Argus-Power-System-MIB
Argus TechnologiesThis MIB defines the information block(s) available in CXC RMU as defined by the following list: - upsDevice: the CXC-series of controllers
snmptranslate -m Argus-Power-System-MIB -Tpsnmpwalk -v2c -c <community> -m Argus-Power-System-MIB <host> 1.3.6.1.4.1.7309Imports
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
|---|---|
| SNMPv2-SMI | Bits, Integer32, IpAddress, MODULE-IDENTITY, MibIdentifier, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, TimeTicks, Unsigned32, enterprises, iso |
| SNMPv2-TC | DisplayString, PhysAddress, TEXTUAL-CONVENTION |
OID tree
| Name | OID | Type | Access | Status |
|---|---|---|---|---|
| Iargus | 1.3.6.1.4.1.7309 | |||
identity This MIB defines the information block(s) available in CXC RMU as defined by the following list: - upsDevice: the CXC-series of controllers | ||||
| NupsPower | 1.3.6.1.4.1.7309.6 | |||
| NupsDevice | 1.3.6.1.4.1.7309.6.1 | |||
| NupsIdent | 1.3.6.1.4.1.7309.6.1.1 | |||
| SupsIdentManufacturer | 1.3.6.1.4.1.7309.6.1.1.1 | DisplayString (SIZE (0..255)) | RO | |
scalar · DisplayString (SIZE (0..255)) · read-only · current The name of the UPS manufacturer. | ||||
| SupsIdentProductCode | 1.3.6.1.4.1.7309.6.1.1.2 | DisplayString (SIZE (0..255)) | RO | |
scalar · DisplayString (SIZE (0..255)) · read-only · current The UPS Model designation. | ||||
| SupsIdentModel | 1.3.6.1.4.1.7309.6.1.1.3 | DisplayString (SIZE (0..255)) | RO | |
scalar · DisplayString (SIZE (0..255)) · read-only · current The UPS Product code designation. | ||||
| SupsIdentUPSSoftwareVersion | 1.3.6.1.4.1.7309.6.1.1.4 | DisplayString (SIZE (0..255)) | RO | |
scalar · DisplayString (SIZE (0..255)) · read-only · current The UPS firmware/software version(s). This variable may or may not have the same value as upsIdentAgentSoftwareVersion in some implementations. | ||||
| SupsIdentAgentSoftwareVersion | 1.3.6.1.4.1.7309.6.1.1.5 | DisplayString (SIZE (0..255)) | RO | |
scalar · DisplayString (SIZE (0..255)) · read-only · current The UPS agent software version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations. | ||||
| SupsIdentName | 1.3.6.1.4.1.7309.6.1.1.6 | DisplayString (SIZE (0..255)) | RO | |
scalar · DisplayString (SIZE (0..255)) · read-only · current A string identifying the UPS. This object should be set by the administrator. | ||||
| SupsIdentAttachedDevices | 1.3.6.1.4.1.7309.6.1.1.7 | DisplayString (SIZE (0..255)) | RO | |
scalar · DisplayString (SIZE (0..255)) · read-only · current A string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator. | ||||
| SupsIdentSiteName | 1.3.6.1.4.1.7309.6.1.1.8 | DisplayString (SIZE (0..255)) | RW | |
scalar · DisplayString (SIZE (0..255)) · read-write · current Site Name | ||||
| SupsIdentSiteCity | 1.3.6.1.4.1.7309.6.1.1.9 | DisplayString (SIZE (0..255)) | RW | |
scalar · DisplayString (SIZE (0..255)) · read-write · current Site City | ||||
| SupsIdentSiteRegion | 1.3.6.1.4.1.7309.6.1.1.10 | DisplayString (SIZE (0..255)) | RW | |
scalar · DisplayString (SIZE (0..255)) · read-write · current Site Region | ||||
| SupsIdentSiteCountry | 1.3.6.1.4.1.7309.6.1.1.11 | DisplayString (SIZE (0..255)) | RW | |
scalar · DisplayString (SIZE (0..255)) · read-write · current Site Country | ||||
| SupsIdentContactName | 1.3.6.1.4.1.7309.6.1.1.12 | DisplayString (SIZE (0..255)) | RW | |
scalar · DisplayString (SIZE (0..255)) · read-write · current Contact Name | ||||
| SupsIdentPhoneNumber | 1.3.6.1.4.1.7309.6.1.1.13 | DisplayString (SIZE (0..255)) | RW | |
scalar · DisplayString (SIZE (0..255)) · read-write · current Phone Number | ||||
| SupsIdentDate | 1.3.6.1.4.1.7309.6.1.1.14 | DisplayString (SIZE (0..255)) | RW | |
scalar · DisplayString (SIZE (0..255)) · read-write · current Date of the RMU-Novus | ||||
| SupsIdentTime | 1.3.6.1.4.1.7309.6.1.1.15 | DisplayString (SIZE (0..255)) | RW | |
scalar · DisplayString (SIZE (0..255)) · read-write · current Time of the RMU-Novus | ||||
| NupsBattery | 1.3.6.1.4.1.7309.6.1.2 | |||
| SupsBatteryStatus | 1.3.6.1.4.1.7309.6.1.2.1 | INTEGER | RO | |
scalar · INTEGER · read-only · current The indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfigLowBattTime. A value of batteryLow indicates that the remaining battery run-time is less than or equal to upsConfigLowBattTime. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output).
| ||||
| SupsMinutesOnBattery | 1.3.6.1.4.1.7309.6.1.2.2 | INTEGER | RO | |
scalar · INTEGER · read-only · current The accumulated elapsed time that the UPS system have been on battery.
| ||||
| SupsBatteryVoltage | 1.3.6.1.4.1.7309.6.1.2.3 | INTEGER | RO | |
scalar · INTEGER · read-only · current The magnitude of the present battery voltage.
| ||||
| SupsBatteryChargingCurrent | 1.3.6.1.4.1.7309.6.1.2.4 | INTEGER | RO | |
scalar · INTEGER · read-only · current The present battery charging current.
| ||||
| SupsBatteryCapacity | 1.3.6.1.4.1.7309.6.1.2.5 | INTEGER | RO | |
scalar · INTEGER · read-only · current The present battery capacity.
| ||||
| SupsBatteryTemperature | 1.3.6.1.4.1.7309.6.1.2.6 | INTEGER | RO | |
scalar · INTEGER · read-only · current The ambient temperature at or near the UPS Battery casing.
| ||||
| SupsBatteryLowWarning | 1.3.6.1.4.1.7309.6.1.2.7 | INTEGER | RW | |
scalar · INTEGER · read-write · current The set battery capacity percentage at which the unit will raise an alarm.
| ||||
| NupsInput | 1.3.6.1.4.1.7309.6.1.3 | |||
| SupsInputNumLines | 1.3.6.1.4.1.7309.6.1.3.1 | INTEGER | RO | |
scalar · INTEGER · read-only · current The number of input lines utilized in this device. This variable indicates the number of rows in the input table. | ||||
| TupsInputTable | 1.3.6.1.4.1.7309.6.1.3.2 | NA | ||
table · not-accessible · current A list of input table entries. The number of entries is given by the value of upsInputNumLines. | ||||
| RupsInputEntry | 1.3.6.1.4.1.7309.6.1.3.2.1 | NA | ||
row · not-accessible · current An entry containing information applicable to a particular input line.
| ||||
| CupsInputLineIndex | 1.3.6.1.4.1.7309.6.1.3.2.1.1 | INTEGER | NA | |
column · INTEGER · not-accessible · current The input line identifier. | ||||
| CupsInputFrequency | 1.3.6.1.4.1.7309.6.1.3.2.1.2 | INTEGER | RO | |
column · INTEGER · read-only · current The present input frequency.
| ||||
| CupsInputVoltage | 1.3.6.1.4.1.7309.6.1.3.2.1.3 | INTEGER | RO | |
column · INTEGER · read-only · current The magnitude of the present input voltage.
| ||||
| NupsOutput | 1.3.6.1.4.1.7309.6.1.4 | |||
| SupsOutputSource | 1.3.6.1.4.1.7309.6.1.4.1 | INTEGER | RO | |
scalar · INTEGER · read-only · current The present source of output power. The enumeration line(2) indicates that the Novus is in line mode.
| ||||
| SupsOutputFrequency | 1.3.6.1.4.1.7309.6.1.4.2 | INTEGER | RO | |
scalar · INTEGER · read-only · current The present output frequency.
| ||||
| SupsOutputNumLines | 1.3.6.1.4.1.7309.6.1.4.3 | INTEGER | RO | |
scalar · INTEGER · read-only · current The number of output lines utilized in this device. This variable indicates the number of rows in the output table. | ||||
| TupsOutputTable | 1.3.6.1.4.1.7309.6.1.4.4 | NA | ||
table · not-accessible · current A list of output table entries. The number of entries is given by the value of upsOutputNumLines. | ||||
| RupsOutputEntry | 1.3.6.1.4.1.7309.6.1.4.4.1 | NA | ||
row · not-accessible · current An entry containing information applicable to a particular output line.
| ||||
| CupsOutputLineIndex | 1.3.6.1.4.1.7309.6.1.4.4.1.1 | INTEGER | NA | |
column · INTEGER · not-accessible · current The output line identifier. | ||||
| CupsOutputVoltage | 1.3.6.1.4.1.7309.6.1.4.4.1.2 | INTEGER | RO | |
column · INTEGER · read-only · current The present output voltage.
| ||||
| CupsOutputCurrent | 1.3.6.1.4.1.7309.6.1.4.4.1.3 | INTEGER | RO | |
column · INTEGER · read-only · current The present output current.
| ||||
| CupsOutputPowerVA | 1.3.6.1.4.1.7309.6.1.4.4.1.4 | INTEGER | RO | |
column · INTEGER · read-only · current The present output VA.
| ||||
| CupsOutputPowerWatt | 1.3.6.1.4.1.7309.6.1.4.4.1.5 | INTEGER | RO | |
column · INTEGER · read-only · current The present output true power.
| ||||
| CupsPowerFactor | 1.3.6.1.4.1.7309.6.1.4.4.1.6 | INTEGER | RO | |
column · INTEGER · read-only · current The present power factor.
| ||||
| CupsOutputPercentLoad | 1.3.6.1.4.1.7309.6.1.4.4.1.7 | INTEGER (0..200) | RO | |
column · INTEGER (0..200) · read-only · current The percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA.
| ||||
| NupsAlarm | 1.3.6.1.4.1.7309.6.1.5 | |||
| SupsAlarmsPresent | 1.3.6.1.4.1.7309.6.1.5.1 | INTEGER | RO | |
scalar · INTEGER · read-only · current The present number of active alarm conditions. | ||||
| TupsAlarmTable | 1.3.6.1.4.1.7309.6.1.5.2 | NA | ||
table · not-accessible · current A list of alarm table entries. | ||||
| RupsAlarmEntry | 1.3.6.1.4.1.7309.6.1.5.2.1 | NA | ||
row · not-accessible · current An entry containing information applicable to a particular alarm.
| ||||
| CupsAlarmId | 1.3.6.1.4.1.7309.6.1.5.2.1.1 | INTEGER | NA | |
column · INTEGER · not-accessible · current A unique identifier for an alarm condition. This value must remain constant. | ||||
| CupsAlarmDescr | 1.3.6.1.4.1.7309.6.1.5.2.1.2 | DisplayString (SIZE (0..255)) | RO | |
column · DisplayString (SIZE (0..255)) · read-only · current A unique description of the alarm. | ||||
| CupsAlarmStatus | 1.3.6.1.4.1.7309.6.1.5.2.1.3 | INTEGER | RO | |
column · INTEGER · read-only · current 1 - ON or 0 - OFF. | ||||
| NupsConfig | 1.3.6.1.4.1.7309.6.1.6 | |||
| SupsConfigLineQualifyTime | 1.3.6.1.4.1.7309.6.1.6.1 | INTEGER | RO | |
scalar · INTEGER · read-only · current This objects displays the line qualify time.
| ||||
| SupsConfigLineOutputVoltageHighLimit | 1.3.6.1.4.1.7309.6.1.6.2 | INTEGER | RO | |
scalar · INTEGER · read-only · current This object represents the Line output High Voltage Limit.
| ||||
| SupsConfigLineOutputVoltageLowLimit | 1.3.6.1.4.1.7309.6.1.6.3 | INTEGER | RO | |
scalar · INTEGER · read-only · current This object represents the Line output Low Voltage Limit.
| ||||
| SupsConfigFanOnTemperature | 1.3.6.1.4.1.7309.6.1.6.4 | INTEGER | RO | |
scalar · INTEGER · read-only · current This object represents the Fan on temperature.
| ||||
| SupsShutdownStatus | 1.3.6.1.4.1.7309.6.1.6.5 | INTEGER | RW | |
scalar · INTEGER · read-write · current This object tells us if output is disabled or enabled. | ||||
| SupsInverterOffDelayTime | 1.3.6.1.4.1.7309.6.1.6.6 | INTEGER | RW | |
scalar · INTEGER · read-write · current This object represents the inverter off delay time.
| ||||
| SupsConfigIPAddress | 1.3.6.1.4.1.7309.6.1.6.7 | DisplayString (SIZE (0..255)) | RW | |
scalar · DisplayString (SIZE (0..255)) · read-write · current This objects displays the IP address of the RMU. | ||||
| SupsConfigNetMask | 1.3.6.1.4.1.7309.6.1.6.8 | DisplayString (SIZE (0..255)) | RW | |
scalar · DisplayString (SIZE (0..255)) · read-write · current This object displays the Net Mask of the RMU. | ||||
| SupsConfigGateway | 1.3.6.1.4.1.7309.6.1.6.9 | DisplayString (SIZE (0..255)) | RW | |
scalar · DisplayString (SIZE (0..255)) · read-write · current This object displays the Gateway of the RMU. | ||||
| SupsConfigSnmpCommunity | 1.3.6.1.4.1.7309.6.1.6.10 | DisplayString (SIZE (0..255)) | RW | |
scalar · DisplayString (SIZE (0..255)) · read-write · current This object displays the SNMP community | ||||
| SupsConfigSnmpTrapIPDestination | 1.3.6.1.4.1.7309.6.1.6.11 | DisplayString (SIZE (0..255)) | RW | |
scalar · DisplayString (SIZE (0..255)) · read-write · current This object displays the SNMP Trap IP destination. | ||||
| NupsTraps | 1.3.6.1.4.1.7309.6.1.7 | |||
| NupsTrap | 1.3.6.1.4.1.7309.6.1.7.0 | |||
| !upsAlarmTrap | 1.3.6.1.4.1.7309.6.1.7.0.1 | |||
notification · current A trap issued from a change in state in one of the Alarms on the Novus controller | ||||
| !upsAgentStartupTrap | 1.3.6.1.4.1.7309.6.1.7.0.2 | |||
notification · current A trap to indicate that the agent software has started up.
| ||||
| !upsAgentShutdownTrap | 1.3.6.1.4.1.7309.6.1.7.0.3 | |||
notification · current A trap to indicate that the agent software has shutdown.
| ||||
| !upsAgentFaultTrap | 1.3.6.1.4.1.7309.6.1.7.0.4 | |||
notification · current A trap issued from a change in state in one of the Faults on the Novus controller | ||||
| !upsAgentEventTrap | 1.3.6.1.4.1.7309.6.1.7.0.5 | |||
notification · current A trap issued from a change in state in one of the Events on the Novus controller | ||||
| NupsExtra | 1.3.6.1.4.1.7309.6.1.8 | |||
| SupsExtraCount | 1.3.6.1.4.1.7309.6.1.8.1 | INTEGER (0..65535) | RO | |
scalar · INTEGER (0..65535) · read-only · current Number of extra variables | ||||
| TupsExtraTable | 1.3.6.1.4.1.7309.6.1.8.2 | NA | ||
table · not-accessible · current A table of CXC upstem controller extra variables | ||||
| RupsExtraEntry | 1.3.6.1.4.1.7309.6.1.8.2.1 | NA | ||
row · not-accessible · current An entry into the CXC upstem controller extra variable table
| ||||
| CupsExtraIndex | 1.3.6.1.4.1.7309.6.1.8.2.1.1 | INTEGER (0..65535) | RO | |
column · INTEGER (0..65535) · read-only · current The index of the extra variable in the CXC upstem controller table | ||||
| CupsExtraName | 1.3.6.1.4.1.7309.6.1.8.2.1.2 | DisplayString (SIZE (0..30)) | RO | |
column · DisplayString (SIZE (0..30)) · read-only · current The description of the extra variable as reported by the CXC upstem controller | ||||
| CupsExtraIntegerValue | 1.3.6.1.4.1.7309.6.1.8.2.1.3 | INTEGER (-1000000000..1000000000) | RO | |
column · INTEGER (-1000000000..1000000000) · read-only · current The integer value of the extra variable as reported by the CXC upstem controller | ||||
| CupsExtraStringValue | 1.3.6.1.4.1.7309.6.1.8.2.1.4 | DisplayString (SIZE (0..255)) | RO | |
column · DisplayString (SIZE (0..255)) · read-only · current The string value of the extra variable as reported by the CXC upstem controller | ||||
Textual conventions
NonNegativeIntegerINTEGER (0..2147483647)Display hint:
dThis data type is a non-negative value.
PositiveIntegerINTEGER (1..2147483647)Display hint:
dThis data type is a non-zero and non-negative value.
Traps / Notifications
- upsAgentEventTrap
1.3.6.1.4.1.7309.6.1.7.0.5 - upsAgentFaultTrap
1.3.6.1.4.1.7309.6.1.7.0.4 - upsAgentShutdownTrap
1.3.6.1.4.1.7309.6.1.7.0.3 - upsAgentStartupTrap
1.3.6.1.4.1.7309.6.1.7.0.2 - upsAlarmTrap
1.3.6.1.4.1.7309.6.1.7.0.1