PowerNet-MIB
American Power Conversion Corp.snmptranslate -m PowerNet-MIB -Tpsnmpwalk -v2c -c <community> -m PowerNet-MIB <host> 1.3.6.1.4.1.318Imports
| INET-ADDRESS-MIB | InetAddress, InetAddressType |
|---|---|
| RFC1155-SMI | Gauge32 |
| SNMP-FRAMEWORK-MIB | SnmpAdminString |
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
| SNMPv2-MIB | sysDescr |
| SNMPv2-SMI | Bits, Integer32, IpAddress, MODULE-IDENTITY, MibIdentifier, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, TRAP-TYPE, TimeTicks, Unsigned32, enterprises, iso |
| SNMPv2-TC | DisplayString, MacAddress, PhysAddress, TEXTUAL-CONVENTION |
OID tree
| Name | OID | Type | Access | Status | Example | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Napc | 1.3.6.1.4.1.318 | ||||||||||||
| Nproducts | 1.3.6.1.4.1.318.1 | ||||||||||||
| Nhardware | 1.3.6.1.4.1.318.1.1 | ||||||||||||
| NcPDU | 1.3.6.1.4.1.318.1.1.32 | ||||||||||||
| NpduNamePlate | 1.3.6.1.4.1.318.1.1.32.1 | ||||||||||||
| SpduNamePlateTableSize | 1.3.6.1.4.1.318.1.1.32.1.1 | Integer32 (1..256) | RO | ||||||||||
scalar · Integer32 (1..256) · read-only · current The total number of PDUs | |||||||||||||
| TpduNamePlateTable | 1.3.6.1.4.1.318.1.1.32.1.2 | NA | |||||||||||
table · not-accessible · current A table of PDU nameplate data | |||||||||||||
| RpduNamePlateEntry | 1.3.6.1.4.1.318.1.1.32.1.2.1 | NA | |||||||||||
row · not-accessible · current Nameplate data from the PDU being queried. The numbers of entries equals the value of pduNamePlateTableSize.
| |||||||||||||
| CpduNamePlateIndex | 1.3.6.1.4.1.318.1.1.32.1.2.1.1 | Integer32 (1..256) | NA | ||||||||||
column · Integer32 (1..256) · not-accessible · current The index of the PDU nameplate table entry | |||||||||||||
| CpduNamePlateName | 1.3.6.1.4.1.318.1.1.32.1.2.1.2 | DisplayString | RO | ||||||||||
column · DisplayString · read-only · current A user-defined string identifying the PDU | |||||||||||||
| CpduNamePlateLocation | 1.3.6.1.4.1.318.1.1.32.1.2.1.3 | DisplayString | RO | ||||||||||
column · DisplayString · read-only · current A user-defined string identifying the location of PDU | |||||||||||||
| CpduNamePlateInetAddressType | 1.3.6.1.4.1.318.1.1.32.1.2.1.4 | INTEGER | RO | ||||||||||
column · INTEGER · read-only · current The type of address format | |||||||||||||
| CpduNamePlateIPAddress | 1.3.6.1.4.1.318.1.1.32.1.2.1.5 | InetAddress | RO | ||||||||||
column · InetAddress · read-only · current The current IP address. A value of 0.0.0.0 indicates an error or an unset option | |||||||||||||
| CpduNamePlateInetNetMask | 1.3.6.1.4.1.318.1.1.32.1.2.1.6 | InetAddress | RO | ||||||||||
column · InetAddress · read-only · current The current netmask. A value of 0.0.0.0 indiates an error or an unset option | |||||||||||||
| CpduNamePlateInetGateway | 1.3.6.1.4.1.318.1.1.32.1.2.1.7 | InetAddress | RO | ||||||||||
column · InetAddress · read-only · current The current gateway. A value of 0.0.0.0 indicates an error or an unset option | |||||||||||||
| CpduNamePlateMACAddress | 1.3.6.1.4.1.318.1.1.32.1.2.1.8 | MacAddress | RO | ||||||||||
column · MacAddress · read-only · current The assigned MAC address for the PDU | |||||||||||||
| CpduNamePlateUTCTimeOffset | 1.3.6.1.4.1.318.1.1.32.1.2.1.9 | DisplayString | RO | ||||||||||
column · DisplayString · read-only · current The difference in hours and minutes from Coordinated Universal Time(UTC) for the time used in a particular time zone | |||||||||||||
| CpduNamePlateModelNumber | 1.3.6.1.4.1.318.1.1.32.1.2.1.10 | DisplayString | RO | 200-240V, 32A, 7.4kVA, 50/60Hz | |||||||||
column · DisplayString · read-only · current The PDU model number Example values from LibreNMS test devices
| |||||||||||||
| CpduNamePlatePartNumber | 1.3.6.1.4.1.318.1.1.32.1.2.1.11 | DisplayString | RO | APDU10150SM | |||||||||
column · DisplayString · read-only · current The PDU part number Example values from LibreNMS test devices
| |||||||||||||
| CpduNamePlateSerialNumber | 1.3.6.1.4.1.318.1.1.32.1.2.1.12 | DisplayString | RO | 5A1234Y56789 | |||||||||
column · DisplayString · read-only · current The PDU serial number Example values from LibreNMS test devices
| |||||||||||||
| CpduNamePlateDateofManufacture | 1.3.6.1.4.1.318.1.1.32.1.2.1.13 | DisplayString | RO | ||||||||||
column · DisplayString · read-only · current The date the PDU was manufactured in mm/dd/yyyy format | |||||||||||||
| CpduNamePlateFirmwareVersion | 1.3.6.1.4.1.318.1.1.32.1.2.1.14 | DisplayString | RO | 2.0.8.2 | |||||||||
column · DisplayString · read-only · current The PDU firmware version Example values from LibreNMS test devices
| |||||||||||||
| CpduNamePlateFirmwareVersionTimeStamp | 1.3.6.1.4.1.318.1.1.32.1.2.1.15 | DisplayString | RO | ||||||||||
column · DisplayString · read-only · current Timestamp of when the PDU firmware was last updated | |||||||||||||
| CpduNamePlateType | 1.3.6.1.4.1.318.1.1.32.1.2.1.16 | INTEGER | RO | ||||||||||
column · INTEGER · read-only · current The type of input
| |||||||||||||
| CpduNamePlateIPV6Address | 1.3.6.1.4.1.318.1.1.32.1.2.1.17 | DisplayString | RO | ||||||||||
column · DisplayString · read-only · current The current IPV6 address. A value of 0.0.0.0 indicates an error or an unset option | |||||||||||||
| CpduNamePlateHWVersion | 1.3.6.1.4.1.318.1.1.32.1.2.1.18 | DisplayString | RO | ||||||||||
column · DisplayString · read-only · current Displays Hardware version of the PDU. | |||||||||||||
| NpduUnit | 1.3.6.1.4.1.318.1.1.32.2 | ||||||||||||
| SpduUnitTableSize | 1.3.6.1.4.1.318.1.1.32.2.1 | Integer32 (1..256) | RO | ||||||||||
scalar · Integer32 (1..256) · read-only · current The number of units. | |||||||||||||
| TpduUnitConfigTable | 1.3.6.1.4.1.318.1.1.32.2.2 | NA | |||||||||||
table · not-accessible · current A table of PDU configuration data | |||||||||||||
| RpduUnitConfigEntry | 1.3.6.1.4.1.318.1.1.32.2.2.1 | NA | |||||||||||
row · not-accessible · current Configuration data from the PDU being queried. The number of entries equals the value of pduUnitTableSize
| |||||||||||||
| CpduUnitConfigIndex | 1.3.6.1.4.1.318.1.1.32.2.2.1.1 | Integer32 (1..256) | NA | ||||||||||
column · Integer32 (1..256) · not-accessible · current The index of the PDU Unit Config Entry | |||||||||||||
| CpduUnitConfigName | 1.3.6.1.4.1.318.1.1.32.2.2.1.2 | DisplayString | RW | ||||||||||
column · DisplayString · read-write · current A user-defined string identifying the PDU | |||||||||||||
| CpduUnitConfigLocation | 1.3.6.1.4.1.318.1.1.32.2.2.1.3 | DisplayString | RW | ||||||||||
column · DisplayString · read-write · current A user-defined string identifying the location of the PDU | |||||||||||||
| CpduUnitConfigDisplayOrientation | 1.3.6.1.4.1.318.1.1.32.2.2.1.4 | INTEGER | RW | ||||||||||
column · INTEGER · read-write · current Indicates the intended physical orientation of the oLED display displayNormal (1) indicates normal orientation. displayReverse (2) indicates upside down orientation NOTE: This OID is compatible only with the two display NMC module. It does not work with the single display NMC module.
| |||||||||||||
| CpduUnitConfigOledDisplayControl | 1.3.6.1.4.1.318.1.1.32.2.2.1.5 | INTEGER | RW | ||||||||||
column · INTEGER · read-write · current Used to turn oled display On or Off displayOff (1) to turn dispaly OFF. displayOn (2) to turn dispaly ON
| |||||||||||||
| CpduUnitConfigColdstartDelay | 1.3.6.1.4.1.318.1.1.32.2.2.1.6 | Unsigned32 (0..3600) | RW | ||||||||||
column · Unsigned32 (0..3600) · read-write · current The amount of time, specified in seconds, between when power is provided to the PDU and when the PDU start providing basic master power to the outlets | |||||||||||||
| CpduUnitConfigGlobalOutletStateOnStartup | 1.3.6.1.4.1.318.1.1.32.2.2.1.7 | INTEGER | RW | ||||||||||
column · INTEGER · read-write · current The outlet state on device startup; applies to all outlets unless overridden at the outlet level
| |||||||||||||
| CpduUnitConfigLowerCriticalThreshold | 1.3.6.1.4.1.318.1.1.32.2.2.1.8 | Unsigned32 | RW | ||||||||||
column · Unsigned32 · read-write · current User-defined lower critical unit active power alarm threshold measured in Watts | |||||||||||||
| CpduUnitConfigLowerWarningThreshold | 1.3.6.1.4.1.318.1.1.32.2.2.1.9 | Unsigned32 | RW | ||||||||||
column · Unsigned32 · read-write · current User-defined lower non-critical (warning) unit active power alarm threshold measured in Watts | |||||||||||||
| CpduUnitConfigUpperCriticalThreshold | 1.3.6.1.4.1.318.1.1.32.2.2.1.10 | Unsigned32 | RW | ||||||||||
column · Unsigned32 · read-write · current User-defined upper critical unit active power alarm threshold measured in Watts | |||||||||||||
| CpduUnitConfigUpperWarningThreshold | 1.3.6.1.4.1.318.1.1.32.2.2.1.11 | Unsigned32 | RW | ||||||||||
column · Unsigned32 · read-write · current User-defined upper non-critical (warning) unit active power alarm threshold measured in Watts | |||||||||||||
| CpduUnitConfigAlarmResetThreshold | 1.3.6.1.4.1.318.1.1.32.2.2.1.12 | Unsigned32 | RW | ||||||||||
column · Unsigned32 · read-write · current The hysteresis used for deassertions in Watts | |||||||||||||
| CpduUnitConfigAlarmStateChangeDelay | 1.3.6.1.4.1.318.1.1.32.2.2.1.13 | Unsigned32 | RW | ||||||||||
column · Unsigned32 · read-write · current The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported. | |||||||||||||
| CpduUnitConfigEnabledThresholds | 1.3.6.1.4.1.318.1.1.32.2.2.1.14 | Bits | RW | ||||||||||
column · Bits · read-write · current A bit string indicating which alarm thresholds are enabled
| |||||||||||||
| CpduUnitConfigPeakPowerReset | 1.3.6.1.4.1.318.1.1.32.2.2.1.15 | INTEGER | RW | ||||||||||
column · INTEGER · read-write · current Setting this OID to reset (2) will cause the existing peak power value to be replaced by the current load power value. Getting this OID will do nothing and return the noOperation(1) value.
| |||||||||||||
| CpduUnitConfigEnergyReset | 1.3.6.1.4.1.318.1.1.32.2.2.1.16 | INTEGER | RW | ||||||||||
column · INTEGER · read-write · current Setting this OID to reset (2) will cause the device energy meter value to be reset to zero. Getting this OID in models that support this feature will do nothing and return the noOperation(1) value. Models that do not support this feature will respond to this OID with a value of notSupported (3). Attempts to set this OID in these models will fail.
| |||||||||||||
| CpduUnitConfigOutletPeakPowerReset | 1.3.6.1.4.1.318.1.1.32.2.2.1.17 | INTEGER | RW | ||||||||||
column · INTEGER · read-write · current Setting this OID to reset (2) will cause the outlet peak power meter value to be reset to zero. Getting this OID in models that support this feature will do nothing and return the noOperation(1) value. Models that do not support this feature will respond to this OID with a value of notSupported (3). Attempts to set this OID in these models will fail.
| |||||||||||||
| CpduUnitConfigOutletEnergyReset | 1.3.6.1.4.1.318.1.1.32.2.2.1.18 | INTEGER | RW | ||||||||||
column · INTEGER · read-write · current Setting this OID to reset (2) will cause the outlet energy meter value to be reset to zero. Getting this OID in models that support this feature will do nothing and return the noOperation(1) value. Models that do not support this feature will respond to this OID with a value of notSupported (3). Attempts to set this OID in these models will fail.
| |||||||||||||
| CpduUnitConfigSsh | 1.3.6.1.4.1.318.1.1.32.2.2.1.19 | INTEGER | RW | ||||||||||
column · INTEGER · read-write · current Setting this OID to off(0) will disable the SSH connection. Setting this OID to on(1) will enable the SSH connection.
| |||||||||||||
| CpduUnitConfigResetNetworkManagementCard | 1.3.6.1.4.1.318.1.1.32.2.2.1.20 | INTEGER | RW | ||||||||||
column · INTEGER · read-write · current Getting this OID will return noOperation(0). Setting this OID to reset(1) will reset NMC.
| |||||||||||||
| CpduUnitConfigUsb | 1.3.6.1.4.1.318.1.1.32.2.2.1.21 | INTEGER | RW | ||||||||||
column · INTEGER · read-write · current Setting this OID to off(0) will disable the USB port. Setting this OID to on(1) will enable the USB port.
| |||||||||||||
| CpduUnitConfigDaisyChainState | 1.3.6.1.4.1.318.1.1.32.2.2.1.22 | INTEGER | RW | ||||||||||
column · INTEGER · read-write · current Setting this OID to 0 will enable daisychain qna mode. Setting this OID to 1 will enable daisychain rna mode. Should be applied on last pdu in DaisyChain
| |||||||||||||
| CpduUnitConfigTelnet | 1.3.6.1.4.1.318.1.1.32.2.2.1.23 | INTEGER | RW | ||||||||||
column · INTEGER · read-write · current Setting this OID to off(0) will disable the Telnet connection. Setting this OID to on(1) will enable the Telnet connection. Changes made will take effect only after reboot.
| |||||||||||||
| TpduUnitPropertiesTable | 1.3.6.1.4.1.318.1.1.32.2.3 | NA | |||||||||||
table · not-accessible · current A table of PDU properties | |||||||||||||
| RpduUnitPropertiesEntry | 1.3.6.1.4.1.318.1.1.32.2.3.1 | NA | |||||||||||
row · not-accessible · current A unit properties entry containing objects for a particular unit. | |||||||||||||
| CpduUnitPropertiesIndex | 1.3.6.1.4.1.318.1.1.32.2.3.1.1 | Integer32 (1..256) | NA | ||||||||||
column · Integer32 (1..256) · not-accessible · current The index of the PDU properties table entry | |||||||||||||
| CpduUnitPropertiesName | 1.3.6.1.4.1.318.1.1.32.2.3.1.2 | DisplayString | RO | ||||||||||
column · DisplayString · read-only · current A user-defined string identifying the PDU | |||||||||||||
| CpduUnitPropertiesOutletCount | 1.3.6.1.4.1.318.1.1.32.2.3.1.3 | Integer32 (1..256) | RO | ||||||||||
column · Integer32 (1..256) · read-only · current The total number of outlets on the PDU | |||||||||||||
| CpduUnitPropertiesSwitchedOutletCount | 1.3.6.1.4.1.318.1.1.32.2.3.1.4 | Integer32 (1..256) | RO | ||||||||||
column · Integer32 (1..256) · read-only · current The total number of switched outlets on the PDU | |||||||||||||
| CpduUnitPropertiesMeteredOutletCount | 1.3.6.1.4.1.318.1.1.32.2.3.1.5 | Integer32 (1..256) | RO | ||||||||||
column · Integer32 (1..256) · read-only · current The total number of metered outlets on the PDU | |||||||||||||
| CpduUnitPropertiesInputPhaseCount | 1.3.6.1.4.1.318.1.1.32.2.3.1.6 | Integer32 (1..256) | RO | ||||||||||
column · Integer32 (1..256) · read-only · current The total number of phases on the PDU | |||||||||||||
| CpduUnitPropertiesCircuitBreakerCount | 1.3.6.1.4.1.318.1.1.32.2.3.1.7 | Integer32 (0..255) | RO | ||||||||||
column · Integer32 (0..255) · read-only · current The total number of circuit breaker on the PDU | |||||||||||||
| CpduUnitPropertiesMaxExternalSensorCount | 1.3.6.1.4.1.318.1.1.32.2.3.1.8 | Integer32 (0..255) | RO | ||||||||||
column · Integer32 (0..255) · read-only · current The maximum number of external sensors that can be connected to the PDU | |||||||||||||
| CpduUnitPropertiesConnExternalSensorCount | 1.3.6.1.4.1.318.1.1.32.2.3.1.9 | Integer32 (0..255) | RO | ||||||||||
column · Integer32 (0..255) · read-only · current The current number of external sensors connected to the PDU | |||||||||||||
| CpduUnitPropertiesRatedVoltage | 1.3.6.1.4.1.318.1.1.32.2.3.1.10 | DisplayString | RO | ||||||||||
column · DisplayString · read-only · current The PDU voltage rating in Volts | |||||||||||||
| CpduUnitPropertiesRatedMaxCurrent | 1.3.6.1.4.1.318.1.1.32.2.3.1.11 | DisplayString | RO | ||||||||||
column · DisplayString · read-only · current The PDU current rating in Amps | |||||||||||||
| CpduUnitPropertiesRatedFrequency | 1.3.6.1.4.1.318.1.1.32.2.3.1.12 | DisplayString | RO | ||||||||||
column · DisplayString · read-only · current The PDU frequency rating in Hz | |||||||||||||
| CpduUnitPropertiesRatedPower | 1.3.6.1.4.1.318.1.1.32.2.3.1.13 | DisplayString | RO | ||||||||||
column · DisplayString · read-only · current The PDU VA (VoltAmps) rating. | |||||||||||||
| CpduUnitPropertiesOrientation | 1.3.6.1.4.1.318.1.1.32.2.3.1.14 | INTEGER | RO | ||||||||||
column · INTEGER · read-only · current The PDU orientation
| |||||||||||||
| CpduUnitPropertiesOutletLayout | 1.3.6.1.4.1.318.1.1.32.2.3.1.15 | INTEGER | RO | ||||||||||
column · INTEGER · read-only · current The outlet layout for the PDU. Getting this OID will return outlet layout for the device. seqPhaseToNeutral(1) indicates outlet layout as follows: 1:1-N,2:2-N,3:3-N,4:1-N,5:2-N,... seqPhaseToPhase(2) indicates outlet layout as follows: 1:1-2,2:2-3,3:3-1,4:1-2,5:2-3,... seqPhToNeu21PhToPh(3) indicates outlet layout as follows: 1:1-N,2:2-N...21:3-N,22:1-2,23:2-3,24:3-1,... seqPhToPhGrouped(4) indicates outlet layout as follows: This unit has 3 outlet groups. Group 1:1-2, Group 2:2-3, Group 3:3-1. seqPhToNGrouped(5) indicates outlet layout as follows: This unit has 3 outlet groups. Group 1:1-N, Group 2:2-N, Group 3:3-N. seqPToN1516PToPGrouped(6) indicates outlet layout as follows: This unit has 4 outlet groups. Group 1 (Outlets 1-14):1-2, Group 2 (Outlets 15-16):1-N, Group 3:2-3, Group 4:3-1. seqPhToPh2xGrouped(7) indicates outlet layout as follows: This unit has 6 outlet groups. Group 1:1-2, Group 2:1-2, Group 3:2-3, Group 4:2-3, Group 5:3-1, Group 6:3-1. seqPhToN2xGrouped(8) indicates outlet layout as follows: This unit has 6 outlet groups. Group 1:1-N, Group 2:1-N, Group 3:2-N, Group 4:2-N, Group 5:3-N, Group 6:3-N. seqNotApplicable(9):
| |||||||||||||
| CpduUnitPropertiesCascadeMemberType | 1.3.6.1.4.1.318.1.1.32.2.3.1.16 | INTEGER | RO | ||||||||||
column · INTEGER · read-only · current The cascading member type
| |||||||||||||
| TpduUnitStatusTable | 1.3.6.1.4.1.318.1.1.32.2.4 | NA | |||||||||||
table · not-accessible · current A table of PDU status information | |||||||||||||
| RpduUnitStatusEntry | 1.3.6.1.4.1.318.1.1.32.2.4.1 | NA | |||||||||||
| CpduUnitStatusIndex | 1.3.6.1.4.1.318.1.1.32.2.4.1.1 | Integer32 (1..256) | NA | 1 | |||||||||
column · Integer32 (1..256) · not-accessible · current The index of the PDU status table entry Example values from LibreNMS test devices
| |||||||||||||
| CpduUnitStatusName | 1.3.6.1.4.1.318.1.1.32.2.4.1.2 | DisplayString | RO | pdu-under-test.hostname | |||||||||
column · DisplayString · read-only · current A user-defined string identifying the PDU Example values from LibreNMS test devices
| |||||||||||||
| CpduUnitStatusLoadState | 1.3.6.1.4.1.318.1.1.32.2.4.1.3 | INTEGER | RO | normal(5) | |||||||||
column · INTEGER · read-only · current Returns the present load status of the PDU based on Active Power.
Example values from LibreNMS test devices
| |||||||||||||
| CpduUnitStatusActivePower | 1.3.6.1.4.1.318.1.1.32.2.4.1.4 | Integer32 | RO | 258 | |||||||||
column · Integer32 · read-only · current Returns power consumption, in Watts(W), of the PDU being queried. Example values from LibreNMS test devices
| |||||||||||||
| CpduUnitStatusApparentPower | 1.3.6.1.4.1.318.1.1.32.2.4.1.5 | Integer32 | RO | 301 | |||||||||
column · Integer32 · read-only · current Returns power consumption, in Volt-Amps(VA) of the PDU load being queried. Example values from LibreNMS test devices
| |||||||||||||
| CpduUnitStatusPeakPower | 1.3.6.1.4.1.318.1.1.32.2.4.1.6 | Integer32 | RO | 657 | |||||||||
column · Integer32 · read-only · current Returns peak power consumption, in Watts(W), of the PDU being queried. Example values from LibreNMS test devices
| |||||||||||||
| CpduUnitStatusPeakPowerTimestamp | 1.3.6.1.4.1.318.1.1.32.2.4.1.7 | DisplayString | RO | 2010/01/01 00:34:36 | |||||||||
column · DisplayString · read-only · current Indicates the date and time that peak power consumption occurred Example values from LibreNMS test devices
| |||||||||||||
| CpduUnitStatusPeakPowerStartTime | 1.3.6.1.4.1.318.1.1.32.2.4.1.8 | DisplayString | RO | 2010/01/01 00:34:36 | |||||||||
column · DisplayString · read-only · current Indicates the date and time of the last device peak power reset Example values from LibreNMS test devices
| |||||||||||||
| CpduUnitStatusEnergy | 1.3.6.1.4.1.318.1.1.32.2.4.1.9 | Integer32 | RO | 7918 | |||||||||
column · Integer32 · read-only · current Returns total energy consumed, in tenths of Kilowatt-Hours(kWh), of the PDU over its lifetime. Example values from LibreNMS test devices
| |||||||||||||
| CpduUnitStatusResettableEnergy | 1.3.6.1.4.1.318.1.1.32.2.4.1.10 | Integer32 | RO | 7918 | |||||||||
column · Integer32 · read-only · current A user resettable energy meter measuring PDU energy consumption in tenths of kilowatt-hours(kWh). Example values from LibreNMS test devices
| |||||||||||||
| CpduUnitStatusEnergyStartTime | 1.3.6.1.4.1.318.1.1.32.2.4.1.11 | DisplayString | RO | 2010/01/01 00:34:36 | |||||||||
column · DisplayString · read-only · current Indicates the date and time of the last device energy meter reset Example values from LibreNMS test devices
| |||||||||||||
| CpduUnitStatusOutletsEnergyStartTime | 1.3.6.1.4.1.318.1.1.32.2.4.1.12 | DisplayString | RO | 2010/01/01 00:34:36 | |||||||||
column · DisplayString · read-only · current Indicates the date and time of the last outlets energy meter reset Example values from LibreNMS test devices
| |||||||||||||
| CpduUnitStatusPowerFactor | 1.3.6.1.4.1.318.1.1.32.2.4.1.13 | Integer32 | RO | 85 | |||||||||
column · Integer32 · read-only · current Returns the ratio of active to apparent power of the PDU, in the hundreths of PowerFactor. Example values from LibreNMS test devices
| |||||||||||||
| TpduUnitPsTable | 1.3.6.1.4.1.318.1.1.32.2.5 | NA | |||||||||||
table · not-accessible · current Aggregate Object with number of entries equal to number of PDUs and Power share | |||||||||||||
| RpduUnitPsEntry | 1.3.6.1.4.1.318.1.1.32.2.5.1 | NA | |||||||||||
row · not-accessible · current The Power share entry containing the avaliable, input, output etc.
| |||||||||||||
| CpduUnitPsIndex | 1.3.6.1.4.1.318.1.1.32.2.5.1.1 | INTEGER (1..4) | RO | ||||||||||
column · INTEGER (1..4) · read-only · current The index of the PDU Power share table entry | |||||||||||||
| CpduUnitPsSupportUpstreamStatus | 1.3.6.1.4.1.318.1.1.32.2.5.1.2 | INTEGER | RO | ||||||||||
column · INTEGER · read-only · current Deprecated because of newly added OID
| |||||||||||||
| CpduUnitPsSupportDownstreamStatus | 1.3.6.1.4.1.318.1.1.32.2.5.1.3 | INTEGER | RO | ||||||||||
column · INTEGER · read-only · current Deprecated because of newly added OID
| |||||||||||||
| CpduUnitPsOptMode | 1.3.6.1.4.1.318.1.1.32.2.5.1.4 | INTEGER | RO | ||||||||||
column · INTEGER · read-only · current Operating power status.
| |||||||||||||
| CpduUnitPsFunc | 1.3.6.1.4.1.318.1.1.32.2.5.1.5 | INTEGER | RW | ||||||||||
column · INTEGER · read-write · current Setting this OID to off(0) will disable the Powershare function. Setting this OID to on(1) will enable the Powershare function.
| |||||||||||||
| CpduUnitPsBackupProtection | 1.3.6.1.4.1.318.1.1.32.2.5.1.6 | INTEGER | RO | ||||||||||
column · INTEGER · read-only · current Power share support from either of the adjacent PDUs
| |||||||||||||
| CpduUnitPsOutput | 1.3.6.1.4.1.318.1.1.32.2.5.1.7 | INTEGER | RO | ||||||||||
column · INTEGER · read-only · current Power share support to either of the adjacent PDUs
| |||||||||||||
| NpduInputPhase | 1.3.6.1.4.1.318.1.1.32.3 | ||||||||||||
| SpduInputPhaseTableSize | 1.3.6.1.4.1.318.1.1.32.3.1 | Integer32 (1..256) | RO | ||||||||||
scalar · Integer32 (1..256) · read-only · current The number of PDU Input Phases | |||||||||||||
| TpduInputPhaseConfigTable | 1.3.6.1.4.1.318.1.1.32.3.2 | NA | |||||||||||
table · not-accessible · current A table of PDU Input Phase configuration data | |||||||||||||
| RpduInputPhaseConfigEntry | 1.3.6.1.4.1.318.1.1.32.3.2.1 | NA | |||||||||||
row · not-accessible · current An input phase entry containing objects for a particular input phase. | |||||||||||||
| CpduInputPhaseConfigIndex | 1.3.6.1.4.1.318.1.1.32.3.2.1.1 | Integer32 (1..256) | NA | ||||||||||
column · Integer32 (1..256) · not-accessible · current The index of the PDU Input Phase configuration table entry | |||||||||||||
| CpduInputPhaseConfigCount | 1.3.6.1.4.1.318.1.1.32.3.2.1.2 | Integer32 (1..256) | RO | ||||||||||
column · Integer32 (1..256) · read-only · current The total number of Input Phases | |||||||||||||
| CpduInputPhaseConfigOverloadRestriction | 1.3.6.1.4.1.318.1.1.32.3.2.1.3 | INTEGER | RW | ||||||||||
column · INTEGER · read-write · current This OID controls the behavior of a Switched PDU Input Phase when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will always allow the outlets on the corresponding Input Phase to turn on. Setting this OID to restrictOnUpperWarning (2) will not allow outlets on the corresponding Input Phase to turn on if the pduInputPhaseConfigUpperWarningThreshold OID is exceeded. Setting this OID to restrictOnUpperCritical (3) will not allow outlets on the corresponding Input Phase to turn on if the pduInputPhaseConfigUpperCriticalThreshold OID is exceeded. Models that do not support this feature will respond to this OID with a value of notSupported (4). Attempts to set this OID in these models will fail.
| |||||||||||||
| CpduInputPhaseConfigCurrentLowerCriticalThreshold | 1.3.6.1.4.1.318.1.1.32.3.2.1.4 | Unsigned32 | RW | ||||||||||
column · Unsigned32 · read-write · current User-defined lower critical input phase current alarm threshold in hundredths of Amps(A). | |||||||||||||
| CpduInputPhaseConfigCurrentLowerWarningThreshold | 1.3.6.1.4.1.318.1.1.32.3.2.1.5 | Unsigned32 | RW | ||||||||||
column · Unsigned32 · read-write · current User-defined lower non-critical (warning) input phase current alarm threshold in hundredths of Amps(A). | |||||||||||||
| CpduInputPhaseConfigCurrentUpperCriticalThreshold | 1.3.6.1.4.1.318.1.1.32.3.2.1.6 | Unsigned32 | RW | ||||||||||
column · Unsigned32 · read-write · current User-defined upper critical input phase current alarm threshold in hundredths of Amps(A). | |||||||||||||
| CpduInputPhaseConfigCurrentUpperWarningThreshold | 1.3.6.1.4.1.318.1.1.32.3.2.1.7 | Unsigned32 | RW | ||||||||||
column · Unsigned32 · read-write · current User-defined upper non-critical (warning) input phase current alarm threshold in hundredths of Amps(A). | |||||||||||||
| CpduInputPhaseConfigVoltageLowerCriticalThreshold | 1.3.6.1.4.1.318.1.1.32.3.2.1.8 | Unsigned32 | RW | ||||||||||
column · Unsigned32 · read-write · current User-defined lower critical input phase voltage alarm threshold in Volts(V). | |||||||||||||
| CpduInputPhaseConfigVoltageLowerWarningThreshold | 1.3.6.1.4.1.318.1.1.32.3.2.1.9 | Unsigned32 | RW | ||||||||||
column · Unsigned32 · read-write · current User-defined lower non-critical (warning) input phase voltage alarm threshold in Volts(V). | |||||||||||||
| CpduInputPhaseConfigVoltageUpperCriticalThreshold | 1.3.6.1.4.1.318.1.1.32.3.2.1.10 | Unsigned32 | RW | ||||||||||
column · Unsigned32 · read-write · current User-defined upper critical input phase voltage alarm threshold in Volts(V). | |||||||||||||
| CpduInputPhaseConfigVoltageUpperWarningThreshold | 1.3.6.1.4.1.318.1.1.32.3.2.1.11 | Unsigned32 | RW | ||||||||||
column · Unsigned32 · read-write · current User-defined upper non-critical (warning) input phase voltage alarm threshold in Volts(V). | |||||||||||||
| CpduInputPhaseConfigCurrentAlarmResetThreshold | 1.3.6.1.4.1.318.1.1.32.3.2.1.12 | Unsigned32 | RW | ||||||||||
column · Unsigned32 · read-write · current The hysteresis used for current alarm deassertions in hundredths of Amps(A). | |||||||||||||
| CpduInputPhaseConfigCurrentAlarmStateChangeDelay | 1.3.6.1.4.1.318.1.1.32.3.2.1.13 | Integer32 | RW | ||||||||||
column · Integer32 · read-write · current The delay measured in samples before a current state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported. | |||||||||||||
| CpduInputPhaseConfigCurrentEnabledThresholds | 1.3.6.1.4.1.318.1.1.32.3.2.1.14 | Bits | RW | ||||||||||
column · Bits · read-write · current A bit string indicating which current alarm thresholds are enabled.
| |||||||||||||
| CpduInputPhaseConfigVoltageAlarmResetThreshold | 1.3.6.1.4.1.318.1.1.32.3.2.1.15 | Unsigned32 | RW | ||||||||||
column · Unsigned32 · read-write · current The hysteresis used for voltage alarm deassertions in Volts(V). | |||||||||||||
| CpduInputPhaseConfigVoltageAlarmStateChangeDelay | 1.3.6.1.4.1.318.1.1.32.3.2.1.16 | Integer32 | RW | ||||||||||
column · Integer32 · read-write · current The delay measured in samples before a voltage state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported. | |||||||||||||
| CpduInputPhaseConfigVoltageEnabledThresholds | 1.3.6.1.4.1.318.1.1.32.3.2.1.17 | Bits | RW | ||||||||||
column · Bits · read-write · current A bit string indicating which voltage alarm thresholds are enabled.
| |||||||||||||
| CpduInputPhaseConfigLineVoltageLowerCriticalThreshold | 1.3.6.1.4.1.318.1.1.32.3.2.1.18 | Unsigned32 | RW | ||||||||||
column · Unsigned32 · read-write · current User-defined lower critical line voltage alarm threshold in Volts(V). Supported only on PDU Phase in case of Y connection. | |||||||||||||
| CpduInputPhaseConfigLineVoltageLowerWarningThreshold | 1.3.6.1.4.1.318.1.1.32.3.2.1.19 | Unsigned32 | RW | ||||||||||
column · Unsigned32 · read-write · current User-defined lower non-critical (warning) line voltage alarm threshold in Volts(V). Supported only on PDU Phase in case of Y connection. | |||||||||||||
| CpduInputPhaseConfigLineVoltageUpperCriticalThreshold | 1.3.6.1.4.1.318.1.1.32.3.2.1.20 | Unsigned32 | RW | ||||||||||
column · Unsigned32 · read-write · current User-defined upper critical line voltage alarm threshold in Volts(V). Supported only on PDU Phase in case of Y connection. | |||||||||||||
| CpduInputPhaseConfigLineVoltageUpperWarningThreshold | 1.3.6.1.4.1.318.1.1.32.3.2.1.21 | Unsigned32 | RW | ||||||||||
column · Unsigned32 · read-write · current User-defined upper non-critical (warning) line voltage alarm threshold in Volts(V). Supported only on PDU Phase in case of Y connection. | |||||||||||||
| CpduInputPhaseConfigLineVoltageAlarmResetThreshold | 1.3.6.1.4.1.318.1.1.32.3.2.1.22 | Unsigned32 | RW | ||||||||||
column · Unsigned32 · read-write · current The hysteresis used for line voltage alarm deassertions in Volts(V). Supported only on PDU Phase in case of Y connection. | |||||||||||||
| CpduInputPhaseConfigLineVoltageAlarmStateChangeDelay | 1.3.6.1.4.1.318.1.1.32.3.2.1.23 | Integer32 | RW | ||||||||||
column · Integer32 · read-write · current The delay measured in samples before a line voltage state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported. Supported only on PDU Phase in case of Y connection. | |||||||||||||
| CpduInputPhaseConfigLineVoltageEnabledThresholds | 1.3.6.1.4.1.318.1.1.32.3.2.1.24 | Bits | RW | ||||||||||
column · Bits · read-write · current A bit string indicating which line voltage alarm thresholds are enabled. Supported only on PDU Phase in case of Y connection.
| |||||||||||||
| TpduInputPhasePropertiesTable | 1.3.6.1.4.1.318.1.1.32.3.3 | NA | |||||||||||
table · not-accessible · current A table of PDU Input Phase properties | |||||||||||||
| RpduInputPhasePropertiesEntry | 1.3.6.1.4.1.318.1.1.32.3.3.1 | NA | |||||||||||
row · not-accessible · current An input phase properties entry containing objects for a particular input phase. | |||||||||||||
| CpduInputPhasePropertiesIndex | 1.3.6.1.4.1.318.1.1.32.3.3.1.1 | Integer32 (1..256) | NA | ||||||||||
column · Integer32 (1..256) · not-accessible · current The index of the PDU Input Phase status entry | |||||||||||||
| CpduInputPhasePropertiesCount | 1.3.6.1.4.1.318.1.1.32.3.3.1.2 | Integer32 (1..256) | RO | ||||||||||
column · Integer32 (1..256) · read-only · current The numeric Input Phase ID | |||||||||||||
| TpduInputPhaseStatusTable | 1.3.6.1.4.1.318.1.1.32.3.4 | NA | |||||||||||
table · not-accessible · current A table of PDU Input Phase status data | |||||||||||||
| RpduInputPhaseStatusEntry | 1.3.6.1.4.1.318.1.1.32.3.4.1 | NA | |||||||||||
row · not-accessible · current An input phase status entry containing objects for a particular input phase. | |||||||||||||
| CpduInputPhaseStatusIndex | 1.3.6.1.4.1.318.1.1.32.3.4.1.1 | Integer32 (1..256) | NA | ||||||||||
column · Integer32 (1..256) · not-accessible · current The index of the PDU Input Phase status entry | |||||||||||||
| CpduInputPhaseStatusCount | 1.3.6.1.4.1.318.1.1.32.3.4.1.2 | Integer32 (1..256) | RO | ||||||||||
column · Integer32 (1..256) · read-only · current The numeric Input Phase ID | |||||||||||||
| CpduInputPhaseStatusCurrentState | 1.3.6.1.4.1.318.1.1.32.3.4.1.3 | INTEGER | RO | ||||||||||
column · INTEGER · read-only · current Indicates the present current status of the PDU Phase in case of Y connection or PDU Line in case of Delta conneciton.
| |||||||||||||
| CpduInputPhaseStatusVoltageState | 1.3.6.1.4.1.318.1.1.32.3.4.1.4 | INTEGER | RO | ||||||||||
column · INTEGER · read-only · current Indicates the present voltage status of the PDU Input Phase being queried
| |||||||||||||
| CpduInputPhaseStatusCurrent | 1.3.6.1.4.1.318.1.1.32.3.4.1.5 | Integer32 | RO | ||||||||||
column · Integer32 · read-only · current Returns the current draw, in hundredths of Amps(A) | |||||||||||||
| CpduInputPhaseStatusVoltage | 1.3.6.1.4.1.318.1.1.32.3.4.1.6 | Integer32 | RO | ||||||||||
column · Integer32 · read-only · current Returns the voltage, in Volts(V) | |||||||||||||
| CpduInputPhaseStatusActivePower | 1.3.6.1.4.1.318.1.1.32.3.4.1.7 | Integer32 | RO | ||||||||||
column · Integer32 · read-only · current Returns power consumption, in Watts(W) | |||||||||||||
| CpduInputPhaseStatusApparentPower | 1.3.6.1.4.1.318.1.1.32.3.4.1.8 | Integer32 | RO | ||||||||||
column · Integer32 · read-only · current Returns power consumption, in Volt-Amps(VA) | |||||||||||||
| CpduInputPhaseStatusPowerFactor | 1.3.6.1.4.1.318.1.1.32.3.4.1.9 | Integer32 | RO | ||||||||||
column · Integer32 · read-only · current Returns the ratio of active to apparent power of the PDU, in the hundreths of PowerFactor. | |||||||||||||
| CpduInputPhaseStatusLineVoltageState | 1.3.6.1.4.1.318.1.1.32.3.4.1.10 | INTEGER | RO | ||||||||||
column · INTEGER · read-only · current Indicates the present line voltage STATUS of the PDU Input Phase being queried. Supported only on PDU Phase in case of Y connection.
| |||||||||||||
| CpduInputPhaseStatusLineVoltage | 1.3.6.1.4.1.318.1.1.32.3.4.1.11 | Integer32 | RO | ||||||||||
column · Integer32 · read-only · current Returns the line voltage, in Volts(V). Supported only on PDU Phase in case of Y connection. | |||||||||||||
| NpduCircuitBreaker | 1.3.6.1.4.1.318.1.1.32.4 | ||||||||||||
| SpduCircuitBreakerTableSize | 1.3.6.1.4.1.318.1.1.32.4.1 | Integer32 (1..256) | RO | ||||||||||
scalar · Integer32 (1..256) · read-only · current The number of PDU Circuit Breakers | |||||||||||||
| TpduCircuitBreakerConfigTable | 1.3.6.1.4.1.318.1.1.32.4.2 | NA | |||||||||||
table · not-accessible · current A table of PDU Circuit Breaker configuration data | |||||||||||||
| RpduCircuitBreakerConfigEntry | 1.3.6.1.4.1.318.1.1.32.4.2.1 | NA | |||||||||||
row · not-accessible · current A circuit breaker configuration entry containing objects for a particular circuit breaker. | |||||||||||||
| CpduCircuitBreakerConfigIndex | 1.3.6.1.4.1.318.1.1.32.4.2.1.1 | Integer32 (1..256) | NA | ||||||||||
column · Integer32 (1..256) · not-accessible · current The index of the PDU Circuit Breaker configuration table entry | |||||||||||||
| CpduCircuitBreakerConfigCount | 1.3.6.1.4.1.318.1.1.32.4.2.1.2 | Integer32 (0..255) | RO | ||||||||||
column · Integer32 (0..255) · read-only · current The number of circuit breakers on the PDU | |||||||||||||
| CpduCircuitBreakerName | 1.3.6.1.4.1.318.1.1.32.4.2.1.3 | DisplayString | RW | ||||||||||
column · DisplayString · read-write · current The label of the circuit breaker | |||||||||||||
| CpduCircuitBreakerConfigOverloadRestriction | 1.3.6.1.4.1.318.1.1.32.4.2.1.4 | INTEGER | RW | ||||||||||
column · INTEGER · read-write · current This OID controls the behavior of a Switched PDU Circuit Breaker when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will always allow the outlets on the corresponding Circuit Breaker to turn on. Setting this OID to restrictOnUpperWarning (2) will not allow outlets on the corresponding Circuit Breaker to turn on if the pduCircuitBreakerConfigUpperWarningThreshold OID is exceeded. Setting this OID to restrictOnUpperCritical (3) will not allow outlets on the corresponding Circuit Breaker to turn on if the pduCircuitBreakerConfigUpperCriticalThreshold OID is exceeded. Models that do not support this feature will respond to this OID with a value of notSupported (4). Attempts to set this OID in these models will fail.
| |||||||||||||
| CpduCircuitBreakerConfigLowerCriticalThreshold | 1.3.6.1.4.1.318.1.1.32.4.2.1.5 | Unsigned32 | RW | ||||||||||
column · Unsigned32 · read-write · current User-defined lower critical circuit breaker current alarm threshold in hundredths of Amps(A). | |||||||||||||
| CpduCircuitBreakerConfigLowerWarningThreshold | 1.3.6.1.4.1.318.1.1.32.4.2.1.6 | Unsigned32 | RW | ||||||||||
column · Unsigned32 · read-write · current User-defined lower non-critical (warning) circuit breaker current alarm threshold in hundredths of Amps(A). | |||||||||||||
| CpduCircuitBreakerConfigUpperCriticalThreshold | 1.3.6.1.4.1.318.1.1.32.4.2.1.7 | Unsigned32 | RW | ||||||||||
column · Unsigned32 · read-write · current User-defined upper critical circuit breaker current alarm threshold in hundredths of Amps(A). | |||||||||||||
| CpduCircuitBreakerConfigUpperWarningThreshold | 1.3.6.1.4.1.318.1.1.32.4.2.1.8 | Unsigned32 | RW | ||||||||||
column · Unsigned32 · read-write · current User-defined upper non-critical (warning) circuit breaker current alarm threshold in hundredths of Amps(A). | |||||||||||||
| CpduCircuitBreakerConfigAlarmResetThreshold | 1.3.6.1.4.1.318.1.1.32.4.2.1.9 | Unsigned32 | RW | ||||||||||
column · Unsigned32 · read-write · current The hysteresis used for deassertions in hundredths of Amps(A). | |||||||||||||
| CpduCircuitBreakerConfigAlarmStateChangeDelay | 1.3.6.1.4.1.318.1.1.32.4.2.1.10 | Unsigned32 | RW | ||||||||||
column · Unsigned32 · read-write · current The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported. | |||||||||||||
| CpduCircuitBreakerConfigEnabledThresholds | 1.3.6.1.4.1.318.1.1.32.4.2.1.11 | Bits | RW | ||||||||||
column · Bits · read-write · current A bit string indicating which alarm thresholds are enabled.
| |||||||||||||
| TpduCircuitBreakerPropertiesTable | 1.3.6.1.4.1.318.1.1.32.4.3 | NA | |||||||||||
table · not-accessible · current A table of PDU circuit breaker properties | |||||||||||||
| RpduCircuitBreakerPropertiesEntry | 1.3.6.1.4.1.318.1.1.32.4.3.1 | NA | |||||||||||
row · not-accessible · current A circuit breaker properties entry containing objects for a particular circuit breaker. | |||||||||||||
| CpduCircuitBreakerPropertiesIndex | 1.3.6.1.4.1.318.1.1.32.4.3.1.1 | Integer32 (1..256) | NA | ||||||||||
column · Integer32 (1..256) · not-accessible · current The index of the PDU Circuit Breaker properties table entry | |||||||||||||
| CpduCircuitBreakerPropertiesCount | 1.3.6.1.4.1.318.1.1.32.4.3.1.2 | Integer32 (0..255) | RO | ||||||||||
column · Integer32 (0..255) · read-only · current The number of Circuit Breakers | |||||||||||||
| CpduCircuitBreakerPropertiesInputLayout | 1.3.6.1.4.1.318.1.1.32.4.3.1.3 | INTEGER | RO | ||||||||||
column · INTEGER · read-only · current This OID describes the outlet phase connections on the referenced bank as follows: seqPhase1ToNeutral(1) indicates that outlets attached to circuit breaker are connected from Phase 1 to Neutral. seqPhase2ToNeutral(2) indicates that outlets attached to circuit breaker are connected from Phase 2 to Neutral. seqPhase3ToNeutral(3) indicates that outlets attached to circuit breaker are connected from Phase 3 to Neutral. seqPhase1ToPhase2(4) indicates that outlets attached to circuit breaker are connected from Phase 1 to Phase2. seqPhase2ToPhase3(5) indicates that outlets attached to circuit breaker are connected from Phase 2 to Phase3. seqPhase3ToPhase1(6) indicates that outlets attached to circuit breaker are connected from Phase 3 to Phase1.
| |||||||||||||
| CpduCircuitBreakerPropertiesCurrentRating | 1.3.6.1.4.1.318.1.1.32.4.3.1.4 | Integer32 (0..255) | RO | ||||||||||
column · Integer32 (0..255) · read-only · current The number of Circuit Breakers | |||||||||||||
| TpduCircuitBreakerStatusTable | 1.3.6.1.4.1.318.1.1.32.4.4 | NA | |||||||||||
table · not-accessible · current A table of PDU circuit breaker status data | |||||||||||||
| RpduCircuitBreakerStatusEntry | 1.3.6.1.4.1.318.1.1.32.4.4.1 | NA | |||||||||||
row · not-accessible · current A circuit breaker status entry containing objects for a particular circuit breaker. | |||||||||||||
| CpduCircuitBreakerStatusIndex | 1.3.6.1.4.1.318.1.1.32.4.4.1.1 | Integer32 (1..256) | NA | ||||||||||
column · Integer32 (1..256) · not-accessible · current The index of the PDU Circuit Breaker status table entry | |||||||||||||
| CpduCircuitBreakerStatusCount | 1.3.6.1.4.1.318.1.1.32.4.4.1.2 | Integer32 (0..255) | RO | ||||||||||
column · Integer32 (0..255) · read-only · current The number of Circuit Breakers | |||||||||||||
| CpduCircuitBreakerLabel | 1.3.6.1.4.1.318.1.1.32.4.4.1.3 | DisplayString | RO | ||||||||||
column · DisplayString · read-only · current The label on the PDU identifying the circuit breaker | |||||||||||||
| CpduCircuitBreakerStatusLoadState | 1.3.6.1.4.1.318.1.1.32.4.4.1.4 | INTEGER | RO | ||||||||||
column · INTEGER · read-only · current Indicates the present load status of the PDU Circuit Breaker being queried
| |||||||||||||
| CpduCircuitBreakerStatusCurrent | 1.3.6.1.4.1.318.1.1.32.4.4.1.5 | Integer32 | RO | ||||||||||
column · Integer32 · read-only · current Returns the current draw, in hundredths of Amps(A), of the load on the PDU Circuit Breaker being queried. | |||||||||||||
| CpduCircuitBreakerStatusPowerFactor | 1.3.6.1.4.1.318.1.1.32.4.4.1.6 | Integer32 | RO | ||||||||||
column · Integer32 · read-only · current Returns the ratio of active to apparent power of the Circuit Breaker, in the hundreths of PowerFactor. | |||||||||||||
| NpduOutlet | 1.3.6.1.4.1.318.1.1.32.5 | ||||||||||||
| SpduOutletSwitchedTableSize | 1.3.6.1.4.1.318.1.1.32.5.1 | Integer32 (1..256) | RO | ||||||||||
scalar · Integer32 (1..256) · read-only · current The number of PDU Outlets | |||||||||||||
| TpduOutletSwitchedConfigTable | 1.3.6.1.4.1.318.1.1.32.5.2 | NA | |||||||||||
table · not-accessible · current A table of PDU Switched Outlet configuration data | |||||||||||||
| RpduOutletSwitchedConfigEntry | 1.3.6.1.4.1.318.1.1.32.5.2.1 | NA | |||||||||||
row · not-accessible · current An outlet configuration entry containing objects for a particular outlet. | |||||||||||||
| CpduOutletSwitchedConfigIndex | 1.3.6.1.4.1.318.1.1.32.5.2.1.1 | Integer32 (1..256) | NA | ||||||||||
column · Integer32 (1..256) · not-accessible · current The index of the PDU Switched Outlet configuration table entry | |||||||||||||
| CpduOutletSwitchedName | 1.3.6.1.4.1.318.1.1.32.5.2.1.2 | DisplayString | RW | ||||||||||
column · DisplayString · read-write · current The user-defined name for the Switched Outlet | |||||||||||||
| CpduOutletSwitchedStateOnStartup | 1.3.6.1.4.1.318.1.1.32.5.2.1.3 | INTEGER | RW | ||||||||||
column · INTEGER · read-write · current The outlet state on device startup; overrides the global value pduUnitConfigGlobalOutletStateOnStartup.
| |||||||||||||
| CpduOutletSwitchedConfigPowerOnTime | 1.3.6.1.4.1.318.1.1.32.5.2.1.4 | Integer32 | RW | ||||||||||
column · Integer32 · read-write · current The amount of delay, in seconds, between when power is provided to outlets the outlet and when this outlet starts providing power | |||||||||||||
| CpduOutletSwitchedConfigPowerOffTime | 1.3.6.1.4.1.318.1.1.32.5.2.1.5 | Integer32 | RW | ||||||||||
column · Integer32 · read-write · current The amount of time, in seconds, this outlet will delay powering off | |||||||||||||
| CpduOutletSwitchedConfigRebootDuration | 1.3.6.1.4.1.318.1.1.32.5.2.1.6 | Integer32 | RW | ||||||||||
column · Integer32 · read-write · current The amount of time, in seconds, this outlet will remain in powered off state before returning to power on state during a reboot action. | |||||||||||||
| TpduOutletSwitchedPropertiesTable | 1.3.6.1.4.1.318.1.1.32.5.3 | NA | |||||||||||
table · not-accessible · current A table of PDU Switched Outlet properties | |||||||||||||
| RpduOutletSwitchedPropertiesEntry | 1.3.6.1.4.1.318.1.1.32.5.3.1 | NA | |||||||||||
row · not-accessible · current An outlet properties entry containing objects for a particular outlet. | |||||||||||||
| CpduOutletSwitchedPropertiesIndex | 1.3.6.1.4.1.318.1.1.32.5.3.1.1 | Integer32 (1..256) | NA | ||||||||||
column · Integer32 (1..256) · not-accessible · current The index of the PDU Switched Outlet properties table entry | |||||||||||||
| CpduOutletSwitchedPropertiesNumber | 1.3.6.1.4.1.318.1.1.32.5.3.1.2 | Integer32 (1..256) | RO | ||||||||||
column · Integer32 (1..256) · read-only · current The numeric Switched Outlet ID | |||||||||||||
| CpduOutletSwitchedPropertiesName | 1.3.6.1.4.1.318.1.1.32.5.3.1.3 | DisplayString | RO | ||||||||||
column · DisplayString · read-only · current The user-defined switched outlet ID string | |||||||||||||
| CpduOutletSwitchedPropertiesInputPhaseLayout | 1.3.6.1.4.1.318.1.1.32.5.3.1.4 | INTEGER | RO | ||||||||||
column · INTEGER · read-only · current This OID describes the outlet phase connections on the referenced bank as follows: seqPhase1ToNeutral(1) indicates that outlets attached to Switched Outlet are connected from Phase 1 to Neutral. seqPhase2ToNeutral(2) indicates that outlets attached to Switched Outlet are connected from Phase 2 to Neutral. seqPhase3ToNeutral(3) indicates that outlets attached to Switched Outlet are connected from Phase 3 to Neutral. seqPhase1ToPhase2(4) indicates that outlets attached to Switched Outlet are connected from Phase 1 to Phase2. seqPhase2ToPhase3(5) indicates that outlets attached to Switched Outlet are connected from Phase 2 to Phase3. seqPhase3ToPhase1(6) indicates that outlets attached to Switched Outlet are connected from Phase 3 to Phase1.
| |||||||||||||
| CpduOutletSwitchedPropertiesCircuitBreaker | 1.3.6.1.4.1.318.1.1.32.5.3.1.5 | Integer32 (1..256) | RO | ||||||||||
column · Integer32 (1..256) · read-only · current The numeric Circuit Breaker ID | |||||||||||||
| CpduOutletSwitchedPropertiesCurrentRating | 1.3.6.1.4.1.318.1.1.32.5.3.1.6 | Integer32 (1..256) | RO | ||||||||||
column · Integer32 (1..256) · read-only · current The current rating of outlet in hundreths of ampere | |||||||||||||
| TpduOutletSwitchedStatusTable | 1.3.6.1.4.1.318.1.1.32.5.4 | NA | |||||||||||
table · not-accessible · current A table of PDU Switched Outlet status data | |||||||||||||
| RpduOutletSwitchedStatusEntry | 1.3.6.1.4.1.318.1.1.32.5.4.1 | NA | |||||||||||
row · not-accessible · current Status data from the PDU Switched Outlet being queried | |||||||||||||
| CpduOutletSwitchedStatusIndex | 1.3.6.1.4.1.318.1.1.32.5.4.1.1 | Integer32 (1..256) | NA | ||||||||||
column · Integer32 (1..256) · not-accessible · current The index of the PDU Switched Outlet status table entry | |||||||||||||
| CpduOutletSwitchedStatusNumber | 1.3.6.1.4.1.318.1.1.32.5.4.1.2 | Integer32 (1..256) | RO | 1 | |||||||||
| CpduOutletSwitchedStatusName | 1.3.6.1.4.1.318.1.1.32.5.4.1.3 | DisplayString | RO | Test Name | |||||||||
| CpduOutletSwitchedStatusState | 1.3.6.1.4.1.318.1.1.32.5.4.1.4 | INTEGER | RO | on(1) | |||||||||
| TpduOutletSwitchedControlTable | 1.3.6.1.4.1.318.1.1.32.5.5 | NA | |||||||||||
table · not-accessible · current A table of PDU Switched Outlet status data | |||||||||||||
| RpduOutletSwitchedControlEntry | 1.3.6.1.4.1.318.1.1.32.5.5.1 | NA | |||||||||||
row · not-accessible · current Status data from the PDU Switched Outlet being queried | |||||||||||||
| CpduOutletSwitchedControlIndex | 1.3.6.1.4.1.318.1.1.32.5.5.1.1 | Integer32 (1..256) | NA | ||||||||||
column · Integer32 (1..256) · not-accessible · current The index to the PDU switched outlet control data table entry | |||||||||||||
| CpduOutletSwitchedControlNumber | 1.3.6.1.4.1.318.1.1.32.5.5.1.2 | Integer32 (1..256) | RO | ||||||||||
column · Integer32 (1..256) · read-only · current The numeric Switched Outlet ID | |||||||||||||
| CpduOutletSwitchedControlName | 1.3.6.1.4.1.318.1.1.32.5.5.1.3 | DisplayString | RO | ||||||||||
column · DisplayString · read-only · current The user-defined switched outlet ID string | |||||||||||||
| CpduOutletSwitchedControlCommand | 1.3.6.1.4.1.318.1.1.32.5.5.1.4 | INTEGER | RW | ||||||||||
column · INTEGER · read-write · current Getting this variable will return the outlet state. If the outlet is on, the immediateOn (2) value will be returned. If the outlet is off, the immediateOff (1) value will be returned. If the state of the outlet cannot be determined, the outletUnknown (7) value will be returned. If the outletUnknown condition should occur, all devices powered by the PDU should be shut down. The PDU's power should then be cycled to clear this condition. Setting this variable to immediateOn (2) will immediately turn the outlet on. Setting this variable to immediateOff (1) will immediately turn the outlet off. Setting this variable to immediateReboot (5) will cause the Switched PDU to perform an immediateOff command, wait the pduOutletSwitchedConfigRebootDuration OID time, and then perform an immediateOn command. Setting this variable to delayedOn (4) will turn the outlet on after the pduOutletSwitchedConfigPowerOnTime OID time has elapsed. Setting this variable to delayedOff (3) will turn the outlet off after the pduOutletSwitchedConfigPowerOffTime OID time has elapsed. Setting this variable to delayedReboot (6) will cause the Switched PDU to perform a delayedOff command, wait the pduOutletSwitchedConfigRebootDuration OID time, and then perform a delayedOn command.
| |||||||||||||
| SpduOutletMeteredTableSize | 1.3.6.1.4.1.318.1.1.32.5.6 | Integer32 (1..256) | RO | ||||||||||
scalar · Integer32 (1..256) · read-only · current The number of PDU Outlets | |||||||||||||
| TpduOutletMeteredConfigTable | 1.3.6.1.4.1.318.1.1.32.5.7 | NA | |||||||||||
table · not-accessible · current A table of PDU Metered Outlet configuration data | |||||||||||||
| RpduOutletMeteredConfigEntry | 1.3.6.1.4.1.318.1.1.32.5.7.1 | NA | |||||||||||
row · not-accessible · current An outlet configuration entry containing objects for a particular outlet. | |||||||||||||
| CpduOutletMeteredConfigIndex | 1.3.6.1.4.1.318.1.1.32.5.7.1.1 | Integer32 (1..256) | NA | ||||||||||
column · Integer32 (1..256) · not-accessible · current The index of the PDU Metered Outlet configuration table entry | |||||||||||||
| CpduOutletMeteredName | 1.3.6.1.4.1.318.1.1.32.5.7.1.2 | DisplayString | RW | ||||||||||
column · DisplayString · read-write · current The user-defined name for the Metered Outlet | |||||||||||||
| CpduOutletMeteredConfigLowerCriticalThreshold | 1.3.6.1.4.1.318.1.1.32.5.7.1.3 | Unsigned32 | RW | ||||||||||
column · Unsigned32 · read-write · current User-defined lower critical outlet active power alarm threshold in Watts(W). | |||||||||||||
| CpduOutletMeteredConfigLowerWarningThreshold | 1.3.6.1.4.1.318.1.1.32.5.7.1.4 | Unsigned32 | RW | ||||||||||
column · Unsigned32 · read-write · current User-defined lower non-critical (warning) outlet active power alarm threshold in Watts(W). | |||||||||||||
| CpduOutletMeteredConfigUpperCriticalThreshold | 1.3.6.1.4.1.318.1.1.32.5.7.1.5 | Unsigned32 | RW | ||||||||||
column · Unsigned32 · read-write · current User-defined upper critical outlet active power alarm threshold in Watts(W). | |||||||||||||
| CpduOutletMeteredConfigUpperWarningThreshold | 1.3.6.1.4.1.318.1.1.32.5.7.1.6 | Unsigned32 | RW | ||||||||||
column · Unsigned32 · read-write · current User-defined upper non-critical (warning) outlet active power alarm threshold in Watts(W). | |||||||||||||
| CpduOutletMeteredConfigAlarmResetThreshold | 1.3.6.1.4.1.318.1.1.32.5.7.1.7 | Unsigned32 | RW | ||||||||||
column · Unsigned32 · read-write · current The hysteresis used for deassertions in Watts(W). | |||||||||||||
| CpduOutletMeteredConfigAlarmStateChangeDelay | 1.3.6.1.4.1.318.1.1.32.5.7.1.8 | Unsigned32 | RW | ||||||||||
column · Unsigned32 · read-write · current The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported. | |||||||||||||
| CpduOutletMeteredConfigEnabledThresholds | 1.3.6.1.4.1.318.1.1.32.5.7.1.9 | Bits | RW | ||||||||||
column · Bits · read-write · current A bit string indicating which alarm thresholds are enabled.
| |||||||||||||
| TpduOutletMeteredPropertiesTable | 1.3.6.1.4.1.318.1.1.32.5.8 | NA | |||||||||||
table · not-accessible · current A table of PDU Metered Outlet properties | |||||||||||||
| RpduOutletMeteredPropertiesEntry | 1.3.6.1.4.1.318.1.1.32.5.8.1 | NA | |||||||||||
row · not-accessible · current Configuration data from the PDU Metered Outlet being queried | |||||||||||||
| CpduOutletMeteredPropertiesIndex | 1.3.6.1.4.1.318.1.1.32.5.8.1.1 | Integer32 (1..256) | NA | ||||||||||
column · Integer32 (1..256) · not-accessible · current The index of the PDU Metered Outlet properties table entry | |||||||||||||
| CpduOutletMeteredPropertiesNumber | 1.3.6.1.4.1.318.1.1.32.5.8.1.2 | Integer32 (1..256) | RO | ||||||||||
column · Integer32 (1..256) · read-only · current The numeric Metered Outlet ID | |||||||||||||
| CpduOutletMeteredPropertiesName | 1.3.6.1.4.1.318.1.1.32.5.8.1.3 | DisplayString | RO | ||||||||||
column · DisplayString · read-only · current The user-defined Metered outlet ID string | |||||||||||||
| CpduOutletMeteredPropertiesInputPhaseLayout | 1.3.6.1.4.1.318.1.1.32.5.8.1.4 | INTEGER | RO | ||||||||||
column · INTEGER · read-only · current This OID describes the outlet phase connections on the referenced bank as follows: seqPhase1ToNeutral(1) indicates that outlets attached to Metered Outlet are connected from Phase 1 to Neutral. seqPhase2ToNeutral(2) indicates that outlets attached to Metered Outlet are connected from Phase 2 to Neutral. seqPhase3ToNeutral(3) indicates that outlets attached to Metered Outlet are connected from Phase 3 to Neutral. seqPhase1ToPhase2(4) indicates that outlets attached to Metered Outlet are connected from Phase 1 to Phase2. seqPhase2ToPhase3(5) indicates that outlets attached to Metered Outlet are connected from Phase 2 to Phase3. seqPhase3ToPhase1(6) indicates that outlets attached to Metered Outlet are connected from Phase 3 to Phase1.
| |||||||||||||
| CpduOutletMeteredPropertiesCircuitBreaker | 1.3.6.1.4.1.318.1.1.32.5.8.1.5 | Integer32 (1..256) | RO | ||||||||||
column · Integer32 (1..256) · read-only · current The numeric Circuit Breaker ID | |||||||||||||
| CpduOutletMeteredPropertiesPowerRating | 1.3.6.1.4.1.318.1.1.32.5.8.1.6 | Integer32 | RO | ||||||||||
column · Integer32 · read-only · current Maximum power rating of the PDU metered outlet | |||||||||||||
| CpduOutletMeteredPropertiesCurrentRating | 1.3.6.1.4.1.318.1.1.32.5.8.1.7 | Integer32 | RO | ||||||||||
column · Integer32 · read-only · current Metered outlet current rating in hundreths of ampere | |||||||||||||
| TpduOutletMeteredStatusTable | 1.3.6.1.4.1.318.1.1.32.5.9 | NA | |||||||||||
table · not-accessible · current A table of PDU Metered Outlet status data | |||||||||||||
| RpduOutletMeteredStatusEntry | 1.3.6.1.4.1.318.1.1.32.5.9.1 | NA | |||||||||||
row · not-accessible · current Status data from the PDU Metered Outlet being queried | |||||||||||||
| CpduOutletMeteredStatusIndex | 1.3.6.1.4.1.318.1.1.32.5.9.1.1 | Integer32 (1..256) | NA | ||||||||||
column · Integer32 (1..256) · not-accessible · current The index of the PDU Metered Outlet status table entry | |||||||||||||
| CpduOutletMeteredStatusNumber | 1.3.6.1.4.1.318.1.1.32.5.9.1.2 | Integer32 (1..256) | RO | 1 | |||||||||
| CpduOutletMeteredStatusName | 1.3.6.1.4.1.318.1.1.32.5.9.1.3 | DisplayString | RO | Test Name | |||||||||
| CpduOutletMeteredStatusLoadState | 1.3.6.1.4.1.318.1.1.32.5.9.1.4 | INTEGER | RO | normal(5) | |||||||||
column · INTEGER · read-only · current Returns the present load status of the PDU metered outlet being queried.
| |||||||||||||
| CpduOutletMeteredStatusCurrent | 1.3.6.1.4.1.318.1.1.32.5.9.1.5 | Integer32 | RO | 0 | |||||||||
| CpduOutletMeteredStatusActivePower | 1.3.6.1.4.1.318.1.1.32.5.9.1.6 | Integer32 | RO | 0 | |||||||||
| CpduOutletMeteredStatusPowerFactor | 1.3.6.1.4.1.318.1.1.32.5.9.1.7 | Integer32 | RO | 100 | |||||||||
| CpduOutletMeteredStatusPeakPower | 1.3.6.1.4.1.318.1.1.32.5.9.1.8 | Integer32 | RO | 190 | |||||||||
| CpduOutletMeteredStatusPeakPowerTimeStamp | 1.3.6.1.4.1.318.1.1.32.5.9.1.9 | DisplayString | RO | 2025/09/30 04:42:13 | |||||||||
column · DisplayString · read-only · current Indicates the date and time that this metered outlet's peak power consumption occurred | |||||||||||||
| CpduOutletMeteredStatusPeakPowerStartTime | 1.3.6.1.4.1.318.1.1.32.5.9.1.10 | DisplayString | RO | 2010/01/01 00:34:36 | |||||||||
| CpduOutletMeteredStatusResettableEnergy | 1.3.6.1.4.1.318.1.1.32.5.9.1.11 | Integer32 | RO | 573 | |||||||||
| NpduExternalSensor | 1.3.6.1.4.1.318.1.1.32.6 | ||||||||||||
| SpduExternalSensorTableSize | 1.3.6.1.4.1.318.1.1.32.6.1 | Integer32 (1..256) | RO | ||||||||||
scalar · Integer32 (1..256) · read-only · current The total number of External Sensors | |||||||||||||
| TpduExternalSensorNamePlateTable | 1.3.6.1.4.1.318.1.1.32.6.2 | NA | |||||||||||
table · not-accessible · current A table of PDU ExternalSensorNamePlate data | |||||||||||||
| RpduExternalSensorNamePlateEntry | 1.3.6.1.4.1.318.1.1.32.6.2.1 | NA | |||||||||||
row · not-accessible · current External Sensor Name Plate data from the external sensor being queried. The number of entries equals the value of pduExternalSensorNamePlateTableSize. | |||||||||||||
| CpduExternalSensorNamePlateIndex | 1.3.6.1.4.1.318.1.1.32.6.2.1.1 | Integer32 (0..255) | NA | ||||||||||
column · Integer32 (0..255) · not-accessible · current The index of the PDU External Sensor status table entry | |||||||||||||
| CpduExternalSensorNamePlateName | 1.3.6.1.4.1.318.1.1.32.6.2.1.2 | DisplayString | RW | ||||||||||
column · DisplayString · read-write · current A user-defined string identifying the external sensor | |||||||||||||
| CpduExternalSensorNamePlateDescription | 1.3.6.1.4.1.318.1.1.32.6.2.1.3 | DisplayString | RW | ||||||||||
column · DisplayString · read-write · current A user-defined description of the external sensor | |||||||||||||
| CpduExternalSensorNamePlateLocation | 1.3.6.1.4.1.318.1.1.32.6.2.1.4 | DisplayString | RW | ||||||||||
column · DisplayString · read-write · current A user-defined string identifying the location of the PDU | |||||||||||||
| CpduExternalSensorNamePlateSerialNumber | 1.3.6.1.4.1.318.1.1.32.6.2.1.5 | DisplayString | RO | deprecated | |||||||||
column · DisplayString · read-only · deprecated The serial code of the external sensor being queried. This OID is used to show the product code of the sensor. Additionally, similar information is shown in the OID 'pduExternalSensorNamePlateProductCode' | |||||||||||||
| CpduExternalSensorNamePlateType | 1.3.6.1.4.1.318.1.1.32.6.2.1.6 | INTEGER | RO | ||||||||||
column · INTEGER · read-only · current The type of external sensor.
| |||||||||||||
| CpduExternalSensorNamePlateUnits | 1.3.6.1.4.1.318.1.1.32.6.2.1.7 | INTEGER | RO | ||||||||||
column · INTEGER · read-only · current The base units the external sensor is measured in. This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors.
| |||||||||||||
| CpduExternalSensorNamePlateIdentifier | 1.3.6.1.4.1.318.1.1.32.6.2.1.8 | Integer32 | RO | ||||||||||
column · Integer32 · read-only · current Unique identifier of the external sensor. | |||||||||||||
| CpduExternalSensorNamePlateProductCode | 1.3.6.1.4.1.318.1.1.32.6.2.1.9 | DisplayString | RO | ||||||||||
column · DisplayString · read-only · current The product code of the external sensor being queried | |||||||||||||
| TpduExternalSensorConfigTable | 1.3.6.1.4.1.318.1.1.32.6.3 | NA | |||||||||||
table · not-accessible · current A table of PDU External Sensor configuration data | |||||||||||||
| RpduExternalSensorConfigEntry | 1.3.6.1.4.1.318.1.1.32.6.3.1 | NA | |||||||||||
row · not-accessible · current Configuration data from the PDU External Sensor being queried | |||||||||||||
| CpduExternalSensorConfigIndex | 1.3.6.1.4.1.318.1.1.32.6.3.1.1 | Integer32 (0..255) | NA | ||||||||||
column · Integer32 (0..255) · not-accessible · current The index of the PDU External Sensor configuration table entry | |||||||||||||
| CpduExternalSensorConfigLowerCriticalThreshold | 1.3.6.1.4.1.318.1.1.32.6.3.1.2 | Unsigned32 | RW | ||||||||||
column · Unsigned32 · read-write · current User-defined lower critical alarm threshold in pduExternalSensorNamePlateUnits. | |||||||||||||
| CpduExternalSensorConfigLowerWarningThreshold | 1.3.6.1.4.1.318.1.1.32.6.3.1.3 | Unsigned32 | RW | ||||||||||
column · Unsigned32 · read-write · current User-defined lower non-critical (warning) alarm threshold in pduExternalSensorNamePlateUnits. | |||||||||||||
| CpduExternalSensorConfigUpperCriticalThreshold | 1.3.6.1.4.1.318.1.1.32.6.3.1.4 | Unsigned32 | RW | ||||||||||
column · Unsigned32 · read-write · current User-defined upper critical alarm threshold in pduExternalSensorNamePlateUnits. | |||||||||||||
| CpduExternalSensorConfigUpperWarningThreshold | 1.3.6.1.4.1.318.1.1.32.6.3.1.5 | Unsigned32 | RW | ||||||||||
column · Unsigned32 · read-write · current User-defined upper non-critical (warning) alarm threshold in pduExternalSensorNamePlateUnits. | |||||||||||||
| CpduExternalSensorConfigEnabledThresholds | 1.3.6.1.4.1.318.1.1.32.6.3.1.6 | Bits | RW | ||||||||||
column · Bits · read-write · current A bit string indicating which alarm thresholds are enabled.
| |||||||||||||
| CpduExternalSensorConfigAlarmState | 1.3.6.1.4.1.318.1.1.32.6.3.1.7 | INTEGER | RW | ||||||||||
column · INTEGER · read-write · current User defined alarm state of external sensor
| |||||||||||||
| CpduExternalSensorConfigAlarmResetThreshold | 1.3.6.1.4.1.318.1.1.32.6.3.1.8 | Unsigned32 | RW | ||||||||||
column · Unsigned32 · read-write · current The hysteresis used for deassertions. | |||||||||||||
| CpduExternalSensorConfigAlarmStateChangeDelay | 1.3.6.1.4.1.318.1.1.32.6.3.1.9 | Unsigned32 | RW | ||||||||||
column · Unsigned32 · read-write · current The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported. | |||||||||||||
| TpduExternalSensorStatusTable | 1.3.6.1.4.1.318.1.1.32.6.4 | NA | |||||||||||
table · not-accessible · current A table of PDU External Sensor status data | |||||||||||||
| RpduExternalSensorStatusEntry | 1.3.6.1.4.1.318.1.1.32.6.4.1 | NA | |||||||||||
row · not-accessible · current Status data from the PDU External Sensor being queried | |||||||||||||
| CpduExternalSensorStatusIndex | 1.3.6.1.4.1.318.1.1.32.6.4.1.1 | Integer32 (0..255) | NA | ||||||||||
column · Integer32 (0..255) · not-accessible · current The index of the PDU External Sensor status table entry | |||||||||||||
| CpduExternalSensorStatusName | 1.3.6.1.4.1.318.1.1.32.6.4.1.2 | DisplayString | RO | ||||||||||
column · DisplayString · read-only · current The user-defined name for the External Sensor | |||||||||||||
| CpduExternalSensorStatusCommStatus | 1.3.6.1.4.1.318.1.1.32.6.4.1.3 | INTEGER | RO | ||||||||||
column · INTEGER · read-only · current The communications status of the sensor
| |||||||||||||
| CpduExternalSensorStatusState | 1.3.6.1.4.1.318.1.1.32.6.4.1.4 | INTEGER | RO | ||||||||||
column · INTEGER · read-only · current This OID reports the current state of the sensor. A notPresent (0) response indicates that no sensor is attached. An alarmed (1) response indicates that the sensor is present and its measured reading indicates alarmed. A normal (2) response indicates that the sensor is present and its measured reading lies within all thresholds. A belowLowerCritical (3) response indicates that the sensor is present and its measured reading lies below the lower critical threshold. A belowLowerWarning (4) response indicates that the sensor is present and its measured reading lies below the lower warning threshold. An aboveUpperWarning (5) response indicates that the sensor is present and its measured reading lies above the upper warning threshold. An aboveUpperCritical (6) response indicates that the sensor is present and its measured reading lies above the upper critical threshold.
| |||||||||||||
| CpduExternalSensorStatusValue | 1.3.6.1.4.1.318.1.1.32.6.4.1.5 | Integer32 | RO | ||||||||||
column · Integer32 · read-only · current Sensor reading in pduExternalSensorConfigUnits value. | |||||||||||||
| CpduExternalSensorStatusTimeStamp | 1.3.6.1.4.1.318.1.1.32.6.4.1.6 | DisplayString | RO | ||||||||||
column · DisplayString · read-only · current The sensor reading timestamp. | |||||||||||||
| CpduExternalSensorStatusHighPrecisionValue | 1.3.6.1.4.1.318.1.1.32.6.4.1.7 | Integer32 | RO | ||||||||||
column · Integer32 · read-only · current Temperature sensor reading in tenths of pduExternalSensorConfigUnits value. This OID is applied to temperature sensor only | |||||||||||||
| CpduExternalSensorSTATUSAisle | 1.3.6.1.4.1.318.1.1.32.6.4.1.8 | INTEGER | RO | ||||||||||
column · INTEGER · read-only · current Indicates whether the external sensor is in a hot or cold aisle
| |||||||||||||
| NpduSmartCabinet | 1.3.6.1.4.1.318.1.1.32.7 | ||||||||||||
| SpduUnitSmartCabinetTableSize | 1.3.6.1.4.1.318.1.1.32.7.1 | Integer32 (0..255) | RO | ||||||||||
scalar · Integer32 (0..255) · read-only · current The total number of Smart Cabinet Configuration | |||||||||||||
| TpduUnitSmartCabinetTable | 1.3.6.1.4.1.318.1.1.32.7.2 | NA | |||||||||||
table · not-accessible · current A table of Smart Cabinet information | |||||||||||||
| RpduUnitSmartCabinetEntry | 1.3.6.1.4.1.318.1.1.32.7.2.1 | NA | |||||||||||
| CpduUnitSmartCabinetIndex | 1.3.6.1.4.1.318.1.1.32.7.2.1.1 | Integer32 (1..256) | NA | ||||||||||
column · Integer32 (1..256) · not-accessible · current The index of the PDU Smart Cabinet table entry | |||||||||||||
| CpduUnitSmartCabinetCardUserName | 1.3.6.1.4.1.318.1.1.32.7.2.1.2 | DisplayString | RO | ||||||||||
column · DisplayString · read-only · current User name of ID card | |||||||||||||
| CpduUnitSmartCabinetCardID | 1.3.6.1.4.1.318.1.1.32.7.2.1.3 | Integer32 | RO | ||||||||||
column · Integer32 · read-only · current Card ID. | |||||||||||||
| CpduUnitSmartCabinetTimestamp | 1.3.6.1.4.1.318.1.1.32.7.2.1.4 | DisplayString | RO | ||||||||||
column · DisplayString · read-only · current Indicates the date and time of information update | |||||||||||||
| CpduUnitSmartCabinetDoor | 1.3.6.1.4.1.318.1.1.32.7.2.1.5 | INTEGER | RO | ||||||||||
column · INTEGER · read-only · current Aisle of Smart Cabinet.
| |||||||||||||
| NpduUnitSmartCabinetControl | 1.3.6.1.4.1.318.1.1.32.7.3 | ||||||||||||
| SpduUnitSmartCabinetControlUserName | 1.3.6.1.4.1.318.1.1.32.7.3.1 | DisplayString | RW | ||||||||||
scalar · DisplayString · read-write · current User name of ID card | |||||||||||||
| SpduUnitSmartCabinetControlCardID | 1.3.6.1.4.1.318.1.1.32.7.3.2 | Integer32 | RW | ||||||||||
scalar · Integer32 · read-write · current Card ID. | |||||||||||||
| SpduUnitSmartCabinetControlTimestamp | 1.3.6.1.4.1.318.1.1.32.7.3.3 | DisplayString | RW | ||||||||||
scalar · DisplayString · read-write · current Indicates the date and time of information update | |||||||||||||
| SpduUnitSmartCabinetControlDoor | 1.3.6.1.4.1.318.1.1.32.7.3.4 | INTEGER | RW | ||||||||||
scalar · INTEGER · read-write · current Aisle of Smart Cabinet.
| |||||||||||||
| SpduUnitSmartCabinetCardIDEdit | 1.3.6.1.4.1.318.1.1.32.7.3.5 | INTEGER | RW | ||||||||||
scalar · INTEGER · read-write · current Smart Cabinet edit CardID
| |||||||||||||
| SpduUnitSmartCabinetColdAisleLockStatus | 1.3.6.1.4.1.318.1.1.32.7.3.6 | INTEGER | RW | ||||||||||
scalar · INTEGER · read-write · current Smart Cabinet ColdAisle lock state
| |||||||||||||
| SpduUnitSmartCabinetHotAisleLockStatus | 1.3.6.1.4.1.318.1.1.32.7.3.7 | INTEGER | RW | ||||||||||
scalar · INTEGER · read-write · current Smart Cabinet HotAisle lock state
| |||||||||||||
| TpduUnitSmartCabinetLockStateTable | 1.3.6.1.4.1.318.1.1.32.7.4 | NA | |||||||||||
table · not-accessible · current A table of Smart Cabinet aisle state control | |||||||||||||
| RpduUnitSmartCabinetLockStateEntry | 1.3.6.1.4.1.318.1.1.32.7.4.1 | NA | |||||||||||
row · not-accessible · current Information of Smart Cabinet Lock State | |||||||||||||
| CpduUnitSmartCabinetLockStateIndex | 1.3.6.1.4.1.318.1.1.32.7.4.1.1 | Integer32 (1..256) | NA | ||||||||||
column · Integer32 (1..256) · not-accessible · current The index of the PDU Smart Cabinet table entry | |||||||||||||
| CpduUnitSmartCabinetColdAisleLockState | 1.3.6.1.4.1.318.1.1.32.7.4.1.2 | INTEGER | RW | ||||||||||
column · INTEGER · read-write · current Smart Cabinet ColdAisle lock state
| |||||||||||||
| CpduUnitSmartCabinetHotAisleLockState | 1.3.6.1.4.1.318.1.1.32.7.4.1.3 | INTEGER | RW | ||||||||||
column · INTEGER · read-write · current Smart Cabinet HotAisle lock state
| |||||||||||||
| CpduUnitSmartCabinetColdAisleLockLabel | 1.3.6.1.4.1.318.1.1.32.7.4.1.4 | DisplayString | RO | ||||||||||
column · DisplayString · read-only · current Label of cold aisle smartcabinet | |||||||||||||
| CpduUnitSmartCabinetHotAisleLockLabel | 1.3.6.1.4.1.318.1.1.32.7.4.1.5 | DisplayString | RO | ||||||||||
column · DisplayString · read-only · current Label of hot aisle smartcabinet | |||||||||||||
| NpduTraps | 1.3.6.1.4.1.318.1.1.32.8 | ||||||||||||
| !trapCritical | 1.3.6.1.4.1.318.1.1.32.8.1 | ||||||||||||
notification · current A critical alarm has occurred.
| |||||||||||||
| TtrapsInfoTable | 1.3.6.1.4.1.318.1.1.32.8.1.1 | NA | |||||||||||
table · not-accessible · current A list of Trap Information entries. The number of entries are given by the value of pduUnitTableSize. | |||||||||||||
| RtrapsInfoEntry | 1.3.6.1.4.1.318.1.1.32.8.1.1.1 | NA | |||||||||||
| CtrapsInfoIndex | 1.3.6.1.4.1.318.1.1.32.8.1.1.1.1 | Integer32 (1..256) | NA | ||||||||||
column · Integer32 (1..256) · not-accessible · current The index of the traps table entry | |||||||||||||
| CuserName | 1.3.6.1.4.1.318.1.1.32.8.1.1.1.2 | DisplayString | RO | ||||||||||
column · DisplayString · read-only · current The user currently logged in. | |||||||||||||
| CuserUpdated | 1.3.6.1.4.1.318.1.1.32.8.1.1.1.3 | DisplayString | RO | ||||||||||
column · DisplayString · read-only · current The user added, deleted, or modified. | |||||||||||||
| CfirmwareVersion | 1.3.6.1.4.1.318.1.1.32.8.1.1.1.4 | DisplayString | RO | ||||||||||
column · DisplayString · read-only · current The version of Firmware. | |||||||||||||
| CroleUpdated | 1.3.6.1.4.1.318.1.1.32.8.1.1.1.5 | DisplayString | RO | ||||||||||
column · DisplayString · read-only · current The role added, deleted, or modified. | |||||||||||||
| CsmtpRecipients | 1.3.6.1.4.1.318.1.1.32.8.1.1.1.6 | DisplayString | RO | ||||||||||
column · DisplayString · read-only · current Comma separated list of SMTP recipients | |||||||||||||
| CsmtpServer | 1.3.6.1.4.1.318.1.1.32.8.1.1.1.7 | DisplayString | RO | ||||||||||
column · DisplayString · read-only · current The IP address/host name of the SMTP server | |||||||||||||
| SpduIndex | 1.3.6.1.4.1.318.1.1.32.8.1.2 | Integer32 | AN | ||||||||||
scalar · Integer32 · accessible-for-notify · current A unique value for PDU. Its value ranges between 1 and the value of PDU count | |||||||||||||
| SexternalSensorIndex | 1.3.6.1.4.1.318.1.1.32.8.1.3 | Integer32 | AN | ||||||||||
scalar · Integer32 · accessible-for-notify · current A unique value for each sensor. Its value ranges between 1 and the value of external sensor count. | |||||||||||||
| SserverPing | 1.3.6.1.4.1.318.1.1.32.8.1.4 | INTEGER | AN | ||||||||||
scalar · INTEGER · accessible-for-notify · current Whether server ping has been enabled or disabled and whether the server is reachable or not reachable
| |||||||||||||
| SusbDevice | 1.3.6.1.4.1.318.1.1.32.8.1.5 | INTEGER | AN | ||||||||||
scalar · INTEGER · accessible-for-notify · current Whether a USB device has been connected or disconnected
| |||||||||||||
| SerrorDescription | 1.3.6.1.4.1.318.1.1.32.8.1.6 | DisplayString | AN | ||||||||||
scalar · DisplayString · accessible-for-notify · current Description of the Error | |||||||||||||
| Scascading | 1.3.6.1.4.1.318.1.1.32.8.1.7 | INTEGER | AN | ||||||||||
scalar · INTEGER · accessible-for-notify · current Whether a cascading member has been connected or disconnected
| |||||||||||||
| SsystemCommunication | 1.3.6.1.4.1.318.1.1.32.8.1.8 | INTEGER | AN | ||||||||||
scalar · INTEGER · accessible-for-notify · current Whether the Network management card has lost contact with cascading member.
| |||||||||||||
| StrapCode | 1.3.6.1.4.1.318.1.1.32.8.1.9 | INTEGER | RO | mandatory | |||||||||
scalar · INTEGER · read-only · mandatory A number identifying the event for the trap that was sent. Mapped unique trap code per unique event to be used by ISEE's decoder ring. | |||||||||||||
| StrapDescription | 1.3.6.1.4.1.318.1.1.32.8.1.10 | DisplayString (SIZE (0..255)) | RO | mandatory | |||||||||
scalar · DisplayString (SIZE (0..255)) · read-only · mandatory A string identifying the event for that last trap that was sent. | |||||||||||||
| NtrapsInfo | 1.3.6.1.4.1.318.1.1.32.8.1 | ||||||||||||
| !trapWarning | 1.3.6.1.4.1.318.1.1.32.8.2 | ||||||||||||
notification · current A warning alarm has occurred.
| |||||||||||||
| !trapInformation | 1.3.6.1.4.1.318.1.1.32.8.3 | ||||||||||||
notification · current An informational alarm has occurred.
| |||||||||||||
| !trapCleared | 1.3.6.1.4.1.318.1.1.32.8.4 | ||||||||||||
notification · current An alarm has cleared.
| |||||||||||||
| !trapTest | 1.3.6.1.4.1.318.1.1.32.8.5 | ||||||||||||
notification · current Test trap sent to a trap receiver to check proper reception of traps
| |||||||||||||
| NpduEhandle | 1.3.6.1.4.1.318.1.1.32.9 | ||||||||||||
| TpduEhandleTable | 1.3.6.1.4.1.318.1.1.32.9.1 | NA | mandatory | ||||||||||
table · not-accessible · mandatory A list of contact sensors. The number of entries are given by number of pdu and pduEhandleCount. | |||||||||||||
| RpduEhandleEntry | 1.3.6.1.4.1.318.1.1.32.9.1.1 | NA | mandatory | ||||||||||
| CpduEhandleIndex | 1.3.6.1.4.1.318.1.1.32.9.1.1.1 | INTEGER (1..2) | RO | mandatory | |||||||||
column · INTEGER (1..2) · read-only · mandatory The index of the PDU HID table entry | |||||||||||||
| CpduEhandleAisle | 1.3.6.1.4.1.318.1.1.32.9.1.1.2 | INTEGER | RO | mandatory | |||||||||
column · INTEGER · read-only · mandatory Aisle of HID handle.
| |||||||||||||
| CpduEhandleHandleOperation | 1.3.6.1.4.1.318.1.1.32.9.1.1.3 | INTEGER | RW | mandatory | |||||||||
column · INTEGER · read-write · mandatory HID handle control opterations
| |||||||||||||
| CpduEhandleFwVer | 1.3.6.1.4.1.318.1.1.32.9.1.1.4 | DisplayString | RO | mandatory | |||||||||
column · DisplayString · read-only · mandatory The firmware revision level of the HID | |||||||||||||
| CpduEhandleMechanicalLock | 1.3.6.1.4.1.318.1.1.32.9.1.1.5 | INTEGER | RO | mandatory | |||||||||
column · INTEGER · read-only · mandatory HID Mechanical opterations
| |||||||||||||
| CpduEhandleSerial | 1.3.6.1.4.1.318.1.1.32.9.1.1.6 | DisplayString | RO | mandatory | |||||||||
column · DisplayString · read-only · mandatory The Serial Number of the HID | |||||||||||||
| CpduEhandleHwVer | 1.3.6.1.4.1.318.1.1.32.9.1.1.7 | DisplayString | RO | mandatory | |||||||||
column · DisplayString · read-only · mandatory The hardware revision level of the HID | |||||||||||||
| CpduEhandleAutoLockTime | 1.3.6.1.4.1.318.1.1.32.9.1.1.8 | INTEGER | RW | mandatory | |||||||||
column · INTEGER · read-write · mandatory HID Electronic Latch Autolock Time in seconds, Value ranges (0-999) | |||||||||||||
| CpduEhandleDoorOpenTime | 1.3.6.1.4.1.318.1.1.32.9.1.1.9 | INTEGER | RW | mandatory | |||||||||
column · INTEGER · read-write · mandatory HID Door Open Time in seconds, Value ranges (0-999) | |||||||||||||
| CpduEhandleMaxDoorOpenTime | 1.3.6.1.4.1.318.1.1.32.9.1.1.10 | INTEGER | RW | mandatory | |||||||||
column · INTEGER · read-write · mandatory HID Max Door Open Time in seconds, Value ranges (0-32400), critical alarm will be raised if door is left open past this time | |||||||||||||
| CpduEhandleUserPinLength | 1.3.6.1.4.1.318.1.1.32.9.1.1.11 | INTEGER | RW | mandatory | |||||||||
column · INTEGER · read-write · mandatory Rack Access User minimum PIN Length, value ranges(1-15) | |||||||||||||
| CpduEhandleUserPinMode | 1.3.6.1.4.1.318.1.1.32.9.1.1.12 | INTEGER | RW | mandatory | |||||||||
column · INTEGER · read-write · mandatory Rack Access User PIN mode setting
| |||||||||||||
| CpduEhandleAisleControl | 1.3.6.1.4.1.318.1.1.32.9.1.1.13 | INTEGER | RW | mandatory | |||||||||
column · INTEGER · read-write · mandatory Rack Access Aisle Control setting, when set to standalone each aisle will controlled seprately, when set to combined opposite aisle can be controlled with authenticated control action on either aisle
| |||||||||||||
| TpduEhandleControlTable | 1.3.6.1.4.1.318.1.1.32.9.2 | NA | mandatory | ||||||||||
table · not-accessible · mandatory A list of smartcard. The number of entries are given by number of pdu and pduEhandleCount. | |||||||||||||
| RpduEhandleControlEntry | 1.3.6.1.4.1.318.1.1.32.9.2.1 | NA | mandatory | ||||||||||
row · not-accessible · mandatory The smart card table entry containing the usrname, cardid, cardaisle etc. | |||||||||||||
| CpduEhandleControlIndex | 1.3.6.1.4.1.318.1.1.32.9.2.1.1 | INTEGER (1..200) | RO | mandatory | |||||||||
column · INTEGER (1..200) · read-only · mandatory The index of the PDU smartcard table entry | |||||||||||||
| CpduEhandleControlUserName | 1.3.6.1.4.1.318.1.1.32.9.2.1.2 | DisplayString | RW | mandatory | |||||||||
column · DisplayString · read-write · mandatory User name of smartcard | |||||||||||||
| CpduEhandleControlCardIdStr | 1.3.6.1.4.1.318.1.1.32.9.2.1.3 | DisplayString | RW | mandatory | |||||||||
column · DisplayString · read-write · mandatory smartcard ID. | |||||||||||||
| CpduEhandleControlTimestamp | 1.3.6.1.4.1.318.1.1.32.9.2.1.4 | DisplayString | RO | mandatory | |||||||||
column · DisplayString · read-only · mandatory Indicates the date and time of accessing | |||||||||||||
| CpduEhandleControlCardAisle | 1.3.6.1.4.1.318.1.1.32.9.2.1.5 | INTEGER | RW | mandatory | |||||||||
column · INTEGER · read-write · mandatory Aisle of authorized card
| |||||||||||||
| CpduEhandleControlStartTime | 1.3.6.1.4.1.318.1.1.32.9.2.1.6 | DisplayString | RW | mandatory | |||||||||
column · DisplayString · read-write · mandatory Indicates the start date and time Rack access user is given access | |||||||||||||
| CpduEhandleControlExpireTime | 1.3.6.1.4.1.318.1.1.32.9.2.1.7 | DisplayString | RW | mandatory | |||||||||
column · DisplayString · read-write · mandatory Indicates the date and time when the access of user card will expire, To set expire time first set user as temporary user | |||||||||||||
| CpduEhandleControlTempUser | 1.3.6.1.4.1.318.1.1.32.9.2.1.8 | INTEGER | RW | mandatory | |||||||||
column · INTEGER · read-write · mandatory Indicates if the card user has temporary access
| |||||||||||||
| CpduEhandleControlPin | 1.3.6.1.4.1.318.1.1.32.9.2.1.9 | DisplayString | RW | mandatory | |||||||||
column · DisplayString · read-write · mandatory Rack acess control entry keypad PIN | |||||||||||||
Traps / Notifications
- trapCleared
1.3.6.1.4.1.318.1.1.32.8.4 - trapCritical
1.3.6.1.4.1.318.1.1.32.8.1 - trapInformation
1.3.6.1.4.1.318.1.1.32.8.3 - trapTest
1.3.6.1.4.1.318.1.1.32.8.5 - trapWarning
1.3.6.1.4.1.318.1.1.32.8.2