansPresent | 1.3.6.1.4.1.318.1.1.23.2.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Indicates whether or not cooling fans are installed in the PDU.
| |||||||||||||||||||||
| SisxModularPduDeviceNominalMainInputVoltage | 1.3.6.1.4.1.318.1.1.23.2.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The nominal main input voltage to the system. Measured in Volts, line-to-line for a 3-wire (delta) service or line-to-neutral for a 4-wire (wye) service. -1 if main input voltage is not being measured. | |||||||||||||||||||||
| NisxModularPduStatus | 1.3.6.1.4.1.318.1.1.23.3 | ||||||||||||||||||||
| SisxModularPduAlarmStatus | 1.3.6.1.4.1.318.1.1.23.3.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The overall status (worst case) of this PDU.
| |||||||||||||||||||||
| SisxModularPduTransformerTempStatus | 1.3.6.1.4.1.318.1.1.23.3.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Indicates if the PDU isolation transformer is over temperature.
| |||||||||||||||||||||
| SisxModularPduFanStatus | 1.3.6.1.4.1.318.1.1.23.3.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Indicates if one or more of the PDU's cooling fans have failed.
| |||||||||||||||||||||
| NuniversalInputOutput | 1.3.6.1.4.1.318.1.1.25 | ||||||||||||||||||||
| NuioSensor | 1.3.6.1.4.1.318.1.1.25.1 | ||||||||||||||||||||
| SuioSensorStatusTableSize | 1.3.6.1.4.1.318.1.1.25.1.1 | INTEGER | RO | mandatory | 2 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the uioSensorStatusTable. Example values from LibreNMS test devices
| |||||||||||||||||||||
| TuioSensorStatusTable | 1.3.6.1.4.1.318.1.1.25.1.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting sensor status information. | |||||||||||||||||||||
| RuioSensorStatusEntry | 1.3.6.1.4.1.318.1.1.25.1.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The unit from which to get data. | |||||||||||||||||||||
| CuioSensorStatusPortID | 1.3.6.1.4.1.318.1.1.25.1.2.1.1 | INTEGER | RO | mandatory | 1 | ||||||||||||||||
column · INTEGER · read-only · mandatory The ID of the port to which the sensor is attached. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CuioSensorStatusSensorID | 1.3.6.1.4.1.318.1.1.25.1.2.1.2 | INTEGER | RO | mandatory | 1 | ||||||||||||||||
column · INTEGER · read-only · mandatory The ID of the sensor. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CuioSensorStatusSensorName | 1.3.6.1.4.1.318.1.1.25.1.2.1.3 | DisplayString | RO | mandatory | Temp. Rack | ||||||||||||||||
column · DisplayString · read-only · mandatory The sensor name. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CuioSensorStatusSensorLocation | 1.3.6.1.4.1.318.1.1.25.1.2.1.4 | DisplayString | RO | mandatory | Room | ||||||||||||||||
column · DisplayString · read-only · mandatory The location of the sensor. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CuioSensorStatusTemperatureDegF | 1.3.6.1.4.1.318.1.1.25.1.2.1.5 | INTEGER | RO | mandatory | 86 | ||||||||||||||||
column · INTEGER · read-only · mandatory The sensor's current temperature reading in degrees Fahrenheit. -1 indicates an invalid reading due to lost communications. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CuioSensorStatusTemperatureDegC | 1.3.6.1.4.1.318.1.1.25.1.2.1.6 | INTEGER | RO | mandatory | 30 | ||||||||||||||||
column · INTEGER · read-only · mandatory The sensor's current temperature reading in degrees Celsius. -1 indicates an invalid reading due to lost communications. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CuioSensorStatusHumidity | 1.3.6.1.4.1.318.1.1.25.1.2.1.7 | INTEGER | RO | mandatory | -1 | ||||||||||||||||
column · INTEGER · read-only · mandatory The sensor's current humidity reading in percent relative humidity. -1 indicates an invalid reading due to either a sensor that doesn't read humidity or lost communications. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CuioSensorStatusViolationStatus | 1.3.6.1.4.1.318.1.1.25.1.2.1.8 | INTEGER | RO | mandatory | 0 | ||||||||||||||||
column · INTEGER · read-only · mandatory The violation status of the sensor. This integer should be interpreted as a bit map, with each bit representing the presence or absence of the specific alarm conditions listed below. The bit will be '1' if the condition is present, and '0' if the condition is not present. Bit Hex. Value Description 1 0x0001 Maximum temperature exceeded. 2 0x0002 High temperature exceeded. 3 0x0004 Low temperature exceeded. 4 0x0008 Minimum temperature exceeded. 5 0x0010 Short-term increasing temperature rate exceeded (Not used). 6 0x0020 Short-term decreasing temperature rate exceeded (Not used). 7 0x0040 Long-term increasing temperature rate exceeded (Not used). 8 0x0080 Long-term decreasing temperature rate exceeded (Not used). 9 0x0100 Maximum humidity exceeded. 10 0x0200 High humidity exceeded. 11 0x0400 Low humidity exceeded. 12 0x0800 Minimum humidity exceeded. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CuioSensorStatusAlarmStatus | 1.3.6.1.4.1.318.1.1.25.1.2.1.9 | INTEGER | RO | mandatory | uioNormal(1) | ||||||||||||||||
column · INTEGER · read-only · mandatory The alarm status of the sensor.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CuioSensorStatusCommStatus | 1.3.6.1.4.1.318.1.1.25.1.2.1.10 | INTEGER | RO | mandatory | commsOK(2) | ||||||||||||||||
column · INTEGER · read-only · mandatory The communications status of the sensor.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| SuioSensorConfigTableSize | 1.3.6.1.4.1.318.1.1.25.1.3 | INTEGER | RO | mandatory | 2 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the uioSensorConfigTable. Example values from LibreNMS test devices
| |||||||||||||||||||||
| TuioSensorConfigTable | 1.3.6.1.4.1.318.1.1.25.1.4 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for configuring the sensor. | |||||||||||||||||||||
| RuioSensorConfigEntry | 1.3.6.1.4.1.318.1.1.25.1.4.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The sensor from which to get configuration. | |||||||||||||||||||||
| CuioSensorConfigPortID | 1.3.6.1.4.1.318.1.1.25.1.4.1.1 | INTEGER | RO | mandatory | 1 | ||||||||||||||||
column · INTEGER · read-only · mandatory The ID of the port to which the sensor is attached. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CuioSensorConfigSensorID | 1.3.6.1.4.1.318.1.1.25.1.4.1.2 | INTEGER | RO | mandatory | 1 | ||||||||||||||||
column · INTEGER · read-only · mandatory The ID of the sensor. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CuioSensorConfigSensorName | 1.3.6.1.4.1.318.1.1.25.1.4.1.3 | DisplayString | RW | mandatory | Temp. Rack | ||||||||||||||||
column · DisplayString · read-write · mandatory The sensor name. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CuioSensorConfigSensorLocation | 1.3.6.1.4.1.318.1.1.25.1.4.1.4 | DisplayString | RW | mandatory | Room | ||||||||||||||||
column · DisplayString · read-write · mandatory The location of the sensor. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CuioSensorConfigMinTemperatureThreshold | 1.3.6.1.4.1.318.1.1.25.1.4.1.5 | INTEGER | RW | mandatory | 0 | ||||||||||||||||
column · INTEGER · read-write · mandatory The minimum (critical) temperature alarm threshold for the probe in degrees C. Must be lower than the low threshold to ensure proper sensor alarm behavior. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CuioSensorConfigLowTemperatureThreshold | 1.3.6.1.4.1.318.1.1.25.1.4.1.6 | INTEGER | RW | mandatory | 10 | ||||||||||||||||
column · INTEGER · read-write · mandatory The low (warning) temperature alarm threshold for the probe in degrees C. Must be higher than the minimum threshold and lower than the high threshold to ensure proper sensor alarm behavior. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CuioSensorConfigHighTemperatureThreshold | 1.3.6.1.4.1.318.1.1.25.1.4.1.7 | INTEGER | RW | mandatory | 40 | ||||||||||||||||
column · INTEGER · read-write · mandatory The high (warning) temperature alarm threshold for the probe in degrees C. Must be lower than the maximum threshold and higher than the low threshold to ensure proper sensor alarm behavior. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CuioSensorConfigMaxTemperatureThreshold | 1.3.6.1.4.1.318.1.1.25.1.4.1.8 | INTEGER | RW | mandatory | 60 | ||||||||||||||||
column · INTEGER · read-write · mandatory The maximum (critical) temperature alarm threshold for the probe in degrees C. Must be higher than the high threshold to ensure proper sensor alarm behavior. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CuioSensorConfigTemperatureHysteresis | 1.3.6.1.4.1.318.1.1.25.1.4.1.9 | INTEGER | RW | mandatory | 0 | ||||||||||||||||
column · INTEGER · read-write · mandatory The number of degrees C beyond the temperature thresholds at which an active temperature alarm will be cleared. This value applies to all temperature thresholds. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CuioSensorConfigMinTemperatureEnable | 1.3.6.1.4.1.318.1.1.25.1.4.1.10 | INTEGER | RW | mandatory | disabled(1) | ||||||||||||||||
column · INTEGER · read-write · mandatory The minimum temperature alarm enable/disable for the sensor. 1 - disabled 2 - enabled
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CuioSensorConfigLowTemperatureEnable | 1.3.6.1.4.1.318.1.1.25.1.4.1.11 | INTEGER | RW | mandatory | disabled(1) | ||||||||||||||||
column · INTEGER · read-write · mandatory The low temperature alarm enable/disable for the sensor. 1 - disabled 2 - enabled
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CuioSensorConfigHighTemperatureEnable | 1.3.6.1.4.1.318.1.1.25.1.4.1.12 | INTEGER | RW | mandatory | disabled(1) | ||||||||||||||||
column · INTEGER · read-write · mandatory The high temperature alarm enable/disable for the sensor. 1 - disabled 2 - enabled
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CuioSensorConfigMaxTemperatureEnable | 1.3.6.1.4.1.318.1.1.25.1.4.1.13 | INTEGER | RW | mandatory | disabled(1) | ||||||||||||||||
column · INTEGER · read-write · mandatory The maximum temperature alarm enable/disable for the sensor. 1 - disabled 2 - enabled
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CuioSensorConfigMinHumidityThreshold | 1.3.6.1.4.1.318.1.1.25.1.4.1.14 | INTEGER | RW | mandatory | -1 | ||||||||||||||||
column · INTEGER · read-write · mandatory The minimum (critical) humidity alarm threshold for the probe in percent relative humidity. Must be lower than the low threshold to ensure proper sensor alarm behavior. -1 if the sensor doesn't read humidity. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CuioSensorConfigLowHumidityThreshold | 1.3.6.1.4.1.318.1.1.25.1.4.1.15 | INTEGER | RW | mandatory | -1 | ||||||||||||||||
column · INTEGER · read-write · mandatory The low (warning) humidity alarm threshold for the probe in percent relative humidity. Must be higher than the minimum threshold and lower than the high threshold to ensure proper sensor alarm behavior. -1 if the sensor doesn't read humidity. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CuioSensorConfigHighHumidityThreshold | 1.3.6.1.4.1.318.1.1.25.1.4.1.16 | INTEGER | RW | mandatory | -1 | ||||||||||||||||
column · INTEGER · read-write · mandatory The high (warning) humidity alarm threshold for the probe in percent relative humidity. Must be lower than the maximum threshold and higher than the low threshold to ensure proper sensor alarm behavior. -1 if the sensor doesn't read humidity. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CuioSensorConfigMaxHumidityThreshold | 1.3.6.1.4.1.318.1.1.25.1.4.1.17 | INTEGER | RW | mandatory | -1 | ||||||||||||||||
column · INTEGER · read-write · mandatory The maximum (critical) humidity alarm threshold for the probe in percent relative humidity. Must be higher than the high threshold to ensure proper sensor alarm behavior. -1 if the sensor doesn't read humidity. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CuioSensorConfigHumidityHysteresis | 1.3.6.1.4.1.318.1.1.25.1.4.1.18 | INTEGER | RW | mandatory | -1 | ||||||||||||||||
column · INTEGER · read-write · mandatory The number of percent relative humidity beyond the humidity thresholds at which an active humidity alarm will be cleared. This value applies to all humidity thresholds. -1 if the sensor doesn't read humidity. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CuioSensorConfigMinHumidityEnable | 1.3.6.1.4.1.318.1.1.25.1.4.1.19 | INTEGER | RW | mandatory | disabled(1) | ||||||||||||||||
column · INTEGER · read-write · mandatory The minimum humidity alarm enable/disable for the sensor. 1 - disabled (always set if the sensor doesn't read humidity) 2 - enabled
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CuioSensorConfigLowHumidityEnable | 1.3.6.1.4.1.318.1.1.25.1.4.1.20 | INTEGER | RW | mandatory | disabled(1) | ||||||||||||||||
column · INTEGER · read-write · mandatory The low humidity alarm enable/disable for the sensor. 1 - disabled (always set if the sensor doesn't read humidity) 2 - enabled
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CuioSensorConfigHighHumidityEnable | 1.3.6.1.4.1.318.1.1.25.1.4.1.21 | INTEGER | RW | mandatory | disabled(1) | ||||||||||||||||
column · INTEGER · read-write · mandatory The high humidity alarm enable/disable for the sensor. 1 - disabled (always set if the sensor doesn't read humidity) 2 - enabled
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CuioSensorConfigMaxHumidityEnable | 1.3.6.1.4.1.318.1.1.25.1.4.1.22 | INTEGER | RW | mandatory | disabled(1) | ||||||||||||||||
column · INTEGER · read-write · mandatory The maximum humidity alarm enable/disable for the sensor. 1 - disabled (always set if the sensor doesn't read humidity) 2 - enabled
Example values from LibreNMS test devices
| |||||||||||||||||||||
| NuioInputContact | 1.3.6.1.4.1.318.1.1.25.2 | ||||||||||||||||||||
| SuioInputContactStatusTableSize | 1.3.6.1.4.1.318.1.1.25.2.1 | INTEGER | RO | mandatory | 0 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the uioInputContactStatusTable. Example values from LibreNMS test devices
| |||||||||||||||||||||
| TuioInputContactStatusTable | 1.3.6.1.4.1.318.1.1.25.2.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting input contact status information. | |||||||||||||||||||||
| RuioInputContactStatusEntry | 1.3.6.1.4.1.318.1.1.25.2.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The input contact from which to get data. | |||||||||||||||||||||
| CuioInputContactStatusPortID | 1.3.6.1.4.1.318.1.1.25.2.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The ID of the port to which the input contact is attached. | |||||||||||||||||||||
| CuioInputContactStatusContactID | 1.3.6.1.4.1.318.1.1.25.2.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The ID of the input contact on the module. | |||||||||||||||||||||
| CuioInputContactStatusContactName | 1.3.6.1.4.1.318.1.1.25.2.2.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The input contact name. | |||||||||||||||||||||
| CuioInputContactStatusContactLocation | 1.3.6.1.4.1.318.1.1.25.2.2.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The location of the input contact. | |||||||||||||||||||||
| CuioInputContactStatusCurrentState | 1.3.6.1.4.1.318.1.1.25.2.2.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The current state of the input contact.
| |||||||||||||||||||||
| CuioInputContactStatusAlarmStatus | 1.3.6.1.4.1.318.1.1.25.2.2.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The alarm status of the input contact.
| |||||||||||||||||||||
| CuioInputContactStatusCommStatus | 1.3.6.1.4.1.318.1.1.25.2.2.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The communications status of the input contact.
| |||||||||||||||||||||
| SuioInputContactConfigTableSize | 1.3.6.1.4.1.318.1.1.25.2.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the uioInputContactConfigTable. | |||||||||||||||||||||
| TuioInputContactConfigTable | 1.3.6.1.4.1.318.1.1.25.2.4 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for configuring the input contacts. | |||||||||||||||||||||
| RuioInputContactConfigEntry | 1.3.6.1.4.1.318.1.1.25.2.4.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The input contact from which to get configuration. | |||||||||||||||||||||
| CuioInputContactConfigPortID | 1.3.6.1.4.1.318.1.1.25.2.4.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The ID of the port to which the input contact is attached. | |||||||||||||||||||||
| CuioInputContactConfigContactID | 1.3.6.1.4.1.318.1.1.25.2.4.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The ID of the input contact on the module. | |||||||||||||||||||||
| CuioInputContactConfigContactName | 1.3.6.1.4.1.318.1.1.25.2.4.1.3 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The input contact name. | |||||||||||||||||||||
| CuioInputContactConfigContactLocation | 1.3.6.1.4.1.318.1.1.25.2.4.1.4 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The location of the input contact. | |||||||||||||||||||||
| CuioInputContactConfigEnable | 1.3.6.1.4.1.318.1.1.25.2.4.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Enable or disable this input contact. 1 - disabled 2 - enabled
| |||||||||||||||||||||
| CuioInputContactConfigNormalState | 1.3.6.1.4.1.318.1.1.25.2.4.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The normal (non-alarm) state of the input contact. 1 - normally open 2 - normally closed
| |||||||||||||||||||||
| CuioInputContactConfigSeverity | 1.3.6.1.4.1.318.1.1.25.2.4.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The severity of the alarm that this input contact will generate in the abnormal state. 1 - critical severity 2 - warning severity
| |||||||||||||||||||||
| NuioOutputRelay | 1.3.6.1.4.1.318.1.1.25.3 | ||||||||||||||||||||
| SuioOutputRelayStatusTableSize | 1.3.6.1.4.1.318.1.1.25.3.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the uioOutputRelayStatusTable. | |||||||||||||||||||||
| TuioOutputRelayStatusTable | 1.3.6.1.4.1.318.1.1.25.3.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting output relay status information. | |||||||||||||||||||||
| RuioOutputRelayStatusEntry | 1.3.6.1.4.1.318.1.1.25.3.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The unit from which to get data. | |||||||||||||||||||||
| CuioOutputRelayStatusPortID | 1.3.6.1.4.1.318.1.1.25.3.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The ID of the port to which the output relay is attached. | |||||||||||||||||||||
| CuioOutputRelayStatusRelayID | 1.3.6.1.4.1.318.1.1.25.3.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The ID of the output relay on the module. | |||||||||||||||||||||
| CuioOutputRelayStatusRelayName | 1.3.6.1.4.1.318.1.1.25.3.2.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The output relay name. | |||||||||||||||||||||
| CuioOutputRelayStatusRelayLocation | 1.3.6.1.4.1.318.1.1.25.3.2.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The location of the output relay. | |||||||||||||||||||||
| CuioOutputRelayStatusCurrentState | 1.3.6.1.4.1.318.1.1.25.3.2.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The current state of the output relay.
| |||||||||||||||||||||
| CuioOutputRelayStatusAlarmStatus | 1.3.6.1.4.1.318.1.1.25.3.2.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The alarm status of the output relay.
| |||||||||||||||||||||
| CuioOutputRelayStatusCommStatus | 1.3.6.1.4.1.318.1.1.25.3.2.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The communications status of the output relay.
| |||||||||||||||||||||
| SuioOutputRelayConfigTableSize | 1.3.6.1.4.1.318.1.1.25.3.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the uioOutputRelayConfigTable. | |||||||||||||||||||||
| TuioOutputRelayConfigTable | 1.3.6.1.4.1.318.1.1.25.3.4 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for configuring the output relay. | |||||||||||||||||||||
| RuioOutputRelayConfigEntry | 1.3.6.1.4.1.318.1.1.25.3.4.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The unit from which to get configuration. | |||||||||||||||||||||
| CuioOutputRelayConfigPortID | 1.3.6.1.4.1.318.1.1.25.3.4.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The ID of the port to which the output relay is attached. | |||||||||||||||||||||
| CuioOutputRelayConfigRelayID | 1.3.6.1.4.1.318.1.1.25.3.4.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The ID of the output relay on the module. | |||||||||||||||||||||
| CuioOutputRelayConfigRelayName | 1.3.6.1.4.1.318.1.1.25.3.4.1.3 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The output relay name. | |||||||||||||||||||||
| CuioOutputRelayConfigRelayLocation | 1.3.6.1.4.1.318.1.1.25.3.4.1.4 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The location of the output relay. | |||||||||||||||||||||
| CuioOutputRelayConfigNormalState | 1.3.6.1.4.1.318.1.1.25.3.4.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The normal state of the output relay. 1 - normally open 2 - normally closed
| |||||||||||||||||||||
| CuioOutputRelayConfigControlState | 1.3.6.1.4.1.318.1.1.25.3.4.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Close or open the output relay for testing purposes. Always returns 1 when read. 1 - close output relay 2 - open output relay
| |||||||||||||||||||||
| CuioOutputRelayConfigDelay | 1.3.6.1.4.1.318.1.1.25.3.4.1.7 | TimeTicks | RW | mandatory | |||||||||||||||||
column · TimeTicks · read-write · mandatory The time a selected alarm condition must exist before the output relay is activated. Valid values are whole seconds from 0 to 65535. | |||||||||||||||||||||
| CuioOutputRelayConfigHold | 1.3.6.1.4.1.318.1.1.25.3.4.1.8 | TimeTicks | RW | mandatory | |||||||||||||||||
column · TimeTicks · read-write · mandatory The minimum time the output relay remains activated after the alarm occurs. Valid values are whole seconds from 0 to 65535. | |||||||||||||||||||||
| NuioSpotFluidSensor | 1.3.6.1.4.1.318.1.1.25.4 | ||||||||||||||||||||
| SuioSpotFluidSensorStatusTableSize | 1.3.6.1.4.1.318.1.1.25.4.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the uioSpotFluidSensorStatusTable. | |||||||||||||||||||||
| TuioSpotFluidSensorStatusTable | 1.3.6.1.4.1.318.1.1.25.4.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for getting fluid sensor status information. | |||||||||||||||||||||
| RuioSpotFluidSensorStatusEntry | 1.3.6.1.4.1.318.1.1.25.4.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The unit from which to get data. | |||||||||||||||||||||
| CuioSpotFluidSensorStatusPortID | 1.3.6.1.4.1.318.1.1.25.4.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The ID of the port to which the fluid sensor is attached. | |||||||||||||||||||||
| CuioSpotFluidSensorStatusSensorID | 1.3.6.1.4.1.318.1.1.25.4.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The ID of the fluid sensor on the module. | |||||||||||||||||||||
| CuioSpotFluidSensorStatusSensorName | 1.3.6.1.4.1.318.1.1.25.4.2.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The fluid sensor name. | |||||||||||||||||||||
| CuioSpotFluidSensorStatusSensorLocation | 1.3.6.1.4.1.318.1.1.25.4.2.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The location of the fluid sensor. | |||||||||||||||||||||
| CuioSpotFluidSensorStatusCurrentState | 1.3.6.1.4.1.318.1.1.25.4.2.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The current state of the fluid sensor.
| |||||||||||||||||||||
| CuioSpotFluidSensorStatusAlarmStatus | 1.3.6.1.4.1.318.1.1.25.4.2.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The alarm status of the fluid sensor.
| |||||||||||||||||||||
| CuioSpotFluidSensorStatusCommStatus | 1.3.6.1.4.1.318.1.1.25.4.2.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The communications status of the fluid sensor.
| |||||||||||||||||||||
| SuioSpotFluidSensorConfigTableSize | 1.3.6.1.4.1.318.1.1.25.4.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of entries in the uioSpotFluidSensorConfigTable. | |||||||||||||||||||||
| TuioSpotFluidSensorConfigTable | 1.3.6.1.4.1.318.1.1.25.4.4 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Allows for configuring the fluid sensor. | |||||||||||||||||||||
| RuioSpotFluidSensorConfigEntry | 1.3.6.1.4.1.318.1.1.25.4.4.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory The unit from which to get configuration. | |||||||||||||||||||||
| CuioSpotFluidSensorConfigPortID | 1.3.6.1.4.1.318.1.1.25.4.4.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The ID of the port to which the fluid sensor is attached. | |||||||||||||||||||||
| CuioSpotFluidSensorConfigSensorID | 1.3.6.1.4.1.318.1.1.25.4.4.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The ID of the fluid sensor on the module. | |||||||||||||||||||||
| CuioSpotFluidSensorConfigSensorName | 1.3.6.1.4.1.318.1.1.25.4.4.1.3 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The fluid sensor name. | |||||||||||||||||||||
| CuioSpotFluidSensorConfigSensorLocation | 1.3.6.1.4.1.318.1.1.25.4.4.1.4 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The location of the fluid sensor. | |||||||||||||||||||||
| NrPDU2 | 1.3.6.1.4.1.318.1.1.26 | ||||||||||||||||||||
| SrPDU2IdentTableSize | 1.3.6.1.4.1.318.1.1.26.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The total number of Rack PDUs | |||||||||||||||||||||
| TrPDU2IdentTable | 1.3.6.1.4.1.318.1.1.26.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A table of Rack PDU identification data | |||||||||||||||||||||
| RrPDU2IdentEntry | 1.3.6.1.4.1.318.1.1.26.2.1 | NA | mandatory | ||||||||||||||||||
| CrPDU2IdentIndex | 1.3.6.1.4.1.318.1.1.26.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the Rack PDU identification table entry | |||||||||||||||||||||
| CrPDU2IdentModule | 1.3.6.1.4.1.318.1.1.26.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The user-defined Rack PDU numeric ID | |||||||||||||||||||||
| CrPDU2IdentName | 1.3.6.1.4.1.318.1.1.26.2.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory A user-defined string identifying the Rack PDU | |||||||||||||||||||||
| CrPDU2IdentLocation | 1.3.6.1.4.1.318.1.1.26.2.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory A user-defined string identifying the location of the Rack PDU | |||||||||||||||||||||
| CrPDU2IdentHardwareRev | 1.3.6.1.4.1.318.1.1.26.2.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The Rack PDU hardware version | |||||||||||||||||||||
| CrPDU2IdentFirmwareRev | 1.3.6.1.4.1.318.1.1.26.2.1.6 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The Rack PDU firmware version | |||||||||||||||||||||
| CrPDU2IdentDateOfManufacture | 1.3.6.1.4.1.318.1.1.26.2.1.7 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The date the Rack PDU was manufactured in mm/dd/yyyy format | |||||||||||||||||||||
| CrPDU2IdentModelNumber | 1.3.6.1.4.1.318.1.1.26.2.1.8 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The Rack PDU model number | |||||||||||||||||||||
| CrPDU2IdentSerialNumber | 1.3.6.1.4.1.318.1.1.26.2.1.9 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The Rack PDU serial number | |||||||||||||||||||||
| CrPDU2IdentContact | 1.3.6.1.4.1.318.1.1.26.2.1.10 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory A user-defined string identifying the person to contact regarding the Rack PDU | |||||||||||||||||||||
| CrPDU2IdentBootMonitorRev | 1.3.6.1.4.1.318.1.1.26.2.1.11 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The Rack PDU Boot Monitor version | |||||||||||||||||||||
| CrPDU2IdentLongDescription | 1.3.6.1.4.1.318.1.1.26.2.1.12 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The Rack PDU Long Description name | |||||||||||||||||||||
| CrPDU2IdentNMCSerialNumber | 1.3.6.1.4.1.318.1.1.26.2.1.13 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The Rack PDU Network Management Card (NMC) serial number | |||||||||||||||||||||
| CrPDU2IndentAppBuildDate | 1.3.6.1.4.1.318.1.1.26.2.1.14 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The Rack PDU Application build date | |||||||||||||||||||||
| CrPDU2IndentAOSBuildDate | 1.3.6.1.4.1.318.1.1.26.2.1.15 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The Rack PDU AOS build date | |||||||||||||||||||||
| CrPDU2IndentBootMonBuildDate | 1.3.6.1.4.1.318.1.1.26.2.1.16 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The Rack PDU Boot Monitor build date | |||||||||||||||||||||
| SrPDU2DeviceTableSize | 1.3.6.1.4.1.318.1.1.26.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The total number of Rack PDUs | |||||||||||||||||||||
| NrPDU2Device | 1.3.6.1.4.1.318.1.1.26.4 | ||||||||||||||||||||
| TrPDU2DeviceConfigTable | 1.3.6.1.4.1.318.1.1.26.4.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A table of Rack PDU configuration data | |||||||||||||||||||||
| RrPDU2DeviceConfigEntry | 1.3.6.1.4.1.318.1.1.26.4.1.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory Configuration data from Rack PDU being queried | |||||||||||||||||||||
| CrPDU2DeviceConfigIndex | 1.3.6.1.4.1.318.1.1.26.4.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the Rack PDU table entry | |||||||||||||||||||||
| CrPDU2DeviceConfigModule | 1.3.6.1.4.1.318.1.1.26.4.1.1.2 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The user-defined Rack PDU numeric ID | |||||||||||||||||||||
| CrPDU2DeviceConfigName | 1.3.6.1.4.1.318.1.1.26.4.1.1.3 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory A user-defined string identifying the Rack PDU | |||||||||||||||||||||
| CrPDU2DeviceConfigLocation | 1.3.6.1.4.1.318.1.1.26.4.1.1.4 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory A user-defined string identifying the location of the Rack PDU | |||||||||||||||||||||
| CrPDU2DeviceConfigDisplayOrientation | 1.3.6.1.4.1.318.1.1.26.4.1.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Indicates the intended physical orientation of the display. displayNormal(1) indicates normal orientation displayReverse(2) indicates upside down orientation
| |||||||||||||||||||||
| CrPDU2DeviceConfigColdstartDelay | 1.3.6.1.4.1.318.1.1.26.4.1.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The amount of delay, measured in seconds, between when power is provided to the Rack PDU and when the Rack PDU provides basic master power to the outlets. Allowed values are: -1 - never apply power automatically. 0 - apply power immediately. 1 to 300 - delay up to 300 seconds (5 minutes). | |||||||||||||||||||||
| CrPDU2DeviceConfigLowLoadPowerThreshold | 1.3.6.1.4.1.318.1.1.26.4.1.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory User-defined low power draw alarm threshold, measured in tenths of kilowatts. Models that do not support this feature will respond to this OID with a value of -1. | |||||||||||||||||||||
| CrPDU2DeviceConfigNearOverloadPowerThreshold | 1.3.6.1.4.1.318.1.1.26.4.1.1.8 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory User-defined near power overload threshold, measured in tenths of kilowatts. Models that do not support this feature will respond to this OID with a value of -1. | |||||||||||||||||||||
| CrPDU2DeviceConfigOverloadPowerThreshold | 1.3.6.1.4.1.318.1.1.26.4.1.1.9 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory User-defined power overload threshold, measured in tenths of kilowatts. Models that do not support this feature will respond to this OID with a value of -1. | |||||||||||||||||||||
| CrPDU2DeviceConfigDevicePeakPowerReset | 1.3.6.1.4.1.318.1.1.26.4.1.1.10 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Setting this OID to reset (2) will cause the existing peak power value to be replaced by the current load power value. Getting this OID will do nothing and return the noOperation(1) value. Models that do not support this feature will respond to this OID with a value of not supported (3). Attempts to set this OID in these models will fail.
| |||||||||||||||||||||
| CrPDU2DeviceConfigDeviceEnergyReset | 1.3.6.1.4.1.318.1.1.26.4.1.1.11 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Setting this OID to reset (2) will cause the device energy meter value to be reset to zero. Getting this OID in models that support this feature will do nothing and return the noOperation(1) value. Models that do not support this feature will respond to this OID with a value of notSupported (3). Attempts to set this OID in these models will fail.
| |||||||||||||||||||||
| CrPDU2DeviceConfigOutletsEnergyReset | 1.3.6.1.4.1.318.1.1.26.4.1.1.12 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Setting this OID to reset (2) will cause the all outlet energy meter values to be reset to zero. Getting this OID will do nothing and return the noOperation(1) value. Models that do not support this feature will respond to this OID with a value of notSupported (3). Attempts to set this OID in these models will fail.
| |||||||||||||||||||||
| CrPDU2DeviceConfigOutletsPeakLoadReset | 1.3.6.1.4.1.318.1.1.26.4.1.1.13 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Setting this OID to reset (2) will cause the all outlet peak load values to be reset to zero. Getting this OID will do nothing and return the noOperation(1) value. Models that do not support this feature will respond to this OID with a value of notSupported (3). Attempts to set this OID in these models will fail.
| |||||||||||||||||||||
| CrPDU2DeviceConfigContact | 1.3.6.1.4.1.318.1.1.26.4.1.1.14 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory A user-defined string identifying the person to contact regarding the Rack PDU | |||||||||||||||||||||
| TrPDU2DevicePropertiesTable | 1.3.6.1.4.1.318.1.1.26.4.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A table of Rack PDU properties | |||||||||||||||||||||
| RrPDU2DevicePropertiesEntry | 1.3.6.1.4.1.318.1.1.26.4.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory Properties of the Rack PDU being queried | |||||||||||||||||||||
| CrPDU2DevicePropertiesIndex | 1.3.6.1.4.1.318.1.1.26.4.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the Rack PDU properties table entry | |||||||||||||||||||||
| CrPDU2DevicePropertiesModule | 1.3.6.1.4.1.318.1.1.26.4.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The user-defined Rack PDU numeric ID | |||||||||||||||||||||
| CrPDU2DevicePropertiesName | 1.3.6.1.4.1.318.1.1.26.4.2.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory A user-defined string identifying the Rack PDU | |||||||||||||||||||||
| CrPDU2DevicePropertiesNumOutlets | 1.3.6.1.4.1.318.1.1.26.4.2.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The number of outlets on the Rack PDU | |||||||||||||||||||||
| CrPDU2DevicePropertiesNumSwitchedOutlets | 1.3.6.1.4.1.318.1.1.26.4.2.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The number of switched outlets on the Rack PDU | |||||||||||||||||||||
| CrPDU2DevicePropertiesNumMeteredOutlets | 1.3.6.1.4.1.318.1.1.26.4.2.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The number of metered outlets on the Rack PDU | |||||||||||||||||||||
| CrPDU2DevicePropertiesNumPhases | 1.3.6.1.4.1.318.1.1.26.4.2.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The number of phases present in the Rack PDU | |||||||||||||||||||||
| CrPDU2DevicePropertiesNumMeteredBanks | 1.3.6.1.4.1.318.1.1.26.4.2.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The number of metered banks present in the Rack PDU | |||||||||||||||||||||
| CrPDU2DevicePropertiesMaxCurrentRating | 1.3.6.1.4.1.318.1.1.26.4.2.1.9 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The maximum current rating, measured in Amps, for the Rack PDU | |||||||||||||||||||||
| CrPDU2DevicePropertiesOrientation | 1.3.6.1.4.1.318.1.1.26.4.2.1.10 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Rack PDU orientation
| |||||||||||||||||||||
| CrPDU2DevicePropertiesOutletLayout | 1.3.6.1.4.1.318.1.1.26.4.2.1.11 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Getting this OID will return outlet layout for the device. seqPhaseToNeutral(1) indicates outlet layout as follows: 1:1-N,2:2-N,3:3-N,4:1-N,5:2-N,... or for single phase SKUs, all outlets 1-N seqPhaseToPhase(2) indicates outlet layout as follows: 1:1-2,2:2-3,3:3-1,4:1-2,5:2-3,... seqPhToNeu21PhToPh(3) indicates outlet layout as follows: 1:1-N,2:2-N...21:3-N,22:1-2,23:2-3,24:3-1,... seqPhToPhGrouped(4) indicates outlet layout as follows: For AP8xxx SKU's Group 1:1-2, Group 2:2-3, Group 3:3-1. seqPhToNGrouped(5) indicates outlet layout as follows: This unit has 3 outlet groups. Group 1:1-N, Group 2:2-N, Group 3:3-N. seqPToN1516PToPGrouped(6) indicates outlet layout as follows: This unit has 4 outlet groups. Group 1 (Outlets 1-14):1-2, Group 2 (Outlets 15-16):1-N, Group 3:2-3, Group 4:3-1. seqPhToPh2xGrouped(7) indicates outlet layout as follows: This unit has 6 outlet groups. Group 1:1-2, Group 2:1-2, Group 3:2-3, Group 4:2-3, Group 5:3-1, Group 6:3-1. seqPhToN2xGrouped(8) indicates outlet layout as follows: This unit has 6 outlet groups. Group 1:1-N, Group 2:1-N, Group 3:2-N, Group 4:2-N, Group 5:3-N, Group 6:3-N. seqNotApplicable(9): Outlet layout does not affect any of the user interfaces for AP88XX SKUs. These SKUs may report seqNotApplicable(9) if there is not an exact outlet layout match available. seqPhToNPhToPhPhToN(10) indicates outlet layout as follows: Group 1:1-N, Group 2:1-2, Group 3:2-N. Only AP7xxx, AP8xxx SKUs support this feature. Product which does not support this feature will respond with -1
| |||||||||||||||||||||
| CrPDU2DevicePropertiesMaxPhaseCurrentRating | 1.3.6.1.4.1.318.1.1.26.4.2.1.12 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The maximum current rating, measured in Amps, for the Rack PDU | |||||||||||||||||||||
| CrPDU2DevicePropertiesDevicePowerRating | 1.3.6.1.4.1.318.1.1.26.4.2.1.13 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The maximum power rating, measured in tenths of kilowatts, for the Rack PDU | |||||||||||||||||||||
| TrPDU2DeviceStatusTable | 1.3.6.1.4.1.318.1.1.26.4.3 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A table of Rack PDU status information | |||||||||||||||||||||
| RrPDU2DeviceStatusEntry | 1.3.6.1.4.1.318.1.1.26.4.3.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory Status information from the Rack PDU being queried | |||||||||||||||||||||
| CrPDU2DeviceStatusIndex | 1.3.6.1.4.1.318.1.1.26.4.3.1.1 | INTEGER | RO | mandatory | 1 | ||||||||||||||||
column · INTEGER · read-only · mandatory The index to the Rack PDU status table entry Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDU2DeviceStatusModule | 1.3.6.1.4.1.318.1.1.26.4.3.1.2 | INTEGER | RO | mandatory | 1 | ||||||||||||||||
column · INTEGER · read-only · mandatory The user-defined Rack PDU numeric ID Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDU2DeviceStatusName | 1.3.6.1.4.1.318.1.1.26.4.3.1.3 | DisplayString | RO | mandatory | alamo | ||||||||||||||||
column · DisplayString · read-only · mandatory A user-defined string identifying the Rack PDU Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDU2DeviceStatusLoadState | 1.3.6.1.4.1.318.1.1.26.4.3.1.4 | INTEGER | RO | mandatory | notsupported(5) | ||||||||||||||||
column · INTEGER · read-only · mandatory Indicates the present load status of the Rack PDU. Models that do not support this feature will respond to this OID with a value of notsupported (5).
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDU2DeviceStatusPower | 1.3.6.1.4.1.318.1.1.26.4.3.1.5 | INTEGER | RO | mandatory | -1 | ||||||||||||||||
column · INTEGER · read-only · mandatory The power consumption of the Rack PDU load in hundredths of kilowatts. Models that do not support this feature will respond to this OID with a value of -1. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDU2DeviceStatusPeakPower | 1.3.6.1.4.1.318.1.1.26.4.3.1.6 | INTEGER | RO | mandatory | -1 | ||||||||||||||||
column · INTEGER · read-only · mandatory The peak power consumption of the Rack PDU load in hundredths of kilowatts. Models that do not support this feature will respond to this OID with a value of -1. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDU2DeviceStatusPeakPowerTimestamp | 1.3.6.1.4.1.318.1.1.26.4.3.1.7 | DisplayString | RO | mandatory | notsupported | ||||||||||||||||
column · DisplayString · read-only · mandatory Indicates the date and time that peak power consumption occurred. Models that do not support this feature will respond to this OID with string 'notsupported'. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDU2DeviceStatusPeakPowerStartTime | 1.3.6.1.4.1.318.1.1.26.4.3.1.8 | DisplayString | RO | mandatory | notsupported | ||||||||||||||||
column · DisplayString · read-only · mandatory Indicates the date and time of the last device peak power reset. Models that do not support this feature will respond to this OID with string 'notsupported'. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDU2DeviceStatusEnergy | 1.3.6.1.4.1.318.1.1.26.4.3.1.9 | INTEGER | RO | mandatory | -1 | ||||||||||||||||
column · INTEGER · read-only · mandatory A user resettable energy meter measuring Rack PDU load energy consumption in tenths of kilowatt-hours. Models that do not support this feature will respond to this OID with a value of -1. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDU2DeviceStatusEnergyStartTime | 1.3.6.1.4.1.318.1.1.26.4.3.1.10 | DisplayString | RO | mandatory | notsupported | ||||||||||||||||
column · DisplayString · read-only · mandatory Indicates the date and time of the last device energy meter reset. Models that do not support this feature will respond to this OID with string 'notsupported'. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDU2DeviceStatusCommandPending | 1.3.6.1.4.1.318.1.1.26.4.3.1.11 | INTEGER | RO | mandatory | noCommandPending(2) | ||||||||||||||||
column · INTEGER · read-only · mandatory Indicates whether or not the device is processing a pending command. If the commandPendingUnknown (3) value is returned, all devices powered by the Rack PDU should be shut down. The Rack PDU's power should then be cycled to clear this condition.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDU2DeviceStatusPowerSupplyAlarm | 1.3.6.1.4.1.318.1.1.26.4.3.1.12 | INTEGER | RO | mandatory | normal(1) | ||||||||||||||||
column · INTEGER · read-only · mandatory Indicates a power supply alarm is active when value equals alarm (2)
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDU2DeviceStatusPowerSupply1Status | 1.3.6.1.4.1.318.1.1.26.4.3.1.13 | INTEGER | RO | mandatory | normal(1) | ||||||||||||||||
column · INTEGER · read-only · mandatory Indicates whether or not an alarm is active in Power Supply 1
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDU2DeviceStatusPowerSupply2Status | 1.3.6.1.4.1.318.1.1.26.4.3.1.14 | INTEGER | RO | mandatory | normal(1) | ||||||||||||||||
column · INTEGER · read-only · mandatory Indicates whether or not an alarm is active in Power Supply 2
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDU2DeviceStatusOutletsEnergyStartTime | 1.3.6.1.4.1.318.1.1.26.4.3.1.15 | DisplayString | RO | mandatory | notsupported | ||||||||||||||||
column · DisplayString · read-only · mandatory Indicates the date and time of the last outlets energy meter reset. Models that do not support this feature will respond to this OID with string 'notsupported'. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDU2DeviceStatusApparentPower | 1.3.6.1.4.1.318.1.1.26.4.3.1.16 | INTEGER | RO | mandatory | -1 | ||||||||||||||||
column · INTEGER · read-only · mandatory The apparent power consumption of the Rack PDU load in hundredths of kiloVoltAmps (kVA). Models that do not support this feature will respond to this OID with a value of -1. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDU2DeviceStatusPowerFactor | 1.3.6.1.4.1.318.1.1.26.4.3.1.17 | INTEGER | RO | mandatory | -1 | ||||||||||||||||
column · INTEGER · read-only · mandatory The power factor of the Rack PDU load in hundredths. Models that do not support this feature will respond to this OID with a value of -1. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDU2DeviceStatusNPSType | 1.3.6.1.4.1.318.1.1.26.4.3.1.18 | INTEGER | RO | mandatory | notNPS(1) | ||||||||||||||||
column · INTEGER · read-only · mandatory The device NPS status: notNPS (1) indicates the Rack PDU is not in an NPS group. host (2) indicates the Rack PDU has been designated as a host in an NPS group. Only one Rack PDU in an NPS group is allowed to be the host. guest (3) indicates the Rack PDU has been designated as a guest in an NPS group.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| TrPDU2DeviceControlTable | 1.3.6.1.4.1.318.1.1.26.4.4 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A table of Rack PDU control data | |||||||||||||||||||||
| RrPDU2DeviceControlEntry | 1.3.6.1.4.1.318.1.1.26.4.4.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory Control data from Rack PDU being queried | |||||||||||||||||||||
| CrPDU2DeviceControlIndex | 1.3.6.1.4.1.318.1.1.26.4.4.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the Rack PDU control table entry | |||||||||||||||||||||
| CrPDU2DeviceControlModule | 1.3.6.1.4.1.318.1.1.26.4.4.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The user-defined Rack PDU numeric ID | |||||||||||||||||||||
| CrPDU2DeviceControlName | 1.3.6.1.4.1.318.1.1.26.4.4.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory A user-defined string identifying the Rack PDU | |||||||||||||||||||||
| CrPDU2DeviceControlCommand | 1.3.6.1.4.1.318.1.1.26.4.4.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Setting this OID to immediateAllOn (1) will turn all outlets on immediately. Setting this OID to delayedAllOn (2) will turn all outlets on as defined by each outlet's rPDU2OutletSwitchedConfigPowerOnTime OID value. Setting this OID to immediateAllOff (3) will turn all outlets off immediately. Setting this OID to immediateAllReboot (4) will cause an immediateAllOff command to be performed. Once all outlets are off, the Switched Rack PDU will then delay the rPDU2OutletSwitchedConfigRebootDuration OID time, and then perform an immediateAllOn command. Setting this OID to delayedAllReboot (5) will cause a delayedAllOff command to be performed. Once all outlets are off, the Switched Rack PDU will then delay the largest rPDU2OutletSwitchedConfigRebootDuration OID time, and then perform a delayedAllOn command. Setting this OID to noCommandAll (6) will have no effect. Setting this OID to delayedAllOff (7) will turn all outlets off as defined by each outlet's rPDU2OutletSwitchedConfigPowerOffTime OID value. Setting this OID to cancelAllPendingCommands (8) will cause all pending commands on the Switched Rack PDU to be cancelled. Getting this OID will return the noCommandAll (6) value.
| |||||||||||||||||||||
| SrPDU2PhaseTableSize | 1.3.6.1.4.1.318.1.1.26.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of connected Rack PDU phases | |||||||||||||||||||||
| NrPDU2Phase | 1.3.6.1.4.1.318.1.1.26.6 | ||||||||||||||||||||
| TrPDU2PhaseConfigTable | 1.3.6.1.4.1.318.1.1.26.6.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A table of Rack PDU phase configuration data | |||||||||||||||||||||
| RrPDU2PhaseConfigEntry | 1.3.6.1.4.1.318.1.1.26.6.1.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory Configuration data from currently queried Rack PDU phase | |||||||||||||||||||||
| CrPDU2PhaseConfigIndex | 1.3.6.1.4.1.318.1.1.26.6.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the Rack PDU phase configuration table entry | |||||||||||||||||||||
| CrPDU2PhaseConfigModule | 1.3.6.1.4.1.318.1.1.26.6.1.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The user-defined Rack PDU numeric ID | |||||||||||||||||||||
| CrPDU2PhaseConfigNumber | 1.3.6.1.4.1.318.1.1.26.6.1.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The numeric phase ID | |||||||||||||||||||||
| CrPDU2PhaseConfigOverloadRestriction | 1.3.6.1.4.1.318.1.1.26.6.1.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory This OID controls the behavior of a Switched Rack PDU phase when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will always allow the outlets on the corresponding phase to turn on. Setting this OID to restrictOnNearOverload (2) will not allow outlets on the corresponding phase to turn on if the rPDULoadConfigNearOverloadThreshold OID is exceeded. Setting this OID to restrictOnOverload (3) will not allow outlets on the corresponding phase to turn on if the rPDULoadConfigOverloadThreshold OID is exceeded. Models that do not support this feature will respond to this OID with a value of notSupported (4). Attempts to set this OID in these models will fail.
| |||||||||||||||||||||
| CrPDU2PhaseConfigLowLoadCurrentThreshold | 1.3.6.1.4.1.318.1.1.26.6.1.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory User-defined low load phase current threshold in Amps | |||||||||||||||||||||
| CrPDU2PhaseConfigNearOverloadCurrentThreshold | 1.3.6.1.4.1.318.1.1.26.6.1.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory User-defined near phase overload warning threshold in Amps | |||||||||||||||||||||
| CrPDU2PhaseConfigOverloadCurrentThreshold | 1.3.6.1.4.1.318.1.1.26.6.1.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory User-defined phase overload current threshold in Amps | |||||||||||||||||||||
| CrPDU2PhaseConfigPhasePeakCurrentReset | 1.3.6.1.4.1.318.1.1.26.6.1.1.8 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Setting this OID to reset (2) will cause the existing peak current value to be replaced by the present load current value. Getting this OID will do nothing and return the noOperation(1) value.
| |||||||||||||||||||||
| TrPDU2PhasePropertiesTable | 1.3.6.1.4.1.318.1.1.26.6.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A table of Rack PDU phase properties | |||||||||||||||||||||
| RrPDU2PhasePropertiesEntry | 1.3.6.1.4.1.318.1.1.26.6.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory Properties of the currently queried Rack PDU phase | |||||||||||||||||||||
| CrPDU2PhasePropertiesIndex | 1.3.6.1.4.1.318.1.1.26.6.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the Rack PDU phase properties table entry | |||||||||||||||||||||
| CrPDU2PhasePropertiesModule | 1.3.6.1.4.1.318.1.1.26.6.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The user-defined Rack PDU numeric ID | |||||||||||||||||||||
| CrPDU2PhasePropertiesNumber | 1.3.6.1.4.1.318.1.1.26.6.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The numeric phase ID | |||||||||||||||||||||
| TrPDU2PhaseStatusTable | 1.3.6.1.4.1.318.1.1.26.6.3 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A table of Rack PDU phase status data | |||||||||||||||||||||
| RrPDU2PhaseStatusEntry | 1.3.6.1.4.1.318.1.1.26.6.3.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory Status data from currently queried Rack PDU phase | |||||||||||||||||||||
| CrPDU2PhaseStatusIndex | 1.3.6.1.4.1.318.1.1.26.6.3.1.1 | INTEGER | RO | mandatory | 1 | ||||||||||||||||
column · INTEGER · read-only · mandatory The index to the Rack PDU phase status table entry Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDU2PhaseStatusModule | 1.3.6.1.4.1.318.1.1.26.6.3.1.2 | INTEGER | RO | mandatory | 1 | ||||||||||||||||
column · INTEGER · read-only · mandatory The user-defined Rack PDU numeric ID Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDU2PhaseStatusNumber | 1.3.6.1.4.1.318.1.1.26.6.3.1.3 | INTEGER | RO | mandatory | 1 | ||||||||||||||||
column · INTEGER · read-only · mandatory The numeric phase ID Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDU2PhaseStatusLoadState | 1.3.6.1.4.1.318.1.1.26.6.3.1.4 | INTEGER | RO | mandatory | normal(2) | ||||||||||||||||
column · INTEGER · read-only · mandatory Indicates the present load status of the Rack PDU phase being queried
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDU2PhaseStatusCurrent | 1.3.6.1.4.1.318.1.1.26.6.3.1.5 | INTEGER | RO | mandatory | 27 | ||||||||||||||||
column · INTEGER · read-only · mandatory Indicates the current draw, in tenths of Amps, of the load on the Rack PDU phase being queried Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDU2PhaseStatusVoltage | 1.3.6.1.4.1.318.1.1.26.6.3.1.6 | INTEGER | RO | mandatory | -1 | ||||||||||||||||
column · INTEGER · read-only · mandatory Indicates the Voltage, in Volts, of the Rack PDU phase being queried. Models that do not support this feature will respond to this OID with a value of -1. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDU2PhaseStatusPower | 1.3.6.1.4.1.318.1.1.26.6.3.1.7 | INTEGER | RO | mandatory | -1 | ||||||||||||||||
column · INTEGER · read-only · mandatory Indicates the load power, in hundredths of kilowatts (kW), consumed on the Rack PDU phase being queried. Models that do not support this feature will respond to this OID with a value of -1. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDU2PhaseStatusApparentPower | 1.3.6.1.4.1.318.1.1.26.6.3.1.8 | INTEGER | RO | mandatory | -1 | ||||||||||||||||
column · INTEGER · read-only · mandatory Indicates the load apparent power, in hundredths of kiloVoltAmps (kVA), consumed on the Rack PDU phase being queried. Models that do not support this feature will respond to this OID with a value of -1. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDU2PhaseStatusPowerFactor | 1.3.6.1.4.1.318.1.1.26.6.3.1.9 | INTEGER | RO | mandatory | -1 | ||||||||||||||||
column · INTEGER · read-only · mandatory Indicates the load power factor, in hundredths, of the Rack PDU phase being queried. Models that do not support this feature will respond to this OID with a value of -1. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDU2PhaseStatusPeakCurrent | 1.3.6.1.4.1.318.1.1.26.6.3.1.10 | INTEGER | RO | mandatory | 58 | ||||||||||||||||
column · INTEGER · read-only · mandatory The peak current of the Rack PDU phase load in tenths of Amps Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDU2PhaseStatusPeakCurrentTimestamp | 1.3.6.1.4.1.318.1.1.26.6.3.1.11 | DisplayString | RO | mandatory | 07/11/2023 19:56:04 | ||||||||||||||||
column · DisplayString · read-only · mandatory Indicates the date and time that the peak current occurred Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDU2PhaseStatusPeakCurrentStartTime | 1.3.6.1.4.1.318.1.1.26.6.3.1.12 | DisplayString | RO | mandatory | 05/20/2021 02:25:08 | ||||||||||||||||
column · DisplayString · read-only · mandatory Indicates the date and time of the last phase peak current reset Example values from LibreNMS test devices
| |||||||||||||||||||||
| SrPDU2BankTableSize | 1.3.6.1.4.1.318.1.1.26.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of connected Rack PDU banks | |||||||||||||||||||||
| NrPDU2Bank | 1.3.6.1.4.1.318.1.1.26.8 | ||||||||||||||||||||
| TrPDU2BankConfigTable | 1.3.6.1.4.1.318.1.1.26.8.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A table of Rack PDU bank configuration data | |||||||||||||||||||||
| RrPDU2BankConfigEntry | 1.3.6.1.4.1.318.1.1.26.8.1.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory Configuration data from currently queried Rack PDU bank
| |||||||||||||||||||||
| CrPDU2BankConfigIndex | 1.3.6.1.4.1.318.1.1.26.8.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the Rack PDU bank configuration table entry | |||||||||||||||||||||
| CrPDU2BankConfigModule | 1.3.6.1.4.1.318.1.1.26.8.1.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The user-defined Rack PDU numeric ID | |||||||||||||||||||||
| CrPDU2BankConfigNumber | 1.3.6.1.4.1.318.1.1.26.8.1.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The numeric bank ID | |||||||||||||||||||||
| CrPDU2BankConfigOverloadRestriction | 1.3.6.1.4.1.318.1.1.26.8.1.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory This OID controls the behavior of a Switched Rack PDU bank when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will always allow the outlets on the corresponding bank to turn on. Setting this OID to restrictOnNearOverload (2) will not allow outlets on the corresponding bank to turn on if the rPDU2BankConfigNearOverloadCurrentThreshold OID is exceeded. Setting this OID to restrictOnOverload (3) will not allow outlets on the corresponding bank to turn on if the rPDU2BankConfigOverloadCurrentThreshold OID is exceeded. Models that do not support this feature will respond to this OID with a value of notSupported (4). Attempts to set this OID in these models will fail.
| |||||||||||||||||||||
| CrPDU2BankConfigLowLoadCurrentThreshold | 1.3.6.1.4.1.318.1.1.26.8.1.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory User-defined low load bank current threshold in Amps | |||||||||||||||||||||
| CrPDU2BankConfigNearOverloadCurrentThreshold | 1.3.6.1.4.1.318.1.1.26.8.1.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory User-defined near bank overload current warning threshold in Amps | |||||||||||||||||||||
| CrPDU2BankConfigOverloadCurrentThreshold | 1.3.6.1.4.1.318.1.1.26.8.1.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory User-defined bank overload current threshold in Amps | |||||||||||||||||||||
| CrPDU2BankConfigBankPeakCurrentReset | 1.3.6.1.4.1.318.1.1.26.8.1.1.8 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Setting this OID to reset (2) will cause the existing peak current value to be replaced by the present load current value. Getting this OID will do nothing and return the noOperation(1) value.
| |||||||||||||||||||||
| TrPDU2BankPropertiesTable | 1.3.6.1.4.1.318.1.1.26.8.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A table of Rack PDU bank properties | |||||||||||||||||||||
| RrPDU2BankPropertiesEntry | 1.3.6.1.4.1.318.1.1.26.8.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory Properties of the currently queried Rack PDU bank | |||||||||||||||||||||
| CrPDU2BankPropertiesIndex | 1.3.6.1.4.1.318.1.1.26.8.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the Rack PDU bank properties table entry | |||||||||||||||||||||
| CrPDU2BankPropertiesModule | 1.3.6.1.4.1.318.1.1.26.8.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The user-defined Rack PDU numeric ID | |||||||||||||||||||||
| CrPDU2BankPropertiesNumber | 1.3.6.1.4.1.318.1.1.26.8.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The numeric bank ID | |||||||||||||||||||||
| CrPDU2BankPropertiesPhaseLayout | 1.3.6.1.4.1.318.1.1.26.8.2.1.4 | Rpdu2OutletPhaseLayoutType | RO | mandatory | |||||||||||||||||
column · Rpdu2OutletPhaseLayoutType · read-only · mandatory This OID describes the outlet phase connections on the referenced bank as follows: seqPhase1ToNeutral(1) indicates that bank outlets are wired from Phase 1 to Neutral. seqPhase2ToNeutral(2) indicates that bank outlets are wired from Phase 2 to Neutral. seqPhase3ToNeutral(3) indicates that bank outlets are wired from Phase 3 to Neutral. seqPhase1ToPhase2(4) indicates that bank outlets are wired from Phase 1 to Phase 2. seqPhase2ToPhase3(5) indicates that bank outlets are wired from Phase 2 to Phase 3. seqPhase3ToPhase1(6) indicates that bank outlets are wired from Phase 3 to Phase 1. | |||||||||||||||||||||
| CrPDU2BankPropertiesBreakerRating | 1.3.6.1.4.1.318.1.1.26.8.2.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory If bank circuit breakers are present on the device, this OID will return the rating of the breaker in Amps. | |||||||||||||||||||||
| TrPDU2BankStatusTable | 1.3.6.1.4.1.318.1.1.26.8.3 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A table of Rack PDU bank status data | |||||||||||||||||||||
| RrPDU2BankStatusEntry | 1.3.6.1.4.1.318.1.1.26.8.3.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory Status data from currently queried Rack PDU bank
| |||||||||||||||||||||
| CrPDU2BankStatusIndex | 1.3.6.1.4.1.318.1.1.26.8.3.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the Rack PDU bank status table entry | |||||||||||||||||||||
| CrPDU2BankStatusModule | 1.3.6.1.4.1.318.1.1.26.8.3.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The user-defined Rack PDU numeric ID | |||||||||||||||||||||
| CrPDU2BankStatusNumber | 1.3.6.1.4.1.318.1.1.26.8.3.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The numeric bank ID | |||||||||||||||||||||
| CrPDU2BankStatusLoadState | 1.3.6.1.4.1.318.1.1.26.8.3.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Indicates the present load status of the Rack PDU bank being queried
| |||||||||||||||||||||
| CrPDU2BankStatusCurrent | 1.3.6.1.4.1.318.1.1.26.8.3.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Indicates the current draw, in tenths of Amps, of the load on the Rack PDU bank being queried | |||||||||||||||||||||
| CrPDU2BankStatusPeakCurrent | 1.3.6.1.4.1.318.1.1.26.8.3.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The peak current of the Rack PDU bank load in tenths of Amps | |||||||||||||||||||||
| CrPDU2BankStatusPeakCurrentTimestamp | 1.3.6.1.4.1.318.1.1.26.8.3.1.7 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory Indicates the date and time the bank peak current occurred | |||||||||||||||||||||
| CrPDU2BankStatusPeakCurrentStartTime | 1.3.6.1.4.1.318.1.1.26.8.3.1.8 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory Indicates the date and time of the last bank peak current reset | |||||||||||||||||||||
| NrPDU2Outlet | 1.3.6.1.4.1.318.1.1.26.9 | ||||||||||||||||||||
| SrPDU2OutletSwitchedTableSize | 1.3.6.1.4.1.318.1.1.26.9.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of switched outlets on connected Rack PDUs | |||||||||||||||||||||
| NrPDU2OutletSwitched | 1.3.6.1.4.1.318.1.1.26.9.2 | ||||||||||||||||||||
| TrPDU2OutletSwitchedConfigTable | 1.3.6.1.4.1.318.1.1.26.9.2.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A table of Rack PDU switched outlet configuration data | |||||||||||||||||||||
| RrPDU2OutletSwitchedConfigEntry | 1.3.6.1.4.1.318.1.1.26.9.2.1.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory Configuration data from currently queried Rack PDU switched outlet | |||||||||||||||||||||
| CrPDU2OutletSwitchedConfigIndex | 1.3.6.1.4.1.318.1.1.26.9.2.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the Rack PDU switched outlet configuration table entry | |||||||||||||||||||||
| CrPDU2OutletSwitchedConfigModule | 1.3.6.1.4.1.318.1.1.26.9.2.1.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The user-defined Rack PDU numeric ID | |||||||||||||||||||||
| CrPDU2OutletSwitchedConfigName | 1.3.6.1.4.1.318.1.1.26.9.2.1.1.3 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The user-defined switched outlet ID string | |||||||||||||||||||||
| CrPDU2OutletSwitchedConfigNumber | 1.3.6.1.4.1.318.1.1.26.9.2.1.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The numeric switched outlet ID | |||||||||||||||||||||
| CrPDU2OutletSwitchedConfigPowerOnTime | 1.3.6.1.4.1.318.1.1.26.9.2.1.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The amount of delay, in seconds, between when power is provided to the Rack PDU and when this switched outlet starts providing power. Range -1...7200 where -1 = Never power on, 0 = immediate power on, and 1-7200 = seconds to delay. | |||||||||||||||||||||
| CrPDU2OutletSwitchedConfigPowerOffTime | 1.3.6.1.4.1.318.1.1.26.9.2.1.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The amount of time, in seconds, this outlet will delay powering off. Range -1...7200 where -1 = Never power off, 0 = immediate power off, and 1-7200 = seconds to delay. | |||||||||||||||||||||
| CrPDU2OutletSwitchedConfigRebootDuration | 1.3.6.1.4.1.318.1.1.26.9.2.1.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory After turning power off during a reboot sequence, the amount of time to wait before turning power to this outlet back on. Range 5-60 seconds delay. | |||||||||||||||||||||
| CrPDU2OutletSwitchedConfigExternalLink | 1.3.6.1.4.1.318.1.1.26.9.2.1.1.8 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory User-defined external device web link. Possible use cases could be the IP address of the external device plugged into the outlet or its manufacturer web page for convenient support such as user manuals, specifications, drivers, etc. | |||||||||||||||||||||
| TrPDU2OutletSwitchedPropertiesTable | 1.3.6.1.4.1.318.1.1.26.9.2.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A table of Rack PDU switched outlet properties | |||||||||||||||||||||
| RrPDU2OutletSwitchedPropertiesEntry | 1.3.6.1.4.1.318.1.1.26.9.2.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory Properties of the currently queried Rack PDU switched outlet | |||||||||||||||||||||
| CrPDU2OutletSwitchedPropertiesIndex | 1.3.6.1.4.1.318.1.1.26.9.2.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the Rack PDU switched outlet properties table entry | |||||||||||||||||||||
| CrPDU2OutletSwitchedPropertiesModule | 1.3.6.1.4.1.318.1.1.26.9.2.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The user-defined Rack PDU numeric ID | |||||||||||||||||||||
| CrPDU2OutletSwitchedPropertiesName | 1.3.6.1.4.1.318.1.1.26.9.2.2.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The user-defined switched outlet ID string | |||||||||||||||||||||
| CrPDU2OutletSwitchedPropertiesNumber | 1.3.6.1.4.1.318.1.1.26.9.2.2.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The numeric switched outlet ID | |||||||||||||||||||||
| CrPDU2OutletSwitchedPropertiesPhaseLayout | 1.3.6.1.4.1.318.1.1.26.9.2.2.1.5 | Rpdu2OutletPhaseLayoutType | RO | mandatory | |||||||||||||||||
column · Rpdu2OutletPhaseLayoutType · read-only · mandatory This OID describes the phase connections of the referenced outlet as follows: seqPhase1ToNeutral(1) indicates that the outlet is wired from Phase 1 to Neutral. seqPhase2ToNeutral(2) indicates that the outlet is wired from Phase 2 to Neutral. seqPhase3ToNeutral(3) indicates that the outlet is wired from Phase 3 to Neutral. seqPhase1ToPhase2(4) indicates that the outlet is wired from Phase 1 to Phase 2. seqPhase2ToPhase3(5) indicates that the outlet is wired from Phase 2 to Phase 3. seqPhase3ToPhase1(6) indicates that the outlet is wired from Phase 3 to Phase 1. | |||||||||||||||||||||
| CrPDU2OutletSwitchedPropertiesBank | 1.3.6.1.4.1.318.1.1.26.9.2.2.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The numeric bank ID | |||||||||||||||||||||
| TrPDU2OutletSwitchedStatusTable | 1.3.6.1.4.1.318.1.1.26.9.2.3 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A table of Rack PDU switched outlet status information | |||||||||||||||||||||
| RrPDU2OutletSwitchedStatusEntry | 1.3.6.1.4.1.318.1.1.26.9.2.3.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory Status information for currently queried Rack PDU switched outlet | |||||||||||||||||||||
| CrPDU2OutletSwitchedStatusIndex | 1.3.6.1.4.1.318.1.1.26.9.2.3.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the Rack PDU switched outlet status information table entry | |||||||||||||||||||||
| CrPDU2OutletSwitchedStatusModule | 1.3.6.1.4.1.318.1.1.26.9.2.3.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The user-defined Rack PDU numeric ID | |||||||||||||||||||||
| CrPDU2OutletSwitchedStatusName | 1.3.6.1.4.1.318.1.1.26.9.2.3.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The user-defined switched outlet ID string | |||||||||||||||||||||
| CrPDU2OutletSwitchedStatusNumber | 1.3.6.1.4.1.318.1.1.26.9.2.3.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The numeric switched outlet ID | |||||||||||||||||||||
| CrPDU2OutletSwitchedStatusState | 1.3.6.1.4.1.318.1.1.26.9.2.3.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Indicates the present switch state of the Rack PDU switched outlet being queried
| |||||||||||||||||||||
| CrPDU2OutletSwitchedStatusCommandPending | 1.3.6.1.4.1.318.1.1.26.9.2.3.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Indicates whether or not the device is processing a command for this outlet. If the commandPendingUnknown (3) value is returned, all devices powered by the Rack PDU should be shut down. The Rack PDU's power should then be cycled to clear this condition.
| |||||||||||||||||||||
| CrPDU2OutletSwitchedStatusExternalLink | 1.3.6.1.4.1.318.1.1.26.9.2.3.1.7 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory Each RPDU outlet can have its own external web URL link. This can be configured in the rPDU2OutletSwitchedConfigExternalLink OID. When this link is clicked in the web interface, the linked URL will open in the web browser. | |||||||||||||||||||||
| TrPDU2OutletSwitchedControlTable | 1.3.6.1.4.1.318.1.1.26.9.2.4 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A table of Rack PDU switched outlet control data | |||||||||||||||||||||
| RrPDU2OutletSwitchedControlEntry | 1.3.6.1.4.1.318.1.1.26.9.2.4.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory Control data for currently queried Rack PDU switched outlet | |||||||||||||||||||||
| CrPDU2OutletSwitchedControlIndex | 1.3.6.1.4.1.318.1.1.26.9.2.4.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the Rack PDU switched outlet control data table entry | |||||||||||||||||||||
| CrPDU2OutletSwitchedControlModule | 1.3.6.1.4.1.318.1.1.26.9.2.4.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The user-defined Rack PDU numeric ID | |||||||||||||||||||||
| CrPDU2OutletSwitchedControlName | 1.3.6.1.4.1.318.1.1.26.9.2.4.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The user-defined switched outlet ID string | |||||||||||||||||||||
| CrPDU2OutletSwitchedControlNumber | 1.3.6.1.4.1.318.1.1.26.9.2.4.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The numeric switched outlet ID | |||||||||||||||||||||
| CrPDU2OutletSwitchedControlCommand | 1.3.6.1.4.1.318.1.1.26.9.2.4.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Getting this variable will return the outlet state. If the outlet is on, the immediateOn (1) value will be returned. If the outlet is off, the immediateOff (2) value will be returned. If the state of the outlet cannot be determined, the outletUnknown (4) value will be returned. If the outletUnknown condition should occur, all devices powered by the PDU should be shut down. The PDU's power should then be cycled to clear this condition. Setting this variable to immediateOn (1) will immediately turn the outlet on. Setting this variable to immediateOff (2) will immediately turn the outlet off. Setting this variable to immediateReboot (3) will cause the Switched Rack PDU to perform an immediateOff command, wait the rPDU2OutletSwitchedConfigRebootDuration OID time, and then perform an immediateOn command. Setting this variable to delayedOn (5) will turn the outlet on after the rPDU2OutletSwitchedConfigPowerOnTime OID time has elapsed. Setting this variable to delayedOff (6) will turn the outlet off after the rPDU2OutletSwitchedConfigPowerOffTime OID time has elapsed. Setting this variable to delayedReboot (7) will cause the Switched Rack PDU to perform a delayedOff command, wait the rPDU2OutletSwitchedConfigRebootDuration OID time, and then perform a delayedOn command. Setting this variable to cancelPendingCommand (8) will cause any pending command to this outlet to be cancelled.
| |||||||||||||||||||||
| SrPDU2OutletMeteredTableSize | 1.3.6.1.4.1.318.1.1.26.9.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of metered outlets on connect Rack PDUs | |||||||||||||||||||||
| NrPDU2OutletMetered | 1.3.6.1.4.1.318.1.1.26.9.4 | ||||||||||||||||||||
| TrPDU2OutletMeteredConfigTable | 1.3.6.1.4.1.318.1.1.26.9.4.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A table of Rack PDU metered outlet configuration data | |||||||||||||||||||||
| RrPDU2OutletMeteredConfigEntry | 1.3.6.1.4.1.318.1.1.26.9.4.1.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory Configuration data from currently queried Rack PDU metered outlet | |||||||||||||||||||||
| CrPDU2OutletMeteredConfigIndex | 1.3.6.1.4.1.318.1.1.26.9.4.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the Rack PDU metered outlet configuration table entry | |||||||||||||||||||||
| CrPDU2OutletMeteredConfigModule | 1.3.6.1.4.1.318.1.1.26.9.4.1.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The user-defined Rack PDU numeric ID | |||||||||||||||||||||
| CrPDU2OutletMeteredConfigName | 1.3.6.1.4.1.318.1.1.26.9.4.1.1.3 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The user-defined metered outlet ID string | |||||||||||||||||||||
| CrPDU2OutletMeteredConfigNumber | 1.3.6.1.4.1.318.1.1.26.9.4.1.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The numeric switched outlet ID | |||||||||||||||||||||
| CrPDU2OutletMeteredConfigLowLoadCurrentThreshold | 1.3.6.1.4.1.318.1.1.26.9.4.1.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory User-defined low load outlet current threshold in Watts | |||||||||||||||||||||
| CrPDU2OutletMeteredConfigNearOverloadCurrentThreshold | 1.3.6.1.4.1.318.1.1.26.9.4.1.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory User-defined near outlet overload warning threshold in Watts | |||||||||||||||||||||
| CrPDU2OutletMeteredConfigOverloadCurrentThreshold | 1.3.6.1.4.1.318.1.1.26.9.4.1.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory User-defined outlet overload current threshold in Watts | |||||||||||||||||||||
| CrPDU2OutletMeteredConfigExternalLink | 1.3.6.1.4.1.318.1.1.26.9.4.1.1.8 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory User-defined external device web link. Possible use cases could be the IP address of the external device plugged into the outlet or its manufacturer web page for convenient support such as user manuals, specifications, drivers, etc. | |||||||||||||||||||||
| TrPDU2OutletMeteredPropertiesTable | 1.3.6.1.4.1.318.1.1.26.9.4.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A table of Rack PDU metered outlet properties | |||||||||||||||||||||
| RrPDU2OutletMeteredPropertiesEntry | 1.3.6.1.4.1.318.1.1.26.9.4.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory Properties of currently queried Rack PDU metered outlet | |||||||||||||||||||||
| CrPDU2OutletMeteredPropertiesIndex | 1.3.6.1.4.1.318.1.1.26.9.4.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the Rack PDU metered properties table entry | |||||||||||||||||||||
| CrPDU2OutletMeteredPropertiesModule | 1.3.6.1.4.1.318.1.1.26.9.4.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The user-defined Rack PDU numeric ID | |||||||||||||||||||||
| CrPDU2OutletMeteredPropertiesName | 1.3.6.1.4.1.318.1.1.26.9.4.2.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The user-defined metered outlet ID string | |||||||||||||||||||||
| CrPDU2OutletMeteredPropertiesNumber | 1.3.6.1.4.1.318.1.1.26.9.4.2.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The numeric metered outlet ID | |||||||||||||||||||||
| CrPDU2OutletMeteredPropertiesLayout | 1.3.6.1.4.1.318.1.1.26.9.4.2.1.5 | Rpdu2OutletPhaseLayoutType | RO | mandatory | |||||||||||||||||
column · Rpdu2OutletPhaseLayoutType · read-only · mandatory This OID describes the phase connections of the referenced outlet as follows: seqPhase1ToNeutral(1) indicates that the outlet is wired from Phase 1 to Neutral. seqPhase2ToNeutral(2) indicates that the outlet is wired from Phase 2 to Neutral. seqPhase3ToNeutral(3) indicates that the outlet is wired from Phase 3 to Neutral. seqPhase1ToPhase2(4) indicates that the outlet is wired from Phase 1 to Phase 2. seqPhase2ToPhase3(5) indicates that the outlet is wired from Phase 2 to Phase 3. seqPhase3ToPhase1(6) indicates that the outlet is wired from Phase 3 to Phase 1. | |||||||||||||||||||||
| CrPDU2OutletMeteredPropertiesPowerRating | 1.3.6.1.4.1.318.1.1.26.9.4.2.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Maximum power rating of Rack PDU metered outlet | |||||||||||||||||||||
| CrPDU2OutletMeteredPropertiesBank | 1.3.6.1.4.1.318.1.1.26.9.4.2.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This outlet's numeric bank ID | |||||||||||||||||||||
| TrPDU2OutletMeteredStatusTable | 1.3.6.1.4.1.318.1.1.26.9.4.3 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A table of Rack PDU metered outlet status data | |||||||||||||||||||||
| RrPDU2OutletMeteredStatusEntry | 1.3.6.1.4.1.318.1.1.26.9.4.3.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory Status data from currently queried Rack PDU metered outlet | |||||||||||||||||||||
| CrPDU2OutletMeteredStatusIndex | 1.3.6.1.4.1.318.1.1.26.9.4.3.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the Rack PDU metered status table entry | |||||||||||||||||||||
| CrPDU2OutletMeteredStatusModule | 1.3.6.1.4.1.318.1.1.26.9.4.3.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The user-defined Rack PDU numeric ID | |||||||||||||||||||||
| CrPDU2OutletMeteredStatusName | 1.3.6.1.4.1.318.1.1.26.9.4.3.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The user-defined metered outlet ID string | |||||||||||||||||||||
| CrPDU2OutletMeteredStatusNumber | 1.3.6.1.4.1.318.1.1.26.9.4.3.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The numeric metered outlet ID | |||||||||||||||||||||
| CrPDU2OutletMeteredStatusState | 1.3.6.1.4.1.318.1.1.26.9.4.3.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Indicates the present load status of the Rack PDU metered outlet being queried
| |||||||||||||||||||||
| CrPDU2OutletMeteredStatusCurrent | 1.3.6.1.4.1.318.1.1.26.9.4.3.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Indicates the current draw, in tenths of Amps, of the load on the Rack PDU outlet being queried | |||||||||||||||||||||
| CrPDU2OutletMeteredStatusPower | 1.3.6.1.4.1.318.1.1.26.9.4.3.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Indicates the power draw of the load on the Rack PDU outlet being queried | |||||||||||||||||||||
| CrPDU2OutletMeteredStatusPeakPower | 1.3.6.1.4.1.318.1.1.26.9.4.3.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Indicates the peak power load draw on the Rack PDU outlet being queried | |||||||||||||||||||||
| CrPDU2OutletMeteredStatusPeakPowerTimestamp | 1.3.6.1.4.1.318.1.1.26.9.4.3.1.9 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory Indicates the date and time that this metered outlet's peak power consumption occurred | |||||||||||||||||||||
| CrPDU2OutletMeteredStatusPeakPowerStartTime | 1.3.6.1.4.1.318.1.1.26.9.4.3.1.10 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory Indicates the start date and time that this metered outlet began recording peak power observations | |||||||||||||||||||||
| CrPDU2OutletMeteredStatusEnergy | 1.3.6.1.4.1.318.1.1.26.9.4.3.1.11 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory A user resettable energy meter measuring Rack PDU load energy consumption in tenths of kilowatt-hours | |||||||||||||||||||||
| CrPDU2OutletMeteredStatusReceptacleType | 1.3.6.1.4.1.318.1.1.26.9.4.3.1.12 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory Indicates receptacle type for the outlet. | |||||||||||||||||||||
| CrPDU2OutletMeteredStatusExternalLink | 1.3.6.1.4.1.318.1.1.26.9.4.3.1.13 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory Each RPDU outlet can have its own external web URL link. This can be configured in the rPDU2OutletMeteredConfigExternalLink OID. When this link is clicked in the web interface, the linked URL will open in the web browser. | |||||||||||||||||||||
| NrPDU2Sensor | 1.3.6.1.4.1.318.1.1.26.10 | ||||||||||||||||||||
| SrPDU2SensorTempHumidityTableSize | 1.3.6.1.4.1.318.1.1.26.10.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of connected temperature-humidity sensors | |||||||||||||||||||||
| NrPDU2SensorTempHumidity | 1.3.6.1.4.1.318.1.1.26.10.2 | ||||||||||||||||||||
| TrPDU2SensorTempHumidityConfigTable | 1.3.6.1.4.1.318.1.1.26.10.2.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A table of temperature-humidity sensor configuration data | |||||||||||||||||||||
| RrPDU2SensorTempHumidityConfigEntry | 1.3.6.1.4.1.318.1.1.26.10.2.1.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory Configuration data from temperature-humidity sensor being queried | |||||||||||||||||||||
| CrPDU2SensorTempHumidityConfigIndex | 1.3.6.1.4.1.318.1.1.26.10.2.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the temperature-humidity sensor configuration data table entry | |||||||||||||||||||||
| CrPDU2SensorTempHumidityConfigModule | 1.3.6.1.4.1.318.1.1.26.10.2.1.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The user-defined Rack PDU numeric ID | |||||||||||||||||||||
| CrPDU2SensorTempHumidityConfigName | 1.3.6.1.4.1.318.1.1.26.10.2.1.1.3 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The user-defined temperature-humidity sensor ID string | |||||||||||||||||||||
| CrPDU2SensorTempHumidityConfigNumber | 1.3.6.1.4.1.318.1.1.26.10.2.1.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The temperature-humidity sensor numeric ID | |||||||||||||||||||||
| CrPDU2SensorTempHumidityConfigTemperatureAlarmEnable | 1.3.6.1.4.1.318.1.1.26.10.2.1.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Setting this OID enables or disables generation of sensor temperature alarm. Getting this OID returns the current value of the temperature alarm enable.
| |||||||||||||||||||||
| CrPDU2SensorTempHumidityConfigHumidityAlarmEnable | 1.3.6.1.4.1.318.1.1.26.10.2.1.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Setting this OID enables or disables generation of sensor humidity alarm. Getting this OID returns the current value of the humidity alarm enable.
| |||||||||||||||||||||
| CrPDU2SensorTempHumidityConfigTempMaxThreshF | 1.3.6.1.4.1.318.1.1.26.10.2.1.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Sensor maximum temperature alarm threshold in Fahrenheit. Attempting to set this OID to a value less than or equal to that of rPDU2SensorTempHumidityConfigTempHighThreshF will result in an error. | |||||||||||||||||||||
| CrPDU2SensorTempHumidityConfigTempHighThreshF | 1.3.6.1.4.1.318.1.1.26.10.2.1.1.8 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Sensor high temperature warning alarm threshold in Fahrenheit. Attempting to set this OID to a value greater than or equal to that of rPDU2SensorTempHumidityConfigTempMaxThreshF will result in an error. | |||||||||||||||||||||
| CrPDU2SensorTempHumidityConfigTempHysteresisF | 1.3.6.1.4.1.318.1.1.26.10.2.1.1.9 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Sensor temperature hysteresis setting in Fahrenheit | |||||||||||||||||||||
| CrPDU2SensorTempHumidityConfigTempMaxThreshC | 1.3.6.1.4.1.318.1.1.26.10.2.1.1.10 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Sensor maximum temperature alarm threshold in Celsius. Attempting to set this OID to a value less than or equal to that of rPDU2SensorTempHumidityConfigTempHighThreshC will result in an error. | |||||||||||||||||||||
| CrPDU2SensorTempHumidityConfigTempHighThreshC | 1.3.6.1.4.1.318.1.1.26.10.2.1.1.11 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Sensor high temperature warning alarm threshold in Celsius. Attempting to set this OID to a value greater than or equal to that of rPDU2SensorTempHumidityConfigTempMaxThreshC will result in an error. | |||||||||||||||||||||
| CrPDU2SensorTempHumidityConfigTempHysteresisC | 1.3.6.1.4.1.318.1.1.26.10.2.1.1.12 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Sensor temperature hysteresis setting in Celsius | |||||||||||||||||||||
| CrPDU2SensorTempHumidityConfigHumidityLowThresh | 1.3.6.1.4.1.318.1.1.26.10.2.1.1.13 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Sensor low humidity warning alarm threshold in percent relative humidity. May be 10% to 90%, but must be greater than rPDU2SensorTempHumidityConfigHumidityMinThresh. | |||||||||||||||||||||
| CrPDU2SensorTempHumidityConfigHumidityMinThresh | 1.3.6.1.4.1.318.1.1.26.10.2.1.1.14 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Sensor minimum humidity alarm threshold in percent relative humidity. May be 10% to 90%, but must be less than rPDU2SensorTempHumidityConfigHumidityLowThresh. | |||||||||||||||||||||
| CrPDU2SensorTempHumidityConfigHumidityHysteresis | 1.3.6.1.4.1.318.1.1.26.10.2.1.1.15 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Sensor humidity hysteresis setting in percent relative humidity | |||||||||||||||||||||
| CrPDU2SensorTempHumidityConfigTempPeakReset | 1.3.6.1.4.1.318.1.1.26.10.2.1.1.16 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Setting this OID to reset (2) will cause the existing peak temperature to be replaced by the present temperature reading. Getting this OID will do nothing and return the noOperation(1) value.
| |||||||||||||||||||||
| TrPDU2SensorTempHumidityStatusTable | 1.3.6.1.4.1.318.1.1.26.10.2.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A table of temperature-humidity sensor status data | |||||||||||||||||||||
| RrPDU2SensorTempHumidityStatusEntry | 1.3.6.1.4.1.318.1.1.26.10.2.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory Status information from temperature-humidity sensor being queried | |||||||||||||||||||||
| CrPDU2SensorTempHumidityStatusIndex | 1.3.6.1.4.1.318.1.1.26.10.2.2.1.1 | INTEGER | RO | mandatory | 1 | ||||||||||||||||
column · INTEGER · read-only · mandatory The index to the temperature-humidity status data table entry Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDU2SensorTempHumidityStatusModule | 1.3.6.1.4.1.318.1.1.26.10.2.2.1.2 | INTEGER | RO | mandatory | 1 | ||||||||||||||||
column · INTEGER · read-only · mandatory The user-defined Rack PDU numeric ID Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDU2SensorTempHumidityStatusName | 1.3.6.1.4.1.318.1.1.26.10.2.2.1.3 | DisplayString | RO | mandatory | | ||||||||||||||||
column · DisplayString · read-only · mandatory The user-defined temperature-humidity sensor ID string Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDU2SensorTempHumidityStatusNumber | 1.3.6.1.4.1.318.1.1.26.10.2.2.1.4 | INTEGER | RO | mandatory | 1 | ||||||||||||||||
column · INTEGER · read-only · mandatory The temperature-humidity sensor numeric ID Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDU2SensorTempHumidityStatusType | 1.3.6.1.4.1.318.1.1.26.10.2.2.1.5 | INTEGER | RO | mandatory | notInstalled(4) | ||||||||||||||||
column · INTEGER · read-only · mandatory The type of the sensor
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDU2SensorTempHumidityStatusCommStatus | 1.3.6.1.4.1.318.1.1.26.10.2.2.1.6 | INTEGER | RO | mandatory | notInstalled(1) | ||||||||||||||||
column · INTEGER · read-only · mandatory The communications status of the sensor
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDU2SensorTempHumidityStatusTempF | 1.3.6.1.4.1.318.1.1.26.10.2.2.1.7 | INTEGER | RO | mandatory | -1 | ||||||||||||||||
column · INTEGER · read-only · mandatory Sensor temperature reading in tenths of degrees Fahrenheit Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDU2SensorTempHumidityStatusTempC | 1.3.6.1.4.1.318.1.1.26.10.2.2.1.8 | INTEGER | RO | mandatory | -1 | ||||||||||||||||
column · INTEGER · read-only · mandatory Sensor temperature reading in tenths of degrees Celsius Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDU2SensorTempHumidityStatusTempStatus | 1.3.6.1.4.1.318.1.1.26.10.2.2.1.9 | INTEGER | RO | mandatory | notPresent(1) | ||||||||||||||||
column · INTEGER · read-only · mandatory This OID reports the current state of the temperature probe. A notPresent (1) response indicates that no probe is attached. A belowMin (2) response indicates that the probe is present and its measured temperature lies below the minimum threshold. A belowLow (3) response indicates that the probe is present and its measured temperature lies below the low threshold. A normal (4) response indicates that the probe is present and its measured temperature lies within all temperature thresholds. An aboveHigh (5) response indicates that the probe is present and is measuring a temperature above the high threshold. An aboveMax (6) response indicates that the probe is present and is measuring a temperature above the max threshold.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDU2SensorTempHumidityStatusRelativeHumidity | 1.3.6.1.4.1.318.1.1.26.10.2.2.1.10 | INTEGER | RO | mandatory | -1 | ||||||||||||||||
column · INTEGER · read-only · mandatory Sensor humidity reading in percent relative humidity Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDU2SensorTempHumidityStatusHumidityStatus | 1.3.6.1.4.1.318.1.1.26.10.2.2.1.11 | INTEGER | RO | mandatory | notPresent(1) | ||||||||||||||||
column · INTEGER · read-only · mandatory This OID reports the current state of the humidity probe. A notPresent (1) response indicates that no probe is attached. A belowMin (2) response indicates that the probe is present and its measured humidity lies below the minimum threshold. A belowLow (3) response indicates that the probe is present and its measured humidity lies below the low threshold. A normal (4) response indicates that the probe is present and its measured humidity lies within all humidity thresholds. An aboveHigh (5) response indicates that the probe is present and is measuring a humidity above the high threshold. An aboveMax (6) response indicates that the probe is present and is measuring a humidity above the max threshold.
Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDU2SensorTempHumidityStatusTempPeakF | 1.3.6.1.4.1.318.1.1.26.10.2.2.1.12 | INTEGER | RO | mandatory | -1 | ||||||||||||||||
column · INTEGER · read-only · mandatory Sensor peak temperature in tenths of degrees Fahrenheit Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDU2SensorTempHumidityStatusTempPeakC | 1.3.6.1.4.1.318.1.1.26.10.2.2.1.13 | INTEGER | RO | mandatory | -1 | ||||||||||||||||
column · INTEGER · read-only · mandatory Sensor peak temperature in tenths of degrees Celsius Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDU2SensorTempHumidityStatusTempPeakTimestamp | 1.3.6.1.4.1.318.1.1.26.10.2.2.1.14 | DisplayString | RO | mandatory | noTempSensorInstalled | ||||||||||||||||
column · DisplayString · read-only · mandatory Indicates the date and time that the peak temperature occurred Example values from LibreNMS test devices
| |||||||||||||||||||||
| CrPDU2SensorTempHumidityStatusTempPeakStartTime | 1.3.6.1.4.1.318.1.1.26.10.2.2.1.15 | DisplayString | RO | mandatory | noTempSensorInstalled | ||||||||||||||||
column · DisplayString · read-only · mandatory Indicates the date and time of the last temperature peak reset Example values from LibreNMS test devices
| |||||||||||||||||||||
| SrPDU2SensorDiscreteTableSize | 1.3.6.1.4.1.318.1.1.26.10.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of connected discrete sensors | |||||||||||||||||||||
| NrPDU2SensorDiscrete | 1.3.6.1.4.1.318.1.1.26.10.4 | ||||||||||||||||||||
| TrPDU2SensorDiscreteConfigTable | 1.3.6.1.4.1.318.1.1.26.10.4.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A table of discrete sensor configuration data | |||||||||||||||||||||
| RrPDU2SensorDiscreteConfigEntry | 1.3.6.1.4.1.318.1.1.26.10.4.1.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory Configuration data from discreste sensor being queried | |||||||||||||||||||||
| CrPDU2SensorDiscreteConfigIndex | 1.3.6.1.4.1.318.1.1.26.10.4.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the discrete sensor configuration data table entry | |||||||||||||||||||||
| CrPDU2SensorDiscreteConfigModule | 1.3.6.1.4.1.318.1.1.26.10.4.1.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The user-defined Rack PDU numeric ID | |||||||||||||||||||||
| CrPDU2SensorDiscreteConfigName | 1.3.6.1.4.1.318.1.1.26.10.4.1.1.3 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The user-defined discrete sensor ID string | |||||||||||||||||||||
| CrPDU2SensorDiscreteConfigNumber | 1.3.6.1.4.1.318.1.1.26.10.4.1.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The discrete sensor numeric ID | |||||||||||||||||||||
| CrPDU2SensorDiscreteConfigNormalState | 1.3.6.1.4.1.318.1.1.26.10.4.1.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Indicates the normal state of the discrete input contact
| |||||||||||||||||||||
| CrPDU2SensorDiscreteConfigAbnormalSeverity | 1.3.6.1.4.1.318.1.1.26.10.4.1.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Indicates the severity of alarm triggered by abnormal discrete input contact state
| |||||||||||||||||||||
| TrPDU2SensorDiscreteStatusTable | 1.3.6.1.4.1.318.1.1.26.10.4.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A table of discrete sensor status data | |||||||||||||||||||||
| RrPDU2SensorDiscreteStatusEntry | 1.3.6.1.4.1.318.1.1.26.10.4.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory Status information from discrete sensor being queried | |||||||||||||||||||||
| CrPDU2SensorDiscreteStatusIndex | 1.3.6.1.4.1.318.1.1.26.10.4.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the discrete sensor status data table entry | |||||||||||||||||||||
| CrPDU2SensorDiscreteStatusModule | 1.3.6.1.4.1.318.1.1.26.10.4.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The user-defined Rack PDU numeric ID | |||||||||||||||||||||
| CrPDU2SensorDiscreteStatusName | 1.3.6.1.4.1.318.1.1.26.10.4.2.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The user-defined discrete sensor ID string | |||||||||||||||||||||
| CrPDU2SensorDiscreteStatusNumber | 1.3.6.1.4.1.318.1.1.26.10.4.2.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The discrete sensor numeric ID | |||||||||||||||||||||
| CrPDU2SensorDiscreteStatusType | 1.3.6.1.4.1.318.1.1.26.10.4.2.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The type of discrete sensor currently being queried
| |||||||||||||||||||||
| CrPDU2SensorDiscreteStatusCommStatus | 1.3.6.1.4.1.318.1.1.26.10.4.2.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The communications status of the sensor
| |||||||||||||||||||||
| CrPDU2SensorDiscreteStatusCurrentState | 1.3.6.1.4.1.318.1.1.26.10.4.2.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The current open/close state of the discrete sensor
| |||||||||||||||||||||
| CrPDU2SensorDiscreteStatusAlarmState | 1.3.6.1.4.1.318.1.1.26.10.4.2.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Indicates alarm status of discrete sensor input
| |||||||||||||||||||||
| SrPDU2SensorAnalogVoltageTableSize | 1.3.6.1.4.1.318.1.1.26.10.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The maximum number of analog voltage sensors for the current hardware configuration. | |||||||||||||||||||||
| NrPDU2SensorAnalogVoltage | 1.3.6.1.4.1.318.1.1.26.10.6 | ||||||||||||||||||||
| TrPDU2SensorAnalogVoltageStatusTable | 1.3.6.1.4.1.318.1.1.26.10.6.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A table of voltage sensor status data. Not supported by rPDU series 9000 or older. | |||||||||||||||||||||
| RrPDU2SensorAnalogVoltageStatusEntry | 1.3.6.1.4.1.318.1.1.26.10.6.1.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory Status information from voltage sensor being queried | |||||||||||||||||||||
| CrPDU2SensorAnalogVoltageStatusIndex | 1.3.6.1.4.1.318.1.1.26.10.6.1.1.1 | INTEGER (0..255) | RO | mandatory | |||||||||||||||||
column · INTEGER (0..255) · read-only · mandatory The index to the voltage sensor status data table entry | |||||||||||||||||||||
| CrPDU2SensorAnalogVoltageStatusModule | 1.3.6.1.4.1.318.1.1.26.10.6.1.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The user-defined Rack PDU numeric ID | |||||||||||||||||||||
| CrPDU2SensorAnalogVoltageStatusNumber | 1.3.6.1.4.1.318.1.1.26.10.6.1.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The voltage sensor numeric ID | |||||||||||||||||||||
| CrPDU2SensorAnalogVoltageStatusName | 1.3.6.1.4.1.318.1.1.26.10.6.1.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The user-defined voltage sensor ID string | |||||||||||||||||||||
| CrPDU2SensorAnalogVoltageStatusCommStatus | 1.3.6.1.4.1.318.1.1.26.10.6.1.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The communications status of the sensor
| |||||||||||||||||||||
| CrPDU2SensorAnalogVoltageStatusHundredthVolts | 1.3.6.1.4.1.318.1.1.26.10.6.1.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Sensor voltage reading in hundredths of volts. Returns -1 for indices without voltage probes. | |||||||||||||||||||||
| CrPDU2SensorAnalogVoltageStatusThreshStatus | 1.3.6.1.4.1.318.1.1.26.10.6.1.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This OID reports the current state of the voltage probe: A notPresent (1) response indicates that no probe is attached, or that the attached probe isn't a voltage probe. A belowMin (2) response indicates that the probe is present and its measured voltage lies below the minimum threshold. A belowLow (3) response indicates that the probe is present and its measured voltage lies below the low threshold. A normal (4) response indicates that the probe is present and its measured voltage lies within all voltage thresholds. An aboveHigh (5) response indicates that the probe is present and is measuring a voltage above the high threshold. An aboveMax (6) response indicates that the probe is present and is measuring a voltage above the maximum threshold.
| |||||||||||||||||||||
| TrPDU2SensorAnalogVoltageConfigTable | 1.3.6.1.4.1.318.1.1.26.10.6.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A table of analog voltage sensor configuration data. Not supported by rPDU series 9000 or older. | |||||||||||||||||||||
| RrPDU2SensorAnalogVoltageConfigEntry | 1.3.6.1.4.1.318.1.1.26.10.6.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory Configuration data from analog voltage sensor being queried | |||||||||||||||||||||
| CrPDU2SensorAnalogVoltageConfigIndex | 1.3.6.1.4.1.318.1.1.26.10.6.2.1.1 | INTEGER (0..255) | RO | mandatory | |||||||||||||||||
column · INTEGER (0..255) · read-only · mandatory The index to the voltage sensor configuration data table entry | |||||||||||||||||||||
| CrPDU2SensorAnalogVoltageConfigModule | 1.3.6.1.4.1.318.1.1.26.10.6.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The user-defined Rack PDU numeric ID | |||||||||||||||||||||
| CrPDU2SensorAnalogVoltageConfigNumber | 1.3.6.1.4.1.318.1.1.26.10.6.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The voltage sensor numeric ID | |||||||||||||||||||||
| CrPDU2SensorAnalogVoltageConfigName | 1.3.6.1.4.1.318.1.1.26.10.6.2.1.4 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The user-defined voltage sensor ID string. | |||||||||||||||||||||
| CrPDU2SensorAnalogVoltageConfigThreshMin | 1.3.6.1.4.1.318.1.1.26.10.6.2.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Sensor minimum voltage alarm threshold in hundredths of volts. This value may be as low as zero and must be less than rPDU2SensorAnalogVoltageConfigThreshMax. Returns -1 for indices without voltage probes. | |||||||||||||||||||||
| CrPDU2SensorAnalogVoltageConfigThreshMax | 1.3.6.1.4.1.318.1.1.26.10.6.2.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Sensor minimum voltage alarm threshold in hundredths of volts. This value must be greater than rPDU2SensorAnalogVoltageConfigThreshMin and may be as high as 50. Returns -1 for indices without voltage probes. | |||||||||||||||||||||
| CrPDU2SensorAnalogVoltageConfigHysteresis | 1.3.6.1.4.1.318.1.1.26.10.6.2.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Sensor voltage hysteresis in hundredths of volts. This value may be 0 to 20. If either of the alarm thresholds are crossed, the measured voltage must recover by this amount before the alarm will be cleared. Returns -1 for indices without voltage probes. | |||||||||||||||||||||
| CrPDU2SensorAnalogVoltageConfigAlarmEnable | 1.3.6.1.4.1.318.1.1.26.10.6.2.1.8 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory This OID may be used to enable or disable voltage alarm generation. Disabling alarm generation while alarms are active clears the active alarms. Returns -1 for indices without voltage probes.
| |||||||||||||||||||||
| NrPDU2Group | 1.3.6.1.4.1.318.1.1.26.11 | ||||||||||||||||||||
| SrPDU2GroupNumberOfDevices | 1.3.6.1.4.1.318.1.1.26.11.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Getting this OID will return the number of Rack PDU devices contributing to the Network Port Sharing (NPS) group power and energy values. Queries to guest units in an NPS group are not applicable and will return 0. | |||||||||||||||||||||
| SrPDU2GroupTotalPower | 1.3.6.1.4.1.318.1.1.26.11.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Getting this OID will return the total power consumption of the Rack PDU Network Port Sharing (NPS) group devices in hundredths of kilowatts. Queries to guest units in an NPS group are not applicable and will return 0. | |||||||||||||||||||||
| SrPDU2GroupTotalEnergy | 1.3.6.1.4.1.318.1.1.26.11.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Getting this OID will return the total energy consumption of the Rack PDU Network Port Sharing (NPS) group devices in tenths of kilowatt-hours. To reset the energy meters for each of the Rack PDU devices that contribute to this value, see the rPDU2GroupEnergyReset OID. To view the start time for each of the Rack PDU device energy meters that contribute to this value, see the rPDU2DeviceStatusEnergyStartTime OID. Queries to guest units in an NPS group are not applicable and will return 0. | |||||||||||||||||||||
| SrPDU2GroupEnergyReset | 1.3.6.1.4.1.318.1.1.26.11.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Setting this OID to reset (2) will cause the device energy meter value on each device in the Rack PDU Network Port Sharing (NPS) group to be reset to zero. Each device in the Rack PDU group will also have its corresponding rPDU2DeviceStatusEnergyStartTime OID value updated. Getting this OID in models that support this feature will do nothing and return the noOperation(1) value. Models that do not support this feature, as well as guest units in an NPS group, will respond to this OID with a value of notSupported (3). Attempts to set this OID in these units will fail.
| |||||||||||||||||||||
| SrPDU2PhaseToPhaseStatusTableSize | 1.3.6.1.4.1.318.1.1.26.12 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of connected Rack PDU banks | |||||||||||||||||||||
| NrPDU2PhaseToPhase | 1.3.6.1.4.1.318.1.1.26.13 | ||||||||||||||||||||
| TrPDU2PhaseToPhaseStatusTable | 1.3.6.1.4.1.318.1.1.26.13.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A table of Rack PDU phase to phase status data. This table is only applicable to SKUs that have phase to phase outputs. | |||||||||||||||||||||
| RrPDU2PhaseToPhaseStatusEntry | 1.3.6.1.4.1.318.1.1.26.13.1.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory Status data from currently queried Rack PDU phase to phase outputs | |||||||||||||||||||||
| CrPDU2PhaseToPhaseStatusIndex | 1.3.6.1.4.1.318.1.1.26.13.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the Rack PDU phase to phase status table entry | |||||||||||||||||||||
| CrPDU2PhaseToPhaseStatusModule | 1.3.6.1.4.1.318.1.1.26.13.1.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The user-defined Rack PDU numeric ID | |||||||||||||||||||||
| CrPDU2PhaseToPhaseStatusVoltage1to2 | 1.3.6.1.4.1.318.1.1.26.13.1.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Indicates the Voltage, in Volts, of the Rack PDU phase 1 to phase 2 output being queried | |||||||||||||||||||||
| CrPDU2PhaseToPhaseStatusVoltage2to3 | 1.3.6.1.4.1.318.1.1.26.13.1.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Indicates the Voltage, in Volts, of the Rack PDU phase 2 to phase 3 output being queried | |||||||||||||||||||||
| CrPDU2PhaseToPhaseStatusVoltage3to1 | 1.3.6.1.4.1.318.1.1.26.13.1.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Indicates the Voltage, in Volts, of the Rack PDU phase 3 to phase 2 output being queried | |||||||||||||||||||||
| NrPDU2AdvBank | 1.3.6.1.4.1.318.1.1.26.14 | ||||||||||||||||||||
| TrPDU2AdvBankConfigTable | 1.3.6.1.4.1.318.1.1.26.14.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A table of Rack PDU bank configuration data | |||||||||||||||||||||
| RrPDU2AdvBankConfigEntry | 1.3.6.1.4.1.318.1.1.26.14.1.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory Configuration data from currently queried Rack PDU bank | |||||||||||||||||||||
| CrPDU2AdvBankConfigIndex | 1.3.6.1.4.1.318.1.1.26.14.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the Rack PDU bank configuration table entry | |||||||||||||||||||||
| CrPDU2AdvBankConfigModule | 1.3.6.1.4.1.318.1.1.26.14.1.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The user-defined Rack PDU numeric ID | |||||||||||||||||||||
| CrPDU2AdvBankConfigNumber | 1.3.6.1.4.1.318.1.1.26.14.1.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The numeric bank ID | |||||||||||||||||||||
| CrPDU2AdvBankConfigOverloadRestriction | 1.3.6.1.4.1.318.1.1.26.14.1.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory This OID controls the behavior of a Switched Rack PDU bank when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will always allow the outlets on the corresponding bank to turn on. Setting this OID to restrictOnNearOverload (2) will not allow outlets on the corresponding bank to turn on if the rPDU2AdvBankConfigNearOverloadCurrentThreshold OID is exceeded. Setting this OID to restrictOnOverload (3) will not allow outlets on the corresponding bank to turn on if the rPDU2AdvBankConfigOverloadCurrentThreshold OID is exceeded. Models that do not support this feature will respond to this OID with a value of notSupported (4). Attempts to set this OID in these models will fail.
| |||||||||||||||||||||
| CrPDU2AdvBankConfigLowLoadCurrentThreshold | 1.3.6.1.4.1.318.1.1.26.14.1.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory User-defined low load bank current threshold in tenths of Amps | |||||||||||||||||||||
| CrPDU2AdvBankConfigNearOverloadCurrentThreshold | 1.3.6.1.4.1.318.1.1.26.14.1.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory User-defined near bank overload current warning threshold in tenths of Amps | |||||||||||||||||||||
| CrPDU2AdvBankConfigOverloadCurrentThreshold | 1.3.6.1.4.1.318.1.1.26.14.1.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory User-defined bank overload current threshold in tenths of Amps | |||||||||||||||||||||
| CrPDU2AdvBankConfigBankPeakCurrentReset | 1.3.6.1.4.1.318.1.1.26.14.1.1.8 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Setting this OID to reset (2) will cause the existing peak current value to be replaced by the present load current value. Getting this OID will do nothing and return the noOperation(1) value.
| |||||||||||||||||||||
| NrPDU2AdvPhase | 1.3.6.1.4.1.318.1.1.26.15 | ||||||||||||||||||||
| TrPDU2AdvPhaseConfigTable | 1.3.6.1.4.1.318.1.1.26.15.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A table of Rack PDU phase configuration data | |||||||||||||||||||||
| RrPDU2AdvPhaseConfigEntry | 1.3.6.1.4.1.318.1.1.26.15.1.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory Configuration data from currently queried Rack PDU phase | |||||||||||||||||||||
| CrPDU2AdvPhaseConfigIndex | 1.3.6.1.4.1.318.1.1.26.15.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the Rack PDU phase configuration table entry | |||||||||||||||||||||
| CrPDU2AdvPhaseConfigModule | 1.3.6.1.4.1.318.1.1.26.15.1.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The user-defined Rack PDU numeric ID | |||||||||||||||||||||
| CrPDU2AdvPhaseConfigNumber | 1.3.6.1.4.1.318.1.1.26.15.1.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The numeric phase ID | |||||||||||||||||||||
| CrPDU2AdvPhaseConfigOverloadRestriction | 1.3.6.1.4.1.318.1.1.26.15.1.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory This OID controls the behavior of a Switched Rack PDU phase when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will always allow the outlets on the corresponding phase to turn on. Setting this OID to restrictOnNearOverload (2) will not allow outlets on the corresponding phase to turn on if the rPDULoadConfigNearOverloadThreshold OID is exceeded. Setting this OID to restrictOnOverload (3) will not allow outlets on the corresponding phase to turn on if the rPDULoadConfigOverloadThreshold OID is exceeded. Models that do not support this feature will respond to this OID with a value of notSupported (4). Attempts to set this OID in these models will fail.
| |||||||||||||||||||||
| CrPDU2AdvPhaseConfigLowLoadCurrentThreshold | 1.3.6.1.4.1.318.1.1.26.15.1.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory User-defined low load phase current threshold measured in tenths of Amps | |||||||||||||||||||||
| CrPDU2AdvPhaseConfigNearOverloadCurrentThreshold | 1.3.6.1.4.1.318.1.1.26.15.1.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory User-defined near phase overload warning threshold measured in tenths of Amps | |||||||||||||||||||||
| CrPDU2AdvPhaseConfigOverloadCurrentThreshold | 1.3.6.1.4.1.318.1.1.26.15.1.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory User-defined phase overload current threshold measured in tenths of Amps | |||||||||||||||||||||
| CrPDU2AdvPhaseConfigPhasePeakCurrentReset | 1.3.6.1.4.1.318.1.1.26.15.1.1.8 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Setting this OID to reset (2) will cause the existing peak current value to be replaced by the present load current value. Getting this OID will do nothing and return the noOperation(1) value.
| |||||||||||||||||||||
| Ncooling | 1.3.6.1.4.1.318.1.1.27 | ||||||||||||||||||||
| NcoolingUnit | 1.3.6.1.4.1.318.1.1.27.1 | ||||||||||||||||||||
| ScoolingUnitTableSize | 1.3.6.1.4.1.318.1.1.27.1.1 | INTEGER (0..2147483647) | RO | mandatory | 1 | ||||||||||||||||
scalar · INTEGER (0..2147483647) · read-only · mandatory The number of cooling units accessible via this agent. Example values from LibreNMS test devices
| |||||||||||||||||||||
| TcoolingUnitTable | 1.3.6.1.4.1.318.1.1.27.1.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A table of cooling unit level data. | |||||||||||||||||||||
| RcoolingUnitEntry | 1.3.6.1.4.1.318.1.1.27.1.2.1 | NA | mandatory | ||||||||||||||||||
| CcoolingUnitTableIndex | 1.3.6.1.4.1.318.1.1.27.1.2.1.1 | INTEGER (1..2147483647) | NA | mandatory | |||||||||||||||||
column · INTEGER (1..2147483647) · not-accessible · mandatory The unit reference identifier for this table and all other table entries subordinate to coolingUnits. | |||||||||||||||||||||
| NcoolingUnitAbout | 1.3.6.1.4.1.318.1.1.27.1.3 | ||||||||||||||||||||
| ScoolingUnitAboutTableSize | 1.3.6.1.4.1.318.1.1.27.1.3.1 | INTEGER (0..2147483647) | RO | mandatory | |||||||||||||||||
scalar · INTEGER (0..2147483647) · read-only · mandatory The potential number of entries available in coolingUnitAboutTable. | |||||||||||||||||||||
| TcoolingUnitAboutTable | 1.3.6.1.4.1.318.1.1.27.1.3.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A table of unit reference information. | |||||||||||||||||||||
| RcoolingUnitAboutEntry | 1.3.6.1.4.1.318.1.1.27.1.3.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An element of coolingUnitAboutTable. | |||||||||||||||||||||
| CcoolingUnitAboutTableIndex | 1.3.6.1.4.1.318.1.1.27.1.3.2.1.1 | INTEGER (1..2147483647) | NA | mandatory | |||||||||||||||||
column · INTEGER (1..2147483647) · not-accessible · mandatory The static reference identifier for each table entry. | |||||||||||||||||||||
| CcoolingUnitAboutDescription | 1.3.6.1.4.1.318.1.1.27.1.3.2.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory A text description of the information presented in coolingUnitAboutValue. | |||||||||||||||||||||
| CcoolingUnitAboutValue | 1.3.6.1.4.1.318.1.1.27.1.3.2.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The actual value of the current table entry. | |||||||||||||||||||||
| NcoolingUnitStatus | 1.3.6.1.4.1.318.1.1.27.1.4 | ||||||||||||||||||||
| NcoolingUnitStatusAnalog | 1.3.6.1.4.1.318.1.1.27.1.4.1 | ||||||||||||||||||||
| ScoolingUnitStatusAnalogTableSize | 1.3.6.1.4.1.318.1.1.27.1.4.1.1 | INTEGER (0..2147483647) | RO | mandatory | |||||||||||||||||
scalar · INTEGER (0..2147483647) · read-only · mandatory The potential number of entries available in coolingUnitStatusAnalogTable. | |||||||||||||||||||||
| TcoolingUnitStatusAnalogTable | 1.3.6.1.4.1.318.1.1.27.1.4.1.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A table of analog unit status data. | |||||||||||||||||||||
| RcoolingUnitStatusAnalogEntry | 1.3.6.1.4.1.318.1.1.27.1.4.1.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An element of coolingUnitStatusAnalogTable. | |||||||||||||||||||||
| CcoolingUnitStatusAnalogTableIndex | 1.3.6.1.4.1.318.1.1.27.1.4.1.2.1.1 | INTEGER (1..2147483647) | NA | mandatory | 1 | ||||||||||||||||
column · INTEGER (1..2147483647) · not-accessible · mandatory The static reference identifier for each table entry. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CcoolingUnitStatusAnalogDescription | 1.3.6.1.4.1.318.1.1.27.1.4.1.2.1.2 | DisplayString | RO | mandatory | Group Minimum Rack Temperature | ||||||||||||||||
column · DisplayString · read-only · mandatory A text description of the information presented in coolingUnitStatusAnalogValue. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CcoolingUnitStatusAnalogValue | 1.3.6.1.4.1.318.1.1.27.1.4.1.2.1.3 | INTEGER | RO | mandatory | 209 | ||||||||||||||||
column · INTEGER · read-only · mandatory The scaled value of the current table entry (multiplied by coolingUnitStatusAnalogScale for integer presentation). Example values from LibreNMS test devices
| |||||||||||||||||||||
| CcoolingUnitStatusAnalogUnits | 1.3.6.1.4.1.318.1.1.27.1.4.1.2.1.4 | DisplayString | RO | mandatory | C | ||||||||||||||||
column · DisplayString · read-only · mandatory The unit of measure by which coolingUnitStatusAnalogValue is expressed. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CcoolingUnitStatusAnalogScale | 1.3.6.1.4.1.318.1.1.27.1.4.1.2.1.5 | INTEGER | RO | mandatory | 10 | ||||||||||||||||
column · INTEGER · read-only · mandatory The factor by which coolingUnitStatusAnalogValue is expressed. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NcoolingUnitStatusDiscrete | 1.3.6.1.4.1.318.1.1.27.1.4.2 | ||||||||||||||||||||
| ScoolingUnitStatusDiscreteTableSize | 1.3.6.1.4.1.318.1.1.27.1.4.2.1 | INTEGER (0..2147483647) | RO | mandatory | |||||||||||||||||
scalar · INTEGER (0..2147483647) · read-only · mandatory The potential number of entries available in coolingUnitStatusDiscreteTable. | |||||||||||||||||||||
| TcoolingUnitStatusDiscreteTable | 1.3.6.1.4.1.318.1.1.27.1.4.2.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A table of discrete unit status data. | |||||||||||||||||||||
| RcoolingUnitStatusDiscreteEntry | 1.3.6.1.4.1.318.1.1.27.1.4.2.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An element of coolingUnitStatusDiscreteTable. | |||||||||||||||||||||
| CcoolingUnitStatusDiscreteTableIndex | 1.3.6.1.4.1.318.1.1.27.1.4.2.2.1.1 | INTEGER (1..2147483647) | NA | mandatory | 1 | ||||||||||||||||
column · INTEGER (1..2147483647) · not-accessible · mandatory The static reference identifier for each table entry. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CcoolingUnitStatusDiscreteDescription | 1.3.6.1.4.1.318.1.1.27.1.4.2.2.1.2 | DisplayString | RO | mandatory | Active Flow Control Status | ||||||||||||||||
column · DisplayString · read-only · mandatory A text description of the information presented in this table's 'value' OIDs. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CcoolingUnitStatusDiscreteValueAsString | 1.3.6.1.4.1.318.1.1.27.1.4.2.2.1.3 | DisplayString | RO | mandatory | NA | ||||||||||||||||
column · DisplayString · read-only · mandatory The actual value of the current table entry expressed as a string. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CcoolingUnitStatusDiscreteValueAsInteger | 1.3.6.1.4.1.318.1.1.27.1.4.2.2.1.4 | INTEGER | RO | mandatory | 4 | ||||||||||||||||
column · INTEGER · read-only · mandatory The actual value of the current table entry expressed as an integer value. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CcoolingUnitStatusDiscreteIntegerReferenceKey | 1.3.6.1.4.1.318.1.1.27.1.4.2.2.1.5 | DisplayString | RO | mandatory | Under(0),Okay(1),Over(2),NA(3),NA(4) | ||||||||||||||||
column · DisplayString · read-only · mandatory A complete listing of all possible coolingUnitStatusDiscreteValueAsInteger values paired with their identifying strings. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NcoolingUnitConfiguration | 1.3.6.1.4.1.318.1.1.27.1.5 | ||||||||||||||||||||
| NcoolingUnitConfigurationAnalog | 1.3.6.1.4.1.318.1.1.27.1.5.1 | ||||||||||||||||||||
| ScoolingUnitConfigurationAnalogTableSize | 1.3.6.1.4.1.318.1.1.27.1.5.1.1 | INTEGER (0..2147483647) | RO | mandatory | |||||||||||||||||
scalar · INTEGER (0..2147483647) · read-only · mandatory The potential number of entries available in coolingUnitConfigurationAnalogTable. | |||||||||||||||||||||
| TcoolingUnitConfigurationAnalogTable | 1.3.6.1.4.1.318.1.1.27.1.5.1.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A table of analog unit configuration data. | |||||||||||||||||||||
| RcoolingUnitConfigurationAnalogEntry | 1.3.6.1.4.1.318.1.1.27.1.5.1.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An element of coolingUnitConfigurationAnalogTable. | |||||||||||||||||||||
| CcoolingUnitConfigurationAnalogTableIndex | 1.3.6.1.4.1.318.1.1.27.1.5.1.2.1.1 | INTEGER (1..2147483647) | NA | mandatory | |||||||||||||||||
column · INTEGER (1..2147483647) · not-accessible · mandatory The static reference identifier for each table entry. | |||||||||||||||||||||
| CcoolingUnitConfigurationAnalogDescription | 1.3.6.1.4.1.318.1.1.27.1.5.1.2.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory A text description of the information presented in coolingUnitConfigurationAnalogValue. | |||||||||||||||||||||
| CcoolingUnitConfigurationAnalogValue | 1.3.6.1.4.1.318.1.1.27.1.5.1.2.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The scaled value of the current table entry (multiplied by coolingUnitConfigurationAnalogScale for integer presentation). | |||||||||||||||||||||
| CcoolingUnitConfigurationAnalogUnits | 1.3.6.1.4.1.318.1.1.27.1.5.1.2.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The unit of measure by which coolingUnitConfigurationAnalogValue is expressed. | |||||||||||||||||||||
| CcoolingUnitConfigurationAnalogScale | 1.3.6.1.4.1.318.1.1.27.1.5.1.2.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The factor by which coolingUnitConfigurationAnalogValue is expressed. | |||||||||||||||||||||
| CcoolingUnitConfigurationAnalogAccess | 1.3.6.1.4.1.318.1.1.27.1.5.1.2.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory A description of available access to coolingUnitConfigurationAnalogValue via SNMP client.
| |||||||||||||||||||||
| CcoolingUnitConfigurationAnalogMinimum | 1.3.6.1.4.1.318.1.1.27.1.5.1.2.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The minimum possible value of coolingUnitConfigurationAnalogValue. | |||||||||||||||||||||
| CcoolingUnitConfigurationAnalogMaximum | 1.3.6.1.4.1.318.1.1.27.1.5.1.2.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The maximum possible value of coolingUnitConfigurationAnalogValue. | |||||||||||||||||||||
| NcoolingUnitConfigurationDiscrete | 1.3.6.1.4.1.318.1.1.27.1.5.2 | ||||||||||||||||||||
| ScoolingUnitConfigurationDiscreteTableSize | 1.3.6.1.4.1.318.1.1.27.1.5.2.1 | INTEGER (0..2147483647) | RO | mandatory | |||||||||||||||||
scalar · INTEGER (0..2147483647) · read-only · mandatory The potential number of entries available in coolingUnitConfigurationDiscreteTable. | |||||||||||||||||||||
| TcoolingUnitConfigurationDiscreteTable | 1.3.6.1.4.1.318.1.1.27.1.5.2.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A table of discrete unit configuration data. | |||||||||||||||||||||
| RcoolingUnitConfigurationDiscreteEntry | 1.3.6.1.4.1.318.1.1.27.1.5.2.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An element of coolingUnitConfigurationDiscreteTable. | |||||||||||||||||||||
| CcoolingUnitConfigurationDiscreteTableIndex | 1.3.6.1.4.1.318.1.1.27.1.5.2.2.1.1 | INTEGER (1..2147483647) | NA | mandatory | |||||||||||||||||
column · INTEGER (1..2147483647) · not-accessible · mandatory The static reference identifier for each table entry. | |||||||||||||||||||||
| CcoolingUnitConfigurationDiscreteDescription | 1.3.6.1.4.1.318.1.1.27.1.5.2.2.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory A text description of the information presented in this table's 'value' OIDs. | |||||||||||||||||||||
| CcoolingUnitConfigurationDiscreteValueAsString | 1.3.6.1.4.1.318.1.1.27.1.5.2.2.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The actual value of the current table entry expressed as a string. | |||||||||||||||||||||
| CcoolingUnitConfigurationDiscreteValueAsInteger | 1.3.6.1.4.1.318.1.1.27.1.5.2.2.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The actual value of the current table entry expressed as an integer value. | |||||||||||||||||||||
| CcoolingUnitConfigurationDiscreteIntegerReferenceKey | 1.3.6.1.4.1.318.1.1.27.1.5.2.2.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory A complete listing of all possible coolingUnitConfigurationDiscreteValueAsInteger values paired with their identifying strings. | |||||||||||||||||||||
| CcoolingUnitConfigurationDiscreteAccess | 1.3.6.1.4.1.318.1.1.27.1.5.2.2.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory A description of available access to coolingUnitConfigurationDiscreteValueAsInteger via SNMP client.
| |||||||||||||||||||||
| NcoolingUnitConfigurationString | 1.3.6.1.4.1.318.1.1.27.1.5.3 | ||||||||||||||||||||
| ScoolingUnitConfigurationStringTableSize | 1.3.6.1.4.1.318.1.1.27.1.5.3.1 | INTEGER (0..2147483647) | RO | mandatory | |||||||||||||||||
scalar · INTEGER (0..2147483647) · read-only · mandatory The potential number of entries available in coolingUnitConfigurationStringTable. | |||||||||||||||||||||
| TcoolingUnitConfigurationStringTable | 1.3.6.1.4.1.318.1.1.27.1.5.3.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A table of unit configuration strings. | |||||||||||||||||||||
| RcoolingUnitConfigurationStringEntry | 1.3.6.1.4.1.318.1.1.27.1.5.3.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An element of coolingUnitConfigurationStringTable. | |||||||||||||||||||||
| CcoolingUnitConfigurationStringTableIndex | 1.3.6.1.4.1.318.1.1.27.1.5.3.2.1.1 | INTEGER (1..2147483647) | NA | mandatory | |||||||||||||||||
column · INTEGER (1..2147483647) · not-accessible · mandatory The static reference identifier for each table entry. | |||||||||||||||||||||
| CcoolingUnitConfigurationStringDescription | 1.3.6.1.4.1.318.1.1.27.1.5.3.2.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory A text description of the information presented in coolingUnitConfigurationStringValue. | |||||||||||||||||||||
| CcoolingUnitConfigurationStringValue | 1.3.6.1.4.1.318.1.1.27.1.5.3.2.1.3 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The actual value of the current table entry. | |||||||||||||||||||||
| CcoolingUnitConfigurationStringMaxLength | 1.3.6.1.4.1.318.1.1.27.1.5.3.2.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The maximum string length supported by coolingUnitConfigurationStringValue. | |||||||||||||||||||||
| CcoolingUnitConfigurationStringAccess | 1.3.6.1.4.1.318.1.1.27.1.5.3.2.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory A description of available access to coolingUnitConfigurationStringValue via SNMP client.
| |||||||||||||||||||||
| NcoolingUnitExtended | 1.3.6.1.4.1.318.1.1.27.1.6 | ||||||||||||||||||||
| NcoolingUnitExtendedAnalog | 1.3.6.1.4.1.318.1.1.27.1.6.1 | ||||||||||||||||||||
| ScoolingUnitExtendedAnalogTableSize | 1.3.6.1.4.1.318.1.1.27.1.6.1.1 | INTEGER (0..2147483647) | RO | mandatory | |||||||||||||||||
scalar · INTEGER (0..2147483647) · read-only · mandatory The potential number of entries available in coolingUnitExtendedAnalogTable. | |||||||||||||||||||||
| TcoolingUnitExtendedAnalogTable | 1.3.6.1.4.1.318.1.1.27.1.6.1.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A table of secondary analog data for the cooling unit or one of its components. | |||||||||||||||||||||
| RcoolingUnitExtendedAnalogEntry | 1.3.6.1.4.1.318.1.1.27.1.6.1.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An element of coolingUnitExtendedAnalogTable. | |||||||||||||||||||||
| CcoolingUnitExtendedAnalogTableIndex | 1.3.6.1.4.1.318.1.1.27.1.6.1.2.1.1 | INTEGER (1..2147483647) | NA | mandatory | 1 | ||||||||||||||||
column · INTEGER (1..2147483647) · not-accessible · mandatory The static reference identifier for each table entry. This identifier may reference different table entries in different unit models. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CcoolingUnitExtendedAnalogDescription | 1.3.6.1.4.1.318.1.1.27.1.6.1.2.1.2 | DisplayString | RO | mandatory | Chilled Water Valve Position | ||||||||||||||||
column · DisplayString · read-only · mandatory A text description of the information presented in coolingUnitExtendedAnalogValue. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CcoolingUnitExtendedAnalogValue | 1.3.6.1.4.1.318.1.1.27.1.6.1.2.1.3 | INTEGER | RO | mandatory | 28 | ||||||||||||||||
column · INTEGER · read-only · mandatory The scaled value of the current table entry (multiplied by coolingUnitExtendedAnalogScale for integer presentation). Example values from LibreNMS test devices
| |||||||||||||||||||||
| CcoolingUnitExtendedAnalogUnits | 1.3.6.1.4.1.318.1.1.27.1.6.1.2.1.4 | DisplayString | RO | mandatory | % | ||||||||||||||||
column · DisplayString · read-only · mandatory The unit of measure by which coolingUnitExtendedAnalogValue is expressed. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CcoolingUnitExtendedAnalogScale | 1.3.6.1.4.1.318.1.1.27.1.6.1.2.1.5 | INTEGER | RO | mandatory | 1 | ||||||||||||||||
column · INTEGER · read-only · mandatory The factor by which coolingUnitExtendedAnalogValue is expressed. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NcoolingUnitExtendedDiscrete | 1.3.6.1.4.1.318.1.1.27.1.6.2 | ||||||||||||||||||||
| ScoolingUnitExtendedDiscreteTableSize | 1.3.6.1.4.1.318.1.1.27.1.6.2.1 | INTEGER (0..2147483647) | RO | mandatory | |||||||||||||||||
scalar · INTEGER (0..2147483647) · read-only · mandatory The potential number of entries available in coolingUnitExtendedDiscreteTable. | |||||||||||||||||||||
| TcoolingUnitExtendedDiscreteTable | 1.3.6.1.4.1.318.1.1.27.1.6.2.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A table of secondary discrete cooling unit data. | |||||||||||||||||||||
| RcoolingUnitExtendedDiscreteEntry | 1.3.6.1.4.1.318.1.1.27.1.6.2.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An element of coolingUnitExtendedDiscreteTable. | |||||||||||||||||||||
| CcoolingUnitExtendedDiscreteTableIndex | 1.3.6.1.4.1.318.1.1.27.1.6.2.2.1.1 | INTEGER (1..2147483647) | NA | mandatory | 1 | ||||||||||||||||
column · INTEGER (1..2147483647) · not-accessible · mandatory The static reference identifier for each table entry. This identifier may reference different table entries in different unit models. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CcoolingUnitExtendedDiscreteDescription | 1.3.6.1.4.1.318.1.1.27.1.6.2.2.1.2 | DisplayString | RO | mandatory | Standby Input State | ||||||||||||||||
column · DisplayString · read-only · mandatory A text description of the information presented in this table's 'value' OIDs. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CcoolingUnitExtendedDiscreteValueAsString | 1.3.6.1.4.1.318.1.1.27.1.6.2.2.1.3 | DisplayString | RO | mandatory | Open | ||||||||||||||||
column · DisplayString · read-only · mandatory The actual value of the current table entry expressed as a string. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CcoolingUnitExtendedDiscreteValueAsInteger | 1.3.6.1.4.1.318.1.1.27.1.6.2.2.1.4 | INTEGER | RO | mandatory | 0 | ||||||||||||||||
column · INTEGER · read-only · mandatory The actual value of the current table entry expressed as an integer value. Example values from LibreNMS test devices
| |||||||||||||||||||||
| CcoolingUnitExtendedDiscreteIntegerReferenceKey | 1.3.6.1.4.1.318.1.1.27.1.6.2.2.1.5 | DisplayString | RO | mandatory | Open(0),Closed(1) | ||||||||||||||||
column · DisplayString · read-only · mandatory A complete listing of all possible coolingUnitExtendedDiscreteValueAsInteger values paired with their identifying strings. Example values from LibreNMS test devices
| |||||||||||||||||||||
| NcoolingUnitExtendedString | 1.3.6.1.4.1.318.1.1.27.1.6.3 | ||||||||||||||||||||
| ScoolingUnitExtendedStringTableSize | 1.3.6.1.4.1.318.1.1.27.1.6.3.1 | INTEGER (0..2147483647) | RO | mandatory | |||||||||||||||||
scalar · INTEGER (0..2147483647) · read-only · mandatory The potential number of entries available in coolingUnitExtendedStringTable. | |||||||||||||||||||||
| TcoolingUnitExtendedStringTable | 1.3.6.1.4.1.318.1.1.27.1.6.3.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A table of secondary unit reference data. | |||||||||||||||||||||
| RcoolingUnitExtendedStringEntry | 1.3.6.1.4.1.318.1.1.27.1.6.3.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An element of coolingUnitExtendedStringTable. | |||||||||||||||||||||
| CcoolingUnitExtendedStringTableIndex | 1.3.6.1.4.1.318.1.1.27.1.6.3.2.1.1 | INTEGER (1..2147483647) | NA | mandatory | |||||||||||||||||
column · INTEGER (1..2147483647) · not-accessible · mandatory The static reference identifier for each table entry. This identifier may reference different table entries in different unit models. | |||||||||||||||||||||
| CcoolingUnitExtendedStringDescription | 1.3.6.1.4.1.318.1.1.27.1.6.3.2.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory A text description of the information presented in coolingUnitExtendedStringValue. | |||||||||||||||||||||
| CcoolingUnitExtendedStringValue | 1.3.6.1.4.1.318.1.1.27.1.6.3.2.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The actual value of the current table entry. | |||||||||||||||||||||
| NpowerManagementModule | 1.3.6.1.4.1.318.1.1.28 | ||||||||||||||||||||
| NpmmIdent | 1.3.6.1.4.1.318.1.1.28.1 | ||||||||||||||||||||
| SpmmIdentModelNumber | 1.3.6.1.4.1.318.1.1.28.1.1 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the model number of the unit. This value is set at the factory. | |||||||||||||||||||||
| SpmmIdentSerialNumber | 1.3.6.1.4.1.318.1.1.28.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the serial number of the unit. This value is set at the factory. | |||||||||||||||||||||
| SpmmIdentDateOfManufacture | 1.3.6.1.4.1.318.1.1.28.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The date when the unit was manufactured in mm/dd/yyyy format. This value is set at the factory. | |||||||||||||||||||||
| SpmmIdentHMISerialNumber | 1.3.6.1.4.1.318.1.1.28.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the serial number of the HMI. This value is set at the factory. | |||||||||||||||||||||
| SpmmIdentHMIHardwareRev | 1.3.6.1.4.1.318.1.1.28.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The hardware revision of the HMI. This value is set at the factory. | |||||||||||||||||||||
| SpmmIdentHMIFirmwareAppRev | 1.3.6.1.4.1.318.1.1.28.1.6 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory An ID string identifying the application firmware revision of the HMI. | |||||||||||||||||||||
| SpmmIdentHMIFirmwareAppOSRev | 1.3.6.1.4.1.318.1.1.28.1.7 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory An ID string identifying the application operating system firmware revision of the HMI. | |||||||||||||||||||||
| NpmmDevice | 1.3.6.1.4.1.318.1.1.28.2 | ||||||||||||||||||||
| SpmmDeviceNominalInputVoltage | 1.3.6.1.4.1.318.1.1.28.2.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The nominal input voltage to the PMM. Measured in Volts, line-to-line for a 3-wire (delta) service or line-to-neutral for a 4-wire (wye) service. | |||||||||||||||||||||
| SpmmDeviceServiceType | 1.3.6.1.4.1.318.1.1.28.2.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The type of utility input to the PMM. Either 3 wires (delta), or 4 wires (wye).
| |||||||||||||||||||||
| SpmmDeviceNominalOutputVoltage | 1.3.6.1.4.1.318.1.1.28.2.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The nominal line-to-neutral output voltage to the load measured in Volts. | |||||||||||||||||||||
| NpmmMonitoring | 1.3.6.1.4.1.318.1.1.28.3 | ||||||||||||||||||||
| NpmmInput | 1.3.6.1.4.1.318.1.1.28.3.1 | ||||||||||||||||||||
| SpmmInputMeterTableSize | 1.3.6.1.4.1.318.1.1.28.3.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of input meters attached to the system. | |||||||||||||||||||||
| TpmmInputTable | 1.3.6.1.4.1.318.1.1.28.3.1.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of input meter entries. | |||||||||||||||||||||
| RpmmInputEntry | 1.3.6.1.4.1.318.1.1.28.3.1.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular input meter.
| |||||||||||||||||||||
| CpmmInputMeterIndex | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The input meter identifier. | |||||||||||||||||||||
| CpmmInputFrequency | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The input frequency in tenths of Hertz. | |||||||||||||||||||||
| CpmmInputTotalActivePower | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Shows the total input active power in tenths of kW. | |||||||||||||||||||||
| CpmmInputTotalApparentPower | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Shows the total input apparent power in tenths of kVA. | |||||||||||||||||||||
| CpmmInputTotalPowerFactor | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Indicates the total power factor. A value of 100 representing a unity power factor (1.00). Specified in hundredths. Returns -255 if unsupported | |||||||||||||||||||||
| CpmmInputActiveEnergyDelivered | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.6 | Integer32 | RO | mandatory | |||||||||||||||||
column · Integer32 · read-only · mandatory Shows the input active energy delivered in tenths of kWh. | |||||||||||||||||||||
| CpmmInputActiveEnergyReceived | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.7 | Integer32 | RO | mandatory | |||||||||||||||||
column · Integer32 · read-only · mandatory Shows the input active energy received in tenths of kWh. | |||||||||||||||||||||
| CpmmInputApparentEnergyDelivered | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.8 | Integer32 | RO | mandatory | |||||||||||||||||
column · Integer32 · read-only · mandatory Shows the input apparent energy delivered in tenths of kVAh. | |||||||||||||||||||||
| CpmmInputApparentEnergyReceived | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.9 | Integer32 | RO | mandatory | |||||||||||||||||
column · Integer32 · read-only · mandatory Shows the input apparent energy received in tenths of kVAh. | |||||||||||||||||||||
| CpmmInputFrequencyDeviation | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.10 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Displays the input frequency deviation in Hertz. Threshold write returns as unsuccessful if one of the breaker threshold groups does not meet conditions. In this case, read the thresholds to know which threshold group's write condition is not met. Threshold needs to be enabled to read value
| |||||||||||||||||||||
| CpmmInputPowerFactorDeviation | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.11 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Displays the input power factor deviation. Specified in tenths. A value of zero indicates that the threshold is disabled. Returns -1 if unsupported. Threshold write returns as unsuccessful if one of the breaker threshold groups does not meet conditions. In this case, read the thresholds to know which threshold group's write condition is not met. Threshold needs to be enabled to read value | |||||||||||||||||||||
| CpmmInputMinVoltThreshold | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.12 | INTEGER (0..100) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..100) · read-write · mandatory Threshold below which an input minimum voltage condition will be generated. Specified as percent deviation from nominal voltage represented in the OID pmmDeviceNominalInputVoltage. A value of zero indicates that the threshold is disabled. Threshold write returns as unsuccessful if one of the breaker threshold groups does not meet conditions. In this case, read the thresholds to know which threshold group's write condition is not met. Threshold needs to be enabled to read value | |||||||||||||||||||||
| CpmmInputLowVoltThreshold | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.13 | INTEGER (0..100) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..100) · read-write · mandatory Threshold below which an input low voltage condition will be generated. Specified as percent deviation from nominal voltage represented in the OID pmmDeviceNominalInputVoltage. A value of zero indicates that the threshold is disabled. Threshold write returns as unsuccessful if one of the breaker threshold groups does not meet conditions. In this case, read the thresholds to know which threshold group's write condition is not met. Threshold needs to be enabled to read value | |||||||||||||||||||||
| CpmmInputHighVoltThreshold | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.14 | INTEGER (0..120) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..120) · read-write · mandatory Threshold above which an input high voltage condition will be generated. Specified as percent deviation from nominal voltage represented in the OID pmmDeviceNominalInputVoltage. A value of zero indicates that the threshold is disabled. Threshold write returns as unsuccessful if one of the breaker threshold groups does not meet conditions. In this case, read the thresholds to know which threshold group's write condition is not met. Threshold needs to be enabled to read value | |||||||||||||||||||||
| CpmmInputMaxVoltThreshold | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.15 | INTEGER (0..120) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..120) · read-write · mandatory Threshold above which an input maximum voltage condition will be generated. Specified as percent deviation from nominal voltage represented in the OID pmmDeviceNominalInputVoltage. A value of zero indicates that the threshold is disabled. Threshold write returns as unsuccessful if one of the breaker threshold groups does not meet conditions. In this case, read the thresholds to know which threshold group's write condition is not met. Threshold needs to be enabled to read value | |||||||||||||||||||||
| CpmmInputMinCurrentThreshold | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.16 | INTEGER (0..100) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..100) · read-write · mandatory Threshold below which an input minimum current condition will be generated. Specified as a percent of the panel breaker rating. A value of zero indicates that the threshold is disabled. Threshold write returns as unsuccessful if one of the breaker threshold groups does not meet conditions. In this case, read the thresholds to know which threshold group's write condition is not met. Threshold needs to be enabled to read value | |||||||||||||||||||||
| CpmmInputLowCurrentThreshold | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.17 | INTEGER (0..100) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..100) · read-write · mandatory Threshold below which an input low current condition will be generated. Specified as a percent of the panel breaker rating. A value of zero indicates that the threshold is disabled. Threshold write returns as unsuccessful if one of the breaker threshold groups does not meet conditions. In this case, read the thresholds to know which threshold group's write condition is not met. Threshold needs to be enabled to read value | |||||||||||||||||||||
| CpmmInputHighCurrentThreshold | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.18 | INTEGER (0..110) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..110) · read-write · mandatory Threshold above which an input high current condition will be generated. Specified as a percent of the panel breaker rating. A value of zero indicates that the threshold is disabled. Threshold write returns as unsuccessful if one of the breaker threshold groups does not meet conditions. In this case, read the thresholds to know which threshold group's write condition is not met. Threshold needs to be enabled to read value | |||||||||||||||||||||
| CpmmInputMaxCurrentThreshold | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.19 | INTEGER (0..100) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..100) · read-write · mandatory Threshold above which an input maximum current condition will be generated. Specified as a percent of the panel breaker rating. A value of zero indicates that the threshold is disabled. Threshold write returns as unsuccessful if one of the breaker threshold groups does not meet conditions. In this case, read the thresholds to know which threshold group's write condition is not met. Threshold needs to be enabled to read value | |||||||||||||||||||||
| CpmmInputMinApparentPowerThreshold | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.20 | INTEGER (0..100) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..100) · read-write · mandatory Threshold below which an input minimum apparent power condition will be generated. Specified as a percent deviation from nominal power rating. A value of zero indicates that the threshold is disabled. Threshold write returns as unsuccessful if one of the breaker threshold groups does not meet conditions. In this case, read the thresholds to know which threshold group's write condition is not met. Threshold needs to be enabled to read value | |||||||||||||||||||||
| CpmmInputMaxApparentPowerThreshold | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.21 | INTEGER (0..110) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..110) · read-write · mandatory Threshold above which an input maximum apparent power condition will be generated. Specified as a percent deviation from nominal power rating. A value of zero indicates that the threshold is disabled. Threshold write returns as unsuccessful if one of the breaker threshold groups does not meet conditions. In this case, read the thresholds to know which threshold group's write condition is not met. Threshold needs to be enabled to read value | |||||||||||||||||||||
| CpmmInputOverActivePowerThreshold | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.22 | INTEGER (0..100) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..100) · read-write · mandatory Threshold above which an input over active power condition will be generated. Specified as a percent deviation from nominal power rating. A value of zero indicates that the threshold is disabled. Threshold write returns as unsuccessful if one of the breaker threshold groups does not meet conditions. In this case, read the thresholds to know which threshold group's write condition is not met. Threshold needs to be enabled to read value | |||||||||||||||||||||
| CpmmInputBreakerState | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.23 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This value indicates the current state of input breaker. 1 will indicate open, 2 will indicate closed, 3 will indicate unknown. Returns -1 if unsupported or failed.
| |||||||||||||||||||||
| CpmmInputBreakerOpenAlarm | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.24 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Breaker open alarm status. 1 will indicate enabled, 2 will indicate disabled, 3 will indicate unknown.
| |||||||||||||||||||||
| CpmmInputAverageCurrent | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.25 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Input Average current. Measured in tenths of Amps. | |||||||||||||||||||||
| CpmmInputNeturalCurrent | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.26 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Input Neutral current. Measured in tenths of Amps. | |||||||||||||||||||||
| CpmmInputMaxInstantaneousNeutralCurrent | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.27 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Input maximum instantaneous neutral current. Measured in tenths of Amps. | |||||||||||||||||||||
| CpmmInputAverageCurrentTHD | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.28 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Input average harmonic distortions. Returns -1 if unsupported or failed. | |||||||||||||||||||||
| CpmmInputAverageVoltageLtoL | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.29 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Input Average Line to Line voltage. Measured in tenths of Volts. Returns -1 if unsupported or failed. | |||||||||||||||||||||
| CpmmInputAverageVoltageLtoN | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.30 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Input Average Line to Neutral voltage. Measured in tenths of Volts. Returns -1 if unsupported or failed. | |||||||||||||||||||||
| CpmmInputLoad | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.31 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Total load of input breaker in percentage. Measured in tenths of percent. Returns -1 if unsupported or failed. | |||||||||||||||||||||
| CpmmInputMeterFirmwareVersion | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.32 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Shows the input meter firmware version. Returns -1 if unsupported or failed. | |||||||||||||||||||||
| CpmmInputMeterSerialNumber | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.33 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory Shows the input meter serial number. Returns -1 if unsupported or failed. | |||||||||||||||||||||
| CpmmInputEnergyUsageAccumulatedTotal | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.34 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Shows the total accumulated input energy usage in kWh. Measured in tenths of kWh. Returns -1 if unsupported or failed. | |||||||||||||||||||||
| CpmmInputPhaseLoss | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.35 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Threshold below which an input phase loss condition will be generated. Specified as a percent deviation from phase to neutral nominal voltage. A value of zero indicates that the threshold is disabled. Returns -1 if unsupported or failed. Threshold write returns as unsuccessful if one of the breaker threshold groups does not meet conditions. In this case, read the thresholds to know which threshold group's write condition is not met. Threshold needs to be enabled to read value | |||||||||||||||||||||
| CpmmInputBreakerCTSize | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.36 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Shows the input breaker CT size. Returns -1 if unsupported or failed. | |||||||||||||||||||||
| CpmmInputBreakerRating | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.37 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Shows the input breaker rating in Amps(A). Returns -1 if unsupported or failed. | |||||||||||||||||||||
| CpmmInputKWHResetDate | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.38 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The date that the kWh usage was reset, in the format mm/dd/yyyy. | |||||||||||||||||||||
| CpmmInputAlarmGeneration | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.39 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Alarm generation status. 1 - enabled 2 - disabled 3 - unknown | |||||||||||||||||||||
| CpmmInputVoltageMaximumAlarm | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.40 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Voltage maximum alarm generation status. 1 - enabled 2 - disabled 3 - unknown | |||||||||||||||||||||
| CpmmInputVoltageHighAlarm | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.41 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Voltage high alarm generation status. 1 - enabled 2 - disabled 3 - unknown | |||||||||||||||||||||
| CpmmInputVoltageLowAlarm | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.42 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Voltage low alarm generation status. 1 - enabled 2 - disabled 3 - unknown | |||||||||||||||||||||
| CpmmInputVoltageMinimumAlarm | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.43 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Voltage minimum alarm generation status. 1 - enabled 2 - disabled 3 - unknown | |||||||||||||||||||||
| CpmmInputCurrentMaximumAlarm | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.44 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Current maximum alarm generation status. 1 - enabled 2 - disabled 3 - unknown | |||||||||||||||||||||
| CpmmInputCurrentHighAlarm | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.45 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Current high alarm generation status. 1 - enabled 2 - disabled 3 - unknown | |||||||||||||||||||||
| CpmmInputCurrentLowAlarm | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.46 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Current low alarm generation status. 1 - enabled 2 - disabled 3 - unknown | |||||||||||||||||||||
| CpmmInputCurrentMinimumAlarm | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.47 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Current minimum alarm generation status. 1 - enabled 2 - disabled 3 - unknown | |||||||||||||||||||||
| CpmmInputApparentPowerMaximumAlarm | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.48 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Apparent Power maximum alarm generation status. 1 - enabled 2 - disabled 3 - unknown | |||||||||||||||||||||
| CpmmInputApparentPowerMinimumAlarm | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.49 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Apparent Power minimum alarm generation status. 1 - enabled 2 - disabled 3 - unknown | |||||||||||||||||||||
| CpmmInputKWOverAlarm | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.50 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Over active power alarm generation status. 1 - enabled 2 - disabled 3 - unknown | |||||||||||||||||||||
| CpmmInputPhaseLossAlarm | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.51 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Phase loss alarm generation status. 1 - enabled 2 - disabled 3 - unknown | |||||||||||||||||||||
| CpmmInputPowerFactorTotalAlarm | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.52 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Total power factor alarm generation status. 1 - enabled 2 - disabled 3 - unknown | |||||||||||||||||||||
| CpmmInputFrequencyDeviationAlarm | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.53 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Frequency deviation alarm generation status. 1 - enabled 2 - disabled 3 - unknown | |||||||||||||||||||||
| CpmmInputNeutralOverCurrentAlarm | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.54 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Neutral Overcurrent alarm generation status. 1 - enabled 2 - disabled 3 - unknown | |||||||||||||||||||||
| CpmmInputNeutralOverCurrentThreshold | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.55 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Threshold above which an input neutral overcurrent condition will be generated. Specified as a percent deviation from nominal current. A value of zero indicates that the threshold is disabled. Returns -1 if unsupported or failed. Threshold write returns as unsuccessful if one of the breaker threshold groups does not meet conditions. In this case, read the thresholds to know which threshold group's write condition is not met. Threshold needs to be enabled to read value | |||||||||||||||||||||
| CpmmInputAveragePowerFactor | 1.3.6.1.4.1.318.1.1.28.3.1.2.1.56 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Indicates the average power factor. A value of 100 representing a unity power factor (1.00). Specified in hundredths. Returns -255 if unsupported. | |||||||||||||||||||||
| TpmmInputPhaseTable | 1.3.6.1.4.1.318.1.1.28.3.1.3 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of input table entries. The number of entries is given by the value of pmmInputMeterTableSize OID. | |||||||||||||||||||||
| RpmmInputPhaseEntry | 1.3.6.1.4.1.318.1.1.28.3.1.3.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular input phase. | |||||||||||||||||||||
| CpmmInputMeterNum | 1.3.6.1.4.1.318.1.1.28.3.1.3.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The input meter identifier. | |||||||||||||||||||||
| CpmmInputPhase | 1.3.6.1.4.1.318.1.1.28.3.1.3.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Input phase index. | |||||||||||||||||||||
| CpmmInputVoltageLtoL | 1.3.6.1.4.1.318.1.1.28.3.1.3.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Line-to-line input voltage available. Measured in tenths of Volts. | |||||||||||||||||||||
| CpmmInputVoltageLtoN | 1.3.6.1.4.1.318.1.1.28.3.1.3.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Line-to-neutral input voltage available. Measured in tenths of Volts. | |||||||||||||||||||||
| CpmmInputPhaseCurrent | 1.3.6.1.4.1.318.1.1.28.3.1.3.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Input current per phase. Measured in tenths of Amps. | |||||||||||||||||||||
| CpmmInputActivePower | 1.3.6.1.4.1.318.1.1.28.3.1.3.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Input active power per phase. Measured in tenths of kW. | |||||||||||||||||||||
| CpmmInputApparentPower | 1.3.6.1.4.1.318.1.1.28.3.1.3.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Input apparent power per phase. Measured in tenths of kVA. | |||||||||||||||||||||
| CpmmInputPowerFactor | 1.3.6.1.4.1.318.1.1.28.3.1.3.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Indicates the power factor of the input per phase. A value of 100 representing a unity power factor (1.00). Specified in hundredths. | |||||||||||||||||||||
| CpmmInputMaxInstantaneousCurrent | 1.3.6.1.4.1.318.1.1.28.3.1.3.1.9 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Input maximum phase instantaneous current. Measured in tenths of Amps. | |||||||||||||||||||||
| CpmmInputPhaseAngle | 1.3.6.1.4.1.318.1.1.28.3.1.3.1.10 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Current phase Angle. Measured in tenths of decimal Returns -255 if unsupported | |||||||||||||||||||||
| CpmmInputTHDLtoL | 1.3.6.1.4.1.318.1.1.28.3.1.3.1.11 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Input harmonic distortions line to line for the present input voltage. Measured in tenths. | |||||||||||||||||||||
| CpmmInputTHDLtoN | 1.3.6.1.4.1.318.1.1.28.3.1.3.1.12 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Input harmonic distortions line to neutral for the present input voltage. Measured in tenths. | |||||||||||||||||||||
| CpmmInputCurrentTHD | 1.3.6.1.4.1.318.1.1.28.3.1.3.1.13 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Input harmonic distortions for each phase, for the present input current.
Returns -1 if unsupported or failed.
Specified in tenths. | |||||||||||||||||||||
| NpmmOutput | 1.3.6.1.4.1.318.1.1.28.3.2 | ||||||||||||||||||||
| SpmmOutputMeterTableSize | 1.3.6.1.4.1.318.1.1.28.3.2.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of output meters attached to the system. | |||||||||||||||||||||
| TpmmOutputTable | 1.3.6.1.4.1.318.1.1.28.3.2.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of output meter entries. | |||||||||||||||||||||
| RpmmOutputEntry | 1.3.6.1.4.1.318.1.1.28.3.2.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular output meter.
| |||||||||||||||||||||
| CpmmOutputMeterIndex | 1.3.6.1.4.1.318.1.1.28.3.2.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The output meter identifier. | |||||||||||||||||||||
| CpmmOutputFrequency | 1.3.6.1.4.1.318.1.1.28.3.2.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The output frequency in tenths of Hertz. | |||||||||||||||||||||
| CpmmOutputTotalActivePower | 1.3.6.1.4.1.318.1.1.28.3.2.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Shows the total output active power in tenths of kW. | |||||||||||||||||||||
| CpmmOutputTotalApparentPower | 1.3.6.1.4.1.318.1.1.28.3.2.2.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Shows the total output apparent power in tenths of kVA. | |||||||||||||||||||||
| CpmmOutputTotalPowerFactor | 1.3.6.1.4.1.318.1.1.28.3.2.2.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Indicates the total power factor. A value of 100 representing a unity power factor (1.00). Specified in hundredths. | |||||||||||||||||||||
| CpmmOutputActiveEnergyDelivered | 1.3.6.1.4.1.318.1.1.28.3.2.2.1.6 | Integer32 | RO | mandatory | |||||||||||||||||
column · Integer32 · read-only · mandatory Shows the output active energy delivered in tenths of kWh. | |||||||||||||||||||||
| CpmmOutputActiveEnergyReceived | 1.3.6.1.4.1.318.1.1.28.3.2.2.1.7 | Integer32 | RO | mandatory | |||||||||||||||||
column · Integer32 · read-only · mandatory Shows the output active energy received in tenths of kWh. | |||||||||||||||||||||
| CpmmOutputApparentEnergyDelivered | 1.3.6.1.4.1.318.1.1.28.3.2.2.1.8 | Integer32 | RO | mandatory | |||||||||||||||||
column · Integer32 · read-only · mandatory Shows the output apparent energy delivered in tenths of kVAh. | |||||||||||||||||||||
| CpmmOutputApparentEnergyReceived | 1.3.6.1.4.1.318.1.1.28.3.2.2.1.9 | Integer32 | RO | mandatory | |||||||||||||||||
column · Integer32 · read-only · mandatory Shows the output apparent energy received in tenths of kVAh. | |||||||||||||||||||||
| CpmmOutputFrequencyDeviation | 1.3.6.1.4.1.318.1.1.28.3.2.2.1.10 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Shows the output frequency deviation in Hertz.
| |||||||||||||||||||||
| CpmmOutputPowerFactorDeviation | 1.3.6.1.4.1.318.1.1.28.3.2.2.1.11 | INTEGER (0..100) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..100) · read-write · mandatory Shows the output power factor deviation. Specified in tenths. A value of zero indicates that the threshold is disabled. | |||||||||||||||||||||
| CpmmOutputMinVoltThreshold | 1.3.6.1.4.1.318.1.1.28.3.2.2.1.12 | INTEGER (0..100) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..100) · read-write · mandatory Threshold below which an output minimum voltage condition will be generated. Specified as percent deviation from nominal voltage represented in the OID pmmDeviceNominalOutputVoltage. A value of zero indicates that the threshold is disabled. | |||||||||||||||||||||
| CpmmOutputLowVoltThreshold | 1.3.6.1.4.1.318.1.1.28.3.2.2.1.13 | INTEGER (0..100) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..100) · read-write · mandatory Threshold below which an output low voltage condition will be generated. Specified as percent deviation from nominal voltage represented in the OID pmmDeviceNominalOutputVoltage. A value of zero indicates that the threshold is disabled. | |||||||||||||||||||||
| CpmmOutputHighVoltThreshold | 1.3.6.1.4.1.318.1.1.28.3.2.2.1.14 | INTEGER (0..120) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..120) · read-write · mandatory Threshold above which an output high voltage condition will be generated. Specified as percent deviation from nominal voltage represented in the OID pmmDeviceNominalOutputVoltage. A value of zero indicates that the threshold is disabled. | |||||||||||||||||||||
| CpmmOutputMaxVoltThreshold | 1.3.6.1.4.1.318.1.1.28.3.2.2.1.15 | INTEGER (0..120) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..120) · read-write · mandatory Threshold above which an output maximum voltage condition will be generated. Specified as percent deviation from nominal voltage represented in the OID pmmDeviceNominalOutputVoltage. A value of zero indicates that the threshold is disabled. | |||||||||||||||||||||
| CpmmOutputMinCurrentThreshold | 1.3.6.1.4.1.318.1.1.28.3.2.2.1.16 | INTEGER (0..100) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..100) · read-write · mandatory Threshold below which an output minimum current condition will be generated. Specified as a percent of the panel breaker rating. A value of zero indicates that the threshold is disabled. | |||||||||||||||||||||
| CpmmOutputLowCurrentThreshold | 1.3.6.1.4.1.318.1.1.28.3.2.2.1.17 | INTEGER (0..100) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..100) · read-write · mandatory Threshold below which an output low current condition will be generated. Specified as a percent of the panel breaker rating. A value of zero indicates that the threshold is disabled. | |||||||||||||||||||||
| CpmmOutputHighCurrentThreshold | 1.3.6.1.4.1.318.1.1.28.3.2.2.1.18 | INTEGER (0..110) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..110) · read-write · mandatory Threshold above which an output high current condition will be generated. Specified as a percent of the panel breaker rating. A value of zero indicates that the threshold is disabled. | |||||||||||||||||||||
| CpmmOutputMaxCurrentThreshold | 1.3.6.1.4.1.318.1.1.28.3.2.2.1.19 | INTEGER (0..100) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..100) · read-write · mandatory Threshold above which an output maximum current condition will be generated. Specified as a percent of the panel breaker rating. A value of zero indicates that the threshold is disabled. | |||||||||||||||||||||
| CpmmOutputMinApparentPowerThreshold | 1.3.6.1.4.1.318.1.1.28.3.2.2.1.20 | INTEGER (0..100) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..100) · read-write · mandatory Threshold below which an output minimum apparent power condition will be generated. Specified as a percent deviation from nominal power rating. A value of zero indicates that the threshold is disabled. | |||||||||||||||||||||
| CpmmOutputMaxApparentPowerThreshold | 1.3.6.1.4.1.318.1.1.28.3.2.2.1.21 | INTEGER (0..110) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..110) · read-write · mandatory Threshold above which an output maximum apparent power condition will be generated. Specified as a percent deviation from nominal power rating. A value of zero indicates that the threshold is disabled. | |||||||||||||||||||||
| CpmmOutputOverActivePowerThreshold | 1.3.6.1.4.1.318.1.1.28.3.2.2.1.22 | INTEGER (0..100) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..100) · read-write · mandatory Threshold above which an output over active power condition will be generated. Specified as a percent deviation from nominal power rating. A value of zero indicates that the threshold is disabled. | |||||||||||||||||||||
| CpmmOutputPhaseLossThreshold | 1.3.6.1.4.1.318.1.1.28.3.2.2.1.23 | INTEGER (0..100) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..100) · read-write · mandatory Threshold below which an output phase loss condition will be generated. Specified as a percent deviation from nominal voltage represented in the OID pmmDeviceNominalOutputVoltage. A value of zero indicates that the threshold is disabled. | |||||||||||||||||||||
| CpmmOutputBreakerState | 1.3.6.1.4.1.318.1.1.28.3.2.2.1.24 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This value indicates the current state of output breaker. 1 will indicate open, 2 will indicate closed, 3 will indicate unknown.
| |||||||||||||||||||||
| CpmmOutputBreakerOpenAlarm | 1.3.6.1.4.1.318.1.1.28.3.2.2.1.25 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Breaker open alarm status. 1 will indicate enabled, 2 will indicate disabled, 3 will indicate unknown.
| |||||||||||||||||||||
| TpmmOutputPhaseTable | 1.3.6.1.4.1.318.1.1.28.3.2.3 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of output table entries. The number of entries is given by the value of pmmOutputMeterTableSize OID. | |||||||||||||||||||||
| RpmmOutputPhaseEntry | 1.3.6.1.4.1.318.1.1.28.3.2.3.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular output phase. | |||||||||||||||||||||
| CpmmOutputMeterNum | 1.3.6.1.4.1.318.1.1.28.3.2.3.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The output meter identifier. | |||||||||||||||||||||
| CpmmOutputPhase | 1.3.6.1.4.1.318.1.1.28.3.2.3.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Output phase index. | |||||||||||||||||||||
| CpmmOutputVoltageLtoL | 1.3.6.1.4.1.318.1.1.28.3.2.3.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Line-to-line output voltage available. Measured in tenths of Volts. | |||||||||||||||||||||
| CpmmOutputVoltageLtoN | 1.3.6.1.4.1.318.1.1.28.3.2.3.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Line-to-neutral output voltage available. Measured in tenths of Volts. | |||||||||||||||||||||
| CpmmOutputPhaseCurrent | 1.3.6.1.4.1.318.1.1.28.3.2.3.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Load current per phase. Measured in tenths of Amps. | |||||||||||||||||||||
| CpmmOutputActivePower | 1.3.6.1.4.1.318.1.1.28.3.2.3.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Output power per phase. Measured in tenths of kW. | |||||||||||||||||||||
| CpmmOutputApparentPower | 1.3.6.1.4.1.318.1.1.28.3.2.3.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Output power per phase. Measured in tenths of kVA. | |||||||||||||||||||||
| CpmmOutputPowerFactor | 1.3.6.1.4.1.318.1.1.28.3.2.3.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Indicates the power factor of the output per phase. A value of 100 representing a unity power factor (1.00). Specified in hundredths. | |||||||||||||||||||||
| NpmmBranch | 1.3.6.1.4.1.318.1.1.28.3.3 | ||||||||||||||||||||
| SpmmnumofBranchMeters | 1.3.6.1.4.1.318.1.1.28.3.3.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of branch meters attached to the system. | |||||||||||||||||||||
| SpmmBranchBreakerTableSize | 1.3.6.1.4.1.318.1.1.28.3.3.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of branch breaker entries. | |||||||||||||||||||||
| TpmmBranchBreakerTable | 1.3.6.1.4.1.318.1.1.28.3.3.3 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of branch breaker table entries. The number of entries is contained in the pmmBranchBreakerTableSize OID. | |||||||||||||||||||||
| RpmmBranchBreakerEntry | 1.3.6.1.4.1.318.1.1.28.3.3.3.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular branch breaker (panel/circuit position). | |||||||||||||||||||||
| CpmmBranchCircuitMeterIndex | 1.3.6.1.4.1.318.1.1.28.3.3.3.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Index of branch circuit meter in the table. | |||||||||||||||||||||
| CpmmBranchCircuitIndex | 1.3.6.1.4.1.318.1.1.28.3.3.3.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The branch circuit index. | |||||||||||||||||||||
| CpmmBranchCircuitNumberOfPoles | 1.3.6.1.4.1.318.1.1.28.3.3.3.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The number of poles. | |||||||||||||||||||||
| CpmmBranchCircuitPhase | 1.3.6.1.4.1.318.1.1.28.3.3.3.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The phase associated with branch circuit. | |||||||||||||||||||||
| CpmmBranchCircuitBreakerIdentifier | 1.3.6.1.4.1.318.1.1.28.3.3.3.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The branch circuit identifier. Returns (-1) if not supported. | |||||||||||||||||||||
| CpmmBranchCircuitLoadIdentifier | 1.3.6.1.4.1.318.1.1.28.3.3.3.1.6 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory Identifies the name or location of the branch circuit load. | |||||||||||||||||||||
| CpmmBranchCircuitCurrent | 1.3.6.1.4.1.318.1.1.28.3.3.3.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The branch circuit current Measured in tenths of Amps. | |||||||||||||||||||||
| CpmmBranchCircuitBreakerRating | 1.3.6.1.4.1.318.1.1.28.3.3.3.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The rating of the branch circuit breaker in Amps. | |||||||||||||||||||||
| CpmmBranchCircuitTotalActivePower | 1.3.6.1.4.1.318.1.1.28.3.3.3.1.9 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Branch circuit total active power. Measured in tenths of kW. | |||||||||||||||||||||
| CpmmBranchCircuitTotalApparentPower | 1.3.6.1.4.1.318.1.1.28.3.3.3.1.10 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Branch circuit total apparent power. Measured in tenths of kVA. | |||||||||||||||||||||
| CpmmBranchCircuitEnergyUsage | 1.3.6.1.4.1.318.1.1.28.3.3.3.1.11 | Gauge | RO | mandatory | |||||||||||||||||
column · Gauge · read-only · mandatory Indicates the accumulated energy usage per phase in tenths of kWh. Displayed as 0 when not available or no energy used. | |||||||||||||||||||||
| CpmmBranchCircuitEnergyUsageResetDate | 1.3.6.1.4.1.318.1.1.28.3.3.3.1.12 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory The date that the kWh usage was reset, in the format mm/dd/yyyy. The default energy usage reset date is Not Available. Displayed as NA when breaker is not installed or if not first pole of breaker. | |||||||||||||||||||||
| CpmmBranchCircuitTotalPowerFactor | 1.3.6.1.4.1.318.1.1.28.3.3.3.1.13 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Indicates the total power factor of the branch circuit. A value of 100 representing a unity power factor (1.00) Specified in hundredths. Returns -1 if unsupported. | |||||||||||||||||||||
| CpmmBranchCircuitBreakerState | 1.3.6.1.4.1.318.1.1.28.3.3.3.1.14 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This value indicates the current state of branch circuit breaker. 1 will indicate open, 2 will indicate closed, 3 will indicate unknown.
| |||||||||||||||||||||
| CpmmBranchCircuitMinCurrentThreshold | 1.3.6.1.4.1.318.1.1.28.3.3.3.1.15 | INTEGER (0..100) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..100) · read-write · mandatory Threshold below which a branch circuit minimum current condition will be generated. Specified as a percentage of the branch breaker rating represented in the OID pmmBranchCircuitBreakerRating A value of zero indicates that the threshold is disabled. Threshold write returns as unsuccessful if one of the breaker threshold groups does not meet conditions. In this case, read the thresholds to know which threshold group's write condition is not met. Threshold needs to be enabled to read value | |||||||||||||||||||||
| CpmmBranchCircuitLowCurrentThreshold | 1.3.6.1.4.1.318.1.1.28.3.3.3.1.16 | INTEGER (0..100) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..100) · read-write · mandatory Threshold below which a branch circuit low current condition will be generated. Specified as a percentage of the branch breaker rating represented in the OID pmmBranchCircuitBreakerRating A value of zero indicates that the threshold is disabled. Threshold write returns as unsuccessful if one of the breaker threshold groups does not meet conditions. In this case, read the thresholds to know which threshold group's write condition is not met. Threshold needs to be enabled to read value | |||||||||||||||||||||
| CpmmBranchCircuitHighCurrentThreshold | 1.3.6.1.4.1.318.1.1.28.3.3.3.1.17 | INTEGER (0..100) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..100) · read-write · mandatory Threshold above which a branch circuit high current condition will be generated. Specified as a percentage of the branch breaker rating represented in the OID pmmBranchCircuitBreakerRating A value of zero indicates that the threshold is disabled. Threshold write returns as unsuccessful if one of the breaker threshold groups does not meet conditions. In this case, read the thresholds to know which threshold group's write condition is not met. Threshold needs to be enabled to read value | |||||||||||||||||||||
| CpmmBranchCircuitMaxCurrentThreshold | 1.3.6.1.4.1.318.1.1.28.3.3.3.1.18 | INTEGER (0..100) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..100) · read-write · mandatory Threshold above which a branch circuit maximum current condition will be generated. Specified as a percentage of the branch breaker rating represented in the OID pmmBranchCircuitBreakerRating A value of zero indicates that the threshold is disabled. Threshold write returns as unsuccessful if one of the breaker threshold groups does not meet conditions. In this case, read the thresholds to know which threshold group's write condition is not met. Threshold needs to be enabled to read value | |||||||||||||||||||||
| CpmmBranchCircuitMinApparentPowerThreshold | 1.3.6.1.4.1.318.1.1.28.3.3.3.1.19 | INTEGER (0..100) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..100) · read-write · mandatory Threshold below which a branch circuit minimum apparent power condition will be generated. Specified as a percent of the branch breaker apparent power rating. A value of zero indicates that the threshold is disabled. Threshold write returns as unsuccessful if one of the breaker threshold groups does not meet conditions. In this case, read the thresholds to know which threshold group's write condition is not met. Threshold needs to be enabled to read value | |||||||||||||||||||||
| CpmmBranchCircuitMaxApparentPowerThreshold | 1.3.6.1.4.1.318.1.1.28.3.3.3.1.20 | INTEGER (0..100) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..100) · read-write · mandatory Threshold above which a branch circuit maximum apparent power condition will be generated. Specified as a percent of the branch breaker apparent power rating. A value of zero indicates that the threshold is disabled. Threshold write returns as unsuccessful if one of the breaker threshold groups does not meet conditions. In this case, read the thresholds to know which threshold group's write condition is not met. Threshold needs to be enabled to read value | |||||||||||||||||||||
| CpmmBranchCircuitAlaramGeneration | 1.3.6.1.4.1.318.1.1.28.3.3.3.1.21 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Alarm generation status. 1 will indicate enabled, 2 will indicate disabled, 3 will indicate unknown.
| |||||||||||||||||||||
| CpmmBranchCircuitBreakerOpenAlarm | 1.3.6.1.4.1.318.1.1.28.3.3.3.1.22 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Breaker open alarm status. 1 will indicate enabled, 2 will indicate disabled, 3 will indicate unknown.
| |||||||||||||||||||||
| CpmmBranchCircuitBreakerAverageCurrent | 1.3.6.1.4.1.318.1.1.28.3.3.3.1.23 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Average branch breaker current. Measured in tenths of Amps. | |||||||||||||||||||||
| CpmmBranchCircuitMaxInstantaneousCurrentPhase | 1.3.6.1.4.1.318.1.1.28.3.3.3.1.24 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Branch circuit maximum instantaneous current. Measured in tenths of Amps. | |||||||||||||||||||||
| CpmmBranchCircuitBreakerMaxInstantaneousAverageCurrent | 1.3.6.1.4.1.318.1.1.28.3.3.3.1.25 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Average branch breaker maximum instantaneous current. Measured in tenths of Amps. | |||||||||||||||||||||
| CpmmBranchCircuitAngle | 1.3.6.1.4.1.318.1.1.28.3.3.3.1.26 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Branch circuit phase angle. Measured in tenths of Decimal. | |||||||||||||||||||||
| CpmmBranchCircuitActivePower | 1.3.6.1.4.1.318.1.1.28.3.3.3.1.27 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Branch circuit Active power. Measured in tenths of kW. | |||||||||||||||||||||
| CpmmBranchCircuitApparentPower | 1.3.6.1.4.1.318.1.1.28.3.3.3.1.28 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Branch circuit apparent power. Measured in tenths of kVA. | |||||||||||||||||||||
| CpmmBranchCircuitBreakerEnergyTotalUsage | 1.3.6.1.4.1.318.1.1.28.3.3.3.1.29 | Gauge | RO | mandatory | |||||||||||||||||
column · Gauge · read-only · mandatory Indicates the circuit Breaker total accumulated energy usage in tenths of kWh. Displayed as 0 when not available or no energy used. | |||||||||||||||||||||
| CpmmBranchCircuitPowerFactor | 1.3.6.1.4.1.318.1.1.28.3.3.3.1.30 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Indicates the power factor of the branch circuit. A value of 100 representing a unity power factor (1.00) Specified in hundredths. | |||||||||||||||||||||
| CpmmBranchCircuitTHD | 1.3.6.1.4.1.318.1.1.28.3.3.3.1.31 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Branch circuit current harmonic distortion. Specified in tenths of percent. | |||||||||||||||||||||
| CpmmBranchCircuitBreakerTHD | 1.3.6.1.4.1.318.1.1.28.3.3.3.1.32 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Average branch breaker current harmonic distortion. Specified in tenths of percent. | |||||||||||||||||||||
| CpmmBranchCircuitBreakerLoad | 1.3.6.1.4.1.318.1.1.28.3.3.3.1.33 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Total load on the Breaker. Measured in tenths of Amps. | |||||||||||||||||||||
| CpmmBranchCircuitBranchNumber | 1.3.6.1.4.1.318.1.1.28.3.3.3.1.34 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The branch number. Returns -1 if unsupported or failed. | |||||||||||||||||||||
| CpmmBranchCircuitChannelCTSize | 1.3.6.1.4.1.318.1.1.28.3.3.3.1.35 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The branch CT Size. Returns -1 if unsupported or failed. | |||||||||||||||||||||
| CpmmBranchCircuitCurrentMaxAlarm | 1.3.6.1.4.1.318.1.1.28.3.3.3.1.36 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Current maximum alarm generation status. 1 - enabled 2 - disabled 3 - unknown | |||||||||||||||||||||
| CpmmBranchCircuitCurrentHighAlarm | 1.3.6.1.4.1.318.1.1.28.3.3.3.1.37 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Current high alarm generation status. 1 - enabled 2 - disabled 3 - unknown | |||||||||||||||||||||
| CpmmBranchCircuitCurrentLowAlarm | 1.3.6.1.4.1.318.1.1.28.3.3.3.1.38 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Current low alarm generation status. 1 - enabled 2 - disabled 3 - unknown | |||||||||||||||||||||
| CpmmBranchCircuitCurrentMinAlarm | 1.3.6.1.4.1.318.1.1.28.3.3.3.1.39 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Current minimum alarm generation status. 1 - enabled 2 - disabled 3 - unknown | |||||||||||||||||||||
| CpmmBranchCircuitApparentPowerMaxAlarm | 1.3.6.1.4.1.318.1.1.28.3.3.3.1.40 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Apparent power maximum alarm generation status. 1 - enabled 2 - disabled 3 - unknown | |||||||||||||||||||||
| CpmmBranchCircuitApparentPowerMinAlarm | 1.3.6.1.4.1.318.1.1.28.3.3.3.1.41 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Apparent power minimum alarm generation status. 1 - enabled 2 - disabled 3 - unknown | |||||||||||||||||||||
| NpmmSiteConfig | 1.3.6.1.4.1.318.1.1.28.3.4 | ||||||||||||||||||||
| SpmmSiteConfigTableSize | 1.3.6.1.4.1.318.1.1.28.3.4.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of site configuration set supported by system. | |||||||||||||||||||||
| TpmmSiteConfigTable | 1.3.6.1.4.1.318.1.1.28.3.4.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of PMM site configurable entries. | |||||||||||||||||||||
| RpmmSiteConfigEntry | 1.3.6.1.4.1.318.1.1.28.3.4.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular site configuration.
| |||||||||||||||||||||
| CpmmSiteConfigIndex | 1.3.6.1.4.1.318.1.1.28.3.4.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory PMM site configuration identifier. | |||||||||||||||||||||
| CpmmSiteConfigNominalPtoPVoltage | 1.3.6.1.4.1.318.1.1.28.3.4.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The nominal input phase to phase voltage to the PMM. Measured in Volts, line-to-line for a 3-wire (delta) service or line-to-neutral for a 4-wire (wye) service. | |||||||||||||||||||||
| CpmmSiteConfigNominalPtoNVoltage | 1.3.6.1.4.1.318.1.1.28.3.4.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The nominal input phase to neutral voltage to the PMM. Measured in Volts, line-to-line for a 3-wire (delta) service or line-to-neutral for a 4-wire (wye) service. | |||||||||||||||||||||
| CpmmSiteConfigNominalCurrent | 1.3.6.1.4.1.318.1.1.28.3.4.2.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The nominal input current to the PMM. Measured in tenths of Amps. | |||||||||||||||||||||
| CpmmSiteConfigNominalFrequency | 1.3.6.1.4.1.318.1.1.28.3.4.2.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The nominal input frequency to the PMM. Measured in tenths of Hertz. | |||||||||||||||||||||
| CpmmSiteConfigNominalApparentPower | 1.3.6.1.4.1.318.1.1.28.3.4.2.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The nominal input apparent power to the PMM. Measured in tenths of kVA. | |||||||||||||||||||||
| CpmmSiteConfigServiceType | 1.3.6.1.4.1.318.1.1.28.3.4.2.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The type of utility input to the PMM. Either 3 wires (delta), or 4 wires (wye).
| |||||||||||||||||||||
| SpmmSiteConfigNumberofPanel | 1.3.6.1.4.1.318.1.1.28.3.4.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of panels present. Returns -1 if unsupported or failed. | |||||||||||||||||||||
| SpmmSiteConfigNumberofChannel | 1.3.6.1.4.1.318.1.1.28.3.4.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of channels present. Returns -1 if unsupported or failed. | |||||||||||||||||||||
| SpmmSiteConfigNumberofsources | 1.3.6.1.4.1.318.1.1.28.3.4.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of input sources present. Returns -1 if unsupported or failed. | |||||||||||||||||||||
| SpmmSiteConfigProductModelNumber | 1.3.6.1.4.1.318.1.1.28.3.4.6 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the model number of the RPP. This value is set at the factory. Returns -1 if unsupported or failed. | |||||||||||||||||||||
| SpmmSiteConfigProductSerialNumber | 1.3.6.1.4.1.318.1.1.28.3.4.7 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the serial number of the RPP. This value is set at the factory. Returns -1 if unsupported or failed. | |||||||||||||||||||||
| NpmmConfig | 1.3.6.1.4.1.318.1.1.28.4 | ||||||||||||||||||||
| NpmmInstallBreaker | 1.3.6.1.4.1.318.1.1.28.4.1 | ||||||||||||||||||||
| SpmmInstallBreakerPanelNum | 1.3.6.1.4.1.318.1.1.28.4.1.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Panel number to which breaker is being installed. | |||||||||||||||||||||
| SpmmInstallBreakerChannelNum | 1.3.6.1.4.1.318.1.1.28.4.1.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Channel number to which breaker is being installed. | |||||||||||||||||||||
| SpmmInstallBreakerRating | 1.3.6.1.4.1.318.1.1.28.4.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Breaker rating in Amperes of breaker being installed. | |||||||||||||||||||||
| SpmmInstallBreakerPoles | 1.3.6.1.4.1.318.1.1.28.4.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Number of poles of breaker being installed. | |||||||||||||||||||||
| SpmmInstallBreakerInstall | 1.3.6.1.4.1.318.1.1.28.4.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Set as 1 to add breaker once breaker related data points have been set. | |||||||||||||||||||||
| NpmmUninstallBreaker | 1.3.6.1.4.1.318.1.1.28.4.2 | ||||||||||||||||||||
| SpmmUninstallBreakerPanelNum | 1.3.6.1.4.1.318.1.1.28.4.2.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Panel number from which breaker is being uninstalled. | |||||||||||||||||||||
| SpmmUninstallBreakerChannelNum | 1.3.6.1.4.1.318.1.1.28.4.2.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Channel number from which breaker is being uninstalled. | |||||||||||||||||||||
| SpmmUninstallBreakerUninstall | 1.3.6.1.4.1.318.1.1.28.4.2.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Set as 1 to delete breaker once breaker related data points have been set. | |||||||||||||||||||||
| Ncharger | 1.3.6.1.4.1.318.1.1.29 | ||||||||||||||||||||
| NchargerIdent | 1.3.6.1.4.1.318.1.1.29.1 | ||||||||||||||||||||
| SchargerIdentModel | 1.3.6.1.4.1.318.1.1.29.1.1 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the model name of the Charger. This value is set at the factory. If not supported, return null string (\0). | |||||||||||||||||||||
| SchargerBasicIdentName | 1.3.6.1.4.1.318.1.1.29.1.2 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory An 8 byte ID string identifying the Charger. This object can be set by the administrator. | |||||||||||||||||||||
| SchargerIdentSerialNumber | 1.3.6.1.4.1.318.1.1.29.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the serial number of the Charger. This value is set at the factory. If not supported, return null string (\0). | |||||||||||||||||||||
| SchargerIdentModelType | 1.3.6.1.4.1.318.1.1.29.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The detailed model information of the Charger. If not supported, return null string (\0). | |||||||||||||||||||||
| NchargerInput | 1.3.6.1.4.1.318.1.1.29.2 | ||||||||||||||||||||
| TchargerInputPhaseTable | 1.3.6.1.4.1.318.1.1.29.2.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of input table entries. The number of entries is given by the sum of the Charger input phases. | |||||||||||||||||||||
| RchargerInputPhaseEntry | 1.3.6.1.4.1.318.1.1.29.2.1.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular input phase. | |||||||||||||||||||||
| CchargerInputPhaseTableIndex | 1.3.6.1.4.1.318.1.1.29.2.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The input identifier. If not supported, return 0. | |||||||||||||||||||||
| CchargerInputPhaseVoltage | 1.3.6.1.4.1.318.1.1.29.2.1.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The input voltage in VAC, or -1 if it's unsupported by this Charger. | |||||||||||||||||||||
| CchargerInputPhaseMinVoltage | 1.3.6.1.4.1.318.1.1.29.2.1.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The lowest input voltage to the Charger during the previous minute of operation, or -1 if it's unsupported by this Charger. | |||||||||||||||||||||
| CchargerInputPhaseMaxVoltage | 1.3.6.1.4.1.318.1.1.29.2.1.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The highest input voltage to the Charger during the previous minute of operation, or -1 if it's unsupported by this Charger. | |||||||||||||||||||||
| CchargerInputPhaseCurrent | 1.3.6.1.4.1.318.1.1.29.2.1.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The input current in 0.1 amperes, or -1 if it's unsupported by this Charger. | |||||||||||||||||||||
| NchargerOutput | 1.3.6.1.4.1.318.1.1.29.3 | ||||||||||||||||||||
| SchargerOutputStatus | 1.3.6.1.4.1.318.1.1.29.3.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The current state of the Charger. If the Charger is unable to determine the state of the Charger, this variable is set to unknown(1). If the charger is not present, the variable is set to chargernotpresent(9)
| |||||||||||||||||||||
| SchargerOutputVauxVoltage | 1.3.6.1.4.1.318.1.1.29.3.2 | Gauge | RO | mandatory | |||||||||||||||||
scalar · Gauge · read-only · mandatory The Load output voltage, measured in VDC. | |||||||||||||||||||||
| SchargerOutputTotalCurrent | 1.3.6.1.4.1.318.1.1.29.3.3 | Gauge | RO | mandatory | |||||||||||||||||
scalar · Gauge · read-only · mandatory The current, in amperes, drawn by the load on the charger. | |||||||||||||||||||||
| SchargerOutputLoad | 1.3.6.1.4.1.318.1.1.29.3.4 | Gauge | RO | mandatory | |||||||||||||||||
scalar · Gauge · read-only · mandatory The current Charger load expressed in percent of the total rated current of the charger. | |||||||||||||||||||||
| NePDU | 1.3.6.1.4.1.318.1.1.30 | ||||||||||||||||||||
| SePDUDeviceStatusTableSize | 1.3.6.1.4.1.318.1.1.30.1 | INTEGER | RO | mandatory | 3 | ||||||||||||||||
scalar · INTEGER · read-only · mandatory The total number of Easy PDUs Example values from LibreNMS test devices
| |||||||||||||||||||||
| NePDUDevice | 1.3.6.1.4.1.318.1.1.30.2 | ||||||||||||||||||||
| TePDUDeviceStatusTable | 1.3.6.1.4.1.318.1.1.30.2.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A table of Easy PDU status information | |||||||||||||||||||||
| RePDUDeviceStatusEntry | 1.3.6.1.4.1.318.1.1.30.2.1.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory Status information from the Easy PDU being queried | |||||||||||||||||||||
| CePDUDeviceStatusIndex | 1.3.6.1.4.1.318.1.1.30.2.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the Easy PDU status table entry | |||||||||||||||||||||
| CePDUDeviceStatusModule | 1.3.6.1.4.1.318.1.1.30.2.1.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The user-defined Rack PDU numeric ID | |||||||||||||||||||||
| CePDUDeviceStatusVersion | 1.3.6.1.4.1.318.1.1.30.2.1.1.3 | DisplayString | RO | mandatory | Ver11.10 | ||||||||||||||||
column · DisplayString · read-only · mandatory The Easy PDU firmware and hardware version Example values from LibreNMS test devices
| |||||||||||||||||||||
| CePDUDeviceStatusModelNumber | 1.3.6.1.4.1.318.1.1.30.2.1.1.4 | DisplayString | RO | mandatory | EPDU1116S | ||||||||||||||||
column · DisplayString · read-only · mandatory The Easy PDU model number Example values from LibreNMS test devices
| |||||||||||||||||||||
| CePDUDeviceStatusSerialNumber | 1.3.6.1.4.1.318.1.1.30.2.1.1.5 | DisplayString | RO | mandatory | 506255602541 | ||||||||||||||||
column · DisplayString · read-only · mandatory The Easy PDU serial number Example values from LibreNMS test devices
| |||||||||||||||||||||
| CePDUDeviceStatusNumPhases | 1.3.6.1.4.1.318.1.1.30.2.1.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The number of phases present in the Easy PDU | |||||||||||||||||||||
| CePDUDeviceStatusActivePower | 1.3.6.1.4.1.318.1.1.30.2.1.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Indicates the PDU Active Power. Units:1 Watt. Models that do not support this feature, will respond to this OID with a value of notSupported (-1). | |||||||||||||||||||||
| CePDUDeviceStatusReactivePower | 1.3.6.1.4.1.318.1.1.30.2.1.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Indicates the PDU Reactive Power. Units:1 Var. Models that do not support this feature, will respond to this OID with a value of notSupported (-1). | |||||||||||||||||||||
| CePDUDeviceStatusApparentPower | 1.3.6.1.4.1.318.1.1.30.2.1.1.9 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Indicates the PDU Apparent Power. Units:1 VA. Models that do not support this feature, will respond to this OID with a value of notSupported (-1). | |||||||||||||||||||||
| CePDUDeviceStatusPowerFactor | 1.3.6.1.4.1.318.1.1.30.2.1.1.10 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Indicates the PDU Power Factor. Units:0.1%. Models that do not support this feature, will respond to this OID with a value of notSupported (-1). | |||||||||||||||||||||
| CePDUDeviceStatusEnergy | 1.3.6.1.4.1.318.1.1.30.2.1.1.11 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Indicates the PDU Energy. Units:1 Wh. Models that do not support this feature, will respond to this OID with a value of notSupported (-1). | |||||||||||||||||||||
| CePDUDeviceStatusFrequency | 1.3.6.1.4.1.318.1.1.30.2.1.1.12 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Indicates the PDU Frequency. Units:0.001 Hz. Models that do not support this feature, will respond to this OID with a value of notSupported (-1). | |||||||||||||||||||||
| TePDUDeviceControlTable | 1.3.6.1.4.1.318.1.1.30.2.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A table of Easy PDU control data | |||||||||||||||||||||
| RePDUDeviceControlEntry | 1.3.6.1.4.1.318.1.1.30.2.2.1 | NA | mandatory | ||||||||||||||||||
| CePDUDeviceControlIndex | 1.3.6.1.4.1.318.1.1.30.2.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the Easy PDU control table entry | |||||||||||||||||||||
| CePDUDeviceControlModule | 1.3.6.1.4.1.318.1.1.30.2.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The user-defined Easy PDU numeric ID | |||||||||||||||||||||
| CePDUDeviceControlReboot | 1.3.6.1.4.1.318.1.1.30.2.2.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Setting this OID to reboot (1) will cause the device reboot immediately. Getting this OID in models that support this feature will do nothing and return the noOperation(0) value.
| |||||||||||||||||||||
| CePDUDeviceControlEnergyReset | 1.3.6.1.4.1.318.1.1.30.2.2.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Setting this OID to reset (1) will cause the device energy meter value to be reset to zero. Getting this OID in models that support this feature will do nothing and return the noOperation(0) value.
| |||||||||||||||||||||
| CePDUDeviceControlBeepAlarm | 1.3.6.1.4.1.318.1.1.30.2.2.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory User-defined Beep alarm, 1 for turn off Beep, 2 for turn on Beep. Models that do not support this feature will respond to this OID with a value of -1.
| |||||||||||||||||||||
| SePDUPhaseTableSize | 1.3.6.1.4.1.318.1.1.30.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of connected Easy PDU phases | |||||||||||||||||||||
| NePDUPhase | 1.3.6.1.4.1.318.1.1.30.4 | ||||||||||||||||||||
| TePDUPhaseConfigTable | 1.3.6.1.4.1.318.1.1.30.4.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A table of Easy PDU phase configuration data | |||||||||||||||||||||
| RePDUPhaseConfigEntry | 1.3.6.1.4.1.318.1.1.30.4.1.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory Configuration data from currently queried Easy PDU phase
| |||||||||||||||||||||
| CePDUPhaseConfigIndex | 1.3.6.1.4.1.318.1.1.30.4.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the Easy PDU phase configuration table entry | |||||||||||||||||||||
| CePDUPhaseConfigModule | 1.3.6.1.4.1.318.1.1.30.4.1.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The user-defined Easy PDU numeric ID | |||||||||||||||||||||
| CePDUPhaseConfigNumber | 1.3.6.1.4.1.318.1.1.30.4.1.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The numeric phase ID | |||||||||||||||||||||
| CePDUPhaseConfigOverVoltageThreshold | 1.3.6.1.4.1.318.1.1.30.4.1.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory User-defined Phase Over Voltage alarm threshold. Units:0.1 V. Models that do not support this feature will respond to this OID with a value of -1. | |||||||||||||||||||||
| CePDUPhaseConfigLowVoltageThreshold | 1.3.6.1.4.1.318.1.1.30.4.1.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory User-defined Phase Low Voltage alarm threshold. Units:0.1 V. Models that do not support this feature will respond to this OID with a value of -1. | |||||||||||||||||||||
| CePDUPhaseConfigOverCurrentThreshold | 1.3.6.1.4.1.318.1.1.30.4.1.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory User-defined Phase Over Current alarm threshold. Units:0.01 A. Models that do not support this feature will respond to this OID with a value of -1. | |||||||||||||||||||||
| CePDUPhaseConfigLowCurrentThreshold | 1.3.6.1.4.1.318.1.1.30.4.1.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory User-defined Phase Low Current alarm threshold. Units:0.01 A. Models that do not support this feature will respond to this OID with a value of -1. | |||||||||||||||||||||
| TePDUPhaseStatusTable | 1.3.6.1.4.1.318.1.1.30.4.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A table of Rack PDU phase status data | |||||||||||||||||||||
| RePDUPhaseStatusEntry | 1.3.6.1.4.1.318.1.1.30.4.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory Status data from currently queried Easy PDU phase
| |||||||||||||||||||||
| CePDUPhaseStatusIndex | 1.3.6.1.4.1.318.1.1.30.4.2.1.1 | INTEGER (1..12) | RO | mandatory | |||||||||||||||||
column · INTEGER (1..12) · read-only · mandatory The index to the Easy PDU phase configuration table entry | |||||||||||||||||||||
| CePDUPhaseStatusModule | 1.3.6.1.4.1.318.1.1.30.4.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The user-defined Easy PDU numeric ID | |||||||||||||||||||||
| CePDUPhaseStatusNumber | 1.3.6.1.4.1.318.1.1.30.4.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The numeric phase ID | |||||||||||||||||||||
| CePDUPhaseStatusVoltage | 1.3.6.1.4.1.318.1.1.30.4.2.1.4 | INTEGER | RO | mandatory | 0 | ||||||||||||||||
column · INTEGER · read-only · mandatory Indicates the Phase Voltage. Units:0.1 V Example values from LibreNMS test devices
| |||||||||||||||||||||
| CePDUPhaseStatusCurrent | 1.3.6.1.4.1.318.1.1.30.4.2.1.5 | INTEGER | RO | mandatory | 0 | ||||||||||||||||
column · INTEGER · read-only · mandatory Indicates the Phase Current. Units:0.01 A Example values from LibreNMS test devices
| |||||||||||||||||||||
| CePDUPhaseStatusActivePower | 1.3.6.1.4.1.318.1.1.30.4.2.1.6 | INTEGER | RO | mandatory | 0 | ||||||||||||||||
column · INTEGER · read-only · mandatory Indicates the Phase Active Power. Units:1 Watt Example values from LibreNMS test devices
| |||||||||||||||||||||
| CePDUPhaseStatusReactivePower | 1.3.6.1.4.1.318.1.1.30.4.2.1.7 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Indicates the Phase Reactive Power. Units:1 Var. Models that do not support this feature, will respond to this OID with a value of notSupported (-1). | |||||||||||||||||||||
| CePDUPhaseStatusApparentPower | 1.3.6.1.4.1.318.1.1.30.4.2.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Indicates the Phase Apparent Power. Units:1 VA. Models that do not support this feature, will respond to this OID with a value of notSupported (-1). | |||||||||||||||||||||
| CePDUPhaseStatusPowerFactor | 1.3.6.1.4.1.318.1.1.30.4.2.1.9 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Indicates the Phase Power Factor. Units:0.1% | |||||||||||||||||||||
| CePDUPhaseStatusEnergy | 1.3.6.1.4.1.318.1.1.30.4.2.1.10 | INTEGER | RO | mandatory | 332241 | ||||||||||||||||
column · INTEGER · read-only · mandatory Indicates the Phase Energy. Units:1 Wh Example values from LibreNMS test devices
| |||||||||||||||||||||
| SePDUOutletTableSize | 1.3.6.1.4.1.318.1.1.30.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of switched outlets on connected Easy PDUs. | |||||||||||||||||||||
| NePDUOutlet | 1.3.6.1.4.1.318.1.1.30.6 | ||||||||||||||||||||
| TePDUOutletStatusTable | 1.3.6.1.4.1.318.1.1.30.6.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory The number of switched outlets on connected Rack PDUs | |||||||||||||||||||||
| RePDUOutletStatusEntry | 1.3.6.1.4.1.318.1.1.30.6.1.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory Switched Outlet status from currently queried Easy PDU switched outlet | |||||||||||||||||||||
| CePDUOutletStatusIndex | 1.3.6.1.4.1.318.1.1.30.6.1.1.1 | INTEGER (1..128) | RO | mandatory | |||||||||||||||||
column · INTEGER (1..128) · read-only · mandatory The index to the Easy PDU switched outlet status information table entry. Models that do not support this feature, will respond to this OID with a value of notSupported (-1). | |||||||||||||||||||||
| CePDUOutletStatusModule | 1.3.6.1.4.1.318.1.1.30.6.1.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The user-defined Easy PDU numeric ID. Models that do not support this feature, will respond to this OID with a value of notSupported (-1). | |||||||||||||||||||||
| CePDUOutletStatusNumber | 1.3.6.1.4.1.318.1.1.30.6.1.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The numeric switched outlet ID. Models that do not support this feature, will respond to this OID with a value of notSupported (-1). | |||||||||||||||||||||
| CePDUOutletStatusState | 1.3.6.1.4.1.318.1.1.30.6.1.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Indicates the present switch state of the Easy PDU switched outlet being queried. Models that do not support this feature, will respond to this OID with a value of notSupported (-1).
| |||||||||||||||||||||
| TePDUOutletControlTable | 1.3.6.1.4.1.318.1.1.30.6.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A table of Easy PDU switched outlet control data | |||||||||||||||||||||
| RePDUOutletControlEntry | 1.3.6.1.4.1.318.1.1.30.6.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory Control data for currently queried Easy PDU switched outlet | |||||||||||||||||||||
| CePDUOutletControlIndex | 1.3.6.1.4.1.318.1.1.30.6.2.1.1 | INTEGER (1..128) | RO | mandatory | |||||||||||||||||
column · INTEGER (1..128) · read-only · mandatory The index to the Easy PDU switched outlet configuration table entry. Models that do not support this feature, will respond to this OID with a value of notSupported (-1). | |||||||||||||||||||||
| CePDUOutletControlModule | 1.3.6.1.4.1.318.1.1.30.6.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The user-defined Easy PDU numeric ID. Models that do not support this feature, will respond to this OID with a value of notSupported (-1). | |||||||||||||||||||||
| CePDUOutletControlNumber | 1.3.6.1.4.1.318.1.1.30.6.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The numeric switched outlet ID. Models that do not support this feature, will respond to this OID with a value of notSupported (-1). | |||||||||||||||||||||
| CePDUOutletControlCommand | 1.3.6.1.4.1.318.1.1.30.6.2.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Getting this variable will return the outlet state. If the outlet is on, the immediateOn (1) value will be returned. If the outlet is off, the immediateOff (2) value will be returned. If the state of the outlet cannot be determined, the outletUnknown (3) value will be returned. If the outletUnknown condition should occur, all devices powered by the PDU should be shut down. The PDU's power should then be cycled to clear this condition. Models that do not support this feature, will respond to this OID with a value of notSupported (-1). Setting this variable to immediateOn (1) will immediately turn the outlet on. Setting this variable to immediateOff (2) will immediately turn the outlet off.
| |||||||||||||||||||||
| SePDUSensorTableSize | 1.3.6.1.4.1.318.1.1.30.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of connected temperature-humidity sensors | |||||||||||||||||||||
| NePDUSensor | 1.3.6.1.4.1.318.1.1.30.8 | ||||||||||||||||||||
| TePDUSensorConfigTable | 1.3.6.1.4.1.318.1.1.30.8.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A table of temperature-humidity sensor configuration data | |||||||||||||||||||||
| RePDUSensorConfigEntry | 1.3.6.1.4.1.318.1.1.30.8.1.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory Configuration data from temperature-humidity sensor being queried | |||||||||||||||||||||
| CePDUSensorConfigIndex | 1.3.6.1.4.1.318.1.1.30.8.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to the temperature-humidity sensor configuration data table entry | |||||||||||||||||||||
| CePDUSensorConfigModule | 1.3.6.1.4.1.318.1.1.30.8.1.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The user-defined Easy PDU numeric ID | |||||||||||||||||||||
| CePDUSensorConfigTempMaxThreshold | 1.3.6.1.4.1.318.1.1.30.8.1.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory User-defined Max Temperature alarm threshold. Units: 0.1 degrees Celsius. Models that do not support this feature will respond to this OID with a value of -1. | |||||||||||||||||||||
| CePDUSensorConfigTempMinThreshold | 1.3.6.1.4.1.318.1.1.30.8.1.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory User-defined Min Temperature alarm threshold. Units: 0.1 degrees Celsius. Models that do not support this feature will respond to this OID with a value of -1. | |||||||||||||||||||||
| CePDUSensorConfigHumidityMaxThreshold | 1.3.6.1.4.1.318.1.1.30.8.1.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory User-defined Max Humidity alarm threshold. Units: 0.1% relative humidity. Models that do not support this feature will respond to this OID with a value of -1. | |||||||||||||||||||||
| CePDUSensorConfigHumidityMinThreshold | 1.3.6.1.4.1.318.1.1.30.8.1.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory User-defined Min Humidity alarm threshold. Units: 0.1% relative humidity. Models that do not support this feature will respond to this OID with a value of -1. | |||||||||||||||||||||
| TePDUSensorStatusTable | 1.3.6.1.4.1.318.1.1.30.8.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A table of temperature-humidity sensor status data | |||||||||||||||||||||
| RePDUSensorStatusEntry | 1.3.6.1.4.1.318.1.1.30.8.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory Status information from temperature-humidity sensor being queried | |||||||||||||||||||||
| CePDUSensorStatusIndex | 1.3.6.1.4.1.318.1.1.30.8.2.1.1 | INTEGER (1..4) | RO | mandatory | |||||||||||||||||
column · INTEGER (1..4) · read-only · mandatory The index to the temperature-humidity status data table entry | |||||||||||||||||||||
| CePDUSensorStatusModule | 1.3.6.1.4.1.318.1.1.30.8.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The user-defined Easy PDU numeric ID | |||||||||||||||||||||
| CePDUSensorStatusTemperature | 1.3.6.1.4.1.318.1.1.30.8.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Sensor temperature reading in tenths of degrees Celsius. | |||||||||||||||||||||
| CePDUSensorStatusHumidity | 1.3.6.1.4.1.318.1.1.30.8.2.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Sensor humidity reading in 0.1 percent relative humidity. | |||||||||||||||||||||
| Nmdc | 1.3.6.1.4.1.318.1.1.31 | ||||||||||||||||||||
| NmdcIdent | 1.3.6.1.4.1.318.1.1.31.1 | ||||||||||||||||||||
| SmdcIdentProductName | 1.3.6.1.4.1.318.1.1.31.1.1 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The name of the MDC. | |||||||||||||||||||||
| SmdcIdentHMIModelNumber | 1.3.6.1.4.1.318.1.1.31.1.2 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The HMI model number | |||||||||||||||||||||
| SmdcIdentHMISerialNumber | 1.3.6.1.4.1.318.1.1.31.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the serial number of the HMI. This value is set at the factory. | |||||||||||||||||||||
| SmdcIdentHMIHardwareRev | 1.3.6.1.4.1.318.1.1.31.1.4 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The hardware revision of the HMI. This value is set at the factory. | |||||||||||||||||||||
| SmdcIdentHMIDateOfManufacture | 1.3.6.1.4.1.318.1.1.31.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The date when the HMI was manufactured in mm/dd/yyyy format. This value is set at the factory. | |||||||||||||||||||||
| SmdcIdentHMIFirmwareAppRev | 1.3.6.1.4.1.318.1.1.31.1.6 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory An ID string identifying the HMI application firmware revision of the MDC. | |||||||||||||||||||||
| SmdcIdentHMIFirmwareAppOSRev | 1.3.6.1.4.1.318.1.1.31.1.7 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory An ID string identifying the HMI application operating system firmware revision of the MDC. | |||||||||||||||||||||
| SmdcIdentModelNumber | 1.3.6.1.4.1.318.1.1.31.1.8 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory The Micro DC model number | |||||||||||||||||||||
| SmdcIdentSerialNumber | 1.3.6.1.4.1.318.1.1.31.1.9 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory A character string identifying the serial number of the MDC. This value is set at the factory. | |||||||||||||||||||||
| NmdcUps | 1.3.6.1.4.1.318.1.1.31.2 | ||||||||||||||||||||
| NmdcUpsNum | 1.3.6.1.4.1.318.1.1.31.2.1 | ||||||||||||||||||||
| SmdcUpsNumUnits | 1.3.6.1.4.1.318.1.1.31.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The value indicates the number of UPS present. | |||||||||||||||||||||
| NmdcUpsInput | 1.3.6.1.4.1.318.1.1.31.2.2 | ||||||||||||||||||||
| TmdcUpsInputTable | 1.3.6.1.4.1.318.1.1.31.2.2.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of UPS input table entries. The number of entries is given by the value of mdcUpsNumUnits. | |||||||||||||||||||||
| RmdcUpsInputEntry | 1.3.6.1.4.1.318.1.1.31.2.2.1.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular input of UPS. | |||||||||||||||||||||
| CmdcUpsInputTableIndex | 1.3.6.1.4.1.318.1.1.31.2.2.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The UPS identifier. | |||||||||||||||||||||
| CmdcUpsInputVoltage | 1.3.6.1.4.1.318.1.1.31.2.2.1.1.2 | Gauge | RO | mandatory | |||||||||||||||||
column · Gauge · read-only · mandatory The current utility line voltage in VAC. | |||||||||||||||||||||
| NmdcUpsOutput | 1.3.6.1.4.1.318.1.1.31.2.3 | ||||||||||||||||||||
| TmdcUpsOutputTable | 1.3.6.1.4.1.318.1.1.31.2.3.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of UPS output table entries. The number of entries is given by the value of mdcUpsNumUnits. | |||||||||||||||||||||
| RmdcUpsOutputEntry | 1.3.6.1.4.1.318.1.1.31.2.3.1.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a output of particular UPS. | |||||||||||||||||||||
| CmdcUpsOutputTableIndex | 1.3.6.1.4.1.318.1.1.31.2.3.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The UPS identifier. | |||||||||||||||||||||
| CmdcUpsOutputVoltage | 1.3.6.1.4.1.318.1.1.31.2.3.1.1.2 | Gauge | RO | mandatory | |||||||||||||||||
column · Gauge · read-only · mandatory The output voltage of the UPS system in VAC. | |||||||||||||||||||||
| CmdcUpsOutputCurrent | 1.3.6.1.4.1.318.1.1.31.2.3.1.1.3 | Gauge | RO | mandatory | |||||||||||||||||
column · Gauge · read-only · mandatory The current in amperes drawn by the load on the UPS. | |||||||||||||||||||||
| CmdcUpsOutputActivePower | 1.3.6.1.4.1.318.1.1.31.2.3.1.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The total output active power of the UPS system in W. | |||||||||||||||||||||
| CmdcUpsOutputFrequency | 1.3.6.1.4.1.318.1.1.31.2.3.1.1.5 | Gauge | RO | mandatory | |||||||||||||||||
column · Gauge · read-only · mandatory The current output frequency of the UPS system in Hz. | |||||||||||||||||||||
| NmdcUpsBattery | 1.3.6.1.4.1.318.1.1.31.2.4 | ||||||||||||||||||||
| TmdcUpsBatteryTable | 1.3.6.1.4.1.318.1.1.31.2.4.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory Table of Battery details. The number of entries is given by the value of mdcUpsNumUnits. | |||||||||||||||||||||
| RmdcUpsBatteryEntry | 1.3.6.1.4.1.318.1.1.31.2.4.1.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to battery of individual UPS. | |||||||||||||||||||||
| CmdcUpsBatteryTableIndex | 1.3.6.1.4.1.318.1.1.31.2.4.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The UPS identifier. | |||||||||||||||||||||
| CmdcUpsBatteryRunTimeRemaining | 1.3.6.1.4.1.318.1.1.31.2.4.1.1.2 | TimeTicks | RO | mandatory | |||||||||||||||||
column · TimeTicks · read-only · mandatory The UPS battery run time remaining before battery exhaustion. | |||||||||||||||||||||
| CmdcUpsBatteryCapacity | 1.3.6.1.4.1.318.1.1.31.2.4.1.1.3 | Gauge | RO | mandatory | |||||||||||||||||
column · Gauge · read-only · mandatory The remaining battery capacity expressed in percent of full capacity. | |||||||||||||||||||||
| NmdcCooling | 1.3.6.1.4.1.318.1.1.31.3 | ||||||||||||||||||||
| NmdcCoolingNum | 1.3.6.1.4.1.318.1.1.31.3.1 | ||||||||||||||||||||
| SmdcCoolingNumUnits | 1.3.6.1.4.1.318.1.1.31.3.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The value indicates the number of cooling units present. | |||||||||||||||||||||
| NmdcCoolingStatus | 1.3.6.1.4.1.318.1.1.31.3.2 | ||||||||||||||||||||
| TmdcCoolingStatusTable | 1.3.6.1.4.1.318.1.1.31.3.2.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of cooling status table entries. The number of entries is given by the value of mdcCoolingNumUnits. | |||||||||||||||||||||
| RmdcCoolingStatusEntry | 1.3.6.1.4.1.318.1.1.31.3.2.1.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular status of cooling unit. | |||||||||||||||||||||
| CmdcCoolingStatusTableIndex | 1.3.6.1.4.1.318.1.1.31.3.2.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The cooling unit identifier. | |||||||||||||||||||||
| CmdcCoolingStatusSupplyAirTemp | 1.3.6.1.4.1.318.1.1.31.3.2.1.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The unit supply air temperature in degree Celsius. | |||||||||||||||||||||
| CmdcCoolingStatusReturnAirTemp | 1.3.6.1.4.1.318.1.1.31.3.2.1.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The unit return air temperature in degree Celsius. | |||||||||||||||||||||
| CmdcCoolingStatusOperateMode | 1.3.6.1.4.1.318.1.1.31.3.2.1.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The cooling unit operating mode.
| |||||||||||||||||||||
| NmdcCoolingConfig | 1.3.6.1.4.1.318.1.1.31.3.3 | ||||||||||||||||||||
| SmdcCoolingConfigRackMaxTemp | 1.3.6.1.4.1.318.1.1.31.3.3.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Rack maximum temperature set point in degree Celsius. | |||||||||||||||||||||
| SmdcCoolingConfigRackMinHum | 1.3.6.1.4.1.318.1.1.31.3.3.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Rack minimum humidity set point in %RH. | |||||||||||||||||||||
| SmdcCoolingConfigUPSMinLoad | 1.3.6.1.4.1.318.1.1.31.3.3.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory UPS minimum load set point in Watts. | |||||||||||||||||||||
| TmdcCoolingConfigTable | 1.3.6.1.4.1.318.1.1.31.3.3.4 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of cooling configuration table entries. The number of entries is given by the value of mdcCoolingNumUnits. | |||||||||||||||||||||
| RmdcCoolingConfigEntry | 1.3.6.1.4.1.318.1.1.31.3.3.4.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to configuration of particular cooling unit. | |||||||||||||||||||||
| CmdcCoolingConfigTableIndex | 1.3.6.1.4.1.318.1.1.31.3.3.4.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The cooling unit identifier. | |||||||||||||||||||||
| CmdcCoolingConfigOutletAirTemp | 1.3.6.1.4.1.318.1.1.31.3.3.4.1.2 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Outlet air temperature set point. This OID represents the value sent to the particular cooling unit in degree Celsius. | |||||||||||||||||||||
| CmdcCoolingConfigPTCHeater | 1.3.6.1.4.1.318.1.1.31.3.3.4.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The status of PTC heater of particular cooling unit.
| |||||||||||||||||||||
| CmdcCoolingConfigCondensationpump | 1.3.6.1.4.1.318.1.1.31.3.3.4.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The status of condensation pump of particular cooling unit.
| |||||||||||||||||||||
| NmdcStatus | 1.3.6.1.4.1.318.1.1.31.4 | ||||||||||||||||||||
| SmdcStatusPowerUsageEffectiveness | 1.3.6.1.4.1.318.1.1.31.4.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The Power Usage Effectiveness of MDC, the vaule displayed in tenths. Returns -1 if not supported. | |||||||||||||||||||||
| NmdcMeter | 1.3.6.1.4.1.318.1.1.31.5 | ||||||||||||||||||||
| NmdcMeterNum | 1.3.6.1.4.1.318.1.1.31.5.1 | ||||||||||||||||||||
| SmdcMeterNumUnits | 1.3.6.1.4.1.318.1.1.31.5.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The value indicates the number of meters present. | |||||||||||||||||||||
| NmdcMeterStatus | 1.3.6.1.4.1.318.1.1.31.5.2 | ||||||||||||||||||||
| TmdcMeterStatusTable | 1.3.6.1.4.1.318.1.1.31.5.2.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of meter status table entries. The number of entries is given by the value of mdcMeterNumUnits. | |||||||||||||||||||||
| RmdcMeterStatusEntry | 1.3.6.1.4.1.318.1.1.31.5.2.1.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to a particular status of meter. | |||||||||||||||||||||
| CmdcMeterStatusTableIndex | 1.3.6.1.4.1.318.1.1.31.5.2.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The meter identifier. | |||||||||||||||||||||
| CmdcMeterFrequency | 1.3.6.1.4.1.318.1.1.31.5.2.1.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The frequency in Hertz. | |||||||||||||||||||||
| CmdcMeterVoltage | 1.3.6.1.4.1.318.1.1.31.5.2.1.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The voltage in Volts as measured by the meter. | |||||||||||||||||||||
| CmdcMeterCurrent | 1.3.6.1.4.1.318.1.1.31.5.2.1.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The current in Amps as measured by the meter. | |||||||||||||||||||||
| CmdcMeterActivePower | 1.3.6.1.4.1.318.1.1.31.5.2.1.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Shows the active power measured by the meter in hundreths of kW. | |||||||||||||||||||||
| CmdcMeterApparentPower | 1.3.6.1.4.1.318.1.1.31.5.2.1.1.6 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory Shows the apparent power measured by the meter in hundreths of kVA. | |||||||||||||||||||||
| NmdcMeterConfig | 1.3.6.1.4.1.318.1.1.31.5.3 | ||||||||||||||||||||
| TmdcMeterConfigTable | 1.3.6.1.4.1.318.1.1.31.5.3.1 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of meter configuration table entries. The number of entries is given by the value of mdcMeterNumUnits. | |||||||||||||||||||||
| RmdcMeterConfigEntry | 1.3.6.1.4.1.318.1.1.31.5.3.1.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information applicable to configuration of particular meter. | |||||||||||||||||||||
| CmdcMeterConfigTableIndex | 1.3.6.1.4.1.318.1.1.31.5.3.1.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The meter identifier. | |||||||||||||||||||||
| CmdcMeterMinVoltThreshold | 1.3.6.1.4.1.318.1.1.31.5.3.1.1.2 | INTEGER (0..100) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..100) · read-write · mandatory Threshold below which an input minimum voltage condition will be generated. Specified as percent deviation from nominal voltage. | |||||||||||||||||||||
| CmdcMeterLowVoltThreshold | 1.3.6.1.4.1.318.1.1.31.5.3.1.1.3 | INTEGER (0..100) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..100) · read-write · mandatory Threshold below which an input low voltage condition will be generated. Specified as percent deviation from nominal voltage. | |||||||||||||||||||||
| CmdcMeterHighVoltThreshold | 1.3.6.1.4.1.318.1.1.31.5.3.1.1.4 | INTEGER (0..120) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..120) · read-write · mandatory Threshold above which an input high voltage condition will be generated. Specified as percent deviation from nominal voltage. | |||||||||||||||||||||
| CmdcMeterMaxVoltThreshold | 1.3.6.1.4.1.318.1.1.31.5.3.1.1.5 | INTEGER (0..120) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..120) · read-write · mandatory Threshold above which an input maximum voltage condition will be generated. Specified as percent deviation from nominal voltage. | |||||||||||||||||||||
| CmdcMeterMinCurrentThreshold | 1.3.6.1.4.1.318.1.1.31.5.3.1.1.6 | INTEGER (0..100) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..100) · read-write · mandatory Threshold below which an input minimum current condition will be generated. | |||||||||||||||||||||
| CmdcMeterLowCurrentThreshold | 1.3.6.1.4.1.318.1.1.31.5.3.1.1.7 | INTEGER (0..100) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..100) · read-write · mandatory Threshold below which an input low current condition will be generated. | |||||||||||||||||||||
| CmdcMeterHighCurrentThreshold | 1.3.6.1.4.1.318.1.1.31.5.3.1.1.8 | INTEGER (0..110) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..110) · read-write · mandatory Threshold above which an input high current condition will be generated. | |||||||||||||||||||||
| CmdcMeterMaxCurrentThreshold | 1.3.6.1.4.1.318.1.1.31.5.3.1.1.9 | INTEGER (0..100) | RW | mandatory | |||||||||||||||||
column · INTEGER (0..100) · read-write · mandatory Threshold above which an input maximum current condition will be generated. | |||||||||||||||||||||
| NcPDU | 1.3.6.1.4.1.318.1.1.32 | ||||||||||||||||||||
| Nats5g | 1.3.6.1.4.1.318.1.1.33 | ||||||||||||||||||||
| Sats5gNumDevices | 1.3.6.1.4.1.318.1.1.33.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory This value is the number of devices in the network port sharing (NPS) group (the size of ats5gDeviceIdentTable, ats5gDeviceSwitchTable, and ats5gDeviceEnvironmentTable). | |||||||||||||||||||||
| Tats5gDeviceIdentTable | 1.3.6.1.4.1.318.1.1.33.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory This table organizes the identifying data of devices in the device group. | |||||||||||||||||||||
| Rats5gDeviceIdentEntry | 1.3.6.1.4.1.318.1.1.33.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory This entry organizes the identity data of a single device. | |||||||||||||||||||||
| Cats5gIdentDeviceIndex | 1.3.6.1.4.1.318.1.1.33.2.1.1 | INTEGER (1..65535) | RO | mandatory | |||||||||||||||||
column · INTEGER (1..65535) · read-only · mandatory This value is the data entry's index in the identity table. | |||||||||||||||||||||
| Cats5gIdentConfigModuleID | 1.3.6.1.4.1.318.1.1.33.2.1.2 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory This value is ID number that can be configured for each device. It cannot be greater than the maximum number of devices in the network port sharing (NPS) group (32). Changing this value causes the device to reboot, which will likely result in an SNMP timeout error even when the write attempt is successful. | |||||||||||||||||||||
| Cats5gIdentModuleType | 1.3.6.1.4.1.318.1.1.33.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This value describes the role the specified device holds in the device group: notNPS(1) specifies that the device is not in a group host(2) specifies that a device will broadcast firmware updates to guests guest(3) specifies that a device will accept firmware updates from the host
| |||||||||||||||||||||
| Cats5gIdentModuleStatus | 1.3.6.1.4.1.318.1.1.33.2.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This value tracks the communication status of a device within the group.
| |||||||||||||||||||||
| Cats5gIdentSerialNumber | 1.3.6.1.4.1.318.1.1.33.2.1.5 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory This is the serial number of the automatic transfer switch. | |||||||||||||||||||||
| Cats5gIdentModelNumber | 1.3.6.1.4.1.318.1.1.33.2.1.6 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory This is the model number of the automatic transfer switch. | |||||||||||||||||||||
| Cats5gIdentHardwareRev | 1.3.6.1.4.1.318.1.1.33.2.1.7 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory This is the hardware revision of the automatic transfer switch. | |||||||||||||||||||||
| Cats5gIdentManufactureDate | 1.3.6.1.4.1.318.1.1.33.2.1.8 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory This is the manufacture date of the automatic transfer switch. | |||||||||||||||||||||
| Cats5gIdentBootmonRev | 1.3.6.1.4.1.318.1.1.33.2.1.9 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory This is the boot monitor firmware revision of the network management card. | |||||||||||||||||||||
| Cats5gIdentAOSRev | 1.3.6.1.4.1.318.1.1.33.2.1.10 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory This is the operating system firmware revision of the network management card. | |||||||||||||||||||||
| Cats5gIdentAppRev | 1.3.6.1.4.1.318.1.1.33.2.1.11 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory This is the application firmware revision of the network management card. | |||||||||||||||||||||
| Cats5gIdentConfigName | 1.3.6.1.4.1.318.1.1.33.2.1.12 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory This is the configurable name of the device. It may be up to 255 characters long. | |||||||||||||||||||||
| Cats5gIdentConfigLocation | 1.3.6.1.4.1.318.1.1.33.2.1.13 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory This is the configurable location of the device. It may be up to 255 characters long. | |||||||||||||||||||||
| Cats5gIdentConfigContact | 1.3.6.1.4.1.318.1.1.33.2.1.14 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory This is the configurable contact information of the device. It may be up to 255 characters long. | |||||||||||||||||||||
| Tats5gDeviceSwitchTable | 1.3.6.1.4.1.318.1.1.33.3 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory This table organizes the data specific to the automatic transfer switch. | |||||||||||||||||||||
| Rats5gDeviceSwitchEntry | 1.3.6.1.4.1.318.1.1.33.3.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory This entry organizes the switch data of a single device. | |||||||||||||||||||||
| Cats5gSwitchDeviceIndex | 1.3.6.1.4.1.318.1.1.33.3.1.1 | INTEGER (1..65535) | RO | mandatory | |||||||||||||||||
column · INTEGER (1..65535) · read-only · mandatory This value is the data entry's index in the switching table. | |||||||||||||||||||||
| Cats5gSwitchModuleID | 1.3.6.1.4.1.318.1.1.33.3.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This value is the ats5gIdentConfigModuleID of the device being queried. | |||||||||||||||||||||
| Cats5gSwitchOrientation | 1.3.6.1.4.1.318.1.1.33.3.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This value describes the voltage orientation of the ATS.
| |||||||||||||||||||||
| Cats5gSwitchCumulativeAlarmStatus | 1.3.6.1.4.1.318.1.1.33.3.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This is the severity of the most severe alarm currently active.
| |||||||||||||||||||||
| Cats5gSwitchCommunicationStatus | 1.3.6.1.4.1.318.1.1.33.3.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This is the communication status between the network management card and the automatic transfer switch.
| |||||||||||||||||||||
| Cats5gSwitchConfigFrontPanelLockout | 1.3.6.1.4.1.318.1.1.33.3.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory This is the configurable lockout status of the source preference toggle button on the front panel. The button does nothing while the front panel is locked.
| |||||||||||||||||||||
| Cats5gSwitchConfigPreferredSource | 1.3.6.1.4.1.318.1.1.33.3.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory This is the configurable source preference. If the ATS is fully redundant the preferred source will be the selected source. If the preferred source is none(3), the ATS will switch sources only in response to measured changes in each source.
| |||||||||||||||||||||
| Cats5gSwitchSelectedSource | 1.3.6.1.4.1.318.1.1.33.3.1.8 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This is the selected source that will be used to power downstream devices.
| |||||||||||||||||||||
| Cats5gSwitchRedundancyState | 1.3.6.1.4.1.318.1.1.33.3.1.9 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This is the ATS redundancy status. While this value is atsFullyRedundant(2), either input may be used to power downstream devices. While this value is atsRedundancyLost(1), one input has failed validation and downstream devices may lose power if the selected source is lost.
| |||||||||||||||||||||
| Cats5gSwitchSourceAStatus | 1.3.6.1.4.1.318.1.1.33.3.1.10 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This is the input status of source A. The ATS will use source B as the selected source while this value is fail(1).
| |||||||||||||||||||||
| Cats5gSwitchSourceBStatus | 1.3.6.1.4.1.318.1.1.33.3.1.11 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This is the input status of source B. The ATS will use source A as the selected source while this value is fail(1).
| |||||||||||||||||||||
| Cats5gSwitchRatedVoltage | 1.3.6.1.4.1.318.1.1.33.3.1.12 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This is the default nominal line VRMS in volts (V) for this unit. | |||||||||||||||||||||
| Cats5gSwitchConfigNominalVoltage | 1.3.6.1.4.1.318.1.1.33.3.1.13 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory This is the configurable line VRMS in volts (V) that will be used to select sources. | |||||||||||||||||||||
| Cats5gSwitchConfigTransferVoltageRange | 1.3.6.1.4.1.318.1.1.33.3.1.14 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory This value specifies which voltage transfer range should be used to disqualify sources and raise alarms. The narrow transfer voltage must be less than the medium transfer voltage, which must be less than the wide transfer voltage. If the difference between ats5gSwitchConfigNominalVoltage and a source's measured VRMS is greater than the value specified by the selected transfer range, the ATS will disqualify that source. The ATS will be in a 'lost redundancy' state until the source recovers or the configuration is updated.
| |||||||||||||||||||||
| Cats5gSwitchConfigTransferVoltageWide | 1.3.6.1.4.1.318.1.1.33.3.1.15 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory This is the configurable transfer range in volts (V) used to disqualify sources when ats5gSwitchConfigTransferVoltageRange is wide(1). | |||||||||||||||||||||
| Cats5gSwitchConfigTransferVoltageMedium | 1.3.6.1.4.1.318.1.1.33.3.1.16 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory This is the configurable transfer range in volts (V) used to disqualify sources when ats5gSwitchConfigTransferVoltageRange is medium(2). | |||||||||||||||||||||
| Cats5gSwitchConfigTransferVoltageNarrow | 1.3.6.1.4.1.318.1.1.33.3.1.17 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory This is the configurable transfer range in volts (V) used to disqualify sources when ats5gSwitchConfigTransferVoltageRange is narrow(3). | |||||||||||||||||||||
| Cats5gSwitchConfigVoltageSensitivity | 1.3.6.1.4.1.318.1.1.33.3.1.18 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory This is the configured sensitivity threshold for rapid changes to input voltage. It is recommended to use high(1) unless frequent small changes are expected.
| |||||||||||||||||||||
| Cats5gSwitchSourceAVoltage | 1.3.6.1.4.1.318.1.1.33.3.1.19 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This is the measured line VRMS of source A reported in volts (V). | |||||||||||||||||||||
| Cats5gSwitchSourceBVoltage | 1.3.6.1.4.1.318.1.1.33.3.1.20 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This is the measured line VRMS of source B reported in volts (V). | |||||||||||||||||||||
| Cats5gSwitchRatedFrequency | 1.3.6.1.4.1.318.1.1.33.3.1.21 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This is the default nominal line frequency for this unit reported in Hertz (Hz). | |||||||||||||||||||||
| Cats5gSwitchConfigNominalFrequency | 1.3.6.1.4.1.318.1.1.33.3.1.22 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory This is the configurable line frequency in Hertz (Hz) that will be used to select sources. If the difference between ats5gSwitchConfigNominalFrequency and a source's measured frequency is greater than ats5gSwitchConfigFrequencyDeviation, the ATS will disqualify that source. The ATS will be in a 'lost redundancy' state until the source recovers or the configuration is updated. | |||||||||||||||||||||
| Cats5gSwitchConfigFrequencyDeviation | 1.3.6.1.4.1.318.1.1.33.3.1.23 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory This is the configurable frequency deviation in Hertz (Hz) that will be used to select sources.
| |||||||||||||||||||||
| Cats5gSwitchSourceAFrequency | 1.3.6.1.4.1.318.1.1.33.3.1.24 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This is the measured line frequency of source A reported in Hertz (Hz). | |||||||||||||||||||||
| Cats5gSwitchSourceBFrequency | 1.3.6.1.4.1.318.1.1.33.3.1.25 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This is the measured line frequency of source B reported in Hertz (Hz). | |||||||||||||||||||||
| Cats5gSwitchEventCountStartTime | 1.3.6.1.4.1.318.1.1.33.3.1.26 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory This value is the time and date of the last event count reset action. | |||||||||||||||||||||
| Cats5gSwitchEventCountRedundancyLoss | 1.3.6.1.4.1.318.1.1.33.3.1.27 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This value tracks the number of redundancy loss events. It increments each time a source becomes invalid. | |||||||||||||||||||||
| Cats5gSwitchEventCountSourceSwitch | 1.3.6.1.4.1.318.1.1.33.3.1.28 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This value tracks the number of source switch events. It increments each time the selected source changes. | |||||||||||||||||||||
| Cats5gSwitchEventCountSourcePrefChange | 1.3.6.1.4.1.318.1.1.33.3.1.29 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This value tracks the number of preferred source configuration change events. It increments each time the user updates their source preference. | |||||||||||||||||||||
| Cats5gSwitchEventCountSpikeOrDrop | 1.3.6.1.4.1.318.1.1.33.3.1.30 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This value tracks voltage spike and drop events. It increments each time a source's measured instantaneous voltage increases or decreases rapidly. This depends on configured voltage sensitivity. | |||||||||||||||||||||
| Cats5gSwitchEventCountSurgeOrDroop | 1.3.6.1.4.1.318.1.1.33.3.1.31 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This value tracks voltage surge or droop events. It increments each time a source's calculated VRMS increases or decreases rapidly. This does not depend on any user configurations. | |||||||||||||||||||||
| Cats5gSwitchEventCountFreqOutOfRange | 1.3.6.1.4.1.318.1.1.33.3.1.32 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This value tracks frequency threshold violations. It increments each time a source is disqualified because the difference between its measured frequency and the configured nominal frequency is greater than the configured frequency deviation. | |||||||||||||||||||||
| Cats5gSwitchControlEventCountReset | 1.3.6.1.4.1.318.1.1.33.3.1.33 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory This control resets the event counts when the value is set to reset(2).
| |||||||||||||||||||||
| Cats5gSwitchVoltageOutStatus | 1.3.6.1.4.1.318.1.1.33.3.1.34 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This value is on(2) while the output outlets are powered.
| |||||||||||||||||||||
| Cats5gSwitchOverCurrentState | 1.3.6.1.4.1.318.1.1.33.3.1.35 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This value is atsOverCurrent(1) when the ATS has exceeded the output current threshold and will not allow a switch over to the alternate power source if the current source fails.
| |||||||||||||||||||||
| Cats5gSwitchPhaseSyncStatus | 1.3.6.1.4.1.318.1.1.33.3.1.36 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This value tracks the phase sync status.
| |||||||||||||||||||||
| Cats5gSwitchSourceA24VSupplyStatus | 1.3.6.1.4.1.318.1.1.33.3.1.37 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This value tracks the internal source A 24VDC power supply status.
| |||||||||||||||||||||
| Cats5gSwitchSourceB24VSupplyStatus | 1.3.6.1.4.1.318.1.1.33.3.1.38 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This value tracks the internal source B 24VDC power supply status.
| |||||||||||||||||||||
| Cats5gSwitchSourceA48VSupplyStatus | 1.3.6.1.4.1.318.1.1.33.3.1.39 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This value tracks the internal source A 48VDC power supply status.
| |||||||||||||||||||||
| Cats5gSwitchSourceB48VSupplyStatus | 1.3.6.1.4.1.318.1.1.33.3.1.40 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This value tracks the internal source B 48VDC power supply status.
| |||||||||||||||||||||
| Cats5gSwitch3p3VSupplyStatus | 1.3.6.1.4.1.318.1.1.33.3.1.41 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This value tracks the internal 3.3VDC power supply status.
| |||||||||||||||||||||
| Tats5gDeviceEnvironmentTable | 1.3.6.1.4.1.318.1.1.33.4 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory This table organizes the data specific to the environment monitoring accessories. | |||||||||||||||||||||
| Rats5gDeviceEnvironmentEntry | 1.3.6.1.4.1.318.1.1.33.4.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory This entry organizes the switch data of a single device.
| |||||||||||||||||||||
| Cats5gEnvDeviceIndex | 1.3.6.1.4.1.318.1.1.33.4.1.1 | INTEGER (1..65535) | RO | mandatory | |||||||||||||||||
column · INTEGER (1..65535) · read-only · mandatory This value is the data entry's index in the environment table. | |||||||||||||||||||||
| Cats5gEnvModuleID | 1.3.6.1.4.1.318.1.1.33.4.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This value is the ats5gIdentConfigModuleID of the device being queried. | |||||||||||||||||||||
| Cats5gEnvSensorType | 1.3.6.1.4.1.318.1.1.33.4.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This value is the type of the currently attached sensor accessory.
| |||||||||||||||||||||
| Cats5gEnvAlarmStatus | 1.3.6.1.4.1.318.1.1.33.4.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This is the severity of the most severe environment-specific alarm currently active.
| |||||||||||||||||||||
| Cats5gEnvTemperature | 1.3.6.1.4.1.318.1.1.33.4.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This is the measured temperature of the attached sensor reported in tenth-degrees Fahrenheit. The value reports as -1 if the attached sensor does not support temperature measurements. | |||||||||||||||||||||
| Cats5gEnvConfigTempMaxThreshold | 1.3.6.1.4.1.318.1.1.33.4.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory This is the configured maximum temperature threshold reported in degrees Fahrenheit. The value reports as -1 if the attached sensor does not support temperature measurements. | |||||||||||||||||||||
| Cats5gEnvConfigTempHighThreshold | 1.3.6.1.4.1.318.1.1.33.4.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory This is the configured high temperature threshold reported in degrees Fahrenheit. The value reports as -1 if the attached sensor does not support temperature measurements. | |||||||||||||||||||||
| Cats5gEnvConfigTempHysteresis | 1.3.6.1.4.1.318.1.1.33.4.1.8 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory This is the configured temperature threshold hysteresis reported in degrees Fahrenheit. The value reports as -1 if the attached sensor does not support temperature measurements. | |||||||||||||||||||||
| Cats5gEnvConfigTempAlarmsEnabled | 1.3.6.1.4.1.318.1.1.33.4.1.9 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory This is the configured temperature monitoring status. While this value is disabled(1), no temperature-related alarms will be active. The value reports as -1 if the attached sensor does not support temperature measurements.
| |||||||||||||||||||||
| Cats5gEnvHumidity | 1.3.6.1.4.1.318.1.1.33.4.1.10 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This is the measured humidity around the attached sensor reported in percent relative humidity. The value reports as -1 if the attached sensor does not support humidity measurements. | |||||||||||||||||||||
| Cats5gEnvConfigHumLowThreshold | 1.3.6.1.4.1.318.1.1.33.4.1.11 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory This is the configured low humidity threshold reported in %RH. The value reports as -1 if the attached sensor does not support humidity measurements. | |||||||||||||||||||||
| Cats5gEnvConfigHumMinThreshold | 1.3.6.1.4.1.318.1.1.33.4.1.12 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory This is the configured minimum humidity threshold reported in %RH. The value reports as -1 if the attached sensor does not support humidity measurements. | |||||||||||||||||||||
| Cats5gEnvConfigHumHysteresis | 1.3.6.1.4.1.318.1.1.33.4.1.13 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory This is the configured humidity threshold hysteresis reported in %RH. The value reports as -1 if the attached sensor does not support humidity measurements. | |||||||||||||||||||||
| Cats5gEnvConfigHumAlarmsEnabled | 1.3.6.1.4.1.318.1.1.33.4.1.14 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory This is the configured humidity monitoring status. While this value is disabled(1), no humidity-related alarms will be active. The value reports as -1 if the attached sensor does not support humidity measurements.
| |||||||||||||||||||||
| Cats5gEnvPeakTemperature | 1.3.6.1.4.1.318.1.1.33.4.1.15 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This is the highest temperature recorded since the last peak temperature reset, reported in degrees Fahrenheit. | |||||||||||||||||||||
| Cats5gEnvPeakTempTime | 1.3.6.1.4.1.318.1.1.33.4.1.16 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory This is the date and time that the peak temperature was recorded. | |||||||||||||||||||||
| Cats5gEnvPeakTempResetTime | 1.3.6.1.4.1.318.1.1.33.4.1.17 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory This is the date and time that the peak temperature was last reset. | |||||||||||||||||||||
| Cats5gEnvControlPeakTempReset | 1.3.6.1.4.1.318.1.1.33.4.1.18 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory This control resets the peak temperature when the value is set to reset(2).
| |||||||||||||||||||||
| Sats5gBankTableSize | 1.3.6.1.4.1.318.1.1.33.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory This value is the number of metered loads in the NPS group (the size of ats5gBankTable). | |||||||||||||||||||||
| Tats5gBankTable | 1.3.6.1.4.1.318.1.1.33.6 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory This table organizes the bank data of devices in the device group. | |||||||||||||||||||||
| Rats5gBankEntry | 1.3.6.1.4.1.318.1.1.33.6.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory This entry organizes the bank data of a single device.
| |||||||||||||||||||||
| Cats5gBankIndex | 1.3.6.1.4.1.318.1.1.33.6.1.1 | INTEGER (1..65535) | RO | mandatory | |||||||||||||||||
column · INTEGER (1..65535) · read-only · mandatory This value is the data entry's index in the bank table. | |||||||||||||||||||||
| Cats5gBankModuleID | 1.3.6.1.4.1.318.1.1.33.6.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This value is the ats5gIdentConfigModuleID of the device being queried. | |||||||||||||||||||||
| Cats5gBankType | 1.3.6.1.4.1.318.1.1.33.6.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This value describes the type of bank associated with this bank index. If a device has multiple banks, then its total(1) output will include the bank1(2) and bank2(3) outputs.
| |||||||||||||||||||||
| Cats5gBankRatedAmps | 1.3.6.1.4.1.318.1.1.33.6.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This value is the rated output of the specified bank reported in amps (A). | |||||||||||||||||||||
| Cats5gBankOutputTenthAmps | 1.3.6.1.4.1.318.1.1.33.6.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This value is the measured output of the specified bank reported in tenths of amps (A). | |||||||||||||||||||||
| Cats5gBankConfigLowLoadThreshold | 1.3.6.1.4.1.318.1.1.33.6.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory This value is the configured low load threshold of the specified bank reported in amps (A). | |||||||||||||||||||||
| Cats5gBankConfigNearOverLoadThreshold | 1.3.6.1.4.1.318.1.1.33.6.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory This value is the configured near overload threshold of the specified bank reported in amps (A). | |||||||||||||||||||||
| Cats5gBankConfigOverloadThreshold | 1.3.6.1.4.1.318.1.1.33.6.1.8 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory This value is the configured overload threshold of the specified bank reported in amps (A). | |||||||||||||||||||||
| Cats5gBankApparentPower | 1.3.6.1.4.1.318.1.1.33.6.1.9 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This value is the calculated apparent power of the specified bank reported in kilovolt-amps (kVA). | |||||||||||||||||||||
| Cats5gBankOutputCurrentStatus | 1.3.6.1.4.1.318.1.1.33.6.1.10 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory This value tracks the load status of the specified bank.
| |||||||||||||||||||||
| Nsoftware | 1.3.6.1.4.1.318.1.2 | ||||||||||||||||||||
| NpowerNetSubAgent | 1.3.6.1.4.1.318.1.2.1 | ||||||||||||||||||||
| NpowerNetSoftwareSystem | 1.3.6.1.4.1.318.1.2.1.1 | ||||||||||||||||||||
| SpowerNetSoftwareSystemDescription | 1.3.6.1.4.1.318.1.2.1.1.1 | DisplayString (SIZE (0..79)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..79)) · read-only · mandatory A brief description of the PowerNet sub-agent. | |||||||||||||||||||||
| SpowerNetSoftwareOid | 1.3.6.1.4.1.318.1.2.1.1.2 | OBJECT IDENTIFIER | RO | mandatory | |||||||||||||||||
scalar · OBJECT IDENTIFIER · read-only · mandatory The object identifier of the PowerNet sub-agent. | |||||||||||||||||||||
| SpowerNetSoftwareSystemUpTime | 1.3.6.1.4.1.318.1.2.1.1.3 | TimeTicks | RO | mandatory | |||||||||||||||||
scalar · TimeTicks · read-only · mandatory The time that the sub-agent has been running. | |||||||||||||||||||||
| NpowerNetSoftwareConfig | 1.3.6.1.4.1.318.1.2.1.2 | ||||||||||||||||||||
| SpowerNetSoftwareTableSize | 1.3.6.1.4.1.318.1.2.1.2.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of software modules supporting the UPS. | |||||||||||||||||||||
| TpowerNetSoftwareTable | 1.3.6.1.4.1.318.1.2.1.2.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of the software monitoring the UPS. | |||||||||||||||||||||
| RpowerNetSoftwareEntry | 1.3.6.1.4.1.318.1.2.1.2.2.1 | NA | mandatory | ||||||||||||||||||
row · not-accessible · mandatory An entry containing information on a software module.
| |||||||||||||||||||||
| CmoduleNumber | 1.3.6.1.4.1.318.1.2.1.2.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index into the Software Entry Table | |||||||||||||||||||||
| CmoduleName | 1.3.6.1.4.1.318.1.2.1.2.2.1.2 | DisplayString (SIZE (0..79)) | RO | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..79)) · read-only · mandatory The name of the software module. | |||||||||||||||||||||
| CmoduleVersion | 1.3.6.1.4.1.318.1.2.1.2.2.1.3 | DisplayString (SIZE (0..8)) | RO | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..8)) · read-only · mandatory The version of the software module. | |||||||||||||||||||||
| CmoduleDate | 1.3.6.1.4.1.318.1.2.1.2.2.1.4 | DisplayString (SIZE (0..9)) | RO | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..9)) · read-only · mandatory The date of the software module represented as mm-dd-yy. | |||||||||||||||||||||
| NstruxureWareOperations | 1.3.6.1.4.1.318.1.2.2 | ||||||||||||||||||||
| NstruxureWareOperationsStatus | 1.3.6.1.4.1.318.1.2.2.1 | ||||||||||||||||||||
| SserverStatus | 1.3.6.1.4.1.318.1.2.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The status of the StruxureWare Operations server: 1: The status of the application server is unknown. Check Webmin and if the problem persists, contact Technical Support. 2: Restart the StruxureWare DC Operation server. If the server was part of a cluster, see the StruxureWare DC Operation User Assistance about rejoining the cluster. If the problem persists, contact Technical Support. 3: No problem. 4: High availability is lost. The StruxureWare DC Operation Application server is running but one or more nodes are not available. If the StruxureWare DC Operation server is part of a cluster, ensure all nodes are running and there is a network connection between the nodes. If the problem persists, contact Technical Support. 5: Wait for the StruxureWare DC Operation Application server to initialize. If the problem persists, contact Technical Support. 6: Wait for the StruxureWare DC Operation Application server to finish starting. If the problem persists, contact Technical Support. 7: This node is running in Disaster Recovery mode. 8: The JBoss postoffice is currently inconsistent. This may be a temporary issue. If the problem persists for more than 10 minutes, contact Technical Support. 9: The JBoss is missing jgroups. This may be a temporary issue. If the problem persists for more than 10 minutes, contact Technical Support.
| |||||||||||||||||||||
| SdatabaseStatus | 1.3.6.1.4.1.318.1.2.2.1.2 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The status of the StruxureWare Operations database: 1: The status of the database is unknown. Check Webmin and if the problem persists, contact Technical Support. 2: Restart the StruxureWare DC Operation server. If the server was part of a cluster, see the StruxureWare DC Operation User Assistance about rejoining the cluster. If the problem persists, contact Technical Support. 3: No problem. 4: High availability is lost. The database is detached from the cluster and does not receive updates. See the StruxureWare DC Operation User Assistance about reattaching the database node to the StruxureWare DC Operation cluster. If the problem persists, contact Technical Support. 5: The database is catching up with the cluster. Wait for the StruxureWare DC Operation database to retrieve all updates from the master node. If the problem persists, contact Technical Support. 6: The database is attaching to the cluster. Wait for the StruxureWare Operation database to attach to the cluster. If the problem persists, contact Technical Support. 7: The database is the master in a cluster. 8: The database is the primary slave in the cluster. All changes on master are synchronously replicated to this node. 9: The database is a secondary slave in the cluster. All changes on master are asynchronously replicated to this node. 10: The database does not replicate its changes to other nodes.
| |||||||||||||||||||||
| SloadBalancerStatus | 1.3.6.1.4.1.318.1.2.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The status of the StruxureWare Operations load balancer: 1: Load Balancer status is unknown. Check Webmin and if the problem persists, contact Technical Support. 2: Load Balancer stopped. Restart the StruxureWare DC Operation server. If the problem persists, contact Technical Support. 3: Normal status 4: High availability is lost. The StruxureWare DC Operation Load Balancer is running but one or more nodes are not available. If the StruxureWare DC Operation server is part of a cluster, ensure all nodes are running and there is a network connection between the nodes. If the problem persists, contact Technical Support.
| |||||||||||||||||||||
| SessentialServicesStatus | 1.3.6.1.4.1.318.1.2.2.1.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The status of the StruxureWare Operations essential services: 1: Unknown status. Check Webmin and if the problem persists, contact Technical Support. 2: Essential services are not running on the StruxureWare DC Operation server. Reboot the node and monitor the status page in Webmin. If the problem persists, contact Technical Support. 3: Normal status 4: The time difference between the StruxureWare DC Operation slave and the master node is too big. Correct the time on the slave to match the time on the master. Consider using an NTP server. If the problem persists, contact Technical Support. 5: The last backup that was attempted on the StruxureWare DC Operation server has failed. Make certain that the system can write to the location specified as backup location. This is particularly relevant for network attached storage. If the problem persists, contact Technical Support.
| |||||||||||||||||||||
| SetlStatus | 1.3.6.1.4.1.318.1.2.2.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The status of the StruxureWare Operations ETL services: 1: Unknown status. Check the network configuration and the server network settings. If the problem persists, contact Technical Support (http://www.apc.com/go/direct/index.cfm?tag=support). 2: Normal status, 3: ETL Transformations have failed and are subsequently stopped. Investigate the cause of the failure. If the problem persists, contact Technical Support (http://www.apc.com/go/direct/index.cfm?tag=support). 4: ETL Transformations are currently paused. 5: ETL Transformations are currently stopped.
| |||||||||||||||||||||
| NpowerChuteNetworkShutdown | 1.3.6.1.4.1.318.1.2.3 | ||||||||||||||||||||
| NpcnsIdent | 1.3.6.1.4.1.318.1.2.3.1 | ||||||||||||||||||||
| Spcnshostname | 1.3.6.1.4.1.318.1.2.3.1.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The hostname of the PCNS instance. | |||||||||||||||||||||
| SpcnsVersion | 1.3.6.1.4.1.318.1.2.3.1.2 | DisplayString (SIZE (0..9)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..9)) · read-only · mandatory The version of PCNS installed. x.x.x | |||||||||||||||||||||
| SpcnsOS | 1.3.6.1.4.1.318.1.2.3.1.3 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The version of OS PCNS is Installed on. | |||||||||||||||||||||
| SpcnsJavaVersion | 1.3.6.1.4.1.318.1.2.3.1.4 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The version of Java PCNS is running on. | |||||||||||||||||||||
| NpcnsNetworking | 1.3.6.1.4.1.318.1.2.3.2 | ||||||||||||||||||||
| SpcnsUIProtocol | 1.3.6.1.4.1.318.1.2.3.2.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Web Protocol used to connect to the PCNS UI.
| |||||||||||||||||||||
| SpcnsHttpPort | 1.3.6.1.4.1.318.1.2.3.2.2 | INTEGER (0..65535) | RO | mandatory | |||||||||||||||||
scalar · INTEGER (0..65535) · read-only · mandatory Port used for PCNS http UI. | |||||||||||||||||||||
| SpcnsHttpsPort | 1.3.6.1.4.1.318.1.2.3.2.3 | INTEGER (0..65535) | RO | mandatory | |||||||||||||||||
scalar · INTEGER (0..65535) · read-only · mandatory Port used for PCNS https UI. | |||||||||||||||||||||
| SpcnsNetworkConfig | 1.3.6.1.4.1.318.1.2.3.2.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Configuration of the TCP Network.
| |||||||||||||||||||||
| SpcnsVirtualInstall | 1.3.6.1.4.1.318.1.2.3.2.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Virtualization technology in use by PCNS.
| |||||||||||||||||||||
| NpcnsNMC | 1.3.6.1.4.1.318.1.2.3.3 | ||||||||||||||||||||
| SpcnsMode | 1.3.6.1.4.1.318.1.2.3.3.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Configuration mode of the UPS(s) which PCNS is monitoring.
| |||||||||||||||||||||
| SpcnsNMCPort | 1.3.6.1.4.1.318.1.2.3.3.2 | INTEGER (0..65535) | RO | mandatory | |||||||||||||||||
scalar · INTEGER (0..65535) · read-only · mandatory Port used to connect to all of the Network Management Card(s). | |||||||||||||||||||||
| SpcnsNMCProtocol | 1.3.6.1.4.1.318.1.2.3.3.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Web Protocol used to connect to all of the Network Management Card(s).
| |||||||||||||||||||||
| TpcnsNmcTable | 1.3.6.1.4.1.318.1.2.3.3.4 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory The Network Management Cards in the UPS devices, which PCNS is monitoring to provide safe shutdown. | |||||||||||||||||||||
| RpcnsNmcEntry | 1.3.6.1.4.1.318.1.2.3.3.4.1 | NA | mandatory | ||||||||||||||||||
| CpcnsNmcIndex | 1.3.6.1.4.1.318.1.2.3.3.4.1.1 | Gauge | RO | mandatory | |||||||||||||||||
column · Gauge · read-only · mandatory Index of the NMC within PCNS setup. | |||||||||||||||||||||
| CpcnsNmcAddr | 1.3.6.1.4.1.318.1.2.3.3.4.1.2 | IpAddress | RO | mandatory | |||||||||||||||||
column · IpAddress · read-only · mandatory The IP address of the NMC. | |||||||||||||||||||||
| CpcnsNmcOutlet | 1.3.6.1.4.1.318.1.2.3.3.4.1.3 | Gauge | RO | mandatory | |||||||||||||||||
column · Gauge · read-only · mandatory The Outlet Group which PCNS is enrolled with on the NMC. | |||||||||||||||||||||
| NpcnsEvents | 1.3.6.1.4.1.318.1.2.3.4 | ||||||||||||||||||||
| NpcnsPowerFailed | 1.3.6.1.4.1.318.1.2.3.4.1 | ||||||||||||||||||||
| SpcnsPowerFailedDesc | 1.3.6.1.4.1.318.1.2.3.4.1.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The Description of the event. | |||||||||||||||||||||
| SpcnsPowerFailedEnableLogging | 1.3.6.1.4.1.318.1.2.3.4.1.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Log occurrences of this event in PCNS log.
| |||||||||||||||||||||
| SpcnsPowerFailedEnableCommandFile | 1.3.6.1.4.1.318.1.2.3.4.1.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Execute a command file when this event occurs.
| |||||||||||||||||||||
| SpcnsPowerFailedCommandFilePath | 1.3.6.1.4.1.318.1.2.3.4.1.4 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory Path of command file to execute when this event occurs. | |||||||||||||||||||||
| SpcnsPowerFailedCommandFileDelay | 1.3.6.1.4.1.318.1.2.3.4.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before executing command file (seconds). | |||||||||||||||||||||
| SpcnsPowerFailedEnableShutdown | 1.3.6.1.4.1.318.1.2.3.4.1.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Perform a graceful shutdown of the server when this event occurs.
| |||||||||||||||||||||
| SpcnsPowerFailedShutdownDelay | 1.3.6.1.4.1.318.1.2.3.4.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before performing a graceful shutdown of the server (seconds). | |||||||||||||||||||||
| NpcnsPowerRestored | 1.3.6.1.4.1.318.1.2.3.4.2 | ||||||||||||||||||||
| SpcnsPowerRestoredDesc | 1.3.6.1.4.1.318.1.2.3.4.2.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The Description of the event. | |||||||||||||||||||||
| SpcnsPowerRestoredEnableLogging | 1.3.6.1.4.1.318.1.2.3.4.2.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Log occurrences of this event in PCNS log.
| |||||||||||||||||||||
| SpcnsPowerRestoredEnableCommandFile | 1.3.6.1.4.1.318.1.2.3.4.2.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Execute a command file when this event occurs.
| |||||||||||||||||||||
| SpcnsPowerRestoredCommandFilePath | 1.3.6.1.4.1.318.1.2.3.4.2.4 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory Path of command file to execute when this event occurs. | |||||||||||||||||||||
| SpcnsPowerRestoredCommandFileDelay | 1.3.6.1.4.1.318.1.2.3.4.2.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before executing command file (seconds). | |||||||||||||||||||||
| NpcnsOverload | 1.3.6.1.4.1.318.1.2.3.4.3 | ||||||||||||||||||||
| SpcnsOverloadDesc | 1.3.6.1.4.1.318.1.2.3.4.3.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The Description of the event. | |||||||||||||||||||||
| SpcnsOverloadEnableLogging | 1.3.6.1.4.1.318.1.2.3.4.3.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Log occurrences of this event in PCNS log.
| |||||||||||||||||||||
| SpcnsOverloadEnableCommandFile | 1.3.6.1.4.1.318.1.2.3.4.3.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Execute a command file when this event occurs.
| |||||||||||||||||||||
| SpcnsOverloadCommandFilePath | 1.3.6.1.4.1.318.1.2.3.4.3.4 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory Path of command file to execute when this event occurs. | |||||||||||||||||||||
| SpcnsOverloadCommandFileDelay | 1.3.6.1.4.1.318.1.2.3.4.3.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before executing command file (seconds). | |||||||||||||||||||||
| SpcnsOverloadEnableShutdown | 1.3.6.1.4.1.318.1.2.3.4.3.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Perform a graceful shutdown of the server when this event occurs.
| |||||||||||||||||||||
| SpcnsOverloadShutdownDelay | 1.3.6.1.4.1.318.1.2.3.4.3.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before performing a graceful shutdown of the server (seconds). | |||||||||||||||||||||
| NpcnsOverloadSolved | 1.3.6.1.4.1.318.1.2.3.4.4 | ||||||||||||||||||||
| SpcnsOverloadSolvedDesc | 1.3.6.1.4.1.318.1.2.3.4.4.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The Description of the event. | |||||||||||||||||||||
| SpcnsOverloadSolvedEnableLogging | 1.3.6.1.4.1.318.1.2.3.4.4.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Log occurrences of this event in PCNS log.
| |||||||||||||||||||||
| SpcnsOverloadSolvedEnableCommandFile | 1.3.6.1.4.1.318.1.2.3.4.4.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Execute a command file when this event occurs.
| |||||||||||||||||||||
| SpcnsOverloadSolvedCommandFilePath | 1.3.6.1.4.1.318.1.2.3.4.4.4 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory Path of command file to execute when this event occurs. | |||||||||||||||||||||
| SpcnsOverloadSolvedCommandFileDelay | 1.3.6.1.4.1.318.1.2.3.4.4.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before executing command file (seconds). | |||||||||||||||||||||
| NpcnsRunTimeExceeded | 1.3.6.1.4.1.318.1.2.3.4.5 | ||||||||||||||||||||
| SpcnsRunTimeExceededDesc | 1.3.6.1.4.1.318.1.2.3.4.5.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The Description of the event. | |||||||||||||||||||||
| SpcnsRunTimeExceededEnableLogging | 1.3.6.1.4.1.318.1.2.3.4.5.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Log occurrences of this event in PCNS log.
| |||||||||||||||||||||
| SpcnsRunTimeExceededEnableCommandFile | 1.3.6.1.4.1.318.1.2.3.4.5.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Execute a command file when this event occurs.
| |||||||||||||||||||||
| SpcnsRunTimeExceededCommandFilePath | 1.3.6.1.4.1.318.1.2.3.4.5.4 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory Path of command file to execute when this event occurs. | |||||||||||||||||||||
| SpcnsRunTimeExceededCommandFileDelay | 1.3.6.1.4.1.318.1.2.3.4.5.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before executing command file (seconds). | |||||||||||||||||||||
| SpcnsRunTimeExceededEnableShutdown | 1.3.6.1.4.1.318.1.2.3.4.5.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Perform a graceful shutdown of the server when this event occurs.
| |||||||||||||||||||||
| SpcnsRunTimeExceededShutdownDelay | 1.3.6.1.4.1.318.1.2.3.4.5.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before performing a graceful shutdown of the server (seconds). | |||||||||||||||||||||
| NpcnsRunTimeWithinRange | 1.3.6.1.4.1.318.1.2.3.4.6 | ||||||||||||||||||||
| SpcnsRunTimeWithinRangeDesc | 1.3.6.1.4.1.318.1.2.3.4.6.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The Description of the event. | |||||||||||||||||||||
| SpcnsRunTimeWithinRangeEnableLogging | 1.3.6.1.4.1.318.1.2.3.4.6.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Log occurrences of this event in PCNS log.
| |||||||||||||||||||||
| SpcnsRunTimeWithinRangeEnableCommandFile | 1.3.6.1.4.1.318.1.2.3.4.6.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Execute a command file when this event occurs.
| |||||||||||||||||||||
| SpcnsRunTimeWithinRangeCommandFilePath | 1.3.6.1.4.1.318.1.2.3.4.6.4 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory Path of command file to execute when this event occurs. | |||||||||||||||||||||
| SpcnsRunTimeWithinRangeCommandFileDelay | 1.3.6.1.4.1.318.1.2.3.4.6.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before executing command file (seconds). | |||||||||||||||||||||
| NpcnsRunTimeBelowThreshold | 1.3.6.1.4.1.318.1.2.3.4.7 | ||||||||||||||||||||
| SpcnsRunTimeBelowThresholdDesc | 1.3.6.1.4.1.318.1.2.3.4.7.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The Description of the event. | |||||||||||||||||||||
| SpcnspcnsRunTimeBelowThresholdEnableLogging | 1.3.6.1.4.1.318.1.2.3.4.7.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Log occurrences of this event in PCNS log.
| |||||||||||||||||||||
| SpcnsRunTimeBelowThresholdEnableCommandFile | 1.3.6.1.4.1.318.1.2.3.4.7.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Execute a command file when this event occurs.
| |||||||||||||||||||||
| SpcnsRunTimeBelowThresholdCommandFilePath | 1.3.6.1.4.1.318.1.2.3.4.7.4 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory Path of command file to execute when this event occurs. | |||||||||||||||||||||
| SpcnsRunTimeBelowThresholdEnableShutdown | 1.3.6.1.4.1.318.1.2.3.4.7.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Perform a graceful shutdown of the server when this event occurs.
| |||||||||||||||||||||
| SpcnsRunTimeBelowThresholdCommandFileThreshold | 1.3.6.1.4.1.318.1.2.3.4.7.8 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory If the Runtime Remaining falls below this (seconds), the command file will run. | |||||||||||||||||||||
| SpcnsRunTimeBelowThresholdShutdownThreshold | 1.3.6.1.4.1.318.1.2.3.4.7.9 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory If the Runtime Remaining falls below this (seconds), the shutdown will begin. | |||||||||||||||||||||
| NpcnsRunTimeAboveThreshold | 1.3.6.1.4.1.318.1.2.3.4.8 | ||||||||||||||||||||
| SpcnsRunTimeAboveThresholdDesc | 1.3.6.1.4.1.318.1.2.3.4.8.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The Description of the event. | |||||||||||||||||||||
| SpcnsRunTimeAboveThresholdEnableLogging | 1.3.6.1.4.1.318.1.2.3.4.8.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Log occurrences of this event in PCNS log.
| |||||||||||||||||||||
| SpcnsRunTimeAboveThresholdEnableCommandFile | 1.3.6.1.4.1.318.1.2.3.4.8.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Execute a command file when this event occurs.
| |||||||||||||||||||||
| SpcnsRunTimeAboveThresholdCommandFilePath | 1.3.6.1.4.1.318.1.2.3.4.8.4 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory Path of command file to execute when this event occurs. | |||||||||||||||||||||
| SpcnsRunTimeAboveThresholdCommandFileDelay | 1.3.6.1.4.1.318.1.2.3.4.8.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before executing command file (seconds). | |||||||||||||||||||||
| NpcnsBatteryDischarged | 1.3.6.1.4.1.318.1.2.3.4.10 | ||||||||||||||||||||
| SpcnsBatteryDischargedDesc | 1.3.6.1.4.1.318.1.2.3.4.10.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The Description of the event. | |||||||||||||||||||||
| SpcnsBatteryDischargedEnableLogging | 1.3.6.1.4.1.318.1.2.3.4.10.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Log occurrences of this event in PCNS log.
| |||||||||||||||||||||
| SpcnsBatteryDischargedEnableCommandFile | 1.3.6.1.4.1.318.1.2.3.4.10.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Execute a command file when this event occurs.
| |||||||||||||||||||||
| SpcnsBatteryDischargedCommandFilePath | 1.3.6.1.4.1.318.1.2.3.4.10.4 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory Path of command file to execute when this event occurs. | |||||||||||||||||||||
| SpcnsBatteryDischargedCommandFileDelay | 1.3.6.1.4.1.318.1.2.3.4.10.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before executing command file (seconds). | |||||||||||||||||||||
| SpcnsBatteryDischargedEnableShutdown | 1.3.6.1.4.1.318.1.2.3.4.10.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Perform a graceful shutdown of the server when this event occurs.
| |||||||||||||||||||||
| SpcnsBatteryDischargedShutdownDelay | 1.3.6.1.4.1.318.1.2.3.4.10.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before performing a graceful shutdown of the server (seconds). | |||||||||||||||||||||
| NpcnsBatteryChargeInRange | 1.3.6.1.4.1.318.1.2.3.4.11 | ||||||||||||||||||||
| SpcnsBatteryChargeInRangeDesc | 1.3.6.1.4.1.318.1.2.3.4.11.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The Description of the event. | |||||||||||||||||||||
| SpcnsBatteryChargeInRangeEnableLogging | 1.3.6.1.4.1.318.1.2.3.4.11.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Log occurrences of this event in PCNS log.
| |||||||||||||||||||||
| SpcnsBatteryChargeInRangeEnableCommandFile | 1.3.6.1.4.1.318.1.2.3.4.11.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Execute a command file when this event occurs.
| |||||||||||||||||||||
| SpcnsBatteryChargeInRangeCommandFilePath | 1.3.6.1.4.1.318.1.2.3.4.11.4 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory Path of command file to execute when this event occurs. | |||||||||||||||||||||
| SpcnsBatteryChargeInRangeCommandFileDelay | 1.3.6.1.4.1.318.1.2.3.4.11.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before executing command file (seconds). | |||||||||||||||||||||
| NpcnsFaultBypassEnabled | 1.3.6.1.4.1.318.1.2.3.4.12 | ||||||||||||||||||||
| SpcnsFaultBypassEnabledDesc | 1.3.6.1.4.1.318.1.2.3.4.12.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The Description of the event. | |||||||||||||||||||||
| SpcnsFaultBypassEnabledEnableLogging | 1.3.6.1.4.1.318.1.2.3.4.12.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Log occurrences of this event in PCNS log.
| |||||||||||||||||||||
| SpcnsFaultBypassEnabledEnableCommandFile | 1.3.6.1.4.1.318.1.2.3.4.12.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Execute a command file when this event occurs.
| |||||||||||||||||||||
| SpcnsFaultBypassEnabledCommandFilePath | 1.3.6.1.4.1.318.1.2.3.4.12.4 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory Path of command file to execute when this event occurs. | |||||||||||||||||||||
| SpcnsFaultBypassEnabledCommandFileDelay | 1.3.6.1.4.1.318.1.2.3.4.12.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before executing command file (seconds). | |||||||||||||||||||||
| SpcnsFaultBypassEnabledEnableShutdown | 1.3.6.1.4.1.318.1.2.3.4.12.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Perform a graceful shutdown of the server when this event occurs.
| |||||||||||||||||||||
| SpcnsFaultBypassEnabledShutdownDelay | 1.3.6.1.4.1.318.1.2.3.4.12.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before performing a graceful shutdown of the server (seconds). | |||||||||||||||||||||
| NpcnsBypassEnabled | 1.3.6.1.4.1.318.1.2.3.4.13 | ||||||||||||||||||||
| SpcnsBypassEnabledDesc | 1.3.6.1.4.1.318.1.2.3.4.13.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The Description of the event. | |||||||||||||||||||||
| SpcnsBypassEnabledEnableLogging | 1.3.6.1.4.1.318.1.2.3.4.13.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Log occurrences of this event in PCNS log.
| |||||||||||||||||||||
| SpcnsBypassEnabledEnableCommandFile | 1.3.6.1.4.1.318.1.2.3.4.13.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Execute a command file when this event occurs.
| |||||||||||||||||||||
| SpcnsBypassEnabledCommandFilePath | 1.3.6.1.4.1.318.1.2.3.4.13.4 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory Path of command file to execute when this event occurs. | |||||||||||||||||||||
| SpcnsBypassEnabledCommandFileDelay | 1.3.6.1.4.1.318.1.2.3.4.13.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before executing command file (seconds). | |||||||||||||||||||||
| SpcnsBypassEnabledEnableShutdown | 1.3.6.1.4.1.318.1.2.3.4.13.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Perform a graceful shutdown of the server when this event occurs.
| |||||||||||||||||||||
| SpcnsBypassEnabledShutdownDelay | 1.3.6.1.4.1.318.1.2.3.4.13.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before performing a graceful shutdown of the server (seconds). | |||||||||||||||||||||
| NpcnsBypassManualEnabled | 1.3.6.1.4.1.318.1.2.3.4.14 | ||||||||||||||||||||
| SpcnsBypassManualEnabledDesc | 1.3.6.1.4.1.318.1.2.3.4.14.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The Description of the event. | |||||||||||||||||||||
| SpcnsBypassManualEnabledEnableLogging | 1.3.6.1.4.1.318.1.2.3.4.14.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Log occurrences of this event in PCNS log.
| |||||||||||||||||||||
| SpcnsBypassManualEnabledEnableCommandFile | 1.3.6.1.4.1.318.1.2.3.4.14.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Execute a command file when this event occurs.
| |||||||||||||||||||||
| SpcnsBypassManualEnabledCommandFilePath | 1.3.6.1.4.1.318.1.2.3.4.14.4 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory Path of command file to execute when this event occurs. | |||||||||||||||||||||
| SpcnsBypassManualEnabledCommandFileDelay | 1.3.6.1.4.1.318.1.2.3.4.14.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before executing command file (seconds). | |||||||||||||||||||||
| SpcnsBypassManualEnabledEnableShutdown | 1.3.6.1.4.1.318.1.2.3.4.14.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Perform a graceful shutdown of the server when this event occurs.
| |||||||||||||||||||||
| SpcnsBypassManualEnabledShutdownDelay | 1.3.6.1.4.1.318.1.2.3.4.14.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before performing a graceful shutdown of the server (seconds). | |||||||||||||||||||||
| NpcnsBypassDisabled | 1.3.6.1.4.1.318.1.2.3.4.15 | ||||||||||||||||||||
| SpcnsBypassDisabledDesc | 1.3.6.1.4.1.318.1.2.3.4.15.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The Description of the event. | |||||||||||||||||||||
| SpcnsBypassDisabledEnableLogging | 1.3.6.1.4.1.318.1.2.3.4.15.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Log occurrences of this event in PCNS log.
| |||||||||||||||||||||
| SpcnsBypassDisabledEnableCommandFile | 1.3.6.1.4.1.318.1.2.3.4.15.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Execute a command file when this event occurs.
| |||||||||||||||||||||
| SpcnsBypassDisabledCommandFilePath | 1.3.6.1.4.1.318.1.2.3.4.15.4 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory Path of command file to execute when this event occurs. | |||||||||||||||||||||
| SpcnsBypassDisabledCommandFileDelay | 1.3.6.1.4.1.318.1.2.3.4.15.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before executing command file (seconds). | |||||||||||||||||||||
| NpcnsBypassContactorFailed | 1.3.6.1.4.1.318.1.2.3.4.16 | ||||||||||||||||||||
| SpcnsBypassContactorFailedDesc | 1.3.6.1.4.1.318.1.2.3.4.16.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The Description of the event. | |||||||||||||||||||||
| SpcnsBypassContactorFailedEnableLogging | 1.3.6.1.4.1.318.1.2.3.4.16.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Log occurrences of this event in PCNS log.
| |||||||||||||||||||||
| SpcnsBypassContactorFailedEnableCommandFile | 1.3.6.1.4.1.318.1.2.3.4.16.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Execute a command file when this event occurs.
| |||||||||||||||||||||
| SpcnsBypassContactorFailedCommandFilePath | 1.3.6.1.4.1.318.1.2.3.4.16.4 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory Path of command file to execute when this event occurs. | |||||||||||||||||||||
| SpcnsBypassContactorFailedCommandFileDelay | 1.3.6.1.4.1.318.1.2.3.4.16.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before executing command file (seconds). | |||||||||||||||||||||
| SpcnsBypassContactorFailedEnableShutdown | 1.3.6.1.4.1.318.1.2.3.4.16.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Perform a graceful shutdown of the server when this event occurs.
| |||||||||||||||||||||
| SpcnsBypassContactorFailedShutdownDelay | 1.3.6.1.4.1.318.1.2.3.4.16.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before performing a graceful shutdown of the server (seconds). | |||||||||||||||||||||
| NpcnsBypassContactorOk | 1.3.6.1.4.1.318.1.2.3.4.17 | ||||||||||||||||||||
| SpcnsBypassContactorOkDesc | 1.3.6.1.4.1.318.1.2.3.4.17.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The Description of the event. | |||||||||||||||||||||
| SpcnsBypassContactorOkEnableLogging | 1.3.6.1.4.1.318.1.2.3.4.17.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Log occurrences of this event in PCNS log.
| |||||||||||||||||||||
| SpcnsBypassContactorOkEnableCommandFile | 1.3.6.1.4.1.318.1.2.3.4.17.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Execute a command file when this event occurs.
| |||||||||||||||||||||
| SpcnsBypassContactorOkCommandFilePath | 1.3.6.1.4.1.318.1.2.3.4.17.4 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory Path of command file to execute when this event occurs. | |||||||||||||||||||||
| SpcnsBypassContactorOkCommandFileDelay | 1.3.6.1.4.1.318.1.2.3.4.17.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before executing command file (seconds). | |||||||||||||||||||||
| NpcnsCommunicationLostOnBattery | 1.3.6.1.4.1.318.1.2.3.4.18 | ||||||||||||||||||||
| SpcnsCommunicationLostOnBatteryDesc | 1.3.6.1.4.1.318.1.2.3.4.18.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The Description of the event. | |||||||||||||||||||||
| SpcnsCommunicationLostOnBatteryEnableLogging | 1.3.6.1.4.1.318.1.2.3.4.18.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Log occurrences of this event in PCNS log.
| |||||||||||||||||||||
| SpcnsCommunicationLostOnBatteryEnableCommandFile | 1.3.6.1.4.1.318.1.2.3.4.18.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Execute a command file when this event occurs.
| |||||||||||||||||||||
| SpcnsCommunicationLostOnBatteryCommandFilePath | 1.3.6.1.4.1.318.1.2.3.4.18.4 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory Path of command file to execute when this event occurs. | |||||||||||||||||||||
| SpcnsCommunicationLostOnBatteryCommandFileDelay | 1.3.6.1.4.1.318.1.2.3.4.18.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before executing command file (seconds). | |||||||||||||||||||||
| SpcnsCommunicationLostOnBatteryEnableShutdown | 1.3.6.1.4.1.318.1.2.3.4.18.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Perform a graceful shutdown of the server when this event occurs.
| |||||||||||||||||||||
| SpcnsCommunicationLostOnBatteryShutdownDelay | 1.3.6.1.4.1.318.1.2.3.4.18.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before performing a graceful shutdown of the server (seconds). | |||||||||||||||||||||
| NpcnsCommunicationLost | 1.3.6.1.4.1.318.1.2.3.4.19 | ||||||||||||||||||||
| SpcnsCommunicationLostDesc | 1.3.6.1.4.1.318.1.2.3.4.19.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The Description of the event. | |||||||||||||||||||||
| SpcnsCommunicationLostEnableLogging | 1.3.6.1.4.1.318.1.2.3.4.19.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Log occurrences of this event in PCNS log.
| |||||||||||||||||||||
| SpcnsCommunicationLostEnableCommandFile | 1.3.6.1.4.1.318.1.2.3.4.19.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Execute a command file when this event occurs.
| |||||||||||||||||||||
| SpcnsCommunicationLostCommandFilePath | 1.3.6.1.4.1.318.1.2.3.4.19.4 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory Path of command file to execute when this event occurs. | |||||||||||||||||||||
| SpcnsCommunicationLostCommandFileDelay | 1.3.6.1.4.1.318.1.2.3.4.19.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before executing command file (seconds). | |||||||||||||||||||||
| SpcnsCommunicationLostEnableShutdown | 1.3.6.1.4.1.318.1.2.3.4.19.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Perform a graceful shutdown of the server when this event occurs.
| |||||||||||||||||||||
| SpcnsCommunicationLostShutdownDelay | 1.3.6.1.4.1.318.1.2.3.4.19.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before performing a graceful shutdown of the server (seconds). | |||||||||||||||||||||
| NpcnsNetCommunicationLost | 1.3.6.1.4.1.318.1.2.3.4.20 | ||||||||||||||||||||
| SpcnsNetCommunicationLostDesc | 1.3.6.1.4.1.318.1.2.3.4.20.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The Description of the event. | |||||||||||||||||||||
| SpcnsNetCommunicationLostEnableLogging | 1.3.6.1.4.1.318.1.2.3.4.20.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Log occurrences of this event in PCNS log.
| |||||||||||||||||||||
| SpcnsNetCommunicationLostEnableCommandFile | 1.3.6.1.4.1.318.1.2.3.4.20.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Execute a command file when this event occurs.
| |||||||||||||||||||||
| SpcnsNetCommunicationLostCommandFilePath | 1.3.6.1.4.1.318.1.2.3.4.20.4 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory Path of command file to execute when this event occurs. | |||||||||||||||||||||
| SpcnsNetCommunicationLostCommandFileDelay | 1.3.6.1.4.1.318.1.2.3.4.20.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before executing command file (seconds). | |||||||||||||||||||||
| SpcnsNetCommunicationLostEnableShutdown | 1.3.6.1.4.1.318.1.2.3.4.20.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Perform a graceful shutdown of the server when this event occurs.
| |||||||||||||||||||||
| SpcnsNetCommunicationLostShutdownDelay | 1.3.6.1.4.1.318.1.2.3.4.20.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before performing a graceful shutdown of the server (seconds). | |||||||||||||||||||||
| NpcnsCommunicationEstablished | 1.3.6.1.4.1.318.1.2.3.4.21 | ||||||||||||||||||||
| SpcnsCommunicationEstablishedDesc | 1.3.6.1.4.1.318.1.2.3.4.21.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The Description of the event. | |||||||||||||||||||||
| SpcnsCommunicationEstablishedEnableLogging | 1.3.6.1.4.1.318.1.2.3.4.21.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Log occurrences of this event in PCNS log.
| |||||||||||||||||||||
| SpcnsCommunicationEstablishedEnableCommandFile | 1.3.6.1.4.1.318.1.2.3.4.21.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Execute a command file when this event occurs.
| |||||||||||||||||||||
| SpcnsCommunicationEstablishedCommandFilePath | 1.3.6.1.4.1.318.1.2.3.4.21.4 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory Path of command file to execute when this event occurs. | |||||||||||||||||||||
| SpcnsCommunicationEstablishedCommandFileDelay | 1.3.6.1.4.1.318.1.2.3.4.21.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before executing command file (seconds). | |||||||||||||||||||||
| NpcnsMinRedundancyLost | 1.3.6.1.4.1.318.1.2.3.4.22 | ||||||||||||||||||||
| SpcnsMinRedundancyLostDesc | 1.3.6.1.4.1.318.1.2.3.4.22.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The Description of the event. | |||||||||||||||||||||
| SpcnsMinRedundancyLostEnableLogging | 1.3.6.1.4.1.318.1.2.3.4.22.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Log occurrences of this event in PCNS log.
| |||||||||||||||||||||
| SpcnsMinRedundancyLostEnableCommandFile | 1.3.6.1.4.1.318.1.2.3.4.22.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Execute a command file when this event occurs.
| |||||||||||||||||||||
| SpcnsMinRedundancyLostCommandFilePath | 1.3.6.1.4.1.318.1.2.3.4.22.4 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory Path of command file to execute when this event occurs. | |||||||||||||||||||||
| SpcnsMinRedundancyLostCommandFileDelay | 1.3.6.1.4.1.318.1.2.3.4.22.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before executing command file (seconds). | |||||||||||||||||||||
| SpcnsMinRedundancyLostEnableShutdown | 1.3.6.1.4.1.318.1.2.3.4.22.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Perform a graceful shutdown of the server when this event occurs.
| |||||||||||||||||||||
| SpcnsMinRedundancyLostShutdownDelay | 1.3.6.1.4.1.318.1.2.3.4.22.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before performing a graceful shutdown of the server (seconds). | |||||||||||||||||||||
| NpcnsMinRedundancyRegained | 1.3.6.1.4.1.318.1.2.3.4.23 | ||||||||||||||||||||
| SpcnsMinRedundancyRegainedDesc | 1.3.6.1.4.1.318.1.2.3.4.23.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The Description of the event. | |||||||||||||||||||||
| SpcnsMinRedundancyRegainedEnableLogging | 1.3.6.1.4.1.318.1.2.3.4.23.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Log occurrences of this event in PCNS log.
| |||||||||||||||||||||
| SpcnsMinRedundancyRegainedEnableCommandFile | 1.3.6.1.4.1.318.1.2.3.4.23.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Execute a command file when this event occurs.
| |||||||||||||||||||||
| SpcnsMinRedundancyRegainedCommandFilePath | 1.3.6.1.4.1.318.1.2.3.4.23.4 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory Path of command file to execute when this event occurs. | |||||||||||||||||||||
| SpcnsMinRedundancyRegainedCommandFileDelay | 1.3.6.1.4.1.318.1.2.3.4.23.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before executing command file (seconds). | |||||||||||||||||||||
| NpcnsParallelRedundancyLost | 1.3.6.1.4.1.318.1.2.3.4.24 | ||||||||||||||||||||
| SpcnsParallelRedundancyLostDesc | 1.3.6.1.4.1.318.1.2.3.4.24.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The Description of the event. | |||||||||||||||||||||
| SpcnsParallelRedundancyLostEnableLogging | 1.3.6.1.4.1.318.1.2.3.4.24.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Log occurrences of this event in PCNS log.
| |||||||||||||||||||||
| SpcnsParallelRedundancyLostEnableCommandFile | 1.3.6.1.4.1.318.1.2.3.4.24.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Execute a command file when this event occurs.
| |||||||||||||||||||||
| SpcnsParallelRedundancyLostCommandFilePath | 1.3.6.1.4.1.318.1.2.3.4.24.4 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory Path of command file to execute when this event occurs. | |||||||||||||||||||||
| SpcnsParallelRedundancyLostCommandFileDelay | 1.3.6.1.4.1.318.1.2.3.4.24.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before executing command file (seconds). | |||||||||||||||||||||
| SpcnsParallelRedundancyLostEnableShutdown | 1.3.6.1.4.1.318.1.2.3.4.24.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Perform a graceful shutdown of the server when this event occurs.
| |||||||||||||||||||||
| SpcnsParallelRedundancyLostShutdownDelay | 1.3.6.1.4.1.318.1.2.3.4.24.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before performing a graceful shutdown of the server (seconds). | |||||||||||||||||||||
| NpcnsParallelRedundancyRegained | 1.3.6.1.4.1.318.1.2.3.4.25 | ||||||||||||||||||||
| SpcnsParallelRedundancyRegainedDesc | 1.3.6.1.4.1.318.1.2.3.4.25.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The Description of the event. | |||||||||||||||||||||
| SpcnsParallelRedundancyRegainedEnableLogging | 1.3.6.1.4.1.318.1.2.3.4.25.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Log occurrences of this event in PCNS log.
| |||||||||||||||||||||
| SpcnsParallelRedundancyRegainedEnableCommandFile | 1.3.6.1.4.1.318.1.2.3.4.25.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Execute a command file when this event occurs.
| |||||||||||||||||||||
| SpcnsParallelRedundancyRegainedCommandFilePath | 1.3.6.1.4.1.318.1.2.3.4.25.4 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory Path of command file to execute when this event occurs. | |||||||||||||||||||||
| SpcnsParallelRedundancyRegainedCommandFileDelay | 1.3.6.1.4.1.318.1.2.3.4.25.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before executing command file (seconds). | |||||||||||||||||||||
| NpcnsMaxInternalTempExceeded | 1.3.6.1.4.1.318.1.2.3.4.26 | ||||||||||||||||||||
| SpcnsMaxInternalTempExceededDesc | 1.3.6.1.4.1.318.1.2.3.4.26.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The Description of the event. | |||||||||||||||||||||
| SpcnsMaxInternalTempExceededEnableLogging | 1.3.6.1.4.1.318.1.2.3.4.26.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Log occurrences of this event in PCNS log.
| |||||||||||||||||||||
| SpcnsMaxInternalTempExceededEnableCommandFile | 1.3.6.1.4.1.318.1.2.3.4.26.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Execute a command file when this event occurs.
| |||||||||||||||||||||
| SpcnsMaxInternalTempExceededCommandFilePath | 1.3.6.1.4.1.318.1.2.3.4.26.4 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory Path of command file to execute when this event occurs. | |||||||||||||||||||||
| SpcnsMaxInternalTempExceededCommandFileDelay | 1.3.6.1.4.1.318.1.2.3.4.26.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before executing command file (seconds). | |||||||||||||||||||||
| SpcnsMaxInternalTempExceededEnableShutdown | 1.3.6.1.4.1.318.1.2.3.4.26.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Perform a graceful shutdown of the server when this event occurs.
| |||||||||||||||||||||
| SpcnsMaxInternalTempExceededShutdownDelay | 1.3.6.1.4.1.318.1.2.3.4.26.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before performing a graceful shutdown of the server (seconds). | |||||||||||||||||||||
| NpcnsMaxInternalTempInRange | 1.3.6.1.4.1.318.1.2.3.4.27 | ||||||||||||||||||||
| SpcnsMaxInternalTempInRangeDesc | 1.3.6.1.4.1.318.1.2.3.4.27.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The Description of the event. | |||||||||||||||||||||
| SpcnsMaxInternalTempInRangeEnableLogging | 1.3.6.1.4.1.318.1.2.3.4.27.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Log occurrences of this event in PCNS log.
| |||||||||||||||||||||
| SpcnsMaxInternalTempInRangeEnableCommandFile | 1.3.6.1.4.1.318.1.2.3.4.27.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Execute a command file when this event occurs.
| |||||||||||||||||||||
| SpcnsMaxInternalTempInRangeCommandFilePath | 1.3.6.1.4.1.318.1.2.3.4.27.4 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory Path of command file to execute when this event occurs. | |||||||||||||||||||||
| SpcnsMaxInternalTempInRangeCommandFileDelay | 1.3.6.1.4.1.318.1.2.3.4.27.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before executing command file (seconds). | |||||||||||||||||||||
| NpcnsMinLoadCapabilityLost | 1.3.6.1.4.1.318.1.2.3.4.28 | ||||||||||||||||||||
| SpcnsMinLoadCapabilityLostDesc | 1.3.6.1.4.1.318.1.2.3.4.28.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The Description of the event. | |||||||||||||||||||||
| SpcnsMinLoadCapabilityLostEnableLogging | 1.3.6.1.4.1.318.1.2.3.4.28.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Log occurrences of this event in PCNS log.
| |||||||||||||||||||||
| SpcnsMinLoadCapabilityLostEnableCommandFile | 1.3.6.1.4.1.318.1.2.3.4.28.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Execute a command file when this event occurs.
| |||||||||||||||||||||
| SpcnsMinLoadCapabilityLostCommandFilePath | 1.3.6.1.4.1.318.1.2.3.4.28.4 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory Path of command file to execute when this event occurs. | |||||||||||||||||||||
| SpcnsMinLoadCapabilityLostCommandFileDelay | 1.3.6.1.4.1.318.1.2.3.4.28.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before executing command file (seconds). | |||||||||||||||||||||
| SpcnsMinLoadCapabilityLostEnableShutdown | 1.3.6.1.4.1.318.1.2.3.4.28.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Perform a graceful shutdown of the server when this event occurs.
| |||||||||||||||||||||
| SpcnsMinLoadCapabilityLostShutdownDelay | 1.3.6.1.4.1.318.1.2.3.4.28.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before performing a graceful shutdown of the server (seconds). | |||||||||||||||||||||
| NpcnsMinLoadCapabilityRegained | 1.3.6.1.4.1.318.1.2.3.4.29 | ||||||||||||||||||||
| SpcnsMinLoadCapabilityRegainedDesc | 1.3.6.1.4.1.318.1.2.3.4.29.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The Description of the event. | |||||||||||||||||||||
| SpcnsMinLoadCapabilityRegainedEnableLogging | 1.3.6.1.4.1.318.1.2.3.4.29.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Log occurrences of this event in PCNS log.
| |||||||||||||||||||||
| SpcnsMinLoadCapabilityRegainedEnableCommandFile | 1.3.6.1.4.1.318.1.2.3.4.29.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Execute a command file when this event occurs.
| |||||||||||||||||||||
| SpcnsMinLoadCapabilityRegainedCommandFilePath | 1.3.6.1.4.1.318.1.2.3.4.29.4 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory Path of command file to execute when this event occurs. | |||||||||||||||||||||
| SpcnsMinLoadCapabilityRegainedCommandFileDelay | 1.3.6.1.4.1.318.1.2.3.4.29.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before executing command file (seconds). | |||||||||||||||||||||
| NpcnsEnvironmentCommunicationEstablished | 1.3.6.1.4.1.318.1.2.3.4.30 | ||||||||||||||||||||
| SpcnsEnvironmentCommunicationEstablishedDesc | 1.3.6.1.4.1.318.1.2.3.4.30.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The Description of the event. | |||||||||||||||||||||
| SpcnsEnvironmentCommunicationEstablishedEnableLogging | 1.3.6.1.4.1.318.1.2.3.4.30.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Log occurrences of this event in PCNS log.
| |||||||||||||||||||||
| SpcnsEnvironmentCommunicationEstablishedEnableCommandFile | 1.3.6.1.4.1.318.1.2.3.4.30.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Execute a command file when this event occurs.
| |||||||||||||||||||||
| SpcnsEnvironmentCommunicationEstablishedCommandFilePath | 1.3.6.1.4.1.318.1.2.3.4.30.4 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory Path of command file to execute when this event occurs. | |||||||||||||||||||||
| SpcnsEnvironmentCommunicationEstablishedCommandFileDelay | 1.3.6.1.4.1.318.1.2.3.4.30.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before executing command file (seconds). | |||||||||||||||||||||
| NpcnsEnvironmentCommunicationLost | 1.3.6.1.4.1.318.1.2.3.4.31 | ||||||||||||||||||||
| SpcnsEnvironmentCommunicationLostDesc | 1.3.6.1.4.1.318.1.2.3.4.31.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The Description of the event. | |||||||||||||||||||||
| SpcnsEnvironmentCommunicationLostEnableLogging | 1.3.6.1.4.1.318.1.2.3.4.31.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Log occurrences of this event in PCNS log.
| |||||||||||||||||||||
| SpcnsEnvironmentCommunicationLostEnableCommandFile | 1.3.6.1.4.1.318.1.2.3.4.31.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Execute a command file when this event occurs.
| |||||||||||||||||||||
| SpcnsEnvironmentCommunicationLostCommandFilePath | 1.3.6.1.4.1.318.1.2.3.4.31.4 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory Path of command file to execute when this event occurs. | |||||||||||||||||||||
| SpcnsEnvironmentCommunicationLostCommandFileDelay | 1.3.6.1.4.1.318.1.2.3.4.31.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before executing command file (seconds). | |||||||||||||||||||||
| NpcnsTempInRangeProbe1 | 1.3.6.1.4.1.318.1.2.3.4.32 | ||||||||||||||||||||
| SpcnsTempInRangeProbe1Desc | 1.3.6.1.4.1.318.1.2.3.4.32.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The Description of the event. | |||||||||||||||||||||
| SpcnsTempInRangeProbe1EnableLogging | 1.3.6.1.4.1.318.1.2.3.4.32.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Log occurrences of this event in PCNS log.
| |||||||||||||||||||||
| SpcnsTempInRangeProbe1EnableCommandFile | 1.3.6.1.4.1.318.1.2.3.4.32.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Execute a command file when this event occurs.
| |||||||||||||||||||||
| SpcnsTempInRangeProbe1CommandFilePath | 1.3.6.1.4.1.318.1.2.3.4.32.4 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory Path of command file to execute when this event occurs. | |||||||||||||||||||||
| SpcnsTempInRangeProbe1CommandFileDelay | 1.3.6.1.4.1.318.1.2.3.4.32.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before executing command file (seconds). | |||||||||||||||||||||
| NpcnsTempOutOfRangeProbe1 | 1.3.6.1.4.1.318.1.2.3.4.33 | ||||||||||||||||||||
| SpcnsTempOutOfRangeProbe1Desc | 1.3.6.1.4.1.318.1.2.3.4.33.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The Description of the event. | |||||||||||||||||||||
| SpcnsTempOutOfRangeProbe1EnableLogging | 1.3.6.1.4.1.318.1.2.3.4.33.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Log occurrences of this event in PCNS log.
| |||||||||||||||||||||
| SpcnsTempOutOfRangeProbe1EnableCommandFile | 1.3.6.1.4.1.318.1.2.3.4.33.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Execute a command file when this event occurs.
| |||||||||||||||||||||
| SpcnsTempOutOfRangeProbe1CommandFilePath | 1.3.6.1.4.1.318.1.2.3.4.33.4 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory Path of command file to execute when this event occurs. | |||||||||||||||||||||
| SpcnsTempOutOfRangeProbe1CommandFileDelay | 1.3.6.1.4.1.318.1.2.3.4.33.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before executing command file (seconds). | |||||||||||||||||||||
| SpcnsTempOutOfRangeProbe1EnableShutdown | 1.3.6.1.4.1.318.1.2.3.4.33.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Perform a graceful shutdown of the server when this event occurs.
| |||||||||||||||||||||
| SpcnsTempOutOfRangeProbe1ShutdownDelay | 1.3.6.1.4.1.318.1.2.3.4.33.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before performing a graceful shutdown of the server (seconds). | |||||||||||||||||||||
| NpcnsHumidityInRangeProbe1 | 1.3.6.1.4.1.318.1.2.3.4.34 | ||||||||||||||||||||
| SpcnsHumidityInRangeProbe1Desc | 1.3.6.1.4.1.318.1.2.3.4.34.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The Description of the event. | |||||||||||||||||||||
| SpcnsHumidityInRangeProbe1EnableLogging | 1.3.6.1.4.1.318.1.2.3.4.34.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Log occurrences of this event in PCNS log.
| |||||||||||||||||||||
| SpcnsHumidityInRangeProbe1EnableCommandFile | 1.3.6.1.4.1.318.1.2.3.4.34.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Execute a command file when this event occurs.
| |||||||||||||||||||||
| SpcnsHumidityInRangeProbe1CommandFilePath | 1.3.6.1.4.1.318.1.2.3.4.34.4 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory Path of command file to execute when this event occurs. | |||||||||||||||||||||
| SpcnsHumidityInRangeProbe1CommandFileDelay | 1.3.6.1.4.1.318.1.2.3.4.34.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before executing command file (seconds). | |||||||||||||||||||||
| NpcnsHumidityOutOfRangeProbe1 | 1.3.6.1.4.1.318.1.2.3.4.35 | ||||||||||||||||||||
| SpcnsHumidityOutOfRangeProbe1Desc | 1.3.6.1.4.1.318.1.2.3.4.35.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The Description of the event. | |||||||||||||||||||||
| SpcnsHumidityOutOfRangeProbe1EnableLogging | 1.3.6.1.4.1.318.1.2.3.4.35.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Log occurrences of this event in PCNS log.
| |||||||||||||||||||||
| SpcnsHumidityOutOfRangeProbe1EnableCommandFile | 1.3.6.1.4.1.318.1.2.3.4.35.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Execute a command file when this event occurs.
| |||||||||||||||||||||
| SpcnsHumidityOutOfRangeProbe1CommandFilePath | 1.3.6.1.4.1.318.1.2.3.4.35.4 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory Path of command file to execute when this event occurs. | |||||||||||||||||||||
| SpcnsHumidityOutOfRangeProbe1CommandFileDelay | 1.3.6.1.4.1.318.1.2.3.4.35.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before executing command file (seconds). | |||||||||||||||||||||
| SpcnsHumidityOutOfRangeProbe1EnableShutdown | 1.3.6.1.4.1.318.1.2.3.4.35.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Perform a graceful shutdown of the server when this event occurs.
| |||||||||||||||||||||
| SpcnsHumidityOutOfRangeProbe1ShutdownDelay | 1.3.6.1.4.1.318.1.2.3.4.35.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before performing a graceful shutdown of the server (seconds). | |||||||||||||||||||||
| NpcnsTempInRangeProbe2 | 1.3.6.1.4.1.318.1.2.3.4.36 | ||||||||||||||||||||
| SpcnsTempInRangeProbe2Desc | 1.3.6.1.4.1.318.1.2.3.4.36.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The Description of the event. | |||||||||||||||||||||
| SpcnsTempInRangeProbe2EnableLogging | 1.3.6.1.4.1.318.1.2.3.4.36.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Log occurrences of this event in PCNS log.
| |||||||||||||||||||||
| SpcnsTempInRangeProbe2EnableCommandFile | 1.3.6.1.4.1.318.1.2.3.4.36.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Execute a command file when this event occurs.
| |||||||||||||||||||||
| SpcnsTempInRangeProbe2CommandFilePath | 1.3.6.1.4.1.318.1.2.3.4.36.4 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory Path of command file to execute when this event occurs. | |||||||||||||||||||||
| SpcnsTempInRangeProbe2CommandFileDelay | 1.3.6.1.4.1.318.1.2.3.4.36.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before executing command file (seconds). | |||||||||||||||||||||
| NpcnsTempOutOfRangeProbe2 | 1.3.6.1.4.1.318.1.2.3.4.37 | ||||||||||||||||||||
| SpcnsTempOutOfRangeProbe2Desc | 1.3.6.1.4.1.318.1.2.3.4.37.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The Description of the event. | |||||||||||||||||||||
| SpcnsTempOutOfRangeProbe2EnableLogging | 1.3.6.1.4.1.318.1.2.3.4.37.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Log occurrences of this event in PCNS log.
| |||||||||||||||||||||
| SpcnsTempOutOfRangeProbe2EnableCommandFile | 1.3.6.1.4.1.318.1.2.3.4.37.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Execute a command file when this event occurs.
| |||||||||||||||||||||
| SpcnsTempOutOfRangeProbe2CommandFilePath | 1.3.6.1.4.1.318.1.2.3.4.37.4 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory Path of command file to execute when this event occurs. | |||||||||||||||||||||
| SpcnsTempOutOfRangeProbe2CommandFileDelay | 1.3.6.1.4.1.318.1.2.3.4.37.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before executing command file (seconds). | |||||||||||||||||||||
| SpcnsTempOutOfRangeProbe2EnableShutdown | 1.3.6.1.4.1.318.1.2.3.4.37.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Perform a graceful shutdown of the server when this event occurs.
| |||||||||||||||||||||
| SpcnsTempOutOfRangeProbe2ShutdownDelay | 1.3.6.1.4.1.318.1.2.3.4.37.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before performing a graceful shutdown of the server (seconds). | |||||||||||||||||||||
| NpcnsHumidityInRangeProbe2 | 1.3.6.1.4.1.318.1.2.3.4.38 | ||||||||||||||||||||
| SpcnsHumidityInRangeProbe2Desc | 1.3.6.1.4.1.318.1.2.3.4.38.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The Description of the event. | |||||||||||||||||||||
| SpcnsHumidityInRangeProbe2EnableLogging | 1.3.6.1.4.1.318.1.2.3.4.38.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Log occurrences of this event in PCNS log.
| |||||||||||||||||||||
| SpcnsHumidityInRangeProbe2EnableCommandFile | 1.3.6.1.4.1.318.1.2.3.4.38.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Execute a command file when this event occurs.
| |||||||||||||||||||||
| SpcnsHumidityInRangeProbe2CommandFilePath | 1.3.6.1.4.1.318.1.2.3.4.38.4 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory Path of command file to execute when this event occurs. | |||||||||||||||||||||
| SpcnsHumidityInRangeProbe2CommandFileDelay | 1.3.6.1.4.1.318.1.2.3.4.38.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before executing command file (seconds). | |||||||||||||||||||||
| NpcnsHumidityOutOfRangeProbe2 | 1.3.6.1.4.1.318.1.2.3.4.39 | ||||||||||||||||||||
| SpcnsHumidityOutOfRangeProbe2Desc | 1.3.6.1.4.1.318.1.2.3.4.39.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The Description of the event. | |||||||||||||||||||||
| SpcnsHumidityOutOfRangeProbe2EnableLogging | 1.3.6.1.4.1.318.1.2.3.4.39.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Log occurrences of this event in PCNS log.
| |||||||||||||||||||||
| SpcnsHumidityOutOfRangeProbe2EnableCommandFile | 1.3.6.1.4.1.318.1.2.3.4.39.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Execute a command file when this event occurs.
| |||||||||||||||||||||
| SpcnsHumidityOutOfRangeProbe2CommandFilePath | 1.3.6.1.4.1.318.1.2.3.4.39.4 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory Path of command file to execute when this event occurs. | |||||||||||||||||||||
| SpcnsHumidityOutOfRangeProbe2CommandFileDelay | 1.3.6.1.4.1.318.1.2.3.4.39.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before executing command file (seconds). | |||||||||||||||||||||
| SpcnsHumidityOutOfRangeProbe2EnableShutdown | 1.3.6.1.4.1.318.1.2.3.4.39.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Perform a graceful shutdown of the server when this event occurs.
| |||||||||||||||||||||
| SpcnsHumidityOutOfRangeProbe2ShutdownDelay | 1.3.6.1.4.1.318.1.2.3.4.39.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before performing a graceful shutdown of the server (seconds). | |||||||||||||||||||||
| NpcnsContactFault1 | 1.3.6.1.4.1.318.1.2.3.4.40 | ||||||||||||||||||||
| SpcnsContactFault1Desc | 1.3.6.1.4.1.318.1.2.3.4.40.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The Description of the event. | |||||||||||||||||||||
| SpcnsContactFault1EnableLogging | 1.3.6.1.4.1.318.1.2.3.4.40.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Log occurrences of this event in PCNS log.
| |||||||||||||||||||||
| SpcnsContactFault1EnableCommandFile | 1.3.6.1.4.1.318.1.2.3.4.40.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Execute a command file when this event occurs.
| |||||||||||||||||||||
| SpcnsContactFault1CommandFilePath | 1.3.6.1.4.1.318.1.2.3.4.40.4 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory Path of command file to execute when this event occurs. | |||||||||||||||||||||
| SpcnsContactFault1CommandFileDelay | 1.3.6.1.4.1.318.1.2.3.4.40.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before executing command file (seconds). | |||||||||||||||||||||
| SpcnsContactFault1EnableShutdown | 1.3.6.1.4.1.318.1.2.3.4.40.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Perform a graceful shutdown of the server when this event occurs.
| |||||||||||||||||||||
| SpcnsContactFault1ShutdownDelay | 1.3.6.1.4.1.318.1.2.3.4.40.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before performing a graceful shutdown of the server (seconds). | |||||||||||||||||||||
| NpcnsContactFault2 | 1.3.6.1.4.1.318.1.2.3.4.41 | ||||||||||||||||||||
| SpcnsContactFault2Desc | 1.3.6.1.4.1.318.1.2.3.4.41.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The Description of the event. | |||||||||||||||||||||
| SpcnsContactFault2EnableLogging | 1.3.6.1.4.1.318.1.2.3.4.41.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Log occurrences of this event in PCNS log.
| |||||||||||||||||||||
| SpcnsContactFault2EnableCommandFile | 1.3.6.1.4.1.318.1.2.3.4.41.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Execute a command file when this event occurs.
| |||||||||||||||||||||
| SpcnsContactFault2CommandFilePath | 1.3.6.1.4.1.318.1.2.3.4.41.4 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory Path of command file to execute when this event occurs. | |||||||||||||||||||||
| SpcnsContactFault2CommandFileDelay | 1.3.6.1.4.1.318.1.2.3.4.41.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before executing command file (seconds). | |||||||||||||||||||||
| SpcnsContactFault2EnableShutdown | 1.3.6.1.4.1.318.1.2.3.4.41.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Perform a graceful shutdown of the server when this event occurs.
| |||||||||||||||||||||
| SpcnsContactFault2ShutdownDelay | 1.3.6.1.4.1.318.1.2.3.4.41.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before performing a graceful shutdown of the server (seconds). | |||||||||||||||||||||
| NpcnsContactFault3 | 1.3.6.1.4.1.318.1.2.3.4.42 | ||||||||||||||||||||
| SpcnsContactFault3Desc | 1.3.6.1.4.1.318.1.2.3.4.42.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The Description of the event. | |||||||||||||||||||||
| SpcnsContactFault3EnableLogging | 1.3.6.1.4.1.318.1.2.3.4.42.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Log occurrences of this event in PCNS log.
| |||||||||||||||||||||
| SpcnsContactFault3EnableCommandFile | 1.3.6.1.4.1.318.1.2.3.4.42.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Execute a command file when this event occurs.
| |||||||||||||||||||||
| SpcnsContactFault3CommandFilePath | 1.3.6.1.4.1.318.1.2.3.4.42.4 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory Path of command file to execute when this event occurs. | |||||||||||||||||||||
| SpcnsContactFault3CommandFileDelay | 1.3.6.1.4.1.318.1.2.3.4.42.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before executing command file (seconds). | |||||||||||||||||||||
| SpcnsContactFault3EnableShutdown | 1.3.6.1.4.1.318.1.2.3.4.42.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Perform a graceful shutdown of the server when this event occurs.
| |||||||||||||||||||||
| SpcnsContactFault3ShutdownDelay | 1.3.6.1.4.1.318.1.2.3.4.42.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before performing a graceful shutdown of the server (seconds). | |||||||||||||||||||||
| NpcnsContactFault4 | 1.3.6.1.4.1.318.1.2.3.4.43 | ||||||||||||||||||||
| SpcnsContactFault4Desc | 1.3.6.1.4.1.318.1.2.3.4.43.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The Description of the event. | |||||||||||||||||||||
| SpcnsContactFault4EnableLogging | 1.3.6.1.4.1.318.1.2.3.4.43.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Log occurrences of this event in PCNS log.
| |||||||||||||||||||||
| SpcnsContactFault4EnableCommandFile | 1.3.6.1.4.1.318.1.2.3.4.43.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Execute a command file when this event occurs.
| |||||||||||||||||||||
| SpcnsContactFault4CommandFilePath | 1.3.6.1.4.1.318.1.2.3.4.43.4 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory Path of command file to execute when this event occurs. | |||||||||||||||||||||
| SpcnsContactFault4CommandFileDelay | 1.3.6.1.4.1.318.1.2.3.4.43.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before executing command file (seconds). | |||||||||||||||||||||
| SpcnsContactFault4EnableShutdown | 1.3.6.1.4.1.318.1.2.3.4.43.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Perform a graceful shutdown of the server when this event occurs.
| |||||||||||||||||||||
| SpcnsContactFault4ShutdownDelay | 1.3.6.1.4.1.318.1.2.3.4.43.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before performing a graceful shutdown of the server (seconds). | |||||||||||||||||||||
| NpcnsContactNormal1 | 1.3.6.1.4.1.318.1.2.3.4.44 | ||||||||||||||||||||
| SpcnsContactNormal1Desc | 1.3.6.1.4.1.318.1.2.3.4.44.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The Description of the event. | |||||||||||||||||||||
| SpcnsContactNormal1EnableLogging | 1.3.6.1.4.1.318.1.2.3.4.44.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Log occurrences of this event in PCNS log.
| |||||||||||||||||||||
| SpcnsContactNormal1EnableCommandFile | 1.3.6.1.4.1.318.1.2.3.4.44.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Execute a command file when this event occurs.
| |||||||||||||||||||||
| SpcnsContactNormal1CommandFilePath | 1.3.6.1.4.1.318.1.2.3.4.44.4 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory Path of command file to execute when this event occurs. | |||||||||||||||||||||
| SpcnsContactNormal1CommandFileDelay | 1.3.6.1.4.1.318.1.2.3.4.44.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before executing command file (seconds). | |||||||||||||||||||||
| NpcnsContactNormal2 | 1.3.6.1.4.1.318.1.2.3.4.45 | ||||||||||||||||||||
| SpcnsContactNormal2Desc | 1.3.6.1.4.1.318.1.2.3.4.45.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The Description of the event. | |||||||||||||||||||||
| SpcnsContactNormal2EnableLogging | 1.3.6.1.4.1.318.1.2.3.4.45.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Log occurrences of this event in PCNS log.
| |||||||||||||||||||||
| SpcnsContactNormal2EnableCommandFile | 1.3.6.1.4.1.318.1.2.3.4.45.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Execute a command file when this event occurs.
| |||||||||||||||||||||
| SpcnsContactNormal2CommandFilePath | 1.3.6.1.4.1.318.1.2.3.4.45.4 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory Path of command file to execute when this event occurs. | |||||||||||||||||||||
| SpcnsContactNormal2CommandFileDelay | 1.3.6.1.4.1.318.1.2.3.4.45.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before executing command file (seconds). | |||||||||||||||||||||
| NpcnsContactNormal3 | 1.3.6.1.4.1.318.1.2.3.4.46 | ||||||||||||||||||||
| SpcnsContactNormal3Desc | 1.3.6.1.4.1.318.1.2.3.4.46.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The Description of the event. | |||||||||||||||||||||
| SpcnsContactNormal3EnableLogging | 1.3.6.1.4.1.318.1.2.3.4.46.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Log occurrences of this event in PCNS log.
| |||||||||||||||||||||
| SpcnsContactNormal3EnableCommandFile | 1.3.6.1.4.1.318.1.2.3.4.46.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Execute a command file when this event occurs.
| |||||||||||||||||||||
| SpcnsContactNormal3CommandFilePath | 1.3.6.1.4.1.318.1.2.3.4.46.4 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory Path of command file to execute when this event occurs. | |||||||||||||||||||||
| SpcnsContactNormal3CommandFileDelay | 1.3.6.1.4.1.318.1.2.3.4.46.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before executing command file (seconds). | |||||||||||||||||||||
| NpcnsContactNormal4 | 1.3.6.1.4.1.318.1.2.3.4.47 | ||||||||||||||||||||
| SpcnsContactNormal4Desc | 1.3.6.1.4.1.318.1.2.3.4.47.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The Description of the event. | |||||||||||||||||||||
| SpcnsContactNormal4EnableLogging | 1.3.6.1.4.1.318.1.2.3.4.47.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Log occurrences of this event in PCNS log.
| |||||||||||||||||||||
| SpcnsContactNormal4EnableCommandFile | 1.3.6.1.4.1.318.1.2.3.4.47.3 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Execute a command file when this event occurs.
| |||||||||||||||||||||
| SpcnsContactNormal4CommandFilePath | 1.3.6.1.4.1.318.1.2.3.4.47.4 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory Path of command file to execute when this event occurs. | |||||||||||||||||||||
| SpcnsContactNormal4CommandFileDelay | 1.3.6.1.4.1.318.1.2.3.4.47.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long to wait after event occurs before executing command file (seconds). | |||||||||||||||||||||
| NpcnsShutdown | 1.3.6.1.4.1.318.1.2.3.5 | ||||||||||||||||||||
| SpcnsShutdownCommandFileEnabled | 1.3.6.1.4.1.318.1.2.3.5.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Run a shutdown command file before performing graceful shutdown.
| |||||||||||||||||||||
| SpcnsShutdownCommandFileDelay | 1.3.6.1.4.1.318.1.2.3.5.2 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long in seconds to wait before running a shutdown command file before graceful shutdown. | |||||||||||||||||||||
| SpcnsShutdownCommandFile | 1.3.6.1.4.1.318.1.2.3.5.3 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory Full name of the shutdown command file to run before graceful shutdown. | |||||||||||||||||||||
| SpcnsShutdownCommandFileDuration | 1.3.6.1.4.1.318.1.2.3.5.4 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory How long in seconds shutdown command file takes to run. | |||||||||||||||||||||
| SpcnsTurnOffUps | 1.3.6.1.4.1.318.1.2.3.5.5 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Turn off the UPS when performing a graceful shutdown.
| |||||||||||||||||||||
| SpcnsTurnOffSOG | 1.3.6.1.4.1.318.1.2.3.5.6 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Turn off the Outlet Group on the UPS when performing a graceful shutdown.
| |||||||||||||||||||||
| SpcnsRuntimeRemainingThreshold | 1.3.6.1.4.1.318.1.2.3.5.7 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory This defines a threshold for runtime remaining. When the UPS is running on battery power and the runtime remaining on the UPS drops below the threshold, PowerChute will trigger a shutdown sequence. | |||||||||||||||||||||
| SpcnsRuntimeRemainingCmdFileThreshold | 1.3.6.1.4.1.318.1.2.3.5.8 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory This defines a threshold for runtime remaining. When runtime remaining drops below this threshold, PowerChute will execute the command file. | |||||||||||||||||||||
| TpcnsAdvancedShutdownTable | 1.3.6.1.4.1.318.1.2.3.5.9 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory The Network Management Cards in the UPS devices, which PCNS is monitoring to provide safe shutdown. | |||||||||||||||||||||
| RpcnsAdvancedShutdownEntry | 1.3.6.1.4.1.318.1.2.3.5.9.1 | NA | mandatory | ||||||||||||||||||
| CpcnsAdvancedGroupNo | 1.3.6.1.4.1.318.1.2.3.5.9.1.1 | Gauge | RO | mandatory | |||||||||||||||||
column · Gauge · read-only · mandatory Index of the Advanced Shutdown Group. | |||||||||||||||||||||
| CpcnsAdvancedGroupName | 1.3.6.1.4.1.318.1.2.3.5.9.1.2 | DisplayString (SIZE (0..32)) | RW | mandatory | |||||||||||||||||
column · DisplayString (SIZE (0..32)) · read-write · mandatory Name of the Advanced Shutdown Group. | |||||||||||||||||||||
| CpcnsAdvancedGroupNMC | 1.3.6.1.4.1.318.1.2.3.5.9.1.3 | DisplayString | RO | mandatory | |||||||||||||||||
column · DisplayString · read-only · mandatory List of NMCs in the Advanced Shutdown Group. | |||||||||||||||||||||
| CpcnsAdvancedShutdownUPSRequiredForLoad | 1.3.6.1.4.1.318.1.2.3.5.9.1.4 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Number of UPS devices required to power load. | |||||||||||||||||||||
| CpcnsAdvancedShutdownCommandFileEnabled | 1.3.6.1.4.1.318.1.2.3.5.9.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Run a shutdown command file before performing graceful shutdown.
| |||||||||||||||||||||
| CpcnsAdvancedShutdownCommandFile | 1.3.6.1.4.1.318.1.2.3.5.9.1.6 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory Full name of the shutdown command file to run before graceful shutdown. | |||||||||||||||||||||
| CpcnsAdvancedShutdownCommandFileDuration | 1.3.6.1.4.1.318.1.2.3.5.9.1.7 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory How long in seconds shutdown command file takes to run. | |||||||||||||||||||||
| CpcnsAdvancedShutdownPowerchuteServer | 1.3.6.1.4.1.318.1.2.3.5.9.1.8 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Shut down PowerChute Server.
| |||||||||||||||||||||
| CpcnsAdvancedShutdownOnLostRedundancy | 1.3.6.1.4.1.318.1.2.3.5.9.1.9 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Shut down if Redundancy lost.
| |||||||||||||||||||||
| CpcnsAdvancedTurnOffUps | 1.3.6.1.4.1.318.1.2.3.5.9.1.10 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Turn off the UPS when performing a graceful shutdown.
| |||||||||||||||||||||
| CpcnsAdvancedTurnOffSOG | 1.3.6.1.4.1.318.1.2.3.5.9.1.11 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory Turn off the Outlet Group on the UPS when performing a graceful shutdown.
| |||||||||||||||||||||
| NpcnsAlarms | 1.3.6.1.4.1.318.1.2.3.6 | ||||||||||||||||||||
| SpcnsCriticalFlag | 1.3.6.1.4.1.318.1.2.3.6.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory PowerChute Network Shutdown has begun a safe shutdown of the host.
| |||||||||||||||||||||
| SpcnsCriticalCause | 1.3.6.1.4.1.318.1.2.3.6.2 | DisplayString (SIZE (0..255)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..255)) · read-only · mandatory The reason PowerChute Network Shutdown has begun a safe shutdown. | |||||||||||||||||||||
| SpcnsNetComsLostFlag | 1.3.6.1.4.1.318.1.2.3.6.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory PowerChute cannot communicate with NMC.
| |||||||||||||||||||||
| SpcnsNMCComsLostFlag | 1.3.6.1.4.1.318.1.2.3.6.4 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory NMC cannot communicate with UPS.
| |||||||||||||||||||||
| SpcnsUpdateAvailableFlag | 1.3.6.1.4.1.318.1.2.3.6.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory PowerChute has detected that a newer version is available.
| |||||||||||||||||||||
| SpcnsUpdateDesc | 1.3.6.1.4.1.318.1.2.3.6.6 | DisplayString (SIZE (0..255)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..255)) · read-only · mandatory Details of the newer version of PowerChute. | |||||||||||||||||||||
| SpcnsLoggingLevel | 1.3.6.1.4.1.318.1.2.3.7 | DisplayString (SIZE (0..6)) | RW | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..6)) · read-write · mandatory Override the Root Logging level for PCNS. Possible Values: CLEAR, DEBUG | |||||||||||||||||||||
| NpowerChuteBusinessEdition | 1.3.6.1.4.1.318.1.2.4 | ||||||||||||||||||||
| NpcbeIdent | 1.3.6.1.4.1.318.1.2.4.1 | ||||||||||||||||||||
| SpcbeHostname | 1.3.6.1.4.1.318.1.2.4.1.1 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The hostname of the PCBE instance. | |||||||||||||||||||||
| SpcbeVersion | 1.3.6.1.4.1.318.1.2.4.1.2 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The version of PCBE installed. x.x.x | |||||||||||||||||||||
| SpcbeOS | 1.3.6.1.4.1.318.1.2.4.1.3 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The version of OS PCBE is installed on. | |||||||||||||||||||||
| SpcbeJavaVersion | 1.3.6.1.4.1.318.1.2.4.1.4 | DisplayString (SIZE (0..32)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..32)) · read-only · mandatory The version of Java PCBE is running on. | |||||||||||||||||||||
| SpcbeUIProtocol | 1.3.6.1.4.1.318.1.2.4.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Web Protocol used to connect to the PCBE UI.
| |||||||||||||||||||||
| SpcbeHttpPort | 1.3.6.1.4.1.318.1.2.4.1.6 | INTEGER (0..65535) | RO | mandatory | |||||||||||||||||
scalar · INTEGER (0..65535) · read-only · mandatory Port used for PCBE http UI. | |||||||||||||||||||||
| SpcbeHttpsPort | 1.3.6.1.4.1.318.1.2.4.1.7 | INTEGER (0..65535) | RO | mandatory | |||||||||||||||||
scalar · INTEGER (0..65535) · read-only · mandatory Port used for PCBE https UI. | |||||||||||||||||||||
| NpcbeAlarms | 1.3.6.1.4.1.318.1.2.4.6 | ||||||||||||||||||||
| SpcbeCriticalFlag | 1.3.6.1.4.1.318.1.2.4.6.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory PowerChute Business Edition has begun a safe shutdown of the host.
| |||||||||||||||||||||
| SpcbeCriticalCause | 1.3.6.1.4.1.318.1.2.4.6.2 | DisplayString (SIZE (0..255)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..255)) · read-only · mandatory The reason PowerChute Business Edition has begun a safe shutdown. | |||||||||||||||||||||
| SpcbeComsLostFlag | 1.3.6.1.4.1.318.1.2.4.6.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory If active (1), PowerChute cannot communicate with UPS
| |||||||||||||||||||||
| SpcbeUpdateAvailableFlag | 1.3.6.1.4.1.318.1.2.4.6.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory PowerChute has detected that a newer version is available.
| |||||||||||||||||||||
| SpcbeUpdateDesc | 1.3.6.1.4.1.318.1.2.4.6.6 | DisplayString (SIZE (0..255)) | RO | mandatory | |||||||||||||||||
scalar · DisplayString (SIZE (0..255)) · read-only · mandatory Details of the newer version of PowerChute. | |||||||||||||||||||||
| Nsystem | 1.3.6.1.4.1.318.1.3 | ||||||||||||||||||||
| NbackUPS | 1.3.6.1.4.1.318.1.3.1 | ||||||||||||||||||||
| NsmartUPS | 1.3.6.1.4.1.318.1.3.2 | ||||||||||||||||||||
| NsmartUPS250 | 1.3.6.1.4.1.318.1.3.2.1 | ||||||||||||||||||||
| NsmartUPS400 | 1.3.6.1.4.1.318.1.3.2.2 | ||||||||||||||||||||
| NsmartUPS600 | 1.3.6.1.4.1.318.1.3.2.3 | ||||||||||||||||||||
| NsmartUPS900 | 1.3.6.1.4.1.318.1.3.2.4 | ||||||||||||||||||||
| NsmartUPS1250 | 1.3.6.1.4.1.318.1.3.2.5 | ||||||||||||||||||||
| NsmartUPS2000 | 1.3.6.1.4.1.318.1.3.2.6 | ||||||||||||||||||||
| NsmartUPS450 | 1.3.6.1.4.1.318.1.3.2.7 | ||||||||||||||||||||
| NsmartUPS700 | 1.3.6.1.4.1.318.1.3.2.8 | ||||||||||||||||||||
| NsmartUPS1000 | 1.3.6.1.4.1.318.1.3.2.9 | ||||||||||||||||||||
| NsmartUPS1400 | 1.3.6.1.4.1.318.1.3.2.10 | ||||||||||||||||||||
| NsmartUPS2200 | 1.3.6.1.4.1.318.1.3.2.11 | ||||||||||||||||||||
| NsmartUPS3000 | 1.3.6.1.4.1.318.1.3.2.12 | ||||||||||||||||||||
| NsmartUPS5000 | 1.3.6.1.4.1.318.1.3.2.13 | ||||||||||||||||||||
| NsmartUPS7500 | 1.3.6.1.4.1.318.1.3.2.14 | ||||||||||||||||||||
| NsmartUPS10000 | 1.3.6.1.4.1.318.1.3.2.15 | ||||||||||||||||||||
| NsmartUPS1500 | 1.3.6.1.4.1.318.1.3.2.16 | ||||||||||||||||||||
| NsmartUPS3000DSP | 1.3.6.1.4.1.318.1.3.2.17 | ||||||||||||||||||||
| NsmartUPS5000DSP | 1.3.6.1.4.1.318.1.3.2.18 | ||||||||||||||||||||
| NsmartUPS8000 | 1.3.6.1.4.1.318.1.3.2.19 | ||||||||||||||||||||
| NmatrixUPS | 1.3.6.1.4.1.318.1.3.3 | ||||||||||||||||||||
| NmatrixUPS3000 | 1.3.6.1.4.1.318.1.3.3.1 | ||||||||||||||||||||
| NmatrixUPS5000 | 1.3.6.1.4.1.318.1.3.3.2 | ||||||||||||||||||||
| NmasterSwitch | 1.3.6.1.4.1.318.1.3.4 | ||||||||||||||||||||
| NmasterSwitchV1 | 1.3.6.1.4.1.318.1.3.4.1 | ||||||||||||||||||||
| NmasterSwitchV2 | 1.3.6.1.4.1.318.1.3.4.2 | ||||||||||||||||||||
| NmasterSwitchVM | 1.3.6.1.4.1.318.1.3.4.3 | ||||||||||||||||||||
| NmasterSwitchMSP | 1.3.6.1.4.1.318.1.3.4.4 | ||||||||||||||||||||
| NmasterSwitchrPDU | 1.3.6.1.4.1.318.1.3.4.5 | ||||||||||||||||||||
| NmasterSwitchrPDU2 | 1.3.6.1.4.1.318.1.3.4.6 | ||||||||||||||||||||
| NmasterSwitchsPDU | 1.3.6.1.4.1.318.1.3.4.7 | ||||||||||||||||||||
| NmasterSwitchrPDUB | 1.3.6.1.4.1.318.1.3.4.8 | ||||||||||||||||||||
| NmasterSwitchePDU | 1.3.6.1.4.1.318.1.3.4.9 | ||||||||||||||||||||
| NsymmetraUPS | 1.3.6.1.4.1.318.1.3.5 | ||||||||||||||||||||
| NsymmetraUPS4kVA | 1.3.6.1.4.1.318.1.3.5.1 | ||||||||||||||||||||
| NsymmetraUPS8kVA | 1.3.6.1.4.1.318.1.3.5.2 | ||||||||||||||||||||
| NsymmetraUPS12kVA | 1.3.6.1.4.1.318.1.3.5.3 | ||||||||||||||||||||
| NsymmetraUPS16kVA | 1.3.6.1.4.1.318.1.3.5.4 | ||||||||||||||||||||
| Ndp100E | 1.3.6.1.4.1.318.1.3.6 | ||||||||||||||||||||
| Ndp300E | 1.3.6.1.4.1.318.1.3.7 | ||||||||||||||||||||
| Nmonitors | 1.3.6.1.4.1.318.1.3.8 | ||||||||||||||||||||
| Nenvironmental | 1.3.6.1.4.1.318.1.3.8.1 | ||||||||||||||||||||
| NenvironmentalMgtSystem | 1.3.6.1.4.1.318.1.3.8.2 | ||||||||||||||||||||
| Nemu2 | 1.3.6.1.4.1.318.1.3.8.3 | ||||||||||||||||||||
| Nmem | 1.3.6.1.4.1.318.1.3.8.4 | ||||||||||||||||||||
| NredundantSwitch | 1.3.6.1.4.1.318.1.3.9 | ||||||||||||||||||||
| NdcPower | 1.3.6.1.4.1.318.1.3.10 | ||||||||||||||||||||
| Ndm3 | 1.3.6.1.4.1.318.1.3.10.1 | ||||||||||||||||||||
| Ndcmim2 | 1.3.6.1.4.1.318.1.3.10.2 | ||||||||||||||||||||
| NautomaticXferSwitch | 1.3.6.1.4.1.318.1.3.11 | ||||||||||||||||||||
| NnetLock | 1.3.6.1.4.1.318.1.3.12 | ||||||||||||||||||||
| Nsymmetra3PhaseUPS | 1.3.6.1.4.1.318.1.3.13 | ||||||||||||||||||||
| Nsymmetra3PhaseUPS40kVA | 1.3.6.1.4.1.318.1.3.13.1 | ||||||||||||||||||||
| Nsymmetra3PhaseUPS60kVA | 1.3.6.1.4.1.318.1.3.13.2 | ||||||||||||||||||||
| Nsymmetra3PhaseUPS80kVA | 1.3.6.1.4.1.318.1.3.13.3 | ||||||||||||||||||||
| Nsymmetra3PhaseUPS20kVA | 1.3.6.1.4.1.318.1.3.13.4 | ||||||||||||||||||||
| NnetworkAir | 1.3.6.1.4.1.318.1.3.14 | ||||||||||||||||||||
| NairFMSeries | 1.3.6.1.4.1.318.1.3.14.1 | ||||||||||||||||||||
| NrackAirRemovalUnit | 1.3.6.1.4.1.318.1.3.14.2 | ||||||||||||||||||||
| NairPASeries | 1.3.6.1.4.1.318.1.3.14.3 | ||||||||||||||||||||
| NairIRSC100Series | 1.3.6.1.4.1.318.1.3.14.4 | ||||||||||||||||||||
| NairIRRC100Series | 1.3.6.1.4.1.318.1.3.14.5 | ||||||||||||||||||||
| NairIRRP100Series | 1.3.6.1.4.1.318.1.3.14.6 | ||||||||||||||||||||
| NairIRRP500Series | 1.3.6.1.4.1.318.1.3.14.7 | ||||||||||||||||||||
| NairIRRD100Series | 1.3.6.1.4.1.318.1.3.14.8 | ||||||||||||||||||||
| NairInRoomPerimeter | 1.3.6.1.4.1.318.1.3.14.9 | ||||||||||||||||||||
| NairACRC300Series | 1.3.6.1.4.1.318.1.3.14.10 | ||||||||||||||||||||
| NairLESeries | 1.3.6.1.4.1.318.1.3.14.11 | ||||||||||||||||||||
| NairIRRDU | 1.3.6.1.4.1.318.1.3.14.12 | ||||||||||||||||||||
| NairEcoBreeze | 1.3.6.1.4.1.318.1.3.14.13 | ||||||||||||||||||||
| NairLELSeries | 1.3.6.1.4.1.318.1.3.14.14 | ||||||||||||||||||||
| NairACRC600Series | 1.3.6.1.4.1.318.1.3.14.15 | ||||||||||||||||||||
| NairACRD600Series | 1.3.6.1.4.1.318.1.3.14.16 | ||||||||||||||||||||
| NairEconomizer | 1.3.6.1.4.1.318.1.3.14.17 | ||||||||||||||||||||
| NairTSAChillers | 1.3.6.1.4.1.318.1.3.14.18 | ||||||||||||||||||||
| NairLEG2Series | 1.3.6.1.4.1.318.1.3.14.19 | ||||||||||||||||||||
| NairAmico | 1.3.6.1.4.1.318.1.3.14.20 | ||||||||||||||||||||
| NairUniflarSP | 1.3.6.1.4.1.318.1.3.14.21 | ||||||||||||||||||||
| NairTrimChiller | 1.3.6.1.4.1.318.1.3.14.22 | ||||||||||||||||||||
| NairACRD300Series | 1.3.6.1.4.1.318.1.3.14.23 | ||||||||||||||||||||
| NairAquaCentr | 1.3.6.1.4.1.318.1.3.14.24 | ||||||||||||||||||||
| NairLeoGen2Series | 1.3.6.1.4.1.318.1.3.14.25 | ||||||||||||||||||||
| NinfraStruXurePDU | 1.3.6.1.4.1.318.1.3.15 | ||||||||||||||||||||
| Nais5000UPS | 1.3.6.1.4.1.318.1.3.16 | ||||||||||||||||||||
| Nais5000UPS10kVA | 1.3.6.1.4.1.318.1.3.16.1 | ||||||||||||||||||||
| Nais5000UPS20kVA | 1.3.6.1.4.1.318.1.3.16.2 | ||||||||||||||||||||
| Nais5000UPS30kVA | 1.3.6.1.4.1.318.1.3.16.3 | ||||||||||||||||||||
| Nais5000UPS40kVA | 1.3.6.1.4.1.318.1.3.16.4 | ||||||||||||||||||||
| Nais5000UPS60kVA | 1.3.6.1.4.1.318.1.3.16.5 | ||||||||||||||||||||
| Nais5000UPS80kVA | 1.3.6.1.4.1.318.1.3.16.6 | ||||||||||||||||||||
| Nais5000UPS100kVA | 1.3.6.1.4.1.318.1.3.16.7 | ||||||||||||||||||||
| NsmartUPS3Phase | 1.3.6.1.4.1.318.1.3.17 | ||||||||||||||||||||
| NsmartUPS3Phase10kVA | 1.3.6.1.4.1.318.1.3.17.1 | ||||||||||||||||||||
| NsmartUPS3Phase15kVA | 1.3.6.1.4.1.318.1.3.17.2 | ||||||||||||||||||||
| NsmartUPS3Phase20kVA | 1.3.6.1.4.1.318.1.3.17.3 | ||||||||||||||||||||
| NsmartUPS3Phase30kVA | 1.3.6.1.4.1.318.1.3.17.4 | ||||||||||||||||||||
| NsmartUPS3Phase40kVA | 1.3.6.1.4.1.318.1.3.17.5 | ||||||||||||||||||||
| NbattManager | 1.3.6.1.4.1.318.1.3.18 | ||||||||||||||||||||
| NinfraStruXureATS | 1.3.6.1.4.1.318.1.3.19 | ||||||||||||||||||||
| NconPortServ | 1.3.6.1.4.1.318.1.3.20 | ||||||||||||||||||||
| NconPortServAP930x | 1.3.6.1.4.1.318.1.3.20.1 | ||||||||||||||||||||
| Ngutor | 1.3.6.1.4.1.318.1.3.21 | ||||||||||||||||||||
| NgutorPEW | 1.3.6.1.4.1.318.1.3.21.1 | ||||||||||||||||||||
| NgutorPDW | 1.3.6.1.4.1.318.1.3.21.2 | ||||||||||||||||||||
| NgutorWEW | 1.3.6.1.4.1.318.1.3.21.3 | ||||||||||||||||||||
| NgutorWDW | 1.3.6.1.4.1.318.1.3.21.4 | ||||||||||||||||||||
| NgutorSDC | 1.3.6.1.4.1.318.1.3.21.5 | ||||||||||||||||||||
| NgutorPXP | 1.3.6.1.4.1.318.1.3.21.6 | ||||||||||||||||||||
| NgutorPXC | 1.3.6.1.4.1.318.1.3.21.7 | ||||||||||||||||||||
| NgutorModularCharger | 1.3.6.1.4.1.318.1.3.21.8 | ||||||||||||||||||||
| NgutorModularInverter | 1.3.6.1.4.1.318.1.3.21.9 | ||||||||||||||||||||
| NgutorModularUPS | 1.3.6.1.4.1.318.1.3.21.10 | ||||||||||||||||||||
| NaccControl | 1.3.6.1.4.1.318.1.3.22 | ||||||||||||||||||||
| NaccPX | 1.3.6.1.4.1.318.1.3.22.1 | ||||||||||||||||||||
| NsymmetraPX | 1.3.6.1.4.1.318.1.3.23 | ||||||||||||||||||||
| NsymmetraPx48kVA | 1.3.6.1.4.1.318.1.3.23.1 | ||||||||||||||||||||
| NsymmetraPx160kVA | 1.3.6.1.4.1.318.1.3.23.2 | ||||||||||||||||||||
| NsymmetraPx250kVA | 1.3.6.1.4.1.318.1.3.23.3 | ||||||||||||||||||||
| NsymmetraPx500kVA | 1.3.6.1.4.1.318.1.3.23.4 | ||||||||||||||||||||
| NsymmetraPx100kVA | 1.3.6.1.4.1.318.1.3.23.5 | ||||||||||||||||||||
| NsymmetraPxDisplay | 1.3.6.1.4.1.318.1.3.23.6 | ||||||||||||||||||||
| NisxModDistribution | 1.3.6.1.4.1.318.1.3.24 | ||||||||||||||||||||
| Nisx24ModuleHalfRackPdu | 1.3.6.1.4.1.318.1.3.24.1 | ||||||||||||||||||||
| Nisx6ModuleRackPdu | 1.3.6.1.4.1.318.1.3.24.2 | ||||||||||||||||||||
| NisxServers | 1.3.6.1.4.1.318.1.3.25 | ||||||||||||||||||||
| NisxcBasic | 1.3.6.1.4.1.318.1.3.25.1 | ||||||||||||||||||||
| NisxcStandard | 1.3.6.1.4.1.318.1.3.25.2 | ||||||||||||||||||||
| NisxcEnterprise | 1.3.6.1.4.1.318.1.3.25.3 | ||||||||||||||||||||
| NisxcVirtual | 1.3.6.1.4.1.318.1.3.25.4 | ||||||||||||||||||||
| NsmartUPS2 | 1.3.6.1.4.1.318.1.3.27 | ||||||||||||||||||||
| Ngalaxy | 1.3.6.1.4.1.318.1.3.28 | ||||||||||||||||||||
| Ngalaxy7000UPS200kVA | 1.3.6.1.4.1.318.1.3.28.1 | ||||||||||||||||||||
| Ngalaxy7000UPS250kVA | 1.3.6.1.4.1.318.1.3.28.2 | ||||||||||||||||||||
| Ngalaxy7000UPS300kVA | 1.3.6.1.4.1.318.1.3.28.3 | ||||||||||||||||||||
| Ngalaxy7000UPS400kVA | 1.3.6.1.4.1.318.1.3.28.4 | ||||||||||||||||||||
| Ngalaxy7000UPS500kVA | 1.3.6.1.4.1.318.1.3.28.5 | ||||||||||||||||||||
| Ngalaxy7000SSC800kVA | 1.3.6.1.4.1.318.1.3.28.6 | ||||||||||||||||||||
| Ngalaxy7000SSC1200kVA | 1.3.6.1.4.1.318.1.3.28.7 | ||||||||||||||||||||
| Ngalaxy7000SSC2000kVA | 1.3.6.1.4.1.318.1.3.28.8 | ||||||||||||||||||||
| Ngalaxy300UPS10kVA33 | 1.3.6.1.4.1.318.1.3.28.9 | ||||||||||||||||||||
| Ngalaxy300UPS15kVA33 | 1.3.6.1.4.1.318.1.3.28.10 | ||||||||||||||||||||
| Ngalaxy300UPS20kVA33 | 1.3.6.1.4.1.318.1.3.28.11 | ||||||||||||||||||||
| Ngalaxy300UPS30kVA33 | 1.3.6.1.4.1.318.1.3.28.12 | ||||||||||||||||||||
| Ngalaxy300UPS40kVA33 | 1.3.6.1.4.1.318.1.3.28.13 | ||||||||||||||||||||
| Ngalaxy300UPS10kVA31 | 1.3.6.1.4.1.318.1.3.28.14 | ||||||||||||||||||||
| Ngalaxy300UPS15kVA31 | 1.3.6.1.4.1.318.1.3.28.15 | ||||||||||||||||||||
| Ngalaxy300UPS20kVA31 | 1.3.6.1.4.1.318.1.3.28.16 | ||||||||||||||||||||
| Ngalaxy300UPS30kVA31 | 1.3.6.1.4.1.318.1.3.28.17 | ||||||||||||||||||||
| Ngalaxy5000UPS20KVA | 1.3.6.1.4.1.318.1.3.28.18 | ||||||||||||||||||||
| Ngalaxy5000UPS30KVA | 1.3.6.1.4.1.318.1.3.28.19 | ||||||||||||||||||||
| Ngalaxy5000UPS40KVA | 1.3.6.1.4.1.318.1.3.28.20 | ||||||||||||||||||||
| Ngalaxy5000UPS50KVA | 1.3.6.1.4.1.318.1.3.28.21 | ||||||||||||||||||||
| Ngalaxy5000UPS60KVA | 1.3.6.1.4.1.318.1.3.28.22 | ||||||||||||||||||||
| Ngalaxy5000UPS80KVA | 1.3.6.1.4.1.318.1.3.28.23 | ||||||||||||||||||||
| Ngalaxy5000UPS100KVA | 1.3.6.1.4.1.318.1.3.28.24 | ||||||||||||||||||||
| Ngalaxy5000UPS120KVA | 1.3.6.1.4.1.318.1.3.28.25 | ||||||||||||||||||||
| Ngalaxy5000UPS130KVA | 1.3.6.1.4.1.318.1.3.28.26 | ||||||||||||||||||||
| Ngalaxy5500UPS20KVA | 1.3.6.1.4.1.318.1.3.28.27 | ||||||||||||||||||||
| Ngalaxy5500UPS30KVA | 1.3.6.1.4.1.318.1.3.28.28 | ||||||||||||||||||||
| Ngalaxy5500UPS40KVA | 1.3.6.1.4.1.318.1.3.28.29 | ||||||||||||||||||||
| Ngalaxy5500UPS50KVA | 1.3.6.1.4.1.318.1.3.28.30 | ||||||||||||||||||||
| Ngalaxy5500UPS60KVA | 1.3.6.1.4.1.318.1.3.28.31 | ||||||||||||||||||||
| Ngalaxy5500UPS80KVA | 1.3.6.1.4.1.318.1.3.28.32 | ||||||||||||||||||||
| Ngalaxy5500UPS100KVA | 1.3.6.1.4.1.318.1.3.28.33 | ||||||||||||||||||||
| Ngalaxy5500UPS120KVA | 1.3.6.1.4.1.318.1.3.28.34 | ||||||||||||||||||||
| Ngalaxy5500UPS130KVA | 1.3.6.1.4.1.318.1.3.28.35 | ||||||||||||||||||||
| NgalaxyVMUPS50kVA | 1.3.6.1.4.1.318.1.3.28.36 | ||||||||||||||||||||
| NgalaxyVMUPS60kVA | 1.3.6.1.4.1.318.1.3.28.37 | ||||||||||||||||||||
| NgalaxyVMUPS80kVA | 1.3.6.1.4.1.318.1.3.28.38 | ||||||||||||||||||||
| NgalaxyVMUPS90kVA | 1.3.6.1.4.1.318.1.3.28.39 | ||||||||||||||||||||
| NgalaxyVMUPS100kVA | 1.3.6.1.4.1.318.1.3.28.40 | ||||||||||||||||||||
| NgalaxyVMUPS110kVA | 1.3.6.1.4.1.318.1.3.28.41 | ||||||||||||||||||||
| NgalaxyVMUPS120kVA | 1.3.6.1.4.1.318.1.3.28.42 | ||||||||||||||||||||
| NgalaxyVMUPS130kVA | 1.3.6.1.4.1.318.1.3.28.43 | ||||||||||||||||||||
| NgalaxyVMUPS160kVA | 1.3.6.1.4.1.318.1.3.28.44 | ||||||||||||||||||||
| NgalaxyVMUPS180kVA | 1.3.6.1.4.1.318.1.3.28.45 | ||||||||||||||||||||
| NgalaxyVMUPS200kVA | 1.3.6.1.4.1.318.1.3.28.46 | ||||||||||||||||||||
| NgalaxyVMUPS225kVA | 1.3.6.1.4.1.318.1.3.28.47 | ||||||||||||||||||||
| Ngalaxy9000UPS | 1.3.6.1.4.1.318.1.3.28.48 | ||||||||||||||||||||
| Ngalaxy9000SSC | 1.3.6.1.4.1.318.1.3.28.49 | ||||||||||||||||||||
| Ngalaxy9000UPSWithSSC | 1.3.6.1.4.1.318.1.3.28.50 | ||||||||||||||||||||
| Ngalaxy9000FreqConverter | 1.3.6.1.4.1.318.1.3.28.51 | ||||||||||||||||||||
| NgalaxyVXUPS625kVA | 1.3.6.1.4.1.318.1.3.28.56 | ||||||||||||||||||||
| NgalaxyVXUPS750kVA | 1.3.6.1.4.1.318.1.3.28.57 | ||||||||||||||||||||
| NgalaxyVXUPS1000kVA | 1.3.6.1.4.1.318.1.3.28.58 | ||||||||||||||||||||
| NgalaxyVXUPS1250kVA | 1.3.6.1.4.1.318.1.3.28.59 | ||||||||||||||||||||
| NgalaxyVXUPS1500kVA | 1.3.6.1.4.1.318.1.3.28.60 | ||||||||||||||||||||
| Ngalaxy300UPS60kVA33 | 1.3.6.1.4.1.318.1.3.28.61 | ||||||||||||||||||||
| Ngalaxy300UPS80kVA33 | 1.3.6.1.4.1.318.1.3.28.62 | ||||||||||||||||||||
| NgalaxyVXUPS500kVA | 1.3.6.1.4.1.318.1.3.28.63 | ||||||||||||||||||||
| NgalaxyVXUPS250kVA | 1.3.6.1.4.1.318.1.3.28.64 | ||||||||||||||||||||
| NgalaxyVXUPS400kVA | 1.3.6.1.4.1.318.1.3.28.65 | ||||||||||||||||||||
| NgalaxyVSUPS100kW | 1.3.6.1.4.1.318.1.3.28.66 | ||||||||||||||||||||
| Ngalaxy7000UPS160kVA | 1.3.6.1.4.1.318.1.3.28.67 | ||||||||||||||||||||
| NgalaxyVXUPS300kVA | 1.3.6.1.4.1.318.1.3.28.68 | ||||||||||||||||||||
| NgalaxyVXUPS1100kVA | 1.3.6.1.4.1.318.1.3.28.69 | ||||||||||||||||||||
| NgalaxyVSUPS10kW | 1.3.6.1.4.1.318.1.3.28.70 | ||||||||||||||||||||
| NgalaxyVSUPS15kW | 1.3.6.1.4.1.318.1.3.28.71 | ||||||||||||||||||||
| NgalaxyVSUPS20kW | 1.3.6.1.4.1.318.1.3.28.72 | ||||||||||||||||||||
| NgalaxyVSUPS25kW | 1.3.6.1.4.1.318.1.3.28.73 | ||||||||||||||||||||
| NgalaxyVSUPS30kW | 1.3.6.1.4.1.318.1.3.28.74 | ||||||||||||||||||||
| NgalaxyVSUPS40kW | 1.3.6.1.4.1.318.1.3.28.75 | ||||||||||||||||||||
| NgalaxyVSUPS50kW | 1.3.6.1.4.1.318.1.3.28.76 | ||||||||||||||||||||
| NgalaxyVSUPS60kW | 1.3.6.1.4.1.318.1.3.28.77 | ||||||||||||||||||||
| NgalaxyVSUPS75kW | 1.3.6.1.4.1.318.1.3.28.78 | ||||||||||||||||||||
| NgalaxyVSUPS80kW | 1.3.6.1.4.1.318.1.3.28.79 | ||||||||||||||||||||
| NgalaxyVSUPS120kW | 1.3.6.1.4.1.318.1.3.28.80 | ||||||||||||||||||||
| NgalaxyVSUPS150kW | 1.3.6.1.4.1.318.1.3.28.81 | ||||||||||||||||||||
| NgalaxyVXUPS800kVA | 1.3.6.1.4.1.318.1.3.28.82 | ||||||||||||||||||||
| NgalaxyPXUPS60kW | 1.3.6.1.4.1.318.1.3.28.83 | ||||||||||||||||||||
| NgalaxyPXUPS80kW | 1.3.6.1.4.1.318.1.3.28.84 | ||||||||||||||||||||
| NgalaxyPXUPS100kW | 1.3.6.1.4.1.318.1.3.28.85 | ||||||||||||||||||||
| NgalaxyVLUPS500kW | 1.3.6.1.4.1.318.1.3.28.86 | ||||||||||||||||||||
| NgalaxyPXUPS250kW | 1.3.6.1.4.1.318.1.3.28.87 | ||||||||||||||||||||
| NgalaxyVXLUPS1250kW | 1.3.6.1.4.1.318.1.3.28.88 | ||||||||||||||||||||
| Neps | 1.3.6.1.4.1.318.1.3.30 | ||||||||||||||||||||
| Neps6000UPS | 1.3.6.1.4.1.318.1.3.30.1 | ||||||||||||||||||||
| Neps6000SSC | 1.3.6.1.4.1.318.1.3.30.2 | ||||||||||||||||||||
| Neps6000UPSWithSSC | 1.3.6.1.4.1.318.1.3.30.3 | ||||||||||||||||||||
| Neps6000FreqConverter | 1.3.6.1.4.1.318.1.3.30.4 | ||||||||||||||||||||
| Neps7000UPS | 1.3.6.1.4.1.318.1.3.30.5 | ||||||||||||||||||||
| Neps7000SSC | 1.3.6.1.4.1.318.1.3.30.6 | ||||||||||||||||||||
| Neps7000UPSWithSSC | 1.3.6.1.4.1.318.1.3.30.7 | ||||||||||||||||||||
| Neps7000FreqConverter | 1.3.6.1.4.1.318.1.3.30.8 | ||||||||||||||||||||
| Neps8000UPS | 1.3.6.1.4.1.318.1.3.30.9 | ||||||||||||||||||||
| Neps8000SSC | 1.3.6.1.4.1.318.1.3.30.10 | ||||||||||||||||||||
| Neps8000UPSWithSSC | 1.3.6.1.4.1.318.1.3.30.11 | ||||||||||||||||||||
| Neps8000FreqConverter | 1.3.6.1.4.1.318.1.3.30.12 | ||||||||||||||||||||
| Npcns | 1.3.6.1.4.1.318.1.3.31 | ||||||||||||||||||||
| Npcns4 | 1.3.6.1.4.1.318.1.3.31.1 | ||||||||||||||||||||
| NautomaticXferSwitch4G | 1.3.6.1.4.1.318.1.3.32 | ||||||||||||||||||||
| Npcbe | 1.3.6.1.4.1.318.1.3.33 | ||||||||||||||||||||
| Npcbe9 | 1.3.6.1.4.1.318.1.3.33.1 | ||||||||||||||||||||
| Npmm | 1.3.6.1.4.1.318.1.3.34 | ||||||||||||||||||||
| Npmm400kVA | 1.3.6.1.4.1.318.1.3.34.1 | ||||||||||||||||||||
| Npmm500kVA | 1.3.6.1.4.1.318.1.3.34.2 | ||||||||||||||||||||
| Npmm1000kVA | 1.3.6.1.4.1.318.1.3.34.3 | ||||||||||||||||||||
| Nrpp | 1.3.6.1.4.1.318.1.3.35 | ||||||||||||||||||||
| Nrpp400kVA | 1.3.6.1.4.1.318.1.3.35.1 | ||||||||||||||||||||
| Nrpp250kVA | 1.3.6.1.4.1.318.1.3.35.2 | ||||||||||||||||||||
| Nmicrodc | 1.3.6.1.4.1.318.1.3.36 | ||||||||||||||||||||
| NkiteMDC | 1.3.6.1.4.1.318.1.3.36.1 | ||||||||||||||||||||
| NeasyMDC | 1.3.6.1.4.1.318.1.3.36.2 | ||||||||||||||||||||
| NeasyUPS | 1.3.6.1.4.1.318.1.3.37 | ||||||||||||||||||||
| NeasyUPS1P | 1.3.6.1.4.1.318.1.3.37.1 | ||||||||||||||||||||
| NeasyUPS3P | 1.3.6.1.4.1.318.1.3.37.2 | ||||||||||||||||||||
| NeasyUPS250kW | 1.3.6.1.4.1.318.1.3.37.3 | ||||||||||||||||||||
| NautomaticXferSwitch5G | 1.3.6.1.4.1.318.1.3.38 | ||||||||||||||||||||
| NsmartUPSUltra | 1.3.6.1.4.1.318.1.3.39 | ||||||||||||||||||||
| Nexperimental | 1.3.6.1.4.1.318.1.4 | ||||||||||||||||||||
| Napcmgmt | 1.3.6.1.4.1.318.2 | ||||||||||||||||||||
| Nmconfig | 1.3.6.1.4.1.318.2.1 | ||||||||||||||||||||
| SmconfigNumTrapReceivers | 1.3.6.1.4.1.318.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The number of managers to send traps to. | |||||||||||||||||||||
| TmconfigTrapReceiverTable | 1.3.6.1.4.1.318.2.1.2 | NA | mandatory | ||||||||||||||||||
table · not-accessible · mandatory A list of managers to send traps to. The number of entries is given by the value of mconfigNumTrapReceivers. | |||||||||||||||||||||
| RmconfigTrapReceiverEntry | 1.3.6.1.4.1.318.2.1.2.1 | NA | mandatory | ||||||||||||||||||
| CtrapIndex | 1.3.6.1.4.1.318.2.1.2.1.1 | INTEGER | RO | mandatory | |||||||||||||||||
column · INTEGER · read-only · mandatory The index to a trap receiver entry. | |||||||||||||||||||||
| CreceiverAddr | 1.3.6.1.4.1.318.2.1.2.1.2 | IpAddress | RW | mandatory | |||||||||||||||||
column · IpAddress · read-write · mandatory The IP address of the manager to send a trap to. | |||||||||||||||||||||
| CcommunityString | 1.3.6.1.4.1.318.2.1.2.1.3 | DisplayString | RW | mandatory | |||||||||||||||||
column · DisplayString · read-write · mandatory The community name to use in the trap when sent to the manager. | |||||||||||||||||||||
| Cseverity | 1.3.6.1.4.1.318.2.1.2.1.4 | INTEGER | RO | obsolete | |||||||||||||||||
column · INTEGER · read-only · obsolete The severity threshold of traps to send to the manager. traps are labeled in severity as informational(1), warning(2), severe(3). Only traps of equal or greater severity than this value are sent to the manager.
| |||||||||||||||||||||
| CacceptThisReceiver | 1.3.6.1.4.1.318.2.1.2.1.5 | INTEGER | RW | mandatory | |||||||||||||||||
column · INTEGER · read-write · mandatory The value of yes(1) indicates that trap generation for this manager is enabled. The value of no(2) indicates that trap generation for this manager is disabled
| |||||||||||||||||||||
| CreceiveTrapType | 1.3.6.1.4.1.318.2.1.2.1.6 | INTEGER | RO | obsolete | |||||||||||||||||
column · INTEGER · read-only · obsolete Type of trap.
| |||||||||||||||||||||
| SmconfigBOOTPEnabled | 1.3.6.1.4.1.318.2.1.3 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory The value of yes(1) indicates the PowerNet Adapter is configured to obtain its IP configuration parameters from a BOOTP server. The value of no(2) indicates adapter will assume IP configuration parameters values saved in adapter's eeprom, which was originally configured at local console.
| |||||||||||||||||||||
| SmconfigTFTPServerIP | 1.3.6.1.4.1.318.2.1.4 | IpAddress | RW | mandatory | |||||||||||||||||
scalar · IpAddress · read-write · mandatory The IP address of TFTP server. If mconfigBOOTPEnabled is yes(1), then this IP address is provided by BOOTP server and not allowed to be modified; otherwise, this IP address can be modified. Before using TFTP to load new code image, the image file should be placed in proper directory of the specified TFTP server. This OID is only supported by APC Network Management Cards. | |||||||||||||||||||||
| SnewCodeAuthentViaTFTP | 1.3.6.1.4.1.318.2.1.5 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory Once mcontrolRestartAgent is set to loadAndExecuteNewAgent (3), PowerNet adapter will
start to load the remote image file, for authentication only, instead of saving the code
into flash memory. Only if a validNewAgentCodeImage (1) is found will the agent reboot
the PowerNet adapter and invoke the loader to load and save new code into the flash memory.
Otherwise, the current agent code will continue to run.
This OID shows the result of the above authentication process.
validNewAgentCodeImage (1) means the code image on TFTP server
is a valid APC agent code and is different version from the current agent.
Once agent identifies this, loader will start to update flash memory with
the new agent code.
sameAgentCodeImage (2) means the code image on TFTP server is exactly the
same as the currently running agent. Currently running agent will not invoke
loader to load the same again.
invalidAgentCodeImage (3) means the code image on TFTP server is NOT a valid
APC agent code. Thus, current agent will not load it into the flash memory.
The value of this OID will be associated with TRAP codeImageAuthentDone.
This OID is only supported by APC Network Management Cards.
| |||||||||||||||||||||
| NmconfigClock | 1.3.6.1.4.1.318.2.1.6 | ||||||||||||||||||||
| SmconfigClockDate | 1.3.6.1.4.1.318.2.1.6.1 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory The current date in the mm/dd/yyyy format. Example: 01/01/2000. | |||||||||||||||||||||
| SmconfigClockTime | 1.3.6.1.4.1.318.2.1.6.2 | DisplayString | RW | mandatory | |||||||||||||||||
scalar · DisplayString · read-write · mandatory The current time in the hh:mm:ss am/pm format. Example: 12:00:00 am. | |||||||||||||||||||||
| Nmcontrol | 1.3.6.1.4.1.318.2.2 | ||||||||||||||||||||
| SmcontrolRestartAgent | 1.3.6.1.4.1.318.2.2.1 | INTEGER | RW | mandatory | |||||||||||||||||
scalar · INTEGER · read-write · mandatory Setting this OID to restartCurrentAgent (1) will restart the same SNMP agent code currently saved in flash memory. Setting this OID to loadAndExecuteNewAgent (3) will enable adapter to load a new agent code into the flash memory and start to execute this new agent code. Bootp/tftp is the default protocol. loadAndExecuteNewAgent is only supported by APC Network Management Cards. Setting this OID to restartWithoutAgent (4) will restart the system and not start the agent. The subsequent time the system restarts the agent will also automatically restart. Setting this OID to resetNetworkAndRestart (5) will set the Boot Mode, IP Address, Subnet Mask, and Default Gateway to defaults, expire any existing DHCP lease and then restart the system. Setting this OID to resetNetworkLeaveModeAndRestart (6) will leave the Boot Mode at the current setting, set the IP Address, Subnet Mask, and Default Gateway to defaults, expire any existing DHCP lease and then restart the system.
| |||||||||||||||||||||
| Nmtrapargs | 1.3.6.1.4.1.318.2.3 | ||||||||||||||||||||
| SmtrapargsInteger | 1.3.6.1.4.1.318.2.3.1 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory This OID allows APC traps to be sent with an integer argument that my not be defined in the APC MIB. A get of this OID will return 0. | |||||||||||||||||||||
| SmtrapargsIpAddress | 1.3.6.1.4.1.318.2.3.2 | IpAddress | RO | mandatory | |||||||||||||||||
scalar · IpAddress · read-only · mandatory This OID allows APC traps to be sent with an IP address argument that my not be defined in the APC MIB. A get of this OID will return 0.0.0.0. | |||||||||||||||||||||
| SmtrapargsString | 1.3.6.1.4.1.318.2.3.3 | SnmpAdminString | RO | mandatory | |||||||||||||||||
scalar · SnmpAdminString · read-only · mandatory This OID allows APC traps to be sent with an octet string argument that my not be defined in the APC MIB. A get of this OID will return a NULL string. | |||||||||||||||||||||
| SmtrapargsGauge | 1.3.6.1.4.1.318.2.3.4 | Gauge | RO | mandatory | |||||||||||||||||
scalar · Gauge · read-only · mandatory This OID allows APC traps to be sent with a Gauge argument that my not be defined in the APC MIB. A get of this OID will return 0. | |||||||||||||||||||||
| SmtrapargsTimeTicks | 1.3.6.1.4.1.318.2.3.5 | TimeTicks | RO | mandatory | |||||||||||||||||
scalar · TimeTicks · read-only · mandatory This OID allows APC traps to be sent with a TimeTicks argument that my not be defined in the APC MIB. A get of this OID will return 0. | |||||||||||||||||||||
| SmtrapargsInteger02 | 1.3.6.1.4.1.318.2.3.6 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory This OID allows APC traps to be sent with an integer argument that my not be defined in the APC MIB. A get of this OID will return 0. | |||||||||||||||||||||
| SmtrapargsInteger03 | 1.3.6.1.4.1.318.2.3.7 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory This OID allows APC traps to be sent with an integer argument that my not be defined in the APC MIB. A get of this OID will return 0. | |||||||||||||||||||||
| SmtrapargsIpAddress02 | 1.3.6.1.4.1.318.2.3.8 | IpAddress | RO | mandatory | |||||||||||||||||
scalar · IpAddress · read-only · mandatory This OID allows APC traps to be sent with an IP address argument that my not be defined in the APC MIB. A get of this OID will return 0.0.0.0. | |||||||||||||||||||||
| SmtrapargsIpAddress03 | 1.3.6.1.4.1.318.2.3.9 | IpAddress | RO | mandatory | |||||||||||||||||
scalar · IpAddress · read-only · mandatory This OID allows APC traps to be sent with an IP address argument that my not be defined in the APC MIB. A get of this OID will return 0.0.0.0. | |||||||||||||||||||||
| SmtrapargsString02 | 1.3.6.1.4.1.318.2.3.10 | SnmpAdminString | RO | mandatory | |||||||||||||||||
scalar · SnmpAdminString · read-only · mandatory This OID allows APC traps to be sent with an octet string argument that my not be defined in the APC MIB. A get of this OID will return a NULL string. | |||||||||||||||||||||
| SmtrapargsString03 | 1.3.6.1.4.1.318.2.3.11 | SnmpAdminString | RO | mandatory | |||||||||||||||||
scalar · SnmpAdminString · read-only · mandatory This OID allows APC traps to be sent with an octet string argument that my not be defined in the APC MIB. A get of this OID will return a NULL string. | |||||||||||||||||||||
| SmtrapargsGauge02 | 1.3.6.1.4.1.318.2.3.12 | Gauge | RO | mandatory | |||||||||||||||||
scalar · Gauge · read-only · mandatory This OID allows APC traps to be sent with a Gauge argument that my not be defined in the APC MIB. A get of this OID will return 0. | |||||||||||||||||||||
| SmtrapargsGauge03 | 1.3.6.1.4.1.318.2.3.13 | Gauge | RO | mandatory | |||||||||||||||||
scalar · Gauge · read-only · mandatory This OID allows APC traps to be sent with a Gauge argument that my not be defined in the APC MIB. A get of this OID will return 0. | |||||||||||||||||||||
| SmtrapargsTimeTicks02 | 1.3.6.1.4.1.318.2.3.14 | TimeTicks | RO | mandatory | |||||||||||||||||
scalar · TimeTicks · read-only · mandatory This OID allows APC traps to be sent with a TimeTicks argument that my not be defined in the APC MIB. A get of this OID will return 0. | |||||||||||||||||||||
| SmtrapargsTimeTicks03 | 1.3.6.1.4.1.318.2.3.15 | TimeTicks | RO | mandatory | |||||||||||||||||
scalar · TimeTicks · read-only · mandatory This OID allows APC traps to be sent with a TimeTicks argument that my not be defined in the APC MIB. A get of this OID will return 0. | |||||||||||||||||||||
| SmtrapargsString04 | 1.3.6.1.4.1.318.2.3.16 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory This OID allows APC traps to be sent with an octet string argument that my not be defined in the APC MIB. A get of this OID will return a NULL string. | |||||||||||||||||||||
| SmtrapargsString05 | 1.3.6.1.4.1.318.2.3.17 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory This OID allows APC traps to be sent with an octet string argument that my not be defined in the APC MIB. A get of this OID will return a NULL string. | |||||||||||||||||||||
| SmtrapargsInteger04 | 1.3.6.1.4.1.318.2.3.18 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory This OID allows APC traps to be sent with an integer argument that my not be defined in the APC MIB. A get of this OID will return 0. | |||||||||||||||||||||
| SmtrapargsInteger05 | 1.3.6.1.4.1.318.2.3.19 | INTEGER | RO | mandatory | |||||||||||||||||
scalar · INTEGER · read-only · mandatory This OID allows APC traps to be sent with an integer argument that my not be defined in the APC MIB. A get of this OID will return 0. | |||||||||||||||||||||
| SmtrapargsString06 | 1.3.6.1.4.1.318.2.3.20 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory This OID allows APC traps to be sent with an octet string argument that my not be defined in the APC MIB. A get of this OID will return a NULL string. | |||||||||||||||||||||
| SmtrapargsString07 | 1.3.6.1.4.1.318.2.3.21 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory This OID allows APC traps to be sent with an octet string argument that my not be defined in the APC MIB. A get of this OID will return a NULL string. | |||||||||||||||||||||
| SmtrapargsString08 | 1.3.6.1.4.1.318.2.3.22 | DisplayString | RO | mandatory | |||||||||||||||||
scalar · DisplayString · read-only · mandatory This OID allows APC traps to be sent with an octet string argument that my not be defined in the APC MIB. A get of this OID will return a NULL string. | |||||||||||||||||||||
| SmtrapargsOctetString | 1.3.6.1.4.1.318.2.3.23 | SnmpAdminString | RO | mandatory | |||||||||||||||||
scalar · SnmpAdminString · read-only · mandatory This OID allows APC traps to be sent with an octet string argument that my not be defined in the APC MIB. A get of this OID will return a NULL string. | |||||||||||||||||||||
| SmtrapargsOctetString02 | 1.3.6.1.4.1.318.2.3.24 | SnmpAdminString | RO | mandatory | |||||||||||||||||
scalar · SnmpAdminString · read-only · mandatory This OID allows APC traps to be sent with an octet string argument that my not be defined in the APC MIB. A get of this OID will return a NULL string. | |||||||||||||||||||||
| SmtrapargsOctetString03 | 1.3.6.1.4.1.318.2.3.25 | SnmpAdminString | RO | mandatory | |||||||||||||||||
scalar · SnmpAdminString · read-only · mandatory This OID allows APC traps to be sent with an octet string argument that my not be defined in the APC MIB. A get of this OID will return a NULL string. | |||||||||||||||||||||
| SmtrapargsOctetString04 | 1.3.6.1.4.1.318.2.3.26 | SnmpAdminString | RO | mandatory | |||||||||||||||||
scalar · SnmpAdminString · read-only · mandatory This OID allows APC traps to be sent with an octet string argument that my not be defined in the APC MIB. A get of this OID will return a NULL string. | |||||||||||||||||||||
| SmtrapargsOctetString05 | 1.3.6.1.4.1.318.2.3.27 | SnmpAdminString | RO | mandatory | |||||||||||||||||
scalar · SnmpAdminString · read-only · mandatory This OID allows APC traps to be sent with an octet string argument that my not be defined in the APC MIB. A get of this OID will return a NULL string. | |||||||||||||||||||||
| SmtrapargsOctetString06 | 1.3.6.1.4.1.318.2.3.28 | SnmpAdminString | RO | mandatory | |||||||||||||||||
scalar · SnmpAdminString · read-only · mandatory This OID allows APC traps to be sent with an octet string argument that my not be defined in the APC MIB. A get of this OID will return a NULL string. | |||||||||||||||||||||
| SmtrapargsOctetString07 | 1.3.6.1.4.1.318.2.3.29 | SnmpAdminString | RO | mandatory | |||||||||||||||||
scalar · SnmpAdminString · read-only · mandatory This OID allows APC traps to be sent with an octet string argument that my not be defined in the APC MIB. A get of this OID will return a NULL string. | |||||||||||||||||||||
| SmtrapargsOctetString08 | 1.3.6.1.4.1.318.2.3.30 | SnmpAdminString | RO | mandatory | |||||||||||||||||
scalar · SnmpAdminString · read-only · mandatory This OID allows APC traps to be sent with an octet string argument that my not be defined in the APC MIB. A get of this OID will return a NULL string. | |||||||||||||||||||||
| Nmfiletransfer | 1.3.6.1.4.1.318.2.4 | ||||||||||||||||||||
| NmfiletransferStatus | 1.3.6.1.4.1.318.2.4.1 | ||||||||||||||||||||
| SmfiletransferStatusLastTransferResult | 1.3.6.1.4.1.318.2.4.1.1 | INTEGER | RO | deprecated | |||||||||||||||||
scalar · INTEGER · read-only · deprecated This OID has been deprecated. Once mfiletransferControlInitiateFileTransfer is set to a value other than doNotInitiateFileTransfer a file transfer of mfiletransferConfigSettingsFilename will be attempted from either a TFTP or FTP server. This OID shows the last attempted file transfer result. lastFileTransferResultSuccessful (1) means the file transfer was successful. lastFileTransferResultNotAvailable (2) means that there have been no previous file transfers. lastFileTransferResultFailureUnknown (3) means that the last file transfer failed for an unknown reason. lastFileTransferResultFailureServerInaccessible (4) means that the TFTP or FTP server could not be found on the network. lastFileTransferResultFailureServerAccessDenied (5) means that the TFTP or FTP server denied access. lastFileTransferResultFailureFileNotFound (6) means that the file could not be located. lastFileTransferResultFailureFileTypeUnknown (7) means the file was examined, but the contents were unknown. lastFileTransferResultFailureFileCorrupt (8) means the transferred file was corrupt.
| |||||||||||||||||||||
| NmfiletransferConfig | 1.3.6.1.4.1.318.2.4.2 | ||||||||||||||||||||
| NmfiletransferConfigSettings | 1.3.6.1.4.1.318.2.4.2.1 | ||||||||||||||||||||
| SmfiletransferConfigSettingsFilename | 1.3.6.1.4.1.318.2.4.2.1.1 | DisplayString | RW | deprecated | |||||||||||||||||
scalar · DisplayString · read-write · deprecated This OID has been deprecated. The path and name of the file to transfer using the mfiletransferControlInitiateFileTransfer OID. If the file to transfer exists in the default server directory then the path may be omitted. | |||||||||||||||||||||
| NmfiletransferConfigTFTP | 1.3.6.1.4.1.318.2.4.2.2 | ||||||||||||||||||||
| SmfiletransferConfigTFTPServerAddress | 1.3.6.1.4.1.318.2.4.2.2.1 | DisplayString | RW | deprecated | |||||||||||||||||
scalar · DisplayString · read-write · deprecated This OID has been deprecated. The IP Address in dotted decimal notation of the TFTP server involved in the file transfer. | |||||||||||||||||||||
| NmfiletransferConfigFTP | 1.3.6.1.4.1.318.2.4.2.3 | ||||||||||||||||||||
| SmfiletransferConfigFTPServerAddress | 1.3.6.1.4.1.318.2.4.2.3.1 | DisplayString | RW | deprecated | |||||||||||||||||
scalar · DisplayString · read-write · deprecated This OID has been deprecated. The IP Address in dotted decimal notation of the FTP server involved in the file transfer. | |||||||||||||||||||||
| SmfiletransferConfigFTPServerUser | 1.3.6.1.4.1.318.2.4.2.3.2 | DisplayString | RW | deprecated | |||||||||||||||||
scalar · DisplayString · read-write · deprecated This OID has been deprecated. The user identification for logging into the FTP server specified with mfiletransferConfigFTPServerAddress. | |||||||||||||||||||||
| SmfiletransferConfigFTPServerPassword | 1.3.6.1.4.1.318.2.4.2.3.3 | DisplayString | RW | deprecated | |||||||||||||||||
scalar · DisplayString · read-write · deprecated This OID has been deprecated. The password for logging into the FTP server specified with mfiletransferConfigFTPServerAddress. | |||||||||||||||||||||
| NmfiletransferControl | 1.3.6.1.4.1.318.2.4.3 | ||||||||||||||||||||
| SmfiletransferControlInitiateFileTransfer | 1.3.6.1.4.1.318.2.4.3.1 | INTEGER | RW | deprecated | |||||||||||||||||
scalar · INTEGER · read-write · deprecated This OID has been deprecated. Setting this OID to doNotInitiateFileTransfer (1) will do nothing. Setting this OID to initiateFileTransferDownloadViaTFTP (2) will attempt to transfer the file named in mfiletransferConfigSettingsFilename from the TFTP Server identified in mfiletransferConfigTFTPAddress. Setting this OID to initiateFileTransferDownloadViaFTP (3) will attempt to transfer the file named in mfiletransferConfigSettingsFilename from the FTP Server identified in mfiletransferConfigFTPAddress using mfiletransferConfigFTPUser and mfiletransferConfigFTPPassword for the FTP Server login process.
| |||||||||||||||||||||
Traps / Notifications
- abnormalCondition
1.3.6.1.4.1.318.0.77 - abnormalConditionCleared
1.3.6.1.4.1.318.0.78 - accessViolationConsole
1.3.6.1.4.1.318.0.46 - accessViolationHTTP
1.3.6.1.4.1.318.0.47 - airCriticalCondition
1.3.6.1.4.1.318.0.306 - airCriticalConditionCleared
1.3.6.1.4.1.318.0.307 - airInformationalCondition
1.3.6.1.4.1.318.0.310 - airInformationalConditionCleared
1.3.6.1.4.1.318.0.311 - airWarningCondition
1.3.6.1.4.1.318.0.308 - airWarningConditionCleared
1.3.6.1.4.1.318.0.309 - apcAdConverterFault
1.3.6.1.4.1.318.0.614 - apcAdConverterFaultCleared
1.3.6.1.4.1.318.0.615 - apcAnalogInputHighThresholdViolation
1.3.6.1.4.1.318.0.561 - apcAnalogInputHighThresholdViolationCleared
1.3.6.1.4.1.318.0.562 - apcAnalogInputLowThresholdViolation
1.3.6.1.4.1.318.0.563 - apcAnalogInputLowThresholdViolationCleared
1.3.6.1.4.1.318.0.564 - apcAnalogInputMaxThresholdViolation
1.3.6.1.4.1.318.0.559 - apcAnalogInputMaxThresholdViolationCleared
1.3.6.1.4.1.318.0.560 - apcAnalogInputMinThresholdViolation
1.3.6.1.4.1.318.0.565 - apcAnalogInputMinThresholdViolationCleared
1.3.6.1.4.1.318.0.566 - apcBeaconConnected
1.3.6.1.4.1.318.0.543 - apcBeaconDisconnected
1.3.6.1.4.1.318.0.544 - apcBeaconOff
1.3.6.1.4.1.318.0.546 - apcBeaconOn
1.3.6.1.4.1.318.0.545 - apcCriticalDiscreteInputContactStateAbnormal
1.3.6.1.4.1.318.0.553 - apcCriticalDiscreteInputContactStateNormal
1.3.6.1.4.1.318.0.554 - apcDcBusOverVoltage
1.3.6.1.4.1.318.0.610 - apcDcBusOverVoltageCleared
1.3.6.1.4.1.318.0.611 - apcDeviceClearLostComms
1.3.6.1.4.1.318.0.567 - apcDeviceClearUserConfigs
1.3.6.1.4.1.318.0.592 - apcDeviceConfigChange
1.3.6.1.4.1.318.0.516 - apcDeviceConnected
1.3.6.1.4.1.318.0.568 - apcDeviceDisconnected
1.3.6.1.4.1.318.0.569 - apcDoorClosed
1.3.6.1.4.1.318.0.578 - apcDoorClosedImproperly
1.3.6.1.4.1.318.0.692 - apcDoorClosedImproperlyCleared
1.3.6.1.4.1.318.0.693 - apcDoorEstablishedComms
1.3.6.1.4.1.318.0.589 - apcDoorLocked
1.3.6.1.4.1.318.0.574 - apcDoorLostComms
1.3.6.1.4.1.318.0.588 - apcDoorOpened
1.3.6.1.4.1.318.0.577 - apcDoorSenseConnected
1.3.6.1.4.1.318.0.587 - apcDoorSenseDisconnected
1.3.6.1.4.1.318.0.586 - apcDoorUnlocked
1.3.6.1.4.1.318.0.573 - apcEnvHighHumidityThresholdViolation
1.3.6.1.4.1.318.0.537 - apcEnvHighHumidityThresholdViolationCleared
1.3.6.1.4.1.318.0.538 - apcEnvHighTempThresholdViolation
1.3.6.1.4.1.318.0.521 - apcEnvHighTempThresholdViolationCleared
1.3.6.1.4.1.318.0.522 - apcEnvLTDecTempRateViolation
1.3.6.1.4.1.318.0.533 - apcEnvLTDecTempRateViolationCleared
1.3.6.1.4.1.318.0.534 - apcEnvLTIncTempRateViolation
1.3.6.1.4.1.318.0.531 - apcEnvLTIncTempRateViolationCleared
1.3.6.1.4.1.318.0.532 - apcEnvLowHumidityThresholdViolation
1.3.6.1.4.1.318.0.539 - apcEnvLowHumidityThresholdViolationCleared
1.3.6.1.4.1.318.0.540 - apcEnvLowTempThresholdViolation
1.3.6.1.4.1.318.0.523 - apcEnvLowTempThresholdViolationCleared
1.3.6.1.4.1.318.0.524 - apcEnvMaxHumidityThresholdViolation
1.3.6.1.4.1.318.0.535 - apcEnvMaxHumidityThresholdViolationCleared
1.3.6.1.4.1.318.0.536 - apcEnvMaxTempThresholdViolation
1.3.6.1.4.1.318.0.519 - apcEnvMaxTempThresholdViolationCleared
1.3.6.1.4.1.318.0.520 - apcEnvMinHumidityThresholdViolation
1.3.6.1.4.1.318.0.541 - apcEnvMinHumidityThresholdViolationCleared
1.3.6.1.4.1.318.0.542 - apcEnvMinTempThresholdViolation
1.3.6.1.4.1.318.0.525 - apcEnvMinTempThresholdViolationCleared
1.3.6.1.4.1.318.0.526 - apcEnvSTDecTempRateViolation
1.3.6.1.4.1.318.0.529 - apcEnvSTDecTempRateViolationCleared
1.3.6.1.4.1.318.0.530 - apcEnvSTIncTempRateViolation
1.3.6.1.4.1.318.0.527 - apcEnvSTIncTempRateViolationCleared
1.3.6.1.4.1.318.0.528 - apcEnvSensorConnected
1.3.6.1.4.1.318.0.517 - apcEnvSensorDisconnected
1.3.6.1.4.1.318.0.518 - apcForcedEntry
1.3.6.1.4.1.318.0.582 - apcForcedEntryCleared
1.3.6.1.4.1.318.0.583 - apcHandleClosed
1.3.6.1.4.1.318.0.576 - apcHandleOpened
1.3.6.1.4.1.318.0.575 - apcHardwareStateAbnormal
1.3.6.1.4.1.318.0.551 - apcHardwareStateNormal
1.3.6.1.4.1.318.0.552 - apcInformationalDiscreteInputContactStateAbnormal
1.3.6.1.4.1.318.0.557 - apcInformationalDiscreteInputContactStateNormal
1.3.6.1.4.1.318.0.558 - apcInternalCommunicationFault
1.3.6.1.4.1.318.0.730 - apcInternalCommunicationFaultCleared
1.3.6.1.4.1.318.0.731 - apcKeyOverrideLocked
1.3.6.1.4.1.318.0.581 - apcKeyOverrideUnlocked
1.3.6.1.4.1.318.0.580 - apcLogicPowerSupplyFault
1.3.6.1.4.1.318.0.616 - apcLogicPowerSupplyFaultCleared
1.3.6.1.4.1.318.0.617 - apcOutletStateAbnormal
1.3.6.1.4.1.318.0.547 - apcOutletStateNormal
1.3.6.1.4.1.318.0.548 - apcOutputRelayFault
1.3.6.1.4.1.318.0.606 - apcOutputRelayFaultCleared
1.3.6.1.4.1.318.0.607 - apcOutputRelayStateAbnormal
1.3.6.1.4.1.318.0.549 - apcOutputRelayStateNormal
1.3.6.1.4.1.318.0.550 - apcOutputShortCircuit
1.3.6.1.4.1.318.0.604 - apcOutputShortCircuitCleared
1.3.6.1.4.1.318.0.605 - apcRegisteredUserAccessChange
1.3.6.1.4.1.318.0.590 - apcRegisteredUserAccessDenied
1.3.6.1.4.1.318.0.571 - apcRegisteredUserConfigChange
1.3.6.1.4.1.318.0.572 - apcRelockTimeout
1.3.6.1.4.1.318.0.584 - apcRelockTimeoutCleared
1.3.6.1.4.1.318.0.585 - apcTestTrap
1.3.6.1.4.1.318.0.636 - apcTransformerDCImbalanceFault
1.3.6.1.4.1.318.0.618 - apcTransformerDCImbalanceFaultCleared
1.3.6.1.4.1.318.0.619 - apcUnregisteredUserAccessDenied
1.3.6.1.4.1.318.0.570 - apcUnregisteredUserStatusChange
1.3.6.1.4.1.318.0.591 - apcUserScheduleViolation
1.3.6.1.4.1.318.0.694 - apcUserScheduleViolationCleared
1.3.6.1.4.1.318.0.695 - apcWarningDiscreteInputContactStateAbnormal
1.3.6.1.4.1.318.0.555 - apcWarningDiscreteInputContactStateNormal
1.3.6.1.4.1.318.0.556 - aruAlinkCommunicationEstablished
1.3.6.1.4.1.318.0.284 - aruAlinkCommunicationLost
1.3.6.1.4.1.318.0.285 - aruDeviceConfigChange
1.3.6.1.4.1.318.0.228 - aruExhaustTemperatureAlarm
1.3.6.1.4.1.318.0.292 - aruExhaustTemperatureAlarmCleared
1.3.6.1.4.1.318.0.293 - aruFanFail
1.3.6.1.4.1.318.0.286 - aruFanFailCleared
1.3.6.1.4.1.318.0.287 - aruFanPoorPerformanceAlarm
1.3.6.1.4.1.318.0.512 - aruFanPoorPerformanceAlarmCleared
1.3.6.1.4.1.318.0.513 - aruFanRuntimeAlarm
1.3.6.1.4.1.318.0.510 - aruFanRuntimeAlarmCleared
1.3.6.1.4.1.318.0.511 - aruHighTemperatureAlarm
1.3.6.1.4.1.318.0.290 - aruHighTemperatureAlarmCleared
1.3.6.1.4.1.318.0.291 - aruRedundantPowerLostAlarm
1.3.6.1.4.1.318.0.514 - aruRedundantPowerLostAlarmCleared
1.3.6.1.4.1.318.0.515 - aruSmokeAlarm
1.3.6.1.4.1.318.0.288 - aruSmokeAlarmCleared
1.3.6.1.4.1.318.0.289 - atsCommunicationEstablished
1.3.6.1.4.1.318.0.130 - atsCommunicationLost
1.3.6.1.4.1.318.0.131 - atsConfigChange
1.3.6.1.4.1.318.0.129 - atsControllerRestart
1.3.6.1.4.1.318.0.702 - atsCriticalCondition
1.3.6.1.4.1.318.0.825 - atsCriticalConditionCleared
1.3.6.1.4.1.318.0.826 - atsHardwareStatusFail
1.3.6.1.4.1.318.0.700 - atsHardwareStatusOk
1.3.6.1.4.1.318.0.701 - atsInformationalCondition
1.3.6.1.4.1.318.0.829 - atsInformationalConditionCleared
1.3.6.1.4.1.318.0.830 - atsLostRedundancy
1.3.6.1.4.1.318.0.127 - atsLowLoad
1.3.6.1.4.1.318.0.638 - atsLowLoadCleared
1.3.6.1.4.1.318.0.639 - atsNearOverload
1.3.6.1.4.1.318.0.640 - atsNearOverloadCleared
1.3.6.1.4.1.318.0.641 - atsOverCurrent
1.3.6.1.4.1.318.0.132 - atsOverCurrentCleared
1.3.6.1.4.1.318.0.133 - atsOverload
1.3.6.1.4.1.318.0.642 - atsOverloadCleared
1.3.6.1.4.1.318.0.643 - atsPowerSupplyFailure
1.3.6.1.4.1.318.0.134 - atsPowerSupplyFailureCleared
1.3.6.1.4.1.318.0.135 - atsRMSOverFrequency
1.3.6.1.4.1.318.0.648 - atsRMSOverFrequencyCleared
1.3.6.1.4.1.318.0.649 - atsRMSOverVoltage
1.3.6.1.4.1.318.0.644 - atsRMSOverVoltageCleared
1.3.6.1.4.1.318.0.645 - atsRMSUnderFrequency
1.3.6.1.4.1.318.0.650 - atsRMSUnderFrequencyCleared
1.3.6.1.4.1.318.0.651 - atsRMSUnderVoltage
1.3.6.1.4.1.318.0.646 - atsRMSUnderVoltageCleared
1.3.6.1.4.1.318.0.647 - atsRedundancyRestored
1.3.6.1.4.1.318.0.128 - atsSourceStatusFail
1.3.6.1.4.1.318.0.698 - atsSourceStatusOk
1.3.6.1.4.1.318.0.699 - atsSourceSwitched
1.3.6.1.4.1.318.0.126 - atsWarningCondition
1.3.6.1.4.1.318.0.827 - atsWarningConditionCleared
1.3.6.1.4.1.318.0.828 - badVoltage
1.3.6.1.4.1.318.0.49 - badVoltageCleared
1.3.6.1.4.1.318.0.50 - baseFanFailure
1.3.6.1.4.1.318.0.25 - baseFanFailureCleared
1.3.6.1.4.1.318.0.637 - batteryDecrease
1.3.6.1.4.1.318.0.68 - batteryIncrease
1.3.6.1.4.1.318.0.67 - batteryOverTemperature
1.3.6.1.4.1.318.0.53 - batteryOverTemperatureCleared
1.3.6.1.4.1.318.0.54 - batteryPackCommEstablished
1.3.6.1.4.1.318.0.27 - batteryPackCommLost
1.3.6.1.4.1.318.0.26 - batteryVoltageCollapse
1.3.6.1.4.1.318.0.715 - batteryVoltageOK
1.3.6.1.4.1.318.0.716 - bmBatManBatteryAlarm
1.3.6.1.4.1.318.0.183 - bmBatManBatteryAlarmCleared
1.3.6.1.4.1.318.0.184 - bmBatManChargerAlarm
1.3.6.1.4.1.318.0.181 - bmBatManChargerAlarmCleared
1.3.6.1.4.1.318.0.182 - bmBatManCommEstab
1.3.6.1.4.1.318.0.177 - bmBatManCommLost
1.3.6.1.4.1.318.0.178 - bmBatManEnvironmentAlarm
1.3.6.1.4.1.318.0.185 - bmBatManEnvironmentAlarmCleared
1.3.6.1.4.1.318.0.186 - bmBatManKneeAlarm
1.3.6.1.4.1.318.0.179 - bmBatManKneeAlarmCleared
1.3.6.1.4.1.318.0.180 - bmBatManMaintenanceAlarm
1.3.6.1.4.1.318.0.187 - bmBatManMaintenanceAlarmCleared
1.3.6.1.4.1.318.0.188 - bmsCriticalCondition
1.3.6.1.4.1.318.0.375 - bmsCriticalConditionCleared
1.3.6.1.4.1.318.0.376 - bmsInformationalCondition
1.3.6.1.4.1.318.0.379 - bmsInformationalConditionCleared
1.3.6.1.4.1.318.0.380 - bmsWarningCondition
1.3.6.1.4.1.318.0.377 - bmsWarningConditionCleared
1.3.6.1.4.1.318.0.378 - bypassOK
1.3.6.1.4.1.318.0.706 - bypassPowerSupplyFailure
1.3.6.1.4.1.318.0.24 - bypassPowerSupplyFailureCleared
1.3.6.1.4.1.318.0.824 - bypassStaticSwitchError
1.3.6.1.4.1.318.0.719 - bypassStaticSwitchOK
1.3.6.1.4.1.318.0.720 - bypassStaticSwitchOverload
1.3.6.1.4.1.318.0.713 - bypassWarningError
1.3.6.1.4.1.318.0.705 - calibrationEnd
1.3.6.1.4.1.318.0.37 - calibrationStart
1.3.6.1.4.1.318.0.28 - ceInformationalCondition
1.3.6.1.4.1.318.0.351 - ceInformationalConditionCleared
1.3.6.1.4.1.318.0.352 - ceSevereCondition
1.3.6.1.4.1.318.0.347 - ceSevereConditionCleared
1.3.6.1.4.1.318.0.348 - ceWarningCondition
1.3.6.1.4.1.318.0.349 - ceWarningConditionCleared
1.3.6.1.4.1.318.0.350 - chargerFailure
1.3.6.1.4.1.318.0.51 - chargerFailureCleared
1.3.6.1.4.1.318.0.52 - codeAuthenticationDone
1.3.6.1.4.1.318.0.32 - communicationEstablished
1.3.6.1.4.1.318.0.8 - communicationLost
1.3.6.1.4.1.318.0.1 - communicationOK
1.3.6.1.4.1.318.0.708 - communicationWarningError
1.3.6.1.4.1.318.0.707 - configChangeOutlet
1.3.6.1.4.1.318.0.45 - configChangeSNMP
1.3.6.1.4.1.318.0.44 - contactFault
1.3.6.1.4.1.318.0.18 - contactFaultResolved
1.3.6.1.4.1.318.0.19 - dcBBCommunicationEstablished
1.3.6.1.4.1.318.0.161 - dcBBCommunicationLost
1.3.6.1.4.1.318.0.162 - dcBatteryBreakerAlarm
1.3.6.1.4.1.318.0.148 - dcBatteryBreakerAlarmCleared
1.3.6.1.4.1.318.0.149 - dcBatteryTestFail
1.3.6.1.4.1.318.0.156 - dcCommunicationEstablished
1.3.6.1.4.1.318.0.110 - dcCommunicationLost
1.3.6.1.4.1.318.0.111 - dcCurrentLimitAlarm
1.3.6.1.4.1.318.0.142 - dcCurrentLimitAlarmCleared
1.3.6.1.4.1.318.0.143 - dcFanFailAlarm
1.3.6.1.4.1.318.0.138 - dcFanFailAlarmCleared
1.3.6.1.4.1.318.0.139 - dcFuseCBAlarm
1.3.6.1.4.1.318.0.154 - dcFuseCBAlarmCleared
1.3.6.1.4.1.318.0.155 - dcHumidityAlarm
1.3.6.1.4.1.318.0.159 - dcHumidityAlarmCleared
1.3.6.1.4.1.318.0.160 - dcInputRelayOff
1.3.6.1.4.1.318.0.120 - dcInputRelayOn
1.3.6.1.4.1.318.0.119 - dcLVDImminentAlarm
1.3.6.1.4.1.318.0.152 - dcLVDImminentAlarmCleared
1.3.6.1.4.1.318.0.153 - dcMainsFailAlarm
1.3.6.1.4.1.318.0.136 - dcMainsFailAlarmCleared
1.3.6.1.4.1.318.0.137 - dcMajorAlarm
1.3.6.1.4.1.318.0.113 - dcMajorAlarmCleared
1.3.6.1.4.1.318.0.114 - dcMinorAlarm
1.3.6.1.4.1.318.0.115 - dcMinorAlarmCleared
1.3.6.1.4.1.318.0.116 - dcMultRectFailAlarm
1.3.6.1.4.1.318.0.146 - dcMultRectFailAlarmCleared
1.3.6.1.4.1.318.0.147 - dcOutputRelayOff
1.3.6.1.4.1.318.0.118 - dcOutputRelayOn
1.3.6.1.4.1.318.0.117 - dcPINChanged
1.3.6.1.4.1.318.0.112 - dcRectifierFailAlarm
1.3.6.1.4.1.318.0.144 - dcRectifierFailAlarmCleared
1.3.6.1.4.1.318.0.145 - dcRectifierOVPAlarm
1.3.6.1.4.1.318.0.150 - dcRectifierOVPAlarmCleared
1.3.6.1.4.1.318.0.151 - dcRectifierOvertempAlarm
1.3.6.1.4.1.318.0.140 - dcRectifierOvertempAlarmCleared
1.3.6.1.4.1.318.0.141 - dcTemperatureAlarm
1.3.6.1.4.1.318.0.157 - dcTemperatureAlarmCleared
1.3.6.1.4.1.318.0.158 - deviceStatusChange
1.3.6.1.4.1.318.0.79 - dischargeCleared
1.3.6.1.4.1.318.0.38 - ePDUCriticalCondition
1.3.6.1.4.1.318.0.812 - ePDUCriticalConditionCleared
1.3.6.1.4.1.318.0.813 - ePDUWarningCondition
1.3.6.1.4.1.318.0.814 - ePDUWarningConditionCleared
1.3.6.1.4.1.318.0.815 - emsAlinkPowerOverload
1.3.6.1.4.1.318.0.296 - emsAlinkPowerOverloadCleared
1.3.6.1.4.1.318.0.297 - emsBeaconConnected
1.3.6.1.4.1.318.0.238 - emsBeaconDisconnected
1.3.6.1.4.1.318.0.239 - emsBeaconOff
1.3.6.1.4.1.318.0.241 - emsBeaconOn
1.3.6.1.4.1.318.0.240 - emsCommunicationEstablished
1.3.6.1.4.1.318.0.230 - emsCommunicationLost
1.3.6.1.4.1.318.0.231 - emsDeviceConfigChange
1.3.6.1.4.1.318.0.252 - emsHardwareStateAbnormal
1.3.6.1.4.1.318.0.345 - emsHardwareStateNormal
1.3.6.1.4.1.318.0.346 - emsInputContactStateAbnormal
1.3.6.1.4.1.318.0.248 - emsInputContactStateNormal
1.3.6.1.4.1.318.0.249 - emsMajorAlarm
1.3.6.1.4.1.318.0.242 - emsMajorAlarmCleared
1.3.6.1.4.1.318.0.243 - emsMinorAlarm
1.3.6.1.4.1.318.0.244 - emsMinorAlarmCleared
1.3.6.1.4.1.318.0.245 - emsOutletStateAbnormal
1.3.6.1.4.1.318.0.246 - emsOutletStateNormal
1.3.6.1.4.1.318.0.247 - emsOutputRelayStateAbnormal
1.3.6.1.4.1.318.0.250 - emsOutputRelayStateNormal
1.3.6.1.4.1.318.0.251 - emsProbeConnected
1.3.6.1.4.1.318.0.232 - emsProbeDisconnected
1.3.6.1.4.1.318.0.233 - emsSensorConnected
1.3.6.1.4.1.318.0.234 - emsSensorDisconnected
1.3.6.1.4.1.318.0.235 - emsSensorFault
1.3.6.1.4.1.318.0.236 - emsSensorFaultCleared
1.3.6.1.4.1.318.0.237 - envAlinkCommunicationEstablished
1.3.6.1.4.1.318.0.294 - envAlinkCommunicationLost
1.3.6.1.4.1.318.0.295 - envHighHumidityThresholdViolation
1.3.6.1.4.1.318.0.257 - envHighHumidityThresholdViolationCleared
1.3.6.1.4.1.318.0.258 - envHighTempThresholdViolation
1.3.6.1.4.1.318.0.253 - envHighTempThresholdViolationCleared
1.3.6.1.4.1.318.0.254 - envLTDecTempRateViolation
1.3.6.1.4.1.318.0.373 - envLTDecTempRateViolationCleared
1.3.6.1.4.1.318.0.374 - envLTIncTempRateViolation
1.3.6.1.4.1.318.0.371 - envLTIncTempRateViolationCleared
1.3.6.1.4.1.318.0.372 - envLowHumidityThresholdViolation
1.3.6.1.4.1.318.0.259 - envLowHumidityThresholdViolationCleared
1.3.6.1.4.1.318.0.260 - envLowTempThresholdViolation
1.3.6.1.4.1.318.0.255 - envLowTempThresholdViolationCleared
1.3.6.1.4.1.318.0.256 - envMaxHumidityThresholdViolation
1.3.6.1.4.1.318.0.363 - envMaxHumidityThresholdViolationCleared
1.3.6.1.4.1.318.0.364 - envMaxTempThresholdViolation
1.3.6.1.4.1.318.0.359 - envMaxTempThresholdViolationCleared
1.3.6.1.4.1.318.0.360 - envMinHumidityThresholdViolation
1.3.6.1.4.1.318.0.365 - envMinHumidityThresholdViolationCleared
1.3.6.1.4.1.318.0.366 - envMinTempThresholdViolation
1.3.6.1.4.1.318.0.361 - envMinTempThresholdViolationCleared
1.3.6.1.4.1.318.0.362 - envSTDecTempRateViolation
1.3.6.1.4.1.318.0.369 - envSTDecTempRateViolationCleared
1.3.6.1.4.1.318.0.370 - envSTIncTempRateViolation
1.3.6.1.4.1.318.0.367 - envSTIncTempRateViolationCleared
1.3.6.1.4.1.318.0.368 - epoActivated
1.3.6.1.4.1.318.0.723 - extBatteryFrameDecrease
1.3.6.1.4.1.318.0.76 - extBatteryFrameIncease
1.3.6.1.4.1.318.0.75 - externalSwitchGearClosed
1.3.6.1.4.1.318.0.123 - externalSwitchGearOpened
1.3.6.1.4.1.318.0.124 - forcedBypassSwitchActivated
1.3.6.1.4.1.318.0.721 - forcedBypassSwitchReleased
1.3.6.1.4.1.318.0.722 - generalDeviceEvent
1.3.6.1.4.1.318.0.125 - gracefulShutdown
1.3.6.1.4.1.318.0.39 - hardwareFailureBypass
1.3.6.1.4.1.318.0.20 - humidityThresholdViolation1
1.3.6.1.4.1.318.0.57 - humidityThresholdViolation2
1.3.6.1.4.1.318.0.61 - humidityThresholdViolationCleared1
1.3.6.1.4.1.318.0.58 - humidityThresholdViolationCleared2
1.3.6.1.4.1.318.0.62 - iemContactFault
1.3.6.1.4.1.318.0.173 - iemContactFaultCleared
1.3.6.1.4.1.318.0.174 - iemHighHumidThresholdViolation
1.3.6.1.4.1.318.0.167 - iemHighHumidThresholdViolationCleared
1.3.6.1.4.1.318.0.168 - iemHighTempThresholdViolation
1.3.6.1.4.1.318.0.163 - iemHighTempThresholdViolationCleared
1.3.6.1.4.1.318.0.164 - iemLowHumidThresholdViolation
1.3.6.1.4.1.318.0.169 - iemLowHumidThresholdViolationCleared
1.3.6.1.4.1.318.0.170 - iemLowTempThresholdViolation
1.3.6.1.4.1.318.0.165 - iemLowTempThresholdViolationCleared
1.3.6.1.4.1.318.0.166 - iemProbeConnected
1.3.6.1.4.1.318.0.172 - iemProbeDisconnected
1.3.6.1.4.1.318.0.171 - iemRelayFault
1.3.6.1.4.1.318.0.175 - iemRelayFaultCleared
1.3.6.1.4.1.318.0.176 - inputOK
1.3.6.1.4.1.318.0.704 - inputWarningError
1.3.6.1.4.1.318.0.703 - intelligenceModuleInserted
1.3.6.1.4.1.318.0.71 - intelligenceModuleRemoved
1.3.6.1.4.1.318.0.72 - isxModularBreakerOpenAlarm
1.3.6.1.4.1.318.0.656 - isxModularBreakerOpenAlarmCleared
1.3.6.1.4.1.318.0.657 - isxModularCoolingFanAlarm
1.3.6.1.4.1.318.0.756 - isxModularCoolingFanAlarmCleared
1.3.6.1.4.1.318.0.757 - isxModularDistributionCommEstablished
1.3.6.1.4.1.318.0.653 - isxModularDistributionCommLost
1.3.6.1.4.1.318.0.652 - isxModularDistributionModuleInserted
1.3.6.1.4.1.318.0.654 - isxModularDistributionModuleRemoved
1.3.6.1.4.1.318.0.655 - isxModularHighCurrentThresholdViolation
1.3.6.1.4.1.318.0.662 - isxModularHighCurrentThresholdViolationCleared
1.3.6.1.4.1.318.0.663 - isxModularLowCurrentThresholdViolation
1.3.6.1.4.1.318.0.660 - isxModularLowCurrentThresholdViolationCleared
1.3.6.1.4.1.318.0.661 - isxModularMaxCurrentThresholdViolation
1.3.6.1.4.1.318.0.664 - isxModularMaxCurrentThresholdViolationCleared
1.3.6.1.4.1.318.0.665 - isxModularMinCurrentThresholdViolation
1.3.6.1.4.1.318.0.658 - isxModularMinCurrentThresholdViolationCleared
1.3.6.1.4.1.318.0.659 - isxModularOutputFrequencyThresholdViolation
1.3.6.1.4.1.318.0.696 - isxModularOutputFrequencyViolationCleared
1.3.6.1.4.1.318.0.697 - isxModularOutputVoltageHighThresholdViolation
1.3.6.1.4.1.318.0.688 - isxModularOutputVoltageHighThresholdViolationCleared
1.3.6.1.4.1.318.0.689 - isxModularOutputVoltageLowThresholdViolation
1.3.6.1.4.1.318.0.686 - isxModularOutputVoltageLowThresholdViolationCleared
1.3.6.1.4.1.318.0.687 - isxModularOutputVoltageMaxThresholdViolation
1.3.6.1.4.1.318.0.690 - isxModularOutputVoltageMaxThresholdViolationCleared
1.3.6.1.4.1.318.0.691 - isxModularOutputVoltageMinThresholdViolation
1.3.6.1.4.1.318.0.684 - isxModularOutputVoltageMinThresholdViolationCleared
1.3.6.1.4.1.318.0.685 - isxModularSubfeedBreakerOpenAlarm
1.3.6.1.4.1.318.0.666 - isxModularSubfeedBreakerOpenAlarmCleared
1.3.6.1.4.1.318.0.667 - isxModularSubfeedHighCurrentThresholdViolation
1.3.6.1.4.1.318.0.672 - isxModularSubfeedHighCurrentThresholdViolationCleared
1.3.6.1.4.1.318.0.673 - isxModularSubfeedLowCurrentThresholdViolation
1.3.6.1.4.1.318.0.670 - isxModularSubfeedLowCurrentThresholdViolationCleared
1.3.6.1.4.1.318.0.671 - isxModularSubfeedMaxCurrentThresholdViolation
1.3.6.1.4.1.318.0.674 - isxModularSubfeedMaxCurrentThresholdViolationCleared
1.3.6.1.4.1.318.0.675 - isxModularSubfeedMinCurrentThresholdViolation
1.3.6.1.4.1.318.0.668 - isxModularSubfeedMinCurrentThresholdViolationCleared
1.3.6.1.4.1.318.0.669 - isxModularTotalOutputCurrentHighThresholdViolation
1.3.6.1.4.1.318.0.680 - isxModularTotalOutputCurrentHighThresholdViolationCleared
1.3.6.1.4.1.318.0.681 - isxModularTotalOutputCurrentLowThresholdViolation
1.3.6.1.4.1.318.0.678 - isxModularTotalOutputCurrentLowThresholdViolationCleared
1.3.6.1.4.1.318.0.679 - isxModularTotalOutputCurrentMaxThresholdViolation
1.3.6.1.4.1.318.0.682 - isxModularTotalOutputCurrentMaxThresholdViolationCleared
1.3.6.1.4.1.318.0.683 - isxModularTotalOutputCurrentMinThresholdViolation
1.3.6.1.4.1.318.0.676 - isxModularTotalOutputCurrentMinThresholdViolationCleared
1.3.6.1.4.1.318.0.677 - isxModularTransformerOverheating
1.3.6.1.4.1.318.0.728 - isxModularTransformerOverheatingCleared
1.3.6.1.4.1.318.0.729 - isxcCriticalAlarm
1.3.6.1.4.1.318.0.746 - isxcCriticalAlarmCleared
1.3.6.1.4.1.318.0.747 - isxcErrorAlarm
1.3.6.1.4.1.318.0.744 - isxcErrorAlarmCleared
1.3.6.1.4.1.318.0.745 - isxcFailureAlarm
1.3.6.1.4.1.318.0.748 - isxcFailureAlarmCleared
1.3.6.1.4.1.318.0.749 - isxcInformationalAlarm
1.3.6.1.4.1.318.0.740 - isxcInformationalAlarmCleared
1.3.6.1.4.1.318.0.741 - isxcWarningAlarm
1.3.6.1.4.1.318.0.742 - isxcWarningAlarmCleared
1.3.6.1.4.1.318.0.743 - logicPowerSuppliesDecreased
1.3.6.1.4.1.318.0.122 - logicPowerSuppliesIncreased
1.3.6.1.4.1.318.0.121 - lowBattery
1.3.6.1.4.1.318.0.7 - mspCommunicationEstablished
1.3.6.1.4.1.318.0.98 - mspCommunicationLost
1.3.6.1.4.1.318.0.99 - mspDeviceConfigChange
1.3.6.1.4.1.318.0.102 - mspOutletConfigChange
1.3.6.1.4.1.318.0.103 - mspOutletOff
1.3.6.1.4.1.318.0.101 - mspOutletOn
1.3.6.1.4.1.318.0.100 - msvmCommunicationEstablished
1.3.6.1.4.1.318.0.85 - msvmCommunicationLost
1.3.6.1.4.1.318.0.86 - msvmDeviceConfigChange
1.3.6.1.4.1.318.0.91 - msvmLowLoad
1.3.6.1.4.1.318.0.93 - msvmLowLoadCleared
1.3.6.1.4.1.318.0.94 - msvmNearOverload
1.3.6.1.4.1.318.0.95 - msvmNearOverloadCleared
1.3.6.1.4.1.318.0.96 - msvmOutletConfigChange
1.3.6.1.4.1.318.0.92 - msvmOutletOff
1.3.6.1.4.1.318.0.90 - msvmOutletOn
1.3.6.1.4.1.318.0.89 - msvmOverload
1.3.6.1.4.1.318.0.87 - msvmOverloadCleared
1.3.6.1.4.1.318.0.88 - msvmPowerSupplyStatusChange
1.3.6.1.4.1.318.0.97 - mupsCommunicationEstablished
1.3.6.1.4.1.318.0.65 - mupsCommunicationLost
1.3.6.1.4.1.318.0.66 - noBatteries
1.3.6.1.4.1.318.0.80 - noBatteriesCleared
1.3.6.1.4.1.318.0.81 - noOverloadOnBypassStaticSwitch
1.3.6.1.4.1.318.0.714 - noOverloadOnInstallation
1.3.6.1.4.1.318.0.718 - onbatterycommunicationLost
1.3.6.1.4.1.318.0.733 - outletOff
1.3.6.1.4.1.318.0.42 - outletOn
1.3.6.1.4.1.318.0.41 - outletReboot
1.3.6.1.4.1.318.0.43 - outputVoltageWaveformError
1.3.6.1.4.1.318.0.711 - outputVoltageWaveformOK
1.3.6.1.4.1.318.0.712 - overloadOnInstallation
1.3.6.1.4.1.318.0.717 - passwordChange
1.3.6.1.4.1.318.0.48 - pcbeComsLost
1.3.6.1.4.1.318.0.792 - pcbeComsLostResolved
1.3.6.1.4.1.318.0.793 - pcbeCriticalEventActive
1.3.6.1.4.1.318.0.790 - pcbeCriticalEventResolved
1.3.6.1.4.1.318.0.791 - pcbeTest
1.3.6.1.4.1.318.0.794 - pcbeUpdateAvailable
1.3.6.1.4.1.318.0.795 - pcnsCriticalEventActive
1.3.6.1.4.1.318.0.779 - pcnsCriticalEventResolved
1.3.6.1.4.1.318.0.780 - pcnsNMCComsLost
1.3.6.1.4.1.318.0.783 - pcnsNMCComsLostResolved
1.3.6.1.4.1.318.0.784 - pcnsNetworkComsLost
1.3.6.1.4.1.318.0.781 - pcnsNetworkComsLostResolved
1.3.6.1.4.1.318.0.782 - pcnsTest
1.3.6.1.4.1.318.0.785 - pcnsUpdateAvailable
1.3.6.1.4.1.318.0.786 - pduAtypicalBypassMode
1.3.6.1.4.1.318.0.212 - pduCircuitPanelFrequencyOutOfRange
1.3.6.1.4.1.318.0.205 - pduCircuitPanelFrequencyOutofRangeCleared
1.3.6.1.4.1.318.0.206 - pduCircuitPanelInputOvercurrent
1.3.6.1.4.1.318.0.203 - pduCircuitPanelInputOvercurrentCleared
1.3.6.1.4.1.318.0.204 - pduCircuitPanelInputOvervoltage
1.3.6.1.4.1.318.0.199 - pduCircuitPanelInputOvervoltageCleared
1.3.6.1.4.1.318.0.200 - pduCircuitPanelInputUndercurrent
1.3.6.1.4.1.318.0.201 - pduCircuitPanelInputUndercurrentCleared
1.3.6.1.4.1.318.0.202 - pduCircuitPanelInputUndervoltage
1.3.6.1.4.1.318.0.197 - pduCircuitPanelInputUndervoltageCleared
1.3.6.1.4.1.318.0.198 - pduCircuitPanelNeutralOvercurrent
1.3.6.1.4.1.318.0.207 - pduCircuitPanelNeutralOvercurrentCleared
1.3.6.1.4.1.318.0.208 - pduCommunicationEstablished
1.3.6.1.4.1.318.0.189 - pduCommunicationLost
1.3.6.1.4.1.318.0.190 - pduContactFault
1.3.6.1.4.1.318.0.220 - pduContactFaultCleared
1.3.6.1.4.1.318.0.221 - pduForcedBypassMode
1.3.6.1.4.1.318.0.215 - pduGroundOvercurrent
1.3.6.1.4.1.318.0.195 - pduGroundOvercurrentCleared
1.3.6.1.4.1.318.0.196 - pduInputTransformerOverTemperature
1.3.6.1.4.1.318.0.216 - pduInputTransformerOverTemperatureCleared
1.3.6.1.4.1.318.0.217 - pduMaintenanceBypassMode
1.3.6.1.4.1.318.0.211 - pduNoPanelFeedMode
1.3.6.1.4.1.318.0.213 - pduOnBatteryMode
1.3.6.1.4.1.318.0.210 - pduSystemOff
1.3.6.1.4.1.318.0.209 - pduUPSInputVoltageLost
1.3.6.1.4.1.318.0.218 - pduUPSInputVoltageRestored
1.3.6.1.4.1.318.0.219 - pduUpsOperationMode
1.3.6.1.4.1.318.0.214 - pduUtilityLineOvervoltage
1.3.6.1.4.1.318.0.193 - pduUtilityLineOvervoltageCleared
1.3.6.1.4.1.318.0.194 - pduUtilityLineUndervoltage
1.3.6.1.4.1.318.0.191 - pduUtilityLineUndervoltageCleared
1.3.6.1.4.1.318.0.192 - pmmCriticalCondition
1.3.6.1.4.1.318.0.796 - pmmCriticalConditionCleared
1.3.6.1.4.1.318.0.797 - pmmInformationalCondition
1.3.6.1.4.1.318.0.800 - pmmInformationalConditionCleared
1.3.6.1.4.1.318.0.801 - pmmWarningCondition
1.3.6.1.4.1.318.0.798 - pmmWarningConditionCleared
1.3.6.1.4.1.318.0.799 - powerModuleDecrease
1.3.6.1.4.1.318.0.70 - powerModuleIncrease
1.3.6.1.4.1.318.0.69 - powerModuleOK
1.3.6.1.4.1.318.0.710 - powerModuleSevereError
1.3.6.1.4.1.318.0.709 - powerRestored
1.3.6.1.4.1.318.0.9 - rPDUBankPhaseLowLoad
1.3.6.1.4.1.318.0.222 - rPDUBankPhaseLowLoadCleared
1.3.6.1.4.1.318.0.223 - rPDUBankPhaseNearOverload
1.3.6.1.4.1.318.0.224 - rPDUBankPhaseNearOverloadCleared
1.3.6.1.4.1.318.0.225 - rPDUBankPhaseOverload
1.3.6.1.4.1.318.0.226 - rPDUBankPhaseOverloadCleared
1.3.6.1.4.1.318.0.227 - rPDUCancelPendingCommand
1.3.6.1.4.1.318.0.283 - rPDUCommunicationEstablished
1.3.6.1.4.1.318.0.266 - rPDUCommunicationLost
1.3.6.1.4.1.318.0.267 - rPDUDeviceConfigChange
1.3.6.1.4.1.318.0.270 - rPDULowLoad
1.3.6.1.4.1.318.0.272 - rPDULowLoadCleared
1.3.6.1.4.1.318.0.273 - rPDUNearOverload
1.3.6.1.4.1.318.0.274 - rPDUNearOverloadCleared
1.3.6.1.4.1.318.0.275 - rPDUOutletConfigChange
1.3.6.1.4.1.318.0.271 - rPDUOutletLowLoad
1.3.6.1.4.1.318.0.630 - rPDUOutletLowLoadCleared
1.3.6.1.4.1.318.0.631 - rPDUOutletNearOverload
1.3.6.1.4.1.318.0.632 - rPDUOutletNearOverloadCleared
1.3.6.1.4.1.318.0.633 - rPDUOutletOff
1.3.6.1.4.1.318.0.269 - rPDUOutletOn
1.3.6.1.4.1.318.0.268 - rPDUOutletOverload
1.3.6.1.4.1.318.0.634 - rPDUOutletOverloadCleared
1.3.6.1.4.1.318.0.635 - rPDUOverload
1.3.6.1.4.1.318.0.276 - rPDUOverloadCleared
1.3.6.1.4.1.318.0.277 - rPDUPhaseConfigChange
1.3.6.1.4.1.318.0.282 - rPDUPowerSupply1Fail
1.3.6.1.4.1.318.0.278 - rPDUPowerSupply1Ok
1.3.6.1.4.1.318.0.279 - rPDUPowerSupply2Fail
1.3.6.1.4.1.318.0.280 - rPDUPowerSupply2Ok
1.3.6.1.4.1.318.0.281 - restartAgent
1.3.6.1.4.1.318.0.29 - returnFromBypass
1.3.6.1.4.1.318.0.23 - returnFromLowBattery
1.3.6.1.4.1.318.0.11 - rintelligenceModuleInserted
1.3.6.1.4.1.318.0.73 - rintelligenceModuleRemoved
1.3.6.1.4.1.318.0.74 - rmPDUCommunicationLost
1.3.6.1.4.1.318.0.229 - rpduCriticalCondition
1.3.6.1.4.1.318.0.750 - rpduCriticalConditionCleared
1.3.6.1.4.1.318.0.751 - rpduInformationalCondition
1.3.6.1.4.1.318.0.754 - rpduInformationalConditionCleared
1.3.6.1.4.1.318.0.755 - rpduWarningCondition
1.3.6.1.4.1.318.0.752 - rpduWarningConditionCleared
1.3.6.1.4.1.318.0.753 - rsCommunicationEstablished
1.3.6.1.4.1.318.0.108 - rsCommunicationLost
1.3.6.1.4.1.318.0.109 - rsConfigChange
1.3.6.1.4.1.318.0.107 - rsLostRedundancy
1.3.6.1.4.1.318.0.105 - rsRedundancyRestored
1.3.6.1.4.1.318.0.106 - rsSourceSwitched
1.3.6.1.4.1.318.0.104 - smartAvrReducing
1.3.6.1.4.1.318.0.31 - smartAvrReducingOff
1.3.6.1.4.1.318.0.35 - smartBoostOff
1.3.6.1.4.1.318.0.34 - smartBoostOn
1.3.6.1.4.1.318.0.6 - smartRelayFault
1.3.6.1.4.1.318.0.55 - smartRelayFaultCleared
1.3.6.1.4.1.318.0.56 - smwCriticalCondition
1.3.6.1.4.1.318.0.300 - smwCriticalConditionCleared
1.3.6.1.4.1.318.0.301 - smwInformationalCondition
1.3.6.1.4.1.318.0.304 - smwInformationalConditionCleared
1.3.6.1.4.1.318.0.305 - smwWarningCondition
1.3.6.1.4.1.318.0.302 - smwWarningConditionCleared
1.3.6.1.4.1.318.0.303 - softwareBypass
1.3.6.1.4.1.318.0.21 - switchedBypass
1.3.6.1.4.1.318.0.22 - temperatureThresholdViolation1
1.3.6.1.4.1.318.0.59 - temperatureThresholdViolation2
1.3.6.1.4.1.318.0.63 - temperatureThresholdViolationCleared1
1.3.6.1.4.1.318.0.60 - temperatureThresholdViolationCleared2
1.3.6.1.4.1.318.0.64 - temporaryBypass
1.3.6.1.4.1.318.0.787 - uioFluidDetected
1.3.6.1.4.1.318.0.831 - uioFluidDetectedCleared
1.3.6.1.4.1.318.0.832 - upsAirFilterWarning
1.3.6.1.4.1.318.0.804 - upsAirFilterWarningCleared
1.3.6.1.4.1.318.0.805 - upsBackfeedRelayFault
1.3.6.1.4.1.318.0.620 - upsBackfeedRelayFaultCleared
1.3.6.1.4.1.318.0.621 - upsBatteryNeedsReplacement
1.3.6.1.4.1.318.0.17 - upsBatteryOverVoltage
1.3.6.1.4.1.318.0.506 - upsBatteryOverVoltageCleared
1.3.6.1.4.1.318.0.507 - upsBatteryPackIncompatible
1.3.6.1.4.1.318.0.806 - upsBatteryPackIncompatibleCleared
1.3.6.1.4.1.318.0.807 - upsBatteryReplaced
1.3.6.1.4.1.318.0.36 - upsBatterySoftBusStartFault
1.3.6.1.4.1.318.0.602 - upsBatterySoftBusStartFaultCleared
1.3.6.1.4.1.318.0.603 - upsBatteryTempSensorFault
1.3.6.1.4.1.318.0.600 - upsBatteryTempSensorFaultCleared
1.3.6.1.4.1.318.0.601 - upsBreakerQ2Closed
1.3.6.1.4.1.318.0.823 - upsBreakerQ2Open
1.3.6.1.4.1.318.0.822 - upsBypassRelayFault
1.3.6.1.4.1.318.0.622 - upsBypassRelayFaultCleared
1.3.6.1.4.1.318.0.623 - upsCalibrationStackChanged
1.3.6.1.4.1.318.0.358 - upsCriticalCondition
1.3.6.1.4.1.318.0.734 - upsCriticalConditionCleared
1.3.6.1.4.1.318.0.735 - upsDiagnosticsFailed
1.3.6.1.4.1.318.0.3 - upsDiagnosticsPassed
1.3.6.1.4.1.318.0.10 - upsDipSwitchChanged
1.3.6.1.4.1.318.0.16 - upsDischarged
1.3.6.1.4.1.318.0.4 - upsEPOActive
1.3.6.1.4.1.318.0.771 - upsEPOActiveCleared
1.3.6.1.4.1.318.0.772 - upsEepromFault
1.3.6.1.4.1.318.0.508 - upsEepromFaultCleared
1.3.6.1.4.1.318.0.509 - upsFirmwareMismatch
1.3.6.1.4.1.318.0.773 - upsFirmwareMismatchCleared
1.3.6.1.4.1.318.0.774 - upsFirmwareUpdateFailed
1.3.6.1.4.1.318.0.761 - upsFirmwareUpdateFinished
1.3.6.1.4.1.318.0.759 - upsFirmwareUpdateStarted
1.3.6.1.4.1.318.0.758 - upsFirmwareUpdateSucceeded
1.3.6.1.4.1.318.0.760 - upsHasNoValidFirmware
1.3.6.1.4.1.318.0.762 - upsHasNoValidFirmwareCleared
1.3.6.1.4.1.318.0.763 - upsInformationalCondition
1.3.6.1.4.1.318.0.738 - upsInformationalConditionCleared
1.3.6.1.4.1.318.0.739 - upsInputContactAbnormal
1.3.6.1.4.1.318.0.808 - upsInputContactAbnormalCleared
1.3.6.1.4.1.318.0.809 - upsInputContactOutputRelayFault
1.3.6.1.4.1.318.0.802 - upsInputContactOutputRelayFaultCleared
1.3.6.1.4.1.318.0.803 - upsInternalOverTemperature
1.3.6.1.4.1.318.0.353 - upsInternalOverTemperatureCleared
1.3.6.1.4.1.318.0.354 - upsInverterFault
1.3.6.1.4.1.318.0.612 - upsInverterFaultCleared
1.3.6.1.4.1.318.0.613 - upsInverterOverTemperature
1.3.6.1.4.1.318.0.504 - upsInverterOverTemperatureCleared
1.3.6.1.4.1.318.0.505 - upsLocalDisplayButtonFault
1.3.6.1.4.1.318.0.767 - upsLocalDisplayButtonFaultCleared
1.3.6.1.4.1.318.0.768 - upsMpuReset
1.3.6.1.4.1.318.0.355 - upsNeedsFactorySetupFault
1.3.6.1.4.1.318.0.769 - upsNeedsFactorySetupFaultCleared
1.3.6.1.4.1.318.0.770 - upsOnBattery
1.3.6.1.4.1.318.0.5 - upsOnBatteryDueToFault
1.3.6.1.4.1.318.0.777 - upsOnBatteryDueToFaultCleared
1.3.6.1.4.1.318.0.778 - upsOscillatorFailed
1.3.6.1.4.1.318.0.775 - upsOscillatorFailedCleared
1.3.6.1.4.1.318.0.776 - upsOutletGroupCommand
1.3.6.1.4.1.318.0.732 - upsOutletGroupTurnedOff
1.3.6.1.4.1.318.0.299 - upsOutletGroupTurnedOn
1.3.6.1.4.1.318.0.298 - upsOutputRelayAbnormal
1.3.6.1.4.1.318.0.810 - upsOutputRelayAbnormalCleared
1.3.6.1.4.1.318.0.811 - upsOutputSwitchClosed
1.3.6.1.4.1.318.0.356 - upsOutputSwitchOpened
1.3.6.1.4.1.318.0.357 - upsOverload
1.3.6.1.4.1.318.0.2 - upsOverloadCleared
1.3.6.1.4.1.318.0.33 - upsPfcFault
1.3.6.1.4.1.318.0.608 - upsPfcFaultCleared
1.3.6.1.4.1.318.0.609 - upsPfcInputRelayFailure
1.3.6.1.4.1.318.0.502 - upsPfcInputRelayFailureCleared
1.3.6.1.4.1.318.0.503 - upsRebootStarted
1.3.6.1.4.1.318.0.15 - upsSleeping
1.3.6.1.4.1.318.0.13 - upsTurnedOff
1.3.6.1.4.1.318.0.12 - upsTurnedOn
1.3.6.1.4.1.318.0.30 - upsWarningCondition
1.3.6.1.4.1.318.0.736 - upsWarningConditionCleared
1.3.6.1.4.1.318.0.737 - upsWokeUp
1.3.6.1.4.1.318.0.14 - userAdded
1.3.6.1.4.1.318.0.82 - userDeleted
1.3.6.1.4.1.318.0.83 - userModified
1.3.6.1.4.1.318.0.84 - xAPCControllerFirmwareUpdateTransferComplete
1.3.6.1.4.1.318.0.500 - xAPCControllerFirmwareUpdateTransferFailed
1.3.6.1.4.1.318.0.501 - xAPCControllerFirmwareUpdateTransferStart
1.3.6.1.4.1.318.0.499 - xATSDCBackupAlarm
1.3.6.1.4.1.318.0.421 - xATSDCBackupAlarmCleared
1.3.6.1.4.1.318.0.422 - xATSDataCommMismatchError
1.3.6.1.4.1.318.0.393 - xATSDataCommMismatchErrorCleared
1.3.6.1.4.1.318.0.394 - xATSDoorOpenAlarm
1.3.6.1.4.1.318.0.419 - xATSDoorOpenAlarmCleared
1.3.6.1.4.1.318.0.420 - xATSEngineStartAsserted
1.3.6.1.4.1.318.0.401 - xATSEngineStopAsserted
1.3.6.1.4.1.318.0.402 - xATSEpoArmed
1.3.6.1.4.1.318.0.410 - xATSEpoReset
1.3.6.1.4.1.318.0.408 - xATSEpoTestMode
1.3.6.1.4.1.318.0.409 - xATSEpoTripped
1.3.6.1.4.1.318.0.407 - xATSGenCommEstablished
1.3.6.1.4.1.318.0.396 - xATSGenCommLost
1.3.6.1.4.1.318.0.395 - xATSGeneratorBatteryCharger
1.3.6.1.4.1.318.0.475 - xATSGeneratorBatteryChargerCleared
1.3.6.1.4.1.318.0.476 - xATSGeneratorControlSwitchNotAuto
1.3.6.1.4.1.318.0.445 - xATSGeneratorControlSwitchNotAutoCleared
1.3.6.1.4.1.318.0.446 - xATSGeneratorEStop
1.3.6.1.4.1.318.0.439 - xATSGeneratorEStopCleared
1.3.6.1.4.1.318.0.440 - xATSGeneratorEngineCold
1.3.6.1.4.1.318.0.459 - xATSGeneratorEngineColdCleared
1.3.6.1.4.1.318.0.460 - xATSGeneratorFuelTankRuptureAlarm
1.3.6.1.4.1.318.0.493 - xATSGeneratorFuelTankRuptureAlarmCleared
1.3.6.1.4.1.318.0.494 - xATSGeneratorGenericEvent
1.3.6.1.4.1.318.0.477 - xATSGeneratorGenericEventCleared
1.3.6.1.4.1.318.0.478 - xATSGeneratorGroundFaultAlarm
1.3.6.1.4.1.318.0.495 - xATSGeneratorGroundFaultAlarmCleared
1.3.6.1.4.1.318.0.496 - xATSGeneratorHighACVEvent
1.3.6.1.4.1.318.0.455 - xATSGeneratorHighACVEventCleared
1.3.6.1.4.1.318.0.456 - xATSGeneratorHighBatteryVolt
1.3.6.1.4.1.318.0.441 - xATSGeneratorHighBatteryVoltCleared
1.3.6.1.4.1.318.0.442 - xATSGeneratorHighCoolantTempAlarm
1.3.6.1.4.1.318.0.427 - xATSGeneratorHighCoolantTempAlarmCleared
1.3.6.1.4.1.318.0.428 - xATSGeneratorLowACVEvent
1.3.6.1.4.1.318.0.453 - xATSGeneratorLowACVEventCleared
1.3.6.1.4.1.318.0.454 - xATSGeneratorLowBatteryVolt
1.3.6.1.4.1.318.0.443 - xATSGeneratorLowBatteryVoltCleared
1.3.6.1.4.1.318.0.444 - xATSGeneratorLowBatteryVoltDuringCrankAlarm
1.3.6.1.4.1.318.0.435 - xATSGeneratorLowBatteryVoltDuringCrankAlarmCleared
1.3.6.1.4.1.318.0.436 - xATSGeneratorLowCoolantLevelAlarm
1.3.6.1.4.1.318.0.423 - xATSGeneratorLowCoolantLevelAlarmCleared
1.3.6.1.4.1.318.0.424 - xATSGeneratorLowCoolantTempAlarm
1.3.6.1.4.1.318.0.431 - xATSGeneratorLowCoolantTempAlarmCleared
1.3.6.1.4.1.318.0.432 - xATSGeneratorLowFuelLevelAlarm
1.3.6.1.4.1.318.0.463 - xATSGeneratorLowFuelLevelAlarmCleared
1.3.6.1.4.1.318.0.464 - xATSGeneratorLowOilLevelAlarm
1.3.6.1.4.1.318.0.433 - xATSGeneratorLowOilLevelAlarmCleared
1.3.6.1.4.1.318.0.434 - xATSGeneratorLowOilPressure
1.3.6.1.4.1.318.0.447 - xATSGeneratorLowOilPressureCleared
1.3.6.1.4.1.318.0.448 - xATSGeneratorLowRunTimeAlarm
1.3.6.1.4.1.318.0.467 - xATSGeneratorLowRunTimeAlarmCleared
1.3.6.1.4.1.318.0.468 - xATSGeneratorOutputBreakerOpen
1.3.6.1.4.1.318.0.461 - xATSGeneratorOutputBreakerOpenCleared
1.3.6.1.4.1.318.0.462 - xATSGeneratorOverload
1.3.6.1.4.1.318.0.451 - xATSGeneratorOverloadCleared
1.3.6.1.4.1.318.0.452 - xATSGeneratorOverspeed
1.3.6.1.4.1.318.0.457 - xATSGeneratorOverspeedCleared
1.3.6.1.4.1.318.0.458 - xATSGeneratorServiceDueAlarm
1.3.6.1.4.1.318.0.471 - xATSGeneratorServiceDueAlarmCleared
1.3.6.1.4.1.318.0.472 - xATSGeneratorShutdown
1.3.6.1.4.1.318.0.473 - xATSGeneratorShutdownCleared
1.3.6.1.4.1.318.0.474 - xATSGeneratorVeryHighCoolantTempAlarm
1.3.6.1.4.1.318.0.429 - xATSGeneratorVeryHighCoolantTempAlarmCleared
1.3.6.1.4.1.318.0.430 - xATSGeneratorVeryLowBatteryVoltDuringCrankAlarm
1.3.6.1.4.1.318.0.437 - xATSGeneratorVeryLowBatteryVoltDuringCrankAlarmCleared
1.3.6.1.4.1.318.0.438 - xATSGeneratorVeryLowCoolantLevelAlarm
1.3.6.1.4.1.318.0.425 - xATSGeneratorVeryLowCoolantLevelAlarmCleared
1.3.6.1.4.1.318.0.426 - xATSGeneratorVeryLowFuelLevelAlarm
1.3.6.1.4.1.318.0.465 - xATSGeneratorVeryLowFuelLevelAlarmCleared
1.3.6.1.4.1.318.0.466 - xATSGeneratorVeryLowOilPressure
1.3.6.1.4.1.318.0.449 - xATSGeneratorVeryLowOilPressureCleared
1.3.6.1.4.1.318.0.450 - xATSGeneratorVeryLowRunTimeAlarm
1.3.6.1.4.1.318.0.469 - xATSGeneratorVeryLowRunTimeAlarmCleared
1.3.6.1.4.1.318.0.470 - xATSInputContactStateAbnormal
1.3.6.1.4.1.318.0.415 - xATSInputContactStateNormal
1.3.6.1.4.1.318.0.416 - xATSInternalATSFault
1.3.6.1.4.1.318.0.399 - xATSInternalATSFaultCleared
1.3.6.1.4.1.318.0.400 - xATSInternalCommError
1.3.6.1.4.1.318.0.391 - xATSInternalCommErrorCleared
1.3.6.1.4.1.318.0.392 - xATSNeutralPosition
1.3.6.1.4.1.318.0.397 - xATSNotInAutomaticMode
1.3.6.1.4.1.318.0.405 - xATSNotInAutomaticModeCleared
1.3.6.1.4.1.318.0.406 - xATSOutputCurrentHighAlarm
1.3.6.1.4.1.318.0.387 - xATSOutputCurrentHighAlarmCleared
1.3.6.1.4.1.318.0.388 - xATSOutputCurrentLowAlarm
1.3.6.1.4.1.318.0.385 - xATSOutputCurrentLowAlarmCleared
1.3.6.1.4.1.318.0.386 - xATSOutputFrequencyAlarm
1.3.6.1.4.1.318.0.389 - xATSOutputFrequencyAlarmCleared
1.3.6.1.4.1.318.0.390 - xATSOutputLoadPoweredByGeneratorAlarm
1.3.6.1.4.1.318.0.497 - xATSOutputLoadPoweredByGeneratorAlarmCleared
1.3.6.1.4.1.318.0.498 - xATSOutputVoltageHighAlarm
1.3.6.1.4.1.318.0.383 - xATSOutputVoltageHighAlarmCleared
1.3.6.1.4.1.318.0.384 - xATSOutputVoltageLowAlarm
1.3.6.1.4.1.318.0.381 - xATSOutputVoltageLowAlarmCleared
1.3.6.1.4.1.318.0.382 - xATSRemoteStartContactMismatch
1.3.6.1.4.1.318.0.417 - xATSRemoteStartContactMismatchCleared
1.3.6.1.4.1.318.0.418 - xATSS1BadPhaseBalance
1.3.6.1.4.1.318.0.726 - xATSS1BadPhaseBalanceCleared
1.3.6.1.4.1.318.0.727 - xATSS1BadPhaseRotation
1.3.6.1.4.1.318.0.724 - xATSS1BadPhaseRotationCleared
1.3.6.1.4.1.318.0.725 - xATSStartFailure
1.3.6.1.4.1.318.0.403 - xATSStopFailure
1.3.6.1.4.1.318.0.404 - xATSSwitchTransferEvent
1.3.6.1.4.1.318.0.398 - xATSTestCanceled
1.3.6.1.4.1.318.0.412 - xATSTestFailed
1.3.6.1.4.1.318.0.413 - xATSTestInitiated
1.3.6.1.4.1.318.0.411 - xATSTestPassed
1.3.6.1.4.1.318.0.414 - xPDUBranchCurrentHighAlarm
1.3.6.1.4.1.318.0.342 - xPDUBranchCurrentHighAlarmCleared
1.3.6.1.4.1.318.0.343 - xPDUBranchCurrentLowAlarm
1.3.6.1.4.1.318.0.340 - xPDUBranchCurrentLowAlarmCleared
1.3.6.1.4.1.318.0.341 - xPDUBranchCurrentMaxAlarm
1.3.6.1.4.1.318.0.628 - xPDUBranchCurrentMaxAlarmCleared
1.3.6.1.4.1.318.0.629 - xPDUBranchCurrentMinAlarm
1.3.6.1.4.1.318.0.626 - xPDUBranchCurrentMinAlarmCleared
1.3.6.1.4.1.318.0.627 - xPDUBreakerChangeEvent
1.3.6.1.4.1.318.0.488 - xPDUBreakerPositionAlarm
1.3.6.1.4.1.318.0.486 - xPDUBreakerPositionAlarmCleared
1.3.6.1.4.1.318.0.487 - xPDUBypassVoltageHighAlarm
1.3.6.1.4.1.318.0.318 - xPDUBypassVoltageHighAlarmCleared
1.3.6.1.4.1.318.0.319 - xPDUBypassVoltageLowAlarm
1.3.6.1.4.1.318.0.316 - xPDUBypassVoltageLowAlarmCleared
1.3.6.1.4.1.318.0.317 - xPDUCoolingFanAlarm
1.3.6.1.4.1.318.0.336 - xPDUCoolingFanAlarmCleared
1.3.6.1.4.1.318.0.337 - xPDUDataCommMismatchError
1.3.6.1.4.1.318.0.489 - xPDUDataCommMismatchErrorCleared
1.3.6.1.4.1.318.0.490 - xPDUEpoArmed
1.3.6.1.4.1.318.0.483 - xPDUEpoTestMode
1.3.6.1.4.1.318.0.482 - xPDUFuseBlownAlarm
1.3.6.1.4.1.318.0.484 - xPDUFuseBlownAlarmCleared
1.3.6.1.4.1.318.0.485 - xPDUInputContactStateAbnormal
1.3.6.1.4.1.318.0.332 - xPDUInputContactStateNormal
1.3.6.1.4.1.318.0.333 - xPDUInputVoltageHighAlarm
1.3.6.1.4.1.318.0.314 - xPDUInputVoltageHighAlarmCleared
1.3.6.1.4.1.318.0.315 - xPDUInputVoltageLowAlarm
1.3.6.1.4.1.318.0.312 - xPDUInputVoltageLowAlarmCleared
1.3.6.1.4.1.318.0.313 - xPDUInternalCommError
1.3.6.1.4.1.318.0.344 - xPDUInternalCommErrorCleared
1.3.6.1.4.1.318.0.479 - xPDUOutputCurrentHighAlarm
1.3.6.1.4.1.318.0.326 - xPDUOutputCurrentHighAlarmCleared
1.3.6.1.4.1.318.0.327 - xPDUOutputCurrentLowAlarm
1.3.6.1.4.1.318.0.324 - xPDUOutputCurrentLowAlarmCleared
1.3.6.1.4.1.318.0.325 - xPDUOutputFrequencyAlarm
1.3.6.1.4.1.318.0.328 - xPDUOutputFrequencyAlarmCleared
1.3.6.1.4.1.318.0.329 - xPDUOutputNeutralCurrentHighAlarm
1.3.6.1.4.1.318.0.334 - xPDUOutputNeutralCurrentHighAlarmCleared
1.3.6.1.4.1.318.0.335 - xPDUOutputVoltageHighAlarm
1.3.6.1.4.1.318.0.322 - xPDUOutputVoltageHighAlarmCleared
1.3.6.1.4.1.318.0.323 - xPDUOutputVoltageLowAlarm
1.3.6.1.4.1.318.0.320 - xPDUOutputVoltageLowAlarmCleared
1.3.6.1.4.1.318.0.321 - xPDUSystemGroundCurrentAlarm
1.3.6.1.4.1.318.0.330 - xPDUSystemGroundCurrentAlarmCleared
1.3.6.1.4.1.318.0.331 - xPDUSystemInMaintenanceBypassMode
1.3.6.1.4.1.318.0.491 - xPDUSystemInUPSOperationalMode
1.3.6.1.4.1.318.0.492 - xPDUSystemStateAlarm
1.3.6.1.4.1.318.0.480 - xPDUSystemStateAlarmCleared
1.3.6.1.4.1.318.0.481 - xPDUTransformerTempAlarm
1.3.6.1.4.1.318.0.338 - xPDUTransformerTempAlarmCleared
1.3.6.1.4.1.318.0.339